California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 1 - Unfired Pressure Vessel Safety Orders
Article 5 - LP-Gas Systems
Section 475 - Location of Storage Containers and Regulating Equipment
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) A single container of 575 gallons or less water capacity can be located 10 feet from an important building providing such container is at least 25 feet from any other container of more than 125 gallons water capacity. For important buildings constructed of concrete or masonry materials with no overhanging roof:
(b) No stationary storage container shall be located less than 10 feet from the nearest street line or sidewalk, or less than 50 feet from the center line of any railroad main track.
(c) Installation of stationary LP-Gas containers on the rooftop shall be prohibited.
1. Amendment filed 4-1-77; effective thirtieth day thereafter (Register 77, No. 14). For prior history, see Register 76, No. 32.
2. New subsection (g) filed 9-11-81; effective thirtieth day thereafter (Register 81, No. 37).
3. Amendment filed 4-13-82; effective thirtieth day thereafter (Register 82, No. 16).
4. Amendment of subsection (a) filed 9-3-82; effective thirtieth day thereafter (Register 82, No. 36).
5. Amendment of section and NOTE filed 12-4-96; operative 1-3-97 (Register 96, No. 49).
6. New subsection (c) filed 1-30-2002; operative 3-1-2002 (Register 2002, No. 5).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code; and Section 13241, Health and Safety Code.