(1) Administrative Facilities. Each specialty care assisted living facility shall provide office space(s) or administrative office(s).
(a) As a minimum, the administrative
office(s) shall be provided with a desk, file cabinet, and related office
equipment and supplies.
(b)
Congregate Specialty Care Assisted Living facilities shall provide separate
rooms for administrative and office purposes.
(c) Communication Facilities. Each specialty
care assisted living facility shall have an adequate number of telephones to
summon help in case of fire or other emergency, and these shall be located so
as to be quickly accessible from all parts of the building.
(d) Fire Protection Arrangements. The
facility shall have arrangements for fire protection with the nearest available
fire department for assistance in case of fire. Each facility shall have a
monitoring service for its fire alarm system.
(e) Central Staff Station. New Group and
Congregate facilities, and existing Group and Congregate facilities that are
enlarged or renovated to accommodate bed increases, shall have a centrally
located staff station with call for assistance and fire alarm system
annunciation panels.
(2) Physical Facilities (Drugs and Medicines).
(a) Medicine Storage. There shall be a
medicine cabinet or storage area in the facility for safekeeping and to avoid
contamination of individual medicine and drugs. The medicine storage area
shall:
1. Be provided with lock and key and be
kept locked when not being used.
2.
Have adequate storage space with shelving.
3. Be adequately lighted with artificial
illumination.
4. Have proper
temperature and humidity levels.
(b) Refrigerator. A refrigerator, capable of
being secured, and dedicated to medicine and drug storage, shall be required
for medicines and drugs, which must be refrigerated.
(3) Resident's Physical Facilities.
(a) All resident bedrooms
shall have an outside window and shall not be below grade. Window areas shall
not be less than one-eighth of the floor area, unless proper lighting,
ventilation, and air-conditioning are provided. All specialty care assisted
living facilities submitted for plan review on or after October 5, 2001, shall
ensure that each resident bedroom has at least one outside window with a
minimum of 20 feet of clear space to any structure, measured perpendicularly. A
peripheral view of the exterior shall be provided from newly constructed
bedrooms. Operable window openings may be restricted to prevent residents from
exiting through the windows.
(b)
Resident bedrooms shall be located so as to minimize the entrance of odors,
noise, and other nuisances.
(c)
Residents bedrooms shall be directly accessible to a main corridor or through
no more than one intervening sitting room within the bedroom suite. In no case
shall a resident bedroom be used for access to another resident's
room.
(d) Residents bedrooms shall
be individually and consistently identified, (numbered, lettered, or
named).
(e) Bedroom Size. As a
minimum, floor area shall be as follows:
1.
Private bedroom without sitting area: 80 square feet. Double bedroom without
sitting area: 130 square feet.
2.
Private bedroom with sitting area: 160 square feet. Double bedroom with sitting
area: 200 square feet.
3. Bedrooms
shall accommodate no more than two residents.
(f) Bedroom furnishings. The resident has the
right to furnish his or her room as he or she so chooses, within the facility's
guidelines. If the facility offers to provide some or all of the furniture, as
a minimum, bedrooms shall contain the following for each resident:
1. A suitable built-in clothes closet or
wardrobe with shelving space and clothing pole.
2. A bed with good springs and mattress and
sufficient clean bedding. In no case shall a cot or rollaway bed be provided
for residents.
3. A dresser or
chest of drawers.
4. A bedside
table and bed lamp.
5. At least one
comfortable chair, preferably an armchair, recliner, or rocker.
6. Window shades, Venetian blinds, or other
suitable provisions for closing the view from the window.
7. Adequate number of electrical outlets
shall be provided. Extension cords, U.L. approved with overload protection
capability may be used for light duty appliances and shall not pose a hazard to
residents.
8. A mirror in the
bedroom or bedroom suite, unless contraindicated by a resident's
condition.
(g) Toilet
and Bathing Facilities. As a minimum, the following toilet and bathing
facilities shall be provided.
1. For all
residents' bedrooms, which do not have adjoining toilet and bathing facilities,
plumbing fixtures shall be provided within the resident sleeping area according
to the following ratios:
(i) Bathtubs or
showers one per eight beds.
(ii)
Lavatories one per six beds.
(iii)
Toilets one per six beds.
2. When a semi-private bedroom is provided,
the facility shall provide a means of privacy for dressing, bathing, and
personal care. When common area bathrooms are provided, they shall be separated
by partitions, curtains, or screens to provide for privacy in the baths and
toilets.
3. Non-skid mats or equal
surface treatment and safety handgrips or grab bars shall be provided in tubs,
showers, and at each toilet fixture. Grab bars shall be installed in new Group
and Congregate facilities to conform to the currently adopted building
code.
(h) All essential
mechanical, electrical, and resident care equipment shall be clean and
maintained in a safe operating condition.
(i) Bed and bath linens shall be clean and in
good condition.
(j) Housekeeping
and maintenance shall provide services necessary to maintain a sanitary,
orderly, and comfortable interior.
(4) Food Service Facilities.
(a) Floors. Floors in food service areas
shall be of such construction as to be easily cleaned, sound, smooth,
non-absorbent, without cracks or crevices, and shall be provided with approved
and conveniently located facilities for the disposal of floor wash
water.
(b) Walls and Ceilings.
Walls and ceilings of food service areas shall be of tight and substantial
construction, and smoothly finished. The walls and ceilings shall be without
horizontal ledges and shall be washable up to the highest level reached by
splash and spray. Roofs and walls shall be maintained free of leaks. All
openings to the exterior shall be provided with doors or windows, which prevent
the entrance of rain or dust during inclement weather.
(c) Screens or Outside Openings. Openings to
the outside shall be effectively screened, or suitable provisions made equal to
screening (such as fly fans). Screen doors shall be equipped with self-closing
devices.
(d) Lighting. The kitchen,
dishwashing area, and the dining room shall have adequate light.
(e) Ventilation. Vent/exhaust hoods, vented
to the outdoors, shall be provided over cooking surfaces to aid in removing
cooking odors. Group homes with residential stoves may use a residential hood
sized for the stove. Commercial exhaust hoods shall be installed when
commercial cooking equipment is used. Congregate facilities shall use a
commercial exhaust hood system.
(f)
Employee Toilet Facilities. Toilet rooms, if provided, shall not open directly
into any room or space in which food is prepared, stored, displayed, or served,
nor into any room in which utensils are washed or stored. Toilet rooms shall
include a lavatory with a soap dispenser and disposable towels, and shall be
well lighted and ventilated.
(g)
Hand washing Facilities. Each Group and Congregate specialty care assisted
living facility shall provide a hand washing lavatory in the kitchens which
shall be equipped with a soap dispenser and a supply of soap, disposable
towels, and hot and cold running water through a mixing valve or combination
faucet. The use of a common towel and common bar soap is prohibited. Hands
shall not be washed in sinks where food is prepared.
(h) Refrigeration Facilities. Adequate
refrigeration facilities, automatic in operation for the storage of perishable
foods, shall be provided Refrigeration shall be maintained at 41 degrees
Fahrenheit or less. All refrigerators shall be provided with thermometers. All
refrigerators shall be kept clean.
(i) Equipment and Utensil Construction.
Equipment and utensils, except single service utensils, shall be so constructed
as to be easily cleaned and shall be kept in good repair. No cadmium plated,
lead, or readily corrodible utensils or equipment shall be used.
(j) Separation of Kitchen from Resident Rooms
and Sleeping Quarters. Any room used for sleeping quarters shall be separated
from the food service area by a solid wall with no direct openings. Sleeping
accommodations shall not be permitted within the food service area.
(k) Clean Rooms. Floors, walls, and ceilings
of rooms in the food service area shall be clean and free of an accumulation of
rubbish, dust, grease, dirt, etc.
(l) Clean Equipment. Equipment in the food
service area shall be clean and free of dust, grease, dirt, etc.
(m) Clean Counters, Tables, Tablecloths, and
Napkins. Tables and counters, which are used for food service, shall be kept
clean. Tablecloths and cloth napkins shall be laundered after each
use.
(n) Location and Space
Requirements. Food service facilities shall be located in a specifically
designated area and shall include the following rooms and space: kitchen,
dishwashing, food storage, and dining room.
(o) Equipment. Minimum equipment in the
kitchen shall include the following:
1.
Range. In a Group specialty care assisted living facility, a residential use
range is permitted. A Congregate specialty care assisted living facility shall
have a heavy duty range suitable for institutional use with double oven, or
equivalent.
2. Refrigerator. A
Group specialty care assisted living facility may use a residential
refrigerator. A Congregate specialty care assisted living facility shall have a
heavy-duty refrigerator suitable for institutional use.
3. Fire extinguisher. Five-pound type BC for
residential hoods and K type for commercial hoods.
4. Dishwashing. The dishwashing equipment for
Group assisted living facilities shall be either residential type using cold
water sanitizers or commercial type with a booster water heater. Dishwashing
equipment for all Congregate assisted living facilities shall be commercial
type using a booster water heater or an automatic dispensing sanitizing
chemical system.
5. A
three-compartment sink with a booster heater or chemical sanitizing system for
the third compartment shall be provided in Congregate assisted living
facilities.
6. Garbage cans with
cover.
(p) Food Storage.
A well-ventilated, cool food storage room, pantry, or cabinets shall be
provided. Adequate shelving, bins, suitable cans, and raised platforms shall be
provided and kept clean. Perishable food shall be stored at least six inches
above the floor. The storeroom shall be of such construction as to prevent the
invasion of rodents and insects, the seepage of dust and water, leakage, or any
other source of contamination.
(q)
Dining Room.
1. A resident dining room, or
rooms, shall be provided which is large enough to seat not less than 100
percent of the bed capacity.
(r) Water Heating Equipment. Equipment for
heating an ample supply of water, under pressure, for all washing purposes
shall be provided. Hot water shall be piped to all hand-washing facilities, and
to each compartment of all dishwashing and laundry sinks. Water heaters shall
be of the automatic type.
(5) Recreational.
(a) Living and Recreational Room(s). Each
specialty care assisted living facility shall provide adequate living and
recreational room(s) for group activities, and for social events, such as
holiday celebrations, without crowding. The following shall be included:
1. Small living room(s) of a personal or
family type so that residents may read or visit with relatives and friends in
private. This requirement may be met when private bedrooms are large enough for
use as small sitting rooms and are furnished for this use. Furniture for small
living rooms and sitting spaces in bedrooms shall include clean comfortable
chairs, tables, and lamps of good repair.
2. Central living or recreational room in
which group activities can take place. This requirement may be met by combining
the resident dining room with a central living or recreational room.
(i) The living and recreational room shall be
furnished according to the activities offered. Furniture shall include clean
comfortable chairs, tables, and lamps of good repair.
(b) Yards and Gardens. Each
specialty care assisted living facility shall provide safe space for outside
activities.
(c) Hobbies or Leisure
Activities. Each specialty care assisted living facility shall provide adequate
space (s) for hobbies and leisure activities.
Authors: Victor Hunt, Kelley Mitchell
Statutory Authority: Code of Ala. 1975, §§ 22-21-20, et seq.
Disclaimer: These regulations may not be the most recent version. Alabama may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.