(a) Connections of aluminum conductors shall be made only inside boxes or equipment enclosures which are designed and installed to prevent the entry or accumulation of moisture within the enclosure.

(b) Only connectors which are listed for use with aluminum conductors shall be used to connect aluminum conductors. If more than one conductor is connected to a connector, the connector shall be provided with a terminal fitting for each conductor.

(c) Prior to inserting an aluminum conductor into the connector, the conductor from which the insulation has been removed shall be wire-brushed and sealed with an approved oxide-inhibiting joint compound.

1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).

Note: Authority cited: Section 18865, Health and Safety Code. Reference: Section 18873.3, Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.