Section 1922 - Portable Fire Fighting Equipment
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Fire Extinguishers and Small Hose Lines.
One 55-gallon open container of water with two fire pails may be substituted for a fire extinguisher having a 2A rating.
A 3/4 -inch diameter garden-type hose line, not to exceed 75 feet in length and equipped with an adjustable nozzle, may be substituted for a 2A-rated fire extinguisher, provided it is connected to a reliable water pressure system capable of discharging a minimum, continuous flow of 5 gallons per minute with a minimum hose stream range of 30 feet horizontally. The garden-type hose lines shall be mounted on conventional racks or reels. The number and location of hose racks or reels shall be such that at least one hose stream can be applied to all points in the floor area.
At least one fire extinguisher rated not less than 2A, shall be provided on each floor. In multi-story buildings, at least one fire extinguisher shall be located adjacent to the stairway at each floor level.
EXCEPTION: Single family residential dwellings other than apartments, lodging houses, hotels or dormitories provided that there is at least one fire extinguisher rated not less than 2A, or the equivalent, available at the job site during working hours.
NOTE: Inspection is a "quick check" that an extinguisher is available and will operate. It is intended to give reasonable assurance that the extinguisher is fully charged and operable. This is done by seeing that it is in its designated place, that it has not been actuated or tampered with, and that there is no obvious or physical damage or condition to prevent operation.
NOTE: Service as defined in the State Fire Marshal's regulations pertains to the act of charging, recharging, inspecting, repairing, and hydrostatic testing of any portable fire extinguisher.
(b) Fire Hose and Connections.
NOTE: For demolition in construction, see Section 1737, "Fire Prevention."
1. Amendment of subsection (a) filed 3-19-79; effective thirtieth day thereafter (Register 79, No. 12).
2. Editorial correction of subsection (a)(4) filed 6-10-83 (Register 83, No. 24).
3. Amendment of subsection (a) filed 10-9-86; effective thirtieth day thereafter (Register 86, No. 43).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.