18 AAC 78.045 - Operation and maintenance of corrosion protection
Current through November 28, 2024
(a) The owner or operator of a steel UST with corrosion protection shall comply with the requirements of this section to ensure that a release caused by corrosion is prevented until the UST is permanently closed or undergoes a change-in-service under 18 AAC 78.085.
(b) A corrosion protection system must be operated and maintained to continuously provide corrosion protection to the metal components of that portion of the tank and piping that routinely contains petroleum and th at is in contact with the ground. This requirement applies to single and double wall steel tanks and piping. For purposes of this subsection, piping that routinely contains petroleum includes all product piping, except for vent lines and except for most tank fill pipe configurations.
(c) A UST equipped with a cathodic protection system must be inspected for proper operation by a cathodic protection tester who is certified under 18 AAC 78.4 10 in accordance with the following requirements:
(d) Repealed 9/27/2018.
(e) A UST with an impressed current cathodic protection system must be inspected every 60 days to ensure that the equipment is running properly. The owner or operator shall document the findings of each inspection. The owner or operator may use a form provided by the department or an equivalent form to document those findings. If the inspection of the impressed current cathodic protection system indicates a redline of zero, the owner or operator shall notify the department and take corrective action to investigate and, if necessary, to correct the problem.
(f) For a UST with cathodic protection, records of the operation of the cathodic protection system must be maintained in accordance with 18 AAC 78.056 to demonstrate compliance with the performance standards in this section. These records must provide the following:
Information about how to review or obtain a copy of the document referred to in 18 AAC 78.045 is in the editor's note at 18 AAC 78.025.
Authority:AS 46.03.020
AS 46.03.365
AS 46.03.375