Current through Register Vol. 49, No. 9, September, 2024
DEFINITIONS
These Rules are promulgated by the Director of the Department
Division of Arkansas State Police, who serves by operation of law as the
Arkansas State Fire Marshal under the authority granted by Arkansas Act 254 of
1955, codified at A.C.A. §§
12-13-101 to
A.C.A. §
12-13-116,
as amended. The purpose of these Rules is to aid in the implementation,
interpretation, and enforcement of the Arkansas Fire Prevention
Code (AFPC), 2021 Edition.
The International Fire Code, 2021 Edition, the
International Building Code, 2021 Edition, and the
International Residential Code, 2021 Edition, as published by
the International Code Council and the rules, as amended, and adopted by the
Arkansas State Fire Marshal, shall constitute the Arkansas Fire
Prevention Code, 2021 Edition. These Rules shall be effective January
1,2023.
The following shall be defined as:
INTERNATIONAL PLUMBING CODE shall mean the Arkansas
State Plumbing Code.
INTERNATIONAL PRIVATE SEWAGE DISPOSAL CODE is replaced by
"Arkansas Department of Health Rules and Regulations Pertaining to Onsite
Wastewater Systems".
INTERNATIONAL MECHANICAL CODE shall mean the
mechanical code for Arkansas.
INTERNATIONAL FUEL GAS CODE shall mean the Arkansas
State Gas Code.
INTERNATIONAL ENERGY CONSERVATION CODE shall mean the
Arkansas Energy Code.
INTERNATIONAL FIRE CODE shall mean the Arkansas Fire
Prevention Code, Volume I.
INTERNATIONAL BUILDING CODE shall mean the Arkansas
Fire Prevention Code, Volume II.
INTERNATIONAL RESIDENTIAL CODE shall mean the Arkansas
Fire Prevention Code, Volume III.
NATIONAL ELECTRICAL CODE shall mean the electric code
for the State of Arkansas.
BUILDING OFFICIAL shall mean any governmental official having
authority to enforce that aspect of the Code.
Dotted lines in the margin indicate Arkansas revisions.
Solid Stars in the margin indicate Arkansas deletions.
Chapter 1
, Administration
[A] 101.1
Title. These rules
shall be known as the
Arkansas Fire Prevention Code.
[A] 101.2.1
Appendices.
Provisions in the appendices shall not apply unless specifically adopted.
Appendices B, C, D, E, F, G, and K arc adopted by the State of Arkansas. Other
appendices shall not apply unless adopted by local ordinance. Requests for
exceptions to Appendix D may be appealed to the Arkansas State Fire Marshal
(State Fire Marshal).
[A] 101.2.2
Locally adopted codes. Each district, county, municipality, or
other political subdivision of this state shall only adopt and enforce the
provisions of the Arkansas Fire Prevention Code, 2021 Edition. The AFPC 2021
Edition shall be the only foundation document available for modification by
local jurisdictions should they choose to adopt more stringent provisions. It
shall be the responsibility of local authorities having jurisdiction to bring
the proposed specific rule or provision up to the minimum standards of the AFPC
2021 Edition. The State Fire Marshal shall advise local jurisdictions of any
requirement that is less stringent than the AFPC 2021 Edition.
[A] 102.4
Application of
building code. The design and construction of new structures shall
comply with the Arkansas Fire Prevention Code, Volume II, and
any alterations, additions, changes in use or changes in structures required by
this code, which are within the scope of the Arkansas Fire Prevention
Code, Volume II, shall be made in accordance therewith.
[A] 102.5
Application of residential
code. Where structures are designed and constructed in accordance with
the
Arkansas Fire Prevention Code, Volume III, the provisions
of this code shall apply as follows:
1.
Construction and design provisions of this code pertaining to the exterior of
the structure shall apply including, but not limited to, premises
identification, fire apparatus access and water supplies. Where interior or
exterior systems or devices arc installed, construction permits required by
Section 105.6 shall apply.
2.
Administrative, operational and maintenance provisions of this code shall
apply.
[A] 102.13
MEMORANDUM OF UNDERSTANDING-HEALTH CARE
FACILITIES.
This Memorandum of Understanding will specify and serve as a
method to resolve conflicts between the Arkansas Fire Prevention Code Rules,
2021 Edition (hereinafter "Arkansas Fire Prevention Code" or "AFPC") adopted
and enforced by the Arkansas State Fire Marshal's Office, under the authority
of the Director of the Division of the Arkansas State Police, and other federal
or state rules governing Arkansas' health care and long-term care facilities,
by law regulated by the Arkansas Department of Health and the Arkansas
Department of Human Services, Division of Provider Services and Quality
Assurance (DPSQA), among others.
1.
The Arkansas Department of Health and the Arkansas Department of Human
Services, Division of Provider Services and Quality Assurance (DPSQA) will have
inspectors and/or plan reviewers obtain training related to the implementation
and application of the National Fire Protection Association Life Safety Code
(NFPA 101) and the Arkansas Fire Prevention Code.
2. The Arkansas Department of Health will
have concurrent authority to do Fire and Life Safety Code inspections in health
care facilities regulated by the Arkansas Department of Health. The Arkansas
Department of Human Services, Division of Provider Services and Quality
Assurance (DPSQA), will have concurrent authority to do Fire and Life Safety
inspections in long-term care facilities regulated by the Arkansas Department
of Human Services, Division of Provider Services and Quality Assurance (DPSQA).
The Arkansas Department of Health's authority and the authority of the Arkansas
Department of Human Services, Division of Provider Services and Quality
Assurance (DPSQA) will be concurrent with the current authority of any other
relevant federal, state or local government agency having authority to do said
inspections.
3. The Arkansas Fire
Prevention Code is the fire prevention code for the State of
Arkansas.
4. When there is a
conflict between the Arkansas Fire Prevention Code and the National Fire
Protection Association Life Safety Code (NFPA 101), New Health Care Occupancies
Chapter, Existing Health Care Occupancies Chapter, New Ambulatory Health Care
Occupancies Chapter, and Existing Ambulatory Health Care Occupancies Chapter,
as adopted by the United States Department of Health and Human Services,
Centers for Medicare Medicaid Services, per Title 42 Code of Federal
Regulations, the aforementioned chapters in the Life Safety Code shall
govern.
5. For new construction,
when one of the affected agencies (Arkansas Department of Health, Arkansas
Department of Human Services, Division of Provider Services and Quality
Assurance (DPSQA), local fire official, or local building official) determines
or perceives that a conflict exists between the Arkansas Fire Prevention Code
and the National Fire Protection Association Life Safety Code (NFPA 101), as it
relates to types of construction or allowable area requirements, they shall
provide written notification of the perceived conflict to the project architect
or engineer and the other affected agencies. The agency alleging the conflict
will convene a meeting with the other affected agencies to resolve the
conflict. The resolution of the conflict must be unanimous. If the group is
unable to resolve the conflict unanimously, the issue will be referred to the
Arkansas State Fire Marshal for final resolution.
Agreed to as evidenced by the signatures of the participating
Parties for their respective offices or associations below:
Click here to view
image
[A]
104.3.2
State Fire Marshal jurisdiction.
(a) The State Fire Marshal's Office has
statewide jurisdiction to inspect all places in Arkansas insofar as it is
necessary for the enforcement of all laws, ordinance and law, or ordinances and
lawful orders requiring any place to be safe from fire. The State Fire Marshal
or his/her duly authorized representative(s) shall be charged with the
enforcement of his Code as granted under the authority of Act 254 of 1955, as
amended.
(b) The fire official
shall have primary responsibility for the safety of places in his/her own
district, city or county. Rules of the State Fire Marshal's Office establishing
minimum standards shall not prevent any district, city or county from enacting
more stringent regulations; and the State Fire Marshal's Office shall cooperate
with the fire official in enforcing all fire safety laws and ordinances of the
state or its political subdivisions. Inspections of property in the territory
served by the fire department shall be made as often as practicable or as often
as the city or county legislative body or other political subdivision fire
officials may direct.
(c) A written
report of continued violations should be sent to the State Fire Marshal, who
will cooperate with local authorities to secure compliance with the
Arkansas Fire Prevention Code and other laws, ordinances and
rules of the state and its political subdivisions relating to matters within
the scope and jurisdiction of the State Fire Marshal's Office.
(d) Town, city or County building Officials:
when a jurisdiction establishes a building department and a building official
as set out in Volume II. Section 103 of the Code, the primary responsibility
for administering and enforcing Volume II (Building Code) of the AFPC shall
fall to that established administrative authority.
[A] 104.10.3
Performance Based
Options. When acceptable to the building official, the most current
edition of the ICC Performance Code for Buildings and Facilities or the SFPE
Engineering Guide to Performance Based Fire Protection may be
followed.
[A] 104.11.2
Report
of fire fatalities. Fire departments responding to fires resulting in a
fatal injury shall report in writing such fatalities to the State Fire
Marshal's Office within three (3) business days of the occurrence.
[A] 104.11.3
Changes in fire department
information. All fire departments shall submit, on or before June
30th of each year, the name of the officer in
charge, the mailing address and electronic mailing address, telephone and
facsimile numbers of the fire department and other information to the State
Fire Marshal's Office on a form provided by the State Fire Marshal's Office.
Any change in the pertinent information during the year shall be sent to the
State Fire Marshal's Office in writing, no later than thirty (30) days after
the change occurs.
[A] 104.11.4
Reports of fireworks accidents. Accidents involving fireworks
resulting in death, serious injury, or major property damage shall be reported
immediately to the State Fire Marshal's Office by the responding fire or police
department or the holder of a fireworks license or public display
permit.
[A] 105.1.1
Permits
required. Where required by the
fire code official, a
property
owner or
owner's authorized agent
who intends to conduct an operation or business or install or modify systems
and equipment that are regulated by this code, or to cause any such work to be
performed, shall first make application to the
fire code
official and obtain the required permit.
[A]
105.1.1.1
General. Fireworks licenses or public display
permits. Permits shall be obtained as required below. Such permits will
be issued when the requirements of the State Fire Marshal's office have been
met; and they may be suspended or revoked if the requirements are violated.
Application for "State Permits" required as follows, shall be made in writing,
on forms required, to the State Fire Marshal, Arkansas State Police, 1 State
Police Plaza Drive, Little Rock, AR 72209-2971. The State Fire Marshal's Office
telephone number is 501-618-8624 until further notice.
1.
Fees. No fee is required for
a state fireworks license or public display permit except as prescribed for
licenses relating to fireworks and except as hereafter otherwise provided by
law and these rules.
2.
State
Permits. A permit or license shall be obtained from the State Fire
Marshal for:
(a) Dealing in fireworks as set
out in state fireworks laws;
(b)
Public fireworks display permit for indoor and outdoor displays; and
(c) Installation of aboveground storage tanks
for combustible liquids, flammable liquids, and hazardous chemicals.
Exception:
1) Tanks that are part of emergency generator
systems.
2) Temporary tanks (period
of use not to exceed six (6) months).
3) Tanks less than 500 gallons in capacity
and not used for retail dispensing.
3.
Local Permits. Where
provisions are made by a municipality or county or other political subdivision
of the state for the issuance of permits, and where such rules are at least as
stringent as those of the State Fire Marshal, a permit from an authorized city
or county official or other political subdivision official shall be obtained
for the construction or substantial remodeling of any:
a) Asylums, hospitals, nursing or
convalescent homes, or other health care facilities, regardless of
capacity.
b) Schools and
educational institutions having a capacity in excess of 50 pupils, and
residence buildings, including dormitories, having sleeping accommodations for
50 or more persons.
c) Auditoriums,
theaters, indoor stadiums, gymnasiums, churches, or other places of assembly
having a capacity in excess of 100 or more persons.
d) Department stores or factories having a
capacity in excess of 200 persons or for any other building if located within
the city or county fire service jurisdiction or other political subdivision. A
city, county, or other political subdivision of the state may, by ordinance,
set out other permits that may be required for new or existing
structures.
4.
Building Permits. Where a jurisdiction has established a building
department in accordance with Vol. II, Section 103 of the Code, permits within
the corporate limits of the jurisdiction for new construction or remodeling
shall be required in accordance with Vol. II, Section 105 of the
Code.
[A] 105.2
Application. Where required by the fire code
official, an application for a permit under this code shall be made to
the fire code official in such form and detail as prescribed
by the fire code official. Applications for permits shall be
accompanied by such plans as prescribed by the fire code
official.
[A] 105.5
Operational permits. Where required, the fire code
official is authorized to issue operational permits for the operations
set forth in Sections 105.5.2 through 105.5.52.
[A] 105.6
Required construction
permits. Where required, the fire code official is
authorized to issue construction permits for work as set forth in Sections
105.7.1 through 105.7.25.
[A] 111.1
Board of appeals established. Any county or municipality or other
political subdivision may establish a local board of adjustments and appeals to
review orders given by the local fire code official-, and to
consist of five (5) members appointed by the applicable governing
body.
[A] 112.4
Violation
penalties. Persons who shall violate a provision of this code or shall
fail to comply with any of the requirements thereof or who shall erect,
install, alter, repair or do work in violation of the approved
construction documents or directive of the fire code
official, or of a permit or certificate used under provisions of this
code, shall be guilty of a Class A Misdemeanor, punishable by a
fine of not more than $ 1,000.00 dollars or by imprisonment not
exceeding 1 year, or both such fine and imprisonment. Each day
that a violation continues after due notice has been served shall be deemed a
separate offense.
[A] 113.4
Failure to comply. Any person who or other legal entity
(corporation, limited liability company, limited liability partnership, etc.)
which shall continue to work after having been served with a stop work order,
except such work as that person or entity is directed to perform to remove a
violation or unsafe condition, shall be subject to penalties imposed by the
circuit or district court having jurisdiction.
Chapter 2
, Definitions.
201.3
Terms defined in other
codes. Where terms arc not defined in this code and are defined in the
International Mechanical Code. Arkansas Fire Prevention Code, Volume
II, The Arkansas Fuel Gas Code, or
The Arkansas Plumbing
Code, such terms shall have the meanings ascribed to them as in those
codes.
[BG] Educational Group E. Educational Group E
occupancy includes, among others, the use of a building or structure, or a
portion thereof, by six or more persons at any one time for educational
purposes through the 12th grade. Rooms normally
occupied by preschool, kindergarten, or first grade students shall be located
on a level of exit discharge. Rooms normally occupied by second grade students
shall not be located more than one level above the level of exit discharge
unless provided with a dedicated and independent means of egress.
[BG] Accessory to places of religious worship.
Religious educational rooms and religious auditoriums, which are
accessory to places of religious worship in accordance with Section 303.1.4 of
the Arkansas Fire Prevention Code, Volume // and have
occupant loads of less than 100 per room or space shall be
classified as Group A-3 occupancies.
[BG] Institutional Group 1-4, day care facilities.
Institutional Group 1-4 shall include buildings and structures occupied
by more than five persons of any age who receive custodial care for less than
24 hours by persons other than parents or guardians; relatives by blood,
marriage, or adoption; and in a place other than the home of the person cared
for. Rooms normally occupied by preschool, kindergarten, or first grade
students shall be located on a level of exit discharge. Rooms normally occupied
by second grade students shall not be located more than one level above the
level of exit discharge unless provided with a dedicated and independent means
of egress. This group shall include, but not be limited to, the following:
Adult day care
Child day care
Chapter 3
, General Requirements
303.10
Scan roof for hot spots.
At the end of day or work period, the roof work shall be scanned (checked) with
a heat source meter or electronic scanner to determine any hot spots on wood
curbs, cants or roof projections on the completed roof which could smolder or
combust after workers leave the job. An acceptable alternative to scanning the
roof is to monitor the roof for a minimum of three (3) hours before workers
leave the job site.
307.4.4
Construction Warming Fires. Unless prohibited by local or county
ordinance or by local burn ban, warming fires shall be allowed when
temperatures are below 32 degrees Fahrenheit. Warming fires must be contained
in a non-combustible container with a spark arrestor. Warming fires shall not
be located within twenty-five (25) feet of any combustible structure or within
ten (10) feet of a roadway. Only vegetation and non-treated lumber will be
allowed to be used for fuel.
SECTION 319
MOBILE FOOD PREPARATION VEHICLES
******LEAVE FOR LOCAL
ADOPTION******
Chapter 4
, Emergency Planning and
Preparedness-No changes
Chapter
5
, Fire Service Features
503.2.1
Dimensions. Fire
apparatus access roads shall have an unobstructed width of not less than 20
feet (6096 mm), exclusive of shoulders and curbs, except for
approved security gates in accordance with Section 503.6, and
an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm).
503.2.1.1
Divided Entrance. When
guard houses, security stations, medians, or other similar obstructions arc so
located as to create a divided entrance or fire lane, each individual lane
shall be a minimum of 15 feet clear width on each side of the obstruction. Such
divisions arc not permitted adjacent to fire hydrants or fire department
connections, or at any location where a fire apparatus vehicle is expected to
be positioned for the duration of a fire event.
503.3
Marking. Where required by
the fire code official, approved signs or other
approved notices or markings that include the words "NO
PARKING-FIRE LANE" shall be provided for fire apparatus access roads to
identify such roads or prohibit the obstruction thereof. The means by which
fire lanes are designated shall be maintained in a clean and
legible condition at all times and be replaced or repaired when necessary to
provide adequate visibility. Signs shall be located at each end of a painted
curb, and additionally in between so that the maximum separation between the
signs is 100 feet (30 mm) as measured along the centerline of the fire
apparatus road or as approved by the fire code official or local authority
having jurisdiction.
506.1
Where required. Where access to or within a structure or an area
is restricted because of secured openings or where immediate access is
necessary for life-saving or firefighting purposes, the
fire code
official is authorized to require a key box to be installed in an
approved location. The key box shall be of an
approved type
listed in accordance with UL
1037, and shall contain keys to gain necessary access as required by the
fire code official.
Exception: Occupancies requiring restricted access
by specific State statutes or Rule.
507.4
Water supply test. The
fire code official shall be notified prior to the water supply
test. Water supply tests shall be witnessed by the fire code
official or approved documentation of the test shall
be provided to the fire code official prior to final approval
of the water supply system. Water supply tests shall be conducted within six
(6) months of hydraulic calculation submittal.
Chapter 6
, Building Services And
Systems
[M] 606.1
General.
Commercial kitchen exhaust hoods shall comply with the requirements of the
International Mechanical Code.
[M] 606.2
Where required. A Type
I hood shall be installed at or above all commercial cooking appliances and
domestic cooking appliances used for commercial purposes that produce grease
vapors. A residential hood is allowed for protection of domestic cooking
appliances in day care facilities that meet requirements of Section 904.14,
Arkansas Fire Prevention Code, Volume I.
606.2.1
Where required-retroactive in
existing buildings or structures. A residential hood shall be installed
in all day care and 1-4 occupancies serving 16 or more persons.
Chapter 7
, Fire
And Smoke Protection Features
701.2.2
Permanent Marking and Notification in New Construction. All Fire
Walls, Fire Barriers, Fire Partitions, and Smoke Partitions shall be
effectively and permanently identified with signs or stenciling in a manner
acceptable to the authority having jurisdiction. Such identification shall be
above any decorative or finish ceiling and in concealed spaces, attics, and
crawl spaces.
Chapter 8
, Interior Finish, Decorative Materials And Furnishings
803.3.1
Interior finish requirements -
day care occupancies. Interior finish requirements shall apply to all
areas used for day care and that are part of the means of egress in day care
facilities serving 10 or fewer clients, located in the care givers home.
Chapter 9
, Fire
Protection And Life Safety Systems
903.2.8
Group R. An
automatic sprinkler system installed in accordance with
Section 903.3 shall be provided throughout all buildings with a Group R
fire area.
Exception: R-2 Live/work units
and R-3 Lodging houses with five (5) or fewer
guestrooms.
903.2.9.4
Group S-l upholstered furniture and mattresses. An
automatic
sprinkler system shall be provided throughout a Group S-l
fire
area where the area used for the storage of upholstered furniture or
mattresses exceeds 2,500 square feet (232 m2).
Exception: Self-service storage facilities not
greater than one story above grade plane where all storage spaces can be
accessed directly from the exterior. Self-service storage facilities with
interior only access not greater than 5,000 square feet (464 m2).
903.3.1
Standards.
Sprinkler systems shall be designed and installed in accordance with Section
903.3.1.1, unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and
other chapters of this code, as applicable. A minimum of 5 psi safety factor
shall be provided between the hydraulic calculated system demand and the
available water supply.
904.14
Domestic cooking facilities. Cooktops and ranges installed in the
following occupancies shall be protected in accordance with Section 904.14.1:
1. In Group 1-4 occupancies where domestic
cooking facilities are installed in accordance with Section 420.9 of the
International Building Code.
2. In Group 1-2 occupancies where domestic
cooking facilities are installed in accordance with Section 407.2.7 of the
International Building Code.
3. In Group R-2 college dormitories where
domestic cooking facilities are installed in accordance with Section 420.11 of
the International Building Code.
4. New and existing day care facilities shall
be provided with automatic fire-extinguishing systems for cooking appliances
utilizing a cooking surface. Automatic fire-extinguishing systems designed for
residential use arc allowed for protection of domestic cooking appliances.
Exception: In-home day care licensed for 16 or
fewer children and all of (he following requirements arc met:
1. The license holder resides in the
home.
2. The licensed care giver
resides in the home.
3. A signed
agreement to not conduct cooking that produces grease laden vapors during the
hours of day care operation is provided.
907.1.2
Fire alarm shop
drawings. Shop drawings for fire alarm systems shall be prepared in
accordance with NFPA 72 and submitted for review and approval prior to system
installation. Final as-built drawings shall be submitted as required by the
authority having jurisdiction. Shop drawings shall include, but not be limited
to, all of the following:
1. Project name and
address. Owner's name address and phone number.
2. Contractor name, address, phone number,
license number, license classification, and license limit.
3. Occupancy classification for building and
each area including occupant load.
4. Fire alarm circuit classification
(power-limited),
5. Class/style
designation of all initiating devise circuit (IDC), signaling circuits (SLC),
and notification appliance circuits (NAC).
6. Conductor type and size.
7. Sequence of operation input/output matrix
as required by NFPA 72.
8. Symbol
legend with equipment description (manufacture's name and model number) and
mounting description (surface, semi-flush, flush, and exterior).
9. When required by the fire code official
symbols used on the shop drawings shall follow NFPA 170.
10. Site plan.
11. Floor plan drawn to an indicated scale
(1/8 inch minimum) on sheets of a uniform size showing:
a. Point of compass (north arrow).
b. Key plans.
c. Walls, doors, windows, stairs, elevators,
high piled storage racks, etc. as needed to indicate all conditions and
requirements.
d. Room use
identification labels.
e. Alarm
initiating devise, notification appliance, and auxiliary controlled or
monitored equipment and systems, control and annunciation equipment
location(s).
f. Conductor/conduit
routing and size.
g. Location of
end-of-linc resistors.
h. Device
address.
i. Notification appliance
numbering by circuit and devise corresponding to the riser and/or one line
diagrams.
j. Power panels and
circuits connections.
k. Ceiling
heights and construction (i.e., beam, joist, soffit, or projection extending
below the ceiling when a ceiling mounted devise device and/or appliance is
used).
12. Mounting
height detail for wall mounted device and/or appliance.
13. Riser diagram including the following
information:
a. General arrangement of the
system, in building cross section.
b. Wall/shaft/stairwell and/or cable ratings
when survivability or class A requirements apply.
c. Type and number of circuits in each
riser.
d. Type and number of fire
alarm system components /devices on each circuit, on each floor or
level.
14. Standardized
calculations:
a. Battery (all
panels)
b. Load (all notification
appliance and auxiliary circuits).
c. Voltage drop (all notification appliance
circuits, including remote annunciators and auxiliary appliances).
15. Project data
submittal including a cover index sheet listing products used by make and model
number, manufacturer data sheets and listing information for all equipment,
devices, materials, wire and cable.
16. Design number and detail of penetration
fire stop system where required.
17. Any additional information determined
necessary by the Fire Code Official.
907.2.3
Group E. A manual fire
alarm system that initiates the occupant notification signal utilizing an
emergency voice/alarm communication system meeting the requirements of Section
907.5.2.2 and installed in accordance with Section 907.6 shall be installed in
Group E occupancies. Where
automatic sprinkler systems or
smoke detectors are installed, such systems or detectors shall be connected to
the building fire alarm system. The provisions of Section 907.2.3.1 through
907.2.3.3 shall apply in rooms normally occupied by preschool or kindergarten
students when used for sleeping.
Exceptions:
1. A manual fire alarm system shall not be
required in Group E occupancies with an occupant load of 50 or
less.
2. Emergency voice/alarm
communication systems meeting the requirements of Section 907.5.2.2 and
installed in accordance with Section 907.6 shall not be required in Group E
occupancies with occupant loads of 100 or less, provided that activation of the
manual fire alarm system initiates an approved occupant
notification signal in accordance with Section 907.5.
3. Manual fire alarm boxes shall not be
required in Group E occupancies where all of the following apply:
3.1.1. Interior corridors
are protected by smoke detectors.
3.1.2. Auditoriums, cafeterias, gymnasiums,
and similar areas are protected by heat detectors or other
approved detection devices.
3.1.3. Shops and laboratories involving dusts
or vapors are protected by heat detectors or other
approved detection devices.
3.1.4. Manual activation is provided from a
normally occupied location.
4. Manual fire alarm boxes shall not be
required in Group E occupancies where all of the following apply:
4.1. The building is equipped throughout with
an approved automatic sprinkler system installed in accordance
with Sections 903.3.1.1.
4.2. The
emergency voice/alarm communication system will activate on sprinkler water
flow.
4.3. Manual activation is
provided from a normally occupied location.
907.2.3.1
Day care facilities.
Day care facilities with an occupant load of 30 or less shall be protected with
single or multiple station smoke alarms in the following places:
1. On the ceiling or wall outside of each
room used for sleeping (in the immediate vicinity of the room).
2. In each day care room used for
sleeping.
907.2.3.2
Interconnection. Where more than one smoke alarm is required to be
installed the smoke detectors shall be interconnected in such a manner that the
activation of one alarm will activate all of the alarms. Physical
interconnection of smoke alarms shall not be required where listed wireless
alarms are installed and all alarms sound upon activation of one
alarm.
907.2.3.3
Power
source. In new construction, required smoke alarms shall receive their
primary power from the building wiring where such wiring is served from a
commercial source and shall be equipped with a battery backup. Smoke alarms
with integral strobes that are not equipped with battery back-up shall be
connected to an emergency electrical system. Smoke alarms shall emit a signal
when the batteries arc low. Wiring shall be permanent and without a
disconnecting switch other than as required for overcurrent protection.
Exception: Smoke alarms arc not required to be
equipped with battery backup where they are connected to an emergency
electrical system.
907.2.11
Single and multiple-station
smoke alarms.
Listed single- and multiple-station smoke
alarms complying with UL 217 shall be installed in accordance with Sections
907.2.11.1 through 907.2.11.7 and NFPA 72. Every new and existing dwelling,
including one and two family dwellings, and every new and existing dwelling
unit within an apartment house, condominium, or townhouse, and every guest and
sleeping room in a motel, hotel, or dormitory shall be provided with an
approved listed smoke alarm.
907.5.2.3.1
Public use areas and common
use areas. Visible alarm notification appliances shall be provided in
public use areas and common use areas. Areas
considered public and common by the NFPA, ADAAG, and The Arkansas School
Facilities Manual shall be included.
907.6.6
Monitoring. Fire alarm
systems required by this chapter or by the
Arkansas Fire Prevention
Code, Volume II shall be monitored by an
approved
supervising station in accordance with NFPA 72.
Exception: Monitoring by a supervising station is
not required for:
1. Single and
multiplc-station smoke alarms required by Section 907.2.11.
2. Smoke detectors in Group 1-3
occupancies.
3.
Automatic
sprinkler systems in one- and two-family
dwellings.
4.
Manual fire alarm systems.
913.6
Supervisory conditions.
The following conditions shall be supervised by the fire alarm system as
appropriate for the type of pump supervised:
1. Pump room temperature;
2. Phase loss;
3. Phase reversal;
4. Pump in manual mode.
Chapter 10
, Means
Of Egress-No changes
Chapter
11
, Construction Requirements For Existing Buildings
1103.5.1
Group A-2. Effective
January 1,2027, where alcoholic beverages are consumed in a Group A-2 occupancy
having an occupant load of 300 or more, the fire area
containing the Group A-2 occupancy shall be equipped with an automatic
sprinkler system in accordance with Section
903.3.1.1.
Chapter 12
, Energy Systems-No changes
Chapters
13 through 19
RESERVED-No changes
Chapter 20
, Aviation Facilities-No
changes
Chapter 21
,
Dry Cleaning-No changes
Chapter
22
, Combustible Dust-Producing Operations-No
changes
Chapter 23
,
Motor Fuel-Dispensing Facilities And Repair Garages
2301.1
Scope. Automotive motor
fuel-dispensing facilities, marine motor fuel-dispensing facilities, fleet
vehicle motor fuel-dispensing facilities, aircraft motor-vehicle
fuel-dispensing facilities and repair garages shall be in accordance with this
chapter and the International Mechanical Code, Arkansas Fire Prevention
Code, Volume II, and the Arkansas Gas Code. Such
facilities shall include both those that are open to the public and private
operations.
2304.3.6
Communications. Deleted in its entirety.
2304.3.7
Quantity limits.
Dispensing equipment used at unsupervised locations shall comply with one of
the following:
1. Dispensing devices shall be
programmed or set to limit uninterrupted fuel delivery to 35 gallons (133
Liters) for cars, pickups, vans, and similar small vehicles: and 100 gallons
per transaction at facilities serving large trucks and requiring a manual
action to resume delivery.
2. The
amount of fuel being dispensed shall be limited in quantity by a preprogrammed
card as approved.
2306.2.3
Above-ground tanks located
outdoors, above grade. Above-ground tanks shall not be used for the
storage of Class I, II, or III liquid motor fuels, except as provided by this
section.
1. Above-ground tanks used for
outdoor, above-grade storage of Class I liquids shall be designed, constructed,
and maintained in accordance with 1 or more of the following nationally
recognized engineering standards and shall be in accordance with Chapter 57.
Such tanks shall be located in accordance with Table 2306.2.3.
4.1. Atmospheric tanks: API Standard 650, API
Specifications 12B, 12D, or 12F, UL 80, UL 142, UL 2080, or UL 2085.
4.2. Low-pressure tanks: ASME Boiler and
Pressure Vessel Code, Section VIII or API Standard 620.
4.3. Pressure Vessels: ASME Boiler and
Pressure Vessel Code, Section VIII.
2. Above-ground tanks used for above-grade
storage of Class II or III A liquids are allowed to be protected above-ground
tanks or, when approved by the fire code official, other above-ground tanks
that comply with Chapter 57. Tank locations shall be in accordance with Table
2306.2.3.
Exception: Other above-ground tanks that comply
with Chapter 57 where approved by the fire code
official.
3. Tanks
containing fuels shall not exceed 12,000 (45 420 L) in individual capacity or
48,000 gallons (181 680 L) in aggregate capacity. Installations with the
maximum allowable aggregate capacity shall be separated from other such
installations by not less than 100 feet (30 480 mm).
4. Tanks located at farms, construction
projects, or rural areas shall comply with Section 5706.2.
5. Above-ground tanks used for outdoor,
above-grade storage of Class IIIB liquid motor fuel shall be
listed and labeled in accordance with UL 142
or listed and labeled as protected
above-ground tanks in accordance with UL 2085 and shall be installed in
accordance with Chapter 57. Tank locations shall be in accordance with Table
2306.2.3.
Chapter
24
, Flammable Finishes-No changes
Chapter 25
, Fruit and Crop Ripening-No
changes
Chapter 26
,
Fumigation and Insecticidal Fogging-No changes
Chapter 27
, Semiconductor Fabrication
Facilities-No changes
Chapter
28
, Lumber Yards and Agro-industrial, Solid Biomass and
Woodworking Facilities-No changes.
Chapter
29
, Manufacture of Organic Coatings-No
changes
Chapter 30
,
Industrial Ovens-No changes
Chapter
31
, Tents, Temporary Structures and Other Membrane
Structures-No changes
Chapter
32
, High-piled Combustible Storage-No
changes
Chapter 33
,
Fire Safety during Construction and Demolition-No changes
Chapter 34
, Tire Rebuilding and Tire
Storage-No changes
Chapter 35
, Welding and Other Hot Work-No changes
Chapter 36
, Marinas-No
changes
Chapter 37
,
Combustible Fibers-No changes
Chapter
38
, Higher Education Laboratories-No
changes
Chapter 39
,
Processing and Extraction Facilities-No changes
Chapter 40
, Storage of Distilled
Spirits and Wines-No change
Chapter
50
, Hazardous Materials-General Provisions-No
changes
Chapter 51
,
Aerosols-No changes
Chapter
53
, Compressed Gasses-No changes
Chapter 54
, Corrosive Materials-No
changes
Chapter 55
,
Cryogenic Fluids-No changes
Chapter
56
, Explosives and Fireworks-No changes
Chapter 57
, Flammable And Combustible
Liquids
5704.2.12.2
Testing of
underground tanks. Before being covered or placed in use, tanks and
piping connected to underground tanks shall be tested for tightness. Piping
shall be tested in accordance with Section 5702.6.3. The system shall not be
covered until it has been approved.
5704.2.13.2.2
Out of service for 90
days. Above-ground tanks not used for a period of 90 days shall be
safeguarded in accordance with Section 5704.2.13.1.2 or removed in accordance
with Section 5704.2.14.
Exceptions:
1. Tanks and containers connected to oil
burners that are not in use during the warm season of the year or are used as a
backup heating system to gas.
2.
In-place, active fire protection (foam) system lines.
3. Farm tanks used for irrigation wells or
other farm uses.
Chapter
58
, Flammable Gases and Flammable Cryogenic Fluids-No
changes
Chapter 59
,
Flammable Solids-No changes
Chapter
60
, Highly Toxic and Toxic Materials-No
changes
Chapter 61
,
Liquefied Petroleum Gases-Delete this chapter in its entirety. Refer instead to
the Arkansas Liquefied Petroleum Gas Code.
Chapter 62
, Organic Peroxides-No
changes
Chapter 63
,
Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids-No
changes
Chapter 64
,
Pyrophoric Materials-No changes
Chapter
65
, Pyroxylin (Cellulose Nitrate) Plastics-No
changes
Chapter 66
,
Unstable (Reactive) Materials-No changes
Chapter 67
, Water-reactive Solids and
Liquids-No changes
Chapter 80
, Referenced Standards-No changes
Appendix A, Board of Appeals-Delete in its
entirety
Appendix B, Fire-flow Requirements for Buildings-No
changes
Appendix C, Fire Hydrant Locations and Distribution-No
changes
Appendix D, Fire Apparatus Access Roads
D10L1
Scope. Fire apparatus
access roads shall be in accordance with this appendix and all other applicable
requirements of the Arkansas Fire Prevention Code. Requests
for exceptions to Appendix D may be appealed to the State Fire
Marshal.
D103.6
Signs.
Where required by the fire code official, fire apparatus
access roads shall be marked with permanent "NO PARKING-FIRE LANE" signs
complying with Figure DI03.6. Signs shall have a minimum dimension of 12 inches
(305 mm) wide by 18 inches (457 mm) high and have red letters on a white
reflective background. Signs shall be located at each end of a painted curb and
additionally in between so that the maximum separation between the signs is 100
feet (30 m) as measured along the centerline of the fire apparatus access road,
or as approved by the fire code official or the authority having jurisdiction.
Signs shall be posted on one or both sides of the fire apparatus road as
required by Section D103.6.1 or D103.6.2.
Appendix E, Hazard Categories-No changes
Appendix F, Hazard Ranking-No changes
Appendix G, Cryogenic Fluids-Weight and Volume
Equivalents-No Change
Appendix H, Hazardous Materials Management Plan (HMMP)
and Hazardous Materials Inventory Statement (HMIS) Instructions-No
change
Appendix I, Fire Protection Systems-Noncompliant
Conditions-No changes
Appendix J, Building Information Sign-No
change
Appendix K, Construction Requirements for Existing
Ambulatory Care Facilities-No changes
Appendix L, Requirements for Fire Fighter Air
Replenishment Systems-No changes
Appendix M, High-Rise Buildings-Retroactive Automatic
Sprinkler Requirement-No changes
Appendix N, Indoor Trade Shows and Exhibitions-No
changes
Appendix O, Day Care Facilities Compilation
Appendix O DAY CARE FACILITIES COMPILATION
0101.1
General. This appendix is
a compilation of sections from Volumes I and II of the Arkansas Fire Prevention
Code, They have been brought together here as a reference guide. Every effort
was made to ensure a complete reference; however, this section exists as an aid
and is not intended as a substitute for the applicable provisions of the
Arkansas Fire Prevention Code, Volumes I, II, and III.
0101.2
Paragraph notation. All
of the following sections will retain their original paragraph designation in
order to provide their location within the code and avoid any confusion
associated with renumbering these requirements.
0101.3
Applicability. This is a
summarized portion of the 2021 Arkansas Fire Prevention Code covering the basic
requirements for Day Care Facilities. It should be understood that some
systems, components, structures, and/or conditions may need to be specifically
evaluated for their compliance to the Arkansas Fire Prevention Code and/or its
referenced standards. There are conditions that warrant evaluation on a
case-by-case basis for code compliance.
[B] IBC
305.1
Educational Group E. Educational Group E
occupancy includes, among others, the use of a building or structure, or a
portion thereof, by six or more persons at any one time for educational
purposes through the 12th grade. Rooms normally occupied by preschool,
kindergarten or first-grade students shall be located on a level of exit
discharge. Rooms normally occupied by second-grade students shall not be
located more than one level above the level of exit discharge unless provided
with a dedicated and independent means of egress.
[B] IBC
305.1.1
Accessory to places of religious worship.
Religious educational rooms and religious auditoriums, which are accessory to
places of religious worship in accordance with Section 303.1.4 and have
occupant loads of less than 100 per room or space, shall be classified as Group
A-3 occupancies.
[B] IBC
305.2
Group E, day care facilities. This group
includes buildings and structures, or portions thereof occupied by more than
five children older than 2 1/2 years of age who receive educational,
supervision or personal care services for fewer than 24 hours per day.
[B] IBC 305.2.1
Within places of
religious worship. Rooms and spaces within places of religious worship
providing such day care during religious functions shall be classified as part
of the primary occupancy.
[B] IBC
305.2.2
Five or fewer children. A facility having
five or fewer children receiving such day care shall be classified as part of
the primary occupancy.
[B] IBC
305.2.3
Five or fewer children in a dwelling unit. A
facility such as the above within a dwelling unit and having five or fewer
children receiving such day care shall be classified as a Group R-3 occupancy
or shall comply with the International Residential Code.
[B] IBC 305.3
Storm shelters in Group E
occupancies. Storm shelters shall be provided for Group E occupancies
where required by Section 423.5.
[B] IBC
308.5
Institutional Group 1-4, day care facilities.
Institutional Group 1-4 occupancy shall include buildings and structures
occupied by more than five persons of any age who receive custodial care for
fewer than 24 hours per day by persons other than parents or guardians;
relatives by blood, marriage or adoption; and in a place other than the home of
the person cared for. Rooms normally occupied by preschool, kindergarten or
first-grade students shall be located on a level of exit discharge. Rooms
normally occupied by second-grade students shall not be located more than one
level above the level of exit discharge unless provided with a dedicated and
independent means of egress. This group shall include, but not be limited to,
the following:
Adult day care
Child day care
[B] IBC
308.5.1
Classification as Group E. A child day care
facility that provides care for more than five but not more than 100 children 2
1/2 years or less of age, where the rooms in which the children are cared for
arc located on a level of exit discharge serving such rooms and each of these
child care rooms has an exit door directly to the exterior, shall be classified
as Group E.
[B] IBC 308.5.2
Within a place of religious worship. Rooms and spaces within
places of religious worship providing such care during religious functions
shall be classified as part of the primary occupancy.
[B] IBC 308.5.3
Five or fewer persons
receiving care. A facility having five or fewer persons receiving
custodial care shall be classified as part of the primary occupancy.
[B] IBC 308.5.4
Five or fewer persons
receiving care in a dwelling unit. A facility such as the above within a
dwelling unit and having five or fewer persons receiving custodial care shall
be classified as a Group R-3 occupancy or shall comply with the International
Residential Code.
AUTOMATIC SPRINKLER SYSTEM
903.2.3
Group E. An automatic
sprinkler system shall be provided for Group E occupancies as follows:
1. Throughout all Group E fire areas greater
than 12,000 square feet (1115 m2) in area.
2. The Group E lire area is located on a
floor other than a level of exit discharge serving such occupancies.
Exception: In buildings where every classroom has
not fewer than one exterior exit door at ground level, an automatic sprinkler
system is not required in any area below the lowest level of exit discharge
serving that area.
3. The
Group E fire area has an occupant load of 300 or more.
903.2.6
Group I. An automatic
sprinkler system shall be provided throughout buildings with a Group I fire
area.
Exceptions:
1. An automatic sprinkler system installed in
accordance with Section 903.3.1.2 shall be permitted in Group 1-1, Condition 1
facilities.
2. An automatic
sprinkler system is not required where Group I-4-day care facilities arc at the
level of exit discharge and where every room where care is provided has not
fewer than one exterior exit door.
3. In buildings where Group 1-4 day care is
provided on levels other than the level of exit discharge, an automatic
sprinkler system in accordance with Section 903.3.1.1 shall be installed on the
entire floor where care is provided, all floors between the level of care and
the level of exit discharge and all floors below the level of exit discharge
other than areas classified as an open parking garage.
MANUAL FIRE ALARM
907.2.3
Group E. A manual fire
alarm system that initiates the occupant notification signal utilizing an
emergency voice/alarm communication system meeting the requirements of Section
907.5.2.2 and installed in accordance with Section 907.6 shall be installed in
Group E occupancies. Where automatic sprinkler systems or smoke detectors are
installed, such systems or detectors shall be connected to the building fire
alarm system. The provisions of Section 907.2.3.1 shall apply in rooms normally
occupied by preschool or kindergarten students when used for sleeping.
Exceptions:
1. A manual fire alarm system shall not be
required in Group E occupancies with an occupant load of 50 or less.
2. Emergency voice/alarm communication
systems meeting the requirements of Section 907.5.2.2 and installed in
accordance with Section 907.6 shall not be required in Group E occupancies with
occupant loads of 100 or less, provided that activation of the manual fire
alarm system initiates an approved occupant notification signal in accordance
with Section 907.5.
3. Manual fire
alarm boxes shall not be required in Group E occupancies where all of the
following apply:
3.1. Interior corridors are
protected by smoke detectors.
3.2.
Auditoriums, cafeterias, gymnasiums and similar areas are protected by heat
detectors or other approved detection devices.
3.3. Shops and laboratories involving dusts
or vapors are protected by heat detectors or other approved detection
devices.
3.4. Manual activation is
provided from a normally occupied location.
4. Manual fire alarm boxes shall not be
required in Group E occupancies where all of the following apply:
4.1. The building is equipped throughout with
an approved automatic sprinkler system installed in accordance with Section
903.3.1.1.
4.2. The emergency
voice/alarm communication system will activate on sprinkler water
flow.
4.3. Manual activation is
provided from a normally occupied location.
907.2.3.1
Day care facilities.
Day care facilities with an occupant load of 30 or less shall be protected with
single or multiple station smoke alarms in the following places:
1. On the ceiling or wall outside of each day
care room used for sleeping (in the immediate vicinity of the room).
2. In each day care room used for
sleeping.
907.2.3.2
Interconnection. Where more than one smoke alarm is required to be
installed, the smoke detectors shall be interconnected in such a manner that
the activation of one alarm will activate all of the alarms. Physical
interconnection of smoke alarms shall not be required where listed wireless
alarms are installed and all alarms sound upon activation of one
alarm.
907.2.3.3
Power
source. In new construction, required smoke alarms shall receive their
primary power from the building wiring where such wiring is served from a
commercial source and shall be equipped with a battery backup. Smoke alarms
with integral strobes that are not equipped with battery back-up shall be
connected to an emergency electrical system. Smoke alarms shall emit a signal
when the batteries are low. Wiring shall be permanent and without a
disconnecting switch, other than as required for overcurrent protection.
Exception: Smoke alarms are not required to be
equipped with battery backup where they arc connected to an emergency
electrical system.
907.2.6
Group
I. A manual fire alarm system that activates the occupant notification
system in accordance with Section 907.5 shall be installed in Group I
occupancies. An automatic smoke detection system that activates the occupant
notification system in accordance with Section 907.5 shall be provided in
accordance with Sections 907.2.6.1..6.2 and 907.2.6.3.3.
Exceptions:
1. Manual fire alarm boxes in sleeping units
of Group 1-1 and 1-2 occupancies shall not be required at exits if located at
all care providers' control stations or other constantly attended staff
locations, provided that such manual fire alarm boxes arc visible and provided
with ready access, and the distances of travel required in Section 907.4.2.1
are not exceeded.
2. Occupant
notification systems arc not required to be activated where private mode
signaling installed in accordance with NFPA 72 is approved by the fire code
official and staff evacuation responsibilities are included in the fire safety
and evacuation plan required by Section 404.
AUTOMATIC SMOKE DETECTION
907.2.3.1
Day care facilities.
Day care facilities with an occupant load of 30 or less shall be protected with
single or multiple station smoke alarms in the following places:
1. On the ceiling or wall outside of each day
care room used for sleeping (in the immediate vicinity of the room).
2. In each day care room used for
sleeping.
907.2.3.2
Interconnection. Where more than one smoke alarm is required to be
installed, the smoke detectors shall be interconnected in such a manner that
the activation of one alarm will activate all of the alarms. Physical
interconnection of smoke alarms shall not be required where listed wireless
alarms arc installed and all alarms sound upon activation of one
alarm.
907.2.3.3
Power
source. In new construction, required smoke alarms shall receive their
primary power from the building wiring where such wiring is served from a
commercial source and shall be equipped with a battery backup. Smoke alarms
with integral strobes that are not equipped with battery back-up shall be
connected to an emergency electrical system. Smoke alarms shall emit a signal
when the batteries are low. Wiring shall be permanent and without a
disconnecting switch, other than as required for overcurrent protection.
Exception: Smoke alarms are not required to be
equipped with battery backup where they arc connected to an emergency
electrical system.
FIRE ALARM MONITORING
907.6.6
Monitoring. Fire alarm
systems required by this chapter or by the Arkansas Fire Prevention Code,
Volume II shall be monitored by an approved supervising station in accordance
with NFPA 72.
Exception: Monitoring by a supervising station is
not required for:
1. Single- and
multiple-station smoke alarms required by Section 907.2.11.
2. Smoke detectors in Group 1-3
occupancies.
3. Automatic sprinkler
systems in one- and two-family dwellings.
COOKING
[M]
606.1
General. Commercial kitchen exhaust hoods shall
comply with the requirements of the International Mechanical Code.
[M] 606.2
Where required. A Type
1 hood shall be installed at or above all commercial cooking appliances and
domestic cooking appliances used for commercial purposes that produce grease
vapors. A residential hood is allowed for protection of domestic cooking
appliances in day care facilities that meet requirements of AFPC 904.14.
Exceptions:
1. Factory-built commercial exhaust hoods
that are listed and labeled in accordance with UL 710, and installed in
accordance with Section 304.1 of the International Mechanical Code, shall not
be required to comply with Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8,
507.3.1, 507.3.3, 507.4 and 507.5 of the International Mechanical
Code.
2. Factory-built commercial
cooking recirculating systems that are listed and labeled in accordance with UL
710B, and installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with Sections 507.1.5,
507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3, 507.4 and 507.5 of the
International Mechanical Code. Spaces in which such systems arc located shall
be considered to be kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code. For the purpose of determining
the floor area required to be ventilated, each individual appliance shall be
considered as occupying not less than 100 square feet (9.3
m2).
3.
Where cooking appliances are equipped with integral down-draft exhaust systems
and such appliances and exhaust systems are listed and labeled for the
application in accordance with NFPA 96, a hood shall not be required at or
above them.
4. A Type I hood shall
not be required for an electric cooking appliance where an approved testing
agency provides documentation that the appliance effluent contains 5
mg/m3 or less of grease when tested at an exhaust
flow rate of 500 cfm (0.236m3/s) in accordance with
UL 710B.
606.2.1
Where
required-retroactive in existing buildings or structures. A residential
hood shall be installed in all day care and 1-4 occupancies serving 16 or more
persons.
606.3
Operations and maintenance. Commercial cooking systems shall be
operated and maintained in accordance with Sections 606.3.1 through 606.3.4.
606.3.1
Ventilation system. The
ventilation system in connection with hoods shall be operated at the required
rate of air movement, and grease filters listed and labeled in accordance with
UL 1046 shall be in place where equipment under a kitchen grease hood is
used.
904.2.2
Commercial hood
and duct systems. Each required commercial kitchen exhaust hood and duct
system required by Section 606 to have a Type I hood shall be protected with an
approved automatic fire-extinguishing system installed in accordance with this
code.
904.13
Commercial cooking systems. The automatic fire-extinguishing
system for commercial cooking systems shall be of a type recognized for
protection of commercial cooking equipment and exhaust systems of the type and
arrangement protected. Pre-engineered automatic dry- and wet-chemical
extinguishing systems shall be tested in accordance with UL 300 and listed and
labeled for the intended application. Other types of automatic
fire-extinguishing systems shall be listed and labeled for specific use as
protection for commercial cooking operations. The system shall be installed in
accordance with this code, NFPA 96, its listing and the manufacturer's
installation instructions. Automatic fire extinguishing systems of the
following types shall be installed in accordance with the referenced standard
indicated, as follows:
1. Carbon dioxide
extinguishing systems, NFPA 12.
2.
Automatic sprinkler systems, NFPA 13.
3. Automatic water mist systems, NFPA
750.
4. Foam-water sprinkler system
or foam-water spray systems, NFPA 16.
5. Dry-chemical extinguishing systems, NFPA
17.
6. Wet-chemical extinguishing
systems, NFPA 17A.
Exception: Factory-built commercial cooking
recirculating systems that are tested in accordance with UL 71 OB and listed,
labeled and installed in accordance with Section 304.1 of the International
Mechanical Code.
904.13.1
Manual
system operation. A manual actuation device shall be located at or near
a means of egress from the cooking area not less than 10 feet (3048 mm) and not
more than 20 feet (6096 mm) from the kitchen exhaust system. The manual
actuation device shall be installed not more than 48 inches (1200 mm) nor less
than 42 inches (1067 mm) above the floor and shall clearly identify the hazard
protected. The manual actuation shall require a maximum force of 40 pounds (178
N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression
system.
Exception: Automatic sprinkler systems shall not
be required to be equipped with manual actuation means.
904.13.2
System interconnection.
The actuation of the fire extinguishing system shall automatically shut down
the fuel or electrical power supply to the cooking equipment. The fuel and
electrical supply reset shall be manual.
904.14
Domestic cooking
facilities. Cooktops and ranges installed in the following occupancies
shall be protected in accordance with Section 904.14.1:
1. In Group 1-1 occupancies where domestic
cooking facilities are installed in accordance with Section 420.9 of the
International Building Code.
2. In
Group 1-2 occupancies where domestic cooking facilities are installed in
accordance with Section 407.2.7 of the International Building Code.
3. In Group R-2 college dormitories where
domestic cooking facilities are installed in accordance with Section 420.11 of
the International Building Code.
4.
New and existing day care facilities shall be provided with automatic
fire-extinguishing systems for cooking appliances utilizing a cooking surface.
Automatic fire-extinguishing systems designed for residential use are allowed
for protection of domestic cooking appliances.
Exception: In-home day care licensed for 16 or
fewer children and all the following requirements are met.
1. The licensed holder resides in the
home
2. The licensed care giver
resides in the home
3. Provides a
signed agreement to not produce grease laden vapors during hours of
operation.
DOORS, GATES, TURNSTILES
[BE] 1010.1
Doors. Doors in the
means of egress shall comply with the requirements of Sections 1010.1.1 through
1010.3.4. Exterior exit doors shall also comply with the requirements of
Section 1022.2. Gates in the means of egress shall comply with the requirements
of Sections 1010.4 and 1010.4.1. Turnstiles in the means of egress shall comply
with the requirements of Sections 1010.5 through 1010.5.4. Doors, gates and
turnstiles provided for egress purposes in numbers greater than required by
this code shall comply with the requirements of this section. Doors in the
means of egress shall be readily distinguishable from the adjacent construction
and finishes such that the doors are easily recognizable as doors. Mirrors or
similar reflecting materials shall not be used on means of egress doors. Means
of egress doors shall not be concealed by curtains, drapes, decorations or
similar materials.
[BE] 1010.1.1
Size of
doors. The required capacity of each door opening shall be sufficient
for the occupant load thereof and shall provide a minimum clear opening width
of 32 inches (813 mm), The clear opening width of doorways with swinging doors
shall be measured between the face of the door and the stop, with the door open
90 degrees (1.57 rad). Where this section requires a minimum clear opening
width of 32 inches (813 mm) and a door opening includes two door leaves without
a mullion, one leaf shall provide a minimum clear opening width of 32 inches
(813 mm). In Group 1-2, doors serving as means of egress doors where used for
the movement of beds shall provide a minimum clear opening width of 41 1/2
inches (1054 mm). The minimum clear opening height of doors shall be not less
than 80 inches (2032 mm).
Exceptions:
1. In Group R-2 and R-3 dwelling and sleeping
units that are not required to be an Accessible unit, Type A unit or Type B
unit, the minimum width shall not apply to door openings that are not part of
the required means of egress.
2.
Group 1-3 door openings to resident sleeping units that are not required to be
an Accessible unit shall have a minimum clear opening width of 28 inches (711
mm).
3. Door openings to storage
closets less than 10 square feet (0.93m2) in area
shall not be limited by the minimum clear opening width.
4. The maximum width of door leaves in
revolving doors that comply with Section 1010.3.1 shall not be
limited.
5. The maximum width of
door leaves in power-operated doors that comply with Section 1010.3.2 shall not
be limited.
6. Door openings within
a dwelling unit or sleeping unit shall have a minimum clear opening height of
78 inches (1981 mm).
7. In dwelling
and sleeping units that arc not required to be Accessible, Type A or Type B
units, exterior door openings, other than the required exit door, shall have a
minimum clear opening height of 76 inches (1930 mm).
8. In Groups 1-1, R-2, R-3 and R-4, in
dwelling and sleeping units that are not required to be Accessible, Type A or
Type B units, the mini-mum clear opening widths shall not apply to interior
egress doors.
9. Door openings
required to be accessible within Type B units intended for user passage shall
have a minimum clear opening width of 31.75 inches (806 mm).
10. Doors to walk-in freezers and coolers
less than 1.000 square feet (93m2) in area shall
have a maximum width of 60 inches (1524 mm) nominal.
11. Doors serving non-accessible single-user
shower or sauna compartments; toilet stalls; or dressing, fitting or changing
rooms shall have a minimum clear opening width of 20 inches (508 mm).
[BE] 1010.1.1.1
Projections into clear
opening. There shall not be projections into the required clear opening
width lower than 34 inches (864 mm) above the floor or ground. Projections into
the clear opening width between 34 inches (864 mm) and 80 inches (2032 mm)
above the floor or ground shall not exceed 4 inches (102
mm).
Exception: Door closers, overhead door stops,
power door operators, and electromagnetic door locks shall be permitted to be
78 inches (1980 mm) minimum above the floor.
[BE]
1010.1.2
Egress door types. Egress doors shall be of
the side-hinged swinging door, pivoted door or balanced door types.
Exceptions:
1. Private garages, office areas, factory and
storage areas with an occupant load of 10 or less.
2. Group 1-3 occupancies used as a place of
detention.
3. Critical or intensive
care patient rooms within suites of health care facilities.
4. Doors within or serving a single dwelling
unit in Groups R-2 and R-3.
5. In
other than Group H occupancies, revolving doors complying with Section
1010.3.1.
6. In other than Group H
occupancies, special purpose horizontal sliding, accordion or folding door
assemblies complying with Section 1010.3.3.
7. Power-operated doors in accordance with
Section 1010.3.2.
8. Doors serving
a bathroom within an individual sleeping unit in Group R-l.
9. In other than Group H occupancies,
manually operated horizontal sliding doors are permitted in a means of egress
from spaces with an occupant load of 10 or less.
[BE] 1010.1.2.1
Direction of
swing. Side-hinged swinging doors, pivoted doors and balanced doors
shall swing in the direction of egress travel where serving a room or area
containing an occupant load of 50 or more persons or a Group H
occupancy.
[BE] 1010.1.3
Forces to unlatch and open doors. The forces to unlatch doors
shall comply with the following:
1. Where door
hardware operates by push or pull, the operational force to unlatch the door
shall not exceed 15 pounds (66.7 N).
2. Where door hardware operates by rotation,
the operational force to unlatch the door shall not exceed 28 inch-pounds (315
N-cm).
The force to open doors shall comply with the following:
1. For interior swinging egress doors that
are manually operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5 pounds (22
N).
2. For other swinging doors,
sliding doors or folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set in motion and
shall move to a full-open position when subjected to not more than a 15-pound
(67 N) force.
[BE] 1010.1.3.1
Location of applied forces. Forces shall be applied to the latch
side of the door.
[BE] 1010.1.3.2
Manual horizontal sliding doors. Where a manual horizontal sliding
door is required to latch, the latch or other mechanism shall prevent the door
from rebounding into a partially open position when the door is closed.
[BE] 1010.2.12
Sensor release of electrically locked egress doors. Sensor release
of electric locking systems shall be permitted on doors located in the means of
egress in any occupancy except Group H where installed and operated in
accordance with all of the following criteria:
1. The sensor shall be installed on the
egress side, arranged to detect an occupant approaching the doors and shall
cause the electric locking system to unlock.
2. The electric locks shall be arranged to
unlock by a signal from or loss of power to the sensor.
3. Loss of power to the lock or locking
system shall automatically unlock the electric locks.
4. The doors shall be arranged to unlock from
a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm)
vertically above the floor and within 5 feet (1524 mm) of the secured doors.
Ready access shall be provided to the manual unlocking device and the device
shall be clearly identified by a sign that reads "PUSH TO EXIT." When operated,
the manual unlocking device shall result in direct interruption of power to the
electric lock-independent of other electronics-and the electric lock shall
remain unlocked for not less than 30 seconds.
5. Activation of the building fire alarm
system, where provided, shall automatically unlock the electric lock, and the
electric lock shall remain unlocked until the fire alarm system has been
reset.
6. Activation of the
building automatic sprinkler system or fire detection system, where provided,
shall automatically unlock the electric lock. The electric lock shall remain
unlocked until the fire alarm system has been reset.
7. Emergency lighting shall be provided on
the egress side of the door.
8. The
door locking system units shall be listed in accordance with UL 294.
[BE] 1010.2.13
Delayed
egress. Delayed egress locking systems shall be permitted to be
installed on doors serving the following occupancies in buildings that are
equipped throughout with an automatic sprinkler system in accordance with
Section 903.3.1.1 or an approved automatic smoke or heat detection system
installed in accordance with Section 907:
1.
Group B, F, 1, M, R, S and U occupancies.
2. Group E classrooms with an occupant load
of less than 50.
3. In courtrooms
in Group A-3 and B occupancies, delayed egress locking systems shall be
permitted to be installed on exit or exit access doors, other than the main
exit or exit access door, in buildings that are equipped throughout with an
automatic sprinkler system in accordance with Section 903.3.1.1.
[BE] 1010.2.13.1
Delayed egress locking
system. The delayed egress locking system shall be installed and
operated in accordance with all of the following:
1. The delay electronics of the delayed
egress locking system shall deactivate upon actuation of the automatic
sprinkler system or automatic fire detection system, allowing immediate, free
egress.
2. The delay electronics of
the delayed egress locking system shall deactivate upon loss of power
controlling the lock or lock mechanism, allowing immediate free
egress.
3. The delayed egress
locking system shall have the capability of being deactivated at the fire
command center and other approved locations.
4. An attempt to egress shall initiate an
irreversible process that shall allow such egress in not more than 15 seconds
when a physical effort to exit is applied to the egress side door hardware for
not more than 3 seconds. Initiation of the irreversible process shall activate
an audible signal in the vicinity of the door. Once the delay electronics have
been deactivated, rearming the delay electronics shall be by manual means only.
Exception: Where approved, a delay of not more
than 30 seconds is permitted on a delayed egress door.
5. The egress path from any point shall not
pass through more than one delayed egress locking system.
Exceptions:
1. In Group 1-1, Condition 2, Group 1-2 or
1-3 occupancies, the egress path from any point in the building shall pass
through not more than two delayed egress locking systems provided that the
combined delay docs not exceed 30 seconds.
2. In Group 1-1, Condition 1 or Group 1-4
occupancies, the egress path from any point in the building shall pass through
not more than two delayed egress locking systems provided that the combined
delay does not exceed 30 seconds and the building is equipped throughout with
an automatic sprinkler system in accordance with Section 903.3.1.1.
6. A sign shall be provided on the
door and shall be located above and within 12 inches (305 mm) of the door exit
hardware:
Exception: Where approved, in Group I occupancies,
the installation of a sign is not required where care recipients who, because
of clinical needs, require restraint or containment as part of the function of
the treatment area.
6.1. For doors
that swing in the direction of egress, the sign shall read: "PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE OPENED IN 15 [30] SECONDS."
6.2. For doors that swing in the opposite
direction of egress, the sign shall read: "PULL UNTIL ALARM SOUNDS. DOOR CAN BE
OPENED IN 15 [30] SECONDS."
6.3.
The sign shall comply with the visual character requirements in ICC Al
17.1.
7. Emergency
lighting shall be provided on the egress side of the door.
8. The delayed egress locking system units
shall be listed in accordance with UL 294
[BE] 1010.2.9
Panic and fire exit
hardware. Swinging doors serving a Group H occupancy and swinging doors
serving rooms or spaces with an occupant load of 50 or more in a Group A or
E occupancy shall not be provided with a latch or lock other than
panic hardware or fire exit hardware.
Exceptions:
1. A main exit of a Group A occupancy shall
be permitted to have locking devices in accordance with Section 1010.2.4, Item
3.
2. Doors provided with panic
hardware or fire exit hardware and serving a Group A or E occupancy shall be
permitted to be electrically locked in accordance with Section 1010.2.12 or
1010.2.11.
3. Exit access doors
serving occupied exterior areas shall be permitted to be locked in accordance
with Section 1010.2.4, Item 8.
4.
Courtrooms shall be permitted to be locked in accordance with Section
1010.2.13, Item 3.
[BE] 1010.2.9.3
Installation. Where panic or fire exit hardware is installed, it
shall comply with the following:
1. Panic
hardware shall be listed in accordance with UL 305.
2. Fire exit hardware shall be listed in
accordance with UL 10C and UL 305.
3. 1 he actuating portion of the releasing
device shall extend not less than one-half of the door leaf width.
4. The maximum unlatching force shall not
exceed 15 pounds (67 N).
MEANS OF EGRESS
[BE]
1008.2
Illumination required. The means of egress
serving a room or space shall be illuminated at all times that the room or
space is occupied.
Exceptions:
1. Occupancies in Group U.
2. Aisle access ways in Group A.
3. Dwelling units and sleeping units in
Groups R-l, R-2 and R-3.
4.
Sleeping units of Group I occupancies.
[BE]
1008.2.1
Illumination level under normal power. The
means of egress illumination level shall be not less than 1 footcandle (11 lux)
at the walking surface. Along exit access stairways, exit stairways and at
their required landings, the illumination level shall be not less than 10
footcandles (108 lux) at the walking surface when the stairway is in use.
Exception: For auditoriums, theaters, concert or
opera halls and similar assembly occupancies, the illumination at the walking
surface is permitted to be reduced during performances by one of the following
methods provided that the required illumination is automatically restored upon
activation of a premises' fire alarm system:
1. Externally illuminated walking surfaces
shall be permitted to be illuminated to not less than 0.2 footcandle (2.15
lux).
2. Steps, landings and the
sides of ramps shall be permitted to be marked with self-luminous materials in
accordance with Sections 1025.2.1, 1025.2.2 and 1025.2.4 by systems listed in
accordance with UL 1994.
[BE] 1008.3
Emergency power for
illumination. The power supply for means of egress illumination shall
normally be provided by the premises' electrical supply.
[BE] 1008.3.1
General. In the
event of power supply failure in rooms and spaces that require two or more
exits or access to exits, an emergency electrical system shall automatically
illuminate all of the following areas:
1.
Aisles.
2. Corridors.
3. Exit access stairways and ramps.
[BE] 1008.3.2
Buildings. In the event of power supply failure, in buildings that
require two or more exits or access to exits, an emergency electrical system
shall automatically illuminate all of the following areas:
1. Interior exit access stairways and
ramps.
2. Interior and exterior
exit stairways and ramps.
3. Exit
passageways.
4. Vestibules and
areas on the level of discharge used for exit discharge in accordance with
Section 1028.2.
5. Exterior
landings as required by Section 1010.1.5 for exit doorways that lead directly
to the exit discharge.
[BE]
1008.3.3
Rooms and spaces. In the event of power
supply failure, an emergency electrical system shall automatically illuminate
all of the following areas:
1. Electrical
equipment rooms.
2. Fire command
centers.
3. Fire pump
rooms.
4. Generator
rooms.
5. Public restrooms with an
area greater than 300 square feet (27.87 m2).
[BE] 1008.3.4
Duration. The
emergency power system shall provide power for a duration of not less than 90
minutes and shall consist of storage batteries, unit equipment or an on-site
generator. The installation of the emergency power system shall be in
accordance with Section 2702 of the International Building Code.
[BE] 1008.3.5
Illumination level under
emergency power. Emergency lighting facilities shall be arranged to
provide initial illumination that is not less than an average of 1 footcandle
(11 lux) and a minimum at any point of 0.1 footcandle (1 lux) measured along
the path of egress at floor level. Illumination levels shall be permitted to
decline to 0.6 footcandle (6 lux) average and a minimum at any point of 0.06
footcandle (0.6 lux) at the end of the emergency lighting time duration. A
maximum-to-mini-mum illumination uniformity ratio of 40 to 1 shall not be
exceeded. In Group 1-2 occupancies, failure of a single lamp in a luminaire
shall not reduce the illumination level to less than 0.2 footcandle (2.2 lux).
EXIT SIGNS
[BE] 1013.1
Where required.
Exits and exit access doors shall be marked by an approved exit sign readily
visible from any direction of egress travel. The path of egress travel to exits
and within exits shall be marked by readily visible exit signs to clearly
indicate the direction of egress travel in cases where the exit or the path of
egress travel is not immediately visible to the occupants. Intervening means of
egress doors within exits shall be marked by exit signs. Exit sign placement
shall be such that any point in an exit access corridor or exit passageway is
within 100 feet (30 480 mm) or the listed viewing distance of the sign,
whichever is less, from the nearest visible exit sign.
Exceptions:
1. Exit signs are not required in rooms or
areas that require only one exit or exit access.
2. Main exterior exit doors or gates that are
obviously and clearly identifiable as exits need not have exit signs where
approved by the fire code official.
3. Exit signs are not required in occupancies
in Group U and individual sleeping units or dwelling units in Group R-l, R-2 or
R-3.
4. Exit signs arc not required
in day rooms, sleeping rooms or dormitories in occupancies in Group
1-3.
5. In occupancies in Groups
A-4 and A-5, exit signs are not required on the seating side of vomitories or
openings into seating areas where exit signs are provided in the concourse that
are readily apparent from the vomitories. Egress lighting is provided to
identify each vomitory or opening within the seating area in an
emergency.
[BE] 1006.1
General. The number of exits or exit access doorways required
within the means of egress system shall comply with the provisions of Section
1006.2 for spaces, including mezzanines, and Section 1006.3 for stories or
occupied roofs.
[BE] 1006.2
Egress from spaces. Rooms, areas or spaces, including mezzanines,
within a story or basement shall be provided with the number of exits or access
to exits in accordance with this section.
[BE]
1006.2.1
Egress based on occupant load and common path of
egress travel distance, Two exits or exit access doorways from any space
shall be provided where the design occupant load or the common path of egress
travel distance exceeds the values listed in Table 1006.2.1. The cumulative
occupant load from adjacent rooms, areas or spaces shall be determined in
accordance with Section 1004.2.
Exceptions:
1. The number of exits from foyers, lobbies,
vestibules or similar spaces need not be based on cumulative occupant loads for
areas discharging through such spaces, but the capacity of the exits from such
spaces shall be based on applicable cumulative occupant loads.
2. Care suites in Group 1-2 occupancies
complying with Section 407.4 of the International Building Code.
3. Unoccupied mechanical rooms and penthouses
are not required to comply with the common path of egress travel distance
measurement.
[BE] 1006.2.1.1
Three or more exits or exit access doorways. Three exits or exit
access doorways shall be provided from any space with an occupant load of 501
to 1,000. Four exits or exit access doorways shall be provided from any space
with an occupant load greater than 1,000.
[BE] TABLE 1006.2.1
SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
OCCUPANCY |
MAXIMUM OCCUPANT LOAD OF
SPACE |
MAXIMUM COMMON PATH OF EGRESS
TRAVEL DISTANCE (feet) |
Without Sprinkler System
(feet) |
With Sprinkler System
(feet) |
Occupant Load |
OL [LESS THAN EQUAL TO]
30 |
OL > 30 |
Ac, E, M |
49 |
75 |
75 |
75a |
B |
49 |
100 |
75 |
100a |
F |
49 |
75 |
75 |
100a |
H-l, H-2, H-3 |
3 |
NP |
NP |
25b |
H-4, H-5 |
10 |
NP |
NP |
75b |
I-1, I-2d,
1-4 |
10 |
NP |
NP |
75a |
1-3 |
10 |
NP |
NP |
100a |
R-l |
10 |
NP |
NP |
75a |
R-2 |
20 |
NP |
NP |
125a |
R-3e |
20 |
NP |
NP |
125ag |
R-4C |
20 |
NP |
NP |
125ag |
Sf |
29 |
100 |
75 |
100a |
U |
49 |
100 |
75 |
75a |
For SI: 1 foot = 304.8 mm.
NP = Not Permitted.
For SI: 1 foot = 304.8 mm.
NP = Not Permitted.
a. Buildings equipped throughout
with an automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems
are permitted in accordance with Section 903.3.1.2
b. Group U occupancies equipped
throughout with an automatic sprinkler system in accordance with Section
903.2.5.
c. For a room or space used for
assembly purposes having fixed seating, see Section 1030.8.
d. For the travel distance
limitations in Group 1-2, see Section 407.4 of the International
Building Code.
e. The common path of egress travel
distance shall apply only in a Group R-3 occupancy located in a mixed occupancy
building.
f. The length of common path of
egress travel distance in a Group S-2 open parking garage shall be not more
than 100 feet.
g. For the travel distance
limitations in Groups R-3 and R-4 equipped throughout with an automatic
sprinkler system in accordance with Section 903.3.1.3, see Section
1006.2.2.6.
[BE] TABLE 1006.3.4(2)
STORIES WITH ONE EXIT OR ACCESS TO ONE EXIT FOR OTHER
OCCUPANCIES
STORY |
OCCUPANCY |
MAXIMUM OCCUPANT LOAD PER
STORY |
MAXIMUM EXIT ACCESS TRAVEL
DISTANCE (feet) |
First story above or below grade plane |
A, Bb, E,
Fb, M, U |
49 |
75 |
H-2, H-3 |
3 |
25 |
H-4, H-5,1, R-l, R-2a,
c |
10 |
75 |
Sb, d |
29 |
75 |
Second story above grade plane |
B, F, M, Sd |
29 |
75 |
Third story above grade plane and
higher |
NP |
NA |
NA |
For SI: I foot = 304.8 mm.
NP = Not Permitted.
NA = Not Applicable.
a. Buildings classified as Group R-2
equipped throughout with an automatic sprinkler system in accordance with
Section 903.3.1.1 or 903.3.1.2 and provided with emergency escape and rescue
openings in accordance with Section 1031.
b. Group B, F and S occupancies in
buildings equipped throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1 shall have a maximum exit access travel distance of 100
feet.
c. This table is used for R-2
occupancies consisting of sleeping units. For R-2 occupancies consisting of
dwelling units, use Table 1006.3.4(1).
d. The length of exit access travel
distance in a Group S-2 open parking garage shall be not more than 100
feet.
Carbon Monoxide Alarms
915.1
General. Carbon monoxide
detection shall be installed in new buildings in accordance with Sections
915.1.1 through 915.6. Carbon monoxide detection shall be installed in existing
buildings in accordance with Section 1103.9. Carbon Monoxide Detector
915.1.1
Where required. Carbon
monoxide detection shall be provided in Group 1-1,1-2, 1-4 and R occupancies
and in classrooms in Group E occupancies in the locations specified in Section
915.2 where any of the conditions in Sections 915.1.2 through 915.1.6
exist.
915.1.2
Fuel-burning
appliances and fuel-burning fireplaces. Carbon monoxide detection shall
be provided in dwelling units, sleeping units and classrooms that contain a
fuel-burning appliance or a fuel-burning fireplace.
915.1.3
Fuel-burning forced-air
furnaces. Carbon monoxide detection shall be provided in dwelling units,
sleeping units and classrooms served by a fuel-burning, forced-air furnace.
Exception: Carbon monoxide detection shall not be
required in dwelling units, sleeping units and classrooms where a carbon
monoxide detector is provided in the first room or area served by each main
duct leaving the furnace, and the carbon monoxide alarm signals are
automatically transmitted to an approved location.
915.1.4
Fuel-burning appliances outside
of dwelling units, sleeping units and classrooms. Carbon monoxide
detection shall be provided in dwelling units, sleeping units and classrooms
located in buildings that contain fuel-burning appliances or fuel-burning
fireplaces.
Exceptions:
1. Carbon monoxide detection shall not be
required in dwelling units, sleeping units and classrooms without communicating
openings between the fuel-burning appliance or fuelburning fireplace and the
dwelling unit, sleeping unit or classroom.
2. Carbon monoxide detection shall not be
required in dwelling units, sleeping units and classrooms where a carbon
monoxide detector is provided in one of the following locations:
2.1. In an approved location between the
fuel-burning appliance or fuel-burning fireplace and the dwelling unit,
sleeping unit or classroom.
2.2. On
the ceiling of the room containing the fuel-burning appliance or fuelburning
fireplace.
915.2
Locations. Where required
by Section 915.1.1, carbon monoxide detection shall be installed in the
locations specified in Sections 915.2.1 through 915.2.3.
915.2.1
Dwelling units. Carbon
monoxide detection shall be installed in dwelling units outside of each
separate sleeping area in the immediate vicinity of the bedrooms. Where a
fuel-burning appliance is located within a bedroom or its attached bathroom,
carbon monoxide detection shall be installed within the bedroom.
915.2.2
Sleeping units. Carbon
monoxide detection shall be installed in sleeping units.
Exception: Carbon monoxide detection shall be
allowed to be installed outside of each separate sleeping area in the immediate
vicinity of the sleeping unit where the sleeping unit or its attached bathroom
does not contain a fuel-burning appliance and is not served by a forced-air
furnace.
915.2.3
Group
E occupancies. Carbon monoxide detectors shall be installed in
classrooms in Group E occupancies. Carbon monoxide alarm signals shall be
automatically transmitted to an on-site location that is staffed by school
personnel.
Exception: Carbon monoxide alarm signals shall not
be required to be automatically transmitted to an on-site location that is
staffed by school personnel in Group E occupancies with an occupant load of 30
or less.
Interior Finish
803.3
Interior finish requirements
based on occupancy. Interior wall and ceiling finish shall have a flame
spread index not greater than that specified in Table 803.3 for the group and
location designated. Interior wall and ceiling finish materials tested in
accordance with NFPA 286, and meeting the acceptance criteria of Section
803.1.1.1, shall be used where a Class A classification in accordance with ASTM
E84 or UL 723 is required.
TABLE 803.3
INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY
OCCUPANCYk
GROUP |
SPRINKLERED1 |
NONSPRINKLERED |
Interior exit stairways and ramps
and exit passagewaysa, b |
Corridors and enclosure for exit
access stairways and ramps |
Rooms and enclose d
spaces0 |
Interior exit stairways and ramps
and exit
passageways3'b |
Corridors and enclosure for exit
access stairways and ramps |
Rooms and enclosed
spaces0 |
A-l and A-2 |
B |
B |
C |
A |
Ad |
Be |
A-3f, A-4,
A-5 |
B |
B |
C |
A |
Ad |
C |
B, E, M, R-l, R-4 |
B |
Cm |
C |
A |
Bm |
C |
F |
C |
C |
C |
B |
C |
C |
II |
B |
B |
Cg |
A |
A |
B |
1-1 |
B |
C |
C |
A |
B |
B |
1-2 |
B |
B |
Bm |
A |
A |
B |
1-3 |
A |
Aj |
C |
A |
A |
B |
1-4 |
B |
B |
Bh, i |
A |
A |
B |
R-2 |
C |
C |
C |
B |
B |
C |
R-3 |
C |
C |
C |
C |
C |
C |
S |
C |
C |
C |
B |
B |
C |
U |
No Restrictions |
No Restrictions |
For SI: 1 inch = 25.4 mm, 1 square foot = 0.0929
m2.
a. Class C interior finish materials
shall be allowed for wainscoting or paneling of not more than 1,000 square feet
of applied surface area in the grade lobby where applied directly to a
noncombustible base or over furring strips applied to a noncombustible base and
fireblocked as required by Section 803.11 of the International Building
Code.
b. In exit enclosures of buildings
less than three stories in height of other than Group 1-3, Class B interior
finish for nonsprinklered buildings and Class C for sprinklered buildings shall
be permitted.
c. Requirements for rooms and
enclosed spaces shall be based on spaces enclosed by partitions. Where a
fire-resistance rating is required for structural elements, the enclosing
partitions shall extend from the floor to the ceiling. Partitions that do not
comply with this shall be considered as enclosing spaces and the rooms or
spaces on both sides shall be considered as one. In determining the applicable
requirements for rooms and enclosed spaces, the specific occupancy thereof
shall be the governing factor, regardless of the group classification of the
building or structure.
d. Lobby areas in Group A-1, A-2 and
A-3 occupancies shall be not less than Class B materials.
e. Class C interior finish materials
shall be allowed in Group A occupancies with an occupant load of 300 persons or
less.
f. In places of religious worship,
wood used for ornamental purposes, trusses, paneling or chancel furnishing
shall be allowed.
g. Class B material is required
where the building exceeds two stories.
h. Class C interior finish materials
shall be allowed in administrative spaces.
i. Class C interior finish materials
shall be allowed in rooms with a capacity of four persons or less.
j. Class B materials shall be
allowed as wainscoting extending not more than 48 inches above the finished
floor in corridors.
k. Finish materials as provided for
in other sections of this code.
l. Applies where the vertical exits,
exit passageways, corridors or rooms and spaces are protected by an approved
automatic sprinkler system installed in accordance with Section 903.3.1.1 or
903.3.1.2.
m. Corridors in ambulatory care
facilities shall have a Class B or better interior finish material.
803.3.1
Interior finish
requirements-child card occupancies. Interior finish requirements shall
apply to all areas used for day care and that are part of the means of egress
in day care facilities serving 10 or fewer clients, located in the care givers
home.
803.4
Fire-retardant coatings. The required flame spread or
smoke-developed index of surfaces in existing buildings shall be allowed to be
achieved by application of approved fire-retardant coatings, paints or
solutions to surfaces having a flame spread index exceeding that allowed.
Such applications shall comply with NFPA 703 and the required
fire-retardant properties shall be maintained or renewed in accordance with the
manufacturer's instructions. The fire-retardant paint, coating or solution
shall have been assessed by testing over the same substrate to be used in the
application.
807.2
Combustible decorative materials. In Groups A, B, E, I, M and R-l
and in dormitories in Group R-2, curtains, draperies, fabric hangings and other
similar combustible decorative materials suspended from walls or ceilings shall
comply with Section 807.3 and shall not exceed 10 percent of the specific wall
or ceiling area to which such materials are attached.
Fixed or movable walls and partitions, paneling, wall pads and
crash pads applied structurally or for decoration, acoustical correction,
surface insulation or other purposes shall be considered to be interior finish,
shall comply with Section 803 and shall not be considered decorative materials
or furnishings.
Exceptions:
1. In auditoriums in Group A, the permissible
amount of curtains, draperies, fabric hangings and similar combustible
decorative material suspended from walls or ceilings shall not exceed 75
percent of the aggregate wall area where the building is equipped throughout
with an approved automatic sprinkler system in accordance with Section
903.3.1.1, and where the material is installed in accordance with Section
803.15 of the International Building Code.
2. In Group R-2 dormitories, within sleeping
units and dwelling units, the permissible amount of curtains, draperies, fabric
hangings and similar decorative materials suspended from walls or ceilings
shall not exceed 50 percent of the aggregate wall areas where the building is
equipped through-out with an approved automatic sprinkler system installed in
accordance with Section 903.3.1.
3.
In Group B and M occupancies, the amount of combustible fabric partitions
suspended from the ceiling and not supported by the floor shall comply with
Section 807.3 and shall not be limited.
4. The 10-percent limit shall not apply to
curtains, draperies, fabric hangings and similar combustible decorative
materials used as window coverings.
807.5.2
Group E. Group E
occupancies shall comply with Sections 807.5.2.1 through 807.5.2.3. 807.5.2.1
Storage in corridors and lobbies. Clothing and personal effects shall not be
stored in corridors and lobbies.
Exceptions:
1. Corridors protected by an approved
automatic sprinkler system installed in accordance with Section
903.3.1.1.
2. Corridors protected
by an approved fire alarm system installed in accordance with Section
907.
3. Storage in metal lockers,
provided the minimum required egress width is maintained.
807.5.2.2
Artwork in corridors.
Artwork and teaching materials shall be limited on the walls of corridors to
not more than 20 percent of the wall area.
807.5.2.3
Artwork in classrooms.
Artwork and teaching materials shall be limited on walls of classrooms to not
more than 50 percent of the specific wall area to which they are
attached.
807.5.5
Group 1-4. Group 1-4 occupancies shall comply with the
requirements in Sections 807.5.5.1 through 807.5.5.3.
807.5.5.1
Storage in corridors and
lobbies. Clothing and personal effects shall not be stored in corridors
and lobbies.
Exceptions:
1. Corridors protected by an approved
automatic sprinkler system installed in accordance with Section
903.3.1.1.
2. Corridors protected
by an approved fire alarm system installed in accordance with Section
907.
3. Storage in metal lockers,
provided the minimum required egress width is maintained.
807.5.5.2
Artwork in corridors.
Artwork and teaching materials shall be limited on walls of corridors to not
more than 20 percent of the wall area.
807.5.5.3
Artwork in classrooms.
Artwork and teaching materials shall be limited on walls of classrooms to not
more than 50 percent of the specific wall area to which they are
attached.
Corridors
[BE]
1020.2
Construction. Corridors shall be
fire-resistance rated in accordance with Table 1020.2. The corridor walls
required to be fire-resistance rated shall comply with Section 708 of the
International Building Code for fire partitions.
Exceptions:
1. A fire-resistance rating is not required
for corridors in an occupancy in Group E where each room that is used for
instruction has not less than one door opening directly to the exterior and
rooms for assembly purposes have not less than one-half of the required means
of egress doors opening directly to the exterior. Exterior doors specified in
this exception arc required to be at ground level.
2. A fire-resistance rating is not required
for corridors contained within a dwelling unit or sleeping unit in an occupancy
in Groups 1-1 and R.
3. A
fire-resistance rating is not required for corridors in open parking
garages.
4. A fire-resistance
rating is not required for corridors in an occupancy in Group B that is a space
requiring only a single means of egress complying with Section
1006.2.
5. Corridors adjacent to
the exterior walls of buildings shall be permitted to have unprotected openings
on unrated exterior walls where unrated walls are permitted by Table 705.5 of
the International Building Code and unprotected openings are permitted by Table
705.8 of the International Building Code.
[BE] TABLE 1020.2
CORRIDOR FIRE-RESISTANCE RATING
OCCUPANCY |
OCCUPANT LOAD SERVED BY
CORRIDOR |
REQUIRED FIRE-RESISTANCE RATING
(hours) |
Without sprinkler
system |
With sprinkler
system |
H-l, H-2, H-3 |
All |
Not Permitted |
1c |
H-4, H-5 |
Greater than 30 |
Not Permitted |
1c |
A, B, E, F, M, S, U |
Greater than 30 |
1 |
0 |
R |
Greater than 10 |
Not Permitted |
0.5c/1d |
I-2a |
All |
Not Permitted |
0 |
1-1, 1-3 |
All |
Not Permitted |
1
b, c |
1-4 |
All |
1 |
0 |
a. For requirements for occupancies
in Group I-2, see Sections 407.2 and 407.3 of the International
Building Code.
b. For a reduction in the
fire-resistance rating for occupancies in Group 1-3, see Section 408.8 of the
International Building Code.
c. Buildings equipped throughout
with an automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2 where allowed.
d. Group R-3 and R-4 buildings
equipped throughout with an automatic sprinkler system in accordance with
Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic
sprinkler systems are permitted in accordance with Section 903.3.1.3.
[BE] TABLE 1020.3 MINIMUM CORRIDOR WIDTH
OCCUPANCY |
MINIMUM WIDTH
(inches) |
Any facility not listed below |
44 |
Access to and utilization of mechanical, plumbing or
electrical systems or equipment |
24 |
With an occupant load of less than 50 |
36 |
Within a dwelling unit |
36 |
In Group E with a corridor having a occupant load of
100 or more |
72 |
In corridors and areas serving stretcher traffic in
ambulatory care facilities |
72 |
Group 1-2 in areas where required for bed
movement |
96 |
For SI: I inch = 25.4 mm.
[BE] 1020.4
Obstruction. The
minimum width or required capacity of corridors shall be unobstructed.
Exception: Encroachments complying with Section
1005.7.
[BE] 1020.5
Dead ends. Where more than one exit or exit access doorway is
required, the exit access shall be arranged such that dead-end corridors do not
exceed 20 feet (6096mm) in length.
Exceptions:
1. In Group 1-3, Condition 2, 3 or 4
occupancies, the dead end in a corridor shall not exceed 50 feet (15 240
mm).
2. In occupancies in Groups B,
E, F, 1-1, M, R-l, R-2, S and U, where the building is equipped throughout with
an automatic sprinkler system in accordance with Section 903.3.1.1, the length
of the dead-end corridors shall not exceed 50 feet (15 240 mm).
3. A dead-end corridor shall not be limited
in length where the length of the dead end corridor is less than 2.5 times the
least width of the dead-end corridor.
4. In Group 1-2, Condition 2 occupancies, the
length of dead-end corridors that do not serve patient rooms or patient
treatment spaces shall not exceed 30 feet (9144 mm).
EXIT ACCESS TRAVEL DISTANCE
[BE] 1017.1
General. Travel
distance within the exit access portion of the means of egress system shall be
in accordance with this section.
[BE]
1017.2
Limitations. Exit access travel distance shall
not exceed the values given in Table 1017.2.
[BE]
1017.2.1
Exterior egress balcony increase. Exit
access travel distances specified in Fable 1017.2 shall be increased up to an
additional 100 feet (30 480 mm) provided that the last portion of the exit
access leading to the exit occurs on an exterior egress balcony constructed in
accordance with Section 1021. The length of such balcony shall be not less than
the amount of the increase taken.
[BE]
1017.3
Measurement. Exit access travel distance shall
be measured from the most remote point of each room, area or space along the
natural and unobstructed path of horizontal and vertical egress travel to the
entrance to an exit. Where more than one exit is required, exit access travel
distance shall be measured to the nearest exit.
Exceptions:
1. In open parking garages, exit access
travel distance is permitted to be measured to the closest riser of an exit
access stairway or the closest slope of an exit access ramp.
2. In smoke-protected seating and open-air
assembly seating, exit access travel distance shall be measured in accordance
with Section 1030.7.
[BE] TABLE 1017.2
EXIT ACCESS TRAVEL
DISTANCE3
OCCUPANCY |
WITHOUT SPRINKLER SYSTEM
(feet) |
WITH SPRINKLER SYSTEM
(feet) |
A, E, F-l, M, R, S-l |
200 |
250b, e |
1-1 |
Not Permitted |
250b |
B |
200 |
300c |
F-2, S-2, U |
300 |
400c |
H-l |
Not Permitted |
75d |
11-2 |
Not Permitted |
100d |
H-3 |
Not Permitted |
150d |
11-4 |
Not Permitted |
175d |
H-5 |
Not Permitted |
200c |
1-2, 1-3 |
Not Permitted |
200c |
1-4 |
150 |
200c |
For SI: I foot = 304.8 mm.
a. See the following sections for
modifications to exit access travel distance requirements:
Section 402.8 of the International Building
Code: For the distance limitation in malls.
Section 407.4 of the International Budding
Code: For the distance limitation in Group 1-2.
Sections 408.6.1 and 408.8.1 of the International
Building Code: For the distance limitations in Group 1-3.
Section 411.2 of the International Building
Code: For the distance limitation in special amusement areas.
Section 412.6 of the International Building
Code: For the distance limitations in aircraft manufacturing
facilities.
Section 1006.2.2.2: For the distance limitation in
refrigeration machinery rooms.
Section 1006.2.2.3: For the distance limitation in refrigerated
rooms and spaces.
Section 1006.3.4: For buildings with one exit.
Section 1017.2.2: For increased distance limitation in Groups
F-l and S-l.
Section 1030.7: For increased limitation in assembly
seating.
Section 3103.4 of the International Budding
Code: For temporary structures.
Section 3104.9 of the International Budding
Code: For pedestrian walkways.
b. Buildings equipped throughout
with an automatic sprinkler system in accordance with Section 903.3.1.1 or
903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems
are permitted in accordance with Section 903.3.1.2.
c. Buildings equipped throughout
with an automatic sprinkler system in accordance with Section 903.3.1.1.
d. Group H occupancies equipped
throughout with an automatic sprinkler system in accordance with Section
903.2.5.1.
e. Group R-3 and R-4 buildings
equipped throughout with an automatic sprinkler system in accordance with
Section 903.3.1.3. See Section 903.2.8 for occupancies where automatic
sprinkler systems are permitted in accordance with Section 903.3.1.3.
Fire Extinguishers
906.1
Where required. Portable
fire extinguishers shall be installed in all of the following locations:
1. In new and existing Group A, B. E, F, II,
I, M. R-l, R-2, R-4 and S occupancies.
Exceptions:
1. In Group R-2 occupancies, portable fire
extinguishers shall be required only in locations specified in Items 2 through
6 where each dwelling unit is provided with a portable fire extinguisher having
a minimum rating of 1-A:10-B:C.
2.
In Group E occupancies, portable fire extinguishers shall be required only in
locations specified in Items 2 through 6 where each classroom is provided with
a portable fire extinguisher having a mini-mum rating of 2-A:20-B:C.
3. In storage areas of Group S occupancies
where forklift, powered industrial truck or powered cart operators arc the
primary occupants, fixed extinguishers, as specified in NFPA 10, shall not be
required where in accordance with all of the following:
3.1. Use of vehicle-mounted extinguishers
shall be approved by the fire code official.
3.2. Each vehicle shall be equipped with a
10-pound, 40A:80B:C extinguisher affixed to the vehicle using a mounting
bracket approved by the extinguisher manufacturer or the fire code official for
vehicular use.
3.3. Not less than
two spare extinguishers of equal or greater rating shall be available on-site
to replace a discharged extinguisher.
3.4. Vehicle operators shall be trained in
the proper operation, use and inspection of extinguishers.
3.5. Inspections of vehicle-mounted
extinguishers shall be performed daily.
2. Within 30 feet (9144 mm) distance of
travel from commercial cooking equipment and from domestic cooking equipment in
Group 1-1; 1-2, Condition 1; and R-2 college dormitory occupancies.
3. In areas where flammable or combustible
liquids arc stored, used or dispensed.
4. On each floor of structures under
construction, except Group R-3 occupancies, in accordance with Section
3316.1.
5. Where required by the
sections indicated in Table 906.1.
6. Special-hazard areas, including but not
limited to laboratories, computer rooms and generator rooms, where required by
the fire code official.
Exception: Portable fire extinguishers are not
required at normally unmanned Group U occupancy buildings or structures where a
portable fire extinguisher suitable to the hazard of the location is provided
on the vehicle of visiting personnel.
906.2
General requirements.
Portable fire extinguishers shall be selected, installed and maintained in
accordance with this section and NFPA 10.
Exceptions:
1. The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.
2. Thirty-day
inspections shall not be required and maintenance shall be allowed to be once
every 3 years for dry-chemical or halogenated agent portable fire extinguishers
that arc supervised by a listed and approved electronic monitoring device,
provided that all of the following conditions are met:
2.1. Electronic monitoring shall confirm that
extinguishers are properly positioned, properly charged and
unobstructed.
2.2. Loss of power or
circuit continuity to the electronic monitoring device shall initiate a trouble
signal.
2.3. The extinguishers
shall be installed inside of a building or cabinet in a noncorrosive
environment.
2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.
2.5. A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA
10.
3. In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff
locations.
Day Care Facility Code Reference Guide
Note: This is a summarized portion of the 2021 Arkansas
Fire Prevention Code covering the basic requirements for Day Care Facilities.
It should be understood that some systems, components, structures, and/or
conditions may need to be specifically evaluated for their compliance to the
Arkansas Fire Prevention Code and/or its referenced standards. There are
conditions that warrant evaluation on a case by case basis for code
compliance.
OCCUPANCY CLASSIFICATION LISTINGS IN VOLUME II OF
ARKANSAS FIRE PREVENTION CODE
SECTION
305
EDUCATIONAL GROUP E
305.1
Educational Group E.
Educational Group E occupancy includes, among others, the use of a building or
structure, or a portion thereof, by six or more persons at any one time for
educational purposes through the 12th grade.
305.1.1
Accessory to places of
religious worship. Religious educational rooms and religious
auditoriums, which are accessory to places of religious worship in accordance
with Section 303.1.4 and have occupant loads of less than 100 per room or
space, shall be classified as Group A-3 occupancies.
305.2
Group E, day care
facilities. This group includes buildings and structures, or portions
thereof occupied by more than five children older than 2 1/2 years of age who
receive educational, supervision or personal care services for fewer than 24
hours per day.
305.2.1
Within places of
religious worship. Rooms and spaces within places of religious worship
providing such day care during religious functions shall be classified as part
of the primary occupancy.
305.2.2
Five or fewer children. A facility having five or fewer children
receiving such day care shall be classified as part of the primary
occupancy.
305.2.3
Five or
fewer children in a dwelling unit. A facility such as the above within a
dwelling unit and having five or fewer children receiving such day care shall
be classified as a Group R-3 occupancy or shall comply with the International
Residential Code.
305.3
Storm shelters in Group E occupancies. Storm shelters shall be
provided for Group E occupancies where required by Section
423.5.
SECTION 308
INSTITUTIONAL GROUP I308.1
Institutional Group I. Institutional Group I occupancy includes,
among others, the use of a building or structure, or a portion thereof, in
which care or supervision is provided to persons who are or arc incapable of
self-preservation without physical assistance or in which persons are detained
for penal or correctional purposes or in which the liberty of the occupants is
restricted. Institutional occupancies shall be classified as Group 1-1,1-2,1-3
or 1-4.
308.5
Institutional
Group 1-4, day care facilities. Institutional Group 1-4 occupancy shall
include buildings and structures occupied by more than five persons of any age
who receive custodial care for fewer than 24 hours per day by persons other
than parents or guardians; relatives by blood, marriage or adoption; and in a
place other than the home of the person cared for. This group shall include,
but not be limited to, the following:
Adult day care
Child day care
308.5.1
Classification as Group E. A child day care facility that provides
care for more than five but not more than 100 children 2 1/2 years or less of
age, where the rooms in which the children are cared for are located on a level
of exit discharge serving such rooms and each of these child care rooms has an
exit door directly to the exterior, shall be classified as Group E.
308.5.2
Within a place of religious
worship. Rooms and spaces within places of religious worship providing
such care during religious functions shall be classified as part of the primary
occupancy.
308.5.3
Five or
fewer persons receiving care. A facility having five or fewer persons
receiving custodial care shall be classified as part of the primary
occupancy.
308.5.4
Five or
fewer persons receiving care in a dwelling unit. A facility such as the
above within a dwelling unit and having five or fewer persons receiving
custodial care shall be classified as a Group R-3 occupancy or shall comply
with the International Residential Code.
Egress
IBC/IFC Chapter 10
_______(B) Table 1004 Occupant Load
______(B) 1006 Number of Exits
_________(B) 1008 Means of Egress Illumination
______(B) 1009 Accessible Means of Egress
______(B) 1010 Doors and Gates
___(B) 1010.1.2.1 Door Swing
__(B) 1010.1.3 Door Opening Force
______(B) 1010.2 Door Operation
______(B) 1010.2.5 Bolt Locks
___(B) 1010.2.1 Unlatching
______(B) 1010.2.13 Delayed Egress Locks
______(B) 1010.2.14 Access-controlled Egress Locks
______(B) 1010.2.9 Panic Hardware
____(B) 1012 Ramps
_______(B) 1013 Exit Signs
______(B) 1016 Exit Access
_______(B) 1017 Exit Access Travel Distance (sec Table
1017.2)
_______(B) 1020 Corridor Fire-resistance Rating
______(B) 1020.3 Minimum Corridor Width
__(B) 1026 Horizontal Exit (separations)
______(B) 1028 Exit Discharge
______(B) 1031 Emergency Escape and Rescue
Sprinkler Requirements
IBC/IFC Chapter 9
_______(F) 901 General Requirements
__(F) 901.6 Inspection Testing and Maintenance
____(F) 901.6.1 Fire Protection Maintenance Standards
Sprinkler System:
______(F) 903.2.3 Group E
_____(F) 903.2.6 Group I
____(F) 903.2.8 Group R
______(F) 903.4 Sprinkler System Supervision and Alarms
_______(F) 903.4.1 Monitoring
__(F) 903.4.2 Alarms
__(F) 903.5 Testing and Maintenance
______(F) 912 Fire Department Connections
Cooking Operations:
______(F) 606 Commercial Kitchen Hoods
_____(F) 904.2.2 Commercial Hood and Duct Systems
______(F) 904.14 Residential Cooking Appliances
Fire Extinguishers:
______(F) 906 Where Required
_______(F) 906.3 Size and Distribution
______(F) 906.5 Conspicuous Location
_________(F) 906.6 Unobstructed and Unobscured
___(F) 906.7 Hangers and Brackets
_______(F) 906.8 Cabinets
___________(F) 906.9 Extinguisher Installation (height)
Fire Alarm System:
__(F) 907 General Requirements
______(F) 907.2.3 Group E (30 or more)
________(F) 907.2.6 Group I
___(F) 907.2.3.1 Smoke Detection (Day Care Facilities)
_______(F) 907.6.6 Monitoring
______(F) 907.8 Inspection Testing and Maintenance
_______(F) 1103.9 Carbon Monoxide Alarms
Emergency Planning
IFC Chapter 4
______(F) 401.7 Unplanned Evacuation
______(F) 405 Evacuation Drill Frequency
______(F) 404 Fire Safety, Eockdown and Evacuation Plans
_____(F) 406 Employee Training and Response Procedures
________(F) 403.4 Group E Evacuation Drill Frequency
__(F) 403.7 Group I
Fire Service Features
IFC Chapter 5
______(F) 503 Fire Apparatus Access Roads
_______(F) 505 Premises Identification
______(F) 506 Key Boxes
_____(F) 507 Fire Protection Water Supplies
__________(F) Appendix B Fire-flow Requirements
______(F) Appendix C Fire Hydrant Locations and
Distribution
______(F) Appendix D Fire Apparatus Access Roads
Building Services and Systems
IFC Chapter 6
____(F) 603.9 Portable Unvented Heaters
_______(F) 605.5 Fuel Fired Heating Appliances
_______(F) 603.4 Electrical Service Equipment Clearance
_______(F) 603.4.1 Electrical Room Doors Labeling
______(F) 603.5 Relocatable Power Taps
______(F) 603.6 Extension Cords
______(F) 603.2 Unapproved Conditions (open
wiring/splices/boxes)
Interior Finish, Decorative Materials and
Furnishings
IFC Chapter 8
_______(F) 803.1.1 Classification of Materials
______(F) Table 803.3 Interior Wall and Ceiling Finish
Requirements by Occupancy
__(F) 803.5 Textiles
______(F) 803.6 Newly Introduced Textile Wall and Ceiling
Coverings
______(F) 806 Natural Decorative Vegetation, New and Existing
Buildings
_______(F) 807 Decorative Materials and Artificial Decorative
Vegetation New and Existing Buildings
______(F) 807.5.2 Occupancy Based Requirements (Decorative
Materials)
______(F) 807.5.2.2 Group E Storage in Corridors and
Lobbies/Artwork
______(F) 807.5.2.3 Group E Storage in
Classrooms/Artwork
_______(F) 807.5.5.2 Group 1 Storage in Corridors and
Lobbies/Artwork
______(F) 807.5.5.3 Group I Storage in
Classrooms/Artwork
______(F) 808.4 Combustible Lockers