California Code of Regulations
Title 25 - Housing and Community Development
Division 1 - Housing and Community Development
Chapter 2.2 - Special Occupancy Parks
Article 3 - Electrical Requirements
Section 2136 - Conductors and Equipment

Universal Citation: 25 CA Code of Regs 2136

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) Six-hundred (600) volts or less. For purposes of this chapter, all electrical conductors and equipment rated at 600 volts or less, installed outside of permanent buildings in park electrical wiring systems constructed, or approved for construction, shall be listed and labeled as approved for their intended use.

(b) Greater than 600 volts. Conductors and equipment installed in systems operated at more than 600 volts shall comply with the applicable provisions contained in the California Electrical Code, Article 490, and the High Voltage Safety Orders contained in Title 8, California Code of Regulations, Chapter 4, Subchapter 5, Group 2.

(c) A grounded neutral conductor may be a bare conductor when properly isolated from phase conductors. A bare neutral conductor, or a bare concentric stranded conductor of a cable used as a grounded neutral conductor, shall be copper when installed underground. These types of systems shall be solidly grounded.

1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).

Note: Authority cited: Section 18865, Health and Safety Code. Reference: Section 18873.3, Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.