Section 592.1 - Compressed Gas Cylinders and Cartridges

Universal Citation: 19 CA Code of Regs 592.1
Current through Register 2024 Notice Reg. No. 38, September 20, 2024

Nitrogen cylinders or cartridges used for inert gas storage used as an expellant for wheeled extinguishers shall be hydrostatically tested every five years.

EXCEPTION: Cylinders (except those charged with carbon dioxide) complying with Section 180.209(b), Title 49, Code of Federal Regulations, shall be hydrostatically tested every 10 years.

1. New section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
2. Amendment of EXCEPTION filed 7-17-2013; operative 10-1-2013 (Register 2013, No. 29).

Note: Authority cited: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.