TEST REQUIREMENTS FOR EXTERIOR FLAME-RETARDANT CHEMICALS (WHEN APPLIED TO STANDARD TEST FABRIC)
Section 1237 - Fire Resistance

Universal Citation: 19 CA Code of Regs 1237
Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(Small Scale Test.) The treated fabric, in its original state, after accelerated weathering, and after water extraction, shall be tested in accordance with the method outlined in Section 1237.1 below, and shall not continue to flame for more than two (2) seconds after the burner is removed. The average length of char (for the standard test fabric) shall not exceed three and one-half inches (3 1/2"). The maximum for any fabric shall not exceed six inches (6").

1. Repealer and new section filed 11-10-60; effective thirtieth day thereafter (Register 60, No. 23).

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.