California Code of Regulations
Title 19 - Public Safety
Division 1 - State Fire Marshal
Chapter 3 - Fire Extinguishers
Article 6 - Inspection, Maintenance and Recharging
Section 578.10 - Leak Test

Universal Citation: 19 CA Code of Regs 578.10

Current through Register 2024 Notice Reg. No. 38, September 20, 2024

(a) After charging, a leak test shall be performed on all stored pressure and self-expelling type fire extinguishers. Leak tests shall be performed by following the manufacture's requirements and may include applying a leak test solution or a solution of soapy water.

(b) Leak testing of halogenated agent extinguishers shall not use water. A halogenated gas leak detector shall be used to determine leakage.

1. New section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
2. Repealer of former section 578.10 and renumbering and amendment of former section 578.12 to section 578.10 filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
3. Amendment of subsection (a) filed 11-21-2002; operative 1-1-2003 (Register 2002, No. 47).

Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.