Protection of Stratospheric Ozone: Determination 39 for the Significant New Alternatives Policy Program, 99720-99727 [2024-28307]
Download as PDF
99720
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
Table of Contents
ENVIRONMENTAL PROTECTION
AGENCY
40 CFR Part 82
[EPA–HQ–OAR–2003–0118; FRL–12145–01–
OAR]
RIN 2060–AG12
Protection of Stratospheric Ozone:
Determination 39 for the Significant
New Alternatives Policy Program
Environmental Protection
Agency (EPA).
ACTION: Determination of acceptability.
AGENCY:
This determination of
acceptability expands the list of
acceptable substitutes pursuant to the
U.S. Environmental Protection Agency’s
Significant New Alternatives Policy
program. This action lists four
substitutes as acceptable additional
substitutes for use in the refrigeration
and air conditioning and foam blowing
sectors.
DATES: This determination is applicable
on December 11, 2024.
ADDRESSES: EPA established a docket
for this action under Docket ID No.
EPA–HQ–OAR–2003–0118
(continuation of Air Docket A–91–42).
All electronic documents in the docket
are listed in the index at https://
www.regulations.gov. Although listed in
the index, some information is not
publicly available, e.g., confidential
business information (CBI) or other
information whose disclosure is
restricted by statute. Publicly available
docket materials are available either
electronically at https://
www.regulations.gov or in hard copy at
the EPA Docket Center (EPA/DC),
(Docket Nos. A–91–42 and EPA–HQ–
OAR–2003–0118), William J. Clinton
West, Room 3334, 1301 Constitution
Avenue NW, Washington, DC 20460.
The telephone number for the Public
Reading Room is (202) 566–1744, and
the telephone number for the Air and
Radiation Docket is (202) 566–1742. The
Docket Center’s hours of operations are
8:30 a.m.–4:30 p.m., Monday–Friday
(except Federal Holidays). For further
information on the EPA Docket Center
services and the current status, please
visit online at https://www.epa.gov/
dockets.
FOR FURTHER INFORMATION CONTACT:
Nathaniel Burola, Stratospheric
Protection Division, Office of
Atmospheric Protection (Mail Code
6205A), U.S. Environmental Protection
Agency, 1200 Pennsylvania Avenue
NW, 20460; telephone number: 202–
564–2883; email address:
Burola.Nathaniel@epa.gov.
lotter on DSK11XQN23PROD with RULES1
SUMMARY:
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
I. Listing of New Acceptable Substitutes
A. Refrigeration and Air Conditioning
1. R–471A
2. R–480A
3. R–513A
B. Foam Blowing
1. Extruded Polystyrene (XPS) Blowing
Agent Blends of 0 to 90 Percent HFO–
1336mzz(Z), 0 to 90 Percent HFO–
1234ze(E), 0 to 75 Percent HFC–152a,
and 0 to 90 Percent CO2
Appendix A: Summary of Decisions for New
Acceptable Substitutes
SUPPLEMENTARY INFORMATION:
I. Listing of New Acceptable Substitutes
This action is listing as acceptable
additional substitutes for use in the
refrigeration and air conditioning and
foam blowing sectors. This action
presents EPA’s most recent decisions
under the Significant New Alternatives
Policy (SNAP) program to list as
acceptable several substitutes in
different end-uses. The new substitutes
are:
• R–471A in retail food refrigeration,
industrial process refrigeration, and
cold storage warehouses (retrofit
equipment only);
• R–480A in cold storage warehouses,
commercial ice machines, positive
displacement chillers, refrigerated
transport, and water coolers (retrofit
equipment only);
• R–513A in residential and light
commercial air conditioning and heat
pumps—self-contained units (new
equipment only);
• XPS foam blowing agent blends of
0 to 90 percent hydrofluoroolefin
(HFO)–1336mzz(Z), 0 to 90 percent
HFO–1234ze(E), 0 to 75 percent
hydrofluorocarbon (HFC)–152a, and 0 to
90 percent carbon dioxide (CO2) in
polystyrene: extruded boardstock and
billet.
Listing decisions in the end-uses in
this document do not prejudge EPA’s
listings of these substitutes for other
end-uses. For additional information on
SNAP, visit the SNAP website at https://
www.epa.gov/snap. The full lists of
acceptable substitutes for ozonedepleting substances (ODS) in the
industrial sectors covered by the SNAP
program are available at https://
www.epa.gov/snap/substitutes-sector.
For more information on the Agency’s
process for administering the SNAP
program or criteria for evaluation of
substitutes, refer to the initial SNAP
rulemaking (59 FR 13044; March 18,
1994). The regulations are codified at 40
CFR part 82, subpart G. SNAP decisions
and the appropriate Federal Register
citations are available at: https://
www.epa.gov/snap/snap-regulations.
PO 00000
Frm 00026
Fmt 4700
Sfmt 4700
Under the SNAP program, EPA may list
a substitute as acceptable for specified
end-uses where the Agency has
reviewed the substitute and found no
reason to restrict or prohibit its use.
Substitutes listed as unacceptable;
acceptable, subject to narrowed use
limits; or acceptable, subject to use
conditions are also listed in the
appendices to 40 CFR part 82, subpart
G.
This document discusses each
substitute listing in detail and
summarizes the results of EPA’s
assessment of the human health and
environmental risks posed by each
substitute. EPA’s evaluation applies the
criteria in 40 CFR 82.180(a)(7),
including atmospheric effects and
related health and environmental
effects, ecosystem risks, occupational
risks, consumer risks, flammability, and
cost and availability of the substitute.
EPA evaluates these criteria in risk
screens, or technical documents that
evaluate risks to human health and the
environment from substitutes in specific
end-uses, including comparisons to
other available substitutes and
evaluations against relevant thresholds
of risk starting with protective
assumptions. The risk screens cited in
this document include evaluation of
atmospheric effects, toxicity data,
exposure assessments, flammability,
and other environmental impacts such
as ecotoxicity and local air quality
impacts. You can find more information
on the criteria used in the evaluation of
substitutes in the SNAP program at
https://www.epa.gov/snap/snapregulations.
In this document, EPA determined the
global warming potential (GWP) for a
chemical or blend using the 100-year
GWP values from the Intergovernmental
Panel on Climate Change’s (IPCC)
Fourth Assessment Report (AR4) 1 for
substances or components of blends if
included.2 Note that Annex F to the
Montreal Protocol on Substances that
Deplete the Ozone Layer lists GWPs for
HFCs that are numerically equivalent to
1 IPCC, 2007: Climate Change 2007: The Physical
Science Basis. Contribution of Working Group I to
the Fourth Assessment Report of the
Intergovernmental Panel on Climate Change
[Solomon, S., Qin, D., Manning, M., Chen, Z.,
Marquis, M., Averyt, K.B., Tignor M., and Miller,
H.L. (eds.)]. Cambridge University Press,
Cambridge, United Kingdom and New York, NY,
USA. Available at: https://www.ipcc.ch/
publications_and_data/ar4/wg1/en/contents.html.
2 The IPCC, 2007 100-year GWP values are
consistent with the exchange values for the
regulated HFCs listed in subsection (c) of the AIM
Act and with the GWPs in Annex F of the Montreal
Protocol.
E:\FR\FM\11DER1.SGM
11DER1
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES1
the AR4 values.3 These HFC 100-year
GWP values are also numerically
equivalent to the exchange values listed
in the American Innovation and
Manufacturing Act of 2020 (hereafter
referred to as ‘‘the AIM Act’’). If no GWP
is provided in AR4 for a substance, the
SNAP program is using the 100-year
GWP listed in World Meteorological
Organization (WMO), 2022.4 To
calculate the GWP of blends of
chemicals, such as the listed refrigerant
blends, this document weights the GWP
of each component of the blend by its
mass percentage. This method of
calculating GWPs is consistent with the
method used to calculate GWPs in the
October 2023 Technology Transitions
Rule as codified at 40 CFR 84.64.
Under section 612 of the Clean Air
Act (CAA), the SNAP program reviews
substitutes using a comparative risk
framework in different industrial
sectors. In making listing decisions, EPA
considers overall risk to human health
and the environment. As a general
matter, the substitutes being added
through this action to the acceptable
lists have a similar or lower risk than
other substitutes already listed as
acceptable in those end-uses. However,
certain substitutes may have a higher
risk than certain other substitutes
already listed as acceptable or
acceptable subject to restrictions. In
such cases, those already-listed
alternatives have other factors that limit
their use in some situations within a
particular end-use.
Appendix A contains tables
summarizing each listing decision in
this action. The statements in the
‘‘Further Information’’ column in the
tables provide additional information,
but these are not legally binding under
section 612 of the CAA. Although users
are not required to follow
recommendations in the ‘‘Further
Information’’ column of the table under
section 612 of the CAA, some of these
statements may refer to obligations that
are enforceable or binding under federal
or state programs other than the SNAP
program. The identification of other
enforceable or binding requirements
should not be construed as a
comprehensive list of such obligations.
In many instances, the information
simply refers to standard operating
practices in existing industry standards
3 Annex F of the Montreal Protocol is available at:
https://ozone.unep.org/treaties/montreal-protocol/
articles/annex-f-controlled-substances.
4 WMO, Scientific Assessment of Ozone
Depletion: 2022, GAW Report No. 278, 509 pp.;
WMO: Geneva, 2022. Available at: https://
ozone.unep.org/system/files/documents/ScientificAssessment-of-Ozone-Depletion-2022.pdf. (WMO,
2022).
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
and/or building codes. When using
these substitutes in the identified enduse, EPA strongly encourages you to
apply the information in the ‘‘Further
Information’’ column. Many of these
recommendations, if adopted, would
not require significant changes to
existing operating practices.
It should be noted that a substitute
listed as acceptable under the SNAP
program may also be subject to
requirements or limitations under other
statutory or regulatory provisions. For
example, there are relevant regulations
under subsection (i) of the AIM Act that
restrict the use of certain HFCs in a
variety of sectors and subsectors. See 88
FR 73098 (October 24, 2023).
Consequently, if a substitute listed as
acceptable under the SNAP program is
also subject to limitations on its use
under other regulations, it may not be
permitted for use in accordance with
those other regulations. Those intending
to use a substitute listed as acceptable
under the SNAP program may need to
consider restrictions under subsection
(i) of the AIM Act, as well as other
relevant authorities, and must also be
followed.5
You can find submissions to EPA for
the substitutes listed in this document,
as well as other materials supporting the
decisions in this action, in the docket
(EPA–HQ–OAR–2003–0118) at https://
www.regulations.gov.
A. Refrigeration and Air Conditioning
1. R–471A
EPA’s decision: EPA finds R–471A
acceptable as a substitute for use in:
• Cold storage warehouses (retrofit
equipment only);
• Industrial process refrigeration
(retrofit equipment only);
• Retail food refrigeration—
Refrigerated food processing and
dispensing equipment (retrofit
equipment only);
• Retail food refrigeration—Remote
condensing units (retrofit equipment
only);
• Retail food refrigeration—
Supermarket systems (retrofit
equipment only).
R–471A, marketed under the trade
name Solstice® N71, is a weighted blend
of 78.7 percent HFO–1234ze(E), also
known as trans-1,3,3,3-tetrafluoroprop1-ene (Chemical Abstracts Service
Registry Number [CAS Reg. No.] 29118–
5 For example, there may be restrictions or
prohibitions in regulations issued under section 610
of the CAA at 40 CFR part 82 subpart C for
nonessential products containing ODS, under the
Toxic Substances Control Act, under the
Occupation Safety and Health Act, and under state
or local laws and regulations that warrant
consideration.
PO 00000
Frm 00027
Fmt 4700
Sfmt 4700
99721
24–9); 17.0 percent HFO–1336mzz(E),
also known as trans-1,1,1,4,4,4hexafluoro-2-butene (CAS Reg. No.
66711–86–2); and 4.3 percent HFC–
227ea, which is also known as
1,1,1,2,3,3,3-heptafluoropropane (CAS
Reg. No. 431–89–0).
You may find a copy of the
applicant’s submission, with CBI
redacted, providing the required health
and environmental information for this
substitute in this end-use in the docket
(EPA–HQ–OAR–2003–0118) at https://
www.regulations.gov under the name,
‘‘Supporting Materials for Notice 39
Listing of R–471A in Refrigeration and
Air Conditioning. SNAP Submission
Received September 15, 2023.’’ EPA
performed assessments to examine the
health and environmental risks of this
substitute, and the results are
summarized below. These assessments
are available in the docket EPA–HQ–
OAR–2003–0118:
• ‘‘Risk Screen on Substitutes in
Retail Food Refrigeration (Retrofit
Equipment) Substitute: R–471A
(Solstice® N71).’’
• ‘‘Risk Screen on Substitutes in
Industrial Process Refrigeration and
Cold Storage Warehouses (Retrofit
Equipment) Substitute: R–471A
(Solstice® N71).’’
Environmental information: R–471A
has an ozone depletion potential (ODP)
of 0. Its components, HFO–1234ze(E),
HFO–1336mzz(E), and HFC–227ea, have
GWPs of 1,6 26,7 and 3,220,8
respectively. When these values are
weighted by mass percentage of the
blend, R–471A has a GWP of about 144.
The components of R–471A are
excluded from the EPA’s regulatory
definition of volatile organic
compounds (VOC) under CAA
regulations (see 40 CFR 51.100(s))
addressing the development of state
implementation plans (SIPs) to attain
and maintain the National Ambient Air
Quality Standards (NAAQS). Knowingly
venting or otherwise knowingly
releasing this refrigerant blend is
limited by the venting prohibition under
section 608(c)(2) of the CAA, codified in
EPA regulations at 40 CFR 82.154(a).
Flammability information: The
component HFO–1234ze(E) has lower
flammability as defined using the
standard test method American Society
of Testing and Materials (ASTM) E681.9
The other two components of R–471A
are not flammable using the same
6 WMO,
2022.
2022.
8 Annex F to the Montreal Protocol.
9 ASTM, E681. Standard Test Method for
Concentration Limits of Flammability of Chemicals
(Vapors and Gases).
7 WMO,
E:\FR\FM\11DER1.SGM
11DER1
99722
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES1
method. R–471A is not flammable as
formulated, in the worst-case
formulation for flammability (WCF) and
the worst-case of fractionation for
flammability (WCFF). The American
Society of Heating, Refrigerating, and
Air-Conditioning Engineers (ASHRAE)
has assigned R–471A a flammability
class of ‘‘1,’’ meaning it does not
propagate a flame under standard test
conditions.10
Toxicity and exposure data: Potential
health effects of exposure to this
substitute include drowsiness or
dizziness. The substitute may also
irritate the skin or eyes or cause frostbite
in the case of rapid evaporation of the
liquid. The substitute could cause
asphyxiation if air is displaced by
vapors in a confined space. Excessive
exposure may cause central nervous
system effects including drowsiness and
dizziness. Excessive exposure may also
cause cardiac arrhythmia. These
potential health effects are common to
many refrigerants.
ASHRAE has adopted an occupational
exposure limit (OEL) for the blend of
710 ppm 11 12 on an eight-hour timeweighted average (8-hr TWA) for HFO–
1336mzz(E), the American Industrial
Hygiene Association (AIHA) has
established a WEEL of 1,000 ppm (8-hr
TWA) for HFC–227ea, and ASHRAE has
adopted an OEL of 800 ppm (8-hr TWA)
for HFO–1234ze(E).13 EPA anticipates
that users will be able to meet these
workplace guidance limits and address
potential health risks by following
recommendations in the manufacturer’s
safety data sheet (SDS), ASHRAE
Standard 15,14 other industry standards,
and other safety precautions common to
the refrigeration and air conditioning
industry.
Comparison to other substitutes in
these end-uses: R–471A has an ODP of
0, comparable to or less than other listed
substitutes in retrofits for these end-uses
with ODPs ranging from 0 to less than
0.0004.
As a retrofit for supermarket systems,
remote condensing units, and
refrigerated food processing and
dispensing equipment, R–471A with a
GWP of 144 is lower than that of all
other acceptable substitutes such as R–
450A which has a GWP of 601; R–513A
10 ASHRAE Standard 34–2022: Designation and
Safety Classification of Refrigerants. (ASHRAE,
2022).
11 ASHRAE, 2022.
12 Trans-1,1,1,4,4,4-hexafluoro-2-butene (HFO–
1336mzz–E) (2018). Toxicology and Industrial
Health. 2019; 35(3):204–210. doi:10.1177/
0748233719825529.
13 ASHRAE, 2022.
14 ASHRAE 15. Safety Standard for Refrigeration
Systems.
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
with a GWP of 630; R–448A with a GWP
of 1,386; R–449A with a GWP of 1,396;
R–449B with a GWP of 1,412; R–407C
with a GWP of 1,770; R–407F with a
GWP of 1,825; and R–407A with a GWP
of 2,107.
For retrofits in industrial process
refrigeration, R–471A’s GWP of 144 is
lower than that of other acceptable
substitutes such as HFC–134a which has
a GWP of 1,430; R–407C with a GWP of
1,770; and R–407F with a GWP of 1,825.
Other alternatives in this sector have a
lower GWP than R–471A such as CO2
with a GWP of 1 and R–290 (propane)
with a GWP of 3. There may be
situations in which lower-GWP options
may not be feasible for certain
retrofitted industrial process
refrigeration equipment. For example,
CO2, which has a GWP of 1 is a highpressure refrigerant and cannot be used
as a retrofit for low-pressure refrigerant
systems. R–471A is a low-pressure
refrigerant, making it more technically
feasible to retrofit systems that use
similar low-pressure refrigerants. R–290
is an A3, highly flammable refrigerant
and may not be feasible for certain
retrofitted industrial process
refrigeration equipment where
flammability is a concern.
Further, refrigerants offer cooling
within a specific temperature range.
Adding R–471A to the list of available
substitutes in industrial process
refrigeration systems may offer a
refrigerant that achieves a specific
cooling temperature that other retrofit
alternatives with lower GWPs cannot
achieve.15 For retrofits of cold storage
warehouses, R–471A’s GWP of 144 is
lower than that of all other acceptable
substitutes such as R–450A with a GWP
of 601; R–513A with a GWP of 630;
HFC–134a with a GWP of 1,430; R–407C
with a GWP of 1,770; and R–407F with
a GWP of 1,825.
Flammability and toxicity risks are
comparable to or lower than
flammability and toxicity risks of other
available substitutes in the same retrofit
end-uses. Toxicity risks can be
minimized by use consistent with the
AIHA and OARS WEELs, ASHRAE
OELs and ASHRAE 15, other industry
standards, recommendations in the
manufacturer’s SDS, and other safety
precautions common in the refrigeration
and air conditioning industry.
Based on the considerations described
above, EPA finds R–471A acceptable as
a retrofit refrigerant for the following
end-uses: cold storage warehouses,
15 The October 2023 Technology Transitions Rule
does not restrict the use of HFCs (i.e., establish
GWP limits) in retrofit applications (See 88 FR
73127).
PO 00000
Frm 00028
Fmt 4700
Sfmt 4700
industrial process refrigeration, and
retail food refrigeration (including
supermarket systems, remote
condensing units, and refrigerated food
processing and dispensing equipment),
because it does not pose greater overall
environmental and human health risk
than other available substitutes in the
same end-uses.
2. R–480A
EPA’s decision: EPA finds R–480A
acceptable as a substitute for use in:
• Cold storage warehouses (retrofit
equipment only);
• Commercial ice machines (retrofit
equipment only);
• Positive displacement chillers
(retrofit equipment only);
• Refrigerated transport (retrofit
equipment only);
• Water coolers (retrofit equipment
only).
R–480A, marketed under the trade
name RS–20, is a weighted blend of 5
percent CO2 (CAS Reg. No. 124–38–9),
86 percent HFO–1234ze(E), also known
as trans-1,3,3,3-tetrafluoroprop-1-ene
(CAS Reg. No. 29118–24–9), and 9
percent HFC–227ea, also known as
1,1,1,2,3,3,3-heptafluoropropane (CAS
Reg. No. 431–89–0).
You may find a copy of the
applicant’s submission, with CBI
redacted, providing the required health
and environmental information for this
substitute in this end-use in the docket
(EPA–HQ–OAR–2003–0118) at https://
www.regulations.gov under the name,
‘‘Supporting Materials for Notice 39
Listing of R–480A in Refrigeration and
Air Conditioning. SNAP Submission
Received May 16, 2024.’’ EPA
performed assessments to examine the
health and environmental risks of this
substitute, and the results are
summarized below. These assessments
are available in the docket EPA–HQ–
OAR–2003–0118:
• ‘‘Risk Screen on Substitutes in Cold
Storage Warehouses (Retrofit
Equipment). Substitute: R–480A (RS–
20).’’
• ‘‘Risk Screen on Substitutes in
Commercial Ice Machines (Retrofit
Equipment). Substitute: R–480A (RS–
20).’’
• ‘‘Risk Screen on Substitutes in
Chillers (Retrofit Equipment).
Substitute: R–480A (RS–20).’’
• ‘‘Risk Screen on Substitutes in
Refrigerated Transport (Retrofit
Equipment). Substitute: R–480A (RS–
20).’’
• ‘‘Risk Screen on Substitutes in
Water Coolers (Retrofit Equipment).
Substitute: R–480A (RS–20).’’
Environmental information: R–480A
has an ODP of 0. This blend consists of
E:\FR\FM\11DER1.SGM
11DER1
lotter on DSK11XQN23PROD with RULES1
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
CO2 with a GWP of 1,16 HFO–1234ze(E)
with a GWP of 1,17 and HFC–227ea with
a GWP of 3,220.18 Weighting these
values by mass percentage results in a
GWP of 291 for R–480A. The
components of R–480A are excluded
from EPA’s regulatory definition of VOC
under CAA regulations (see 40 CFR
51.100(s)) addressing the development
of SIPs to attain and maintain the
NAAQS. Knowingly venting or
otherwise knowingly releasing this
refrigerant blend is limited by the
venting prohibition under CAA section
608(c)(2), codified at 40 CFR 82.154(a).
Flammability information: The
component HFO–1234ze(E) has lower
flammability as defined using the
standard test method ASTM E681, while
the other two components of R–480A
are not flammable using the same
method. R–480A is not flammable as
formulated, in the WCF and the WCFF.
ASHRAE has assigned R–480A a
flammability class of ‘‘1,’’ meaning it
does not propagate a flame under
standard test conditions.
Toxicity and exposure data: The
substitute may be hazardous if
inhalation, skin contact, or eye contact
with the substitute occurs at sufficiently
high levels. The substitute could cause
symptoms of asphyxiation if air is
displaced by vapors in a confined space.
These potential health effects are
common to many refrigerants.
ASHRAE has adopted an OEL for the
blend of 900 ppm (8-hr TWA).19 For the
components of R–480A, the U.S.
Occupational Safety and Health
Administration (OSHA) has established
a permissible exposure limit (PEL) of
5,000 ppm (8-hr TWA) for CO2, AIHA
has established a WEEL of 1,000 ppm
for HFC–227ea, and ASHRAE has
adopted an OEL of 800 ppm (8-hr TWA)
for HFO–1234ze(E).20 EPA anticipates
that users will be able to meet these
workplace guidance limits and address
potential health risks by following
recommendations in the manufacturer’s
SDS, ASHRAE Standard 15, other
industry standards, and other safety
precautions common to the refrigeration
and air conditioning industry.
Comparison to other substitutes in
these end-uses: R–480A has an ODP of
0, comparable to or less than other listed
substitutes in these end-uses with ODPs
ranging from 0 to less than 0.0004.
For cold storage warehouses, R–480A
with a GWP of 291 is lower than all
other acceptable substitutes for retrofit
16 IPCC,
2007.
2022.
18 Annex F to the Montreal Protocol.
19 ASHRAE, 2022, Addendum h.
20 ASHRAE, 2022.
17 WMO,
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
equipment in this end-use, such as a
number of HFC blends, including R–
450A and R–513A, with GWPs of 601
and 630, respectively.
For commercial ice machines, R–
480A’s GWP of 291 is lower than all
other acceptable substitutes for retrofit
equipment in this end-use, such as a
number of HFC blends, including R–
450A and R–513A, with GWPs of 601
and 630, respectively.
For positive displacement chillers, R–
480A’s GWP of 291 is lower than that
of certain other acceptable substitutes
for retrofit equipment in this end-use,
such as a number of HFC blends,
including R–450A and R–513A, with
GWPs of 601 and 630, respectively. The
GWP of R–480A is higher than the
GWPs of two other acceptable
substitutes for retrofit equipment in this
end-use, namely R–1224yd(Z) and R–
514A, with GWPs of 1 21 and 2,22
respectively. EPA is listing this
substitute as acceptable because
available lower-GWP options are not
feasible to use in certain applications.
For example, equipment retrofitted with
R–480A can operate within a specific
temperature range and pressure range
that other retrofitted chillers using
lower-GWP options such as R–
1224yd(Z) and R–514A cannot achieve.
For refrigerated transport, R–480A’s
GWP of 291 is lower than that of all
other acceptable substitutes for retrofit
equipment in this end-use, such as R–
450A, R–513A, and HFC–134a, with
GWPs of 601, 630, and 1,430,
respectively.
For water coolers, R–480A’s GWP of
291 is lower than that of all other
acceptable substitutes for retrofit
equipment in this end-use, such as R–
450A, R–513A, R–426A, and R–411A,
with GWPs of 601, 630, 1,510, and
1,600, respectively.
Flammability and toxicity risks are
comparable to or lower than
flammability and toxicity risks of other
available substitutes in the same retrofit
end-uses. Toxicity risks can be
minimized by use consistent with the
OSHA PEL, AIHA WEEL, ASHRAE
OELs, ASHRAE 15 and other industry
standards, recommendations in the
manufacturer’s SDS, and other safety
precautions common in the refrigeration
and air conditioning industry.
Based on the considerations described
above, EPA finds R–480A acceptable in
retrofit equipment in the following enduses: cold storage warehouses,
21 WMO,
2022.
value is calculated by weighting the GWPs
of HFO–1336mzz(Z) (2) and 1,2-dichloroethene(Z)
(1) from WMO, 2022 by the mass percentages of the
blend components of 74.7 percent and 25.3 percent,
respectively.
22 This
PO 00000
Frm 00029
Fmt 4700
Sfmt 4700
99723
commercial ice machines, positive
displacement chillers, refrigerated
transport, and water coolers, because it
does not pose greater overall
environmental and human health risk
than other available substitutes in the
same end-uses.
3. R–513A
EPA’s decision: EPA finds R–513A
acceptable as a substitute for use in:
• Residential and light commercial
air conditioning and heat pumps—selfcontained units (new equipment only).
R–513A, marketed under the trade
name Opteon® XP–10, is a weighted
blend of 44 percent HFC–134a and 56
percent HFO–1234yf by weight. HFC–
134a is an HFC and is also known as
1,1,1,2-tetrafluoroethane (CAS Reg. No.
811–97–2). HFO–1234yf is an HFO and
is also known as 2,3,3,3 tetrafluoroprop1-ene (CAS Reg. No.754–12–1).
You may find a copy of the
applicant’s submission, with CBI
redacted, providing the required health
and environmental information for this
substitute in this end-use category in
Docket EPA–HQ–OAR–2003–0118 at
www.regulations.gov under the name,
‘‘SNAP Information Notice for R–513A
as a Refrigerant. SNAP Submission
Received January 9, 2024.’’ EPA has
performed an assessment to examine the
health and environmental risks of this
substitute and the results are
summarized below. This assessment is
available in Docket EPA–HQ–OAR–
2003–0118:
• ‘‘Risk Screen on Substitutes for Use
in Residential and Light Commercial Air
Conditioning and Heat Pumps—SelfContained Units (New Equipment)
Substitute: R–513A (Opteon® XP–10).’’
Environmental information: R–513A
is a blend of HFC–134a and HFO–
1234yf with an ODP of 0. HFC–134a has
a GWP of 1,430 23 and HFO–1234yf has
a GWP of 1.24 The GWP of R–513A is
630 when the two components are
weighted by mass percentage of their
GWPs. All components of the blends are
excluded from the EPA’s regulatory
definition of VOC under CAA
regulations (see 40 CFR 51.100(s))
addressing the development of SIPs to
attain and maintain the NAAQS.
Knowingly venting or otherwise
knowingly releasing this refrigerant
blend is limited by the venting
prohibition under section 608(c)(2) of
the CAA, codified in EPA’s regulations
at 40 CFR 82.154(a).
Flammability information: The
component HFO–1234yf has lower
flammability as defined using the
23 Annex
24 WMO,
E:\FR\FM\11DER1.SGM
F to the Montreal Protocol.
2022.
11DER1
lotter on DSK11XQN23PROD with RULES1
99724
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
standard test method ASTM E681. HFC–
134a is not flammable using the same
method. R–513A is not flammable as
formulated in the WCF and the WCFF.
ASHRAE has assigned R–513A a
flammability class of ‘‘1,’’ meaning it
does not propagate a flame under
standard test conditions.
Toxicity and exposure data: Potential
health effects of exposure to this
substitute include skin and eye
irritation and frostbite upon contact.
The substitute could cause asphyxiation
if air is displaced by vapors in a
confined space. These potential health
effects are common to many refrigerants.
EPA anticipates that R–513A will be
used consistent with the
recommendations specified in the SDS.
ASHRAE has adopted an OEL for the
blend R–513A of 650 ppm as an 8-hr
TWA. The AIHA has established WEELs
of 1000 ppm for HFC–134a and of 500
ppm for HFO–1234yf, both as an 8-hr
TWA. EPA anticipates that users will be
able to meet these workplace guidance
limits and will address potential health
risks by following requirements and
recommendations in the manufacturer’s
SDSs, ASHRAE Standard 15, other
industry standards, and other safety
precautions common to the refrigeration
and air conditioning industry.
Comparison to other refrigerants in
this end-use category: R–513A has an
ODP of 0, which is comparable to other
acceptable substitutes in the residential
and light commercial air conditioning
and heat pumps—self-contained units
end-use category with ODPs ranging
from 0 to less than 0.0004. R–513A
which has a GWP of 630 is lower than
or comparable to those of some
acceptable substitutes in the same enduse category for which we are finding it
acceptable, such as R–452B which has
a GWP of 700 and HFC–32 which has
a GWP of 675. R–513A has a GWP of
630, which is higher than those of other
acceptable substitutes in this end-use
category such as R–290, which has a
GWP of 3, R–454A, which has a GWP
of 240, R–454B, which has a GWP of
470, R–454C, which has a GWP of 150,
and R–457A, which has a GWP of 140.
While other acceptable substitutes
have lower GWPs, EPA is listing R–
513A as acceptable in this end-use
category recognizing it likely will be
used only in certain self-contained units
that use R–134a where other available
options are not technically feasible.
Self-contained units can include but are
not limited to window units, packaged
terminal air conditioners, packaged
terminal heat pumps, portable room air
conditioning units, and portable air
conditioners used to cool commercial
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
aircraft interiors while on the ground.25
As a general matter, the replacements
for most of the equipment in the
residential and light commercial air
conditioning and heat pumps end-use
category use refrigerants that mimic the
thermodynamic qualities and high
pressure of R–410A which was the
dominant refrigerant used for the
majority of equipment types in this enduse category. There are, however, some
specific applications where R–134a was
used in self-contained units because of
its unique thermodynamic properties
that make it a better choice. For
example, self-contained portable air
conditioners used to cool commercial
aircraft while on the ground currently
use R–134a. This refrigerant is used
because R–134a is optimized for
equipment that use screw compressors
and need to be able to operate at
extremely high ambient temperatures
with high humidity. R–513A’s
thermodynamic properties closely
mimic those of R–134a, making it an
important option for applications where
R–134a is used. As noted above, selfcontained portable air conditioners used
to cool the aircraft interior while on the
ground must function in a wide range of
ambient temperatures and humidities,
making R–513A an important option for
this specific use. Other available
refrigerant options with lower GWPs do
not have the correct thermodynamic
properties to fit the technical needs for
this specific use. In addition, R–513A
and R–134a are both low pressure
refrigerants. As a result, R–513A could
replace R–134a in equipment with
minimal modifications but it is not
expected to replace R–410A due to the
extensive re-engineering required.
EPA expects that use of R–513A in
residential and light commercial air
conditioning and heat pumps will be
limited to a narrow set of specific
applications because it is likely to be
used only in those few applications
where R–134a is currently used in selfcontained units and where other
available options are not technically
feasible. Therefore, EPA is listing this
refrigerant as acceptable for use in the
residential and light commercial air
conditioning and heat pumps–selfcontained units end-use category.
Flammability and toxicity risks are
comparable to or lower than
flammability and toxicity risks of other
25 These are all examples of equipment defined as
‘‘factory sealed appliances’’ in the UL 60335–2–40
standard for electrical heat pumps, air-conditioners,
and dehumidifiers, in which all refrigerating system
parts have been sealed tight during the
manufacturing process. Other equipment that meets
the UL definition of factory sealed appliances are
also self-contained units.
PO 00000
Frm 00030
Fmt 4700
Sfmt 4700
available substitutes in the same enduse category. For example, R–513A is
non-flammable and has comparable or
lower flammability risk compared to
other acceptable refrigerants in this enduse category, such as the lower
flammability refrigerants R–454B and
R–454C. Toxicity risks can be
minimized by use consistent with the
AIHA’s WEELs, ASHRAE’s OEL,
ASHRAE 15 and other industry
standards, recommendations in the SDS,
and other safety precautions common in
the refrigeration and air conditioning
industry.
Based on the considerations described
above, EPA finds R–513A acceptable in
new self-contained units in the
residential and light commercial air
conditioning end-use because it
provides a lower-GWP alternative for
this end-use category. R–513A does not
pose greater overall environmental and
human health risk than other available
substitutes in the same end-use
category.
B. Foam Blowing
1. Extruded Polystyrene (XPS) Blowing
Agent Blends of 0 to 90 Percent HFO–
1336mzz(Z), 0 to 90 Percent HFO–
1234ze(E), 0 to 75 Percent HFC–152a,
and 0 to 90 Percent CO2
EPA’s decision: EPA finds blends of 0
to 90 percent HFO–1336mzz(Z), 0 to 90
percent HFO–1234ze(E), 0 to 75 percent
HFC–152a, and 0 to 90 percent CO2
(‘‘HFO–1336mzz(Z)/HFO–1234ze(E)/
HFC–152a/CO2 blends’’) acceptable as a
substitute for use as a foam blowing
agent in:
• Polystyrene: extruded boardstock
and billet.
HFO–1336mzz(Z) is an HFO and is
also called (Z)-1,1,1,4,4,4-hexafluorobut2-ene or cis-1,1,1,4,4,4-hexafluorobut-2ene (CAS Reg. No. 692–49–9); it also
goes by the trade names of FEA–1100 or
Formacel® 1100. HFO–1234ze(E) is an
HFO and is also known as trans-1,3,3,3tetrafluoroprop-1-ene (CAS Reg. No.
29118–24–9). HFC–152a is an HFC and
is also called ethane, 1,1-difluoro (CAS
Reg. No. 75–37–6). CO2 has CAS Reg.
No. 124–38–9.
You may find a copy of the
applicant’s submission, with CBI
redacted, providing the required health
and environmental information for this
substitute in this end-use in the docket
(EPA–HQ–OAR–2003–0118) at https://
www.regulations.gov under the name,
‘‘SNAP Information Notice for Extruded
Polystyrene Blend of 0 to 90% HFO–
1336mzz(Z), 0 to 90% HFO–1234ze(E),
0 to 75% HFC–152a, and 0 to 90% CO2
as a Foam Blowing Agent SNAP
Submission Received August 7, 2023.’’
E:\FR\FM\11DER1.SGM
11DER1
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
EPA has performed an assessment to
examine the health and environmental
risks of this substitute. This assessment
is available in the docket EPA–HQ–
OAR–2003–0118:
• ‘‘Risk Screen on Substitutes for Use
in Extruded Polystyrene Boardstock and
Billet Foam Substitute: HFO–
1336mzz(Z)/HFO–1234ze(E)/HFC–152a/
CO2 Blends.’’
Environmental information: These
HFO–1336mzz(Z)/HFO–1234ze(E)/
HFC–152a/CO2 foam blowing agent
blends have an ODP of 0. The
components, HFO–1336mzz(Z), HFO–
1234ze(E), HFC–152a, and CO2 have
GWPs of 2,26 1,27 124,28 and 1,
respectively. The GWPs of the blowing
agent blends using these components
range from 1 to 94. These reflect the
composition ranges that result in the
lowest GWP of 1 to the highest GWP of
94 given the GWP and range of
percentages for each component. The
components of the HFO–1336mzz(Z)/
HFO–1234ze(E)/HFC–152a/CO2 blends
are excluded from EPA’s regulatory
definition of VOC under CAA
regulations (see 40 CFR 51.100(s))
addressing the development of SIPs to
attain and maintain the NAAQS.
Flammability information: The
component HFC–152a is flammable at
standard temperature and pressure as
defined by standard test method ASTM
E681. HFO–1336mzz(Z) and HFO–
1234ze(E) are not flammable at standard
temperature and pressure using the
same method. However, at higher
temperatures, such as the temperatures
typical for extruding XPS, HFO–
1234ze(E) may also be flammable,
particularly at higher humidity levels.29
HFO–1336mzz(Z)/HFO–1234ze(E)/
HFC–152a/CO2 blends anticipated to be
used in manufacturing polystyrene:
extruded boardstock and billet are
flammable at the temperatures typical
for extruding XPS.
Toxicity and exposure data: Potential
health effects of exposure to this
substitute include skin or eye irritation
or frostbite. At sufficiently high
concentrations, the substitute may cause
irregular heartbeat. The substitute could
cause asphyxiation if air is displaced by
vapors in a confined space. These
potential health effects are common to
many foam blowing agents. Exposure
may be possible during the blowing of
the foam if the foam manufacturer does
not take standard precautions such as
the use of personal protective
equipment. EPA anticipates that these
HFO–1336mzz(Z)/HFO–1234ze(E)/
HFC–152a/CO2 blends will be used
consistent with the recommendations
specified in the SDS.
The AIHA has established a WEEL of
1,000 ppm for HFC–152a as an 8-hr
TWA. The WEEL committee of the
OARS has established a WEEL of 500
ppm 30 for HFO–1336mzz(Z). OSHA has
established a PEL of 5,000 ppm on an
8-hr TWA for CO2. The manufacturer of
HFO–1234ze(E) recommends an OEL of
800 ppm 31 (8-hr TWA) for this
chemical. EPA anticipates that users
will be able to meet the AIHA and
OARS WEELs, OSHA PEL, and
manufacturer’s OEL and will follow
requirements and recommendations in
the manufacturer’s SDSs and other
safety precautions common to the foam
blowing industry, thereby addressing
potential health risks.
Comparison to other foam blowing
agents in this end-use: These HFO–
1336mzz(Z)/HFO–1234ze(E)/HFC–152a/
CO2 blends have an ODP of 0,
comparable to other acceptable
substitutes in the polystyrene: extruded
boardstock and billet end-use, such as
HFC–152a, HFO–1234ze(E), methyl
formate, and CO2. These HFO–
1336mzz(Z)/HFO–1234ze(E)/HFC–152a/
CO2 blends’ GWPs from 1 to 94 are
lower than or comparable to those of
other acceptable substitutes in the same
99725
end-use for which we are finding it
acceptable. Examples include HFC–
152a, HFO–1234ze(E), light saturated
hydrocarbons C3–C6, and methyl
formate, with respective GWPs of 124,32
1,33 less than 4,34 and 11.35 Depending
on the specific composition, the blend
used may have a higher GWP than that
of some individual chemicals that are
acceptable substitutes in this end-use
that are more flammable (e.g., HFO–
1234ze(E)) or are less able to meet
standard specifications (e.g., ASTM
C578) than the blends because of
properties such as solvency in the
plastic resin (e.g., HFO–1336mzz(Z)) or
contributions to insulation value (e.g.,
CO2, water).
Flammability and toxicity risks are
comparable to or lower than
flammability and toxicity risks of other
available substitutes in the same enduse. Toxicity risks can be minimized by
use consistent with the AIHA’s and
OARS’s WEELs, OSHA’s PEL,
recommendations in the SDS, and other
safety precautions common in the foam
blowing industry.
Based on the considerations described
above, EPA finds blends of 0 to 90
percent HFO–1336mzz(Z), 0 to 90
percent HFO–1234ze(E), 0 to 75 percent
HFC–152a, and 0 to 90 percent CO2
acceptable in the polystyrene: extruded
boardstock and billet end-use because
they do not pose greater overall
environmental and human health risk
than other available substitutes in the
same end-use.
List of Subjects in 40 CFR Part 82
Environmental protection,
Administrative practice and procedure,
Air pollution control, Reporting and
recordkeeping requirements.
Paul M. Gunning,
Director, Office of Atmospheric Protection.
Appendix A: Summary of Decisions for
New Acceptable Substitutes
REFRIGERATION AND AIR CONDITIONING
Substitute
Decision
Further information 1
R–471A ................
Acceptable ............
This substitute is a blend of 78.7 percent hydrofluoroolefin (HFO)-1234ze(E), which is also
known as trans-1,3,3,3-tetrafluoroprop-1-ene; (Chemical Abstracts Service Registry
Number [CAS Reg. No.] 29118–24–9); 17.0 percent HFO–1336mzz(E), also known as
trans-1,1,1,4,4,4-hexafluoro-2-butene (CAS Reg. No. 66711–86–2); and 4.3 percent
HFC–227ea, which is also known as 1,1,1,2,3,3,3-heptafluoropropane (CAS Reg. No.
431–89–0).
R–471A has a global warming potential (GWP) of 144 and an ozone depletion potential
(ODP) of 0. The blend is not flammable as it has an American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) flammability classification of ‘‘1’’.
End-use
lotter on DSK11XQN23PROD with RULES1
Cold storage warehouses
(retrofit equipment only).
26 WMO,
2022.
2022.
28 Annex F to the Montreal Protocol.
29 Bellair and Hood, 2019. Comprehensive
evaluation of the flammability and ignitability of
HFO–1234ze, R.J. Bellair and L. Hood, Process
27 WMO,
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
Safety and Environmental Protection 132 (2019)
273–284. Available online at doi.org/10.1016/
j.psep.2019.09.033.
30 Cis-1,1,1,4,4,4-hexafluoro-2-butene (HFO–
1336mzz-Z) (2018). Toxicology and Industrial
Health. 2019;35(3):180–188. doi:10.1177/
0748233719825530.
PO 00000
Frm 00031
Fmt 4700
Sfmt 4700
31 ASHRAE,
2022.
F to the Montreal Protocol.
33 WMO, 2022.
34 IPCC, 2007.
35 WMO, 2022.
32 Annex
E:\FR\FM\11DER1.SGM
11DER1
99726
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
REFRIGERATION AND AIR CONDITIONING—Continued
lotter on DSK11XQN23PROD with RULES1
End-use
Substitute
Cold storage warehouses
(retrofit equipment only).
R–480A ................
Acceptable ............
Commercial ice machines
(retrofit equipment only).
R–480A ................
Acceptable ............
Industrial process refrigeration (retrofit equipment
only).
R–471A ................
Acceptable ............
Positive displacement chillers
(retrofit equipment only).
R–480A ................
Acceptable ............
Refrigerated transport (retrofit
equipment only).
R–480A ................
Acceptable ............
Residential and light commercial air conditioning and
heat pumps—self-contained units (new equipment only).
R–513A ................
Acceptable ............
Retail food refrigeration—Refrigerated food processing
and dispensing equipment
(retrofit equipment only).
R–471A ................
Acceptable ............
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
Further information 1
Decision
PO 00000
Frm 00032
ASHRAE has adopted an occupational exposure limit (OEL) for the blend of 710 ppm on
an eight-hour time-weighted average (8-hr TWA). For the components of R–471A, the
Workplace Environmental Exposure Limit (WEEL) Committee of the Occupational Alliance for Risk Science (OARS) has established a WEEL of 400 ppm on an 8-hr TWA for
HFO–1336mzz(E), the AIHA has established a WEEL of 1,000 ppm for HFC–227ea (8hr TWA), and ASHRAE has adopted an OEL of 800 ppm on an 8-hr TWA for HFO–
1234ze(E).
This substitute is a weighted blend of 5 percent CO2, 86 percent HFO–1234ze(E), which is
also known as trans-1,3,3,3-tetrafluoroprop-1-ene CAS Reg. No. 29118–24–9), and 9
percent HFC–227ea, which is also known as 1,1,1,2,3,3,3-heptafluoropropane (CAS
Reg. No. 431–89–0).
R–480A has a GWP of 291 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1.’’
ASHRAE has adopted an OEL for the blend of 900 ppm (8-hr TWA). For the components
of R–480A, the Occupational Safety and Health Administration (OSHA) has established
a permissible exposure limit (PEL) for CO2 of 5,000 ppm on an 8-hr TWA, AIHA has established a WEEL of 1,000 ppm for HFC–227ea (8-hr TWA), and ASHRAE has adopted
an OEL of 800 ppm on an 8-hr TWA for HFO–1234ze(E).
This substitute is a weighted blend of 5 percent CO2, 86 percent HFO–1234ze(E), which is
also known as trans-1,3,3,3-tetrafluoroprop-1-ene CAS Reg. No. 29118–24–9), and 9
percent HFC–227ea, which is also known as 1,1,1,2,3,3,3-heptafluoropropane (CAS
Reg. No. 431–89–0).
R–480A has a GWP of 291 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1.’’
ASHRAE has adopted an OEL for the blend of 900 ppm (8-hr TWA). For the components
of R–480A, OSHA has established a PEL for CO2 of 5,000 ppm on an 8-hr TWA, AIHA
has established a WEEL of 1,000 ppm for HFC–227ea (8-hr TWA), and ASHRAE has
adopted an OEL of 800 ppm on an 8-hr TWA for HFO–1234ze(E).
This substitute is a blend of 78.7 percent HFO–1234ze(E), which is also known as trans1,3,3,3-tetrafluoroprop-1-ene; (CAS Reg. No. 29118–24–9); 17.0 percent HFO–
1336mzz(E), also known as trans-1,1,1,4,4,4-hexafluoro-2-butene (CAS Reg. No.
66711–86–2); and 4.3 percent HFC–227ea, which is also known as 1,1,1,2,3,3,3heptafluoropropane (CAS Reg. No. 431–89–0).
R–471A has a GWP of 144 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1’’.
ASHRAE has adopted an OEL for the blend of 710 ppm (8-hr TWA). For the components
of R–471A, OARS has established a WEEL of 400 ppm on an 8-hr TWA for HFO–
1336mzz(E), AIHA has established a WEEL of 1,000 ppm for HFC–227ea (8-hr TWA),
and ASHRAE has adopted an OEL of 800 ppm on an 8-hr TWA for HFO–1234ze(E).
This substitute is a weighted blend of 5 percent CO2, 86 percent HFO–1234ze(E), which is
also known as trans-1,3,3,3-tetrafluoroprop-1-ene CAS Reg. No. 29118–24–9), and 9
percent HFC–227ea, which is also known as 1,1,1,2,3,3,3-heptafluoropropane (CAS
Reg. No. 431–89–0).
R–480A has a GWP of 291 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1.’’ ASHRAE has adopted an OEL for the blend
of 900 ppm (8-hr TWA). For the components of R–480A, the Occupational Safety and
Health Administration (OSHA) has established a permissible exposure limit (PEL) for
CO2 of 5,000 ppm on an 8-hr TWA, AIHA has established a WEEL of 1,000 ppm for
HFC–227ea (8-hr TWA), and ASHRAE has adopted an OEL of 800 ppm on an 8-hr
TWA for HFO–1234ze(E).
This substitute is a weighted blend of 5 percent CO2, 86 percent HFO–1234ze(E), which is
also known as trans-1,3,3,3-tetrafluoroprop-1-ene CAS Reg. No. 29118–24–9), and 9
percent HFC–227ea, which is also known as 1,1,1,2,3,3,3-heptafluoropropane (CAS
Reg. No. 431–89–0).
R–480A has a GWP of 291 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1.’’ ASHRAE has adopted an OEL for the blend
of 900 ppm (8-hr TWA). For the components of R–480A, OSHA has established a PEL
for CO2 of 5,000 ppm on an 8-hr TWA, AIHA has established a WEEL of 1,000 ppm for
HFC–227ea (8-hr TWA), and ASHRAE has adopted an OEL of 800 ppm on an 8-hr
TWA for HFO–1234ze(E).
This HFC–134a/HFO–1234yf blend R–513A has an ODP of 0. Its components include
HFC–134a which has a GWP of 1,430 and HFO–1234yf which has a GWP of 1. If these
values are weighted by mass percentage, then the blend would have a GWP of 630. All
components of the blends are excluded from EPA’s regulatory definition of VOC under
CAA regulations (see 40 CFR 51.100(s)).
ASHRAE has assigned R–513A a flammability class of ‘‘1,’’ meaning it does not propagate
a flame under standard test conditions. ASHRAE has adopted an OEL for the blend R–
513A of 650 ppm (8-hr TWA). The AIHA has established WEELs of 1000 ppm for HFC–
134a and of 500 ppm for HFO–1234yf, both as an 8-hr TWA.
This substitute is a blend of 78.7 percent HFO–1234ze(E), which is also known as trans1,3,3,3-tetrafluoroprop-1-ene; (CAS Reg. No. 29118–24–9); 17.0 percent HFO–
1336mzz(E), also known as trans-1,1,1,4,4,4-hexafluoro-2-butene (CAS Reg. No.
66711–86–2); and 4.3 percent HFC–227ea, which is also known as 1,1,1,2,3,3,3heptafluoropropane (CAS Reg. No. 431–89–0).
R–471A has a GWP of 144 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1’’. ASHRAE has established an OEL for the
blend of 710 ppm on an eight-hour time-weighted average (8-hr TWA). For the components of R–471A, OARS has established a WEEL of 400 ppm on an 8-hr TWA for
HFO–1336mzz(E), AIHA has established a WEEL of 1,000 ppm for HFC–227ea (8-hr
TWA), and ASHRAE has adopted an OEL of 800 ppm on an 8-hr TWA for HFO–
1234ze(E).
Fmt 4700
Sfmt 4700
E:\FR\FM\11DER1.SGM
11DER1
Federal Register / Vol. 89, No. 238 / Wednesday, December 11, 2024 / Rules and Regulations
99727
REFRIGERATION AND AIR CONDITIONING—Continued
End-use
Substitute
Decision
Further information 1
Retail food refrigeration—Remote condensing units (retrofit equipment only).
R–471A ................
Acceptable ............
Retail food refrigeration—Supermarket systems (retrofit
equipment only).
R–471A ................
Acceptable ............
Water coolers (retrofit equipment only).
R–480A ................
Acceptable ............
This substitute is a blend of 78.7 percent HFO–1234ze(E), which is also known as trans1,3,3,3-tetrafluoroprop-1-ene; (CAS Reg. No. 29118–24–9); 17.0 percent HFO–
1336mzz(E), also known as trans-1,1,1,4,4,4-hexafluoro-2-butene (CAS Reg. No.
66711–86–2); and 4.3 percent HFC–227ea, which is also known as 1,1,1,2,3,3,3heptafluoropropane (CAS Reg. No. 431–89–0).
R–471A has a GWP of 144 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1’’. ASHRAE has established an OEL for the
blend of 710 ppm (8-hr TWA). For the components of R–471A, OARS has established a
WEEL of 400 ppm on an 8-hr TWA for HFO–1336mzz(E), AIHA has established a
WEEL of 1,000 ppm for HFC–227ea (8-hr TWA), and ASHRAE has adopted an OEL of
800 ppm on an 8-hr TWA for HFO–1234ze(E).
This substitute is a blend of 78.7 percent HFO–1234ze(E), which is also known as trans1,3,3,3-tetrafluoroprop-1-ene; (CAS Reg. No. 29118–24–9); 17.0 percent HFO–
1336mzz(E), also known as trans-1,1,1,4,4,4-hexafluoro-2-butene (CAS Reg. No.
66711–86–2); and 4.3 percent HFC–227ea, which is also known as 1,1,1,2,3,3,3heptafluoropropane (CAS Reg. No. 431–89–0).
R–471A has a GWP of 144 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1’’. ASHRAE has established an OEL for the
blend of 710 ppm (8-hr TWA). For the components of R–471A, OARS has established a
WEEL of 400 ppm on an 8-hr TWA for HFO–1336mzz(E), AIHA has established a
WEEL of 1,000 ppm for HFC–227ea (8-hr TWA), and ASHRAE has adopted an OEL of
800 ppm on an 8-hr TWA for HFO–1234ze(E).
This substitute is a weighted blend of 5 percent CO2, 86 percent HFO–1234ze(E), which is
also known as trans-1,3,3,3-tetrafluoroprop-1-ene CAS Reg. No. 29118–24–9), and 9
percent HFC–227ea, which is also known as 1,1,1,2,3,3,3-heptafluoropropane (CAS
Reg. No. 431–89–0).
R–480A has a GWP of 291 and an ODP of 0. The blend is not flammable as it has an
ASHRAE flammability classification of ‘‘1.’’ ASHRAE has adopted an OEL for the blend
of 900 ppm (8-hr TWA). For the components of R–480A, OSHA has established a PEL
for CO2 of 5,000 ppm on an 8-hr TWA, AIHA has established a WEEL of 1,000 ppm for
HFC–227ea (8-hr TWA), and ASHRAE has adopted an OEL of 800 ppm on an 8-hr
TWA for HFO–1234ze(E).
1 See
recommendations in the manufacturer’s SDS and guidance for all listed refrigerants.
FOAM BLOWING
End-use
Polystyrene: Extruded
boardstock and billet.
1 See
Decision
Further information 1
Acceptable ............
HFO–1234ze(E) is also known as trans-1,3,3,3-tetrafluoroprop-1-ene
(Chemical Abstracts Service Registry Number [CAS Reg. No.] 29118–
24–9). HFO–1336mzz(Z) is also known as (Z)-1,1,1,4,4,4-hexafluoro2-butene and cis-1,1,1,4,4,4-hexafluoro-2-butene (CAS Reg. No. 692–
49–9). HFC–152a is also known as 1,1-difluoroethane (CAS Reg. No.
75–37–6). CO2 has CAS Reg. No. 124–38–9.
These blends have 100-year GWPs from 1 to about 94, depending on
the specific composition. Blends of these compounds anticipated to
be used in manufacturing are flammable.
The AIHA has established a WEEL of 1,000 ppm for HFC–152a on an
eight-hour Time-Weighted Average (8-hr TWA). The OARS has established a WEEL of 500 ppm (8-hr TWA) for HFO–1336mzz(Z). The
manufacturer of HFO–1234ze(E) has established an OEL of 800 ppm
(8-hr TWA) and the American Society of Heating, Refrigerating and
Air-Conditioning Engineers has adopted an OEL of 800 ppm (8-hr
TWA) for this compound. The U.S. OSHA has established a PEL of
5,000 ppm on an 8-hr TWA for CO2.
Substitute
Extruded polystyrene (XPS) foam blowing
agent blends of 0 to 90 percent HFO–
1336mzz(Z), 0 to 90 percent HFO–
1234ze(E), 0 to 75 percent HFC–152a,
and 0 to 90 percent CO2.
recommendations in the manufacturer’s SDS and guidance for all listed foam blowing agents.
[FR Doc. 2024–28307 Filed 12–10–24; 8:45 am]
BILLING CODE 6560–50–P
ENVIRONMENTAL PROTECTION
AGENCY
40 CFR Parts 261, 262, and 266
[EPA–HQ–OLEM–2023–0081; FRL 8687–04–
OLEM]
lotter on DSK11XQN23PROD with RULES1
RIN 2050–AH23
Hazardous Waste Generator
Improvements Rule, the Hazardous
Waste Pharmaceuticals Rule, and the
Definition of Solid Waste Rule;
Technical Corrections
Environmental Protection
Agency (EPA).
AGENCY:
VerDate Sep<11>2014
16:09 Dec 10, 2024
Jkt 265001
PO 00000
Frm 00033
Fmt 4700
Sfmt 4700
ACTION:
Final rule.
The Environmental Protection
Agency (EPA or the Agency) is
finalizing five amendments that were
withdrawn in its December 6, 2023,
partial withdrawal of direct final rule.
Due to receipt of adverse comments, the
EPA withdrew eight amendments from
the August 9, 2023, direct final rule that
included revisions to the 2016
Hazardous Waste Generator
Improvements Rule, the 2019 Hazardous
Waste Pharmaceuticals Rule and the
2018 Vacatur of the Definition of Solid
Waste Rule (88 FR 54086). The EPA is
SUMMARY:
E:\FR\FM\11DER1.SGM
11DER1
Agencies
[Federal Register Volume 89, Number 238 (Wednesday, December 11, 2024)]
[Rules and Regulations]
[Pages 99720-99727]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2024-28307]
[[Page 99720]]
=======================================================================
-----------------------------------------------------------------------
ENVIRONMENTAL PROTECTION AGENCY
40 CFR Part 82
[EPA-HQ-OAR-2003-0118; FRL-12145-01-OAR]
RIN 2060-AG12
Protection of Stratospheric Ozone: Determination 39 for the
Significant New Alternatives Policy Program
AGENCY: Environmental Protection Agency (EPA).
ACTION: Determination of acceptability.
-----------------------------------------------------------------------
SUMMARY: This determination of acceptability expands the list of
acceptable substitutes pursuant to the U.S. Environmental Protection
Agency's Significant New Alternatives Policy program. This action lists
four substitutes as acceptable additional substitutes for use in the
refrigeration and air conditioning and foam blowing sectors.
DATES: This determination is applicable on December 11, 2024.
ADDRESSES: EPA established a docket for this action under Docket ID No.
EPA-HQ-OAR-2003-0118 (continuation of Air Docket A-91-42). All
electronic documents in the docket are listed in the index at https://www.regulations.gov. Although listed in the index, some information is
not publicly available, e.g., confidential business information (CBI)
or other information whose disclosure is restricted by statute.
Publicly available docket materials are available either electronically
at https://www.regulations.gov or in hard copy at the EPA Docket Center
(EPA/DC), (Docket Nos. A-91-42 and EPA-HQ-OAR-2003-0118), William J.
Clinton West, Room 3334, 1301 Constitution Avenue NW, Washington, DC
20460. The telephone number for the Public Reading Room is (202) 566-
1744, and the telephone number for the Air and Radiation Docket is
(202) 566-1742. The Docket Center's hours of operations are 8:30 a.m.-
4:30 p.m., Monday-Friday (except Federal Holidays). For further
information on the EPA Docket Center services and the current status,
please visit online at https://www.epa.gov/dockets.
FOR FURTHER INFORMATION CONTACT: Nathaniel Burola, Stratospheric
Protection Division, Office of Atmospheric Protection (Mail Code
6205A), U.S. Environmental Protection Agency, 1200 Pennsylvania Avenue
NW, 20460; telephone number: 202-564-2883; email address:
[email protected].
Table of Contents
I. Listing of New Acceptable Substitutes
A. Refrigeration and Air Conditioning
1. R-471A
2. R-480A
3. R-513A
B. Foam Blowing
1. Extruded Polystyrene (XPS) Blowing Agent Blends of 0 to 90
Percent HFO-1336mzz(Z), 0 to 90 Percent HFO-1234ze(E), 0 to 75
Percent HFC-152a, and 0 to 90 Percent CO2
Appendix A: Summary of Decisions for New Acceptable Substitutes
SUPPLEMENTARY INFORMATION:
I. Listing of New Acceptable Substitutes
This action is listing as acceptable additional substitutes for use
in the refrigeration and air conditioning and foam blowing sectors.
This action presents EPA's most recent decisions under the Significant
New Alternatives Policy (SNAP) program to list as acceptable several
substitutes in different end-uses. The new substitutes are:
R-471A in retail food refrigeration, industrial process
refrigeration, and cold storage warehouses (retrofit equipment only);
R-480A in cold storage warehouses, commercial ice
machines, positive displacement chillers, refrigerated transport, and
water coolers (retrofit equipment only);
R-513A in residential and light commercial air
conditioning and heat pumps--self-contained units (new equipment only);
XPS foam blowing agent blends of 0 to 90 percent
hydrofluoroolefin (HFO)-1336mzz(Z), 0 to 90 percent HFO-1234ze(E), 0 to
75 percent hydrofluorocarbon (HFC)-152a, and 0 to 90 percent carbon
dioxide (CO2) in polystyrene: extruded boardstock and
billet.
Listing decisions in the end-uses in this document do not prejudge
EPA's listings of these substitutes for other end-uses. For additional
information on SNAP, visit the SNAP website at https://www.epa.gov/snap. The full lists of acceptable substitutes for ozone-depleting
substances (ODS) in the industrial sectors covered by the SNAP program
are available at https://www.epa.gov/snap/substitutes-sector. For more
information on the Agency's process for administering the SNAP program
or criteria for evaluation of substitutes, refer to the initial SNAP
rulemaking (59 FR 13044; March 18, 1994). The regulations are codified
at 40 CFR part 82, subpart G. SNAP decisions and the appropriate
Federal Register citations are available at: https://www.epa.gov/snap/snap-regulations. Under the SNAP program, EPA may list a substitute as
acceptable for specified end-uses where the Agency has reviewed the
substitute and found no reason to restrict or prohibit its use.
Substitutes listed as unacceptable; acceptable, subject to narrowed use
limits; or acceptable, subject to use conditions are also listed in the
appendices to 40 CFR part 82, subpart G.
This document discusses each substitute listing in detail and
summarizes the results of EPA's assessment of the human health and
environmental risks posed by each substitute. EPA's evaluation applies
the criteria in 40 CFR 82.180(a)(7), including atmospheric effects and
related health and environmental effects, ecosystem risks, occupational
risks, consumer risks, flammability, and cost and availability of the
substitute. EPA evaluates these criteria in risk screens, or technical
documents that evaluate risks to human health and the environment from
substitutes in specific end-uses, including comparisons to other
available substitutes and evaluations against relevant thresholds of
risk starting with protective assumptions. The risk screens cited in
this document include evaluation of atmospheric effects, toxicity data,
exposure assessments, flammability, and other environmental impacts
such as ecotoxicity and local air quality impacts. You can find more
information on the criteria used in the evaluation of substitutes in
the SNAP program at https://www.epa.gov/snap/snap-regulations.
In this document, EPA determined the global warming potential (GWP)
for a chemical or blend using the 100-year GWP values from the
Intergovernmental Panel on Climate Change's (IPCC) Fourth Assessment
Report (AR4) \1\ for substances or components of blends if included.\2\
Note that Annex F to the Montreal Protocol on Substances that Deplete
the Ozone Layer lists GWPs for HFCs that are numerically equivalent to
[[Page 99721]]
the AR4 values.\3\ These HFC 100-year GWP values are also numerically
equivalent to the exchange values listed in the American Innovation and
Manufacturing Act of 2020 (hereafter referred to as ``the AIM Act'').
If no GWP is provided in AR4 for a substance, the SNAP program is using
the 100-year GWP listed in World Meteorological Organization (WMO),
2022.\4\ To calculate the GWP of blends of chemicals, such as the
listed refrigerant blends, this document weights the GWP of each
component of the blend by its mass percentage. This method of
calculating GWPs is consistent with the method used to calculate GWPs
in the October 2023 Technology Transitions Rule as codified at 40 CFR
84.64.
---------------------------------------------------------------------------
\1\ IPCC, 2007: Climate Change 2007: The Physical Science Basis.
Contribution of Working Group I to the Fourth Assessment Report of
the Intergovernmental Panel on Climate Change [Solomon, S., Qin, D.,
Manning, M., Chen, Z., Marquis, M., Averyt, K.B., Tignor M., and
Miller, H.L. (eds.)]. Cambridge University Press, Cambridge, United
Kingdom and New York, NY, USA. Available at: https://www.ipcc.ch/publications_and_data/ar4/wg1/en/contents.html.
\2\ The IPCC, 2007 100-year GWP values are consistent with the
exchange values for the regulated HFCs listed in subsection (c) of
the AIM Act and with the GWPs in Annex F of the Montreal Protocol.
\3\ Annex F of the Montreal Protocol is available at: https://ozone.unep.org/treaties/montreal-protocol/articles/annex-f-controlled-substances.
\4\ WMO, Scientific Assessment of Ozone Depletion: 2022, GAW
Report No. 278, 509 pp.; WMO: Geneva, 2022. Available at: https://ozone.unep.org/system/files/documents/Scientific-Assessment-of-Ozone-Depletion-2022.pdf. (WMO, 2022).
---------------------------------------------------------------------------
Under section 612 of the Clean Air Act (CAA), the SNAP program
reviews substitutes using a comparative risk framework in different
industrial sectors. In making listing decisions, EPA considers overall
risk to human health and the environment. As a general matter, the
substitutes being added through this action to the acceptable lists
have a similar or lower risk than other substitutes already listed as
acceptable in those end-uses. However, certain substitutes may have a
higher risk than certain other substitutes already listed as acceptable
or acceptable subject to restrictions. In such cases, those already-
listed alternatives have other factors that limit their use in some
situations within a particular end-use.
Appendix A contains tables summarizing each listing decision in
this action. The statements in the ``Further Information'' column in
the tables provide additional information, but these are not legally
binding under section 612 of the CAA. Although users are not required
to follow recommendations in the ``Further Information'' column of the
table under section 612 of the CAA, some of these statements may refer
to obligations that are enforceable or binding under federal or state
programs other than the SNAP program. The identification of other
enforceable or binding requirements should not be construed as a
comprehensive list of such obligations. In many instances, the
information simply refers to standard operating practices in existing
industry standards and/or building codes. When using these substitutes
in the identified end-use, EPA strongly encourages you to apply the
information in the ``Further Information'' column. Many of these
recommendations, if adopted, would not require significant changes to
existing operating practices.
It should be noted that a substitute listed as acceptable under the
SNAP program may also be subject to requirements or limitations under
other statutory or regulatory provisions. For example, there are
relevant regulations under subsection (i) of the AIM Act that restrict
the use of certain HFCs in a variety of sectors and subsectors. See 88
FR 73098 (October 24, 2023). Consequently, if a substitute listed as
acceptable under the SNAP program is also subject to limitations on its
use under other regulations, it may not be permitted for use in
accordance with those other regulations. Those intending to use a
substitute listed as acceptable under the SNAP program may need to
consider restrictions under subsection (i) of the AIM Act, as well as
other relevant authorities, and must also be followed.\5\
---------------------------------------------------------------------------
\5\ For example, there may be restrictions or prohibitions in
regulations issued under section 610 of the CAA at 40 CFR part 82
subpart C for nonessential products containing ODS, under the Toxic
Substances Control Act, under the Occupation Safety and Health Act,
and under state or local laws and regulations that warrant
consideration.
---------------------------------------------------------------------------
You can find submissions to EPA for the substitutes listed in this
document, as well as other materials supporting the decisions in this
action, in the docket (EPA-HQ-OAR-2003-0118) at https://www.regulations.gov.
A. Refrigeration and Air Conditioning
1. R-471A
EPA's decision: EPA finds R-471A acceptable as a substitute for use
in:
Cold storage warehouses (retrofit equipment only);
Industrial process refrigeration (retrofit equipment
only);
Retail food refrigeration--Refrigerated food processing
and dispensing equipment (retrofit equipment only);
Retail food refrigeration--Remote condensing units
(retrofit equipment only);
Retail food refrigeration--Supermarket systems (retrofit
equipment only).
R-471A, marketed under the trade name Solstice[supreg] N71, is a
weighted blend of 78.7 percent HFO-1234ze(E), also known as trans-
1,3,3,3-tetrafluoroprop-1-ene (Chemical Abstracts Service Registry
Number [CAS Reg. No.] 29118-24-9); 17.0 percent HFO-1336mzz(E), also
known as trans-1,1,1,4,4,4-hexafluoro-2-butene (CAS Reg. No. 66711-86-
2); and 4.3 percent HFC-227ea, which is also known as 1,1,1,2,3,3,3-
heptafluoropropane (CAS Reg. No. 431-89-0).
You may find a copy of the applicant's submission, with CBI
redacted, providing the required health and environmental information
for this substitute in this end-use in the docket (EPA-HQ-OAR-2003-
0118) at https://www.regulations.gov under the name, ``Supporting
Materials for Notice 39 Listing of R-471A in Refrigeration and Air
Conditioning. SNAP Submission Received September 15, 2023.'' EPA
performed assessments to examine the health and environmental risks of
this substitute, and the results are summarized below. These
assessments are available in the docket EPA-HQ-OAR-2003-0118:
``Risk Screen on Substitutes in Retail Food Refrigeration
(Retrofit Equipment) Substitute: R-471A (Solstice[supreg] N71).''
``Risk Screen on Substitutes in Industrial Process
Refrigeration and Cold Storage Warehouses (Retrofit Equipment)
Substitute: R-471A (Solstice[supreg] N71).''
Environmental information: R-471A has an ozone depletion potential
(ODP) of 0. Its components, HFO-1234ze(E), HFO-1336mzz(E), and HFC-
227ea, have GWPs of 1,\6\ 26,\7\ and 3,220,\8\ respectively. When these
values are weighted by mass percentage of the blend, R-471A has a GWP
of about 144. The components of R-471A are excluded from the EPA's
regulatory definition of volatile organic compounds (VOC) under CAA
regulations (see 40 CFR 51.100(s)) addressing the development of state
implementation plans (SIPs) to attain and maintain the National Ambient
Air Quality Standards (NAAQS). Knowingly venting or otherwise knowingly
releasing this refrigerant blend is limited by the venting prohibition
under section 608(c)(2) of the CAA, codified in EPA regulations at 40
CFR 82.154(a).
---------------------------------------------------------------------------
\6\ WMO, 2022.
\7\ WMO, 2022.
\8\ Annex F to the Montreal Protocol.
---------------------------------------------------------------------------
Flammability information: The component HFO-1234ze(E) has lower
flammability as defined using the standard test method American Society
of Testing and Materials (ASTM) E681.\9\ The other two components of R-
471A are not flammable using the same
[[Page 99722]]
method. R-471A is not flammable as formulated, in the worst-case
formulation for flammability (WCF) and the worst-case of fractionation
for flammability (WCFF). The American Society of Heating,
Refrigerating, and Air-Conditioning Engineers (ASHRAE) has assigned R-
471A a flammability class of ``1,'' meaning it does not propagate a
flame under standard test conditions.\10\
---------------------------------------------------------------------------
\9\ ASTM, E681. Standard Test Method for Concentration Limits of
Flammability of Chemicals (Vapors and Gases).
\10\ ASHRAE Standard 34-2022: Designation and Safety
Classification of Refrigerants. (ASHRAE, 2022).
---------------------------------------------------------------------------
Toxicity and exposure data: Potential health effects of exposure to
this substitute include drowsiness or dizziness. The substitute may
also irritate the skin or eyes or cause frostbite in the case of rapid
evaporation of the liquid. The substitute could cause asphyxiation if
air is displaced by vapors in a confined space. Excessive exposure may
cause central nervous system effects including drowsiness and
dizziness. Excessive exposure may also cause cardiac arrhythmia. These
potential health effects are common to many refrigerants.
ASHRAE has adopted an occupational exposure limit (OEL) for the
blend of 710 ppm 11 12 on an eight-hour time-weighted
average (8-hr TWA) for HFO-1336mzz(E), the American Industrial Hygiene
Association (AIHA) has established a WEEL of 1,000 ppm (8-hr TWA) for
HFC-227ea, and ASHRAE has adopted an OEL of 800 ppm (8-hr TWA) for HFO-
1234ze(E).\13\ EPA anticipates that users will be able to meet these
workplace guidance limits and address potential health risks by
following recommendations in the manufacturer's safety data sheet
(SDS), ASHRAE Standard 15,\14\ other industry standards, and other
safety precautions common to the refrigeration and air conditioning
industry.
---------------------------------------------------------------------------
\11\ ASHRAE, 2022.
\12\ Trans-1,1,1,4,4,4-hexafluoro-2-butene (HFO-1336mzz-E)
(2018). Toxicology and Industrial Health. 2019; 35(3):204-210.
doi:10.1177/0748233719825529.
\13\ ASHRAE, 2022.
\14\ ASHRAE 15. Safety Standard for Refrigeration Systems.
---------------------------------------------------------------------------
Comparison to other substitutes in these end-uses: R-471A has an
ODP of 0, comparable to or less than other listed substitutes in
retrofits for these end-uses with ODPs ranging from 0 to less than
0.0004.
As a retrofit for supermarket systems, remote condensing units, and
refrigerated food processing and dispensing equipment, R-471A with a
GWP of 144 is lower than that of all other acceptable substitutes such
as R-450A which has a GWP of 601; R-513A with a GWP of 630; R-448A with
a GWP of 1,386; R-449A with a GWP of 1,396; R-449B with a GWP of 1,412;
R-407C with a GWP of 1,770; R-407F with a GWP of 1,825; and R-407A with
a GWP of 2,107.
For retrofits in industrial process refrigeration, R-471A's GWP of
144 is lower than that of other acceptable substitutes such as HFC-134a
which has a GWP of 1,430; R-407C with a GWP of 1,770; and R-407F with a
GWP of 1,825. Other alternatives in this sector have a lower GWP than
R-471A such as CO2 with a GWP of 1 and R-290 (propane) with
a GWP of 3. There may be situations in which lower-GWP options may not
be feasible for certain retrofitted industrial process refrigeration
equipment. For example, CO2, which has a GWP of 1 is a high-
pressure refrigerant and cannot be used as a retrofit for low-pressure
refrigerant systems. R-471A is a low-pressure refrigerant, making it
more technically feasible to retrofit systems that use similar low-
pressure refrigerants. R-290 is an A3, highly flammable refrigerant and
may not be feasible for certain retrofitted industrial process
refrigeration equipment where flammability is a concern.
Further, refrigerants offer cooling within a specific temperature
range. Adding R-471A to the list of available substitutes in industrial
process refrigeration systems may offer a refrigerant that achieves a
specific cooling temperature that other retrofit alternatives with
lower GWPs cannot achieve.\15\ For retrofits of cold storage
warehouses, R-471A's GWP of 144 is lower than that of all other
acceptable substitutes such as R-450A with a GWP of 601; R-513A with a
GWP of 630; HFC-134a with a GWP of 1,430; R-407C with a GWP of 1,770;
and R-407F with a GWP of 1,825.
---------------------------------------------------------------------------
\15\ The October 2023 Technology Transitions Rule does not
restrict the use of HFCs (i.e., establish GWP limits) in retrofit
applications (See 88 FR 73127).
---------------------------------------------------------------------------
Flammability and toxicity risks are comparable to or lower than
flammability and toxicity risks of other available substitutes in the
same retrofit end-uses. Toxicity risks can be minimized by use
consistent with the AIHA and OARS WEELs, ASHRAE OELs and ASHRAE 15,
other industry standards, recommendations in the manufacturer's SDS,
and other safety precautions common in the refrigeration and air
conditioning industry.
Based on the considerations described above, EPA finds R-471A
acceptable as a retrofit refrigerant for the following end-uses: cold
storage warehouses, industrial process refrigeration, and retail food
refrigeration (including supermarket systems, remote condensing units,
and refrigerated food processing and dispensing equipment), because it
does not pose greater overall environmental and human health risk than
other available substitutes in the same end-uses.
2. R-480A
EPA's decision: EPA finds R-480A acceptable as a substitute for use
in:
Cold storage warehouses (retrofit equipment only);
Commercial ice machines (retrofit equipment only);
Positive displacement chillers (retrofit equipment only);
Refrigerated transport (retrofit equipment only);
Water coolers (retrofit equipment only).
R-480A, marketed under the trade name RS-20, is a weighted blend of
5 percent CO2 (CAS Reg. No. 124-38-9), 86 percent HFO-
1234ze(E), also known as trans-1,3,3,3-tetrafluoroprop-1-ene (CAS Reg.
No. 29118-24-9), and 9 percent HFC-227ea, also known as 1,1,1,2,3,3,3-
heptafluoropropane (CAS Reg. No. 431-89-0).
You may find a copy of the applicant's submission, with CBI
redacted, providing the required health and environmental information
for this substitute in this end-use in the docket (EPA-HQ-OAR-2003-
0118) at https://www.regulations.gov under the name, ``Supporting
Materials for Notice 39 Listing of R-480A in Refrigeration and Air
Conditioning. SNAP Submission Received May 16, 2024.'' EPA performed
assessments to examine the health and environmental risks of this
substitute, and the results are summarized below. These assessments are
available in the docket EPA-HQ-OAR-2003-0118:
``Risk Screen on Substitutes in Cold Storage Warehouses
(Retrofit Equipment). Substitute: R-480A (RS-20).''
``Risk Screen on Substitutes in Commercial Ice Machines
(Retrofit Equipment). Substitute: R-480A (RS-20).''
``Risk Screen on Substitutes in Chillers (Retrofit
Equipment). Substitute: R-480A (RS-20).''
``Risk Screen on Substitutes in Refrigerated Transport
(Retrofit Equipment). Substitute: R-480A (RS-20).''
``Risk Screen on Substitutes in Water Coolers (Retrofit
Equipment). Substitute: R-480A (RS-20).''
Environmental information: R-480A has an ODP of 0. This blend
consists of
[[Page 99723]]
CO2 with a GWP of 1,\16\ HFO-1234ze(E) with a GWP of 1,\17\
and HFC-227ea with a GWP of 3,220.\18\ Weighting these values by mass
percentage results in a GWP of 291 for R-480A. The components of R-480A
are excluded from EPA's regulatory definition of VOC under CAA
regulations (see 40 CFR 51.100(s)) addressing the development of SIPs
to attain and maintain the NAAQS. Knowingly venting or otherwise
knowingly releasing this refrigerant blend is limited by the venting
prohibition under CAA section 608(c)(2), codified at 40 CFR 82.154(a).
---------------------------------------------------------------------------
\16\ IPCC, 2007.
\17\ WMO, 2022.
\18\ Annex F to the Montreal Protocol.
---------------------------------------------------------------------------
Flammability information: The component HFO-1234ze(E) has lower
flammability as defined using the standard test method ASTM E681, while
the other two components of R-480A are not flammable using the same
method. R-480A is not flammable as formulated, in the WCF and the WCFF.
ASHRAE has assigned R-480A a flammability class of ``1,'' meaning it
does not propagate a flame under standard test conditions.
Toxicity and exposure data: The substitute may be hazardous if
inhalation, skin contact, or eye contact with the substitute occurs at
sufficiently high levels. The substitute could cause symptoms of
asphyxiation if air is displaced by vapors in a confined space. These
potential health effects are common to many refrigerants.
ASHRAE has adopted an OEL for the blend of 900 ppm (8-hr TWA).\19\
For the components of R-480A, the U.S. Occupational Safety and Health
Administration (OSHA) has established a permissible exposure limit
(PEL) of 5,000 ppm (8-hr TWA) for CO2, AIHA has established
a WEEL of 1,000 ppm for HFC-227ea, and ASHRAE has adopted an OEL of 800
ppm (8-hr TWA) for HFO-1234ze(E).\20\ EPA anticipates that users will
be able to meet these workplace guidance limits and address potential
health risks by following recommendations in the manufacturer's SDS,
ASHRAE Standard 15, other industry standards, and other safety
precautions common to the refrigeration and air conditioning industry.
---------------------------------------------------------------------------
\19\ ASHRAE, 2022, Addendum h.
\20\ ASHRAE, 2022.
---------------------------------------------------------------------------
Comparison to other substitutes in these end-uses: R-480A has an
ODP of 0, comparable to or less than other listed substitutes in these
end-uses with ODPs ranging from 0 to less than 0.0004.
For cold storage warehouses, R-480A with a GWP of 291 is lower than
all other acceptable substitutes for retrofit equipment in this end-
use, such as a number of HFC blends, including R-450A and R-513A, with
GWPs of 601 and 630, respectively.
For commercial ice machines, R-480A's GWP of 291 is lower than all
other acceptable substitutes for retrofit equipment in this end-use,
such as a number of HFC blends, including R-450A and R-513A, with GWPs
of 601 and 630, respectively.
For positive displacement chillers, R-480A's GWP of 291 is lower
than that of certain other acceptable substitutes for retrofit
equipment in this end-use, such as a number of HFC blends, including R-
450A and R-513A, with GWPs of 601 and 630, respectively. The GWP of R-
480A is higher than the GWPs of two other acceptable substitutes for
retrofit equipment in this end-use, namely R-1224yd(Z) and R-514A, with
GWPs of 1 \21\ and 2,\22\ respectively. EPA is listing this substitute
as acceptable because available lower-GWP options are not feasible to
use in certain applications. For example, equipment retrofitted with R-
480A can operate within a specific temperature range and pressure range
that other retrofitted chillers using lower-GWP options such as R-
1224yd(Z) and R-514A cannot achieve. For refrigerated transport, R-
480A's GWP of 291 is lower than that of all other acceptable
substitutes for retrofit equipment in this end-use, such as R-450A, R-
513A, and HFC-134a, with GWPs of 601, 630, and 1,430, respectively.
---------------------------------------------------------------------------
\21\ WMO, 2022.
\22\ This value is calculated by weighting the GWPs of HFO-
1336mzz(Z) (2) and 1,2-dichloroethene(Z) (1) from WMO, 2022 by the
mass percentages of the blend components of 74.7 percent and 25.3
percent, respectively.
---------------------------------------------------------------------------
For water coolers, R-480A's GWP of 291 is lower than that of all
other acceptable substitutes for retrofit equipment in this end-use,
such as R-450A, R-513A, R-426A, and R-411A, with GWPs of 601, 630,
1,510, and 1,600, respectively.
Flammability and toxicity risks are comparable to or lower than
flammability and toxicity risks of other available substitutes in the
same retrofit end-uses. Toxicity risks can be minimized by use
consistent with the OSHA PEL, AIHA WEEL, ASHRAE OELs, ASHRAE 15 and
other industry standards, recommendations in the manufacturer's SDS,
and other safety precautions common in the refrigeration and air
conditioning industry.
Based on the considerations described above, EPA finds R-480A
acceptable in retrofit equipment in the following end-uses: cold
storage warehouses, commercial ice machines, positive displacement
chillers, refrigerated transport, and water coolers, because it does
not pose greater overall environmental and human health risk than other
available substitutes in the same end-uses.
3. R-513A
EPA's decision: EPA finds R-513A acceptable as a substitute for use
in:
Residential and light commercial air conditioning and heat
pumps--self-contained units (new equipment only).
R-513A, marketed under the trade name Opteon[supreg] XP-10, is a
weighted blend of 44 percent HFC-134a and 56 percent HFO-1234yf by
weight. HFC-134a is an HFC and is also known as 1,1,1,2-
tetrafluoroethane (CAS Reg. No. 811-97-2). HFO-1234yf is an HFO and is
also known as 2,3,3,3 tetrafluoroprop-1-ene (CAS Reg. No.754-12-1).
You may find a copy of the applicant's submission, with CBI
redacted, providing the required health and environmental information
for this substitute in this end-use category in Docket EPA-HQ-OAR-2003-
0118 at www.regulations.gov under the name, ``SNAP Information Notice
for R-513A as a Refrigerant. SNAP Submission Received January 9,
2024.'' EPA has performed an assessment to examine the health and
environmental risks of this substitute and the results are summarized
below. This assessment is available in Docket EPA-HQ-OAR-2003-0118:
``Risk Screen on Substitutes for Use in Residential and
Light Commercial Air Conditioning and Heat Pumps--Self-Contained Units
(New Equipment) Substitute: R-513A (Opteon[supreg] XP-10).''
Environmental information: R-513A is a blend of HFC-134a and HFO-
1234yf with an ODP of 0. HFC-134a has a GWP of 1,430 \23\ and HFO-
1234yf has a GWP of 1.\24\ The GWP of R-513A is 630 when the two
components are weighted by mass percentage of their GWPs. All
components of the blends are excluded from the EPA's regulatory
definition of VOC under CAA regulations (see 40 CFR 51.100(s))
addressing the development of SIPs to attain and maintain the NAAQS.
Knowingly venting or otherwise knowingly releasing this refrigerant
blend is limited by the venting prohibition under section 608(c)(2) of
the CAA, codified in EPA's regulations at 40 CFR 82.154(a).
---------------------------------------------------------------------------
\23\ Annex F to the Montreal Protocol.
\24\ WMO, 2022.
---------------------------------------------------------------------------
Flammability information: The component HFO-1234yf has lower
flammability as defined using the
[[Page 99724]]
standard test method ASTM E681. HFC-134a is not flammable using the
same method. R-513A is not flammable as formulated in the WCF and the
WCFF. ASHRAE has assigned R-513A a flammability class of ``1,'' meaning
it does not propagate a flame under standard test conditions.
Toxicity and exposure data: Potential health effects of exposure to
this substitute include skin and eye irritation and frostbite upon
contact. The substitute could cause asphyxiation if air is displaced by
vapors in a confined space. These potential health effects are common
to many refrigerants. EPA anticipates that R-513A will be used
consistent with the recommendations specified in the SDS. ASHRAE has
adopted an OEL for the blend R-513A of 650 ppm as an 8-hr TWA. The AIHA
has established WEELs of 1000 ppm for HFC-134a and of 500 ppm for HFO-
1234yf, both as an 8-hr TWA. EPA anticipates that users will be able to
meet these workplace guidance limits and will address potential health
risks by following requirements and recommendations in the
manufacturer's SDSs, ASHRAE Standard 15, other industry standards, and
other safety precautions common to the refrigeration and air
conditioning industry.
Comparison to other refrigerants in this end-use category: R-513A
has an ODP of 0, which is comparable to other acceptable substitutes in
the residential and light commercial air conditioning and heat pumps--
self-contained units end-use category with ODPs ranging from 0 to less
than 0.0004. R-513A which has a GWP of 630 is lower than or comparable
to those of some acceptable substitutes in the same end-use category
for which we are finding it acceptable, such as R-452B which has a GWP
of 700 and HFC-32 which has a GWP of 675. R-513A has a GWP of 630,
which is higher than those of other acceptable substitutes in this end-
use category such as R-290, which has a GWP of 3, R-454A, which has a
GWP of 240, R-454B, which has a GWP of 470, R-454C, which has a GWP of
150, and R-457A, which has a GWP of 140.
While other acceptable substitutes have lower GWPs, EPA is listing
R-513A as acceptable in this end-use category recognizing it likely
will be used only in certain self-contained units that use R-134a where
other available options are not technically feasible. Self-contained
units can include but are not limited to window units, packaged
terminal air conditioners, packaged terminal heat pumps, portable room
air conditioning units, and portable air conditioners used to cool
commercial aircraft interiors while on the ground.\25\ As a general
matter, the replacements for most of the equipment in the residential
and light commercial air conditioning and heat pumps end-use category
use refrigerants that mimic the thermodynamic qualities and high
pressure of R-410A which was the dominant refrigerant used for the
majority of equipment types in this end-use category. There are,
however, some specific applications where R-134a was used in self-
contained units because of its unique thermodynamic properties that
make it a better choice. For example, self-contained portable air
conditioners used to cool commercial aircraft while on the ground
currently use R-134a. This refrigerant is used because R-134a is
optimized for equipment that use screw compressors and need to be able
to operate at extremely high ambient temperatures with high humidity.
R-513A's thermodynamic properties closely mimic those of R-134a, making
it an important option for applications where R-134a is used. As noted
above, self-contained portable air conditioners used to cool the
aircraft interior while on the ground must function in a wide range of
ambient temperatures and humidities, making R-513A an important option
for this specific use. Other available refrigerant options with lower
GWPs do not have the correct thermodynamic properties to fit the
technical needs for this specific use. In addition, R-513A and R-134a
are both low pressure refrigerants. As a result, R-513A could replace
R-134a in equipment with minimal modifications but it is not expected
to replace R-410A due to the extensive re-engineering required.
---------------------------------------------------------------------------
\25\ These are all examples of equipment defined as ``factory
sealed appliances'' in the UL 60335-2-40 standard for electrical
heat pumps, air-conditioners, and dehumidifiers, in which all
refrigerating system parts have been sealed tight during the
manufacturing process. Other equipment that meets the UL definition
of factory sealed appliances are also self-contained units.
---------------------------------------------------------------------------
EPA expects that use of R-513A in residential and light commercial
air conditioning and heat pumps will be limited to a narrow set of
specific applications because it is likely to be used only in those few
applications where R-134a is currently used in self-contained units and
where other available options are not technically feasible. Therefore,
EPA is listing this refrigerant as acceptable for use in the
residential and light commercial air conditioning and heat pumps-self-
contained units end-use category.
Flammability and toxicity risks are comparable to or lower than
flammability and toxicity risks of other available substitutes in the
same end-use category. For example, R-513A is non-flammable and has
comparable or lower flammability risk compared to other acceptable
refrigerants in this end-use category, such as the lower flammability
refrigerants R-454B and R-454C. Toxicity risks can be minimized by use
consistent with the AIHA's WEELs, ASHRAE's OEL, ASHRAE 15 and other
industry standards, recommendations in the SDS, and other safety
precautions common in the refrigeration and air conditioning industry.
Based on the considerations described above, EPA finds R-513A
acceptable in new self-contained units in the residential and light
commercial air conditioning end-use because it provides a lower-GWP
alternative for this end-use category. R-513A does not pose greater
overall environmental and human health risk than other available
substitutes in the same end-use category.
B. Foam Blowing
1. Extruded Polystyrene (XPS) Blowing Agent Blends of 0 to 90 Percent
HFO-1336mzz(Z), 0 to 90 Percent HFO-1234ze(E), 0 to 75 Percent HFC-
152a, and 0 to 90 Percent CO2
EPA's decision: EPA finds blends of 0 to 90 percent HFO-1336mzz(Z),
0 to 90 percent HFO-1234ze(E), 0 to 75 percent HFC-152a, and 0 to 90
percent CO2 (``HFO-1336mzz(Z)/HFO-1234ze(E)/HFC-152a/
CO2 blends'') acceptable as a substitute for use as a foam
blowing agent in:
Polystyrene: extruded boardstock and billet.
HFO-1336mzz(Z) is an HFO and is also called (Z)-1,1,1,4,4,4-
hexafluorobut-2-ene or cis-1,1,1,4,4,4-hexafluorobut-2-ene (CAS Reg.
No. 692-49-9); it also goes by the trade names of FEA-1100 or
Formacel[supreg] 1100. HFO-1234ze(E) is an HFO and is also known as
trans-1,3,3,3-tetrafluoroprop-1-ene (CAS Reg. No. 29118-24-9). HFC-152a
is an HFC and is also called ethane, 1,1-difluoro (CAS Reg. No. 75-37-
6). CO2 has CAS Reg. No. 124-38-9.
You may find a copy of the applicant's submission, with CBI
redacted, providing the required health and environmental information
for this substitute in this end-use in the docket (EPA-HQ-OAR-2003-
0118) at https://www.regulations.gov under the name, ``SNAP Information
Notice for Extruded Polystyrene Blend of 0 to 90% HFO-1336mzz(Z), 0 to
90% HFO-1234ze(E), 0 to 75% HFC-152a, and 0 to 90% CO2 as a
Foam Blowing Agent SNAP Submission Received August 7, 2023.''
[[Page 99725]]
EPA has performed an assessment to examine the health and environmental
risks of this substitute. This assessment is available in the docket
EPA-HQ-OAR-2003-0118:
``Risk Screen on Substitutes for Use in Extruded
Polystyrene Boardstock and Billet Foam Substitute: HFO-1336mzz(Z)/HFO-
1234ze(E)/HFC-152a/CO2 Blends.''
Environmental information: These HFO-1336mzz(Z)/HFO-1234ze(E)/HFC-
152a/CO2 foam blowing agent blends have an ODP of 0. The
components, HFO-1336mzz(Z), HFO-1234ze(E), HFC-152a, and CO2
have GWPs of 2,\26\ 1,\27\ 124,\28\ and 1, respectively. The GWPs of
the blowing agent blends using these components range from 1 to 94.
These reflect the composition ranges that result in the lowest GWP of 1
to the highest GWP of 94 given the GWP and range of percentages for
each component. The components of the HFO-1336mzz(Z)/HFO-1234ze(E)/HFC-
152a/CO2 blends are excluded from EPA's regulatory
definition of VOC under CAA regulations (see 40 CFR 51.100(s))
addressing the development of SIPs to attain and maintain the NAAQS.
---------------------------------------------------------------------------
\26\ WMO, 2022.
\27\ WMO, 2022.
\28\ Annex F to the Montreal Protocol.
---------------------------------------------------------------------------
Flammability information: The component HFC-152a is flammable at
standard temperature and pressure as defined by standard test method
ASTM E681. HFO-1336mzz(Z) and HFO-1234ze(E) are not flammable at
standard temperature and pressure using the same method. However, at
higher temperatures, such as the temperatures typical for extruding
XPS, HFO-1234ze(E) may also be flammable, particularly at higher
humidity levels.\29\ HFO-1336mzz(Z)/HFO-1234ze(E)/HFC-152a/
CO2 blends anticipated to be used in manufacturing
polystyrene: extruded boardstock and billet are flammable at the
temperatures typical for extruding XPS.
---------------------------------------------------------------------------
\29\ Bellair and Hood, 2019. Comprehensive evaluation of the
flammability and ignitability of HFO-1234ze, R.J. Bellair and L.
Hood, Process Safety and Environmental Protection 132 (2019) 273-
284. Available online at doi.org/10.1016/j.psep.2019.09.033.
---------------------------------------------------------------------------
Toxicity and exposure data: Potential health effects of exposure to
this substitute include skin or eye irritation or frostbite. At
sufficiently high concentrations, the substitute may cause irregular
heartbeat. The substitute could cause asphyxiation if air is displaced
by vapors in a confined space. These potential health effects are
common to many foam blowing agents. Exposure may be possible during the
blowing of the foam if the foam manufacturer does not take standard
precautions such as the use of personal protective equipment. EPA
anticipates that these HFO-1336mzz(Z)/HFO-1234ze(E)/HFC-152a/
CO2 blends will be used consistent with the recommendations
specified in the SDS.
The AIHA has established a WEEL of 1,000 ppm for HFC-152a as an 8-
hr TWA. The WEEL committee of the OARS has established a WEEL of 500
ppm \30\ for HFO-1336mzz(Z). OSHA has established a PEL of 5,000 ppm on
an 8-hr TWA for CO2. The manufacturer of HFO-1234ze(E)
recommends an OEL of 800 ppm \31\ (8-hr TWA) for this chemical. EPA
anticipates that users will be able to meet the AIHA and OARS WEELs,
OSHA PEL, and manufacturer's OEL and will follow requirements and
recommendations in the manufacturer's SDSs and other safety precautions
common to the foam blowing industry, thereby addressing potential
health risks.
---------------------------------------------------------------------------
\30\ Cis-1,1,1,4,4,4-hexafluoro-2-butene (HFO-1336mzz-Z) (2018).
Toxicology and Industrial Health. 2019;35(3):180-188. doi:10.1177/
0748233719825530.
\31\ ASHRAE, 2022.
---------------------------------------------------------------------------
Comparison to other foam blowing agents in this end-use: These HFO-
1336mzz(Z)/HFO-1234ze(E)/HFC-152a/CO2 blends have an ODP of
0, comparable to other acceptable substitutes in the polystyrene:
extruded boardstock and billet end-use, such as HFC-152a, HFO-
1234ze(E), methyl formate, and CO2. These HFO-1336mzz(Z)/
HFO-1234ze(E)/HFC-152a/CO2 blends' GWPs from 1 to 94 are
lower than or comparable to those of other acceptable substitutes in
the same end-use for which we are finding it acceptable. Examples
include HFC-152a, HFO-1234ze(E), light saturated hydrocarbons C3-C6,
and methyl formate, with respective GWPs of 124,\32\ 1,\33\ less than
4,\34\ and 11.\35\ Depending on the specific composition, the blend
used may have a higher GWP than that of some individual chemicals that
are acceptable substitutes in this end-use that are more flammable
(e.g., HFO-1234ze(E)) or are less able to meet standard specifications
(e.g., ASTM C578) than the blends because of properties such as
solvency in the plastic resin (e.g., HFO-1336mzz(Z)) or contributions
to insulation value (e.g., CO2, water).
---------------------------------------------------------------------------
\32\ Annex F to the Montreal Protocol.
\33\ WMO, 2022.
\34\ IPCC, 2007.
\35\ WMO, 2022.
---------------------------------------------------------------------------
Flammability and toxicity risks are comparable to or lower than
flammability and toxicity risks of other available substitutes in the
same end-use. Toxicity risks can be minimized by use consistent with
the AIHA's and OARS's WEELs, OSHA's PEL, recommendations in the SDS,
and other safety precautions common in the foam blowing industry.
Based on the considerations described above, EPA finds blends of 0
to 90 percent HFO-1336mzz(Z), 0 to 90 percent HFO-1234ze(E), 0 to 75
percent HFC-152a, and 0 to 90 percent CO2 acceptable in the
polystyrene: extruded boardstock and billet end-use because they do not
pose greater overall environmental and human health risk than other
available substitutes in the same end-use.
List of Subjects in 40 CFR Part 82
Environmental protection, Administrative practice and procedure,
Air pollution control, Reporting and recordkeeping requirements.
Paul M. Gunning,
Director, Office of Atmospheric Protection.
Appendix A: Summary of Decisions for New Acceptable Substitutes
Refrigeration and Air Conditioning
----------------------------------------------------------------------------------------------------------------
End-use Substitute Decision Further information \1\
----------------------------------------------------------------------------------------------------------------
Cold storage warehouses R-471A................. Acceptable............. This substitute is a blend
(retrofit equipment only). of 78.7 percent
hydrofluoroolefin (HFO)-
1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene;
(Chemical Abstracts Service
Registry Number [CAS Reg.
No.] 29118-24-9); 17.0
percent HFO-1336mzz(E),
also known as trans-
1,1,1,4,4,4-hexafluoro-2-
butene (CAS Reg. No. 66711-
86-2); and 4.3 percent HFC-
227ea, which is also known
as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-471A has a global warming
potential (GWP) of 144 and
an ozone depletion
potential (ODP) of 0. The
blend is not flammable as
it has an American Society
of Heating, Refrigerating,
and Air-Conditioning
Engineers (ASHRAE)
flammability classification
of ``1''.
[[Page 99726]]
ASHRAE has adopted an
occupational exposure limit
(OEL) for the blend of 710
ppm on an eight-hour time-
weighted average (8-hr
TWA). For the components of
R-471A, the Workplace
Environmental Exposure
Limit (WEEL) Committee of
the Occupational Alliance
for Risk Science (OARS) has
established a WEEL of 400
ppm on an 8-hr TWA for HFO-
1336mzz(E), the AIHA has
established a WEEL of 1,000
ppm for HFC-227ea (8-hr
TWA), and ASHRAE has
adopted an OEL of 800 ppm
on an 8-hr TWA for HFO-
1234ze(E).
Cold storage warehouses R-480A................. Acceptable............. This substitute is a
(retrofit equipment only). weighted blend of 5 percent
CO2, 86 percent HFO-
1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene CAS
Reg. No. 29118-24-9), and 9
percent HFC-227ea, which is
also known as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-480A has a GWP of 291 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1.''
ASHRAE has adopted an OEL
for the blend of 900 ppm (8-
hr TWA). For the components
of R-480A, the Occupational
Safety and Health
Administration (OSHA) has
established a permissible
exposure limit (PEL) for
CO2 of 5,000 ppm on an 8-hr
TWA, AIHA has established a
WEEL of 1,000 ppm for HFC-
227ea (8-hr TWA), and
ASHRAE has adopted an OEL
of 800 ppm on an 8-hr TWA
for HFO-1234ze(E).
Commercial ice machines R-480A................. Acceptable............. This substitute is a
(retrofit equipment only). weighted blend of 5 percent
CO2, 86 percent HFO-
1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene CAS
Reg. No. 29118-24-9), and 9
percent HFC-227ea, which is
also known as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-480A has a GWP of 291 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1.''
ASHRAE has adopted an OEL
for the blend of 900 ppm (8-
hr TWA). For the components
of R-480A, OSHA has
established a PEL for CO2
of 5,000 ppm on an 8-hr
TWA, AIHA has established a
WEEL of 1,000 ppm for HFC-
227ea (8-hr TWA), and
ASHRAE has adopted an OEL
of 800 ppm on an 8-hr TWA
for HFO-1234ze(E).
Industrial process refrigeration R-471A................. Acceptable............. This substitute is a blend
(retrofit equipment only). of 78.7 percent HFO-
1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene; (CAS
Reg. No. 29118-24-9); 17.0
percent HFO-1336mzz(E),
also known as trans-
1,1,1,4,4,4-hexafluoro-2-
butene (CAS Reg. No. 66711-
86-2); and 4.3 percent HFC-
227ea, which is also known
as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-471A has a GWP of 144 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1''.
ASHRAE has adopted an OEL
for the blend of 710 ppm (8-
hr TWA). For the components
of R-471A, OARS has
established a WEEL of 400
ppm on an 8-hr TWA for HFO-
1336mzz(E), AIHA has
established a WEEL of 1,000
ppm for HFC-227ea (8-hr
TWA), and ASHRAE has
adopted an OEL of 800 ppm
on an 8-hr TWA for HFO-
1234ze(E).
Positive displacement chillers R-480A................. Acceptable............. This substitute is a
(retrofit equipment only). weighted blend of 5 percent
CO2, 86 percent HFO-
1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene CAS
Reg. No. 29118-24-9), and 9
percent HFC-227ea, which is
also known as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-480A has a GWP of 291 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1.''
ASHRAE has adopted an OEL
for the blend of 900 ppm (8-
hr TWA). For the components
of R-480A, the Occupational
Safety and Health
Administration (OSHA) has
established a permissible
exposure limit (PEL) for
CO2 of 5,000 ppm on an 8-hr
TWA, AIHA has established a
WEEL of 1,000 ppm for HFC-
227ea (8-hr TWA), and
ASHRAE has adopted an OEL
of 800 ppm on an 8-hr TWA
for HFO-1234ze(E).
Refrigerated transport (retrofit R-480A................. Acceptable............. This substitute is a
equipment only). weighted blend of 5 percent
CO2, 86 percent HFO-
1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene CAS
Reg. No. 29118-24-9), and 9
percent HFC-227ea, which is
also known as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-480A has a GWP of 291 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1.''
ASHRAE has adopted an OEL
for the blend of 900 ppm (8-
hr TWA). For the components
of R-480A, OSHA has
established a PEL for CO2
of 5,000 ppm on an 8-hr
TWA, AIHA has established a
WEEL of 1,000 ppm for HFC-
227ea (8-hr TWA), and
ASHRAE has adopted an OEL
of 800 ppm on an 8-hr TWA
for HFO-1234ze(E).
Residential and light commercial R-513A................. Acceptable............. This HFC-134a/HFO-1234yf
air conditioning and heat blend R-513A has an ODP of
pumps--self-contained units 0. Its components include
(new equipment only). HFC-134a which has a GWP of
1,430 and HFO-1234yf which
has a GWP of 1. If these
values are weighted by mass
percentage, then the blend
would have a GWP of 630.
All components of the
blends are excluded from
EPA's regulatory definition
of VOC under CAA
regulations (see 40 CFR
51.100(s)).
ASHRAE has assigned R-513A a
flammability class of
``1,'' meaning it does not
propagate a flame under
standard test conditions.
ASHRAE has adopted an OEL
for the blend R-513A of 650
ppm (8-hr TWA). The AIHA
has established WEELs of
1000 ppm for HFC-134a and
of 500 ppm for HFO-1234yf,
both as an 8-hr TWA.
Retail food refrigeration-- R-471A................. Acceptable............. This substitute is a blend
Refrigerated food processing of 78.7 percent HFO-
and dispensing equipment 1234ze(E), which is also
(retrofit equipment only). known as trans-1,3,3,3-
tetrafluoroprop-1-ene; (CAS
Reg. No. 29118-24-9); 17.0
percent HFO-1336mzz(E),
also known as trans-
1,1,1,4,4,4-hexafluoro-2-
butene (CAS Reg. No. 66711-
86-2); and 4.3 percent HFC-
227ea, which is also known
as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-471A has a GWP of 144 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1''.
ASHRAE has established an
OEL for the blend of 710
ppm on an eight-hour time-
weighted average (8-hr
TWA). For the components of
R-471A, OARS has
established a WEEL of 400
ppm on an 8-hr TWA for HFO-
1336mzz(E), AIHA has
established a WEEL of 1,000
ppm for HFC-227ea (8-hr
TWA), and ASHRAE has
adopted an OEL of 800 ppm
on an 8-hr TWA for HFO-
1234ze(E).
[[Page 99727]]
Retail food refrigeration-- R-471A................. Acceptable............. This substitute is a blend
Remote condensing units of 78.7 percent HFO-
(retrofit equipment only). 1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene; (CAS
Reg. No. 29118-24-9); 17.0
percent HFO-1336mzz(E),
also known as trans-
1,1,1,4,4,4-hexafluoro-2-
butene (CAS Reg. No. 66711-
86-2); and 4.3 percent HFC-
227ea, which is also known
as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-471A has a GWP of 144 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1''.
ASHRAE has established an
OEL for the blend of 710
ppm (8-hr TWA). For the
components of R-471A, OARS
has established a WEEL of
400 ppm on an 8-hr TWA for
HFO-1336mzz(E), AIHA has
established a WEEL of 1,000
ppm for HFC-227ea (8-hr
TWA), and ASHRAE has
adopted an OEL of 800 ppm
on an 8-hr TWA for HFO-
1234ze(E).
Retail food refrigeration-- R-471A................. Acceptable............. This substitute is a blend
Supermarket systems (retrofit of 78.7 percent HFO-
equipment only). 1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene; (CAS
Reg. No. 29118-24-9); 17.0
percent HFO-1336mzz(E),
also known as trans-
1,1,1,4,4,4-hexafluoro-2-
butene (CAS Reg. No. 66711-
86-2); and 4.3 percent HFC-
227ea, which is also known
as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-471A has a GWP of 144 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1''.
ASHRAE has established an
OEL for the blend of 710
ppm (8-hr TWA). For the
components of R-471A, OARS
has established a WEEL of
400 ppm on an 8-hr TWA for
HFO-1336mzz(E), AIHA has
established a WEEL of 1,000
ppm for HFC-227ea (8-hr
TWA), and ASHRAE has
adopted an OEL of 800 ppm
on an 8-hr TWA for HFO-
1234ze(E).
Water coolers (retrofit R-480A................. Acceptable............. This substitute is a
equipment only). weighted blend of 5 percent
CO2, 86 percent HFO-
1234ze(E), which is also
known as trans-1,3,3,3-
tetrafluoroprop-1-ene CAS
Reg. No. 29118-24-9), and 9
percent HFC-227ea, which is
also known as 1,1,1,2,3,3,3-
heptafluoropropane (CAS
Reg. No. 431-89-0).
R-480A has a GWP of 291 and
an ODP of 0. The blend is
not flammable as it has an
ASHRAE flammability
classification of ``1.''
ASHRAE has adopted an OEL
for the blend of 900 ppm (8-
hr TWA). For the components
of R-480A, OSHA has
established a PEL for CO2
of 5,000 ppm on an 8-hr
TWA, AIHA has established a
WEEL of 1,000 ppm for HFC-
227ea (8-hr TWA), and
ASHRAE has adopted an OEL
of 800 ppm on an 8-hr TWA
for HFO-1234ze(E).
----------------------------------------------------------------------------------------------------------------
\1\ See recommendations in the manufacturer's SDS and guidance for all listed refrigerants.
Foam Blowing
----------------------------------------------------------------------------------------------------------------
End-use Substitute Decision Further information \1\
----------------------------------------------------------------------------------------------------------------
Polystyrene: Extruded boardstock Extruded polystyrene Acceptable.............. HFO-1234ze(E) is also known
and billet. (XPS) foam blowing as trans-1,3,3,3-
agent blends of 0 tetrafluoroprop-1-ene
to 90 percent HFO- (Chemical Abstracts Service
1336mzz(Z), 0 to 90 Registry Number [CAS Reg.
percent HFO- No.] 29118-24-9). HFO-
1234ze(E), 0 to 75 1336mzz(Z) is also known as
percent HFC-152a, (Z)-1,1,1,4,4,4-hexafluoro-2-
and 0 to 90 percent butene and cis-1,1,1,4,4,4-
CO2. hexafluoro-2-butene (CAS
Reg. No. 692-49-9). HFC-152a
is also known as 1,1-
difluoroethane (CAS Reg. No.
75-37-6). CO2 has CAS Reg.
No. 124-38-9.
These blends have 100-year
GWPs from 1 to about 94,
depending on the specific
composition. Blends of these
compounds anticipated to be
used in manufacturing are
flammable.
The AIHA has established a
WEEL of 1,000 ppm for HFC-
152a on an eight-hour Time-
Weighted Average (8-hr TWA).
The OARS has established a
WEEL of 500 ppm (8-hr TWA)
for HFO-1336mzz(Z). The
manufacturer of HFO-
1234ze(E) has established an
OEL of 800 ppm (8-hr TWA)
and the American Society of
Heating, Refrigerating and
Air-Conditioning Engineers
has adopted an OEL of 800
ppm (8-hr TWA) for this
compound. The U.S. OSHA has
established a PEL of 5,000
ppm on an 8-hr TWA for CO2.
----------------------------------------------------------------------------------------------------------------
\1\ See recommendations in the manufacturer's SDS and guidance for all listed foam blowing agents.
[FR Doc. 2024-28307 Filed 12-10-24; 8:45 am]
BILLING CODE 6560-50-P