GROUNDING CONDUCTORS
Section 2395.114 - Continuity and Attachment of Branch-Circuit Equipment Grounding Conductors to Boxes
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
Where more than one equipment grounding conductor of a branch circuit enters a box, all such conductors shall be in good electrical contact with each other and the arrangement shall be such that the disconnection or removal of a receptacle, fixture, or other device fed from the box will not interfere with or interrupt the grounding continuity.
(a) Metal Boxes. A connection shall be made between the one or more equipment grounding conductors and a metal box by means of a grounding screw which shall be used for no other purpose, or an approved grounding device.
(b) Nonmetallic Boxes. One or more equipment grounding conductors brought into a nonmetallic outlet box shall be so arranged that a connection can be made to any fitting or device in that box requiring grounding.
(Title 24, Part 3, Section 250-114.)