Section 2320.2 - Energized Equipment or Systems
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Work shall not be performed on exposed energized parts of equipment or systems until the following conditions are met:
EXCEPTION: The use of approved insulating gloves or insulated tools or other protective measures are not required when working on exposed parts of equipment or systems energized at less than 50 volts provided a conclusive determination has been made prior to the start of work by a qualified person that there will be no employee exposure to electrical shock, electrical burns, explosion or hazards due to electric arcs.
NOTE: The ASTM F 496-08 standard contains provisions regarding the care, inspection, testing and use of insulating gloves and sleeves. Among other requirements, this standard provides that electrical retests shall not exceed 6 months for insulating gloves and 12 months for insulating sleeves and that insulating gloves and sleeves that have been electrically tested but not issued for service shall not be placed into service unless they have been electrically tested within the previous twelve months.
NOTE: to subsection (a)(8): See Section 2320.11 for protection from flames and electric arcs that apply to power generation, transmission and distribution.
(b) Making Connections. The employer shall ensure that employees make connections as follows:
(c) After the required work on an energized system or equipment has been completed, an authorized person shall be responsible for:
(d) Minimum Approach Distance. The employer shall ensure that no employee takes a conductive object closer to exposed energized parts than the established minimum approach distances unless:
Minimum Approach Distances |
||
Voltage (V) | Phase to Ground | Phase to Phase |
0-300 | Avoid contact | Avoid contact |
301-600 | 1 foot 1 inch | 1 foot 1 inch |
NOTE: For voltages greater than 600 Volts, see Section 2940.2.
1. Editorial correction adding NOTE filed 11-2-83 (Register 83, No. 45).
2. Amendment of subsection (a)(3) filed 8-27-86; effective thirtieth day thereafter (Register 86. No. 37).
3. Amendment of subsection (a)(3), new subsection (a)(4), subsection renumbering, and amendment of newly designated subsection (a)(6) filed 1-16-2001; operative 2-15-2001 (Register 2001, No. 3).
4. New subsection (a)(7) filed 8-27-2001; operative 9-26-2001 (Register 2001, No. 35).
5. Amendment filed 4-22-2002; operative 5-22-2002 (Register 2002, No. 17).
6. Amendment of subsections (a)(3)-(a)(3)(B) filed 10-9-2007; operative 11-8-2007 (Register 2007, No. 41).
7. Amendment filed 2-27-2018; operative 4-1-2018 (Register 2018, No. 9).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.