California Code of Regulations
Title 25 - Housing and Community Development
Division 1 - Housing and Community Development
Chapter 2 - Mobilehome Parks and Installations
Article 4 - Fuel Gas and Oil Requirements
Section 1230 - Required Gas Supply
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) The minimum hourly volume of gas required at each lot outlet, or any section of a park gas piping system shall be calculated as shown in Table 1230-1.
(b) Required gas supply for other fuel gas consuming appliances connected to the park gas piping system shall be calculated as provided in the California Plumbing Code, Chapter 12.
Table 1230-1 Demand Factors for Use in Calculating Gas Piping Systems in Parks |
|||
Number of Lots |
BTU Per Hours Per Lot |
||
1 | 125,000 | ||
2 | 117,000 | ||
3 | 104,000 | ||
4 | 96,000 | ||
5 | 92,000 | ||
6 | 87,000 | ||
7 | 83,000 | ||
8 | 81,000 | ||
9 | 79,000 | ||
10 | 77,000 | ||
11-20 | 66,000 | ||
21-30 | 62,000 | ||
31-40 | 58,000 | ||
41-60 | 55,000 | ||
Over 60 | 50,000 |
1. Amendment of subsection (b) filed 8-22-85; effective upon filing pursuant to Government Code Section 11346.2(d) (Register 85, No. 36).
2. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18690, Health and Safety Code.