California Code of Regulations
Title 8 - Industrial Relations
Division 1 - Department of Industrial Relations
Chapter 4 - Division of Industrial Safety
Subchapter 1 - Unfired Pressure Vessel Safety Orders
Appendix A - Minimum Capacity Requirement of Relief Valves for Fire Exposure for Liquefied Natural Gas Tanks and Vaporizers

Universal Citation: 8 CA Code of Regs A
Current through Register 2024 Notice Reg. No. 38, September 20, 2024

A1. The minimum total heat influx during a possible fire exposure of an insulated container shall be computed by the applicable formula:

NOTE: Equation (1) shall be used for vaporizers with external insulation and Equation (2) for uninsulated vaporizers. The value of A is obtained by adding the area of the shell in contact with LN-Gas and the area of heat exchange surface in contact with LN-Gas.

(1) H = 1560C1A0.82+ Hn

where:

H = Total heat influx, Btu per hour.

C1 = Conductance of the insulation, Btu/sq. ft.-hr.-deg. F. (The value of C increases with temperature and a mean value for the range from -260 F to +1660 F should be used.)

A = Total exposed wetted surface area in sq. ft.

Hn = Total normal heat gain to the stored liquid without fire exposures and at maximum ambient temperatures, Btu per hour.

A2. If the insulation system, including any jacketing material, is such that it will disappear, deteriorate or dislodge in an exposure fire, a higher heat gain will occur. This requires special consideration depending upon the extent of loss of the insulating properties. If only a part of the insulation is lost, the heat gain may be estimated by the formula:

(2) H = (34,500 - 360C2)A0.82+ Hn

In this case, the value of C2 should be the mean value for the range from -260° F to +100° F.

A3. The required relief valve capacity shall be computed by the formula

(3) Qa = 3.09(H/L)Y(T/M)

where:

Qa = Required flow capacity of air, cu. ft. per hour at 60 F and 14.7 psia.

H = Total heat influx, Btu per hour from the formula (1) or (2).

L = Latent heat of vaporization of the stored liquid, Btu per lb. (219 may be used for LN-Gas).

T = Absolute temperature of the gas at the relief valve inlet, deg. R.

M = Molecular weight of the gas (16.0 may be used for LNG).

1. Relocation of Appendix A filed 12-14-76; effective thirtieth day thereafter (Register 76, No. 51).

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.