Section 6816 - Blinding or Isolating of Pipe Lines and Equipment for Entry
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Isolation of equipment shall be accomplished by blinding or disconnecting and disaligning. Where equipment, operations or conditions will not allow blinding or disconnecting and disaligning, double blocking with a bleeder (located between the block valves) may be utilized to isolate pipelines or equipment under the following conditions:
(b) Cold water, air and foam lines need not be blinded or disconnected, but shall be provided with block valves.
(c) Blinds shall be of sufficient strength and so installed as to provide safe conditions of pressure, temperature and service.
(d) Lines which are blinded shall be clearly identified.