(a) Combustible liquids and gases shall be stored at least 100 feet from the following:

(1) Mine openings

(2) Buildings and snow sheds connected to mine openings

(3) Ventilation fan houses

(4) Hoist houses

(5) Explosive magazines

The storage place shall be located where contents of leaking containers cannot run over the surface to any point within 100 feet of the above-mentioned places and structures.

NOTE: Certain petroleum gases, such as butane and propane, are compressed to liquid form in pressure tanks. When a tank containing liquefied petroleum gases leaks or is ruptured, the contents vaporize in the atmosphere. These vapors are heavier than air and will flow downhill over the surface of the ground much like water until the vapors are diffused. For this reason tanks containing liquefied petroleum gases must be stored at locations which are in compliance with the provisions of this section.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.