Energy Conservation Program: Test Procedure for Air-Cooled, Evaporatively-Cooled, and Water-Cooled Commercial Package Air Conditioners and Heat Pumps, 43986-44049 [2024-08543]
Download as PDF
43986
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE–2023–BT–TP–0014]
RIN 1904–AD93
Energy Conservation Program: Test
Procedure for Air-Cooled,
Evaporatively-Cooled, and WaterCooled Commercial Package Air
Conditioners and Heat Pumps
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
The U.S. Department of
Energy (‘‘DOE’’) is amending the Federal
test procedures for air-cooled
commercial package air conditioners
and heat pumps with a rated cooling
capacity greater than or equal to 65,000
Btu/h, evaporatively-cooled commercial
package air conditioners, and watercooled commercial package air
conditioners to incorporate by reference
the latest versions of the applicable
industry test standards. Specifically,
DOE is amending the current test
procedure for this equipment for
measuring the current cooling and
heating metrics—integrated energy
efficiency ratio (‘‘IEER’’) and coefficient
of performance (‘‘COP’’), respectively;
and establishing a new test procedure
for this equipment that adopts two new
metrics—integrated ventilation,
economizer, and cooling (‘‘IVEC’’) and
integrated ventilation and heating
efficiency (‘‘IVHE’’). Testing to the IVEC
and IVHE metrics will not be required
until such time as compliance is
required with any amended energy
conservation standard based on the new
metrics. Additionally, DOE is amending
certain provisions of DOE’s regulations
related to representations and
enforcement for the subject equipment.
DATES: The effective date of this rule is
August 5, 2024. The amendments will
be mandatory for testing the subject
equipment starting May 15, 2025.
The incorporation by reference of
certain material listed in this rule is
approved by the Director of the Federal
Register on August 5, 2024. The
incorporation by reference of certain
other materials listed in this rule were
approved by the Director of the Federal
Register as of January 22, 2016.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
webinar attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at www.regulations.gov under
docket number EERE–2023–BT–TP–
lotter on DSK11XQN23PROD with RULES2
SUMMARY:
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
0014. All documents in the docket are
listed in the www.regulations.gov index.
However, not all documents listed in
the index may be publicly available,
such as those containing information
that is exempt from public disclosure.
A link to the docket web page can be
found at www.regulations.gov/docket/
EERE-2023-BT-TP-0014. The docket
web page contains instructions on how
to access all documents, including
public comments, in the docket.
For further information on how to
review the docket, contact the
Appliance and Equipment Standards
Program staff at (202) 287–1445 or by
email: ApplianceStandardsQuestions@
ee.doe.gov.
FOR FURTHER INFORMATION CONTACT: Mr.
Troy Watson, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, EE–5B, 1000
Independence Avenue SW, Washington,
DC 20585–0121. Telephone: (240) 449–
9387. Email: ApplianceStandards
Questions@ee.doe.gov.
Mr. Eric Stas, U.S. Department of
Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue SW,
Washington, DC 20585–0121.
Telephone: (202) 586–4798. Email:
Eric.Stas@hq.doe.gov.
For further information on how to
review the docket, contact the
Appliance and Equipment Standards
Program staff at (202) 287–1445 or by
email: ApplianceStandardsQuestions@
ee.doe.gov.
SUPPLEMENTARY INFORMATION: DOE
maintains a previously approved
incorporation by reference and
incorporates by reference the following
industry standards into parts 429 and
431:
AHRI Standard 340/360–2022 (I–P),
2022 Standard for Performance Rating
of Commercial and Industrial Unitary
Air-conditioning and Heat Pump
Equipment, AHRI-approved January 26,
2022 (‘‘AHRI 340/360–2022’’).
AHRI Standard 1340–2023 (I–P), 2023
Standard for Performance Rating of
Commercial and Industrial Unitary Airconditioning and Heat Pump
Equipment, AHRI-approved November
16, 2023 (‘‘AHRI 1340–2023’’).
Copies of AHRI 340/360–2022 and
AHRI 1340–2023 can be obtained from
the Air-Conditioning, Heating, and
Refrigeration Institute (‘‘AHRI’’), 2311
Wilson Blvd., Suite 400, Arlington, VA
22201, (703) 524–8800, or online at:
www.ahrinet.org/standards/searchstandards.
ANSI/ASHRAE Standard 37–2009,
Methods of Testing for Rating
Electrically Driven Unitary Air-
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
Conditioning and Heat Pump
Equipment, ASHRAE-approved June 24,
2009 (‘‘ANSI/ASHRAE 37–2009’’).
Copies of ANSI/ASHRAE 37–2009
can be obtained from the American
Society of Heating, Refrigerating and
Air-Conditioning Engineers
(‘‘ASHRAE’’), 180 Technology Parkway
NW, Peachtree Corners, GA 30092, (404)
636–8400, or online at: www.ashrae.org.
See section IV.N of this document for
a further discussion of these standards.
Table of Contents
I. Synopsis of the Final Rule
II. Authority and Background
A. Authority
B. Background
III. Discussion
A. Scope of Applicability
B. Definitions
1. CUAC and CUHP Definition
2. Basic Model Definition
3. Double-Duct Definition
4. Metric Definitions
C. Updates to Industry Standards
1. AHRI 340/360
2. AHRI 1340
3. ASHRAE 37
D. Term Sheet Recommendations and
Metrics
1. IVEC
2. IVHE
E. DOE Adopted Test Procedures and
Comments Received
1. Overall
2. Double-Duct Systems
3. ECUACs and WCUACs
a. Overall
b. ESP Requirements for ECUACs and
WCUACs
c. ECUAC and WCUAC Test Temperatures
and WCUAC Heat Rejection Components
4. IVHE for Colder Climates
5. Test Conditions Used for Current
Metrics in Appendix A
6. Test Conditions Used for New Metrics in
Appendix A1
7. Provisions Introduced in the AHRI
1340–202X Draft
a. Cooling Weighting Factors Adjustment
b. ESP Testing Target Calculation
c. Test Instructions for Splitting ESP
Between Return and Supply Duct
d. Default Fan Power and Maximum
Pressure Drop for Coil-Only Systems
e. Component Power Measurement
f. Non-Standard Low-Static Indoor Fan
Motors
g. IVHE Equations
8. Heating Test Provisions Not Included in
the AHRI 1340–202X Draft
a. General
b. Definitions of Heating Operating Levels
c. Boost2 Heating Operating Level and
COP25
d. Extrapolation of Boost Heating
Operating Level to 21 °F
e. Operating Levels Used for Optional
COP217 Representations
9. Test Procedure Revisions Recommended
for a Future Rulemaking
F. Configuration of Unit Under Test
1. Summary
2. Background
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
3. Proposed Approach for Exclusion of
Certain Components
a. Components Addressed Through Test
Provisions of 10 CFR Part 431, Subpart
F, Appendices A and A1
b. Components Addressed Through
Representation Provisions of 10 CFR
429.43
c. Enforcement Provisions of 10 CFR
429.134
d. Testing Specially Built Units That Are
Not Distributed in Commerce
4. Updates in AHRI 1340–2023
5. Comments Received and Adopted
Provisions
a. Overall Approach
b. Coated Coils
G. Represented Values
1. Cooling Capacity
a. Representations of Cooling Capacity
b. Verification of Cooling Capacity
2. AEDM Tolerance for IVEC and IVHE
3. Minimum Part-Load Airflow
H. Enforcement Procedure for Verifying
Cut-In and Cut-Out Temperatures
I. Organization of the Regulatory Text for
CUACs and CUHPs
J. Effective and Compliance Dates
K. Test Procedure Costs and Impact
1. Appendix A
2. Appendix A1
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866,
13563, and 14094
B. Review Under the Regulatory Flexibility
Act
1. Estimate of Small Entities Regulated
2. Description and Estimate of Compliance
Requirements
a. Cost and Compliance Associated With
Appendix A
b. Cost and Compliance Associated With
Appendix A1
3. Significant Alternatives to the Rule
4. Certification Statement
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by
Reference
V. Approval of the Office of the Secretary
I. Synopsis of the Final Rule
In this final rule, DOE updates its test
procedures for CUACs and CUHPs by:
(1) updating the reference in the Federal
test procedure to the most recent
version of the industry test procedure,
AHRI 340/360–2022, for measuring
integrated energy efficiency ratio
(‘‘IEER’’), energy efficiency ratio
(‘‘EER’’), and coefficient of performance
(‘‘COP’’), consistent with the latest
version of ASHRAE Standard 90.1; and
(2) establishing a new test procedure
that references a new industry test
procedure, AHRI 1340–2023, which is
consistent with recommendations from
the ACUAC and ACUHP Working Group
TP Term Sheet, including ones for the
adoption of new efficiency metrics (i.e.,
integrated ventilation, economizer, and
cooling (‘‘IVEC’’) and integrated
ventilation and heating efficiency
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
43987
(‘‘IVHE’’)) and new testing
requirements.
To implement the changes, DOE is: (1)
amending appendix A to incorporate by
reference AHRI 340/360–2022 for
CUACs and CUHPs, while maintaining
the current efficiency metrics (i.e., EER,
IEER, and COP); and (2) adding a new
appendix A1 to subpart F of 10 CFR part
431. At 10 CFR 431.96, ‘‘Uniform test
method for the measurement of energy
efficiency of commercial air
conditioners and heat pumps,’’ DOE is
listing appendix A1 as the applicable
test method for CUACs and CUHPs for
any subsequent energy conservation
standards denominated in terms of IVEC
and IVHE. Appendix A1 utilizes AHRI
1340–2023, including the new IVEC and
IVHE efficiency metrics recommended
by the ACUAC and ACUHP Working
Group TP Term Sheet. Use of appendix
A1 will not be required until such time
as compliance is required with any
amended energy conservation standard
based on the new metrics, should DOE
adopt such standards. After the date on
which compliance with appendix A1 is
required, appendix A will no longer be
used as part of the Federal test
procedure. DOE is also amending
certain provisions within DOE’s
regulations for representation and
enforcement consistent with the test
procedure amendments.
Table I–1 summarizes the adopted
amendments to the DOE test procedure
for CUACs and CUHPs, the test
procedure provision prior to the
amendment, and the reason for each
adopted change.
E:\FR\FM\20MYR2.SGM
20MYR2
43988
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
Table 1-1 Summary of Chan2es in the Amended Test Procedure
Attribution
Incorporates by reference AHRI 340/3602022 and ANSI/ASHRAE 37-2009 in
appendix A. Incorporates by reference
AHRI 1340-2023 and ANSI/ASHRAE 372009 in a new appendix A 1.
Update to the
most recent
industry test
procedures.
Maintains appendix A with provisions for
determining EER, IEER, and COP.
Establishes appendix Al with provisions
for determining EER2, COP2, IVEC, and
IVHE.
Establish test
procedure for new
efficiency metrics
recommended by
the Working
Group.
Improve
representativeness
oftest procedure.
Does not include certain CUAC and
CUHP provisions regarding overrating capacity and specific
components for determination of
represented values in 10 CFR
429.43.
Includes provisions in 10 CFR 429.43
specific to CUACs and CUHPs to
determine represented values for units with
specific components (applies to
representations of IVEC and IVHE in
accordance with appendix A 1 only), and to
prevent cooling capacity over-rating.
Does not include certain CUAC- and
CUHP-specific enforcement
provisions in 10 CFR 429.134.
Adopts product-specific enforcement
provisions for CUACs and CUHPs
regarding: (1) testing of units with specific
components; and (2) verification of cut-in
and cut-out temperatures.
DOE has determined that the
amendments to appendix A will not
alter the measured efficiency of CUACs
and CUHPs or require retesting or
recertification solely as a result of DOE’s
adoption of the amendments to the test
procedure. Additionally, DOE has
determined that the amendments to
appendix A will not increase the cost of
testing. Representations of energy use or
energy efficiency will be required to be
based on testing in accordance with the
amended test procedure in appendix A
beginning 360 days after the date of
publication of this test procedure final
rule in the Federal Register.
DOE has determined that the new test
procedure at appendix A1 will alter the
measured efficiency of CUACs and
CUHPs and, as a result, manufacturers
would need to retest, or rerun the
alternative efficiency determination
method where allowed, prior to making
any representations under the test
procedure in appendix A1. Cost
estimates for retesting are discussed in
section III.K of this document. As
discussed, use of appendix A1 will not
be required until the compliance date of
any amended energy conservation
VerDate Sep<11>2014
Amended Test Procedure
19:59 May 17, 2024
Jkt 262001
standard denominated in terms of the
new metrics in appendix A1, should
DOE adopt such standards.
The amendments to representation
requirements in 10 CFR 429.43 will not
be required until either 360 days after
publication in the Federal Register of
this test procedure final rule or
beginning on the compliance date of
amended standards for CUACs and
CUHPs based on IVEC and IVHE (as
applicable), depending on the specific
provisions.
The effective date for the amended
test procedures adopted in this final
rule is 75 days after publication of this
document in the Federal Register.
II. Authority and Background
Small, large, and very large
commercial package air conditioning
and heating equipment are included in
the list of ‘‘covered equipment’’ for
which DOE is authorized to establish
and amend energy conservation
standards and test procedures. (42
U.S.C. 6311(1)(B)–(D)) Commercial
package air conditioning and heating
equipment includes as equipment
categories air-cooled commercial
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
Clarify how DOE
will conduct
enforcement
testing.
unitary air conditioners with a rated
cooling capacity greater than or equal to
65,000 Btu/h (‘‘ACUACs’’) and aircooled commercial unitary heat pumps
with a rated cooling capacity greater
than or equal to 65,000 Btu/h
(‘‘ACUHPs’’), evaporatively-cooled
commercial unitary air conditioners
(‘‘ECUACs’’), and water-cooled
commercial unitary air conditioners
(‘‘WCUACs’’), which are the subject of
this final rule.1 (ECUACs, WCUACs,
ACUACs, and ACUHPs, which includes
double-duct equipment, are collectively
referred to as ‘‘CUACs and CUHPs’’ in
this document.) DOE’s test procedures
for CUACs and CUHPs are currently
prescribed at title 10 of the Code of
Federal Regulations (‘‘CFR’’), part 431,
subpart F, § 431.96, table 1. The
following sections discuss DOE’s
1 While ACUACs with a rated cooling capacity
less than 65,000 Btu/h are included in the broader
category of CUACs, they are not addressed in this
final rule. The test procedure for ACUACs with
rated cooling capacity less than 65,000 Btu/h have
been addressed in a separate rulemaking: see
Docket No. EERE–2017–BT–TP–0031. All
references within this final rule to ACUACs and
ACUHPs exclude equipment with rated cooling
capacity less than 65,000 Btu/h.
E:\FR\FM\20MYR2.SGM
20MYR2
ER20MY24.126
lotter on DSK11XQN23PROD with RULES2
DOE Test Procedure Prior to
Amendment
Incorporates by reference:
1. ANSI/AHRI 340/360-2007 for
CUACs and CUHPs with a cooling
capacity greater than or equal to
65,000 Btu/h; and
2. ANSI/AHRI 210/240-2008 for
ECUACs and WCUACs with a
cooling capacity less than 65,000
Btu/h.
Includes provisions for determining
EER, IEER, and COP.
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
authority to establish and amend test
procedures for CUACs and CUHPs and
relevant background information
regarding DOE’s amendments to the test
procedures for this equipment.
lotter on DSK11XQN23PROD with RULES2
A. Authority
The Energy Policy and Conservation
Act, Public Law 94–163 (42 U.S.C.
6291–6317, as codified), as amended
(‘‘EPCA’’),2 authorizes DOE to regulate
the energy efficiency of a number of
consumer products and certain
industrial equipment. Title III, Part C 3
of EPCA, added by Public Law 95–619,
Title IV, section 441(a), established the
Energy Conservation Program for
Certain Industrial Equipment, which
sets forth a variety of provisions
designed to improve energy efficiency.
This covered equipment includes small,
large, and very large commercial
package air conditioning and heating
equipment. (42 U.S.C. 6311(1)(B)–(D))
Commercial package air conditioning
and heating equipment includes CUACs
and CUHPs, the subject of this
document.
The energy conservation program
under EPCA consists essentially of four
parts: (1) testing; (2) labeling; (3) Federal
energy conservation standards, and (4)
certification and enforcement
procedures. Relevant provisions of
EPCA include definitions (42 U.S.C.
6311), energy conservation standards
(42 U.S.C. 6313), test procedures (42
U.S.C. 6314), labeling provisions (42
U.S.C. 6315), and the authority to
require information and reports from
manufacturers (42 U.S.C. 6316; 42
U.S.C. 6296).
The Federal testing requirements
consist of test procedures that
manufacturers of covered equipment
must use as the basis for: (1) certifying
to DOE that their equipment complies
with the applicable energy conservation
standards adopted pursuant to EPCA (42
U.S.C. 6316(b); 42 U.S.C. 6296), and (2)
making other representations about the
efficiency of that equipment (42 U.S.C.
6314(d)). Similarly, DOE uses these test
procedures to determine whether the
equipment complies with relevant
standards promulgated under EPCA.
Federal energy efficiency
requirements for covered equipment
established under EPCA generally
supersede State laws and regulations
concerning energy conservation testing,
labeling, and standards. (42 U.S.C.
2 All references to EPCA in this document refer
to the statute as amended through the Energy Act
of 2020, Public Law 116–260 (Dec. 27, 2020), which
reflect the last statutory amendments that impact
Parts A and A–1 of EPCA.
3 For editorial reasons, upon codification in the
U.S. Code, Part C was redesignated Part A–1.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
6316(a) and (b); 42 U.S.C. 6297) DOE
may, however, grant waivers of Federal
preemption in limited circumstances for
particular State laws or regulations, in
accordance with the procedures and
other provisions of EPCA. (42 U.S.C.
6316(b)(2)(D))
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered equipment.
Specifically, EPCA requires that any test
procedures prescribed or amended
under this section must be reasonably
designed to produce test results which
reflect energy efficiency, energy use, or
estimated annual operating cost of a
given type of covered equipment (or
class thereof) during a representative
average use cycle (as determined by the
Secretary) and requires that such test
procedures not be unduly burdensome
to conduct. (42 U.S.C. 6314(a)(2)–(3))
EPCA generally requires that, at least
once every seven years, DOE evaluate
test procedures for each type of covered
equipment, including CUACs and
CUHPs, to determine whether amended
test procedures would more accurately
or fully comply with the requirements
for the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 6314(a)(1)–(3))
DOE refers to these provisions as the
‘‘lookback’’ provisions and rulemakings
conducted under these provisions as
‘‘lookback’’ rulemakings.
Specific to certain commercial
equipment, including CUACs and
CUHPs, EPCA requires that the test
procedures be those generally accepted
industry testing procedures or rating
procedures developed or recognized by
AHRI or ASHRAE, as referenced in
ASHRAE Standard 90.1, ‘‘Energy
Standard for Buildings Except Low-Rise
Residential Buildings’’ (‘‘ASHRAE
Standard 90.1’’). (42 U.S.C.
6314(a)(4)(A)) Further, if such an
industry test procedure is amended,
DOE must update its test procedure to
be consistent with the amended
industry test procedure unless DOE
determines, by rule published in the
Federal Register and supported by clear
and convincing evidence, that the
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden, in which case DOE may
establish an amended test procedure
that does satisfy those statutory
provisions. (42 U.S.C. 6314(a)(4)(B) and
(C)) DOE refers to these provisions as
the ‘‘ASHRAE trigger’’ provisions and
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
43989
rulemakings conducted under these
provisions as ‘‘ASHRAE trigger’’
rulemakings. As noted in the recent
update to DOE’s procedures,
interpretations, and policies for
consideration of new or amended
energy conservation standards and test
procedures, DOE considers an ASHRAE
trigger to occur only when ASHRAE
Standard 90.1 is updated to include an
amended industry test procedure, and
that referenced test procedure includes
amendments relative to the existing
DOE test procedure. 89 FR 24340, 24351
(April 8, 2024).
Whether pursuant to the lookback
provision or the trigger provision, if
DOE determines that a test procedure
amendment is warranted, the
Department must publish proposed test
procedures in the Federal Register, and
afford interested persons an opportunity
(of not less than 45 days duration) to
present oral and written data, views,
and arguments on the proposed test
procedures. (42 U.S.C. 6314(b)) If DOE
determines that test procedure revisions
are not appropriate, DOE must publish
in the Federal Register its
determination not to amend the test
procedures. (42 U.S.C. 6314(a)(1)(A)(ii))
DOE is publishing this final rule in
satisfaction of its aforementioned
statutory obligations under EPCA.
Specifically, in accordance with the
ASHRAE trigger provisions at 42 U.S.C.
6314(a)(4)(B), DOE is updating appendix
A to reference the most recent version
of the industry test procedure, AHRI
340/360–2022, which was adopted in
ASHRAE Standard 90.1–2022, and
which includes amendments relative to
the existing Federal test procedure at
appendix A to subpart F to 10 CFR part
431.4 Pursuant to section 6314(a)(4)(B),
DOE also evaluated whether AHRI 340/
360–2022 could provide representative
results for the new efficiency metrics
recommended by the Working Group
(i.e., IVEC and IVHE). While AHRI 340/
360–2022 provides representative
results for the current energy efficiency
metrics, IEER, EER, and COP, it does not
include, among other things, operating
modes other than mechanical-coolingonly operation in the cooling metric,
part-load heating tests, higher ESP
requirements, or crankcase heater
operation, which are integral to the
IVEC and IVHE metrics recommended
4 As discussed in section I.B of this document,
DOE was also triggered by updated industry test
procedures in ASHRAE Standard 90.1–2016 and
ASHRAE Standard 90.1–2019, both of which
included amendments relative to the existing
Federal test procedure. However, ASHRAE
Standard 90.1–2022, and its referenced industry test
procedure, AHRI 340/360–2022, supersedes these
previous versions.
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
43990
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
by the Working Group. A more complete
discussion of the differences between
the current efficiency metrics and the
IVEC and IVHE efficiency metrics can
be found in section III.D. Accordingly,
as detailed below, DOE has determined,
supported by clear and convincing
evidence, that AHRI 340/360–2022
cannot provide representative energy
use results for the IVEC and IVHE
efficiency metrics.
As a result, consistent with 42 U.S.C.
6314(a)(4)(C), DOE is establishing a new
test procedure, appendix A1, to measure
energy use for the IVEC and IVHE
efficiency metrics. DOE has determined
that appendix A1 is reasonably designed
to reflect energy use for the IVEC and
IVHE efficiency metrics during a
representative average use cycle without
being unduly burdensome to conduct.
(See 42 U.S.C. 6314(a)(4)(C); id. section
6314 (a)(2)) In particular, DOE notes that
appendix A1 includes: (1) a more
mathematically accurate representation
of cooling efficiency; (2) an integrated
heating metric rather than the singlepoint full-load COP metric, which
includes performance at multiple
outdoor air temperatures as well as
other operating modes not previously
accounted for in the COP metric (i.e.,
part-load heating, heating-season
ventilation hours, unoccupied no-load
hours, and supplemental electric
resistance heat operation); (3) operating
modes other than mechanical-coolingonly operation in the cooling metric
(i.e., integrated mechanical and
economizer cooling, economizer-only
cooling, cooling season ventilation,
unoccupied no-load hours); (4) higher
external static pressure (‘‘ESP’’)
requirements; (5) crankcase heater
operation; and (6) oversizing of units in
field installations.
As DOE has determined that the
updated version of the industry test
procedure, AHRI 340/360–2022,
adopted in appendix A is more
representative than the previous version
of the test procedure referenced in
appendix A (because it would more
fully comply with the requirements that
the test procedure be not unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle) and because the test
procedure adopted in appendix A1 is
more representative for the new IVEC
and IVHE metrics, this rulemaking also
satisfies DOE’s obligations under the
lookback provisions at 42 U.S.C.
6314(a)(1)(A). For more details on the
improved representativeness of AHRI
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
340/360–2022, see section III.E of this
document.
B. Background
DOE’s existing test procedure for
CUACs and CUHPs appears at 10 CFR
431.96 (Uniform test method for the
measurement of energy efficiency of
commercial air conditioners and heat
pumps). The test procedure for ACUACs
and ACUHPs with a rated cooling
capacity of greater than or equal to
65,000 Btu/h specified in 10 CFR 431.96
references appendix A to subpart F of
part 431 (‘‘Uniform Test Method for the
Measurement of Energy Consumption of
Air-Cooled Small (≥65,000 Btu/h),
Large, and Very Large Commercial
Package Air Conditioning and Heating
Equipment,’’ referred to as ‘‘appendix
A’’ in this document). Appendix A
references certain sections of ANSI/
AHRI Standard 340/360–2007, ‘‘2007
Standard for Performance Rating of
Commercial and Industrial Unitary AirConditioning and Heat Pump
Equipment,’’ approved by ANSI on
October 27, 2011 and updated by
addendum 1 in December 2010 and
addendum 2 in June 2011 (‘‘ANSI/AHRI
340/360–2007’’); ANSI/ASHRAE
Standard 37–2009, ‘‘Methods of Testing
for Rating Electrically Driven Unitary
Air-Conditioning and Heat Pump
Equipment’’ (‘‘ANSI/ASHRAE 37–
2009’’); and specifies other test
procedure requirements related to
minimum external static pressure
(‘‘ESP’’), optional break-in period,
refrigerant charging, setting indoor
airflow, condenser head pressure
controls, standard airflow and air
quantity, tolerance on capacity at partload test points, and condenser air inlet
temperature for part-load tests.
The DOE test procedure for ECUACs
and WCUACs with a rated cooling
capacity of greater than or equal to
65,000 Btu/h specified in 10 CFR 431.96
incorporates by reference ANSI/AHRI
340/360–2007, excluding section 6.3 of
ANSI/AHRI 340/360–2007 and
including paragraphs (c) and (e) of 10
CFR 431.96.5 The DOE test procedure
for ECUACs and WCUACs with a rated
cooling capacity of less than 65,000 Btu/
h incorporates by reference ANSI/AHRI
Standard 210/240–2008, ‘‘2008
Standard for Performance Rating of
Unitary Air-Conditioning & Air-Source
Heat Pump Equipment,’’ approved by
ANSI on October 27, 2011 and updated
by addendum 1 in June 2011 and
addendum 2 in March 2012 (‘‘ANSI/
AHRI 210/240–2008’’), excluding
section 6.5 of ANSI/AHRI 210/240–2008
and including paragraphs (c) and (e) of
10 CFR 431.96.
On October 26, 2016, ASHRAE
published ASHRAE Standard 90.1–
2016, which included updates to the
test procedure references for CUACs and
CUHPs (excluding CUACs and CUHPs
with a rated cooling capacity less than
65,000 Btu/h) to reference AHRI
Standard 340/360–2015, ‘‘2015
Standard for Performance Rating of
Commercial and Industrial Unitary AirConditioning and Heat Pump
Equipment’’ (‘‘AHRI 340/360–2015’’).6
This action by ASHRAE triggered DOE’s
obligations under 42 U.S.C.
6314(a)(4)(B), as outlined previously
because AHRI 340/360–2015 included
substantive changes compared to the
current DOE test procedure at appendix
A to subpart F of 10 CFR part 431. On
July 25, 2017, DOE published a request
for information (‘‘RFI’’) (‘‘July 2017 TP
RFI’’) in the Federal Register to collect
information and data to consider
amendments to DOE’s test procedures
for certain categories of commercial
package air conditioning and heating
equipment including CUACs and
CUHPs. 82 FR 34427.
At the time DOE published the July
2017 TP RFI, the applicable version of
ASHRAE Standard 90.1 was the 2016
edition, which referenced AHRI
Standard 340/360–2015, ‘‘2015
Standard for Performance Rating of
Commercial and Industrial Unitary AirConditioning and Heat Pump
Equipment’’ as the test procedure for
CUACs and CUHPs. However, on
October 24, 2019, ASHRAE published
ASHRAE Standard 90.1–2019, which
updated the relevant AHRI Standard
340/360 reference to the 2019 edition,
‘‘2019 Standard for Performance Rating
of Commercial and Industrial Unitary
Air-Conditioning and Heat Pump
Equipment’’ (‘‘AHRI 340/360–2019’’).
This action by ASHRAE again triggered
DOE’s obligations under 42 U.S.C.
6314(a)(4)(B), as outlined previously,
because AHRI 340/360–2019 included
substantive changes compared to the
current DOE test procedure at appendix
A to subpart F of 10 CFR part 431. In
January 2022, AHRI published
additional updates to its test procedure
standard for CUACs and CUHPs, with
the publication of AHRI Standard 340/
360–2022, ‘‘2022 Standard for
Performance Rating of Commercial and
Industrial Unitary Air-conditioning and
Heat Pump Equipment’’ (‘‘AHRI 340/
360–2022’’), which DOE references in
5 Paragraphs (c) and (e) of 10 CFR 431.96 address
optional break-in provisions and additional
provisions regarding set-up, respectively.
6 The previous version of ASHRAE Standard 90.1
(i.e., ASHRAE Standard 90.1–2013) references
ANSI/AHRI 340/360–2007.
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
the amended test procedure in appendix
A to subpart F of 10 CFR part 431, as
established in this final rule.
For ECUACs and WCUACs with a
rated cooling capacity less than 65,000
Btu/h, ASHRAE Standard 90.1–2016
references ANSI/AHRI 210/240–2008,
which is referenced by the current
Federal test procedure at 10 CFR 431.96
for this equipment. After the publication
of the July 2017 RFI, AHRI published
AHRI Standard 210/240–2017, ‘‘2017
Standard for Performance Rating of
Unitary Air-conditioning & Air-source
Heat Pump Equipment’’ (‘‘AHRI 210/
240–2017’’). ASHRAE Standard 90.1–
2019 updated its reference to AHRI 210/
240–2017 as the test procedure for
ECUACs and WCUACs with rated
cooling capacities less than 65,000 Btu/
h. This action by ASHRAE triggered
DOE’s obligations under 42 U.S.C.
6314(a)(4)(B), as outlined previously,
because AHRI 210/240–2017 included
substantive changes compared to the
current DOE test procedure for ECUACs
and WCUACs with a rated cooling
capacity less than 65,000 Btu/h at 10
CFR 431.96. However, after the
publication of AHRI 210/240–2017,
AHRI released two updates to that
industry standard: (1) AHRI Standard
210/240–2017 with Addendum 1, ‘‘2017
Standard for Performance Rating of
Unitary Air-conditioning & Air-source
Heat Pump Equipment’’ (‘‘AHRI 210/
240–2017 with Addendum 1’’), which
was published in April 2019; and (2)
AHRI Standard 210/240–2023, ‘‘2023
Standard for Performance Rating of
Unitary Air-conditioning & Air-source
Heat Pump Equipment’’ (‘‘AHRI 210/
240–2023’’), which was published in
May 2020.7
On May 12, 2020, DOE published an
RFI in the Federal Register regarding
energy conservation standards for
ACUACs, ACUHPs, and commercial
lotter on DSK11XQN23PROD with RULES2
7 AHRI 210/240–2023 notes at the beginning of
the standard that while it was first published in
May 2020, it establishes a method to rate residential
central air conditioners and heat pumps consistent
with the Federal test procedure for residential
central air conditioners and heat pumps codified in
10 CFR part 430, subpart B, appendix M1
(‘‘appendix M1’’). Appendix M1 was required to be
used coincident with the January 1, 2023
compliance date of Federal energy conservation
standards denominated in terms of seasonal energy
efficiency ratio 2 (‘‘SEER2’’), energy efficiency ratio
2 (‘‘EER2’’), and heating seasonal performance
factor 2 (‘‘HSPF2’’). Therefore, despite being
published in May 2020, this version was named
AHRI 210/240–2023.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
warm air furnaces (‘‘May 2020 ECS
RFI’’). 85 FR 27941. In response to the
May 2020 ECS RFI, DOE received
comments from various stakeholders,
including ones related to the test
procedure for ACUACs and ACUHPs.
On May 25, 2022, DOE published an
RFI in the Federal Register regarding
test procedures and energy
conservations standards for CUACs and
CUHPs (‘‘May 2022 TP/ECS RFI’’). 87
FR 31743.
On July 29, 2022, DOE published in
the Federal Register a notice of intent
to establish a working group for
commercial unitary air conditioners and
heat pumps (‘‘Working Group’’) to
negotiate proposed test procedures and
amended energy conservation standards
for this equipment (‘‘July 2022 Notice of
Intent’’). 87 FR 45703. The Working
Group was established under the
Appliance Standards and Rulemaking
Federal Advisory Committee
(‘‘ASRAC’’) in accordance with the
Federal Advisory Committee Act
(FACA) (5 U.S.C. App 2) and the
Negotiated Rulemaking Act (‘‘NRA’’) (5
U.S.C. 561–570, Pub. L. 104–320). The
purpose of the Working Group was to
discuss, and if possible, reach
consensus on recommended
amendments to the test procedures and
energy conservation standards for
ACUACs and ACUHPs. The Working
Group consisted of 14 voting members,
including DOE. (See appendix A,
Working Group Members, to Document
No. 65 in Docket No. EERE–2022–BT–
STD–0015) On December 15, 2022, the
Working Group signed a term sheet of
recommendations regarding ACUAC
and ACUHP test procedures to be
submitted to ASRAC, the contents of
which are referenced throughout this
final rule (referred to hereafter as the
‘‘ACUAC and ACUHP Working Group
TP Term Sheet’’). (See Id.) The ACUAC
and ACUHP Working Group TP Term
Sheet was approved by ASRAC on
March 2, 2023. These recommendations
are discussed further in section III.D of
this final rule.
In January 2023, ASHRAE published
ASHRAE Standard 90.1–2022, which
included updates to the test procedure
references for CUACs and CUHPs with
cooling capacities greater than or equal
to 65,000 Btu/h, specifically referencing
AHRI 340/360–2022. For ECUACs and
WCUACs with capacities less than
65,000 Btu/h, ASHRAE Standard 90.1–
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
43991
2022 references AHRI 210/240–2023.
Notably, ECUACs and WCUACs with a
rated cooling capacity less than 65,000
Btu/h were removed from the scope of
AHRI 210/240–2023 and are instead
included in the scope of AHRI 340/360–
2022.8 DOE discusses this change in
scope to the industry test procedure and
comments received related to ECUACs
and WCUACs with a cooling capacity
less than 65,000 Btu/h in section III.E.3
of this final rule. These actions by
ASHRAE again triggered DOE’s
obligations under 42 U.S.C.
6314(a)(4)(B) for ACUACs and ACUHPs,
as outlined previously, because AHRI
340/360–2022 again included
substantive changes compared to the
current DOE test procedure at appendix
A to subpart F of 10 CFR 431. While
DOE was triggered previously with the
publication of ASHRAE 90.1–2016 and
ASHRAE 90.1–2019, the latest version,
ASHRAE 90.1–2022, and its referenced
industry test procedure, AHRI 340/360–
2022, supersedes these previous
versions. Therefore, in this final rule
DOE evaluated the amendments under
ASHRAE 90.1–2022 (i.e., AHRI 340/
360–2022) relative to the current
Federal test procedures for the CUACs
and CUHPs.
DOE published a notice of proposed
rulemaking (‘‘NOPR’’) in the Federal
Register on August 17, 2023, presenting
DOE’s proposals to amend the CUAC
and CUHP test procedure (‘‘August 2023
TP NOPR’’). 88 FR 56392. The August
2023 TP NOPR also summarized and
responded to comments pertaining to
test procedures for CUACs and CUHPs
received in response to the July 2017 TP
RFI, the May 2020 ECS RFI, and the
May 2022 TP/ECS RFI. Id. DOE held a
public webinar related to the August
2023 TP NOPR on September 7, 2023
(hereafter, the ‘‘NOPR public webinar’’).
DOE received comments in response
to the August 2023 TP NOPR from the
interested parties listed in Table II–1,
along with each commenter’s
abbreviated name used throughout this
final rule. Discussion of relevant
comments and DOE’s responses are
provided in appropriate sections of this
document.
8 ECUACs and WCUACs with a rated cooling
capacity greater than or equal to 65,000 Btu/h are
included in the scope of ANSI/AHRI 340/360–2007
and continue to be included in scope of the latest
version of AHRI 340/360 (i.e., AHRI 340/360–2022).
E:\FR\FM\20MYR2.SGM
20MYR2
43992
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
Table 11-1 List of Commenters with Written Submissions Relevant to the Test
Procedures for CUACs and CUHPs in Response to the August 2023 TP NOPR
lotter on DSK11XQN23PROD with RULES2
A parenthetical reference at the end of
a comment quotation or paraphrase
provides the location of the item in the
public record.9 To the extent that
interested parties have provided written
comments that are substantively
consistent with any oral comments
provided during the September 7, 2023
NOPR public webinar, DOE cites the
written comments throughout this final
rule. DOE did not identify any oral
comments provided during the NOPR
public webinar that are not
substantively addressed by written
comments.
In response to the August 2023 TP
NOPR, DOE received multiple
comments regarding energy
conservation standards for CUACs and
CUHPs, particularly regarding standards
for ECUACs, WCUACs, and double-duct
systems. Comments regarding energy
9 The parenthetical reference provides a reference
for information located in the docket of DOE’s
rulemaking to develop test procedures for CUACs
and CUHPs. (Docket No. EERE–2023–BT–TP–0014,
which is maintained at www.regulations.gov) The
references are arranged as follows: (commenter
name, comment docket ID number, page of that
document).
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
AHRI
Comment
No. in the
Commenter Type
Docket
Industry Trade
15
Association
ASAP&
ACEEE
11
Efficiency Advocacy
Organizations
CAIOUs
10
Utilities
Carrier
Lennox
8
9
NEEA
16
Manufacturer
Manufacturer
Efficiency Advocacy
Organization
NYSERDA
13
State Agency
Rheem
12
Manufacturer
Trane
14
Manufacturer
conservation standards are outside the
scope of consideration for this test
procedure rulemaking and are not
addressed in this final rule. Topics
related to energy conservation standards
for CUACs and CUHPs would be
addressed in separate rulemaking
processes.
Following the publication of the
August 2023 TP NOPR, AHRI published
AHRI Standard 1340–2023, ‘‘2023
Standard for Performance Rating of
Commercial and Industrial Unitary Airconditioning and Heat Pump
Equipment’’ (‘‘AHRI 1340–2023’’). This
is an update to AHRI Standard 340/360
that incorporates the recommendations
in the ACUAC and ACUHP Working
Group TP Term Sheet. This updated
industry standard has not yet been
adopted in ASHRAE Standard 90.1, and
as such does not constitute an ASHRAE
trigger, as outlined previously.
III. Discussion
In the following sections, DOE
outlines certain amendments to its test
procedures for CUACs and CUHPs. For
each amendment, DOE provides
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
relevant background information,
explains why the amendment is
necessary, discusses relevant public
comments, and discusses the approach
DOE has implemented.
A. Scope of Applicability
This rulemaking applies to ACUACs
and ACUHPs with a rated cooling
capacity greater than or equal to 65,000
Btu/h, including double-duct air
conditioners and heat pumps, as well as
ECUACs and WCUACs of all capacities.
Definitions that apply to CUACs and
CUHPs are discussed in section III.B of
this final rule.
DOE’s regulations for CUACs and
CUHPs cover both single-package units
and split systems. See the definition of
‘‘commercial package air-conditioning
and heating equipment’’ at 10 CFR
431.92. A split system consists of a
condensing unit—which includes a
condenser coil, condenser fan and
motor, and compressor—that is paired
with a separate component that includes
an evaporator coil to form a complete
refrigeration circuit for space
conditioning. One application for
E:\FR\FM\20MYR2.SGM
20MYR2
ER20MY24.127
Commenter(s)
Air-Conditioning, Heating, and
Refrigeration Institute
Appliance Standards Awareness
Project, American Council for
an Energv-Efficient Economy
Pacific Gas and Electric
Company, San Diego Gas and
Electric, and Southern
California Edison (collectively
referred to as the "California
Investor-Owned Utilities")
Carrier Corporation
Lennox International Inc.
Northwest Energy Efficiency
Alliance
New York State Energy
Research and Development
Authority
Rheem Manufacturing
Company
Trane Technologies
Reference in
this Final
Rule
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
condensing units is to be paired with an
air handler (which includes an
evaporator coil), such that the combined
system (i.e., the condensing unit with
air handler) meets the definition of a
split system CUAC or CUHP. It should
be pointed out that AHRI has a
certification program for unitary large
equipment that includes certification of
CUACs, CUHPs, and condensing units.
DOE notes that as part of the AHRI
certification program for unitary large
equipment, manufacturers who sell aircooled condensing units with a rated
cooling capacity greater than or equal to
65,000 Btu/h and less than 135,000 Btu/
h must certify condensing units as a
complete system (i.e., paired with an air
handler) according to the AHRI 340/360
test procedure.10 However, for
condensing units with a rated cooling
capacity greater than or equal to 135,000
Btu/h and less than 250,000 Btu/h, the
AHRI certification program allows
manufacturers to certify condensing
units as a complete system according to
AHRI 340/360 or optionally certify as a
condensing unit only according to AHRI
Standard 365, ‘‘Standard for
Performance Rating of Commercial and
Industrial Unitary Air-Conditioning
Condensing Units’’ (‘‘AHRI 365’’).
In the August 2023 TP NOPR, DOE
emphasized that these AHRI testing and
certification requirements differ from
the Federal test procedure at 10 CFR
431.96, which requires testing to ANSI/
AHRI 340/360–2007 and does not
permit certifying to DOE as a
condensing unit only according to AHRI
365. 88 FR 56392, 56398–56399 (August
17, 2023). Additionally, the AHRI
certification program does not include
unitary split systems or condensing
units with cooling capacities above
250,000 Btu/h, whereas the Federal test
procedure and standards (codified at 10
CFR 431.96 and 431.97, respectively)
cover all CUACs and CUHPs with
cooling capacities up to 760,000 Btu/h.
Once again, in the August 2023 TP
NOPR, DOE emphasized that
condensing unit models distributed in
commerce with air handlers with
cooling capacities up to 760,000 Btu/h
are covered as commercial package airconditioning and heating equipment
(see definition at 10 CFR 431.92), and as
such, they are subject to the Federal
regulations specified for CUACs and
CUHPs regarding test procedures (10
CFR 431.96), energy conservation
standards (10 CFR 431.97), and
10 See appendix A of the AHRI Unitary Large
Equipment Certification Program Operations
Manual (January 2024). This can be found at
www.ahrinet.org/system/files/2023-10/ULE_
OM.pdf.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
certification and representation
requirements (10 CFR 429.43). 88 FR
56392, 56398–56399 (August 17, 2023).
In response to the August 2023 TP
NOPR, DOE received several comments
regarding DOE’s clarification of
coverage of condensing units. Trane
commented that single-package and
split-system equipment are included in
the DOE regulation, but stated that the
AHRI certification program structure
specific to split systems exists for
several reasons. (Trane, No. 14 at p. 2)
Trane stated that split systems between
65,000 Btu/h and 250,000 Btu/h are
often matched sets, but split systems
between 135,000 Btu/h to 250,000 Btu/
h may be installed in applications
where a stand-alone condenser is
matched in the field with a nonmatched air-handling unit, which Trane
commented warrants a separate standalone condenser rating. Trane stated
that in larger split-system applications
(with capacities greater than 250,000
Btu/h) condensing units are often paired
with: (1) semi-custom and custom airhandling units that are unique to that
installation; (2) more than one airhandling unit, or (3) air-handling units
manufactured by different HVAC
manufacturers, or the system is built up
in the field and all controls for the
system are installed on site. Trane
asserted that even considering only the
air handlers offered by a single
manufacturer, there would be thousands
of condenser and air handler
combinations that would require testing,
alternative efficiency determination
method (‘‘AEDM’’) development, and
certification. Trane also stated that in
split-system replacements, condensing
units are often replaced more frequently
than the air-handling unit. Id.
AHRI commented that certifying
condensing units as a complete system
(paired with an air handler) is
appropriate for the capacity range
between 65,000 and 135,000 Btu/h, but
that rating models with capacities
greater than or equal to 135,000 Btu/h
as either a complete system (using AHRI
340/360) or as a condensing unit only
(using AHRI 365) allows manufacturers
to provide condensing units for
installation in a system that may be
connected to a number of different
indoor equipment types. (AHRI, No. 15
at pp. 4–5) AHRI commented that using
AHRI 365 to rate models allows
manufacturers to meet customer needs
when indoor equipment and controls
with which the condensing unit would
be paired in the field are not known.
AHRI stated that there is no procedure
in AHRI 340/360 nor AHRI 1340 for
rating outdoor units such as condensing
units without an indoor match.
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
43993
Furthermore, AHRI commented that
DOE had not investigated the impact of
this proposed change sufficiently and
asserted that there could be serious
consequences. Id.
In response to concerns raised by
AHRI and Trane, DOE emphasizes that
the clarification provided in the August
2023 TP NOPR regarding the coverage of
condensing units paired with air
handlers is not a change from the
existing requirements for rating these
models. Neither the current DOE test
procedure nor the amended test
procedures adopted in this final rule
reference AHRI 365 for testing or rating
condensing units only. Accordingly, in
this final rule, DOE reiterates that
condensing unit models distributed in
commerce with air handlers with
cooling capacities up to 760,000 Btu/h
are covered as commercial package airconditioning and heating equipment
(see definition at 10 CFR 431.92), and as
such, they are subject to the Federal
regulations specified for CUACs and
CUHPs regarding test procedures (10
CFR 431.96), energy conservation
standards (10 CFR 431.97), and
certification and representation
requirements (10 CFR 429.43).
Regarding Trane’s assertion as to the
extent of testing, AEDM development,
and certification needed, DOE notes that
its regulations do not require that
ratings for CUACs and CUHPs
(including split systems that comprise a
condensing unit and air handler) be
developed through testing, and that
AEDMs can be used to rate all such
systems. DOE further notes that to the
extent that manufacturers have
developed simulations of condensing
unit model performance in accordance
with AHRI 365, such simulations could
be used as the basis of an AEDM to rate
condensing units paired with air
handlers, provided the AEDM satisfies
the minimum requirements specified at
10 CFR 429.70(c).
B. Definitions
1. CUAC and CUHP Definition
As in this final rule, DOE has
previously used the colloquial terms
‘‘commercial unitary air conditioners’’
and ‘‘commercial unitary heat pump’’
(i.e., CUACs and CUHPs), to refer to
certain commercial package air
conditioning and heating equipment,
recognizing that CUAC is not a statutory
term and is not currently used in the
CFR. See 79 FR 58948, 58950 (Sept. 30,
2014); 80 FR 52676, 52676 (Sept. 1,
2015). As codified in regulation, the
classes for which EPCA prescribed
standards have been grouped under the
headings ‘‘commercial air conditioners
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
43994
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
and heat pumps’’ (10 CFR 431.96(b),
table 1) and ‘‘air conditioning and
heating equipment’’ (10 CFR 431.97(b),
table 1), although these are not defined
terms. These classes have also been
identified by the broader equipment
type with which they are associated
(i.e., small, large, or very large
commercial package air conditioning
and heating equipment). Id.
In the August 2023 TP NOPR, DOE
proposed to establish a definition for
‘‘commercial unitary air conditioner and
commercial unitary heat pump’’ to
assist in distinguishing between the
regulated categories of commercial
package air conditioning and heating
equipment. 88 FR 56392, 56399–56400
(August 17, 2023). The proposed
definition was structured to indicate
categories of commercial package air
conditioning and heating equipment
that are excluded from the definition,
rather than stipulating features or
characteristics of CUACs and CUHPs.
The proposed definition excluded single
package vertical air conditioners and
heat pumps (‘‘SPVUs’’), variable
refrigerant flow multi-split air
conditioners and heat pumps, and
water-source heat pumps. Specifically,
DOE proposed to define ‘‘commercial
unitary air conditioner and commercial
unitary heat pump’’ as any small, large,
or very large air-cooled, water-cooled, or
evaporatively-cooled commercial
package air conditioning and heating
equipment that consists of one or more
factory-made assemblies that provide
space conditioning; but does not
include: (1) single package vertical air
conditioners and heat pumps; (2)
variable refrigerant flow multi-split air
conditioners and heat pumps; (3) watersource heat pumps; (4) equipment
marketed only for use in computer
rooms, data processing rooms, or other
information technology cooling
applications, and (5) equipment only
capable of providing ventilation and
conditioning of 100-percent outdoor air
marketed only for ventilation and
conditioning of 100-percent outdoor air.
Id. at 88 FR 56399. DOE also requested
comment on the proposed definition for
‘‘commercial unitary air conditioners
and heat pumps.’’ Id. at 88 FR 56400.
DOE received feedback from several
commenters regarding the proposed
definition for CUACs and CUHPs. AHRI,
Rheem, and Trane commented that they
did not agree that the proposed
definition for CUACs and CUHPs is
necessary or addresses any existing
problems. (AHRI, No. 15 at p. 3; Rheem,
No. 12 at pp. 1–2; Trane, No. 14 at p.
3) AHRI asserted that manufacturers,
regulators, and design engineers
understand the phrase ‘‘unitary central
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
air conditioners and central airconditioning heat pumps for
commercial application’’ within the
existing definition for ‘‘commercial
package air-conditioning and heating
equipment’’ as referring to CUACs and
CUHPs. (AHRI, No. 15 at p. 3) AHRI also
stated that the proposed definition for
CUACs and CUHPs creates a circular
reference to the existing definition of
‘‘Commercial package air-conditioning
and heating equipment.’’ (Id.) AHRI
further asserted that the proposed
definition for CUACs and CUHPs
should not be implemented, as the term
is not referenced (or proposed) in 42
U.S.C. 6311. (Id at p. 4) AHRI did not
support any changes that would
separate small, large, or very large
commercial package air conditioning
and heating equipment from their
designation as ‘‘ASHRAE equipment’’
per 42 U.S.C. 6313. (Id.)
Carrier, NEEA, and NYSERDA
supported the proposed definition of
‘‘commercial unitary air conditioner and
commercial unitary heat pump.’’
(Carrier, No. 8 at pp. 1–2; NEEA, No. 16
at pp. 3–4; NYSERDA, No. 13 at p. 3)
Carrier recommended DOE also adopt
the definitions for ‘‘Commercial and
Industrial Unitary Air-Conditioning
Equipment’’ and ‘‘Commercial and
Industrial Unitary Heat Pump’’ in
sections 3.4 and 3.5 of AHRI 340/360–
2022 and sections 3.5 and 3.6 of AHRI
1340–202X Draft to provide additional
clarity. (Carrier, No. 8 at pp. 1–2)
NYSERDA recommended including
‘‘packaged or split’’ in the definition for
additional clarity. (NYSERDA, No. 13 at
p. 3)
NEEA also commented that the
definition proposed for CUACs and
CUHPs includes excluded products,
which appeared contradictory to DOE’s
statement that models can meet the
definition for multiple equipment
categories. (NEEA, No. 16 at pp. 3–4)
NEEA requested clarification regarding
DOE’s intent with the proposed
definition. (Id.) AHRI also requested
clarification as to why DOE used
distinct descriptions for the fourth and
fifth exclusions in the proposed CUAC
and CUHP definition rather than using
the already defined terms in 10 CFR
431.92, ‘‘Computer room air
conditioners,’’ and ‘‘Unitary dedicated
outdoor air systems’’ respectively.
(AHRI, No. 15 at pp. 3–4)
After consideration of the comments
received and upon further review, DOE
is declining to finalize the proposed
definition for CUACs and CUHPs in this
final rule. DOE may consider adopting
a definition for CUACs and CUHPs in a
future rulemaking action.
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
2. Basic Model Definition
The current definition for ‘‘basic
model’’ in DOE’s regulations includes a
provision applicable for ‘‘small, large,
and very large air-cooled or watercooled commercial package air
conditioning and heating equipment
(excluding air-cooled, three-phase,
small commercial package air
conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h).’’ 10 CFR 431.92.
Additionally, the term in the current
‘‘basic model’’ definition includes
ACUACs, ACUHPs, and WCUACs, but
does not explicitly include ECUACs.
However, the definition of ‘‘commercial
package air-conditioning and heating
equipment’’ at 10 CFR 431.92 makes
clear that that term includes
evaporatively-cooled equipment.
Consequently, ECUACs are part of the
relevant basic model definition, so the
omission of the term ‘‘evaporativelycooled’’ from the heading should not
impact the proper functioning and use
of the test procedure.
In the August 2023 TP NOPR, DOE
proposed to update the definition of
‘‘basic model’’ so that this provision
instead applies to the proposed defined
term ‘‘commercial unitary air
conditioner and commercial unitary
heat pump,’’ which would also
inherently include evaporatively-cooled
equipment. 88 FR 56392, 56400 (August
17, 2023). DOE also proposed editorial
changes more generally to the definition
of ‘‘basic model’’ specified in 10 CFR
431.92 to address that the current
wording could be misinterpreted to read
as a definition of each equipment
category, rather than as the definition of
what constitutes a basic model for each
equipment category. Id.
DOE did not receive any comments in
response to its proposal to update the
definition for ‘‘basic model.’’ As
discussed in section III.B.1, DOE is not
finalizing the proposed defined term
‘‘commercial unitary air conditioner and
commercial unitary heat pump.’’ As
such, DOE is applying the definition of
‘‘basic model’’ to the existing defined
term ‘‘commercial package airconditioning and heating equipment’’ at
10 CFR 431.92. Therefore, other than
this terminology change, DOE is
amending the definition for ‘‘basic
model’’ as proposed, for the reasons
discussed in the preceding paragraphs
and in the August 2023 TP NOPR.
3. Double-Duct Definition
DOE established a definition for
‘‘double-duct air conditioner or heat
pump’’ at 10 CFR 431.92 (referred to as
‘‘double-duct air conditioners and heat
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
pumps’’ or ‘‘double-duct systems’’) in
an energy conservation standards direct
final rule published in the Federal
Register on January 15, 2016 (‘‘January
2016 Direct Final Rule’’). 81 FR 2420,
2529. This definition was included in a
term sheet by the ASRAC working group
for commercial package air conditioners
(‘‘Commercial Package Air Conditioners
Working Group’’) as part of the
rulemaking that culminated with the
January 2016 Direct Final Rule. (See
Document No. 93 in Docket No. EERE–
2013–BT–STD–0007, pp. 4–5) DOE
defines ‘‘double-duct systems’’ as aircooled commercial package air
conditioning and heating equipment
that: (1) is either a horizontal single
package or split-system unit or a vertical
unit that consists of two components
that may be shipped or installed either
connected or split; (2) is intended for
indoor installation with ducting of
outdoor air from the building exterior to
and from the unit, as evidenced by the
unit and/or all of its components being
non-weatherized, including the absence
of any marking (or listing) indicating
compliance with UL 1995,11 ‘‘Heating
and Cooling Equipment,’’ or any other
equivalent requirements for outdoor
use; (3) if it is a horizontal unit, a
complete unit has a maximum height of
35 inches; if it is a vertical unit, a
complete unit has a maximum depth of
35 inches; and (4) has a rated cooling
capacity greater than or equal to 65,000
Btu/h and up to 300,000 Btu/h. 10 CFR
431.92.
In the August 2023 TP NOPR, DOE
proposed to amend the ‘‘double-duct air
conditioner or heat pump’’ definition
consistent with the definition in both
AHRI 340/360–2022 and the AHRI
1340–202X Draft. 88 FR 56392, 56400–
56401 (August 17, 2023). AHRI 340/
360–2022 and the AHRI 1340–202X
Draft specify the following definition for
‘‘double-duct systems’’: an air
conditioner or heat pump that complies
with all of the following: (1) is either a
horizontal single package or splitsystem unit; or a vertical unit that
consists of two components that can be
shipped or installed either connected or
split; or a vertical single packaged unit
that is not intended for exterior
mounting on, adjacent interior to, or
through an outside wall; (2) is intended
for indoor installation with ducting of
outdoor air from the building exterior to
and from the unit, where the unit and/
or all of its components are nonweatherized; (3) if it is a horizontal unit,
the complete unit shall have a
11 Underwriters Laboratory (UL) 1995, UL
Standard for Safety for Heating and Cooling
Equipment (UL 1995).
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
maximum height of 35 in. or the unit
shall have components that do not
exceed a maximum height of 35 in. If it
is a vertical unit, the complete (split,
connected, or assembled) unit shall
have components that do not exceed
maximum depth of 35 in.; (4) has a rated
cooling capacity greater than and equal
to 65,000 Btu/h and less than or equal
to 300,000 Btu/h.
In comparison to DOE’s definition,
DOE noted the following regarding the
definition for double-duct system in
AHRI 340/360–2022 and the AHRI
1340–202X Draft: (1) vertical single
packaged units not intended for exterior
mounting on, adjacent interior to, or
through an outside wall can be
classified as double-duct systems; (2)
the maximum dimensions apply to each
component of a split system; and (3) the
AHRI 340/360–2022 and AHRI 1340–
202X Draft definition does not include
compliance with UL 1995 as a criterion
for determining whether a model is nonweatherized. In the August 2023 TP
NOPR, DOE tentatively concluded that
the definition for ‘‘double-duct system’’
in section 3.7 of AHRI 340/360–2022
and section 3.12 of the AHRI 1340–202X
Draft more appropriately classifies
double-duct systems and differentiates
this equipment from other categories of
commercial package air conditioning
and heating equipment. 88 FR 56392,
56400–56401 (August 17, 2023).
DOE did not receive comment
regarding the proposed revisions to the
definition for ‘‘double-duct air
conditioner or heat pump.’’ DOE has
determined that the substance of the
definitions for ‘‘double-duct system’’ in
AHRI 340/360–2022 and AHRI 1340–
2023 better implement the intent of DOE
and the Commercial Package Air
Conditioners Working Group to create a
separate equipment class of ACUACs
and ACUHPs that are designed for
indoor installation and that require
ducting of outdoor air from the building
exterior. 81 FR 2420, 2446 (Jan. 15,
2016). Thus, DOE is revising the
definition of ‘‘double-duct air
conditioner or heat pump’’ in 10 CFR
431.92 as proposed in the August 2023
TP NOPR, which is consistent with the
definition in section 3.2.7 of AHRI
1340–2023.
4. Metric Definitions
As mentioned in sections III.D.1 and
III.D.2, and discussed in further detail in
section III.E of this final rule, DOE is
adopting new cooling and heating
metrics in appendix A1 (i.e., IVEC and
IVHE). Additionally, DOE is adopting
three metrics for optional
representations in appendix A1, as
discussed further in section III.E.6 of
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
43995
this final rule: energy efficiency ratio 2
(‘‘EER2’’), coefficient of performance 2
(‘‘COP2’’), and IVHE for colder climates
(‘‘IVHEC’’). In the August 2023 TP
NOPR, DOE proposed to add new
definitions at 10 CFR 431.92 for the
terms ‘‘IVEC,’’ ‘‘IVHE,’’ ‘‘EER2,’’ and
‘‘COP2’’ that describe what each metric
represents, the test procedure used to
determine each metric, and specific
designations applicable to each metric
(e.g., IVHEC). 88 FR 56392, 56401
(August 17, 2023). DOE did not receive
comment on the proposed definitions
for ‘‘IVEC,’’ ‘‘IVHE,’’ ‘‘EER2,’’ and
‘‘COP2.’’ Therefore, DOE is adopting the
definitions as proposed in the August
2023 TP NOPR.
C. Updates to Industry Standards
The following sections discuss the
changes included in the most recent
updates to AHRI 340/360 and ASHRAE
37, which are incorporated by reference
in the current DOE test procedure for
ACUACs and ACUHPs with a rated
cooling capacity greater than or equal to
65,000 Btu/h at 10 CFR 431.96 and 10
CFR part 431, subpart F, appendix A.
AHRI 340/360 is also incorporated by
reference in the current DOE test
procedure for ECUACs and WCUACs
with a rated cooling capacity greater
than or equal to 65,000 Btu/h at 10 CFR
431.96. The following sections also
discuss the new industry test standard,
AHRI 1340–2023, which DOE is
incorporating by reference for use in the
new DOE test procedure for CUACs and
CUHPs at 10 CFR part 431, subpart F,
appendix A1.
1. AHRI 340/360
As noted previously, DOE’s current
test procedures for ACUACs, ACUHPs,
and ECUACs and WCUACs with a rated
cooling capacity greater than or equal to
65,000 Btu/h incorporates by reference
ANSI/AHRI 340/360–2007. DOE’s
current test procedure for ECUACs and
WCUACs with a rated cooling capacity
less than 65,000 Btu/h incorporates by
reference ANSI/AHRI 210/240–2008.
The most recent version of ASHRAE
Standard 90.1 (i.e., ASHRAE Standard
90.1–2022) references AHRI 340/360–
2022 as the test procedure for ACUACs,
ACUHPs, and ECUACs and WCUACs
with a rated cooling capacity greater
than or equal to 65,000 Btu/h. ASHRAE
Standard 90.1–2022 included updates to
the test procedure references for
ECUACs and WCUACs with capacities
less than 65,000 Btu/h to reference
AHRI 210/240–2023. However, ECUACs
and WCUACs with capacities less than
65,000 Btu/h are outside of the scope of
AHRI 210/240–2023 and are instead
included in AHRI 340/360–2022. Given
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
43996
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
these changes to the relevant industry
test standards, DOE believes that such
reference was an oversight.
The following list includes
substantive additions in AHRI 340/360–
2022 as compared to the current Federal
test procedures that apply to CUACs
and CUHPs, which reference ANSI/
AHRI 340/360–2007 and ANSI/AHRI
210/240–2008:
1. A method for testing double-duct
systems at non-zero outdoor air ESP (see
section 6.1.3.7 and appendix I of AHRI
340/360–2022);
2. A method for comparing relative
efficiency of indoor integrated fan and
motor combinations (‘‘IFMs’’) that
allows CUACs and CUHPs with nonstandard (i.e., higher ESP) IFMs to be
rated in the same basic model as
otherwise identical models with
standard IFMs (see section D4.2 of
appendix D of AHRI 340/360–2022);
3. Requirements for indoor and
outdoor air condition measurement (see
appendix C of AHRI 340/360–2022);
4. Detailed provisions for setting
indoor airflow and ESP (see sections
6.1.3.3–6.1.3.5 of AHRI 340/360–2022)
and refrigerant charging instructions to
be used in cases in which
manufacturer’s instructions conflict or
are incomplete (see section 5.8 of AHRI
340/360–2022); and
5. ECUACs and WCUACs with
cooling capacities less than 65,000 Btu/
h are included within the scope of the
standard.
As discussed, DOE is amending its
test procedure for CUACs and CUHPs by
incorporating by reference AHRI 340/
360–2022 in appendix A. Section III.E
discusses the specific sections of AHRI
340/360–2022 that DOE references in
the amendments to appendix A adopted
in this final rule. As discussed, DOE is
adopting these amendments in
accordance with the requirement that
the test procedures for commercial
package air conditioning and heating
equipment be those generally accepted
industry testing procedures or rating
procedures developed or recognized by
AHRI or ASHRAE, as referenced in
ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A)) As DOE has noted,
ASHRAE Standard 90.1 references an
incorrect industry standard for ECUACs
and WCUACs with capacities less than
65,000 Btu/h, AHRI 210/240–2023, so
DOE is amending appendix A to
reference the applicable industry
standard, AHRI 340/360–2022.
2. AHRI 1340
The recommendations of the ACUAC
and ACUHP Working Group TP Term
Sheet have been incorporated into an
updated version of AHRI 340/360,
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
denoted as AHRI 1340–2023, which
supersedes AHRI 340/360–2022, but has
not yet been adopted in ASHRAE
Standard 90.1. In the August 2023 TP
NOPR, DOE proposed to adopt the AHRI
1340–202X Draft, a draft version of
AHRI 1340 available at the time. DOE
noted its intent to update its
incorporation by reference to the final
published version of the AHRI 1340–
202X Draft, unless there were
substantive changes between the draft
and published versions. 88 FR 56392,
56402 (August 17, 2023). Differences
between the ACUAC/ACUHP Working
Group TP Term Sheet, the AHRI 1340–
202X Draft, and AHRI 1340–2023 are
discussed in the paragraphs that follow.
The AHRI 1340–202X Draft proposed
for adoption in the August 2023 TP
NOPR includes recommendations from
the ACUAC and ACUHP Working Group
TP Term Sheet described in section III.D
of this final rule (including the IVEC
and IVHE metrics). The AHRI 1340–
202X Draft also included the following
revisions and additions to the IVEC and
IVHE metrics not included in the
ACUAC and ACUHP Working Group TP
Term Sheet, which are discussed in
detail in section III.E of this final rule:
1. Detailed test instructions for
splitting ESP between the return and
supply ductwork, consistent with ESP
requirements recommended in the
ACUAC and ACUHP Working Group TP
Term Sheet;
2. Corrections to the hour-based IVEC
weighting factors included in the
ACUAC and ACUHP Working Group TP
Term Sheet;
3. Correction of the equation in the
ACUAC and ACUHP Working Group TP
Term Sheet for calculating adjusted ESP
for any cooling or heating tests
conducted with an airflow rate that
differs from the full-load cooling
airflow;
4. Addition of separate hour-based
weighting factors and bin temperatures
to calculate a separate version of IVHE
that is representative of colder climates,
designated IVHEC;
5. Changes to the default fan power
and maximum pressure drop used for
testing coil-only systems;
6. Additional instruction for
component power measurement during
testing;
7. Corrections to equations used for
calculating IVHE;
8. Provisions for testing with nonstandard low-static indoor fan motors;
and
9. Revision to the power adder for
WCUACs that reflects power that would
be consumed by field-installed heat
rejection components.
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
Since publication of the August 2023
TP NOPR, the AHRI 1340–202X Draft
was finalized and published as AHRI
1340–2023 in December 2023. DOE has
reviewed AHRI 1340–2023 and has
identified that AHRI 1340–2023
includes the previously discussed
revisions and additions to the IVEC and
IVHE metrics in the AHRI 1340–202X
Draft that were not included in the
ACUAC and ACUHP Working Group TP
Term Sheet. AHRI 1340–2023 also
includes several revisions and updates
to the test procedures specified in the
AHRI 1340–202X Draft. DOE reviewed
these revisions and updates, which
include the following items, and
discusses them in detail in sections
III.E.3, III.E.7, III.E.8, III.F, and III.H of
this document. Those sections also
include discussion of the justification
for adopting the content of these
changes (which are largely consistent
with corresponding proposals in the
August 2023 TP NOPR) in this final
rule.
1. A method for calculating capacity
and fan power adjustments for coil-only
systems operating at part-load airflow,
consistent with DOE’s proposal in the
August 2023 TP NOPR;
2. Addition of a method to verify cutin and cut-out temperatures, consistent
with DOE’s proposal in the August 2023
TP NOPR but with additional
specificity;
3. Addition of an optional boost 2 test
for optional representations of 5 °F
capacity and performance for systems
with more than two operating levels;
4. Allowance for the test conducted at
5 °F and 17 °F at the boost heating
operating level to be used for IVHE bins
ranging from 5 °F to 21 °F;
5. Revisions to appendix D of AHRI
1340 to align with the specific
components approach proposed by DOE
in the August 2023 TP NOPR, and
inclusion of provision for how to test
models with drain pan heaters present;
and
6. Revisions to the test temperatures
for ECUACs and WCUACs and
corresponding revision to the tower fan
and pump power values for WCUACs.
Consistent with the proposals in the
August 2023 TP NOPR, in this final rule
DOE is incorporating by reference AHRI
1340–2023 in the new test procedure at
appendix A1 as DOE has determined,
supported by clear and convincing
evidence, that AHRI 340/360–2022
cannot provide representative energy
use results for the IVEC and IVHE
efficiency metrics. Further, DOE has
determined that AHRI 1340–2023 would
not be unduly burdensome to conduct
and reflects energy efficiency during a
representative average use cycle for the
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
IVEC and IVHE efficiency metrics.
Specific aspects of AHRI 1340–2023 are
discussed in more detail in section III.E.
Section III.E of this document also
discusses comments received on DOE’s
proposal to adopt the AHRI 1340–202X
Draft, as well as the specific sections of
AHRI 1340–2023 that DOE references in
appendix A1.
lotter on DSK11XQN23PROD with RULES2
3. ASHRAE 37
ANSI/ASHRAE 37–2009, which
provides a method of test for many
categories of air conditioning and
heating equipment, is referenced for
testing CUACs and CUHPs by AHRI
340/360–2022 and AHRI 1340–2023.
More specifically, sections 5 and 6 and
appendices C, D, and E of AHRI 340/
360–2022 and sections 5 and 6 and
appendices C, D, and E of AHRI 1340–
2023 reference methods of test in ANSI/
ASHRAE 37–2009. DOE currently
incorporates by reference ANSI/
ASHRAE 37–2009 in 10 CFR 431.95,
and the current incorporation by
reference applies to the current Federal
test procedure for ACUACs and
ACUHPs specified at appendix A. The
current Federal test procedures at 10
CFR 431.96 for ECUACs and WCUACs
do not explicitly reference ANSI/
ASHRAE 37–2009. In the August 2023
TP NOPR, DOE proposed to maintain
the incorporation by reference of ANSI/
ASHRAE 37–2009 to the proposed
appendix A, which would also apply
ANSI/ASHRAE 37–2009 to testing
ECUACs and WCUACs, and to
incorporate by reference ANSI/ASHRAE
37–2009 for use with appendix A1. 88
FR 56392, 56402 (August 17, 2023).
DOE did not receive any comments
regarding its proposal to incorporate by
reference ANSI/ASHRAE 37–2009 to
both appendices A and A1. Therefore,
as proposed, DOE is maintaining its
incorporation by reference of ANSI/
ASHRAE 37–2009 in appendix A and
incorporating by reference ANSI/
ASHRAE 37–2009 in appendix A1.
Section III.E of this document discusses
the specific sections of ANSI/ASHRAE
37–2009 that DOE references in
appendices A and A1.
D. Term Sheet Recommendations and
Metrics
As previously mentioned, DOE
published in the Federal Register the
July 2022 Notice of Intent. 87 FR 45703
(July 29, 2022). DOE then established
the Working Group in accordance with
FACA and NRA. The Working Group
consisted of 14 members and met six
times, while the Working Group’s
subcommittee met an additional seven
times. The Working Group meetings
were held between September 20, 2022,
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
and December 15, 2022, after which the
Working Group successfully reached
consensus on an amended test
procedure. The Working Group signed a
term sheet of recommendations on
December 15, 2022. (See EERE–2022–
BT–STD–0015–0065) The Working
Group addressed the following aspects
of the test procedure for ACUACs and
ACUHPs:
1. Mathematical representation of
cooling efficiency: The current cooling
metric specified by AHRI 340/360–2022
(i.e., IEER) represents a weighted
average of the measured energy
efficiency ratios (EER) measured at four
distinct test conditions, whereas the
IVEC metric is calculated as the total
annual cooling capacity divided by the
total annual energy use, as discussed
further in section III.D.1 of this
document. The Working Group agreed
that this calculation approach provides
a more mathematically accurate way of
representing the cooling efficiency of
ACUACs and ACUHPs compared to the
current approach used for IEER. As part
of this equation format, the IVEC metric
also uses hour-based weighting factors
to represent the time spent per year in
each operating mode.
2. Integrated heating metric: The
current heating metric for ACUHPs (i.e.,
COP) represents the ratio of heating
capacity to the power input, calculated
at a single test condition of 47 °F. COP
does not account for the performance at
part-load or over the range of
temperatures seen during an average
heating season, and it does not include
energy use in heating season ventilation
mode. IVHE accounts for both full-load
and part-load operation at a range of
typical ambient temperatures seen
during the heating season, and it
includes energy use in heating season
ventilation mode. Analogous to IVEC,
the IVHE metric is calculated as the
total annual heating load divided by the
total annual energy use, as discussed
further in section III.D.2 of this
document, and the metric also uses
hour-based weighting factors to
represent the time spent per year in
each operating mode.
3. Operating modes other than
mechanical cooling: The IEER metric
currently does not include the energy
use of operating modes other than
mechanical cooling, such as
economizer-only cooling and cooling
season ventilation. The newly
established IVEC metric includes the
energy use of these other modes.
4. ESP: The IVEC and IVHE metrics
require increased ESPs—in comparison
to the ESPs required for determining
IEER and COP—to more accurately
represent ESPs and corresponding
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
43997
indoor fan power that would be
experienced in real-world installations.
5. Crankcase heater operation: The
current IEER metric includes crankcase
heater power consumption only when
operating at part-load compressor stages
(i.e., for part-load cooling operation,
crankcase heater power is included only
for higher-stage compressors that are
staged off, and it is not included for
lower-stage compressors when all
compressors are cycled off). The COP
metric does not include any crankcase
heater power consumption. In contrast,
the IVEC and IVHE metrics include all
annual crankcase heater operation,
including when all compressors are
cycled off in part-load cooling or
heating, ventilation mode, unoccupied
no-load hours, and in heating season
(for ACUACs only).
6. Oversizing: The current IEER and
COP metrics do not consider that
ACUACs and ACUHPs are typically
oversized in field installations. In
contrast, the IVEC and IVHE metrics
include an oversizing factor of 15
percent (i.e., it is assumed that the unit’s
measured full-load cooling capacity is
15 percent higher than the peak
building cooling load and peak building
heating load). Accounting for oversizing
is more representative of the load
fractions seen in field applications and
better enables the test procedure to
differentiate efficiency improvements
from the use of modulating/staged
components.
Based on discussions related to these
six topics, the Working Group
developed the ACUAC and ACUHP
Working Group TP Term Sheet, which
includes the following
recommendations:
1. A recommendation to adopt the
latest version of AHRI 340/360–2022
with IEER and COP metrics required for
compliance beginning 360 days from the
date a test procedure final rule
publishes (see Recommendation #0);
2. The IVEC efficiency metric, to be
required on the date of amended energy
conservation standards for ACUACs and
ACUHPs (see Recommendation #1);
3. Hour-based weighting factors for
the IVEC metric (see Recommendation
#2);
4. Details on determination of IVEC,
including provisions for determining
IVEC in appendix B of the ACUAC and
ACUHP Working Group TP Term Sheet
(see Recommendation #3);
5. Target load fractions and
temperature test conditions for IVEC,
which account for oversizing (see
Recommendation #4);
6. A requirement that representations
of full-load EER be made in accordance
E:\FR\FM\20MYR2.SGM
20MYR2
43998
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
with the full-load ‘‘A’’ test (see
Recommendation #5); 12
7. A requirement to provide
representations of airflow used for the
full-load ‘‘A’’ test and the part-load ‘‘D’’
test (i.e., the airflow used in the loweststage test for the D point), and a
provision for determining the minimum
airflow that can be used for testing (see
Recommendation #6);
8. The IVHE efficiency metric (see
Recommendation #7);
9. Hour-based weighting factors, load
bins, and outdoor air temperatures for
each bin (i.e., temperatures used for the
building heating load line, not test
temperature conditions) for the IVHE
metric (see Recommendation #8);
10. The test conditions and list of
required and optional tests and
representations for the IVHE metric (see
Recommendation #9);
11. Provisions for manufacturers to
certify cut-in and cut-out temperatures
for heat pumps to DOE and provisions
for a DOE verification test of those
temperatures (see Recommendation
#10);
12. Commitment of the Working
Group to analyze ventilation and fanonly operation included in the IVEC and
IVHE metrics to validate that these
metrics adequately capture fan energy
use during the energy conservation
standards portion of the negotiated
rulemaking. If the IVEC and IVHE levels
do not adequately drive more efficient
air moving systems that are
technologically feasible and
economically justified, the Working
Group committed to developing a metric
addressing furnace fan energy use (see
Recommendation #11);
13. ESP requirements for the IVEC
and IVHE metrics, requirements for
splitting the ESP requirements between
the return and supply ducts, and a
requirement that certified airflow for
full load and D bin be made public in
the DOE Compliance Certification
Database (see Recommendation #12);
14. Provisions requiring
manufacturers to certify crankcase
heater wattages and tolerances for
certification (see Recommendation #13);
and
15. Provisions that the contents of the
ACUAC and ACUHP Working Group TP
Term Sheet be implemented in a test
procedure NOPR and final rule, with the
final rule issuing no later than any
energy conservation standards direct
final rule (see Recommendation #14).
The following sections provide a
summary of the development and final
recommendations regarding the IVEC
and IVHE cooling and heating metrics in
the ACUAC and ACUHP Working Group
TP Term Sheet.
1. IVEC
For the new cooling metric, the
Working Group determined to
prospectively modify the climate zones
and building types accounted for in the
test procedure as compared to those
included in the existing DOE test
procedure, in order to improve the
representativeness of the metrics to
better reflect the broad range of
applications of CUACs and CUHPs. To
do so, the Working Group utilized hourbased weighting factors, which
represent the average time spent per
year in each operating mode and load
bin. To develop these weighting factors,
members of the Working Group used
building modeling developed by Carrier
that was based on 10 ASHRAE Standard
90.1 building prototypes across all U.S.
climate zones. (See EERE–2022–BT–
STD–0015–0019) The resulting hour-
based weighting factors are provided in
Recommendation #2 of the ACUAC and
ACUHP Working Group TP Term Sheet.
(See EERE–2022–BT–STD–0015–0065)
The ACUAC and ACUHP Working
Group concluded that including
economizer-only cooling and cooling
season ventilation operating modes in a
seasonal cooling metric would improve
the representativeness for ACUACs and
ACUHPs, and as such, included these
modes in the IVEC metric outlined in
Recommendation #1 and the hour-based
weighting factors in Recommendation
#2 of the ACUAC and ACUHP Working
Group TP Term Sheet. Appendix B of
the ACUAC and ACUHP Working Group
TP Term Sheet provides the
recommended calculation method for
the IVEC method and includes sections
specifying the methods for including
ventilation and economizer-only cooling
operation in the calculation of IVEC.
(See EERE–2022–BT–STD–0015–0065)
The Working Group also considered
ESP requirements for the IVEC and
IVHE metrics. Stakeholders indicated
the need for higher ESP requirements to
improve representativeness of field
performance. Additionally, stakeholders
discussed the importance of
maintaining uniformity in testing of
units at higher ESP conditions. (See
EERE–2022–BT–STD–0015–0062 at p.
11) The ESP requirements agreed to by
the Working Group are provided in
Recommendation #12 of the ACUAC
and ACUHP Working Group TP Term
Sheet (see EERE–2022–BT–STD–0015–
0065) and include the following:
1. Higher ESP requirements for
testing: As discussed previously, the
minimum ESP conditions recommended
by the Working Group are provided in
Table III–1.
Table 111-1 Minimum ESP Requirements for IVEC and IVHE
Recommended by the ACUAC and ACUHP Working Group
lotter on DSK11XQN23PROD with RULES2
2. Economizer pressure drop:
ASHRAE Standard 90.1–2022 requires
the use of economizers for comfort
cooling applications for almost all U.S.
climate zones. The analysis conducted
by Carrier in support of the Working
Group indicates that over 96 percent of
buildings require the use of
economizers. (see EERE–2022–BT–STD–
0015–0019 at p. 14) Economizers
installed in CUACs and CUHPs add
internal static pressure that the indoor
12 Similar to the current test procedure for
determining IEER, the test procedure recommended
in the ACUAC and ACUHP Working Group TP
Term Sheet includes four cooling tests designated
with letters ‘‘A,’’ ‘‘B,’’ ‘‘C,’’ and ‘‘D.’’ The ‘‘A’’ test
is a full-load cooling test, while the ‘‘B,’’ ‘‘C,’’ and
‘‘D’’ tests are part-load cooling tests.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
ER20my24.128
ESP (in. H20)
0.75
1.0
1.0
1.5
Rated Cooling Capacity
>65 and <135 kBtu/h
?:135 and <240 kBtu/h
?:240 and <280 kBtu/h
?:280 and <760 kBtu/h
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
fan has to overcome, even when the
economizer dampers are closed. The
current DOE test procedure does not
require the installation of an economizer
on a tested unit, and DOE is aware that
manufacturers generally do not test
CUACs and CUHPs with economizers
installed. The ESP requirements
specified by the current DOE test
procedure are the same regardless of
whether a unit is tested with or without
an economizer. As such, testing a unit
without an economizer does not reflect
the total static pressure that would be
experienced in the field for installations
that require the use of an economizer.
Accordingly, in order to better represent
the fan power of ACUACs and ACUHPs
that are typically installed with
economizers, the Working Group
recommended that for all units tested
without an economizer installed, 0.10
in. H2O shall be added to the full-load
ESP values specified in Table III–1.13
3. Return and supply static split
requirements: Test procedures for
CUACs and CUHPs include ESP
requirements that reflect the total ESP
applied within the return and supply
ductwork of the test set-up. The current
Federal test procedure does not specify
requirements for how ESP is distributed
during testing (i.e., the relative
contribution from return ductwork
versus supply ductwork). Given the
recommendation to increase the
required ESP levels for testing, the
Working Group concluded that the
higher ESP conditions could cause
variability in test results if the
distribution of ESP between return
ductwork and supply ductwork were
not specified in the revised test
procedure. Therefore, to ensure
repeatable and reproducible testing
conditions for CUAC and CUHP units,
the Working Group recommended
specifying that ESP requirements be
split with 25 percent applied in the
return ductwork and the remaining 75
percent applied in the supply ductwork.
The Working Group further
recommended that the fraction of ESP
applied in the return ductwork shall
have a ¥5/+0 percent tolerance (i.e., the
return static must be within 20 to 25
percent of the total ESP) for the full-load
cooling test. In a case where there is no
additional restriction on the return duct
and more than 25 percent of the ESP is
already applied in the return ductwork
without a restriction, then greater than
25 percent ESP in the return ductwork
will be allowed. Once set for the fullload cooling test, these restriction
settings shall remain unchanged for the
other cooling and heating tests
conducted.
To incorporate the various changes
involved in testing requirements and
weighting factors already discussed, the
Working Group created the IVEC metric
provided in Recommendation #1 with
further specifications in appendix B of
the ACUAC and ACUHP Working Group
TP Term Sheet. The IVEC metric is a
summation formula analogous to the
seasonal energy efficiency ratio 2
(‘‘SEER2’’) metric designated for
residential central air conditioner and
central air conditioning heat pumps
(‘‘CAC/HP’’) equipment. (See appendix
M1 to subpart B of 10 CFR part 430,
‘‘Uniform Test Method for Measuring
the Energy Consumption of Central Air
Conditioners and Heat Pumps.’’) Stated
simply, the IVEC metric is calculated by
dividing the total annual cooling
capacity by the total annual energy use.
Key aspects encompassed in the IVEC
metric include the following:
1. Accounting for energy consumed in
different modes: The IVEC metric
includes energy use during mechanical
cooling, integrated mechanical and
economizer cooling, economizer-only
cooling, cooling season ventilation,
unoccupied no-load hours, and heating
season operation of crankcase heat (for
CUACs only). Appendix B of the
ACUAC and ACUHP Working Group TP
Term Sheet specifies instructions for
determining energy consumption during
each mode.
2. Testing parameters: The ACUAC
and ACUHP Working Group TP Term
Sheet further specifies instructions in
appendix B for the mechanical cooling
tests at each target mechanical load.
These methodologies and tolerances
mirror those specified in AHRI 340/
360–2022, including a 3-percent
tolerance on the target mechanical load
for part-load tests, and in cases when
the target mechanical load cannot be
met within tolerance, instructions for
using interpolation and cyclic
degradation to determine the
performance at the target test point.
3. Target load percentages:
Recommendation #4 of the ACUAC and
ACUHP Working Group TP Term Sheet
includes target conditions for testing,
including load percentages for testing
units at part-load conditions. For each
bin, the specified target load percent
(%Loadi) reflects the average load as a
percentage of the full-load capacity for
that bin met by using all modes of
cooling, and is used for determining
total annual cooling provided in the
numerator of the IVEC equation. The
target mechanical load percent
(%Loadi,mech) is the average load for
each bin met only through mechanical
cooling (i.e., mechanical-only cooling
and the mechanical portion of
integrated mechanical and economizer
cooling) and is the target load fraction
used for the part-load cooling test for
each bin.
As mentioned, the IVEC metric
includes the annual operation of
crankcase heaters for CUACs and
CUHPs. Appendix B of the ACUAC and
ACUHP Working Group TP Term Sheet
further specifies the accounting of
crankcase heater energy consumption in
each operating mode. Recommendation
#2 of the ACUAC and ACUHP Working
Group TP Term Sheet specifies hourbased weighting factors to account for
crankcase heat operation in unoccupied
no-load cooling season hours for CUACs
and CUHPs, as well as heating season
hours for CUACs. Appendix B of the
ACUAC and ACUHP Working Group TP
Term Sheet also specifies that for partload cooling tests, crankcase heat is
accounted for in power measurements
of higher-stage compressors that are
staged off during testing, while
crankcase heat operation of lower-stage
compressors when cycled off as well as
crankcase heat operation in other
operating modes is calculated using the
certified crankcase heater power.
The IVEC metric also accounts for a
15-percent oversizing factor.
Accordingly, the target load percentages
specified in Recommendation #4
include this 15-percent oversizing
factor. Additionally, the A test
condition is excluded from the IVEC
calculation; however, the A test is still
a required test point for determining
full-load capacity.
IVEC includes outdoor and return air
dry-bulb and wet-bulb test temperatures
that differ from those used in the
current test procedure for determining
IEER, as shown in Table III–2.
13 An economizer is an apparatus that supplies
outdoor air to reduce or eliminate the need for
mechanical cooling during mild or cooler weather.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
43999
E:\FR\FM\20MYR2.SGM
20MYR2
44000
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
Table 111-2 IEER and IVEC Test Temperatures
Outdoor Air
Dry-Bulb
Temperature
(OF)
Return Air
Temperature
(Dry-Bulb/
Wet-Bulb) {°F)
Outdoor Air
Dry-Bulb
Temperature
{°F)
Return Air
Temperature
(Dry-Bulb/
Wet-Bulb) {°F)
A
95
80/67
95
80/67
B
C
D
81.5
68
65
80/67
80/67
80/67
85
75
65
77/64
77/64
77/64
lotter on DSK11XQN23PROD with RULES2
The IVEC metric also limits the
minimum airflow that can be used for
testing. This minimum airflow limit
calculation method is based on the
average ventilation rate determined in
building modeling performed to develop
IVEC and is a function of the full-load
cooling capacity. Unlike AHRI 340/360–
2022 (see section 6.1.3.4.5), the
provisions for determining IVEC do not
specify separate test provisions for
setting airflow during part-load tests of
multi-zone variable air volume
(‘‘MZVAV’’) units. Rather, the part-load
airflow used for testing all CUACs and
CUHPs will be based on the certified
part-load cooling airflow.
2. IVHE
The IVHE metric specified in the
ACUAC and ACUHP Working Group TP
Term Sheet differs from the COP heating
efficiency metric specified in the
current DOE test procedure by the
inclusion of heating season operating
modes not currently accounted for, a
combined seasonal performance metric
rather than individual ratings at specific
temperature conditions, and additional
optional test conditions. In alignment
with the development of the IVEC
metric described in section III.D.1 of
this final rule, the Working Group
determined to utilize hour-based
weighting factors to account for heating
loads across more building types and
climate zones than are included in the
current DOE test procedure. The
building heating load lines and hours
developed for the IVHE metric rely on
a similar ASHRAE Standard 90.1
building and climate zone analysis as
the one conducted for the IVEC metric
development. Additionally, in
developing the heating load line on
which the hour-based weighting factors
rely, the Working Group utilized the
previously discussed 15-percent
oversizing factor and assumed a heat-tocool ratio of 1, as outlined in
Recommendation #8 (i.e., assumed the
VerDate Sep<11>2014
IVEC Test Conditions
19:59 May 17, 2024
Jkt 262001
peak building cooling load equals the
peak building heating load).
The heating rating requirements
recommended in the ACUAC and
ACUHP Working Group TP Term Sheet
include several distinct provisions
regarding testing requirements from the
existing DOE test procedure. In the
current DOE test procedure, CUHPs are
required to be tested only at a 47 °F fullload condition to generate a COP rating.
Recommendation #9 of the ACUAC and
ACUHP Working Group TP Term Sheet,
however, introduces several provisions
with significant differences from the
existing DOE test procedure. First, the
recommendation includes required
testing at 47 °F and 17 °F full-load
conditions, aligning with those
previously specified in AHRI 340/360–
2022. Additionally, the
recommendation introduces optional
part-load test conditions at both 47 °F
and 17 °F temperature conditions, as
well as test conditions for optional
testing at a 5 °F full-load condition.
Finally, the recommendation includes
test requirements for optional boost tests
at the 17 °F and 5 °F test conditions for
variable-speed units. Additionally, the
IVHE metric incorporates two operating
modes previously excluded from the
DOE test procedure: heating season
ventilation mode and supplemental
electric resistance heat operation.
Lastly, the IVHE test conditions rely on
the same ESP requirements per capacity
bin as those specified for IVEC, as
detailed in Recommendation #12. The
airflow provisions pertaining to IVEC
mentioned in section III.D.1 of this final
rule (i.e., a limit on minimum airflow
used for testing and no separate test
provisions for MZVAV units) apply to
the test provisions for the IVHE metric
as well.
The results from optional and
required testing, as well as the newly
included operating modes, are included
in the calculation of the IVHE metric
utilizing the weighting factors outlined
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
in Recommendation #8 and calculation
methods from appendix C of the
ACUAC and ACUHP Working Group TP
Term Sheet. The calculation methods
for IVHE that implement these changes
are further detailed in the paragraphs
that follow.
The IVHE metric includes
contributions from both mechanical and
resistance heating to meet building
heating load. Similar to the IVEC
calculation approach, the IVHE metric is
calculated by dividing the total annual
building heating load by the total
annual energy use.
Recommendations #8, #9, and #10, as
well as appendices B and C of the
ACUAC and ACUHP Working Group TP
Term Sheet, provide the calculation
methods for the IVHE metric. The hourbased weighting factors and bin
temperatures for IVHE are included in
Recommendation #8 of the ACUAC and
ACUHP Working Group TP Term Sheet,
which specifies 10 distinct load-based
bins alongside weighting factors for
heating season ventilation and operation
of crankcase heat in unoccupied no-load
heating season hours. The calculation
methods outlined for the IVHE metric in
the ACUAC and ACUHP Working Group
TP Term Sheet are specified as the
following:
1. Building load calculation:
Recommendation #8 includes the
calculation method for the building load
in each load bin based on the measured
full-load cooling capacity.
2. Interpolation between
temperatures: Appendix C of the
ACUAC and ACUHP Working Group TP
Term Sheet specifies interpolation
instructions for the various test
temperatures specified in
Recommendation #8. Interpolation
instructions are specified for bins with
temperatures between 17 °F and 47 °F.
Appendix C also includes the following
instructions for bins with temperatures
less than 17 °F: (1) interpolation
instructions to be used if the optional
E:\FR\FM\20MYR2.SGM
20MYR2
ER20my24.129
IEER Test Conditions
Test Point
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
5 °F test is conducted, and (2)
extrapolation instructions utilizing the
47 °F and 17 °F test data to be used if the
5 °F test is not conducted.
3. Determination of heating stage,
auxiliary heat, and cyclic degradation:
For load bins in which the calculated
building load exceeds the highest-stage
mechanical heating capacity determined
for the bin temperature, appendix C of
the ACUAC and ACUHP Working Group
TP Term Sheet includes calculation
methods for determining the power
required by auxiliary resistance heat
and is included in the overall IVHE
calculation. For load bins in which the
calculated building load is lower than
the lowest-stage mechanical heating
capacity determined for the bin
temperature, appendix C of the ACUAC
and ACUHP Working Group TP Term
Sheet includes calculation methodology
for calculating power and incorporating
cyclic degradation with a cyclic
degradation factor of 0.25. This cyclic
degradation methodology is consistent
with the methodology specified in
appendix M1 to subpart B of 10 CFR
part 430 for residential central heat
pumps. For load bins in which the
calculated building load is in between
the lowest-stage and highest-stage
mechanical heating capacities
determined for the bin temperature,
appendix C of the ACUAC and ACUHP
Working Group TP Term Sheet includes
calculations for determining power
based on interpolation between
performance of mechanical heating
stages.
4. Defrost degradation: The capacity
calculations for all load bins with
temperatures less than 40 °F include a
defrost degradation coefficient, with
calculations specified in appendix C of
the ACUAC and ACUHP Working Group
TP Term Sheet.
5. Cut-out factor: Recommendation
#10 of the ACUAC and ACUHP Working
Group TP Term Sheet specifies that
manufacturers will certify cut-in and
cut-out temperatures, or the lack
thereof, to DOE to ensure resistanceonly operation is included at
temperatures below which mechanical
heating would not operate. This
restriction is implemented in
calculations through a cut-out factor
included in appendix C. DOE is not
amending the certification or reporting
requirements for ACUHPs in this final
rule to require reporting cut-in and cutout temperatures. Instead, DOE may
consider proposals to amend the
certification and reporting requirements
for this equipment under a separate
rulemaking regarding appliance and
equipment certification.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
6. Crankcase heater power
contribution: In alignment with the
inclusion of crankcase heater power
contribution in IVEC, appendix C of the
ACUAC and ACUHP Working Group TP
Term Sheet specifies a method for
incorporating crankcase heat power for
all heating season operating modes for
ACUHPs. Specifically, for part-load
heating tests, crankcase heat is
accounted for in power measurements
of higher-stage compressors that are
staged off during testing, while
crankcase heat operation of lower-stage
compressors when cycled off, as well as
crankcase heat operation in other
operating modes, is calculated using the
certified crankcase heater power.
E. DOE Adopted Test Procedures and
Comments Received
In the August 2023 TP NOPR, DOE
proposed to maintain the current
efficiency metrics of IEER, EER, and
COP in appendix A, and reference AHRI
340/360–2022 in appendix A for
measuring the existing metrics. 88 FR
56392, 56403–56404 (August 17, 2023).
Additionally, DOE proposed to establish
a new test procedure at appendix A1
that adopts the substance of the AHRI
1340–202X Draft, including the new
IVEC and IVHE metrics, through
incorporation by reference of a finalized
version of that industry test standard.
Id. The following sections discuss
DOE’s proposals, comments received,
and DOE’s adopted provisions regarding
(1) AHRI 1340–2023 and the IVEC and
IVHE metrics; (2) double-duct systems;
(3) ECUACs and WCUACs; (4) the IVHE
metric for colder climates; (5) the test
conditions used in appendix A; (6) the
test conditions used in appendix A1; (7)
provisions introduced in the AHRI
1340–202X Draft that are not included
in the ACUAC and ACUHP Working
Group TP Term Sheet; and (8) heating
test provisions introduced in AHRI
1340–2023.
1. Overall
As discussed, DOE proposed to
establish a new test procedure at
appendix A1 that would adopt the AHRI
1340–202X Draft, including the newly
proposed IVEC and IVHE metrics. DOE
noted its intent to ideally incorporate by
reference a finalized version of that
industry test standard. DOE further
stated that if a finalized version of the
AHRI 1340–202X Draft is not published
before the test procedure final rule, or
if there are substantive changes between
the draft and published versions of the
standard that are not supported by
stakeholder comments in response to
this NOPR, DOE may adopt the
substance of the AHRI 1340–202X Draft
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
44001
or provide additional opportunity for
comment on the final version of that
industry consensus standard. Id. As
noted in the August 2023 TP NOPR,
certain provisions in the current
appendix A and table 1 to 10 CFR
431.96(b) (e.g., regarding minimum ESP,
optional break-in) would be redundant
with the reference to AHRI 340/360–
2022, and, as such, DOE proposed to
remove those explicit provisions from
table 1 to 10 CFR 431.96(b) and
appendix A, and instead reference them
through the relevant provisions of the
updated AHRI 340/360. Id.
Further, in both appendix A and
appendix A1, DOE proposed to
incorporate by reference ANSI/ASHRAE
37–2009. Id.
Specifically for appendix A1, DOE
proposed to adopt certain sections of the
AHRI 1340–202X Draft to determine
IVEC and IVHE, which are generally
consistent with the recommendations
from the ACUAC and ACUHP Working
Group TP Term Sheet. Id. The ACUAC
and ACUHP Working Group TP Term
Sheet applies only to the test procedures
for ACUACs and ACUHPs, excluding
double-duct systems. However, the
AHRI 1340–202X Draft proposed for
adoption in the August 2023 TP NOPR,
as well as the final version of the
standard (i.e., AHRI 1340–2023),
include additional provisions for
determining IVEC and IVHE for doubleduct systems, ECUACs, and WCUACs,
indicating industry consensus that these
metrics are appropriate for these
categories of CUACs and CUHPs. Id.
DOE requested comment on the
proposed adoption of the IVEC and
IVHE metrics as determined using the
AHRI 1340–202X Draft in appendix A1
for all CUACs and CUHPs. Id.
On this topic, AHRI, ASAP & ACEEE,
Carrier, the CA IOUs, Lennox, NEEA,
Rheem, and Trane generally supported
the proposal to adopt the IVEC and
IVHE metrics as determined in the AHRI
1340–202X Draft, consistent with the
ACUAC and ACUHP Working Group TP
Term Sheet. (AHRI, No. 15 at pp. 1, 5;
ASAP & ACEEE, No. 11 at p. 1; Carrier,
No. 8 at p. 2; CA IOUs, No. 10 at pp.
1–2; Lennox, No. 9 at p. 2; NEEA, No.
16 at pp. 1–2; Rheem, No. 12 at p. 2,
Trane, No. 14 at p. 1) NEEA specifically
supported the ESP requirements
proposed by DOE consistent with the
recommendations of the ACUAC and
ACUHP Working Group TP Term Sheet.
(NEEA, No. 16 at p. 2) The CA IOUs
stated that the new test procedure
improves representativeness. (CA IOUs,
No. 10 at p. 1) AHRI and ASAP &
ACEEE acknowledged the efforts made
by the AHRI Commercial Unitary
Standards Technical Committee
E:\FR\FM\20MYR2.SGM
20MYR2
44002
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
(‘‘STC’’) and supported the corrections
and additions to the ACUAC and
ACUHP Working Group TP Term Sheet
included in the AHRI 1340–202X Draft.
(AHRI, No. 15 at pp. 1–2; ASAP &
ACEEE, No. 11 at p. 1)
As proposed, DOE is adopting the
most recent version of AHRI Standard
340/360 (i.e., AHRI 340/360–2022) in
appendix A for testing CUACs and
CUHPs (including ACUACs, ACUHPs,
ECUACs, WCUACs, and double-duct
systems) to measure the current
metrics—EER, IEER, and COP.
Specifically, DOE is adopting the
following sections of AHRI 340/360–
2022: sections 3 (with certain
exclusions 14), 4, 5, and 6, and
appendices A, C, D (excluding sections
D1 through D3), and E. As proposed,
DOE is also removing certain provisions
from table 1 to 10 CFR 431.96(b) and the
current appendix A that are redundant
with the reference to AHRI 340/360–
2022 adopted in appendix A in this
final rule. As discussed, DOE is
adopting these amendments in
accordance with the requirement that
the test procedures for commercial
package air conditioning and heating
equipment be those generally accepted
industry testing procedures or rating
procedures developed or recognized by
AHRI or ASHRAE, as referenced in
ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A))
As discussed in section III.C.2 of this
document, AHRI 1340–2023 includes
certain updates that are not included in
the ACUAC and ACUHP Working Group
TP Term Sheet. Most of these updates
were included in the AHRI 1340–202X
Draft, and they are discussed in detail
in section III.E.7 of this final rule. There
are also several updates included AHRI
1340–2023 that were not included in the
AHRI 1340–202X Draft, notably
regarding ECUACs and WCUACs
(discussed in further detail in section
III.E.3 of this document) and boost
heating tests (described in further detail
in section III.E.8 of this document).
Based on comments received and DOE’s
review of AHRI 1340–2023, DOE has
determined that the updates to the test
procedure in AHRI 1340–2023 are
14 DOE is not referencing the following provisions
in section 3 of AHRI 340/360–2022 because the
terms are either defined at 10 CFR 431.92 or are not
needed for the DOE test procedure: 3.2 (Basic
Model), 3.4 (Commercial and Industrial Unitary
Air-conditioning Equipment), 3.5 (Commercial and
Industrial Unitary Heat Pump), 3.7 (Double-duct
System), 3.8 (Energy Efficiency Ratio), 3.12 (Heating
Coefficient of Performance), 3.14 (Integrated Energy
Efficiency Ratio), 3.23 (Published Rating), 3.26
(Single Package Air-Conditioners), 3.27 (Single
Package Heat Pumps), 3.29 (Split System Airconditioners), 3.30 (Split System Heat Pump), and
3.36 (Year Round Single Package Air-conditioners).
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
appropriate, consistent with the intent
of the ACUAC and ACUHP Working
Group TP Term Sheet and the intent of
the provisions proposed in the August
2023 TP NOPR, and improve the
representativeness of the test procedure.
DOE has determined that the
recommendations specified in the
ACUAC and ACUHP Working Group TP
Term Sheet are consistent with the
EPCA requirement that test procedures
for covered equipment, including
CUACs and CUHPs, be reasonably
designed to produce test results that
reflect energy efficiency, energy use,
and estimated operating costs of a type
of industrial equipment (or class
thereof) during a representative average
use cycle (as determined by the
Secretary), and shall not be unduly
burdensome to conduct (42 U.S.C.
6314(a)(2)). As a result, DOE is adopting
a new test procedure in appendix A1 in
accordance with the Term Sheet.
Therefore, DOE is amending the test
procedure for CUACs and CUHPs to
adopt in the new appendix A1 the test
provisions in AHRI 1340–2023 and
ASHRAE 37–2009. DOE is adopting the
following sections of AHRI 1340–2023
in appendix A1: sections 3 (with certain
exclusions),15 4, 5 (excluding section
5.2), and 6.1 through 6.3, and
appendices A, C, D (excluding sections
D.1 and D.2), and E. Use of appendix A1
will not be required until the
compliance date of amended energy
conservation standards denominated in
15 DOE is not referencing the following provisions
in section 3 of AHRI 1340–2023 because the terms
are either defined at 10 CFR 431.92 or are not
needed for the DOE test procedure: 3.2.2
(Barometric Relief Dampers), 3.2.3 (Basic Model),
3.2.5 (Commercial and Industrial Unitary Airconditioning Equipment), 3.2.5.1 (Commercial and
Industrial Unitary Air-Conditioning System), 3.2.5.2
(Commercial and Industrial Unitary Heat Pump),
3.2.7 (Double-duct System), 3.2.9 (Desiccant
Dehumidification Component), 3.2.10 (Drain Pan
Heater), 3.2.11.1 (Air Economizer), 3.2.12 (Energy
Efficiency Ratio 2), 3.2.13 (Evaporative Cooling),
3.2.13.1 (Direct Evaporative Cooling System),
3.2.13.2 (Indirect Evaporative Cooling System),
3.2.14 (Fresh Air Damper), 3.2.15 (Fire, Smoke, or
Isolation Damper), 3.2.17 (Hail Guard), 3.2.19
(Heating Coefficient of Performance 2), 3.2.20
(High-Effectiveness Indoor Air Filtration), 3.2.22
(Indoor Single Package Air-conditioners), 3.2.23
(Integrated Ventilation, Economizing, and Cooling
Efficiency (IVEC)), 3.2.34 (Integrated Ventilation
and Heating Efficiency (IVHE)), 3.2.29 (Nonstandard Ducted Condenser Fan), 3.2.31.2 (Boost2
Heating Operational Level (B2)), 3.2.34 (Power
Correction Capacitor), 3.2.35 (Powered Exhaust Air
Fan), 3.2.36 (Powered Return Air Fan), 3.2.37
(Process Heat Recovery, Reclaim, or Thermal
Storage Coil), 3.2.38 (Published Rating), 3.2.41
(Refrigerant Reheat Coil), 3.2.42 (Single Package
Air-Conditioners), 3.2.43 (Single Package Heat
Pumps), 3.2.45 (Sound Trap), 3.2.46 (Split System),
3.2.51 (Steam or Hydronic Heat Coils), 3.2.53 (UV
Lights), 3.2.55 (Ventilation Energy Recovery System
(VERS)), 3.2.56 (Year Round Single Package Airconditioners), and 3.2.57 (Year Round Single
Package Heat Pump).
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
terms of the new metrics in appendix
A1, should such standards be adopted.
As proposed, for appendices A and
A1, DOE is incorporating by reference
ANSI/ASHRAE 37–2009. Appendices A
and A1 reference all sections of the
industry test standard except sections 1
(Purpose), 2 (Scope), and 4
(Classifications).
2. Double-Duct Systems
As discussed in section III.B.3 of this
final rule, double-duct systems are
equipment classes of ACUACs and
ACUHPs, either single package or split,
designed for indoor installation in
constrained spaces, such that outdoor
air must be ducted to and from the
outdoor coil.
Pursuant to the current DOE test
procedure (which references ANSI/
AHRI 340/360–2007), double-duct
systems are tested and rated under the
same test conditions at zero outdoor air
ESP as conventional ACUACs and
ACUHPs (i.e., that are not double-duct
systems). AHRI 340/360–2022 includes
two different set of test provisions that
can be used for testing double-duct
systems. Section 6.1.3.7 of AHRI 340/
360–2022 includes provisions for
measuring performance at zero outdoor
air ESP to determine the EER, IEER,
and/or COP metrics, consistent with the
current DOE test procedure. AHRI 340/
360–2022 added an additional test
method in appendix I for double-duct
systems that specifies an outdoor air
ESP requirement of 0.50 in. H2O for
double-duct systems. When testing with
0.50 in. H2O outdoor air ESP, ratings are
designated with the subscript ‘‘DD’’
(e.g., EERDD, COPDD, and IEERDD) to
distinguish them from the ratings
determined by testing at zero outdoor
air ESP. ASHRAE Standard 90.1–2022
does not include any separate
provisions for double-duct systems or
the EERDD, COPDD, and/or IEERDD
metrics; therefore, testing per Appendix
I to AHRI 340/360–2022 is not required
per ASHRAE Standard 90.1–2022. As a
result, DOE’s statutory obligation to
consider the test procedures for CUACs
and CUHPs referenced in ASHRAE
Standard 90.1 (per 42 U.S.C.
6314(a)(4)(A)) does not include
Appendix I to AHRI 340/360–2022.
The ACUAC and ACUHP Working
Group TP Term Sheet did not include
provisions for double-duct systems.
However, the AHRI 1340–202X Draft
included provisions for determining the
new IVEC and IVHE metrics for doubleduct systems. Specifically, similar to
appendix I of AHRI 340/360–2022, the
AHRI 1340–202X Draft applied a 0.50
in. H2O outdoor air ESP requirement for
determining IVEC and IVHE for double-
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
duct systems. Other than this outdoor
air ESP requirement, the AHRI 1340–
202X Draft specified no differences in
determining IVEC and IVHE for doubleduct systems as compared to
conventional ACUACs and ACUHPs. In
the August 2023 TP NOPR, DOE
proposed to: (1) maintain the existing
metrics for double-duct systems and
reference AHRI 340/360–2022 for
double-duct systems in appendix A, and
(2) adopt the IVEC and IVHE metrics for
double-duct systems in appendix A1 as
specified in the AHRI 1340–202X Draft.
88 FR 56392, 56421–56422 (August 17,
2023).
In response, Carrier supported the
adoption of the IVEC and IVHE metric,
as specified in AHRI 1340–202X, in
appendix A1, as well as the proposal to
maintain the test procedure from AHRI
340/360–2022 in appendix A without
the provisions of appendix I of that test
procedure. (Carrier, No. 8 at p. 3) AHRI
similarly supported the adoption of
IVEC and IVHE for double-duct systems
in appendix A1. (AHRI, No. 15 at p. 2)
DOE notes that AHRI 1340–2023
maintains the same ESP conditions and
method for determining IVEC and IVHE
for double-duct systems as the method
specified in the AHRI 1340–202X Draft.
Because double-duct systems are
installed indoors with ducting of
outdoor air to and from the outdoor coil,
DOE has concluded that testing at a
non-zero outdoor air ESP (as specified
in the AHRI 1340–2023) would be more
representative of field applications than
testing at zero outdoor air ESP (as
specified in the current Federal test
procedure). DOE has also concluded
that the IVEC and IVHE metrics
specified in AHRI 1340–2023 better
capture actual energy use in the field
than the COP, EER, and IEER metrics
specified in the current DOE test
procedure, for the reasons discussed
throughout this final rule for ACUACs
and ACUHPs more generally. Further,
DOE has concluded that the application
of the IVEC and IVHE metrics in AHRI
1340–2023 to double-duct systems
reflect industry consensus that these
metrics are suitable for double-duct
systems. For these reasons and given the
support expressed by stakeholders, DOE
is adopting the provisions in AHRI
1340–2023 for determining IVEC and
IVHE for double-duct systems in
appendix A1.
As mentioned previously, the current
cooling energy conservation standards
for double-duct systems are in terms of
EER and the current heating energy
conservation standards are in terms of
COP. Testing to the IVEC and IVHE
metrics will not be required until such
time as compliance is required with
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
amended energy conservation standards
for double-duct systems denominated in
terms of IVEC and IVHE, should DOE
adopt such standards. As discussed,
DOE is also updating the current test
procedure for all CUACs and CUHPs,
including double-duct systems, in
appendix A to reference AHRI 340/360–
2022, maintaining the current EER and
COP metrics until the compliance date
of any energy conservation standards for
double-duct systems denominated in
terms of IVEC and IVHE. As discussed,
ASHRAE Standard 90.1–2022 does not
include any provisions specific to
double-duct systems or standards
denominated in terms of the EERDD,
COPDD, and/or IEERDD metrics;
therefore, testing double-duct systems at
non-zero outdoor air ESP per Appendix
I to AHRI 340/360–2022 which
generates results in terms of EERDD,
COPDD, and/or IEERDD (as opposed to
testing a zero outdoor air ESP per
section 6.1.3.7 of AHRI 340/360–2022
which generates results in terms of EER,
COP, and/or IEER) is not required per
ASHRAE Standard 90.1–2022. As a
result, DOE’s statutory obligation to
consider the test procedures for CUACs
and CUHPs referenced in ASHRAE
Standard 90.1 (per 42 U.S.C.
6314(a)(4)(A)) does not include
Appendix I to AHRI 340/360–2022.
3. ECUACs and WCUACs
a. Overall
The current DOE test procedure for
ECUACs and WCUACs is specified at 10
CFR 431.96 and includes the EER
metric. The ACUAC and ACUHP
Working Group TP Term Sheet does not
include provisions for ECUACs and
WCUACs. However, the AHRI 1340–
202X Draft includes provisions for
determining the new IVEC and optional
EER2 metric for ECUACs and WCUACs.
The AHRI 1340–202X Draft and AHRI
1340–2023 provisions for determining
IVEC and EER2 for ECUACs and
WCUACs are largely the same as the
provisions for ACUACs and ACUHPs;
however, there are several provisions
specific or unique to ECUACs and
WCUACs, specifically regarding: (1) ESP
requirements, (2) test temperatures, and
(3) accounting for power of WCUAC
heat rejection components.
In the August 2023 TP NOPR, DOE
proposed to adopt the IVEC metric for
ECUACs and WCUACs in appendix A1,
as specified in the AHRI 1340–202X
Draft, and sought comment on this
proposal, including the test temperature
requirements. 88 FR 56392, 56419–
56420 (August 17, 2023).
In response to the August 2023 TP
NOPR, Carrier supported the adoption
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
44003
of the IVEC metric for ECUACs and
WCUACs in appendix A1 as specified in
the proposed AHRI 1340–202X Draft.
(Carrier, No. 8 at p. 2) Carrier also
commented that the working version of
AHRI 1340 (at the time of Carrier’s
comment) included updated test
temperatures for determining IVEC and
EER2 for ECUACs and WCUACs, and
Carrier presented these updated test
conditions. (Id.) AHRI also expressed
support for DOE’s proposal to adopt the
IVEC and IVHE metrics for ECUACs and
WCUACs. (AHRI, No. 15 at pp. 2, 5)
Trane supported the product
classifications and water temperatures
for WCUACs in AHRI 1340 but did not
support adopting the IVEC metric for
WCUACs as specified in AHRI 1340.
Trane further stated that issues specific
to WCUACs need to be addressed in
order to adopt an IVEC metric for
WCUACs that is truly representative of
field applications. Trane asserted that
the provisions in AHRI 1340 do not
adequately consider the difference
between indoor and outdoor single
package units and stated that the vast
majority of WCUACs are indoor
packaged units. Trane further
commented that WCUACs installed
indoors most often use waterside
economizers rather than airside
economizers and are typically installed
in the core of a multi-story office
building, such that outdoor air for
economizing or ventilation is not
introduced through the WCUAC air
handling section. Trane also commented
that because WCUACs typically
distribute conditioned air only within a
single floor of a building, duct runs are
typically shorter than for traditional
rooftop systems, and, therefore, the ESP
conditions included in AHRI 1340
should be different for WCUACs.
(Trane, No. 14 at pp. 3–4)
Regarding Trane’s concerns about the
IVEC metric for WCUACs, DOE
acknowledges that WCUACs have a
range of applications that may not
always align with the assumptions
included in the analyses to develop the
IVEC metric. However, DOE notes that
this is also true for ACUACs and
ACUHPs, which serve a wide range of
applications and operate in a wide
variety of different operating conditions.
The intent of the IVEC metric, as
developed by the Working Group, was
to representatively capture performance
of the U.S. national average of CUAC
and CUHP applications, understanding
that this ‘‘average performance’’ cannot
perfectly represent the unique aspects of
certain applications. DOE notes that the
IVEC metric is specified for WCUACs in
the recently published industry
consensus test procedure AHRI 1340–
E:\FR\FM\20MYR2.SGM
20MYR2
44004
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
2023 consistent with DOE’s proposals
(with certain updated test conditions, as
discussed). Therefore, DOE understands
AHRI 1340–2023 and the IVEC metric
specified in the test procedure to
represent general industry consensus on
a representative test procedure and
metric for CUACs and CUHPs, including
WCUACs.
AHRI 1340–2023 includes updates to
the provisions for determining IVEC for
ECUACs and WCUACs—specifically,
the test temperature and accounting for
power of WCUAC heat rejection
components. The ESP requirements
specified for ECUACs and WCUACs are
unchanged from the AHRI 1340–202X
Draft. These provisions are discussed in
detail in the following subsections. DOE
has concluded that the IVEC metric
specified in AHRI 1340–2023 for
ECUACs and WCUACs (including the
ESP requirements, updated test
temperatures, and updated WCUAC
heat rejection component power
allowances) is consistent with the
proposed adoption of the IVEC metric
specified in the AHRI 1340–202X Draft
and meets the criteria in 42 U.S.C.
6314(a)(2)–(3). Accordingly, DOE is
adopting the IVEC metric (as well as the
optional EER2 metric) and associated
test provisions specified in AHRI 1340–
2023 in appendix A1 for ECUACs and
WCUACs.
As mentioned previously, the current
energy conservation standards for
ECUACs and WCUACs are in terms of
EER. Testing to the IVEC metric will not
be required until such time as
compliance is required with amended
energy conservation standards for
ECUACs and WCUACs denominated in
terms of IVEC, should DOE adopt such
standards. As discussed, DOE is also
updating the current test procedure for
all CUACs and CUHPs, including
ECUACs and WCUACs, in appendix A
to reference AHRI 340/360–2022,
maintaining the current EER metric
until the compliance date of any energy
conservation standards for ECUACs and
WCUACs denominated in terms of the
IVEC metric. As discussed in section
III.C.1 of this final rule, DOE has
concluded that this amendment in
Appendix A is consistent with the
intent of the test procedure references
for ECUACs and WCUACs in the latest
published version of ASHRAE Standard
90.1.
b. ESP Requirements for ECUACs and
WCUACs
The IVEC and EER2 metrics include
higher ESP requirements than the
current DOE test procedures and AHRI
340/360–2022. For ECUACs and
WCUACs with cooling capacity greater
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
than or equal to 65,000 Btu/h, the AHRI
1340–202X Draft specifies the same ESP
requirements for determining IVEC and
EER2 for ECUACs and WCUACs as for
ACUACs and ACUHPs. For ECUACs
and WCUACs with cooling capacity less
than 65,000 Btu/h, there are no aircooled equipment of comparable
cooling capacity within the scope of the
AHRI 1340–202X Draft. Therefore, the
AHRI 1340–202X Draft includes an ESP
requirement of 0.5 in. H2O for testing
ECUACs and WCUACs with cooling
capacity less than 65,000 Btu/h, which
is consistent with the ESP requirement
specified in AHRI 210/240–2023 for
comparable air-cooled equipment (i.e.,
air-cooled, three-phase CUACs and
CUHPs with cooling capacity less than
65,000 Btu/h). As discussed in the
August 2023 TP NOPR, DOE understood
that the provisions for determining IVEC
and EER2 for ECUACs and WCUACs,
specifically including the higher ESP
requirements outlined in the AHRI
1340–202X Draft, reflect industry
consensus that the IVEC metric (and
optional EER2 metric) provide a more
representative measure of energy
efficiency for ECUACs and WCUACs. 88
FR 56392, 56419–56420 (August 17,
2023). AHRI 1340–2023 maintains the
same ESP requirements as those
outlined in the AHRI 1340–202X Draft.
In this final rule, DOE maintains its
conclusion that the ESP requirements
specified for ECUACs and WCUACs in
AHRI 1340–2023 are representative of
field installations for ECUACs and
WCUACs. As such, DOE is adopting the
ESP requirements for testing ECUACs
and WCUACs as outlined in AHRI
1340–2023.
c. ECUAC and WCUAC Test
Temperatures and WCUAC Heat
Rejection Components
ECUACs and WCUACs use different
test temperatures than ACUACs and
ACUHPs, and in the August 2023 TP
NOPR, DOE presented test temperature
requirements for full-load and part-load
test points for determining IVEC for
ECUACs and WCUACs, as specified in
the AHRI 1340–202X Draft. 88 FR
56392, 56419–56420 (August 17, 2023).
WCUACs are typically installed in the
field with separate heat rejection
components 16 that reject heat from the
16 Separate heat rejection components (e.g., a
cooling tower or circulating water pump) are
required for WCUACs but not used with ACUACs
or ECUACs. ACUACs and ECUACs contain all
components needed to reject heat to the ambient air
surrounding the ACUAC or ECUAC. WCUACs,
however, reject heat to a building’s water loop.
Separate components are needed to circulate the
water in the water loop and reject heat from the
water loop to the ambient air surrounding the
building.
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
water loop to outdoor ambient air, but
these separate heat rejection
components are not installed nor is their
power measured during testing of
WCUACs under the current DOE test
procedure. These heat rejection
components typically consist of a
circulating water pump (or pumps) and
a cooling tower. To account for the
power that would be consumed by these
components in field installations,
section 6.1.1.7 of AHRI 340/360–2022
specifies that WCUACs with cooling
capacities less than 135,000 Btu/h shall
add 10.0 W to the total power of the unit
for every 1,000 Btu/h of cooling
capacity.
Section 6.2.4.3 of the AHRI 1340–
202X Draft includes similar provisions
for accounting for the power of heat
rejection components for WCUACs to
those in AHRI 340/360–2022. However,
unlike AHRI 340/360–2022, the heat
rejection component power addition
was not limited to units with cooling
capacities less than 135,000 Btu/h in the
AHRI 1340–202X Draft, and instead, it
applied to WCUACs of all cooling
capacities. DOE proposed the adoption
of the approach specified in the AHRI
1340–202X Draft in the August 2023 TP
NOPR. 88 FR 56392, 56420–56421
(August 17, 2023).
As noted by Carrier’s comment
(summarized in section III.E.3.a of this
document), based on further discussions
and analysis in AHRI Commercial
Unitary STC meetings after the issuance
of the AHRI 1340–202X Draft, the test
conditions for ECUACs and WCUACs
were updated in the published AHRI
1340–2023. Additionally, AHRI 1340–
2023 includes different values to
account for the power of heat rejection
components of WCUACs as compared to
the AHRI 1340–202X Draft. Both of
these changes were related to a changed
assumption in operation of cooling
towers in water loops serving WCUACs.
The analysis conducted to develop
the heat rejection component power
adder and the WCUAC entering water
temperature (‘‘EWT’’) test conditions in
the AHRI 1340–202X Draft assumed
constant cooling tower fan speed
regardless of load level. In other words,
the analysis to develop the AHRI 1340–
202X Draft method assumed that the
cooling tower fans do not slow down
when there is less heat to reject in the
cooling tower, and thus: (1) the cooling
tower fan power does not reduce at
lower load levels; and (2) the cooling
tower approach 17 reduces significantly
17 For an evaporative cooling tower, the ‘‘cooling
tower approach’’ is the difference between the cold
water temperature (i.e., the temperature of the
cooled water leaving the cooling tower) and the
outdoor air wet-bulb temperature.
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
at lower load levels. Specifically, as the
cooling load reduces, the same amount
of cooling tower airflow is being
provided to reject less heat in the
cooling tower, so the water is cooled in
the cooling tower to a temperature
closer to the outdoor air wet-bulb
temperature, and, therefore, the water
leaving the cooling tower (and entering
the WCUAC) is at a lower temperature,
resulting in a lower WCUAC EWT test
condition.
The analysis conducted to develop
the heat rejection component power
adder and the WCUAC EWT test
conditions in AHRI 1340–2023 assumes
that variable frequency drives (‘‘VFDs’’)
are used on cooling tower fans to reduce
cooling tower fan speed (and thus
cooling tower fan power) for lower
cooling loads. The use of VFDs on
cooling tower fans impacts both the
cooling tower fan power and the
WCUAC EWT. First, the cooling tower
fan VFD reduces cooling tower fan
power at part load. Therefore, instead of
a single power adder in W per 1,000
Btu/h of cooling capacity applied
regardless of the test being conducted
(i.e., independent of the test bin) as
specified in the AHRI 1340–202X Draft,
AHRI 1340–2023 includes four different
condenser tower fan and pump power
rate adders (in units of W per 1,000 Btu/
h of cooling capacity)—a separate adder
for each test bin, with the adders
decreasing at lower load levels. Second,
the reduced cooling tower fan speed at
part load means that the cooling tower
approach does not significantly reduce
at lower load levels, because cooling
tower airflow driving heat transfer in
the cooling tower reduces along with
the amount of heat rejected.18
Correspondingly, the WCUAC part-load
EWT test conditions in AHRI 1340–2023
are higher than the EWT test conditions
in the AHRI 1340–202X Draft. The EWT
test conditions for WCUACs in AHRI
1340–2023, which were developed
44005
based on the assumption that VFDs are
used on cooling tower fans to reduce
cooling tower fan speed, are the same as
those included in Carrier’s comment
(Carrier, No. 8 at p. 2) in response to the
August 2023 TP NOPR.
Additionally, AHRI 1340–2023
includes slight changes to the outdoor
air wet-bulb temperature test conditions
for ECUACs, based on updated analysis
of representative temperatures. The
outdoor air wet-bulb temperature
requirements for ECUACs in AHRI
1340–2023 are the same as those
included in Carrier’s comment (Carrier,
No. 8 at p. 2) in response to the August
2023 TP NOPR.
Table III–3 and Table III–4 show the
test temperatures included in the AHRI
1340–202X Draft and the final test
temperatures included in AHRI 1340–
2023 for ECUACs and WCUACs,
respectively.
Table 111-3 IVEC Test Temperatures for ECUACs
Test
Point
A
B
C
D
ARRI 1340-202X Draft IVEC Test
Temperatures
Make-up
Outdoor Air Outdoor Air
Dry-Bulb
Wet-Bulb
Water (°F)
(OF)
(OF)
95
75
85
85
65
77
75
57
77
52
65
77
ARRI 1340-2023 IVEC Test
Temperatures
Make-up
Outdoor Air Outdoor Air
Dry-Bulb
Wet-Bulb
Water (°F)
(OF)
(OF)
95
75
85
85
66
77
75
58
77
65
53
77
Table 111-4 IVEC Test Temperatures for WCUACs
62
55
* The ARRI 1340-202X Draft and ARRI 1340-2023 include a leaving water temperature condition only for
the A test. Testing with the specified entering and leaving water temperature test determines the water flow
rate used for the A test. For part-load tests, the ARRI 1340-202X Draft and ARRI 1340-2023 specify that
the part-load water flow rate be set per the manufacturer's installation instructions; and for any full-load
tests conducted at B, C, or D rating points (i.e., for interpolation to reach the target percent load), that the
water flow rate used match the flow rate measured for the A test. Therefore, a leaving water temperature is
not specified for the B, C, and D tests.
18 For the AHRI 1340–2023 EWTs, the assumed
cooling tower approach is the same for B, C, and
D bins –i.e., as shown in Table III–3 and Table III–
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
4, the difference between the outdoor air wet-bulb
temperature in Table III–3 and the EWT in Table
III–4 is 8 °F for the B, C, and D bins. Therefore, the
PO 00000
Frm 00021
Fmt 4701
Sfmt 4725
EWT test conditions in AHRI 1340–2023 decrease
for each part-load bin by the same amount as the
outdoor air wet-bulb temperature test conditions.
E:\FR\FM\20MYR2.SGM
20MYR2
ER20my24.131
-
72
ARRI 1340-2023 IVEC Test
Temperatures
Entering Water
Leaving Water (°F)*
(OF)
85
95
74
66
61
-
ER20my24.130
lotter on DSK11XQN23PROD with RULES2
Test
Point
A
B
C
D
ARRI 1340-202X Draft IVEC Test
Temperatures
Entering Water
Leaving Water
(OF)
(OF)*
85
95
44006
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
Regarding the minor revisions to the
ECUAC outdoor air wet-bulb
temperatures in AHRI 1340–2023, DOE
has concluded that these updated
temperatures are representative of
applications for ECUACs, and that
adopting these slight updates to the
proposed ECUAC test temperatures is
consistent with the intent of the
proposed approach and with comments
from Carrier that included these
updated temperatures. Therefore, in this
final rule, DOE is adopting the ECUAC
test temperatures specified in AHRI
1340–2023.
Regarding the test temperatures and
heat rejection component power for
WCUACs, DOE has concluded that
VFDs are typically used on cooling
tower fans to reduce cooling tower fan
speed with reduced cooling load, and,
therefore, concludes that assuming the
presence of cooling tower fan VFDs is a
more representative basis for
determining the WCUAC EWTs and
tower fan and pump power rate or
‘‘TFPPR’’ adders. Additionally, DOE has
concluded that the updates to the
approach in AHRI 1340–2023 (i.e.,
updated WCUAC test temperatures and
updated TFPPR approach) are generally
consistent with the approach proposed
in the August 2023 TP NOPR, but with
more representative technical details.
Further, DOE concludes that adopting
the updated WCUAC test temperatures
(and, thus, generally, the updated
approach for developing WCUAC test
temperatures and TFPPR values that
assumes cooling tower fan VFDs) is
consistent with comments from Carrier
that included these updated
temperatures.
However, DOE is aware of three issues
in the WCUAC heat rejection
components power adders (referred to
in AHRI 1340–2023 as the TFPPR) used
in Table 7 to AHRI 1340–2023. The first
issue is a mismatch between how the
TFPPR values were developed and how
they were implemented in AHRI 1340–
2023. Specifically, the TFPPR values in
Table 7 to AHRI 1340–2023 were
determined based on the full-load
cooling capacity; therefore, the TFPPR
value for each bin was intended to be
multiplied by the full-load capacity.
However, the approach implemented in
AHRI 1340–2023 is inconsistent with
these values—specifically, equations 8,
10, 11, and 13 specify to multiply the
TFPPR by the cooling capacity
determined for the test(s) performed for
a given cooling bin. Because part-load
cooling capacities are lower than fullload cooling capacities, multiplying the
TFPPR value for a part-load cooling bin
by the part-load capacity for that bin
results in an unrepresentatively low
tower fan and pump power calculated
for the bin. To resolve this issue, DOE
has concluded that the values should
instead be based on the target cooling
capacity for each part-load cooling bin,
which aligns with the approach in
equations 8, 10, 11, and 13 of AHRI
1340–2023 (i.e., multiplying the TFPPR
values by the measured cooling capacity
for each bin).
The second issue is that the full-load
cooling tower fan power was developed
without consideration of the cooling
tower fan motor efficiency; therefore,
the calculation reflected a fan motor
efficiency of 100 percent. Because 100
percent is a physically impossible motor
efficiency (and, therefore,
underestimates the amount of power a
fan motor consumes), DOE has
concluded that the TFPPR values
should include a more representative
(i.e., lower) full-load fan motor
efficiency.
The third issue is that the TFPPR
values in AHRI 1340–2023 are based on
an unrepresentatively low fan power at
low loads. Specifically, the fan power
was assumed to decrease cubically with
decreasing cooling load.19 However, this
assumption does not account for VFD,
motor, and transmission losses which
do not decrease cubically with
decreasing cooling load. At low cooling
load (e.g., for the D bin), this
significantly underestimates cooling
tower fan power because the VFD,
motor, and transmission losses are
underestimated. DOE has concluded
that a more representative approach
would be to account for the VFD, motor,
and transmission losses when
developing the relationship between
cooling tower fan power and load.
Accounting for these losses impacts the
TFPPR values for the B, C, and D partload bins.
Corrected TFPPR values that address
these three issues with the values
published in AHRI 1340–2023 are
shown in Table III–5. DOE understands
that the AHRI Commercial Unitary STC
also plans to address the
aforementioned issues with the TFPPR
values that were published in AHRI
1340–2023. DOE expects that AHRI will
consider including the corrected TFPPR
values shown in Table III–5 and
adopted in this final rule in a future
version of AHRI 1340.
Table 111-5 IVEC TFPPR Values for WCUACs
lotter on DSK11XQN23PROD with RULES2
A
B
C
D
Corrected TFPPR Values
(W/1,000 Btu/h)
0.0102
0.0099
0.0121
0.0430
For the reasons discussed in detail in
the previous paragraphs, DOE has
concluded that the updated TFPPR
values shown in Table III–5 are
generally consistent with the approach
proposed in the August 2023 TP NOPR,
but that the corrected TFPPR values
provide a more representative
accounting of WCUAC heat rejection
component power than the values
published in AHRI 1340–2023 or the
AHRI 1340–202X Draft.
For these reasons, DOE is adopting
the updated WCUAC IVEC test
temperatures for IVEC in AHRI 1340–
2023 and the TFPPR approach in AHRI
1340–2023 as modified by the revised
TFPPR values shown in Table III–5.
19 The theoretical fan laws indicate that fan power
decreases cubically with decreasing fan speed. It
was assumed that cooling tower fan speed is
proportional to cooling load (i.e., heat to be rejected
in the cooling tower), and, therefore, that cooling
tower fan power decreases cubically with
decreasing cooling load.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
4. IVHE for Colder Climates
As discussed in the August 2023 TP
NOPR (see 88 FR 56392, 56416 (August
17, 2023)), it is likely that in the future
manufacturers will develop CUHPs that
E:\FR\FM\20MYR2.SGM
20MYR2
ER20my24.132
AHRI 1340-2023 TFPPR
Values (W/1,000 Btu/h)
0.0094
0.0066
0.0053
0.0048
Test Bin
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
are designed for operation in colder
climates, and correspondingly that the
market for CUHPs in colder climates is
expected to grow. Because the IVHE
metric is based on the US national
average climate across all US climate
zones, the lowest bin temperature for
calculating IVHE is 15.9 °F, and a small
fraction of heating hours are at colder
temperatures (i.e., 19 percent of heating
hours are in a load bin with a
temperature colder than 32 °F, and less
than 1 percent of heating hours are in
a load bin with a temperature colder
than 17 °F).
As a result, the AHRI 1340–202X
Draft includes provisions that are
distinct from the provisions used for
IVHE, including weighting factors and
temperature bins, for calculating a
colder climate-specific IVHE metric,
designated as IVHEC. Specifically,
IVHEC was developed using the same
building heating analysis that was used
to develop IVHE (as discussed in section
III.D.2 of this final rule), but the IVHEC
weighting factors and load bins were
developed using the results for climates
zones 5 and above (i.e., climate zone 5
as well as all climate zones colder than
climate zone 5), weighted by the share
of the U.S. population in each of those
climate zones. The use of only climate
zones 5 and colder for IVHEC results in
the following, compared to IVHE: lower
outdoor dry-bulb temperature for each
load bin, more heating season hours in
all load bins, and a higher heating
season building load. Specifically, for
IVHEC, 56 percent of heating hours are
in a load bin with a temperature colder
than 32 °F, and 12 percent of heating
hours are in a load bin with a
temperature colder than 17 °F. Further,
because the defrost degradation
coefficients specified in appendix C of
the ACUAC and ACUHP Working Group
TP Term Sheet depend on the outdoor
temperature for each load bin (and
IVHEC has colder bin temperatures than
IVHE), the AHRI 1340–202X Draft also
specifies separate defrost degradation
coefficients for calculating IVHEC. In the
August 2023 TP NOPR, DOE proposed
to adopt provisions for determining the
IVHEC metric in appendix A1 via
reference to the AHRI 1340–202X Draft
and to allow for optional
representations of IVHEC for CUHPs. 88
FR 56392, 56416 (August 17, 2023).
In response to the August 2023 TP
NOPR, NEEA and NYSERDA supported
DOE’s proposal to include in the test
procedure and allow optional
representations of the colder climate
IVHEC. (NEEA, No. 16 at pp. 2–3;
NYSERDA, No. 13 at p. 2)
Given the potential for the
development of CUHPs designed for
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
operation in colder climates and the
expected increased number of
shipments of CUHPs into colder
climates, DOE recognizes the utility in
having CUHP ratings for a separate
IVHE metric that is specific to colder
climates. AHRI 1340–2023 includes
provisions for determining IVHEC that
are generally consistent with the AHRI
1340–202X Draft, with the additional
specificity discussed in section III.E.8 of
this final rule. Correspondingly, DOE
has concluded that the IVHEC metric as
specified in AHRI 1340–2023 (including
the minor updates in the published
AHRI 1340–2023 that provide
additional specificity as discussed in
section III.E.8 of this document) is more
representative of field conditions for
CUHPs installed in colder US climates.
Therefore, DOE is adopting provisions
for determining the IVHEC metric in
appendix A1 via reference to AHRI
1340–2023 and allowing for optional
representations of IVHEC for CUHPs.
Specifically, DOE is amending the test
procedure so that IVHE will be the
regulated heating metric when testing to
appendix A1; therefore, should DOE
adopt amended standards for CUHPs
denominated in terms of IVEC and
IVHE, all CUHPs will be required to
certify compliance with IVHE standards,
and additional representations of IVHEC
will be optional.
5. Test Conditions Used for Current
Metrics in Appendix A
AHRI 340/360–2022 designates
certain test conditions for test
procedures characterized as ‘‘standard
rating tests’’ and certain other test
conditions for test procedures
characterized as ‘‘performance operating
tests.’’ The ‘‘standard rating tests’’ are
used for determining representations of
cooling capacity, heating capacity, and
cooling and heating efficiencies. The
‘‘performance operating tests’’ evaluate
other operating conditions, such as
‘‘maximum operating conditions’’ (see
section 8 of AHRI 340/360–2022).
Specifically, Table 6 of AHRI 340/360–
2022 specifies test conditions for
standard rating and performance
operating tests for CUACs and CUHPs.
The relevant conditions for EER and
IEER cooling tests are those referred to
as ‘‘standard rating conditions’’ in AHRI
340/360–2022.
To clarify this distinction and
consistent with its proposal to adopt
AHRI 340/360–2022 in appendix A,
DOE proposed in the August 2023 TP
NOPR to specify explicitly in section 3
of appendix A that the cooling test
conditions used for representations as
required under the DOE regulations
would be: (1) for equipment subject to
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
44007
standards in terms of EER, the
‘‘Standard Rating Conditions, Cooling’’
conditions specified in Table 6 of AHRI
340/360–2022; and (2) for equipment
subject to standards in terms of IEER,
the ‘‘Standard Rating Conditions,
Cooling’’ and ‘‘Standard Rating PartLoad Conditions (IEER)’’ conditions
specified in Table 6 of AHRI 340/360–
2022. 88 FR 56392, 56412 (August 17,
2023).
For heating mode tests of CUHPs,
Table 6 of AHRI 340/360–2022 includes
‘‘Standard Rating Conditions’’ for both a
‘‘High Temperature Steady-state Test for
Heating’’ and a ‘‘Low Temperature
Steady-state Test for Heating’’
(conducted at 47 °F and 17 °F outdoor
air dry-bulb temperatures, respectively).
To clarify which conditions are
applicable for representations as
required under the DOE regulations and
consistent with its proposal to adopt
AHRI 340/360–2022 in appendix A,
DOE proposed to specify explicitly in
section 3 of appendix A that the heating
test conditions used for compliance are
the ‘‘Standard Rating Conditions (High
Temperature Steady-state Heating)’’
conditions specified in Table 6 of AHRI
340/360–2022. Further, DOE proposed
to include the low-temperature (i.e.,
17 °F) heating test condition specified in
Table 6 of AHRI 340/360–2022 (referred
to as ‘‘Low Temperature Steady-state
Heating’’) and specify in section 3 of
appendix A that representations of COP
at this low-temperature heating
condition are optional. 88 FR 56392,
56412 (August 17, 2023).
DOE did not receive any comments in
response to these proposals. Therefore,
DOE is adopting the specification of the
relevant test conditions in AHRI 340/
360–2022 in appendix A as proposed.
These amendments in appendix A are
consistent with the test requirements
referenced in the latest version of
ASHRAE Standard 90.1.
6. Test Conditions Used for New Metrics
in Appendix A1
Consistent with DOE’s proposal to
adopt the AHRI 1340–202X Draft for
determining IVEC and IVHE, as
discussed more fully in the August 2023
TP NOPR, DOE proposed to specify in
section 3 of the proposed appendix A1
which test conditions in the AHRI
1340–202X Draft would be required and
optional for rating to IVEC and IVHE. 88
FR 56392, 56412–56413 (August 17,
2023). DOE also proposed to include
provisions for optional representations
of the full-load efficiency metrics, EER2,
COP247, COP217, and COP25, and
specified the test conditions required for
these optional representations. Id. DOE
did not receive any comments regarding
E:\FR\FM\20MYR2.SGM
20MYR2
44008
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
the proposed approach for specifying
the required and optional test
conditions. The test conditions in AHRI
1340–2023 align with those in the AHRI
1340–202X Draft except for certain test
conditions for ECUACs and WCUACs,
which are discussed in section III.E.3 of
this final rule. Therefore, DOE is
adopting the specification of test
conditions in appendix A1 as proposed,
referencing the corresponding test
conditions in the published AHRI 1340–
2023.
lotter on DSK11XQN23PROD with RULES2
7. Provisions Introduced in the AHRI
1340–202X Draft
The AHRI 1340–202X Draft proposed
for adoption in the August 2023 TP
NOPR includes several provisions
regarding the new IVEC and IVHE
metrics that are not included in the
ACUAC and ACUHP Working Group TP
Term Sheet. DOE notes that the ACUAC
and ACUHP Working Group TP Term
Sheet includes provisions to allow
changes to the recommendations in the
term sheet if mistakes in the original
recommendations are identified through
further analysis or discussion between
stakeholders. (See EERE–2022–BT–
STD–0015–0065, Recommendations #2,
#8, #11) Further, the AHRI 1340–202X
Draft includes a number of additional
test provisions that arose as a result of
discussions between many interested
stakeholders participating in the AHRI
Commercial Unitary STC and that DOE
has concluded are consistent with the
intent of the ACUAC and ACUHP
Working Group TP Term Sheet but
provide additional guidance for
determining IVEC and IVHE. DOE
included discussion of provisions
regarding the topics discussed in the
following sub-sections in the August
2023 TP NOPR and proposed to adopt
the provisions in the AHRI 1340–202X
Draft regarding all of these topics. 88 FR
56392, 56416–56419 (August 17, 2023).
DOE did not receive comment regarding
the provisions in the AHRI 1340–202X
Draft addressing these topics, and these
provisions are also included in the
published AHRI 1340–2023, consistent
with DOE’s proposals in the August
2023 TP NOPR. As discussed, DOE is
adopting AHRI 1340–2023 for
determining IVEC and IVHE in
appendix A1, including these additional
provisions not specified in the ACUAC
and ACUHP Working Group TP Term
Sheet, consistent with proposals in the
August 2023 TP NOPR. The following
sections discuss these provisions in
further detail.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
a. Cooling Weighting Factors
Adjustment
Subsequent to the development of the
ACUAC and ACUHP Working Group TP
Term Sheet, additional analysis of the
building models used to develop the
weighting factors for the IVEC metric
indicated that the recommended
weighting hours included in the
ACUAC and ACUHP Working Group TP
Term Sheet are incorrect. Specifically,
the weighting hour factors in the
ACUAC and ACUHP Working Group TP
Term Sheet over-represent mechanicalonly cooling hours and underrepresent
economizer-only and integratedeconomizer hours for all IVEC load bins.
DOE presented corrected weighting
factors during the ACUAC and ACUHP
standards negotiations, and no concerns
were raised. (See EERE–2022–BT–STD–
0015–0078 at p. 8) These corrected IVEC
weighting factors were included in the
AHRI 1340–202X Draft and remain the
same in AHRI 1340–2023. DOE is
adopting AHRI 1340–2023 for
determining IVEC and IVHE in
appendix A1, including these updated
IVEC weighting factors.
b. ESP Testing Target Calculation
Recommendation #12 of the ACUAC
and ACUHP Working Group TP Term
Sheet includes an equation for
determining adjusted ESP for cooling or
heating tests that use an airflow that
differs from the full-load cooling
airflow. However, the equation specified
in Recommendation #12 is missing a
term for the full-load ESP. This equation
was corrected in the AHRI 1340–202X
Draft and remains the same in AHRI
1340–2023. DOE is adopting AHRI
1340–2023 for determining IVEC and
IVHE in appendix A1, including this
corrected equation for determining
adjusted ESP.
c. Test Instructions for Splitting ESP
Between Return and Supply Duct
As discussed previously,
Recommendation #12 of the ACUAC
and ACUHP Working Group TP Term
Sheet specifies that ESP shall be split
between return and supply ducts during
testing, such that 25 percent of the ESP
is applied in the return ductwork.
However, the ACUAC and ACUHP
Working Group TP Term Sheet does not
contain explicit test se-tup instructions
specifying how to achieve the split in
ESP between return and supply
ductwork. Section E11 in appendix E of
the AHRI 1340–202X Draft and section
E11 in appendix E of AHRI 1340–2023
include more detailed instructions
regarding the duct and pressure
measurement set-up, the measurement
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
and adjustment of the return static
pressure, and the restriction devices that
can be used in the return ductwork to
achieve the required split of between 20
and 25 percent of the total ESP applied
to the return ductwork. The AHRI 1340–
202X Draft and AHRI 1340–2023 also
include the same test instructions for
cases in which the ESP split is not
achieved in the first test, as well as any
exceptions to the specified tolerance
requirement. DOE has concluded that
these additional instructions provide a
more consistent measurement of ESP
and are aligned with the intent of
Recommendation #12 of the ACUAC
and ACUHP Working Group TP Term
Sheet. Therefore, DOE is adopting these
provisions of AHRI 1340–2023 for
determining IVEC and IVHE.
d. Default Fan Power and Maximum
Pressure Drop for Coil-Only Systems
DOE’s current test procedure for
CUACs and CUHPs references ANSI/
AHRI 340/360–2007, and section 6.1 of
that test standard specifies default fan
power and corresponding capacity
adjustment for ACUACs, ACUHPs,
ECUACs, and WCUACs with a coil-only
configuration (i.e., without an integral
indoor fan). Specifically, ANSI/AHRI
340/360–2007 requires that an indoor
fan power of 365 Watts (‘‘W’’) per 1,000
standard cubic feet per minute (‘‘scfm’’)
be added to power input for coil-only
units and that the corresponding heat
addition (i.e., 1,250 Btu/h per 1,000
scfm) be subtracted from measured
cooling capacity (and added to
measured heating capacity), regardless
of the capacity of the unit under test and
regardless of full-load or part-load test
conditions.
Section 6.1.1.6 of AHRI 340/360–2022
has the same requirement as ANSI/
AHRI 340/360–2007 regarding default
fan power and capacity adjustment of
coil-only systems. Additionally, both
section 6.1.3.2(d) of ANSI/AHRI 340/
360–2007 and section 6.1.3.3.4 of AHRI
340/360–2022 specify that for coil-only
systems, the pressure drop across the
indoor assembly shall not exceed 0.30
in. H2O for the full-load cooling test. If
the measured pressure drop exceeds
that value, then the industry test
standards specify that the indoor airflow
rate be reduced such that the measured
pressure drop does not exceed the
specified maximum pressure drop.
The AHRI 1340–202X Draft included
different requirements for testing coilonly units as compared to ANSI/AHRI
340/360–2007 and AHRI 340/360–2022.
First, section 5.17.4 of the AHRI 1340–
202X Draft includes a higher maximum
pressure drop across the indoor
assembly of 1.0 in. H2O when testing
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
coil-only units, as compared to the
maximum pressure drop of 0.3 in. H2O
specified in ANSI/AHRI 340/360–2007
and AHRI 340/360–2022. Second,
section 6.2.4.2 of the AHRI 1340–202X
Draft includes higher default fan power
values than specified in ANSI/AHRI
340/360–2007 and AHRI 340/360–2022;
these values were updated to reflect the
higher ESP requirements used for IVEC
and IVHE. Because the ACUAC and
ACUHP Working Group TP Term Sheet
and the AHRI 1340–202X Draft specify
ESP requirements that vary by capacity
bin, section 6.2.4.2 of the AHRI 1340–
202X Draft specifies different default fan
power adders and capacity adjustments
for each capacity bin, developed based
on fan power needed to overcome the
ESP requirement for each bin. DOE
proposed in the August 2023 TP NOPR
to adopt the default fan power adders
and capacity adjustments included in
the AHRI 1340–202X Draft in appendix
A1. 88 FR 56392, 56417 (August 17,
2023).
Lastly, while ANSI/AHRI 340/360–
2007 and AHRI 340/360–2022 specify a
single default fan power adder (and
corresponding capacity adjustment) to
be used for all tests, the AHRI 1340–
202X Draft included separate default fan
power adders and capacity adjustments
for full-load tests and part-load tests
(i.e., tests conducted at an airflow lower
than the full-load cooling airflow) to
reflect that fan power does not decrease
linearly with airflow (i.e., reducing
airflow in part-load operation would
reduce fan power in field operation by
more than would be calculated using a
single power adder that is normalized
by airflow). These part-load fan power
adders and capacity adjustments were
developed assuming a part-load airflow
that is 67 percent of the full-load
airflow. The AHRI 1340–202X Draft
does not specify what values to use if
the part-load airflow is between 67 and
100 percent of the full-load airflow.
Alongside proposing to adopt the fan
power adders specified in the AHRI
1340–202X Draft in the August 2023 TP
NOPR, DOE proposed to adopt a linear
interpolation approach in appendix A1
in the case where the part-load airflow
for coil-only CUACs and CUHPs
specified by a manufacturer for a test is
between 67 and 100 percent of the fullload airflow, which would specify how
to calculate the default fan power
coefficient and capacity adjustment in
such cases. 88 FR 56392, 56417 (August
17, 2023). The proposed approach is
consistent with the approach adopted
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
for the residential CAC/HP test
procedure.20
Consistent with the basis of part-load
values in the AHRI 1340–202X Draft on
67 percent of full-load cooling airflow,
DOE also proposed in the August 2023
TP NOPR to clarify that for tests in
which the manufacturer-specified
airflow is less than the full-load cooling
airflow, the target airflow for the test
must be the higher of: (1) the
manufacturer-specified airflow for the
test; or (2) 67 percent of the airflow
measured for the full-load cooling test.
88 FR 56392, 56417 (August 17, 2023).
AHRI 1340–2023 includes provisions
consistent with those DOE proposed to
adopt for testing coil-only units in the
August 2023 TP NOPR. Id. Specifically,
the already discussed maximum
pressure drop and capacity and fan
power adjustments included in sections
5.17.4 and 6.2.4.2 of the AHRI 1340–
202X Draft are included in sections
5.17.2 and 6.2.4.3 of AHRI 1340–2023.
Additionally, AHRI 1340–2023 includes
provisions consistent with DOE’s
proposals regarding issues for testing
coil-only units not addressed in the
AHRI 1340–202X Draft. Specifically,
section 6.2.4.2 of AHRI 1340–2023
includes the linear interpolation method
to address cases in which the part-load
airflow specified by a manufacturer for
a test is between 67 and 100 percent of
the full-load airflow. Further, section
5.18.4.2 of AHRI 1340–2023 includes
the clarification regarding which target
airflow should be used for tests in
which the manufacturer-specified
airflow is less than the full-load cooling
airflow.
Accordingly, DOE has concluded that
the coil-only test procedure in AHRI
1340–2023 aligns with the approach
proposed in the August 2023 TP NOPR
and represents industry consensus on
the most appropriate and representative
way to test and determine the IVEC and
IVHE of coil-only systems. Therefore,
DOE is adopting these provisions of
AHRI 1340–2023 for determining IVEC
and IVHE for coil-only units.
e. Component Power Measurement
Section E10 of the AHRI 1340–202X
Draft and AHRI 1340–2023 include
additional instruction regarding how the
total unit, indoor fan, controls,
compressor, condenser section, and
crankcase heat power should be
measured and accounted for during a
test. This includes details that were not
included in the ACUAC and ACUHP
Working Group TP Term Sheet, as well
20 The CAC/HP test procedure final rule was
published in the Federal Register on October 25,
2022, and can be found at 87 FR 64550.
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
44009
as updates to address issues such as
unique model designs and power meter
precision that were identified after the
term sheet was completed. For example,
although the ACUAC and ACUHP
Working Group TP Term Sheet specified
that controls power be determined by
subtracting all other power
measurements from the total unit
power, sections E10.1 and E10.2 of both
the AHRI 1340–202X Draft and AHRI
1340–2023 require that controls power
be measured. This is because controls
power is a much smaller value than
power consumed by other components
of a CUAC or CUHP and, thus, is more
accurately determined by measuring
directly with a power meter of sufficient
precision. Section E10.2 of both the
AHRI 1340–202X Draft and AHRI 1340–
2023 also allow for determination of
compressor and condenser section
power by measurement together or by
subtraction from total power (i.e.,
separate power measurement of power
consumed by the compressor and
condenser section is not required).
These provisions address cases in which
unique wiring of certain models may
make separate measurement of
compressor and condenser section
power very difficult or impossible, in
addition to cases in which the
laboratory does not have enough power
meters to measure all components
separately. Section E10.3 of both the
AHRI 1340–202X Draft and AHRI 1340–
2023 also provide an equation for
calculating default value(s) for
crankcase heater power to address the
case in which a manufacturer does not
specify crankcase heater wattage.21
Because DOE has concluded that these
provisions will provide more repeatable
and representative test results, DOE is
adopting AHRI 1340–2023 for
determining IVEC and IVHE in
appendix A1, including these
provisions for component power
measurement.
f. Non-Standard Low-Static Indoor Fan
Motors
As discussed in section III.D.1 of this
document, DOE is adopting higher ESPs
recommended by the Working Group
and included in AHRI 1340–2023 in the
appendix A1 Federal test procedure for
CUACs and CUHPs. However,
individual models of CUACs and
CUHPs with indoor fan motors intended
21 As discussed, Recommendation #13 of the
ACUAC and ACUHP Working Group TP Term
Sheet requires that manufacturers certify crankcase
heater wattage for each heater. DOE is not adopting
amendments to certification requirements in this
rulemaking, and will instead address certification
requirements in a separate rulemaking for
certification, compliance, and enforcement.
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
44010
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
for installation in applications with a
low ESP may not be able to operate at
the adopted full-load ESP requirements
at the full-load indoor rated airflow. To
address this situation, section 3.25 of
the AHRI 1340–202X Draft and section
3.2.30 of AHRI 1340–2023 both define
‘‘non-standard low-static indoor fan
motors’’ as motors which cannot
maintain ESP as high as specified in the
test procedure when operating at the
full-load rated indoor airflow and that
are distributed in commerce as part of
an individual model within the same
basic model that is distributed in
commerce with a different motor
specified for testing that can maintain
the required ESP. Section 5.19.3.3 of the
AHRI 1340–202X Draft and section
5.19.3.3 of AHRI 1340–2023 include the
same test provisions for CUACs and
CUHPs with non-standard low-static
indoor fan motors that cannot reach the
ESP within tolerance during testing,
which require using the maximum
available fan speed that does not
overload the motor or motor drive,
adjusting the airflow-measuring
apparatus to maintain airflow within
tolerance, and operating with an ESP as
close as possible to the minimum ESP
requirements for testing. This approach
is consistent with the industry test
standard referenced by the DOE test
procedure for DX–DOASes (AHRI 920–
2020).
As discussed in section III.F.5.a of
this document, DOE is clarifying that
representations for a CUAC or CUHP
basic model must be based on the least
efficient individual model(s) distributed
in commerce within the basic model
(with the exception specified in 10 CFR
429.43(a)(3)(vi)(A) for certain individual
models with the components listed in
table 6 to 10 CFR 429.43(a)(3)). DOE has
concluded that the combination of: (1)
the provisions in AHRI 1340–2023 for
testing models with ‘‘non-standard lowstatic indoor fan motors’’ with (2) the
requirement that basic models be rated
based on the least efficient individual
model (with certain exceptions, as
discussed) provides an appropriate
approach for handling CUAC and CUHP
models with these motors—if an
individual model with a non-standard
low-static indoor fan motor is tested, the
test will be conducted at an indoor
airflow representative for that model.
But because testing at the rated airflow
for such an individual model will result
in testing at an ESP lower than the
requirement and, thus, a lower indoor
fan power, the representations for that
basic model will be required to be based
on an individual model with an indoor
fan motor that can achieve the ESP
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
requirements at the rated airflow.
Consistent with the adoption of AHRI
340/360–2023 in appendix A1, DOE is
not deviating from the provisions for
testing models with non-standard lowstatic indoor fan motors.
g. IVHE Equations
Section 6.3 of the AHRI 1340–202X
Draft and section 6.3 of AHRI 1340–
2023 both include several changes
regarding the heating metric equations
that differ from the provisions in
appendix C of the ACUAC and ACUHP
Working Group TP Term Sheet. DOE
has concluded that these updated IVHE
equations, described in the following
paragraphs, provide for a more accurate
calculation of IVHE. Further,
Recommendation #9 of the ACUAC and
ACUHP Working Group TP Term Sheet
states that the equations in appendix C
of the term sheet are subject to quality
control checking (‘‘QC’’) for errors, with
the intent remaining the same as voted
on. DOE has concluded that the
discussed deviations in the AHRI 1340–
202X Draft and the published AHRI
1340–2023 hold the same intent of the
recommendations set forth in the
ACUAC and ACUHP Working Group TP
Term Sheet. Therefore, DOE is adopting
the provisions of AHRI 1340–2023 for
determining IVHE in appendix A1,
including the updated equations
discussed in this section.
1. Removal of the cut-out factor from
certain equations: Appendix C of the
ACUAC and ACUHP Working Group TP
Term Sheet includes a cut-out factor in
IVHE calculations to reflect the
dependence of unit performance on
whether compressors are cut-out at a
given bin temperature. However, the
cut-out factor was inadvertently
included in certain equations in
appendix C of the ACUAC and ACUHP
Working Group TP Term Sheet where it
should not apply (i.e., equations to
determine unit performance that should
not be impacted by the fraction of time
in which compressors are cut out).
Therefore, in the AHRI 1340–202X Draft
and AHRI 1340–2023, the cut-out factor
is removed from those equations where
it was incorrectly applied in the ACUAC
and ACUHP Working Group TP Term
Sheet. For all CUHPs that DOE is aware
of on the market today, the cut-in and
cut-out temperatures are less than the
temperature of the lowest load bin. As
such, the cut-out factor only applies
when the unit is operating at full-load
capacity and does not affect the
calculation of IVHE.
2. Accounting for auxiliary heat when
compressors are cut out: When
compressors are cut out, auxiliary heat
would operate to meet the building
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
load. This auxiliary heat operation is
addressed in section b of appendix C of
the ACUAC and ACUHP Working Group
TP Term Sheet (i.e., when building load
exceeds the highest stage unit heating
capacity at a given bin temperature), but
was inadvertently excluded in sections
c and d of appendix C of the ACUAC
and ACUHP Working Group TP Term
Sheet (i.e., when building load is
between capacities of a unit tested with
multiple heating stages, or when
building load is less than the capacity
for the lowest tested compressor stage).
Therefore, the AHRI 1340–202X Draft
and AHRI 1340–2023 include
corrections in these cases so that
auxiliary heat demand is applied to
meet building load in all cases in which
compressors are cut out.
3. Fan power applied in auxiliary
heat-only mode: In appendix C of the
Term Sheet, the equations do not
subtract the heat gain in the indoor
airstream from the indoor fan (i.e., ‘‘fan
heat’’) from the auxiliary heat demand.
The AHRI 1340–202X Draft and AHRI
1340–2023 address this issue by
subtracting fan heat from auxiliary heat
demand. Additionally, sections c and d
of appendix C of the ACUAC and
ACUHP Working Group TP Term Sheet
assume that the fan would be either
cycling between airflows when cycling
between stages of compression or
operating at the lowest-measured indoor
airflow for any cooling or heating test
when cycling on and off at the lowest
stage of compression; however, the
indoor fan would likely be operating at
the airflow corresponding to the fullload heating test when operating in
auxiliary heat mode. The AHRI 1340–
202X Draft and AHRI 1340–2023
address this by applying fan power from
the full-load heating test for auxiliary
heat-only mode. However, DOE notes
that because both fan heat and auxiliary
heat apply heat to the indoor airstream
with the same efficiency (i.e., COP of 1),
the airflow assumed for auxiliary heatonly mode does not impact results, as
the fan heat resulting from an increase
in fan power reduces the auxiliary heat
needed to meet the building load by the
same amount, resulting in no net change
to calculated IVHE.
4. Interpolation for variable-speed
compressor systems: When building
load is between capacities of a unit
tested with multiple heating stages,
section c of appendix C of the Term
Sheet includes a separate method for
interpolating between stages for
variable-speed compressor systems (i.e.,
a method that interpolates capacity
divided by power) from the method for
all other units (i.e., a method that
linearly interpolates power). As part of
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
development of the AHRI 1340–202X
Draft, it was determined that there were
insufficient data to support a separate
interpolation method for variable-speed
compressor systems, and, therefore, the
AHRI 1340–202X Draft and AHRI 1340–
2023 apply the same linear interpolation
method based on power for all units.
The linear interpolation method for
variable-speed compressor systems
included in the AHRI 1340–202X Draft
is also maintained in AHRI 1340–2023.
5. Compressor operating levels for
heating tests: Recommendation #9 of the
Term Sheet includes details on the
required and optional tests based on
configuration of the system (i.e., singlestage, two or more stages, and variablecapacity). Required tests include a test
at ‘‘high’’ operating level at 17 °F and
47 °F; optional tests include tests at low
and intermediate operating levels at
17 °F and 47 °F, as well as high and
‘‘boost’’ operating levels at 5 °F. For
variable-capacity systems, the Term
Sheet specifies that the high speed and
low speed at each temperature should
be the normal maximum and minimum
for each ambient temperature. The AHRI
1340–202X Draft includes additional
explanation of which compressor
speeds correspond to the low, medium,
high, and boost designations at each test
temperature. AHRI 1340–2023
maintains the explanations included in
AHRI 1340–202X Draft and includes
further explanation of the compressor
operating levels, as discussed in section
III.E.8.b of this final rule.
In the August 2023 TP NOPR, DOE
tentatively concluded that these
updated IVHE equations as described in
the preceding paragraphs would provide
for a more accurate calculation of IVHE.
88 FR 56392, 56419 (August 17, 2023).
Further, Recommendation #9 of the
ACUAC and ACUHP Working Group TP
Term Sheet states that the equations in
appendix C of the Term Sheet are
subject to quality control checking
(‘‘QC’’) for errors with the intent
remaining the same as voted on. In the
August 2023 TP NOPR, DOE tentatively
concluded that the discussed deviations
in the AHRI 1340–202X Draft hold the
same intent of the recommendations set
forth in the ACUAC and ACUHP
Working Group TP Term Sheet.
Therefore, DOE proposed to adopt the
provisions of AHRI 1340–202X Draft for
determining IVHE in appendix A1,
including the updated equations
discussed in this section. 88 FR 56392,
56418–56419 (August 17, 2023).
AHRI 1340–2023 includes the largely
the same provisions as AHRI 1340–202X
Draft for determining IVHE. Any
differences between the provisions in
AHRI 1340–202X Draft and AHRI 1340–
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
2023 are discussed in section III.E.8 of
this final rule. Therefore, DOE has
concluded that that the updated IVHE
equations in AHRI 1340–2023, as
described in the preceding paragraphs,
would provide for a more accurate
calculation of IVHE than the equations
in the ACUAC and ACUHP Working
Group TP Term Sheet, and that the
discussed deviations hold the same
intent as the recommendations set forth
in the ACUAC and ACUHP Working
Group TP Term Sheet. Therefore, DOE
is adopting in appendix A1 the
approach for determining IVHE from
AHRI 1340–2023.
DOE notes that appendix C of the
ACUAC and ACUHP Working Group TP
Term Sheet includes a provision that
‘‘additional provisions, still TBD would
apply for variable-speed compressors for
which pairs of full-speed or minimumspeed tests are not run at the same
speed.’’ (See EERE–2022–BT–STD–
0015–0065 at p. 14) The AHRI 1340–
202X Draft does not include any
provisions allowing for determination of
capacity for a bin by interpolating
between tests conducted at different
compressor operating levels. In the
August 2023 TP NOPR, DOE tentatively
concluded that this approach is
appropriate and that calculating IVHE
with results from multiple tests at each
compressor operating level would
provide representative ratings for
manufacturers that choose to include
performance at operating levels beyond
the required high operating level tests at
47 and 17 °F in their representations of
IVHE. 88 FR 56392, 56419 (August 17,
2023). AHRI 1340–2023 also includes
no such provisions allowing
interpolation between tests conducted at
different compressor operating levels.
Therefore, DOE maintains its tentative
conclusion from the August 2023 TP
NOPR and is adopting the approach for
determining IVHE from AHRI 1340–
2023 unchanged.
8. Heating Test Provisions Not Included
in the AHRI 1340–202X Draft
a. General
As discussed in the August 2023 TP
NOPR (88 FR 56392, 56418–56419
(August 17, 2023)) and section III.E.7.g
of this final rule, the AHRI 1340–202X
Draft includes conditions for heating
tests and calculations for the IVHE,
IVHEC, and COP2 metrics that DOE
proposed to adopt in the August 2023
TP NOPR. AHRI 1340–2023 includes
several updates to the heating test
provisions as compared to the AHRI
1340–202X Draft. The following
sections describe these updates and
what DOE is adopting in this final rule.
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
44011
b. Definitions of Heating Operating
Levels
Table 26 to AHRI 1340–202X Draft
and section 6.3.5 of AHRI 1340–202X
Draft specify the heating operating
levels to use and the requirements for
each, but do not make clear the
parameters included in defining an
operating level. Section 3.2.31 of AHRI
1340–2023 includes definitions for all
heating operating levels, as well as a
general definition of ‘‘operating level.’’
Section 3.2.31.6 defines ‘‘operating
level’’ as being determined by the
number of compressors operating, the
modulation level of each operating
compressor, and the indoor fan speed.
The definition indicates that the
modulation level of a single compressor
is determined by the speed, duty cycle,
vapor injection setting, and state of any
other operating parameters that affect
the continuous capacity of the
compressor at a single set of operating
conditions.
DOE is adopting these AHRI 1340–
2023 operating level definitions in the
DOE test procedure for CUACs and
CUHPs, because DOE has concluded
that they provide appropriate clarity on
how to determine the operating levels to
be used for heating tests and are
substantively consistent with the AHRI
1340–202X Draft, which DOE proposed
to adopt in the August 2023 TP NOPR.
The one exception is the definition for
the ‘‘boost2 heating operating level,’’
which is discussed in section III.E.8.c of
this final rule.
c. Boost2 Heating Operating Level and
COP25
The AHRI 1340–202X Draft includes
low, medium, high, and boost heating
operating levels, with boost being the
operating level with the highest heating
capacity. The boost operating level uses
the maximum compressor operating
capacity that is allowed by the controls
at 17 °F, and the airflow that is allowed
by the controls at 17 °F when operating
at the chosen compressor operating
capacity. AHRI 1340–2023 includes all
the same heating operating levels as the
AHRI 1340–202X Draft, plus a boost2
heating operating level. AHRI 1340–
2023 defines the ‘‘boost2 operating
level’’ as an operating level allowed by
the controls at 5 °F outdoor dry-bulb
temperature with a capacity at 5 °F
outdoor dry-bulb temperature that is
greater than the capacity of the boost
heating operating level at 5 °F outdoor
dry-bulb temperature and less than or
equal to the maximum capacity allowed
by the controls at 5 °F outdoor dry-bulb
temperature.
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
44012
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
For units with a boost operating level,
AHRI 1340–2023 specifies
representations of COP25 be based on
the capacity and power determined at
the boost or boost2 heating operating
level denoted as the H5B or H5B2 tests
in Table 23 to AHRI 1340–2023.
However, AHRI 1340–2023 does not
allow the H5B2 test to be used in the
calculation of IVHE or IVHEC. As
discussed in section III.E.7.g of this
document, AHRI 1340–2023 does not
include any provisions allowing for
determination of capacity for a bin by
interpolating between tests conducted at
different compressor operating levels.
Therefore, inclusion of results from the
boost2 operating level would require at
least two tests conducted at this
operating level. Because there is no
other test specified at a different
outdoor dry-bulb temperature condition
at this same boost2 operating level,
AHRI 1340–2023 only allows the H5B2
test to be used to determine the capacity
at 5 °F outdoor dry-bulb temperature or
COP2 at 5 °F.
DOE has determined that including a
boost2 heating operating level allows for
manufacturers to make performance
representations that adequately reflect
boosted heating performance at lower
temperatures. DOE notes that
Recommendation #9 of the ACUAC and
ACUHP Working Group TP Term Sheet
includes the following: ‘‘Manufacturers
can make representations of COP and
capacity at any of the following
temperatures: 5 °F, 17 °F, and 47 °F, in
accordance with the DOE test
procedure, in addition to the IVHE
metric that will be required for
standards.’’ (See EERE–2022–BT–STD–
0015–0065 at p. 6) As mentioned in
section III.E.4 of this final rule, DOE
acknowledges that in the future
manufacturers will likely develop
CUHPs that are designed for operation
in colder climates. This may include
designing CUHPs that are capable of
providing boosted heating capacity at
low temperatures. DOE has determined
that the inclusion of the boost2 heating
operating level and the H5B2 test in
AHRI 1340–2023 is consistent with the
intent of Recommendation #9 of the
Term Sheet. This will allow for
manufacturers designing systems with
boosted heating capacity at 5 °F that
differs from the operating levels at
higher outdoor temperatures to make
representations of capacity and
performance at 5 °F, and
correspondingly provide commercial
consumers interested in lowtemperature heating performance an
additional standardized metric to
compare such performance across
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
models. Further, DOE has concluded
that the inclusion of the boost2 heating
operating level and the H5B2 test in
AHRI 1340–2023 is generally consistent
with the AHRI 1340–202X Draft, in that
it maintains the proposed allowance for
optional representations at 5 °F, but
adds additional options for
manufacturers to determine this
optional representation at the
compressor speed most representative
for a model. As discussed, testing at the
boost2 heating operating level is
optional and would not be required for
determinations of IVHE. DOE is
adopting the H5B2 test in its amended
test procedure at appendix A1, but with
two additional clarifying provisions not
included in AHRI 1340–2023.
First, section 6.3.14.2 of AHRI 1340–
2023 specifies that for determining the
COP25 of units with a boost operating
level, one must use the capacity and
power determined for the H5B or H5B2
test, instead of the H5H test. These
provisions indicate that optional COP25
representations for such units are based
on a higher heating operating level but
do not specify whether the H5B or H5B2
test is to be used for a unit that has both
a boost heating operating level and a
boost2 heating operating level. DOE has
determined that additional specificity is
warranted as to which test is used to
determine optional COP25
representations—specifically, DOE has
concluded that it should be clarified to
use the highest applicable heating
operating level to determine COP25.
Therefore, DOE is adding the following
clarification to section 5.3 of appendix
A1: For units without a boost heating
operating level and without a boost 2
heating operating level, use capacity
and power determined for the H5H test.
For units with a boost heating operating
level and without a boost 2 heating
operating level, use capacity and power
determined for the H5B test. For units
with a boost 2 heating operating level,
use capacity and power determined for
the H5B2 test.
Second, section 3.2.31.1 of AHRI
1340–2023 defines the ‘‘boost heating
operating level’’ as the operating level
that has the maximum capacity allowed
by the controls at 17 °F outdoor dry-bulb
temperature, with a capacity at 17.0 °F
outdoor dry-bulb temperature that is
greater than the capacity of the high
heating operating level 22 at 17 °F. This
means that there is no boost heating
operating level if the high heating
operating level is the heating operating
22 Section 3.2.31.3 of AHRI 1340–2023 defines
‘‘high heating operating level’’ as the operating level
with the maximum capacity that is allowed by the
controls at 47.0 °F outdoor dry-bulb temperature.
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
level with the maximum capacity at
17 °F. Section 3.2.31.2 of AHRI 1340–
2023 defines the ‘‘boost2 heating
operating level’’ as an operating level
allowed by the controls at 5 °F outdoor
dry bulb-temperature with a capacity at
5 °F outdoor dry bulb-temperature that
is greater than the capacity of the boost
heating operating level at 5 °F and less
than or equal to the maximum capacity
allowed by the controls at 5 °F outdoor
dry bulb-temperature.
Because the definition of the ‘‘boost2
heating operating level’’ relies on the
capacity of the boost operating level, the
definition implies that a model must
have an operating level that meets the
definition for the boost heating
operating level in order for it to also
have a boost2 heating operating level.
This implication means that AHRI
1340–2023 would not allow the H5B2
test to be conducted for a model which
has no boost heating operating level at
17 °F, even if that model has an
operating level with a capacity at 5 °F
that is greater than the capacity of the
high heating operating level at 5 °F. DOE
has determined that such a scenario is
possible and should be accounted for in
the definition for the ‘‘boost2 heating
operating level’’ and the requirements
for the H5B2 test.
As such, DOE is not adopting the
definition for the ‘‘boost2 heating
operating level’’ in section 3.2.31.2 of
AHRI 1340–2023. Instead, DOE is
adopting the following definition for the
‘‘boost2 heating operating level’’ in
section 5.1 of appendix A1, which
addresses the aforementioned scenario
of a model with a boosted operating
level at 17 °F but not 5 °F: ‘‘An operating
level allowed by the controls at 5.0 °F
outdoor dry-bulb temperature with a
capacity at 5.0 °F outdoor dry-bulb
temperature that is less than or equal to
the maximum capacity allowed by the
controls at 5.0 °F outdoor dry-bulb
temperature, and greater than the
capacity of: (a) the Boost Heating
Operating Level at 5.0 °F outdoor drybulb temperature, if there is an
operating level that meets the definition
for Boost Heating Operating Level
specified in section 3.2.31.1 of AHRI
1340–2023; or (b) the High Heating
Operating Level at 5.0 °F outdoor drybulb temperature, if there is not an
operating level that meets the definition
for Boost Heating Operating Level’’
specified in section 3.2.31.1 of AHRI
1340–2023.
Correspondingly, DOE is also
specifying in section 5.2 of appendix A1
updated requirements for the H5B2 test
of AHRI 1340–2023 that are to be used
in case a model has no heating operating
level that meets the definition of ‘‘boost
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
heating operating level’’ in section
3.2.31.1 of AHRI 1340–2023. Section
6.3.6 of AHRI 1340–2023 specifies to
run the H5B2 test in Table 23 to AHRI
1340–2023 with an operating level
allowed by the controls at 5.0 °F outdoor
dry-bulb temperature that has a capacity
at 5.0 °F outdoor dry-bulb temperature
that is greater than the capacity of the
Boost Heating Operating Level at 5.0 °F.
In section 5.2 of appendix A1, DOE is
instead adopting a revised version of
that provision that replaces the
comparison to capacity of the Boost
Heating Operating Level at 5.0 °F with a
comparison to capacity of the High
Heating Operating Level at 5.0 °F.
As noted previously, DOE has
concluded that the inclusion of the
boost2 heating operating level and the
H5B2 test in AHRI 1340–2023 is
generally consistent with the AHRI
1340–202X Draft. Similarly, DOE has
concluded that the provisions discussed
in this section (i.e., to allow use of the
boost2 heating operating level for
determining optional representations at
5 °F for a model which has no boost
heating operating level at 17 °F, and to
clarify which test should be used for
optional COP25 representations
depending on which heating operating
levels apply at 5 °F) maintain the
proposed allowance for optional
representations at 5 °F, but add options
and clarity for manufacturers to
consistently determine this optional
representation at the compressor speed
most representative for a model.
DOE understands that the AHRI
Commercial Unitary STC also plans to
address the aforementioned
clarifications regarding the instructions
for which test to use for optional
representation of COP25 and the
definition of ‘‘boost2 heating operating
level’’ that were published in AHRI
1340–2023. DOE expects that AHRI will
consider including such clarifications in
a future version of AHRI 1340,
consistent with the clarifications
adopted in this final rule.
d. Extrapolation of Boost Heating
Operating Level to 21 °F
As discussed in section III.E.7.g of
this final rule, AHRI 1340–202X Draft
requires interpolation of capacity and
power between tests of the same
operating level at different outdoor air
temperatures when calculating values
for the temperature bins used in IVHE
and IVHEC. Extrapolation of capacity
and power are not allowed in AHRI
1340–202X Draft.
Sections 6.3.8 and 6.3.9 of AHRI
1340–2023 allow for capacity and power
from boost heating operating level tests
conducted at 5 °F and 17 °F to be used
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
to extrapolate boost heating operating
level performance up to 21 °F. This
allows manufacturers to take advantage
of the boost heating operating level for
calculations of the IVHE and IVHEC bins
with outdoor air dry-bulb temperatures
between 17 °F and 22 °F.23
DOE has determined that these
provisions are appropriate and will
allow for more representative
accounting of performance for bin
temperatures between 17 °F and 22 °F,
which are conditions at which models
would likely operate at boost heating
operating level, as necessary, to meet
the building load, if the model operated
as such for tests at 17 °F (i.e., it would
be unlikely that a model would have a
boost operating level that engages at
17 °F but not at 22 °F). Further, DOE has
concluded that these provisions are
generally consistent with the AHRI
1340–202X Draft in that the provisions
maintain the same compressor operating
levels for determining IVHE, but the
upper temperature limit to which boost
heating performance can be applied is
being slightly extended (by 5 °F, from
17 °F to 22 °F) to more representatively
account for performance between 17 °F
to 22 °F. Therefore, DOE is adopting the
provisions allowing extrapolation of
boost heating operating level
performance in sections 6.3.8 and 6.3.9
of AHRI 1340–2023.
e. Operating Levels Used for Optional
COP217 Representations
As previously mentioned in section
III.E.8.c of this document, AHRI 1340–
2023 specifies that for units with a boost
operating level, representations of
COP25 is to be based on the capacity
and power determined at the boost or
boost 2 heating operating level denoted
as the H5B or H5B2 test, instead of the
H5H test. However, while AHRI 1340–
2023 includes a boost operating level
test at 17 °F (the H17B test), section
6.3.14.2 of AHRI 1340–2023 requires
that COP217 be determined using the
capacity and power determined for the
H17H test and does not allow for the
COP217 to be determined using the
capacity and power determined for the
H17B test if conducted. Similar to its
conclusions regarding the use of the
H5B or H5B2 test for determining
COP25, DOE has determined it would be
appropriate to require the H17B test to
be used for representations of COP217 if
conducted because representations of
efficiency at the maximum capacity for
a given test condition are common and
23 Table 22 of AHRI 1340–2023 specifies: (1) for
the IVHE metric, bin temperatures of 21 °F and
18.1 °F for bin numbers 8 and 9; and (2) for the
IVHEC metric, a bin temperature of 20.0 °F for bin
number 5.
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
44013
useful for consumers and utilities.
Therefore, DOE is also specifying in this
final rule that the H17B test, if
conducted, be used for determining
COP217, in order to allow manufacturers
to make optional representations of
capacity and performance at that
operating level for models that are
capable of boost operation. DOE
understands that the AHRI Commercial
Unitary STC also plans to specify that
the H17B test is to be used for
determining COP217 if this test is
conducted. DOE expects that AHRI will
consider including prescribing the use
of the H17B test in appropriate cases for
representations of COP217, consistent
with this final rule, in a future version
of AHRI 1340.
9. Test Procedure Revisions
Recommended for a Future Rulemaking
NYSERDA generally supported the
proposed IVEC and IVHE metrics but
commented that the heating test
provisions proposed do not adequately
account for fan energy consumed during
auxiliary heating mode. (NYSERDA, No.
13 at pp. 2–3) NYSERDA recommended
DOE consider the inclusion of an
additional energy consumption term in
the denominator of the IVHE calculation
to account for supply fan energy use for
commercial warm air furnaces, which
NYSERDA stated would support
recommendation #11 of the ACUAC and
ACUHP Working Group TP Term Sheet.
NYSERDA recommended addressing the
fan energy consumption issue at the
next appropriate juncture. (Id.)
NEEA recommended DOE consider
the following items the next time the
CUAC/HP test procedure is reviewed:
(1) impacts of outside air damper
leakage; (2) energy saving potential from
energy recovery ventilators (‘‘ERV’’); (3)
benefits of variable-capacity or variablespeed compressors, and (4) a controls
verification procedure (‘‘CVP’’). (NEEA,
No. 16 at p. 4)
At this time DOE has concluded that
it does not have sufficient information
or data to justify adopting deviations
from the IVEC and IVHE metrics
negotiated by the Working Group and
included in the industry consensus test
procedure AHRI 1340–2023. Therefore,
DOE is adopting the IVEC and IVHE
metrics as specified in AHRI 1340–2023.
Regarding NYSERDA’s comments on
fan energy consumption in the IVHE
metric, DOE notes that IVHE is the
heating metric for CUHPs and assumes
electric resistance supplementary heat
for all models. Dual fuel CUHPs (i.e.,
CUHPs with gas furnace supplementary
heat) will still have IVHE ratings that
reflect electric resistance supplementary
heat. The IVHE metric accounts for
E:\FR\FM\20MYR2.SGM
20MYR2
44014
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
supply fan energy during all hours with
a heating load, regardless of whether the
IVHE calculations assume the heating
load is met by mechanical heating only,
electric resistance heating only, or both,
as described in section III.D.2 of this
document. Therefore, DOE has
concluded that no fan energy use for
CUHPs is unaccounted for in the IVHE
metric. DOE recognizes NEEA’s
suggested topics for consideration in a
future test procedure rulemaking, but
consistent with NEEA’s comment, DOE
is not addressing these topics in this
final rule.
lotter on DSK11XQN23PROD with RULES2
F. Configuration of Unit Under Test
1. Summary
CUACs and CUHPs are sold with a
wide variety of components, including
many that can optionally be installed on
or within the unit both at the factory
and in the field. The following sections
address the required configuration of
units under test. In all cases, these
components are distributed in
commerce with the CUAC and CUHP
but can be packaged or shipped in
different ways from the point of
manufacture for ease of transportation.
Each optional component may or may
not affect a model’s measured efficiency
when tested to the DOE test procedure
adopted in this final rule. For certain
components not directly addressed in
the DOE test procedure, the August
2023 TP NOPR proposed more specific
instructions on how each component
should be handled for the purposes of
making representations in 10 CFR part
429. 88 FR 56392, 56430–56433 (August
17, 2023). Specifically, the proposed
instructions were intended to provide
manufacturers with clarity on how
components should be treated and how
to group individual models with and
without optional components for the
purposes of representations to reduce
burden. Id. DOE proposed these
provisions in 10 CFR part 429 to allow
for testing of certain individual models
that can be used as a proxy to represent
the performance of equipment with
multiple combinations of components.
Id.
In the August 2023 TP NOPR, DOE
proposed to handle CUAC and CUHP
components in two distinct ways to
help manufacturers better understand
their options for developing
representations for their differing
product offerings. Id. First, DOE
proposed that the treatment of certain
components be specified by the test
procedure, such that their impact on
measured efficiency is limited. Id. For
example, a fresh air damper must be set
in the closed position and sealed during
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
testing, resulting in a measured
efficiency that would be similar or
identical to the measured efficiency for
a unit without a fresh air damper.
Second, DOE proposed provisions
expressly allowing certain models to be
grouped together for the purposes of
making representations and allowing
the performance of a model without
certain optional components to be used
as a proxy for models with any
combinations of the specified
components, even if such components
would impact the measured efficiency
of a model. Id. A steam/hydronic coil is
an example of such a component. The
efficiency representation for a model
with a steam/hydronic coil is based on
the measured performance of the CUAC
and CUHP as tested without the
component installed because the steam/
hydronic coil is not easily removed from
the CUAC and CUHP for testing.24 Id.
In this final rule, DOE is adopting
provisions regarding configuration of
unit under test largely similar to those
proposed, but with several differences
from the proposed provisions, as
discussed in the following sections.
Specifically, the following sections
provide a background for the proposed
provisions, describe the proposed
provisions, describe relevant updates in
AHRI 1340–2023 that were not included
in the AHRI 1340–202X Draft,
summarize and respond to the
comments that DOE received in
response to the August 2023 TP NOPR,
and discuss the provisions that DOE is
adopting in this final rule.
2. Background
In 2013, ASRAC formed the
Commercial HVAC Working Group to
engage in a negotiated rulemaking effort
regarding the certification of certain
commercial heating, ventilating, and air
conditioning equipment, including
CUACs and CUHPs. (See 78 FR 15653
(March 12, 2013)) This Commercial
HVAC Working Group submitted a term
sheet (Commercial HVAC Term Sheet)
providing the Commercial HVAC
Working Group’s recommendations.
(See EERE–2013–BT–NOC–0023–
0052 25) The Commercial HVAC
Working Group recommended that DOE
issue guidance under current
regulations on how to test certain
equipment features when included in a
basic model, until such time as the
testing of such features can be addressed
through a test procedure rulemaking.
24 Note that in certain cases, as explained further
in section III.F.3.b of this document, the
representation may have to be based on an
individual model with a steam/hydronic coil.
25 Available at www.regulations.gov/document/
EERE-2013-BT-NOC-0023-0052.
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
The Commercial HVAC Term Sheet
listed the subject features under the
heading ‘‘Equipment Features Requiring
Test Procedure Action.’’ (Id at pp. 3–9)
The Commercial HVAC Working Group
also recommended that DOE issue an
enforcement policy stating that DOE
would exclude certain equipment with
specified features from DOE testing, but
only when the manufacturer offers for
sale at all times a model that is identical
in all other features; otherwise, the
model with that feature would be
eligible for DOE testing. These features
were listed under the heading
‘‘Equipment Features Subject to
Enforcement Policy.’’ (Id. at pp. 9–15)
On January 30, 2015, DOE issued a
Commercial HVAC Enforcement Policy
addressing the treatment of specific
features during DOE testing of
commercial HVAC equipment. (See
www.energy.gov/gc/downloads/
commercial-equipment-testingenforcement-policies) The Commercial
HVAC Enforcement Policy stated that—
for the purposes of assessment testing
pursuant to 10 CFR 429.104, verification
testing pursuant to 10 CFR 429.70(c)(5),
and enforcement testing pursuant to 10
CFR 429.110—DOE would not test a
unit with one of the optional features
listed for a specified equipment type if
a manufacturer distributes in commerce
an otherwise identical unit that does not
include that optional feature.
(Commercial HVAC Enforcement Policy
at p. 1) The objective of the Commercial
HVAC Enforcement Policy is to ensure
that each basic model has a
commercially-available version eligible
for DOE testing. That is, each basic
model includes a model either without
the optional feature(s) listed in the
policy or that is eligible for testing with
the feature(s). Id. The features in the
Commercial HVAC Enforcement Policy
for CUACs and CUHPs (Id. at pp. 1–3
and 5–6) align with the Commercial
HVAC Term Sheet’s list designated
‘‘Equipment Features Subject to
Enforcement Policy.’’ (EERE–2013–BT–
NOC–0023–0052, pp. 9–15)
By way of comparison, AHRI 340/
360–2022 and AHRI 1340–202X Draft
include appendix D, ‘‘Unit
Configuration for Standard Efficiency
Determination—Normative.’’ Section D3
to appendix D of AHRI 340/360–2022
and AHRI 1340–202X Draft includes a
list of features that are optional for
testing, and it further specifies the
following general provisions regarding
testing of units with optional features:
• If an otherwise identical model
(within the basic model) without the
feature is not distributed in commerce,
conduct tests with the feature according
to the individual provisions specified in
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
section D3 to appendix D of AHRI 340/
360–2022 and AHRI 1340–202X Draft.
• For each optional feature, section
D3 to appendix D of AHRI 340/360–
2022 and AHRI 1340–202X Draft
includes explicit instructions on how to
conduct testing for equipment with the
optional feature present.
The optional features provisions in
AHRI 340/360–2022 and AHRI 1340–
202X Draft are generally consistent with
DOE’s Commercial HVAC Enforcement
Policy, but the optional features in
section D3 to appendix D of AHRI 340/
360–2022 and AHRI 1340–202X Draft
do not entirely align with the list of
features included for CUACs and
CUHPs in the Commercial HVAC
Enforcement Policy.
DOE notes that the list of features and
provisions in section D3 to appendix D
of AHRI 340/360–2022 and AHRI 1340–
202X Draft conflate components that
can be addressed by testing provisions
with components that, if present on a
unit under test, could have a substantive
impact on test results and that cannot be
disabled or otherwise mitigated. This
differentiation was central to the
Commercial HVAC Term Sheet, which
as noted previously, included separate
lists for ‘‘Equipment Features Requiring
Test Procedure Action’’ and
‘‘Equipment Features Subject to
Enforcement Policy,’’ and remains
central to providing clarity in DOE’s
regulations. Therefore, in the August
2023 TP NOPR, DOE tentatively
determined that provisions more
explicit than those included in section
D3 of appendix D of AHRI 340/360–
2022 and AHRI 1340–202X Draft are
warranted to clarify treatment of models
that include more than one optional
component. 88 FR 56392, 56430 (August
17, 2023).
In order to provide clarity between
test procedure provisions (i.e., how to
test a specific unit) and certification and
enforcement provisions (e.g., which
model to test), DOE proposed in the
August 2023 TP NOPR to exclude
appendix D of AHRI 340/360–2022 or
AHRI 1340–202X Draft from adoption
and instead proposed related provisions
in 10 CFR 429.43 and 429.134 and 10
CFR part 431, subpart F, appendices A
and A1. Id.
a. Components Addressed Through Test
Provisions of 10 CFR Part 431, Subpart
F, Appendices A and A1
In the August 2023 TP NOPR, DOE
proposed in 10 CFR part 431, subpart F,
appendices A and A1, test provisions
for specific components, including all of
the components listed in section D3 to
appendix D of AHRI 340/360–2022 and
AHRI 1340–202X Draft, for which there
is a test procedure action that limits the
impacts on measured efficiency (i.e.,
test procedure provisions specific to the
component that are not addressed by
general provisions in AHRI 340/360–
2022 or AHRI 1340–202X Draft that
negate the component’s impact on
performance). 88 FR 56392, 56430
(August 17, 2023). These provisions
would specify how to test a unit with
such a component (e.g., for a unit with
hail guards, remove hail guards for
testing). These proposed test provisions
were consistent with the provision in
section D3 to appendix D of AHRI 340/
360–2022 and AHRI 1340–202X Draft
but include revisions for further clarity
and specificity (e.g., adding clarifying
provisions for how to test units with
modular economizers as opposed to
units shipped with economizers
installed). Id. Specifically, DOE
proposed to require in appendices A
and A1 that steps be taken during unit
set-up and testing to limit the impacts
on the measurement of these
components:
• Air Economizers
• Barometric Relief Dampers
• Desiccant Dehumidification
Components
• Evaporative Pre-cooling of Air-cooled
Condenser Intake Air
• Fire/Smoke/Isolation Dampers
• Fresh Air Dampers
• Hail Guards
• High-Effectiveness Indoor Air
Filtration
• Power Correction Capacitors
• Process Heat Recovery/Reclaim Coils/
Thermal Storage
• Refrigerant Reheat Coils
• Steam/Hydronic Heat Coils
• UV Lights
• Ventilation Energy Recovery Systems
(VERS)
The components were listed and
described in the proposed table 1 to
appendix A and table 1 to appendix A1.
Test provisions for the components
were provided in the tables. Id.
3. Proposed Approach for Exclusion of
Certain Components
b. Components Addressed Through
Representation Provisions of 10 CFR
429.43
DOE’s proposals in August 2023 TP
NOPR for addressing treatment of
certain components are discussed in the
following sub-sections.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
Overall Approach
Consistent with the Commercial
HVAC Term Sheet and the Commercial
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
44015
HVAC Enforcement Policy, in the
August 2023 TP NOPR, DOE proposed
provisions that explicitly allow
representations for individual models
with certain components to be based on
testing for individual models without
those components. 88 FR 56392, 56430–
56433 (August 17, 2023). DOE proposed
a table (table 6) at 10 CFR
429.43(a)(3)(v)(A) listing the
components for which these provisions
would apply. Id. 88 FR 56430–56431.
DOE proposed the following
components be listed in table 6 to 10
CFR 429.43(a)(3)(v)(A):
• Air Economizers
• Desiccant Dehumidification
Components
• Evaporative Pre-cooling of Air-cooled
Condenser Intake Air
• Fire/Smoke/Isolation Dampers
• Indirect/Direct Evaporative Cooling of
Ventilation Air
• Non-Standard Ducted Condenser Fans
• Non-Standard Indoor Fan Motors
• Powered Exhaust/Powered Return Air
Fans
• Process Heat Recovery/Reclaim Coils/
Thermal Storage
• Refrigerant Reheat Coils
• Sound Traps/Sound Attenuators
• Steam/Hydronic Heat Coils
• Ventilation Energy Recovery Systems
(VERS)
In the August 2023 TP NOPR, DOE
proposed to specify that the basic model
representation must be based on the
least-efficient individual model that
comprises a basic model, and clarified
how this long-standing basic model
provision interacts with the proposed
component treatment in 10 CFR 429.43.
Id. 88 FR 56431–56432. DOE tentatively
concluded that regulated entities may
benefit from clarity in the regulatory
text as to how the least-efficient
individual model within a basic model
provision works in concert with the
component treatment for CUACs and
CUHPs. Id. The amendments proposed
in the August 2023 TP NOPR explicitly
state that excluding the specified
components from consideration in
determining basic model efficiency in
certain scenarios is an exception to
basing representations on the leastefficient individual model within a
basic model. Id. In other words, the
components listed in 10 CFR 429.43 are
not being considered as part of the
representation under DOE’s regulatory
framework if certain conditions are met
as discussed in the following
paragraphs, and, thus, their impact on
efficiency is not reflected in the
representation. In this case, the basic
model’s representation is generally
determined by applying the testing and
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
44016
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
sampling provisions to the leastefficient individual model in the basic
model that does not have a component
listed in 10 CFR 429.43.
DOE proposed clarifying instructions
for instances when individual models
within a basic model may have more
than one of the specified components
and there may be no individual model
without any of the specified
components. Id. DOE proposed the
concept of an otherwise comparable
model group (‘‘OCMG’’). Id. An OCMG
is a group of individual models within
the basic model that do not differ in
components that affect energy
consumption as measured according to
the applicable test procedure other than
the specific components listed in table
6 to 10 CFR 429.43(a)(3)(v)(A) but may
include individual models with any
combination of such specified
components. Therefore, a basic model
can be composed of multiple OCMGs,
each representing a unique combination
of components that affect energy
consumption as measured according to
the applicable test procedure, other than
the specified excluded components
listed in table 6 to 10 CFR
429.43(a)(3)(v)(A). For example, a
manufacturer might include two tiers of
control systems within the same basic
model, in which one of the control
systems has sophisticated diagnostics
capabilities that require a more
powerful control board with a higher
wattage input. CUAC and CUHP
individual models with the ‘‘standard’’
control system would be part of OCMG
A, while individual models with the
‘‘premium’’ control system would be
part of a different OCMG B, because the
control system is not one of the
specified exempt components listed in
table 6 to 10 CFR 429.43(a)(3)(v)(A).
However, both OCMGs may include
different combinations of specified
exempt components. Also, both OCMGs
may include any combination of
characteristics that do not affect the
efficiency measurement, such as paint
color.
An OCMG identifies which individual
models are to be used to determine a
represented value. Id. Specifically,
when identifying the individual model
within an OCMG for the purpose of
determining a representation for the
basic model, only the individual
model(s) with the least number (which
could be zero) of the specific
components listed in table 6 to 10 CFR
429.43(a)(3)(v)(A) is considered. This
clarifies which individual models are
exempted from consideration for
determination of represented values in
the case of an OCMG with multiple
specified components and no individual
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
models with zero specific components
listed in table 6 to 10 CFR
429.43(a)(3)(v)(A) (i.e., models with a
number of specific components listed in
table 6 greater than the least number in
the OCMG are exempted). In the case
that the OCMG includes an individual
model with no specific components
listed in table 1 to 10 CFR
429.43(a)(3)(i)(A), then all individual
models in the OCMG with specified
components would be exempted from
consideration. The least-efficient
individual model across the OCMGs
within a basic model would be used to
determine the representation of the
basic model. In the case where there are
multiple individual models within a
single OCMG with the same non-zero
least number of specified components,
the least efficient of these would be
considered.
DOE relies on the term ‘‘comparable’’
as opposed to ‘‘identical’’ to indicate
that, for the purpose of representations,
the components that impact energy
consumption as measured by the
applicable test procedure are the
relevant components to consider. Id. In
other words, differences that do not
impact energy consumption, such as
unit color and presence of utility
outlets, would not warrant separate
OCMGs.
The use of the OCMG concept results
in the represented values of
performance that are representative of
the individual model(s) with the lowest
efficiency found within the basic model,
excluding certain individual models
with the specific components listed in
table 6 to 10 CFR 429.43(a)(3)(v)(A). Id.
Specifically with regard to basic models
of CUACs and CUHPs distributed in
commerce with multiple different
heating capacities of furnaces, the
individual model with the lowest
efficiency found within the basic model
(with the aforementioned exception)
would likely include the furnace with
the highest offered heating capacity.
Additionally, selection of the individual
model with the lowest efficiency within
the basic model would be required to
consider all options for factory-installed
components and manufacturer-supplied
field-installed components (e.g., electric
resistance supplementary heat),
excluding the specific components
listed in table 6 to 10 CFR
429.43(a)(3)(v)(A). If manufacturers
want to represent more-efficient models
within the same group, they would be
able to establish those units as new
basic models and test and report the
results accordingly. Further, the
approach, as proposed, is structured to
more explicitly address individual
models with more than one of the
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
specific components listed in table 6 to
10 CFR 429.43(a)(3)(v)(A), as well as
instances in which there is no
comparable model without any of the
specified components. DOE developed a
document of examples to illustrate the
approach proposed in the August 2023
TP NOPR for determining represented
values for CUACs and CUHPs with
specific components, and in particular
the OCMG concept (see EERE–2023–
BT–TP–0014–0001).
DOE’s proposed provisions in 10 CFR
429.43(a)(3)(v)(A) include each of the
components specified in section D3 of
AHRI 340/360–2022 for which the test
provisions for a unit with these
components may result in differences in
ratings compared to testing a unit
without these components. 88 FR
56392, 56431–56432 (August 17, 2023).
DOE’s proposed treatment for nonstandard indoor fan motors and coated
coils is discussed in the following subsections.
High-Static Non-Standard Indoor Fan
Motors
The Commercial HVAC Enforcement
Policy includes high-static indoor
blowers or oversized motors as an
optional feature for CUACs and CUHPs,
among other equipment. The
Commercial HVAC Enforcement Policy
states that when selecting a unit of a
basic model for DOE-initiated testing, if
the basic model includes a variety of
high-static indoor blowers or oversized
motor options,26 DOE will test a unit
that has a standard indoor fan assembly
(as described in the supplemental test
instructions (‘‘STI’’) that is part of the
manufacturer’s certification, including
information about the standard motor
and associated drive that was used in
determining the certified rating). This
policy only applies where: (a) the
manufacturer distributes in commerce a
model within the basic model with the
standard indoor fan assembly (i.e.,
standard motor and drive), and (b) all
models in the basic model have a motor
with the same or better relative
efficiency performance as the standard
motor included in the test unit, as
described in a separate guidance
document discussed subsequently. If the
manufacturer does not offer models
with the standard motor identified in
the STI or offers models with high-static
motors that do not comply with the
26 The Commercial HVAC Enforcement Policy
defines ‘‘high static indoors blower or oversized
motor’’ as an indoor fan assembly, including a
motor, that drives the fan and can deliver higher
external static pressure than the standard indoor fan
assembly sold with the equipment. (See
www.energy.gov/sites/default/files/2019/04/f62/
Enforcement_Policy-Commercial_HVAC.pdf. at p.6)
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
comparable efficiency guidance, DOE
will test any indoor fan assembly
offered for sale by the manufacturer.
DOE subsequently issued a draft
guidance document (Draft Commercial
HVAC Guidance Document) on June 29,
2015 to request comment on a method
for comparing the efficiencies of a
standard motor and a high-static indoor
blower/oversized motor.27 As presented
in the Draft Commercial HVAC
Guidance Document, the relative
efficiency of an indoor fan motor would
be determined by comparing the
percentage losses of the standard indoor
fan motor to the percentage losses of the
non-standard (oversized) indoor fan
motor. The percentage losses would be
determined by comparing each motor’s
wattage losses to the wattage losses of a
corresponding reference motor.
Additionally, the draft method contains
a table that includes a number of
situations with different combinations
of characteristics of the standard motor
and oversized motor (e.g., whether each
motor is subject to Federal standards for
motors; whether each motor can be
tested to the Federal test procedure for
motors; whether each motor horsepower
is less than 1 and specifies for each
combination whether the non-standard
fan enforcement policy would apply
(i.e., whether DOE would not test a
model with an oversized motor, as long
as the relative efficiency of the
oversized motor is at least as good as
performance of the standard motor)).
DOE has not issued a final guidance
document and is instead addressing the
issue for CUACs and CUHPs in this test
procedure rulemaking.
The current Federal test procedure
does not address this issue. Section D4.1
of appendix D of AHRI 340/360–2022
and AHRI 1340–202X Draft provide an
approach for including an individual
model with a non-standard indoor fan
motor as part of the same basic model
as an individual model with a standard
indoor fan motor. Under the approach
in section D4.1 of appendix D of AHRI
340/360–2022 and AHRI 1340–202X
Draft, the non-standard indoor fan
motor efficiency must exceed the
minimum value calculated using
equation D1 in appendix D of AHRI
340/360–2022 and AHRI 1340–202X
Draft. This minimum non-standard
motor efficiency calculation is
dependent on the efficiency of the
standard fan motor and the reference
efficiencies (determined per Table D1 of
appendix D of AHRI 340/360–2022 and
27 Available at www1.eere.energy.gov/buildings/
appliance_standards/pdfs/draft-commercial-hvacmotor-faq-2015-06-29.pdf.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
AHRI 1340–202X Draft) of the standard
and non-standard fan motors.
Section D4.2 of appendix D of AHRI
340/360–2022 and AHRI 1340–202X
Draft contain a method for how to
compare performance for integrated fans
and motors (IFMs). Because the fan
motor in an IFM is not separately rated
from the fan, this method compares the
performance of the entire fan-motor
assemblies for the standard and nonstandard IFMs, rather than just the fan
motors. This approach enables
comparing relative performance of
standard and non-standard IFMs, for
which motor efficiencies could
otherwise not be compared using the
method specified in section D4.1 of
appendix D of AHRI 340/360–2022 or
AHRI 1340–202X Draft. Specifically,
this method determines the ratio of the
input power of the non-standard IFM to
the input power of the standard IFM at
the same duty point as defined in
section D4.2 of appendix D of AHRI
340/360–2022 and AHRI 1340–202X
Draft (i.e., operating at the maximum
ESP for the standard IFM at the rated
airflow). If the input power ratio does
not exceed the maximum ratio specified
in Table D3 of appendix D of AHRI 340/
360–2022 and AHRI 1340–202X Draft,
the individual model with the nonstandard IFM may be included within
the same basic model as the individual
model with the standard IFM. Section
D4.2 of appendix D of AHRI 340/360–
2022 and AHRI 1340–202X Draft allow
these calculations to be conducted using
either test data or simulated
performance data.
The approaches in section D4 of
appendix D of AHRI 340/360–2022 and
AHRI 1340–202X Draft for high-static
non-standard indoor fan motors and
non-standard indoor IFMs generally
align with the approaches of the
Commercial HVAC Term Sheet, the
Commercial HVAC Enforcement Policy,
and the Draft Commercial HVAC
Guidance Document, while providing
greater detail and accommodating a
wider range of fan motor options. For
the reasons presented in the preceding
paragraphs, DOE proposed in the
August 2023 TP NOPR to adopt in table
6 to 10 CFR 429.43(a)(3)(v)(A) the
provisions for comparing performance
of standard and high-static non-standard
indoor fan motors/IFMs in section D4 of
appendix D of AHRI 340/360–2022 and
AHRI 1340–202X Draft 28 for the
28 Per DOE’s existing certification regulations, if
a manufacturer were to use the proposed approach
to certify a basic model, the manufacturer would be
required to maintain documentation of how the
relative efficiencies of the standard and nonstandard fan motors or the input powers of the
standard and non-standard IFMs were determined,
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
44017
determination of the represented
efficiency value for CUACs and CUHPs
at 10 CFR 429.43(a)(3). 88 FR 56392,
56432 (August 17, 2023).
Coated Coils
In the August 2023 TP NOPR, DOE
proposed to exclude coated coils from
the specific components list specified in
10 CFR 429.43 because DOE tentatively
concluded that the presence of coated
coils does not result in a significant
impact to performance of CUACs and
CUHPs, and, therefore, models with
coated coils should be rated based on
performance of models with coated coils
present (rather than based on
performance of an individual model
within an OCMG without coated coils).
88 FR 56392, 56432–56433 (August 17,
2023).
c. Enforcement Provisions of 10 CFR
429.134
Consistent with the Commercial
HVAC Term Sheet and the Commercial
HVAC Enforcement Policy, in the
August 2023 TP NOPR, DOE proposed
provisions in 10 CFR 429.134(g)(2)
regarding how DOE would assess
compliance for basic models of CUACs
and CUHPs that include individual
models distributed in commerce if DOE
cannot obtain for testing individual
models without certain components
consistent with the model that served as
the basis of representation. 88 FR 56392,
56433 (August 17, 2023). Specifically,
DOE proposed that if a basic model
includes individual models with
components listed at table 6 to 10 CFR
429.43(a)(3)(v)(A) and DOE is not able to
obtain an individual model with the
least number of those components
within an OCMG (as defined in the
proposed 10 CFR 429.43(a)(3)(v)(A)(1)
and discussed in section III.F.3.b of this
final rule), DOE may test any individual
model within the OCMG. Id.
d. Testing Specially Built Units That
Are Not Distributed in Commerce
Unlike section D3 to appendix D of
AHRI 340/360–2022 and AHRI 1340–
202X Draft, DOE’s Commercial HVAC
Enforcement Policy does not allow a
manufacturer to test a model that is
specially built for testing without a
feature if models without that feature
are not actually distributed in
commerce. Because testing such
specially built models would not
provide ratings representative of
equipment distributed in commerce,
DOE tentatively concluded in the
August 2023 TP NOPR that such
as well as the supporting calculations. See 10 CFR
429.71.
E:\FR\FM\20MYR2.SGM
20MYR2
44018
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
approach is not appropriate. 88 FR
56392, 56433 (August 17, 2023).
Therefore, consistent with the
Commercial HVAC Enforcement Policy,
DOE did not propose to allow testing of
specially built units in its representation
and enforcement provisions. Id.
4. Updates in AHRI 1340–2023
In the final version of AHRI 1340–
2023, appendix D to AHRI 1340–2023
was updated to align with the approach
and list of features proposed by DOE in
the August 2023 TP NOPR, as discussed
in section III.F.3 of this final rule. In
addition, Table 37 to appendix D to
AHRI 1340–2023 includes instructions
specifying that drain pan heaters be
disconnected during testing. DOE’s
consideration of this AHRI 1340–2023
provision for drain pan heaters is
discussed in the following section.
lotter on DSK11XQN23PROD with RULES2
5. Comments Received and Adopted
Provisions
a. Overall Approach
DOE received several comments
pertaining to DOE’s proposed approach.
Carrier stated that DOE’s proposal for
specific components was not fully clear
to Carrier, but that if the intent is that
the lowest-efficiency model should be
used for representations of performance,
Carrier agrees with that approach.
(Carrier, No. 8 at p. 3) For rating models,
Carrier also agreed that specially built
models not distributed in commerce
should not be allowed for compliance
testing used to determine ratings. (Id.)
Carrier commented that breaking into
separate groups of components and
introducing an additional concept of
OCMG could create further confusion
and undue complexity. (Id.) Carrier
stated that it would like to see these
provisions for specific components be
laid out in a more straightforward
manner to provide manufacturers clarity
when choosing models for
representations. (Id.) Rheem similarly
commented that the proposed OCMG
concept lacks clarity and recommended
DOE explore ways to make the proposed
regulatory text clearer with visual aids
or examples. (Rheem, No. 12 at p. 2)
Rheem recommended the regulatory
language to remain the same as it is
currently if no further explanation is
provided. (Id.)
Regarding Carrier and Rheem’s
concerns, DOE’s intent is for the lowestefficiency model within a basic model
to be used for representations of
performance, as is stated in the
provisions adopted at 10 CFR
429.43(a)(3)(vi)(A)(1) in this final rule.29
29 In the August 2023 TP NOPR, DOE proposed
the provisions regarding certain components
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
DOE acknowledges that the ability to
exclude certain specific components
specified in table 7 to 10 CFR
429.43(a)(3)(vi)(A) from consideration
when identifying the lowest-efficiency
model means that there could be
confusion in determining the leastefficient model(s) that can be used to
determine representations for the basic
model. This is the reason that the
OCMG concept is required. As
discussed, the OCMG formalizes the
process by which a manufacturer can
consider groups of individual models
within a basic model that are
comparable, other than the presence of
certain specific components specified in
table 7 to 10 CFR 429.43(a)(3)(vi)(A),
and determine the individual model(s)
that can be used to determine
representations for the basic model.
This ensures that the process is
performed in the same way by all
manufacturers and also by DOE, thereby
preventing the potential for confusion
and inaccurate representations.
Regarding Carrier’s and Rheem’s
requests for more clarity and visual aids,
DOE notes that, as discussed, the
Department has developed a document
which includes visual aids and
examples of how the OCMG concept
works in application (see EERE–2023–
BT–TP–0014–0001). This document
presents several examples that make
clear the OCMG concept and how it is
used to determine the individual
model(s) that can be used to determine
representations for a basic model. DOE
encourages stakeholders to review this
document for additional clarification,
and the Department will consider
developing other forms of visual aid and
examples should stakeholders request it.
For the reasons discussed in the
previous paragraphs and the August
2023 TP NOPR, DOE is adopting its
proposed approach for determining the
configuration of a unit under test. DOE
is also adopting two updates to the
approach proposed in the August 2023
TP NOPR, as explained in the
paragraphs that follow.
First, after consideration of comments
received, DOE is changing the required
compliance date to be when certifying
to standards denominated in terms of
IVHE and IVEC, should those standards
be established, rather than starting 360
days after publication of the test
procedure final rule in the Federal
Register (as proposed). This is
consistent with the approach that DOE
addressed through representation provisions of 10
CFR 429.43(a)(3)(v). In this final rule, those
provisions are instead being adopted at 10 CFR
429.43(a)(3)(vi). Further, the provisions proposed in
table 6 to 10 CFR 429.43(a)(3)(v)(A) are being
adopted in table 7 to 10 CFR 429.43(a)(3)(vi)(A).
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
has taken for establishing similar
provisions for other categories of
commercial air conditioning equipment;
i.e., for other categories such as CRACs
(88 FR 21816, 21836–21837 (April 11,
2023)), variable refrigerant flow multisplit systems (87 FR 63860, 63892 (Oct.
20, 2022)), and SPVUs (87 FR 75144,
75166 (Dec. 7, 2022)), DOE specified a
compliance date for similar
‘‘configuration of unit under test’’
provisions to be the compliance date of
amended energy conservation standards
in terms of the new metric.
Additionally, this compliance date
change ensures that manufacturers will
have adequate time to learn and
understand the process. As a result, the
provisions that DOE is adopting in 10
CFR 429.43 and 429.134 will apply
when certifying to standards
denominated in terms of IVHE and IVEC
or for assessment and enforcement
testing of models subject to energy
conservation standards denominated in
terms of IVEC and IVHE, if such
standards are adopted. Consistent with
the compliance date for provisions in 10
CFR 429.43 and 429.134, DOE is also
not adopting any test provisions for
units with specific components in
appendix A, and is instead only
adopting such test provisions in
appendix A1, which would be used
when certifying compliance with
standards in terms of IVHE and IVEC,
should those standards be established.
Second, DOE is adopting in table 2 to
appendix A1 the provision for how to
test units with drain pan heaters
specified in Table 37 to appendix D2 to
AHRI 1340–2023 (i.e., disconnect drain
pan heaters for testing). Although not
proposed in the August 2023 TP NOPR,
DOE has concluded that this guidance
for how to test units with drain pan
heaters is appropriate and consistent
with test provisions for other
components that DOE proposed in the
August 2023 TP NOPR.
As discussed, DOE’s adopted
provisions regarding configuration of
unit under test in 10 CFR 429.43 and
429.134 apply to equipment subject to
standards in terms of IVHE and IVEC.
b. Coated Coils
DOE received several comments in
response to the proposal to exclude
coated coils from the specific
components list in 10 CFR 429.43.
Carrier, Trane, AHRI, and Lennox
opposed DOE’s proposed exclusion of
coated coils from the specific
components list. (Carrier, No. 8 at p. 3;
Trane, No. 14 at p. 4; AHRI, No. 15 at
p. 6; Lennox, No. 9 at p. 2) AHRI
asserted that DOE provided no data to
support the proposal and that the
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
proposal could more than double
manufacturers’ listed basic models.
(AHRI, No. 15 at p. 6)
Trane stated that there are a multitude
of coil coatings available in the
marketplace and that many are
customized per specific customer
requests. (Trane, No. 14 at p. 4) Trane
further commented that many coils
undergo a special ‘‘non-standard’’
process to have coil coatings applied,
often requiring coils to be sent to a third
party prior to being installed in the unit
during the manufacturing process,
which adds significant lead time to the
equipment as well as variability in types
of coatings that are applied. (Id.) Trane
argued that excluding coated coils from
the list of specific components would
necessitate extensive testing in order to
develop adequate performance models
for all cases. (Id.) Trane additionally
stated that this would also multiply the
number of listed models, as some coil
coatings may have significant
performance impacts while some may
not. (Id.) Trane stated that units with
coated coils only represent a very small
fraction of the market, and, therefore,
requiring all equipment to include coil
coatings in the basic models is not
representative of the vast majority of
applications in the marketplace. (Id.)
Trane also argued that this requirement
would be unduly burdensome for
manufacturers, given that coated coils
represent such a small share of the
market. (Id.)
Carrier stated that there is a negative
impact to performance when a unit is
first produced with coated coils, but
Carrier asserted that the coating
prevents degradation over the lifetime of
the unit as compared to a unit with an
uncoated coil in certain applications.
(Carrier, No. 8 at p. 3) In the event that
coated coils are removed from the list of
specific components, Carrier stated that
it is concerned that energy conservation
will be reduced over the life of products
in the applications that require these
components. (Id.) If coated coils are
excluded from the list of specific
components, Carrier opposed the
proposed 360-day compliance date for
requirements for representations of
those models, stating that compliance
would require additional laboratory
time and engineering resources that are
currently fully allocated to refrigerating
transition projects required to meet the
Environmental Protection Agency’s
January 1, 2025 compliance date. (Id.)
In response, DOE notes that the
comments received in response to the
August 2023 TP NOPR indicate that
some coil coatings may not have a
significant impact on performance while
other coil coatings would. Given that
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
comments suggest that certain
implementations of coated coils do not
impact energy use whereas others do,
DOE has determined that for those units
for which coated coils do impact energy
use, representations should include
those impacts, thereby providing full
disclosure for commercial customers.
Regarding Trane’s assertion that
including coated coils in
representations would be unduly
burdensome and assertions that the
proposal would significantly increase
the number of listed basic models, DOE
notes that not all coil coatings would
necessarily warrant separate basic
models. DOE’s definition for ‘‘basic
model’’ at 10 CFR 431.92 specifies that
a basic model for CUACs and CUHPs
can comprise models with ‘‘comparably
performing’’ heat exchangers, which
allows for models with small variations
in performance still to be included
together in the same basic model, so
long as, consistent with the
clarifications adopted and previously
discussed in this final rule, the
representations for the basic model are
based on the least-efficient
configuration. Therefore, coil coatings
with similar performance impacts could
be rated within the same basic model,
and coil coatings without a significant
impact on performance could be
included in the same basic model as
models with no coil coatings.
DOE expects that manufacturers
already have a general understanding of
which coil coatings might have
significant impacts on performance,
based on coil coating material and
thickness. To the extent that a
manufacturer needs to determine
whether a coil coating impacts
performance, the manufacturer could
presumably determine this for a given
model and apply that understanding to
other models. In other words, a given
coil coating is likely to have similar
impacts across all basic models of
CUACs and CUHPs, such that finding
that the coating has no substantive
impact on performance for a given
model likely indicates such a finding
would apply to other models as well.
Thus, DOE expects that there would be
no need to separately confirm ‘‘no
impact’’ from a given coil coating on
each basic model for which it is offered.
Further, DOE notes that AEDMs can be
used to simulate performance of models
with coated coils such that not all
models require testing. Therefore, DOE
has concluded that the proposed
approach for coated coils is not unduly
burdensome.
DOE disagrees with Trane’s comment
that requiring all equipment to include
coil coatings in the basic models is not
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
44019
representative of the vast majority of
applications in the marketplace. The
proposed approach does not require that
all representations for CUACs and
CUHPs be based on the presence of coil
coatings; to the extent that
manufacturers offer a model with and
without a coil coating that substantively
impacts performance, the manufacturer
can rate as separate basic models with
and without the coil coatings. The basic
model with ratings based on
performance without the coil coating
would represent the shipments of units
without coil coatings. Further, for coil
coatings that impact performance,
ratings based on the presence of coil
coatings are representative of shipments
of units with such coil coatings, and
performance ratings based on the
presence of the coil coating provide a
more accurate assessment of the unit’s
energy consumption to commercial
consumers.
Regarding AHRI’s assertion that DOE
has not provided any data to support its
proposal, DOE notes that comments
received from both Trane and Carrier
indicate that some coil coatings have
negative performance impacts.
Therefore, DOE concludes that no
further data are needed to justify
adopting a provision requiring that
ratings reflect coated coils with
substantive negative performance
impacts, as this is consistent with DOE’s
statutory authority to prescribe test
procedures that produce results that are
representative of an average use cycle.
Additionally, as discussed earlier in this
section, to the extent that manufacturers
produce units with coated coils that do
not impact performance as compared to
units with uncoated coils, the
manufacturer may group such
individual models together within the
same basic model.
DOE disagrees with Carrier’s assertion
that including coated coils in
representations will result in energy
conservation being reduced over the life
of products in the applications that
require coated coils. DOE expects that
commercial customers who are
currently purchasing CUACs and
CUHPs with coated coils do so because
they understand coil protection to be
important for their application, and
DOE does not expect that such
consumers would stop purchasing units
with coated coils if ratings are required
to reflect performance impacts of coated
coils. However, the incorporation of
performance impacts of coated coils into
ratings for CUACs and CUHPs will
provide commercial consumers with
more accurate assessments of the energy
consumption of various models of
CUACs and CUHPs, and will, therefore,
E:\FR\FM\20MYR2.SGM
20MYR2
44020
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
better elucidate any performance tradeoffs associated with coil coatings and
will better inform consumers as to coil
coatings that may have less performance
impact than others.
Regarding Carrier’s concern about the
timeline for required representations
with coated coils, as previously
discussed, DOE is adopting all
provisions for specific components with
a compliance date starting when
certifying to standards in terms of IVHE
and IVEC, should those standards be
established, instead of the proposed
compliance date of 360 days after
publication of the final rule in the
Federal Register. DOE has concluded
that the adopted compliance date will
provide adequate lead time for
manufacturers to develop
representations that reflect the amended
test procedure and representation
provisions adopted in this final rule.
For the reasons described in the
previous paragraphs and consistent with
the proposals in the August 2023 TP
NOPR, DOE is not incorporating coated
coils into DOE’s provisions specified in
10 CFR 429.43(a)(3) that allow for the
exclusion of specified components
when determining represented values
for CUACs and CUHPs.
G. Represented Values
In the following sections, DOE
discusses requirements regarding
represented values. To the extent DOE
is adopting changes to the requirements
specified in 10 CFR 429 regarding
representations of CUACs and CUHPs,
such amendments to 10 CFR part 429,
will be required: (1) starting 360 days
after the date of publication in the
Federal Register of this final rule when
certifying to an EER, IEER, or COP
standard or (2) starting on the
compliance date of amended energy
conservation standards denominated in
terms of IVEC or IVHE, should DOE
adopt such standards. Prior to 360 days
after the date of publication in the
Federal Register of this final rule, the
current requirements will apply.
lotter on DSK11XQN23PROD with RULES2
1. Cooling Capacity
In the August 2023 TP NOPR, DOE
proposed to adopt provisions relating to
the represented value of cooling
capacity at 10 CFR 429.43(a)(1)(iv), as
well as the verification of cooling
capacity during enforcement testing at
10 CFR 429.134(g). 88 FR 56392, 56433–
56434 (August 17, 2023). The following
sections include discussion of the
proposals in the NOPR, responses to
related comments, and the approaches
adopted in this final rule.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
a. Representations of Cooling Capacity
For CUACs and CUHPs, cooling
capacity determines equipment class,
which in turn determines the applicable
energy conservation standard. 10 CFR
431.97. Cooling capacity also dictates
the minimum ESP test condition
applicable under Table 7 of AHRI 340/
360–2022 (i.e., larger capacity units are
required to be tested at higher ESPs),
which in turn affects the performance of
the unit. Cooling capacity is a required
represented value for all CUACs and
CUHPs, but the requirements currently
specified in 10 CFR 429.43(a)(1)(iv)
regarding how the represented value of
cooling capacity is determined only
apply to ACUACs and ACUHPs.
In the August 2023 TP NOPR, DOE
proposed to make certain modifications
to these provisions and to expand the
applicability of these provisions, as
amended, to all of the CUACs and
CUHPs that are the subject of this
rulemaking. Specifically, DOE proposed
that the represented value of cooling
capacity must be between 95 and 100
percent of the mean of the total cooling
capacities measured for the units in the
sample. 88 FR 56392, 56433 (August 17,
2023). DOE also proposed in the August
2023 TP NOPR that for units where the
represented value is determined through
an AEDM, the represented value of
cooling capacity must be between 95
and 100 percent of the total cooling
capacity output simulated by the
AEDM. Id. Additionally, DOE proposed
to remove the existing requirement in 10
CFR 429.43(a)(1)(iv) that the represented
value of cooling capacity correspond to
the nearest appropriate Btu/h multiple
according to Table 4 of ANSI/AHRI 340/
360–2007 in order to allow
manufacturers flexibility in certifying a
rated value that provides a
representation of cooling capacity that
may be more meaningful for commercial
consumers. Id. DOE argued that these
proposals would ensure that the rated
capacity is representative of the unit’s
performance, while allowing
manufacturers to conservatively rate
capacity if the manufacturer deemed
such conservative rating necessary to
ensure that equipment is capable of
performing at the cooling capacity for
which it is represented to consumers.
Id. DOE requested comment on its
proposals related to the representation
of cooling capacity. Id.
Carrier supported DOE’s cooling
capacity representation proposal.
(Carrier, No. 8 at p. 4) AHRI commented
that it opposes DOE’s proposal that
represented capacity must be between
95 to 100 percent of measured or
simulated capacity for units where the
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
represented value is determined through
an AEDM, asserting that this tolerance
is too narrow given that manufacturers
can rate capacity at 95 percent of
development tests. AHRI further argued
that the proposal allows for no (0
percent) tolerance for variation because
tested capacity during enforcement
could be at 105 percent (per DOE’s
proposal regarding cooling capacity
used to determine ESP requirements
during DOE testing, which is discussed
in section III.G.1.b of this final rule).
(AHRI, No. 15 at p. 6) Rheem
commented that it opposed DOE’s
proposal for a one-sided tolerance to be
within 95 to 100 percent of rated
cooling capacity, arguing that this
tolerance does not provide enough
margin to account for factors that affect
measurements such as manufacturing
variation and test lab conditions.
Instead, Rheem recommended that DOE
consider adoption of a wider two-sided
tolerance that accounts for measurement
variability, such as 90 to 110 percent of
rated capacity. (Rheem, No. 12 at p. 2)
Lennox similarly commented that it
opposes DOE’s proposal to require that
the measured cooling capacity must be
between 95 and 100 percent of the
represented value and argued the
proposed tolerance is too narrow, given
that manufacturers can rate up to 100
percent of the tested value. Lennox
recommended DOE instead provide a
tolerance range for measured capacity
between 95 and 105 percent. (Lennox,
No. 9 at p. 2)
As previously expressed, DOE’s
proposal to limit the represented value
of cooling capacity to be within 95 and
100 percent of the mean of the total
cooling capacities measured for the
units in the sample (or simulated by an
AEDM) was intended to allow
manufacturers to conservatively rate
capacity if the manufacturer deemed
such conservative rating necessary to
ensure that equipment is capable of
performing at the cooling capacity for
which it is represented to consumers,
but it was also intended to prevent
manufacturers from over-rating
capacity. Comments from Rheem and
Lennox suggest that the commenters
misunderstood the proposal to be
imposing a tolerance on the measured
cooling capacity that is compared to the
rated cooling capacity. To clarify, this
provision specifies how represented
values of cooling capacity are
determined based on the sample of
measured values (or values calculated in
an AEDM) for a given basic model.
Verification of rated cooling capacity,
which is a separate issue, is discussed
in the following section.
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
Rated cooling capacity is used to
determine the ESP requirements used in
testing; therefore, DOE has concluded
that significant underrating or
overrating of capacity could cause
unintended consequences such as
inequitable ratings due to differences in
self declarations. Further, significant
underrating or overrating of capacity
would provide an inaccurate assessment
to consumers of the amount of space
cooling a model can provide.
Additionally, the 95 to 100 percent
tolerance is consistent with what has
been adopted for other categories of
commercial air-conditioning, such as
DX–DOASes, SPVUs, and CRACs. See
10 CFR 429.43(a)(3)(i)(B)(1),
(a)(3)(iii)(B), and (a)(3)(iv)(B).
Regarding comments on
manufacturing variation and test
variability, DOE notes that if a
manufacturer develops ratings for a
basic model based on testing, the
manufacturer must test in accordance
with 10 CFR 429.43(a)(1), which
requires testing to be conducted on a
sample consistent of no less than two
units per basic model. The provisions at
10 CFR 429.43(a)(1) specify statistics
used to develop represented values
based on the mean and standard
deviation of measurements—i.e.,
reflecting the variation in measurements
included in the sample. If a
manufacturer chooses to consider more
units or variation in measured
performance using different test
chambers, DOE does not limit the
number of units or test chambers that
can be used in the sample to develop a
rating for a basic model. In other words,
a manufacturer can include in the
sample results from all testing it has
conducted for a basic model; therefore,
there should not be a scenario in which
a manufacturer has test results
suggesting that the mean of the sample
does not accurately reflect performance
of the basic model, because those test
results can be included in the sample.
Thus, there would be no basis for a
manufacturer to: (1) underrate cooling
capacity (as compared to the mean of
measured values) by more than 5
percent; or (2) overrate cooling capacity.
Similar logic applies if a manufacturer
develops ratings for a basic model based
on AEDM simulations in accordance
with 10 CFR 429.43(a)(2). DOE’s
regulations at 10 CFR 429.70 provide a
minimum number of tested models
needed for validation of an AEDM, but
if a manufacturer is concerned that the
tested models do not reflect what is
likely to be the ‘‘average’’ performance
for those models given manufacturing
variation and test variability, DOE does
not limit the number of units or test
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
chambers that can be used in the test
results used to validate an AEDM.
Therefore, similar to development of
ratings via testing, for AEDM-simulated
models, there would be no basis for a
manufacturer to: (1) underrate cooling
capacity (as compared to the AEDMsimulated values) by more than 5
percent; or (2) overrate cooling capacity.
Consequently, DOE has concluded
that the issues of manufacturing
variation and test variability are
sufficiently captured in DOE’s existing
regulations, so the Department is not
adopting any wider tolerance on the
represented cooling capacity than
proposed. As such, DOE is adopting the
provisions regarding representations of
cooling capacity as originally proposed.
b. Verification of Cooling Capacity
DOE currently outlines productspecific enforcement provisions at 10
CFR 429.134(g) for ACUACs and
ACUHPs, specifically that the mean of
cooling capacity measurements during
assessment or enforcement testing will
be used to determine the applicable
standards (which depend on cooling
capacity) for purposes of compliance.
First, DOE proposed in the August 2023
TP NOPR to expand the scope of this
requirement to include ECUACs and
WCUACs. 88 FR 56392, 56433 (August
17, 2023). Second, DOE proposed in the
August 2023 TP NOPR for all CUACs
and CUHPs that are the subject of this
rulemaking that if the mean of the
cooling capacity measurements exceeds
by more than 5 percent the cooling
capacity certified by the manufacturer,
the mean of the measurement(s) will be
used to select the applicable minimum
ESP test condition from Table 7 of AHRI
340/360–2022 in appendix A or from
Table 5 of the AHRI 1340–202X Draft in
appendix A1.30 Id.
In the August 2023 TP NOPR, DOE
requested comment on its proposal
related to the verification testing of
cooling capacity. Id. In response, Carrier
and Trane disagreed with DOE’s
proposal to establish a 5-percent
tolerance on rated capacity for
determining the applicable minimum
ESP condition when conducting
verification testing. (Carrier, No. 8 at p.
4; Trane, No. 14 at p. 5)
Trane asserted that this tolerance did
not provide enough range for
manufacturing, design, and testing
variability. Trane also asserted that as a
result of DOE’s proposed 5-percent
tested capacity limit above capacity
ratings, in some cases, capacity ratings
30 Table 5 of AHRI 1340–2023 includes the same
ESP test conditions as Table 5 of the AHRI 1340–
202X Draft.
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
44021
would be difficult to establish with the
proposed approach because the tested
capacity and ESP requirement
continually impact each other in a way
which would cause the tested capacity
to be either too high or too low
depending on the ESP applied. Trane
provided an example illustrating the
range of different capacities measured
under different ESP conditions for the
same model. Trane further asserted that
there would be no benefit for
manufacturers to conservatively rate
units at lower ESPs due to capacity
fluctuations because doing so could
increase the minimum efficiency
requirement and the resulting energy
efficiency performance could be
negatively impacted. (Trane, No. 14 at p.
5)
Carrier argued that if manufacturers
use the 5-percent margin in the certified
capacity rating as the proposed rule
allows, it is likely that the tested
capacity during assessment and
enforcement testing could go above the
105 percent tolerance, and, therefore,
Carrier recommended that a tolerance of
10-percent be applied to the tested
capacity. (Carrier, No. 8 at p. 4)
Carrier also commented regarding an
issue it found with the tolerance
proposal due to the new ESP
requirements in AHRI 1340. Carrier
commented that the tested net capacity
of a unit can decrease at higher static
pressures due to heat loss from the
electric motor operating against a higher
static pressure. As such, Carrier
commented that the tested capacity at
lower static pressures could be above
the test tolerance, but for the same unit
at higher ESPs, the tested capacity could
be below the test tolerances. Carrier
requested further clarification from DOE
as to which capacity should be used for
ESP determination if this situation were
to occur. (Id.)
After careful consideration of
comments received, DOE has concluded
that the proposed provision to use the
measured cooling capacity during
assessment and enforcement testing to
determine the ESP test condition if the
measured cooling capacity exceeds the
certified cooling capacity by more than
5 percent is not necessary at this time.
As stated in the August 2023 TP NOPR,
the intent of this proposal was to ensure
the unit is being tested to the
appropriate ESP and being evaluated
against the appropriate standard during
assessment and enforcement testing. 88
FR 56392, 56433 (August 17, 2023).
DOE has concluded that the adopted
requirement (discussed in section
III.G.1.a of this final rule) for the
represented value of cooling capacity to
be between 95 and 100 percent of the
E:\FR\FM\20MYR2.SGM
20MYR2
44022
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
mean of the total cooling capacities
measured for the units in the sample (or
between 95 and 100 percent of the
AEDM-simulated cooling capacity) will
ensure that the rated cooling capacity
accurately reflects the cooling capacity
for a basic model. Therefore, DOE has
determined that maintaining the current
policy of selecting the ESP requirement
used for DOE testing based on the rated
cooling capacity rather than the
measured cooling capacity will provide
a representative measure of the
equipment’s energy use. DOE
acknowledges the issue raised by
commenters, and notes that maintaining
the current policy will prevent a
situation in which the measured
capacity iteratively affects the
applicable ESP requirement, and will
avoid any conflicts between DOE’s
enforcement provisions and DOE’s
adopted provisions allowing
conservative rating of cooling capacity
as low as 95 percent. As such, DOE is
not adopting its proposal that the mean
of measured capacities be used to select
the applicable minimum ESP condition
when it exceeds the rated cooling
capacity of a basic model by more than
5 percent.
DOE did not receive comment
regarding its proposal to expand the
scope of the current product-specific
enforcement requirements at 10 CFR
429.134(g) to ECUACs and WCUACs.
DOE has determined that extending this
provision to ECUACs and WCUACs will
ensure that the unit is being evaluated
against the appropriate standard. As
such, DOE is expanding the scope of the
requirement at 10 CFR 429.134(g) that
the mean of cooling capacity
measurements will be used to determine
the applicable standards (which depend
on cooling capacity) for purposes of
compliance to apply to ECUACs and
WCUACs.
2. AEDM Tolerance for IVEC and IVHE
As discussed previously, DOE’s
existing testing regulations allow the
use of an AEDM, in lieu of testing, to
simulate the efficiency of CUACs and
CUHPs. 10 CFR 429.43(a). For models
certified with an AEDM, results from
DOE verification tests are subject to
certain tolerances when compared to
certified ratings. In the August 2023 TP
NOPR, DOE proposed in table 2 to
paragraph (c)(5)(vi)(B) at 10 CFR 429.70
to specify a tolerance of 10 percent for
CUAC and CUHP verification tests for
IVEC and IVHE. 88 FR 56392, 56434
(August 17, 2023). This tolerance is
identical to the current tolerance
specified for IEER (for ACUACs and
ACUHPs) and for integrated metrics for
other categories of commercial air
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
conditioners and heat pumps (e.g.,
integrated seasonal coefficient of
performance 2 and integrated seasonal
moisture removal efficiency 2 for DX–
DOASes). DOE also proposed to specify
a tolerance of 5 percent for CUAC and
CUHP verification testing for the
optional EER2 and COP2 metrics. This
tolerance is identical to the current
tolerances specified for EER and COP
for CUACs and CUHPs. Id.
DOE did not receive any comments
regarding this proposal. Therefore, DOE
is adopting the AEDM tolerances
applicable to IVEC, IVHE, EER2, and
COP2 as proposed in the August 2023
TP NOPR.
3. Minimum Part-Load Airflow
As previously discussed in sections
III.D.1 and III.D.2 of this document, the
IVEC and IVHE metrics account for
energy consumed (specifically that of
the indoor fan) in mechanical cooling
and heating, as well as modes other than
mechanical cooling and heating (e.g.,
economizer-only cooling, cooling season
ventilation, heating season ventilation).
IVEC and IVHE do not include separate
tests or airflow rates for ventilation
hours or economizer-only cooling (only
applicable to IVEC). For example, for
the economizer-only cooling hours in
the D bin, the indoor fan power
measured when operating at the lowest
manufacturer-specified part-load airflow
for a given load bin is applied for
economizer-only cooling hours in that
bin. Section 6.2.7 and 6.3.10 of the
AHRI 1340–202X Draft require that the
lowest indoor fan power measured for
cooling or heating tests is applied for
cooling-season ventilation hours in
IVEC and heating-season ventilation
hours in IVHE. AHRI 1340–2023
maintains these provisions. Therefore,
considering mechanical cooling and
heating, as well as other operating
modes (e.g., economizer-only cooling,
ventilation), the indoor fan power
measured at the lowest manufacturerspecified part-load cooling and heating
airflow rates represents a significant
fraction of the power included in the
IVEC and IVHE metrics (i.e., indoor fan
power measured at these airflow rates is
weighted by a significant number of
hours), and differences in the lowest
manufacturer-specified part-load airflow
can significantly impact IVEC and IVHE
ratings.
Based on examination of publiclyavailable product literature, DOE
understands that many basic models of
a CUAC or CUHP have controls that
allow for modulation of the minimum
airflow used across a wide range of
airflow turndown. DOE’s research
suggests that many models are
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
distributed in commerce with an ‘‘asshipped’’ minimum airflow and/or a
default minimum airflow setting
recommended in manufacturer
installation instructions. However, in
many cases, DOE observed that the unit
controls allow the installer to change
this minimum airflow setting during
installation to reflect any constraints
specific to a particular installation. DOE
understands that such constraints may
include the duct distribution system,
the thermostat the CUAC or CUHP is
paired with, and the minimum
ventilation rate for the conditioned
space served by the CUAC or CUHP. To
ensure that IVEC and IVHE ratings
reflect indoor fan power that is
generally representative of airflow rates
that would be used in the field for a
given basic model, DOE considered the
following two options for requirements
related to minimum part-load airflow
used for representations of IVEC and
IVHE in the August 2023 TP NOPR:
1. Representations of IVEC and IVHE
(including IVHEc, as applicable) must
be based on setting the lowest stage of
airflow to the highest part-load airflow
allowable by the basic model’s system
controls. For example, if fan control
settings for a basic model allow its
lowest stage of airflow to range from 40
to 60 percent, the basic model will need
to be represented based on the lowest
stage of airflow set to 60 percent of the
full-load airflow.
2. Representations of IVEC and IVHE
(including IVHEc, as applicable) must
be determined using minimum part-load
airflow that is no lower than the highest
of the following: (1) the minimum partload airflow obtained using the asshipped system control settings; (2) the
minimum part-load airflow obtained
using the default system control settings
specified in the manufacturer
installation instructions (as applicable);
and (3) the minimum airflow rate
specified in section 5.18.2 of AHRI
1340–202X Draft.31 88 FR 56392,
56434–56435 (August 17, 2023).
In the August 2023 TP NOPR, DOE
tentatively concluded that option 1,
which requires representations based on
the highest minimum part-load airflow
allowable by system controls, may result
in unrepresentatively high airflow rates
in cases in which a basic model allows
configuration of minimum airflow to a
very high percentage to accommodate a
small fraction of installations in which
minimum part-load airflow must be
high (e.g., in applications with very high
minimum ventilation rates). Id.
31 Section 5.18.2 of AHRI 1340–2023 includes the
same provisions as those specified in section 5.18.2
of the AHRI 1340–202X Draft.
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
Therefore, DOE proposed in the August
2023 TP NOPR to adopt option 2 and
requested comment on its proposal, as
well as any alternate options not listed
that would ensure representations of
IVEC and IVHE are based on minimum
part-load airflow that is representative
of field installations. Id.
AHRI, Carrier, Lennox, Rheem, and
Trane opposed DOE’s proposal and
argued that the only restriction on
minimum airflow rate should be what
was agreed to in Recommendation #6 of
the ACUAC and ACUHP Working Group
TP Term Sheet (i.e., limiting the
minimum airflow rate to that specified
in Section 5.18.2 of the AHRI 1340–
202X Draft). (AHRI, No. 15 at pp. 6–7;
Carrier, No. 8 at p. 5; Lennox, No. 9 at
p. 3; Rheem, No. 12 at p. 2; Trane No.
14 at p. 6) Carrier commented that the
ACUAC and ACUHP Working Group TP
Term Sheet includes a requirement for
manufacturers to certify the airflow that
is used in the lowest-stage cooling test,
and stated that this ensures that the unit
is capable of running in application at
the airflows that were used in the tests
or AEDM. Carrier further stated that
restricting the broad range of airflow
settings in commercial equipment to
only those that are default from the
factory is not appropriate and
recommended that no further
restrictions be placed on tested airflows
beyond what was agreed upon in the
ACUAC and ACUHP Working Group TP
Term Sheet. (Carrier, No. 8 at p. 5)
AHRI and Trane asserted that ratings
are based on a representative average of
many customer applications and that
equipment built for stock has a default
airflow and ESP with the expectation
that customers will adjust and
commission (i.e., adjust sheaves, VFDs,
discharge air temperature setpoints, or
other parts of the equipment) for their
specific applications, and made-to-order
equipment is built per customer
specifications for a given installation.
(AHRI, No. 15 at pp. 6–7; Trane, No. 14
at p. 6) AHRI and Trane further stated
that the default airflow and ESP may not
align with the ESP requirements in the
test procedure, and that considerable
variation across installations does not
align with a single rating point. (Id.)
Trane further stated that equipment
utilizing sheaves in the airflow system
almost always require field adjustment
up to and including different sheave
components ordered as field-installed
accessories to complete an equipment
installation. (Trane, No. 14 at p. 6) AHRI
and Trane further stated that
supplemental test instructions
submitted as part of certification ensure
that the equipment is properly set up for
any verification testing as per the test
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
procedure. (AHRI, No. 15 at pp. 6–7;
Trane, No. 14 at p. 6)
ASAP & ACEEE expressed support for
DOE’s proposal regarding determination
of part-load airflow, stating that it
improves representativeness by
considering the default and as-shipped
settings, and expressed concern that
without DOE’s proposal, manufacturers
could rate models with airflows lower
than would be representative. (ASAP &
ACEEE, No. 11 at pp. 1–2)
Regarding the comments that DOE
should impose no additional
requirements on minimum part-load
airflow and that the only requirements
should be the ones in the ACUAC/HP
Working Group TP Term Sheet, DOE
has concluded that the minimum partload airflow requirements proposed for
10 CFR 429.43 have a different purpose
than, and do not deviate from or conflict
with, the requirement regarding
minimum airflow specified in
Recommendation #6 of the ACUAC and
ACUHP Working Group TP Term Sheet
(which is the minimum part-load
airflow specified in section 5.18.2 of the
AHRI 1340–202X Draft and AHRI 1340–
2023). In this final rule, DOE is adopting
section 5.18.2 of AHRI 1340–2023 in the
test procedure at appendix A1,
consistent with Recommendation #6 of
the ACUAC and ACUHP Working Group
TP Term Sheet. This minimum partload airflow requirement from the Term
Sheet and AHRI 1340 represents the
minimum airflow required to provide
adequate ventilation in a typical
building (based on an average of
building types used to develop the IVEC
metric, as discussed in section III.D.1 of
this document). In other words, the
requirement in the test procedure is a
lower bound on minimum airflow for
any CUAC/HP model serving the
average building, but it is not
necessarily representative of the
minimum part-load airflow used in the
field for a given CUAC or CUHP model.
For example, for a model that is
typically installed with a minimum
part-load airflow of 67 percent of fullload airflow, the minimum airflow limit
specified in section 5.18.2 of AHRI
1340–2023 would be far lower than that
that representative minimum and
would, therefore, fail to serve as a
guardrail ensuring the minimum partload airflow used for rating that model
is representative of how the model is
typically installed. DOE found in an
examination of publicly-available
product literature, the range of airflows,
including minimum part-load airflow,
can differ between models based on
application, design of the unit, and
manufacturer preferences.
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
44023
As part of Working Group discussions
regarding energy conservation
standards, which occurred after the
ACUAC and ACUHP Working Group TP
Term Sheet was agreed to, it was
discussed that minimum part-load
airflow is one of the largest
determinants of IVEC performance (see
EERE–2022–BT–STD–0015–0092 at pp.
22–27). Specifically, during the course
of the Working Group energy
conservation standards negotiations,
industry members in the ACUAC/HP
Working Group provided a DOE
contractor with a confidential,
anonymized dataset that included
simulated IEER and IVEC values for
more than 100 models of CUACs and
CUHPs currently available on the
market. Analysis of this dataset
indicated that the minimum part-load
airflow is one of the most significant
differentiators between models with
lower and higher IVEC values. This is
because, as discussed, the minimum
part-load airflow is allocated to a large
number of hours when calculating IVEC,
so lower values of minimum part-load
airflow are associated with higher
values of IVEC. Given the Department’s
statutory obligation to ensure that
ratings are based on a test procedure
that is reasonably designed to produce
test results which reflect energy
efficiency during a representative
average use cycle that is not unduly
burdensome to conduct (42 U.S.C.
6314(a)(2)), DOE has concluded that
provisions beyond those included in
AHRI 1340–2023 are needed to ensure
that the minimum part-load airflow
used to determine IVEC is
representative of how a given model is
typically installed. Such provisions,
when combined with the minimum
airflow limit in AHRI 1340–2023 that
DOE is also adopting in this final rule,
would prevent use of an
unrepresentatively low minimum partload airflow that could boost efficiency
ratings but not ultimately result in
energy savings in the field. The
provisions proposed by DOE address
this issue by using the as-shipped or
default values of minimum part-load
airflow as indicators of the
representative minimum part-load
airflow used in the field. Although
industry commenters objected to having
additional requirements on the
minimum part-load airflow, the
objecting commenters apparently did
not recognize the representativeness
issue identified by DOE nor provide any
alternate approaches to address the
issue. In the absence of any suggested
alternative approaches, DOE has
determined that the proposed approach
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
44024
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
is appropriate to ensure that the
minimum part-load airflow used to
determine IVEC is representative of field
operation.
Regarding comments from AHRI and
Trane that ratings are based on a
representative average of many
customer applications and that
considerable variation across
installations does not align with a single
rating point, DOE agrees that the test
procedure is and should be based on a
representative average of many
applications. While this average rating
inherently cannot perfectly represent
every application, it should be
representative of an average or typical
installation. DOE disagrees that its
proposed minimum part-load airflow
provisions deviate from this
‘‘representative average application’’
approach underlying the test procedure.
Without DOE’s proposed provisions,
there would be no mechanism
constraining the certified minimum
part-load airflow to be representative of
how a given model is typically installed,
and further, manufacturers would be
incentivized to certify as low a
minimum part-load airflow as possible
in order to achieve a higher IVEC rating.
DOE has concluded that the default or
as-shipped minimum airflow setting is
the best publicly-available proxy for
what the most representative minimum
part-load airflow is for a given model.
DOE understands that many installers of
CUACs and CUHPs do not change
settings from their default and/or asshipped values; therefore, DOE expects
that manufacturers are incentivized to
provide default and/or as-shipped
minimum airflow values that are
appropriate for and representative of a
typical installation. DOE understands
that that some applications may have
lower minimum part-load airflows than
provided by the default settings, but has
concluded that the default or as-shipped
minimum part-load airflow settings are
representative of a typical installation.
Additionally, the default airflow setting
for a specific model is not a single rating
condition for all models (such as an ESP
requirement or test condition)—it
instead reflects whatever model-specific
considerations the manufacturer might
use to determine the default or asshipped minimum part-load airflow for
the model.
Additionally, DOE notes that several
of the concerns expressed by
commenters do not apply to DOE’s
proposal. Specifically, concerns
expressed regarding the adjustment of
sheaves and whether the default airflow
settings are compatible with the airflow
and ESP requirements in the test
procedure are not relevant to the
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
proposal, because DOE’s proposal only
addresses part-load airflow. For CUACs
and CUHPs with adjustable sheaves, the
sheaves are adjusted when installing the
unit to ensure the fan drive assembly is
providing the appropriate airflow for a
given installation. Similarly, sheaves are
typically adjusted as part of test set-up
for the full-load cooling test to meet the
full-load airflow and ESP test
requirements withing tolerance.
However, sheaves are not adjusted
between full-load and part-load
operation, and are, therefore, not
relevant to this proposal. Similarly, DOE
recognizes that the default full-load
airflow settings may not be compatible
with the airflow and ESP requirements
in the test procedure, but DOE has
proposed no restrictions on the certified
full-load airflow. In summary, DOE’s
proposal does not have any effect on the
fan control settings used to achieve the
full-load airflow and ESP used for
testing. DOE’s proposal only affects the
minimum part-load airflow for testing,
which is a percentage of the full-load
airflow already achieved in the full-load
cooling test, not an absolute value. Partload airflow is typically reduced by
lowering the power provided to the fan
motor by a VFD (relative to the power
provided for full-load cooling), an
adjustment that it made automatically in
field installations but can be manually
programmed during test. Therefore,
regardless of how different the fan
control settings needed to achieve the
full-load airflow and ESP used for
testing may be from the default or asshipped full-load airflow settings, DOE
has concluded that the default or asshipped minimum part-load airflow
settings provide an appropriate and
representative degree of airflow
turndown that will allow for meeting all
test tolerances.
Regarding comments by AHRI and
Trane that supplemental test
instructions indicate how units should
be set up for test, DOE notes that
supplemental test instructions are used
to ensure that DOE testing is performed
consistent with how the manufacturer
rated the equipment. Supplemental test
instructions do not ensure that
manufacturer-specified settings are
representative of field use for a basic
model. Similarly, the manufacturer’s
certification of the minimum airflow
used for ratings of a basic model (which
was cited by Carrier) does not ensure
that the certified airflow is
representative of field use. The
provisions proposed in 10 CFR 429.43
for minimum part-load airflow,
however, are intended to ensure that
manufacturer-specified and certified
PO 00000
Frm 00040
Fmt 4701
Sfmt 4700
minimum part-load airflows are
representative of field use.
For the reasons discussed in the
previous paragraphs, DOE is adopting
the proposed provisions for minimum
airflow in 10 CFR 429.43. DOE is not
amending certification requirements for
CUACs and CUHPs in this rulemaking,
but DOE will consider such
amendments in a separate rulemaking
for certification, compliance, and
enforcement. As part of that rulemaking,
DOE will consider certification
requirements pertaining to this
minimum airflow issue, such as
requiring certification of the range of
minimum part-load airflow allowed by
system controls for each basic model.
H. Enforcement Procedure for Verifying
Cut-In and Cut-Out Temperatures
Recommendation #10 of the ACUAC
and ACUHP Working Group TP Term
Sheet states that DOE will adopt
product-specific enforcement provisions
for ACUHPs that include a method to
verify certified cut-out and cut-in
temperatures based on the test method
outlined in the Residential Cold-Climate
Heat Pump Technology Challenge
(‘‘CCHP Challenge’’).32 The docketed
AHRI 1340–202X Draft did not include
test provisions for verifying cut-in and
cut-out temperatures, but in the August
2023 TP NOPR, DOE proposed to adopt
a method for verifying certified cut-out
and cut-in temperatures at 10 CFR
429.134(g) consistent with
Recommendation #10 of the ACUAC
and ACUHP Working Group TP Term
Sheet. 88 FR 56392, 56435 (August 17,
2023). Specifically, consistent with the
CCHP Challenge method and the
ACUAC and ACUHP Working Group TP
Term Sheet, the proposed method
specified gradually ramping down
outdoor air temperature until the unit
cuts out and gradually ramping back up
outdoor air temperature until the unit
cuts back on, with the temperature
ramp-up and ramp-down conducted at
1.0 °F every 5 minutes. DOE did not
receive any comments on its proposed
method for verifying cut-in and cut-out
temperatures.
Appendix H of AHRI 1340–2023
includes a procedure for verifying cutin and cut-out temperatures that is
generally consistent with the procedure
proposed in the August 2023 TP NOPR.
As such, and consistent with
Recommendation #10 of the ACUAC
and ACUHP Working Group TP Term
Sheet, DOE is adopting this procedure
for verifying certified cut-in and cut-out
temperatures through reference to
32 See www.energy.gov/sites/default/files/202110/bto-cchp-tech-challenge-spec-102521.pdf.
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
appendix H of AHRI 1340–2023 in
DOE’s product-specific enforcement
provisions at 10 CFR 429.134(g). DOE
will address certification requirements
for CUACs and CUHPs, including the
potential requirement for certification of
cut-out and cut-in temperatures, in a
separate rulemaking for certification,
compliance, and enforcement.
lotter on DSK11XQN23PROD with RULES2
I. Organization of the Regulatory Text
for CUACs and CUHPs
In addition to the substantive changes
discussed previously in this document,
DOE proposed organizational changes to
table 1 to 10 CFR 431.96(b) and tables
1 through 6 to 10 CFR 431.97 in the
August 2023 TP NOPR that were not
substantive and were intended to reflect
terminology changes and to improve the
overall readability of the tables. 88 FR
56392, 56435–56436 (August 17, 2023).
Specifically, in table 1 to 10 CFR
431.96(b) (regarding test procedures for
commercial air conditioners and heat
pumps), DOE proposed to revise
terminology to reflect the proposed
definition for ‘‘commercial unitary air
conditioners with a rated cooling
capacity greater than or equal to 65,000
Btu/h (CUACs) and commercial unitary
heat pumps with a rated cooling
capacity greater than or equal to 65,000
Btu/h (CUHPs),’’ discussed further in
section III.B.1 of this final rule. Id.
Additionally, tables 1 through 5 to 10
CFR 431.97 currently specify cooling
and heating standards for CUACs,
CUHPs, and water-source heat pumps
(‘‘WSHPs’’). DOE also proposed to
revise this terminology to reflect the
proposed definition for CUACs and
CUHPs, remove outdated standards no
longer in effect, combine cooling and
heating standards into the same tables,
and create separate tables for standards
for ACUACs and ACUHPs (in Table 1),
WCUACs (in Table 2), ECUACs (in
Table 3), double-duct systems (in Table
4), and WSHPs (in Table 5). Id.
DOE did not receive comment in
response to the August 2023 TP NOPR
with respect to the proposed
organization of regulatory text for
CUACs and CUHPs. DOE has
determined that these changes will
improve the overall readability of the
tables in 10 CFR 431.96 and 431.97 and
are consistent with the other changes
adopted in this final rule. However, as
discussed in section III.B.1, DOE is not
finalizing the proposed definition for
CUAC and CUHP. As such, DOE is not
implementing the proposed changes in
10 CFR 431.96 and 431.97 to reflect the
proposed term for CUAC and CUHP.
Other than these terminology changes,
DOE is adopting its proposed
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
reorganization of regulatory text for
CUACs and CUHPs in this final rule.
J. Effective and Compliance Dates
The effective date for the adopted test
procedure amendments will be 75 days
after the date of publication of this final
rule in the Federal Register. EPCA
prescribes that all representations of
energy efficiency and energy use,
including those made on marketing
materials and product labels, must be
made in accordance with an amended
test procedure, beginning 360 days after
the date of publication of the final rule
in the Federal Register. (42 U.S.C.
6314(d)(1)) To the extent the modified
test procedure adopted in this final rule
is required only for the evaluation and
issuance of updated efficiency
standards, compliance with the
amended test procedure does not
require use of such modified test
procedure provisions until the
compliance date of updated standards.
K. Test Procedure Costs and Impact
EPCA requires that the test
procedures for commercial package air
conditioning and heating equipment,
which includes CUACs and CUHPs, be
those generally accepted industry
testing procedures or rating procedures
developed or recognized by either AHRI
or ASHRAE, as referenced in ASHRAE
Standard 90.1. (42 U.S.C. 6314(a)(4)(A))
Further, if such an industry test
procedure is amended, DOE must
amend its test procedure to be
consistent with the amended industry
test procedure, unless DOE determines,
by rule published in the Federal
Register and supported by clear and
convincing evidence, that such an
amended test procedure would not meet
the requirements in 42 U.S.C.
6314(a)(2)–(3) related to representative
use and test burden. (42 U.S.C.
6314(a)(4)(B))
In this final rule, DOE is revising the
existing test procedure for CUACs and
CUHPs (consolidating for ACUACs and
ACUHPs, ECUACs, and WCUACs) at
appendix A and adopting an amended
test procedure at appendix A1. These
adoptions are discussed in the following
sub-sections. DOE has also amended its
representation and enforcement
provisions for CUACs and CUHPs.
1. Appendix A
In this final rule, DOE has amended
the existing Federal test procedure for
CUACs and CUHPs (including doubleduct systems), which is currently
located at appendix A for ACUACs and
ACUHPs and 10 CFR 431.96 for
ECUACs and WCUACs. Specifically,
DOE consolidated the test procedures
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
44025
for ACUACs and ACUHPs, ECUACs,
and WCUACs at appendix A and
updated the test procedure to
incorporate by reference an updated
version of the applicable industry test
method, AHRI 340/360–2022. The
revisions to appendix A retain the
current efficiency metrics (i.e., EER,
IEER, and COP). The testing
requirements in appendix A are
generally consistent with those in AHRI
340/360–2022, which in turn references
ANSI/ASHRAE 37–2009. This is
generally consistent with the industry
test procedures referenced in the latest
version of ASHRAE Standard 90.1.
DOE has determined that the
amendments to appendix A will
improve the representativeness,
accuracy, and reproducibility of the test
results and will not be unduly
burdensome for manufacturers to
conduct or result in increased testing
cost as compared to the current test
procedure. The revisions to the test
procedure in appendix A for measuring
EER, IEER, and COP per AHRI 340/360–
2022 will not increase third-party
laboratory testing costs per unit relative
to the current DOE test procedure. DOE
estimates the current costs of physical
testing to the current required metrics to
be $10,500 for ACUACs, $12,000 for
ACUHPs, $6,800 for double-duct air
conditioners, $8,300 for double-duct
heat pumps, and $6,800 for ECUACs
and WCUACs. Further, DOE has
concluded that the adopted revisions to
the test procedure in appendix A will
not change efficiency ratings for CUACs
and CUHPs, and, therefore, will not
require retesting solely as a result of
DOE’s adoption of this amendment to
the DOE test procedure.33
2. Appendix A1
In the August 2023 TP NOPR, DOE
proposed to amend the existing test
procedure for CUACs and CUHPs
(including double-duct equipment) by
adopting a new appendix A1 that
references AHRI 1340–202X Draft,
including the IVEC and IVHE energy
efficiency metrics. DOE noted that the
proposed test procedure in appendix A1
would lead to an increase in test cost
from the current Federal test procedure;
therefore, DOE presented estimates of
33 Manufacturers are not required to perform
laboratory testing on all basic models. In
accordance with 10 CFR 429.70, CUAC and CUHP
manufacturers may elect to use AEDMs. An AEDM
is a computer modeling or mathematical tool that
predicts the performance of non-tested basic
models. These computer modeling and
mathematical tools, when properly developed, can
provide a means to predict the energy usage or
efficiency characteristics of a basic model of a given
covered product or equipment and to reduce the
burden and cost associated with testing.
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
44026
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
the test costs associated with the
proposed test procedure in appendix
A1. 88 FR 56392, 56436–56437 (August
17, 2023). The proposed test cost
estimates are presented in Table III–6.
DOE requested comments regarding its
tentative understanding of the impact of
the proposals in the NOPR, particularly
regarding DOE’s initial estimate of the
cost impacts associated with appendix
A1. Id.
Carrier commented that the test cost
estimates presented in the NOPR are
likely incorrect, as there is a substantial
difference in set-up time and the
amount of energy required to test from
the smallest systems to the largest.
(Carrier, No. 8 at p. 5)
Trane expressed concerns regarding
the cost estimate for the 5 °F optional
test, and the commenter argued that
testing to these low temperatures would
require significant capital investment on
the part of certification laboratories, as
well as increased time to conduct
testing at low temperature conditions
due to the need for more frequent
defrosting of the facility. (Trane, No. 14
at pp. 6–7) Specifically, Trane stated the
test cost for the optional 5 °F test should
be closer to $9,600 (representing four
additional shifts in the test laboratory)
rather than the $2,000–$4,000
additional cost estimated in the NOPR.
Id.
In this final rule, DOE is amending
the existing test procedure for CUACs
and CUHPs (including double-duct
equipment) by adopting a new appendix
A1 that utilizes the most recent version
of the applicable industry consensus
test procedure, AHRI 1340–2023,
including the IVEC and IVHE energy
efficiency metrics. Should DOE adopt
standards in a future energy
conservation standards rulemaking
denominated in terms of the new
metrics, the test procedure in appendix
A1 (which references AHRI 1340–2023)
would be required.
In light of the comments received,
DOE once again considered the
estimated costs and burdens associated
with the new appendix A1. For the
reasons that follow, DOE determined
these costs to have remained largely the
same as those presented in the August
2023 TP NOPR, with just a few
adjustments.
DOE has determined that these
amendments will be representative of an
average use cycle and will not be
unduly burdensome for manufacturers
to conduct. The test procedure in
appendix A1 will lead to an increase in
test cost from the current Federal test
procedure, as discussed in the following
paragraphs. The following paragraphs
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
include estimates for increases in cost of
testing at a third-party laboratory.
The change in ESP requirements
discussed in section III.D.1 that apply to
measuring the IVEC and IVHE metrics
will require additional test set-up that
DOE expects will increase test costs.
DOE has concluded that metal ductwork
will need to be fabricated for testing to
withstand the higher ESP requirements
(as compared to foamboard ductwork
typically used for testing to the current
test procedure). DOE estimates a test
cost increase ranging from $500 to
$1,500 per unit, depending on the unit
size/cooling capacity, associated with
this transition to metal ductwork. To
meet the return/supply duct ESP
requirement, DOE estimates an increase
of $200 per unit for the time required to
apply return duct restrictions. In
combination, DOE estimates a total test
cost increase of between $700 and
$1,700 per unit to meet the new ESP
requirements.
For determining IVEC, DOE has
concluded that there will not be an
increase in testing cost as compared to
measuring IEER per the current Federal
test procedure, beyond the costs
associated with the new ESP
requirements discussed previously.
For determining IVHE, there are two
required heating tests and several
additional optional heating tests. The
required heating tests are full-load tests
at 47 °F and 17 °F. The full-load test at
47 °F is already required for the current
Federal test procedure for determining
COP. The full-load test at 17 °F is
currently required for the AHRI
certification program. Because all
identified CUHP manufacturers are
AHRI members and participate in the
AHRI certification program and because
third-party laboratories currently have
the capability to perform these tests,
DOE expects that that the required
heating tests for IVHE will not increase
test cost as compared to testing that is
typically already conducted, beyond the
costs associated with the new ESP
requirements discussed previously.
Optional heating tests for CUHPs will
increase the cost of heating testing if
conducted. The optional tests for IVHE
are outlined in III.D.2 of this final rule,
which include: (1) an additional fullload test at 5 °F; (2) part-load tests at
17 °F and 47 °F (including up to 2 partload tests at each temperature); and (3)
for variable-speed units, boost tests at
17 °F and 5 °F. DOE estimates that each
optional test conducted will increase
the cost of heating testing by $2,000 to
$4,000 depending on the test condition.
Regarding Trane’s comments on
burden of the optional 5 °F test, DOE
disagrees that conducting a heating test
PO 00000
Frm 00042
Fmt 4701
Sfmt 4700
for CUHPs would cost as much as
$9,600 at third-party laboratories. DOE
expects Trane’s estimate may be
referring to test facilities that are not
designed for low-temperature testing.
However, DOE is aware of multiple
third-party laboratories commonly used
by the CUAC and CUHP industry for
testing that have test chambers that can
already achieve the 5 °F test condition
in much less time than would warrant
four shifts. Further, DOE notes that it
has received a test quote from a thirdparty laboratory for conducting the 5 °F
test that is within the range of test costs
estimated in the August 2023 TP NOPR.
Therefore, DOE maintains its estimate of
$2,000 to $4,000 for each optional
heating test. DOE reiterates that these
tests are optional, and, thus, the test
procedure adopted in this final rule will
not require any manufacturers to
conduct a 5 °F test.
For ECUACs, WCUACs, and doubleduct systems, the current Federal test
procedure requires testing to EER for
cooling tests; testing to IEER is not
currently required for ECUACs,
WCUACs, or double-duct systems.
Because measuring EER requires only a
single test, DOE expects that measuring
IVEC for ECUACs, WCUACs, and
double-duct systems will increase the
cost of cooling testing. Specifically, DOE
estimates the cost of additional cooling
tests to be $3,700 per unit. Further, the
previously discussed costs associated
with the new indoor air ESP
requirements ($700 to $1,700 depending
on unit size) will also apply to ECUACs,
WCUACs, and double-duct systems. In
addition, for double-duct systems DOE
expects that testing to appendix A1 will
require an additional $2,000 per unit for
set-up to meet the non-zero outdoor air
ESP requirement. Otherwise, DOE
expects similar test burden for
determining IVHE for double-duct
systems as for determining IVHE for
conventional ACUHPs, as discussed in
the preceding paragraphs.
Regarding Carrier’s comment about
the burden of testing higher-capacity
equipment, DOE acknowledges that
there may be higher third-party
laboratory test costs associated with test
set-up for larger units than for smaller
units. Accordingly, DOE estimates that
up to an additional shift (which DOE
estimates to cost approximately $2,600)
may be necessary for test set-up for the
largest covered basic models, and the
Department has adjusted the upper
bound of its estimated test cost range
accordingly.
Table III–6 shows DOE’s estimates for
testing to the current Federal test
procedure and the test procedure in
appendix A1.
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
44027
Equipment
Type
Test Cost for
Current
Federal Test
Procedure
ACUACs
ACUHPs
$10,500
$12,000
Double-duct
air
conditioners
Double-duct
heat pumps
$6,800
ECUACs and
WCUACs
$6,800
$8,300
In the August 2023 TP NOPR, DOE
also estimated the cost to develop and
validate an AEDM for determining IVEC
(and IVHE as applicable) for CUACs and
CUHPs (including double-duct systems)
to be $19,000 per AEDM. Once the
AEDM is developed, DOE estimated that
it would take one hour of an engineer’s
time (calculated based upon an
engineering technician wage of $41 per
hour) to determine efficiency for each
basic model using the AEDM. 88 FR
56392, 56437 (August 17, 2023).
AHRI, Carrier, Trane, and Rheem
commented that the proposed cost to
develop an AEDM to rate units to the
new IVEC and IVHE metrics were
greatly underestimated in the NOPR.
(AHRI, No. 15 at p. 7; Carrier, No. 8 at
p. 5; Trane, No. 14 at pp. 6–7; Rheem,
No. 12 at p. 3) Carrier stated that to
lower potential risk of failure or product
availability associated with an AEDM
issue, manufacturers typically test more
than the minimum two units required
for AEDM validation, and
manufacturers develop multiple AEDMs
to limit the number of basic models for
which each AEDM was used to generate
ratings. (Carrier, No. 8 at p. 5) AHRI and
Trane stated that manufacturers may
test significantly more units than the
two required by DOE to validate an
AEDM. (AHRI, No. 15 at p. 7; Trane, No.
14 at pp. 6–7) Rheem stated that the
adoption of appendix A1 will require
significant investment by manufacturers
for product development, laboratory
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
NOPR Estimated
Test Cost for the
Proposed Test
Procedure in
Appendix Al
$11,200- $12,200
$12,700- $13,700
(plus $2,000 - $4,000
per optional heating
test)
$13,200- $14,200
$14,700- $15,700
(plus $2,000 - $4,000
per optional heating
test)
$11,200- $12,200
Final Rule Estimated Test
Cost for Adopted Test
Procedure in Appendix Al
$11,200 - $14,800
$12,700- $16,300 (plus
$2,000 - $4,000 per optional
heating test)
$13,200 - $16,800
$14,700- $18,300 (plus
$2,000- $4,000 per optional
heating test
upgrades, and additional testing.
(Rheem, No. 12 at p. 3)
In response, DOE notes that most
CUAC/HP manufacturers have in-house
testing capabilities and would
principally use those resources for
required testing. DOE expects in-house
testing to be cheaper on a per-test basis
than third-party testing. DOE is
conservatively presenting costs
associated with a scenario where a
manufacturer does not have these inhouse testing resources, or where those
resources are otherwise occupied and
the manufacturer has to rely on thirdparty testing. Apart from the optional
heating tests, DOE has concluded that
the amended test procedures adopted in
this final rule would not require capital
improvements to in-house testing
facilities. (DOE once again notes that the
5 °F test, which some manufacturer’s
test chambers may need upgrades to
conduct, is optional.) Further, the
amended test procedures will not
require manufacturers to undergo any
new product development. Any burden
associated with model redesign to meet
amended energy conservation standards
would be addressed in a separate
standards rulemaking.
As discussed, DOE has concluded that
that the potential adoption of amended
energy conservation standards
denominated in terms of IVEC and IVHE
(and corresponding requirement to use
the adopted test procedure in appendix
A1) would alter the measured energy
PO 00000
Frm 00043
Fmt 4701
Sfmt 4700
$11,200 - $14,800
efficiency of CUACs and CUHPs.
Consequently, manufacturers would not
be able to rely on data generated under
the current test procedure and would,
therefore, be required to re-rate CUAC
and CUHP models. In accordance with
10 CFR 429.70, however, CUAC and
CUHP manufacturers may elect to use
AEDMs to rate models, which
significantly reduces costs to industry.
DOE has updated its estimate of AEDM
creation costs to reflect both the
previously mentioned modest increase
in labor time associated with testing of
large units and the cost range of
physical testing broadly. In this final
rule, DOE estimates the total cost to
develop and validate an AEDM for
determining IVEC (and IVHE as
applicable) for CUACs and CUHPs
(including double-duct systems) to be
between $26,400 and $40,600 per
AEDM.34 Once the AEDM is developed,
DOE estimates that it will take one hour
of an engineer’s time (calculated based
upon a fully burdened engineering
technician wage of $41.52 per hour) to
34 DOE estimates that a technician would need 80
hours to develop an AEDM and 16 hours to validate
an AEDM based on testing, and that the tests of two
basic models would be required per AEDM. At a
fully burdened labor rate of $41.52 per hour, the
cost to develop and validate an AEDM would be
approximately $4,000 and the cost to carry out the
testing would be between $11,200 and $18,300 for
each basic model, depending on the equipment
category of models tested. Therefore, DOE estimates
that total AEDM creation costs would be between
$26,400 and $40,600.
E:\FR\FM\20MYR2.SGM
20MYR2
ER20MY24.133
lotter on DSK11XQN23PROD with RULES2
Table 111-6 Test Cost Estimates for the Test Procedure in Appendix Al
44028
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
determine efficiency for each basic
model using the AEDM.
In accordance with 10 CFR 429.70,
manufacturers rating their CUAC and
CUHP models with AEDMs must
validate an AEDM with testing of a
minimum of two basic models per
validation class (see 10 CFR
429.70(c)(2)(iv)). DOE acknowledges
that manufacturers may choose to test
more models than the minimum
required by DOE, but DOE has estimated
burden associated with what would be
required by its amended regulations, not
including additional testing
manufacturers might choose to
undertake at their discretion.
Accordingly, in this final rule, DOE
maintains a cost estimate for AEDM
development based on testing test two
basic models for each AEDM.
lotter on DSK11XQN23PROD with RULES2
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Orders
12866, 13563, and 14094
Executive Order (‘‘E.O.’’) 12866,
‘‘Regulatory Planning and Review,’’ 58
FR 51735 (Oct. 4, 1993), as
supplemented and reaffirmed by E.O.
13563, ‘‘Improving Regulation and
Regulatory Review,’’ 76 FR 3821 (Jan.
21, 2011), and E.O. 14094,
‘‘Modernizing Regulatory Review,’’ 88
FR 21879 (April 11, 2023), requires
agencies, to the extent permitted by law,
to: (1) propose or adopt a regulation
only upon a reasoned determination
that its benefits justify its costs
(recognizing that some benefits and
costs are difficult to quantify); (2) tailor
regulations to impose the least burden
on society, consistent with obtaining
regulatory objectives, taking into
account, among other things, and to the
extent practicable, the costs of
cumulative regulations; (3) select, in
choosing among alternative regulatory
approaches, those approaches that
maximize net benefits (including
potential economic, environmental,
public health and safety, and other
advantages; distributive impacts; and
equity); (4) to the extent feasible, specify
performance objectives, rather than
specifying the behavior or manner of
compliance that regulated entities must
adopt; and (5) identify and assess
available alternatives to direct
regulation, including providing
economic incentives to encourage the
desired behavior, such as user fees or
marketable permits, or providing
information upon which choices can be
made by the public. DOE emphasizes as
well that E.O. 13563 requires agencies to
use the best available techniques to
quantify anticipated present and future
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
benefits and costs as accurately as
possible. In its guidance, the Office of
Information and Regulatory Affairs
(‘‘OIRA’’) in the Office of Management
and Budget (‘‘OMB’’) has emphasized
that such techniques may include
identifying changing future compliance
costs that might result from
technological innovation or anticipated
behavioral changes. For the reasons
stated in the preamble, this final
regulatory action is consistent with
these principles.
Section 6(a) of E.O. 12866 also
requires agencies to submit ‘‘significant
regulatory actions’’ to OIRA for review.
OIRA has determined that this final
regulatory action does not constitute a
‘‘significant regulatory action’’ under
section 3(f) of E.O. 12866, as amended
by E.O. 14094. Accordingly, this action
was not submitted to OIRA for review
under E.O. 12866.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis (‘‘IRFA’’) and a final regulatory
flexibility analysis (‘‘FRFA’’) for any
rule where the agency was first required
by law to publish a proposed rule for
public comment, unless the agency
certifies that the rule, if promulgated,
will not have a significant economic
impact on a substantial number of small
entities. As required by Executive Order
13272, ‘‘Proper Consideration of Small
Entities in Agency Rulemaking,’’ 67 FR
53461 (August 16, 2002), DOE
published procedures and policies in
the Federal Register on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s website: www.energy.gov/gc/
office-general-counsel. DOE reviewed
this final rule under the provisions of
the Regulatory Flexibility Act and the
procedures and policies published on
February 19, 2003.
The following sections explain DOE’s
determination that this final rule does
not have a ‘‘significant economic impact
on a substantial number of small
entities,’’ and that the preparation of a
FRFA is not warranted.
1. Estimate of Small Entities Regulated
For manufacturers of CUACs and
CUHPs, the Small Business
Administration (‘‘SBA’’) has set a size
threshold, which defines those entities
classified as ‘‘small businesses’’ for the
purposes of the statute. DOE used the
PO 00000
Frm 00044
Fmt 4701
Sfmt 4700
SBA’s small business size standards to
determine whether any small entities
would be subject to the requirements of
the rule. See 13 CFR part 121. The
equipment covered by this rule is
classified under North American
Industry Classification System
(‘‘NAICS’’) code 333415,35 ‘‘AirConditioning and Warm Air Heating
Equipment and Commercial and
Industrial Refrigeration Equipment
Manufacturing.’’ In 13 CFR 121.201, the
SBA sets a threshold of 1,250 employees
or fewer for an entity to be considered
as a small business for this category.
DOE reviewed the test procedures
adopted in this final rule under the
provisions of the Regulatory Flexibility
Act and the procedures and policies
published on February 19, 2003. DOE
utilized DOE’s Compliance Certification
Database (‘‘CCD’’) 36 and manufacturer
websites to identify potential small
businesses that manufacture CUACs and
CUHPs covered by this rulemaking.
DOE identified 13 companies that are
original equipment manufacturers
(‘‘OEMs’’) of CUACs and CUHPs
covered by this rulemaking. Next, DOE
screened out companies that do not
meet the definition of a ‘‘small
business’’ or are foreign-owned and
operated. Ultimately, for this final rule
DOE identified two small, domestic
OEMs for consideration. DOE’s
assessment indicates that of these two
OEMs, one is an AHRI member, and one
is not an AHRI member and does not
certify their equipment in the AHRI
Directory. DOE used subscription-based
business information tools (e.g., reports
from Dun & Bradstreet) 37 to determine
headcount and revenue of each small
business.
2. Description and Estimate of
Compliance Requirements
In this final rule, DOE is revising the
existing test procedure for CUACs and
CUHPs (consolidating for ACUACs and
ACUHPs, ECUACs, and WCUACs) at
appendix A of subpart F of part 431
(appendix A) by adopting sections of
AHRI 340/360–2022. DOE is also
amending the test procedure for CUACs
and CUHPs by adopting a new appendix
A1 to subpart F of part 431 (‘‘appendix
A1’’) that references the industry test
35 The size standards are listed by NAICS code
and industry description and are available at
www.sba.gov/document/support--table-sizestandards (last accessed April 4, 2023).
36 Certified equipment in the CCD is listed by
equipment class and can be accessed at
www.regulations.doe.gov/certification-data/
#q=Product_Group_s%3A* (last accessed Dec. 16,
2023).
37 Market research is available through the Dun &
Bradstreet Hoovers login page at:
app.dnbhoovers.com (last accessed April 3, 2023).
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
standard AHRI 1340–2023.
Additionally, this final rule amends the
representation and enforcement
provisions for CUACs and CUHPs in 10
CFR part 429 and certain definitions for
CUACs and CUHPs in 10 CFR part 431.
Specific cost and compliance associated
with each appendix are discussed in the
subsections that follow.
a. Cost and Compliance Associated With
Appendix A
In appendix A, DOE has amended the
existing test procedure for CUACs and
CUHPs (relocated to appendix A for
ECUACs and WCUACs, for which the
current test procedure is located at 10
CFR 431.96) by incorporating by
reference an updated version of the
applicable industry test method, AHRI
340/360–2022, which includes the
energy efficiency metrics IEER (required
metric for ACUACs and ACUHPs), EER
(required metric for ECUACs, WCUACs,
and double-duct systems), and COP
(required metric for ACUHPs and
double-duct heat pumps) and
maintaining an existing reference to
industry test method ANSI/ASHRAE
37–2009. The adopted test procedure at
appendix A does not change efficiency
ratings as compared to the current
Federal test procedure, and, therefore,
will not require retesting nor increase
third-party laboratory testing costs per
unit solely as a result of DOE’s adoption
of this amendment to the test procedure.
DOE estimates the current costs of
physical testing to the current required
metrics to be: $10,500 for ACUACs;
$12,000 for ACUHPs; $6,800 for doubleduct air conditioners; $8,300 for doubleduct heat pumps; and $6,800 for
ECUACs and WCUACs. In accordance
with 10 CFR 429.70, CUAC and CUHP
manufacturers may elect to use AEDMs
to rate models, an approach which can
significantly reduce costs to industry.
44029
b. Cost and Compliance Associated
With Appendix A1
In appendix A1, DOE is adopting the
test conditions and procedures in AHRI
1340–2023 and ANSI/ASHRAE 37–
2009. The test procedure in appendix
A1 includes provisions for measuring
CUAC and CUHP energy efficiency
using the IVEC and IVHE metrics so as
to be consistent with the updated
industry test procedure. Should DOE
adopt amended energy conservation
standards in the future denominated in
terms of IVEC and IVHE, the
Department expects there would be an
increase in third-party laboratory testing
cost relative to the current Federal test
procedure, as outlined in further detail
in section III.K.2 of this document.
Table IV–1 shows DOE’s estimates for
testing to the current Federal test
procedure, the initial cost estimate
associated with the NOPR, and this final
rule’s cost estimate for the adopted test
procedure in appendix A1.
Table IV-1 Test Cost Estimates for the Test Procedure in Appendix Al
Test Cost for
Current
Federal Test
Procedure
$10,500
$12,000
lotter on DSK11XQN23PROD with RULES2
ACUACs
ACUHPs
Double-duct
air
conditioners
Double-duct
heat pumps
$6,800
ECUACs and
WCUACs
$6,800
$8,300
If CUAC and CUHP manufacturers
conduct physical testing to certify a
basic model, two units are required to
be tested per basic model. However,
manufacturers are not required to
perform laboratory testing on all basic
models, as manufacturers may elect to
use AEDMs, in accordance with 10 CFR
429.70. An AEDM is a computer
modeling or mathematical tool that
predicts the performance of non-tested
basic models. These computer modeling
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
NOPR Estimated Test
Cost for the Proposed
Test Procedure in
AooendixAl
$11,200 - $12,200
$12,700 - $13,700
(plus $2,000 - $4,000
per optional heating
test)
$13,200 - $14,200
Final Rule Estimated
Test Cost for the Adopted
Test Procedure in
Appendix Al
$11,200- $14,800
$12,700- $16,300 (plus
$2,000 - $4,000 per
optional heating test)
$14,700 - $15,700
(plus $2,000 - $4,000
per optional heating
test)
$11,200 - $12,200
$14,700 - $16,800 (plus
$2,000- $4,000 per
optional heating test
and mathematical tools, when properly
developed, can provide a means to
predict the energy usage or efficiency
characteristics of a basic model of a
given covered product or equipment
and reduce the burden and cost
associated with testing.
Small businesses would be expected
to have different potential regulatory
costs depending on whether they are a
member of AHRI. DOE understands that
all AHRI members and all
PO 00000
Frm 00045
Fmt 4701
Sfmt 4700
$13,200- $16,300
$11,200- $14,800
manufacturers currently certifying to the
AHRI Directory will be testing their
CUAC and CUHP models in accordance
with AHRI 1340–2023, the industry test
procedure DOE is adopting, and using
AHRI’s certification program.
The adopted test procedure
amendments will not add any
additional testing burden to
manufacturers which are members of
AHRI. As discussed, DOE identified one
small, domestic OEM that is an AHRI
E:\FR\FM\20MYR2.SGM
20MYR2
ER20MY24.134
Equipment
Type
44030
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
member. Therefore, DOE has concluded
that the adopted test procedure
amendments will not add additional
testing burden to one of the two
identified small, domestic OEMs, as that
AHRI member company will soon be
using AHRI 1340–2023. DOE estimated
the potential impacts for the one
identified small, domestic OEM that is
not an AHRI member and does not
certify their equipment in the AHRI
Directory. This small business would
only incur additional costs if the
company would not otherwise be using
the AHRI 1340–2023 test procedure to
rate their models of CUACs and CUHPs.
DOE estimates that this non-AHRI
member company manufactures 14
basic models of ECUACs and WCUACs.
To develop cost estimates for this small
business, DOE considered the cost to
develop an AEDM, the costs to validate
the AEDM through physical testing, and
the cost per model to determine ratings
using the AEDM. DOE anticipates that
this small OEM would avail itself of the
cost-saving option which the AEDM
provides. DOE estimated the cost to
develop an AEDM for ECUACs or
WCUACs to be $33,600 per AEDM,
which includes the required physical
testing of two basic models per
validation class. Because ECUACs and
WCUACs are separate validation classes
(per 10 CFR 429.70), the manufacturer
would require two AEDMs—one for
ECUACs and one for WCUACs, for a
total AEDM development cost of
$67,200. Additionally, DOE estimated a
cost of $41.52 per basic model for
determining energy efficiency using the
validated AEDM. The estimated cost to
rate the 14 basic models with the AEDM
would be approximately $600.
Therefore, total testing and rating
costs expected for this small business,
when and if DOE adopts amended
energy conservation standards for
ECUACs and WCUACs denominated in
terms of the IVEC metric, would be
approximately $67,800 for the two
AEDMs along with the rating costs for
14 basic models. Market research tools
report that company’s annual revenue to
be approximately $50.6 million.
Accordingly, testing and AEDM costs to
rate in accordance with appendix A1
could cause this small business
manufacturer to incur costs significantly
less than one percent of annual revenue
for that small manufacturer.
3. Significant Alternatives to the Rule
DOE considered alternative test
methods and modifications to the
adopted test procedures in appendices
A and A1 for CUACs and CUHPs,
referencing AHRI 340/360–2022 and
AHRI 1340–2023, respectively.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
However, DOE has determined that
there are no better alternatives than the
adopted test procedures, in terms of
both meeting the agency’s objectives
and reducing burden on manufacturers.
Therefore, DOE is amending the existing
DOE test procedure for CUACs and
CUHPs through incorporation by
reference of AHRI 340/360–2022 in
appendix A, and incorporation by
reference of AHRI 1340–2023 in
appendix A1.
As discussed previously,
manufacturers, including small
businesses, will have the option to
implement AEDMs to certify their basic
models—which will likely be more costeffective than testing each basic model.
This option is explained in further
detail in section III.K.2 of this
document.
In addition, individual manufacturers
may petition for a waiver of the
applicable test procedure. (See 10 CFR
431.401) Also, section 504 of the
Department of Energy Organization Act,
42 U.S.C. 7194, provides authority for
the Secretary to adjust a rule issued
under EPCA in order to prevent ‘‘special
hardship, inequity, or unfair
distribution of burdens’’ that may be
imposed on that manufacturer as a
result of such rule. Manufacturers
should refer to 10 CFR part 1003 for
additional details.
4. Certification Statement
DOE identified 13 OEMs affected by
this final rule, two of which would be
considered small businesses. Of these
two small businesses, one is a member
of AHRI, and DOE has determined that
the AHRI member company will already
be testing to the updated industry test
standard (i.e., AHRI 1340–2023) in order
to certify in the AHRI Directory.
Consequently, DOE does not anticipate
its amended test procedure will add to
the testing burden for this AHRI
member small business. Finally, DOE
has determined that testing costs and
burden will not increase substantially
for the non-AHRI-member small
business either. As discussed
previously, the amendments to
appendix A will result in zero costs to
that small manufacturer. Further, the
new appendix A1 will have no cost
impact until and if amended energy
conservation standards denominated in
terms of the new metrics IVEC and IVHE
are adopted. DOE has determined that if
energy conservation standards are
amended, the potential cost associated
with this final rule is significantly less
than one percent of revenue for the one
non-AHRI-member small business.
Thus, DOE concludes that this
PO 00000
Frm 00046
Fmt 4701
Sfmt 4700
rulemaking does not significantly affect
a substantial number of small entities.
Based on the limited number of small
entities affected and the de minimis cost
impacts, DOE certifies that this final
rule does not have a ‘‘significant
economic impact on a substantial
number of small entities,’’ and
accordingly, the Department has
determined that the preparation of a
FRFA is not warranted. DOE will
transmit a certification and supporting
statement of factual basis to the Chief
Counsel for Advocacy of the Small
Business Administration for review
under 5 U.S.C. 605(b).
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of CUACs and CUHPs
must certify to DOE that their
equipment complies with any
applicable energy conservation
standards. To certify compliance,
manufacturers must first obtain test data
for their equipment according to the
DOE test procedures, including any
amendments adopted for those test
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including
CUACs and CUHPs. (See generally 10
CFR part 429.) The collection-ofinformation requirement for the
certification and recordkeeping is
subject to review and approval by OMB
under the Paperwork Reduction Act
(PRA). This requirement has been
approved by OMB under OMB control
number 1910–1400. Public reporting
burden for the certification is estimated
to average 35 hours per response,
including the time for reviewing
instructions, searching existing data
sources, gathering and maintaining the
data needed, and completing and
reviewing the collection of information.
DOE is not amending the certification
or reporting requirements for CUACs
and CUHPs in this final rule. Instead,
DOE may consider proposals to amend
the certification requirements and
reporting for CUACs and CUHPs under
a separate rulemaking regarding
appliance and equipment certification.
DOE will address changes to OMB
Control Number 1910–1400 at that time,
as necessary.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE adopts test
procedure amendments that it expects
will be used to develop and implement
future energy conservation standards for
CUACs and CUHPs. DOE has
determined that this rule falls into a
class of actions that are categorically
excluded from review under the
National Environmental Policy Act of
1969 (42 U.S.C. 4321 et seq.) and DOE’s
implementing regulations at 10 CFR part
1021. Specifically, DOE has determined
that adopting test procedures for
measuring energy efficiency of
consumer products and industrial
equipment is consistent with activities
identified in 10 CFR part 1021, subpart
D, appendix A, sections A5 and A6.
Accordingly, neither an environmental
assessment nor an environmental
impact statement is required.
lotter on DSK11XQN23PROD with RULES2
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive order also requires agencies to
have an accountable process to ensure
meaningful and timely input by State
and local officials in the development of
regulatory policies that have federalism
implications. On March 14, 2000, DOE
published a statement of policy
describing the intergovernmental
consultation process it will follow in the
development of such regulations. 65 FR
13735. DOE examined this final rule
and determined that it will not have a
substantial direct effect on the States, on
the relationship between the national
government and the States, or on the
distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
final rule. States can petition DOE for
exemption from such preemption to the
extent, and based on criteria, set forth in
EPCA. (42 U.S.C. 6297(d)) No further
action is required by Executive Order
13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Regarding the
review required by section 3(a), section
3(b) of Executive Order 12988
specifically requires that Executive
agencies make every reasonable effort to
ensure that the regulation: (1) clearly
specifies the preemptive effect, if any;
(2) clearly specifies any effect on
existing Federal law or regulation; (3)
provides a clear legal standard for
affected conduct while promoting
simplification and burden reduction; (4)
specifies the retroactive effect, if any; (5)
adequately defines key terms; and (6)
addresses other important issues
affecting clarity and general
draftsmanship under any guidelines
issued by the Attorney General. Section
3(c) of Executive Order 12988 sections
3(a) and 3(b) to determine whether they
are met or it is unreasonable to meet one
or more of them. DOE has completed the
required review and determined that, to
the extent permitted by law, this final
rule meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (‘‘UMRA’’) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action likely to result in a
rule that may cause the expenditure by
State, local, and Tribal governments, in
the aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect them. On
PO 00000
Frm 00047
Fmt 4701
Sfmt 4700
44031
March 18, 1997, DOE published a
statement of policy on its process for
intergovernmental consultation under
UMRA. 62 FR 12820. DOE’s policy
statement is also available at
www.energy.gov/sites/prod/files/gcprod/
documents/umra_97.pdf. DOE
examined this final rule according to
UMRA and its statement of policy and
determined that the rule contains
neither an intergovernmental mandate,
nor a mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
final rule will not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). Pursuant to OMB
Memorandum M–19–15, Improving
Implementation of the Information
Quality Act (April 24, 2019), DOE
published updated guidelines which are
available at: www.energy.gov/sites/prod/
files/2019/12/f70/DOE%20Final%20
Updated%20IQA%20Guidelines%20
Dec%202019.pdf. DOE has reviewed
this final rule under the OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
E:\FR\FM\20MYR2.SGM
20MYR2
44032
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OIRA at OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgates or is
expected to lead to promulgation of a
final rule, and that: (1) is a significant
regulatory action under Executive Order
12866, or any successor order, and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy, or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use if the
regulation is implemented, and of
reasonable alternatives to the action and
their expected benefits on energy
supply, distribution, and use.
This regulatory action to amend the
test procedure for measuring the energy
efficiency of CUACs and CUHPs is not
a significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
lotter on DSK11XQN23PROD with RULES2
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; ‘‘FEAA’’) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (‘‘FTC’’)
concerning the impact of the
commercial or industry standards on
competition.
The modifications to the test
procedure for CUACs and CUHPs
adopted in this final rule incorporate
testing methods contained in certain
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
sections of the following commercial
standards: AHRI 340/360–2022, AHRI
1340–2023, and ANSI/ASHRAE 37–
2009. DOE has evaluated these
standards and is unable to conclude
whether they fully comply with the
requirements of section 32(b) of the
FEAA (i.e., whether they were
developed in a manner that fully
provides for public participation,
comment, and review). DOE has
consulted with both the Attorney
General and the Chairman of the FTC
about the impact on competition of
using the methods contained in these
standards and has received no
comments objecting to their use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that the Office of
Information and Regulatory Affairs has
determined that this action is not a
‘‘major rule’’ under the criteria set forth
in 5 U.S.C. 804(2).
N. Description of Materials Incorporated
by Reference
In this final rule, DOE is incorporating
by reference the following test
standards:
AHRI 340/360–2022 is an industryaccepted test procedure for measuring
the performance of air-cooled,
evaporatively-cooled, and water-cooled
unitary air-conditioning and heat pump
equipment. AHRI 340/360–2022 is
available from AHRI at www.ahrinet.
org/standards/search-standards.
AHRI 1340–2023 is the most recent
industry-accepted test procedure for
measuring the performance of aircooled, evaporatively-cooled, and watercooled unitary air-conditioning and heat
pump equipment. AHRI 1340–2023 is
available from AHRI at www.ahrinet.
org/standards/search-standards.
ANSI/ASHRAE 37–2009 is an
industry-accepted test procedure for
measuring the performance of
electrically driven unitary airconditioning and heat pump equipment.
ANSI/ASHRAE 37–2009 is available
from ASHRAE on ANSI’s website at:
https://webstore.ansi.org/standards/
ashrae/ansiashraestandard372009.
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
PO 00000
Frm 00048
Fmt 4701
Sfmt 4700
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Reporting
and recordkeeping requirements, Small
businesses.
10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation test
procedures, Incorporation by reference,
Reporting and recordkeeping
requirements.
Signing Authority
This document of the Department of
Energy was signed on April 12, 2024, by
Jeffrey Marootian, Principal Deputy
Assistant Secretary for Energy Efficiency
and Renewable Energy, pursuant to
delegated authority from the Secretary
of Energy. That document with the
original signature and date is
maintained by DOE. For administrative
purposes only, and in compliance with
requirements of the Office of the Federal
Register, the undersigned DOE Federal
Register Liaison Officer has been
authorized to sign and submit the
document in electronic format for
publication, as an official document of
the Department of Energy. This
administrative process in no way alters
the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on April 17,
2024.
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
For the reasons stated in the
preamble, DOE amends parts 429 and
431 of chapter II of title 10, Code of
Federal Regulations as set forth below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
2. Amend § 429.4 by:
a. Removing paragraph (c)(2);
b. Redesignating paragraphs (c)(3)
through (5) as paragraphs (c)(2) through
(4); and
■ c. Adding new paragraph (c)(5).
The addition reads as follows:
■
■
■
§ 429.4 Materials incorporated by
reference.
*
*
*
*
*
(c) * * *
(5) AHRI Standard 1340–2023 (I–P)
(‘‘AHRI 1340–2023’’), 2023 Standard for
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
Performance Rating of Commercial and
Industrial Unitary Air-conditioning and
Heat Pump Equipment, approved
November 16, 2023; IBR approved for
§§ 429.43; 429.134.
*
*
*
*
*
■ 3. Amend § 429.43 by:
■ a. Removing paragraph (a)(1)(iv);
■ b. Removing and reserving paragraph
(a)(2)(ii); and
■ c. Adding paragraph (a)(3)(vi).
The addition reads as follows:
§ 429.43 Commercial heating, ventilating,
air conditioning (HVAC) equipment
(excluding air-cooled, three-phase, small
commercial package air conditioning and
heating equipment with a cooling capacity
of less than 65,000 British thermal units per
hour and air-cooled, three-phase, variable
refrigerant flow multi-split air conditioners
and heat pumps with less than 65,000
British thermal units per hour cooling
capacity).
(a) * * *
(3) * * *
(vi) Commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/
h). Before May 15, 2025, the provisions
in 10 CFR 429.43, revised as of January
1, 2024, are applicable. On and after
May 15, 2025, when certifying to energy
conservation standards in terms of EER
or IEER and (as applicable) COP, the
provisions in paragraph (a)(3)(vi)(B) of
this section apply. When certifying to
energy conservation standards in terms
of IVEC and (as applicable) IVHE, all
provisions in this paragraph (a)(3)(vi)
apply.
(A) For individual model selection
when certifying to energy conservation
standards in terms of IVEC and (as
applicable) IVHE:
(1) Representations for a basic model
must be based on the least-efficient
individual model(s) distributed in
commerce among all otherwise
comparable model groups comprising
the basic model, with selection of the
least-efficient individual model
considering all options for factoryinstalled components and manufacturersupplied components for field
installation, except as provided in
paragraph (a)(3)(vi)(A)(2) of this section
for individual models that include
components listed in table 7 to
paragraph (a)(3)(vi)(A) of this section.
For the purpose of this paragraph
(a)(3)(vi)(A)(1), ‘‘otherwise comparable
model group’’ means a group of
individual models distributed in
commerce within the basic model that
44033
do not differ in components that affect
energy consumption as measured
according to the applicable test
procedure specified at 10 CFR 431.96
other than those listed in table 7 to
paragraph (a)(3)(vi)(A) of this section.
An otherwise comparable model group
may include individual models
distributed in commerce with any
combination of the components listed in
table 7 (or none of the components
listed in table 7). An otherwise
comparable model group may consist of
only one individual model.
(2) For a basic model that includes
individual models distributed in
commerce with components listed in
table 7 to paragraph (a)(3)(vi)(A) of this
section, the requirements for
determining representations apply only
to the individual model(s) of a specific
otherwise comparable model group
distributed in commerce with the least
number (which could be zero) of
components listed in table 7 to
paragraph (a)(3)(vi)(A) included in
individual models of the group. Testing
under this paragraph (a)(3)(vi)(A)(2)
shall be consistent with any componentspecific test provisions specified in
section 6 of appendix A1 to subpart F
of 10 CFR part 431.
TABLE 7 TO PARAGRAPH (a)(3)(vi)(A)—SPECIFIC COMPONENTS FOR COMMERCIAL PACKAGE AIR CONDITIONING AND
HEATING EQUIPMENT
[Excluding air-cooled equipment with a cooling capacity of less than 65,000 Btu/h]
Component
Description
Air Economizers ......................................
An automatic system that enables a cooling system to supply outdoor air to reduce or eliminate the
need for mechanical cooling during mild or cold weather.
An assembly that reduces the moisture content of the supply air through moisture transfer with solid
or liquid desiccants.
Water is evaporated into the air entering the air-cooled condenser to lower the dry-bulb temperature
and thereby increase efficiency of the refrigeration cycle.
A damper assembly including means to open and close the damper mounted at the supply or return
duct opening of the equipment.
Water is used indirectly or directly to cool ventilation air. In a direct system, the water is introduced
directly into the ventilation air, and in an indirect system, the water is evaporated in secondary air
stream, and the heat is removed through a heat exchanger.
A higher-static condenser fan/motor assembly designed for external ducting of condenser air that provides greater pressure rise and has a higher rated motor horsepower than the condenser fan provided as a standard component with the equipment.
The standard indoor fan motor is the motor specified in the manufacturer’s installation instructions for
testing and shall be distributed in commerce as part of a particular model. A non-standard motor is
an indoor fan motor that is not the standard indoor fan motor and that is distributed in commerce
as part of an individual model within the same basic model.
For a non-standard high-static indoor fan motor(s) to be considered a specific component for a basic
model (and thus subject to the provisions of paragraph (a)(3)(vi)(A)(2) of this section), the following
provisions must be met:
(1) Non-standard high-static indoor fan motor(s) must meet the minimum allowable efficiency determined per section D.3.1 of AHRI 1340–2023 (incorporated by reference, see § 429.4) for
non-standard high-static indoor fan motors or per section D.3.2 of AHRI 1340–2023 for nonstandard high-static indoor integrated fan and motor combinations.
(2) If the standard indoor fan motor can vary fan speed through control system adjustment of
motor speed, all non-standard high-static indoor fan motors must also allow speed control (including with the use of variable-frequency drive).
A powered exhaust fan is a fan that transfers directly to the outside a portion of the building air that is
returning to the unit, rather than allowing it to recirculate to the indoor coil and back to the building.
A powered return fan is a fan that draws building air into the equipment.
Desiccant Dehumidification Components
Evaporative Pre-cooling of Air-cooled
Condenser Intake Air.
Fire/Smoke/Isolation Dampers ................
Indirect/Direct Evaporative Cooling of
Ventilation Air.
lotter on DSK11XQN23PROD with RULES2
Non-Standard Ducted Condenser Fans
(not applicable to Double-duct Systems).
Non-Standard High-Static Indoor Fan
Motors.
Powered Exhaust/Powered Return Air
Fans.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00049
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
44034
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 7 TO PARAGRAPH (a)(3)(vi)(A)—SPECIFIC COMPONENTS FOR COMMERCIAL PACKAGE AIR CONDITIONING AND
HEATING EQUIPMENT—Continued
[Excluding air-cooled equipment with a cooling capacity of less than 65,000 Btu/h]
Component
Description
Process Heat recovery/Reclaim Coils/
Thermal Storage.
Refrigerant Reheat Coils .........................
A heat exchanger located inside the unit that conditions the equipment’s supply air using energy
transferred from an external source using a vapor, gas, or liquid.
A heat exchanger located downstream of the indoor coil that heats the supply air during cooling operation using high pressure refrigerant in order to increase the ratio of moisture removal to cooling
capacity provided by the equipment.
An assembly of structures through which the supply air passes before leaving the equipment or
through which the return air from the building passes immediately after entering the equipment for
which the sound insertion loss is at least 6 dB for the 125 Hz octave band frequency range.
Coils used to provide supplemental heating.
An assembly that preconditions outdoor air entering the equipment through direct or indirect thermal
and/or moisture exchange with the exhaust air, which is defined as the building air being exhausted
to the outside from the equipment.
Sound Traps/Sound Attenuators .............
Steam/Hydronic Heat Coils .....................
Ventilation Energy Recovery System
(VERS).
(B) The represented value of total
cooling capacity must be between 95
percent and 100 percent of the mean of
the total cooling capacities measured for
the units in the sample selected as
described in paragraph (a)(1)(ii) of this
section, or between 95 percent and 100
percent of the total cooling capacity
output simulated by the AEDM as
described in paragraph (a)(2) of this
section.
(C) Representations of IVEC and IVHE
(including IVHEc, as applicable) must be
determined using a minimum part-load
airflow that is no lower than the highest
of the following:
(1) The minimum part-load airflow
obtained using the as-shipped system
control settings;
(2) The minimum part-load airflow
obtained using the default system
control settings specified in the
manufacturer installation instructions
(as applicable); and
(3) The minimum airflow rate
specified in section 5.18.2 of AHRI
1340–2023.
*
*
*
*
*
4. Amend § 429.70 by revising table 2
to paragraph (c)(5)(vi)(B) to read as
follows:
■
§ 429.70 Alternative methods for
determining energy efficiency and energy
use.
*
*
*
(c) * * *
(5) * * *
(vi) * * *
(B) * * *
*
*
TABLE 2 TO PARAGRAPH (c)(5)(vi)(B)
Equipment
Applicable
tolerance
Metric
lotter on DSK11XQN23PROD with RULES2
Commercial Packaged Boilers ....................................................
Combustion Efficiency ...............................................................
Thermal Efficiency .....................................................................
Commercial Water Heaters or Hot Water Supply Boilers .......... Thermal Efficiency .....................................................................
Standby Loss .............................................................................
Unfired Storage Tanks ................................................................ R-Value ......................................................................................
Air-Cooled, Split and Packaged ACs and HPs Greater Than or Energy Efficiency Ratio ..............................................................
Equal to 65,000 Btu/h Cooling Capacity and Less than
Energy Efficiency Ratio 2 ..........................................................
760,000 Btu/h Cooling Capacity.
Coefficient of Performance ........................................................
Coefficient of Performance 2 .....................................................
Integrated Energy Efficiency Ratio ............................................
Integrated Ventilation, Economizing, and Cooling .....................
Integrated Ventilation and Heating Efficiency ............................
Water-Cooled, Split and Packaged ACs, All Cooling Capacities Energy Efficiency Ratio ..............................................................
Energy Efficiency Ratio 2 ..........................................................
Integrated Energy Efficiency Ratio ............................................
Integrated Ventilation, Economizing, and Cooling .....................
Evaporatively-Cooled, Split and Packaged ACs, All Capacities
Energy Efficiency Ratio ..............................................................
Energy Efficiency Ratio 2 ..........................................................
Integrated Energy Efficiency Ratio ............................................
Integrated Ventilation, Economizing, and Cooling .....................
Water-Source HPs, All Capacities .............................................. Energy Efficiency Ratio ..............................................................
Coefficient of Performance ........................................................
Integrated Energy Efficiency Ratio ............................................
Single Package Vertical ACs and HPs ....................................... Energy Efficiency Ratio ..............................................................
Coefficient of Performance ........................................................
Packaged Terminal ACs and HPs .............................................. Energy Efficiency Ratio ..............................................................
Coefficient of Performance ........................................................
Variable Refrigerant Flow ACs and HPs (Excluding Air-Cooled, Energy Efficiency Ratio ..............................................................
Three-phase with Less Than 65,000 Btu/h Cooling Capacity). Coefficient of Performance ........................................................
Integrated Energy Efficiency Ratio ............................................
Computer Room Air Conditioners ............................................... Sensible Coefficient of Performance .........................................
Direct Expansion- Dedicated Outdoor Air Systems ................... Integrated Seasonal Coefficient of Performance 2 ...................
Integrated Seasonal Moisture Removal Efficiency 2 .................
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00050
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
5% (0.05)
5% (0.05)
5% (0.05)
10% (0.1)
10% (0.1)
5% (0.05)
5% (0.05)
5% (0.05)
5% (0.05)
10% (0.1)
10% (0.1)
10% (0.1)
5% (0.05)
5% (0.05)
10% (0.1)
10% (0.1)
5% (0.05)
5% (0.05)
10% (0.1)
10% (0.1)
5% (0.05)
5% (0.05)
10% (0.1)
5% (0.05)
5% (0.05)
5% (0.05)
5% (0.05)
5% (0.05)
5% (0.05)
10% (0.1)
5% (0.05)
10% (0.1)
10% (0.1)
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
44035
TABLE 2 TO PARAGRAPH (c)(5)(vi)(B)—Continued
Metric
Commercial Warm-Air Furnaces ................................................
Commercial Refrigeration Equipment .........................................
Thermal Efficiency .....................................................................
Daily Energy Consumption ........................................................
*
*
*
*
*
■
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
§ 429.134 Product-specific enforcement
provisions.
■
5. Amend § 429.134 by revising
paragraph (g) to read as follows:
*
lotter on DSK11XQN23PROD with RULES2
Applicable
tolerance
Equipment
*
*
*
*
(g) Commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/
h). Before May 15, 2025, the provisions
in 10 CFR 429.134, revised as of January
1, 2024, are applicable. On and after
May 15, 2025, the following provisions
apply.
(1) Verification of cooling capacity.
The cooling capacity of each tested unit
of the basic model will be measured
pursuant to the test requirements of
appendix A or appendix A1 to subpart
F of part 431. The mean of the cooling
capacity measurement(s) will be used to
determine the applicable standards for
purposes of compliance.
(2) Specific components. For
assessment and enforcement testing of
models subject to energy conservation
standards denominated in terms of IVEC
and IVHE, if a basic model includes
individual models with components
listed at table 7 to § 429.43(a)(3)(vi)(A)
and DOE is not able to obtain an
individual model with the least number
(which could be zero) of those
components within an otherwise
comparable model group (as defined in
§ 429.43(a)(3)(vi)(A)(1)), DOE may test
any individual model within the
otherwise comparable model group.
(3) Verification of cut-out and cut-in
temperatures. For assessment and
enforcement testing of models of
commercial package air conditioning
and heating equipment subject to energy
conservation standards denominated in
terms of IVHE, the cut-out and cut-in
temperatures may be verified using the
method in appendix H to AHRI 1340–
2023 (incorporated by reference, see
§ 429.4). If this method is conducted,
the cut-in and cut-out temperatures
determined using this method will be
used to calculate IVHE for purposes of
compliance.
*
*
*
*
*
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
6. The authority citation for part 431
continues to read as follows:
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
7. Amend § 431.92 by:
a. Revising the definitions for ‘‘Basic
model’’ and ‘‘Coefficient of
performance, or COP’’;
■ b. Adding in alphabetical order a
definition for ‘‘Coefficient of
performance 2, or COP2’’;
■ c. Revising the definitions for
‘‘Double-duct air conditioner or heat
pump’’ and ‘‘Energy efficiency ratio, or
EER’’;
■ d. Adding in alphabetical order a
definition for ‘‘Energy efficiency ratio 2,
or EER2’’;
■ e. Revising the definition for
‘‘Integrated energy efficiency ratio, or
IEER’’; and
■ f. Adding in alphabetical order
definitions for ‘‘Integrated ventilation
and heating efficiency, or IVHE’’ and
‘‘Integrated ventilation, economizing,
and cooling, or IVEC’’.
The revisions and additions read as
follows:
■
■
§ 431.92 Definitions concerning
commercial air conditioners and heat
pumps.
*
*
*
*
*
Basic model means:
(1) For air-cooled, three-phase, small
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 Btu/h and
air-cooled, three-phase, variable
refrigerant flow multi-split air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h. All units manufactured by one
manufacturer, having the same primary
energy source, and, which have
essentially identical electrical, physical,
and functional (or hydraulic)
characteristics that affect energy
consumption, energy efficiency, water
consumption, or water efficiency; where
essentially identical electrical, physical,
and functional (or hydraulic)
characteristics means:
(i) For split systems manufactured by
outdoor unit manufacturers (OUMs): all
PO 00000
Frm 00051
Fmt 4701
Sfmt 4700
5% (0.05)
5% (0.05)
individual combinations having the
same model of outdoor unit, which
means comparably performing
compressor(s) [a variation of no more
than five percent in displacement rate
(volume per time) as rated by the
compressor manufacturer, and no more
than five percent in capacity and power
input for the same operating conditions
as rated by the compressor
manufacturer], outdoor coil(s) [no more
than five percent variation in face area
and total fin surface area; same fin
material; same tube material], and
outdoor fan(s) [no more than ten percent
variation in airflow and no more than
twenty percent variation in power
input];
(ii) For split systems having indoor
units manufactured by independent coil
manufacturers (ICMs): all individual
combinations having comparably
performing indoor coil(s) [plus or minus
one square foot face area, plus or minus
one fin per inch fin density, and the
same fin material, tube material, number
of tube rows, tube pattern, and tube
size]; and
(iii) For single-package systems: all
individual models having comparably
performing compressor(s) [no more than
five percent variation in displacement
rate (volume per time) rated by the
compressor manufacturer, and no more
than five percent variations in capacity
and power input rated by the
compressor manufacturer corresponding
to the same compressor rating
conditions], outdoor coil(s) and indoor
coil(s) [no more than five percent
variation in face area and total fin
surface area; same fin material; same
tube material], outdoor fan(s) [no more
than ten percent variation in outdoor
airflow], and indoor blower(s) [no more
than ten percent variation in indoor
airflow, with no more than twenty
percent variation in fan motor power
input];
(iv) Except that:
(A) For single-package systems and
single-split systems, manufacturers may
instead choose to make each individual
model/combination its own basic model
provided the testing and represented
value requirements in 10 CFR 429.67 are
met; and
(B) For multi-split, multi-circuit, and
multi-head mini-split combinations, a
basic model may not include both
E:\FR\FM\20MYR2.SGM
20MYR2
lotter on DSK11XQN23PROD with RULES2
44036
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
individual small-duct, high velocity
(SDHV) combinations and non-SDHV
combinations even when they include
the same model of outdoor unit. The
manufacturer may choose to identify
specific individual combinations as
additional basic models.
(2) For commercial package air
conditioning and heating equipment
(excluding air-cooled, three-phase,
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 Btu/h). All
units manufactured by one
manufacturer within a single equipment
class, having the same or comparably
performing compressor(s), heat
exchangers, and air moving system(s)
that have a common ‘‘nominal’’ cooling
capacity.
(3) For computer room air
conditioners. All units manufactured by
one manufacturer within a single
equipment class, having the same
primary energy source (e.g., electric or
gas), and which have the same or
comparably performing compressor(s),
heat exchangers, and air moving
system(s) that have a common
‘‘nominal’’ cooling capacity.
(4) For direct expansion-dedicated
outdoor air system. All units
manufactured by one manufacturer,
having the same primary energy source
(e.g., electric or gas), within a single
equipment class; with the same or
comparably performing compressor(s),
heat exchangers, ventilation energy
recovery system(s) (if present), and air
moving system(s) that have a common
‘‘nominal’’ moisture removal capacity.
(5) For packaged terminal air
conditioner (PTAC) or packaged
terminal heat pump (PTHP). All units
manufactured by one manufacturer
within a single equipment class, having
the same primary energy source (e.g.,
electric or gas), and which have the
same or comparable compressors, same
or comparable heat exchangers, and
same or comparable air moving systems
that have a cooling capacity within 300
Btu/h of one another.
(6) For single package vertical units.
All units manufactured by one
manufacturer within a single equipment
class, having the same primary energy
source (e.g., electric or gas), and which
have the same or comparably
performing compressor(s), heat
exchangers, and air moving system(s)
that have a rated cooling capacity
within 1500 Btu/h of one another.
(7) For variable refrigerant flow
systems (excluding air-cooled, threephase, variable refrigerant flow air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h). All units manufactured by one
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
manufacturer within a single equipment
class, having the same primary energy
source (e.g., electric or gas), and which
have the same or comparably
performing compressor(s) that have a
common ‘‘nominal’’ cooling capacity
and the same heat rejection medium
(e.g., air or water) (includes VRF water
source heat pumps).
(8) For water-source heat pumps. All
units manufactured by one
manufacturer within a single equipment
class, having the same primary energy
source (e.g., electric or gas), and which
have the same or comparable
compressors, same or comparable heat
exchangers, and same or comparable
‘‘nominal’’ cooling capacity.
*
*
*
*
*
Coefficient of performance, or COP,
means the ratio of the produced cooling
effect of an air conditioner or heat pump
(or its produced heating effect,
depending on the mode of operation) to
its net work input, when both the
cooling (or heating) effect and the net
work input are expressed in identical
units of measurement. For air-cooled
commercial package air conditioning
and heating equipment (excluding
equipment with a cooling capacity less
than 65,000 Btu/h), COP is measured
per appendix A to this subpart.
Coefficient of performance 2, or
COP2, means the ratio of the produced
cooling effect of an air conditioner or
heat pump (or its produced heating
effect, depending on the mode of
operation) to its net work input, when
both the cooling (or heating) effect and
the net work input are expressed in
identical units of measurement. COP2
must be used with a subscript to
indicate the outdoor temperature in
degrees Fahrenheit at which the COP2
was measured (e.g., COP217 for COP2
measured at 17 °F). For air-cooled
commercial package air conditioning
and heating equipment (excluding
equipment with a cooling capacity less
than 65,000 Btu/h), COP2 is measured
per appendix A1 to this subpart.
*
*
*
*
*
Double-duct air conditioner or heat
pump means air-cooled commercial
package air conditioning and heating
equipment that meets the following
criteria—
(1) Is either a horizontal single
package or split-system unit; or a
vertical unit that consists of two
components that may be shipped or
installed either connected or split; or a
vertical single package unit that is not
intended for exterior mounting on,
adjacent interior to, or through an
outside wall;
PO 00000
Frm 00052
Fmt 4701
Sfmt 4700
(2) Is intended for indoor installation
with ducting of outdoor air from the
building exterior to and from the unit
(e.g., the unit and/or all of its
components are non-weatherized);
(3) If it is a horizontal unit, the
complete unit shall have a maximum
height of 35 inches or the unit shall
have components that do not exceed a
maximum height of 35 inches. If it is a
vertical unit, the complete (split,
connected, or assembled) unit shall
have components that do not exceed a
maximum depth of 35 inches; and
(4) Has a rated cooling capacity
greater than or equal to 65,000 Btu/h
and less than 300,000 Btu/h.
*
*
*
*
*
Energy efficiency ratio, or EER, means
the ratio of the produced cooling effect
of an air conditioner or heat pump to its
net work input, expressed in Btu/watthour. For commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
EER is measured per appendix A to this
subpart.
Energy efficiency ratio 2, or EER2,
means the ratio of the produced cooling
effect of an air conditioner or heat pump
to its net work input, expressed in Btu/
watt-hour. For commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
EER2 is measured per appendix A1 to
this subpart.
*
*
*
*
*
Integrated energy efficiency ratio, or
IEER, means a weighted average
calculation of mechanical cooling EERs
determined for four load levels and
corresponding rating conditions,
expressed in Btu/watt-hour. IEER is
measured:
(1) Per appendix A to this subpart for
commercial package air conditioning
and heating equipment (excluding aircooled equipment with a cooling
capacity less than 65,000 Btu/h);
(2) Per appendix C1 to this subpart for
water-source heat pumps;
(3) Per appendix D1 to this subpart for
variable refrigerant flow multi-split air
conditioners and heat pumps (other
than air-cooled with rated cooling
capacity less than 65,000 Btu/h); and
(4) Per appendix G1 to this subpart for
single package vertical air conditioners
and single package vertical heat pumps.
*
*
*
*
*
Integrated ventilation and heating
efficiency, or IVHE, means a sum of the
space heating provided (Btu) divided by
the sum of the energy consumed (Wh),
including mechanical heating,
supplementary electric resistance
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
heating, and heating season ventilation
operating modes. IVHE with subscript C
(IVHEC) refers to the IVHE of heat
pumps using a cold-climate heating load
line. For air-cooled commercial package
air conditioning and heating equipment
(excluding equipment with a cooling
capacity less than 65,000 Btu/h), IVHE
and IVHEC are measured per appendix
A1 to this subpart.
Integrated ventilation, economizing,
and cooling, or IVEC, means a sum of
the space cooling provided (Btu)
divided by the sum of the energy
consumed (Wh), including mechanical
cooling, economizing, and cooling
season ventilation operating modes. For
commercial package air conditioning
and heating equipment (excluding aircooled equipment with a cooling
capacity less than 65,000 Btu/h), IVEC
is measured per appendix A1 to this
subpart.
*
*
*
*
*
8. Amend § 431.95 by:
a. Revising paragraph (b)(4);
b. Redesignating paragraph (b)(11) as
paragraph (b)(12);
■ c. Adding new paragraph (b)(11); and
■ d. Revising paragraph (c)(2).
The revision and addition read as
follows:
■
■
■
§ 431.95 Materials incorporated by
reference.
*
*
*
*
*
(b) * * *
(4) AHRI Standard 340/360–2022 (I–
P) (‘‘AHRI 340/360–2022’’), 2022
Standard for Performance Rating of
Commercial and Industrial Unitary Airconditioning and Heat Pump
Equipment, approved January 26, 2022;
IBR approved for appendix A to this
subpart.
*
*
*
*
*
(11) AHRI Standard 1340–2023 (I–P)
(‘‘AHRI 1340–2023’’), 2023 Standard for
Performance Rating of Commercial and
44037
Industrial Unitary Air-conditioning and
Heat Pump Equipment, approved
November 16, 2023; IBR approved for
appendix A1 to this subpart.
*
*
*
*
*
(c) * * *
(2) ANSI/ASHRAE Standard 37–2009
(‘‘ANSI/ASHRAE 37–2009’’), Methods
of Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat
Pump Equipment, approved June 24,
2009; IBR approved for § 431.96 and
appendices A, A1, B, C1, D1, E1, F1, G,
and G1 to this subpart.
*
*
*
*
*
■ 9. Amend § 431.96 by revising table 1
to paragraph (b) to read as follows:
§ 431.96 Uniform test method for the
measurement of energy efficiency of
commercial air conditioners and heat
pumps.
*
*
*
(b) * * *
*
*
lotter on DSK11XQN23PROD with RULES2
TABLE 1 TO PARAGRAPH (b)—TEST PROCEDURES FOR COMMERCIAL AIR CONDITIONERS AND HEAT PUMPS
Cooling
capacity or
moisture
removal
capacity 1
Energy
efficiency descriptor
Air-Cooled, 3-Phase, AC
and HP.
<65,000 Btu/h .................
SEER and HSPF ............
Appendix F to this subpart 2.
None.
Air-Cooled, 3-Phase, AC
and HP.
<65,000 Btu/h .................
SEER2 and HSPF2 ........
Appendix F1 to this subpart 2.
None.
Air-Cooled AC and HP
(excluding double-duct
AC and HP).
Air-Cooled AC and HP
(excluding double-duct
AC and HP).
Double-duct AC and HP
≥65,000 Btu/h and
<760,000 Btu/h.
EER, IEER, and COP ....
Appendix A to this subpart 2.
None.
≥65,000 Btu/h and
<760,000 Btu/h.
EER2, COP2, IVEC, and
IVHE.
Appendix A1 to this subpart 2.
None.
≥65,000 Btu/h and
<300,000 Btu/h.
EER, IEER, and COP ....
Appendix A to this subpart 2.
None.
Double-duct AC and HP
≥65,000 Btu/h and
<300,000 Btu/h.
EER2, COP2, IVEC, and
IVHE.
Appendix A1 to this subpart 2.
None.
Water-Cooled and Evaporatively-Cooled AC.
<760,000 Btu/h ...............
EER and IEER ...............
Appendix A to this subpart 2.
None.
Water-Cooled and Evaporatively-Cooled AC.
<760,000 Btu/h ...............
EER2 and IVEC .............
Appendix A1 to this subpart 2.
None.
HP ...................................
<760,000 Btu/h ...............
EER and COP ................
None.
HP ...................................
<760,000 Btu/h ...............
IEER and ACOP .............
AC and HP .....................
<760,000 Btu/h ...............
EER and COP ................
Appendix C to this subpart 2.
Appendix C1 to this subpart 2.
Paragraph (g) of this section.
AC ...................................
<760,000 Btu/h ...............
SCOP .............................
E to this sub-
None.
AC ...................................
NSenCOP .......................
E1 to this sub-
None.
AC ...................................
<760,000 Btu/h or
<930,000 Btu/h 3.
<65,000 Btu/h (3-phase)
SEER ..............................
F to this sub-
None.
AC ...................................
<65,000 Btu/h (3-phase)
SEER2 ............................
F1 to this sub-
None.
HP ...................................
<65,000 Btu/h (3-phase)
SEER and HSPF ............
Appendix
part 2.
Appendix
part 2.
Appendix
part 2.
Appendix
part 2.
Appendix
part 2.
F to this sub-
None.
HP ...................................
<65,000 Btu/h (3-phase)
SEER2 and HSPF2 ........
Equipment
Category
Commercial Package Air
Conditioning and Heating Equipment.
Commercial Package Air
Conditioning and Heating Equipment.
Commercial Package Air
Conditioning and Heating Equipment.
Commercial Package Air
Conditioning and Heating Equipment.
Commercial Package Air
Conditioning and Heating Equipment.
Commercial Package Air
Conditioning and Heating Equipment.
Commercial Package Air
Conditioning and Heating Equipment.
Commercial Package Air
Conditioning and Heating Equipment.
Water-Source Heat
Pumps.
Water-Source Heat
Pumps.
Packaged Terminal Air
Conditioners and Heat
Pumps.
Computer Room Air Conditioners.
Computer Room Air Conditioners.
Variable Refrigerant Flow
Multi-split Systems.
Variable Refrigerant Flow
Multi-split Systems.
Variable Refrigerant Flow
Multi-split Systems, Aircooled.
Variable Refrigerant Flow
Multi-split Systems, Aircooled.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00053
Fmt 4701
Sfmt 4700
Use tests,
conditions, an
procedures in
Appendix F1 to this subpart 2.
E:\FR\FM\20MYR2.SGM
20MYR2
Additional test procedure
provisions as indicated in
the listed paragraphs of
this section
None.
Paragraphs (c), (e), and
(g).
None.
44038
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 1 TO PARAGRAPH (b)—TEST PROCEDURES FOR COMMERCIAL AIR CONDITIONERS AND HEAT PUMPS—Continued
Cooling
capacity or
moisture
removal
capacity 1
Use tests,
conditions, an
procedures in
Energy
efficiency descriptor
Additional test procedure
provisions as indicated in
the listed paragraphs of
this section
Equipment
Category
Variable Refrigerant Flow
Multi-split Systems, Aircooled.
Variable Refrigerant Flow
Multi-split Systems, Aircooled.
Variable Refrigerant Flow
Multi-split Systems,
Water-source.
Variable Refrigerant Flow
Multi-split Systems,
Water-source.
Single Package Vertical
Air Conditioners and
Single Package Vertical
Heat Pumps.
Single Package Vertical
Air Conditioners and
Single Package Vertical
Heat Pumps.
Direct Expansion-Dedicated Outdoor Air Systems.
AC and HP .....................
≥65,000 Btu/h and
<760,000 Btu/h.
EER and COP ................
Appendix D to this subpart 2.
None.
AC and HP .....................
≥65,000 Btu/h and
<760,000 Btu/h.
IEER and COP ...............
Appendix D1 to this subpart 2.
None.
HP ...................................
<760,000 Btu/h ...............
EER and COP ................
Appendix D to this subpart 2.
None.
HP ...................................
<760,000 Btu/h ...............
IEER and COP ...............
Appendix D1 to this subpart 2.
None.
AC and HP .....................
<760,000 Btu/h ...............
EER and COP ................
Appendix G to this subpart 2.
None.
AC and HP .....................
<760,000 Btu/h ...............
EER, IEER, and COP ....
Appendix G1 to this subpart 2.
None.
All ....................................
<324 lbs. of moisture removal/hr.
ISMRE2 and ISCOP2 .....
Appendix B to this subpart.
None.
1 Moisture
removal capacity applies only to direct expansion-dedicated outdoor air systems.
2 For equipment with multiple appendices listed in this table, consult the notes at the beginning of those appendices to determine the applicable appendix to use for
testing.
3 For upflow ducted and downflow floor-mounted computer room air conditioners, the test procedure in appendix E1 to this subpart applies to equipment with net
sensible cooling capacity less than 930,000 Btu/h. For all other configurations of computer room air conditioners, the test procedure in appendix E1 to this subpart applies to equipment with net sensible cooling capacity less than 760,000 Btu/h.
*
■
*
*
*
*
10. Revise § 431.97 to read as follows:
§ 431.97 Energy efficiency standards and
their compliance dates.
(a) All basic models of commercial
package air conditioning and heating
equipment must be tested for
performance using the applicable DOE
test procedure in § 431.96, be compliant
with the applicable standards set forth
in paragraphs (b) through (i) of this
section, and be certified to the
Department under 10 CFR part 429.
(b) Each commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with
cooling capacity less than 65,000 Btu/h)
manufactured starting on the
compliance date listed in tables 1
through 4 to this paragraph (b) must
meet the applicable minimum energy
efficiency standard level(s) set forth in
tables 1 through 4.
TABLE 1 TO PARAGRAPH (b)—MINIMUM EFFICIENCY STANDARDS FOR AIR-COOLED COMMERCIAL PACKAGE AIR
CONDITIONING AND HEATING EQUIPMENT WITH A COOLING CAPACITY GREATER THAN OR EQUAL TO 65,000 BTU/H
[Excluding double-duct air-conditioners and heat pumps]
Cooling capacity
Subcategory
Minimum
efficiency 1
Supplementary heating type
Compliance date:
equipment
manufactured
starting
on . . .
lotter on DSK11XQN23PROD with RULES2
Air-Cooled Commercial Package Air Conditioning and Heating Equipment with a Cooling Capacity Greater Than or Equal to 65,000 Btu/h (Excluding
Double-Duct Air Conditioners and Heat Pumps)
≥65,000 Btu/h and <135,000 Btu/h ...........................
≥65,000 Btu/h and <135,000 Btu/h ...........................
≥65,000 Btu/h and <135,000 Btu/h ...........................
AC .................
AC .................
HP .................
Electric Resistance Heating or No Heating ..............
All Other Types of Heating .......................................
Electric Resistance Heating or No Heating ..............
≥65,000 Btu/h and <135,000 Btu/h ...........................
HP .................
All Other Types of Heating .......................................
≥135,000 Btu/h and <240,000 Btu/h .........................
≥135,000 Btu/h and <240,000 Btu/h .........................
≥135,000 Btu/h and <240,000 Btu/h .........................
AC .................
AC .................
HP .................
Electric Resistance Heating or No Heating ..............
All Other Types of Heating .......................................
Electric Resistance Heating or No Heating ..............
≥135,000 Btu/h and <240,000 Btu/h .........................
HP .................
All Other Types of Heating .......................................
≥240,000 Btu/h and <760,000 Btu/h .........................
≥240,000 Btu/h and <760,000 Btu/h .........................
≥240,000 Btu/h and <760,000 Btu/h .........................
AC .................
AC .................
HP .................
Electric Resistance Heating or No Heating ..............
All Other Types of Heating .......................................
Electric Resistance Heating or No Heating ..............
≥240,000 Btu/h and <760,000 Btu/h .........................
HP .................
All Other Types of Heating .......................................
1 See
IEER = 14.8 .........
IEER = 14.6 .........
IEER = 14.1 .........
COP = 3.4 ............
IEER = 13.9 .........
COP = 3.4 ............
IEER = 14.2 .........
IEER = 14.0 .........
IEER = 13.5 .........
COP = 3.3 ............
IEER = 13.3 .........
COP = 3.3 ............
IEER = 13.2 .........
IEER = 13.0 .........
IEER = 12.5 .........
COP = 3.2 ............
IEER = 12.3 .........
COP = 3.2 ............
section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00054
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
January 1, 2023.
44039
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 2 TO PARAGRAPH (b)—MINIMUM COOLING EFFICIENCY STANDARDS FOR WATER-COOLED COMMERCIAL PACKAGE
AIR CONDITIONING EQUIPMENT
Cooling capacity
Compliance date: equipment
manufactured starting
on . . .
Minimum
efficiency
Supplementary heating type
Water-Cooled Commercial Package Air Conditioning Equipment
<65,000 Btu/h .................................................
≥65,000 Btu/h and <135,000 Btu/h ................
≥65,000 Btu/h and <135,000 Btu/h ................
≥135,000 Btu/h and <240,000 Btu/h ..............
≥135,000 Btu/h and <240,000 Btu/h ..............
≥240,000 Btu/h and <760,000 Btu/h ..............
≥240,000 Btu/h and <760,000 Btu/h ..............
All ...................................................................
No Heating or Electric Resistance Heating ...
All Other Types of Heating ............................
No Heating or Electric Resistance Heating ...
All Other Types of Heating ............................
No Heating or Electric Resistance Heating ...
All Other Types of Heating ............................
EER
EER
EER
EER
EER
EER
EER
=
=
=
=
=
=
=
12.1
12.1
11.9
12.5
12.3
12.4
12.2
........
........
........
........
........
........
........
October 29, 2003.
June 1, 2013.
June 1, 2013.
June 1, 2014.
June 1, 2014.
June 1, 2014.
June 1, 2014.
TABLE 3 TO PARAGRAPH (b)—MINIMUM COOLING EFFICIENCY STANDARDS FOR EVAPORATIVELY-COOLED COMMERCIAL
PACKAGE AIR CONDITIONING EQUIPMENT
Cooling capacity
Compliance date: equipment
manufactured starting
on . . .
Minimum
efficiency
Supplementary heating type
Evaporatively-Cooled Commercial Package Air Conditioning Equipment
<65,000 Btu/h .................................................
≥65,000 Btu/h and <135,000 Btu/h ................
≥65,000 Btu/h and <135,000 Btu/h ................
≥135,000 Btu/h and <240,000 Btu/h ..............
≥135,000 Btu/h and <240,000 Btu/h ..............
≥240,000 Btu/h and <760,000 Btu/h ..............
≥240,000 Btu/h and <760,000 Btu/h ..............
All ...................................................................
No Heating or Electric Resistance Heating ...
All Other Types of Heating ............................
No Heating or Electric Resistance Heating ...
All Other Types of Heating ............................
No Heating or Electric Resistance Heating ...
All Other Types of Heating ............................
EER
EER
EER
EER
EER
EER
EER
=
=
=
=
=
=
=
12.1
12.1
11.9
12.0
11.8
11.9
11.7
........
........
........
........
........
........
........
October 29, 2003.
June 1, 2013.
June 1, 2013.
June 1, 2014.
June 1, 2014.
June 1, 2014.
June 1, 2014.
TABLE 4 TO PARAGRAPH (b)—MINIMUM EFFICIENCY STANDARDS FOR DOUBLE-DUCT AIR CONDITIONERS AND HEAT
PUMPS
Cooling capacity
Subcategory
Minimum
efficiency 1
Supplementary heating type
Compliance date:
equipment
manufactured
starting
on . . .
Double-Duct Air Conditioners and Heat Pumps
≥65,000 Btu/h and <135,000 Btu/h ...........................
≥65,000 Btu/h and <135,000 Btu/h ...........................
≥65,000 Btu/h and <135,000 Btu/h ...........................
AC .................
AC .................
HP .................
Electric Resistance Heating or No Heating ..............
All Other Types of Heating .......................................
Electric Resistance Heating or No Heating ..............
≥65,000 Btu/h and <135,000 Btu/h ...........................
HP .................
All Other Types of Heating .......................................
≥135,000 Btu/h and <240,000 Btu/h .........................
≥135,000 Btu/h and <240,000 Btu/h .........................
≥135,000 Btu/h and <240,000 Btu/h .........................
AC .................
AC .................
HP .................
Electric Resistance Heating or No Heating ..............
All Other Types of Heating .......................................
Electric Resistance Heating or No Heating ..............
≥135,000 Btu/h and <240,000 Btu/h .........................
HP .................
All Other Types of Heating .......................................
≥240,000 Btu/h and <300,000 Btu/h .........................
≥240,000 Btu/h and <300,000 Btu/h .........................
≥240,000 Btu/h and <300,000 Btu/h .........................
AC .................
AC .................
HP .................
Electric Resistance Heating or No Heating ..............
All Other Types of Heating .......................................
Electric Resistance Heating or No Heating ..............
≥240,000 Btu/h and <300,000 Btu/h .........................
HP .................
All Other Types of Heating .......................................
1 See
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
(c) Each water-source heat pump
manufactured starting on the
lotter on DSK11XQN23PROD with RULES2
EER = 11.2 ..........
EER = 11.0 ..........
EER = 11.0 ..........
COP = 3.3 ............
EER = 10.8 ..........
COP = 3.3 ............
EER = 11.0 ..........
EER = 10.8 ..........
EER = 10.6 ..........
COP = 3.2 ............
EER = 10.4 ..........
COP = 3.2 ............
EER = 10.0 ..........
EER = 9.8 ............
EER = 9.5 ............
COP = 3.2 ............
EER = 9.3 ............
COP = 3.2 ............
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
compliance date listed in table 5 to this
paragraph (c) must meet the applicable
PO 00000
Frm 00055
Fmt 4701
Sfmt 4700
minimum energy efficiency standard
level(s) set forth in this paragraph (c).
E:\FR\FM\20MYR2.SGM
20MYR2
44040
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 5 TO PARAGRAPH (c)—MINIMUM EFFICIENCY STANDARDS FOR WATER-SOURCE HEAT PUMPS (WATER-TO-AIR,
WATER-LOOP)
Cooling capacity
Compliance date: equipment manufactured starting
on . . .
Minimum efficiency
Water-Source Heat Pumps (Water-to-Air, Water-Loop)
<17,000 Btu/h ..............................................................
≥17,000 Btu/h and <65,000 Btu/h ...............................
≥65,000 Btu/h and <135,000 Btu/h .............................
(d) Each non-standard size packaged
terminal air conditioner (PTAC) and
packaged terminal heat pump (PTHP)
manufactured on or after October 7,
2010, must meet the applicable
minimum energy efficiency standard
level(s) set forth in table 6 to this
paragraph (d). Each standard size PTAC
EER = 12.2 ....................................
COP = 4.3 .....................................
EER = 13.0 ....................................
COP = 4.3 .....................................
EER = 13.0 ....................................
COP = 4.3 .....................................
October 9, 2015.
October 9, 2015.
October 9, 2015.
manufactured on or after October 8,
2012, and before January 1, 2017, must
meet the applicable minimum energy
efficiency standard level(s) set forth in
table 6. Each standard size PTHP
manufactured on or after October 8,
2012, must meet the applicable
minimum energy efficiency standard
level(s) set forth in table 6. Each
standard size PTAC manufactured on or
after January 1, 2017, must meet the
applicable minimum energy efficiency
standard level(s) set forth in table 7 to
this paragraph (d).
TABLE 6 TO PARAGRAPH (d)—MINIMUM EFFICIENCY STANDARDS FOR PTAC AND PTHP
Compliance date: products
manufactured on and
after . . .
Equipment
type
Category
Cooling capacity
Efficiency level
PTAC .............
Standard Size ............
<7,000 Btu/h ..................................
≥7,000 Btu/h and ≤15,000 Btu/h ....
>15,000 Btu/h ................................
<7,000 Btu/h ..................................
≥7,000 Btu/h and ≤15,000 Btu/h ....
>15,000 Btu/h ................................
<7,000 Btu/h ..................................
EER = 11.7 ....................................
EER = 13.8¥(0.3 × Cap 1) ............
EER = 9.3 ......................................
EER = 9.4 ......................................
EER = 10.9¥(0.213 × Cap 1) ........
EER = 7.7 ......................................
EER = 11.9 ....................................
COP = 3.3 ......................................
EER = 14.0¥(0.3 × Cap 1) ............
COP = 3.7¥(0.052 × Cap 1) ..........
EER = 9.5 ......................................
COP = 2.9 ......................................
EER = 9.3 ......................................
COP = 2.7 ......................................
EER = 10.8¥(0.213 × Cap 1) ........
COP = 2.9¥(0.026 × Cap 1) ..........
EER = 7.6 ......................................
COP = 2.5 ......................................
Non-Standard Size ....
PTHP .............
Standard Size ............
≥7,000 Btu/h and ≤15,000 Btu/h ....
>15,000 Btu/h ................................
Non-Standard Size ....
<7,000 Btu/h ..................................
≥7,000 Btu/h and ≤15,000 Btu/h ....
>15,000 Btu/h ................................
October
October
October
October
October
October
October
8,
8,
8,
7,
7,
7,
8,
2012.2
2012.2
2012.2
2010.
2010.
2010.
2012.
October 8, 2012.
October 8, 2012.
October 7, 2010.
October 7, 2010.
October 7, 2010.
means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.
manufactured before January 1, 2017. See table 7 to this paragraph (d) for updated efficiency standards that apply to this category of
equipment manufactured on and after January 1, 2017.
1 ‘‘Cap’’
2 And
TABLE 7 TO PARAGRAPH (d)—UPDATED MINIMUM EFFICIENCY STANDARDS FOR PTAC
Category
Cooling capacity
Efficiency level
PTAC .............
Standard Size ............
<7,000 Btu/h ..................................
≥7,000 Btu/h and ≤15,000 Btu/h ....
>15,000 Btu/h ................................
EER = 11.9 ....................................
EER = 14.0¥(0.3 × Cap 1) ............
EER = 9.5 ......................................
1 ‘‘Cap’’
lotter on DSK11XQN23PROD with RULES2
Compliance date: products
manufactured on and
after . . .
Equipment
type
January 1, 2017.
January 1, 2017.
January 1, 2017.
means cooling capacity in thousand Btu/h at 95 °F outdoor dry-bulb temperature.
(e)(1) Each single package vertical air
conditioner and single package vertical
heat pump manufactured on or after
January 1, 2010, but before October 9,
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
2015 (for models ≥65,000 Btu/h and
<135,000 Btu/h), or October 9, 2016 (for
models ≥135,000 Btu/h and <240,000
Btu/h), must meet the applicable
PO 00000
Frm 00056
Fmt 4701
Sfmt 4700
minimum energy conservation standard
level(s) set forth in this paragraph (e)(1).
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
44041
TABLE 8 TO PARAGRAPH (e)(1)—MINIMUM EFFICIENCY STANDARDS FOR SINGLE PACKAGE VERTICAL AIR CONDITIONERS
AND SINGLE PACKAGE VERTICAL HEAT PUMPS
Equipment type
Cooling capacity
Sub-category
Efficiency
level
Single package vertical air conditioners and single package vertical heat pumps, single-phase
and three-phase.
Single package vertical air conditioners and single package vertical heat pumps.
<65,000 Btu/h .............
AC ...............
HP ...............
≥65,000 Btu/h and
<135,000 Btu/h.
AC ...............
HP ...............
Single package vertical air conditioners and single package vertical heat pumps.
≥135,000 Btu/h and
<240,000 Btu/h.
AC ...............
HP ...............
EER = 9.0 .....
EER = 9.0 .....
COP = 3.0 ....
EER = 8.9 .....
EER = 8.9 .....
COP = 3.0 ....
EER = 8.6 .....
EER = 8.6 .....
COP = 2.9 ....
(2) Each single package vertical air
conditioner and single package vertical
heat pump manufactured on and after
October 9, 2015 (for models ≥65,000
Btu/h and <135,000 Btu/h), or October
9, 2016 (for models ≥135,000 Btu/h and
<240,000 Btu/h), but before September
23, 2019, must meet the applicable
Compliance date: products
manufactured on and after . . .
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
January 1, 2010.
minimum energy conservation standard
level(s) set forth in this paragraph (e)(2).
TABLE 9 TO PARAGRAPH (e)(2)—MINIMUM EFFICIENCY STANDARDS FOR SINGLE PACKAGE VERTICAL AIR CONDITIONERS
AND SINGLE PACKAGE VERTICAL HEAT PUMPS
Equipment type
Cooling capacity
Sub-category
Efficiency
level
Single package vertical air conditioners and single package vertical heat pumps, single-phase
and three-phase.
Single package vertical air conditioners and single package vertical heat pumps.
<65,000 Btu/h .............
AC ...............
HP ...............
≥65,000 Btu/h and
<135,000 Btu/h.
AC ...............
HP ...............
Single package vertical air conditioners and single package vertical heat pumps.
≥135,000 Btu/h and
<240,000 Btu/h.
AC ...............
HP ...............
EER = 9.0 .....
EER = 9.0 .....
COP = 3.0 ....
EER = 10.0 ...
EER = 10.0 ...
COP = 3.0 ....
EER = 10.0 ...
EER = 10.0 ...
COP = 3.0 ....
(3) Each single package vertical air
conditioner and single package vertical
heat pump manufactured on and after
September 23, 2019, must meet the
applicable minimum energy
Compliance date: products
manufactured on and after . . .
January 1, 2010.
January 1, 2010.
October 9, 2015.
October 9, 2015.
October 9, 2016.
October 9, 2016.
conservation standard level(s) set forth
in this paragraph (e)(3).
TABLE 10 TO PARAGRAPH (e)(3)—UPDATED MINIMUM EFFICIENCY STANDARDS FOR SINGLE PACKAGE VERTICAL AIR
CONDITIONERS AND SINGLE PACKAGE VERTICAL HEAT PUMPS
Cooling
capacity
Sub-category
Efficiency
level
Single package vertical air conditioners and single package vertical heat pumps, single-phase
and three-phase.
Single package vertical air conditioners and single package vertical heat pumps.
<65,000 Btu/h .............
AC ...............
HP ...............
≥65,000 Btu/h and
<135,000 Btu/h.
AC ...............
HP ...............
Single package vertical air conditioners and single package vertical heat pumps.
≥135,000 Btu/h and
<240,000 Btu/h.
AC ...............
HP ...............
EER = 11.0 ...
EER = 11.0 ...
COP = 3.3 ....
EER = 10.0 ...
EER = 10.0 ...
COP = 3.0 ....
EER = 10.0 ...
EER = 10.0 ...
COP = 3.0 ....
lotter on DSK11XQN23PROD with RULES2
Equipment type
(f)(1) Each computer room air
conditioner with a net sensible cooling
capacity less than 65,000 Btu/h
manufactured on or after October 29,
2012, and before May 28, 2024 and each
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
computer room air conditioner with a
net sensible cooling capacity greater
than or equal to 65,000 Btu/h and less
than 760,000 Btu/h manufactured on or
after October 29, 2013, and before May
PO 00000
Frm 00057
Fmt 4701
Sfmt 4700
Compliance date: products
manufactured on and after . . .
September 23, 2019.
September 23, 2019.
October 9, 2015.
October 9, 2015.
October 9, 2016.
October 9, 2016.
28, 2024, must meet the applicable
minimum energy efficiency standard
level(s) set forth in this paragraph (f)(1).
E:\FR\FM\20MYR2.SGM
20MYR2
44042
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 11 TO PARAGRAPH (f)(1)—MINIMUM EFFICIENCY STANDARDS FOR COMPUTER ROOM AIR CONDITIONERS
Minimum SCOP efficiency
Equipment type
Net sensible cooling capacity
Downflow
Air-Cooled .....................................................................
Water-Cooled ................................................................
Water-Cooled with Fluid Economizer ...........................
Glycol-Cooled ...............................................................
Glycol-Cooled with Fluid Economizer ..........................
(2) Each computer room air
conditioner manufactured on or after
May 28, 2024, must meet the applicable
<65,000 Btu/h ...............................................................
≥65,000 Btu/h and <240,000 Btu/h ..............................
≥240,000 Btu/h and <760,000 Btu/h ............................
<65,000 Btu/h ...............................................................
≥65,000 Btu/h and <240,000 Btu/h ..............................
≥240,000 Btu/h and <760,000 Btu/h ............................
<65,000 Btu/h ...............................................................
≥65,000 Btu/h and <240,000 Btu/h ..............................
≥240,000 Btu/h and <760,000 Btu/h ............................
<65,000 Btu/h ...............................................................
≥65,000 Btu/h and <240,000 Btu/h ..............................
≥240,000 Btu/h and <760,000 Btu/h ............................
<65,000 Btu/h ...............................................................
≥65,000 Btu/h and <240,000 Btu/h ..............................
≥240,000 Btu/h and <760,000 Btu/h ............................
Upflow
2.20
2.10
1.90
2.60
2.50
2.40
2.55
2.45
2.35
2.50
2.15
2.10
2.45
2.10
2.05
2.09
1.99
1.79
2.49
2.39
2.29
2.44
2.34
2.24
2.39
2.04
1.99
2.34
1.99
1.94
minimum energy efficiency standard
level(s) set forth in this paragraph (f)(2).
TABLE 12 TO PARAGRAPH (f)(2)—UPDATED MINIMUM EFFICIENCY STANDARDS FOR FLOOR-MOUNTED COMPUTER ROOM
AIR CONDITIONERS
Downflow and upflow ducted
Upflow non-ducted and horizontal flow
Minimum NSenCOP efficiency
Equipment type
Net sensible cooling capacity
Downflow
Air-Cooled ......................
Air-Cooled with Fluid
Economizer.
Water-Cooled .................
Water-Cooled with Fluid
Economizer.
Glycol-Cooled .................
lotter on DSK11XQN23PROD with RULES2
Glycol-Cooled with Fluid
Economizer.
Minimum NSenCOP efficiency
Net sensible cooling capacity
<80,000 Btu/h .............................
≥80,000 Btu/h and <295,000 Btu/
h.
≥295,000 Btu/h and <930,000
Btu/h.
<80,000 Btu/h .............................
2.70
2.58
2.67
2.55
2.36
2.33
2.70
2.67
≥80,000 Btu/h and <295,000 Btu/
h.
≥295,000 Btu/h and <930,000
Btu/h.
<80,000 Btu/h .............................
≥80,000 Btu/h and <295,000 Btu/
h.
≥295,000 Btu/h and <930,000
Btu/h.
<80,000 Btu/h .............................
2.58
2.55
2.36
2.33
2.82
2.73
2.79
2.70
2.67
2.64
2.77
2.74
2.68
2.65
2.61
2.58
2.56
2.24
2.53
2.21
2.21
2.18
2.51
2.48
2.19
2.16
2.15
2.12
≥80,000 Btu/h and <295,000 Btu/
h.
≥295,000 Btu/h and <930,000
Btu/h.
<80,000 Btu/h .............................
≥80,000 Btu/h and <295,000 Btu/
h.
≥295,000 Btu/h and <930,000
Btu/h.
<80,000 Btu/h .............................
≥80,000 Btu/h and <295,000 Btu/
h.
≥295,000 Btu/h and <930,000
Btu/h.
Upflow
non-ducted
Upflow ducted
<65,000 Btu/h .............................
≥65,000 Btu/h and <240,000 Btu/
h.
≥240,000 Btu/h and <760,000
Btu/h.
<65,000 Btu/h .............................
≥65,000 Btu/h and <240,000 Btu/
h.
≥240,000 Btu/h and <760,000
Btu/h.
<65,000 Btu/h .............................
≥65,000 Btu/h and <240,000 Btu/
h.
≥240,000 Btu/h and <760,000
Btu/h.
<65,000 Btu/h .............................
≥65,000 Btu/h and <240,000 Btu/
h.
≥240,000 Btu/h and <760,000
Btu/h.
<65,000 Btu/h .............................
≥65,000 Btu/h and <240,000 Btu/
h.
≥240,000 Btu/h and <760,000
Btu/h.
<65,000 Btu/h .............................
≥65,000 Btu/h and <240,000 Btu/
h.
≥240,000 Btu/h and <760,000
Btu/h.
Horizontal
flow
2.16
2.04
2.65
2.55
1.89
2.47
2.09
2.65
1.99
2.55
1.81
2.47
2.43
2.32
2.79
2.68
2.20
2.60
2.35
2.71
2.24
2.60
2.12
2.54
2.08
1.90
2.48
2.18
1.81
2.18
2.00
2.44
1.82
2.10
1.73
2.10
TABLE 13 TO PARAGRAPH (f)(2)—MINIMUM EFFICIENCY STANDARDS FOR CEILING-MOUNTED COMPUTER ROOM AIR
CONDITIONERS
Minimum NSenCOP efficiency
Equipment type
Net sensible cooling capacity
Ducted
Air-Cooled with Free Air Discharge Condenser ...........
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
<29,000 Btu/h ...............................................................
Frm 00058
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
I Non-ducted
2.05 I
2.08
44043
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 13 TO PARAGRAPH (f)(2)—MINIMUM EFFICIENCY STANDARDS FOR CEILING-MOUNTED COMPUTER ROOM AIR
CONDITIONERS—Continued
Minimum NSenCOP efficiency
Equipment type
Net sensible cooling capacity
Ducted
Air-Cooled with Free Air Discharge Condenser and
Fluid Economizer.
Air-Cooled with Ducted Condenser ..............................
Air-Cooled with Fluid Economizer and Ducted Condenser.
Water-Cooled ................................................................
Water-Cooled with Fluid Economizer ...........................
Glycol-Cooled ...............................................................
Glycol-Cooled with Fluid Economizer ..........................
(g)(1) Each variable refrigerant flow
air conditioner or heat pump
manufactured on or after the
Non-ducted
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
<29,000 Btu/h ...............................................................
2.02
1.92
2.01
2.05
1.94
2.04
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
<29,000 Btu/h ...............................................................
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
<29,000 Btu/h ...............................................................
1.97
1.87
1.86
1.83
1.73
1.82
2
1.89
1.89
1.86
1.75
1.85
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
<29,000 Btu/h ...............................................................
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
<29,000 Btu/h ...............................................................
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
<29,000 Btu/h ...............................................................
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
<29,000 Btu/h ...............................................................
≥29,000 Btu/h and <65,000 Btu/h ................................
≥65,000 Btu/h and <760,000 Btu/h ..............................
1.78
1.68
2.38
2.28
2.18
2.33
2.23
2.13
1.97
1.93
1.78
1.92
1.88
1.73
1.81
1.7
2.41
2.31
2.2
2.36
2.26
2.16
2
1.98
1.81
1.95
1.93
1.76
compliance date listed in table 14 to this
paragraph (g)(1) and prior to January 1,
2024, must meet the applicable
minimum energy efficiency standard
level(s) set forth in this paragraph (g)(1).
TABLE 14 TO PARAGRAPH (g)(1)—MINIMUM EFFICIENCY STANDARDS FOR VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR
CONDITIONERS AND HEAT PUMPS
Equipment type
VRF Multi-Split Air Conditioners (Air-Cooled).
≥65,000 Btu/h and
<135,000 Btu/h.
≥135,000 Btu/h and
<240,000 Btu/h.
≥240,000 Btu/h and
<760,000 Btu/h.
VRF Multi-Split Heat
Pumps (Air-Cooled).
≥65,000 Btu/h and
<135,000 Btu/h.
≥135,000 Btu/h and
<240,000 Btu/h.
≥240,000 Btu/h and
<760,000 Btu/h.
lotter on DSK11XQN23PROD with RULES2
VRF Multi-Split Heat
Pumps (Water-Source).
<17,000 Btu/h ...................
≥17,000 Btu/h and
<65,000 Btu/h.
≥65,000 Btu/h and
<135,000 Btu/h.
≥135,000 Btu/h and
<760,000 Btu/h.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Compliance date:
equipment manufactured
on and after . . .
Heating type 1
Efficiency level
No Heating or Electric Resistance Heating.
All Other Types of Heating
No Heating or Electric Resistance Heating.
All Other Types of Heating
No Heating or Electric Resistance Heating.
All Other Types of Heating
No Heating or Electric Resistance Heating.
All Other Types of Heating
No Heating or Electric Resistance Heating.
All Other Types of Heating
No Heating or Electric Resistance Heating.
All Other Types of Heating
Without Heat Recovery .....
11.2 EER ...........................
January 1, 2010.
11.0 EER ...........................
11.0 EER ...........................
January 1, 2010.
January 1, 2010.
10.8 EER ...........................
10.0 EER ...........................
January 1, 2010.
January 1, 2010.
9.8 EER .............................
11.0 EER, 3.3 COP ..........
January 1, 2010.
January 1, 2010.
10.8 EER, 3.3 COP ..........
10.6 EER, 3.2 COP ..........
January 1, 2010.
January 1, 2010.
10.4 EER, 3.2 COP ..........
9.5 EER, 3.2 COP ............
January 1, 2010.
January 1, 2010.
9.3 EER, 3.2 COP ............
12.0 EER, 4.2 COP ..........
Cooling capacity
With Heat Recovery ..........
11.8 EER, 4.2 COP ..........
All.
12.0 EER, 4.2 COP ..........
January
October
October
October
October
October
All.
12.0 EER, 4.2 COP ..........
October 29, 2003.
Without Heat Recovery .....
10.0 EER, 3.9 COP ..........
October 29, 2013.
Frm 00059
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
1, 2010.
29, 2012.
29, 2003.
29, 2012.
29, 2003.
29, 2003.
44044
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 14 TO PARAGRAPH (g)(1)—MINIMUM EFFICIENCY STANDARDS FOR VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR
CONDITIONERS AND HEAT PUMPS—Continued
Equipment type
Heating type 1
Efficiency level
With Heat Recovery ..........
9.8 EER, 3.9 COP ............
Cooling capacity
Compliance date:
equipment manufactured
on and after . . .
October 29, 2013.
1 VRF
multi-split heat pumps (air-cooled) with heat recovery fall under the category of ‘‘All Other Types of Heating’’ unless they also have electric resistance heating, in which case it falls under the category for ‘‘No Heating or Electric Resistance Heating.’’
(2) Each variable refrigerant flow air
conditioner or heat pump (except aircooled systems with cooling capacity
less than 65,000 Btu/h) manufactured
on or after January 1, 2024, must meet
the applicable minimum energy
efficiency standard level(s) set forth in
this paragraph (g)(2).
TABLE 15 TO PARAGRAPH (g)(2)—UPDATED MINIMUM EFFICIENCY STANDARDS FOR VARIABLE REFRIGERANT FLOW MULTISPLIT AIR CONDITIONERS AND HEAT PUMPS
Equipment type
VRF Multi-Split Air Conditioners (AirCooled).
VRF Multi-Split Heat Pumps (Air-Cooled)
Size category
Heating type
≥65,000 and <135,000 Btu/h .....................
All ..............................................
15.5 IEER.
≥135,000 and <240,000 Btu/h ...................
≥240,000 Btu/h and <760,000 Btu/h .........
≥65,000 and <135,000 Btu/h .....................
All ..............................................
All ..............................................
Heat Pump without Heat Recovery.
Heat Pump with Heat Recovery
Heat Pump without Heat Recovery.
Heat Pump with Heat Recovery
Heat Pump without Heat Recovery.
Heat Pump with Heat Recovery
Heat Pump without Heat Recovery.
Heat Pump with Heat Recovery
Heat Pump without Heat Recovery.
Heat Pump with Heat Recovery
Heat Pump without Heat Recovery.
Heat Pump with Heat Recovery
Heat Pump without Heat Recovery.
Heat Pump with Heat Recovery
14.9 IEER.
13.9 IEER.
14.6 IEER, 3.3 COP.
≥135,000 and <240,000 Btu/h ...................
≥240,000 Btu/h and <760,000 Btu/h .........
VRF Multi-Split Heat Pumps (WaterSource).
<65,000 Btu/h ............................................
≥65,000 and <135,000 Btu/h .....................
≥135,000 and <240,000 Btu/h ...................
≥240,000 Btu/h and <760,000 Btu/h .........
(h) Each direct expansion-dedicated
outdoor air system manufactured on or
after the compliance date listed in table
16 to this paragraph (h) must meet the
applicable minimum energy efficiency
Minimum efficiency
14.4 IEER, 3.3 COP.
13.9 IEER, 3.2 COP.
13.7 IEER, 3.2 COP.
12.7 IEER, 3.2 COP.
12.5 IEER, 3.2 COP.
16.0 IEER, 4.3 COP.
15.8 IEER, 4.3 COP.
16.0 IEER, 4.3 COP.
15.8 IEER, 4.3 COP.
14.0 IEER, 4.0 COP.
13.8 IEER, 4.0 COP.
12.0 IEER, 3.9 COP.
11.8 IEER, 3.9 COP.
standard level(s) set forth in this
paragraph (h).
lotter on DSK11XQN23PROD with RULES2
TABLE 16 TO PARAGRAPH (h)—MINIMUM EFFICIENCY STANDARDS FOR DIRECT EXPANSION-DEDICATED OUTDOOR AIR
SYSTEMS
Compliance date:
equipment
manufactured
starting on . . .
Equipment Category
Subcategory
Efficiency level
Direct expansion-dedicated outdoor air systems.
(AC)—Air-cooled without ventilation energy
recovery systems.
(AC w/VERS)—Air-cooled with ventilation energy recovery systems.
(ASHP)—Air-source heat pumps without ventilation energy recovery systems.
(ASHP w/VERS)—Air-source heat pumps
with ventilation energy recovery systems.
(WC)—Water-cooled without ventilation energy recovery systems.
(WC w/VERS)—Water-cooled with ventilation
energy recovery systems.
ISMRE2 = 3.8 ............
May 1, 2024.
ISMRE2 = 5.0 ............
May 1, 2024.
ISMRE2 = 3.8 ............
ISCOP2 = 2.05 ...........
ISMRE2 = 5.0 ............
ISCOP2 = 3.20 ...........
ISMRE2 = 4.7 ............
May 1, 2024.
ISMRE2 = 5.1 ............
May 1, 2024.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00060
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
May 1, 2024.
May 1, 2024.
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
44045
TABLE 16 TO PARAGRAPH (h)—MINIMUM EFFICIENCY STANDARDS FOR DIRECT EXPANSION-DEDICATED OUTDOOR AIR
SYSTEMS—Continued
Equipment Category
(i) Air-cooled, three-phase,
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 Btu/h and
air-cooled, three-phase variable
Subcategory
Efficiency level
(WSHP)—Water-source heat pumps without
ventilation energy recovery systems.
(WSHP w/VERS)—Water-source heat pumps
with ventilation energy recovery systems.
ISMRE2 = 3.8 ............
ISCOP2 = 2.13 ...........
ISMRE2 = 4.6 ............
ISCOP2 = 4.04 ...........
refrigerant flow multi-split air
conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h manufactured on or after
the compliance date listed in tables 17
Compliance date:
equipment
manufactured
starting on . . .
May 1, 2024.
May 1, 2024.
and 18 to this paragraph (i) must meet
the applicable minimum energy
efficiency standard level(s) set forth in
this paragraph (i).
TABLE 17 TO PARAGRAPH (i)—MINIMUM EFFICIENCY STANDARDS FOR AIR-COOLED, THREE-PHASE, COMMERCIAL PACKAGE AIR CONDITIONING AND HEATING EQUIPMENT WITH A COOLING CAPACITY OF LESS THAN 65,000 BTU/H AND
AIR-COOLED, THREE-PHASE, SMALL VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR CONDITIONING AND HEATING
EQUIPMENT WITH A COOLING CAPACITY OF LESS THAN 65,000 BTU/H
Compliance date:
equipment
manufactured
starting on . . .
Equipment type
Cooling capacity
Subcategory
Minimum efficiency
Commercial Package Air Conditioning Equipment.
Commercial Package Air Conditioning Equipment.
Commercial Package Air Conditioning and
Heating Equipment.
Commercial Package Air Conditioning and
Heating Equipment.
VRF Air Conditioners .....................................
VRF Heat Pumps ...........................................
<65,000 Btu/h ............
Split-System ...............
13.0 SEER .................
June 16, 2008.1
<65,000 Btu/h ............
Single-Package ..........
14.0 SEER .................
January 1, 2017.1
<65,000 Btu/h ............
Split-System ...............
January 1, 2017.1
<65,000 Btu/h ............
Single-Package ..........
<65,000 Btu/h ............
<65,000 Btu/h ............
....................................
....................................
14.0 SEER .................
8.2 HSPF ...................
14.0 SEER .................
8.0 HSPF ...................
13.0 SEER .................
13.0 SEER .................
7.7 HSPF ...................
January 1, 2017.1
June 16, 2008.1
June 16, 2008.1
1 And manufactured before January 1, 2025. For equipment manufactured on or after January 1, 2025, see table 18 to this paragraph (i) for
updated efficiency standards.
lotter on DSK11XQN23PROD with RULES2
TABLE 18 TO PARAGRAPH (i)—UPDATED MINIMUM EFFICIENCY STANDARDS FOR AIR-COOLED, THREE-PHASE, COMMERCIAL PACKAGE AIR CONDITIONING AND HEATING EQUIPMENT WITH A COOLING CAPACITY OF LESS THAN 65,000 BTU/
H AND AIR-COOLED, THREE-PHASE, SMALL VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR CONDITIONING AND
HEATING EQUIPMENT WITH A COOLING CAPACITY OF LESS THAN 65,000 BTU/H
Compliance date:
equipment
manufactured
starting on. . .
Equipment type
Cooling capacity
Subcategory
Minimum efficiency
Commercial Package Air Conditioning Equipment.
Commercial Package Air Conditioning Equipment.
Commercial Package Air Conditioning and
Heating Equipment.
Commercial Package Air Conditioning and
Heating Equipment.
Space-Constrained Commercial Package Air
Conditioning Equipment.
Space-Constrained Commercial Package Air
Conditioning Equipment.
Space-Constrained Commercial Package Air
Conditioning and Heating Equipment.
Space-Constrained Commercial Package Air
Conditioning and Heating Equipment.
Small-Duct, High-Velocity Commercial Package Air Conditioning.
< 65,000 Btu/h ...........
Split-System ...............
13.4 SEER2 ...............
January 1, 2025.
< 65,000 Btu/h ...........
Single-Package ..........
13.4 SEER2 ...............
January 1, 2025.
< 65,000 Btu/h ...........
Split-System ...............
January 1, 2025.
< 65,000 Btu/h ...........
Single-Package ..........
≤ 30,000 Btu/h ...........
Split-System ...............
14.3 SEER2 ...............
7.5 HSPF2 .................
13.4 SEER2 ...............
6.7 HSPF2 .................
12.7 SEER2 ...............
≤ 30,000 Btu/h ...........
Single-Package ..........
13.9 SEER2 ...............
January 1, 2025.
≤ 30,000 Btu/h ...........
Split-System ...............
January 1, 2025.
≤ 30,000 Btu/h ...........
Single-Package ..........
< 65,000 Btu/h ...........
Split-System ...............
13.9 SEER2 ...............
7.0 HSPF2 .................
13.9 SEER2 ...............
6.7 HSPF2 .................
13.0 SEER2 ...............
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00061
Fmt 4701
Sfmt 4700
E:\FR\FM\20MYR2.SGM
20MYR2
January 1, 2025.
January 1, 2025.
January 1, 2025.
January 1, 2025.
44046
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 18 TO PARAGRAPH (i)—UPDATED MINIMUM EFFICIENCY STANDARDS FOR AIR-COOLED, THREE-PHASE, COMMERCIAL PACKAGE AIR CONDITIONING AND HEATING EQUIPMENT WITH A COOLING CAPACITY OF LESS THAN 65,000 BTU/
H AND AIR-COOLED, THREE-PHASE, SMALL VARIABLE REFRIGERANT FLOW MULTI-SPLIT AIR CONDITIONING AND
HEATING EQUIPMENT WITH A COOLING CAPACITY OF LESS THAN 65,000 BTU/H—Continued
Cooling capacity
Subcategory
Minimum efficiency
Small-Duct, High-Velocity Commercial Package Air Conditioning and Heating Equipment.
VRF Air Conditioners .....................................
VRF Heat Pumps ...........................................
< 65,000 Btu/h ...........
Split-System ...............
14.0 SEER2 ...............
6.9 HSPF2 .................
January 1, 2025.
< 65,000 Btu/h ...........
< 65,000 Btu/h ...........
....................................
....................................
13.4 SEER2 ...............
13.4 SEER2 ...............
7.5 HSPF2 .................
January 1, 2025.
January 1, 2025.
11. Appendix A to subpart F of part
431 is revised to read as follows:
■
Appendix A to Subpart F of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
Commercial Package Air Conditioning
and Heating Equipment (Excluding AirCooled Equipment With a Cooling
Capacity Less Than 65,000 Btu/h)
lotter on DSK11XQN23PROD with RULES2
Compliance date:
equipment
manufactured
starting on. . .
Equipment type
Note: Prior to May 15, 2025,
representations with respect to the energy
use or efficiency of commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
including compliance certifications, must be
based on testing conducted in accordance
with:
(a) The applicable provisions (appendix A
to subpart F of part 431 for air-cooled
equipment, and table 1 to § 431.96 for watercooled and evaporatively-cooled equipment)
as they appeared in subpart F of 10 CFR part
431, revised as of January 1, 2024; or
(b) This appendix.
Beginning May 15, 2025, and prior to the
compliance date of amended standards for
commercial package air conditioning and
heating equipment (excluding air-cooled
equipment with a cooling capacity less than
65,000 Btu/h) based on integrated
ventilation, economizing, and cooling (IVEC)
and integrated ventilation and heating
efficiency (IVHE) (see § 431.97),
representations with respect to energy use or
efficiency of commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
including compliance certifications, must be
based on testing conducted in accordance
with this appendix.
Beginning on the compliance date of
amended standards for commercial package
air conditioning and heating equipment
(excluding equipment with a cooling
capacity less than 65,000 Btu/h) based on
IVEC and IVHE (see § 431.97),
representations with respect to energy use or
efficiency of commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
including compliance certifications, must be
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
based on testing conducted in accordance
with appendix A1 to this subpart.
Manufacturers may also certify compliance
with any amended energy conservation
standards for commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h)
based on IVEC or IVHE prior to the
applicable compliance date for those
standards (see § 431.97), and those
compliance certifications must be based on
testing in accordance with appendix A1 to
this subpart.
1. Incorporation by Reference
DOE incorporated by reference in § 431.95,
the entire standard for AHRI 340/360–2022
and ANSI/ASHRAE 37–2009. However,
certain enumerated provisions of AHRI 340/
360–2022 and ANSI/ASHRAE 37–2009, as
set forth in this section 1 are inapplicable. To
the extent there is a conflict between the
terms or provisions of a referenced industry
standard and the CFR, the CFR provisions
control.
1.1. AHRI 340/360–2022:
(a) Section 1 Purpose is inapplicable,
(b) Section 2 Scope is inapplicable,
(c) The following subsections of Section 3
Definitions are inapplicable: 3.2 (Basic
Model), 3.4 (Commercial and Industrial
Unitary Air-conditioning Equipment), 3.5
(Commercial and Industrial Unitary Heat
Pump), 3.7 (Double-duct System), 3.8 (Energy
Efficiency Ratio (EER)), 3.12 (Heating
Coefficient of Performance (COPH)), 3.14
(Integrated Energy Efficiency Ratio (IEER)),
3.23 (Published Rating), 3.26 (Single Package
Air-Conditioners), 3.27 (Single Package Heat
Pumps), 3.29 (Split System Air-conditioners),
3.30 (Split System Heat Pump), 3.36 (Year
Round Single Package Air-conditioners),
(d) Section 7 Minimum Data
Requirements for Published Ratings is
inapplicable,
(e) Section 8 Operating Requirements is
inapplicable,
(f) Section 9 Marking and Nameplate Data
is inapplicable,
(g) Section 10 Conformance Conditions is
inapplicable,
(h) Appendix B References—Informative
is inapplicable,
(i) Appendix D Unit Configuration for
Standard Efficiency Determination—
Normative is inapplicable,
PO 00000
Frm 00062
Fmt 4701
Sfmt 4700
(j) Appendix F International Rating
Conditions—Normative is inapplicable,
(k) Appendix G Examples of IEER
Calculations—Informative is inapplicable,
(l) Appendix H Example of Determination
of Fan and Motor Efficiency for Non-standard
Integrated Indoor Fan and Motors—
Informative is inapplicable, and
(m) Appendix I Double-duct System
Efficiency Metrics with Non-Zero Outdoor
Air External Static Pressure (ESP)—
Normative is inapplicable.
1.2. ANSI/ASHRAE 37–2009:
(a) Section 1 Purpose is inapplicable
(b) Section 2 Scope is inapplicable, and
(c) Section 4 Classifications is
inapplicable.
2. General
Determine the applicable energy efficiency
metrics (IEER, EER, and COP) in accordance
with this appendix and the applicable
sections of AHRI 340/360–2022 and ANSI/
ASHRAE 37–2009.
Section 3 of this appendix provides
additional instructions for testing. In cases
where there is a conflict, the language of this
appendix takes highest precedence, followed
by AHRI 340/360–2022, followed by ANSI/
ASHRAE 37–2009. Any subsequent
amendment to a referenced document by the
standard-setting organization will not affect
the test procedure in this appendix, unless
and until the test procedure is amended by
DOE.
3. Test Conditions
The following conditions specified in
Table 6 of AHRI 340/360–2022 apply when
testing to certify to the energy conservation
standards in § 431.97. For cooling mode tests
for equipment subject to standards in terms
of EER, test using the ‘‘Standard Rating
Conditions Cooling’’. For cooling mode tests
for equipment subject to standards in terms
of IEER, test using the ‘‘Standard Rating
Conditions Cooling’’ and the ‘‘Standard
Rating Part-Load Conditions (IEER)’’. For
heat pump heating mode tests for equipment
subject to standards in terms of COP, test
using the ‘‘Standard Rating Conditions (High
Temperature Steady State Heating)’’.
For equipment subject to standards in
terms of EER, representations of IEER made
using the ‘‘Standard Rating Part-Load
Conditions (IEER)’’ in Table 6 of AHRI 340/
360–2022 are optional. For equipment
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
subject to standards in terms of IEER,
representations of EER made using the
‘‘Standard Rating Conditions Cooling’’ in
Table 6 of AHRI 340/360–2022 are optional.
Representations of COP made using the
‘‘Standard Rating Conditions (Low
Temperature Steady State Heating)’’ in Table
6 of AHRI 340/360–2022 are optional and are
not to be used as the basis for determining
compliance with energy efficiency standards
in terms of COP.
12. Add appendix A1 to subpart F of
part 431 to read as follows:
■
lotter on DSK11XQN23PROD with RULES2
Appendix A1 to Subpart F of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
Commercial Package Air Conditioning
and Heating Equipment (Excluding AirCooled Equipment With a Cooling
Capacity Less Than 65,000 Btu/h)
Note: Prior to May 15, 2025,
representations with respect to the energy
use or efficiency of commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
including compliance certifications, must be
based on testing conducted in accordance
with:
(a) The applicable provisions (appendix A
to subpart F of part 431 for air-cooled
equipment, and table 1 to § 431.96 for watercooled and evaporatively-cooled equipment)
as it appeared in subpart F of 10 CFR part
431, revised as of January 1, 2024; or
(b) Appendix A to this subpart.
Beginning May 15, 2025, and prior to the
compliance date of amended standards for
commercial package air conditioning and
heating equipment (excluding air-cooled
equipment with a cooling capacity less than
65,000 Btu/h) based on integrated
ventilation, economizing, and cooling (IVEC)
and integrated ventilation and heating
efficiency (IVHE) (see § 431.97),
representations with respect to energy use or
efficiency of commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
including compliance certifications, must be
based on testing conducted in accordance
with appendix A to this subpart.
Beginning on the compliance date of
amended standards for commercial package
air conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h)
based on IVEC and IVHE (see § 431.97),
representations with respect to energy use or
efficiency of commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h),
including compliance certifications, must be
based on testing conducted in accordance
with this appendix.
Manufacturers may also certify compliance
with any amended energy conservation
standards for commercial package air
conditioning and heating equipment
(excluding air-cooled equipment with a
cooling capacity less than 65,000 Btu/h)
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
based on IVEC or IVHE prior to the
applicable compliance date for those
standards (see § 431.97), and those
compliance certifications must be based on
testing in accordance with this appendix.
1. Incorporation by Reference
DOE incorporated by reference in § 431.95,
the entire standard for AHRI 1340–2023 and
ANSI/ASHRAE 37–2009. However, certain
enumerated provisions of AHRI 1340–2023
and ANSI/ASHRAE 37–2009, as listed in this
section 1 are inapplicable. To the extent there
is a conflict between the terms or provisions
of a referenced industry standard and the
CFR, the CFR provisions control.
1.1. AHRI 1340–2023:
(a) Section 1 Purpose is inapplicable,
(b) Section 2 Scope is inapplicable,
(c) The following subsections of section 3
Definitions are inapplicable: 3.2.2
(Barometric Relief Damper), 3.2.3 (Basic
Model), 3.2.5 (Commercial and Industrial
Unitary Air-conditioner and Heat Pump
Equipment), 3.2.5.1 (Commercial and
Industrial Unitary Air-Conditioning System),
3.2.5.2 (Commercial and Industrial Unitary
Heat Pump System), 3.2.7 (Double-duct
System), 3.2.9 (Desiccant Dehumidification
Component), 3.2.10 (Drain Pan Heater),
3.2.11.1 (Air Economizer), 3.2.12 (Energy
Efficiency Ratio 2), 3.2.13 (Evaporative
Cooling), 3.2.13.1 (Direct Evaporative Cooling
System), 3.2.13.2 (Indirect Evaporative
Cooling System), 3.2.14 (Fresh Air Damper),
3.2.15 (Fire, Smoke, or Isolation Damper),
3.2.17 (Hail Guard), 3.2.19 (Heating
Coefficient of Performance 2 (COP2H)), 3.2.20
(High-Effectiveness Indoor Air Filtration),
3.2.22 (Indoor Single Package Airconditioners), 3.2.23 (Integrated Ventilation,
Economizing, and Cooling Efficiency (IVEC)),
3.2.34 (Integrated Ventilation and Heating
Efficiency (IVHE)), 3.2.29 (Non-standard
Ducted Condenser Fan), 3.2.31.2 (Boost2
Heating Operating Level (B2)), 3.2.34 (Power
Correction Capacitor), 3.2.35 (Powered
Exhaust Air Fan), 3.2.36 (Powered Return Air
Fan), 3.2.37 (Process Heat Recovery, Reclaim,
or Thermal Storage Coil), 3.2.38 (Published
Rating), 3.2.41 (Refrigerant Reheat Coil),
3.2.42 (Single Package Air-conditioner),
3.2.43 (Single Package Heat Pumps), 3.2.44
(Single Package System), 3.2.45 (Sound
Trap), 3.2.46 (Split System), 3.2.51 (Steam or
Hydronic Heat Coils), 3.2.53 (UV Lights),
3.2.55 (Ventilation Energy Recovery System
(VERS)), 3.2.56 (Year Round Single Package
Air-conditioner), 3.2.57 (Year Round Single
Package Heat Pump),
(d) Subsection 5.2 (Optional System
Features) of section 5 Test Requirements is
inapplicable,
(e) The following subsections of section 6
Rating Requirements are inapplicable: 6.4
(Rating Values), 6.5 (Uncertainty), and 6.6
(Verification Testing),
(f) Section 7 Minimum Data
Requirements for Published Ratings is
inapplicable,
(g) Section 8 Operating Requirements is
inapplicable,
(h) Section 9 Marking and Nameplate
Data is inapplicable,
(i) Section 10 Conformance Conditions is
inapplicable,
PO 00000
Frm 00063
Fmt 4701
Sfmt 4700
44047
(j) Appendix B References—Informative
is inapplicable,
(k) Sections D.1 (Purpose) and D.2
(Configuration Requirements) of Appendix D
Unit Configuration for Standard Efficiency
Determination—Normative are inapplicable,
(l) Appendix F International Rating
Conditions—Normative is inapplicable,
(m) Appendix G Example of
Determination of Fan and Motor Efficiency
for Non-standard Integrated Indoor Fan and
Motors—Informative is inapplicable, and
(n) Appendix H Determination of Lowtemperature Cut-in and Cut-out
Temperatures—Normative is inapplicable.
1.2. ANSI/ASHRAE 37–2009:
(a) Section 1 Purpose is inapplicable
(b) Section 2 Scope is inapplicable, and
(c) Section 4 Classifications is
inapplicable.
2. General
For air conditioners and heat pumps,
determine IVEC and IVHE (as applicable) in
accordance with this appendix and the
applicable sections of AHRI 1340–2023 and
ANSI/ASHRAE 37–2009. Representations of
energy efficiency ratio 2 (EER2) and IVHEC
may optionally be made. Representations of
coefficient of performance 2 (COP2) at 5 °F,
17 °F, and 47 °F may optionally be made.
Sections 3 and 4 of this appendix provide
additional instructions for testing. In cases
where there is a conflict, the language of this
appendix takes highest precedence, followed
by AHRI 1340–2023, followed by ANSI/
ASHRAE 37–2009. Any subsequent
amendment to a referenced document by the
standard-setting organization will not affect
the test procedure in this appendix, unless
and until the test procedure is amended by
DOE.
3. Test Conditions
The following conditions specified in
AHRI 1340–2023 apply when testing to
certify to the energy conservation standards
in § 431.97. For cooling mode, use the rating
conditions in Table 7 of AHRI 1340–2023.
For heat pump heating mode tests, use the
rating conditions in Table 23 of AHRI 1340–
2023 and the IVHE building load profile in
Table 22 of AHRI 1340–2023.
Representations of EER2 made using the
‘‘Cooling Bin A’’ conditions in Table 7 of
AHRI 1340–2023 are optional.
Representations of IVHEC made using the
IVHEC Cold Climate building load profile in
Table 22 of AHRI 1340–2023 are optional.
Representations of COP247, COP217, and
COP25 are optional.
4. Tower Fan and Pump Power Rate (TFPPR)
Where equations 8, 10, 11, and 13 to AHRI
1340–2023 call for using the cooling tower
fan and condenser water pump power rate
(TFPPR) for the cooling bin specified in
Table 7 to AHRI 1340–2023, instead use the
TFPPR value for the cooling bin specified in
table 1 to this appendix. Where equation 22
to AHRI 1340–2023 calls for using a value of
0.0094 W/(Btu/h) for TFPPR, instead use a
value of 0.0102 W/(Btu/h).
E:\FR\FM\20MYR2.SGM
20MYR2
44048
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
TABLE 1—TOWER FAN AND PUMP POWER RATE
[TFPPR]
Cooling bin
Cooling Bin A
Cooling Bin B
Cooling Bin C
Cooling Bin D
Tower Fan and Pump Power Rate (TFPPR), W/(Btu/h) .................................
0.0102
0.0099
0.0121
0.0430
5. Additional Heating Operating Level
Provisions
5.1. Boost2 Heating Operating Level
Definition
In place of the boost2 heating operating
level definition in section 3.2.31.2 of AHRI
1340–2023, use the following definition: An
operating level allowed by the controls at
5.0 °F outdoor dry-bulb temperature with a
capacity at 5.0 °F outdoor dry-bulb
temperature that is less than or equal to the
maximum capacity allowed by the controls at
5.0 °F outdoor dry-bulb temperature and
greater than the capacity of:
(a) The boost heating operating level at
5.0 °F outdoor dry-bulb temperature, if there
is an operating level that meets the definition
for boost heating operating level specified in
section 3.2.31.1 of AHRI 1340–2023; or
(b) The high heating operating level at
5.0 °F outdoor dry-bulb temperature, if there
is not an operating level that meets the
definition for boost heating operating level
specified in section 3.2.31.1 of AHRI 1340–
2023.
5.2. Requirements for H5B2 Test in Table 23
to AHRI 1340–2023
In place of the third to last paragraph of
section 6.3.6 of AHRI 1340–2023, use the
following provisions.
Run the H5B2 test in Table 23 of AHRI
1340–2023 only if there is an operating level
allowed by the controls at 5.0 °F that meets
the definition of the boost2 heating operating
level specified in section 5.1 of this
appendix, and the H5B2 test is being used to
determine the capacity at 5.0 °F outdoor drybulb temperature and/or COP25.
If the unit has a boost heating operating
level, run the H5B2 test in Table 23 of AHRI
1340–2023 with an operating level allowed
by the controls at 5.0 °F outdoor dry-bulb
temperature that has a capacity at 5.0 °F
outdoor dry-bulb temperature that is greater
than the capacity of the boost heating
operating level at 5.0 °F outdoor dry-bulb
temperature and less than or equal to the
maximum capacity allowed by the controls at
5.0 °F outdoor dry-bulb temperature.
If the unit does not have a boost heating
operating level, run the H5B2 test in Table
23 of AHRI 1340–2023 with an operating
level allowed by the controls at 5.0 °F
outdoor dry-bulb temperature that has a
capacity at 5.0 °F outdoor dry-bulb
temperature that is greater than the capacity
of the high heating operating level at 5.0 °F
outdoor dry-bulb temperature and less than
or equal to the maximum capacity allowed by
the controls at 5.0 °F outdoor dry-bulb
temperature. Use the indoor airflow that is
used by the controls at 5.0 °F outdoor drybulb temperature when operating at the
chosen operating level.
The H5B2 test shall not be used in the
calculation of IVHE or IVHEC.
5.3. Operating Level Requirements for COP2
Any references to COP2H in AHRI 1340–
2023 shall be considered synonymous with
COP2 as defined in § 431.92. In place of
section 6.3.14.2 of AHRI 1340–2023, use the
following provisions.
To determine COP247, use capacity and
power determined for the H47H test.
To determine COP217, the following
provisions apply. For units without a boost
heating operating level, use capacity and
power determined for the H17H test. For
units with a boost operating level, use
capacity and power determined for the H17B
test.
To determine COP25, the following
provisions apply. For units without a boost
heating operating level and without a boost2
heating operating level, use capacity and
power determined for the H5H test. For units
with a boost heating operating level and
without a boost2 heating operating level, use
capacity and power determined for the H5B
test. For units with a boost2 heating
operating level, use capacity and power
determined for the H5B2 test.
6. Set-Up and Test Provisions for Specific
Components
When testing equipment that includes any
of the features listed in table 2 to this
appendix, test in accordance with the set-up
and test provisions specified in table 2.
TABLE 2—TEST PROVISIONS FOR SPECIFIC COMPONENTS
Component
Description
Air Economizers ................................................
An automatic system that enables a cooling
system to supply outdoor air to reduce or
eliminate the need for mechanical cooling
during mild or cold weather
Barometric Relief Dampers ...............................
An assembly with dampers and means to
automatically set the damper position in a
closed position and one or more open positions to allow venting directly to the outside
a portion of the building air that is returning
to the unit, rather than allowing it to recirculate to the indoor coil and back to the building
An assembly that reduces the moisture content of the supply air through moisture
transfer with solid or liquid desiccants
A heater that heats the drain pan to make certain that water shed from the outdoor coil
during a defrost does not freeze
Water is evaporated into the air entering the
air-cooled condenser to lower the dry-bulb
temperature and thereby increase efficiency
of the refrigeration cycle
Desiccant Dehumidification Components ..........
Drain Pan Heaters .............................................
lotter on DSK11XQN23PROD with RULES2
Test provisions
Evaporative Pre-cooling of Air-cooled Condenser Intake Air.
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00064
Fmt 4701
Sfmt 4700
For any air economizer that is factory-installed, place the economizer in the 100%
return position and close and seal the outside air dampers for testing. For any modular air economizer shipped with the unit but
not factory-installed, do not install the
economizer for testing.
For any barometric relief dampers that are
factory-installed, close and seal the
dampers for testing. For any modular barometric relief dampers shipped with the unit
but not factory-installed, do not install the
dampers for testing.
Disable desiccant dehumidification components for testing.
Disconnect drain pan heaters for testing.
Disconnect the unit from a water supply for
testing i.e., operate without active evaporative cooling.
E:\FR\FM\20MYR2.SGM
20MYR2
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and Regulations
44049
TABLE 2—TEST PROVISIONS FOR SPECIFIC COMPONENTS—Continued
Component
Description
Test provisions
Fire/Smoke/Isolation Dampers ..........................
A damper assembly including means to open
and close the damper mounted at the supply or return duct opening of the equipment
Fresh Air Dampers ............................................
An assembly with dampers and means to set
the damper position in a closed and one
open position to allow air to be drawn into
the equipment when the indoor fan is operating
Hail Guards ........................................................
A grille or similar structure mounted to the outside of the unit covering the outdoor coil to
protect the coil from hail, flying debris and
damage from large objects
Indoor air filters with greater air filtration effectiveness than the filters used for testing
A capacitor that increases the power factor
measured at the line connection to the
equipment
A heat exchanger located inside the unit that
conditions the equipment’s supply air using
energy transferred from an external source
using a vapor, gas, or liquid
A heat exchanger located downstream of the
indoor coil that heats the supply air during
cooling operation using high pressure refrigerant in order to increase the ratio of moisture removal to cooling capacity provided by
the equipment
Coils used to provide supplemental heating
For any fire/smoke/isolation dampers that are
factory-installed, set the dampers in the fully
open position for testing. For any modular
fire/smoke/isolation dampers shipped with
the unit but not factory-installed, do not install the dampers for testing.
For any fresh air dampers that are factory-installed, close and seal the dampers for testing. For any modular fresh air dampers
shipped with the unit but not factory-installed, do not install the dampers for testing.
Remove hail guards for testing.
High-Effectiveness Indoor Air Filtration .............
Power Correction Capacitors ............................
Process Heat recovery/Reclaim Coils/Thermal
Storage.
Refrigerant Reheat Coils ...................................
Steam/Hydronic Heat Coils ...............................
UV Lights ...........................................................
Ventilation Energy Recovery System (VERS) ..
A lighting fixture and lamp mounted so that it
shines light on the indoor coil, that emits ultraviolet light to inhibit growth of organisms
on the indoor coil surfaces, the condensate
drip pan, and/other locations within the
equipment
An assembly that preconditions outdoor air
entering the equipment through direct or indirect thermal and/or moisture exchange
with the exhaust air, which is defined as the
building air being exhausted to the outside
from the equipment
Test with the standard filter.
Remove power correction capacitors for testing.
Disconnect the heat exchanger from its heat
source for testing.
De-activate refrigerant reheat coils for testing
so as to provide the minimum (none if possible) reheat achievable by the system controls.
Test with steam/hydronic heat coils in place
but providing no heat.
Turn off UV lights for testing.
For any VERS that is factory-installed, place
the VERS in the 100% return position and
close and seal the outside air dampers and
exhaust air dampers for testing, and do not
energize any VERS subcomponents (e.g.,
energy recovery wheel motors). For any
VERS module shipped with the unit but not
factory-installed, do not install the VERS for
testing.
[FR Doc. 2024–08543 Filed 5–17–24; 8:45 am]
lotter on DSK11XQN23PROD with RULES2
BILLING CODE 6450–01–P
VerDate Sep<11>2014
19:59 May 17, 2024
Jkt 262001
PO 00000
Frm 00065
Fmt 4701
Sfmt 9990
E:\FR\FM\20MYR2.SGM
20MYR2
Agencies
[Federal Register Volume 89, Number 98 (Monday, May 20, 2024)]
[Rules and Regulations]
[Pages 43986-44049]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2024-08543]
[[Page 43985]]
Vol. 89
Monday,
No. 98
May 20, 2024
Part II
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Air-Cooled,
Evaporatively-Cooled, and Water-Cooled Commercial Package Air
Conditioners and Heat Pumps; Final Rule
Federal Register / Vol. 89, No. 98 / Monday, May 20, 2024 / Rules and
Regulations
[[Page 43986]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE-2023-BT-TP-0014]
RIN 1904-AD93
Energy Conservation Program: Test Procedure for Air-Cooled,
Evaporatively-Cooled, and Water-Cooled Commercial Package Air
Conditioners and Heat Pumps
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (``DOE'') is amending the
Federal test procedures for air-cooled commercial package air
conditioners and heat pumps with a rated cooling capacity greater than
or equal to 65,000 Btu/h, evaporatively-cooled commercial package air
conditioners, and water-cooled commercial package air conditioners to
incorporate by reference the latest versions of the applicable industry
test standards. Specifically, DOE is amending the current test
procedure for this equipment for measuring the current cooling and
heating metrics--integrated energy efficiency ratio (``IEER'') and
coefficient of performance (``COP''), respectively; and establishing a
new test procedure for this equipment that adopts two new metrics--
integrated ventilation, economizer, and cooling (``IVEC'') and
integrated ventilation and heating efficiency (``IVHE''). Testing to
the IVEC and IVHE metrics will not be required until such time as
compliance is required with any amended energy conservation standard
based on the new metrics. Additionally, DOE is amending certain
provisions of DOE's regulations related to representations and
enforcement for the subject equipment.
DATES: The effective date of this rule is August 5, 2024. The
amendments will be mandatory for testing the subject equipment starting
May 15, 2025.
The incorporation by reference of certain material listed in this
rule is approved by the Director of the Federal Register on August 5,
2024. The incorporation by reference of certain other materials listed
in this rule were approved by the Director of the Federal Register as
of January 22, 2016.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting webinar attendee lists and transcripts, comments, and other
supporting documents/materials, is available for review at
www.regulations.gov under docket number EERE-2023-BT-TP-0014. All
documents in the docket are listed in the www.regulations.gov index.
However, not all documents listed in the index may be publicly
available, such as those containing information that is exempt from
public disclosure.
A link to the docket web page can be found at www.regulations.gov/docket/EERE-2023-BT-TP-0014. The docket web page contains instructions
on how to access all documents, including public comments, in the
docket.
For further information on how to review the docket, contact the
Appliance and Equipment Standards Program staff at (202) 287-1445 or by
email: [email protected].
FOR FURTHER INFORMATION CONTACT: Mr. Troy Watson, U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Office, EE-5B, 1000 Independence Avenue SW, Washington, DC
20585-0121. Telephone: (240) 449-9387. Email:
[email protected].
Mr. Eric Stas, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC 20585-0121.
Telephone: (202) 586-4798. Email: [email protected].
For further information on how to review the docket, contact the
Appliance and Equipment Standards Program staff at (202) 287-1445 or by
email: [email protected].
SUPPLEMENTARY INFORMATION: DOE maintains a previously approved
incorporation by reference and incorporates by reference the following
industry standards into parts 429 and 431:
AHRI Standard 340/360-2022 (I-P), 2022 Standard for Performance
Rating of Commercial and Industrial Unitary Air-conditioning and Heat
Pump Equipment, AHRI-approved January 26, 2022 (``AHRI 340/360-2022'').
AHRI Standard 1340-2023 (I-P), 2023 Standard for Performance Rating
of Commercial and Industrial Unitary Air-conditioning and Heat Pump
Equipment, AHRI-approved November 16, 2023 (``AHRI 1340-2023'').
Copies of AHRI 340/360-2022 and AHRI 1340-2023 can be obtained from
the Air-Conditioning, Heating, and Refrigeration Institute (``AHRI''),
2311 Wilson Blvd., Suite 400, Arlington, VA 22201, (703) 524-8800, or
online at: www.ahrinet.org/standards/search-standards.
ANSI/ASHRAE Standard 37-2009, Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment,
ASHRAE-approved June 24, 2009 (``ANSI/ASHRAE 37-2009'').
Copies of ANSI/ASHRAE 37-2009 can be obtained from the American
Society of Heating, Refrigerating and Air-Conditioning Engineers
(``ASHRAE''), 180 Technology Parkway NW, Peachtree Corners, GA 30092,
(404) 636-8400, or online at: www.ashrae.org.
See section IV.N of this document for a further discussion of these
standards.
Table of Contents
I. Synopsis of the Final Rule
II. Authority and Background
A. Authority
B. Background
III. Discussion
A. Scope of Applicability
B. Definitions
1. CUAC and CUHP Definition
2. Basic Model Definition
3. Double-Duct Definition
4. Metric Definitions
C. Updates to Industry Standards
1. AHRI 340/360
2. AHRI 1340
3. ASHRAE 37
D. Term Sheet Recommendations and Metrics
1. IVEC
2. IVHE
E. DOE Adopted Test Procedures and Comments Received
1. Overall
2. Double-Duct Systems
3. ECUACs and WCUACs
a. Overall
b. ESP Requirements for ECUACs and WCUACs
c. ECUAC and WCUAC Test Temperatures and WCUAC Heat Rejection
Components
4. IVHE for Colder Climates
5. Test Conditions Used for Current Metrics in Appendix A
6. Test Conditions Used for New Metrics in Appendix A1
7. Provisions Introduced in the AHRI 1340-202X Draft
a. Cooling Weighting Factors Adjustment
b. ESP Testing Target Calculation
c. Test Instructions for Splitting ESP Between Return and Supply
Duct
d. Default Fan Power and Maximum Pressure Drop for Coil-Only
Systems
e. Component Power Measurement
f. Non-Standard Low-Static Indoor Fan Motors
g. IVHE Equations
8. Heating Test Provisions Not Included in the AHRI 1340-202X
Draft
a. General
b. Definitions of Heating Operating Levels
c. Boost2 Heating Operating Level and COP25
d. Extrapolation of Boost Heating Operating Level to 21 [deg]F
e. Operating Levels Used for Optional COP217
Representations
9. Test Procedure Revisions Recommended for a Future Rulemaking
F. Configuration of Unit Under Test
1. Summary
2. Background
[[Page 43987]]
3. Proposed Approach for Exclusion of Certain Components
a. Components Addressed Through Test Provisions of 10 CFR Part
431, Subpart F, Appendices A and A1
b. Components Addressed Through Representation Provisions of 10
CFR 429.43
c. Enforcement Provisions of 10 CFR 429.134
d. Testing Specially Built Units That Are Not Distributed in
Commerce
4. Updates in AHRI 1340-2023
5. Comments Received and Adopted Provisions
a. Overall Approach
b. Coated Coils
G. Represented Values
1. Cooling Capacity
a. Representations of Cooling Capacity
b. Verification of Cooling Capacity
2. AEDM Tolerance for IVEC and IVHE
3. Minimum Part-Load Airflow
H. Enforcement Procedure for Verifying Cut-In and Cut-Out
Temperatures
I. Organization of the Regulatory Text for CUACs and CUHPs
J. Effective and Compliance Dates
K. Test Procedure Costs and Impact
1. Appendix A
2. Appendix A1
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866, 13563, and 14094
B. Review Under the Regulatory Flexibility Act
1. Estimate of Small Entities Regulated
2. Description and Estimate of Compliance Requirements
a. Cost and Compliance Associated With Appendix A
b. Cost and Compliance Associated With Appendix A1
3. Significant Alternatives to the Rule
4. Certification Statement
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by Reference
V. Approval of the Office of the Secretary
I. Synopsis of the Final Rule
In this final rule, DOE updates its test procedures for CUACs and
CUHPs by: (1) updating the reference in the Federal test procedure to
the most recent version of the industry test procedure, AHRI 340/360-
2022, for measuring integrated energy efficiency ratio (``IEER''),
energy efficiency ratio (``EER''), and coefficient of performance
(``COP''), consistent with the latest version of ASHRAE Standard 90.1;
and (2) establishing a new test procedure that references a new
industry test procedure, AHRI 1340-2023, which is consistent with
recommendations from the ACUAC and ACUHP Working Group TP Term Sheet,
including ones for the adoption of new efficiency metrics (i.e.,
integrated ventilation, economizer, and cooling (``IVEC'') and
integrated ventilation and heating efficiency (``IVHE'')) and new
testing requirements.
To implement the changes, DOE is: (1) amending appendix A to
incorporate by reference AHRI 340/360-2022 for CUACs and CUHPs, while
maintaining the current efficiency metrics (i.e., EER, IEER, and COP);
and (2) adding a new appendix A1 to subpart F of 10 CFR part 431. At 10
CFR 431.96, ``Uniform test method for the measurement of energy
efficiency of commercial air conditioners and heat pumps,'' DOE is
listing appendix A1 as the applicable test method for CUACs and CUHPs
for any subsequent energy conservation standards denominated in terms
of IVEC and IVHE. Appendix A1 utilizes AHRI 1340-2023, including the
new IVEC and IVHE efficiency metrics recommended by the ACUAC and ACUHP
Working Group TP Term Sheet. Use of appendix A1 will not be required
until such time as compliance is required with any amended energy
conservation standard based on the new metrics, should DOE adopt such
standards. After the date on which compliance with appendix A1 is
required, appendix A will no longer be used as part of the Federal test
procedure. DOE is also amending certain provisions within DOE's
regulations for representation and enforcement consistent with the test
procedure amendments.
Table I-1 summarizes the adopted amendments to the DOE test
procedure for CUACs and CUHPs, the test procedure provision prior to
the amendment, and the reason for each adopted change.
[[Page 43988]]
[GRAPHIC] [TIFF OMITTED] TR20MY24.126
DOE has determined that the amendments to appendix A will not alter
the measured efficiency of CUACs and CUHPs or require retesting or
recertification solely as a result of DOE's adoption of the amendments
to the test procedure. Additionally, DOE has determined that the
amendments to appendix A will not increase the cost of testing.
Representations of energy use or energy efficiency will be required to
be based on testing in accordance with the amended test procedure in
appendix A beginning 360 days after the date of publication of this
test procedure final rule in the Federal Register.
DOE has determined that the new test procedure at appendix A1 will
alter the measured efficiency of CUACs and CUHPs and, as a result,
manufacturers would need to retest, or rerun the alternative efficiency
determination method where allowed, prior to making any representations
under the test procedure in appendix A1. Cost estimates for retesting
are discussed in section III.K of this document. As discussed, use of
appendix A1 will not be required until the compliance date of any
amended energy conservation standard denominated in terms of the new
metrics in appendix A1, should DOE adopt such standards.
The amendments to representation requirements in 10 CFR 429.43 will
not be required until either 360 days after publication in the Federal
Register of this test procedure final rule or beginning on the
compliance date of amended standards for CUACs and CUHPs based on IVEC
and IVHE (as applicable), depending on the specific provisions.
The effective date for the amended test procedures adopted in this
final rule is 75 days after publication of this document in the Federal
Register.
II. Authority and Background
Small, large, and very large commercial package air conditioning
and heating equipment are included in the list of ``covered equipment''
for which DOE is authorized to establish and amend energy conservation
standards and test procedures. (42 U.S.C. 6311(1)(B)-(D)) Commercial
package air conditioning and heating equipment includes as equipment
categories air-cooled commercial unitary air conditioners with a rated
cooling capacity greater than or equal to 65,000 Btu/h (``ACUACs'') and
air-cooled commercial unitary heat pumps with a rated cooling capacity
greater than or equal to 65,000 Btu/h (``ACUHPs''), evaporatively-
cooled commercial unitary air conditioners (``ECUACs''), and water-
cooled commercial unitary air conditioners (``WCUACs''), which are the
subject of this final rule.\1\ (ECUACs, WCUACs, ACUACs, and ACUHPs,
which includes double-duct equipment, are collectively referred to as
``CUACs and CUHPs'' in this document.) DOE's test procedures for CUACs
and CUHPs are currently prescribed at title 10 of the Code of Federal
Regulations (``CFR''), part 431, subpart F, Sec. 431.96, table 1. The
following sections discuss DOE's
[[Page 43989]]
authority to establish and amend test procedures for CUACs and CUHPs
and relevant background information regarding DOE's amendments to the
test procedures for this equipment.
---------------------------------------------------------------------------
\1\ While ACUACs with a rated cooling capacity less than 65,000
Btu/h are included in the broader category of CUACs, they are not
addressed in this final rule. The test procedure for ACUACs with
rated cooling capacity less than 65,000 Btu/h have been addressed in
a separate rulemaking: see Docket No. EERE-2017-BT-TP-0031. All
references within this final rule to ACUACs and ACUHPs exclude
equipment with rated cooling capacity less than 65,000 Btu/h.
---------------------------------------------------------------------------
A. Authority
The Energy Policy and Conservation Act, Public Law 94-163 (42
U.S.C. 6291-6317, as codified), as amended (``EPCA''),\2\ authorizes
DOE to regulate the energy efficiency of a number of consumer products
and certain industrial equipment. Title III, Part C \3\ of EPCA, added
by Public Law 95-619, Title IV, section 441(a), established the Energy
Conservation Program for Certain Industrial Equipment, which sets forth
a variety of provisions designed to improve energy efficiency. This
covered equipment includes small, large, and very large commercial
package air conditioning and heating equipment. (42 U.S.C. 6311(1)(B)-
(D)) Commercial package air conditioning and heating equipment includes
CUACs and CUHPs, the subject of this document.
---------------------------------------------------------------------------
\2\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020), which reflect the last statutory amendments that impact
Parts A and A-1 of EPCA.
\3\ For editorial reasons, upon codification in the U.S. Code,
Part C was redesignated Part A-1.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) testing; (2) labeling; (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. Relevant
provisions of EPCA include definitions (42 U.S.C. 6311), energy
conservation standards (42 U.S.C. 6313), test procedures (42 U.S.C.
6314), labeling provisions (42 U.S.C. 6315), and the authority to
require information and reports from manufacturers (42 U.S.C. 6316; 42
U.S.C. 6296).
The Federal testing requirements consist of test procedures that
manufacturers of covered equipment must use as the basis for: (1)
certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted pursuant to EPCA (42 U.S.C.
6316(b); 42 U.S.C. 6296), and (2) making other representations about
the efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE
uses these test procedures to determine whether the equipment complies
with relevant standards promulgated under EPCA.
Federal energy efficiency requirements for covered equipment
established under EPCA generally supersede State laws and regulations
concerning energy conservation testing, labeling, and standards. (42
U.S.C. 6316(a) and (b); 42 U.S.C. 6297) DOE may, however, grant waivers
of Federal preemption in limited circumstances for particular State
laws or regulations, in accordance with the procedures and other
provisions of EPCA. (42 U.S.C. 6316(b)(2)(D))
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered equipment. Specifically, EPCA requires that any test procedures
prescribed or amended under this section must be reasonably designed to
produce test results which reflect energy efficiency, energy use, or
estimated annual operating cost of a given type of covered equipment
(or class thereof) during a representative average use cycle (as
determined by the Secretary) and requires that such test procedures not
be unduly burdensome to conduct. (42 U.S.C. 6314(a)(2)-(3))
EPCA generally requires that, at least once every seven years, DOE
evaluate test procedures for each type of covered equipment, including
CUACs and CUHPs, to determine whether amended test procedures would
more accurately or fully comply with the requirements for the test
procedures to not be unduly burdensome to conduct and be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs during a representative average use
cycle. (42 U.S.C. 6314(a)(1)-(3)) DOE refers to these provisions as the
``lookback'' provisions and rulemakings conducted under these
provisions as ``lookback'' rulemakings.
Specific to certain commercial equipment, including CUACs and
CUHPs, EPCA requires that the test procedures be those generally
accepted industry testing procedures or rating procedures developed or
recognized by AHRI or ASHRAE, as referenced in ASHRAE Standard 90.1,
``Energy Standard for Buildings Except Low-Rise Residential Buildings''
(``ASHRAE Standard 90.1''). (42 U.S.C. 6314(a)(4)(A)) Further, if such
an industry test procedure is amended, DOE must update its test
procedure to be consistent with the amended industry test procedure
unless DOE determines, by rule published in the Federal Register and
supported by clear and convincing evidence, that the amended test
procedure would not meet the requirements in 42 U.S.C. 6314(a)(2) and
(3) related to representative use and test burden, in which case DOE
may establish an amended test procedure that does satisfy those
statutory provisions. (42 U.S.C. 6314(a)(4)(B) and (C)) DOE refers to
these provisions as the ``ASHRAE trigger'' provisions and rulemakings
conducted under these provisions as ``ASHRAE trigger'' rulemakings. As
noted in the recent update to DOE's procedures, interpretations, and
policies for consideration of new or amended energy conservation
standards and test procedures, DOE considers an ASHRAE trigger to occur
only when ASHRAE Standard 90.1 is updated to include an amended
industry test procedure, and that referenced test procedure includes
amendments relative to the existing DOE test procedure. 89 FR 24340,
24351 (April 8, 2024).
Whether pursuant to the lookback provision or the trigger
provision, if DOE determines that a test procedure amendment is
warranted, the Department must publish proposed test procedures in the
Federal Register, and afford interested persons an opportunity (of not
less than 45 days duration) to present oral and written data, views,
and arguments on the proposed test procedures. (42 U.S.C. 6314(b)) If
DOE determines that test procedure revisions are not appropriate, DOE
must publish in the Federal Register its determination not to amend the
test procedures. (42 U.S.C. 6314(a)(1)(A)(ii))
DOE is publishing this final rule in satisfaction of its
aforementioned statutory obligations under EPCA. Specifically, in
accordance with the ASHRAE trigger provisions at 42 U.S.C.
6314(a)(4)(B), DOE is updating appendix A to reference the most recent
version of the industry test procedure, AHRI 340/360-2022, which was
adopted in ASHRAE Standard 90.1-2022, and which includes amendments
relative to the existing Federal test procedure at appendix A to
subpart F to 10 CFR part 431.\4\ Pursuant to section 6314(a)(4)(B), DOE
also evaluated whether AHRI 340/360-2022 could provide representative
results for the new efficiency metrics recommended by the Working Group
(i.e., IVEC and IVHE). While AHRI 340/360-2022 provides representative
results for the current energy efficiency metrics, IEER, EER, and COP,
it does not include, among other things, operating modes other than
mechanical-cooling-only operation in the cooling metric, part-load
heating tests, higher ESP requirements, or crankcase heater operation,
which are integral to the IVEC and IVHE metrics recommended
[[Page 43990]]
by the Working Group. A more complete discussion of the differences
between the current efficiency metrics and the IVEC and IVHE efficiency
metrics can be found in section III.D. Accordingly, as detailed below,
DOE has determined, supported by clear and convincing evidence, that
AHRI 340/360-2022 cannot provide representative energy use results for
the IVEC and IVHE efficiency metrics.
---------------------------------------------------------------------------
\4\ As discussed in section I.B of this document, DOE was also
triggered by updated industry test procedures in ASHRAE Standard
90.1-2016 and ASHRAE Standard 90.1-2019, both of which included
amendments relative to the existing Federal test procedure. However,
ASHRAE Standard 90.1-2022, and its referenced industry test
procedure, AHRI 340/360-2022, supersedes these previous versions.
---------------------------------------------------------------------------
As a result, consistent with 42 U.S.C. 6314(a)(4)(C), DOE is
establishing a new test procedure, appendix A1, to measure energy use
for the IVEC and IVHE efficiency metrics. DOE has determined that
appendix A1 is reasonably designed to reflect energy use for the IVEC
and IVHE efficiency metrics during a representative average use cycle
without being unduly burdensome to conduct. (See 42 U.S.C.
6314(a)(4)(C); id. section 6314 (a)(2)) In particular, DOE notes that
appendix A1 includes: (1) a more mathematically accurate representation
of cooling efficiency; (2) an integrated heating metric rather than the
single-point full-load COP metric, which includes performance at
multiple outdoor air temperatures as well as other operating modes not
previously accounted for in the COP metric (i.e., part-load heating,
heating-season ventilation hours, unoccupied no-load hours, and
supplemental electric resistance heat operation); (3) operating modes
other than mechanical-cooling-only operation in the cooling metric
(i.e., integrated mechanical and economizer cooling, economizer-only
cooling, cooling season ventilation, unoccupied no-load hours); (4)
higher external static pressure (``ESP'') requirements; (5) crankcase
heater operation; and (6) oversizing of units in field installations.
As DOE has determined that the updated version of the industry test
procedure, AHRI 340/360-2022, adopted in appendix A is more
representative than the previous version of the test procedure
referenced in appendix A (because it would more fully comply with the
requirements that the test procedure be not unduly burdensome to
conduct and be reasonably designed to produce test results that reflect
energy efficiency, energy use, and estimated operating costs during a
representative average use cycle) and because the test procedure
adopted in appendix A1 is more representative for the new IVEC and IVHE
metrics, this rulemaking also satisfies DOE's obligations under the
lookback provisions at 42 U.S.C. 6314(a)(1)(A). For more details on the
improved representativeness of AHRI 340/360-2022, see section III.E of
this document.
B. Background
DOE's existing test procedure for CUACs and CUHPs appears at 10 CFR
431.96 (Uniform test method for the measurement of energy efficiency of
commercial air conditioners and heat pumps). The test procedure for
ACUACs and ACUHPs with a rated cooling capacity of greater than or
equal to 65,000 Btu/h specified in 10 CFR 431.96 references appendix A
to subpart F of part 431 (``Uniform Test Method for the Measurement of
Energy Consumption of Air-Cooled Small (>=65,000 Btu/h), Large, and
Very Large Commercial Package Air Conditioning and Heating Equipment,''
referred to as ``appendix A'' in this document). Appendix A references
certain sections of ANSI/AHRI Standard 340/360-2007, ``2007 Standard
for Performance Rating of Commercial and Industrial Unitary Air-
Conditioning and Heat Pump Equipment,'' approved by ANSI on October 27,
2011 and updated by addendum 1 in December 2010 and addendum 2 in June
2011 (``ANSI/AHRI 340/360-2007''); ANSI/ASHRAE Standard 37-2009,
``Methods of Testing for Rating Electrically Driven Unitary Air-
Conditioning and Heat Pump Equipment'' (``ANSI/ASHRAE 37-2009''); and
specifies other test procedure requirements related to minimum external
static pressure (``ESP''), optional break-in period, refrigerant
charging, setting indoor airflow, condenser head pressure controls,
standard airflow and air quantity, tolerance on capacity at part-load
test points, and condenser air inlet temperature for part-load tests.
The DOE test procedure for ECUACs and WCUACs with a rated cooling
capacity of greater than or equal to 65,000 Btu/h specified in 10 CFR
431.96 incorporates by reference ANSI/AHRI 340/360-2007, excluding
section 6.3 of ANSI/AHRI 340/360-2007 and including paragraphs (c) and
(e) of 10 CFR 431.96.\5\ The DOE test procedure for ECUACs and WCUACs
with a rated cooling capacity of less than 65,000 Btu/h incorporates by
reference ANSI/AHRI Standard 210/240-2008, ``2008 Standard for
Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump
Equipment,'' approved by ANSI on October 27, 2011 and updated by
addendum 1 in June 2011 and addendum 2 in March 2012 (``ANSI/AHRI 210/
240-2008''), excluding section 6.5 of ANSI/AHRI 210/240-2008 and
including paragraphs (c) and (e) of 10 CFR 431.96.
---------------------------------------------------------------------------
\5\ Paragraphs (c) and (e) of 10 CFR 431.96 address optional
break-in provisions and additional provisions regarding set-up,
respectively.
---------------------------------------------------------------------------
On October 26, 2016, ASHRAE published ASHRAE Standard 90.1-2016,
which included updates to the test procedure references for CUACs and
CUHPs (excluding CUACs and CUHPs with a rated cooling capacity less
than 65,000 Btu/h) to reference AHRI Standard 340/360-2015, ``2015
Standard for Performance Rating of Commercial and Industrial Unitary
Air-Conditioning and Heat Pump Equipment'' (``AHRI 340/360-2015'').\6\
This action by ASHRAE triggered DOE's obligations under 42 U.S.C.
6314(a)(4)(B), as outlined previously because AHRI 340/360-2015
included substantive changes compared to the current DOE test procedure
at appendix A to subpart F of 10 CFR part 431. On July 25, 2017, DOE
published a request for information (``RFI'') (``July 2017 TP RFI'') in
the Federal Register to collect information and data to consider
amendments to DOE's test procedures for certain categories of
commercial package air conditioning and heating equipment including
CUACs and CUHPs. 82 FR 34427.
---------------------------------------------------------------------------
\6\ The previous version of ASHRAE Standard 90.1 (i.e., ASHRAE
Standard 90.1-2013) references ANSI/AHRI 340/360-2007.
---------------------------------------------------------------------------
At the time DOE published the July 2017 TP RFI, the applicable
version of ASHRAE Standard 90.1 was the 2016 edition, which referenced
AHRI Standard 340/360-2015, ``2015 Standard for Performance Rating of
Commercial and Industrial Unitary Air-Conditioning and Heat Pump
Equipment'' as the test procedure for CUACs and CUHPs. However, on
October 24, 2019, ASHRAE published ASHRAE Standard 90.1-2019, which
updated the relevant AHRI Standard 340/360 reference to the 2019
edition, ``2019 Standard for Performance Rating of Commercial and
Industrial Unitary Air-Conditioning and Heat Pump Equipment'' (``AHRI
340/360-2019''). This action by ASHRAE again triggered DOE's
obligations under 42 U.S.C. 6314(a)(4)(B), as outlined previously,
because AHRI 340/360-2019 included substantive changes compared to the
current DOE test procedure at appendix A to subpart F of 10 CFR part
431. In January 2022, AHRI published additional updates to its test
procedure standard for CUACs and CUHPs, with the publication of AHRI
Standard 340/360-2022, ``2022 Standard for Performance Rating of
Commercial and Industrial Unitary Air-conditioning and Heat Pump
Equipment'' (``AHRI 340/360-2022''), which DOE references in
[[Page 43991]]
the amended test procedure in appendix A to subpart F of 10 CFR part
431, as established in this final rule.
For ECUACs and WCUACs with a rated cooling capacity less than
65,000 Btu/h, ASHRAE Standard 90.1-2016 references ANSI/AHRI 210/240-
2008, which is referenced by the current Federal test procedure at 10
CFR 431.96 for this equipment. After the publication of the July 2017
RFI, AHRI published AHRI Standard 210/240-2017, ``2017 Standard for
Performance Rating of Unitary Air-conditioning & Air-source Heat Pump
Equipment'' (``AHRI 210/240-2017''). ASHRAE Standard 90.1-2019 updated
its reference to AHRI 210/240-2017 as the test procedure for ECUACs and
WCUACs with rated cooling capacities less than 65,000 Btu/h. This
action by ASHRAE triggered DOE's obligations under 42 U.S.C.
6314(a)(4)(B), as outlined previously, because AHRI 210/240-2017
included substantive changes compared to the current DOE test procedure
for ECUACs and WCUACs with a rated cooling capacity less than 65,000
Btu/h at 10 CFR 431.96. However, after the publication of AHRI 210/240-
2017, AHRI released two updates to that industry standard: (1) AHRI
Standard 210/240-2017 with Addendum 1, ``2017 Standard for Performance
Rating of Unitary Air-conditioning & Air-source Heat Pump Equipment''
(``AHRI 210/240-2017 with Addendum 1''), which was published in April
2019; and (2) AHRI Standard 210/240-2023, ``2023 Standard for
Performance Rating of Unitary Air-conditioning & Air-source Heat Pump
Equipment'' (``AHRI 210/240-2023''), which was published in May
2020.\7\
---------------------------------------------------------------------------
\7\ AHRI 210/240-2023 notes at the beginning of the standard
that while it was first published in May 2020, it establishes a
method to rate residential central air conditioners and heat pumps
consistent with the Federal test procedure for residential central
air conditioners and heat pumps codified in 10 CFR part 430, subpart
B, appendix M1 (``appendix M1''). Appendix M1 was required to be
used coincident with the January 1, 2023 compliance date of Federal
energy conservation standards denominated in terms of seasonal
energy efficiency ratio 2 (``SEER2''), energy efficiency ratio 2
(``EER2''), and heating seasonal performance factor 2 (``HSPF2'').
Therefore, despite being published in May 2020, this version was
named AHRI 210/240-2023.
---------------------------------------------------------------------------
On May 12, 2020, DOE published an RFI in the Federal Register
regarding energy conservation standards for ACUACs, ACUHPs, and
commercial warm air furnaces (``May 2020 ECS RFI''). 85 FR 27941. In
response to the May 2020 ECS RFI, DOE received comments from various
stakeholders, including ones related to the test procedure for ACUACs
and ACUHPs.
On May 25, 2022, DOE published an RFI in the Federal Register
regarding test procedures and energy conservations standards for CUACs
and CUHPs (``May 2022 TP/ECS RFI''). 87 FR 31743.
On July 29, 2022, DOE published in the Federal Register a notice of
intent to establish a working group for commercial unitary air
conditioners and heat pumps (``Working Group'') to negotiate proposed
test procedures and amended energy conservation standards for this
equipment (``July 2022 Notice of Intent''). 87 FR 45703. The Working
Group was established under the Appliance Standards and Rulemaking
Federal Advisory Committee (``ASRAC'') in accordance with the Federal
Advisory Committee Act (FACA) (5 U.S.C. App 2) and the Negotiated
Rulemaking Act (``NRA'') (5 U.S.C. 561-570, Pub. L. 104-320). The
purpose of the Working Group was to discuss, and if possible, reach
consensus on recommended amendments to the test procedures and energy
conservation standards for ACUACs and ACUHPs. The Working Group
consisted of 14 voting members, including DOE. (See appendix A, Working
Group Members, to Document No. 65 in Docket No. EERE-2022-BT-STD-0015)
On December 15, 2022, the Working Group signed a term sheet of
recommendations regarding ACUAC and ACUHP test procedures to be
submitted to ASRAC, the contents of which are referenced throughout
this final rule (referred to hereafter as the ``ACUAC and ACUHP Working
Group TP Term Sheet''). (See Id.) The ACUAC and ACUHP Working Group TP
Term Sheet was approved by ASRAC on March 2, 2023. These
recommendations are discussed further in section III.D of this final
rule.
In January 2023, ASHRAE published ASHRAE Standard 90.1-2022, which
included updates to the test procedure references for CUACs and CUHPs
with cooling capacities greater than or equal to 65,000 Btu/h,
specifically referencing AHRI 340/360-2022. For ECUACs and WCUACs with
capacities less than 65,000 Btu/h, ASHRAE Standard 90.1-2022 references
AHRI 210/240-2023. Notably, ECUACs and WCUACs with a rated cooling
capacity less than 65,000 Btu/h were removed from the scope of AHRI
210/240-2023 and are instead included in the scope of AHRI 340/360-
2022.\8\ DOE discusses this change in scope to the industry test
procedure and comments received related to ECUACs and WCUACs with a
cooling capacity less than 65,000 Btu/h in section III.E.3 of this
final rule. These actions by ASHRAE again triggered DOE's obligations
under 42 U.S.C. 6314(a)(4)(B) for ACUACs and ACUHPs, as outlined
previously, because AHRI 340/360-2022 again included substantive
changes compared to the current DOE test procedure at appendix A to
subpart F of 10 CFR 431. While DOE was triggered previously with the
publication of ASHRAE 90.1-2016 and ASHRAE 90.1-2019, the latest
version, ASHRAE 90.1-2022, and its referenced industry test procedure,
AHRI 340/360-2022, supersedes these previous versions. Therefore, in
this final rule DOE evaluated the amendments under ASHRAE 90.1-2022
(i.e., AHRI 340/360-2022) relative to the current Federal test
procedures for the CUACs and CUHPs.
---------------------------------------------------------------------------
\8\ ECUACs and WCUACs with a rated cooling capacity greater than
or equal to 65,000 Btu/h are included in the scope of ANSI/AHRI 340/
360-2007 and continue to be included in scope of the latest version
of AHRI 340/360 (i.e., AHRI 340/360-2022).
---------------------------------------------------------------------------
DOE published a notice of proposed rulemaking (``NOPR'') in the
Federal Register on August 17, 2023, presenting DOE's proposals to
amend the CUAC and CUHP test procedure (``August 2023 TP NOPR''). 88 FR
56392. The August 2023 TP NOPR also summarized and responded to
comments pertaining to test procedures for CUACs and CUHPs received in
response to the July 2017 TP RFI, the May 2020 ECS RFI, and the May
2022 TP/ECS RFI. Id. DOE held a public webinar related to the August
2023 TP NOPR on September 7, 2023 (hereafter, the ``NOPR public
webinar'').
DOE received comments in response to the August 2023 TP NOPR from
the interested parties listed in Table II-1, along with each
commenter's abbreviated name used throughout this final rule.
Discussion of relevant comments and DOE's responses are provided in
appropriate sections of this document.
[[Page 43992]]
[GRAPHIC] [TIFF OMITTED] TR20MY24.127
A parenthetical reference at the end of a comment quotation or
paraphrase provides the location of the item in the public record.\9\
To the extent that interested parties have provided written comments
that are substantively consistent with any oral comments provided
during the September 7, 2023 NOPR public webinar, DOE cites the written
comments throughout this final rule. DOE did not identify any oral
comments provided during the NOPR public webinar that are not
substantively addressed by written comments.
---------------------------------------------------------------------------
\9\ The parenthetical reference provides a reference for
information located in the docket of DOE's rulemaking to develop
test procedures for CUACs and CUHPs. (Docket No. EERE-2023-BT-TP-
0014, which is maintained at www.regulations.gov) The references are
arranged as follows: (commenter name, comment docket ID number, page
of that document).
---------------------------------------------------------------------------
In response to the August 2023 TP NOPR, DOE received multiple
comments regarding energy conservation standards for CUACs and CUHPs,
particularly regarding standards for ECUACs, WCUACs, and double-duct
systems. Comments regarding energy conservation standards are outside
the scope of consideration for this test procedure rulemaking and are
not addressed in this final rule. Topics related to energy conservation
standards for CUACs and CUHPs would be addressed in separate rulemaking
processes.
Following the publication of the August 2023 TP NOPR, AHRI
published AHRI Standard 1340-2023, ``2023 Standard for Performance
Rating of Commercial and Industrial Unitary Air-conditioning and Heat
Pump Equipment'' (``AHRI 1340-2023''). This is an update to AHRI
Standard 340/360 that incorporates the recommendations in the ACUAC and
ACUHP Working Group TP Term Sheet. This updated industry standard has
not yet been adopted in ASHRAE Standard 90.1, and as such does not
constitute an ASHRAE trigger, as outlined previously.
III. Discussion
In the following sections, DOE outlines certain amendments to its
test procedures for CUACs and CUHPs. For each amendment, DOE provides
relevant background information, explains why the amendment is
necessary, discusses relevant public comments, and discusses the
approach DOE has implemented.
A. Scope of Applicability
This rulemaking applies to ACUACs and ACUHPs with a rated cooling
capacity greater than or equal to 65,000 Btu/h, including double-duct
air conditioners and heat pumps, as well as ECUACs and WCUACs of all
capacities. Definitions that apply to CUACs and CUHPs are discussed in
section III.B of this final rule.
DOE's regulations for CUACs and CUHPs cover both single-package
units and split systems. See the definition of ``commercial package
air-conditioning and heating equipment'' at 10 CFR 431.92. A split
system consists of a condensing unit--which includes a condenser coil,
condenser fan and motor, and compressor--that is paired with a separate
component that includes an evaporator coil to form a complete
refrigeration circuit for space conditioning. One application for
[[Page 43993]]
condensing units is to be paired with an air handler (which includes an
evaporator coil), such that the combined system (i.e., the condensing
unit with air handler) meets the definition of a split system CUAC or
CUHP. It should be pointed out that AHRI has a certification program
for unitary large equipment that includes certification of CUACs,
CUHPs, and condensing units. DOE notes that as part of the AHRI
certification program for unitary large equipment, manufacturers who
sell air-cooled condensing units with a rated cooling capacity greater
than or equal to 65,000 Btu/h and less than 135,000 Btu/h must certify
condensing units as a complete system (i.e., paired with an air
handler) according to the AHRI 340/360 test procedure.\10\ However, for
condensing units with a rated cooling capacity greater than or equal to
135,000 Btu/h and less than 250,000 Btu/h, the AHRI certification
program allows manufacturers to certify condensing units as a complete
system according to AHRI 340/360 or optionally certify as a condensing
unit only according to AHRI Standard 365, ``Standard for Performance
Rating of Commercial and Industrial Unitary Air-Conditioning Condensing
Units'' (``AHRI 365'').
---------------------------------------------------------------------------
\10\ See appendix A of the AHRI Unitary Large Equipment
Certification Program Operations Manual (January 2024). This can be
found at www.ahrinet.org/system/files/2023-10/ULE_OM.pdf.
---------------------------------------------------------------------------
In the August 2023 TP NOPR, DOE emphasized that these AHRI testing
and certification requirements differ from the Federal test procedure
at 10 CFR 431.96, which requires testing to ANSI/AHRI 340/360-2007 and
does not permit certifying to DOE as a condensing unit only according
to AHRI 365. 88 FR 56392, 56398-56399 (August 17, 2023). Additionally,
the AHRI certification program does not include unitary split systems
or condensing units with cooling capacities above 250,000 Btu/h,
whereas the Federal test procedure and standards (codified at 10 CFR
431.96 and 431.97, respectively) cover all CUACs and CUHPs with cooling
capacities up to 760,000 Btu/h. Once again, in the August 2023 TP NOPR,
DOE emphasized that condensing unit models distributed in commerce with
air handlers with cooling capacities up to 760,000 Btu/h are covered as
commercial package air-conditioning and heating equipment (see
definition at 10 CFR 431.92), and as such, they are subject to the
Federal regulations specified for CUACs and CUHPs regarding test
procedures (10 CFR 431.96), energy conservation standards (10 CFR
431.97), and certification and representation requirements (10 CFR
429.43). 88 FR 56392, 56398-56399 (August 17, 2023).
In response to the August 2023 TP NOPR, DOE received several
comments regarding DOE's clarification of coverage of condensing units.
Trane commented that single-package and split-system equipment are
included in the DOE regulation, but stated that the AHRI certification
program structure specific to split systems exists for several reasons.
(Trane, No. 14 at p. 2) Trane stated that split systems between 65,000
Btu/h and 250,000 Btu/h are often matched sets, but split systems
between 135,000 Btu/h to 250,000 Btu/h may be installed in applications
where a stand-alone condenser is matched in the field with a non-
matched air-handling unit, which Trane commented warrants a separate
stand-alone condenser rating. Trane stated that in larger split-system
applications (with capacities greater than 250,000 Btu/h) condensing
units are often paired with: (1) semi-custom and custom air-handling
units that are unique to that installation; (2) more than one air-
handling unit, or (3) air-handling units manufactured by different HVAC
manufacturers, or the system is built up in the field and all controls
for the system are installed on site. Trane asserted that even
considering only the air handlers offered by a single manufacturer,
there would be thousands of condenser and air handler combinations that
would require testing, alternative efficiency determination method
(``AEDM'') development, and certification. Trane also stated that in
split-system replacements, condensing units are often replaced more
frequently than the air-handling unit. Id.
AHRI commented that certifying condensing units as a complete
system (paired with an air handler) is appropriate for the capacity
range between 65,000 and 135,000 Btu/h, but that rating models with
capacities greater than or equal to 135,000 Btu/h as either a complete
system (using AHRI 340/360) or as a condensing unit only (using AHRI
365) allows manufacturers to provide condensing units for installation
in a system that may be connected to a number of different indoor
equipment types. (AHRI, No. 15 at pp. 4-5) AHRI commented that using
AHRI 365 to rate models allows manufacturers to meet customer needs
when indoor equipment and controls with which the condensing unit would
be paired in the field are not known. AHRI stated that there is no
procedure in AHRI 340/360 nor AHRI 1340 for rating outdoor units such
as condensing units without an indoor match. Furthermore, AHRI
commented that DOE had not investigated the impact of this proposed
change sufficiently and asserted that there could be serious
consequences. Id.
In response to concerns raised by AHRI and Trane, DOE emphasizes
that the clarification provided in the August 2023 TP NOPR regarding
the coverage of condensing units paired with air handlers is not a
change from the existing requirements for rating these models. Neither
the current DOE test procedure nor the amended test procedures adopted
in this final rule reference AHRI 365 for testing or rating condensing
units only. Accordingly, in this final rule, DOE reiterates that
condensing unit models distributed in commerce with air handlers with
cooling capacities up to 760,000 Btu/h are covered as commercial
package air-conditioning and heating equipment (see definition at 10
CFR 431.92), and as such, they are subject to the Federal regulations
specified for CUACs and CUHPs regarding test procedures (10 CFR
431.96), energy conservation standards (10 CFR 431.97), and
certification and representation requirements (10 CFR 429.43).
Regarding Trane's assertion as to the extent of testing, AEDM
development, and certification needed, DOE notes that its regulations
do not require that ratings for CUACs and CUHPs (including split
systems that comprise a condensing unit and air handler) be developed
through testing, and that AEDMs can be used to rate all such systems.
DOE further notes that to the extent that manufacturers have developed
simulations of condensing unit model performance in accordance with
AHRI 365, such simulations could be used as the basis of an AEDM to
rate condensing units paired with air handlers, provided the AEDM
satisfies the minimum requirements specified at 10 CFR 429.70(c).
B. Definitions
1. CUAC and CUHP Definition
As in this final rule, DOE has previously used the colloquial terms
``commercial unitary air conditioners'' and ``commercial unitary heat
pump'' (i.e., CUACs and CUHPs), to refer to certain commercial package
air conditioning and heating equipment, recognizing that CUAC is not a
statutory term and is not currently used in the CFR. See 79 FR 58948,
58950 (Sept. 30, 2014); 80 FR 52676, 52676 (Sept. 1, 2015). As codified
in regulation, the classes for which EPCA prescribed standards have
been grouped under the headings ``commercial air conditioners
[[Page 43994]]
and heat pumps'' (10 CFR 431.96(b), table 1) and ``air conditioning and
heating equipment'' (10 CFR 431.97(b), table 1), although these are not
defined terms. These classes have also been identified by the broader
equipment type with which they are associated (i.e., small, large, or
very large commercial package air conditioning and heating equipment).
Id.
In the August 2023 TP NOPR, DOE proposed to establish a definition
for ``commercial unitary air conditioner and commercial unitary heat
pump'' to assist in distinguishing between the regulated categories of
commercial package air conditioning and heating equipment. 88 FR 56392,
56399-56400 (August 17, 2023). The proposed definition was structured
to indicate categories of commercial package air conditioning and
heating equipment that are excluded from the definition, rather than
stipulating features or characteristics of CUACs and CUHPs. The
proposed definition excluded single package vertical air conditioners
and heat pumps (``SPVUs''), variable refrigerant flow multi-split air
conditioners and heat pumps, and water-source heat pumps. Specifically,
DOE proposed to define ``commercial unitary air conditioner and
commercial unitary heat pump'' as any small, large, or very large air-
cooled, water-cooled, or evaporatively-cooled commercial package air
conditioning and heating equipment that consists of one or more
factory-made assemblies that provide space conditioning; but does not
include: (1) single package vertical air conditioners and heat pumps;
(2) variable refrigerant flow multi-split air conditioners and heat
pumps; (3) water-source heat pumps; (4) equipment marketed only for use
in computer rooms, data processing rooms, or other information
technology cooling applications, and (5) equipment only capable of
providing ventilation and conditioning of 100-percent outdoor air
marketed only for ventilation and conditioning of 100-percent outdoor
air. Id. at 88 FR 56399. DOE also requested comment on the proposed
definition for ``commercial unitary air conditioners and heat pumps.''
Id. at 88 FR 56400.
DOE received feedback from several commenters regarding the
proposed definition for CUACs and CUHPs. AHRI, Rheem, and Trane
commented that they did not agree that the proposed definition for
CUACs and CUHPs is necessary or addresses any existing problems. (AHRI,
No. 15 at p. 3; Rheem, No. 12 at pp. 1-2; Trane, No. 14 at p. 3) AHRI
asserted that manufacturers, regulators, and design engineers
understand the phrase ``unitary central air conditioners and central
air-conditioning heat pumps for commercial application'' within the
existing definition for ``commercial package air-conditioning and
heating equipment'' as referring to CUACs and CUHPs. (AHRI, No. 15 at
p. 3) AHRI also stated that the proposed definition for CUACs and CUHPs
creates a circular reference to the existing definition of ``Commercial
package air-conditioning and heating equipment.'' (Id.) AHRI further
asserted that the proposed definition for CUACs and CUHPs should not be
implemented, as the term is not referenced (or proposed) in 42 U.S.C.
6311. (Id at p. 4) AHRI did not support any changes that would separate
small, large, or very large commercial package air conditioning and
heating equipment from their designation as ``ASHRAE equipment'' per 42
U.S.C. 6313. (Id.)
Carrier, NEEA, and NYSERDA supported the proposed definition of
``commercial unitary air conditioner and commercial unitary heat
pump.'' (Carrier, No. 8 at pp. 1-2; NEEA, No. 16 at pp. 3-4; NYSERDA,
No. 13 at p. 3) Carrier recommended DOE also adopt the definitions for
``Commercial and Industrial Unitary Air-Conditioning Equipment'' and
``Commercial and Industrial Unitary Heat Pump'' in sections 3.4 and 3.5
of AHRI 340/360-2022 and sections 3.5 and 3.6 of AHRI 1340-202X Draft
to provide additional clarity. (Carrier, No. 8 at pp. 1-2) NYSERDA
recommended including ``packaged or split'' in the definition for
additional clarity. (NYSERDA, No. 13 at p. 3)
NEEA also commented that the definition proposed for CUACs and
CUHPs includes excluded products, which appeared contradictory to DOE's
statement that models can meet the definition for multiple equipment
categories. (NEEA, No. 16 at pp. 3-4) NEEA requested clarification
regarding DOE's intent with the proposed definition. (Id.) AHRI also
requested clarification as to why DOE used distinct descriptions for
the fourth and fifth exclusions in the proposed CUAC and CUHP
definition rather than using the already defined terms in 10 CFR
431.92, ``Computer room air conditioners,'' and ``Unitary dedicated
outdoor air systems'' respectively. (AHRI, No. 15 at pp. 3-4)
After consideration of the comments received and upon further
review, DOE is declining to finalize the proposed definition for CUACs
and CUHPs in this final rule. DOE may consider adopting a definition
for CUACs and CUHPs in a future rulemaking action.
2. Basic Model Definition
The current definition for ``basic model'' in DOE's regulations
includes a provision applicable for ``small, large, and very large air-
cooled or water-cooled commercial package air conditioning and heating
equipment (excluding air-cooled, three-phase, small commercial package
air conditioning and heating equipment with a cooling capacity of less
than 65,000 Btu/h).'' 10 CFR 431.92. Additionally, the term in the
current ``basic model'' definition includes ACUACs, ACUHPs, and WCUACs,
but does not explicitly include ECUACs. However, the definition of
``commercial package air-conditioning and heating equipment'' at 10 CFR
431.92 makes clear that that term includes evaporatively-cooled
equipment. Consequently, ECUACs are part of the relevant basic model
definition, so the omission of the term ``evaporatively-cooled'' from
the heading should not impact the proper functioning and use of the
test procedure.
In the August 2023 TP NOPR, DOE proposed to update the definition
of ``basic model'' so that this provision instead applies to the
proposed defined term ``commercial unitary air conditioner and
commercial unitary heat pump,'' which would also inherently include
evaporatively-cooled equipment. 88 FR 56392, 56400 (August 17, 2023).
DOE also proposed editorial changes more generally to the definition of
``basic model'' specified in 10 CFR 431.92 to address that the current
wording could be misinterpreted to read as a definition of each
equipment category, rather than as the definition of what constitutes a
basic model for each equipment category. Id.
DOE did not receive any comments in response to its proposal to
update the definition for ``basic model.'' As discussed in section
III.B.1, DOE is not finalizing the proposed defined term ``commercial
unitary air conditioner and commercial unitary heat pump.'' As such,
DOE is applying the definition of ``basic model'' to the existing
defined term ``commercial package air-conditioning and heating
equipment'' at 10 CFR 431.92. Therefore, other than this terminology
change, DOE is amending the definition for ``basic model'' as proposed,
for the reasons discussed in the preceding paragraphs and in the August
2023 TP NOPR.
3. Double-Duct Definition
DOE established a definition for ``double-duct air conditioner or
heat pump'' at 10 CFR 431.92 (referred to as ``double-duct air
conditioners and heat
[[Page 43995]]
pumps'' or ``double-duct systems'') in an energy conservation standards
direct final rule published in the Federal Register on January 15, 2016
(``January 2016 Direct Final Rule''). 81 FR 2420, 2529. This definition
was included in a term sheet by the ASRAC working group for commercial
package air conditioners (``Commercial Package Air Conditioners Working
Group'') as part of the rulemaking that culminated with the January
2016 Direct Final Rule. (See Document No. 93 in Docket No. EERE-2013-
BT-STD-0007, pp. 4-5) DOE defines ``double-duct systems'' as air-cooled
commercial package air conditioning and heating equipment that: (1) is
either a horizontal single package or split-system unit or a vertical
unit that consists of two components that may be shipped or installed
either connected or split; (2) is intended for indoor installation with
ducting of outdoor air from the building exterior to and from the unit,
as evidenced by the unit and/or all of its components being non-
weatherized, including the absence of any marking (or listing)
indicating compliance with UL 1995,\11\ ``Heating and Cooling
Equipment,'' or any other equivalent requirements for outdoor use; (3)
if it is a horizontal unit, a complete unit has a maximum height of 35
inches; if it is a vertical unit, a complete unit has a maximum depth
of 35 inches; and (4) has a rated cooling capacity greater than or
equal to 65,000 Btu/h and up to 300,000 Btu/h. 10 CFR 431.92.
---------------------------------------------------------------------------
\11\ Underwriters Laboratory (UL) 1995, UL Standard for Safety
for Heating and Cooling Equipment (UL 1995).
---------------------------------------------------------------------------
In the August 2023 TP NOPR, DOE proposed to amend the ``double-duct
air conditioner or heat pump'' definition consistent with the
definition in both AHRI 340/360-2022 and the AHRI 1340-202X Draft. 88
FR 56392, 56400-56401 (August 17, 2023). AHRI 340/360-2022 and the AHRI
1340-202X Draft specify the following definition for ``double-duct
systems'': an air conditioner or heat pump that complies with all of
the following: (1) is either a horizontal single package or split-
system unit; or a vertical unit that consists of two components that
can be shipped or installed either connected or split; or a vertical
single packaged unit that is not intended for exterior mounting on,
adjacent interior to, or through an outside wall; (2) is intended for
indoor installation with ducting of outdoor air from the building
exterior to and from the unit, where the unit and/or all of its
components are non-weatherized; (3) if it is a horizontal unit, the
complete unit shall have a maximum height of 35 in. or the unit shall
have components that do not exceed a maximum height of 35 in. If it is
a vertical unit, the complete (split, connected, or assembled) unit
shall have components that do not exceed maximum depth of 35 in.; (4)
has a rated cooling capacity greater than and equal to 65,000 Btu/h and
less than or equal to 300,000 Btu/h.
In comparison to DOE's definition, DOE noted the following
regarding the definition for double-duct system in AHRI 340/360-2022
and the AHRI 1340-202X Draft: (1) vertical single packaged units not
intended for exterior mounting on, adjacent interior to, or through an
outside wall can be classified as double-duct systems; (2) the maximum
dimensions apply to each component of a split system; and (3) the AHRI
340/360-2022 and AHRI 1340-202X Draft definition does not include
compliance with UL 1995 as a criterion for determining whether a model
is non-weatherized. In the August 2023 TP NOPR, DOE tentatively
concluded that the definition for ``double-duct system'' in section 3.7
of AHRI 340/360-2022 and section 3.12 of the AHRI 1340-202X Draft more
appropriately classifies double-duct systems and differentiates this
equipment from other categories of commercial package air conditioning
and heating equipment. 88 FR 56392, 56400-56401 (August 17, 2023).
DOE did not receive comment regarding the proposed revisions to the
definition for ``double-duct air conditioner or heat pump.'' DOE has
determined that the substance of the definitions for ``double-duct
system'' in AHRI 340/360-2022 and AHRI 1340-2023 better implement the
intent of DOE and the Commercial Package Air Conditioners Working Group
to create a separate equipment class of ACUACs and ACUHPs that are
designed for indoor installation and that require ducting of outdoor
air from the building exterior. 81 FR 2420, 2446 (Jan. 15, 2016). Thus,
DOE is revising the definition of ``double-duct air conditioner or heat
pump'' in 10 CFR 431.92 as proposed in the August 2023 TP NOPR, which
is consistent with the definition in section 3.2.7 of AHRI 1340-2023.
4. Metric Definitions
As mentioned in sections III.D.1 and III.D.2, and discussed in
further detail in section III.E of this final rule, DOE is adopting new
cooling and heating metrics in appendix A1 (i.e., IVEC and IVHE).
Additionally, DOE is adopting three metrics for optional
representations in appendix A1, as discussed further in section III.E.6
of this final rule: energy efficiency ratio 2 (``EER2''), coefficient
of performance 2 (``COP2''), and IVHE for colder climates
(``IVHEC''). In the August 2023 TP NOPR, DOE proposed to add
new definitions at 10 CFR 431.92 for the terms ``IVEC,'' ``IVHE,''
``EER2,'' and ``COP2'' that describe what each metric represents, the
test procedure used to determine each metric, and specific designations
applicable to each metric (e.g., IVHEC). 88 FR 56392, 56401
(August 17, 2023). DOE did not receive comment on the proposed
definitions for ``IVEC,'' ``IVHE,'' ``EER2,'' and ``COP2.'' Therefore,
DOE is adopting the definitions as proposed in the August 2023 TP NOPR.
C. Updates to Industry Standards
The following sections discuss the changes included in the most
recent updates to AHRI 340/360 and ASHRAE 37, which are incorporated by
reference in the current DOE test procedure for ACUACs and ACUHPs with
a rated cooling capacity greater than or equal to 65,000 Btu/h at 10
CFR 431.96 and 10 CFR part 431, subpart F, appendix A. AHRI 340/360 is
also incorporated by reference in the current DOE test procedure for
ECUACs and WCUACs with a rated cooling capacity greater than or equal
to 65,000 Btu/h at 10 CFR 431.96. The following sections also discuss
the new industry test standard, AHRI 1340-2023, which DOE is
incorporating by reference for use in the new DOE test procedure for
CUACs and CUHPs at 10 CFR part 431, subpart F, appendix A1.
1. AHRI 340/360
As noted previously, DOE's current test procedures for ACUACs,
ACUHPs, and ECUACs and WCUACs with a rated cooling capacity greater
than or equal to 65,000 Btu/h incorporates by reference ANSI/AHRI 340/
360-2007. DOE's current test procedure for ECUACs and WCUACs with a
rated cooling capacity less than 65,000 Btu/h incorporates by reference
ANSI/AHRI 210/240-2008.
The most recent version of ASHRAE Standard 90.1 (i.e., ASHRAE
Standard 90.1-2022) references AHRI 340/360-2022 as the test procedure
for ACUACs, ACUHPs, and ECUACs and WCUACs with a rated cooling capacity
greater than or equal to 65,000 Btu/h. ASHRAE Standard 90.1-2022
included updates to the test procedure references for ECUACs and WCUACs
with capacities less than 65,000 Btu/h to reference AHRI 210/240-2023.
However, ECUACs and WCUACs with capacities less than 65,000 Btu/h are
outside of the scope of AHRI 210/240-2023 and are instead included in
AHRI 340/360-2022. Given
[[Page 43996]]
these changes to the relevant industry test standards, DOE believes
that such reference was an oversight.
The following list includes substantive additions in AHRI 340/360-
2022 as compared to the current Federal test procedures that apply to
CUACs and CUHPs, which reference ANSI/AHRI 340/360-2007 and ANSI/AHRI
210/240-2008:
1. A method for testing double-duct systems at non-zero outdoor air
ESP (see section 6.1.3.7 and appendix I of AHRI 340/360-2022);
2. A method for comparing relative efficiency of indoor integrated
fan and motor combinations (``IFMs'') that allows CUACs and CUHPs with
non-standard (i.e., higher ESP) IFMs to be rated in the same basic
model as otherwise identical models with standard IFMs (see section
D4.2 of appendix D of AHRI 340/360-2022);
3. Requirements for indoor and outdoor air condition measurement
(see appendix C of AHRI 340/360-2022);
4. Detailed provisions for setting indoor airflow and ESP (see
sections 6.1.3.3-6.1.3.5 of AHRI 340/360-2022) and refrigerant charging
instructions to be used in cases in which manufacturer's instructions
conflict or are incomplete (see section 5.8 of AHRI 340/360-2022); and
5. ECUACs and WCUACs with cooling capacities less than 65,000 Btu/h
are included within the scope of the standard.
As discussed, DOE is amending its test procedure for CUACs and
CUHPs by incorporating by reference AHRI 340/360-2022 in appendix A.
Section III.E discusses the specific sections of AHRI 340/360-2022 that
DOE references in the amendments to appendix A adopted in this final
rule. As discussed, DOE is adopting these amendments in accordance with
the requirement that the test procedures for commercial package air
conditioning and heating equipment be those generally accepted industry
testing procedures or rating procedures developed or recognized by AHRI
or ASHRAE, as referenced in ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A)) As DOE has noted, ASHRAE Standard 90.1 references an
incorrect industry standard for ECUACs and WCUACs with capacities less
than 65,000 Btu/h, AHRI 210/240-2023, so DOE is amending appendix A to
reference the applicable industry standard, AHRI 340/360-2022.
2. AHRI 1340
The recommendations of the ACUAC and ACUHP Working Group TP Term
Sheet have been incorporated into an updated version of AHRI 340/360,
denoted as AHRI 1340-2023, which supersedes AHRI 340/360-2022, but has
not yet been adopted in ASHRAE Standard 90.1. In the August 2023 TP
NOPR, DOE proposed to adopt the AHRI 1340-202X Draft, a draft version
of AHRI 1340 available at the time. DOE noted its intent to update its
incorporation by reference to the final published version of the AHRI
1340-202X Draft, unless there were substantive changes between the
draft and published versions. 88 FR 56392, 56402 (August 17, 2023).
Differences between the ACUAC/ACUHP Working Group TP Term Sheet, the
AHRI 1340-202X Draft, and AHRI 1340-2023 are discussed in the
paragraphs that follow.
The AHRI 1340-202X Draft proposed for adoption in the August 2023
TP NOPR includes recommendations from the ACUAC and ACUHP Working Group
TP Term Sheet described in section III.D of this final rule (including
the IVEC and IVHE metrics). The AHRI 1340-202X Draft also included the
following revisions and additions to the IVEC and IVHE metrics not
included in the ACUAC and ACUHP Working Group TP Term Sheet, which are
discussed in detail in section III.E of this final rule:
1. Detailed test instructions for splitting ESP between the return
and supply ductwork, consistent with ESP requirements recommended in
the ACUAC and ACUHP Working Group TP Term Sheet;
2. Corrections to the hour-based IVEC weighting factors included in
the ACUAC and ACUHP Working Group TP Term Sheet;
3. Correction of the equation in the ACUAC and ACUHP Working Group
TP Term Sheet for calculating adjusted ESP for any cooling or heating
tests conducted with an airflow rate that differs from the full-load
cooling airflow;
4. Addition of separate hour-based weighting factors and bin
temperatures to calculate a separate version of IVHE that is
representative of colder climates, designated IVHEC;
5. Changes to the default fan power and maximum pressure drop used
for testing coil-only systems;
6. Additional instruction for component power measurement during
testing;
7. Corrections to equations used for calculating IVHE;
8. Provisions for testing with non-standard low-static indoor fan
motors; and
9. Revision to the power adder for WCUACs that reflects power that
would be consumed by field-installed heat rejection components.
Since publication of the August 2023 TP NOPR, the AHRI 1340-202X
Draft was finalized and published as AHRI 1340-2023 in December 2023.
DOE has reviewed AHRI 1340-2023 and has identified that AHRI 1340-2023
includes the previously discussed revisions and additions to the IVEC
and IVHE metrics in the AHRI 1340-202X Draft that were not included in
the ACUAC and ACUHP Working Group TP Term Sheet. AHRI 1340-2023 also
includes several revisions and updates to the test procedures specified
in the AHRI 1340-202X Draft. DOE reviewed these revisions and updates,
which include the following items, and discusses them in detail in
sections III.E.3, III.E.7, III.E.8, III.F, and III.H of this document.
Those sections also include discussion of the justification for
adopting the content of these changes (which are largely consistent
with corresponding proposals in the August 2023 TP NOPR) in this final
rule.
1. A method for calculating capacity and fan power adjustments for
coil-only systems operating at part-load airflow, consistent with DOE's
proposal in the August 2023 TP NOPR;
2. Addition of a method to verify cut-in and cut-out temperatures,
consistent with DOE's proposal in the August 2023 TP NOPR but with
additional specificity;
3. Addition of an optional boost 2 test for optional
representations of 5 [deg]F capacity and performance for systems with
more than two operating levels;
4. Allowance for the test conducted at 5 [deg]F and 17 [deg]F at
the boost heating operating level to be used for IVHE bins ranging from
5 [deg]F to 21 [deg]F;
5. Revisions to appendix D of AHRI 1340 to align with the specific
components approach proposed by DOE in the August 2023 TP NOPR, and
inclusion of provision for how to test models with drain pan heaters
present; and
6. Revisions to the test temperatures for ECUACs and WCUACs and
corresponding revision to the tower fan and pump power values for
WCUACs.
Consistent with the proposals in the August 2023 TP NOPR, in this
final rule DOE is incorporating by reference AHRI 1340-2023 in the new
test procedure at appendix A1 as DOE has determined, supported by clear
and convincing evidence, that AHRI 340/360-2022 cannot provide
representative energy use results for the IVEC and IVHE efficiency
metrics. Further, DOE has determined that AHRI 1340-2023 would not be
unduly burdensome to conduct and reflects energy efficiency during a
representative average use cycle for the
[[Page 43997]]
IVEC and IVHE efficiency metrics. Specific aspects of AHRI 1340-2023
are discussed in more detail in section III.E. Section III.E of this
document also discusses comments received on DOE's proposal to adopt
the AHRI 1340-202X Draft, as well as the specific sections of AHRI
1340-2023 that DOE references in appendix A1.
3. ASHRAE 37
ANSI/ASHRAE 37-2009, which provides a method of test for many
categories of air conditioning and heating equipment, is referenced for
testing CUACs and CUHPs by AHRI 340/360-2022 and AHRI 1340-2023. More
specifically, sections 5 and 6 and appendices C, D, and E of AHRI 340/
360-2022 and sections 5 and 6 and appendices C, D, and E of AHRI 1340-
2023 reference methods of test in ANSI/ASHRAE 37-2009. DOE currently
incorporates by reference ANSI/ASHRAE 37-2009 in 10 CFR 431.95, and the
current incorporation by reference applies to the current Federal test
procedure for ACUACs and ACUHPs specified at appendix A. The current
Federal test procedures at 10 CFR 431.96 for ECUACs and WCUACs do not
explicitly reference ANSI/ASHRAE 37-2009. In the August 2023 TP NOPR,
DOE proposed to maintain the incorporation by reference of ANSI/ASHRAE
37-2009 to the proposed appendix A, which would also apply ANSI/ASHRAE
37-2009 to testing ECUACs and WCUACs, and to incorporate by reference
ANSI/ASHRAE 37-2009 for use with appendix A1. 88 FR 56392, 56402
(August 17, 2023). DOE did not receive any comments regarding its
proposal to incorporate by reference ANSI/ASHRAE 37-2009 to both
appendices A and A1. Therefore, as proposed, DOE is maintaining its
incorporation by reference of ANSI/ASHRAE 37-2009 in appendix A and
incorporating by reference ANSI/ASHRAE 37-2009 in appendix A1. Section
III.E of this document discusses the specific sections of ANSI/ASHRAE
37-2009 that DOE references in appendices A and A1.
D. Term Sheet Recommendations and Metrics
As previously mentioned, DOE published in the Federal Register the
July 2022 Notice of Intent. 87 FR 45703 (July 29, 2022). DOE then
established the Working Group in accordance with FACA and NRA. The
Working Group consisted of 14 members and met six times, while the
Working Group's subcommittee met an additional seven times. The Working
Group meetings were held between September 20, 2022, and December 15,
2022, after which the Working Group successfully reached consensus on
an amended test procedure. The Working Group signed a term sheet of
recommendations on December 15, 2022. (See EERE-2022-BT-STD-0015-0065)
The Working Group addressed the following aspects of the test procedure
for ACUACs and ACUHPs:
1. Mathematical representation of cooling efficiency: The current
cooling metric specified by AHRI 340/360-2022 (i.e., IEER) represents a
weighted average of the measured energy efficiency ratios (EER)
measured at four distinct test conditions, whereas the IVEC metric is
calculated as the total annual cooling capacity divided by the total
annual energy use, as discussed further in section III.D.1 of this
document. The Working Group agreed that this calculation approach
provides a more mathematically accurate way of representing the cooling
efficiency of ACUACs and ACUHPs compared to the current approach used
for IEER. As part of this equation format, the IVEC metric also uses
hour-based weighting factors to represent the time spent per year in
each operating mode.
2. Integrated heating metric: The current heating metric for ACUHPs
(i.e., COP) represents the ratio of heating capacity to the power
input, calculated at a single test condition of 47 [deg]F. COP does not
account for the performance at part-load or over the range of
temperatures seen during an average heating season, and it does not
include energy use in heating season ventilation mode. IVHE accounts
for both full-load and part-load operation at a range of typical
ambient temperatures seen during the heating season, and it includes
energy use in heating season ventilation mode. Analogous to IVEC, the
IVHE metric is calculated as the total annual heating load divided by
the total annual energy use, as discussed further in section III.D.2 of
this document, and the metric also uses hour-based weighting factors to
represent the time spent per year in each operating mode.
3. Operating modes other than mechanical cooling: The IEER metric
currently does not include the energy use of operating modes other than
mechanical cooling, such as economizer-only cooling and cooling season
ventilation. The newly established IVEC metric includes the energy use
of these other modes.
4. ESP: The IVEC and IVHE metrics require increased ESPs--in
comparison to the ESPs required for determining IEER and COP--to more
accurately represent ESPs and corresponding indoor fan power that would
be experienced in real-world installations.
5. Crankcase heater operation: The current IEER metric includes
crankcase heater power consumption only when operating at part-load
compressor stages (i.e., for part-load cooling operation, crankcase
heater power is included only for higher-stage compressors that are
staged off, and it is not included for lower-stage compressors when all
compressors are cycled off). The COP metric does not include any
crankcase heater power consumption. In contrast, the IVEC and IVHE
metrics include all annual crankcase heater operation, including when
all compressors are cycled off in part-load cooling or heating,
ventilation mode, unoccupied no-load hours, and in heating season (for
ACUACs only).
6. Oversizing: The current IEER and COP metrics do not consider
that ACUACs and ACUHPs are typically oversized in field installations.
In contrast, the IVEC and IVHE metrics include an oversizing factor of
15 percent (i.e., it is assumed that the unit's measured full-load
cooling capacity is 15 percent higher than the peak building cooling
load and peak building heating load). Accounting for oversizing is more
representative of the load fractions seen in field applications and
better enables the test procedure to differentiate efficiency
improvements from the use of modulating/staged components.
Based on discussions related to these six topics, the Working Group
developed the ACUAC and ACUHP Working Group TP Term Sheet, which
includes the following recommendations:
1. A recommendation to adopt the latest version of AHRI 340/360-
2022 with IEER and COP metrics required for compliance beginning 360
days from the date a test procedure final rule publishes (see
Recommendation #0);
2. The IVEC efficiency metric, to be required on the date of
amended energy conservation standards for ACUACs and ACUHPs (see
Recommendation #1);
3. Hour-based weighting factors for the IVEC metric (see
Recommendation #2);
4. Details on determination of IVEC, including provisions for
determining IVEC in appendix B of the ACUAC and ACUHP Working Group TP
Term Sheet (see Recommendation #3);
5. Target load fractions and temperature test conditions for IVEC,
which account for oversizing (see Recommendation #4);
6. A requirement that representations of full-load EER be made in
accordance
[[Page 43998]]
with the full-load ``A'' test (see Recommendation #5); \12\
---------------------------------------------------------------------------
\12\ Similar to the current test procedure for determining IEER,
the test procedure recommended in the ACUAC and ACUHP Working Group
TP Term Sheet includes four cooling tests designated with letters
``A,'' ``B,'' ``C,'' and ``D.'' The ``A'' test is a full-load
cooling test, while the ``B,'' ``C,'' and ``D'' tests are part-load
cooling tests.
---------------------------------------------------------------------------
7. A requirement to provide representations of airflow used for the
full-load ``A'' test and the part-load ``D'' test (i.e., the airflow
used in the lowest-stage test for the D point), and a provision for
determining the minimum airflow that can be used for testing (see
Recommendation #6);
8. The IVHE efficiency metric (see Recommendation #7);
9. Hour-based weighting factors, load bins, and outdoor air
temperatures for each bin (i.e., temperatures used for the building
heating load line, not test temperature conditions) for the IVHE metric
(see Recommendation #8);
10. The test conditions and list of required and optional tests and
representations for the IVHE metric (see Recommendation #9);
11. Provisions for manufacturers to certify cut-in and cut-out
temperatures for heat pumps to DOE and provisions for a DOE
verification test of those temperatures (see Recommendation #10);
12. Commitment of the Working Group to analyze ventilation and fan-
only operation included in the IVEC and IVHE metrics to validate that
these metrics adequately capture fan energy use during the energy
conservation standards portion of the negotiated rulemaking. If the
IVEC and IVHE levels do not adequately drive more efficient air moving
systems that are technologically feasible and economically justified,
the Working Group committed to developing a metric addressing furnace
fan energy use (see Recommendation #11);
13. ESP requirements for the IVEC and IVHE metrics, requirements
for splitting the ESP requirements between the return and supply ducts,
and a requirement that certified airflow for full load and D bin be
made public in the DOE Compliance Certification Database (see
Recommendation #12);
14. Provisions requiring manufacturers to certify crankcase heater
wattages and tolerances for certification (see Recommendation #13); and
15. Provisions that the contents of the ACUAC and ACUHP Working
Group TP Term Sheet be implemented in a test procedure NOPR and final
rule, with the final rule issuing no later than any energy conservation
standards direct final rule (see Recommendation #14).
The following sections provide a summary of the development and
final recommendations regarding the IVEC and IVHE cooling and heating
metrics in the ACUAC and ACUHP Working Group TP Term Sheet.
1. IVEC
For the new cooling metric, the Working Group determined to
prospectively modify the climate zones and building types accounted for
in the test procedure as compared to those included in the existing DOE
test procedure, in order to improve the representativeness of the
metrics to better reflect the broad range of applications of CUACs and
CUHPs. To do so, the Working Group utilized hour-based weighting
factors, which represent the average time spent per year in each
operating mode and load bin. To develop these weighting factors,
members of the Working Group used building modeling developed by
Carrier that was based on 10 ASHRAE Standard 90.1 building prototypes
across all U.S. climate zones. (See EERE-2022-BT-STD-0015-0019) The
resulting hour-based weighting factors are provided in Recommendation
#2 of the ACUAC and ACUHP Working Group TP Term Sheet. (See EERE-2022-
BT-STD-0015-0065)
The ACUAC and ACUHP Working Group concluded that including
economizer-only cooling and cooling season ventilation operating modes
in a seasonal cooling metric would improve the representativeness for
ACUACs and ACUHPs, and as such, included these modes in the IVEC metric
outlined in Recommendation #1 and the hour-based weighting factors in
Recommendation #2 of the ACUAC and ACUHP Working Group TP Term Sheet.
Appendix B of the ACUAC and ACUHP Working Group TP Term Sheet provides
the recommended calculation method for the IVEC method and includes
sections specifying the methods for including ventilation and
economizer-only cooling operation in the calculation of IVEC. (See
EERE-2022-BT-STD-0015-0065)
The Working Group also considered ESP requirements for the IVEC and
IVHE metrics. Stakeholders indicated the need for higher ESP
requirements to improve representativeness of field performance.
Additionally, stakeholders discussed the importance of maintaining
uniformity in testing of units at higher ESP conditions. (See EERE-
2022-BT-STD-0015-0062 at p. 11) The ESP requirements agreed to by the
Working Group are provided in Recommendation #12 of the ACUAC and ACUHP
Working Group TP Term Sheet (see EERE-2022-BT-STD-0015-0065) and
include the following:
1. Higher ESP requirements for testing: As discussed previously,
the minimum ESP conditions recommended by the Working Group are
provided in Table III-1.
[GRAPHIC] [TIFF OMITTED] TR20MY24.128
2. Economizer pressure drop: ASHRAE Standard 90.1-2022 requires the
use of economizers for comfort cooling applications for almost all U.S.
climate zones. The analysis conducted by Carrier in support of the
Working Group indicates that over 96 percent of buildings require the
use of economizers. (see EERE-2022-BT-STD-0015-0019 at p. 14)
Economizers installed in CUACs and CUHPs add internal static pressure
that the indoor
[[Page 43999]]
fan has to overcome, even when the economizer dampers are closed. The
current DOE test procedure does not require the installation of an
economizer on a tested unit, and DOE is aware that manufacturers
generally do not test CUACs and CUHPs with economizers installed. The
ESP requirements specified by the current DOE test procedure are the
same regardless of whether a unit is tested with or without an
economizer. As such, testing a unit without an economizer does not
reflect the total static pressure that would be experienced in the
field for installations that require the use of an economizer.
Accordingly, in order to better represent the fan power of ACUACs and
ACUHPs that are typically installed with economizers, the Working Group
recommended that for all units tested without an economizer installed,
0.10 in. H2O shall be added to the full-load ESP values specified in
Table III-1.\13\
---------------------------------------------------------------------------
\13\ An economizer is an apparatus that supplies outdoor air to
reduce or eliminate the need for mechanical cooling during mild or
cooler weather.
---------------------------------------------------------------------------
3. Return and supply static split requirements: Test procedures for
CUACs and CUHPs include ESP requirements that reflect the total ESP
applied within the return and supply ductwork of the test set-up. The
current Federal test procedure does not specify requirements for how
ESP is distributed during testing (i.e., the relative contribution from
return ductwork versus supply ductwork). Given the recommendation to
increase the required ESP levels for testing, the Working Group
concluded that the higher ESP conditions could cause variability in
test results if the distribution of ESP between return ductwork and
supply ductwork were not specified in the revised test procedure.
Therefore, to ensure repeatable and reproducible testing conditions for
CUAC and CUHP units, the Working Group recommended specifying that ESP
requirements be split with 25 percent applied in the return ductwork
and the remaining 75 percent applied in the supply ductwork. The
Working Group further recommended that the fraction of ESP applied in
the return ductwork shall have a -5/+0 percent tolerance (i.e., the
return static must be within 20 to 25 percent of the total ESP) for the
full-load cooling test. In a case where there is no additional
restriction on the return duct and more than 25 percent of the ESP is
already applied in the return ductwork without a restriction, then
greater than 25 percent ESP in the return ductwork will be allowed.
Once set for the full-load cooling test, these restriction settings
shall remain unchanged for the other cooling and heating tests
conducted.
To incorporate the various changes involved in testing requirements
and weighting factors already discussed, the Working Group created the
IVEC metric provided in Recommendation #1 with further specifications
in appendix B of the ACUAC and ACUHP Working Group TP Term Sheet. The
IVEC metric is a summation formula analogous to the seasonal energy
efficiency ratio 2 (``SEER2'') metric designated for residential
central air conditioner and central air conditioning heat pumps (``CAC/
HP'') equipment. (See appendix M1 to subpart B of 10 CFR part 430,
``Uniform Test Method for Measuring the Energy Consumption of Central
Air Conditioners and Heat Pumps.'') Stated simply, the IVEC metric is
calculated by dividing the total annual cooling capacity by the total
annual energy use. Key aspects encompassed in the IVEC metric include
the following:
1. Accounting for energy consumed in different modes: The IVEC
metric includes energy use during mechanical cooling, integrated
mechanical and economizer cooling, economizer-only cooling, cooling
season ventilation, unoccupied no-load hours, and heating season
operation of crankcase heat (for CUACs only). Appendix B of the ACUAC
and ACUHP Working Group TP Term Sheet specifies instructions for
determining energy consumption during each mode.
2. Testing parameters: The ACUAC and ACUHP Working Group TP Term
Sheet further specifies instructions in appendix B for the mechanical
cooling tests at each target mechanical load. These methodologies and
tolerances mirror those specified in AHRI 340/360-2022, including a 3-
percent tolerance on the target mechanical load for part-load tests,
and in cases when the target mechanical load cannot be met within
tolerance, instructions for using interpolation and cyclic degradation
to determine the performance at the target test point.
3. Target load percentages: Recommendation #4 of the ACUAC and
ACUHP Working Group TP Term Sheet includes target conditions for
testing, including load percentages for testing units at part-load
conditions. For each bin, the specified target load percent (%Loadi)
reflects the average load as a percentage of the full-load capacity for
that bin met by using all modes of cooling, and is used for determining
total annual cooling provided in the numerator of the IVEC equation.
The target mechanical load percent (%Loadi,mech) is the average load
for each bin met only through mechanical cooling (i.e., mechanical-only
cooling and the mechanical portion of integrated mechanical and
economizer cooling) and is the target load fraction used for the part-
load cooling test for each bin.
As mentioned, the IVEC metric includes the annual operation of
crankcase heaters for CUACs and CUHPs. Appendix B of the ACUAC and
ACUHP Working Group TP Term Sheet further specifies the accounting of
crankcase heater energy consumption in each operating mode.
Recommendation #2 of the ACUAC and ACUHP Working Group TP Term Sheet
specifies hour-based weighting factors to account for crankcase heat
operation in unoccupied no-load cooling season hours for CUACs and
CUHPs, as well as heating season hours for CUACs. Appendix B of the
ACUAC and ACUHP Working Group TP Term Sheet also specifies that for
part-load cooling tests, crankcase heat is accounted for in power
measurements of higher-stage compressors that are staged off during
testing, while crankcase heat operation of lower-stage compressors when
cycled off as well as crankcase heat operation in other operating modes
is calculated using the certified crankcase heater power.
The IVEC metric also accounts for a 15-percent oversizing factor.
Accordingly, the target load percentages specified in Recommendation #4
include this 15-percent oversizing factor. Additionally, the A test
condition is excluded from the IVEC calculation; however, the A test is
still a required test point for determining full-load capacity.
IVEC includes outdoor and return air dry-bulb and wet-bulb test
temperatures that differ from those used in the current test procedure
for determining IEER, as shown in Table III-2.
[[Page 44000]]
[GRAPHIC] [TIFF OMITTED] TR20MY24.129
The IVEC metric also limits the minimum airflow that can be used
for testing. This minimum airflow limit calculation method is based on
the average ventilation rate determined in building modeling performed
to develop IVEC and is a function of the full-load cooling capacity.
Unlike AHRI 340/360-2022 (see section 6.1.3.4.5), the provisions for
determining IVEC do not specify separate test provisions for setting
airflow during part-load tests of multi-zone variable air volume
(``MZVAV'') units. Rather, the part-load airflow used for testing all
CUACs and CUHPs will be based on the certified part-load cooling
airflow.
2. IVHE
The IVHE metric specified in the ACUAC and ACUHP Working Group TP
Term Sheet differs from the COP heating efficiency metric specified in
the current DOE test procedure by the inclusion of heating season
operating modes not currently accounted for, a combined seasonal
performance metric rather than individual ratings at specific
temperature conditions, and additional optional test conditions. In
alignment with the development of the IVEC metric described in section
III.D.1 of this final rule, the Working Group determined to utilize
hour-based weighting factors to account for heating loads across more
building types and climate zones than are included in the current DOE
test procedure. The building heating load lines and hours developed for
the IVHE metric rely on a similar ASHRAE Standard 90.1 building and
climate zone analysis as the one conducted for the IVEC metric
development. Additionally, in developing the heating load line on which
the hour-based weighting factors rely, the Working Group utilized the
previously discussed 15-percent oversizing factor and assumed a heat-
to-cool ratio of 1, as outlined in Recommendation #8 (i.e., assumed the
peak building cooling load equals the peak building heating load).
The heating rating requirements recommended in the ACUAC and ACUHP
Working Group TP Term Sheet include several distinct provisions
regarding testing requirements from the existing DOE test procedure. In
the current DOE test procedure, CUHPs are required to be tested only at
a 47 [deg]F full-load condition to generate a COP rating.
Recommendation #9 of the ACUAC and ACUHP Working Group TP Term Sheet,
however, introduces several provisions with significant differences
from the existing DOE test procedure. First, the recommendation
includes required testing at 47 [deg]F and 17 [deg]F full-load
conditions, aligning with those previously specified in AHRI 340/360-
2022. Additionally, the recommendation introduces optional part-load
test conditions at both 47 [deg]F and 17 [deg]F temperature conditions,
as well as test conditions for optional testing at a 5 [deg]F full-load
condition. Finally, the recommendation includes test requirements for
optional boost tests at the 17 [deg]F and 5 [deg]F test conditions for
variable-speed units. Additionally, the IVHE metric incorporates two
operating modes previously excluded from the DOE test procedure:
heating season ventilation mode and supplemental electric resistance
heat operation. Lastly, the IVHE test conditions rely on the same ESP
requirements per capacity bin as those specified for IVEC, as detailed
in Recommendation #12. The airflow provisions pertaining to IVEC
mentioned in section III.D.1 of this final rule (i.e., a limit on
minimum airflow used for testing and no separate test provisions for
MZVAV units) apply to the test provisions for the IVHE metric as well.
The results from optional and required testing, as well as the
newly included operating modes, are included in the calculation of the
IVHE metric utilizing the weighting factors outlined in Recommendation
#8 and calculation methods from appendix C of the ACUAC and ACUHP
Working Group TP Term Sheet. The calculation methods for IVHE that
implement these changes are further detailed in the paragraphs that
follow.
The IVHE metric includes contributions from both mechanical and
resistance heating to meet building heating load. Similar to the IVEC
calculation approach, the IVHE metric is calculated by dividing the
total annual building heating load by the total annual energy use.
Recommendations #8, #9, and #10, as well as appendices B and C of
the ACUAC and ACUHP Working Group TP Term Sheet, provide the
calculation methods for the IVHE metric. The hour-based weighting
factors and bin temperatures for IVHE are included in Recommendation #8
of the ACUAC and ACUHP Working Group TP Term Sheet, which specifies 10
distinct load-based bins alongside weighting factors for heating season
ventilation and operation of crankcase heat in unoccupied no-load
heating season hours. The calculation methods outlined for the IVHE
metric in the ACUAC and ACUHP Working Group TP Term Sheet are specified
as the following:
1. Building load calculation: Recommendation #8 includes the
calculation method for the building load in each load bin based on the
measured full-load cooling capacity.
2. Interpolation between temperatures: Appendix C of the ACUAC and
ACUHP Working Group TP Term Sheet specifies interpolation instructions
for the various test temperatures specified in Recommendation #8.
Interpolation instructions are specified for bins with temperatures
between 17 [deg]F and 47 [deg]F. Appendix C also includes the following
instructions for bins with temperatures less than 17 [deg]F: (1)
interpolation instructions to be used if the optional
[[Page 44001]]
5 [deg]F test is conducted, and (2) extrapolation instructions
utilizing the 47 [deg]F and 17 [deg]F test data to be used if the 5
[deg]F test is not conducted.
3. Determination of heating stage, auxiliary heat, and cyclic
degradation: For load bins in which the calculated building load
exceeds the highest-stage mechanical heating capacity determined for
the bin temperature, appendix C of the ACUAC and ACUHP Working Group TP
Term Sheet includes calculation methods for determining the power
required by auxiliary resistance heat and is included in the overall
IVHE calculation. For load bins in which the calculated building load
is lower than the lowest-stage mechanical heating capacity determined
for the bin temperature, appendix C of the ACUAC and ACUHP Working
Group TP Term Sheet includes calculation methodology for calculating
power and incorporating cyclic degradation with a cyclic degradation
factor of 0.25. This cyclic degradation methodology is consistent with
the methodology specified in appendix M1 to subpart B of 10 CFR part
430 for residential central heat pumps. For load bins in which the
calculated building load is in between the lowest-stage and highest-
stage mechanical heating capacities determined for the bin temperature,
appendix C of the ACUAC and ACUHP Working Group TP Term Sheet includes
calculations for determining power based on interpolation between
performance of mechanical heating stages.
4. Defrost degradation: The capacity calculations for all load bins
with temperatures less than 40 [deg]F include a defrost degradation
coefficient, with calculations specified in appendix C of the ACUAC and
ACUHP Working Group TP Term Sheet.
5. Cut-out factor: Recommendation #10 of the ACUAC and ACUHP
Working Group TP Term Sheet specifies that manufacturers will certify
cut-in and cut-out temperatures, or the lack thereof, to DOE to ensure
resistance-only operation is included at temperatures below which
mechanical heating would not operate. This restriction is implemented
in calculations through a cut-out factor included in appendix C. DOE is
not amending the certification or reporting requirements for ACUHPs in
this final rule to require reporting cut-in and cut-out temperatures.
Instead, DOE may consider proposals to amend the certification and
reporting requirements for this equipment under a separate rulemaking
regarding appliance and equipment certification.
6. Crankcase heater power contribution: In alignment with the
inclusion of crankcase heater power contribution in IVEC, appendix C of
the ACUAC and ACUHP Working Group TP Term Sheet specifies a method for
incorporating crankcase heat power for all heating season operating
modes for ACUHPs. Specifically, for part-load heating tests, crankcase
heat is accounted for in power measurements of higher-stage compressors
that are staged off during testing, while crankcase heat operation of
lower-stage compressors when cycled off, as well as crankcase heat
operation in other operating modes, is calculated using the certified
crankcase heater power.
E. DOE Adopted Test Procedures and Comments Received
In the August 2023 TP NOPR, DOE proposed to maintain the current
efficiency metrics of IEER, EER, and COP in appendix A, and reference
AHRI 340/360-2022 in appendix A for measuring the existing metrics. 88
FR 56392, 56403-56404 (August 17, 2023). Additionally, DOE proposed to
establish a new test procedure at appendix A1 that adopts the substance
of the AHRI 1340-202X Draft, including the new IVEC and IVHE metrics,
through incorporation by reference of a finalized version of that
industry test standard. Id. The following sections discuss DOE's
proposals, comments received, and DOE's adopted provisions regarding
(1) AHRI 1340-2023 and the IVEC and IVHE metrics; (2) double-duct
systems; (3) ECUACs and WCUACs; (4) the IVHE metric for colder
climates; (5) the test conditions used in appendix A; (6) the test
conditions used in appendix A1; (7) provisions introduced in the AHRI
1340-202X Draft that are not included in the ACUAC and ACUHP Working
Group TP Term Sheet; and (8) heating test provisions introduced in AHRI
1340-2023.
1. Overall
As discussed, DOE proposed to establish a new test procedure at
appendix A1 that would adopt the AHRI 1340-202X Draft, including the
newly proposed IVEC and IVHE metrics. DOE noted its intent to ideally
incorporate by reference a finalized version of that industry test
standard. DOE further stated that if a finalized version of the AHRI
1340-202X Draft is not published before the test procedure final rule,
or if there are substantive changes between the draft and published
versions of the standard that are not supported by stakeholder comments
in response to this NOPR, DOE may adopt the substance of the AHRI 1340-
202X Draft or provide additional opportunity for comment on the final
version of that industry consensus standard. Id. As noted in the August
2023 TP NOPR, certain provisions in the current appendix A and table 1
to 10 CFR 431.96(b) (e.g., regarding minimum ESP, optional break-in)
would be redundant with the reference to AHRI 340/360-2022, and, as
such, DOE proposed to remove those explicit provisions from table 1 to
10 CFR 431.96(b) and appendix A, and instead reference them through the
relevant provisions of the updated AHRI 340/360. Id.
Further, in both appendix A and appendix A1, DOE proposed to
incorporate by reference ANSI/ASHRAE 37-2009. Id.
Specifically for appendix A1, DOE proposed to adopt certain
sections of the AHRI 1340-202X Draft to determine IVEC and IVHE, which
are generally consistent with the recommendations from the ACUAC and
ACUHP Working Group TP Term Sheet. Id. The ACUAC and ACUHP Working
Group TP Term Sheet applies only to the test procedures for ACUACs and
ACUHPs, excluding double-duct systems. However, the AHRI 1340-202X
Draft proposed for adoption in the August 2023 TP NOPR, as well as the
final version of the standard (i.e., AHRI 1340-2023), include
additional provisions for determining IVEC and IVHE for double-duct
systems, ECUACs, and WCUACs, indicating industry consensus that these
metrics are appropriate for these categories of CUACs and CUHPs. Id.
DOE requested comment on the proposed adoption of the IVEC and IVHE
metrics as determined using the AHRI 1340-202X Draft in appendix A1 for
all CUACs and CUHPs. Id.
On this topic, AHRI, ASAP & ACEEE, Carrier, the CA IOUs, Lennox,
NEEA, Rheem, and Trane generally supported the proposal to adopt the
IVEC and IVHE metrics as determined in the AHRI 1340-202X Draft,
consistent with the ACUAC and ACUHP Working Group TP Term Sheet. (AHRI,
No. 15 at pp. 1, 5; ASAP & ACEEE, No. 11 at p. 1; Carrier, No. 8 at p.
2; CA IOUs, No. 10 at pp. 1-2; Lennox, No. 9 at p. 2; NEEA, No. 16 at
pp. 1-2; Rheem, No. 12 at p. 2, Trane, No. 14 at p. 1) NEEA
specifically supported the ESP requirements proposed by DOE consistent
with the recommendations of the ACUAC and ACUHP Working Group TP Term
Sheet. (NEEA, No. 16 at p. 2) The CA IOUs stated that the new test
procedure improves representativeness. (CA IOUs, No. 10 at p. 1) AHRI
and ASAP & ACEEE acknowledged the efforts made by the AHRI Commercial
Unitary Standards Technical Committee
[[Page 44002]]
(``STC'') and supported the corrections and additions to the ACUAC and
ACUHP Working Group TP Term Sheet included in the AHRI 1340-202X Draft.
(AHRI, No. 15 at pp. 1-2; ASAP & ACEEE, No. 11 at p. 1)
As proposed, DOE is adopting the most recent version of AHRI
Standard 340/360 (i.e., AHRI 340/360-2022) in appendix A for testing
CUACs and CUHPs (including ACUACs, ACUHPs, ECUACs, WCUACs, and double-
duct systems) to measure the current metrics--EER, IEER, and COP.
Specifically, DOE is adopting the following sections of AHRI 340/360-
2022: sections 3 (with certain exclusions \14\), 4, 5, and 6, and
appendices A, C, D (excluding sections D1 through D3), and E. As
proposed, DOE is also removing certain provisions from table 1 to 10
CFR 431.96(b) and the current appendix A that are redundant with the
reference to AHRI 340/360-2022 adopted in appendix A in this final
rule. As discussed, DOE is adopting these amendments in accordance with
the requirement that the test procedures for commercial package air
conditioning and heating equipment be those generally accepted industry
testing procedures or rating procedures developed or recognized by AHRI
or ASHRAE, as referenced in ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A))
---------------------------------------------------------------------------
\14\ DOE is not referencing the following provisions in section
3 of AHRI 340/360-2022 because the terms are either defined at 10
CFR 431.92 or are not needed for the DOE test procedure: 3.2 (Basic
Model), 3.4 (Commercial and Industrial Unitary Air-conditioning
Equipment), 3.5 (Commercial and Industrial Unitary Heat Pump), 3.7
(Double-duct System), 3.8 (Energy Efficiency Ratio), 3.12 (Heating
Coefficient of Performance), 3.14 (Integrated Energy Efficiency
Ratio), 3.23 (Published Rating), 3.26 (Single Package Air-
Conditioners), 3.27 (Single Package Heat Pumps), 3.29 (Split System
Air-conditioners), 3.30 (Split System Heat Pump), and 3.36 (Year
Round Single Package Air-conditioners).
---------------------------------------------------------------------------
As discussed in section III.C.2 of this document, AHRI 1340-2023
includes certain updates that are not included in the ACUAC and ACUHP
Working Group TP Term Sheet. Most of these updates were included in the
AHRI 1340-202X Draft, and they are discussed in detail in section
III.E.7 of this final rule. There are also several updates included
AHRI 1340-2023 that were not included in the AHRI 1340-202X Draft,
notably regarding ECUACs and WCUACs (discussed in further detail in
section III.E.3 of this document) and boost heating tests (described in
further detail in section III.E.8 of this document). Based on comments
received and DOE's review of AHRI 1340-2023, DOE has determined that
the updates to the test procedure in AHRI 1340-2023 are appropriate,
consistent with the intent of the ACUAC and ACUHP Working Group TP Term
Sheet and the intent of the provisions proposed in the August 2023 TP
NOPR, and improve the representativeness of the test procedure.
DOE has determined that the recommendations specified in the ACUAC
and ACUHP Working Group TP Term Sheet are consistent with the EPCA
requirement that test procedures for covered equipment, including CUACs
and CUHPs, be reasonably designed to produce test results that reflect
energy efficiency, energy use, and estimated operating costs of a type
of industrial equipment (or class thereof) during a representative
average use cycle (as determined by the Secretary), and shall not be
unduly burdensome to conduct (42 U.S.C. 6314(a)(2)). As a result, DOE
is adopting a new test procedure in appendix A1 in accordance with the
Term Sheet. Therefore, DOE is amending the test procedure for CUACs and
CUHPs to adopt in the new appendix A1 the test provisions in AHRI 1340-
2023 and ASHRAE 37-2009. DOE is adopting the following sections of AHRI
1340-2023 in appendix A1: sections 3 (with certain exclusions),\15\ 4,
5 (excluding section 5.2), and 6.1 through 6.3, and appendices A, C, D
(excluding sections D.1 and D.2), and E. Use of appendix A1 will not be
required until the compliance date of amended energy conservation
standards denominated in terms of the new metrics in appendix A1,
should such standards be adopted.
---------------------------------------------------------------------------
\15\ DOE is not referencing the following provisions in section
3 of AHRI 1340-2023 because the terms are either defined at 10 CFR
431.92 or are not needed for the DOE test procedure: 3.2.2
(Barometric Relief Dampers), 3.2.3 (Basic Model), 3.2.5 (Commercial
and Industrial Unitary Air-conditioning Equipment), 3.2.5.1
(Commercial and Industrial Unitary Air-Conditioning System), 3.2.5.2
(Commercial and Industrial Unitary Heat Pump), 3.2.7 (Double-duct
System), 3.2.9 (Desiccant Dehumidification Component), 3.2.10 (Drain
Pan Heater), 3.2.11.1 (Air Economizer), 3.2.12 (Energy Efficiency
Ratio 2), 3.2.13 (Evaporative Cooling), 3.2.13.1 (Direct Evaporative
Cooling System), 3.2.13.2 (Indirect Evaporative Cooling System),
3.2.14 (Fresh Air Damper), 3.2.15 (Fire, Smoke, or Isolation
Damper), 3.2.17 (Hail Guard), 3.2.19 (Heating Coefficient of
Performance 2), 3.2.20 (High-Effectiveness Indoor Air Filtration),
3.2.22 (Indoor Single Package Air-conditioners), 3.2.23 (Integrated
Ventilation, Economizing, and Cooling Efficiency (IVEC)), 3.2.34
(Integrated Ventilation and Heating Efficiency (IVHE)), 3.2.29 (Non-
standard Ducted Condenser Fan), 3.2.31.2 (Boost2 Heating Operational
Level (B2)), 3.2.34 (Power Correction Capacitor), 3.2.35 (Powered
Exhaust Air Fan), 3.2.36 (Powered Return Air Fan), 3.2.37 (Process
Heat Recovery, Reclaim, or Thermal Storage Coil), 3.2.38 (Published
Rating), 3.2.41 (Refrigerant Reheat Coil), 3.2.42 (Single Package
Air-Conditioners), 3.2.43 (Single Package Heat Pumps), 3.2.45 (Sound
Trap), 3.2.46 (Split System), 3.2.51 (Steam or Hydronic Heat Coils),
3.2.53 (UV Lights), 3.2.55 (Ventilation Energy Recovery System
(VERS)), 3.2.56 (Year Round Single Package Air-conditioners), and
3.2.57 (Year Round Single Package Heat Pump).
---------------------------------------------------------------------------
As proposed, for appendices A and A1, DOE is incorporating by
reference ANSI/ASHRAE 37-2009. Appendices A and A1 reference all
sections of the industry test standard except sections 1 (Purpose), 2
(Scope), and 4 (Classifications).
2. Double-Duct Systems
As discussed in section III.B.3 of this final rule, double-duct
systems are equipment classes of ACUACs and ACUHPs, either single
package or split, designed for indoor installation in constrained
spaces, such that outdoor air must be ducted to and from the outdoor
coil.
Pursuant to the current DOE test procedure (which references ANSI/
AHRI 340/360-2007), double-duct systems are tested and rated under the
same test conditions at zero outdoor air ESP as conventional ACUACs and
ACUHPs (i.e., that are not double-duct systems). AHRI 340/360-2022
includes two different set of test provisions that can be used for
testing double-duct systems. Section 6.1.3.7 of AHRI 340/360-2022
includes provisions for measuring performance at zero outdoor air ESP
to determine the EER, IEER, and/or COP metrics, consistent with the
current DOE test procedure. AHRI 340/360-2022 added an additional test
method in appendix I for double-duct systems that specifies an outdoor
air ESP requirement of 0.50 in. H2O for double-duct systems.
When testing with 0.50 in. H2O outdoor air ESP, ratings are
designated with the subscript ``DD'' (e.g., EERDD,
COPDD, and IEERDD) to distinguish them from the
ratings determined by testing at zero outdoor air ESP. ASHRAE Standard
90.1-2022 does not include any separate provisions for double-duct
systems or the EERDD, COPDD, and/or
IEERDD metrics; therefore, testing per Appendix I to AHRI
340/360-2022 is not required per ASHRAE Standard 90.1-2022. As a
result, DOE's statutory obligation to consider the test procedures for
CUACs and CUHPs referenced in ASHRAE Standard 90.1 (per 42 U.S.C.
6314(a)(4)(A)) does not include Appendix I to AHRI 340/360-2022.
The ACUAC and ACUHP Working Group TP Term Sheet did not include
provisions for double-duct systems. However, the AHRI 1340-202X Draft
included provisions for determining the new IVEC and IVHE metrics for
double-duct systems. Specifically, similar to appendix I of AHRI 340/
360-2022, the AHRI 1340-202X Draft applied a 0.50 in. H2O
outdoor air ESP requirement for determining IVEC and IVHE for double-
[[Page 44003]]
duct systems. Other than this outdoor air ESP requirement, the AHRI
1340-202X Draft specified no differences in determining IVEC and IVHE
for double-duct systems as compared to conventional ACUACs and ACUHPs.
In the August 2023 TP NOPR, DOE proposed to: (1) maintain the existing
metrics for double-duct systems and reference AHRI 340/360-2022 for
double-duct systems in appendix A, and (2) adopt the IVEC and IVHE
metrics for double-duct systems in appendix A1 as specified in the AHRI
1340-202X Draft. 88 FR 56392, 56421-56422 (August 17, 2023).
In response, Carrier supported the adoption of the IVEC and IVHE
metric, as specified in AHRI 1340-202X, in appendix A1, as well as the
proposal to maintain the test procedure from AHRI 340/360-2022 in
appendix A without the provisions of appendix I of that test procedure.
(Carrier, No. 8 at p. 3) AHRI similarly supported the adoption of IVEC
and IVHE for double-duct systems in appendix A1. (AHRI, No. 15 at p. 2)
DOE notes that AHRI 1340-2023 maintains the same ESP conditions and
method for determining IVEC and IVHE for double-duct systems as the
method specified in the AHRI 1340-202X Draft. Because double-duct
systems are installed indoors with ducting of outdoor air to and from
the outdoor coil, DOE has concluded that testing at a non-zero outdoor
air ESP (as specified in the AHRI 1340-2023) would be more
representative of field applications than testing at zero outdoor air
ESP (as specified in the current Federal test procedure). DOE has also
concluded that the IVEC and IVHE metrics specified in AHRI 1340-2023
better capture actual energy use in the field than the COP, EER, and
IEER metrics specified in the current DOE test procedure, for the
reasons discussed throughout this final rule for ACUACs and ACUHPs more
generally. Further, DOE has concluded that the application of the IVEC
and IVHE metrics in AHRI 1340-2023 to double-duct systems reflect
industry consensus that these metrics are suitable for double-duct
systems. For these reasons and given the support expressed by
stakeholders, DOE is adopting the provisions in AHRI 1340-2023 for
determining IVEC and IVHE for double-duct systems in appendix A1.
As mentioned previously, the current cooling energy conservation
standards for double-duct systems are in terms of EER and the current
heating energy conservation standards are in terms of COP. Testing to
the IVEC and IVHE metrics will not be required until such time as
compliance is required with amended energy conservation standards for
double-duct systems denominated in terms of IVEC and IVHE, should DOE
adopt such standards. As discussed, DOE is also updating the current
test procedure for all CUACs and CUHPs, including double-duct systems,
in appendix A to reference AHRI 340/360-2022, maintaining the current
EER and COP metrics until the compliance date of any energy
conservation standards for double-duct systems denominated in terms of
IVEC and IVHE. As discussed, ASHRAE Standard 90.1-2022 does not include
any provisions specific to double-duct systems or standards denominated
in terms of the EERDD, COPDD, and/or
IEERDD metrics; therefore, testing double-duct systems at
non-zero outdoor air ESP per Appendix I to AHRI 340/360-2022 which
generates results in terms of EERDD, COPDD, and/
or IEERDD (as opposed to testing a zero outdoor air ESP per
section 6.1.3.7 of AHRI 340/360-2022 which generates results in terms
of EER, COP, and/or IEER) is not required per ASHRAE Standard 90.1-
2022. As a result, DOE's statutory obligation to consider the test
procedures for CUACs and CUHPs referenced in ASHRAE Standard 90.1 (per
42 U.S.C. 6314(a)(4)(A)) does not include Appendix I to AHRI 340/360-
2022.
3. ECUACs and WCUACs
a. Overall
The current DOE test procedure for ECUACs and WCUACs is specified
at 10 CFR 431.96 and includes the EER metric. The ACUAC and ACUHP
Working Group TP Term Sheet does not include provisions for ECUACs and
WCUACs. However, the AHRI 1340-202X Draft includes provisions for
determining the new IVEC and optional EER2 metric for ECUACs and
WCUACs. The AHRI 1340-202X Draft and AHRI 1340-2023 provisions for
determining IVEC and EER2 for ECUACs and WCUACs are largely the same as
the provisions for ACUACs and ACUHPs; however, there are several
provisions specific or unique to ECUACs and WCUACs, specifically
regarding: (1) ESP requirements, (2) test temperatures, and (3)
accounting for power of WCUAC heat rejection components.
In the August 2023 TP NOPR, DOE proposed to adopt the IVEC metric
for ECUACs and WCUACs in appendix A1, as specified in the AHRI 1340-
202X Draft, and sought comment on this proposal, including the test
temperature requirements. 88 FR 56392, 56419-56420 (August 17, 2023).
In response to the August 2023 TP NOPR, Carrier supported the
adoption of the IVEC metric for ECUACs and WCUACs in appendix A1 as
specified in the proposed AHRI 1340-202X Draft. (Carrier, No. 8 at p.
2) Carrier also commented that the working version of AHRI 1340 (at the
time of Carrier's comment) included updated test temperatures for
determining IVEC and EER2 for ECUACs and WCUACs, and Carrier presented
these updated test conditions. (Id.) AHRI also expressed support for
DOE's proposal to adopt the IVEC and IVHE metrics for ECUACs and
WCUACs. (AHRI, No. 15 at pp. 2, 5)
Trane supported the product classifications and water temperatures
for WCUACs in AHRI 1340 but did not support adopting the IVEC metric
for WCUACs as specified in AHRI 1340. Trane further stated that issues
specific to WCUACs need to be addressed in order to adopt an IVEC
metric for WCUACs that is truly representative of field applications.
Trane asserted that the provisions in AHRI 1340 do not adequately
consider the difference between indoor and outdoor single package units
and stated that the vast majority of WCUACs are indoor packaged units.
Trane further commented that WCUACs installed indoors most often use
waterside economizers rather than airside economizers and are typically
installed in the core of a multi-story office building, such that
outdoor air for economizing or ventilation is not introduced through
the WCUAC air handling section. Trane also commented that because
WCUACs typically distribute conditioned air only within a single floor
of a building, duct runs are typically shorter than for traditional
rooftop systems, and, therefore, the ESP conditions included in AHRI
1340 should be different for WCUACs. (Trane, No. 14 at pp. 3-4)
Regarding Trane's concerns about the IVEC metric for WCUACs, DOE
acknowledges that WCUACs have a range of applications that may not
always align with the assumptions included in the analyses to develop
the IVEC metric. However, DOE notes that this is also true for ACUACs
and ACUHPs, which serve a wide range of applications and operate in a
wide variety of different operating conditions. The intent of the IVEC
metric, as developed by the Working Group, was to representatively
capture performance of the U.S. national average of CUAC and CUHP
applications, understanding that this ``average performance'' cannot
perfectly represent the unique aspects of certain applications. DOE
notes that the IVEC metric is specified for WCUACs in the recently
published industry consensus test procedure AHRI 1340-
[[Page 44004]]
2023 consistent with DOE's proposals (with certain updated test
conditions, as discussed). Therefore, DOE understands AHRI 1340-2023
and the IVEC metric specified in the test procedure to represent
general industry consensus on a representative test procedure and
metric for CUACs and CUHPs, including WCUACs.
AHRI 1340-2023 includes updates to the provisions for determining
IVEC for ECUACs and WCUACs--specifically, the test temperature and
accounting for power of WCUAC heat rejection components. The ESP
requirements specified for ECUACs and WCUACs are unchanged from the
AHRI 1340-202X Draft. These provisions are discussed in detail in the
following subsections. DOE has concluded that the IVEC metric specified
in AHRI 1340-2023 for ECUACs and WCUACs (including the ESP
requirements, updated test temperatures, and updated WCUAC heat
rejection component power allowances) is consistent with the proposed
adoption of the IVEC metric specified in the AHRI 1340-202X Draft and
meets the criteria in 42 U.S.C. 6314(a)(2)-(3). Accordingly, DOE is
adopting the IVEC metric (as well as the optional EER2 metric) and
associated test provisions specified in AHRI 1340-2023 in appendix A1
for ECUACs and WCUACs.
As mentioned previously, the current energy conservation standards
for ECUACs and WCUACs are in terms of EER. Testing to the IVEC metric
will not be required until such time as compliance is required with
amended energy conservation standards for ECUACs and WCUACs denominated
in terms of IVEC, should DOE adopt such standards. As discussed, DOE is
also updating the current test procedure for all CUACs and CUHPs,
including ECUACs and WCUACs, in appendix A to reference AHRI 340/360-
2022, maintaining the current EER metric until the compliance date of
any energy conservation standards for ECUACs and WCUACs denominated in
terms of the IVEC metric. As discussed in section III.C.1 of this final
rule, DOE has concluded that this amendment in Appendix A is consistent
with the intent of the test procedure references for ECUACs and WCUACs
in the latest published version of ASHRAE Standard 90.1.
b. ESP Requirements for ECUACs and WCUACs
The IVEC and EER2 metrics include higher ESP requirements than the
current DOE test procedures and AHRI 340/360-2022. For ECUACs and
WCUACs with cooling capacity greater than or equal to 65,000 Btu/h, the
AHRI 1340-202X Draft specifies the same ESP requirements for
determining IVEC and EER2 for ECUACs and WCUACs as for ACUACs and
ACUHPs. For ECUACs and WCUACs with cooling capacity less than 65,000
Btu/h, there are no air-cooled equipment of comparable cooling capacity
within the scope of the AHRI 1340-202X Draft. Therefore, the AHRI 1340-
202X Draft includes an ESP requirement of 0.5 in. H2O for
testing ECUACs and WCUACs with cooling capacity less than 65,000 Btu/h,
which is consistent with the ESP requirement specified in AHRI 210/240-
2023 for comparable air-cooled equipment (i.e., air-cooled, three-phase
CUACs and CUHPs with cooling capacity less than 65,000 Btu/h). As
discussed in the August 2023 TP NOPR, DOE understood that the
provisions for determining IVEC and EER2 for ECUACs and WCUACs,
specifically including the higher ESP requirements outlined in the AHRI
1340-202X Draft, reflect industry consensus that the IVEC metric (and
optional EER2 metric) provide a more representative measure of energy
efficiency for ECUACs and WCUACs. 88 FR 56392, 56419-56420 (August 17,
2023). AHRI 1340-2023 maintains the same ESP requirements as those
outlined in the AHRI 1340-202X Draft. In this final rule, DOE maintains
its conclusion that the ESP requirements specified for ECUACs and
WCUACs in AHRI 1340-2023 are representative of field installations for
ECUACs and WCUACs. As such, DOE is adopting the ESP requirements for
testing ECUACs and WCUACs as outlined in AHRI 1340-2023.
c. ECUAC and WCUAC Test Temperatures and WCUAC Heat Rejection
Components
ECUACs and WCUACs use different test temperatures than ACUACs and
ACUHPs, and in the August 2023 TP NOPR, DOE presented test temperature
requirements for full-load and part-load test points for determining
IVEC for ECUACs and WCUACs, as specified in the AHRI 1340-202X Draft.
88 FR 56392, 56419-56420 (August 17, 2023).
WCUACs are typically installed in the field with separate heat
rejection components \16\ that reject heat from the water loop to
outdoor ambient air, but these separate heat rejection components are
not installed nor is their power measured during testing of WCUACs
under the current DOE test procedure. These heat rejection components
typically consist of a circulating water pump (or pumps) and a cooling
tower. To account for the power that would be consumed by these
components in field installations, section 6.1.1.7 of AHRI 340/360-2022
specifies that WCUACs with cooling capacities less than 135,000 Btu/h
shall add 10.0 W to the total power of the unit for every 1,000 Btu/h
of cooling capacity.
---------------------------------------------------------------------------
\16\ Separate heat rejection components (e.g., a cooling tower
or circulating water pump) are required for WCUACs but not used with
ACUACs or ECUACs. ACUACs and ECUACs contain all components needed to
reject heat to the ambient air surrounding the ACUAC or ECUAC.
WCUACs, however, reject heat to a building's water loop. Separate
components are needed to circulate the water in the water loop and
reject heat from the water loop to the ambient air surrounding the
building.
---------------------------------------------------------------------------
Section 6.2.4.3 of the AHRI 1340-202X Draft includes similar
provisions for accounting for the power of heat rejection components
for WCUACs to those in AHRI 340/360-2022. However, unlike AHRI 340/360-
2022, the heat rejection component power addition was not limited to
units with cooling capacities less than 135,000 Btu/h in the AHRI 1340-
202X Draft, and instead, it applied to WCUACs of all cooling
capacities. DOE proposed the adoption of the approach specified in the
AHRI 1340-202X Draft in the August 2023 TP NOPR. 88 FR 56392, 56420-
56421 (August 17, 2023).
As noted by Carrier's comment (summarized in section III.E.3.a of
this document), based on further discussions and analysis in AHRI
Commercial Unitary STC meetings after the issuance of the AHRI 1340-
202X Draft, the test conditions for ECUACs and WCUACs were updated in
the published AHRI 1340-2023. Additionally, AHRI 1340-2023 includes
different values to account for the power of heat rejection components
of WCUACs as compared to the AHRI 1340-202X Draft. Both of these
changes were related to a changed assumption in operation of cooling
towers in water loops serving WCUACs.
The analysis conducted to develop the heat rejection component
power adder and the WCUAC entering water temperature (``EWT'') test
conditions in the AHRI 1340-202X Draft assumed constant cooling tower
fan speed regardless of load level. In other words, the analysis to
develop the AHRI 1340-202X Draft method assumed that the cooling tower
fans do not slow down when there is less heat to reject in the cooling
tower, and thus: (1) the cooling tower fan power does not reduce at
lower load levels; and (2) the cooling tower approach \17\ reduces
significantly
[[Page 44005]]
at lower load levels. Specifically, as the cooling load reduces, the
same amount of cooling tower airflow is being provided to reject less
heat in the cooling tower, so the water is cooled in the cooling tower
to a temperature closer to the outdoor air wet-bulb temperature, and,
therefore, the water leaving the cooling tower (and entering the WCUAC)
is at a lower temperature, resulting in a lower WCUAC EWT test
condition.
---------------------------------------------------------------------------
\17\ For an evaporative cooling tower, the ``cooling tower
approach'' is the difference between the cold water temperature
(i.e., the temperature of the cooled water leaving the cooling
tower) and the outdoor air wet-bulb temperature.
---------------------------------------------------------------------------
The analysis conducted to develop the heat rejection component
power adder and the WCUAC EWT test conditions in AHRI 1340-2023 assumes
that variable frequency drives (``VFDs'') are used on cooling tower
fans to reduce cooling tower fan speed (and thus cooling tower fan
power) for lower cooling loads. The use of VFDs on cooling tower fans
impacts both the cooling tower fan power and the WCUAC EWT. First, the
cooling tower fan VFD reduces cooling tower fan power at part load.
Therefore, instead of a single power adder in W per 1,000 Btu/h of
cooling capacity applied regardless of the test being conducted (i.e.,
independent of the test bin) as specified in the AHRI 1340-202X Draft,
AHRI 1340-2023 includes four different condenser tower fan and pump
power rate adders (in units of W per 1,000 Btu/h of cooling capacity)--
a separate adder for each test bin, with the adders decreasing at lower
load levels. Second, the reduced cooling tower fan speed at part load
means that the cooling tower approach does not significantly reduce at
lower load levels, because cooling tower airflow driving heat transfer
in the cooling tower reduces along with the amount of heat
rejected.\18\ Correspondingly, the WCUAC part-load EWT test conditions
in AHRI 1340-2023 are higher than the EWT test conditions in the AHRI
1340-202X Draft. The EWT test conditions for WCUACs in AHRI 1340-2023,
which were developed based on the assumption that VFDs are used on
cooling tower fans to reduce cooling tower fan speed, are the same as
those included in Carrier's comment (Carrier, No. 8 at p. 2) in
response to the August 2023 TP NOPR.
---------------------------------------------------------------------------
\18\ For the AHRI 1340-2023 EWTs, the assumed cooling tower
approach is the same for B, C, and D bins -i.e., as shown in Table
III-3 and Table III-4, the difference between the outdoor air wet-
bulb temperature in Table III-3 and the EWT in Table III-4 is 8
[deg]F for the B, C, and D bins. Therefore, the EWT test conditions
in AHRI 1340-2023 decrease for each part-load bin by the same amount
as the outdoor air wet-bulb temperature test conditions.
---------------------------------------------------------------------------
Additionally, AHRI 1340-2023 includes slight changes to the outdoor
air wet-bulb temperature test conditions for ECUACs, based on updated
analysis of representative temperatures. The outdoor air wet-bulb
temperature requirements for ECUACs in AHRI 1340-2023 are the same as
those included in Carrier's comment (Carrier, No. 8 at p. 2) in
response to the August 2023 TP NOPR.
Table III-3 and Table III-4 show the test temperatures included in
the AHRI 1340-202X Draft and the final test temperatures included in
AHRI 1340-2023 for ECUACs and WCUACs, respectively.
[GRAPHIC] [TIFF OMITTED] TR20MY24.130
[GRAPHIC] [TIFF OMITTED] TR20MY24.131
[[Page 44006]]
Regarding the minor revisions to the ECUAC outdoor air wet-bulb
temperatures in AHRI 1340-2023, DOE has concluded that these updated
temperatures are representative of applications for ECUACs, and that
adopting these slight updates to the proposed ECUAC test temperatures
is consistent with the intent of the proposed approach and with
comments from Carrier that included these updated temperatures.
Therefore, in this final rule, DOE is adopting the ECUAC test
temperatures specified in AHRI 1340-2023.
Regarding the test temperatures and heat rejection component power
for WCUACs, DOE has concluded that VFDs are typically used on cooling
tower fans to reduce cooling tower fan speed with reduced cooling load,
and, therefore, concludes that assuming the presence of cooling tower
fan VFDs is a more representative basis for determining the WCUAC EWTs
and tower fan and pump power rate or ``TFPPR'' adders. Additionally,
DOE has concluded that the updates to the approach in AHRI 1340-2023
(i.e., updated WCUAC test temperatures and updated TFPPR approach) are
generally consistent with the approach proposed in the August 2023 TP
NOPR, but with more representative technical details. Further, DOE
concludes that adopting the updated WCUAC test temperatures (and, thus,
generally, the updated approach for developing WCUAC test temperatures
and TFPPR values that assumes cooling tower fan VFDs) is consistent
with comments from Carrier that included these updated temperatures.
However, DOE is aware of three issues in the WCUAC heat rejection
components power adders (referred to in AHRI 1340-2023 as the TFPPR)
used in Table 7 to AHRI 1340-2023. The first issue is a mismatch
between how the TFPPR values were developed and how they were
implemented in AHRI 1340-2023. Specifically, the TFPPR values in Table
7 to AHRI 1340-2023 were determined based on the full-load cooling
capacity; therefore, the TFPPR value for each bin was intended to be
multiplied by the full-load capacity. However, the approach implemented
in AHRI 1340-2023 is inconsistent with these values--specifically,
equations 8, 10, 11, and 13 specify to multiply the TFPPR by the
cooling capacity determined for the test(s) performed for a given
cooling bin. Because part-load cooling capacities are lower than full-
load cooling capacities, multiplying the TFPPR value for a part-load
cooling bin by the part-load capacity for that bin results in an
unrepresentatively low tower fan and pump power calculated for the bin.
To resolve this issue, DOE has concluded that the values should instead
be based on the target cooling capacity for each part-load cooling bin,
which aligns with the approach in equations 8, 10, 11, and 13 of AHRI
1340-2023 (i.e., multiplying the TFPPR values by the measured cooling
capacity for each bin).
The second issue is that the full-load cooling tower fan power was
developed without consideration of the cooling tower fan motor
efficiency; therefore, the calculation reflected a fan motor efficiency
of 100 percent. Because 100 percent is a physically impossible motor
efficiency (and, therefore, underestimates the amount of power a fan
motor consumes), DOE has concluded that the TFPPR values should include
a more representative (i.e., lower) full-load fan motor efficiency.
The third issue is that the TFPPR values in AHRI 1340-2023 are
based on an unrepresentatively low fan power at low loads.
Specifically, the fan power was assumed to decrease cubically with
decreasing cooling load.\19\ However, this assumption does not account
for VFD, motor, and transmission losses which do not decrease cubically
with decreasing cooling load. At low cooling load (e.g., for the D
bin), this significantly underestimates cooling tower fan power because
the VFD, motor, and transmission losses are underestimated. DOE has
concluded that a more representative approach would be to account for
the VFD, motor, and transmission losses when developing the
relationship between cooling tower fan power and load. Accounting for
these losses impacts the TFPPR values for the B, C, and D part-load
bins.
---------------------------------------------------------------------------
\19\ The theoretical fan laws indicate that fan power decreases
cubically with decreasing fan speed. It was assumed that cooling
tower fan speed is proportional to cooling load (i.e., heat to be
rejected in the cooling tower), and, therefore, that cooling tower
fan power decreases cubically with decreasing cooling load.
---------------------------------------------------------------------------
Corrected TFPPR values that address these three issues with the
values published in AHRI 1340-2023 are shown in Table III-5. DOE
understands that the AHRI Commercial Unitary STC also plans to address
the aforementioned issues with the TFPPR values that were published in
AHRI 1340-2023. DOE expects that AHRI will consider including the
corrected TFPPR values shown in Table III-5 and adopted in this final
rule in a future version of AHRI 1340.
[GRAPHIC] [TIFF OMITTED] TR20MY24.132
For the reasons discussed in detail in the previous paragraphs, DOE
has concluded that the updated TFPPR values shown in Table III-5 are
generally consistent with the approach proposed in the August 2023 TP
NOPR, but that the corrected TFPPR values provide a more representative
accounting of WCUAC heat rejection component power than the values
published in AHRI 1340-2023 or the AHRI 1340-202X Draft.
For these reasons, DOE is adopting the updated WCUAC IVEC test
temperatures for IVEC in AHRI 1340-2023 and the TFPPR approach in AHRI
1340-2023 as modified by the revised TFPPR values shown in Table III-5.
4. IVHE for Colder Climates
As discussed in the August 2023 TP NOPR (see 88 FR 56392, 56416
(August 17, 2023)), it is likely that in the future manufacturers will
develop CUHPs that
[[Page 44007]]
are designed for operation in colder climates, and correspondingly that
the market for CUHPs in colder climates is expected to grow. Because
the IVHE metric is based on the US national average climate across all
US climate zones, the lowest bin temperature for calculating IVHE is
15.9 [deg]F, and a small fraction of heating hours are at colder
temperatures (i.e., 19 percent of heating hours are in a load bin with
a temperature colder than 32 [deg]F, and less than 1 percent of heating
hours are in a load bin with a temperature colder than 17 [deg]F).
As a result, the AHRI 1340-202X Draft includes provisions that are
distinct from the provisions used for IVHE, including weighting factors
and temperature bins, for calculating a colder climate-specific IVHE
metric, designated as IVHEC. Specifically, IVHEC
was developed using the same building heating analysis that was used to
develop IVHE (as discussed in section III.D.2 of this final rule), but
the IVHEC weighting factors and load bins were developed
using the results for climates zones 5 and above (i.e., climate zone 5
as well as all climate zones colder than climate zone 5), weighted by
the share of the U.S. population in each of those climate zones. The
use of only climate zones 5 and colder for IVHEC results in
the following, compared to IVHE: lower outdoor dry-bulb temperature for
each load bin, more heating season hours in all load bins, and a higher
heating season building load. Specifically, for IVHEC, 56
percent of heating hours are in a load bin with a temperature colder
than 32 [deg]F, and 12 percent of heating hours are in a load bin with
a temperature colder than 17 [deg]F. Further, because the defrost
degradation coefficients specified in appendix C of the ACUAC and ACUHP
Working Group TP Term Sheet depend on the outdoor temperature for each
load bin (and IVHEC has colder bin temperatures than IVHE),
the AHRI 1340-202X Draft also specifies separate defrost degradation
coefficients for calculating IVHEC. In the August 2023 TP
NOPR, DOE proposed to adopt provisions for determining the
IVHEC metric in appendix A1 via reference to the AHRI 1340-
202X Draft and to allow for optional representations of
IVHEC for CUHPs. 88 FR 56392, 56416 (August 17, 2023).
In response to the August 2023 TP NOPR, NEEA and NYSERDA supported
DOE's proposal to include in the test procedure and allow optional
representations of the colder climate IVHEC. (NEEA, No. 16
at pp. 2-3; NYSERDA, No. 13 at p. 2)
Given the potential for the development of CUHPs designed for
operation in colder climates and the expected increased number of
shipments of CUHPs into colder climates, DOE recognizes the utility in
having CUHP ratings for a separate IVHE metric that is specific to
colder climates. AHRI 1340-2023 includes provisions for determining
IVHEC that are generally consistent with the AHRI 1340-202X
Draft, with the additional specificity discussed in section III.E.8 of
this final rule. Correspondingly, DOE has concluded that the
IVHEC metric as specified in AHRI 1340-2023 (including the
minor updates in the published AHRI 1340-2023 that provide additional
specificity as discussed in section III.E.8 of this document) is more
representative of field conditions for CUHPs installed in colder US
climates. Therefore, DOE is adopting provisions for determining the
IVHEC metric in appendix A1 via reference to AHRI 1340-2023
and allowing for optional representations of IVHEC for
CUHPs. Specifically, DOE is amending the test procedure so that IVHE
will be the regulated heating metric when testing to appendix A1;
therefore, should DOE adopt amended standards for CUHPs denominated in
terms of IVEC and IVHE, all CUHPs will be required to certify
compliance with IVHE standards, and additional representations of
IVHEC will be optional.
5. Test Conditions Used for Current Metrics in Appendix A
AHRI 340/360-2022 designates certain test conditions for test
procedures characterized as ``standard rating tests'' and certain other
test conditions for test procedures characterized as ``performance
operating tests.'' The ``standard rating tests'' are used for
determining representations of cooling capacity, heating capacity, and
cooling and heating efficiencies. The ``performance operating tests''
evaluate other operating conditions, such as ``maximum operating
conditions'' (see section 8 of AHRI 340/360-2022). Specifically, Table
6 of AHRI 340/360-2022 specifies test conditions for standard rating
and performance operating tests for CUACs and CUHPs. The relevant
conditions for EER and IEER cooling tests are those referred to as
``standard rating conditions'' in AHRI 340/360-2022.
To clarify this distinction and consistent with its proposal to
adopt AHRI 340/360-2022 in appendix A, DOE proposed in the August 2023
TP NOPR to specify explicitly in section 3 of appendix A that the
cooling test conditions used for representations as required under the
DOE regulations would be: (1) for equipment subject to standards in
terms of EER, the ``Standard Rating Conditions, Cooling'' conditions
specified in Table 6 of AHRI 340/360-2022; and (2) for equipment
subject to standards in terms of IEER, the ``Standard Rating
Conditions, Cooling'' and ``Standard Rating Part-Load Conditions
(IEER)'' conditions specified in Table 6 of AHRI 340/360-2022. 88 FR
56392, 56412 (August 17, 2023).
For heating mode tests of CUHPs, Table 6 of AHRI 340/360-2022
includes ``Standard Rating Conditions'' for both a ``High Temperature
Steady-state Test for Heating'' and a ``Low Temperature Steady-state
Test for Heating'' (conducted at 47 [deg]F and 17 [deg]F outdoor air
dry-bulb temperatures, respectively). To clarify which conditions are
applicable for representations as required under the DOE regulations
and consistent with its proposal to adopt AHRI 340/360-2022 in appendix
A, DOE proposed to specify explicitly in section 3 of appendix A that
the heating test conditions used for compliance are the ``Standard
Rating Conditions (High Temperature Steady-state Heating)'' conditions
specified in Table 6 of AHRI 340/360-2022. Further, DOE proposed to
include the low-temperature (i.e., 17 [deg]F) heating test condition
specified in Table 6 of AHRI 340/360-2022 (referred to as ``Low
Temperature Steady-state Heating'') and specify in section 3 of
appendix A that representations of COP at this low-temperature heating
condition are optional. 88 FR 56392, 56412 (August 17, 2023).
DOE did not receive any comments in response to these proposals.
Therefore, DOE is adopting the specification of the relevant test
conditions in AHRI 340/360-2022 in appendix A as proposed. These
amendments in appendix A are consistent with the test requirements
referenced in the latest version of ASHRAE Standard 90.1.
6. Test Conditions Used for New Metrics in Appendix A1
Consistent with DOE's proposal to adopt the AHRI 1340-202X Draft
for determining IVEC and IVHE, as discussed more fully in the August
2023 TP NOPR, DOE proposed to specify in section 3 of the proposed
appendix A1 which test conditions in the AHRI 1340-202X Draft would be
required and optional for rating to IVEC and IVHE. 88 FR 56392, 56412-
56413 (August 17, 2023). DOE also proposed to include provisions for
optional representations of the full-load efficiency metrics, EER2,
COP247, COP217, and COP25, and
specified the test conditions required for these optional
representations. Id. DOE did not receive any comments regarding
[[Page 44008]]
the proposed approach for specifying the required and optional test
conditions. The test conditions in AHRI 1340-2023 align with those in
the AHRI 1340-202X Draft except for certain test conditions for ECUACs
and WCUACs, which are discussed in section III.E.3 of this final rule.
Therefore, DOE is adopting the specification of test conditions in
appendix A1 as proposed, referencing the corresponding test conditions
in the published AHRI 1340-2023.
7. Provisions Introduced in the AHRI 1340-202X Draft
The AHRI 1340-202X Draft proposed for adoption in the August 2023
TP NOPR includes several provisions regarding the new IVEC and IVHE
metrics that are not included in the ACUAC and ACUHP Working Group TP
Term Sheet. DOE notes that the ACUAC and ACUHP Working Group TP Term
Sheet includes provisions to allow changes to the recommendations in
the term sheet if mistakes in the original recommendations are
identified through further analysis or discussion between stakeholders.
(See EERE-2022-BT-STD-0015-0065, Recommendations #2, #8, #11) Further,
the AHRI 1340-202X Draft includes a number of additional test
provisions that arose as a result of discussions between many
interested stakeholders participating in the AHRI Commercial Unitary
STC and that DOE has concluded are consistent with the intent of the
ACUAC and ACUHP Working Group TP Term Sheet but provide additional
guidance for determining IVEC and IVHE. DOE included discussion of
provisions regarding the topics discussed in the following sub-sections
in the August 2023 TP NOPR and proposed to adopt the provisions in the
AHRI 1340-202X Draft regarding all of these topics. 88 FR 56392, 56416-
56419 (August 17, 2023). DOE did not receive comment regarding the
provisions in the AHRI 1340-202X Draft addressing these topics, and
these provisions are also included in the published AHRI 1340-2023,
consistent with DOE's proposals in the August 2023 TP NOPR. As
discussed, DOE is adopting AHRI 1340-2023 for determining IVEC and IVHE
in appendix A1, including these additional provisions not specified in
the ACUAC and ACUHP Working Group TP Term Sheet, consistent with
proposals in the August 2023 TP NOPR. The following sections discuss
these provisions in further detail.
a. Cooling Weighting Factors Adjustment
Subsequent to the development of the ACUAC and ACUHP Working Group
TP Term Sheet, additional analysis of the building models used to
develop the weighting factors for the IVEC metric indicated that the
recommended weighting hours included in the ACUAC and ACUHP Working
Group TP Term Sheet are incorrect. Specifically, the weighting hour
factors in the ACUAC and ACUHP Working Group TP Term Sheet over-
represent mechanical-only cooling hours and underrepresent economizer-
only and integrated-economizer hours for all IVEC load bins. DOE
presented corrected weighting factors during the ACUAC and ACUHP
standards negotiations, and no concerns were raised. (See EERE-2022-BT-
STD-0015-0078 at p. 8) These corrected IVEC weighting factors were
included in the AHRI 1340-202X Draft and remain the same in AHRI 1340-
2023. DOE is adopting AHRI 1340-2023 for determining IVEC and IVHE in
appendix A1, including these updated IVEC weighting factors.
b. ESP Testing Target Calculation
Recommendation #12 of the ACUAC and ACUHP Working Group TP Term
Sheet includes an equation for determining adjusted ESP for cooling or
heating tests that use an airflow that differs from the full-load
cooling airflow. However, the equation specified in Recommendation #12
is missing a term for the full-load ESP. This equation was corrected in
the AHRI 1340-202X Draft and remains the same in AHRI 1340-2023. DOE is
adopting AHRI 1340-2023 for determining IVEC and IVHE in appendix A1,
including this corrected equation for determining adjusted ESP.
c. Test Instructions for Splitting ESP Between Return and Supply Duct
As discussed previously, Recommendation #12 of the ACUAC and ACUHP
Working Group TP Term Sheet specifies that ESP shall be split between
return and supply ducts during testing, such that 25 percent of the ESP
is applied in the return ductwork. However, the ACUAC and ACUHP Working
Group TP Term Sheet does not contain explicit test se-tup instructions
specifying how to achieve the split in ESP between return and supply
ductwork. Section E11 in appendix E of the AHRI 1340-202X Draft and
section E11 in appendix E of AHRI 1340-2023 include more detailed
instructions regarding the duct and pressure measurement set-up, the
measurement and adjustment of the return static pressure, and the
restriction devices that can be used in the return ductwork to achieve
the required split of between 20 and 25 percent of the total ESP
applied to the return ductwork. The AHRI 1340-202X Draft and AHRI 1340-
2023 also include the same test instructions for cases in which the ESP
split is not achieved in the first test, as well as any exceptions to
the specified tolerance requirement. DOE has concluded that these
additional instructions provide a more consistent measurement of ESP
and are aligned with the intent of Recommendation #12 of the ACUAC and
ACUHP Working Group TP Term Sheet. Therefore, DOE is adopting these
provisions of AHRI 1340-2023 for determining IVEC and IVHE.
d. Default Fan Power and Maximum Pressure Drop for Coil-Only Systems
DOE's current test procedure for CUACs and CUHPs references ANSI/
AHRI 340/360-2007, and section 6.1 of that test standard specifies
default fan power and corresponding capacity adjustment for ACUACs,
ACUHPs, ECUACs, and WCUACs with a coil-only configuration (i.e.,
without an integral indoor fan). Specifically, ANSI/AHRI 340/360-2007
requires that an indoor fan power of 365 Watts (``W'') per 1,000
standard cubic feet per minute (``scfm'') be added to power input for
coil-only units and that the corresponding heat addition (i.e., 1,250
Btu/h per 1,000 scfm) be subtracted from measured cooling capacity (and
added to measured heating capacity), regardless of the capacity of the
unit under test and regardless of full-load or part-load test
conditions.
Section 6.1.1.6 of AHRI 340/360-2022 has the same requirement as
ANSI/AHRI 340/360-2007 regarding default fan power and capacity
adjustment of coil-only systems. Additionally, both section 6.1.3.2(d)
of ANSI/AHRI 340/360-2007 and section 6.1.3.3.4 of AHRI 340/360-2022
specify that for coil-only systems, the pressure drop across the indoor
assembly shall not exceed 0.30 in. H2O for the full-load
cooling test. If the measured pressure drop exceeds that value, then
the industry test standards specify that the indoor airflow rate be
reduced such that the measured pressure drop does not exceed the
specified maximum pressure drop.
The AHRI 1340-202X Draft included different requirements for
testing coil-only units as compared to ANSI/AHRI 340/360-2007 and AHRI
340/360-2022. First, section 5.17.4 of the AHRI 1340-202X Draft
includes a higher maximum pressure drop across the indoor assembly of
1.0 in. H2O when testing
[[Page 44009]]
coil-only units, as compared to the maximum pressure drop of 0.3 in.
H2O specified in ANSI/AHRI 340/360-2007 and AHRI 340/360-
2022. Second, section 6.2.4.2 of the AHRI 1340-202X Draft includes
higher default fan power values than specified in ANSI/AHRI 340/360-
2007 and AHRI 340/360-2022; these values were updated to reflect the
higher ESP requirements used for IVEC and IVHE. Because the ACUAC and
ACUHP Working Group TP Term Sheet and the AHRI 1340-202X Draft specify
ESP requirements that vary by capacity bin, section 6.2.4.2 of the AHRI
1340-202X Draft specifies different default fan power adders and
capacity adjustments for each capacity bin, developed based on fan
power needed to overcome the ESP requirement for each bin. DOE proposed
in the August 2023 TP NOPR to adopt the default fan power adders and
capacity adjustments included in the AHRI 1340-202X Draft in appendix
A1. 88 FR 56392, 56417 (August 17, 2023).
Lastly, while ANSI/AHRI 340/360-2007 and AHRI 340/360-2022 specify
a single default fan power adder (and corresponding capacity
adjustment) to be used for all tests, the AHRI 1340-202X Draft included
separate default fan power adders and capacity adjustments for full-
load tests and part-load tests (i.e., tests conducted at an airflow
lower than the full-load cooling airflow) to reflect that fan power
does not decrease linearly with airflow (i.e., reducing airflow in
part-load operation would reduce fan power in field operation by more
than would be calculated using a single power adder that is normalized
by airflow). These part-load fan power adders and capacity adjustments
were developed assuming a part-load airflow that is 67 percent of the
full-load airflow. The AHRI 1340-202X Draft does not specify what
values to use if the part-load airflow is between 67 and 100 percent of
the full-load airflow. Alongside proposing to adopt the fan power
adders specified in the AHRI 1340-202X Draft in the August 2023 TP
NOPR, DOE proposed to adopt a linear interpolation approach in appendix
A1 in the case where the part-load airflow for coil-only CUACs and
CUHPs specified by a manufacturer for a test is between 67 and 100
percent of the full-load airflow, which would specify how to calculate
the default fan power coefficient and capacity adjustment in such
cases. 88 FR 56392, 56417 (August 17, 2023). The proposed approach is
consistent with the approach adopted for the residential CAC/HP test
procedure.\20\
---------------------------------------------------------------------------
\20\ The CAC/HP test procedure final rule was published in the
Federal Register on October 25, 2022, and can be found at 87 FR
64550.
---------------------------------------------------------------------------
Consistent with the basis of part-load values in the AHRI 1340-202X
Draft on 67 percent of full-load cooling airflow, DOE also proposed in
the August 2023 TP NOPR to clarify that for tests in which the
manufacturer-specified airflow is less than the full-load cooling
airflow, the target airflow for the test must be the higher of: (1) the
manufacturer-specified airflow for the test; or (2) 67 percent of the
airflow measured for the full-load cooling test. 88 FR 56392, 56417
(August 17, 2023).
AHRI 1340-2023 includes provisions consistent with those DOE
proposed to adopt for testing coil-only units in the August 2023 TP
NOPR. Id. Specifically, the already discussed maximum pressure drop and
capacity and fan power adjustments included in sections 5.17.4 and
6.2.4.2 of the AHRI 1340-202X Draft are included in sections 5.17.2 and
6.2.4.3 of AHRI 1340-2023. Additionally, AHRI 1340-2023 includes
provisions consistent with DOE's proposals regarding issues for testing
coil-only units not addressed in the AHRI 1340-202X Draft.
Specifically, section 6.2.4.2 of AHRI 1340-2023 includes the linear
interpolation method to address cases in which the part-load airflow
specified by a manufacturer for a test is between 67 and 100 percent of
the full-load airflow. Further, section 5.18.4.2 of AHRI 1340-2023
includes the clarification regarding which target airflow should be
used for tests in which the manufacturer-specified airflow is less than
the full-load cooling airflow.
Accordingly, DOE has concluded that the coil-only test procedure in
AHRI 1340-2023 aligns with the approach proposed in the August 2023 TP
NOPR and represents industry consensus on the most appropriate and
representative way to test and determine the IVEC and IVHE of coil-only
systems. Therefore, DOE is adopting these provisions of AHRI 1340-2023
for determining IVEC and IVHE for coil-only units.
e. Component Power Measurement
Section E10 of the AHRI 1340-202X Draft and AHRI 1340-2023 include
additional instruction regarding how the total unit, indoor fan,
controls, compressor, condenser section, and crankcase heat power
should be measured and accounted for during a test. This includes
details that were not included in the ACUAC and ACUHP Working Group TP
Term Sheet, as well as updates to address issues such as unique model
designs and power meter precision that were identified after the term
sheet was completed. For example, although the ACUAC and ACUHP Working
Group TP Term Sheet specified that controls power be determined by
subtracting all other power measurements from the total unit power,
sections E10.1 and E10.2 of both the AHRI 1340-202X Draft and AHRI
1340-2023 require that controls power be measured. This is because
controls power is a much smaller value than power consumed by other
components of a CUAC or CUHP and, thus, is more accurately determined
by measuring directly with a power meter of sufficient precision.
Section E10.2 of both the AHRI 1340-202X Draft and AHRI 1340-2023 also
allow for determination of compressor and condenser section power by
measurement together or by subtraction from total power (i.e., separate
power measurement of power consumed by the compressor and condenser
section is not required). These provisions address cases in which
unique wiring of certain models may make separate measurement of
compressor and condenser section power very difficult or impossible, in
addition to cases in which the laboratory does not have enough power
meters to measure all components separately. Section E10.3 of both the
AHRI 1340-202X Draft and AHRI 1340-2023 also provide an equation for
calculating default value(s) for crankcase heater power to address the
case in which a manufacturer does not specify crankcase heater
wattage.\21\ Because DOE has concluded that these provisions will
provide more repeatable and representative test results, DOE is
adopting AHRI 1340-2023 for determining IVEC and IVHE in appendix A1,
including these provisions for component power measurement.
---------------------------------------------------------------------------
\21\ As discussed, Recommendation #13 of the ACUAC and ACUHP
Working Group TP Term Sheet requires that manufacturers certify
crankcase heater wattage for each heater. DOE is not adopting
amendments to certification requirements in this rulemaking, and
will instead address certification requirements in a separate
rulemaking for certification, compliance, and enforcement.
---------------------------------------------------------------------------
f. Non-Standard Low-Static Indoor Fan Motors
As discussed in section III.D.1 of this document, DOE is adopting
higher ESPs recommended by the Working Group and included in AHRI 1340-
2023 in the appendix A1 Federal test procedure for CUACs and CUHPs.
However, individual models of CUACs and CUHPs with indoor fan motors
intended
[[Page 44010]]
for installation in applications with a low ESP may not be able to
operate at the adopted full-load ESP requirements at the full-load
indoor rated airflow. To address this situation, section 3.25 of the
AHRI 1340-202X Draft and section 3.2.30 of AHRI 1340-2023 both define
``non-standard low-static indoor fan motors'' as motors which cannot
maintain ESP as high as specified in the test procedure when operating
at the full-load rated indoor airflow and that are distributed in
commerce as part of an individual model within the same basic model
that is distributed in commerce with a different motor specified for
testing that can maintain the required ESP. Section 5.19.3.3 of the
AHRI 1340-202X Draft and section 5.19.3.3 of AHRI 1340-2023 include the
same test provisions for CUACs and CUHPs with non-standard low-static
indoor fan motors that cannot reach the ESP within tolerance during
testing, which require using the maximum available fan speed that does
not overload the motor or motor drive, adjusting the airflow-measuring
apparatus to maintain airflow within tolerance, and operating with an
ESP as close as possible to the minimum ESP requirements for testing.
This approach is consistent with the industry test standard referenced
by the DOE test procedure for DX-DOASes (AHRI 920-2020).
As discussed in section III.F.5.a of this document, DOE is
clarifying that representations for a CUAC or CUHP basic model must be
based on the least efficient individual model(s) distributed in
commerce within the basic model (with the exception specified in 10 CFR
429.43(a)(3)(vi)(A) for certain individual models with the components
listed in table 6 to 10 CFR 429.43(a)(3)). DOE has concluded that the
combination of: (1) the provisions in AHRI 1340-2023 for testing models
with ``non-standard low-static indoor fan motors'' with (2) the
requirement that basic models be rated based on the least efficient
individual model (with certain exceptions, as discussed) provides an
appropriate approach for handling CUAC and CUHP models with these
motors--if an individual model with a non-standard low-static indoor
fan motor is tested, the test will be conducted at an indoor airflow
representative for that model. But because testing at the rated airflow
for such an individual model will result in testing at an ESP lower
than the requirement and, thus, a lower indoor fan power, the
representations for that basic model will be required to be based on an
individual model with an indoor fan motor that can achieve the ESP
requirements at the rated airflow. Consistent with the adoption of AHRI
340/360-2023 in appendix A1, DOE is not deviating from the provisions
for testing models with non-standard low-static indoor fan motors.
g. IVHE Equations
Section 6.3 of the AHRI 1340-202X Draft and section 6.3 of AHRI
1340-2023 both include several changes regarding the heating metric
equations that differ from the provisions in appendix C of the ACUAC
and ACUHP Working Group TP Term Sheet. DOE has concluded that these
updated IVHE equations, described in the following paragraphs, provide
for a more accurate calculation of IVHE. Further, Recommendation #9 of
the ACUAC and ACUHP Working Group TP Term Sheet states that the
equations in appendix C of the term sheet are subject to quality
control checking (``QC'') for errors, with the intent remaining the
same as voted on. DOE has concluded that the discussed deviations in
the AHRI 1340-202X Draft and the published AHRI 1340-2023 hold the same
intent of the recommendations set forth in the ACUAC and ACUHP Working
Group TP Term Sheet. Therefore, DOE is adopting the provisions of AHRI
1340-2023 for determining IVHE in appendix A1, including the updated
equations discussed in this section.
1. Removal of the cut-out factor from certain equations: Appendix C
of the ACUAC and ACUHP Working Group TP Term Sheet includes a cut-out
factor in IVHE calculations to reflect the dependence of unit
performance on whether compressors are cut-out at a given bin
temperature. However, the cut-out factor was inadvertently included in
certain equations in appendix C of the ACUAC and ACUHP Working Group TP
Term Sheet where it should not apply (i.e., equations to determine unit
performance that should not be impacted by the fraction of time in
which compressors are cut out). Therefore, in the AHRI 1340-202X Draft
and AHRI 1340-2023, the cut-out factor is removed from those equations
where it was incorrectly applied in the ACUAC and ACUHP Working Group
TP Term Sheet. For all CUHPs that DOE is aware of on the market today,
the cut-in and cut-out temperatures are less than the temperature of
the lowest load bin. As such, the cut-out factor only applies when the
unit is operating at full-load capacity and does not affect the
calculation of IVHE.
2. Accounting for auxiliary heat when compressors are cut out: When
compressors are cut out, auxiliary heat would operate to meet the
building load. This auxiliary heat operation is addressed in section b
of appendix C of the ACUAC and ACUHP Working Group TP Term Sheet (i.e.,
when building load exceeds the highest stage unit heating capacity at a
given bin temperature), but was inadvertently excluded in sections c
and d of appendix C of the ACUAC and ACUHP Working Group TP Term Sheet
(i.e., when building load is between capacities of a unit tested with
multiple heating stages, or when building load is less than the
capacity for the lowest tested compressor stage). Therefore, the AHRI
1340-202X Draft and AHRI 1340-2023 include corrections in these cases
so that auxiliary heat demand is applied to meet building load in all
cases in which compressors are cut out.
3. Fan power applied in auxiliary heat-only mode: In appendix C of
the Term Sheet, the equations do not subtract the heat gain in the
indoor airstream from the indoor fan (i.e., ``fan heat'') from the
auxiliary heat demand. The AHRI 1340-202X Draft and AHRI 1340-2023
address this issue by subtracting fan heat from auxiliary heat demand.
Additionally, sections c and d of appendix C of the ACUAC and ACUHP
Working Group TP Term Sheet assume that the fan would be either cycling
between airflows when cycling between stages of compression or
operating at the lowest-measured indoor airflow for any cooling or
heating test when cycling on and off at the lowest stage of
compression; however, the indoor fan would likely be operating at the
airflow corresponding to the full-load heating test when operating in
auxiliary heat mode. The AHRI 1340-202X Draft and AHRI 1340-2023
address this by applying fan power from the full-load heating test for
auxiliary heat-only mode. However, DOE notes that because both fan heat
and auxiliary heat apply heat to the indoor airstream with the same
efficiency (i.e., COP of 1), the airflow assumed for auxiliary heat-
only mode does not impact results, as the fan heat resulting from an
increase in fan power reduces the auxiliary heat needed to meet the
building load by the same amount, resulting in no net change to
calculated IVHE.
4. Interpolation for variable-speed compressor systems: When
building load is between capacities of a unit tested with multiple
heating stages, section c of appendix C of the Term Sheet includes a
separate method for interpolating between stages for variable-speed
compressor systems (i.e., a method that interpolates capacity divided
by power) from the method for all other units (i.e., a method that
linearly interpolates power). As part of
[[Page 44011]]
development of the AHRI 1340-202X Draft, it was determined that there
were insufficient data to support a separate interpolation method for
variable-speed compressor systems, and, therefore, the AHRI 1340-202X
Draft and AHRI 1340-2023 apply the same linear interpolation method
based on power for all units. The linear interpolation method for
variable-speed compressor systems included in the AHRI 1340-202X Draft
is also maintained in AHRI 1340-2023.
5. Compressor operating levels for heating tests: Recommendation #9
of the Term Sheet includes details on the required and optional tests
based on configuration of the system (i.e., single-stage, two or more
stages, and variable-capacity). Required tests include a test at
``high'' operating level at 17 [deg]F and 47 [deg]F; optional tests
include tests at low and intermediate operating levels at 17 [deg]F and
47 [deg]F, as well as high and ``boost'' operating levels at 5 [deg]F.
For variable-capacity systems, the Term Sheet specifies that the high
speed and low speed at each temperature should be the normal maximum
and minimum for each ambient temperature. The AHRI 1340-202X Draft
includes additional explanation of which compressor speeds correspond
to the low, medium, high, and boost designations at each test
temperature. AHRI 1340-2023 maintains the explanations included in AHRI
1340-202X Draft and includes further explanation of the compressor
operating levels, as discussed in section III.E.8.b of this final rule.
In the August 2023 TP NOPR, DOE tentatively concluded that these
updated IVHE equations as described in the preceding paragraphs would
provide for a more accurate calculation of IVHE. 88 FR 56392, 56419
(August 17, 2023). Further, Recommendation #9 of the ACUAC and ACUHP
Working Group TP Term Sheet states that the equations in appendix C of
the Term Sheet are subject to quality control checking (``QC'') for
errors with the intent remaining the same as voted on. In the August
2023 TP NOPR, DOE tentatively concluded that the discussed deviations
in the AHRI 1340-202X Draft hold the same intent of the recommendations
set forth in the ACUAC and ACUHP Working Group TP Term Sheet.
Therefore, DOE proposed to adopt the provisions of AHRI 1340-202X Draft
for determining IVHE in appendix A1, including the updated equations
discussed in this section. 88 FR 56392, 56418-56419 (August 17, 2023).
AHRI 1340-2023 includes the largely the same provisions as AHRI
1340-202X Draft for determining IVHE. Any differences between the
provisions in AHRI 1340-202X Draft and AHRI 1340-2023 are discussed in
section III.E.8 of this final rule. Therefore, DOE has concluded that
that the updated IVHE equations in AHRI 1340-2023, as described in the
preceding paragraphs, would provide for a more accurate calculation of
IVHE than the equations in the ACUAC and ACUHP Working Group TP Term
Sheet, and that the discussed deviations hold the same intent as the
recommendations set forth in the ACUAC and ACUHP Working Group TP Term
Sheet. Therefore, DOE is adopting in appendix A1 the approach for
determining IVHE from AHRI 1340-2023.
DOE notes that appendix C of the ACUAC and ACUHP Working Group TP
Term Sheet includes a provision that ``additional provisions, still TBD
would apply for variable-speed compressors for which pairs of full-
speed or minimum-speed tests are not run at the same speed.'' (See
EERE-2022-BT-STD-0015-0065 at p. 14) The AHRI 1340-202X Draft does not
include any provisions allowing for determination of capacity for a bin
by interpolating between tests conducted at different compressor
operating levels. In the August 2023 TP NOPR, DOE tentatively concluded
that this approach is appropriate and that calculating IVHE with
results from multiple tests at each compressor operating level would
provide representative ratings for manufacturers that choose to include
performance at operating levels beyond the required high operating
level tests at 47 and 17 [deg]F in their representations of IVHE. 88 FR
56392, 56419 (August 17, 2023). AHRI 1340-2023 also includes no such
provisions allowing interpolation between tests conducted at different
compressor operating levels. Therefore, DOE maintains its tentative
conclusion from the August 2023 TP NOPR and is adopting the approach
for determining IVHE from AHRI 1340-2023 unchanged.
8. Heating Test Provisions Not Included in the AHRI 1340-202X Draft
a. General
As discussed in the August 2023 TP NOPR (88 FR 56392, 56418-56419
(August 17, 2023)) and section III.E.7.g of this final rule, the AHRI
1340-202X Draft includes conditions for heating tests and calculations
for the IVHE, IVHEC, and COP2 metrics that DOE proposed to
adopt in the August 2023 TP NOPR. AHRI 1340-2023 includes several
updates to the heating test provisions as compared to the AHRI 1340-
202X Draft. The following sections describe these updates and what DOE
is adopting in this final rule.
b. Definitions of Heating Operating Levels
Table 26 to AHRI 1340-202X Draft and section 6.3.5 of AHRI 1340-
202X Draft specify the heating operating levels to use and the
requirements for each, but do not make clear the parameters included in
defining an operating level. Section 3.2.31 of AHRI 1340-2023 includes
definitions for all heating operating levels, as well as a general
definition of ``operating level.'' Section 3.2.31.6 defines ``operating
level'' as being determined by the number of compressors operating, the
modulation level of each operating compressor, and the indoor fan
speed. The definition indicates that the modulation level of a single
compressor is determined by the speed, duty cycle, vapor injection
setting, and state of any other operating parameters that affect the
continuous capacity of the compressor at a single set of operating
conditions.
DOE is adopting these AHRI 1340-2023 operating level definitions in
the DOE test procedure for CUACs and CUHPs, because DOE has concluded
that they provide appropriate clarity on how to determine the operating
levels to be used for heating tests and are substantively consistent
with the AHRI 1340-202X Draft, which DOE proposed to adopt in the
August 2023 TP NOPR. The one exception is the definition for the
``boost2 heating operating level,'' which is discussed in section
III.E.8.c of this final rule.
c. Boost2 Heating Operating Level and COP25
The AHRI 1340-202X Draft includes low, medium, high, and boost
heating operating levels, with boost being the operating level with the
highest heating capacity. The boost operating level uses the maximum
compressor operating capacity that is allowed by the controls at 17
[deg]F, and the airflow that is allowed by the controls at 17 [deg]F
when operating at the chosen compressor operating capacity. AHRI 1340-
2023 includes all the same heating operating levels as the AHRI 1340-
202X Draft, plus a boost2 heating operating level. AHRI 1340-2023
defines the ``boost2 operating level'' as an operating level allowed by
the controls at 5 [deg]F outdoor dry-bulb temperature with a capacity
at 5 [deg]F outdoor dry-bulb temperature that is greater than the
capacity of the boost heating operating level at 5 [deg]F outdoor dry-
bulb temperature and less than or equal to the maximum capacity allowed
by the controls at 5 [deg]F outdoor dry-bulb temperature.
[[Page 44012]]
For units with a boost operating level, AHRI 1340-2023 specifies
representations of COP25 be based on the capacity and power
determined at the boost or boost2 heating operating level denoted as
the H5B or H5B2 tests in Table 23 to AHRI 1340-2023. However, AHRI
1340-2023 does not allow the H5B2 test to be used in the calculation of
IVHE or IVHEC. As discussed in section III.E.7.g of this
document, AHRI 1340-2023 does not include any provisions allowing for
determination of capacity for a bin by interpolating between tests
conducted at different compressor operating levels. Therefore,
inclusion of results from the boost2 operating level would require at
least two tests conducted at this operating level. Because there is no
other test specified at a different outdoor dry-bulb temperature
condition at this same boost2 operating level, AHRI 1340-2023 only
allows the H5B2 test to be used to determine the capacity at 5 [deg]F
outdoor dry-bulb temperature or COP2 at 5 [deg]F.
DOE has determined that including a boost2 heating operating level
allows for manufacturers to make performance representations that
adequately reflect boosted heating performance at lower temperatures.
DOE notes that Recommendation #9 of the ACUAC and ACUHP Working Group
TP Term Sheet includes the following: ``Manufacturers can make
representations of COP and capacity at any of the following
temperatures: 5 [deg]F, 17 [deg]F, and 47 [deg]F, in accordance with
the DOE test procedure, in addition to the IVHE metric that will be
required for standards.'' (See EERE-2022-BT-STD-0015-0065 at p. 6) As
mentioned in section III.E.4 of this final rule, DOE acknowledges that
in the future manufacturers will likely develop CUHPs that are designed
for operation in colder climates. This may include designing CUHPs that
are capable of providing boosted heating capacity at low temperatures.
DOE has determined that the inclusion of the boost2 heating operating
level and the H5B2 test in AHRI 1340-2023 is consistent with the intent
of Recommendation #9 of the Term Sheet. This will allow for
manufacturers designing systems with boosted heating capacity at 5
[deg]F that differs from the operating levels at higher outdoor
temperatures to make representations of capacity and performance at 5
[deg]F, and correspondingly provide commercial consumers interested in
low-temperature heating performance an additional standardized metric
to compare such performance across models. Further, DOE has concluded
that the inclusion of the boost2 heating operating level and the H5B2
test in AHRI 1340-2023 is generally consistent with the AHRI 1340-202X
Draft, in that it maintains the proposed allowance for optional
representations at 5 [deg]F, but adds additional options for
manufacturers to determine this optional representation at the
compressor speed most representative for a model. As discussed, testing
at the boost2 heating operating level is optional and would not be
required for determinations of IVHE. DOE is adopting the H5B2 test in
its amended test procedure at appendix A1, but with two additional
clarifying provisions not included in AHRI 1340-2023.
First, section 6.3.14.2 of AHRI 1340-2023 specifies that for
determining the COP25 of units with a boost operating level,
one must use the capacity and power determined for the H5B or H5B2
test, instead of the H5H test. These provisions indicate that optional
COP25 representations for such units are based on a higher
heating operating level but do not specify whether the H5B or H5B2 test
is to be used for a unit that has both a boost heating operating level
and a boost2 heating operating level. DOE has determined that
additional specificity is warranted as to which test is used to
determine optional COP25 representations--specifically, DOE
has concluded that it should be clarified to use the highest applicable
heating operating level to determine COP25. Therefore, DOE
is adding the following clarification to section 5.3 of appendix A1:
For units without a boost heating operating level and without a boost 2
heating operating level, use capacity and power determined for the H5H
test. For units with a boost heating operating level and without a
boost 2 heating operating level, use capacity and power determined for
the H5B test. For units with a boost 2 heating operating level, use
capacity and power determined for the H5B2 test.
Second, section 3.2.31.1 of AHRI 1340-2023 defines the ``boost
heating operating level'' as the operating level that has the maximum
capacity allowed by the controls at 17 [deg]F outdoor dry-bulb
temperature, with a capacity at 17.0 [deg]F outdoor dry-bulb
temperature that is greater than the capacity of the high heating
operating level \22\ at 17 [deg]F. This means that there is no boost
heating operating level if the high heating operating level is the
heating operating level with the maximum capacity at 17 [deg]F. Section
3.2.31.2 of AHRI 1340-2023 defines the ``boost2 heating operating
level'' as an operating level allowed by the controls at 5 [deg]F
outdoor dry bulb-temperature with a capacity at 5 [deg]F outdoor dry
bulb-temperature that is greater than the capacity of the boost heating
operating level at 5 [deg]F and less than or equal to the maximum
capacity allowed by the controls at 5 [deg]F outdoor dry bulb-
temperature.
---------------------------------------------------------------------------
\22\ Section 3.2.31.3 of AHRI 1340-2023 defines ``high heating
operating level'' as the operating level with the maximum capacity
that is allowed by the controls at 47.0 [deg]F outdoor dry-bulb
temperature.
---------------------------------------------------------------------------
Because the definition of the ``boost2 heating operating level''
relies on the capacity of the boost operating level, the definition
implies that a model must have an operating level that meets the
definition for the boost heating operating level in order for it to
also have a boost2 heating operating level. This implication means that
AHRI 1340-2023 would not allow the H5B2 test to be conducted for a
model which has no boost heating operating level at 17 [deg]F, even if
that model has an operating level with a capacity at 5 [deg]F that is
greater than the capacity of the high heating operating level at 5
[deg]F. DOE has determined that such a scenario is possible and should
be accounted for in the definition for the ``boost2 heating operating
level'' and the requirements for the H5B2 test.
As such, DOE is not adopting the definition for the ``boost2
heating operating level'' in section 3.2.31.2 of AHRI 1340-2023.
Instead, DOE is adopting the following definition for the ``boost2
heating operating level'' in section 5.1 of appendix A1, which
addresses the aforementioned scenario of a model with a boosted
operating level at 17 [deg]F but not 5 [deg]F: ``An operating level
allowed by the controls at 5.0 [deg]F outdoor dry-bulb temperature with
a capacity at 5.0 [deg]F outdoor dry-bulb temperature that is less than
or equal to the maximum capacity allowed by the controls at 5.0 [deg]F
outdoor dry-bulb temperature, and greater than the capacity of: (a) the
Boost Heating Operating Level at 5.0 [deg]F outdoor dry-bulb
temperature, if there is an operating level that meets the definition
for Boost Heating Operating Level specified in section 3.2.31.1 of AHRI
1340-2023; or (b) the High Heating Operating Level at 5.0 [deg]F
outdoor dry-bulb temperature, if there is not an operating level that
meets the definition for Boost Heating Operating Level'' specified in
section 3.2.31.1 of AHRI 1340-2023.
Correspondingly, DOE is also specifying in section 5.2 of appendix
A1 updated requirements for the H5B2 test of AHRI 1340-2023 that are to
be used in case a model has no heating operating level that meets the
definition of ``boost
[[Page 44013]]
heating operating level'' in section 3.2.31.1 of AHRI 1340-2023.
Section 6.3.6 of AHRI 1340-2023 specifies to run the H5B2 test in Table
23 to AHRI 1340-2023 with an operating level allowed by the controls at
5.0 [deg]F outdoor dry-bulb temperature that has a capacity at 5.0
[deg]F outdoor dry-bulb temperature that is greater than the capacity
of the Boost Heating Operating Level at 5.0 [deg]F. In section 5.2 of
appendix A1, DOE is instead adopting a revised version of that
provision that replaces the comparison to capacity of the Boost Heating
Operating Level at 5.0 [deg]F with a comparison to capacity of the High
Heating Operating Level at 5.0 [deg]F.
As noted previously, DOE has concluded that the inclusion of the
boost2 heating operating level and the H5B2 test in AHRI 1340-2023 is
generally consistent with the AHRI 1340-202X Draft. Similarly, DOE has
concluded that the provisions discussed in this section (i.e., to allow
use of the boost2 heating operating level for determining optional
representations at 5 [deg]F for a model which has no boost heating
operating level at 17 [deg]F, and to clarify which test should be used
for optional COP25 representations depending on which
heating operating levels apply at 5 [deg]F) maintain the proposed
allowance for optional representations at 5 [deg]F, but add options and
clarity for manufacturers to consistently determine this optional
representation at the compressor speed most representative for a model.
DOE understands that the AHRI Commercial Unitary STC also plans to
address the aforementioned clarifications regarding the instructions
for which test to use for optional representation of COP25
and the definition of ``boost2 heating operating level'' that were
published in AHRI 1340-2023. DOE expects that AHRI will consider
including such clarifications in a future version of AHRI 1340,
consistent with the clarifications adopted in this final rule.
d. Extrapolation of Boost Heating Operating Level to 21 [deg]F
As discussed in section III.E.7.g of this final rule, AHRI 1340-
202X Draft requires interpolation of capacity and power between tests
of the same operating level at different outdoor air temperatures when
calculating values for the temperature bins used in IVHE and
IVHEC. Extrapolation of capacity and power are not allowed
in AHRI 1340-202X Draft.
Sections 6.3.8 and 6.3.9 of AHRI 1340-2023 allow for capacity and
power from boost heating operating level tests conducted at 5 [deg]F
and 17 [deg]F to be used to extrapolate boost heating operating level
performance up to 21 [deg]F. This allows manufacturers to take
advantage of the boost heating operating level for calculations of the
IVHE and IVHEC bins with outdoor air dry-bulb temperatures
between 17 [deg]F and 22 [deg]F.\23\
---------------------------------------------------------------------------
\23\ Table 22 of AHRI 1340-2023 specifies: (1) for the IVHE
metric, bin temperatures of 21 [deg]F and 18.1 [deg]F for bin
numbers 8 and 9; and (2) for the IVHEC metric, a bin
temperature of 20.0 [deg]F for bin number 5.
---------------------------------------------------------------------------
DOE has determined that these provisions are appropriate and will
allow for more representative accounting of performance for bin
temperatures between 17 [deg]F and 22 [deg]F, which are conditions at
which models would likely operate at boost heating operating level, as
necessary, to meet the building load, if the model operated as such for
tests at 17 [deg]F (i.e., it would be unlikely that a model would have
a boost operating level that engages at 17 [deg]F but not at 22
[deg]F). Further, DOE has concluded that these provisions are generally
consistent with the AHRI 1340-202X Draft in that the provisions
maintain the same compressor operating levels for determining IVHE, but
the upper temperature limit to which boost heating performance can be
applied is being slightly extended (by 5 [deg]F, from 17 [deg]F to 22
[deg]F) to more representatively account for performance between 17
[deg]F to 22 [deg]F. Therefore, DOE is adopting the provisions allowing
extrapolation of boost heating operating level performance in sections
6.3.8 and 6.3.9 of AHRI 1340-2023.
e. Operating Levels Used for Optional COP217 Representations
As previously mentioned in section III.E.8.c of this document, AHRI
1340-2023 specifies that for units with a boost operating level,
representations of COP25 is to be based on the capacity and
power determined at the boost or boost 2 heating operating level
denoted as the H5B or H5B2 test, instead of the H5H test. However,
while AHRI 1340-2023 includes a boost operating level test at 17 [deg]F
(the H17B test), section 6.3.14.2 of AHRI 1340-2023 requires that
COP217 be determined using the capacity and power determined
for the H17H test and does not allow for the COP217 to be
determined using the capacity and power determined for the H17B test if
conducted. Similar to its conclusions regarding the use of the H5B or
H5B2 test for determining COP25, DOE has determined it would
be appropriate to require the H17B test to be used for representations
of COP217 if conducted because representations of efficiency
at the maximum capacity for a given test condition are common and
useful for consumers and utilities. Therefore, DOE is also specifying
in this final rule that the H17B test, if conducted, be used for
determining COP217, in order to allow manufacturers to make
optional representations of capacity and performance at that operating
level for models that are capable of boost operation. DOE understands
that the AHRI Commercial Unitary STC also plans to specify that the
H17B test is to be used for determining COP217 if this test
is conducted. DOE expects that AHRI will consider including prescribing
the use of the H17B test in appropriate cases for representations of
COP217, consistent with this final rule, in a future version
of AHRI 1340.
9. Test Procedure Revisions Recommended for a Future Rulemaking
NYSERDA generally supported the proposed IVEC and IVHE metrics but
commented that the heating test provisions proposed do not adequately
account for fan energy consumed during auxiliary heating mode.
(NYSERDA, No. 13 at pp. 2-3) NYSERDA recommended DOE consider the
inclusion of an additional energy consumption term in the denominator
of the IVHE calculation to account for supply fan energy use for
commercial warm air furnaces, which NYSERDA stated would support
recommendation #11 of the ACUAC and ACUHP Working Group TP Term Sheet.
NYSERDA recommended addressing the fan energy consumption issue at the
next appropriate juncture. (Id.)
NEEA recommended DOE consider the following items the next time the
CUAC/HP test procedure is reviewed: (1) impacts of outside air damper
leakage; (2) energy saving potential from energy recovery ventilators
(``ERV''); (3) benefits of variable-capacity or variable-speed
compressors, and (4) a controls verification procedure (``CVP'').
(NEEA, No. 16 at p. 4)
At this time DOE has concluded that it does not have sufficient
information or data to justify adopting deviations from the IVEC and
IVHE metrics negotiated by the Working Group and included in the
industry consensus test procedure AHRI 1340-2023. Therefore, DOE is
adopting the IVEC and IVHE metrics as specified in AHRI 1340-2023.
Regarding NYSERDA's comments on fan energy consumption in the IVHE
metric, DOE notes that IVHE is the heating metric for CUHPs and assumes
electric resistance supplementary heat for all models. Dual fuel CUHPs
(i.e., CUHPs with gas furnace supplementary heat) will still have IVHE
ratings that reflect electric resistance supplementary heat. The IVHE
metric accounts for
[[Page 44014]]
supply fan energy during all hours with a heating load, regardless of
whether the IVHE calculations assume the heating load is met by
mechanical heating only, electric resistance heating only, or both, as
described in section III.D.2 of this document. Therefore, DOE has
concluded that no fan energy use for CUHPs is unaccounted for in the
IVHE metric. DOE recognizes NEEA's suggested topics for consideration
in a future test procedure rulemaking, but consistent with NEEA's
comment, DOE is not addressing these topics in this final rule.
F. Configuration of Unit Under Test
1. Summary
CUACs and CUHPs are sold with a wide variety of components,
including many that can optionally be installed on or within the unit
both at the factory and in the field. The following sections address
the required configuration of units under test. In all cases, these
components are distributed in commerce with the CUAC and CUHP but can
be packaged or shipped in different ways from the point of manufacture
for ease of transportation. Each optional component may or may not
affect a model's measured efficiency when tested to the DOE test
procedure adopted in this final rule. For certain components not
directly addressed in the DOE test procedure, the August 2023 TP NOPR
proposed more specific instructions on how each component should be
handled for the purposes of making representations in 10 CFR part 429.
88 FR 56392, 56430-56433 (August 17, 2023). Specifically, the proposed
instructions were intended to provide manufacturers with clarity on how
components should be treated and how to group individual models with
and without optional components for the purposes of representations to
reduce burden. Id. DOE proposed these provisions in 10 CFR part 429 to
allow for testing of certain individual models that can be used as a
proxy to represent the performance of equipment with multiple
combinations of components. Id.
In the August 2023 TP NOPR, DOE proposed to handle CUAC and CUHP
components in two distinct ways to help manufacturers better understand
their options for developing representations for their differing
product offerings. Id. First, DOE proposed that the treatment of
certain components be specified by the test procedure, such that their
impact on measured efficiency is limited. Id. For example, a fresh air
damper must be set in the closed position and sealed during testing,
resulting in a measured efficiency that would be similar or identical
to the measured efficiency for a unit without a fresh air damper.
Second, DOE proposed provisions expressly allowing certain models to be
grouped together for the purposes of making representations and
allowing the performance of a model without certain optional components
to be used as a proxy for models with any combinations of the specified
components, even if such components would impact the measured
efficiency of a model. Id. A steam/hydronic coil is an example of such
a component. The efficiency representation for a model with a steam/
hydronic coil is based on the measured performance of the CUAC and CUHP
as tested without the component installed because the steam/hydronic
coil is not easily removed from the CUAC and CUHP for testing.\24\ Id.
---------------------------------------------------------------------------
\24\ Note that in certain cases, as explained further in section
III.F.3.b of this document, the representation may have to be based
on an individual model with a steam/hydronic coil.
---------------------------------------------------------------------------
In this final rule, DOE is adopting provisions regarding
configuration of unit under test largely similar to those proposed, but
with several differences from the proposed provisions, as discussed in
the following sections. Specifically, the following sections provide a
background for the proposed provisions, describe the proposed
provisions, describe relevant updates in AHRI 1340-2023 that were not
included in the AHRI 1340-202X Draft, summarize and respond to the
comments that DOE received in response to the August 2023 TP NOPR, and
discuss the provisions that DOE is adopting in this final rule.
2. Background
In 2013, ASRAC formed the Commercial HVAC Working Group to engage
in a negotiated rulemaking effort regarding the certification of
certain commercial heating, ventilating, and air conditioning
equipment, including CUACs and CUHPs. (See 78 FR 15653 (March 12,
2013)) This Commercial HVAC Working Group submitted a term sheet
(Commercial HVAC Term Sheet) providing the Commercial HVAC Working
Group's recommendations. (See EERE-2013-BT-NOC-0023-0052 \25\) The
Commercial HVAC Working Group recommended that DOE issue guidance under
current regulations on how to test certain equipment features when
included in a basic model, until such time as the testing of such
features can be addressed through a test procedure rulemaking. The
Commercial HVAC Term Sheet listed the subject features under the
heading ``Equipment Features Requiring Test Procedure Action.'' (Id at
pp. 3-9) The Commercial HVAC Working Group also recommended that DOE
issue an enforcement policy stating that DOE would exclude certain
equipment with specified features from DOE testing, but only when the
manufacturer offers for sale at all times a model that is identical in
all other features; otherwise, the model with that feature would be
eligible for DOE testing. These features were listed under the heading
``Equipment Features Subject to Enforcement Policy.'' (Id. at pp. 9-15)
---------------------------------------------------------------------------
\25\ Available at www.regulations.gov/document/EERE-2013-BT-NOC-0023-0052.
---------------------------------------------------------------------------
On January 30, 2015, DOE issued a Commercial HVAC Enforcement
Policy addressing the treatment of specific features during DOE testing
of commercial HVAC equipment. (See www.energy.gov/gc/downloads/commercial-equipment-testing-enforcement-policies) The Commercial HVAC
Enforcement Policy stated that--for the purposes of assessment testing
pursuant to 10 CFR 429.104, verification testing pursuant to 10 CFR
429.70(c)(5), and enforcement testing pursuant to 10 CFR 429.110--DOE
would not test a unit with one of the optional features listed for a
specified equipment type if a manufacturer distributes in commerce an
otherwise identical unit that does not include that optional feature.
(Commercial HVAC Enforcement Policy at p. 1) The objective of the
Commercial HVAC Enforcement Policy is to ensure that each basic model
has a commercially-available version eligible for DOE testing. That is,
each basic model includes a model either without the optional
feature(s) listed in the policy or that is eligible for testing with
the feature(s). Id. The features in the Commercial HVAC Enforcement
Policy for CUACs and CUHPs (Id. at pp. 1-3 and 5-6) align with the
Commercial HVAC Term Sheet's list designated ``Equipment Features
Subject to Enforcement Policy.'' (EERE-2013-BT-NOC-0023-0052, pp. 9-15)
By way of comparison, AHRI 340/360-2022 and AHRI 1340-202X Draft
include appendix D, ``Unit Configuration for Standard Efficiency
Determination--Normative.'' Section D3 to appendix D of AHRI 340/360-
2022 and AHRI 1340-202X Draft includes a list of features that are
optional for testing, and it further specifies the following general
provisions regarding testing of units with optional features:
If an otherwise identical model (within the basic model)
without the feature is not distributed in commerce, conduct tests with
the feature according to the individual provisions specified in
[[Page 44015]]
section D3 to appendix D of AHRI 340/360-2022 and AHRI 1340-202X Draft.
For each optional feature, section D3 to appendix D of
AHRI 340/360-2022 and AHRI 1340-202X Draft includes explicit
instructions on how to conduct testing for equipment with the optional
feature present.
The optional features provisions in AHRI 340/360-2022 and AHRI
1340-202X Draft are generally consistent with DOE's Commercial HVAC
Enforcement Policy, but the optional features in section D3 to appendix
D of AHRI 340/360-2022 and AHRI 1340-202X Draft do not entirely align
with the list of features included for CUACs and CUHPs in the
Commercial HVAC Enforcement Policy.
DOE notes that the list of features and provisions in section D3 to
appendix D of AHRI 340/360-2022 and AHRI 1340-202X Draft conflate
components that can be addressed by testing provisions with components
that, if present on a unit under test, could have a substantive impact
on test results and that cannot be disabled or otherwise mitigated.
This differentiation was central to the Commercial HVAC Term Sheet,
which as noted previously, included separate lists for ``Equipment
Features Requiring Test Procedure Action'' and ``Equipment Features
Subject to Enforcement Policy,'' and remains central to providing
clarity in DOE's regulations. Therefore, in the August 2023 TP NOPR,
DOE tentatively determined that provisions more explicit than those
included in section D3 of appendix D of AHRI 340/360-2022 and AHRI
1340-202X Draft are warranted to clarify treatment of models that
include more than one optional component. 88 FR 56392, 56430 (August
17, 2023).
In order to provide clarity between test procedure provisions
(i.e., how to test a specific unit) and certification and enforcement
provisions (e.g., which model to test), DOE proposed in the August 2023
TP NOPR to exclude appendix D of AHRI 340/360-2022 or AHRI 1340-202X
Draft from adoption and instead proposed related provisions in 10 CFR
429.43 and 429.134 and 10 CFR part 431, subpart F, appendices A and A1.
Id.
3. Proposed Approach for Exclusion of Certain Components
DOE's proposals in August 2023 TP NOPR for addressing treatment of
certain components are discussed in the following sub-sections.
a. Components Addressed Through Test Provisions of 10 CFR Part 431,
Subpart F, Appendices A and A1
In the August 2023 TP NOPR, DOE proposed in 10 CFR part 431,
subpart F, appendices A and A1, test provisions for specific
components, including all of the components listed in section D3 to
appendix D of AHRI 340/360-2022 and AHRI 1340-202X Draft, for which
there is a test procedure action that limits the impacts on measured
efficiency (i.e., test procedure provisions specific to the component
that are not addressed by general provisions in AHRI 340/360-2022 or
AHRI 1340-202X Draft that negate the component's impact on
performance). 88 FR 56392, 56430 (August 17, 2023). These provisions
would specify how to test a unit with such a component (e.g., for a
unit with hail guards, remove hail guards for testing). These proposed
test provisions were consistent with the provision in section D3 to
appendix D of AHRI 340/360-2022 and AHRI 1340-202X Draft but include
revisions for further clarity and specificity (e.g., adding clarifying
provisions for how to test units with modular economizers as opposed to
units shipped with economizers installed). Id. Specifically, DOE
proposed to require in appendices A and A1 that steps be taken during
unit set-up and testing to limit the impacts on the measurement of
these components:
Air Economizers
Barometric Relief Dampers
Desiccant Dehumidification Components
Evaporative Pre-cooling of Air-cooled Condenser Intake Air
Fire/Smoke/Isolation Dampers
Fresh Air Dampers
Hail Guards
High-Effectiveness Indoor Air Filtration
Power Correction Capacitors
Process Heat Recovery/Reclaim Coils/Thermal Storage
Refrigerant Reheat Coils
Steam/Hydronic Heat Coils
UV Lights
Ventilation Energy Recovery Systems (VERS)
The components were listed and described in the proposed table 1 to
appendix A and table 1 to appendix A1. Test provisions for the
components were provided in the tables. Id.
b. Components Addressed Through Representation Provisions of 10 CFR
429.43
Overall Approach
Consistent with the Commercial HVAC Term Sheet and the Commercial
HVAC Enforcement Policy, in the August 2023 TP NOPR, DOE proposed
provisions that explicitly allow representations for individual models
with certain components to be based on testing for individual models
without those components. 88 FR 56392, 56430-56433 (August 17, 2023).
DOE proposed a table (table 6) at 10 CFR 429.43(a)(3)(v)(A) listing the
components for which these provisions would apply. Id. 88 FR 56430-
56431. DOE proposed the following components be listed in table 6 to 10
CFR 429.43(a)(3)(v)(A):
Air Economizers
Desiccant Dehumidification Components
Evaporative Pre-cooling of Air-cooled Condenser Intake Air
Fire/Smoke/Isolation Dampers
Indirect/Direct Evaporative Cooling of Ventilation Air
Non-Standard Ducted Condenser Fans
Non-Standard Indoor Fan Motors
Powered Exhaust/Powered Return Air Fans
Process Heat Recovery/Reclaim Coils/Thermal Storage
Refrigerant Reheat Coils
Sound Traps/Sound Attenuators
Steam/Hydronic Heat Coils
Ventilation Energy Recovery Systems (VERS)
In the August 2023 TP NOPR, DOE proposed to specify that the basic
model representation must be based on the least-efficient individual
model that comprises a basic model, and clarified how this long-
standing basic model provision interacts with the proposed component
treatment in 10 CFR 429.43. Id. 88 FR 56431-56432. DOE tentatively
concluded that regulated entities may benefit from clarity in the
regulatory text as to how the least-efficient individual model within a
basic model provision works in concert with the component treatment for
CUACs and CUHPs. Id. The amendments proposed in the August 2023 TP NOPR
explicitly state that excluding the specified components from
consideration in determining basic model efficiency in certain
scenarios is an exception to basing representations on the least-
efficient individual model within a basic model. Id. In other words,
the components listed in 10 CFR 429.43 are not being considered as part
of the representation under DOE's regulatory framework if certain
conditions are met as discussed in the following paragraphs, and, thus,
their impact on efficiency is not reflected in the representation. In
this case, the basic model's representation is generally determined by
applying the testing and
[[Page 44016]]
sampling provisions to the least-efficient individual model in the
basic model that does not have a component listed in 10 CFR 429.43.
DOE proposed clarifying instructions for instances when individual
models within a basic model may have more than one of the specified
components and there may be no individual model without any of the
specified components. Id. DOE proposed the concept of an otherwise
comparable model group (``OCMG''). Id. An OCMG is a group of individual
models within the basic model that do not differ in components that
affect energy consumption as measured according to the applicable test
procedure other than the specific components listed in table 6 to 10
CFR 429.43(a)(3)(v)(A) but may include individual models with any
combination of such specified components. Therefore, a basic model can
be composed of multiple OCMGs, each representing a unique combination
of components that affect energy consumption as measured according to
the applicable test procedure, other than the specified excluded
components listed in table 6 to 10 CFR 429.43(a)(3)(v)(A). For example,
a manufacturer might include two tiers of control systems within the
same basic model, in which one of the control systems has sophisticated
diagnostics capabilities that require a more powerful control board
with a higher wattage input. CUAC and CUHP individual models with the
``standard'' control system would be part of OCMG A, while individual
models with the ``premium'' control system would be part of a different
OCMG B, because the control system is not one of the specified exempt
components listed in table 6 to 10 CFR 429.43(a)(3)(v)(A). However,
both OCMGs may include different combinations of specified exempt
components. Also, both OCMGs may include any combination of
characteristics that do not affect the efficiency measurement, such as
paint color.
An OCMG identifies which individual models are to be used to
determine a represented value. Id. Specifically, when identifying the
individual model within an OCMG for the purpose of determining a
representation for the basic model, only the individual model(s) with
the least number (which could be zero) of the specific components
listed in table 6 to 10 CFR 429.43(a)(3)(v)(A) is considered. This
clarifies which individual models are exempted from consideration for
determination of represented values in the case of an OCMG with
multiple specified components and no individual models with zero
specific components listed in table 6 to 10 CFR 429.43(a)(3)(v)(A)
(i.e., models with a number of specific components listed in table 6
greater than the least number in the OCMG are exempted). In the case
that the OCMG includes an individual model with no specific components
listed in table 1 to 10 CFR 429.43(a)(3)(i)(A), then all individual
models in the OCMG with specified components would be exempted from
consideration. The least-efficient individual model across the OCMGs
within a basic model would be used to determine the representation of
the basic model. In the case where there are multiple individual models
within a single OCMG with the same non-zero least number of specified
components, the least efficient of these would be considered.
DOE relies on the term ``comparable'' as opposed to ``identical''
to indicate that, for the purpose of representations, the components
that impact energy consumption as measured by the applicable test
procedure are the relevant components to consider. Id. In other words,
differences that do not impact energy consumption, such as unit color
and presence of utility outlets, would not warrant separate OCMGs.
The use of the OCMG concept results in the represented values of
performance that are representative of the individual model(s) with the
lowest efficiency found within the basic model, excluding certain
individual models with the specific components listed in table 6 to 10
CFR 429.43(a)(3)(v)(A). Id. Specifically with regard to basic models of
CUACs and CUHPs distributed in commerce with multiple different heating
capacities of furnaces, the individual model with the lowest efficiency
found within the basic model (with the aforementioned exception) would
likely include the furnace with the highest offered heating capacity.
Additionally, selection of the individual model with the lowest
efficiency within the basic model would be required to consider all
options for factory-installed components and manufacturer-supplied
field-installed components (e.g., electric resistance supplementary
heat), excluding the specific components listed in table 6 to 10 CFR
429.43(a)(3)(v)(A). If manufacturers want to represent more-efficient
models within the same group, they would be able to establish those
units as new basic models and test and report the results accordingly.
Further, the approach, as proposed, is structured to more explicitly
address individual models with more than one of the specific components
listed in table 6 to 10 CFR 429.43(a)(3)(v)(A), as well as instances in
which there is no comparable model without any of the specified
components. DOE developed a document of examples to illustrate the
approach proposed in the August 2023 TP NOPR for determining
represented values for CUACs and CUHPs with specific components, and in
particular the OCMG concept (see EERE-2023-BT-TP-0014-0001).
DOE's proposed provisions in 10 CFR 429.43(a)(3)(v)(A) include each
of the components specified in section D3 of AHRI 340/360-2022 for
which the test provisions for a unit with these components may result
in differences in ratings compared to testing a unit without these
components. 88 FR 56392, 56431-56432 (August 17, 2023). DOE's proposed
treatment for non-standard indoor fan motors and coated coils is
discussed in the following sub-sections.
High-Static Non-Standard Indoor Fan Motors
The Commercial HVAC Enforcement Policy includes high-static indoor
blowers or oversized motors as an optional feature for CUACs and CUHPs,
among other equipment. The Commercial HVAC Enforcement Policy states
that when selecting a unit of a basic model for DOE[hyphen]initiated
testing, if the basic model includes a variety of high-static indoor
blowers or oversized motor options,\26\ DOE will test a unit that has a
standard indoor fan assembly (as described in the supplemental test
instructions (``STI'') that is part of the manufacturer's
certification, including information about the standard motor and
associated drive that was used in determining the certified rating).
This policy only applies where: (a) the manufacturer distributes in
commerce a model within the basic model with the standard indoor fan
assembly (i.e., standard motor and drive), and (b) all models in the
basic model have a motor with the same or better relative efficiency
performance as the standard motor included in the test unit, as
described in a separate guidance document discussed subsequently. If
the manufacturer does not offer models with the standard motor
identified in the STI or offers models with high-static motors that do
not comply with the
[[Page 44017]]
comparable efficiency guidance, DOE will test any indoor fan assembly
offered for sale by the manufacturer.
---------------------------------------------------------------------------
\26\ The Commercial HVAC Enforcement Policy defines ``high
static indoors blower or oversized motor'' as an indoor fan
assembly, including a motor, that drives the fan and can deliver
higher external static pressure than the standard indoor fan
assembly sold with the equipment. (See www.energy.gov/sites/default/files/2019/04/f62/Enforcement_Policy-Commercial_HVAC.pdf. at p.6)
---------------------------------------------------------------------------
DOE subsequently issued a draft guidance document (Draft Commercial
HVAC Guidance Document) on June 29, 2015 to request comment on a method
for comparing the efficiencies of a standard motor and a high-static
indoor blower/oversized motor.\27\ As presented in the Draft Commercial
HVAC Guidance Document, the relative efficiency of an indoor fan motor
would be determined by comparing the percentage losses of the standard
indoor fan motor to the percentage losses of the non-standard
(oversized) indoor fan motor. The percentage losses would be determined
by comparing each motor's wattage losses to the wattage losses of a
corresponding reference motor. Additionally, the draft method contains
a table that includes a number of situations with different
combinations of characteristics of the standard motor and oversized
motor (e.g., whether each motor is subject to Federal standards for
motors; whether each motor can be tested to the Federal test procedure
for motors; whether each motor horsepower is less than 1 and specifies
for each combination whether the non-standard fan enforcement policy
would apply (i.e., whether DOE would not test a model with an oversized
motor, as long as the relative efficiency of the oversized motor is at
least as good as performance of the standard motor)). DOE has not
issued a final guidance document and is instead addressing the issue
for CUACs and CUHPs in this test procedure rulemaking.
---------------------------------------------------------------------------
\27\ Available at www1.eere.energy.gov/buildings/appliance_standards/pdfs/draft-commercial-hvac-motor-faq-2015-06-29.pdf.
---------------------------------------------------------------------------
The current Federal test procedure does not address this issue.
Section D4.1 of appendix D of AHRI 340/360-2022 and AHRI 1340-202X
Draft provide an approach for including an individual model with a non-
standard indoor fan motor as part of the same basic model as an
individual model with a standard indoor fan motor. Under the approach
in section D4.1 of appendix D of AHRI 340/360-2022 and AHRI 1340-202X
Draft, the non-standard indoor fan motor efficiency must exceed the
minimum value calculated using equation D1 in appendix D of AHRI 340/
360-2022 and AHRI 1340-202X Draft. This minimum non-standard motor
efficiency calculation is dependent on the efficiency of the standard
fan motor and the reference efficiencies (determined per Table D1 of
appendix D of AHRI 340/360-2022 and AHRI 1340-202X Draft) of the
standard and non-standard fan motors.
Section D4.2 of appendix D of AHRI 340/360-2022 and AHRI 1340-202X
Draft contain a method for how to compare performance for integrated
fans and motors (IFMs). Because the fan motor in an IFM is not
separately rated from the fan, this method compares the performance of
the entire fan-motor assemblies for the standard and non-standard IFMs,
rather than just the fan motors. This approach enables comparing
relative performance of standard and non-standard IFMs, for which motor
efficiencies could otherwise not be compared using the method specified
in section D4.1 of appendix D of AHRI 340/360-2022 or AHRI 1340-202X
Draft. Specifically, this method determines the ratio of the input
power of the non-standard IFM to the input power of the standard IFM at
the same duty point as defined in section D4.2 of appendix D of AHRI
340/360-2022 and AHRI 1340-202X Draft (i.e., operating at the maximum
ESP for the standard IFM at the rated airflow). If the input power
ratio does not exceed the maximum ratio specified in Table D3 of
appendix D of AHRI 340/360-2022 and AHRI 1340-202X Draft, the
individual model with the non-standard IFM may be included within the
same basic model as the individual model with the standard IFM. Section
D4.2 of appendix D of AHRI 340/360-2022 and AHRI 1340-202X Draft allow
these calculations to be conducted using either test data or simulated
performance data.
The approaches in section D4 of appendix D of AHRI 340/360-2022 and
AHRI 1340-202X Draft for high-static non-standard indoor fan motors and
non-standard indoor IFMs generally align with the approaches of the
Commercial HVAC Term Sheet, the Commercial HVAC Enforcement Policy, and
the Draft Commercial HVAC Guidance Document, while providing greater
detail and accommodating a wider range of fan motor options. For the
reasons presented in the preceding paragraphs, DOE proposed in the
August 2023 TP NOPR to adopt in table 6 to 10 CFR 429.43(a)(3)(v)(A)
the provisions for comparing performance of standard and high-static
non-standard indoor fan motors/IFMs in section D4 of appendix D of AHRI
340/360-2022 and AHRI 1340-202X Draft \28\ for the determination of the
represented efficiency value for CUACs and CUHPs at 10 CFR
429.43(a)(3). 88 FR 56392, 56432 (August 17, 2023).
---------------------------------------------------------------------------
\28\ Per DOE's existing certification regulations, if a
manufacturer were to use the proposed approach to certify a basic
model, the manufacturer would be required to maintain documentation
of how the relative efficiencies of the standard and non-standard
fan motors or the input powers of the standard and non-standard IFMs
were determined, as well as the supporting calculations. See 10 CFR
429.71.
---------------------------------------------------------------------------
Coated Coils
In the August 2023 TP NOPR, DOE proposed to exclude coated coils
from the specific components list specified in 10 CFR 429.43 because
DOE tentatively concluded that the presence of coated coils does not
result in a significant impact to performance of CUACs and CUHPs, and,
therefore, models with coated coils should be rated based on
performance of models with coated coils present (rather than based on
performance of an individual model within an OCMG without coated
coils). 88 FR 56392, 56432-56433 (August 17, 2023).
c. Enforcement Provisions of 10 CFR 429.134
Consistent with the Commercial HVAC Term Sheet and the Commercial
HVAC Enforcement Policy, in the August 2023 TP NOPR, DOE proposed
provisions in 10 CFR 429.134(g)(2) regarding how DOE would assess
compliance for basic models of CUACs and CUHPs that include individual
models distributed in commerce if DOE cannot obtain for testing
individual models without certain components consistent with the model
that served as the basis of representation. 88 FR 56392, 56433 (August
17, 2023). Specifically, DOE proposed that if a basic model includes
individual models with components listed at table 6 to 10 CFR
429.43(a)(3)(v)(A) and DOE is not able to obtain an individual model
with the least number of those components within an OCMG (as defined in
the proposed 10 CFR 429.43(a)(3)(v)(A)(1) and discussed in section
III.F.3.b of this final rule), DOE may test any individual model within
the OCMG. Id.
d. Testing Specially Built Units That Are Not Distributed in Commerce
Unlike section D3 to appendix D of AHRI 340/360-2022 and AHRI 1340-
202X Draft, DOE's Commercial HVAC Enforcement Policy does not allow a
manufacturer to test a model that is specially built for testing
without a feature if models without that feature are not actually
distributed in commerce. Because testing such specially built models
would not provide ratings representative of equipment distributed in
commerce, DOE tentatively concluded in the August 2023 TP NOPR that
such
[[Page 44018]]
approach is not appropriate. 88 FR 56392, 56433 (August 17, 2023).
Therefore, consistent with the Commercial HVAC Enforcement Policy, DOE
did not propose to allow testing of specially built units in its
representation and enforcement provisions. Id.
4. Updates in AHRI 1340-2023
In the final version of AHRI 1340-2023, appendix D to AHRI 1340-
2023 was updated to align with the approach and list of features
proposed by DOE in the August 2023 TP NOPR, as discussed in section
III.F.3 of this final rule. In addition, Table 37 to appendix D to AHRI
1340-2023 includes instructions specifying that drain pan heaters be
disconnected during testing. DOE's consideration of this AHRI 1340-2023
provision for drain pan heaters is discussed in the following section.
5. Comments Received and Adopted Provisions
a. Overall Approach
DOE received several comments pertaining to DOE's proposed
approach. Carrier stated that DOE's proposal for specific components
was not fully clear to Carrier, but that if the intent is that the
lowest-efficiency model should be used for representations of
performance, Carrier agrees with that approach. (Carrier, No. 8 at p.
3) For rating models, Carrier also agreed that specially built models
not distributed in commerce should not be allowed for compliance
testing used to determine ratings. (Id.) Carrier commented that
breaking into separate groups of components and introducing an
additional concept of OCMG could create further confusion and undue
complexity. (Id.) Carrier stated that it would like to see these
provisions for specific components be laid out in a more
straightforward manner to provide manufacturers clarity when choosing
models for representations. (Id.) Rheem similarly commented that the
proposed OCMG concept lacks clarity and recommended DOE explore ways to
make the proposed regulatory text clearer with visual aids or examples.
(Rheem, No. 12 at p. 2) Rheem recommended the regulatory language to
remain the same as it is currently if no further explanation is
provided. (Id.)
Regarding Carrier and Rheem's concerns, DOE's intent is for the
lowest-efficiency model within a basic model to be used for
representations of performance, as is stated in the provisions adopted
at 10 CFR 429.43(a)(3)(vi)(A)(1) in this final rule.\29\ DOE
acknowledges that the ability to exclude certain specific components
specified in table 7 to 10 CFR 429.43(a)(3)(vi)(A) from consideration
when identifying the lowest-efficiency model means that there could be
confusion in determining the least-efficient model(s) that can be used
to determine representations for the basic model. This is the reason
that the OCMG concept is required. As discussed, the OCMG formalizes
the process by which a manufacturer can consider groups of individual
models within a basic model that are comparable, other than the
presence of certain specific components specified in table 7 to 10 CFR
429.43(a)(3)(vi)(A), and determine the individual model(s) that can be
used to determine representations for the basic model. This ensures
that the process is performed in the same way by all manufacturers and
also by DOE, thereby preventing the potential for confusion and
inaccurate representations. Regarding Carrier's and Rheem's requests
for more clarity and visual aids, DOE notes that, as discussed, the
Department has developed a document which includes visual aids and
examples of how the OCMG concept works in application (see EERE-2023-
BT-TP-0014-0001). This document presents several examples that make
clear the OCMG concept and how it is used to determine the individual
model(s) that can be used to determine representations for a basic
model. DOE encourages stakeholders to review this document for
additional clarification, and the Department will consider developing
other forms of visual aid and examples should stakeholders request it.
---------------------------------------------------------------------------
\29\ In the August 2023 TP NOPR, DOE proposed the provisions
regarding certain components addressed through representation
provisions of 10 CFR 429.43(a)(3)(v). In this final rule, those
provisions are instead being adopted at 10 CFR 429.43(a)(3)(vi).
Further, the provisions proposed in table 6 to 10 CFR
429.43(a)(3)(v)(A) are being adopted in table 7 to 10 CFR
429.43(a)(3)(vi)(A).
---------------------------------------------------------------------------
For the reasons discussed in the previous paragraphs and the August
2023 TP NOPR, DOE is adopting its proposed approach for determining the
configuration of a unit under test. DOE is also adopting two updates to
the approach proposed in the August 2023 TP NOPR, as explained in the
paragraphs that follow.
First, after consideration of comments received, DOE is changing
the required compliance date to be when certifying to standards
denominated in terms of IVHE and IVEC, should those standards be
established, rather than starting 360 days after publication of the
test procedure final rule in the Federal Register (as proposed). This
is consistent with the approach that DOE has taken for establishing
similar provisions for other categories of commercial air conditioning
equipment; i.e., for other categories such as CRACs (88 FR 21816,
21836-21837 (April 11, 2023)), variable refrigerant flow multi-split
systems (87 FR 63860, 63892 (Oct. 20, 2022)), and SPVUs (87 FR 75144,
75166 (Dec. 7, 2022)), DOE specified a compliance date for similar
``configuration of unit under test'' provisions to be the compliance
date of amended energy conservation standards in terms of the new
metric. Additionally, this compliance date change ensures that
manufacturers will have adequate time to learn and understand the
process. As a result, the provisions that DOE is adopting in 10 CFR
429.43 and 429.134 will apply when certifying to standards denominated
in terms of IVHE and IVEC or for assessment and enforcement testing of
models subject to energy conservation standards denominated in terms of
IVEC and IVHE, if such standards are adopted. Consistent with the
compliance date for provisions in 10 CFR 429.43 and 429.134, DOE is
also not adopting any test provisions for units with specific
components in appendix A, and is instead only adopting such test
provisions in appendix A1, which would be used when certifying
compliance with standards in terms of IVHE and IVEC, should those
standards be established.
Second, DOE is adopting in table 2 to appendix A1 the provision for
how to test units with drain pan heaters specified in Table 37 to
appendix D2 to AHRI 1340-2023 (i.e., disconnect drain pan heaters for
testing). Although not proposed in the August 2023 TP NOPR, DOE has
concluded that this guidance for how to test units with drain pan
heaters is appropriate and consistent with test provisions for other
components that DOE proposed in the August 2023 TP NOPR.
As discussed, DOE's adopted provisions regarding configuration of
unit under test in 10 CFR 429.43 and 429.134 apply to equipment subject
to standards in terms of IVHE and IVEC.
b. Coated Coils
DOE received several comments in response to the proposal to
exclude coated coils from the specific components list in 10 CFR
429.43. Carrier, Trane, AHRI, and Lennox opposed DOE's proposed
exclusion of coated coils from the specific components list. (Carrier,
No. 8 at p. 3; Trane, No. 14 at p. 4; AHRI, No. 15 at p. 6; Lennox, No.
9 at p. 2) AHRI asserted that DOE provided no data to support the
proposal and that the
[[Page 44019]]
proposal could more than double manufacturers' listed basic models.
(AHRI, No. 15 at p. 6)
Trane stated that there are a multitude of coil coatings available
in the marketplace and that many are customized per specific customer
requests. (Trane, No. 14 at p. 4) Trane further commented that many
coils undergo a special ``non-standard'' process to have coil coatings
applied, often requiring coils to be sent to a third party prior to
being installed in the unit during the manufacturing process, which
adds significant lead time to the equipment as well as variability in
types of coatings that are applied. (Id.) Trane argued that excluding
coated coils from the list of specific components would necessitate
extensive testing in order to develop adequate performance models for
all cases. (Id.) Trane additionally stated that this would also
multiply the number of listed models, as some coil coatings may have
significant performance impacts while some may not. (Id.) Trane stated
that units with coated coils only represent a very small fraction of
the market, and, therefore, requiring all equipment to include coil
coatings in the basic models is not representative of the vast majority
of applications in the marketplace. (Id.) Trane also argued that this
requirement would be unduly burdensome for manufacturers, given that
coated coils represent such a small share of the market. (Id.)
Carrier stated that there is a negative impact to performance when
a unit is first produced with coated coils, but Carrier asserted that
the coating prevents degradation over the lifetime of the unit as
compared to a unit with an uncoated coil in certain applications.
(Carrier, No. 8 at p. 3) In the event that coated coils are removed
from the list of specific components, Carrier stated that it is
concerned that energy conservation will be reduced over the life of
products in the applications that require these components. (Id.) If
coated coils are excluded from the list of specific components, Carrier
opposed the proposed 360-day compliance date for requirements for
representations of those models, stating that compliance would require
additional laboratory time and engineering resources that are currently
fully allocated to refrigerating transition projects required to meet
the Environmental Protection Agency's January 1, 2025 compliance date.
(Id.)
In response, DOE notes that the comments received in response to
the August 2023 TP NOPR indicate that some coil coatings may not have a
significant impact on performance while other coil coatings would.
Given that comments suggest that certain implementations of coated
coils do not impact energy use whereas others do, DOE has determined
that for those units for which coated coils do impact energy use,
representations should include those impacts, thereby providing full
disclosure for commercial customers.
Regarding Trane's assertion that including coated coils in
representations would be unduly burdensome and assertions that the
proposal would significantly increase the number of listed basic
models, DOE notes that not all coil coatings would necessarily warrant
separate basic models. DOE's definition for ``basic model'' at 10 CFR
431.92 specifies that a basic model for CUACs and CUHPs can comprise
models with ``comparably performing'' heat exchangers, which allows for
models with small variations in performance still to be included
together in the same basic model, so long as, consistent with the
clarifications adopted and previously discussed in this final rule, the
representations for the basic model are based on the least-efficient
configuration. Therefore, coil coatings with similar performance
impacts could be rated within the same basic model, and coil coatings
without a significant impact on performance could be included in the
same basic model as models with no coil coatings.
DOE expects that manufacturers already have a general understanding
of which coil coatings might have significant impacts on performance,
based on coil coating material and thickness. To the extent that a
manufacturer needs to determine whether a coil coating impacts
performance, the manufacturer could presumably determine this for a
given model and apply that understanding to other models. In other
words, a given coil coating is likely to have similar impacts across
all basic models of CUACs and CUHPs, such that finding that the coating
has no substantive impact on performance for a given model likely
indicates such a finding would apply to other models as well. Thus, DOE
expects that there would be no need to separately confirm ``no impact''
from a given coil coating on each basic model for which it is offered.
Further, DOE notes that AEDMs can be used to simulate performance of
models with coated coils such that not all models require testing.
Therefore, DOE has concluded that the proposed approach for coated
coils is not unduly burdensome.
DOE disagrees with Trane's comment that requiring all equipment to
include coil coatings in the basic models is not representative of the
vast majority of applications in the marketplace. The proposed approach
does not require that all representations for CUACs and CUHPs be based
on the presence of coil coatings; to the extent that manufacturers
offer a model with and without a coil coating that substantively
impacts performance, the manufacturer can rate as separate basic models
with and without the coil coatings. The basic model with ratings based
on performance without the coil coating would represent the shipments
of units without coil coatings. Further, for coil coatings that impact
performance, ratings based on the presence of coil coatings are
representative of shipments of units with such coil coatings, and
performance ratings based on the presence of the coil coating provide a
more accurate assessment of the unit's energy consumption to commercial
consumers.
Regarding AHRI's assertion that DOE has not provided any data to
support its proposal, DOE notes that comments received from both Trane
and Carrier indicate that some coil coatings have negative performance
impacts. Therefore, DOE concludes that no further data are needed to
justify adopting a provision requiring that ratings reflect coated
coils with substantive negative performance impacts, as this is
consistent with DOE's statutory authority to prescribe test procedures
that produce results that are representative of an average use cycle.
Additionally, as discussed earlier in this section, to the extent that
manufacturers produce units with coated coils that do not impact
performance as compared to units with uncoated coils, the manufacturer
may group such individual models together within the same basic model.
DOE disagrees with Carrier's assertion that including coated coils
in representations will result in energy conservation being reduced
over the life of products in the applications that require coated
coils. DOE expects that commercial customers who are currently
purchasing CUACs and CUHPs with coated coils do so because they
understand coil protection to be important for their application, and
DOE does not expect that such consumers would stop purchasing units
with coated coils if ratings are required to reflect performance
impacts of coated coils. However, the incorporation of performance
impacts of coated coils into ratings for CUACs and CUHPs will provide
commercial consumers with more accurate assessments of the energy
consumption of various models of CUACs and CUHPs, and will, therefore,
[[Page 44020]]
better elucidate any performance trade-offs associated with coil
coatings and will better inform consumers as to coil coatings that may
have less performance impact than others.
Regarding Carrier's concern about the timeline for required
representations with coated coils, as previously discussed, DOE is
adopting all provisions for specific components with a compliance date
starting when certifying to standards in terms of IVHE and IVEC, should
those standards be established, instead of the proposed compliance date
of 360 days after publication of the final rule in the Federal
Register. DOE has concluded that the adopted compliance date will
provide adequate lead time for manufacturers to develop representations
that reflect the amended test procedure and representation provisions
adopted in this final rule.
For the reasons described in the previous paragraphs and consistent
with the proposals in the August 2023 TP NOPR, DOE is not incorporating
coated coils into DOE's provisions specified in 10 CFR 429.43(a)(3)
that allow for the exclusion of specified components when determining
represented values for CUACs and CUHPs.
G. Represented Values
In the following sections, DOE discusses requirements regarding
represented values. To the extent DOE is adopting changes to the
requirements specified in 10 CFR 429 regarding representations of CUACs
and CUHPs, such amendments to 10 CFR part 429, will be required: (1)
starting 360 days after the date of publication in the Federal Register
of this final rule when certifying to an EER, IEER, or COP standard or
(2) starting on the compliance date of amended energy conservation
standards denominated in terms of IVEC or IVHE, should DOE adopt such
standards. Prior to 360 days after the date of publication in the
Federal Register of this final rule, the current requirements will
apply.
1. Cooling Capacity
In the August 2023 TP NOPR, DOE proposed to adopt provisions
relating to the represented value of cooling capacity at 10 CFR
429.43(a)(1)(iv), as well as the verification of cooling capacity
during enforcement testing at 10 CFR 429.134(g). 88 FR 56392, 56433-
56434 (August 17, 2023). The following sections include discussion of
the proposals in the NOPR, responses to related comments, and the
approaches adopted in this final rule.
a. Representations of Cooling Capacity
For CUACs and CUHPs, cooling capacity determines equipment class,
which in turn determines the applicable energy conservation standard.
10 CFR 431.97. Cooling capacity also dictates the minimum ESP test
condition applicable under Table 7 of AHRI 340/360-2022 (i.e., larger
capacity units are required to be tested at higher ESPs), which in turn
affects the performance of the unit. Cooling capacity is a required
represented value for all CUACs and CUHPs, but the requirements
currently specified in 10 CFR 429.43(a)(1)(iv) regarding how the
represented value of cooling capacity is determined only apply to
ACUACs and ACUHPs.
In the August 2023 TP NOPR, DOE proposed to make certain
modifications to these provisions and to expand the applicability of
these provisions, as amended, to all of the CUACs and CUHPs that are
the subject of this rulemaking. Specifically, DOE proposed that the
represented value of cooling capacity must be between 95 and 100
percent of the mean of the total cooling capacities measured for the
units in the sample. 88 FR 56392, 56433 (August 17, 2023). DOE also
proposed in the August 2023 TP NOPR that for units where the
represented value is determined through an AEDM, the represented value
of cooling capacity must be between 95 and 100 percent of the total
cooling capacity output simulated by the AEDM. Id. Additionally, DOE
proposed to remove the existing requirement in 10 CFR 429.43(a)(1)(iv)
that the represented value of cooling capacity correspond to the
nearest appropriate Btu/h multiple according to Table 4 of ANSI/AHRI
340/360-2007 in order to allow manufacturers flexibility in certifying
a rated value that provides a representation of cooling capacity that
may be more meaningful for commercial consumers. Id. DOE argued that
these proposals would ensure that the rated capacity is representative
of the unit's performance, while allowing manufacturers to
conservatively rate capacity if the manufacturer deemed such
conservative rating necessary to ensure that equipment is capable of
performing at the cooling capacity for which it is represented to
consumers. Id. DOE requested comment on its proposals related to the
representation of cooling capacity. Id.
Carrier supported DOE's cooling capacity representation proposal.
(Carrier, No. 8 at p. 4) AHRI commented that it opposes DOE's proposal
that represented capacity must be between 95 to 100 percent of measured
or simulated capacity for units where the represented value is
determined through an AEDM, asserting that this tolerance is too narrow
given that manufacturers can rate capacity at 95 percent of development
tests. AHRI further argued that the proposal allows for no (0 percent)
tolerance for variation because tested capacity during enforcement
could be at 105 percent (per DOE's proposal regarding cooling capacity
used to determine ESP requirements during DOE testing, which is
discussed in section III.G.1.b of this final rule). (AHRI, No. 15 at p.
6) Rheem commented that it opposed DOE's proposal for a one-sided
tolerance to be within 95 to 100 percent of rated cooling capacity,
arguing that this tolerance does not provide enough margin to account
for factors that affect measurements such as manufacturing variation
and test lab conditions. Instead, Rheem recommended that DOE consider
adoption of a wider two-sided tolerance that accounts for measurement
variability, such as 90 to 110 percent of rated capacity. (Rheem, No.
12 at p. 2) Lennox similarly commented that it opposes DOE's proposal
to require that the measured cooling capacity must be between 95 and
100 percent of the represented value and argued the proposed tolerance
is too narrow, given that manufacturers can rate up to 100 percent of
the tested value. Lennox recommended DOE instead provide a tolerance
range for measured capacity between 95 and 105 percent. (Lennox, No. 9
at p. 2)
As previously expressed, DOE's proposal to limit the represented
value of cooling capacity to be within 95 and 100 percent of the mean
of the total cooling capacities measured for the units in the sample
(or simulated by an AEDM) was intended to allow manufacturers to
conservatively rate capacity if the manufacturer deemed such
conservative rating necessary to ensure that equipment is capable of
performing at the cooling capacity for which it is represented to
consumers, but it was also intended to prevent manufacturers from over-
rating capacity. Comments from Rheem and Lennox suggest that the
commenters misunderstood the proposal to be imposing a tolerance on the
measured cooling capacity that is compared to the rated cooling
capacity. To clarify, this provision specifies how represented values
of cooling capacity are determined based on the sample of measured
values (or values calculated in an AEDM) for a given basic model.
Verification of rated cooling capacity, which is a separate issue, is
discussed in the following section.
[[Page 44021]]
Rated cooling capacity is used to determine the ESP requirements
used in testing; therefore, DOE has concluded that significant
underrating or overrating of capacity could cause unintended
consequences such as inequitable ratings due to differences in self
declarations. Further, significant underrating or overrating of
capacity would provide an inaccurate assessment to consumers of the
amount of space cooling a model can provide. Additionally, the 95 to
100 percent tolerance is consistent with what has been adopted for
other categories of commercial air-conditioning, such as DX-DOASes,
SPVUs, and CRACs. See 10 CFR 429.43(a)(3)(i)(B)(1), (a)(3)(iii)(B), and
(a)(3)(iv)(B).
Regarding comments on manufacturing variation and test variability,
DOE notes that if a manufacturer develops ratings for a basic model
based on testing, the manufacturer must test in accordance with 10 CFR
429.43(a)(1), which requires testing to be conducted on a sample
consistent of no less than two units per basic model. The provisions at
10 CFR 429.43(a)(1) specify statistics used to develop represented
values based on the mean and standard deviation of measurements--i.e.,
reflecting the variation in measurements included in the sample. If a
manufacturer chooses to consider more units or variation in measured
performance using different test chambers, DOE does not limit the
number of units or test chambers that can be used in the sample to
develop a rating for a basic model. In other words, a manufacturer can
include in the sample results from all testing it has conducted for a
basic model; therefore, there should not be a scenario in which a
manufacturer has test results suggesting that the mean of the sample
does not accurately reflect performance of the basic model, because
those test results can be included in the sample. Thus, there would be
no basis for a manufacturer to: (1) underrate cooling capacity (as
compared to the mean of measured values) by more than 5 percent; or (2)
overrate cooling capacity.
Similar logic applies if a manufacturer develops ratings for a
basic model based on AEDM simulations in accordance with 10 CFR
429.43(a)(2). DOE's regulations at 10 CFR 429.70 provide a minimum
number of tested models needed for validation of an AEDM, but if a
manufacturer is concerned that the tested models do not reflect what is
likely to be the ``average'' performance for those models given
manufacturing variation and test variability, DOE does not limit the
number of units or test chambers that can be used in the test results
used to validate an AEDM. Therefore, similar to development of ratings
via testing, for AEDM-simulated models, there would be no basis for a
manufacturer to: (1) underrate cooling capacity (as compared to the
AEDM-simulated values) by more than 5 percent; or (2) overrate cooling
capacity.
Consequently, DOE has concluded that the issues of manufacturing
variation and test variability are sufficiently captured in DOE's
existing regulations, so the Department is not adopting any wider
tolerance on the represented cooling capacity than proposed. As such,
DOE is adopting the provisions regarding representations of cooling
capacity as originally proposed.
b. Verification of Cooling Capacity
DOE currently outlines product-specific enforcement provisions at
10 CFR 429.134(g) for ACUACs and ACUHPs, specifically that the mean of
cooling capacity measurements during assessment or enforcement testing
will be used to determine the applicable standards (which depend on
cooling capacity) for purposes of compliance. First, DOE proposed in
the August 2023 TP NOPR to expand the scope of this requirement to
include ECUACs and WCUACs. 88 FR 56392, 56433 (August 17, 2023).
Second, DOE proposed in the August 2023 TP NOPR for all CUACs and CUHPs
that are the subject of this rulemaking that if the mean of the cooling
capacity measurements exceeds by more than 5 percent the cooling
capacity certified by the manufacturer, the mean of the measurement(s)
will be used to select the applicable minimum ESP test condition from
Table 7 of AHRI 340/360-2022 in appendix A or from Table 5 of the AHRI
1340-202X Draft in appendix A1.\30\ Id.
---------------------------------------------------------------------------
\30\ Table 5 of AHRI 1340-2023 includes the same ESP test
conditions as Table 5 of the AHRI 1340-202X Draft.
---------------------------------------------------------------------------
In the August 2023 TP NOPR, DOE requested comment on its proposal
related to the verification testing of cooling capacity. Id. In
response, Carrier and Trane disagreed with DOE's proposal to establish
a 5-percent tolerance on rated capacity for determining the applicable
minimum ESP condition when conducting verification testing. (Carrier,
No. 8 at p. 4; Trane, No. 14 at p. 5)
Trane asserted that this tolerance did not provide enough range for
manufacturing, design, and testing variability. Trane also asserted
that as a result of DOE's proposed 5-percent tested capacity limit
above capacity ratings, in some cases, capacity ratings would be
difficult to establish with the proposed approach because the tested
capacity and ESP requirement continually impact each other in a way
which would cause the tested capacity to be either too high or too low
depending on the ESP applied. Trane provided an example illustrating
the range of different capacities measured under different ESP
conditions for the same model. Trane further asserted that there would
be no benefit for manufacturers to conservatively rate units at lower
ESPs due to capacity fluctuations because doing so could increase the
minimum efficiency requirement and the resulting energy efficiency
performance could be negatively impacted. (Trane, No. 14 at p. 5)
Carrier argued that if manufacturers use the 5-percent margin in
the certified capacity rating as the proposed rule allows, it is likely
that the tested capacity during assessment and enforcement testing
could go above the 105 percent tolerance, and, therefore, Carrier
recommended that a tolerance of 10-percent be applied to the tested
capacity. (Carrier, No. 8 at p. 4)
Carrier also commented regarding an issue it found with the
tolerance proposal due to the new ESP requirements in AHRI 1340.
Carrier commented that the tested net capacity of a unit can decrease
at higher static pressures due to heat loss from the electric motor
operating against a higher static pressure. As such, Carrier commented
that the tested capacity at lower static pressures could be above the
test tolerance, but for the same unit at higher ESPs, the tested
capacity could be below the test tolerances. Carrier requested further
clarification from DOE as to which capacity should be used for ESP
determination if this situation were to occur. (Id.)
After careful consideration of comments received, DOE has concluded
that the proposed provision to use the measured cooling capacity during
assessment and enforcement testing to determine the ESP test condition
if the measured cooling capacity exceeds the certified cooling capacity
by more than 5 percent is not necessary at this time. As stated in the
August 2023 TP NOPR, the intent of this proposal was to ensure the unit
is being tested to the appropriate ESP and being evaluated against the
appropriate standard during assessment and enforcement testing. 88 FR
56392, 56433 (August 17, 2023). DOE has concluded that the adopted
requirement (discussed in section III.G.1.a of this final rule) for the
represented value of cooling capacity to be between 95 and 100 percent
of the
[[Page 44022]]
mean of the total cooling capacities measured for the units in the
sample (or between 95 and 100 percent of the AEDM-simulated cooling
capacity) will ensure that the rated cooling capacity accurately
reflects the cooling capacity for a basic model. Therefore, DOE has
determined that maintaining the current policy of selecting the ESP
requirement used for DOE testing based on the rated cooling capacity
rather than the measured cooling capacity will provide a representative
measure of the equipment's energy use. DOE acknowledges the issue
raised by commenters, and notes that maintaining the current policy
will prevent a situation in which the measured capacity iteratively
affects the applicable ESP requirement, and will avoid any conflicts
between DOE's enforcement provisions and DOE's adopted provisions
allowing conservative rating of cooling capacity as low as 95 percent.
As such, DOE is not adopting its proposal that the mean of measured
capacities be used to select the applicable minimum ESP condition when
it exceeds the rated cooling capacity of a basic model by more than 5
percent.
DOE did not receive comment regarding its proposal to expand the
scope of the current product-specific enforcement requirements at 10
CFR 429.134(g) to ECUACs and WCUACs. DOE has determined that extending
this provision to ECUACs and WCUACs will ensure that the unit is being
evaluated against the appropriate standard. As such, DOE is expanding
the scope of the requirement at 10 CFR 429.134(g) that the mean of
cooling capacity measurements will be used to determine the applicable
standards (which depend on cooling capacity) for purposes of compliance
to apply to ECUACs and WCUACs.
2. AEDM Tolerance for IVEC and IVHE
As discussed previously, DOE's existing testing regulations allow
the use of an AEDM, in lieu of testing, to simulate the efficiency of
CUACs and CUHPs. 10 CFR 429.43(a). For models certified with an AEDM,
results from DOE verification tests are subject to certain tolerances
when compared to certified ratings. In the August 2023 TP NOPR, DOE
proposed in table 2 to paragraph (c)(5)(vi)(B) at 10 CFR 429.70 to
specify a tolerance of 10 percent for CUAC and CUHP verification tests
for IVEC and IVHE. 88 FR 56392, 56434 (August 17, 2023). This tolerance
is identical to the current tolerance specified for IEER (for ACUACs
and ACUHPs) and for integrated metrics for other categories of
commercial air conditioners and heat pumps (e.g., integrated seasonal
coefficient of performance 2 and integrated seasonal moisture removal
efficiency 2 for DX-DOASes). DOE also proposed to specify a tolerance
of 5 percent for CUAC and CUHP verification testing for the optional
EER2 and COP2 metrics. This tolerance is identical to the current
tolerances specified for EER and COP for CUACs and CUHPs. Id.
DOE did not receive any comments regarding this proposal.
Therefore, DOE is adopting the AEDM tolerances applicable to IVEC,
IVHE, EER2, and COP2 as proposed in the August 2023 TP NOPR.
3. Minimum Part-Load Airflow
As previously discussed in sections III.D.1 and III.D.2 of this
document, the IVEC and IVHE metrics account for energy consumed
(specifically that of the indoor fan) in mechanical cooling and
heating, as well as modes other than mechanical cooling and heating
(e.g., economizer-only cooling, cooling season ventilation, heating
season ventilation). IVEC and IVHE do not include separate tests or
airflow rates for ventilation hours or economizer-only cooling (only
applicable to IVEC). For example, for the economizer-only cooling hours
in the D bin, the indoor fan power measured when operating at the
lowest manufacturer-specified part-load airflow for a given load bin is
applied for economizer-only cooling hours in that bin. Section 6.2.7
and 6.3.10 of the AHRI 1340-202X Draft require that the lowest indoor
fan power measured for cooling or heating tests is applied for cooling-
season ventilation hours in IVEC and heating-season ventilation hours
in IVHE. AHRI 1340-2023 maintains these provisions. Therefore,
considering mechanical cooling and heating, as well as other operating
modes (e.g., economizer-only cooling, ventilation), the indoor fan
power measured at the lowest manufacturer-specified part-load cooling
and heating airflow rates represents a significant fraction of the
power included in the IVEC and IVHE metrics (i.e., indoor fan power
measured at these airflow rates is weighted by a significant number of
hours), and differences in the lowest manufacturer-specified part-load
airflow can significantly impact IVEC and IVHE ratings.
Based on examination of publicly-available product literature, DOE
understands that many basic models of a CUAC or CUHP have controls that
allow for modulation of the minimum airflow used across a wide range of
airflow turndown. DOE's research suggests that many models are
distributed in commerce with an ``as-shipped'' minimum airflow and/or a
default minimum airflow setting recommended in manufacturer
installation instructions. However, in many cases, DOE observed that
the unit controls allow the installer to change this minimum airflow
setting during installation to reflect any constraints specific to a
particular installation. DOE understands that such constraints may
include the duct distribution system, the thermostat the CUAC or CUHP
is paired with, and the minimum ventilation rate for the conditioned
space served by the CUAC or CUHP. To ensure that IVEC and IVHE ratings
reflect indoor fan power that is generally representative of airflow
rates that would be used in the field for a given basic model, DOE
considered the following two options for requirements related to
minimum part-load airflow used for representations of IVEC and IVHE in
the August 2023 TP NOPR:
1. Representations of IVEC and IVHE (including IVHEc, as
applicable) must be based on setting the lowest stage of airflow to the
highest part-load airflow allowable by the basic model's system
controls. For example, if fan control settings for a basic model allow
its lowest stage of airflow to range from 40 to 60 percent, the basic
model will need to be represented based on the lowest stage of airflow
set to 60 percent of the full-load airflow.
2. Representations of IVEC and IVHE (including IVHEc, as
applicable) must be determined using minimum part-load airflow that is
no lower than the highest of the following: (1) the minimum part-load
airflow obtained using the as-shipped system control settings; (2) the
minimum part-load airflow obtained using the default system control
settings specified in the manufacturer installation instructions (as
applicable); and (3) the minimum airflow rate specified in section
5.18.2 of AHRI 1340-202X Draft.\31\ 88 FR 56392, 56434-56435 (August
17, 2023).
---------------------------------------------------------------------------
\31\ Section 5.18.2 of AHRI 1340-2023 includes the same
provisions as those specified in section 5.18.2 of the AHRI 1340-
202X Draft.
---------------------------------------------------------------------------
In the August 2023 TP NOPR, DOE tentatively concluded that option
1, which requires representations based on the highest minimum part-
load airflow allowable by system controls, may result in
unrepresentatively high airflow rates in cases in which a basic model
allows configuration of minimum airflow to a very high percentage to
accommodate a small fraction of installations in which minimum part-
load airflow must be high (e.g., in applications with very high minimum
ventilation rates). Id.
[[Page 44023]]
Therefore, DOE proposed in the August 2023 TP NOPR to adopt option 2
and requested comment on its proposal, as well as any alternate options
not listed that would ensure representations of IVEC and IVHE are based
on minimum part-load airflow that is representative of field
installations. Id.
AHRI, Carrier, Lennox, Rheem, and Trane opposed DOE's proposal and
argued that the only restriction on minimum airflow rate should be what
was agreed to in Recommendation #6 of the ACUAC and ACUHP Working Group
TP Term Sheet (i.e., limiting the minimum airflow rate to that
specified in Section 5.18.2 of the AHRI 1340-202X Draft). (AHRI, No. 15
at pp. 6-7; Carrier, No. 8 at p. 5; Lennox, No. 9 at p. 3; Rheem, No.
12 at p. 2; Trane No. 14 at p. 6) Carrier commented that the ACUAC and
ACUHP Working Group TP Term Sheet includes a requirement for
manufacturers to certify the airflow that is used in the lowest-stage
cooling test, and stated that this ensures that the unit is capable of
running in application at the airflows that were used in the tests or
AEDM. Carrier further stated that restricting the broad range of
airflow settings in commercial equipment to only those that are default
from the factory is not appropriate and recommended that no further
restrictions be placed on tested airflows beyond what was agreed upon
in the ACUAC and ACUHP Working Group TP Term Sheet. (Carrier, No. 8 at
p. 5)
AHRI and Trane asserted that ratings are based on a representative
average of many customer applications and that equipment built for
stock has a default airflow and ESP with the expectation that customers
will adjust and commission (i.e., adjust sheaves, VFDs, discharge air
temperature setpoints, or other parts of the equipment) for their
specific applications, and made-to-order equipment is built per
customer specifications for a given installation. (AHRI, No. 15 at pp.
6-7; Trane, No. 14 at p. 6) AHRI and Trane further stated that the
default airflow and ESP may not align with the ESP requirements in the
test procedure, and that considerable variation across installations
does not align with a single rating point. (Id.) Trane further stated
that equipment utilizing sheaves in the airflow system almost always
require field adjustment up to and including different sheave
components ordered as field-installed accessories to complete an
equipment installation. (Trane, No. 14 at p. 6) AHRI and Trane further
stated that supplemental test instructions submitted as part of
certification ensure that the equipment is properly set up for any
verification testing as per the test procedure. (AHRI, No. 15 at pp. 6-
7; Trane, No. 14 at p. 6)
ASAP & ACEEE expressed support for DOE's proposal regarding
determination of part-load airflow, stating that it improves
representativeness by considering the default and as-shipped settings,
and expressed concern that without DOE's proposal, manufacturers could
rate models with airflows lower than would be representative. (ASAP &
ACEEE, No. 11 at pp. 1-2)
Regarding the comments that DOE should impose no additional
requirements on minimum part-load airflow and that the only
requirements should be the ones in the ACUAC/HP Working Group TP Term
Sheet, DOE has concluded that the minimum part-load airflow
requirements proposed for 10 CFR 429.43 have a different purpose than,
and do not deviate from or conflict with, the requirement regarding
minimum airflow specified in Recommendation #6 of the ACUAC and ACUHP
Working Group TP Term Sheet (which is the minimum part-load airflow
specified in section 5.18.2 of the AHRI 1340-202X Draft and AHRI 1340-
2023). In this final rule, DOE is adopting section 5.18.2 of AHRI 1340-
2023 in the test procedure at appendix A1, consistent with
Recommendation #6 of the ACUAC and ACUHP Working Group TP Term Sheet.
This minimum part-load airflow requirement from the Term Sheet and AHRI
1340 represents the minimum airflow required to provide adequate
ventilation in a typical building (based on an average of building
types used to develop the IVEC metric, as discussed in section III.D.1
of this document). In other words, the requirement in the test
procedure is a lower bound on minimum airflow for any CUAC/HP model
serving the average building, but it is not necessarily representative
of the minimum part-load airflow used in the field for a given CUAC or
CUHP model. For example, for a model that is typically installed with a
minimum part-load airflow of 67 percent of full-load airflow, the
minimum airflow limit specified in section 5.18.2 of AHRI 1340-2023
would be far lower than that that representative minimum and would,
therefore, fail to serve as a guardrail ensuring the minimum part-load
airflow used for rating that model is representative of how the model
is typically installed. DOE found in an examination of publicly-
available product literature, the range of airflows, including minimum
part-load airflow, can differ between models based on application,
design of the unit, and manufacturer preferences.
As part of Working Group discussions regarding energy conservation
standards, which occurred after the ACUAC and ACUHP Working Group TP
Term Sheet was agreed to, it was discussed that minimum part-load
airflow is one of the largest determinants of IVEC performance (see
EERE-2022-BT-STD-0015-0092 at pp. 22-27). Specifically, during the
course of the Working Group energy conservation standards negotiations,
industry members in the ACUAC/HP Working Group provided a DOE
contractor with a confidential, anonymized dataset that included
simulated IEER and IVEC values for more than 100 models of CUACs and
CUHPs currently available on the market. Analysis of this dataset
indicated that the minimum part-load airflow is one of the most
significant differentiators between models with lower and higher IVEC
values. This is because, as discussed, the minimum part-load airflow is
allocated to a large number of hours when calculating IVEC, so lower
values of minimum part-load airflow are associated with higher values
of IVEC. Given the Department's statutory obligation to ensure that
ratings are based on a test procedure that is reasonably designed to
produce test results which reflect energy efficiency during a
representative average use cycle that is not unduly burdensome to
conduct (42 U.S.C. 6314(a)(2)), DOE has concluded that provisions
beyond those included in AHRI 1340-2023 are needed to ensure that the
minimum part-load airflow used to determine IVEC is representative of
how a given model is typically installed. Such provisions, when
combined with the minimum airflow limit in AHRI 1340-2023 that DOE is
also adopting in this final rule, would prevent use of an
unrepresentatively low minimum part-load airflow that could boost
efficiency ratings but not ultimately result in energy savings in the
field. The provisions proposed by DOE address this issue by using the
as-shipped or default values of minimum part-load airflow as indicators
of the representative minimum part-load airflow used in the field.
Although industry commenters objected to having additional requirements
on the minimum part-load airflow, the objecting commenters apparently
did not recognize the representativeness issue identified by DOE nor
provide any alternate approaches to address the issue. In the absence
of any suggested alternative approaches, DOE has determined that the
proposed approach
[[Page 44024]]
is appropriate to ensure that the minimum part-load airflow used to
determine IVEC is representative of field operation.
Regarding comments from AHRI and Trane that ratings are based on a
representative average of many customer applications and that
considerable variation across installations does not align with a
single rating point, DOE agrees that the test procedure is and should
be based on a representative average of many applications. While this
average rating inherently cannot perfectly represent every application,
it should be representative of an average or typical installation. DOE
disagrees that its proposed minimum part-load airflow provisions
deviate from this ``representative average application'' approach
underlying the test procedure. Without DOE's proposed provisions, there
would be no mechanism constraining the certified minimum part-load
airflow to be representative of how a given model is typically
installed, and further, manufacturers would be incentivized to certify
as low a minimum part-load airflow as possible in order to achieve a
higher IVEC rating. DOE has concluded that the default or as-shipped
minimum airflow setting is the best publicly-available proxy for what
the most representative minimum part-load airflow is for a given model.
DOE understands that many installers of CUACs and CUHPs do not change
settings from their default and/or as-shipped values; therefore, DOE
expects that manufacturers are incentivized to provide default and/or
as-shipped minimum airflow values that are appropriate for and
representative of a typical installation. DOE understands that that
some applications may have lower minimum part-load airflows than
provided by the default settings, but has concluded that the default or
as-shipped minimum part-load airflow settings are representative of a
typical installation. Additionally, the default airflow setting for a
specific model is not a single rating condition for all models (such as
an ESP requirement or test condition)--it instead reflects whatever
model-specific considerations the manufacturer might use to determine
the default or as-shipped minimum part-load airflow for the model.
Additionally, DOE notes that several of the concerns expressed by
commenters do not apply to DOE's proposal. Specifically, concerns
expressed regarding the adjustment of sheaves and whether the default
airflow settings are compatible with the airflow and ESP requirements
in the test procedure are not relevant to the proposal, because DOE's
proposal only addresses part-load airflow. For CUACs and CUHPs with
adjustable sheaves, the sheaves are adjusted when installing the unit
to ensure the fan drive assembly is providing the appropriate airflow
for a given installation. Similarly, sheaves are typically adjusted as
part of test set-up for the full-load cooling test to meet the full-
load airflow and ESP test requirements withing tolerance. However,
sheaves are not adjusted between full-load and part-load operation, and
are, therefore, not relevant to this proposal. Similarly, DOE
recognizes that the default full-load airflow settings may not be
compatible with the airflow and ESP requirements in the test procedure,
but DOE has proposed no restrictions on the certified full-load
airflow. In summary, DOE's proposal does not have any effect on the fan
control settings used to achieve the full-load airflow and ESP used for
testing. DOE's proposal only affects the minimum part-load airflow for
testing, which is a percentage of the full-load airflow already
achieved in the full-load cooling test, not an absolute value. Part-
load airflow is typically reduced by lowering the power provided to the
fan motor by a VFD (relative to the power provided for full-load
cooling), an adjustment that it made automatically in field
installations but can be manually programmed during test. Therefore,
regardless of how different the fan control settings needed to achieve
the full-load airflow and ESP used for testing may be from the default
or as-shipped full-load airflow settings, DOE has concluded that the
default or as-shipped minimum part-load airflow settings provide an
appropriate and representative degree of airflow turndown that will
allow for meeting all test tolerances.
Regarding comments by AHRI and Trane that supplemental test
instructions indicate how units should be set up for test, DOE notes
that supplemental test instructions are used to ensure that DOE testing
is performed consistent with how the manufacturer rated the equipment.
Supplemental test instructions do not ensure that manufacturer-
specified settings are representative of field use for a basic model.
Similarly, the manufacturer's certification of the minimum airflow used
for ratings of a basic model (which was cited by Carrier) does not
ensure that the certified airflow is representative of field use. The
provisions proposed in 10 CFR 429.43 for minimum part-load airflow,
however, are intended to ensure that manufacturer-specified and
certified minimum part-load airflows are representative of field use.
For the reasons discussed in the previous paragraphs, DOE is
adopting the proposed provisions for minimum airflow in 10 CFR 429.43.
DOE is not amending certification requirements for CUACs and CUHPs in
this rulemaking, but DOE will consider such amendments in a separate
rulemaking for certification, compliance, and enforcement. As part of
that rulemaking, DOE will consider certification requirements
pertaining to this minimum airflow issue, such as requiring
certification of the range of minimum part-load airflow allowed by
system controls for each basic model.
H. Enforcement Procedure for Verifying Cut-In and Cut-Out Temperatures
Recommendation #10 of the ACUAC and ACUHP Working Group TP Term
Sheet states that DOE will adopt product-specific enforcement
provisions for ACUHPs that include a method to verify certified cut-out
and cut-in temperatures based on the test method outlined in the
Residential Cold-Climate Heat Pump Technology Challenge (``CCHP
Challenge'').\32\ The docketed AHRI 1340-202X Draft did not include
test provisions for verifying cut-in and cut-out temperatures, but in
the August 2023 TP NOPR, DOE proposed to adopt a method for verifying
certified cut-out and cut-in temperatures at 10 CFR 429.134(g)
consistent with Recommendation #10 of the ACUAC and ACUHP Working Group
TP Term Sheet. 88 FR 56392, 56435 (August 17, 2023). Specifically,
consistent with the CCHP Challenge method and the ACUAC and ACUHP
Working Group TP Term Sheet, the proposed method specified gradually
ramping down outdoor air temperature until the unit cuts out and
gradually ramping back up outdoor air temperature until the unit cuts
back on, with the temperature ramp-up and ramp-down conducted at 1.0
[deg]F every 5 minutes. DOE did not receive any comments on its
proposed method for verifying cut-in and cut-out temperatures.
---------------------------------------------------------------------------
\32\ See www.energy.gov/sites/default/files/2021-10/bto-cchp-tech-challenge-spec-102521.pdf.
---------------------------------------------------------------------------
Appendix H of AHRI 1340-2023 includes a procedure for verifying
cut-in and cut-out temperatures that is generally consistent with the
procedure proposed in the August 2023 TP NOPR. As such, and consistent
with Recommendation #10 of the ACUAC and ACUHP Working Group TP Term
Sheet, DOE is adopting this procedure for verifying certified cut-in
and cut-out temperatures through reference to
[[Page 44025]]
appendix H of AHRI 1340-2023 in DOE's product-specific enforcement
provisions at 10 CFR 429.134(g). DOE will address certification
requirements for CUACs and CUHPs, including the potential requirement
for certification of cut-out and cut-in temperatures, in a separate
rulemaking for certification, compliance, and enforcement.
I. Organization of the Regulatory Text for CUACs and CUHPs
In addition to the substantive changes discussed previously in this
document, DOE proposed organizational changes to table 1 to 10 CFR
431.96(b) and tables 1 through 6 to 10 CFR 431.97 in the August 2023 TP
NOPR that were not substantive and were intended to reflect terminology
changes and to improve the overall readability of the tables. 88 FR
56392, 56435-56436 (August 17, 2023).
Specifically, in table 1 to 10 CFR 431.96(b) (regarding test
procedures for commercial air conditioners and heat pumps), DOE
proposed to revise terminology to reflect the proposed definition for
``commercial unitary air conditioners with a rated cooling capacity
greater than or equal to 65,000 Btu/h (CUACs) and commercial unitary
heat pumps with a rated cooling capacity greater than or equal to
65,000 Btu/h (CUHPs),'' discussed further in section III.B.1 of this
final rule. Id.
Additionally, tables 1 through 5 to 10 CFR 431.97 currently specify
cooling and heating standards for CUACs, CUHPs, and water-source heat
pumps (``WSHPs''). DOE also proposed to revise this terminology to
reflect the proposed definition for CUACs and CUHPs, remove outdated
standards no longer in effect, combine cooling and heating standards
into the same tables, and create separate tables for standards for
ACUACs and ACUHPs (in Table 1), WCUACs (in Table 2), ECUACs (in Table
3), double-duct systems (in Table 4), and WSHPs (in Table 5). Id.
DOE did not receive comment in response to the August 2023 TP NOPR
with respect to the proposed organization of regulatory text for CUACs
and CUHPs. DOE has determined that these changes will improve the
overall readability of the tables in 10 CFR 431.96 and 431.97 and are
consistent with the other changes adopted in this final rule. However,
as discussed in section III.B.1, DOE is not finalizing the proposed
definition for CUAC and CUHP. As such, DOE is not implementing the
proposed changes in 10 CFR 431.96 and 431.97 to reflect the proposed
term for CUAC and CUHP. Other than these terminology changes, DOE is
adopting its proposed reorganization of regulatory text for CUACs and
CUHPs in this final rule.
J. Effective and Compliance Dates
The effective date for the adopted test procedure amendments will
be 75 days after the date of publication of this final rule in the
Federal Register. EPCA prescribes that all representations of energy
efficiency and energy use, including those made on marketing materials
and product labels, must be made in accordance with an amended test
procedure, beginning 360 days after the date of publication of the
final rule in the Federal Register. (42 U.S.C. 6314(d)(1)) To the
extent the modified test procedure adopted in this final rule is
required only for the evaluation and issuance of updated efficiency
standards, compliance with the amended test procedure does not require
use of such modified test procedure provisions until the compliance
date of updated standards.
K. Test Procedure Costs and Impact
EPCA requires that the test procedures for commercial package air
conditioning and heating equipment, which includes CUACs and CUHPs, be
those generally accepted industry testing procedures or rating
procedures developed or recognized by either AHRI or ASHRAE, as
referenced in ASHRAE Standard 90.1. (42 U.S.C. 6314(a)(4)(A)) Further,
if such an industry test procedure is amended, DOE must amend its test
procedure to be consistent with the amended industry test procedure,
unless DOE determines, by rule published in the Federal Register and
supported by clear and convincing evidence, that such an amended test
procedure would not meet the requirements in 42 U.S.C. 6314(a)(2)-(3)
related to representative use and test burden. (42 U.S.C.
6314(a)(4)(B))
In this final rule, DOE is revising the existing test procedure for
CUACs and CUHPs (consolidating for ACUACs and ACUHPs, ECUACs, and
WCUACs) at appendix A and adopting an amended test procedure at
appendix A1. These adoptions are discussed in the following sub-
sections. DOE has also amended its representation and enforcement
provisions for CUACs and CUHPs.
1. Appendix A
In this final rule, DOE has amended the existing Federal test
procedure for CUACs and CUHPs (including double-duct systems), which is
currently located at appendix A for ACUACs and ACUHPs and 10 CFR 431.96
for ECUACs and WCUACs. Specifically, DOE consolidated the test
procedures for ACUACs and ACUHPs, ECUACs, and WCUACs at appendix A and
updated the test procedure to incorporate by reference an updated
version of the applicable industry test method, AHRI 340/360-2022. The
revisions to appendix A retain the current efficiency metrics (i.e.,
EER, IEER, and COP). The testing requirements in appendix A are
generally consistent with those in AHRI 340/360-2022, which in turn
references ANSI/ASHRAE 37-2009. This is generally consistent with the
industry test procedures referenced in the latest version of ASHRAE
Standard 90.1.
DOE has determined that the amendments to appendix A will improve
the representativeness, accuracy, and reproducibility of the test
results and will not be unduly burdensome for manufacturers to conduct
or result in increased testing cost as compared to the current test
procedure. The revisions to the test procedure in appendix A for
measuring EER, IEER, and COP per AHRI 340/360-2022 will not increase
third-party laboratory testing costs per unit relative to the current
DOE test procedure. DOE estimates the current costs of physical testing
to the current required metrics to be $10,500 for ACUACs, $12,000 for
ACUHPs, $6,800 for double-duct air conditioners, $8,300 for double-duct
heat pumps, and $6,800 for ECUACs and WCUACs. Further, DOE has
concluded that the adopted revisions to the test procedure in appendix
A will not change efficiency ratings for CUACs and CUHPs, and,
therefore, will not require retesting solely as a result of DOE's
adoption of this amendment to the DOE test procedure.\33\
---------------------------------------------------------------------------
\33\ Manufacturers are not required to perform laboratory
testing on all basic models. In accordance with 10 CFR 429.70, CUAC
and CUHP manufacturers may elect to use AEDMs. An AEDM is a computer
modeling or mathematical tool that predicts the performance of non-
tested basic models. These computer modeling and mathematical tools,
when properly developed, can provide a means to predict the energy
usage or efficiency characteristics of a basic model of a given
covered product or equipment and to reduce the burden and cost
associated with testing.
---------------------------------------------------------------------------
2. Appendix A1
In the August 2023 TP NOPR, DOE proposed to amend the existing test
procedure for CUACs and CUHPs (including double-duct equipment) by
adopting a new appendix A1 that references AHRI 1340-202X Draft,
including the IVEC and IVHE energy efficiency metrics. DOE noted that
the proposed test procedure in appendix A1 would lead to an increase in
test cost from the current Federal test procedure; therefore, DOE
presented estimates of
[[Page 44026]]
the test costs associated with the proposed test procedure in appendix
A1. 88 FR 56392, 56436-56437 (August 17, 2023). The proposed test cost
estimates are presented in Table III-6. DOE requested comments
regarding its tentative understanding of the impact of the proposals in
the NOPR, particularly regarding DOE's initial estimate of the cost
impacts associated with appendix A1. Id.
Carrier commented that the test cost estimates presented in the
NOPR are likely incorrect, as there is a substantial difference in set-
up time and the amount of energy required to test from the smallest
systems to the largest. (Carrier, No. 8 at p. 5)
Trane expressed concerns regarding the cost estimate for the 5
[deg]F optional test, and the commenter argued that testing to these
low temperatures would require significant capital investment on the
part of certification laboratories, as well as increased time to
conduct testing at low temperature conditions due to the need for more
frequent defrosting of the facility. (Trane, No. 14 at pp. 6-7)
Specifically, Trane stated the test cost for the optional 5 [deg]F test
should be closer to $9,600 (representing four additional shifts in the
test laboratory) rather than the $2,000-$4,000 additional cost
estimated in the NOPR. Id.
In this final rule, DOE is amending the existing test procedure for
CUACs and CUHPs (including double-duct equipment) by adopting a new
appendix A1 that utilizes the most recent version of the applicable
industry consensus test procedure, AHRI 1340-2023, including the IVEC
and IVHE energy efficiency metrics. Should DOE adopt standards in a
future energy conservation standards rulemaking denominated in terms of
the new metrics, the test procedure in appendix A1 (which references
AHRI 1340-2023) would be required.
In light of the comments received, DOE once again considered the
estimated costs and burdens associated with the new appendix A1. For
the reasons that follow, DOE determined these costs to have remained
largely the same as those presented in the August 2023 TP NOPR, with
just a few adjustments.
DOE has determined that these amendments will be representative of
an average use cycle and will not be unduly burdensome for
manufacturers to conduct. The test procedure in appendix A1 will lead
to an increase in test cost from the current Federal test procedure, as
discussed in the following paragraphs. The following paragraphs include
estimates for increases in cost of testing at a third-party laboratory.
The change in ESP requirements discussed in section III.D.1 that
apply to measuring the IVEC and IVHE metrics will require additional
test set-up that DOE expects will increase test costs. DOE has
concluded that metal ductwork will need to be fabricated for testing to
withstand the higher ESP requirements (as compared to foamboard
ductwork typically used for testing to the current test procedure). DOE
estimates a test cost increase ranging from $500 to $1,500 per unit,
depending on the unit size/cooling capacity, associated with this
transition to metal ductwork. To meet the return/supply duct ESP
requirement, DOE estimates an increase of $200 per unit for the time
required to apply return duct restrictions. In combination, DOE
estimates a total test cost increase of between $700 and $1,700 per
unit to meet the new ESP requirements.
For determining IVEC, DOE has concluded that there will not be an
increase in testing cost as compared to measuring IEER per the current
Federal test procedure, beyond the costs associated with the new ESP
requirements discussed previously.
For determining IVHE, there are two required heating tests and
several additional optional heating tests. The required heating tests
are full-load tests at 47 [deg]F and 17 [deg]F. The full-load test at
47 [deg]F is already required for the current Federal test procedure
for determining COP. The full-load test at 17 [deg]F is currently
required for the AHRI certification program. Because all identified
CUHP manufacturers are AHRI members and participate in the AHRI
certification program and because third-party laboratories currently
have the capability to perform these tests, DOE expects that that the
required heating tests for IVHE will not increase test cost as compared
to testing that is typically already conducted, beyond the costs
associated with the new ESP requirements discussed previously.
Optional heating tests for CUHPs will increase the cost of heating
testing if conducted. The optional tests for IVHE are outlined in
III.D.2 of this final rule, which include: (1) an additional full-load
test at 5 [deg]F; (2) part-load tests at 17 [deg]F and 47 [deg]F
(including up to 2 part-load tests at each temperature); and (3) for
variable-speed units, boost tests at 17 [deg]F and 5 [deg]F. DOE
estimates that each optional test conducted will increase the cost of
heating testing by $2,000 to $4,000 depending on the test condition.
Regarding Trane's comments on burden of the optional 5 [deg]F test,
DOE disagrees that conducting a heating test for CUHPs would cost as
much as $9,600 at third-party laboratories. DOE expects Trane's
estimate may be referring to test facilities that are not designed for
low-temperature testing. However, DOE is aware of multiple third-party
laboratories commonly used by the CUAC and CUHP industry for testing
that have test chambers that can already achieve the 5 [deg]F test
condition in much less time than would warrant four shifts. Further,
DOE notes that it has received a test quote from a third-party
laboratory for conducting the 5 [deg]F test that is within the range of
test costs estimated in the August 2023 TP NOPR. Therefore, DOE
maintains its estimate of $2,000 to $4,000 for each optional heating
test. DOE reiterates that these tests are optional, and, thus, the test
procedure adopted in this final rule will not require any manufacturers
to conduct a 5 [deg]F test.
For ECUACs, WCUACs, and double-duct systems, the current Federal
test procedure requires testing to EER for cooling tests; testing to
IEER is not currently required for ECUACs, WCUACs, or double-duct
systems. Because measuring EER requires only a single test, DOE expects
that measuring IVEC for ECUACs, WCUACs, and double-duct systems will
increase the cost of cooling testing. Specifically, DOE estimates the
cost of additional cooling tests to be $3,700 per unit. Further, the
previously discussed costs associated with the new indoor air ESP
requirements ($700 to $1,700 depending on unit size) will also apply to
ECUACs, WCUACs, and double-duct systems. In addition, for double-duct
systems DOE expects that testing to appendix A1 will require an
additional $2,000 per unit for set-up to meet the non-zero outdoor air
ESP requirement. Otherwise, DOE expects similar test burden for
determining IVHE for double-duct systems as for determining IVHE for
conventional ACUHPs, as discussed in the preceding paragraphs.
Regarding Carrier's comment about the burden of testing higher-
capacity equipment, DOE acknowledges that there may be higher third-
party laboratory test costs associated with test set-up for larger
units than for smaller units. Accordingly, DOE estimates that up to an
additional shift (which DOE estimates to cost approximately $2,600) may
be necessary for test set-up for the largest covered basic models, and
the Department has adjusted the upper bound of its estimated test cost
range accordingly.
Table III-6 shows DOE's estimates for testing to the current
Federal test procedure and the test procedure in appendix A1.
[[Page 44027]]
[GRAPHIC] [TIFF OMITTED] TR20MY24.133
In the August 2023 TP NOPR, DOE also estimated the cost to develop
and validate an AEDM for determining IVEC (and IVHE as applicable) for
CUACs and CUHPs (including double-duct systems) to be $19,000 per AEDM.
Once the AEDM is developed, DOE estimated that it would take one hour
of an engineer's time (calculated based upon an engineering technician
wage of $41 per hour) to determine efficiency for each basic model
using the AEDM. 88 FR 56392, 56437 (August 17, 2023).
AHRI, Carrier, Trane, and Rheem commented that the proposed cost to
develop an AEDM to rate units to the new IVEC and IVHE metrics were
greatly underestimated in the NOPR. (AHRI, No. 15 at p. 7; Carrier, No.
8 at p. 5; Trane, No. 14 at pp. 6-7; Rheem, No. 12 at p. 3) Carrier
stated that to lower potential risk of failure or product availability
associated with an AEDM issue, manufacturers typically test more than
the minimum two units required for AEDM validation, and manufacturers
develop multiple AEDMs to limit the number of basic models for which
each AEDM was used to generate ratings. (Carrier, No. 8 at p. 5) AHRI
and Trane stated that manufacturers may test significantly more units
than the two required by DOE to validate an AEDM. (AHRI, No. 15 at p.
7; Trane, No. 14 at pp. 6-7) Rheem stated that the adoption of appendix
A1 will require significant investment by manufacturers for product
development, laboratory upgrades, and additional testing. (Rheem, No.
12 at p. 3)
In response, DOE notes that most CUAC/HP manufacturers have in-
house testing capabilities and would principally use those resources
for required testing. DOE expects in-house testing to be cheaper on a
per-test basis than third-party testing. DOE is conservatively
presenting costs associated with a scenario where a manufacturer does
not have these in-house testing resources, or where those resources are
otherwise occupied and the manufacturer has to rely on third-party
testing. Apart from the optional heating tests, DOE has concluded that
the amended test procedures adopted in this final rule would not
require capital improvements to in-house testing facilities. (DOE once
again notes that the 5 [deg]F test, which some manufacturer's test
chambers may need upgrades to conduct, is optional.) Further, the
amended test procedures will not require manufacturers to undergo any
new product development. Any burden associated with model redesign to
meet amended energy conservation standards would be addressed in a
separate standards rulemaking.
As discussed, DOE has concluded that that the potential adoption of
amended energy conservation standards denominated in terms of IVEC and
IVHE (and corresponding requirement to use the adopted test procedure
in appendix A1) would alter the measured energy efficiency of CUACs and
CUHPs. Consequently, manufacturers would not be able to rely on data
generated under the current test procedure and would, therefore, be
required to re-rate CUAC and CUHP models. In accordance with 10 CFR
429.70, however, CUAC and CUHP manufacturers may elect to use AEDMs to
rate models, which significantly reduces costs to industry. DOE has
updated its estimate of AEDM creation costs to reflect both the
previously mentioned modest increase in labor time associated with
testing of large units and the cost range of physical testing broadly.
In this final rule, DOE estimates the total cost to develop and
validate an AEDM for determining IVEC (and IVHE as applicable) for
CUACs and CUHPs (including double-duct systems) to be between $26,400
and $40,600 per AEDM.\34\ Once the AEDM is developed, DOE estimates
that it will take one hour of an engineer's time (calculated based upon
a fully burdened engineering technician wage of $41.52 per hour) to
[[Page 44028]]
determine efficiency for each basic model using the AEDM.
---------------------------------------------------------------------------
\34\ DOE estimates that a technician would need 80 hours to
develop an AEDM and 16 hours to validate an AEDM based on testing,
and that the tests of two basic models would be required per AEDM.
At a fully burdened labor rate of $41.52 per hour, the cost to
develop and validate an AEDM would be approximately $4,000 and the
cost to carry out the testing would be between $11,200 and $18,300
for each basic model, depending on the equipment category of models
tested. Therefore, DOE estimates that total AEDM creation costs
would be between $26,400 and $40,600.
---------------------------------------------------------------------------
In accordance with 10 CFR 429.70, manufacturers rating their CUAC
and CUHP models with AEDMs must validate an AEDM with testing of a
minimum of two basic models per validation class (see 10 CFR
429.70(c)(2)(iv)). DOE acknowledges that manufacturers may choose to
test more models than the minimum required by DOE, but DOE has
estimated burden associated with what would be required by its amended
regulations, not including additional testing manufacturers might
choose to undertake at their discretion. Accordingly, in this final
rule, DOE maintains a cost estimate for AEDM development based on
testing test two basic models for each AEDM.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866, 13563, and 14094
Executive Order (``E.O.'') 12866, ``Regulatory Planning and
Review,'' 58 FR 51735 (Oct. 4, 1993), as supplemented and reaffirmed by
E.O. 13563, ``Improving Regulation and Regulatory Review,'' 76 FR 3821
(Jan. 21, 2011), and E.O. 14094, ``Modernizing Regulatory Review,'' 88
FR 21879 (April 11, 2023), requires agencies, to the extent permitted
by law, to: (1) propose or adopt a regulation only upon a reasoned
determination that its benefits justify its costs (recognizing that
some benefits and costs are difficult to quantify); (2) tailor
regulations to impose the least burden on society, consistent with
obtaining regulatory objectives, taking into account, among other
things, and to the extent practicable, the costs of cumulative
regulations; (3) select, in choosing among alternative regulatory
approaches, those approaches that maximize net benefits (including
potential economic, environmental, public health and safety, and other
advantages; distributive impacts; and equity); (4) to the extent
feasible, specify performance objectives, rather than specifying the
behavior or manner of compliance that regulated entities must adopt;
and (5) identify and assess available alternatives to direct
regulation, including providing economic incentives to encourage the
desired behavior, such as user fees or marketable permits, or providing
information upon which choices can be made by the public. DOE
emphasizes as well that E.O. 13563 requires agencies to use the best
available techniques to quantify anticipated present and future
benefits and costs as accurately as possible. In its guidance, the
Office of Information and Regulatory Affairs (``OIRA'') in the Office
of Management and Budget (``OMB'') has emphasized that such techniques
may include identifying changing future compliance costs that might
result from technological innovation or anticipated behavioral changes.
For the reasons stated in the preamble, this final regulatory action is
consistent with these principles.
Section 6(a) of E.O. 12866 also requires agencies to submit
``significant regulatory actions'' to OIRA for review. OIRA has
determined that this final regulatory action does not constitute a
``significant regulatory action'' under section 3(f) of E.O. 12866, as
amended by E.O. 14094. Accordingly, this action was not submitted to
OIRA for review under E.O. 12866.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of an initial regulatory flexibility analysis (``IRFA'')
and a final regulatory flexibility analysis (``FRFA'') for any rule
where the agency was first required by law to publish a proposed rule
for public comment, unless the agency certifies that the rule, if
promulgated, will not have a significant economic impact on a
substantial number of small entities. As required by Executive Order
13272, ``Proper Consideration of Small Entities in Agency Rulemaking,''
67 FR 53461 (August 16, 2002), DOE published procedures and policies in
the Federal Register on February 19, 2003, to ensure that the potential
impacts of its rules on small entities are properly considered during
the DOE rulemaking process. 68 FR 7990. DOE has made its procedures and
policies available on the Office of the General Counsel's website:
www.energy.gov/gc/office-general-counsel. DOE reviewed this final rule
under the provisions of the Regulatory Flexibility Act and the
procedures and policies published on February 19, 2003.
The following sections explain DOE's determination that this final
rule does not have a ``significant economic impact on a substantial
number of small entities,'' and that the preparation of a FRFA is not
warranted.
1. Estimate of Small Entities Regulated
For manufacturers of CUACs and CUHPs, the Small Business
Administration (``SBA'') has set a size threshold, which defines those
entities classified as ``small businesses'' for the purposes of the
statute. DOE used the SBA's small business size standards to determine
whether any small entities would be subject to the requirements of the
rule. See 13 CFR part 121. The equipment covered by this rule is
classified under North American Industry Classification System
(``NAICS'') code 333415,\35\ ``Air-Conditioning and Warm Air Heating
Equipment and Commercial and Industrial Refrigeration Equipment
Manufacturing.'' In 13 CFR 121.201, the SBA sets a threshold of 1,250
employees or fewer for an entity to be considered as a small business
for this category.
---------------------------------------------------------------------------
\35\ The size standards are listed by NAICS code and industry
description and are available at www.sba.gov/document/support--table-size-standards (last accessed April 4, 2023).
---------------------------------------------------------------------------
DOE reviewed the test procedures adopted in this final rule under
the provisions of the Regulatory Flexibility Act and the procedures and
policies published on February 19, 2003. DOE utilized DOE's Compliance
Certification Database (``CCD'') \36\ and manufacturer websites to
identify potential small businesses that manufacture CUACs and CUHPs
covered by this rulemaking. DOE identified 13 companies that are
original equipment manufacturers (``OEMs'') of CUACs and CUHPs covered
by this rulemaking. Next, DOE screened out companies that do not meet
the definition of a ``small business'' or are foreign-owned and
operated. Ultimately, for this final rule DOE identified two small,
domestic OEMs for consideration. DOE's assessment indicates that of
these two OEMs, one is an AHRI member, and one is not an AHRI member
and does not certify their equipment in the AHRI Directory. DOE used
subscription-based business information tools (e.g., reports from Dun &
Bradstreet) \37\ to determine headcount and revenue of each small
business.
---------------------------------------------------------------------------
\36\ Certified equipment in the CCD is listed by equipment class
and can be accessed at www.regulations.doe.gov/certification-data/#q=Product_Group_s%3A* (last accessed Dec. 16, 2023).
\37\ Market research is available through the Dun & Bradstreet
Hoovers login page at: app.dnbhoovers.com (last accessed April 3,
2023).
---------------------------------------------------------------------------
2. Description and Estimate of Compliance Requirements
In this final rule, DOE is revising the existing test procedure for
CUACs and CUHPs (consolidating for ACUACs and ACUHPs, ECUACs, and
WCUACs) at appendix A of subpart F of part 431 (appendix A) by adopting
sections of AHRI 340/360-2022. DOE is also amending the test procedure
for CUACs and CUHPs by adopting a new appendix A1 to subpart F of part
431 (``appendix A1'') that references the industry test
[[Page 44029]]
standard AHRI 1340-2023. Additionally, this final rule amends the
representation and enforcement provisions for CUACs and CUHPs in 10 CFR
part 429 and certain definitions for CUACs and CUHPs in 10 CFR part
431. Specific cost and compliance associated with each appendix are
discussed in the subsections that follow.
a. Cost and Compliance Associated With Appendix A
In appendix A, DOE has amended the existing test procedure for
CUACs and CUHPs (relocated to appendix A for ECUACs and WCUACs, for
which the current test procedure is located at 10 CFR 431.96) by
incorporating by reference an updated version of the applicable
industry test method, AHRI 340/360-2022, which includes the energy
efficiency metrics IEER (required metric for ACUACs and ACUHPs), EER
(required metric for ECUACs, WCUACs, and double-duct systems), and COP
(required metric for ACUHPs and double-duct heat pumps) and maintaining
an existing reference to industry test method ANSI/ASHRAE 37-2009. The
adopted test procedure at appendix A does not change efficiency ratings
as compared to the current Federal test procedure, and, therefore, will
not require retesting nor increase third-party laboratory testing costs
per unit solely as a result of DOE's adoption of this amendment to the
test procedure. DOE estimates the current costs of physical testing to
the current required metrics to be: $10,500 for ACUACs; $12,000 for
ACUHPs; $6,800 for double-duct air conditioners; $8,300 for double-duct
heat pumps; and $6,800 for ECUACs and WCUACs. In accordance with 10 CFR
429.70, CUAC and CUHP manufacturers may elect to use AEDMs to rate
models, an approach which can significantly reduce costs to industry.
b. Cost and Compliance Associated With Appendix A1
In appendix A1, DOE is adopting the test conditions and procedures
in AHRI 1340-2023 and ANSI/ASHRAE 37-2009. The test procedure in
appendix A1 includes provisions for measuring CUAC and CUHP energy
efficiency using the IVEC and IVHE metrics so as to be consistent with
the updated industry test procedure. Should DOE adopt amended energy
conservation standards in the future denominated in terms of IVEC and
IVHE, the Department expects there would be an increase in third-party
laboratory testing cost relative to the current Federal test procedure,
as outlined in further detail in section III.K.2 of this document.
Table IV-1 shows DOE's estimates for testing to the current Federal
test procedure, the initial cost estimate associated with the NOPR, and
this final rule's cost estimate for the adopted test procedure in
appendix A1.
[GRAPHIC] [TIFF OMITTED] TR20MY24.134
If CUAC and CUHP manufacturers conduct physical testing to certify
a basic model, two units are required to be tested per basic model.
However, manufacturers are not required to perform laboratory testing
on all basic models, as manufacturers may elect to use AEDMs, in
accordance with 10 CFR 429.70. An AEDM is a computer modeling or
mathematical tool that predicts the performance of non-tested basic
models. These computer modeling and mathematical tools, when properly
developed, can provide a means to predict the energy usage or
efficiency characteristics of a basic model of a given covered product
or equipment and reduce the burden and cost associated with testing.
Small businesses would be expected to have different potential
regulatory costs depending on whether they are a member of AHRI. DOE
understands that all AHRI members and all manufacturers currently
certifying to the AHRI Directory will be testing their CUAC and CUHP
models in accordance with AHRI 1340-2023, the industry test procedure
DOE is adopting, and using AHRI's certification program.
The adopted test procedure amendments will not add any additional
testing burden to manufacturers which are members of AHRI. As
discussed, DOE identified one small, domestic OEM that is an AHRI
[[Page 44030]]
member. Therefore, DOE has concluded that the adopted test procedure
amendments will not add additional testing burden to one of the two
identified small, domestic OEMs, as that AHRI member company will soon
be using AHRI 1340-2023. DOE estimated the potential impacts for the
one identified small, domestic OEM that is not an AHRI member and does
not certify their equipment in the AHRI Directory. This small business
would only incur additional costs if the company would not otherwise be
using the AHRI 1340-2023 test procedure to rate their models of CUACs
and CUHPs.
DOE estimates that this non-AHRI member company manufactures 14
basic models of ECUACs and WCUACs. To develop cost estimates for this
small business, DOE considered the cost to develop an AEDM, the costs
to validate the AEDM through physical testing, and the cost per model
to determine ratings using the AEDM. DOE anticipates that this small
OEM would avail itself of the cost-saving option which the AEDM
provides. DOE estimated the cost to develop an AEDM for ECUACs or
WCUACs to be $33,600 per AEDM, which includes the required physical
testing of two basic models per validation class. Because ECUACs and
WCUACs are separate validation classes (per 10 CFR 429.70), the
manufacturer would require two AEDMs--one for ECUACs and one for
WCUACs, for a total AEDM development cost of $67,200. Additionally, DOE
estimated a cost of $41.52 per basic model for determining energy
efficiency using the validated AEDM. The estimated cost to rate the 14
basic models with the AEDM would be approximately $600.
Therefore, total testing and rating costs expected for this small
business, when and if DOE adopts amended energy conservation standards
for ECUACs and WCUACs denominated in terms of the IVEC metric, would be
approximately $67,800 for the two AEDMs along with the rating costs for
14 basic models. Market research tools report that company's annual
revenue to be approximately $50.6 million. Accordingly, testing and
AEDM costs to rate in accordance with appendix A1 could cause this
small business manufacturer to incur costs significantly less than one
percent of annual revenue for that small manufacturer.
3. Significant Alternatives to the Rule
DOE considered alternative test methods and modifications to the
adopted test procedures in appendices A and A1 for CUACs and CUHPs,
referencing AHRI 340/360-2022 and AHRI 1340-2023, respectively.
However, DOE has determined that there are no better alternatives than
the adopted test procedures, in terms of both meeting the agency's
objectives and reducing burden on manufacturers. Therefore, DOE is
amending the existing DOE test procedure for CUACs and CUHPs through
incorporation by reference of AHRI 340/360-2022 in appendix A, and
incorporation by reference of AHRI 1340-2023 in appendix A1.
As discussed previously, manufacturers, including small businesses,
will have the option to implement AEDMs to certify their basic models--
which will likely be more cost-effective than testing each basic model.
This option is explained in further detail in section III.K.2 of this
document.
In addition, individual manufacturers may petition for a waiver of
the applicable test procedure. (See 10 CFR 431.401) Also, section 504
of the Department of Energy Organization Act, 42 U.S.C. 7194, provides
authority for the Secretary to adjust a rule issued under EPCA in order
to prevent ``special hardship, inequity, or unfair distribution of
burdens'' that may be imposed on that manufacturer as a result of such
rule. Manufacturers should refer to 10 CFR part 1003 for additional
details.
4. Certification Statement
DOE identified 13 OEMs affected by this final rule, two of which
would be considered small businesses. Of these two small businesses,
one is a member of AHRI, and DOE has determined that the AHRI member
company will already be testing to the updated industry test standard
(i.e., AHRI 1340-2023) in order to certify in the AHRI Directory.
Consequently, DOE does not anticipate its amended test procedure will
add to the testing burden for this AHRI member small business. Finally,
DOE has determined that testing costs and burden will not increase
substantially for the non-AHRI-member small business either. As
discussed previously, the amendments to appendix A will result in zero
costs to that small manufacturer. Further, the new appendix A1 will
have no cost impact until and if amended energy conservation standards
denominated in terms of the new metrics IVEC and IVHE are adopted. DOE
has determined that if energy conservation standards are amended, the
potential cost associated with this final rule is significantly less
than one percent of revenue for the one non-AHRI-member small business.
Thus, DOE concludes that this rulemaking does not significantly affect
a substantial number of small entities.
Based on the limited number of small entities affected and the de
minimis cost impacts, DOE certifies that this final rule does not have
a ``significant economic impact on a substantial number of small
entities,'' and accordingly, the Department has determined that the
preparation of a FRFA is not warranted. DOE will transmit a
certification and supporting statement of factual basis to the Chief
Counsel for Advocacy of the Small Business Administration for review
under 5 U.S.C. 605(b).
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of CUACs and CUHPs must certify to DOE that their
equipment complies with any applicable energy conservation standards.
To certify compliance, manufacturers must first obtain test data for
their equipment according to the DOE test procedures, including any
amendments adopted for those test procedures. DOE has established
regulations for the certification and recordkeeping requirements for
all covered consumer products and commercial equipment, including CUACs
and CUHPs. (See generally 10 CFR part 429.) The collection-of-
information requirement for the certification and recordkeeping is
subject to review and approval by OMB under the Paperwork Reduction Act
(PRA). This requirement has been approved by OMB under OMB control
number 1910-1400. Public reporting burden for the certification is
estimated to average 35 hours per response, including the time for
reviewing instructions, searching existing data sources, gathering and
maintaining the data needed, and completing and reviewing the
collection of information.
DOE is not amending the certification or reporting requirements for
CUACs and CUHPs in this final rule. Instead, DOE may consider proposals
to amend the certification requirements and reporting for CUACs and
CUHPs under a separate rulemaking regarding appliance and equipment
certification. DOE will address changes to OMB Control Number 1910-1400
at that time, as necessary.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
[[Page 44031]]
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE adopts test procedure amendments that it
expects will be used to develop and implement future energy
conservation standards for CUACs and CUHPs. DOE has determined that
this rule falls into a class of actions that are categorically excluded
from review under the National Environmental Policy Act of 1969 (42
U.S.C. 4321 et seq.) and DOE's implementing regulations at 10 CFR part
1021. Specifically, DOE has determined that adopting test procedures
for measuring energy efficiency of consumer products and industrial
equipment is consistent with activities identified in 10 CFR part 1021,
subpart D, appendix A, sections A5 and A6. Accordingly, neither an
environmental assessment nor an environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 4,
1999), imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have federalism implications. The Executive order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE examined this final
rule and determined that it will not have a substantial direct effect
on the States, on the relationship between the national government and
the States, or on the distribution of power and responsibilities among
the various levels of government. EPCA governs and prescribes Federal
preemption of State regulations as to energy conservation for the
products that are the subject of this final rule. States can petition
DOE for exemption from such preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Regarding the review required by section 3(a),
section 3(b) of Executive Order 12988 specifically requires that
Executive agencies make every reasonable effort to ensure that the
regulation: (1) clearly specifies the preemptive effect, if any; (2)
clearly specifies any effect on existing Federal law or regulation; (3)
provides a clear legal standard for affected conduct while promoting
simplification and burden reduction; (4) specifies the retroactive
effect, if any; (5) adequately defines key terms; and (6) addresses
other important issues affecting clarity and general draftsmanship
under any guidelines issued by the Attorney General. Section 3(c) of
Executive Order 12988 sections 3(a) and 3(b) to determine whether they
are met or it is unreasonable to meet one or more of them. DOE has
completed the required review and determined that, to the extent
permitted by law, this final rule meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (``UMRA'')
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a regulatory action likely to result in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect them. On March 18, 1997, DOE published
a statement of policy on its process for intergovernmental consultation
under UMRA. 62 FR 12820. DOE's policy statement is also available at
www.energy.gov/sites/prod/files/gcprod/documents/umra_97.pdf. DOE
examined this final rule according to UMRA and its statement of policy
and determined that the rule contains neither an intergovernmental
mandate, nor a mandate that may result in the expenditure of $100
million or more in any year, so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This final rule will not have any impact on the autonomy or integrity
of the family as an institution. Accordingly, DOE has concluded that it
is not necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights,'' 53 FR 8859 (March 18, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). Pursuant
to OMB Memorandum M-19-15, Improving Implementation of the Information
Quality Act (April 24, 2019), DOE published updated guidelines which
are available at: www.energy.gov/sites/prod/files/2019/12/f70/DOE%20Final%20Updated%20IQA%20Guidelines%20Dec%202019.pdf. DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
[[Page 44032]]
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OIRA
at OMB, a Statement of Energy Effects for any significant energy
action. A ``significant energy action'' is defined as any action by an
agency that promulgates or is expected to lead to promulgation of a
final rule, and that: (1) is a significant regulatory action under
Executive Order 12866, or any successor order, and (2) is likely to
have a significant adverse effect on the supply, distribution, or use
of energy, or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use if the regulation is implemented, and of
reasonable alternatives to the action and their expected benefits on
energy supply, distribution, and use.
This regulatory action to amend the test procedure for measuring
the energy efficiency of CUACs and CUHPs is not a significant
regulatory action under Executive Order 12866. Moreover, it would not
have a significant adverse effect on the supply, distribution, or use
of energy, nor has it been designated as a significant energy action by
the Administrator of OIRA. Therefore, it is not a significant energy
action, and, accordingly, DOE has not prepared a Statement of Energy
Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788;
``FEAA'') Section 32 essentially provides in relevant part that, where
a proposed rule authorizes or requires use of commercial standards, the
notice of proposed rulemaking must inform the public of the use and
background of such standards. In addition, section 32(c) requires DOE
to consult with the Attorney General and the Chairman of the Federal
Trade Commission (``FTC'') concerning the impact of the commercial or
industry standards on competition.
The modifications to the test procedure for CUACs and CUHPs adopted
in this final rule incorporate testing methods contained in certain
sections of the following commercial standards: AHRI 340/360-2022, AHRI
1340-2023, and ANSI/ASHRAE 37-2009. DOE has evaluated these standards
and is unable to conclude whether they fully comply with the
requirements of section 32(b) of the FEAA (i.e., whether they were
developed in a manner that fully provides for public participation,
comment, and review). DOE has consulted with both the Attorney General
and the Chairman of the FTC about the impact on competition of using
the methods contained in these standards and has received no comments
objecting to their use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that the Office of Information and Regulatory Affairs has
determined that this action is not a ``major rule'' under the criteria
set forth in 5 U.S.C. 804(2).
N. Description of Materials Incorporated by Reference
In this final rule, DOE is incorporating by reference the following
test standards:
AHRI 340/360-2022 is an industry-accepted test procedure for
measuring the performance of air-cooled, evaporatively-cooled, and
water-cooled unitary air-conditioning and heat pump equipment. AHRI
340/360-2022 is available from AHRI at www.ahrinet.org/standards/search-standards.
AHRI 1340-2023 is the most recent industry-accepted test procedure
for measuring the performance of air-cooled, evaporatively-cooled, and
water-cooled unitary air-conditioning and heat pump equipment. AHRI
1340-2023 is available from AHRI at www.ahrinet.org/standards/search-standards.
ANSI/ASHRAE 37-2009 is an industry-accepted test procedure for
measuring the performance of electrically driven unitary air-
conditioning and heat pump equipment. ANSI/ASHRAE 37-2009 is available
from ASHRAE on ANSI's website at: https://webstore.ansi.org/standards/ashrae/ansiashraestandard372009.
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Reporting and
recordkeeping requirements, Small businesses.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation test procedures, Incorporation by
reference, Reporting and recordkeeping requirements.
Signing Authority
This document of the Department of Energy was signed on April 12,
2024, by Jeffrey Marootian, Principal Deputy Assistant Secretary for
Energy Efficiency and Renewable Energy, pursuant to delegated authority
from the Secretary of Energy. That document with the original signature
and date is maintained by DOE. For administrative purposes only, and in
compliance with requirements of the Office of the Federal Register, the
undersigned DOE Federal Register Liaison Officer has been authorized to
sign and submit the document in electronic format for publication, as
an official document of the Department of Energy. This administrative
process in no way alters the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on April 17, 2024.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
For the reasons stated in the preamble, DOE amends parts 429 and
431 of chapter II of title 10, Code of Federal Regulations as set forth
below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
2. Amend Sec. 429.4 by:
0
a. Removing paragraph (c)(2);
0
b. Redesignating paragraphs (c)(3) through (5) as paragraphs (c)(2)
through (4); and
0
c. Adding new paragraph (c)(5).
The addition reads as follows:
Sec. 429.4 Materials incorporated by reference.
* * * * *
(c) * * *
(5) AHRI Standard 1340-2023 (I-P) (``AHRI 1340-2023''), 2023
Standard for
[[Page 44033]]
Performance Rating of Commercial and Industrial Unitary Air-
conditioning and Heat Pump Equipment, approved November 16, 2023; IBR
approved for Sec. Sec. 429.43; 429.134.
* * * * *
0
3. Amend Sec. 429.43 by:
0
a. Removing paragraph (a)(1)(iv);
0
b. Removing and reserving paragraph (a)(2)(ii); and
0
c. Adding paragraph (a)(3)(vi).
The addition reads as follows:
Sec. 429.43 Commercial heating, ventilating, air conditioning (HVAC)
equipment (excluding air-cooled, three-phase, small commercial package
air conditioning and heating equipment with a cooling capacity of less
than 65,000 British thermal units per hour and air-cooled, three-phase,
variable refrigerant flow multi-split air conditioners and heat pumps
with less than 65,000 British thermal units per hour cooling capacity).
(a) * * *
(3) * * *
(vi) Commercial package air conditioning and heating equipment
(excluding air-cooled equipment with a cooling capacity less than
65,000 Btu/h). Before May 15, 2025, the provisions in 10 CFR 429.43,
revised as of January 1, 2024, are applicable. On and after May 15,
2025, when certifying to energy conservation standards in terms of EER
or IEER and (as applicable) COP, the provisions in paragraph
(a)(3)(vi)(B) of this section apply. When certifying to energy
conservation standards in terms of IVEC and (as applicable) IVHE, all
provisions in this paragraph (a)(3)(vi) apply.
(A) For individual model selection when certifying to energy
conservation standards in terms of IVEC and (as applicable) IVHE:
(1) Representations for a basic model must be based on the least-
efficient individual model(s) distributed in commerce among all
otherwise comparable model groups comprising the basic model, with
selection of the least-efficient individual model considering all
options for factory-installed components and manufacturer-supplied
components for field installation, except as provided in paragraph
(a)(3)(vi)(A)(2) of this section for individual models that include
components listed in table 7 to paragraph (a)(3)(vi)(A) of this
section. For the purpose of this paragraph (a)(3)(vi)(A)(1),
``otherwise comparable model group'' means a group of individual models
distributed in commerce within the basic model that do not differ in
components that affect energy consumption as measured according to the
applicable test procedure specified at 10 CFR 431.96 other than those
listed in table 7 to paragraph (a)(3)(vi)(A) of this section. An
otherwise comparable model group may include individual models
distributed in commerce with any combination of the components listed
in table 7 (or none of the components listed in table 7). An otherwise
comparable model group may consist of only one individual model.
(2) For a basic model that includes individual models distributed
in commerce with components listed in table 7 to paragraph
(a)(3)(vi)(A) of this section, the requirements for determining
representations apply only to the individual model(s) of a specific
otherwise comparable model group distributed in commerce with the least
number (which could be zero) of components listed in table 7 to
paragraph (a)(3)(vi)(A) included in individual models of the group.
Testing under this paragraph (a)(3)(vi)(A)(2) shall be consistent with
any component-specific test provisions specified in section 6 of
appendix A1 to subpart F of 10 CFR part 431.
Table 7 to Paragraph (a)(3)(vi)(A)--Specific Components for Commercial Package Air Conditioning and Heating
Equipment
[Excluding air-cooled equipment with a cooling capacity of less than 65,000 Btu/h]
----------------------------------------------------------------------------------------------------------------
Component Description
----------------------------------------------------------------------------------------------------------------
Air Economizers............................. An automatic system that enables a cooling system to supply
outdoor air to reduce or eliminate the need for mechanical
cooling during mild or cold weather.
Desiccant Dehumidification Components....... An assembly that reduces the moisture content of the supply air
through moisture transfer with solid or liquid desiccants.
Evaporative Pre-cooling of Air-cooled Water is evaporated into the air entering the air-cooled condenser
Condenser Intake Air. to lower the dry-bulb temperature and thereby increase efficiency
of the refrigeration cycle.
Fire/Smoke/Isolation Dampers................ A damper assembly including means to open and close the damper
mounted at the supply or return duct opening of the equipment.
Indirect/Direct Evaporative Cooling of Water is used indirectly or directly to cool ventilation air. In a
Ventilation Air. direct system, the water is introduced directly into the
ventilation air, and in an indirect system, the water is
evaporated in secondary air stream, and the heat is removed
through a heat exchanger.
Non-Standard Ducted Condenser Fans (not A higher-static condenser fan/motor assembly designed for external
applicable to Double-duct Systems). ducting of condenser air that provides greater pressure rise and
has a higher rated motor horsepower than the condenser fan
provided as a standard component with the equipment.
Non-Standard High-Static Indoor Fan Motors.. The standard indoor fan motor is the motor specified in the
manufacturer's installation instructions for testing and shall be
distributed in commerce as part of a particular model. A non-
standard motor is an indoor fan motor that is not the standard
indoor fan motor and that is distributed in commerce as part of
an individual model within the same basic model.
For a non-standard high-static indoor fan motor(s) to be
considered a specific component for a basic model (and thus
subject to the provisions of paragraph (a)(3)(vi)(A)(2) of this
section), the following provisions must be met:
(1) Non-standard high-static indoor fan motor(s) must meet the
minimum allowable efficiency determined per section D.3.1 of
AHRI 1340-2023 (incorporated by reference, see Sec. 429.4)
for non-standard high-static indoor fan motors or per section
D.3.2 of AHRI 1340-2023 for non-standard high-static indoor
integrated fan and motor combinations.
(2) If the standard indoor fan motor can vary fan speed through
control system adjustment of motor speed, all non-standard
high-static indoor fan motors must also allow speed control
(including with the use of variable-frequency drive).
Powered Exhaust/Powered Return Air Fans..... A powered exhaust fan is a fan that transfers directly to the
outside a portion of the building air that is returning to the
unit, rather than allowing it to recirculate to the indoor coil
and back to the building. A powered return fan is a fan that
draws building air into the equipment.
[[Page 44034]]
Process Heat recovery/Reclaim Coils/Thermal A heat exchanger located inside the unit that conditions the
Storage. equipment's supply air using energy transferred from an external
source using a vapor, gas, or liquid.
Refrigerant Reheat Coils.................... A heat exchanger located downstream of the indoor coil that heats
the supply air during cooling operation using high pressure
refrigerant in order to increase the ratio of moisture removal to
cooling capacity provided by the equipment.
Sound Traps/Sound Attenuators............... An assembly of structures through which the supply air passes
before leaving the equipment or through which the return air from
the building passes immediately after entering the equipment for
which the sound insertion loss is at least 6 dB for the 125 Hz
octave band frequency range.
Steam/Hydronic Heat Coils................... Coils used to provide supplemental heating.
Ventilation Energy Recovery System (VERS)... An assembly that preconditions outdoor air entering the equipment
through direct or indirect thermal and/or moisture exchange with
the exhaust air, which is defined as the building air being
exhausted to the outside from the equipment.
----------------------------------------------------------------------------------------------------------------
(B) The represented value of total cooling capacity must be between
95 percent and 100 percent of the mean of the total cooling capacities
measured for the units in the sample selected as described in paragraph
(a)(1)(ii) of this section, or between 95 percent and 100 percent of
the total cooling capacity output simulated by the AEDM as described in
paragraph (a)(2) of this section.
(C) Representations of IVEC and IVHE (including IVHEc,
as applicable) must be determined using a minimum part-load airflow
that is no lower than the highest of the following:
(1) The minimum part-load airflow obtained using the as-shipped
system control settings;
(2) The minimum part-load airflow obtained using the default system
control settings specified in the manufacturer installation
instructions (as applicable); and
(3) The minimum airflow rate specified in section 5.18.2 of AHRI
1340-2023.
* * * * *
0
4. Amend Sec. 429.70 by revising table 2 to paragraph (c)(5)(vi)(B) to
read as follows:
Sec. 429.70 Alternative methods for determining energy efficiency and
energy use.
* * * * *
(c) * * *
(5) * * *
(vi) * * *
(B) * * *
Table 2 to Paragraph (c)(5)(vi)(B)
------------------------------------------------------------------------
Applicable
Equipment Metric tolerance
------------------------------------------------------------------------
Commercial Packaged Boilers.... Combustion Efficiency.. 5% (0.05)
Thermal Efficiency..... 5% (0.05)
Commercial Water Heaters or Hot Thermal Efficiency..... 5% (0.05)
Water Supply Boilers.
Standby Loss........... 10% (0.1)
Unfired Storage Tanks.......... R-Value................ 10% (0.1)
Air-Cooled, Split and Packaged Energy Efficiency Ratio 5% (0.05)
ACs and HPs Greater Than or Energy Efficiency Ratio 5% (0.05)
Equal to 65,000 Btu/h Cooling 2. 5% (0.05)
Capacity and Less than 760,000 Coefficient of 5% (0.05)
Btu/h Cooling Capacity. Performance. 10% (0.1)
Coefficient of 10% (0.1)
Performance 2. 10% (0.1)
Integrated Energy
Efficiency Ratio.
Integrated Ventilation,
Economizing, and
Cooling.
Integrated Ventilation
and Heating Efficiency.
Water-Cooled, Split and Energy Efficiency Ratio 5% (0.05)
Packaged ACs, All Cooling Energy Efficiency Ratio 5% (0.05)
Capacities. 2. 10% (0.1)
Integrated Energy 10% (0.1)
Efficiency Ratio.
Integrated Ventilation,
Economizing, and
Cooling.
Evaporatively-Cooled, Split and Energy Efficiency Ratio 5% (0.05)
Packaged ACs, All Capacities. Energy Efficiency Ratio 5% (0.05)
2. 10% (0.1)
Integrated Energy 10% (0.1)
Efficiency Ratio.
Integrated Ventilation,
Economizing, and
Cooling.
Water-Source HPs, All Energy Efficiency Ratio 5% (0.05)
Capacities.
Coefficient of 5% (0.05)
Performance.
Integrated Energy 10% (0.1)
Efficiency Ratio.
Single Package Vertical ACs and Energy Efficiency Ratio 5% (0.05)
HPs.
Coefficient of 5% (0.05)
Performance.
Packaged Terminal ACs and HPs.. Energy Efficiency Ratio 5% (0.05)
Coefficient of 5% (0.05)
Performance.
Variable Refrigerant Flow ACs Energy Efficiency Ratio 5% (0.05)
and HPs (Excluding Air-Cooled, Coefficient of 5% (0.05)
Three-phase with Less Than Performance. 10% (0.1)
65,000 Btu/h Cooling Capacity). Integrated Energy
Efficiency Ratio.
Computer Room Air Conditioners. Sensible Coefficient of 5% (0.05)
Performance.
Direct Expansion- Dedicated Integrated Seasonal 10% (0.1)
Outdoor Air Systems. Coefficient of 10% (0.1)
Performance 2.
Integrated Seasonal
Moisture Removal
Efficiency 2.
[[Page 44035]]
Commercial Warm-Air Furnaces... Thermal Efficiency..... 5% (0.05)
Commercial Refrigeration Daily Energy 5% (0.05)
Equipment. Consumption.
------------------------------------------------------------------------
* * * * *
0
5. Amend Sec. 429.134 by revising paragraph (g) to read as follows:
Sec. 429.134 Product-specific enforcement provisions.
* * * * *
(g) Commercial package air conditioning and heating equipment
(excluding air-cooled equipment with a cooling capacity less than
65,000 Btu/h). Before May 15, 2025, the provisions in 10 CFR 429.134,
revised as of January 1, 2024, are applicable. On and after May 15,
2025, the following provisions apply.
(1) Verification of cooling capacity. The cooling capacity of each
tested unit of the basic model will be measured pursuant to the test
requirements of appendix A or appendix A1 to subpart F of part 431. The
mean of the cooling capacity measurement(s) will be used to determine
the applicable standards for purposes of compliance.
(2) Specific components. For assessment and enforcement testing of
models subject to energy conservation standards denominated in terms of
IVEC and IVHE, if a basic model includes individual models with
components listed at table 7 to Sec. 429.43(a)(3)(vi)(A) and DOE is
not able to obtain an individual model with the least number (which
could be zero) of those components within an otherwise comparable model
group (as defined in Sec. 429.43(a)(3)(vi)(A)(1)), DOE may test any
individual model within the otherwise comparable model group.
(3) Verification of cut-out and cut-in temperatures. For assessment
and enforcement testing of models of commercial package air
conditioning and heating equipment subject to energy conservation
standards denominated in terms of IVHE, the cut-out and cut-in
temperatures may be verified using the method in appendix H to AHRI
1340-2023 (incorporated by reference, see Sec. 429.4). If this method
is conducted, the cut-in and cut-out temperatures determined using this
method will be used to calculate IVHE for purposes of compliance.
* * * * *
PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
6. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
7. Amend Sec. 431.92 by:
0
a. Revising the definitions for ``Basic model'' and ``Coefficient of
performance, or COP'';
0
b. Adding in alphabetical order a definition for ``Coefficient of
performance 2, or COP2'';
0
c. Revising the definitions for ``Double-duct air conditioner or heat
pump'' and ``Energy efficiency ratio, or EER'';
0
d. Adding in alphabetical order a definition for ``Energy efficiency
ratio 2, or EER2'';
0
e. Revising the definition for ``Integrated energy efficiency ratio, or
IEER''; and
0
f. Adding in alphabetical order definitions for ``Integrated
ventilation and heating efficiency, or IVHE'' and ``Integrated
ventilation, economizing, and cooling, or IVEC''.
The revisions and additions read as follows:
Sec. 431.92 Definitions concerning commercial air conditioners and
heat pumps.
* * * * *
Basic model means:
(1) For air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less than
65,000 Btu/h and air-cooled, three-phase, variable refrigerant flow
multi-split air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h. All units manufactured by one manufacturer,
having the same primary energy source, and, which have essentially
identical electrical, physical, and functional (or hydraulic)
characteristics that affect energy consumption, energy efficiency,
water consumption, or water efficiency; where essentially identical
electrical, physical, and functional (or hydraulic) characteristics
means:
(i) For split systems manufactured by outdoor unit manufacturers
(OUMs): all individual combinations having the same model of outdoor
unit, which means comparably performing compressor(s) [a variation of
no more than five percent in displacement rate (volume per time) as
rated by the compressor manufacturer, and no more than five percent in
capacity and power input for the same operating conditions as rated by
the compressor manufacturer], outdoor coil(s) [no more than five
percent variation in face area and total fin surface area; same fin
material; same tube material], and outdoor fan(s) [no more than ten
percent variation in airflow and no more than twenty percent variation
in power input];
(ii) For split systems having indoor units manufactured by
independent coil manufacturers (ICMs): all individual combinations
having comparably performing indoor coil(s) [plus or minus one square
foot face area, plus or minus one fin per inch fin density, and the
same fin material, tube material, number of tube rows, tube pattern,
and tube size]; and
(iii) For single-package systems: all individual models having
comparably performing compressor(s) [no more than five percent
variation in displacement rate (volume per time) rated by the
compressor manufacturer, and no more than five percent variations in
capacity and power input rated by the compressor manufacturer
corresponding to the same compressor rating conditions], outdoor
coil(s) and indoor coil(s) [no more than five percent variation in face
area and total fin surface area; same fin material; same tube
material], outdoor fan(s) [no more than ten percent variation in
outdoor airflow], and indoor blower(s) [no more than ten percent
variation in indoor airflow, with no more than twenty percent variation
in fan motor power input];
(iv) Except that:
(A) For single-package systems and single-split systems,
manufacturers may instead choose to make each individual model/
combination its own basic model provided the testing and represented
value requirements in 10 CFR 429.67 are met; and
(B) For multi-split, multi-circuit, and multi-head mini-split
combinations, a basic model may not include both
[[Page 44036]]
individual small-duct, high velocity (SDHV) combinations and non-SDHV
combinations even when they include the same model of outdoor unit. The
manufacturer may choose to identify specific individual combinations as
additional basic models.
(2) For commercial package air conditioning and heating equipment
(excluding air-cooled, three-phase, commercial package air conditioning
and heating equipment with a cooling capacity of less than 65,000 Btu/
h). All units manufactured by one manufacturer within a single
equipment class, having the same or comparably performing
compressor(s), heat exchangers, and air moving system(s) that have a
common ``nominal'' cooling capacity.
(3) For computer room air conditioners. All units manufactured by
one manufacturer within a single equipment class, having the same
primary energy source (e.g., electric or gas), and which have the same
or comparably performing compressor(s), heat exchangers, and air moving
system(s) that have a common ``nominal'' cooling capacity.
(4) For direct expansion-dedicated outdoor air system. All units
manufactured by one manufacturer, having the same primary energy source
(e.g., electric or gas), within a single equipment class; with the same
or comparably performing compressor(s), heat exchangers, ventilation
energy recovery system(s) (if present), and air moving system(s) that
have a common ``nominal'' moisture removal capacity.
(5) For packaged terminal air conditioner (PTAC) or packaged
terminal heat pump (PTHP). All units manufactured by one manufacturer
within a single equipment class, having the same primary energy source
(e.g., electric or gas), and which have the same or comparable
compressors, same or comparable heat exchangers, and same or comparable
air moving systems that have a cooling capacity within 300 Btu/h of one
another.
(6) For single package vertical units. All units manufactured by
one manufacturer within a single equipment class, having the same
primary energy source (e.g., electric or gas), and which have the same
or comparably performing compressor(s), heat exchangers, and air moving
system(s) that have a rated cooling capacity within 1500 Btu/h of one
another.
(7) For variable refrigerant flow systems (excluding air-cooled,
three-phase, variable refrigerant flow air conditioners and heat pumps
with a cooling capacity of less than 65,000 Btu/h). All units
manufactured by one manufacturer within a single equipment class,
having the same primary energy source (e.g., electric or gas), and
which have the same or comparably performing compressor(s) that have a
common ``nominal'' cooling capacity and the same heat rejection medium
(e.g., air or water) (includes VRF water source heat pumps).
(8) For water-source heat pumps. All units manufactured by one
manufacturer within a single equipment class, having the same primary
energy source (e.g., electric or gas), and which have the same or
comparable compressors, same or comparable heat exchangers, and same or
comparable ``nominal'' cooling capacity.
* * * * *
Coefficient of performance, or COP, means the ratio of the produced
cooling effect of an air conditioner or heat pump (or its produced
heating effect, depending on the mode of operation) to its net work
input, when both the cooling (or heating) effect and the net work input
are expressed in identical units of measurement. For air-cooled
commercial package air conditioning and heating equipment (excluding
equipment with a cooling capacity less than 65,000 Btu/h), COP is
measured per appendix A to this subpart.
Coefficient of performance 2, or COP2, means the ratio of the
produced cooling effect of an air conditioner or heat pump (or its
produced heating effect, depending on the mode of operation) to its net
work input, when both the cooling (or heating) effect and the net work
input are expressed in identical units of measurement. COP2 must be
used with a subscript to indicate the outdoor temperature in degrees
Fahrenheit at which the COP2 was measured (e.g., COP217 for
COP2 measured at 17 [deg]F). For air-cooled commercial package air
conditioning and heating equipment (excluding equipment with a cooling
capacity less than 65,000 Btu/h), COP2 is measured per appendix A1 to
this subpart.
* * * * *
Double-duct air conditioner or heat pump means air-cooled
commercial package air conditioning and heating equipment that meets
the following criteria--
(1) Is either a horizontal single package or split-system unit; or
a vertical unit that consists of two components that may be shipped or
installed either connected or split; or a vertical single package unit
that is not intended for exterior mounting on, adjacent interior to, or
through an outside wall;
(2) Is intended for indoor installation with ducting of outdoor air
from the building exterior to and from the unit (e.g., the unit and/or
all of its components are non-weatherized);
(3) If it is a horizontal unit, the complete unit shall have a
maximum height of 35 inches or the unit shall have components that do
not exceed a maximum height of 35 inches. If it is a vertical unit, the
complete (split, connected, or assembled) unit shall have components
that do not exceed a maximum depth of 35 inches; and
(4) Has a rated cooling capacity greater than or equal to 65,000
Btu/h and less than 300,000 Btu/h.
* * * * *
Energy efficiency ratio, or EER, means the ratio of the produced
cooling effect of an air conditioner or heat pump to its net work
input, expressed in Btu/watt-hour. For commercial package air
conditioning and heating equipment (excluding air-cooled equipment with
a cooling capacity less than 65,000 Btu/h), EER is measured per
appendix A to this subpart.
Energy efficiency ratio 2, or EER2, means the ratio of the produced
cooling effect of an air conditioner or heat pump to its net work
input, expressed in Btu/watt-hour. For commercial package air
conditioning and heating equipment (excluding air-cooled equipment with
a cooling capacity less than 65,000 Btu/h), EER2 is measured per
appendix A1 to this subpart.
* * * * *
Integrated energy efficiency ratio, or IEER, means a weighted
average calculation of mechanical cooling EERs determined for four load
levels and corresponding rating conditions, expressed in Btu/watt-hour.
IEER is measured:
(1) Per appendix A to this subpart for commercial package air
conditioning and heating equipment (excluding air-cooled equipment with
a cooling capacity less than 65,000 Btu/h);
(2) Per appendix C1 to this subpart for water-source heat pumps;
(3) Per appendix D1 to this subpart for variable refrigerant flow
multi-split air conditioners and heat pumps (other than air-cooled with
rated cooling capacity less than 65,000 Btu/h); and
(4) Per appendix G1 to this subpart for single package vertical air
conditioners and single package vertical heat pumps.
* * * * *
Integrated ventilation and heating efficiency, or IVHE, means a sum
of the space heating provided (Btu) divided by the sum of the energy
consumed (Wh), including mechanical heating, supplementary electric
resistance
[[Page 44037]]
heating, and heating season ventilation operating modes. IVHE with
subscript C (IVHEC) refers to the IVHE of heat pumps using a
cold-climate heating load line. For air-cooled commercial package air
conditioning and heating equipment (excluding equipment with a cooling
capacity less than 65,000 Btu/h), IVHE and IVHEC are
measured per appendix A1 to this subpart.
Integrated ventilation, economizing, and cooling, or IVEC, means a
sum of the space cooling provided (Btu) divided by the sum of the
energy consumed (Wh), including mechanical cooling, economizing, and
cooling season ventilation operating modes. For commercial package air
conditioning and heating equipment (excluding air-cooled equipment with
a cooling capacity less than 65,000 Btu/h), IVEC is measured per
appendix A1 to this subpart.
* * * * *
0
8. Amend Sec. 431.95 by:
0
a. Revising paragraph (b)(4);
0
b. Redesignating paragraph (b)(11) as paragraph (b)(12);
0
c. Adding new paragraph (b)(11); and
0
d. Revising paragraph (c)(2).
The revision and addition read as follows:
Sec. 431.95 Materials incorporated by reference.
* * * * *
(b) * * *
(4) AHRI Standard 340/360-2022 (I-P) (``AHRI 340/360-2022''), 2022
Standard for Performance Rating of Commercial and Industrial Unitary
Air-conditioning and Heat Pump Equipment, approved January 26, 2022;
IBR approved for appendix A to this subpart.
* * * * *
(11) AHRI Standard 1340-2023 (I-P) (``AHRI 1340-2023''), 2023
Standard for Performance Rating of Commercial and Industrial Unitary
Air-conditioning and Heat Pump Equipment, approved November 16, 2023;
IBR approved for appendix A1 to this subpart.
* * * * *
(c) * * *
(2) ANSI/ASHRAE Standard 37-2009 (``ANSI/ASHRAE 37-2009''), Methods
of Testing for Rating Electrically Driven Unitary Air-Conditioning and
Heat Pump Equipment, approved June 24, 2009; IBR approved for Sec.
431.96 and appendices A, A1, B, C1, D1, E1, F1, G, and G1 to this
subpart.
* * * * *
0
9. Amend Sec. 431.96 by revising table 1 to paragraph (b) to read as
follows:
Sec. 431.96 Uniform test method for the measurement of energy
efficiency of commercial air conditioners and heat pumps.
* * * * *
(b) * * *
Table 1 to Paragraph (b)--Test Procedures for Commercial Air Conditioners and Heat Pumps
--------------------------------------------------------------------------------------------------------------------------------------------------------
Additional test
Cooling capacity or Use tests, procedure provisions
Equipment Category moisture removal Energy efficiency conditions, an as indicated in the
capacity \1\ descriptor procedures in listed paragraphs of
this section
--------------------------------------------------------------------------------------------------------------------------------------------------------
Commercial Package Air Conditioning Air-Cooled, 3-Phase, <65,000 Btu/h......... SEER and HSPF........ Appendix F to this None.
and Heating Equipment. AC and HP. subpart \2\.
Commercial Package Air Conditioning Air-Cooled, 3-Phase, <65,000 Btu/h......... SEER2 and HSPF2...... Appendix F1 to this None.
and Heating Equipment. AC and HP. subpart \2\.
Commercial Package Air Conditioning Air-Cooled AC and HP >=65,000 Btu/h and EER, IEER, and COP... Appendix A to this None.
and Heating Equipment. (excluding double- <760,000 Btu/h. subpart \2\.
duct AC and HP).
Commercial Package Air Conditioning Air-Cooled AC and HP >=65,000 Btu/h and EER2, COP2, IVEC, and Appendix A1 to this None.
and Heating Equipment. (excluding double- <760,000 Btu/h. IVHE. subpart \2\.
duct AC and HP).
Commercial Package Air Conditioning Double-duct AC and HP. >=65,000 Btu/h and EER, IEER, and COP... Appendix A to this None.
and Heating Equipment. <300,000 Btu/h. subpart \2\.
Commercial Package Air Conditioning Double-duct AC and HP. >=65,000 Btu/h and EER2, COP2, IVEC, and Appendix A1 to this None.
and Heating Equipment. <300,000 Btu/h. IVHE. subpart \2\.
Commercial Package Air Conditioning Water-Cooled and <760,000 Btu/h........ EER and IEER......... Appendix A to this None.
and Heating Equipment. Evaporatively-Cooled subpart \2\.
AC.
Commercial Package Air Conditioning Water-Cooled and <760,000 Btu/h........ EER2 and IVEC........ Appendix A1 to this None.
and Heating Equipment. Evaporatively-Cooled subpart \2\.
AC.
Water-Source Heat Pumps............ HP.................... <760,000 Btu/h........ EER and COP.......... Appendix C to this None.
subpart \2\.
Water-Source Heat Pumps............ HP.................... <760,000 Btu/h........ IEER and ACOP........ Appendix C1 to this None.
subpart \2\.
Packaged Terminal Air Conditioners AC and HP............. <760,000 Btu/h........ EER and COP.......... Paragraph (g) of this Paragraphs (c), (e),
and Heat Pumps. section. and (g).
Computer Room Air Conditioners..... AC.................... <760,000 Btu/h........ SCOP................. Appendix E to this None.
subpart \2\.
Computer Room Air Conditioners..... AC.................... <760,000 Btu/h or NSenCOP.............. Appendix E1 to this None.
<930,000 Btu/h \3\. subpart \2\.
Variable Refrigerant Flow Multi- AC.................... <65,000 Btu/h (3- SEER................. Appendix F to this None.
split Systems. phase). subpart \2\.
Variable Refrigerant Flow Multi- AC.................... <65,000 Btu/h (3- SEER2................ Appendix F1 to this None.
split Systems. phase). subpart \2\.
Variable Refrigerant Flow Multi- HP.................... <65,000 Btu/h (3- SEER and HSPF........ Appendix F to this None.
split Systems, Air-cooled. phase). subpart \2\.
Variable Refrigerant Flow Multi- HP.................... <65,000 Btu/h (3- SEER2 and HSPF2...... Appendix F1 to this None.
split Systems, Air-cooled. phase). subpart \2\.
[[Page 44038]]
Variable Refrigerant Flow Multi- AC and HP............. >=65,000 Btu/h and EER and COP.......... Appendix D to this None.
split Systems, Air-cooled. <760,000 Btu/h. subpart \2\.
Variable Refrigerant Flow Multi- AC and HP............. >=65,000 Btu/h and IEER and COP......... Appendix D1 to this None.
split Systems, Air-cooled. <760,000 Btu/h. subpart \2\.
Variable Refrigerant Flow Multi- HP.................... <760,000 Btu/h........ EER and COP.......... Appendix D to this None.
split Systems, Water-source. subpart \2\.
Variable Refrigerant Flow Multi- HP.................... <760,000 Btu/h........ IEER and COP......... Appendix D1 to this None.
split Systems, Water-source. subpart \2\.
Single Package Vertical Air AC and HP............. <760,000 Btu/h........ EER and COP.......... Appendix G to this None.
Conditioners and Single Package subpart \2\.
Vertical Heat Pumps.
Single Package Vertical Air AC and HP............. <760,000 Btu/h........ EER, IEER, and COP... Appendix G1 to this None.
Conditioners and Single Package subpart \2\.
Vertical Heat Pumps.
Direct Expansion-Dedicated Outdoor All................... <324 lbs. of moisture ISMRE2 and ISCOP2.... Appendix B to this None.
Air Systems. removal/hr. subpart.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Moisture removal capacity applies only to direct expansion-dedicated outdoor air systems.
\2\ For equipment with multiple appendices listed in this table, consult the notes at the beginning of those appendices to determine the applicable
appendix to use for testing.
\3\ For upflow ducted and downflow floor-mounted computer room air conditioners, the test procedure in appendix E1 to this subpart applies to equipment
with net sensible cooling capacity less than 930,000 Btu/h. For all other configurations of computer room air conditioners, the test procedure in
appendix E1 to this subpart applies to equipment with net sensible cooling capacity less than 760,000 Btu/h.
* * * * *
0
10. Revise Sec. 431.97 to read as follows:
Sec. 431.97 Energy efficiency standards and their compliance dates.
(a) All basic models of commercial package air conditioning and
heating equipment must be tested for performance using the applicable
DOE test procedure in Sec. 431.96, be compliant with the applicable
standards set forth in paragraphs (b) through (i) of this section, and
be certified to the Department under 10 CFR part 429.
(b) Each commercial package air conditioning and heating equipment
(excluding air-cooled equipment with cooling capacity less than 65,000
Btu/h) manufactured starting on the compliance date listed in tables 1
through 4 to this paragraph (b) must meet the applicable minimum energy
efficiency standard level(s) set forth in tables 1 through 4.
Table 1 to Paragraph (b)--Minimum Efficiency Standards for Air-Cooled Commercial Package Air Conditioning and
Heating Equipment With a Cooling Capacity Greater Than or Equal to 65,000 Btu/h
[Excluding double-duct air-conditioners and heat pumps]
----------------------------------------------------------------------------------------------------------------
Compliance date:
Supplementary Minimum efficiency equipment
Cooling capacity Subcategory heating type \1\ manufactured starting
on . . .
----------------------------------------------------------------------------------------------------------------
Air-Cooled Commercial Package Air Conditioning and Heating Equipment with a Cooling Capacity Greater Than or
Equal to 65,000 Btu/h (Excluding Double-Duct Air Conditioners and Heat Pumps)
----------------------------------------------------------------------------------------------------------------
>=65,000 Btu/h and <135,000 AC.............. Electric IEER = 14.8.......... January 1, 2023.
Btu/h. Resistance
Heating or No
Heating.
>=65,000 Btu/h and <135,000 AC.............. All Other Types IEER = 14.6.......... January 1, 2023.
Btu/h. of Heating.
>=65,000 Btu/h and <135,000 HP.............. Electric IEER = 14.1.......... January 1, 2023.
Btu/h. Resistance COP = 3.4............
Heating or No
Heating.
>=65,000 Btu/h and <135,000 HP.............. All Other Types IEER = 13.9.......... January 1, 2023.
Btu/h. of Heating. COP = 3.4............
>=135,000 Btu/h and <240,000 AC.............. Electric IEER = 14.2.......... January 1, 2023.
Btu/h. Resistance
Heating or No
Heating.
>=135,000 Btu/h and <240,000 AC.............. All Other Types IEER = 14.0.......... January 1, 2023.
Btu/h. of Heating.
>=135,000 Btu/h and <240,000 HP.............. Electric IEER = 13.5.......... January 1, 2023.
Btu/h. Resistance COP = 3.3............
Heating or No
Heating.
>=135,000 Btu/h and <240,000 HP.............. All Other Types IEER = 13.3.......... January 1, 2023.
Btu/h. of Heating. COP = 3.3............
>=240,000 Btu/h and <760,000 AC.............. Electric IEER = 13.2.......... January 1, 2023.
Btu/h. Resistance
Heating or No
Heating.
>=240,000 Btu/h and <760,000 AC.............. All Other Types IEER = 13.0.......... January 1, 2023.
Btu/h. of Heating.
>=240,000 Btu/h and <760,000 HP.............. Electric IEER = 12.5.......... January 1, 2023.
Btu/h. Resistance COP = 3.2............
Heating or No
Heating.
>=240,000 Btu/h and <760,000 HP.............. All Other Types IEER = 12.3.......... January 1, 2023.
Btu/h. of Heating. COP = 3.2............
----------------------------------------------------------------------------------------------------------------
\1\ See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
[[Page 44039]]
Table 2 to Paragraph (b)--Minimum Cooling Efficiency Standards for Water-Cooled Commercial Package Air
Conditioning Equipment
----------------------------------------------------------------------------------------------------------------
Compliance date:
Cooling capacity Supplementary heating Minimum efficiency equipment manufactured
type starting on . . .
----------------------------------------------------------------------------------------------------------------
Water-Cooled Commercial Package Air Conditioning Equipment
----------------------------------------------------------------------------------------------------------------
<65,000 Btu/h........................ All.................... EER = 12.1............. October 29, 2003.
>=65,000 Btu/h and <135,000 Btu/h.... No Heating or Electric EER = 12.1............. June 1, 2013.
Resistance Heating.
>=65,000 Btu/h and <135,000 Btu/h.... All Other Types of EER = 11.9............. June 1, 2013.
Heating.
>=135,000 Btu/h and <240,000 Btu/h... No Heating or Electric EER = 12.5............. June 1, 2014.
Resistance Heating.
>=135,000 Btu/h and <240,000 Btu/h... All Other Types of EER = 12.3............. June 1, 2014.
Heating.
>=240,000 Btu/h and <760,000 Btu/h... No Heating or Electric EER = 12.4............. June 1, 2014.
Resistance Heating.
>=240,000 Btu/h and <760,000 Btu/h... All Other Types of EER = 12.2............. June 1, 2014.
Heating.
----------------------------------------------------------------------------------------------------------------
Table 3 to Paragraph (b)--Minimum Cooling Efficiency Standards for Evaporatively-Cooled Commercial Package Air
Conditioning Equipment
----------------------------------------------------------------------------------------------------------------
Compliance date:
Cooling capacity Supplementary heating Minimum efficiency equipment manufactured
type starting on . . .
----------------------------------------------------------------------------------------------------------------
Evaporatively-Cooled Commercial Package Air Conditioning Equipment
----------------------------------------------------------------------------------------------------------------
<65,000 Btu/h........................ All.................... EER = 12.1............. October 29, 2003.
>=65,000 Btu/h and <135,000 Btu/h.... No Heating or Electric EER = 12.1............. June 1, 2013.
Resistance Heating.
>=65,000 Btu/h and <135,000 Btu/h.... All Other Types of EER = 11.9............. June 1, 2013.
Heating.
>=135,000 Btu/h and <240,000 Btu/h... No Heating or Electric EER = 12.0............. June 1, 2014.
Resistance Heating.
>=135,000 Btu/h and <240,000 Btu/h... All Other Types of EER = 11.8............. June 1, 2014.
Heating.
>=240,000 Btu/h and <760,000 Btu/h... No Heating or Electric EER = 11.9............. June 1, 2014.
Resistance Heating.
>=240,000 Btu/h and <760,000 Btu/h... All Other Types of EER = 11.7............. June 1, 2014.
Heating.
----------------------------------------------------------------------------------------------------------------
Table 4 to Paragraph (b)--Minimum Efficiency Standards for Double-Duct Air Conditioners and Heat Pumps
----------------------------------------------------------------------------------------------------------------
Compliance date:
Supplementary Minimum efficiency equipment
Cooling capacity Subcategory heating type \1\ manufactured starting
on . . .
----------------------------------------------------------------------------------------------------------------
Double-Duct Air Conditioners and Heat Pumps
----------------------------------------------------------------------------------------------------------------
>=65,000 Btu/h and <135,000 AC.............. Electric EER = 11.2........... January 1, 2010.
Btu/h. Resistance
Heating or No
Heating.
>=65,000 Btu/h and <135,000 AC.............. All Other Types EER = 11.0........... January 1, 2010.
Btu/h. of Heating.
>=65,000 Btu/h and <135,000 HP.............. Electric EER = 11.0........... January 1, 2010.
Btu/h. Resistance COP = 3.3............
Heating or No
Heating.
>=65,000 Btu/h and <135,000 HP.............. All Other Types EER = 10.8........... January 1, 2010.
Btu/h. of Heating. COP = 3.3............
>=135,000 Btu/h and <240,000 AC.............. Electric EER = 11.0........... January 1, 2010.
Btu/h. Resistance
Heating or No
Heating.
>=135,000 Btu/h and <240,000 AC.............. All Other Types EER = 10.8........... January 1, 2010.
Btu/h. of Heating.
>=135,000 Btu/h and <240,000 HP.............. Electric EER = 10.6........... January 1, 2010.
Btu/h. Resistance COP = 3.2............
Heating or No
Heating.
>=135,000 Btu/h and <240,000 HP.............. All Other Types EER = 10.4........... January 1, 2010.
Btu/h. of Heating. COP = 3.2............
>=240,000 Btu/h and <300,000 AC.............. Electric EER = 10.0........... January 1, 2010.
Btu/h. Resistance
Heating or No
Heating.
>=240,000 Btu/h and <300,000 AC.............. All Other Types EER = 9.8............ January 1, 2010.
Btu/h. of Heating.
>=240,000 Btu/h and <300,000 HP.............. Electric EER = 9.5............ January 1, 2010.
Btu/h. Resistance COP = 3.2............
Heating or No
Heating.
>=240,000 Btu/h and <300,000 HP.............. All Other Types EER = 9.3............ January 1, 2010.
Btu/h. of Heating. COP = 3.2............
----------------------------------------------------------------------------------------------------------------
\1\ See section 3 of appendix A to this subpart for the test conditions upon which the COP standards are based.
(c) Each water-source heat pump manufactured starting on the
compliance date listed in table 5 to this paragraph (c) must meet the
applicable minimum energy efficiency standard level(s) set forth in
this paragraph (c).
[[Page 44040]]
Table 5 to Paragraph (c)--Minimum Efficiency Standards for Water-Source
Heat Pumps (Water-to-Air, Water-Loop)
------------------------------------------------------------------------
Compliance date:
equipment
Cooling capacity Minimum efficiency manufactured
starting on . . .
------------------------------------------------------------------------
Water-Source Heat Pumps (Water-to-Air, Water-Loop)
------------------------------------------------------------------------
<17,000 Btu/h................... EER = 12.2........ October 9, 2015.
COP = 4.3.........
>=17,000 Btu/h and <65,000 Btu/h EER = 13.0........ October 9, 2015.
COP = 4.3.........
>=65,000 Btu/h and <135,000 Btu/ EER = 13.0........ October 9, 2015.
h. COP = 4.3.........
------------------------------------------------------------------------
(d) Each non-standard size packaged terminal air conditioner (PTAC)
and packaged terminal heat pump (PTHP) manufactured on or after October
7, 2010, must meet the applicable minimum energy efficiency standard
level(s) set forth in table 6 to this paragraph (d). Each standard size
PTAC manufactured on or after October 8, 2012, and before January 1,
2017, must meet the applicable minimum energy efficiency standard
level(s) set forth in table 6. Each standard size PTHP manufactured on
or after October 8, 2012, must meet the applicable minimum energy
efficiency standard level(s) set forth in table 6. Each standard size
PTAC manufactured on or after January 1, 2017, must meet the applicable
minimum energy efficiency standard level(s) set forth in table 7 to
this paragraph (d).
Table 6 to Paragraph (d)--Minimum Efficiency Standards for PTAC and PTHP
--------------------------------------------------------------------------------------------------------------------------------------------------------
Compliance date: products manufactured
Equipment type Category Cooling capacity Efficiency level on and after . . .
--------------------------------------------------------------------------------------------------------------------------------------------------------
PTAC...................... Standard Size..................... <7,000 Btu/h.......... EER = 11.7............ October 8, 2012.\2\
>=7,000 Btu/h and EER = 13.8-(0.3 x Cap October 8, 2012.\2\
<=15,000 Btu/h. \1\).
>15,000 Btu/h......... EER = 9.3............. October 8, 2012.\2\
Non-Standard Size................. <7,000 Btu/h.......... EER = 9.4............. October 7, 2010.
>=7,000 Btu/h and EER = 10.9-(0.213 x October 7, 2010.
<=15,000 Btu/h. Cap \1\).
>15,000 Btu/h......... EER = 7.7............. October 7, 2010.
PTHP...................... Standard Size..................... <7,000 Btu/h.......... EER = 11.9............ October 8, 2012.
COP = 3.3.............
>=7,000 Btu/h and EER = 14.0-(0.3 x Cap October 8, 2012.
<=15,000 Btu/h. \1\).
COP = 3.7-(0.052 x Cap
\1\).
>15,000 Btu/h......... EER = 9.5............. October 8, 2012.
COP = 2.9.............
Non-Standard Size................. <7,000 Btu/h.......... EER = 9.3............. October 7, 2010.
COP = 2.7.............
>=7,000 Btu/h and EER = 10.8-(0.213 x October 7, 2010.
<=15,000 Btu/h. Cap \1\).
COP = 2.9-(0.026 x Cap
\1\).
>15,000 Btu/h......... EER = 7.6............. October 7, 2010.
COP = 2.5.............
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ ``Cap'' means cooling capacity in thousand Btu/h at 95 [deg]F outdoor dry-bulb temperature.
\2\ And manufactured before January 1, 2017. See table 7 to this paragraph (d) for updated efficiency standards that apply to this category of equipment
manufactured on and after January 1, 2017.
Table 7 to Paragraph (d)--Updated Minimum Efficiency Standards for PTAC
--------------------------------------------------------------------------------------------------------------------------------------------------------
Compliance date: products manufactured
Equipment type Category Cooling capacity Efficiency level on and after . . .
--------------------------------------------------------------------------------------------------------------------------------------------------------
PTAC...................... Standard Size..................... <7,000 Btu/h.......... EER = 11.9............ January 1, 2017.
>=7,000 Btu/h and EER = 14.0-(0.3 x Cap January 1, 2017.
<=15,000 Btu/h. \1\).
>15,000 Btu/h......... EER = 9.5............. January 1, 2017.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ ``Cap'' means cooling capacity in thousand Btu/h at 95 [deg]F outdoor dry-bulb temperature.
(e)(1) Each single package vertical air conditioner and single
package vertical heat pump manufactured on or after January 1, 2010,
but before October 9, 2015 (for models >=65,000 Btu/h and <135,000 Btu/
h), or October 9, 2016 (for models >=135,000 Btu/h and <240,000 Btu/h),
must meet the applicable minimum energy conservation standard level(s)
set forth in this paragraph (e)(1).
[[Page 44041]]
Table 8 to Paragraph (e)(1)--Minimum Efficiency Standards for Single Package Vertical Air Conditioners and
Single Package Vertical Heat Pumps
----------------------------------------------------------------------------------------------------------------
Compliance date:
products
Equipment type Cooling capacity Sub-category Efficiency level manufactured on
and after . . .
----------------------------------------------------------------------------------------------------------------
Single package vertical air <65,000 Btu/h..... AC................. EER = 9.0.......... January 1, 2010.
conditioners and single HP................. EER = 9.0.......... January 1, 2010.
package vertical heat pumps, COP = 3.0..........
single-phase and three-phase.
Single package vertical air >=65,000 Btu/h and AC................. EER = 8.9.......... January 1, 2010.
conditioners and single <135,000 Btu/h. HP................. EER = 8.9.......... January 1, 2010.
package vertical heat pumps. COP = 3.0..........
Single package vertical air >=135,000 Btu/h AC................. EER = 8.6.......... January 1, 2010.
conditioners and single and <240,000 Btu/ HP................. EER = 8.6.......... January 1, 2010.
package vertical heat pumps. h. COP = 2.9..........
----------------------------------------------------------------------------------------------------------------
(2) Each single package vertical air conditioner and single package
vertical heat pump manufactured on and after October 9, 2015 (for
models >=65,000 Btu/h and <135,000 Btu/h), or October 9, 2016 (for
models >=135,000 Btu/h and <240,000 Btu/h), but before September 23,
2019, must meet the applicable minimum energy conservation standard
level(s) set forth in this paragraph (e)(2).
Table 9 to Paragraph (e)(2)--Minimum Efficiency Standards for Single Package Vertical Air Conditioners and
Single Package Vertical Heat Pumps
----------------------------------------------------------------------------------------------------------------
Compliance date:
products
Equipment type Cooling capacity Sub-category Efficiency level manufactured on
and after . . .
----------------------------------------------------------------------------------------------------------------
Single package vertical air <65,000 Btu/h..... AC................. EER = 9.0.......... January 1, 2010.
conditioners and single HP................. EER = 9.0.......... January 1, 2010.
package vertical heat pumps, COP = 3.0..........
single-phase and three-phase.
Single package vertical air >=65,000 Btu/h and AC................. EER = 10.0......... October 9, 2015.
conditioners and single <135,000 Btu/h. HP................. EER = 10.0......... October 9, 2015.
package vertical heat pumps. COP = 3.0..........
Single package vertical air >=135,000 Btu/h AC................. EER = 10.0......... October 9, 2016.
conditioners and single and <240,000 Btu/ HP................. EER = 10.0......... October 9, 2016.
package vertical heat pumps. h. COP = 3.0..........
----------------------------------------------------------------------------------------------------------------
(3) Each single package vertical air conditioner and single package
vertical heat pump manufactured on and after September 23, 2019, must
meet the applicable minimum energy conservation standard level(s) set
forth in this paragraph (e)(3).
Table 10 to Paragraph (e)(3)--Updated Minimum Efficiency Standards for Single Package Vertical Air Conditioners
and Single Package Vertical Heat Pumps
----------------------------------------------------------------------------------------------------------------
Compliance date:
products
Equipment type Cooling capacity Sub-category Efficiency level manufactured on
and after . . .
----------------------------------------------------------------------------------------------------------------
Single package vertical air <65,000 Btu/h..... AC................. EER = 11.0......... September 23,
conditioners and single HP................. EER = 11.0......... 2019.
package vertical heat pumps, COP = 3.3.......... September 23,
single-phase and three-phase. 2019.
Single package vertical air >=65,000 Btu/h and AC................. EER = 10.0......... October 9, 2015.
conditioners and single <135,000 Btu/h. HP................. EER = 10.0......... October 9, 2015.
package vertical heat pumps. COP = 3.0..........
Single package vertical air >=135,000 Btu/h AC................. EER = 10.0......... October 9, 2016.
conditioners and single and <240,000 Btu/ HP................. EER = 10.0......... October 9, 2016.
package vertical heat pumps. h. COP = 3.0..........
----------------------------------------------------------------------------------------------------------------
(f)(1) Each computer room air conditioner with a net sensible
cooling capacity less than 65,000 Btu/h manufactured on or after
October 29, 2012, and before May 28, 2024 and each computer room air
conditioner with a net sensible cooling capacity greater than or equal
to 65,000 Btu/h and less than 760,000 Btu/h manufactured on or after
October 29, 2013, and before May 28, 2024, must meet the applicable
minimum energy efficiency standard level(s) set forth in this paragraph
(f)(1).
[[Page 44042]]
Table 11 to Paragraph (f)(1)--Minimum Efficiency Standards for Computer Room Air Conditioners
----------------------------------------------------------------------------------------------------------------
Minimum SCOP efficiency
Equipment type Net sensible cooling capacity -------------------------------
Downflow Upflow
----------------------------------------------------------------------------------------------------------------
Air-Cooled................................. <65,000 Btu/h...................... 2.20 2.09
>=65,000 Btu/h and <240,000 Btu/h.. 2.10 1.99
>=240,000 Btu/h and <760,000 Btu/h. 1.90 1.79
Water-Cooled............................... <65,000 Btu/h...................... 2.60 2.49
>=65,000 Btu/h and <240,000 Btu/h.. 2.50 2.39
>=240,000 Btu/h and <760,000 Btu/h. 2.40 2.29
Water-Cooled with Fluid Economizer......... <65,000 Btu/h...................... 2.55 2.44
>=65,000 Btu/h and <240,000 Btu/h.. 2.45 2.34
>=240,000 Btu/h and <760,000 Btu/h. 2.35 2.24
Glycol-Cooled.............................. <65,000 Btu/h...................... 2.50 2.39
>=65,000 Btu/h and <240,000 Btu/h.. 2.15 2.04
>=240,000 Btu/h and <760,000 Btu/h. 2.10 1.99
Glycol-Cooled with Fluid Economizer........ <65,000 Btu/h...................... 2.45 2.34
>=65,000 Btu/h and <240,000 Btu/h.. 2.10 1.99
>=240,000 Btu/h and <760,000 Btu/h. 2.05 1.94
----------------------------------------------------------------------------------------------------------------
(2) Each computer room air conditioner manufactured on or after May
28, 2024, must meet the applicable minimum energy efficiency standard
level(s) set forth in this paragraph (f)(2).
Table 12 to Paragraph (f)(2)--Updated Minimum Efficiency Standards for Floor-Mounted Computer Room Air Conditioners
--------------------------------------------------------------------------------------------------------------------------------------------------------
Downflow and upflow ducted Upflow non-ducted and horizontal flow
---------------------------------------------------------------------------------------------------------------------
Minimum NSenCOP efficiency Minimum NSenCOP efficiency
Equipment type Net sensible cooling -------------------------------- Net sensible cooling -------------------------------
capacity capacity Upflow non- Horizontal
Downflow Upflow ducted ducted flow
--------------------------------------------------------------------------------------------------------------------------------------------------------
Air-Cooled........................ <80,000 Btu/h............ 2.70 2.67 <65,000 Btu/h............ 2.16 2.65
>=80,000 Btu/h and 2.58 2.55 >=65,000 Btu/h and 2.04 2.55
<295,000 Btu/h. <240,000 Btu/h.
>=295,000 Btu/h and 2.36 2.33 >=240,000 Btu/h and 1.89 2.47
<930,000 Btu/h. <760,000 Btu/h.
Air-Cooled with Fluid Economizer.. <80,000 Btu/h............ 2.70 2.67 <65,000 Btu/h............ 2.09 2.65
>=80,000 Btu/h and 2.58 2.55 >=65,000 Btu/h and 1.99 2.55
<295,000 Btu/h. <240,000 Btu/h.
>=295,000 Btu/h and 2.36 2.33 >=240,000 Btu/h and 1.81 2.47
<930,000 Btu/h. <760,000 Btu/h.
Water-Cooled...................... <80,000 Btu/h............ 2.82 2.79 <65,000 Btu/h............ 2.43 2.79
>=80,000 Btu/h and 2.73 2.70 >=65,000 Btu/h and 2.32 2.68
<295,000 Btu/h. <240,000 Btu/h.
>=295,000 Btu/h and 2.67 2.64 >=240,000 Btu/h and 2.20 2.60
<930,000 Btu/h. <760,000 Btu/h.
Water-Cooled with Fluid Economizer <80,000 Btu/h............ 2.77 2.74 <65,000 Btu/h............ 2.35 2.71
>=80,000 Btu/h and 2.68 2.65 >=65,000 Btu/h and 2.24 2.60
<295,000 Btu/h. <240,000 Btu/h.
>=295,000 Btu/h and 2.61 2.58 >=240,000 Btu/h and 2.12 2.54
<930,000 Btu/h. <760,000 Btu/h.
Glycol-Cooled..................... <80,000 Btu/h............ 2.56 2.53 <65,000 Btu/h............ 2.08 2.48
>=80,000 Btu/h and 2.24 2.21 >=65,000 Btu/h and 1.90 2.18
<295,000 Btu/h. <240,000 Btu/h.
>=295,000 Btu/h and 2.21 2.18 >=240,000 Btu/h and 1.81 2.18
<930,000 Btu/h. <760,000 Btu/h.
Glycol-Cooled with Fluid <80,000 Btu/h............ 2.51 2.48 <65,000 Btu/h............ 2.00 2.44
Economizer.
>=80,000 Btu/h and 2.19 2.16 >=65,000 Btu/h and 1.82 2.10
<295,000 Btu/h. <240,000 Btu/h.
>=295,000 Btu/h and 2.15 2.12 >=240,000 Btu/h and 1.73 2.10
<930,000 Btu/h. <760,000 Btu/h.
--------------------------------------------------------------------------------------------------------------------------------------------------------
Table 13 to Paragraph (f)(2)--Minimum Efficiency Standards for Ceiling-Mounted Computer Room Air Conditioners
----------------------------------------------------------------------------------------------------------------
Minimum NSenCOP efficiency
Equipment type Net sensible cooling capacity -------------------------------
Ducted Non-ducted
----------------------------------------------------------------------------------------------------------------
Air-Cooled with Free Air Discharge <29,000 Btu/h...................... 2.05 2.08
Condenser.
[[Page 44043]]
>=29,000 Btu/h and <65,000 Btu/h... 2.02 2.05
>=65,000 Btu/h and <760,000 Btu/h.. 1.92 1.94
Air-Cooled with Free Air Discharge <29,000 Btu/h...................... 2.01 2.04
Condenser and Fluid Economizer.
>=29,000 Btu/h and <65,000 Btu/h... 1.97 2
>=65,000 Btu/h and <760,000 Btu/h.. 1.87 1.89
Air-Cooled with Ducted Condenser........... <29,000 Btu/h...................... 1.86 1.89
>=29,000 Btu/h and <65,000 Btu/h... 1.83 1.86
>=65,000 Btu/h and <760,000 Btu/h.. 1.73 1.75
Air-Cooled with Fluid Economizer and Ducted <29,000 Btu/h...................... 1.82 1.85
Condenser.
>=29,000 Btu/h and <65,000 Btu/h... 1.78 1.81
>=65,000 Btu/h and <760,000 Btu/h.. 1.68 1.7
Water-Cooled............................... <29,000 Btu/h...................... 2.38 2.41
>=29,000 Btu/h and <65,000 Btu/h... 2.28 2.31
>=65,000 Btu/h and <760,000 Btu/h.. 2.18 2.2
Water-Cooled with Fluid Economizer......... <29,000 Btu/h...................... 2.33 2.36
>=29,000 Btu/h and <65,000 Btu/h... 2.23 2.26
>=65,000 Btu/h and <760,000 Btu/h.. 2.13 2.16
Glycol-Cooled.............................. <29,000 Btu/h...................... 1.97 2
>=29,000 Btu/h and <65,000 Btu/h... 1.93 1.98
>=65,000 Btu/h and <760,000 Btu/h.. 1.78 1.81
Glycol-Cooled with Fluid Economizer........ <29,000 Btu/h...................... 1.92 1.95
>=29,000 Btu/h and <65,000 Btu/h... 1.88 1.93
>=65,000 Btu/h and <760,000 Btu/h.. 1.73 1.76
----------------------------------------------------------------------------------------------------------------
(g)(1) Each variable refrigerant flow air conditioner or heat pump
manufactured on or after the compliance date listed in table 14 to this
paragraph (g)(1) and prior to January 1, 2024, must meet the applicable
minimum energy efficiency standard level(s) set forth in this paragraph
(g)(1).
Table 14 to Paragraph (g)(1)--Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air
Conditioners and Heat Pumps
----------------------------------------------------------------------------------------------------------------
Compliance date:
equipment
Equipment type Cooling capacity Heating type \1\ Efficiency level manufactured on
and after . . .
----------------------------------------------------------------------------------------------------------------
VRF Multi-Split Air Conditioners >=65,000 Btu/h and No Heating or 11.2 EER.......... January 1, 2010.
(Air-Cooled). <135,000 Btu/h. Electric
Resistance
Heating.
All Other Types of 11.0 EER.......... January 1, 2010.
Heating.
>=135,000 Btu/h No Heating or 11.0 EER.......... January 1, 2010.
and <240,000 Btu/ Electric
h. Resistance
Heating.
All Other Types of 10.8 EER.......... January 1, 2010.
Heating.
>=240,000 Btu/h No Heating or 10.0 EER.......... January 1, 2010.
and <760,000 Btu/ Electric
h. Resistance
Heating.
All Other Types of 9.8 EER........... January 1, 2010.
Heating.
VRF Multi-Split Heat Pumps (Air- >=65,000 Btu/h and No Heating or 11.0 EER, 3.3 COP. January 1, 2010.
Cooled). <135,000 Btu/h. Electric
Resistance
Heating.
All Other Types of 10.8 EER, 3.3 COP. January 1, 2010.
Heating.
>=135,000 Btu/h No Heating or 10.6 EER, 3.2 COP. January 1, 2010.
and <240,000 Btu/ Electric
h. Resistance
Heating.
All Other Types of 10.4 EER, 3.2 COP. January 1, 2010.
Heating.
>=240,000 Btu/h No Heating or 9.5 EER, 3.2 COP.. January 1, 2010.
and <760,000 Btu/ Electric
h. Resistance
Heating.
All Other Types of 9.3 EER, 3.2 COP.. January 1, 2010.
Heating.
VRF Multi-Split Heat Pumps <17,000 Btu/h..... Without Heat 12.0 EER, 4.2 COP. October 29, 2012.
(Water-Source). Recovery. October 29, 2003.
With Heat Recovery 11.8 EER, 4.2 COP. October 29, 2012.
October 29, 2003.
>=17,000 Btu/h and All. 12.0 EER, 4.2 COP. October 29, 2003.
<65,000 Btu/h.
>=65,000 Btu/h and All. 12.0 EER, 4.2 COP. October 29, 2003.
<135,000 Btu/h.
>=135,000 Btu/h Without Heat 10.0 EER, 3.9 COP. October 29, 2013.
and <760,000 Btu/ Recovery.
h.
[[Page 44044]]
With Heat Recovery 9.8 EER, 3.9 COP.. October 29, 2013.
----------------------------------------------------------------------------------------------------------------
\1\ VRF multi-split heat pumps (air-cooled) with heat recovery fall under the category of ``All Other Types of
Heating'' unless they also have electric resistance heating, in which case it falls under the category for
``No Heating or Electric Resistance Heating.''
(2) Each variable refrigerant flow air conditioner or heat pump
(except air-cooled systems with cooling capacity less than 65,000 Btu/
h) manufactured on or after January 1, 2024, must meet the applicable
minimum energy efficiency standard level(s) set forth in this paragraph
(g)(2).
Table 15 to Paragraph (g)(2)--Updated Minimum Efficiency Standards for Variable Refrigerant Flow Multi-Split Air
Conditioners and Heat Pumps
----------------------------------------------------------------------------------------------------------------
Equipment type Size category Heating type Minimum efficiency
----------------------------------------------------------------------------------------------------------------
VRF Multi-Split Air Conditioners >=65,000 and <135,000 Btu/h All................... 15.5 IEER.
(Air-Cooled).
>=135,000 and <240,000 Btu/ All................... 14.9 IEER.
h.
>=240,000 Btu/h and All................... 13.9 IEER.
<760,000 Btu/h.
VRF Multi-Split Heat Pumps (Air- >=65,000 and <135,000 Btu/h Heat Pump without Heat 14.6 IEER, 3.3 COP.
Cooled). Recovery.
Heat Pump with Heat 14.4 IEER, 3.3 COP.
Recovery.
>=135,000 and <240,000 Btu/ Heat Pump without Heat 13.9 IEER, 3.2 COP.
h. Recovery. 13.7 IEER, 3.2 COP.
Heat Pump with Heat
Recovery.
>=240,000 Btu/h and Heat Pump without Heat 12.7 IEER, 3.2 COP.
<760,000 Btu/h. Recovery. 12.5 IEER, 3.2 COP.
Heat Pump with Heat
Recovery.
VRF Multi-Split Heat Pumps (Water- <65,000 Btu/h.............. Heat Pump without Heat 16.0 IEER, 4.3 COP.
Source). Recovery. 15.8 IEER, 4.3 COP.
Heat Pump with Heat
Recovery.
>=65,000 and <135,000 Btu/h Heat Pump without Heat 16.0 IEER, 4.3 COP.
Recovery. 15.8 IEER, 4.3 COP.
Heat Pump with Heat
Recovery.
>=135,000 and <240,000 Btu/ Heat Pump without Heat 14.0 IEER, 4.0 COP.
h. Recovery. 13.8 IEER, 4.0 COP.
Heat Pump with Heat
Recovery.
>=240,000 Btu/h and Heat Pump without Heat 12.0 IEER, 3.9 COP.
<760,000 Btu/h. Recovery. 11.8 IEER, 3.9 COP.
Heat Pump with Heat
Recovery.
----------------------------------------------------------------------------------------------------------------
(h) Each direct expansion-dedicated outdoor air system manufactured
on or after the compliance date listed in table 16 to this paragraph
(h) must meet the applicable minimum energy efficiency standard
level(s) set forth in this paragraph (h).
Table 16 to Paragraph (h)--Minimum Efficiency Standards for Direct Expansion-Dedicated Outdoor Air Systems
----------------------------------------------------------------------------------------------------------------
Compliance date:
Equipment Category Subcategory Efficiency level equipment manufactured
starting on . . .
----------------------------------------------------------------------------------------------------------------
Direct expansion-dedicated outdoor (AC)--Air-cooled without ISMRE2 = 3.8.......... May 1, 2024.
air systems. ventilation energy
recovery systems.
(AC w/VERS)--Air-cooled ISMRE2 = 5.0.......... May 1, 2024.
with ventilation energy
recovery systems.
(ASHP)--Air-source heat ISMRE2 = 3.8.......... May 1, 2024.
pumps without ventilation ISCOP2 = 2.05.........
energy recovery systems.
(ASHP w/VERS)--Air-source ISMRE2 = 5.0.......... May 1, 2024.
heat pumps with ISCOP2 = 3.20.........
ventilation energy
recovery systems.
(WC)--Water-cooled without ISMRE2 = 4.7.......... May 1, 2024.
ventilation energy
recovery systems.
(WC w/VERS)--Water-cooled ISMRE2 = 5.1.......... May 1, 2024.
with ventilation energy
recovery systems.
[[Page 44045]]
(WSHP)--Water-source heat ISMRE2 = 3.8.......... May 1, 2024.
pumps without ventilation ISCOP2 = 2.13.........
energy recovery systems.
(WSHP w/VERS)--Water-source ISMRE2 = 4.6.......... May 1, 2024.
heat pumps with ISCOP2 = 4.04.........
ventilation energy
recovery systems.
----------------------------------------------------------------------------------------------------------------
(i) Air-cooled, three-phase, commercial package air conditioning
and heating equipment with a cooling capacity of less than 65,000 Btu/h
and air-cooled, three-phase variable refrigerant flow multi-split air
conditioning and heating equipment with a cooling capacity of less than
65,000 Btu/h manufactured on or after the compliance date listed in
tables 17 and 18 to this paragraph (i) must meet the applicable minimum
energy efficiency standard level(s) set forth in this paragraph (i).
Table 17 to Paragraph (i)--Minimum Efficiency Standards for Air-Cooled, Three-Phase, Commercial Package Air
Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/h and Air-Cooled, Three-
Phase, Small Variable Refrigerant Flow Multi-Split Air Conditioning and Heating Equipment With a Cooling
Capacity of Less Than 65,000 Btu/h
----------------------------------------------------------------------------------------------------------------
Compliance date:
equipment
Equipment type Cooling capacity Subcategory Minimum efficiency manufactured
starting on . . .
----------------------------------------------------------------------------------------------------------------
Commercial Package Air <65,000 Btu/h..... Split-System...... 13.0 SEER......... June 16, 2008.\1\
Conditioning Equipment.
Commercial Package Air <65,000 Btu/h..... Single-Package.... 14.0 SEER......... January 1,
Conditioning Equipment. 2017.\1\
Commercial Package Air <65,000 Btu/h..... Split-System...... 14.0 SEER......... January 1,
Conditioning and Heating 8.2 HSPF.......... 2017.\1\
Equipment.
Commercial Package Air <65,000 Btu/h..... Single-Package.... 14.0 SEER......... January 1,
Conditioning and Heating 8.0 HSPF.......... 2017.\1\
Equipment.
VRF Air Conditioners............ <65,000 Btu/h..... .................. 13.0 SEER......... June 16, 2008.\1\
VRF Heat Pumps.................. <65,000 Btu/h..... .................. 13.0 SEER......... June 16, 2008.\1\
7.7 HSPF..........
----------------------------------------------------------------------------------------------------------------
\1\ And manufactured before January 1, 2025. For equipment manufactured on or after January 1, 2025, see table
18 to this paragraph (i) for updated efficiency standards.
Table 18 to Paragraph (i)--Updated Minimum Efficiency Standards for Air-Cooled, Three-Phase, Commercial Package
Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/h and Air-Cooled, Three-
Phase, Small Variable Refrigerant Flow Multi-Split Air Conditioning and Heating Equipment With a Cooling
Capacity of Less Than 65,000 Btu/h
----------------------------------------------------------------------------------------------------------------
Compliance date:
equipment
Equipment type Cooling capacity Subcategory Minimum efficiency manufactured
starting on. . .
----------------------------------------------------------------------------------------------------------------
Commercial Package Air < 65,000 Btu/h.... Split-System...... 13.4 SEER2........ January 1, 2025.
Conditioning Equipment.
Commercial Package Air < 65,000 Btu/h.... Single-Package.... 13.4 SEER2........ January 1, 2025.
Conditioning Equipment.
Commercial Package Air < 65,000 Btu/h.... Split-System...... 14.3 SEER2........ January 1, 2025.
Conditioning and Heating 7.5 HSPF2.........
Equipment.
Commercial Package Air < 65,000 Btu/h.... Single-Package.... 13.4 SEER2........ January 1, 2025.
Conditioning and Heating 6.7 HSPF2.........
Equipment.
Space-Constrained Commercial <= 30,000 Btu/h... Split-System...... 12.7 SEER2........ January 1, 2025.
Package Air Conditioning
Equipment.
Space-Constrained Commercial <= 30,000 Btu/h... Single-Package.... 13.9 SEER2........ January 1, 2025.
Package Air Conditioning
Equipment.
Space-Constrained Commercial <= 30,000 Btu/h... Split-System...... 13.9 SEER2........ January 1, 2025.
Package Air Conditioning and 7.0 HSPF2.........
Heating Equipment.
Space-Constrained Commercial <= 30,000 Btu/h... Single-Package.... 13.9 SEER2........ January 1, 2025.
Package Air Conditioning and 6.7 HSPF2.........
Heating Equipment.
Small-Duct, High-Velocity < 65,000 Btu/h.... Split-System...... 13.0 SEER2........ January 1, 2025.
Commercial Package Air
Conditioning.
[[Page 44046]]
Small-Duct, High-Velocity < 65,000 Btu/h.... Split-System...... 14.0 SEER2........ January 1, 2025.
Commercial Package Air 6.9 HSPF2.........
Conditioning and Heating
Equipment.
VRF Air Conditioners............ < 65,000 Btu/h.... .................. 13.4 SEER2........ January 1, 2025.
VRF Heat Pumps.................. < 65,000 Btu/h.... .................. 13.4 SEER2........ January 1, 2025.
7.5 HSPF2.........
----------------------------------------------------------------------------------------------------------------
0
11. Appendix A to subpart F of part 431 is revised to read as follows:
Appendix A to Subpart F of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of Commercial Package Air
Conditioning and Heating Equipment (Excluding Air-Cooled Equipment With
a Cooling Capacity Less Than 65,000 Btu/h)
Note: Prior to May 15, 2025, representations with respect to the
energy use or efficiency of commercial package air conditioning and
heating equipment (excluding air-cooled equipment with a cooling
capacity less than 65,000 Btu/h), including compliance
certifications, must be based on testing conducted in accordance
with:
(a) The applicable provisions (appendix A to subpart F of part
431 for air-cooled equipment, and table 1 to Sec. 431.96 for water-
cooled and evaporatively-cooled equipment) as they appeared in
subpart F of 10 CFR part 431, revised as of January 1, 2024; or
(b) This appendix.
Beginning May 15, 2025, and prior to the compliance date of
amended standards for commercial package air conditioning and
heating equipment (excluding air-cooled equipment with a cooling
capacity less than 65,000 Btu/h) based on integrated ventilation,
economizing, and cooling (IVEC) and integrated ventilation and
heating efficiency (IVHE) (see Sec. 431.97), representations with
respect to energy use or efficiency of commercial package air
conditioning and heating equipment (excluding air-cooled equipment
with a cooling capacity less than 65,000 Btu/h), including
compliance certifications, must be based on testing conducted in
accordance with this appendix.
Beginning on the compliance date of amended standards for
commercial package air conditioning and heating equipment (excluding
equipment with a cooling capacity less than 65,000 Btu/h) based on
IVEC and IVHE (see Sec. 431.97), representations with respect to
energy use or efficiency of commercial package air conditioning and
heating equipment (excluding air-cooled equipment with a cooling
capacity less than 65,000 Btu/h), including compliance
certifications, must be based on testing conducted in accordance
with appendix A1 to this subpart.
Manufacturers may also certify compliance with any amended
energy conservation standards for commercial package air
conditioning and heating equipment (excluding air-cooled equipment
with a cooling capacity less than 65,000 Btu/h) based on IVEC or
IVHE prior to the applicable compliance date for those standards
(see Sec. 431.97), and those compliance certifications must be
based on testing in accordance with appendix A1 to this subpart.
1. Incorporation by Reference
DOE incorporated by reference in Sec. 431.95, the entire
standard for AHRI 340/360-2022 and ANSI/ASHRAE 37-2009. However,
certain enumerated provisions of AHRI 340/360-2022 and ANSI/ASHRAE
37-2009, as set forth in this section 1 are inapplicable. To the
extent there is a conflict between the terms or provisions of a
referenced industry standard and the CFR, the CFR provisions
control.
1.1. AHRI 340/360-2022:
(a) Section 1 Purpose is inapplicable,
(b) Section 2 Scope is inapplicable,
(c) The following subsections of Section 3 Definitions are
inapplicable: 3.2 (Basic Model), 3.4 (Commercial and Industrial
Unitary Air-conditioning Equipment), 3.5 (Commercial and Industrial
Unitary Heat Pump), 3.7 (Double-duct System), 3.8 (Energy Efficiency
Ratio (EER)), 3.12 (Heating Coefficient of Performance
(COPH)), 3.14 (Integrated Energy Efficiency Ratio
(IEER)), 3.23 (Published Rating), 3.26 (Single Package Air-
Conditioners), 3.27 (Single Package Heat Pumps), 3.29 (Split System
Air-conditioners), 3.30 (Split System Heat Pump), 3.36 (Year Round
Single Package Air-conditioners),
(d) Section 7 Minimum Data Requirements for Published Ratings is
inapplicable,
(e) Section 8 Operating Requirements is inapplicable,
(f) Section 9 Marking and Nameplate Data is inapplicable,
(g) Section 10 Conformance Conditions is inapplicable,
(h) Appendix B References--Informative is inapplicable,
(i) Appendix D Unit Configuration for Standard Efficiency
Determination--Normative is inapplicable,
(j) Appendix F International Rating Conditions--Normative is
inapplicable,
(k) Appendix G Examples of IEER Calculations--Informative is
inapplicable,
(l) Appendix H Example of Determination of Fan and Motor
Efficiency for Non-standard Integrated Indoor Fan and Motors--
Informative is inapplicable, and
(m) Appendix I Double-duct System Efficiency Metrics with Non-
Zero Outdoor Air External Static Pressure (ESP)--Normative is
inapplicable.
1.2. ANSI/ASHRAE 37-2009:
(a) Section 1 Purpose is inapplicable
(b) Section 2 Scope is inapplicable, and
(c) Section 4 Classifications is inapplicable.
2. General
Determine the applicable energy efficiency metrics (IEER, EER,
and COP) in accordance with this appendix and the applicable
sections of AHRI 340/360-2022 and ANSI/ASHRAE 37-2009.
Section 3 of this appendix provides additional instructions for
testing. In cases where there is a conflict, the language of this
appendix takes highest precedence, followed by AHRI 340/360-2022,
followed by ANSI/ASHRAE 37-2009. Any subsequent amendment to a
referenced document by the standard-setting organization will not
affect the test procedure in this appendix, unless and until the
test procedure is amended by DOE.
3. Test Conditions
The following conditions specified in Table 6 of AHRI 340/360-
2022 apply when testing to certify to the energy conservation
standards in Sec. 431.97. For cooling mode tests for equipment
subject to standards in terms of EER, test using the ``Standard
Rating Conditions Cooling''. For cooling mode tests for equipment
subject to standards in terms of IEER, test using the ``Standard
Rating Conditions Cooling'' and the ``Standard Rating Part-Load
Conditions (IEER)''. For heat pump heating mode tests for equipment
subject to standards in terms of COP, test using the ``Standard
Rating Conditions (High Temperature Steady State Heating)''.
For equipment subject to standards in terms of EER,
representations of IEER made using the ``Standard Rating Part-Load
Conditions (IEER)'' in Table 6 of AHRI 340/360-2022 are optional.
For equipment
[[Page 44047]]
subject to standards in terms of IEER, representations of EER made
using the ``Standard Rating Conditions Cooling'' in Table 6 of AHRI
340/360-2022 are optional. Representations of COP made using the
``Standard Rating Conditions (Low Temperature Steady State
Heating)'' in Table 6 of AHRI 340/360-2022 are optional and are not
to be used as the basis for determining compliance with energy
efficiency standards in terms of COP.
0
12. Add appendix A1 to subpart F of part 431 to read as follows:
Appendix A1 to Subpart F of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of Commercial Package Air
Conditioning and Heating Equipment (Excluding Air-Cooled Equipment With
a Cooling Capacity Less Than 65,000 Btu/h)
Note: Prior to May 15, 2025, representations with respect to
the energy use or efficiency of commercial package air conditioning
and heating equipment (excluding air-cooled equipment with a cooling
capacity less than 65,000 Btu/h), including compliance
certifications, must be based on testing conducted in accordance
with:
(a) The applicable provisions (appendix A to subpart F of part
431 for air-cooled equipment, and table 1 to Sec. 431.96 for water-
cooled and evaporatively-cooled equipment) as it appeared in subpart
F of 10 CFR part 431, revised as of January 1, 2024; or
(b) Appendix A to this subpart.
Beginning May 15, 2025, and prior to the compliance date of
amended standards for commercial package air conditioning and
heating equipment (excluding air-cooled equipment with a cooling
capacity less than 65,000 Btu/h) based on integrated ventilation,
economizing, and cooling (IVEC) and integrated ventilation and
heating efficiency (IVHE) (see Sec. 431.97), representations with
respect to energy use or efficiency of commercial package air
conditioning and heating equipment (excluding air-cooled equipment
with a cooling capacity less than 65,000 Btu/h), including
compliance certifications, must be based on testing conducted in
accordance with appendix A to this subpart.
Beginning on the compliance date of amended standards for
commercial package air conditioning and heating equipment (excluding
air-cooled equipment with a cooling capacity less than 65,000 Btu/h)
based on IVEC and IVHE (see Sec. 431.97), representations with
respect to energy use or efficiency of commercial package air
conditioning and heating equipment (excluding air-cooled equipment
with a cooling capacity less than 65,000 Btu/h), including
compliance certifications, must be based on testing conducted in
accordance with this appendix.
Manufacturers may also certify compliance with any amended
energy conservation standards for commercial package air
conditioning and heating equipment (excluding air-cooled equipment
with a cooling capacity less than 65,000 Btu/h) based on IVEC or
IVHE prior to the applicable compliance date for those standards
(see Sec. 431.97), and those compliance certifications must be
based on testing in accordance with this appendix.
1. Incorporation by Reference
DOE incorporated by reference in Sec. 431.95, the entire
standard for AHRI 1340-2023 and ANSI/ASHRAE 37-2009. However,
certain enumerated provisions of AHRI 1340-2023 and ANSI/ASHRAE 37-
2009, as listed in this section 1 are inapplicable. To the extent
there is a conflict between the terms or provisions of a referenced
industry standard and the CFR, the CFR provisions control.
1.1. AHRI 1340-2023:
(a) Section 1 Purpose is inapplicable,
(b) Section 2 Scope is inapplicable,
(c) The following subsections of section 3 Definitions are
inapplicable: 3.2.2 (Barometric Relief Damper), 3.2.3 (Basic Model),
3.2.5 (Commercial and Industrial Unitary Air-conditioner and Heat
Pump Equipment), 3.2.5.1 (Commercial and Industrial Unitary Air-
Conditioning System), 3.2.5.2 (Commercial and Industrial Unitary
Heat Pump System), 3.2.7 (Double-duct System), 3.2.9 (Desiccant
Dehumidification Component), 3.2.10 (Drain Pan Heater), 3.2.11.1
(Air Economizer), 3.2.12 (Energy Efficiency Ratio 2), 3.2.13
(Evaporative Cooling), 3.2.13.1 (Direct Evaporative Cooling System),
3.2.13.2 (Indirect Evaporative Cooling System), 3.2.14 (Fresh Air
Damper), 3.2.15 (Fire, Smoke, or Isolation Damper), 3.2.17 (Hail
Guard), 3.2.19 (Heating Coefficient of Performance 2
(COP2H)), 3.2.20 (High-Effectiveness Indoor Air
Filtration), 3.2.22 (Indoor Single Package Air-conditioners), 3.2.23
(Integrated Ventilation, Economizing, and Cooling Efficiency
(IVEC)), 3.2.34 (Integrated Ventilation and Heating Efficiency
(IVHE)), 3.2.29 (Non-standard Ducted Condenser Fan), 3.2.31.2
(Boost2 Heating Operating Level (B2)), 3.2.34 (Power Correction
Capacitor), 3.2.35 (Powered Exhaust Air Fan), 3.2.36 (Powered Return
Air Fan), 3.2.37 (Process Heat Recovery, Reclaim, or Thermal Storage
Coil), 3.2.38 (Published Rating), 3.2.41 (Refrigerant Reheat Coil),
3.2.42 (Single Package Air-conditioner), 3.2.43 (Single Package Heat
Pumps), 3.2.44 (Single Package System), 3.2.45 (Sound Trap), 3.2.46
(Split System), 3.2.51 (Steam or Hydronic Heat Coils), 3.2.53 (UV
Lights), 3.2.55 (Ventilation Energy Recovery System (VERS)), 3.2.56
(Year Round Single Package Air-conditioner), 3.2.57 (Year Round
Single Package Heat Pump),
(d) Subsection 5.2 (Optional System Features) of section 5 Test
Requirements is inapplicable,
(e) The following subsections of section 6 Rating Requirements
are inapplicable: 6.4 (Rating Values), 6.5 (Uncertainty), and 6.6
(Verification Testing),
(f) Section 7 Minimum Data Requirements for Published Ratings is
inapplicable,
(g) Section 8 Operating Requirements is inapplicable,
(h) Section 9 Marking and Nameplate Data is inapplicable,
(i) Section 10 Conformance Conditions is inapplicable,
(j) Appendix B References--Informative is inapplicable,
(k) Sections D.1 (Purpose) and D.2 (Configuration Requirements)
of Appendix D Unit Configuration for Standard Efficiency
Determination--Normative are inapplicable,
(l) Appendix F International Rating Conditions--Normative is
inapplicable,
(m) Appendix G Example of Determination of Fan and Motor
Efficiency for Non-standard Integrated Indoor Fan and Motors--
Informative is inapplicable, and
(n) Appendix H Determination of Low-temperature Cut-in and Cut-
out Temperatures--Normative is inapplicable.
1.2. ANSI/ASHRAE 37-2009:
(a) Section 1 Purpose is inapplicable
(b) Section 2 Scope is inapplicable, and
(c) Section 4 Classifications is inapplicable.
2. General
For air conditioners and heat pumps, determine IVEC and IVHE (as
applicable) in accordance with this appendix and the applicable
sections of AHRI 1340-2023 and ANSI/ASHRAE 37-2009. Representations
of energy efficiency ratio 2 (EER2) and IVHEC may
optionally be made. Representations of coefficient of performance 2
(COP2) at 5 [deg]F, 17 [deg]F, and 47 [deg]F may optionally be made.
Sections 3 and 4 of this appendix provide additional
instructions for testing. In cases where there is a conflict, the
language of this appendix takes highest precedence, followed by AHRI
1340-2023, followed by ANSI/ASHRAE 37-2009. Any subsequent amendment
to a referenced document by the standard-setting organization will
not affect the test procedure in this appendix, unless and until the
test procedure is amended by DOE.
3. Test Conditions
The following conditions specified in AHRI 1340-2023 apply when
testing to certify to the energy conservation standards in Sec.
431.97. For cooling mode, use the rating conditions in Table 7 of
AHRI 1340-2023. For heat pump heating mode tests, use the rating
conditions in Table 23 of AHRI 1340-2023 and the IVHE building load
profile in Table 22 of AHRI 1340-2023.
Representations of EER2 made using the ``Cooling Bin A''
conditions in Table 7 of AHRI 1340-2023 are optional.
Representations of IVHEC made using the IVHEC
Cold Climate building load profile in Table 22 of AHRI 1340-2023 are
optional. Representations of COP247, COP217,
and COP25 are optional.
4. Tower Fan and Pump Power Rate (TFPPR)
Where equations 8, 10, 11, and 13 to AHRI 1340-2023 call for
using the cooling tower fan and condenser water pump power rate
(TFPPR) for the cooling bin specified in Table 7 to AHRI 1340-2023,
instead use the TFPPR value for the cooling bin specified in table 1
to this appendix. Where equation 22 to AHRI 1340-2023 calls for
using a value of 0.0094 W/(Btu/h) for TFPPR, instead use a value of
0.0102 W/(Btu/h).
[[Page 44048]]
Table 1--Tower Fan and Pump Power Rate
[TFPPR]
----------------------------------------------------------------------------------------------------------------
Cooling bin Cooling Bin A Cooling Bin B Cooling Bin C Cooling Bin D
----------------------------------------------------------------------------------------------------------------
Tower Fan and Pump Power Rate (TFPPR), W/ 0.0102 0.0099 0.0121 0.0430
(Btu/h)....................................
----------------------------------------------------------------------------------------------------------------
5. Additional Heating Operating Level Provisions
5.1. Boost2 Heating Operating Level Definition
In place of the boost2 heating operating level definition in
section 3.2.31.2 of AHRI 1340-2023, use the following definition: An
operating level allowed by the controls at 5.0 [deg]F outdoor dry-
bulb temperature with a capacity at 5.0 [deg]F outdoor dry-bulb
temperature that is less than or equal to the maximum capacity
allowed by the controls at 5.0 [deg]F outdoor dry-bulb temperature
and greater than the capacity of:
(a) The boost heating operating level at 5.0 [deg]F outdoor dry-
bulb temperature, if there is an operating level that meets the
definition for boost heating operating level specified in section
3.2.31.1 of AHRI 1340-2023; or
(b) The high heating operating level at 5.0 [deg]F outdoor dry-
bulb temperature, if there is not an operating level that meets the
definition for boost heating operating level specified in section
3.2.31.1 of AHRI 1340-2023.
5.2. Requirements for H5B2 Test in Table 23 to AHRI 1340-2023
In place of the third to last paragraph of section 6.3.6 of AHRI
1340-2023, use the following provisions.
Run the H5B2 test in Table 23 of AHRI 1340-2023 only if there is
an operating level allowed by the controls at 5.0 [deg]F that meets
the definition of the boost2 heating operating level specified in
section 5.1 of this appendix, and the H5B2 test is being used to
determine the capacity at 5.0 [deg]F outdoor dry-bulb temperature
and/or COP25.
If the unit has a boost heating operating level, run the H5B2
test in Table 23 of AHRI 1340-2023 with an operating level allowed
by the controls at 5.0 [deg]F outdoor dry-bulb temperature that has
a capacity at 5.0 [deg]F outdoor dry-bulb temperature that is
greater than the capacity of the boost heating operating level at
5.0 [deg]F outdoor dry-bulb temperature and less than or equal to
the maximum capacity allowed by the controls at 5.0 [deg]F outdoor
dry-bulb temperature.
If the unit does not have a boost heating operating level, run
the H5B2 test in Table 23 of AHRI 1340-2023 with an operating level
allowed by the controls at 5.0 [deg]F outdoor dry-bulb temperature
that has a capacity at 5.0 [deg]F outdoor dry-bulb temperature that
is greater than the capacity of the high heating operating level at
5.0 [deg]F outdoor dry-bulb temperature and less than or equal to
the maximum capacity allowed by the controls at 5.0 [deg]F outdoor
dry-bulb temperature. Use the indoor airflow that is used by the
controls at 5.0 [deg]F outdoor dry-bulb temperature when operating
at the chosen operating level.
The H5B2 test shall not be used in the calculation of IVHE or
IVHEC.
5.3. Operating Level Requirements for COP2
Any references to COP2H in AHRI 1340-2023 shall be
considered synonymous with COP2 as defined in Sec. 431.92. In place
of section 6.3.14.2 of AHRI 1340-2023, use the following provisions.
To determine COP247, use capacity and power
determined for the H47H test.
To determine COP217, the following provisions apply.
For units without a boost heating operating level, use capacity and
power determined for the H17H test. For units with a boost operating
level, use capacity and power determined for the H17B test.
To determine COP25, the following provisions apply.
For units without a boost heating operating level and without a
boost2 heating operating level, use capacity and power determined
for the H5H test. For units with a boost heating operating level and
without a boost2 heating operating level, use capacity and power
determined for the H5B test. For units with a boost2 heating
operating level, use capacity and power determined for the H5B2
test.
6. Set-Up and Test Provisions for Specific Components
When testing equipment that includes any of the features listed
in table 2 to this appendix, test in accordance with the set-up and
test provisions specified in table 2.
Table 2--Test Provisions for Specific Components
------------------------------------------------------------------------
Component Description Test provisions
------------------------------------------------------------------------
Air Economizers................ An automatic system For any air
that enables a economizer that
cooling system to is factory-
supply outdoor air installed, place
to reduce or the economizer in
eliminate the need the 100% return
for mechanical position and
cooling during close and seal
mild or cold the outside air
weather dampers for
testing. For any
modular air
economizer
shipped with the
unit but not
factory-
installed, do not
install the
economizer for
testing.
Barometric Relief Dampers...... An assembly with For any barometric
dampers and means relief dampers
to automatically that are factory-
set the damper installed, close
position in a and seal the
closed position dampers for
and one or more testing. For any
open positions to modular
allow venting barometric relief
directly to the dampers shipped
outside a portion with the unit but
of the building not factory-
air that is installed, do not
returning to the install the
unit, rather than dampers for
allowing it to testing.
recirculate to the
indoor coil and
back to the
building
Desiccant Dehumidification An assembly that Disable desiccant
Components. reduces the dehumidification
moisture content components for
of the supply air testing.
through moisture
transfer with
solid or liquid
desiccants
Drain Pan Heaters.............. A heater that heats Disconnect drain
the drain pan to pan heaters for
make certain that testing.
water shed from
the outdoor coil
during a defrost
does not freeze
Evaporative Pre-cooling of Air- Water is evaporated Disconnect the
cooled Condenser Intake Air. into the air unit from a water
entering the air- supply for
cooled condenser testing i.e.,
to lower the dry- operate without
bulb temperature active
and thereby evaporative
increase cooling.
efficiency of the
refrigeration
cycle
[[Page 44049]]
Fire/Smoke/Isolation Dampers... A damper assembly For any fire/smoke/
including means to isolation dampers
open and close the that are factory-
damper mounted at installed, set
the supply or the dampers in
return duct the fully open
opening of the position for
equipment testing. For any
modular fire/
smoke/isolation
dampers shipped
with the unit but
not factory-
installed, do not
install the
dampers for
testing.
Fresh Air Dampers.............. An assembly with For any fresh air
dampers and means dampers that are
to set the damper factory-
position in a installed, close
closed and one and seal the
open position to dampers for
allow air to be testing. For any
drawn into the modular fresh air
equipment when the dampers shipped
indoor fan is with the unit but
operating not factory-
installed, do not
install the
dampers for
testing.
Hail Guards.................... A grille or similar Remove hail guards
structure mounted for testing.
to the outside of
the unit covering
the outdoor coil
to protect the
coil from hail,
flying debris and
damage from large
objects
High-Effectiveness Indoor Air Indoor air filters Test with the
Filtration. with greater air standard filter.
filtration
effectiveness than
the filters used
for testing
Power Correction Capacitors.... A capacitor that Remove power
increases the correction
power factor capacitors for
measured at the testing.
line connection to
the equipment
Process Heat recovery/Reclaim A heat exchanger Disconnect the
Coils/Thermal Storage. located inside the heat exchanger
unit that from its heat
conditions the source for
equipment's supply testing.
air using energy
transferred from
an external source
using a vapor,
gas, or liquid
Refrigerant Reheat Coils....... A heat exchanger De-activate
located downstream refrigerant
of the indoor coil reheat coils for
that heats the testing so as to
supply air during provide the
cooling operation minimum (none if
using high possible) reheat
pressure achievable by the
refrigerant in system controls.
order to increase
the ratio of
moisture removal
to cooling
capacity provided
by the equipment
Steam/Hydronic Heat Coils...... Coils used to Test with steam/
provide hydronic heat
supplemental coils in place
heating but providing no
heat.
UV Lights...................... A lighting fixture Turn off UV lights
and lamp mounted for testing.
so that it shines
light on the
indoor coil, that
emits ultraviolet
light to inhibit
growth of
organisms on the
indoor coil
surfaces, the
condensate drip
pan, and/other
locations within
the equipment
Ventilation Energy Recovery An assembly that For any VERS that
System (VERS). preconditions is factory-
outdoor air installed, place
entering the the VERS in the
equipment through 100% return
direct or indirect position and
thermal and/or close and seal
moisture exchange the outside air
with the exhaust dampers and
air, which is exhaust air
defined as the dampers for
building air being testing, and do
exhausted to the not energize any
outside from the VERS
equipment subcomponents
(e.g., energy
recovery wheel
motors). For any
VERS module
shipped with the
unit but not
factory-
installed, do not
install the VERS
for testing.
------------------------------------------------------------------------
[FR Doc. 2024-08543 Filed 5-17-24; 8:45 am]
BILLING CODE 6450-01-P