California Code of Regulations
Title 25 - Housing and Community Development
Division 1 - Housing and Community Development
Chapter 2 - Mobilehome Parks and Installations
Article 3 - Electrical Requirements
Section 1183 - Access to Electrical Equipment
All park or lot service equipment shall be accessible by an unobstructed entrance or passageway not less than twenty-four (24) inches in width and seventy-eight (78) inches high and shall have a working space not less than thirty (30) inches wide and thirty-six (36) inches deep in front of any panel opening on the service equipment used for examination, servicing, adjustment, or maintenance. The lot service equipment shall be located and maintained not less than twelve (12) inches nor more than seventy-eight (78) inches above the stabilizing pad.
EXCEPTION: parks constructed prior to July 1, 1979, shall have a working space not less than thirty (30) inches wide and thirty (30) inches deep in front of and centered on the service equipment.
1. Renumbering of former section 1646 to new section 1183, including amendment of section, filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
2. Amendment filed 7-22-2005; operative 7-22-2005 pursuant to Government Code section 11343.4 (Register 2005, No. 29).
3. Editorial correction of HISTORY 2 (Register 2005, No. 33).
4. Amendment filed 1-21-2009; operative 1-21-2009 pursuant to Government Code section 11343.4 (Register 2009, No. 4).
Note: Authority cited: Section 18300, Health and Safety Code. Reference: Sections 18550 and 18670, Health and Safety Code.