California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 5 - Electrical Safety Orders
Group 1 - Low-Voltage Electrical Safety Orders
Article 11 - Grounding
Section 2395.3 - Direct-Current Systems

Universal Citation: 8 CA Code of Regs 2395.3

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Systems to be Grounded. Systems that supply premises wiring shall be grounded as follows:

(a) Two-Wire Direct Current Systems. Two-wire DC systems operating at over 50 volts through 300 volts between conductors shall be grounded.

EXCEPTIONS:

1. A system equipped with a ground detector and supplying only industrial equipment in limited areas.

2. A rectifier derived DC system supplied from a grounded AC system.

3. DC Fire Alarm Circuits having a maximum current of 0.030 amperes.

(b) Three-Wire Direct-Current Systems. The neutral conductor of all 3-wire DC systems shall be grounded.

1. Editorial correction filed 11-2-83 (Register 83, No. 45).
2. Amendment of section and NOTE filed 5-5-2008; operative 5-5-2008. Submitted to OAL for printing only pursuant to Labor Code 142.3(a)(3) (Register 2008, No. 19).

Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.