Alaska Administrative Code
Title 8 - Labor and Workforce Development
Part 4 - Occupational Safety and Health Division
Chapter 61 - Occupational Safety and Health
Article 11 - Occupational Safety and Health Standards
8 AAC 61.1160 - Additional power transmission and distribution standards

Universal Citation: 8 AK Admin Code 61.1160

Current through August 30, 2024

(a) Notwithstanding 29 C.F.R. 1926.950(c)(1), as amended, an employer may not allow an employee to perform rubber glove work on energized lines of 5,000 volts or greater from phase-to-phase or phase-to-ground.

(b) Notwithstanding 29 C.F.R. 1926.950(c)(1), as amended, an employer may not allow an employee to approach or take any conductive object, without an insulating handle that meets the requirements of 29 C.F.R. 1910.269(j)(1), closer to exposed energized parts of 5,000 volts or greater than shown in Tables R-6 - R-10 contained in 29 C.F.R. 1910.269, as amended, or Table V-1 contained in 29 C.F.R. 1926.950, as amended.

Authority:AS 18.60.020

AS 18.60.030

AS 18.60.075

Disclaimer: These regulations may not be the most recent version. Alaska may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.