Section 2340.5 - Conductors

Universal Citation: 8 CA Code of Regs 2340.5

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Insulation. All conductors used for general wiring shall be insulated unless otherwise permitted in these safety orders.

(b) Type. The conductor insulation shall be of a type that is approved for the voltage, operating temperature, and location of use.

(c) Distinguishable. Insulated conductors shall be distinguishable by appropriate color or other suitable means as being grounded conductors, ungrounded conductors, or equipment grounding conductors.

1. New section filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19). For prior history, see Register 79, No. 12.

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.