Section 1275.03 - Hydrants
Current through Register 2024 Notice Reg. No. 38, September 20, 2024
(a) The Fire Hydrant shall be eighteen (18) inches above the finished surface. Its location in relation to the Road or dRiveway and to the Building(s) or Structure(s) it serves shall comply with California Fire Code, California Code of Regulations title 24, part 9, Chapter 5, and Appendix C.
(b) The Fire Hydrant head shall be a two and half (2 1/2) inch National Hose male thread with cap for pressure and gravity flow systems and four and a half (4 1/2) inch for draft systems.
(c) Fire Hydrants shall be wet or dry barrel and have suitable freeze or crash protection as required by the Local Jurisdiction.
1.
Renumbering of former section
1275.15 to new section 1275.03,
including amendment of section heading and section, filed 9-6-2019; operative
1-1-2020 (Register 2019, No. 36).
2. Amendment of section heading
and section filed 1-31-2023; operative 4-1-2023 (Register 2023, No. 5).
Transmission deadline specified in Government Code section
11346.4(b)
extended 60 calendar days pursuant to Executive Order N-40-20 and an additional
60 calendar days pursuant to Executive Order N-71-20. Filing deadline specified
in Government Code section
11349.3(a)
extended 60 calendar days pursuant to Executive Order N-40-20 and an additional
60 calendar days pursuant to Executive Order
N-71-20.
Note: Authority cited: Section 4290, Public Resources Code. Reference: Sections 4290 and 4291, Public Resources Code.