New Source Performance Standards Review for Volatile Organic Liquid Storage Vessels (Including Petroleum Liquid Storage Vessels), 83296-83336 [2024-22823]
Download as PDF
83296
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
ENVIRONMENTAL PROTECTION
AGENCY
40 CFR Part 60
[EPA–HQ–OAR–2023–0358; FRL–10655–02–
OAR]
RIN 2060–AV93
New Source Performance Standards
Review for Volatile Organic Liquid
Storage Vessels (Including Petroleum
Liquid Storage Vessels)
Environmental Protection
Agency (EPA).
ACTION: Final rule.
AGENCY:
The Environmental Protection
Agency (EPA) is finalizing amendments
to the new source performance
standards (NSPS) for Volatile Organic
Liquid Storage Vessels (Including
Petroleum Liquid Storage Vessels)
pursuant to the review required by the
Clean Air Act (CAA). The EPA is
finalizing revisions to the NSPS that are
applicable to volatile organic liquid
(VOL) storage vessels that commence
construction, reconstruction, or
modification after October 4, 2023,
under a new NSPS subpart, as well as
amendments to an existing subpart. In
the new NSPS subpart Kc, the EPA is
finalizing requirements to reduce the
vapor pressure applicability thresholds
and revise the volatile organic
compound (VOC) standards to reflect
the best system of emission reduction
(BSER) for affected storage vessels. In
addition, the EPA is finalizing degassing
emission controls; clarification of
startup, shutdown, and malfunction
(SSM) requirements; additional
monitoring requirements; and other
technical improvements
DATES: This final rule is effective on
October 15, 2024. The incorporation by
reference of certain publications listed
in the rule is approved by the Director
of the Federal Register as of October 15,
2024.
ADDRESSES: The EPA has established a
docket for this action under Docket ID
No. EPA–HQ–OAR–2023–0358. All
documents in the docket are listed on
the https://www.regulations.gov
website. Although listed, some
information is not publicly available,
e.g., Confidential Business Information
(CBI) or other information whose
disclosure is restricted by statute.
Certain other material, such as
copyrighted material, is not placed on
the internet and will be publicly
available only as portable document
format (PDF) versions that can only be
accessed on the EPA computers in the
docket office reading room. Certain
khammond on DSKJM1Z7X2PROD with RULES4
SUMMARY:
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
databases and physical items cannot be
downloaded from the docket but may be
requested by contacting the Public
Reading Room at (202) 566–1744. The
docket office has up to 10 business days
to respond to these requests. With the
exception of such material, publicly
available docket materials are available
electronically in Regulations.gov or on
the EPA computers in the Public
Reading Room at the EPA Docket
Center, WJC West Building, Room
Number 3334, 1301 Constitution Ave.
NW, Washington, DC. The Public
Reading Room hours of operation are
8:30 a.m. to 4:30 p.m. Eastern Standard
Time (EST), Monday through Friday.
The telephone number for the Public
Reading Room is (202) 566–1744, and
the telephone number for the EPA
Docket Center is (202) 566–1742.
FOR FURTHER INFORMATION CONTACT: Mr.
Michael Cantoni III, Sector Policies and
Programs Division (E143–01), Office of
Air Quality Planning and Standards,
U.S. Environmental Protection Agency,
109 T.W. Alexander Drive, P.O. Box
12055, Research Triangle Park, North
Carolina 27711; telephone number:
(919) 541–5593; and email address:
cantoni.michael@epa.gov.
SUPPLEMENTARY INFORMATION:
Preamble acronyms and
abbreviations. Throughout this
document the use of ‘‘we,’’ ‘‘us,’’ or
‘‘our’’ is intended to refer to the EPA.
We use multiple acronyms and terms in
this preamble. While this list may not be
exhaustive, to ease the reading of this
preamble and for reference purposes,
the EPA defines the following terms and
acronyms here:
AMEL alternative means of emissions
limitation
API American Petroleum Institute
ASTM American Society for Testing and
Materials
AVO audible, visual, and olfactory
BSER best system of emission reduction
CAA Clean Air Act
CBI Confidential Business Information
CDX Central Data Exchange
CEDRI Compliance and Emissions Data
Reporting Interface
CFR Code of Federal Regulations
EFR external floating roof
EIA economic impact analysis
EJ environmental justice
EPA Environmental Protection Agency
FR Federal Register
gal gallons
HAP hazardous air pollutant(s)
IBR incorporate by reference
ICR information collection request
IFR internal floating roof
kg/hr kilograms per hour
kPa kilopascals
LEL lower explosive limit
m3 cubic meters
MON Miscellaneous Organic Chemical
Manufacturing NESHAP
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
MTVP maximum true vapor pressure
NAICS North American Industry
Classification System
NESHAP national emission standards for
hazardous air pollutants
NSPS new source performance standards
NTAA National Tribal Air Association
NTTAA National Technology Transfer and
Advancement Act
OMB Office of Management and Budget
PDF portable document format
PRA Paperwork Reduction Act
PRD pressure relief device
ppmv parts per million by volume
psia pounds per square inch absolute
psig pounds per square inch gauge
RFA Regulatory Flexibility Act
RIN Regulatory Information Number
SCAQMD South Coast Air Quality
Management District
SSM startup, shutdown, and malfunction
STERPP 2000 U.S. EPA Storage Tank
Emission Reduction Partnership Program
UMRA Unfunded Mandates Reform Act
VCU vapor combustion unit
VOC volatile organic compound(s)
VOL volatile organic liquid
Organization of this document. The
information in this preamble is
organized as follows:
I. General Information
A. Does this action apply to me?
B. Where can I get a copy of this document
and other related information?
C. Judicial Review and Administrative
Review
II. Background
A. What is the statutory authority for this
action?
B. How does the EPA perform the NSPS
review?
C. What is the source category regulated in
this final action?
D. What outreach and engagement did the
EPA conduct?
III. What changes did we propose for the VOL
Storage Vessel NSPS?
IV. What actions are we finalizing and what
is our rationale for such decisions?
A. Revised NSPS for VOL Storage Vessels
That Commenced Construction,
Reconstruction, or Modification After
July 23, 1984, and on or Before October
4, 2023
B. Revised NSPS for VOL Storage Vessels
That Commenced Construction,
Reconstruction, or Modification After
October 4, 2023
C. NSPS Subpart Kc Without Startup,
Shutdown, and Malfunction Exemptions
D. Testing, Monitoring, and Inspection
Requirements
E. Recordkeeping and Electronic Reporting
F. Other Final Amendments
G. Effective Date and Compliance Dates
V. Summary of Cost, Environmental, and
Economic Impacts
A. What are the air quality impacts?
B. What are the cost impacts?
C. What are the economic impacts?
D. What are the benefits?
E. What analysis of environmental justice
did we conduct?
VI. Statutory and Executive Order Reviews
A. Executive Order 12866: Regulatory
Planning and Review and Executive
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
Order 14094: Modernizing Regulatory
Review
B. Paperwork Reduction Act (PRA)
C. Regulatory Flexibility Act (RFA)
D. Unfunded Mandates Reform Act
(UMRA)
E. Executive Order 13132: Federalism
F. Executive Order 13175: Consultation
and Coordination With Indian Tribal
Governments
G. Executive Order 13045: Protection of
Children From Environmental Health
Risks and Safety Risks
H. Executive Order 13211: Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use
I. National Technology Transfer and
Advancement Act (NTTAA) and 1 CFR
Part 51
J. Executive Order 12898: Federal Actions
To Address Environmental Justice in
Minority Populations and Low-Income
Populations and Executive Order 14096:
Revitalizing Our Nation’s Commitment
to Environmental Justice for All
K. Congressional Review Act (CRA)
khammond on DSKJM1Z7X2PROD with RULES4
I. General Information
A. Does this action apply to me?
The source category that is the subject
of this final action is composed of VOL
storage vessels (including petroleum
liquid storage vessels) regulated under
CAA section 111, NSPS. The 2022 North
American Industry Classification
System (NAICS) codes for the source
category are 325, 324, and 422710. The
NAICS codes serve as a guide for
readers outlining the type of entities
that this final action is likely to affect.
The NSPS codified in 40 CFR part 60,
subpart Kc, are directly applicable to
affected facilities that begin
construction, reconstruction, or
modification after October 4, 2023. Final
amendments to 40 CFR part 60, subpart
Kb, are applicable to affected facilities
that begin construction, reconstruction,
or modification after July 23, 1984, and
before October 4, 2023. Federal, State,
local, and Tribal government entities
that own and/or operate VOL storage
vessels are affected by this action. If you
have any questions regarding the
applicability of this action to a
particular entity, you should carefully
examine the applicability criteria found
in 40 CFR part 60, subparts Kb and Kc,
and consult the person listed in the FOR
FURTHER INFORMATION CONTACT section of
this preamble, your State air pollution
control agency with delegated authority
for NSPS, or your EPA Regional Office.
B. Where can I get a copy of this
document and other related
information?
In addition to being available in the
docket, an electronic copy of this final
action is available on the internet at
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
https://www.epa.gov/stationary-sourcesair-pollution/volatile-organic-liquidstorage-vessels-including-petroleum.
Following publication in the Federal
Register, the EPA will post the Federal
Register version of the final rule and
key technical documents at this same
website.
C. Judicial Review and Administrative
Review
Under CAA section 307(b)(1), judicial
review of this final action is available
only by filing a petition for review in
the United States Court of Appeals for
the District of Columbia Circuit (the
court) by December 16, 2024. Under
CAA section 307(b)(2), the requirements
established by this final rule may not be
challenged separately in any civil or
criminal proceedings brought by the
EPA to enforce the requirements.
Section 307(d)(7)(B) of the CAA
further provides that ‘‘[o]nly an
objection to a rule or procedure which
was raised with reasonable specificity
during the period for public comment
(including any public hearing) may be
raised during judicial review.’’ This
section also provides a mechanism for
the EPA to convene a proceeding for
reconsideration, ‘‘[i]f the person raising
an objection can demonstrate to the EPA
that it was impracticable to raise such
objection within [the period for public
comment] or if the grounds for such
objection arose after the period for
public comment (but within the time
specified for judicial review) and if such
objection is of central relevance to the
outcome of the rule.’’ Any person
seeking to make such a demonstration to
us should submit a Petition for
Reconsideration to the Office of the
Administrator, U.S. Environmental
Protection Agency, Room 3000, WJC
West Building, 1200 Pennsylvania Ave.
NW, Washington, DC 20460, with a
copy to both the person(s) listed in the
preceding FOR FURTHER INFORMATION
CONTACT section and the Associate
General Counsel for the Air and
Radiation Law Office, Office of General
Counsel (Mail Code 2344A), U.S.
Environmental Protection Agency, 1200
Pennsylvania Ave. NW, Washington, DC
20460.
II. Background
A. What is the statutory authority for
this action?
The EPA’s authority for this final rule
is CAA section 111, which governs the
establishment of standards of
performance for stationary sources.
Section 111(b)(1)(A) of the CAA requires
the EPA Administrator to list categories
of stationary sources that in the
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
83297
Administrator’s judgment cause or
contribute significantly to air pollution
that may reasonably be anticipated to
endanger public health or welfare. The
EPA must then issue performance
standards for new (and modified or
reconstructed) sources in each source
category pursuant to CAA section
111(b)(1)(B). These standards are
referred to as new source performance
standards, or NSPS. The EPA has the
authority to define the scope of the
source categories, determine the
pollutants for which standards should
be developed, set the emission level of
the standards, and distinguish among
classes, types, and sizes within
categories in establishing the standards.
CAA section 111(b)(1)(B) requires the
EPA to ‘‘at least every 8 years review
and, if appropriate, revise’’ new source
performance standards. However, the
Administrator need not review any such
standard if the ‘‘Administrator
determines that such review is not
appropriate in light of readily available
information on the efficacy’’ of the
standard. When conducting a review of
an existing performance standard, the
EPA has the discretion and authority to
add emission limits for pollutants or
emission sources not currently regulated
for that source category.
In setting or revising a performance
standard, CAA section 111(a)(1)
provides that performance standards are
to reflect ‘‘the degree of emission
limitation achievable through the
application of the best system of
emission reduction which (taking into
account the cost of achieving such
reduction and any nonair quality health
and environmental impact and energy
requirements) the Administrator
determines has been adequately
demonstrated.’’ The term ‘‘standard of
performance’’ in CAA section 111(a)(1)
makes clear that the EPA is to determine
both the best system of emission
reduction for the regulated sources in
the source category and the degree of
emission limitation achievable through
application of the BSER. The EPA must
then, under CAA section 111(b)(1)(B),
promulgate standards of performance
for new sources that reflect that level of
stringency. CAA section 111(b)(5)
generally precludes the EPA from
prescribing a particular technological
system that must be used to comply
with a standard of performance. Rather,
sources can select any measure or
combination of measures that will
achieve the standard. CAA section
111(h)(1) authorizes the Administrator
to promulgate ‘‘a design, equipment,
work practice, or operational standard,
or combination thereof’’ if in his or her
judgment, ‘‘it is not feasible to prescribe
E:\FR\FM\15OCR4.SGM
15OCR4
83298
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
or enforce a standard of performance.’’
CAA section 111(h)(2) provides the
circumstances under which prescribing
or enforcing a standard of performance
is ‘‘not feasible,’’ such as when the
pollutant cannot be emitted through a
conveyance designed to emit or capture
the pollutant or when there is no
practicable measurement methodology
for the particular class of sources.
Pursuant to the definition of new
source in CAA section 111(a)(2),
standards of performance apply to
facilities that begin construction,
reconstruction, or modification after the
date of publication of the proposed
standards in the Federal Register.
Under CAA section 111(a)(4),
‘‘modification’’ means any physical
change in, or change in the method of
operation of, a stationary source that
increases the amount of any air
pollutant emitted by such source or
which results in the emission of any air
pollutant not previously emitted.
Changes to an existing facility that do
not result in an increase in emissions
are not considered modifications. Under
the provisions in 40 CFR 60.15,
‘‘reconstruction’’ means the replacement
of components of an existing facility
such that: (1) the fixed capital cost of
the new components exceeds 50 percent
of the fixed capital cost that would be
required to construct a comparable
entirely new facility; and (2) it is
technologically and economically
feasible to meet the applicable
standards. Pursuant to CAA section
111(b)(1)(B), the standards of
performance or revisions thereof shall
become effective upon promulgation.
B. How does the EPA perform the NSPS
review?
As noted in section II.A. of this
preamble, CAA section 111 requires the
EPA to, at least every 8 years, review
and, if appropriate, revise the standards
of performance applicable to new,
modified, and reconstructed sources. If
the EPA revises the standards of
performance, the standards must reflect
the degree of emission limitation
achievable through the application of
the BSER considering the cost of
achieving such reduction and any
nonair quality health and environmental
impact and energy requirements. CAA
section 111(a)(1).
In reviewing an NSPS to determine
whether it is ‘‘appropriate’’ to revise the
standards of performance, the EPA
evaluates the statutory factors, which
may include consideration of the
following information:
• Expected growth for the source
category, including how many new
facilities, reconstructions, and
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
modifications may trigger NSPS in the
future.
• Pollution control measures,
including advances in control
technologies, process operations, design
or efficiency improvements, or other
systems of emission reduction, that are
‘‘adequately demonstrated’’ in the
regulated industry.
• Available information from the
implementation and enforcement of
current requirements that indicates that
emission limitations and percent
reductions beyond those required by the
current standards are achieved in
practice.
• Costs (including capital and annual
costs) associated with implementation
of the available pollution control
measures.
• The amount of emission reductions
achievable through application of such
pollution control measures.
• Any non-air quality health and
environmental impact and energy
requirements associated with those
control measures.
In evaluating whether the cost of a
particular system of emission reduction
is reasonable, the EPA considers various
costs associated with the particular air
pollution control measure or a level of
control, including capital costs and
operating costs, and the emission
reductions that the control measure or
particular level of control can achieve.
The Agency considers these costs in the
context of the industry’s overall capital
expenditures and revenues. The Agency
also considers cost effectiveness
analysis as a useful metric and as a
means of evaluating whether a given
control achieves emission reduction at a
reasonable cost. A cost effectiveness
analysis allows comparisons of relative
costs and outcomes (effects) of two or
more options. In general, cost
effectiveness is a measure of the
outcomes produced by resources spent.
In the context of air pollution control
options, cost effectiveness typically
refers to the annualized cost of
implementing an air pollution control
option divided by the amount of
pollutant reductions realized annually.
After the EPA evaluates the statutory
factors, the EPA compares the various
systems of emission reductions and
determines which system is ‘‘best’’ and
therefore represents the BSER. The EPA
then establishes a standard of
performance that reflects the degree of
emission limitation achievable through
the implementation of the BSER. In
performing this analysis, the EPA can
determine whether subcategorization is
appropriate based on classes, types, and
sizes of sources, and may identify a
different BSER and establish different
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
performance standards for each
subcategory. The result of the analysis
and the BSER determination leads to
standards of performance that apply to
facilities that begin construction,
reconstruction, or modification after the
date of publication of the proposed
standards in the Federal Register.
Because the NSPS reflect the BSER
under conditions of proper operation
and maintenance, in doing its review,
the EPA also evaluates and determines
the proper testing, monitoring,
recordkeeping, and reporting
requirements needed to ensure
compliance with the emission
standards.
C. What is the source category regulated
in this final action?
The EPA first promulgated NSPS for
petroleum liquid storage vessels on
March 8, 1974 (39 FR 9317). These
standards of performance are codified in
40 CFR part 60, subpart K, and are
applicable to sources that commence
construction, modification, or
reconstruction after June 11, 1973, and
prior to May 19, 1978. These standards
were amended several times before
1980, when the EPA proposed to
establish revised NSPS for petroleum
liquid storage vessels as NSPS subpart
Ka (45 FR 23379; April 4, 1980). In
1982, the EPA published a list of
priority sources for which additional
NSPS should be established (47 FR 951;
January 8, 1982), and VOL storage
vessels at synthetic organic chemical
manufacturers were included in the
priority list.
Pursuant to the EPA’s authority under
CAA section 111, the Agency proposed
(49 FR 29698; July 23, 1984) and
promulgated (52 FR 11420; April 8,
1987) NSPS for VOL storage vessels
(including petroleum liquid storage
vessels) for which construction,
reconstruction, or modification
commenced after July 23, 1984, as NSPS
subpart Kb.1 NSPS subpart Kb regulates
storage vessels with a capacity of 75
cubic meters (m3) (∼20,000 gallons) or
more that store VOLs with a maximum
true vapor pressure (MTVP) greater than
or equal to 15.0 kilopascals (kPa) (∼2.18
pounds per square inch absolute (psia))
and from storage vessels with a capacity
of 151 m3 (∼40,000 gallons) or more that
store organic liquids with an MTVP
1 On October 15, 2003 (68 FR 59328), the EPA
finalized amendments to NSPS subpart Kb to
exempt certain storage vessels by capacity and
vapor pressure, exempt process tanks, and add a
process tank definition. At the same time, the EPA
also amended the rule to exempt storage vessels
that are subject to the National Emission Standards
for Hazardous Air Pollutants (NESHAP) for Solvent
Extraction of Vegetable Oil Production.
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
greater than or equal to 3.5 kPa (∼0.51
psia). VOC emissions controls are
required on storage vessels with a
capacity of 75 m3 (∼20,000 gallons) or
more that store VOLs with an MTVP
greater than or equal to 27.6 kPa (∼4.0
psia) and from storage vessels with a
capacity of 151 m3 (∼40,000 gallons) or
more that store organic liquids with an
MTVP greater than or equal to 5.2 kPa
(∼0.75 psia). NSPS subpart Kb emission
controls include the use of an external
floating roof (EFR), an internal floating
roof (IFR), or a closed vent system and
a control device (see 40 CFR 60.110b(a)
and 40 CFR 60.112b(a) and (b)).2 3 NSPS
subpart Kb also specifies testing,
monitoring, recordkeeping, reporting,
and other requirements in 40 CFR
60.113b through 40 CFR 60.116b to
ensure compliance with the standards.
Storage vessels with an EFR consist of
an open-top cylindrical steel shell
equipped with a deck that floats on the
surface (commonly referred to as a
floating ‘‘roof’’) of the stored liquid.
Storage vessels with an IFR are fixed
roof vessels 4 that also have a deck
internal to the vessel that floats on the
liquid surface (commonly referred to as
an internal floating ‘‘roof’’) within the
fixed roof vessel.
The standards set in NSPS subpart Kb
for storage vessels with an EFR or IFR
are a combination of design, equipment,
work practice, and operational
standards set pursuant to CAA section
111(h). These standards require, among
other things, that a rim seal be installed
continuously around the circumference
of the vessel (between the inner wall of
the vessel and the floating roof) to
prevent VOC emissions from escaping to
the atmosphere through gaps between
the floating roof and the inner wall of
the storage vessel. For IFRs, NSPS
subpart Kb allows a single liquidmounted or mechanical shoe primary
seal (to be used with or without a
secondary seal), or a vapor-mounted
primary seal in combination with a
2 All affected storage vessels storing organic
liquids with a true vapor pressure of 76.6 kPa or
more must use a closed vent system and a control
device. See 40 CFR 60.112b(b).
3 As part of NSPS subpart Kb, the EPA proposed
(49 FR 29703; July 23, 1984) and finalized (52 FR
11421; April 8, 1987) that the best demonstrated
technology for vessels storing VOL liquids with
vapor pressures less than 76.6 kPa (≅11.1 psia)
consists of an IFR with a liquid-mounted or
mechanical shoe primary seal and controlled
fittings or an EFR with a liquid-mounted or
mechanical shoe primary seal and gasketed fittings.
For vessels with greater vapor pressures, the EPA
determined the best demonstrated technology to be
a closed vent system and control device.
4 A fixed roof storage vessel consists of a
cylindrical steel shell with a permanently affixed
roof, which may vary in design from cone or domeshaped to flat.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
secondary seal. For EFRs, NSPS subpart
Kb allows either a liquid-mounted or
mechanical shoe primary seal, both of
which must be used with a secondary
seal; vapor-mounted primary seals are
not allowed for EFRs. NSPS subpart Kb
also requires numerous deck fittings 5
on the floating roof to be equipped with
a gasketed cover or lid that is kept in the
closed position at all times (i.e., no
visible gap), except when the device
(deck fitting) is in actual use, to prevent
VOC emissions from escaping through
the deck fittings. In addition, NSPS
subpart Kb requires owners and
operators to conduct visual inspections
to check for defects in the floating roof,
rim seals, and deck fittings (e.g., holes,
tears, or other openings in the rim seal,
or covers and lids on deck fittings that
no longer close properly) that could
expose the liquid surface to the
atmosphere and potentially result in
VOC emission losses through rim seals
and deck fittings.6
NSPS subpart Kb includes two
primary alternative means of
compliance. Owners or operators may
either comply with the consolidated air
rule provisions for storage vessels in 40
CFR part 65, subpart C, or comply with
the national emission standards for
hazardous air pollutants (NESHAP) for
storage vessels in 40 CFR part 63,
subpart WW (NESHAP subpart WW).
The substantive control requirements in
these rules are the same as in NSPS
subpart Kb although they may have
slight differences in the details of the
fitting and inspection requirements.
The EPA proposed the current review
of the VOL storage vessels (including
petroleum liquid storage vessels) NSPS
subpart Kb on October 4, 2023. We
received 29 comments from industry,
environmental groups, State
environmental agencies, and others
during the comment period. After the
conclusion of the comment period, we
received one additional comment in
February 2024. A summary of the more
significant comments we received
regarding the proposed rule and our
responses are provided in this preamble.
5 Numerous fittings pass through or are attached
to floating decks to accommodate structure support
components or to allow for operational functions.
Typical deck fittings include, but are not limited to
access hatches, gauge floats, gauge hatch/sample
wells, rim vents, deck drains, deck legs, vacuum
breakers, pontoon covers and guidepoles. IFR
storage vessels may also have deck seams, fixed roof
support columns, ladders, and/or stub drains.
6 For details about storage vessel emissions, refer
to the Compilation of Air Pollutant Emission
Factors, Volume 1: Stationary Point and Area
Sources, AP–42, Fifth Edition, Chapter 7: Liquid
Storage Tanks, dated June 2020 which is available
at: https://www.epa.gov/air-emissions-factorsandquantification/ap-42-compilation-air-emissionsfactors.
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
83299
A summary of all other public
comments on the proposal and the
EPA’s responses to those comments is
available in New Source Performance
Standards for Volatile Organic Liquid
Storage Vessels, Background
Information for Final Amendments,
Summary of Public Comments and
Responses, Docket ID No. EPA–HQ–
OAR–2023–0358. In this action, the EPA
is finalizing decisions and revisions
pursuant to CAA section 111(b)(1)(B)
review for VOL storage vessels after our
considerations of all the comments
received.
D. What outreach and engagement did
the EPA conduct?
As part of this rulemaking, the EPA
engaged and consulted with the public,
including communities with
environmental justice (EJ) concerns,
through interactions such as providing a
webinar, offering information on the
website for this rule, and informing the
public of the proposed action by
sending notifications with summaries of
the action and information on how to
comment. These opportunities allowed
the EPA to hear directly from the public,
especially communities potentially
impacted by this final action. The
webinar slides can be found in the
docket for this rule (Docket ID No. EPA–
HQ–OAR–2023–0358).
Prior to proposal publication, the EPA
conducted outreach by providing
background on the source category and
the existing requirements of NSPS
subpart Kb on the September 19, 2023,
EJ National Community Engagement call
and on the August 31, 2023, National
Tribal Air Association (NTAA) call.
After publication, the EPA conducted a
community outreach webinar on
October 24, 2023, which was focused on
discussing the details of the proposed
rulemaking and how to provide
comment on the proposed rule.
Additionally, the EPA discussed the
contents of the proposed rule on an
October 26, 2023, NTAA call and
encouraged interested parties to submit
comments. The EPA received a request
from one Tribe for consultation. On
November 8, 2023, the EPA met with
that Tribe for the purposes of discussing
NSPS subpart Kc and other issues but
was unable to conduct consultation on
this specific rulemaking.
III. What changes did we propose for
the VOL Storage Vessel NSPS?
On October 4, 2023, the EPA
proposed the current review of the VOL
Storage Vessel NSPS. In that action, we
proposed the following actions under
NSPS subpart Kc:
E:\FR\FM\15OCR4.SGM
15OCR4
83300
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
• General applicability thresholds
that include VOL storage vessels greater
than or equal to 20,000 gallons (gal).
• Vapor pressure thresholds for
controlled VOL storage vessels greater
than or equal to 40,000 gal (151 m3)
with MTVPs greater than or equal to 0.5
psia (3.4 kPa).
• Vapor pressure thresholds for
controlled VOL storage vessels greater
than or equal to 20,000 gal (75.7 m3) and
less than 40,000 gal (151 m3) with
MTVPs greater than or equal to 1.5 psia
(10.3 kPa).
• Improved standards of performance
for vessels that have IFRs, EFRs, and
closed vent systems routed to a control
device, fuel gas system, or process
designed to achieve an average 98
percent control efficiency.
• Updated standards of performance
for IFR storage vessels that include
improved seal system requirements,
guidepole configurations reflective of
the 2000 U.S. EPA Storage Tank
Emission Reduction Partnership
Program (STERPP), and annual lower
explosive limit (LEL) monitoring.
• Updated standards of performance
for EFR storage vessels that include
requirements for welded deck seams,
and improved guidepole requirements.
• Updated standards for closed vent
systems that are routed to a control
device, fuel gas system, or process and
include requirements for preventing
emissions venting to atmosphere,
annual EPA Method 21 monitoring, and
quarterly audible, visual, and olfactory
(AVO) inspections.
• Degassing standards of performance
for VOL storage vessels greater than or
equal to 1 million gal (3,790 m3) with
MTVPs greater than or equal to 1.5 psia
(10.3 kPa).
• Modification provisions dependent
upon an increase of the MTVP from the
VOLs previously stored.
• Improved testing, monitoring, and
inspection requirements.
• Provisions establishing that
emission limitations apply at all times,
including during periods of SSM.
• Improved recordkeeping and
reporting requirements, which include
the implementation of electronic
reporting.
Additionally, we proposed to add
electronic reporting requirements to the
existing subpart, NSPS subpart Kb.
IV. What actions are we finalizing and
what is our rationale for such
decisions?
The EPA is finalizing revisions to the
NSPS for VOL storage vessels pursuant
to CAA section 111(b)(1)(B) review. The
EPA is promulgating the NSPS revisions
in a new subpart, 40 CFR part 60,
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
subpart Kc. The new NSPS subpart is
applicable to affected sources
constructed, modified, or reconstructed
after October 4, 2023.
Under NSPS subpart Kc, we are
finalizing standards that reflect the
BSER for affected storage vessels. The
rulemaking proposal included different
criteria thresholds for general
applicability versus for storage vessel
control. Under the finalized general
applicability provisions, the EPA has
included a new exemption for storage
vessels that only store VOL with an
MTVP less than 0.25 psia (1.7 kPa) in
response to comments we received
asking to eliminate recordkeeping
requirements for storage vessels with
vapor pressures well below the
thresholds for which controls are
required. We are finalizing the capacity
and vapor pressure thresholds for which
controls are required as proposed.
Specifically, we are finalizing control
requirements for: (1) VOL storage
vessels greater than or equal to 40,000
gal (151 m3) with MTVPs greater than or
equal to 0.5 psia (3.4 kPa); and (2) VOL
storage vessels greater than or equal to
20,000 gal (75.7 m3) and less than
40,000 gal (151 m3) with MTVPs greater
than or equal to 1.5 psia (10.3 kPa). We
are also finalizing modification
provisions similar to those proposed,
but we are clarifying that a modification
occurs when a ‘‘. . . storage vessel is
used to store VOL that has a greater
maximum true vapor pressure than all
VOL historically stored or permitted.’’
In addition to updates involving
applicability and modification, we are
finalizing the proposed standards for
storage vessels with IFRs, EFRs, and
closed vent systems routed to a control
device, fuel gas system, or process, with
minor adjustments based on feedback.
Regarding degassing controls, we are
finalizing the provisions with minor
revisions to require controls on
nonflammable liquid degassing until
reaching 5,000 parts per million by
volume (ppmv) as methane vapor space
concentration rather than the 10 percent
LEL.
We are finalizing testing, monitoring,
and inspection requirements as
proposed, with some minor revisions
that involve matters such as the
timelines and frequency for completing
inspections, LEL monitoring calibration
procedures, inspection requirements,
and the MTVP determinations.
Similarly, we are finalizing the
recordkeeping and reporting
requirements with minor revisions from
the proposal involving matters such as
pressure releases, closed vent system
monitoring, and reporting deadlines.
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
This action also finalizes standards of
performance in NSPS subpart Kc that
apply at all times including during
periods of SSM and other changes such
as electronic reporting, as proposed.
This action also finalizes revisions in
NSPS subpart Kb to require electronic
reporting as proposed.
A. Revised NSPS for VOL Storage
Vessels That Commenced Construction,
Reconstruction, or Modification After
July 23, 1984, and on or Before October
4, 2023
We proposed revisions to NSPS
subpart Kb to add electronic reporting
requirements. We are finalizing those
revisions as proposed. Our response to
major comments received on the
proposed NSPS subpart Kb revisions are
provided in this section. Additional
public comments received and our
responses to those comments are
include in the Summary of Public
Comments and Responses document
included in Docket ID No. EPA–HQ–
OAR–2023–0358.
Comment: One commenter stated that
the EPA has no lawful or rational basis
for not reviewing the flare standards
from existing NSPS subpart Kb to
consider whether to revise NSPS
subpart Kb itself. The commenter stated
that since the EPA has declined to
revise the general provisions to include
specific monitoring requirements to
ensure compliance, the EPA must revise
the NSPS subpart Kb provisions to do
so, as expressly required by 40 CFR
60.18(d). The commenter stated that the
EPA’s failure to consider whether to
revise the NSPS subpart Kb standards
also violates a consent decree that the
EPA entered into to resolve
environmental groups’ lawsuit regarding
the EPA’s failure to comply with its 8year review obligations under CAA
section 111(b)(1)(B) for the flare
provisions from NSPS subpart Kb and
other NSPS subparts, as well as its 8year review obligations for certain
NESHAP subparts.
Response: The EPA disagrees with
this comment. We reviewed NSPS
subpart Kb and proposed new standards
of performance, including new design,
operating, and monitoring requirements
for flares, in the new NSPS subpart Kc
under CAA section 111(b)(1)(B), which
requires that the EPA ‘‘. . . review and,
if appropriate, revise such standards
following the same procedures required
by this subsection for promulgating
such standards.’’
CAA section 111(b)(1)(B) does not
require retroactive revisions to the
existing NSPS subpart (i.e., NSPS
subpart Kb). Rather, any revision to an
NSPS must follow the same procedures
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
for promulgating such standards under
CAA section 111(b)(1)(B). CAA section
111 establishes a bifurcated approach to
regulating sources. Under CAA section
111(b)(1)(B), the EPA is required to
promulgate standards of performance
for new sources, which CAA section
111(a)(2) defines as ‘‘any stationary
source, the construction or modification
of which is commenced after the
publication of regulations (or, if earlier,
proposed regulations) prescribing a
standard of performance under this
section which will be applicable to such
source.’’ Existing sources are defined at
CAA section 111(a)(6) to mean ‘‘any
stationary source other than a new
source’’ and are regulated via a State
planning process pursuant to CAA
section 111(d). Accordingly, the
revisions, which are being finalized in
a new NSPS subpart Kc, apply to
sources that have commenced
construction, reconstruction, or
modification after October 4, 2023, the
proposal date for this action. Sources
presently subject to NSPS subpart Kb
are not, by definition under this
statutory provision, new sources that
could be subjected to the revised
standards finalized in NSPS subpart Kc.
Rather, they are treated as existing
sources relative to the revised standards
finalized in NSPS subpart Kc. Revision
of the flare provisions in NSPS subpart
Kb consistent with the changes being
finalized with respect to NSPS subpart
Kc would be akin to directly applying
a new standard of performance to
existing sources, which would be
inconsistent with the statutory structure
that subjects regulation of new and
existing sources to separate processes.
Further, NSPS subpart Kc includes
standards prescribed in accordance with
CAA section 111(h)(1), for flares and
other closed vent systems routed to a
control device designed to achieve a 98
percent reduction in VOC emissions.
Because CAA section 111(b)(1)(B) does
not require revisions to the existing
NSPS subpart (i.e., NSPS subpart Kb),
which continues to require 95 percent
reduction in VOC emissions when using
a flare, the EPA did not propose in this
rulemaking to reopen NSPS subpart Kb
to include the new operating and
monitoring requirements for flares that
are needed to assure 98 percent VOC
reduction when using a flare.
Moreover, because regulated sources
subject to NSPS subpart Kb were not
given notice of any such potential
change, altering the flare requirements
in NSPS subpart Kb in the final rule
would unfairly put sources that have
been using flares to comply with NSPS
subpart Kb in violation of such
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
requirements upon the effective date of
this final rule. Thus, the EPA is not
amending NSPS subpart Kb to reflect
the new operating and monitoring flare
requirements that are included in the
new NSPS subpart Kc. The EPA notes,
however, that as existing sources trigger
modification, they will become subject
to NSPS subpart Kc and the new flare
requirements in the rule.
We disagree with the commenter’s
assertion that our review findings
violate the consent decree. In that
consent decree, the EPA agreed to
review and, if necessary, revise NSPS
subpart Kb. In this case, the EPA
proposed these revisions as a new
subpart to prevent application of ‘‘new
source’’ standards to sources that are
‘‘existing’’ at the time of proposal. Thus,
our proposal of NSPS subpart Kc
reflects our review of NSPS subpart Kb
and the revisions to that standard
appropriate for new sources.
Comment: One commenter stated that
the EPA unlawfully and arbitrarily
failed to revise existing NSPS subpart
Kb to specify that the SSM exemptions
from the [40 CFR part 60] general
provisions do not apply. The
commenter stated that the EPA has
acted outside its statutory authority in
promulgating the unlawful SSM
exemptions from the general provisions,
and therefore the Agency must revise
NSPS subpart Kb to make clear that the
general provisions’ exemptions do not
apply. The commenter noted that
although CAA section 111(b)(1)(B)
allows the EPA to avoid revising
standards when ‘‘review is not
appropriate in light of readily available
information on the efficacy of such
standard,’’ the EPA could not lawfully
or rationally invoke that exception,
since the application of the general
provisions’ exemptions to NSPS subpart
Kb is plainly unlawful.
Response: As noted in the previous
comment response, we reviewed the
current subpart Kb standards,
determined a series of appropriate
revisions, and concluded that these
revisions should be completed as a
separate subpart. We disagree with the
commenter that additional revision to
NSPS subpart Kb is necessary to remove
SSM exemptions in the 40 CFR part 60
general provisions. First, we note that
the performance testing requirements in
40 CFR 60.113b(c) clearly indicate that
the provisions in 40 CFR 60.8 do not
apply. As such, objectionable language
regarding performance test results
obtained during SSM events is not
applicable under NSPS subpart Kb.
Second, the SSM exemption in 40 CFR
60.11(c) is also not applicable to NSPS
subpart Kb because NSPS subpart Kb
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
83301
does not contain opacity limits. Because
the sections in the 40 CFR part 60
general provisions that contain
potentially unlawful SSM exemptions
are not applicable under NSPS subpart
Kb, we found no need to further revise
NSPS subpart Kb at this time.
B. Revised NSPS for VOL Storage
Vessels That Commenced Construction,
Reconstruction, or Modification After
October 4, 2023
This section describes the key
technical standards that were proposed,
the major comments received on the
proposed requirements, our responses to
those comments, and our rationale for
the final requirements. Additional
public comments received on the
technical standards and our responses
to those comments are included in the
Summary of Public Comments and
Responses document included in
Docket ID No. EPA–HQ–OAR–2023–
0358.
The EPA is finalizing standards of
performance that reflect the BSER as
well as alternative compliance
standards for controlled storage vessels.
The final standards are consistent with
the determinations explained in the
rulemaking proposal (88 FR 68540–47;
October 4, 2023) and the analysis
detailed in the memorandum Control
Options for Storage Vessels in Docket ID
No. EPA–HQ–OAR–2023–0358. While
the EPA has made minor adjustments to
these standards based on public
comment, the BSER determination
remains unchanged. The adjustments
incorporated based on public comment
are detailed in sections IV.B.4. and 5. of
this document.
In summary, the finalized BSER
analyses for NSPS subpart Kc are
dependent on the MTVP of a stored
VOL and follow the precedent
established in NSPS subparts Kb, Ka,
and K. In the NSPS subpart K proposal,
the EPA detailed its justification for the
use of equipment specification (or work
practice) standards. As part of the
original rulemaking proposal, the EPA
explained that equipment specifications
are the most practical method of
regulating storage vessel emissions.
Direct emission measurements for
storage vessels are often impractical,
and storage vessel emissions are often
modeled and dependent on many
distinguishing factors and variables. The
EPA believes that equipment
specification standards are less
burdensome for the storage vessel
operation and enforcement (38 FR
15406; May 4, 1973). For VOL storage
vessels with an MTVP less than 11.1
psia, the EPA is finalizing the following
BSER as proposed (88 FR 68542;
E:\FR\FM\15OCR4.SGM
15OCR4
83302
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
October 4, 2023): a fixed roof in
conjunction with an internal floating
roof equipped with a liquid-mounted or
mechanical shoe primary seal and a
continuous rim mounted secondary
seal, either a flexible fabric sleeve or
gasketed sliding cover on pipe columns
(if any), specific STERPP compliant
guidepole configurations, and gasketed
covers.
The EPA is also finalizing two
alternative compliance options for VOL
storage vessels with MTVPs less than
11.1 psia as proposed:
(1) An external floating roof equipped
with a liquid-mounted or mechanical
shoe primary seal and a continuous rimmounted secondary seal, with welded
deck seams and both seals meeting
certain gap requirements, specific
guidepole configurations, and gasketed
covers; or
(2) A closed vent system routed to a
98 percent effective control device, fuel
gas system, or process.
For VOL storage vessels with MTVPs
greater than or equal to 11.1 psia, the
EPA is finalizing, as proposed, the BSER
as a closed vent system routed to a 98
percent effective control device, fuel gas
system, or process.
khammond on DSKJM1Z7X2PROD with RULES4
1. Vapor Pressure Applicability
Thresholds
NSPS subpart Kb established control
requirements, at 40 CFR 60.112b(a), for
storage vessels based on vessel capacity
and VOL vapor pressures. In our review
of NSPS subpart Kb, we assessed the
vapor applicability thresholds for
affected facilities and for controls on
affected storage vessels to determine
whether these thresholds needed to be
revised for purposes of NSPS subpart
Kc. In NSPS subpart Kb there are two
different sets of vapor pressure
applicability thresholds: one for
determining affected facilities and one
for determining controls.
We proposed to not include specific
vapor pressure applicability thresholds
in defining an affected facility under
NSPS subpart Kc. As such, the proposed
affected facility under NSPS subpart Kc
is any storage vessel with a capacity of
20,000 gallons or more used to store a
VOL without exclusion for storage
vessels under a set vapor pressure.
Based on comments received, we are
adding an exemption at 40 CFR
60.110c(b)(8) for storage vessels that
only store VOL with an MTVP of less
than 0.25 psia. This revision from
proposal helps to limit burden for
storage vessels that only store VOL with
very low vapor pressures, but it does not
otherwise impact the control standards
proposed for NSPS subpart Kc.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
Based on the BSER analysis, we
proposed to revise the vapor
applicability thresholds that require
emission controls under NSPS subpart
Kc. Specifically, we proposed to revise
the MTVP threshold for smaller storage
vessels (those with capacity of at least
20,000 gallons but less than 40,000
gallons) to 1.5 psia and for larger storage
vessels (those with capacity of 40,000
gallons or more) to 0.5 psia. We
determined that applying controls for
VOL at or above these thresholds
yielded cost-effective emission
reductions. We are finalizing these
thresholds as proposed.
2. Other Applicability Provisions
NSPS subpart Kb includes several
provisions that exempt specific groups
of VOL storage vessels from
applicability under the standard. We
proposed to carry over several of these
exemptions, such as exemptions for:
storage vessels that operate at coke oven
by-product plants; bulk gasoline plants;
gasoline service stations; pressure
vessels; vessels attached to mobile
vehicles; certain vessels at oil and gas
production sites prior to custody
transfer; and vessels that store beverage
alcohol. We proposed to remove
exemptions under NSPS subpart Kc for
vessels subject to the NESHAP for
solvent extraction for vegetable oil
production outlined in 40 CFR part 63,
subpart GGGG, because the standards
proposed in NSPS subpart Kc are more
stringent than the existing NESHAP
subpart GGGG standards. We are
finalizing these applicability provisions
as proposed.
We are adding overlap provisions,
based on comments received, to allow
storage vessels subject to NSPS subparts
K, Ka, or Kb, or NESHAP subpart WW
to comply with the provisions in NSPS
subpart Kc because the final provisions
in NSPS subpart Kc are at least as
stringent as those in NSPS subparts Kb,
Ka, and K, and NESHAP subpart WW.
These overlap provisions, which were
not proposed, allow facilities the
operational flexibility of simply
complying with NSPS subpart Kc if they
operate storage vessels covered under
the specified existing storage vessel
rules.
Comment: One commenter stated that
the EPA should add an alternative
compliance option that complying with
NSPS subpart Kc demonstrates
compliance with the floating roof
requirements in NESHAP subpart WW.
Another commenter suggested that the
EPA should address overlaps between
NSPS subpart Kc and other rules
consistent with the overlap provisions
in NSPS subpart Kb.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
Response: There are not overlap
provisions in NSPS subpart Kb beyond
the alternative means of compliance in
40 CFR 60.110b(e). The requirements in
the rules listed in 40 CFR 60.110b(e) are
not equivalent to the requirements in
NSPS subpart Kc, so we removed these
alternative means of compliance from
NSPS subpart Kc. We agree with
commenters that including provisions
in NSPS subpart Kc to allow compliance
with the provision in NSPS subpart Kc
to be considered compliance with the
provisions in NSPS subpart Kb or
NESHAP subpart WW is appropriate
because the final requirements in NSPS
subpart Kc are at least as stringent as
those in NSPS subpart Kb and NESHAP
subpart WW. As such, we have added
provisions under 40 CFR 60.110c(h) and
40 CFR 60.110c(i) that allow owners and
operators with storage vessels subject to
the standards of NSPS subparts K, Ka,
and Kb, and NESHAP subpart WW to
choose to comply with the provisions of
NSPS subpart Kc to demonstrate
compliance. This will allow facilities
that may be subject to a NESHAP that
references NSPS subpart Kb or NESHAP
subpart WW but also subject to NSPS
subpart Kc to consolidate their
recordkeeping and reporting
requirements and comply only with
NSPS subpart Kc.
3. Modification Provisions
For purposes of CAA section 111,
modifications are defined as ‘‘. . . any
physical change in, or change in the
method of operation of,’’ an existing
facility which increases the amount of
any air pollutant (to which a standard
applies) emitted into the atmosphere by
that facility or which results in the
emission of any air pollutant (to which
a standard applies) into the atmosphere
not previously emitted. NSPS subpart A
further provides provisions explaining
how a modification is identified, as well
as defining certain exemptions to those
general rules. In particular, 40 CFR
60.14(e)(4) states that the ‘‘[u]se of an
alternative fuel or raw material’’ is not
considered a modification if the existing
facility was designed to accommodate
that alternative use. The EPA proposed,
for purposes of NSPS subpart Kc, that a
change in the liquid stored in the
storage vessel to a VOL with a higher
MTVP does not constitute a ‘‘use of an
alternative fuel or raw material’’ and
would be considered a modification
under NSPS subpart Kc. Specifically,
the EPA proposed that a modification
occurs when a ‘‘storage vessel is used to
store VOL that has a greater maximum
true vapor pressure than the VOL
previously stored.’’
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
We are finalizing modification
provisions similar to those proposed,
but we are clarifying that a modification
occurs when a ‘‘. . . storage vessel is
used to store VOL that has a greater
maximum true vapor pressure than all
VOL historically stored or permitted.’’
Commenters were concerned that our
proposed language, which referred to
VOL ‘‘previously stored,’’ was
ambiguous and potentially limited the
modification assessment to the most
recently stored VOL. We revised the text
to ‘‘. . . historically stored or permitted
. . . ,’’ in order to clarify our intent that
a modification occurs when a new VOL
is stored that has a higher MTVP than
any of the previously stored or
permitted VOL (and not just the most
recently stored VOL). Finally, we are
also clearly stating, consistent with our
discussion in section III.G. of the
proposal preamble, that the alternative
fuel or raw material exemption in 40
CFR 60.14(e)(4) does not apply to
storage vessels under NSPS subpart Kc.
Comment: Several commenters stated
that the language ‘‘the VOL previously
stored’’ in 40 CFR 60.110c(e) is unclear
as to whether any VOL the storage
vessel has previously stored is included,
or just the VOL stored immediately
prior to the change. The proposed 40
CFR 60.110c(e) language does not clarify
which liquids are different, or not
different, from ‘‘the VOL previously
stored.’’ Without clarity on these points,
the rule language is subject to a
significant range of interpretations, from
any stored organic liquid being the same
VOL, to any de minimis change in
liquid properties being a different VOL.
Another commenter stated that the
phrase ‘‘the VOL previously stored’’
should be removed from 40 CFR
60.110c(e).
Several commenters requested that
storing a VOL with a higher MTVP than
the liquid previously stored only be
considered a modification if storing
such a liquid would require
modification of a facility’s operating
permit. One commenter further stated
that using a facility’s operating permit to
determine modification would place an
unreasonable burden of proof on facility
owners or operators. Another
commenter stated that storage vessels
are permitted to handle multiple
materials, typically using a worst-case
scenario, and changing the liquid stored
in the storage vessel to one above the
permitted vapor pressure threshold
would not necessarily increase
emissions since emissions are based on
other parameters and conditions, such
as changing the hourly pumping rate,
annual throughput, or storage
temperature.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
Two commenters noted that storage
vessels routinely switch between storing
materials with lower and higher vapor
pressures at certain facilities, such as
batch chemical plants, refineries, and
gasoline terminals (for example, annual
transitions between summer and winter
gasoline). According to the commenters,
such routine and other operational
transitions between products do not rise
to the level of a ‘‘modification’’
triggering performance standards for
new sources under the CAA.
Response: We agree with the
commenters that the proposed language
(‘‘the VOL previously stored’’) could be
misinterpreted to refer only to the VOL
stored immediately prior to the change,
and that was not our intent. For
example, if a storage vessel has been
used to store both summer and winter
grades of gasoline, we did not intend
that the next switch from summer to
winter gasoline would trigger a
modification of the storage vessel. We
also agree that owners and operators
should not trigger modification for
introducing VOLs that do not exceed the
MTVP of all VOLs that may also exist
in a permit. We are clarifying the
regulatory language to match our intent
at proposal and reduce burden by
replacing the phrase ‘‘the VOL
previously stored’’ with the phrase ‘‘all
VOL historically stored or permitted.’’
In discussions with industry
representatives and the EPA permit
specialists, we found that specific VOLs
are not always listed in permits.
Therefore, we are not including
revisions suggested by some
commenters to limit modification to
only those actions that would require
modification of a facility’s operating
permit.
We disagree with the commenters
who suggested that changing the
volatility of the liquids stored does not
increase emissions from the storage
vessel. We note that the emission rate
for modification is expressed in
kilograms per hour (kg/hr) and that it is
not evaluated on an annual basis. Even
if the facility intends to lower the fill
rate to limit increases in annual
emissions, the storage vessel will still
have higher emissions (in kg/hr) during
periods when the storage vessel is not
being filled.
Comment: Several commenters
disagreed with the EPA’s proposal that
a change in the liquid stored in the
storage vessel to a VOL with a higher
MTVP does not constitute a ‘‘use of an
alternative fuel or raw material’’ and
thus would instead be considered a
change in the method of operation of a
source. According to the commenters,
the stored materials are fuels or raw
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
83303
materials for some customer or
downstream user, and there is no
requirement for a material to be used at
the facility where it is being stored for
it to be considered a raw material or a
fuel. According to one commenter, the
EPA had determined that changing a
liquid, regardless of volatility, is not an
operational change, and another
commenter stated that storage vessel
service changes are the kind of event
that the EPA intended to address in 40
CFR 60.14(e)(4). Other commenters
recommended that the EPA retain its
long-held interpretation that a change of
liquids in an existing VOL storage vessel
does not constitute a ‘‘modification’’
triggering applicability of NSPS subpart
Kc. Commenters also noted that the
proposed interpretation would
arbitrarily apply NSPS subpart Kc to
some storage vessels, and not to other
identical vessels, based on their historic
use rather than their design capabilities.
One commenter stated that changing
a liquid in a storage vessel is not a
modification if the material could have
been previously accommodated without
a physical change or a capital
expenditure. Some commenters
requested that the EPA revise proposed
40 CFR 60.110c(e) to clearly state that
changing the material stored is not a
modification if the storage vessel could
accommodate the new material without
a physical change or significant capital
expenditure. Commenters requested that
the EPA review historical documents
related to NSPS subpart Kb and
reconfirm these long-held policies
regarding modification of storage
vessels.
One commenter stated that the EPA’s
reference to FCC v. Fox Television
Stations, Inc. for the proposition that it
need only articulate a ‘‘good reason’’ for
its ‘‘change in policy’’ is misplaced.
According to the commenter, the EPA is
not proposing to amend any of its
existing regulations setting forth its
policy for NSPS triggering
‘‘modifications.’’ Rather, the proposal
reflects a reversal of the EPA’s
longstanding interpretation of the CAA
and its regulations in 40 CFR 60.2 and
60.14. Unlike a change in policy, the
commenter contends, ‘‘an agency’s
interpretation of a statute or regulation
that conflicts with a prior interpretation
is entitled to considerably less deference
than a consistently held agency view.’’
Advanced Energy United, Inc. v. FERC
(82 F.4th 1095, 1114 (D.C. Cir. 2023)
(quoting Thomas Jefferson University v.
Shalala, 512 U.S. 504 (1994)).
Accordingly, it is the EPA’s long-held
interpretation of ‘‘modifications’’—for
nearly 40 years—that is entitled to
deference. The commenter asserts that
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83304
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
this is particularly true where, as here,
the EPA has not provided a justification
for the conflicting interpretation or
articulated the scope of changes in
volatility of stored liquids that would
actually trigger a ‘‘modification.’’
Response: The EPA disagrees with
these comments. First, the EPA’s
reliance on FCC v. Fox, 556 U.S. 502
(2009), the controlling case on changes
in agency policy, is appropriate here.
The quote that commenters cite above,
asserting that an agency’s statutory
interpretation which conflicts with a
prior interpretation is ‘‘entitled to
considerably less deference than a
consistently held view,’’ is from
Thomas Jefferson University v. Shalala,
512 U.S. 504 (1994), a 1994 Supreme
Court case whose precedent on changes
in agency policy was displaced by FCC
v. Fox, in 2009, 556 U.S. 502. Under
FCC v. Fox, ‘‘it suffices that the new
policy is permissible under the statute,
that there are good reasons for it, and
that the agency believes it to be better,
which the conscious change of course
adequately indicates.’’ Id. at 515.
According to the commenters,
anything stored in a storage vessel
should be considered an alternative fuel
or raw material and therefore any
change in the liquid stored should be
exempt from being considered a
modification. We find in this final rule
that this interpretation of the alternative
fuel or raw material exemption as
applied to storage vessels is
inappropriate and often excludes
changes in the stored VOL that increase
emissions and that therefore should
trigger additional control requirements.
The EPA explained its rationale for
including additional modification
provisions in section III.G. of the
proposal preamble (88 FR 68543;
October 4, 2023). The EPA explained
that for purposes of NSPS subpart Kc, a
change in the liquid stored in the
storage vessel to an organic liquid with
a greater MTVP does not constitute a
‘‘use of an alternative fuel or raw
material’’ and would be considered a
change in the method of operation of the
storage vessel. The primary function of
this affected facility is the storage of
materials. The VOLs stored in the
storage vessel are neither raw material
nor fuel inputs to a process at the
affected facility itself. Furthermore,
even had the EPA not revisited its
interpretation regarding the application
of 40 CFR 60.14(e)(4), we maintain that
changing the VOL stored to one with a
higher MTVP is a modification (a
change in the method of operation that
results in an increase in the emissions
rate). The NSPS subpart Kc modification
provisions result in meaningful
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
emission reductions. For these reasons,
the final rulemaking appropriately
supersedes the general provisions. As
such, the EPA is finalizing modification
provisions such that a change in the
liquid stored, which results in increased
VOC emissions, would be a
modification under NSPS subpart Kc
and is clarifying in 40 CFR 60.110c(e)
that, for the purposes of this source
category, the exemption at 40 CFR
60.14(e)(4) does not apply.
The precedent of MTVP dependent
standards of performance for VOL
storage vessels was established as part
of NSPS subpart K and has informed the
establishment of standards for
subsequent rulemakings under NSPS
subparts Ka and Kb. Under these
standards, a VOL’s MTVP (along with a
vessel’s capacity) has served as a
primary mechanism for determining
suitable standards for control. The
amended modification provisions will
provide meaningful emission reductions
from storage vessels that would
otherwise go unregulated despite
satisfying the statutory criteria for a
modification under CAA section
111(a)(4), as explained in this section
and at III.G. of the proposal preamble
(88 FR 68543; October 4, 2023). The
modification provision, as amended,
effectively curtails a previously existing
loophole which had allowed owners
and operators to circumvent the
standards in NSPS subpart Kb. For
example, prior to this rulemaking, an
uncontrolled fixed roof vessel could be
constructed and be exempt from NSPS
subpart Kb standards because it was
storing a low vapor pressure VOL. The
vessel could then change operation to
introduce a new material with a higher
vapor pressure that would otherwise be
subject to the NSPS had it been stored
in the tank at the time of construction,
but the owner or operator could
continue to operate without meeting the
floating roof or closed vent system and
control device standards even if the
vessel was constructed after the Kb
applicability date. Similarly, if an owner
or operator built floating roof tanks for
VOLs with less than 11.1 psia and later
replaced the liquid stored with a liquid
with a vapor pressure greater than 11.1
psia, they could thereby circumvent the
closed vent system and control device
requirements under 40 CFR 60.112b
which are directly dependent on the
MTVP of the stored VOL and which
would otherwise apply. As such, the
prior NSPS provided significant leeway
for owners and operators to circumvent
the regulations intended to control
storage vessel emissions. To address this
concern, the EPA is finalizing
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
modification provisions such that the
MTVP can be used as an indicator to
determine that a change in the liquid
stored, which results in increased VOC
emissions, would be a modification
under NSPS subpart Kc.
The EPA’s decision to consider a
change in the liquid historically stored
or permitted to one with a higher vapor
pressure to be a modification is
consistent with both the statutory and
regulatory definitions of those terms.
CAA section 111(a) defines modification
to mean, ‘‘any physical change in, or
change in the method of operation of, a
stationary source which increases the
amount of any air pollutant emitted by
such source or which results in the
emission of any air pollutant not
previously emitted.’’ Similarly, the
General Provisions to 40 CFR part 60
define modification at 40 CFR 60.2 to
mean, ‘‘any physical change in, or
change in the method of operation of, an
existing facility which increases the
amount of any air pollutant (to which a
standard applies) emitted into the
atmosphere by that facility or which
results in the emission of any air
pollutant (to which a standard applies)
into the atmosphere not previously
emitted.’’ And 40 CFR 60.14 provides a
more detailed framework for evaluating
modifications, which similarly states at
paragraph (a) that: ‘‘Except as provided
under paragraphs (e) and (f) of this
section, any physical or operational
change to an existing facility which
results in an increase in the emission
rate to the atmosphere of any pollutant
to which a standard applies shall be
considered a modification within the
meaning of section 111 of the Act.’’
Thus, the CAA and general provisions
for 40 CFR part 60 all rely on the same
basic two-step process: (1) a physical
change in, or change in the method of
operation of, a stationary source; and (2)
a resulting increase in emissions.
Notably, it is not necessary for there to
be a physical change at the source in the
first step if there is a change in the
method of operation. One or the other
will suffice. We address each of these
criteria in turn.
First, as proposed, the EPA has
determined that a change in the liquid
stored in a storage vessel constitutes a
change in the method of operation of a
storage vessel. The primary function of
this affected facility is the storage of
materials, and so the only logical
‘‘change in the method of operation’’
that a storage vessel would undergo is
a change in the material stored. In other
words, whenever a storage vessel
changes the VOL that is stored, that is
a change in that facility’s method of
operation. The EPA’s interpretation
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
regarding what constitutes a change in
the ‘‘method of operation’’ for storage
vessels has not changed with this
rulemaking. In explaining the
applicability of modification under the
CAA, in the NSPS subpart Kb preamble,
the EPA affirmed, ‘‘Few, if any, changes
in the physical configuration of the
storage vessels that would increase
emissions are anticipated. An
operational change that would increase
emissions is a changing of the stored
liquid from a VOC non-emitting liquid
to a VOC emitting liquid’’ (49 FR 29707;
July 23, 1984). Thus, the EPA has long
considered the changing of the stored
liquid to meet the statutory
requirements for an operational change.
Second, the changing of the stored
liquid can lead to an increase of
emissions whenever the MTVP of the
new liquid is greater than the previously
stored liquid. Thus, both statutory
criteria for identifying a modification
are met.
The EPA agrees that we have
historically applied the regulatory
exemption under 60.14(e) for ‘‘use of an
alternative fuel or raw material’’ to
storage vessels. In making our decision
regarding modifications, we reviewed
several documents 7 and questioned
both industry and enforcement
personnel to better understand what
changes are currently considered
modifications. In the NSPS subpart Kb
preamble, the EPA explained, ‘‘Section
60.14(e) of the General Provisions to
Part 60 lists several changes that are not
considered modifications. Among these
is the use of raw material, if prior to the
date of proposal of the standard, the
existing facility was designed to
accommodate that alternative use’’ (49
FR 29707; July 23, 1984). However, the
EPA did not provide any further
explanation at that time as to why the
Agency believed this exemption applied
to this affected facility, and the Agency
has reconsidered the application of that
exemption for purposes of NSPS subpart
Kc. As explained in section III.G. of the
proposal preamble, when the affected
source is a storage vessel and not a
process unit, we no longer consider a
change in the liquid stored in the
storage vessel (to an organic liquid with
a higher MTVP) to qualify as a ‘‘use of
an alternative fuel or raw material.’’ As
discussed above, the primary function
of an affected facility in this source
category is the storage of materials, and
the VOL stored in the vessel are neither
7 See, e.g., U.S. EPA Applicability Determination
Index, Control Number: 0400015, (referencing 40
CFR 60.14(e)(4)–(5)) and NSPS subpart Kb
Background Information Document (Docket ID No.
EPA–HQ–OAR–2023–0358–0012).
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
raw material nor alternative fuel inputs
to a process at the facility itself. While
the storage vessel may store liquids that
are used as an alternative fuel or raw
material used for inputs to a process for
another facility, it is not reasonable to
extend application of the exemption to
mere storage of the alternative fuel or
raw material. Accordingly, we no longer
believe that the exemption should be
applied to these factual circumstances
by the terms of the regulation.
The EPA notes that, the fact that 40
CFR 60.14(e) is framed as exempting
certain activities from the definition of
modification indicates that, absent these
exemptions, the EPA would consider
the exempted activity to meet the
statutory definition of modification in
CAA section 111(a)(4). In other words,
the EPA created a specific provision
exempting the ‘‘use of an alternative
fuel or raw material’’ from the
regulatory definition of modification
because this activity would, as the EPA
proposed, typically be considered an
operational change,8 a consideration
reinforced by the EPA’s discussion on
modification in the NSPS subpart Kb
preamble. In this rulemaking, the EPA
confirms that it does not consider a
change in the liquid stored to one with
a higher MTVP to qualify under this
exemption. Moreover, irrespective of
this determination, the EPA is also
finalizing in this rulemaking that the
exemption in 40 CFR 60.14(e)(4)
regarding alternative fuel or raw
material does not apply to storage
vessels.
While we have determined for
purposes of NSPS subpart Kc that a
change in the liquid stored to a liquid
with a higher vapor pressure does not
constitute the ‘‘use of an alternative fuel
or raw material,’’ we note that even if
this exemption would otherwise apply
by its terms, this rulemaking supersedes
the exemption pursuant to 40 CFR
60.14(f), because, as explained earlier,
we have concluded that it is the better
policy and consistent with the statutory
definition of modification based on the
facts of how this affected facility
operates. The EPA has always
maintained that there are some sources
for which the basic exemptions from the
standard definition of a modification
may not be appropriate, and 40 CFR
8 This is bolstered when considering the other
exemptions in 40 CFR 60.14(e): a ‘‘replacement’’
referred to in (e)(1) and the addition of a system or
device referred to in (e)(5) is a physical change to
a facility, and an increase in production rate or an
increase in hours of operation referred to in (e)(2)
or (3) is a change in the facility’s operation.
However, the EPA had a rational basis for
exempting these particular physical or operational
changes, as a general matter, from the broader
definition of modification under the regulations.
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
83305
60.14(f) was included in the general
provisions to afford the EPA the ability
to supersede the general modification
regulations, the exemption provisions in
40 CFR 60.14(e), for those sources for
which these provisions should not
reasonably be applied. The EPA has
previously applied specialized
interpretations of modification for other
source categories. For example, in NSPS
subpart Ja, we included special
provisions for the modification of flares
at petroleum refineries because the basic
considerations under 40 CFR 60.14(e),
were generally developed considering
process unit emission sources. The
intermittent operation of a flare makes
it difficult to use the criteria of 40 CFR
60.14(e) to determine when a flare is
modified (73 FR 35843; June 24, 2008).
In our review of NSPS subpart Kb, we
identified similar short-comings
regarding the ‘‘process unit-oriented’’
modification exemptions as previously
applied to storage vessels. The
specialized modification provision for
storage vessels is consistent with the
CAA statutory requirements, the general
definition of modification outlined in 40
CFR 60.2 and 60.14, and previous
determinations that source-specific
modification provisions are justified for
certain source categories. Accordingly,
in this rulemaking, the EPA confirms
that it does not consider a change in the
liquid stored to one with a higher MTVP
to qualify under the exemption in 40
CFR 60.14(e)(4), and, as a matter of
clarity, irrespective of this
determination, this rulemaking is
superseding the exemption.
With respect to the comment that the
proposed definition of modification
would arbitrarily apply differently for
identical vessels based on their historic
use rather than their design capabilities,
we disagree. As stated above, the
modification provisions are directly
dependent on the MTVP of the stored
VOL. The precedent of MTVP
dependent standards of performance for
VOL storage vessels was established as
part of NSPS subpart K and has
informed the establishment of standards
for subsequent rulemakings under NSPS
subparts Ka and Kb. We are finalizing
that storing a VOL with a greater MTVP
than historically stored or permitted is
a modification. We determined the
BSER and set standards of performance
considering existing emission controls
of modified storage vessels.
The EPA also disagrees with the
comment advocating a requirement for
capital expenditure to determine
whether there is a modification and that
a capital expenditure clause should be
added to the language proposed at 40
CFR 110c(e). First, we note that the
E:\FR\FM\15OCR4.SGM
15OCR4
83306
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
statute at CAA section 111(a)(4)
contains no such requirement and the
general provisions at 40 CFR 60.14(e)(2)
only consider whether a capital
expenditure is needed when
considering an exemption from the
definition of modification tied to
increase in production at the facility.
Critically, neither the statute nor the
general provisions provide that the
determination of whether a modification
has occurred must be based on a capital
expenditure. Thus, the commenters seek
to impose an additional requirement
that is not plainly necessary under the
statute nor anticipated, either by
Congress or by the EPA, without an
explanation as to why that would be
justified for this source category. In
many cases, a capital expenditure is not
needed to change the liquid stored in a
fixed roof tank. Under the commenter’s
proposed capital expenditure paradigm,
an operator of a fixed roof tank used to
store a low volatility fluid could change
to a higher vapor pressure fluid and
argue that no modification occurred
even though the storage vessel has
changed its method of operation. This
would permit the resulting emissions
increases without the requisite control
that the statute would otherwise
anticipate under such circumstances. It
is more consistent with the statutory
standard to consider the change in the
liquid stored or permitted as a change
in the method of operation and then
assess whether an increase in the vapor
pressure of the liquid stored triggers the
need for controls (which would require
a capital expenditure). We found the
controls required under proposed NSPS
subpart Kc are cost effective and meet
the BSER criteria, and we see no reason
to allow uncontrolled modified storage
vessels or less stringent controls simply
because the tank was initially permitted
for or stored a less volatile liquid.
4. Control Standards for IFRs and EFRs
The EPA proposed standards of
performance that reflect the BSER for
IFRs as well as alternative compliance
standards for controlled storage vessel
EFRs. The EPA proposed a work
practice standard that would require
new IFR storage vessels be constructed
with either a liquid-mounted or a
mechanical shoe primary seal, a rimmounted secondary seal, and fittings on
the floating roof that meet certain
control requirements (e.g., gasketed
covers, specific guidepole control
configurations) mostly consistent with
the requirements of fitting controls in
NSPS subpart Kb. The EPA also
proposed that new EFR storage vessels
be constructed with either a liquidmounted or a mechanical shoe primary
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
seal, a rim-mounted secondary seal,
welded deck seams, and fittings on the
floating roof that meet certain control
requirements (e.g., gasketed covers,
specific guidepole control
configurations). Except for the
guidepole controls, the fitting controls
are mostly consistent with the
requirements of fitting controls in NSPS
subpart Kb.
We are finalizing the control
requirements for IFRs and EFRs as
proposed with minor editorial revisions
(such as replacing ‘‘roof leg supports’’
with ‘‘roof supports,’’ replacing
‘‘bolted’’ with ‘‘bolted or otherwise
mechanically secured,’’ and using
consistent language regarding
requirements for vacuum breaker/
automatic bleeder vents). For EFRs, we
are also adding provisions for
emergency roof drains to be provided
with a slotted membrane fabric cover
that covers at least 90 percent of the area
of the opening. As noted by
commenters, this provision is included
in NSPS subpart Kb and the IFR drain
requirements were inadvertently copied
for EFRs in the proposed rule for NSPS
subpart Kc.
Comment: One commenter stated the
proposed NSPS subpart Kc language
refers to the floating roof being
supported by legs when the floating roof
is landed, but a common design for IFRs
involves suspending the IFR from the
fixed roof of the tank via cables. The
commenter stated that proposed
language at 40 CFR 60.112c(b)(1) and (4)
should be revised to accommodate the
cable-suspended design alternative.
Similarly, a commenter recommended
the EPA revise the definition of the term
‘‘Vacuum breaker/Automatic bleeder
vent’’ to avoid restricting vacuum
breakers to the leg-actuated type.
Another commenter noted that since leg
operated vacuum breakers must contact
the floor prior to the roof support legs,
the EPA should consider setting a
maximum opening distance or clarify
that the roof is considered landed when
the vacuum breaker leg lands. One
commenter noted that 40 CFR
60.112c(b)(1) reads ‘‘. . . and during
those intervals when the storage vessel
is completely emptied or subsequently
emptied and refilled’’ whereas 40 CFR
60.112c(c)(1) reads: ‘‘. . . and when the
storage vessel is completely emptied
and subsequently refilled.’’ The
commenter suggested that the
requirements for EFRs in 40 CFR
60.112c(c)(1) be revised to be consistent
with 40 CFR 60.112c(b)(1).
Response: We agree with the
commenters that the language regarding
roof legs and vacuum breaker/automatic
bleeder vents should be generalized to
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
allow roof supports other than roof legs
and vacuum actuations other than leg
actuated devices and that consistent
language should be used for EFRs.
While we understand cable suspended
roofs are specific to IFRs, we
generalized the language for EFRs in the
event different supports are developed
for EFRs and to make the language
consistent between 40 CFR 60.112c(b)
and (c). We also revised the use of the
term ‘‘vacuum breaker’’ by replacing it
with ‘‘vacuum breaker/automatic
bleeder vent’’ because that is the
defined term for these devices on a
floating roof and to distinguish these
from vacuum breaking devices on a
fixed roof. We are also adding a
sentence to the roof landing monitoring
requirements at 40 CFR 60.113c(a)(5)
and (b)(8) to clarify that the roof is
considered landed when the floating
roof first rests on supports or when the
vacuum breaker/automatic bleeder vent
begins to open, whichever is first. This
clarifies that the landing alarm must be
set at the height the leg-actuated
vacuum breaker/automatic bleeder vent
begins to open the vent, which will be
prior to the floating roof resting on the
roof supports.
Comment: One commenter stated that
the proposed NSPS subpart Kc does not
address the emergency roof drains that
are utilized with certain EFRs. The
commenter noted that NSPS subpart Kc
specifies that ‘‘stub drains’’ are not
required to be covered at all, which
could be understood as exempting EFR
emergency roof drains from control. The
commenter recommended that the EPA
clarify, consistent with NSPS subpart
Kb at 40 CFR 60.112(b)(2)(ii), that each
emergency roof drain is to be provided
with a slotted membrane fabric cover
that covers at least 90 percent of the area
of the opening.
Response: We agree with the
commenter that we inadvertently used
the language allowing uncontrolled stub
drains for IFRs in the proposed EFR
requirements. We had intended to
maintain consistency with the EFR
drain requirements in NSPS subpart Kb.
We agree with the commenter that the
reference to stub drains for EFRs is not
appropriate as stub drains are not used
for EFRs. In the final rule, we are
including the requirements to use a
slotted membrane fabric cover that
covers at least 90 percent of the area of
the opening at 40 CFR 60.112c(c)(2)(viii)
consistent with the requirements for
EFR drains in NSPS subpart Kb, as
suggested by the commenter.
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
5. Control Standards for Closed Vent
Systems Routed to a Control Device,
Fuel Gas System, or Process
For storage vessels with closed vent
systems routed to a control device, fuel
gas system, or process, the EPA
proposed certain design requirements
for the storage vessel to prevent pressure
releases from the storage vessel and
proposed that control devices must meet
98 percent or greater emission reduction
efficiency. The EPA proposed that nonflare thermal combustion devices must
conduct performance tests initially and
at least once every 60 months, in which
they establish a temperature operating
limit to which they must comply at all
times. For flares, the EPA proposed that
flares must meet the operating and
monitoring requirements consistent
with the requirements in the Refinery
NESHAP (40 CFR 63.670 and 63.671).
We are finalizing requirements for
closed vent systems routed to a control
device, fuel gas system, or process with
some revisions from proposal for
reasons noted in the following
comments and responses.
First, we are revising the vacuum
pressure at which vacuum breaking
devices must close from ¥0.1 pounds
per square inch gauge (psig) to ¥0.1
inches of water (¥0.0036 psig) to better
reflect common storage vessel design
requirements. We are also clarifying the
language since a higher vacuum setting
would be a lower absolute pressure and
the proposed language was potentially
ambiguous. The revised provision
clarifies that any vacuum breaking
device on the storage vessel must close
while the storage vessel is still under
vacuum of at least ¥0.1 inches of water
(¥0.0036 psig or ¥0.025 kPa gauge).
We proposed that storage vessels that
are vented to a closed vent system must
be designed to operate at elevated
pressures (1 psig above MTVP plus any
back pressure from the control device)
without venting to the atmosphere. We
are retaining this as an option but are
adding an option to design and operate
the recovery system to prevent venting
from the storage vessel. In either case,
we are retaining requirements consistent
with those proposed that monitoring
systems must be installed to detect
pressure releases from each pressure
relief device (PRD) or vacuum breaking
device on a storage vessel and each PRD
on the closed vent system. For owner
and operators electing to design the
storage vessel and closed vent system to
operate at elevated pressures, we are
including provisions that allow the
control device to be taken out of service
for maintenance provided that the
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
storage vessels are operated with no
emissions to the atmosphere.
We are retaining requirements for
control devices to meet 98 percent
control efficiencies as proposed. We
allow enclosed combustion devices to
demonstrate on-going compliance with
the 98 percent control efficiency using
temperature operating limit, as
proposed. However, we are also
finalizing an alternative for enclosed
combustion devices, if elected, to
comply with the flare operating limits,
consistent with recent provisions
provided for gasoline distribution
facilities (40 CFR part 60, subpart XXa
and 40 CFR part 63, subparts R and
BBBBBB). Lastly, we are amending the
requirements for open-ended lines to
align with provisions more closely
under the Miscellaneous Organic
Chemical Manufacturing NESHAP
(MON).
Comment: Two commenters suggested
that the pressure constraints on design
operating pressure and vacuum breaking
devices are not technically feasible and
could result in significant damage or
failures of the storage vessels, stating
that a gauge pressure higher than the
designed pressure of the storage vessel
or a vacuum greater than the design
requirements could result in
catastrophic failure of the storage vessel.
The commenters noted that the
proposed requirements conflict with
American Petroleum Institute (API)
Codes 650 and 2000. The commenters
recommended the EPA delete the
specific pressure requirements proposed
and replace with general language that
atmospheric vents should be designed
to remain closed during normal
operation.
Response: In the proposal, we
intended to require the use of lowpressure storage vessels rather than
atmospheric storage vessels so that the
storage vessels would be built to
withstand higher pressures. However,
we recognize that this may be a more
significant retrofit for modified storage
vessels with gas collection systems
designed to operate at lower pressures
such that the pressure in the storage
vessels can remain near atmospheric
pressure. However, if the vapor recovery
compressor or fan fails or is shut down
for any reason, then the storage vessel
would vent rather than being able to
withstand the buildup of pressure as the
headspace in the storage vessel reaches
saturation without venting to the
atmosphere like a low-pressure storage
vessel would. We are maintaining the
positive pressure requirements as one
compliance option, but we are also
finalizing an option for facilities to
design and operate a vapor recovery
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
83307
system in a manner to prevent
atmospheric releases from the storage
vessel. As proposed, any pressure
release from the storage vessel is a
deviation of the storage vessel and
closed vent system requirements. We
are finalizing monitoring system
requirements for the pressure relief
devices and vacuum breaking devices to
identify these deviations.
With respect to the vacuum
requirements, we reviewed the API 650
standards applicable to low-pressure
storage vessels and found in section
5.10.5.2 that these storage vessels ‘‘. . .
may be safely subjected to a partial
vacuum in the gas or vapor space not
exceeding 1 ounce per square inch with
the operating liquid level in the tank at
any stage from full to empty.’’ One
ounce per square inch is equivalent to
0.0625 psi or 2 inches of water, so we
agree that the vacuum requirement
proposed is beyond standard design
requirements for low-pressure storage
vessels. We also confirmed that the API
650 standard indicates that the
maximum vacuum for atmospheric
storage vessels (without needing
additional design considerations) is
¥0.25 kPa (or ¥1 inch of water or
¥0.036 psig). In our proposal, we
wanted to ensure that the vacuum vent
is closed while there is still a slight
vacuum in the storage vessel, to prevent
venting to the atmosphere from the
vacuum breaking device as the pressure
in the storage vessel increases. In
reviewing the storage vessel
specifications, we determined that the
value we proposed was higher than
needed to achieve this objective. The
vacuum breaking devices must open
before the maximum vacuum pressure is
reached, so typical opening pressures
are 0.5 inches of water pressure.
Therefore, we are finalizing that the
vacuum breaking device must close
while the storage vessel is still under
vacuum of at least ¥0.1 inches of water
(¥0.0036 psig or ¥0.025 kPa gauge)
and are finalizing that a pressure release
(deviation) occurs when the vessel
reaches atmospheric pressure and the
vacuum breaking device remains open.
We are providing separate paragraphs
for the monitoring requirements for
PRDs between storage vessels and
closed vent systems and adding
monitoring requirements for the vacuum
breaking devices on the storage vessels.
Otherwise, the separate pressure release
monitoring requirements we are
finalizing in 40 CFR 60.112c(d)(1)(iii)
and (d)(2)(iii) are the same as proposed
for ‘‘each pressure relief device on a
storage vessel or in a closed vent
system,’’ in 40 CFR 60.112c(d)(2)(iii).
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83308
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
Comment: One commenter
recommended that the EPA add a 240hour planned routine maintenance
provision for storage vessels equipped
with a closed vent system routed to a
control device to NSPS subparts Kb and
Kc similar to the language in the part 63
NESHAP regulations such as the MON
and Organic Liquids Distribution (nongasoline) NESHAP. According to the
commenter, if the EPA decides to retain
the language in 40 CFR 60.110c(g)
removing the SSM provisions, it is
reasonable for the EPA to include a
separate 240-hour planned routine
maintenance provision for control
devices in NSPS subpart Kc similar to
the language in the MON (40 CFR
63.2470(d)) and the associated
recordkeeping and reporting
requirement similar to the language in
40 CFR 63.998(d)(2) and 63.999(c)(4).
Response: We disagree that we should
provide 240 hours for uncontrolled
emissions when using an add-on control
device. Similar provisions are not
needed or appropriate for IFRs, which
were determined to be the BSER for
storage vessels storing VOLs with an
MTVP less than 11.1 psia. We maintain
that a 98 percent control requirement at
all times is necessary for add-on control
devices to achieve emission reductions
equivalent to those for IFRs. Even for
storage vessels storing VOLs with an
MTVP of 11.1 psia or higher, we
maintain that a 98 percent control
requirement is the BSER, and that level
of control cannot be achieved if we
allow 240 hours of uncontrolled
emissions. Nonetheless, if the storage
vessel is designed to be able to operate
at pressures above the MTVP consistent
with the storage vessel design pressure
requirements proposed (and being
finalized as one compliance option),
then the control device can be isolated
from the storage vessel, and the closed
vent system and the storage vessel can
remain in service without venting to the
atmosphere provided that the storage
vessel is not filled to the extent that the
pressure limits of the pressure relief
valves on the storage vessel and closed
vent system are exceeded and there is a
pressure release. If there is no pressure
release from the storage vessel during
the planned maintenance activity, we
agree that planned maintenance can be
allowed. Therefore, we are including
provisions at 40 CFR 60.112c(d)(7) to
allow owners or operators to conduct
planned maintenance on control devices
while storage vessel affected facilities
are still storing VOL under specific
circumstances. Specifically, the storage
vessel(s) storing VOL must be designed
to operate above the MTVP of the stored
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
VOL according to the requirements in
40 CFR 60.112c(d)(1)(i) and must
comply with the pressure release
monitoring, recordkeeping, and
reporting requirements. Eliminating
pressure releases during the
maintenance periods may require
operators to limit VOL addition to the
storage vessel (such as only adding VOL
when there is also corresponding
withdrawal of VOL from the storage
vessel), but the operator is expected to
operate the storage vessel without a
pressure release or atmospheric venting
during the maintenance period.
Comment: One commenter stated that
the EPA should define ‘‘vapor
combustion unit’’ separately from
‘‘incinerator’’ and apply appropriate
monitoring provisions to vapor
combustion units (VCUs) to avoid
subjecting VCUs to inappropriate
requirements. The commenter stated
that the EPA should allow VCUs to elect
to meet the proposed flare provisions, as
was provided in the Gasoline
Distribution rules.
Response: In general, we agree with
the commenter. We note that we had
proposed specific requirements for
‘‘enclosed combustion devices’’ so we
elected to define that term. We
recognize that some enclosed
combustion devices may operate more
like a flare than like an incinerator (no
direct combustion chamber and no
means to control the amount of air
entering the device). In similar
situations in other rules (gasoline
distribution rules at 40 CFR part 60,
subpart XXa, and 40 CFR part 63,
subparts R and BBBBBB, and the oil and
gas rule at 40 CFR part 60, subparts
OOOOb and OOOOc), we have allowed
the enclosed combustion devices to
comply with the flare operating limits
rather than with the temperature
operating limit. As such, we agree with
the commenter’s suggestion to allow
enclosed combustion devices to comply
with the flare operating limits. We have
added a definition of both ‘‘enclosed
combustion device’’ and ‘‘flare’’ to help
distinguish between these devices
(enclosed combustion devices emit
pollutants through a conveyance
suitable to conduct a performance test,
and flares have open or shrouded flames
and do not emit pollutants through a
conveyance suitable to conduct a
performance test). We note that the
implementation of this provision led to
revision of several paragraphs related to
control device operating limits and
monitoring, recordkeeping, and
reporting requirements to allow
‘‘enclosed combustion devices electing
to comply with § 60.112c(d)(5)’’ to be
treated differently than other non-flare
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
combustion devices. We are retaining
the requirement for enclosed
combustion devices to conduct a
performance test to demonstrate that the
enclosed combustion device is
achieving a 98 percent VOC emission
reduction regardless of whether the
enclosed combustion device is
complying with the flare operating
limits in 40 CFR 60.112c(d)(5) or the
temperature operating limits in 40 CFR
60.113c(c)(1)(ii)(E).
Comment: One commenter stated that
the EPA should clarify in the final NSPS
subpart Kc rule, in the closed vent
system and bypass line provisions, that
open-ended valves or lines that use a
cap, blind flange, plug, or second valve
are not considered to be bypass lines.
According to the commenter, the EPA
should add the text that is in 40 CFR
63.2450(e)(6)(v)(B) of the MON rule to
40 CFR 60.112c(d)(2)(ii) to clearly
exempt these open-ended valves or lines
from the bypass requirements.
Response: We agree with the
recommendations to align NSPS subpart
Kc more closely with the provisions in
the MON regarding open-ended valves
or lines that use a cap, blind flange,
plug, or second valve, and have revised
to 40 CFR 60.112c(d)(2)(ii) accordingly.
6. Control Standards for Degassing
Based on the analysis presented at
proposal, the EPA proposed emptying
and degassing standards in accordance
with the BSER applicable to: (1) storage
vessels equipped with a closed vent
system routed to a control device, fuel
gas system, or process; and (2) IFR and
EFR storage vessels that have a capacity
of greater than or equal to 1 million
gallons storing a VOL with an MTVP
greater than or equal to 1.5 psia. These
vessels must meet certain requirements
while the vapors in the storage vessel
are at or above 10 percent of the LEL.
The proposed standards of performance
for degassing emissions reflect a 98
percent VOC reduction efficiency.
Regarding degassing controls, we are
finalizing these provisions with minor
revisions to what was proposed. We are
finalizing standards for storage vessels
subject to controlling degassing
emissions as proposed. We are
finalizing a requirement that controls
must be used until the vapor space
concentration is less than 10 percent of
the LEL, as proposed, but we are also
finalizing provisions for nonflammable
liquids to comply with a 5,000 ppmv as
methane concentration level based on
comments received, because 5,000
ppmv is equal to 10 percent LEL if the
vapors were methane. We are finalizing
that the degassing emissions that must
be controlled must be vented to control
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
device that achieves a 98 weight percent
VOC reduction or greater as proposed.
We are finalizing additional provisions
to check LEL instrument calibration and
instrumental offset response each day
the instrument is used and prior to
discontinuing controlled degassing
consistent with LEL measurement
requirements for IFR monitoring to
ensure the accuracy of the instrument
readings. We are also finalizing
provisions that allow the introduction of
chemicals or diluents for the purpose of
reducing vapor concentration before or
during active degassing, after
considering comments received.
Comment: Two commenters stated
that the EPA should incorporate a
concentration limit for the storage vessel
degassing emissions in 40 CFR
60.112c(e) since nonflammable
chemicals do not exhibit an LEL. The
commenter requested that the EPA
include a concentration limit of less
than 5,000 ppmv as methane as an
alternative to the LEL requirement,
consistent with the National Emission
Standards for Organic Hazardous Air
Pollutants From the Synthetic Organic
Chemical Manufacturing Industry
proposal.
Response: We expect that most VOLs
with an MTVP above 1.5 psia will have
some flammability, but we agree that a
concentration limit of 5,000 ppmv as
methane for nonflammable liquids is
appropriate because 5,000 ppmv is the
10 percent LEL of methane and it
generally provides a concentration value
that is similar to or lower than the 10
percent LEL level for heavier organics.
For example, 10 percent LEL of butane
is as stringent as or more stringent than
1,900 ppmv as butane or about 7,600
ppmv as methane.
Comment: One commenter noted that
some companies flood the bottom of the
tank with a low vapor pressure material
to facilitate removal of residual sludges
and/or to reduce the concentration of
vapors in the vapor space of the tank
prior to or during active degassing.
According to the commenter, while the
proposed rule language does not
prohibit bottom flushing, this practice
should be expressly accommodated in
the rule language.
Response: We agree that flooding the
bottom of the tank with a low vapor
pressure material is a reasonable control
measure for degassing. As such, we are
revising 40 CFR 60.112c(e)(1) to
expressly allow the addition of chemical
or a diluent for the purpose of reducing
vapor concentration before or during
active degassing.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
7. Alternative Means of Emission
Limitation
We are finalizing the alternative
means of emissions limitation (AMEL)
provisions as proposed except for the
addition of two clarifications. First, at
40 CFR 60.114c(a), we are replacing
‘‘any’’ with ‘‘the applicable’’ when
referencing requirements in 40 CFR
60.112c, to clarify that the equivalency
must be made for the same type of
control system (IFR, EFR, or closed vent
system routed to a control device, fuel
gas system, or process). This
clarification prevents operators that are
using an IFR from reducing the fitting
control requirements finalized for an
IFR because, for that size of storage
vessel and stored VOL, the required IFR
controls achieve greater than a 98
percent reduction or greater reduction
than an EFR meeting the final EFR
requirements. Second, we are clarifying
that the written application to the
Administrator in 40 CFR 60.114c(c) may
include either actual emissions test
results or an engineering evaluation that
the Administrator determines to be
accurate, but it does not necessarily
have to include both.
Comment: One commenter noted the
proposed NSPS subpart Kc provides for
requesting an AMEL at 40 CFR 60.114c
and this section specifies that a request
for approval of an alternative must
include an actual emissions test;
however, there are numerous alternative
control measures that have already been
tested and for which the EPA has
published emission factors in AP–42.
The commenter stated that the EPA
should not arbitrarily require repeated
testing for those control measures that
have already been tested and for which
the results have already been accepted
by the EPA. The commenter stated that
the language in 40 CFR 60.114c should
be replaced with the language in
NESHAP subpart WW at 40 CFR
63.1064.
Response: We have revised 40 CFR
60.114c(c) such that an AMEL written
application must include either an
actual emissions test (that covers the
appropriate range of meteorological
conditions) or an engineering
evaluation, which may include use of
emission factors as published in the
EPA Report No. AP–42, Compilation of
Air Pollutant Emission Factors. We
reviewed the AMEL provision in
NESHAP subpart WW. The NESHAP
subpart WW provisions include a listing
of test methods but do not limit the
testing to those methods. As such, we
are determining that the language that is
included in the final rule is equivalent
to the provisions in NESHAP subpart
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
83309
WW. We also note that the provisions in
40 CFR 63.1064(c) allow the use of
different combinations of rim and deck
fitting controls ‘‘. . . if the alternate
emits no more than the combination
specified in the § 63.1063.’’ We interpret
this provision to allow comparisons of
fitting controls for IFRs to those
required specifically for IFRs. While we
consider that the three control options
we provided are equivalent, we
acknowledge that, depending on the
size of tank, volatility of the VOL, and
prevailing meteorological conditions,
one of the control configurations (IFR,
EFR, or closed vent system routed to a
control device, fuel gas system, or
process) will perform better and one
configuration will perform worse than
the other options allowed. We did not
intend to allow changes to the specified
control provisions to only require the
lowest control efficiency for a given
combination of tank size, VOL stored,
and meteorological conditions.
Therefore, we are also clarifying,
consistent with our interpretation of the
NESHAP subpart WW provisions, that
the AMEL must compare with the
‘‘applicable’’ requirement. That is, for
storage vessels with IFRs, you may
request an AMEL for a different set of
fittings, but you must show equivalency
with the IFR requirements specified in
40 CFR 60.112c(b). For storage vessels
with EFRs, the AMEL must show
equivalency with the EFR requirements
specified in 40 CFR 60.112c(c). For
storage vessels with a closed vent
system routed to a control device, fuel
gas system, or process, the AMEL must
show equivalency with the control
requirements specified in 40 CFR
60.112c(d). With these revisions, we
determine that the final AMEL
provisions in NSPS subpart Kc are
consistent with the AMEL provisions in
NESHAP subpart WW.
Since control measures that were
determined to be equivalent to NSPS
subpart Kb may not be equivalent to
controls required under NSPS subpart
Kc, a new AMEL application must be
submitted following 40 CFR 60.114c(c)
in order to demonstrate that an AMEL
is equivalent to the requirements in
NSPS subpart Kc.
C. NSPS Subpart Kc Without Startup,
Shutdown, and Malfunction Exemptions
Consistent with Sierra Club v. EPA,
551 F.3d 1019 (D.C. Cir. 2008), the EPA
has established standards in this rule
that apply at all times. We are finalizing
in NSPS subpart Kc specific
requirements at 40 CFR 60.110c(g) that
override the general provisions for SSM
requirements. In finalizing the standards
in this rule, the EPA has considered
E:\FR\FM\15OCR4.SGM
15OCR4
83310
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
startup and shutdown periods and, for
the reasons explained in this section of
the preamble, has not finalized alternate
standards for those periods. The EPA
has determined that the reasoning in the
court’s decision in Sierra Club applies
equally to CAA section 111 because the
definition of ‘‘emission standard’’ in
CAA section 302(k), and the embedded
requirement for continuous standards,
also applies to the NSPS.
Periods of startup, normal operations,
and shutdown are all predictable and
routine aspects of a source’s operations.
Malfunctions, in contrast, are neither
predictable nor routine. Instead, they
are, by definition, sudden, infrequent,
and not reasonably preventable failures
of emissions control, process, or
monitoring equipment (40 CFR 60.2).
The EPA interprets CAA section 111 as
not requiring emissions that occur
during periods of malfunction to be
factored into development of CAA
section 111 standards. Nothing in CAA
section 111 or in caselaw requires that
the EPA consider malfunctions when
determining what standards of
performance reflect the degree of
emission limitation achievable through
‘‘the application of the best system of
emission reduction’’ that the EPA
determines is adequately demonstrated.
While the EPA accounts for variability
in setting emissions standards, nothing
in CAA section 111 requires the Agency
to consider malfunctions as part of that
analysis. The EPA is not required to
treat a malfunction in the same manner
as the type of variation in performance
that occurs during routine operations of
a source. A malfunction is a failure of
the source to perform in a ‘‘normal or
usual manner,’’ and no statutory
language compels the EPA to consider
such events in setting CAA section 111
standards of performance. The EPA’s
approach to malfunctions in the
analogous circumstances (setting
‘‘achievable’’ standards under CAA
section 112) has been upheld as
reasonable by the D.C. Circuit in U.S.
Sugar Corp. v. EPA, 830 F.3d 579, 606–
610 (2016).
D. Testing, Monitoring, and Inspection
Requirements
Because the NSPS reflect the BSER
under conditions of proper operation
and maintenance, we also, in
performing our review, evaluate and
determine the proper testing,
monitoring, inspection, recordkeeping,
and reporting requirements needed to
ensure compliance with the emission
standards. This section of the preamble
includes our discussion of the proposed
revisions to testing, monitoring, and
inspection requirements, a summary of
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
the significant comments received, our
responses to the comments, and our
final determinations regarding testing,
monitoring, and inspection
requirements. Changes to recordkeeping
and reporting requirements are included
in the section for recordkeeping and
electronic reporting.
Generally, we proposed testing,
monitoring, and inspection
requirements consistent with those in
NSPS subpart Kb and other Federal
standards that would provide the best
clarity for the specific requirements
along with the following enhancements.
The EPA proposed annual LEL
monitoring as an enhancement to the
monitoring and inspection requirements
for storage vessels with IFRs. The EPA
also proposed equipping floating roof
storage vessels with a visual or audible
alarm system to monitor when the
floating roof approaches specified
landing heights. For closed vent
systems, the EPA proposed quarterly
AVO inspections, annual EPA Method
21 instrument monitoring, and
monitoring of bypasses. The EPA also
proposed that storage vessels using
closed vent systems routed to control
devices, fuel gas systems, or processes
must equip pressure relief devices with
appropriate monitoring to identify
releases. For storage vessels with closed
vent systems routed to a control device,
the EPA proposed that performance
tests must be conducted at least once
every 60 months rather than rely on a
single initial performance test. Finally,
the EPA proposed enhanced monitoring
requirements for flares consistent with
the Refinery NESHAP (40 CFR 63.671).
We are finalizing testing, monitoring,
and inspection requirements as
proposed except for the revisions
outlined here.
• We revised the specification of the
timing of these requirements to be
‘‘calendar months’’ rather than just
‘‘months,’’ to clarify the timing and
allow limited flexibility when
scheduling the required testing or
inspections.
• For IFRs, we are amending the
requirements to conduct internal
inspections of the floating roof at least
once every 120 calendar months. We are
retaining this inspection requirement
each time the vessel is emptied and
degassed, but we are not requiring
storage vessels to be taken out of service
specifically to conduct this inspection.
• We are making minor revisions to
the LEL monitoring calibration
procedures. We proposed language used
from the gasoline distribution rule (40
CFR part 63, subpart R), which would
require the correction factor to be based
on ‘‘gasoline vapor.’’ Because NSPS
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
subpart Kc is applicable to a much
broader range of chemicals, we are
revising references to ‘‘gasoline vapors’’
to ‘‘vapors of the stored VOL.’’ We are
retaining the use of butane as the
surrogate if correction factors are not
available for the vapors of the VOL
stored.
• We are adding specific
requirements that fittings on EFR must
be visually inspected during annual seal
gap measurement inspections to ensure
that covers are closed and gasketed with
no visible gaps and that there are no
tears in sleeves, wipers, or similar
controls used for a given fitting during
annual seal gap measurement
inspections. Visual fitting inspections
were proposed at 40 CFR 60.113c(b)(7)
for inspections conducted when the
storage vessel is emptied and degassed
but did not specify fitting conditions
that would result in an inspection
failure, and we are adding these details
to clarify the fitting inspection
requirements based on comments
received.
• For closed vent systems, we are
including an additional reference at 40
CFR 60.113c(c)(2) for the quarterly AVO
monitoring as required under both the
proposed and final requirements at 40
CFR 60.112c(d)(2)(i). We are also
revising the provision of 40 CFR
60.113c(c)(3) to clarify that emissions
detected using visible, audible, and
olfactory methods are leaks triggering
corrective action.
• Regarding MTVP test methods, we
are clarifying that owners and operators
must determine the MTVP of the VOL
prior to refilling the storage vessel with
a new VOL. The proposed language only
referenced ‘‘initial filling’’ and may
allow facilities to change VOL without
reassessing the MTVP. However, we
considered that, when a new VOL is
stored, that would be an initial filling of
that VOL. The rephrasing of that
provision helps to clarify this
requirement. Additionally, we are
adding a requirement to use a vapor-toliquid ratio of 4:1 when using American
Society for Testing and Materials
(ASTM) D6378–22. We proposed this
requirement when using ASTM D6377–
20 but consider that the same provision
should apply to both of the MTVP test
methods. The EPA’s intention to use a
vapor-to-liquid ratio of 4:1 when using
ASTM D6378–22 was detailed in the
proposal preamble but was erroneously
omitted from the proposed rule text.
• Additionally, as noted in section
IV.B.5. of this preamble, we are allowing
enclosed combustion devices to comply
with the monitoring provisions for flares
as an alternative to the temperature
monitoring requirement.
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
Comment: One commenter stated that
the EPA’s proposed monitoring and
inspection requirements for floating roof
tanks are inadequate and must be
strengthened to make it more likely that
the tanks can reduce 98 percent of
VOCs. According to the commenter, at
a minimum, the EPA must require
monitoring and inspection in keeping
with the current requirements from
South Coast Air Quality Management
District (SCAQMD) Rule 1178. In
addition, the commenter stated that the
EPA must make it explicit that, for IFR
visual inspections, the entire perimeter
of the floating roof seal must be visually
evaluated, even if that requires opening
multiple manways. The commenter
stated that the EPA must also require
quarterly forward-looking infrared
measurements from tank decks.
Response: In general, we considered
that we had incorporated much from the
SCAQMD Rule 1178 monitoring
provisions in our proposal. We included
LEL monitoring provisions for IFR
storage vessels and PRD monitoring
provisions for storage vessels with
closed vent systems routed to a control
device, fuel gas system, or process that
are reasonably consistent with the
monitoring requirements in SCAQMD
Rule 1178. However, upon further
review of SCAQMD Rule 1178 and our
proposed inspection requirements, we
noted that the inspection requirements
we proposed for EFR storage vessels
only covered inspections of the primary
and secondary seals. Visual fitting
inspections were proposed for IFR
inspections and mentioned in the
proposed inspections at 40 CFR
60.113c(b)(7) when the storage vessel is
emptied and degassed. However, no
requirement for fitting inspections were
proposed during annual gap
measurements, and the inspections
proposed at 40 CFR 60.113c(b)(7) did
not specify fitting conditions that would
result in an inspection failure. After our
review of SCAQMD Rule 1178
monitoring and inspection requirements
based on this comment, we are adding
specific requirements that fittings on
EFR must be visually inspected during
annual seal gap measurement
inspections to ensure that covers are
closed and gasketed with no visible gaps
and that there are no tears in sleeves,
wipers, or similar controls used for a
given fitting. We are also adding the
conditions under which an inspection
failure occurs for the inspections
conducted when the EFR storage vessel
is emptied and degassed.
We considered optical gas imaging
requirements in previous reviews of
storage vessels, which we reviewed
again for NSPS subpart Kc, and
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
concluded that these requirements were
not cost-effective. Regarding manways,
we agree with the commenter’s assertion
that while performing IFR visual
inspections, the entire perimeter of the
floating roof seal must be visually
evaluated, even if that requires opening
multiple manways. We have elected not
to add specific rule language, because
we believe that having visual access to
the entire primary seal, is already a
necessary component of annual IFR
inspections both in the rule language of
NSPS subpart Kc and in the existing
rule language of NSPS subpart Kb. As
such, except for the specifications for
fitting inspections for EFR storage
vessels, we are not adding additional
monitoring requirements to NSPS
subpart Kc.
Comment: Numerous commenters
requested that the EPA allow in-service
inspections of IFRs either by providing
additional language in 40 CFR
60.113c(a)(2) allowing for top-side
inspections when there is visual access
to all deck components or by
incorporating an alternate means of
compliance option to comply with
NESHAP subpart WW [40 CFR
63.1063(d)(1) and (2)]. The commenters
noted that in-service inspections were
allowed in NSPS subpart Kb to avoid
the costs and emissions associated with
emptying and degassing vessels for
inspection. If in-service inspections are
provided, the commenters noted, rule
revisions may also be needed in the
notification requirements at 40 CFR
60.116c(b)(1) and the reporting
requirements at 40 CFR 60.116c(c)(2)(ii).
Response: We had proposed language
consistent with NSPS subpart Kb at 40
CFR 60.113b(a)(4) to require more
detailed ‘‘out of service’’ inspections at
least once every 10 years. The EPA
agrees with the commenter’s request to
allow for in-service inspections to be
performed entirely from the top side of
the floating roof. The EPA is
incorporating language into 40 CFR
60.113c(a)(2)(ii) to allow for in-service
inspections to be performed entirely
from the top side of the floating roof, as
long as there is visual access to all deck
fittings and rim seal systems specified
in 40 CFR 60.112c(b). We are also
adding repair timelines in 40 CFR
60.112c(b), similar to those already
established for the annual visual
inspection. We are also specifying that
a 30-day notification must be provided
for inspections in 40 CFR 60.116c(b)(1).
Also, we are deleting the phrase
‘‘emptied and degassed and’’ from 40
CFR 60.116c(c)(2)(iii) to account for the
reporting of these in-service inspections.
Comment: One commenter stated that
the calibration requirements for the LEL
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
83311
meter in 40 CFR 60.113c(a)(3)(ii) and
(iv) that are specified for demonstrating
compliance with the 25 percent LEL
limit for IFR storage vessels are
burdensome and should be simplified to
be consistent with the calibration
requirements for the LEL meter within
the storage vessel degassing
requirements in 40 CFR 60.112c(e). The
commenter stated that following the
procedures for ‘‘calibration and
maintenance according to
manufacturer’s specifications’’ should
be adequate for both sections of the rule.
The commenter recommended that the
EPA simplify the language in 40 CFR
60.113c(a)(3)(ii) and (iv) consistent with
the LEL calibration requirements in the
storage vessel degassing section.
Another commenter noted that the
language at 40 CFR 60.113c(a)(3)(iv)
references gasoline vapors and should
be generalized to accommodate other
stored VOLs.
Response: We disagree that the LEL
calibration requirements in 40 CFR
60.113c(a)(3)(ii) and (iv) are
burdensome. These paragraphs allow
the use of manufacturers’ calibration
methods, and they primarily specify
when calibration checks must be made
and specify the LEL span response.
Upon review of the two LEL monitoring
requirements, we are adding more
specific calibration requirements for the
LEL monitoring instrument used to
monitor degassing. Specifically, we are
requiring calibration and zero offset
checks each day and at the end of the
degassing event prior to completion to
confirm that the final readings are
accurate before controlled degassing can
be discontinued.
With respect to the comment
regarding the reference to gasoline
vapors in the calibration requirements at
40 CFR 60.113c(a)(3)(iv), we agree that
the proposed language needed to be
generalized. We used calibration
language from the gasoline distribution
rule (40 CFR part 63, subpart R), which
requires the correction factor to be based
on ‘‘gasoline vapor.’’ Because NSPS
subpart Kc is applicable to a much
broader range of chemicals, we are
revising references to ‘‘gasoline vapors’’
to ‘‘vapors of the stored VOL.’’ We are,
however, retaining the use of butane as
the surrogate if correction factors are not
available for the vapors of the VOL
stored, because a surrogate is needed
when no published correction factor is
available for the VOL, and butane is
considered a reasonable surrogate for
any VOL that does not have a published
correction factor.
Comment: Two commenters stated
that EPA Method 21 testing is laborious,
costly, and time-consuming for
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83312
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
facilities. One commenter believes that
the sensory monitoring provisions as
proposed would place undue burdens
on operators and would result in
redundancy in monitoring and
compliance measures. Both commenters
stated that when coupled with the
quarterly sensory testing, the
requirement for annual EPA Method 21
testing is unnecessary. One commenter
submitted a 1997 rule interpretation
memorandum written by the Texas
Natural Resource Conservation
Commission, which explained that the
EPA Method 21 test under NSPS
subpart Kb is not considered a
performance test under 40 CFR 60.8
since the EPA Method 21 is considered
a screening measurement rather than a
performance test, subject to the
recordkeeping requirements in the
General Provisions of 40 CFR 60.7(f) and
not required to be reported by either
NSPS subpart A or Kb. The commenter
requested that the EPA discuss whether
the EPA agrees or disagrees with this
guidance and whether the interpretation
also applies to NSPS subpart Kc.
Response: We disagree that quarterly
AVO monitoring is burdensome. If a
leak is found via AVO monitoring, it
triggers corrective action. Additionally,
we disagree that annual EPA Method 21
monitoring is unnecessary, because EPA
Method 21 will detect small emissions
sources that are above 500 ppm but that
would remain undetected by AVO
monitoring. The closed vent system is to
be operated ‘‘with no detectable
emissions as indicated by an instrument
reading of less than 500 ppm above
background and visual inspections, as
determined in part 60, subpart VV,
§ 60.485(b).’’ In the case of NSPS
subpart Kb, 40 CFR 60.113b(c) states:
‘‘The owner or operator of each source
that is equipped with a closed vent
system and control device as required in
§ 60.112b (a)(3) or (b)(2) (other than a
flare) is exempt from § 60.8 of the
General Provisions and shall meet the
following requirements.’’ As such, the
language in NSPS subpart Kb indicates
that 40 CFR 60.8 does not apply.
For NSPS subpart Kc, we used
language that the closed vent system
must operate ‘‘. . . with no detectable
emissions as indicated by an instrument
reading of less than 500 ppmv above
background . . .’’ (see 40 CFR
60.112c(d)(2)), but there is no clear
exemption from 40 CFR 60.8 in 40 CFR
60.113c(c)(2). Nonetheless, we agree
that the requirements in 40 CFR 60.8 do
not apply to EPA Method 21 instrument
monitoring under NSPS subpart Kb.
Unlike in NSPS subpart Kb, we
proposed and are finalizing reporting
requirements in NSPS subpart Kc for
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
EPA Method 21 instrument monitoring
events. In reviewing the proposed NSPS
subpart Kc provisions related to EPA
Method 21 and AVO monitoring, we
recognized that we focused on the
instrument monitoring requirements
when using EPA Method 21 and
inadvertently neglected to mention the
AVO inspection requirements.
Therefore, we are adding reference to
the monthly AVO monitoring
requirement in 40 CFR 60.113c(c)(2)
consistent with the requirement under
the proposed and final requirements at
40 CFR 60.112c(d)(2)(i), and we are
revising the provision of 40 CFR
60.113c(c)(3) to clarify that emissions
detected using AVO methods are
‘‘leaks’’ triggering corrective action. This
latter revision also clarifies that leaks
identified from AVO monitoring do not
trigger the need to conduct EPA Method
21 monitoring of an AVO-identified
leak. In our review, we also identified
a lack of reporting requirements related
to AVO-identified leaks. Therefore, we
have also revised what we proposed for
recordkeeping requirements at 40 CFR
60.115c(d)(3)(v) and reporting
requirements at 40 CFR 60.116c(f)(8)(ii)
to indicate the type of monitoring
conducted and to report information
regarding all leaks identified, not just
those identified during EPA Method 21
instrument monitoring.
Comment: Several commenters
requested revisions to the vapor
pressure testing requirements for
mixtures of indeterminate or variable
composition to define the term
‘‘variable’’ and to not require the initial
and repeat physical testing for liquids
whose upper and lower bounds of vapor
pressure are known or are readily
calculated using standard reference
texts and good engineering judgment.
Response: We agree with the
commenters that the concept of
‘‘variable compositions’’ of stored liquid
mixtures for which the proposed rule
would require initial and repeat
physical testing to determine MTVP
could be applied more broadly than
intended. Thus, in 40 CFR 60.113c(d)(1)
of the final rule, we are clarifying that
for mixtures of variable composition, if
the range of concentrations for each
constituent is known such that the
MTVP can be determined from data and
procedures in standard reference texts,
then physical testing is not required.
Similarly, under the final rule, physical
testing is not required for crude oils and
refined petroleum products for which
Reid vapor pressure is known and
MTVP can be determined from
nomographs and other procedures
described in reference texts such as AP–
42. Additionally, in 40 CFR
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
60.113c(d)(2) we have clarified that the
provisions apply to affected storage
vessels storing a mixture of
indeterminate composition or a mixture
of unknown variable composition.
E. Recordkeeping and Electronic
Reporting
The EPA is finalizing a requirement
that owners and operators of new,
modified, or reconstructed VOL storage
vessels subject to NSPS subpart Kc
maintain records of the results of
required testing, monitoring, and
inspections. The EPA is finalizing a
requirement that owners and operators
of VOL storage vessels subject to the
current and new NSPS at 40 CFR part
60, subparts Kb and Kc, submit
electronic copies of required
performance test reports and the
semiannual excess emissions and
continuous monitoring system
performance and summary reports,
through the EPA’s Central Data
Exchange (CDX) using the Compliance
and Emissions Data Reporting Interface
(CEDRI).
We are finalizing the recordkeeping
and reporting requirements similar to
those proposed except that some of the
revisions made to the standards, testing,
and monitoring provisions required
revision of the recordkeeping and
reporting requirements for the final rule.
The revisions to the proposed
recordkeeping and reporting
requirements and our rationale for
making the revisions are summarized in
this section.
• As noted in section IV.D. of this
preamble, we are revising the
recordkeeping and reporting
requirements in 40 CFR 60.115c(d)(3)(v)
and 60.116c(c)(8)(ii) to include the type
of monitoring conducted and to report
information regarding all leaks
identified, including leaks identified
using AVO methods.
• As noted in section IV.B.5. of this
preamble, we separated PRD monitoring
requirements to separately address
devices on storage vessels and devices
on the closed vent system and included
provisions to monitor vacuum breaking
devices on storage vessels. In reviewing
recordkeeping and reporting
requirements related to these
provisions, we noted that we had
proposed reporting requirements for
PRDs, but we failed to include
recordkeeping requirements for PRDs.
Therefore, we are adding recordkeeping
requirements at 40 CFR
60.115c(d)(3)(vii) for PRDs or vacuum
breaking devices on a storage vessel or
closed vent system that include: the
device type; the monitoring device or
system used for the device; data from
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
the device or system indicating whether
a pressure release occurred; and the
date, time, and duration of each
pressure release, if applicable. We are
also adding reporting requirements at 40
CFR 60.116c(c)(12) for each pressure
release that occurred as a result of a
vacuum breaking device that failed to
close prior to the storage vessel reaching
atmospheric pressure. The added
reporting requirements include:
identification of the vacuum breaking
device; start date, start time, and
duration (in minutes) of the pressure
release; and an estimate of the mass
quantity in pounds of VOL released.
These requirements mimic the pressure
release reporting requirements proposed
(and being finalized) for PRDs, and
these similar reporting requirements are
needed to document compliance with or
deviations from the requirements for
vacuum breaking devices used for
storage vessels using a closed vent
system routed to a control device.
• As noted in section IV.B.5. of this
preamble, we are including alternative
provisions that allow enclosed
combustion devices to comply with the
flare operating and monitoring
requirements. We include minor
revisions to the proposed recordkeeping
and reporting requirements
commensurate with the provided
alternative, to specify which
recordkeeping and reporting
requirements apply to control systems
‘‘other than flares or enclosed
combustion devices electing to comply
with § 60.112c(d)(5)’’ and which
recordkeeping and reporting
requirements apply to ‘‘flares or
enclosed combustion devices electing to
comply with § 60.112c(d)(5).’’ We are
also adding a reporting requirement for
the initial notification at 40 CFR
60.116c(a)(6) that includes a
requirement to specify the type of
control device used and the compliance
option selected, which, if an enclosed
combustion device is used, include
whether the device is complying with a
temperature operating limit or is instead
electing to comply with the flare
requirements in 40 CFR 60.112c(d)(5).
This initial notification requirement
will be useful for EPA permitting and
enforcement personnel to clearly
understand the compliance option being
elected for the enclosed combustion
device.
• For EFRs, as discussed in section
IV.D. of this preamble, we added
requirements to visually inspect the roof
fittings (such as access hatches, gauge
floats, gauge hatch/sample wells, rim
vents, deck drains, deck legs, vacuum
breakers, pontoon covers, and
guidepoles) when gap measurements are
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
conducted. We are adding to the list at
40 CFR 60.116c(c)(5)(vi)(A) to include
reference to deviations of the fitting
controls outlined in 40 CFR
60.113c(b)(4)(iii)(A) through (D) to allow
reporting of fitting deviations identified
during the gap measurement
inspections.
• As discussed in the comment and
response included in this section of the
preamble, we are revising what we
proposed for the timing of semiannual
compliance reports to either cover fixed
time periods (from January 1 to June 30
or July 1 to December 31) or align with
established reporting dates based on 40
CFR parts 70 or 71 permit requirements.
The proposed schedule for semiannual
reports appeared to require separate
semiannual reports for different affected
storage vessels at a facility depending
on when the storage vessel became
affected under NSPS subpart Kc.
Because facilities may have several
affected storage vessels under NSPS
subpart Kc, having fixed reporting
periods simplifies the reporting
requirements for these facilities.
Comment: Numerous commenters
requested that the EPA revise NSPS
subpart Kc so that reporting
requirements are consistent with other
reporting obligations and establish the
same semiannual reporting deadline for
all VOL storage vessels. The
commenters noted that, as proposed, it
appeared that each affected VOL storage
vessel could have a separate reporting
schedule depending on when the
sources became affected sources under
NSPS subpart Kc. The commenters
recommended that the EPA require the
annual reports to cover activities in set
time periods (January 1 through June 30
or July 1 through December 31, as
applicable). One commenter also
recommended that the EPA include an
alternative that would allow each
affected facility subject to permitting
regulations pursuant to 40 CFR parts 70
or 71 to align the semiannual reports
with established dates for submitting
semiannual reports pursuant to 40 CFR
70.6(a)(3)(iii)(A) or 40 CFR
71.6(a)(3)(iii)(A).
Response: First, we never intended to
have different semiannual compliance
report schedules for different storage
vessels at a given facility. We note that
the reporting form template was
designed to allow reporting of all
storage vessels at the facility in one
semiannual report. However, we agree
that, because the affected facility is each
VOL storage vessel, the proposed
requirements at 40 CFR 60.116c(d)
could be interpreted to impose different
reporting schedules for different storage
vessels if they become affected facilities
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
83313
in different months. Several
commenters suggested that the
semiannual reports cover fixed
timeframes, specifically January through
June and July through December. This
appears reasonable. One commenter
also suggested including reference to
semiannual reports under 40 CFR parts
70 or 71 in the event that the current
semiannual reporting period is different
from January through June and July
through December. This also appears
reasonable. Therefore, we are providing
a fixed timeframe for the semiannual
reports (January through June and July
through December) and providing an
alternative timeframe to harmonize with
other semiannual reports as scheduled
under 40 CFR parts 70 or 71, if different
from the fixed timeframe being
finalized. We clarify that the first
semiannual compliance report is
triggered by the date on which the first
storage vessel at the facility becomes an
affected facility subject to NSPS subpart
Kc and would cover, for example, April
15 through June 30 if the source
becomes an affected facility on April 15.
As new storage vessels become affected
facilities under NSPS subpart Kc, the
information for those storage vessels
will be added to the semiannual report.
These semiannual reporting
requirements simplify the reporting
requirements compared to the timing
proposed and allow alignment of the
semiannual reports provided for NSPS
subpart Kc with other reporting
requirements that may apply for the
facility.
F. Other Final Amendments
1. Editorial Corrections
We received a number of comments
regarding editorial, typographical, and
cross-reference corrections that we agree
with and are finalizing. Additionally,
we received comments recommending
clarification of requirement language to
reduce misinterpretation. After
reviewing these comments, we are
revising some language in the final rule.
We are revising references of ‘‘a control’’
to ‘‘a control device.’’ Beyond these
changes, the EPA made several revisions
throughout NSPS subpart Kc to improve
clarity.
One commenter recommended that
the EPA clarify in 40 CFR 60.113c(d)(1)
that the requirement to determine
MTVP is not a one-time requirement, as
implied by the word ‘‘initial,’’ but also
applies to non-anticipated tank service
changes. We agree that if the VOL stored
in the storage vessel changes, the MTVP
should be reassessed. We are revising 40
CFR 60.113c(d)(1) to require that this
determination be made prior to the
E:\FR\FM\15OCR4.SGM
15OCR4
83314
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
initial filling of the storage vessel or to
the refilling of the storage vessel with a
new VOL.
One commenter recommended that in
40 CFR 60.115c(d)(5)(i) and 40 CFR
60.116c(c)(10)(i)(A) the EPA should add
‘‘or flare flame’’ to any occurrence of
‘‘pilot flame’’ consistent with the
provisions in 40 CFR 60.112c(d)(5)(iv)
and 40 CFR 60.113c(c)(1)(iv)(B). We are
revising 40 CFR 60.115c(d)(5)(i) and 40
CFR 60.116c(c)(10)(i)(A) accordingly.
2. Definitions
We received several comments
recommending the inclusion of
definitions that were not included in the
proposal. Additionally, we received
comments recommending definition
revisions. This section of the preamble
summarizes major comments received
concerning definitions and provides our
responses to those comments.
Comment: Several commenters
recommended that the EPA define the
term ‘‘pressure relief device’’ in NSPS
subpart Kc and provided a suggested
definition:
khammond on DSKJM1Z7X2PROD with RULES4
Pressure relief device means a valve,
rupture disk, or similar device used only to
release an unplanned, nonroutine discharge
of gas from process equipment in order to
avoid safety hazards or equipment damage. A
pressure relief device discharge can result
from an operator error, a malfunction such as
a power failure or equipment failure, or other
unexpected cause. Such devices include
conventional, spring-actuated relief valves,
balanced bellows relief valves, pilot-operated
relief valves, rupture disks, and breaking,
buckling, or shearing pin devices. Devices
that are actuated either by a pressure of less
than or equal to 2.5 pounds per square inch
gauge or by a vacuum are not pressure relief
devices.
Response: We agree with the
commenters and are including a
definition of ‘‘pressure relief device’’ in
NSPS subpart Kc similar to the
commenters’ suggestion. For storage
vessels, we consider ‘‘conservation
vents’’ to be PRDs. These conservation
vents typically have actuation pressure
less than 2.5 psig. As such, the last
sentence in our final definition reflects
a change from the last sentence in our
proposed definition to only exclude
vacuum breaking devices from the
definition of ‘‘pressure relief devices.’’
We are also clarifying that, if a device
has both a pressure relief function and
a vacuum breaking function, such as a
conservation vent, the portion of the
conservation vent that acts to relieve
pressure is considered a PRD and the
portion of the conservation vent that
acts to relieve vacuum is a vacuum
breaking device and not a PRD. We are
also adding a definition of ‘‘vacuum
breaking device,’’ which is specific to
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
the fixed roof portion of the storage
vessel and a vacuum breaker which is
a component of a floating roof.
Comment: One commenter
recommended that the EPA define the
term ‘‘pressure release.’’
Response: We are adding a definition
of ‘‘pressure release’’ to 40 CFR 60.111c.
We are including in the definition of
‘‘pressure release’’ emissions of
materials resulting from a vacuum
breaking device failing to close prior to
the system reaching atmospheric
pressure.
Comment: One commenter
recommended that the EPA define the
terms ‘‘vapor balancing system,’’ ‘‘fuel
gas,’’ ‘‘fuel gas system,’’ and ‘‘routed to
a process or route to a process.’’
Response: We determined that vapor
balancing is not appropriate or
equivalent to the BSER identified for
VOL storage vessels. As such, we are not
including a definition of ‘‘vapor
balancing system’’ in NSPS subpart Kc.
We disagree with the commenter’s
request to define ‘‘fuel gas’’ because the
‘‘fuel gas system’’ definition is
sufficient. We are finalizing definitions
for ‘‘fuel gas system’’ and ‘‘routed to a
process or route to a process’’ in NSPS
subpart Kc.
Comment: One commenter
recommended that the EPA define
‘‘degassing’’ with language consistent
with the Texas Commission on
Environmental Quality’s (TCEQ)
definition.
Response: The EPA agrees with the
commenter to define ‘‘degassing’’;
however, the TCEQ definition is
insufficient as there may be other
reasons to empty and degas a storage
vessel other than cleaning. While we
agree that cleaning may be a step in the
process, we expect degassing to occur
for other reasons. We are finalizing a
definition for ‘‘degassing’’ in NSPS
subpart Kc to clarify this point.
G. Effective Date and Compliance Dates
Pursuant to CAA section 111(b)(1)(B),
the effective date of the final rule
requirements in subpart Kc will be the
promulgation date. Affected sources that
commence construction, reconstruction,
or modification after October 4, 2023,
must comply with all requirements of
subpart Kc no later than the effective
date of the final rule or upon startup,
whichever is later. The EPA is finalizing
amendments to NSPS subpart Kb to
include electronic submission
requirements. Affected NSPS subpart Kb
sources that commence construction,
reconstruction, or modification after
July 23, 1984, and before October 4,
2023, must comply with the updated
requirements to submit reports
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
electronically no later than the effective
date of the final rule.
V. Summary of Cost, Environmental,
and Economic Impacts
A. What are the air quality impacts?
The final provisions in NSPS subpart
Kc reduce emissions of VOCs, some of
which may also be hazardous air
pollutants (HAPs). The EPA estimates
that the final standards will reduce VOC
emissions by 1,085 tons per year, which
includes the impacts from new,
modified, and reconstructed storage
vessels. More information regarding the
air quality impacts and emission
reductions are included in the
memorandum Control Options for
Storage Vessels (Docket ID No. EPA–
HQ–OAR–2023–0358–0002).
B. What are the cost impacts?
This final action will cost (in 2022
dollars) approximately $21.1 million in
total capital cost and result in a total
annualized cost of $5.38 million per
year (including product recovery) based
on our analysis of the final actions in
NSPS subpart Kc. More information
about the estimated cost of the final
actions can be found in the
memorandum Control Options for
Storage Vessels (Docket ID No. EPA–
HQ–OAR–2023–0358–0002).
C. What are the economic impacts?
For economic impact analyses (EIA)
of rules that directly affect a single
industry or a few industries, the EPA
often prepares a partial equilibrium
analysis. In this type of economic
analysis, the focus of the effort is on
estimating impacts on a single affected
industry or several affected industries,
and all impacts of this rule on industries
outside of those affected are assumed to
be zero or so inconsequential as to not
be considered in the analysis. If the
compliance costs, which are key inputs
to an EIA, are quite insignificant, then
the impact analysis could consist of a
calculation of annual (or annualized)
costs as a percentage of sales for affected
companies. This latter type of analysis
is called a screening analysis and is
applied when a partial equilibrium or
more complex EIA approach is deemed
not necessary given the expected size of
the impacts.
The net present value of the estimated
cost impacts of NSPS subpart Kc is
$19.4 million, discounted at a 3 percent
rate over a 5-year analytic timeframe
from 2024 to 2028 in 2022 dollars.
Using a 7 percent discount rate, the net
present value of the estimated cost
impacts is $17.3 million. The equivalent
annualized value in 2022 dollars is a
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
cost of approximately $4.1 million using
a discount rate of either 3 or 7 percent.
Storage vessels in NSPS subpart Kb
are most closely associated with the
petroleum and coal products industry
(NAICS 324000), the chemical products
industry (NAICS 325000), and the
petroleum bulk stations and terminals
industry (NAICS 424710). While we do
not know the precise distribution of
new and modified storage vessels across
the affected sectors, we know that there
are affected storage vessels in the sectors
mentioned earlier in this preamble.
These sectors contribute gross value
added, ranging from $200 to $501
billion per sector, to the national
economy. In comparison, the
requirements in NSPS subpart Kc have
estimated total costs of $21 million. The
total cost is the total incurred
collectively amongst numerous sectors,
and each of the sectors examined has
sales of at least $200 billion. Thus, the
compliance costs of this action are
insignificant relative to the scale for the
sectors affected, and it is appropriate to
evaluate the economic impacts by
conducting a screening analysis
comparing the costs to entity-level sales.
Given the results of the analysis, these
economic impacts are relatively low for
affected industries and entities
impacted by this final rule, and there
will not be substantial impacts on the
markets for affected products. The costs
of the final rule are not expected to
result in a significant market impact,
regardless of whether they are passed on
to the purchaser or absorbed by the
firms. We also expect minimal impacts
on employment.
khammond on DSKJM1Z7X2PROD with RULES4
D. What are the benefits?
The final provisions in NSPS subpart
Kc would reduce emissions of VOCs,
some of which may also be HAPs.
Because VOCs react in the atmosphere
to produce ozone, these standards
would help to reduce atmospheric
ozone concentrations and reduce health
effects associated with high levels of
ozone. Furthermore, the final
requirements to submit reports and test
results electronically would improve
monitoring, compliance, and
implementation of the rule.
E. What analysis of environmental
justice did we conduct?
For purposes of analyzing regulatory
impacts, under Executive Order 12898,
Federal Actions to Address
Environmental Justice in Minority
Populations and Low-Income
Populations, the EPA relies upon its
June 2016 ‘‘Technical Guidance for
Assessing Environmental Justice in
Regulatory Analysis,’’ which provides
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
recommendations that encourage
analysts to conduct the highest quality
analysis feasible, recognizing that data
limitations, time, resource constraints,
and analytical challenges will vary by
media and circumstance. The Technical
Guidance states that a regulatory action
may involve potential EJ concerns if it
could: (1) create new disproportionate
impacts on communities with EJ
concerns; (2) exacerbate existing
disproportionate impacts on
communities with EJ concerns; or (3)
present opportunities to address
existing disproportionate impacts on
communities with EJ concerns through
this action under development.
The EPA’s EJ technical guidance
states that ‘‘[t]he analysis of potential EJ
concerns for regulatory actions should
address three questions: (A) Are there
potential EJ concerns associated with
environmental stressors affected by the
regulatory action for population groups
of concern in the baseline? (B) Are there
potential EJ concerns associated with
environmental stressors affected by the
regulatory action for population groups
of concern for the regulatory option(s)
under consideration? (C) For the
regulatory option(s) under
consideration, are potential EJ concerns
created or mitigated compared to the
baseline?’’ 9
Because this action finalizes
standards of performance for new,
modified, and reconstructed sources
that commence construction after
October 4, 2023, the locations of the
construction of new VOL storage vessels
are not known. In addition, it is not
known which of the existing facilities
will be modified or reconstructed in the
future. Therefore, we are unable to
quantitatively estimate the potential
environmental justice impact of NSPS
subpart Kc. Over the next 5 years, the
EPA estimates that 1,440 new tanks and
30 modified tanks would be subject to
NSPS subpart Kc. We estimate that there
are more than 10,000 existing VOL
storage vessels, but we do not have a list
of specific storage vessels and their
locations. Therefore, we cannot perform
a proximity demographic analysis of
populations near existing units as a
proxy for units that may be modified or
reconstructed and become subject to
NSPS subpart Kc. Finally, because we
based the analysis of the impacts and
emission reductions on model plants,
we cannot ascertain specifically how the
9 Technical Guidance for Assessing
Environmental Justice in Regulatory Analysis, U.S.
EPA, June 2016. Quote is from Section 3—Key
Analytic Considerations, page 11. https://
www.epa.gov/environmentaljustice/technicalguidance-assessing-environmental-justiceregulatory-analysis.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
83315
potential benefits of this rule would be
distributed across the population. Thus,
we are limited in our ability to estimate
the potential EJ impacts of this rule.
The EPA expects that NSPS subpart
Kc will ensure compliance via revised
vapor pressure applicability thresholds,
stricter seal requirements on IFR tanks,
equivalent control requirements for
EFRs, and strengthened closed vent
system standards for vessels routed to a
control device, fuel gas system, or
process. This action finalizes standards
of performance that apply at all times
(including periods of SSM) and achieve
an average 98 percent control efficiency.
The rule will also increase data
transparency through electronic
reporting. Therefore, effects of
emissions on populations in proximity
to any future affected sources, including
in communities potentially
overburdened by pollution, which are
often communities with EJ concerns,
will be minimized due to the
compliance with the standards of
performance being finalized in this
action.
VI. Statutory and Executive Order
Reviews
Additional information about these
statutes and Executive orders can be
found at https://www.epa.gov/lawsregulations/laws-and-executive-orders.
A. Executive Order 12866: Regulatory
Planning and Review and Executive
Order 14094: Modernizing Regulatory
Review
This action is not a significant
regulatory action as defined in
Executive Order 12866, as amended by
Executive Order 14094, and was
therefore not subject to a requirement
for Executive Order 12866 review.
B. Paperwork Reduction Act (PRA)
The information collection activities
in this rule have been submitted for
approval to OMB under the PRA. The
Information Collection Request (ICR)
document that the EPA prepared has
been assigned EPA ICR number 2791.01.
You can find a copy of the ICR in the
docket for this rule, and it is briefly
summarized here. The information
collection requirements are not
enforceable until the Office of
Management and Budget (OMB)
approves them.
The EPA is finalizing requirements for
storage vessels, including periodic
inspections based on the type of storage
vessel. This information will be
collected to assure compliance with
NSPS subpart Kc.
E:\FR\FM\15OCR4.SGM
15OCR4
83316
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
Respondents/affected entities:
Owners or operators of VOL storage
vessels.
Respondent’s obligation to respond:
Mandatory (40 CFR part 60, subpart Kc).
Estimated number of respondents:
588.
Frequency of response: Initially and
semiannually.
Total estimated burden: 16,394 hours
(per year). Burden is defined at 5 CFR
1320.3(b).
Total estimated cost: $2,009,357 (per
year), includes $528,240 in annualized
capital and no operation or maintenance
costs.
An agency may not conduct or
sponsor, and a person is not required to
respond to, a collection of information
unless it displays a currently valid OMB
control number. The OMB control
numbers for the EPA’s regulations in 40
CFR are listed in 40 CFR part 9. When
OMB approves this ICR, the Agency will
announce that approval in the Federal
Register and publish a technical
amendment to 40 CFR part 9 to display
the OMB control number for the
approved information collection
activities contained in this final rule.
khammond on DSKJM1Z7X2PROD with RULES4
C. Regulatory Flexibility Act (RFA)
I certify that this action will not have
a significant economic impact on a
substantial number of small entities
under the RFA. The small entities
subject to the requirements of this
action are small businesses and small
governmental jurisdictions that own or
operate VOL storage vessels. The
Agency has determined that small
entities may experience an impact of
likely below 1 percent relative to sales
for any affected small entity, and an
even larger margin before it would
approach a 1 percent impact for a
substantial number of small entities.
Details of this analysis are presented in
the memorandum Economic Impact
Analysis for the New Source
Performance Standards (NSPS) for the
Volatile Organic Liquid Storage Vessels
(Tanks) included in the docket.
D. Unfunded Mandates Reform Act
(UMRA)
This action does not contain an
unfunded mandate of $100 million or
more as described in UMRA, 2 U.S.C.
1531–1538, and does not significantly or
uniquely affect small governments. The
action imposes no enforceable duty on
any State, local, or Tribal governments
or the private sector.
E. Executive Order 13132: Federalism
This action does not have federalism
implications. It will not have substantial
direct effects on the States, on the
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
relationship between the national
government and the States, or on the
distribution of power and
responsibilities among the various
levels of government.
to reduce atmospheric ozone
concentrations and reduce health effects
associated with high levels of ozone and
are projected to improve overall health,
including that of children.
F. Executive Order 13175: Consultation
and Coordination With Indian Tribal
Governments
This action does have Tribal
implications as specified in Executive
Order 13175. NSPS subpart Kb includes
provisions for storage vessels that
already have impacts on Tribal
governments that have storage vessels
with at least 20,000 gallons of capacity
and that meet the vapor pressure
thresholds for general rule applicability
or control applicability. NSPS subpart
Kc includes updates to the VOC
standards and monitoring requirements
for storage vessels that meet the revised
vapor pressure thresholds for control.
Additionally, basic requirements for
determining a VOL’s MTVP,
recordkeeping, and good air pollution
control practices are being finalized for
all storage vessels greater than 20,000
gallons that only store VOLs with an
MTVP greater than or equal to 0.25 psia.
These changes will only impact storage
vessels that are constructed, modified,
or reconstructed after the proposal date.
Consistent with the EPA Policy on
Consultation and Coordination with
Indian Tribes, the EPA offered
government-to-government consultation
with Tribes by sending a letter dated
October 3, 2023, inviting all federally
recognized Tribes to request a
consultation. The EPA received one
request for consultation. On November
8, 2023, the EPA met with the Tribe for
the purposes of discussing NSPS
subpart Kc and other issues but were
unable to conduct consultation on this
specific rulemaking.
H. Executive Order 13211: Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use
This action is not subject to Executive
Order 13211, because it is not a
significant regulatory action under
Executive Order 12866.
G. Executive Order 13045: Protection of
Children From Environmental Health
Risks and Safety Risks
Executive Order 13045 directs Federal
agencies to include an evaluation of the
health and safety effects of the planned
regulation on children in Federal health
and safety standards and explain why
the regulation is preferable to
potentially effective and reasonably
feasible alternatives. This action is not
subject to Executive Order 13045
because it is not economically
significant as defined in Executive
Order 12866 and because the EPA does
not believe the environmental health or
safety risks addressed by this action
present a disproportionate risk to
children. The final rule will reduce
emissions of VOCs, some of which may
also be HAPs. These standards will help
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
I. National Technology Transfer and
Advancement Act (NTTAA) and 1 CFR
Part 51
This action for NSPS subparts Kb and
Kc involves technical standards.
Therefore, the EPA conducted a search
to identify potentially applicable
voluntary consensus standards.
However, the Agency identified no such
standards. Searches were conducted for
EPA Methods 1, 1A, 2, 2A, 2C, 2D, 3A,
3B, 3C, 4, 6, 10, 15, 16, 16A, 18, 21, 22,
and 25A of 40 CFR part 60, appendix A.
The EPA has decided to use EPA
Methods 21, 22, and 25A. Additional
information for the voluntary consensus
standard search and determinations can
be found in the memorandum titled,
Voluntary Consensus Standard Results
for Review of Standards of Performance
for Volatile Organic Liquid Storage
Vessels (Including Petroleum Liquid
Storage Vessels). All potential standards
were reviewed to determine the
practicality of the voluntary consensus
standards for this rule. Although there
were no applicable voluntary consensus
standards identified, we are finalizing
the proposal to amend 40 CFR 60.17 to
incorporate by reference two ASTM
methods as discussed in section III.M. of
the proposal preamble (88 FR 68550;
October 4, 2023). These include the
following:
• ASTM D6377–20, Standard Test
Method for Determination of Vapor
Pressure of Crude Oil: VPCRx
(Expansion Method). The method is an
automated device method for measuring
vapor pressures for crude oils samples
between 29 kPa and 180 kPa at 37.8 °C.
The method is suitable for testing with
a 4:1 vapor-liquid ratio.
• ASTM D6378–22, Standard Test
Method for Determination of Vapor
Pressure (VPX) of Petroleum Products,
Hydrocarbons, and HydrocarbonOxygenate Mixtures (Triple Expansion
Method). The method is an automated
device method for measuring vapor
pressures between 7 kPa and 150 kPa at
37.8 °C for tested samples with boiling
points at 0 °C. The method is suitable
for volatile organic liquids,
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
hydrocarbons and liquid petroleum
products sampled at a 4:1 vapor-liquid
ratio.
The ASTM standards are available
from ASTM, International, 100 Barr
Harbor Drive, Post Office Box C700,
West Conshohocken, PA 19428–2959.
See https://www.astm.org.
J. Executive Order 12898: Federal
Actions To Address Environmental
Justice in Minority Populations and
Low-Income Populations and Executive
Order 14096: Revitalizing Our Nation’s
Commitment to Environmental Justice
for All
khammond on DSKJM1Z7X2PROD with RULES4
The EPA believes that it is not
practicable to assess whether the human
health or environmental conditions that
exist prior to this action result in
disproportionate and adverse effects on
communities with EJ concerns. Over the
next 5 years, the EPA estimates that
1,440 new tanks and 30 modified tanks
will be subject to NSPS subpart Kc.
However, the locations of any new VOL
storage vessels that would be subject to
NSPS subpart Kc are not known.
Furthermore, there is insufficient data
available regarding the locations of
existing VOL storage vessels. The EPA
estimates that there are more than
10,000 existing storage vessels subject to
NSPS subpart Kb, but we do not have
a list of specific storage vessels and their
locations. Therefore, we cannot perform
a proximity demographic analysis of
populations near existing storage vessels
as a proxy for storage vessels that may
be modified or reconstructed and
become subject to NSPS subpart Kc.
Finally, because we based the analysis
of the impacts and emission reductions
on model plants, we cannot ascertain
specifically how the potential benefits
of this rule would be distributed across
the population. Thus, we are limited in
our ability to estimate the potential EJ
impacts of this rule.
The information supporting this
Executive Order review is contained in
section V.E. of this document. All
pertinent supporting documents such as
the technical memorandum, Control
Options for Storage Vessels (Docket ID
No. EPA–HQ–OAR–2023–0358–0002),
which discusses the costs and
environmental impacts of the regulatory
options considered, is in the docket.
K. Congressional Review Act (CRA)
This action is subject to the CRA, and
the EPA will submit a rule report to
each House of the Congress and to the
Comptroller General of the United
States. This action is not a ‘‘major rule’’
as defined by 5 U.S.C. 804(2).
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
List of Subjects in 40 CFR Part 60
Environmental protection,
Administrative practice and procedures,
Air pollution control, Incorporation by
reference, Reporting and recordkeeping
requirements.
Michael S. Regan,
Administrator.
For the reasons set forth in the
preamble, the Environmental Protection
Agency is amending part 60 of title 40,
chapter I, of the Code of Federal
Regulations as follows:
*
1. The authority citation for part 60
continues to read as follows:
■
Authority: 42 U.S.C. 7401 et seq.
Subpart A—General Provisions
2. Amend § 60.17 by:
a. Redesignating paragraphs (h)(198)
through (233) as (h)(200) through (235);
and
■ b. Adding paragraphs (h)(198) and
(199).
The additions read as follows:
■
■
Incorporations by reference.
*
*
*
*
*
(h) * * *
(198) ASTM D6377–20, Standard Test
Method for Determination of Vapor
Pressure of Crude Oil: VPCRx
(Expansion Method), (Approved June 1,
2020); IBR approved for § 60.113c.
(199) ASTM–D6378–22, Standard
Test Method for Determination of Vapor
Pressure (VPX) of Petroleum Products,
Hydrocarbons, and HydrocarbonOxygenate Mixtures (Triple Expansion
Method), (Approved July 1, 2022); IBR
approved for § 60.113c.
*
*
*
*
*
Subpart Kb—Standards of
Performance for Volatile Organic
Liquid Storage Vessels (Including
Petroleum Liquid Storage Vessels) for
Which Construction, Reconstruction,
or Modification Commenced After July
23, 1984, and On or Before October 4,
2023
3. Revise the heading of subpart Kb to
read as set out above.
■ 4. Amend § 60.110b by revising
paragraph (a) to read as follows:
■
§ 60.110b Applicability and designation of
affected facility.
(a) Except as provided in paragraph
(b) of this section, the affected facility to
which this subpart applies is each
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
storage vessel with a capacity greater
than or equal to 75 cubic meters (m3)
that is used to store volatile organic
liquids (VOL) for which construction,
reconstruction, or modification is
commenced after July 23, 1984, and on
or before October 4, 2023.
*
*
*
*
*
■ 5. Amend § 60.115b by:
■ a. Revising paragraphs (a), (b), and (d);
and
■ b. Adding paragraphs (e), (f), and (g).
The revisions and additions read as
follows:
§ 60.115b Reporting and recordkeeping
requirements.
PART 60—STANDARDS OF
PERFORMANCE FOR NEW
STATIONARY SOURCES
§ 60.17
83317
*
*
*
*
(a) After installing control equipment
in accordance with § 60.112b(a)(1)
(fixed roof and internal floating roof),
the owner or operator shall meet the
following requirements.
(1) Furnish the Administrator with a
report that describes the control
equipment and certifies that the control
equipment meets the specifications of
§ 60.112b(a)(1) and § 60.113b(a)(1). Prior
to October 15, 2024, this report shall be
an attachment to the notification
required by § 60.7(a)(3). Beginning
October 15, 2024, the owner or operator
must submit all subsequent reports in
PDF format following the procedures
specified in paragraph (e) of this
section.
(2) Keep a record of each inspection
performed as required by
§ 60.113b(a)(1), (a)(2), (a)(3), and (a)(4).
Each record shall identify the storage
vessel on which the inspection was
performed and shall contain the date the
vessel was inspected and the observed
condition of each component of the
control equipment (seals, internal
floating roof, and fittings).
(3) If any of the conditions described
in § 60.113b(a)(2) are detected during
the annual visual inspection required by
§ 60.113b(a)(2), a report shall be
furnished to the Administrator within
30 days of the inspection. Each report
shall identify the storage vessel, the
nature of the defects, and the date the
storage vessel was emptied or the nature
of and date the repair was made.
Beginning October 15, 2024, all
subsequent reports must be submitted in
PDF format following the procedures in
paragraph (e) of this section.
(4) After each inspection required by
§ 60.113b(a)(3) that finds holes or tears
in the seal or seal fabric, or defects in
the internal floating roof, or other
control equipment defects listed in
§ 60.113b(a)(3)(ii), a report shall be
furnished to the Administrator within
30 days of the inspection. The report
shall identify the storage vessel and the
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83318
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
reason it did not meet the specifications
of § 60.112b(a)(1) or § 60.113b(a)(3) and
list each repair made. Beginning
October 15, 2024, all subsequent reports
must be submitted in PDF format
following the procedures in paragraph
(e) of this section.
(b) After installing control equipment
in accordance with § 60.112b(a)(2)
(external floating roof), the owner or
operator shall meet the following
requirements.
(1) Furnish the Administrator with a
report that describes the control
equipment and certifies that the control
equipment meets the specifications of
§ 60.112b(a)(2) and § 60.113b(b)(2),
(b)(3), and (b)(4). Prior to October 15,
2024, this report shall be an attachment
to the notification required by
§ 60.7(a)(3). Beginning October 15, 2024,
the owner or operator must submit all
subsequent reports in PDF format
following the procedures specified in
paragraph (e) of this section.
(2) Within 60 days of performing the
seal gap measurements required by
§ 60.113b(b)(1), furnish the
Administrator with a report that
contains the following information.
Beginning October 15, 2024, all
subsequent reports must be submitted in
PDF format following the procedures in
paragraph (e) of this section.
(i) The date of measurement;
(ii) The raw data obtained in the
measurement; and
(iii) The calculations described in
§ 60.113b(b)(2) and (b)(3).
(3) Keep a record of each gap
measurement performed as required by
§ 60.113b(b). Each record shall identify
the storage vessel in which the
measurement was performed and shall
contain:
(i) The date of measurement;
(ii) The raw data obtained in the
measurement; and
(iii) The calculations described in
§ 60.113b(b)(2) and (b)(3).
(4) After each seal gap measurement
that detects gaps exceeding the
limitations specified by § 60.113b(b)(4),
submit a report to the Administrator
within 30 days of the inspection. The
report will identify the vessel and
contain the information specified in
paragraph (b)(2) of this section and the
date the vessel was emptied or the
repairs made and date of repair.
Beginning October 15, 2024, all
subsequent reports must be submitted in
PDF format following the procedures in
paragraph (e) of this section.
*
*
*
*
*
(d) After installing a closed vent
system and flare to comply with
§ 60.112b, the owner or operator shall
meet the following requirements.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(1) A report containing the
measurements required by § 60.18(f)(1)
through (6) shall be furnished to the
Administrator as required by § 60.8 of
the General Provisions. This report shall
be submitted within 6 months of the
initial start-up date. Beginning October
15, 2024, all subsequent reports must be
submitted in PDF format following the
procedures in paragraph (e) of this
section.
(2) Records shall be kept of all periods
of operation during which the flare pilot
flame is absent.
(3) Semiannual reports of all periods
recorded under § 60.115b(d)(2) in which
the pilot flame was absent shall be
furnished to the Administrator.
Beginning October 15, 2024, all
subsequent reports must be submitted in
PDF format following the procedures
specified in paragraph (e) of this
section.
(e) An owner or operator required to
submit notifications or reports following
the procedures specified in this
paragraph (e) must submit notifications
or reports to the EPA via the
Compliance and Emissions Data
Reporting Interface (CEDRI), which can
be accessed through the EPA’s Central
Data Exchange (CDX) (https://
cdx.epa.gov/). The EPA will make all
the information submitted through
CEDRI available to the public without
further notice to the owner or operator.
Do not use CEDRI to submit information
the owner or operator claims as CBI.
Although the EPA does not expect
persons to assert a claim of CBI, if an
owner or operator wishes to assert a CBI
claim for some of the information in the
report or notification, the owner or
operator must submit a complete file in
the format specified in this subpart,
including information claimed to be
CBI, to the EPA following the
procedures in paragraphs (e)(1) and (2)
of this section. Clearly mark the part or
all of the information claimed to be CBI.
Information not marked as CBI may be
authorized for public release without
prior notice. Information marked as CBI
will not be disclosed except in
accordance with procedures set forth in
40 CFR part 2. All CBI claims must be
asserted at the time of submission.
Anything submitted using CEDRI cannot
later be claimed CBI. Furthermore,
under CAA section 114(c), emissions
data is not entitled to confidential
treatment, and the EPA is required to
make emissions data available to the
public. Thus, emissions data will not be
protected as CBI and will be made
publicly available. The owner or
operator must submit the same file
submitted to the CBI office with the CBI
omitted to the EPA via the EPA’s CDX
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
as described earlier in this paragraph
(e).
(1) The preferred method to receive
CBI is for it to be transmitted
electronically using email attachments,
File Transfer Protocol, or other online
file sharing services. Electronic
submissions must be transmitted
directly to the OAQPS CBI Office at the
email address oaqpscbi@epa.gov, and as
described above, should include clear
CBI markings, and be flagged to the
attention of the NSPS Kb Lead. Owners
and operators who do not have their
own file sharing service and who
require assistance with submitting large
electronic files that exceed the file size
limit for email attachments should
email oaqpscbi@epa.gov to request a file
transfer link.
(2) If an owner or operator cannot
transmit the file electronically, the
owner or operator may send CBI
information through the postal service
to the following address: U.S. EPA,
Attn: OAQPS Document Control Officer
and NSPS Kb Lead, Mail Drop: C404–
02, 109 T.W. Alexander, P.O. Box
12055, RTP, NC 27711. The mailed CBI
material should be double wrapped and
clearly marked. Any CBI markings
should not show through the outer
envelope.
(f) Owners and operators required to
electronically submit notifications or
reports through CEDRI in the EPA’s
CDX may assert a claim of EPA system
outage for failure to timely comply with
the electronic submittal requirement. To
assert a claim of EPA system outage,
owners and operators must meet the
requirements outlined in paragraphs
(f)(1) through (7) of this section.
(1) The owner or operator must have
been or will be precluded from
accessing CEDRI and submitting a
required report within the time
prescribed due to an outage of either the
EPA’s CEDRI or CDX systems.
(2) The outage must have occurred
within the period of time beginning 5
business days prior to the date that the
submission is due.
(3) The outage may be planned or
unplanned.
(4) The owner or operator must
submit notification to the Administrator
in writing as soon as possible following
the date the owner or operator first
knew, or through due diligence should
have known, that the event may cause
or has caused a delay in reporting.
(5) The owner or operator must
provide to the Administrator a written
description identifying:
(i) The date(s) and time(s) when CDX
or CEDRI was accessed and the system
was unavailable;
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
(ii) A rationale for attributing the
delay in reporting beyond the regulatory
deadline to EPA system outage;
(iii) A description of measures taken
or to be taken to minimize the delay in
reporting; and
(iv) The date by which the owner or
operator proposes to report, or if the
owner or operator has already met the
reporting requirement at the time of the
notification, the date the report was
submitted.
(6) The decision to accept the claim
of EPA system outage and allow an
extension to the reporting deadline is
solely within the discretion of the
Administrator.
(7) In any circumstance, the report
must be submitted electronically as
soon as possible after the outage is
resolved.
(g) Owners and operators required to
electronically submit notifications or
reports through CEDRI in the EPA’s
CDX may assert a claim of force majeure
for failure to timely comply with the
electronic submittal requirement. To
assert a claim of force majeure, you
must meet the requirements outlined in
paragraphs (g)(1) through (5) of this
section.
(1) An owner or operator may submit
a claim if a force majeure event is about
to occur, occurs, or has occurred or
there are lingering effects from such an
event within the period of time
beginning 5 business days prior to the
date the submission is due. For the
purposes of this section, a force majeure
event is defined as an event that will be
or has been caused by circumstances
beyond the control of the affected
facility, its contractors, or any entity
controlled by the affected facility that
prevents the owner or operator from
complying with the requirement to
submit a report electronically within the
time period prescribed. Examples of
such events are acts of nature (e.g.,
hurricanes, earthquakes, or floods), acts
of war or terrorism, or equipment failure
or safety hazard beyond the control of
the affected facility (e.g., large scale
power outage).
(2) The owner or operator must
submit notification to the Administrator
in writing as soon as possible following
the date the owner or operator first
knew, or through due diligence should
have known, that the event may cause
or has caused a delay in reporting.
(3) The owner or operator must
provide to the Administrator:
(i) A written description of the force
majeure event;
(ii) A rationale for attributing the
delay in reporting beyond the regulatory
deadline to the force majeure event;
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(iii) A description of measures taken
or to be taken to minimize the delay in
reporting; and
(iv) The date by which the owner or
operator proposes to report, or if the
owner or operator has already met the
reporting requirement at the time of the
notification, the date the report was
submitted.
(4) The decision to accept the claim
of force majeure and allow an extension
to the reporting deadline is solely
within the discretion of the
Administrator.
(5) In any circumstance, the reporting
must occur as soon as possible after the
force majeure event occurs.
■ 6. Amend § 60.116b by revising
paragraph (d) to read as follows:
§ 60.116b
Monitoring of operations.
*
*
*
*
*
(d) Except as provided in paragraph
(g) of this section, the owner or operator
of each storage vessel either with a
design capacity greater than or equal to
151 m3 storing a liquid with a maximum
true vapor pressure that is normally less
than 5.2 kPa or with a design capacity
greater than or equal to 75 m3 but less
than 151 m3 storing a liquid with a
maximum true vapor pressure that is
normally less than 27.6 kPa shall notify
the Administrator within 30 days when
the maximum true vapor pressure of the
liquid exceeds the respective maximum
true vapor pressure values for each
volume range. Beginning October 15,
2024, all subsequent notifications must
be submitted in PDF format following
the procedures specified in § 60.115b(e).
*
*
*
*
*
■ 7. Amend § 60.117b by revising
paragraph (b) to read as follows:
§ 60.117b
Delegation of authority.
*
*
*
*
*
(b) Authorities which will not be
delegated to States: §§ 60.111b(f)(4),
60.114b, 60.116b(e)(3)(iii),
60.116b(e)(3)(iv), and 60.116b(f)(2)(iii),
and approval of an alternative to any
electronic reporting to the EPA required
by this subpart.
■ 8. Add subpart Kc consisting of
§§ 60.110c through 60.117c to part 60 to
read as follows:
Subpart Kc—Standards of
Performance for Volatile Organic
Liquid Storage Vessels (Including
Petroleum Liquid Storage Vessels) for
Which Construction, Reconstruction,
or Modification Commenced After
October 4, 2023
Sec.
60.110c Applicability and designation of
affected facility.
60.111c Definitions.
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
83319
60.112c Standard for volatile organic
compounds (VOC).
60.113c Testing, monitoring, and inspection
procedures.
60.114c Alternative means of emission
limitation.
60.115c Recordkeeping requirements.
60.116c Reporting requirements.
60.117c Delegation of authority.
§ 60.110c Applicability and designation of
affected facility.
(a) Except as provided in paragraph
(b) of this section, the affected facility to
which this subpart applies is each
storage vessel with a capacity greater
than or equal to 20,000 gallons (gal)
(75.7 cubic meters (m3)) that is used to
store volatile organic liquids (VOL) for
which construction, reconstruction, or
modification is commenced after
October 4, 2023.
(b) This subpart does not apply to the
following:
(1) Vessels at coke oven by-product
plants;
(2) Pressure vessels designed to
operate in excess of 29.7 pounds per
square inch absolute (psia) (204.9
kilopascals (kPa) absolute) and without
emissions to the atmosphere;
(3) Vessels permanently attached to
mobile vehicles such as trucks, railcars,
barges, or ships;
(4) Vessels with a design capacity less
than or equal to 420,000 gal (1,589.874
m3) used for petroleum or condensate
stored, processed, or treated prior to
custody transfer;
(5) Vessels located at bulk gasoline
plants as defined in 40 CFR 63.11100;
(6) Vessels located at gasoline service
stations;
(7) Vessels used to store beverage
alcohol; or
(8) Vessels that only store VOL with
a maximum true vapor pressure less
than 0.25 psia (1.7 kPa absolute).
(c) Storage vessels that are affected
facilities according to paragraph (a) of
this section for which construction or
reconstruction commenced after
October 4, 2023 are subject to the
standards in § 60.112c and the
corresponding requirements in
§§ 60.113c through 60.116c as new
sources any time they meet the
specifications in either paragraph (c)(1)
or (2) of this section, regardless of
whether they initially contained VOL
with a maximum true vapor pressure
below the applicable threshold in
paragraph (c)(1) or (2) of this section.
(1) Storage vessels with a capacity
greater than or equal to 40,000 gal (151
m3) containing a VOL that, as stored,
has a maximum true vapor pressure
equal to or greater than 0.5 psia (3.4
kPa).
(2) Storage vessels with a capacity
greater than or equal to 20,000 gal (75.7
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83320
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
m3) but less than 40,000 gal (151 m3)
containing a VOL that, as stored, has a
maximum true vapor pressure equal to
or greater than 1.5 psia (10.3 kPa).
(d) Storage vessels that are affected
facilities according to paragraph (a) of
this section for which construction or
reconstruction commenced on or before
October 4, 2023, (‘‘existing storage
vessels’’) and are modified after October
4, 2023, are subject to the standards in
§ 60.112c and the corresponding
requirements in §§ 60.113c through
60.116c as modified sources any time
they meet the specifications in either
paragraph (d)(1) or (2) of this section.
(1) For an existing storage vessel with
a capacity greater than or equal to
40,000 gal (151 m3), containing a VOL
that, as stored, has a maximum true
vapor pressure equal to or greater than
0.5 psia (3.4 kPa).
(2) For an existing storage vessel with
a capacity greater than or equal to
20,000 gal (75.7 m3) but less than 40,000
gal (151 m3), containing a VOL that, as
stored, has a maximum true vapor
pressure equal to or greater than 1.5 psia
(10.3 kPa).
(e) For the purposes of this subpart,
(1) The phrase ‘‘change in the method
of operation of, an existing facility
which increases the amount of any air
pollutant’’ in the definition of
modification in § 60.2 or ‘‘operational
change to an existing facility which
results in an increase in the emission
rate to the atmosphere of any pollutant
to which a standard applies’’ in
§ 60.14(a) means a change in operation
occurs if the storage vessel is used to
store a VOL that has a greater maximum
true vapor pressure than all VOL
historically stored or permitted; and
(2) The exemption in § 60.14(e)(4)
regarding alternative fuel or raw
material does not apply to storage
vessels.
(f) Storage vessels that are affected
facilities according to paragraph (a) of
this section and do not meet the criteria
in either paragraph (c)(1), (c)(2), (d)(1),
or (d)(2) of this section are subject to the
requirements in § 60.113c(d), if
applicable, and § 60.115c(b).
(g) All standards including emission
limitations shall apply at all times,
including periods of startup, shutdown
and malfunction. As provided in
§ 60.11(f), this paragraph (g) supersedes
the exemptions for periods of startup,
shutdown, and malfunction in subpart
A of this part.
(h) Owners or operators may choose
to comply with the provisions of this
subpart to demonstrate compliance with
subparts K, Ka, and Kb of this part.
Compliance with the provisions of this
subpart, including all control
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
requirements, recordkeeping, and
reporting requirements, will constitute
compliance with the applicable storage
vessel provisions in subparts K, Ka, and
Kb.
(i) Owners or operators may choose to
comply with this subpart to demonstrate
compliance with 40 CFR part 63,
subpart WW for storage vessels
equipped with an internal or external
floating roof that is subject to this
subpart and 40 CFR part 63, subpart
WW. Compliance with this subpart,
including all floating roof requirements,
recordkeeping, and reporting
requirements, will constitute
compliance with the applicable storage
vessel provisions in 40 CFR part 63,
subpart WW.
§ 60.111c
Definitions.
Terms used in this subpart are
defined in the Act, in subpart A of this
part, or in this section as follows:
Access hatch means an opening in the
roof with a vertical well and a cover
attached to it. Access hatch provides
passage for workers and materials
through the roof for construction or
maintenance.
Condensate means hydrocarbon
liquid separated from natural gas that
condenses due to changes in the
temperature or pressure, or both, and
remains liquid at standard conditions.
Closed vent system means a system
that is not open to the atmosphere and
is composed of piping, ductwork,
connections, and, if necessary, flow
inducing devices that transport gas or
vapor from an emission point to a
control device. Closed vent system does
not include the vapor collection system
that is part of any tank truck or railcar.
Custody transfer means the transfer of
produced petroleum and/or condensate,
after processing and/or treatment in the
producing operations, from storage
vessels or automatic transfer facilities to
pipelines or any other forms of
transportation.
Degassing means the process of
removing VOL vapors from a storage
vessel during, or in preparation of,
cleaning or when taking the storage
vessel out of service for inspection,
repair, or other reason.
Enclosed combustion device means a
thermal combustion device used to mix
and ignite fuel, air pollutants, and air to
provide a flame to heat and oxidize air
pollutants and that emits the oxidized
pollutants through a conveyance
suitable to conduct a performance test.
An enclosed combustion device may
have recovery heat to preheat
combustion air, but its primary purpose
is for emission control and not to
produce useful heat. Enclosed
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
combustion devices include, but are not
limited to, thermal oxidizers and
incinerators. For the purpose of this
subpart, process heaters and boilers are
not enclosed combustion devices.
External floating roof means a
pontoon-type or double-deck type cover
that rests on the liquid surface in a
storage vessel without a fixed roof.
Fill means the introduction of VOL
into a storage vessel but not necessarily
to complete capacity.
Flare means a thermal combustion
device using an open or shrouded flame
(without full enclosure) such that the
pollutants are not emitted through a
conveyance suitable to conduct a
performance test.
Fuel gas system means the offsite and
onsite piping and control system that
gathers gaseous stream(s) generated by
onsite operations, may blend them with
other sources of gas, and transports the
gaseous stream for use as fuel gas in
combustion devices, or in- process
combustion equipment such as furnaces
and gas turbines, either singly or in
combination.
Gasoline service station means any
site where gasoline is dispensed to
motor vehicle fuel tanks from stationary
storage vessels.
Gauge float means a device that is
used to indicate the level of liquid
within the storage vessel. The float rests
on the liquid surface and is housed
inside a well that is closed by a
removable cover.
Gauge hatch/sample port/sample well
means an opening in the roof that
provides access for gauging or sampling.
A gauge hatch is usually equipped with
a closing cover or a funnel and slitfabric seal to cover the opening.
Internal floating roof means a floating
roof located in a storage vessel with a
fixed roof. For the purposes of this
subpart, an external floating roof located
in a storage vessel to which a fixed roof
has been added is considered to be an
internal floating roof.
Liquid-mounted primary seal means a
liquid or foam-filled seal mounted in
continuous contact with the liquid
between the wall of the storage vessel
and the floating roof around the entire
circumference of the storage vessel.
Maximum true vapor pressure means
the equilibrium partial pressure exerted
by the volatile organic compounds (as
defined in 40 CFR 51.100) in the stored
VOL at the temperature equal to the
highest calendar-month average of the
VOL storage temperature for VOLs
stored above or below the ambient
temperature or at the local maximum
monthly average temperature as
reported by the National Weather
Service for VOLs stored at the ambient
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
temperature, as determined using the
procedures specified in § 60.113c(d).
Mechanical shoe primary seal means
a metal sheet (the shoe) held vertically
against the wall of the storage vessel by
springs or weighted levels and is
connected by braces to the floating roof.
A flexible coated fabric (the envelope)
spans the annular space between the
metal sheet and the floating roof.
Petroleum means the crude oil
removed from the earth and the oils
derived from tar sands, shale, and coal.
Petroleum liquids means petroleum,
condensate, and any finished or
intermediate products manufactured in
a petroleum refinery.
Pressure release means the emission
of materials resulting from the system
pressure being greater than the set
pressure of the pressure relief device or
resulting from vacuum breaking device
failing to close prior to the system
reaching atmospheric pressure. This
release can be one release or a series of
releases over a short time period.
Pressure relief device means a valve,
rupture disk, or similar device used
only to release an unplanned,
nonroutine discharge of gas from
process equipment in order to avoid
safety hazards or equipment damage.
Devices with low opening pressures
must be monitored as bypass lines. A
pressure relief device discharge can
result from an operator error, a
malfunction such as a power failure or
equipment failure, or other unexpected
cause. Such devices include
conventional, spring-actuated relief
valves, balanced bellows relief valves,
pilot-operated relief valves, rupture
disks, and breaking, buckling, or
shearing pin devices. Devices that are
actuated only by a vacuum are not
pressure relief devices. If a device has
both a pressure relief function and a
vacuum breaking function, such as a
conservation vent, the portion of the
conservation vent that acts to relieve
pressure is considered a pressure relief
device and the portion of the
conservation vent that acts to relieve
vacuum is a vacuum breaking device
and not a pressure relief device.
Process tank means a tank that is used
within a process (including a solvent or
raw material recovery process) to collect
material discharged from a feedstock
storage vessel or equipment within the
process before the material is transferred
to other equipment within the process,
to a product or by-product storage
vessel, or to a vessel used to store
recovered solvent or raw material. In
many process tanks, unit operations
such as reactions and blending are
conducted. Other process tanks, such as
surge control vessels and bottoms
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
receivers, however, may not involve
unit operations.
Reid vapor pressure means the
absolute vapor pressure of volatile crude
oil and volatile nonviscous petroleum
liquids except liquified petroleum gases.
Rim-mounted secondary seal means a
secondary seal mounted on the rim of
the floating roof of a storage vessel and
forms continuous seal from the rim of
the floating roof to the wall of the
storage vessel.
Rim seal system means a primary seal
or a primary and secondary seal, which
is mounted above the primary seal, and
is attached to the deck perimeter and
contacts the storage vessel wall.
Rim vent means a device consisting of
a weighted pallet that rests on a valve
seat. Rim vents are used to release any
excess pressure or vacuum present in
the vapor pocket between the seal and
the rim area of a floating roof storage
vessel.
Routed to a process or route to a
process means the emissions are
conveyed by hardpiping or a closed vent
system to any enclosed portion of a
process unit where the emissions are
predominately recycled and/or
consumed in the same manner as a
material that fulfills the same function
in the process; and/or transformed by
chemical reaction into materials that are
not volatile organic liquids; and/or
incorporated into a product; and/or
recovered.
Storage vessel means each tank,
reservoir, or container used for the
storage of volatile organic liquids but
does not include:
(1) Frames, housing, auxiliary
supports, or other components that are
not directly involved in the containment
of liquids or vapors;
(2) Subsurface caverns or porous rock
reservoirs; or
(3) Process tanks.
Vacuum breaker/automatic bleeder
vent means a device used to equalize the
pressure of the vapor space across the
deck of a floating roof as the floating
roof is either being landed on or floated
off its roof supports. A vacuum breaker/
automatic bleeder vent consists of a well
with a cover. The cover is designed to
open as the floating roof is landed.
Opening of the cover may be
accomplished by mechanisms such as
leg actuation or pressure actuation.
Vacuum breaking device means a
device on a fixed roof of a storage vessel
used to prevent mechanical failure of
the storage vessel due to vacuum
created as liquids are withdrawn from
the storage vessel. If a device has both
a pressure relief function and a vacuum
breaking function, such as a
conservation vent, the portion of the
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
83321
conservation vent that acts to relieve
vacuum is considered a vacuum
breaking device and the portion of the
conservation vent that acts to relieve
excess pressure is a pressure relief
device and not a vacuum breaking
device.
Volatile organic liquid (VOL) means
any organic liquid which can emit
volatile organic compounds (as defined
in 40 CFR 51.100) into the atmosphere.
Waste means any liquid resulting
from industrial, commercial, mining, or
agricultural operations, or from
community activities that is discarded
or is being accumulated, stored, or
physically, chemically, or biologically
treated prior to being discarded or
recycled.
§ 60.112c Standard for volatile organic
compounds (VOC).
(a) General storage vessel control
requirements. You must equip and
operate each storage vessel affected
facility meeting the thresholds in
§ 60.110c(c)(1), (c)(2), (d)(1), or (d)(2) as
specified in paragraphs (a)(1) through
(4) of this section, as applicable.
(1) For each storage vessel affected
facility containing a VOL that, as stored,
has a maximum true vapor pressure less
than 11.1 psia (76.6 kPa), you may elect
to install and operate either an internal
floating roof meeting the requirements
in paragraph (b) of this section, an
external floating roof meeting the
requirements in paragraph (c) of this
section, or a closed vent system routed
to a control device, fuel gas system, or
process as specified in paragraph (d) of
this section.
(2) For each storage vessel affected
facility containing a VOL that, as stored,
has a maximum true vapor pressure of
11.1 psia (76.6 kPa) or more, you must
install and operate a closed vent system
routed to a control device, fuel gas
system, or process as specified in
paragraph (d) of this section.
(3) For each storage vessel affected
facility complying with the closed vent
system routed to a control device, fuel
gas system, or process provisions
specified in paragraph (d) of this section
regardless of size and for each storage
vessel with a design capacity greater
than or equal to 1,000,000 gal (3,790 m3)
containing a VOL that, as stored, has a
maximum true vapor pressure equal to
or greater than 1.5 psia (10.3 kPa), you
must also comply with the requirements
in paragraph (e) of this section.
(4) You must meet the applicable
testing, monitoring, and inspection
requirements specified in § 60.113c,
recordkeeping requirements specified in
§ 60.115c, and reporting requirements
specified in § 60.116c.
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83322
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
(b) Requirements for an internal
floating roof. You must equip and
operate each internal floating roof as
specified in paragraphs (b)(1) through
(16) of this section, as applicable.
(1) The internal floating roof must rest
or float on the liquid surface (but not
necessarily in complete contact with it)
inside a storage vessel that has a fixed
roof. The internal floating roof must be
floating on the liquid surface at all
times, except during initial fill and
during those intervals when the storage
vessel is completely emptied or
subsequently emptied and refilled.
When the roof is resting on the roof
supports, the process of filling,
emptying, or refilling must be
continuous and must be accomplished
as rapidly as possible.
(2) Except as provided in paragraph
(b)(14) of this section, each internal
floating roof must be equipped with the
following closure devices between the
wall of the storage vessel and the edge
of the internal floating roof:
(i) Two seals mounted one above the
other so that each forms a continuous
closure that completely covers the space
between the wall of the storage vessel
and the edge of the internal floating
roof. The lower seal is referred to as the
primary seal, and the upper seal is
referred to as the secondary seal.
(ii) The primary seal must be either a
mechanical shoe seal or a liquidmounted seal. If a mechanical shoe seal
is used, it must be installed so that one
end of the shoe extends into the stored
VOL and the other end extends a
minimum vertical distance of 6 inches
(15 centimeters) above the stored
organic liquid surface.
(iii) The secondary seal must be rimmounted.
(3) Each opening in a noncontact
internal floating roof except for vacuum
breaker/automatic bleeder vents and the
rim vents is to provide a projection
below the liquid surface.
(4) Vacuum breaker/automatic bleeder
vents must be equipped with a gasket
and are to be closed at all times, with
no visible gaps, when the roof is
floating. Vacuum breaker/automatic
bleeder vents must be set to open only
when the roof is being floated off or is
being landed on the roof supports.
(5) Rim vents must be equipped with
a gasket and must be closed at all times
with no visible gaps when the roof is
floating. Rim vents must be set to open
only when the internal floating roof is
not floating or when the pressure
beneath the rim seal system exceeds the
manufacturer’s recommended setting.
(6) Each penetration of the internal
floating roof for the purpose of sampling
must be a gauge hatch/sample well.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
Except as specified in paragraph (b)(14)
of this section, the gauge hatch/sample
well must have a gasketed cover, which
must be closed at all times, with no
visible gaps, except when the hatch or
well must be opened for access.
(7) Each access hatch and gauge float
well must be equipped with a cover that
is gasketed and that is bolted or
otherwise mechanically secured. The
cover must be closed and must be bolted
or otherwise mechanically secured at all
times, with no visible gaps, except when
the hatch or well must be opened for
access.
(8) Each penetration of the internal
floating roof that allows for passage of
a column supporting the fixed roof must
have a flexible fabric sleeve seal or a
gasketed sliding cover.
(9) Each penetration of the internal
floating roof that allows for passage of
an unslotted leg ladder or unslotted
ladder/guidepole combination must
have a gasketed sliding cover. The cover
must be closed at all times, with no
visible gaps, except when the well must
be opened for access.
(10) Each slotted guidepole must be
equipped with one of the controls
specified in paragraphs (b)(10)(i)
through (v) of this section. The covers
must be designed to be closed at all
times, with no visible gaps, except when
the cover must be opened for access.
(i) Gasketed sliding well cover, with
pole sleeve. The sleeve must extend into
the stored liquid.
(ii) Gasketed sliding well cover, with
pole sleeve and pole wiper. The sleeve
must extend into the stored liquid.
(iii) Gasketed sliding well cover, with
pole float and pole wiper. The wiper or
seal of the pole float must be at or above
the height of the pole wiper.
(iv) Gasketed sliding well cover, with
pole float, pole sleeve, and pole wiper.
The sleeve must extend into the stored
liquid. The wiper or seal of the pole
float must be at or above the height of
the pole wiper.
(v) A flexible device that completely
encloses the slotted guidepole and
eliminates the hydrocarbon vapor
emissions pathway from inside the
storage vessel through the guidepole
slots to the outside air; a gasketed
guidepole cover at the top of the
guidepole; and a gasketed sliding well
cover positioned at the top of the
guidepole well that seals any openings
between the well cover and the
guidepole (e.g., pole wiper), any
openings between the well cover and
any other objects that pass through the
well cover, and any other openings in
the top of the guidepole well.
(11) Ladder-slotted guidepole
combination wells must be equipped
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
with a gasketed sliding well cover and
a ladder sleeve. The sliding well cover
must be designed to be closed at all
times with no visible gaps, except when
gauging or sampling.
(12) Unslotted guidepoles must be
equipped with one of the controls
specified in paragraph (b)(12)(i) or (ii) of
this section. The controls must be
designed to be closed at all times with
no visible gaps.
(i) A gasketed guidepole cover at the
top of the guidepole; a gasketed sliding
well cover; and a pole sleeve. The
guidepole cover must be closed at all
times, except when required to be
opened for access. The gasketed sliding
well cover must seal any openings
between the well cover and the
guidepole, any openings between the
well cover and any other objects that
pass through the well cover, and any
other openings in the top of the
guidepole well.
(ii) A gasketed guidepole cover at the
top of the guidepole; a gasketed sliding
well cover; and a pole wiper. The
guidepole cover must be closed at all
times, except when required to be
opened for access. The gasketed sliding
well cover must seal any openings
between the well cover and the
guidepole (e.g., pole wiper), any
openings between the well cover and
any other objects that pass through the
well cover, and any other openings in
the top of the guidepole well.
(13) Except for leg sleeves and stub
drains, each opening in the internal
floating roof not specified in paragraphs
(b)(4) through (12) of this section, must
be equipped with a cover or lid which
is to be maintained in a closed position
at all times (i.e., no visible gap) except
when the device must be opened for
access. The cover or lid must be
equipped with a gasket.
(14) For each modified storage vessel
as specified in § 60.110c(d) with an
existing internal floating roof, you may
elect to comply with the rim seal system
requirements in § 60.112b(a)(1)(ii) or
§ 60.110b(e) instead of the requirements
in paragraph (b)(2) of this section, and
you may elect to comply with the gauge
hatch/sample well requirements in
§ 60.112b(a)(1)(vii) or § 60.110b(e)
instead of the requirements in paragraph
(b)(6) of this section.
(15) A system equivalent to those
described in paragraphs (b)(1) though
(14) of this section, as applicable, as
provided in § 60.114c.
(16) Equip, maintain, and operate
each internal floating roof control
system to maintain the vapor
concentration above the floating roof at
or below 25 percent of the lower
explosive limit (LEL) on a 5-minute
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
rolling average basis without the use of
purge gas. This standard may require
additional controls, such as improved
seam seals, beyond those specified in
paragraphs (b)(1) through (15) of this
section. Compliance with this paragraph
(b)(16) must be determined using the
methods in § 60.113c(a)(3). Exceeding
the LEL is considered an inspection
failure under § 60.113c(a)(2)(i) and must
be remedied as such. Any repairs made
must be confirmed effective through remonitoring of the LEL and meeting the
limits in this paragraph (b)(16) within
the timeframes specified in
§ 60.113c(a)(2)(i).
(c) Requirements for an external
floating roof. You must equip and
operate each external floating roof as
specified in paragraphs (c)(1) through
(4) of this section.
(1) The roof must be floating on the
liquid at all times (i.e., off the roof
supports) except during initial fill until
the roof is lifted off roof supports and
when the storage vessel is completely
emptied or subsequently emptied and
refilled. The process of filling,
emptying, or refilling when the roof is
resting on the roof supports must be
continuous and must be accomplished
as rapidly as possible.
(2) Each external floating roof must be
equipped with a primary and secondary
rim seal system as specified in
paragraph (b)(2) of this section, except
that if a mechanical shoe primary seal
is used, it must be installed so that one
end of the shoe extends into the stored
VOL and the other end extends a
minimum vertical distance of 24 inches
(61 centimeters) above the stored
organic liquid surface. The external
floating roof also must have welded
deck seams, and it must have deck
fitting controls as specified in
paragraphs (c)(2)(i) through (ix) of this
section, as applicable. References to an
internal floating roof in paragraph (b)(2)
of this section means an external
floating roof for the purposes of this
paragraph (c)(2).
(i) Each opening in an external
floating roof except for vacuum breaker/
automatic bleeder vents and the rim
vents is to provide a projection below
the liquid surface.
(ii) Vacuum breaker/automatic
bleeder vents must be equipped with a
gasket and are to be closed at all times,
with no visible gaps, when the roof is
floating. Vacuum breaker/automatic
bleeder vents must be set to open only
when the roof is being floated off or is
being landed on the roof supports.
(iii) Rim vents must be equipped with
a gasket and must be closed at all times
with no visible gaps when the roof is
floating. Rim vents must be set to open
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
only when the external floating roof is
not floating or when the pressure
beneath the rim seal system exceeds the
manufacturer’s recommended setting.
(iv) Each penetration of the external
floating roof for the purpose of sampling
must be a gauge hatch/sample well. The
gauge hatch/sample well must have a
gasketed cover, which must be closed at
all times, with no visible gaps, except
when the hatch or well must be opened
for access.
(v) Each access hatch and gauge float
well must be equipped with a cover that
is gasketed and that is bolted or
otherwise mechanically secured. The
cover must be closed and must be bolted
or otherwise mechanically secured at all
times, with no visible gaps, except when
the hatch or well must be opened for
access.
(vi) Except as specified in paragraph
(c)(3) of this section, if the external
floating roof does not have a liquidmounted primary seal, all guidepoles
must be unslotted and must be
equipped as specified in paragraph
(b)(12) of this section.
(vii) Except as specified in paragraph
(c)(3) of this section, if the external
floating roof has a liquid-mounted
primary seal, equip each guidepole as
specified in paragraphs (c)(2)(vii)(A)
and (B) of this section.
(A) Each slotted guidepole must be
equipped as specified in paragraphs
(b)(10)(ii) or (iv) of this section.
(B) Each unslotted guidepole must be
equipped as specified in paragraph
(b)(12) of this section.
(viii) Each emergency roof drain is to
be provided with a slotted membrane
fabric cover that covers at least 90
percent of the area of the opening.
(ix) Except for leg sleeves, each
opening in the external floating roof not
subject to controls specified in
paragraphs (c)(2)(i) through (viii) of this
section must be equipped with a cover
or lid which is to be maintained in a
closed position at all times (i.e., no
visible gap), except when the device
must be opened for access. The cover or
lid must be equipped with a gasket.
(3) For each modified storage vessel as
specified in § 60.110c(d) with an
existing external floating roof, you may
elect to comply with any of the
guidepole controls specified in
paragraphs (b)(10) and (12) of this
section regardless of the type of primary
seal used.
(4) A system equivalent to those
described in paragraphs (c)(1) through
(3) of this section as provided in
§ 60.114c.
(d) Requirements for closed vent
system routed to a control device, fuel
gas system, or process. You must design,
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
83323
install, and operate each affected storage
vessel with a closed vent system that
routes to a control device, fuel gas
system, or process as specified in
paragraphs (d)(1) through (7) of this
section.
(1) The storage vessel must be
designed and operated to be routed
through a closed vent system to a
control device, fuel gas system, or
process at all times the storage vessel
contains VOL without venting to the
atmosphere through either meeting the
storage vessel design requirements
specified in paragraph (d)(1)(i) of this
section or the vapor recovery system
design requirements specified in
paragraph (d)(1)(ii) of this section.
Compliance with this requirement must
be demonstrated according to paragraph
(d)(1)(iii) of this section. Any vacuum
breaking device on the storage vessel
must close while the storage vessel is
still under vacuum of at least ¥0.1
inches of water (¥0.0036 psig or
¥0.025 kPa gauge).
(i) The storage vessel must be
designed to operate at a gauge pressure
of no less than 1 psi greater than the
maximum true vapor pressure of the
stored liquid and any back pressure
anticipated when the storage vessel is
filled at its maximum rate without
venting to the atmosphere.
(ii) The vapor recovery system must
be designed and operated to maintain
the pressure in each storage vessel
routed to a control device below the
venting pressure of that storage vessel.
(iii) You must equip each pressure
relief device and vacuum breaking
device on a storage vessel with a
device(s) or use a monitoring system
that is capable of meeting the
requirements in paragraphs (d)(1)(iii)(A)
through (C) of this section. If all
emissions from a pressure relief device
are routed through a closed vent system
to a control device, process, or fuel gas
system, then you are not required to
comply with the requirements of this
paragraph (d)(1)(iii).
(A) Identifying the pressure release.
(B) Recording the time and duration
of each pressure release.
(C) Notifying operators immediately
that a pressure release is occurring. The
device or monitoring system must be
either specific to the pressure relief
device or vacuum breaking device itself
or must be associated with each storage
vessel to indicate a pressure release to
the atmosphere. Examples of these types
of devices and systems include, but are
not limited to, a rupture disk indicator,
magnetic sensor, motion detector on the
pressure relief valve stem, flow monitor,
or pressure monitor.
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83324
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
(2) Except for closed vent systems
operated and maintained under negative
pressure, each closed vent system must
meet the requirements specified in
paragraphs (d)(2)(i) through (iii) of this
section.
(i) The closed vent system must be
designed to collect all VOC vapors and
gases discharged from the storage vessel
and operated with no detectable
emissions as indicated by an instrument
reading of less than 500 parts per
million by volume (ppmv) above
background, as determined using
Method 21 of appendix A–7 to this part
as specified in § 60.113c(c)(2) and (3),
and as determined by observations for
visible, audible, and olfactory
indications of leaks. Visible, audible,
and olfactory inspections must be
performed quarterly and Method 21 of
appendix A–7 instrument monitoring
must be conducted at least annually.
(ii) Except for pressure relief devices
and except for open-ended valves or
lines that use a cap, blind flange, plug,
or second valve and follow the
requirements specified in § 60.482–
6(a)(2), (b), and (c) or follow
requirements codified in another
regulation that are the same as § 60.482–
6(a)(2), (b), and (c), you must comply
with the provisions of either paragraph
(d)(2)(ii)(A) or (B) of this section for
each closed vent system that contains
bypass lines that could divert a vent
stream to the atmosphere.
(A) Properly install, maintain, and
operate a flow indicator that is capable
of taking readings every 15 minutes.
Install the flow indicator at the entrance
to any bypass line.
(B) Secure the bypass line valve in the
non-diverting position with a car-seal or
a lock-and-key type configuration.
(iii) You must equip each pressure
relief device on a closed vent system
with a device(s) or use a monitoring
system that is capable of meeting the
requirements in paragraphs (d)(2)(iii)(A)
through (C) of this section. If all releases
and potential leaks from a pressure
relief device are routed through a closed
vent system to a control device, process,
or fuel gas system, then you are not
required to comply with the
requirements of this paragraph
(d)(2)(iii).
(A) Identifying the pressure release.
(B) Recording the time and duration
of each pressure release.
(C) Notifying operators immediately
that a pressure release is occurring. The
device or monitoring system must be
either specific to the pressure relief
device itself or must be associated with
the process system or piping, sufficient
to indicate a pressure release to the
atmosphere. Examples of these types of
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
devices and systems include, but are not
limited to, a rupture disk indicator,
magnetic sensor, motion detector on the
pressure relief valve stem, flow monitor,
or pressure monitor.
(3) If you route emissions from a
storage vessel to a control device, the
control device must be designed and
operated to reduce inlet VOC emissions
by 98 percent or greater. If a flare is used
as the control device or if an enclosed
combustion device is used for which
you elect to comply with the flare
operating limits, you must meet the
specifications described in paragraph
(d)(5) of this section. The control device
must be operated at all times when
emissions from an affected storage
vessel are routed to it except as
provided in paragraph (d)(7) of this
section.
(4) A system equivalent to those
described in paragraphs (d)(1) through
(3) of this section as provided in
§ 60.114c.
(5) If you route from a storage vessel
to a flare or enclosed combustion device
for with you elect to comply with these
flare operating limits, you must meet all
applicable requirements specified in 40
CFR 63.670(b) through (g) and (i)
through (n) except as provided in
paragraphs (d)(5)(i) through (v) of this
section.
(i) For the purpose of this subpart,
(A) The term ‘‘regulated materials’’
refers to ‘‘vapors from a storage vessel
affected facility’’;
(B) The term ‘‘pilot flame’’ means
‘‘pilot flame or flare flame’’;
(C) The terms ‘‘petroleum refinery’’
and ‘‘refinery’’ mean ‘‘storage vessel
affected facility’’.
(ii) For visible emissions, use the
following text instead of 40 CFR
63.670(c): The owner or operator shall
operate with no visible emissions,
except for periods not to exceed a total
of five (5) minutes during any two (2)
consecutive hours, when regulated
material is routed to the flare. You must
monitor for visible emissions from the
flare as specified in
§ 60.113c(c)(1)(iv)(A).
(iii) The phrase ‘‘and the flare vent gas
flow rate is less than the smokeless
design capacity of the flare’’ in 40 CFR
63.670(d) for flare tip velocity
requirements does not apply.
(6) If you route emissions from a
storage vessel to a fuel gas system or
process, you must meet the
requirements in paragraphs (d)(6)(i)
through (iv) of this section, as
applicable.
(i) The fuel gas system or process
must be operating at all times when
emissions from an affected storage
vessel are routed to it.
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
(ii) If all emissions are routed to a
process, the VOL in the emissions must
meet one or more of the conditions
specified in paragraphs (d)(6)(ii)(A)
through (D) of this section and you must
comply with the compliance
demonstration requirements in
paragraph (d)(6)(iii) of this section.
(A) Recycled and/or consumed in the
same manner as a material that fulfills
the same function in that process.
(B) Transformed by chemical reaction
into materials that are not regulated
materials.
(C) Incorporated into a product.
(D) Recovered.
(iii) To demonstrate compliance with
paragraph (d)(6)(ii) of this section for an
affected storage vessel, you must
prepare a design evaluation (or
engineering assessment) that
demonstrates the extent to which one or
more of the conditions specified in
paragraphs (d)(6)(ii)(A) through (D) of
this section are being met.
(iv) If emissions from an affected
storage vessel are routed to a fuel gas
system, you must submit the statement
of connection for fuel gas systems
specified in § 60.116c(a)(7).
(7) To the extent practical, routine
maintenance on the control device
should be conducted when the storage
vessel(s) is(are) out of VOL service. If
you comply with all the provisions in
paragraphs (d)(7)(i) through (iv) of this
section, you may conduct routine
maintenance on a control device while
one or more storage vessels vented to
the control device are storing a VOL.
(i) The storage vessel(s) storing VOL
must be designed to operate above the
maximum true vapor pressure of the
stored VOL according to paragraph
(d)(1)(i) of this section.
(ii) The control device must be
isolated from the storage vessel(s) using
valves(s), blind flange(s), or similar
device(s) at the control device or in the
closed vent system as near as practical
to the control device. You may purge
the control device and downstream
portion of the closed vent system to
remove potentially explosive vapors and
create a safe work environment only
after the control device is isolated from
the storage vessel(s).
(iii) You must continue to comply
with the bypass and pressure relief
device monitoring requirements in
paragraphs (d)(1)(iii), (d)(2)(ii), and
(d)(2)(iii) of this section and their
associated recordkeeping and reporting
requirements. If there are multiple
storage vessels connected to the closed
vent system with significantly different
pressure design limits, you must isolate
individual storage vessels to prevent
venting during planned maintenance.
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
Compliance with this paragraph
(d)(7)(iii) may limit VOL addition to the
storage vessel. If VOL is added to the
storage vessel, there must be an
approximately equivalent withdrawal of
VOL such that the liquid level does not
rise sufficiently to increase the pressure
in the storage vessel to cause a pressure
release from the storage vessel or the
closed vent system.
(iv) During this routine maintenance
period the affected storage vessels
cannot be actively degassed. If the
storage vessel is to be emptied and
actively degassed, the planned
maintenance activity must be conducted
when the storage vessel is out of VOL
service.
(e) Requirements for storage vessel
degassing. For each storage vessel
meeting the specifications in paragraph
(a)(3) of this section, you must meet the
requirements in paragraphs (e)(1)
through (3) of this section during
emptying and degassing of a storage
vessel until the vapor space
concentration in the storage vessel is
less than 10 percent of the LEL or, for
nonflammable liquids, 5,000 ppmv as
methane. You must determine the LEL
or methane concentration using process
instrumentation or a portable
measurement device and follow
procedures for calibration and
maintenance according to
manufacturer’s specifications. You must
check instrument calibration and check
the instrumental offset response each
day the instrument is used and prior to
discontinuing controlled degassing to
confirm the accuracy of the instrument’s
readings.
(1) Remove liquids from the storage
vessel as much as practicable.
Chemicals or a diluent such as a
distillate fuel may be introduced into
the storage vessel for the purpose of
reducing vapor concentration before or
during active degassing.
(2) Comply with one of the following:
(i) Reduce total VOC emissions by
venting emissions through a closed vent
system to a flare or enclosed combustion
device for which you elect to comply
with the flare provisions and meet the
requirements specified in paragraph
(d)(5) of this section.
(ii) Reduce total VOC emissions by 98
weight percent by venting emissions
through a closed vent system to any
combination of non-flare control
devices.
(iii) Reduce total VOC emissions by
routing emissions to a fuel gas system or
process and meet the requirements
specified in paragraph (d)(6) of this
section.
(3) For floating roof storage vessels,
the storage vessel may be opened to set
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
up equipment (e.g., making connections
to a temporary control device) for the
shutdown operations but must not be
actively degassed during this time
period.
§ 60.113c Testing, monitoring, and
inspection procedures.
For each storage vessel subject to the
provision in § 60.112c(a), you must meet
the requirements of paragraph (a) of this
section if you installed an internal
floating roof, paragraph (b) of this
section if you installed an external
floating roof, or paragraph (c) of this
section if you route emissions through
a closed vent system to a control device,
fuel gas system, or process. You must
also meet the applicable requirements of
paragraph (d) of this section.
(a) Requirements for an internal
floating roof. After installing the control
equipment for an internal floating roof
to meet the provisions in § 60.112c(b),
you must meet the requirements
specified in paragraphs (a)(1) through
(5) of this section.
(1) Visually inspect the internal
floating roof, the primary seal, the
secondary seal (if one is in service), and
deck fittings prior to filling the storage
vessel with VOL. Any of the conditions
described in paragraphs (a)(1)(i) through
(iii) of this section constitutes
inspection failure. You must repair the
items before filling the storage vessel.
(i) Holes, tears, or other openings in
the primary seal, the secondary seal, or
the seal fabric;
(ii) Defects in the internal floating
roof; or
(iii) A rim seal or deck fitting control
not meeting the applicable requirements
in § 60.112c(b)(2) through (13).
(2) Inspect the internal floating roof as
specified in paragraph (a)(2)(i) of this
section at least once every 12 calendar
months after initial fill, and inspect the
internal floating roof as specified in
paragraph (a)(2)(ii) of this section each
time the storage vessel is emptied and
degassed, or at a frequency no greater
than every 120 calendar months,
whichever occurs first.
(i) Visually inspect the internal
floating roof, the primary seal, the
secondary seal (if one is service), and
deck fittings, through openings in the
fixed roof and conduct LEL monitoring.
Any of the conditions described in
paragraphs (a)(2)(i)(A) through (F) of
this section constitutes inspection
failure. Identification of holes or tears in
the rim seal is required only for the seal
that is visible from the top of the storage
vessel. You must repair the items or
empty and remove the storage vessel
from service within 45 days. If a failure
that is detected during inspections
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
83325
required in this paragraph (a)(2)(i)
cannot be repaired within 45 days and
if the storage vessel cannot be emptied
within 45 days, you may request a 30day extension from the Administrator.
Such a request for an extension must
document that alternate storage capacity
is unavailable and specify a schedule of
actions the company will take that will
assure that the control equipment will
be repaired or the storage vessel will be
emptied as soon as possible.
(A) Stored liquid on the floating roof;
(B) The internal floating roof is not
resting on the surface of the VOL inside
the storage vessel;
(C) Holes, tears, or other openings in
the primary seal, the secondary seal, or
the seal fabric;
(D) Defects in the internal floating
roof;
(E) A rim seal or deck fitting control
not meeting the applicable requirements
in § 60.112c(b)(2) through (13); or
(F) The concentration measured
according to paragraph (a)(3) of this
section exceeds 25 percent of the LEL.
(ii) Visually inspect the internal
floating roof, the primary seal, the
secondary seal (if one is in service),
gaskets, slotted membranes, and sleeve
seals (if any). Any of the conditions
described in paragraphs (a)(2)(ii)(A)
through (C) of this section constitutes an
inspection failure. You must repair the
items as necessary so that none of the
conditions specified in this paragraph
(a)(2)(ii) exist before refilling the storage
vessel with VOL. The inspection may be
performed entirely from the top side of
the floating roof, as long as there is
visual access to all deck fittings and rim
seal system specified in § 60.112c(b).
You must repair the items or empty and
remove the storage vessel from service
within 45 days. If a failure that is
detected during inspections required in
this paragraph (a)(2)(ii) cannot be
repaired within 45 days and if the
storage vessel cannot be emptied within
45 days, you may request a 30-day
extension from the Administrator. Such
a request for an extension must
document that alternate storage capacity
is unavailable and specify a schedule of
actions the company will take that will
assure that the control equipment will
be repaired or the storage vessel will be
emptied as soon as possible.
(A) Defects in the internal floating
roof;
(B) Holes, tears, or other openings in
the primary seal, the secondary seal, or
the seal fabric; or
(C) A rim seal or deck fitting control
not meeting the applicable requirements
in § 60.112c(b)(2) through (13).
(3) Compliance with the LEL limit for
internal floating roof storage vessels at
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83326
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
§ 60.112c(b)(16) must be determined
based on the procedures specified in
paragraphs (a)(3)(i) through (v) of this
section. If tubing is necessary to obtain
the measurements, the tubing must be
non-crimping and made of Teflon or
other inert material.
(i) You must conduct LEL monitoring
as part of the annual inspection
specified in paragraph (a)(2)(i) of this
section and at other times upon request
by the Administrator. If the
measurement cannot be performed
during the visual inspection due to
wind speeds exceeding those specified
in paragraph (a)(3)(iii)(C) of this section,
the measurement must be performed
within 30 days of the visual inspection.
If there is an exceedance of the LEL
limit, you must re-monitor in
accordance with § 60.112c(b)(16) within
30 days after repair or placing the
storage vessel back in service.
(ii) The calibration of the LEL meter
must be checked per manufacturer
specifications immediately before and
after the measurements as specified in
paragraphs (a)(3)(ii)(A) and (B) of this
section. If tubing will be used for the
measurements, the tubing must be
attached during calibration so that the
calibration gas travels through the entire
measurement system.
(A) Conduct the span check using a
calibration gas recommended by the
LEL meter manufacturer. The
calibration gas must contain a single
hydrocarbon at a concentration of the
vapor corresponding to 50 percent of the
LEL (e.g., 2.50 percent by volume when
using methane as the calibration gas).
The vendor must provide a Certificate of
Analysis for the gas, and the certified
concentration must be within ±2 percent
(e.g., 2.45 percent–2.55 percent by
volume when using methane as the
calibration gas). The LEL span response
must be between 49 percent and 51
percent. If the span check prior to the
measurements does not meet this
requirement, the LEL meter must be
recalibrated or replaced. If the span
check after the measurements does not
meet this requirement, the LEL meter
must be recalibrated or replaced, and
the measurements must be repeated.
(B) Check the instrumental offset
response using a certified compressed
gas cylinder of zero air or an ambient
environment that is free of organic
compounds. The pre-measurement
instrumental offset response must be 0
percent LEL. If the LEL meter does not
meet this requirement, the LEL meter
must be recalibrated or replaced.
(iii) Conduct the monitoring
measurements as specified in
paragraphs (a)(3)(iii)(A) through (D) of
this section.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(A) Measurements of the vapors
within the internal floating roof storage
vessel must be collected no more than
3 feet above the internal floating roof.
(B) Measurements must be taken for a
minimum of 20 minutes, logging the
measurements at least once every 15
seconds, or until one 5-minute average
as determined according to paragraph
(a)(3)(v)(B) of this section exceeds the
limit specified in § 60.112c(b)(16).
(C) Measurements shall be taken
when the wind speed at the top of the
storage vessel is 5 mph or less to the
extent practicable, but in no case shall
measurements be taken when the
sustained wind speed at top of storage
vessel is greater than the annual average
wind speed at the site or 15 mph,
whichever is less.
(D) Measurements should be
conducted when the internal floating
roof is floating with limited product
movement (limited filling or emptying
of the storage vessel).
(iv) To determine the actual
concentration of the vapor within the
storage vessel, the percent of the LEL
‘‘as the calibration gas’’ must be
corrected according to one of the
procedures in paragraph (a)(3)(iv)(A) or
(B) of this section. Alternatively, if the
LEL meter used has correction factors
that can be selected from the meter’s
program, you may enable this feature to
automatically apply one of the
correction factors in paragraph
(a)(3)(iv)(A) or (B) of this section.
(A) Multiply the measurement by the
published vapor correction factor for the
specific LEL meter, stored VOL, and
calibration gas used; or
(B) If there is no published correction
factor for the specific LEL meter used
and the vapors of the stored VOL,
multiply the measurement by the
published correction factor for butane as
a surrogate for determining the LEL of
the vapors of the stored VOL. The
correction factor must correspond to the
calibration gas used.
(v) Use the calculation procedures in
paragraphs (a)(3)(v)(A) through (C) of
this section to determine compliance
with the LEL limit.
(A) For each minute while
measurements are being taken,
determine the 1-minute average reading
as the arithmetic average of the
corrected individual measurements
(taken at least once every 15 seconds)
during the minute.
(B) Starting with the end of the fifth
minute of data, calculate a 5-minute
rolling average as the arithmetic average
of the previous five 1-minute readings
determined under paragraph (a)(3)(v)(A)
of this section. Determine a new 5-
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
minute average reading for every
subsequent 1-minute reading.
(C) Each 5-minute rolling average
must meet the LEL limit specified in
§ 60.112c(b)(16).
(4) Notify the Administrator as
specified in § 60.116c(b) at least 30 days
prior to the inspection of each storage
vessel for which an inspection is
required by paragraph (a)(1) or (a)(2)(ii)
of this section to afford the
Administrator the opportunity to have
an observer present.
(5) You must equip each affected
storage vessel that has an internal
floating roof with an alarm system that
provides a visual or audible signal that
alerts the operator when the internal
floating roof is approaching the landed
height and that provides a separate
visual or audible signal to alert the
operator when the roof has landed. The
roof is considered landed when the
floating roof first rests on supports or
when the vacuum breaker/automatic
bleeder vent begins to open, whichever
is first (for example, when using a legactuated vent that triggers the vent prior
to resting on the roof supports).
(b) Requirements for an external
floating roof. After installing the control
equipment for an external floating roof
to meet the provisions in § 60.112c(c),
you must inspect the external floating
roof according to the specifications in
paragraphs (b)(1) through (8) of this
section.
(1) Determine the gap areas and
maximum gap widths, between the
primary seal and the wall of the storage
vessel and between the secondary seal
and the wall of the storage vessel
according to the frequency provided in
paragraphs (b)(1)(i) and (ii) of this
section. You must visually inspect all
roof fittings to ensure that covers are
closed and gasketed with no visible gaps
and that there are no tears in sleeves,
wipers, or similar controls used for a
given fitting during each measurement
of gaps as required under this paragraph
(b)(1).
(i) Measurements of gaps between the
storage vessel wall and the primary seal
(seal gaps) must be performed during
the hydrostatic testing of the storage
vessel or within 60 days of the initial fill
with VOL and at least once every 60
calendar months thereafter.
(ii) Measurements of gaps between the
storage vessel wall and the secondary
seal must be performed within 60 days
of the initial fill with VOL and at least
once every 12 calendar months
thereafter.
(iii) If any source ceases to store VOL
for a period of 12 calendar months or
more, subsequent introduction of VOL
into the storage vessel must be
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
considered an initial fill for the
purposes of paragraphs (b)(1)(i) and
(b)(1)(ii) of this section.
(2) Determine gap widths and areas in
the primary and secondary seals
individually by the following
procedures:
(i) Measure seal gaps, if any, at one or
more floating roof levels when the roof
is floating off the roof supports.
(ii) Measure seal gaps around the
entire circumference of the storage
vessel in each place where a 0.125-inch
(0.32-centimeter (cm)) diameter uniform
probe passes freely (without forcing or
binding against seal) between the seal
and the wall of the storage vessel and
measure the circumferential distance of
each such location.
(iii) The total surface area of each gap
described in paragraph (b)(2)(ii) of this
section must be determined by using
probes of various widths to measure
accurately the actual distance from the
storage vessel wall to the seal and
multiplying each such width by its
respective circumferential distance.
(3) Add the gap surface area of each
gap location for the primary seal and the
secondary seal individually and divide
the sum for each seal by the nominal
diameter of the storage vessel and
compare each ratio to the respective
standards in paragraph (b)(4) of this
section.
(4) Except as provided in paragraph
(b)(5) of this section, make necessary
repairs or empty the storage vessel
within 45 days of identification in any
inspection failure as specified in
paragraphs (b)(4)(i) through (iii) of this
section.
(i) For primary seals, any deviation of
the requirements in paragraphs
(b)(4)(i)(A) through (D) of this section is
an inspection failure.
(A) The accumulated area of gaps
between the storage vessel wall and the
mechanical shoe or liquid-mounted
primary seal must not exceed 10 square
inches (in2) per foot of storage vessel
diameter (212 square centimeters (cm2)
per meter of storage vessel diameter).
(B) The maximum width of any
portion of any gap must not exceed 1.5
inches (3.81 cm).
(C) If a mechanical shoe seal is used,
one end of the mechanical shoe is to
extend into the stored liquid, and the
other end is to extend a minimum
vertical distance of 2 feet (61 cm) above
the stored liquid surface.
(D) There are to be no holes, tears, or
other openings in the shoe, seal fabric,
or seal envelope.
(ii) For secondary seals, any deviation
of the requirements in paragraphs
(b)(4)(ii)(A) through (D) of this section is
an inspection failure.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(A) The secondary seal is to be
installed above the primary seal so that
it completely covers the space between
the roof edge and the storage vessel wall
except for allowed gaps as provided in
paragraphs (b)(4)(ii)(B) and (C) of this
section.
(B) The accumulated area of gaps
between the storage vessel wall and the
secondary seal must not exceed 1 in2
per foot (21.2 cm2 per meter) of storage
vessel diameter.
(C) The maximum width of any
portion of any gap must not exceed 0.5
inches (1.27 cm).
(D) There are to be no holes, tears, or
other openings in the seal or seal fabric.
(iii) For roof fittings (e.g., vacuum
breaker/automatic bleeder vents and rim
vents, gauge hatch/sample wells, access
hatches, guidepoles, ladders, and
emergency roof drains), any deviation of
the requirements in paragraphs
(b)(4)(iii)(A) through (D) of this section
is an inspection failure.
(A) Each opening in an external
floating roof except for vacuum breaker/
automatic bleeder vents and the rim
vents provides a projection below the
liquid surface.
(B) Vacuum breaker/automatic
bleeder vents and rim vents are
equipped with a gasket and are closed
with no visible gaps when the roof is
floating.
(C) The gauge hatch/sample well,
access hatch, and gauge float must have
a gasketed cover and closed with no
visible gaps.
(D) There are to be no tears or visible
defects of sleeves, wipers, or fabric
covers used to control emissions from a
roof fitting.
(5) If a failure that is detected as
specified in paragraph (b)(4) of this
section cannot be repaired within 45
days and if the storage vessel cannot be
emptied within 45 days, you may
request a 30-day extension from the
Administrator. Such extension request
must include a demonstration of
unavailability of alternate storage
capacity and a specification of a
schedule that will assure that the
control equipment will be repaired or
the storage vessel will be emptied as
soon as possible.
(6) Notify the Administrator, as
specified in § 60.116c(b)(2), 30 days in
advance of any gap measurements
required by paragraph (b)(1) of this
section to afford the Administrator the
opportunity to have an observer present.
(7) Visually inspect the external
floating roof, primary seal, secondary
seal, and fittings each time the vessel is
emptied and degassed.
(i) If the external floating roof has
defects, the primary seal has holes,
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
83327
tears, or other openings in the seal or
the seal fabric, the secondary seal has
holes, tears, or other openings in the
seal or the seal fabric, covers have
visible openings or missing or torn
gaskets, or there are tears or other
visible defects in flexible covers,
sleeves, wipers, or other fitting controls,
you must repair the items as necessary
so that none of the conditions specified
in this paragraph (b)(7)(i) exist before
filling or refilling the storage vessel with
VOL.
(ii) For each inspection required by
paragraph (b)(7) of this section, notify
the Administrator as specified in
§ 60.116c(b)(1) at least 30 days prior to
the inspection of each storage vessel to
afford the Administrator the
opportunity to inspect the storage
vessel.
(8) You must equip each affected
storage vessel that has an external
floating roof with an alarm system that
provides a visual or audible signal that
alerts the operator when the external
floating roof is approaching the landed
height and that provides a separate
visual or audible signal to alert the
operator when the roof has landed. The
roof is considered landed when the
floating roof first rests on supports or
when the vacuum breaker/automatic
bleeder vent begins to open, whichever
is first (for example, when using a legactuated vent that triggers the vent prior
to resting on the roof supports).
(c) Requirements for closed vent
systems routed to a control device, fuel
gas system, or process. For each source
that is equipped with a closed vent
system and routes to a control device,
fuel gas system, or process to meet the
requirements in § 60.112c(d), you must
conduct performance testing and
monitoring of the control device as
specified in paragraph (c)(1) of this
section, conduct monitoring and
inspections of the closed vent system as
specified in paragraph (c)(2) of this
section, repair leaks as specified in
paragraph (c)(3) of this section, and
develop a monitoring plan as specified
in paragraph (c)(4) of this section.
(1) For each control device used to
meet the requirements in § 60.112c(d),
you must comply with the requirements
in paragraphs (c)(1)(i) through (iv) of
this section, as applicable.
(i) For each enclosed combustion
device or flare, you must install,
calibrate, maintain, and operate a
backpressure regulator valve calibrated
to open at the minimum pressure set
point corresponding to the minimum
inlet gas flow rate. The set point must
be consistent with manufacturer
specifications for minimum flow or
pressure and must be supported by an
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
engineering evaluation. At least
annually, you must confirm that the
backpressure regulator valve set point is
correct and consistent with the
engineering evaluation and
manufacturer specifications and that the
valve fully closes when not in the open
position.
(ii) For each control device other than
a flare, except as specified in paragraph
(c)(1)(iii) of this section, you must
conduct a performance test as specified
in paragraphs (c)(1)(ii)(A) through (E) of
this section not later than 180 days after
becoming subject to § 60.112c(d). You
must conduct subsequent performance
tests within 60 calendar months after
each previous performance test. Submit
the results of all performance tests
following the procedures in
§ 60.116c(e).
(A) Each performance test must
demonstrate that the control device
achieves greater than or equal to the
required control device performance
level specified in § 60.112c(d)(3).
Performance tests must be conducted
under such conditions as the
Administrator specifies based on
representative performance of the
affected source for the period being
tested. You may not conduct
performance tests during periods of
malfunction. You must record the
process information that is necessary to
document operating conditions during
the test and include in such record an
explanation to support that such
conditions represent the entire range of
normal operation, including operational
conditions for maximum emissions if
such emissions are not expected during
maximum production. You must make
available to the Administrator such
records as may be necessary to
determine the conditions of
performance tests.
(B) You must conduct a minimum of
three test runs. Each test run must be at
least 1 hour long.
(C) The following methods in
appendix A to this part, except as
provided in § 60.8(b), must be used as
reference methods to determine
compliance with the percent reduction
requirement.
(1) Method 1 or 1A of appendix A–1
to this part, as appropriate, for selection
of the sampling sites. Sampling sites
must be located at the inlet of the first
control device and at the outlet of the
final control device to determine
compliance with a control device
percent reduction requirement.
(2) Method 2, 2A, 2C, or 2D of
appendix A–1 to this part, as
appropriate to determine the gas
volumetric flow rate.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(3) Method 25A of appendix A–7 to
this part. Use propane as the calibration
gas. You must use Method 4 of
appendix A–3 to this part to convert the
Method 25A of appendix A–7 results to
a dry basis.
(D) You must use the procedures in
paragraphs (c)(1)(ii)(D)(1) and (2) of this
section to calculate percent reduction
efficiency.
(1) You must compute the mass rate
of TOC using the following equations:
Ei = K2CiMpQi
Eo = K2CoMpQo
Equations 1 and 2 to Paragraph
(c)(1)(ii)(D)(1)
Where:
Ei, Eo = Mass rate of TOC at the inlet and
outlet of the control device, respectively,
dry basis, kilograms per hour.
K2 = Constant, 2.494 × 10¥6 (parts per
million) (gram-mole per standard cubic
meter) (kilogram/gram) (minute/hour),
where standard temperature (gram-mole
per standard cubic meter) is 20 degrees
Celsius.
Ci, Co = Concentration of TOC, as propane,
of the gas stream as measured by Method
25A of appendix A–7 to this part at the
inlet and outlet of the control device,
respectively, dry basis, parts per million
by volume.
Mp = Molecular weight of propane, 44.1
gram/gram-mole.
Qi, Qo = Flowrate of gas stream at the inlet
and outlet of the control device,
respectively, dry standard cubic meter
per minute.
(2) You must calculate the percent
reduction in TOC as follows:
Rcd
= E-i E--E
O
X
100°1.
70
i
Equation 3 to Paragraph (c)(1)(ii)(D)(2)
Where:
Rcd = Control efficiency of control device,
percent.
Ei = Mass rate of TOC at the inlet to the
control device as calculated under
paragraph (c)(1)(ii)(D)(1) of this section,
kilograms per hour.
Eo = Mass rate of TOC at the outlet of the
control device, as calculated under
paragraph (c)(1)(ii)(D)(1) of this section,
kilograms per hour.
(E) Except as provided in paragraph
(c)(1)(ii)(E)(5) of this section, you must
establish the applicable operating
parameter limit as specified in
paragraphs (c)(1)(ii)(E)(1) through (3) of
this section by calculating the value(s)
as the arithmetic average of operating
parameter measurements recorded
during the three test runs conducted for
the most recent performance test (the
average of the test run averages). You
may operate outside of the established
operating parameter limit(s) during
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
subsequent performance tests in order to
establish new operating limits. You
must include the updated operating
limits with the performance test results
submitted to the Administrator pursuant
to § 60.116c(e). Upon establishment of a
new operating limit, you must thereafter
operate under the new operating limit.
You must demonstrate compliance with
your operating parameter according to
paragraph (c)(1)(ii)(E)(4) of this section.
(1) If you use an enclosed combustion
device, a boiler, or a process heater
other than those specified in paragraph
(c)(1)(iii) of this section to control
emissions, you must set a minimum
firebox temperature limit during the
performance test. You must
continuously monitor the firebox
temperature with a temperature
monitoring device installed in the
firebox or in the ductwork immediately
downstream from the firebox in a
position before any substantial heat
exchange occurs and equipped with a
continuous recorder that records a
reading at least once every 15 minutes.
The monitoring device must have a
minimum accuracy of ±1 percent of the
temperature being monitored in degrees
Celsius, or ±2.5 degrees Celsius,
whichever value is greater.
(2) If you use a catalytic incinerator
other than those specified in paragraph
(c)(1)(iii) of this section to control
emissions, you must set a minimum
temperature limit on the temperature at
the inlet of the catalyst bed and a
minimum temperature limit on the
temperature difference between the
catalyst bed outlet and inlet. You must
continuously monitor the temperatures
with a temperature monitoring device
equipped with a continuous recorder
that records a reading at least once every
15 minutes. The device must be capable
of monitoring temperature at two
locations and have a minimum accuracy
of ±1 percent of the temperature being
monitored in degrees Celsius, or ±2.5
degrees Celsius, whichever value is
greater. You must install one
temperature sensor in the vent stream at
the nearest feasible point to the catalyst
bed inlet, and you must install a second
temperature sensor in the vent stream at
the nearest feasible point to the catalyst
bed outlet. You must install the
temperature sensor at a location
representative of the firebox
temperature.
(3) If you use a control device other
than a flare or other than a device listed
in paragraphs (c)(1)(ii)(E)(1),
(c)(1)(ii)(E)(2), (c)(1)(ii)(E)(5), or
(c)(1)(iii) to control emissions, you must
submit the operating parameters you
plan to monitor in the performance test
E:\FR\FM\15OCR4.SGM
15OCR4
ER15OC24.000
khammond on DSKJM1Z7X2PROD with RULES4
83328
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
notice you provide to the Administrator
pursuant to § 60.8(d).
(4) Using the continuous monitoring
system (CMS) data, you must calculate
the hourly average of each operating
parameter. You must demonstrate
compliance by maintaining the
operating parameter at or above the
minimum operating parameter limit on
a 3-hour rolling average basis. For each
hour, calculate the hourly value of the
operating parameter from your CMS.
Average the three most recent hours of
data to determine the 3-hour average.
Determine the 3-hour rolling average by
recalculating the 3-hour average each
hour. You must not include periods of
data collected during monitoring system
breakdowns, repairs, maintenance
periods, instrument adjustments, or
checks to maintain precision and
accuracy in the operating parameter
averages.
(5) For enclosed combustion devices
for which you elect to comply with the
flare requirements in § 60.112c(d)(5),
you must comply with the monitoring
provisions in paragraph (c)(1)(iv) of this
section instead of paragraphs
(c)(1)(ii)(E)(1) through (4) of this section.
(iii) No performance test is required
for the control devices identified in
paragraphs (c)(1)(iii)(A) through (C) of
this section.
(A) A boiler or process heater with a
design heat input capacity of 44
megawatts (150 million British thermal
units per hour) or greater.
(B) A boiler or process heater into
which the vent stream is introduced
with the primary fuel.
(C) A boiler, process heater, or
incinerator burning hazardous waste,
which is regulated under 40 CFR part
63, subpart EEE; part 264; part 265; or
part 266.
(iv) For each source that is equipped
with a closed vent system and a flare to
meet the requirements in § 60.112c(d) or
enclosed combustion device electing to
comply with the requirements in
§ 60.112c(d)(5), you must conduct
visible emission observations as
specified in paragraph (c)(1)(iv)(A) of
this section and install, operate, and
maintain CMS for flares following the
requirements specified in 40 CFR 63.671
and as specified in paragraphs
(c)(1)(iv)(B) and (C) of this section.
(A) If visible emissions are observed
for more than 1 continuous minute
during normal duties, visible emissions
observation using Method 22 of
appendix A–7 to this part must be
conducted for 2 hours or until 5minutes of visible emissions are
observed.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(B) Substitute ‘‘pilot flame or flare
flame’’ for each occurrence of ‘‘pilot
flame.’’
(C) As an alternative to determining
the flare tip velocity rate for each 15minute block to determine compliance
with the flare tip velocity operating
limit as specified in 40 CFR
63.670(k)(2), you may elect to conduct
a one-time flare tip velocity operating
limit compliance assessment as
provided in paragraphs (c)(1)(iv)(C)(1)
through (4) of this section. If the flare or
storage vessel control configurations
change (e.g., flare tip modified or
additional storage vessel or other
sources are added for which vapors are
directed to the flare), you must repeat
this one-time assessment based on the
new configuration.
(1) Determine the unobstructed crosssectional area of the flare tip, in units of
square feet, as specified in 40 CFR
63.670(k)(1).
(2) Determine the maximum flow rate,
in units of cubic feet per second, based
on the maximum cumulative loading
rate for a 15-minute block period
considering maximum filling rates for
all storage vessel affected facilities
controlled by the flare and, if
applicable, considering the maximum
release pressure of any other vapors
directed to the flare.
(3) Calculate the maximum flare tip
velocity as the maximum flow rate from
paragraph (c)(1)(iv)(C)(2) of this section
divided by the unobstructed crosssectional area of the flare tip from
paragraph (c)(1)(iv)(C)(1) of this section.
(4) Demonstrate that the maximum
flare tip velocity as calculated in
paragraph (c)(1)(iv)(C)(3) of this section
is less than 60 feet per second.
(2) For each closed vent system, you
must conduct the instrument
monitoring in paragraphs (c)(2)(i)
through (iii) of this section. You must
conduct the initial instrument
monitoring within 180 days of an
affected facility being connected to the
closed vent system. Subsequent
instrument inspections must be
conducted within 365 days of the
previous inspection. Visual, audible,
and olfactory inspections must be
conducted quarterly.
(i) Conduct instrument monitoring
using the procedures in Method 21 of
appendix A–7 to this part. The detection
instrument must meet the performance
criteria of Method 21 of appendix A–7,
except that the instrument response
factor criteria in section 8.1.1 of Method
21 of appendix A–7 must be for the
average composition of the fluid and not
for each individual organic compound
in the stream. For streams that contain
nitrogen, air, water, or other inerts that
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
83329
are not organic VOC, the representative
stream response factor must be
determined on an inert-free basis. The
instrument reading that defines a leak is
500 ppmv (as methane). The instrument
shall be calibrated before use each day
of its use by the procedures specified in
Method 21 of appendix A–7. The
calibration gases in paragraphs
(c)(2)(i)(A) and (B) of this section must
be used. The drift assessment specified
in paragraph (c)(2)(i)(C) of this section
must be performed at the end of each
monitoring day.
(A) Zero air (less than 10 ppm of
hydrocarbon in air).
(B) A mixture of methane in air at a
concentration of approximately 500
ppmv.
(C) At the end of each monitoring day,
check the instrument using the same
calibration gas that was used to calibrate
the instrument before use. Follow the
procedures specified in Method 21 of
appendix A–7 to this part, section 10.1,
except do not adjust the meter readout
to correspond to the calibration gas
value. If multiple scales are used, record
the instrument reading for each scale
used. Divide the arithmetic difference of
the initial and post-test calibration
response by the corresponding
calibration gas value for each scale and
multiply by 100 to express the
calibration drift as a percentage. If a
calibration drift assessment shows a
negative drift of more than 10 percent,
then re-monitor all equipment
monitored since the last calibration with
instrument readings between the leak
definition and the leak definition
multiplied by (100 minus the percent of
negative drift) divided by 100. If any
calibration drift assessment shows a
positive drift of more than 10 percent
from the initial calibration value, then,
at the owner/operator’s discretion, all
equipment with instrument readings
above the leak definition and below the
leak definition multiplied by (100 plus
the percent of positive drift) divided by
100 monitored since the last calibration
may be re-monitored.
(ii) Any parts of the closed vent
system that are designated as unsafe to
inspect are exempt from the inspection
requirements of paragraph (c)(2)(i) of
this section if the conditions of
paragraphs (c)(2)(ii)(A) and (B) of this
section are met.
(A) The owner or operator determines
that the equipment is unsafe-to-inspect
because inspecting personnel would be
exposed to an imminent or potential
danger as a consequence of complying
with paragraph (c)(2)(i) of this section;
and
(B) The owner or operator has a
written plan that requires inspection of
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83330
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
the equipment as frequently as practical
during safe-to-inspect times. Inspection
is not required more than once
annually.
(iii) Any parts of the closed vent
system that are designated as difficultto-inspect are exempt from the
inspection requirements of paragraph
(c)(2)(i) of this section if the provisions
of paragraphs (c)(2)(iii)(A) and (B) of
this section apply.
(A) The owner or operator determines
that the equipment cannot be inspected
without elevating the inspecting
personnel more than 2 meters (7 feet)
above a support surface; and
(B) The owner or operator has a
written plan that requires inspection of
the equipment at least once every 60
calendar months.
(3) Leaks, as indicated by an
instrument reading greater than 500
ppmv or emissions detected by visible,
audible, and olfactory methods, shall be
repaired as soon as practical following
the requirements outlined in paragraphs
(c)(3)(i) and (ii) of this section.
(i) Except as allowed by paragraph
(c)(3)(ii) of this section, a first attempt
at repair shall be made no later than 5
days after the leak is detected. Repairs
shall be completed no later than 15 days
after the leak is detected or at the
beginning of the next introduction of
vapors to the system, whichever is later.
(ii) Delay of repair of a closed vent
system for which leaks have been
detected is allowed if repair within 15
days after a leak is detected is
technically infeasible or unsafe or if the
owner or operator determines that
emissions resulting from immediate
repair would be greater than the
emissions likely to result from delay of
repair. Repair of such equipment shall
be completed as soon as practical.
(4) You must develop a monitoring
plan that covers each CMS used to
demonstrate continuous compliance for
your control device as outlined in
paragraphs (c)(4)(i) and (ii) of this
section. You must install, calibrate,
operate, and maintain each CMS in
accordance with the procedures in your
monitoring plan.
(i) For each control device other than
those specified in paragraph (c)(4)(ii) of
this section, your monitoring plan must
contain the information required in
paragraphs (c)(4)(i)(A) through (G) of
this section.
(A) The parameter to be monitored
and the operating limit for the
parameter.
(B) Sampling interface (e.g.,
thermocouple) location such that the
monitoring system will provide
representative measurements.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(C) Description of the monitoring
system specifications, including the
detector signal analyzer, data
acquisition, and calculations.
(D) Equipment performance checks,
system accuracy audits, or other audit
procedures, including the information
in paragraphs (c)(4)(i)(D)(1) through (4)
of this section.
(1) You must conduct the CMS
equipment performance checks, system
accuracy audits, or other audit
procedures specified in the monitoring
plan at least once every 12 calendar
months.
(2) You must also conduct calibration
checks following any period of more
than 24 hours throughout which the
sensor exceeded the manufacturer’s
specified maximum range unless you
install a new sensor.
(3) At least quarterly, you must
inspect all components for integrity and
all electrical connections for continuity,
oxidation, and galvanic corrosion,
unless you use a redundant CMS.
(4) Daily checks for indications that
the system is responding.
(E) Description of how periods of data
collected during CMS breakdowns, outof-control periods, repairs, maintenance
periods, instrument adjustments, or
checks to maintain precision and
accuracy, calibration checks, and zero
(low-level), mid-level (if applicable),
and high-level adjustments will be
excluded from operating parameter
averages.
(F) Ongoing operation and
maintenance procedures.
(G) Ongoing recordkeeping
procedures.
(ii) For each flare or enclosed
combustion device for with you elect to
comply with the flare provisions in
§ 60.112c(d)(5), your monitoring plan
must contain the information required
by 40 CFR 63.671(b).
(d) Requirements for determining
maximum true vapor pressure. For each
affected storage vessel, you must
determine the maximum true vapor
pressure of the stored VOL according to
the requirements specified in
paragraphs (d)(1) and (2) of this section.
For storage vessels operated above or
below ambient temperatures, the
maximum true vapor pressure is
calculated based upon the highest
expected calendar-month average of the
storage temperature. For storage vessels
operated at ambient temperatures, the
maximum true vapor pressure is
calculated based upon the maximum
local monthly average ambient
temperature as reported by the National
Weather Service.
(1) Prior to the initial filling of the
storage vessel or to the refilling of the
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
storage vessel with a new VOL, the
highest maximum true vapor pressure
for the range of anticipated liquids to be
stored, including mixtures for which
you can define the range of
concentrations for constituents in the
mixture or with a known maximum
Reid vapor pressure, must be
determined using any one of the
methods described in paragraphs
(d)(1)(i) through (iv) of this section.
(i) As obtained from standard
reference texts.
(ii) ASTM D6377–20 (incorporated by
reference; see § 60.17). Perform the
method using a vapor-to-liquid ratio of
4:1, which is expressed in the method
as VPCR.
(iii) ASTM D6378–22 (incorporated
by reference; see § 60.17). Perform the
method using a vapor-to-liquid ratio of
4:1.
(iv) As measured by an appropriate
method as approved by the
Administrator.
(2) For each affected storage vessel
storing a mixture of indeterminate
composition or a mixture of unknown
variable composition, the initial
determination of the vapor pressure
required by paragraph (d)(1) of this
section must be a physical test using
one of the methods specified in
paragraphs (d)(1)(ii) through (iv) of this
section. Additional physical tests using
one of the methods specified in
paragraphs (d)(1)(ii) through (iv) of this
section are required at least once every
6 calendar months thereafter as long as
the measured vapor pressure remains
below the applicable thresholds in
§ 60.110c(c)(1), (c)(2), (d)(1), or (d)(2). If
the vapor pressure measured under this
paragraph (d)(2) exceeds the threshold
defined in § 60.110c(c)(1), (c)(2), (d)(1),
or (d)(2) you must meet the
requirements in § 60.112c and the
corresponding requirements in
§§ 60.113c through 60.116c. If the
storage vessel does not have controls
meeting the requirements in § 60.112c,
the storage vessel must be emptied and
taken out of service until controls
meeting the requirements in § 60.112c
can be installed. Upon compliance with
the provisions in § 60.112c, no
additional vapor pressure monitoring is
required.
§ 60.114c Alternative means of emission
limitation.
(a) If, in the Administrator’s
judgment, an alternative means of
emission limitation will achieve a
reduction in emissions at least
equivalent to the reduction in emissions
achieved by the applicable requirement
in § 60.112c, the Administrator will
publish in the Federal Register a
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
document permitting the use of the
alternative means for purposes of
compliance with that requirement.
(b) Any document under paragraph (a)
of this section will be published only
after notice and an opportunity for a
hearing.
(c) Any person seeking permission
under this section must submit to the
Administrator a written application
including either:
(1) An actual emissions test that uses
a full-sized or scale-model storage vessel
that accurately collects and measures all
VOC emissions from a given control
device and that accurately simulates
wind and accounts for other emission
variables such as temperature and
barometric pressure; or
(2) An engineering evaluation that the
Administrator determines is an accurate
method of determining equivalence.
(d) The Administrator may condition
the permission on requirements that
may be necessary to ensure operation
and maintenance to achieve the same
emission reduction as specified in
§ 60.112c.
khammond on DSKJM1Z7X2PROD with RULES4
§ 60.115c
Recordkeeping requirements.
(a) Except as otherwise specified in
paragraphs (b) through (d) of this
section, you must keep copies of all
records required by this section and all
reports required under § 60.116c for at
least 5 years.
(b) For each storage vessel affected
facility as specified in § 60.110c(a), you
must keep readily accessible records for
the life of the source showing the
dimension of the storage vessel and an
analysis showing the capacity of the
storage vessel.
(c) Except as provided in paragraphs
(c)(1) and (2) of this section, for each
storage vessel affected facility under this
subpart, you must maintain a record of
the VOL currently stored, including a
description of the VOL stored, the date
when the VOL was first stored in the
storage vessel, and the maximum true
vapor pressure of that VOL.
(1) For each vessel storing a mixture
of indeterminate or variable
composition that meets the
requirements for vapor pressure
measurement at least once every 6
calendar months in § 60.113c(d), you
must maintain records of each vapor
pressure measurement for 5 years.
(2) Each vessel equipped with a
closed vent system routed to a control
device, fuel gas system, or process
meeting the specification of § 60.112c(d)
is exempt from the requirements of
paragraph (c) of this section.
(d) For each storage vessel as
specified in § 60.112c(a), you must keep
records as required in paragraphs (d)(1)
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
through (5) of this section, as applicable
depending upon the control equipment
installed to meet the requirements of
§ 60.112c.
(1) After installing control equipment
for an internal floating roof to meet the
provisions in § 60.112c(b), you must
keep the following records.
(i) Keep a record of each inspection
performed as required by
§ 60.113c(a)(1), (a)(2)(i), and (a)(2)(ii).
Each record must identify the storage
vessel on which the inspection was
performed and must contain the date
the vessel was inspected and the
observed condition of each component
of the control equipment (seals, internal
floating roof, and fittings).
(ii) For each LEL monitoring event,
keep records as specified in paragraphs
(a)(1)(ii)(A) through (I) of this section.
(A) Date and time of the LEL
monitoring, and the storage vessel being
monitored.
(B) A description of the monitoring
event (annual monitoring conducted
concurrent with visual inspection
required under § 60.113c(a)(2)(i); remonitoring due to high winds during
annual monitoring; re-monitoring after
repair attempt; other monitoring event
as required by the Administrator).
(C) Wind speed at the top of the
storage vessel on the date of LEL
monitoring.
(D) The LEL meter manufacturer and
model number used, as well as an
indication of whether tubing was used
during the LEL monitoring, and if so,
the type and length of tubing used.
(E) Calibration checks conducted
before and after making the
measurements, including both the span
check and instrumental offset. This
includes the hydrocarbon used as the
calibration gas, the Certificate of
Analysis for the calibration gas(es), the
results of the calibration check, and any
corrective action for calibration checks
that do not meet the required response.
(F) Location of the measurements and
the location of the floating roof.
(G) Each measurement (taken at least
once every 15 seconds). The records
should indicate whether the recorded
values were automatically corrected
using the meter’s programming. If the
values were not automatically corrected,
record both the raw (as the calibration
gas) and corrected measurements, as
well as the correction factor used.
(H) Each of the 5-minute rolling
average readings.
(I) If the vapor concentration of the
storage vessel was above 25 percent of
the LEL on a 5-minute rolling average
basis, a description of whether the
floating roof was repaired, replaced, or
taken out of service.
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
83331
(2) After installing control equipment
for an external floating roof to meet the
provisions in § 60.112c(c), you must
keep a record of each inspection and
gap measurement performed as required
by § 60.113c(b). The record must
contain:
(i) Identification of the storage vessel
on which the inspection was performed;
(ii) The date the storage vessel was
inspected;
(iii) The type of inspection
[inspection with gap measurements as
specified in § 60.113c(b)(1) through (4);
visual inspection as specified in
§ 60.113c(b)(7)];
(iv) The observed condition of each
component of the control equipment
(seals, internal floating roof, and
fittings); and
(v) For each inspection with gap
measurements as specified in
§ 60.113c(b)(1) through (4):
(A) The raw data obtained in the
measurement; and
(B) The calculations described in
§ 60.113c(b)(2) and (b)(3).
(3) After installing a closed vent
system routed to a control device, fuel
gas system, or process to comply with
the provisions in § 60.112c(d), you must
keep the following records, as well as
the records in paragraph (d)(4) or (5) of
this section, as applicable.
(i) The make and model of the
backpressure regulator valve, date of
installation, and inlet flow rating.
Maintain records of the engineering
evaluation and manufacturer
specifications that identify the pressure
set point corresponding to the minimum
inlet gas flow rate, the annual
confirmation that the backpressure
regulator valve set point is correct and
consistent with the engineering
evaluation and manufacturer
specifications, and the annual
confirmation that the backpressure
regulator valve fully closes when not in
open position.
(ii) The CMS monitoring plan
required by § 60.113c(c)(4), if the closed
vent system is routed to a control
device. Retain this plan for the life of
the control equipment.
(iii) Monitoring for the closed vent
system conducted under § 60.113c(c)(2),
including the date of inspection.
(iv) The written plan(s) required
under § 60.113c(c)(2)(ii) and (iii) for
unsafe-to-inspect and difficult-toinspect portions of the closed vent
system.
(v) For each leak detected during the
monitoring conducted under
§ 60.113c(c)(2) and (3), you must record:
the date the leak was detected; the
location of the leak; the method used to
detect the leak (Method 21 of appendix
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83332
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
A–7 to this part or visible, audible, and
olfactory methods); and the maximum
concentration reading obtained by
Method 21 of appendix A–7, if
applicable. For each repair attempt, you
must record: the date of each repair
attempt; the actions taken to repair the
leak during each repair attempt; and
date the repair was completed. If the
repair is delayed, you must record the
reason for the delay and the date you
expect to complete the repair.
(vi) For each bypass line, maintain a
record of the following, as applicable:
readings from the flow indicator; each
inspection of the seal or closure
mechanism; the date and time of each
instance when the seal mechanism is
broken, the bypass line valve position
has changed, or the key for a lock-andkey type lock has been checked out.
(vii) For each pressure relief device or
vacuum breaking device on a storage
vessel or closed vent system required to
be monitored according to
§ 60.112c(d)(1)(iii) or (d)(2)(iii): the
device type; the monitoring device or
system used for the device; data from
the device or system indicating whether
a pressure release occurred; and the
date, time, and duration of each
pressure release, if applicable.
(4) After installing a closed vent
system routed to a control device other
than a flare or enclosed combustion
device electing to comply with
§ 60.112c(d), you must keep the
following records.
(i) Each performance test.
(ii) All CMS performance checks,
audits, maintenance, and repairs.
(iii) The hourly values recorded by
the CMS and all 3-hour rolling averages.
(iv) The periods when the CMS is not
operational.
(5) After installing a closed vent
system routed to a flare to comply with
§ 60.112c(d) or an enclosed combustion
device for which you elected to comply
with § 60.112c(d)(5), you must keep the
following records.
(i) Pilot flame or flare flame
monitoring as specified in paragraphs
(d)(5)(i)(A) and (B) of this section.
(A) The output of the monitoring
device used to detect the presence of a
pilot flame as required in 40 CFR
63.670(b). Retain these records for a
minimum of 2 years.
(B) Each 15-minute block during
which there was at least 1 minute that
no pilot flame was present when VOL
vapors were routed to the flare. Each
record must identify the start and end
time and date of each 15-minute block.
(ii) Visible emissions observations as
specified in paragraphs (d)(5)(ii)(A)
through (B) of this section, as
applicable.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(A) If visible emissions observations
are performed using Method 22 of
appendix A–7 to this part, the record
must identify the date, the start and end
time of the visible emissions
observation, and the number of minutes
for which visible emissions were
observed during the observation. If the
owner or operator performs visible
emissions observations more than one
time during a day, include separate
records for each visible emissions
observation performed.
(B) For each 2-hour period for which
visible emissions are observed for more
than 5 minutes in 2 consecutive hours
but visible emissions observations
according to Method 22 of appendix A–
7 to this part were not conducted for the
full 2-hour period, the record must
include the date, the start and end time
of the visible emissions observation, and
an estimate of the cumulative number of
minutes in the 2-hour period for which
emissions were visible based on best
information available to the owner or
operator.
(iii) Each 15-minute block period
during which operating values are
outside of the applicable operating
limits specified in 40 CFR 63.670(d)
through (f) when vapors from a storage
vessel affected facility are directed to
the flare for at least 15-minutes
identifying each specific operating limit
that was not met.
(iv) The 15-minute block average
cumulative flows for the enclosed
combustion device vent gas or flare vent
gas and, if applicable, total steam,
perimeter assist air, and premix assist
air specified to be monitored under 40
CFR 63.670(i), along with the date and
start and end time for the 15-minute
block. If multiple monitoring locations
are used to determine cumulative vent
gas flow, total steam, perimeter assist
air, and premix assist air, retain records
of the 15-minute block average flows for
each monitoring location for a minimum
of 2 years, and retain the 15-minute
block average cumulative flows that are
used in subsequent calculations for a
minimum of 5 years. If pressure and
temperature monitoring is used, retain
records of the 15-minute block average
temperature, pressure and molecular
weight of the flare vent gas, enclosed
combustion device vent gas, or assist gas
stream for each measurement location
used to determine the 15-minute block
average cumulative flows for a
minimum of 2 years, and retain the 15minute block average cumulative flows
that are used in subsequent calculations
for a minimum of 5 years.
(v) The flare vent gas or enclosed
combustion device vent gas
compositions specified to be monitored
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
under 40 CFR 63.670(j). Retain records
of individual component concentrations
from each compositional analyses for a
minimum of 2 years. If an NHVvg
analyzer is used, retain records of the
15-minute block average values for a
minimum of 5 years, as well as records
of quality assurance activities
conducted on the analyzer and any
cylinder gas certificates. If you
demonstrate your gas streams have
consistent composition using the
provisions in 40 CFR 63.670(j)(6), retain
records of the current application for
which you are using for as long as you
use the fixed NHVvg as determined
using the provisions in 40 CFR
63.670(j)(6).
(vi) Each 15-minute block average
operating parameter calculated
following the methods specified in 40
CFR 63.670(k) through (n), as
applicable.
(vii) All periods during which you did
not perform monitoring according to the
procedures in 40 CFR 63.670(g), (i), and
(j) as applicable. Note the start date,
start time, and duration in minutes for
each period.
(viii) If you conduct a one-time flare
tip velocity operating limit compliance
assessment according to
§ 60.113c(c)(1)(iv)(C), a copy of the
assessment, including all calculations
for as long as you use this compliance
method.
(ix) For each parameter monitored
using a CMS, retain the records
specified in paragraphs (d)(5)(ix)(A)
through (C) of this section, as
applicable:
(A) For each deviation, record the
start date and time, duration, cause, and
corrective action taken.
(B) For each period when there is a
CMS outage or the CMS is out of
control, record the start date and time,
duration, cause, and corrective action
taken.
(C) Each inspection or calibration of
the CMS including a unique identifier,
make, and model number of the CMS,
and date of calibration check.
(x) For an enclosed combustion
device for which you elected to comply
with § 60.112c(d)(5), you must also keep
a copy of each performance test.
(e) If you are required to meet the
degassing requirements in
§ 60.112c(a)(3), you must maintain
records necessary to demonstrate
compliance with the requirements in
§ 60.112c(e) including, if appropriate,
records of existing standard site
procedures used to empty and degas
(deinventory) equipment for safety
purposes.
E:\FR\FM\15OCR4.SGM
15OCR4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
§ 60.116c
Reporting requirements.
(a) Initial notification requirements.
You must submit initial notifications to
the Administrator within 60 days after
October 15, 2024 or within 60 days after
becoming an affected storage vessel,
whichever is later. Once the report
template for this subpart has been
available on the Compliance and
Emissions Data Reporting Interface
(CEDRI) website (https://www.epa.gov/
electronic-reporting-air-emissions/cedri)
for 1 year, you must submit all
subsequent initial notifications using
the appropriate electronic report
template on the CEDRI website for this
subpart and following the procedure
specified in paragraph (f) of this section.
The date report templates become
available will be listed on the CEDRI
website. For each storage vessel affected
facility subject to the standards in
§ 60.112c, include the following
information in the initial notification:
(1) The following general facility
information:
(i) Facility name;
(ii) Facility physical address,
including city, county, State, and zip
code;
(iii) Latitude and longitude of
facility’s physical location. Coordinates
must be in decimal degrees with at least
five decimal places; and
(iv) The following information for the
facility contact person:
(A) Name;
(B) Mailing address, including city,
county, State, and zip code;
(C) Telephone number; and
(D) Email address.
(2) Identification of the storage
vessel(s) subject to this subpart.
(3) Capacity (in gallons) of each
storage vessel.
(4) Maximum true vapor pressure of
the liquid stored (in psia) in each
storage vessel.
(5) Indication of the standards for
which the storage vessel complies
[§§ 60.112c(b); 60.112c(c); 60.112c(d);
60.112c(e)].
(6) If you route emissions to a control
device, specify the design of the storage
vessel and closed vent system (i.e.,
storage vessel designed according to
§ 60.112c(d)(1)(i); or closed vent system
designed according to
§ 60.112c(d)(1)(ii)), the type of control
device (i.e., enclosed combustion device
complying with temperature operating
limit; enclosed combustion device
electing to comply with § 60.112c(d)(5);
process heater or boiler; catalytic
incinerator; flare, or other control device
(specify)).
(7) If you route emissions to a process,
submit the information specified in
§ 60.112c(d)(6)(ii) and (iii).
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(8) If you route emissions to a fuel gas
system, as specified in
§ 60.112c(d)(6)(iv), submit a statement
that the emission stream is connected to
the fuel gas system.
(b) Other notifications. Submit
notifications for filling and refilling an
affected storage vessel and for
conducting gap measurements as
specified in paragraphs (b)(1) and (2) of
this section.
(1) As specified in § 60.113c(a)(4) and
(b)(7)(ii), you must notify the
Administrator at least 30 days prior to
inspection of each storage vessel for
which an inspection is required by
§ 60.113c(a)(1), (a)(2)(ii) or (b)(7) to
afford the Administrator the
opportunity to have an observer present.
Submit the notification using CEDRI as
specified in paragraph (f) of this section.
If the inspection required by
§ 60.113c(a)(2)(ii) or (b)(7) is not
planned and you could not have known
about the inspection 30 days in advance
of refilling the storage vessel, you must
notify the Administrator at least 7 days
prior to the refilling of the storage
vessel. Notification shall be made by
telephone immediately followed by
written documentation using CEDRI
demonstrating why the inspection was
unplanned.
(2) As specified in § 60.113c(b)(6), you
must notify the Administrator 30 days
in advance of any gap measurements
required by § 60.113c(b)(1) to afford the
Administrator the opportunity to have
an observer present. Submit the
notification using CEDRI as specified in
paragraph (f) of this section. If the
inspection required by § 60.113c(b)(1) is
not planned and you could not have
known about the inspection 30 days in
advance of the gap measurement, you
must notify the Administrator at least 7
days prior to the conducting the gap
measurement. Notification must be
made by telephone immediately
followed by written documentation
using CEDRI demonstrating why the gap
measurement was unplanned.
(c) Reporting requirements for
semiannual report. You must submit to
the Administrator semiannual reports
with the applicable information in
paragraphs (c)(1) through (12) of this
section by the dates specified in
paragraph (d) of this section. For this
subpart, the semiannual reports
supersede the excess emissions and
monitoring systems performance report
and/or summary report form required
under § 60.7. Once the report template
for this subpart has been available on
the CEDRI website (https://
www.epa.gov/electronic-reporting-airemissions/cedri) for 1 year, you must
submit all subsequent reports using the
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
83333
appropriate electronic report template
on the CEDRI website for this subpart
and following the procedure specified
in paragraph (f) of this section. The date
report templates become available will
be listed on the CEDRI website. Unless
the Administrator or delegated State
agency or other authority has approved
a different schedule for submission of
reports, the report must be submitted by
the deadline specified in this subpart,
regardless of the method in which the
report is submitted.
(1) Report the following general
facility information:
(i) Facility name;
(ii) Facility physical address,
including city, county, and State;
(iii) Latitude and longitude of
facility’s physical location. Coordinates
must be in decimal degrees with at least
five decimal places;
(iv) The following information for the
facility contact person:
(A) Name;
(B) Mailing address;
(C) Telephone number; and
(D) Email address.
(v) Date of report and beginning and
ending dates of the reporting period.
You are no longer required to provide
the date of report when the report is
submitted via CEDRI; and
(vi) Statement by a responsible
official, with that official’s name, title,
and signature, certifying the truth,
accuracy, and completeness of the
content of the report. If your report is
submitted via CEDRI, the certifier’s
electronic signature during the
submission process replaces the
requirement in this paragraph (c)(1)(vi).
(2) For storage vessels complying with
the provisions of § 60.112c(b) or (c):
(i) Identification of the storage vessel
and an indication of whether you
comply with § 60.112c(b) or (c).
(ii) An indication whether the storage
vessel was inspected during the
reporting period, and if so, the date and
type of each inspection conducted
during the reporting period [the type of
inspection shall be selected from the
following list: initial IFR inspection
according to § 60.113c(a)(1), IFR visual
inspection from fixed roof according to
§ 60.113c(a)(2)(i), combined IFR visual
inspection with LEL monitoring
according to § 60.113c(a)(2)(i) and (3),
internal IFR inspection according to
§ 60.113c(a)(2)(ii), IFR LEL monitoring
according to § 60.113c(a)(3), EFR gap
measurements according to
§ 60.113c(b)(1) through (4), or visual
EFR inspection according to
§ 60.113c(b)(7)].
(iii) For storage vessels complying
with the provisions of § 60.112c(b) that
were not inspected according to
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
83334
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
§ 60.113c(a)(2)(ii) during the reporting
period, report the last date the storage
vessel was inspected according to the
provisions in § 60.113c(a)(2)(ii).
(3) For each failure of a visual
inspection required under
§ 60.113c(a)(2)(i), report the information
in paragraphs (c)(3)(i) through (iii) of
this section. For each failure of LEL
monitoring required under
§ 60.113c(a)(3), report the information in
paragraphs (c)(3)(i) through (iv) of this
section.
(i) Identification of the storage vessel;
(ii) The date of the inspection;
(iii) The nature of the defects; and
(iv) The following information
regarding the LEL monitoring
conducted:
(A) Date and start and end times of
the LEL monitoring conducted.
(B) Wind speed in miles per hour at
the top of the storage vessel on the date
of LEL monitoring.
(C) The highest 5-minute rolling
average reading during the monitoring
event.
(D) If re-monitoring was required due
to excessive wind or repair during the
visual inspection, report the information
in paragraphs (b)(3)(iv)(A) through (C) of
this section for the re-monitoring event.
(E) Whether the floating roof was
repaired, replaced, or taken out of VOL
service. If the storage vessel was taken
out of VOL service, report the date the
storage vessel was emptied. If the
floating roof was replaced or repaired,
report the nature of and date the repair
was made and the information in
paragraphs (b)(3)(iv)(A) through (C) of
this section for each re-monitoring
conducted to confirm the repair.
(4) For each inspection required by
§ 60.113c(a)(2)(ii) that finds holes or
tears in the seal or seal fabric, defects in
the internal floating roof, or other
control equipment defects listed in
§ 60.113c(a)(2)(ii), report:
(i) Identification of the storage vessel
and date of inspection;
(ii) The reason it did not meet the
specifications of § 60.112c(b) or
§ 60.113c(a)(2)(ii);
(iii) A description of each repair
made; and
(iv) Date of repair.
(5) For each inspection required
under § 60.113c(b)(1), report the
following information:
(i) Identification of the storage vessel
and the date of the inspection;
(ii) The accumulated area of gaps
between the storage vessel wall and the
primary seal (in square inches per foot
of storage vessel diameter);
(iii) The maximum width of any
portion of any gap in the primary seal
(in inches);
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(iv) The accumulated area of gaps
between the storage vessel wall and the
secondary seal (in square inches per foot
of storage vessel diameter);
(v) The maximum width of any
portion of any gap in the secondary seal
(in inches); and
(vi) An indication whether there was
an inspection failure. If there was an
inspection failure, also include the
following information in the report:
(A) An indication of the type of
deviation(s) [indicating all that apply
from: §§ 60.113c(b)(4)(i)(A),
60.113c(b)(4)(i)(B), 60.113c(b)(4)(i)(C),
60.113c(b)(4)(i)(D), 60.113c(b)(4)(ii)(A),
60.113c(b)(4)(ii)(B), 60.113c(b)(4)(ii)(C),
60.113c(b)(4)(ii)(D), 60.113c(b)(4)(iii)(A),
60.113c(b)(4)(iii)(B),
60.113c(b)(4)(iii)(C),
60.113c(b)(4)(iii)(D)]; and
(B) The date the storage vessel was
emptied or the repairs made and date of
repair.
(6) For each inspection required by
§ 60.113c(b)(7) that finds defects as
listed in § 60.113c(b)(7)(i), report:
(i) Identification of the storage vessel
and date of inspection;
(ii) The reason it did not meet the
specifications of § 60.112c(c) or
§ 60.113c(b)(7);
(iii) A description of each repair
made; and
(iv) Date of repair.
(7) For each landing of an internal
floating roof or an external floating roof
that triggers an alarm required by
§ 60.113c(a)(5) or (b)(8), report:
(i) Identification of the storage vessel;
(ii) Date the roof was landed; and
(iii) Indication of whether the roof
landed because the storage vessel was
being emptied.
(8) After installing a closed vent
system that routes to a control device,
fuel gas system, or process to comply
with § 60.112c, report the following, as
well as the information in paragraphs
(c)(9) or (10) of this section, as
applicable:
(i) Results of annual inspections that
indicate a backpressure regulator valve
is not set correctly or does not fully
close when not in the open position.
Include the date and time of the
inspection, the type of deviation, the
corrective action taken, and the date and
time when the backpressure regulator
valve is set correctly, repaired, or
replaced.
(ii) For each inspection conducted
under § 60.113c(c)(2), identification of
the closed vent system, the date of
inspection, the type of inspection
(Method 21 of appendix A–7 to this part
or visible, audible, and olfactory
methods) and summary result of the
inspection (no leaks detected or leaks
PO 00000
Frm 00040
Fmt 4701
Sfmt 4700
were detected). For each leak detected,
provide an identification of the part of
the closed vent system associated with
the leak, the date of the first attempt at
repair, and the date of successful repair
or anticipated repair if the repair is
delayed.
(iii) The start date and time, duration
in hours, and an estimate of the mass
quantity in pounds of VOL released for
times when flow is detected or
emissions are diverted from the control
device through a bypass line while a
storage vessel affected facility vented to
the closed vent system contains VOL or
is being degassed.
(9) After installing a closed vent
system and control device to comply
with § 60.112c other than a flare or an
enclosed combustion device electing to
comply with § 60.112c(d)(5), report:
(i) For each instance when the CMS
measured 3-hour rolling averages below
the established operating limit:
(A) The date and start time of the
deviation;
(B) The duration of the deviation in
hours;
(C) The lowest 3-hour rolling average
operating parameter reading during the
period of the deviation;
(D) A unique identifier for the CMS;
(E) The make, model number, and
date of last calibration check of the
CMS; and
(F) The cause of the deviation and the
corrective action taken.
(ii) For all instances when the CMS
was inoperative:
(A) The date and start time of the
deviation;
(B) The duration of the deviation in
hours;
(C) A unique identifier for the CMS;
(D) The make, model number, and
date of last calibration check of the
CMS; and
(E) The cause of the deviation and the
corrective action taken.
(10) After installing a closed vent
system and a flare to comply with
§ 60.112c or an enclosed combustion
device electing to comply with
§ 60.112c(d)(5), report:
(i) The date and start and end times
for each of the following instances:
(A) Each 15-minute block during
which there was at least 1 minute when
storage vessel vapors were routed to the
flare and no pilot flame or flare flame
was present.
(B) Each period of 2 consecutive
hours during which visible emissions
exceeded a total of 5 minutes.
Additionally, report the number of
minutes for which visible emissions
were observed during the observation or
an estimate of the cumulative number of
minutes in the 2-hour period for which
E:\FR\FM\15OCR4.SGM
15OCR4
khammond on DSKJM1Z7X2PROD with RULES4
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
emissions were visible based on best
information available to the owner or
operator.
(C) Each 15-minute period for which
the applicable operating limits specified
in 40 CFR 63.670(d) through (f) were not
met. You must identify the specific
operating limit that was not met and
report the value of the net heating value
operating parameter(s) during the
deviation determined following the
methods in 40 CFR 63.670(k) through
(n) as applicable.
(ii) The start date, start time, and
duration in minutes for each period
when storage vessel vapors were routed
to the flare or enclosed combustion
device and the applicable monitoring
was not performed.
(iii) For each instance reported under
paragraphs (c)(10)(i) and (ii) of this
section that involves CMS, report the
following information:
(A) A unique identifier for the CMS;
(B) The make, model number, and
date of last calibration check of the
CMS; and
(C) The cause of the deviation or
downtime and the corrective action
taken.
(11) For pressure relief devices on a
storage vessel or closed vent system
subject to § 60.112c(d)(1)(iii) or
(d)(2)(iii), report each pressure release to
the atmosphere, including pressure
relief device identification name or
number, the start date, start time, and
duration (in minutes) of the pressure
release; and an estimate of the mass
quantity in pounds of VOL released.
(12) For vacuum breaking devices on
a storage vessel subject to § 60.112c(d)
and (d)(1)(iii), report the following
information for each time the vacuum
breaking device failed to close prior to
the storage vessel reaching atmospheric
pressure: identification name or number
of vacuum breaking device; the start
date, start time, and duration (in
minutes) of the pressure release; and an
estimate of the mass quantity in pounds
of VOL released.
(d) Timeframe for semiannual report
submissions. (1) The first semiannual
report will cover the period starting
with the date the source first becomes
an affected facility subject to this
subpart and ending June 30 or December
31, whichever date is earlier. For
example, if the source becomes an
affected facility on April 15, the first
semiannual report would cover the
period from April 15 to June 30. The
first semiannual report must be
submitted on or before the last day of
the month 2 months after the last date
covered by the semiannual report. In
this example, the first semiannual report
would be due August 31.
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
(2) Subsequent semiannual reports
will cover subsequent 6 calendar month
periods (January 1 through June 30 or
July 1 through December 31, as
applicable) with each report due on or
before the last day of the month 2
months after the last date covered by the
semiannual report (August 31 or
February 28 or 29, as applicable).
(3) For each affected facility that is
subject to permitting regulations
pursuant to 40 CFR parts 70 or 71, if the
delegated authority has established
dates for submitting semiannual reports
pursuant to 40 CFR 70.6(a)(3)(iii)(A) or
71.6(a)(3)(iii)(A), you may submit the
first and subsequent semiannual reports
according to the dates the delegated
authority has established instead of the
dates in paragraphs (d)(1) and (2) of this
section.
(e) Reporting requirements for
performance tests. Within 60 days after
the date of completing each
performance test, you must submit the
results following the procedures
specified in paragraph (f) of this section.
Data collected using test methods that
are supported by the U.S.
Environmental Protection Agency (EPA)
Electronic Reporting Tool (ERT) as
listed on the EPA’s ERT website
(https://www.epa.gov/electronicreporting-air-emissions/electronicreporting-tool-ert) at the time of the test
must be submitted in a file format
generated using the EPA’s ERT.
Alternatively, you may submit an
electronic file consistent with the
extensible markup language (XML)
schema listed on the EPA’s ERT
website. Data collected using test
methods that are not supported by the
EPA’s ERT as listed on the EPA’s ERT
website at the time of the test must be
included as an attachment in the ERT or
an alternate electronic file.
(f) Requirements for electronically
submitting reports. If you are required to
submit notifications or reports following
the procedures specified in this
paragraph (f), you must submit
notifications or reports to the EPA via
CEDRI, which can be accessed through
the EPA’s Central Data Exchange (CDX)
(https://cdx.epa.gov/). The EPA will
make all the information submitted
through CEDRI available to the public
without further notice to you. Do not
use CEDRI to submit information you
claim as confidential business
information (CBI). Although we do not
expect persons to assert a claim of CBI,
if you wish to assert a CBI claim for
some of the information in the report,
you must submit a complete file in the
format specified in this subpart,
including information claimed to be
CBI, to the EPA following the
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
83335
procedures in paragraphs (f)(1) and (2)
of this section. Clearly mark the part or
all of the information that you claim to
be CBI. Information not marked as CBI
may be authorized for public release
without prior notice. Information
marked as CBI will not be disclosed
except in accordance with procedures
set forth in 40 CFR part 2. All CBI
claims must be asserted at the time of
submission. Anything submitted using
CEDRI cannot later be claimed CBI.
Furthermore, under CAA section 114(c),
emissions data are not entitled to
confidential treatment, and the EPA is
required to make emissions data
available to the public. Thus, emissions
data will not be protected as CBI and
will be made publicly available. You
must submit the same file submitted to
the CBI office with the CBI omitted to
the EPA via the EPA’s CDX as described
earlier in this paragraph (f).
(1) The preferred method to receive
CBI is for it to be transmitted
electronically using email attachments,
File Transfer Protocol, or other online
file sharing services. Electronic
submissions must be transmitted
directly to the OAQPS CBI Office at the
email address oaqpscbi@epa.gov, and as
described above, should include clear
CBI markings. ERT files should be
flagged to the attention of the
Measurement Policy Group Leader and
all other files should be flagged to the
attention of the NSPS Kc Rule Lead. If
assistance is needed with submitting
large electronic files that exceed the file
size limit for email attachments, and if
you do not have your own file sharing
service, please email oaqpscbi@epa.gov
to request a file transfer link.
(2) If you cannot transmit the file
electronically, you may send CBI
information through the postal service
to the following address: U.S. EPA,
Attn: OAQPS Document Control Officer,
Mail Drop: C404–02, 109 T.W.
Alexander Drive, P.O. Box 12055, RTP,
NC 27711. ERT files should be sent to
the secondary attention of the
Measurement Policy Group Leader and
all other files should be sent to the
secondary attention of the NSPS Kc
Rule Lead. The mailed CBI material
should be double wrapped and clearly
marked. Any CBI markings should not
show through the outer envelope.
(g) Claims of EPA system outage. If
you are required to electronically
submit a report through CEDRI in the
EPA’s CDX, you may assert a claim of
EPA system outage for failure to timely
comply with that reporting requirement.
To assert a claim of EPA system outage,
you must meet the requirements
outlined in paragraphs (g)(1) through (7)
of this section.
E:\FR\FM\15OCR4.SGM
15OCR4
83336
Federal Register / Vol. 89, No. 199 / Tuesday, October 15, 2024 / Rules and Regulations
khammond on DSKJM1Z7X2PROD with RULES4
(1) You must have been or will be
precluded from accessing CEDRI and
submitting a required report within the
time prescribed due to an outage of
either the EPA’s CEDRI or CDX systems.
(2) The outage must have occurred
within the period of time beginning 5
business days prior to the date that the
submission is due.
(3) The outage may be planned or
unplanned.
(4) You must submit notification to
the Administrator in writing as soon as
possible following the date you first
knew, or through due diligence should
have known, that the event may cause
or has caused a delay in reporting.
(5) You must provide to the
Administrator a written description
identifying:
(i) The date(s) and time(s) when CDX
or CEDRI was accessed and the system
was unavailable;
(ii) A rationale for attributing the
delay in reporting beyond the regulatory
deadline to EPA system outage;
(iii) A description of measures taken
or to be taken to minimize the delay in
reporting; and
(iv) The date by which you propose to
report, or if you have already met the
reporting requirement at the time of the
notification, the date you reported.
(6) The decision to accept the claim
of EPA system outage and allow an
extension to the reporting deadline is
solely within the discretion of the
Administrator.
(7) In any circumstance, the report
must be submitted electronically as
VerDate Sep<11>2014
19:04 Oct 11, 2024
Jkt 265001
soon as possible after the outage is
resolved.
(h) Claims of force majeure. If you are
required to electronically submit a
report through CEDRI in the EPA’s CDX,
you may assert a claim of force majeure
for failure to timely comply with that
reporting requirement. To assert a claim
of force majeure, you must meet the
requirements outlined in paragraphs
(h)(1) through (5) of this section.
(1) You may submit a claim if a force
majeure event is about to occur, occurs,
or has occurred or there are lingering
effects from such an event within the
period of time beginning 5 business
days prior to the date the submission is
due. For the purposes of this section, a
force majeure event is defined as an
event that will be or has been caused by
circumstances beyond the control of the
affected facility, its contractors, or any
entity controlled by the affected facility
that prevents you from complying with
the requirement to submit a report
electronically within the time period
prescribed. Examples of such events are
acts of nature (e.g., hurricanes,
earthquakes, or floods), acts of war or
terrorism, or equipment failure or safety
hazard beyond the control of the
affected facility (e.g., large scale power
outage).
(2) You must submit notification to
the Administrator in writing as soon as
possible following the date you first
knew, or through due diligence should
have known, that the event may cause
or has caused a delay in reporting.
(3) You must provide to the
Administrator:
PO 00000
Frm 00042
Fmt 4701
Sfmt 9990
(i) A written description of the force
majeure event;
(ii) A rationale for attributing the
delay in reporting beyond the regulatory
deadline to the force majeure event;
(iii) A description of measures taken
or to be taken to minimize the delay in
reporting; and
(iv) The date by which you propose to
report, or if you have already met the
reporting requirement at the time of the
notification, the date you reported.
(4) The decision to accept the claim
of force majeure and allow an extension
to the reporting deadline is solely
within the discretion of the
Administrator.
(5) In any circumstance, the reporting
must occur as soon as possible after the
force majeure event occurs.
§ 60.117c
Delegation of authority.
(a) In delegating implementation and
enforcement authority of this subpart to
a State, local, or Tribal agency under
section 111(c) of the Act, the authorities
contained in paragraph (b) of this
section shall be retained by the
Administrator of U.S. EPA and cannot
be transferred to the State, local, or
Tribal agency.
(b) Authorities which will not be
delegated to State, local, or Tribal
agencies: §§ 60.113c(d)(1)(iv) and
60.114c and approval of an alternative
to any electronic reporting to the EPA
required by this subpart.
[FR Doc. 2024–22823 Filed 10–11–24; 8:45 am]
BILLING CODE 6560–50–P
E:\FR\FM\15OCR4.SGM
15OCR4
Agencies
[Federal Register Volume 89, Number 199 (Tuesday, October 15, 2024)]
[Rules and Regulations]
[Pages 83296-83336]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2024-22823]
[[Page 83295]]
Vol. 89
Tuesday,
No. 199
October 15, 2024
Part IV
Environmental Protection Agency
-----------------------------------------------------------------------
40 CFR Part 60
New Source Performance Standards Review for Volatile Organic Liquid
Storage Vessels (Including Petroleum Liquid Storage Vessels); Final
Rule
Federal Register / Vol. 89 , No. 199 / Tuesday, October 15, 2024 /
Rules and Regulations
[[Page 83296]]
-----------------------------------------------------------------------
ENVIRONMENTAL PROTECTION AGENCY
40 CFR Part 60
[EPA-HQ-OAR-2023-0358; FRL-10655-02-OAR]
RIN 2060-AV93
New Source Performance Standards Review for Volatile Organic
Liquid Storage Vessels (Including Petroleum Liquid Storage Vessels)
AGENCY: Environmental Protection Agency (EPA).
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The Environmental Protection Agency (EPA) is finalizing
amendments to the new source performance standards (NSPS) for Volatile
Organic Liquid Storage Vessels (Including Petroleum Liquid Storage
Vessels) pursuant to the review required by the Clean Air Act (CAA).
The EPA is finalizing revisions to the NSPS that are applicable to
volatile organic liquid (VOL) storage vessels that commence
construction, reconstruction, or modification after October 4, 2023,
under a new NSPS subpart, as well as amendments to an existing subpart.
In the new NSPS subpart Kc, the EPA is finalizing requirements to
reduce the vapor pressure applicability thresholds and revise the
volatile organic compound (VOC) standards to reflect the best system of
emission reduction (BSER) for affected storage vessels. In addition,
the EPA is finalizing degassing emission controls; clarification of
startup, shutdown, and malfunction (SSM) requirements; additional
monitoring requirements; and other technical improvements
DATES: This final rule is effective on October 15, 2024. The
incorporation by reference of certain publications listed in the rule
is approved by the Director of the Federal Register as of October 15,
2024.
ADDRESSES: The EPA has established a docket for this action under
Docket ID No. EPA-HQ-OAR-2023-0358. All documents in the docket are
listed on the https://www.regulations.gov website. Although listed,
some information is not publicly available, e.g., Confidential Business
Information (CBI) or other information whose disclosure is restricted
by statute. Certain other material, such as copyrighted material, is
not placed on the internet and will be publicly available only as
portable document format (PDF) versions that can only be accessed on
the EPA computers in the docket office reading room. Certain databases
and physical items cannot be downloaded from the docket but may be
requested by contacting the Public Reading Room at (202) 566-1744. The
docket office has up to 10 business days to respond to these requests.
With the exception of such material, publicly available docket
materials are available electronically in Regulations.gov or on the EPA
computers in the Public Reading Room at the EPA Docket Center, WJC West
Building, Room Number 3334, 1301 Constitution Ave. NW, Washington, DC.
The Public Reading Room hours of operation are 8:30 a.m. to 4:30 p.m.
Eastern Standard Time (EST), Monday through Friday. The telephone
number for the Public Reading Room is (202) 566-1744, and the telephone
number for the EPA Docket Center is (202) 566-1742.
FOR FURTHER INFORMATION CONTACT: Mr. Michael Cantoni III, Sector
Policies and Programs Division (E143-01), Office of Air Quality
Planning and Standards, U.S. Environmental Protection Agency, 109 T.W.
Alexander Drive, P.O. Box 12055, Research Triangle Park, North Carolina
27711; telephone number: (919) 541-5593; and email address:
[email protected].
SUPPLEMENTARY INFORMATION:
Preamble acronyms and abbreviations. Throughout this document the
use of ``we,'' ``us,'' or ``our'' is intended to refer to the EPA. We
use multiple acronyms and terms in this preamble. While this list may
not be exhaustive, to ease the reading of this preamble and for
reference purposes, the EPA defines the following terms and acronyms
here:
AMEL alternative means of emissions limitation
API American Petroleum Institute
ASTM American Society for Testing and Materials
AVO audible, visual, and olfactory
BSER best system of emission reduction
CAA Clean Air Act
CBI Confidential Business Information
CDX Central Data Exchange
CEDRI Compliance and Emissions Data Reporting Interface
CFR Code of Federal Regulations
EFR external floating roof
EIA economic impact analysis
EJ environmental justice
EPA Environmental Protection Agency
FR Federal Register
gal gallons
HAP hazardous air pollutant(s)
IBR incorporate by reference
ICR information collection request
IFR internal floating roof
kg/hr kilograms per hour
kPa kilopascals
LEL lower explosive limit
m3 cubic meters
MON Miscellaneous Organic Chemical Manufacturing NESHAP
MTVP maximum true vapor pressure
NAICS North American Industry Classification System
NESHAP national emission standards for hazardous air pollutants
NSPS new source performance standards
NTAA National Tribal Air Association
NTTAA National Technology Transfer and Advancement Act
OMB Office of Management and Budget
PDF portable document format
PRA Paperwork Reduction Act
PRD pressure relief device
ppmv parts per million by volume
psia pounds per square inch absolute
psig pounds per square inch gauge
RFA Regulatory Flexibility Act
RIN Regulatory Information Number
SCAQMD South Coast Air Quality Management District
SSM startup, shutdown, and malfunction
STERPP 2000 U.S. EPA Storage Tank Emission Reduction Partnership
Program
UMRA Unfunded Mandates Reform Act
VCU vapor combustion unit
VOC volatile organic compound(s)
VOL volatile organic liquid
Organization of this document. The information in this preamble is
organized as follows:
I. General Information
A. Does this action apply to me?
B. Where can I get a copy of this document and other related
information?
C. Judicial Review and Administrative Review
II. Background
A. What is the statutory authority for this action?
B. How does the EPA perform the NSPS review?
C. What is the source category regulated in this final action?
D. What outreach and engagement did the EPA conduct?
III. What changes did we propose for the VOL Storage Vessel NSPS?
IV. What actions are we finalizing and what is our rationale for
such decisions?
A. Revised NSPS for VOL Storage Vessels That Commenced
Construction, Reconstruction, or Modification After July 23, 1984,
and on or Before October 4, 2023
B. Revised NSPS for VOL Storage Vessels That Commenced
Construction, Reconstruction, or Modification After October 4, 2023
C. NSPS Subpart Kc Without Startup, Shutdown, and Malfunction
Exemptions
D. Testing, Monitoring, and Inspection Requirements
E. Recordkeeping and Electronic Reporting
F. Other Final Amendments
G. Effective Date and Compliance Dates
V. Summary of Cost, Environmental, and Economic Impacts
A. What are the air quality impacts?
B. What are the cost impacts?
C. What are the economic impacts?
D. What are the benefits?
E. What analysis of environmental justice did we conduct?
VI. Statutory and Executive Order Reviews
A. Executive Order 12866: Regulatory Planning and Review and
Executive
[[Page 83297]]
Order 14094: Modernizing Regulatory Review
B. Paperwork Reduction Act (PRA)
C. Regulatory Flexibility Act (RFA)
D. Unfunded Mandates Reform Act (UMRA)
E. Executive Order 13132: Federalism
F. Executive Order 13175: Consultation and Coordination With
Indian Tribal Governments
G. Executive Order 13045: Protection of Children From
Environmental Health Risks and Safety Risks
H. Executive Order 13211: Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use
I. National Technology Transfer and Advancement Act (NTTAA) and
1 CFR Part 51
J. Executive Order 12898: Federal Actions To Address
Environmental Justice in Minority Populations and Low-Income
Populations and Executive Order 14096: Revitalizing Our Nation's
Commitment to Environmental Justice for All
K. Congressional Review Act (CRA)
I. General Information
A. Does this action apply to me?
The source category that is the subject of this final action is
composed of VOL storage vessels (including petroleum liquid storage
vessels) regulated under CAA section 111, NSPS. The 2022 North American
Industry Classification System (NAICS) codes for the source category
are 325, 324, and 422710. The NAICS codes serve as a guide for readers
outlining the type of entities that this final action is likely to
affect. The NSPS codified in 40 CFR part 60, subpart Kc, are directly
applicable to affected facilities that begin construction,
reconstruction, or modification after October 4, 2023. Final amendments
to 40 CFR part 60, subpart Kb, are applicable to affected facilities
that begin construction, reconstruction, or modification after July 23,
1984, and before October 4, 2023. Federal, State, local, and Tribal
government entities that own and/or operate VOL storage vessels are
affected by this action. If you have any questions regarding the
applicability of this action to a particular entity, you should
carefully examine the applicability criteria found in 40 CFR part 60,
subparts Kb and Kc, and consult the person listed in the FOR FURTHER
INFORMATION CONTACT section of this preamble, your State air pollution
control agency with delegated authority for NSPS, or your EPA Regional
Office.
B. Where can I get a copy of this document and other related
information?
In addition to being available in the docket, an electronic copy of
this final action is available on the internet at https://www.epa.gov/stationary-sources-air-pollution/volatile-organic-liquid-storage-vessels-including-petroleum. Following publication in the Federal
Register, the EPA will post the Federal Register version of the final
rule and key technical documents at this same website.
C. Judicial Review and Administrative Review
Under CAA section 307(b)(1), judicial review of this final action
is available only by filing a petition for review in the United States
Court of Appeals for the District of Columbia Circuit (the court) by
December 16, 2024. Under CAA section 307(b)(2), the requirements
established by this final rule may not be challenged separately in any
civil or criminal proceedings brought by the EPA to enforce the
requirements.
Section 307(d)(7)(B) of the CAA further provides that ``[o]nly an
objection to a rule or procedure which was raised with reasonable
specificity during the period for public comment (including any public
hearing) may be raised during judicial review.'' This section also
provides a mechanism for the EPA to convene a proceeding for
reconsideration, ``[i]f the person raising an objection can demonstrate
to the EPA that it was impracticable to raise such objection within
[the period for public comment] or if the grounds for such objection
arose after the period for public comment (but within the time
specified for judicial review) and if such objection is of central
relevance to the outcome of the rule.'' Any person seeking to make such
a demonstration to us should submit a Petition for Reconsideration to
the Office of the Administrator, U.S. Environmental Protection Agency,
Room 3000, WJC West Building, 1200 Pennsylvania Ave. NW, Washington, DC
20460, with a copy to both the person(s) listed in the preceding FOR
FURTHER INFORMATION CONTACT section and the Associate General Counsel
for the Air and Radiation Law Office, Office of General Counsel (Mail
Code 2344A), U.S. Environmental Protection Agency, 1200 Pennsylvania
Ave. NW, Washington, DC 20460.
II. Background
A. What is the statutory authority for this action?
The EPA's authority for this final rule is CAA section 111, which
governs the establishment of standards of performance for stationary
sources. Section 111(b)(1)(A) of the CAA requires the EPA Administrator
to list categories of stationary sources that in the Administrator's
judgment cause or contribute significantly to air pollution that may
reasonably be anticipated to endanger public health or welfare. The EPA
must then issue performance standards for new (and modified or
reconstructed) sources in each source category pursuant to CAA section
111(b)(1)(B). These standards are referred to as new source performance
standards, or NSPS. The EPA has the authority to define the scope of
the source categories, determine the pollutants for which standards
should be developed, set the emission level of the standards, and
distinguish among classes, types, and sizes within categories in
establishing the standards.
CAA section 111(b)(1)(B) requires the EPA to ``at least every 8
years review and, if appropriate, revise'' new source performance
standards. However, the Administrator need not review any such standard
if the ``Administrator determines that such review is not appropriate
in light of readily available information on the efficacy'' of the
standard. When conducting a review of an existing performance standard,
the EPA has the discretion and authority to add emission limits for
pollutants or emission sources not currently regulated for that source
category.
In setting or revising a performance standard, CAA section
111(a)(1) provides that performance standards are to reflect ``the
degree of emission limitation achievable through the application of the
best system of emission reduction which (taking into account the cost
of achieving such reduction and any nonair quality health and
environmental impact and energy requirements) the Administrator
determines has been adequately demonstrated.'' The term ``standard of
performance'' in CAA section 111(a)(1) makes clear that the EPA is to
determine both the best system of emission reduction for the regulated
sources in the source category and the degree of emission limitation
achievable through application of the BSER. The EPA must then, under
CAA section 111(b)(1)(B), promulgate standards of performance for new
sources that reflect that level of stringency. CAA section 111(b)(5)
generally precludes the EPA from prescribing a particular technological
system that must be used to comply with a standard of performance.
Rather, sources can select any measure or combination of measures that
will achieve the standard. CAA section 111(h)(1) authorizes the
Administrator to promulgate ``a design, equipment, work practice, or
operational standard, or combination thereof'' if in his or her
judgment, ``it is not feasible to prescribe
[[Page 83298]]
or enforce a standard of performance.'' CAA section 111(h)(2) provides
the circumstances under which prescribing or enforcing a standard of
performance is ``not feasible,'' such as when the pollutant cannot be
emitted through a conveyance designed to emit or capture the pollutant
or when there is no practicable measurement methodology for the
particular class of sources.
Pursuant to the definition of new source in CAA section 111(a)(2),
standards of performance apply to facilities that begin construction,
reconstruction, or modification after the date of publication of the
proposed standards in the Federal Register. Under CAA section
111(a)(4), ``modification'' means any physical change in, or change in
the method of operation of, a stationary source that increases the
amount of any air pollutant emitted by such source or which results in
the emission of any air pollutant not previously emitted. Changes to an
existing facility that do not result in an increase in emissions are
not considered modifications. Under the provisions in 40 CFR 60.15,
``reconstruction'' means the replacement of components of an existing
facility such that: (1) the fixed capital cost of the new components
exceeds 50 percent of the fixed capital cost that would be required to
construct a comparable entirely new facility; and (2) it is
technologically and economically feasible to meet the applicable
standards. Pursuant to CAA section 111(b)(1)(B), the standards of
performance or revisions thereof shall become effective upon
promulgation.
B. How does the EPA perform the NSPS review?
As noted in section II.A. of this preamble, CAA section 111
requires the EPA to, at least every 8 years, review and, if
appropriate, revise the standards of performance applicable to new,
modified, and reconstructed sources. If the EPA revises the standards
of performance, the standards must reflect the degree of emission
limitation achievable through the application of the BSER considering
the cost of achieving such reduction and any nonair quality health and
environmental impact and energy requirements. CAA section 111(a)(1).
In reviewing an NSPS to determine whether it is ``appropriate'' to
revise the standards of performance, the EPA evaluates the statutory
factors, which may include consideration of the following information:
Expected growth for the source category, including how
many new facilities, reconstructions, and modifications may trigger
NSPS in the future.
Pollution control measures, including advances in control
technologies, process operations, design or efficiency improvements, or
other systems of emission reduction, that are ``adequately
demonstrated'' in the regulated industry.
Available information from the implementation and
enforcement of current requirements that indicates that emission
limitations and percent reductions beyond those required by the current
standards are achieved in practice.
Costs (including capital and annual costs) associated with
implementation of the available pollution control measures.
The amount of emission reductions achievable through
application of such pollution control measures.
Any non-air quality health and environmental impact and
energy requirements associated with those control measures.
In evaluating whether the cost of a particular system of emission
reduction is reasonable, the EPA considers various costs associated
with the particular air pollution control measure or a level of
control, including capital costs and operating costs, and the emission
reductions that the control measure or particular level of control can
achieve. The Agency considers these costs in the context of the
industry's overall capital expenditures and revenues. The Agency also
considers cost effectiveness analysis as a useful metric and as a means
of evaluating whether a given control achieves emission reduction at a
reasonable cost. A cost effectiveness analysis allows comparisons of
relative costs and outcomes (effects) of two or more options. In
general, cost effectiveness is a measure of the outcomes produced by
resources spent. In the context of air pollution control options, cost
effectiveness typically refers to the annualized cost of implementing
an air pollution control option divided by the amount of pollutant
reductions realized annually.
After the EPA evaluates the statutory factors, the EPA compares the
various systems of emission reductions and determines which system is
``best'' and therefore represents the BSER. The EPA then establishes a
standard of performance that reflects the degree of emission limitation
achievable through the implementation of the BSER. In performing this
analysis, the EPA can determine whether subcategorization is
appropriate based on classes, types, and sizes of sources, and may
identify a different BSER and establish different performance standards
for each subcategory. The result of the analysis and the BSER
determination leads to standards of performance that apply to
facilities that begin construction, reconstruction, or modification
after the date of publication of the proposed standards in the Federal
Register. Because the NSPS reflect the BSER under conditions of proper
operation and maintenance, in doing its review, the EPA also evaluates
and determines the proper testing, monitoring, recordkeeping, and
reporting requirements needed to ensure compliance with the emission
standards.
C. What is the source category regulated in this final action?
The EPA first promulgated NSPS for petroleum liquid storage vessels
on March 8, 1974 (39 FR 9317). These standards of performance are
codified in 40 CFR part 60, subpart K, and are applicable to sources
that commence construction, modification, or reconstruction after June
11, 1973, and prior to May 19, 1978. These standards were amended
several times before 1980, when the EPA proposed to establish revised
NSPS for petroleum liquid storage vessels as NSPS subpart Ka (45 FR
23379; April 4, 1980). In 1982, the EPA published a list of priority
sources for which additional NSPS should be established (47 FR 951;
January 8, 1982), and VOL storage vessels at synthetic organic chemical
manufacturers were included in the priority list.
Pursuant to the EPA's authority under CAA section 111, the Agency
proposed (49 FR 29698; July 23, 1984) and promulgated (52 FR 11420;
April 8, 1987) NSPS for VOL storage vessels (including petroleum liquid
storage vessels) for which construction, reconstruction, or
modification commenced after July 23, 1984, as NSPS subpart Kb.\1\ NSPS
subpart Kb regulates storage vessels with a capacity of 75 cubic meters
(m\3\) (~20,000 gallons) or more that store VOLs with a maximum true
vapor pressure (MTVP) greater than or equal to 15.0 kilopascals (kPa)
(~2.18 pounds per square inch absolute (psia)) and from storage vessels
with a capacity of 151 m\3\ (~40,000 gallons) or more that store
organic liquids with an MTVP
[[Page 83299]]
greater than or equal to 3.5 kPa (~0.51 psia). VOC emissions controls
are required on storage vessels with a capacity of 75 m\3\ (~20,000
gallons) or more that store VOLs with an MTVP greater than or equal to
27.6 kPa (~4.0 psia) and from storage vessels with a capacity of 151
m\3\ (~40,000 gallons) or more that store organic liquids with an MTVP
greater than or equal to 5.2 kPa (~0.75 psia). NSPS subpart Kb emission
controls include the use of an external floating roof (EFR), an
internal floating roof (IFR), or a closed vent system and a control
device (see 40 CFR 60.110b(a) and 40 CFR 60.112b(a) and
(b)).2 3 NSPS subpart Kb also specifies testing, monitoring,
recordkeeping, reporting, and other requirements in 40 CFR 60.113b
through 40 CFR 60.116b to ensure compliance with the standards. Storage
vessels with an EFR consist of an open-top cylindrical steel shell
equipped with a deck that floats on the surface (commonly referred to
as a floating ``roof'') of the stored liquid. Storage vessels with an
IFR are fixed roof vessels \4\ that also have a deck internal to the
vessel that floats on the liquid surface (commonly referred to as an
internal floating ``roof'') within the fixed roof vessel.
---------------------------------------------------------------------------
\1\ On October 15, 2003 (68 FR 59328), the EPA finalized
amendments to NSPS subpart Kb to exempt certain storage vessels by
capacity and vapor pressure, exempt process tanks, and add a process
tank definition. At the same time, the EPA also amended the rule to
exempt storage vessels that are subject to the National Emission
Standards for Hazardous Air Pollutants (NESHAP) for Solvent
Extraction of Vegetable Oil Production.
\2\ All affected storage vessels storing organic liquids with a
true vapor pressure of 76.6 kPa or more must use a closed vent
system and a control device. See 40 CFR 60.112b(b).
\3\ As part of NSPS subpart Kb, the EPA proposed (49 FR 29703;
July 23, 1984) and finalized (52 FR 11421; April 8, 1987) that the
best demonstrated technology for vessels storing VOL liquids with
vapor pressures less than 76.6 kPa ([cong]11.1 psia) consists of an
IFR with a liquid-mounted or mechanical shoe primary seal and
controlled fittings or an EFR with a liquid-mounted or mechanical
shoe primary seal and gasketed fittings. For vessels with greater
vapor pressures, the EPA determined the best demonstrated technology
to be a closed vent system and control device.
\4\ A fixed roof storage vessel consists of a cylindrical steel
shell with a permanently affixed roof, which may vary in design from
cone or dome-shaped to flat.
---------------------------------------------------------------------------
The standards set in NSPS subpart Kb for storage vessels with an
EFR or IFR are a combination of design, equipment, work practice, and
operational standards set pursuant to CAA section 111(h). These
standards require, among other things, that a rim seal be installed
continuously around the circumference of the vessel (between the inner
wall of the vessel and the floating roof) to prevent VOC emissions from
escaping to the atmosphere through gaps between the floating roof and
the inner wall of the storage vessel. For IFRs, NSPS subpart Kb allows
a single liquid-mounted or mechanical shoe primary seal (to be used
with or without a secondary seal), or a vapor-mounted primary seal in
combination with a secondary seal. For EFRs, NSPS subpart Kb allows
either a liquid-mounted or mechanical shoe primary seal, both of which
must be used with a secondary seal; vapor-mounted primary seals are not
allowed for EFRs. NSPS subpart Kb also requires numerous deck fittings
\5\ on the floating roof to be equipped with a gasketed cover or lid
that is kept in the closed position at all times (i.e., no visible
gap), except when the device (deck fitting) is in actual use, to
prevent VOC emissions from escaping through the deck fittings. In
addition, NSPS subpart Kb requires owners and operators to conduct
visual inspections to check for defects in the floating roof, rim
seals, and deck fittings (e.g., holes, tears, or other openings in the
rim seal, or covers and lids on deck fittings that no longer close
properly) that could expose the liquid surface to the atmosphere and
potentially result in VOC emission losses through rim seals and deck
fittings.\6\
---------------------------------------------------------------------------
\5\ Numerous fittings pass through or are attached to floating
decks to accommodate structure support components or to allow for
operational functions. Typical deck fittings include, but are not
limited to access hatches, gauge floats, gauge hatch/sample wells,
rim vents, deck drains, deck legs, vacuum breakers, pontoon covers
and guidepoles. IFR storage vessels may also have deck seams, fixed
roof support columns, ladders, and/or stub drains.
\6\ For details about storage vessel emissions, refer to the
Compilation of Air Pollutant Emission Factors, Volume 1: Stationary
Point and Area Sources, AP-42, Fifth Edition, Chapter 7: Liquid
Storage Tanks, dated June 2020 which is available at: https://www.epa.gov/air-emissions-factors-andquantification/ap-42-compilation-air-emissions-factors.
---------------------------------------------------------------------------
NSPS subpart Kb includes two primary alternative means of
compliance. Owners or operators may either comply with the consolidated
air rule provisions for storage vessels in 40 CFR part 65, subpart C,
or comply with the national emission standards for hazardous air
pollutants (NESHAP) for storage vessels in 40 CFR part 63, subpart WW
(NESHAP subpart WW). The substantive control requirements in these
rules are the same as in NSPS subpart Kb although they may have slight
differences in the details of the fitting and inspection requirements.
The EPA proposed the current review of the VOL storage vessels
(including petroleum liquid storage vessels) NSPS subpart Kb on October
4, 2023. We received 29 comments from industry, environmental groups,
State environmental agencies, and others during the comment period.
After the conclusion of the comment period, we received one additional
comment in February 2024. A summary of the more significant comments we
received regarding the proposed rule and our responses are provided in
this preamble. A summary of all other public comments on the proposal
and the EPA's responses to those comments is available in New Source
Performance Standards for Volatile Organic Liquid Storage Vessels,
Background Information for Final Amendments, Summary of Public Comments
and Responses, Docket ID No. EPA-HQ-OAR-2023-0358. In this action, the
EPA is finalizing decisions and revisions pursuant to CAA section
111(b)(1)(B) review for VOL storage vessels after our considerations of
all the comments received.
D. What outreach and engagement did the EPA conduct?
As part of this rulemaking, the EPA engaged and consulted with the
public, including communities with environmental justice (EJ) concerns,
through interactions such as providing a webinar, offering information
on the website for this rule, and informing the public of the proposed
action by sending notifications with summaries of the action and
information on how to comment. These opportunities allowed the EPA to
hear directly from the public, especially communities potentially
impacted by this final action. The webinar slides can be found in the
docket for this rule (Docket ID No. EPA-HQ-OAR-2023-0358).
Prior to proposal publication, the EPA conducted outreach by
providing background on the source category and the existing
requirements of NSPS subpart Kb on the September 19, 2023, EJ National
Community Engagement call and on the August 31, 2023, National Tribal
Air Association (NTAA) call. After publication, the EPA conducted a
community outreach webinar on October 24, 2023, which was focused on
discussing the details of the proposed rulemaking and how to provide
comment on the proposed rule. Additionally, the EPA discussed the
contents of the proposed rule on an October 26, 2023, NTAA call and
encouraged interested parties to submit comments. The EPA received a
request from one Tribe for consultation. On November 8, 2023, the EPA
met with that Tribe for the purposes of discussing NSPS subpart Kc and
other issues but was unable to conduct consultation on this specific
rulemaking.
III. What changes did we propose for the VOL Storage Vessel NSPS?
On October 4, 2023, the EPA proposed the current review of the VOL
Storage Vessel NSPS. In that action, we proposed the following actions
under NSPS subpart Kc:
[[Page 83300]]
General applicability thresholds that include VOL storage
vessels greater than or equal to 20,000 gallons (gal).
Vapor pressure thresholds for controlled VOL storage
vessels greater than or equal to 40,000 gal (151 m\3\) with MTVPs
greater than or equal to 0.5 psia (3.4 kPa).
Vapor pressure thresholds for controlled VOL storage
vessels greater than or equal to 20,000 gal (75.7 m\3\) and less than
40,000 gal (151 m\3\) with MTVPs greater than or equal to 1.5 psia
(10.3 kPa).
Improved standards of performance for vessels that have
IFRs, EFRs, and closed vent systems routed to a control device, fuel
gas system, or process designed to achieve an average 98 percent
control efficiency.
Updated standards of performance for IFR storage vessels
that include improved seal system requirements, guidepole
configurations reflective of the 2000 U.S. EPA Storage Tank Emission
Reduction Partnership Program (STERPP), and annual lower explosive
limit (LEL) monitoring.
Updated standards of performance for EFR storage vessels
that include requirements for welded deck seams, and improved guidepole
requirements.
Updated standards for closed vent systems that are routed
to a control device, fuel gas system, or process and include
requirements for preventing emissions venting to atmosphere, annual EPA
Method 21 monitoring, and quarterly audible, visual, and olfactory
(AVO) inspections.
Degassing standards of performance for VOL storage vessels
greater than or equal to 1 million gal (3,790 m\3\) with MTVPs greater
than or equal to 1.5 psia (10.3 kPa).
Modification provisions dependent upon an increase of the
MTVP from the VOLs previously stored.
Improved testing, monitoring, and inspection requirements.
Provisions establishing that emission limitations apply at
all times, including during periods of SSM.
Improved recordkeeping and reporting requirements, which
include the implementation of electronic reporting.
Additionally, we proposed to add electronic reporting requirements
to the existing subpart, NSPS subpart Kb.
IV. What actions are we finalizing and what is our rationale for such
decisions?
The EPA is finalizing revisions to the NSPS for VOL storage vessels
pursuant to CAA section 111(b)(1)(B) review. The EPA is promulgating
the NSPS revisions in a new subpart, 40 CFR part 60, subpart Kc. The
new NSPS subpart is applicable to affected sources constructed,
modified, or reconstructed after October 4, 2023.
Under NSPS subpart Kc, we are finalizing standards that reflect the
BSER for affected storage vessels. The rulemaking proposal included
different criteria thresholds for general applicability versus for
storage vessel control. Under the finalized general applicability
provisions, the EPA has included a new exemption for storage vessels
that only store VOL with an MTVP less than 0.25 psia (1.7 kPa) in
response to comments we received asking to eliminate recordkeeping
requirements for storage vessels with vapor pressures well below the
thresholds for which controls are required. We are finalizing the
capacity and vapor pressure thresholds for which controls are required
as proposed. Specifically, we are finalizing control requirements for:
(1) VOL storage vessels greater than or equal to 40,000 gal (151 m\3\)
with MTVPs greater than or equal to 0.5 psia (3.4 kPa); and (2) VOL
storage vessels greater than or equal to 20,000 gal (75.7 m\3\) and
less than 40,000 gal (151 m\3\) with MTVPs greater than or equal to 1.5
psia (10.3 kPa). We are also finalizing modification provisions similar
to those proposed, but we are clarifying that a modification occurs
when a ``. . . storage vessel is used to store VOL that has a greater
maximum true vapor pressure than all VOL historically stored or
permitted.''
In addition to updates involving applicability and modification, we
are finalizing the proposed standards for storage vessels with IFRs,
EFRs, and closed vent systems routed to a control device, fuel gas
system, or process, with minor adjustments based on feedback. Regarding
degassing controls, we are finalizing the provisions with minor
revisions to require controls on nonflammable liquid degassing until
reaching 5,000 parts per million by volume (ppmv) as methane vapor
space concentration rather than the 10 percent LEL.
We are finalizing testing, monitoring, and inspection requirements
as proposed, with some minor revisions that involve matters such as the
timelines and frequency for completing inspections, LEL monitoring
calibration procedures, inspection requirements, and the MTVP
determinations. Similarly, we are finalizing the recordkeeping and
reporting requirements with minor revisions from the proposal involving
matters such as pressure releases, closed vent system monitoring, and
reporting deadlines.
This action also finalizes standards of performance in NSPS subpart
Kc that apply at all times including during periods of SSM and other
changes such as electronic reporting, as proposed. This action also
finalizes revisions in NSPS subpart Kb to require electronic reporting
as proposed.
A. Revised NSPS for VOL Storage Vessels That Commenced Construction,
Reconstruction, or Modification After July 23, 1984, and on or Before
October 4, 2023
We proposed revisions to NSPS subpart Kb to add electronic
reporting requirements. We are finalizing those revisions as proposed.
Our response to major comments received on the proposed NSPS subpart Kb
revisions are provided in this section. Additional public comments
received and our responses to those comments are include in the Summary
of Public Comments and Responses document included in Docket ID No.
EPA-HQ-OAR-2023-0358.
Comment: One commenter stated that the EPA has no lawful or
rational basis for not reviewing the flare standards from existing NSPS
subpart Kb to consider whether to revise NSPS subpart Kb itself. The
commenter stated that since the EPA has declined to revise the general
provisions to include specific monitoring requirements to ensure
compliance, the EPA must revise the NSPS subpart Kb provisions to do
so, as expressly required by 40 CFR 60.18(d). The commenter stated that
the EPA's failure to consider whether to revise the NSPS subpart Kb
standards also violates a consent decree that the EPA entered into to
resolve environmental groups' lawsuit regarding the EPA's failure to
comply with its 8-year review obligations under CAA section
111(b)(1)(B) for the flare provisions from NSPS subpart Kb and other
NSPS subparts, as well as its 8-year review obligations for certain
NESHAP subparts.
Response: The EPA disagrees with this comment. We reviewed NSPS
subpart Kb and proposed new standards of performance, including new
design, operating, and monitoring requirements for flares, in the new
NSPS subpart Kc under CAA section 111(b)(1)(B), which requires that the
EPA ``. . . review and, if appropriate, revise such standards following
the same procedures required by this subsection for promulgating such
standards.''
CAA section 111(b)(1)(B) does not require retroactive revisions to
the existing NSPS subpart (i.e., NSPS subpart Kb). Rather, any revision
to an NSPS must follow the same procedures
[[Page 83301]]
for promulgating such standards under CAA section 111(b)(1)(B). CAA
section 111 establishes a bifurcated approach to regulating sources.
Under CAA section 111(b)(1)(B), the EPA is required to promulgate
standards of performance for new sources, which CAA section 111(a)(2)
defines as ``any stationary source, the construction or modification of
which is commenced after the publication of regulations (or, if
earlier, proposed regulations) prescribing a standard of performance
under this section which will be applicable to such source.'' Existing
sources are defined at CAA section 111(a)(6) to mean ``any stationary
source other than a new source'' and are regulated via a State planning
process pursuant to CAA section 111(d). Accordingly, the revisions,
which are being finalized in a new NSPS subpart Kc, apply to sources
that have commenced construction, reconstruction, or modification after
October 4, 2023, the proposal date for this action. Sources presently
subject to NSPS subpart Kb are not, by definition under this statutory
provision, new sources that could be subjected to the revised standards
finalized in NSPS subpart Kc. Rather, they are treated as existing
sources relative to the revised standards finalized in NSPS subpart Kc.
Revision of the flare provisions in NSPS subpart Kb consistent with the
changes being finalized with respect to NSPS subpart Kc would be akin
to directly applying a new standard of performance to existing sources,
which would be inconsistent with the statutory structure that subjects
regulation of new and existing sources to separate processes. Further,
NSPS subpart Kc includes standards prescribed in accordance with CAA
section 111(h)(1), for flares and other closed vent systems routed to a
control device designed to achieve a 98 percent reduction in VOC
emissions. Because CAA section 111(b)(1)(B) does not require revisions
to the existing NSPS subpart (i.e., NSPS subpart Kb), which continues
to require 95 percent reduction in VOC emissions when using a flare,
the EPA did not propose in this rulemaking to reopen NSPS subpart Kb to
include the new operating and monitoring requirements for flares that
are needed to assure 98 percent VOC reduction when using a flare.
Moreover, because regulated sources subject to NSPS subpart Kb were
not given notice of any such potential change, altering the flare
requirements in NSPS subpart Kb in the final rule would unfairly put
sources that have been using flares to comply with NSPS subpart Kb in
violation of such requirements upon the effective date of this final
rule. Thus, the EPA is not amending NSPS subpart Kb to reflect the new
operating and monitoring flare requirements that are included in the
new NSPS subpart Kc. The EPA notes, however, that as existing sources
trigger modification, they will become subject to NSPS subpart Kc and
the new flare requirements in the rule.
We disagree with the commenter's assertion that our review findings
violate the consent decree. In that consent decree, the EPA agreed to
review and, if necessary, revise NSPS subpart Kb. In this case, the EPA
proposed these revisions as a new subpart to prevent application of
``new source'' standards to sources that are ``existing'' at the time
of proposal. Thus, our proposal of NSPS subpart Kc reflects our review
of NSPS subpart Kb and the revisions to that standard appropriate for
new sources.
Comment: One commenter stated that the EPA unlawfully and
arbitrarily failed to revise existing NSPS subpart Kb to specify that
the SSM exemptions from the [40 CFR part 60] general provisions do not
apply. The commenter stated that the EPA has acted outside its
statutory authority in promulgating the unlawful SSM exemptions from
the general provisions, and therefore the Agency must revise NSPS
subpart Kb to make clear that the general provisions' exemptions do not
apply. The commenter noted that although CAA section 111(b)(1)(B)
allows the EPA to avoid revising standards when ``review is not
appropriate in light of readily available information on the efficacy
of such standard,'' the EPA could not lawfully or rationally invoke
that exception, since the application of the general provisions'
exemptions to NSPS subpart Kb is plainly unlawful.
Response: As noted in the previous comment response, we reviewed
the current subpart Kb standards, determined a series of appropriate
revisions, and concluded that these revisions should be completed as a
separate subpart. We disagree with the commenter that additional
revision to NSPS subpart Kb is necessary to remove SSM exemptions in
the 40 CFR part 60 general provisions. First, we note that the
performance testing requirements in 40 CFR 60.113b(c) clearly indicate
that the provisions in 40 CFR 60.8 do not apply. As such, objectionable
language regarding performance test results obtained during SSM events
is not applicable under NSPS subpart Kb. Second, the SSM exemption in
40 CFR 60.11(c) is also not applicable to NSPS subpart Kb because NSPS
subpart Kb does not contain opacity limits. Because the sections in the
40 CFR part 60 general provisions that contain potentially unlawful SSM
exemptions are not applicable under NSPS subpart Kb, we found no need
to further revise NSPS subpart Kb at this time.
B. Revised NSPS for VOL Storage Vessels That Commenced Construction,
Reconstruction, or Modification After October 4, 2023
This section describes the key technical standards that were
proposed, the major comments received on the proposed requirements, our
responses to those comments, and our rationale for the final
requirements. Additional public comments received on the technical
standards and our responses to those comments are included in the
Summary of Public Comments and Responses document included in Docket ID
No. EPA-HQ-OAR-2023-0358.
The EPA is finalizing standards of performance that reflect the
BSER as well as alternative compliance standards for controlled storage
vessels. The final standards are consistent with the determinations
explained in the rulemaking proposal (88 FR 68540-47; October 4, 2023)
and the analysis detailed in the memorandum Control Options for Storage
Vessels in Docket ID No. EPA-HQ-OAR-2023-0358. While the EPA has made
minor adjustments to these standards based on public comment, the BSER
determination remains unchanged. The adjustments incorporated based on
public comment are detailed in sections IV.B.4. and 5. of this
document.
In summary, the finalized BSER analyses for NSPS subpart Kc are
dependent on the MTVP of a stored VOL and follow the precedent
established in NSPS subparts Kb, Ka, and K. In the NSPS subpart K
proposal, the EPA detailed its justification for the use of equipment
specification (or work practice) standards. As part of the original
rulemaking proposal, the EPA explained that equipment specifications
are the most practical method of regulating storage vessel emissions.
Direct emission measurements for storage vessels are often impractical,
and storage vessel emissions are often modeled and dependent on many
distinguishing factors and variables. The EPA believes that equipment
specification standards are less burdensome for the storage vessel
operation and enforcement (38 FR 15406; May 4, 1973). For VOL storage
vessels with an MTVP less than 11.1 psia, the EPA is finalizing the
following BSER as proposed (88 FR 68542;
[[Page 83302]]
October 4, 2023): a fixed roof in conjunction with an internal floating
roof equipped with a liquid-mounted or mechanical shoe primary seal and
a continuous rim mounted secondary seal, either a flexible fabric
sleeve or gasketed sliding cover on pipe columns (if any), specific
STERPP compliant guidepole configurations, and gasketed covers.
The EPA is also finalizing two alternative compliance options for
VOL storage vessels with MTVPs less than 11.1 psia as proposed:
(1) An external floating roof equipped with a liquid-mounted or
mechanical shoe primary seal and a continuous rim-mounted secondary
seal, with welded deck seams and both seals meeting certain gap
requirements, specific guidepole configurations, and gasketed covers;
or
(2) A closed vent system routed to a 98 percent effective control
device, fuel gas system, or process.
For VOL storage vessels with MTVPs greater than or equal to 11.1
psia, the EPA is finalizing, as proposed, the BSER as a closed vent
system routed to a 98 percent effective control device, fuel gas
system, or process.
1. Vapor Pressure Applicability Thresholds
NSPS subpart Kb established control requirements, at 40 CFR
60.112b(a), for storage vessels based on vessel capacity and VOL vapor
pressures. In our review of NSPS subpart Kb, we assessed the vapor
applicability thresholds for affected facilities and for controls on
affected storage vessels to determine whether these thresholds needed
to be revised for purposes of NSPS subpart Kc. In NSPS subpart Kb there
are two different sets of vapor pressure applicability thresholds: one
for determining affected facilities and one for determining controls.
We proposed to not include specific vapor pressure applicability
thresholds in defining an affected facility under NSPS subpart Kc. As
such, the proposed affected facility under NSPS subpart Kc is any
storage vessel with a capacity of 20,000 gallons or more used to store
a VOL without exclusion for storage vessels under a set vapor pressure.
Based on comments received, we are adding an exemption at 40 CFR
60.110c(b)(8) for storage vessels that only store VOL with an MTVP of
less than 0.25 psia. This revision from proposal helps to limit burden
for storage vessels that only store VOL with very low vapor pressures,
but it does not otherwise impact the control standards proposed for
NSPS subpart Kc.
Based on the BSER analysis, we proposed to revise the vapor
applicability thresholds that require emission controls under NSPS
subpart Kc. Specifically, we proposed to revise the MTVP threshold for
smaller storage vessels (those with capacity of at least 20,000 gallons
but less than 40,000 gallons) to 1.5 psia and for larger storage
vessels (those with capacity of 40,000 gallons or more) to 0.5 psia. We
determined that applying controls for VOL at or above these thresholds
yielded cost-effective emission reductions. We are finalizing these
thresholds as proposed.
2. Other Applicability Provisions
NSPS subpart Kb includes several provisions that exempt specific
groups of VOL storage vessels from applicability under the standard. We
proposed to carry over several of these exemptions, such as exemptions
for: storage vessels that operate at coke oven by-product plants; bulk
gasoline plants; gasoline service stations; pressure vessels; vessels
attached to mobile vehicles; certain vessels at oil and gas production
sites prior to custody transfer; and vessels that store beverage
alcohol. We proposed to remove exemptions under NSPS subpart Kc for
vessels subject to the NESHAP for solvent extraction for vegetable oil
production outlined in 40 CFR part 63, subpart GGGG, because the
standards proposed in NSPS subpart Kc are more stringent than the
existing NESHAP subpart GGGG standards. We are finalizing these
applicability provisions as proposed.
We are adding overlap provisions, based on comments received, to
allow storage vessels subject to NSPS subparts K, Ka, or Kb, or NESHAP
subpart WW to comply with the provisions in NSPS subpart Kc because the
final provisions in NSPS subpart Kc are at least as stringent as those
in NSPS subparts Kb, Ka, and K, and NESHAP subpart WW. These overlap
provisions, which were not proposed, allow facilities the operational
flexibility of simply complying with NSPS subpart Kc if they operate
storage vessels covered under the specified existing storage vessel
rules.
Comment: One commenter stated that the EPA should add an
alternative compliance option that complying with NSPS subpart Kc
demonstrates compliance with the floating roof requirements in NESHAP
subpart WW. Another commenter suggested that the EPA should address
overlaps between NSPS subpart Kc and other rules consistent with the
overlap provisions in NSPS subpart Kb.
Response: There are not overlap provisions in NSPS subpart Kb
beyond the alternative means of compliance in 40 CFR 60.110b(e). The
requirements in the rules listed in 40 CFR 60.110b(e) are not
equivalent to the requirements in NSPS subpart Kc, so we removed these
alternative means of compliance from NSPS subpart Kc. We agree with
commenters that including provisions in NSPS subpart Kc to allow
compliance with the provision in NSPS subpart Kc to be considered
compliance with the provisions in NSPS subpart Kb or NESHAP subpart WW
is appropriate because the final requirements in NSPS subpart Kc are at
least as stringent as those in NSPS subpart Kb and NESHAP subpart WW.
As such, we have added provisions under 40 CFR 60.110c(h) and 40 CFR
60.110c(i) that allow owners and operators with storage vessels subject
to the standards of NSPS subparts K, Ka, and Kb, and NESHAP subpart WW
to choose to comply with the provisions of NSPS subpart Kc to
demonstrate compliance. This will allow facilities that may be subject
to a NESHAP that references NSPS subpart Kb or NESHAP subpart WW but
also subject to NSPS subpart Kc to consolidate their recordkeeping and
reporting requirements and comply only with NSPS subpart Kc.
3. Modification Provisions
For purposes of CAA section 111, modifications are defined as ``. .
. any physical change in, or change in the method of operation of,'' an
existing facility which increases the amount of any air pollutant (to
which a standard applies) emitted into the atmosphere by that facility
or which results in the emission of any air pollutant (to which a
standard applies) into the atmosphere not previously emitted. NSPS
subpart A further provides provisions explaining how a modification is
identified, as well as defining certain exemptions to those general
rules. In particular, 40 CFR 60.14(e)(4) states that the ``[u]se of an
alternative fuel or raw material'' is not considered a modification if
the existing facility was designed to accommodate that alternative use.
The EPA proposed, for purposes of NSPS subpart Kc, that a change in the
liquid stored in the storage vessel to a VOL with a higher MTVP does
not constitute a ``use of an alternative fuel or raw material'' and
would be considered a modification under NSPS subpart Kc. Specifically,
the EPA proposed that a modification occurs when a ``storage vessel is
used to store VOL that has a greater maximum true vapor pressure than
the VOL previously stored.''
[[Page 83303]]
We are finalizing modification provisions similar to those
proposed, but we are clarifying that a modification occurs when a ``. .
. storage vessel is used to store VOL that has a greater maximum true
vapor pressure than all VOL historically stored or permitted.''
Commenters were concerned that our proposed language, which referred to
VOL ``previously stored,'' was ambiguous and potentially limited the
modification assessment to the most recently stored VOL. We revised the
text to ``. . . historically stored or permitted . . . ,'' in order to
clarify our intent that a modification occurs when a new VOL is stored
that has a higher MTVP than any of the previously stored or permitted
VOL (and not just the most recently stored VOL). Finally, we are also
clearly stating, consistent with our discussion in section III.G. of
the proposal preamble, that the alternative fuel or raw material
exemption in 40 CFR 60.14(e)(4) does not apply to storage vessels under
NSPS subpart Kc.
Comment: Several commenters stated that the language ``the VOL
previously stored'' in 40 CFR 60.110c(e) is unclear as to whether any
VOL the storage vessel has previously stored is included, or just the
VOL stored immediately prior to the change. The proposed 40 CFR
60.110c(e) language does not clarify which liquids are different, or
not different, from ``the VOL previously stored.'' Without clarity on
these points, the rule language is subject to a significant range of
interpretations, from any stored organic liquid being the same VOL, to
any de minimis change in liquid properties being a different VOL.
Another commenter stated that the phrase ``the VOL previously stored''
should be removed from 40 CFR 60.110c(e).
Several commenters requested that storing a VOL with a higher MTVP
than the liquid previously stored only be considered a modification if
storing such a liquid would require modification of a facility's
operating permit. One commenter further stated that using a facility's
operating permit to determine modification would place an unreasonable
burden of proof on facility owners or operators. Another commenter
stated that storage vessels are permitted to handle multiple materials,
typically using a worst-case scenario, and changing the liquid stored
in the storage vessel to one above the permitted vapor pressure
threshold would not necessarily increase emissions since emissions are
based on other parameters and conditions, such as changing the hourly
pumping rate, annual throughput, or storage temperature.
Two commenters noted that storage vessels routinely switch between
storing materials with lower and higher vapor pressures at certain
facilities, such as batch chemical plants, refineries, and gasoline
terminals (for example, annual transitions between summer and winter
gasoline). According to the commenters, such routine and other
operational transitions between products do not rise to the level of a
``modification'' triggering performance standards for new sources under
the CAA.
Response: We agree with the commenters that the proposed language
(``the VOL previously stored'') could be misinterpreted to refer only
to the VOL stored immediately prior to the change, and that was not our
intent. For example, if a storage vessel has been used to store both
summer and winter grades of gasoline, we did not intend that the next
switch from summer to winter gasoline would trigger a modification of
the storage vessel. We also agree that owners and operators should not
trigger modification for introducing VOLs that do not exceed the MTVP
of all VOLs that may also exist in a permit. We are clarifying the
regulatory language to match our intent at proposal and reduce burden
by replacing the phrase ``the VOL previously stored'' with the phrase
``all VOL historically stored or permitted.'' In discussions with
industry representatives and the EPA permit specialists, we found that
specific VOLs are not always listed in permits. Therefore, we are not
including revisions suggested by some commenters to limit modification
to only those actions that would require modification of a facility's
operating permit.
We disagree with the commenters who suggested that changing the
volatility of the liquids stored does not increase emissions from the
storage vessel. We note that the emission rate for modification is
expressed in kilograms per hour (kg/hr) and that it is not evaluated on
an annual basis. Even if the facility intends to lower the fill rate to
limit increases in annual emissions, the storage vessel will still have
higher emissions (in kg/hr) during periods when the storage vessel is
not being filled.
Comment: Several commenters disagreed with the EPA's proposal that
a change in the liquid stored in the storage vessel to a VOL with a
higher MTVP does not constitute a ``use of an alternative fuel or raw
material'' and thus would instead be considered a change in the method
of operation of a source. According to the commenters, the stored
materials are fuels or raw materials for some customer or downstream
user, and there is no requirement for a material to be used at the
facility where it is being stored for it to be considered a raw
material or a fuel. According to one commenter, the EPA had determined
that changing a liquid, regardless of volatility, is not an operational
change, and another commenter stated that storage vessel service
changes are the kind of event that the EPA intended to address in 40
CFR 60.14(e)(4). Other commenters recommended that the EPA retain its
long-held interpretation that a change of liquids in an existing VOL
storage vessel does not constitute a ``modification'' triggering
applicability of NSPS subpart Kc. Commenters also noted that the
proposed interpretation would arbitrarily apply NSPS subpart Kc to some
storage vessels, and not to other identical vessels, based on their
historic use rather than their design capabilities.
One commenter stated that changing a liquid in a storage vessel is
not a modification if the material could have been previously
accommodated without a physical change or a capital expenditure. Some
commenters requested that the EPA revise proposed 40 CFR 60.110c(e) to
clearly state that changing the material stored is not a modification
if the storage vessel could accommodate the new material without a
physical change or significant capital expenditure. Commenters
requested that the EPA review historical documents related to NSPS
subpart Kb and reconfirm these long-held policies regarding
modification of storage vessels.
One commenter stated that the EPA's reference to FCC v. Fox
Television Stations, Inc. for the proposition that it need only
articulate a ``good reason'' for its ``change in policy'' is misplaced.
According to the commenter, the EPA is not proposing to amend any of
its existing regulations setting forth its policy for NSPS triggering
``modifications.'' Rather, the proposal reflects a reversal of the
EPA's longstanding interpretation of the CAA and its regulations in 40
CFR 60.2 and 60.14. Unlike a change in policy, the commenter contends,
``an agency's interpretation of a statute or regulation that conflicts
with a prior interpretation is entitled to considerably less deference
than a consistently held agency view.'' Advanced Energy United, Inc. v.
FERC (82 F.4th 1095, 1114 (D.C. Cir. 2023) (quoting Thomas Jefferson
University v. Shalala, 512 U.S. 504 (1994)). Accordingly, it is the
EPA's long-held interpretation of ``modifications''--for nearly 40
years--that is entitled to deference. The commenter asserts that
[[Page 83304]]
this is particularly true where, as here, the EPA has not provided a
justification for the conflicting interpretation or articulated the
scope of changes in volatility of stored liquids that would actually
trigger a ``modification.''
Response: The EPA disagrees with these comments. First, the EPA's
reliance on FCC v. Fox, 556 U.S. 502 (2009), the controlling case on
changes in agency policy, is appropriate here. The quote that
commenters cite above, asserting that an agency's statutory
interpretation which conflicts with a prior interpretation is
``entitled to considerably less deference than a consistently held
view,'' is from Thomas Jefferson University v. Shalala, 512 U.S. 504
(1994), a 1994 Supreme Court case whose precedent on changes in agency
policy was displaced by FCC v. Fox, in 2009, 556 U.S. 502. Under FCC v.
Fox, ``it suffices that the new policy is permissible under the
statute, that there are good reasons for it, and that the agency
believes it to be better, which the conscious change of course
adequately indicates.'' Id. at 515.
According to the commenters, anything stored in a storage vessel
should be considered an alternative fuel or raw material and therefore
any change in the liquid stored should be exempt from being considered
a modification. We find in this final rule that this interpretation of
the alternative fuel or raw material exemption as applied to storage
vessels is inappropriate and often excludes changes in the stored VOL
that increase emissions and that therefore should trigger additional
control requirements. The EPA explained its rationale for including
additional modification provisions in section III.G. of the proposal
preamble (88 FR 68543; October 4, 2023). The EPA explained that for
purposes of NSPS subpart Kc, a change in the liquid stored in the
storage vessel to an organic liquid with a greater MTVP does not
constitute a ``use of an alternative fuel or raw material'' and would
be considered a change in the method of operation of the storage
vessel. The primary function of this affected facility is the storage
of materials. The VOLs stored in the storage vessel are neither raw
material nor fuel inputs to a process at the affected facility itself.
Furthermore, even had the EPA not revisited its interpretation
regarding the application of 40 CFR 60.14(e)(4), we maintain that
changing the VOL stored to one with a higher MTVP is a modification (a
change in the method of operation that results in an increase in the
emissions rate). The NSPS subpart Kc modification provisions result in
meaningful emission reductions. For these reasons, the final rulemaking
appropriately supersedes the general provisions. As such, the EPA is
finalizing modification provisions such that a change in the liquid
stored, which results in increased VOC emissions, would be a
modification under NSPS subpart Kc and is clarifying in 40 CFR
60.110c(e) that, for the purposes of this source category, the
exemption at 40 CFR 60.14(e)(4) does not apply.
The precedent of MTVP dependent standards of performance for VOL
storage vessels was established as part of NSPS subpart K and has
informed the establishment of standards for subsequent rulemakings
under NSPS subparts Ka and Kb. Under these standards, a VOL's MTVP
(along with a vessel's capacity) has served as a primary mechanism for
determining suitable standards for control. The amended modification
provisions will provide meaningful emission reductions from storage
vessels that would otherwise go unregulated despite satisfying the
statutory criteria for a modification under CAA section 111(a)(4), as
explained in this section and at III.G. of the proposal preamble (88 FR
68543; October 4, 2023). The modification provision, as amended,
effectively curtails a previously existing loophole which had allowed
owners and operators to circumvent the standards in NSPS subpart Kb.
For example, prior to this rulemaking, an uncontrolled fixed roof
vessel could be constructed and be exempt from NSPS subpart Kb
standards because it was storing a low vapor pressure VOL. The vessel
could then change operation to introduce a new material with a higher
vapor pressure that would otherwise be subject to the NSPS had it been
stored in the tank at the time of construction, but the owner or
operator could continue to operate without meeting the floating roof or
closed vent system and control device standards even if the vessel was
constructed after the Kb applicability date. Similarly, if an owner or
operator built floating roof tanks for VOLs with less than 11.1 psia
and later replaced the liquid stored with a liquid with a vapor
pressure greater than 11.1 psia, they could thereby circumvent the
closed vent system and control device requirements under 40 CFR 60.112b
which are directly dependent on the MTVP of the stored VOL and which
would otherwise apply. As such, the prior NSPS provided significant
leeway for owners and operators to circumvent the regulations intended
to control storage vessel emissions. To address this concern, the EPA
is finalizing modification provisions such that the MTVP can be used as
an indicator to determine that a change in the liquid stored, which
results in increased VOC emissions, would be a modification under NSPS
subpart Kc.
The EPA's decision to consider a change in the liquid historically
stored or permitted to one with a higher vapor pressure to be a
modification is consistent with both the statutory and regulatory
definitions of those terms. CAA section 111(a) defines modification to
mean, ``any physical change in, or change in the method of operation
of, a stationary source which increases the amount of any air pollutant
emitted by such source or which results in the emission of any air
pollutant not previously emitted.'' Similarly, the General Provisions
to 40 CFR part 60 define modification at 40 CFR 60.2 to mean, ``any
physical change in, or change in the method of operation of, an
existing facility which increases the amount of any air pollutant (to
which a standard applies) emitted into the atmosphere by that facility
or which results in the emission of any air pollutant (to which a
standard applies) into the atmosphere not previously emitted.'' And 40
CFR 60.14 provides a more detailed framework for evaluating
modifications, which similarly states at paragraph (a) that: ``Except
as provided under paragraphs (e) and (f) of this section, any physical
or operational change to an existing facility which results in an
increase in the emission rate to the atmosphere of any pollutant to
which a standard applies shall be considered a modification within the
meaning of section 111 of the Act.'' Thus, the CAA and general
provisions for 40 CFR part 60 all rely on the same basic two-step
process: (1) a physical change in, or change in the method of operation
of, a stationary source; and (2) a resulting increase in emissions.
Notably, it is not necessary for there to be a physical change at the
source in the first step if there is a change in the method of
operation. One or the other will suffice. We address each of these
criteria in turn.
First, as proposed, the EPA has determined that a change in the
liquid stored in a storage vessel constitutes a change in the method of
operation of a storage vessel. The primary function of this affected
facility is the storage of materials, and so the only logical ``change
in the method of operation'' that a storage vessel would undergo is a
change in the material stored. In other words, whenever a storage
vessel changes the VOL that is stored, that is a change in that
facility's method of operation. The EPA's interpretation
[[Page 83305]]
regarding what constitutes a change in the ``method of operation'' for
storage vessels has not changed with this rulemaking. In explaining the
applicability of modification under the CAA, in the NSPS subpart Kb
preamble, the EPA affirmed, ``Few, if any, changes in the physical
configuration of the storage vessels that would increase emissions are
anticipated. An operational change that would increase emissions is a
changing of the stored liquid from a VOC non-emitting liquid to a VOC
emitting liquid'' (49 FR 29707; July 23, 1984). Thus, the EPA has long
considered the changing of the stored liquid to meet the statutory
requirements for an operational change. Second, the changing of the
stored liquid can lead to an increase of emissions whenever the MTVP of
the new liquid is greater than the previously stored liquid. Thus, both
statutory criteria for identifying a modification are met.
The EPA agrees that we have historically applied the regulatory
exemption under 60.14(e) for ``use of an alternative fuel or raw
material'' to storage vessels. In making our decision regarding
modifications, we reviewed several documents \7\ and questioned both
industry and enforcement personnel to better understand what changes
are currently considered modifications. In the NSPS subpart Kb
preamble, the EPA explained, ``Section 60.14(e) of the General
Provisions to Part 60 lists several changes that are not considered
modifications. Among these is the use of raw material, if prior to the
date of proposal of the standard, the existing facility was designed to
accommodate that alternative use'' (49 FR 29707; July 23, 1984).
However, the EPA did not provide any further explanation at that time
as to why the Agency believed this exemption applied to this affected
facility, and the Agency has reconsidered the application of that
exemption for purposes of NSPS subpart Kc. As explained in section
III.G. of the proposal preamble, when the affected source is a storage
vessel and not a process unit, we no longer consider a change in the
liquid stored in the storage vessel (to an organic liquid with a higher
MTVP) to qualify as a ``use of an alternative fuel or raw material.''
As discussed above, the primary function of an affected facility in
this source category is the storage of materials, and the VOL stored in
the vessel are neither raw material nor alternative fuel inputs to a
process at the facility itself. While the storage vessel may store
liquids that are used as an alternative fuel or raw material used for
inputs to a process for another facility, it is not reasonable to
extend application of the exemption to mere storage of the alternative
fuel or raw material. Accordingly, we no longer believe that the
exemption should be applied to these factual circumstances by the terms
of the regulation.
---------------------------------------------------------------------------
\7\ See, e.g., U.S. EPA Applicability Determination Index,
Control Number: 0400015, (referencing 40 CFR 60.14(e)(4)-(5)) and
NSPS subpart Kb Background Information Document (Docket ID No. EPA-
HQ-OAR-2023-0358-0012).
---------------------------------------------------------------------------
The EPA notes that, the fact that 40 CFR 60.14(e) is framed as
exempting certain activities from the definition of modification
indicates that, absent these exemptions, the EPA would consider the
exempted activity to meet the statutory definition of modification in
CAA section 111(a)(4). In other words, the EPA created a specific
provision exempting the ``use of an alternative fuel or raw material''
from the regulatory definition of modification because this activity
would, as the EPA proposed, typically be considered an operational
change,\8\ a consideration reinforced by the EPA's discussion on
modification in the NSPS subpart Kb preamble. In this rulemaking, the
EPA confirms that it does not consider a change in the liquid stored to
one with a higher MTVP to qualify under this exemption. Moreover,
irrespective of this determination, the EPA is also finalizing in this
rulemaking that the exemption in 40 CFR 60.14(e)(4) regarding
alternative fuel or raw material does not apply to storage vessels.
---------------------------------------------------------------------------
\8\ This is bolstered when considering the other exemptions in
40 CFR 60.14(e): a ``replacement'' referred to in (e)(1) and the
addition of a system or device referred to in (e)(5) is a physical
change to a facility, and an increase in production rate or an
increase in hours of operation referred to in (e)(2) or (3) is a
change in the facility's operation. However, the EPA had a rational
basis for exempting these particular physical or operational
changes, as a general matter, from the broader definition of
modification under the regulations.
---------------------------------------------------------------------------
While we have determined for purposes of NSPS subpart Kc that a
change in the liquid stored to a liquid with a higher vapor pressure
does not constitute the ``use of an alternative fuel or raw material,''
we note that even if this exemption would otherwise apply by its terms,
this rulemaking supersedes the exemption pursuant to 40 CFR 60.14(f),
because, as explained earlier, we have concluded that it is the better
policy and consistent with the statutory definition of modification
based on the facts of how this affected facility operates. The EPA has
always maintained that there are some sources for which the basic
exemptions from the standard definition of a modification may not be
appropriate, and 40 CFR 60.14(f) was included in the general provisions
to afford the EPA the ability to supersede the general modification
regulations, the exemption provisions in 40 CFR 60.14(e), for those
sources for which these provisions should not reasonably be applied.
The EPA has previously applied specialized interpretations of
modification for other source categories. For example, in NSPS subpart
Ja, we included special provisions for the modification of flares at
petroleum refineries because the basic considerations under 40 CFR
60.14(e), were generally developed considering process unit emission
sources. The intermittent operation of a flare makes it difficult to
use the criteria of 40 CFR 60.14(e) to determine when a flare is
modified (73 FR 35843; June 24, 2008). In our review of NSPS subpart
Kb, we identified similar short-comings regarding the ``process unit-
oriented'' modification exemptions as previously applied to storage
vessels. The specialized modification provision for storage vessels is
consistent with the CAA statutory requirements, the general definition
of modification outlined in 40 CFR 60.2 and 60.14, and previous
determinations that source-specific modification provisions are
justified for certain source categories. Accordingly, in this
rulemaking, the EPA confirms that it does not consider a change in the
liquid stored to one with a higher MTVP to qualify under the exemption
in 40 CFR 60.14(e)(4), and, as a matter of clarity, irrespective of
this determination, this rulemaking is superseding the exemption.
With respect to the comment that the proposed definition of
modification would arbitrarily apply differently for identical vessels
based on their historic use rather than their design capabilities, we
disagree. As stated above, the modification provisions are directly
dependent on the MTVP of the stored VOL. The precedent of MTVP
dependent standards of performance for VOL storage vessels was
established as part of NSPS subpart K and has informed the
establishment of standards for subsequent rulemakings under NSPS
subparts Ka and Kb. We are finalizing that storing a VOL with a greater
MTVP than historically stored or permitted is a modification. We
determined the BSER and set standards of performance considering
existing emission controls of modified storage vessels.
The EPA also disagrees with the comment advocating a requirement
for capital expenditure to determine whether there is a modification
and that a capital expenditure clause should be added to the language
proposed at 40 CFR 110c(e). First, we note that the
[[Page 83306]]
statute at CAA section 111(a)(4) contains no such requirement and the
general provisions at 40 CFR 60.14(e)(2) only consider whether a
capital expenditure is needed when considering an exemption from the
definition of modification tied to increase in production at the
facility. Critically, neither the statute nor the general provisions
provide that the determination of whether a modification has occurred
must be based on a capital expenditure. Thus, the commenters seek to
impose an additional requirement that is not plainly necessary under
the statute nor anticipated, either by Congress or by the EPA, without
an explanation as to why that would be justified for this source
category. In many cases, a capital expenditure is not needed to change
the liquid stored in a fixed roof tank. Under the commenter's proposed
capital expenditure paradigm, an operator of a fixed roof tank used to
store a low volatility fluid could change to a higher vapor pressure
fluid and argue that no modification occurred even though the storage
vessel has changed its method of operation. This would permit the
resulting emissions increases without the requisite control that the
statute would otherwise anticipate under such circumstances. It is more
consistent with the statutory standard to consider the change in the
liquid stored or permitted as a change in the method of operation and
then assess whether an increase in the vapor pressure of the liquid
stored triggers the need for controls (which would require a capital
expenditure). We found the controls required under proposed NSPS
subpart Kc are cost effective and meet the BSER criteria, and we see no
reason to allow uncontrolled modified storage vessels or less stringent
controls simply because the tank was initially permitted for or stored
a less volatile liquid.
4. Control Standards for IFRs and EFRs
The EPA proposed standards of performance that reflect the BSER for
IFRs as well as alternative compliance standards for controlled storage
vessel EFRs. The EPA proposed a work practice standard that would
require new IFR storage vessels be constructed with either a liquid-
mounted or a mechanical shoe primary seal, a rim-mounted secondary
seal, and fittings on the floating roof that meet certain control
requirements (e.g., gasketed covers, specific guidepole control
configurations) mostly consistent with the requirements of fitting
controls in NSPS subpart Kb. The EPA also proposed that new EFR storage
vessels be constructed with either a liquid-mounted or a mechanical
shoe primary seal, a rim-mounted secondary seal, welded deck seams, and
fittings on the floating roof that meet certain control requirements
(e.g., gasketed covers, specific guidepole control configurations).
Except for the guidepole controls, the fitting controls are mostly
consistent with the requirements of fitting controls in NSPS subpart
Kb.
We are finalizing the control requirements for IFRs and EFRs as
proposed with minor editorial revisions (such as replacing ``roof leg
supports'' with ``roof supports,'' replacing ``bolted'' with ``bolted
or otherwise mechanically secured,'' and using consistent language
regarding requirements for vacuum breaker/automatic bleeder vents). For
EFRs, we are also adding provisions for emergency roof drains to be
provided with a slotted membrane fabric cover that covers at least 90
percent of the area of the opening. As noted by commenters, this
provision is included in NSPS subpart Kb and the IFR drain requirements
were inadvertently copied for EFRs in the proposed rule for NSPS
subpart Kc.
Comment: One commenter stated the proposed NSPS subpart Kc language
refers to the floating roof being supported by legs when the floating
roof is landed, but a common design for IFRs involves suspending the
IFR from the fixed roof of the tank via cables. The commenter stated
that proposed language at 40 CFR 60.112c(b)(1) and (4) should be
revised to accommodate the cable-suspended design alternative.
Similarly, a commenter recommended the EPA revise the definition of the
term ``Vacuum breaker/Automatic bleeder vent'' to avoid restricting
vacuum breakers to the leg-actuated type. Another commenter noted that
since leg operated vacuum breakers must contact the floor prior to the
roof support legs, the EPA should consider setting a maximum opening
distance or clarify that the roof is considered landed when the vacuum
breaker leg lands. One commenter noted that 40 CFR 60.112c(b)(1) reads
``. . . and during those intervals when the storage vessel is
completely emptied or subsequently emptied and refilled'' whereas 40
CFR 60.112c(c)(1) reads: ``. . . and when the storage vessel is
completely emptied and subsequently refilled.'' The commenter suggested
that the requirements for EFRs in 40 CFR 60.112c(c)(1) be revised to be
consistent with 40 CFR 60.112c(b)(1).
Response: We agree with the commenters that the language regarding
roof legs and vacuum breaker/automatic bleeder vents should be
generalized to allow roof supports other than roof legs and vacuum
actuations other than leg actuated devices and that consistent language
should be used for EFRs. While we understand cable suspended roofs are
specific to IFRs, we generalized the language for EFRs in the event
different supports are developed for EFRs and to make the language
consistent between 40 CFR 60.112c(b) and (c). We also revised the use
of the term ``vacuum breaker'' by replacing it with ``vacuum breaker/
automatic bleeder vent'' because that is the defined term for these
devices on a floating roof and to distinguish these from vacuum
breaking devices on a fixed roof. We are also adding a sentence to the
roof landing monitoring requirements at 40 CFR 60.113c(a)(5) and (b)(8)
to clarify that the roof is considered landed when the floating roof
first rests on supports or when the vacuum breaker/automatic bleeder
vent begins to open, whichever is first. This clarifies that the
landing alarm must be set at the height the leg-actuated vacuum
breaker/automatic bleeder vent begins to open the vent, which will be
prior to the floating roof resting on the roof supports.
Comment: One commenter stated that the proposed NSPS subpart Kc
does not address the emergency roof drains that are utilized with
certain EFRs. The commenter noted that NSPS subpart Kc specifies that
``stub drains'' are not required to be covered at all, which could be
understood as exempting EFR emergency roof drains from control. The
commenter recommended that the EPA clarify, consistent with NSPS
subpart Kb at 40 CFR 60.112(b)(2)(ii), that each emergency roof drain
is to be provided with a slotted membrane fabric cover that covers at
least 90 percent of the area of the opening.
Response: We agree with the commenter that we inadvertently used
the language allowing uncontrolled stub drains for IFRs in the proposed
EFR requirements. We had intended to maintain consistency with the EFR
drain requirements in NSPS subpart Kb. We agree with the commenter that
the reference to stub drains for EFRs is not appropriate as stub drains
are not used for EFRs. In the final rule, we are including the
requirements to use a slotted membrane fabric cover that covers at
least 90 percent of the area of the opening at 40 CFR
60.112c(c)(2)(viii) consistent with the requirements for EFR drains in
NSPS subpart Kb, as suggested by the commenter.
[[Page 83307]]
5. Control Standards for Closed Vent Systems Routed to a Control
Device, Fuel Gas System, or Process
For storage vessels with closed vent systems routed to a control
device, fuel gas system, or process, the EPA proposed certain design
requirements for the storage vessel to prevent pressure releases from
the storage vessel and proposed that control devices must meet 98
percent or greater emission reduction efficiency. The EPA proposed that
non-flare thermal combustion devices must conduct performance tests
initially and at least once every 60 months, in which they establish a
temperature operating limit to which they must comply at all times. For
flares, the EPA proposed that flares must meet the operating and
monitoring requirements consistent with the requirements in the
Refinery NESHAP (40 CFR 63.670 and 63.671). We are finalizing
requirements for closed vent systems routed to a control device, fuel
gas system, or process with some revisions from proposal for reasons
noted in the following comments and responses.
First, we are revising the vacuum pressure at which vacuum breaking
devices must close from -0.1 pounds per square inch gauge (psig) to -
0.1 inches of water (-0.0036 psig) to better reflect common storage
vessel design requirements. We are also clarifying the language since a
higher vacuum setting would be a lower absolute pressure and the
proposed language was potentially ambiguous. The revised provision
clarifies that any vacuum breaking device on the storage vessel must
close while the storage vessel is still under vacuum of at least -0.1
inches of water (-0.0036 psig or -0.025 kPa gauge). We proposed that
storage vessels that are vented to a closed vent system must be
designed to operate at elevated pressures (1 psig above MTVP plus any
back pressure from the control device) without venting to the
atmosphere. We are retaining this as an option but are adding an option
to design and operate the recovery system to prevent venting from the
storage vessel. In either case, we are retaining requirements
consistent with those proposed that monitoring systems must be
installed to detect pressure releases from each pressure relief device
(PRD) or vacuum breaking device on a storage vessel and each PRD on the
closed vent system. For owner and operators electing to design the
storage vessel and closed vent system to operate at elevated pressures,
we are including provisions that allow the control device to be taken
out of service for maintenance provided that the storage vessels are
operated with no emissions to the atmosphere.
We are retaining requirements for control devices to meet 98
percent control efficiencies as proposed. We allow enclosed combustion
devices to demonstrate on-going compliance with the 98 percent control
efficiency using temperature operating limit, as proposed. However, we
are also finalizing an alternative for enclosed combustion devices, if
elected, to comply with the flare operating limits, consistent with
recent provisions provided for gasoline distribution facilities (40 CFR
part 60, subpart XXa and 40 CFR part 63, subparts R and BBBBBB).
Lastly, we are amending the requirements for open-ended lines to align
with provisions more closely under the Miscellaneous Organic Chemical
Manufacturing NESHAP (MON).
Comment: Two commenters suggested that the pressure constraints on
design operating pressure and vacuum breaking devices are not
technically feasible and could result in significant damage or failures
of the storage vessels, stating that a gauge pressure higher than the
designed pressure of the storage vessel or a vacuum greater than the
design requirements could result in catastrophic failure of the storage
vessel. The commenters noted that the proposed requirements conflict
with American Petroleum Institute (API) Codes 650 and 2000. The
commenters recommended the EPA delete the specific pressure
requirements proposed and replace with general language that
atmospheric vents should be designed to remain closed during normal
operation.
Response: In the proposal, we intended to require the use of low-
pressure storage vessels rather than atmospheric storage vessels so
that the storage vessels would be built to withstand higher pressures.
However, we recognize that this may be a more significant retrofit for
modified storage vessels with gas collection systems designed to
operate at lower pressures such that the pressure in the storage
vessels can remain near atmospheric pressure. However, if the vapor
recovery compressor or fan fails or is shut down for any reason, then
the storage vessel would vent rather than being able to withstand the
buildup of pressure as the headspace in the storage vessel reaches
saturation without venting to the atmosphere like a low-pressure
storage vessel would. We are maintaining the positive pressure
requirements as one compliance option, but we are also finalizing an
option for facilities to design and operate a vapor recovery system in
a manner to prevent atmospheric releases from the storage vessel. As
proposed, any pressure release from the storage vessel is a deviation
of the storage vessel and closed vent system requirements. We are
finalizing monitoring system requirements for the pressure relief
devices and vacuum breaking devices to identify these deviations.
With respect to the vacuum requirements, we reviewed the API 650
standards applicable to low-pressure storage vessels and found in
section 5.10.5.2 that these storage vessels ``. . . may be safely
subjected to a partial vacuum in the gas or vapor space not exceeding 1
ounce per square inch with the operating liquid level in the tank at
any stage from full to empty.'' One ounce per square inch is equivalent
to 0.0625 psi or 2 inches of water, so we agree that the vacuum
requirement proposed is beyond standard design requirements for low-
pressure storage vessels. We also confirmed that the API 650 standard
indicates that the maximum vacuum for atmospheric storage vessels
(without needing additional design considerations) is -0.25 kPa (or -1
inch of water or -0.036 psig). In our proposal, we wanted to ensure
that the vacuum vent is closed while there is still a slight vacuum in
the storage vessel, to prevent venting to the atmosphere from the
vacuum breaking device as the pressure in the storage vessel increases.
In reviewing the storage vessel specifications, we determined that the
value we proposed was higher than needed to achieve this objective. The
vacuum breaking devices must open before the maximum vacuum pressure is
reached, so typical opening pressures are 0.5 inches of water pressure.
Therefore, we are finalizing that the vacuum breaking device must close
while the storage vessel is still under vacuum of at least -0.1 inches
of water (-0.0036 psig or -0.025 kPa gauge) and are finalizing that a
pressure release (deviation) occurs when the vessel reaches atmospheric
pressure and the vacuum breaking device remains open. We are providing
separate paragraphs for the monitoring requirements for PRDs between
storage vessels and closed vent systems and adding monitoring
requirements for the vacuum breaking devices on the storage vessels.
Otherwise, the separate pressure release monitoring requirements we are
finalizing in 40 CFR 60.112c(d)(1)(iii) and (d)(2)(iii) are the same as
proposed for ``each pressure relief device on a storage vessel or in a
closed vent system,'' in 40 CFR 60.112c(d)(2)(iii).
[[Page 83308]]
Comment: One commenter recommended that the EPA add a 240-hour
planned routine maintenance provision for storage vessels equipped with
a closed vent system routed to a control device to NSPS subparts Kb and
Kc similar to the language in the part 63 NESHAP regulations such as
the MON and Organic Liquids Distribution (non-gasoline) NESHAP.
According to the commenter, if the EPA decides to retain the language
in 40 CFR 60.110c(g) removing the SSM provisions, it is reasonable for
the EPA to include a separate 240-hour planned routine maintenance
provision for control devices in NSPS subpart Kc similar to the
language in the MON (40 CFR 63.2470(d)) and the associated
recordkeeping and reporting requirement similar to the language in 40
CFR 63.998(d)(2) and 63.999(c)(4).
Response: We disagree that we should provide 240 hours for
uncontrolled emissions when using an add-on control device. Similar
provisions are not needed or appropriate for IFRs, which were
determined to be the BSER for storage vessels storing VOLs with an MTVP
less than 11.1 psia. We maintain that a 98 percent control requirement
at all times is necessary for add-on control devices to achieve
emission reductions equivalent to those for IFRs. Even for storage
vessels storing VOLs with an MTVP of 11.1 psia or higher, we maintain
that a 98 percent control requirement is the BSER, and that level of
control cannot be achieved if we allow 240 hours of uncontrolled
emissions. Nonetheless, if the storage vessel is designed to be able to
operate at pressures above the MTVP consistent with the storage vessel
design pressure requirements proposed (and being finalized as one
compliance option), then the control device can be isolated from the
storage vessel, and the closed vent system and the storage vessel can
remain in service without venting to the atmosphere provided that the
storage vessel is not filled to the extent that the pressure limits of
the pressure relief valves on the storage vessel and closed vent system
are exceeded and there is a pressure release. If there is no pressure
release from the storage vessel during the planned maintenance
activity, we agree that planned maintenance can be allowed. Therefore,
we are including provisions at 40 CFR 60.112c(d)(7) to allow owners or
operators to conduct planned maintenance on control devices while
storage vessel affected facilities are still storing VOL under specific
circumstances. Specifically, the storage vessel(s) storing VOL must be
designed to operate above the MTVP of the stored VOL according to the
requirements in 40 CFR 60.112c(d)(1)(i) and must comply with the
pressure release monitoring, recordkeeping, and reporting requirements.
Eliminating pressure releases during the maintenance periods may
require operators to limit VOL addition to the storage vessel (such as
only adding VOL when there is also corresponding withdrawal of VOL from
the storage vessel), but the operator is expected to operate the
storage vessel without a pressure release or atmospheric venting during
the maintenance period.
Comment: One commenter stated that the EPA should define ``vapor
combustion unit'' separately from ``incinerator'' and apply appropriate
monitoring provisions to vapor combustion units (VCUs) to avoid
subjecting VCUs to inappropriate requirements. The commenter stated
that the EPA should allow VCUs to elect to meet the proposed flare
provisions, as was provided in the Gasoline Distribution rules.
Response: In general, we agree with the commenter. We note that we
had proposed specific requirements for ``enclosed combustion devices''
so we elected to define that term. We recognize that some enclosed
combustion devices may operate more like a flare than like an
incinerator (no direct combustion chamber and no means to control the
amount of air entering the device). In similar situations in other
rules (gasoline distribution rules at 40 CFR part 60, subpart XXa, and
40 CFR part 63, subparts R and BBBBBB, and the oil and gas rule at 40
CFR part 60, subparts OOOOb and OOOOc), we have allowed the enclosed
combustion devices to comply with the flare operating limits rather
than with the temperature operating limit. As such, we agree with the
commenter's suggestion to allow enclosed combustion devices to comply
with the flare operating limits. We have added a definition of both
``enclosed combustion device'' and ``flare'' to help distinguish
between these devices (enclosed combustion devices emit pollutants
through a conveyance suitable to conduct a performance test, and flares
have open or shrouded flames and do not emit pollutants through a
conveyance suitable to conduct a performance test). We note that the
implementation of this provision led to revision of several paragraphs
related to control device operating limits and monitoring,
recordkeeping, and reporting requirements to allow ``enclosed
combustion devices electing to comply with Sec. 60.112c(d)(5)'' to be
treated differently than other non-flare combustion devices. We are
retaining the requirement for enclosed combustion devices to conduct a
performance test to demonstrate that the enclosed combustion device is
achieving a 98 percent VOC emission reduction regardless of whether the
enclosed combustion device is complying with the flare operating limits
in 40 CFR 60.112c(d)(5) or the temperature operating limits in 40 CFR
60.113c(c)(1)(ii)(E).
Comment: One commenter stated that the EPA should clarify in the
final NSPS subpart Kc rule, in the closed vent system and bypass line
provisions, that open-ended valves or lines that use a cap, blind
flange, plug, or second valve are not considered to be bypass lines.
According to the commenter, the EPA should add the text that is in 40
CFR 63.2450(e)(6)(v)(B) of the MON rule to 40 CFR 60.112c(d)(2)(ii) to
clearly exempt these open-ended valves or lines from the bypass
requirements.
Response: We agree with the recommendations to align NSPS subpart
Kc more closely with the provisions in the MON regarding open-ended
valves or lines that use a cap, blind flange, plug, or second valve,
and have revised to 40 CFR 60.112c(d)(2)(ii) accordingly.
6. Control Standards for Degassing
Based on the analysis presented at proposal, the EPA proposed
emptying and degassing standards in accordance with the BSER applicable
to: (1) storage vessels equipped with a closed vent system routed to a
control device, fuel gas system, or process; and (2) IFR and EFR
storage vessels that have a capacity of greater than or equal to 1
million gallons storing a VOL with an MTVP greater than or equal to 1.5
psia. These vessels must meet certain requirements while the vapors in
the storage vessel are at or above 10 percent of the LEL. The proposed
standards of performance for degassing emissions reflect a 98 percent
VOC reduction efficiency.
Regarding degassing controls, we are finalizing these provisions
with minor revisions to what was proposed. We are finalizing standards
for storage vessels subject to controlling degassing emissions as
proposed. We are finalizing a requirement that controls must be used
until the vapor space concentration is less than 10 percent of the LEL,
as proposed, but we are also finalizing provisions for nonflammable
liquids to comply with a 5,000 ppmv as methane concentration level
based on comments received, because 5,000 ppmv is equal to 10 percent
LEL if the vapors were methane. We are finalizing that the degassing
emissions that must be controlled must be vented to control
[[Page 83309]]
device that achieves a 98 weight percent VOC reduction or greater as
proposed. We are finalizing additional provisions to check LEL
instrument calibration and instrumental offset response each day the
instrument is used and prior to discontinuing controlled degassing
consistent with LEL measurement requirements for IFR monitoring to
ensure the accuracy of the instrument readings. We are also finalizing
provisions that allow the introduction of chemicals or diluents for the
purpose of reducing vapor concentration before or during active
degassing, after considering comments received.
Comment: Two commenters stated that the EPA should incorporate a
concentration limit for the storage vessel degassing emissions in 40
CFR 60.112c(e) since nonflammable chemicals do not exhibit an LEL. The
commenter requested that the EPA include a concentration limit of less
than 5,000 ppmv as methane as an alternative to the LEL requirement,
consistent with the National Emission Standards for Organic Hazardous
Air Pollutants From the Synthetic Organic Chemical Manufacturing
Industry proposal.
Response: We expect that most VOLs with an MTVP above 1.5 psia will
have some flammability, but we agree that a concentration limit of
5,000 ppmv as methane for nonflammable liquids is appropriate because
5,000 ppmv is the 10 percent LEL of methane and it generally provides a
concentration value that is similar to or lower than the 10 percent LEL
level for heavier organics. For example, 10 percent LEL of butane is as
stringent as or more stringent than 1,900 ppmv as butane or about 7,600
ppmv as methane.
Comment: One commenter noted that some companies flood the bottom
of the tank with a low vapor pressure material to facilitate removal of
residual sludges and/or to reduce the concentration of vapors in the
vapor space of the tank prior to or during active degassing. According
to the commenter, while the proposed rule language does not prohibit
bottom flushing, this practice should be expressly accommodated in the
rule language.
Response: We agree that flooding the bottom of the tank with a low
vapor pressure material is a reasonable control measure for degassing.
As such, we are revising 40 CFR 60.112c(e)(1) to expressly allow the
addition of chemical or a diluent for the purpose of reducing vapor
concentration before or during active degassing.
7. Alternative Means of Emission Limitation
We are finalizing the alternative means of emissions limitation
(AMEL) provisions as proposed except for the addition of two
clarifications. First, at 40 CFR 60.114c(a), we are replacing ``any''
with ``the applicable'' when referencing requirements in 40 CFR
60.112c, to clarify that the equivalency must be made for the same type
of control system (IFR, EFR, or closed vent system routed to a control
device, fuel gas system, or process). This clarification prevents
operators that are using an IFR from reducing the fitting control
requirements finalized for an IFR because, for that size of storage
vessel and stored VOL, the required IFR controls achieve greater than a
98 percent reduction or greater reduction than an EFR meeting the final
EFR requirements. Second, we are clarifying that the written
application to the Administrator in 40 CFR 60.114c(c) may include
either actual emissions test results or an engineering evaluation that
the Administrator determines to be accurate, but it does not
necessarily have to include both.
Comment: One commenter noted the proposed NSPS subpart Kc provides
for requesting an AMEL at 40 CFR 60.114c and this section specifies
that a request for approval of an alternative must include an actual
emissions test; however, there are numerous alternative control
measures that have already been tested and for which the EPA has
published emission factors in AP-42. The commenter stated that the EPA
should not arbitrarily require repeated testing for those control
measures that have already been tested and for which the results have
already been accepted by the EPA. The commenter stated that the
language in 40 CFR 60.114c should be replaced with the language in
NESHAP subpart WW at 40 CFR 63.1064.
Response: We have revised 40 CFR 60.114c(c) such that an AMEL
written application must include either an actual emissions test (that
covers the appropriate range of meteorological conditions) or an
engineering evaluation, which may include use of emission factors as
published in the EPA Report No. AP-42, Compilation of Air Pollutant
Emission Factors. We reviewed the AMEL provision in NESHAP subpart WW.
The NESHAP subpart WW provisions include a listing of test methods but
do not limit the testing to those methods. As such, we are determining
that the language that is included in the final rule is equivalent to
the provisions in NESHAP subpart WW. We also note that the provisions
in 40 CFR 63.1064(c) allow the use of different combinations of rim and
deck fitting controls ``. . . if the alternate emits no more than the
combination specified in the Sec. 63.1063.'' We interpret this
provision to allow comparisons of fitting controls for IFRs to those
required specifically for IFRs. While we consider that the three
control options we provided are equivalent, we acknowledge that,
depending on the size of tank, volatility of the VOL, and prevailing
meteorological conditions, one of the control configurations (IFR, EFR,
or closed vent system routed to a control device, fuel gas system, or
process) will perform better and one configuration will perform worse
than the other options allowed. We did not intend to allow changes to
the specified control provisions to only require the lowest control
efficiency for a given combination of tank size, VOL stored, and
meteorological conditions. Therefore, we are also clarifying,
consistent with our interpretation of the NESHAP subpart WW provisions,
that the AMEL must compare with the ``applicable'' requirement. That
is, for storage vessels with IFRs, you may request an AMEL for a
different set of fittings, but you must show equivalency with the IFR
requirements specified in 40 CFR 60.112c(b). For storage vessels with
EFRs, the AMEL must show equivalency with the EFR requirements
specified in 40 CFR 60.112c(c). For storage vessels with a closed vent
system routed to a control device, fuel gas system, or process, the
AMEL must show equivalency with the control requirements specified in
40 CFR 60.112c(d). With these revisions, we determine that the final
AMEL provisions in NSPS subpart Kc are consistent with the AMEL
provisions in NESHAP subpart WW.
Since control measures that were determined to be equivalent to
NSPS subpart Kb may not be equivalent to controls required under NSPS
subpart Kc, a new AMEL application must be submitted following 40 CFR
60.114c(c) in order to demonstrate that an AMEL is equivalent to the
requirements in NSPS subpart Kc.
C. NSPS Subpart Kc Without Startup, Shutdown, and Malfunction
Exemptions
Consistent with Sierra Club v. EPA, 551 F.3d 1019 (D.C. Cir. 2008),
the EPA has established standards in this rule that apply at all times.
We are finalizing in NSPS subpart Kc specific requirements at 40 CFR
60.110c(g) that override the general provisions for SSM requirements.
In finalizing the standards in this rule, the EPA has considered
[[Page 83310]]
startup and shutdown periods and, for the reasons explained in this
section of the preamble, has not finalized alternate standards for
those periods. The EPA has determined that the reasoning in the court's
decision in Sierra Club applies equally to CAA section 111 because the
definition of ``emission standard'' in CAA section 302(k), and the
embedded requirement for continuous standards, also applies to the
NSPS.
Periods of startup, normal operations, and shutdown are all
predictable and routine aspects of a source's operations. Malfunctions,
in contrast, are neither predictable nor routine. Instead, they are, by
definition, sudden, infrequent, and not reasonably preventable failures
of emissions control, process, or monitoring equipment (40 CFR 60.2).
The EPA interprets CAA section 111 as not requiring emissions that
occur during periods of malfunction to be factored into development of
CAA section 111 standards. Nothing in CAA section 111 or in caselaw
requires that the EPA consider malfunctions when determining what
standards of performance reflect the degree of emission limitation
achievable through ``the application of the best system of emission
reduction'' that the EPA determines is adequately demonstrated. While
the EPA accounts for variability in setting emissions standards,
nothing in CAA section 111 requires the Agency to consider malfunctions
as part of that analysis. The EPA is not required to treat a
malfunction in the same manner as the type of variation in performance
that occurs during routine operations of a source. A malfunction is a
failure of the source to perform in a ``normal or usual manner,'' and
no statutory language compels the EPA to consider such events in
setting CAA section 111 standards of performance. The EPA's approach to
malfunctions in the analogous circumstances (setting ``achievable''
standards under CAA section 112) has been upheld as reasonable by the
D.C. Circuit in U.S. Sugar Corp. v. EPA, 830 F.3d 579, 606-610 (2016).
D. Testing, Monitoring, and Inspection Requirements
Because the NSPS reflect the BSER under conditions of proper
operation and maintenance, we also, in performing our review, evaluate
and determine the proper testing, monitoring, inspection,
recordkeeping, and reporting requirements needed to ensure compliance
with the emission standards. This section of the preamble includes our
discussion of the proposed revisions to testing, monitoring, and
inspection requirements, a summary of the significant comments
received, our responses to the comments, and our final determinations
regarding testing, monitoring, and inspection requirements. Changes to
recordkeeping and reporting requirements are included in the section
for recordkeeping and electronic reporting.
Generally, we proposed testing, monitoring, and inspection
requirements consistent with those in NSPS subpart Kb and other Federal
standards that would provide the best clarity for the specific
requirements along with the following enhancements. The EPA proposed
annual LEL monitoring as an enhancement to the monitoring and
inspection requirements for storage vessels with IFRs. The EPA also
proposed equipping floating roof storage vessels with a visual or
audible alarm system to monitor when the floating roof approaches
specified landing heights. For closed vent systems, the EPA proposed
quarterly AVO inspections, annual EPA Method 21 instrument monitoring,
and monitoring of bypasses. The EPA also proposed that storage vessels
using closed vent systems routed to control devices, fuel gas systems,
or processes must equip pressure relief devices with appropriate
monitoring to identify releases. For storage vessels with closed vent
systems routed to a control device, the EPA proposed that performance
tests must be conducted at least once every 60 months rather than rely
on a single initial performance test. Finally, the EPA proposed
enhanced monitoring requirements for flares consistent with the
Refinery NESHAP (40 CFR 63.671).
We are finalizing testing, monitoring, and inspection requirements
as proposed except for the revisions outlined here.
We revised the specification of the timing of these
requirements to be ``calendar months'' rather than just ``months,'' to
clarify the timing and allow limited flexibility when scheduling the
required testing or inspections.
For IFRs, we are amending the requirements to conduct
internal inspections of the floating roof at least once every 120
calendar months. We are retaining this inspection requirement each time
the vessel is emptied and degassed, but we are not requiring storage
vessels to be taken out of service specifically to conduct this
inspection.
We are making minor revisions to the LEL monitoring
calibration procedures. We proposed language used from the gasoline
distribution rule (40 CFR part 63, subpart R), which would require the
correction factor to be based on ``gasoline vapor.'' Because NSPS
subpart Kc is applicable to a much broader range of chemicals, we are
revising references to ``gasoline vapors'' to ``vapors of the stored
VOL.'' We are retaining the use of butane as the surrogate if
correction factors are not available for the vapors of the VOL stored.
We are adding specific requirements that fittings on EFR
must be visually inspected during annual seal gap measurement
inspections to ensure that covers are closed and gasketed with no
visible gaps and that there are no tears in sleeves, wipers, or similar
controls used for a given fitting during annual seal gap measurement
inspections. Visual fitting inspections were proposed at 40 CFR
60.113c(b)(7) for inspections conducted when the storage vessel is
emptied and degassed but did not specify fitting conditions that would
result in an inspection failure, and we are adding these details to
clarify the fitting inspection requirements based on comments received.
For closed vent systems, we are including an additional
reference at 40 CFR 60.113c(c)(2) for the quarterly AVO monitoring as
required under both the proposed and final requirements at 40 CFR
60.112c(d)(2)(i). We are also revising the provision of 40 CFR
60.113c(c)(3) to clarify that emissions detected using visible,
audible, and olfactory methods are leaks triggering corrective action.
Regarding MTVP test methods, we are clarifying that owners
and operators must determine the MTVP of the VOL prior to refilling the
storage vessel with a new VOL. The proposed language only referenced
``initial filling'' and may allow facilities to change VOL without
reassessing the MTVP. However, we considered that, when a new VOL is
stored, that would be an initial filling of that VOL. The rephrasing of
that provision helps to clarify this requirement. Additionally, we are
adding a requirement to use a vapor-to-liquid ratio of 4:1 when using
American Society for Testing and Materials (ASTM) D6378-22. We proposed
this requirement when using ASTM D6377-20 but consider that the same
provision should apply to both of the MTVP test methods. The EPA's
intention to use a vapor-to-liquid ratio of 4:1 when using ASTM D6378-
22 was detailed in the proposal preamble but was erroneously omitted
from the proposed rule text.
Additionally, as noted in section IV.B.5. of this
preamble, we are allowing enclosed combustion devices to comply with
the monitoring provisions for flares as an alternative to the
temperature monitoring requirement.
[[Page 83311]]
Comment: One commenter stated that the EPA's proposed monitoring
and inspection requirements for floating roof tanks are inadequate and
must be strengthened to make it more likely that the tanks can reduce
98 percent of VOCs. According to the commenter, at a minimum, the EPA
must require monitoring and inspection in keeping with the current
requirements from South Coast Air Quality Management District (SCAQMD)
Rule 1178. In addition, the commenter stated that the EPA must make it
explicit that, for IFR visual inspections, the entire perimeter of the
floating roof seal must be visually evaluated, even if that requires
opening multiple manways. The commenter stated that the EPA must also
require quarterly forward-looking infrared measurements from tank
decks.
Response: In general, we considered that we had incorporated much
from the SCAQMD Rule 1178 monitoring provisions in our proposal. We
included LEL monitoring provisions for IFR storage vessels and PRD
monitoring provisions for storage vessels with closed vent systems
routed to a control device, fuel gas system, or process that are
reasonably consistent with the monitoring requirements in SCAQMD Rule
1178. However, upon further review of SCAQMD Rule 1178 and our proposed
inspection requirements, we noted that the inspection requirements we
proposed for EFR storage vessels only covered inspections of the
primary and secondary seals. Visual fitting inspections were proposed
for IFR inspections and mentioned in the proposed inspections at 40 CFR
60.113c(b)(7) when the storage vessel is emptied and degassed. However,
no requirement for fitting inspections were proposed during annual gap
measurements, and the inspections proposed at 40 CFR 60.113c(b)(7) did
not specify fitting conditions that would result in an inspection
failure. After our review of SCAQMD Rule 1178 monitoring and inspection
requirements based on this comment, we are adding specific requirements
that fittings on EFR must be visually inspected during annual seal gap
measurement inspections to ensure that covers are closed and gasketed
with no visible gaps and that there are no tears in sleeves, wipers, or
similar controls used for a given fitting. We are also adding the
conditions under which an inspection failure occurs for the inspections
conducted when the EFR storage vessel is emptied and degassed.
We considered optical gas imaging requirements in previous reviews
of storage vessels, which we reviewed again for NSPS subpart Kc, and
concluded that these requirements were not cost-effective. Regarding
manways, we agree with the commenter's assertion that while performing
IFR visual inspections, the entire perimeter of the floating roof seal
must be visually evaluated, even if that requires opening multiple
manways. We have elected not to add specific rule language, because we
believe that having visual access to the entire primary seal, is
already a necessary component of annual IFR inspections both in the
rule language of NSPS subpart Kc and in the existing rule language of
NSPS subpart Kb. As such, except for the specifications for fitting
inspections for EFR storage vessels, we are not adding additional
monitoring requirements to NSPS subpart Kc.
Comment: Numerous commenters requested that the EPA allow in-
service inspections of IFRs either by providing additional language in
40 CFR 60.113c(a)(2) allowing for top-side inspections when there is
visual access to all deck components or by incorporating an alternate
means of compliance option to comply with NESHAP subpart WW [40 CFR
63.1063(d)(1) and (2)]. The commenters noted that in-service
inspections were allowed in NSPS subpart Kb to avoid the costs and
emissions associated with emptying and degassing vessels for
inspection. If in-service inspections are provided, the commenters
noted, rule revisions may also be needed in the notification
requirements at 40 CFR 60.116c(b)(1) and the reporting requirements at
40 CFR 60.116c(c)(2)(ii).
Response: We had proposed language consistent with NSPS subpart Kb
at 40 CFR 60.113b(a)(4) to require more detailed ``out of service''
inspections at least once every 10 years. The EPA agrees with the
commenter's request to allow for in-service inspections to be performed
entirely from the top side of the floating roof. The EPA is
incorporating language into 40 CFR 60.113c(a)(2)(ii) to allow for in-
service inspections to be performed entirely from the top side of the
floating roof, as long as there is visual access to all deck fittings
and rim seal systems specified in 40 CFR 60.112c(b). We are also adding
repair timelines in 40 CFR 60.112c(b), similar to those already
established for the annual visual inspection. We are also specifying
that a 30-day notification must be provided for inspections in 40 CFR
60.116c(b)(1). Also, we are deleting the phrase ``emptied and degassed
and'' from 40 CFR 60.116c(c)(2)(iii) to account for the reporting of
these in-service inspections.
Comment: One commenter stated that the calibration requirements for
the LEL meter in 40 CFR 60.113c(a)(3)(ii) and (iv) that are specified
for demonstrating compliance with the 25 percent LEL limit for IFR
storage vessels are burdensome and should be simplified to be
consistent with the calibration requirements for the LEL meter within
the storage vessel degassing requirements in 40 CFR 60.112c(e). The
commenter stated that following the procedures for ``calibration and
maintenance according to manufacturer's specifications'' should be
adequate for both sections of the rule. The commenter recommended that
the EPA simplify the language in 40 CFR 60.113c(a)(3)(ii) and (iv)
consistent with the LEL calibration requirements in the storage vessel
degassing section. Another commenter noted that the language at 40 CFR
60.113c(a)(3)(iv) references gasoline vapors and should be generalized
to accommodate other stored VOLs.
Response: We disagree that the LEL calibration requirements in 40
CFR 60.113c(a)(3)(ii) and (iv) are burdensome. These paragraphs allow
the use of manufacturers' calibration methods, and they primarily
specify when calibration checks must be made and specify the LEL span
response. Upon review of the two LEL monitoring requirements, we are
adding more specific calibration requirements for the LEL monitoring
instrument used to monitor degassing. Specifically, we are requiring
calibration and zero offset checks each day and at the end of the
degassing event prior to completion to confirm that the final readings
are accurate before controlled degassing can be discontinued.
With respect to the comment regarding the reference to gasoline
vapors in the calibration requirements at 40 CFR 60.113c(a)(3)(iv), we
agree that the proposed language needed to be generalized. We used
calibration language from the gasoline distribution rule (40 CFR part
63, subpart R), which requires the correction factor to be based on
``gasoline vapor.'' Because NSPS subpart Kc is applicable to a much
broader range of chemicals, we are revising references to ``gasoline
vapors'' to ``vapors of the stored VOL.'' We are, however, retaining
the use of butane as the surrogate if correction factors are not
available for the vapors of the VOL stored, because a surrogate is
needed when no published correction factor is available for the VOL,
and butane is considered a reasonable surrogate for any VOL that does
not have a published correction factor.
Comment: Two commenters stated that EPA Method 21 testing is
laborious, costly, and time-consuming for
[[Page 83312]]
facilities. One commenter believes that the sensory monitoring
provisions as proposed would place undue burdens on operators and would
result in redundancy in monitoring and compliance measures. Both
commenters stated that when coupled with the quarterly sensory testing,
the requirement for annual EPA Method 21 testing is unnecessary. One
commenter submitted a 1997 rule interpretation memorandum written by
the Texas Natural Resource Conservation Commission, which explained
that the EPA Method 21 test under NSPS subpart Kb is not considered a
performance test under 40 CFR 60.8 since the EPA Method 21 is
considered a screening measurement rather than a performance test,
subject to the recordkeeping requirements in the General Provisions of
40 CFR 60.7(f) and not required to be reported by either NSPS subpart A
or Kb. The commenter requested that the EPA discuss whether the EPA
agrees or disagrees with this guidance and whether the interpretation
also applies to NSPS subpart Kc.
Response: We disagree that quarterly AVO monitoring is burdensome.
If a leak is found via AVO monitoring, it triggers corrective action.
Additionally, we disagree that annual EPA Method 21 monitoring is
unnecessary, because EPA Method 21 will detect small emissions sources
that are above 500 ppm but that would remain undetected by AVO
monitoring. The closed vent system is to be operated ``with no
detectable emissions as indicated by an instrument reading of less than
500 ppm above background and visual inspections, as determined in part
60, subpart VV, Sec. 60.485(b).'' In the case of NSPS subpart Kb, 40
CFR 60.113b(c) states: ``The owner or operator of each source that is
equipped with a closed vent system and control device as required in
Sec. 60.112b (a)(3) or (b)(2) (other than a flare) is exempt from
Sec. 60.8 of the General Provisions and shall meet the following
requirements.'' As such, the language in NSPS subpart Kb indicates that
40 CFR 60.8 does not apply.
For NSPS subpart Kc, we used language that the closed vent system
must operate ``. . . with no detectable emissions as indicated by an
instrument reading of less than 500 ppmv above background . . .'' (see
40 CFR 60.112c(d)(2)), but there is no clear exemption from 40 CFR 60.8
in 40 CFR 60.113c(c)(2). Nonetheless, we agree that the requirements in
40 CFR 60.8 do not apply to EPA Method 21 instrument monitoring under
NSPS subpart Kb. Unlike in NSPS subpart Kb, we proposed and are
finalizing reporting requirements in NSPS subpart Kc for EPA Method 21
instrument monitoring events. In reviewing the proposed NSPS subpart Kc
provisions related to EPA Method 21 and AVO monitoring, we recognized
that we focused on the instrument monitoring requirements when using
EPA Method 21 and inadvertently neglected to mention the AVO inspection
requirements. Therefore, we are adding reference to the monthly AVO
monitoring requirement in 40 CFR 60.113c(c)(2) consistent with the
requirement under the proposed and final requirements at 40 CFR
60.112c(d)(2)(i), and we are revising the provision of 40 CFR
60.113c(c)(3) to clarify that emissions detected using AVO methods are
``leaks'' triggering corrective action. This latter revision also
clarifies that leaks identified from AVO monitoring do not trigger the
need to conduct EPA Method 21 monitoring of an AVO-identified leak. In
our review, we also identified a lack of reporting requirements related
to AVO-identified leaks. Therefore, we have also revised what we
proposed for recordkeeping requirements at 40 CFR 60.115c(d)(3)(v) and
reporting requirements at 40 CFR 60.116c(f)(8)(ii) to indicate the type
of monitoring conducted and to report information regarding all leaks
identified, not just those identified during EPA Method 21 instrument
monitoring.
Comment: Several commenters requested revisions to the vapor
pressure testing requirements for mixtures of indeterminate or variable
composition to define the term ``variable'' and to not require the
initial and repeat physical testing for liquids whose upper and lower
bounds of vapor pressure are known or are readily calculated using
standard reference texts and good engineering judgment.
Response: We agree with the commenters that the concept of
``variable compositions'' of stored liquid mixtures for which the
proposed rule would require initial and repeat physical testing to
determine MTVP could be applied more broadly than intended. Thus, in 40
CFR 60.113c(d)(1) of the final rule, we are clarifying that for
mixtures of variable composition, if the range of concentrations for
each constituent is known such that the MTVP can be determined from
data and procedures in standard reference texts, then physical testing
is not required. Similarly, under the final rule, physical testing is
not required for crude oils and refined petroleum products for which
Reid vapor pressure is known and MTVP can be determined from nomographs
and other procedures described in reference texts such as AP-42.
Additionally, in 40 CFR 60.113c(d)(2) we have clarified that the
provisions apply to affected storage vessels storing a mixture of
indeterminate composition or a mixture of unknown variable composition.
E. Recordkeeping and Electronic Reporting
The EPA is finalizing a requirement that owners and operators of
new, modified, or reconstructed VOL storage vessels subject to NSPS
subpart Kc maintain records of the results of required testing,
monitoring, and inspections. The EPA is finalizing a requirement that
owners and operators of VOL storage vessels subject to the current and
new NSPS at 40 CFR part 60, subparts Kb and Kc, submit electronic
copies of required performance test reports and the semiannual excess
emissions and continuous monitoring system performance and summary
reports, through the EPA's Central Data Exchange (CDX) using the
Compliance and Emissions Data Reporting Interface (CEDRI).
We are finalizing the recordkeeping and reporting requirements
similar to those proposed except that some of the revisions made to the
standards, testing, and monitoring provisions required revision of the
recordkeeping and reporting requirements for the final rule. The
revisions to the proposed recordkeeping and reporting requirements and
our rationale for making the revisions are summarized in this section.
As noted in section IV.D. of this preamble, we are
revising the recordkeeping and reporting requirements in 40 CFR
60.115c(d)(3)(v) and 60.116c(c)(8)(ii) to include the type of
monitoring conducted and to report information regarding all leaks
identified, including leaks identified using AVO methods.
As noted in section IV.B.5. of this preamble, we separated
PRD monitoring requirements to separately address devices on storage
vessels and devices on the closed vent system and included provisions
to monitor vacuum breaking devices on storage vessels. In reviewing
recordkeeping and reporting requirements related to these provisions,
we noted that we had proposed reporting requirements for PRDs, but we
failed to include recordkeeping requirements for PRDs. Therefore, we
are adding recordkeeping requirements at 40 CFR 60.115c(d)(3)(vii) for
PRDs or vacuum breaking devices on a storage vessel or closed vent
system that include: the device type; the monitoring device or system
used for the device; data from
[[Page 83313]]
the device or system indicating whether a pressure release occurred;
and the date, time, and duration of each pressure release, if
applicable. We are also adding reporting requirements at 40 CFR
60.116c(c)(12) for each pressure release that occurred as a result of a
vacuum breaking device that failed to close prior to the storage vessel
reaching atmospheric pressure. The added reporting requirements
include: identification of the vacuum breaking device; start date,
start time, and duration (in minutes) of the pressure release; and an
estimate of the mass quantity in pounds of VOL released. These
requirements mimic the pressure release reporting requirements proposed
(and being finalized) for PRDs, and these similar reporting
requirements are needed to document compliance with or deviations from
the requirements for vacuum breaking devices used for storage vessels
using a closed vent system routed to a control device.
As noted in section IV.B.5. of this preamble, we are
including alternative provisions that allow enclosed combustion devices
to comply with the flare operating and monitoring requirements. We
include minor revisions to the proposed recordkeeping and reporting
requirements commensurate with the provided alternative, to specify
which recordkeeping and reporting requirements apply to control systems
``other than flares or enclosed combustion devices electing to comply
with Sec. 60.112c(d)(5)'' and which recordkeeping and reporting
requirements apply to ``flares or enclosed combustion devices electing
to comply with Sec. 60.112c(d)(5).'' We are also adding a reporting
requirement for the initial notification at 40 CFR 60.116c(a)(6) that
includes a requirement to specify the type of control device used and
the compliance option selected, which, if an enclosed combustion device
is used, include whether the device is complying with a temperature
operating limit or is instead electing to comply with the flare
requirements in 40 CFR 60.112c(d)(5). This initial notification
requirement will be useful for EPA permitting and enforcement personnel
to clearly understand the compliance option being elected for the
enclosed combustion device.
For EFRs, as discussed in section IV.D. of this preamble,
we added requirements to visually inspect the roof fittings (such as
access hatches, gauge floats, gauge hatch/sample wells, rim vents, deck
drains, deck legs, vacuum breakers, pontoon covers, and guidepoles)
when gap measurements are conducted. We are adding to the list at 40
CFR 60.116c(c)(5)(vi)(A) to include reference to deviations of the
fitting controls outlined in 40 CFR 60.113c(b)(4)(iii)(A) through (D)
to allow reporting of fitting deviations identified during the gap
measurement inspections.
As discussed in the comment and response included in this
section of the preamble, we are revising what we proposed for the
timing of semiannual compliance reports to either cover fixed time
periods (from January 1 to June 30 or July 1 to December 31) or align
with established reporting dates based on 40 CFR parts 70 or 71 permit
requirements. The proposed schedule for semiannual reports appeared to
require separate semiannual reports for different affected storage
vessels at a facility depending on when the storage vessel became
affected under NSPS subpart Kc. Because facilities may have several
affected storage vessels under NSPS subpart Kc, having fixed reporting
periods simplifies the reporting requirements for these facilities.
Comment: Numerous commenters requested that the EPA revise NSPS
subpart Kc so that reporting requirements are consistent with other
reporting obligations and establish the same semiannual reporting
deadline for all VOL storage vessels. The commenters noted that, as
proposed, it appeared that each affected VOL storage vessel could have
a separate reporting schedule depending on when the sources became
affected sources under NSPS subpart Kc. The commenters recommended that
the EPA require the annual reports to cover activities in set time
periods (January 1 through June 30 or July 1 through December 31, as
applicable). One commenter also recommended that the EPA include an
alternative that would allow each affected facility subject to
permitting regulations pursuant to 40 CFR parts 70 or 71 to align the
semiannual reports with established dates for submitting semiannual
reports pursuant to 40 CFR 70.6(a)(3)(iii)(A) or 40 CFR
71.6(a)(3)(iii)(A).
Response: First, we never intended to have different semiannual
compliance report schedules for different storage vessels at a given
facility. We note that the reporting form template was designed to
allow reporting of all storage vessels at the facility in one
semiannual report. However, we agree that, because the affected
facility is each VOL storage vessel, the proposed requirements at 40
CFR 60.116c(d) could be interpreted to impose different reporting
schedules for different storage vessels if they become affected
facilities in different months. Several commenters suggested that the
semiannual reports cover fixed timeframes, specifically January through
June and July through December. This appears reasonable. One commenter
also suggested including reference to semiannual reports under 40 CFR
parts 70 or 71 in the event that the current semiannual reporting
period is different from January through June and July through
December. This also appears reasonable. Therefore, we are providing a
fixed timeframe for the semiannual reports (January through June and
July through December) and providing an alternative timeframe to
harmonize with other semiannual reports as scheduled under 40 CFR parts
70 or 71, if different from the fixed timeframe being finalized. We
clarify that the first semiannual compliance report is triggered by the
date on which the first storage vessel at the facility becomes an
affected facility subject to NSPS subpart Kc and would cover, for
example, April 15 through June 30 if the source becomes an affected
facility on April 15. As new storage vessels become affected facilities
under NSPS subpart Kc, the information for those storage vessels will
be added to the semiannual report. These semiannual reporting
requirements simplify the reporting requirements compared to the timing
proposed and allow alignment of the semiannual reports provided for
NSPS subpart Kc with other reporting requirements that may apply for
the facility.
F. Other Final Amendments
1. Editorial Corrections
We received a number of comments regarding editorial,
typographical, and cross-reference corrections that we agree with and
are finalizing. Additionally, we received comments recommending
clarification of requirement language to reduce misinterpretation.
After reviewing these comments, we are revising some language in the
final rule. We are revising references of ``a control'' to ``a control
device.'' Beyond these changes, the EPA made several revisions
throughout NSPS subpart Kc to improve clarity.
One commenter recommended that the EPA clarify in 40 CFR
60.113c(d)(1) that the requirement to determine MTVP is not a one-time
requirement, as implied by the word ``initial,'' but also applies to
non-anticipated tank service changes. We agree that if the VOL stored
in the storage vessel changes, the MTVP should be reassessed. We are
revising 40 CFR 60.113c(d)(1) to require that this determination be
made prior to the
[[Page 83314]]
initial filling of the storage vessel or to the refilling of the
storage vessel with a new VOL.
One commenter recommended that in 40 CFR 60.115c(d)(5)(i) and 40
CFR 60.116c(c)(10)(i)(A) the EPA should add ``or flare flame'' to any
occurrence of ``pilot flame'' consistent with the provisions in 40 CFR
60.112c(d)(5)(iv) and 40 CFR 60.113c(c)(1)(iv)(B). We are revising 40
CFR 60.115c(d)(5)(i) and 40 CFR 60.116c(c)(10)(i)(A) accordingly.
2. Definitions
We received several comments recommending the inclusion of
definitions that were not included in the proposal. Additionally, we
received comments recommending definition revisions. This section of
the preamble summarizes major comments received concerning definitions
and provides our responses to those comments.
Comment: Several commenters recommended that the EPA define the
term ``pressure relief device'' in NSPS subpart Kc and provided a
suggested definition:
Pressure relief device means a valve, rupture disk, or similar
device used only to release an unplanned, nonroutine discharge of
gas from process equipment in order to avoid safety hazards or
equipment damage. A pressure relief device discharge can result from
an operator error, a malfunction such as a power failure or
equipment failure, or other unexpected cause. Such devices include
conventional, spring-actuated relief valves, balanced bellows relief
valves, pilot-operated relief valves, rupture disks, and breaking,
buckling, or shearing pin devices. Devices that are actuated either
by a pressure of less than or equal to 2.5 pounds per square inch
gauge or by a vacuum are not pressure relief devices.
Response: We agree with the commenters and are including a
definition of ``pressure relief device'' in NSPS subpart Kc similar to
the commenters' suggestion. For storage vessels, we consider
``conservation vents'' to be PRDs. These conservation vents typically
have actuation pressure less than 2.5 psig. As such, the last sentence
in our final definition reflects a change from the last sentence in our
proposed definition to only exclude vacuum breaking devices from the
definition of ``pressure relief devices.'' We are also clarifying that,
if a device has both a pressure relief function and a vacuum breaking
function, such as a conservation vent, the portion of the conservation
vent that acts to relieve pressure is considered a PRD and the portion
of the conservation vent that acts to relieve vacuum is a vacuum
breaking device and not a PRD. We are also adding a definition of
``vacuum breaking device,'' which is specific to the fixed roof portion
of the storage vessel and a vacuum breaker which is a component of a
floating roof.
Comment: One commenter recommended that the EPA define the term
``pressure release.''
Response: We are adding a definition of ``pressure release'' to 40
CFR 60.111c. We are including in the definition of ``pressure release''
emissions of materials resulting from a vacuum breaking device failing
to close prior to the system reaching atmospheric pressure.
Comment: One commenter recommended that the EPA define the terms
``vapor balancing system,'' ``fuel gas,'' ``fuel gas system,'' and
``routed to a process or route to a process.''
Response: We determined that vapor balancing is not appropriate or
equivalent to the BSER identified for VOL storage vessels. As such, we
are not including a definition of ``vapor balancing system'' in NSPS
subpart Kc. We disagree with the commenter's request to define ``fuel
gas'' because the ``fuel gas system'' definition is sufficient. We are
finalizing definitions for ``fuel gas system'' and ``routed to a
process or route to a process'' in NSPS subpart Kc.
Comment: One commenter recommended that the EPA define
``degassing'' with language consistent with the Texas Commission on
Environmental Quality's (TCEQ) definition.
Response: The EPA agrees with the commenter to define
``degassing''; however, the TCEQ definition is insufficient as there
may be other reasons to empty and degas a storage vessel other than
cleaning. While we agree that cleaning may be a step in the process, we
expect degassing to occur for other reasons. We are finalizing a
definition for ``degassing'' in NSPS subpart Kc to clarify this point.
G. Effective Date and Compliance Dates
Pursuant to CAA section 111(b)(1)(B), the effective date of the
final rule requirements in subpart Kc will be the promulgation date.
Affected sources that commence construction, reconstruction, or
modification after October 4, 2023, must comply with all requirements
of subpart Kc no later than the effective date of the final rule or
upon startup, whichever is later. The EPA is finalizing amendments to
NSPS subpart Kb to include electronic submission requirements. Affected
NSPS subpart Kb sources that commence construction, reconstruction, or
modification after July 23, 1984, and before October 4, 2023, must
comply with the updated requirements to submit reports electronically
no later than the effective date of the final rule.
V. Summary of Cost, Environmental, and Economic Impacts
A. What are the air quality impacts?
The final provisions in NSPS subpart Kc reduce emissions of VOCs,
some of which may also be hazardous air pollutants (HAPs). The EPA
estimates that the final standards will reduce VOC emissions by 1,085
tons per year, which includes the impacts from new, modified, and
reconstructed storage vessels. More information regarding the air
quality impacts and emission reductions are included in the memorandum
Control Options for Storage Vessels (Docket ID No. EPA-HQ-OAR-2023-
0358-0002).
B. What are the cost impacts?
This final action will cost (in 2022 dollars) approximately $21.1
million in total capital cost and result in a total annualized cost of
$5.38 million per year (including product recovery) based on our
analysis of the final actions in NSPS subpart Kc. More information
about the estimated cost of the final actions can be found in the
memorandum Control Options for Storage Vessels (Docket ID No. EPA-HQ-
OAR-2023-0358-0002).
C. What are the economic impacts?
For economic impact analyses (EIA) of rules that directly affect a
single industry or a few industries, the EPA often prepares a partial
equilibrium analysis. In this type of economic analysis, the focus of
the effort is on estimating impacts on a single affected industry or
several affected industries, and all impacts of this rule on industries
outside of those affected are assumed to be zero or so inconsequential
as to not be considered in the analysis. If the compliance costs, which
are key inputs to an EIA, are quite insignificant, then the impact
analysis could consist of a calculation of annual (or annualized) costs
as a percentage of sales for affected companies. This latter type of
analysis is called a screening analysis and is applied when a partial
equilibrium or more complex EIA approach is deemed not necessary given
the expected size of the impacts.
The net present value of the estimated cost impacts of NSPS subpart
Kc is $19.4 million, discounted at a 3 percent rate over a 5-year
analytic timeframe from 2024 to 2028 in 2022 dollars. Using a 7 percent
discount rate, the net present value of the estimated cost impacts is
$17.3 million. The equivalent annualized value in 2022 dollars is a
[[Page 83315]]
cost of approximately $4.1 million using a discount rate of either 3 or
7 percent.
Storage vessels in NSPS subpart Kb are most closely associated with
the petroleum and coal products industry (NAICS 324000), the chemical
products industry (NAICS 325000), and the petroleum bulk stations and
terminals industry (NAICS 424710). While we do not know the precise
distribution of new and modified storage vessels across the affected
sectors, we know that there are affected storage vessels in the sectors
mentioned earlier in this preamble. These sectors contribute gross
value added, ranging from $200 to $501 billion per sector, to the
national economy. In comparison, the requirements in NSPS subpart Kc
have estimated total costs of $21 million. The total cost is the total
incurred collectively amongst numerous sectors, and each of the sectors
examined has sales of at least $200 billion. Thus, the compliance costs
of this action are insignificant relative to the scale for the sectors
affected, and it is appropriate to evaluate the economic impacts by
conducting a screening analysis comparing the costs to entity-level
sales.
Given the results of the analysis, these economic impacts are
relatively low for affected industries and entities impacted by this
final rule, and there will not be substantial impacts on the markets
for affected products. The costs of the final rule are not expected to
result in a significant market impact, regardless of whether they are
passed on to the purchaser or absorbed by the firms. We also expect
minimal impacts on employment.
D. What are the benefits?
The final provisions in NSPS subpart Kc would reduce emissions of
VOCs, some of which may also be HAPs. Because VOCs react in the
atmosphere to produce ozone, these standards would help to reduce
atmospheric ozone concentrations and reduce health effects associated
with high levels of ozone. Furthermore, the final requirements to
submit reports and test results electronically would improve
monitoring, compliance, and implementation of the rule.
E. What analysis of environmental justice did we conduct?
For purposes of analyzing regulatory impacts, under Executive Order
12898, Federal Actions to Address Environmental Justice in Minority
Populations and Low-Income Populations, the EPA relies upon its June
2016 ``Technical Guidance for Assessing Environmental Justice in
Regulatory Analysis,'' which provides recommendations that encourage
analysts to conduct the highest quality analysis feasible, recognizing
that data limitations, time, resource constraints, and analytical
challenges will vary by media and circumstance. The Technical Guidance
states that a regulatory action may involve potential EJ concerns if it
could: (1) create new disproportionate impacts on communities with EJ
concerns; (2) exacerbate existing disproportionate impacts on
communities with EJ concerns; or (3) present opportunities to address
existing disproportionate impacts on communities with EJ concerns
through this action under development.
The EPA's EJ technical guidance states that ``[t]he analysis of
potential EJ concerns for regulatory actions should address three
questions: (A) Are there potential EJ concerns associated with
environmental stressors affected by the regulatory action for
population groups of concern in the baseline? (B) Are there potential
EJ concerns associated with environmental stressors affected by the
regulatory action for population groups of concern for the regulatory
option(s) under consideration? (C) For the regulatory option(s) under
consideration, are potential EJ concerns created or mitigated compared
to the baseline?'' \9\
---------------------------------------------------------------------------
\9\ Technical Guidance for Assessing Environmental Justice in
Regulatory Analysis, U.S. EPA, June 2016. Quote is from Section 3--
Key Analytic Considerations, page 11. https://www.epa.gov/environmentaljustice/technical-guidance-assessing-environmental-justice-regulatory-analysis.
---------------------------------------------------------------------------
Because this action finalizes standards of performance for new,
modified, and reconstructed sources that commence construction after
October 4, 2023, the locations of the construction of new VOL storage
vessels are not known. In addition, it is not known which of the
existing facilities will be modified or reconstructed in the future.
Therefore, we are unable to quantitatively estimate the potential
environmental justice impact of NSPS subpart Kc. Over the next 5 years,
the EPA estimates that 1,440 new tanks and 30 modified tanks would be
subject to NSPS subpart Kc. We estimate that there are more than 10,000
existing VOL storage vessels, but we do not have a list of specific
storage vessels and their locations. Therefore, we cannot perform a
proximity demographic analysis of populations near existing units as a
proxy for units that may be modified or reconstructed and become
subject to NSPS subpart Kc. Finally, because we based the analysis of
the impacts and emission reductions on model plants, we cannot
ascertain specifically how the potential benefits of this rule would be
distributed across the population. Thus, we are limited in our ability
to estimate the potential EJ impacts of this rule.
The EPA expects that NSPS subpart Kc will ensure compliance via
revised vapor pressure applicability thresholds, stricter seal
requirements on IFR tanks, equivalent control requirements for EFRs,
and strengthened closed vent system standards for vessels routed to a
control device, fuel gas system, or process. This action finalizes
standards of performance that apply at all times (including periods of
SSM) and achieve an average 98 percent control efficiency. The rule
will also increase data transparency through electronic reporting.
Therefore, effects of emissions on populations in proximity to any
future affected sources, including in communities potentially
overburdened by pollution, which are often communities with EJ
concerns, will be minimized due to the compliance with the standards of
performance being finalized in this action.
VI. Statutory and Executive Order Reviews
Additional information about these statutes and Executive orders
can be found at https://www.epa.gov/laws-regulations/laws-and-executive-orders.
A. Executive Order 12866: Regulatory Planning and Review and Executive
Order 14094: Modernizing Regulatory Review
This action is not a significant regulatory action as defined in
Executive Order 12866, as amended by Executive Order 14094, and was
therefore not subject to a requirement for Executive Order 12866
review.
B. Paperwork Reduction Act (PRA)
The information collection activities in this rule have been
submitted for approval to OMB under the PRA. The Information Collection
Request (ICR) document that the EPA prepared has been assigned EPA ICR
number 2791.01. You can find a copy of the ICR in the docket for this
rule, and it is briefly summarized here. The information collection
requirements are not enforceable until the Office of Management and
Budget (OMB) approves them.
The EPA is finalizing requirements for storage vessels, including
periodic inspections based on the type of storage vessel. This
information will be collected to assure compliance with NSPS subpart
Kc.
[[Page 83316]]
Respondents/affected entities: Owners or operators of VOL storage
vessels.
Respondent's obligation to respond: Mandatory (40 CFR part 60,
subpart Kc).
Estimated number of respondents: 588.
Frequency of response: Initially and semiannually.
Total estimated burden: 16,394 hours (per year). Burden is defined
at 5 CFR 1320.3(b).
Total estimated cost: $2,009,357 (per year), includes $528,240 in
annualized capital and no operation or maintenance costs.
An agency may not conduct or sponsor, and a person is not required
to respond to, a collection of information unless it displays a
currently valid OMB control number. The OMB control numbers for the
EPA's regulations in 40 CFR are listed in 40 CFR part 9. When OMB
approves this ICR, the Agency will announce that approval in the
Federal Register and publish a technical amendment to 40 CFR part 9 to
display the OMB control number for the approved information collection
activities contained in this final rule.
C. Regulatory Flexibility Act (RFA)
I certify that this action will not have a significant economic
impact on a substantial number of small entities under the RFA. The
small entities subject to the requirements of this action are small
businesses and small governmental jurisdictions that own or operate VOL
storage vessels. The Agency has determined that small entities may
experience an impact of likely below 1 percent relative to sales for
any affected small entity, and an even larger margin before it would
approach a 1 percent impact for a substantial number of small entities.
Details of this analysis are presented in the memorandum Economic
Impact Analysis for the New Source Performance Standards (NSPS) for the
Volatile Organic Liquid Storage Vessels (Tanks) included in the docket.
D. Unfunded Mandates Reform Act (UMRA)
This action does not contain an unfunded mandate of $100 million or
more as described in UMRA, 2 U.S.C. 1531-1538, and does not
significantly or uniquely affect small governments. The action imposes
no enforceable duty on any State, local, or Tribal governments or the
private sector.
E. Executive Order 13132: Federalism
This action does not have federalism implications. It will not have
substantial direct effects on the States, on the relationship between
the national government and the States, or on the distribution of power
and responsibilities among the various levels of government.
F. Executive Order 13175: Consultation and Coordination With Indian
Tribal Governments
This action does have Tribal implications as specified in Executive
Order 13175. NSPS subpart Kb includes provisions for storage vessels
that already have impacts on Tribal governments that have storage
vessels with at least 20,000 gallons of capacity and that meet the
vapor pressure thresholds for general rule applicability or control
applicability. NSPS subpart Kc includes updates to the VOC standards
and monitoring requirements for storage vessels that meet the revised
vapor pressure thresholds for control. Additionally, basic requirements
for determining a VOL's MTVP, recordkeeping, and good air pollution
control practices are being finalized for all storage vessels greater
than 20,000 gallons that only store VOLs with an MTVP greater than or
equal to 0.25 psia. These changes will only impact storage vessels that
are constructed, modified, or reconstructed after the proposal date.
Consistent with the EPA Policy on Consultation and Coordination
with Indian Tribes, the EPA offered government-to-government
consultation with Tribes by sending a letter dated October 3, 2023,
inviting all federally recognized Tribes to request a consultation. The
EPA received one request for consultation. On November 8, 2023, the EPA
met with the Tribe for the purposes of discussing NSPS subpart Kc and
other issues but were unable to conduct consultation on this specific
rulemaking.
G. Executive Order 13045: Protection of Children From Environmental
Health Risks and Safety Risks
Executive Order 13045 directs Federal agencies to include an
evaluation of the health and safety effects of the planned regulation
on children in Federal health and safety standards and explain why the
regulation is preferable to potentially effective and reasonably
feasible alternatives. This action is not subject to Executive Order
13045 because it is not economically significant as defined in
Executive Order 12866 and because the EPA does not believe the
environmental health or safety risks addressed by this action present a
disproportionate risk to children. The final rule will reduce emissions
of VOCs, some of which may also be HAPs. These standards will help to
reduce atmospheric ozone concentrations and reduce health effects
associated with high levels of ozone and are projected to improve
overall health, including that of children.
H. Executive Order 13211: Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use
This action is not subject to Executive Order 13211, because it is
not a significant regulatory action under Executive Order 12866.
I. National Technology Transfer and Advancement Act (NTTAA) and 1 CFR
Part 51
This action for NSPS subparts Kb and Kc involves technical
standards. Therefore, the EPA conducted a search to identify
potentially applicable voluntary consensus standards. However, the
Agency identified no such standards. Searches were conducted for EPA
Methods 1, 1A, 2, 2A, 2C, 2D, 3A, 3B, 3C, 4, 6, 10, 15, 16, 16A, 18,
21, 22, and 25A of 40 CFR part 60, appendix A. The EPA has decided to
use EPA Methods 21, 22, and 25A. Additional information for the
voluntary consensus standard search and determinations can be found in
the memorandum titled, Voluntary Consensus Standard Results for Review
of Standards of Performance for Volatile Organic Liquid Storage Vessels
(Including Petroleum Liquid Storage Vessels). All potential standards
were reviewed to determine the practicality of the voluntary consensus
standards for this rule. Although there were no applicable voluntary
consensus standards identified, we are finalizing the proposal to amend
40 CFR 60.17 to incorporate by reference two ASTM methods as discussed
in section III.M. of the proposal preamble (88 FR 68550; October 4,
2023). These include the following:
ASTM D6377-20, Standard Test Method for Determination of
Vapor Pressure of Crude Oil: VPCRx (Expansion Method). The method is an
automated device method for measuring vapor pressures for crude oils
samples between 29 kPa and 180 kPa at 37.8 [deg]C. The method is
suitable for testing with a 4:1 vapor-liquid ratio.
ASTM D6378-22, Standard Test Method for Determination of
Vapor Pressure (VPX) of Petroleum Products, Hydrocarbons, and
Hydrocarbon-Oxygenate Mixtures (Triple Expansion Method). The method is
an automated device method for measuring vapor pressures between 7 kPa
and 150 kPa at 37.8 [deg]C for tested samples with boiling points at 0
[deg]C. The method is suitable for volatile organic liquids,
[[Page 83317]]
hydrocarbons and liquid petroleum products sampled at a 4:1 vapor-
liquid ratio.
The ASTM standards are available from ASTM, International, 100 Barr
Harbor Drive, Post Office Box C700, West Conshohocken, PA 19428-2959.
See https://www.astm.org.
J. Executive Order 12898: Federal Actions To Address Environmental
Justice in Minority Populations and Low-Income Populations and
Executive Order 14096: Revitalizing Our Nation's Commitment to
Environmental Justice for All
The EPA believes that it is not practicable to assess whether the
human health or environmental conditions that exist prior to this
action result in disproportionate and adverse effects on communities
with EJ concerns. Over the next 5 years, the EPA estimates that 1,440
new tanks and 30 modified tanks will be subject to NSPS subpart Kc.
However, the locations of any new VOL storage vessels that would be
subject to NSPS subpart Kc are not known. Furthermore, there is
insufficient data available regarding the locations of existing VOL
storage vessels. The EPA estimates that there are more than 10,000
existing storage vessels subject to NSPS subpart Kb, but we do not have
a list of specific storage vessels and their locations. Therefore, we
cannot perform a proximity demographic analysis of populations near
existing storage vessels as a proxy for storage vessels that may be
modified or reconstructed and become subject to NSPS subpart Kc.
Finally, because we based the analysis of the impacts and emission
reductions on model plants, we cannot ascertain specifically how the
potential benefits of this rule would be distributed across the
population. Thus, we are limited in our ability to estimate the
potential EJ impacts of this rule.
The information supporting this Executive Order review is contained
in section V.E. of this document. All pertinent supporting documents
such as the technical memorandum, Control Options for Storage Vessels
(Docket ID No. EPA-HQ-OAR-2023-0358-0002), which discusses the costs
and environmental impacts of the regulatory options considered, is in
the docket.
K. Congressional Review Act (CRA)
This action is subject to the CRA, and the EPA will submit a rule
report to each House of the Congress and to the Comptroller General of
the United States. This action is not a ``major rule'' as defined by 5
U.S.C. 804(2).
List of Subjects in 40 CFR Part 60
Environmental protection, Administrative practice and procedures,
Air pollution control, Incorporation by reference, Reporting and
recordkeeping requirements.
Michael S. Regan,
Administrator.
For the reasons set forth in the preamble, the Environmental
Protection Agency is amending part 60 of title 40, chapter I, of the
Code of Federal Regulations as follows:
PART 60--STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES
0
1. The authority citation for part 60 continues to read as follows:
Authority: 42 U.S.C. 7401 et seq.
Subpart A--General Provisions
0
2. Amend Sec. 60.17 by:
0
a. Redesignating paragraphs (h)(198) through (233) as (h)(200) through
(235); and
0
b. Adding paragraphs (h)(198) and (199).
The additions read as follows:
Sec. 60.17 Incorporations by reference.
* * * * *
(h) * * *
(198) ASTM D6377-20, Standard Test Method for Determination of
Vapor Pressure of Crude Oil: VPCRx (Expansion Method),
(Approved June 1, 2020); IBR approved for Sec. 60.113c.
(199) ASTM-D6378-22, Standard Test Method for Determination of
Vapor Pressure (VPX) of Petroleum Products, Hydrocarbons, and
Hydrocarbon-Oxygenate Mixtures (Triple Expansion Method), (Approved
July 1, 2022); IBR approved for Sec. 60.113c.
* * * * *
Subpart Kb--Standards of Performance for Volatile Organic Liquid
Storage Vessels (Including Petroleum Liquid Storage Vessels) for
Which Construction, Reconstruction, or Modification Commenced After
July 23, 1984, and On or Before October 4, 2023
0
3. Revise the heading of subpart Kb to read as set out above.
0
4. Amend Sec. 60.110b by revising paragraph (a) to read as follows:
Sec. 60.110b Applicability and designation of affected facility.
(a) Except as provided in paragraph (b) of this section, the
affected facility to which this subpart applies is each storage vessel
with a capacity greater than or equal to 75 cubic meters (m\3\) that is
used to store volatile organic liquids (VOL) for which construction,
reconstruction, or modification is commenced after July 23, 1984, and
on or before October 4, 2023.
* * * * *
0
5. Amend Sec. 60.115b by:
0
a. Revising paragraphs (a), (b), and (d); and
0
b. Adding paragraphs (e), (f), and (g).
The revisions and additions read as follows:
Sec. 60.115b Reporting and recordkeeping requirements.
* * * * *
(a) After installing control equipment in accordance with Sec.
60.112b(a)(1) (fixed roof and internal floating roof), the owner or
operator shall meet the following requirements.
(1) Furnish the Administrator with a report that describes the
control equipment and certifies that the control equipment meets the
specifications of Sec. 60.112b(a)(1) and Sec. 60.113b(a)(1). Prior to
October 15, 2024, this report shall be an attachment to the
notification required by Sec. 60.7(a)(3). Beginning October 15, 2024,
the owner or operator must submit all subsequent reports in PDF format
following the procedures specified in paragraph (e) of this section.
(2) Keep a record of each inspection performed as required by Sec.
60.113b(a)(1), (a)(2), (a)(3), and (a)(4). Each record shall identify
the storage vessel on which the inspection was performed and shall
contain the date the vessel was inspected and the observed condition of
each component of the control equipment (seals, internal floating roof,
and fittings).
(3) If any of the conditions described in Sec. 60.113b(a)(2) are
detected during the annual visual inspection required by Sec.
60.113b(a)(2), a report shall be furnished to the Administrator within
30 days of the inspection. Each report shall identify the storage
vessel, the nature of the defects, and the date the storage vessel was
emptied or the nature of and date the repair was made. Beginning
October 15, 2024, all subsequent reports must be submitted in PDF
format following the procedures in paragraph (e) of this section.
(4) After each inspection required by Sec. 60.113b(a)(3) that
finds holes or tears in the seal or seal fabric, or defects in the
internal floating roof, or other control equipment defects listed in
Sec. 60.113b(a)(3)(ii), a report shall be furnished to the
Administrator within 30 days of the inspection. The report shall
identify the storage vessel and the
[[Page 83318]]
reason it did not meet the specifications of Sec. 60.112b(a)(1) or
Sec. 60.113b(a)(3) and list each repair made. Beginning October 15,
2024, all subsequent reports must be submitted in PDF format following
the procedures in paragraph (e) of this section.
(b) After installing control equipment in accordance with Sec.
60.112b(a)(2) (external floating roof), the owner or operator shall
meet the following requirements.
(1) Furnish the Administrator with a report that describes the
control equipment and certifies that the control equipment meets the
specifications of Sec. 60.112b(a)(2) and Sec. 60.113b(b)(2), (b)(3),
and (b)(4). Prior to October 15, 2024, this report shall be an
attachment to the notification required by Sec. 60.7(a)(3). Beginning
October 15, 2024, the owner or operator must submit all subsequent
reports in PDF format following the procedures specified in paragraph
(e) of this section.
(2) Within 60 days of performing the seal gap measurements required
by Sec. 60.113b(b)(1), furnish the Administrator with a report that
contains the following information. Beginning October 15, 2024, all
subsequent reports must be submitted in PDF format following the
procedures in paragraph (e) of this section.
(i) The date of measurement;
(ii) The raw data obtained in the measurement; and
(iii) The calculations described in Sec. 60.113b(b)(2) and (b)(3).
(3) Keep a record of each gap measurement performed as required by
Sec. 60.113b(b). Each record shall identify the storage vessel in
which the measurement was performed and shall contain:
(i) The date of measurement;
(ii) The raw data obtained in the measurement; and
(iii) The calculations described in Sec. 60.113b(b)(2) and (b)(3).
(4) After each seal gap measurement that detects gaps exceeding the
limitations specified by Sec. 60.113b(b)(4), submit a report to the
Administrator within 30 days of the inspection. The report will
identify the vessel and contain the information specified in paragraph
(b)(2) of this section and the date the vessel was emptied or the
repairs made and date of repair. Beginning October 15, 2024, all
subsequent reports must be submitted in PDF format following the
procedures in paragraph (e) of this section.
* * * * *
(d) After installing a closed vent system and flare to comply with
Sec. 60.112b, the owner or operator shall meet the following
requirements.
(1) A report containing the measurements required by Sec.
60.18(f)(1) through (6) shall be furnished to the Administrator as
required by Sec. 60.8 of the General Provisions. This report shall be
submitted within 6 months of the initial start-up date. Beginning
October 15, 2024, all subsequent reports must be submitted in PDF
format following the procedures in paragraph (e) of this section.
(2) Records shall be kept of all periods of operation during which
the flare pilot flame is absent.
(3) Semiannual reports of all periods recorded under Sec.
60.115b(d)(2) in which the pilot flame was absent shall be furnished to
the Administrator. Beginning October 15, 2024, all subsequent reports
must be submitted in PDF format following the procedures specified in
paragraph (e) of this section.
(e) An owner or operator required to submit notifications or
reports following the procedures specified in this paragraph (e) must
submit notifications or reports to the EPA via the Compliance and
Emissions Data Reporting Interface (CEDRI), which can be accessed
through the EPA's Central Data Exchange (CDX) (https://cdx.epa.gov/).
The EPA will make all the information submitted through CEDRI available
to the public without further notice to the owner or operator. Do not
use CEDRI to submit information the owner or operator claims as CBI.
Although the EPA does not expect persons to assert a claim of CBI, if
an owner or operator wishes to assert a CBI claim for some of the
information in the report or notification, the owner or operator must
submit a complete file in the format specified in this subpart,
including information claimed to be CBI, to the EPA following the
procedures in paragraphs (e)(1) and (2) of this section. Clearly mark
the part or all of the information claimed to be CBI. Information not
marked as CBI may be authorized for public release without prior
notice. Information marked as CBI will not be disclosed except in
accordance with procedures set forth in 40 CFR part 2. All CBI claims
must be asserted at the time of submission. Anything submitted using
CEDRI cannot later be claimed CBI. Furthermore, under CAA section
114(c), emissions data is not entitled to confidential treatment, and
the EPA is required to make emissions data available to the public.
Thus, emissions data will not be protected as CBI and will be made
publicly available. The owner or operator must submit the same file
submitted to the CBI office with the CBI omitted to the EPA via the
EPA's CDX as described earlier in this paragraph (e).
(1) The preferred method to receive CBI is for it to be transmitted
electronically using email attachments, File Transfer Protocol, or
other online file sharing services. Electronic submissions must be
transmitted directly to the OAQPS CBI Office at the email address
[email protected], and as described above, should include clear CBI
markings, and be flagged to the attention of the NSPS Kb Lead. Owners
and operators who do not have their own file sharing service and who
require assistance with submitting large electronic files that exceed
the file size limit for email attachments should email [email protected]
to request a file transfer link.
(2) If an owner or operator cannot transmit the file
electronically, the owner or operator may send CBI information through
the postal service to the following address: U.S. EPA, Attn: OAQPS
Document Control Officer and NSPS Kb Lead, Mail Drop: C404-02, 109 T.W.
Alexander, P.O. Box 12055, RTP, NC 27711. The mailed CBI material
should be double wrapped and clearly marked. Any CBI markings should
not show through the outer envelope.
(f) Owners and operators required to electronically submit
notifications or reports through CEDRI in the EPA's CDX may assert a
claim of EPA system outage for failure to timely comply with the
electronic submittal requirement. To assert a claim of EPA system
outage, owners and operators must meet the requirements outlined in
paragraphs (f)(1) through (7) of this section.
(1) The owner or operator must have been or will be precluded from
accessing CEDRI and submitting a required report within the time
prescribed due to an outage of either the EPA's CEDRI or CDX systems.
(2) The outage must have occurred within the period of time
beginning 5 business days prior to the date that the submission is due.
(3) The outage may be planned or unplanned.
(4) The owner or operator must submit notification to the
Administrator in writing as soon as possible following the date the
owner or operator first knew, or through due diligence should have
known, that the event may cause or has caused a delay in reporting.
(5) The owner or operator must provide to the Administrator a
written description identifying:
(i) The date(s) and time(s) when CDX or CEDRI was accessed and the
system was unavailable;
[[Page 83319]]
(ii) A rationale for attributing the delay in reporting beyond the
regulatory deadline to EPA system outage;
(iii) A description of measures taken or to be taken to minimize
the delay in reporting; and
(iv) The date by which the owner or operator proposes to report, or
if the owner or operator has already met the reporting requirement at
the time of the notification, the date the report was submitted.
(6) The decision to accept the claim of EPA system outage and allow
an extension to the reporting deadline is solely within the discretion
of the Administrator.
(7) In any circumstance, the report must be submitted
electronically as soon as possible after the outage is resolved.
(g) Owners and operators required to electronically submit
notifications or reports through CEDRI in the EPA's CDX may assert a
claim of force majeure for failure to timely comply with the electronic
submittal requirement. To assert a claim of force majeure, you must
meet the requirements outlined in paragraphs (g)(1) through (5) of this
section.
(1) An owner or operator may submit a claim if a force majeure
event is about to occur, occurs, or has occurred or there are lingering
effects from such an event within the period of time beginning 5
business days prior to the date the submission is due. For the purposes
of this section, a force majeure event is defined as an event that will
be or has been caused by circumstances beyond the control of the
affected facility, its contractors, or any entity controlled by the
affected facility that prevents the owner or operator from complying
with the requirement to submit a report electronically within the time
period prescribed. Examples of such events are acts of nature (e.g.,
hurricanes, earthquakes, or floods), acts of war or terrorism, or
equipment failure or safety hazard beyond the control of the affected
facility (e.g., large scale power outage).
(2) The owner or operator must submit notification to the
Administrator in writing as soon as possible following the date the
owner or operator first knew, or through due diligence should have
known, that the event may cause or has caused a delay in reporting.
(3) The owner or operator must provide to the Administrator:
(i) A written description of the force majeure event;
(ii) A rationale for attributing the delay in reporting beyond the
regulatory deadline to the force majeure event;
(iii) A description of measures taken or to be taken to minimize
the delay in reporting; and
(iv) The date by which the owner or operator proposes to report, or
if the owner or operator has already met the reporting requirement at
the time of the notification, the date the report was submitted.
(4) The decision to accept the claim of force majeure and allow an
extension to the reporting deadline is solely within the discretion of
the Administrator.
(5) In any circumstance, the reporting must occur as soon as
possible after the force majeure event occurs.
0
6. Amend Sec. 60.116b by revising paragraph (d) to read as follows:
Sec. 60.116b Monitoring of operations.
* * * * *
(d) Except as provided in paragraph (g) of this section, the owner
or operator of each storage vessel either with a design capacity
greater than or equal to 151 m\3\ storing a liquid with a maximum true
vapor pressure that is normally less than 5.2 kPa or with a design
capacity greater than or equal to 75 m\3\ but less than 151 m\3\
storing a liquid with a maximum true vapor pressure that is normally
less than 27.6 kPa shall notify the Administrator within 30 days when
the maximum true vapor pressure of the liquid exceeds the respective
maximum true vapor pressure values for each volume range. Beginning
October 15, 2024, all subsequent notifications must be submitted in PDF
format following the procedures specified in Sec. 60.115b(e).
* * * * *
0
7. Amend Sec. 60.117b by revising paragraph (b) to read as follows:
Sec. 60.117b Delegation of authority.
* * * * *
(b) Authorities which will not be delegated to States: Sec. Sec.
60.111b(f)(4), 60.114b, 60.116b(e)(3)(iii), 60.116b(e)(3)(iv), and
60.116b(f)(2)(iii), and approval of an alternative to any electronic
reporting to the EPA required by this subpart.
0
8. Add subpart Kc consisting of Sec. Sec. 60.110c through 60.117c to
part 60 to read as follows:
Subpart Kc--Standards of Performance for Volatile Organic Liquid
Storage Vessels (Including Petroleum Liquid Storage Vessels) for
Which Construction, Reconstruction, or Modification Commenced After
October 4, 2023
Sec.
60.110c Applicability and designation of affected facility.
60.111c Definitions.
60.112c Standard for volatile organic compounds (VOC).
60.113c Testing, monitoring, and inspection procedures.
60.114c Alternative means of emission limitation.
60.115c Recordkeeping requirements.
60.116c Reporting requirements.
60.117c Delegation of authority.
Sec. 60.110c Applicability and designation of affected facility.
(a) Except as provided in paragraph (b) of this section, the
affected facility to which this subpart applies is each storage vessel
with a capacity greater than or equal to 20,000 gallons (gal) (75.7
cubic meters (m\3\)) that is used to store volatile organic liquids
(VOL) for which construction, reconstruction, or modification is
commenced after October 4, 2023.
(b) This subpart does not apply to the following:
(1) Vessels at coke oven by-product plants;
(2) Pressure vessels designed to operate in excess of 29.7 pounds
per square inch absolute (psia) (204.9 kilopascals (kPa) absolute) and
without emissions to the atmosphere;
(3) Vessels permanently attached to mobile vehicles such as trucks,
railcars, barges, or ships;
(4) Vessels with a design capacity less than or equal to 420,000
gal (1,589.874 m\3\) used for petroleum or condensate stored,
processed, or treated prior to custody transfer;
(5) Vessels located at bulk gasoline plants as defined in 40 CFR
63.11100;
(6) Vessels located at gasoline service stations;
(7) Vessels used to store beverage alcohol; or
(8) Vessels that only store VOL with a maximum true vapor pressure
less than 0.25 psia (1.7 kPa absolute).
(c) Storage vessels that are affected facilities according to
paragraph (a) of this section for which construction or reconstruction
commenced after October 4, 2023 are subject to the standards in Sec.
60.112c and the corresponding requirements in Sec. Sec. 60.113c
through 60.116c as new sources any time they meet the specifications in
either paragraph (c)(1) or (2) of this section, regardless of whether
they initially contained VOL with a maximum true vapor pressure below
the applicable threshold in paragraph (c)(1) or (2) of this section.
(1) Storage vessels with a capacity greater than or equal to 40,000
gal (151 m\3\) containing a VOL that, as stored, has a maximum true
vapor pressure equal to or greater than 0.5 psia (3.4 kPa).
(2) Storage vessels with a capacity greater than or equal to 20,000
gal (75.7
[[Page 83320]]
m\3\) but less than 40,000 gal (151 m\3\) containing a VOL that, as
stored, has a maximum true vapor pressure equal to or greater than 1.5
psia (10.3 kPa).
(d) Storage vessels that are affected facilities according to
paragraph (a) of this section for which construction or reconstruction
commenced on or before October 4, 2023, (``existing storage vessels'')
and are modified after October 4, 2023, are subject to the standards in
Sec. 60.112c and the corresponding requirements in Sec. Sec. 60.113c
through 60.116c as modified sources any time they meet the
specifications in either paragraph (d)(1) or (2) of this section.
(1) For an existing storage vessel with a capacity greater than or
equal to 40,000 gal (151 m\3\), containing a VOL that, as stored, has a
maximum true vapor pressure equal to or greater than 0.5 psia (3.4
kPa).
(2) For an existing storage vessel with a capacity greater than or
equal to 20,000 gal (75.7 m\3\) but less than 40,000 gal (151 m\3\),
containing a VOL that, as stored, has a maximum true vapor pressure
equal to or greater than 1.5 psia (10.3 kPa).
(e) For the purposes of this subpart,
(1) The phrase ``change in the method of operation of, an existing
facility which increases the amount of any air pollutant'' in the
definition of modification in Sec. 60.2 or ``operational change to an
existing facility which results in an increase in the emission rate to
the atmosphere of any pollutant to which a standard applies'' in Sec.
60.14(a) means a change in operation occurs if the storage vessel is
used to store a VOL that has a greater maximum true vapor pressure than
all VOL historically stored or permitted; and
(2) The exemption in Sec. 60.14(e)(4) regarding alternative fuel
or raw material does not apply to storage vessels.
(f) Storage vessels that are affected facilities according to
paragraph (a) of this section and do not meet the criteria in either
paragraph (c)(1), (c)(2), (d)(1), or (d)(2) of this section are subject
to the requirements in Sec. 60.113c(d), if applicable, and Sec.
60.115c(b).
(g) All standards including emission limitations shall apply at all
times, including periods of startup, shutdown and malfunction. As
provided in Sec. 60.11(f), this paragraph (g) supersedes the
exemptions for periods of startup, shutdown, and malfunction in subpart
A of this part.
(h) Owners or operators may choose to comply with the provisions of
this subpart to demonstrate compliance with subparts K, Ka, and Kb of
this part. Compliance with the provisions of this subpart, including
all control requirements, recordkeeping, and reporting requirements,
will constitute compliance with the applicable storage vessel
provisions in subparts K, Ka, and Kb.
(i) Owners or operators may choose to comply with this subpart to
demonstrate compliance with 40 CFR part 63, subpart WW for storage
vessels equipped with an internal or external floating roof that is
subject to this subpart and 40 CFR part 63, subpart WW. Compliance with
this subpart, including all floating roof requirements, recordkeeping,
and reporting requirements, will constitute compliance with the
applicable storage vessel provisions in 40 CFR part 63, subpart WW.
Sec. 60.111c Definitions.
Terms used in this subpart are defined in the Act, in subpart A of
this part, or in this section as follows:
Access hatch means an opening in the roof with a vertical well and
a cover attached to it. Access hatch provides passage for workers and
materials through the roof for construction or maintenance.
Condensate means hydrocarbon liquid separated from natural gas that
condenses due to changes in the temperature or pressure, or both, and
remains liquid at standard conditions.
Closed vent system means a system that is not open to the
atmosphere and is composed of piping, ductwork, connections, and, if
necessary, flow inducing devices that transport gas or vapor from an
emission point to a control device. Closed vent system does not include
the vapor collection system that is part of any tank truck or railcar.
Custody transfer means the transfer of produced petroleum and/or
condensate, after processing and/or treatment in the producing
operations, from storage vessels or automatic transfer facilities to
pipelines or any other forms of transportation.
Degassing means the process of removing VOL vapors from a storage
vessel during, or in preparation of, cleaning or when taking the
storage vessel out of service for inspection, repair, or other reason.
Enclosed combustion device means a thermal combustion device used
to mix and ignite fuel, air pollutants, and air to provide a flame to
heat and oxidize air pollutants and that emits the oxidized pollutants
through a conveyance suitable to conduct a performance test. An
enclosed combustion device may have recovery heat to preheat combustion
air, but its primary purpose is for emission control and not to produce
useful heat. Enclosed combustion devices include, but are not limited
to, thermal oxidizers and incinerators. For the purpose of this
subpart, process heaters and boilers are not enclosed combustion
devices.
External floating roof means a pontoon-type or double-deck type
cover that rests on the liquid surface in a storage vessel without a
fixed roof.
Fill means the introduction of VOL into a storage vessel but not
necessarily to complete capacity.
Flare means a thermal combustion device using an open or shrouded
flame (without full enclosure) such that the pollutants are not emitted
through a conveyance suitable to conduct a performance test.
Fuel gas system means the offsite and onsite piping and control
system that gathers gaseous stream(s) generated by onsite operations,
may blend them with other sources of gas, and transports the gaseous
stream for use as fuel gas in combustion devices, or in- process
combustion equipment such as furnaces and gas turbines, either singly
or in combination.
Gasoline service station means any site where gasoline is dispensed
to motor vehicle fuel tanks from stationary storage vessels.
Gauge float means a device that is used to indicate the level of
liquid within the storage vessel. The float rests on the liquid surface
and is housed inside a well that is closed by a removable cover.
Gauge hatch/sample port/sample well means an opening in the roof
that provides access for gauging or sampling. A gauge hatch is usually
equipped with a closing cover or a funnel and slit-fabric seal to cover
the opening.
Internal floating roof means a floating roof located in a storage
vessel with a fixed roof. For the purposes of this subpart, an external
floating roof located in a storage vessel to which a fixed roof has
been added is considered to be an internal floating roof.
Liquid-mounted primary seal means a liquid or foam-filled seal
mounted in continuous contact with the liquid between the wall of the
storage vessel and the floating roof around the entire circumference of
the storage vessel.
Maximum true vapor pressure means the equilibrium partial pressure
exerted by the volatile organic compounds (as defined in 40 CFR 51.100)
in the stored VOL at the temperature equal to the highest calendar-
month average of the VOL storage temperature for VOLs stored above or
below the ambient temperature or at the local maximum monthly average
temperature as reported by the National Weather Service for VOLs stored
at the ambient
[[Page 83321]]
temperature, as determined using the procedures specified in Sec.
60.113c(d).
Mechanical shoe primary seal means a metal sheet (the shoe) held
vertically against the wall of the storage vessel by springs or
weighted levels and is connected by braces to the floating roof. A
flexible coated fabric (the envelope) spans the annular space between
the metal sheet and the floating roof.
Petroleum means the crude oil removed from the earth and the oils
derived from tar sands, shale, and coal.
Petroleum liquids means petroleum, condensate, and any finished or
intermediate products manufactured in a petroleum refinery.
Pressure release means the emission of materials resulting from the
system pressure being greater than the set pressure of the pressure
relief device or resulting from vacuum breaking device failing to close
prior to the system reaching atmospheric pressure. This release can be
one release or a series of releases over a short time period.
Pressure relief device means a valve, rupture disk, or similar
device used only to release an unplanned, nonroutine discharge of gas
from process equipment in order to avoid safety hazards or equipment
damage. Devices with low opening pressures must be monitored as bypass
lines. A pressure relief device discharge can result from an operator
error, a malfunction such as a power failure or equipment failure, or
other unexpected cause. Such devices include conventional, spring-
actuated relief valves, balanced bellows relief valves, pilot-operated
relief valves, rupture disks, and breaking, buckling, or shearing pin
devices. Devices that are actuated only by a vacuum are not pressure
relief devices. If a device has both a pressure relief function and a
vacuum breaking function, such as a conservation vent, the portion of
the conservation vent that acts to relieve pressure is considered a
pressure relief device and the portion of the conservation vent that
acts to relieve vacuum is a vacuum breaking device and not a pressure
relief device.
Process tank means a tank that is used within a process (including
a solvent or raw material recovery process) to collect material
discharged from a feedstock storage vessel or equipment within the
process before the material is transferred to other equipment within
the process, to a product or by-product storage vessel, or to a vessel
used to store recovered solvent or raw material. In many process tanks,
unit operations such as reactions and blending are conducted. Other
process tanks, such as surge control vessels and bottoms receivers,
however, may not involve unit operations.
Reid vapor pressure means the absolute vapor pressure of volatile
crude oil and volatile nonviscous petroleum liquids except liquified
petroleum gases.
Rim-mounted secondary seal means a secondary seal mounted on the
rim of the floating roof of a storage vessel and forms continuous seal
from the rim of the floating roof to the wall of the storage vessel.
Rim seal system means a primary seal or a primary and secondary
seal, which is mounted above the primary seal, and is attached to the
deck perimeter and contacts the storage vessel wall.
Rim vent means a device consisting of a weighted pallet that rests
on a valve seat. Rim vents are used to release any excess pressure or
vacuum present in the vapor pocket between the seal and the rim area of
a floating roof storage vessel.
Routed to a process or route to a process means the emissions are
conveyed by hardpiping or a closed vent system to any enclosed portion
of a process unit where the emissions are predominately recycled and/or
consumed in the same manner as a material that fulfills the same
function in the process; and/or transformed by chemical reaction into
materials that are not volatile organic liquids; and/or incorporated
into a product; and/or recovered.
Storage vessel means each tank, reservoir, or container used for
the storage of volatile organic liquids but does not include:
(1) Frames, housing, auxiliary supports, or other components that
are not directly involved in the containment of liquids or vapors;
(2) Subsurface caverns or porous rock reservoirs; or
(3) Process tanks.
Vacuum breaker/automatic bleeder vent means a device used to
equalize the pressure of the vapor space across the deck of a floating
roof as the floating roof is either being landed on or floated off its
roof supports. A vacuum breaker/automatic bleeder vent consists of a
well with a cover. The cover is designed to open as the floating roof
is landed. Opening of the cover may be accomplished by mechanisms such
as leg actuation or pressure actuation.
Vacuum breaking device means a device on a fixed roof of a storage
vessel used to prevent mechanical failure of the storage vessel due to
vacuum created as liquids are withdrawn from the storage vessel. If a
device has both a pressure relief function and a vacuum breaking
function, such as a conservation vent, the portion of the conservation
vent that acts to relieve vacuum is considered a vacuum breaking device
and the portion of the conservation vent that acts to relieve excess
pressure is a pressure relief device and not a vacuum breaking device.
Volatile organic liquid (VOL) means any organic liquid which can
emit volatile organic compounds (as defined in 40 CFR 51.100) into the
atmosphere.
Waste means any liquid resulting from industrial, commercial,
mining, or agricultural operations, or from community activities that
is discarded or is being accumulated, stored, or physically,
chemically, or biologically treated prior to being discarded or
recycled.
Sec. 60.112c Standard for volatile organic compounds (VOC).
(a) General storage vessel control requirements. You must equip and
operate each storage vessel affected facility meeting the thresholds in
Sec. 60.110c(c)(1), (c)(2), (d)(1), or (d)(2) as specified in
paragraphs (a)(1) through (4) of this section, as applicable.
(1) For each storage vessel affected facility containing a VOL
that, as stored, has a maximum true vapor pressure less than 11.1 psia
(76.6 kPa), you may elect to install and operate either an internal
floating roof meeting the requirements in paragraph (b) of this
section, an external floating roof meeting the requirements in
paragraph (c) of this section, or a closed vent system routed to a
control device, fuel gas system, or process as specified in paragraph
(d) of this section.
(2) For each storage vessel affected facility containing a VOL
that, as stored, has a maximum true vapor pressure of 11.1 psia (76.6
kPa) or more, you must install and operate a closed vent system routed
to a control device, fuel gas system, or process as specified in
paragraph (d) of this section.
(3) For each storage vessel affected facility complying with the
closed vent system routed to a control device, fuel gas system, or
process provisions specified in paragraph (d) of this section
regardless of size and for each storage vessel with a design capacity
greater than or equal to 1,000,000 gal (3,790 m\3\) containing a VOL
that, as stored, has a maximum true vapor pressure equal to or greater
than 1.5 psia (10.3 kPa), you must also comply with the requirements in
paragraph (e) of this section.
(4) You must meet the applicable testing, monitoring, and
inspection requirements specified in Sec. 60.113c, recordkeeping
requirements specified in Sec. 60.115c, and reporting requirements
specified in Sec. 60.116c.
[[Page 83322]]
(b) Requirements for an internal floating roof. You must equip and
operate each internal floating roof as specified in paragraphs (b)(1)
through (16) of this section, as applicable.
(1) The internal floating roof must rest or float on the liquid
surface (but not necessarily in complete contact with it) inside a
storage vessel that has a fixed roof. The internal floating roof must
be floating on the liquid surface at all times, except during initial
fill and during those intervals when the storage vessel is completely
emptied or subsequently emptied and refilled. When the roof is resting
on the roof supports, the process of filling, emptying, or refilling
must be continuous and must be accomplished as rapidly as possible.
(2) Except as provided in paragraph (b)(14) of this section, each
internal floating roof must be equipped with the following closure
devices between the wall of the storage vessel and the edge of the
internal floating roof:
(i) Two seals mounted one above the other so that each forms a
continuous closure that completely covers the space between the wall of
the storage vessel and the edge of the internal floating roof. The
lower seal is referred to as the primary seal, and the upper seal is
referred to as the secondary seal.
(ii) The primary seal must be either a mechanical shoe seal or a
liquid-mounted seal. If a mechanical shoe seal is used, it must be
installed so that one end of the shoe extends into the stored VOL and
the other end extends a minimum vertical distance of 6 inches (15
centimeters) above the stored organic liquid surface.
(iii) The secondary seal must be rim-mounted.
(3) Each opening in a noncontact internal floating roof except for
vacuum breaker/automatic bleeder vents and the rim vents is to provide
a projection below the liquid surface.
(4) Vacuum breaker/automatic bleeder vents must be equipped with a
gasket and are to be closed at all times, with no visible gaps, when
the roof is floating. Vacuum breaker/automatic bleeder vents must be
set to open only when the roof is being floated off or is being landed
on the roof supports.
(5) Rim vents must be equipped with a gasket and must be closed at
all times with no visible gaps when the roof is floating. Rim vents
must be set to open only when the internal floating roof is not
floating or when the pressure beneath the rim seal system exceeds the
manufacturer's recommended setting.
(6) Each penetration of the internal floating roof for the purpose
of sampling must be a gauge hatch/sample well. Except as specified in
paragraph (b)(14) of this section, the gauge hatch/sample well must
have a gasketed cover, which must be closed at all times, with no
visible gaps, except when the hatch or well must be opened for access.
(7) Each access hatch and gauge float well must be equipped with a
cover that is gasketed and that is bolted or otherwise mechanically
secured. The cover must be closed and must be bolted or otherwise
mechanically secured at all times, with no visible gaps, except when
the hatch or well must be opened for access.
(8) Each penetration of the internal floating roof that allows for
passage of a column supporting the fixed roof must have a flexible
fabric sleeve seal or a gasketed sliding cover.
(9) Each penetration of the internal floating roof that allows for
passage of an unslotted leg ladder or unslotted ladder/guidepole
combination must have a gasketed sliding cover. The cover must be
closed at all times, with no visible gaps, except when the well must be
opened for access.
(10) Each slotted guidepole must be equipped with one of the
controls specified in paragraphs (b)(10)(i) through (v) of this
section. The covers must be designed to be closed at all times, with no
visible gaps, except when the cover must be opened for access.
(i) Gasketed sliding well cover, with pole sleeve. The sleeve must
extend into the stored liquid.
(ii) Gasketed sliding well cover, with pole sleeve and pole wiper.
The sleeve must extend into the stored liquid.
(iii) Gasketed sliding well cover, with pole float and pole wiper.
The wiper or seal of the pole float must be at or above the height of
the pole wiper.
(iv) Gasketed sliding well cover, with pole float, pole sleeve, and
pole wiper. The sleeve must extend into the stored liquid. The wiper or
seal of the pole float must be at or above the height of the pole
wiper.
(v) A flexible device that completely encloses the slotted
guidepole and eliminates the hydrocarbon vapor emissions pathway from
inside the storage vessel through the guidepole slots to the outside
air; a gasketed guidepole cover at the top of the guidepole; and a
gasketed sliding well cover positioned at the top of the guidepole well
that seals any openings between the well cover and the guidepole (e.g.,
pole wiper), any openings between the well cover and any other objects
that pass through the well cover, and any other openings in the top of
the guidepole well.
(11) Ladder-slotted guidepole combination wells must be equipped
with a gasketed sliding well cover and a ladder sleeve. The sliding
well cover must be designed to be closed at all times with no visible
gaps, except when gauging or sampling.
(12) Unslotted guidepoles must be equipped with one of the controls
specified in paragraph (b)(12)(i) or (ii) of this section. The controls
must be designed to be closed at all times with no visible gaps.
(i) A gasketed guidepole cover at the top of the guidepole; a
gasketed sliding well cover; and a pole sleeve. The guidepole cover
must be closed at all times, except when required to be opened for
access. The gasketed sliding well cover must seal any openings between
the well cover and the guidepole, any openings between the well cover
and any other objects that pass through the well cover, and any other
openings in the top of the guidepole well.
(ii) A gasketed guidepole cover at the top of the guidepole; a
gasketed sliding well cover; and a pole wiper. The guidepole cover must
be closed at all times, except when required to be opened for access.
The gasketed sliding well cover must seal any openings between the well
cover and the guidepole (e.g., pole wiper), any openings between the
well cover and any other objects that pass through the well cover, and
any other openings in the top of the guidepole well.
(13) Except for leg sleeves and stub drains, each opening in the
internal floating roof not specified in paragraphs (b)(4) through (12)
of this section, must be equipped with a cover or lid which is to be
maintained in a closed position at all times (i.e., no visible gap)
except when the device must be opened for access. The cover or lid must
be equipped with a gasket.
(14) For each modified storage vessel as specified in Sec.
60.110c(d) with an existing internal floating roof, you may elect to
comply with the rim seal system requirements in Sec. 60.112b(a)(1)(ii)
or Sec. 60.110b(e) instead of the requirements in paragraph (b)(2) of
this section, and you may elect to comply with the gauge hatch/sample
well requirements in Sec. 60.112b(a)(1)(vii) or Sec. 60.110b(e)
instead of the requirements in paragraph (b)(6) of this section.
(15) A system equivalent to those described in paragraphs (b)(1)
though (14) of this section, as applicable, as provided in Sec.
60.114c.
(16) Equip, maintain, and operate each internal floating roof
control system to maintain the vapor concentration above the floating
roof at or below 25 percent of the lower explosive limit (LEL) on a 5-
minute
[[Page 83323]]
rolling average basis without the use of purge gas. This standard may
require additional controls, such as improved seam seals, beyond those
specified in paragraphs (b)(1) through (15) of this section. Compliance
with this paragraph (b)(16) must be determined using the methods in
Sec. 60.113c(a)(3). Exceeding the LEL is considered an inspection
failure under Sec. 60.113c(a)(2)(i) and must be remedied as such. Any
repairs made must be confirmed effective through re-monitoring of the
LEL and meeting the limits in this paragraph (b)(16) within the
timeframes specified in Sec. 60.113c(a)(2)(i).
(c) Requirements for an external floating roof. You must equip and
operate each external floating roof as specified in paragraphs (c)(1)
through (4) of this section.
(1) The roof must be floating on the liquid at all times (i.e., off
the roof supports) except during initial fill until the roof is lifted
off roof supports and when the storage vessel is completely emptied or
subsequently emptied and refilled. The process of filling, emptying, or
refilling when the roof is resting on the roof supports must be
continuous and must be accomplished as rapidly as possible.
(2) Each external floating roof must be equipped with a primary and
secondary rim seal system as specified in paragraph (b)(2) of this
section, except that if a mechanical shoe primary seal is used, it must
be installed so that one end of the shoe extends into the stored VOL
and the other end extends a minimum vertical distance of 24 inches (61
centimeters) above the stored organic liquid surface. The external
floating roof also must have welded deck seams, and it must have deck
fitting controls as specified in paragraphs (c)(2)(i) through (ix) of
this section, as applicable. References to an internal floating roof in
paragraph (b)(2) of this section means an external floating roof for
the purposes of this paragraph (c)(2).
(i) Each opening in an external floating roof except for vacuum
breaker/automatic bleeder vents and the rim vents is to provide a
projection below the liquid surface.
(ii) Vacuum breaker/automatic bleeder vents must be equipped with a
gasket and are to be closed at all times, with no visible gaps, when
the roof is floating. Vacuum breaker/automatic bleeder vents must be
set to open only when the roof is being floated off or is being landed
on the roof supports.
(iii) Rim vents must be equipped with a gasket and must be closed
at all times with no visible gaps when the roof is floating. Rim vents
must be set to open only when the external floating roof is not
floating or when the pressure beneath the rim seal system exceeds the
manufacturer's recommended setting.
(iv) Each penetration of the external floating roof for the purpose
of sampling must be a gauge hatch/sample well. The gauge hatch/sample
well must have a gasketed cover, which must be closed at all times,
with no visible gaps, except when the hatch or well must be opened for
access.
(v) Each access hatch and gauge float well must be equipped with a
cover that is gasketed and that is bolted or otherwise mechanically
secured. The cover must be closed and must be bolted or otherwise
mechanically secured at all times, with no visible gaps, except when
the hatch or well must be opened for access.
(vi) Except as specified in paragraph (c)(3) of this section, if
the external floating roof does not have a liquid-mounted primary seal,
all guidepoles must be unslotted and must be equipped as specified in
paragraph (b)(12) of this section.
(vii) Except as specified in paragraph (c)(3) of this section, if
the external floating roof has a liquid-mounted primary seal, equip
each guidepole as specified in paragraphs (c)(2)(vii)(A) and (B) of
this section.
(A) Each slotted guidepole must be equipped as specified in
paragraphs (b)(10)(ii) or (iv) of this section.
(B) Each unslotted guidepole must be equipped as specified in
paragraph (b)(12) of this section.
(viii) Each emergency roof drain is to be provided with a slotted
membrane fabric cover that covers at least 90 percent of the area of
the opening.
(ix) Except for leg sleeves, each opening in the external floating
roof not subject to controls specified in paragraphs (c)(2)(i) through
(viii) of this section must be equipped with a cover or lid which is to
be maintained in a closed position at all times (i.e., no visible gap),
except when the device must be opened for access. The cover or lid must
be equipped with a gasket.
(3) For each modified storage vessel as specified in Sec.
60.110c(d) with an existing external floating roof, you may elect to
comply with any of the guidepole controls specified in paragraphs
(b)(10) and (12) of this section regardless of the type of primary seal
used.
(4) A system equivalent to those described in paragraphs (c)(1)
through (3) of this section as provided in Sec. 60.114c.
(d) Requirements for closed vent system routed to a control device,
fuel gas system, or process. You must design, install, and operate each
affected storage vessel with a closed vent system that routes to a
control device, fuel gas system, or process as specified in paragraphs
(d)(1) through (7) of this section.
(1) The storage vessel must be designed and operated to be routed
through a closed vent system to a control device, fuel gas system, or
process at all times the storage vessel contains VOL without venting to
the atmosphere through either meeting the storage vessel design
requirements specified in paragraph (d)(1)(i) of this section or the
vapor recovery system design requirements specified in paragraph
(d)(1)(ii) of this section. Compliance with this requirement must be
demonstrated according to paragraph (d)(1)(iii) of this section. Any
vacuum breaking device on the storage vessel must close while the
storage vessel is still under vacuum of at least -0.1 inches of water
(-0.0036 psig or -0.025 kPa gauge).
(i) The storage vessel must be designed to operate at a gauge
pressure of no less than 1 psi greater than the maximum true vapor
pressure of the stored liquid and any back pressure anticipated when
the storage vessel is filled at its maximum rate without venting to the
atmosphere.
(ii) The vapor recovery system must be designed and operated to
maintain the pressure in each storage vessel routed to a control device
below the venting pressure of that storage vessel.
(iii) You must equip each pressure relief device and vacuum
breaking device on a storage vessel with a device(s) or use a
monitoring system that is capable of meeting the requirements in
paragraphs (d)(1)(iii)(A) through (C) of this section. If all emissions
from a pressure relief device are routed through a closed vent system
to a control device, process, or fuel gas system, then you are not
required to comply with the requirements of this paragraph (d)(1)(iii).
(A) Identifying the pressure release.
(B) Recording the time and duration of each pressure release.
(C) Notifying operators immediately that a pressure release is
occurring. The device or monitoring system must be either specific to
the pressure relief device or vacuum breaking device itself or must be
associated with each storage vessel to indicate a pressure release to
the atmosphere. Examples of these types of devices and systems include,
but are not limited to, a rupture disk indicator, magnetic sensor,
motion detector on the pressure relief valve stem, flow monitor, or
pressure monitor.
[[Page 83324]]
(2) Except for closed vent systems operated and maintained under
negative pressure, each closed vent system must meet the requirements
specified in paragraphs (d)(2)(i) through (iii) of this section.
(i) The closed vent system must be designed to collect all VOC
vapors and gases discharged from the storage vessel and operated with
no detectable emissions as indicated by an instrument reading of less
than 500 parts per million by volume (ppmv) above background, as
determined using Method 21 of appendix A-7 to this part as specified in
Sec. 60.113c(c)(2) and (3), and as determined by observations for
visible, audible, and olfactory indications of leaks. Visible, audible,
and olfactory inspections must be performed quarterly and Method 21 of
appendix A-7 instrument monitoring must be conducted at least annually.
(ii) Except for pressure relief devices and except for open-ended
valves or lines that use a cap, blind flange, plug, or second valve and
follow the requirements specified in Sec. 60.482-6(a)(2), (b), and (c)
or follow requirements codified in another regulation that are the same
as Sec. 60.482-6(a)(2), (b), and (c), you must comply with the
provisions of either paragraph (d)(2)(ii)(A) or (B) of this section for
each closed vent system that contains bypass lines that could divert a
vent stream to the atmosphere.
(A) Properly install, maintain, and operate a flow indicator that
is capable of taking readings every 15 minutes. Install the flow
indicator at the entrance to any bypass line.
(B) Secure the bypass line valve in the non-diverting position with
a car-seal or a lock-and-key type configuration.
(iii) You must equip each pressure relief device on a closed vent
system with a device(s) or use a monitoring system that is capable of
meeting the requirements in paragraphs (d)(2)(iii)(A) through (C) of
this section. If all releases and potential leaks from a pressure
relief device are routed through a closed vent system to a control
device, process, or fuel gas system, then you are not required to
comply with the requirements of this paragraph (d)(2)(iii).
(A) Identifying the pressure release.
(B) Recording the time and duration of each pressure release.
(C) Notifying operators immediately that a pressure release is
occurring. The device or monitoring system must be either specific to
the pressure relief device itself or must be associated with the
process system or piping, sufficient to indicate a pressure release to
the atmosphere. Examples of these types of devices and systems include,
but are not limited to, a rupture disk indicator, magnetic sensor,
motion detector on the pressure relief valve stem, flow monitor, or
pressure monitor.
(3) If you route emissions from a storage vessel to a control
device, the control device must be designed and operated to reduce
inlet VOC emissions by 98 percent or greater. If a flare is used as the
control device or if an enclosed combustion device is used for which
you elect to comply with the flare operating limits, you must meet the
specifications described in paragraph (d)(5) of this section. The
control device must be operated at all times when emissions from an
affected storage vessel are routed to it except as provided in
paragraph (d)(7) of this section.
(4) A system equivalent to those described in paragraphs (d)(1)
through (3) of this section as provided in Sec. 60.114c.
(5) If you route from a storage vessel to a flare or enclosed
combustion device for with you elect to comply with these flare
operating limits, you must meet all applicable requirements specified
in 40 CFR 63.670(b) through (g) and (i) through (n) except as provided
in paragraphs (d)(5)(i) through (v) of this section.
(i) For the purpose of this subpart,
(A) The term ``regulated materials'' refers to ``vapors from a
storage vessel affected facility'';
(B) The term ``pilot flame'' means ``pilot flame or flare flame'';
(C) The terms ``petroleum refinery'' and ``refinery'' mean
``storage vessel affected facility''.
(ii) For visible emissions, use the following text instead of 40
CFR 63.670(c): The owner or operator shall operate with no visible
emissions, except for periods not to exceed a total of five (5) minutes
during any two (2) consecutive hours, when regulated material is routed
to the flare. You must monitor for visible emissions from the flare as
specified in Sec. 60.113c(c)(1)(iv)(A).
(iii) The phrase ``and the flare vent gas flow rate is less than
the smokeless design capacity of the flare'' in 40 CFR 63.670(d) for
flare tip velocity requirements does not apply.
(6) If you route emissions from a storage vessel to a fuel gas
system or process, you must meet the requirements in paragraphs
(d)(6)(i) through (iv) of this section, as applicable.
(i) The fuel gas system or process must be operating at all times
when emissions from an affected storage vessel are routed to it.
(ii) If all emissions are routed to a process, the VOL in the
emissions must meet one or more of the conditions specified in
paragraphs (d)(6)(ii)(A) through (D) of this section and you must
comply with the compliance demonstration requirements in paragraph
(d)(6)(iii) of this section.
(A) Recycled and/or consumed in the same manner as a material that
fulfills the same function in that process.
(B) Transformed by chemical reaction into materials that are not
regulated materials.
(C) Incorporated into a product.
(D) Recovered.
(iii) To demonstrate compliance with paragraph (d)(6)(ii) of this
section for an affected storage vessel, you must prepare a design
evaluation (or engineering assessment) that demonstrates the extent to
which one or more of the conditions specified in paragraphs
(d)(6)(ii)(A) through (D) of this section are being met.
(iv) If emissions from an affected storage vessel are routed to a
fuel gas system, you must submit the statement of connection for fuel
gas systems specified in Sec. 60.116c(a)(7).
(7) To the extent practical, routine maintenance on the control
device should be conducted when the storage vessel(s) is(are) out of
VOL service. If you comply with all the provisions in paragraphs
(d)(7)(i) through (iv) of this section, you may conduct routine
maintenance on a control device while one or more storage vessels
vented to the control device are storing a VOL.
(i) The storage vessel(s) storing VOL must be designed to operate
above the maximum true vapor pressure of the stored VOL according to
paragraph (d)(1)(i) of this section.
(ii) The control device must be isolated from the storage vessel(s)
using valves(s), blind flange(s), or similar device(s) at the control
device or in the closed vent system as near as practical to the control
device. You may purge the control device and downstream portion of the
closed vent system to remove potentially explosive vapors and create a
safe work environment only after the control device is isolated from
the storage vessel(s).
(iii) You must continue to comply with the bypass and pressure
relief device monitoring requirements in paragraphs (d)(1)(iii),
(d)(2)(ii), and (d)(2)(iii) of this section and their associated
recordkeeping and reporting requirements. If there are multiple storage
vessels connected to the closed vent system with significantly
different pressure design limits, you must isolate individual storage
vessels to prevent venting during planned maintenance.
[[Page 83325]]
Compliance with this paragraph (d)(7)(iii) may limit VOL addition to
the storage vessel. If VOL is added to the storage vessel, there must
be an approximately equivalent withdrawal of VOL such that the liquid
level does not rise sufficiently to increase the pressure in the
storage vessel to cause a pressure release from the storage vessel or
the closed vent system.
(iv) During this routine maintenance period the affected storage
vessels cannot be actively degassed. If the storage vessel is to be
emptied and actively degassed, the planned maintenance activity must be
conducted when the storage vessel is out of VOL service.
(e) Requirements for storage vessel degassing. For each storage
vessel meeting the specifications in paragraph (a)(3) of this section,
you must meet the requirements in paragraphs (e)(1) through (3) of this
section during emptying and degassing of a storage vessel until the
vapor space concentration in the storage vessel is less than 10 percent
of the LEL or, for nonflammable liquids, 5,000 ppmv as methane. You
must determine the LEL or methane concentration using process
instrumentation or a portable measurement device and follow procedures
for calibration and maintenance according to manufacturer's
specifications. You must check instrument calibration and check the
instrumental offset response each day the instrument is used and prior
to discontinuing controlled degassing to confirm the accuracy of the
instrument's readings.
(1) Remove liquids from the storage vessel as much as practicable.
Chemicals or a diluent such as a distillate fuel may be introduced into
the storage vessel for the purpose of reducing vapor concentration
before or during active degassing.
(2) Comply with one of the following:
(i) Reduce total VOC emissions by venting emissions through a
closed vent system to a flare or enclosed combustion device for which
you elect to comply with the flare provisions and meet the requirements
specified in paragraph (d)(5) of this section.
(ii) Reduce total VOC emissions by 98 weight percent by venting
emissions through a closed vent system to any combination of non-flare
control devices.
(iii) Reduce total VOC emissions by routing emissions to a fuel gas
system or process and meet the requirements specified in paragraph
(d)(6) of this section.
(3) For floating roof storage vessels, the storage vessel may be
opened to set up equipment (e.g., making connections to a temporary
control device) for the shutdown operations but must not be actively
degassed during this time period.
Sec. 60.113c Testing, monitoring, and inspection procedures.
For each storage vessel subject to the provision in Sec.
60.112c(a), you must meet the requirements of paragraph (a) of this
section if you installed an internal floating roof, paragraph (b) of
this section if you installed an external floating roof, or paragraph
(c) of this section if you route emissions through a closed vent system
to a control device, fuel gas system, or process. You must also meet
the applicable requirements of paragraph (d) of this section.
(a) Requirements for an internal floating roof. After installing
the control equipment for an internal floating roof to meet the
provisions in Sec. 60.112c(b), you must meet the requirements
specified in paragraphs (a)(1) through (5) of this section.
(1) Visually inspect the internal floating roof, the primary seal,
the secondary seal (if one is in service), and deck fittings prior to
filling the storage vessel with VOL. Any of the conditions described in
paragraphs (a)(1)(i) through (iii) of this section constitutes
inspection failure. You must repair the items before filling the
storage vessel.
(i) Holes, tears, or other openings in the primary seal, the
secondary seal, or the seal fabric;
(ii) Defects in the internal floating roof; or
(iii) A rim seal or deck fitting control not meeting the applicable
requirements in Sec. 60.112c(b)(2) through (13).
(2) Inspect the internal floating roof as specified in paragraph
(a)(2)(i) of this section at least once every 12 calendar months after
initial fill, and inspect the internal floating roof as specified in
paragraph (a)(2)(ii) of this section each time the storage vessel is
emptied and degassed, or at a frequency no greater than every 120
calendar months, whichever occurs first.
(i) Visually inspect the internal floating roof, the primary seal,
the secondary seal (if one is service), and deck fittings, through
openings in the fixed roof and conduct LEL monitoring. Any of the
conditions described in paragraphs (a)(2)(i)(A) through (F) of this
section constitutes inspection failure. Identification of holes or
tears in the rim seal is required only for the seal that is visible
from the top of the storage vessel. You must repair the items or empty
and remove the storage vessel from service within 45 days. If a failure
that is detected during inspections required in this paragraph
(a)(2)(i) cannot be repaired within 45 days and if the storage vessel
cannot be emptied within 45 days, you may request a 30-day extension
from the Administrator. Such a request for an extension must document
that alternate storage capacity is unavailable and specify a schedule
of actions the company will take that will assure that the control
equipment will be repaired or the storage vessel will be emptied as
soon as possible.
(A) Stored liquid on the floating roof;
(B) The internal floating roof is not resting on the surface of the
VOL inside the storage vessel;
(C) Holes, tears, or other openings in the primary seal, the
secondary seal, or the seal fabric;
(D) Defects in the internal floating roof;
(E) A rim seal or deck fitting control not meeting the applicable
requirements in Sec. 60.112c(b)(2) through (13); or
(F) The concentration measured according to paragraph (a)(3) of
this section exceeds 25 percent of the LEL.
(ii) Visually inspect the internal floating roof, the primary seal,
the secondary seal (if one is in service), gaskets, slotted membranes,
and sleeve seals (if any). Any of the conditions described in
paragraphs (a)(2)(ii)(A) through (C) of this section constitutes an
inspection failure. You must repair the items as necessary so that none
of the conditions specified in this paragraph (a)(2)(ii) exist before
refilling the storage vessel with VOL. The inspection may be performed
entirely from the top side of the floating roof, as long as there is
visual access to all deck fittings and rim seal system specified in
Sec. 60.112c(b). You must repair the items or empty and remove the
storage vessel from service within 45 days. If a failure that is
detected during inspections required in this paragraph (a)(2)(ii)
cannot be repaired within 45 days and if the storage vessel cannot be
emptied within 45 days, you may request a 30-day extension from the
Administrator. Such a request for an extension must document that
alternate storage capacity is unavailable and specify a schedule of
actions the company will take that will assure that the control
equipment will be repaired or the storage vessel will be emptied as
soon as possible.
(A) Defects in the internal floating roof;
(B) Holes, tears, or other openings in the primary seal, the
secondary seal, or the seal fabric; or
(C) A rim seal or deck fitting control not meeting the applicable
requirements in Sec. 60.112c(b)(2) through (13).
(3) Compliance with the LEL limit for internal floating roof
storage vessels at
[[Page 83326]]
Sec. 60.112c(b)(16) must be determined based on the procedures
specified in paragraphs (a)(3)(i) through (v) of this section. If
tubing is necessary to obtain the measurements, the tubing must be non-
crimping and made of Teflon or other inert material.
(i) You must conduct LEL monitoring as part of the annual
inspection specified in paragraph (a)(2)(i) of this section and at
other times upon request by the Administrator. If the measurement
cannot be performed during the visual inspection due to wind speeds
exceeding those specified in paragraph (a)(3)(iii)(C) of this section,
the measurement must be performed within 30 days of the visual
inspection. If there is an exceedance of the LEL limit, you must re-
monitor in accordance with Sec. 60.112c(b)(16) within 30 days after
repair or placing the storage vessel back in service.
(ii) The calibration of the LEL meter must be checked per
manufacturer specifications immediately before and after the
measurements as specified in paragraphs (a)(3)(ii)(A) and (B) of this
section. If tubing will be used for the measurements, the tubing must
be attached during calibration so that the calibration gas travels
through the entire measurement system.
(A) Conduct the span check using a calibration gas recommended by
the LEL meter manufacturer. The calibration gas must contain a single
hydrocarbon at a concentration of the vapor corresponding to 50 percent
of the LEL (e.g., 2.50 percent by volume when using methane as the
calibration gas). The vendor must provide a Certificate of Analysis for
the gas, and the certified concentration must be within 2
percent (e.g., 2.45 percent-2.55 percent by volume when using methane
as the calibration gas). The LEL span response must be between 49
percent and 51 percent. If the span check prior to the measurements
does not meet this requirement, the LEL meter must be recalibrated or
replaced. If the span check after the measurements does not meet this
requirement, the LEL meter must be recalibrated or replaced, and the
measurements must be repeated.
(B) Check the instrumental offset response using a certified
compressed gas cylinder of zero air or an ambient environment that is
free of organic compounds. The pre-measurement instrumental offset
response must be 0 percent LEL. If the LEL meter does not meet this
requirement, the LEL meter must be recalibrated or replaced.
(iii) Conduct the monitoring measurements as specified in
paragraphs (a)(3)(iii)(A) through (D) of this section.
(A) Measurements of the vapors within the internal floating roof
storage vessel must be collected no more than 3 feet above the internal
floating roof.
(B) Measurements must be taken for a minimum of 20 minutes, logging
the measurements at least once every 15 seconds, or until one 5-minute
average as determined according to paragraph (a)(3)(v)(B) of this
section exceeds the limit specified in Sec. 60.112c(b)(16).
(C) Measurements shall be taken when the wind speed at the top of
the storage vessel is 5 mph or less to the extent practicable, but in
no case shall measurements be taken when the sustained wind speed at
top of storage vessel is greater than the annual average wind speed at
the site or 15 mph, whichever is less.
(D) Measurements should be conducted when the internal floating
roof is floating with limited product movement (limited filling or
emptying of the storage vessel).
(iv) To determine the actual concentration of the vapor within the
storage vessel, the percent of the LEL ``as the calibration gas'' must
be corrected according to one of the procedures in paragraph
(a)(3)(iv)(A) or (B) of this section. Alternatively, if the LEL meter
used has correction factors that can be selected from the meter's
program, you may enable this feature to automatically apply one of the
correction factors in paragraph (a)(3)(iv)(A) or (B) of this section.
(A) Multiply the measurement by the published vapor correction
factor for the specific LEL meter, stored VOL, and calibration gas
used; or
(B) If there is no published correction factor for the specific LEL
meter used and the vapors of the stored VOL, multiply the measurement
by the published correction factor for butane as a surrogate for
determining the LEL of the vapors of the stored VOL. The correction
factor must correspond to the calibration gas used.
(v) Use the calculation procedures in paragraphs (a)(3)(v)(A)
through (C) of this section to determine compliance with the LEL limit.
(A) For each minute while measurements are being taken, determine
the 1-minute average reading as the arithmetic average of the corrected
individual measurements (taken at least once every 15 seconds) during
the minute.
(B) Starting with the end of the fifth minute of data, calculate a
5-minute rolling average as the arithmetic average of the previous five
1-minute readings determined under paragraph (a)(3)(v)(A) of this
section. Determine a new 5-minute average reading for every subsequent
1-minute reading.
(C) Each 5-minute rolling average must meet the LEL limit specified
in Sec. 60.112c(b)(16).
(4) Notify the Administrator as specified in Sec. 60.116c(b) at
least 30 days prior to the inspection of each storage vessel for which
an inspection is required by paragraph (a)(1) or (a)(2)(ii) of this
section to afford the Administrator the opportunity to have an observer
present.
(5) You must equip each affected storage vessel that has an
internal floating roof with an alarm system that provides a visual or
audible signal that alerts the operator when the internal floating roof
is approaching the landed height and that provides a separate visual or
audible signal to alert the operator when the roof has landed. The roof
is considered landed when the floating roof first rests on supports or
when the vacuum breaker/automatic bleeder vent begins to open,
whichever is first (for example, when using a leg-actuated vent that
triggers the vent prior to resting on the roof supports).
(b) Requirements for an external floating roof. After installing
the control equipment for an external floating roof to meet the
provisions in Sec. 60.112c(c), you must inspect the external floating
roof according to the specifications in paragraphs (b)(1) through (8)
of this section.
(1) Determine the gap areas and maximum gap widths, between the
primary seal and the wall of the storage vessel and between the
secondary seal and the wall of the storage vessel according to the
frequency provided in paragraphs (b)(1)(i) and (ii) of this section.
You must visually inspect all roof fittings to ensure that covers are
closed and gasketed with no visible gaps and that there are no tears in
sleeves, wipers, or similar controls used for a given fitting during
each measurement of gaps as required under this paragraph (b)(1).
(i) Measurements of gaps between the storage vessel wall and the
primary seal (seal gaps) must be performed during the hydrostatic
testing of the storage vessel or within 60 days of the initial fill
with VOL and at least once every 60 calendar months thereafter.
(ii) Measurements of gaps between the storage vessel wall and the
secondary seal must be performed within 60 days of the initial fill
with VOL and at least once every 12 calendar months thereafter.
(iii) If any source ceases to store VOL for a period of 12 calendar
months or more, subsequent introduction of VOL into the storage vessel
must be
[[Page 83327]]
considered an initial fill for the purposes of paragraphs (b)(1)(i) and
(b)(1)(ii) of this section.
(2) Determine gap widths and areas in the primary and secondary
seals individually by the following procedures:
(i) Measure seal gaps, if any, at one or more floating roof levels
when the roof is floating off the roof supports.
(ii) Measure seal gaps around the entire circumference of the
storage vessel in each place where a 0.125-inch (0.32-centimeter (cm))
diameter uniform probe passes freely (without forcing or binding
against seal) between the seal and the wall of the storage vessel and
measure the circumferential distance of each such location.
(iii) The total surface area of each gap described in paragraph
(b)(2)(ii) of this section must be determined by using probes of
various widths to measure accurately the actual distance from the
storage vessel wall to the seal and multiplying each such width by its
respective circumferential distance.
(3) Add the gap surface area of each gap location for the primary
seal and the secondary seal individually and divide the sum for each
seal by the nominal diameter of the storage vessel and compare each
ratio to the respective standards in paragraph (b)(4) of this section.
(4) Except as provided in paragraph (b)(5) of this section, make
necessary repairs or empty the storage vessel within 45 days of
identification in any inspection failure as specified in paragraphs
(b)(4)(i) through (iii) of this section.
(i) For primary seals, any deviation of the requirements in
paragraphs (b)(4)(i)(A) through (D) of this section is an inspection
failure.
(A) The accumulated area of gaps between the storage vessel wall
and the mechanical shoe or liquid-mounted primary seal must not exceed
10 square inches (in\2\) per foot of storage vessel diameter (212
square centimeters (cm\2\) per meter of storage vessel diameter).
(B) The maximum width of any portion of any gap must not exceed 1.5
inches (3.81 cm).
(C) If a mechanical shoe seal is used, one end of the mechanical
shoe is to extend into the stored liquid, and the other end is to
extend a minimum vertical distance of 2 feet (61 cm) above the stored
liquid surface.
(D) There are to be no holes, tears, or other openings in the shoe,
seal fabric, or seal envelope.
(ii) For secondary seals, any deviation of the requirements in
paragraphs (b)(4)(ii)(A) through (D) of this section is an inspection
failure.
(A) The secondary seal is to be installed above the primary seal so
that it completely covers the space between the roof edge and the
storage vessel wall except for allowed gaps as provided in paragraphs
(b)(4)(ii)(B) and (C) of this section.
(B) The accumulated area of gaps between the storage vessel wall
and the secondary seal must not exceed 1 in\2\ per foot (21.2 cm\2\ per
meter) of storage vessel diameter.
(C) The maximum width of any portion of any gap must not exceed 0.5
inches (1.27 cm).
(D) There are to be no holes, tears, or other openings in the seal
or seal fabric.
(iii) For roof fittings (e.g., vacuum breaker/automatic bleeder
vents and rim vents, gauge hatch/sample wells, access hatches,
guidepoles, ladders, and emergency roof drains), any deviation of the
requirements in paragraphs (b)(4)(iii)(A) through (D) of this section
is an inspection failure.
(A) Each opening in an external floating roof except for vacuum
breaker/automatic bleeder vents and the rim vents provides a projection
below the liquid surface.
(B) Vacuum breaker/automatic bleeder vents and rim vents are
equipped with a gasket and are closed with no visible gaps when the
roof is floating.
(C) The gauge hatch/sample well, access hatch, and gauge float must
have a gasketed cover and closed with no visible gaps.
(D) There are to be no tears or visible defects of sleeves, wipers,
or fabric covers used to control emissions from a roof fitting.
(5) If a failure that is detected as specified in paragraph (b)(4)
of this section cannot be repaired within 45 days and if the storage
vessel cannot be emptied within 45 days, you may request a 30-day
extension from the Administrator. Such extension request must include a
demonstration of unavailability of alternate storage capacity and a
specification of a schedule that will assure that the control equipment
will be repaired or the storage vessel will be emptied as soon as
possible.
(6) Notify the Administrator, as specified in Sec. 60.116c(b)(2),
30 days in advance of any gap measurements required by paragraph (b)(1)
of this section to afford the Administrator the opportunity to have an
observer present.
(7) Visually inspect the external floating roof, primary seal,
secondary seal, and fittings each time the vessel is emptied and
degassed.
(i) If the external floating roof has defects, the primary seal has
holes, tears, or other openings in the seal or the seal fabric, the
secondary seal has holes, tears, or other openings in the seal or the
seal fabric, covers have visible openings or missing or torn gaskets,
or there are tears or other visible defects in flexible covers,
sleeves, wipers, or other fitting controls, you must repair the items
as necessary so that none of the conditions specified in this paragraph
(b)(7)(i) exist before filling or refilling the storage vessel with
VOL.
(ii) For each inspection required by paragraph (b)(7) of this
section, notify the Administrator as specified in Sec. 60.116c(b)(1)
at least 30 days prior to the inspection of each storage vessel to
afford the Administrator the opportunity to inspect the storage vessel.
(8) You must equip each affected storage vessel that has an
external floating roof with an alarm system that provides a visual or
audible signal that alerts the operator when the external floating roof
is approaching the landed height and that provides a separate visual or
audible signal to alert the operator when the roof has landed. The roof
is considered landed when the floating roof first rests on supports or
when the vacuum breaker/automatic bleeder vent begins to open,
whichever is first (for example, when using a leg-actuated vent that
triggers the vent prior to resting on the roof supports).
(c) Requirements for closed vent systems routed to a control
device, fuel gas system, or process. For each source that is equipped
with a closed vent system and routes to a control device, fuel gas
system, or process to meet the requirements in Sec. 60.112c(d), you
must conduct performance testing and monitoring of the control device
as specified in paragraph (c)(1) of this section, conduct monitoring
and inspections of the closed vent system as specified in paragraph
(c)(2) of this section, repair leaks as specified in paragraph (c)(3)
of this section, and develop a monitoring plan as specified in
paragraph (c)(4) of this section.
(1) For each control device used to meet the requirements in Sec.
60.112c(d), you must comply with the requirements in paragraphs
(c)(1)(i) through (iv) of this section, as applicable.
(i) For each enclosed combustion device or flare, you must install,
calibrate, maintain, and operate a backpressure regulator valve
calibrated to open at the minimum pressure set point corresponding to
the minimum inlet gas flow rate. The set point must be consistent with
manufacturer specifications for minimum flow or pressure and must be
supported by an
[[Page 83328]]
engineering evaluation. At least annually, you must confirm that the
backpressure regulator valve set point is correct and consistent with
the engineering evaluation and manufacturer specifications and that the
valve fully closes when not in the open position.
(ii) For each control device other than a flare, except as
specified in paragraph (c)(1)(iii) of this section, you must conduct a
performance test as specified in paragraphs (c)(1)(ii)(A) through (E)
of this section not later than 180 days after becoming subject to Sec.
60.112c(d). You must conduct subsequent performance tests within 60
calendar months after each previous performance test. Submit the
results of all performance tests following the procedures in Sec.
60.116c(e).
(A) Each performance test must demonstrate that the control device
achieves greater than or equal to the required control device
performance level specified in Sec. 60.112c(d)(3). Performance tests
must be conducted under such conditions as the Administrator specifies
based on representative performance of the affected source for the
period being tested. You may not conduct performance tests during
periods of malfunction. You must record the process information that is
necessary to document operating conditions during the test and include
in such record an explanation to support that such conditions represent
the entire range of normal operation, including operational conditions
for maximum emissions if such emissions are not expected during maximum
production. You must make available to the Administrator such records
as may be necessary to determine the conditions of performance tests.
(B) You must conduct a minimum of three test runs. Each test run
must be at least 1 hour long.
(C) The following methods in appendix A to this part, except as
provided in Sec. 60.8(b), must be used as reference methods to
determine compliance with the percent reduction requirement.
(1) Method 1 or 1A of appendix A-1 to this part, as appropriate,
for selection of the sampling sites. Sampling sites must be located at
the inlet of the first control device and at the outlet of the final
control device to determine compliance with a control device percent
reduction requirement.
(2) Method 2, 2A, 2C, or 2D of appendix A-1 to this part, as
appropriate to determine the gas volumetric flow rate.
(3) Method 25A of appendix A-7 to this part. Use propane as the
calibration gas. You must use Method 4 of appendix A-3 to this part to
convert the Method 25A of appendix A-7 results to a dry basis.
(D) You must use the procedures in paragraphs (c)(1)(ii)(D)(1) and
(2) of this section to calculate percent reduction efficiency.
(1) You must compute the mass rate of TOC using the following
equations:
Ei = K2CiMpQi
Eo = K2CoMpQo
Equations 1 and 2 to Paragraph (c)(1)(ii)(D)(1)
Where:
Ei, Eo = Mass rate of TOC at the inlet and
outlet of the control device, respectively, dry basis, kilograms per
hour.
K2 = Constant, 2.494 x 10-6 (parts per
million) (gram-mole per standard cubic meter) (kilogram/gram)
(minute/hour), where standard temperature (gram-mole per standard
cubic meter) is 20 degrees Celsius.
Ci, Co = Concentration of TOC, as propane, of
the gas stream as measured by Method 25A of appendix A-7 to this
part at the inlet and outlet of the control device, respectively,
dry basis, parts per million by volume.
Mp = Molecular weight of propane, 44.1 gram/gram-mole.
Qi, Qo = Flowrate of gas stream at the inlet
and outlet of the control device, respectively, dry standard cubic
meter per minute.
(2) You must calculate the percent reduction in TOC as follows:
[GRAPHIC] [TIFF OMITTED] TR15OC24.000
Equation 3 to Paragraph (c)(1)(ii)(D)(2)
Where:
Rcd = Control efficiency of control device, percent.
Ei = Mass rate of TOC at the inlet to the control device
as calculated under paragraph (c)(1)(ii)(D)(1) of this section,
kilograms per hour.
Eo = Mass rate of TOC at the outlet of the control
device, as calculated under paragraph (c)(1)(ii)(D)(1) of this
section, kilograms per hour.
(E) Except as provided in paragraph (c)(1)(ii)(E)(5) of this
section, you must establish the applicable operating parameter limit as
specified in paragraphs (c)(1)(ii)(E)(1) through (3) of this section by
calculating the value(s) as the arithmetic average of operating
parameter measurements recorded during the three test runs conducted
for the most recent performance test (the average of the test run
averages). You may operate outside of the established operating
parameter limit(s) during subsequent performance tests in order to
establish new operating limits. You must include the updated operating
limits with the performance test results submitted to the Administrator
pursuant to Sec. 60.116c(e). Upon establishment of a new operating
limit, you must thereafter operate under the new operating limit. You
must demonstrate compliance with your operating parameter according to
paragraph (c)(1)(ii)(E)(4) of this section.
(1) If you use an enclosed combustion device, a boiler, or a
process heater other than those specified in paragraph (c)(1)(iii) of
this section to control emissions, you must set a minimum firebox
temperature limit during the performance test. You must continuously
monitor the firebox temperature with a temperature monitoring device
installed in the firebox or in the ductwork immediately downstream from
the firebox in a position before any substantial heat exchange occurs
and equipped with a continuous recorder that records a reading at least
once every 15 minutes. The monitoring device must have a minimum
accuracy of 1 percent of the temperature being monitored in
degrees Celsius, or 2.5 degrees Celsius, whichever value is
greater.
(2) If you use a catalytic incinerator other than those specified
in paragraph (c)(1)(iii) of this section to control emissions, you must
set a minimum temperature limit on the temperature at the inlet of the
catalyst bed and a minimum temperature limit on the temperature
difference between the catalyst bed outlet and inlet. You must
continuously monitor the temperatures with a temperature monitoring
device equipped with a continuous recorder that records a reading at
least once every 15 minutes. The device must be capable of monitoring
temperature at two locations and have a minimum accuracy of 1 percent of the temperature being monitored in degrees Celsius,
or 2.5 degrees Celsius, whichever value is greater. You
must install one temperature sensor in the vent stream at the nearest
feasible point to the catalyst bed inlet, and you must install a second
temperature sensor in the vent stream at the nearest feasible point to
the catalyst bed outlet. You must install the temperature sensor at a
location representative of the firebox temperature.
(3) If you use a control device other than a flare or other than a
device listed in paragraphs (c)(1)(ii)(E)(1), (c)(1)(ii)(E)(2),
(c)(1)(ii)(E)(5), or (c)(1)(iii) to control emissions, you must submit
the operating parameters you plan to monitor in the performance test
[[Page 83329]]
notice you provide to the Administrator pursuant to Sec. 60.8(d).
(4) Using the continuous monitoring system (CMS) data, you must
calculate the hourly average of each operating parameter. You must
demonstrate compliance by maintaining the operating parameter at or
above the minimum operating parameter limit on a 3-hour rolling average
basis. For each hour, calculate the hourly value of the operating
parameter from your CMS. Average the three most recent hours of data to
determine the 3-hour average. Determine the 3-hour rolling average by
recalculating the 3-hour average each hour. You must not include
periods of data collected during monitoring system breakdowns, repairs,
maintenance periods, instrument adjustments, or checks to maintain
precision and accuracy in the operating parameter averages.
(5) For enclosed combustion devices for which you elect to comply
with the flare requirements in Sec. 60.112c(d)(5), you must comply
with the monitoring provisions in paragraph (c)(1)(iv) of this section
instead of paragraphs (c)(1)(ii)(E)(1) through (4) of this section.
(iii) No performance test is required for the control devices
identified in paragraphs (c)(1)(iii)(A) through (C) of this section.
(A) A boiler or process heater with a design heat input capacity of
44 megawatts (150 million British thermal units per hour) or greater.
(B) A boiler or process heater into which the vent stream is
introduced with the primary fuel.
(C) A boiler, process heater, or incinerator burning hazardous
waste, which is regulated under 40 CFR part 63, subpart EEE; part 264;
part 265; or part 266.
(iv) For each source that is equipped with a closed vent system and
a flare to meet the requirements in Sec. 60.112c(d) or enclosed
combustion device electing to comply with the requirements in Sec.
60.112c(d)(5), you must conduct visible emission observations as
specified in paragraph (c)(1)(iv)(A) of this section and install,
operate, and maintain CMS for flares following the requirements
specified in 40 CFR 63.671 and as specified in paragraphs (c)(1)(iv)(B)
and (C) of this section.
(A) If visible emissions are observed for more than 1 continuous
minute during normal duties, visible emissions observation using Method
22 of appendix A-7 to this part must be conducted for 2 hours or until
5-minutes of visible emissions are observed.
(B) Substitute ``pilot flame or flare flame'' for each occurrence
of ``pilot flame.''
(C) As an alternative to determining the flare tip velocity rate
for each 15-minute block to determine compliance with the flare tip
velocity operating limit as specified in 40 CFR 63.670(k)(2), you may
elect to conduct a one-time flare tip velocity operating limit
compliance assessment as provided in paragraphs (c)(1)(iv)(C)(1)
through (4) of this section. If the flare or storage vessel control
configurations change (e.g., flare tip modified or additional storage
vessel or other sources are added for which vapors are directed to the
flare), you must repeat this one-time assessment based on the new
configuration.
(1) Determine the unobstructed cross-sectional area of the flare
tip, in units of square feet, as specified in 40 CFR 63.670(k)(1).
(2) Determine the maximum flow rate, in units of cubic feet per
second, based on the maximum cumulative loading rate for a 15-minute
block period considering maximum filling rates for all storage vessel
affected facilities controlled by the flare and, if applicable,
considering the maximum release pressure of any other vapors directed
to the flare.
(3) Calculate the maximum flare tip velocity as the maximum flow
rate from paragraph (c)(1)(iv)(C)(2) of this section divided by the
unobstructed cross-sectional area of the flare tip from paragraph
(c)(1)(iv)(C)(1) of this section.
(4) Demonstrate that the maximum flare tip velocity as calculated
in paragraph (c)(1)(iv)(C)(3) of this section is less than 60 feet per
second.
(2) For each closed vent system, you must conduct the instrument
monitoring in paragraphs (c)(2)(i) through (iii) of this section. You
must conduct the initial instrument monitoring within 180 days of an
affected facility being connected to the closed vent system. Subsequent
instrument inspections must be conducted within 365 days of the
previous inspection. Visual, audible, and olfactory inspections must be
conducted quarterly.
(i) Conduct instrument monitoring using the procedures in Method 21
of appendix A-7 to this part. The detection instrument must meet the
performance criteria of Method 21 of appendix A-7, except that the
instrument response factor criteria in section 8.1.1 of Method 21 of
appendix A-7 must be for the average composition of the fluid and not
for each individual organic compound in the stream. For streams that
contain nitrogen, air, water, or other inerts that are not organic VOC,
the representative stream response factor must be determined on an
inert-free basis. The instrument reading that defines a leak is 500
ppmv (as methane). The instrument shall be calibrated before use each
day of its use by the procedures specified in Method 21 of appendix A-
7. The calibration gases in paragraphs (c)(2)(i)(A) and (B) of this
section must be used. The drift assessment specified in paragraph
(c)(2)(i)(C) of this section must be performed at the end of each
monitoring day.
(A) Zero air (less than 10 ppm of hydrocarbon in air).
(B) A mixture of methane in air at a concentration of approximately
500 ppmv.
(C) At the end of each monitoring day, check the instrument using
the same calibration gas that was used to calibrate the instrument
before use. Follow the procedures specified in Method 21 of appendix A-
7 to this part, section 10.1, except do not adjust the meter readout to
correspond to the calibration gas value. If multiple scales are used,
record the instrument reading for each scale used. Divide the
arithmetic difference of the initial and post-test calibration response
by the corresponding calibration gas value for each scale and multiply
by 100 to express the calibration drift as a percentage. If a
calibration drift assessment shows a negative drift of more than 10
percent, then re-monitor all equipment monitored since the last
calibration with instrument readings between the leak definition and
the leak definition multiplied by (100 minus the percent of negative
drift) divided by 100. If any calibration drift assessment shows a
positive drift of more than 10 percent from the initial calibration
value, then, at the owner/operator's discretion, all equipment with
instrument readings above the leak definition and below the leak
definition multiplied by (100 plus the percent of positive drift)
divided by 100 monitored since the last calibration may be re-
monitored.
(ii) Any parts of the closed vent system that are designated as
unsafe to inspect are exempt from the inspection requirements of
paragraph (c)(2)(i) of this section if the conditions of paragraphs
(c)(2)(ii)(A) and (B) of this section are met.
(A) The owner or operator determines that the equipment is unsafe-
to-inspect because inspecting personnel would be exposed to an imminent
or potential danger as a consequence of complying with paragraph
(c)(2)(i) of this section; and
(B) The owner or operator has a written plan that requires
inspection of
[[Page 83330]]
the equipment as frequently as practical during safe-to-inspect times.
Inspection is not required more than once annually.
(iii) Any parts of the closed vent system that are designated as
difficult-to-inspect are exempt from the inspection requirements of
paragraph (c)(2)(i) of this section if the provisions of paragraphs
(c)(2)(iii)(A) and (B) of this section apply.
(A) The owner or operator determines that the equipment cannot be
inspected without elevating the inspecting personnel more than 2 meters
(7 feet) above a support surface; and
(B) The owner or operator has a written plan that requires
inspection of the equipment at least once every 60 calendar months.
(3) Leaks, as indicated by an instrument reading greater than 500
ppmv or emissions detected by visible, audible, and olfactory methods,
shall be repaired as soon as practical following the requirements
outlined in paragraphs (c)(3)(i) and (ii) of this section.
(i) Except as allowed by paragraph (c)(3)(ii) of this section, a
first attempt at repair shall be made no later than 5 days after the
leak is detected. Repairs shall be completed no later than 15 days
after the leak is detected or at the beginning of the next introduction
of vapors to the system, whichever is later.
(ii) Delay of repair of a closed vent system for which leaks have
been detected is allowed if repair within 15 days after a leak is
detected is technically infeasible or unsafe or if the owner or
operator determines that emissions resulting from immediate repair
would be greater than the emissions likely to result from delay of
repair. Repair of such equipment shall be completed as soon as
practical.
(4) You must develop a monitoring plan that covers each CMS used to
demonstrate continuous compliance for your control device as outlined
in paragraphs (c)(4)(i) and (ii) of this section. You must install,
calibrate, operate, and maintain each CMS in accordance with the
procedures in your monitoring plan.
(i) For each control device other than those specified in paragraph
(c)(4)(ii) of this section, your monitoring plan must contain the
information required in paragraphs (c)(4)(i)(A) through (G) of this
section.
(A) The parameter to be monitored and the operating limit for the
parameter.
(B) Sampling interface (e.g., thermocouple) location such that the
monitoring system will provide representative measurements.
(C) Description of the monitoring system specifications, including
the detector signal analyzer, data acquisition, and calculations.
(D) Equipment performance checks, system accuracy audits, or other
audit procedures, including the information in paragraphs
(c)(4)(i)(D)(1) through (4) of this section.
(1) You must conduct the CMS equipment performance checks, system
accuracy audits, or other audit procedures specified in the monitoring
plan at least once every 12 calendar months.
(2) You must also conduct calibration checks following any period
of more than 24 hours throughout which the sensor exceeded the
manufacturer's specified maximum range unless you install a new sensor.
(3) At least quarterly, you must inspect all components for
integrity and all electrical connections for continuity, oxidation, and
galvanic corrosion, unless you use a redundant CMS.
(4) Daily checks for indications that the system is responding.
(E) Description of how periods of data collected during CMS
breakdowns, out-of-control periods, repairs, maintenance periods,
instrument adjustments, or checks to maintain precision and accuracy,
calibration checks, and zero (low-level), mid-level (if applicable),
and high-level adjustments will be excluded from operating parameter
averages.
(F) Ongoing operation and maintenance procedures.
(G) Ongoing recordkeeping procedures.
(ii) For each flare or enclosed combustion device for with you
elect to comply with the flare provisions in Sec. 60.112c(d)(5), your
monitoring plan must contain the information required by 40 CFR
63.671(b).
(d) Requirements for determining maximum true vapor pressure. For
each affected storage vessel, you must determine the maximum true vapor
pressure of the stored VOL according to the requirements specified in
paragraphs (d)(1) and (2) of this section. For storage vessels operated
above or below ambient temperatures, the maximum true vapor pressure is
calculated based upon the highest expected calendar-month average of
the storage temperature. For storage vessels operated at ambient
temperatures, the maximum true vapor pressure is calculated based upon
the maximum local monthly average ambient temperature as reported by
the National Weather Service.
(1) Prior to the initial filling of the storage vessel or to the
refilling of the storage vessel with a new VOL, the highest maximum
true vapor pressure for the range of anticipated liquids to be stored,
including mixtures for which you can define the range of concentrations
for constituents in the mixture or with a known maximum Reid vapor
pressure, must be determined using any one of the methods described in
paragraphs (d)(1)(i) through (iv) of this section.
(i) As obtained from standard reference texts.
(ii) ASTM D6377-20 (incorporated by reference; see Sec. 60.17).
Perform the method using a vapor-to-liquid ratio of 4:1, which is
expressed in the method as VPCR.
(iii) ASTM D6378-22 (incorporated by reference; see Sec. 60.17).
Perform the method using a vapor-to-liquid ratio of 4:1.
(iv) As measured by an appropriate method as approved by the
Administrator.
(2) For each affected storage vessel storing a mixture of
indeterminate composition or a mixture of unknown variable composition,
the initial determination of the vapor pressure required by paragraph
(d)(1) of this section must be a physical test using one of the methods
specified in paragraphs (d)(1)(ii) through (iv) of this section.
Additional physical tests using one of the methods specified in
paragraphs (d)(1)(ii) through (iv) of this section are required at
least once every 6 calendar months thereafter as long as the measured
vapor pressure remains below the applicable thresholds in Sec.
60.110c(c)(1), (c)(2), (d)(1), or (d)(2). If the vapor pressure
measured under this paragraph (d)(2) exceeds the threshold defined in
Sec. 60.110c(c)(1), (c)(2), (d)(1), or (d)(2) you must meet the
requirements in Sec. 60.112c and the corresponding requirements in
Sec. Sec. 60.113c through 60.116c. If the storage vessel does not have
controls meeting the requirements in Sec. 60.112c, the storage vessel
must be emptied and taken out of service until controls meeting the
requirements in Sec. 60.112c can be installed. Upon compliance with
the provisions in Sec. 60.112c, no additional vapor pressure
monitoring is required.
Sec. 60.114c Alternative means of emission limitation.
(a) If, in the Administrator's judgment, an alternative means of
emission limitation will achieve a reduction in emissions at least
equivalent to the reduction in emissions achieved by the applicable
requirement in Sec. 60.112c, the Administrator will publish in the
Federal Register a
[[Page 83331]]
document permitting the use of the alternative means for purposes of
compliance with that requirement.
(b) Any document under paragraph (a) of this section will be
published only after notice and an opportunity for a hearing.
(c) Any person seeking permission under this section must submit to
the Administrator a written application including either:
(1) An actual emissions test that uses a full-sized or scale-model
storage vessel that accurately collects and measures all VOC emissions
from a given control device and that accurately simulates wind and
accounts for other emission variables such as temperature and
barometric pressure; or
(2) An engineering evaluation that the Administrator determines is
an accurate method of determining equivalence.
(d) The Administrator may condition the permission on requirements
that may be necessary to ensure operation and maintenance to achieve
the same emission reduction as specified in Sec. 60.112c.
Sec. 60.115c Recordkeeping requirements.
(a) Except as otherwise specified in paragraphs (b) through (d) of
this section, you must keep copies of all records required by this
section and all reports required under Sec. 60.116c for at least 5
years.
(b) For each storage vessel affected facility as specified in Sec.
60.110c(a), you must keep readily accessible records for the life of
the source showing the dimension of the storage vessel and an analysis
showing the capacity of the storage vessel.
(c) Except as provided in paragraphs (c)(1) and (2) of this
section, for each storage vessel affected facility under this subpart,
you must maintain a record of the VOL currently stored, including a
description of the VOL stored, the date when the VOL was first stored
in the storage vessel, and the maximum true vapor pressure of that VOL.
(1) For each vessel storing a mixture of indeterminate or variable
composition that meets the requirements for vapor pressure measurement
at least once every 6 calendar months in Sec. 60.113c(d), you must
maintain records of each vapor pressure measurement for 5 years.
(2) Each vessel equipped with a closed vent system routed to a
control device, fuel gas system, or process meeting the specification
of Sec. 60.112c(d) is exempt from the requirements of paragraph (c) of
this section.
(d) For each storage vessel as specified in Sec. 60.112c(a), you
must keep records as required in paragraphs (d)(1) through (5) of this
section, as applicable depending upon the control equipment installed
to meet the requirements of Sec. 60.112c.
(1) After installing control equipment for an internal floating
roof to meet the provisions in Sec. 60.112c(b), you must keep the
following records.
(i) Keep a record of each inspection performed as required by Sec.
60.113c(a)(1), (a)(2)(i), and (a)(2)(ii). Each record must identify the
storage vessel on which the inspection was performed and must contain
the date the vessel was inspected and the observed condition of each
component of the control equipment (seals, internal floating roof, and
fittings).
(ii) For each LEL monitoring event, keep records as specified in
paragraphs (a)(1)(ii)(A) through (I) of this section.
(A) Date and time of the LEL monitoring, and the storage vessel
being monitored.
(B) A description of the monitoring event (annual monitoring
conducted concurrent with visual inspection required under Sec.
60.113c(a)(2)(i); re-monitoring due to high winds during annual
monitoring; re-monitoring after repair attempt; other monitoring event
as required by the Administrator).
(C) Wind speed at the top of the storage vessel on the date of LEL
monitoring.
(D) The LEL meter manufacturer and model number used, as well as an
indication of whether tubing was used during the LEL monitoring, and if
so, the type and length of tubing used.
(E) Calibration checks conducted before and after making the
measurements, including both the span check and instrumental offset.
This includes the hydrocarbon used as the calibration gas, the
Certificate of Analysis for the calibration gas(es), the results of the
calibration check, and any corrective action for calibration checks
that do not meet the required response.
(F) Location of the measurements and the location of the floating
roof.
(G) Each measurement (taken at least once every 15 seconds). The
records should indicate whether the recorded values were automatically
corrected using the meter's programming. If the values were not
automatically corrected, record both the raw (as the calibration gas)
and corrected measurements, as well as the correction factor used.
(H) Each of the 5-minute rolling average readings.
(I) If the vapor concentration of the storage vessel was above 25
percent of the LEL on a 5-minute rolling average basis, a description
of whether the floating roof was repaired, replaced, or taken out of
service.
(2) After installing control equipment for an external floating
roof to meet the provisions in Sec. 60.112c(c), you must keep a record
of each inspection and gap measurement performed as required by Sec.
60.113c(b). The record must contain:
(i) Identification of the storage vessel on which the inspection
was performed;
(ii) The date the storage vessel was inspected;
(iii) The type of inspection [inspection with gap measurements as
specified in Sec. 60.113c(b)(1) through (4); visual inspection as
specified in Sec. 60.113c(b)(7)];
(iv) The observed condition of each component of the control
equipment (seals, internal floating roof, and fittings); and
(v) For each inspection with gap measurements as specified in Sec.
60.113c(b)(1) through (4):
(A) The raw data obtained in the measurement; and
(B) The calculations described in Sec. 60.113c(b)(2) and (b)(3).
(3) After installing a closed vent system routed to a control
device, fuel gas system, or process to comply with the provisions in
Sec. 60.112c(d), you must keep the following records, as well as the
records in paragraph (d)(4) or (5) of this section, as applicable.
(i) The make and model of the backpressure regulator valve, date of
installation, and inlet flow rating. Maintain records of the
engineering evaluation and manufacturer specifications that identify
the pressure set point corresponding to the minimum inlet gas flow
rate, the annual confirmation that the backpressure regulator valve set
point is correct and consistent with the engineering evaluation and
manufacturer specifications, and the annual confirmation that the
backpressure regulator valve fully closes when not in open position.
(ii) The CMS monitoring plan required by Sec. 60.113c(c)(4), if
the closed vent system is routed to a control device. Retain this plan
for the life of the control equipment.
(iii) Monitoring for the closed vent system conducted under Sec.
60.113c(c)(2), including the date of inspection.
(iv) The written plan(s) required under Sec. 60.113c(c)(2)(ii) and
(iii) for unsafe-to-inspect and difficult-to-inspect portions of the
closed vent system.
(v) For each leak detected during the monitoring conducted under
Sec. 60.113c(c)(2) and (3), you must record: the date the leak was
detected; the location of the leak; the method used to detect the leak
(Method 21 of appendix
[[Page 83332]]
A-7 to this part or visible, audible, and olfactory methods); and the
maximum concentration reading obtained by Method 21 of appendix A-7, if
applicable. For each repair attempt, you must record: the date of each
repair attempt; the actions taken to repair the leak during each repair
attempt; and date the repair was completed. If the repair is delayed,
you must record the reason for the delay and the date you expect to
complete the repair.
(vi) For each bypass line, maintain a record of the following, as
applicable: readings from the flow indicator; each inspection of the
seal or closure mechanism; the date and time of each instance when the
seal mechanism is broken, the bypass line valve position has changed,
or the key for a lock-and-key type lock has been checked out.
(vii) For each pressure relief device or vacuum breaking device on
a storage vessel or closed vent system required to be monitored
according to Sec. 60.112c(d)(1)(iii) or (d)(2)(iii): the device type;
the monitoring device or system used for the device; data from the
device or system indicating whether a pressure release occurred; and
the date, time, and duration of each pressure release, if applicable.
(4) After installing a closed vent system routed to a control
device other than a flare or enclosed combustion device electing to
comply with Sec. 60.112c(d), you must keep the following records.
(i) Each performance test.
(ii) All CMS performance checks, audits, maintenance, and repairs.
(iii) The hourly values recorded by the CMS and all 3-hour rolling
averages.
(iv) The periods when the CMS is not operational.
(5) After installing a closed vent system routed to a flare to
comply with Sec. 60.112c(d) or an enclosed combustion device for which
you elected to comply with Sec. 60.112c(d)(5), you must keep the
following records.
(i) Pilot flame or flare flame monitoring as specified in
paragraphs (d)(5)(i)(A) and (B) of this section.
(A) The output of the monitoring device used to detect the presence
of a pilot flame as required in 40 CFR 63.670(b). Retain these records
for a minimum of 2 years.
(B) Each 15-minute block during which there was at least 1 minute
that no pilot flame was present when VOL vapors were routed to the
flare. Each record must identify the start and end time and date of
each 15-minute block.
(ii) Visible emissions observations as specified in paragraphs
(d)(5)(ii)(A) through (B) of this section, as applicable.
(A) If visible emissions observations are performed using Method 22
of appendix A-7 to this part, the record must identify the date, the
start and end time of the visible emissions observation, and the number
of minutes for which visible emissions were observed during the
observation. If the owner or operator performs visible emissions
observations more than one time during a day, include separate records
for each visible emissions observation performed.
(B) For each 2-hour period for which visible emissions are observed
for more than 5 minutes in 2 consecutive hours but visible emissions
observations according to Method 22 of appendix A-7 to this part were
not conducted for the full 2-hour period, the record must include the
date, the start and end time of the visible emissions observation, and
an estimate of the cumulative number of minutes in the 2-hour period
for which emissions were visible based on best information available to
the owner or operator.
(iii) Each 15-minute block period during which operating values are
outside of the applicable operating limits specified in 40 CFR
63.670(d) through (f) when vapors from a storage vessel affected
facility are directed to the flare for at least 15-minutes identifying
each specific operating limit that was not met.
(iv) The 15-minute block average cumulative flows for the enclosed
combustion device vent gas or flare vent gas and, if applicable, total
steam, perimeter assist air, and premix assist air specified to be
monitored under 40 CFR 63.670(i), along with the date and start and end
time for the 15-minute block. If multiple monitoring locations are used
to determine cumulative vent gas flow, total steam, perimeter assist
air, and premix assist air, retain records of the 15-minute block
average flows for each monitoring location for a minimum of 2 years,
and retain the 15-minute block average cumulative flows that are used
in subsequent calculations for a minimum of 5 years. If pressure and
temperature monitoring is used, retain records of the 15-minute block
average temperature, pressure and molecular weight of the flare vent
gas, enclosed combustion device vent gas, or assist gas stream for each
measurement location used to determine the 15-minute block average
cumulative flows for a minimum of 2 years, and retain the 15-minute
block average cumulative flows that are used in subsequent calculations
for a minimum of 5 years.
(v) The flare vent gas or enclosed combustion device vent gas
compositions specified to be monitored under 40 CFR 63.670(j). Retain
records of individual component concentrations from each compositional
analyses for a minimum of 2 years. If an NHVvg analyzer is
used, retain records of the 15-minute block average values for a
minimum of 5 years, as well as records of quality assurance activities
conducted on the analyzer and any cylinder gas certificates. If you
demonstrate your gas streams have consistent composition using the
provisions in 40 CFR 63.670(j)(6), retain records of the current
application for which you are using for as long as you use the fixed
NHVvg as determined using the provisions in 40 CFR
63.670(j)(6).
(vi) Each 15-minute block average operating parameter calculated
following the methods specified in 40 CFR 63.670(k) through (n), as
applicable.
(vii) All periods during which you did not perform monitoring
according to the procedures in 40 CFR 63.670(g), (i), and (j) as
applicable. Note the start date, start time, and duration in minutes
for each period.
(viii) If you conduct a one-time flare tip velocity operating limit
compliance assessment according to Sec. 60.113c(c)(1)(iv)(C), a copy
of the assessment, including all calculations for as long as you use
this compliance method.
(ix) For each parameter monitored using a CMS, retain the records
specified in paragraphs (d)(5)(ix)(A) through (C) of this section, as
applicable:
(A) For each deviation, record the start date and time, duration,
cause, and corrective action taken.
(B) For each period when there is a CMS outage or the CMS is out of
control, record the start date and time, duration, cause, and
corrective action taken.
(C) Each inspection or calibration of the CMS including a unique
identifier, make, and model number of the CMS, and date of calibration
check.
(x) For an enclosed combustion device for which you elected to
comply with Sec. 60.112c(d)(5), you must also keep a copy of each
performance test.
(e) If you are required to meet the degassing requirements in Sec.
60.112c(a)(3), you must maintain records necessary to demonstrate
compliance with the requirements in Sec. 60.112c(e) including, if
appropriate, records of existing standard site procedures used to empty
and degas (deinventory) equipment for safety purposes.
[[Page 83333]]
Sec. 60.116c Reporting requirements.
(a) Initial notification requirements. You must submit initial
notifications to the Administrator within 60 days after October 15,
2024 or within 60 days after becoming an affected storage vessel,
whichever is later. Once the report template for this subpart has been
available on the Compliance and Emissions Data Reporting Interface
(CEDRI) website (https://www.epa.gov/electronic-reporting-air-emissions/cedri) for 1 year, you must submit all subsequent initial
notifications using the appropriate electronic report template on the
CEDRI website for this subpart and following the procedure specified in
paragraph (f) of this section. The date report templates become
available will be listed on the CEDRI website. For each storage vessel
affected facility subject to the standards in Sec. 60.112c, include
the following information in the initial notification:
(1) The following general facility information:
(i) Facility name;
(ii) Facility physical address, including city, county, State, and
zip code;
(iii) Latitude and longitude of facility's physical location.
Coordinates must be in decimal degrees with at least five decimal
places; and
(iv) The following information for the facility contact person:
(A) Name;
(B) Mailing address, including city, county, State, and zip code;
(C) Telephone number; and
(D) Email address.
(2) Identification of the storage vessel(s) subject to this
subpart.
(3) Capacity (in gallons) of each storage vessel.
(4) Maximum true vapor pressure of the liquid stored (in psia) in
each storage vessel.
(5) Indication of the standards for which the storage vessel
complies [Sec. Sec. 60.112c(b); 60.112c(c); 60.112c(d); 60.112c(e)].
(6) If you route emissions to a control device, specify the design
of the storage vessel and closed vent system (i.e., storage vessel
designed according to Sec. 60.112c(d)(1)(i); or closed vent system
designed according to Sec. 60.112c(d)(1)(ii)), the type of control
device (i.e., enclosed combustion device complying with temperature
operating limit; enclosed combustion device electing to comply with
Sec. 60.112c(d)(5); process heater or boiler; catalytic incinerator;
flare, or other control device (specify)).
(7) If you route emissions to a process, submit the information
specified in Sec. 60.112c(d)(6)(ii) and (iii).
(8) If you route emissions to a fuel gas system, as specified in
Sec. 60.112c(d)(6)(iv), submit a statement that the emission stream is
connected to the fuel gas system.
(b) Other notifications. Submit notifications for filling and
refilling an affected storage vessel and for conducting gap
measurements as specified in paragraphs (b)(1) and (2) of this section.
(1) As specified in Sec. 60.113c(a)(4) and (b)(7)(ii), you must
notify the Administrator at least 30 days prior to inspection of each
storage vessel for which an inspection is required by Sec.
60.113c(a)(1), (a)(2)(ii) or (b)(7) to afford the Administrator the
opportunity to have an observer present. Submit the notification using
CEDRI as specified in paragraph (f) of this section. If the inspection
required by Sec. 60.113c(a)(2)(ii) or (b)(7) is not planned and you
could not have known about the inspection 30 days in advance of
refilling the storage vessel, you must notify the Administrator at
least 7 days prior to the refilling of the storage vessel. Notification
shall be made by telephone immediately followed by written
documentation using CEDRI demonstrating why the inspection was
unplanned.
(2) As specified in Sec. 60.113c(b)(6), you must notify the
Administrator 30 days in advance of any gap measurements required by
Sec. 60.113c(b)(1) to afford the Administrator the opportunity to have
an observer present. Submit the notification using CEDRI as specified
in paragraph (f) of this section. If the inspection required by Sec.
60.113c(b)(1) is not planned and you could not have known about the
inspection 30 days in advance of the gap measurement, you must notify
the Administrator at least 7 days prior to the conducting the gap
measurement. Notification must be made by telephone immediately
followed by written documentation using CEDRI demonstrating why the gap
measurement was unplanned.
(c) Reporting requirements for semiannual report. You must submit
to the Administrator semiannual reports with the applicable information
in paragraphs (c)(1) through (12) of this section by the dates
specified in paragraph (d) of this section. For this subpart, the
semiannual reports supersede the excess emissions and monitoring
systems performance report and/or summary report form required under
Sec. 60.7. Once the report template for this subpart has been
available on the CEDRI website (https://www.epa.gov/electronic-reporting-air-emissions/cedri) for 1 year, you must submit all
subsequent reports using the appropriate electronic report template on
the CEDRI website for this subpart and following the procedure
specified in paragraph (f) of this section. The date report templates
become available will be listed on the CEDRI website. Unless the
Administrator or delegated State agency or other authority has approved
a different schedule for submission of reports, the report must be
submitted by the deadline specified in this subpart, regardless of the
method in which the report is submitted.
(1) Report the following general facility information:
(i) Facility name;
(ii) Facility physical address, including city, county, and State;
(iii) Latitude and longitude of facility's physical location.
Coordinates must be in decimal degrees with at least five decimal
places;
(iv) The following information for the facility contact person:
(A) Name;
(B) Mailing address;
(C) Telephone number; and
(D) Email address.
(v) Date of report and beginning and ending dates of the reporting
period. You are no longer required to provide the date of report when
the report is submitted via CEDRI; and
(vi) Statement by a responsible official, with that official's
name, title, and signature, certifying the truth, accuracy, and
completeness of the content of the report. If your report is submitted
via CEDRI, the certifier's electronic signature during the submission
process replaces the requirement in this paragraph (c)(1)(vi).
(2) For storage vessels complying with the provisions of Sec.
60.112c(b) or (c):
(i) Identification of the storage vessel and an indication of
whether you comply with Sec. 60.112c(b) or (c).
(ii) An indication whether the storage vessel was inspected during
the reporting period, and if so, the date and type of each inspection
conducted during the reporting period [the type of inspection shall be
selected from the following list: initial IFR inspection according to
Sec. 60.113c(a)(1), IFR visual inspection from fixed roof according to
Sec. 60.113c(a)(2)(i), combined IFR visual inspection with LEL
monitoring according to Sec. 60.113c(a)(2)(i) and (3), internal IFR
inspection according to Sec. 60.113c(a)(2)(ii), IFR LEL monitoring
according to Sec. 60.113c(a)(3), EFR gap measurements according to
Sec. 60.113c(b)(1) through (4), or visual EFR inspection according to
Sec. 60.113c(b)(7)].
(iii) For storage vessels complying with the provisions of Sec.
60.112c(b) that were not inspected according to
[[Page 83334]]
Sec. 60.113c(a)(2)(ii) during the reporting period, report the last
date the storage vessel was inspected according to the provisions in
Sec. 60.113c(a)(2)(ii).
(3) For each failure of a visual inspection required under Sec.
60.113c(a)(2)(i), report the information in paragraphs (c)(3)(i)
through (iii) of this section. For each failure of LEL monitoring
required under Sec. 60.113c(a)(3), report the information in
paragraphs (c)(3)(i) through (iv) of this section.
(i) Identification of the storage vessel;
(ii) The date of the inspection;
(iii) The nature of the defects; and
(iv) The following information regarding the LEL monitoring
conducted:
(A) Date and start and end times of the LEL monitoring conducted.
(B) Wind speed in miles per hour at the top of the storage vessel
on the date of LEL monitoring.
(C) The highest 5-minute rolling average reading during the
monitoring event.
(D) If re-monitoring was required due to excessive wind or repair
during the visual inspection, report the information in paragraphs
(b)(3)(iv)(A) through (C) of this section for the re-monitoring event.
(E) Whether the floating roof was repaired, replaced, or taken out
of VOL service. If the storage vessel was taken out of VOL service,
report the date the storage vessel was emptied. If the floating roof
was replaced or repaired, report the nature of and date the repair was
made and the information in paragraphs (b)(3)(iv)(A) through (C) of
this section for each re-monitoring conducted to confirm the repair.
(4) For each inspection required by Sec. 60.113c(a)(2)(ii) that
finds holes or tears in the seal or seal fabric, defects in the
internal floating roof, or other control equipment defects listed in
Sec. 60.113c(a)(2)(ii), report:
(i) Identification of the storage vessel and date of inspection;
(ii) The reason it did not meet the specifications of Sec.
60.112c(b) or Sec. 60.113c(a)(2)(ii);
(iii) A description of each repair made; and
(iv) Date of repair.
(5) For each inspection required under Sec. 60.113c(b)(1), report
the following information:
(i) Identification of the storage vessel and the date of the
inspection;
(ii) The accumulated area of gaps between the storage vessel wall
and the primary seal (in square inches per foot of storage vessel
diameter);
(iii) The maximum width of any portion of any gap in the primary
seal (in inches);
(iv) The accumulated area of gaps between the storage vessel wall
and the secondary seal (in square inches per foot of storage vessel
diameter);
(v) The maximum width of any portion of any gap in the secondary
seal (in inches); and
(vi) An indication whether there was an inspection failure. If
there was an inspection failure, also include the following information
in the report:
(A) An indication of the type of deviation(s) [indicating all that
apply from: Sec. Sec. 60.113c(b)(4)(i)(A), 60.113c(b)(4)(i)(B),
60.113c(b)(4)(i)(C), 60.113c(b)(4)(i)(D), 60.113c(b)(4)(ii)(A),
60.113c(b)(4)(ii)(B), 60.113c(b)(4)(ii)(C), 60.113c(b)(4)(ii)(D),
60.113c(b)(4)(iii)(A), 60.113c(b)(4)(iii)(B), 60.113c(b)(4)(iii)(C),
60.113c(b)(4)(iii)(D)]; and
(B) The date the storage vessel was emptied or the repairs made and
date of repair.
(6) For each inspection required by Sec. 60.113c(b)(7) that finds
defects as listed in Sec. 60.113c(b)(7)(i), report:
(i) Identification of the storage vessel and date of inspection;
(ii) The reason it did not meet the specifications of Sec.
60.112c(c) or Sec. 60.113c(b)(7);
(iii) A description of each repair made; and
(iv) Date of repair.
(7) For each landing of an internal floating roof or an external
floating roof that triggers an alarm required by Sec. 60.113c(a)(5) or
(b)(8), report:
(i) Identification of the storage vessel;
(ii) Date the roof was landed; and
(iii) Indication of whether the roof landed because the storage
vessel was being emptied.
(8) After installing a closed vent system that routes to a control
device, fuel gas system, or process to comply with Sec. 60.112c,
report the following, as well as the information in paragraphs (c)(9)
or (10) of this section, as applicable:
(i) Results of annual inspections that indicate a backpressure
regulator valve is not set correctly or does not fully close when not
in the open position. Include the date and time of the inspection, the
type of deviation, the corrective action taken, and the date and time
when the backpressure regulator valve is set correctly, repaired, or
replaced.
(ii) For each inspection conducted under Sec. 60.113c(c)(2),
identification of the closed vent system, the date of inspection, the
type of inspection (Method 21 of appendix A-7 to this part or visible,
audible, and olfactory methods) and summary result of the inspection
(no leaks detected or leaks were detected). For each leak detected,
provide an identification of the part of the closed vent system
associated with the leak, the date of the first attempt at repair, and
the date of successful repair or anticipated repair if the repair is
delayed.
(iii) The start date and time, duration in hours, and an estimate
of the mass quantity in pounds of VOL released for times when flow is
detected or emissions are diverted from the control device through a
bypass line while a storage vessel affected facility vented to the
closed vent system contains VOL or is being degassed.
(9) After installing a closed vent system and control device to
comply with Sec. 60.112c other than a flare or an enclosed combustion
device electing to comply with Sec. 60.112c(d)(5), report:
(i) For each instance when the CMS measured 3-hour rolling averages
below the established operating limit:
(A) The date and start time of the deviation;
(B) The duration of the deviation in hours;
(C) The lowest 3-hour rolling average operating parameter reading
during the period of the deviation;
(D) A unique identifier for the CMS;
(E) The make, model number, and date of last calibration check of
the CMS; and
(F) The cause of the deviation and the corrective action taken.
(ii) For all instances when the CMS was inoperative:
(A) The date and start time of the deviation;
(B) The duration of the deviation in hours;
(C) A unique identifier for the CMS;
(D) The make, model number, and date of last calibration check of
the CMS; and
(E) The cause of the deviation and the corrective action taken.
(10) After installing a closed vent system and a flare to comply
with Sec. 60.112c or an enclosed combustion device electing to comply
with Sec. 60.112c(d)(5), report:
(i) The date and start and end times for each of the following
instances:
(A) Each 15-minute block during which there was at least 1 minute
when storage vessel vapors were routed to the flare and no pilot flame
or flare flame was present.
(B) Each period of 2 consecutive hours during which visible
emissions exceeded a total of 5 minutes. Additionally, report the
number of minutes for which visible emissions were observed during the
observation or an estimate of the cumulative number of minutes in the
2-hour period for which
[[Page 83335]]
emissions were visible based on best information available to the owner
or operator.
(C) Each 15-minute period for which the applicable operating limits
specified in 40 CFR 63.670(d) through (f) were not met. You must
identify the specific operating limit that was not met and report the
value of the net heating value operating parameter(s) during the
deviation determined following the methods in 40 CFR 63.670(k) through
(n) as applicable.
(ii) The start date, start time, and duration in minutes for each
period when storage vessel vapors were routed to the flare or enclosed
combustion device and the applicable monitoring was not performed.
(iii) For each instance reported under paragraphs (c)(10)(i) and
(ii) of this section that involves CMS, report the following
information:
(A) A unique identifier for the CMS;
(B) The make, model number, and date of last calibration check of
the CMS; and
(C) The cause of the deviation or downtime and the corrective
action taken.
(11) For pressure relief devices on a storage vessel or closed vent
system subject to Sec. 60.112c(d)(1)(iii) or (d)(2)(iii), report each
pressure release to the atmosphere, including pressure relief device
identification name or number, the start date, start time, and duration
(in minutes) of the pressure release; and an estimate of the mass
quantity in pounds of VOL released.
(12) For vacuum breaking devices on a storage vessel subject to
Sec. 60.112c(d) and (d)(1)(iii), report the following information for
each time the vacuum breaking device failed to close prior to the
storage vessel reaching atmospheric pressure: identification name or
number of vacuum breaking device; the start date, start time, and
duration (in minutes) of the pressure release; and an estimate of the
mass quantity in pounds of VOL released.
(d) Timeframe for semiannual report submissions. (1) The first
semiannual report will cover the period starting with the date the
source first becomes an affected facility subject to this subpart and
ending June 30 or December 31, whichever date is earlier. For example,
if the source becomes an affected facility on April 15, the first
semiannual report would cover the period from April 15 to June 30. The
first semiannual report must be submitted on or before the last day of
the month 2 months after the last date covered by the semiannual
report. In this example, the first semiannual report would be due
August 31.
(2) Subsequent semiannual reports will cover subsequent 6 calendar
month periods (January 1 through June 30 or July 1 through December 31,
as applicable) with each report due on or before the last day of the
month 2 months after the last date covered by the semiannual report
(August 31 or February 28 or 29, as applicable).
(3) For each affected facility that is subject to permitting
regulations pursuant to 40 CFR parts 70 or 71, if the delegated
authority has established dates for submitting semiannual reports
pursuant to 40 CFR 70.6(a)(3)(iii)(A) or 71.6(a)(3)(iii)(A), you may
submit the first and subsequent semiannual reports according to the
dates the delegated authority has established instead of the dates in
paragraphs (d)(1) and (2) of this section.
(e) Reporting requirements for performance tests. Within 60 days
after the date of completing each performance test, you must submit the
results following the procedures specified in paragraph (f) of this
section. Data collected using test methods that are supported by the
U.S. Environmental Protection Agency (EPA) Electronic Reporting Tool
(ERT) as listed on the EPA's ERT website (https://www.epa.gov/electronic-reporting-air-emissions/electronic-reporting-tool-ert) at
the time of the test must be submitted in a file format generated using
the EPA's ERT. Alternatively, you may submit an electronic file
consistent with the extensible markup language (XML) schema listed on
the EPA's ERT website. Data collected using test methods that are not
supported by the EPA's ERT as listed on the EPA's ERT website at the
time of the test must be included as an attachment in the ERT or an
alternate electronic file.
(f) Requirements for electronically submitting reports. If you are
required to submit notifications or reports following the procedures
specified in this paragraph (f), you must submit notifications or
reports to the EPA via CEDRI, which can be accessed through the EPA's
Central Data Exchange (CDX) (https://cdx.epa.gov/). The EPA will make
all the information submitted through CEDRI available to the public
without further notice to you. Do not use CEDRI to submit information
you claim as confidential business information (CBI). Although we do
not expect persons to assert a claim of CBI, if you wish to assert a
CBI claim for some of the information in the report, you must submit a
complete file in the format specified in this subpart, including
information claimed to be CBI, to the EPA following the procedures in
paragraphs (f)(1) and (2) of this section. Clearly mark the part or all
of the information that you claim to be CBI. Information not marked as
CBI may be authorized for public release without prior notice.
Information marked as CBI will not be disclosed except in accordance
with procedures set forth in 40 CFR part 2. All CBI claims must be
asserted at the time of submission. Anything submitted using CEDRI
cannot later be claimed CBI. Furthermore, under CAA section 114(c),
emissions data are not entitled to confidential treatment, and the EPA
is required to make emissions data available to the public. Thus,
emissions data will not be protected as CBI and will be made publicly
available. You must submit the same file submitted to the CBI office
with the CBI omitted to the EPA via the EPA's CDX as described earlier
in this paragraph (f).
(1) The preferred method to receive CBI is for it to be transmitted
electronically using email attachments, File Transfer Protocol, or
other online file sharing services. Electronic submissions must be
transmitted directly to the OAQPS CBI Office at the email address
[email protected], and as described above, should include clear CBI
markings. ERT files should be flagged to the attention of the
Measurement Policy Group Leader and all other files should be flagged
to the attention of the NSPS Kc Rule Lead. If assistance is needed with
submitting large electronic files that exceed the file size limit for
email attachments, and if you do not have your own file sharing
service, please email [email protected] to request a file transfer link.
(2) If you cannot transmit the file electronically, you may send
CBI information through the postal service to the following address:
U.S. EPA, Attn: OAQPS Document Control Officer, Mail Drop: C404-02, 109
T.W. Alexander Drive, P.O. Box 12055, RTP, NC 27711. ERT files should
be sent to the secondary attention of the Measurement Policy Group
Leader and all other files should be sent to the secondary attention of
the NSPS Kc Rule Lead. The mailed CBI material should be double wrapped
and clearly marked. Any CBI markings should not show through the outer
envelope.
(g) Claims of EPA system outage. If you are required to
electronically submit a report through CEDRI in the EPA's CDX, you may
assert a claim of EPA system outage for failure to timely comply with
that reporting requirement. To assert a claim of EPA system outage, you
must meet the requirements outlined in paragraphs (g)(1) through (7) of
this section.
[[Page 83336]]
(1) You must have been or will be precluded from accessing CEDRI
and submitting a required report within the time prescribed due to an
outage of either the EPA's CEDRI or CDX systems.
(2) The outage must have occurred within the period of time
beginning 5 business days prior to the date that the submission is due.
(3) The outage may be planned or unplanned.
(4) You must submit notification to the Administrator in writing as
soon as possible following the date you first knew, or through due
diligence should have known, that the event may cause or has caused a
delay in reporting.
(5) You must provide to the Administrator a written description
identifying:
(i) The date(s) and time(s) when CDX or CEDRI was accessed and the
system was unavailable;
(ii) A rationale for attributing the delay in reporting beyond the
regulatory deadline to EPA system outage;
(iii) A description of measures taken or to be taken to minimize
the delay in reporting; and
(iv) The date by which you propose to report, or if you have
already met the reporting requirement at the time of the notification,
the date you reported.
(6) The decision to accept the claim of EPA system outage and allow
an extension to the reporting deadline is solely within the discretion
of the Administrator.
(7) In any circumstance, the report must be submitted
electronically as soon as possible after the outage is resolved.
(h) Claims of force majeure. If you are required to electronically
submit a report through CEDRI in the EPA's CDX, you may assert a claim
of force majeure for failure to timely comply with that reporting
requirement. To assert a claim of force majeure, you must meet the
requirements outlined in paragraphs (h)(1) through (5) of this section.
(1) You may submit a claim if a force majeure event is about to
occur, occurs, or has occurred or there are lingering effects from such
an event within the period of time beginning 5 business days prior to
the date the submission is due. For the purposes of this section, a
force majeure event is defined as an event that will be or has been
caused by circumstances beyond the control of the affected facility,
its contractors, or any entity controlled by the affected facility that
prevents you from complying with the requirement to submit a report
electronically within the time period prescribed. Examples of such
events are acts of nature (e.g., hurricanes, earthquakes, or floods),
acts of war or terrorism, or equipment failure or safety hazard beyond
the control of the affected facility (e.g., large scale power outage).
(2) You must submit notification to the Administrator in writing as
soon as possible following the date you first knew, or through due
diligence should have known, that the event may cause or has caused a
delay in reporting.
(3) You must provide to the Administrator:
(i) A written description of the force majeure event;
(ii) A rationale for attributing the delay in reporting beyond the
regulatory deadline to the force majeure event;
(iii) A description of measures taken or to be taken to minimize
the delay in reporting; and
(iv) The date by which you propose to report, or if you have
already met the reporting requirement at the time of the notification,
the date you reported.
(4) The decision to accept the claim of force majeure and allow an
extension to the reporting deadline is solely within the discretion of
the Administrator.
(5) In any circumstance, the reporting must occur as soon as
possible after the force majeure event occurs.
Sec. 60.117c Delegation of authority.
(a) In delegating implementation and enforcement authority of this
subpart to a State, local, or Tribal agency under section 111(c) of the
Act, the authorities contained in paragraph (b) of this section shall
be retained by the Administrator of U.S. EPA and cannot be transferred
to the State, local, or Tribal agency.
(b) Authorities which will not be delegated to State, local, or
Tribal agencies: Sec. Sec. 60.113c(d)(1)(iv) and 60.114c and approval
of an alternative to any electronic reporting to the EPA required by
this subpart.
[FR Doc. 2024-22823 Filed 10-11-24; 8:45 am]
BILLING CODE 6560-50-P