Section 473 - Gauging Devices
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) A permanent dip pipe or a fixed level gauge shall be installed in all containers filled by volume and shall be of such length or position that it will indicate when the tank is 86 1/2 percent full.
(b) Each tank 125-gallon capacity or more, filled by volume, shall be equipped with a liquid level gauging device, such as a rotary gauge, magnetic gage, or series of fixed pipes, in addition to the fixed dip pipe required in Section 473(a).
(c) Each tank having an allowable working pressure of less than 250 psi shall have a thermometer well. This Order does not apply to tanks built before January 1, 1946, or to code tanks constructed in accordance with Paragraphs U-68, U-69, and UW-52 (b) for a working pressure of 200 psi or more. The thermometer well shall be plugged or capped when not in use to prevent the entrance of moisture and the resulting hazard of corrosion.