8 AAC 61.1160 - Additional power transmission and distribution standards
Current through August 30, 2024
(a) Notwithstanding 29 C.F.R. 1926.950(c)(1), as amended, an employer may not allow an employee to perform rubber glove work on energized lines of 5,000 volts or greater from phase-to-phase or phase-to-ground.
(b) Notwithstanding 29 C.F.R. 1926.950(c)(1), as amended, an employer may not allow an employee to approach or take any conductive object, without an insulating handle that meets the requirements of 29 C.F.R. 1910.269(j)(1), closer to exposed energized parts of 5,000 volts or greater than shown in Tables R-6 - R-10 contained in 29 C.F.R. 1910.269, as amended, or Table V-1 contained in 29 C.F.R. 1926.950, as amended.