Extinguishing Agent Extinguisher type and size Old Classification Approximate Present -- Classification
(a) Chemical solution (1) 1 1/4, 1 1/2 gallon A-2 1-A
(soda-acid) (2) 2 1/2 gallon A-1 2-A
(3) 17 gallon A 10-A
(4) 33 gallon A 20-A
(b) Water (1) 1 1/2, 1 3/4 gallon (pump or pressure) A-2 1-A
(2) 2 1/2 gallon (pump or pressure) A-1 2-A
(3) 4 gallon (pump or pressure) A-1 4-A
(4) 5 gallon (pump or pressure) A-1 4-A
(5) 17 gallon (pressure) A 10-A
(6) 33 gallon (pressure) A 20-A
(7) 5 12-qt. or 6 10-qt. water filled pails A-1 2-A
(8) 55 gallon water filled pails A-1 2-A
(9) 25 55-gallon water filled tank with above 5 or 6 fire pails A-1 2-A
(c) Loaded stream (1) gallon A-2, B-4 1-A
(2) 1 3/4 and 2 1/2 gallon A-1, B-2 2-A, 1/2 -B
(3) 33 gallon A 20-A
(d) Foam (1) 1 1/4 and 1 1/2 gallon A-2, B-2 1-A, 2-B
(2) 2 1/2 gallon A-1, B-1 2-A, 4-B
(3) 5 gallon A-1, B-1 4-A, 6-B
(4) 10 gallon A, B 6-A, 8-B
(5) 17 gallon A, B 10-A, 10-B
(6) 33 gallon A, B 20-A, 20-B
(e) Vaporizing Liquid (1) 1, 1 1/4, 1 1/2 -qt. (pump) B-2, C-2 1/2 -B, C
(carbon tetrachloride base) (2) 1, 1 1/2, 2, 2 1/2 -qt. (pressure) B-2, C-2 1/2 -B, C
(3) 1, 3 1/2 -gallon (pressure) B-2, C-1 1-B, C
(f) Vaporizing Liquid (1) 1 and 1 1/2 -qt. (pressure) B-2, C-1 1-B, C
(chlorobromo methane) (2) 1 gallon (pressure) B-2, C-1 2-B, C
(g) Carbon dioxide (1) 6 or less pounds of carbon dioxide B-2, C-2 1-B, C
(2) 7 1/2 pounds of carbon dioxide B-2, C-1 2-B, C
(3) 10 to 12 pounds of carbon dioxide B-2, C-1 4-B, C
(4) 15 to 20 pounds of carbon dioxide B-1, C-1 4-B, C
(5) 25 to 26 pounds of carbon dioxide B-1, C-1 6-B, C
(6) 30 pounds of carbon dioxide B-1, C-1 10-B. C
(7) 75 pounds of carbon dioxide B-1, C-1 12-B, C
(8) 100 pounds of carbon dioxide B, C 12-B, C
(h) Dry chemical (1) 4 to 6 1/4 pounds of dry chemical B-2, C-2 4-B, C
(2) 7 1/2 pounds of dry chemical B-2, C-1 6-B, C
(3) 10 to 15 pounds of dry chemical B-1, C-1 8-B, C
(4) 20 pounds of dry chemical B-1, C-1 16-B, C
(5) 30 pounds of dry chemical B-1, C-1 20-B, C
(6) 75 to 350 pounds of dry chemical B, C 40-B, C
(i) Wetting agent (1) 10 gallons A, B 6-A
(2) 20 gallons A, B 12-A
(3) 50 gallons A, B 30-A

NOTE: Carbon dioxide extinguishers with metallic horns will not carry any C classification.

Disclaimer: These regulations may not be the most recent version. California may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.