California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 1 - Low-Voltage Electrical Safety Orders
Article 13 - Temporary Wiring
Section 2405.4 - Ground-Fault Circuit Protection-Construction Site
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) General. For purposes of this Section, a construction site is a place of employment where erection, demolition, alteration or excavation is being performed on a building, structure or underground facility, other than mining.
(b) Construction Sites. To protect employees on construction sites, the employer shall use either or both ground-fault circuit interrupters as specified in Subsection (c) of this Section or an assured equipment grounding conductor program as specified in Subsection (d) of this Section. These requirements are in addition to any other requirements for equipment grounding conductors.
(c) Ground-Fault Circuit Interrupters. All 120-volt, AC, single-phase, 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single phase portable or vehicle-mounted generator rated not more than 5 KW, where the circuit conductors of the generator are insulated from the generator frame and all their grounded surfaces, need not be protected with ground-fault circuit interrupters.
Feeders supplying 15- and 20-ampere receptacle branch circuits shall be permitted to be protected by a ground-fault circuit interrupter approved for the purpose in lieu of the above provisions.
(d) Assured Equipment Grounding Conductor Program. The employer shall establish and implement an assured equipment grounding conductor program on construction sites covering all cord sets, receptacles which are not a part of the permanent wiring of the building or structure and equipment connected by cord and plug, which are available for use or used by employees. This program shall comply with the following minimum requirements:
NOTE: Double-insulated tools or other similar equipment are not required to be grounded. See Section 2395.45 Exception 2.
1. Amendment of subsection (b) filed 11-16-79; effective thirtieth day thereafter (Register 79, No. 46).
2. Amendment of subsection (d)(5)(D) filed 2-1-83; effective thirtieth day thereafter (Register 83, No. 6).
3. Amendment of subsections (a), (d) and (d)(4) filed 4-6-2010; operative 5-6-2010 (Register 2010, No. 15).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.