California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 1 - Unfired Pressure Vessel Safety Orders
Article 6 - Anhydrous Ammonia
Section 502 - Warning Signs

Universal Citation: 8 CA Code of Regs 502

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Except as noted in Section 502 (b), all anhydrous ammonia tanks 60 gallons capacity or more shall have warning signs provided on at least 2 sides with the words "Caution--Ammonia" in sharply contrasting colors, with letters at least 1/12 of the tank diameter in height, but need not be in excess of 1 1/2 inches for tanks 500 gallons capacity or less or 4 inches for tanks exceeding 500 gallons capacity.

(b) All tanks used for the transportation of ammonia on the highways shall be marked as specified by the DOT and adopted by Section 1222, California Administrative Code, under authority of Section 34500, Vehicle Code. These markings also will be acceptable to the Division in lieu of the markings required under Section 502 (a) for such tanks in off-highway service.

(c) Uninsulated containers shall have a highly reflective surface maintained in good condition.

1. Amendment filed 12-8-72 as procedural and organizational; effective upon filing (Register 72, No. 50).
2. New subsection (c) filed 3-28-75; effective thirtieth day thereafter (Register 75, No. 13).

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.