California Code of Regulations
Title 25 - Housing and Community Development
Division 1 - Housing and Community Development
Chapter 2 - Mobilehome Parks and Installations
Article 4 - Fuel Gas and Oil Requirements
Section 1226 - Gas Meters
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) When gas meters are installed, they shall not depend on the gas riser outlet for support. Gas meters shall be adequately supported by a post and bracket or by other means approved by the enforcement agency.
(b) Meters shall not be installed beneath units, in unventilated or inaccessible locations, or closer than three (3) feet from sources of ignition. The unit electrical service equipment shall not be considered a source of ignition when not enclosed in the same compartment with a gas meter.
(c) All gas meter installations shall be provided with a shutoff valve or cock located adjacent to and on the inlet side of the meter. In the case of a single meter installation utilizing a LPG tank, the tank service valve may be used in lieu of the shutoff valve or cock.
(d) Each meter installed shall be in a readily accessible location and shall be provided with unions or other fittings so as to be easily removed and replaced while maintaining an upright position.
(e) Parks constructed after January 1, 1997, shall have individual gas meters for each lot and shall be served by gas distribution facilities owned, operated, and maintained by the gas corporation, as defined in section 222 of the Public Utilities Code, providing gas service in the area.
1. Amendment of subsection (c) filed 8-22-85; effective upon filing pursuant to Government Code Section 11346.2(d) (Register 85, No. 36).
2. Amendment of section and NOTE filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
Note: Authority cited: Sections 18300 and 18690, Health and Safety Code. Reference: Section 18690, Health and Safety Code; and Section 2791, Public Utilities Code.