California Code of Regulations
Title 14 - Natural Resources
Division 1.5 - Department of Forestry and Fire Protection
Chapter 7 - Fire Protection
Subchapter 3 - Fire Hazard
Article 3 - Fire Hazard Reduction Around Buildings and Structures
Section 1299.03 - Requirements
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
Defensible space is required to be maintained at all times, whenever flammable vegetative conditions exist. One hundred feet (100 ft.) of defensible space clearance shall be maintained in two distinct "Zones" as follows: "Zone 1" extends thirty feet (30 ft.) out from each "Building or Structure," or to the property line, whichever comes first; "Zone 2" extends from thirty feet (30 ft.) to one hundred feet (100 ft.) from each "Building or Structure," but not beyond the property line. The vegetation treatment requirements for Zone 1 are more restrictive than for Zone 2, as provided in (a) and (b) below. The Department of Forestry and Fire Protection's "Property Inspection Guide, 2000 version, April 2000," provides additional guidance on vegetation treatment within Zone 1 and Zone 2, but is not mandatory and is not intended as a substitute for these regulations.
(a) Zone 1 Requirements:
(b) Zone 2 Requirements:
(c) For both Zones 1 and 2:
1. New
section filed 3-6-2013; operative 7-1-2013. Provisions derived from repealed
section 1299, subsections (a), (b) and (d)
(Register 2013, No. 10).
2. New subsection (b)(2)(A) filed
8-19-2013; operative 10-1-2013 (Register 2013, No. 34).
3. Change
without regulatory effect amending first paragraph and subsection (b)(1) filed
3-27-2018 pursuant to section
100, title 1, California Code of
Regulations (Register 2018, No. 13).
Note: Authority cited: Sections 4290 and 4291, Public Resources Code. Reference: Section 4291, Public Resources Code; and Sections 18908 and 18917, Health and Safety Code.