California Code of Regulations
Title 23 - Waters
Division 1 - Central Valley Flood Protection Board
Chapter 1 - Organization, Powers and Standards
Article 8 - Standards
Section 122 - Irrigation and Drainage Ditches, Tile Drains, and Septic Systems
Universal Citation: 23 CA Code of Regs 122
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) Irrigation ditches, drainage ditches, and similar facilities must satisfy the following criteria:
(1) All ditches must be located at least ten (10) feet from the levee toe.
(2) The bottom of any agricultural ditch must be located above the projected levee slope. Accordingly, a deep ditch may need to be located farther than the minimum ten (10) feet from the levee toe. (See Figure 8.01.)
(b) Tile drains, septic systems, and similar facilities must satisfy the following criteria:
(1) All tile drains, septic tanks, or leach fields must be located at least ten (10) feet from the levee toe.
(2) The bottom of any tile drain, septic tank, or leach field must be located above the projected levee slope.
(3) Positive closure valves may be required on a tile drain pipeline to prevent backflow.
1. New section filed 9-30-96; operative 10-30-96 (Register 96, No. 40).
Note: Authority cited: Section 8571, Water Code. Reference: Sections 8608 and 8710, Water Code.
Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.