California Code of Regulations
Title 19 - Public Safety
Division 1 - State Fire Marshal
Chapter 3 - Fire Extinguishers
Article 7 - Hydrostatic Testing
Table 5 - Hydrostatic Test Interval for Extinguishers
Universal Citation: 19 CA Code of Regs 5
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
Extinguisher type | Test Interval (Years) | |
Stored Pressure Water and/or Antifreeze/Loaded Stream | 5 | |
AFFF (Aqueous Film Forming Foam) | 5 | |
FFFP (Film Forming Fluoroprotein Foam) | 5 | |
Wet Chemical | 5 | |
Dry Chemical with Stainless Steel Shells | 5 | |
Carbon Dioxide | 5 | |
Dry Chemical, Stored Pressure with Mild Steel Shells, Brazed Brass Shells, or Aluminum Shells | 12 | |
Dry Chemical, Cartridge and Cylinder-Operated, with Mild Steel Shells | 12 | |
Halogenated Agents | 12 | |
Dry Powder, stored pressure, cartridge- or cylinder-operated with mild steel shells | 12 |
1. Amendment filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52). For prior history, see Register 92, No. 15.
Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.