Energy Conservation Program: Test Procedure for Computer Room Air Conditioners, 21816-21842 [2023-06760]
Download as PDF
21816
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE–2021–BT–TP–0017]
RIN 1904–AE45
Energy Conservation Program: Test
Procedure for Computer Room Air
Conditioners
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
The U.S. Department of
Energy (‘‘DOE’’) is publishing a final
rule to amend its test procedure for
computer room air conditioners
(‘‘CRACs’’). DOE is incorporating by
reference the latest version of the
relevant industry consensus test
standard, AHRI 1360–2022. DOE is also
adopting the net sensible coefficient of
performance (‘‘NSenCOP’’) metric in its
test procedures for CRACs.
Additionally, DOE is amending certain
provisions for representations and
enforcement.
SUMMARY:
The effective date of this rule is
May 11, 2023. The final rule changes
will be mandatory for CRAC equipment
testing starting April 5, 2024. The
incorporation by reference of certain
materials listed in this rule is approved
by the Director of the Federal Register
on May 11, 2023.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at www.regulations.gov under
docket number EERE–2021–BT–TP–
0017. All documents in the docket are
listed in the www.regulations.gov index.
However, not all documents listed in
the index may be publicly available,
such as those containing information
that is exempt from public disclosure.
A link to the docket web page can be
found at: www.regulations.gov/docket/
EERE-2021-BT-TP-0017. The docket
web page contains instructions on how
to access all documents, including
public comments, in the docket.
For further information on how to
review the docket, contact the
Appliance and Equipment Standards
Program staff at (202) 287–1445 or by
email: ApplianceStandardsQuestions@
ee.doe.gov.
lotter on DSK11XQN23PROD with RULES3
DATES:
FOR FURTHER INFORMATION CONTACT:
Ms. Catherine Rivest, U.S. Department
of Energy, Office of Energy Efficiency
and Renewable Energy, Building
Technologies Office, EE–5B, 1000
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
Independence Avenue SW, Washington,
DC 20585–0121. Telephone: (202) 586–
7335. Email:
ApplianceStandardsQuestions@
ee.doe.gov.
Mr. Eric Stas, U.S. Department of
Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue SW,
Washington, DC 20585–0121.
Telephone: (202) 586–5827. Email:
Eric.Stas@hq.doe.gov.
SUPPLEMENTARY INFORMATION: DOE
incorporates by reference the following
industry standards:
AHRI Standard 1360–2022 (I–P),
‘‘2022 Standard for Performance Rating
of Computer and Data Processing Room
Air Conditioners’’, copyright 2022
(‘‘AHRI 1360–2022’’) into parts 429 and
431.
ANSI/ASHRAE Standard 37–2009,
‘‘Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment,’’ approved June 24, 2009
(‘‘ANSI/ASHRAE 37–2009’’) into part
431.
ASHRAE Standard 127–2007,
‘‘Method of Testing for Rating Computer
and Data Processing Room Unitary Air
Conditioners’’, approved June 28, 2007
(‘‘ANSI/ASHRAE 127–2007’’) into part
431.
ANSI/ASHRAE 127–2020, ‘‘Method of
Testing for Rating Air-Conditioning
Units Serving Data Center (DC) and
Other Information Technology
Equipment (ITE) Spaces’’, ANSIapproved November 30, 2020 (‘‘ANSI/
ASHRAE 127–2020’’) into part 431.
Copies of AHRI 1360–2022 can be
obtained from the Air-Conditioning,
Heating, and Refrigeration Institute
(‘‘AHRI’’), 2311 Wilson Blvd., Suite 400,
Arlington, VA 22201, (703) 524–8800, or
online at: www.ahrinet.org.
Copies of ANSI/ASHRAE 37–2009,
ANSI/ASHRAE 127–2007, and ANSI/
ASHRAE 127–2020, can be obtained
from the American National Standards
Institute (‘‘ANSI’’), 25 W 43rd Street,
4th Floor, New York, NY 10036, (212)
642–4900, or online at:
webstore.ansi.org/.
For a further discussion of these
standards, see section IV.N of this
document.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Scope of Applicability
B. Revised Organization of the CRAC Test
Procedure
C. Updates to Industry Test Standards
D. Definitions
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
1. CRAC Definition
2. CRAC Configuration Definitions
E. Metric
1. NSenCOP
2. Integrated Efficiency Metric
3. Part-Load Operation and Air Circulation
Mode
4. Controls Verification Procedure
F. Configuration of Unit Under Test
1. Background and Summary
2. Approach for Exclusion of Certain
Components
3. Non-Standard Indoor Fan Motors
G. Represented Values
1. Multiple Refrigerants
2. Net Sensible Cooling Capacity
3. Validation Class for Glycol-Cooled
CRACs
H. Effective and Compliance Dates
I. Test Procedure Costs
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866
and 13563
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by
Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Small, large, and very large
commercial package air conditioning
and heating equipment are included in
the list of ‘‘covered equipment’’ for
which the U.S. Department of Energy
(‘‘DOE’’) is authorized to establish and
amend energy conservation standards
and test procedures. (42 U.S.C.
6311(1)(B)–(D)) Commercial package air
conditioning and heating equipment
includes computer room air
conditioners (‘‘CRACs’’) as an
equipment category. DOE’s test
procedures for CRACs are currently
prescribed at title 10 of the Code of
Federal Regulations (‘‘CFR’’), Table 1 to
§ 431.96. The following sections discuss
DOE’s authority to establish and amend
test procedures for CRACs and relevant
background information regarding
DOE’s consideration of amendments to
the test procedures for this equipment.
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
A. Authority
The Energy Policy and Conservation
Act, as amended (‘‘EPCA’’),1 among
other things, authorizes DOE to regulate
the energy efficiency of a number of
consumer products and certain
industrial equipment. (42 U.S.C. 6291–
6317) Title III, Part C 2 of EPCA, Public
Law 94–163 (42 U.S.C. 6311–6317, as
codified), added by Public Law 95–619,
Title IV, section 441(a), established the
Energy Conservation Program for
Certain Industrial Equipment, which
sets forth a variety of provisions
designed to improve energy efficiency.
This covered equipment includes small,
large, and very large commercial
package air conditioning and heating
equipment. (42 U.S.C. 6311(1)(B)–(D))
Commercial package air conditioning
and heating equipment includes CRACs,
which are the subject of this final rule.
The energy conservation program
under EPCA consists essentially of four
parts: (1) testing, (2) labeling, (3) Federal
energy conservation standards, and (4)
certification and enforcement
procedures. Relevant provisions of
EPCA include definitions (42 U.S.C.
6311), energy conservation standards
(42 U.S.C. 6313), test procedures (42
U.S.C. 6314), labeling provisions (42
U.S.C. 6315), and the authority to
require information and reports from
manufacturers (42 U.S.C. 6316).
The Federal testing requirements
consist of test procedures that
manufacturers of covered equipment
must use as the basis for: (1) certifying
to DOE that their equipment complies
with the applicable energy conservation
standards adopted pursuant to EPCA (42
U.S.C. 6316(b); 42 U.S.C. 6296), and (2)
making other representations about the
efficiency of that equipment (42 U.S.C.
6314(d)). Similarly, DOE uses these test
procedures to determine whether the
equipment complies with relevant
standards promulgated under EPCA.
Federal energy efficiency
requirements for covered equipment
established under EPCA generally
supersede State laws and regulations
concerning energy conservation testing,
labeling, and standards. (42 U.S.C.
6316(a) and (b); 42 U.S.C. 6297) DOE
may, however, grant waivers of Federal
preemption in limited circumstances for
particular State laws or regulations, in
accordance with the procedures and
other provisions of EPCA. (42 U.S.C.
6316(b)(2)(D))
1 All references to EPCA in this document refer
to the statute as amended through the Energy Act
of 2020, Public Law 116–260 (Dec. 27, 2020), which
reflect the last statutory amendments that impact
Parts A and A–1 of EPCA.
2 For editorial reasons, upon codification in the
U.S. Code, Part C was redesignated Part A–1.
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
Under 42 U.S.C. 6314, EPCA also sets
forth the criteria and procedures DOE
must follow when prescribing or
amending test procedures for covered
equipment. Specifically, EPCA requires
that any test procedures prescribed or
amended under this section must be
reasonably designed to produce test
results which reflect energy efficiency,
energy use, or estimated annual
operating cost of a given type of covered
equipment (or class thereof) during a
representative average use cycle and
requires that test procedures not be
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
EPCA requires that the test
procedures for commercial package air
conditioning and heating equipment (of
which CRACs are a category) be those
generally accepted industry testing
procedures or rating procedures
developed or recognized by the AirConditioning, Heating and Refrigeration
Institute (‘‘AHRI’’) or by the American
Society of Heating, Refrigerating, and
Air-Conditioning Engineers
(‘‘ASHRAE’’), as referenced in ASHRAE
Standard 90.1, ‘‘Energy Standard for
Buildings Except Low-Rise Residential
Buildings’’ (‘‘ASHRAE Standard 90.1’’).
(42 U.S.C. 6314(a)(4)(A)) Further, if such
an industry test procedure is amended,
DOE must update its test procedure to
be consistent with the amended
industry test procedure, unless DOE
determines, by rule published in the
Federal Register and supported by clear
and convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B))
EPCA also requires that, at least once
every seven years, DOE evaluate test
procedures for each type of covered
equipment, including CRACs, to
determine whether amended test
procedures would more accurately or
fully comply with the requirements for
the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 6314(a)(1)–(3))
In addition, if DOE determines that a
test procedure amendment is warranted,
the Department must publish proposed
test procedures in the Federal Register
and afford interested persons an
opportunity (of not less than 45 days’
duration) to present oral and written
data, views, and arguments on the
proposed test procedures. (42 U.S.C.
6314(b)) If DOE determines that test
procedure revisions are not appropriate,
DOE must publish in the Federal
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
21817
Register its determination not to amend
the test procedures. (42 U.S.C.
6314(a)(1)(A)(ii))
DOE is publishing this final rule
amending the test procedure for CRACs
in satisfaction of its aforementioned
obligations under EPCA.
B. Background
On May 16, 2012, DOE published a
final rule in the Federal Register,
which, in relevant part, adopted test
procedures for CRACs that incorporate
by reference American National
Standards Institute (‘‘ANSI’’)/ASHRAE
Standard 127–2007, ‘‘Method of Testing
for Rating Computer and Data
Processing Room Unitary Air
Conditioners’’ (‘‘ANSI/ASHRAE 127–
2007’’), which was the industry test
procedure referenced in ASHRAE
Standard 90.1–2010 for CRACs, as the
basis for the Federal test procedure for
such equipment. 77 FR 28928, 28989.
On October 26, 2016, ASHRAE
published ASHRAE Standard 90.1–
2016, which included updates to the
test procedure (‘‘TP’’) references for
CRACs as compared to ASHRAE
Standard 90.1–2010 and ASHRAE
Standard 90.1–2013.3 This action by
ASHRAE triggered DOE’s obligations
under 42 U.S.C. 6314(a)(4)(B), as
outlined previously. Accordingly, DOE
published a request for information
(‘‘RFI’’) in the Federal Register on July
25, 2017 (‘‘July 2017 ASHRAE TP RFI’’)
to collect information and data in
consideration of amendments to DOE’s
test procedures for commercial package
air conditioning and heating equipment,
given the test procedure updates
included in ASHRAE Standard 90.1–
2016. 82 FR 34427. Following the July
2017 ASHRAE TP RFI, AHRI published
additional updates to its test procedure
standard for CRACs on December 21,
2017 (i.e., AHRI Standard 1360–2017,
‘‘2017 Standard for Performance Rating
of Computer and Data Processing Room
Air Conditioners’’ (‘‘AHRI 1360–
2017’’)). ASHRAE published ASHRAE
Standard 90.1–2019 on October 24,
2019, which updated the test procedure
referenced for CRACs from AHRI 1360–
2016 to AHRI 1360–2017 and added
equipment classes for ceiling-mounted
CRACs. Following the publication of
ASHRAE Standard 90.1–2019, AHRI
initiated work on an update to AHRI
Standard 1360 (i.e., AHRI Standard
1360–202X Draft, ‘‘Performance Rating
of Computer and Data Processing Room
3 More specifically, ASHRAE Standard 90.1–2016
references AHRI 1360–2016, ‘‘Standard for
Performance Rating of Computer and Data
Processing Room Air Conditioners’’ for CRACs.
E:\FR\FM\11APR3.SGM
11APR3
21818
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
Air Conditioners (‘‘Draft Standard’’)’’
(‘‘AHRI 1360–202X Draft’’).
On February 7, 2022, DOE published
in the Federal Register a notice of
proposed rulemaking (‘‘NOPR’’)
(‘‘February 2022 NOPR’’) proposing, in
relevant part, to update the Federal test
procedure for CRACs consistent with
AHRI 1360–202X Draft. 87 FR 6948. A
copy of the draft was added to the
docket for this rulemaking for review by
interested parties.4 As stated in the
February 2022 NOPR, if AHRI were to
publish a final version of AHRI 1360–
202X Draft prior to DOE publishing a
final rule, DOE’s intention would be to
reference the latest version of AHRI
1360 in the final rule. 87 FR 6948, 6951
(Feb. 7. 2022). DOE held a public
meeting webinar on March 15, 2022, to
discuss the proposed amendments to
the CRACs test procedure presented in
the February 2022 NOPR.
DOE received several comments in
response to the February 2022 NOPR.
Table I.1 lists the commenters, along
with each commenter’s abbreviated
name used throughout the final rule.
Discussion of these comments, along
with DOE’s responses, are provided in
the appropriate sections of this
document.
lotter on DSK11XQN23PROD with RULES3
TABLE I.1—LIST OF COMMENTERS WITH WRITTEN SUBMISSIONS IN RESPONSE TO THE FEBRUARY 2022 NOPR
Commenter(s)
Abbreviation used in this final
rule
Comment No.
in the docket
Air-Conditioning, Heating and Refrigeration Institute ...............
Appliance Standards Awareness Project, American Council
for an Energy-Efficient Economy, Natural Resources Defense Council and New York State Energy Research and
Development Authority.
Northwest Energy Efficiency Alliance .......................................
AHRI 5 .....................................
Joint Advocates ......................
9
7
Industry Trade Organization.
Efficiency Advocacy Organizations.
NEEA ......................................
5
Pacific Gas and Electric Company (‘‘PG&E’’), San Diego Gas
and Electric, and Southern California Edison; collectively,
the California Investor-Owned Utilities.
CA IOUs ..................................
6
Efficiency Advocacy Organization.
Utilities.
Commenter type
A parenthetical reference at the end of
a comment quotation or paraphrase
provides the location of the item in the
public record.6 To the extent that
interested parties have provided written
comments that are substantively similar
to any oral comments provided during
the March 15, 2022 NOPR public
meeting, DOE cites the written
comments throughout this final rule.
Any oral comments provided during the
webinar that are substantively distinct
from a submitter’s written comments are
summarized and cited separately
throughout this final rule.7
On March 7, 2022, DOE published in
the Federal Register a NOPR proposing
revised energy conservation standards
(‘‘March 2022 ECS NOPR’’) for CRACs
in terms of net sensible coefficient of
performance (‘‘NSenCOP’’). 87 FR
12802. DOE conducted a crosswalk
analysis to translate the current Federal
standards in terms of sensible
coefficient of performance (‘‘SCOP’’) to
equivalent levels in terms of NSenCOP
to evaluate potential amendments to the
energy conservation standards, as
appropriate. Id. at 87 FR 12817–12826.
Any comments received in response to
the February 2022 NOPR that pertain to
energy conservation standards will be
addressed in the energy conservation
standards rulemaking and are not
addressed in this document.
In November, 2022, AHRI finalized
AHRI 1360–202X Draft without
substantial change and published AHRI
Standard 1360–2022, ‘‘Performance
Rating of Computer and Data Processing
Room Air Conditioners (‘‘AHRI 1360–
2022’’).
In January 2023, ASHRAE published
the 2022 edition of ASHRAE Standard
90.1, ‘‘Energy Standard for Buildings
Except Low-Rise Residential Buildings’’
(‘‘ASHRAE Standard 90.1–2022’’).
ASHRAE Standard 90.1–2022 maintains
AHRI 1360–2017 as the referenced test
procedure reference for CRACs.
II. Synopsis of the Final Rule
In this final rule, DOE is updating its
regulations for CRACs by: (1)
incorporating by reference the updated
version of AHRI Standard 1360 (i.e.,
AHRI 1360–2022), as well as the
relevant industry test standards
referenced in AHRI 1360–2022; (2)
establishing provisions for determining
NSenCOP for CRACs; (3) clarifying the
definition of a ‘‘computer room air
conditioner’’ to include consideration of
how the equipment is marketed; and (4)
amending certain provisions for
representations and enforcement in 10
CFR part 429, consistent with the
changes adopted in the test procedure.
In terms of implementation, DOE is
adding new appendices E and E1 to
subpart F of 10 CFR part 431, ‘‘Uniform
test method for measuring the energy
consumption of computer room air
conditioners,’’ (‘‘appendix E’’ and
‘‘appendix E1,’’ respectively). The
current DOE test procedure for CRACs
is being relocated to appendix E without
change, and the new test procedure
incorporating by reference AHRI 1360–
2022 is being established in appendix
E1 for determining NSenCOP. Testing in
accordance with appendix E1 is not
required until such time as compliance
is required with amended energy
conservation standards for CRACs that
rely on NSenCOP, should DOE adopt
such standards. After such time,
appendix E will no longer be used as
part of the Federal test procedure.
The adopted amendments are
summarized in Table II.1 and compared
to the relevant test procedure provisions
in place prior to the amendment, as well
as the reason for the adopted change.
4 The AHRI 1360–202X Draft test procedure is
available in the docket for this rulemaking at:
www.regulations.gov/document/EERE-2021-BT-TP0017-0001.
5 AHRI’s comment was received 23 days after the
comment submission deadline.
6 The parenthetical reference provides a reference
for information located in the docket of DOE’s
rulemaking to develop test procedures for CRACs.
(Docket No. EERE–2021–BT–TP–0017, which is
maintained at www.regulations.gov.) The references
are arranged as follows: (commenter name,
comment docket ID number, page of that
document).
7 The March 15, 2022 TP NOPR Public Meeting
Transcript can be found in the docket for this
rulemaking at: www.regulations.gov under entry
number EERE–2021–BT–TP–0017–0008. Comments
arising from the public meeting are cited as follows:
(commenter name, Public Meeting Transcript, No.
8 at p. X).
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
21819
TABLE II.1—SUMMARY OF CHANGES IN THE AMENDED CRACS TEST PROCEDURE RELATIVE TO CURRENT TEST
PROCEDURE
DOE test procedure prior to amendment
Amended test procedure
Located in 10 CFR 431.96 .................................
Current test procedure unchanged but relocated to appendix E.
Incorporates by reference in a new appendix
E1—AHRI 1360–2022, ANSI/ASHRAE
127–2020, and ANSI/ASHRAE 37–2009.
Includes provisions for determining NSenCOP
in appendix E1.
CRAC definition criteria include: (1) marketed
for use in computer rooms (or similar applications); and (2) not a consumer product.
Improve readability.
Defines roof, wall, and ceiling-mounted CRAC
configurations and provides test provisions
specific to such units.
Includes provisions in 10 CFR 429.43 specific
to CRACs to determine represented values
for models with specific components and
prevent cooling capacity over-rating.
Adopts product-specific enforcement provisions for CRACs regarding verification of
cooling capacity and testing of units with
specific components.
Updates to the applicable industry test procedures.
Incorporates by reference ANSI/ASHRAE 127–
2007.
Includes provisions for determining SCOP ........
CRAC definition criteria include: (1) used in
computer rooms (or similar applications); (2)
whether rated for SCOP and tested in accordance with 10 CFR 431.96; and (3) not a
consumer product.
Does not specify provisions specific to testing
roof, wall, and ceiling-mounted CRAC units.
Does not include CRAC-specific provisions for
determination of represented values in 10
CFR 429.43.
Does not include CRAC-specific enforcement
provisions in 10 CFR 429.134.
lotter on DSK11XQN23PROD with RULES3
DOE has determined that the
amendments described in section III of
this final rule regarding the
establishment of appendix E do not alter
the measured efficiency of CRACs or
require retesting solely as a result of
DOE’s adoption of the amendments to
the test procedure. DOE has determined,
however, that the test procedure
amendments in appendix E1 do alter the
measured efficiency of CRACs and that
such amendments are consistent with
the updated industry test procedure.
Further, use of appendix E1 and the
amendments to the representation
requirements in 10 CFR 429.43 are not
required until the compliance date of
any amended standards denominated in
terms of NSenCOP, if adopted.
However, manufacturers may use
appendix E1 to certify compliance with
any amended standards prior to the
applicable compliance date for those
standards. Additionally, DOE has
determined that the finalized
amendments will not increase the cost
of testing. The effective date for the
amended test procedures adopted in
this final rule is 30 days after
publication of this document in the
Federal Register. Detailed discussion of
DOE’s actions is included in section III
of this final rule.
III. Discussion
A. Scope of Applicability
DOE currently defines ‘‘computer
room air conditioner’’ as a basic model
of commercial package air-conditioning
and heating equipment (packaged or
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
split) that is: used in computer rooms,
data processing rooms, or other
information technology cooling
applications; rated for SCOP and tested
in accordance with 10 CFR 431.96; and
is not a covered consumer product
under 42 U.S.C. 6291(1)–(2) and 42
U.S.C. 6292. A CRAC may be provided
with, or have as available options, an
integrated humidifier, temperature and/
or humidity control of the supplied air,
and reheating function. 10 CFR 431.92.
DOE did not receive any comments from
stakeholders regarding any revision of
scope for this rulemaking.
As discussed in section III.D.1 of this
document, DOE is amending the
definition of CRAC in this final rule.
Specifically, DOE is revising the
definition of ‘‘computer room air
conditioner’’ to mean commercial
package air conditioning and heating
equipment (packaged or split) that is:
marketed for use in computer rooms,
data processing rooms, or other
information technology cooling
applications and not a covered
consumer product under 42 U.S.C.
6291(1)–(2) and 6292. A computer room
air conditioner may be provided with,
or have as available options, an
integrated humidifier, temperature and/
or humidity control of the supplied air,
and reheating function. Computer room
air conditioners include, but are not
limited to, the following configurations
as defined in 10 CFR 431.92: downflow, horizontal-flow, up-flow ducted,
up-flow non-ducted, ceiling-mounted
ducted, ceiling mounted non-ducted,
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
Attribution
Updates to the applicable industry test procedures.
Updates to the applicable industry test procedures.
To more clearly define CRACs and distinguish
from other equipment categories.
Establish CRAC-specific provisions for determination of represented values.
Establish provisions for DOE enforcement
testing of CRACs.
roof-mounted, and wall-mounted. The
scope of the CRAC test procedure, as
amended by this final rule, is based on
this revised definition.
B. Revised Organization of the CRAC
Test Procedure
In the February 2022 NOPR, DOE
proposed to relocate and centralize the
current test procedure for CRACs to a
new appendix E to subpart F of 10 CFR
part 431, without change. 87 FR 6948,
6952 (Feb. 7, 2022). As proposed,
appendix E would continue to reference
ANSI/ASHRAE 127–2007 and provide
instructions for determining SCOP. Id.
As proposed, CRACs would be required
to be tested according to appendix E
until such time as compliance is
required with amended energy
conservation standards that rely on the
NSenCOP metric, should DOE adopt
such standards. Id.
Accordingly, in parallel, DOE
proposed to establish an amended test
procedure for CRACs that adopted the
substance of AHRI 1360–202X Draft in
a new appendix E1 to subpart F of 10
CFR part 431. Id. DOE noted that it
intended to incorporate by reference the
final published version of AHRI 1360–
202X Draft in the final rule, unless there
were substantive changes between the
draft and published versions, in which
case DOE may adopt the substance of
AHRI 1360–202X Draft or provide
additional opportunity for comment on
changes presented in the final version of
the industry consensus test standard. Id.
DOE noted that CRACs would not be
E:\FR\FM\11APR3.SGM
11APR3
21820
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
required to be tested according to the
test procedure in appendix E1 until
such time as compliance is required
with amended energy conservation
standards that rely on the NSenCOP
metric, should DOE adopt such
standards. Id.
DOE did not receive any comments in
response to the February 2022 NOPR’s
proposed reorganization of the test
procedure. As discussed in the
following sections of this final rule,
DOE is adopting the finalized version of
AHRI 1360 (i.e., AHRI 1360–2022),
including the NSenCOP metric. AHRI
1360–2022 does not include any
significant revisions as compared to
AHRI 1360–202X Draft Accordingly, for
the reasons discussed in the February
2022 NOPR and as discussed in the
preceding paragraphs, DOE is finalizing
the proposed reorganization of the test
procedure by establishing appendices E
and E1 for testing CRACs.
lotter on DSK11XQN23PROD with RULES3
C. Updates to Industry Test Standards
As noted previously, DOE’s current
test procedure for CRACs is codified at
10 CFR 431.96 and incorporates by
reference ANSI/ASHRAE Standard 127–
2007,8 which is the test procedure
recognized by ASHRAE Standard 90.1–
2010 for CRACs. However, the 2019 and
2022 versions of ASHRAE Standard 90.1
recognize AHRI 1360–2017 as the test
procedure for CRACs.
After publication of AHRI 1360–2017,
DOE and other stakeholders supported
the AHRI 1360 committee in its process
to further update AHRI Standard 1360,
which culminated in the publication of
AHRI 1360–2022. AHRI 1360–2022
references ANSI/ASHRAE 127–2020,
‘‘Method of Testing for Rating Computer
and Data Processing Room Unitary Air
Conditioners’’ (‘‘ANSI/ASHRAE 127–
2020’’),9 and ANSI/ASHRAE 37–2009,
‘‘Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment’’ (‘‘ANSI/ASHRAE 37–
2009’’). Both AHRI 1360–2017 and
AHRI 1360–2022 include significant
changes from ANSI/ASHRAE 127–2007,
including the use of NSenCOP instead
of SCOP as the test metric. Both
efficiency metrics (NSenCOP and SCOP)
are ratios of net sensible cooling
capacity delivered to the power
consumed, but there are several
8 While ANSI/ASHRAE Standard 127–2007 is
incorporated by reference in its entirety, Table 1 to
10 CFR 431.96 (which defines the applicable test
methods for each category of equipment) excludes
section 5.11 of ANSI/ASHRAE Standard 127–2007
for testing CRACs. The test procedure also includes
additional provisions related to break-in period and
test set-up. See 10 CFR 431.96(c) and (e).
9 ASHRAE published ANSI/ASHRAE Standard
127–2020 on November 30, 2020.
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
differences in the conditions at which
tests are performed. Section III.E.1 of
this final rule includes further
discussion of the differences between
these test metrics.
In the February 2022 NOPR, DOE
proposed to adopt AHRI 1360–202X
Draft and provided a copy of that
industry test standard in the regulatory
docket.10 87 FR 6948, 6952 (Feb. 7,
2022).
In response to the February 2022
NOPR, AHRI commented that the AHRI
1360–202X draft standard was not yet
complete (at the time), and
manufacturers, particularly those of
newly included equipment, had not yet
had an opportunity to evaluate the
impact of this change, nor had the
ASHRAE 90.1 committee. (AHRI, No. 9
at p. 2) AHRI further commented that
DOE does not have the authority to
adopt a test procedure edition not yet
cited in ASHRAE Standard 90.1 as the
national test procedure. Id.
Consequently, AHRI recommended that
DOE should adopt AHRI 1360–2017,
continue to work with AHRI and other
relevant stakeholders to finalize the new
edition of the test procedure, support
the introduction of a proposed
amendment to ASHRAE Standard 90.1,
and then adopt the new procedure as
the national test procedure during the
next rulemaking for these products.
(AHRI, No. 9 at p. 3)
After the publication of the February
2022 NOPR, AHRI 1360–202X Draft was
finalized and issued as AHRI 1360–2022
in November, 2022. AHRI 1360–2022
does not include any significant
deviations from AHRI 1360–202X Draft.
As such, the adoption of AHRI 1360–
2022 in this final rule is consistent with
the proposal to reference AHRI 1360–
202X Draft in the February 2022 NOPR.
AHRI’s concern regarding the draft
status of AHRI 1360–202X Draft no
longer applies, given the subsequent
finalization of the draft and publication
of AHRI 1360–2022. DOE notes that the
Department was heavily involved with
the AHRI 1360 committee, along with
relevant industry stakeholders, to aid in
the development of AHRI 1360–2022.
DOE further notes that AHRI 1360–2022
represents an industry consensus
update to AHRI 1360–2017. DOE
disagrees with AHRI’s argument that it
lacks statutory authority for the
adoption of AHRI 1360–2022, rather
than AHRI 1360–2017, for the reasons
that follow.
With respect to small, large, and very
large commercial package air
conditioning and heating equipment (of
10 See Document No. EERE–2021–BT–TP–0017–
0001 at www.regulations.gov.
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
which CRACs are a category), EPCA
directs that when the generally accepted
industry testing procedures or rating
procedures developed or recognized by
AHRI or by ASHRAE, as referenced in
ASHRAE Standard 90.1, is amended,
the Secretary shall amend the DOE test
procedure consistent with the amended
industry test procedure or rating
procedure unless the Secretary
determines, by clear and convincing
evidence, that to do so would not meet
the requirements for test procedures to
produce results representative of an
average use cycle and is not unduly
burdensome to conduct. (42 U.S.C.
6314(a)(4)(B))
As noted, DOE has a duty under the
statute to adopt a test procedure that
produces results representative of the
covered equipment’s average use cycle.
Here, DOE has concluded, supported by
clear and convincing evidence, that
AHRI 1360–2022 would better meet that
criterion of EPCA than AHRI 1360–
2017. First, AHRI 1360–2022 includes
test provisions for measuring
performance of roof-mounted and wallmounted CRACs, configurations which
are not considered in AHRI 1360–2017.
Were DOE to adopt AHRI 1360–2017
instead of AHRI 1360–2022, the DOE
test procedure would not address
representations for these configurations
in terms of NSenCOP. Second, AHRI
1360–2022 provides clarifications and
additional test requirements on several
test procedure elements, including test
tolerances, enclosure for CRACs with
compressors in indoor units, secondary
verification of capacity, ducted
condensers, and refrigerant charging
instructions. These elements were
discussed in detail in the February 2022
NOPR. See 87 FR 6948, 6960–6963 (Feb.
7, 2022). These additional test
requirements improve the
representativeness of the CRACs test
procedure. For these reasons, DOE
considers AHRI 1360–2022 to be more
representative of CRAC operation than
AHRI 1360–2017. With this finding
made, DOE does not read EPCA as
requiring the Department to dissect the
industry standard and surgically
transplant individual provisions of the
new industry standard into the prior
industry standard. DOE views the
industry test standard as a functioning
whole, so the approach AHRI suggests
could insert errors and inconsistencies
into the industry standard, as would
prevent its proper functioning in
practice as part of the DOE test
procedure. Further, even if AHRI’s
approach were possible, it would be
largely unnecessary; adoption of all the
major provisions of the latest industry
E:\FR\FM\11APR3.SGM
11APR3
lotter on DSK11XQN23PROD with RULES3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
test standard would arguably result in
the remaining provisions being
uncontroversial. Again, DOE would
point out that the test procedure in
question is the most current version of
the industry’s own approved test
procedure, even if ASHRAE Standard
90.1 has not yet caught up with such
change. DOE considered AHRI 1360–
2017, as EPCA requires, but it ultimately
determined that AHRI 1360–2022 would
produce results that better reflect an
average use cycle than would AHRI
1360–2017. DOE has concluded that
EPCA does not allow the Department to
turn a blind eye to such real world
developments.
Furthermore, DOE believes that
Congress foresaw the practical benefits
of a statutory reading consistent with
DOE’s interpretation. Although DOE
recognizes that adopting AHRI 1360–
2022 as the Federal test procedure for
CRACs may create some disharmony
between the Federal test procedure and
the test procedure currently specified in
ASHRAE Standard 90.1 for a period of
time, such situation is arguably
preferable to the alternative in which
DOE and stakeholders would need to
waste significant resources to reinitiate
another rulemaking in short order after
this proceeding to once again amend the
Federal test procedure for CRACs to
update the reference therein from AHRI
1360–2017 to AHRI 1360–2022—the
very same testing standard available for
consideration at the present time.
Finally, DOE notes that manufacturers
are not required to use the test
procedure to certify compliance with
any energy conservation standards for
CRACs until the compliance date
established for such standards
denominated in terms of the NSenCOP
metric, if DOE proceeds to adopt such
standards. The difference in ratings
between measuring SCOP per the
current Federal test procedure and
measuring NSenCOP per the test
procedure adopted in this final rule
(which incorporates by reference AHRI
1360–2022) is addressed in the ongoing
energy conservation standards
rulemaking (see 87 FR 12802 (March 7,
2022)).
Therefore, in light of these updates to
the relevant industry consensus
standards and for the reasons explained,
DOE is amending its test procedure for
CRACs by incorporating by reference
AHRI 1360–2022 for use in the new
appendix E1. Specifically, in the new
test procedure for CRACs at appendix
E1, DOE is adopting sections 3.1, 3.2.2,
3.2.7, 3.2.22, 3.2.25, 3.2.27, 3.2.28,
3.2.37, 3.2.38, 5, 6.1–6.3, 6.6, and 6.8
and Appendices C, E, and F of AHRI
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
1360–2022 for the Federal test
procedure for CRACs.11
In the February 2022 NOPR, DOE
proposed to incorporate by reference
several industry standards that are
internally referenced by AHRI 1360–
202X Draft. First, DOE proposed to
incorporate by reference ANSI/ASHRAE
127–2020. Specifically, in the proposed
test procedure for CRACs at 10 CFR part
431, subpart F, appendix E1, DOE
proposed to reference Figure A–1, Test
duct for measuring air flow and static
pressure on downflow units, of
Appendix A of ANSI/ASHRAE 127–
2020, because Figure A–1 of Appendix
A is referenced in section 5.8 of AHRI
1360–202X Draft. Second, DOE
proposed to incorporate by reference
ANSI/ASHRAE 37–2009 because
section 5, Appendix D, and Appendix E
of AHRI 1360–202X Draft reference
methods of test in ANSI/ASHRAE 37–
2009. More specifically, DOE proposed
to adopt all sections of ANSI/ASHRAE
37–2009, except sections 1, 2, and 4. 87
FR 6948, 6952 (Feb. 7, 2022).
DOE did not receive any comments in
response to its proposal to reference
ANSI/ASHRAE 127–2020 and ANSI/
ASHRAE 37–2009 in the test method for
CRACs. These standards are also
referenced in the finalized standard,
AHRI 1360–2022, which DOE is
incorporating by reference in this final
rule. Therefore, for the reasons
discussed in the preceding paragraphs
and in the February 2022 NOPR, DOE
incorporates by reference ANSI/
ASHRAE 127–2020 and ANSI/ASHRAE
37–2009, and adopts the relevant
sections for testing CRACs, as proposed
in the February 2022 NOPR.
21821
1. CRAC Definition
As discussed, DOE currently defines a
CRAC as a basic model of commercial
package air-conditioning and heating
equipment (packaged or split) that is:
used in computer rooms, data
processing rooms, or other information
technology cooling applications; rated
for SCOP and tested in accordance with
10 CFR 431.96; and is not a covered
consumer product under 42 U.S.C.
6291(1)–(2) and 42 U.S.C. 6292. 10 CFR
431.92. A computer room air
conditioner may be provided with, or
have as available options, an integrated
humidifier, temperature and/or
humidity control of the supplied air,
and reheating function. Id. In defining a
CRAC, DOE was unable to identify
physical characteristics that consistently
distinguish CRACs from other categories
of commercial package air conditioning
and heating equipment that provide
comfort-cooling. See 77 FR 16769,
16772–16774 (March 22, 2012); 77 FR
28928, 28947–28948 (May 16, 2012).
In the February 2022 NOPR, DOE
proposed to amend the CRAC definition
to include how the manufacturer
markets a model for use, consistent with
the definition in the draft industry
standard, AHRI 1360–202X Draft, which
also defines CRACs based on
marketing.12 87 FR 6948, 6952–6954
(Feb. 7, 2022). DOE also proposed to
remove the current wording ‘‘. . . rated
for sensible coefficient of performance
(SCOP) and tested in accordance with
10 CFR 431.96’’ to ensure that a unit
that otherwise meets the definition of a
CRAC would be covered as a CRAC
regardless of how the manufacturer has
tested and rated the model. Id. DOE also
proposed to remove the unnecessary
current wording ‘‘. . . a basic model of’’
to avoid confusion as to whether the
equipment constitutes a basic model—
DOE specifies different basic model
definitions for each equipment category
at 10 CFR 431.92—before the
determination is made whether the
equipment meets the CRAC definition.
Id. Specifically, DOE proposed to define
‘‘computer room air conditioner’’ as
commercial package air conditioning
and heating equipment (packaged or
split) that is: marketed for use in
computer rooms, data processing rooms,
or other information technology cooling
applications; and not a covered
consumer product under 42 U.S.C.
6291(1)–(2) and 6292. Id. The definition
stated that a computer room air
conditioner may be provided with, or
have as available options, an integrated
humidifier, temperature and/or
humidity control of the supplied air,
and reheating function. Id. Additionally,
DOE proposed to specify in the
definition that computer room air
conditioners include, but are not limited
to, the following configurations as
defined in 10 CFR 431.92: down-flow,
horizontal-flow, up-flow ducted, upflow non-ducted, ceiling-mounted
11 DOE notes that the substance of these
provisions remains the same as those proposed in
the February 2022 TP NOPR, but AHRI did some
reorganization in moving from AHRI 1360–202X
Draft to AHRI 1360–2022. Consequently, the
adopted section numbers cited here differ from
those presented in DOE’s proposed rule. See 87 FR
6948, 6952 (Feb. 7, 2022).
12 Section 3.5 of AHRI 1360–202X Draft defines
‘‘computer room air conditioner’’ as a subset of
‘‘computer and data processing room air
conditioner.’’ Section 3.4 of AHRI 1360–202X Draft
defines ‘‘computer and data processing room air
conditioner,’’ as an air conditioning unit
specifically marketed for cooling data centers and
information technology equipment.
D. Definitions
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
E:\FR\FM\11APR3.SGM
11APR3
lotter on DSK11XQN23PROD with RULES3
21822
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
ducted, ceiling mounted non-ducted,
roof-mounted, and wall-mounted. Id.
In the February 2022 NOPR, DOE
requested comment on the proposed
definition for ‘‘computer room air
conditioner’’ that distinguishes between
CRACs and other categories of air
conditioning equipment, based on the
marketing of the equipment. 87 FR
6948, 6954 (Feb. 7, 2022).
AHRI recommended that DOE remove
roof-mounted and wall-mounted units
from the CRAC definition, as they are
currently not included in the scope of
AHRI 1360–2017 and of ASHRAE
Standard 90.1–2019. (AHRI, No. 9 at pp.
4–5) Instead, AHRI expressed support
for a definition consistent with DOE’s
proposal, but with roof-mounted and
wall-mounted CRACs redacted from the
definition. Id.
The CA IOUs recommended adding
the term ‘‘exclusively’’ to the proposed
revised CRAC definition and to exclude
comfort cooling products that are
sometimes marketed for use in
computer rooms (or similar
applications) from the requirement to be
tested to the CRAC test procedure. (CA
IOUs, No. 6 at p. 1) The CA IOUs
provided estimated performance data at
CRAC rating conditions for commercial
unitary air conditioners (‘‘CUACs’’) and
3-phase central air conditioners that
they asserted as indicating that these
equipment categories will always meet
the CRAC efficiency standards in
ASHRAE Standard 90.1–2019. (CA
IOUs, No. 6 at pp. 1–5) The CA IOUs
did not analyze the performance of
single-packaged vertical air conditioners
(‘‘SPVU’’) equipment under the CRAC
test conditions but noted that DOE’s
energy efficiency metric for SPVUs is
also energy efficiency ratio (‘‘EER’’), that
SPVUs are tested at the same conditions
as CUACs, and that the energy
conservation standards for SPVUs are
similar to the CUAC EER requirements
in ASHRAE Standard 90.1–2019.
Therefore, the CA IOUs recommended
that DOE should also exclude SPVUs
from the requirement of testing to the
CRAC test procedure for equipment
marketed for use in computer rooms (or
similar applications). Id. Alternatively,
the CA IOUs recommended that DOE
allow NSenCOP to be calculated with an
alternate efficiency determination
method (‘‘AEDM’’). (CA IOUs, No. 6 at
p. 6)
In response to AHRI, the addition of
roof-mounted and wall-mounted CRACs
to the scope of AHRI 1360–202X Draft,
and as finalized in AHRI 1360–2022,
occurred after considerable deliberation
in the AHRI 1360 committee, in which
DOE actively participated. As such,
DOE considers this inclusion in a
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
published AHRI standard to now
represent industry consensus that
models meeting the definition of roofmounted and wall-mounted CRACs
should be tested to AHRI 1360–2022.
Further, DOE has concluded that
because such models meet the
definition of CRAC and exist on the
market, the Federal test procedure
should include test provisions for such
models. Therefore, DOE has determined
the addition of these configurations to
be appropriate for the CRAC Federal test
procedure.
In response to CA IOUs, DOE is not
adopting the suggested exclusionary
language (i.e., limiting coverage of
CRAC regulations to models marketed
exclusively for computer room cooling
applications) because this would cause
any CRAC equipment marketed for both
data centers and comfort cooling to not
meet the definition of a CRAC as set out
in AHRI 1360–2022. To the extent that
a basic model is covered under more
than one equipment category (e.g.,
CRAC and CUAC), it would be subject
to the regulations applicable to each
equipment class that covers that basic
model. Regarding AEDMs, DOE notes
that current DOE regulations already
allow manufacturers to use AEDMs to
develop CRAC efficiency ratings,
provided they perform physical testing
on two test models per validation class.
10 CFR 429.70(c)(2).
In summary, for the reasons
discussed, DOE is updating the
‘‘computer room air conditioner’’
definition in 10 CFR 431.92 as proposed
in the February 2022 NOPR. Further,
regarding the ‘‘marketed for’’ criterion
in the revised CRAC definition, DOE
will consider any publicly-available
document published by the
manufacturer (e.g., product literature,
catalogs, and packaging labels) to
determine the application for which the
equipment is marketed.
2. CRAC Configuration Definitions
CRACs can be installed in a variety of
different configurations that vary by
installation location, direction of airflow
over the evaporator coil (e.g., up, down,
or horizontal), and by return and
discharge air connections (e.g., raised
floor plenum, ducted, free air). To
provide additional instruction as to
which configuration (and, thus, which
testing requirements and standards, as
applicable) should be used for testing,
the February 2022 NOPR proposed to
add definitions for the following terms,
consistent with the definitions in AHRI
1360–202X Draft: floor-mounted,
ceiling-mounted, wall-mounted, roofmounted, up-flow, down-flow,
horizontal-flow, up-flow ducted, up-
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
flow non-ducted, ceiling-mounted
ducted, ceiling-mounted non-ducted,
and fluid economizer. 87 FR 6948, 6954
(Feb. 7, 2022). DOE requested comment
on the proposed definitions. Id.
AHRI suggested that DOE should
adopt definitions consistent with AHRI
1360–2017, stating that the current draft
procedure was not yet ready for
adoption. Instead, AHRI recommended
that DOE should wait to adopt the
definitions in AHRI 1360–202X Draft
until they are adopted through the
ASHRAE Standard 90.1 process. (AHRI,
No. 9 at p. 5)
DOE notes that AHRI’s concern about
the draft status of AHRI 1360–202X
Draft no longer applies, given the
finalization and publication of AHRI
1360–2022. Furthermore, for the reasons
discussed in section III.C of this
document, the Department has
concluded that EPCA does not preclude
the agency from considering this
updated industry test standard until it
has been formally adopted through the
ASHRAE Standard 90.1 process.
Accordingly, DOE has concluded that
the inclusion of revised definitions for
CRAC configurations in the published
AHRI standard represent industry
consensus that these revised definitions
in AHRI 1360–2022 appropriately
classify different configurations of
CRACs. DOE notes that the definitions
finalized in AHRI 1360–2022 are
substantively the same as those
included in DOE’s proposal. DOE
further notes that AHRI did not raise
substantive issues with the specific
proposed definitions for CRAC
configurations. Therefore, DOE has
concluded that the definitions proposed
in the February 2022 NOPR, which are
consistent with the updated industry
consensus test procedure AHRI 1360–
2022, appropriately classify different
configurations of CRACs to clarify
which test conditions apply to each
configuration.
As such, DOE is finalizing the
definitions as proposed in the February
2022 NOPR. Specifically, DOE is
defining ‘‘floor-mounted,’’ ‘‘ceilingmounted,’’ ‘‘wall-mounted,’’ ‘‘roofmounted,’’ ‘‘up-flow,’’ ‘‘down-flow,’’
‘‘horizontal-flow,’’ ‘‘up-flow ducted,’’
‘‘up-flow non-ducted,’’ ‘‘ceilingmounted ducted,’’ ‘‘ceiling-mounted
non-ducted,’’ and ‘‘fluid economizer’’ as
set out in 10 CFR 431.92 13 at the end
of this document.
13 As explained in the February 2022 NOPR, DOE
is italicizing the defined terms within these
definitions at 10 CFR 431.92 in order to signal to
the reader which terms are separately defined. 87
FR 6948, 6954 (Feb. 7, 2022).
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
E. Metric
1. NSenCOP
DOE’s current efficiency metric for
CRACs is SCOP, which is a ratio of
sensible cooling capacity delivered to
the power consumed. For most
categories of air conditioners and heat
pumps other than CRACs, efficiency
metrics are calculated based on total
cooling capacity (which includes both
sensible cooling and latent cooling).
However, unlike the conditioned spaces
in most commercial buildings, computer
rooms and data centers typically have
limited human occupancy and minimal
dehumidification requirements, and,
thus, primarily require only sensible
cooling. Therefore, SCOP is calculated
based on sensible cooling capacity
rather than total cooling capacity.
As discussed, ASHRAE Standard
90.1–2016 amended the efficiency
metric for CRACs from SCOP (measured
per ANSI/ASHRAE 127–2007) to
NSenCOP (measured per AHRI 1360–
2016). ASHRAE Standard 90.1–2019
subsequently retained NSenCOP as the
test metric, but it updated the test
reference to AHRI 1360–2017 (which
specifies NSenCOP as the test metric
and has the same test conditions as
AHRI 1360–2016). AHRI 1360–202X
Draft also specifies NSenCOP as the test
metric and maintains the rating
conditions found in AHRI 1360–2017,
while also adding rating conditions for
roof-mounted and wall-mounted units.
Like SCOP, NSenCOP is a ratio of
sensible cooling capacity to the power
consumed. However, as discussed in the
February 2022 NOPR, the test procedure
to determine NSenCOP differs from that
to determine SCOP in four key aspects:
(1) For several CRAC configurations
(e.g., down-flow, up-flow ducted),
different indoor entering air
temperatures are specified; (2) for watercooled CRACs, different entering water
temperatures are specified; (3) for upflow ducted configurations, different
indoor air external static pressure
(‘‘ESP’’) requirements are specified; and
(4) for water-cooled and glycol-cooled
CRACs, NSenCOP accounts for energy
consumed by fans and pumps that
would be installed in the outdoor heat
rejection loop, which is not accounted
for in SCOP. 87 FR 6948, 6956–6957
(Feb. 7, 2022).
In response to the changes to the
efficiency metric and referenced
industry test standard for CRACs in
ASHRAE Standard 90.1–2019 and AHRI
1360–202X Draft, DOE proposed to
update its efficiency metric for CRACs
to NSenCOP and requested comment on
its proposal. 87 FR 6948, 6957 (Feb. 7,
2022). DOE also sought feedback on
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
whether the rating conditions in AHRI
1360–202X Draft are appropriately
representative of field applications. Id.
On this topic, AHRI commented at the
NOPR public meeting that it supported
the adoption of NSenCOP as calculated
in AHRI 1360–2017, as opposed to
AHRI 1360–202X Draft. (AHRI, Public
Meeting Transcript, No. 8 at pp. 11–12)
AHRI stated that a minor clarification
would be required to be made in AHRI
1360–2017, which would align the
capacity bins in AHRI 1360–2017 with
those in ASHRAE 90.1–2019. Id. AHRI
asserted that the revised approach for
up-flow CRACs in a limited-height setup would have a measurable impact on
the efficiency of those units, and that
the stringency of the standard level
established in ASHRAE Standard 90.1–
2019 for this equipment would not
correlate to the efficiency of the
equipment as tested with the draft test
procedure. Id. AHRI further asserted
that the SCOP to NSenCOP crosswalk
would, therefore, not be a direct
crosswalk, at least for the up-flow units
and for any other products for which
ESP test requirements have changed. Id.
In response, DOE notes the fact that
the clarification mentioned by AHRI
regarding the capacity demarcations is
appropriately addressed in AHRI 1360–
2022.
Regarding the issue of testing up-flow
units in a limited-height set-up, DOE
surmises that the inclusion of a limitedheight approach in the finalized AHRI
1360–2022 that aligns with the
approach in AHRI 1360–202X Draft
indicates that this limited-height
approach represents industry consensus
on an appropriate test method. Further,
DOE notes that the current Federal test
procedure, which references ANSI/
ASHRAE 127–2007, does not have any
provisions that allow for testing up-flow
CRAC units in a limited-height set-up.
As such, the crosswalk analysis
conducted to translate standards from
SCOP to NSenCOP (as presented in the
March 2022 ECS NOPR; see 87 FR
12802, 12817–12822 (March 7, 2022))
compared SCOP as measured per ANSI/
ASHRAE 127–2007 to NSenCOP as
measured per AHRI 1360–202X Draft
(which is the test procedure DOE
proposed to adopt in the February 2022
NOPR). Therefore, the test approaches
in any intermediate CRAC industry test
procedures released between ANSI/
ASHRAE 127–2007 and AHRI 1360–
202X Draft (e.g., AHRI 1360–2017 as
mentioned by AHRI) are not relevant for
DOE’s crosswalk analysis, as such
intermediate industry test procedures
were never proposed or adopted as part
of the Federal test procedure.
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
21823
The CA IOUs provided several
recommendations to modify the
proposed test procedure. (CA IOUs, No.
6 at p. 6) First, the CA IOUs
recommended that DOE adopt the same
entering air dry-bulb temperature for all
CRAC configurations, asserting that
containment, server rack orientation,
and room temperature setpoints have
much more significant impacts on
return air temperature than CRAC
configuration; therefore, basing test
temperature on CRAC configuration
may create arbitrary differences in
efficiency representations among CRAC
configurations, which would result in a
market distortion in favor of some
configurations over others. Id. Second,
the CA IOUs recommended DOE use
86 °F as the full-load condenser entering
water temperature, as opposed to 83 °F
as prescribed in AHRI 1360–202X Draft,
asserting that typically water-cooled
CRACs and other water-cooled heating,
ventilation, and air conditioning
(HVAC) equipment receive condenser
water via a water-to-water heat
exchanger, and that the 86 °F point takes
into account the approach temperature
of such a heat exchanger. Id. The CA
IOUs added that test procedures for
three other equipment categories have
used 86 °F as the full-load condenser
entering water temperature: direct
expansion-dedicated outdoor air system
units (i.e., AHRI Standard 920–2020),
variable refrigerant flow (‘‘VRF’’) watersource heat pumps (i.e., AHRI Standard
1230–2021), and water-source heat
pumps less than 135,000 Btu/h (i.e., ISO
13256–1:1998) Third, the CA IOUs
supported the inclusion of cooling
tower/dry cooler fan and heat rejection
pump energy in the CRAC efficiency
rating, but suggested that DOE examine
if the power demand adders of 5 percent
and 7.5 percent for water-cooled and
glycol-cooled CRACs, respectively, are
representative. Id.
The Joint Advocates supported the
inclusion of a power adder for heat
rejection components to improve the
representativeness of the test for watercooled and glycol-cooled CRACs. (Joint
Advocates, No. 7 at p. 1) The Joint
Advocates encouraged DOE to
investigate the representativeness of the
proposed entering air dry-bulb
temperatures,14 asserting that it did not
appear that DOE has performed a
thorough analysis of the
representativeness of the proposed
temperature values, but was rather
simply proposing to adopt the values in
AHRI 1360–202X Draft. (Joint
Advocates, No. 7 at p. 1) The Joint
14 In their comment, the Joint Advocates refer to
this as ‘‘return air temperature.’’
E:\FR\FM\11APR3.SGM
11APR3
lotter on DSK11XQN23PROD with RULES3
21824
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
Advocates referenced the March 2022
ECS NOPR, noting that the impact of
increasing the entering air dry-bulb
temperature from 75 °F to 95 °F for upflow ducted and down-flow CRACs, led
to an increase of net sensible cooling
capacity and SCOP by approximately 22
percent and 19 percent, respectively.
(Joint Advocates, No. 7 at pp. 1–2) The
Joint Advocates commented that given
the large potential magnitude of change
to the metrics, DOE should scrutinize
the appropriateness of updating the
entering air dry-bulb temperature values
and, if a revision is found to be justified,
the representativeness of the proposed
entering air dry-bulb temperature
values. Id.
NEEA recommended that DOE ensure
that the required ESP test conditions are
representative of actual ESP conditions
that units experience in the field.
(NEEA, No. 5 at p. 4)
As noted earlier, EPCA requires that
the test procedures for commercial
package air conditioning and heating
equipment be those generally accepted
industry testing procedures or rating
procedures developed or recognized by
AHRI or ASHRAE, as referenced in
ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A)) Further, if such an
industry test procedure is amended,
DOE must update its test procedure to
be consistent with the amended
industry test procedure, unless DOE
determines, by rule published in the
Federal Register and supported by clear
and convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B)) As
discussed in section III.C, DOE has
concluded, supported by clear and
convincing evidence, that AHRI 1360–
2022 would better meet the criterion of
EPCA than AHRI 1360–2017. DOE is not
aware of any data or information
indicating that the entering air dry-bulb
temperature or ESP conditions in AHRI
1360–2022 are not representative of an
average CRAC use cycle, and
commenters did not provide any data or
information to contradict this
understanding. Therefore, DOE
concludes that the rating conditions
finalized in AHRI 1360–2022 are
appropriate. The following paragraphs
include DOE’s responses to some of the
comments received regarding specific
rating conditions in AHRI 1360–202X
Draft (and the subsequently finalized
AHRI 1360–2022).
Regarding entering air dry-bulb
temperature, it is DOE’s understanding
that CRAC configurations in which the
return air inlet is located close to the
heat source (e.g., horizontal flow units,
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
which are typically located adjacent to
server racks) have higher entering air
dry-bulb temperatures than
configurations with return air inlets
located further from the heat source.
Numerous other versions of CRAC
industry test procedures (i.e., ANSI/
ASHRAE 127–2020, AHRI 1360–2017,
and AHRI 1360–2016) also include
different entering air dry-bulb
temperatures for each configuration that
are consistent with AHRI 1360–202X
Draft (and the subsequently finalized
AHRI 1360–2022). Regarding the
comment from Joint Advocates, while
DOE agrees that differing entering air
dry-bulb temperature values lead to a
measurable change in the evaluated
metrics for each configuration, DOE also
notes that the standards proposed in the
March 2022 ECS NOPR are separate for
each configuration and reflect the
different rating conditions. See 87 FR
12802, 12809–12816 (March 7, 2022).
Additionally, industry consensus as
reflected in AHRI 1360–2022 suggests
that using the same entering air dry-bulb
temperature for all CRAC configurations
would be less representative of an
average use cycle for each unique CRAC
configuration. Therefore, DOE has
concluded that different entering air
dry-bulb temperatures for each separate
configuration are appropriate for
inclusion in the revised test procedure.
Similarly, ESP conditions may differ
for CRAC configurations depending on
how and where they may be installed.
As noted earlier, DOE is not aware of
any data or information indicating that
the ESP conditions in AHRI 1360–2022
are not representative of an average
CRAC use cycle, and NEEA did not
provide any data or information to
contradict this understanding.
Regarding condenser entering water
temperature, ANSI/ASHRAE 127–2007
prescribes a test condition of 86 °F (as
suggested by the CA IOUs) for SCOP,
but the lower 83 °F condition was
adopted in subsequent CRAC industry
test procedures—ASHRAE 127–2020,
AHRI 1360–2016, and AHRI 1360–
2017—in addition to AHRI 1360–202X
Draft (and the subsequently finalized
AHRI 1360–2022). DOE considers that
this decrease in the condenser entering
water temperature test condition from
86 °F to 83 °F was made after industry
deliberation and represents industry
consensus. DOE also notes that not all
industry test procedures for other
categories of commercial air
conditioning and heating equipment are
consistent in entering water temperature
test conditions, as AHRI Standard 340/
360–2022, ‘‘Performance Rating of
Commercial and Industrial Unitary Airconditioning and Heat Pump
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
Equipment,’’ specifies an entering water
temperature of 85 °F for water-cooled
CUACs. Therefore, DOE has concluded
that the proposed 83 °F condition as the
condenser entering water temperature
for water-cooled CRACs is appropriate
and would produce the most
representative results.
Regarding the power consumption
adders for heat rejection components for
water-cooled and glycol-cooled CRACs,
ANSI/ASHRAE 127–2020, AHRI 1360–
2016, and AHRI 1360–2017 also specify
the same adders of 5 percent and 7.5
percent for water-cooled and glycolcooled CRACs as proposed in the
February 2022 NOPR. After a careful
review, DOE was not able to find any
information indicating that these values
are not representative for CRAC
installations. Therefore, DOE considers
these demand adders to be appropriate
for CRACs.
In summary, DOE is updating its
efficiency metric for CRACs to
NSenCOP as measured per AHRI 1360–
2022, at appendix E1. Appendix E
continues to reference ANSI/ASHRAE
127–2007 and to provide instructions
for determining SCOP. As noted earlier,
CRACs are not required to be tested
according to the test procedure in
appendix E1 until such time as
compliance is required with an
amended energy conservation standard
that relies on the NSenCOP metric,
should DOE adopt such a standard.
2. Integrated Efficiency Metric
In contrast to an efficiency metric that
measures performance at only one test
point, an annualized, or ‘‘integrated’’
efficiency metric measures performance
at multiple test points (i.e., tests with
different outdoor test conditions) that
are intended to reflect seasonal variation
in outdoor ambient temperatures that
would be experienced by the equipment
installed in the field.
AHRI 1360–2016, AHRI–1360–2017,
and AHRI 1360–202X Draft include an
integrated efficiency metric—integrated
net sensible coefficient of performance
(‘‘iNSenCOP’’). The iNSenCOP metric
comprises a weighted average of
NSenCOP values for four test points at
different outdoor conditions.15
In the February 2022 NOPR, DOE
noted that section D1 of AHRI 1360–
2017 (and section G1 of the
subsequently updated AHRI 1360–202X
Draft) states that ‘‘a long-term goal is for
iNSenCOP to replace NSenCOP after a
more readily testable means has been
15 The rating conditions A, B, C, and D for
iNSenCOP for air-cooled units correspond to
outdoor entering air temperatures of 95.0 °F, 80.0 °F,
65.0 °F, and 40.0 °F, respectively.
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
standardized.’’ 87 FR 6948, 6957 (Feb. 7.
2022). DOE indicated that it was not
aware of any test data that verify the
validity of the iNSenCOP metric and
that minimum efficiency levels in terms
of iNSenCOP have not been adopted in
ASHRAE Standard 90.1. Id. DOE
acknowledged the potential benefit
regarding representativeness that would
be provided with an annualized metric
for CRACs but concluded that given the
apparent need for further validation and
the lack of test data, DOE was unable to
propose to use the iNSenCOP metric at
this time. Id.
The Joint Advocates and NEEA
encouraged DOE to continue to
investigate an annualized metric for
CRACs. (Joint Advocates, No. 7 at p. 2;
NEEA, No. 5 at pp. 1–2) The Joint
Advocates commented that CRACs are
designed to provide year-round cooling
at a stable indoor cooling load and that
an annualized metric that reflects an
integrated measure of CRAC
performance at different outdoor
temperatures would be more
representative of the efficiency of this
equipment. (Joint Advocates, No. 7 at p.
2) NEEA commented that it supports
DOE’s proposal to use NSenCOP instead
of SCOP, but encouraged DOE to
conduct the research required to
transition to the iNSenCOP metric,
which NEEA asserted better accounts
for the energy efficiency of CRACs given
that it provides a standardized
evaluation of the annualized cooling
energy consumption of a unit operated
across the specified range of outdoor
ambient temperatures. (NEEA, No. 5 at
pp. 1–2) NEEA commented that it
believed integrating a part-load
operation assessment was also feasible
when this efficiency metric is adopted
for CRACs in the future. Id.
As noted in the February 2022 NOPR,
DOE acknowledges the potential benefit
regarding representativeness that would
be provided with an annualized,
integrated metric for CRACs. However,
given the need for further validation and
the lack of test data, DOE is not
adopting the iNSenCOP metric at this
time.
3. Part-Load Operation and Air
Circulation Mode
In the July 2017 ASHRAE TP RFI,
DOE noted that CRACs typically operate
at part-load (i.e., less than designed full
cooling capacity) in the field. 82 FR
34427, 34432 (July 25, 2017). DOE
discussed that the reasons for this may
include, but are not limited to,
redundancy in installed units to prevent
server shutdown if a CRAC unit stops
working, and server room designers
building in extra cooling capacity to
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
21825
accommodate additional server racks in
the future. Id. DOE also noted that while
the current DOE test procedure
measures performance at full-load, DOE
has estimated that CRACs operate on
average at a sensible load of 65 percent
of the full-load sensible capacity.16 Id.
Comments received in response to the
July 2017 ASHRAE TP RFI and
discussed in the February 2022 NOPR
also suggested that CRACs are
commonly oversized when installed in
the field, and that this oversizing can
significantly influence performance. 87
FR 6948, 6958 (Feb. 7, 2022).
Additionally, in the February 2022
NOPR, DOE noted it understands that
many CRACs operate in air circulation
mode and that incorporating air
circulation mode in testing might
incentivize use of more-efficient fan
technologies for CRACs that typically
operate at lower fan speeds in air
circulation mode. Id. However, DOE did
not have information or data on partload or air circulation mode operation of
CRACs to support a proposal to amend
the efficiency metric to account for
performance in these operating modes.
Id.
In response to the February 2022
NOPR, NEEA encouraged DOE to gather
more data on the conditions and the
percentage of time when CRACs
typically operate in air circulation
mode, noting that this information will
help ensure that DOE’s metric for
CRACs is representative of average
annual operation, which includes
accounting for energy consumption in
these modes. (NEEA, No. 5 at p. 2)
Similarly, NEEA commented that it
believes that incorporating part-load
performance in the efficiency metric for
CRACs would encourage the adoption of
technologies that improve performance,
such as variable-speed fans and
compressors. (NEEA, No. 5 at pp. 2–3)
NEAA asserted that incorporating partload and air-circulation modes into
efficiency ratings would give consumers
better information about the
performance of different CRAC units.
(NEEA, No. 5 at p. 3) NEEA agreed with
DOE’s statement that there is a lack of
information and data on part-load or aircirculation-mode operation of CRACs,
but the commenter recommended that
DOE conduct more research to collect
the necessary data to amend the
proposed efficiency metric. Id.
The Joint Advocates encouraged DOE
to capture the part-load operation and
air-circulation-mode operation of
CRACs. (Joint Advocates, No. 7 at p. 2)
The Joint Advocates asserted that the
CRAC test procedure for determining
NSenCOP is not representative of an
average use cycle because many CRACs
operate in part-load and air-circulation
mode, and fan energy is not accounted
for in the NSenCOP metric. Id.
The CA IOUs commented that CRACs
operate at part load at nearly all times,
so efficient part-load performance is
more important than full-load
performance for optimal energy use. (CA
IOUs, No. 6 at p. 7) The CA IOUs
referenced studies conducted by PG&E,
which they commented indicate that
data centers are typically operated at
part load to ensure maximum
temperature and humidity control
stability, reliability, and margin for
future load increases. Id. The CA IOUs
suggested that instead of adopting a
part-load performance rating
requirement at this time, DOE should
consider requiring manufacturers to
state the temperature at which capacity
control becomes unstable and when the
CRAC cannot operate within acceptable
test capacity tolerance, and that this
information would allow designers to
evaluate the suitability of the part-load
performance of different equipment
options for specific applications. Id.
These comments suggest that many
CRACs operate in part load and in aircirculation mode and that incorporating
these modes in testing could lead to a
more representative test procedure.
However, CRAC operation in these
operating modes has not been addressed
in any CRAC industry consensus test
procedures. At this time, DOE does not
have enough information or data on
part-load or air-circulation mode
operation of CRACs to support
amending the efficiency metric to
account for performance in these
operating modes. Regarding CA IOUs’
suggestion to require manufacturers to
state the temperature at which capacity
control becomes unstable, DOE has
concluded that such provisions do not
apply for testing to a full-load metric,
which does not involve modulation of
capacity below full-load. Because the
Department is not adopting a part-load
metric in this final rule, DOE is
correspondingly not adopting the CA
IOU’s suggestion.
16 See the analysis for a final rule for standards
and test procedures for certain commercial heating,
air conditioning, and water heating equipment
(including CRACs) published in the Federal
Register on May 16, 2012 (77 FR 28928). (Technical
Support Document, EERE–2011–BT–STD–0029–
0021, pp. 4–15, 4–16)
4. Controls Verification Procedure
Neither the current Federal test
procedure nor AHRI 1360–2022
incorporates a controls verification
procedure (‘‘CVP’’) for CRACs. The
purpose of a CVP is to validate that the
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
E:\FR\FM\11APR3.SGM
11APR3
21826
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
observed positions of critical parameters
for modulating components during the
CVP are within tolerance of the certified
critical parameter values in the
supplementary test instructions (‘‘STI’’)
that are set by the manufacturer in
steady-state tests. This ensures that the
measured results of the test procedure
are based on critical parameter settings
that are representative of critical
parameter behavior that would be
experienced in the field.
In response to the February 2022
NOPR, NEEA commented that CRACs
could benefit from a CVP and that a CVP
would help ensure that manufacturer
claims of energy savings from controls
are accurate and can help verify that
units are achieving the variable-speed
benefits that are claimed. (NEEA, No. 5
at p. 3) NEEA noted that there is
precedence for including a CVP in
commercial HVAC products, such as
VRF multi-split air conditioners and
heat pumps. Id. NEEA further
commented that a CVP may also check
and test the energy savings from
economizers, given that they are not a
component of the proposed test
procedure for basic CRAC models, and
that incorporating a CVP is one
potential way to capture those energy
saving benefits for CRAC units that have
an economizer. Id.
As noted, AHRI 1360–2022, the
industry standard that DOE is adopting
in this final rule, does not include a
CVP for CRACs. Further, DOE is not
aware of any industry test procedures
that include a CVP that would apply for
CRACs. While DOE understands that
there may be potential benefits of
implementing a CVP for CRACs and
acknowledges the precedent of a CVP
for other commercial equipment such as
VRF multi-split systems, DOE
understands that the market penetration
of variable-speed CRAC equipment is
much smaller than for VRF multi-split
systems. Given that DOE is not aware of
an established CVP for CRAC nor any
test data that could support adopting
such a CVP, DOE is not adopting a CVP
for CRACs in this final rule.
lotter on DSK11XQN23PROD with RULES3
F. Configuration of Unit Under Test
1. Background and Summary
CRACs are sold with a wide variety of
components, including many that can
optionally be installed on or within the
unit both in the factory and in the field.
In all cases, these components are
distributed in commerce with the
CRAC, but can be packaged or shipped
in different ways from the point of
manufacture for ease of transportation.
Some optional components may affect a
model’s measured efficiency when
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
tested to the DOE test procedure
adopted in this final rule, and others
may not. DOE is handling CRAC
components in two distinct ways in this
final rule to help manufacturers better
understand their options for developing
representations for their differing
product offerings.
First, the treatment of some
components is specified by the test
procedure to limit their impact on
measured efficiency. For example, a
fire/smoke/isolation damper must be set
in the closed position and sealed during
testing, resulting in a measured
efficiency that would be similar or
identical to the measured efficiency for
a unit without a fire/smoke/isolation
damper.
Second, for certain components not
directly addressed in the DOE test
procedure, this final rule provides more
specific instructions on how each
component should be handled for the
purposes of making representations in
10 CFR part 429. Specifically, these
instructions provide clarity to
manufacturers on how components
should be treated and how to group
individual models with and without
optional components for the purposes of
representations, in order to reduce
burden. DOE is adopting these
provisions in 10 CFR part 429 to allow
for testing of certain individual models
that can be used as a proxy to represent
the performance of equipment with
multiple combinations of components.
DOE is adopting provisions expressly
allowing certain models to be grouped
together for the purposes of making
representations and allowing the
performance of a model without certain
optional components to be used as a
proxy for models with any combinations
of the specified components, even if
such components would impact the
measured efficiency of a model. Steam/
hydronic heat coils are an example of
such a component. The efficiency
representation for a model with a steam/
hydronic heat coil is based on the
measured performance of the CRAC as
tested without the component installed
because the steam/hydronic heat coil is
not easily removed from the CRAC for
testing.17
2. Approach for Exclusion of Certain
Components
a. Proposals
Appendix D of AHRI 1360–2022 (and
Appendix D of AHRI 1360–202X Draft)
provides discussion of components
17 Note that in certain cases, as explained further
in section III.F.2.c of this document, the
representation may have to be based on an
individual model with a steam/hydronic coil.
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
which would not be considered in
representations, and provides
instructions either to neutralize their
impact during testing or for determining
representations for individual models
with such components based on other
individual models that do not include
them.
Instead of referencing Appendix D of
AHRI 1360–202X Draft, DOE tentatively
determined in the February 2022 NOPR
that it would be necessary to include
related provisions in the proposed
appendix E1 test procedure and in the
proposed representation requirements at
10 CFR 429.43. 87 FR 6948, 6964 (Feb.
7. 2022). DOE noted that this revised
approach would provide more detailed
direction and clarity between test
procedure provisions (i.e., how to test a
specific unit) and certification and
enforcement provisions (e.g., which
model(s) to test). Id. Specifically, DOE
proposed to include provisions for
certain specific components to limit
their impact on measured efficiency
during testing. 87 FR 6948, 6981 (Feb.
7, 2022). Additionally, DOE proposed
representation requirements in 10 CFR
429.43(a)(4) that explicitly allowed
representations for individual models
with certain components to be based on
testing for individual models without
those components. The proposal
included a table listing the components
for which these provisions would apply:
air economizers, process heat recovery/
reclaim coils/thermal storage,
evaporative pre-cooling of air-cooled
condenser intake air, steam/hydronic
heat coils, refrigerant reheat coils,
powered exhaust/powered return air
fans, compressor variable frequency
drive (‘‘VFD’’), fire/smoke/isolation
dampers, non-standard indoor fan
motors, humidifiers, flooded condenser
head pressure controls, chilled water
dual cooling coils, and condensate
pump. 87 FR 6948, 6974–6975 (Feb. 7.
2022). Finally, DOE proposed specific
product enforcement provisions in 10
CFR 429.134 indicating that DOE would
conduct enforcement testing on
individual models that do not include
the components listed in the
aforementioned table, except in certain
enumerated circumstances. 87 FR 6948,
6977 (Feb. 7. 2022).
b. General Comments
AHRI generally supported DOE’s
proposals and agreed with the approach
to include the optional features
provisions in the test procedure directly
and remove them from DOE’s
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
Commercial HVAC Enforcement
Policy.18 (AHRI, No. 9 at p. 6)
In this final rule, DOE is adopting its
proposals in the February 2022 NOPR
regarding the exclusion of certain
components, with some additional
simplifications to further improve
clarity. The different aspects of the
provisions are described in the
following sections.
c. Test Provisions Within Appendix E1
lotter on DSK11XQN23PROD with RULES3
DOE is adopting test provisions in
section 4 of appendix E1 to prescribe
how certain components must be
configured for testing, as proposed in
the February 2022 NOPR. Specifically,
DOE is requiring in appendix E1 that
steps be taken during unit set-up and
testing to limit the impacts on the
measurement of these components:
• Air economizers
• Process heat recovery/reclaim coils/
thermal storage
• Evaporative pre-cooling of condenser
intake air
• Steam/hydronic heat coils
• Refrigerant reheat coils
• Fire/smoke/isolation dampers
• Harmonic distortion mitigation
devices
• Humidifiers
• Electric reheat elements
• Non-standard power transformer
• Chilled water dual cooling coils
• High-effectiveness indoor air filtration
The components are listed and
described along with their
corresponding test provisions in Table
4.1 in section 4 of the new appendix E1.
In response to the February 2022
NOPR, AHRI suggested the inclusion of
provisions for four specific components
(i.e., harmonic distortion mitigation
devices, humidifiers, non-standard
power transformers, and chilled water
coils) to limit their impact on measured
efficiency during testing. (AHRI, No. 9
at pp. 6–7) For harmonic distortion
mitigation devices and non-standard
power transformers, AHRI commented
that these components cannot be
removed for testing and that AHRI will
consider including relevant provisions
in the finalized version of AHRI 1360–
202X Draft. For humidifiers and chilled
water coils, AHRI commented that these
should be de-energized and removed
from testing, respectively. Id.
For humidifiers and chilled water
coils, appendix E1 (as proposed in the
February 2022 NOPR) includes
18 On
January 30, 2015, DOE issued a Commercial
HVAC Enforcement Policy addressing the treatment
of specific features during DOE testing of
commercial HVAC equipment. (See
www.energy.gov/gc/downloads/commercialequipment-testing-enforcement-policies.)
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
provisions consistent with AHRI’s
suggestions. For harmonic distortion
mitigation devices and non-standard
power transformers, AHRI 1360–2022
does not provide any further guidance
on these components as AHRI’s
comment indicated. In the absence of
any suggested alternative provisions,
DOE has concluded that the provisions
that were proposed for testing with
these components in appendix E1 in the
February 2022 NOPR are appropriate for
the CRAC test procedure. Therefore,
DOE is adopting the appendix E1
provisions for these components as
proposed.
d. Representation Provisions Within 10
CFR 429.43
As discussed, in the February 2022
NOPR, DOE proposed representation
requirements in 10 CFR 429.43(a)(4) that
explicitly allowed representations for
individual models with certain
components to be based on testing for
individual models without those
components. The proposal included a
table 19 listing the components for
which these provisions would apply
(i.e., air economizers, process heat
recovery/reclaim coils/thermal storage,
evaporative pre-cooling of air-cooled
condenser intake air, steam/hydronic
heat coils, refrigerant reheat coils,
powered exhaust/powered return air
fans, compressor VFD, fire/smoke/
isolation dampers, non-standard indoor
fan motors, humidifiers, flooded
condenser head pressure controls,
chilled water dual cooling coils, and
condensate pump). 87 FR 6948, 6974–
6975 (Feb. 7, 2022).
In this final rule, DOE is making two
clarifications to the representation
requirements as proposed in the
February 2022 NOPR.
First, DOE is specifying that the basic
model representation must be based on
the least-efficient individual model that
is a part of the basic model, and
clarifying how this long-standing basic
model provision interacts with the
component treatment in 10 CFR 429.43
that this final rule adopts. Adoption of
this clarification in the regulatory text is
consistent with the February 2022
NOPR, in which DOE noted that in
some cases, individual models may
include more than one of the specified
components or there may be individual
models within a basic model that
include various versions of the specified
19 In the February 2022 NOPR, this table was
referred to as ‘‘Table 1’’; however, due to the
publication of other test procedure actions
subsequent to the February 2022 NOPR, this final
rule refers to this table as ‘‘Table 5 to paragraph
(a)(3)(iv)(A)—Specific Components for Computer
Room Air Conditioners’’ of 10 CFR 429.43.
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
21827
components that result in more or less
energy use. 87 FR 6948, 6965 (Feb. 7,
2022). In such cases, DOE stated that the
represented values of performance must
be representative of the individual
model with the lowest efficiency found
within the basic model. Id.
DOE has determined that regulated
entities may benefit from clarity in the
regulatory text as to how the leastefficient individual model within a
basic model provision is applied with
the additional component-specific
instructions for CRACs. The
amendments in this final rule explicitly
state that the exclusion of the specified
components from consideration in
determining basic model efficiency in
certain scenarios is an exception to
basing representations on the leastefficient individual model within a
basic model. In other words, the
components listed in 10 CFR 429.43 are
not being considered as part of the
representation under DOE’s regulatory
framework if certain conditions are met
as discussed in the following
paragraphs, and, thus, their impact on
efficiency is not reflected in the
representation. In this case, the basic
model’s representation is generally
determined by applying the testing and
sampling provisions to the leastefficient individual model in the basic
model that does not have a component
listed in 10 CFR 429.43.
Second, DOE is also clarifying
instructions for determining the unit
used for basic model representation to
resolve instances where individual
models within a basic model may have
more than one of the specified
components and there may be no
individual model without any of the
specified components. DOE is adopting
the concept of an ‘‘otherwise
comparable model group’’ (‘‘OCMG’’)
instead of using the ‘‘otherwise
identical’’ provisions proposed in the
February 2022 NOPR. 87 FR 6948,
6964–6965 (Feb. 7, 2022). DOE is using
the term ‘‘comparable’’ as opposed to
‘‘identical’’ to indicate that components
that impact energy consumption as
measured by the applicable test
procedure are the relevant components
to consider for the purpose of
representations. Differences that do not
impact energy consumption, such as
unit color and presence of utility
outlets, would, therefore, not warrant
separate OCMGs. DOE developed and
placed in the docket a document of
examples to illustrate the approach in
this final rule for determining
represented values for CRACs with
specific components, and in particular
the OCMG concept. See EERE–2021–
BT–TP–0017–0010.
E:\FR\FM\11APR3.SGM
11APR3
lotter on DSK11XQN23PROD with RULES3
21828
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
An OCMG is a group of individual
models within the basic model that do
not differ in components that affect
energy consumption as measured
according to the applicable test
procedure other than the specific
components listed in Table 5 of 10 CFR
429.43(a)(3)(iv)(A) (‘‘Table 5 of
§ 429.43’’). An OCMG may include
individual models with any
combination of such specified
components, including no specified
components, and an OCMG can be
comprised of one individual model.
Because every model within each
OCMG is within the definition of the
basic model, a basic model can be
composed of multiple OCMGs. Each
OCMG represents a unique combination
of components that affect energy
consumption, as measured according to
the applicable test procedure, other than
the specified components listed in Table
5 of § 429.43; this means that a new
combination of such components
represents a new OCMG. For example,
a manufacturer might include two tiers
of control system within the same basic
model, in which one of the control
systems has sophisticated diagnostics
capabilities that require a more
powerful control board with a higher
wattage input. CRAC individual models
with the ‘‘standard’’ control system
would be part of OCMG A, while
individual models with the ‘‘premium’’
control system would be part of a
different OCMG B, since the control
system is a component that affects
energy consumption and is not one of
the specified exempt components listed
in Table 5 of § 429.43. However, OCMG
A and OCMG B both may include
individual models with different
combinations of steam/hydronic coils,
harmonic distortion mitigation devices,
and humidifiers, for example. Both
OCMGs may also include any
combination of characteristics that do
not affect the efficiency measurement,
such as paint color.
The OCMG is used to identify which
individual models are used to determine
a represented value for the basic model.
Specifically, only the individual
model(s) with the least number (which
could be zero) of the specific
components listed in Table 5 of § 429.43
is considered when identifying the
individual model. This clarifies which
individual models are exempted from
consideration for determination of
represented values in the case of an
OCMG with multiple specified
components and no individual models
with zero specific components listed in
Table 5 of § 429.43. Models with a
number of specific components listed in
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
Table 5 greater than the model(s) with
the least number in the OCMG are
exempted from consideration. In the
case that the OCMG includes an
individual model with no specific
components listed in Table 5 of
§ 429.43, then all individual models in
the OCMG with any specified
components would be excluded from
consideration. Among the remaining
non-excluded models, the least efficient
individual model across the OCMGs
would be used to determine the
representation of the basic model. In the
case where there are multiple individual
models within a single OCMG with the
same non-zero least number of specified
components, the least efficient of these
would be considered.
The use of the OCMG concept results
in representations being based on the
same individual models as the approach
proposed in the February 2022 NOPR,
i.e., the represented values of
performance are representative of the
individual model(s) with the lowest
efficiency found within the basic model,
excluding certain individual models
with the specific components listed in
Table 5 of § 429.43. However, the
approach as adopted in this final rule is
structured to more explicitly address
individual models with more than one
of the specific components listed in
Table 5 of § 429.43, as well as instances
in which there is no comparable model
without any of the specified
components.
Finally, DOE notes that use of the
OCMG concept for CRACs is consistent
with the approach finalized by DOE in
test procedure final rules for direct
expansion-dedicated outdoor air
systems (see 87 FR 45164 (July 27,
2022)) 20 and single package vertical
units (see 87 FR 75144 (Dec. 7, 2022),21
and proposed in a test procedure NOPR
for water-source heat pumps (see 87 FR
53302 (August 30, 2022)).22
In response to the February 2022
NOPR, AHRI suggested that DOE should
include in appendix E six additional
components (coated coils, sound traps/
sound attenuators, indoor or outdoor
fans with VFD, compressor VFD,
20 See also ‘‘Direct Expansion Dedicated Outdoor
Air Systems (DX–DOAS) Illustration of Specified
Components Requirements Presentation’’ (available
at: www.regulations.gov/document/EERE-2017-BTTP-0018-0038).
21 See also ‘‘Single Package Vertical Units (SPVU)
Illustration of Specified Components Requirements,
November 2022’’ (available at:
www.regulations.gov/document/EERE-2017-BT-TP0020-0025).
22 See also ‘‘Water Source Heat Pumps (WSHP)
Illustration of Specified Components Requirements,
Test Procedure NOPR—August 2022’’ (available at:
www.regulations.gov/document/EERE-2017-BT-TP0029-0013).
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
evaporative pre-cooling of condenser
intake air, and hot gas bypass) at 10 CFR
429.134; AHRI commented that these
components were included in the
Commercial HVAC Enforcement Policy.
(AHRI, No. 9 at pp. 6–7)
In response, DOE notes that none of
these six components are specified for
CRACs in the Commercial HVAC
Enforcement Policy. However, AHRI
1360–202X Draft (and the subsequently
finalized AHRI 1360–2022) includes
three of the components—compressor
VFD, evaporative pre-cooling of
condenser intake air, and coated coils—
as optional features for CRACS. In the
February 2022 NOPR, DOE tentatively
concluded that it was appropriate to
consider inclusion of compressor VFD
and evaporative pre-cooling of
condenser intake air as optional
features, and the Department proposed
provisions for these features at 10 CFR
429.43. 87 FR 6948, 6975 (Feb. 7, 2022).
Correspondingly, in this final rule DOE
is including these two components as
specific components listed in Table 5 of
§ 429.43.
Regarding sound traps/sound
attenuator, indoor or outdoor fans with
VFD, and hot gas bypass, DOE notes that
these components are not included in
AHRI 1360–202X Draft (and the
subsequently finalized industry
consensus test procedure AHRI 1360–
2022). Further, DOE notes that AHRI did
not provide any rationale as to the need
for including these components as
specific components in Table 5 of
§ 429.43. Additionally, these
components are not included for CRACs
in the Commercial HVAC Enforcement
Policy. Therefore, DOE has concluded
that it has no basis to include these
components as specific components
listed in Table 5 of § 429.43.
Regarding coated coils, in the
February 2022 NOPR, DOE proposed to
exclude coated coils from the specific
components list specified in 10 CFR
429.43 because DOE tentatively
concluded that the presence of coated
coils does not result in a significant
impact to performance of CRACs, and,
therefore, that models with coated coils
should be rated based on performance of
models with coated coils. 87 FR 6948,
6965 (Feb. 7, 2022). As discussed, DOE
received comments from AHRI in
response to the February 2022 NOPR
that DOE should consider including
coated coils in the list of specific
components for CRACs at 10 CFR
429.134. DOE also received similar
comments pertaining to coated coils in
response to other commercial HVAC
equipment test procedure NOPRs,
specifically the test procedure
supplemental notice of proposed
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
rulemaking (‘‘SNOPR’’) published for
direct expansion-dedicated outdoor air
systems (‘‘DX–DOASes’’).23 (Docket No.
EERE–2017–BT–TP–0018, AHRI, No. 34
at p. 4) In response to the DX–DOAS
SNOPR, AHRI and Madison Indoor Air
Quality (‘‘MIAQ’’) asserted that some
coated coils impact performance, but
that each coating is different. (Docket
No. EERE–2017–BT–TP–0018, AHRI,
No. 34 at p. 4; MIAQ, No. 29 at p. 4)
AHRI’s and MIAQ’s assertions that
some coated coils do impact energy use
suggest that there are other
implementations of coated coils that do
not impact energy consumption as
measured by the adopted test procedure
(i.e., the implementation of coated coils
does not necessarily or inherently
impact energy use). DOE has no data
indicating the range of impacts for those
coatings that do affect energy use, or
how other characteristics of the
coatings, such as durability and cost,
correlate with energy use impacts.
Absent such data, DOE is unable to
determine the specific range of impacts
on energy use made by coated coils.
Nevertheless, given that comments on
the DX–DOAS SNOPR suggest that
certain implementations of coated coils
do not impact energy use, DOE has
determined that for those units for
which coated coils do impact energy
use, representations should include
those impacts, thereby providing full
disclosure for commercial customers.
Consequently, DOE is not incorporating
coated coils into DOE’s provisions
specified in 10 CFR 429.43(a)(3) that
allow for the exclusion of specified
components when determining
represented values for CRACs. This
approach is consistent with the one
DOE has established in a final rule for
the DX–DOAS test procedure. 87 FR
45164, 45186 (July 27, 2022).
e. Enforcement Provisions Within 10
CFR 429.134
In the February 2022 NOPR, DOE
sought to address CRACs that include
components specified in 10 CFR
429.43(a)(4)(i) both in the requirements
for representations (i.e., 10 CFR 429.43)
and in the equipment-specific
enforcement provisions for assessing
compliance (i.e., 10 CFR 429.134). 87 FR
6948, 6975–6977 (Feb. 7, 2022). DOE
received no comments on this topic.
Instructions on which units to test for
the purpose of representations are
addressed in 10 CFR 429.43.
Consequently, DOE has determined that
including parallel enforcement
provisions in 10 CFR 429.134 would be
redundant and potentially cause
23 See
86 FR 72874 (Dec. 23, 2021).
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
confusion because DOE would select for
enforcement only those individual
models that are the basis for making
basic model representations as specified
in 10 CFR 429.43. Therefore, in this
final rule, DOE is providing the
requirements for making representations
of CRACs that include the specified
components in 10 CFR 429.43 and is not
including parallel direction in the
enforcement provisions of 10 CFR
429.134 established in this final rule.
However, DOE is finalizing the
provision that allows enforcement
testing of alternative individual models
with specific components, if DOE
cannot obtain for test the individual
models without the components that are
the basis of representation.
3. Non-Standard Indoor Fan Motors
The Commercial HVAC Enforcement
Policy includes high-static indoor
blowers/oversized motors as an optional
feature for CRACs, among other
equipment. The Commercial HVAC
Enforcement Policy states that when
selecting a unit of a basic model for
DOE-initiated testing, if the basic model
includes a variety of high-static indoor
blowers or oversized motor options,24
DOE will test a unit that has a standard
indoor fan assembly (as described in the
STI that is part of the manufacturer’s
certification, including information
about the standard motor and associated
drive that was used in determining the
certified rating). This policy only
applies where: (a) the manufacturer
distributes in commerce a model within
the basic model with the standard
indoor fan assembly (i.e., standard
motor and drive), and (b) all models in
the basic model have a motor with the
same or better relative efficiency
performance as the standard motor
included in the test unit, as described in
a separate guidance document discussed
subsequently. If the manufacturer does
not offer models with the standard
motor identified in the STI or offers
models with high-static motors that do
not comply with the comparable
efficiency guidance, DOE will test any
indoor fan assembly offered for sale by
the manufacturer.
DOE subsequently issued a draft
guidance document (‘‘Draft Commercial
HVAC Guidance Document’’) on June
29, 2015 to request comment on a
method for comparing the efficiencies of
a standard motor and a high-static
24 The Commercial HVAC Enforcement Policy
defines ‘‘high-static indoor blower or oversized
motor’’ as an assembly that drives the fan and can
deliver higher external static pressure than the
standard indoor fan assembly sold with the
equipment.
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
21829
indoor blower/oversized motor.25 As
presented in the Draft Commercial
HVAC Guidance Document, the relative
efficiency of an indoor fan motor would
be determined by comparing the
percentage losses of the standard indoor
fan motor to the percentage losses of the
non-standard (oversized) indoor fan
motor. The percentage losses would be
determined by comparing each motor’s
wattage losses to the wattage losses of a
corresponding reference motor.
Additionally, the draft method contains
a table that includes a number of
situations with different combinations
of characteristics of the standard motor
and oversized motor (e.g., whether each
motor is subject to Federal standards for
motors, whether each motor can be
tested to the Federal test procedure for
motors, whether each motor horsepower
is less than one) and specifies for each
combination whether the non-standard
fan enforcement policy would apply
(i.e., whether DOE would not test a
model with an oversized motor, as long
as the relative efficiency of the
oversized motor is at least as good as
performance of the standard motor).
DOE has not issued a final guidance
document and is instead addressing the
issue for CRACs in this test procedure
rulemaking.
In the February 2022 NOPR, DOE
noted that the approaches in section D3
of AHRI 1360–202X Draft for nonstandard indoor fan motors and
integrated fan and motor combinations
(‘‘IFMs’’) generally align with the
approaches of the Commercial HVAC
Enforcement Policy and the Draft
Commercial HVAC Guidance
Document, while providing greater
detail and accommodating a wider range
of fan motor options. 87 FR 6948, 6966
(Feb. 7, 2022). DOE also tentatively
determined that section D3 of Appendix
D of AHRI 1360–202X Draft would more
fully provide the guidance intended by
the Commercial HVAC Enforcement
Policy with regard to non-standard
indoor fan motors. Id. DOE proposed to
adopt the provisions in section D3 of
AHRI 1360–202X Draft for comparing
the performance of standard and nonstandard indoor fan motors and IFMs in
the proposed appendix E1.26 Id.
25 Available at www1.eere.energy.gov/buildings/
appliance_standards/pdfs/draft-commercial-hvacmotor-faq-2015-06-29.pdf.
26 Per DOE’s existing certification regulations, if
a manufacturer were to use the proposed approach
to certify a basic model, the manufacturer would be
required to maintain documentation of how the
relative efficiencies of the standard and nonstandard fan motors or the input power of the
standard and non-standard IFMs were determined,
as well as the supporting calculations. See 10 CFR
429.71.
E:\FR\FM\11APR3.SGM
11APR3
21830
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
Additionally, DOE proposed to adopt
the provisions in section D3 of
Appendix D of AHRI 1360–202X Draft
for the determination of the represented
efficiency value of CRACs at 10 CFR
429.43(a)(3)(v)(C) and for DOE
assessment and enforcement testing of
CRACs at 10 CFR 429.134(s)(1). Id.
In commenting on this issue, AHRI
stated support for maintaining
enforcement policy guidance even if
such guidance moves to the test
procedure provisions, and that for
future adoption, AHRI would support
provisions included in section D3 of
Appendix D of 1360–202X Draft. (AHRI,
No. 9 at p. 7)
In the February 2022 NOPR, the
Department proposed provisions
(referencing section D3 of AHRI 1360–
202X Draft) regarding non-standard
indoor fan motors in the proposed 10
CFR 429.43(a)(3), which addresses
representation requirements for CRACs,
rather than in the DOE test procedure
(i.e., appendix E1). Section D2 of AHRI
1360–2022 includes the same provisions
as those present in AHRI 1360–202X
Draft. DOE has concluded that
maintaining provisions in both
enforcement guidance and DOE
regulations would be redundant, and
that including provisions in DOE
regulations provides better clarity to
stakeholders. For the reasons discussed
in the preceding paragraphs and the
February 2022 NOPR, DOE is finalizing
its proposals regarding non-standard
indoor fan motors as proposed in the
February 2022 NOPR.
lotter on DSK11XQN23PROD with RULES3
G. Represented Values
1. Multiple Refrigerants
In the February 2022 NOPR, DOE
noted that some commercial package air
conditioning and heating equipment
may be sold with more than one
refrigerant option, and that DOE has
identified at least one CRAC
manufacturer that provides two
refrigerant options under the same
model number. 87 FR 6948, 6967 (Feb.
7, 2022). DOE stated that the use of a
refrigerant (such as R–407C as compared
to R–410A) that requires different
hardware (i.e., compressors, heat
exchangers, or air moving systems that
are not the same or comparably
performing) would represent a different
basic model, and according to current
DOE regulations, separate
representations of energy efficiency are
required for each basic model under 10
CFR 429.43(a). Id. DOE also noted that
some refrigerants (such as R–422D and
R–427A) would not require different
hardware, and a manufacturer may
consider them to be the same basic
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
model. Id. In the February 2022 NOPR,
DOE proposed and requested comment
specifying that a manufacturer must
determine the represented values for
that basic model based on the
refrigerant(s)—among all refrigerants
listed on the unit’s nameplate—that
result in the lowest cooling efficiency.
Id.
AHRI supported the concept of DOE’s
proposal regarding representations for
CRAC models approved for use with
multiple refrigerants. (AHRI, No. 9 at p.
7) The CA IOUs also supported DOE’s
proposal to require only ratings for the
worst-performance refrigerant for a
given basic model and noted that this
approach is consistent with DOE’s
policy for other HVAC equipment. (CA
IOUs, No. 6 at p. 7) However, the CA
IOUs recommended that DOE allow
manufacturers to report test results of
the same basic model with multiple
refrigerants, stating that this would
highlight equipment with the same
hardware that can be operated with
better-performing refrigerants. Id. The
CA IOUs commented that commercial
refrigeration equipment uses more than
one refrigerant for rating, and that DOE
allows representations using multiple
refrigerants for consumer central air
conditioners and heat pumps. Id.
As discussed in section III.F.2 of this
final rule, DOE is generally clarifying in
10 CFR 429.43(a)(3)(iv)(A) that
representations for a CRAC basic model
must be based on the least-efficient
individual model(s) distributed in
commerce within the basic model (with
the exception specified in 10 CFR
429.43(a)(3)(iv)(A) for certain individual
models with the components listed in
Table 5 to 10 CFR 429.43(a)(3); this list
does not include different refrigerants).
Therefore, upon further consideration,
DOE has determined that the content of
the proposal in the February 2022 NOPR
regarding multiple refrigerants (which
would have required representations
based on the least-efficient refrigerant)
is already included and clarified in the
provision adopted at 10 CFR
429.43(a)(3)(iv)(A) (which require
representations based on the leastefficient individual model (and thus
also the least-efficient refrigerant), with
the exception mentioned earlier in this
paragraph), and that the refrigerantspecific provisions proposed in the
February 2022 NOPR at 10 CFR
429.43(a)(3) would be redundant. As
such, in this final rule, DOE is not
adopting the refrigerant-specific
language proposed in the February 2022
NOPR.
Regarding the CA IOU’s comment
requesting provision allowing
additional representations within a
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
basic model for different refrigerants,
DOE has concluded that because the
efficiency of the CRAC could be
impacted by different refrigerant
choices, the least-efficient individual
model requirement necessitates
consideration of the least-efficient
refrigerant when determining
represented values for that basic model.
Therefore, DOE is not adopting the CA
IOUs’ suggestion to allow
representations for multiple refrigerants
within a single basic model, because it
would be inconsistent with the
Department’s adopted requirement that
the represented values for a basic model
be based on the least-efficient
individual model.
2. Net Sensible Cooling Capacity
For CRACs, net sensible cooling
capacity (‘‘NSCC’’) determines
equipment class, which in turn
determines the applicable energy
conservation standard. 10 CFR 431.97.
In the February 2022 NOPR, DOE noted
that while NSCC is a required
represented value for CRACs, DOE does
not currently specify provisions for
CRACs regarding how close the
represented value of NSCC must be to
the tested or alternative energyefficiency determination method
(‘‘AEDM’’) simulated NSCC, or whether
DOE will use measured or certified
NSCC to determine equipment class for
enforcement testing. 87 FR 6948, 6967
(Feb. 7, 2022). DOE proposed to add to
its regulations the following provisions
regarding NSCC for CRACs: (1) a
requirement that the represented NSCC
be between 95 percent and 100 percent
of the tested or AEDM-simulated
cooling capacity; and (2) an enforcement
provision stating that DOE would use
the mean of measured NSCC values
from testing, rather than the certified
cooling capacity, to determine the
applicable standards. Id.
AHRI expressed support for DOE’s
proposal that the represented NSCC be
between 95 percent and 100 percent of
the tested or AEDM-simulated cooling
capacity. (AHRI, No. 9 at p. 8) However,
AHRI opposed DOE’s proposed
enforcement provision of using the
mean of measured NSCC values from
testing to determine the applicable
standards, rather than the certified
NSCC, stating that this is a deviation
from the current requirement that DOE
conduct statistical averaging of three
units to confirm published capacity, and
that this proposal was presented
without supporting evidence necessary
to make the change. Id. AHRI
recommended that DOE apply
enforcement provisions similar to those
for packaged terminal air conditioners
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
(‘‘PTACs’’), which specify in paragraph
(e) of 10 CFR 429.134 that if the certified
cooling capacity is found to be ‘‘valid’’
based on the 5-percent allowance to the
tested mean, the reported certified value
of cooling capacity is used in the next
steps of decision making rather than just
the mean itself. Id. AHRI noted that this
5-percent allowance is also currently
provided for portable air conditioners,
water heaters, and dehumidifiers. AHRI
stated that using just the mean of the
measurement(s) to determine the
applicable standard with which the
model must comply is too restrictive
and does not follow precedence set by
similar products. Id.
In response, DOE acknowledges that
the enforcement provisions for PTACs
specified at 10 CFR 429.134(e) are
different than those specified for CUACs
at 10 CFR 429.134(g) (which are
consistent with the provisions proposed
for CRACs). However, the efficiency
standards for PTACs are linearly
variable with capacity (i.e., a change in
PTAC capacity changes the minimum
efficiency required). This relationship
between capacity and the applicable
standard justifies DOE’s approach for
PTACs to use the reported certified
value of cooling capacity if the certified
cooling capacity is found to be within
tolerance. In contrast, the energy
conservation standards for CRACs are
based on equipment classes that are
differentiated based on fixed-capacity
thresholds (i.e., no linear relationship
between capacity and the applicable
standard). As noted, the proposed
provisions for CRACs are consistent
with the current enforcement provisions
for CUACs at 10 CFR 429.134(g), which
have similar capacity thresholds for
equipment classes and also have fixed
efficiency standards within each class.
To maintain consistency with the
approach used for other similarly
situated commercial air conditioning
and heating equipment with equipment
classes based on fixed-capacity
thresholds, DOE is adopting the
enforcement provisions specifying that
DOE would use the mean of measured
cooling capacity values from testing to
determine the applicable standards.
3. Validation Class for Glycol-Cooled
CRACs
DOE’s existing testing regulations
allow the use of an AEDM, in lieu of
actual testing, to simulate the efficiency
of CRACs. 10 CFR 429.43(a). In the
AEDM requirements for CRACs in 10
CFR 429.70, the table itemizing
validation classes for commercial HVAC
equipment inadvertently omits glycolcooled CRACs, which DOE understands
to be similar in design to water-cooled
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
CRACs. To address this, in the February
2022 NOPR, DOE proposed to include
glycol-cooled CRACs in the existing
validation class for water-cooled CRACs
at 10 CFR 429.70(c)(2)(iv). 87 FR 6948,
6968 (Feb. 7, 2022). Specifically, DOE
proposed at 10 CFR 429.70(c)(2)(iv) that
the minimum number of distinct watercooled and/or glycol-cooled models that
must be tested per AEDM would be two
basic models, which aligns with the
‘‘two basic model’’ requirement that
currently applies to the water-cooled
CRACs validation class. Id.
DOE did not receive any comments
regarding this proposal, and for the
reasons discussed in the preceding
paragraph and the February 2022 NOPR,
DOE is adopting this change as
proposed.
H. Effective and Compliance Dates
As noted in the DATES section of this
document, the effective date for the
adopted test procedure amendments for
CRACs is 30 days after publication of
this final rule in the Federal Register.
Regarding the compliance date, EPCA
prescribes that, if DOE amends a test
procedure, all representations of energy
efficiency and energy use, including
those made in the context of
certification and on marketing materials
and product labels, must be made in
accordance with an amended test
procedure, beginning 360 days after
publication of the final rule in the
Federal Register. (42 U.S.C. 6314(d)(1))
However, CRACs are not required to be
tested according to the test procedure in
appendix E1 (that relies on the
NSenCOP metric) until the compliance
date of amended energy conservation
standards denominated in terms of the
NSenCOP metric, should DOE adopt
such standards.
I. Test Procedure Costs
EPCA requires that the test
procedures for commercial package air
conditioning and heating equipment be
generally accepted industry testing
procedures or rating procedures
developed or recognized by either AHRI
or ASHRAE, as referenced in ASHRAE
Standard 90.1. (42 U.S.C. 6314(a)(4)(A))
Further, if such an industry test
procedure is amended, DOE must
amend its test procedure to be
consistent with the amended industry
test procedure unless DOE determines,
by rule published in the Federal
Register and supported by clear and
convincing evidence, that such an
amended test procedure would not meet
the requirements in 42 U.S.C.
6314(a)(2)–(3) related to representative
use and test burden. (42 U.S.C.
6314(a)(4)(B)) In this final rule, DOE is
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
21831
amending the existing test procedure for
CRACs, by adopting the industry test
standard AHRI 1360–2022, including
the energy efficiency metric, NSenCOP.
DOE is also amending its representation
and enforcement provisions for CRACs.
In the February 2022 NOPR, DOE
walked through the anticipated
compliance costs associated with the
proposed test procedure and tentatively
determined that the test procedure
proposals presented in the NOPR would
not increase testing burden for most
CRAC manufacturers (i.e., CRAC
manufacturers who are AHRI members),
compared to current industry practice as
indicated by AHRI 1360–202X Draft,
and that those proposed amendments
would not have a significant impact on
the remaining CRAC manufacturers (i.e.,
CRAC manufacturers who are not AHRI
members). 87 FR 6948, 6968–6970 (Feb.
7, 2022).
AHRI commented that manufacturers,
particularly of up-flow CRACs, will
experience significant impact if DOE
adopts AHRI 1360–202X Draft, rather
than AHRI 1360–2017, noting that AHRI
1360–202X Draft includes a revised
right-angle static pressure deduction
based on a study conducted on forward
curve fans, which changes the static
pressure deduction from a fixed 0.3
inches water gauge to one based on
velocity. (AHRI, No. 9 at pp. 8–9)
In response, DOE first notes that as
previously mentioned, AHRI 1360–202X
Draft has been finalized as AHRI 1360–
2022. The amended test procedure
adopted in this final rule does not
impose any additional test ducting
provisions beyond those included in the
amended industry consensus test
procedure, AHRI 1360–2022.
Additionally, DOE notes that the test
provision for up-flow CRACs
highlighted by AHRI is an alternate
ducting methodology to be used when
there is limited chamber height to meet
the ducting requirements of ANSI/
ASHRAE Standard 37, which are
referenced in both ANSI/ASHRAE 127–
2007 and AHRI 1360–2022. For most
up-flow CRAC units (i.e., all CRACs
except for tall units with large discharge
duct dimensions), manufacturers can
still choose to test their units in taller
test chambers using the ducting
requirements of ANSI/ASHRAE
Standard 37, which comply with both
the current CRAC test procedure and the
amended test procedure adopted in this
final rule. Further, DOE notes that the
AEDM provision in 10 CFR 429.70
allow the use of AEDMs to develop
ratings for CRACs, and, thus,
manufacturers would not be required to
test their very tall up-flow CRACs.
E:\FR\FM\11APR3.SGM
11APR3
21832
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
DOE has determined that the
amendments in this final rule will
improve the representativeness,
accuracy, and reproducibility of the test
results and will not be unduly
burdensome for manufacturers to
conduct or result in increased testing
cost as compared to the current test
procedure. Because the current DOE test
procedure for CRACs is being relocated
to appendix E without change, the test
procedure in appendix E for measuring
SCOP will result in no change in testing
practices. Should DOE adopt the
proposed standards in the ongoing
energy conservation standards
rulemaking (see 87 FR 12802 (March 7,
2022)) denominated in terms of the new
metric (i.e., NSenCOP), the amended
test procedure in appendix E1 for
measuring NSenCOP (as per AHRI
1360–2022) would be required for use
upon the compliance date of such
standards.
DOE has concluded that the test
procedure at appendix E will not
increase third-party lab testing costs per
unit relative to the current DOE test
procedure, which DOE estimates to be
$10,200 (for CRACs that are physically
tested 27). However, DOE has concluded
that the potential adoption of standards
denominated in terms of NSenCOP (and
the corresponding requirement to use
the amended test procedure in appendix
E1) would alter the measured energy
efficiency for CRACs. Consequently,
manufacturers would likely not be able
to rely on data generated under the
current test procedure and would,
therefore, be required to re-rate CRAC
models. In accordance with 10 CFR
429.70, CRAC manufacturers may elect
to use AEDMs to rate models, which
significantly reduces costs to industry.
DOE estimates the per-manufacturer
cost to develop and validate an AEDM
for CRACs to be $46,000. DOE estimates
a cost of approximately $50 per basic
model 28 for determining energy
efficiency using the validated AEDM.
27 Manufacturers are not required to perform
laboratory testing on all basic models. In
accordance with 10 CFR 429.70, CRAC
manufacturers may elect to use AEDMs. An AEDM
is a computer modeling or mathematical tool that
predicts the performance of non-tested basic
models. These computer modeling and
mathematical tools, when properly developed, can
provide a means to predict the energy usage or
efficiency characteristics of a basic model of a given
covered product or equipment and reduce the
burden and cost associated with testing.
28 DOE estimated initial costs to validate an
AEDM assuming 80 hours of general time to
develop an AEDM based on existing simulation
tools and 16 hours to validate two basic models
within that AEDM at the cost of an engineering
technician wage of $50 per hour plus the cost of
third-party physical testing of two units per
validation class (as required in 10 CFR
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
Given that most CRAC manufacturers
are AHRI members, and that DOE is
adopting the procedure in the prevailing
industry test procedure that was
established for use in AHRI’s
certification program, which has already
been updated to include NSenCOP, DOE
expects that most manufacturers will
already be testing using the published
version of the AHRI 1360–2022 in the
timeframe of any potential future energy
conservation standard. Based on this,
DOE has determined that the test
procedure amendments are not expected
to increase the testing burden on CRAC
manufacturers that are AHRI members.
For the minority of CRAC manufacturers
that are not members of AHRI, the test
procedure amendments may have costs
associated with model re-rating, to the
extent that the manufacturers would not
already be testing to the updated
industry test procedure.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Orders
12866 and 13563
Executive Order (‘‘E.O.’’) 12866,
‘‘Regulatory Planning and Review,’’ 58
FR 51735 (Oct. 4, 1993), as
supplemented and reaffirmed by E.O.
13563, ‘‘Improving Regulation and
Regulatory Review,’’ 76 FR 3821 (Jan.
21, 2011), requires agencies, to the
extent permitted by law, to: (1) propose
or adopt a regulation only upon a
reasoned determination that its benefits
justify its costs (recognizing that some
benefits and costs are difficult to
quantify); (2) tailor regulations to
impose the least burden on society,
consistent with obtaining regulatory
objectives, taking into account, among
other things, and to the extent
practicable, the costs of cumulative
regulations; (3) select, in choosing
among alternative regulatory
approaches, those approaches that
maximize net benefits (including
potential economic, environmental,
public health and safety, and other
advantages; distributive impacts; and
equity); (4) to the extent feasible, specify
performance objectives, rather than
specifying the behavior or manner of
compliance that regulated entities must
adopt; and (5) identify and assess
available alternatives to direct
regulation, including providing
economic incentives to encourage the
desired behavior, such as user fees or
marketable permits, or providing
information upon which choices can be
429.70(c)(2)(iv)). DOE estimated the additional per
basic model cost to determine efficiency using an
AEDM, assuming 1 hour per basic model at the cost
of an engineering technician wage of $50 per hour.
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
made by the public. DOE emphasizes as
well that E.O. 13563 requires agencies to
use the best available techniques to
quantify anticipated present and future
benefits and costs as accurately as
possible. In its guidance, the Office of
Information and Regulatory Affairs
(‘‘OIRA’’) in the Office of Management
and Budget (‘‘OMB’’) has emphasized
that such techniques may include
identifying changing future compliance
costs that might result from
technological innovation or anticipated
behavioral changes. For the reasons
stated in the preamble, this final
regulatory action is consistent with
these principles.
Section 6(a) of E.O. 12866 also
requires agencies to submit ‘‘significant
regulatory actions’’ to OIRA for review.
OIRA has determined that this final
regulatory action does not constitute a
‘‘significant regulatory action’’ under
section 3(f) of E.O. 12866. Accordingly,
this action was not submitted to OIRA
for review under E.O. 12866.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of a final regulatory flexibility analysis
(FRFA) for any final rule where the
agency was first required by law to
publish a proposed rule for public
comment, unless the agency certifies
that the rule, if promulgated, will not
have a significant economic impact on
a substantial number of small entities.
As required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003 to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s website: www.energy.gov/gc/
office-general-counsel. DOE reviewed
this final rule under the provisions of
the Regulatory Flexibility Act and the
procedures and policies published on
February 19, 2003.
On February 7, 2022, DOE published
in the Federal Register a notice of
proposed rulemaking (‘‘February 2022
NOPR’’) proposing to update the
references in the Federal test procedures
to the most recent version of the
relevant industry test procedures as they
relate to computer room air conditioners
(‘‘CRACs’’).
As part of the February 2022 NOPR,
DOE conducted its initial regulatory
flexibility analysis (‘‘IRFA’’). 87 FR
6948, 6969–6970 (Feb. 7, 2022). DOE
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
used the Small Business Administration
(‘‘SBA’’) small business size standards
to determine whether manufacturers
qualify as small businesses, which are
listed by the North American Industry
Classification System (NAICS).29 The
SBA considers a business entity to be a
small business, if, together with its
affiliates, it employs less than a
threshold number of workers specified
in 13 CFR part 121.
CRAC manufacturers are classified
under NAICS code 333415, ‘‘AirConditioning and Warm Air Heating
Equipment and Commercial and
Industrial Refrigeration Equipment
Manufacturing.’’ In 13 CFR 121.201, the
SBA sets a threshold of 1,250 employees
or fewer for an entity to be considered
as a small business for this category.
DOE utilized the California Energy
Commission’s Modernized Appliance
Efficiency Database System
(‘‘MAEDbS’’) 30 and DOE’s Compliance
Certification Database (‘‘CCD’’) 31 in
identifying potential small businesses
that manufacture CRACs covered by this
rulemaking. DOE used subscriptionbased business information tools (e.g.,
reports from Dun & Bradstreet 32) to
determine headcount and revenue of
those small businesses. DOE identified
nine companies that are original
equipment manufacturers (‘‘OEMs’’) of
CRACs covered by this rulemaking. DOE
screened out companies that do not
meet the definition of a ‘‘small
business’’ or are foreign-owned and
operated. DOE identified three small,
domestic OEMs for consideration and
noted that one small, domestic OEM
was not an AHRI member, while the
other two small, domestic OEMs were
AHRI members. 87 FR 6948, 6969 (Feb.
7, 2022). DOE noted that small
businesses would be expected to have
different potential regulatory costs
depending on whether they are a
member of AHRI or not. Id. at 87 FR
6970. DOE requested comment on the
number of small businesses DOE
identified and on the potential costs for
the small business that is not an AHRI
member and manufactures CRACs. Id.
29 The size standards are listed by NAICS code
and industry description and are available at:
www.sba.gov/document/support--table-sizestandards (last accessed on August 30, 2021).
30 MAEDbS can be accessed at
www.cacertappliances.energy.ca.gov/Pages/Search/
AdvancedSearch.aspx (last accessed August 30,
2021).
31 Certified equipment in the CCD are listed by
product class and can be accessed at
www.regulations.doe.gov/certification-data/
#q=Product_Group_s%3A* (last accessed August
30, 2021).
32 Market research available at:
app.dnbhoovers.com (last accessed August 30,
2021).
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
On that topic, AHRI commented that
it represented the following single
package vertical units (‘‘SPVU’’)
companies that likely met the criteria of
small businesses that could be
disproportionally impacted by amended
energy conservation standards: Bard
Manufacturing Company, Marvair,
Systemair, Temspec, and United
CoolAir. (AHRI, No. 9 at p. 9)
In response to AHRI’s comment, DOE
evaluated the four manufacturers
mentioned by AHRI and their product
offerings. While these manufacturers
primarily manufacture SPVUs, which
are not the subject of this rulemaking,
DOE’s review found that two of these
manufacturers also offer products that
meet the definition of wall-mounted
CRAC adopted in this final rule. One of
the two manufacturers qualifies as a
small business under the applicable
NAICS code (NAICS code 333415).
However, DOE notes that there are
currently no energy conservation
standards for wall-mounted CRACs, and
this is a test procedure rulemaking with
no proposed amendments to energy
conservation standards. Furthermore,
DOE notes that no standards were
proposed for wall-mounted CRACs in
the March 2022 ECS NOPR.
Consequently, these two manufacturers
would not incur costs as a result of this
final rule unless they choose to make
voluntary representations regarding the
NSenCOP of the subject equipment.
Further, DOE is not adopting any test
requirements for wall-mounted CRACs
that are not included in the industry
consensus test procedure AHRI 1360–
2022. Additionally, AHRI’s comment
suggests that these manufacturers are
AHRI members. Therefore, as discussed
later in this section, it is DOE’s
conclusion that the test procedure
amendments would not add any
additional testing burden (beyond the
updated industry consensus test
procedure) to manufacturers that are
members of AHRI.
In this final rule, DOE is relocating
the current DOE test procedure to a new
appendix E of subpart F of part 431
(‘‘appendix E’’) without change. DOE is
also establishing an amended test
procedure at appendix E1 to subpart F
of part 431 (‘‘appendix E1’’), which
incorporates by reference the updated
industry test standard AHRI 1360–2022
for CRACs. Additionally, this final rule
amends certain representation and
enforcement provisions for CRACs in 10
CFR part 429.
Appendix E does not contain any
changes from the current Federal test
procedure, and, therefore, will not
impose no cost on industry and will not
require retesting solely as a result of
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
21833
DOE’s adoption of this amendment to
the test procedure.
The amended test procedure in
appendix E1 includes amendments for
measuring CRAC energy efficiency
using the NSenCOP metric so as to be
consistent with the updated industry
test procedure. Should DOE adopt
amended energy conservation standards
in the future that are denominated in
terms of NSenCOP (as proposed in the
March 2022 ECS NOPR), DOE expects
there would not be an increase in thirdparty lab testing costs per unit relative
to the current Federal test procedure.
DOE estimates such testing costs to be
$10,200 per unit for physical testing.
DOE has concluded that the amended
test procedure may require re-rating of
CRAC models; however, this would not
be mandatory until such time as DOE
amends the energy conservation
standards for CRACs based on
NSenCOP, should DOE adopt such
amendments.
If CRAC manufacturers conduct
physical testing to certify a basic model,
two units are required to be tested per
basic model. However, manufacturers
are not required to perform laboratory
testing on all basic models, as CRAC
manufacturers may elect to use
AEDMs.33 An AEDM is a computer
modeling or mathematical tool that
predicts the performance of non-tested
basic models. These computer modeling
and mathematical tools, when properly
developed, can provide a means to
predict the energy usage or efficiency
characteristics of a basic model of a
given covered product or equipment
and reduce the burden and cost
associated with testing.
Small businesses would be expected
to have different potential regulatory
costs depending on whether they are a
member of AHRI. DOE understands that
all AHRI members and all
manufacturers currently certifying to the
AHRI Directory will be testing their
CRAC models in accordance with AHRI
1360–2022, the industry test procedure
DOE is incorporating by reference, and
using AHRI’s certification program,
which has already been updated to
include the NSenCOP metric.
The test procedure amendments
would not add any additional testing
burden to manufacturers that are
members of AHRI, as those members
currently are or soon will be using the
AHRI 1360–2022 test procedure. If DOE
were to adopt energy conservation
standards denominated in terms of the
NSenCOP metric, the amended test
procedure may, however, result in rerating costs for manufacturers which are
33 In
E:\FR\FM\11APR3.SGM
accordance with 10 CFR 429.70.
11APR3
21834
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES3
not AHRI members (currently one
identified OEM).
DOE estimated the range of additional
potential testing costs for the single
small CRAC manufacturer that is not an
AHRI member. This small business
would only incur additional testing
costs if they would not already be using
AHRI 1360–2022 to test their CRAC
models. DOE estimates that this small
business manufactures 113 basic
models.
When developing cost estimates for
this single, non-AHRI-member small
business, DOE considered the cost to
develop an AEDM, the costs to validate
the AEDM through physical testing, and
the cost per model to determine ratings
using the AEDM. DOE anticipates that
this small OEM would avail itself of the
cost-saving option which the AEDM
provides. DOE estimated the cost to
develop and validate an AEDM for
CRACs to be approximately $46,000,
which includes physical testing of two
models per validation class.
Additionally, DOE estimated a cost of
approximately $50 per basic model for
determining energy efficiency using the
validated AEDM. The estimated cost to
rate the 113 basic models with the
AEDM would be $5,650. Therefore,
should DOE adopt amended energy
conservation standards denominated in
terms of NSenCOP as the efficiency
metric (as proposed in the March 2022
ECS NOPR), this small business could
incur total testing and rating costs of
$51,650. DOE understands the annual
revenue of this small business to be
approximately $17 million. Therefore,
testing and AEDM costs could cause this
small business manufacturer to incur
costs of up to 0.30 percent of its annual
revenue.
Therefore, for the reasons stated in the
preceding paragraphs, DOE concludes
and certifies that the cost effects
accruing from this test procedure final
rule would not have a ‘‘significant
economic impact on a substantial
number of small entities,’’ and that the
preparation of a FRFA is not warranted.
DOE has submitted a certification and
supporting statement of factual basis to
the Chief Counsel for Advocacy of the
Small Business Administration for
review under 5 U.S.C. 605(b).
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of CRACs must certify
to DOE that their products comply with
any applicable energy conservation
standards. To certify compliance,
manufacturers must first obtain test data
for their products according to the DOE
test procedures, including any
amendments adopted for those test
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including
CRACs. (See generally 10 CFR part 429.)
The collection-of-information
requirement for the certification and
recordkeeping is subject to review and
approval by OMB under the Paperwork
Reduction Act (PRA). This requirement
has been approved by OMB under OMB
control number 1910–1400. Public
reporting burden for the certification is
estimated to average 35 hours per
response, including the time for
reviewing instructions, searching
existing data sources, gathering and
maintaining the data needed, and
completing and reviewing the collection
of information.
DOE is not amending the certification
or reporting requirements for CRACs in
this final rule. Instead, DOE may
consider proposals to amend the
certification requirements and reporting
for CRACs under a separate rulemaking
regarding appliance and equipment
certification. DOE will address changes
to OMB Control Number 1910–1400 at
that time, as necessary.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
DOE has analyzed this regulation in
accordance with the National
Environmental Policy Act of 1969 (42
U.S.C. 4321 et seq.; ‘‘NEPA’’) and DOE’s
NEPA implementing regulations (10
CFR part 1021). In this final rule, DOE
establishes test procedure amendments
that it expects will be used to develop
and implement future energy
conservation standards for CRACs. DOE
has determined that this rule falls into
a class of actions that are categorically
excluded from review under NEPA and
DOE’s implementing regulations,
because it is a rulemaking that interprets
or amends an existing rule or regulation
that does not change the environmental
effect of the rule or regulation being
amended. Specifically, DOE has
determined that adopting test
procedures for measuring energy
efficiency of consumer products and
industrial equipment is consistent with
activities identified in 10 CFR part 1021,
subpart D, appendix A, sections A5 and
A6. Accordingly, neither an
environmental assessment nor an
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 10, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive order also requires agencies to
have an accountable process to ensure
meaningful and timely input by State
and local officials in the development of
regulatory policies that have federalism
implications. On March 14, 2000, DOE
published a statement of policy
describing the intergovernmental
consultation process it will follow in the
development of such regulations. 65 FR
13735. DOE examined this final rule
and has determined that it will not have
a substantial direct effect on the States,
on the relationship between the
National Government and the States, or
on the distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
final rule. States can petition DOE for
exemption from such preemption to the
extent, and based on criteria, set forth in
EPCA. (42 U.S.C. 6297(d)) No further
action is required by Executive Order
13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that executive agencies make
every reasonable effort to ensure that the
regulation: (1) clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
lotter on DSK11XQN23PROD with RULES3
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (‘‘UMRA’’) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action resulting in a rule that
may cause the expenditure by State,
local, and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820; also available at
www.energy.gov/gc/office-generalcounsel. DOE examined this final rule
according to UMRA and its statement of
policy and determined that the rule
contains neither an intergovernmental
mandate, nor a mandate that may result
in the expenditure of $100 million or
more in any year, so these requirements
do not apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
final rule will not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). Pursuant to OMB
Memorandum M–19–15, Improving
Implementation of the Information
Quality Act (April 24, 2019), DOE
published updated guidelines which are
available at www.energy.gov/sites/prod/
files/2019/12/f70/DOE%20Final%20
Updated%20IQA%20Guidelines
%20Dec%202019.pdf. DOE has
reviewed this final rule under the OMB
and DOE guidelines and has concluded
that it is consistent with applicable
policies in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that: (1) is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
21835
energy supply, distribution, or use if the
regulation is implemented, and of
reasonable alternatives to the action and
their expected benefits on energy
supply, distribution, and use.
This regulatory action to amend the
test procedure for measuring the energy
efficiency of CRACs is not a significant
regulatory action under Executive Order
12866. Moreover, it would not have a
significant adverse effect on the supply,
distribution, or use of energy, nor has it
been designated as a significant energy
action by the Administrator of OIRA.
Therefore, it is not a significant energy
action, and, accordingly, DOE has not
prepared a Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; ‘‘FEAA’’) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (‘‘FTC’’)
concerning the impact of the
commercial or industry standards on
competition.
The amendments to the Federal test
procedure for CRACs contained in this
final rule adopt testing methods
contained in certain sections of the
following commercial standards: AHRI
1360–2022, ANSI/ASHRAE 37–2009,
and ANSI/ASHRAE 127–2020. DOE has
evaluated these standards and is unable
to conclude whether they fully comply
with the requirements of section 32(b) of
the FEAA (i.e., whether they were
developed in a manner that fully
provides for public participation,
comment, and review.) DOE has
consulted with both the Attorney
General and the Chairman of the FTC
about the impact on competition of
using the methods contained in these
standards and has received no
comments objecting to their use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that it has been
determined that the final rule is not a
E:\FR\FM\11APR3.SGM
11APR3
21836
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
‘‘major rule’’ as defined by 5 U.S.C.
804(2).
Incorporation by reference, Reporting
and recordkeeping requirements.
N. Description of Materials Incorporated
by Reference
Signing Authority
This document of the Department of
Energy was signed on March 28, 2023,
by Francisco Alejandro Moreno, Acting
Assistant Secretary for Energy Efficiency
and Renewable Energy, pursuant to
delegated authority from the Secretary
of Energy. That document with the
original signature and date is
maintained by DOE. For administrative
purposes only, and in compliance with
requirements of the Office of the Federal
Register, the undersigned DOE Federal
Register Liaison Officer has been
authorized to sign and submit the
document in electronic format for
publication, as an official document of
the Department of Energy. This
administrative process in no way alters
the legal effect of this document upon
publication in the Federal Register.
In this final rule, DOE incorporates by
reference the following test standards:
AHRI 1360–2022 is an industryaccepted test standard for measuring the
performance of CRACs. AHRI 1360–
2022 is available from AHRI at
www.ahrinet.org/search-standards.aspx.
ANSI/ASHRAE 37–2009 is an
industry-accepted test procedure that
provides a method of test for many
categories of air conditioning and
heating equipment. ANSI/ASHRAE 37–
2009 is available from ASHRAE and on
ANSI’s website at webstore.ansi.org/
RecordDetail.aspx?
sku=ANSI%2FASHRAE+Standard+372009.
ANSI/ASHRAE 127–2007 is an
industry-accepted test procedure for
measuring the performance of CRACs.
ANSI/ASHRAE 127–2007 is available
from ASHRAE and on ANSI’s website at
https://webstore.ansi.org/standards/
ashrae/ansiashrae1272007.
ANSI/ASHRAE 127–2020 is an
industry-accepted test procedure for
measuring the performance of CRACs,
which updates ANSI/ASHRAE 127–
2007 to include new CRAC cooling
configurations. ANSI/ASHRAE 127–
2020 is available from ASHRAE and on
ANSI’s website at webstore.ansi.org/
standards/ashrae/ansiashrae1272020.
The following standards were
previously approved for incorporation
by reference in the sections where they
appear and no change is made: AHRI
210/240–2008, AHRI 340/360–2007, and
ISO Standard 13256–1.
V. Approval of the Office of the
Secretary
List of Subjects
10 CFR Part 429
lotter on DSK11XQN23PROD with RULES3
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Reporting
and recordkeeping requirements, Small
businesses.
Administrative practice and
procedure, Confidential business
information, Energy conservation,
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
For the reasons stated in the
preamble, DOE is amending parts 429
and 431 of chapter II of title 10, Code
of Federal Regulations as set forth
below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
2. Amend § 429.4 by:
a. Removing the text ‘‘https://’’
wherever it appears;
■ b. Redesignating paragraph (c)(5) as
paragraph (c)(6); and
■ c. Adding new paragraph (c)(5).
The addition reads as follows:
■
■
The Secretary of Energy has approved
publication of this final rule.
10 CFR Part 431
Signed in Washington, DC, on March 28,
2023.
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
§ 429.4 Materials incorporated by
reference.
*
*
*
*
*
(c) * * *
(5) AHRI Standard 1360–2022 (I–P)
(‘‘AHRI 1360–2022’’), 2022 Standard for
Performance Rating of Computer and
Data Processing Room Air Conditioners,
copyright 2022; IBR approved for
§ 429.43.
*
*
*
*
*
■ 3. Amend § 429.43 by adding
paragraph (a)(3)(iv) to read as follows.
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
§ 429.43 Commercial heating, ventilating,
air conditioning (HVAC) equipment
(excluding air-cooled, three-phase, small
commercial package air conditioning and
heating equipment with a cooling capacity
of less than 65,000 British thermal units per
hour and air-cooled, three-phase, variable
refrigerant flow multi-split air conditioners
and heat pumps with less than 65,000
British thermal units per hour cooling
capacity).
(a) * * *
(3) * * *
(iv) Computer room air conditioners.
When certifying to standards in terms of
net sensible coefficient of performance
(NSenCOP), the following provisions
apply.
(A) For individual model selection:
(1) Representations for a basic model
must be based on the least-efficient
individual model(s) distributed in
commerce among all otherwise
comparable model groups comprising
the basic model, except as provided in
paragraph (a)(3)(iv)(A)(2) of this section
for individual models that include
components listed in table 5 to
paragraph (a)(3)(iv)(A) of this section.
For the purpose of this paragraph
(a)(3)(iv)(A)(1), otherwise comparable
model group means a group of
individual models distributed in
commerce within the basic model that
do not differ in components that affect
energy consumption as measured
according to the applicable test
procedure specified at 10 CFR 431.96
other than those listed in table 5 to
paragraph (a)(3)(iv)(A) of this section.
An otherwise comparable model group
may include individual models
distributed in commerce with any
combination of the components listed in
table 5 (or none of the components
listed in table 5). An otherwise
comparable model group may consist of
only one individual model.
(2) For a basic model that includes
individual models distributed in
commerce, with components listed in
table 5 to paragraph (a)(3)(iv)(A) of this
section, the requirements for
determining representations apply only
to the individual model(s) of a specific
otherwise comparable model group
distributed in commerce with the least
number (which could be zero) of
components listed in table 5 to
paragraph (a)(3)(iv)(A) included in
individual models of the group. Testing
under this paragraph (a)(3)(iv)(A)(2)
shall be consistent with any componentspecific test provisions specified in
section 4 of appendix E1 to subpart F of
10 CFR part 431.
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
21837
TABLE 5 TO PARAGRAPH (a)(3)(iv)(A)—SPECIFIC COMPONENTS FOR COMPUTER ROOM AIR CONDITIONERS
Component
Description
Air Economizers ..................................................
An automatic system that enables a cooling system to supply and use outdoor air to reduce or
eliminate the need for mechanical cooling during mild or cold weather.
A heat exchanger located inside the unit that conditions the equipment’s supply air using energy transferred from an external source using a vapor, gas, or liquid.
Water is evaporated into the air entering the air-cooled condenser to lower the dry-bulb temperature and thereby increase efficiency of the refrigeration cycle.
Coils used to provide supplemental heat.
A heat exchanger located downstream of the indoor coil that heats the supply air during cooling operation using high pressure refrigerant in order to increase the ratio of moisture removal to cooling capacity provided by the equipment.
A powered exhaust fan is a fan that transfers directly to the outside a portion of the building
air that is returning to the unit, rather than allowing it to recirculate to the indoor coil and
back to the building. A powered return air fan is a fan that draws building air into the equipment.
A device connected electrically between the equipment’s power supply connection and the
compressor that can vary the frequency of power supplied to the compressor in order to
allow variation of the compressor’s rotational speed. If the manufacturer chooses to make
representations for performance at part-load and/or low-ambient conditions, compressor
VFDs must be treated consistently for all cooling capacity tests for the basic model (i.e., if
the compressor VFD is installed and active for the part-load and/or low-ambient tests, it
must also be installed and active for the NSenCOP test).
A damper assembly including means to open and close the damper mounted at the supply or
return duct opening of the equipment.
The standard indoor fan motor is the motor specified in the manufacturer’s installation instructions for testing and shall be distributed in commerce as part of a particular model. A nonstandard motor is an indoor fan motor that is not the standard indoor fan motor and that is
distributed in commerce as part of an individual model within the same basic model.
For a non-standard indoor fan motor(s) to be considered a specific component for a basic
model (and thus subject to the provisions of paragraph (a)(3)(iv)(A) of this section), the following provisions must be met:
1. Non-standard indoor fan motor(s) must meet the minimum allowable efficiency determined
per section D.2.1 of AHRI 1360–2022 (incorporated by reference, see § 429.4) (i.e., for nonstandard indoor fan motors) or per section D.2.2 of AHRI 1360–2022 for non-standard indoor integrated fan and motor combinations).
If the standard indoor fan motor can vary fan speed through control system adjustment of
motor speed, all non-standard indoor fan motors must also allow speed control (including
with the use of VFD).
A device placed in the supply air stream for moisture evaporation and distribution. The device
may require building steam or water, hot water, electricity, or gas to operate.
An assembly, including a receiver and head pressure control valve, used to allow for unit operation at lower outdoor ambient temperatures than the standard operating control system.
A secondary chilled water coil added in the indoor air stream for use as the primary or secondary cooling circuit in conjunction with a separate chiller.
A device used to pump condensate and/or humidifier drain water from inside the unit to a customer drain outside the unit.
Process Heat Recovery/Reclaim Coils/Thermal
Storage.
Evaporative Pre-cooling of Air-cooled Condenser Intake Air.
Steam/Hydronic Heat Coils .................................
Refrigerant Reheat Coils .....................................
Powered Exhaust/Powered Return Air Fans ......
Compressor Variable Frequency Drive (VFD) ....
Fire/Smoke/Isolation Dampers ............................
Non-Standard Indoor Fan Motors .......................
Humidifiers ..........................................................
Flooded Condenser Head Pressure Controls .....
Chilled Water Dual Cooling Coils ........................
Condensate Pump ..............................................
(B) The represented value of net
sensible cooling capacity must be
between 95 percent and 100 percent of
the mean of the capacities measured for
the units in the sample selected as
described in paragraph (a)(1)(ii) of this
section, or between 95 percent and 100
percent of the net sensible cooling
capacity output simulated by the AEDM
as described in paragraph (a)(2) of this
section.
*
*
*
*
*
§ 429.70 Alternative methods for
determining energy efficiency and energy
use.
*
4. Amend § 429.70 by revising the
table in paragraph (c)(2)(iv) to read as
follows:
■
*
*
(c) * * *
(2) * * *
(iv) * * *
*
*
TABLE 1 TO PARAGRAPH (c)(2)(iv)
Minimum number of distinct models that must
be tested per AEDM
Validation class
lotter on DSK11XQN23PROD with RULES3
(A) Commercial HVAC Validation Classes
Air-Cooled, Split and Packaged ACs and HPs Greater than or Equal to 65,000 Btu/h Cooling
Capacity and Less than 760,000 Btu/h Cooling Capacity.
Water-Cooled, Split and Packaged ACs and HPs, All Cooling Capacities ....................................
Evaporatively-Cooled, Split and Packaged ACs and HPs, All Capacities ......................................
Water-Source HPs, All Capacities ..................................................................................................
Single Package Vertical ACs and HPs ...........................................................................................
Packaged Terminal ACs and HPs ..................................................................................................
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
2 Basic Models.
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
E:\FR\FM\11APR3.SGM
Models.
Models.
Models.
Models.
Models.
11APR3
21838
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
TABLE 1 TO PARAGRAPH (c)(2)(iv)—Continued
Minimum number of distinct models that must
be tested per AEDM
Validation class
Air-Cooled, Variable Refrigerant Flow ACs and HPs Greater than or Equal to 65,000 Btu/h
Cooling Capacity.
Water-Cooled, Variable Refrigerant Flow ACs and HPs ................................................................
Computer Room Air Conditioners, Air Cooled ................................................................................
Computer Room Air Conditioners, Water-Cooled and Glycol-Cooled ............................................
Direct Expansion-Dedicated Outdoor Air Systems, Air-cooled or Air-source Heat Pump, Without
Ventilation Energy Recovery Systems.
Direct Expansion-Dedicated Outdoor Air Systems, Air-cooled or Air-source Heat Pump, With
Ventilation Energy Recovery Systems.
Direct Expansion-Dedicated Outdoor Air Systems, Water-cooled, Water-source Heat Pump, or
Ground Source Closed-loop Heat Pump, Without Ventilation Energy Recovery Systems.
Direct Expansion-Dedicated Outdoor Air Systems, Water-cooled, Water-source Heat Pump, or
Ground Source Closed-loop Heat Pump, With Ventilation Energy Recovery Systems.
2 Basic Models.
2
2
2
2
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
2 Basic Models.
2 Basic Models.
2 Basic Models.
(B) Commercial Water Heater Validation Classes
Gas-fired Water Heaters and Hot Water Supply Boilers Less than 10 Gallons .............................
Gas-fired Water Heaters and Hot Water Supply Boilers Greater than or Equal to 10 Gallons .....
Oil-fired Water Heaters and Hot Water Supply Boilers Less than 10 Gallons ...............................
Oil-fired Water Heaters and Hot Water Supply Boilers Greater than or Equal to 10 Gallons .......
Electric Water Heaters ....................................................................................................................
Heat Pump Water Heaters ..............................................................................................................
Unfired Hot Water Storage Tanks ...................................................................................................
2
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
Models.
(C) Commercial Packaged Boilers Validation Classes
Gas-fired, Hot Water Only Commercial Packaged Boilers .............................................................
Gas-fired, Steam Only Commercial Packaged Boilers ...................................................................
Gas-fired Hot Water/Steam Commercial Packaged Boilers ...........................................................
Oil-fired, Hot Water Only Commercial Packaged Boilers ...............................................................
Oil-fired, Steam Only Commercial Packaged Boilers .....................................................................
Oil-fired Hot Water/Steam Commercial Packaged Boilers .............................................................
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
(D) Commercial Furnace Validation Classes
Gas-fired Furnaces ..........................................................................................................................
Oil-fired Furnaces ............................................................................................................................
2 Basic Models.
2 Basic Models.
(E) Commercial Refrigeration Equipment Validation Classes 1
Self-Contained Open Refrigerators .................................................................................................
Self-Contained Open Freezers ........................................................................................................
Remote Condensing Open Refrigerators ........................................................................................
Remote Condensing Open Freezers ..............................................................................................
Self-Contained Closed Refrigerators ...............................................................................................
Self-Contained Closed Freezers .....................................................................................................
Remote Condensing Closed Refrigerators .....................................................................................
Remote Condensing Closed Freezers ............................................................................................
2
2
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
1 The minimum number of tests indicated above must be comprised of a transparent model, a solid model, a vertical model, a semi-vertical
model, a horizontal model, and a service-over-the counter model, as applicable based on the equipment offering. However, manufacturers do not
need to include all types of these models if it will increase the minimum number of tests that need to be conducted.
*
*
*
*
*
5. Amend § 429.134 by adding
paragraph (aa) to read as follows:
■
§ 429.134 Product-specific enforcement
provisions.
lotter on DSK11XQN23PROD with RULES3
*
*
*
*
*
(aa) Computer room air conditioners.
The following provisions apply for
assessment and enforcement testing of
models subject to energy conservation
standards denominated in terms of
NSenCOP.
(1) Verification of net sensible cooling
capacity. The net sensible cooling
capacity of each tested unit of the basic
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
model will be measured pursuant to the
test requirements of 10 CFR part 431,
subpart F, appendix E1. The mean of the
net sensible cooling capacity
measurement(s) will be used to
determine the applicable energy
conservation standards for purposes of
compliance.
(2) Specific components. If a basic
model includes individual models with
components listed at table 5 to
§ 429.43(a)(3)(iv)(A) and DOE is not able
to obtain an individual model with the
least number (which could be zero) of
those components within an otherwise
comparable model group (as defined in
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
§ 429.43(a)(3)(iv)(A)(1)), DOE may test
any individual model within the
otherwise comparable model group.
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
6. The authority citation for part 431
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
■
■
7. Section 431.92 is amended by:
a. Revising the introductory text;
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
b. Adding, in alphabetical order,
definitions for ‘‘Ceiling-mounted,’’
‘‘Ceiling-mounted ducted,’’ and
‘‘Ceiling-mounted non-ducted’’;
■ c. Removing the definition for
‘‘Computer Room Air Conditioner’’ and
adding the definition ‘‘Computer room
air conditioner’’ in its place; and
■ d. Adding, in alphabetical order,
definitions for ‘‘Down-flow,’’ ‘‘Floormounted,’’ ‘‘Fluid economizer,’’
‘‘Horizontal-flow,’’ ‘‘Net sensible
coefficient of performance, or
NSenCOP,’’ ‘‘Roof-mounted,’’ ‘‘Upflow,’’ ‘‘Up-flow ducted,’’ ‘‘Up-flow
non-ducted,’’ and ‘‘Wall-mounted.’’
The revisions and additions read as
follows:
■
lotter on DSK11XQN23PROD with RULES3
§ 431.92 Definitions concerning
commercial air conditioners and heat
pumps.
The following definitions apply for
purposes of this subpart, and of subparts
J through M of this part. Any words or
terms not defined in this section or
elsewhere in this part shall be defined
as provided in 42 U.S.C. 6311. For
definitions that reference the
application for which the equipment is
marketed, DOE will consider any
publicly available document published
by the manufacturer (e.g., product
literature, catalogs, and packaging
labels) to determine marketing intent.
For definitions in this section that
pertain to computer room air
conditioners, italicized terms within a
definition indicate terms that are
separately defined in this section.
*
*
*
*
*
Ceiling-mounted means a
configuration of a computer room air
conditioner for which the unit housing
the evaporator coil is configured for
indoor installation on or through a
ceiling.
Ceiling-mounted ducted means a
configuration of a ceiling-mounted
computer room air conditioner that is
configured for use with discharge
ducting (even if the unit is also
configurable for use without discharge
ducting).
Ceiling-mounted non-ducted means a
configuration of a ceiling-mounted
computer room air conditioner that is
configured only for use without
discharge ducting.
*
*
*
*
*
Computer room air conditioner means
commercial package air-conditioning
and heating equipment (packaged or
split) that is marketed for use in
computer rooms, data processing rooms,
or other information technology cooling
applications and not a covered
consumer product under 42 U.S.C.
6291(1)–(2) and 42 U.S.C. 6292. A
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
computer room air conditioner may be
provided with, or have as available
options, an integrated humidifier,
temperature and/or humidity control of
the supplied air, and reheating function.
Computer room air conditioners
include, but are not limited to, the
following configurations as defined in
this section: down-flow, horizontal-flow,
up-flow ducted, up-flow non-ducted,
ceiling-mounted ducted, ceiling
mounted non-ducted, roof-mounted,
and wall-mounted.
*
*
*
*
*
Down-flow means a configuration of
floor-mounted computer room air
conditioner in which return air enters
above the top of the evaporator coil and
discharge air leaves below the bottom of
the evaporator coil.
*
*
*
*
*
Floor-mounted means a configuration
of a computer room air conditioner for
which the unit housing the evaporator
coil is configured for indoor installation
on a solid floor, raised floor, or floorstand. Floor-mounted computer room
air conditioners are one of the following
three configurations: down-flow,
horizontal-flow, and up-flow.
Fluid economizer means an option
available with a computer room air
conditioner in which a fluid (other than
air), cooled externally from the unit,
provides cooling of the indoor air to
reduce or eliminate unit compressor
operation when outdoor temperature is
low. The fluid may include, but is not
limited to, chilled water, water/glycol
solution, or refrigerant. An external
fluid cooler such as, but not limited to
a dry cooler, cooling tower, or
condenser is utilized for heat rejection.
This component is sometimes referred
to as a free cooling coil, econ-o-coil, or
economizer.
*
*
*
*
*
Horizontal-flow means a configuration
of a floor-mounted computer room air
conditioner that is neither a down-flow
nor an up-flow unit.
*
*
*
*
*
Net sensible coefficient of
performance, or NSenCOP, means a
ratio of the net sensible cooling capacity
in kilowatts to the total power input in
kilowatts for computer room air
conditioners, as measured in appendix
E1 of this subpart.
*
*
*
*
*
Roof-mounted means a configuration
of a computer room air conditioner that
is not wall-mounted, and for which the
unit housing the evaporator coil is
configured for outdoor installation.
*
*
*
*
*
Up-flow means a configuration of a
floor-mounted computer room air
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
21839
conditioner in which return air enters
below the bottom of the evaporator coil
and discharge air leaves above the top
of the evaporator coil.
Up-flow ducted means a configuration
of an up-flow computer room air
conditioner that is configured for use
with discharge ducting (even if the unit
is also configurable for use without
discharge ducting).
Up-flow non-ducted means a
configuration of an up-flow computer
room air conditioner that is configured
only for use without discharge ducting.
*
*
*
*
*
Wall-mounted means a configuration
of a computer room air conditioner for
which the unit housing the evaporator
coil is configured for installation on or
through a wall.
*
*
*
*
*
■ 8. Amend § 431.95 by:
■ a. Adding paragraph (b)(10);
■ b. In paragraph (c)(2), removing the
text ‘‘D1, F1’’ and adding, in its place,
‘‘D1, E1, F1’’;
■ c. In paragraph (c)(7), removing the
text ‘‘§ 431.96’’ and adding, in its place,
‘‘§ 431.96 and appendix E to this
subpart’’;
■ d. Redesignating paragraph (c)(8) as
paragraph (c)(9); and
■ e. Adding new paragraph (c)(8).
The additions and revisions read as
follows:
§ 431.95 Materials incorporated by
reference.
*
*
*
*
*
(b) * * *
(10) AHRI Standard 1360–2022 (I–P)
(‘‘AHRI 1360–2022’’), 2022 Standard for
Performance Rating of Computer and
Data Processing Room Air Conditioners,
copyright 2022; IBR approved for
appendix E1 to this subpart.
(c) * * *
(8) ANSI/ASHRAE Standard 127–
2020 (‘‘ANSI/ASHRAE 127–2020’’),
Method of Rating Air-Conditioning
Units Serving Data Center (DC) and
Other Information Technology
Equipment (ITE) Spaces, ANSIapproved on November 30, 2020; IBR
approved for appendix E1 to this
subpart.
*
*
*
*
*
■ 9. Amend § 431.96 by revising table 1
to paragraph (b) to read as follows:
§ 431.96 Uniform test method for the
measurement of energy efficiency of
commercial air conditioners and heat
pumps.
*
*
*
(b) * * *
E:\FR\FM\11APR3.SGM
11APR3
*
*
21840
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
TABLE 1 TO PARAGRAPH (b)—TEST PROCEDURES FOR COMMERCIAL AIR CONDITIONERS AND HEAT PUMPS
Equipment type
Category
Small Commercial Package Air-Conditioning
and Heating Equipment.
Air-Cooled, 3-Phase, AC
and HP.
Air-Cooled AC and HP ...
Water-Cooled and Evaporatively-Cooled AC.
Large Commercial Package Air-Conditioning
and Heating Equipment.
Very Large Commercial
Package Air-Conditioning and Heating
Equipment.
Packaged Terminal Air
Conditioners and Heat
Pumps.
Computer Room Air Conditioners.
Variable Refrigerant Flow
Multi-split Systems.
Water-Source HP ...........
Air-Cooled AC and HP ...
Energy efficiency
descriptor
<65,000 Btu/h .................
SEER and HSPF ............
Appendix F to this subpart 3.
None.
SEER2 and HSPF2 ........
Appendix F1 to this subpart 3.
Appendix A of this subpart.
AHRI 210/240–2008
(omit section 6.5).
AHRI 340/360–2007
(omit section 6.3).
ISO Standard 13256–1 ..
Appendix A to this subpart.
None.
≥65,000 Btu/h and
<135,000 Btu/h.
<65,000 Btu/h .................
≥65,000 Btu/h and
<135,000 Btu/h.
<135,000 Btu/h ...............
≥135,000 Btu/h and
<240,000 Btu/h.
EER, IEER, and COP ....
EER ................................
EER ................................
EER and COP ................
EER, IEER, and COP ....
Water-Cooled and Evaporatively-Cooled AC.
Air-Cooled AC and HP ...
≥135,000 Btu/h and
<240,000 Btu/h.
≥240,000 Btu/h and
<760,000 Btu/h.
Water-Cooled and Evaporatively-Cooled AC.
AC and HP .....................
≥240,000 Btu/h and
<760,000 Btu/h.
<760,000 Btu/h ...............
EER and COP ................
AC ...................................
<760,000 Btu/h ...............
SCOP .............................
<760,000 Btu/h ...............
NSenCOP .......................
<65,000 Btu/h (3-phase)
SEER ..............................
AC ...................................
EER ................................
EER, IEER, and COP ....
EER ................................
SEER2 ............................
Variable Refrigerant Flow
Multi-split Systems, Aircooled.
HP ...................................
<65,000 Btu/h (3-phase)
SEER and HSPF ............
SEER2 and HSPF2 ........
Variable Refrigerant Flow
Multi-split Systems, Aircooled.
Variable Refrigerant Flow
Multi-split Systems,
Water-source.
Single Package Vertical
Air Conditioners and
Single Package Vertical
Heat Pumps.
AC and HP .....................
HP ...................................
AC and HP .....................
≥65,000 Btu/h and
<760,000 Btu/h.
EER and COP ................
≥65,000 Btu/h and
<760,000 Btu/h.
<760,000 Btu/h ...............
IEER and COP ...............
EER and COP ................
<760,000 Btu/h ...............
IEER and COP ...............
<760,000 Btu/h ...............
EER and COP ................
EER, IEER, and COP ....
Direct Expansion-Dedicated Outdoor Air Systems.
All ....................................
Additional test procedure
provisions as indicated in
the listed paragraphs of
this section
Cooling capacity or
moisture removal
capacity 2
<324 lbs. of moisture removal/hr.
ISMRE2 and ISCOP2 .....
Use tests, conditions,
and procedures 1 in
AHRI 340/360–2007
(omit section 6.3).
Appendix A to this subpart.
AHRI 340/360–2007
(omit section 6.3).
Paragraph (g) of this section.
Appendix
part 3.
Appendix
part 3.
Appendix
part 3.
Appendix
part 3.
Appendix
part 3.
None.
Paragraphs (c) and (e).
Paragraphs (c) and (e).
Paragraph (e).
None.
Paragraphs (c) and (e).
None.
Paragraphs (c) and (e).
Paragraphs (c), (e), and
(g).
E to this sub-
None.
E1 to this sub-
None.
F to this sub-
None.
F1 to this sub-
None.
F to this sub-
None.
Appendix F1 to this subpart 3.
Appendix D of this subpart 3.
None.
Appendix D1 of this subpart 3.
Appendix D of this subpart 3.
None.
Appendix D1 of this subpart 3.
Appendix G to this subpart 3.
None.
Appendix G1 to this subpart 3.
Appendix B of this subpart.
None.
None.
None.
None.
None.
1 Incorporated
by reference; see § 431.95.
removal capacity applies only to direct expansion-dedicated outdoor air systems.
equipment with multiple appendices listed in this table, consult the notes at the beginning of those appendices to determine the applicable appendix to use for
2 Moisture
3 For
testing.
*
*
*
*
*
10. Add appendix E to subpart F of
part 431 to read as follows:
lotter on DSK11XQN23PROD with RULES3
■
Appendix E to Subpart F of Part 431—
Uniform Test Method for Measuring the
Energy Consumption of Computer
Room Air Conditioners
Note: Manufacturers must use the results of
testing under this appendix to determine
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
compliance with the relevant energy
conservation standards for computer room air
conditioners from § 431.97 as that standard
appeared in the January 1, 2022 edition of 10
CFR parts 200 through 499. Specifically,
representations, including compliance
certifications, must be based upon results
generated either under this appendix or
under 10 CFR 431.96 as it appeared in the
10 CFR parts 200 through 499 edition revised
as of January 1, 2022.
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
For any amended standards for computer
room air conditioners that rely on net
sensible coefficient of performance
(NSenCOP) published after January 1, 2022,
manufacturers must use the results of testing
under appendix E1 to this subpart to
determine compliance. Manufacturers may
use appendix E1 to certify compliance with
any amended standards prior to the
applicable compliance date for those
standards.
E:\FR\FM\11APR3.SGM
11APR3
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
Specifically, representations, including
compliance certifications, related to energy
consumption must be based upon results
generated under the appropriate appendix
that applies (i.e., this appendix or appendix
E1 to this subpart) when determining
compliance with the relevant standard.
1. Incorporation by Reference.
DOE incorporated by reference in § 431.95
the entire standard for ASHRAE 127–2007.
However, certain enumerated provisions of
ASHRAE 127–2007, as listed in section 1.1,
are inapplicable. To the extent that there is
a conflict between the terms or provisions of
a referenced industry standard and the CFR,
the CFR provisions control.
1.1 ASHRAE 127–2007:
(a) Section 5.11 is inapplicable as specified
in section 2 of this appendix.
(b) [Reserved]
1.2 [Reserved]
2. General. Determine the sensible
coefficient of performance (SCOP) in
accordance with ASHRAE 127–2007.
3. Optional break-in period. Manufacturers
may optionally specify a ‘‘break-in’’ period,
not to exceed 20 hours, to operate the
equipment under test prior to conducting the
test method specified in this appendix. A
manufacturer who elects to use an optional
compressor break-in period in its
certification testing should record this
period’s duration as part of the information
in the supplemental testing instructions
under 10 CFR 429.43.
4. Additional provisions for equipment setup. The only additional specifications that
may be used in setting up the basic model
for test are those set forth in the installation
and operation manual shipped with the unit.
Each unit should be set up for test in
accordance with the manufacturer
installation and operation manuals. Sections
4.1 and 4.2 of this appendix provide
specifications for addressing key information
typically found in the installation and
operation manuals.
4.1. If a manufacturer specifies a range of
superheat, sub-cooling, and/or refrigerant
pressure in its installation and operation
manual for a given basic model, any value(s)
within that range may be used to determine
refrigerant charge or mass of refrigerant,
unless the manufacturer clearly specifies a
rating value in its installation and operation
manual, in which case the specified rating
value must be used.
4.2. The airflow rate used for testing must
be that set forth in the installation and
operation manuals being shipped to the
commercial customer with the basic model
and clearly identified as that used to generate
the DOE performance ratings. If a rated
airflow value for testing is not clearly
identified, a value of 400 standard cubic feet
per minute (scfm) per ton must be used.
11. Add appendix E1 to subpart F of
part 431 to read as follows:
■
Appendix E1 to Subpart F of Part 431—
Uniform Test Method for Measuring the
Energy Consumption of Computer
Room Air Conditioners
Note: Prior to the compliance date for any
amended energy conservation standards
based on NSenCOP for computer room air
conditioners, representations with respect to
energy use or efficiency of this equipment,
including compliance certifications, must be
based on testing pursuant to appendix E to
this subpart. Subsequently, manufacturers
must use the results of testing under this
appendix to determine compliance with any
amended energy conservation standards for
computer room air conditioners provided in
§ 431.97 that are published after January 1,
2022, and that rely on net sensible coefficient
of performance (NSenCOP). Specifically,
representations, including compliance
certifications, related to energy consumption
must be based upon results generated under
the appropriate appendix that applies (i.e.,
appendix E to this subpart or this appendix)
when determining compliance with the
relevant standard. Manufacturers may use
this appendix to certify compliance with any
amended standards prior to the applicable
compliance date for those standards.
1. Incorporation by Reference
DOE incorporated by reference in § 431.95
the entire standards for AHRI 1360–2022,
ANSI/ASHRAE 37–2009, and ANSI/ASHRAE
127–2020. However, as listed in sections 1.1,
1.2, and 1.3 of this appendix, only certain
enumerated provisions of AHRI 1360–2022
and ANSI/ASHRAE 127–2020 are applicable,
and only certain enumerated provisions of
ANSI/ASHRAE 37–2009 are not applicable.
To the extent that there is a conflict between
the terms or provisions of a referenced
industry standard and the CFR, the CFR
provisions control.
1.1 AHRI 1360–2022:
(a) The following sections of Section 3.
Definitions—3.1 (Expressions of Provision),
3.2.2 (Air Sampling Device(s)), 3.2.7
(Computer and Data Processing Room Air
Conditioner), 3.2.22 (Indoor Unit), 3.2.25
(Manufacturer’s Installation Instruction),
3.2.27 (Net Sensible Cooling Capacity), 3.2.28
(Net Total Cooling Capacity), 3.2.37
21841
(Standard Air) and 3.2.38 (Standard Airflow)
are applicable.
(b) Section 5. Test Requirements, is
applicable.
(c) The following sections of Section 6.
Rating Requirements—6.1–6.3, 6.5 and 6.7
are applicable.
(d) Appendix C. Standard Configurations—
Normative, is applicable.
(e) Section D2 of Appendix D. NonStandard Indoor Fan Motors for CRAC units,
is applicable.
(f) Appendix E. Method of Testing
Computer and Data Processing Room Air
Conditioners—Normative, is applicable.
(g) Appendix F. Indoor and Outdoor Air
Condition Measurement—Normative is
applicable.
1.2 ANSI/ASHRAE 127–2020:
(a) Appendix A—Figure A–1, Test duct for
measuring air flow and static pressure on
downflow units, is applicable.
(b) [Reserved].
1.3 ASHRAE 37–2009:
(a) Section 1 Purpose is inapplicable.
(b) Section 2 Scope is inapplicable.
(c) Section 4 Classification is inapplicable.
2. General. Determine the net sensible
coefficient of performance (NSenCOP), in
accordance with AHRI 1360–2022, ANSI/
ASHRAE 127–2020, and ANSI/ASHRAE 37–
2009. In cases where there is a conflict
between these sources, the language of this
appendix takes highest precedence, followed
by AHRI 1360–2022, followed by ANSI/
ASHRAE 127–2020, followed by ANSI/
ASHRAE 37–2009. Any subsequent
amendment to a referenced document by a
standard-setting organization will not affect
the test procedure in this appendix, unless
and until this test procedure is amended by
DOE. Material is incorporated as it exists on
the date of the approval, and notification of
any change in the incorporation will be
published in the Federal Register.
3. Test Conditions
3.1. Test Conditions for Certification. When
testing to certify to the energy conservation
standards in § 431.97, test using the ‘‘Indoor
Return Air Temperature Standard Rating
Conditions’’ and ‘‘Heat Rejection/Cooling
Fluid Standard Rating Conditions’’
conditions, as specified in Tables 3 and 4 of
AHRI 1360–2022, respectively.
4. Set-Up and Test Provisions for Specific
Components. When testing a unit that
includes any of the features listed in Table
4.1 of this appendix, test in accordance with
the set-up and test provisions specified in
Table 4.1 of this appendix.
lotter on DSK11XQN23PROD with RULES3
TABLE 4.1—TEST PROVISIONS FOR SPECIFIC COMPONENTS
Component
Description
Test provisions
Air Economizers .................................................................
An automatic system that enables a cooling system
to supply outdoor air to reduce or eliminate the
need for mechanical cooling during mild or cold
weather.
Process Heat Recovery/Reclaim Coils/Thermal Storage ...
A heat exchanger located inside the unit that conditions the equipment’s supply air using energy
transferred from an external source using a
vapor, gas, or liquid.
For any air economizer that is factory-installed,
place the economizer in the 100% return position
and close and seal the outside air dampers for
testing. For any modular air economizer shipped
with the unit but not factory-installed, do not install the economizer for testing.
Disconnect the heat exchanger from its heat source
for testing.
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
E:\FR\FM\11APR3.SGM
11APR3
21842
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules and Regulations
TABLE 4.1—TEST PROVISIONS FOR SPECIFIC COMPONENTS—Continued
Component
Description
Test provisions
Evaporative Pre-cooling of Condenser Intake Air ..............
Water is evaporated into the air entering the aircooled condenser to lower the dry-bulb temperature and thereby increase efficiency of the refrigeration cycle.
Coils used to provide supplemental heat .................
Disconnect the unit from the water supply for testing (i.e., operate without active evaporative cooling).
Steam/Hydronic Heat Coils ................................................
Refrigerant Reheat Coils ....................................................
Fire/Smoke/Isolation Dampers ...........................................
Harmonic Distortion Mitigation Devices ..............................
Humidifiers ..........................................................................
Electric Reheat Elements ...................................................
Non-standard Power Transformer ......................................
Chilled Water Dual Cooling Coils .......................................
High-Effectiveness Indoor Air Filtration ..............................
A heat exchanger located downstream of the indoor coil that heats the supply air during cooling
operation using high pressure refrigerant in order
to increase the ratio of moisture removal to cooling capacity provided by the equipment.
A damper assembly including means to open and
close the damper mounted at the supply or return duct opening of the equipment.
A high voltage device that reduces harmonic distortion measured at the line connection of the
equipment that is created by electronic equipment in the unit.
A device placed in the supply air stream for moisture evaporation and distribution. The device may
require building steam or water, hot water, electricity, or gas to operate.
Electric reheat elements and controls that are located downstream of the cooling coil that may
heat the air using electrical power during the
dehumidification process.
A device applied to a high voltage load that transforms input electrical voltage to that voltage necessary to operate the load.
A secondary chilled water coil added in the indoor
air stream for use as the primary or secondary
cooling circuit in conjunction with a separate chiller.
Indoor air filters with greater air filtration effectiveness than Minimum Efficiency Reporting Value
(MERV) 8 for ducted units and MERV 1 for nonducted units.
Test with steam/hydronic heat coils in place but
providing no heat.
De-activate refrigerant re-heat coils so as to provide the minimum (none if possible) reheat
achievable by the system controls.
For any fire/smoke/isolation dampers that are factory-installed, close and seal the dampers for
testing. For any modular fire/smoke/isolation
dampers shipped with the unit but not factory-installed, do not install the dampers for testing.
Remove harmonic distortion mitigation devices for
testing.
Test with humidifiers in place but providing no humidification.
Test with electric reheat elements in place but providing no heat.
Disable the non-standard power transformer during
testing.
Test with chilled water dual cooling coils in place
but providing no cooling.
Test with the filter offered by the manufacturer with
the least air filtration effectiveness that meets or
exceeds MERV 8 for ducted units and MERV 1
for non-ducted units.
[FR Doc. 2023–06760 Filed 4–10–23; 8:45 am]
lotter on DSK11XQN23PROD with RULES3
BILLING CODE 6450–01–P
VerDate Sep<11>2014
19:39 Apr 10, 2023
Jkt 259001
PO 00000
Frm 00028
Fmt 4701
Sfmt 9990
E:\FR\FM\11APR3.SGM
11APR3
Agencies
[Federal Register Volume 88, Number 69 (Tuesday, April 11, 2023)]
[Rules and Regulations]
[Pages 21816-21842]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2023-06760]
[[Page 21815]]
Vol. 88
Tuesday,
No. 69
April 11, 2023
Part III
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Computer Room Air
Conditioners; Final Rule
Federal Register / Vol. 88, No. 69 / Tuesday, April 11, 2023 / Rules
and Regulations
[[Page 21816]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE-2021-BT-TP-0017]
RIN 1904-AE45
Energy Conservation Program: Test Procedure for Computer Room Air
Conditioners
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (``DOE'') is publishing a final
rule to amend its test procedure for computer room air conditioners
(``CRACs''). DOE is incorporating by reference the latest version of
the relevant industry consensus test standard, AHRI 1360-2022. DOE is
also adopting the net sensible coefficient of performance (``NSenCOP'')
metric in its test procedures for CRACs. Additionally, DOE is amending
certain provisions for representations and enforcement.
DATES: The effective date of this rule is May 11, 2023. The final rule
changes will be mandatory for CRAC equipment testing starting April 5,
2024. The incorporation by reference of certain materials listed in
this rule is approved by the Director of the Federal Register on May
11, 2023.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at www.regulations.gov
under docket number EERE-2021-BT-TP-0017. All documents in the docket
are listed in the www.regulations.gov index. However, not all documents
listed in the index may be publicly available, such as those containing
information that is exempt from public disclosure.
A link to the docket web page can be found at: www.regulations.gov/docket/EERE-2021-BT-TP-0017. The docket web page contains instructions
on how to access all documents, including public comments, in the
docket.
For further information on how to review the docket, contact the
Appliance and Equipment Standards Program staff at (202) 287-1445 or by
email: [email protected].
FOR FURTHER INFORMATION CONTACT:
Ms. Catherine Rivest, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, EE-5B,
1000 Independence Avenue SW, Washington, DC 20585-0121. Telephone:
(202) 586-7335. Email: [email protected].
Mr. Eric Stas, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC 20585-0121.
Telephone: (202) 586-5827. Email: [email protected].
SUPPLEMENTARY INFORMATION: DOE incorporates by reference the following
industry standards:
AHRI Standard 1360-2022 (I-P), ``2022 Standard for Performance
Rating of Computer and Data Processing Room Air Conditioners'',
copyright 2022 (``AHRI 1360-2022'') into parts 429 and 431.
ANSI/ASHRAE Standard 37-2009, ``Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment,''
approved June 24, 2009 (``ANSI/ASHRAE 37-2009'') into part 431.
ASHRAE Standard 127-2007, ``Method of Testing for Rating Computer
and Data Processing Room Unitary Air Conditioners'', approved June 28,
2007 (``ANSI/ASHRAE 127-2007'') into part 431.
ANSI/ASHRAE 127-2020, ``Method of Testing for Rating Air-
Conditioning Units Serving Data Center (DC) and Other Information
Technology Equipment (ITE) Spaces'', ANSI-approved November 30, 2020
(``ANSI/ASHRAE 127-2020'') into part 431.
Copies of AHRI 1360-2022 can be obtained from the Air-Conditioning,
Heating, and Refrigeration Institute (``AHRI''), 2311 Wilson Blvd.,
Suite 400, Arlington, VA 22201, (703) 524-8800, or online at:
www.ahrinet.org.
Copies of ANSI/ASHRAE 37-2009, ANSI/ASHRAE 127-2007, and ANSI/
ASHRAE 127-2020, can be obtained from the American National Standards
Institute (``ANSI''), 25 W 43rd Street, 4th Floor, New York, NY 10036,
(212) 642-4900, or online at: webstore.ansi.org/.
For a further discussion of these standards, see section IV.N of
this document.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Scope of Applicability
B. Revised Organization of the CRAC Test Procedure
C. Updates to Industry Test Standards
D. Definitions
1. CRAC Definition
2. CRAC Configuration Definitions
E. Metric
1. NSenCOP
2. Integrated Efficiency Metric
3. Part-Load Operation and Air Circulation Mode
4. Controls Verification Procedure
F. Configuration of Unit Under Test
1. Background and Summary
2. Approach for Exclusion of Certain Components
3. Non-Standard Indoor Fan Motors
G. Represented Values
1. Multiple Refrigerants
2. Net Sensible Cooling Capacity
3. Validation Class for Glycol-Cooled CRACs
H. Effective and Compliance Dates
I. Test Procedure Costs
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866 and 13563
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Small, large, and very large commercial package air conditioning
and heating equipment are included in the list of ``covered equipment''
for which the U.S. Department of Energy (``DOE'') is authorized to
establish and amend energy conservation standards and test procedures.
(42 U.S.C. 6311(1)(B)-(D)) Commercial package air conditioning and
heating equipment includes computer room air conditioners (``CRACs'')
as an equipment category. DOE's test procedures for CRACs are currently
prescribed at title 10 of the Code of Federal Regulations (``CFR''),
Table 1 to Sec. 431.96. The following sections discuss DOE's authority
to establish and amend test procedures for CRACs and relevant
background information regarding DOE's consideration of amendments to
the test procedures for this equipment.
[[Page 21817]]
A. Authority
The Energy Policy and Conservation Act, as amended (``EPCA''),\1\
among other things, authorizes DOE to regulate the energy efficiency of
a number of consumer products and certain industrial equipment. (42
U.S.C. 6291-6317) Title III, Part C \2\ of EPCA, Public Law 94-163 (42
U.S.C. 6311-6317, as codified), added by Public Law 95-619, Title IV,
section 441(a), established the Energy Conservation Program for Certain
Industrial Equipment, which sets forth a variety of provisions designed
to improve energy efficiency. This covered equipment includes small,
large, and very large commercial package air conditioning and heating
equipment. (42 U.S.C. 6311(1)(B)-(D)) Commercial package air
conditioning and heating equipment includes CRACs, which are the
subject of this final rule.
---------------------------------------------------------------------------
\1\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020), which reflect the last statutory amendments that impact
Parts A and A-1 of EPCA.
\2\ For editorial reasons, upon codification in the U.S. Code,
Part C was redesignated Part A-1.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. Relevant
provisions of EPCA include definitions (42 U.S.C. 6311), energy
conservation standards (42 U.S.C. 6313), test procedures (42 U.S.C.
6314), labeling provisions (42 U.S.C. 6315), and the authority to
require information and reports from manufacturers (42 U.S.C. 6316).
The Federal testing requirements consist of test procedures that
manufacturers of covered equipment must use as the basis for: (1)
certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted pursuant to EPCA (42 U.S.C.
6316(b); 42 U.S.C. 6296), and (2) making other representations about
the efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE
uses these test procedures to determine whether the equipment complies
with relevant standards promulgated under EPCA.
Federal energy efficiency requirements for covered equipment
established under EPCA generally supersede State laws and regulations
concerning energy conservation testing, labeling, and standards. (42
U.S.C. 6316(a) and (b); 42 U.S.C. 6297) DOE may, however, grant waivers
of Federal preemption in limited circumstances for particular State
laws or regulations, in accordance with the procedures and other
provisions of EPCA. (42 U.S.C. 6316(b)(2)(D))
Under 42 U.S.C. 6314, EPCA also sets forth the criteria and
procedures DOE must follow when prescribing or amending test procedures
for covered equipment. Specifically, EPCA requires that any test
procedures prescribed or amended under this section must be reasonably
designed to produce test results which reflect energy efficiency,
energy use, or estimated annual operating cost of a given type of
covered equipment (or class thereof) during a representative average
use cycle and requires that test procedures not be unduly burdensome to
conduct. (42 U.S.C. 6314(a)(2))
EPCA requires that the test procedures for commercial package air
conditioning and heating equipment (of which CRACs are a category) be
those generally accepted industry testing procedures or rating
procedures developed or recognized by the Air-Conditioning, Heating and
Refrigeration Institute (``AHRI'') or by the American Society of
Heating, Refrigerating, and Air-Conditioning Engineers (``ASHRAE''), as
referenced in ASHRAE Standard 90.1, ``Energy Standard for Buildings
Except Low-Rise Residential Buildings'' (``ASHRAE Standard 90.1''). (42
U.S.C. 6314(a)(4)(A)) Further, if such an industry test procedure is
amended, DOE must update its test procedure to be consistent with the
amended industry test procedure, unless DOE determines, by rule
published in the Federal Register and supported by clear and convincing
evidence, that such amended test procedure would not meet the
requirements in 42 U.S.C. 6314(a)(2) and (3) related to representative
use and test burden. (42 U.S.C. 6314(a)(4)(B))
EPCA also requires that, at least once every seven years, DOE
evaluate test procedures for each type of covered equipment, including
CRACs, to determine whether amended test procedures would more
accurately or fully comply with the requirements for the test
procedures to not be unduly burdensome to conduct and be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs during a representative average use
cycle. (42 U.S.C. 6314(a)(1)-(3))
In addition, if DOE determines that a test procedure amendment is
warranted, the Department must publish proposed test procedures in the
Federal Register and afford interested persons an opportunity (of not
less than 45 days' duration) to present oral and written data, views,
and arguments on the proposed test procedures. (42 U.S.C. 6314(b)) If
DOE determines that test procedure revisions are not appropriate, DOE
must publish in the Federal Register its determination not to amend the
test procedures. (42 U.S.C. 6314(a)(1)(A)(ii))
DOE is publishing this final rule amending the test procedure for
CRACs in satisfaction of its aforementioned obligations under EPCA.
B. Background
On May 16, 2012, DOE published a final rule in the Federal
Register, which, in relevant part, adopted test procedures for CRACs
that incorporate by reference American National Standards Institute
(``ANSI'')/ASHRAE Standard 127-2007, ``Method of Testing for Rating
Computer and Data Processing Room Unitary Air Conditioners'' (``ANSI/
ASHRAE 127-2007''), which was the industry test procedure referenced in
ASHRAE Standard 90.1-2010 for CRACs, as the basis for the Federal test
procedure for such equipment. 77 FR 28928, 28989.
On October 26, 2016, ASHRAE published ASHRAE Standard 90.1-2016,
which included updates to the test procedure (``TP'') references for
CRACs as compared to ASHRAE Standard 90.1-2010 and ASHRAE Standard
90.1-2013.\3\ This action by ASHRAE triggered DOE's obligations under
42 U.S.C. 6314(a)(4)(B), as outlined previously. Accordingly, DOE
published a request for information (``RFI'') in the Federal Register
on July 25, 2017 (``July 2017 ASHRAE TP RFI'') to collect information
and data in consideration of amendments to DOE's test procedures for
commercial package air conditioning and heating equipment, given the
test procedure updates included in ASHRAE Standard 90.1-2016. 82 FR
34427. Following the July 2017 ASHRAE TP RFI, AHRI published additional
updates to its test procedure standard for CRACs on December 21, 2017
(i.e., AHRI Standard 1360-2017, ``2017 Standard for Performance Rating
of Computer and Data Processing Room Air Conditioners'' (``AHRI 1360-
2017'')). ASHRAE published ASHRAE Standard 90.1-2019 on October 24,
2019, which updated the test procedure referenced for CRACs from AHRI
1360-2016 to AHRI 1360-2017 and added equipment classes for ceiling-
mounted CRACs. Following the publication of ASHRAE Standard 90.1-2019,
AHRI initiated work on an update to AHRI Standard 1360 (i.e., AHRI
Standard 1360-202X Draft, ``Performance Rating of Computer and Data
Processing Room
[[Page 21818]]
Air Conditioners (``Draft Standard'')'' (``AHRI 1360-202X Draft'').
---------------------------------------------------------------------------
\3\ More specifically, ASHRAE Standard 90.1-2016 references AHRI
1360-2016, ``Standard for Performance Rating of Computer and Data
Processing Room Air Conditioners'' for CRACs.
---------------------------------------------------------------------------
On February 7, 2022, DOE published in the Federal Register a notice
of proposed rulemaking (``NOPR'') (``February 2022 NOPR'') proposing,
in relevant part, to update the Federal test procedure for CRACs
consistent with AHRI 1360-202X Draft. 87 FR 6948. A copy of the draft
was added to the docket for this rulemaking for review by interested
parties.\4\ As stated in the February 2022 NOPR, if AHRI were to
publish a final version of AHRI 1360-202X Draft prior to DOE publishing
a final rule, DOE's intention would be to reference the latest version
of AHRI 1360 in the final rule. 87 FR 6948, 6951 (Feb. 7. 2022). DOE
held a public meeting webinar on March 15, 2022, to discuss the
proposed amendments to the CRACs test procedure presented in the
February 2022 NOPR.
---------------------------------------------------------------------------
\4\ The AHRI 1360-202X Draft test procedure is available in the
docket for this rulemaking at: www.regulations.gov/document/EERE-2021-BT-TP-0017-0001.
---------------------------------------------------------------------------
DOE received several comments in response to the February 2022
NOPR. Table I.1 lists the commenters, along with each commenter's
abbreviated name used throughout the final rule. Discussion of these
comments, along with DOE's responses, are provided in the appropriate
sections of this document.
---------------------------------------------------------------------------
\5\ AHRI's comment was received 23 days after the comment
submission deadline.
Table I.1--List of Commenters With Written Submissions in Response to the February 2022 NOPR
----------------------------------------------------------------------------------------------------------------
Abbreviation used in this Comment No. in
Commenter(s) final rule the docket Commenter type
----------------------------------------------------------------------------------------------------------------
Air-Conditioning, Heating and AHRI \5\.................. 9 Industry Trade
Refrigeration Institute. Organization.
Appliance Standards Awareness Project, Joint Advocates........... 7 Efficiency Advocacy
American Council for an Energy- Organizations.
Efficient Economy, Natural Resources
Defense Council and New York State
Energy Research and Development
Authority.
Northwest Energy Efficiency Alliance.... NEEA...................... 5 Efficiency Advocacy
Organization.
Pacific Gas and Electric Company CA IOUs................... 6 Utilities.
(``PG&E''), San Diego Gas and Electric,
and Southern California Edison;
collectively, the California Investor-
Owned Utilities.
----------------------------------------------------------------------------------------------------------------
A parenthetical reference at the end of a comment quotation or
paraphrase provides the location of the item in the public record.\6\
To the extent that interested parties have provided written comments
that are substantively similar to any oral comments provided during the
March 15, 2022 NOPR public meeting, DOE cites the written comments
throughout this final rule. Any oral comments provided during the
webinar that are substantively distinct from a submitter's written
comments are summarized and cited separately throughout this final
rule.\7\
---------------------------------------------------------------------------
\6\ The parenthetical reference provides a reference for
information located in the docket of DOE's rulemaking to develop
test procedures for CRACs. (Docket No. EERE-2021-BT-TP-0017, which
is maintained at www.regulations.gov.) The references are arranged
as follows: (commenter name, comment docket ID number, page of that
document).
\7\ The March 15, 2022 TP NOPR Public Meeting Transcript can be
found in the docket for this rulemaking at: www.regulations.gov
under entry number EERE-2021-BT-TP-0017-0008. Comments arising from
the public meeting are cited as follows: (commenter name, Public
Meeting Transcript, No. 8 at p. X).
---------------------------------------------------------------------------
On March 7, 2022, DOE published in the Federal Register a NOPR
proposing revised energy conservation standards (``March 2022 ECS
NOPR'') for CRACs in terms of net sensible coefficient of performance
(``NSenCOP''). 87 FR 12802. DOE conducted a crosswalk analysis to
translate the current Federal standards in terms of sensible
coefficient of performance (``SCOP'') to equivalent levels in terms of
NSenCOP to evaluate potential amendments to the energy conservation
standards, as appropriate. Id. at 87 FR 12817-12826. Any comments
received in response to the February 2022 NOPR that pertain to energy
conservation standards will be addressed in the energy conservation
standards rulemaking and are not addressed in this document.
In November, 2022, AHRI finalized AHRI 1360-202X Draft without
substantial change and published AHRI Standard 1360-2022, ``Performance
Rating of Computer and Data Processing Room Air Conditioners (``AHRI
1360-2022'').
In January 2023, ASHRAE published the 2022 edition of ASHRAE
Standard 90.1, ``Energy Standard for Buildings Except Low-Rise
Residential Buildings'' (``ASHRAE Standard 90.1-2022''). ASHRAE
Standard 90.1-2022 maintains AHRI 1360-2017 as the referenced test
procedure reference for CRACs.
II. Synopsis of the Final Rule
In this final rule, DOE is updating its regulations for CRACs by:
(1) incorporating by reference the updated version of AHRI Standard
1360 (i.e., AHRI 1360-2022), as well as the relevant industry test
standards referenced in AHRI 1360-2022; (2) establishing provisions for
determining NSenCOP for CRACs; (3) clarifying the definition of a
``computer room air conditioner'' to include consideration of how the
equipment is marketed; and (4) amending certain provisions for
representations and enforcement in 10 CFR part 429, consistent with the
changes adopted in the test procedure. In terms of implementation, DOE
is adding new appendices E and E1 to subpart F of 10 CFR part 431,
``Uniform test method for measuring the energy consumption of computer
room air conditioners,'' (``appendix E'' and ``appendix E1,''
respectively). The current DOE test procedure for CRACs is being
relocated to appendix E without change, and the new test procedure
incorporating by reference AHRI 1360-2022 is being established in
appendix E1 for determining NSenCOP. Testing in accordance with
appendix E1 is not required until such time as compliance is required
with amended energy conservation standards for CRACs that rely on
NSenCOP, should DOE adopt such standards. After such time, appendix E
will no longer be used as part of the Federal test procedure.
The adopted amendments are summarized in Table II.1 and compared to
the relevant test procedure provisions in place prior to the amendment,
as well as the reason for the adopted change.
[[Page 21819]]
Table II.1--Summary of Changes in the Amended CRACs Test Procedure
Relative to Current Test Procedure
------------------------------------------------------------------------
DOE test procedure prior to Amended test
amendment procedure Attribution
------------------------------------------------------------------------
Located in 10 CFR 431.96.... Current test Improve readability.
procedure unchanged
but relocated to
appendix E.
Incorporates by reference Incorporates by Updates to the
ANSI/ASHRAE 127-2007. reference in a new applicable industry
appendix E1--AHRI test procedures.
1360-2022, ANSI/
ASHRAE 127-2020,
and ANSI/ASHRAE 37-
2009.
Includes provisions for Includes provisions Updates to the
determining SCOP. for determining applicable industry
NSenCOP in appendix test procedures.
E1.
CRAC definition criteria CRAC definition To more clearly
include: (1) used in criteria include: define CRACs and
computer rooms (or similar (1) marketed for distinguish from
applications); (2) whether use in computer other equipment
rated for SCOP and tested rooms (or similar categories.
in accordance with 10 CFR applications); and
431.96; and (3) not a (2) not a consumer
consumer product. product.
Does not specify provisions Defines roof, wall, Updates to the
specific to testing roof, and ceiling-mounted applicable industry
wall, and ceiling-mounted CRAC configurations test procedures.
CRAC units. and provides test
provisions specific
to such units.
Does not include CRAC- Includes provisions Establish CRAC-
specific provisions for in 10 CFR 429.43 specific provisions
determination of specific to CRACs for determination
represented values in 10 to determine of represented
CFR 429.43. represented values values.
for models with
specific components
and prevent cooling
capacity over-
rating.
Does not include CRAC- Adopts product- Establish provisions
specific enforcement specific for DOE enforcement
provisions in 10 CFR enforcement testing of CRACs.
429.134. provisions for
CRACs regarding
verification of
cooling capacity
and testing of
units with specific
components.
------------------------------------------------------------------------
DOE has determined that the amendments described in section III of
this final rule regarding the establishment of appendix E do not alter
the measured efficiency of CRACs or require retesting solely as a
result of DOE's adoption of the amendments to the test procedure. DOE
has determined, however, that the test procedure amendments in appendix
E1 do alter the measured efficiency of CRACs and that such amendments
are consistent with the updated industry test procedure. Further, use
of appendix E1 and the amendments to the representation requirements in
10 CFR 429.43 are not required until the compliance date of any amended
standards denominated in terms of NSenCOP, if adopted. However,
manufacturers may use appendix E1 to certify compliance with any
amended standards prior to the applicable compliance date for those
standards. Additionally, DOE has determined that the finalized
amendments will not increase the cost of testing. The effective date
for the amended test procedures adopted in this final rule is 30 days
after publication of this document in the Federal Register. Detailed
discussion of DOE's actions is included in section III of this final
rule.
III. Discussion
A. Scope of Applicability
DOE currently defines ``computer room air conditioner'' as a basic
model of commercial package air-conditioning and heating equipment
(packaged or split) that is: used in computer rooms, data processing
rooms, or other information technology cooling applications; rated for
SCOP and tested in accordance with 10 CFR 431.96; and is not a covered
consumer product under 42 U.S.C. 6291(1)-(2) and 42 U.S.C. 6292. A CRAC
may be provided with, or have as available options, an integrated
humidifier, temperature and/or humidity control of the supplied air,
and reheating function. 10 CFR 431.92. DOE did not receive any comments
from stakeholders regarding any revision of scope for this rulemaking.
As discussed in section III.D.1 of this document, DOE is amending
the definition of CRAC in this final rule. Specifically, DOE is
revising the definition of ``computer room air conditioner'' to mean
commercial package air conditioning and heating equipment (packaged or
split) that is: marketed for use in computer rooms, data processing
rooms, or other information technology cooling applications and not a
covered consumer product under 42 U.S.C. 6291(1)-(2) and 6292. A
computer room air conditioner may be provided with, or have as
available options, an integrated humidifier, temperature and/or
humidity control of the supplied air, and reheating function. Computer
room air conditioners include, but are not limited to, the following
configurations as defined in 10 CFR 431.92: down-flow, horizontal-flow,
up-flow ducted, up-flow non-ducted, ceiling-mounted ducted, ceiling
mounted non-ducted, roof-mounted, and wall-mounted. The scope of the
CRAC test procedure, as amended by this final rule, is based on this
revised definition.
B. Revised Organization of the CRAC Test Procedure
In the February 2022 NOPR, DOE proposed to relocate and centralize
the current test procedure for CRACs to a new appendix E to subpart F
of 10 CFR part 431, without change. 87 FR 6948, 6952 (Feb. 7, 2022). As
proposed, appendix E would continue to reference ANSI/ASHRAE 127-2007
and provide instructions for determining SCOP. Id. As proposed, CRACs
would be required to be tested according to appendix E until such time
as compliance is required with amended energy conservation standards
that rely on the NSenCOP metric, should DOE adopt such standards. Id.
Accordingly, in parallel, DOE proposed to establish an amended test
procedure for CRACs that adopted the substance of AHRI 1360-202X Draft
in a new appendix E1 to subpart F of 10 CFR part 431. Id. DOE noted
that it intended to incorporate by reference the final published
version of AHRI 1360-202X Draft in the final rule, unless there were
substantive changes between the draft and published versions, in which
case DOE may adopt the substance of AHRI 1360-202X Draft or provide
additional opportunity for comment on changes presented in the final
version of the industry consensus test standard. Id. DOE noted that
CRACs would not be
[[Page 21820]]
required to be tested according to the test procedure in appendix E1
until such time as compliance is required with amended energy
conservation standards that rely on the NSenCOP metric, should DOE
adopt such standards. Id.
DOE did not receive any comments in response to the February 2022
NOPR's proposed reorganization of the test procedure. As discussed in
the following sections of this final rule, DOE is adopting the
finalized version of AHRI 1360 (i.e., AHRI 1360-2022), including the
NSenCOP metric. AHRI 1360-2022 does not include any significant
revisions as compared to AHRI 1360-202X Draft Accordingly, for the
reasons discussed in the February 2022 NOPR and as discussed in the
preceding paragraphs, DOE is finalizing the proposed reorganization of
the test procedure by establishing appendices E and E1 for testing
CRACs.
C. Updates to Industry Test Standards
As noted previously, DOE's current test procedure for CRACs is
codified at 10 CFR 431.96 and incorporates by reference ANSI/ASHRAE
Standard 127-2007,\8\ which is the test procedure recognized by ASHRAE
Standard 90.1-2010 for CRACs. However, the 2019 and 2022 versions of
ASHRAE Standard 90.1 recognize AHRI 1360-2017 as the test procedure for
CRACs.
---------------------------------------------------------------------------
\8\ While ANSI/ASHRAE Standard 127-2007 is incorporated by
reference in its entirety, Table 1 to 10 CFR 431.96 (which defines
the applicable test methods for each category of equipment) excludes
section 5.11 of ANSI/ASHRAE Standard 127-2007 for testing CRACs. The
test procedure also includes additional provisions related to break-
in period and test set-up. See 10 CFR 431.96(c) and (e).
---------------------------------------------------------------------------
After publication of AHRI 1360-2017, DOE and other stakeholders
supported the AHRI 1360 committee in its process to further update AHRI
Standard 1360, which culminated in the publication of AHRI 1360-2022.
AHRI 1360-2022 references ANSI/ASHRAE 127-2020, ``Method of Testing for
Rating Computer and Data Processing Room Unitary Air Conditioners''
(``ANSI/ASHRAE 127-2020''),\9\ and ANSI/ASHRAE 37-2009, ``Methods of
Testing for Rating Electrically Driven Unitary Air-Conditioning and
Heat Pump Equipment'' (``ANSI/ASHRAE 37-2009''). Both AHRI 1360-2017
and AHRI 1360-2022 include significant changes from ANSI/ASHRAE 127-
2007, including the use of NSenCOP instead of SCOP as the test metric.
Both efficiency metrics (NSenCOP and SCOP) are ratios of net sensible
cooling capacity delivered to the power consumed, but there are several
differences in the conditions at which tests are performed. Section
III.E.1 of this final rule includes further discussion of the
differences between these test metrics.
---------------------------------------------------------------------------
\9\ ASHRAE published ANSI/ASHRAE Standard 127-2020 on November
30, 2020.
---------------------------------------------------------------------------
In the February 2022 NOPR, DOE proposed to adopt AHRI 1360-202X
Draft and provided a copy of that industry test standard in the
regulatory docket.\10\ 87 FR 6948, 6952 (Feb. 7, 2022).
---------------------------------------------------------------------------
\10\ See Document No. EERE-2021-BT-TP-0017-0001 at
www.regulations.gov.
---------------------------------------------------------------------------
In response to the February 2022 NOPR, AHRI commented that the AHRI
1360-202X draft standard was not yet complete (at the time), and
manufacturers, particularly those of newly included equipment, had not
yet had an opportunity to evaluate the impact of this change, nor had
the ASHRAE 90.1 committee. (AHRI, No. 9 at p. 2) AHRI further commented
that DOE does not have the authority to adopt a test procedure edition
not yet cited in ASHRAE Standard 90.1 as the national test procedure.
Id. Consequently, AHRI recommended that DOE should adopt AHRI 1360-
2017, continue to work with AHRI and other relevant stakeholders to
finalize the new edition of the test procedure, support the
introduction of a proposed amendment to ASHRAE Standard 90.1, and then
adopt the new procedure as the national test procedure during the next
rulemaking for these products. (AHRI, No. 9 at p. 3)
After the publication of the February 2022 NOPR, AHRI 1360-202X
Draft was finalized and issued as AHRI 1360-2022 in November, 2022.
AHRI 1360-2022 does not include any significant deviations from AHRI
1360-202X Draft. As such, the adoption of AHRI 1360-2022 in this final
rule is consistent with the proposal to reference AHRI 1360-202X Draft
in the February 2022 NOPR.
AHRI's concern regarding the draft status of AHRI 1360-202X Draft
no longer applies, given the subsequent finalization of the draft and
publication of AHRI 1360-2022. DOE notes that the Department was
heavily involved with the AHRI 1360 committee, along with relevant
industry stakeholders, to aid in the development of AHRI 1360-2022. DOE
further notes that AHRI 1360-2022 represents an industry consensus
update to AHRI 1360-2017. DOE disagrees with AHRI's argument that it
lacks statutory authority for the adoption of AHRI 1360-2022, rather
than AHRI 1360-2017, for the reasons that follow.
With respect to small, large, and very large commercial package air
conditioning and heating equipment (of which CRACs are a category),
EPCA directs that when the generally accepted industry testing
procedures or rating procedures developed or recognized by AHRI or by
ASHRAE, as referenced in ASHRAE Standard 90.1, is amended, the
Secretary shall amend the DOE test procedure consistent with the
amended industry test procedure or rating procedure unless the
Secretary determines, by clear and convincing evidence, that to do so
would not meet the requirements for test procedures to produce results
representative of an average use cycle and is not unduly burdensome to
conduct. (42 U.S.C. 6314(a)(4)(B))
As noted, DOE has a duty under the statute to adopt a test
procedure that produces results representative of the covered
equipment's average use cycle. Here, DOE has concluded, supported by
clear and convincing evidence, that AHRI 1360-2022 would better meet
that criterion of EPCA than AHRI 1360-2017. First, AHRI 1360-2022
includes test provisions for measuring performance of roof-mounted and
wall-mounted CRACs, configurations which are not considered in AHRI
1360-2017. Were DOE to adopt AHRI 1360-2017 instead of AHRI 1360-2022,
the DOE test procedure would not address representations for these
configurations in terms of NSenCOP. Second, AHRI 1360-2022 provides
clarifications and additional test requirements on several test
procedure elements, including test tolerances, enclosure for CRACs with
compressors in indoor units, secondary verification of capacity, ducted
condensers, and refrigerant charging instructions. These elements were
discussed in detail in the February 2022 NOPR. See 87 FR 6948, 6960-
6963 (Feb. 7, 2022). These additional test requirements improve the
representativeness of the CRACs test procedure. For these reasons, DOE
considers AHRI 1360-2022 to be more representative of CRAC operation
than AHRI 1360-2017. With this finding made, DOE does not read EPCA as
requiring the Department to dissect the industry standard and
surgically transplant individual provisions of the new industry
standard into the prior industry standard. DOE views the industry test
standard as a functioning whole, so the approach AHRI suggests could
insert errors and inconsistencies into the industry standard, as would
prevent its proper functioning in practice as part of the DOE test
procedure. Further, even if AHRI's approach were possible, it would be
largely unnecessary; adoption of all the major provisions of the latest
industry
[[Page 21821]]
test standard would arguably result in the remaining provisions being
uncontroversial. Again, DOE would point out that the test procedure in
question is the most current version of the industry's own approved
test procedure, even if ASHRAE Standard 90.1 has not yet caught up with
such change. DOE considered AHRI 1360-2017, as EPCA requires, but it
ultimately determined that AHRI 1360-2022 would produce results that
better reflect an average use cycle than would AHRI 1360-2017. DOE has
concluded that EPCA does not allow the Department to turn a blind eye
to such real world developments.
Furthermore, DOE believes that Congress foresaw the practical
benefits of a statutory reading consistent with DOE's interpretation.
Although DOE recognizes that adopting AHRI 1360-2022 as the Federal
test procedure for CRACs may create some disharmony between the Federal
test procedure and the test procedure currently specified in ASHRAE
Standard 90.1 for a period of time, such situation is arguably
preferable to the alternative in which DOE and stakeholders would need
to waste significant resources to reinitiate another rulemaking in
short order after this proceeding to once again amend the Federal test
procedure for CRACs to update the reference therein from AHRI 1360-2017
to AHRI 1360-2022--the very same testing standard available for
consideration at the present time.
Finally, DOE notes that manufacturers are not required to use the
test procedure to certify compliance with any energy conservation
standards for CRACs until the compliance date established for such
standards denominated in terms of the NSenCOP metric, if DOE proceeds
to adopt such standards. The difference in ratings between measuring
SCOP per the current Federal test procedure and measuring NSenCOP per
the test procedure adopted in this final rule (which incorporates by
reference AHRI 1360-2022) is addressed in the ongoing energy
conservation standards rulemaking (see 87 FR 12802 (March 7, 2022)).
Therefore, in light of these updates to the relevant industry
consensus standards and for the reasons explained, DOE is amending its
test procedure for CRACs by incorporating by reference AHRI 1360-2022
for use in the new appendix E1. Specifically, in the new test procedure
for CRACs at appendix E1, DOE is adopting sections 3.1, 3.2.2, 3.2.7,
3.2.22, 3.2.25, 3.2.27, 3.2.28, 3.2.37, 3.2.38, 5, 6.1-6.3, 6.6, and
6.8 and Appendices C, E, and F of AHRI 1360-2022 for the Federal test
procedure for CRACs.\11\
---------------------------------------------------------------------------
\11\ DOE notes that the substance of these provisions remains
the same as those proposed in the February 2022 TP NOPR, but AHRI
did some reorganization in moving from AHRI 1360-202X Draft to AHRI
1360-2022. Consequently, the adopted section numbers cited here
differ from those presented in DOE's proposed rule. See 87 FR 6948,
6952 (Feb. 7, 2022).
---------------------------------------------------------------------------
In the February 2022 NOPR, DOE proposed to incorporate by reference
several industry standards that are internally referenced by AHRI 1360-
202X Draft. First, DOE proposed to incorporate by reference ANSI/ASHRAE
127-2020. Specifically, in the proposed test procedure for CRACs at 10
CFR part 431, subpart F, appendix E1, DOE proposed to reference Figure
A-1, Test duct for measuring air flow and static pressure on downflow
units, of Appendix A of ANSI/ASHRAE 127-2020, because Figure A-1 of
Appendix A is referenced in section 5.8 of AHRI 1360-202X Draft.
Second, DOE proposed to incorporate by reference ANSI/ASHRAE 37-2009
because section 5, Appendix D, and Appendix E of AHRI 1360-202X Draft
reference methods of test in ANSI/ASHRAE 37-2009. More specifically,
DOE proposed to adopt all sections of ANSI/ASHRAE 37-2009, except
sections 1, 2, and 4. 87 FR 6948, 6952 (Feb. 7, 2022).
DOE did not receive any comments in response to its proposal to
reference ANSI/ASHRAE 127-2020 and ANSI/ASHRAE 37-2009 in the test
method for CRACs. These standards are also referenced in the finalized
standard, AHRI 1360-2022, which DOE is incorporating by reference in
this final rule. Therefore, for the reasons discussed in the preceding
paragraphs and in the February 2022 NOPR, DOE incorporates by reference
ANSI/ASHRAE 127-2020 and ANSI/ASHRAE 37-2009, and adopts the relevant
sections for testing CRACs, as proposed in the February 2022 NOPR.
D. Definitions
1. CRAC Definition
As discussed, DOE currently defines a CRAC as a basic model of
commercial package air-conditioning and heating equipment (packaged or
split) that is: used in computer rooms, data processing rooms, or other
information technology cooling applications; rated for SCOP and tested
in accordance with 10 CFR 431.96; and is not a covered consumer product
under 42 U.S.C. 6291(1)-(2) and 42 U.S.C. 6292. 10 CFR 431.92. A
computer room air conditioner may be provided with, or have as
available options, an integrated humidifier, temperature and/or
humidity control of the supplied air, and reheating function. Id. In
defining a CRAC, DOE was unable to identify physical characteristics
that consistently distinguish CRACs from other categories of commercial
package air conditioning and heating equipment that provide comfort-
cooling. See 77 FR 16769, 16772-16774 (March 22, 2012); 77 FR 28928,
28947-28948 (May 16, 2012).
In the February 2022 NOPR, DOE proposed to amend the CRAC
definition to include how the manufacturer markets a model for use,
consistent with the definition in the draft industry standard, AHRI
1360-202X Draft, which also defines CRACs based on marketing.\12\ 87 FR
6948, 6952-6954 (Feb. 7, 2022). DOE also proposed to remove the current
wording ``. . . rated for sensible coefficient of performance (SCOP)
and tested in accordance with 10 CFR 431.96'' to ensure that a unit
that otherwise meets the definition of a CRAC would be covered as a
CRAC regardless of how the manufacturer has tested and rated the model.
Id. DOE also proposed to remove the unnecessary current wording ``. . .
a basic model of'' to avoid confusion as to whether the equipment
constitutes a basic model--DOE specifies different basic model
definitions for each equipment category at 10 CFR 431.92--before the
determination is made whether the equipment meets the CRAC definition.
Id. Specifically, DOE proposed to define ``computer room air
conditioner'' as commercial package air conditioning and heating
equipment (packaged or split) that is: marketed for use in computer
rooms, data processing rooms, or other information technology cooling
applications; and not a covered consumer product under 42 U.S.C.
6291(1)-(2) and 6292. Id. The definition stated that a computer room
air conditioner may be provided with, or have as available options, an
integrated humidifier, temperature and/or humidity control of the
supplied air, and reheating function. Id. Additionally, DOE proposed to
specify in the definition that computer room air conditioners include,
but are not limited to, the following configurations as defined in 10
CFR 431.92: down-flow, horizontal-flow, up-flow ducted, up-flow non-
ducted, ceiling-mounted
[[Page 21822]]
ducted, ceiling mounted non-ducted, roof-mounted, and wall-mounted. Id.
---------------------------------------------------------------------------
\12\ Section 3.5 of AHRI 1360-202X Draft defines ``computer room
air conditioner'' as a subset of ``computer and data processing room
air conditioner.'' Section 3.4 of AHRI 1360-202X Draft defines
``computer and data processing room air conditioner,'' as an air
conditioning unit specifically marketed for cooling data centers and
information technology equipment.
---------------------------------------------------------------------------
In the February 2022 NOPR, DOE requested comment on the proposed
definition for ``computer room air conditioner'' that distinguishes
between CRACs and other categories of air conditioning equipment, based
on the marketing of the equipment. 87 FR 6948, 6954 (Feb. 7, 2022).
AHRI recommended that DOE remove roof-mounted and wall-mounted
units from the CRAC definition, as they are currently not included in
the scope of AHRI 1360-2017 and of ASHRAE Standard 90.1-2019. (AHRI,
No. 9 at pp. 4-5) Instead, AHRI expressed support for a definition
consistent with DOE's proposal, but with roof-mounted and wall-mounted
CRACs redacted from the definition. Id.
The CA IOUs recommended adding the term ``exclusively'' to the
proposed revised CRAC definition and to exclude comfort cooling
products that are sometimes marketed for use in computer rooms (or
similar applications) from the requirement to be tested to the CRAC
test procedure. (CA IOUs, No. 6 at p. 1) The CA IOUs provided estimated
performance data at CRAC rating conditions for commercial unitary air
conditioners (``CUACs'') and 3-phase central air conditioners that they
asserted as indicating that these equipment categories will always meet
the CRAC efficiency standards in ASHRAE Standard 90.1-2019. (CA IOUs,
No. 6 at pp. 1-5) The CA IOUs did not analyze the performance of
single-packaged vertical air conditioners (``SPVU'') equipment under
the CRAC test conditions but noted that DOE's energy efficiency metric
for SPVUs is also energy efficiency ratio (``EER''), that SPVUs are
tested at the same conditions as CUACs, and that the energy
conservation standards for SPVUs are similar to the CUAC EER
requirements in ASHRAE Standard 90.1-2019. Therefore, the CA IOUs
recommended that DOE should also exclude SPVUs from the requirement of
testing to the CRAC test procedure for equipment marketed for use in
computer rooms (or similar applications). Id. Alternatively, the CA
IOUs recommended that DOE allow NSenCOP to be calculated with an
alternate efficiency determination method (``AEDM''). (CA IOUs, No. 6
at p. 6)
In response to AHRI, the addition of roof-mounted and wall-mounted
CRACs to the scope of AHRI 1360-202X Draft, and as finalized in AHRI
1360-2022, occurred after considerable deliberation in the AHRI 1360
committee, in which DOE actively participated. As such, DOE considers
this inclusion in a published AHRI standard to now represent industry
consensus that models meeting the definition of roof-mounted and wall-
mounted CRACs should be tested to AHRI 1360-2022. Further, DOE has
concluded that because such models meet the definition of CRAC and
exist on the market, the Federal test procedure should include test
provisions for such models. Therefore, DOE has determined the addition
of these configurations to be appropriate for the CRAC Federal test
procedure.
In response to CA IOUs, DOE is not adopting the suggested
exclusionary language (i.e., limiting coverage of CRAC regulations to
models marketed exclusively for computer room cooling applications)
because this would cause any CRAC equipment marketed for both data
centers and comfort cooling to not meet the definition of a CRAC as set
out in AHRI 1360-2022. To the extent that a basic model is covered
under more than one equipment category (e.g., CRAC and CUAC), it would
be subject to the regulations applicable to each equipment class that
covers that basic model. Regarding AEDMs, DOE notes that current DOE
regulations already allow manufacturers to use AEDMs to develop CRAC
efficiency ratings, provided they perform physical testing on two test
models per validation class. 10 CFR 429.70(c)(2).
In summary, for the reasons discussed, DOE is updating the
``computer room air conditioner'' definition in 10 CFR 431.92 as
proposed in the February 2022 NOPR. Further, regarding the ``marketed
for'' criterion in the revised CRAC definition, DOE will consider any
publicly-available document published by the manufacturer (e.g.,
product literature, catalogs, and packaging labels) to determine the
application for which the equipment is marketed.
2. CRAC Configuration Definitions
CRACs can be installed in a variety of different configurations
that vary by installation location, direction of airflow over the
evaporator coil (e.g., up, down, or horizontal), and by return and
discharge air connections (e.g., raised floor plenum, ducted, free
air). To provide additional instruction as to which configuration (and,
thus, which testing requirements and standards, as applicable) should
be used for testing, the February 2022 NOPR proposed to add definitions
for the following terms, consistent with the definitions in AHRI 1360-
202X Draft: floor-mounted, ceiling-mounted, wall-mounted, roof-mounted,
up-flow, down-flow, horizontal-flow, up-flow ducted, up-flow non-
ducted, ceiling-mounted ducted, ceiling-mounted non-ducted, and fluid
economizer. 87 FR 6948, 6954 (Feb. 7, 2022). DOE requested comment on
the proposed definitions. Id.
AHRI suggested that DOE should adopt definitions consistent with
AHRI 1360-2017, stating that the current draft procedure was not yet
ready for adoption. Instead, AHRI recommended that DOE should wait to
adopt the definitions in AHRI 1360-202X Draft until they are adopted
through the ASHRAE Standard 90.1 process. (AHRI, No. 9 at p. 5)
DOE notes that AHRI's concern about the draft status of AHRI 1360-
202X Draft no longer applies, given the finalization and publication of
AHRI 1360-2022. Furthermore, for the reasons discussed in section III.C
of this document, the Department has concluded that EPCA does not
preclude the agency from considering this updated industry test
standard until it has been formally adopted through the ASHRAE Standard
90.1 process. Accordingly, DOE has concluded that the inclusion of
revised definitions for CRAC configurations in the published AHRI
standard represent industry consensus that these revised definitions in
AHRI 1360-2022 appropriately classify different configurations of
CRACs. DOE notes that the definitions finalized in AHRI 1360-2022 are
substantively the same as those included in DOE's proposal. DOE further
notes that AHRI did not raise substantive issues with the specific
proposed definitions for CRAC configurations. Therefore, DOE has
concluded that the definitions proposed in the February 2022 NOPR,
which are consistent with the updated industry consensus test procedure
AHRI 1360-2022, appropriately classify different configurations of
CRACs to clarify which test conditions apply to each configuration.
As such, DOE is finalizing the definitions as proposed in the
February 2022 NOPR. Specifically, DOE is defining ``floor-mounted,''
``ceiling-mounted,'' ``wall-mounted,'' ``roof-mounted,'' ``up-flow,''
``down-flow,'' ``horizontal-flow,'' ``up-flow ducted,'' ``up-flow non-
ducted,'' ``ceiling-mounted ducted,'' ``ceiling-mounted non-ducted,''
and ``fluid economizer'' as set out in 10 CFR 431.92 \13\ at the end of
this document.
---------------------------------------------------------------------------
\13\ As explained in the February 2022 NOPR, DOE is italicizing
the defined terms within these definitions at 10 CFR 431.92 in order
to signal to the reader which terms are separately defined. 87 FR
6948, 6954 (Feb. 7, 2022).
---------------------------------------------------------------------------
[[Page 21823]]
E. Metric
1. NSenCOP
DOE's current efficiency metric for CRACs is SCOP, which is a ratio
of sensible cooling capacity delivered to the power consumed. For most
categories of air conditioners and heat pumps other than CRACs,
efficiency metrics are calculated based on total cooling capacity
(which includes both sensible cooling and latent cooling). However,
unlike the conditioned spaces in most commercial buildings, computer
rooms and data centers typically have limited human occupancy and
minimal dehumidification requirements, and, thus, primarily require
only sensible cooling. Therefore, SCOP is calculated based on sensible
cooling capacity rather than total cooling capacity.
As discussed, ASHRAE Standard 90.1-2016 amended the efficiency
metric for CRACs from SCOP (measured per ANSI/ASHRAE 127-2007) to
NSenCOP (measured per AHRI 1360-2016). ASHRAE Standard 90.1-2019
subsequently retained NSenCOP as the test metric, but it updated the
test reference to AHRI 1360-2017 (which specifies NSenCOP as the test
metric and has the same test conditions as AHRI 1360-2016). AHRI 1360-
202X Draft also specifies NSenCOP as the test metric and maintains the
rating conditions found in AHRI 1360-2017, while also adding rating
conditions for roof-mounted and wall-mounted units.
Like SCOP, NSenCOP is a ratio of sensible cooling capacity to the
power consumed. However, as discussed in the February 2022 NOPR, the
test procedure to determine NSenCOP differs from that to determine SCOP
in four key aspects: (1) For several CRAC configurations (e.g., down-
flow, up-flow ducted), different indoor entering air temperatures are
specified; (2) for water-cooled CRACs, different entering water
temperatures are specified; (3) for up-flow ducted configurations,
different indoor air external static pressure (``ESP'') requirements
are specified; and (4) for water-cooled and glycol-cooled CRACs,
NSenCOP accounts for energy consumed by fans and pumps that would be
installed in the outdoor heat rejection loop, which is not accounted
for in SCOP. 87 FR 6948, 6956-6957 (Feb. 7, 2022).
In response to the changes to the efficiency metric and referenced
industry test standard for CRACs in ASHRAE Standard 90.1-2019 and AHRI
1360-202X Draft, DOE proposed to update its efficiency metric for CRACs
to NSenCOP and requested comment on its proposal. 87 FR 6948, 6957
(Feb. 7, 2022). DOE also sought feedback on whether the rating
conditions in AHRI 1360-202X Draft are appropriately representative of
field applications. Id.
On this topic, AHRI commented at the NOPR public meeting that it
supported the adoption of NSenCOP as calculated in AHRI 1360-2017, as
opposed to AHRI 1360-202X Draft. (AHRI, Public Meeting Transcript, No.
8 at pp. 11-12) AHRI stated that a minor clarification would be
required to be made in AHRI 1360-2017, which would align the capacity
bins in AHRI 1360-2017 with those in ASHRAE 90.1-2019. Id. AHRI
asserted that the revised approach for up-flow CRACs in a limited-
height set-up would have a measurable impact on the efficiency of those
units, and that the stringency of the standard level established in
ASHRAE Standard 90.1-2019 for this equipment would not correlate to the
efficiency of the equipment as tested with the draft test procedure.
Id. AHRI further asserted that the SCOP to NSenCOP crosswalk would,
therefore, not be a direct crosswalk, at least for the up-flow units
and for any other products for which ESP test requirements have
changed. Id.
In response, DOE notes the fact that the clarification mentioned by
AHRI regarding the capacity demarcations is appropriately addressed in
AHRI 1360-2022.
Regarding the issue of testing up-flow units in a limited-height
set-up, DOE surmises that the inclusion of a limited-height approach in
the finalized AHRI 1360-2022 that aligns with the approach in AHRI
1360-202X Draft indicates that this limited-height approach represents
industry consensus on an appropriate test method. Further, DOE notes
that the current Federal test procedure, which references ANSI/ASHRAE
127-2007, does not have any provisions that allow for testing up-flow
CRAC units in a limited-height set-up. As such, the crosswalk analysis
conducted to translate standards from SCOP to NSenCOP (as presented in
the March 2022 ECS NOPR; see 87 FR 12802, 12817-12822 (March 7, 2022))
compared SCOP as measured per ANSI/ASHRAE 127-2007 to NSenCOP as
measured per AHRI 1360-202X Draft (which is the test procedure DOE
proposed to adopt in the February 2022 NOPR). Therefore, the test
approaches in any intermediate CRAC industry test procedures released
between ANSI/ASHRAE 127-2007 and AHRI 1360-202X Draft (e.g., AHRI 1360-
2017 as mentioned by AHRI) are not relevant for DOE's crosswalk
analysis, as such intermediate industry test procedures were never
proposed or adopted as part of the Federal test procedure.
The CA IOUs provided several recommendations to modify the proposed
test procedure. (CA IOUs, No. 6 at p. 6) First, the CA IOUs recommended
that DOE adopt the same entering air dry-bulb temperature for all CRAC
configurations, asserting that containment, server rack orientation,
and room temperature setpoints have much more significant impacts on
return air temperature than CRAC configuration; therefore, basing test
temperature on CRAC configuration may create arbitrary differences in
efficiency representations among CRAC configurations, which would
result in a market distortion in favor of some configurations over
others. Id. Second, the CA IOUs recommended DOE use 86 [deg]F as the
full-load condenser entering water temperature, as opposed to 83 [deg]F
as prescribed in AHRI 1360-202X Draft, asserting that typically water-
cooled CRACs and other water-cooled heating, ventilation, and air
conditioning (HVAC) equipment receive condenser water via a water-to-
water heat exchanger, and that the 86 [deg]F point takes into account
the approach temperature of such a heat exchanger. Id. The CA IOUs
added that test procedures for three other equipment categories have
used 86 [deg]F as the full-load condenser entering water temperature:
direct expansion-dedicated outdoor air system units (i.e., AHRI
Standard 920-2020), variable refrigerant flow (``VRF'') water-source
heat pumps (i.e., AHRI Standard 1230-2021), and water-source heat pumps
less than 135,000 Btu/h (i.e., ISO 13256-1:1998) Third, the CA IOUs
supported the inclusion of cooling tower/dry cooler fan and heat
rejection pump energy in the CRAC efficiency rating, but suggested that
DOE examine if the power demand adders of 5 percent and 7.5 percent for
water-cooled and glycol-cooled CRACs, respectively, are representative.
Id.
The Joint Advocates supported the inclusion of a power adder for
heat rejection components to improve the representativeness of the test
for water-cooled and glycol-cooled CRACs. (Joint Advocates, No. 7 at p.
1) The Joint Advocates encouraged DOE to investigate the
representativeness of the proposed entering air dry-bulb
temperatures,\14\ asserting that it did not appear that DOE has
performed a thorough analysis of the representativeness of the proposed
temperature values, but was rather simply proposing to adopt the values
in AHRI 1360-202X Draft. (Joint Advocates, No. 7 at p. 1) The Joint
[[Page 21824]]
Advocates referenced the March 2022 ECS NOPR, noting that the impact of
increasing the entering air dry-bulb temperature from 75 [deg]F to 95
[deg]F for up-flow ducted and down-flow CRACs, led to an increase of
net sensible cooling capacity and SCOP by approximately 22 percent and
19 percent, respectively. (Joint Advocates, No. 7 at pp. 1-2) The Joint
Advocates commented that given the large potential magnitude of change
to the metrics, DOE should scrutinize the appropriateness of updating
the entering air dry-bulb temperature values and, if a revision is
found to be justified, the representativeness of the proposed entering
air dry-bulb temperature values. Id.
---------------------------------------------------------------------------
\14\ In their comment, the Joint Advocates refer to this as
``return air temperature.''
---------------------------------------------------------------------------
NEEA recommended that DOE ensure that the required ESP test
conditions are representative of actual ESP conditions that units
experience in the field. (NEEA, No. 5 at p. 4)
As noted earlier, EPCA requires that the test procedures for
commercial package air conditioning and heating equipment be those
generally accepted industry testing procedures or rating procedures
developed or recognized by AHRI or ASHRAE, as referenced in ASHRAE
Standard 90.1. (42 U.S.C. 6314(a)(4)(A)) Further, if such an industry
test procedure is amended, DOE must update its test procedure to be
consistent with the amended industry test procedure, unless DOE
determines, by rule published in the Federal Register and supported by
clear and convincing evidence, that such amended test procedure would
not meet the requirements in 42 U.S.C. 6314(a)(2) and (3) related to
representative use and test burden. (42 U.S.C. 6314(a)(4)(B)) As
discussed in section III.C, DOE has concluded, supported by clear and
convincing evidence, that AHRI 1360-2022 would better meet the
criterion of EPCA than AHRI 1360-2017. DOE is not aware of any data or
information indicating that the entering air dry-bulb temperature or
ESP conditions in AHRI 1360-2022 are not representative of an average
CRAC use cycle, and commenters did not provide any data or information
to contradict this understanding. Therefore, DOE concludes that the
rating conditions finalized in AHRI 1360-2022 are appropriate. The
following paragraphs include DOE's responses to some of the comments
received regarding specific rating conditions in AHRI 1360-202X Draft
(and the subsequently finalized AHRI 1360-2022).
Regarding entering air dry-bulb temperature, it is DOE's
understanding that CRAC configurations in which the return air inlet is
located close to the heat source (e.g., horizontal flow units, which
are typically located adjacent to server racks) have higher entering
air dry-bulb temperatures than configurations with return air inlets
located further from the heat source. Numerous other versions of CRAC
industry test procedures (i.e., ANSI/ASHRAE 127-2020, AHRI 1360-2017,
and AHRI 1360-2016) also include different entering air dry-bulb
temperatures for each configuration that are consistent with AHRI 1360-
202X Draft (and the subsequently finalized AHRI 1360-2022). Regarding
the comment from Joint Advocates, while DOE agrees that differing
entering air dry-bulb temperature values lead to a measurable change in
the evaluated metrics for each configuration, DOE also notes that the
standards proposed in the March 2022 ECS NOPR are separate for each
configuration and reflect the different rating conditions. See 87 FR
12802, 12809-12816 (March 7, 2022). Additionally, industry consensus as
reflected in AHRI 1360-2022 suggests that using the same entering air
dry-bulb temperature for all CRAC configurations would be less
representative of an average use cycle for each unique CRAC
configuration. Therefore, DOE has concluded that different entering air
dry-bulb temperatures for each separate configuration are appropriate
for inclusion in the revised test procedure.
Similarly, ESP conditions may differ for CRAC configurations
depending on how and where they may be installed. As noted earlier, DOE
is not aware of any data or information indicating that the ESP
conditions in AHRI 1360-2022 are not representative of an average CRAC
use cycle, and NEEA did not provide any data or information to
contradict this understanding.
Regarding condenser entering water temperature, ANSI/ASHRAE 127-
2007 prescribes a test condition of 86 [deg]F (as suggested by the CA
IOUs) for SCOP, but the lower 83 [deg]F condition was adopted in
subsequent CRAC industry test procedures--ASHRAE 127-2020, AHRI 1360-
2016, and AHRI 1360-2017--in addition to AHRI 1360-202X Draft (and the
subsequently finalized AHRI 1360-2022). DOE considers that this
decrease in the condenser entering water temperature test condition
from 86 [deg]F to 83 [deg]F was made after industry deliberation and
represents industry consensus. DOE also notes that not all industry
test procedures for other categories of commercial air conditioning and
heating equipment are consistent in entering water temperature test
conditions, as AHRI Standard 340/360-2022, ``Performance Rating of
Commercial and Industrial Unitary Air-conditioning and Heat Pump
Equipment,'' specifies an entering water temperature of 85 [deg]F for
water-cooled CUACs. Therefore, DOE has concluded that the proposed 83
[deg]F condition as the condenser entering water temperature for water-
cooled CRACs is appropriate and would produce the most representative
results.
Regarding the power consumption adders for heat rejection
components for water-cooled and glycol-cooled CRACs, ANSI/ASHRAE 127-
2020, AHRI 1360-2016, and AHRI 1360-2017 also specify the same adders
of 5 percent and 7.5 percent for water-cooled and glycol-cooled CRACs
as proposed in the February 2022 NOPR. After a careful review, DOE was
not able to find any information indicating that these values are not
representative for CRAC installations. Therefore, DOE considers these
demand adders to be appropriate for CRACs.
In summary, DOE is updating its efficiency metric for CRACs to
NSenCOP as measured per AHRI 1360-2022, at appendix E1. Appendix E
continues to reference ANSI/ASHRAE 127-2007 and to provide instructions
for determining SCOP. As noted earlier, CRACs are not required to be
tested according to the test procedure in appendix E1 until such time
as compliance is required with an amended energy conservation standard
that relies on the NSenCOP metric, should DOE adopt such a standard.
2. Integrated Efficiency Metric
In contrast to an efficiency metric that measures performance at
only one test point, an annualized, or ``integrated'' efficiency metric
measures performance at multiple test points (i.e., tests with
different outdoor test conditions) that are intended to reflect
seasonal variation in outdoor ambient temperatures that would be
experienced by the equipment installed in the field.
AHRI 1360-2016, AHRI-1360-2017, and AHRI 1360-202X Draft include an
integrated efficiency metric--integrated net sensible coefficient of
performance (``iNSenCOP''). The iNSenCOP metric comprises a weighted
average of NSenCOP values for four test points at different outdoor
conditions.\15\
---------------------------------------------------------------------------
\15\ The rating conditions A, B, C, and D for iNSenCOP for air-
cooled units correspond to outdoor entering air temperatures of 95.0
[deg]F, 80.0 [deg]F, 65.0 [deg]F, and 40.0 [deg]F, respectively.
---------------------------------------------------------------------------
In the February 2022 NOPR, DOE noted that section D1 of AHRI 1360-
2017 (and section G1 of the subsequently updated AHRI 1360-202X Draft)
states that ``a long-term goal is for iNSenCOP to replace NSenCOP after
a more readily testable means has been
[[Page 21825]]
standardized.'' 87 FR 6948, 6957 (Feb. 7. 2022). DOE indicated that it
was not aware of any test data that verify the validity of the iNSenCOP
metric and that minimum efficiency levels in terms of iNSenCOP have not
been adopted in ASHRAE Standard 90.1. Id. DOE acknowledged the
potential benefit regarding representativeness that would be provided
with an annualized metric for CRACs but concluded that given the
apparent need for further validation and the lack of test data, DOE was
unable to propose to use the iNSenCOP metric at this time. Id.
The Joint Advocates and NEEA encouraged DOE to continue to
investigate an annualized metric for CRACs. (Joint Advocates, No. 7 at
p. 2; NEEA, No. 5 at pp. 1-2) The Joint Advocates commented that CRACs
are designed to provide year-round cooling at a stable indoor cooling
load and that an annualized metric that reflects an integrated measure
of CRAC performance at different outdoor temperatures would be more
representative of the efficiency of this equipment. (Joint Advocates,
No. 7 at p. 2) NEEA commented that it supports DOE's proposal to use
NSenCOP instead of SCOP, but encouraged DOE to conduct the research
required to transition to the iNSenCOP metric, which NEEA asserted
better accounts for the energy efficiency of CRACs given that it
provides a standardized evaluation of the annualized cooling energy
consumption of a unit operated across the specified range of outdoor
ambient temperatures. (NEEA, No. 5 at pp. 1-2) NEEA commented that it
believed integrating a part-load operation assessment was also feasible
when this efficiency metric is adopted for CRACs in the future. Id.
As noted in the February 2022 NOPR, DOE acknowledges the potential
benefit regarding representativeness that would be provided with an
annualized, integrated metric for CRACs. However, given the need for
further validation and the lack of test data, DOE is not adopting the
iNSenCOP metric at this time.
3. Part-Load Operation and Air Circulation Mode
In the July 2017 ASHRAE TP RFI, DOE noted that CRACs typically
operate at part-load (i.e., less than designed full cooling capacity)
in the field. 82 FR 34427, 34432 (July 25, 2017). DOE discussed that
the reasons for this may include, but are not limited to, redundancy in
installed units to prevent server shutdown if a CRAC unit stops
working, and server room designers building in extra cooling capacity
to accommodate additional server racks in the future. Id. DOE also
noted that while the current DOE test procedure measures performance at
full-load, DOE has estimated that CRACs operate on average at a
sensible load of 65 percent of the full-load sensible capacity.\16\ Id.
---------------------------------------------------------------------------
\16\ See the analysis for a final rule for standards and test
procedures for certain commercial heating, air conditioning, and
water heating equipment (including CRACs) published in the Federal
Register on May 16, 2012 (77 FR 28928). (Technical Support Document,
EERE-2011-BT-STD-0029-0021, pp. 4-15, 4-16)
---------------------------------------------------------------------------
Comments received in response to the July 2017 ASHRAE TP RFI and
discussed in the February 2022 NOPR also suggested that CRACs are
commonly oversized when installed in the field, and that this
oversizing can significantly influence performance. 87 FR 6948, 6958
(Feb. 7, 2022). Additionally, in the February 2022 NOPR, DOE noted it
understands that many CRACs operate in air circulation mode and that
incorporating air circulation mode in testing might incentivize use of
more-efficient fan technologies for CRACs that typically operate at
lower fan speeds in air circulation mode. Id. However, DOE did not have
information or data on part-load or air circulation mode operation of
CRACs to support a proposal to amend the efficiency metric to account
for performance in these operating modes. Id.
In response to the February 2022 NOPR, NEEA encouraged DOE to
gather more data on the conditions and the percentage of time when
CRACs typically operate in air circulation mode, noting that this
information will help ensure that DOE's metric for CRACs is
representative of average annual operation, which includes accounting
for energy consumption in these modes. (NEEA, No. 5 at p. 2) Similarly,
NEEA commented that it believes that incorporating part-load
performance in the efficiency metric for CRACs would encourage the
adoption of technologies that improve performance, such as variable-
speed fans and compressors. (NEEA, No. 5 at pp. 2-3) NEAA asserted that
incorporating part-load and air-circulation modes into efficiency
ratings would give consumers better information about the performance
of different CRAC units. (NEEA, No. 5 at p. 3) NEEA agreed with DOE's
statement that there is a lack of information and data on part-load or
air-circulation-mode operation of CRACs, but the commenter recommended
that DOE conduct more research to collect the necessary data to amend
the proposed efficiency metric. Id.
The Joint Advocates encouraged DOE to capture the part-load
operation and air-circulation-mode operation of CRACs. (Joint
Advocates, No. 7 at p. 2) The Joint Advocates asserted that the CRAC
test procedure for determining NSenCOP is not representative of an
average use cycle because many CRACs operate in part-load and air-
circulation mode, and fan energy is not accounted for in the NSenCOP
metric. Id.
The CA IOUs commented that CRACs operate at part load at nearly all
times, so efficient part-load performance is more important than full-
load performance for optimal energy use. (CA IOUs, No. 6 at p. 7) The
CA IOUs referenced studies conducted by PG&E, which they commented
indicate that data centers are typically operated at part load to
ensure maximum temperature and humidity control stability, reliability,
and margin for future load increases. Id. The CA IOUs suggested that
instead of adopting a part-load performance rating requirement at this
time, DOE should consider requiring manufacturers to state the
temperature at which capacity control becomes unstable and when the
CRAC cannot operate within acceptable test capacity tolerance, and that
this information would allow designers to evaluate the suitability of
the part-load performance of different equipment options for specific
applications. Id.
These comments suggest that many CRACs operate in part load and in
air-circulation mode and that incorporating these modes in testing
could lead to a more representative test procedure. However, CRAC
operation in these operating modes has not been addressed in any CRAC
industry consensus test procedures. At this time, DOE does not have
enough information or data on part-load or air-circulation mode
operation of CRACs to support amending the efficiency metric to account
for performance in these operating modes. Regarding CA IOUs' suggestion
to require manufacturers to state the temperature at which capacity
control becomes unstable, DOE has concluded that such provisions do not
apply for testing to a full-load metric, which does not involve
modulation of capacity below full-load. Because the Department is not
adopting a part-load metric in this final rule, DOE is correspondingly
not adopting the CA IOU's suggestion.
4. Controls Verification Procedure
Neither the current Federal test procedure nor AHRI 1360-2022
incorporates a controls verification procedure (``CVP'') for CRACs. The
purpose of a CVP is to validate that the
[[Page 21826]]
observed positions of critical parameters for modulating components
during the CVP are within tolerance of the certified critical parameter
values in the supplementary test instructions (``STI'') that are set by
the manufacturer in steady-state tests. This ensures that the measured
results of the test procedure are based on critical parameter settings
that are representative of critical parameter behavior that would be
experienced in the field.
In response to the February 2022 NOPR, NEEA commented that CRACs
could benefit from a CVP and that a CVP would help ensure that
manufacturer claims of energy savings from controls are accurate and
can help verify that units are achieving the variable-speed benefits
that are claimed. (NEEA, No. 5 at p. 3) NEEA noted that there is
precedence for including a CVP in commercial HVAC products, such as VRF
multi-split air conditioners and heat pumps. Id. NEEA further commented
that a CVP may also check and test the energy savings from economizers,
given that they are not a component of the proposed test procedure for
basic CRAC models, and that incorporating a CVP is one potential way to
capture those energy saving benefits for CRAC units that have an
economizer. Id.
As noted, AHRI 1360-2022, the industry standard that DOE is
adopting in this final rule, does not include a CVP for CRACs. Further,
DOE is not aware of any industry test procedures that include a CVP
that would apply for CRACs. While DOE understands that there may be
potential benefits of implementing a CVP for CRACs and acknowledges the
precedent of a CVP for other commercial equipment such as VRF multi-
split systems, DOE understands that the market penetration of variable-
speed CRAC equipment is much smaller than for VRF multi-split systems.
Given that DOE is not aware of an established CVP for CRAC nor any test
data that could support adopting such a CVP, DOE is not adopting a CVP
for CRACs in this final rule.
F. Configuration of Unit Under Test
1. Background and Summary
CRACs are sold with a wide variety of components, including many
that can optionally be installed on or within the unit both in the
factory and in the field. In all cases, these components are
distributed in commerce with the CRAC, but can be packaged or shipped
in different ways from the point of manufacture for ease of
transportation. Some optional components may affect a model's measured
efficiency when tested to the DOE test procedure adopted in this final
rule, and others may not. DOE is handling CRAC components in two
distinct ways in this final rule to help manufacturers better
understand their options for developing representations for their
differing product offerings.
First, the treatment of some components is specified by the test
procedure to limit their impact on measured efficiency. For example, a
fire/smoke/isolation damper must be set in the closed position and
sealed during testing, resulting in a measured efficiency that would be
similar or identical to the measured efficiency for a unit without a
fire/smoke/isolation damper.
Second, for certain components not directly addressed in the DOE
test procedure, this final rule provides more specific instructions on
how each component should be handled for the purposes of making
representations in 10 CFR part 429. Specifically, these instructions
provide clarity to manufacturers on how components should be treated
and how to group individual models with and without optional components
for the purposes of representations, in order to reduce burden. DOE is
adopting these provisions in 10 CFR part 429 to allow for testing of
certain individual models that can be used as a proxy to represent the
performance of equipment with multiple combinations of components. DOE
is adopting provisions expressly allowing certain models to be grouped
together for the purposes of making representations and allowing the
performance of a model without certain optional components to be used
as a proxy for models with any combinations of the specified
components, even if such components would impact the measured
efficiency of a model. Steam/hydronic heat coils are an example of such
a component. The efficiency representation for a model with a steam/
hydronic heat coil is based on the measured performance of the CRAC as
tested without the component installed because the steam/hydronic heat
coil is not easily removed from the CRAC for testing.\17\
---------------------------------------------------------------------------
\17\ Note that in certain cases, as explained further in section
III.F.2.c of this document, the representation may have to be based
on an individual model with a steam/hydronic coil.
---------------------------------------------------------------------------
2. Approach for Exclusion of Certain Components
a. Proposals
Appendix D of AHRI 1360-2022 (and Appendix D of AHRI 1360-202X
Draft) provides discussion of components which would not be considered
in representations, and provides instructions either to neutralize
their impact during testing or for determining representations for
individual models with such components based on other individual models
that do not include them.
Instead of referencing Appendix D of AHRI 1360-202X Draft, DOE
tentatively determined in the February 2022 NOPR that it would be
necessary to include related provisions in the proposed appendix E1
test procedure and in the proposed representation requirements at 10
CFR 429.43. 87 FR 6948, 6964 (Feb. 7. 2022). DOE noted that this
revised approach would provide more detailed direction and clarity
between test procedure provisions (i.e., how to test a specific unit)
and certification and enforcement provisions (e.g., which model(s) to
test). Id. Specifically, DOE proposed to include provisions for certain
specific components to limit their impact on measured efficiency during
testing. 87 FR 6948, 6981 (Feb. 7, 2022). Additionally, DOE proposed
representation requirements in 10 CFR 429.43(a)(4) that explicitly
allowed representations for individual models with certain components
to be based on testing for individual models without those components.
The proposal included a table listing the components for which these
provisions would apply: air economizers, process heat recovery/reclaim
coils/thermal storage, evaporative pre-cooling of air-cooled condenser
intake air, steam/hydronic heat coils, refrigerant reheat coils,
powered exhaust/powered return air fans, compressor variable frequency
drive (``VFD''), fire/smoke/isolation dampers, non-standard indoor fan
motors, humidifiers, flooded condenser head pressure controls, chilled
water dual cooling coils, and condensate pump. 87 FR 6948, 6974-6975
(Feb. 7. 2022). Finally, DOE proposed specific product enforcement
provisions in 10 CFR 429.134 indicating that DOE would conduct
enforcement testing on individual models that do not include the
components listed in the aforementioned table, except in certain
enumerated circumstances. 87 FR 6948, 6977 (Feb. 7. 2022).
b. General Comments
AHRI generally supported DOE's proposals and agreed with the
approach to include the optional features provisions in the test
procedure directly and remove them from DOE's
[[Page 21827]]
Commercial HVAC Enforcement Policy.\18\ (AHRI, No. 9 at p. 6)
---------------------------------------------------------------------------
\18\ On January 30, 2015, DOE issued a Commercial HVAC
Enforcement Policy addressing the treatment of specific features
during DOE testing of commercial HVAC equipment. (See
www.energy.gov/gc/downloads/commercial-equipment-testing-enforcement-policies.)
---------------------------------------------------------------------------
In this final rule, DOE is adopting its proposals in the February
2022 NOPR regarding the exclusion of certain components, with some
additional simplifications to further improve clarity. The different
aspects of the provisions are described in the following sections.
c. Test Provisions Within Appendix E1
DOE is adopting test provisions in section 4 of appendix E1 to
prescribe how certain components must be configured for testing, as
proposed in the February 2022 NOPR. Specifically, DOE is requiring in
appendix E1 that steps be taken during unit set-up and testing to limit
the impacts on the measurement of these components:
Air economizers
Process heat recovery/reclaim coils/thermal storage
Evaporative pre-cooling of condenser intake air
Steam/hydronic heat coils
Refrigerant reheat coils
Fire/smoke/isolation dampers
Harmonic distortion mitigation devices
Humidifiers
Electric reheat elements
Non-standard power transformer
Chilled water dual cooling coils
High-effectiveness indoor air filtration
The components are listed and described along with their
corresponding test provisions in Table 4.1 in section 4 of the new
appendix E1.
In response to the February 2022 NOPR, AHRI suggested the inclusion
of provisions for four specific components (i.e., harmonic distortion
mitigation devices, humidifiers, non-standard power transformers, and
chilled water coils) to limit their impact on measured efficiency
during testing. (AHRI, No. 9 at pp. 6-7) For harmonic distortion
mitigation devices and non-standard power transformers, AHRI commented
that these components cannot be removed for testing and that AHRI will
consider including relevant provisions in the finalized version of AHRI
1360-202X Draft. For humidifiers and chilled water coils, AHRI
commented that these should be de-energized and removed from testing,
respectively. Id.
For humidifiers and chilled water coils, appendix E1 (as proposed
in the February 2022 NOPR) includes provisions consistent with AHRI's
suggestions. For harmonic distortion mitigation devices and non-
standard power transformers, AHRI 1360-2022 does not provide any
further guidance on these components as AHRI's comment indicated. In
the absence of any suggested alternative provisions, DOE has concluded
that the provisions that were proposed for testing with these
components in appendix E1 in the February 2022 NOPR are appropriate for
the CRAC test procedure. Therefore, DOE is adopting the appendix E1
provisions for these components as proposed.
d. Representation Provisions Within 10 CFR 429.43
As discussed, in the February 2022 NOPR, DOE proposed
representation requirements in 10 CFR 429.43(a)(4) that explicitly
allowed representations for individual models with certain components
to be based on testing for individual models without those components.
The proposal included a table \19\ listing the components for which
these provisions would apply (i.e., air economizers, process heat
recovery/reclaim coils/thermal storage, evaporative pre-cooling of air-
cooled condenser intake air, steam/hydronic heat coils, refrigerant
reheat coils, powered exhaust/powered return air fans, compressor VFD,
fire/smoke/isolation dampers, non-standard indoor fan motors,
humidifiers, flooded condenser head pressure controls, chilled water
dual cooling coils, and condensate pump). 87 FR 6948, 6974-6975 (Feb.
7, 2022).
---------------------------------------------------------------------------
\19\ In the February 2022 NOPR, this table was referred to as
``Table 1''; however, due to the publication of other test procedure
actions subsequent to the February 2022 NOPR, this final rule refers
to this table as ``Table 5 to paragraph (a)(3)(iv)(A)--Specific
Components for Computer Room Air Conditioners'' of 10 CFR 429.43.
---------------------------------------------------------------------------
In this final rule, DOE is making two clarifications to the
representation requirements as proposed in the February 2022 NOPR.
First, DOE is specifying that the basic model representation must
be based on the least-efficient individual model that is a part of the
basic model, and clarifying how this long-standing basic model
provision interacts with the component treatment in 10 CFR 429.43 that
this final rule adopts. Adoption of this clarification in the
regulatory text is consistent with the February 2022 NOPR, in which DOE
noted that in some cases, individual models may include more than one
of the specified components or there may be individual models within a
basic model that include various versions of the specified components
that result in more or less energy use. 87 FR 6948, 6965 (Feb. 7,
2022). In such cases, DOE stated that the represented values of
performance must be representative of the individual model with the
lowest efficiency found within the basic model. Id.
DOE has determined that regulated entities may benefit from clarity
in the regulatory text as to how the least-efficient individual model
within a basic model provision is applied with the additional
component-specific instructions for CRACs. The amendments in this final
rule explicitly state that the exclusion of the specified components
from consideration in determining basic model efficiency in certain
scenarios is an exception to basing representations on the least-
efficient individual model within a basic model. In other words, the
components listed in 10 CFR 429.43 are not being considered as part of
the representation under DOE's regulatory framework if certain
conditions are met as discussed in the following paragraphs, and, thus,
their impact on efficiency is not reflected in the representation. In
this case, the basic model's representation is generally determined by
applying the testing and sampling provisions to the least-efficient
individual model in the basic model that does not have a component
listed in 10 CFR 429.43.
Second, DOE is also clarifying instructions for determining the
unit used for basic model representation to resolve instances where
individual models within a basic model may have more than one of the
specified components and there may be no individual model without any
of the specified components. DOE is adopting the concept of an
``otherwise comparable model group'' (``OCMG'') instead of using the
``otherwise identical'' provisions proposed in the February 2022 NOPR.
87 FR 6948, 6964-6965 (Feb. 7, 2022). DOE is using the term
``comparable'' as opposed to ``identical'' to indicate that components
that impact energy consumption as measured by the applicable test
procedure are the relevant components to consider for the purpose of
representations. Differences that do not impact energy consumption,
such as unit color and presence of utility outlets, would, therefore,
not warrant separate OCMGs. DOE developed and placed in the docket a
document of examples to illustrate the approach in this final rule for
determining represented values for CRACs with specific components, and
in particular the OCMG concept. See EERE-2021-BT-TP-0017-0010.
[[Page 21828]]
An OCMG is a group of individual models within the basic model that
do not differ in components that affect energy consumption as measured
according to the applicable test procedure other than the specific
components listed in Table 5 of 10 CFR 429.43(a)(3)(iv)(A) (``Table 5
of Sec. 429.43''). An OCMG may include individual models with any
combination of such specified components, including no specified
components, and an OCMG can be comprised of one individual model.
Because every model within each OCMG is within the definition of the
basic model, a basic model can be composed of multiple OCMGs. Each OCMG
represents a unique combination of components that affect energy
consumption, as measured according to the applicable test procedure,
other than the specified components listed in Table 5 of Sec. 429.43;
this means that a new combination of such components represents a new
OCMG. For example, a manufacturer might include two tiers of control
system within the same basic model, in which one of the control systems
has sophisticated diagnostics capabilities that require a more powerful
control board with a higher wattage input. CRAC individual models with
the ``standard'' control system would be part of OCMG A, while
individual models with the ``premium'' control system would be part of
a different OCMG B, since the control system is a component that
affects energy consumption and is not one of the specified exempt
components listed in Table 5 of Sec. 429.43. However, OCMG A and OCMG
B both may include individual models with different combinations of
steam/hydronic coils, harmonic distortion mitigation devices, and
humidifiers, for example. Both OCMGs may also include any combination
of characteristics that do not affect the efficiency measurement, such
as paint color.
The OCMG is used to identify which individual models are used to
determine a represented value for the basic model. Specifically, only
the individual model(s) with the least number (which could be zero) of
the specific components listed in Table 5 of Sec. 429.43 is considered
when identifying the individual model. This clarifies which individual
models are exempted from consideration for determination of represented
values in the case of an OCMG with multiple specified components and no
individual models with zero specific components listed in Table 5 of
Sec. 429.43. Models with a number of specific components listed in
Table 5 greater than the model(s) with the least number in the OCMG are
exempted from consideration. In the case that the OCMG includes an
individual model with no specific components listed in Table 5 of Sec.
429.43, then all individual models in the OCMG with any specified
components would be excluded from consideration. Among the remaining
non-excluded models, the least efficient individual model across the
OCMGs would be used to determine the representation of the basic model.
In the case where there are multiple individual models within a single
OCMG with the same non-zero least number of specified components, the
least efficient of these would be considered.
The use of the OCMG concept results in representations being based
on the same individual models as the approach proposed in the February
2022 NOPR, i.e., the represented values of performance are
representative of the individual model(s) with the lowest efficiency
found within the basic model, excluding certain individual models with
the specific components listed in Table 5 of Sec. 429.43. However, the
approach as adopted in this final rule is structured to more explicitly
address individual models with more than one of the specific components
listed in Table 5 of Sec. 429.43, as well as instances in which there
is no comparable model without any of the specified components.
Finally, DOE notes that use of the OCMG concept for CRACs is
consistent with the approach finalized by DOE in test procedure final
rules for direct expansion-dedicated outdoor air systems (see 87 FR
45164 (July 27, 2022)) \20\ and single package vertical units (see 87
FR 75144 (Dec. 7, 2022),\21\ and proposed in a test procedure NOPR for
water-source heat pumps (see 87 FR 53302 (August 30, 2022)).\22\
---------------------------------------------------------------------------
\20\ See also ``Direct Expansion Dedicated Outdoor Air Systems
(DX-DOAS) Illustration of Specified Components Requirements
Presentation'' (available at: www.regulations.gov/document/EERE-2017-BT-TP-0018-0038).
\21\ See also ``Single Package Vertical Units (SPVU)
Illustration of Specified Components Requirements, November 2022''
(available at: www.regulations.gov/document/EERE-2017-BT-TP-0020-0025).
\22\ See also ``Water Source Heat Pumps (WSHP) Illustration of
Specified Components Requirements, Test Procedure NOPR--August
2022'' (available at: www.regulations.gov/document/EERE-2017-BT-TP-0029-0013).
---------------------------------------------------------------------------
In response to the February 2022 NOPR, AHRI suggested that DOE
should include in appendix E six additional components (coated coils,
sound traps/sound attenuators, indoor or outdoor fans with VFD,
compressor VFD, evaporative pre-cooling of condenser intake air, and
hot gas bypass) at 10 CFR 429.134; AHRI commented that these components
were included in the Commercial HVAC Enforcement Policy. (AHRI, No. 9
at pp. 6-7)
In response, DOE notes that none of these six components are
specified for CRACs in the Commercial HVAC Enforcement Policy. However,
AHRI 1360-202X Draft (and the subsequently finalized AHRI 1360-2022)
includes three of the components--compressor VFD, evaporative pre-
cooling of condenser intake air, and coated coils--as optional features
for CRACS. In the February 2022 NOPR, DOE tentatively concluded that it
was appropriate to consider inclusion of compressor VFD and evaporative
pre-cooling of condenser intake air as optional features, and the
Department proposed provisions for these features at 10 CFR 429.43. 87
FR 6948, 6975 (Feb. 7, 2022). Correspondingly, in this final rule DOE
is including these two components as specific components listed in
Table 5 of Sec. 429.43.
Regarding sound traps/sound attenuator, indoor or outdoor fans with
VFD, and hot gas bypass, DOE notes that these components are not
included in AHRI 1360-202X Draft (and the subsequently finalized
industry consensus test procedure AHRI 1360-2022). Further, DOE notes
that AHRI did not provide any rationale as to the need for including
these components as specific components in Table 5 of Sec. 429.43.
Additionally, these components are not included for CRACs in the
Commercial HVAC Enforcement Policy. Therefore, DOE has concluded that
it has no basis to include these components as specific components
listed in Table 5 of Sec. 429.43.
Regarding coated coils, in the February 2022 NOPR, DOE proposed to
exclude coated coils from the specific components list specified in 10
CFR 429.43 because DOE tentatively concluded that the presence of
coated coils does not result in a significant impact to performance of
CRACs, and, therefore, that models with coated coils should be rated
based on performance of models with coated coils. 87 FR 6948, 6965
(Feb. 7, 2022). As discussed, DOE received comments from AHRI in
response to the February 2022 NOPR that DOE should consider including
coated coils in the list of specific components for CRACs at 10 CFR
429.134. DOE also received similar comments pertaining to coated coils
in response to other commercial HVAC equipment test procedure NOPRs,
specifically the test procedure supplemental notice of proposed
[[Page 21829]]
rulemaking (``SNOPR'') published for direct expansion-dedicated outdoor
air systems (``DX-DOASes'').\23\ (Docket No. EERE-2017-BT-TP-0018,
AHRI, No. 34 at p. 4) In response to the DX-DOAS SNOPR, AHRI and
Madison Indoor Air Quality (``MIAQ'') asserted that some coated coils
impact performance, but that each coating is different. (Docket No.
EERE-2017-BT-TP-0018, AHRI, No. 34 at p. 4; MIAQ, No. 29 at p. 4)
---------------------------------------------------------------------------
\23\ See 86 FR 72874 (Dec. 23, 2021).
---------------------------------------------------------------------------
AHRI's and MIAQ's assertions that some coated coils do impact
energy use suggest that there are other implementations of coated coils
that do not impact energy consumption as measured by the adopted test
procedure (i.e., the implementation of coated coils does not
necessarily or inherently impact energy use). DOE has no data
indicating the range of impacts for those coatings that do affect
energy use, or how other characteristics of the coatings, such as
durability and cost, correlate with energy use impacts. Absent such
data, DOE is unable to determine the specific range of impacts on
energy use made by coated coils. Nevertheless, given that comments on
the DX-DOAS SNOPR suggest that certain implementations of coated coils
do not impact energy use, DOE has determined that for those units for
which coated coils do impact energy use, representations should include
those impacts, thereby providing full disclosure for commercial
customers. Consequently, DOE is not incorporating coated coils into
DOE's provisions specified in 10 CFR 429.43(a)(3) that allow for the
exclusion of specified components when determining represented values
for CRACs. This approach is consistent with the one DOE has established
in a final rule for the DX-DOAS test procedure. 87 FR 45164, 45186
(July 27, 2022).
e. Enforcement Provisions Within 10 CFR 429.134
In the February 2022 NOPR, DOE sought to address CRACs that include
components specified in 10 CFR 429.43(a)(4)(i) both in the requirements
for representations (i.e., 10 CFR 429.43) and in the equipment-specific
enforcement provisions for assessing compliance (i.e., 10 CFR 429.134).
87 FR 6948, 6975-6977 (Feb. 7, 2022). DOE received no comments on this
topic.
Instructions on which units to test for the purpose of
representations are addressed in 10 CFR 429.43. Consequently, DOE has
determined that including parallel enforcement provisions in 10 CFR
429.134 would be redundant and potentially cause confusion because DOE
would select for enforcement only those individual models that are the
basis for making basic model representations as specified in 10 CFR
429.43. Therefore, in this final rule, DOE is providing the
requirements for making representations of CRACs that include the
specified components in 10 CFR 429.43 and is not including parallel
direction in the enforcement provisions of 10 CFR 429.134 established
in this final rule. However, DOE is finalizing the provision that
allows enforcement testing of alternative individual models with
specific components, if DOE cannot obtain for test the individual
models without the components that are the basis of representation.
3. Non-Standard Indoor Fan Motors
The Commercial HVAC Enforcement Policy includes high-static indoor
blowers/oversized motors as an optional feature for CRACs, among other
equipment. The Commercial HVAC Enforcement Policy states that when
selecting a unit of a basic model for DOE[hyphen]initiated testing, if
the basic model includes a variety of high-static indoor blowers or
oversized motor options,\24\ DOE will test a unit that has a standard
indoor fan assembly (as described in the STI that is part of the
manufacturer's certification, including information about the standard
motor and associated drive that was used in determining the certified
rating). This policy only applies where: (a) the manufacturer
distributes in commerce a model within the basic model with the
standard indoor fan assembly (i.e., standard motor and drive), and (b)
all models in the basic model have a motor with the same or better
relative efficiency performance as the standard motor included in the
test unit, as described in a separate guidance document discussed
subsequently. If the manufacturer does not offer models with the
standard motor identified in the STI or offers models with high-static
motors that do not comply with the comparable efficiency guidance, DOE
will test any indoor fan assembly offered for sale by the manufacturer.
---------------------------------------------------------------------------
\24\ The Commercial HVAC Enforcement Policy defines ``high-
static indoor blower or oversized motor'' as an assembly that drives
the fan and can deliver higher external static pressure than the
standard indoor fan assembly sold with the equipment.
---------------------------------------------------------------------------
DOE subsequently issued a draft guidance document (``Draft
Commercial HVAC Guidance Document'') on June 29, 2015 to request
comment on a method for comparing the efficiencies of a standard motor
and a high-static indoor blower/oversized motor.\25\ As presented in
the Draft Commercial HVAC Guidance Document, the relative efficiency of
an indoor fan motor would be determined by comparing the percentage
losses of the standard indoor fan motor to the percentage losses of the
non-standard (oversized) indoor fan motor. The percentage losses would
be determined by comparing each motor's wattage losses to the wattage
losses of a corresponding reference motor. Additionally, the draft
method contains a table that includes a number of situations with
different combinations of characteristics of the standard motor and
oversized motor (e.g., whether each motor is subject to Federal
standards for motors, whether each motor can be tested to the Federal
test procedure for motors, whether each motor horsepower is less than
one) and specifies for each combination whether the non-standard fan
enforcement policy would apply (i.e., whether DOE would not test a
model with an oversized motor, as long as the relative efficiency of
the oversized motor is at least as good as performance of the standard
motor). DOE has not issued a final guidance document and is instead
addressing the issue for CRACs in this test procedure rulemaking.
---------------------------------------------------------------------------
\25\ Available at www1.eere.energy.gov/buildings/appliance_standards/pdfs/draft-commercial-hvac-motor-faq-2015-06-29.pdf.
---------------------------------------------------------------------------
In the February 2022 NOPR, DOE noted that the approaches in section
D3 of AHRI 1360-202X Draft for non-standard indoor fan motors and
integrated fan and motor combinations (``IFMs'') generally align with
the approaches of the Commercial HVAC Enforcement Policy and the Draft
Commercial HVAC Guidance Document, while providing greater detail and
accommodating a wider range of fan motor options. 87 FR 6948, 6966
(Feb. 7, 2022). DOE also tentatively determined that section D3 of
Appendix D of AHRI 1360-202X Draft would more fully provide the
guidance intended by the Commercial HVAC Enforcement Policy with regard
to non-standard indoor fan motors. Id. DOE proposed to adopt the
provisions in section D3 of AHRI 1360-202X Draft for comparing the
performance of standard and non-standard indoor fan motors and IFMs in
the proposed appendix E1.\26\ Id.
[[Page 21830]]
Additionally, DOE proposed to adopt the provisions in section D3 of
Appendix D of AHRI 1360-202X Draft for the determination of the
represented efficiency value of CRACs at 10 CFR 429.43(a)(3)(v)(C) and
for DOE assessment and enforcement testing of CRACs at 10 CFR
429.134(s)(1). Id.
---------------------------------------------------------------------------
\26\ Per DOE's existing certification regulations, if a
manufacturer were to use the proposed approach to certify a basic
model, the manufacturer would be required to maintain documentation
of how the relative efficiencies of the standard and non-standard
fan motors or the input power of the standard and non-standard IFMs
were determined, as well as the supporting calculations. See 10 CFR
429.71.
---------------------------------------------------------------------------
In commenting on this issue, AHRI stated support for maintaining
enforcement policy guidance even if such guidance moves to the test
procedure provisions, and that for future adoption, AHRI would support
provisions included in section D3 of Appendix D of 1360-202X Draft.
(AHRI, No. 9 at p. 7)
In the February 2022 NOPR, the Department proposed provisions
(referencing section D3 of AHRI 1360-202X Draft) regarding non-standard
indoor fan motors in the proposed 10 CFR 429.43(a)(3), which addresses
representation requirements for CRACs, rather than in the DOE test
procedure (i.e., appendix E1). Section D2 of AHRI 1360-2022 includes
the same provisions as those present in AHRI 1360-202X Draft. DOE has
concluded that maintaining provisions in both enforcement guidance and
DOE regulations would be redundant, and that including provisions in
DOE regulations provides better clarity to stakeholders. For the
reasons discussed in the preceding paragraphs and the February 2022
NOPR, DOE is finalizing its proposals regarding non-standard indoor fan
motors as proposed in the February 2022 NOPR.
G. Represented Values
1. Multiple Refrigerants
In the February 2022 NOPR, DOE noted that some commercial package
air conditioning and heating equipment may be sold with more than one
refrigerant option, and that DOE has identified at least one CRAC
manufacturer that provides two refrigerant options under the same model
number. 87 FR 6948, 6967 (Feb. 7, 2022). DOE stated that the use of a
refrigerant (such as R-407C as compared to R-410A) that requires
different hardware (i.e., compressors, heat exchangers, or air moving
systems that are not the same or comparably performing) would represent
a different basic model, and according to current DOE regulations,
separate representations of energy efficiency are required for each
basic model under 10 CFR 429.43(a). Id. DOE also noted that some
refrigerants (such as R-422D and R-427A) would not require different
hardware, and a manufacturer may consider them to be the same basic
model. Id. In the February 2022 NOPR, DOE proposed and requested
comment specifying that a manufacturer must determine the represented
values for that basic model based on the refrigerant(s)--among all
refrigerants listed on the unit's nameplate--that result in the lowest
cooling efficiency. Id.
AHRI supported the concept of DOE's proposal regarding
representations for CRAC models approved for use with multiple
refrigerants. (AHRI, No. 9 at p. 7) The CA IOUs also supported DOE's
proposal to require only ratings for the worst-performance refrigerant
for a given basic model and noted that this approach is consistent with
DOE's policy for other HVAC equipment. (CA IOUs, No. 6 at p. 7)
However, the CA IOUs recommended that DOE allow manufacturers to report
test results of the same basic model with multiple refrigerants,
stating that this would highlight equipment with the same hardware that
can be operated with better-performing refrigerants. Id. The CA IOUs
commented that commercial refrigeration equipment uses more than one
refrigerant for rating, and that DOE allows representations using
multiple refrigerants for consumer central air conditioners and heat
pumps. Id.
As discussed in section III.F.2 of this final rule, DOE is
generally clarifying in 10 CFR 429.43(a)(3)(iv)(A) that representations
for a CRAC basic model must be based on the least-efficient individual
model(s) distributed in commerce within the basic model (with the
exception specified in 10 CFR 429.43(a)(3)(iv)(A) for certain
individual models with the components listed in Table 5 to 10 CFR
429.43(a)(3); this list does not include different refrigerants).
Therefore, upon further consideration, DOE has determined that the
content of the proposal in the February 2022 NOPR regarding multiple
refrigerants (which would have required representations based on the
least-efficient refrigerant) is already included and clarified in the
provision adopted at 10 CFR 429.43(a)(3)(iv)(A) (which require
representations based on the least-efficient individual model (and thus
also the least-efficient refrigerant), with the exception mentioned
earlier in this paragraph), and that the refrigerant-specific
provisions proposed in the February 2022 NOPR at 10 CFR 429.43(a)(3)
would be redundant. As such, in this final rule, DOE is not adopting
the refrigerant-specific language proposed in the February 2022 NOPR.
Regarding the CA IOU's comment requesting provision allowing
additional representations within a basic model for different
refrigerants, DOE has concluded that because the efficiency of the CRAC
could be impacted by different refrigerant choices, the least-efficient
individual model requirement necessitates consideration of the least-
efficient refrigerant when determining represented values for that
basic model. Therefore, DOE is not adopting the CA IOUs' suggestion to
allow representations for multiple refrigerants within a single basic
model, because it would be inconsistent with the Department's adopted
requirement that the represented values for a basic model be based on
the least-efficient individual model.
2. Net Sensible Cooling Capacity
For CRACs, net sensible cooling capacity (``NSCC'') determines
equipment class, which in turn determines the applicable energy
conservation standard. 10 CFR 431.97. In the February 2022 NOPR, DOE
noted that while NSCC is a required represented value for CRACs, DOE
does not currently specify provisions for CRACs regarding how close the
represented value of NSCC must be to the tested or alternative energy-
efficiency determination method (``AEDM'') simulated NSCC, or whether
DOE will use measured or certified NSCC to determine equipment class
for enforcement testing. 87 FR 6948, 6967 (Feb. 7, 2022). DOE proposed
to add to its regulations the following provisions regarding NSCC for
CRACs: (1) a requirement that the represented NSCC be between 95
percent and 100 percent of the tested or AEDM-simulated cooling
capacity; and (2) an enforcement provision stating that DOE would use
the mean of measured NSCC values from testing, rather than the
certified cooling capacity, to determine the applicable standards. Id.
AHRI expressed support for DOE's proposal that the represented NSCC
be between 95 percent and 100 percent of the tested or AEDM-simulated
cooling capacity. (AHRI, No. 9 at p. 8) However, AHRI opposed DOE's
proposed enforcement provision of using the mean of measured NSCC
values from testing to determine the applicable standards, rather than
the certified NSCC, stating that this is a deviation from the current
requirement that DOE conduct statistical averaging of three units to
confirm published capacity, and that this proposal was presented
without supporting evidence necessary to make the change. Id. AHRI
recommended that DOE apply enforcement provisions similar to those for
packaged terminal air conditioners
[[Page 21831]]
(``PTACs''), which specify in paragraph (e) of 10 CFR 429.134 that if
the certified cooling capacity is found to be ``valid'' based on the 5-
percent allowance to the tested mean, the reported certified value of
cooling capacity is used in the next steps of decision making rather
than just the mean itself. Id. AHRI noted that this 5-percent allowance
is also currently provided for portable air conditioners, water
heaters, and dehumidifiers. AHRI stated that using just the mean of the
measurement(s) to determine the applicable standard with which the
model must comply is too restrictive and does not follow precedence set
by similar products. Id.
In response, DOE acknowledges that the enforcement provisions for
PTACs specified at 10 CFR 429.134(e) are different than those specified
for CUACs at 10 CFR 429.134(g) (which are consistent with the
provisions proposed for CRACs). However, the efficiency standards for
PTACs are linearly variable with capacity (i.e., a change in PTAC
capacity changes the minimum efficiency required). This relationship
between capacity and the applicable standard justifies DOE's approach
for PTACs to use the reported certified value of cooling capacity if
the certified cooling capacity is found to be within tolerance. In
contrast, the energy conservation standards for CRACs are based on
equipment classes that are differentiated based on fixed-capacity
thresholds (i.e., no linear relationship between capacity and the
applicable standard). As noted, the proposed provisions for CRACs are
consistent with the current enforcement provisions for CUACs at 10 CFR
429.134(g), which have similar capacity thresholds for equipment
classes and also have fixed efficiency standards within each class. To
maintain consistency with the approach used for other similarly
situated commercial air conditioning and heating equipment with
equipment classes based on fixed-capacity thresholds, DOE is adopting
the enforcement provisions specifying that DOE would use the mean of
measured cooling capacity values from testing to determine the
applicable standards.
3. Validation Class for Glycol-Cooled CRACs
DOE's existing testing regulations allow the use of an AEDM, in
lieu of actual testing, to simulate the efficiency of CRACs. 10 CFR
429.43(a). In the AEDM requirements for CRACs in 10 CFR 429.70, the
table itemizing validation classes for commercial HVAC equipment
inadvertently omits glycol-cooled CRACs, which DOE understands to be
similar in design to water-cooled CRACs. To address this, in the
February 2022 NOPR, DOE proposed to include glycol-cooled CRACs in the
existing validation class for water-cooled CRACs at 10 CFR
429.70(c)(2)(iv). 87 FR 6948, 6968 (Feb. 7, 2022). Specifically, DOE
proposed at 10 CFR 429.70(c)(2)(iv) that the minimum number of distinct
water-cooled and/or glycol-cooled models that must be tested per AEDM
would be two basic models, which aligns with the ``two basic model''
requirement that currently applies to the water-cooled CRACs validation
class. Id.
DOE did not receive any comments regarding this proposal, and for
the reasons discussed in the preceding paragraph and the February 2022
NOPR, DOE is adopting this change as proposed.
H. Effective and Compliance Dates
As noted in the DATES section of this document, the effective date
for the adopted test procedure amendments for CRACs is 30 days after
publication of this final rule in the Federal Register. Regarding the
compliance date, EPCA prescribes that, if DOE amends a test procedure,
all representations of energy efficiency and energy use, including
those made in the context of certification and on marketing materials
and product labels, must be made in accordance with an amended test
procedure, beginning 360 days after publication of the final rule in
the Federal Register. (42 U.S.C. 6314(d)(1)) However, CRACs are not
required to be tested according to the test procedure in appendix E1
(that relies on the NSenCOP metric) until the compliance date of
amended energy conservation standards denominated in terms of the
NSenCOP metric, should DOE adopt such standards.
I. Test Procedure Costs
EPCA requires that the test procedures for commercial package air
conditioning and heating equipment be generally accepted industry
testing procedures or rating procedures developed or recognized by
either AHRI or ASHRAE, as referenced in ASHRAE Standard 90.1. (42
U.S.C. 6314(a)(4)(A)) Further, if such an industry test procedure is
amended, DOE must amend its test procedure to be consistent with the
amended industry test procedure unless DOE determines, by rule
published in the Federal Register and supported by clear and convincing
evidence, that such an amended test procedure would not meet the
requirements in 42 U.S.C. 6314(a)(2)-(3) related to representative use
and test burden. (42 U.S.C. 6314(a)(4)(B)) In this final rule, DOE is
amending the existing test procedure for CRACs, by adopting the
industry test standard AHRI 1360-2022, including the energy efficiency
metric, NSenCOP. DOE is also amending its representation and
enforcement provisions for CRACs.
In the February 2022 NOPR, DOE walked through the anticipated
compliance costs associated with the proposed test procedure and
tentatively determined that the test procedure proposals presented in
the NOPR would not increase testing burden for most CRAC manufacturers
(i.e., CRAC manufacturers who are AHRI members), compared to current
industry practice as indicated by AHRI 1360-202X Draft, and that those
proposed amendments would not have a significant impact on the
remaining CRAC manufacturers (i.e., CRAC manufacturers who are not AHRI
members). 87 FR 6948, 6968-6970 (Feb. 7, 2022).
AHRI commented that manufacturers, particularly of up-flow CRACs,
will experience significant impact if DOE adopts AHRI 1360-202X Draft,
rather than AHRI 1360-2017, noting that AHRI 1360-202X Draft includes a
revised right-angle static pressure deduction based on a study
conducted on forward curve fans, which changes the static pressure
deduction from a fixed 0.3 inches water gauge to one based on velocity.
(AHRI, No. 9 at pp. 8-9)
In response, DOE first notes that as previously mentioned, AHRI
1360-202X Draft has been finalized as AHRI 1360-2022. The amended test
procedure adopted in this final rule does not impose any additional
test ducting provisions beyond those included in the amended industry
consensus test procedure, AHRI 1360-2022. Additionally, DOE notes that
the test provision for up-flow CRACs highlighted by AHRI is an
alternate ducting methodology to be used when there is limited chamber
height to meet the ducting requirements of ANSI/ASHRAE Standard 37,
which are referenced in both ANSI/ASHRAE 127-2007 and AHRI 1360-2022.
For most up-flow CRAC units (i.e., all CRACs except for tall units with
large discharge duct dimensions), manufacturers can still choose to
test their units in taller test chambers using the ducting requirements
of ANSI/ASHRAE Standard 37, which comply with both the current CRAC
test procedure and the amended test procedure adopted in this final
rule. Further, DOE notes that the AEDM provision in 10 CFR 429.70 allow
the use of AEDMs to develop ratings for CRACs, and, thus, manufacturers
would not be required to test their very tall up-flow CRACs.
[[Page 21832]]
DOE has determined that the amendments in this final rule will
improve the representativeness, accuracy, and reproducibility of the
test results and will not be unduly burdensome for manufacturers to
conduct or result in increased testing cost as compared to the current
test procedure. Because the current DOE test procedure for CRACs is
being relocated to appendix E without change, the test procedure in
appendix E for measuring SCOP will result in no change in testing
practices. Should DOE adopt the proposed standards in the ongoing
energy conservation standards rulemaking (see 87 FR 12802 (March 7,
2022)) denominated in terms of the new metric (i.e., NSenCOP), the
amended test procedure in appendix E1 for measuring NSenCOP (as per
AHRI 1360-2022) would be required for use upon the compliance date of
such standards.
DOE has concluded that the test procedure at appendix E will not
increase third-party lab testing costs per unit relative to the current
DOE test procedure, which DOE estimates to be $10,200 (for CRACs that
are physically tested \27\). However, DOE has concluded that the
potential adoption of standards denominated in terms of NSenCOP (and
the corresponding requirement to use the amended test procedure in
appendix E1) would alter the measured energy efficiency for CRACs.
Consequently, manufacturers would likely not be able to rely on data
generated under the current test procedure and would, therefore, be
required to re-rate CRAC models. In accordance with 10 CFR 429.70, CRAC
manufacturers may elect to use AEDMs to rate models, which
significantly reduces costs to industry. DOE estimates the per-
manufacturer cost to develop and validate an AEDM for CRACs to be
$46,000. DOE estimates a cost of approximately $50 per basic model \28\
for determining energy efficiency using the validated AEDM.
---------------------------------------------------------------------------
\27\ Manufacturers are not required to perform laboratory
testing on all basic models. In accordance with 10 CFR 429.70, CRAC
manufacturers may elect to use AEDMs. An AEDM is a computer modeling
or mathematical tool that predicts the performance of non-tested
basic models. These computer modeling and mathematical tools, when
properly developed, can provide a means to predict the energy usage
or efficiency characteristics of a basic model of a given covered
product or equipment and reduce the burden and cost associated with
testing.
\28\ DOE estimated initial costs to validate an AEDM assuming 80
hours of general time to develop an AEDM based on existing
simulation tools and 16 hours to validate two basic models within
that AEDM at the cost of an engineering technician wage of $50 per
hour plus the cost of third-party physical testing of two units per
validation class (as required in 10 CFR 429.70(c)(2)(iv)). DOE
estimated the additional per basic model cost to determine
efficiency using an AEDM, assuming 1 hour per basic model at the
cost of an engineering technician wage of $50 per hour.
---------------------------------------------------------------------------
Given that most CRAC manufacturers are AHRI members, and that DOE
is adopting the procedure in the prevailing industry test procedure
that was established for use in AHRI's certification program, which has
already been updated to include NSenCOP, DOE expects that most
manufacturers will already be testing using the published version of
the AHRI 1360-2022 in the timeframe of any potential future energy
conservation standard. Based on this, DOE has determined that the test
procedure amendments are not expected to increase the testing burden on
CRAC manufacturers that are AHRI members. For the minority of CRAC
manufacturers that are not members of AHRI, the test procedure
amendments may have costs associated with model re-rating, to the
extent that the manufacturers would not already be testing to the
updated industry test procedure.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866 and 13563
Executive Order (``E.O.'') 12866, ``Regulatory Planning and
Review,'' 58 FR 51735 (Oct. 4, 1993), as supplemented and reaffirmed by
E.O. 13563, ``Improving Regulation and Regulatory Review,'' 76 FR 3821
(Jan. 21, 2011), requires agencies, to the extent permitted by law, to:
(1) propose or adopt a regulation only upon a reasoned determination
that its benefits justify its costs (recognizing that some benefits and
costs are difficult to quantify); (2) tailor regulations to impose the
least burden on society, consistent with obtaining regulatory
objectives, taking into account, among other things, and to the extent
practicable, the costs of cumulative regulations; (3) select, in
choosing among alternative regulatory approaches, those approaches that
maximize net benefits (including potential economic, environmental,
public health and safety, and other advantages; distributive impacts;
and equity); (4) to the extent feasible, specify performance
objectives, rather than specifying the behavior or manner of compliance
that regulated entities must adopt; and (5) identify and assess
available alternatives to direct regulation, including providing
economic incentives to encourage the desired behavior, such as user
fees or marketable permits, or providing information upon which choices
can be made by the public. DOE emphasizes as well that E.O. 13563
requires agencies to use the best available techniques to quantify
anticipated present and future benefits and costs as accurately as
possible. In its guidance, the Office of Information and Regulatory
Affairs (``OIRA'') in the Office of Management and Budget (``OMB'') has
emphasized that such techniques may include identifying changing future
compliance costs that might result from technological innovation or
anticipated behavioral changes. For the reasons stated in the preamble,
this final regulatory action is consistent with these principles.
Section 6(a) of E.O. 12866 also requires agencies to submit
``significant regulatory actions'' to OIRA for review. OIRA has
determined that this final regulatory action does not constitute a
``significant regulatory action'' under section 3(f) of E.O. 12866.
Accordingly, this action was not submitted to OIRA for review under
E.O. 12866.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of a final regulatory flexibility analysis (FRFA) for any
final rule where the agency was first required by law to publish a
proposed rule for public comment, unless the agency certifies that the
rule, if promulgated, will not have a significant economic impact on a
substantial number of small entities. As required by Executive Order
13272, ``Proper Consideration of Small Entities in Agency Rulemaking,''
67 FR 53461 (August 16, 2002), DOE published procedures and policies on
February 19, 2003 to ensure that the potential impacts of its rules on
small entities are properly considered during the DOE rulemaking
process. 68 FR 7990. DOE has made its procedures and policies available
on the Office of the General Counsel's website: www.energy.gov/gc/office-general-counsel. DOE reviewed this final rule under the
provisions of the Regulatory Flexibility Act and the procedures and
policies published on February 19, 2003.
On February 7, 2022, DOE published in the Federal Register a notice
of proposed rulemaking (``February 2022 NOPR'') proposing to update the
references in the Federal test procedures to the most recent version of
the relevant industry test procedures as they relate to computer room
air conditioners (``CRACs'').
As part of the February 2022 NOPR, DOE conducted its initial
regulatory flexibility analysis (``IRFA''). 87 FR 6948, 6969-6970 (Feb.
7, 2022). DOE
[[Page 21833]]
used the Small Business Administration (``SBA'') small business size
standards to determine whether manufacturers qualify as small
businesses, which are listed by the North American Industry
Classification System (NAICS).\29\ The SBA considers a business entity
to be a small business, if, together with its affiliates, it employs
less than a threshold number of workers specified in 13 CFR part 121.
---------------------------------------------------------------------------
\29\ The size standards are listed by NAICS code and industry
description and are available at: www.sba.gov/document/support--table-size-standards (last accessed on August 30, 2021).
---------------------------------------------------------------------------
CRAC manufacturers are classified under NAICS code 333415, ``Air-
Conditioning and Warm Air Heating Equipment and Commercial and
Industrial Refrigeration Equipment Manufacturing.'' In 13 CFR 121.201,
the SBA sets a threshold of 1,250 employees or fewer for an entity to
be considered as a small business for this category. DOE utilized the
California Energy Commission's Modernized Appliance Efficiency Database
System (``MAEDbS'') \30\ and DOE's Compliance Certification Database
(``CCD'') \31\ in identifying potential small businesses that
manufacture CRACs covered by this rulemaking. DOE used subscription-
based business information tools (e.g., reports from Dun & Bradstreet
\32\) to determine headcount and revenue of those small businesses. DOE
identified nine companies that are original equipment manufacturers
(``OEMs'') of CRACs covered by this rulemaking. DOE screened out
companies that do not meet the definition of a ``small business'' or
are foreign-owned and operated. DOE identified three small, domestic
OEMs for consideration and noted that one small, domestic OEM was not
an AHRI member, while the other two small, domestic OEMs were AHRI
members. 87 FR 6948, 6969 (Feb. 7, 2022). DOE noted that small
businesses would be expected to have different potential regulatory
costs depending on whether they are a member of AHRI or not. Id. at 87
FR 6970. DOE requested comment on the number of small businesses DOE
identified and on the potential costs for the small business that is
not an AHRI member and manufactures CRACs. Id.
---------------------------------------------------------------------------
\30\ MAEDbS can be accessed at
www.cacertappliances.energy.ca.gov/Pages/Search/AdvancedSearch.aspx
(last accessed August 30, 2021).
\31\ Certified equipment in the CCD are listed by product class
and can be accessed at www.regulations.doe.gov/certification-data/#q=Product_Group_s%3A* (last accessed August 30, 2021).
\32\ Market research available at: app.dnbhoovers.com (last
accessed August 30, 2021).
---------------------------------------------------------------------------
On that topic, AHRI commented that it represented the following
single package vertical units (``SPVU'') companies that likely met the
criteria of small businesses that could be disproportionally impacted
by amended energy conservation standards: Bard Manufacturing Company,
Marvair, Systemair, Temspec, and United CoolAir. (AHRI, No. 9 at p. 9)
In response to AHRI's comment, DOE evaluated the four manufacturers
mentioned by AHRI and their product offerings. While these
manufacturers primarily manufacture SPVUs, which are not the subject of
this rulemaking, DOE's review found that two of these manufacturers
also offer products that meet the definition of wall-mounted CRAC
adopted in this final rule. One of the two manufacturers qualifies as a
small business under the applicable NAICS code (NAICS code 333415).
However, DOE notes that there are currently no energy conservation
standards for wall-mounted CRACs, and this is a test procedure
rulemaking with no proposed amendments to energy conservation
standards. Furthermore, DOE notes that no standards were proposed for
wall-mounted CRACs in the March 2022 ECS NOPR. Consequently, these two
manufacturers would not incur costs as a result of this final rule
unless they choose to make voluntary representations regarding the
NSenCOP of the subject equipment. Further, DOE is not adopting any test
requirements for wall-mounted CRACs that are not included in the
industry consensus test procedure AHRI 1360-2022. Additionally, AHRI's
comment suggests that these manufacturers are AHRI members. Therefore,
as discussed later in this section, it is DOE's conclusion that the
test procedure amendments would not add any additional testing burden
(beyond the updated industry consensus test procedure) to manufacturers
that are members of AHRI.
In this final rule, DOE is relocating the current DOE test
procedure to a new appendix E of subpart F of part 431 (``appendix E'')
without change. DOE is also establishing an amended test procedure at
appendix E1 to subpart F of part 431 (``appendix E1''), which
incorporates by reference the updated industry test standard AHRI 1360-
2022 for CRACs. Additionally, this final rule amends certain
representation and enforcement provisions for CRACs in 10 CFR part 429.
Appendix E does not contain any changes from the current Federal
test procedure, and, therefore, will not impose no cost on industry and
will not require retesting solely as a result of DOE's adoption of this
amendment to the test procedure.
The amended test procedure in appendix E1 includes amendments for
measuring CRAC energy efficiency using the NSenCOP metric so as to be
consistent with the updated industry test procedure. Should DOE adopt
amended energy conservation standards in the future that are
denominated in terms of NSenCOP (as proposed in the March 2022 ECS
NOPR), DOE expects there would not be an increase in third-party lab
testing costs per unit relative to the current Federal test procedure.
DOE estimates such testing costs to be $10,200 per unit for physical
testing. DOE has concluded that the amended test procedure may require
re-rating of CRAC models; however, this would not be mandatory until
such time as DOE amends the energy conservation standards for CRACs
based on NSenCOP, should DOE adopt such amendments.
If CRAC manufacturers conduct physical testing to certify a basic
model, two units are required to be tested per basic model. However,
manufacturers are not required to perform laboratory testing on all
basic models, as CRAC manufacturers may elect to use AEDMs.\33\ An AEDM
is a computer modeling or mathematical tool that predicts the
performance of non-tested basic models. These computer modeling and
mathematical tools, when properly developed, can provide a means to
predict the energy usage or efficiency characteristics of a basic model
of a given covered product or equipment and reduce the burden and cost
associated with testing.
---------------------------------------------------------------------------
\33\ In accordance with 10 CFR 429.70.
---------------------------------------------------------------------------
Small businesses would be expected to have different potential
regulatory costs depending on whether they are a member of AHRI. DOE
understands that all AHRI members and all manufacturers currently
certifying to the AHRI Directory will be testing their CRAC models in
accordance with AHRI 1360-2022, the industry test procedure DOE is
incorporating by reference, and using AHRI's certification program,
which has already been updated to include the NSenCOP metric.
The test procedure amendments would not add any additional testing
burden to manufacturers that are members of AHRI, as those members
currently are or soon will be using the AHRI 1360-2022 test procedure.
If DOE were to adopt energy conservation standards denominated in terms
of the NSenCOP metric, the amended test procedure may, however, result
in re-rating costs for manufacturers which are
[[Page 21834]]
not AHRI members (currently one identified OEM).
DOE estimated the range of additional potential testing costs for
the single small CRAC manufacturer that is not an AHRI member. This
small business would only incur additional testing costs if they would
not already be using AHRI 1360-2022 to test their CRAC models. DOE
estimates that this small business manufactures 113 basic models.
When developing cost estimates for this single, non-AHRI-member
small business, DOE considered the cost to develop an AEDM, the costs
to validate the AEDM through physical testing, and the cost per model
to determine ratings using the AEDM. DOE anticipates that this small
OEM would avail itself of the cost-saving option which the AEDM
provides. DOE estimated the cost to develop and validate an AEDM for
CRACs to be approximately $46,000, which includes physical testing of
two models per validation class. Additionally, DOE estimated a cost of
approximately $50 per basic model for determining energy efficiency
using the validated AEDM. The estimated cost to rate the 113 basic
models with the AEDM would be $5,650. Therefore, should DOE adopt
amended energy conservation standards denominated in terms of NSenCOP
as the efficiency metric (as proposed in the March 2022 ECS NOPR), this
small business could incur total testing and rating costs of $51,650.
DOE understands the annual revenue of this small business to be
approximately $17 million. Therefore, testing and AEDM costs could
cause this small business manufacturer to incur costs of up to 0.30
percent of its annual revenue.
Therefore, for the reasons stated in the preceding paragraphs, DOE
concludes and certifies that the cost effects accruing from this test
procedure final rule would not have a ``significant economic impact on
a substantial number of small entities,'' and that the preparation of a
FRFA is not warranted. DOE has submitted a certification and supporting
statement of factual basis to the Chief Counsel for Advocacy of the
Small Business Administration for review under 5 U.S.C. 605(b).
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of CRACs must certify to DOE that their products
comply with any applicable energy conservation standards. To certify
compliance, manufacturers must first obtain test data for their
products according to the DOE test procedures, including any amendments
adopted for those test procedures. DOE has established regulations for
the certification and recordkeeping requirements for all covered
consumer products and commercial equipment, including CRACs. (See
generally 10 CFR part 429.) The collection-of-information requirement
for the certification and recordkeeping is subject to review and
approval by OMB under the Paperwork Reduction Act (PRA). This
requirement has been approved by OMB under OMB control number 1910-
1400. Public reporting burden for the certification is estimated to
average 35 hours per response, including the time for reviewing
instructions, searching existing data sources, gathering and
maintaining the data needed, and completing and reviewing the
collection of information.
DOE is not amending the certification or reporting requirements for
CRACs in this final rule. Instead, DOE may consider proposals to amend
the certification requirements and reporting for CRACs under a separate
rulemaking regarding appliance and equipment certification. DOE will
address changes to OMB Control Number 1910-1400 at that time, as
necessary.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
DOE has analyzed this regulation in accordance with the National
Environmental Policy Act of 1969 (42 U.S.C. 4321 et seq.; ``NEPA'') and
DOE's NEPA implementing regulations (10 CFR part 1021). In this final
rule, DOE establishes test procedure amendments that it expects will be
used to develop and implement future energy conservation standards for
CRACs. DOE has determined that this rule falls into a class of actions
that are categorically excluded from review under NEPA and DOE's
implementing regulations, because it is a rulemaking that interprets or
amends an existing rule or regulation that does not change the
environmental effect of the rule or regulation being amended.
Specifically, DOE has determined that adopting test procedures for
measuring energy efficiency of consumer products and industrial
equipment is consistent with activities identified in 10 CFR part 1021,
subpart D, appendix A, sections A5 and A6. Accordingly, neither an
environmental assessment nor an environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 10,
1999), imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have federalism implications. The Executive order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE examined this final
rule and has determined that it will not have a substantial direct
effect on the States, on the relationship between the National
Government and the States, or on the distribution of power and
responsibilities among the various levels of government. EPCA governs
and prescribes Federal preemption of State regulations as to energy
conservation for the products that are the subject of this final rule.
States can petition DOE for exemption from such preemption to the
extent, and based on criteria, set forth in EPCA. (42 U.S.C. 6297(d))
No further action is required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that executive agencies make every reasonable
effort to ensure that the regulation: (1) clearly specifies the
preemptive effect, if any; (2) clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the
[[Page 21835]]
retroactive effect, if any; (5) adequately defines key terms; and (6)
addresses other important issues affecting clarity and general
draftsmanship under any guidelines issued by the Attorney General.
Section 3(c) of Executive Order 12988 requires executive agencies to
review regulations in light of applicable standards in sections 3(a)
and 3(b) to determine whether they are met or it is unreasonable to
meet one or more of them. DOE has completed the required review and
determined that, to the extent permitted by law, this final rule meets
the relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (``UMRA'')
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a regulatory action resulting in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820; also available
at www.energy.gov/gc/office-general-counsel. DOE examined this final
rule according to UMRA and its statement of policy and determined that
the rule contains neither an intergovernmental mandate, nor a mandate
that may result in the expenditure of $100 million or more in any year,
so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This final rule will not have any impact on the autonomy or integrity
of the family as an institution. Accordingly, DOE has concluded that it
is not necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights,'' 53 FR 8859 (March 18, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). Pursuant
to OMB Memorandum M-19-15, Improving Implementation of the Information
Quality Act (April 24, 2019), DOE published updated guidelines which
are available at www.energy.gov/sites/prod/files/2019/12/f70/DOE%20Final%20Updated%20IQA%20Guidelines%20Dec%202019.pdf. DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any significant energy action. A
``significant energy action'' is defined as any action by an agency
that promulgated or is expected to lead to promulgation of a final
rule, and that: (1) is a significant regulatory action under Executive
Order 12866, or any successor order; and (2) is likely to have a
significant adverse effect on the supply, distribution, or use of
energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use if the regulation is implemented, and of
reasonable alternatives to the action and their expected benefits on
energy supply, distribution, and use.
This regulatory action to amend the test procedure for measuring
the energy efficiency of CRACs is not a significant regulatory action
under Executive Order 12866. Moreover, it would not have a significant
adverse effect on the supply, distribution, or use of energy, nor has
it been designated as a significant energy action by the Administrator
of OIRA. Therefore, it is not a significant energy action, and,
accordingly, DOE has not prepared a Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788;
``FEAA'') Section 32 essentially provides in relevant part that, where
a proposed rule authorizes or requires use of commercial standards, the
notice of proposed rulemaking must inform the public of the use and
background of such standards. In addition, section 32(c) requires DOE
to consult with the Attorney General and the Chairman of the Federal
Trade Commission (``FTC'') concerning the impact of the commercial or
industry standards on competition.
The amendments to the Federal test procedure for CRACs contained in
this final rule adopt testing methods contained in certain sections of
the following commercial standards: AHRI 1360-2022, ANSI/ASHRAE 37-
2009, and ANSI/ASHRAE 127-2020. DOE has evaluated these standards and
is unable to conclude whether they fully comply with the requirements
of section 32(b) of the FEAA (i.e., whether they were developed in a
manner that fully provides for public participation, comment, and
review.) DOE has consulted with both the Attorney General and the
Chairman of the FTC about the impact on competition of using the
methods contained in these standards and has received no comments
objecting to their use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that it has been determined that the final rule is not a
[[Page 21836]]
``major rule'' as defined by 5 U.S.C. 804(2).
N. Description of Materials Incorporated by Reference
In this final rule, DOE incorporates by reference the following
test standards:
AHRI 1360-2022 is an industry-accepted test standard for measuring
the performance of CRACs. AHRI 1360-2022 is available from AHRI at
www.ahrinet.org/search-standards.aspx.
ANSI/ASHRAE 37-2009 is an industry-accepted test procedure that
provides a method of test for many categories of air conditioning and
heating equipment. ANSI/ASHRAE 37-2009 is available from ASHRAE and on
ANSI's website at webstore.ansi.org/RecordDetail.aspx?sku=ANSI%2FASHRAE+Standard+37-2009.
ANSI/ASHRAE 127-2007 is an industry-accepted test procedure for
measuring the performance of CRACs. ANSI/ASHRAE 127-2007 is available
from ASHRAE and on ANSI's website at https://webstore.ansi.org/standards/ashrae/ansiashrae1272007.
ANSI/ASHRAE 127-2020 is an industry-accepted test procedure for
measuring the performance of CRACs, which updates ANSI/ASHRAE 127-2007
to include new CRAC cooling configurations. ANSI/ASHRAE 127-2020 is
available from ASHRAE and on ANSI's website at webstore.ansi.org/standards/ashrae/ansiashrae1272020.
The following standards were previously approved for incorporation
by reference in the sections where they appear and no change is made:
AHRI 210/240-2008, AHRI 340/360-2007, and ISO Standard 13256-1.
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Reporting and
recordkeeping requirements, Small businesses.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation, Incorporation by reference, Reporting
and recordkeeping requirements.
Signing Authority
This document of the Department of Energy was signed on March 28,
2023, by Francisco Alejandro Moreno, Acting Assistant Secretary for
Energy Efficiency and Renewable Energy, pursuant to delegated authority
from the Secretary of Energy. That document with the original signature
and date is maintained by DOE. For administrative purposes only, and in
compliance with requirements of the Office of the Federal Register, the
undersigned DOE Federal Register Liaison Officer has been authorized to
sign and submit the document in electronic format for publication, as
an official document of the Department of Energy. This administrative
process in no way alters the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on March 28, 2023.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
For the reasons stated in the preamble, DOE is amending parts 429
and 431 of chapter II of title 10, Code of Federal Regulations as set
forth below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
2. Amend Sec. 429.4 by:
0
a. Removing the text ``https://'' wherever it appears;
0
b. Redesignating paragraph (c)(5) as paragraph (c)(6); and
0
c. Adding new paragraph (c)(5).
The addition reads as follows:
Sec. 429.4 Materials incorporated by reference.
* * * * *
(c) * * *
(5) AHRI Standard 1360-2022 (I-P) (``AHRI 1360-2022''), 2022
Standard for Performance Rating of Computer and Data Processing Room
Air Conditioners, copyright 2022; IBR approved for Sec. 429.43.
* * * * *
0
3. Amend Sec. 429.43 by adding paragraph (a)(3)(iv) to read as
follows.
Sec. 429.43 Commercial heating, ventilating, air conditioning (HVAC)
equipment (excluding air-cooled, three-phase, small commercial package
air conditioning and heating equipment with a cooling capacity of less
than 65,000 British thermal units per hour and air-cooled, three-phase,
variable refrigerant flow multi-split air conditioners and heat pumps
with less than 65,000 British thermal units per hour cooling capacity).
(a) * * *
(3) * * *
(iv) Computer room air conditioners. When certifying to standards
in terms of net sensible coefficient of performance (NSenCOP), the
following provisions apply.
(A) For individual model selection:
(1) Representations for a basic model must be based on the least-
efficient individual model(s) distributed in commerce among all
otherwise comparable model groups comprising the basic model, except as
provided in paragraph (a)(3)(iv)(A)(2) of this section for individual
models that include components listed in table 5 to paragraph
(a)(3)(iv)(A) of this section. For the purpose of this paragraph
(a)(3)(iv)(A)(1), otherwise comparable model group means a group of
individual models distributed in commerce within the basic model that
do not differ in components that affect energy consumption as measured
according to the applicable test procedure specified at 10 CFR 431.96
other than those listed in table 5 to paragraph (a)(3)(iv)(A) of this
section. An otherwise comparable model group may include individual
models distributed in commerce with any combination of the components
listed in table 5 (or none of the components listed in table 5). An
otherwise comparable model group may consist of only one individual
model.
(2) For a basic model that includes individual models distributed
in commerce, with components listed in table 5 to paragraph
(a)(3)(iv)(A) of this section, the requirements for determining
representations apply only to the individual model(s) of a specific
otherwise comparable model group distributed in commerce with the least
number (which could be zero) of components listed in table 5 to
paragraph (a)(3)(iv)(A) included in individual models of the group.
Testing under this paragraph (a)(3)(iv)(A)(2) shall be consistent with
any component-specific test provisions specified in section 4 of
appendix E1 to subpart F of 10 CFR part 431.
[[Page 21837]]
Table 5 to Paragraph (a)(3)(iv)(A)--Specific Components for Computer
Room Air Conditioners
------------------------------------------------------------------------
Component Description
------------------------------------------------------------------------
Air Economizers................... An automatic system that enables a
cooling system to supply and use
outdoor air to reduce or eliminate
the need for mechanical cooling
during mild or cold weather.
Process Heat Recovery/Reclaim A heat exchanger located inside the
Coils/Thermal Storage. unit that conditions the
equipment's supply air using energy
transferred from an external source
using a vapor, gas, or liquid.
Evaporative Pre-cooling of Air- Water is evaporated into the air
cooled Condenser Intake Air. entering the air-cooled condenser
to lower the dry-bulb temperature
and thereby increase efficiency of
the refrigeration cycle.
Steam/Hydronic Heat Coils......... Coils used to provide supplemental
heat.
Refrigerant Reheat Coils.......... A heat exchanger located downstream
of the indoor coil that heats the
supply air during cooling operation
using high pressure refrigerant in
order to increase the ratio of
moisture removal to cooling
capacity provided by the equipment.
Powered Exhaust/Powered Return Air A powered exhaust fan is a fan that
Fans. transfers directly to the outside a
portion of the building air that is
returning to the unit, rather than
allowing it to recirculate to the
indoor coil and back to the
building. A powered return air fan
is a fan that draws building air
into the equipment.
Compressor Variable Frequency A device connected electrically
Drive (VFD). between the equipment's power
supply connection and the
compressor that can vary the
frequency of power supplied to the
compressor in order to allow
variation of the compressor's
rotational speed. If the
manufacturer chooses to make
representations for performance at
part-load and/or low-ambient
conditions, compressor VFDs must be
treated consistently for all
cooling capacity tests for the
basic model (i.e., if the
compressor VFD is installed and
active for the part-load and/or low-
ambient tests, it must also be
installed and active for the
NSenCOP test).
Fire/Smoke/Isolation Dampers...... A damper assembly including means to
open and close the damper mounted
at the supply or return duct
opening of the equipment.
Non-Standard Indoor Fan Motors.... The standard indoor fan motor is the
motor specified in the
manufacturer's installation
instructions for testing and shall
be distributed in commerce as part
of a particular model. A non-
standard motor is an indoor fan
motor that is not the standard
indoor fan motor and that is
distributed in commerce as part of
an individual model within the same
basic model.
For a non-standard indoor fan
motor(s) to be considered a
specific component for a basic
model (and thus subject to the
provisions of paragraph
(a)(3)(iv)(A) of this section), the
following provisions must be met:
1. Non-standard indoor fan motor(s)
must meet the minimum allowable
efficiency determined per section
D.2.1 of AHRI 1360-2022
(incorporated by reference, see
Sec. 429.4) (i.e., for non-
standard indoor fan motors) or per
section D.2.2 of AHRI 1360-2022 for
non-standard indoor integrated fan
and motor combinations).
If the standard indoor fan motor can
vary fan speed through control
system adjustment of motor speed,
all non-standard indoor fan motors
must also allow speed control
(including with the use of VFD).
Humidifiers....................... A device placed in the supply air
stream for moisture evaporation and
distribution. The device may
require building steam or water,
hot water, electricity, or gas to
operate.
Flooded Condenser Head Pressure An assembly, including a receiver
Controls. and head pressure control valve,
used to allow for unit operation at
lower outdoor ambient temperatures
than the standard operating control
system.
Chilled Water Dual Cooling Coils.. A secondary chilled water coil added
in the indoor air stream for use as
the primary or secondary cooling
circuit in conjunction with a
separate chiller.
Condensate Pump................... A device used to pump condensate and/
or humidifier drain water from
inside the unit to a customer drain
outside the unit.
------------------------------------------------------------------------
(B) The represented value of net sensible cooling capacity must be
between 95 percent and 100 percent of the mean of the capacities
measured for the units in the sample selected as described in paragraph
(a)(1)(ii) of this section, or between 95 percent and 100 percent of
the net sensible cooling capacity output simulated by the AEDM as
described in paragraph (a)(2) of this section.
* * * * *
0
4. Amend Sec. 429.70 by revising the table in paragraph (c)(2)(iv) to
read as follows:
Sec. 429.70 Alternative methods for determining energy efficiency
and energy use.
* * * * *
(c) * * *
(2) * * *
(iv) * * *
Table 1 to Paragraph (c)(2)(iv)
------------------------------------------------------------------------
Minimum number of distinct
Validation class models that must be tested
per AEDM
------------------------------------------------------------------------
(A) Commercial HVAC Validation Classes
------------------------------------------------------------------------
Air-Cooled, Split and Packaged ACs and HPs 2 Basic Models.
Greater than or Equal to 65,000 Btu/h
Cooling Capacity and Less than 760,000 Btu/
h Cooling Capacity.
Water-Cooled, Split and Packaged ACs and 2 Basic Models.
HPs, All Cooling Capacities.
Evaporatively-Cooled, Split and Packaged 2 Basic Models.
ACs and HPs, All Capacities.
Water-Source HPs, All Capacities........... 2 Basic Models.
Single Package Vertical ACs and HPs........ 2 Basic Models.
Packaged Terminal ACs and HPs.............. 2 Basic Models.
[[Page 21838]]
Air-Cooled, Variable Refrigerant Flow ACs 2 Basic Models.
and HPs Greater than or Equal to 65,000
Btu/h Cooling Capacity.
Water-Cooled, Variable Refrigerant Flow ACs 2 Basic Models.
and HPs.
Computer Room Air Conditioners, Air Cooled. 2 Basic Models.
Computer Room Air Conditioners, Water- 2 Basic Models.
Cooled and Glycol-Cooled.
Direct Expansion-Dedicated Outdoor Air 2 Basic Models.
Systems, Air-cooled or Air-source Heat
Pump, Without Ventilation Energy Recovery
Systems.
Direct Expansion-Dedicated Outdoor Air 2 Basic Models.
Systems, Air-cooled or Air-source Heat
Pump, With Ventilation Energy Recovery
Systems.
Direct Expansion-Dedicated Outdoor Air 2 Basic Models.
Systems, Water-cooled, Water-source Heat
Pump, or Ground Source Closed-loop Heat
Pump, Without Ventilation Energy Recovery
Systems.
Direct Expansion-Dedicated Outdoor Air 2 Basic Models.
Systems, Water-cooled, Water-source Heat
Pump, or Ground Source Closed-loop Heat
Pump, With Ventilation Energy Recovery
Systems.
------------------------------------------------------------------------
(B) Commercial Water Heater Validation Classes
------------------------------------------------------------------------
Gas-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Less than 10 Gallons.
Gas-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Greater than or Equal to 10
Gallons.
Oil-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Less than 10 Gallons.
Oil-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Greater than or Equal to 10
Gallons.
Electric Water Heaters..................... 2 Basic Models.
Heat Pump Water Heaters.................... 2 Basic Models.
Unfired Hot Water Storage Tanks............ 2 Basic Models.
------------------------------------------------------------------------
(C) Commercial Packaged Boilers Validation Classes
------------------------------------------------------------------------
Gas-fired, Hot Water Only Commercial 2 Basic Models.
Packaged Boilers.
Gas-fired, Steam Only Commercial Packaged 2 Basic Models.
Boilers.
Gas-fired Hot Water/Steam Commercial 2 Basic Models.
Packaged Boilers.
Oil-fired, Hot Water Only Commercial 2 Basic Models.
Packaged Boilers.
Oil-fired, Steam Only Commercial Packaged 2 Basic Models.
Boilers.
Oil-fired Hot Water/Steam Commercial 2 Basic Models.
Packaged Boilers.
------------------------------------------------------------------------
(D) Commercial Furnace Validation Classes
------------------------------------------------------------------------
Gas-fired Furnaces......................... 2 Basic Models.
Oil-fired Furnaces......................... 2 Basic Models.
------------------------------------------------------------------------
(E) Commercial Refrigeration Equipment Validation Classes \1\
------------------------------------------------------------------------
Self-Contained Open Refrigerators.......... 2 Basic Models.
Self-Contained Open Freezers............... 2 Basic Models.
Remote Condensing Open Refrigerators....... 2 Basic Models.
Remote Condensing Open Freezers............ 2 Basic Models.
Self-Contained Closed Refrigerators........ 2 Basic Models.
Self-Contained Closed Freezers............. 2 Basic Models.
Remote Condensing Closed Refrigerators..... 2 Basic Models.
Remote Condensing Closed Freezers.......... 2 Basic Models.
------------------------------------------------------------------------
\1\ The minimum number of tests indicated above must be comprised of a
transparent model, a solid model, a vertical model, a semi-vertical
model, a horizontal model, and a service-over-the counter model, as
applicable based on the equipment offering. However, manufacturers do
not need to include all types of these models if it will increase the
minimum number of tests that need to be conducted.
* * * * *
0
5. Amend Sec. 429.134 by adding paragraph (aa) to read as follows:
Sec. 429.134 Product-specific enforcement provisions.
* * * * *
(aa) Computer room air conditioners. The following provisions apply
for assessment and enforcement testing of models subject to energy
conservation standards denominated in terms of NSenCOP.
(1) Verification of net sensible cooling capacity. The net sensible
cooling capacity of each tested unit of the basic model will be
measured pursuant to the test requirements of 10 CFR part 431, subpart
F, appendix E1. The mean of the net sensible cooling capacity
measurement(s) will be used to determine the applicable energy
conservation standards for purposes of compliance.
(2) Specific components. If a basic model includes individual
models with components listed at table 5 to Sec. 429.43(a)(3)(iv)(A)
and DOE is not able to obtain an individual model with the least number
(which could be zero) of those components within an otherwise
comparable model group (as defined in Sec. 429.43(a)(3)(iv)(A)(1)),
DOE may test any individual model within the otherwise comparable model
group.
PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
6. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
7. Section 431.92 is amended by:
0
a. Revising the introductory text;
[[Page 21839]]
0
b. Adding, in alphabetical order, definitions for ``Ceiling-mounted,''
``Ceiling-mounted ducted,'' and ``Ceiling-mounted non-ducted'';
0
c. Removing the definition for ``Computer Room Air Conditioner'' and
adding the definition ``Computer room air conditioner'' in its place;
and
0
d. Adding, in alphabetical order, definitions for ``Down-flow,''
``Floor-mounted,'' ``Fluid economizer,'' ``Horizontal-flow,'' ``Net
sensible coefficient of performance, or NSenCOP,'' ``Roof-mounted,''
``Up-flow,'' ``Up-flow ducted,'' ``Up-flow non-ducted,'' and ``Wall-
mounted.''
The revisions and additions read as follows:
Sec. 431.92 Definitions concerning commercial air conditioners and
heat pumps.
The following definitions apply for purposes of this subpart, and
of subparts J through M of this part. Any words or terms not defined in
this section or elsewhere in this part shall be defined as provided in
42 U.S.C. 6311. For definitions that reference the application for
which the equipment is marketed, DOE will consider any publicly
available document published by the manufacturer (e.g., product
literature, catalogs, and packaging labels) to determine marketing
intent. For definitions in this section that pertain to computer room
air conditioners, italicized terms within a definition indicate terms
that are separately defined in this section.
* * * * *
Ceiling-mounted means a configuration of a computer room air
conditioner for which the unit housing the evaporator coil is
configured for indoor installation on or through a ceiling.
Ceiling-mounted ducted means a configuration of a ceiling-mounted
computer room air conditioner that is configured for use with discharge
ducting (even if the unit is also configurable for use without
discharge ducting).
Ceiling-mounted non-ducted means a configuration of a ceiling-
mounted computer room air conditioner that is configured only for use
without discharge ducting.
* * * * *
Computer room air conditioner means commercial package air-
conditioning and heating equipment (packaged or split) that is marketed
for use in computer rooms, data processing rooms, or other information
technology cooling applications and not a covered consumer product
under 42 U.S.C. 6291(1)-(2) and 42 U.S.C. 6292. A computer room air
conditioner may be provided with, or have as available options, an
integrated humidifier, temperature and/or humidity control of the
supplied air, and reheating function. Computer room air conditioners
include, but are not limited to, the following configurations as
defined in this section: down-flow, horizontal-flow, up-flow ducted,
up-flow non-ducted, ceiling-mounted ducted, ceiling mounted non-ducted,
roof-mounted, and wall-mounted.
* * * * *
Down-flow means a configuration of floor-mounted computer room air
conditioner in which return air enters above the top of the evaporator
coil and discharge air leaves below the bottom of the evaporator coil.
* * * * *
Floor-mounted means a configuration of a computer room air
conditioner for which the unit housing the evaporator coil is
configured for indoor installation on a solid floor, raised floor, or
floor-stand. Floor-mounted computer room air conditioners are one of
the following three configurations: down-flow, horizontal-flow, and up-
flow.
Fluid economizer means an option available with a computer room air
conditioner in which a fluid (other than air), cooled externally from
the unit, provides cooling of the indoor air to reduce or eliminate
unit compressor operation when outdoor temperature is low. The fluid
may include, but is not limited to, chilled water, water/glycol
solution, or refrigerant. An external fluid cooler such as, but not
limited to a dry cooler, cooling tower, or condenser is utilized for
heat rejection. This component is sometimes referred to as a free
cooling coil, econ-o-coil, or economizer.
* * * * *
Horizontal-flow means a configuration of a floor-mounted computer
room air conditioner that is neither a down-flow nor an up-flow unit.
* * * * *
Net sensible coefficient of performance, or NSenCOP, means a ratio
of the net sensible cooling capacity in kilowatts to the total power
input in kilowatts for computer room air conditioners, as measured in
appendix E1 of this subpart.
* * * * *
Roof-mounted means a configuration of a computer room air
conditioner that is not wall-mounted, and for which the unit housing
the evaporator coil is configured for outdoor installation.
* * * * *
Up-flow means a configuration of a floor-mounted computer room air
conditioner in which return air enters below the bottom of the
evaporator coil and discharge air leaves above the top of the
evaporator coil.
Up-flow ducted means a configuration of an up-flow computer room
air conditioner that is configured for use with discharge ducting (even
if the unit is also configurable for use without discharge ducting).
Up-flow non-ducted means a configuration of an up-flow computer
room air conditioner that is configured only for use without discharge
ducting.
* * * * *
Wall-mounted means a configuration of a computer room air
conditioner for which the unit housing the evaporator coil is
configured for installation on or through a wall.
* * * * *
0
8. Amend Sec. 431.95 by:
0
a. Adding paragraph (b)(10);
0
b. In paragraph (c)(2), removing the text ``D1, F1'' and adding, in its
place, ``D1, E1, F1'';
0
c. In paragraph (c)(7), removing the text ``Sec. 431.96'' and adding,
in its place, ``Sec. 431.96 and appendix E to this subpart'';
0
d. Redesignating paragraph (c)(8) as paragraph (c)(9); and
0
e. Adding new paragraph (c)(8).
The additions and revisions read as follows:
Sec. 431.95 Materials incorporated by reference.
* * * * *
(b) * * *
(10) AHRI Standard 1360-2022 (I-P) (``AHRI 1360-2022''), 2022
Standard for Performance Rating of Computer and Data Processing Room
Air Conditioners, copyright 2022; IBR approved for appendix E1 to this
subpart.
(c) * * *
(8) ANSI/ASHRAE Standard 127-2020 (``ANSI/ASHRAE 127-2020''),
Method of Rating Air-Conditioning Units Serving Data Center (DC) and
Other Information Technology Equipment (ITE) Spaces, ANSI-approved on
November 30, 2020; IBR approved for appendix E1 to this subpart.
* * * * *
0
9. Amend Sec. 431.96 by revising table 1 to paragraph (b) to read as
follows:
Sec. 431.96 Uniform test method for the measurement of energy
efficiency of commercial air conditioners and heat pumps.
* * * * *
(b) * * *
[[Page 21840]]
Table 1 to Paragraph (b)--Test Procedures for Commercial Air Conditioners and Heat Pumps
--------------------------------------------------------------------------------------------------------------------------------------------------------
Additional test
Cooling capacity or Use tests, procedure provisions
Equipment type Category moisture removal Energy efficiency conditions, and as indicated in the
capacity \2\ descriptor procedures \1\ in listed paragraphs of
this section
--------------------------------------------------------------------------------------------------------------------------------------------------------
Small Commercial Package Air- Air-Cooled, 3-Phase, <65,000 Btu/h......... SEER and HSPF........ Appendix F to this None.
Conditioning and Heating Equipment. AC and HP. subpart \3\.
SEER2 and HSPF2...... Appendix F1 to this None.
subpart \3\.
Air-Cooled AC and HP.. >=65,000 Btu/h and EER, IEER, and COP... Appendix A of this None.
<135,000 Btu/h. subpart.
Water-Cooled and <65,000 Btu/h......... EER.................. AHRI 210/240-2008 Paragraphs (c) and
Evaporatively-Cooled (omit section 6.5). (e).
AC.
>=65,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
<135,000 Btu/h. (omit section 6.3). (e).
Water-Source HP....... <135,000 Btu/h........ EER and COP.......... ISO Standard 13256-1. Paragraph (e).
Large Commercial Package Air- Air-Cooled AC and HP.. >=135,000 Btu/h and EER, IEER, and COP... Appendix A to this None.
Conditioning and Heating Equipment. <240,000 Btu/h. subpart.
Water-Cooled and >=135,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
Evaporatively-Cooled <240,000 Btu/h. (omit section 6.3). (e).
AC.
Very Large Commercial Package Air- Air-Cooled AC and HP.. >=240,000 Btu/h and EER, IEER, and COP... Appendix A to this None.
Conditioning and Heating Equipment. <760,000 Btu/h. subpart.
Water-Cooled and >=240,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
Evaporatively-Cooled <760,000 Btu/h. (omit section 6.3). (e).
AC.
Packaged Terminal Air Conditioners AC and HP............. <760,000 Btu/h........ EER and COP.......... Paragraph (g) of this Paragraphs (c), (e),
and Heat Pumps. section. and (g).
Computer Room Air Conditioners..... AC.................... <760,000 Btu/h........ SCOP................. Appendix E to this None.
subpart \3\.
<760,000 Btu/h........ NSenCOP.............. Appendix E1 to this None.
subpart \3\.
Variable Refrigerant Flow Multi- AC.................... <65,000 Btu/h (3- SEER................. Appendix F to this None.
split Systems. phase). subpart \3\.
SEER2................ Appendix F1 to this None.
subpart \3\.
Variable Refrigerant Flow Multi- HP.................... <65,000 Btu/h (3- SEER and HSPF........ Appendix F to this None.
split Systems, Air-cooled. phase). subpart \3\.
SEER2 and HSPF2...... Appendix F1 to this None.
subpart \3\.
Variable Refrigerant Flow Multi- AC and HP............. >=65,000 Btu/h and EER and COP.......... Appendix D of this None.
split Systems, Air-cooled. <760,000 Btu/h. subpart \3\.
>=65,000 Btu/h and IEER and COP......... Appendix D1 of this None.
<760,000 Btu/h. subpart \3\.
Variable Refrigerant Flow Multi- HP.................... <760,000 Btu/h........ EER and COP.......... Appendix D of this None.
split Systems, Water-source. subpart \3\.
<760,000 Btu/h........ IEER and COP......... Appendix D1 of this None.
subpart \3\.
Single Package Vertical Air AC and HP............. <760,000 Btu/h........ EER and COP.......... Appendix G to this None.
Conditioners and Single Package subpart \3\.
Vertical Heat Pumps.
EER, IEER, and COP... Appendix G1 to this None.
subpart \3\.
Direct Expansion-Dedicated Outdoor All................... <324 lbs. of moisture ISMRE2 and ISCOP2.... Appendix B of this None.
Air Systems. removal/hr. subpart.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Incorporated by reference; see Sec. 431.95.
\2\ Moisture removal capacity applies only to direct expansion-dedicated outdoor air systems.
\3\ For equipment with multiple appendices listed in this table, consult the notes at the beginning of those appendices to determine the applicable
appendix to use for testing.
* * * * *
0
10. Add appendix E to subpart F of part 431 to read as follows:
Appendix E to Subpart F of Part 431--Uniform Test Method for Measuring
the Energy Consumption of Computer Room Air Conditioners
Note: Manufacturers must use the results of testing under this
appendix to determine compliance with the relevant energy
conservation standards for computer room air conditioners from Sec.
431.97 as that standard appeared in the January 1, 2022 edition of
10 CFR parts 200 through 499. Specifically, representations,
including compliance certifications, must be based upon results
generated either under this appendix or under 10 CFR 431.96 as it
appeared in the 10 CFR parts 200 through 499 edition revised as of
January 1, 2022.
For any amended standards for computer room air conditioners
that rely on net sensible coefficient of performance (NSenCOP)
published after January 1, 2022, manufacturers must use the results
of testing under appendix E1 to this subpart to determine
compliance. Manufacturers may use appendix E1 to certify compliance
with any amended standards prior to the applicable compliance date
for those standards.
[[Page 21841]]
Specifically, representations, including compliance
certifications, related to energy consumption must be based upon
results generated under the appropriate appendix that applies (i.e.,
this appendix or appendix E1 to this subpart) when determining
compliance with the relevant standard.
1. Incorporation by Reference.
DOE incorporated by reference in Sec. 431.95 the entire
standard for ASHRAE 127-2007. However, certain enumerated provisions
of ASHRAE 127-2007, as listed in section 1.1, are inapplicable. To
the extent that there is a conflict between the terms or provisions
of a referenced industry standard and the CFR, the CFR provisions
control.
1.1 ASHRAE 127-2007:
(a) Section 5.11 is inapplicable as specified in section 2 of
this appendix.
(b) [Reserved]
1.2 [Reserved]
2. General. Determine the sensible coefficient of performance
(SCOP) in accordance with ASHRAE 127-2007.
3. Optional break-in period. Manufacturers may optionally
specify a ``break-in'' period, not to exceed 20 hours, to operate
the equipment under test prior to conducting the test method
specified in this appendix. A manufacturer who elects to use an
optional compressor break-in period in its certification testing
should record this period's duration as part of the information in
the supplemental testing instructions under 10 CFR 429.43.
4. Additional provisions for equipment set-up. The only
additional specifications that may be used in setting up the basic
model for test are those set forth in the installation and operation
manual shipped with the unit. Each unit should be set up for test in
accordance with the manufacturer installation and operation manuals.
Sections 4.1 and 4.2 of this appendix provide specifications for
addressing key information typically found in the installation and
operation manuals.
4.1. If a manufacturer specifies a range of superheat, sub-
cooling, and/or refrigerant pressure in its installation and
operation manual for a given basic model, any value(s) within that
range may be used to determine refrigerant charge or mass of
refrigerant, unless the manufacturer clearly specifies a rating
value in its installation and operation manual, in which case the
specified rating value must be used.
4.2. The airflow rate used for testing must be that set forth in
the installation and operation manuals being shipped to the
commercial customer with the basic model and clearly identified as
that used to generate the DOE performance ratings. If a rated
airflow value for testing is not clearly identified, a value of 400
standard cubic feet per minute (scfm) per ton must be used.
0
11. Add appendix E1 to subpart F of part 431 to read as follows:
Appendix E1 to Subpart F of Part 431--Uniform Test Method for Measuring
the Energy Consumption of Computer Room Air Conditioners
Note: Prior to the compliance date for any amended energy
conservation standards based on NSenCOP for computer room air
conditioners, representations with respect to energy use or
efficiency of this equipment, including compliance certifications,
must be based on testing pursuant to appendix E to this subpart.
Subsequently, manufacturers must use the results of testing under
this appendix to determine compliance with any amended energy
conservation standards for computer room air conditioners provided
in Sec. 431.97 that are published after January 1, 2022, and that
rely on net sensible coefficient of performance (NSenCOP).
Specifically, representations, including compliance certifications,
related to energy consumption must be based upon results generated
under the appropriate appendix that applies (i.e., appendix E to
this subpart or this appendix) when determining compliance with the
relevant standard. Manufacturers may use this appendix to certify
compliance with any amended standards prior to the applicable
compliance date for those standards.
1. Incorporation by Reference
DOE incorporated by reference in Sec. 431.95 the entire
standards for AHRI 1360-2022, ANSI/ASHRAE 37-2009, and ANSI/ASHRAE
127-2020. However, as listed in sections 1.1, 1.2, and 1.3 of this
appendix, only certain enumerated provisions of AHRI 1360-2022 and
ANSI/ASHRAE 127-2020 are applicable, and only certain enumerated
provisions of ANSI/ASHRAE 37-2009 are not applicable. To the extent
that there is a conflict between the terms or provisions of a
referenced industry standard and the CFR, the CFR provisions
control.
1.1 AHRI 1360-2022:
(a) The following sections of Section 3. Definitions--3.1
(Expressions of Provision), 3.2.2 (Air Sampling Device(s)), 3.2.7
(Computer and Data Processing Room Air Conditioner), 3.2.22 (Indoor
Unit), 3.2.25 (Manufacturer's Installation Instruction), 3.2.27 (Net
Sensible Cooling Capacity), 3.2.28 (Net Total Cooling Capacity),
3.2.37 (Standard Air) and 3.2.38 (Standard Airflow) are applicable.
(b) Section 5. Test Requirements, is applicable.
(c) The following sections of Section 6. Rating Requirements--
6.1-6.3, 6.5 and 6.7 are applicable.
(d) Appendix C. Standard Configurations--Normative, is
applicable.
(e) Section D2 of Appendix D. Non-Standard Indoor Fan Motors for
CRAC units, is applicable.
(f) Appendix E. Method of Testing Computer and Data Processing
Room Air Conditioners--Normative, is applicable.
(g) Appendix F. Indoor and Outdoor Air Condition Measurement--
Normative is applicable.
1.2 ANSI/ASHRAE 127-2020:
(a) Appendix A--Figure A-1, Test duct for measuring air flow and
static pressure on downflow units, is applicable.
(b) [Reserved].
1.3 ASHRAE 37-2009:
(a) Section 1 Purpose is inapplicable.
(b) Section 2 Scope is inapplicable.
(c) Section 4 Classification is inapplicable.
2. General. Determine the net sensible coefficient of
performance (NSenCOP), in accordance with AHRI 1360-2022, ANSI/
ASHRAE 127-2020, and ANSI/ASHRAE 37-2009. In cases where there is a
conflict between these sources, the language of this appendix takes
highest precedence, followed by AHRI 1360-2022, followed by ANSI/
ASHRAE 127-2020, followed by ANSI/ASHRAE 37-2009. Any subsequent
amendment to a referenced document by a standard-setting
organization will not affect the test procedure in this appendix,
unless and until this test procedure is amended by DOE. Material is
incorporated as it exists on the date of the approval, and
notification of any change in the incorporation will be published in
the Federal Register.
3. Test Conditions
3.1. Test Conditions for Certification. When testing to certify
to the energy conservation standards in Sec. 431.97, test using the
``Indoor Return Air Temperature Standard Rating Conditions'' and
``Heat Rejection/Cooling Fluid Standard Rating Conditions''
conditions, as specified in Tables 3 and 4 of AHRI 1360-2022,
respectively.
4. Set-Up and Test Provisions for Specific Components. When
testing a unit that includes any of the features listed in Table 4.1
of this appendix, test in accordance with the set-up and test
provisions specified in Table 4.1 of this appendix.
Table 4.1--Test Provisions for Specific Components
------------------------------------------------------------------------
Component Description Test provisions
------------------------------------------------------------------------
Air Economizers............. An automatic system For any air
that enables a economizer that is
cooling system to factory-installed,
supply outdoor air place the
to reduce or economizer in the
eliminate the need 100% return
for mechanical position and close
cooling during mild and seal the
or cold weather. outside air dampers
for testing. For
any modular air
economizer shipped
with the unit but
not factory-
installed, do not
install the
economizer for
testing.
Process Heat Recovery/ A heat exchanger Disconnect the heat
Reclaim Coils/Thermal located inside the exchanger from its
Storage. unit that heat source for
conditions the testing.
equipment's supply
air using energy
transferred from an
external source
using a vapor, gas,
or liquid.
[[Page 21842]]
Evaporative Pre-cooling of Water is evaporated Disconnect the unit
Condenser Intake Air. into the air from the water
entering the air- supply for testing
cooled condenser to (i.e., operate
lower the dry-bulb without active
temperature and evaporative
thereby increase cooling).
efficiency of the
refrigeration cycle.
Steam/Hydronic Heat Coils... Coils used to Test with steam/
provide hydronic heat coils
supplemental heat. in place but
providing no heat.
Refrigerant Reheat Coils.... A heat exchanger De-activate
located downstream refrigerant re-heat
of the indoor coil coils so as to
that heats the provide the minimum
supply air during (none if possible)
cooling operation reheat achievable
using high pressure by the system
refrigerant in controls.
order to increase
the ratio of
moisture removal to
cooling capacity
provided by the
equipment.
Fire/Smoke/Isolation Dampers A damper assembly For any fire/smoke/
including means to isolation dampers
open and close the that are factory-
damper mounted at installed, close
the supply or and seal the
return duct opening dampers for
of the equipment. testing. For any
modular fire/smoke/
isolation dampers
shipped with the
unit but not
factory-installed,
do not install the
dampers for
testing.
Harmonic Distortion A high voltage Remove harmonic
Mitigation Devices. device that reduces distortion
harmonic distortion mitigation devices
measured at the for testing.
line connection of
the equipment that
is created by
electronic
equipment in the
unit.
Humidifiers................. A device placed in Test with
the supply air humidifiers in
stream for moisture place but providing
evaporation and no humidification.
distribution. The
device may require
building steam or
water, hot water,
electricity, or gas
to operate.
Electric Reheat Elements.... Electric reheat Test with electric
elements and reheat elements in
controls that are place but providing
located downstream no heat.
of the cooling coil
that may heat the
air using
electrical power
during the
dehumidification
process.
Non-standard Power A device applied to Disable the non-
Transformer. a high voltage load standard power
that transforms transformer during
input electrical testing.
voltage to that
voltage necessary
to operate the load.
Chilled Water Dual Cooling A secondary chilled Test with chilled
Coils. water coil added in water dual cooling
the indoor air coils in place but
stream for use as providing no
the primary or cooling.
secondary cooling
circuit in
conjunction with a
separate chiller.
High-Effectiveness Indoor Indoor air filters Test with the filter
Air Filtration. with greater air offered by the
filtration manufacturer with
effectiveness than the least air
Minimum Efficiency filtration
Reporting Value effectiveness that
(MERV) 8 for ducted meets or exceeds
units and MERV 1 MERV 8 for ducted
for non-ducted units and MERV 1
units. for non-ducted
units.
------------------------------------------------------------------------
[FR Doc. 2023-06760 Filed 4-10-23; 8:45 am]
BILLING CODE 6450-01-P