Arkansas Water Well Construction Commission Rules and
Regulations (updated June 1, 2018)
Section
1.
Scope
1.1
Application. The rules and
regulations hereby prescribed provide minimum standards for the construction or
repair of water wells, and locations of water wells which are used or intended
to be used to locate, acquire, divert or artificially recharge ground water
within the boundaries of the State of Arkansas. No water well as defined below
shall be constructed or repaired contrary to the provisions of these
regulations.
1.2
Rules
applicable to old wells. When a well constructed prior to May 27, 1969,
is repaired, rehabilitated or reconstructed, the work shall include those
changes necessary to make the well conform to these rules and
regulations.
1.3
Exemptions . In some instances safe, potable water may be obtained
from wells in certain geographical locations which are not in strict accordance
with these rules and regulations. In this event permission, in writing, shall
be obtained from the Commission prior to developing the
well.
Section 2.
Procedure (reserved)
Section 3.
Licensing and
bonding
3.1
Authorized constructor. Water wells subject to these rules and
regulations shall be constructed only by persons having a valid license under
Act 641 of 1969, enacted by the General Assembly of the State of Arkansas,
unless exempt under provisions of that Act.
3.2
Supervision. During the
construction, alteration, or repair of a water well, or installation or repair
of pumping equipment there must be, within a two hour drive, a person who has
obtained a registration certificate and has been certified in the type of
construction engaged. The person who has obtained a registration certificate or
an apprentice with proper supervision as defined by Rule
3.10.1.1
shall remain informed and have knowledge of the status of the work being
accomplished.
3.3
Engineers
and geologists. Arkansas Registered Professional Engineers and Arkansas
Registered Professional Geologists practicing geotechnical engineering or
geologic investigations may be declared exempt from certification, bonding, and
testing requirements upon application for exemption from the
Commission.
3.4
Fees.
The following fees will be charged for licensing, registration, and rig
permitting.
Drilling and Pump System License
...................................... |
$350.00 |
Pump System-Only License
................................................. |
$175.00 |
Drilling-Only License
.......................................................... |
$175.00 |
Driller Registration Certificate
............................................ |
$125.00 |
Pump Installer Registration Certificate
................................ |
$125.00 |
Apprentice Certificate
.......................................................... |
$125.00 |
Rig permit
............................................................................ |
$145.00 |
3.4.1
Fees
non-refundable. All applicants for registration certificates shall pay
said fees prior to completing the exam. Once processed, all application and
licensing fees are non-refundable.
3.5
Categories for
registration certificates
3.5.1
Driller
registration.
3.5.1.1
Consolidated. Includes water well construction techniques for all
water wells, other than monitoring wells, completed in rock formation or in
formations which will not cave, including the overburden and soils overlying
consolidated formations.
3.5.1.2
Unconsolidated. Includes water well construction techniques for
all water wells, other than monitoring wells, completed in sand, clay, and
gravel formations which are caving in nature.
3.5.1.3
Monitoring and piezometer.
Includes construction for the purpose of locating and sampling for
engineering or geological data or sampling ground water.
3.5.1.4
Hydrofracturing.
Includes pumping or injecting fluids into a well and does not include the use
of explosives.
3.5.1.5
Geothermal. Includes construction of wells built for the purpose
of geothermal energy exchange including earth-coupled and direct exchange
systems.
3.5.2
Pump installer registration.
3.5.2.1
Turbine pumps. Includes
equipment consisting of, or used in conjunction with, line shaft turbine
pumps.
3.5.2.2
Submersible
pumps. Includes equipment consisting of, or used in conjunction with,
submersible pumps and motors.
3.5.2.3
Jet pumps. Includes
equipment used in conjunction with the jetting action of a venturi
nozzle.
3.5.2.4
Monitoring /
purging/ sampling. Includes pumps and other devices permanently
installed to purge monitor wells, obtain samples from a monitoring well, or
recover foreign substances from ground water.
3.5.2.5
Positive displacement pumps and
other devices.
Includes the installation of equipment and pumping devices not
listed above, such as hand pumps, windmills, stroke pumps or sucker rod pumps
and equipment.
3.5.2.6
Plugging. Registered pump installers who have demonstrated
knowledge of the applicable rules and possession of the required skills by
passing a test on those subjects administered by the Commission are authorized
to plug abandoned water wells
3.6
Water well contractor
licenses.
3.6.1
General. Any person who contracts for or is engaged in well
construction or pump installation shall hold or be employed by a person holding
an Arkansas Water Well Contractor License. The Water Well Contractor shall hold
the proper license, certificates, and permits for the type of construction
engaged and shall meet continuing education requirements as set forth
herein.
3.6.2
Categories for licenses.
3.6.2.1
Drilling and pump
systems. Includes contracting for all elements of water well
construction, including drilling and pump installation.
3.6.2.2
Pump systems. Includes
contracting for the installation and repair of pumps and related equipment and
does not include excavating the well.
3.6.2.3
Drilling. Includes
excavation of a water well, modification of the borehole, setting or removal of
casing up to the point of installing or repairing pumping equipment and
plugging abandoned water wells.
3.6.2.4
Master electricians. A
Master Electrician holding a valid license may repair or install pressure
switches, control boxes and other electrical components of the pumping
equipment at the well head without holding licenses issued by the Commission.
The Electrician shall adhere to these regulations for the installation and is
not authorized to break the well seal, or alter, cut or drill into the
casing.
3.6.2.5
Master
plumbers. A Master Plumber holding a valid Master Plumber License may
repair or install pressure switches, pressure tanks, valves and pipes at the
well head, without holding licenses issued by the Commission. The plumber shall
adhere to these regulations for the installation and is not authorized to break
the well seal, or alter, cut or drill into the casing.
3.7
Bonding.
3.7.1
Conditions of bond for resident and nonresident
contractor.
The Water Well Contractor as defined in Act 641, as amended, as
principal and a surety company or corporation authorized to do business in the
State of Arkansas as surety shall bind themselves and their successors and
assigns jointly and severally to the Arkansas Water Well Construction
Commission for the use and benefit of the public in the full penal sum of no
less than twenty thousand dollars ($20,000.00) for each licensing year
beginning August 1, 2016; that said principal and any person employed by him
shall duly comply with Act 641 of 1969, as amended, and all rules and
regulations pertaining to said Act. Any one contract, as prescribed herein by
section 3.7.7, between said principal and a person doing business with said
principal exceeding twenty thousand dollars ($20,000.00) or the amount of
aforesaid bond if in excess of twenty thousand dollars ($20,000.00) shall
require said principal to enter into a separate agreement and a bond equal to
the amount of said contract as required in Subsection (c) of Section
11 of Act 641 of 1969.
3.7.2
Recovery of damages. Any
and all persons doing business with said principal or person in his employ, who
have been damaged by reason of violation of any of the provisions set out in
Act 641 of 1969, as amended, and all rules and regulations pertaining to said
Act, may in their own name and without joining the Commission as a party, sue
thereon and join in said action as one of the defendants against the surety on
said bond(s).
3.7.3
Exhaustion of administrative remedies. No action shall be taken
against the principal and surety on said bond(s) until all reasonable
administrative remedies have been exhausted by the Commission.
3.7.4
Term of bond. Each bond
shall be construed as a new bond in the sum aforesaid in section
3.7.1, for each year it remains in full
force unless the bond is waived as set forth in Section 3.7.8.
3.7.5
Termination of bond. The
surety shall terminate each bond by giving not less than thirty (30) days
written notice of the effective date of said termination to the Commission.
Termination shall not relieve said surety or principal of any liability during
which the bond was in force until a period of not less than five (5) years from
the effective date of termination has expired.
3.7.6
Bond form. The Commission
shall provide a contractor's bond form to each person applying for the
contractor's license. Each contractor's license shall be issued only after the
receipt of the original copy of the water well contractor's bond prescribed
above and said form is completed and notarized. The contractor's license may be
renewed annually without receipt of a new contractor's bond form provided the
Commission has proof that the original contractor's bond(s) remains in full
force and effect.
3.7.7
The
amount of the contract. "The amount of the contract" as used in section
3.7.1 shall be defined as the amount or cost of the construction of the well,
including but not limited to the cost of drilling, casing, screens, grout,
seals, etc., excluding the costs of systems employed, constructed or installed
on the discharge side of the pressure tank or beyond the point of discharge
from the pump if no tank is employed, or to pivot systems, ditches, pumping
stations, pump houses, buildings, air conditioning duct work, or items which
the water well contractor may construct or install, but are not directly
connected with the construction of the well or included under the Definition or
Scope of a water well as prescribed in Subsection (E) of Section 3, and Section
4 of Act 641 of 1969, as amended, and
these rules and regulations.
3.7.8
Waiver. The Commission shall reserve the right to waive the
requirement of obtaining a water well contractor's bond in the amount of twenty
thousand dollars ($20,000.00) in favor of a bond of a lesser amount to those
contractors whose contracts for each one year period consistently amount to
less than twenty thousand dollars ($20,000.00). The contractor must provide
proof that he is unable to obtain a bond, or such bond would cause an undue
hardship. Further, the Executive Secretary of the Commission must be willing to
recommend that a bond of a lesser amount would be sufficient protection for any
persons doing business with the Contractor.
3.7.9
Cash bond. Persons who
install pumping equipment or repair pumping equipment that have been granted a
waiver for a twenty thousand dollar ($20,000) bond and are unable to post a
twenty thousand dollar ($20,000) bond may post in lieu of a water well
contractor's bond an escrow cash bond of no less than five hundred dollars
($500.00) per year until twenty thousand dollars ($20,000) is accrued. Persons
authorized to post an escrow cash bond in lieu of posting bond shall also
submit a statement of personal indemnification signed by the principal owner or
Chief Executive Officer.
3.8
Mail.
3.8.1
General. All persons
licensed or certified by the Commission agree to keep the Commission advised of
his or her current address and must readily accept all mail sent to them from
the Commission.
3.8.2
Registered or certified mail. Registered or certified mail sent
with proper postage and to the last known address that is returned unclaimed
shall be considered adequate notification of notice served.
3.8.3
Change of address. The
Commission shall be notified of any change of address within fifteen (15) days
of the change.
3.8.4
Refusal
to accept mail. Refusal to accept mail is considered a violation of
these regulations and will result in immediate suspension of any registration
or license until the matter is resolved and could result in further
disciplinary action.
3.9
Continuing education. Beginning August 1,
2002, as a condition of annual license renewal, a contractor or one designee
who is a partner, officer, or fulltime employee and a registered driller or
pump installer shall submit proof of 6 approved continuing education credits
completed during the previous licensing year. For each additional designee, two
(2) additional credits will be required per contractor per year. Credits
exceeding the required number may be carried over into the next licensing year.
The Commission may pre-approve continuing education programs and the number of
credits to be given for those programs therefore. Programs submitted for
pre-approval shall be considered by the Commission only upon submission, by the
sponsor or attendee, of a written description, which must include the names and
qualifications of the presenters, the time and location, the proposed number of
credits, and the program's objectives. Programs may be held in state or out of
state, and must be related to water wells or pump systems technology, science,
or health, sound business practices, or compliance with the Commission's Rules
and other governmental and industry requirements including worker health and
safety. Program sponsors must provide written proof of attendance to attendees,
and providers of pre-approved classes must provide a list of attendees to the
Commission by July 31 of each year.
3.10
Apprenticeship
program.
3.10.1
General. A natural person obtaining the knowledge, skills, and
abilities necessary to obtain a certificate of registration as a pump installer
or water well driller under the personal supervision of a registered pump
installer or registered water well driller may apply to the Commission for an
apprenticeship certificate.
3.10.1.1
Personal supervision. "Personal supervision" means that the
supervisor is at the job site with the apprentice or within two hours'
traveling distance of the apprentice whenever the apprentice is working in well
construction or pump installation. When the supervisor is not physically
present at the job site with the apprentice, the supervisor must be reachable
at any time by wireless telephone or radio contact.
3.10.1.2
Supervisor Employment.
A registered certificate holder serving as an apprentice supervisor shall be a
full time employee of the company hiring the apprentice.
3.10.2
Requirements for apprenticeship
certificate. All applicants for apprenticeship certificates must submit
the following:
1. Completed application
form;
2. Notarized letter from a
registered certificate holder stating:
a. that
he or she holds a certificate of registration in the same area or a comparable
area sought by the apprenticeship applicant and that he or she has held that
certificate for at least five of the previous ten years;
b. that he or she has no record of
construction violations in the specialty area unless waived by the
Commission;
c. that he or she has
no outstanding fines or fees owed to the Commission;
d. that he or she is willing to serve in a
supervisory capacity during the apprenticeship;
e. the number of apprentices including the
applicant that the supervisor currently supervises or anticipates supervising
within a year of drafting the letter will not exceed five; and f. a description
of training program;
3.
Written statement from a contractor employing the supervisor whereby the
contractor agrees to accept responsibility for the apprenticeship;
4. Copy of driver's license or other document
illustrating that applicant is at least eighteen years old; and
5. Registration fee.
3.10.3
Registration for concurrent
apprenticeships. An applicant may register for both a drilling
apprenticeship and a pump installer's apprenticeship at the same time. Each
registration will require separate registration fees.
3.10.4
Transfer of supervisory
authority. A supervisor may agree to temporarily transfer supervising
responsibility to a person holding a certificate of registration in the area
sought by the apprentice and employed by the same contractor. The supervisor to
whom responsibility is temporarily transferred must not already supervise more
than five other apprenticeships and must meet the requirements of
3.10.2.
3.10.5
Apprentice
responsibilities. An apprentice's certificate may be revoked for
engaging in prohibited activities.
3.10.5.1
Driller apprentice responsibilities. A driller apprentice shall:
1. represent his supervising driller during
operations at the well site;
2. not
perform, or offer to perform, any services associated with water well drilling
except under the personal supervision of a certified driller; and
3. not perform, or offer to perform, any
services associated with pump installation unless the apprentice holds a pump
installer apprentice certificate or pump installer certificate of
registration.
3.10.5.2
Pump installer apprentice responsibilities. A pump installer
apprentice shall:
1. represent his supervising
pump installer during operations at the well site;
2. not perform, or offer to perform, any
services associated with pump installation except under the direct supervision
of a certified pump installer; and
3. not perform, or offer to perform, any
services associated with water well drilling unless the apprentice holds a
driller apprentice certificate or driller certificate of
registration.
3.10.6
Length of apprenticeship.
A person must be apprenticed with the Commission for at least two years before
that person is eligible to apply for certification as a water well driller or
pump installer.
3.10.7
Eligibility to apply for driller and pump installer certification.
3.10.7.1
Supervisor recommendation.
After the apprentice has completed at least two years of
apprenticeship, the apprentice's supervisor may send the Commission a letter on
the apprentice's behalf stating that the apprentice is ready to sit for
examination to obtain a certificate of registration as a water well driller or
pump installer.
3.10.7.2
Application by apprentice. After the apprentice has completed two
years of apprenticeship, the apprentice may submit IRS W2 Wage and Tax
Statement forms demonstrating that he has spent three years in the employ of a
licensed water well contractor and that he is ready to sit for the certificate
of registration examination. The Commission will then approve or disapprove the
apprentice to take the examination.
3.10.7.2.1
Inability to secure letter from contractor. If after the
apprentice has completed at least two years of apprenticeship but is unable due
to extenuating circumstances to secure a letter from his supervisor
recommending that he be qualified to sit for examination, the apprentice may
petition the Commission to waive the requirement that he provide a letter from
a supervisor prior to sitting for the
examination.
3.10.8
Renewal of apprenticeship
certificate. An apprentice's certificate shall be deemed expired on July
31 of each year. If the apprentice has knowingly violated Commission rules or
owes fees assessed by the Commission, the Commission may choose to deny
renewal. A certificate must be renewed prior to the certificate's expiration
date by complying with all of the following requirements:
1. Submission of the renewal application
form; and
2. Payment of an annual
registration fee to the Commission.
3.10.9
Change of responsible supervisor
or contractor. If a supervisor terminates supervision of an apprentice,
the contractor employing the apprentice must send a written statement to the
Commission stating the relationship has ended. In order to continue the
apprenticeship, the apprentice must find another certificate holder to
supervise him or her, and that new supervisor must send a notarized letter to
the Commission that meets the requirements of Rule 3.10.2.
3.10.10
Apprenticeship Program
Exemption. A person who is seeking reinstatement of a certificate of
registration after his or her registration has been expired for more than one
year shall not be required to go through the apprenticeship program. Instead
this person shall:
1. Demonstrate via
application that he or she:
A. Was previously
registered in this state in the area of interest;
B. Held the registration in good standing at
the time of registration;
C. Did
not have his or her registration revoked for:
i. An act of bad faith; or
ii. A violation of law, rule or
ethics;
D. Is not holding
a suspended or probationary registration or license in any state;
E. Is sufficiently competent in his or her
area of interest by:
i. Satisfactorily
completing a competency examination approved by the Commission; and
ii. Producing two (2) letters of
recommendation from persons holding a valid registration in the area of
interest; and
2. Pay the certificate of registration fee
set out in Section
3.4
of these rules and regulations plus a twenty-five dollar ($25.00)
penalty.
3.10.10.1
Continuing
Education. The Commission may require the person to participate in
continuing education consistent with these rules and regulations.
3.10.10.2
Reciprocity. A person
shall not be required to comply with the requirement of 3.10.10 to obtain
reinstatement of a license if the person meets the requirements of
reciprocity.
3.11
Rules applicable to
active duty service members, returning military veterans, and
spouses.
3.11.1
Temporary accreditation for active duty military,
returning
military veterans, and spouses. The AWWCC will issue a temporary license
or certificate for any of the AWWCC programs to an individual applying for
Arkansas accreditation who
1. Holds a
substantially equivalent license or certificate issued by another state who is
in good standing with that state; and
2. Is one of the following:
A. An active duty military service member
stationed in the State of Arkansas;
B. A returning military veteran applying
within one (1) year of his or her discharge from active duty; or
C. The spouse of a person described by (2)(A)
or (B).
3.11.2
Expedited certification. The Commission shall expedite the
certification process for the following individuals:
1. A an active duty military member stationed
in Arkansas;
2. A returning
military veteran applying within one (1) year of his or her discharge from
active duty; or
3. The spouse of a
person described by (1) or (2) of this section.
3.11.3
Consideration of military
training and experience in
lieu of experience or education.
When considering an application for full licensure, the AWWCC
shall:
A. Consider whether or not the
applicant's military training and experience is substantially similar to
experience or education required for the applicable permit or license;
and
B. Accept the applicant's
military training and experience in lieu of experience or education required
for the applicable permit or license if the AWWCC determines the military
training and experience is a satisfactory substitute for the experience or
education required for the permit or license.
3.11.4
License or permit expiration.
A license or permit issued by the AWWCC held by an active duty military
service member or the spouse of an active duty military service member deployed
outside Arkansas shall not expire until one hundred eighty (180) days following
the active duty military service member's or the spouse's return from active
deployment.
3.11.5
Continuing
education exemption.
A. The AWWCC
shall allow a full or partial exemption from continuing education requirements
for the following individuals:
1. An active
duty military service member deployed ouside of the State of
Arkansas;
2. A returning military
veteran applying within one (1) year of his or her discharge from active duty;
or
3. The spouse of a person under
(1) or (2) of this section.
B. The Commission may require the completion
of continuing education before issuing any subsequent
renewals.
Section
4.
Reporting
4.1
Reports. Within ninety (90)
days after a water well has been constructed or repaired, the constructor shall
submit a report of construction to the Arkansas Water Well Construction
Commission on such forms as are prescribed and furnished by the Commission. The
date of construction and time of completion shall be the date and time the rig
is removed or pulled off the bore hole or well. Reports must be legible, must
supply all requested information applicable to the type of work done, and must
contain the longitude and latitude of the well location.
4.1.1
Test holes. When a water
well contractor constructs a test hole for a well that may be developed into a
water well, the contractor shall file a construction report within thirty (30)
days after the date of construction regardless of the stage of completion of
the water well.
4.2
Domestic wells. The contractor is required to maintain adequate
records at his place of business of pumps installed in water wells used for
domestic purposes. Generally all warranty information should be maintained as
well as depth of settings, size of wire, size of pipe, etc.
4.3
Copy to be provided to customer.
A copy of the construction report shall be provided to the customer
upon demand.
Section 5.
Construction
Note: Construction requirements vary according to type of
formation, type of well and intended use. Please review both the general
requirements and Section
6, "Special well construction techniques"
for the type of well you are working on.
5.1
Location.
5.1.1
General. In establishing
the location of a well the constructor shall give consideration to sources of
contamination which exist on or adjacent to the premises where the well is to
be located. As far as possible, the well shall be located on ground which is
higher than sources of contamination and shall have ready access for repairs,
maintenance, treatment and inspection.
5.1.2
Relation to sources of
contamination. Determination of minimum lateral distances to locate a
well from potential sources of contamination involves evaluation of the
character and location of the sources of contamination, types of geologic
formations present, depth to the aquifer, effect on ground water movement by
well pumping and possibilities of flooding of the site by surface waters. Based
on practice and experience, accepted minimum lateral distances for some common
sources of pollution with respect to a well have been established. The lack of
specific distances for other possible sources of contamination such as streams,
refuse disposal sites, excavations, waste treatment facilities, buried oil and
gasoline storage tanks, improperly constructed wells and cisterns, etc. does
not minimize their potential hazard. These must be evaluated in each particular
situation and a distance arrived at based on the pertinent facts.
5.1.3
Minimum lateral distances.
The following minimum lateral distances shall apply for common sources
of contamination listed:
Potential sources of contamination |
Minimum lateral distances for clay and loam
soils |
Cess Pools |
100 Feet |
Leaching Pit |
100 Feet |
Pit Privy |
100 Feet |
Subsurface Seepage Tile |
100 Feet |
Manure Piles |
100 Feet |
Septic Tank |
100 Feet |
Sewers (Cast iron with water tight, leaded or mechanical
joints) |
50 Feet |
Footing Drains (No connection to a sewer or a sump
handling sewage) |
10 Feet |
Pump House Floor Drain (Cast iron with water tight joints
and having free fall discharge to ground surface) |
2 Feet |
When the upper formations are more pervious, the lateral
distances shall be increased (i.e., double the distance for highly pervious
gravel formations).
5.1.4
Flood water. Locations subject to flooding should be avoided. If
no reasonable alternate site exists, wells may be constructed in flood zones
providing special protective construction is included.
5.1.5
Vertical closed loop systems /
wells. Vertical closed loop systems and wells shall not be located
closer than fifty (50) feet to a septic tank, its field lines, or other water
supply wells used for human consumption. This requirement may be waived. An
approved waiver may be requested by contacting the Commission office by
telephone or mail. Written approval must be obtained from the Commission prior
to construction of the well.
5.1.6
Open loop systems / wells. The location of open loop wells shall
meet the same criteria as water wells used for domestic or human
consumption.
5.1.7
Industrial
and irrigation wells. No industrial or irrigation well shall be located
nearer than one hundred (100) feet to any other well producing potable water.
It is recommended that locations subject to flooding be avoided. If no
reasonable alternate exists, wells should be constructed with the casing
terminating two (2) feet above the maximum known flood water
elevation.
5.1.8
Relations to
buildings. With respect to buildings, the location of a well shall be as
follows:
5.1.8.1
Adjacent to
building. When a well must be located adjacent to a building, it shall
be located so that the center line of the well extended vertically will clear
any projection from the building by not less than ten (10) feet. The well shall
also be located at least ten (10) feet away from any power lines.
5.1.8.2
Inside building. The
casing top of a well and any other opening shall not terminate in the basement
of any building, or in any pit, room or space which is below ground surface or
connected to a basement, which is not properly drained or pumped. Where it is
necessary to seal out seep water or rain water in small diameter wells that are
underground, National Water Well Association approved pitless adapters, or an
approved seal, shall be used.
5.2
Design
factors. The design of each well shall include
consideration of the following:
5.2.1
Natural protection. Location of the well shall include utilization
of every natural protection available to promote sanitary conditions.
5.2.2
Undesirable geological
formations. The exclusions of water bearing formations which are or may
become contaminated formations which have undesirable
characteristics.
5.2.3
Durability. The use of construction methods and materials which
will result in a durable well producing safe water, without excessive sediment
and sand, or harmful bacteria.
5.3
Materials and technical
requirements.
5.3.1
Construction water. Water used in the drilling process should be
obtained from a source which will not result in contamination of the well. It
is required that an appropriate amount of chlorine solution be added to the
construction water in order to protect the well from contamination. Please
refer to the tables in Section
11 to determine the proper amount of
chlorine to use.
5.3.2
Plumbness and alignment. Each drilled well shall be tested for
plumbness and alignment and the bore of the hole shall be sufficiently plumb
and straight to receive the casing without binding. The casing shall be
sufficiently plumb and straight so that it will not interfere with installation
and operation of the pump.
5.3.3
Yield. Each well shall be tested for yield and draw down by pump,
bailer, or air.
5.4
Casing.
The casing shall be installed
where the purpose of casing is to seal off surface, near surface, or deeper
contaminants or where the purpose is to retain the wall of the well in addition
to repelling outside contaminants. In selection of casing pipe, consideration
shall be given to the strain to which the pipe will be subjected during
construction and the corrosiveness of the water with which it comes in contact.
Used or reject pipe is not acceptable.
5.4.1
Temporary (outer) casing. Casing intended for construction
purposes only shall be of weight and design as necessary to be watertight and
permit installation without distortion or rupture to the specified
depth.
5.4.2
Grouting
guides. Protective casing that is to be grouted in the drill hole should
have sufficient guides welded to the casing to permit the unobstructed flow and
disposition of the thickness of grout specified.
5.4.3
Screens. Screen openings
shall provide the maximum amount of open area consistent with the strength of
screen and the grading of the water bearing formation or gravel pack. The
opening shall permit maximum transmitting ability without clogging or
jamming.
5.4.4
Joints.
All casing pipe joints shall be watertight welded construction or threaded
couplings.
5.4.5
Upper
terminal. The casing, well curb or riser pipe shall be terminated at a
height above ground surface consistent with the proposed plans for a pump house
and pump installation but not less than eight (8) inches above ground surface
or twenty-four (24) inches above maximum high water level where flooding
occurs.
5.4.6
Steel casing
for domestic, individual, and stock
wells. Casing for
domestic, individual and stock wells of steel construction shall be as follows:
Minimum eleven (11) pound black steel pipe may be used
in consolidated formations. ASA Galvanized Standard Weight Schedule 40 pipe,
one (1) inch I.D. to four (4) inches I.D. pipe size and weight are covered in
Section 11. 4.090 inch I. D. galvanized pipe, 9-1/2 pound (schedule 30) may be
used on a statewide basis with the following provision that any failure of this
weight pipe within a five (5) year period be replaced by the contractor at no
cost to the landowner.
5.4.7
PVC casing. Effective January 1, 1989, PVC plastic casing may be
used provided the PVC pipe is manufactured as water well casing and is
permanently marked as well casing. The casing shall be made to ASTM F480. The
Contractor shall be responsible to assure that the PVC wall thickness shall be
sufficient to withstand both the formation and hydrostatic pressures imposed on
the casing during its installation and development. PVC casing shall be used
only when construction practices will allow the bore hole to remain open during
casing installation and the casing can be lowered freely without
driving.
5.4.8
Fiberglass
casing. Fiberglass reinforced plastic well casing, tested in accordance
with ASTM D1180 (American Society Testing Materials), may be used where judged
desirable by the contractor and approved by the customer, in consolidated and
unconsolidated formations. Each coupling shall form a watertight seal. Pipe
having a minimum bursting pressure of 660 PSI may be used.
5.4.9
Casing of industrial
and irrigation wells.
5.4.9.1
General. All casing,
including steel shall be strong enough to resist the forces imposed during
installation and other forces that can be expected after installation. It shall
be the contractor's responsibility to see that all casing used in industrial
and irrigation wells will not collapse. Any material used in construction of
industrial and irrigation wells that collapses or breaks within (5) five years
shall be renewed with a material strong enough to withstand the stress or
pressure without charge to the customer.
5.4.9.2
PVC casing. PVC 160 PSI
NSF or stronger material classification may be used in construction of
industrial and irrigation wells, where judged desirable by the contractor and
approved by the customer in unconsolidated formations. All pipes shall be
permanently marked under a method suitable to the National Sanitation
Foundation. Plastic pipe must be made of new, not reclaimed material.
5.4.9.3
Joints. The joints of
all casing shall be watertight and plumb and in alignment. All casing shall be
installed so as to seal off water bearing formations that contain undesirable
water (such as saline) and prevent water from the surface entering the fresh
water aquifer so as not to contaminate them. Each joint of PVC pipe shall have
a minimum of four (4) screws or rivets in the coupling.
5.4.10
Casing in
consolidated formations. Metal or plastic casing shall
extend a minimum of one (1) foot into solid bedrock or slate in a cement or
Bentonite seal at least one (1) inch thick from rock upward for five (5) feet.
In wells where consolidated formations, such as bedrock or slate, occur as a
definable unit, the casing shall be set into the consolidated formation and
sealed below all crevices that would normally release water of inferior quality
into the well. Plastic casing may be used to case through overburden in
consolidated formations, providing the casing meets the requirements for the
depth being cased.
5.4.10.1
Rock below
creviced formation. The diameter of the drill hole through the creviced
formation shall be a minimum of two (2) inches greater than the diameter of the
casing. If an outer casing is left in place in the earth mantle, the annular
opening around that casing shall be sealed as outlined in Section 5.4.11. All
wells constructed in consolidated formations shall be cased a minimum of ten
(10) feet from ground surface or one (1) foot minimum into the consolidated
formation.1 All casing left permanently installed in
consolidated formations shall be grouted with the appropriate materials, as
outlined in Section
5.5,
from the bottom of the casing upward five (5) feet. Where a desirable water
bearing formation underlies a crevice or undesirable water bearing formation,
the overlaying formation should be completely grout sealed and watertight.
Drilling construction should extend into the desired formation.
1 Ten feet from ground surface or one foot
minimum into the consolidated formation means that wells must be cased at least
ten feet. Wells will never have less than 5 feet of cement or Bentonite grout
in the annulus. Wells must also be cased at least one foot into consolidated
formations. Minimum of one foot into consolidated rock means that many times
even thought the formation is consolidated, ground water, at a particular depth
would be undesirable and additional casing and grout to a depth greater than
one foot into consolidated formation is required.
5.4.11
Casing in unconsolidated formations.
Unconsolidated formations such as sand and gravel may extend to or near the
ground surface. Generally, however, they lie below the ground surface at
varying depths and are covered by an over burden of earth. The kind, nature and
depth of the over burden are factors in determining how a well shall be
constructed. Wells constructed in unconsolidated formations shall have a
permanent casing installed, in which the casing or screen shall extend the
complete length of the drill hole. A minimum of the upper ten (10) feet shall
be filled with grout after the casing is in place.
5.4.11.1
Gravel wall construction.
When an oversized drill hole is constructed to permit the placement of
a gravel wall around the well screen or perforated casing, the annular opening
between the casing and the drill hole shall be sealed in the top twenty (20)
feet with concrete, cement, or Bentonite grout. If a permanent outer casing is
installed, it shall extend to a depth of at least twenty (20) feet depending on
the formations present, the annular opening between the drill hole and the
outer casing shall be sealed as provided for in Section 5.4.12. The annular
opening between inner and outer casings shall be filled with concrete, cement,
or Bentonite grout in the upper twenty (20) feet.
5.5
Grouting.
5.5.1
Sand and cement grout.
This mixture should consist of cement, sand and water, in the proportion of one
bag of cement (94 pounds) and an equal volume of dry sand to not more than six
(6) gallons of clean water.
5.5.2
Neat cement grout. This mixture should consist of one bag of
cement (94 pounds) to not more than six (6) gallons of clean water. Additives
up to 6% by weight to increase fluidity may be used.
5.5.3
Concrete. This mixture
should consist of cement, sand, aggregate (gravel), and water in the proportion
of one bag of cement (94 pounds) and an equal amount of dry sand and aggregate
and clean water. Concrete can be used in the top ten (10) feet of the annular
space around the casing of the large diameter wells when the annular space is
larger than two (2) inches from the outside of the casing wall to the face of
the bore hole. Aggregate shall be no larger than 1/5 of the dimension between
the outside casing and the face of the bore hole. All concrete shall be placed
to prevent voids.
5.5.4
Bentonite grout. Bentonite or sealing clay grout is a manufactured
clay product that expands in contact with moisture to form a seal that prevents
the movement of water and may be used in consolidated and unconsolidated
formations. It is the responsibility of the contractor to make the viscosity of
the bentonite thick enough to seal out all contaminates.
5.5.5
Grouting of metal-cased wells.
Metal casing shall be encased in a cement seal at least two (2) inches
thick from ground level to a distance of at least ten (10) feet below
established ground surface.
5.5.6
Grouting of curbed wells. Curbed wells shall be concreted at lease
six (6) inches thick poured monolithically from the upper terminal to a
distance of at lease ten feet below established ground
surface.
5.6
Well seals or caps.
5.6.1
General. Well seals or
caps installed on wells shall be securely capped. The seal may provide
ventilation but shall be sufficiently tight and secure so as to prohibit
foreign objects, insects and other creatures from entering the well. The well
seal shall be secure so as to prohibit entrance to the well from unauthorized
persons without tools or excessive physical exertion.
5.6.2
Timing. The well seal or
cap shall be installed immediately upon completion of the well and prior to
departure of the driller and or contractor or his drilling equipment from the
well site. An effort should be made by the driller or contractor to insure that
the well seal or cap provided/installed is compatible to the type of pump and
pipe to be installed.
5.6.3
Seals or caps when pump installed. Well seals or caps shall be
installed on all water wells after pump installation, and shall be securely
capped. The seal MAY provide ventilation but be sufficiently tight and secure
to prohibit foreign objects, contamination, insects and other pests from
entering the well. The well seal shall be secure to prohibit entrance to the
well from unauthorized persons without tools or excessive physical exertion.
All wells in consolidated areas will be vented with insect proof vents. If the
well is located inside a building it shall be vented to the outside.
5.6.4
Pitless adapters. Pitless
adapters shall be installed in a manner that excludes entrance of water or
other materials into the well.
5.6.5
Test holes. The contractor
shall insure that the well/hole is capped to prevent injury or pollution. If
the test well is abandoned then the well shall be plugged as outlined in
Section
5.8.
5.7
Disinfection.
5.7.1
General. Every new well, or existing water supply system that has
been disrupted for service or repair, should be disinfected before it is
returned to use. Water in the well and storage tank should be treated with a
strong chlorine solution to destroy disease organisms. All pipe lines and
fixtures in the distribution system should be rinsed and flushed with
chlorinated water. All wells, excluding irrigation, will be
disinfected.
5.7.2
Timing. If the constructor of the well is also responsible for
preparing the well for the pump installation and making the pump installations,
disinfection may be postponed until his work is completed. In the event the
constructor does not have this responsibility, it is required before capping
the well that an appropriate amount of chlorine solution be introduced into the
well.
5.7.3
Disinfection and
pump installation. At the time of new pump installation or
reinstallation of an existing pump, the water system shall be chlorinated to a
minimum concentration of 50 ppm for a minimum of 24 hours. Each well shall be
disinfected by tablets and/or liquid.
5.7.4
Water. Water, which has
made contact with pipe or equipment used in chemigation, shall not be allowed
to back siphon or be used to backwash the well.
5.7.5
Emergencies. If an
emergency situation exists the water system may be used, provided, the system
is not for human consumption, and the system is disinfected as soon as the
situation permits. Refer to the tables in Section
11 for guidance on administering
chlorine.
5.8
Plugging or abandonment of wells.
5.8.1
General. In an effort to
restore geologic and hydrogeologic conditions existing prior to a well's
construction, any person who abandons an abandoned well, as defined in Rule
10.28,
must use methods and materials that will protect the ground water from surface
contamination and prohibit cross-contamination (co-mingling) of aquifers. Clay,
cement, or bentonite will be allowed to plug wells with certain restrictions
applied when using bentonite.
5.8.2
Dry holes. If no water is encountered and the landowner does not
wish to abandon the well in the event that he might plan further development of
the well at a later date, the contractor shall complete the well according to
the rules and regulations, including casing, sealing, and capping the
well.
5.8.3
File well
abandonment form. All wells plugged in the State should be reported by
the water well contractor to the AWWCC on a well abandonment form to be
approved by the AWWCC within ninety (90) days of abandonment.
5.8.4.1
Consolidated formations.
When information has been obtained about a well completed in a single
consolidated aquifer from a water well construction report, geophysical data,
or usage of a down-hole camera, the well shall be plugged with cement, clay, or
bentonite to a depth of fifty (50) feet below the bottom of the surface casing,
with a minimum depth of one hundred (100) feet of depth below land surface. The
remaining depth of the well may be filled with clean sand or pea gravel. Wells
completed in more than one major aquifer must have a minimum fifty (50) foot
clay, cement, or bentonite seal emplaced in the borehole within each confining
unit between the aquifers, and between any aquifer and the surface
overburden.
5.8.4.2
No
information. If no information on well construction is available, the
well must be filled from bottom to within two (2) feet of land surface with
clay, cement, or bentonite in a manner that will protect the ground-water flow
system.
5.8.5
Unconsolidated formations. All wells in unconsolidated formations
will be filled with sand or natural material to twelve (12) feet of ground
surface, from twelve (12) feet to two (2) feet with bentonite or
cement.
5.8.6
Usage of
packers. Packers should be emplaced in wells overlying flowing artesian
aquifers, or aquifers with more than seventy five (75) feet hydrostatic head to
curtail flow prior to plugging and prevent intercommunication of
aquifers.
5.8.7
Usage of
bentonite.
5.8.7.1
Chips.
Bentonite chips may only be used to plug a well if the well's diameter is four
(4) inches or more, the well's depth is less than six hundred (600) feet below
land surface, and the well contains less than five hundred (500) feet of
standing water.
5.8.7.2
Slurries. Bentonite slurries are not allowed for well abandonment
in the unsaturated zone (above water level).
5.8.7.3
Prohibited use of bentonite
under certain conditions. Bentonite should only be used in accordance
with package label recommendations.
5.8.8
Caves. A driller should
contact AWWCC staff for specific abandonment procedures if he encounters caves
while drilling.
5.9
Fracturing.
5.9.1
General. Fracturing
includes the use of explosives, acid, or pumping fluids (hydrofracturing) into
a water well. A Driller registered in category 4 shall supervise
hydrofracturing. A driller registered in category 1-3 may use explosives or
acid without being registered in category 4. Wells which do not meet the
requirements of these construction regulations shall not be
fractured.
5.9.2
Water. Water used in fracturing must be free of contamination and
chlorinated to fifty (50) milligrams per liter chlorine prior to
injection.
5.9.3
Relation to
sources of contamination. Water wells located closer than one hundred
(100) ft. to any potential source of contamination shall not be
fractured.
5.9.4
Process. The following action must take place when hydrofracturing
a water well:
1. Analysis of the well site
and well to determine the location of other wells and potential sources of
contamination in the immediate vicinity. Determine if the well needs repair and
if so bring up to standards. Determine the effect on geological formations and
ground water.
2. Conduct a test and
estimate well yield.
3. Advise
owner of hazards and potential liability of fracturing.
4. Disinfect well to be fractured to 50
milligrams per liter chlorine.
5.
Fracture well.
6. Reinstall pump
equipment.
7. Disinfect well and
pump equipment.
8. Pump well to
recover no less than the amount of water injected.
9. Conduct test and estimate well
yield.
10. Complete a construction
report. On the report, in the space provided for description of formation,
indicate the depth and PSI (or amount of explosive) of each zone fractured.
* The above steps are not meant to be all inclusive. The
contractor remains responsible and liable for damages to the well or wells in
the immediate vicinity resulting from hydrofracturing, even though the
Contractor may have complied with these regulations.
5.9.5
Consolidated formations.
Fracturing PSI shall not be excessive.
Section 6.
Special well
construction techniques
6.1
Artesian
wells. In known artesian territories, initial drilling
operations shall extend into but not through the formation confining the water.
The casing shall be installed and the annular opening between the drill hole
and casing sealed with cement or Bentonite grout and allowed to set. The hole
shall then be extended into artesian formation. Flow control from the well
shall be provided by valved pipe connections, watertight pump connections, or
receiving reservoirs set at an altitude corresponding to the artesian
head.
6.2
Driven,
dug, or bored wells. Wells in this classification are dug,
bored or driven, unless the type or purpose of the well applies to all methods
of well construction (test holes, heat pump wells etc.).
6.2.1
Driven wells. On all
driven wells there shall be an outer casing grouted from ground surface to a
minimum ten (10) feet depth. Plastic or steel casing that will accommodate the
outside diameter of the pipe being driven shall be placed in a hole that has a
minimum diameter of four (4) inches larger than the surface casing. This should
give a minimum of two (2) inches thickness of grout.
6.2.2
Dug or bored wells. Every
dug or bored well shall have a continuous watertight lining of steel casing or
concrete pipe extending from above ground surface to a depth of at least ten
(10) feet below the ground surface. When more than one formation bearing
suitable water exists, the lower formation should be used. The lining in the
producing zone shall readily admit water and shall be structurally sound to
withstand external pressures.
6.2.3
Annular openings. The open space between the excavation and the
installed lining shall be sealed with grout. If the first ten (10) feet of the
casing is jointed, such as concrete, and would allow surface water to seep into
cracks of casing, the grout will continue from the ten (10) foot seal to ground
level.
6.2.4
Upper terminal.
The watertight lining shall extend at least eight (8) inches above
finished ground surface. A cover slab at least two and one half (2 1/2) inches
thick, adequately reinforced and having a diameter sufficient to overlap the
lining by two (2) inches shall be provided. The top of the slab shall be sloped
to drain to all sides and a watertight joint made where the slab rests on the
well lining using cement mortar or a mastic compound. A manhole, if installed,
shall consist of a metal curb cast in the slab and extending four (4) inches
above the slab. The manhole shall have a watertight covering having sides to
overhang the curb at least two (2) inches. Adequate sized pipe (plastic pipe
may be used) shall be cast in place in the slab, extending at least eight (8)
inches above the slab, to accommodate the type of pump or pump piping proposed
for the well. If the well contractor does not install the pump, a cap (seal)
will be placed on top of the pipe. The owner or licensed driller may cut off
the cap and must leave a minimum of two (2) inches above the
slab.
6.3
Industrial and irrigation wells. This
section applies to wells constructed for purposes other than human consumption.
6.3.1
Outer casing seal for gravel well
industrial and irrigation wells.
Industrial wells shall be sealed with a concrete slab or grouted
or both. Irrigation wells shall be sealed with a bentonite seal. It is optional
to use a slab for an irrigation well.
6.3.1.1
Slabs. Slabs must be of
reinforced concrete and at least four (4) inches thick and have a diameter
sufficient to overlap the drill hole by two (2) feet. The top of the slab shall
be sloped to drain to all sides.
6.3.1.2
Grout. Grout must be
composed of sodium montmorillonite clay, also known as Bentonite, cement, or a
sodium montmorillonite (Bentonite)-cement mixture and shall fill the annular
opening between the casing and the drill hole in the upper ten (10)
feet.
6.3.1.3
Timing.
If noted on the Report of Water Well Construction, a slab may be placed on
non-grouted wells within one year of the date of construction to allow for
settling.
6.3.1.4
Gravel
refill pipes. Gravel refill pipes may be installed if they terminate
above the concrete slab surface and are provided with watertight
caps.
6.3.2
Public
notice. Each new industrial or irrigation well and each existing
industrial or irrigation well when brought under the rules and regulations of
the Act shall have a weatherproof sign attached in a conspicuous location
stating that "THIS WATER IS NOT FOR DRINKING PURPOSES" or a suitable decal of
weatherproof material.
6.3.3
Casing, screen, and all material for industrial and irrigation wells of
steel construction over four inches in diameter.
The minimum wall thickness shall be seven gauge or .1875. All
material used shall not allow sand or sediment to enter a well. Where there is
an acid condition screen material may be stainless steel, plastic, bronze, or
other material suitable for the water and ground formations in which the well
has been completed.
6.3.4
Gravel refill pipes. Gravel refill pipes may be installed if they
terminate above ground surface and are provided with water tight
caps.
6.3.5
Artificial
pack. Wells designed for placement of an artificial pack shall be
provided with an adequate screen having openings sized on the basis of the
grain size of the gravel. The well shall be developed to insure free entry of
water without sediment.
6.4
Geothermal (heat pump)
wells. Heat pump wells are designed for two major types of
Heat pump Systems.
6.4.1
Closed loop or
earth coil. Fluid is circulated in a continuous unbroken pipe beneath
the surface of the earth or under ponds, swimming pools, lakes or in a medium
where the system can obtain a sufficient cooling or heat exchange. Normally no
fluid is gained or lost. Depths of installation vary and are dependent upon the
type and size of closed loop system, the land area available, soils/formation,
climate, and seasonal variation in ground temperature, etc. There are three
types of closed loop heat pump well systems:
6.4.1.1
Horizontal system. A
closed loop system where pipes are installed horizontally under the earth's
surface or under ponds, swimming pools, lakes, etc.
6.4.1.2
Vertical system. A
closed loop system where pipes are vertically installed beneath the surface of
the earth.
6.4.1.3
Combination horizontal and vertical system. A system that has
pipes installed beneath the earth's surface horizontally and
vertically.
6.4.1.4
Direct
exchange (DX) wells. A small diameter bore hole constructed for the
purpose of sinking or sourcing thermal energy between the direct exchange loop
and the earth.
6.4.1.4.1
Additional
construction standards.
1. A DX well
shall comply with Commission Rules
5.1
and
5.2
2. The DX well does not have to be
completely vertical.
3. The DX well
casing is a metal tube with the bottom capped, running from the bottom of the
bore hole to within 1 foot of the top of the bore hole. A thermal fluid can be
used to fill the DX Well Casing to within 2 feet of the top of the DX Well
casing. A water tight sealing material will be used to seal the top of the DX
Well Casing. The material can be silicone, latex, or other material suitable
for the seal. The DX Well Casing shall comply with Rule
5.5.5.
4. DX Well Casing will be required if the pH
of the material around the DX Loop can not be corrected to a pH of 8.5 or
greater with the use of back fill or grout.
5. If the DX well Casing material is steel,
then no cathodic protection is required. (The DX Loop is Copper, which is more
noble than steel; therefore, the steel acts as cathodic protection.) The joints
will be threaded or welded.
6. If
the DX Well Casing material is Copper then cathodic protection is required. The
Joint will be welded using Arkansas Heating, Ventilation, Air Conditioning, and
Refrigeration (HVACR) standards for joining Refrigeration copper.
7. The DX Loop can be constructed of Type L
copper tubing (ACR) Any joint must comply with HVACR standards for joining
Refrigeration Copper. The copper tubing's length and diameter is sized for
proper refrigerant flow.
6.4.2
Open loop or water source.
Water is obtained from a source (water well, lake, river, etc.) and
circulated, usually one time, for the purpose cooling or heat exchange. Water
quality, quantity and disposal are primary concerns with open loop systems.
There are three types/categories of open loop well systems:
6.4.2.1
General. Open loop wells
shall be constructed in the same manner and conform to rules for wells used for
domestic purposes. This shall pertain to the supply well and return
well.
6.4.2.2
Single well
open system. Water is obtained from a well, circulated and returned to
the same well.
6.4.2.3
Dual
well open system. Water is obtained from a supply well, circulated, and
injected/dumped into a return well. These wells may be designed to switch roles
and the return well becomes the supply well, the supply well the return
well.
6.4.2.4
Single well /
waste open system. Water is obtained from a well, circulated, and
dumped/wasted into some other medium (land surface, lake, pond, ditch, sewer,
etc.).
6.4.3
Vertical closed loop systems / wells. The Contractor is
responsible and shall insure that water quantity and quality are not adversely
effected.
6.4.3.1
Grouting.
Closed loop wells constructed in consolidated formations shall be back filled
with grout (prescribed in Section
5.5) the entire length of the bore hole. Wells constructed in unconsolidated
formations may be back filled with cuttings, sand, or native material, provided
the material does not adversely affect the quality of the ground water. The
upper ten (10) feet (minimum requirement) of wells constructed in
unconsolidated formations shall be grouted (prescribed in Section
5.5). A well meeting requirements for a domestic water well is not required to be
back filled as outlined in this Section.
6.4.3.2
Horizontal excavation.
The top of the bore hole may terminate at the bottom of the excavation for
installation of horizontal pipes. The horizontal excavation is not required to
be back filled with grout. The grout shall be placed at least 10 feet below the
bottom of the excavation in unconsolidated formations.
6.4.4
Approved fluids. The fluid
or liquid used for circulation must be an approved fluid. Fluids which are
highly combustible, corrosive or toxic will not be used. A list of approved
fluids will be maintained by the Commission. Ethylene Glycol is not an approved
fluid. Approved fluids include but are not limited to: water, salt water,
calcium chloride, food quality propylene glycol.
6.4.5
Joints and fittings. All
joints and fittings installed and buried shall be heat, socket or butt fused.
Glue or clamps shall not be used below ground level unless the joint or
connection serves as a service outlet, and the joint or connection is not
covered with earth.
6.4.6
Circulating pipes. The circulating pipes shall be made of approved
materials. Approved circulating pipe are approved gas rated materials such as
polyethylene and polybutylene. Polyvinyl chloride (PVC) material is not
acceptable for circulating pipes for closed loop systems, below ground level.
Polyethylene pipe meeting or exceeding PPI PE 3408, ASTM D 3350, cell
classification 355434C, SDR-11 is approved. Polybutylene pipe meeting or
exceeding ASTM D 3309, rated at 160 PSI at 73 degrees Fahrenheit and also 100
PSI at 180 degrees Fahrenheit is approved.
6.4.7
Pressure testing. Pipes
shall be pressure tested at 150% of maximum working pressure for 15 minutes
prior to installation and shall not leak.
6.5
Monitoring and
piezometer wells. This section applies to monitoring well
construction. Monitoring wells are exempted from the construction requirements
established in Sections
4 through
16 of these rules and regulations. Design
and Construction Techniques published by the Environmental Protection Agency in
RCRA GROUND-WATER MONITORING TECHNICAL ENFORCEMENT GUIDANCE DOCUMENT (TEGD)
shall be used as a guide in the location, construction, and design of
monitoring wells. The latest publication of this document may be obtained by
contacting: Arkansas Water Well Construction Commission. 101 East
Capitol Avenue, Suite 350, Little Rock, Arkansas
7
2201, phone (501) 68 2-1025. Ask for the RCRA book
on monitor wells - cost $22.00.
6.6
Test and sample wells. Water wells
constructed for the purpose of locating, or sampling ground water or other
scientific purposes shall be constructed in a manner which shall not
contaminate ground water or provide a conduit to further contaminate ground
water.
6.7
Public
and semi-public wells. Wells for public and semi-public
water systems shall be located, designed, and constructed in accordance with
the respective regulations of the Arkansas Department of Health (ADH) and shall
have written approval from the ADH prior to the start of construction. If
uncertain that a well is public or semi-public, the well contractor shall
obtain a written determination from the ADH prior to
construction.
Section 7.
Pump installation
7.1
General. Installation shall
be in accordance with the manufacturer's recommendation and these regulations.
All pump installations shall be designed and installed so as to prevent
contamination of the well.
7.2
Licensing and registration. Pump installation shall be by a
licensed Water Well Contractor and registered pump installer.
7.3
Efficiency. Pump capacity
shall be consistent with intended use and yield characteristics of the well.
The pumping capacity of the pump installed in a well shall be consistent with
the intended use of the ground water and with the yield characteristics of the
well.
7.4
Location of
pressure tanks and switches. Pressure tanks and switches shall be
located above ground or in a pit or basement that is adequately drained. A
pressure tank may be buried provided, the tank is designed for installation
below ground. Tanks designed for use inside the bore of a water well must be
designed for that purpose and approved by the Commission.
7.5
Venting of gasses. Toxic or
flammable gases shall be vented from a well to the outside above roof level or
a point where they will not produce a hazard.
7.6
Upper terminal. Pump
Installers shall leave no less than eight inches of casing above normal ground
level.
7.7
Temporary seal.
If the pump equipment is not installed at the time drilling is
completed, all openings to the well must be closed to prevent pollution or
vandalism. After installation, all open spaces must be sealed off to prevent
contamination of the ground water.
7.8
Pipe drop, wire, etc. All
pipe drop, wire, pumps and other pumping equipment shall be clean and installed
to permit removal and repair of all equipment. If equipment or tools are lost
in the well and not recovered a statement describing the item or items lost
shall be attached to the installation report, or, maintained in the
contractor's records, when no report is required.
7.9
Well tanks. Well tanks
installed shall be adequate to meet the needs of the water system.
7.10
Plumbness. All pumps shall
be installed in a plumb manner so as not to interfere with proper operation or
efficiency, and not cause excessive wear on pumping equipment.
7.11
Prevention from contamination.
Pumping Equipment shall be installed in such a manner to discourage the
entrance of contamination into the ground water. Discharge pipes shall include
devices which will discourage the entrance of animals.
7.12
Check valves. Pumping
Equipment installed, which may be used in conjunction with chemigation shall
employ at least one check valve or other back siphoning device between the well
head and point of entrance of the foreign substances.
7.13
Submersible pump
installation.
7.13.1
Check valves. Submersible Pumps shall have no less than two (2)
check valves installed. One check valve must be installed above ground.
Submersible Pumps used for irrigation are excluded from this
requirement.
7.13.2
Wire.
Wire shall be secured to the drop pipe in a manner which will support
the weight of the wire and keep the wire close to the pipe.
7.13.3
Torque arrestors and cable
guards. Torque arresters and cable guards shall be used on all
submersible installations. Torque arresters are not required for pump
installation using steel pipe or schedule 80 PVC.
7.13.4
Clamps. All clamps used
shall be all stainless steel.
7.14
Jet pump
installation.
7.14.1
Check valves. Jet Pumps shall have a check valve installed on the
discharge side of the pressure tank.
7.14.2
Approved pipe drop.
Polyethylene plastic pipe and fittings shall be a minimum of SDR-7 PE-2306,
with a pressure rating of 160 PSI and is approved for use as the drop pipe in
jet pump installations.
7.14.3
Clamps. All clamps used shall be all stainless
steel.
7.15
Turbine pumps.
7.15.1
Steel column pipe for line shaft
turbine pumps.
Column pipe for irrigation wells shall be of .188 steel wall
thickness. Flange or threaded steel column pipe shall be used on turbine pump
installation. Plastic Column Pipe for turbine pump installation may be used
provided the pipe meets or exceeds specifications.
7.16
Pressure
systems.
7.16.1
Relief valve. All pressure systems will have a pressure relief valve
installed between the well seal and pressure switch.
7.17
Power and control wiring.
Licensees and registrants may run power and control wiring from a disconnect
box to water well equipment without obtaining an electrician's license.
Licensees and registrants may not alter the existing electrical service to any
building or structure. (See Act 493 of 1999) All wiring must meet the
requirements of the National Electrical Code 1999 edition, of the National Fire
Protection Association, or any updates or new editions of the National
Electrical Code adopted by the Board of Electrical Examiners after notice and
public hearing.
Section
8.
Rig permits and rig
confiscation.
8.1
General. A contractor who owns and operates a water well rig shall
follow the Commission's rig permitting requirements. Each rig owned and
operated by a contractor shall have a separate permit per permit year. Rig
permits are not transferable.
8.1.1
Rig
operation. No water well contractor shall operate a rig or permit an
employee to operate a rig unless the contractor holds a valid rig permit issued
by the Commission. The contractor shall firmly and conspicuously attach the
permit to the rig for which it was issued.
8.2
Requirements. In order to
obtain a rig permit, a contractor must hold a valid license, make proper
application for a rig permit and pay the required permit fee.
8.3
Expiration. Rig permits
shall expire on July 31 each year. The contractor must renew the rig permit
annually by applying for the renewal no later than thirty (30) days after the
expiration date.
8.3.1
Late fee.
After August 31 of each year, the Commission shall not renew a rig permit
unless the application, applicable fee and a late penalty of twenty-five
dollars ($25) is submitted.
8.4
Rig Confiscation. Those
persons who continuously violate Arkansas law and these rules and regulations
requiring that they obtain the proper registration, licensure, and training for
construction of water wells as well as the proper bond to protect well owners
are subject to forfeiture of certain property and proceeds in accordance with
Ark. Code Ann. §
17-50-401, et
seq.
Section 9.
Excessive Sediment.
9.1
Excessive sediment standards
. The following standards shall be used to determine when excessive sediment
exists in a well. Excessive sediment will be determined using EPA Test Method
160.5 (Imhoff Cone). Amounts in excess of the
below standards are considered excessive.
1. 1
mg/liter - water to be used directly in contact with, or in the processing of,
food and beverages.
2. 5 mg/liter -
water for homes, institutions, municipalities, and industries.
3. 10 mg/liter - water for sprinkler
irrigation systems, industrial evaporative cooling systems, and any other use
where a moderate amount of sediment is not especially harmful.
4. 15 mg/liter - water for flood-type
irrigation
9.2
Arkansas Water Well Construction Commission
Excessive Sediment Protocol . When determining
whether or not a well produces excessive sediment in accordance with the above
standards, Commission staff shall use the following procedure for collecting
samples.
9.2.1
Routine water
well inspections. Routine water well inspections for which no specific
complaint of excessive sediment has been received shall include the following
sampling process using EPA Test Method 160.5 (Imhoff Cone) and USGS approved
500 ml sample bottles:
1. The well shall be
purged by three (3) volumes of water,
2. Five (5) samples shall be collected over a
two (2) hour period, spaced at a minimum of twenty (20) minute
intervals,
3. Sediment volume shall
be estimated from all five (5) samples and averaged to determine the amount of
sediment produced by the well, and
4. Data shall be recorded on an AWWCC
inspection form.
If it is determined that the sediment amount exceeds 5 mg/L, the
AWWCC staff member shall follow the protocol outlined in 9.2.1.2.
9.2.1.2
Investigation of
excessive sediment complaints or
wells that produce more than 5 mg/L of sediment. If
a complaint of excessive sediment is received, or if a routine well inspection
reveals that a well is producing more than 5 mg/L of sediment, the following
sampling process using EPA Test Method 160.5 (Imhoff Cone) and USGS approved
500 ml sample bottles shall be followed:
1. Staff inspectors shall coordinate with an
ANRC registered geologist or engineer who has been trained in water quality
data collections. These two individuals will conduct the sampling of the well
in question,
2. The well shall be
purged by three (3) volumes,
3.
Five (5) samples shall be collected over a two (2) hour period, spaced at a
minimum of twenty (20) minute intervals,
4. At the time of sampling, a data collection
sheet shall be completed. The data collection sheet shall include, at a
minimum:
a. Date,
b. Time each sample was collected,
c. Well location to include longitude and
latitude,
d. Well owner
information,
e. Location where the
sample was taken (i.e. faucet in the home, etc.),
f. Photos, if possible,
g. Aquifer information, and
h. General description of the area including
a site sketch if possible,
5. All efforts to prevent sample
contamination shall be used to include the use of the USGS approved 500 ml
sample bottles. After the samples are collected, the bottles are to be sealed
and labeled with the date and the initials of the person collecting the sample,
and
6. Following the sealing of the
samples, a "Chain of Custody" form shall be completed by the employee who
completed the sampling and shall include:
a.
Information from the data collection sheets,
b. Names of the personnel collecting the
samples,
c. Name and Location of
the lab the sample was taken to,
d.
Initials of the lab personnel who accepted delivery of the samples,
and
7. Samples shall be
placed on ice and kept at cool temperatures until they are delivered to a
qualified water quality testing laboratory. The samples shall be delivered to a
qualified laboratory within seventy-two (72) hours of collection.
8. Sediment volume shall be estimated from
all five (5) samples and averaged to determine the amount of sediment produced
by the well using EPA Test Method 160.5
Section 10.
Definitions
For the purpose of these rules and regulations, the following
definitions shall apply:
10.1
Commission means the Arkansas Water Well Construction Commission
as created by Section 5 of Act 641 of 1969, as amended.
10.2
Water well means any
excavation that is drilled, redrilled, cored, bored, washed, driven, dug,
jetted or otherwise artificially constructed for the purpose of locating,
acquiring, diverting or artificially recharging ground water; but such terms do
not include an excavation made for the purpose of obtaining or for prospecting
for oil, natural gas, minerals, or products of mining or quarrying, or for
inserting media to repressure oil or natural gas, or other products.
(Subsection E, Section 3, of Act 641 of 1969).
10.3
Heat pump wells means any
excavation that is drilled, redrilled, cored, bored, washed, driven, dug,
jetted or otherwise artificially constructed for the purpose of obtaining or
exchanging geothermal energy for use with ground water source air conditioning
or heat pump systems. The excavation may have pipes installed inside the
excavation to circulate or discharge various fluids for the above said use and
purpose and the well may or may not be back filled after excavation.
(Subsection H, Section 3, of Act 641 of 1969).
10.4
Well construction means the
act of setting up the rig for and engaging in the excavation of a water well,
the modification of the borehole, and the setting or removal of casing, up to
the point of installing or repairing pump equipment, and plugging abandoned
water wells.
10.5
Aquifer
means a water bearing formation that transmits water in sufficient
quantity to supply a well.
10.6
Established ground surface means the elevation of the ground
surface at the site of the well.
10.7
Non-pumping (static) water
level means the elevation of the water surface in a well when no water
is being pumped.
10.8
Annular
space means the opening between a well hole excavation and the well
casing or curb, or between a casing pipe and a liner pipe.
10.9
Well seal means an
arrangement or device used to cap a well or to establish closure of the
junction of a well pump or piping with the well casing at the upper terminal of
the well.
10.10
Unconsolidated formation means a geological formation above
bedrock such as sand or gravel which is caving in nature.
10.11
Consolidated formation
means a geological formation which is firm such as rock, slate or clay that
will not cave.
10.12
Owner means the persons who own the property on which the well is
being constructed.
10.13
Rig means the machinery used in the construction or repair of
water wells. As used in this definition the word "machinery" shall not be
construed to include vehicles or any other equipment used in the
transportation, or as the foundation, or any other component part, of the
apparatus specifically designed and used in the construction or repair of water
wells.
10.14
Chemigation
means any activity or method which adds a foreign substance; such as
fertilizers, herbicides, fungicides, pesticides, and other substances or
chemicals, to a water system through mechanical or manual means.
10.15
Backwash means the surging
effect or reversal of water flow in a well.
10.16
Pressure system means a
system that includes a switch or other cut off device that operates off of the
water pressure, generated by the same system.
10.17
Excessive sediment means
sediment which is excessive for the purpose or intended use of the well as
measured using EPA Test Method 160.5 (Imhoff Cone).
10.18
Sediment - All particles
or materials which are not suspended in standing water. Natural occurring
minerals and elements such as iron, sodium, silica, lignite, manganese, etc.
may also be used to calculate sediment provided the minerals are not
suspended.
10.19
Undesirable
geological formations are formations that produce water which have
characteristics that are not conducive to the use or purpose for which the well
is to be used. The characteristics of each Geological Formation vary greatly
depending upon the location and depth of each formation. Formations with
undesirable characteristics are considered undesirable relative to other
formations at the same location which can produce water for the intended use,
which are known to have the desired quality.
10.20
Ground water - Water
occurring in the ground.
10.21
Surface water - Water located above the ground.
10.22
Harmful bacteria - The
presence of coliform bacteria constitutes the presence of harmful
bacteria.
10.23
Saturated
zone - The subsurface zone in which all openings are full of
water.
10.24
Contamination
- The degradation of natural water quality as a result of man's
activities. There is no implication of any specific limits, since the degree of
permissible contamination depends upon the intended end use, or uses, of the
water.
10.25
Monitoring wells
- Wells constructed for the purpose of locating and sampling for
Engineering or Geological data.
10.26
Static water level - The
level water naturally reaches in a well, at atmospheric pressure.
10.27
Well yield - The volume of
water discharged from the well after construction expressed in gallons per
minute (gpm) or gallons per hour (gph). Well yield is an estimate of the total
volume of water the well is capable of producing at the time of
construction.
10.28
Abandoned
water well means a well whose use has been permanently discontinued. Any
well shall be deemed abandoned which is in such a state of disrepair that
continued use for the purpose of obtaining ground water is
impractical.
10.29
Standard
dimension ration (SDR) - Outside diameter in inches divided by the wall
thickness in inches.
10.30
Master plumber - A person currently holding a valid master
plumbers license pursuant to Arkansas Code Ann.
17-31-101 et.
seq.
10.31
Master
electrician - A person currently holding a valid master electricians
license pursuant to Arkansas Code Ann.
17-25-101
et. seq. and
20-31-101 et.
seq.
10.32
Water well
contractor means any person (including a partnership or corporation) who
engages in the business of well construction or pump installation or repair,
exclusive of surveying or other acts preparatory to the construction of a water
well.
10.33
Water well
driller means any natural person, whether or not connected with a firm,
partnership, corporation, or other public or private association, who engages
for compensation in well construction.
10.34
Pump installer means any
natural person, whether or not connected with a firm, partnership, corporation,
or public or private association, who engages for compensation in pump
installation or repair.
10.35
Public well means any well supplying water to a public water
system as defined and regulated by the Arkansas Department of Health. In
general, this means a well serving or anticipated to serve 15 or more
connections or an average of at least 24 individuals 60 or more days in a
year.
10.36
Semi-public
well means any well supplying water to a semi-public water system as
defined and regulated by the Arkansas Department of Health. In general, this
means a well supply made available to the public for drinking or used in
connection with the manufacturing, processing, or handling of ice, food, or
drink.
10.37
Apprentice
means a natural person who under the supervision of a registered Water
Well Pump Installer or registered Water Well Driller is obtaining the
knowledge, skills, and abilities necessary to obtain a Certificate of
Registration as a Water Well Pump Installer or Water Well Driller.
10.38
Apprenticeship program
means a program developed by the Commission pursuant to §
17-50-312
to develop certain minimum knowledge, skills or abilities in those natural
persons desiring registration as Pump Installers or Water Well
Drillers.
10.39
Direct
exchange well means a small diameter bore hole constructed for the
purpose of sinking or sourcing thermal energy between the direct exchange loop
and the earth.
10.40
Direct
exchange loop means a continuous unbroken pipe beneath the surface of
the earth that circulates refrigerant for the purpose of sinking or sourcing
thermal energy between the direct exchange loop and the earth.
10.41
Thermal fluid means a
fluid used to transfer thermal energy. The thermal fluid must be biodegradable
and non-toxic in soil or water.
10.42
Unsaturated zone means the
subsurface zone, usually starting at the land surface, which contains both air
and water.
10.43
Bentonite means altered volcanic ash consisting of an assemblage
of clay minerals, primarily montmorillonite, a swelling clay.
10.44
Major aquifers means
water-bearing layers of rock or sediment capable of yielding water in large
quantities to wells or springs. These aquifers include the Boone aquifer, and
those of the Ozark aquifer system such as the Roubidoux formation and Gunter
sandstone.
10.45
Packer
means a piece of downhole equipment that consists of a sealing device,
a holding or setting device, and an inside passage for fluids.
10.46
Contraband property means
property of any nature, including personal, tangible, or intangible, but not
real property, that is used or intended to be used in violation of Ark. Code
Ann. §
17-50-104.
10.47
Pumping equipment means
all machinery and parts of pumps such as deep well turbine pumps with right
angle gear drive, vertical hollow shaft motors, jet pumps and motors,
submersible pumps and motors, and other parts and fittings installed or
attached to the well. It does not include cooling units, horizontal electric
motors, heat pump circulating pipe, and stationary diesel or gas
engines.
10.48
Returning
military veteran means a former member of the United States Armed Forces
who was discharged from active duty under circumstances other than
dishonorable.
Section 11.
Tables Table 1. Casing Dimensions.
Size
|
External
|
Internal
|
Thickness
|
Weight plain end
|
(Lbs. / Ft.)
Threaded and coupled
|
1.00 |
1.315 |
1.049 |
.133 |
1.68 |
1.70 |
1.25 |
1.660 |
1.049 |
.140 |
2.27 |
2.30 |
1.50 |
1.900 |
1.610 |
.145 |
2.72 |
2.75 |
2.00 |
2.375 |
2.061 |
.154 |
3.65 |
3.75 |
2.50 |
2.875 |
2.469 |
.203 |
5.79 |
5.90 |
3.00 |
3.500 |
3.068 |
.216 |
7.58 |
7.70 |
3.50 |
4.000 |
3.548 |
.226 |
9.11 |
9.25 |
4.00 |
4.500 |
4.026 |
.237 |
10.70 |
11.00 |
5.00 |
5.563 |
5.047 |
.258 |
14.62 |
15.00 |
Table 2. Chlorine Compound Required to Produce a 50-mg / l
Solution in 100 ft (30.5 m) of Water-Filled Casing*
Casing Diameter |
Volume 100ft. (30.5 m) |
65% HTH, Perchloron, etc. (dry weight) |
25% Chloride of Lime (dry weight)H |
5.25% Purex, Chlorox, etc.(sodium hypochlorite)
(liquid measure) |
in
|
mm
|
gal
|
3 m
|
oz
|
g
|
oz
|
g
|
oz
|
l
|
2 |
51 |
16.3 |
0.06 |
0.2 |
5.7 |
0.5 |
14.2 |
2 |
0.06 |
4 |
102 |
65.3 |
0.25 |
0.7 |
19.8 |
2 |
56.7 |
9 |
0.3 |
6 |
152 |
147 |
0.56 |
2 |
56.7 |
4 |
113 |
20 |
0.6 |
8 |
203 |
261 |
.99 |
3 |
85.1 |
7 |
198 |
34 |
1.0 |
10 |
254 |
408 |
1.5 |
4 |
113 |
11 |
312 |
56 |
1.7 |
12 |
305 |
588 |
2.2 |
6 |
170 |
16 |
454 |
80 |
2.4 |
16 |
406 |
1,045 |
4.0 |
11 |
312 |
28 |
794 |
128 |
3.8 |
20 |
508 |
1,632 |
6.2 |
17 |
482 |
43 |
1,219 |
214 |
6.4 |
24 |
610 |
2,350 |
8.9 |
24 |
680 |
63 |
1,786 |
298 |
8.7 |
Note: Liquid sodium hypochlorite in a 12-percent solution is
often sold for use in water and wastewater treatment plants, and as a
commercial bleach or for use in swimming pools. Utilizing a solution of this
nature would call for a liquid (chemical) measure equal to one-half the volumes
presented in column 5.
*EPA recommends a minimum concentration of 100 mg/ l available
chlorine. To obtain this concentration, double the amounts indicated.
Where a dry chemical is used, it should be mixed with water to
form a chlorine solution before putting it into the well.
Table 3. How to Sanitize a Water System to 400 ppm using
Autotrol's Well Sanitizer Pellets. Autotrol's pellets contain 70%
calcium hypochlorite and 30% inert material.
Well Diameter-Inches
|
For each 100 feet of water depth use*
|
Weight of Pellets lbs. - oz.
|
Cups of Pellets
|
Number of Pellets
|
2 |
0 - 1.5 |
1 / 4 |
40 |
3 |
0 - 3.0 |
2 / 5 |
80 |
4 |
0 - 6.0 |
3 / 4 |
140 |
5 |
0 - 8.0 |
1 |
200 |
6 |
0 - 12.0 |
1 - 1/2 |
300 |
8 |
1 - 5.0 |
2 - 1/2 |
500 |
10 |
2 - 0 |
4 |
800 |
12 |
3 - 0 |
6 |
- - - |
24 |
12 - 0 |
24 |
- - - |
36 |
26 - 0 |
- - - |
- - - |
* To produce a 400 PPM chlorine dosage
Note: Pellets Weight = 1.14 gram each, 25 pellets/oz., 400
pellets/lb.
1 cup of pellets = 1/2 lb., or 8 oz., or 200 pellets
Autotrol Corporation's Well Sanitizer chlorinating pellets can be
used for well, storage tank, or cistern sanitization. The amount of pellets
used will depend on the amount of water in the system to be sanitized. To
produce a 400 ppm chlorine concentration, to sanitize a water system, use
one-half (1/2) pound chlorination pellets for each 100 gallons of water in the
system (1/2 lb/100 gal = 8 oz/100 gal = 200 pellets/100 gal = 1 cup pellets/100
gal). Table 3 shows how many pellets to use per 100 feet of water in various
diameter wells.
Drilled Wells
1. Remove the cap or seal from the casing and
measure the depth of the water in the well, then refer to the Table to
determine how many chlorine pellets should be used. In some instances removing
the seal to measure the water can be a difficult task, and it is easier to
estimate well and water depth from well log or other records.
2. Remove well cap and determine if there is
an unobstructed path from the top of the well to the water level. If it is not
possible to remove the well cap, remove vent or sanitization access
plug.
3. Drop one pellet into the
well and listen to hear if it hits the water. If the pellet hits the water,
drop one-half (1/2) the number of pellets determined to be needed into the
well. These will sink to the bottom and sanitize the lower part of the
well.
4. Mix the remaining pellets
in a few gallons of water in a CLEAN plastic container and pour the solution
into the well.
5. In order to mix
the chlorine thoroughly throughout the entire water system, it is necessary to
recirculate the water in the well. This can be accomplished by connecting a
hose to an outside silcock that is located after the pressure tank. Use hose to
run water back down the well (this also rinses upper portion of well). After
about 15 minutes of recirculation the water, a strong chlorine odor should be
apparent. Turn off hose.
6. Bypass
water softener and filters and open each water outlet in the water system until
chlorine is present in water. This procedure assures that all the water in the
system is chlorinated.
7. Allow the
chlorinated water to stand in the system for at least six (6) hours, and
preferably overnight. After this, open an outside faucet and flush system until
water runs chlorine free. Repeat flush operation on each faucet in system.
Note:
A. Chlorine may
break loose iron deposits, slime and organic material. This material will make
the water run colored. The material broken loose may plug pump screens. DO NOT
CONTINUE TO RUN PUMP IF WATER DOESN'T FLOW.
B. The high level of chlorine required to
sanitize a water system is corrosive to most metals and chlorine solution must
not be allowed to remain in water system more than 36 hours before being
completely flushed from system.
8. After system has been completely flushed,
perform a bacterial analysis on the water following all applicable procedures.
Large Diameter Bored Wells
Calculate the volume of water in well by determining the total
cubic inches or cubic feet of water in the well. Each 231 cubic inches of water
is equal to one gallon. Each cubic foot of water is 7.5 gallons of water. Use
1/2 pound of chlorine pellets for each 100 gallons of water in well. Dissolve
pellets in clean, plastic pail and add to well. Pour two cups of pellets
directly into well. Connect a garden hose to a faucet in water system and run
water from hose back down well. When strong chlorine odor is present in hose
water, wash down sides of well with chlorinated water. Proceed with steps Nos.
6, 7 and 8 of instructions for Drilled Wells.
Springs and Cisterns
Mix about 1/2 cup of pellets in 5 gallons of water use this to
scrub the walls of the spring box or holding tank. With a constant flow of
fresh water from the spring there is probably no way of detaining the chlorine
solution in the reservoir for more than a few minutes. However, the chlorinated
water should flow through the pipeline to disinfect the distribution system.
Cisterns can be disinfected in the same way but a source of clean water will be
needed to flush the dirty waste out of the system.
Note: This product is intended to sanitize a water supply system
that has been temporarily contaminated, and is not intended to solve a
recurring contamination problem.
NOTE: These regulations are the minimum requirements for water
wells constructed in Arkansas.
For additional information pertaining to Public or Semi-Public
Water Systems contact the Arkansas Department of Health.
For information regarding water use reporting, water rights, and
ground water diversions contact the Arkansas Natural Resources
Commission.
For information on having your well water sampled, contact your
local county sanitarian, county health unit.
For additional information on water well construction or if you
believe you have a complaint contact the Arkansas Water Well Construction
Commission.
For Underground Storage Tank information contact the Arkansas
Department of Environmental Quality.