California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 2 - Boiler and Fired Pressure Vessel Safety Orders
Article 6 - Operation
Section 782 - Safe Practices
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) The following Safety Orders from Title 8, California Administrative Code are hereby made a part of these orders:
(b) All fired boilers, not included in Sections 763 and 771, equipped with controls to permit the burners to be ignited automatically shall be equipped with a full safety pilot or other device that will provide equivalent safety. Such safety pilot or other device shall be of a type that will de-energize the electrical circuit and/or cause the main burner fuel valve to close within the following burner input and time limits.
400,000 BTU/HR and under.......................... | ..........................90 seconds |
400,001 to 2,500,000 BTU/HR.......................... | ..........................9 seconds |
Over 2,500,000 BTU/HR.......................... | ..........................5 seconds |
(c) All dampers used in smokestacks of boilers which use natural draft shall have suitable openings to vent the furnace.
(d) When portable electric lights are used inside any boiler or pressure vessel they shall be equipped with a vaportight globe, substantial guard, rugged nonconducting lamp holder and handle, and shall have type S cord or equivalent sufficiently long to reach to a plug-in or junction box outside the vessel.
1. Repealer and new subsection (b) filed 8-12-76; effective thirtieth day thereafter (Register 76, No. 33). For prior history, see Register 74, No. 42.
2. Amendment of subsection (a) filed 12-14-76; effective thirtieth day thereafter (Register 76, No. 51).