California Code of Regulations
Title 25 - Housing and Community Development
Division 1 - Housing and Community Development
Chapter 2 - Mobilehome Parks and Installations
Article 3 - Electrical Requirements
Section 1150 - Park Electrical Disconnecting Means

Universal Citation: 25 CA Code of Regs 1150

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Each service equipment enclosure for the park shall be provided with a single main disconnect switch or circuit breaker lockable in the open position for disconnecting the electrical wiring system or systems of the park.

(b) A disconnecting means shall be provided for disconnecting each distribution transformer. When the disconnecting means is not installed immediately adjacent to the distribution transformer, it shall be identified as to its usage and shall be arranged to be locked in the open position.

1. Amendment of section heading and section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).

Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.