Current through Register Vol. 42, No. 11, August 30, 2024
The provisions of this section shall apply to all inpatient
hospices licensed by the State Board of Health.
(2)
Location.
(a) Each hospice shall be located so that
they are free from undue noises, smoke, dust, or foul odors and shall not be
located adjacent to railroads, freight yards, airports, industrial plants,
disposal plants, cemeteries, funeral homes, or any other similar facility or
activity. This rule shall not prevent additions to existing
facilities.
(b) The location and
construction of all facilities shall comply with local zoning, building and
fire ordinances. Evidence to this effect, signed by local fire, building, and
zoning officials, shall be furnished to the State Board of Health.
(c) Facilities shall be located on streets or
roads which are kept passable at all times. Facilities constructed after the
effective date of these rules shall be located on paved roads.
(6)
General Requirements - Inpatient Hospices. The provisions of this
section shall apply to all inpatient hospices licensed by the State Board of
Health on the effective date of these regulations.
(a) All hospices shall comply with the
applicable regulations of the State Board of Health and the codes and standards
as adopted by the State Board of Health, see Alabama Administrative Code, Rule
420-5-22, "Submission of Plans and Specifications for Health Care
Facilities."
(b) The occupancy
classification for all hospice facilities shall be "health care - limited care
facility" as defined in the NFPA 101 Life Safety Code.
1. Exception 1 - a hospice located within a
hospital shall meet the NFPA 101 Life Safety Code requirement for "health care
- hospital" and all requirements for hospitals by the Department of Public
Health in addition to those requirements contained within these
regulations.
2. Exception 2 - a
hospice located within a nursing home shall meet the NFPA 101 Life Safety Code
requirement for "healthcare - nursing home" and all requirements for nursing
homes by the Department of Public Health in addition to those requirements
contained within these regulations.
(c) Water supply.
1. If at all possible, all water shall be
obtained from a public water supply. If it is impossible to connect to a public
water system, the private water supply shall be approved by the State Board of
Health.
2. Water under pressure of
not less than 15 lbs. per square inch shall be piped within the building to all
sinks, toilets, lavatories, tubs, showers, and other fixtures requiring
water.
3. An adequate supply of hot
water shall be provided at all times throughout the facility. Temperature of
hot water at plumbing fixtures used by patients shall be automatically
regulated thermostatically by control valves and will not exceed 120 degree
F.
4. In the laundry, provision
shall be made to increase the water temperature to 160 degree F.
5. There shall be procedures established to
ensure that water can be provided for all essential services in the event of
loss of the normal water supply.
(d) Disposal of liquid and human wastes.
1. There shall be installed within the
building a properly designed waste disposal system connecting to all fixtures
to which water under pressure is piped.
2. All liquid and human waste, including
floor wash water and liquid waste from refrigerators, shall be disposed of
through trapped drains into a public sanitary sewer system in localities where
such system is available.
3. In
localities where a public sanitary sewer is not available, liquid and human
waste shall be disposed through trapped drains into a sewage disposal system
approved by the county health department and/or the State Board of
Health.
4. The sewage disposal
system shall be of a size and capacity based on the number of patients and
personnel housed and employed in the institution. Where the sewage disposal
system is installed prior to the opening of the institution, it shall be
assumed, unless otherwise proven, that the system was designed for 10 or fewer
persons.
5. Plumbing shall be
sized, installed, and maintained to carry adequate quantities of water to
required locations throughout the facility, to prevent contamination of the
water supply, and to properly convey sewage and liquid wastes from the
establishment to the sewerage or sewage disposal system, in a manner not to
constitute a source of contamination or create an unsanitary condition or
nuisance.
(e) Solid
waste.
1. Solid, non-infectious wastes shall
be kept in leakproof, non-absorbent containers which shall be kept covered with
tight-fitting lids, and shall be disposed of with sufficient frequency and in a
manner to prevent a nuisance.
2.
Solid wastes which are potentially infectious shall be burned on the premises
in an incinerator approved by the State Board of Health or disposed of in a
manner approved by the State Board of Health or its appropriate designated
agency.
3. Trash chutes are
prohibited.
(f) No part
of a hospice may be rented, leased, or used for any purpose that is disruptive
to the operation of the facility. Building uses not necessary to the facility
operation shall be distinctly separated from the licensed facility operation.
The State Board of Health shall approve all plans for functions not necessary
to the operation of the facility. These areas shall be separated from the
licensed facility by a two-hour fire separation.
(g) Construction type. The construction type
of all buildings shall be classified according to National Fire Protection
Association 220. All buildings shall meet the minimum construction requirements
called for in the applicable occupancy sections of National Fire Protection
Association 101 including automatic sprinkler system, if required.
(h) The building shall be structurally sound
from leaks and excessive moisture, in good repair, and painted at sufficient
intervals to be reasonably attractive inside and out.
(i) Distance to property line or adjacent
structures.
1. There shall be a minimum of 30
feet of clear space measured perpendicular between a patient bedroom window and
any building or the property line.
2. There shall be, as a minimum, 30 feet
between any part of the building and any adjacent building(s) not conforming to
the requirements of these regulations.
(j) The building area shall not occupy more
than 40 percent of the site.
(k)
There shall be telephones, as necessary, to summon help in case of fire or
other emergency.
(l) Lighting.
1. All lighting shall be electric.
2. Each patient's room and bathroom shall
have artificial light adequate for eating and other uses as needed. All
entrances, hallways, stairways, ramps, cellars, rooms, storerooms, kitchens,
laundries, and service units shall have sufficient artificial lighting to
prevent accidents and promote efficiency of service.
3. Night lights shall be provided in
bedrooms, hallways, and toilets and/or bathrooms that open into patient rooms.
Glowing toggle switches are acceptable in toilets and/or bathrooms.
(m) Floors.
1. All floors are smooth and free from cracks
and finished so that they can be easily cleaned. All floors in the facility
except mechanical rooms shall be covered wall-to-wall with inlaid linoleums,
resilient tile, hard tile, carpet, or the equivalent. A painted floor finish is
not acceptable except in mechanical rooms and electrical rooms. Carpet is not
acceptable in kitchens, utility rooms, toilets, baths, and janitor's
closets.
2. All carpet must meet
NFPA 101 requirements for "Class I" interior floor finishes.
(n) Patient bedrooms shall have an
outside window, installed so that it can be opened from the inside without the
use of tools or keys. Screens shall be provided on all operable
windows.
(o) Walls and ceilings
shall be of sound construction with an acceptable surface and maintained in
good repair.
(p) A ceiling height
of 8 feet or more (does not include furred area) shall be provided throughout
the facility. After the effective date of these regulations, a ceiling height
of 7 feet 6 inches is allowed in corridors.
(q) Doors. To avoid the danger of a patient
falling and blocking the swing of a door, all doors to patients' baths and
toilets shall swing out or be double-acting and equipped with an emergency stop
release.
(r) Fire hydrants. All
facilities shall have access to public fire hydrant protection, or the
equivalent approved by the local fire department or state fire marshal. Access
to fire hydrants shall be within 500 feet.
(s) Handrails shall be installed on both
sides of all corridors and shall be maintained in safe repair. Handrails shall
return to the wall at the end of each handrail section.
(t) Nurse call system.
1. The facility shall have an electrical
nurse call system at the side of each bed which will provide an audible and
visual signal on an annunciator panel at the nurses' station.
2. Each facility shall have a light over the
door to the bedroom in the corridor.
3. Nurse call system shall be provided in
each patient toilet and bath.
(u) Elevators.
1. Facilities with patients on one or more
floors above the first floor shall be equipped with at least one automatic
elevator of a size sufficient to carry a patient on a stretcher.
2. Routine inspections shall be made of
elevators in accordance with codes and city ordinances.
(v) Exit signs. Exit signs shall be provided
at all required exits. Additional exit signs shall be provided in corridors to
indicate two directions of exit travel from any point. Additional exit signs
for suites and places of assembly shall be installed as required.
(w) General storage. A general storage room
shall be provided for the central storage of equipment, supplies, etc., at the
rate of 8 square feet per bed and concentrated in one area. The storage room
shall be designed to provide adequate and orderly storage so as to prevent the
use of corridors and non-storage areas for storage purposes. When any part of
the facility is remodeled or renovated, general storage shall be provided at
the rate of 8 square feet per bed. The general storage room shall be adequately
ventilated. Space under stairs shall not be used for storage
purposes.
(x) Facilities for
physically handicapped. Necessary physical accommodations shall be made to meet
the needs of persons with physical disabilities, sight and hearing
disabilities, disabilities of coordination, as well as other disabilities in
accordance with the standards adopted by the State Board of Health.
(y) Heating ventilation and air conditioning.
The building shall be well ventilated at all times. Patients bedrooms shall be
ventilated in such a manner as to supply fresh air and to prevent accumulation
of objectionable odors. Kitchens, laundries, service rooms, toilets, bathrooms,
and all inside rooms shall be vented to prevent offensive odors from entering
other parts of the building.
1. Ventilating
fans and blowers. Ventilating fans and blowers, if installed, shall not be so
located that they will obstruct any required exit, stairway, or corridor and
shall not create a draft from one floor to another.
2. Temperature to be maintained. The heating
and cooling system must be capable of maintaining a temperature of 70 degree F.
throughout the patient/resident section of the building. The heating of all
facilities shall be restricted to steam, hot water, or warm air systems
employing central heating plants, or UL listed electric heating. The use of
portable heaters of any kind is prohibited.
3. A laboratory, if provided, shall be
ventilated and temperature controlled for proper equipment operation and/or
test results.
(z) Ramps
and inclines. Exterior and interior ramps and inclines, shall not be steeper
than 1 footing rise in 12 feet of run, shall be finished with a non-slip
surface and shall be provided with handrails on both sides.
(aa) Basements.
1. The basement shall be considered as a
story if one-half or more of its perimeter is level with or above
grade.
2. No patient/resident shall
be housed in any room that is more than 50 percent below ground
level.
(bb) Emergency
power. An emergency generator shall be provided to supply power to the
following:
1. Emergency corridor
illumination.
2. Exit
signs.
3. An exterior light at each
exit.
4. Fire alarm
system.
5. Smoke detection
system.
6. Sprinkler
system.
7. Life support systems by
providing wall receptacles in the corridor at least every 50 feet and in at
least two bedrooms in each nursing unit.
8. Telephone system.
9. Public address system.
10. Nurses' call system.
11. Medicine preparation area.
12. Sprinkler riser room.
13. Main electrical panel room.
14. Emergency generator location.
(cc) Existing mechanical and
electrical systems. Mechanical and electrical systems installed prior to the
effective date of these rules shall be inspected by local building, electrical,
plumbing officials, or the state fire marshal or such other persons as the
State Board of Health may request, and the recommendations regarding adequacy
and safety shall be presented to the board.
(dd) Smoke dampers.
1. Smoke dampers shall be located in all
ducts passing through smoke partitions. They shall be arranged to close upon
activation of the fire alarm system by an initiating device.
2. Dampers shall remain closed while the fire
alarm system is in the silence mode and shall remain closed until the fire
alarm system is reset to normal.
(ee) Fire alarm.
1. A manual fire alarm system shall be
provided to generate an audible and visual alarm throughout the
facility.
2. Manual pull stations
shall be installed at each exit.
3.
The visual signal shall continue to flash while the alarm system is in the
silence mode.
4. The fire alarm
system shall sound upon activation of the automatic detection system,
extinguishing system, and manual system.
5. In all buildings and additions connected
by a common wall and corridor, the fire alarm system shall operate in all parts
of the facility as one system.
(ff) Sprinkler. Building protection shall be
provided throughout by an approved supervised automatic sprinkler system
installed in accordance with NFPA 13 "standard for the installation of
sprinkler systems."
(gg) Dead-end
corridor shall not exceed 20 feet in length.
(hh) Rooms, spaces and equipment.
1. Each nursing unit shall have:
(i) Nurses' station.
(ii) Clean utility room.
(iii) Soiled utility room.
(iv) Medicine preparation area.
(v) Clean linen storage area. Cabinets on the
corridor are not allowable.
(vi)
Wheelchair and stretcher storage areas.
(vii) Janitor's closet.
(viii) On a nursing unit, no patient bedroom
door shall be more than 120 feet from the nurses' station.
2. Bedrooms.
(i) Patients' bedrooms shall be located so as
to minimize the entrance of odors, noise and other nuisances.
(ii) Patients' bedrooms shall be directly
accessible from the main corridor of the nursing unit. In no case shall a
patient's bedroom be used for access to another patient's room.
(iii) The bed capacity of any room shall not
exceed four.
(iv) The minimum floor
area of bedrooms (exclusive of toilets, closets, wardrobes, alcoves or
vestibules) shall be as follows:
Private bedroom 120 square feet per bed
Multi-patient bedroom 80 square feet per bed
(v) There shall be sufficient space to permit
nursing procedures to be performed and to permit the placing of beds at least 3
feet apart and 2 feet from the wall at the side of the bed and 3 feet from the
wall at the foot of the bed.
(vi)
Private bedrooms shall be provided at the ratio of 1 per 15 beds, or a major
fraction thereof, which may include the special care or isolation
room(s).
(vii) Each multi-patient
room shall have permanently installed cubicle curtains and tracks to permit
enclosing each bed with curtains to allow for the privacy of each patient
without obstructing the passage of other patients to the corridor, closet, and
toilet/lavatory.
(viii) Cubicle
curtains installed in sprinklered building shall have 1\2 inch mesh openings
extending 18 inches below the sprinkler deflector.
3. Accommodations for patients. The minimum
accommodations for patient shall include the following:
(i) Bed patients shall be provided with an
adjustable hospital bed with proper fitting mattress and personal care
items.
(ii) Ambulatory patients
shall be provided with a standard or adjustable hospital bed.
(iii) Pillows and necessary
coverings.
(iv) Chair and bedside
table.
(v) Chest for storage of
clothing, toilet articles, and personal belongings.
(vi) Bedside electrical call system for
summoning aid.
(vii) Waste paper
receptacle.
(viii) Closet or
wardrobe unit for each bed.
(ix)
All facilities shall have a bed light mounted on the wall at the head of the
bed, (operable by patient).
(x) All
facilities shall provide a hand washing lavatory in each room. They may be
omitted from a single-bed or a two-bed room when a lavatory is provided in an
adjoining toilet or bathroom.
4. Isolation rooms shall be provided at the
rate of not less than 1 private bedroom per 50 beds or major fraction thereof
for the isolation of patients suffering from infectious diseases. The bedroom
shall meet all of the requirements for bedrooms in these rules. Isolation
bedrooms may be used to provide for the special care of patients with special
needs. Isolation rooms shall have a private toilet.
5. The nurses' station for each nursing unit
shall include as a minimum the following:
(i)
Annunciator board for receiving patients' calls.
(ii) Cabinet space.
(iii) Storage space for current patients'
charts.
(iv) Working space and
accommodations for recording and charting purposes by facility staff.
(v) Medicine preparation room/area. (See
storage of drugs and biologicals for specific requirements.)
6. All facilities shall provide a
separate clean and soiled utility room for each nursing unit.
(i) The clean utility room shall contain as a
minimum:
(I) Wall and base
cabinets.
(II) Counter
space.
(III) Single-compartment
counter sink.
(IV) Paper towel
cabinet.
(V) Soap
dispenser.
(ii) The
soiled utility room shall contain as a minimum:
(I) Paper towel and soap
dispensers.
(II) Shelves.
(III) Cabinets for storage of poisonous
substances; i.e., cleaning supplies, urine test products, etc.
(IV) Table or counter.
(V) Service sink for chemical sterilization
of bed pans, urinals and commode pails, and/or pressure sterilizer.
(VI) Lavatory.
(VII) Soiled linen hamper.
7. Toilet and bathing
facilities.
(i) For all patients bedrooms
which do not have adjoining toilet and bath facilities, plumbing fixtures shall
be provided within the nursing unit according to the following ratio:
bathtubs or showers 1 per 12 beds
lavatories 1 per 6 beds
toilets (water closets) 1 per 6 beds
(ii) Non-skid mats or equivalent and grab
bars shall be provided at tubs and showers. Grab handles on soap dishes are not
acceptable for grab bars.
(iii)
Grab bars shall be provided at each water closet.
(iv) Only one tub or shower shall be
installed in a bath or shower room. The room may also contain a lavatory and a
water closet.
8.
Nourishment units.
(i) All facilities shall
have a nourishment station containing the following:
(I) Work counter.
(II) Refrigerator.
(III) Hot plate or microwave.
(IV) Storage cabinet.
(V) Sink in the counter.
(VI) Ice machine.
(VII) Storage space for trays and
dishes.
(VIII) Hand washing
lavatory.
(ii) A clean
utility room, separate from a soiled utility room, may be used as a nourishment
station when the above requirements are met.
9. Patient dining and recreation areas shall
be provided in accordance with the following:
(i) The total area set aside for these
purposes shall be at least 20 square feet per bed.
(ii) The area shall contain at least one
sitting area and a dining area.
(iii) Each nursing unit shall contain at
least one sitting area.
(iv) The
dining room shall be of such size and dimensions as to permit placing of dining
tables and chairs to seat not less than 50 percent of the patients in the
facility at one seating. The dining room may also be used for recreational
purposes. The kitchen shall not be used as a dining room for patients or
personnel. Facilities shall provide a minimum of 12 square feet per person in
the dining room.
(v) Dietary
manager's office shall be located within the department and shall be equipped
with necessary equipment.
10. Physical therapy areas, if provided,
shall be in a specifically designated area and shall include equipment and
areas as needed to meet specific patient requirements and shall also include
storage space for linens, supplies, and equipment, a lavatory and a
sink.
11. The Administrative
Department and services shall be located in a specifically designated area and
shall include the following:
(i)
Administration.
(ii) Business
Office/Accounting Services.
(iii)
Lobby or waiting area.
12. All facilities shall provide maintenance
services.
13. Employee toilets.
Employee toilets shall be provided and shall include the following:
(i) Water closet.
(ii) Lavatory.
(iii) Soap dispenser.
(iv) Disposable towel dispenser.
(v) Covered waste receptacle.
Author: Jimmy D. Prince