California Code of Regulations
Title 25 - Housing and Community Development
Division 1 - Housing and Community Development
Chapter 2.2 - Special Occupancy Parks
Article 3 - Electrical Requirements
Section 2152 - Ground-Fault Protection

Universal Citation: 25 CA Code of Regs 2152
Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Ground-fault protection of park service equipment shall be provided for solidly grounded wye electrical services of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase for each service disconnecting means rated at 1,000 amperes or more. Each service disconnecting means rated 1000-amperes or more shall be performance tested when first installed, as required by the California Electrical Code, Section 230-95. The test shall be conducted in accordance with approved instructions, which shall be provided with the equipment. A written record of this test shall be made and shall be available to the enforcement agency.

1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
2. Amendment filed 7-22-2005; operative 7-22-2005 pursuant to Government Code section 11343.4 (Register 2005, No. 29).
3. Editorial correction of HISTORY 2 (Register 2005, No. 33).

Note: Authority cited: Section 18865, Health and Safety Code. Reference: Section 18873.3, Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.