California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 2 - Boiler and Fired Pressure Vessel Safety Orders
Article 5 - Inspection
Section 770 - Boilers Subject to Annual Inspection
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) All boilers subject to these Orders are subject to annual internal and external inspection, except as provided in subsection (b), and except those boilers exempted from annual inspection in Section 771.
(b) Boilers installed in turboelectric plants in such a manner that each boiler furnishes steam to a single turbine only shall be inspected internally at least once each eighteen (18) months. The permit to operate issued following internal inspection shall expire not more than twelve (12) months after the date of inspection. The boiler shall be externally inspected prior to or on the expiration date of the permit by a qualified inspector who may, if conditions warrant, issue a temporary permit which shall expire not more than six (6) months after the date of external inspection. A copy of the external inspection report shall be forwarded to the Division by the qualified inspector. Such report shall show the expiration date of the temporary permit to operate.
The Division, upon individual application from petroleum companies, chemical plants, public utilities or other industries considered by the Division as having superior preventive maintenance and examination programs, may grant a maximum interval of thirty-six (36) months between internal inspection of fired boilers. A fired boiler is defined for this section as one whose temperature input can cause metallurgical damage to the boiler, or whose combustion of fuel can cause a furnace explosion. For boilers other than fired boilers, the Division may grant a maximum interval of seventy-two (72) months between internal inspections, provided the temperature input cannot cause metallurgical damage. Boilers of the latter type are typically called process steam generators. Such applications, to be reviewed by the Division, shall contain as a minimum the following information and proposals:
Boilers operating longer than twenty-four (24) months between internal inspections shall have a program of on-stream examination of corrosion points, and inspection of operations and safety controls that is acceptable to the Division, and the certified inspection agency. The maximum interval of each temporary permit shall be six (6) months.
If the boiler is located within a local jurisdiction that has regulations concerning boiler inspections, the jurisdiction must also be consulted concerning the acceptability of the inspection program.
The certified inspector shall submit reports to the Division of each external inspection, noting the expiration date of the permit issued, and recording any unusual condition found. The inspection report shall include a statement that water treatment records have been reviewed. Reports of on-stream wall thickness readings must also be submitted to the Division via the certified inspector.
1. Amendment of subsection (b) filed 10-25-74; effective thirtieth day thereafter (Register 74, No. 43).
2. Amendment of section and new NOTE filed 8-2-2005; operative 9-1-2005 (Register 2005, No. 31).
Note: Authority cited: Sections 142.3 and 7682, Labor Code. Reference: Sections 142.3 and 7682, Labor Code.