California Code of Regulations
Title 19 - Public Safety
Division 1 - State Fire Marshal
Chapter 11.5 - Gasoline Vapor Control Systems
Article 6 - Electrical
Section 1918.70 - Electrical Requirements
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) General. All electrical equipment and wiring shall comply with the requirements set forth in Part 3, Title 24, California Administrative Code.
(b) Emergency Pump Cut-Off. All electrically energized vapor collection equipment shall be directly connected to, and controlled by, an emergency pump cut-off switch.
(c) Cut-Off Switch Location. The emergency pump cut-off switch shall be located in a readily accessible and clearly visible location, outside of any enclosure, within 75 feet of but no closer than 15 feet to any gasoline dispenser.
(d) Labeling. The emergency pump cut-off switch shall be clearly and legibly labeled as to its function.
1. Amendment filed 9-27-85; effective thirtieth day thereafter (Register 85, No. 41).
Note: Authority cited: Section 41956, Health and Safety Code. Reference: Sections 41956 and 41958, Health and Safety Code.