Section 1146 - Voltage Drop
Universal Citation: 25 CA Code of Regs 1146
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
The voltage drop shall not exceed five (5) percent on the park electrical wiring system from the park service to the most remote outlet on the system, except that taps to compensate for below normal full capacity voltage may be used on the primary side of secondary distribution transformers to correct for voltage drop on the primary feeders. The voltage of secondary systems shall not exceed a nominal 240 volts.
1. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.
Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.