Current through Register Vol. 42, No. 11, August 30, 2024
(1) Purpose and Scope.
(a) This rule contains requirements for the
use of sealed sources containing radioactive material in irradiators used to
irradiate objects or materials using gamma radiation. This rule also contains
radiation safety requirements for operating irradiators. The requirements of
this rule are in addition to other requirements of these rules. Nothing in this
rule relieves the licensee from complying with other applicable federal, state
and local regulations governing the siting, zoning, land use, and building code
requirements for industrial facilities.
(b) The requirements in this rule apply to
panoramic irradiators that have either dry or wet storage of the radioactive
sealed sources and to underwater irradiators in which both the source and the
product being irradiated are under water. Irradiators whose dose rates exceed 5
grays (500 rads) per hour at 1 meter from the radioactive sealed sources in air
or in water, as applicable for the irradiator type, are covered by this
rule.
(c) The requirements in this
rule do not apply to self-contained dry-source-storage irradiators in which
both the source and the area subject to irradiation are contained within a
device and are not accessible by personnel; medical radiology or teletherapy;
radiography for the irradiation of materials for nondestructive testing
purposes; gauging; or open-field, agricultural irradiations.
(2) Definitions.
(a) "Annually" means at intervals not to
exceed one year.
(b) "Doubly
encapsulated sealed source" means a sealed source in which the radioactive
material is sealed within an inner capsule and that capsule is sealed within an
outer capsule.
(c) "Irradiator"
means a facility that uses radioactive sealed sources for the irradiation of
objects or materials and in which radiation dose rates exceeding 5 grays (500
rads) per hour exist at 1 meter from the sealed radioactive sources in air or
water, as applicable for the irradiator type, but does not include irradiators
in which both the sealed source and the area subject to irradiation are
contained within a device and are not accessible to personnel.
(d) "Irradiator operator" means an individual
who has successfully completed the training and testing described in 420-3-26
-.14(17) and is authorized by the terms of the license to operate the
irradiator without a supervisor present.
(e) "Irradiator operator supervisor" means an
individual who meets the requirements for an irradiator operator and who
physically oversees operation of the irradiator by an individual who is
currently receiving training and testing described in 420-3-26
-.14(17).
(f) "Panoramic
dry-source-storage irradiator" means an irradiator in which the irradiations
occur in air in areas potentially accessible to personnel and in which the
sources are stored in shields made of solid materials. The term includes
beam-type dry-source-storage irradiators in which only a narrow beam of
radiation is produced for performing irradiations.
(g) "Panoramic irradiator" means an
irradiator in which the irradiations are done in air in areas potentially
accessible to personnel. The term includes beam-type irradiators.
(h) "Panoramic wet-source-storage irradiator"
means an irradiator in which the irradiations occur in air in areas potentially
accessible to personnel and in which the sources are stored under water in a
storage pool.
(i) "Pool irradiator"
means any irradiator at which the sources are stored or used in a pool of water
including panoramic wet-source-storage irradiators and underwater
irradiators.
(k) "Product conveyor
system" means a system for moving the product to be irradiated to, from, and
within the area where irradiation takes place.
(l) "Radiation room" means a shielded room in
which irradiations take place. Underwater irradiators do not have radiation
rooms.
(m) "Sealed source" (see
definition in
420-3-26-.01(2)
(a)95.).
(n) "Seismic area" means any area where the
probability of a horizontal acceleration in rock of more than 0.3 times the
acceleration of gravity in 250 years is greater than 10%, as designated by the
US Geological Survey.
(o)
"Underwater irradiator" means an irradiator in which the sources always remain
shielded under water and humans do not have access to the sealed sources or the
space subject to irradiation without entering the pool.
(3) Start of Construction. The applicant may
not begin construction of a new irradiator prior to the submission to the
Agency of both an application for a license for the irradiator and any fee
required by the applicable state requirement or statute. As used in this part,
the term "construction" includes the construction of any portion of the
permanent irradiator structure on the site but does not include: engineering
and design work, purchase of a site, site surveys or soil testing, site
preparation, site excavation, construction of warehouse or auxiliary
structures, and other similar tasks. Any activities undertaken prior to the
issuance of a license are entirely at the risk of the applicant and have no
bearing on the issuance of a license with respect to the requirements of the
appropriate state statute, rules, regulations, and orders issued under the
appropriate state statute.
(4)
Applications for Exemptions. Any application for a license or for amendment of
a license authorizing use of a teletherapy-type unit for irradiation of
materials or objects may include proposed alternatives from the requirements of
this rule. The Agency will approve the proposed alternatives if the applicant
provides adequate rationale for the proposed alternatives and demonstrates that
they are likely to provide an adequate level of safety for workers and the
public.
(5) Request for Written
Statements. Each license is issued with the condition that the licensee will,
at any time before expiration of the license, upon the Agency's request, submit
a written statement to enable the Agency to determine whether the license
should be modified, suspended, or revoked.
(6) Performance Criteria for Sealed Sources.
(a) Requirements for sealed sources installed
in irradiators after July 1, 1996:
1. Must
have been evaluated in accordance with
10 CFR
32.210.
2. Must be doubly encapsulated;
3. Must use radioactive material that is as
nondispersible as practical and that is as insoluble as practical if the source
is used in a wet-source-storage or wet-source-change irradiator;
4. Must be encapsulated in a material
resistant to general corrosion and to localized corrosion, such as 316L
stainless steel or other material with equivalent resistance if the sources are
for use in irradiator pools; and
5.
In prototype testing of the sealed source, must have been leak tested and found
leak-free after each of the tests described in
420-3-26-.14(6)(b) through
(g).
(b) Temperature. The test source must be held
at - 40 C for 20 minutes, 600 C for one hour, and then be subjected to thermal
shock test with a temperature drop from 600 C to 20 C within 15
seconds.
(c) Pressure. The test
source must be twice subjected for at least five minutes to an absolute
external pressure of 2 million newtons per square meter.
(d) Impact. A 2 kilogram steel weight, 2.5
centimeters in diameter, must be dropped from a height of 1 meter onto the test
source.
(e) Vibration. The test
source must be subjected three times for ten minutes each to vibrations
sweeping from 25 hertz to 500 hertz with a peak amplitude of five times the
acceleration of gravity. In addition, each test source must be vibrated for 30
minutes at each resonant frequency found.
(f) Puncture. A 50 gram weight and pin, 0.3
centimeter pin diameter, must be dropped from a height of 1 meter onto the test
source.
(g) Bend. If the length of
the source is more than 15 times larger than the minimum cross-sectional
dimension, the test source must be subjected to a force of 2000 newtons at its
center equidistant from two support cylinders, the distance between which is
ten times the minimum cross-sectional dimension of the source.
(7) Access Control.
(a) Each entrance to a radiation room at a
panoramic irradiator must have a door or other physical barrier to prevent
inadvertent entry of personnel if the sources are not in the shielded position.
Product conveyor systems may serve as barriers as long as they reliably and
consistently function as a barrier. It must not be possible to move the sources
out of their shielded position if the door or barrier is open. Opening the door
or barrier while the sources are exposed must cause the sources to return
promptly to the shielded position. The personnel entrance door or barrier must
have a lock that is operated by the same key used to move the sources. The
control panel lock must be designed so that the key cannot be removed unless
the sources have been returned to the shielded position. The doors and barriers
must not prevent any individual in the radiation room from leaving.
(b) In addition, each entrance to a radiation
room at a panoramic irradiator must have an independent backup access control
to detect personnel entry while the sources are exposed. Detection of entry
while the sources are exposed must cause the sources to return to their fully
shielded position and must also activate a visible and audible alarm to make
the individual entering the room aware of the hazard. The alarm must also alert
at least one other individual who is on-site of the entry. That individual
shall be trained on how to respond to the alarm and prepared to promptly render
or summon assistance.
(c) A
radiation monitor must be provided to detect the presence of high radiation
levels in the radiation room of a panoramic irradiator before personnel entry.
The monitor must be integrated with personnel access door locks to prevent room
access when radiation levels are high. Attempted personnel entry while the
monitor measures high radiation levels must activate the alarm described in
420-3-26-.14(7)(b).
The monitor may be located in the entrance, normally referred to as the maze,
but not in the direct radiation beam.
(d) Before the sources move from their
shielded position in a panoramic irradiator, the source control must
automatically activate conspicuous visible and audible alarms to alert people
in the radiation room that the sources will be moved from their shielded
position. The alarms must give individuals enough time to leave the room before
the sources leave the shielded position.
(e) Each radiation room at a panoramic
irradiator must have a clearly visible and readily accessible control that
would allow an individual in the room to make the sources return to the fully
shielded position.
(f) Each
radiation room of a panoramic irradiator must contain a control that prevents
the sources from moving from the shielded position unless the control has been
activated and the door or barrier to the radiation room has been closed within
a preset time after activation of the control.
(g) Each entrance to the radiation room of a
panoramic irradiator and each entrance to the area within the personnel access
barrier of an underwater irradiator must have a sign bearing the radiation
symbol and the words, "CAUTION (or DANGER) RADIOACTIVE MATERIAL." Panoramic
irradiators must also have a sign stating "GRAVE DANGER, VERY HIGH RADIATION
AREA", but the sign may be removed, covered, or otherwise made inoperative when
the sources are fully shielded.
(h)
If the radiation room of a panoramic irradiator has roof plugs or other movable
shielding, it must not be possible to operate the irradiator unless the
shielding is in its proper location. The requirement may be met by interlocks
that prevent operation if shielding is not placed properly or by an operating
procedure requiring inspection of shielding before operating.
(i) Underwater irradiators must have a
personnel access barrier around the pool which must be locked to prevent access
when the irradiator is not attended. Only operators or facility management
shall have access to keys that operate the personnel access barrier. There must
be an intrusion alarm to detect unauthorized entry when the personnel access
barrier is locked. Activation of the intrusion alarm must alert an individual
who is not necessarily on-site but who is prepared to respond or summon
assistance.
(10)
Shielding.
(a) The radiation dose rate in
areas that are normally occupied during operation of a panoramic irradiator may
not exceed 0.02 millisievert (2 mrem) per hour at any location 30 centimeters
or more from the wall of the room when the sources are exposed. The dose rate
must be averaged over an area not to exceed 100 square centimeters having no
linear dimension greater than 20 centimeters. Any area where the radiation dose
rate exceeds 0.02 millisievert (2 mrem) per hour must be locked, roped off, or
posted.
(b) The radiation dose at
30 centimeters over the edge of the pool of a pool irradiator may not exceed
0.02 millisievert (2 mrem) per hour when the sources are in the fully shielded
position.
(c) The radiation dose
rate at 1 meter from the shield of a dry-source-storage panoramic irradiator
when the source is shielded may not exceed 0.02 millisievert (2 mrem) per hour
and at 5 centimeters from the shield may not exceed 0.2 millisievert (20 mrem)
per hour.
(9) Fire
Protection.
(a) The radiation room at a
panoramic irradiator must have heat and smoke detectors. The detectors must
activate an audible alarm. The alarm must be capable of alerting a person who
is prepared to summon assistance promptly. The sources must automatically
become fully shielded if a fire is detected.
(b) The radiation room at a panoramic
irradiator must be equipped with a fire extinguishing system capable of
extinguishing a fire without the entry of personnel into the room. The system
for the radiation room must have a shut-off valve to control flooding into
unrestricted areas.
(10)
Radiation Monitors.
(a) Irradiators with
automatic product conveyor systems must have a radiation monitor with an
audible alarm located to detect loose radioactive sources that are carried
toward the product exit. If the monitor detects a source, an alarm must sound
and product conveyors must stop automatically. The alarm must be capable of
alerting an individual in the facility who is prepared to summon assistance.
Underwater irradiators in which the product moves within an enclosed stationary
tube are exempt from the requirements of this paragraph.
(b) Underwater irradiators that are not in a
shielded radiation room must have a radiation monitor over the pool to detect
abnormal radiation levels. The monitor must have an audible alarm and a visible
indicator at entrances to the personnel access barrier around the pool. The
audible alarm may have a manual shut-off. The alarm must be capable of alerting
an individual who is prepared to respond promptly.
(11) Control of Source Movement.
(a) The mechanism that moves the sources of a
panoramic irradiator must require a key to actuate. Actuation of the mechanism
must cause an audible signal to indicate that the sources are leaving the
shielded position. Only one key may be in use at any time, and only operators
or facility management may possess it. The key must be attached to a portable
radiation survey meter by a chain or cable. The lock for source control must be
designed so that the key may not be removed if the sources are in an unshielded
position. The door to the radiation room must require the same key.
(b) The console of a panoramic irradiator
must have a source position indicator that indicates when the sources are in
the fully shielded position, when they are in transit, and when the sources are
exposed.
(c) The control console of
a panoramic irradiator must have a control that promptly returns the sources to
the shielded position.
(d) Each
control for a panoramic irradiator must be clearly marked as to its
function.
(12)
Irradiator Pools.
(a) For licenses initially
issued after July 1, 1996, irradiator pools must either:
1. Have a water-tight stainless steel liner
or a liner metallurgically compatible with other components in the pool;
or
2. Be constructed so that there
is a low likelihood of substantial leakage and have a surface designed to
facilitate decontamination. In either case, the licensee shall have a method to
safely store the sources during repairs of the pool.
(b) For licenses initially issued after July
1, 1996, irradiator pools must have no outlets more than 0.5 meter below the
normal low water level that could allow water to drain out of the pool. Pipes
that have intakes more than 0.5 meter below the normal low water level and that
could act as siphons must have siphon breakers to prevent the siphoning of pool
water.
(c) A means must be provided
to replenish water losses from the pool.
(d) A visible indicator must be provided in a
clearly observable location to indicate if the pool water level is below the
normal low water level or above the normal high water level.
(e) Irradiator pools must be equipped with a
purification system designed to be capable of maintaining the water during
normal operation at a conductivity of 20 microsiemens per centimeter or less
and with a clarity so that the sources can be seen clearly.
(f) A physical barrier, such as a railing or
cover, must be used around or over irradiator pools during normal operation to
prevent personnel from accidentally falling into the pool. The barrier may be
removed during maintenance, inspection, and service operations.
(g) If long-handled tools or poles are used
in irradiator pools, the radiation dose rate to the operator at the handling
areas of the tools may not exceed 0.02 millisievert (2 mrem) per
hour.
(13) Source Rack
Protection. If the product to be irradiated moves on a product conveyor system,
the source rack and the mechanism that moves the rack must be protected by a
carrier or guides to prevent products and product carriers from hitting or
touching the rack or mechanism.
(14) Power Failures.
(a) If electrical power at a panoramic
irradiator is lost for longer than ten seconds, the sources must automatically
return to the shielded position.
(b) The lock on the door of the radiation
room of a panoramic irradiator must remain locked in the event of a power
failure.
(c) During a power
failure, the area of any irradiator where sources are located may be entered
only when using an operable and calibrated radiation survey meter.
(15) Design Requirements.
Irradiators whose construction begins after July 1, 1996, must meet the design
requirements of this section.
(a) Shielding.
For panoramic irradiators, the licensee shall design shielding walls to meet
generally accepted building code requirements for reinforced concrete and
design the walls, wall penetrations, and entranceways to meet the radiation
shielding requirements of
420-3-26-.14(8).
If the irradiator will use more than 2 x 1017 becquerels (5 million Ci) of
activity, the licensee shall evaluate the effects of heating of the shielding
walls by the irradiator sources.
(b) Foundations. For panoramic irradiators,
the licensee shall design the foundation, with consideration given to soil
characteristics, to ensure it is adequate to support the weight of the facility
shield walls.
(c) Pool integrity.
For pool irradiators, the licensee shall design the pool to assure that it is
leak resistant, that it is strong enough to bear the weight of the pool water
and shipping casks, that a dropped cask would not fall on sealed sources, that
all outlets or pipes meet the requirements of
420-3-26-.14(12)(b),
and that metal components are metallurgically compatible with other components
in the pool.
(d) Water handling
system. For pool irradiators, the licensee shall verify that the design of the
water purification system is adequate to meet the requirements of
420-3-26-.14(12)
(e). The system must be designed so that
water leaking from the system does not drain to unrestricted areas without
being monitored.
(e) Radiation
monitors. For all irradiators, the licensee shall evaluate the location and
sensitivity of the monitor to detect sources carried by the product conveyor
system as required by
420-3-26-.14(10)(a).
The licensee shall verify that the product conveyor is designed to stop before
a source on the product conveyor would cause a radiation overexposure to any
person. For pool irradiators, if the licensee uses radiation monitors to detect
contamination under
420-3-26-.14(21)(b).,
the licensee shall verify that the design of radiation monitoring systems to
detect pool contamination includes sensitive detectors located close to where
contamination is likely to concentrate.
(f) Source rack. For pool irradiators, the
licensee shall verify that there are no crevices on the source or between the
source and source holder that would promote corrosion on a critical area of the
source. For panoramic irradiators, the licensee shall determine that source
rack drops due to loss of power will not damage the source rack and that source
rack drops due to failure of cables, or alternate means of support, will not
cause loss of integrity of sealed sources. For panoramic irradiators, the
licensee shall review the design of the mechanism that moves the sources to
assure that the likelihood of a stuck source is low and that, if the rack
sticks, a means exists to free it with minimal risk to personnel.
(g) Access control. For panoramic
irradiators, the licensee shall verify from the design and logic diagram that
the access control system will meet the requirements of 420-3-26
-.14(7).
(h) Fire protection. For
panoramic irradiators, the licensee shall verify that the number, locations,
and spacing of the smoke and heat detectors are appropriate to detect fires and
that the detectors are protected from mechanical and radiation damage. The
licensee shall verify that the design of the fire extinguishing system provides
the necessary discharge patterns, densities, and flow characteristics for
complete coverage of the radiation room and that the system is protected from
mechanical and radiation damage.
(i) Source return. For panoramic irradiators,
the licensee shall verify that the source rack will automatically return to the
fully shielded position if power is lost for more than ten seconds.
(j) Seismic. For panoramic irradiators to be
built in seismic areas, the licensee shall design the reinforced concrete
radiation shields to retain their integrity in the event of an earthquake by
designing to the seismic requirements of an appropriate source such as the
American Concrete Institute Standard ACI 318-89, "Building Code Requirements
for Reinforced Concrete," Chapter 21, "Special Provisions for Seismic Design,"
or local building codes, if current.
(k) Wiring. For panoramic irradiators, the
licensee shall verify that electrical wiring and electrical equipment in the
radiation room are selected to minimize failures due to prolonged exposure to
radiation.
(16)
Construction Monitoring and Acceptance Testing. The requirements of this
section must be met for irradiators whose construction begins after July 1,
1996. The requirements must be met prior to loading sources.
(a) Shielding. For panoramic irradiators, the
licensee shall monitor the construction of the shielding to verify that its
construction meets design specifications and generally accepted building code
requirements for reinforced concrete.
(b) Foundations. For panoramic irradiators,
the licensee shall monitor the construction of the foundations to verify that
their construction meets design specifications.
(c) Pool integrity. For pool irradiators, the
licensee shall verify that the pool meets design specifications and shall test
the integrity of the pool. The licensee shall verify that outlets and pipes
meet the requirements of
420-3-26-.14(12)(b).
(d) Water handling system. For pool
irradiators, the licensee shall verify that the water purification system, the
conductivity meter, and the water level indicators operate properly.
(e) Radiation monitors. For all irradiators,
the licensee shall verify the proper operation of the monitor to detect sources
carried on the product conveyor system and the related alarms and interlocks
required by
420-3-26-.14(10)(a).
For pool irradiators, the licensee shall verify the proper operation of the
radiation monitors and the related alarm if used to meet
420-3-26-.14(21)(b).
For underwater irradiators, the licensee shall verify the proper operation of
the over-the-pool monitor, alarms, and interlocks required by
420-3-26-.14(10)(b).
(f) Source rack. For panoramic irradiators,
the licensee shall test the movement of the source racks for proper operation
prior to source loading; testing must include source rack lowering due to
simulated loss of power. For all irradiators with product conveyor systems, the
licensee shall observe and test the operation of the conveyor system to assure
that the requirements in
420-3-26-.14(13)
are met for protection of the source rack
and the mechanism that moves the rack; testing must include tests of any limit
switches and interlocks used to protect the source rack and mechanism that
moves that rack from moving product carriers.
(g) Access control. For panoramic
irradiators, the licensee shall test the completed access control system to
assure that it functions as designed and that all alarms, controls, and
interlocks work properly.
(h) Fire
protection. For panoramic irradiators, the licensee shall test the ability of
the heat and smoke detectors to detect a fire, to activate alarms, and to cause
the source rack to automatically become fully shielded. The licensee shall test
the operability of the fire extinguishing system.
(i) Source return. For panoramic irradiators,
the licensee shall demonstrate that the source racks can be returned to their
fully shielded positions without power.
(j) Computer systems. For panoramic
irradiators that use a computer system to control the access control system,
the licensee shall verify that the access control system will operate properly
if power is lost and shall verify that the computer has security features that
prevent an irradiator operator from commanding the computer to override the
access control system when the system is required to be operable.
(k) Wiring. For panoramic irradiators, the
licensee shall verify that the electrical wiring and electrical equipment that
were installed meet the design specifications.
(17) Training.
(a) Before an individual is permitted to act
as an irradiator operator without a supervisor present, the individual must be
instructed in:
1. The fundamentals of
radiation protection applied to irradiators. This must include the differences
between external radiation and radioactive contamination, units of radiation
dose, dose limits, why large radiation doses must be avoided, how shielding and
access controls prevent large doses, how an irradiator is designed to prevent
contamination, the proper use of survey meters and personnel dosimeters, other
radiation safety features of an irradiator, and the basic function of the
irradiator;
2. The requirements of
these rules and the applicable sections of Rule
420-3-26-.03 and Rule
420-3-26-.10 that are relevant to
the irradiator;
3. The operation of
the irradiator;
4. Those operating
and emergency procedures listed in
420-3-26-.14(18)
that the individual is responsible for
performing; and
5. Case histories
of accidents or problems involving irradiators.
(b) Before an individual is permitted to act
as an irradiator operator without a supervisor present, the individual shall
pass a written test on the instruction received consisting primarily of
questions based on the licensee's operating and emergency procedures that the
individual is responsible for performing and other operations necessary to
safely operate the irradiator without supervision.
(c) Before an individual is permitted to act
as an irradiator operator without a supervisor present, the individual must
have received on-the-job training or simulator training in the use of the
irradiator as described in the license application. The individual shall also
demonstrate the ability to perform those portions of the operating and
emergency procedures that he or she is to perform.
(d) The licensee shall conduct safety reviews
for irradiator operators at least annually. The licensee shall give each
operator a brief written test on the information. Each safety review must
include, to the extent appropriate, each of the following:
1. Changes in operating and emergency
procedures since the last review, if any;
2. Changes in regulations and license
conditions since the last review, if any;
3. Reports on recent accidents, mistakes, or
problems that have occurred at irradiators, if any;
4. Relevant results of inspections of
operator safety performance;
5.
Relevant results of the facility's inspection and maintenance checks;
and
6. A drill to practice an
emergency or abnormal event procedure.
(e) The licensee shall evaluate the safety
performance of each irradiator operator at least annually to ensure that
regulations, license conditions, and operating, safety, and emergency
procedures are followed. The licensee shall discuss the results of the
evaluation with the operator and shall instruct the operator on how to correct
any mistakes or deficiencies observed.
(f) Individuals who will be permitted
unescorted access to the radiation room of the irradiator or the area around
the pool of an underwater irradiator, but who have not received the training
required for operators and the radiation safety officer, shall be instructed
and tested in any precautions they should take to avoid radiation exposure, any
procedures or parts of procedures listed in
420-3-26-.14(18)
that they are expected to perform or comply
with, and their proper response to alarms required in this part. Tests may be
oral.
(g) Individuals who must be
prepared to respond to alarms required by
420-3-26-.14(7)(b).
and (i), 420-3-26-.14(9)(a),
420-3-26-.14(10)(a) and
(b), and
420-3-26-.14(21)(b)
shall be trained and tested on how to
respond. Each individual shall be retested at least annually. Tests may be
oral.
(18) Operating and
Emergency Procedures.
(a) The licensee shall
have and follow written operating procedures for:
1. Operation of the irradiator, including
entering and leaving the radiation room;
2. Use of personnel dosimeters;
3. Surveying the shielding of panoramic
irradiators;
4. Monitoring pool
water for contamination while the water is in the pool and before release of
pool water to unrestricted areas;
5. Leak testing of sources;
6. Inspection and maintenance checks required
by 420-3-26-.14(22);
7. Loading, unloading, and repositioning
sources, if the operations will be performed by the licensee; and
8. Inspection of movable shielding required
by 420-3-26-.14(7)(h),
if applicable.
(b) The
licensee shall have and follow emergency or abnormal event procedures,
appropriate for the irradiator type, for:
1.
Sources stuck in the unshielded position;
2. Personnel overexposures;
3. A radiation alarm from the product exit
portal monitor or pool monitor;
4.
Detection of leaking sources, pool contamination, or alarm caused by
contamination of pool water;
5. A
low or high water level indicator, an abnormal water loss, or leakage from the
source storage pool;
6. A prolonged
loss of electrical power;
7. A fire
alarm or explosion in the radiation room;
8. An alarm indicating unauthorized entry
into the radiation room, area around pool, or another alarmed area;
9. Natural phenomena, including an
earthquake, a tornado, flooding, or other phenomena as appropriate for the
geographical location of the facility; and
10. The jamming of automatic conveyor
systems.
(c) The
licensee may revise operating and emergency procedures without Agency approval
only if all of the following conditions are met:
1. The revisions do not reduce the safety of
the facility;
2. The revisions are
consistent with the outline or summary of procedures submitted with the license
application;
3. The revisions have
been reviewed and approved by the radiation safety officer; and
4. The users or operators are instructed and
tested on the revised procedures before they are put into use.
(19) Personnel
Monitoring.
(a) Irradiator operators shall
wear either a film badge or a thermoluminescent dosimeter (TLD) while operating
a panoramic irradiator or while in the area around the pool of an underwater
irradiator. The film badge or TLD processor must be accredited by the National
Voluntary Laboratory Accreditation Program for high energy photons in the
normal and accident dose ranges [see
420-3-26-.03(17)(c)]
. Each film badge or TLD must be assigned to and worn by only one individual.
Film badges must be processed at least monthly, and TLDs must be processed at
least quarterly.
(b) Other
individuals who enter the radiation room of a panoramic irradiator shall wear a
dosimeter, which may be a pocket dosimeter. For groups of visitors, only two
people who enter the radiation room are required to wear dosimeters. If pocket
dosimeters are used to meet the requirements of the paragraph, a check of their
response to radiation must be done at least annually. Acceptable dosimeters
must read within ñ20% of the true radiation dose.
(20) Radiation Surveys.
(a) A radiation survey of the area outside
the shielding of the radiation room of a panoramic irradiator must be conducted
with the sources in the exposed position before the facility starts to operate.
A radiation survey of the area above the pool of pool irradiators must be
conducted after the sources are loaded but before the facility starts to
operate. Additional radiation surveys of the shielding must be performed at
intervals not to exceed three years and before resuming operation after
addition of new sources or any modification to the radiation room shielding or
structure that might increase dose rates.
(b) If the radiation levels specified in
420-3-26-.14(8)
are exceeded, the facility must be modified to comply with the requirements in
420-3-26-.14(8).
(c) Portable radiation survey meters must be
calibrated at least annually to an accuracy of ñ20% for the gamma energy
of the sources in use. The calibration must be done at two points on each scale
or, for digital instruments, at one point per decade over the range that will
be used. Portable radiation survey meters must be of a type that does not
saturate and read zero at high radiation dose rates.
(d) Water from the irradiator pool, other
potentially contaminated liquids, and sediments from pool vacuuming must be
monitored for radioactive contamination before release to unrestricted areas.
Radioactive concentrations must not exceed those specified in Table II, Column
2 or Table III of Appendix B, "Annual Limits on Intake (ALIs) and Derived Air
Concentrations (DAC) of Radionuclides for Occupational Exposure; Effluent
Concentrations; Concentrations for Release to Sanitary Sewerage" of rule
420-3-26-.03.
(e) Before releasing resins for unrestricted
use, they must be monitored before release in an area with a background level
less than 0.5 microsievert (0.05 mrem) per hour. The resins may be released
only if the survey does not detect radiation levels above background radiation
levels. The survey meter used must be capable of detecting radiation levels of
0.5 microsievert (0.05 mrem) per hour.
(21) Detection of Leaking Sources.
(a) Each dry-source-storage sealed source
must be tested for leakage at intervals not to exceed six months using a leak
test kit or method approved by the Agency, the U. S. Nuclear Regulatory
Commission, or an Agreement State. In the absence of a certificate from a
transferor that a test has been made within the six months before the transfer,
the sealed source may not be used until tested. The test must be capable of
detecting the presence of 200 becquerels (0.005 æCi) of radioactive
material and must be performed by a person approved by the Agency, the U. S.
Nuclear Regulatory Commission, or an Agreement State, to perform the
test.
(b) For pool irradiators,
sources may not be put into the pool unless the licensee tests the sources for
leaks or has a certificate from a transferor that leak test has been done
within the six months before the transfer. Water from the pool must be checked
for contamination each day the irradiator operates. The check may be done
either by using a radiation monitor on a pool water circulating system or by
analysis of a sample of pool water. If a check for contamination is done by
analysis of a sample of pool water, the results of the analysis must be
available within 24 hours. If the licensee uses a radiation monitor on a pool
water circulating system, the detection of above normal radiation levels must
activate an alarm. The alarm set-point must be set as low as practical, but
high enough to avoid false alarms. The licensee may reset the alarm set-point
to a higher level if necessary to operate the pool water purification system to
clear up contamination in the pool if specifically provided for in written
emergency procedures.
(c) If a
leaking source is detected, the licensee shall arrange to remove the leaking
source from service and have it decontaminated, repaired, or disposed of by an
Agency, the Nuclear Regulatory Commission, or an Agreement State licensee that
is authorized to perform these functions. The licensee shall promptly check its
personnel, equipment, facilities, and irradiated product for radioactive
contamination. No product may be shipped until the product has been checked and
found free of contamination. If a product has been shipped that may have been
inadvertently contaminated, the licensee shall arrange to locate and survey
that product for contamination. If any personnel are found to be contaminated,
decontamination must be performed promptly. If contaminated equipment,
facilities, or products are found, the licensee shall arrange to have them
decontaminated or disposed of by an Agency, the Nuclear Regulatory Commission,
or an Agreement State licensee that is authorized to perform these functions.
If a pool is contaminated, the licensee shall arrange to clean the pool until
the contamination levels do not exceed the appropriate concentration in Table
II, Column 2, Appendix B of
420-3-26-.03. See
420-3-26-.02(29)
for reporting requirements.
(22) Inspection and Maintenance.
(a) The licensee shall perform inspection and
maintenance checks that include, as a minimum, each of the following at the
frequency specified in the license or license application:
1. Operability of each aspect of the access
control system required by
420-3-26-.14(7).
2. Functioning of the source position
indicator required by
420-3-26-.14(11)(b).
3. Operability of the radiation monitor for
radioactive contamination in pool water required by
420-3-26-.14(21)(b)
using a radiation check source, if
applicable.
4. Operability of the
over-pool radiation monitor at underwater irradiators as required by 420-3-26
-.14(10)(b).
5. Operability of the
product exit monitor required by
420-3-26-.14(10)(a).
6. Operability of the emergency source return
control required by
420-3-26-.14(11)(c).
7. Visual inspection of leak-tightness of
systems through which pool water circulates.
8. Operability of the heat and smoke
detectors and extinguisher system required by
420-3-26-.14(9),
without turning extinguishers on.
9. Operability of the means of pool water
replenishment required by
420-3-26-.14(12)(c).
10. Operability of the indicators of high and
low pool water levels required by
420-3-26-.14(12)(d).
11. Operability of the intrusion alarm
required by
420-3-26-.14(7)(i),
if applicable.
12. Functioning and
wear of the system, mechanisms, and cables used to raise and lower
sources.
13. Condition of the
barrier to prevent products from hitting the sources or source mechanism as
required by
420-3-26-.14(13).
14. Amount of water added to the pool to
determine if the pool is leaking.
15. Electrical wiring on required safety
systems for radiation damage.
16.
Pool water conductivity measurements and analysis as required by
420-3-26-.14(23)(b).
(b) Malfunctions and defects found
during inspection and maintenance checks must be repaired within time frames
specified in the license or license application.
(23) Pool Water Purity.
(a) Pool water purification system must be
run sufficiently to maintain the conductivity of the pool water below 20
microsiemens per centimeter under normal circumstances. If pool water
conductivity rises above 20 microsiemens per centimeter, the licensee shall
take prompt actions to lower the pool water conductivity and shall take
corrective actions to prevent future recurrences.
(b) The licensee shall measure the pool water
conductivity frequently enough, but no less than weekly, to assure that the
conductivity remains below 20 microsiemens per centimeter. Conductivity meters
must be calibrated at least annually.
(24) Attendance During Operation.
(a) Both an irradiator operator and at least
one other individual, who is trained on how to respond and prepared to promptly
render or summon assistance if the access control alarm sounds, shall be
present on site:
1. Whenever the irradiator
is operated using an automatic product conveyor system; and
2. Whenever the product is moved into or out
of the radiation room when the irradiator is operated in a batch
mode.
(b) At a panoramic
irradiator at which static irradiations with no movement of the product are
occurring, a person who has received the training on how to respond to alarms
described in
420-3-26-.14(17)(g)
must be on site.
(c) At an underwater irradiator, an
irradiator operator must be present at the facility whenever the product is
moved into or out of the pool. Individuals who move the product into or out of
the pool of an underwater irradiator need not be qualified as irradiator
operators; however, they must have received the training described in
420-3-26-.14(17)(f) and
(g). Static irradiations may be performed
without a person present at the facility.
(25) Entering and Leaving the Radiation Room.
(a) Upon first entering the radiation room of
a panoramic irradiator after an irradiation, the irradiator operator shall use
a survey meter to determine that the source has returned to its fully shielded
position. The operator shall check the functioning of the survey meter with a
radiation check source prior to entry.
(b) Before exiting from and locking the door
to the radiation room of a panoramic irradiator prior to a planned irradiation,
the irradiator operator shall:
1. Visually
inspect the entire radiation room to verify that no one else is in it;
and
2. Activate a control in the
radiation room that permits the sources to be moved from the shielded position
only if the door to the radiation room is locked within a preset time after
setting the control.
(c)
During a power failure, the area around the pool of an underwater irradiator
may not be entered without using an operable and calibrated radiation survey
meter unless the over-the-pool monitor required by
420-3-26-.14(10)(b)
is operating with backup power.
(26) Irradiation of Explosive or
Flammable Materials.
(a) Irradiation of
explosive material is prohibited unless the licensee has received prior written
authorization from the Agency. Authorization will not be granted unless the
licensee can demonstrate that detonation of the explosive would not rupture the
sealed sources, injure personnel, damage safety systems, or cause radiation
overexposures of personnel.
(b)
Irradiation of more than small quantities of flammable material with a flash
point below 140 F is prohibited in panoramic irradiators unless the licensee
has received prior written authorization from the Agency. Authorization will
not be granted unless the licensee can demonstrate that a fire in the radiation
room could be controlled without damage to sealed sources or safety systems and
without radiation overexposures of personnel.
(27) Records and Retention Periods. The
licensee shall maintain the following records at the irradiator for the periods
specified.
(a) A copy of the license, the
license conditions, documents incorporated into the license by reference, and
amendments thereto until superseded by new documents or until the Agency
terminates the license for documents not superseded.
(b) Records of each individual's training,
tests, and safety reviews provided to meet the requirements of 420-3-26
-.14(17)(a), (b), (c), (d), (f), and (g) until three years after the individual
terminates work.
(c) Records of the
annual evaluations of the safety performance of irradiator operators required
by 420-3-26-.14(17)
(e) for three years after the
evaluation.
(d) A copy of the
current operating and emergency procedures required by
420-3-26-.14(18)
until superseded or the Agency terminates
the license. Records of the radiation safety officer's review and approval of
changes in procedures as required by
420-3-26-.14(18)(c)3.
retained for three years from the date of the change.
(e) Film badge and TLD results required by
420-3-26-.14(19)
until the Agency terminates the
license.
(f) Records of radiation
surveys required by
420-3-26-.14(20)
for three years from the date of the
survey.
(g) Records of radiation
survey meter calibrations required by
420-3-26-.14(20)
and pool water conductivity meter
calibrations required by
420-3-26-.14(23)(b)
until three years from the date of
calibration.
(h) Records of the
results of leak tests required by
420-3-26-.14(21)(a)
and the results of contamination checks
required by
420-3-26-.14(21)(b)
for three years from the date of each
test.
(i) Records of inspection and
maintenance checks required by
420-3-26-.14(22)
for three years.
(j) Records of major malfunctions,
significant defects, operating difficulties or irregularities, and major
operating problems that involve required radiation safety equipment for three
years after repairs are completed.
(k) Records of the receipt, transfer and
disposal, of all licensed sealed sources as required by Rule
420-3-26-.01 and Rule
420-3-26-.03.
(l) Records on the design checks required by
420-3-26-.14(15)
and the construction control checks as
required by
420-3-26-.14(16)
until the license is terminated. The records must be signed and dated. The
title or qualification of the person signing must be included.
(m) Records related to decommissioning of the
irradiator as required by
420-3-26-.02(26)(i).
(28) Reports.
(a) In addition to the reporting requirements
in other parts of these rules, the licensee shall report the following events
if not reported under other sections of these rules:
1. Source stuck in an unshielded
position.
2. Any fire or explosion
in a radiation room.
3. Damage to
the source racks.
4. Failure of the
cable or drive mechanism used to move the source racks.
5. Inoperability of the access control
system.
6. Detection of radiation
source by the product exit monitor.
7. Detection of radioactive contamination
attributable to licensed radioactive material.
8. Structural damage to the pool liner or
walls.
9. Water loss or leakage
from the source storage pool, greater than the irradiator pool design
parameters submitted by the licensee or applicant.
10. Pool water conductivity exceeding 100
microsiemens per centimeter.
(b) The report must include a telephone
report within 24 hours as described in
420-3-26-.02(29)(c)1.
and a written report within 30 days as described in
420-3-26-.02(29)(c)2.
Authors: David Turberville, Division of Radiation
Control, Bureau of Health Care Standards, Alabama Department of Public
Health.
Statutory Authority:
Code of Ala.
1975, §§
22-14-4,
22-14-6,
22-14-7,
22-14-8,
22-14-9,
22-14-11,
22-14-12,
22-14-13,
22-14-14,
22-2-1,
22-2-2,
22-2-5,
22-2-6.