Energy Conservation Program: Test Procedure for Consumer Boilers, 15510-15555 [2023-03982]
Download as PDF
15510
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[EERE–2019–BT–TP–0037]
RIN 1904–AE83
Energy Conservation Program: Test
Procedure for Consumer Boilers
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
The U.S. Department of
Energy (‘‘DOE’’) amends its test
procedure for consumer boilers
established under the Energy Policy and
Conservation Act. This rulemaking
fulfills DOE’s obligation to review its
test procedures for covered products at
least once every seven years. The
revisions include: incorporating by
reference the latest versions of the
industry standards currently referenced
in the Federal test procedure; relocating
the test procedure to a new appendix
separate from the residential furnace
test procedure; removing an extraneous
definition from its regulatory
definitions; and making clarifying
corrections to calculations. These
revisions will improve the
representativeness of the test method
and will not be unduly burdensome to
conduct.
DATES: The effective date of this rule is
April 12, 2023. The amendments will be
mandatory for product testing starting
September 11, 2023.
The incorporation by reference of
certain material listed in the rule is
approved by the Director of the Federal
Register as of April 12, 2023. The
incorporation by reference of certain
other material listed in the rule was
approved by the Director of the Federal
Register on March 23, 2009, and
February 16, 2016.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at www.regulations.gov. All
documents in the docket are listed in
the www.regulations.gov index.
However, not all documents listed in
the index may be publicly available,
such as those containing information
that is exempt from public disclosure.
A link to the docket web page can be
found at www.regulations.gov/docket/
EERE-2019-BT-TP-0037. The docket
web page contains instructions on how
to access all documents, including
public comments, in the docket.
ddrumheller on DSK120RN23PROD with RULES2
SUMMARY:
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
For further information on how to
review the docket, contact the
Appliance and Equipment Standards
Program staff at (202) 287–1445 or by
email: ApplianceStandardsQuestions@
ee.doe.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Julia Hegarty, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, EE–2J, 1000
Independence Avenue SW, Washington,
DC 20585–0121. Telephone: (240) 597–
6737. Email: ApplianceStandards
Questions@ee.doe.gov.
Ms. Amelia Whiting, U.S. Department
of Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue SW,
Washington, DC 20585–0121.
Telephone: (202) 586–2588. Email:
Amelia.Whiting@hq.doe.gov.
SUPPLEMENTARY INFORMATION: DOE
maintains material previously approved
for incorporation by reference in part
430: ANSI/ASHRAE 103–1993 and
ASTM D2156–09 (Reapproved 2013).
DOE incorporates by reference the
following industry standards into 10
CFR part 430:
ANSI/ASHRAE Standard 41.6–2014,
‘‘Standard Method for Humidity
Measurement,’’ ANSI-approved July 3,
2014 (‘‘ASHRAE 41.6–2014’’).
ANSI/ASHRAE 103–2017, ‘‘Method of
Testing for Annual Fuel Utilization
Efficiency of Residential Central
Furnaces and Boilers,’’ ANSI-approved
July 3, 2017 (‘‘ASHRAE 103–2017’’).
Copies ofANSI/ASHRAE 41.6–2014
and ANSI/ASHRAE 103–2017 can be
obtained from the American Society of
Heating, Refrigerating and AirConditioning Engineers, Inc. (ASHRAE),
180 Technology Parkway NW, Peachtree
Corners, GA 30092, (800) 527–4723 or
(404) 636–8400, or online at
www.ashrae.org.
ASTM International (‘‘ASTM’’)
Standard D2156–09 (Reapproved 2018),
‘‘Standard Test Method for Smoke
Density in Flue Gases from Burning
Distillate Fuels,’’approved October 1,
2018 (‘‘ASTM D2156–09 (R2018)’’).
Copies of ASTM D2156–09 (R2018)
can be obtained from ASTM
International, 100 Barr Harbor Drive,
P.O. Box C700, West Conshohocken, PA
19428–2959 or online at www.astm.org.
International Electrotechnical
Commission (‘‘IEC’’) 62301, ‘‘Household
electrical appliances—Measurement of
standby power,’’ (Edition 2.0) 2011–01
(‘‘IEC 62301’’).
Copies of IEC 62301 can be obtained
from the International Electrotechnical
Commission (‘‘IEC’’), 3 Rue de Varembe,
Case Postale 131, 1211 Geneva 20,
Switzerland; or online at
webstore.iec.ch.
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
See section IV.N of this document for
a further discussion of these standards.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Scope of Applicability
1. Combination Space/Water Heating
Boilers
2. Heat Pump Boilers
B. Definitions
C. Metric
D. Updates to Industry Standards
1. ANSI/ASHRAE 103
2. IEC 62301 and ASTM D2156–09
E. Steady-State Efficiency for Condensing
Modulating Boilers
F. Corrections and Clarifications
1. Off-Cycle Losses
2. Conversion Factor for British Thermal
Units
3. Oil Pressure Instrumentation Error
4. Gas Inlet Conditions
5. Active Mode Electrical Energy
Consumption
6. Circulator Pumps
7. Units With Draft Hoods or Draft
Diverters
8. Rounding of AFUE
G. Other Test Procedure Topics
1. Outdoor Design Temperature
2. Ambient Conditions
3. Combustion Settings
4. Supplemental Test Instructions
5. Input Rates for Step Modulating Boilers
6. Return Water Temperature
7. Standby Mode and Off Mode Electrical
Energy Consumption
8. Full Fuel Cycle Efficiency
9. Idle Losses
H. Alternative Efficiency Determination
Methods
I. Certification Provisions for Cast-Iron
Boilers
J. Effective and Compliance Dates
K. Test Procedure Costs
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866
and 13563
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by
Reference
V. Approval of the Office of the Secretary
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
I. Authority and Background
Furnaces, which include consumer
boilers, are included in the list of
‘‘covered products’’ for which the U.S.
Department of Energy (‘‘DOE’’) is
authorized to establish and amend
energy conservation standards and test
procedures. (42 U.S.C. 6291(23); 42
U.S.C. 6292(a)(5)) DOE’s energy
conservation standards and test
procedures for consumer boilers are
currently prescribed at 10 CFR
430.32(e)(2) and 10 CFR part 430,
subpart B, appendix N, Uniform Test
Method for Measuring the Energy
Consumption of Furnaces and Boilers
(‘‘appendix N’’), respectively.1 The
following sections discuss DOE’s
authority to establish test procedures for
consumer boilers and relevant
background information regarding
DOE’s consideration of test procedures
for this product.
ddrumheller on DSK120RN23PROD with RULES2
A. Authority
The Energy Policy and Conservation
Act, Public Law 94–163, as amended
(‘‘EPCA’’),2 authorizes DOE to regulate
the energy efficiency of a number of
consumer products and certain
industrial equipment. (42 U.S.C. 6291–
6317) Title III, Part B of EPCA 3
established the Energy Conservation
Program for Consumer Products Other
Than Automobiles, which sets forth a
variety of provisions designed to
improve energy efficiency. These
products include furnaces, which
include consumer boilers, the subject of
this document. (42 U.S.C. 6292(a)(5))
The energy conservation program
under EPCA consists essentially of four
parts: (1) testing, (2) labeling, (3) Federal
energy conservation standards, and (4)
certification and enforcement
procedures. Relevant provisions of
EPCA specifically include definitions
(42 U.S.C. 6291), test procedures (42
U.S.C. 6293), labeling provisions (42
U.S.C. 6294), energy conservation
standards (42 U.S.C. 6295), and the
authority to require information and
reports from manufacturers (42 U.S.C.
6296).
The testing requirements consist of
test procedures that manufacturers of
covered products must use as the basis
for (1) certifying to DOE that their
products comply with the applicable
1 Upon the effective date of this final rule, the test
procedure for consumer boilers will be relocated to
10 CFR 430, subpart B, appendix EE.
2 All references to EPCA in this document refer
to the statute as amended through the Energy Act
of 2020, Public Law 116–260 (Dec. 27, 2020), which
reflect the last statutory amendments that impact
Parts A and A–1 of EPCA.
3 For editorial reasons, upon codification in the
U.S. Code, Part B was redesignated Part A.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
energy conservation standards adopted
under EPCA (42 U.S.C. 6295(s)), and (2)
making other representations about the
efficiency of those products (42 U.S.C.
6293(c)). Similarly, DOE must use these
test procedures to determine whether
the products comply with any relevant
standards promulgated under EPCA. (42
U.S.C. 6295(s))
Federal energy efficiency
requirements for covered products
established under EPCA generally
supersede State laws and regulations
concerning energy conservation testing,
labeling, and standards. (42 U.S.C. 6297)
DOE may, however, grant waivers of
Federal preemption for particular State
laws or regulations, in accordance with
the procedures and other provisions of
EPCA. (42 U.S.C. 6297(d))
Under 42 U.S.C. 6293, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered products.
EPCA requires that any test procedures
prescribed or amended under this
section shall be reasonably designed to
produce test results which measure
energy efficiency, energy use, or
estimated annual operating cost of a
covered product during a representative
average use cycle (as determined by the
Secretary) or period of use and shall not
be unduly burdensome to conduct. (42
U.S.C. 6293(b)(3))
EPCA also requires that, at least once
every 7 years, DOE evaluate test
procedures for each type of covered
product, including consumer boilers, to
determine whether amended test
procedures would more accurately or
fully comply with the requirements for
the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle or period of use. (42 U.S.C.
6293(b)(1)(A))
If the Secretary determines, on her
own behalf or in response to a petition
by any interested person, that a test
procedure should be prescribed or
amended, the Secretary shall promptly
publish in the Federal Register
proposed test procedures and afford
interested persons an opportunity to
present oral and written data, views,
and arguments with respect to such
procedures. The comment period on a
proposed rule to amend a test procedure
shall be at least 60 days and may not
exceed 270 days. In prescribing or
amending a test procedure, the
Secretary shall take into account such
information as the Secretary determines
relevant to such procedure, including
technological developments relating to
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
15511
energy use or energy efficiency of the
type (or class) of covered products
involved. (42 U.S.C. 6293(b)(2)) If DOE
determines that test procedure revisions
are not appropriate, DOE must publish
its determination not to amend the test
procedures.
In addition, EPCA requires that DOE
amend its test procedures for all covered
products to integrate measures of
standby mode and off mode energy
consumption into the overall energy
efficiency, energy consumption, or other
energy descriptor, unless the current
test procedure already incorporates the
standby mode and off mode energy
consumption, or if such integration is
technically infeasible. (42 U.S.C.
6295(gg)(2)(A)) If an integrated test
procedure is technically infeasible, DOE
must prescribe separate standby mode
and off mode energy use test procedures
for the covered product, if a separate
test is technically feasible. (Id.) Any
such amendment must consider the
most current versions of the
International Electrotechnical
Commission (‘‘IEC’’) Standard 62301 4
and IEC Standard 62087 5 as applicable.
(42 U.S.C. 6295(gg)(2)(A))
DOE is publishing this final rule in
satisfaction of the 7-year review
requirement specified in EPCA. (42
U.S.C. 6293(b)(1)(A))
B. Background
As stated, DOE’s existing test
procedure for consumer boilers appears
at Title 10 of CFR part 430, subpart B,
appendix N, Uniform Test Method for
Measuring the Energy Consumption of
Furnaces and Boilers (‘‘appendix N’’)
and is used to determine the annual fuel
utilization efficiency (‘‘AFUE’’), which
is the regulatory metric for consumer
boilers.
DOE most recently updated its test
procedure for consumer boilers in a
final rule published in the Federal
Register on January 15, 2016 (‘‘January
2016 Final Rule’’). 81 FR 2628. The
January 2016 Final Rule amended the
existing DOE test procedure for
consumer boilers to improve the
consistency and accuracy of test results
generated using the DOE test procedure
and to reduce test burden. In particular,
the modifications relevant to consumer
boilers included: (1) clarifying the
definition of the electrical power term
‘‘PE’’; (2) adopting a smoke stick test for
determining whether minimum default
4 IEC 62301, Household electrical appliances—
Measurement of standby power (Edition 2.0, 2011–
01).
5 IEC 62087, Audio, video and related
equipment—Methods of measurement for power
consumption (Edition 1.0, Parts 1–6: 2015, Part 7:
2018).
E:\FR\FM\13MRR2.SGM
13MRR2
15512
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
draft factors can be applied; (3) allowing
for optional measurement of condensate
during establishment of steady-state
conditions; (4) updating references to
the applicable installation and operation
(‘‘I&O’’) manual and providing
clarifications for when the I&O manual
does not specify test setup; and (5)
revising the AFUE reporting precision.
DOE also revised the definitions of
several terms in the test procedure and
added an enforcement provision to
provide a method of test for DOE to
determine compliance with the
automatic means design requirement
mandated by the Energy Independence
and Security Act of 2007, Public Law
110–140 (Dec. 19, 2007). 81 FR 2628,
2629–2630.
On May 15, 2020, DOE published in
the Federal Register a request for
information (‘‘May 2020 RFI’’) seeking
comments on the existing DOE test
procedure for consumer boilers, which
incorporates by reference ANSI/
ASHRAE Standard 103–1993. 85 FR
29352. ANSI/ASHRAE 103–1993
provides test procedures for
determining the AFUE of residential
central furnaces and boilers. In the May
2020 RFI, DOE requested comments,
information, and data about a number of
issues, including: (1) the test
procedure’s scope and definitions; (2)
updates to industry standards; (3)
ambient test conditions; (4) provisions
for testing boilers with manually
adjustable combustion airflow; (5)
calculation of steady-state heat loss for
condensing, modulating boilers; and (6)
provisions for testing step modulating
boilers. Id. at 85 FR 29354–29357. DOE
also sought comment generally on
whether the current test procedures are
reasonably designed to produce results
that measure energy efficiency during a
representative average use cycle or
period of use, whether any potential
amendments would make the test
procedure unduly burdensome to
conduct, whether existing test
procedures limit a manufacturer’s
ability to provide additional features,
the impact of any potential amendments
on manufacturers including small
businesses, whether there are any
potential issues related to emerging
smart technologies, and generally any
other aspect of the test procedure for
consumer boilers. Id. at 85 FR 23957.
On March 15, 2022, DOE published in
the Federal Register a notice of
proposed rulemaking (‘‘March 2022
NOPR’’) proposing to amend the current
test procedure to incorporate by
reference the most current revision to
the applicable industry standard that
was available at the time, ANSI/
ASHRAE 103–2017, ‘‘Methods of
Testing for Annual Fuel Utilization
Efficiency of Residential Central
Furnaces and Boilers,’’ as well as
updating the definitions to reflect the
changes in ANSI/ASHRAE 103–2017 as
compared to the version of the standard
currently incorporated by reference (i.e.,
ANSI/ASHRAE 103–1993). 87 FR
14624. In addition, the March 2022
NOPR proposed to update appendix N
to remove the provisions applicable
only to consumer boilers and to rename
the appendix ‘‘Uniform Test Method for
Measuring the Energy Consumption of
Furnaces.’’ Correspondingly, DOE
proposed to relocate the test procedure
specific to consumer boilers at 10 CFR
430 subpart B to a new appendix, EE,
‘‘Uniform Test Method for Measuring
the Energy Consumption of Boilers’’
(‘‘appendix EE’’). Id.
On April 7, 2022, DOE held a public
meeting via webinar to solicit feedback
from stakeholders on the requests for
comment in the March 2022 NOPR.
DOE received comments in response
to the March 2022 NOPR from the
interested parties listed in Table I.1.
ddrumheller on DSK120RN23PROD with RULES2
TABLE I.1—LIST OF COMMENTERS WITH WRITTEN SUBMISSION IN RESPONSE TO THE MARCH 2022 NOPR
Comment
No. in
the docket
Commenter(s)
Reference in this
final rule
American Gas Association and American Public Gas Association ...........................
Air-Conditioning, Heating, and Refrigeration Institute ...............................................
A.O. Smith Corporation ..............................................................................................
John Busse ................................................................................................................
Bradford White Corporation .......................................................................................
Pacific Gas and Electric Company, San Diego Gas and Electric, and Southern
California Edison (collectively, the California Investor-Owned Utilities).
Crown Boiler Company ..............................................................................................
Appliance Standards Awareness Project, American Council for an Energy-Efficient
Economy, Consumer Federation of America, National Consumer Law Center
Natural Resources Defense Council, and Northwest Energy Efficiency Alliance.
New York State Energy Research and Development Authority ................................
Rheem Manufacturing Company ...............................................................................
U.S. Boiler Company .................................................................................................
AGA and APGA .....
AHRI .......................
A.O. Smith ..............
Busse .....................
BWC .......................
CA IOUs .................
25
26
24
22
19
20
Utility Associations.
Trade Association.
Manufacturer.
Individual.
Manufacturer.
Utilities.
Crown .....................
Joint Advocates ......
16
21
Manufacturer.
Efficiency Organizations.
NYSERDA ..............
Rheem ....................
U.S. Boiler ..............
23
18
17
State Agency.
Manufacturer.
Manufacturer.
A parenthetical reference at the end of
a comment quotation or paraphrase
provides the location of the item in the
public record.6 To the extent that
interested parties have provided written
comments that are substantively
consistent with any oral comments
6 The parenthetical reference provides a reference
for information located in the docket of DOE’s
rulemaking to develop test procedures for consumer
boilers. (Docket No. EERE–2019–BT–TP–0037,
maintained at www.regulations.gov.) The references
are arranged as follows: (commenter name,
comment docket ID number, page of that
document).
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
provided during the April 7, 2022,
public meeting, DOE cites the written
comments throughout this final rule.
DOE did not identify any oral comments
provided during the webinar that are
not substantively addressed by written
comments.
II. Synopsis of the Final Rule
In this final rule, DOE updates
appendix N to remove the provisions
applicable only to consumer boilers and
to rename the appendix ‘‘Uniform Test
Method for Measuring the Energy
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
Commenter type
Consumption of Furnaces.’’
Correspondingly, this final rule
establishes a new test procedure specific
to consumer boilers in a new appendix
EE. In appendix EE, DOE includes all
provisions currently included in
appendix N relevant to consumer
boilers, with the following
modifications:
(1) Incorporate by reference the
current version of the applicable
industry standard, ANSI/ASHRAE 103–
2017, ‘‘Methods of Testing for Annual
Fuel Utilization Efficiency of
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
Residential Central Furnaces and
Boilers,’’ which includes several
updates to the test method.
(2) Incorporate by reference the
current version of ASTM Standard
D2156–09 (Reapproved 2018),
‘‘Standard Test Method for Smoke
Density in Flue Gases from Burning
Distillate Fuels.’’
(3) Incorporate by reference ANSI/
ASHRAE 41.6–2014, ‘‘Standard Method
for Humidity Measurement.’’
(4) Update the definitions to reflect
the changes in ANSI/ASHRAE 103–
2017 as compared to ANSI/ASHRAE
103–1993.
(5) Provide corrections to erroneous
calculations and add clarifications to
test conditions and setup requirements.
15513
DOE is also removing the definition of
‘‘outdoor furnace or boiler’’ from 10 CFR
430.2.
The adopted amendments are
summarized in Table II.1 compared to
the test procedure provision prior to the
amendment, as well as the reason for
the adopted change.
TABLE II.1—SUMMARY OF CHANGES IN THE AMENDED TEST PROCEDURE
DOE test procedure prior to amendment
Amended test procedure
Attribution
Incorporated by reference industry standard ANSI/
ASHRAE 103–1993.
Incorporated by reference the procedure for adjusting
oil-fired burner by referencing industry standard ASTM
D2156–09 (Reapproved 2013).
Incorporates by reference ANSI/ASHRAE 103–2017 in
the new appendix EE.
Incorporates by reference the procedure for adjusting
oil-fired burner by referencing industry standard
ASTM D2156–09 (Reapproved 2018) in the new appendix EE.
Incorporates by reference ANSI/ASHRAE 41.6–2014 instructions for measuring relative humidity of the test
room in the new appendix EE.
Harmonization with industry
standard update.
Harmonization with industry
standard update.
Limited the maximum relative humidity of the test room
during certain tests but did not provide specific instructions for how to measure relative humidity.
Included a definition for ‘‘outdoor furnace or boiler’’ at 10
CFR 430.2.
Included an undefined term, ‘‘standard cubic foot of gas’’
Defined ‘‘control’’ and ‘‘isolated combustion system’’ in
appendix N.
Referenced calculations in ANSI/ASHRAE 103–1993
which yielded a circular reference when calculating
the steady-state efficiency for condensing modulating
boilers.
Referenced Table 9 in ANSI/ASHRAE 103–1993, which
assigned fixed values for the average on-time and offtime per cycle for two-stage and modulating boilers.
Specified cycle times (tON and tOFF) to a fraction of a
second through reference to ANSI/ASHRAE 103–1993
Table 9.
Calculated oversize factor from a lookup table based on
design heating requirement (‘‘DHR’’) in ANSI/ASHRAE
103–1993.
Used a purge time limit of 5 seconds to determine
whether heat-up and cool-down tests may be optionally omitted, whereas a purge time limit of 30 seconds
was used to determine whether a post-purge (tP) of 0
seconds could be assigned in calculations.
Limited the maximum value of post-purge (tP) to 180
seconds if a purge time of greater than 3 minutes was
observed.
ddrumheller on DSK120RN23PROD with RULES2
Referenced calculations for off-cycle infiltration losses in
ANSI/ASHRAE 103–1993 which had a typographical
error where the conversion from minutes to hours was
performed incorrectly.
Provided inconsistent unit conversion factor from watts
(‘‘W’’) to British thermal units per hour (‘‘Btu/h’’), using
values of 3.412 or 3.413.
Required the use of a gas having a specific gravity as
shown in Table 1 of ANSI/ASHRAE 103–1993.
Referenced incorrect sections of appendix N test procedure regarding average annual auxiliary electrical consumption determination provisions at 10 CFR
430.23(n)(1).
Referenced values in ANSI/ASHRAE 103–1993 for determining national average burner operating hours
(‘‘BOH’’), average annual fuel energy consumption
(‘‘EF’’), and average annual auxiliary electrical energy
consumption (‘‘EAE’’).
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
PO 00000
Removes the definition for ‘‘outdoor furnace or boiler’’ ..
Adds a definition for ‘‘standard cubic foot of gas’’ in
new appendix EE.
Adopts the definitions for the terms ‘‘control’’ and ‘‘isolated combustion system’’ from ASHRAE 103–2017
in new appendix EE.
Includes an amended calculation for balance-point temperature (TC) which resolves the circular reference in
new appendix EE.
References Table 7 of ANSI/ASHRAE 103–2017 in the
new appendix EE, which uses calculations for determining the average on-time and off-time per cycle for
two-stage and modulating boilers.
Provides additional specification in appendix EE to require that calculated cycle timings shall be rounded
to the nearest second.
Adopts the ANSI/ASHRAE 103–2017 methodology of
assigning a constant value of 0.70 to a to represent
the national average oversize factor in appendix EE.
Applies the 30-second limit in appendix EE for determining when the heat-up and cool-down tests may
be optionally omitted.
Referenced by industry
standard ANSI/ASHRAE
103–2017, which is being
incorporated by reference
in this final rule.
Unused definition.
Increase clarity for testing
conditions.
Harmonization with industry
standard update.
Correction.
Harmonization with industry
standard update.
Clarification to reduce test
burden.
Harmonization with industry
standard update.
Harmonization with industry
standard update.
Removes the maximum value of 180 seconds in appendix EE and requires an additional temperature
measurement to be taken if the post-purge is greater
than 3 minutes.
Specifies the correct calculation for off-cycle infiltration
losses through reference to ANSI/ASHRAE 103–
2017 and corrects minutes to hours conversion error
in new appendix EE.
Corrects the conversion factor from W to Btu/h to 3.412
throughout new appendix EE.
Harmonization with industry
standard update.
Requires the use of a gas having a specific gravity
‘‘approximate’’ to what is shown in Table 1 of ANSI/
ASHRAE 103–2017 in the new appendix EE.
Revises 10 CFR 430.23(n)(1) to update references regarding average annual auxiliary electrical consumption to the correct sections of appendix N and the
new appendix EE.
References values in ANSI/ASHRAE 103–2017 for determining national average BOH, average annual EF,
and average annual EAE in the new appendix EE.
Clarification to reduce test
burden.
Frm 00005
Fmt 4701
Sfmt 4700
E:\FR\FM\13MRR2.SGM
13MRR2
Correction.
Correction.
Correction.
Harmonization with industry
standard update.
15514
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
TABLE II.1—SUMMARY OF CHANGES IN THE AMENDED TEST PROCEDURE—Continued
DOE test procedure prior to amendment
Amended test procedure
Included instructions for the setup of boilers with draft
hoods or draft diverters which specified a minimum Rvalue for insulation but did not specify the units of
measure for R-value.
ddrumheller on DSK120RN23PROD with RULES2
DOE has determined that the
amendments described in section III of
this document and adopted in this final
rule will not substantively impact the
measured efficiency of consumer boilers
or require retesting or recertification
solely as a result of DOE’s adoption of
the amendments to the test procedures.
Additionally, DOE has determined that
the amendments will not increase the
cost of testing. Discussion of DOE’s
actions is addressed in detail in section
III of this document.
The effective date for the amended
test procedures adopted in this final
rule is 30 days after publication of this
document in the Federal Register.
Representations of energy use or energy
efficiency must be based on testing in
accordance with the amended test
procedures beginning 180 days after the
publication of this final rule.
III. Discussion
The subsequent sections of this final
rule discuss specific topics raised in this
rulemaking, including comments DOE
received in response to the March 2022
NOPR. These topics include: scope of
applicability of the test procedure,
definitions in the test procedure, the
AFUE metric, updates to industry
standards, clarifications and corrections
to the current test procedure, and test
conditions.
In addition, DOE received comments
relating to the general processes by
which DOE amends test procedures and
energy conservation standards for
covered products and equipment.
BWC urged DOE to consider the
cumulative regulatory burden placed on
manufacturers that produce several
different types of regulated products for
which there are simultaneous
rulemakings. BWC noted that additional
burdens on manufacturers include
changes to ENERGY STAR
specifications; the Securities and
Exchange Commission’s proposed rule
to enhance and standardize climaterelated disclosures; updated state and
local codes; demand-response
requirements for electric water heaters
in Western States; lower nitrogen oxides
(NOX) emissions proposals in the State
of California; proposed amendments to
California Proposition 65; and extended
producer responsibility legislation
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
Includes units of measure for R-value in the new appendix EE.
recently enacted in both Maine and
Oregon. (BWC, No. 19 at p. 4–5)
In response, DOE notes that
cumulative regulatory burden on
manufacturers is assessed as part of
energy conservation standards
rulemakings. The amendments to the
consumer boilers test procedure, as
promulgated by this final rule, are not
expected to add burden to
manufacturers because the amendments
do not substantially impact efficiency
ratings or alter the type of equipment
necessary to perform testing. Test costs
and burden are discussed in section
III.K of this document.
AGA and APGA commented that DOE
should implement the recommendations
from the recent National Academies of
Sciences, Engineering, and Medicine
report (‘‘NASEM report’’) 7 into all of its
appliance rulemakings for test
procedures or energy conservation
standards. AGA and APGA reiterated
recommendations pertaining to analyses
that DOE conducts in order to determine
whether potential new or amended
energy conservation standards are
technologically feasible and
economically justified. (AGA and
APGA, No. 25, p. 3) For example, AGA
and APGA highlighted the NASEM
report’s recommendations that DOE pay
greater attention to the justification for
its standards, expand the Cost Analysis
segment of the Engineering Analysis for
its rules, put greater weight on ex post
and market-based evidence markups,
place greater emphasis on providing an
argument for the plausibility and
magnitude of any market failure related
to the energy efficiency gap, and give
greater attention to a broader set of
potential market failures on the supply
side. Id.
Given that this is a test procedure
rulemaking for which DOE must meet
specific statutory criteria as outlined in
42 U.S.C. 6293(b)(3), the
recommendations in the NASEM report
7 Although not specified, DOE interprets this
comment to refer to the National Academies of
Science, Engineering, and Medicine 2021 report
entitled ‘‘Review of Methods Used by the U.S.
Department of Energy in Setting Appliance and
Equipment Standards.’’ Copies of the report are
available at nap.nationalacademies.org/catalog/
25992/review-of-methods-used-by-the-usdepartment-of-energy-in-setting-appliance-andequipment-standards.
PO 00000
Attribution
Frm 00006
Fmt 4701
Sfmt 4700
Correction.
which pertain specifically to the
processes by which DOE analyzes
energy conservation standards are
misplaced. DOE will consider this
comment in a separate rulemaking
considering all product categories.
A. Scope of Applicability
As discussed, in the context of
‘‘covered products,’’ EPCA includes
boilers in the definition of ‘‘furnace.’’
(42 U.S.C. 6291(23)) EPCA defines the
term ‘‘furnace’’ to mean a product
which utilizes only single-phase electric
current, or single-phase electric current
or DC current in conjunction with
natural gas, propane, or home heating
oil, and which: (1) is designed to be the
principal heating source for the living
space of a residence; (2) is not contained
within the same cabinet with a central
air conditioner whose rated cooling
capacity is above 65,000 Btu/h; (3) is an
electric central furnace, electric boiler,
forced-air central furnace, gravity
central furnace, or low pressure steam
or hot water boiler; and (4) has a heat
input rate of less than 300,000 Btu/h for
electric boilers and low pressure steam
or hot water boilers and less than
225,000 Btu/h for forced-air central
furnaces, gravity central furnaces, and
electric central furnaces. Id. DOE has
codified this definition in its regulations
at 10 CFR 430.2.
DOE defines ‘‘electric boiler’’ as an
electrically powered furnace designed to
supply low pressure steam or hot water
for space heating application. A low
pressure steam boiler operates at or
below 15 pounds per square inch gauge
(‘‘psig’’) steam pressure; a hot water
boiler operates at or below 160 psig
water pressure and 250 degrees
Fahrenheit (°F) water temperature. 10
CFR 430.2.
DOE defines ‘‘low pressure steam or
hot water boiler’’ as an electric, gas or
oil burning furnace designed to supply
low pressure steam or hot water for
space heating application. 10 CFR 430.2.
As with an electric boiler, a low
pressure steam boiler operates at or
below 15 pounds psig steam pressure; a
hot water boiler operates at or below
160 psig water pressure and 250 °F
water temperature. Id.
The scope of the test procedure for
consumer boilers is currently specified
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
in section 1 of appendix N, which
references section 2 of ANSI/ASHRAE
103–1993. In relevant part, section 2 of
ANSI/ASHRAE 103–1993 states that the
industry test standard applies to
boilers 8 with inputs less than 300,000
Btu/h; having gas, oil, or electric input;
and intended for use in residential
applications. Further, ANSI/ASHRAE
103–1993 applies to equipment that
utilizes single-phase electric current or
low-voltage DC current.
DOE is not changing the scope of
products covered by its consumer boiler
test procedure in this final rule. The
following sections discuss specific types
of boilers that DOE addressed in the
March 2022 NOPR with respect to
whether such products are covered by
the scope of DOE’s test procedure.
1. Combination Space/Water Heating
Boilers
Some consumer boilers are capable of
providing both space heating and
domestic hot water heating, and are
often referred to as ‘‘combination’’
boilers. In the March 2022 NOPR, DOE
responded to comments from the
Northwest Energy Efficiency Alliance
(‘‘NEEA’’) and Rheem recommending
that DOE consider developing a separate
test procedure for combination space
and domestic hot water boilers. 87 FR
14622, 14626–14627. While DOE did
not propose a specific definition for
combination space and water heating
boilers in the NOPR, DOE noted that, to
the extent that a combination space and
water heating product meets the
definition of electric boiler or low
pressure steam or hot water boiler, it is
subject to the test procedure at appendix
N and energy conservation standards for
consumer boilers at 10 CFR 430.32(e)(2),
and must be tested and rated
accordingly. 87 FR 14622, 14625–14626.
DOE also stated that it is unaware of any
design characteristics of combination
space and water heating products that
would prevent their testing according to
appendix N. Id.
DOE did not receive any comments in
response to the March 2022 NOPR with
regard to combination space and heating
water boilers. In this final rule, DOE
reiterates its statements presented in the
March 2022 NOPR with respect to
combination boilers. To the extent that
a combination space and water heating
product meets the definition of electric
boiler or low pressure steam or hot
8 ASHRAE 103–1993 defines a boiler as ‘‘a selfcontained fuel-burning or electrically heated
appliance for supplying low pressure steam or hot
water for space heating application.’’ This
definition covers electric boilers and low pressure
steam or hot water boilers as those terms are
defined by DOE at 10 CFR 430.2.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
water boiler, it is subject to the test
procedure at appendix N (or, as of the
effective date of this final rule, appendix
EE) and energy conservation standards
for consumer boilers at 10 CFR
430.32(e)(2), and must be tested and
rated accordingly.
2. Heat Pump Boilers
In the March 2022 NOPR, DOE
discussed comments received in
response to the May 2021 RFI with
regard to hydronic air-to-water and
water-to-water heat pumps. DOE
tentatively determined that air-to-water
and water-to-water heat pumps meet the
definitional criteria to be classified as a
consumer boiler. 87 FR 14622, 14625.
DOE noted that these products utilize
only single-phase electric current, are
designed to be the principal heating
source for the living space of a
residence, are not contained within the
same cabinet with a central air
conditioner whose rated cooling
capacity is above 65,000 Btu/h, meet the
definition of an electric boiler,9 and
have a heat input rate of less than
300,000 Btu/h (i.e., the requirement for
electric boilers). As such, they meet the
criteria of ‘‘furnace’’ as defined in 10
CFR 430.2. Id. at 87 FR 14625–14626.
In the March 2022 NOPR, DOE also
tentatively determined that the test
procedure in appendix N does not
address such products and would not
provide a rated value that is
representative of the performance of
these products. Id. at 14626. In
particular, DOE noted that the AFUE
metric for electric boilers in ANSI/
ASHRAE 103–1993 is calculated as 100
percent minus jacket loss,10 which
provides a representative measure of
efficiency for electric boilers using
electric resistance technology, for which
an efficiency value of 100 percent (the
ratio of heat output to energy input) is
the maximum upper limit that
technically could be achieved. DOE
tentatively concluded that the AFUE
metric would not provide a
representative or meaningful measure of
efficiency for a boiler with a heat pump
supplying the heat input, because heat
pump efficiency (in terms of heat output
to energy input) typically exceeds 100
percent, and the AFUE metric does not
9 ‘‘Electric boiler’’ means an electrically powered
furnace designed to supply low pressure steam or
hot water for space heating application. A low
pressure steam boiler operates at or below 15 psig
steam pressure; a hot water boiler operates at or
below 160 psig water pressure and 250 °F water
temperature. 10 CFR 430.2.
10 The term ‘‘jacket loss’’ is used by industry to
mean the transfer of heat from the outer surface (i.e.,
jacket) of a boiler to the ambient air surrounding the
boiler.
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
15515
allow for ratings greater than 100
percent for electric boilers. Id.
Based on these considerations, DOE
tentatively determined that hydronic
air-to-water and water-to-water heat
pumps are consumer boilers under
EPCA, but that due to the lack of a
Federal test procedure, such products
are not subject to the current
performance standards at 10 CFR
430.32(e). Id.
In response to the March 2022 NOPR,
Crown and U.S. Boiler 11 stated that
hydronic heat pumps should not be
classified as boilers under EPCA
because hydronic heat pumps cannot
deliver water at the same temperatures
and heating capacities as traditional
boilers. Crown and U.S. Boiler further
commented that it is unclear whether
hydronic heat pumps are ‘‘designed to
be the principal heating source for a
living space of a residence’’ (a
requirement to meet the definition of a
furnace at 10 CFR 430.2) because these
products are mostly incapable of
reaching above 150 °F on a design day,
whereas traditional boilers are designed
to deliver water at a temperature of
180 °F or higher. Crown and U.S. Boiler
also stated that gas, oil, and electric
resistance boilers are capable of heating
any hot water or steam heating system
throughout the entire heating season,
whereas hydronic heat pumps do not
have such capabilities. Crown and U.S.
Boiler stated that heat pumps and
boilers provide different consumer
utility, and suggested that presenting
heat pumps to consumers as ‘‘boilers’’
could create confusion with regard to
the different capabilities of each.
(Crown, No. 16 at p. 1–2; -U.S. Boiler,
No. 17 at p. 1–2)
AHRI and AGA and APGA
commented that hydronic heat pumps
cannot currently provide the same
functionality as boilers for high
temperature installations as they are
unable to provide water at or over
210 °F, and that this lack of utility
should disqualify these products from
being considered in the boiler test
procedure. (AHRI, No. 26 at p. 2; AGA
and APGA, No. 25 at p. 2)
BWC disagreed with DOE’s tentative
determination that air-to-water and
water-to-water heat pumps should be
defined as consumer boilers. BWC
stated that heat pump products and
consumer boilers have pronounced
differences that should prevent them
from being defined as the same product.
11 DOE notes that both Crown and U.S. Boiler’s
comments stated that the companies are
subsidiaries of Burnham Holdings, Inc. (‘‘BHI’’).
The comments submitted by Crown and U.S. Boiler
in response to the March 2022 NOPR were identical
in content.
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
15516
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
BWC noted that boilers and heat
pumps 12 are already separate product
categories on DOE’s website and
certified separately through DOE’s
Compliance Certification Management
System. BWC also stated that hydronic
heat pumps are rated to Coefficient of
Performance (‘‘COP’’) rather than AFUE
(for boilers), and that the unique
technologies utilized by both product
types necessitate different methods for
testing and rating them. BWC further
stated that consumer boilers are
designed exclusively to provide a
heating utility, whereas hydronic heat
pumps can be used to provide both
space heating and cooling. (BWC, No. 19
at p. 2–3)
Rheem supported DOE’s tentative
determination that hydronic air-to-water
and water-to-water heat pumps are
consumer boilers under EPCA. Rheem
stated that although these products may
not necessarily be able to achieve the
same maximum temperatures as
conventional boilers (without electric
resistance or gas backup), hydronic heat
pump boilers can still provide adequate
space heating in many applications.
Rheem recommended that DOE either
add procedures to test hydronic heat
pumps in this consumer boiler test
procedure rulemaking or initiate a
separate test procedure rulemaking.
Rheem asserted that these products
perform the same function as other
types of boilers and should be tested
and rated in a similar manner, and that
DOE could use the current AFUE test
procedure as a guide to produce an
‘‘AFUE metric’’ for hydronic heat
pumps that combines the various energy
use modes and input rate conditions
with test conditions and operating
assumptions that are representative of
hydronic heat pumps. Rheem stated that
any differences in ability to meet
consumer heating demands should be
considered in the development of
energy conservation standards, as
opposed to the test procedure. (Rheem,
No. 18 at p. 2)
NYSERDA agreed with DOE’s
tentative determination that air-to-water
and water-to-water heat pumps should
be considered boilers under EPCA.
NYSERDA recommended that DOE
develop a test procedure for these heat
pumps and combination space heating
and water heating products. NYSERDA
asserted that the adoption of these test
procedures will also enable future
standards revisions to adopt more
efficient heat pump levels of
performance. (NYSERDA, No. 23 at p.
5–6)
12 DOE understands BWC is referring to central
air conditioning and heat pump units.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
In consideration of the comments
received on this issue, as well as further
consideration of the discussion
presented in the March 2022 NOPR,
DOE has concluded that hydronic air-towater and water-to-water heat pumps
meet the definitional criteria to be
classified as a consumer boiler. In
particular, as noted initially in the
March 2022 NOPR, DOE concludes that
these products utilize only single-phase
electric current, are designed to be the
principal heating source for the living
space of a residence, and are not
contained within the same cabinet with
a central air conditioner whose rated
cooling capacity is above 65,000 Btu/h.
In addition, electric heat pump boilers
meet the definition of an electric boiler;
and gas-fired heat pump boilers meet
the definition of a low pressure steam or
hot water boiler and have a heat input
rate of less than 300,000 Btu/h (i.e., the
requirement for electric boilers and low
pressure steam or hot water boilers). As
such, these products meet the criteria of
‘‘furnace’’ as defined in 10 CFR 430.2.
With respect to comments from
Crown, U.S. Boiler, AHRI, and AGA and
APGA suggesting hydronic air-to-water
heat pumps and water-to-water heat
pumps should be excluded from the
definition because they cannot provide
the same maximum water temperature
as non-heat pump hydronic systems,
DOE notes that neither EPCA nor DOE’s
definitions at 10 CFR 430.2 provide a
minimum water temperature
requirement. In addition, in response to
comments that hydronic heat pumps
serve different applications than boilers,
DOE notes that hydronic heat pumps are
marketed as providing the principal
heating source for a residence, and
nothing in EPCA’s or DOE’s definition
would exclude them based on their
ability to also provide cooling.
DOE recognizes that hydronic heat
pump products differ significantly from
non-heat pump boilers, and that the
current test procedure for consumer
boilers (as well as the amended test
procedure established by this final rule)
would not provide test results that are
representative of the energy use or
energy efficiency of an air-to-water or
water-to-water heat pump product.
Because of these differences and
uncertainty regarding the most
representative approach to testing these
products, DOE is not establishing
separate test procedures for hydronic
heat pump products in this final rule.
Although air-to-water and water-towater heat pump products meet all the
definitional criteria to be considered a
consumer boiler, the Department
requires more information in order to
determine a representative approach for
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
testing these products. Further
consideration of an appropriate test
procedure for such products would be
provided in a separate test procedure
rulemaking. Section III.C of this
document further discusses the
applicability of the AFUE metric to
hydronic heat pump products.
B. Definitions
In addition to the overarching
definition of ‘‘furnace’’ (which includes
boilers) and the associated definitions
for ‘‘electric boiler’’ and ‘‘low pressure
steam or hot water boiler’’ presented in
section III.A of this document, DOE also
has defined ‘‘outdoor boilers’’ and
‘‘weatherized warm air boilers’’ at 10
CFR 430.2 as follows:
• ‘‘Outdoor furnace or boiler’’ is a
furnace or boiler normally intended for
installation out-of-doors or in an
unheated space (such as an attic or a
crawl space).
• ‘‘Weatherized warm air furnace or
boiler’’ means a furnace or boiler
designed for installation outdoors,
approved for resistance to wind, rain,
and snow, and supplied with its own
venting system.
In the March 2022 NOPR, DOE
proposed to remove the definition of
‘‘outdoor furnace or boiler’’ from its
regulations, noting that the definition is
not used for the energy conservation
standards for boilers at 10 CFR
430.32(e)(2)(iii), nor for applying the
test procedure.13 87 FR 14622, 14626–
14627. DOE sought comment on its
proposal to remove the definition of
‘‘outdoor furnace or boiler’’ from its
regulations and whether removing the
definition for ‘‘outdoor furnace or
boiler’’ would impact the application of
the test procedure or energy
conservation standards for any such
products.
Rheem and BWC supported DOE’s
proposal to remove the definition of
‘‘outdoor furnace or boiler’’ from 10 CFR
430.2. (Rheem, No. 18 at p. 2; BWC, No.
19 at p. 1) A.O. Smith stated that
removal of this definition from the DOE
regulations would not have a negative
impact on the application of the test
procedure or energy conservation
standards. (A.O. Smith, No. 24 at p. 2)
AHRI and AGA and APGA also
supported removing the definition and
13 Specifically, with respect to the test procedure,
DOE noted that different jacket loss factors are
applied based on whether a boiler is intended to be
installed indoors, outdoors, or as an isolated
combustion system. The heating seasonal efficiency
(EffyHS) calculation, which is an element of AFUE,
is based on the assumption that all weatherized
boilers are located outdoors (see section 10.1 of
appendix N). Appendix N does not specify a
separate jacket loss assumption for outdoor furnaces
or boilers.
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
stated that the removal would add
clarity and consistency to the test
procedure. (AHRI, No. 26 at p. 2; AGA
and APGA, No. 25 at p. 2)
For the reasons discussed in the
March 2022 NOPR, and in consideration
of these comments, in this final rule
DOE finalizes its proposal to remove the
definition of ‘‘outdoor furnace or boiler’’
from 10 CFR 430.2.
In the March 2022 NOPR, DOE
proposed to incorporate by reference
ANSI/ASHRAE 103–2017, including the
definitions included therein. 87 FR
14622, 14627. DOE noted that ANSI/
ASHRAE 103–2017 includes definitions
for ‘‘air intake terminal,’’ ‘‘control,’’ and
‘‘isolated combustion system’’ that are
not in ANSI/ASHRAE 103–1993. Id. The
definitions for ‘‘control’’ and ‘‘isolated
combustion system’’ in ANSI/ASHRAE
103–2017 are almost identical to the
definitions for those terms currently
defined in sections 2.3 and 2.7 of
appendix N, respectively. Therefore,
DOE proposed to remove the definitions
for ‘‘control’’ and ‘‘isolated combustion
system’’ from DOE’s consumer boiler
test procedure, as they would be
redundant with the definitions
incorporated by reference through
ANSI/ASHRAE 103–2017, if the
proposal to incorporate by reference
ANSI/ASHRAE 103–2017 were
finalized. Id.
Rheem, The CA IOUs, A.O. Smith,
AHRI, and AGA and APGA supported
incorporating by reference the
definitions in ANSI/ASHRAE 103–2017
and removing the separate definitions
for ‘‘control’’ and ‘‘isolated combustions
system’’ from DOE’s test procedure.
(Rheem, No. 18 at p. 3; CA IOUs, No. 20
at p. 1; A.O. Smith, No. 24 at p. 3; AHRI,
No. 26 at p. 2; AGA and APGA, No. 25
at p. 2)
For the reasons discussed in the
March 2022 NOPR, and in consideration
of these comments, DOE is removing the
separate definitions for ‘‘control’’ and
‘‘isolated combustion system’’ from the
consumer boiler test procedure, as
proposed in the March 2022 NOPR. The
definitions for these products are
instead provided through DOE’s
incorporation by reference of ANSI/
ASHRAE 103–2017, as discussed further
in section III.D.1 of this final rule.
In response to the March 2022 NOPR,
Busse suggested that DOE add a
definition for ‘‘standard cubic unit of
gas’’ as follows:
‘‘Standard cubic foot of gas: The
amount of gas that would occupy 1
cubic foot when at a temperature of
60 °F, if saturated with water vapor, and
under a pressure equivalent to that of 30
inches mercury column.’’ (Busse, No. 22
at p. 9)
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
Busse stated that a definition of
standard cubic foot of gas is necessary
to comply with the conditions specified
in section 7.1 of appendix N, Fuel
Supply.14 Busse further stated that the
suggested definition would be
consistent with industry standards
NFPA 54/ANSI Z223.1, National Fuel
Gas Code, and CSA 4.9/ANSI Z21.13,
Gas-Fired Low Pressure Steam and Hot
Water Boilers and asserted that
manufacturers are familiar with this
definition when conducting
performance testing. Busse noted that
the difference between a saturated
‘‘wet’’ and unsaturated ‘‘dry’’ cubic foot
of gas is 1.73 percent at standard
temperature and pressure. Busse also
recommended that DOE modify the
language of section 7.3 of appendix N,
Gas Burner, to replace ‘‘gas
characteristics at a temperature of 60 °F
and atmospheric pressure of 30 in of
Hg’’ with reference to this new
definition, i.e., ‘‘gas characteristics to
standard cubic foot of gas, as defined in
section 2 of this appendix,’’ in
specifying the conditions needed to
correct the burner input rate.15 (Busse,
No. 22 at p. 9–10)
In response, DOE notes that as
proposed in the March 2022 NOPR,
section 7.3 of appendix EE would
require that the burner input rate be
corrected to reflect gas characteristics at
a temperature of 60 °F and atmospheric
pressure of 30 in of Hg when adjusting
the burner input rate. Therefore, an
additional definition for a standard
cubic foot of gas for the purpose of
referencing it in sections 7.1 and 7.3
(which is consistent with the language
in section 9.1.2.2.1 of both ANSI/
ASHRAE 103–1993 and ANSI/ASHRAE
103–2017) would be unnecessary;
however, it may be useful for
clarification.
As such, DOE is adding a definition
for a ‘‘standard cubic foot of gas’’ to
section 2 of appendix EE to specify the
temperature and pressure for a standard
cubic foot of gas.
C. Metric
As discussed, the energy conservation
standards for consumer boilers rely on
the AFUE metric. 10 CFR 430.32(e)(2).
For gas-fired and oil-fired boilers, AFUE
accounts for fossil fuel consumption in
active, standby, and off modes, but does
14 Section 7.1 of appendix N requires determining
the actual higher heating value in Btu per standard
cubic foot for the gas to be used in the test within
an error no greater than 1 percent.
15 Busse also commented that, with respect to the
current instruction to ‘‘Correct the burner input rate
to reflect gas characteristics,’’ technically the Ideal
Gas Laws can be applied only to the volume of gas
consumed and the higher heating value, and not to
the burner input rate.
PO 00000
Frm 00009
Fmt 4701
Sfmt 4700
15517
not include electrical energy
consumption. For electric boilers, AFUE
accounts for electrical energy
consumption in active mode. EPCA
defines the term ‘‘annual fuel utilization
efficiency,’’ in part, as the efficiency
descriptor for furnaces and boilers. (42
U.S.C. 6291(20)) In addition, DOE has
established separate metrics and energy
conservation standards for power
consumption during standby mode and
off mode (PW,SB and PW,OFF,
respectively). 10 CFR
430.32(e)(2)(iii)(B).
AFUE is defined by ASHRAE 103
(both the 1993 and 2017 versions) as the
ratio of annual output energy to annual
input energy, which includes any nonheating-season pilot input loss but does
not include electric energy for gas- or
oil-fired furnaces or boilers. For gas- and
oil-fired boilers, the AFUE test generally
consists of steady-state, cool down, and
heat up tests, during which various
measurements are taken (e.g., flue gas
temperature, concentration of CO2 in the
flue gas). (See sections 9.1, 9.5, and 9.6
of both ANSI/ASHRAE 103–1993 and
ANSI/ASHRAE 103–2017.) For
condensing boilers, condensate
collection tests during steady-state and
cyclic operation are also specified. (See
sections 9.2 and 9.8 of both ANSI/
ASHRAE 103–1993 and ANSI/ASHRAE
103–2017.) The test measurements are
used in conjunction with certain
assumptions to calculate the AFUE. (See
section 11 of both ANSI/ASHRAE 103–
1993 and ANSI/ASHRAE 103–2017.)
In the March 2022 NOPR, after
tentatively concluding that hydronic
heat pumps meet the definitional
criteria to be considered a consumer
boiler but that the existing test
procedure does not apply to them, DOE
sought comment on whether any other
industry test methods exist for
determining the heating efficiency of
air-to-water or water-to-water heat
pumps. DOE sought comment
specifically on AHRI 550/590, and
whether it would be appropriate for
adoption as a Federal test procedure for
such products, and if so, whether
modifications could be made to result in
an AFUE rating. 87 FR 14622, 14626.
NYSERDA urged DOE to adopt
appropriate, industry-recognized test
procedures to support informed
consumer choice between electric
resistance and heat pump products.
(NYSERDA, No. 23 at p. 5–6)
BWC stated that it believes DOE has
correctly identified the appropriate test
procedures for both consumer boilers
and hydronic heat pumps at this time,
with those procedures being ASHRAE
103–2017 and AHRI 550/590
respectively. (BWC, No. 19 at p 2–3)
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
15518
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
Rheem identified AHRI 550/590 as an
industry test method to determine
maximum and part-load COP values but
noted this test method would have to be
modified to account for standby mode
and off mode energy use as well as to
produce an AFUE metric. (Rheem, No.
18 at p. 2)
The Joint Advocates stated that while
AHRI 550/590 is appropriate for
evaluating the performance of consumer
air-to-water heat pumps, it is only
applicable for water-to-water heat
pumps with a capacity greater or equal
to 135,000 Btu/h. The Joint Advocates
stated that ASHRAE/ANSI/AHRI/ISO
Standard 13256–2 is more appropriate
for consumer water-to-water heat pumps
and referred to international standards
EN 14511 and EN 14825 as starting
points. The Joint Advocates asserted
that a seasonal performance rating
analogous to AFUE could be established
and encouraged DOE to establish these
procedures in a timely manner so that
consumers have access to efficiency
ratings based on a standardized test
procedure. Finally, the Joint Advocates
stated that based on 2015 Residential
Energy Consumption Survey (‘‘RECS’’)
data, hydronic systems are the main
heating means in 8 percent of U.S.
homes overall and the main heating
means for 28 percent of households in
the Northeastern United States. (Joint
Advocates, No. 21 at p. 1–2)
A.O. Smith stated that ISO Standard
13256–2 would be the most appropriate
test method for water source heat pump
water heaters intended to be used as
consumer hot water boilers, and that
AHRI Standard 550/590 would be the
most appropriate test method for air
source heat pump water heaters
intended to be used as consumer hot
water boilers. Pertaining specifically to
AHRI 550/590, A.O. Smith stated that
the test procedure to measure COP has
fundamental differences than the test
procedure to measure AFUE, and that
there is no means of deriving an AFUE
value from the COP measurement. In
addition, A.O. Smith claimed that if the
limit for consumer heat pump water
‘‘boilers’’ is defined by an input rate of
less than 300,000 Btu/h, then the output
for these products will include products
with heating capacities up to 900,000
Btu/h, which would be outside the
scope of a consumer boiler. A.O. Smith
recommended that DOE review the
referenced performance standards, as
they define the heating capacity based
on the heat moved into the water being
heated, whereas DOE’s definition is
based on the energy being consumed by
the boiler. (A.O. Smith, No. 24 at p. 2)
As stated in section III.A.2 of this
document, DOE has concluded that
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
hydronic heat pumps meet the
definitional criteria to be covered as a
consumer boiler under EPCA’s statutory
definition at 42 U.S.C. 6291(23) and
DOE’s regulatory definition at 10 CFR
430.2. However, DOE is not adopting a
separate test procedure or metric for
hydronic heat pumps in this final rule
because the Department requires more
information in order to determine a
representative approach for testing these
products. DOE will continue to consider
the appropriate metric to assess the
efficiency of such products, and any
proposed test procedure would be
addressed in a separate test procedure
rulemaking in the future.
D. Updates to Industry Standards
The DOE test method for consumer
boilers references several industry
standards, including ANSI/ASHRAE
103 for various testing requirements
pertaining to determination of AFUE,
certain sections of IEC 62301 (Second
Edition) for determining the electrical
standby mode and off mode energy
consumption, and ASTM D2156–09
(Reapproved 2013) for adjusting oil
burners. The following sections discuss
DOE’s amendments pertaining to the
incorporation by reference of these
industry standards.
1. ANSI/ASHRAE 103
As discussed, ANSI/ASHRAE 103–
1993 is referenced throughout appendix
N for various testing requirements
pertaining to determination of the AFUE
of consumer boilers. ANSI/ASHRAE
103–1993 provides procedures for
determining the AFUE of consumer
boilers (and furnaces). As mentioned
previously, ANSI/ASHRAE 103–1993
has been updated multiple times. In the
rulemaking that culminated in the
January 2016 Final Rule, DOE initially
proposed to incorporate by reference the
most recent version of ANSI/ASHRAE
103 available at the time (i.e., ANSI/
ASHRAE 103–2007), but ultimately
declined to adopt the proposal in the
final rule based on concerns about the
impact this change would have on
AFUE ratings of products distributed in
commerce at that time. 81 FR 2628,
2632–2633 (Jan. 15, 2016). DOE stated
that further evaluation was needed to
determine the potential impacts of
ANSI/ASHRAE 103–2007 on the
measured AFUE of boilers. Id. DOE
theorized that ANSI/ASHRAE 103–2007
might better account for the operation of
two-stage and modulating products and
stated that DOE may further investigate
adopting it or a successor test procedure
in the future. Id.
After the January 2016 Final Rule,
ANSI/ASHRAE 103 was again updated
PO 00000
Frm 00010
Fmt 4701
Sfmt 4700
in 2017 (i.e., ANSI/ASHRAE 103–2017).
In the May 2020 RFI, DOE identified
several substantive differences between
ANSI/ASHRAE 103–1993 and ANSI/
ASHRAE 103–2017 that pertain to
consumer boilers and requested further
comment on the differences between
ANSI/ASHRAE 103–1993 and ANSI/
ASHRAE 103–2017. 85 FR 29352,
29355.
In the March 2022 NOPR, DOE
discussed additional differences
between ANSI/ASHRAE 103–1993 and
ANSI/ASHRAE 103–2017 raised by
commenters in response to the May
2020 RFI. 87 FR 14622, 14628–14631.
The differences between the two
versions of the standard are discussed in
detail in sections III.D.1.a through
III.D.1.f of this document. After
considering the differences between the
standards and the potential impact, DOE
proposed to incorporate by reference the
most recent version (at the time) of
ANSI/ASHRAE 103, i.e., ANSI/ASHRAE
103–2017. 87 FR 14622, 14630. DOE
tentatively concluded that the
improvements included in ANSI/
ASHRAE 103–2017 provide a more
representative average use cycle for
consumer boilers, in particular for twostage and modulating boilers, and that
the change would not materially alter
the burden or cost of conducting an
AFUE test. Id. DOE also noted that test
data indicate the update to the 2017
edition of ASHRAE 103 could result in
changes to the measured AFUE of twostage and modulating boilers ranging
from –0.50 percent to 0.23 percent, with
no discernable trend in the direction or
magnitude of change, and that several
commenters indicated incorporating
ANSI/ASHRAE 103–2017 would likely
not impact rated values significantly. 87
FR 14622, 14631. DOE sought further
comment on its proposal to incorporate
by reference ANSI/ASHRAE 103–2017,
the potential impact on ratings and
whether retesting would be required. Id.
Rheem agreed with DOE’s tentative
determination that the proposed
amendments would result in minimal
differences in AFUE ratings but
requested that DOE test a representative
sample of minimally compliant
consumer boilers to determine the
effect. Rheem requested that DOE
provide this test data in the final rule
and assess the impacts on the ongoing
energy conservation standards
rulemaking. Rheem additionally
suggested that DOE could provide an
enforcement policy to state that models
tested and certified prior to the effective
date of the test procedure final rule
would be tested to the current appendix
N test procedure during an enforcement
investigation. (Rheem, No. 18 at p. 3–4)
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
As discussed, DOE’s assessment of the
changes in ANSI/ASHRAE 103–2017,
along with stakeholder comments
provided throughout this rulemaking,
indicate that the only update in the
industry test procedure with the
potential to impact ratings would be the
change in cycle times. This topic is
discussed in detail in section III.D.2.c of
this document. The updated cycle times
pertain to condensing boilers, which
employ heat exchanger technologies
with efficiency performance that
surpasses the current minimum AFUE
requirements for boilers at 10 CFR
430.32(e)(2)(iii). As discussed in section
III.D.2.c of this document, DOE
conducted testing to determine that the
impact on AFUE ratings of this change
would be minimal. Based on this
information, DOE has determined that
the amendments to the consumer boilers
test procedure will not have a
significant or substantive impact on
ratings, nor affect compliance of any
products.
On January 10, 2022, ASHRAE and
ANSI approved a 2022 edition of
ASHRAE 103 (i.e., ‘‘ANSI/ASHRAE
103–2022’’). DOE did not discuss ANSI/
ASHRAE 103–2022 in the March 2022
NOPR, and parties commenting in
response to the March 2022 NOPR did
not indicate that DOE should consider
incorporating by reference ANSI/
ASHRAE 103–2022. A March 4, 2022,
online publication by ANSI states that
ANSI/ASHRAE 103–2022 includes
mostly editorial changes and quality
improvements to test duct and plenum
figure, the system number table, and
figures for the surface heat transfer
coefficient and coefficient of
radiation.16 Given that stakeholders
provided general support for adopting
ANSI/ASHRAE 103–2017, and that the
updates in ANSI/ASHRAE 103–2022 do
not substantively change the industry
test procedure DOE is not considering
ANSI/ASHRAE 103–2022 in this
rulemaking.
The following subsections discuss the
updates in ANSI/ASHRAE 103–2017
with respect to ANSI/ASHRAE 103–
1993.
a. Post-Purge Time
Power vented units, power burner
units, and forced-draft units use a
combustion blower to exhaust the flue
gas during operation. ‘‘Post purge’’ is
defined in both ANSI/ASHRAE 103–
1993 and ANSI/ASHRAE 103–2017 as
‘‘the design that permits the continued
16 Brad Kelechava, ‘‘ANSI/ASHRAE 103–2022:
AFUE Testing of Residential Furnaces and Boilers,’’
The ANSI Blog, March 4, 2022, blog.ansi.org/ansiashrae-103–2022-fuel-efficiency-afue-testing/#gref.
Last accessed October 5, 2022.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
operation of the combustion blower in
a power vented unit, power burner unit,
or forced-draft unit for a period of time
after the main burner is shut off for the
purpose of venting of residential flue
gas in the heat exchanger and the
venting system.’’ For the determination
of off-cycle flue losses, it is necessary to
demarcate when the boiler has entered
its off-cycle after completion of the postpurge period, especially since postpurge periods can last several minutes.
Section 8.7 of appendix N specifies the
timing of flue temperature
measurements during the off-cycle
portion of the test method based on the
length of the post-purge period. Section
8.7 of appendix N generally corresponds
to section 9.5.2.1 of ANSI/ASHRAE
103–1993, except that section 8.7 of
appendix N specifies that when the
post-purge time is less than or equal to
30 seconds, it can be set to 0 and the
cool-down test be conducted as if there
is no post-purge; while section 9.5.2.1 of
ANSI/ASHRAE 103–1993 specifies that
if post-purge time is less than or equal
to 5 seconds, it shall be tested as if there
is no post-purge. Additionally, the
length of the post-purge cycle is used as
one criterion for determining whether
the heat-up and cool-down tests can
optionally be omitted. Section 8.10 of
appendix N generally corresponds to
section 9.10 of ANSI/ASHRAE 103–
1993, and both sections require a postpurge period of less than 5 seconds to
optionally omit the heat-up and cooldown tests.
Section 9.5.2.1 of ANSI/ASHRAE 103
was updated in the 2017 version to
match DOE’s requirement that if the
post-purge period is 30 seconds or less,
it shall be tested as if there is no postpurge. Additionally, in the March 2022
NOPR, DOE identified the post-purge
time threshold being increased to 30
seconds in the criterion for determining
whether the ‘‘Optional Test Procedures
for Conducting Furnaces and Boilers
that have no OFF-Period Flue Loss’’ is
applicable as a change in ANSI/
ASHRAE 103–2017. DOE proposed to
adopt the 30-second threshold in the
newly proposed appendix EE,
consistent with the change to ANSI/
ASHRAE 103–2017. 87 FR 14622,
14628.
BWC stated that it appreciated DOE’s
inclusion of the change in post-purge
time length to 30 seconds. (BWC, No.
19, p. 2–3)
Additionally, in the March 2022
NOPR, DOE proposed minor changes to
the test method for models with postpurge times longer than 3 minutes,
consistent with the updates included in
ANSI/ASHRAE 103–2017. 87 FR 14622,
14631. Specifically, section 9.5.2.1 of
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
15519
ANSI/ASHRAE 103–2017 requires that
for cases where the post-purge period is
greater than 3 minutes, an additional
measurement of the flue gas temperature
during the cool-down test is required at
the midpoint of the post-purge period.
DOE proposed to adopt a harmonizing
change in the newly proposed appendix
EE. 87 FR 14622, 14631 and 14654.
DOE did not receive any comments
regarding this proposal. For the reasons
discussed in the March 2022 NOPR,
DOE is finalizing this amendment to
section 8.5(d) of appendix EE.
b. Calculations for Omission of Heat-Up
and Cool-Down Tests
The current test procedure for
consumer boilers allows certain units to
omit the cool-down and heat-up tests.
These include units that have been
determined to have no measurable
airflow through the combustion
chamber and heat exchanger during the
burner off-period and that have minimal
post-purge periods (see section III.D.1.a
of this document for discussion of postpurge time). For these boilers, the offcycle losses are expected to be minimal.
However, off-cycle losses (typically
determined during the cool-down and
heat-up tests) must be accounted for
when determining the heating seasonal
efficiency, EffyHS. Section 8.10 of
appendix N currently states, ‘‘In lieu of
conducting the cool-down and heat-up
tests, the tester may use the losses
determined during the steady-state test
described in section 9.1 of ASHRAE
103–1993 when calculating heating
seasonal efficiency, EffyHS.’’
Accordingly, sections 10.2 and 10.3 of
appendix N provide the appropriate
equations to use when calculating
EffyHS if the cool-down and heat-up
tests are omitted per section 8.10 of
appendix N. These equations are
provided in sections 10.2 and 10.3 of
appendix N because they were not
included in ANSI/ASHRAE 103–1993.
As discussed in the March 2022
NOPR, ANSI/ASHRAE 103–2017 makes
several updates to include these
equations, and the equations in ANSI/
ASHRAE 103–2017 are identical to
those in appendix N. 87 FR 14622,
14629. Due to this harmonizing update,
DOE proposed not to include these
equations in the new appendix EE and
to instead directly reference the relevant
sections in ANSI/ASHRAE 103–2017
(11.3.11.3, 11.5.11.1, and 11.5.11.2). 87
FR 14622, 14631. DOE did not receive
comment on this topic and is finalizing
this amendment as proposed in the
March 2022 NOPR.
E:\FR\FM\13MRR2.SGM
13MRR2
15520
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
c. Cycle Timings
ANSI/ASHRAE 103–2017 includes
calculations, originally included in
ANSI/ASHRAE 103–2007, for
determining the average on-time and
off-time per cycle for two-stage and
modulating boilers, rather than
assigning fixed values as in ANSI/
ASHRAE 103–1993. DOE received
comments in response to the May 2020
RFI generally indicating that these
updated cycle timings are more
representative. DOE referenced test data
from the previous rulemaking to
ascertain the potential impact of this
update and tentatively determined that
the new method would be more
representative and not unduly
burdensome and have minimal impact
on AFUE ratings. 87 FR 14622, 14628.
Therefore, DOE proposed to adopt the
updated cycle times via adoption of the
ASHRAE 103–2017 as the reference
standard in the newly proposed
appendix EE. 87 FR 14622, 14630.
In addition, DOE discussed that data
collected for the January 2016 Final
Rule 17 for three models of condensing,
modulating boilers showed that the
changes in on-cycle and off-cycle times
resulted in changes in AFUE of 0.11,
¥0.50, and 0.22 percent, respectively.
For two models of non-condensing,
modulating boilers, calculating the
AFUE based on the on-cycle and offcycle times in ANSI/ASHRAE 103–2007
changed the AFUE by 0.11 and ¥0.14
percent, respectively. 87 FR 14622,
14630.
In response to the March 2022 NOPR,
BWC stated that it agreed with DOE’s
conclusion that the new average use
cycle calculations from ANSI/ASHRAE
103–2017 are more representative for
modulating boilers and have little
impact on efficiency ratings. (BWC, No.
19 at p. 4) The CA IOUs stated the
ANSI/ASHRAE 103–2017 on/off time
per cycle more accurately represents the
typical operation for two-stage,
modulating, and condensing boiler
technologies. (CA IOUs, No. 20 at p. 1)
AHRI requested that DOE provide
more data regarding the impacts of cycle
timing on condensing models. (AHRI,
No. 26 at p. 3)
In response to this request, DOE has
conducted testing on two additional
modulating condensing boilers to
investigate the impact of the revised
cycle timings on AFUE. Data collected
from this testing is shown in Table III.1.
For this investigation, DOE used the
updated steady-state efficiency
calculation method discussed in section
III.E of this final rule for both the ANSI/
ASHRAE 103–1993 and ANSI/ASHRAE
103–2017 results such that the only
variable influencing differences in
AFUE ratings would be the cycle
timings.
TABLE III.1—IMPACT OF CYCLE TIMINGS ON AFUE FOR MODULATING CONDENSING BOILERS
ddrumheller on DSK120RN23PROD with RULES2
ANSI/ASHRAE 103–1993
Model
Cycle timings
(mm:ss)
Unit No. 1 ...........
Unit No. 2 ...........
15:00 on/15:00 off ..........................
15:00 on/15:00 off ..........................
ANSI/ASHRAE 103–2017
AFUE
(percent)
90.98
91.61
Cycle timings
(mm:ss)
23:10 on/11:05 off ..........................
20:29 on/11:50 off ..........................
As indicated in Table III.1, the change
in cycle timings resulted in insignificant
changes to the AFUE values (+0.45
percent and ¥0.15 percent). These
additional sample points are consistent
with DOE’s tentative determination that
impacts to AFUE would be minimal as
a result of the updated cycle timings in
ANSI/ASHRAE 103–2017. Therefore,
manufacturers would not be required to
retest and rerate consumer boilers due
to this change. Based on the discussion
provided in the March 2022 NOPR,
consideration of comments from
interested parties, and this additional
test data, DOE has determined that the
updated approach in ANSI/ASHRAE
103–2017 increases the
representativeness of the test procedure
without being unduly burdensome.
During its testing of these two boilers,
DOE recognized that the determination
of cycle timings in Table 7 of ANSI/
ASHRAE 103–2017 does not specify the
precision to which these timings (tON
and tOFF) should be calculated (i.e., to
the nearest minute or second). ANSI/
ASHRAE 103–2017 provides no
indication of whether these cycle
timings can or should be rounded.
Acknowledging that many testing
facilities may only be able to time the
burner cycling operation of the boiler
under test to the nearest second, DOE is
providing additional specification in
appendix EE to require that calculated
cycle timings shall be rounded to the
nearest second. This clarification is not
expected to impact results significantly
but serves to improve repeatability and
reproducibility of test results by
clarifying the duration of the cycle time.
17 These data were presented at a public meeting
for the March 11, 2015, NOPR pertaining to test
procedures for furnaces and boilers and can be
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
d. Oversize Factor
The oversize factor for a boiler
indicates the ratio between the boiler’s
nominal capacity and the home’s
heating load. This factor is represented
by the symbol ‘‘a’’ and is determined in
sections 11.2.8.3 and 11.4.8.3 of ANSI/
ASHRAE 103–1993 and sections
11.2.8.2 and 11.4.8.2 of ANSI/ASHRAE
103–2017.
ANSI/ASHRAE 103–2017 updates the
method for calculating the oversize
factor. While the oversize factor was
calculated from a lookup table based on
design heating requirement (‘‘DHR’’) in
ANSI/ASHRAE 103–1993, ANSI/
ASHRAE 103–2017 assigns a constant
value of 0.70 to a to represent the
PO 00000
Frm 00012
Fmt 4701
AFUE
(percent)
Sfmt 4700
91.43
91.46
Change in
AFUE
(percent)
+0.45
¥0.15
national average oversize factor. Based
on DOE’s assessment of its test data,
DOE stated in the March 2022 NOPR
that this change would be unlikely to
have a substantive impact on AFUE
ratings because the calculations are not
particularly sensitive to changes in the
oversize factor value. Specifically, DOE
reviewed test data for three modulating,
condensing boilers and found that the
change in oversize factor from a
calculated value, as specified in ANSI/
ASHRAE 103–1993, to 0.7 changed the
AFUE rating by 0.01 AFUE percentage
points or less for all 3 models. 87 FR
14622, 14629. In the March 2022 NOPR,
DOE proposed to adopt the constant 0.7
oversize factor through incorporation by
reference of ANSI/ASHRAE 103–2017.
Id.
BWC supported DOE’s proposal to
adopt the constant 0.7 oversize factor
through incorporation of ANSI/
ASHRAE 103–2017. BWC’s analysis of
this proposal demonstrated that
adopting this approach would not have
a significant impact on overall product
efficiency. (BWC, No. 19 at p. 3)
Busse stated that the oversize factor
should be a constant value less than 0.4
found at www.regulations.gov/document/EERE2012-BT-TP-0024-0021.
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
based on an Air Conditioning
Contractors of America (‘‘ACCA’’)
equipment selection checklist 18
indicating to installers that the selected
equipment should be less than or equal
to 140 percent of the designed total
heating load. Busse commented that in
the last 40 years, it has become apparent
that oversized equipment is less
efficient, such that a more appropriate
oversize factor of approximately 0.35 is
justified. (Busse, No. 22 at p. 6–7)
In response, DOE notes that
commenters did not provide field
statistics that would help to determine
what a national average representative
oversize factor would be, nor is DOE
aware of any such data. While
contractors may be oversizing boilers to
a lesser degree today than in the past,
DOE expects that many replacements
will be made on a like-for-like basis
such that the input capacity of the
replacement boiler will match that of
the previous boiler (and thus maintain
the same oversize factor as the previous
boiler). Without sufficient nationally
representative data to support deviation
from the industry-accepted oversize
factor specified in ANSI/ASHRAE 103–
2017, DOE is adopting the provision to
use a constant oversize factor of 0.70
through incorporation by reference of
ANSI/ASHRAE 103–2017. In addition,
as discussed previously in this
document and initially discussed in the
March 2022 NOPR, based on a review of
its test data DOE has determined that
this change would not substantively
impact on AFUE.
ddrumheller on DSK120RN23PROD with RULES2
e. Annual Performance Metrics
ANSI/ASHRAE 103–2017 changes the
method for determining national
average burner operating hours
(‘‘BOH’’), average annual fuel energy
consumption (‘‘EF’’), and average annual
auxiliary electrical energy consumption
(‘‘EAE’’),19 especially for two-stage and
modulating products, based on a 2002
study from NIST.
The CA IOUs stated that ASHRAE
103–2017 utilizes differentiating
calculations for annual operating hours
and reduced fuel input rates that reflect
real-world operation conditions of
boilers that more accurately represents
the typical operation for two-stage,
modulating, and condensing boilers that
spend a significant amount of time
18 ACCA ‘‘Verifying ACCA Manual S®
Procedures’’ brochure, www.acca.org/HigherLogic/
System/DownloadDocumentFile.ashx?
DocumentFileKey=2f0a6828-2205-e112-745f7215c9a85541&forceDialog=0. Last accessed
October 7, 2022.
19 A typographical correction to the
determination of EAE at 10 CFR 430.23(n) is
discussed in section III.F.5 of this final rule.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
operating at part-load conditions. (CA
IOUs, No. 20 at p. 1)
These additional annual performance
metrics are not required for
representations or certifications to DOE
at this time. Federal Trade Commission
product labeling requirements at 16 CFR
305.8 specify that determinations of
estimated annual energy consumption,
estimated annual operating cost, and
energy efficiency rating must be
determined in accordance with the
testing and sampling provisions
required by DOE as set forth in subpart
B of 10 CFR part 430. For boilers, the
product labeling provisions are
specified at 16 CFR 305.20(f) and
currently only require AFUE to be
presented. Thus, manufacturers are not
required to report BOH, EF, or EAE for
consumer boilers as of this final rule.
However, manufacturers may
voluntarily represent these values. To
ensure that any voluntary
representations of these values are
conducted in accordance with the DOE
test procedure, DOE is adopting the
revised calculation methods in ANSI/
ASHRAE 103–2017 for BOH, EF, and
EAE.
f. Measurement of Relative Humidity
The current DOE test procedure at
appendix N, through incorporation by
reference of ANSI/ASHRAE 103–1993,
specifies limitations on the relative
humidity of the ambient air of the test
chamber when testing a condensing
boiler. Sections 9.2 and 9.8.1 of ANSI/
ASHRAE 103–1993 state, ‘‘The
humidity of the room air shall at no
time exceed 80 percent’’ but do not
provide instruction on the
instrumentation necessary to measure
the relative humidity. ANSI/ASHRAE
103–2017 provides new requirements in
section 8.5.1 to follow ANSI/ASHRAE
41.6–2014 in order to measure relative
humidity for testing condensing boilers.
Because the DOE test method and ANSI/
ASHRAE 103–1993 currently limit
relative humidity allowed during
testing, DOE reasoned in the March
2022 NOPR that relative humidity
already must be measured under the
current procedure; thus, DOE tentatively
concluded that the method prescribed
by ANSI/ASHRAE 103–2017 would
likely be similar to current practices and
requested comment on this topic. 87 FR
14622, 14636–14637.
Busse suggested that DOE should
verify that ANSI/ASHRAE 41.6–2014
includes precision and calibration
requirements. (Busse, No. 22 at p. 9–10)
DOE has reviewed ANSI/ASHRAE 41.6–
2014 in detail and notes that it provides
setup and calibration methods for both
psychrometers and hygrometers (two
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
15521
types of instruments which can be used
to measure relative humidity). Section 6
of ANSI/ASHRAE 41.6–2014 provides
calibration requirements, and sections 7
and 8 of ANSI/ASHRAE 41.6–2014
provide measurement methods,
precision requirements, and
measurement uncertainty analysis.
As discussed further in section III.K of
this document, DOE received comments
indicating that introducing these new
requirements for measurement and
instrumentation would not be unduly
burdensome to industry. In this final
rule, DOE is incorporating by reference
ANSI/ASHRAE 41.6–2014 in appendix
EE for the purpose of performing the
required humidity measurement.
2. IEC 62301 and ASTM D2156–09
DOE noted in the May 2020 RFI that
the version of IEC 62301 currently
incorporated by reference in appendix N
is still the most recent version, and the
most recent iteration of ASTM D2156–
09 is a version reapproved in 2018 that
did not contain any changes from the
2009 version. 85 FR 29352, 29355. DOE
did not receive any comments
pertaining to its incorporation by
reference of IEC 62301 or ASTM D2156–
09 and in the March 2022 NOPR
proposed to maintain the current
reference to IEC 62301, and to update
the reference to ASTM D2156–09 to
reflect the version that was reapproved
in 2018. 87 FR 14622, 14628. DOE did
not receive any comments related to its
incorporation by reference of these
standards. In this final rule, DOE is
finalizing their adoption for appendix
EE as proposed.
E. Steady-State Efficiency for
Condensing Modulating Boilers
In the May 2020 RFI and the March
2022 NOPR, DOE discussed that ANSI/
ASHRAE 103–1993 and ANSI/ASHRAE
103–2017 yield a circular reference
when calculating the steady-state
efficiency for condensing modulating
boilers. 85 FR 29352, 29357; 87 FR
14622, 14629.
As discussed in the March 2022
NOPR, the circular reference arises
within the calculation of steady-state
efficiencies at maximum and minimum
input rate, which depends in part on the
steady-state heat loss due to condensate
going down the drain at the maximum
and reduced input rates. (See section
11.5.7.3 of ANSI/ASHRAE 103–2017,
which refers to section 11.3.7.3.) The
steady-state heat loss due to condensate
going down the drain at the maximum
and minimum input rates is calculated
in part based on the national average
outdoor air temperature at the
maximum and minimum input rates.
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
(See section 11.5.7.2 of ANSI/ASHRAE
103–2017, which refers to section
11.3.7.2.) The national average outdoor
air temperatures at the maximum and
minimum input rates are both a
function of the balance point
temperature. (See section 11.5.8.3 of
ANSI/ASHRAE 103–2017, which refers
to section 11.4.8.3.) The balance point
temperature is calculated based on the
oversize factor at maximum input rate
(which is, as discussed previously, a
constant value in ANSI/ASHRAE 103–
2017) and the ratio of the heating
capacity at the minimum input rate to
the heating capacity at the maximum
input rate. (See section 11.5.8.4 of
ANSI/ASHRAE 103–2017, which
references section 11.4.8.4.) The heating
capacities at the minimum and
maximum input rates are calculated
based in part on the steady-state
efficiencies at minimum and maximum
input rates, respectively. (See section
11.5.8.1 of ANSI/ASHRAE 103–2017,
which references section 11.4.8.1.) If the
calculations were interpreted to refer
back to the steady-state efficiencies at
minimum and maximum input rates for
a modulating, condensing model, as
determined by section 11.5.7.2 of ANSI/
ASHRAE 103–2017, a circular reference
would result.
However, since there is no specific
instruction to use the values as
calculated by section 11.5.7.2, DOE
stated in the March 2022 NOPR that it
interprets ANSI/ASHRAE 103–2017 to
instruct that the steady-state efficiency
at maximum and reduced input rates be
determined as specified in section
11.4.8.1, which refers to section 11.4.7,
which in turn refers to section 11.2.7 for
the calculation of steady-state efficiency
for non-condensing, non-modulating
boilers. 87 FR 14622, 14629. The steadystate efficiencies at maximum and
minimum input calculated using section
11.2.7 can then be used to obtain values
for output capacities at the maximum
and reduced input, which are needed to
calculate the balance point temperature,
the average outdoor air temperature at
maximum and minimum input, and
finally the heat loss due to condensate
going down the drain at maximum and
minimum input rates. Id.
In the March 2022 NOPR, DOE
proposed to add provisions to clarify the
approach for calculating steady-state
efficiencies at maximum and minimum
input rates for condensing, modulating
boilers using ANSI/ASHRAE 103–2017.
87 FR 14622, 14629. Specifically, DOE
proposed to codify provisions in section
10.1.2 of appendix EE to explain how to
calculate these values without a circular
reference, ultimately by referring back to
section 11.2.7 of ANSI/ASHRAE 103–
2017. 87 FR 14622, 14655.
Crown, U.S. Boiler, BWC, Rheem,
A.O. Smith, AHRI, and AGA & APGA all
supported DOE’s proposal to provide
additional specification that would
avoid a circular reference in the test
procedure. (A.O. Smith, No. 24 at p. 3;
AGA & APGA, No. 25 at p. 2) Rheem
recommended that each subsection in
section 10.1.2 of appendix EE should
not say ‘‘previous step’’ but should refer
to the appropriate subsection.
Specifically, Rheem recommended that
DOE present an equation for balance
point temperature, TC, in which the
variables used in the equation reference
the relevant sections in ANSI/ASHRAE
103–2017. (Rheem, No. 18 at p. 3)
Crown, U.S. Boiler, BWC, and AHRI all
recommended the same revision for
section 10.1.2 to improve the clarity of
the section. (Crown, No. 16 at p. 3; U.S.
Boiler, No. 17 at p. 2–3; BWC, No. 19
at p. 3; AHRI, No. 26 at p. 2–3)
Specifically, the commenters
recommended revising section 10.1.2 to
replace the output capacity parameters
QOUT,R and QOUT as follows:
10.1.2 Calculate the balance point
temperature (TC) for condensing,
modulating boilers by using the
following equation in place of that
referenced by 11.5.8.4 [of ANSI/
ASHRAE 103–2017]:
Where:
TSH = typical average outdoor temperature at
which a boiler starts operating, 65 °F
TOA,T = the typical outdoor design
temperature, 5 °F
a = oversize factor, as defined in 11.4.8.2 [of
ANSI/ASHRAE 103–2017]
QIN = steady-state nameplate maximum fuel
input rate
QIN,R = steady-state reduced input fuel input
rate
LS,SSR = average sensible heat loss at steady
state, reduced input operation
LS,SS = average sensible heat loss at steady
state, maximum input operation
2017) to calculate TC, the suggested
equation simply inserts the appropriate
variables directly into the equation for
TC, providing the same result. DOE is
therefore adopting this revised equation
in section 10.1.3 of appendix EE.
in ANSI/ASHRAE 103–2007, but
inadvertently copied the equation for
LS,OFF1 to LI,OFF1 for units having postpurge times below 3 minutes, and this
error was not corrected in the 2017
edition. (Crown, No. 16 at p. 3; U.S.
Boiler, No. 17 at p. 3) Similarly, Rheem
identified this issue involving the factor
of 60 in the equations for LS,OFF1 and
LI,OFF1 and asked DOE to evaluate the
impact on ratings. (Rheem, No. 18, p. 6)
DOE has examined the equations for
LS,OFF1 and LI,OFF1 in ANSI/ASHRAE
103–2017 and understands that the
factor of 60 is used to convert the cycle
times (reported in minutes) into hours
because the input rate is expressed in
terms of Btu/h. Thus, the cycle times
must be divided by 60 to convert these
values into hours. Section 11.2.10.6 of
ANSI/ASHRAE 103–2017 performs this
operation correctly for determining
LS,OFF1, but the factor of 60 is used
incorrectly in sections 11.2.10.6 and
11.2.10.8 of ANSI/ASHRAE 103–1993.
As Crown and U.S. Boiler indicated,
industry has been aware of this error
In reviewing this equation, DOE
agrees that the recommended equation
adequately resolves the circular
reference issue in the same manner as
DOE proposed in the March 2022
NOPR, but with a simplified approach
to specifying the correct calculations for
determining the steady-state efficiency
for condensing modulating boilers.
Rather than determining QOUT and
QOUT,R based on the steady-state
efficiencies EffySS and EffySS,R (using
section 11.2.7 of ANSI/ASHRAE 103–
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
F. Corrections and Clarifications
1. Off-Cycle Losses
In response to the March 2022 NOPR,
several commenters indicated that
ANSI/ASHRAE 103–2017 has a
typographical error in the equations
used to determine LI,OFF1 and LS,OFF1
(off-cycle infiltration and sensible
losses, respectively). Specifically,
Crown and U.S. Boiler stated there is an
error in section 11.2.10.8 of ANSI/
ASHRAE 103–2017 for the calculation
of LI,OFF1. Crown and U.S. Boiler stated
that the equation for LI,OFF1 in ANSI/
ASHRAE 103–1993 was erroneous
because QIN was multiplied by 60 when
it should have been divided by 60.
According to Crown and U.S. Boiler,
ASHRAE attempted to correct this error
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
E:\FR\FM\13MRR2.SGM
13MRR2
ER13MR23.000
ddrumheller on DSK120RN23PROD with RULES2
15522
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
since the development of ANSI/
ASHRAE 103–2007. As such, DOE
expects that current ratings are
determined based on the corrected use
of the factor of 60. In particular, DOE is
aware that the Gas Appliance
Manufacturers Association (GAMA) 20
developed a computer program to
calculate AFUE.21 DOE has reviewed a
version of this program (dated October
15, 2003) and determined this
calculation was corrected in the
underlying code. Based on this finding,
correcting the use of the factor of 60 (by
incorporating by reference ANSI/
ASHRAE 103–2017) should not affect
the ratings of products which have
already been tested and certified.
Furthermore, these calculations apply
only to consumer boilers that have
system numbers 2, 3, or 4 with postpurge times greater than 30 seconds,
which DOE understands to be a
relatively low fraction of the market
based on its own compliance testing.
DOE notes that section 11.2.10.8 of
ANSI/ASHRAE 103–1993 provided the
correct equation for LI,OFF1 for models
with post-purge periods that are less
than or equal to 3 minutes (albeit with
the aforementioned error with the factor
of 60).
The equation for L I,OFF1 for models
with post-purge periods that are greater
than to 3 minutes is corrected in ANSI/
ASHRAE 103–2017 and is adopted in
this final rule through incorporation by
reference.
2. Conversion Factor for British Thermal
Units
In the March 2022 NOPR, DOE noted
inconsistencies in the conversion factors
from watts (W) or kilowatts (kW) to
British thermal units per hour (Btu/h),
in which some sections used a
conversion factor of 3.412 and other
sections use 3.413. 87 FR 14622, 14634.
DOE stated that the conversion factor
between watts and Btu/h is generally
accepted to be 1 watt = 3.412142 Btu/
h (or 1 Btu/h = 0.2930711 watts), as
published in the 2021 ASHRAE
Handbook—Fundamentals.22 Id. This
value is more appropriately rounded to
3.412 W/(Btu/h); therefore, DOE
proposed correcting the test procedures
to use 3.412 W/(Btu/h) in all
calculations where 3.413 W/(Btu/h) was
previously used. Id. DOE stated in the
March 2022 NOPR that it did not expect
this correction to affect AFUE ratings.
Id.
DOE did not receive comments on
this topic. For the reasons discussed
here and in the March 2022 NOPR, this
final rule implements a conversion
factor of 3.412 in each instance within
new appendix EE. DOE also amends
appendix N—which will remain
applicable to consumer furnaces other
than boilers—to use the corrected
conversion factor.
3. Oil Pressure Instrumentation Error
Section 6.3 of ANSI/ASHRAE 103–
2017 states, ‘‘Instruments for measuring
gas, oil, air, water, and steam pressure
shall be calibrated so that the error is no
15523
greater than the following.’’ However,
the specifications that follow omit the
instrumentation requirements
applicable to measuring oil pressure.
Section 6.3(b) of ANSI/ASHRAE 103–
1993 included the oil pressure
specification.
In response to the March 2022 NOPR,
Rheem commented that DOE should
add the oil pressure instrumentation
specification from ANSI/ASHRAE 103–
1993 to section 5 of the new appendix
EE test procedure. (Rheem, No. 18 at p.
6)
This final rule reinstates the omitted
provisions from section 6.3 of ANSI/
ASHRAE 103–1993 in section 5 of
appendix EE.
4. Gas Inlet Conditions
Section 7.1 of appendix N references
Table 1 of ANSI/ASHRAE 103–1993 for
maintaining the gas supply, ahead of all
controls for a furnace,23 at an acceptable
test pressure. The natural gas inlet
pressure shall be between the ‘‘normal’’
and ‘‘increased’’ values shown in Table
1 of ANSI/ASHRAE 103–1993. Table 1
in ANSI/ASHRAE 103–2017 provides
identical gas inlet pressures to those in
ANSI/ASHRAE 103–1993 (this table is
presented in section 8.2.1.3 of ASHRAE
103–2017, which is excluded from
reference in the current appendix N test
procedure). Table 1 also specifies the
specific gravity of the test gases. The
pressures and specific gravity of the test
gases are reproduced in Table III.2 of
this document.
TABLE III.2—NATURAL GAS INLET PRESSURES AND SPECIFIC GRAVITY OF TEST GASES IN TABLE 1 OF ANSI/ASHRAE
103–1993 AND ANSI/ASHRAE 103–2017
Test pressure
(inches water column)
Type
Normal
ddrumheller on DSK120RN23PROD with RULES2
Natural .........................................................................................................................................
Manufactured ...............................................................................................................................
Butane ..........................................................................................................................................
Propane .......................................................................................................................................
7.0
3.5
11.0
11.0
Increased
10.50
5.25
13.00
13.00
Specific
gravity
(air = 1.0)
.65
.38
2.00
1.53
In response to the March 2022 NOPR,
Crown and U.S. Boiler stated that the
gas inlet pressure requirements in
section 8.2.1.3 of ANSI/ASHRAE 103–
2017 are appropriate and necessary for
units with pilot lights because most
pilots have no pressure regulation
within the appliance itself, and thus the
input rate of the pilot is determined in
large part by the inlet pressure. Crown
and U.S. Boiler noted, however, that
since continuous standing pilots are
prohibited by EPCA on consumer
boilers, such restrictive requirements on
the gas inlet pressure are no longer
necessary in the Federal test procedure
and may place undue burden on test
labs. Crown and U.S. Boiler commented
that maintaining a 7.0 inches water
column (‘‘in. w.c.’’) minimum inlet
pressure is not always possible in some
test labs, nor is it necessary as long as
the regulator outlet pressure can be
maintained, and the nameplate input
20 GAMA and the Air-Conditioning and
Refrigeration Institute (ARI) merged in 2008 to form
AHRI.
21 In the May 2020 RFI, DOE discussed the
industry-developed computer program that
calculates AFUE based on ANSI/ASHRAE 103–
1993 ‘‘AFUE v1.2.’’ This software was most recently
updated in April 2004. 85 FR 29352, 29356.
22 2021 ASHRAE Handbook—Fundamentals (I–P
Edition). Peachtree Corners, GA: American Society
of Heating, Refrigeration and Air-Conditioning
Engineers, 2021. Available at www.ashrae.org/
technical-resources/ashrae-handbook/description2021-ashrae-handbook-fundamentals.
23 This term refers to the broader definition of
‘‘furnace,’’ which includes warm air furnaces and
boilers.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
15524
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
achieved. Crown and U.S. Boiler further
indicated that expensive gas booster
equipment may be necessary to meet the
7.0 in. w.c. minimum. Crown and U.S.
Boiler stated that gas appliances are
generally listed for use up to 14.0 in.
w.c. inlet pressure, so there is also no
reason to reduce this pressure to 10.5 in.
w.c. on a boiler without a continuous
pilot in order to provide results that are
repeatable and representative of what
can be expected in the field. In order to
afford labs greater flexibility while still
preventing boilers from being tested at
gas inlet pressures for which they are
not intended to be used in the field,
Crown and U.S. Boiler suggested
replacing the second sentence of section
8.2.1.3 of ANSI/ASHRAE 103–2017
with: ‘‘The gas supply, ahead of all
controls for a furnace, shall be
maintained at a test pressure within the
upper and lower limits shown in the
manufacturer’s instructions or on the
boiler itself. In the absence of any such
limits, the gas supply pressure shall be
maintained between the normal and
increased values shown in Table 1 of
ANSI/ASHRAE 103–2017.’’ (Crown, No.
16 at p. 2–3; U.S. Boiler, No. 17 at p. 2)
Busse urged DOE to modify the
language in section 7.1 of appendix EE
to include the term ‘‘approximately’’
when referring to meeting the specific
gravity requirements in Table 1 of
ANSI/ASHRAE 103–2017, asserting that
the omission of this term suggests that
DOE expects the specific gravity to be
exactly as shown in Table 1 without
providing instrument requirements for
measuring. (Busse, No. 22 at p. 10)
At 42 U.S.C. 6295(f)(3)(A), EPCA
mandates that gas-fired boilers
manufactured on or after September 1,
2012, must not have a constant burning
pilot. DOE agrees that the test procedure
requirements in appendix N (which
reference Table 1 of ANSI/ASHRAE
103–1993) have a greater contribution to
maintaining the reproducibility and
repeatability of test results for consumer
boilers with constant burning pilots;
however, it is currently unclear to DOE
what the impacts of updating the
natural gas inlet pressure requirements
as suggested would be on measured
efficiency ratings for boilers without
constant burning pilots. Crown and U.S.
Boiler did not provide data to indicate
that their suggested approach of relying
on the manufacturer’s instructions for
setting natural gas inlet pressure will
not significantly impact ratings.
Manufacturers have not previously
expressed concern regarding the ability
to meet the inlet pressure requirements
in appendix N, and no waivers have
been received for consumer boilers that
are not compatible with the inlet
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
pressure provisions. This suggests that
manufacturers and test laboratories have
been able to meet these setup
requirements since compliance with the
currently applicable appendix N test
procedure has been required (July 13,
2016).
For these reasons, DOE has
determined that no correction to the
natural gas inlet pressure requirements
is necessary at this time and is adopting
the reference to Table 1 of ANSI/
ASHRAE 103–2017 in section 7.1 of
appendix EE as proposed in the March
2022 NOPR. Regarding Busse’s
suggestion to include the word
‘‘approximately’’ in reference to the
specific gravity values referenced in
section 7.1, DOE agrees that the specific
gravity may not be exactly as provided
in Table 1 of ANSI/ASHRAE 103–2017
because variations exist due to
differences in gas composition in supply
sources. DOE understands that the
purpose of specifying the gas
characteristics in Table 1 of ANSI/
ASHRAE 103–2017 is to ensure that the
energy content in the gas is consistent
for the repeatability and reproducibility
of the test. DOE notes that explicit
tolerances are provided for the higher
heating value of the gas used, such that
providing explicit tolerances for the
specific gravity of the gas would be
redundant. As such, DOE is adopting
Busse’s suggestion to state that the
specific gravity of the gas should be
‘‘approximately’’ that shown in Table 1
of ANSI/ASHRAE 103–2017.
5. Active Mode Electrical Energy
Consumption
As previously discussed, AFUE does
not include active mode electrical
consumption for gas-fired and oil-fired
boilers. Instead, the DOE test procedure
includes provisions for determining the
average annual auxiliary electrical
energy consumption for gas-fired and
oil-fired boilers (EAE), as a separate
metric from AFUE, that accounts for
active mode, standby mode, and off
mode electrical consumption. (See
appendix N, section 10.4.3.) EAE is
referenced by the calculations at 10 CFR
430.23(n)(1) for determining the
estimated annual operating cost for
furnaces. However, the provisions at 10
CFR 430.23(n) include several incorrect
references to sections in appendix N. In
the March 2022 NOPR, DOE proposed to
correct 10 CFR 430.23(n)(1) to reference
the appropriate sections of appendix N
where the currently codified provisions
point to the wrong sections.
Additionally, DOE proposed to revise 10
CFR 430.23(n)(1) such that sections in
appendix N are referenced for furnaces
and sections in appendix EE are
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
referenced for boilers. 87 FR 14622,
14633, and 14643.
DOE did not receive any comments on
this topic. In this final rule, DOE adopts
these corrections as proposed.
6. Circulator Pumps
Section 8.2 of the proposed appendix
EE from the March 2022 NOPR included
instructions on the electrical energy
consumption measurements for various
boiler components in order to calculate
PE, the electrical power involved in
burner operation. 87 FR 14622, 14654.
It stated that the measurement of PE
must include the boiler pump if so
equipped. Id.
In response to the March 2022 NOPR,
Rheem noted that section 2 of the
proposed appendix EE defines a ‘‘boiler
pump’’ 24 as being separate from the
circulating water pump; however, the
term ‘‘circulating water pump’’ is not
defined in the proposed appendix EE or
ANSI/ASHRAE 103–2017. Rheem
recommended that DOE add a definition
for ‘‘circulating water pump’’ to clarify
the difference between these pumps and
to reduce confusion when performing
the procedure in section 8.2 of appendix
EE, which refers to both pump types.
(Rheem, No. 18 at p. 5–6)
DOE notes that the definition for
‘‘boiler pump’’ was established in the
January 2016 Test Procedure Final Rule.
81 FR 2628, 2647. In the January 2016
Test Procedure Final Rule, in describing
devices that use power during the active
mode, DOE discussed a secondary
pump for boilers (i.e., boiler pump) used
to maintain a minimum flow rate
through the boiler heat exchanger,
which is most typically associated with
condensing boiler designs. Id. at 81 FR
2633. In the preamble to the January
2016 Test Procedure Final Rule, DOE
stated that it would define a boiler
pump as, ‘‘a pump installed on a boiler
that maintains adequate water flow
through the boiler heat exchanger and
that is separate from the circulating
water pump;’’ however, this definition
was not codified with the additional
clarification that the boiler pump
maintains adequate water flow through
the heat exchanger. Id. at 81 FR 2634.
In order to improve the clarity of the
boiler pump definition, DOE is revising
this definition to reflect the language
which was inadvertently omitted from
the January 2016 Test Procedure Final
Rule.
Additionally, section 9.1.2.2 of ANSI/
ASHRAE 103–2017 states that, for hot
water boilers, the circulating water
24 Section 2.2 of appendix N defines a ‘‘boiler
pump’’ as a pump installed on a boiler that is
separate from the circulating water pump.
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
pump nameplate power is to be used to
determine the electrical power to the
circulating water pump (BE), and if the
pump nameplate power is not available,
use the pump power listed in the water
pump manufacturer’s literature or use
0.13 kW. In response to the March 2022
NOPR, Busse suggested that, because
circulator pumps do not have a
‘‘nameplate’’ power value, the water
pump manufacturer’s literature could be
used instead for calculating the value of
BE. Busse also commented that the
default value of 0.13 kW in ANSI/
ASHRAE 103–2017 may not be
appropriate for modern electronically
commutated motor-based circulator
pumps. (Busse, No. 22 at p. 11)
At this time, DOE does not have
sufficient data on circulating water
pumps used with consumer hot water
boilers to specify a more representative
power draw to be used in lieu of
manufacturer-reported information
(either on a nameplate or in the I&O
manual). As ANSI/ASHRAE 103–2017
is currently the industry-accepted test
standard 25 for consumer boilers, DOE
expects that the provisions for circulator
pump power remain representative for
current installations. Additionally, DOE
notes that the value of BE is not a factor
that determines AFUE (see section III.C
for discussion about the AFUE metric).
7. Units With Draft Hoods or Draft
Diverters
Section 6.4 of appendix N provides
installation instructions for units with
draft hoods or draft diverters. Among
other requirements, this section
specifies installing the stack damper in
accordance with the ‘‘I&O manual.’’
In response to the March 2022 NOPR,
Rheem commented that section 6.4 of
appendix N appeared to have been
omitted from the proposed appendix EE.
Rheem noted that these provisions are
still relevant to boilers and should be
carried over into the new appendix EE
test procedure. (Rheem, No. 18 at p. 6)
The March 2022 NOPR proposed in
section 6 (‘‘Apparatus’’) of appendix EE
to reference section 7 of ANSI/ASHRAE
103–2017 (‘‘Apparatus’’) including
sections 7.2.3.1 and 7.3.3.1. Section
7.3.3.1 of ANSI/ASHRAE 103–2017
specifies stack and flue installation
requirements for boilers with draft
hoods or draft diverters by referencing
section 7.2.3.1 of ANSI/ASHRAE 103–
2017. The language in section 7.2.3.1 of
ANSI/ASHRAE 103–2017 is identical to
the provisions in section 6.4 of the
current appendix N, except that section
25 ANSI/ASHRAE 103–2022 does not provide
substantive updates to provisions for circulator
pump power.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
7.2.3.1 specifies that the stack damper
be installed in accordance with the
‘‘manufacturer’s instructions’’ rather
than the ‘‘I&O manual’’ specified in
section 6.4. DOE’s proposal to reference
sections 7.2.3.1 and 7.3.3.1 of ANSI/
ASHRAE 103–2017 through reference to
section 7 in the new appendix EE test
procedure maintained the installation
instructions for units with draft hoods
or draft diverters in appendix EE. This
final rule maintains the reference to
section 7 of ANSI/ASHRAE 103–2017 in
section 6 of appendix EE.
DOE has determined, however, that
maintaining the more specific reference
to the manufacturer’s I&O manual,
rather than a general reference to
manufacturer’s instructions, will ensure
the reproducibility of the test procedure
by providing a more specific reference
to the document that must be consulted
with regard to installing the stack
damper. Therefore, this final rule adds
an exception in section 6 of appendix
EE to specify referencing the I&O
manual in lieu of manufacturer’s
instructions in section 7.2.3.1 of ANSI/
ASHRAE 103–2017.
8. Rounding of AFUE
In response to the March 2022 NOPR,
Busse observed an inconsistency
between requirements to round the
AFUE at 10 CFR 430.23(n)(2)(iii) and
requirements to truncate the AFUE at 10
CFR 429.18(a)(2)(vii). (Busse, No. 22 at
p. 11)
On July 22, 2022, DOE published a
final rule regarding certification
requirements for several covered
products and equipment, including
consumer boilers (‘‘July 2022
Certification Final Rule’’). 87 FR 43952.
In an amendment established by that
final rule, effective August 22, 2022,
DOE modified 10 CFR 429.18(a)(2)(vii)
to state that AFUE must be rounded to
the nearest one-tenth of a percentage
point. Id. at 87 FR 43968. As this
amendment provides consistency
between the certification requirement
and the test procedure, no further
correction is required in this
rulemaking.
G. Other Test Procedure Topics
In the course of this rulemaking, DOE
solicited feedback on additional aspects
of the current test procedure for
consumer boilers to assess whether they
remain representative of the energy
consumption during an average use
cycle. DOE did not propose to amend
the test procedure for consumer boilers
with regard to these topics in the March
2022 NOPR, and after consideration of
comments received in response to that
NOPR, DOE determined not to amend
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
15525
the test procedure accordingly.
Comments received with regard to these
topics are discussed in the following
subsections.
1. Outdoor Design Temperature
ANSI/ASHRAE 103–2017 assigns a
value of 5 °F for the typical outdoor
design temperature and 42 °F for the
average outdoor air temperature,
represented by TOA,T and TOA,
respectively. The outdoor design
temperature is the lowest expected
temperature at which the boiler can
satisfy the home’s heating demand,
while the average outdoor air
temperature is the average temperature
during the heating season.
In response to the March 2022 NOPR,
Busse stated that the 5 °F outdoor design
temperature used in ANSI/ASHRAE
103–1993 26 may be out of date due to
climate change and suggested that
different outdoor design temperatures
could be assigned for furnaces and
boilers. (Busse, No. 22 at p. 4) Similarly,
Busse indicated that a 42 °F average
outdoor air temperature may no longer
be valid based on recent climate change
data. (Busse, No. 22 at p. 11)
In response, DOE notes that homes in
the United States—particularly in the
Northeast region, where most boilers are
installed—still experience temperatures
as low as 5 °F during the heating
season 27 despite climate change trends.
DOE does not have any data, nor did
Busse or other commenters provide any
such data, suggesting a value other than
5 °F that would provide more
representative test results. As such, DOE
is maintaining 5 °F as the outdoor
design temperature in the appendix EE
test procedure for consumer boilers.
Regarding the average outdoor air
temperature, DOE examined average
outdoor air temperatures for the
contiguous United States during the
months of October, November,
December, January, February, and
March (i.e., the months during which
consumer boilers would be expected to
operate).28 This data indicates that from
26 DOE notes that the same requirement is also
specified in ANSI/ASHRAE 103–2017.
27 For example, daily temperature data for the
Albany, NY, area for the winter of 2022 (December
1, 2021, through March 1, 2022) shows 13 days
during which the observed temperature reached at
or below 5 °F. The Duluth, MN, area experienced 55
days during which the observed temperature
reached at or below 5 °F during the same time
period. Data for these areas are available at
www.weather.gov/wrh/Climate?wfo=aly and
www.weather.gov/wrh/Climate?wfo=dlh. Last
accessed October 7, 2022.
28 These temperatures are published by the
National Oceanic and Atmospheric Administration
and are available at www.ncei.noaa.gov/access/
E:\FR\FM\13MRR2.SGM
Continued
13MRR2
15526
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
2012 through 2022, average outdoor air
temperatures during these months is
41 °F, which aligns closely with the
value of 42 °F specified in ANSI/
ASHRAE 103–2017. Therefore, in this
final rule, DOE is maintaining the value
of 42 °F for TOA as specified by ANSI/
ASHRAE 103–2017.
2. Ambient Conditions
The current test procedure for
consumer boilers in appendix N,
through incorporation by reference of
ANSI/ASHRAE 103–1993, specifies that
the ambient air temperature during
testing must be between 65 °F and
100 °F for non-condensing boilers, and
between 65 °F and 85 °F for condensing
boilers (see section 7 of appendix N and
section 8.5.2 of ANSI/ASHRAE 103–
1993). In addition, the relative humidity
cannot exceed 80 percent during
condensate measurement (see section 8
of appendix N and section 9.2 of ANSI/
ASHRAE 103–1993).
In the May 2020 RFI, DOE requested
comment and data on the effects of
ambient temperature and relative
humidity on AFUE results, whether the
current ranges of allowable conditions
adversely impact the representativeness
of AFUE values or repeatability of AFUE
testing, and whether a narrower range of
allowable ambient conditions would
increase testing burden. 85 FR 29352,
29356.
As discussed in the March 2022
NOPR, DOE received comments from
AHRI and manufacturers supporting the
current range of allowable operating
conditions, while the CA IOUs and
NEEA suggested limiting this range to
reflect the temperatures of spaces where
boilers may be installed. 87 FR 14622,
14631.
DOE investigated concerns regarding
the ambient conditions as part of the
January 2016 Final Rule (see 81 FR
2628, 2638; Jan. 15, 2016). Testing
conducted in support of the January
2016 Final Rule indicated there was no
definitive impact of variation of ambient
conditions on the resultant AFUE, and
DOE determined there was not adequate
data to justify changing the test
procedure to narrow the ranges. In the
March 2022 NOPR, DOE provided a
similar tentative determination based on
the lack of sufficient evidence, and thus
did not propose any changes at that
time. 87 FR 14622, 14631–14632.
In response, while the CA IOUs
supported incorporation by reference of
ANSI/ASHRAE 103–2017, they
encouraged DOE to reexamine the
impacts of ambient conditions on AFUE
monitoring/climate-at-a-glance/national/timeseries. Last accessed October 7, 2022.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
ratings by conducting additional testing.
(CA IOUs, No. 20 at p. 2) NYSERDA
requested that DOE revise the test
procedure to ensure that condensing
and non-condensing boilers are tested
under the same ambient conditions to
allow consumers to make informed
decisions between these products.
NYSERDA also requested that DOE
review the impacts of ambient
temperature on boiler performance and
review the jacket loss assumptions
based on likely real-world operating
conditions. Citing that DOE has not
provided a further study on ambient
conditions since the 2016 rulemaking,
NYSERDA urged DOE to revisit the
issue of ambient temperature impacts on
consumer boiler performance and
conduct additional analysis and/or
testing either as part of the current
rulemaking or in anticipation of the next
statutorily mandated review.
(NYSERDA, No. 23 at p. 5)
The Joint Advocates stated they did
not believe that separate ambient
conditions are necessary for noncondensing and condensing boilers, and
that the range of allowable ambient
temperatures is too broad to accurately
measure energy use during a
representative average use cycle. The
Joint Advocates cited course material
from Continuing Education and
Development, Inc. indicating that a
variation in ambient temperature of
20 °F can affect the thermal efficiency of
a commercial package boiler by over 0.5
percent, and therefore suggested that
DOE require the ambient temperature to
be maintained between 65 °F and 85 °F
for all consumer boilers. (Joint
Advocates, No. 21 at p. 3)
Busse stated that a boiler tested at the
current temperature and humidity limits
should perform at a higher AFUE than
when tested at a ‘‘normal’’ lab condition
of 70 °F and 50 percent relative
humidity due to higher water vapor
content and higher dew point
temperature and thus recommended
limiting the test room conditions to
75 °F and 55 percent relative humidity.
Busse noted that the National Bureau of
Standards Information Report
(‘‘NBSIR’’) recommended limits on the
original test room conditions,29 and that
water vapor content and dew point
temperature vary significantly with
temperature (specifically providing
29 Busse’s comment references two reports from
National Bureau of Information: NBSIR 78–1543:
‘‘Recommended Testing and Calculation Procedures
for Determining the Seasonal Performance of
Residential Central Furnaces and Boilers’’
(September 1978) and NBSIR 80–2110,
‘‘Recommended Testing and Calculation Procedures
for Estimating the Seasonal Performance of
Residential Condensing Furnaces and Boilers’’
(April 1981).
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
information at 42 °F [average outdoor air
temperature], 70 °F [‘‘normal’’ lab
condition], and 85 °F [maximum
allowable during AFUE test]). Busse
also cited Burnham Holdings, Inc.
(‘‘BHI’’) test data for a single condensing
boiler which showed a change in AFUE
of 1.3 percent when the relative
humidity was changed from
approximately 30 percent to 70 percent.
(Busse, No. 22 at p. 5)
DOE notes the data collected thus far
has been on a limited sample of boilers,
and the information required to amend
the ambient conditions should reflect
the array of boiler designs on the
market. The impact of the ambient air
conditions would vary based on how
the ambient air interacts with the boiler
during its normal operation. As noted
previously, in the January 2016 NOPR,
DOE concluded that the test data was
not definitive enough to provide
justification for changing the ambient
conditions. Regarding the data
submitted by Busse, DOE notes that BHI
also provided that data point in a
comment responding to the May 2020
RFI (BHI, No. 11 at p. 2, 11). As
discussed in the March 2022 NOPR,
although BHI provided test data for a
single unit showing a difference in
performance under different conditions,
DOE notes that DOE’s previous test data,
obtained from multiple units, did not
indicate conclusively that ambient test
conditions within the current bounds
cause substantive differences in AFUE.
As a result, DOE is not amending the
test procedure for consumer boilers to
narrow or revise the ambient test
conditions at this time due to
insufficient conclusive evidence
demonstrating the impact on AFUE for
various boiler types.
3. Combustion Settings
In the course of the rulemaking for the
January 2016 Final Rule, to provide for
greater consistency in burner airflow
settings during testing, DOE proposed
specifying that the excess air ratio, flue
oxygen (‘‘O2’’) percentage, or flue carbon
dioxide (‘‘CO2’’) percentage be within
the middle 30th percentile of the
acceptable range specified in the I&O
manual. 80 FR 12876, 12883, 12906
(Mar. 11, 2015). In absence of a
specified range in the I&O manual, DOE
proposed requiring the combustion
airflow to be adjusted to provide
between 6.9 percent and 7.1 percent dry
flue gas O2, or the lowest dry flue gas
O2 percentage that produces a stable
flame, no carbon deposits, and an airfree flue gas carbon monoxide (‘‘CO’’)
ratio below 400 parts per million
(‘‘ppm’’) during the steady-state test
described in section 9.1 of ANSI/
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ASHRAE 103–2007, whichever is
higher. 80 FR 12876, 12906. However,
after considering comments regarding
the representativeness of the proposal
and the potential impact on rated AFUE,
DOE determined in the January 2016
Final Rule that further study was
needed to determine how such changes
would impact AFUE ratings. 81 FR
2628, 2636.
In the May 2020 RFI, DOE requested
comment on whether more specific
instructions for setting the excess air
ratio, flue O2 percentage, and/or flue
CO2 percentage should be provided in
the consumer boilers test procedure,
and if so, what those instructions
should entail. 85 FR 29352, 29356. DOE
was particularly interested in
understanding whether such a change
would improve the representativeness
of the test method, and whether it
would impact test burden.
In the March 2022 NOPR, after
considering comments received in
response to the May 2020 RFI, DOE
tentatively concluded that it lacked
sufficient data and information to
indicate that establishing a requirement
for setting the excess air ratio, flue O2
percentage, and/or flue CO2 percentage
would provide ratings that are more
representative than the ratings provided
under the current approach. Therefore,
DOE tentatively determined to maintain
the current test procedure and did not
propose to establish a requirement for
setting the excess air ratio, flue O2
percentage, and/or flue CO2 percentage.
87 FR 14622, 14633.
In response to the March 2022 NOPR,
the CA IOUs encouraged DOE to
examine the impacts of excess air ratio,
flue oxygen percentage, and flue carbon
dioxide percentage on AFUE ratings by
conducting additional testing. (CA
IOUs, No. 20 at p. 2) The Joint
Advocates also encouraged DOE to
investigate the efficiency impacts of
combustion airflow settings and to
consider establishing criteria around
those settings in the test procedure in
order to provide more accurate product
rankings. The Joint Advocates asserted
that excess air, which can be
determined by flue gas O2 and CO2
concentrations, affects combustion
efficiency and, as an example, cited a
2002 fact sheet published by the
National Renewable Energy Laboratory
that indicated combustion efficiency of
commercial boilers can be increased by
1 percent for each 15 percent reduction
in excess air ratio.30 (Joint Advocates,
No. 21 at p. 3–4)
30 The fact sheet referenced by the Joint
Advocates is available at: https://www.nrel.gov/
docs/fy02osti/31496.pdf. (Last accessed 11/3/2022).
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
NYSERDA recommended that DOE
study how excess oxygen impacts the
efficiency of the boiler operation.
NYSERDA pointed out that DOE
received input from multiple
stakeholders regarding changes to
excess air ratio, flue O2 percentage, and/
or flue CO2 percentage in the 2016
rulemaking cycle. NYSERDA urged DOE
to either revisit this proposal regarding
excess oxygen or commit to further
study of this topic for a future revision.
(NYSERDA, No. 23 at p. 4–5)
Busse suggested updating the test
procedure to include two requirements:
(1) verify reduced input rate is 98
percent or greater than nameplate
minimum input rate and, if less than 98
percent, adjust controls or settings as
specified in the I&O manual and restart
test at maximum input rate or, if 98
percent or greater, no additional control
or setting changes are allowed; and (2)
verify combustion products do not
exceed 400 parts per million air-free and
there are no deposits of carbon on the
burner, and correct these conditions, if
necessary, as specified in the I&O
manual. Busse stated that a reduced
input rate below 98 percent of
nameplate minimum input rate would
likely result in a higher efficiency, and
that requiring adjustment and restarting
a test when above 102 percent of
nameplate minimum input rate could
increase test burden. Busse further
stated that these provisions would strive
towards more accurate AFUE results
while not greatly increasing the testing
burden. (Busse, No. 22 at p. 10)
In the January 2016 Final Rule, DOE
explained that industry stakeholders
indicated that the current practice is
typically to use the CO2 percentage at
the ‘‘top’’ of the manufacturer’s
specified range, and in some cases, even
higher than that. Stakeholders provided
data suggesting that the impacts on
AFUE could be significant but
variable,31 and there was also concern
that some products may not feature any
means of providing combustion setting
adjustment. Finally, commenters
indicated that DOE must evaluate the
burden associated with potential retesting should combustion setting
specifications require manufacturers to
re-rate their products. As discussed
31 AHRI stated that the results of the testing of
three residential boilers that it conducted at Intertek
Testing Laboratories indicate that the proposed
revised burner setup requirements change AFUE by
0.3 percent for each 1 percent difference in the CO2
values. By contrast, Burnham stated that based on
test data that it provided, for an oil-fired hot water
boiler with an 11.5 to 12.5 percent CO2 adjustment
range in the I&O manual, DOE’s proposed
adjustment would reduce AFUE by as much as 1.0
percent compared to the rating under the existing
test procedure. 81 FR 2628, 2636.
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
15527
previously, DOE ultimately agreed that
further study was needed on the
impacts of the CO2 percentage on AFUE
and, therefore, declined to adopt the
proposed amendments. 81 FR 2628,
2635–2636. Thus, there remained a lack
of certainty regarding what settings
would be most representative of field
use.
DOE did not receive any information
in response to the March 2022 NOPR
that provided further clarity on this
issue. Therefore, DOE has determined
that it still lacks sufficient information
to indicate that establishing a
specification for excess air ratio, flue O2
percentage, and/or flue CO2 percentage
would provide ratings that are more
representative than the ratings provided
under the current approach, and that
doing so would not be unduly
burdensome.
Therefore, DOE is maintaining the
current instructions and is not
establishing additional requirements
specifying excess air ratio, flue O2
percentage, and/or flue CO2 percentage.
4. Supplemental Test Instructions
In the March 2022 NOPR, DOE
responded to comments from BHI
suggesting that DOE create a repository
of supplemental test instructions,
similar to that currently in place for
commercial boilers,32 instead of
requiring a waiver to allow for use of
specific test instructions not included in
the I&O manual or the DOE test
procedure. 87 FR 14622, 14635–14636.
Specifically, BHI asserted that control
systems are increasingly complex,
which makes it impractical to run the
test without special tools or codes, and
that there are safety and reliability
concerns with putting testing-specific
instructions in the I&O manual. BHI also
asserted that the use of the waiver
process for these test instruction issues
is burdensome, unnecessary, and
inconsistent with the test procedure for
commercial boilers.
In response, DOE noted that BHI did
not provide specific examples of test
instructions that would not be able to be
included in the I&O manual due to
concerns about safety or reliability, and
that would thus need to be presented in
a waiver. In addition, DOE noted it has
not received any petitions for waiver for
any basic models of consumer boilers,
32 For commercial boilers, DOE provides that a
certification report may include supplemental
testing instructions, if such information is necessary
to run a valid test. Specifically, supplemental
information must include any additional testing
and testing set-up instructions (e.g., specific
operational or control codes or settings) which
would be necessary to operate the basic model
under the required conditions specified by the
relevant test procedure. 10 CFR 429.60(b)(4).
E:\FR\FM\13MRR2.SGM
13MRR2
15528
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
indicating there is not a problem with
testing absent such additional
information. Therefore, DOE did not
propose to establish a repository for test
instructions for consumer boilers and
stated that if testing of a consumer
boiler necessitates controls or
instructions other than those included
in the I&O manual, manufacturers may
petition for a waiver under the process
established at 10 CFR 430.27. DOE
sought further comment on whether
supplemental test instructions are
necessary for consumer boilers. 87 FR
14622, 14636.
Rheem recommended that DOE use
the I&O manual provided with the
product as the primary instruction for
testing a consumer boiler, and where a
manufacturer participates in a thirdparty certification program (such as
AHRI’s) and declares supplemental
instructions for product testing, the
manufacturer should have the option to
use such instructions for audit or
enforcement testing. (Rheem, No. 18 at
p. 5) A.O. Smith recommended that
some supplemental instructions from
manufacturers could ensure consistency
in testing, such as the need to use the
recirculation loop to prevent flashing in
the heat exchanger or instructions to
remove a water temperature sensor and
plug the opening. (A.O. Smith, No. 24
at p. 5) Busse suggested that
supplemental test instructions are
necessary for minimum input rate
adjustment (for step-modulating
condensing boilers) and for steam boiler
low water cutoff (wherein the feature
periodically turns off the burner to
monitor the settled water level and
therefore prevents the boiler from
operating continuously during a steadystate test). (Busse, No. 22 at p. 9)
As discussed in the March 2022
NOPR, DOE has not received any
petitions for waivers for any basic
models of consumer boilers, indicating
there is not a problem with testing
absent such additional information.
Should testing of a consumer boiler
necessitate controls or instructions other
than those included in the I&O manual,
manufacturers may petition for a waiver
under the process established at 10 CFR
430.27.
5. Input Rates for Step Modulating
Boilers
Appendix N includes a number of
specific provisions for consumer boilers
with step modulating controls. Boilers
with step modulating controls are
capable of operating at reduced input
rates (i.e., less than that maximum
nameplate input rate) and gradually or
incrementally increasing or decreasing
the input rate as needed to meet the
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
heating load. The test procedure
currently requires step modulating
boilers to be tested at the maximum rate
and the minimum (i.e., reduced) input
rate for the steady-state test (referencing
section 9.1 of ANSI/ASHRAE 103–
1993), the reduced input rate for the
cool-down test (referencing section
9.5.2.4 of ANSI/ASHRAE 103–1993),
and the reduced input rate for the heatup test (referencing section 9.6.2.1 of
ANSI/ASHRAE 103–1993). In addition,
both the optional tracer gas test and the
measurement of condensate under
cyclic conditions, when conducted, are
performed at the reduced input rate
(referencing sections 9.7.5 and 9.8 of
ANSI/ASHRAE 103–1993, respectively).
ANSI/ASHRAE 103–2017 contains the
same input rate requirements for
modulating boilers as ANSI/ASHRAE
103–1993.
In the May 2020 RFI, DOE requested
comment on whether the existing
provisions for testing step modulating
boilers appropriately reflect the
performance of such boilers. If not, DOE
sought specific recommendations on the
changes that would be necessary to
make the test procedure more
representative for such products. 85 FR
29352, 29357. Commenters indicated
these provisions were adequate, and
DOE did not propose any amendments
to the provisions for testing step
modulating boilers in the March 2022
NOPR. 87 FR 14622, 14633.
In response to the March 2022 NOPR,
BWC stated that it appreciated DOE not
proposing that step modulating units
account for operation at any additional
input rates beyond those specified in
the current test procedure. BWC stated
that the test methods in ANSI/ASHRAE
103–2017 sufficiently measure the
performance of these units at different
input rates and are representative of a
product’s average use cycle. (BWC, No.
19, p. 4)
For the reasons discussed in the
March 2022 NOPR, and in consideration
of the comments received, DOE is not
adopting any changes to the provisions
for testing step modulating boilers in
this final rule.
6. Return Water Temperature
The test procedure at appendix N
currently requires a nominal return
water temperature (‘‘RWT’’) of 120 °F to
124 °F for non-condensing boilers and
120 °F ± 2 °F for condensing boilers (see
section 7 of appendix N and sections
8.4.2.3 and 8.4.2.3.2 of ANSI/ASHRAE
103–1993, which are incorporated by
reference).
In response to the May 2020 RFI, the
CA IOUs requested that DOE consider
adopting multiple RWTs in the
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
amended test procedure for consumer
boilers, consistent with the
methodology being developed by the
ASHRAE Standard 155P Committee for
testing and rating commercial boilers,
which requires testing at multiple RWTs
depending on the operational
characteristics of the boiler. As
discussed in the March 2022 NOPR,
DOE considers the impact of varying
RWTs on field-installed efficiency in its
energy conservation standards
rulemakings. In the previous energy
conservation standards rulemaking for
consumer boilers, DOE developed AFUE
adjustment factors for low, medium, and
high RWT scenarios and estimated that,
on average, AFUE would vary from the
rated value by 2.66 percent to +3.15
percent depending on the model
characteristics and RWT (see 81 FR
2320, 2354); however, DOE noted there
is still a wide range of potential RWTs
in the field. Thus, in the March 2022
NOPR, DOE sought additional comment
on whether the RWT requirements in
the current test method and ANSI/
ASHRAE 103–2017 are representative
and appropriate, and whether any
specific changes to the required
conditions could improve
representativeness. DOE also sought
comment on any associated test burden
with changing RWTs. 87 FR 14622,
14633.
In response, the CA IOUs reiterated
their request for DOE to review whether
the 120 °F RWT requirement is
appropriately representative of realworld operating conditions. (CA IOUs,
No. 20 at p. 2)
AHRI and AGA & APGA urged DOE
to align return water temperatures with
those in ANSI/ASHRAE 103–2017.
(AHRI, No. 26 at p. 3; AGA & APGA, No.
25 at p. 2)
BWC supported DOE’s tentative
conclusion of including the single
return water temperature specified in
ANSI/ASHRAE 103–2017 for ease of
comparison between models and
manufacturers. (BWC, No. 19 at p. 4)
BWC asserted that a single condition
would not increase the test burden.
(BWC, No. 19 at p. 4)
A.O. Smith commented that the
current return water temperature is
representative of an average value for
the wide range of operating
temperatures in the field and indicated
that requiring testing to multiple
conditions may require adjustment of
the standards. A.O. Smith added that
non-condensing boilers are more likely
to be installed in systems with higher
supply and return water temperatures,
and condensing boilers are more likely
to be installed in systems with lower
temperatures. (A.O. Smith, No. 24 at p.
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
3–4) A.O. Smith stated that testing at
multiple water temperatures would add
testing burden to a test that could
already span two days to complete, and
that the burden to retest and rerate
products would also include updating
heat output ratings and safety
certifications. (Id.)
Rheem supported maintaining the
return water temperature in the current
test method, asserting that any change
that could make the return water
temperature more representative would
be outweighed by the testing and
certification burden on manufacturers.
Specifically, Rheem noted that slight
changes to the water temperature would
not produce significantly more
representative results, and major
changes would require retesting of
nearly all consumer boilers. (Rheem,
No. 18 at p. 4)
Crown and U.S. Boiler supported the
use of the water temperatures specified
by ANSI/ASHRAE 103–2017 to reduce
testing burden and complication. Crown
and U.S. Boiler stated that a single set
of water temperatures for all types of hot
water boilers is appropriate to avoid
consumer confusion, increased
certification burden, and departure from
the industry test method. Crown and
U.S. Boiler added that changes to these
water temperatures would cause
significant changes in AFUE ratings for
condensing boilers. (Crown, No. 16 at p.
3–4; U.S. Boiler, No. 17 at p. 3–4)
NYSERDA noted that return water
temperature has a significant impact on
boiler performance and urged DOE to
incorporate return water temperatures
that more accurately reflect real-world
conditions. NYSERDA stated that the
120 °F return water temperature is too
low, does not represent the boiler
running conditions according to a
research study done by The Electric and
Gas Program Administrators of
Massachusetts Part of the Residential
Evaluation Program Area in 2015,33 and
should be considered closer to 140 °F.
NYSERDA claimed that the rationale for
choosing the 120 °F return water
temperature from 1978 is outdated and
inconsistent with DOE’s current test
procedure methodologies for
commercial HVAC equipment.
NYSERDA recommended that DOE test
at both 120 °F and 140 °F for return
water temperatures but stated that if
DOE had to test at only one temperature,
33 High Efficiency Heating Equipment Impact
Evaluation, Prepared for: The Electric and Gas
Program Administrators of Massachusetts Part of
the Residential Evaluation Program Area, March
2015 at 22, available at ma-eeac.org/wp-content/
uploads/High-Efficiency-Heating-EquipmentImpact-Evaluation-Final-Report.pdf.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
it should be 140 °F. (NYSERDA, No. 23
at p. 2–4)
The Joint Advocates urged DOE to
continue to investigate return water
temperatures used in the test procedure
to capture more representative
performance, directing attention to data
presented in appendix 7B to DOE’s
preliminary analysis technical support
document (‘‘TSD’’),34 which indicated
that there was an impact of return water
temperature on the thermal efficiency 35
of a boiler. The Joint Advocates
suggested that multiple temperatures
(i.e., 108 °F and 158 °F) would be more
appropriate to be able to differentiate
amongst different condensing boiler
models, and that non-condensing
boilers should be tested at a higher
temperature of 158 °F. (Joint Advocates,
No. 21 at p. 2–3)
Busse stated that the current RWT
settings were from NBSIR 80–2110 and
asserted that the underlying
assumptions for the current return water
temperature found in NBSIR 80–2110,
pages 1–2 are out of date or invalid.36
Busse stated that the average
distribution system water temperature
in the current DOE test procedure
should be closer to 133 °F based on heat
load calculations to maintain a home at
65 °F. Busse noted that the current test
procedure has an average distribution
system water temperature of 130 °F
(based on a return water temperature of
120 °F and an outlet temperature of
140 °F). However, Busse added that the
average distribution system water
temperature may be too high based on
current or historically available heat
distribution products, and that review
literature from two cast-iron baseboard
manufacturers and two finned-tube
copper baseboard manufacturers suggest
an average distribution system water
temperature of 127 °F would be more
representative. Busse stated that current
industry practice for step-modulating,
condensing boilers may not allow
operation at the original 190 °F average
34 Appendix 7B of the preliminary analysis TSD
is available at www.regulations.gov at Docket
Number EERE–2019–BT–STD–0036. The data can
be found in chapter 7B, page 11.
35 Thermal efficiency for a commercial packaged
boiler is determined using test procedures
prescribed under 10 CFR 431.86 and is the ratio of
the heat absorbed by the water or the water and
steam to the higher heating value in the fuel
burned. Data presented in the May 2022
Preliminary Analysis TSD reflected the
performance of commercial packaged boilers due to
the absence of information on consumer boilers.
36 Kelly, George E. and Kuklewicz, Mark E.,
NBSIR 80–2110: Recommended Testing and
Calculation Procedures for Estimating the Seasonal
Performance of Residential Condensing Furnaces
and Boilers, National Bureau of Standards
(Sponsored by U.S. Department of Energy), April
1981.
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
15529
boiler water temperature (200 °F supply)
or deliver 140 °F supply temperature at
the 42 °F average outdoor temperature at
the default controller settings. (Busse,
No. 22 at p. 2–4) Busse recommended
that a separate test should be required
for determining heating capacity using a
180 °F return supply water temperature
(or the maximum supply temperature
allowed by the control system, if less
than 200 °F), or, alternatively, the
current return water temperature could
be used with consideration of sensible
heat losses only in order to estimate the
steady-state efficiency for a
noncondensing operation at high return
water temperatures. (Busse, No. 22 at p.
6) Busse also asserted that boilers with
reported ratings of 95 percent or 96
percent AFUE have such ratings as a
result of a flawed calculation in the
current test procedure, which does not
account for the portion of the season
during which the boiler would operate
in a non-condensing mode (due to
return water temperatures being higher
than 120 °F in certain conditions).
(Busse, No. 22 at p. 11–12)
As acknowledged by commenters, the
specification of RWT has a substantive
impact on the AFUE of boilers.
Condensing boilers in particular achieve
higher efficiency levels by extracting
latent heat from the flue gases in
addition to sensible heat (i.e., the
condensation of flue gases releases a
substantial amount of energy into the
water that is being heated). However,
flue gases can condense only if the dew
point temperature of the vapor is
reached. If the return (inlet) water is
hotter than this dew point temperature,
then condensation of the flue gases
cannot occur in the heat exchanger, and
the boiler operates in a non-condensing
mode, reducing AFUE.
In addition to the recommendations
provided by commenters, DOE research
indicates a range of RWTs in consumer
applications. DOE is aware that many
existing consumer boiler installations
require the RWT to be 160 °F and some
even as high as 180 °F.37 However, as
new applications such as radiant floor
heating and heat pump boilers become
more prevalent in the market, DOE
recognizes that some new boilers may
be installed in homes that require lower
37 On May 4, 2022, DOE published in the Federal
Register a notice of availability of the preliminary
analysis for energy conservation standards for
consumer boilers (the ‘‘May 2022 Preliminary
Analysis’’). 87 FR 26304. DOE provided a technical
support document (‘‘TSD’’) for the May 2022
Preliminary Analysis in the rulemaking docket. Id.
In the energy use analysis of the May 2022
Preliminary Analysis TSD, DOE estimated that 90
percent of condensing boilers installed as
replacements to non-condensing boilers would be
subject to a higher RWT of 158 °F to 160 °F.
E:\FR\FM\13MRR2.SGM
13MRR2
15530
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
RWTs. In addition, condensing boilers
in new installations would be subject to
lower RWTs because radiant floor
heating and hydronic air handler
applications represent a substantial
proportion of new hot water boiler
installations.38 DOE research indicates
some installations have RWT conditions
as low as 85 °F in certain cases.39 DOE
notes that the midpoint of the range of
RWTs observed through DOE’s research
(ranging between 85 °F and 160 °F) is
122 °F, which is reasonably close to the
120 °F condition specified in appendix
N and the industry test procedures.
Given these considerations, DOE has
determined that testing a consumer
boiler at a single ‘‘high’’ RWT, as
suggested by the Joint Advocates,
NYSERDA, and Busse, would be less
representative than the conditions
specified by the current test procedure.
DOE also acknowledges the concerns
raised by manufacturers regarding the
potential need to retest and recertify all
consumer boilers if a new test condition
were to be required in addition to the
currently established 120 °F condition.
EPCA requires DOE to establish test
procedures that are reasonably designed
to produce test results that measure
energy efficiency of a consumer boiler
during a representative average use
cycle or period of use, as determined by
the Secretary, and shall not be unduly
burdensome to conduct. (42 U.S.C.
6293(b)(3)) Based on the considerations
discussed in this section, DOE has
determined that it lacks data and
information to conclude that a different
RWT (or multiple RWTs) would be more
representative than the current RWT
requirements such that it would justify
the potential burden of such a change.
Hence, in this final rule, DOE is
finalizing its proposal from the March
2022 NOPR to incorporate by reference
the test conditions in ANSI/ASHRAE
103–2017. Should additional data or
information become available in the
future, DOE would consider this topic
again in a subsequent test procedure
rulemaking.
38 In the May 2022 Preliminary Analysis, DOE
estimated that condensing boilers in new
installations (new constructions or new owners)
would be subject to an average RWT of 108 °F. See
Appendix 7B of the preliminary analysis TSD,
available at: www.regulations.gov/document/EERE2019-BT-STD-0036-0021.
39 See, for example: www.barronheating.com/
blog/the-book-on-radiant-heating-when-it-makessense-and-when-it-might-not/
#:∼:text=Radiant%2Dfloor%20
heating%20systems%20typically,
55%E2%80%9370%C2%B0C). (Last accessed on
October 6, 2022)
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
7. Standby Mode and Off Mode
Electrical Energy Consumption
As discussed in section I.A of this
final rule, EPCA requires that DOE
amend test procedures to include
standby mode and off mode energy
consumption, ‘‘taking into consideration
the most current versions of Standards
62301 and 62087 of the International
Electrotechnical Commission.’’ (42
U.S.C. 6295(gg)(2)(A)) The DOE test
method currently references IEC 62301
(Edition 2.0 2011–01), which provides
instructions for measuring standby
mode and off mode energy
consumption. IEC 62301 provides
several options for measuring the
standby mode and off mode power
consumption using either the ‘‘sampling
method,’’ ‘‘average reading method,’’ or
‘‘direct meter reading method.’’
Although these methods vary, if the
standby or off mode consumption is
stable, each method can be completed in
under 1 hour, and the sampling method
can be completed in as little as 15
minutes.
In the March 2022 NOPR, DOE
tentatively determined that the
provisions in IEC 62301 provide an
appropriate representation of standby
mode and off mode energy consumption
of consumer boilers and are not unduly
burdensome; hence DOE did not
propose any changes. Because
commenters responding to the May
2020 RFI recommended streamlining
the procedure for determining standby
mode and off mode energy
consumption, in the March 2022 NOPR
DOE requested further comment on
whether a simplified approach for
measuring standby mode and off mode
electrical energy consumption is
appropriate and would provide
accurate, representative results that are
comparable to those obtained with IEC
62301. 87 FR 14622, 14634.
In response, BWC commented that the
standby mode and off mode test
methods are appropriate and do not
need to be amended at this time. (BWC,
No. 19 at p. 4)
Rheem stated that the current
approach for measuring standby and off
mode electrical energy consumption is
not overly burdensome and should be
maintained. Rheem also recommended
that DOE examine a combined AFUE
metric that includes standby and off
mode electrical energy use, asserting
that an increase in standby and off mode
energy use may be needed to
accommodate an increase in overall
efficiency, and thus a combined AFUE
metric would provide for greater design
flexibility. (Rheem, No. 18 at p. 4)
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
DOE considered an integrated AFUE
metric (‘‘AFUEI’’) in a test procedure
final rule published October 20, 2010
(‘‘October 2010 Final Rule’’), which
established the standby mode and off
mode electrical energy use metrics. 75
FR 64621, 64626–64627 (Oct. 20, 2010).
In the October 2010 Final Rule, DOE
explored the possibility of regulating
AFUEI; however, commenters objected
that the approach would provide an
ineffective basis for regulation, and thus
it was not ‘‘technically feasible’’ to
integrate AFUE with standby mode and
off mode energy consumption. Id.
Separate metrics were established
because the magnitude of the standby
mode and off mode energy consumption
was very small compared to the active
mode fuel consumption, and, as a result,
it was not possible to discern different
levels of standby and off mode power
consumption (i.e., AFUEI values were
essentially identical to AFUE values).
Id.
Neither Rheem nor other commenters
have presented DOE with any
information to suggest that the
conclusions from the October 2010
Final Rule—specifically, that an
integrated metric would not be
technically feasible—are no longer
applicable. Furthermore, DOE is not
aware of any current industry-accepted
test procedure that combines the current
AFUE metric with the standby mode
and off mode power consumption
metrics. For these reasons, DOE is not
adopting any new provisions for a
combined metric in this final rule.
A.O. Smith recommended eliminating
the standby mode and off mode power
consumption testing due to the little
impact the associated power
consumption has on the total efficiency
of a consumer boiler (less than a fraction
of one percent). A.O. Smith indicated
that procuring the adequate equipment
and instrumentation required for this
testing is burdensome. A.O. Smith also
commented that removing these
requirements would afford
manufacturers the opportunity to
potentially add safety enhancements
such as carbon monoxide sensors,
which require a small heating element
to prevent premature failure, as well as
options for control displays and ways to
reduce cycling losses. (A.O. Smith, No.
24 at p. 4) A.O. Smith recommended
that if DOE were to keep the standby
mode and off mode tests as part of the
test procedure, the standby mode and
off mode power consumption should be
measured with a simple current
measurement with a calibrated watt
meter. (A.O. Smith, No. 24 at p. 6)
As discussed, EPCA requires that DOE
include in its test procedures a method
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
for measuring standby mode and off
mode power consumption, unless
technically infeasible. (42 U.S.C.
6295(gg)(2)(A)) Further, in doing so,
EPCA requires that DOE must consider
IEC Standard 62301 and IEC Standard
62087. (42 U.S.C. 6295(gg)(2)(A))
Section 4.4 of IEC 62301 provides
instruction on selecting acceptable
power measuring instrumentation by
specifying power measurement
uncertainty bounds, frequency response,
and long-term averaging (integrating)
requirements. DOE notes that if a
calibrated watt meter is capable of
meeting these requirements, then it may
be used in accordance with section 4.4
of IEC 62301.
AHRI noted that standby mode and
off mode power consumption should
not count as a loss because all energy
brought into the system provides useful
resistive heat to the building. AHRI
stated that similar logic is used to give
electric boilers a rating of 100 percent
efficiency. (AHRI, No. 26 at p. 3)
While electrical component power
draws that dissipate small amounts of
heat to the surroundings may contribute
to useful heating to the building, the
building does not always demand
heating. During the cooling season, any
heat dissipated would be
counterproductive. Furthermore, not all
boilers are located in conditioned
spaces. In addition, as discussed
previously, EPCA requires DOE to
include in its test procedures a method
for measuring standby mode and off
mode power consumption. (42 U.S.C.
6295(gg)(2)(A)) For these reasons, DOE
makes no change to its inclusion of
standby mode and off mode power in
this final rule.
In conclusion, DOE has determined
that no changes to the standby mode
and off mode test provisions are
warranted. As such, the new appendix
EE test procedure maintains the same
test methods for measuring these
metrics as specified in the current
appendix N test procedure.
8. Full Fuel Cycle Efficiency
The full fuel cycle (‘‘FFC’’) accounts
for the energy consumed in extracting,
processing, and transporting fuels. In
the March 2022 NOPR, DOE responded
to comments received in response to the
May 2020 RFI requesting that DOE
consider incorporating an FFC analysis
into the test procedure in order to allow
for direct comparisons between fossil
fuel-fired systems and electric systems.
87 FR 14622, 14634. DOE responded
that FFC is typically considered in
energy conservation standards
rulemakings—not as a metric for
representing product efficiency. Id. In
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
the March 2022 NOPR, DOE maintained
its previous conclusion from the January
2016 Final Rule that a mathematical
adjustment to the test procedure to
account for FFC is not appropriate
because the mathematical adjustment to
the site-based energy descriptor relies
on information that is updated annually,
which would require annual updating of
the test method. Id.
In response to the March 2022 NOPR,
BWC stated that the FFC efficiency and
source efficiency analysis are not
appropriate to include in the Federal
test procedure. (BWC, No. 19, p. 4)
For the reasons discussed in the
March 2022 NOPR, DOE maintains in
this final rule its previous determination
not to account for FFC in the consumer
boiler test procedure.
9. Idle Losses
In the March 2022 NOPR, DOE
responded to comments received in
response to the May 2020 RFI requesting
that DOE consider ‘‘idle losses’’ that are
not captured in the AFUE metric. 87 FR
14622, 14628. Specifically, Energy
Kinetics asserted that oversizing of
boilers can lead to wasted energy to heat
up the boiler but not contribute to the
heating of the hydronic loop. In the
March 2022 NOPR, DOE stated that
EPCA (42 U.S.C. 6295(f)(3)(A)–(B))
requires hot water boilers to have an
automatic means for adjusting water
temperature, which limits idle losses.
DOE indicated that idle losses could be
further addressed in the determination
of AFUE; however, there was
insufficient data to propose
amendments to the test procedure to do
so. DOE sought further comment from
interested parties on the topic. 87 FR
14622, 14628.
In response to the March 2022 NOPR,
Rheem agreed with DOE’s statement
that the prescriptive design
requirements in EPCA at 42 U.S.C.
6295(f)(3) effectively reduce idle losses
in the field. Rheem noted that if idle
losses, both electrical and fossil fuel,
were fully accounted for in the AFUE
metric, then a standard could be
proposed that would not require
separate design requirements. (Rheem,
No. 18 at p. 5)
DOE has determined that there
remains insufficient information to
further address idle losses in this
rulemaking as it pertains to the
determination of AFUE in the new
appendix EE test procedure for
consumer boilers.
H. Alternative Efficiency Determination
Methods
At 10 CFR 429.70, DOE includes
provisions for alternative efficiency
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
15531
determination methods (‘‘AEDMs’’),
which are computer modeling or
mathematical tools that predict the
performance of non-tested basic models.
They are derived from mathematical
models and engineering principles that
govern the energy efficiency and energy
consumption characteristics of a type of
covered equipment. These computer
modeling and mathematical tools, when
properly developed, can provide a
relatively straight-forward and
reasonably accurate means to predict
the energy usage or efficiency
characteristics of a basic model of a
given covered product or equipment
and reduce the burden and cost
associated with testing. 78 FR 79579,
79580 (Dec. 31, 2013; the ‘‘December
2013 AEDM Final Rule’’). Where
authorized by regulation, AEDMs enable
manufacturers to rate and certify their
basic models by using the projected
energy use or energy efficiency results
derived from these simulation models in
lieu of testing. Id. at 78 FR 79580.
DOE does not currently authorize the
use of AEDMs for consumer boilers,
whereas DOE does authorize the use of
AEDMs for commercial packaged
boilers.40 Manufacturers of consumer
boilers (or furnaces more generally) are
not authorized to use an AEDM to
determine ratings for these products.
However, manufacturers of cast-iron
boilers may determine AFUE for models
at a capacity other than the highest or
lowest of the group of basic models
having identical intermediate sections
and combustion chambers through
linear interpolation of data obtained for
the smallest and largest capacity units of
the family. See 10 CFR
429.18(a)(2)(iv)(A). These provisions
already provide manufacturers with an
alternative method of rating consumer
boilers without testing every model, and
this alternative method reduces
manufacturer test burden.
In the March 2022 NOPR, DOE
requested comment on whether AEDM
provisions similar to those in place for
commercial equipment would be
necessary and appropriate for consumer
boilers. 87 FR 14622, 14635.
A.O. Smith stated that adding an
AEDM option for consumer boilers
would be reasonable; however, there is
40 In the December 2013 AEDM Final Rule, DOE
explained that the AEDM provisions extend to
those products or equipment which ‘‘have
expensive or highly-customized basic models.’’ 78
FR 79579, 79580. The current AEDM provisions for
commercial HVAC equipment (including
commercial package boilers, for example) were in
part the result of a negotiated rulemaking effort by
the Appliance Standards and Rulemaking Federal
Advisory Committee (ASRAC) in 2013. Id. Boilers
designed for residential applications were not
considered at the time. 78 FR 79579.
E:\FR\FM\13MRR2.SGM
13MRR2
15532
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
greater value to have an AEDM for
commercial products given that those
models can be engineered to order.
(A.O. Smith, No. 24 at p. 4) Busse
indicated that the breadth of a product
line with similar geometries and
performance would not seem to justify
an AEDM; however, an AEDM may be
the only method to avoid testing each
model. (Busse, No. 22 at p. 8)
In consideration of these comments,
as well as considerations discussed in
the March 2022 NOPR (see 87 FR 14622,
14635), in this final rule, DOE
concludes that manufacturer testing
burden is alleviated by the linear
interpolation provisions for cast-iron
boilers, such that an AEDM for
consumer boilers more broadly is not
warranted at this time.
I. Certification Provisions for Cast-Iron
Boilers
ddrumheller on DSK120RN23PROD with RULES2
As discussed in the March 2022
NOPR, the certification provisions at 10
CFR 429.18(a)(2)(iv)(A) alleviate testing
burden for cast-iron boilers, which are
commonly constructed of identical castiron heat exchanger sections. Boilers of
the same cast-iron product family are
often constructed so that the heating
capacity can be increased by adding
more sections to the heat exchanger.
When a product family is designed in
this way, linear interpolation is
accurate 41 to predict the performance of
intermediately-sized boilers. The March
2022 NOPR sought data and other
information that would demonstrate
that using a linear interpolation method
for heat exchanger materials other than
cast-iron would produce representative
test results. 87 FR 14622, 14635.
AHRI and AGA and APGA supported
extending of the use of linear
interpolation to heat exchanger
materials other than cast-iron, stating
that linear interpolation is a valid
calculation method for these products,
as proven by the current cast-iron
allowance. (AHRI, No. 26 at p. 4; AGA
and APGA, No. 25 at p. 2)
A.O. Smith supported use of the
interpolation method for boilers with
heat exchangers other than cast-iron,
stating that its copper finned-tube
boilers have a tray of tubes that increase
in length proportionate to input rate, are
consistent in geometry, and have only
incremental changes proportionate to
41 Test data analyzed as part of the 1979
rulemaking which established these provisions
showed that the annual fuel utilization efficiency,
energy consumption, and estimated annual
operating cost of sectional cast-iron boilers can be
accurately predicted by a linear interpolation based
on data obtained from units having the smallest and
largest number of intermediate sections. 44 FR
22410, 22415 (April 13, 1979).
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
input rate. A.O. Smith added that its
Lochinvar brand models have seven
input rates ranging from 45,000 Btu/h
through 260,000 Btu/h and all perform
near 84.0-percent AFUE. (A.O. Smith,
No. 24 at p. 5)
Rheem did not support the use of
linear interpolation for certification of
consumer boilers beyond what is
already allowed for cast-iron boilers,
stating that interpolation produces less
accurate results than results derived
from actual tests. (Rheem, No. 18 at p.
4)
Busse did not support using a linear
interpolation method for heat exchanger
materials other than cast-iron. Busse
asserted that any difference and/or nonproportionality in excess air, flue
loading, and/or flue cross-sectional area
could produce non-linear results, which
is also why cast-iron units equipped
with draft hoods, draft diverters, or
induced draft systems are more prone to
producing non-linear results. (Busse,
No. 22 at p. 7–8)
Based on DOE’s review of product
literature, DOE has determined that heat
exchangers made of different materials
may not be constructed with identical
additive components the way cast-iron
sectional heat exchangers are
constructed; hence, the linear
interpolation method may be less viable
for other heat exchanger materials. DOE
notes that stakeholders commenting in
support of using linear interpolation for
materials other than cast-iron did not
provide any data to demonstrate the
viability of a linear interpolation
method for other heat exchanger
materials. Given the concerns raised by
Rheem and Busse regarding the
potential for non-linear results for
intermediately-sized boilers with noncast-iron heat exchangers, as well as
DOE’s review of product literature, DOE
has concluded that there is not enough
information to substantiate such a
provision at this time. Hence, in this
final rule, DOE maintains that the linear
interpolation AEDM method applies
only to cast-iron boilers.
Additionally, Busse recommended the
following clarifications for using linear
interpolation: (1) clarify if interpolated
values are derived from truncated or
pre-truncated AFUE values of smallest
and largest capacity units, (2) update 10
CFR part 429 to allow interpolation of
heating capacity derived from
unrounded EffySS values of smallest and
largest capacity units, and (3) require
third-party test agencies to qualify
AFUE and heating capacity on an
‘‘interpolated’’ model. (Busse, No. 22 at
p. 7–8)
First, as discussed in section III.F.8,
DOE has amended the certification
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
requirements for AFUE in the July 2022
Certification Final Rule to require that
AFUE must be rounded to the nearest
tenth of a percentage point when this
value is reported. 87 FR 43968. Thus, as
of this final rule, truncation is no longer
used to report AFUE. DOE is clarifying
in this final rule, however, that
manufacturers may use either the
rounded or unrounded AFUE values of
the smallest and largest capacity units
for linear interpolation. DOE is making
this determination based on the fact that
the results of the linear interpolation
would be minimally impacted by
rounding AFUE to the nearest tenth of
a percentage point, compared to using
unrounded values.
Second, DOE notes that heating
capacity (QOUT), which is calculated in
the current test procedure as a function
of steady-state efficiency (EffySS), is not
required to be certified to DOE at this
time, nor has DOE proposed to make
this a requirement. Currently,
manufacturers must certify the
nameplate input rate (QIN), which is a
separate metric and not a function of
EffySS. Hence, DOE is not updating the
linear interpolation provisions to
include heating capacity (QOUT).
Third, requiring third-party testing to
qualify AFUE ratings derived using the
linear interpolation method would
eliminate the reduction in test burden
achieved with the alternate linear
interpolation approach. DOE notes,
however, that it can conduct assessment
or enforcement testing on consumer
boiler models, and this process serves to
verify ratings (see subpart C to 10 CFR
part 429).
In conclusion, DOE has determined in
this final rule not to amend the linear
interpolation provisions for consumer
boilers.
J. Effective and Compliance Dates
The effective date for the adopted test
procedure amendment will be 30 days
after publication of this final rule in the
Federal Register. EPCA prescribes that
all representations of energy efficiency
and energy use, including those made
on marketing materials and product
labels, must be made in accordance with
an amended test procedure, beginning
180 days after publication of the final
rule in the Federal Register. (42 U.S.C.
6293©(2)) EPCA provides an allowance
for individual manufacturers to petition
DOE for an extension of the 180-day
period if the manufacturer may
experience undue hardship in meeting
the deadline. (42 U.S.C. 6293(c)(3)) To
receive such an extension, petitions
must be filed with DOE no later than 60
days before the end of the 180-day
period and must detail how the
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
manufacturer will experience undue
hardship. (Id.)
K. Test Procedure Costs
EPCA requires that test procedures
proposed by DOE not be unduly
burdensome to conduct. (42 U.S.C.
6293(b)(3))
In the March 2022 NOPR, DOE
discussed that the amendments
proposed to the test procedure for
consumer boilers would be expected to
have minimal impact on efficiency
ratings such that manufacturers would
not be required to retest and recertify
ratings. 87 FR 14622, 14625, 14636.
DOE also tentatively determined that
the proposed amendments would not
impact testing costs or increase burden.
DOE requested feedback from
stakeholders on these tentative
determinations. Id.
A.O. Smith supported DOE’s
determination that the proposed
incorporation by reference of ASHRAE
41.6–2014 will not increase testing
burden. A.O. Smith also stated that
DOE’s estimate for third-party AFUE
testing is reasonable and agreed that the
proposed incorporation by reference of
ANSI/ASHRAE 103–2017 is not unduly
burdensome. (A.O. Smith, No. 24 at p.
5) A.O. Smith stated that although there
may be fractional changes in the AFUE
rating as a result of testing to the 2017
version, these should not necessitate
retesting or rerating of any existing
boilers. A.O. Smith also supported
having a publicly available AFUE
calculation tool to enhance consistency
of results across the industry. (A.O.
Smith, No. 24 at p. 3)
Rheem stated that the test costs under
the proposed appendix EE test
procedure are likely to remain similar to
the current appendix N test procedure.
(Rheem, No. 18 at p. 5)
AHRI stated that it previously
commented that a move to ANSI/
ASHRAE 103–2017 would not result in
increased test burden; however, it had
come to AHRI’s attention that there are
manufacturers using automated
programs that would incur an increased
test burden. (AHRI, No. 26 at p. 4)
DOE understands that AHRI is
referring to pre-programmed cycle
times, which execute burner on and off
functions at pre-determined times per
the DOE test procedure. From DOE’s
own testing of the impact of cycle
timings at a third-party lab using an
automated program, DOE has
determined that these parameters can be
simple to re-program and that doing so
would not constitute undue test burden.
As discussed in section III.D.1.c, other
commenters requested DOE to further
investigate whether the update in cycle
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
times would increase burden by
requiring retesting. Based on test data
indicating little variation in test results
due to the update in cycle times, DOE
has determined that the impact of these
amendments on ratings would be
minimal. With regard to providing a
publicly available AFUE calculation
tool, DOE provides test report templates
on its certification website,42 including
a template for the consumer boiler test
procedure.
For this final rule, DOE has evaluated
the impacts on ratings resulting from its
adoption of the test methods in the
updated industry test standard, ANSI/
ASHRAE 103–2017. These updates are
discussed in detail in section III.D.1 of
this final rule. Based on this review,
DOE has determined that manufacturers
will be able to rely on data generated
under the current test procedure. As
such, it is unlikely that retesting of
consumer boilers would be required
solely as a result of DOE’s adoption of
the finalized amendments to the test
procedure. However, if a manufacturer
were to retest a model using the
amended test procedure as finalized,
DOE estimates that the cost of
performing the amended AFUE test at a
third-party laboratory would be $3,600,
the same as the cost of performing the
current AFUE test. This estimate
represents an increase of $600 from the
cost estimate in the March 2022 NOPR,
to account for overall increases in
laboratory testing fees.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Orders
12866 and 13563
Executive Order (‘‘E.O.’’) 12866,
‘‘Regulatory Planning and Review,’’ as
supplemented and reaffirmed by E.O.
13563, ‘‘Improving Regulation and
Regulatory Review,’’ 76 FR 3821 (Jan.
21, 2011), requires agencies, to the
extent permitted by law, to (1) propose
or adopt a regulation only upon a
reasoned determination that its benefits
justify its costs (recognizing that some
benefits and costs are difficult to
quantify); (2) tailor regulations to
impose the least burden on society,
consistent with obtaining regulatory
objectives, taking into account, among
other things, and to the extent
practicable, the costs of cumulative
regulations; (3) select, in choosing
among alternative regulatory
approaches, those approaches that
maximize net benefits (including
potential economic, environmental,
42 Standardized test report templates are available
online at: www.energy.gov/eere/buildings/
standardized-templates-reporting-test-results.
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
15533
public health and safety, and other
advantages; distributive impacts; and
equity); (4) to the extent feasible, specify
performance objectives, rather than
specifying the behavior or manner of
compliance that regulated entities must
adopt; and (5) identify and assess
available alternatives to direct
regulation, including providing
economic incentives to encourage the
desired behavior, such as user fees or
marketable permits, or providing
information upon which choices can be
made by the public. DOE emphasizes as
well that E.O. 13563 requires agencies to
use the best available techniques to
quantify anticipated present and future
benefits and costs as accurately as
possible. In its guidance, the Office of
Information and Regulatory Affairs
(‘‘OIRA’’) in the Office of Management
and Budget (‘‘OMB’’) has emphasized
that such techniques may include
identifying changing future compliance
costs that might result from
technological innovation or anticipated
behavioral changes. For the reasons
stated in the preamble, this final
regulatory action is consistent with
these principles.
Section 6(a) of E.O. 12866 also
requires agencies to submit ‘‘significant
regulatory actions’’ to OIRA for review.
OIRA has determined that this final
regulatory action does not constitute a
‘‘significant regulatory action’’ under
section 3(f) of E.O. 12866. Accordingly,
this action was not submitted to OIRA
for review under E.O. 12866.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of a final regulatory flexibility analysis
(FRFA) for any final rule where the
agency was first required by law to
publish a proposed rule for public
comment, unless the agency certifies
that the rule, if promulgated, will not
have a significant economic impact on
a substantial number of small entities.
As required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s website: www.energy.gov/gc/
office-general-counsel.
DOE reviewed this final rule under
the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
15534
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
2003. DOE certifies that this rule, if
adopted, would not have significant
economic impact on a substantial
number of small entities. The factual
basis of this certification is set forth
below.
Under 42 U.S.C. 6293, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered products.
EPCA requires that any test procedures
prescribed or amended under this
section shall be reasonably designed to
produce test results which measure
energy efficiency, energy use, or
estimated annual operating cost of a
covered product during a representative
average use cycle (as determined by the
Secretary) or period of use and shall not
be unduly burdensome to conduct. (42
U.S.C. 6293(b)(3))
EPCA also requires that, at least once
every 7 years, DOE evaluate test
procedures for each type of covered
product, including consumer boilers, to
determine whether amended test
procedures would more accurately or
fully comply with the requirements for
the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle or period of use. (42 U.S.C.
6293(b)(1)(A)) DOE is publishing this
final rule in satisfaction of the 7-year
review requirement specified in EPCA.
(42 U.S.C. 6293(b)(1)(A))
DOE did not receive written
comments that specifically addressed
impacts on small businesses or that
were provided in response to the March
2022 NOPR.
The Small Business Administration
(‘‘SBA’’) has set a size threshold, which
defines those entities classified as
‘‘small businesses’’ for the purposes of
the statute. DOE used the SBA’s small
business size standards to determine
whether any small entities would be
subject to the requirements of the rule.
See 13 CFR part 121. The products
covered by this rule are classified under
North American Industry Classification
System (‘‘NAICS’’) code 333414,43
‘‘Heating Equipment (except Warm Air
Furnaces) Manufacturing.’’ In 13 CFR
121.201, the SBA sets a threshold of 500
employees or fewer for an entity to be
considered as a small business for this
category. This employment figure is
enterprise-wide, encompassing
43 The SBA size standards (effective October 1,
2022) are listed by NAICS code and industry
description and are available at: www.sba.gov/
document/support-table-size-standards (last
accessed on December 1, 2022).
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
employees at the parent, subsidiary, and
sister corporations.
Consistent with the March 2022
NOPR, DOE relied on the Compliance
Certification Database (‘‘CCD’’),44 the
AHRI database,45 the California Energy
Commission’s Modernized Appliance
Efficiency Database System
(‘‘MAEDbS’’),46 the ENERGY STAR
Product Finder database,47 and the prior
consumer boiler energy conservation
standards rulemaking to create a list of
companies that import or otherwise
manufacture the products covered by
this final rule. DOE used the publicly
available information and subscriptionbased market research tools (e.g., reports
from Dun & Bradstreet 48) to identify 27
original equipment manufacturers
(‘‘OEMs’’) affected by this final rule. Of
the 27 OEMs, DOE identified five
domestic OEMs of consumer boilers that
met the SBA definition of a ‘‘small
business’’ and are not foreign-owned
and operated.
In this final rule, DOE updates
appendix N to remove the provisions
applicable only to consumer boilers and
to rename the current appendix as
‘‘Uniform Test Method for Measuring
the Energy Consumption of Furnaces.’’
Correspondingly, this final rule
establishes a new test procedure at 10
CFR part 430 subpart B, appendix EE,
‘‘Uniform Test Method for Measuring
the Energy Consumption of Boilers’’
(‘‘appendix EE’’). In the new appendix
EE, DOE includes all provisions
currently included in appendix N
relevant to consumer boilers, with the
following modifications:
(1) Incorporate by reference the
current revision to the applicable
industry standard, ANSI/ASHRAE 103–
2017, ‘‘Methods of Testing for Annual
Fuel Utilization Efficiency of
Residential Central Furnaces and
Boilers.’’
(2) Incorporate by reference the
current revision of ASTM Standard
D2156–09 (Reapproved 2018),
‘‘Standard Test Method for Smoke
Density in Flue Gases from Burning
Distillate Fuels.’’
44 U.S. Department of Energy Compliance
Certification Database, available at:
www.regulations.doe.gov/certification-data/
products.html.
45 The AHRI Database is available at:
www.ahridirectory.org (last accessed March 3,
2021).
46 California Energy Commission’s MAEDbS is
available at cacertappliances.energy.ca.gov/Pages/
ApplianceSearch.aspx (last accessed September 22,
2021).
47 The ENERGY STAR Product Finder database is
available at energystar.gov/productfinder/ (last
accessed September 22, 2021).
48 D&B Hoovers | Company Information | Industry
Information | Lists, app.dnbhoovers.com/ (last
accessed September 29, 2022).
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
(3) Incorporate by reference ANSI/
ASHRAE 41.6–2014, ‘‘Standard Method
for Humidity Measurement.’’
(4) Update the definitions to reflect
the changes in ANSI/ASHRAE 103–
2017 as compared to ANSI/ASHRAE
103–1993.
(5) Provide corrections to erroneous
calculations and add clarifications to
test conditions and setup requirements.
DOE is also removing the definition of
outdoor furnace or boiler from 10 CFR
430.2.
DOE has determined that the
amendments adopted in this final rule
will not substantively impact the
measured efficiency of consumer boilers
or require retesting or recertification
solely as a result of DOE’s adoption of
the amendments to the test procedures.
As outlined in Table II.1 of this final
rule, the new appendix EE includes all
provisions currently included in
appendix N relevant to consumer
boilers, with modifications to:
harmonize with industry standard
updates; provide corrections to
erroneous calculations; and add
clarifications to test conditions and
setup requirements. Additionally, the
update to use more representative cycle
timings and oversize factors in the new
appendix EE test procedure was
demonstrated to have minimal impact
on AFUE ratings as a result of testing.
See section III.K of this final rule for
additional details on test procedure
costs. DOE also determined that the
amendments would not increase the
testing costs or burden associated with
the DOE test procedure for consumer
boilers, as the cost to test consumer
boilers under the amended test
procedure is $3,600, the same as the
cost to test consumer boilers under the
existing test procedure.
Therefore, DOE concludes that the
cost effects accruing from the final rule
would not have a ‘‘significant economic
impact on a substantial number of small
entities,’’ and that the preparation of a
FRFA is not warranted.
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of consumer boilers
must certify to DOE that their products
comply with any applicable energy
conservation standards. To certify
compliance, manufacturers must first
obtain test data for their products
according to the DOE test procedures,
including any amendments adopted for
those test procedures. DOE has
established regulations for the
certification and recordkeeping
requirements for all covered consumer
products and commercial equipment,
including consumer boilers. (See
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
generally 10 CFR part 429.) The
collection-of-information requirement
for the certification and recordkeeping
is subject to review and approval by
OMB under the Paperwork Reduction
Act (PRA). This requirement has been
approved by OMB under OMB control
number 1910–1400. Public reporting
burden for the certification is estimated
to average 35 hours per response,
including the time for reviewing
instructions, searching existing data
sources, gathering and maintaining the
data needed, and completing and
reviewing the collection of information.
DOE is not amending the certification
or reporting requirements for consumer
boilers in this final rule.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
ddrumheller on DSK120RN23PROD with RULES2
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE establishes test
procedure amendments that it expects
will be used to develop and implement
future energy conservation standards for
consumer boilers. DOE has determined
that this rule falls into a class of actions
that are categorically excluded from
review under the National
Environmental Policy Act of 1969 (42
U.S.C. 4321 et seq.) and DOE’s
implementing regulations at 10 CFR part
1021. Specifically, DOE has determined
that adopting test procedures for
measuring energy efficiency of
consumer products and industrial
equipment is consistent with activities
identified in 10 CFR part 1021,
appendix A to subpart D, A5 and A6.
Accordingly, neither an environmental
assessment nor an environmental
impact statement is required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive order also requires agencies to
have an accountable process to ensure
meaningful and timely input by State
and local officials in the development of
regulatory policies that have federalism
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
implications. On March 14, 2000, DOE
published a statement of policy
describing the intergovernmental
consultation process it will follow in the
development of such regulations. 65 FR
13735. DOE examined this final rule
and determined that it will not have a
substantial direct effect on the States, on
the relationship between the national
government and the States, or on the
distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
final rule. States can petition DOE for
exemption from such preemption to the
extent, and based on criteria, set forth in
EPCA. (42 U.S.C. 6297(d)) No further
action is required by Executive Order
13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that executive agencies make
every reasonable effort to ensure that the
regulation: (1) clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (‘‘UMRA’’) requires
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
15535
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
regulatory action resulting in a rule that
may cause the expenditure by State,
local, and Tribal governments, in the
aggregate, or by the private sector, of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820; also available at energy.gov/gc/
office-general-counsel. DOE examined
this final rule according to UMRA and
its statement of policy and determined
that the rule contains neither an
intergovernmental mandate, nor a
mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
final rule will not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
E:\FR\FM\13MRR2.SGM
13MRR2
15536
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). Pursuant to OMB
Memorandum M–19–15, Improving
Implementation of the Information
Quality Act (April 24, 2019), DOE
published updated guidelines which are
available at energy.gov/sites/prod/files/
2019/12/f70/DOE%20
Final%20Updated
%20IQA%20Guidelines%20
Dec%202019.pdf. DOE has reviewed
this final rule under the OMB and DOE
guidelines and has concluded that it is
consistent with applicable policies in
those guidelines.
ddrumheller on DSK120RN23PROD with RULES2
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that: (1) is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use if the
regulation is implemented, and of
reasonable alternatives to the action and
its expected benefits on energy supply,
distribution, and use.
This regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; ‘‘FEAA’’) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (‘‘FTC’’)
concerning the impact of the
commercial or industry standards on
competition.
The modifications to the test
procedure for consumer boilers adopted
in this final rule incorporates testing
methods contained in certain sections of
the following commercial standards:
ASHRAE Standard 103–2017, ASTM
D2156–09 (R2018), and ASHRAE
Standard 41.6–2014. DOE has evaluated
these standards and is unable to
conclude whether it fully complies with
the requirements of section 32(b) of the
FEAA (i.e., whether it was developed in
a manner that fully provides for public
participation, comment, and review.)
DOE has consulted with both the
Attorney General and the Chairman of
the FTC about the impact on
competition of using the methods
contained in these standards and has
received no comments objecting to their
use.
ASHRAE 41.6–2014 is an industry
accepted test standard that includes
instructions for measuring the relative
humidity of test chamber air.
Specifically, the test procedure codified
by this final rule references sections of
ASHRAE 103–2017 that in turn
reference ASHRAE 41.6–2014 for air
humidity measurement instructions.
These test standards are all readily
available from ANSI (webstore.ansi.org)
or ASHRAE (www.ashrae.org).
ASTM D2156–09 (R2018) is an
industry accepted test standard that
includes instructions for determining
the amount of smoke produced by an oil
burner to ensure the burner is adjusted
properly. Specifically, the test
procedure codified by this final rule
references sections of ASTM D2156–09
(R2018) for these instructions.
This test standard is readily available
from ASTM International
(www.astm.org).
IEC 62301 is an industry-accepted test
procedure for measuring standby mode
and off mode energy consumption. The
test procedure codified by this final rule
references IEC 62301 for performing the
standby mode and off mode power
measurements for consumer boilers.
This test standard is readily available
from IEC (webstore.iec.ch).
The following standards included in
the regulatory text were previously
approved for incorporation by reference
for the locations in which they appear
in this final rule: ANSI/ASHRAE 103–
1993, and ASTM D2156–09
(Reapproved 2013).
V. Approval of the Office of the
Secretary
The Secretary of Energy has approved
publication of this final rule.
M. Congressional Notification
List of Subjects
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Intergovernmental relations, Reporting
and recordkeeping requirements, Small
businesses.
N. Description of Materials Incorporated
by Reference
ASHRAE 103–2017 is an industry
accepted test standard that provides
procedures for determining the annual
fuel utilization efficiency of consumer
furnaces and boilers. Specifically, the
test procedure codified by this final rule
references sections of ASHRAE 103–
2017 for definitions, classifications,
requirements, instruments, methods of
testing, testing procedures,
nomenclature, and calculations for
determining the AFUE of consumer
boilers.
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
10 CFR Part 430
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Small
businesses.
Signing Authority
This document of the Department of
Energy was signed on February 21,
2023, by Francisco Alejandro Moreno,
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
Acting Assistant Secretary for Energy
Efficiency and Renewable Energy. That
document with the original signature
and date is maintained by DOE. For
administrative purposes only, and in
compliance with requirements of the
Office of the Federal Register, the
undersigned DOE Federal Register
Liaison Officer has been authorized to
sign and submit the document in
electronic format for publication, as an
official document of the Department of
Energy. This administrative process in
no way alters the legal effect of this
document upon publication in the
Federal Register.
Signed in Washington, DC, on February 22,
2023.
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
For the reasons stated in the
preamble, DOE amends parts 429 and
430 of chapter II of title 10, Code of
Federal Regulations as set forth below:
PART 429—CERTIFICATION
COMPLIANCE AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
[Amended]
2. Section 429.134 is amended by:
a. In paragraph (h) introductory text,
removing the words ‘‘appendix N’’ and
adding in their place the word
‘‘appendix EE’’;
■ b. In paragraph (h)(1)(i)(A), removing
the words ‘‘section 6 of appendix N’’
and adding in their place the words
‘‘section 6 of appendix EE’’; and
■ c. In paragraph (h)(2)(i)(A), removing
the words ‘‘appendix N’’ and adding in
their place the words ‘‘appendix EE’’.
■
■
PART 430—ENERGY CONSERVATION
PROGRAM FOR CONSUMER
PRODUCTS
3. The authority citation for part 430
continues to read as follows:
■
ddrumheller on DSK120RN23PROD with RULES2
Authority: 42 U.S.C. 6291–6309; 28 U.S.C.
2461 note.
[Amended]
4. Section 430.2 is amended by
removing the definition of ‘‘Outdoor
furnace or boiler’’.
■ 5. Section 430.3 is amended by:
■ a. In paragraph (g)(11), removing the
words ‘‘appendix F’’ and adding in their
place the words ‘‘appendices F and EE’’;
■
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
*
*
*
*
*
(j) ATSM. ASTM International, 100
Barr Harbor Drive, Post Office Box C700,
West Conshohocken, PA 19428–2959,
(877) 909–2786, www.astm.org.
*
*
*
*
*
■ 6. Section 430.23 is amended by
revising paragraph (n) to read as
follows:
*
1. The authority citation for part 429
continues to read as follows:
§ 430.2
§ 430.3 Materials incorporated by
reference.
§ 430.23 Test Procedures for the
measurement of energy and water
consumption.
■
§ 429.134
b. In paragraph (g)(17), removing the
words ‘‘appendix O’’ and adding in
their place the words ‘‘§ 430.23 and
appendices O and EE’’;
■ c. Revising paragraph (j) introductory
text;
■ d. In paragraph (j)(3), removing the
words ‘‘appendix O’’ and adding in
their place the words ‘‘appendices O
and EE’’; and
■ e. In paragraph (p)(7), removing the
text ‘‘CC, and FF’’ and adding in their
place ‘‘CC, EE, and FF’’.
The revision reads as follows:
■
*
*
*
*
(n) Furnaces. (1) The estimated
annual operating cost for furnaces is the
sum of:
(i) The product of the average annual
fuel energy consumption, in Btu’s per
year for gas or oil furnaces or in
kilowatt-hours per year for electric
furnaces, determined according to
section 10.2.2 or 10.3 of appendix N of
this subpart, respectively, (for furnaces,
excluding low pressure steam or hot
water boilers and electric boilers) or
section 10.2.2 or 10.3 of appendix EE of
this subpart, respectively (for low
pressure steam or hot water boilers and
electric boilers), and the representative
average unit cost in dollars per Btu for
gas or oil, or dollars per kilowatt-hour
for electric, as appropriate, as provided
pursuant to section 323(b)(2) of the Act;
plus
(ii) The product of the average annual
auxiliary electric energy consumption in
kilowatt-hours per year determined
according to section 10.2.3 of appendix
N of this subpart (for furnaces,
excluding low pressure steam or hot
water boilers and electric boilers) or
section 10.2.3 of appendix EE of this
subpart (for low pressure steam or hot
water boilers and electric boilers) of this
subpart, and the representative average
unit cost in dollars per kilowatt-hour as
provided pursuant to section 323(b)(2)
of the Act.
(iii) Round the resulting sum to the
nearest dollar per year.
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
15537
(2) The annual fuel utilization
efficiency (AFUE) for furnaces,
expressed in percent, is the ratio of the
annual fuel output of useful energy
delivered to the heated space to the
annual fuel energy input to the furnace.
(i) For gas and oil furnaces, determine
AFUE according to section 10.1 of
appendix N (for furnaces, excluding low
pressure steam or hot water boilers and
electric boilers) or section 10.1 of
appendix EE (for low pressure steam or
hot water boilers and electric boilers) of
this subpart, as applicable.
(ii) For electric furnaces, excluding
electric boilers, determine AFUE in
accordance with section 11.1 of ANSI/
ASHRAE 103–1993 (incorporated by
reference, see § 430.3); for electric
boilers, determine AFUE in accordance
with section 11.1 of ANSI/ASHRAE
103–2017 (incorporated by reference,
see § 430.3).
(iii) Round the AFUE to one-tenth of
a percentage point.
(3) The estimated regional annual
operating cost for furnaces is calculated
as follows:
(i) When using appendix N of this
subpart for furnaces excluding low
pressure steam or hot water boilers and
electric boilers (see the note at the
beginning of appendix N of this
subpart),
(A) For gas or oil-fueled furnaces,
(EFR × CBTU) + (EAER × CKWH)
Where:
EFR = the regional annual fuel energy
consumption in Btu per year, determined
according to section 10.7.1 of appendix
N of this subpart;
CBTU = the representative average unit cost in
dollars per Btu of gas or oil, as provided
pursuant to section 323(b)(2) of the Act;
EAER = the regional annual auxiliary
electrical energy consumption in
kilowatt-hours per year, determined
according to section 10.7.2 of appendix
N of this subpart; and
CKWH = the representative average unit cost
in dollars per kilowatt-hour of
electricity, as provided pursuant to
section 323(b)(2) of the Act.
(B) For electric furnaces,
(EER × CKWH)
Where:
EER = the regional annual fuel energy
consumption in kilowatt-hours per year,
determined according to section 10.7.3 of
appendix N of this subpart; and
CKWH is as defined in paragraph (n)(3)(i)(A)
of this section.
(ii) When using appendix EE of this
subpart for low pressure steam or hot
water boilers and electric boilers (see
the note at the beginning of appendix EE
of this subpart),
(A) For gas or oil-fueled boilers,
(EER × CBTU) + (EAER × CKWH)
E:\FR\FM\13MRR2.SGM
13MRR2
15538
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
Where:
EFR = the regional annual fuel energy
consumption in Btu per year, determined
according to section 10.5.1 of appendix
EE of this subpart;
CBTU and CKWH are as defined in paragraph
(n)(3)(i)(A) of this section; and
EAER = the regional annual auxiliary
electrical energy consumption in
kilowatt-hours per year, determined
according to section 10.5.2 of appendix
EE of this subpart.
(B) For electric boilers,
(EER × CKWH)
ddrumheller on DSK120RN23PROD with RULES2
Where:
EER = the regional annual fuel energy
consumption in kilowatt-hours per year,
determined according to section 10.5.3 of
appendix EE of this subpart; and
CKWH is as defined in paragraph (n)(3)(i)(A)
of this section.
(iii) Round the estimated regional
annual operating cost to the nearest
dollar per year.
(4) The energy factor for furnaces,
expressed in percent, is the ratio of
annual fuel output of useful energy
delivered to the heated space to the total
annual energy input to the furnace
determined according to either section
10.6 of appendix N of this subpart (for
furnaces, excluding low pressure steam
or hot water boilers and electric boilers)
or section 10.4 of appendix EE of this
subpart (for low pressure steam or hot
water boilers and electric boilers), as
applicable.
(5) The average standby mode and off
mode electrical power consumption for
furnaces shall be determined according
to section 8.10 of appendix N of this
subpart (for furnaces, excluding low
pressure steam or hot water boilers and
electric boilers) or section 8.9 of
appendix EE of this subpart (for low
pressure steam or hot water boilers and
electric boilers), as applicable. Round
the average standby mode and off mode
electrical power consumption to the
nearest tenth of a watt.
(6) Other useful measures of energy
consumption for furnaces shall be those
measures of energy consumption which
the Secretary determines are likely to
assist consumers in making purchasing
decisions and which are derived from
the application of appendix N of this
subpart (for furnaces, excluding low
pressure steam or hot water boilers and
electric boilers) or appendix EE of this
subpart (for low pressure steam or hot
water boilers and electric boilers).
*
*
*
*
*
7. Appendix N to subpart B of part
430 is revised to read as follows:
■
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
Appendix N to Subpart B of Part 430—
Uniform Test Method for Measuring the
Energy Consumption of Consumer
Furnaces Other Than Boilers
0. Incorporation by Reference
DOE incorporated by reference in
§ 430.3, the entire standards for ASTM
D2156R13 and IEC 62301. DOE also
incorporated selected provisions of
ASHRAE 103–1993.
1. Scope. The scope of this appendix
is as specified in section 2 of ASHRAE
103–1993 as it pertains to furnaces other
than low pressure steam or hot water
boilers or to electric boilers. Low
pressure steam or hot water boilers and
electric boilers are addressed in
appendix EE of this subpart.
2. Definitions. Definitions include
those specified in section 3 of ASHRAE
103–1993 and the following additional
and modified definitions.
Active mode means the condition in
which the furnace is connected to the
power source, and at least one of the
burner, electric resistance elements, or
any electrical auxiliaries such as
blowers, are activated.
Control means a device used to
regulate the operation of a piece of
equipment and the supply of fuel,
electricity, air, or water.
Draft inducer means a fan
incorporated in the furnace that either
draws or forces air into the combustion
chamber.
Gas valve means an automatic or
semi-automatic device consisting
essentially of a valve and operator that
controls the gas supply to the burner(s)
during normal operation of an
appliance. The operator may be actuated
by application of gas pressure on a
flexible diaphragm, by electrical means,
by mechanical means or by other means.
Installation and operation (I&O)
manual means instructions for
installing, commissioning, and
operating the furnace, which are
supplied with the product when
shipped by the manufacturer.
Isolated combustion system means a
system where a unit is installed within
the structure, but isolated from the
heated space. A portion of the jacket
heat from the unit is lost, and air for
ventilation, combustion and draft
control comes from outside the heated
space.
Multi-position furnace means a
furnace that can be installed in more
than one airflow configuration (i.e.,
upflow or horizontal; downflow or
horizontal; upflow or downflow; and
upflow, or downflow, or horizontal).
Off mode means a mode in which the
furnace is connected to a mains power
source and is not providing any active
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
mode or standby mode function, and
where the mode may persist for an
indefinite time. The existence of an off
switch in off position (a disconnected
circuit) is included within the
classification of off mode.
Off switch means the switch on the
furnace that, when activated, results in
a measurable change in energy
consumption between the standby and
off modes.
Oil control valve means an
automatically or manually operated
device consisting of an oil valve for
controlling the fuel supply to a burner
to regulate burner input.
Standby mode means any mode in
which the furnace is connected to a
mains power source and offers one or
more of the following space heating
functions that may persist:
(a) Activation of other modes
(including activation or deactivation of
active mode) by remote switch
(including thermostat or remote
control), internal or external sensors,
and/or timer; and
(b) Continuous functions, including
information or status displays or sensorbased functions.
Thermal stack damper means a type
of stack damper that relies exclusively
upon the changes in temperature in the
stack gases to open or close the damper.
3. Classifications. Classifications are
as specified in section 4 of ASHRAE
103–1993 for furnaces.
4. Requirements. Requirements are as
specified in section 5 of ASHRAE 103–
1993 for furnaces.
5. Instruments. Instruments must be
as specified in section 6 of ASHRAE
103–1993.
6. Apparatus. The apparatus used in
conjunction with the furnace during the
testing must be as specified in section
7 of ASHRAE 103–1993 (except for the
excluded sub-sections as enumerated at
§ 430.3(g)(15)); and as specified in
sections 6.1 through 6.5 of this
appendix.
6.1 General.
(a) Install the furnace in the test room
in accordance with the I&O manual, as
defined in section 2.6 of this appendix,
except that if provisions within this
appendix are specified, then the
provisions herein drafted and
prescribed by DOE govern. If the I&O
manual and any additional provisions of
this appendix are not sufficient for
testing a furnace, the manufacturer must
request a waiver from the test procedure
pursuant to § 430.27.
(b) If the I&O manual indicates the
unit should not be installed with a
return duct, then the return (inlet) duct
specified in section 7.2.1 of ASHRAE
103–1993 is not required.
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
(c) Test multi-position furnaces in the
least efficient configuration. Testing of
multi-position furnaces in other
configurations is permitted if energy use
or efficiency is represented pursuant to
the requirements in 10 CFR part 429.
(d) The apparatuses described in
section 6 of this appendix are used in
conjunction with the furnace during
testing. Each piece of apparatus shall
conform to material and construction
specifications listed in this appendix
and in ASHRAE 103–1993, and the
reference standards cited in this
appendix and in ASHRAE 103–1993.
(e) Test rooms containing equipment
must have suitable facilities for
providing the utilities (including but not
limited to environmental controls,
applicable measurement equipment,
and any other technology or tools)
necessary for performance of the test
and must be able to maintain conditions
within the limits specified in section 6
of this appendix.
6.2 Forced-air central furnaces
(direct vent and direct exhaust).
(a) Units not equipped with a draft
hood or draft diverter must be provided
with the minimum-length vent
configuration recommended in the I&O
manual or a 5-ft flue pipe if there is no
recommendation provided in the I&O
manual (see Figure 4 of ASHRAE 103–
1993). For a direct exhaust system,
insulate the minimum-length vent
configuration or the 5-ft flue pipe with
insulation having an R-value not less
than 7 and an outer layer of aluminum
foil. For a direct vent system, see section
7.5 of ASHRAE 103–1993 for insulation
requirements.
(b) For units with power burners,
cover the flue collection box with
insulation having an R-value of not less
than 7 and an outer layer of aluminum
foil before the cool-down and heat-up
tests described in sections 9.5 and 9.6 of
ASHRAE 103–1993, respectively.
However, do not apply the insulation
for the jacket loss test (if conducted)
described in section 8.6 of ASHRAE
103–1993 or the steady-state test
described in section 9.1 of ASHRAE
103–1993.
(c) For power-vented units, insulate
the shroud surrounding the blower
impeller with insulation having an
R-value of not less than 7 and an outer
layer of aluminum foil before the cooldown and heat-up tests described in
sections 9.5 and 9.6, respectively, of
ASHRAE 103–1993. However, do not
apply the insulation for the jacket loss
test (if conducted) described in section
8.6 of ASHRAE 103–1993 or the steadystate test described in section 9.1 of
ASHRAE 103–1993. Do not insulate the
blower motor or block the airflow
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
openings that facilitate the cooling of
the combustion blower motor or
bearings.
6.3 Downflow furnaces. Install an
internal section of vent pipe the same
size as the flue collar for connecting the
flue collar to the top of the unit, if not
supplied by the manufacturer. However,
do not insulate the internal vent pipe
during the jacket loss test (if conducted)
described in section 8.6 of ASHRAE
103–1993 or the steady-state test
described in section 9.1 of ASHRAE
103–1993. Do not insulate the internal
vent pipe before the cool-down and
heat-up tests described in sections 9.5
and 9.6, respectively, of ASHRAE 103–
1993. If the vent pipe is surrounded by
a metal jacket, do not insulate the metal
jacket. Install a 5-ft test stack of the
same cross-sectional area or perimeter
as the vent pipe above the top of the
furnace. Tape or seal around the
junction connecting the vent pipe and
the 5-ft test stack. Insulate the 5-ft test
stack with insulation having an R-value
not less than 7 and an outer layer of
aluminum foil. (See Figure 3–E of
ASHRAE 103–1993.)
6.4 Units with draft hoods or draft
diverters. Install the stack damper in
accordance with the I&O manual. Install
5 feet of stack above the damper.
(a) For units with an integral draft
diverter, cover the 5-ft stack with
insulation having an R-value of not less
than 7 and an outer layer of aluminum
foil.
(b) For units with draft hoods,
insulate the flue pipe between the outlet
of the furnace and the draft hood with
insulation having an R-value of not less
than 7 and an outer layer of aluminum
foil.
(c) For units with integral draft
diverters that are mounted in an
exposed position (not inside the overall
unit cabinet), cover the diverter boxes
(excluding any openings through which
draft relief air flows) before the
beginning of any test (including jacket
loss test) with insulation having an Rvalue of not less than 7 and an outer
layer of aluminum foil.
(d) For units equipped with integral
draft diverters that are enclosed within
the overall unit cabinet, insulate the
draft diverter box with insulation as
described in section 6.4.c before the
cool-down and heat-up tests described
in sections 9.5 and 9.6, respectively, of
ASHRAE 103–1993. However, do not
apply the insulation for the jacket loss
test (if conducted) described in section
8.6 of ASHRAE 103–1993 or the steadystate test described in section 9.1 of
ASHRAE 103–1993.
6.5 Condensate collection. Attach
condensate drain lines to the unit as
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
15539
specified in the I&O manual. Maintain
a continuous downward slope of drain
lines from the unit. Additional
precautions (such as eliminating any
line configuration or position that
would otherwise restrict or block the
flow of condensate or checking to
ensure a proper connection with
condensate drain spout that allows for
unobstructed flow) must be taken to
facilitate uninterrupted flow of
condensate during the test. Collection
containers must be glass or polished
stainless steel to facilitate removal of
interior deposits. The collection
container must have a vent opening to
the atmosphere.
7. Testing conditions. The testing
conditions must be as specified in
section 8 of ASHRAE 103–1993 (except
for the excluded sub-sections as
enumerated at § 430.3(g)(15)); and as
specified in sections 7.1 to 7.9 of this
appendix, respectively.
7.1 Fuel supply, gas. In conducting
the tests specified herein, gases with
characteristics as shown in Table 1 of
ASHRAE 103–1993 shall be used.
Maintain the gas supply, ahead of all
controls for a furnace, at a test pressure
between the normal and increased
values shown in Table 1 of ASHRAE
103–1993. Maintain the regulator outlet
pressure at a level approximating that
recommended in the I&O manual, as
defined in section 2.6 of this appendix,
or, in the absence of such
recommendation, to the nominal
regulator settings used when the
product is shipped by the manufacturer.
Use a gas having a specific gravity as
shown in Table 1 of ASHRAE 103–1993
and with a higher heating value within
±5% of the higher heating value shown
in Table 1 of ASHRAE 103–1993.
Determine the actual higher heating
value in Btu per standard cubic foot for
the gas to be used in the test within an
error no greater than 1%.
7.2 Gas burner. Adjust the burners
of gas-fired furnaces to their maximum
Btu input ratings at the normal test
pressure specified by section 7.1 of this
appendix. Correct the burner input rate
to reflect gas characteristics at a
temperature of 60 °F and atmospheric
pressure of 30 in of Hg and adjust down
to within ±2 percent of the hourly Btu
nameplate input rating specified by the
manufacturer as measured during the
steady-state performance test in section
8 of this appendix. Set the primary air
shutters in accordance with the I&O
manual to give a good flame at this
condition. If, however, the setting
results in the deposit of carbon on the
burners during any test specified herein,
the tester shall adjust the shutters and
burners until no more carbon is
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
15540
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
deposited and shall perform the tests
again with the new settings (see Figure
9 of ASHRAE 103–1993). After the
steady-state performance test has been
started, do not make additional
adjustments to the burners during the
required series of performance tests
specified in section 9 of ASHRAE 103–
1993. If a vent-limiting means is
provided on a gas pressure regulator,
keep it in place during all tests.
7.3 Modulating gas burner
adjustment at reduced input rate. For
gas-fired furnaces equipped with
modulating-type controls, adjust the
controls to operate the unit at the
nameplate minimum input rate. If the
modulating control is of a nonautomatic type, adjust the control to the
setting recommended in the I&O
manual. In the absence of such
recommendation, the midpoint setting
of the non-automatic control shall be
used as the setting for determining the
reduced fuel input rate. Start the
furnace by turning the safety control
valve to the ‘‘ON’’ position.
7.4 Oil burner. Adjust the burners of
oil-fired furnaces to give a CO2 reading
specified in the I&O manual and an
hourly Btu input during the steady-state
performance test described in section 8
of this appendix. Ensure the hourly BTU
input is within ±2% of the normal
hourly Btu input rating as specified in
the I&O manual. Smoke in the flue may
not exceed a No. 1 smoke during the
steady-state performance test as
measured by the procedure in ASTM
D2156R13). Maintain the average draft
over the fire and in the flue during the
steady-state performance test at the
value specified in the I&O manual. Do
not allow draft fluctuations exceeding
0.005 in. water. Do not make additional
adjustments to the burner during the
required series of performance tests. The
instruments and measuring apparatus
for this test are described in section 6 of
this appendix and shown in Figure 8 of
ASHRAE 103–1993.
7.5 Temperature Rise Targets.
Adjust air throughputs to achieve a
temperature rise that is the higher of a
and b, below, unless c applies. A
tolerance of ±2 °F is permitted.
(a) 15 °F less than the nameplate
maximum temperature rise or
(b) 15 °F higher than the minimum
temperature rise specified in the I&O
manual.
(c) A furnace with a non-adjustable air
temperature rise range and an
automatically controlled airflow that
does not permit a temperature rise range
of 30 °F or more must be tested at the
midpoint of the rise range.
7.6 Temperature Rise Adjustments.
Establish the temperature rise specified
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
in section 7.5 of this appendix by
adjusting the circulating airflow. This
adjustment must be accomplished by
symmetrically restricting the outlet air
duct and varying blower speed selection
to obtain the desired temperature rise
and minimum external static pressure,
as specified in Table 4 of ASHRAE 103–
1993. If the required temperature rise
cannot be obtained at the minimum
specified external static pressure by
adjusting blower speed selection and
duct outlet restriction, then the
following applies.
(a) If the resultant temperature rise is
less than the required temperature rise,
vary the blower speed by gradually
adjusting the blower voltage so as to
maintain the minimum external static
pressure listed in Table 4 of ASHRAE
103–1993. The airflow restrictions shall
then remain unchanged. If static
pressure must be varied to prevent
unstable blower operation, then increase
the static pressure until blower
operation is stabilized, except that the
static pressure must not exceed the
maximum external static pressure as
specified by the manufacturer in the
I&O manual.
(b) If the resultant temperature rise is
greater than the required temperature
rise, then the unit can be tested at a
higher temperature rise value, but one
not greater than nameplate maximum
temperature rise. In order not to exceed
the maximum temperature rise, the
speed of a direct-driven blower may be
increased by increasing the circulating
air blower motor voltage.
7.7 Measurement of jacket surface
temperature. Divide the jacket of the
furnace into 6-inch squares when
practical, and otherwise into 36-squareinch regions comprising 4-inch by 9inch or 3-inch by 12-inch sections, and
determine the surface temperature at the
center of each square or section with a
surface thermocouple. Record the
surface temperature of the 36-squareinch areas in groups where the
temperature differential of the 36square-inch areas is less than 10 °F for
temperature up to 100 °F above room
temperature, and less than 20 °F for
temperatures more than 100 °F above
room temperature. For forced-air central
furnaces, the circulating air blower
compartment is considered as part of
the duct system, and no surface
temperature measurement of the blower
compartment needs to be recorded for
the purpose of this test. For downflow
furnaces, measure all cabinet surface
temperatures of the heat exchanger and
combustion section, including the
bottom around the outlet duct and the
burner door, using the 36-square-inch
thermocouple grid. The cabinet surface
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
temperatures around the blower section
do not need to be measured (See Figure
3–E of ASHRAE 103–1993).
7.8 Installation of vent system. Keep
the vent or air intake system supplied
by the manufacturer in place during all
tests. Test units intended for installation
with a variety of vent pipe lengths with
the minimum vent length as specified in
the I&O manual, or a 5-ft. flue pipe if
there are no recommendations in the
I&O manual. Do not connect a furnace
employing a direct vent system to a
chimney or induced-draft source. Vent
combustion products solely by using the
venting incorporated in the furnace and
the vent or air intake system supplied
by the manufacturer. For units that are
not designed to significantly preheat the
incoming air, see section 7.4 of this
appendix and Figure 4a or 4b of
ASHRAE 103–1993. For units that do
significantly preheat the incoming air,
see Figure 4c or 4d of ASHRAE 103–
1993.
7.9 Additional optional method of
testing for determining DP and DF for
furnaces. On units whose design is such
that there is no measurable airflow
through the combustion chamber and
heat exchanger when the burner(s) is
(are) off as determined by the optional
test procedure in section 7.9.1 of this
appendix, DF and DP may be set equal
to 0.05.
7.9.1 Optional test method for
indicating the absence of flow through
the heat exchanger. Manufacturers may
use the following test protocol to
determine whether air flows through the
combustion chamber and heat
exchanger when the burner(s) is (are)
off. The minimum default draft factor
may be used only for units determined
pursuant to this protocol to have no
airflow through the combustion
chamber and heat exchanger.
7.9.1.1 Test apparatus. Use a smoke
stick that produces smoke that is easily
visible and has a density less than or
approximately equal to air. Use a smoke
stick that produces smoke that is nontoxic to the test personnel and produces
gas that is unreactive with the
environment in the test chamber.
7.9.1.2 Test conditions. Minimize all
air currents and drafts in the test
chamber, including turning off
ventilation if the test chamber is
mechanically ventilated. Wait at least
two minutes following the termination
of the furnace on-cycle before beginning
the optional test method for indicating
the absence of flow through the heat
exchanger.
7.9.1.3 Location of the test
apparatus. After all air currents and
drafts in the test chamber have been
eliminated or minimized, position the
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
smoke stick based on the following
equipment configuration:
(a) For horizontal combustion air
intakes, approximately 4 inches from
the vertical plane at the termination of
the intake vent and 4 inches below the
bottom edge of the combustion air
intake; or
(b) for vertical combustion air intakes,
approximately 4 inches horizontal from
vent perimeter at the termination of the
intake vent and 4 inches down (parallel
to the vertical axis of the vent).
7.9.1.4 Duration of test. Establish the
presence of smoke from the smoke stick
and then monitor the direction of the
smoke flow for no less than 30 seconds.
7.9.1.5 Test results. During visual
assessment, determine whether there is
any draw of smoke into the combustion
air intake vent.
(a) If absolutely no smoke is drawn
into the combustion air intake, the
furnace meets the requirements to allow
use of the minimum default draft factor
pursuant to section 7.9 of this appendix.
(b) If there is any smoke drawn into
the intake, proceed with the methods of
testing as prescribed in section 8.8 of
ASHRAE 103–1993.
8. Test procedure. Conduct testing
and measurements as specified in
section 9 of ASHRAE 103–1993 (except
for the excluded sub-sections as
enumerated at § 430.3(g)(15)); and as
specified in sections 8.1 through 8.10 of
this appendix. Section 8.4 of this
appendix may be used in lieu of section
9.2 of ASHRAE 103–1993.
8.1 Fuel input. For gas units,
measure and record the steady-state gas
input rate in Btu/hr, including pilot gas,
corrected to standard conditions of 60 °F
and 30 in. Hg. Use measured values of
gas temperature and pressure at the
meter and barometric pressure to correct
the metered gas flow rate to the above
standard conditions. For oil units,
measure and record the steady-state fuel
input rate.
8.2 Electrical input. During the
steady-state test, perform a single
measurement of all of the electrical
power involved in burner operation
(PE), including energizing the ignition
system, controls, gas valve or oil control
valve, and draft inducer, if applicable.
During the steady-state test, perform a
single measurement of the electrical
power to the circulating air blower (BE).
8.3 Input to interrupted ignition
device. For burners equipped with an
interrupted ignition device, record the
nameplate electric power used by the
ignition device, PEIG, or record that PEIG
= 0.4 kW if no nameplate power input
is provided. Record the nameplate
ignition device on-time interval, tIG, or,
if the nameplate does not provide the
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
ignition device on-time interval,
measure the on-time interval with a
stopwatch at the beginning of the test,
starting when the burner is turned on.
Set tIG = 0 and PEIG = 0 if the device
on-time interval is less than or equal to
5 seconds after the burner is on.
8.4 Optional test procedures for
condensing furnaces, measurement of
condensate during the establishment of
steady-state conditions. For units with
step-modulating or two-stage controls,
conduct the test at both the maximum
and reduced inputs. In lieu of collecting
the condensate immediately after the
steady state conditions have been
reached as required by section 9.2 of
ASHRAE 103–1993, condensate may be
collected during the establishment of
steady state conditions as defined by
section 9.1.2.1 of ASHRAE 103–1993.
Perform condensate collection for at
least 30 minutes. Measure condensate
mass immediately at the end of the
collection period to prevent evaporation
loss from the sample. Record fuel input
for the 30-minute condensate collection
test period. Observe and record fuel
higher heating value (HHV),
temperature, and pressures necessary
for determining fuel energy input
(Qc,ss). Measure the fuel quantity and
HHV with errors no greater than 1%.
The humidity for the room air shall at
no time exceed 80%. Determine the
mass of condensate for the
establishment of steady state conditions
(Mc,ss) in pounds by subtracting the
tare container weight from the total
container and condensate weight
measured at the end of the 30-minute
condensate collection test period.
8.5 Cool-down test for gas- and oilfueled gravity and forced-air central
furnaces without stack dampers. Turn
off the main burner after completing
steady-state testing, and measure the
flue gas temperature by means of the
thermocouple grid described in section
7.6 of ASHRAE 103–1993 at 1.5 minutes
(TF,OFF(t3)) and 9 minutes (TF,OFF(t4))
after shutting off the burner. When
taking these temperature readings, the
integral draft diverter must remain
blocked and insulated, and the stack
restriction must remain in place. On
atmospheric systems with an integral
draft diverter or draft hood and
equipped with either an
electromechanical inlet damper or an
electromechanical flue damper that
closes within 10 seconds after the
burner shuts off to restrict the flow
through the heat exchanger in the offcycle, bypass or adjust the control for
the electromechanical damper so that
the damper remains open during the
cool-down test.
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
15541
For furnaces that employ post-purge,
measure the length of the post-purge
period with a stopwatch. Record the
time from burner ‘‘OFF’’ to combustion
blower ‘‘OFF’’ (electrically deenergized) as tP. If the measured tP is
less than or equal to 30 seconds, set tP
at 0 and conduct the cool-down test as
if there is no post-purge. If tP is
prescribed by the I&O manual or
measured to be greater than 180
seconds, stop the combustion blower at
180 seconds and use that value for tP.
Measure the flue gas temperature by
means of the thermocouple grid
described in section 7.6 of ASHRAE
103–1993 at the end of the post-purge
period, tP(TF,OFF (tP)), and at the time
(1.5 + tP) minutes (TF,OFF(t3)) and (9.0 +
tP) minutes (TF,OFF(t4)) after the main
burner shuts off.
8.6 Cool-down test for gas- and oilfueled gravity and forced-air central
furnaces without stack dampers and
with adjustable fan control. For a
furnace with adjustable fan control,
measure the time delay between burner
shutdown and blower shutdown, t+.
This time delay, t+, will be 3.0 minutes
for non-condensing furnaces or 1.5
minutes for condensing furnaces or
until the supply air temperature drops
to a value of 40 °F above the inlet air
temperature, whichever results in the
longest fan on-time. For a furnace
without adjustable fan control or with
the type of adjustable fan control whose
range of adjustment does not allow for
the time delay, t+, specified above,
bypass the fan control and manually
control the fan to allow for the
appropriate delay time as specified in
section 9.5.1.2 of ASHRAE 103–1993.
For a furnace that employs a single
motor to drive both the power burner
and the indoor air circulating blower,
the power burner and indoor air
circulating blower must be stopped at
the same time.
8.7 [Reserved]
8.8 Calculation options. The rate of
the flue gas mass flow through the
furnace and the factors DP, DF, and DS
are calculated by the equations in
sections 11.6.1, 11.6.2, 11.6.3, 11.6.4,
11.7.1, and 11.7.2 of ASHRAE 103–
1993. On units whose design is such
that there is no measurable airflow
through the combustion chamber and
heat exchanger when the burner(s) is
(are) off (as determined by the optional
test procedure in section 7.9 of this
appendix), DF and DP may be set equal
to 0.05.
8.9 Optional test procedures for
condensing furnaces that have no offperiod flue losses. For units that have
applied the test method in section 7.9 of
this appendix to determine that no
E:\FR\FM\13MRR2.SGM
13MRR2
15542
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
measurable airflow exists through the
combustion chamber and heat
exchanger during the burner off-period
and having post-purge periods of less
than 5 seconds, the cool-down and heatup tests specified in sections 9.5 and 9.6
of ASHRAE 103–1993 may be omitted.
In lieu of conducting the cool-down and
heat-up tests, the tester may use the
losses determined during the steadystate test described in section 9.1 of
ASHRAE 103–1993 when calculating
heating seasonal efficiency, EffyHS.
8.10 Measurement of electrical
standby and off mode power.
8.10.1 Standby power measurement.
With all electrical auxiliaries of the
furnace not activated, measure the
standby power (PW,SB) in accordance
with the procedures in IEC 62301,
except that section 8.5, Room Ambient
Temperature, of ASHRAE 103–1993 and
the voltage provision of section 8.2.1.4,
Electrical Supply, of ASHRAE 103–1993
shall apply in lieu of the corresponding
provisions of IEC 62301 at section 4.2,
Test room, and the voltage specification
of section 4.3, Power supply. Frequency
shall be 60Hz. Clarifying further, IEC
62301 section 4.4, Power measurement
instruments, and Section 5,
Measurements, apply in lieu of
ASHRAE 103–1993 section 6.10, Energy
Flow Rate. Measure the wattage so that
all possible standby mode wattage for
the entire appliance is recorded, not just
the standby mode wattage of a single
auxiliary. Round the recorded standby
power (PW,SB) to the second decimal
place, except for loads greater than or
equal to 10W, which must be recorded
to at least three significant figures.
8.10.2 Off mode power
measurement. If the unit is equipped
with an off switch or there is an
expected difference between off mode
power and standby mode power,
measure off mode power (PW,OFF) in
accordance with the standby power
procedures in IEC 62301, except that
section 8.5, Room Ambient
Temperature, of ASHRAE 103–1993 and
the voltage provision of section 8.2.1.4,
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
Electrical Supply, of ASHRAE 103–1993
shall apply in lieu of the corresponding
provisions of IEC 62301 at section 4.2,
Test room, and the voltage specification
of section 4.3, Power supply. Frequency
shall be 60Hz. Clarifying further, IEC
62301 section 4.4, Power measurement
instruments, and section 5,
Measurements, apply for this
measurement in lieu of ASHRAE 103–
1993 section 6.10, Energy Flow Rate.
Measure the wattage so that all possible
off mode wattage for the entire
appliance is recorded, not just the off
mode wattage of a single auxiliary. If
there is no expected difference in off
mode power and standby mode power,
let PW,OFF = PW,SB, in which case no
separate measurement of off mode
power is necessary. Round the recorded
off mode power (PW,OFF) to the second
decimal place, except for loads greater
than or equal to 10W, in which case
round the recorded value to at least
three significant figures.
9. Nomenclature. Nomenclature
includes the nomenclature specified in
section 10 of ASHRAE 103–1993 and
the following additional variables:
Effmotor = Efficiency of power burner
motor
PEIG = Electrical power to the
interrupted ignition device, kW
RT,a = RT,F if flue gas is measured
= RT,S if stack gas is measured
RT,F = Ratio of combustion air mass flow
rate to stoichiometric air mass flow
rate
RT,S = Ratio of the sum of combustion
air and relief air mass flow rate to
stoichiometric air mass flow rate
tIG = Electrical interrupted ignition
device on-time, min.
Ta,SS,X = TF,SS,X if flue gas temperature
is measured, °F
= TS,SS,X if stack gas temperature is
measured, °F
yIG = Ratio of electrical interrupted
ignition device on-time to average
burner on-time
yP = Ratio of power burner combustion
blower on-time to average burner ontime
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
ESO = Average annual electric standby
mode and off mode energy
consumption, in kilowatt-hours
PW,OFF = Furnace off mode power, in
watts
PW,SB = Furnace standby mode power,
in watts
10. Calculation of derived results from
test measurements. Perform calculations
as specified in section 11 of ASHRAE
103–1993 (except for the excluded subsections as enumerated at
§ 430.3(g)(15)); and as specified in
sections 10.1 through 10.11 and Figure
1 of this appendix.
10.1 Annual fuel utilization
efficiency. The annual fuel utilization
efficiency (AFUE) is as defined in
sections 11.2.12 (non-condensing
systems), 11.3.12 (condensing systems),
11.4.12 (non-condensing modulating
systems) and 11.5.12 (condensing
modulating systems) of ASHRAE 103–
1993, except for the definition for the
term EffyHS in the defining equation for
AFUE. EffyHS is defined as:
EffyHS = heating seasonal efficiency as
defined in sections 11.2.11 (noncondensing systems), 11.3.11
(condensing systems), 11.4.11 (noncondensing modulating systems) and
11.5.11 (condensing modulating
systems) of ASHRAE 103–1993,
except that for condensing
modulating systems sections 11.5.11.1
and 11.5.11.2 are replaced by sections
10.2 and 10.3 of this appendix. EffyHS
is based on the assumptions that all
weatherized warm air furnaces are
located outdoors and that nonweatherized warm air furnaces are
installed as isolated combustion
systems.
10.2 Part-load efficiency at reduced
fuel input rate. If the option in section
8.9 of this appendix is not employed,
calculate the part-load efficiency at the
reduced fuel input rate, EffyU,R, for
condensing furnaces equipped with
either step-modulating or two-stage
controls, expressed as a percent and
defined as:
E:\FR\FM\13MRR2.SGM
13MRR2
15543
Where:
LL,A = value as defined in section 11.2.7 of
ASHRAE 103–1993,
LG = value as defined in section 11.3.11.1 of
ASHRAE 103–1993, at reduced input
rate,
LC = value as defined in section 11.3.11.2 of
ASHRAE 103–1993 at reduced input
rate,
LJ = value as defined in section 11.4.8.1.1 of
ASHRAE 103–1993 at maximum input
rate,
tON = value as defined in section 11.4.9.11 of
ASHRAE 103–1993,
QP = pilot fuel input rate determined in
accordance with section 9.2 of ASHRAE
103–1993 in Btu/h,
QIN = value as defined in section 11.4.8.1.1
of ASHRAE 103–1993,
tOFF = value as defined in section 11.4.9.12
of ASHRAE 103–1993 at reduced input
rate,
LS,ON = value as defined in section 11.4.10.5
of ASHRAE 103–1993 at reduced input
rate,
LS,OFF = value as defined in section 11.4.10.6
of ASHRAE 103–1993 at reduced input
rate,
LI,ON = value as defined in section 11.4.10.7
of ASHRAE 103–1993 at reduced input
rate,
LI,OFF = value as defined in section 11.4.10.8
of ASHRAE 103–1993 at reduced input
rate,
CJ = jacket loss factor and equal to:
= 0.0 for furnaces intended to be installed
indoors
= 1.7 for furnaces intended to be installed as
isolated combustion systems
= 3.3 for furnaces intended to be installed
outdoors
LS,SS = value as defined in section 11.4.6 of
ASHRAE 103–1993 at reduced input
rate,
CS = value as defined in section 11.3.10.1 of
ASHRAE 103–1993 at reduced input
rate.
Where:
LL,A = value as defined in section 11.2.7 of
ASHRAE 103–1993,
LG = value as defined in section 11.3.11.1 of
ASHRAE 103–1993 at maximum input
rate,
LC = value as defined in section 11.3.11.2 of
ASHRAE 103–1993 at maximum input
rate,
LJ = value as defined in section 11.4.8.1.1 of
ASHRAE 103–1993 at maximum input
rate,
tON = value as defined in section 11.4.9.11 of
ASHRAE 103–1993,
QP = pilot fuel input rate determined in
accordance with section 9.2 of ASHRAE
103–1993 in Btu/h,
QIN = value as defined in section 11.4.8.1.1
of ASHRAE 103–1993,
tOFF = value as defined in section 11.4.9.12
of ASHRAE 103–1993 at maximum input
rate,
LS,ON = value as defined in section 11.4.10.5
of ASHRAE 103–1993 at maximum input
rate,
LS,OFF = value as defined in section 11.4.10.6
of ASHRAE 103–1993 at maximum input
rate,
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
PO 00000
Frm 00035
Fmt 4701
Sfmt 4700
E:\FR\FM\13MRR2.SGM
13MRR2
ER13MR23.002
10.3 Part-Load Efficiency at
Maximum Fuel Input Rate. If the option
in section 8.9 of this appendix is not
employed, calculate the part-load
efficiency at maximum fuel input rate,
EffyU,H, for condensing furnaces
equipped with two-stage controls,
expressed as a percent and defined as:
ER13MR23.001
ddrumheller on DSK120RN23PROD with RULES2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
15544
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
LI,ON = value as defined in section 11.4.10.7
of ASHRAE 103–1993 at maximum input
rate,
LI,OFF = value as defined in section 11.4.10.8
of ASHRAE 103–1993 at maximum input
rate,
CJ = value as defined in section 10.2 of this
appendix,
LS,SS = value as defined in section 11.4.6 of
ASHRAE 103–1993 at maximum input
rate,
CS = value as defined in section 11.4.10.1 of
ASHRAE 103–1993 at maximum input
rate.
ddrumheller on DSK120RN23PROD with RULES2
10.4 National average burner
operating hours, average annual fuel
energy consumption, and average
annual auxiliary electrical energy
consumption for gas or oil furnaces.
10.4.1 National average number of
burner operating hours. For furnaces
equipped with single-stage controls, the
national average number of burner
operating hours is defined as:
BOHSS = 2,080 (0.77) (A) DHR ¥ 2,080
(B)
Where:
2,080 = national average heating load hours
0.77 = adjustment factor to adjust the
calculated design heating requirement
and heating load hours to the actual
heating load experienced by the heating
system
A = 100,000/[341,200 (yP PE + yIG PEIG + y
BE) + (QIN ¥ QP) EffyHS], for forced draft
unit, indoors
= 100,000/[341,200 (yP PE Effmotor + yIG PEIG
+ y BE) + (QIN ¥ QP) EffyHS], for forced
draft unit, isolated combustion system,
= 100,000/[341,200 (yP PE (1 ¥ Effmotor) + yIG
PEIG + y BE) + (QIN ¥ QP) EffyHS], for
induced draft unit, indoors, and
= 100,000/[341,200 (yIG PEIG + y BE) + (QIN
¥ QP) EffyHS], for induced draft unit,
isolated combustion system.
DHR = typical design heating requirements as
listed in Table 8 (in kBtu/h) of ASHRAE
103–1993, using the proper value of
QOUT defined in section 11.2.8.1 of
ASHRAE 103–1993.
B = 2 QP (EffyHS) (A)/100,000
Where:
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
100,000 = factor that accounts for percent
and kBtu
yP = ratio of induced or forced draft blower
on-time to average burner on-time, as
follows:
1 for units without post-purge;
1 + (tP/3.87) for single stage furnaces with
post purge; or
1 + (tP/10) for two-stage and step modulating
furnaces with post purge.
PE = all electrical power related to burner
operation at full load steady-state
operation, including electrical ignition
device if energized, controls, gas valve or
oil control valve, and draft inducer, as
determined in section 8.2 of this
appendix.
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
yIG = ratio of burner interrupted ignition
device on-time to average burner ontime, as follows:
0 for burners not equipped with interrupted
ignition device;
(tIG/3.87) for single-stage furnaces; or
(tIG/10) for two-stage and step modulating
furnaces;
PEIG = electrical input rate to the interrupted
ignition device on burner (if employed),
as defined in section 8.3 of this appendix
y = ratio of blower on-time to average burner
on-time, as follows:
1 for furnaces without fan delay;
1 + (t+¥t¥)/3.87 for single-stage furnaces
with fan delay; or
1 + (t+¥t¥)/10 for two-stage and step
modulating furnaces with fan delay.
BE = circulating air fan electrical energy
input rate at full-load steady-state
operation as defined in section 8.2 of this
appendix.
tP = post-purge time as defined in section 8.5
of this appendix
= 0 if tP is equal to or less than 30 seconds
tIG = on-time of the burner interrupted
ignition device, as defined in section 8.3
of this appendix
QIN = as defined in section 11.2.8.1 of
ASHRAE 103–1993
QP = as defined in section 11.2.11 of
ASHRAE 103–1993
EffyHS = as defined in section 11.2.11 (noncondensing systems) or section 11.3.11.3
(condensing systems) of ASHRAE 103–
1993, percent, and calculated on the
basis of:
isolated combustion system installation, for
non-weatherized warm air furnaces; or
outdoor installation, for furnaces that are
weatherized.
2 = ratio of the average length of the heating
season in hours to the average heating
load hours
t+ = delay time between burner shutoff and
the blower shutoff measured as defined
in section 9.5.1.2 of ASHRAE 103–1993
t¥ = as defined in section 9.6.1 of ASHRAE
103–1993
10.4.1.1 For furnaces equipped with
two stage or step modulating controls
the average annual energy used during
the heating season, EM, is defined as:
EM = (QIN¥QP) BOHSS + (8,760¥4,600)
QP
Where:
QIN = as defined in section 11.4.8.1.1 of
ASHRAE 103–1993
QP = as defined in section 11.4.12 of
ASHRAE 103–1993
BOHSS = as defined in section 10.4.1 of this
appendix, in which the weighted EffyHS
as defined in section 11.4.11.3 or
11.5.11.3 of ASHRAE 103–1993 is used
for calculating the values of A and B, the
term DHR is based on the value of QOUT
defined in section 11.4.8.1.1 or 11.5.8.1.1
of ASHRAE 103–1993, and the term
(yPPE + yIGPEIG + yBE) in the factor A
is increased by the factor R, which is
defined as:
R = 2.3 for two stage controls
= 2.3 for step modulating controls when the
ratio of minimum-to-maximum output is
greater than or equal to 0.5
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
= 3.0 for step modulating controls when the
ratio of minimum-to-maximum output is
less than 0.5
A = 100,000/[341,200 (yP PE + yIG PEIG + y
BE) R + (QIN¥QP) EffyHS], for forced
draft unit, indoors
= 100,000/[341,200 (yP PE Effmotor + yIG PEIG
+ y BE) R + (QIN¥QP) EffyHS], for forced
draft unit, isolated combustion system,
= 100,000/[341,200 (yP PE (1¥Effmotor) + yIG
PEIG + y BE) R + (QIN¥QP) EffyHS], for
induced draft unit, indoors, and
= 100,000/[341,200 (yIG PEIG + y BE) R +
(QIN¥QP) EffyHS], for induced draft unit,
isolated combustion system.
Where:
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
EffyHS = as defined in section 11.4.11.3 or
11.5.11.3 of ASHRAE 103–1993, and
calculated on the basis of:
isolated combustion system installation, for
non-weatherized warm air furnaces; or
outdoor installation, for furnaces that are
weatherized.
8,760 = total number of hours per year
4,600 = as defined in section 11.4.12 of
ASHRAE 103–1993
10.4.1.2 For furnaces equipped with
two-stage or step-modulating controls,
the national average number of burner
operating hours at the reduced operating
mode (BOHR) is defined as:
BOHR = XR EM/QIN,R
Where:
XR = as defined in section 11.4.8.7 of
ASHRAE 103–1993
EM = as defined in section 10.4.1.1 of this
appendix
QIN,R = as defined in section 11.4.8.1.2 of
ASHRAE 103–1993
10.4.1.3 For furnaces equipped with
two-stage controls, the national average
number of burner operating hours at the
maximum operating mode (BOHH) is
defined as:
BOHH = XH EM/QIN
Where:
XH = as defined in section 11.4.8.6 of
ASHRAE 103–1993
EM = as defined in section 10.4.1.1 of this
appendix
QIN = as defined in section 11.4.8.1.1 of
ASHRAE 103–1993
10.4.1.4 For furnaces equipped with
step-modulating controls, the national
average number of burner operating
hours at the modulating operating mode
(BOHM) is defined as:
BOHM = XH EM/QIN,M
Where:
XH = as defined in section 11.4.8.6 of
ASHRAE 103–1993
EM = as defined in section 10.4.1.1 of this
appendix
QIN,M = QOUT,M/(EffySS,M/100)
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
QOUT,M = as defined in section 11.4.8.10 or
11.5.8.10 of ASHRAE 103–1993, as
appropriate
EffySS,M = as defined in section 11.4.8.8 or
11.5.8.8 of ASHRAE 103–1993, as
appropriate, in percent
100 = factor that accounts for percent
10.4.2 Average annual fuel energy
consumption for gas or oil fueled
furnaces. For furnaces equipped with
single-stage controls, the average annual
fuel energy consumption (EF) is
expressed in Btu per year and defined
as:
EF = BOHSS (QIN¥QP) + 8,760 QP
Where:
BOHSS = as defined in section 10.4.1 of this
appendix
QIN = as defined in section 11.2.8.1 of
ASHRAE 103–1993
QP = as defined in section 11.2.11 of
ASHRAE 103–1993
8,760 = as defined in section 10.4.1.1 of this
appendix
10.4.2.1 For furnaces equipped with
either two-stage or step modulating
controls, EF is defined as:
EF = EM + 4,600 QP
Where:
EM = as defined in section 10.4.1.1 of this
appendix
4,600 = as defined in section 11.4.12 of
ASHRAE 103–1993
QP = as defined in section 11.2.11 of
ASHRAE 103–1993
ddrumheller on DSK120RN23PROD with RULES2
10.4.2.2 [Reserved]
10.4.3 Average annual auxiliary
electrical energy consumption for gas or
oil-fueled furnaces. For furnaces
equipped with single-stage controls, the
average annual auxiliary electrical
consumption (EAE) is expressed in
kilowatt-hours and defined as:
EAE = BOHSS (yP PE + yIG PEIG + yBE)
+ ESO
Where:
BOHSS = as defined in section 10.4.1 of this
appendix
yP = as defined in section 10.4.1 of this
appendix
PE = as defined in section 10.4.1 of this
appendix
yIG = as defined in section 10.4.1 of this
appendix
PEIG = as defined in section 10.4.1 of this
appendix
y = as defined in section 10.4.1 of this
appendix
BE = as defined in section 10.4.1 of this
appendix
ESO = as defined in section 10.11 of this
appendix
10.4.3.1 For furnaces equipped with
two-stage controls, EAE is defined as:
EAE = BOHR (yP PER + yIG PEIG + yBER)
+ BOHH (yP PEH + yIG PEIG + y BEH)
+ ESO
Where:
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
BOHR = as defined in section 10.4.1.2 of this
appendix
yP = as defined in section 10.4.1 of this
appendix
PER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
yIG = as defined in section 10.4.1 of this
appendix
PEIG = as defined in section 10.4.1 of this
appendix
y = as defined in section 10.4.1 of this
appendix
BER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
BOHH = as defined in section 10.4.1.3 of this
appendix
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
ESO = as defined in section 10.11 of this
appendix
10.4.3.2 For furnaces equipped with
step-modulating controls, EAE is defined
as:
EAE = BOHR (yP PER + yIG PEIG + y BER)
+ BOHM (yP PEH + yIG PEIG + y BEH)
+ ESO
Where:
BOHR = as defined in section 10.4.1.2 of this
appendix
yP = as defined in section 10.4.1 of this
appendix
PER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
yIG = as defined in section 10.4.1 of this
appendix
PEIG = as defined in section 10.4.1 of this
appendix
y = as defined in section 10.4.1 of this
appendix
BER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
BOHM = as defined in 10.4.1.4 of this
appendix
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
ESO = as defined in section 10.11 of this
appendix
10.5 Average annual electric energy
consumption for electric furnaces. For
electric furnaces, the average annual
electrical energy consumption (EE) is
expressed in kilowatt-hours and defined
as:
EE = 100 (2,080) (0.77) DHR/(3.412
AFUE) + ESO
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this
appendix
0.77 = as defined in section 10.4.1 of this
appendix
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
15545
DHR = as defined in section 10.4.1 of this
appendix
3.412 = conversion factor from watt-hours to
Btu
AFUE = as defined in section 11.1 of
ASHRAE 103–1993, in percent, and
calculated on the basis of:
isolated combustion system installation, for
non-weatherized warm air furnaces; or
outdoor installation, for furnaces that are
weatherized.
ESO = as defined in section 10.11 of this
appendix.
10.6 Energy factor.
10.6.1 Energy factor for gas or oil
furnaces. Calculate the energy factor,
EF, for gas or oil furnaces defined as, in
percent:
EF = (EF¥4,600 (QP))(EffyHS)/(EF + 3,412
(EAE))
Where:
EF = average annual fuel consumption as
defined in section 10.4.2 of this
appendix
4,600 = as defined in section 11.4.12 of
ASHRAE 103–1993
QP = pilot fuel input rate determined in
accordance with section 9.2 of ASHRAE
103–1993 in Btu/h
EffyHS = annual fuel utilization efficiency as
defined in sections 11.2.11, 11.3.11,
11.4.11 or 11.5.11 of ASHRAE 103–1993,
in percent, and calculated on the basis
of:
isolated combustion system installation, for
non-weatherized warm air furnaces; or
outdoor installation, for furnaces that are
weatherized.
3,412 = conversion factor from kW to Btu/h
EAE = as defined in section 10.4.3 of this
appendix
10.6.2 Energy factor for electric
furnaces. The energy factor, EF, for
electric furnaces is defined as:
EF = AFUE
Where:
AFUE = annual fuel utilization efficiency as
defined in section 10.4.3 of this
appendix, in percent
10.7 Average annual energy
consumption for furnaces located in a
different geographic region of the
United States and in buildings with
different design heating requirements.
10.7.1 Average annual fuel energy
consumption for gas or oil-fueled
furnaces located in a different
geographic region of the United States
and in buildings with different design
heating requirements. For gas or oilfueled furnaces, the average annual fuel
energy consumption for a specific
geographic region and a specific typical
design heating requirement (EFR) is
expressed in Btu per year and defined
as:
EFR = (EF¥8,760 QP) (HLH/2,080) +
8,760 QP
Where:
E:\FR\FM\13MRR2.SGM
13MRR2
15546
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
EF = as defined in section 10.4.2 of this
appendix
8,760 = as defined in section 10.4.1.1 of this
appendix
QP = as defined in section 11.2.11 of
ASHRAE 103–1993
HLH = heating load hours for a specific
geographic region determined from the
heating load hour map in Figure 1 of this
appendix
2,080 = as defined in section 10.4.1 of this
appendix
10.7.2 Average annual auxiliary
electrical energy consumption for gas or
oil-fueled furnaces located in a different
geographic region of the United States
and in buildings with different design
heating requirements. For gas or oilfueled furnaces, the average annual
auxiliary electrical energy consumption
for a specific geographic region and a
specific typical design heating
requirement (EAER) is expressed in
kilowatt-hours and defined as:
EAER = (EAE¥ESO) (HLH/2080) + ESOR
Where:
EAE = as defined in section 10.4.3 of this
appendix
ESO = as defined in section 10.11 of this
appendix
HLH = as defined in section 10.7.1 of this
appendix
2,080 = as defined in section 10.4.1 of this
appendix
ESOR = as defined in section 10.7.3 of this
appendix.
10.7.3 Average annual electric
energy consumption for electric
furnaces located in a different
geographic region of the United States
and in buildings with different design
heating requirements. For electric
furnaces, the average annual electric
energy consumption for a specific
geographic region and a specific typical
design heating requirement (EER) is
expressed in kilowatt-hours and defined
as:
EER = 100 (0.77) DHR HLH/(3.412
AFUE) + ESOR
ddrumheller on DSK120RN23PROD with RULES2
Where:
100 = as defined in section 10.4.3 of this
appendix
0.77 = as defined in section 10.4.1 of this
appendix
DHR = as defined in section 10.4.1 of this
appendix
HLH = as defined in section 10.7.1 of this
appendix
3.412 = as defined in section 10.4.3 of this
appendix
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
AFUE = as defined in section 10.4.3 of this
appendix
ESOR = ESO as defined in section 10.11 of this
appendix, except that in the equation for
ESO, the term BOH is multiplied by the
expression (HLH/2080) to get the
appropriate regional accounting of
standby mode and off mode loss.
10.8 Annual energy consumption for
mobile home furnaces
10.8.1 National average number of
burner operating hours for mobile home
furnaces (BOHSS). BOHSS is the same as
in section 10.4.1 of this appendix,
except that the value of EffyHS in the
calculation of the burner operating
hours, BOHSS, is calculated on the basis
of a direct vent unit with system
number 9 or 10.
10.8.2 Average annual fuel energy
for mobile home furnaces (EF). EF is
same as in section 10.4.2 of this
appendix except that the burner
operating hours, BOHSS, is calculated as
specified in section 10.8.1 of this
appendix.
10.8.3 Average annual auxiliary
electrical energy consumption for
mobile home furnaces (EAE). EAE is the
same as in section 10.4.3 of this
appendix, except that the burner
operating hours, BOHSS, is calculated as
specified in section 10.8.1 of this
appendix.
10.9 Calculation of sales weighted
average annual energy consumption for
mobile home furnaces. To reflect the
distribution of mobile homes to
geographical regions with average
HLHMHF values different from 2,080,
adjust the annual fossil fuel and
auxiliary electrical energy consumption
values for mobile home furnaces using
the following adjustment calculations.
10.9.1 For mobile home furnaces,
the sales weighted average annual fossil
fuel energy consumption is expressed in
Btu per year and defined as:
EF,MHF = (EF¥8,760 QP) HLHMHF/2,080 +
8,760 QP
Where:
EF = as defined in section 10.8.2 of this
appendix
8,760 = as defined in section 10.4.1.1 of this
appendix
QP = as defined in section 10.2 of this
appendix
HLHMHF = 1880, sales weighted average
heating load hours for mobile home
furnaces
2,080 = as defined in section 10.4.1 of this
appendix
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
10.9.2 For mobile home furnaces,
the sales-weighted-average annual
auxiliary electrical energy consumption
is expressed in kilowatt-hours and
defined as:
EAE,MHF = EAE HLHMHF/2,080
Where:
EAE = as defined in section 10.8.3 of this
appendix
HLHMHF = as defined in section 10.9.1 of this
appendix
2,080 = as defined in section 10.4.1 of this
appendix
10.10 [Reserved]
10.11 Average annual electrical
standby mode and off mode energy
consumption. Calculate the annual
electrical standby mode and off mode
energy consumption (ESO) in kilowatthours, defined as:
ESO = (PW,SB (4160¥BOH) + 4600
PW,OFF) K
Where:
PW,SB = furnace standby mode power, in
watts, as measured in section 8.10.1 of
this appendix
4,160 = average heating season hours per year
BOH = total burner operating hours as
calculated in section 10.4 of this
appendix for gas or oil-fueled furnaces.
Where for gas or oil-fueled furnaces
equipped with single-stage controls,
BOH = BOHSS; for gas or oil-fueled
furnaces equipped with two-stage
controls, BOH = (BOHR + BOHH); and for
gas or oil-fueled furnaces equipped with
step-modulating controls, BOH = (BOHR
+ BOHM). For electric furnaces, BOH =
100(2080)(0.77)DHR/(Ein 3.412(AFUE))
4,600 = as defined in section 11.4.12 of
ASHRAE 103–1993
PW,OFF = furnace off mode power, in watts,
as measured in section 8.10.2 of this
appendix
K = 0.001 kWh/Wh, conversion factor from
watt-hours to kilowatt-hours
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this
appendix
0.77 = as defined in section 10.4.1 of this
appendix
DHR = as defined in section 10.4.1 of this
appendix
Ein = steady-state electric rated power, in
kilowatts, from section 9.3 of ASHRAE
103–1993
3.412 = as defined in section 10.4.3 of this
appendix
AFUE = as defined in section 11.1 of
ASHRAE 103–1993 in percent
E:\FR\FM\13MRR2.SGM
13MRR2
8. Appendix EE to subpart B of part
430 is added to read as follows:
■
ddrumheller on DSK120RN23PROD with RULES2
Appendix EE to Subpart B of Part 430—
Uniform Test Method For Measuring
the Energy Consumption of Consumer
Boilers
0. Incorporation by reference
DOE incorporated by reference in
§ 430.3, the entire standard for ASHRAE
103–2017, ASHRAE 41.6–2014, ASTM
D2156–09 (R2018), and IEC 62301.
However, only enumerated provisions
of ASHRAE 103–2017 are applicable to
this appendix, as follows. In cases
where there is a conflict, the language
of the test procedure in this appendix
takes precedence over the incorporated
standards.
0.1 ASHRAE 103–2017
(a) Section 2 ‘‘Scope’’ as referenced in
section 1 of this appendix;
(b) Section 3 ‘‘Definitions’’ as
referenced in section 2 of this appendix;
(c) Section 4 ‘‘Classifications’’ as
referenced in section 3 of this appendix;
(d) Section 5 ‘‘Requirements’’ as
referenced in section 4 of this appendix;
(e) Section 6 ‘‘Instruments’’ as
referenced in sections 5 and 8 of this
appendix;
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
(f) Section 7 ‘‘Apparatus’’ (except for
sections 7.1 and 7.8) as referenced in
sections 6, 7.7, and 8.6 of this appendix;
(g) Section 8 ‘‘Methods of Testing’’
(except for sections 8.3.1.3, 8.3.3.1,
8.4.1.1, 8.4.1.1.1, 8.4.1.2, 8.6.1.1, 8.7.2,
and 8.8.3) as referenced in sections 7
and 8 of this appendix;
(h) Section 9 ‘‘Test Procedure’’
(except for 9.1.2.2.1, 9.1.2.2.2, 9.5.2.1,
9.7.4, and 9.10) as referenced in sections
7.3, 8, and 10.4 of this appendix;
(i) Section 10 ‘‘Nomenclature’’ as
referenced in section 9 of this appendix;
and
(j) Section 11 ‘‘Calculations’’ as
referenced in sections 8.8 and 10 of this
appendix.
0.2 [Reserved]
1. Scope. The scope of this appendix
is as specified in section 2 of ASHRAE
103–2017 as it pertains to low pressure
steam or hot water boiler and electric
boilers.
2. Definitions. Definitions include
those specified in section 3 of ASHRAE
103–2017 and the following additional
and modified definitions.
Active mode means the condition in
which the boiler is connected to the
power source, and at least one of the
burner, electric resistance elements, or
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
15547
any electrical auxiliaries such as
blowers or pumps, are activated.
Boiler pump means a pump installed
on a boiler that maintains adequate
water flow through the boiler heat
exchanger and that is separate from the
circulating water pump.
Draft inducer means a fan
incorporated in the boiler that either
draws or forces air into the combustion
chamber.
Gas valve means an automatic or
semi-automatic device consisting
essentially of a valve and operator that
controls the gas supply to the burner(s)
during normal operation of an
appliance. The operator may be actuated
by application of gas pressure on a
flexible diaphragm, by electrical means,
by mechanical means or by other means.
Installation and operation (I&O)
manual means instructions for
installing, commissioning, and
operating the boiler, which are supplied
with the product when shipped by the
manufacturer.
Off mode means a mode in which the
boiler is connected to a mains power
source and is not providing any active
mode or standby mode function, and
where the mode may persist for an
indefinite time. The existence of an off
switch in off position (a disconnected
E:\FR\FM\13MRR2.SGM
13MRR2
ER13MR23.003
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
15548
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
circuit) is included within the
classification of off mode.
Off switch means the switch on the
boiler that, when activated, results in a
measurable change in energy
consumption between the standby and
off modes.
Oil control valve means an
automatically or manually operated
device consisting of an oil valve for
controlling the fuel supply to a burner
to regulate burner input.
Standard cubic foot of gas means the
amount of gas that would occupy 1
cubic foot when at a temperature of
60 °F and under a pressure equivalent to
that of 30 inches Hg if saturated with
water vapor.
Standby mode means any mode in
which the boiler is connected to a mains
power source and offers one or more of
the following space heating functions
that may persist:
(a) To facilitate the activation of other
modes (including activation or
deactivation of active mode) by remote
switch (including thermostat or remote
control), internal or external sensors, or
timer;
(b) Continuous functions, including
information or status displays or sensorbased functions.
Thermal stack damper means a type
of stack damper that relies exclusively
upon the changes in temperature in the
stack gases to open or close the damper.
3. Classifications. Classifications are
as specified in section 4 of ASHRAE
103–2017.
4. Requirements. Requirements are as
specified in section 5 of ASHRAE 103–
2017.
5. Instruments. Instruments must be
as specified in section 6 of ASHRAE
103–2017. In addition to the
requirements in Section 6.3 of ASHRAE
103–2017, instruments for oil pressure
shall be calibrated so that the error is no
greater than ±0.5 psi.
6. Apparatus. The apparatus used in
conjunction with the boiler during the
testing must be as specified in section
7 of ASHRAE 103–2017 except for
sections 7.1 and 7.8; and as specified in
sections 6.1 and 6.2 of this appendix. In
section 7.2.3.1 of ASHRAE 103–2017,
substitute ‘‘in accordance with the I&O
manual’’ for ‘‘in accordance with
manufacturer instructions’’ with regard
to installing the stack damper.
6.1 General.
(a) Install the boiler in the test room
in accordance with the I&O manual, as
defined in section 2.5 of this appendix,
except that if provisions within this
appendix are specified, then the
provisions herein drafted and
prescribed by DOE govern. If the I&O
manual and any additional provisions of
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
this appendix are not sufficient for
testing a boiler, the manufacturer must
request a waiver from the test procedure
pursuant to § 430.27.
(b) The apparatuses described in
section 6 of this appendix are used in
conjunction with the boiler during
testing. Each piece of apparatus shall
conform to material and construction
specifications listed in this appendix
and in ASHRAE 103–2017, and the
reference standards cited in this
appendix and in ASHRAE 103–2017.
(c) Test rooms containing equipment
must have suitable facilities for
providing the utilities (including but not
limited to environmental controls,
sufficient fluid source(s), applicable
measurement equipment, and any other
technology or tools) necessary for
performance of the test and must be able
to maintain conditions within the limits
specified in section 6 of this appendix.
6.2 Condensate collection. Attach
condensate drain lines to the unit as
specified in the I&O manual. Maintain
a continuous downward slope of drain
lines from the unit. Additional
precautions (such as eliminating any
line configuration or position that
would otherwise restrict or block the
flow of condensate or checking to
ensure a proper connection with
condensate drain spout that allows for
unobstructed flow) must be taken to
facilitate uninterrupted flow of
condensate during the test. Collection
containers must be glass or polished
stainless steel to facilitate removal of
interior deposits. The collection
container must have a vent opening to
the atmosphere.
7. Testing conditions. The testing
conditions must be as specified in
section 8 of ASHRAE 103–2017 (except
for the excluded sub-sections as
enumerated in section 0.1(g) of this
appendix); and as specified in sections
7.1 to 7.8 of this appendix, respectively.
For condensing furnaces and boilers, the
relative humidity of the room air shall
be measured in accordance with one of
the methods described in ASHRAE
41.6–2014 (see section 8.5 of ASHRAE
103–2017).
7.1 Fuel supply, gas. In conducting
the tests specified herein, gases with
characteristics as shown in Table 1 of
ASHRAE 103–2017 shall be used.
Maintain the gas supply, ahead of all
controls for a boiler, at a test pressure
between the normal and increased
values shown in Table 1 of ASHRAE
103–2017. Maintain the regulator outlet
pressure at a level approximating that
recommended in the I&O manual, as
defined in section 2.5 of this appendix,
or, in the absence of such
recommendation, to the regulator
PO 00000
Frm 00040
Fmt 4701
Sfmt 4700
settings used when the product is
shipped by the manufacturer. Use a gas
having a specific gravity of
approximately that shown in Table 1 of
ASHRAE 103–2017 and with a higher
heating value within ±5% of the higher
heating value shown in Table 1 of
ASHRAE 103–2017. Determine the
actual higher heating value in Btu per
standard cubic foot of gas (defined in
section 2 of this appendix) to be used
in the test within an error no greater
than 1%.
7.2 Installation of piping. Install
piping equipment in accordance with
the I&O manual. In the absence of such
specification, install piping in
accordance with section 8.3.1.1 of
ASHRAE 103–2017.
7.3 Gas burner. Adjust the burners
of gas-fired boilers to their maximum
Btu input ratings at the normal test
pressure specified by section 7.1 of this
appendix. Correct the burner input rate
to reflect gas characteristics at a
temperature of 60 °F and atmospheric
pressure of 30 in of Hg and adjust to
within ±2 percent of the hourly Btu
nameplate input rating specified by the
manufacturer as measured at the
maximum input rate during the steadystate performance test in section 8 of
this appendix. Set the primary air
shutters in accordance with the I&O
manual to give a good flame at this
condition. If, however, the setting
results in the deposit of carbon on the
burners during any test specified herein,
the tester shall adjust the shutters and
burners until no more carbon is
deposited and shall perform the tests
again with the new settings (see Figure
9 of ASHRAE 103–2017). After the
steady-state performance test has been
started, do not make additional
adjustments to the burners during the
required series of performance tests
specified in section 9 of ASHRAE 103–
2017. If a vent-limiting means is
provided on a gas pressure regulator,
keep it in place during all tests.
7.4 Modulating gas burner
adjustment at reduced input rate. For
gas-fired boilers equipped with
modulating-type controls, adjust the
controls to operate the unit at the
nameplate minimum input rate. If the
modulating control is of a nonautomatic type, adjust the control to the
setting recommended in the I&O
manual. In the absence of such
recommendation, the midpoint setting
of the non-automatic control shall be
used as the setting for determining the
reduced fuel input rate. Start the boiler
by turning the safety control valve to the
‘‘ON’’ position. Use a supply water
temperature that will allow for
continuous operation without shutoff by
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
the control. If necessary to achieve such
continuous operation, supply water may
be increased above 120 °F; in such cases,
gradually increase the supply water
temperature to determine what
minimum supply water temperature,
with a 20 °F temperature rise across the
boiler, will be needed to adjust for the
minimum input rate at the reduced
input rate control setting. Monitor
regulated gas pressure out of the
modulating control valve (or entering
the burner) to determine when no
further reduction of gas pressure results.
The flow rate of water through the boiler
shall be adjusted to achieve a 20 °F
temperature rise.
7.5 Oil burner. Adjust the burners of
oil-fired boilers to give a CO2 reading
specified in the I&O manual and an
hourly Btu input within ±2% of the
hourly Btu nameplate input rating as
specified in the I&O manual and as
measured at maximum input rate during
steady-state performance test as
described in section 8 of this appendix.
Smoke in the flue may not exceed a No.
1 smoke during the steady-state
performance test as measured by the
procedure in ASTM D2156–09 (R2018).
Maintain the average draft over the fire
and in the flue during the steady-state
performance test at the value specified
in the I&O manual. Do not allow draft
fluctuations exceeding 0.005 in. water.
Do not make additional adjustments to
the burner during the required series of
performance tests. The instruments and
measuring apparatus for this test are
described in section 6 of this appendix
and shown in Figure 8 of ASHRAE 103–
2017.
7.6 Measurement of jacket surface
temperature. Divide the jacket of the
boiler into 6-inch squares when
practical, and otherwise into 36-squareinch regions comprising 4 inch by 9
inch or 3 inch by 12 inch sections, and
determine the surface temperature at the
center of each square or section with a
surface thermocouple. Record the
surface temperature of the 36-squareinch areas in groups where the
temperature differential of the 36square-inch areas is less than 10 °F for
temperature up to 100 °F above room
temperature, and less than 20 °F for
temperatures more than 100 °F above
room temperature.
7.7 Installation of vent system. Keep
the vent or air intake system supplied
by the manufacturer in place during all
tests. Test units intended for installation
with a variety of vent pipe lengths with
the minimum vent length as specified in
the I&O manual, or a 5-ft. flue pipe if
there are no recommendations in the
I&O manual. Do not connect a boiler
employing a direct vent system to a
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
chimney or induced-draft source. Vent
combustion products solely by using the
venting incorporated in the boiler and
the vent or air intake system supplied
by the manufacturer. For units that are
not designed to significantly preheat the
incoming air, see section 7.5 of this
appendix and Figure 4a or 4b in section
7 of ASHRAE 103–2017. For units that
do significantly preheat the incoming
air, see Figure 4c or 4d in section 7 of
ASHRAE 103–2017.
7.8 Additional optional method of
testing for determining DP and DF. On
units whose design is such that there is
no measurable airflow through the
combustion chamber and heat
exchanger when the burner(s) is (are) off
as determined by the optional test
procedure in section 7.8.1 of this
appendix, DF and DP may be set equal
to 0.05.
7.8.1 Optional test method for
indicating the absence of flow through
the heat exchanger. Manufacturers may
use the following test protocol to
determine whether air flows through the
combustion chamber and heat
exchanger when the burner(s) is (are)
off. The minimum default draft factor
may be used only for units determined
pursuant to this protocol to have no
airflow through the combustion
chamber and heat exchanger.
7.8.1.1 Test apparatus. Use a smoke
stick that produces smoke that is easily
visible and has a density less than or
approximately equal to air. Use a smoke
stick that produces smoke that is nontoxic to the test personnel and produces
gas that is unreactive with the
environment in the test chamber.
7.8.1.2 Test conditions. Minimize all
air currents and drafts in the test
chamber, including turning off
ventilation if the test chamber is
mechanically ventilated. Wait at least
two minutes following the termination
of the boiler on-cycle before beginning
the optional test method for indicating
the absence of flow through the heat
exchanger.
7.8.1.3 Location of the test
apparatus. After all air currents and
drafts in the test chamber have been
eliminated or minimized, position the
smoke stick based on the following
equipment configuration:
(a) For horizontal combustion air
intakes, approximately 4 inches from
the vertical plane at the termination of
the intake vent and 4 inches below the
bottom edge of the combustion air
intake; or
(b) for vertical combustion air intakes,
approximately 4 inches horizontal from
vent perimeter at the termination of the
intake vent and 4 inches down (parallel
to the vertical axis of the vent). In the
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
15549
instance where the boiler combustion
air intake is closer than 4 inches to the
floor, place the smoke device directly on
the floor without impeding the flow of
smoke.
7.8.1.4 Duration of test. Establish the
presence of smoke from the smoke stick
and then monitor the direction of the
smoke flow for no less than 30 seconds.
7.8.1.5 Test results. During visual
assessment, determine whether there is
any draw of smoke into the combustion
air intake vent.
If absolutely no smoke is drawn into
the combustion air intake, the boiler
meets the requirements to allow use of
the minimum default draft factor
provided in section 7.8 of this appendix.
If there is any smoke drawn into the
intake, proceed with the methods of
testing as prescribed in section 8.8 of
ASHRAE 103–2017.
7.8.2 [Reserved]
8. Test procedure. Conduct testing
and measurements as specified in
Section 9 of ASHRAE 103–2017 (except
for the excluded sub-sections as
enumerated in section 0.1(h) of this
appendix); and as specified in sections
8.1 through 8.9 of this appendix.
Section 8.4 of this appendix may be
used in lieu of section 9.2 of ASHRAE
103–2017.
8.1 Fuel input. For gas units,
measure and record the steady-state gas
input rate in Btu/h, including pilot gas,
corrected to standard conditions of 60 °F
and 30 in. Hg. Use measured values of
gas temperature and pressure at the
meter and barometric pressure to correct
the metered gas flow rate to the above
standard conditions. For oil units,
measure and record the steady-state fuel
input rate. For maximum input rate, the
measured burner input rate shall be
within ±2% of the hourly Btu nameplate
input rating (QIN) specified by the
manufacturer. For modulating furnaces
and boilers operating at reduced input
rate, the measured reduced heat input
rate (QIN,R) shall be recorded. At the
discretion of the one testing, the hourly
Btu nameplate minimum input rating
specified by the manufacturer may be
used in the calculations in place of QIN,R
if the measured rate is within ±2% of
the nameplate rating.
8.2 Electrical input. During the
steady-state test, perform a single
measurement of all of the electrical
power involved in burner operation
(PE), including energizing the ignition
system, controls, gas valve or oil control
valve, and draft inducer, if applicable.
For boilers, the measurement of PE must
include the boiler pump if so equipped.
If the boiler pump does not operate
during the measurement of PE, add the
boiler pump nameplate power to the
E:\FR\FM\13MRR2.SGM
13MRR2
ddrumheller on DSK120RN23PROD with RULES2
15550
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
measurement of PE. If the boiler pump
nameplate power is not available, use
0.13 kW. For hot water boilers, use the
circulating water pump nameplate
power for BE, or if the pump nameplate
power is not available, use 0.13 kW.
8.3 Input to interrupted ignition
device. For burners equipped with an
interrupted ignition device, record the
nameplate electric power used by the
ignition device, PEIG, or record that PEIG
= 0.4 kW if no nameplate power input
is provided. Record the nameplate
ignition device on-time interval, tIG, or,
if the nameplate does not provide the
ignition device on-time interval,
measure the on-time interval with a
stopwatch at the beginning of the test,
starting when the burner is turned on.
Set tIG = 0 and PEIG = 0 if the device
on-time interval is less than or equal to
5 seconds after the burner is on.
8.4 Cycling Test Requirements. For
the measurement of condensate heat
loss under cyclic conditions (for
condensing boilers), section 9.8 of
ASHRAE 103–2017 shall apply. Cycle
times calculated from Table 7 of
ASHRAE 103–2017 shall be rounded to
the nearest second.
8.5 Optional test procedures for
condensing boilers, measurement of
condensate during the establishment of
steady-state conditions. For units with
step-modulating or two-stage controls,
conduct the test at both the maximum
and reduced inputs. In lieu of collecting
the condensate immediately after the
steady state conditions have been
reached as required by section 9.2 of
ASHRAE 103–2017, condensate may be
collected during the establishment of
steady state conditions as defined by
section 9.1.2.1 of ASHRAE 103–2017.
Perform condensate collection for at
least 30 minutes. Measure condensate
mass immediately at the end of the
collection period to prevent evaporation
loss from the sample. Record fuel input
for the 30-minute condensate collection
test period. Observe and record fuel
higher heating value (HHV),
temperature, and pressures necessary
for determining fuel energy input
(QC,SS). Measure the fuel quantity and
HHV with errors no greater than 1%.
The humidity for the room air shall at
no time exceed 80%. Determine the
mass of condensate for the
establishment of steady state conditions
(MC,SS) in pounds by subtracting the tare
container weight from the total
container and condensate weight
measured at the end of the 30-minute
condensate collection test period.
8.6 Cool-down test for gas- and oilfueled boilers without stack dampers.
After steady-state testing has been
completed, turn the main burner(s)
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
‘‘OFF’’ and measure the flue gas
temperature at 3.75 minutes
(temperature designated as TF,OFF(t3))
and 22.5 minutes (temperature
designated as TF,OFF(t4)) after the burner
shut-off using the thermocouple grid
described in section 7.6 of ASHRAE
103–2017.
a. During this off-period, for units that
do not have pump delay after shut-off,
do not allow any water to circulate
through the hot water boilers.
b. For units that have pump delay on
shut-off, except those having pump
controls sensing water temperature, the
unit control must stop the pump.
Measure and record the time between
burner shut-off and pump shut-off (t+) to
the nearest second.
c. For units having pump delay
controls that sense water temperature,
operate the pump for 15 minutes and
record t+ as 15 minutes. While the pump
is operating, maintain the inlet water
temperature and flow rate at the same
values as used during the steady-state
test, as specified in sections 9.1 and
8.4.2.3 of ASHRAE 103–2017.
d. For boilers that employ post-purge,
measure the length of the post-purge
period with a stopwatch. Record the
time from burner ‘‘OFF’’ to combustion
blower ‘‘OFF’’ (electrically deenergized) as tP. Measure the flue gas
temperature by means of the
thermocouple grid described in section
7.6 of ASHRAE 103–2017 at the end of
the post-purge period tP (TF,OFF(tP)) and
at (3.75 + tP) minutes (TF,OFF(t3)) and
(22.5 + tP) minutes (TF,OFF(t4)) after the
main burner shuts off. If tP is prescribed
by the I&O manual or measured to be
greater than 3 minutes, also measure the
flue gas temperature at the midpoint of
the post-purge period tP/2 (TF,OFF(tP/2)).
If the measured tP is less than or equal
to 30 seconds, record tP as 0 and
conduct the cool-down test as if there is
no post-purge.
8.7 [Reserved]
8.8 Calculation options. The rate of
the flue gas mass flow through the boiler
and the factors DP, DF, and DS are
calculated by the equations in sections
11.6.1, 11.6.2, 11.6.3, 11.6.4, 11.7.1, and
11.7.2 of ASHRAE 103–2017. On units
whose design is such that there is no
measurable airflow through the
combustion chamber and heat
exchanger when the burner(s) is (are) off
(as determined by the optional test
procedure in section 7.8 of this
appendix), DF and DP may be set equal
to 0.05.
8.9 Optional test procedures for
condensing boilers that have no offperiod flue losses. For units that have
applied the test method in section 7.8 of
this appendix to determine that no
PO 00000
Frm 00042
Fmt 4701
Sfmt 4700
measurable airflow exists through the
combustion chamber and heat
exchanger during the burner off-period
and having post-purge periods of less
than 30 seconds, the cool-down and
heat-up tests specified in sections 9.5
and 9.6 of ASHRAE 103–2017 may be
omitted. In lieu of conducting the cooldown and heat-up tests, the tester may
use the losses determined during the
steady-state test described in section 9.1
of ASHRAE 103–2017 when calculating
heating seasonal efficiency, EffyHS.
8.10 Measurement of electrical
standby and off mode power.
8.10.1 Standby power measurement.
With all electrical auxiliaries of the
boiler not activated, measure the
standby power (PW,SB) in accordance
with the procedures in IEC 62301,
except that section 8.5, Room Ambient
Temperature, of ASHRAE 103–2017 and
the voltage provision of section 8.2.1.4,
Electrical Supply, of ASHRAE 103–2017
shall apply in lieu of the corresponding
provisions of IEC 62301 at section 4.2,
Test room, and the voltage specification
of section 4.3, Power supply. Frequency
shall be 60Hz. Clarifying further, IEC
62301 section 4.4, Power measurement
instruments, and section 5,
Measurements, apply in lieu of
ASHRAE 103–2017 section 6.10, Energy
Flow Rate. Measure the wattage so that
all possible standby mode wattage for
the entire appliance is recorded, not just
the standby mode wattage of a single
auxiliary. Round the recorded standby
power (PW,SB) to the second decimal
place, except for loads greater than or
equal to 10W, which must be recorded
to at least three significant figures.
8.10.2 Off mode power
measurement. If the unit is equipped
with an off switch or there is an
expected difference between off mode
power and standby mode power,
measure off mode power (PW,OFF) in
accordance with the standby power
procedures in IEC 62301, except that
section 8.5, Room Ambient
Temperature, of ASHRAE 103–2017 and
the voltage provision of section 8.2.1.4,
Electrical Supply, of ASHRAE 103–2017
shall apply in lieu of the corresponding
provisions of IEC 62301 at section 4.2,
Test room, and the voltage specification
of section 4.3, Power supply. Frequency
shall be 60Hz. Clarifying further, IEC
62301 section 4.4, Power measurement
instruments, and section 5,
Measurements, apply for this
measurement in lieu of SHRAE 103–
2017 section 6.10, Energy Flow Rate.
Measure the wattage so that all possible
off mode wattage for the entire
appliance is recorded, not just the off
mode wattage of a single auxiliary. If
there is no expected difference in off
E:\FR\FM\13MRR2.SGM
13MRR2
C; and as specified in sections 10.1
through 10.7 and Figure 1 of this
appendix.
10.1 Annual fuel utilization
efficiency. The annual fuel utilization
efficiency (AFUE) is as defined in
sections 11.2.12 (non-condensing
systems), 11.3.12 (condensing systems),
11.4.12 (non-condensing modulating
systems) and 11.5.12 (condensing
modulating systems) of ASHRAE 103–
2017, except for the following:
10.1.1 Off-cycle Infiltration Heat
Loss. The off-cycle infiltration heat loss
(LI,OFF1) is as defined in sections
11.2.10.8 (non-condensing systems),
11.3.10.8 (condensing systems),
11.4.10.8 (non-condensing modulating
systems) and 11.5.10.8 (condensing
modulating systems) of ASHREAE 103–
2017, with the following exception. For
systems numbered 2, 3, and 4, with a
post-purge time of 3 minutes or less,
LI,OFF1 shall be determined as follows:
10.1.2 Determination of EffyHS in the
Defining Equation for AFUE. EffyHS is
defined as:
EffyHS = heating seasonal efficiency as
defined in sections 11.2.11 (noncondensing systems), 11.3.11
(condensing systems), 11.4.11 (non-
condensing modulating systems) and
11.5.11 (condensing modulating
systems) of ASHRAE 103–2017, and is
based on the assumptions that
weatherized boilers are located
outdoors and that non-weatherized
boilers are installed indoors.
10.1.3 Balance Point Temperature
for Condensing Modulating Boilers.
Calculate the balance point temperature
(TC) for condensing, modulating boilers
by using the following equation in place
of that referenced by section 11.5.8.4 of
ASHRAE 103–2017: TC =
Where:
TSH = typical average outdoor temperature at
which a boiler starts operating, 65 °F
TOA,T = the typical outdoor design
temperature, 5 °F
a = oversize factor, as defined in 11.4.8.2
QIN = steady-state nameplate maximum fuel
input rate
QIN,R = steady-state reduced input fuel input
rate
LS,SSR = average sensible heat loss at steady
state, reduced input operation
LS,SS = average sensible heat loss at steady
state, maximum input operation
10.2 National average burner
operating hours, average annual fuel
energy consumption, and average
annual auxiliary electrical energy
consumption for gas or oil boilers.
10.2.1 National average number of
burner operating hours.
10.2.1.1 For boilers equipped with
single-stage controls, the national
average number of burner operating
hours is defined as:
BOHSS = 2,080 (0.77) (A) [(QOUT/1000)/
(1+a)]¥2,080 (B)
Where:
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
PO 00000
Frm 00043
Fmt 4701
Sfmt 4700
2,080 = national average heating load hours
0.77 = adjustment factor to adjust the
calculated design heating requirement
and heating load hours to the actual
heating load experienced by the heating
system
A = 100,000/[341,200 (yP PE + yIG PEIG + y
BE) + (QIN¥QP) EffyHS], for forced draft
unit, indoors
= 100,000/[341,200 (yP PE (1¥Effmotor) + yIG
PEIG + y BE) + (QIN¥QP) EffyHS], for
induced draft unit, indoors, and
QOUT = value as defined in section 11.2.8.1
of ASHRAE 103–2017.
a = value as defined in section 11.2.8.2 of
ASHRAE 103–2017.
E:\FR\FM\13MRR2.SGM
13MRR2
ER13MR23.005
Effmotor = Efficiency of power burner
motor
PEIG = Electrical power to the
interrupted ignition device, kW
RT,a = RT,F if flue gas is measured
= RT,S if stack gas is measured
RT,F = Ratio of combustion air mass flow
rate to stoichiometric air mass flow
rate
RT,S = Ratio of the sum of combustion
air and relief air mass flow rate to
stoichiometric air mass flow rate
tIG = Electrical interrupted ignition
device on-time, min.
Ta,SS,X = TF,SS,X if flue gas temperature
is measured, °F
= TS,SS,X if stack gas temperature is
measured, °F
yIG = Ratio of electrical interrupted
ignition device on-time to average
burner on-time
yP = Ratio of power burner combustion
blower on-time to average burner ontime
ESO = Average annual electric standby
mode and off mode energy
consumption, in kilowatt-hours
PW,OFF = Boiler off mode power, in watts
PW,SB = Boiler standby mode power, in
watts
10. Calculation of derived results from
test measurements. Perform calculations
as specified in section 11 of ASHRAE
103–2017, except for appendices B and
mode power and standby mode power,
let PW,OFF = PW,SB, in which case no
separate measurement of off mode
power is necessary. Round the recorded
off mode power (PW,OFF) to the second
decimal place, except for loads greater
than or equal to 10W, in which case
round the recorded value to at least
three significant figures.
9. Nomenclature. Nomenclature
includes the nomenclature specified in
Section 10 of ASHRAE 103–2017 and
the following additional variables:
ddrumheller on DSK120RN23PROD with RULES2
15551
ER13MR23.004
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
15552
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
ddrumheller on DSK120RN23PROD with RULES2
B = 2 QP (EffyHS) (A)/100,000
Where:
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
100,000 = factor that accounts for percent
and kBtu
yP = ratio of induced or forced draft blower
on-time to average burner on-time, as
follows:
1 for units without post-purge;
1 + (tP/tON) for single stage boilers with post
purge; or
PE = all electrical power related to burner
operation at full load steady-state
operation, including electrical ignition
device if energized, controls, gas valve or
oil control valve, draft inducer, and
boiler pump, as determined in section
8.2 of this appendix.
yIG = ratio of burner interrupted ignition
device on-time to average burner ontime, as follows:
0 for burners not equipped with interrupted
ignition device;
(tIG/tON) for single stage boilers
PEIG = electrical input rate to the interrupted
ignition device on burner (if employed),
as defined in section 8.3 of this appendix
y = ratio of pump on-time to average burner
on-time, as follows:
1 for boilers without a pump delay;
1 + (t+/tON) for single-stage boilers with pump
delay;
BE = circulating water pump electrical
energy input rate at full-load steady-state
operation as defined in section 8.2 of this
appendix.
tP = post-purge time as defined in section 8.5
of this appendix
= 0 if tP is equal to or less than 30 seconds
tIG = on-time of the burner interrupted
ignition device, as defined in section 8.3
of this appendix
QIN = as defined in section 11.2.8.1 of
ASHRAE 103–2017
QP = as defined in section 11.2.11 of
ASHRAE 103–2017
EffyHS = as defined in section 11.2.11 (noncondensing systems) or section 11.3.11.3
(condensing systems) of ASHRAE 103–
2017, percent, and calculated on the
basis of:
indoor installation, for non-weatherized
boilers; or outdoor installation, for
boilers that are weatherized.
2 = ratio of the average length of the heating
season in hours to the average heating
load hours
t+ = delay time between burner shutoff and
the pump shutoff measured as defined in
section 8.5 of this appendix.
tON = value as defined in Table 7 of ASHRAE
103–2017.
10.2.1.2 For boilers equipped with
two-stage or step-modulating
controls, the national average
number of burner operating hours at
the reduced operating mode (BOHR)
is defined as:
BOHR = XR (2080)(0.77)[(QOUT/1,000)/
(1+a)](AR)¥2080(BR)
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
Where:
XR = as defined in section 11.4.8.6 of SHRAE
103–2017
2080 = as defined in section 10.2.1.1 of this
appendix
0.77 = as defined in section 10.2.1.1 of this
appendix
QOUT = as defined in section 11.4.8.1.1 or
11.5.8.1.1 of ASHRAE 103–2017
a = as defined in section 11.4.8.2 of ASHRAE
103–2017
AR = 100,000/[341,200(yP,RPER + yIG,RPEIG +
yRBER) + (QIN,R¥QP) EffyU,R] for forced
draft unit, indoors; and
= 100,000/[341,200(yP,RPER (1¥Effmotor) +
yIG,RPEIG + yRBER) + (QIN,R¥QP) EffyU,R]
for induced draft unit, indoors
BR = 2QP (EffyU,R) (AR)/100,000
100,000 = conversion factor accounting for
percent and 1,000 Btu/kBtu
341,200 = conversion factor accounting for
percent and 3412 Btu/h/kW
yP,R = 1 + (tp/tON,R) for two-stage and step
modulating boilers with post purge
PER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
yIG,R = tIG/tON,R
PEIG = as defined in section 8.3 of this
appendix
yR = 1 + (t+)/tON,R for two-stage and step
modulating boilers with fan delay
BER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
QIN,R = as defined in section 11.4.8.1.2 of
ASHRAE 103–2017
QP = as defined in section 11.4.12 of
ASHRAE 103–2017
EffyU,R = as defined in section 11.4.11.1 or
11.5.11.1 of ASHRAE 103–2017, and
calculated on the basis of:
indoor installation, for non-weatherized
boilers; or
outdoor installation, for boilers that are
weatherized.
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
10.2.1.3 For boilers equipped with
two-stage controls, the national average
number of burner operating hours at the
maximum operating mode (BOHH) is
defined as:
BOHH = XH (2080)(0.77)[(QOUT/1,000)/
(1+a)](AH)—2080(BH)
Where:
XH = as defined in section 11.4.8.5 of SHRAE
103–2017
2080 = as defined in section 10.2.1.1 of this
appendix
0.77 = as defined in section 10.2.1.1 of this
appendix
QOUT = as defined in section 11.4.8.1.1 or
11.5.8.1.1 ofASHRAE 103–2017
a = as defined in section 11.4.8.2 of ASHRAE
103–2017
AH = 100,000/[341,200(yP,HPEH + yIG,HPEIG +
yHBEH) + (QIN,H—QP) EffyU,H] for forced
draft unit, indoors; and
= 100,000/[341,200(yP,HPEH (1—Effmotor) +
yIG,HPEIG + yHBEH) + (QIN,H—QP) EffyU,H]
for induced draft unit, indoors
PO 00000
Frm 00044
Fmt 4701
Sfmt 4700
BH = 2QP (EffyU,H) (AH)/100,000
100,000 = conversion factor accounting for
percent and 1,000 Btu/kBtu
341,200 = conversion factor accounting for
percent and 3412 Btu/h/kW
yP,H = 1 + (tp/tON,H) for two-stage and step
modulating boilers with post purge
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
yIG,H = tIG/tON,H
PEIG = as defined in section 8.3 of this
appendix
yH = 1 + (t+)/tON,H for two-stage and step
modulating boilers with fan delay
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
QIN,H = as defined in section 11.4.8.1.1 of
ASHRAE 103–2017
QP = as defined in section 11.4.12 of
ASHRAE 103–2017
EffyU,H = as defined in section 11.4.11.2 or
11.5.11.2 of ASHRAE 103–2017, and
calculated on the basis of:
indoor installation, for non-weatherized
boilers; or
outdoor installation, for boilers that are
weatherized.
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
10.2.1.4 For boilers equipped with
step-modulating controls, the national
average number of burner operating
hours at the modulating operating mode
(BOHM) is defined as:
BOHM = XH (2080)(0.77)[(QOUT/1,000)/
(1+a)](AM)—2080(BM)
Where:
XH = as defined in section 11.4.8.5 of
ASHRAE 103–2017
2080 = as defined in section 10.2.1.1 of this
appendix
0.77 = as defined in section 10.2.1.1 of this
appendix
QOUT = as defined in section 11.4.8.1.1 or
11.5.8.1.1 of ASHRAE 103–2017
a = as defined in section 11.4.8.2 of ASHRAE
103–2017
AM = 100,000/[341,200(yP,HPEH + yIG,HPEIG +
yHBEH) + (QIN,M—QP) EffyU,M] for forced
draft unit, indoors; and
= 100,000/[341,200(yP,HPEH (1—Effmotor) +
yIG,HPEIG + yHBEH) + (QIN,M—QP)
EffyU,M] for induced draft unit, indoors
BM = 2QP (EffyU,M) (AM)/100,000
100,000 = conversion factor accounting for
percent and 1,000 Btu/kBtu
341,200 = conversion factor accounting for
percent and 3412 Btu/h/kW
yP,H = 1 + (tp/tON,H) for two-stage and step
modulating boilers with post purge
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
yIG,H = tIG/tON,H
PEIG = as defined in section 8.3 of this
appendix
yH = 1 + (t+)/tON,H for two-stage and step
modulating boilers with fan delay
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
QIN,M = (100)(QOUT,M/EffySS,M)
QOUT,M = as defined in section 11.4.8.9 or
11.5.8.9 of ASHRAE 103–2017
EffySS,M = value as defined in section 11.4.8.7
or 11.5.8.7 of ASHRAE 103–2017
QP = as defined in section 11.4.12 of
ASHRAE 103–2017
EffyU,M = as defined in section 11.4.9.2.3 or
11.5.9.2.3 of ASHRAE 103–2017, and
calculated on the basis of:
indoor installation, for non-weatherized
boilers; or
outdoor installation, for boilers that are
weatherized.
Effmotor = nameplate power burner motor
efficiency provided by the manufacturer,
= 0.50, an assumed default power burner
efficiency if not provided by the
manufacturer.
10.2.2 Average annual fuel energy
consumption for gas or oil fueled
boilers.
10.2.2.1 For boilers equipped with
single-stage controls, the average annual
fuel energy consumption (EF) is
expressed in Btu per year and defined
as:
EF = BOHSS (QIN ¥ QP) + 8,760 QP
Where:
BOHSS = as defined in section 10.2.1.1 of this
appendix
QIN = as defined in section 11.2.8.1 of
ASHRAE 103–2017
QP = as defined in section 11.2.11 of
ASHRAE 103–2017
8,760 = total number of hours per year.
ddrumheller on DSK120RN23PROD with RULES2
10.2.2.2 For boilers equipped with
either two-stage or step modulating
controls, EF is defined as follows. For
two-stage control:
EF = (BOHH)(QIN) + (BOHR)(QIN,R) +
[8760 ¥ (BOHH + BOHR)]QP
For step-modulating control:
EF = (BOHM)(QIN,M) + (BOHR)(QIN,R) +
[8760 ¥ (BOHH + BOHR)]QP
Where:
BOHH = as defined in section 10.2.1.3 of this
appendix
BOHR = as defined in section 10.2.1.2 of this
appendix
BOHM = as defined in section 10.2.1.4 of this
appendix
QIN = as defined in section 11.2.8.1 of
ASHRAE 103–2017
QIN,R = as defined in section 11.4.8.1.2 of
ASHRAE 103–2017
QIN,M = as defined in section 10.2.1.4 of this
appendix
8,760 = total number of hours per year
QP = as defined in section 11.2.11 of
ASHRAE 103–2017.
10.2.3 Average annual auxiliary
electrical energy consumption for gas or
oil-fueled boilers.
10.2.3.1 For boilers equipped with
single-stage controls, the average annual
auxiliary electrical consumption (EAE) is
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
expressed in kilowatt-hours and defined
as:
EAE = BOHSS (yP PE + yIG PEIG + yBE)
+ ESO
Where:
BOHSS = as defined in section 10.2.1.1 of this
appendix
yP = as defined in section 10.2.1.1 of this
appendix
PE = as defined in section 10.2.1.1 of this
appendix
yIG = as defined in section 10.2.1.1 of this
appendix
PEIG = as defined in section 10.2.1.1 of this
appendix
y = as defined in section 10.2.1.1 of this
appendix
BE = as defined in section 10.2.1.1 of this
appendix
ESO = as defined in section 10.7 of this
appendix.
10.2.3.2 For boilers equipped with
two-stage controls, EAE is defined as:
EAE = BOHR (yP,R PER + yIG,R PEIG +
yRBER) + BOHH (yP,H PEH + yIG,H
PEIG + yHBEH) + ESO
Where:
BOHR = as defined in section 10.2.1.2 of this
appendix
yP,R = as defined in section 10.2.1.2 of this
appendix
PER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
yIG,R = as defined in section 10.2.1.2 of this
appendix
PEIG = as defined in section 10.2.1.1 of this
appendix
yR = as defined in section 10.2.1.2 of this
appendix
BER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
BOHH = as defined in section 10.2.1.3 of this
appendix
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
yP,H = as defined in section 10.2.1.3 of this
appendix
yIG,H = as defined in section 10.2.1.3 of this
appendix
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
yH = as defined in section 10.2.1.3 of this
appendix
ESO = as defined in section 10.7 of this
appendix.
10.2.3.3 For boilers equipped with
step-modulating controls, EAE is defined
as:
EAE = BOHR (yP,R PER + yIG,R PEIG + yR
BER) + BOHM (yP,H PEH + yIG,H PEIG
+ yHBEH) + ESO
Where:
BOHR = as defined in section 10.2.1.2 of this
appendix
yP,R = as defined in section 10.2.1.2 of this
appendix
PO 00000
Frm 00045
Fmt 4701
Sfmt 4700
15553
PER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
yIG,R = as defined in section 10.2.1.2 of this
appendix
PEIG = as defined in section 10.2.1 of this
appendix
yR = as defined in section 10.2.1.2 of this
appendix
BER = as defined in section 8.2 of this
appendix and measured at the reduced
fuel input rate
BOHM = as defined in 10.2.1.4 of this
appendix
yP,H = as defined in section 10.2.1.3 of this
appendix
PEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
yIG,H = as defined in section 10.2.1.3 of this
appendix
yH = as defined in section 10.2.1.3 of this
appendix
BEH = as defined in section 8.2 of this
appendix and measured at the maximum
fuel input rate
ESO = as defined in section 10.7 of this
appendix.
10.3 Average annual electric energy
consumption for electric boilers. For
electric boilers, the average annual
electrical energy consumption (EE) is
expressed in kilowatt-hours and defined
as:
EE = 100 (2,080) (0.77) [QOUT/(1+a)]/
(3412 AFUE) + ESO
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.2.1.1 of this
appendix
0.77 = as defined in section 10.2.1.1 of this
appendix
QOUT = as defined in section 11.2.8 of
ASHRAE 103–2017
a = as defined in section 11.2.8.2 of ASHRAE
103–2017
3412 = conversion factor from kilowatt-hours
to Btu
AFUE = as defined in section 11.1 of
ASHRAE 103–2017, in percent, and
calculated on the basis of:
indoor installation, for non-weatherized
boilers; or
outdoor installation, for boilers that are
weatherized.
ESO = as defined in section 10.7 of this
appendix.
10.4 Energy factor.
10.4.1 Energy factor for gas or oil
boilers. Calculate the energy factor, EF,
for gas or oil boilers defined as, in
percent:
EF = (EF ¥ 4,600 (QP))(EffyHS)/(EF +
3,412 (EAE))
Where:
EF = average annual fuel consumption as
defined in section 10.2.2 of this
appendix
4,600 = as defined in section 11.4.12 of
ASHRAE 103–2017
QP = pilot fuel input rate determined in
accordance with section 9.2 of ASHRAE
103–2017 in Btu/h
E:\FR\FM\13MRR2.SGM
13MRR2
15554
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
EffyHS = annual fuel utilization efficiency as
defined in sections 11.2.11, 11.3.11,
11.4.11 or 11.5.11 of ASHRAE 103–2017,
in percent, and calculated on the basis
of:
indoor installation, for non-weatherized
boilers; or
outdoor installation, for boilers that are
weatherized.
3,412 = conversion factor from kW to Btu/h
EAE = as defined in section 10.2.3 of this
appendix.
10.4.2 Energy factor for electric boilers.
The energy factor, EF, for electric
boilers is defined as:
EF = AFUE
Where:
AFUE = annual fuel utilization efficiency as
defined in section 10.3 of this appendix,
in percent.
10.5 Average annual energy
consumption for boilers located in a
different geographic region of the
United States and in buildings with
different design heating requirements.
10.5.1 Average annual fuel energy
consumption for gas or oil-fueled boilers
located in a different geographic region
of the United States and in buildings
with different design heating
requirements. For gas or oil-fueled
boilers, the average annual fuel energy
consumption for a specific geographic
region and a specific typical design
heating requirement (EFR) is expressed
in Btu per year and defined as:
EFR = (EF ¥ 8,760 QP) (HLH/2,080) +
8,760 QP
Where:
EF = as defined in section 10.2.2 of this
appendix
8,760 = as defined in section 10.2.2 of this
appendix
QP = as defined in section 11.2.11 of
ASHRAE 103–2017
HLH = heating load hours for a specific
geographic region determined from the
heating load hour map in Figure 1 of this
appendix
2,080 = as defined in section 10.2.1.1 of this
appendix.
ddrumheller on DSK120RN23PROD with RULES2
10.5.2 Average annual auxiliary
electrical energy consumption for gas or
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
oil-fueled boilers located in a different
geographic region of the United States
and in buildings with different design
heating requirements. For gas or oilfueled boilers, the average annual
auxiliary electrical energy consumption
for a specific geographic region and a
specific typical design heating
requirement (EAER) is expressed in
kilowatt-hours and defined as:
EAER = (EAE¥ESO) (HLH/2080) + ESOR
Where:
EAE = as defined in section 10.2.3 of this
appendix
ESO = as defined in section 10.7 of this
appendix
HLH = as defined in section 10.5.1 of this
appendix
2,080 = as defined in section 10.2.1.1 of this
appendix
ESOR = as defined in section 10.5.3 of this
appendix.
10.5.3 Average annual electric
energy consumption for electric boilers
located in a different geographic region
of the United States and in buildings
with different design heating
requirements. For electric boilers, the
average annual electric energy
consumption for a specific geographic
region and a specific typical design
heating requirement (EER) is expressed
in kilowatt-hours and defined as:
EER = 100 (0.77) [QOUT/(1+a)] HLH/
(3.412 AFUE) + ESOR
Where:
100 = as defined in section 10.2.3 of this
appendix
0.77 = as defined in section 10.2.1.1 of this
appendix
QOUT = as defined in section 11.2.8.1 of
ASHRAE 103–2017
a = as defined in section 11.2.8.2 of ASHRAE
103–2017
HLH = as defined in section 10.5.1 of this
appendix
3.412 = as defined in section 10.2.3 of this
appendix
AFUE = as defined in section 10.2.3 of this
appendix
ESOR = ESO as defined in section 10.7 of this
appendix, except that in the equation for
ESO, the term BOH is multiplied by the
expression (HLH/2080) to get the
PO 00000
Frm 00046
Fmt 4701
Sfmt 4700
appropriate regional accounting of
standby mode and off mode loss.
10.6 [Reserved]
10.7 Average annual electrical
standby mode and off mode energy
consumption. Calculate the annual
electrical standby mode and off mode
energy consumption (ESO) in kilowatthours, defined as:
ESO = (PW,SB (4160¥BOH) + 4600
PW,OFF) K
Where:
PW,SB = boiler standby mode power, in watts,
as measured in section 8.9.1 of this
appendix
4,160 = average heating season hours per year
BOH = total burner operating hours as
calculated in section 10.2 of this
appendix for gas or oil-fueled boilers.
Where for gas or oil-fueled boilers
equipped with single-stage controls,
BOH = BOHSS; for gas or oil-fueled
boilers equipped with two-stage controls,
BOH = (BOHR + BOHH); and for gas or
oil-fueled boilers equipped with stepmodulating controls, BOH = (BOHR +
BOHM). For electric boilers, BOH =
100(2080)(0.77)[QOUT/(1+a)]/(Ein
3412(AFUE))
4,600 = as defined in section 11.4.12 of
ASHRAE 103–2017
PW,OFF = boiler off mode power, in watts, as
measured in section 8.9.2 of this
appendix
K = 0.001 kWh/Wh, conversion factor from
watt-hours to kilowatt-hours
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.2.1.1 of this
appendix
0.77 = as defined in section 10.2.1.1 of this
appendix
QOUT = as defined in section 11.2.8 of
ASHRAE 103–2017
a = as defined in section 11.2.8.2 of ASHRAE
103–2017
Ein = steady-state electric rated power, in
kilowatts, from section 9.3 of ASHRAE
103–2017
3412 = as defined in section 10.3 of this
appendix
AFUE = as defined in section 11.1 of
ASHRAE 103–2017 in percent.
BILLING CODE 6450–01–P
E:\FR\FM\13MRR2.SGM
13MRR2
Federal Register / Vol. 88, No. 48 / Monday, March 13, 2023 / Rules and Regulations
15555
[FR Doc. 2023–03982 Filed 3–10–23; 8:45 am]
VerDate Sep<11>2014
20:33 Mar 10, 2023
Jkt 259001
PO 00000
Frm 00047
Fmt 4701
Sfmt 9990
E:\FR\FM\13MRR2.SGM
13MRR2
ER13MR23.006
ddrumheller on DSK120RN23PROD with RULES2
BILLING CODE 6450–01–C
Agencies
[Federal Register Volume 88, Number 48 (Monday, March 13, 2023)]
[Rules and Regulations]
[Pages 15510-15555]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2023-03982]
[[Page 15509]]
Vol. 88
Monday,
No. 48
March 13, 2023
Part II
Department of Energy
-----------------------------------------------------------------------
10 Part 429, 430
Energy Conservation Program: Test Procedure for Consumer Boilers; Final
Rule
Federal Register / Vol. 88 , No. 48 / Monday, March 13, 2023 / Rules
and Regulations
[[Page 15510]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 430
[EERE-2019-BT-TP-0037]
RIN 1904-AE83
Energy Conservation Program: Test Procedure for Consumer Boilers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (``DOE'') amends its test
procedure for consumer boilers established under the Energy Policy and
Conservation Act. This rulemaking fulfills DOE's obligation to review
its test procedures for covered products at least once every seven
years. The revisions include: incorporating by reference the latest
versions of the industry standards currently referenced in the Federal
test procedure; relocating the test procedure to a new appendix
separate from the residential furnace test procedure; removing an
extraneous definition from its regulatory definitions; and making
clarifying corrections to calculations. These revisions will improve
the representativeness of the test method and will not be unduly
burdensome to conduct.
DATES: The effective date of this rule is April 12, 2023. The
amendments will be mandatory for product testing starting September 11,
2023.
The incorporation by reference of certain material listed in the
rule is approved by the Director of the Federal Register as of April
12, 2023. The incorporation by reference of certain other material
listed in the rule was approved by the Director of the Federal Register
on March 23, 2009, and February 16, 2016.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at www.regulations.gov.
All documents in the docket are listed in the www.regulations.gov
index. However, not all documents listed in the index may be publicly
available, such as those containing information that is exempt from
public disclosure.
A link to the docket web page can be found at www.regulations.gov/docket/EERE-2019-BT-TP-0037. The docket web page contains instructions
on how to access all documents, including public comments, in the
docket.
For further information on how to review the docket, contact the
Appliance and Equipment Standards Program staff at (202) 287-1445 or by
email: [email protected]">ApplianceStandards[email protected].
FOR FURTHER INFORMATION CONTACT:
Ms. Julia Hegarty, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, EE-2J,
1000 Independence Avenue SW, Washington, DC 20585-0121. Telephone:
(240) 597-6737. Email: [email protected]">ApplianceStandards[email protected].
Ms. Amelia Whiting, U.S. Department of Energy, Office of the
General Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC
20585-0121. Telephone: (202) 586-2588. Email:
[email protected].
SUPPLEMENTARY INFORMATION: DOE maintains material previously approved
for incorporation by reference in part 430: ANSI/ASHRAE 103-1993 and
ASTM D2156-09 (Reapproved 2013). DOE incorporates by reference the
following industry standards into 10 CFR part 430:
ANSI/ASHRAE Standard 41.6-2014, ``Standard Method for Humidity
Measurement,'' ANSI-approved July 3, 2014 (``ASHRAE 41.6-2014'').
ANSI/ASHRAE 103-2017, ``Method of Testing for Annual Fuel
Utilization Efficiency of Residential Central Furnaces and Boilers,''
ANSI-approved July 3, 2017 (``ASHRAE 103-2017'').
Copies ofANSI/ASHRAE 41.6-2014 and ANSI/ASHRAE 103-2017 can be
obtained from the American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc. (ASHRAE), 180 Technology Parkway NW,
Peachtree Corners, GA 30092, (800) 527-4723 or (404) 636-8400, or
online at www.ashrae.org.
ASTM International (``ASTM'') Standard D2156-09 (Reapproved 2018),
``Standard Test Method for Smoke Density in Flue Gases from Burning
Distillate Fuels,''approved October 1, 2018 (``ASTM D2156-09
(R2018)'').
Copies of ASTM D2156-09 (R2018) can be obtained from ASTM
International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken,
PA 19428-2959 or online at www.astm.org.
International Electrotechnical Commission (``IEC'') 62301,
``Household electrical appliances--Measurement of standby power,''
(Edition 2.0) 2011-01 (``IEC 62301'').
Copies of IEC 62301 can be obtained from the International
Electrotechnical Commission (``IEC''), 3 Rue de Varembe, Case Postale
131, 1211 Geneva 20, Switzerland; or online at webstore.iec.ch.
See section IV.N of this document for a further discussion of these
standards.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Scope of Applicability
1. Combination Space/Water Heating Boilers
2. Heat Pump Boilers
B. Definitions
C. Metric
D. Updates to Industry Standards
1. ANSI/ASHRAE 103
2. IEC 62301 and ASTM D2156-09
E. Steady-State Efficiency for Condensing Modulating Boilers
F. Corrections and Clarifications
1. Off-Cycle Losses
2. Conversion Factor for British Thermal Units
3. Oil Pressure Instrumentation Error
4. Gas Inlet Conditions
5. Active Mode Electrical Energy Consumption
6. Circulator Pumps
7. Units With Draft Hoods or Draft Diverters
8. Rounding of AFUE
G. Other Test Procedure Topics
1. Outdoor Design Temperature
2. Ambient Conditions
3. Combustion Settings
4. Supplemental Test Instructions
5. Input Rates for Step Modulating Boilers
6. Return Water Temperature
7. Standby Mode and Off Mode Electrical Energy Consumption
8. Full Fuel Cycle Efficiency
9. Idle Losses
H. Alternative Efficiency Determination Methods
I. Certification Provisions for Cast-Iron Boilers
J. Effective and Compliance Dates
K. Test Procedure Costs
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866 and 13563
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by Reference
V. Approval of the Office of the Secretary
[[Page 15511]]
I. Authority and Background
Furnaces, which include consumer boilers, are included in the list
of ``covered products'' for which the U.S. Department of Energy
(``DOE'') is authorized to establish and amend energy conservation
standards and test procedures. (42 U.S.C. 6291(23); 42 U.S.C.
6292(a)(5)) DOE's energy conservation standards and test procedures for
consumer boilers are currently prescribed at 10 CFR 430.32(e)(2) and 10
CFR part 430, subpart B, appendix N, Uniform Test Method for Measuring
the Energy Consumption of Furnaces and Boilers (``appendix N''),
respectively.\1\ The following sections discuss DOE's authority to
establish test procedures for consumer boilers and relevant background
information regarding DOE's consideration of test procedures for this
product.
---------------------------------------------------------------------------
\1\ Upon the effective date of this final rule, the test
procedure for consumer boilers will be relocated to 10 CFR 430,
subpart B, appendix EE.
---------------------------------------------------------------------------
A. Authority
The Energy Policy and Conservation Act, Public Law 94-163, as
amended (``EPCA''),\2\ authorizes DOE to regulate the energy efficiency
of a number of consumer products and certain industrial equipment. (42
U.S.C. 6291-6317) Title III, Part B of EPCA \3\ established the Energy
Conservation Program for Consumer Products Other Than Automobiles,
which sets forth a variety of provisions designed to improve energy
efficiency. These products include furnaces, which include consumer
boilers, the subject of this document. (42 U.S.C. 6292(a)(5))
---------------------------------------------------------------------------
\2\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020), which reflect the last statutory amendments that impact
Parts A and A-1 of EPCA.
\3\ For editorial reasons, upon codification in the U.S. Code,
Part B was redesignated Part A.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. Relevant
provisions of EPCA specifically include definitions (42 U.S.C. 6291),
test procedures (42 U.S.C. 6293), labeling provisions (42 U.S.C. 6294),
energy conservation standards (42 U.S.C. 6295), and the authority to
require information and reports from manufacturers (42 U.S.C. 6296).
The testing requirements consist of test procedures that
manufacturers of covered products must use as the basis for (1)
certifying to DOE that their products comply with the applicable energy
conservation standards adopted under EPCA (42 U.S.C. 6295(s)), and (2)
making other representations about the efficiency of those products (42
U.S.C. 6293(c)). Similarly, DOE must use these test procedures to
determine whether the products comply with any relevant standards
promulgated under EPCA. (42 U.S.C. 6295(s))
Federal energy efficiency requirements for covered products
established under EPCA generally supersede State laws and regulations
concerning energy conservation testing, labeling, and standards. (42
U.S.C. 6297) DOE may, however, grant waivers of Federal preemption for
particular State laws or regulations, in accordance with the procedures
and other provisions of EPCA. (42 U.S.C. 6297(d))
Under 42 U.S.C. 6293, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered products. EPCA requires that any test procedures prescribed or
amended under this section shall be reasonably designed to produce test
results which measure energy efficiency, energy use, or estimated
annual operating cost of a covered product during a representative
average use cycle (as determined by the Secretary) or period of use and
shall not be unduly burdensome to conduct. (42 U.S.C. 6293(b)(3))
EPCA also requires that, at least once every 7 years, DOE evaluate
test procedures for each type of covered product, including consumer
boilers, to determine whether amended test procedures would more
accurately or fully comply with the requirements for the test
procedures to not be unduly burdensome to conduct and be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs during a representative average use
cycle or period of use. (42 U.S.C. 6293(b)(1)(A))
If the Secretary determines, on her own behalf or in response to a
petition by any interested person, that a test procedure should be
prescribed or amended, the Secretary shall promptly publish in the
Federal Register proposed test procedures and afford interested persons
an opportunity to present oral and written data, views, and arguments
with respect to such procedures. The comment period on a proposed rule
to amend a test procedure shall be at least 60 days and may not exceed
270 days. In prescribing or amending a test procedure, the Secretary
shall take into account such information as the Secretary determines
relevant to such procedure, including technological developments
relating to energy use or energy efficiency of the type (or class) of
covered products involved. (42 U.S.C. 6293(b)(2)) If DOE determines
that test procedure revisions are not appropriate, DOE must publish its
determination not to amend the test procedures.
In addition, EPCA requires that DOE amend its test procedures for
all covered products to integrate measures of standby mode and off mode
energy consumption into the overall energy efficiency, energy
consumption, or other energy descriptor, unless the current test
procedure already incorporates the standby mode and off mode energy
consumption, or if such integration is technically infeasible. (42
U.S.C. 6295(gg)(2)(A)) If an integrated test procedure is technically
infeasible, DOE must prescribe separate standby mode and off mode
energy use test procedures for the covered product, if a separate test
is technically feasible. (Id.) Any such amendment must consider the
most current versions of the International Electrotechnical Commission
(``IEC'') Standard 62301 \4\ and IEC Standard 62087 \5\ as applicable.
(42 U.S.C. 6295(gg)(2)(A))
---------------------------------------------------------------------------
\4\ IEC 62301, Household electrical appliances--Measurement of
standby power (Edition 2.0, 2011-01).
\5\ IEC 62087, Audio, video and related equipment--Methods of
measurement for power consumption (Edition 1.0, Parts 1-6: 2015,
Part 7: 2018).
---------------------------------------------------------------------------
DOE is publishing this final rule in satisfaction of the 7-year
review requirement specified in EPCA. (42 U.S.C. 6293(b)(1)(A))
B. Background
As stated, DOE's existing test procedure for consumer boilers
appears at Title 10 of CFR part 430, subpart B, appendix N, Uniform
Test Method for Measuring the Energy Consumption of Furnaces and
Boilers (``appendix N'') and is used to determine the annual fuel
utilization efficiency (``AFUE''), which is the regulatory metric for
consumer boilers.
DOE most recently updated its test procedure for consumer boilers
in a final rule published in the Federal Register on January 15, 2016
(``January 2016 Final Rule''). 81 FR 2628. The January 2016 Final Rule
amended the existing DOE test procedure for consumer boilers to improve
the consistency and accuracy of test results generated using the DOE
test procedure and to reduce test burden. In particular, the
modifications relevant to consumer boilers included: (1) clarifying the
definition of the electrical power term ``PE''; (2) adopting a smoke
stick test for determining whether minimum default
[[Page 15512]]
draft factors can be applied; (3) allowing for optional measurement of
condensate during establishment of steady-state conditions; (4)
updating references to the applicable installation and operation
(``I&O'') manual and providing clarifications for when the I&O manual
does not specify test setup; and (5) revising the AFUE reporting
precision. DOE also revised the definitions of several terms in the
test procedure and added an enforcement provision to provide a method
of test for DOE to determine compliance with the automatic means design
requirement mandated by the Energy Independence and Security Act of
2007, Public Law 110-140 (Dec. 19, 2007). 81 FR 2628, 2629-2630.
On May 15, 2020, DOE published in the Federal Register a request
for information (``May 2020 RFI'') seeking comments on the existing DOE
test procedure for consumer boilers, which incorporates by reference
ANSI/ASHRAE Standard 103-1993. 85 FR 29352. ANSI/ASHRAE 103-1993
provides test procedures for determining the AFUE of residential
central furnaces and boilers. In the May 2020 RFI, DOE requested
comments, information, and data about a number of issues, including:
(1) the test procedure's scope and definitions; (2) updates to industry
standards; (3) ambient test conditions; (4) provisions for testing
boilers with manually adjustable combustion airflow; (5) calculation of
steady-state heat loss for condensing, modulating boilers; and (6)
provisions for testing step modulating boilers. Id. at 85 FR 29354-
29357. DOE also sought comment generally on whether the current test
procedures are reasonably designed to produce results that measure
energy efficiency during a representative average use cycle or period
of use, whether any potential amendments would make the test procedure
unduly burdensome to conduct, whether existing test procedures limit a
manufacturer's ability to provide additional features, the impact of
any potential amendments on manufacturers including small businesses,
whether there are any potential issues related to emerging smart
technologies, and generally any other aspect of the test procedure for
consumer boilers. Id. at 85 FR 23957.
On March 15, 2022, DOE published in the Federal Register a notice
of proposed rulemaking (``March 2022 NOPR'') proposing to amend the
current test procedure to incorporate by reference the most current
revision to the applicable industry standard that was available at the
time, ANSI/ASHRAE 103-2017, ``Methods of Testing for Annual Fuel
Utilization Efficiency of Residential Central Furnaces and Boilers,''
as well as updating the definitions to reflect the changes in ANSI/
ASHRAE 103-2017 as compared to the version of the standard currently
incorporated by reference (i.e., ANSI/ASHRAE 103-1993). 87 FR 14624. In
addition, the March 2022 NOPR proposed to update appendix N to remove
the provisions applicable only to consumer boilers and to rename the
appendix ``Uniform Test Method for Measuring the Energy Consumption of
Furnaces.'' Correspondingly, DOE proposed to relocate the test
procedure specific to consumer boilers at 10 CFR 430 subpart B to a new
appendix, EE, ``Uniform Test Method for Measuring the Energy
Consumption of Boilers'' (``appendix EE''). Id.
On April 7, 2022, DOE held a public meeting via webinar to solicit
feedback from stakeholders on the requests for comment in the March
2022 NOPR.
DOE received comments in response to the March 2022 NOPR from the
interested parties listed in Table I.1.
Table I.1--List of Commenters With Written Submission in Response to the March 2022 NOPR
----------------------------------------------------------------------------------------------------------------
Reference in this Comment No. in
Commenter(s) final rule the docket Commenter type
----------------------------------------------------------------------------------------------------------------
American Gas Association and American Public Gas AGA and APGA.......... 25 Utility Associations.
Association.
Air-Conditioning, Heating, and Refrigeration AHRI.................. 26 Trade Association.
Institute.
A.O. Smith Corporation.......................... A.O. Smith............ 24 Manufacturer.
John Busse...................................... Busse................. 22 Individual.
Bradford White Corporation...................... BWC................... 19 Manufacturer.
Pacific Gas and Electric Company, San Diego Gas CA IOUs............... 20 Utilities.
and Electric, and Southern California Edison
(collectively, the California Investor-Owned
Utilities).
Crown Boiler Company............................ Crown................. 16 Manufacturer.
Appliance Standards Awareness Project, American Joint Advocates....... 21 Efficiency
Council for an Energy-Efficient Economy, Organizations.
Consumer Federation of America, National
Consumer Law Center Natural Resources Defense
Council, and Northwest Energy Efficiency
Alliance.
New York State Energy Research and Development NYSERDA............... 23 State Agency.
Authority.
Rheem Manufacturing Company..................... Rheem................. 18 Manufacturer.
U.S. Boiler Company............................. U.S. Boiler........... 17 Manufacturer.
----------------------------------------------------------------------------------------------------------------
A parenthetical reference at the end of a comment quotation or
paraphrase provides the location of the item in the public record.\6\
To the extent that interested parties have provided written comments
that are substantively consistent with any oral comments provided
during the April 7, 2022, public meeting, DOE cites the written
comments throughout this final rule. DOE did not identify any oral
comments provided during the webinar that are not substantively
addressed by written comments.
---------------------------------------------------------------------------
\6\ The parenthetical reference provides a reference for
information located in the docket of DOE's rulemaking to develop
test procedures for consumer boilers. (Docket No. EERE-2019-BT-TP-
0037, maintained at www.regulations.gov.) The references are
arranged as follows: (commenter name, comment docket ID number, page
of that document).
---------------------------------------------------------------------------
II. Synopsis of the Final Rule
In this final rule, DOE updates appendix N to remove the provisions
applicable only to consumer boilers and to rename the appendix
``Uniform Test Method for Measuring the Energy Consumption of
Furnaces.'' Correspondingly, this final rule establishes a new test
procedure specific to consumer boilers in a new appendix EE. In
appendix EE, DOE includes all provisions currently included in appendix
N relevant to consumer boilers, with the following modifications:
(1) Incorporate by reference the current version of the applicable
industry standard, ANSI/ASHRAE 103-2017, ``Methods of Testing for
Annual Fuel Utilization Efficiency of
[[Page 15513]]
Residential Central Furnaces and Boilers,'' which includes several
updates to the test method.
(2) Incorporate by reference the current version of ASTM Standard
D2156-09 (Reapproved 2018), ``Standard Test Method for Smoke Density in
Flue Gases from Burning Distillate Fuels.''
(3) Incorporate by reference ANSI/ASHRAE 41.6-2014, ``Standard
Method for Humidity Measurement.''
(4) Update the definitions to reflect the changes in ANSI/ASHRAE
103-2017 as compared to ANSI/ASHRAE 103-1993.
(5) Provide corrections to erroneous calculations and add
clarifications to test conditions and setup requirements.
DOE is also removing the definition of ``outdoor furnace or
boiler'' from 10 CFR 430.2.
The adopted amendments are summarized in Table II.1 compared to the
test procedure provision prior to the amendment, as well as the reason
for the adopted change.
Table II.1--Summary of Changes in the Amended Test Procedure
------------------------------------------------------------------------
DOE test procedure prior to
amendment Amended test procedure Attribution
------------------------------------------------------------------------
Incorporated by reference Incorporates by Harmonization
industry standard ANSI/ASHRAE reference ANSI/ASHRAE with industry
103-1993. 103-2017 in the new standard
appendix EE. update.
Incorporated by reference the Incorporates by Harmonization
procedure for adjusting oil- reference the with industry
fired burner by referencing procedure for standard
industry standard ASTM D2156- adjusting oil-fired update.
09 (Reapproved 2013). burner by referencing
industry standard
ASTM D2156-09
(Reapproved 2018) in
the new appendix EE.
Limited the maximum relative Incorporates by Referenced by
humidity of the test room reference ANSI/ASHRAE industry
during certain tests but did 41.6-2014 standard ANSI/
not provide specific instructions for ASHRAE 103-
instructions for how to measuring relative 2017, which is
measure relative humidity. humidity of the test being
room in the new incorporated by
appendix EE. reference in
this final
rule.
Included a definition for Removes the definition Unused
``outdoor furnace or boiler'' for ``outdoor furnace definition.
at 10 CFR 430.2. or boiler''.
Included an undefined term, Adds a definition for Increase clarity
``standard cubic foot of ``standard cubic foot for testing
gas''. of gas'' in new conditions.
appendix EE.
Defined ``control'' and Adopts the definitions Harmonization
``isolated combustion for the terms with industry
system'' in appendix N. ``control'' and standard
``isolated combustion update.
system'' from ASHRAE
103-2017 in new
appendix EE.
Referenced calculations in Includes an amended Correction.
ANSI/ASHRAE 103-1993 which calculation for
yielded a circular reference balance-point
when calculating the steady- temperature (TC)
state efficiency for which resolves the
condensing modulating boilers. circular reference in
new appendix EE.
Referenced Table 9 in ANSI/ References Table 7 of Harmonization
ASHRAE 103-1993, which ANSI/ASHRAE 103-2017 with industry
assigned fixed values for the in the new appendix standard
average on-time and off-time EE, which uses update.
per cycle for two-stage and calculations for
modulating boilers. determining the
average on-time and
off-time per cycle
for two-stage and
modulating boilers.
Specified cycle times (tON and Provides additional Clarification to
tOFF) to a fraction of a specification in reduce test
second through reference to appendix EE to burden.
ANSI/ASHRAE 103-1993 Table 9. require that
calculated cycle
timings shall be
rounded to the
nearest second.
Calculated oversize factor Adopts the ANSI/ASHRAE Harmonization
from a lookup table based on 103-2017 methodology with industry
design heating requirement of assigning a standard
(``DHR'') in ANSI/ASHRAE 103- constant value of update.
1993. 0.70 to [alpha] to
represent the
national average
oversize factor in
appendix EE.
Used a purge time limit of 5 Applies the 30-second Harmonization
seconds to determine whether limit in appendix EE with industry
heat-up and cool-down tests for determining when standard
may be optionally omitted, the heat-up and cool- update.
whereas a purge time limit of down tests may be
30 seconds was used to optionally omitted.
determine whether a post-
purge (tP) of 0 seconds could
be assigned in calculations.
Limited the maximum value of Removes the maximum Harmonization
post-purge (tP) to 180 value of 180 seconds with industry
seconds if a purge time of in appendix EE and standard
greater than 3 minutes was requires an update.
observed. additional
temperature
measurement to be
taken if the post-
purge is greater than
3 minutes.
Referenced calculations for Specifies the correct Correction.
off-cycle infiltration losses calculation for off-
in ANSI/ASHRAE 103-1993 which cycle infiltration
had a typographical error losses through
where the conversion from reference to ANSI/
minutes to hours was ASHRAE 103-2017 and
performed incorrectly. corrects minutes to
hours conversion
error in new appendix
EE.
Provided inconsistent unit Corrects the Correction.
conversion factor from watts conversion factor
(``W'') to British thermal from W to Btu/h to
units per hour (``Btu/h''), 3.412 throughout new
using values of 3.412 or appendix EE.
3.413.
Required the use of a gas Requires the use of a Clarification to
having a specific gravity as gas having a specific reduce test
shown in Table 1 of ANSI/ gravity burden.
ASHRAE 103-1993. ``approximate'' to
what is shown in
Table 1 of ANSI/
ASHRAE 103-2017 in
the new appendix EE.
Referenced incorrect sections Revises 10 CFR Correction.
of appendix N test procedure 430.23(n)(1) to
regarding average annual update references
auxiliary electrical regarding average
consumption determination annual auxiliary
provisions at 10 CFR electrical
430.23(n)(1). consumption to the
correct sections of
appendix N and the
new appendix EE.
Referenced values in ANSI/ References values in Harmonization
ASHRAE 103-1993 for ANSI/ASHRAE 103-2017 with industry
determining national average for determining standard
burner operating hours national average BOH, update.
(``BOH''), average annual average annual EF,
fuel energy consumption and average annual
(``EF''), and average annual EAE in the new
auxiliary electrical energy appendix EE.
consumption (``EAE'').
[[Page 15514]]
Included instructions for the Includes units of Correction.
setup of boilers with draft measure for R-value
hoods or draft diverters in the new appendix
which specified a minimum R- EE.
value for insulation but did
not specify the units of
measure for R-value.
------------------------------------------------------------------------
DOE has determined that the amendments described in section III of
this document and adopted in this final rule will not substantively
impact the measured efficiency of consumer boilers or require retesting
or recertification solely as a result of DOE's adoption of the
amendments to the test procedures. Additionally, DOE has determined
that the amendments will not increase the cost of testing. Discussion
of DOE's actions is addressed in detail in section III of this
document.
The effective date for the amended test procedures adopted in this
final rule is 30 days after publication of this document in the Federal
Register. Representations of energy use or energy efficiency must be
based on testing in accordance with the amended test procedures
beginning 180 days after the publication of this final rule.
III. Discussion
The subsequent sections of this final rule discuss specific topics
raised in this rulemaking, including comments DOE received in response
to the March 2022 NOPR. These topics include: scope of applicability of
the test procedure, definitions in the test procedure, the AFUE metric,
updates to industry standards, clarifications and corrections to the
current test procedure, and test conditions.
In addition, DOE received comments relating to the general
processes by which DOE amends test procedures and energy conservation
standards for covered products and equipment.
BWC urged DOE to consider the cumulative regulatory burden placed
on manufacturers that produce several different types of regulated
products for which there are simultaneous rulemakings. BWC noted that
additional burdens on manufacturers include changes to ENERGY STAR
specifications; the Securities and Exchange Commission's proposed rule
to enhance and standardize climate-related disclosures; updated state
and local codes; demand-response requirements for electric water
heaters in Western States; lower nitrogen oxides (NOX)
emissions proposals in the State of California; proposed amendments to
California Proposition 65; and extended producer responsibility
legislation recently enacted in both Maine and Oregon. (BWC, No. 19 at
p. 4-5)
In response, DOE notes that cumulative regulatory burden on
manufacturers is assessed as part of energy conservation standards
rulemakings. The amendments to the consumer boilers test procedure, as
promulgated by this final rule, are not expected to add burden to
manufacturers because the amendments do not substantially impact
efficiency ratings or alter the type of equipment necessary to perform
testing. Test costs and burden are discussed in section III.K of this
document.
AGA and APGA commented that DOE should implement the
recommendations from the recent National Academies of Sciences,
Engineering, and Medicine report (``NASEM report'') \7\ into all of its
appliance rulemakings for test procedures or energy conservation
standards. AGA and APGA reiterated recommendations pertaining to
analyses that DOE conducts in order to determine whether potential new
or amended energy conservation standards are technologically feasible
and economically justified. (AGA and APGA, No. 25, p. 3) For example,
AGA and APGA highlighted the NASEM report's recommendations that DOE
pay greater attention to the justification for its standards, expand
the Cost Analysis segment of the Engineering Analysis for its rules,
put greater weight on ex post and market-based evidence markups, place
greater emphasis on providing an argument for the plausibility and
magnitude of any market failure related to the energy efficiency gap,
and give greater attention to a broader set of potential market
failures on the supply side. Id.
---------------------------------------------------------------------------
\7\ Although not specified, DOE interprets this comment to refer
to the National Academies of Science, Engineering, and Medicine 2021
report entitled ``Review of Methods Used by the U.S. Department of
Energy in Setting Appliance and Equipment Standards.'' Copies of the
report are available at nap.nationalacademies.org/catalog/25992/review-of-methods-used-by-the-us-department-of-energy-in-setting-appliance-and-equipment-standards.
---------------------------------------------------------------------------
Given that this is a test procedure rulemaking for which DOE must
meet specific statutory criteria as outlined in 42 U.S.C. 6293(b)(3),
the recommendations in the NASEM report which pertain specifically to
the processes by which DOE analyzes energy conservation standards are
misplaced. DOE will consider this comment in a separate rulemaking
considering all product categories.
A. Scope of Applicability
As discussed, in the context of ``covered products,'' EPCA includes
boilers in the definition of ``furnace.'' (42 U.S.C. 6291(23)) EPCA
defines the term ``furnace'' to mean a product which utilizes only
single-phase electric current, or single-phase electric current or DC
current in conjunction with natural gas, propane, or home heating oil,
and which: (1) is designed to be the principal heating source for the
living space of a residence; (2) is not contained within the same
cabinet with a central air conditioner whose rated cooling capacity is
above 65,000 Btu/h; (3) is an electric central furnace, electric
boiler, forced-air central furnace, gravity central furnace, or low
pressure steam or hot water boiler; and (4) has a heat input rate of
less than 300,000 Btu/h for electric boilers and low pressure steam or
hot water boilers and less than 225,000 Btu/h for forced-air central
furnaces, gravity central furnaces, and electric central furnaces. Id.
DOE has codified this definition in its regulations at 10 CFR 430.2.
DOE defines ``electric boiler'' as an electrically powered furnace
designed to supply low pressure steam or hot water for space heating
application. A low pressure steam boiler operates at or below 15 pounds
per square inch gauge (``psig'') steam pressure; a hot water boiler
operates at or below 160 psig water pressure and 250 degrees Fahrenheit
([deg]F) water temperature. 10 CFR 430.2.
DOE defines ``low pressure steam or hot water boiler'' as an
electric, gas or oil burning furnace designed to supply low pressure
steam or hot water for space heating application. 10 CFR 430.2. As with
an electric boiler, a low pressure steam boiler operates at or below 15
pounds psig steam pressure; a hot water boiler operates at or below 160
psig water pressure and 250 [deg]F water temperature. Id.
The scope of the test procedure for consumer boilers is currently
specified
[[Page 15515]]
in section 1 of appendix N, which references section 2 of ANSI/ASHRAE
103-1993. In relevant part, section 2 of ANSI/ASHRAE 103-1993 states
that the industry test standard applies to boilers \8\ with inputs less
than 300,000 Btu/h; having gas, oil, or electric input; and intended
for use in residential applications. Further, ANSI/ASHRAE 103-1993
applies to equipment that utilizes single-phase electric current or
low-voltage DC current.
---------------------------------------------------------------------------
\8\ ASHRAE 103-1993 defines a boiler as ``a self-contained fuel-
burning or electrically heated appliance for supplying low pressure
steam or hot water for space heating application.'' This definition
covers electric boilers and low pressure steam or hot water boilers
as those terms are defined by DOE at 10 CFR 430.2.
---------------------------------------------------------------------------
DOE is not changing the scope of products covered by its consumer
boiler test procedure in this final rule. The following sections
discuss specific types of boilers that DOE addressed in the March 2022
NOPR with respect to whether such products are covered by the scope of
DOE's test procedure.
1. Combination Space/Water Heating Boilers
Some consumer boilers are capable of providing both space heating
and domestic hot water heating, and are often referred to as
``combination'' boilers. In the March 2022 NOPR, DOE responded to
comments from the Northwest Energy Efficiency Alliance (``NEEA'') and
Rheem recommending that DOE consider developing a separate test
procedure for combination space and domestic hot water boilers. 87 FR
14622, 14626-14627. While DOE did not propose a specific definition for
combination space and water heating boilers in the NOPR, DOE noted
that, to the extent that a combination space and water heating product
meets the definition of electric boiler or low pressure steam or hot
water boiler, it is subject to the test procedure at appendix N and
energy conservation standards for consumer boilers at 10 CFR
430.32(e)(2), and must be tested and rated accordingly. 87 FR 14622,
14625-14626. DOE also stated that it is unaware of any design
characteristics of combination space and water heating products that
would prevent their testing according to appendix N. Id.
DOE did not receive any comments in response to the March 2022 NOPR
with regard to combination space and heating water boilers. In this
final rule, DOE reiterates its statements presented in the March 2022
NOPR with respect to combination boilers. To the extent that a
combination space and water heating product meets the definition of
electric boiler or low pressure steam or hot water boiler, it is
subject to the test procedure at appendix N (or, as of the effective
date of this final rule, appendix EE) and energy conservation standards
for consumer boilers at 10 CFR 430.32(e)(2), and must be tested and
rated accordingly.
2. Heat Pump Boilers
In the March 2022 NOPR, DOE discussed comments received in response
to the May 2021 RFI with regard to hydronic air-to-water and water-to-
water heat pumps. DOE tentatively determined that air-to-water and
water-to-water heat pumps meet the definitional criteria to be
classified as a consumer boiler. 87 FR 14622, 14625. DOE noted that
these products utilize only single-phase electric current, are designed
to be the principal heating source for the living space of a residence,
are not contained within the same cabinet with a central air
conditioner whose rated cooling capacity is above 65,000 Btu/h, meet
the definition of an electric boiler,\9\ and have a heat input rate of
less than 300,000 Btu/h (i.e., the requirement for electric boilers).
As such, they meet the criteria of ``furnace'' as defined in 10 CFR
430.2. Id. at 87 FR 14625-14626.
---------------------------------------------------------------------------
\9\ ``Electric boiler'' means an electrically powered furnace
designed to supply low pressure steam or hot water for space heating
application. A low pressure steam boiler operates at or below 15
psig steam pressure; a hot water boiler operates at or below 160
psig water pressure and 250 [deg]F water temperature. 10 CFR 430.2.
---------------------------------------------------------------------------
In the March 2022 NOPR, DOE also tentatively determined that the
test procedure in appendix N does not address such products and would
not provide a rated value that is representative of the performance of
these products. Id. at 14626. In particular, DOE noted that the AFUE
metric for electric boilers in ANSI/ASHRAE 103-1993 is calculated as
100 percent minus jacket loss,\10\ which provides a representative
measure of efficiency for electric boilers using electric resistance
technology, for which an efficiency value of 100 percent (the ratio of
heat output to energy input) is the maximum upper limit that
technically could be achieved. DOE tentatively concluded that the AFUE
metric would not provide a representative or meaningful measure of
efficiency for a boiler with a heat pump supplying the heat input,
because heat pump efficiency (in terms of heat output to energy input)
typically exceeds 100 percent, and the AFUE metric does not allow for
ratings greater than 100 percent for electric boilers. Id.
---------------------------------------------------------------------------
\10\ The term ``jacket loss'' is used by industry to mean the
transfer of heat from the outer surface (i.e., jacket) of a boiler
to the ambient air surrounding the boiler.
---------------------------------------------------------------------------
Based on these considerations, DOE tentatively determined that
hydronic air-to-water and water-to-water heat pumps are consumer
boilers under EPCA, but that due to the lack of a Federal test
procedure, such products are not subject to the current performance
standards at 10 CFR 430.32(e). Id.
In response to the March 2022 NOPR, Crown and U.S. Boiler \11\
stated that hydronic heat pumps should not be classified as boilers
under EPCA because hydronic heat pumps cannot deliver water at the same
temperatures and heating capacities as traditional boilers. Crown and
U.S. Boiler further commented that it is unclear whether hydronic heat
pumps are ``designed to be the principal heating source for a living
space of a residence'' (a requirement to meet the definition of a
furnace at 10 CFR 430.2) because these products are mostly incapable of
reaching above 150 [deg]F on a design day, whereas traditional boilers
are designed to deliver water at a temperature of 180 [deg]F or higher.
Crown and U.S. Boiler also stated that gas, oil, and electric
resistance boilers are capable of heating any hot water or steam
heating system throughout the entire heating season, whereas hydronic
heat pumps do not have such capabilities. Crown and U.S. Boiler stated
that heat pumps and boilers provide different consumer utility, and
suggested that presenting heat pumps to consumers as ``boilers'' could
create confusion with regard to the different capabilities of each.
(Crown, No. 16 at p. 1-2; -U.S. Boiler, No. 17 at p. 1-2)
---------------------------------------------------------------------------
\11\ DOE notes that both Crown and U.S. Boiler's comments stated
that the companies are subsidiaries of Burnham Holdings, Inc.
(``BHI''). The comments submitted by Crown and U.S. Boiler in
response to the March 2022 NOPR were identical in content.
---------------------------------------------------------------------------
AHRI and AGA and APGA commented that hydronic heat pumps cannot
currently provide the same functionality as boilers for high
temperature installations as they are unable to provide water at or
over 210 [deg]F, and that this lack of utility should disqualify these
products from being considered in the boiler test procedure. (AHRI, No.
26 at p. 2; AGA and APGA, No. 25 at p. 2)
BWC disagreed with DOE's tentative determination that air-to-water
and water-to-water heat pumps should be defined as consumer boilers.
BWC stated that heat pump products and consumer boilers have pronounced
differences that should prevent them from being defined as the same
product.
[[Page 15516]]
BWC noted that boilers and heat pumps \12\ are already separate product
categories on DOE's website and certified separately through DOE's
Compliance Certification Management System. BWC also stated that
hydronic heat pumps are rated to Coefficient of Performance (``COP'')
rather than AFUE (for boilers), and that the unique technologies
utilized by both product types necessitate different methods for
testing and rating them. BWC further stated that consumer boilers are
designed exclusively to provide a heating utility, whereas hydronic
heat pumps can be used to provide both space heating and cooling. (BWC,
No. 19 at p. 2-3)
---------------------------------------------------------------------------
\12\ DOE understands BWC is referring to central air
conditioning and heat pump units.
---------------------------------------------------------------------------
Rheem supported DOE's tentative determination that hydronic air-to-
water and water-to-water heat pumps are consumer boilers under EPCA.
Rheem stated that although these products may not necessarily be able
to achieve the same maximum temperatures as conventional boilers
(without electric resistance or gas backup), hydronic heat pump boilers
can still provide adequate space heating in many applications. Rheem
recommended that DOE either add procedures to test hydronic heat pumps
in this consumer boiler test procedure rulemaking or initiate a
separate test procedure rulemaking. Rheem asserted that these products
perform the same function as other types of boilers and should be
tested and rated in a similar manner, and that DOE could use the
current AFUE test procedure as a guide to produce an ``AFUE metric''
for hydronic heat pumps that combines the various energy use modes and
input rate conditions with test conditions and operating assumptions
that are representative of hydronic heat pumps. Rheem stated that any
differences in ability to meet consumer heating demands should be
considered in the development of energy conservation standards, as
opposed to the test procedure. (Rheem, No. 18 at p. 2)
NYSERDA agreed with DOE's tentative determination that air-to-water
and water-to-water heat pumps should be considered boilers under EPCA.
NYSERDA recommended that DOE develop a test procedure for these heat
pumps and combination space heating and water heating products. NYSERDA
asserted that the adoption of these test procedures will also enable
future standards revisions to adopt more efficient heat pump levels of
performance. (NYSERDA, No. 23 at p. 5-6)
In consideration of the comments received on this issue, as well as
further consideration of the discussion presented in the March 2022
NOPR, DOE has concluded that hydronic air-to-water and water-to-water
heat pumps meet the definitional criteria to be classified as a
consumer boiler. In particular, as noted initially in the March 2022
NOPR, DOE concludes that these products utilize only single-phase
electric current, are designed to be the principal heating source for
the living space of a residence, and are not contained within the same
cabinet with a central air conditioner whose rated cooling capacity is
above 65,000 Btu/h. In addition, electric heat pump boilers meet the
definition of an electric boiler; and gas-fired heat pump boilers meet
the definition of a low pressure steam or hot water boiler and have a
heat input rate of less than 300,000 Btu/h (i.e., the requirement for
electric boilers and low pressure steam or hot water boilers). As such,
these products meet the criteria of ``furnace'' as defined in 10 CFR
430.2.
With respect to comments from Crown, U.S. Boiler, AHRI, and AGA and
APGA suggesting hydronic air-to-water heat pumps and water-to-water
heat pumps should be excluded from the definition because they cannot
provide the same maximum water temperature as non-heat pump hydronic
systems, DOE notes that neither EPCA nor DOE's definitions at 10 CFR
430.2 provide a minimum water temperature requirement. In addition, in
response to comments that hydronic heat pumps serve different
applications than boilers, DOE notes that hydronic heat pumps are
marketed as providing the principal heating source for a residence, and
nothing in EPCA's or DOE's definition would exclude them based on their
ability to also provide cooling.
DOE recognizes that hydronic heat pump products differ
significantly from non-heat pump boilers, and that the current test
procedure for consumer boilers (as well as the amended test procedure
established by this final rule) would not provide test results that are
representative of the energy use or energy efficiency of an air-to-
water or water-to-water heat pump product. Because of these differences
and uncertainty regarding the most representative approach to testing
these products, DOE is not establishing separate test procedures for
hydronic heat pump products in this final rule. Although air-to-water
and water-to-water heat pump products meet all the definitional
criteria to be considered a consumer boiler, the Department requires
more information in order to determine a representative approach for
testing these products. Further consideration of an appropriate test
procedure for such products would be provided in a separate test
procedure rulemaking. Section III.C of this document further discusses
the applicability of the AFUE metric to hydronic heat pump products.
B. Definitions
In addition to the overarching definition of ``furnace'' (which
includes boilers) and the associated definitions for ``electric
boiler'' and ``low pressure steam or hot water boiler'' presented in
section III.A of this document, DOE also has defined ``outdoor
boilers'' and ``weatherized warm air boilers'' at 10 CFR 430.2 as
follows:
``Outdoor furnace or boiler'' is a furnace or boiler
normally intended for installation out-of-doors or in an unheated space
(such as an attic or a crawl space).
``Weatherized warm air furnace or boiler'' means a furnace
or boiler designed for installation outdoors, approved for resistance
to wind, rain, and snow, and supplied with its own venting system.
In the March 2022 NOPR, DOE proposed to remove the definition of
``outdoor furnace or boiler'' from its regulations, noting that the
definition is not used for the energy conservation standards for
boilers at 10 CFR 430.32(e)(2)(iii), nor for applying the test
procedure.\13\ 87 FR 14622, 14626-14627. DOE sought comment on its
proposal to remove the definition of ``outdoor furnace or boiler'' from
its regulations and whether removing the definition for ``outdoor
furnace or boiler'' would impact the application of the test procedure
or energy conservation standards for any such products.
---------------------------------------------------------------------------
\13\ Specifically, with respect to the test procedure, DOE noted
that different jacket loss factors are applied based on whether a
boiler is intended to be installed indoors, outdoors, or as an
isolated combustion system. The heating seasonal efficiency
(EffyHS) calculation, which is an element of AFUE, is
based on the assumption that all weatherized boilers are located
outdoors (see section 10.1 of appendix N). Appendix N does not
specify a separate jacket loss assumption for outdoor furnaces or
boilers.
---------------------------------------------------------------------------
Rheem and BWC supported DOE's proposal to remove the definition of
``outdoor furnace or boiler'' from 10 CFR 430.2. (Rheem, No. 18 at p.
2; BWC, No. 19 at p. 1) A.O. Smith stated that removal of this
definition from the DOE regulations would not have a negative impact on
the application of the test procedure or energy conservation standards.
(A.O. Smith, No. 24 at p. 2) AHRI and AGA and APGA also supported
removing the definition and
[[Page 15517]]
stated that the removal would add clarity and consistency to the test
procedure. (AHRI, No. 26 at p. 2; AGA and APGA, No. 25 at p. 2)
For the reasons discussed in the March 2022 NOPR, and in
consideration of these comments, in this final rule DOE finalizes its
proposal to remove the definition of ``outdoor furnace or boiler'' from
10 CFR 430.2.
In the March 2022 NOPR, DOE proposed to incorporate by reference
ANSI/ASHRAE 103-2017, including the definitions included therein. 87 FR
14622, 14627. DOE noted that ANSI/ASHRAE 103-2017 includes definitions
for ``air intake terminal,'' ``control,'' and ``isolated combustion
system'' that are not in ANSI/ASHRAE 103-1993. Id. The definitions for
``control'' and ``isolated combustion system'' in ANSI/ASHRAE 103-2017
are almost identical to the definitions for those terms currently
defined in sections 2.3 and 2.7 of appendix N, respectively. Therefore,
DOE proposed to remove the definitions for ``control'' and ``isolated
combustion system'' from DOE's consumer boiler test procedure, as they
would be redundant with the definitions incorporated by reference
through ANSI/ASHRAE 103-2017, if the proposal to incorporate by
reference ANSI/ASHRAE 103-2017 were finalized. Id.
Rheem, The CA IOUs, A.O. Smith, AHRI, and AGA and APGA supported
incorporating by reference the definitions in ANSI/ASHRAE 103-2017 and
removing the separate definitions for ``control'' and ``isolated
combustions system'' from DOE's test procedure. (Rheem, No. 18 at p. 3;
CA IOUs, No. 20 at p. 1; A.O. Smith, No. 24 at p. 3; AHRI, No. 26 at p.
2; AGA and APGA, No. 25 at p. 2)
For the reasons discussed in the March 2022 NOPR, and in
consideration of these comments, DOE is removing the separate
definitions for ``control'' and ``isolated combustion system'' from the
consumer boiler test procedure, as proposed in the March 2022 NOPR. The
definitions for these products are instead provided through DOE's
incorporation by reference of ANSI/ASHRAE 103-2017, as discussed
further in section III.D.1 of this final rule.
In response to the March 2022 NOPR, Busse suggested that DOE add a
definition for ``standard cubic unit of gas'' as follows:
``Standard cubic foot of gas: The amount of gas that would occupy 1
cubic foot when at a temperature of 60 [deg]F, if saturated with water
vapor, and under a pressure equivalent to that of 30 inches mercury
column.'' (Busse, No. 22 at p. 9)
Busse stated that a definition of standard cubic foot of gas is
necessary to comply with the conditions specified in section 7.1 of
appendix N, Fuel Supply.\14\ Busse further stated that the suggested
definition would be consistent with industry standards NFPA 54/ANSI
Z223.1, National Fuel Gas Code, and CSA 4.9/ANSI Z21.13, Gas-Fired Low
Pressure Steam and Hot Water Boilers and asserted that manufacturers
are familiar with this definition when conducting performance testing.
Busse noted that the difference between a saturated ``wet'' and
unsaturated ``dry'' cubic foot of gas is 1.73 percent at standard
temperature and pressure. Busse also recommended that DOE modify the
language of section 7.3 of appendix N, Gas Burner, to replace ``gas
characteristics at a temperature of 60 [deg]F and atmospheric pressure
of 30 in of Hg'' with reference to this new definition, i.e., ``gas
characteristics to standard cubic foot of gas, as defined in section 2
of this appendix,'' in specifying the conditions needed to correct the
burner input rate.\15\ (Busse, No. 22 at p. 9-10)
---------------------------------------------------------------------------
\14\ Section 7.1 of appendix N requires determining the actual
higher heating value in Btu per standard cubic foot for the gas to
be used in the test within an error no greater than 1 percent.
\15\ Busse also commented that, with respect to the current
instruction to ``Correct the burner input rate to reflect gas
characteristics,'' technically the Ideal Gas Laws can be applied
only to the volume of gas consumed and the higher heating value, and
not to the burner input rate.
---------------------------------------------------------------------------
In response, DOE notes that as proposed in the March 2022 NOPR,
section 7.3 of appendix EE would require that the burner input rate be
corrected to reflect gas characteristics at a temperature of 60 [deg]F
and atmospheric pressure of 30 in of Hg when adjusting the burner input
rate. Therefore, an additional definition for a standard cubic foot of
gas for the purpose of referencing it in sections 7.1 and 7.3 (which is
consistent with the language in section 9.1.2.2.1 of both ANSI/ASHRAE
103-1993 and ANSI/ASHRAE 103-2017) would be unnecessary; however, it
may be useful for clarification.
As such, DOE is adding a definition for a ``standard cubic foot of
gas'' to section 2 of appendix EE to specify the temperature and
pressure for a standard cubic foot of gas.
C. Metric
As discussed, the energy conservation standards for consumer
boilers rely on the AFUE metric. 10 CFR 430.32(e)(2). For gas-fired and
oil-fired boilers, AFUE accounts for fossil fuel consumption in active,
standby, and off modes, but does not include electrical energy
consumption. For electric boilers, AFUE accounts for electrical energy
consumption in active mode. EPCA defines the term ``annual fuel
utilization efficiency,'' in part, as the efficiency descriptor for
furnaces and boilers. (42 U.S.C. 6291(20)) In addition, DOE has
established separate metrics and energy conservation standards for
power consumption during standby mode and off mode (PW,SB
and PW,OFF, respectively). 10 CFR 430.32(e)(2)(iii)(B).
AFUE is defined by ASHRAE 103 (both the 1993 and 2017 versions) as
the ratio of annual output energy to annual input energy, which
includes any non-heating-season pilot input loss but does not include
electric energy for gas- or oil-fired furnaces or boilers. For gas- and
oil-fired boilers, the AFUE test generally consists of steady-state,
cool down, and heat up tests, during which various measurements are
taken (e.g., flue gas temperature, concentration of CO2 in
the flue gas). (See sections 9.1, 9.5, and 9.6 of both ANSI/ASHRAE 103-
1993 and ANSI/ASHRAE 103-2017.) For condensing boilers, condensate
collection tests during steady-state and cyclic operation are also
specified. (See sections 9.2 and 9.8 of both ANSI/ASHRAE 103-1993 and
ANSI/ASHRAE 103-2017.) The test measurements are used in conjunction
with certain assumptions to calculate the AFUE. (See section 11 of both
ANSI/ASHRAE 103-1993 and ANSI/ASHRAE 103-2017.)
In the March 2022 NOPR, after tentatively concluding that hydronic
heat pumps meet the definitional criteria to be considered a consumer
boiler but that the existing test procedure does not apply to them, DOE
sought comment on whether any other industry test methods exist for
determining the heating efficiency of air-to-water or water-to-water
heat pumps. DOE sought comment specifically on AHRI 550/590, and
whether it would be appropriate for adoption as a Federal test
procedure for such products, and if so, whether modifications could be
made to result in an AFUE rating. 87 FR 14622, 14626.
NYSERDA urged DOE to adopt appropriate, industry-recognized test
procedures to support informed consumer choice between electric
resistance and heat pump products. (NYSERDA, No. 23 at p. 5-6)
BWC stated that it believes DOE has correctly identified the
appropriate test procedures for both consumer boilers and hydronic heat
pumps at this time, with those procedures being ASHRAE 103-2017 and
AHRI 550/590 respectively. (BWC, No. 19 at p 2-3)
[[Page 15518]]
Rheem identified AHRI 550/590 as an industry test method to determine
maximum and part-load COP values but noted this test method would have
to be modified to account for standby mode and off mode energy use as
well as to produce an AFUE metric. (Rheem, No. 18 at p. 2)
The Joint Advocates stated that while AHRI 550/590 is appropriate
for evaluating the performance of consumer air-to-water heat pumps, it
is only applicable for water-to-water heat pumps with a capacity
greater or equal to 135,000 Btu/h. The Joint Advocates stated that
ASHRAE/ANSI/AHRI/ISO Standard 13256-2 is more appropriate for consumer
water-to-water heat pumps and referred to international standards EN
14511 and EN 14825 as starting points. The Joint Advocates asserted
that a seasonal performance rating analogous to AFUE could be
established and encouraged DOE to establish these procedures in a
timely manner so that consumers have access to efficiency ratings based
on a standardized test procedure. Finally, the Joint Advocates stated
that based on 2015 Residential Energy Consumption Survey (``RECS'')
data, hydronic systems are the main heating means in 8 percent of U.S.
homes overall and the main heating means for 28 percent of households
in the Northeastern United States. (Joint Advocates, No. 21 at p. 1-2)
A.O. Smith stated that ISO Standard 13256-2 would be the most
appropriate test method for water source heat pump water heaters
intended to be used as consumer hot water boilers, and that AHRI
Standard 550/590 would be the most appropriate test method for air
source heat pump water heaters intended to be used as consumer hot
water boilers. Pertaining specifically to AHRI 550/590, A.O. Smith
stated that the test procedure to measure COP has fundamental
differences than the test procedure to measure AFUE, and that there is
no means of deriving an AFUE value from the COP measurement. In
addition, A.O. Smith claimed that if the limit for consumer heat pump
water ``boilers'' is defined by an input rate of less than 300,000 Btu/
h, then the output for these products will include products with
heating capacities up to 900,000 Btu/h, which would be outside the
scope of a consumer boiler. A.O. Smith recommended that DOE review the
referenced performance standards, as they define the heating capacity
based on the heat moved into the water being heated, whereas DOE's
definition is based on the energy being consumed by the boiler. (A.O.
Smith, No. 24 at p. 2)
As stated in section III.A.2 of this document, DOE has concluded
that hydronic heat pumps meet the definitional criteria to be covered
as a consumer boiler under EPCA's statutory definition at 42 U.S.C.
6291(23) and DOE's regulatory definition at 10 CFR 430.2. However, DOE
is not adopting a separate test procedure or metric for hydronic heat
pumps in this final rule because the Department requires more
information in order to determine a representative approach for testing
these products. DOE will continue to consider the appropriate metric to
assess the efficiency of such products, and any proposed test procedure
would be addressed in a separate test procedure rulemaking in the
future.
D. Updates to Industry Standards
The DOE test method for consumer boilers references several
industry standards, including ANSI/ASHRAE 103 for various testing
requirements pertaining to determination of AFUE, certain sections of
IEC 62301 (Second Edition) for determining the electrical standby mode
and off mode energy consumption, and ASTM D2156-09 (Reapproved 2013)
for adjusting oil burners. The following sections discuss DOE's
amendments pertaining to the incorporation by reference of these
industry standards.
1. ANSI/ASHRAE 103
As discussed, ANSI/ASHRAE 103-1993 is referenced throughout
appendix N for various testing requirements pertaining to determination
of the AFUE of consumer boilers. ANSI/ASHRAE 103-1993 provides
procedures for determining the AFUE of consumer boilers (and furnaces).
As mentioned previously, ANSI/ASHRAE 103-1993 has been updated multiple
times. In the rulemaking that culminated in the January 2016 Final
Rule, DOE initially proposed to incorporate by reference the most
recent version of ANSI/ASHRAE 103 available at the time (i.e., ANSI/
ASHRAE 103-2007), but ultimately declined to adopt the proposal in the
final rule based on concerns about the impact this change would have on
AFUE ratings of products distributed in commerce at that time. 81 FR
2628, 2632-2633 (Jan. 15, 2016). DOE stated that further evaluation was
needed to determine the potential impacts of ANSI/ASHRAE 103-2007 on
the measured AFUE of boilers. Id. DOE theorized that ANSI/ASHRAE 103-
2007 might better account for the operation of two-stage and modulating
products and stated that DOE may further investigate adopting it or a
successor test procedure in the future. Id.
After the January 2016 Final Rule, ANSI/ASHRAE 103 was again
updated in 2017 (i.e., ANSI/ASHRAE 103-2017). In the May 2020 RFI, DOE
identified several substantive differences between ANSI/ASHRAE 103-1993
and ANSI/ASHRAE 103-2017 that pertain to consumer boilers and requested
further comment on the differences between ANSI/ASHRAE 103-1993 and
ANSI/ASHRAE 103-2017. 85 FR 29352, 29355.
In the March 2022 NOPR, DOE discussed additional differences
between ANSI/ASHRAE 103-1993 and ANSI/ASHRAE 103-2017 raised by
commenters in response to the May 2020 RFI. 87 FR 14622, 14628-14631.
The differences between the two versions of the standard are discussed
in detail in sections III.D.1.a through III.D.1.f of this document.
After considering the differences between the standards and the
potential impact, DOE proposed to incorporate by reference the most
recent version (at the time) of ANSI/ASHRAE 103, i.e., ANSI/ASHRAE 103-
2017. 87 FR 14622, 14630. DOE tentatively concluded that the
improvements included in ANSI/ASHRAE 103-2017 provide a more
representative average use cycle for consumer boilers, in particular
for two-stage and modulating boilers, and that the change would not
materially alter the burden or cost of conducting an AFUE test. Id. DOE
also noted that test data indicate the update to the 2017 edition of
ASHRAE 103 could result in changes to the measured AFUE of two-stage
and modulating boilers ranging from -0.50 percent to 0.23 percent, with
no discernable trend in the direction or magnitude of change, and that
several commenters indicated incorporating ANSI/ASHRAE 103-2017 would
likely not impact rated values significantly. 87 FR 14622, 14631. DOE
sought further comment on its proposal to incorporate by reference
ANSI/ASHRAE 103-2017, the potential impact on ratings and whether
retesting would be required. Id.
Rheem agreed with DOE's tentative determination that the proposed
amendments would result in minimal differences in AFUE ratings but
requested that DOE test a representative sample of minimally compliant
consumer boilers to determine the effect. Rheem requested that DOE
provide this test data in the final rule and assess the impacts on the
ongoing energy conservation standards rulemaking. Rheem additionally
suggested that DOE could provide an enforcement policy to state that
models tested and certified prior to the effective date of the test
procedure final rule would be tested to the current appendix N test
procedure during an enforcement investigation. (Rheem, No. 18 at p. 3-
4)
[[Page 15519]]
As discussed, DOE's assessment of the changes in ANSI/ASHRAE 103-
2017, along with stakeholder comments provided throughout this
rulemaking, indicate that the only update in the industry test
procedure with the potential to impact ratings would be the change in
cycle times. This topic is discussed in detail in section III.D.2.c of
this document. The updated cycle times pertain to condensing boilers,
which employ heat exchanger technologies with efficiency performance
that surpasses the current minimum AFUE requirements for boilers at 10
CFR 430.32(e)(2)(iii). As discussed in section III.D.2.c of this
document, DOE conducted testing to determine that the impact on AFUE
ratings of this change would be minimal. Based on this information, DOE
has determined that the amendments to the consumer boilers test
procedure will not have a significant or substantive impact on ratings,
nor affect compliance of any products.
On January 10, 2022, ASHRAE and ANSI approved a 2022 edition of
ASHRAE 103 (i.e., ``ANSI/ASHRAE 103-2022''). DOE did not discuss ANSI/
ASHRAE 103-2022 in the March 2022 NOPR, and parties commenting in
response to the March 2022 NOPR did not indicate that DOE should
consider incorporating by reference ANSI/ASHRAE 103-2022. A March 4,
2022, online publication by ANSI states that ANSI/ASHRAE 103-2022
includes mostly editorial changes and quality improvements to test duct
and plenum figure, the system number table, and figures for the surface
heat transfer coefficient and coefficient of radiation.\16\ Given that
stakeholders provided general support for adopting ANSI/ASHRAE 103-
2017, and that the updates in ANSI/ASHRAE 103-2022 do not substantively
change the industry test procedure DOE is not considering ANSI/ASHRAE
103-2022 in this rulemaking.
---------------------------------------------------------------------------
\16\ Brad Kelechava, ``ANSI/ASHRAE 103-2022: AFUE Testing of
Residential Furnaces and Boilers,'' The ANSI Blog, March 4, 2022,
blog.ansi.org/ansi-ashrae-103-2022-fuel-efficiency-afue-testing/#gref. Last accessed October 5, 2022.
---------------------------------------------------------------------------
The following subsections discuss the updates in ANSI/ASHRAE 103-
2017 with respect to ANSI/ASHRAE 103-1993.
a. Post-Purge Time
Power vented units, power burner units, and forced-draft units use
a combustion blower to exhaust the flue gas during operation. ``Post
purge'' is defined in both ANSI/ASHRAE 103-1993 and ANSI/ASHRAE 103-
2017 as ``the design that permits the continued operation of the
combustion blower in a power vented unit, power burner unit, or forced-
draft unit for a period of time after the main burner is shut off for
the purpose of venting of residential flue gas in the heat exchanger
and the venting system.'' For the determination of off-cycle flue
losses, it is necessary to demarcate when the boiler has entered its
off-cycle after completion of the post-purge period, especially since
post-purge periods can last several minutes. Section 8.7 of appendix N
specifies the timing of flue temperature measurements during the off-
cycle portion of the test method based on the length of the post-purge
period. Section 8.7 of appendix N generally corresponds to section
9.5.2.1 of ANSI/ASHRAE 103-1993, except that section 8.7 of appendix N
specifies that when the post-purge time is less than or equal to 30
seconds, it can be set to 0 and the cool-down test be conducted as if
there is no post-purge; while section 9.5.2.1 of ANSI/ASHRAE 103-1993
specifies that if post-purge time is less than or equal to 5 seconds,
it shall be tested as if there is no post-purge. Additionally, the
length of the post-purge cycle is used as one criterion for determining
whether the heat-up and cool-down tests can optionally be omitted.
Section 8.10 of appendix N generally corresponds to section 9.10 of
ANSI/ASHRAE 103-1993, and both sections require a post-purge period of
less than 5 seconds to optionally omit the heat-up and cool-down tests.
Section 9.5.2.1 of ANSI/ASHRAE 103 was updated in the 2017 version
to match DOE's requirement that if the post-purge period is 30 seconds
or less, it shall be tested as if there is no post-purge. Additionally,
in the March 2022 NOPR, DOE identified the post-purge time threshold
being increased to 30 seconds in the criterion for determining whether
the ``Optional Test Procedures for Conducting Furnaces and Boilers that
have no OFF-Period Flue Loss'' is applicable as a change in ANSI/ASHRAE
103-2017. DOE proposed to adopt the 30-second threshold in the newly
proposed appendix EE, consistent with the change to ANSI/ASHRAE 103-
2017. 87 FR 14622, 14628.
BWC stated that it appreciated DOE's inclusion of the change in
post-purge time length to 30 seconds. (BWC, No. 19, p. 2-3)
Additionally, in the March 2022 NOPR, DOE proposed minor changes to
the test method for models with post-purge times longer than 3 minutes,
consistent with the updates included in ANSI/ASHRAE 103-2017. 87 FR
14622, 14631. Specifically, section 9.5.2.1 of ANSI/ASHRAE 103-2017
requires that for cases where the post-purge period is greater than 3
minutes, an additional measurement of the flue gas temperature during
the cool-down test is required at the midpoint of the post-purge
period. DOE proposed to adopt a harmonizing change in the newly
proposed appendix EE. 87 FR 14622, 14631 and 14654.
DOE did not receive any comments regarding this proposal. For the
reasons discussed in the March 2022 NOPR, DOE is finalizing this
amendment to section 8.5(d) of appendix EE.
b. Calculations for Omission of Heat-Up and Cool-Down Tests
The current test procedure for consumer boilers allows certain
units to omit the cool-down and heat-up tests. These include units that
have been determined to have no measurable airflow through the
combustion chamber and heat exchanger during the burner off-period and
that have minimal post-purge periods (see section III.D.1.a of this
document for discussion of post-purge time). For these boilers, the
off-cycle losses are expected to be minimal. However, off-cycle losses
(typically determined during the cool-down and heat-up tests) must be
accounted for when determining the heating seasonal efficiency,
EffyHS. Section 8.10 of appendix N currently states, ``In
lieu of conducting the cool-down and heat-up tests, the tester may use
the losses determined during the steady-state test described in section
9.1 of ASHRAE 103-1993 when calculating heating seasonal efficiency,
EffyHS.'' Accordingly, sections 10.2 and 10.3 of appendix N
provide the appropriate equations to use when calculating
EffyHS if the cool-down and heat-up tests are omitted per
section 8.10 of appendix N. These equations are provided in sections
10.2 and 10.3 of appendix N because they were not included in ANSI/
ASHRAE 103-1993.
As discussed in the March 2022 NOPR, ANSI/ASHRAE 103-2017 makes
several updates to include these equations, and the equations in ANSI/
ASHRAE 103-2017 are identical to those in appendix N. 87 FR 14622,
14629. Due to this harmonizing update, DOE proposed not to include
these equations in the new appendix EE and to instead directly
reference the relevant sections in ANSI/ASHRAE 103-2017 (11.3.11.3,
11.5.11.1, and 11.5.11.2). 87 FR 14622, 14631. DOE did not receive
comment on this topic and is finalizing this amendment as proposed in
the March 2022 NOPR.
[[Page 15520]]
c. Cycle Timings
ANSI/ASHRAE 103-2017 includes calculations, originally included in
ANSI/ASHRAE 103-2007, for determining the average on-time and off-time
per cycle for two-stage and modulating boilers, rather than assigning
fixed values as in ANSI/ASHRAE 103-1993. DOE received comments in
response to the May 2020 RFI generally indicating that these updated
cycle timings are more representative. DOE referenced test data from
the previous rulemaking to ascertain the potential impact of this
update and tentatively determined that the new method would be more
representative and not unduly burdensome and have minimal impact on
AFUE ratings. 87 FR 14622, 14628. Therefore, DOE proposed to adopt the
updated cycle times via adoption of the ASHRAE 103-2017 as the
reference standard in the newly proposed appendix EE. 87 FR 14622,
14630.
In addition, DOE discussed that data collected for the January 2016
Final Rule \17\ for three models of condensing, modulating boilers
showed that the changes in on-cycle and off-cycle times resulted in
changes in AFUE of 0.11, -0.50, and 0.22 percent, respectively. For two
models of non-condensing, modulating boilers, calculating the AFUE
based on the on-cycle and off-cycle times in ANSI/ASHRAE 103-2007
changed the AFUE by 0.11 and -0.14 percent, respectively. 87 FR 14622,
14630.
---------------------------------------------------------------------------
\17\ These data were presented at a public meeting for the March
11, 2015, NOPR pertaining to test procedures for furnaces and
boilers and can be found at www.regulations.gov/document/EERE-2012-BT-TP-0024-0021.
---------------------------------------------------------------------------
In response to the March 2022 NOPR, BWC stated that it agreed with
DOE's conclusion that the new average use cycle calculations from ANSI/
ASHRAE 103-2017 are more representative for modulating boilers and have
little impact on efficiency ratings. (BWC, No. 19 at p. 4) The CA IOUs
stated the ANSI/ASHRAE 103-2017 on/off time per cycle more accurately
represents the typical operation for two-stage, modulating, and
condensing boiler technologies. (CA IOUs, No. 20 at p. 1)
AHRI requested that DOE provide more data regarding the impacts of
cycle timing on condensing models. (AHRI, No. 26 at p. 3)
In response to this request, DOE has conducted testing on two
additional modulating condensing boilers to investigate the impact of
the revised cycle timings on AFUE. Data collected from this testing is
shown in Table III.1. For this investigation, DOE used the updated
steady-state efficiency calculation method discussed in section III.E
of this final rule for both the ANSI/ASHRAE 103-1993 and ANSI/ASHRAE
103-2017 results such that the only variable influencing differences in
AFUE ratings would be the cycle timings.
Table III.1--Impact of Cycle Timings on AFUE for Modulating Condensing Boilers
----------------------------------------------------------------------------------------------------------------
ANSI/ASHRAE 103-1993 ANSI/ASHRAE 103-2017
------------------------------------------------------------------- Change in AFUE
Model Cycle timings Cycle timings (percent)
(mm:ss) AFUE (percent) (mm:ss) AFUE (percent)
----------------------------------------------------------------------------------------------------------------
Unit No. 1................... 15:00 on/15:00 90.98 23:10 on/11:05 91.43 +0.45
off. off.
Unit No. 2................... 15:00 on/15:00 91.61 20:29 on/11:50 91.46 -0.15
off. off.
----------------------------------------------------------------------------------------------------------------
As indicated in Table III.1, the change in cycle timings resulted
in insignificant changes to the AFUE values (+0.45 percent and -0.15
percent). These additional sample points are consistent with DOE's
tentative determination that impacts to AFUE would be minimal as a
result of the updated cycle timings in ANSI/ASHRAE 103-2017. Therefore,
manufacturers would not be required to retest and rerate consumer
boilers due to this change. Based on the discussion provided in the
March 2022 NOPR, consideration of comments from interested parties, and
this additional test data, DOE has determined that the updated approach
in ANSI/ASHRAE 103-2017 increases the representativeness of the test
procedure without being unduly burdensome.
During its testing of these two boilers, DOE recognized that the
determination of cycle timings in Table 7 of ANSI/ASHRAE 103-2017 does
not specify the precision to which these timings (tON and
tOFF) should be calculated (i.e., to the nearest minute or
second). ANSI/ASHRAE 103-2017 provides no indication of whether these
cycle timings can or should be rounded. Acknowledging that many testing
facilities may only be able to time the burner cycling operation of the
boiler under test to the nearest second, DOE is providing additional
specification in appendix EE to require that calculated cycle timings
shall be rounded to the nearest second. This clarification is not
expected to impact results significantly but serves to improve
repeatability and reproducibility of test results by clarifying the
duration of the cycle time.
d. Oversize Factor
The oversize factor for a boiler indicates the ratio between the
boiler's nominal capacity and the home's heating load. This factor is
represented by the symbol ``[alpha]'' and is determined in sections
11.2.8.3 and 11.4.8.3 of ANSI/ASHRAE 103-1993 and sections 11.2.8.2 and
11.4.8.2 of ANSI/ASHRAE 103-2017.
ANSI/ASHRAE 103-2017 updates the method for calculating the
oversize factor. While the oversize factor was calculated from a lookup
table based on design heating requirement (``DHR'') in ANSI/ASHRAE 103-
1993, ANSI/ASHRAE 103-2017 assigns a constant value of 0.70 to [alpha]
to represent the national average oversize factor. Based on DOE's
assessment of its test data, DOE stated in the March 2022 NOPR that
this change would be unlikely to have a substantive impact on AFUE
ratings because the calculations are not particularly sensitive to
changes in the oversize factor value. Specifically, DOE reviewed test
data for three modulating, condensing boilers and found that the change
in oversize factor from a calculated value, as specified in ANSI/ASHRAE
103-1993, to 0.7 changed the AFUE rating by 0.01 AFUE percentage points
or less for all 3 models. 87 FR 14622, 14629. In the March 2022 NOPR,
DOE proposed to adopt the constant 0.7 oversize factor through
incorporation by reference of ANSI/ASHRAE 103-2017. Id.
BWC supported DOE's proposal to adopt the constant 0.7 oversize
factor through incorporation of ANSI/ASHRAE 103-2017. BWC's analysis of
this proposal demonstrated that adopting this approach would not have a
significant impact on overall product efficiency. (BWC, No. 19 at p. 3)
Busse stated that the oversize factor should be a constant value
less than 0.4
[[Page 15521]]
based on an Air Conditioning Contractors of America (``ACCA'')
equipment selection checklist \18\ indicating to installers that the
selected equipment should be less than or equal to 140 percent of the
designed total heating load. Busse commented that in the last 40 years,
it has become apparent that oversized equipment is less efficient, such
that a more appropriate oversize factor of approximately 0.35 is
justified. (Busse, No. 22 at p. 6-7)
---------------------------------------------------------------------------
\18\ ACCA ``Verifying ACCA Manual S[supreg] Procedures''
brochure, www.acca.org/HigherLogic/System/DownloadDocumentFile.ashx?DocumentFileKey=2f0a6828-2205-e112-745f-7215c9a85541&forceDialog=0. Last accessed October 7, 2022.
---------------------------------------------------------------------------
In response, DOE notes that commenters did not provide field
statistics that would help to determine what a national average
representative oversize factor would be, nor is DOE aware of any such
data. While contractors may be oversizing boilers to a lesser degree
today than in the past, DOE expects that many replacements will be made
on a like-for-like basis such that the input capacity of the
replacement boiler will match that of the previous boiler (and thus
maintain the same oversize factor as the previous boiler). Without
sufficient nationally representative data to support deviation from the
industry-accepted oversize factor specified in ANSI/ASHRAE 103-2017,
DOE is adopting the provision to use a constant oversize factor of 0.70
through incorporation by reference of ANSI/ASHRAE 103-2017. In
addition, as discussed previously in this document and initially
discussed in the March 2022 NOPR, based on a review of its test data
DOE has determined that this change would not substantively impact on
AFUE.
e. Annual Performance Metrics
ANSI/ASHRAE 103-2017 changes the method for determining national
average burner operating hours (``BOH''), average annual fuel energy
consumption (``EF''), and average annual auxiliary
electrical energy consumption (``EAE''),\19\ especially for
two-stage and modulating products, based on a 2002 study from NIST.
---------------------------------------------------------------------------
\19\ A typographical correction to the determination of
EAE at 10 CFR 430.23(n) is discussed in section III.F.5
of this final rule.
---------------------------------------------------------------------------
The CA IOUs stated that ASHRAE 103-2017 utilizes differentiating
calculations for annual operating hours and reduced fuel input rates
that reflect real-world operation conditions of boilers that more
accurately represents the typical operation for two-stage, modulating,
and condensing boilers that spend a significant amount of time
operating at part-load conditions. (CA IOUs, No. 20 at p. 1)
These additional annual performance metrics are not required for
representations or certifications to DOE at this time. Federal Trade
Commission product labeling requirements at 16 CFR 305.8 specify that
determinations of estimated annual energy consumption, estimated annual
operating cost, and energy efficiency rating must be determined in
accordance with the testing and sampling provisions required by DOE as
set forth in subpart B of 10 CFR part 430. For boilers, the product
labeling provisions are specified at 16 CFR 305.20(f) and currently
only require AFUE to be presented. Thus, manufacturers are not required
to report BOH, EF, or EAE for consumer boilers as
of this final rule. However, manufacturers may voluntarily represent
these values. To ensure that any voluntary representations of these
values are conducted in accordance with the DOE test procedure, DOE is
adopting the revised calculation methods in ANSI/ASHRAE 103-2017 for
BOH, EF, and EAE.
f. Measurement of Relative Humidity
The current DOE test procedure at appendix N, through incorporation
by reference of ANSI/ASHRAE 103-1993, specifies limitations on the
relative humidity of the ambient air of the test chamber when testing a
condensing boiler. Sections 9.2 and 9.8.1 of ANSI/ASHRAE 103-1993
state, ``The humidity of the room air shall at no time exceed 80
percent'' but do not provide instruction on the instrumentation
necessary to measure the relative humidity. ANSI/ASHRAE 103-2017
provides new requirements in section 8.5.1 to follow ANSI/ASHRAE 41.6-
2014 in order to measure relative humidity for testing condensing
boilers. Because the DOE test method and ANSI/ASHRAE 103-1993 currently
limit relative humidity allowed during testing, DOE reasoned in the
March 2022 NOPR that relative humidity already must be measured under
the current procedure; thus, DOE tentatively concluded that the method
prescribed by ANSI/ASHRAE 103-2017 would likely be similar to current
practices and requested comment on this topic. 87 FR 14622, 14636-
14637.
Busse suggested that DOE should verify that ANSI/ASHRAE 41.6-2014
includes precision and calibration requirements. (Busse, No. 22 at p.
9-10) DOE has reviewed ANSI/ASHRAE 41.6-2014 in detail and notes that
it provides setup and calibration methods for both psychrometers and
hygrometers (two types of instruments which can be used to measure
relative humidity). Section 6 of ANSI/ASHRAE 41.6-2014 provides
calibration requirements, and sections 7 and 8 of ANSI/ASHRAE 41.6-2014
provide measurement methods, precision requirements, and measurement
uncertainty analysis.
As discussed further in section III.K of this document, DOE
received comments indicating that introducing these new requirements
for measurement and instrumentation would not be unduly burdensome to
industry. In this final rule, DOE is incorporating by reference ANSI/
ASHRAE 41.6-2014 in appendix EE for the purpose of performing the
required humidity measurement.
2. IEC 62301 and ASTM D2156-09
DOE noted in the May 2020 RFI that the version of IEC 62301
currently incorporated by reference in appendix N is still the most
recent version, and the most recent iteration of ASTM D2156-09 is a
version reapproved in 2018 that did not contain any changes from the
2009 version. 85 FR 29352, 29355. DOE did not receive any comments
pertaining to its incorporation by reference of IEC 62301 or ASTM
D2156-09 and in the March 2022 NOPR proposed to maintain the current
reference to IEC 62301, and to update the reference to ASTM D2156-09 to
reflect the version that was reapproved in 2018. 87 FR 14622, 14628.
DOE did not receive any comments related to its incorporation by
reference of these standards. In this final rule, DOE is finalizing
their adoption for appendix EE as proposed.
E. Steady-State Efficiency for Condensing Modulating Boilers
In the May 2020 RFI and the March 2022 NOPR, DOE discussed that
ANSI/ASHRAE 103-1993 and ANSI/ASHRAE 103-2017 yield a circular
reference when calculating the steady-state efficiency for condensing
modulating boilers. 85 FR 29352, 29357; 87 FR 14622, 14629.
As discussed in the March 2022 NOPR, the circular reference arises
within the calculation of steady-state efficiencies at maximum and
minimum input rate, which depends in part on the steady-state heat loss
due to condensate going down the drain at the maximum and reduced input
rates. (See section 11.5.7.3 of ANSI/ASHRAE 103-2017, which refers to
section 11.3.7.3.) The steady-state heat loss due to condensate going
down the drain at the maximum and minimum input rates is calculated in
part based on the national average outdoor air temperature at the
maximum and minimum input rates.
[[Page 15522]]
(See section 11.5.7.2 of ANSI/ASHRAE 103-2017, which refers to section
11.3.7.2.) The national average outdoor air temperatures at the maximum
and minimum input rates are both a function of the balance point
temperature. (See section 11.5.8.3 of ANSI/ASHRAE 103-2017, which
refers to section 11.4.8.3.) The balance point temperature is
calculated based on the oversize factor at maximum input rate (which
is, as discussed previously, a constant value in ANSI/ASHRAE 103-2017)
and the ratio of the heating capacity at the minimum input rate to the
heating capacity at the maximum input rate. (See section 11.5.8.4 of
ANSI/ASHRAE 103-2017, which references section 11.4.8.4.) The heating
capacities at the minimum and maximum input rates are calculated based
in part on the steady-state efficiencies at minimum and maximum input
rates, respectively. (See section 11.5.8.1 of ANSI/ASHRAE 103-2017,
which references section 11.4.8.1.) If the calculations were
interpreted to refer back to the steady-state efficiencies at minimum
and maximum input rates for a modulating, condensing model, as
determined by section 11.5.7.2 of ANSI/ASHRAE 103-2017, a circular
reference would result.
However, since there is no specific instruction to use the values
as calculated by section 11.5.7.2, DOE stated in the March 2022 NOPR
that it interprets ANSI/ASHRAE 103-2017 to instruct that the steady-
state efficiency at maximum and reduced input rates be determined as
specified in section 11.4.8.1, which refers to section 11.4.7, which in
turn refers to section 11.2.7 for the calculation of steady-state
efficiency for non-condensing, non-modulating boilers. 87 FR 14622,
14629. The steady-state efficiencies at maximum and minimum input
calculated using section 11.2.7 can then be used to obtain values for
output capacities at the maximum and reduced input, which are needed to
calculate the balance point temperature, the average outdoor air
temperature at maximum and minimum input, and finally the heat loss due
to condensate going down the drain at maximum and minimum input rates.
Id.
In the March 2022 NOPR, DOE proposed to add provisions to clarify
the approach for calculating steady-state efficiencies at maximum and
minimum input rates for condensing, modulating boilers using ANSI/
ASHRAE 103-2017. 87 FR 14622, 14629. Specifically, DOE proposed to
codify provisions in section 10.1.2 of appendix EE to explain how to
calculate these values without a circular reference, ultimately by
referring back to section 11.2.7 of ANSI/ASHRAE 103-2017. 87 FR 14622,
14655.
Crown, U.S. Boiler, BWC, Rheem, A.O. Smith, AHRI, and AGA & APGA
all supported DOE's proposal to provide additional specification that
would avoid a circular reference in the test procedure. (A.O. Smith,
No. 24 at p. 3; AGA & APGA, No. 25 at p. 2) Rheem recommended that each
subsection in section 10.1.2 of appendix EE should not say ``previous
step'' but should refer to the appropriate subsection. Specifically,
Rheem recommended that DOE present an equation for balance point
temperature, TC, in which the variables used in the equation
reference the relevant sections in ANSI/ASHRAE 103-2017. (Rheem, No. 18
at p. 3) Crown, U.S. Boiler, BWC, and AHRI all recommended the same
revision for section 10.1.2 to improve the clarity of the section.
(Crown, No. 16 at p. 3; U.S. Boiler, No. 17 at p. 2-3; BWC, No. 19 at
p. 3; AHRI, No. 26 at p. 2-3) Specifically, the commenters recommended
revising section 10.1.2 to replace the output capacity parameters
QOUT,R and QOUT as follows:
10.1.2 Calculate the balance point temperature (TC) for
condensing, modulating boilers by using the following equation in place
of that referenced by 11.5.8.4 [of ANSI/ASHRAE 103-2017]:
[GRAPHIC] [TIFF OMITTED] TR13MR23.000
Where:
TSH = typical average outdoor temperature at which a
boiler starts operating, 65 [deg]F
TOA,T = the typical outdoor design temperature, 5 [deg]F
[alpha] = oversize factor, as defined in 11.4.8.2 [of ANSI/ASHRAE
103-2017]
QIN = steady-state nameplate maximum fuel input rate
QIN,R = steady-state reduced input fuel input rate
LS,SSR = average sensible heat loss at steady state,
reduced input operation
LS,SS = average sensible heat loss at steady state,
maximum input operation
In reviewing this equation, DOE agrees that the recommended
equation adequately resolves the circular reference issue in the same
manner as DOE proposed in the March 2022 NOPR, but with a simplified
approach to specifying the correct calculations for determining the
steady-state efficiency for condensing modulating boilers. Rather than
determining QOUT and QOUT,R based on the steady-
state efficiencies EffySS and EffySS,R (using
section 11.2.7 of ANSI/ASHRAE 103-2017) to calculate TC, the
suggested equation simply inserts the appropriate variables directly
into the equation for TC, providing the same result. DOE is
therefore adopting this revised equation in section 10.1.3 of appendix
EE.
F. Corrections and Clarifications
1. Off-Cycle Losses
In response to the March 2022 NOPR, several commenters indicated
that ANSI/ASHRAE 103-2017 has a typographical error in the equations
used to determine LI,OFF1 and LS,OFF1 (off-cycle
infiltration and sensible losses, respectively). Specifically, Crown
and U.S. Boiler stated there is an error in section 11.2.10.8 of ANSI/
ASHRAE 103-2017 for the calculation of LI,OFF1. Crown and
U.S. Boiler stated that the equation for LI,OFF1 in ANSI/
ASHRAE 103-1993 was erroneous because QIN was multiplied by
60 when it should have been divided by 60. According to Crown and U.S.
Boiler, ASHRAE attempted to correct this error in ANSI/ASHRAE 103-2007,
but inadvertently copied the equation for LS,OFF1 to
LI,OFF1 for units having post-purge times below 3 minutes,
and this error was not corrected in the 2017 edition. (Crown, No. 16 at
p. 3; U.S. Boiler, No. 17 at p. 3) Similarly, Rheem identified this
issue involving the factor of 60 in the equations for
LS,OFF1 and LI,OFF1 and asked DOE to evaluate the
impact on ratings. (Rheem, No. 18, p. 6)
DOE has examined the equations for LS,OFF1 and
LI,OFF1 in ANSI/ASHRAE 103-2017 and understands that the
factor of 60 is used to convert the cycle times (reported in minutes)
into hours because the input rate is expressed in terms of Btu/h. Thus,
the cycle times must be divided by 60 to convert these values into
hours. Section 11.2.10.6 of ANSI/ASHRAE 103-2017 performs this
operation correctly for determining LS,OFF1, but the factor
of 60 is used incorrectly in sections 11.2.10.6 and 11.2.10.8 of ANSI/
ASHRAE 103-1993.
As Crown and U.S. Boiler indicated, industry has been aware of this
error
[[Page 15523]]
since the development of ANSI/ASHRAE 103-2007. As such, DOE expects
that current ratings are determined based on the corrected use of the
factor of 60. In particular, DOE is aware that the Gas Appliance
Manufacturers Association (GAMA) \20\ developed a computer program to
calculate AFUE.\21\ DOE has reviewed a version of this program (dated
October 15, 2003) and determined this calculation was corrected in the
underlying code. Based on this finding, correcting the use of the
factor of 60 (by incorporating by reference ANSI/ASHRAE 103-2017)
should not affect the ratings of products which have already been
tested and certified. Furthermore, these calculations apply only to
consumer boilers that have system numbers 2, 3, or 4 with post-purge
times greater than 30 seconds, which DOE understands to be a relatively
low fraction of the market based on its own compliance testing.
---------------------------------------------------------------------------
\20\ GAMA and the Air-Conditioning and Refrigeration Institute
(ARI) merged in 2008 to form AHRI.
\21\ In the May 2020 RFI, DOE discussed the industry-developed
computer program that calculates AFUE based on ANSI/ASHRAE 103-1993
``AFUE v1.2.'' This software was most recently updated in April
2004. 85 FR 29352, 29356.
---------------------------------------------------------------------------
DOE notes that section 11.2.10.8 of ANSI/ASHRAE 103-1993 provided
the correct equation for LI,OFF1 for models with post-purge
periods that are less than or equal to 3 minutes (albeit with the
aforementioned error with the factor of 60).
The equation for L I,OFF1 for models with post-purge
periods that are greater than to 3 minutes is corrected in ANSI/ASHRAE
103-2017 and is adopted in this final rule through incorporation by
reference.
2. Conversion Factor for British Thermal Units
In the March 2022 NOPR, DOE noted inconsistencies in the conversion
factors from watts (W) or kilowatts (kW) to British thermal units per
hour (Btu/h), in which some sections used a conversion factor of 3.412
and other sections use 3.413. 87 FR 14622, 14634. DOE stated that the
conversion factor between watts and Btu/h is generally accepted to be 1
watt = 3.412142 Btu/h (or 1 Btu/h = 0.2930711 watts), as published in
the 2021 ASHRAE Handbook--Fundamentals.\22\ Id. This value is more
appropriately rounded to 3.412 W/(Btu/h); therefore, DOE proposed
correcting the test procedures to use 3.412 W/(Btu/h) in all
calculations where 3.413 W/(Btu/h) was previously used. Id. DOE stated
in the March 2022 NOPR that it did not expect this correction to affect
AFUE ratings. Id.
---------------------------------------------------------------------------
\22\ 2021 ASHRAE Handbook--Fundamentals (I-P Edition). Peachtree
Corners, GA: American Society of Heating, Refrigeration and Air-
Conditioning Engineers, 2021. Available at www.ashrae.org/technical-resources/ashrae-handbook/description-2021-ashrae-handbook-fundamentals.
---------------------------------------------------------------------------
DOE did not receive comments on this topic. For the reasons
discussed here and in the March 2022 NOPR, this final rule implements a
conversion factor of 3.412 in each instance within new appendix EE. DOE
also amends appendix N--which will remain applicable to consumer
furnaces other than boilers--to use the corrected conversion factor.
3. Oil Pressure Instrumentation Error
Section 6.3 of ANSI/ASHRAE 103-2017 states, ``Instruments for
measuring gas, oil, air, water, and steam pressure shall be calibrated
so that the error is no greater than the following.'' However, the
specifications that follow omit the instrumentation requirements
applicable to measuring oil pressure. Section 6.3(b) of ANSI/ASHRAE
103-1993 included the oil pressure specification.
In response to the March 2022 NOPR, Rheem commented that DOE should
add the oil pressure instrumentation specification from ANSI/ASHRAE
103-1993 to section 5 of the new appendix EE test procedure. (Rheem,
No. 18 at p. 6)
This final rule reinstates the omitted provisions from section 6.3
of ANSI/ASHRAE 103-1993 in section 5 of appendix EE.
4. Gas Inlet Conditions
Section 7.1 of appendix N references Table 1 of ANSI/ASHRAE 103-
1993 for maintaining the gas supply, ahead of all controls for a
furnace,\23\ at an acceptable test pressure. The natural gas inlet
pressure shall be between the ``normal'' and ``increased'' values shown
in Table 1 of ANSI/ASHRAE 103-1993. Table 1 in ANSI/ASHRAE 103-2017
provides identical gas inlet pressures to those in ANSI/ASHRAE 103-1993
(this table is presented in section 8.2.1.3 of ASHRAE 103-2017, which
is excluded from reference in the current appendix N test procedure).
Table 1 also specifies the specific gravity of the test gases. The
pressures and specific gravity of the test gases are reproduced in
Table III.2 of this document.
---------------------------------------------------------------------------
\23\ This term refers to the broader definition of ``furnace,''
which includes warm air furnaces and boilers.
Table III.2--Natural Gas Inlet Pressures and Specific Gravity of Test Gases in Table 1 of ANSI/ASHRAE 103-1993
and ANSI/ASHRAE 103-2017
----------------------------------------------------------------------------------------------------------------
Test pressure (inches water
column) Specific
Type -------------------------------- gravity (air =
Normal Increased 1.0)
----------------------------------------------------------------------------------------------------------------
Natural......................................................... 7.0 10.50 .65
Manufactured.................................................... 3.5 5.25 .38
Butane.......................................................... 11.0 13.00 2.00
Propane......................................................... 11.0 13.00 1.53
----------------------------------------------------------------------------------------------------------------
In response to the March 2022 NOPR, Crown and U.S. Boiler stated
that the gas inlet pressure requirements in section 8.2.1.3 of ANSI/
ASHRAE 103-2017 are appropriate and necessary for units with pilot
lights because most pilots have no pressure regulation within the
appliance itself, and thus the input rate of the pilot is determined in
large part by the inlet pressure. Crown and U.S. Boiler noted, however,
that since continuous standing pilots are prohibited by EPCA on
consumer boilers, such restrictive requirements on the gas inlet
pressure are no longer necessary in the Federal test procedure and may
place undue burden on test labs. Crown and U.S. Boiler commented that
maintaining a 7.0 inches water column (``in. w.c.'') minimum inlet
pressure is not always possible in some test labs, nor is it necessary
as long as the regulator outlet pressure can be maintained, and the
nameplate input
[[Page 15524]]
achieved. Crown and U.S. Boiler further indicated that expensive gas
booster equipment may be necessary to meet the 7.0 in. w.c. minimum.
Crown and U.S. Boiler stated that gas appliances are generally listed
for use up to 14.0 in. w.c. inlet pressure, so there is also no reason
to reduce this pressure to 10.5 in. w.c. on a boiler without a
continuous pilot in order to provide results that are repeatable and
representative of what can be expected in the field. In order to afford
labs greater flexibility while still preventing boilers from being
tested at gas inlet pressures for which they are not intended to be
used in the field, Crown and U.S. Boiler suggested replacing the second
sentence of section 8.2.1.3 of ANSI/ASHRAE 103-2017 with: ``The gas
supply, ahead of all controls for a furnace, shall be maintained at a
test pressure within the upper and lower limits shown in the
manufacturer's instructions or on the boiler itself. In the absence of
any such limits, the gas supply pressure shall be maintained between
the normal and increased values shown in Table 1 of ANSI/ASHRAE 103-
2017.'' (Crown, No. 16 at p. 2-3; U.S. Boiler, No. 17 at p. 2)
Busse urged DOE to modify the language in section 7.1 of appendix
EE to include the term ``approximately'' when referring to meeting the
specific gravity requirements in Table 1 of ANSI/ASHRAE 103-2017,
asserting that the omission of this term suggests that DOE expects the
specific gravity to be exactly as shown in Table 1 without providing
instrument requirements for measuring. (Busse, No. 22 at p. 10)
At 42 U.S.C. 6295(f)(3)(A), EPCA mandates that gas-fired boilers
manufactured on or after September 1, 2012, must not have a constant
burning pilot. DOE agrees that the test procedure requirements in
appendix N (which reference Table 1 of ANSI/ASHRAE 103-1993) have a
greater contribution to maintaining the reproducibility and
repeatability of test results for consumer boilers with constant
burning pilots; however, it is currently unclear to DOE what the
impacts of updating the natural gas inlet pressure requirements as
suggested would be on measured efficiency ratings for boilers without
constant burning pilots. Crown and U.S. Boiler did not provide data to
indicate that their suggested approach of relying on the manufacturer's
instructions for setting natural gas inlet pressure will not
significantly impact ratings. Manufacturers have not previously
expressed concern regarding the ability to meet the inlet pressure
requirements in appendix N, and no waivers have been received for
consumer boilers that are not compatible with the inlet pressure
provisions. This suggests that manufacturers and test laboratories have
been able to meet these setup requirements since compliance with the
currently applicable appendix N test procedure has been required (July
13, 2016).
For these reasons, DOE has determined that no correction to the
natural gas inlet pressure requirements is necessary at this time and
is adopting the reference to Table 1 of ANSI/ASHRAE 103-2017 in section
7.1 of appendix EE as proposed in the March 2022 NOPR. Regarding
Busse's suggestion to include the word ``approximately'' in reference
to the specific gravity values referenced in section 7.1, DOE agrees
that the specific gravity may not be exactly as provided in Table 1 of
ANSI/ASHRAE 103-2017 because variations exist due to differences in gas
composition in supply sources. DOE understands that the purpose of
specifying the gas characteristics in Table 1 of ANSI/ASHRAE 103-2017
is to ensure that the energy content in the gas is consistent for the
repeatability and reproducibility of the test. DOE notes that explicit
tolerances are provided for the higher heating value of the gas used,
such that providing explicit tolerances for the specific gravity of the
gas would be redundant. As such, DOE is adopting Busse's suggestion to
state that the specific gravity of the gas should be ``approximately''
that shown in Table 1 of ANSI/ASHRAE 103-2017.
5. Active Mode Electrical Energy Consumption
As previously discussed, AFUE does not include active mode
electrical consumption for gas-fired and oil-fired boilers. Instead,
the DOE test procedure includes provisions for determining the average
annual auxiliary electrical energy consumption for gas-fired and oil-
fired boilers (EAE), as a separate metric from AFUE, that
accounts for active mode, standby mode, and off mode electrical
consumption. (See appendix N, section 10.4.3.) EAE is
referenced by the calculations at 10 CFR 430.23(n)(1) for determining
the estimated annual operating cost for furnaces. However, the
provisions at 10 CFR 430.23(n) include several incorrect references to
sections in appendix N. In the March 2022 NOPR, DOE proposed to correct
10 CFR 430.23(n)(1) to reference the appropriate sections of appendix N
where the currently codified provisions point to the wrong sections.
Additionally, DOE proposed to revise 10 CFR 430.23(n)(1) such that
sections in appendix N are referenced for furnaces and sections in
appendix EE are referenced for boilers. 87 FR 14622, 14633, and 14643.
DOE did not receive any comments on this topic. In this final rule,
DOE adopts these corrections as proposed.
6. Circulator Pumps
Section 8.2 of the proposed appendix EE from the March 2022 NOPR
included instructions on the electrical energy consumption measurements
for various boiler components in order to calculate PE, the electrical
power involved in burner operation. 87 FR 14622, 14654. It stated that
the measurement of PE must include the boiler pump if so equipped. Id.
In response to the March 2022 NOPR, Rheem noted that section 2 of
the proposed appendix EE defines a ``boiler pump'' \24\ as being
separate from the circulating water pump; however, the term
``circulating water pump'' is not defined in the proposed appendix EE
or ANSI/ASHRAE 103-2017. Rheem recommended that DOE add a definition
for ``circulating water pump'' to clarify the difference between these
pumps and to reduce confusion when performing the procedure in section
8.2 of appendix EE, which refers to both pump types. (Rheem, No. 18 at
p. 5-6)
---------------------------------------------------------------------------
\24\ Section 2.2 of appendix N defines a ``boiler pump'' as a
pump installed on a boiler that is separate from the circulating
water pump.
---------------------------------------------------------------------------
DOE notes that the definition for ``boiler pump'' was established
in the January 2016 Test Procedure Final Rule. 81 FR 2628, 2647. In the
January 2016 Test Procedure Final Rule, in describing devices that use
power during the active mode, DOE discussed a secondary pump for
boilers (i.e., boiler pump) used to maintain a minimum flow rate
through the boiler heat exchanger, which is most typically associated
with condensing boiler designs. Id. at 81 FR 2633. In the preamble to
the January 2016 Test Procedure Final Rule, DOE stated that it would
define a boiler pump as, ``a pump installed on a boiler that maintains
adequate water flow through the boiler heat exchanger and that is
separate from the circulating water pump;'' however, this definition
was not codified with the additional clarification that the boiler pump
maintains adequate water flow through the heat exchanger. Id. at 81 FR
2634. In order to improve the clarity of the boiler pump definition,
DOE is revising this definition to reflect the language which was
inadvertently omitted from the January 2016 Test Procedure Final Rule.
Additionally, section 9.1.2.2 of ANSI/ASHRAE 103-2017 states that,
for hot water boilers, the circulating water
[[Page 15525]]
pump nameplate power is to be used to determine the electrical power to
the circulating water pump (BE), and if the pump nameplate power is not
available, use the pump power listed in the water pump manufacturer's
literature or use 0.13 kW. In response to the March 2022 NOPR, Busse
suggested that, because circulator pumps do not have a ``nameplate''
power value, the water pump manufacturer's literature could be used
instead for calculating the value of BE. Busse also commented that the
default value of 0.13 kW in ANSI/ASHRAE 103-2017 may not be appropriate
for modern electronically commutated motor-based circulator pumps.
(Busse, No. 22 at p. 11)
At this time, DOE does not have sufficient data on circulating
water pumps used with consumer hot water boilers to specify a more
representative power draw to be used in lieu of manufacturer-reported
information (either on a nameplate or in the I&O manual). As ANSI/
ASHRAE 103-2017 is currently the industry-accepted test standard \25\
for consumer boilers, DOE expects that the provisions for circulator
pump power remain representative for current installations.
Additionally, DOE notes that the value of BE is not a factor that
determines AFUE (see section III.C for discussion about the AFUE
metric).
---------------------------------------------------------------------------
\25\ ANSI/ASHRAE 103-2022 does not provide substantive updates
to provisions for circulator pump power.
---------------------------------------------------------------------------
7. Units With Draft Hoods or Draft Diverters
Section 6.4 of appendix N provides installation instructions for
units with draft hoods or draft diverters. Among other requirements,
this section specifies installing the stack damper in accordance with
the ``I&O manual.''
In response to the March 2022 NOPR, Rheem commented that section
6.4 of appendix N appeared to have been omitted from the proposed
appendix EE. Rheem noted that these provisions are still relevant to
boilers and should be carried over into the new appendix EE test
procedure. (Rheem, No. 18 at p. 6)
The March 2022 NOPR proposed in section 6 (``Apparatus'') of
appendix EE to reference section 7 of ANSI/ASHRAE 103-2017
(``Apparatus'') including sections 7.2.3.1 and 7.3.3.1. Section 7.3.3.1
of ANSI/ASHRAE 103-2017 specifies stack and flue installation
requirements for boilers with draft hoods or draft diverters by
referencing section 7.2.3.1 of ANSI/ASHRAE 103-2017. The language in
section 7.2.3.1 of ANSI/ASHRAE 103-2017 is identical to the provisions
in section 6.4 of the current appendix N, except that section 7.2.3.1
specifies that the stack damper be installed in accordance with the
``manufacturer's instructions'' rather than the ``I&O manual''
specified in section 6.4. DOE's proposal to reference sections 7.2.3.1
and 7.3.3.1 of ANSI/ASHRAE 103-2017 through reference to section 7 in
the new appendix EE test procedure maintained the installation
instructions for units with draft hoods or draft diverters in appendix
EE. This final rule maintains the reference to section 7 of ANSI/ASHRAE
103-2017 in section 6 of appendix EE.
DOE has determined, however, that maintaining the more specific
reference to the manufacturer's I&O manual, rather than a general
reference to manufacturer's instructions, will ensure the
reproducibility of the test procedure by providing a more specific
reference to the document that must be consulted with regard to
installing the stack damper. Therefore, this final rule adds an
exception in section 6 of appendix EE to specify referencing the I&O
manual in lieu of manufacturer's instructions in section 7.2.3.1 of
ANSI/ASHRAE 103-2017.
8. Rounding of AFUE
In response to the March 2022 NOPR, Busse observed an inconsistency
between requirements to round the AFUE at 10 CFR 430.23(n)(2)(iii) and
requirements to truncate the AFUE at 10 CFR 429.18(a)(2)(vii). (Busse,
No. 22 at p. 11)
On July 22, 2022, DOE published a final rule regarding
certification requirements for several covered products and equipment,
including consumer boilers (``July 2022 Certification Final Rule''). 87
FR 43952. In an amendment established by that final rule, effective
August 22, 2022, DOE modified 10 CFR 429.18(a)(2)(vii) to state that
AFUE must be rounded to the nearest one-tenth of a percentage point.
Id. at 87 FR 43968. As this amendment provides consistency between the
certification requirement and the test procedure, no further correction
is required in this rulemaking.
G. Other Test Procedure Topics
In the course of this rulemaking, DOE solicited feedback on
additional aspects of the current test procedure for consumer boilers
to assess whether they remain representative of the energy consumption
during an average use cycle. DOE did not propose to amend the test
procedure for consumer boilers with regard to these topics in the March
2022 NOPR, and after consideration of comments received in response to
that NOPR, DOE determined not to amend the test procedure accordingly.
Comments received with regard to these topics are discussed in the
following subsections.
1. Outdoor Design Temperature
ANSI/ASHRAE 103-2017 assigns a value of 5 [deg]F for the typical
outdoor design temperature and 42 [deg]F for the average outdoor air
temperature, represented by TOA,T and TOA,
respectively. The outdoor design temperature is the lowest expected
temperature at which the boiler can satisfy the home's heating demand,
while the average outdoor air temperature is the average temperature
during the heating season.
In response to the March 2022 NOPR, Busse stated that the 5 [deg]F
outdoor design temperature used in ANSI/ASHRAE 103-1993 \26\ may be out
of date due to climate change and suggested that different outdoor
design temperatures could be assigned for furnaces and boilers. (Busse,
No. 22 at p. 4) Similarly, Busse indicated that a 42 [deg]F average
outdoor air temperature may no longer be valid based on recent climate
change data. (Busse, No. 22 at p. 11)
---------------------------------------------------------------------------
\26\ DOE notes that the same requirement is also specified in
ANSI/ASHRAE 103-2017.
---------------------------------------------------------------------------
In response, DOE notes that homes in the United States--
particularly in the Northeast region, where most boilers are
installed--still experience temperatures as low as 5 [deg]F during the
heating season \27\ despite climate change trends. DOE does not have
any data, nor did Busse or other commenters provide any such data,
suggesting a value other than 5 [deg]F that would provide more
representative test results. As such, DOE is maintaining 5 [deg]F as
the outdoor design temperature in the appendix EE test procedure for
consumer boilers.
---------------------------------------------------------------------------
\27\ For example, daily temperature data for the Albany, NY,
area for the winter of 2022 (December 1, 2021, through March 1,
2022) shows 13 days during which the observed temperature reached at
or below 5 [deg]F. The Duluth, MN, area experienced 55 days during
which the observed temperature reached at or below 5 [deg]F during
the same time period. Data for these areas are available at
www.weather.gov/wrh/Climate?wfo=aly and www.weather.gov/wrh/Climate?wfo=dlh. Last accessed October 7, 2022.
---------------------------------------------------------------------------
Regarding the average outdoor air temperature, DOE examined average
outdoor air temperatures for the contiguous United States during the
months of October, November, December, January, February, and March
(i.e., the months during which consumer boilers would be expected to
operate).\28\ This data indicates that from
[[Page 15526]]
2012 through 2022, average outdoor air temperatures during these months
is 41 [deg]F, which aligns closely with the value of 42 [deg]F
specified in ANSI/ASHRAE 103-2017. Therefore, in this final rule, DOE
is maintaining the value of 42 [deg]F for TOA as specified
by ANSI/ASHRAE 103-2017.
---------------------------------------------------------------------------
\28\ These temperatures are published by the National Oceanic
and Atmospheric Administration and are available at
www.ncei.noaa.gov/access/monitoring/climate-at-a-glance/national/time-series. Last accessed October 7, 2022.
---------------------------------------------------------------------------
2. Ambient Conditions
The current test procedure for consumer boilers in appendix N,
through incorporation by reference of ANSI/ASHRAE 103-1993, specifies
that the ambient air temperature during testing must be between 65
[deg]F and 100 [deg]F for non-condensing boilers, and between 65 [deg]F
and 85 [deg]F for condensing boilers (see section 7 of appendix N and
section 8.5.2 of ANSI/ASHRAE 103-1993). In addition, the relative
humidity cannot exceed 80 percent during condensate measurement (see
section 8 of appendix N and section 9.2 of ANSI/ASHRAE 103-1993).
In the May 2020 RFI, DOE requested comment and data on the effects
of ambient temperature and relative humidity on AFUE results, whether
the current ranges of allowable conditions adversely impact the
representativeness of AFUE values or repeatability of AFUE testing, and
whether a narrower range of allowable ambient conditions would increase
testing burden. 85 FR 29352, 29356.
As discussed in the March 2022 NOPR, DOE received comments from
AHRI and manufacturers supporting the current range of allowable
operating conditions, while the CA IOUs and NEEA suggested limiting
this range to reflect the temperatures of spaces where boilers may be
installed. 87 FR 14622, 14631.
DOE investigated concerns regarding the ambient conditions as part
of the January 2016 Final Rule (see 81 FR 2628, 2638; Jan. 15, 2016).
Testing conducted in support of the January 2016 Final Rule indicated
there was no definitive impact of variation of ambient conditions on
the resultant AFUE, and DOE determined there was not adequate data to
justify changing the test procedure to narrow the ranges. In the March
2022 NOPR, DOE provided a similar tentative determination based on the
lack of sufficient evidence, and thus did not propose any changes at
that time. 87 FR 14622, 14631-14632.
In response, while the CA IOUs supported incorporation by reference
of ANSI/ASHRAE 103-2017, they encouraged DOE to reexamine the impacts
of ambient conditions on AFUE ratings by conducting additional testing.
(CA IOUs, No. 20 at p. 2) NYSERDA requested that DOE revise the test
procedure to ensure that condensing and non-condensing boilers are
tested under the same ambient conditions to allow consumers to make
informed decisions between these products. NYSERDA also requested that
DOE review the impacts of ambient temperature on boiler performance and
review the jacket loss assumptions based on likely real-world operating
conditions. Citing that DOE has not provided a further study on ambient
conditions since the 2016 rulemaking, NYSERDA urged DOE to revisit the
issue of ambient temperature impacts on consumer boiler performance and
conduct additional analysis and/or testing either as part of the
current rulemaking or in anticipation of the next statutorily mandated
review. (NYSERDA, No. 23 at p. 5)
The Joint Advocates stated they did not believe that separate
ambient conditions are necessary for non-condensing and condensing
boilers, and that the range of allowable ambient temperatures is too
broad to accurately measure energy use during a representative average
use cycle. The Joint Advocates cited course material from Continuing
Education and Development, Inc. indicating that a variation in ambient
temperature of 20 [deg]F can affect the thermal efficiency of a
commercial package boiler by over 0.5 percent, and therefore suggested
that DOE require the ambient temperature to be maintained between 65
[deg]F and 85 [deg]F for all consumer boilers. (Joint Advocates, No. 21
at p. 3)
Busse stated that a boiler tested at the current temperature and
humidity limits should perform at a higher AFUE than when tested at a
``normal'' lab condition of 70 [deg]F and 50 percent relative humidity
due to higher water vapor content and higher dew point temperature and
thus recommended limiting the test room conditions to 75 [deg]F and 55
percent relative humidity. Busse noted that the National Bureau of
Standards Information Report (``NBSIR'') recommended limits on the
original test room conditions,\29\ and that water vapor content and dew
point temperature vary significantly with temperature (specifically
providing information at 42 [deg]F [average outdoor air temperature],
70 [deg]F [``normal'' lab condition], and 85 [deg]F [maximum allowable
during AFUE test]). Busse also cited Burnham Holdings, Inc. (``BHI'')
test data for a single condensing boiler which showed a change in AFUE
of 1.3 percent when the relative humidity was changed from
approximately 30 percent to 70 percent. (Busse, No. 22 at p. 5)
---------------------------------------------------------------------------
\29\ Busse's comment references two reports from National Bureau
of Information: NBSIR 78-1543: ``Recommended Testing and Calculation
Procedures for Determining the Seasonal Performance of Residential
Central Furnaces and Boilers'' (September 1978) and NBSIR 80-2110,
``Recommended Testing and Calculation Procedures for Estimating the
Seasonal Performance of Residential Condensing Furnaces and
Boilers'' (April 1981).
---------------------------------------------------------------------------
DOE notes the data collected thus far has been on a limited sample
of boilers, and the information required to amend the ambient
conditions should reflect the array of boiler designs on the market.
The impact of the ambient air conditions would vary based on how the
ambient air interacts with the boiler during its normal operation. As
noted previously, in the January 2016 NOPR, DOE concluded that the test
data was not definitive enough to provide justification for changing
the ambient conditions. Regarding the data submitted by Busse, DOE
notes that BHI also provided that data point in a comment responding to
the May 2020 RFI (BHI, No. 11 at p. 2, 11). As discussed in the March
2022 NOPR, although BHI provided test data for a single unit showing a
difference in performance under different conditions, DOE notes that
DOE's previous test data, obtained from multiple units, did not
indicate conclusively that ambient test conditions within the current
bounds cause substantive differences in AFUE. As a result, DOE is not
amending the test procedure for consumer boilers to narrow or revise
the ambient test conditions at this time due to insufficient conclusive
evidence demonstrating the impact on AFUE for various boiler types.
3. Combustion Settings
In the course of the rulemaking for the January 2016 Final Rule, to
provide for greater consistency in burner airflow settings during
testing, DOE proposed specifying that the excess air ratio, flue oxygen
(``O2'') percentage, or flue carbon dioxide
(``CO2'') percentage be within the middle 30th percentile of
the acceptable range specified in the I&O manual. 80 FR 12876, 12883,
12906 (Mar. 11, 2015). In absence of a specified range in the I&O
manual, DOE proposed requiring the combustion airflow to be adjusted to
provide between 6.9 percent and 7.1 percent dry flue gas O2,
or the lowest dry flue gas O2 percentage that produces a
stable flame, no carbon deposits, and an air-free flue gas carbon
monoxide (``CO'') ratio below 400 parts per million (``ppm'') during
the steady-state test described in section 9.1 of ANSI/
[[Page 15527]]
ASHRAE 103-2007, whichever is higher. 80 FR 12876, 12906. However,
after considering comments regarding the representativeness of the
proposal and the potential impact on rated AFUE, DOE determined in the
January 2016 Final Rule that further study was needed to determine how
such changes would impact AFUE ratings. 81 FR 2628, 2636.
In the May 2020 RFI, DOE requested comment on whether more specific
instructions for setting the excess air ratio, flue O2
percentage, and/or flue CO2 percentage should be provided in
the consumer boilers test procedure, and if so, what those instructions
should entail. 85 FR 29352, 29356. DOE was particularly interested in
understanding whether such a change would improve the
representativeness of the test method, and whether it would impact test
burden.
In the March 2022 NOPR, after considering comments received in
response to the May 2020 RFI, DOE tentatively concluded that it lacked
sufficient data and information to indicate that establishing a
requirement for setting the excess air ratio, flue O2
percentage, and/or flue CO2 percentage would provide ratings
that are more representative than the ratings provided under the
current approach. Therefore, DOE tentatively determined to maintain the
current test procedure and did not propose to establish a requirement
for setting the excess air ratio, flue O2 percentage, and/or
flue CO2 percentage. 87 FR 14622, 14633.
In response to the March 2022 NOPR, the CA IOUs encouraged DOE to
examine the impacts of excess air ratio, flue oxygen percentage, and
flue carbon dioxide percentage on AFUE ratings by conducting additional
testing. (CA IOUs, No. 20 at p. 2) The Joint Advocates also encouraged
DOE to investigate the efficiency impacts of combustion airflow
settings and to consider establishing criteria around those settings in
the test procedure in order to provide more accurate product rankings.
The Joint Advocates asserted that excess air, which can be determined
by flue gas O2 and CO2 concentrations, affects
combustion efficiency and, as an example, cited a 2002 fact sheet
published by the National Renewable Energy Laboratory that indicated
combustion efficiency of commercial boilers can be increased by 1
percent for each 15 percent reduction in excess air ratio.\30\ (Joint
Advocates, No. 21 at p. 3-4)
---------------------------------------------------------------------------
\30\ The fact sheet referenced by the Joint Advocates is
available at: https://www.nrel.gov/docs/fy02osti/31496.pdf. (Last
accessed 11/3/2022).
---------------------------------------------------------------------------
NYSERDA recommended that DOE study how excess oxygen impacts the
efficiency of the boiler operation. NYSERDA pointed out that DOE
received input from multiple stakeholders regarding changes to excess
air ratio, flue O2 percentage, and/or flue CO2
percentage in the 2016 rulemaking cycle. NYSERDA urged DOE to either
revisit this proposal regarding excess oxygen or commit to further
study of this topic for a future revision. (NYSERDA, No. 23 at p. 4-5)
Busse suggested updating the test procedure to include two
requirements: (1) verify reduced input rate is 98 percent or greater
than nameplate minimum input rate and, if less than 98 percent, adjust
controls or settings as specified in the I&O manual and restart test at
maximum input rate or, if 98 percent or greater, no additional control
or setting changes are allowed; and (2) verify combustion products do
not exceed 400 parts per million air-free and there are no deposits of
carbon on the burner, and correct these conditions, if necessary, as
specified in the I&O manual. Busse stated that a reduced input rate
below 98 percent of nameplate minimum input rate would likely result in
a higher efficiency, and that requiring adjustment and restarting a
test when above 102 percent of nameplate minimum input rate could
increase test burden. Busse further stated that these provisions would
strive towards more accurate AFUE results while not greatly increasing
the testing burden. (Busse, No. 22 at p. 10)
In the January 2016 Final Rule, DOE explained that industry
stakeholders indicated that the current practice is typically to use
the CO2 percentage at the ``top'' of the manufacturer's
specified range, and in some cases, even higher than that. Stakeholders
provided data suggesting that the impacts on AFUE could be significant
but variable,\31\ and there was also concern that some products may not
feature any means of providing combustion setting adjustment. Finally,
commenters indicated that DOE must evaluate the burden associated with
potential re-testing should combustion setting specifications require
manufacturers to re-rate their products. As discussed previously, DOE
ultimately agreed that further study was needed on the impacts of the
CO2 percentage on AFUE and, therefore, declined to adopt the
proposed amendments. 81 FR 2628, 2635-2636. Thus, there remained a lack
of certainty regarding what settings would be most representative of
field use.
---------------------------------------------------------------------------
\31\ AHRI stated that the results of the testing of three
residential boilers that it conducted at Intertek Testing
Laboratories indicate that the proposed revised burner setup
requirements change AFUE by 0.3 percent for each 1 percent
difference in the CO2 values. By contrast, Burnham stated
that based on test data that it provided, for an oil-fired hot water
boiler with an 11.5 to 12.5 percent CO2 adjustment range
in the I&O manual, DOE's proposed adjustment would reduce AFUE by as
much as 1.0 percent compared to the rating under the existing test
procedure. 81 FR 2628, 2636.
---------------------------------------------------------------------------
DOE did not receive any information in response to the March 2022
NOPR that provided further clarity on this issue. Therefore, DOE has
determined that it still lacks sufficient information to indicate that
establishing a specification for excess air ratio, flue O2
percentage, and/or flue CO2 percentage would provide ratings
that are more representative than the ratings provided under the
current approach, and that doing so would not be unduly burdensome.
Therefore, DOE is maintaining the current instructions and is not
establishing additional requirements specifying excess air ratio, flue
O2 percentage, and/or flue CO2 percentage.
4. Supplemental Test Instructions
In the March 2022 NOPR, DOE responded to comments from BHI
suggesting that DOE create a repository of supplemental test
instructions, similar to that currently in place for commercial
boilers,\32\ instead of requiring a waiver to allow for use of specific
test instructions not included in the I&O manual or the DOE test
procedure. 87 FR 14622, 14635-14636. Specifically, BHI asserted that
control systems are increasingly complex, which makes it impractical to
run the test without special tools or codes, and that there are safety
and reliability concerns with putting testing-specific instructions in
the I&O manual. BHI also asserted that the use of the waiver process
for these test instruction issues is burdensome, unnecessary, and
inconsistent with the test procedure for commercial boilers.
---------------------------------------------------------------------------
\32\ For commercial boilers, DOE provides that a certification
report may include supplemental testing instructions, if such
information is necessary to run a valid test. Specifically,
supplemental information must include any additional testing and
testing set-up instructions (e.g., specific operational or control
codes or settings) which would be necessary to operate the basic
model under the required conditions specified by the relevant test
procedure. 10 CFR 429.60(b)(4).
---------------------------------------------------------------------------
In response, DOE noted that BHI did not provide specific examples
of test instructions that would not be able to be included in the I&O
manual due to concerns about safety or reliability, and that would thus
need to be presented in a waiver. In addition, DOE noted it has not
received any petitions for waiver for any basic models of consumer
boilers,
[[Page 15528]]
indicating there is not a problem with testing absent such additional
information. Therefore, DOE did not propose to establish a repository
for test instructions for consumer boilers and stated that if testing
of a consumer boiler necessitates controls or instructions other than
those included in the I&O manual, manufacturers may petition for a
waiver under the process established at 10 CFR 430.27. DOE sought
further comment on whether supplemental test instructions are necessary
for consumer boilers. 87 FR 14622, 14636.
Rheem recommended that DOE use the I&O manual provided with the
product as the primary instruction for testing a consumer boiler, and
where a manufacturer participates in a third-party certification
program (such as AHRI's) and declares supplemental instructions for
product testing, the manufacturer should have the option to use such
instructions for audit or enforcement testing. (Rheem, No. 18 at p. 5)
A.O. Smith recommended that some supplemental instructions from
manufacturers could ensure consistency in testing, such as the need to
use the recirculation loop to prevent flashing in the heat exchanger or
instructions to remove a water temperature sensor and plug the opening.
(A.O. Smith, No. 24 at p. 5) Busse suggested that supplemental test
instructions are necessary for minimum input rate adjustment (for step-
modulating condensing boilers) and for steam boiler low water cutoff
(wherein the feature periodically turns off the burner to monitor the
settled water level and therefore prevents the boiler from operating
continuously during a steady-state test). (Busse, No. 22 at p. 9)
As discussed in the March 2022 NOPR, DOE has not received any
petitions for waivers for any basic models of consumer boilers,
indicating there is not a problem with testing absent such additional
information. Should testing of a consumer boiler necessitate controls
or instructions other than those included in the I&O manual,
manufacturers may petition for a waiver under the process established
at 10 CFR 430.27.
5. Input Rates for Step Modulating Boilers
Appendix N includes a number of specific provisions for consumer
boilers with step modulating controls. Boilers with step modulating
controls are capable of operating at reduced input rates (i.e., less
than that maximum nameplate input rate) and gradually or incrementally
increasing or decreasing the input rate as needed to meet the heating
load. The test procedure currently requires step modulating boilers to
be tested at the maximum rate and the minimum (i.e., reduced) input
rate for the steady-state test (referencing section 9.1 of ANSI/ASHRAE
103-1993), the reduced input rate for the cool-down test (referencing
section 9.5.2.4 of ANSI/ASHRAE 103-1993), and the reduced input rate
for the heat-up test (referencing section 9.6.2.1 of ANSI/ASHRAE 103-
1993). In addition, both the optional tracer gas test and the
measurement of condensate under cyclic conditions, when conducted, are
performed at the reduced input rate (referencing sections 9.7.5 and 9.8
of ANSI/ASHRAE 103-1993, respectively). ANSI/ASHRAE 103-2017 contains
the same input rate requirements for modulating boilers as ANSI/ASHRAE
103-1993.
In the May 2020 RFI, DOE requested comment on whether the existing
provisions for testing step modulating boilers appropriately reflect
the performance of such boilers. If not, DOE sought specific
recommendations on the changes that would be necessary to make the test
procedure more representative for such products. 85 FR 29352, 29357.
Commenters indicated these provisions were adequate, and DOE did not
propose any amendments to the provisions for testing step modulating
boilers in the March 2022 NOPR. 87 FR 14622, 14633.
In response to the March 2022 NOPR, BWC stated that it appreciated
DOE not proposing that step modulating units account for operation at
any additional input rates beyond those specified in the current test
procedure. BWC stated that the test methods in ANSI/ASHRAE 103-2017
sufficiently measure the performance of these units at different input
rates and are representative of a product's average use cycle. (BWC,
No. 19, p. 4)
For the reasons discussed in the March 2022 NOPR, and in
consideration of the comments received, DOE is not adopting any changes
to the provisions for testing step modulating boilers in this final
rule.
6. Return Water Temperature
The test procedure at appendix N currently requires a nominal
return water temperature (``RWT'') of 120 [deg]F to 124 [deg]F for non-
condensing boilers and 120 [deg]F 2 [deg]F for condensing
boilers (see section 7 of appendix N and sections 8.4.2.3 and 8.4.2.3.2
of ANSI/ASHRAE 103-1993, which are incorporated by reference).
In response to the May 2020 RFI, the CA IOUs requested that DOE
consider adopting multiple RWTs in the amended test procedure for
consumer boilers, consistent with the methodology being developed by
the ASHRAE Standard 155P Committee for testing and rating commercial
boilers, which requires testing at multiple RWTs depending on the
operational characteristics of the boiler. As discussed in the March
2022 NOPR, DOE considers the impact of varying RWTs on field-installed
efficiency in its energy conservation standards rulemakings. In the
previous energy conservation standards rulemaking for consumer boilers,
DOE developed AFUE adjustment factors for low, medium, and high RWT
scenarios and estimated that, on average, AFUE would vary from the
rated value by 2.66 percent to +3.15 percent depending on the model
characteristics and RWT (see 81 FR 2320, 2354); however, DOE noted
there is still a wide range of potential RWTs in the field. Thus, in
the March 2022 NOPR, DOE sought additional comment on whether the RWT
requirements in the current test method and ANSI/ASHRAE 103-2017 are
representative and appropriate, and whether any specific changes to the
required conditions could improve representativeness. DOE also sought
comment on any associated test burden with changing RWTs. 87 FR 14622,
14633.
In response, the CA IOUs reiterated their request for DOE to review
whether the 120 [deg]F RWT requirement is appropriately representative
of real-world operating conditions. (CA IOUs, No. 20 at p. 2)
AHRI and AGA & APGA urged DOE to align return water temperatures
with those in ANSI/ASHRAE 103-2017. (AHRI, No. 26 at p. 3; AGA & APGA,
No. 25 at p. 2)
BWC supported DOE's tentative conclusion of including the single
return water temperature specified in ANSI/ASHRAE 103-2017 for ease of
comparison between models and manufacturers. (BWC, No. 19 at p. 4) BWC
asserted that a single condition would not increase the test burden.
(BWC, No. 19 at p. 4)
A.O. Smith commented that the current return water temperature is
representative of an average value for the wide range of operating
temperatures in the field and indicated that requiring testing to
multiple conditions may require adjustment of the standards. A.O. Smith
added that non-condensing boilers are more likely to be installed in
systems with higher supply and return water temperatures, and
condensing boilers are more likely to be installed in systems with
lower temperatures. (A.O. Smith, No. 24 at p.
[[Page 15529]]
3-4) A.O. Smith stated that testing at multiple water temperatures
would add testing burden to a test that could already span two days to
complete, and that the burden to retest and rerate products would also
include updating heat output ratings and safety certifications. (Id.)
Rheem supported maintaining the return water temperature in the
current test method, asserting that any change that could make the
return water temperature more representative would be outweighed by the
testing and certification burden on manufacturers. Specifically, Rheem
noted that slight changes to the water temperature would not produce
significantly more representative results, and major changes would
require retesting of nearly all consumer boilers. (Rheem, No. 18 at p.
4)
Crown and U.S. Boiler supported the use of the water temperatures
specified by ANSI/ASHRAE 103-2017 to reduce testing burden and
complication. Crown and U.S. Boiler stated that a single set of water
temperatures for all types of hot water boilers is appropriate to avoid
consumer confusion, increased certification burden, and departure from
the industry test method. Crown and U.S. Boiler added that changes to
these water temperatures would cause significant changes in AFUE
ratings for condensing boilers. (Crown, No. 16 at p. 3-4; U.S. Boiler,
No. 17 at p. 3-4)
NYSERDA noted that return water temperature has a significant
impact on boiler performance and urged DOE to incorporate return water
temperatures that more accurately reflect real-world conditions.
NYSERDA stated that the 120 [deg]F return water temperature is too low,
does not represent the boiler running conditions according to a
research study done by The Electric and Gas Program Administrators of
Massachusetts Part of the Residential Evaluation Program Area in
2015,\33\ and should be considered closer to 140 [deg]F. NYSERDA
claimed that the rationale for choosing the 120 [deg]F return water
temperature from 1978 is outdated and inconsistent with DOE's current
test procedure methodologies for commercial HVAC equipment. NYSERDA
recommended that DOE test at both 120 [deg]F and 140 [deg]F for return
water temperatures but stated that if DOE had to test at only one
temperature, it should be 140 [deg]F. (NYSERDA, No. 23 at p. 2-4)
---------------------------------------------------------------------------
\33\ High Efficiency Heating Equipment Impact Evaluation,
Prepared for: The Electric and Gas Program Administrators of
Massachusetts Part of the Residential Evaluation Program Area, March
2015 at 22, available at ma-eeac.org/wp-content/uploads/High-Efficiency-Heating-Equipment-Impact-Evaluation-Final-Report.pdf.
---------------------------------------------------------------------------
The Joint Advocates urged DOE to continue to investigate return
water temperatures used in the test procedure to capture more
representative performance, directing attention to data presented in
appendix 7B to DOE's preliminary analysis technical support document
(``TSD''),\34\ which indicated that there was an impact of return water
temperature on the thermal efficiency \35\ of a boiler. The Joint
Advocates suggested that multiple temperatures (i.e., 108 [deg]F and
158 [deg]F) would be more appropriate to be able to differentiate
amongst different condensing boiler models, and that non-condensing
boilers should be tested at a higher temperature of 158 [deg]F. (Joint
Advocates, No. 21 at p. 2-3)
---------------------------------------------------------------------------
\34\ Appendix 7B of the preliminary analysis TSD is available at
www.regulations.gov at Docket Number EERE-2019-BT-STD-0036. The data
can be found in chapter 7B, page 11.
\35\ Thermal efficiency for a commercial packaged boiler is
determined using test procedures prescribed under 10 CFR 431.86 and
is the ratio of the heat absorbed by the water or the water and
steam to the higher heating value in the fuel burned. Data presented
in the May 2022 Preliminary Analysis TSD reflected the performance
of commercial packaged boilers due to the absence of information on
consumer boilers.
---------------------------------------------------------------------------
Busse stated that the current RWT settings were from NBSIR 80-2110
and asserted that the underlying assumptions for the current return
water temperature found in NBSIR 80-2110, pages 1-2 are out of date or
invalid.\36\ Busse stated that the average distribution system water
temperature in the current DOE test procedure should be closer to 133
[deg]F based on heat load calculations to maintain a home at 65 [deg]F.
Busse noted that the current test procedure has an average distribution
system water temperature of 130 [deg]F (based on a return water
temperature of 120 [deg]F and an outlet temperature of 140 [deg]F).
However, Busse added that the average distribution system water
temperature may be too high based on current or historically available
heat distribution products, and that review literature from two cast-
iron baseboard manufacturers and two finned-tube copper baseboard
manufacturers suggest an average distribution system water temperature
of 127 [deg]F would be more representative. Busse stated that current
industry practice for step-modulating, condensing boilers may not allow
operation at the original 190 [deg]F average boiler water temperature
(200 [deg]F supply) or deliver 140 [deg]F supply temperature at the 42
[deg]F average outdoor temperature at the default controller settings.
(Busse, No. 22 at p. 2-4) Busse recommended that a separate test should
be required for determining heating capacity using a 180 [deg]F return
supply water temperature (or the maximum supply temperature allowed by
the control system, if less than 200 [deg]F), or, alternatively, the
current return water temperature could be used with consideration of
sensible heat losses only in order to estimate the steady-state
efficiency for a noncondensing operation at high return water
temperatures. (Busse, No. 22 at p. 6) Busse also asserted that boilers
with reported ratings of 95 percent or 96 percent AFUE have such
ratings as a result of a flawed calculation in the current test
procedure, which does not account for the portion of the season during
which the boiler would operate in a non-condensing mode (due to return
water temperatures being higher than 120 [deg]F in certain conditions).
(Busse, No. 22 at p. 11-12)
---------------------------------------------------------------------------
\36\ Kelly, George E. and Kuklewicz, Mark E., NBSIR 80-2110:
Recommended Testing and Calculation Procedures for Estimating the
Seasonal Performance of Residential Condensing Furnaces and Boilers,
National Bureau of Standards (Sponsored by U.S. Department of
Energy), April 1981.
---------------------------------------------------------------------------
As acknowledged by commenters, the specification of RWT has a
substantive impact on the AFUE of boilers. Condensing boilers in
particular achieve higher efficiency levels by extracting latent heat
from the flue gases in addition to sensible heat (i.e., the
condensation of flue gases releases a substantial amount of energy into
the water that is being heated). However, flue gases can condense only
if the dew point temperature of the vapor is reached. If the return
(inlet) water is hotter than this dew point temperature, then
condensation of the flue gases cannot occur in the heat exchanger, and
the boiler operates in a non-condensing mode, reducing AFUE.
In addition to the recommendations provided by commenters, DOE
research indicates a range of RWTs in consumer applications. DOE is
aware that many existing consumer boiler installations require the RWT
to be 160 [deg]F and some even as high as 180 [deg]F.\37\ However, as
new applications such as radiant floor heating and heat pump boilers
become more prevalent in the market, DOE recognizes that some new
boilers may be installed in homes that require lower
[[Page 15530]]
RWTs. In addition, condensing boilers in new installations would be
subject to lower RWTs because radiant floor heating and hydronic air
handler applications represent a substantial proportion of new hot
water boiler installations.\38\ DOE research indicates some
installations have RWT conditions as low as 85 [deg]F in certain
cases.\39\ DOE notes that the midpoint of the range of RWTs observed
through DOE's research (ranging between 85 [deg]F and 160 [deg]F) is
122 [deg]F, which is reasonably close to the 120 [deg]F condition
specified in appendix N and the industry test procedures. Given these
considerations, DOE has determined that testing a consumer boiler at a
single ``high'' RWT, as suggested by the Joint Advocates, NYSERDA, and
Busse, would be less representative than the conditions specified by
the current test procedure.
---------------------------------------------------------------------------
\37\ On May 4, 2022, DOE published in the Federal Register a
notice of availability of the preliminary analysis for energy
conservation standards for consumer boilers (the ``May 2022
Preliminary Analysis''). 87 FR 26304. DOE provided a technical
support document (``TSD'') for the May 2022 Preliminary Analysis in
the rulemaking docket. Id. In the energy use analysis of the May
2022 Preliminary Analysis TSD, DOE estimated that 90 percent of
condensing boilers installed as replacements to non-condensing
boilers would be subject to a higher RWT of 158 [deg]F to 160
[deg]F.
\38\ In the May 2022 Preliminary Analysis, DOE estimated that
condensing boilers in new installations (new constructions or new
owners) would be subject to an average RWT of 108 [deg]F. See
Appendix 7B of the preliminary analysis TSD, available at:
www.regulations.gov/document/EERE-2019-BT-STD-0036-0021.
\39\ See, for example: www.barronheating.com/blog/the-book-on-
radiant-heating-when-it-makes-sense-and-when-it-might-not/
#:~:text=Radiant%2Dfloor%20heating%20systems%20typically,55%E2%80%937
0%C2%B0C). (Last accessed on October 6, 2022)
---------------------------------------------------------------------------
DOE also acknowledges the concerns raised by manufacturers
regarding the potential need to retest and recertify all consumer
boilers if a new test condition were to be required in addition to the
currently established 120 [deg]F condition. EPCA requires DOE to
establish test procedures that are reasonably designed to produce test
results that measure energy efficiency of a consumer boiler during a
representative average use cycle or period of use, as determined by the
Secretary, and shall not be unduly burdensome to conduct. (42 U.S.C.
6293(b)(3)) Based on the considerations discussed in this section, DOE
has determined that it lacks data and information to conclude that a
different RWT (or multiple RWTs) would be more representative than the
current RWT requirements such that it would justify the potential
burden of such a change. Hence, in this final rule, DOE is finalizing
its proposal from the March 2022 NOPR to incorporate by reference the
test conditions in ANSI/ASHRAE 103-2017. Should additional data or
information become available in the future, DOE would consider this
topic again in a subsequent test procedure rulemaking.
7. Standby Mode and Off Mode Electrical Energy Consumption
As discussed in section I.A of this final rule, EPCA requires that
DOE amend test procedures to include standby mode and off mode energy
consumption, ``taking into consideration the most current versions of
Standards 62301 and 62087 of the International Electrotechnical
Commission.'' (42 U.S.C. 6295(gg)(2)(A)) The DOE test method currently
references IEC 62301 (Edition 2.0 2011-01), which provides instructions
for measuring standby mode and off mode energy consumption. IEC 62301
provides several options for measuring the standby mode and off mode
power consumption using either the ``sampling method,'' ``average
reading method,'' or ``direct meter reading method.'' Although these
methods vary, if the standby or off mode consumption is stable, each
method can be completed in under 1 hour, and the sampling method can be
completed in as little as 15 minutes.
In the March 2022 NOPR, DOE tentatively determined that the
provisions in IEC 62301 provide an appropriate representation of
standby mode and off mode energy consumption of consumer boilers and
are not unduly burdensome; hence DOE did not propose any changes.
Because commenters responding to the May 2020 RFI recommended
streamlining the procedure for determining standby mode and off mode
energy consumption, in the March 2022 NOPR DOE requested further
comment on whether a simplified approach for measuring standby mode and
off mode electrical energy consumption is appropriate and would provide
accurate, representative results that are comparable to those obtained
with IEC 62301. 87 FR 14622, 14634.
In response, BWC commented that the standby mode and off mode test
methods are appropriate and do not need to be amended at this time.
(BWC, No. 19 at p. 4)
Rheem stated that the current approach for measuring standby and
off mode electrical energy consumption is not overly burdensome and
should be maintained. Rheem also recommended that DOE examine a
combined AFUE metric that includes standby and off mode electrical
energy use, asserting that an increase in standby and off mode energy
use may be needed to accommodate an increase in overall efficiency, and
thus a combined AFUE metric would provide for greater design
flexibility. (Rheem, No. 18 at p. 4)
DOE considered an integrated AFUE metric (``AFUEI'') in
a test procedure final rule published October 20, 2010 (``October 2010
Final Rule''), which established the standby mode and off mode
electrical energy use metrics. 75 FR 64621, 64626-64627 (Oct. 20,
2010). In the October 2010 Final Rule, DOE explored the possibility of
regulating AFUEI; however, commenters objected that the
approach would provide an ineffective basis for regulation, and thus it
was not ``technically feasible'' to integrate AFUE with standby mode
and off mode energy consumption. Id. Separate metrics were established
because the magnitude of the standby mode and off mode energy
consumption was very small compared to the active mode fuel
consumption, and, as a result, it was not possible to discern different
levels of standby and off mode power consumption (i.e.,
AFUEI values were essentially identical to AFUE values). Id.
Neither Rheem nor other commenters have presented DOE with any
information to suggest that the conclusions from the October 2010 Final
Rule--specifically, that an integrated metric would not be technically
feasible--are no longer applicable. Furthermore, DOE is not aware of
any current industry-accepted test procedure that combines the current
AFUE metric with the standby mode and off mode power consumption
metrics. For these reasons, DOE is not adopting any new provisions for
a combined metric in this final rule.
A.O. Smith recommended eliminating the standby mode and off mode
power consumption testing due to the little impact the associated power
consumption has on the total efficiency of a consumer boiler (less than
a fraction of one percent). A.O. Smith indicated that procuring the
adequate equipment and instrumentation required for this testing is
burdensome. A.O. Smith also commented that removing these requirements
would afford manufacturers the opportunity to potentially add safety
enhancements such as carbon monoxide sensors, which require a small
heating element to prevent premature failure, as well as options for
control displays and ways to reduce cycling losses. (A.O. Smith, No. 24
at p. 4) A.O. Smith recommended that if DOE were to keep the standby
mode and off mode tests as part of the test procedure, the standby mode
and off mode power consumption should be measured with a simple current
measurement with a calibrated watt meter. (A.O. Smith, No. 24 at p. 6)
As discussed, EPCA requires that DOE include in its test procedures
a method
[[Page 15531]]
for measuring standby mode and off mode power consumption, unless
technically infeasible. (42 U.S.C. 6295(gg)(2)(A)) Further, in doing
so, EPCA requires that DOE must consider IEC Standard 62301 and IEC
Standard 62087. (42 U.S.C. 6295(gg)(2)(A)) Section 4.4 of IEC 62301
provides instruction on selecting acceptable power measuring
instrumentation by specifying power measurement uncertainty bounds,
frequency response, and long-term averaging (integrating) requirements.
DOE notes that if a calibrated watt meter is capable of meeting these
requirements, then it may be used in accordance with section 4.4 of IEC
62301.
AHRI noted that standby mode and off mode power consumption should
not count as a loss because all energy brought into the system provides
useful resistive heat to the building. AHRI stated that similar logic
is used to give electric boilers a rating of 100 percent efficiency.
(AHRI, No. 26 at p. 3)
While electrical component power draws that dissipate small amounts
of heat to the surroundings may contribute to useful heating to the
building, the building does not always demand heating. During the
cooling season, any heat dissipated would be counterproductive.
Furthermore, not all boilers are located in conditioned spaces. In
addition, as discussed previously, EPCA requires DOE to include in its
test procedures a method for measuring standby mode and off mode power
consumption. (42 U.S.C. 6295(gg)(2)(A)) For these reasons, DOE makes no
change to its inclusion of standby mode and off mode power in this
final rule.
In conclusion, DOE has determined that no changes to the standby
mode and off mode test provisions are warranted. As such, the new
appendix EE test procedure maintains the same test methods for
measuring these metrics as specified in the current appendix N test
procedure.
8. Full Fuel Cycle Efficiency
The full fuel cycle (``FFC'') accounts for the energy consumed in
extracting, processing, and transporting fuels. In the March 2022 NOPR,
DOE responded to comments received in response to the May 2020 RFI
requesting that DOE consider incorporating an FFC analysis into the
test procedure in order to allow for direct comparisons between fossil
fuel-fired systems and electric systems. 87 FR 14622, 14634. DOE
responded that FFC is typically considered in energy conservation
standards rulemakings--not as a metric for representing product
efficiency. Id. In the March 2022 NOPR, DOE maintained its previous
conclusion from the January 2016 Final Rule that a mathematical
adjustment to the test procedure to account for FFC is not appropriate
because the mathematical adjustment to the site-based energy descriptor
relies on information that is updated annually, which would require
annual updating of the test method. Id.
In response to the March 2022 NOPR, BWC stated that the FFC
efficiency and source efficiency analysis are not appropriate to
include in the Federal test procedure. (BWC, No. 19, p. 4)
For the reasons discussed in the March 2022 NOPR, DOE maintains in
this final rule its previous determination not to account for FFC in
the consumer boiler test procedure.
9. Idle Losses
In the March 2022 NOPR, DOE responded to comments received in
response to the May 2020 RFI requesting that DOE consider ``idle
losses'' that are not captured in the AFUE metric. 87 FR 14622, 14628.
Specifically, Energy Kinetics asserted that oversizing of boilers can
lead to wasted energy to heat up the boiler but not contribute to the
heating of the hydronic loop. In the March 2022 NOPR, DOE stated that
EPCA (42 U.S.C. 6295(f)(3)(A)-(B)) requires hot water boilers to have
an automatic means for adjusting water temperature, which limits idle
losses. DOE indicated that idle losses could be further addressed in
the determination of AFUE; however, there was insufficient data to
propose amendments to the test procedure to do so. DOE sought further
comment from interested parties on the topic. 87 FR 14622, 14628.
In response to the March 2022 NOPR, Rheem agreed with DOE's
statement that the prescriptive design requirements in EPCA at 42
U.S.C. 6295(f)(3) effectively reduce idle losses in the field. Rheem
noted that if idle losses, both electrical and fossil fuel, were fully
accounted for in the AFUE metric, then a standard could be proposed
that would not require separate design requirements. (Rheem, No. 18 at
p. 5)
DOE has determined that there remains insufficient information to
further address idle losses in this rulemaking as it pertains to the
determination of AFUE in the new appendix EE test procedure for
consumer boilers.
H. Alternative Efficiency Determination Methods
At 10 CFR 429.70, DOE includes provisions for alternative
efficiency determination methods (``AEDMs''), which are computer
modeling or mathematical tools that predict the performance of non-
tested basic models. They are derived from mathematical models and
engineering principles that govern the energy efficiency and energy
consumption characteristics of a type of covered equipment. These
computer modeling and mathematical tools, when properly developed, can
provide a relatively straight-forward and reasonably accurate means to
predict the energy usage or efficiency characteristics of a basic model
of a given covered product or equipment and reduce the burden and cost
associated with testing. 78 FR 79579, 79580 (Dec. 31, 2013; the
``December 2013 AEDM Final Rule''). Where authorized by regulation,
AEDMs enable manufacturers to rate and certify their basic models by
using the projected energy use or energy efficiency results derived
from these simulation models in lieu of testing. Id. at 78 FR 79580.
DOE does not currently authorize the use of AEDMs for consumer
boilers, whereas DOE does authorize the use of AEDMs for commercial
packaged boilers.\40\ Manufacturers of consumer boilers (or furnaces
more generally) are not authorized to use an AEDM to determine ratings
for these products. However, manufacturers of cast-iron boilers may
determine AFUE for models at a capacity other than the highest or
lowest of the group of basic models having identical intermediate
sections and combustion chambers through linear interpolation of data
obtained for the smallest and largest capacity units of the family. See
10 CFR 429.18(a)(2)(iv)(A). These provisions already provide
manufacturers with an alternative method of rating consumer boilers
without testing every model, and this alternative method reduces
manufacturer test burden.
---------------------------------------------------------------------------
\40\ In the December 2013 AEDM Final Rule, DOE explained that
the AEDM provisions extend to those products or equipment which
``have expensive or highly-customized basic models.'' 78 FR 79579,
79580. The current AEDM provisions for commercial HVAC equipment
(including commercial package boilers, for example) were in part the
result of a negotiated rulemaking effort by the Appliance Standards
and Rulemaking Federal Advisory Committee (ASRAC) in 2013. Id.
Boilers designed for residential applications were not considered at
the time. 78 FR 79579.
---------------------------------------------------------------------------
In the March 2022 NOPR, DOE requested comment on whether AEDM
provisions similar to those in place for commercial equipment would be
necessary and appropriate for consumer boilers. 87 FR 14622, 14635.
A.O. Smith stated that adding an AEDM option for consumer boilers
would be reasonable; however, there is
[[Page 15532]]
greater value to have an AEDM for commercial products given that those
models can be engineered to order. (A.O. Smith, No. 24 at p. 4) Busse
indicated that the breadth of a product line with similar geometries
and performance would not seem to justify an AEDM; however, an AEDM may
be the only method to avoid testing each model. (Busse, No. 22 at p. 8)
In consideration of these comments, as well as considerations
discussed in the March 2022 NOPR (see 87 FR 14622, 14635), in this
final rule, DOE concludes that manufacturer testing burden is
alleviated by the linear interpolation provisions for cast-iron
boilers, such that an AEDM for consumer boilers more broadly is not
warranted at this time.
I. Certification Provisions for Cast-Iron Boilers
As discussed in the March 2022 NOPR, the certification provisions
at 10 CFR 429.18(a)(2)(iv)(A) alleviate testing burden for cast-iron
boilers, which are commonly constructed of identical cast-iron heat
exchanger sections. Boilers of the same cast-iron product family are
often constructed so that the heating capacity can be increased by
adding more sections to the heat exchanger. When a product family is
designed in this way, linear interpolation is accurate \41\ to predict
the performance of intermediately-sized boilers. The March 2022 NOPR
sought data and other information that would demonstrate that using a
linear interpolation method for heat exchanger materials other than
cast-iron would produce representative test results. 87 FR 14622,
14635.
---------------------------------------------------------------------------
\41\ Test data analyzed as part of the 1979 rulemaking which
established these provisions showed that the annual fuel utilization
efficiency, energy consumption, and estimated annual operating cost
of sectional cast-iron boilers can be accurately predicted by a
linear interpolation based on data obtained from units having the
smallest and largest number of intermediate sections. 44 FR 22410,
22415 (April 13, 1979).
---------------------------------------------------------------------------
AHRI and AGA and APGA supported extending of the use of linear
interpolation to heat exchanger materials other than cast-iron, stating
that linear interpolation is a valid calculation method for these
products, as proven by the current cast-iron allowance. (AHRI, No. 26
at p. 4; AGA and APGA, No. 25 at p. 2)
A.O. Smith supported use of the interpolation method for boilers
with heat exchangers other than cast-iron, stating that its copper
finned-tube boilers have a tray of tubes that increase in length
proportionate to input rate, are consistent in geometry, and have only
incremental changes proportionate to input rate. A.O. Smith added that
its Lochinvar brand models have seven input rates ranging from 45,000
Btu/h through 260,000 Btu/h and all perform near 84.0-percent AFUE.
(A.O. Smith, No. 24 at p. 5)
Rheem did not support the use of linear interpolation for
certification of consumer boilers beyond what is already allowed for
cast-iron boilers, stating that interpolation produces less accurate
results than results derived from actual tests. (Rheem, No. 18 at p. 4)
Busse did not support using a linear interpolation method for heat
exchanger materials other than cast-iron. Busse asserted that any
difference and/or non-proportionality in excess air, flue loading, and/
or flue cross-sectional area could produce non-linear results, which is
also why cast-iron units equipped with draft hoods, draft diverters, or
induced draft systems are more prone to producing non-linear results.
(Busse, No. 22 at p. 7-8)
Based on DOE's review of product literature, DOE has determined
that heat exchangers made of different materials may not be constructed
with identical additive components the way cast-iron sectional heat
exchangers are constructed; hence, the linear interpolation method may
be less viable for other heat exchanger materials. DOE notes that
stakeholders commenting in support of using linear interpolation for
materials other than cast-iron did not provide any data to demonstrate
the viability of a linear interpolation method for other heat exchanger
materials. Given the concerns raised by Rheem and Busse regarding the
potential for non-linear results for intermediately-sized boilers with
non-cast-iron heat exchangers, as well as DOE's review of product
literature, DOE has concluded that there is not enough information to
substantiate such a provision at this time. Hence, in this final rule,
DOE maintains that the linear interpolation AEDM method applies only to
cast-iron boilers.
Additionally, Busse recommended the following clarifications for
using linear interpolation: (1) clarify if interpolated values are
derived from truncated or pre-truncated AFUE values of smallest and
largest capacity units, (2) update 10 CFR part 429 to allow
interpolation of heating capacity derived from unrounded
EffySS values of smallest and largest capacity units, and
(3) require third-party test agencies to qualify AFUE and heating
capacity on an ``interpolated'' model. (Busse, No. 22 at p. 7-8)
First, as discussed in section III.F.8, DOE has amended the
certification requirements for AFUE in the July 2022 Certification
Final Rule to require that AFUE must be rounded to the nearest tenth of
a percentage point when this value is reported. 87 FR 43968. Thus, as
of this final rule, truncation is no longer used to report AFUE. DOE is
clarifying in this final rule, however, that manufacturers may use
either the rounded or unrounded AFUE values of the smallest and largest
capacity units for linear interpolation. DOE is making this
determination based on the fact that the results of the linear
interpolation would be minimally impacted by rounding AFUE to the
nearest tenth of a percentage point, compared to using unrounded
values.
Second, DOE notes that heating capacity (QOUT), which is
calculated in the current test procedure as a function of steady-state
efficiency (EffySS), is not required to be certified to DOE
at this time, nor has DOE proposed to make this a requirement.
Currently, manufacturers must certify the nameplate input rate
(QIN), which is a separate metric and not a function of
EffySS. Hence, DOE is not updating the linear interpolation
provisions to include heating capacity (QOUT).
Third, requiring third-party testing to qualify AFUE ratings
derived using the linear interpolation method would eliminate the
reduction in test burden achieved with the alternate linear
interpolation approach. DOE notes, however, that it can conduct
assessment or enforcement testing on consumer boiler models, and this
process serves to verify ratings (see subpart C to 10 CFR part 429).
In conclusion, DOE has determined in this final rule not to amend
the linear interpolation provisions for consumer boilers.
J. Effective and Compliance Dates
The effective date for the adopted test procedure amendment will be
30 days after publication of this final rule in the Federal Register.
EPCA prescribes that all representations of energy efficiency and
energy use, including those made on marketing materials and product
labels, must be made in accordance with an amended test procedure,
beginning 180 days after publication of the final rule in the Federal
Register. (42 U.S.C. 6293(copyright)(2)) EPCA provides an allowance for
individual manufacturers to petition DOE for an extension of the 180-
day period if the manufacturer may experience undue hardship in meeting
the deadline. (42 U.S.C. 6293(c)(3)) To receive such an extension,
petitions must be filed with DOE no later than 60 days before the end
of the 180-day period and must detail how the
[[Page 15533]]
manufacturer will experience undue hardship. (Id.)
K. Test Procedure Costs
EPCA requires that test procedures proposed by DOE not be unduly
burdensome to conduct. (42 U.S.C. 6293(b)(3))
In the March 2022 NOPR, DOE discussed that the amendments proposed
to the test procedure for consumer boilers would be expected to have
minimal impact on efficiency ratings such that manufacturers would not
be required to retest and recertify ratings. 87 FR 14622, 14625, 14636.
DOE also tentatively determined that the proposed amendments would not
impact testing costs or increase burden. DOE requested feedback from
stakeholders on these tentative determinations. Id.
A.O. Smith supported DOE's determination that the proposed
incorporation by reference of ASHRAE 41.6-2014 will not increase
testing burden. A.O. Smith also stated that DOE's estimate for third-
party AFUE testing is reasonable and agreed that the proposed
incorporation by reference of ANSI/ASHRAE 103-2017 is not unduly
burdensome. (A.O. Smith, No. 24 at p. 5) A.O. Smith stated that
although there may be fractional changes in the AFUE rating as a result
of testing to the 2017 version, these should not necessitate retesting
or rerating of any existing boilers. A.O. Smith also supported having a
publicly available AFUE calculation tool to enhance consistency of
results across the industry. (A.O. Smith, No. 24 at p. 3)
Rheem stated that the test costs under the proposed appendix EE
test procedure are likely to remain similar to the current appendix N
test procedure. (Rheem, No. 18 at p. 5)
AHRI stated that it previously commented that a move to ANSI/ASHRAE
103-2017 would not result in increased test burden; however, it had
come to AHRI's attention that there are manufacturers using automated
programs that would incur an increased test burden. (AHRI, No. 26 at p.
4)
DOE understands that AHRI is referring to pre-programmed cycle
times, which execute burner on and off functions at pre-determined
times per the DOE test procedure. From DOE's own testing of the impact
of cycle timings at a third-party lab using an automated program, DOE
has determined that these parameters can be simple to re-program and
that doing so would not constitute undue test burden. As discussed in
section III.D.1.c, other commenters requested DOE to further
investigate whether the update in cycle times would increase burden by
requiring retesting. Based on test data indicating little variation in
test results due to the update in cycle times, DOE has determined that
the impact of these amendments on ratings would be minimal. With regard
to providing a publicly available AFUE calculation tool, DOE provides
test report templates on its certification website,\42\ including a
template for the consumer boiler test procedure.
---------------------------------------------------------------------------
\42\ Standardized test report templates are available online at:
www.energy.gov/eere/buildings/standardized-templates-reporting-test-results.
---------------------------------------------------------------------------
For this final rule, DOE has evaluated the impacts on ratings
resulting from its adoption of the test methods in the updated industry
test standard, ANSI/ASHRAE 103-2017. These updates are discussed in
detail in section III.D.1 of this final rule. Based on this review, DOE
has determined that manufacturers will be able to rely on data
generated under the current test procedure. As such, it is unlikely
that retesting of consumer boilers would be required solely as a result
of DOE's adoption of the finalized amendments to the test procedure.
However, if a manufacturer were to retest a model using the amended
test procedure as finalized, DOE estimates that the cost of performing
the amended AFUE test at a third-party laboratory would be $3,600, the
same as the cost of performing the current AFUE test. This estimate
represents an increase of $600 from the cost estimate in the March 2022
NOPR, to account for overall increases in laboratory testing fees.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866 and 13563
Executive Order (``E.O.'') 12866, ``Regulatory Planning and
Review,'' as supplemented and reaffirmed by E.O. 13563, ``Improving
Regulation and Regulatory Review,'' 76 FR 3821 (Jan. 21, 2011),
requires agencies, to the extent permitted by law, to (1) propose or
adopt a regulation only upon a reasoned determination that its benefits
justify its costs (recognizing that some benefits and costs are
difficult to quantify); (2) tailor regulations to impose the least
burden on society, consistent with obtaining regulatory objectives,
taking into account, among other things, and to the extent practicable,
the costs of cumulative regulations; (3) select, in choosing among
alternative regulatory approaches, those approaches that maximize net
benefits (including potential economic, environmental, public health
and safety, and other advantages; distributive impacts; and equity);
(4) to the extent feasible, specify performance objectives, rather than
specifying the behavior or manner of compliance that regulated entities
must adopt; and (5) identify and assess available alternatives to
direct regulation, including providing economic incentives to encourage
the desired behavior, such as user fees or marketable permits, or
providing information upon which choices can be made by the public. DOE
emphasizes as well that E.O. 13563 requires agencies to use the best
available techniques to quantify anticipated present and future
benefits and costs as accurately as possible. In its guidance, the
Office of Information and Regulatory Affairs (``OIRA'') in the Office
of Management and Budget (``OMB'') has emphasized that such techniques
may include identifying changing future compliance costs that might
result from technological innovation or anticipated behavioral changes.
For the reasons stated in the preamble, this final regulatory action is
consistent with these principles.
Section 6(a) of E.O. 12866 also requires agencies to submit
``significant regulatory actions'' to OIRA for review. OIRA has
determined that this final regulatory action does not constitute a
``significant regulatory action'' under section 3(f) of E.O. 12866.
Accordingly, this action was not submitted to OIRA for review under
E.O. 12866.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of a final regulatory flexibility analysis (FRFA) for any
final rule where the agency was first required by law to publish a
proposed rule for public comment, unless the agency certifies that the
rule, if promulgated, will not have a significant economic impact on a
substantial number of small entities. As required by Executive Order
13272, ``Proper Consideration of Small Entities in Agency Rulemaking,''
67 FR 53461 (August 16, 2002), DOE published procedures and policies on
February 19, 2003, to ensure that the potential impacts of its rules on
small entities are properly considered during the DOE rulemaking
process. 68 FR 7990. DOE has made its procedures and policies available
on the Office of the General Counsel's website: www.energy.gov/gc/office-general-counsel.
DOE reviewed this final rule under the provisions of the Regulatory
Flexibility Act and the procedures and policies published on February
19,
[[Page 15534]]
2003. DOE certifies that this rule, if adopted, would not have
significant economic impact on a substantial number of small entities.
The factual basis of this certification is set forth below.
Under 42 U.S.C. 6293, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered products. EPCA requires that any test procedures prescribed or
amended under this section shall be reasonably designed to produce test
results which measure energy efficiency, energy use, or estimated
annual operating cost of a covered product during a representative
average use cycle (as determined by the Secretary) or period of use and
shall not be unduly burdensome to conduct. (42 U.S.C. 6293(b)(3))
EPCA also requires that, at least once every 7 years, DOE evaluate
test procedures for each type of covered product, including consumer
boilers, to determine whether amended test procedures would more
accurately or fully comply with the requirements for the test
procedures to not be unduly burdensome to conduct and be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs during a representative average use
cycle or period of use. (42 U.S.C. 6293(b)(1)(A)) DOE is publishing
this final rule in satisfaction of the 7-year review requirement
specified in EPCA. (42 U.S.C. 6293(b)(1)(A))
DOE did not receive written comments that specifically addressed
impacts on small businesses or that were provided in response to the
March 2022 NOPR.
The Small Business Administration (``SBA'') has set a size
threshold, which defines those entities classified as ``small
businesses'' for the purposes of the statute. DOE used the SBA's small
business size standards to determine whether any small entities would
be subject to the requirements of the rule. See 13 CFR part 121. The
products covered by this rule are classified under North American
Industry Classification System (``NAICS'') code 333414,\43\ ``Heating
Equipment (except Warm Air Furnaces) Manufacturing.'' In 13 CFR
121.201, the SBA sets a threshold of 500 employees or fewer for an
entity to be considered as a small business for this category. This
employment figure is enterprise-wide, encompassing employees at the
parent, subsidiary, and sister corporations.
---------------------------------------------------------------------------
\43\ The SBA size standards (effective October 1, 2022) are
listed by NAICS code and industry description and are available at:
www.sba.gov/document/support-table-size-standards (last accessed on
December 1, 2022).
---------------------------------------------------------------------------
Consistent with the March 2022 NOPR, DOE relied on the Compliance
Certification Database (``CCD''),\44\ the AHRI database,\45\ the
California Energy Commission's Modernized Appliance Efficiency Database
System (``MAEDbS''),\46\ the ENERGY STAR Product Finder database,\47\
and the prior consumer boiler energy conservation standards rulemaking
to create a list of companies that import or otherwise manufacture the
products covered by this final rule. DOE used the publicly available
information and subscription-based market research tools (e.g., reports
from Dun & Bradstreet \48\) to identify 27 original equipment
manufacturers (``OEMs'') affected by this final rule. Of the 27 OEMs,
DOE identified five domestic OEMs of consumer boilers that met the SBA
definition of a ``small business'' and are not foreign-owned and
operated.
---------------------------------------------------------------------------
\44\ U.S. Department of Energy Compliance Certification
Database, available at: www.regulations.doe.gov/certification-data/products.html.
\45\ The AHRI Database is available at: www.ahridirectory.org
(last accessed March 3, 2021).
\46\ California Energy Commission's MAEDbS is available at
cacertappliances.energy.ca.gov/Pages/ApplianceSearch.aspx (last
accessed September 22, 2021).
\47\ The ENERGY STAR Product Finder database is available at
energystar.gov/productfinder/ (last accessed September 22, 2021).
\48\ D&B Hoovers [verbar] Company Information [verbar] Industry
Information [verbar] Lists, app.dnbhoovers.com/ (last accessed
September 29, 2022).
---------------------------------------------------------------------------
In this final rule, DOE updates appendix N to remove the provisions
applicable only to consumer boilers and to rename the current appendix
as ``Uniform Test Method for Measuring the Energy Consumption of
Furnaces.'' Correspondingly, this final rule establishes a new test
procedure at 10 CFR part 430 subpart B, appendix EE, ``Uniform Test
Method for Measuring the Energy Consumption of Boilers'' (``appendix
EE''). In the new appendix EE, DOE includes all provisions currently
included in appendix N relevant to consumer boilers, with the following
modifications:
(1) Incorporate by reference the current revision to the applicable
industry standard, ANSI/ASHRAE 103-2017, ``Methods of Testing for
Annual Fuel Utilization Efficiency of Residential Central Furnaces and
Boilers.''
(2) Incorporate by reference the current revision of ASTM Standard
D2156-09 (Reapproved 2018), ``Standard Test Method for Smoke Density in
Flue Gases from Burning Distillate Fuels.''
(3) Incorporate by reference ANSI/ASHRAE 41.6-2014, ``Standard
Method for Humidity Measurement.''
(4) Update the definitions to reflect the changes in ANSI/ASHRAE
103-2017 as compared to ANSI/ASHRAE 103-1993.
(5) Provide corrections to erroneous calculations and add
clarifications to test conditions and setup requirements.
DOE is also removing the definition of outdoor furnace or boiler
from 10 CFR 430.2.
DOE has determined that the amendments adopted in this final rule
will not substantively impact the measured efficiency of consumer
boilers or require retesting or recertification solely as a result of
DOE's adoption of the amendments to the test procedures. As outlined in
Table II.1 of this final rule, the new appendix EE includes all
provisions currently included in appendix N relevant to consumer
boilers, with modifications to: harmonize with industry standard
updates; provide corrections to erroneous calculations; and add
clarifications to test conditions and setup requirements. Additionally,
the update to use more representative cycle timings and oversize
factors in the new appendix EE test procedure was demonstrated to have
minimal impact on AFUE ratings as a result of testing. See section
III.K of this final rule for additional details on test procedure
costs. DOE also determined that the amendments would not increase the
testing costs or burden associated with the DOE test procedure for
consumer boilers, as the cost to test consumer boilers under the
amended test procedure is $3,600, the same as the cost to test consumer
boilers under the existing test procedure.
Therefore, DOE concludes that the cost effects accruing from the
final rule would not have a ``significant economic impact on a
substantial number of small entities,'' and that the preparation of a
FRFA is not warranted.
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of consumer boilers must certify to DOE that their
products comply with any applicable energy conservation standards. To
certify compliance, manufacturers must first obtain test data for their
products according to the DOE test procedures, including any amendments
adopted for those test procedures. DOE has established regulations for
the certification and recordkeeping requirements for all covered
consumer products and commercial equipment, including consumer boilers.
(See
[[Page 15535]]
generally 10 CFR part 429.) The collection-of-information requirement
for the certification and recordkeeping is subject to review and
approval by OMB under the Paperwork Reduction Act (PRA). This
requirement has been approved by OMB under OMB control number 1910-
1400. Public reporting burden for the certification is estimated to
average 35 hours per response, including the time for reviewing
instructions, searching existing data sources, gathering and
maintaining the data needed, and completing and reviewing the
collection of information.
DOE is not amending the certification or reporting requirements for
consumer boilers in this final rule.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE establishes test procedure amendments that
it expects will be used to develop and implement future energy
conservation standards for consumer boilers. DOE has determined that
this rule falls into a class of actions that are categorically excluded
from review under the National Environmental Policy Act of 1969 (42
U.S.C. 4321 et seq.) and DOE's implementing regulations at 10 CFR part
1021. Specifically, DOE has determined that adopting test procedures
for measuring energy efficiency of consumer products and industrial
equipment is consistent with activities identified in 10 CFR part 1021,
appendix A to subpart D, A5 and A6. Accordingly, neither an
environmental assessment nor an environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 4,
1999), imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have federalism implications. The Executive order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE examined this final
rule and determined that it will not have a substantial direct effect
on the States, on the relationship between the national government and
the States, or on the distribution of power and responsibilities among
the various levels of government. EPCA governs and prescribes Federal
preemption of State regulations as to energy conservation for the
products that are the subject of this final rule. States can petition
DOE for exemption from such preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that executive agencies make every reasonable
effort to ensure that the regulation: (1) clearly specifies the
preemptive effect, if any; (2) clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the retroactive effect, if any; (5) adequately defines
key terms; and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to review regulations in light of applicable standards in
sections 3(a) and 3(b) to determine whether they are met or it is
unreasonable to meet one or more of them. DOE has completed the
required review and determined that, to the extent permitted by law,
this final rule meets the relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (``UMRA'')
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a regulatory action resulting in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector, of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820; also available
at energy.gov/gc/office-general-counsel. DOE examined this final rule
according to UMRA and its statement of policy and determined that the
rule contains neither an intergovernmental mandate, nor a mandate that
may result in the expenditure of $100 million or more in any year, so
these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This final rule will not have any impact on the autonomy or integrity
of the family as an institution. Accordingly, DOE has concluded that it
is not necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights,'' 53 FR 8859 (March 18, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
[[Page 15536]]
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). Pursuant
to OMB Memorandum M-19-15, Improving Implementation of the Information
Quality Act (April 24, 2019), DOE published updated guidelines which
are available at energy.gov/sites/prod/files/2019/12/f70/DOE%20Final%20Updated%20IQA%20Guidelines%20Dec%202019.pdf. DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any significant energy action. A
``significant energy action'' is defined as any action by an agency
that promulgated or is expected to lead to promulgation of a final
rule, and that: (1) is a significant regulatory action under Executive
Order 12866, or any successor order; and (2) is likely to have a
significant adverse effect on the supply, distribution, or use of
energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use if the regulation is implemented, and of
reasonable alternatives to the action and its expected benefits on
energy supply, distribution, and use.
This regulatory action is not a significant regulatory action under
Executive Order 12866. Moreover, it would not have a significant
adverse effect on the supply, distribution, or use of energy, nor has
it been designated as a significant energy action by the Administrator
of OIRA. Therefore, it is not a significant energy action, and,
accordingly, DOE has not prepared a Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788;
``FEAA'') Section 32 essentially provides in relevant part that, where
a proposed rule authorizes or requires use of commercial standards, the
notice of proposed rulemaking must inform the public of the use and
background of such standards. In addition, section 32(c) requires DOE
to consult with the Attorney General and the Chairman of the Federal
Trade Commission (``FTC'') concerning the impact of the commercial or
industry standards on competition.
The modifications to the test procedure for consumer boilers
adopted in this final rule incorporates testing methods contained in
certain sections of the following commercial standards: ASHRAE Standard
103-2017, ASTM D2156-09 (R2018), and ASHRAE Standard 41.6-2014. DOE has
evaluated these standards and is unable to conclude whether it fully
complies with the requirements of section 32(b) of the FEAA (i.e.,
whether it was developed in a manner that fully provides for public
participation, comment, and review.) DOE has consulted with both the
Attorney General and the Chairman of the FTC about the impact on
competition of using the methods contained in these standards and has
received no comments objecting to their use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that it has been determined that the rule is not a ``major rule''
as defined by 5 U.S.C. 804(2).
N. Description of Materials Incorporated by Reference
ASHRAE 103-2017 is an industry accepted test standard that provides
procedures for determining the annual fuel utilization efficiency of
consumer furnaces and boilers. Specifically, the test procedure
codified by this final rule references sections of ASHRAE 103-2017 for
definitions, classifications, requirements, instruments, methods of
testing, testing procedures, nomenclature, and calculations for
determining the AFUE of consumer boilers.
ASHRAE 41.6-2014 is an industry accepted test standard that
includes instructions for measuring the relative humidity of test
chamber air. Specifically, the test procedure codified by this final
rule references sections of ASHRAE 103-2017 that in turn reference
ASHRAE 41.6-2014 for air humidity measurement instructions.
These test standards are all readily available from ANSI
(webstore.ansi.org) or ASHRAE (www.ashrae.org).
ASTM D2156-09 (R2018) is an industry accepted test standard that
includes instructions for determining the amount of smoke produced by
an oil burner to ensure the burner is adjusted properly. Specifically,
the test procedure codified by this final rule references sections of
ASTM D2156-09 (R2018) for these instructions.
This test standard is readily available from ASTM International
(www.astm.org).
IEC 62301 is an industry-accepted test procedure for measuring
standby mode and off mode energy consumption. The test procedure
codified by this final rule references IEC 62301 for performing the
standby mode and off mode power measurements for consumer boilers. This
test standard is readily available from IEC (webstore.iec.ch).
The following standards included in the regulatory text were
previously approved for incorporation by reference for the locations in
which they appear in this final rule: ANSI/ASHRAE 103-1993, and ASTM
D2156-09 (Reapproved 2013).
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Intergovernmental relations, Reporting and recordkeeping requirements,
Small businesses.
10 CFR Part 430
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Small
businesses.
Signing Authority
This document of the Department of Energy was signed on February
21, 2023, by Francisco Alejandro Moreno,
[[Page 15537]]
Acting Assistant Secretary for Energy Efficiency and Renewable Energy.
That document with the original signature and date is maintained by
DOE. For administrative purposes only, and in compliance with
requirements of the Office of the Federal Register, the undersigned DOE
Federal Register Liaison Officer has been authorized to sign and submit
the document in electronic format for publication, as an official
document of the Department of Energy. This administrative process in no
way alters the legal effect of this document upon publication in the
Federal Register.
Signed in Washington, DC, on February 22, 2023.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
For the reasons stated in the preamble, DOE amends parts 429 and
430 of chapter II of title 10, Code of Federal Regulations as set forth
below:
PART 429--CERTIFICATION COMPLIANCE AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
Sec. 429.134 [Amended]
0
2. Section 429.134 is amended by:
0
a. In paragraph (h) introductory text, removing the words ``appendix
N'' and adding in their place the word ``appendix EE'';
0
b. In paragraph (h)(1)(i)(A), removing the words ``section 6 of
appendix N'' and adding in their place the words ``section 6 of
appendix EE''; and
0
c. In paragraph (h)(2)(i)(A), removing the words ``appendix N'' and
adding in their place the words ``appendix EE''.
PART 430--ENERGY CONSERVATION PROGRAM FOR CONSUMER PRODUCTS
0
3. The authority citation for part 430 continues to read as follows:
Authority: 42 U.S.C. 6291-6309; 28 U.S.C. 2461 note.
Sec. 430.2 [Amended]
0
4. Section 430.2 is amended by removing the definition of ``Outdoor
furnace or boiler''.
0
5. Section 430.3 is amended by:
0
a. In paragraph (g)(11), removing the words ``appendix F'' and adding
in their place the words ``appendices F and EE'';
0
b. In paragraph (g)(17), removing the words ``appendix O'' and adding
in their place the words ``Sec. 430.23 and appendices O and EE'';
0
c. Revising paragraph (j) introductory text;
0
d. In paragraph (j)(3), removing the words ``appendix O'' and adding in
their place the words ``appendices O and EE''; and
0
e. In paragraph (p)(7), removing the text ``CC, and FF'' and adding in
their place ``CC, EE, and FF''.
The revision reads as follows:
Sec. 430.3 Materials incorporated by reference.
* * * * *
(j) ATSM. ASTM International, 100 Barr Harbor Drive, Post Office
Box C700, West Conshohocken, PA 19428-2959, (877) 909-2786,
www.astm.org.
* * * * *
0
6. Section 430.23 is amended by revising paragraph (n) to read as
follows:
Sec. 430.23 Test Procedures for the measurement of energy and water
consumption.
* * * * *
(n) Furnaces. (1) The estimated annual operating cost for furnaces
is the sum of:
(i) The product of the average annual fuel energy consumption, in
Btu's per year for gas or oil furnaces or in kilowatt-hours per year
for electric furnaces, determined according to section 10.2.2 or 10.3
of appendix N of this subpart, respectively, (for furnaces, excluding
low pressure steam or hot water boilers and electric boilers) or
section 10.2.2 or 10.3 of appendix EE of this subpart, respectively
(for low pressure steam or hot water boilers and electric boilers), and
the representative average unit cost in dollars per Btu for gas or oil,
or dollars per kilowatt-hour for electric, as appropriate, as provided
pursuant to section 323(b)(2) of the Act; plus
(ii) The product of the average annual auxiliary electric energy
consumption in kilowatt-hours per year determined according to section
10.2.3 of appendix N of this subpart (for furnaces, excluding low
pressure steam or hot water boilers and electric boilers) or section
10.2.3 of appendix EE of this subpart (for low pressure steam or hot
water boilers and electric boilers) of this subpart, and the
representative average unit cost in dollars per kilowatt-hour as
provided pursuant to section 323(b)(2) of the Act.
(iii) Round the resulting sum to the nearest dollar per year.
(2) The annual fuel utilization efficiency (AFUE) for furnaces,
expressed in percent, is the ratio of the annual fuel output of useful
energy delivered to the heated space to the annual fuel energy input to
the furnace.
(i) For gas and oil furnaces, determine AFUE according to section
10.1 of appendix N (for furnaces, excluding low pressure steam or hot
water boilers and electric boilers) or section 10.1 of appendix EE (for
low pressure steam or hot water boilers and electric boilers) of this
subpart, as applicable.
(ii) For electric furnaces, excluding electric boilers, determine
AFUE in accordance with section 11.1 of ANSI/ASHRAE 103-1993
(incorporated by reference, see Sec. 430.3); for electric boilers,
determine AFUE in accordance with section 11.1 of ANSI/ASHRAE 103-2017
(incorporated by reference, see Sec. 430.3).
(iii) Round the AFUE to one-tenth of a percentage point.
(3) The estimated regional annual operating cost for furnaces is
calculated as follows:
(i) When using appendix N of this subpart for furnaces excluding
low pressure steam or hot water boilers and electric boilers (see the
note at the beginning of appendix N of this subpart),
(A) For gas or oil-fueled furnaces,
(EFR x CBTU) + (EAER x CKWH)
Where:
EFR = the regional annual fuel energy consumption in Btu
per year, determined according to section 10.7.1 of appendix N of
this subpart;
CBTU = the representative average unit cost in dollars
per Btu of gas or oil, as provided pursuant to section 323(b)(2) of
the Act;
EAER = the regional annual auxiliary electrical energy
consumption in kilowatt-hours per year, determined according to
section 10.7.2 of appendix N of this subpart; and
CKWH = the representative average unit cost in dollars
per kilowatt-hour of electricity, as provided pursuant to section
323(b)(2) of the Act.
(B) For electric furnaces,
(EER x CKWH)
Where:
EER = the regional annual fuel energy consumption in
kilowatt-hours per year, determined according to section 10.7.3 of
appendix N of this subpart; and
CKWH is as defined in paragraph (n)(3)(i)(A) of this
section.
(ii) When using appendix EE of this subpart for low pressure steam
or hot water boilers and electric boilers (see the note at the
beginning of appendix EE of this subpart),
(A) For gas or oil-fueled boilers,
(EER x CBTU) + (EAER x CKWH)
[[Page 15538]]
Where:
EFR = the regional annual fuel energy consumption in Btu
per year, determined according to section 10.5.1 of appendix EE of
this subpart;
CBTU and CKWH are as defined in paragraph
(n)(3)(i)(A) of this section; and
EAER = the regional annual auxiliary electrical energy
consumption in kilowatt-hours per year, determined according to
section 10.5.2 of appendix EE of this subpart.
(B) For electric boilers,
(EER x CKWH)
Where:
EER = the regional annual fuel energy consumption in
kilowatt-hours per year, determined according to section 10.5.3 of
appendix EE of this subpart; and
CKWH is as defined in paragraph (n)(3)(i)(A) of this
section.
(iii) Round the estimated regional annual operating cost to the
nearest dollar per year.
(4) The energy factor for furnaces, expressed in percent, is the
ratio of annual fuel output of useful energy delivered to the heated
space to the total annual energy input to the furnace determined
according to either section 10.6 of appendix N of this subpart (for
furnaces, excluding low pressure steam or hot water boilers and
electric boilers) or section 10.4 of appendix EE of this subpart (for
low pressure steam or hot water boilers and electric boilers), as
applicable.
(5) The average standby mode and off mode electrical power
consumption for furnaces shall be determined according to section 8.10
of appendix N of this subpart (for furnaces, excluding low pressure
steam or hot water boilers and electric boilers) or section 8.9 of
appendix EE of this subpart (for low pressure steam or hot water
boilers and electric boilers), as applicable. Round the average standby
mode and off mode electrical power consumption to the nearest tenth of
a watt.
(6) Other useful measures of energy consumption for furnaces shall
be those measures of energy consumption which the Secretary determines
are likely to assist consumers in making purchasing decisions and which
are derived from the application of appendix N of this subpart (for
furnaces, excluding low pressure steam or hot water boilers and
electric boilers) or appendix EE of this subpart (for low pressure
steam or hot water boilers and electric boilers).
* * * * *
0
7. Appendix N to subpart B of part 430 is revised to read as follows:
Appendix N to Subpart B of Part 430--Uniform Test Method for Measuring
the Energy Consumption of Consumer Furnaces Other Than Boilers
0. Incorporation by Reference
DOE incorporated by reference in Sec. 430.3, the entire standards
for ASTM D2156R13 and IEC 62301. DOE also incorporated selected
provisions of ASHRAE 103-1993.
1. Scope. The scope of this appendix is as specified in section 2
of ASHRAE 103-1993 as it pertains to furnaces other than low pressure
steam or hot water boilers or to electric boilers. Low pressure steam
or hot water boilers and electric boilers are addressed in appendix EE
of this subpart.
2. Definitions. Definitions include those specified in section 3 of
ASHRAE 103-1993 and the following additional and modified definitions.
Active mode means the condition in which the furnace is connected
to the power source, and at least one of the burner, electric
resistance elements, or any electrical auxiliaries such as blowers, are
activated.
Control means a device used to regulate the operation of a piece of
equipment and the supply of fuel, electricity, air, or water.
Draft inducer means a fan incorporated in the furnace that either
draws or forces air into the combustion chamber.
Gas valve means an automatic or semi-automatic device consisting
essentially of a valve and operator that controls the gas supply to the
burner(s) during normal operation of an appliance. The operator may be
actuated by application of gas pressure on a flexible diaphragm, by
electrical means, by mechanical means or by other means.
Installation and operation (I&O) manual means instructions for
installing, commissioning, and operating the furnace, which are
supplied with the product when shipped by the manufacturer.
Isolated combustion system means a system where a unit is installed
within the structure, but isolated from the heated space. A portion of
the jacket heat from the unit is lost, and air for ventilation,
combustion and draft control comes from outside the heated space.
Multi-position furnace means a furnace that can be installed in
more than one airflow configuration (i.e., upflow or horizontal;
downflow or horizontal; upflow or downflow; and upflow, or downflow, or
horizontal).
Off mode means a mode in which the furnace is connected to a mains
power source and is not providing any active mode or standby mode
function, and where the mode may persist for an indefinite time. The
existence of an off switch in off position (a disconnected circuit) is
included within the classification of off mode.
Off switch means the switch on the furnace that, when activated,
results in a measurable change in energy consumption between the
standby and off modes.
Oil control valve means an automatically or manually operated
device consisting of an oil valve for controlling the fuel supply to a
burner to regulate burner input.
Standby mode means any mode in which the furnace is connected to a
mains power source and offers one or more of the following space
heating functions that may persist:
(a) Activation of other modes (including activation or deactivation
of active mode) by remote switch (including thermostat or remote
control), internal or external sensors, and/or timer; and
(b) Continuous functions, including information or status displays
or sensor-based functions.
Thermal stack damper means a type of stack damper that relies
exclusively upon the changes in temperature in the stack gases to open
or close the damper.
3. Classifications. Classifications are as specified in section 4
of ASHRAE 103-1993 for furnaces.
4. Requirements. Requirements are as specified in section 5 of
ASHRAE 103-1993 for furnaces.
5. Instruments. Instruments must be as specified in section 6 of
ASHRAE 103-1993.
6. Apparatus. The apparatus used in conjunction with the furnace
during the testing must be as specified in section 7 of ASHRAE 103-1993
(except for the excluded sub-sections as enumerated at Sec.
430.3(g)(15)); and as specified in sections 6.1 through 6.5 of this
appendix.
6.1 General.
(a) Install the furnace in the test room in accordance with the I&O
manual, as defined in section 2.6 of this appendix, except that if
provisions within this appendix are specified, then the provisions
herein drafted and prescribed by DOE govern. If the I&O manual and any
additional provisions of this appendix are not sufficient for testing a
furnace, the manufacturer must request a waiver from the test procedure
pursuant to Sec. 430.27.
(b) If the I&O manual indicates the unit should not be installed
with a return duct, then the return (inlet) duct specified in section
7.2.1 of ASHRAE 103-1993 is not required.
[[Page 15539]]
(c) Test multi-position furnaces in the least efficient
configuration. Testing of multi-position furnaces in other
configurations is permitted if energy use or efficiency is represented
pursuant to the requirements in 10 CFR part 429.
(d) The apparatuses described in section 6 of this appendix are
used in conjunction with the furnace during testing. Each piece of
apparatus shall conform to material and construction specifications
listed in this appendix and in ASHRAE 103-1993, and the reference
standards cited in this appendix and in ASHRAE 103-1993.
(e) Test rooms containing equipment must have suitable facilities
for providing the utilities (including but not limited to environmental
controls, applicable measurement equipment, and any other technology or
tools) necessary for performance of the test and must be able to
maintain conditions within the limits specified in section 6 of this
appendix.
6.2 Forced-air central furnaces (direct vent and direct exhaust).
(a) Units not equipped with a draft hood or draft diverter must be
provided with the minimum-length vent configuration recommended in the
I&O manual or a 5-ft flue pipe if there is no recommendation provided
in the I&O manual (see Figure 4 of ASHRAE 103-1993). For a direct
exhaust system, insulate the minimum-length vent configuration or the
5-ft flue pipe with insulation having an R-value not less than 7 and an
outer layer of aluminum foil. For a direct vent system, see section 7.5
of ASHRAE 103-1993 for insulation requirements.
(b) For units with power burners, cover the flue collection box
with insulation having an R-value of not less than 7 and an outer layer
of aluminum foil before the cool-down and heat-up tests described in
sections 9.5 and 9.6 of ASHRAE 103-1993, respectively. However, do not
apply the insulation for the jacket loss test (if conducted) described
in section 8.6 of ASHRAE 103-1993 or the steady-state test described in
section 9.1 of ASHRAE 103-1993.
(c) For power-vented units, insulate the shroud surrounding the
blower impeller with insulation having an R-value of not less than 7
and an outer layer of aluminum foil before the cool-down and heat-up
tests described in sections 9.5 and 9.6, respectively, of ASHRAE 103-
1993. However, do not apply the insulation for the jacket loss test (if
conducted) described in section 8.6 of ASHRAE 103-1993 or the steady-
state test described in section 9.1 of ASHRAE 103-1993. Do not insulate
the blower motor or block the airflow openings that facilitate the
cooling of the combustion blower motor or bearings.
6.3 Downflow furnaces. Install an internal section of vent pipe the
same size as the flue collar for connecting the flue collar to the top
of the unit, if not supplied by the manufacturer. However, do not
insulate the internal vent pipe during the jacket loss test (if
conducted) described in section 8.6 of ASHRAE 103-1993 or the steady-
state test described in section 9.1 of ASHRAE 103-1993. Do not insulate
the internal vent pipe before the cool-down and heat-up tests described
in sections 9.5 and 9.6, respectively, of ASHRAE 103-1993. If the vent
pipe is surrounded by a metal jacket, do not insulate the metal jacket.
Install a 5-ft test stack of the same cross-sectional area or perimeter
as the vent pipe above the top of the furnace. Tape or seal around the
junction connecting the vent pipe and the 5-ft test stack. Insulate the
5-ft test stack with insulation having an R-value not less than 7 and
an outer layer of aluminum foil. (See Figure 3-E of ASHRAE 103-1993.)
6.4 Units with draft hoods or draft diverters. Install the stack
damper in accordance with the I&O manual. Install 5 feet of stack above
the damper.
(a) For units with an integral draft diverter, cover the 5-ft stack
with insulation having an R-value of not less than 7 and an outer layer
of aluminum foil.
(b) For units with draft hoods, insulate the flue pipe between the
outlet of the furnace and the draft hood with insulation having an R-
value of not less than 7 and an outer layer of aluminum foil.
(c) For units with integral draft diverters that are mounted in an
exposed position (not inside the overall unit cabinet), cover the
diverter boxes (excluding any openings through which draft relief air
flows) before the beginning of any test (including jacket loss test)
with insulation having an R-value of not less than 7 and an outer layer
of aluminum foil.
(d) For units equipped with integral draft diverters that are
enclosed within the overall unit cabinet, insulate the draft diverter
box with insulation as described in section 6.4.c before the cool-down
and heat-up tests described in sections 9.5 and 9.6, respectively, of
ASHRAE 103-1993. However, do not apply the insulation for the jacket
loss test (if conducted) described in section 8.6 of ASHRAE 103-1993 or
the steady-state test described in section 9.1 of ASHRAE 103-1993.
6.5 Condensate collection. Attach condensate drain lines to the
unit as specified in the I&O manual. Maintain a continuous downward
slope of drain lines from the unit. Additional precautions (such as
eliminating any line configuration or position that would otherwise
restrict or block the flow of condensate or checking to ensure a proper
connection with condensate drain spout that allows for unobstructed
flow) must be taken to facilitate uninterrupted flow of condensate
during the test. Collection containers must be glass or polished
stainless steel to facilitate removal of interior deposits. The
collection container must have a vent opening to the atmosphere.
7. Testing conditions. The testing conditions must be as specified
in section 8 of ASHRAE 103-1993 (except for the excluded sub-sections
as enumerated at Sec. 430.3(g)(15)); and as specified in sections 7.1
to 7.9 of this appendix, respectively.
7.1 Fuel supply, gas. In conducting the tests specified herein,
gases with characteristics as shown in Table 1 of ASHRAE 103-1993 shall
be used. Maintain the gas supply, ahead of all controls for a furnace,
at a test pressure between the normal and increased values shown in
Table 1 of ASHRAE 103-1993. Maintain the regulator outlet pressure at a
level approximating that recommended in the I&O manual, as defined in
section 2.6 of this appendix, or, in the absence of such
recommendation, to the nominal regulator settings used when the product
is shipped by the manufacturer. Use a gas having a specific gravity as
shown in Table 1 of ASHRAE 103-1993 and with a higher heating value
within 5% of the higher heating value shown in Table 1 of
ASHRAE 103-1993. Determine the actual higher heating value in Btu per
standard cubic foot for the gas to be used in the test within an error
no greater than 1%.
7.2 Gas burner. Adjust the burners of gas-fired furnaces to their
maximum Btu input ratings at the normal test pressure specified by
section 7.1 of this appendix. Correct the burner input rate to reflect
gas characteristics at a temperature of 60 [deg]F and atmospheric
pressure of 30 in of Hg and adjust down to within 2 percent
of the hourly Btu nameplate input rating specified by the manufacturer
as measured during the steady-state performance test in section 8 of
this appendix. Set the primary air shutters in accordance with the I&O
manual to give a good flame at this condition. If, however, the setting
results in the deposit of carbon on the burners during any test
specified herein, the tester shall adjust the shutters and burners
until no more carbon is
[[Page 15540]]
deposited and shall perform the tests again with the new settings (see
Figure 9 of ASHRAE 103-1993). After the steady-state performance test
has been started, do not make additional adjustments to the burners
during the required series of performance tests specified in section 9
of ASHRAE 103-1993. If a vent-limiting means is provided on a gas
pressure regulator, keep it in place during all tests.
7.3 Modulating gas burner adjustment at reduced input rate. For
gas-fired furnaces equipped with modulating-type controls, adjust the
controls to operate the unit at the nameplate minimum input rate. If
the modulating control is of a non-automatic type, adjust the control
to the setting recommended in the I&O manual. In the absence of such
recommendation, the midpoint setting of the non-automatic control shall
be used as the setting for determining the reduced fuel input rate.
Start the furnace by turning the safety control valve to the ``ON''
position.
7.4 Oil burner. Adjust the burners of oil-fired furnaces to give a
CO2 reading specified in the I&O manual and an hourly Btu
input during the steady-state performance test described in section 8
of this appendix. Ensure the hourly BTU input is within 2%
of the normal hourly Btu input rating as specified in the I&O manual.
Smoke in the flue may not exceed a No. 1 smoke during the steady-state
performance test as measured by the procedure in ASTM D2156R13).
Maintain the average draft over the fire and in the flue during the
steady-state performance test at the value specified in the I&O manual.
Do not allow draft fluctuations exceeding 0.005 in. water. Do not make
additional adjustments to the burner during the required series of
performance tests. The instruments and measuring apparatus for this
test are described in section 6 of this appendix and shown in Figure 8
of ASHRAE 103-1993.
7.5 Temperature Rise Targets. Adjust air throughputs to achieve a
temperature rise that is the higher of a and b, below, unless c
applies. A tolerance of 2 [deg]F is permitted.
(a) 15 [deg]F less than the nameplate maximum temperature rise or
(b) 15 [deg]F higher than the minimum temperature rise specified in
the I&O manual.
(c) A furnace with a non-adjustable air temperature rise range and
an automatically controlled airflow that does not permit a temperature
rise range of 30 [deg]F or more must be tested at the midpoint of the
rise range.
7.6 Temperature Rise Adjustments. Establish the temperature rise
specified in section 7.5 of this appendix by adjusting the circulating
airflow. This adjustment must be accomplished by symmetrically
restricting the outlet air duct and varying blower speed selection to
obtain the desired temperature rise and minimum external static
pressure, as specified in Table 4 of ASHRAE 103-1993. If the required
temperature rise cannot be obtained at the minimum specified external
static pressure by adjusting blower speed selection and duct outlet
restriction, then the following applies.
(a) If the resultant temperature rise is less than the required
temperature rise, vary the blower speed by gradually adjusting the
blower voltage so as to maintain the minimum external static pressure
listed in Table 4 of ASHRAE 103-1993. The airflow restrictions shall
then remain unchanged. If static pressure must be varied to prevent
unstable blower operation, then increase the static pressure until
blower operation is stabilized, except that the static pressure must
not exceed the maximum external static pressure as specified by the
manufacturer in the I&O manual.
(b) If the resultant temperature rise is greater than the required
temperature rise, then the unit can be tested at a higher temperature
rise value, but one not greater than nameplate maximum temperature
rise. In order not to exceed the maximum temperature rise, the speed of
a direct-driven blower may be increased by increasing the circulating
air blower motor voltage.
7.7 Measurement of jacket surface temperature. Divide the jacket of
the furnace into 6-inch squares when practical, and otherwise into 36-
square-inch regions comprising 4-inch by 9-inch or 3-inch by 12-inch
sections, and determine the surface temperature at the center of each
square or section with a surface thermocouple. Record the surface
temperature of the 36-square-inch areas in groups where the temperature
differential of the 36-square-inch areas is less than 10 [deg]F for
temperature up to 100 [deg]F above room temperature, and less than 20
[deg]F for temperatures more than 100 [deg]F above room temperature.
For forced-air central furnaces, the circulating air blower compartment
is considered as part of the duct system, and no surface temperature
measurement of the blower compartment needs to be recorded for the
purpose of this test. For downflow furnaces, measure all cabinet
surface temperatures of the heat exchanger and combustion section,
including the bottom around the outlet duct and the burner door, using
the 36-square-inch thermocouple grid. The cabinet surface temperatures
around the blower section do not need to be measured (See Figure 3-E of
ASHRAE 103-1993).
7.8 Installation of vent system. Keep the vent or air intake system
supplied by the manufacturer in place during all tests. Test units
intended for installation with a variety of vent pipe lengths with the
minimum vent length as specified in the I&O manual, or a 5-ft. flue
pipe if there are no recommendations in the I&O manual. Do not connect
a furnace employing a direct vent system to a chimney or induced-draft
source. Vent combustion products solely by using the venting
incorporated in the furnace and the vent or air intake system supplied
by the manufacturer. For units that are not designed to significantly
preheat the incoming air, see section 7.4 of this appendix and Figure
4a or 4b of ASHRAE 103-1993. For units that do significantly preheat
the incoming air, see Figure 4c or 4d of ASHRAE 103-1993.
7.9 Additional optional method of testing for determining DP and DF
for furnaces. On units whose design is such that there is no measurable
airflow through the combustion chamber and heat exchanger when the
burner(s) is (are) off as determined by the optional test procedure in
section 7.9.1 of this appendix, DF and DP may be
set equal to 0.05.
7.9.1 Optional test method for indicating the absence of flow
through the heat exchanger. Manufacturers may use the following test
protocol to determine whether air flows through the combustion chamber
and heat exchanger when the burner(s) is (are) off. The minimum default
draft factor may be used only for units determined pursuant to this
protocol to have no airflow through the combustion chamber and heat
exchanger.
7.9.1.1 Test apparatus. Use a smoke stick that produces smoke that
is easily visible and has a density less than or approximately equal to
air. Use a smoke stick that produces smoke that is non-toxic to the
test personnel and produces gas that is unreactive with the environment
in the test chamber.
7.9.1.2 Test conditions. Minimize all air currents and drafts in
the test chamber, including turning off ventilation if the test chamber
is mechanically ventilated. Wait at least two minutes following the
termination of the furnace on-cycle before beginning the optional test
method for indicating the absence of flow through the heat exchanger.
7.9.1.3 Location of the test apparatus. After all air currents and
drafts in the test chamber have been eliminated or minimized, position
the
[[Page 15541]]
smoke stick based on the following equipment configuration:
(a) For horizontal combustion air intakes, approximately 4 inches
from the vertical plane at the termination of the intake vent and 4
inches below the bottom edge of the combustion air intake; or
(b) for vertical combustion air intakes, approximately 4 inches
horizontal from vent perimeter at the termination of the intake vent
and 4 inches down (parallel to the vertical axis of the vent).
7.9.1.4 Duration of test. Establish the presence of smoke from the
smoke stick and then monitor the direction of the smoke flow for no
less than 30 seconds.
7.9.1.5 Test results. During visual assessment, determine whether
there is any draw of smoke into the combustion air intake vent.
(a) If absolutely no smoke is drawn into the combustion air intake,
the furnace meets the requirements to allow use of the minimum default
draft factor pursuant to section 7.9 of this appendix.
(b) If there is any smoke drawn into the intake, proceed with the
methods of testing as prescribed in section 8.8 of ASHRAE 103-1993.
8. Test procedure. Conduct testing and measurements as specified in
section 9 of ASHRAE 103-1993 (except for the excluded sub-sections as
enumerated at Sec. 430.3(g)(15)); and as specified in sections 8.1
through 8.10 of this appendix. Section 8.4 of this appendix may be used
in lieu of section 9.2 of ASHRAE 103-1993.
8.1 Fuel input. For gas units, measure and record the steady-state
gas input rate in Btu/hr, including pilot gas, corrected to standard
conditions of 60 [deg]F and 30 in. Hg. Use measured values of gas
temperature and pressure at the meter and barometric pressure to
correct the metered gas flow rate to the above standard conditions. For
oil units, measure and record the steady-state fuel input rate.
8.2 Electrical input. During the steady-state test, perform a
single measurement of all of the electrical power involved in burner
operation (PE), including energizing the ignition system, controls, gas
valve or oil control valve, and draft inducer, if applicable.
During the steady-state test, perform a single measurement of the
electrical power to the circulating air blower (BE).
8.3 Input to interrupted ignition device. For burners equipped with
an interrupted ignition device, record the nameplate electric power
used by the ignition device, PEIG, or record that
PEIG = 0.4 kW if no nameplate power input is provided.
Record the nameplate ignition device on-time interval, tIG,
or, if the nameplate does not provide the ignition device on-time
interval, measure the on-time interval with a stopwatch at the
beginning of the test, starting when the burner is turned on. Set
tIG = 0 and PEIG = 0 if the device on-time
interval is less than or equal to 5 seconds after the burner is on.
8.4 Optional test procedures for condensing furnaces, measurement
of condensate during the establishment of steady-state conditions. For
units with step-modulating or two-stage controls, conduct the test at
both the maximum and reduced inputs. In lieu of collecting the
condensate immediately after the steady state conditions have been
reached as required by section 9.2 of ASHRAE 103-1993, condensate may
be collected during the establishment of steady state conditions as
defined by section 9.1.2.1 of ASHRAE 103-1993. Perform condensate
collection for at least 30 minutes. Measure condensate mass immediately
at the end of the collection period to prevent evaporation loss from
the sample. Record fuel input for the 30-minute condensate collection
test period. Observe and record fuel higher heating value (HHV),
temperature, and pressures necessary for determining fuel energy input
(Qc,ss). Measure the fuel quantity and HHV with errors no greater than
1%. The humidity for the room air shall at no time exceed 80%.
Determine the mass of condensate for the establishment of steady state
conditions (Mc,ss) in pounds by subtracting the tare container weight
from the total container and condensate weight measured at the end of
the 30-minute condensate collection test period.
8.5 Cool-down test for gas- and oil-fueled gravity and forced-air
central furnaces without stack dampers. Turn off the main burner after
completing steady-state testing, and measure the flue gas temperature
by means of the thermocouple grid described in section 7.6 of ASHRAE
103-1993 at 1.5 minutes (TF,OFF(t3)) and 9
minutes (TF,OFF(t4)) after shutting off the
burner. When taking these temperature readings, the integral draft
diverter must remain blocked and insulated, and the stack restriction
must remain in place. On atmospheric systems with an integral draft
diverter or draft hood and equipped with either an electromechanical
inlet damper or an electromechanical flue damper that closes within 10
seconds after the burner shuts off to restrict the flow through the
heat exchanger in the off-cycle, bypass or adjust the control for the
electromechanical damper so that the damper remains open during the
cool-down test.
For furnaces that employ post-purge, measure the length of the
post-purge period with a stopwatch. Record the time from burner ``OFF''
to combustion blower ``OFF'' (electrically de-energized) as
tP. If the measured tP is less than or equal to
30 seconds, set tP at 0 and conduct the cool-down test as if
there is no post-purge. If tP is prescribed by the I&O
manual or measured to be greater than 180 seconds, stop the combustion
blower at 180 seconds and use that value for tP. Measure the
flue gas temperature by means of the thermocouple grid described in
section 7.6 of ASHRAE 103-1993 at the end of the post-purge period,
tP(TF,OFF (tP)), and at the time (1.5
+ tP) minutes (TF,OFF(t3)) and (9.0 +
tP) minutes (TF,OFF(t4)) after the
main burner shuts off.
8.6 Cool-down test for gas- and oil-fueled gravity and forced-air
central furnaces without stack dampers and with adjustable fan control.
For a furnace with adjustable fan control, measure the time delay
between burner shutdown and blower shutdown, t\+\. This time delay,
t\+\, will be 3.0 minutes for non-condensing furnaces or 1.5 minutes
for condensing furnaces or until the supply air temperature drops to a
value of 40 [deg]F above the inlet air temperature, whichever results
in the longest fan on-time. For a furnace without adjustable fan
control or with the type of adjustable fan control whose range of
adjustment does not allow for the time delay, t\+\, specified above,
bypass the fan control and manually control the fan to allow for the
appropriate delay time as specified in section 9.5.1.2 of ASHRAE 103-
1993. For a furnace that employs a single motor to drive both the power
burner and the indoor air circulating blower, the power burner and
indoor air circulating blower must be stopped at the same time.
8.7 [Reserved]
8.8 Calculation options. The rate of the flue gas mass flow through
the furnace and the factors DP, DF, and
DS are calculated by the equations in sections 11.6.1,
11.6.2, 11.6.3, 11.6.4, 11.7.1, and 11.7.2 of ASHRAE 103-1993. On units
whose design is such that there is no measurable airflow through the
combustion chamber and heat exchanger when the burner(s) is (are) off
(as determined by the optional test procedure in section 7.9 of this
appendix), DF and DP may be set equal to 0.05.
8.9 Optional test procedures for condensing furnaces that have no
off-period flue losses. For units that have applied the test method in
section 7.9 of this appendix to determine that no
[[Page 15542]]
measurable airflow exists through the combustion chamber and heat
exchanger during the burner off-period and having post-purge periods of
less than 5 seconds, the cool-down and heat-up tests specified in
sections 9.5 and 9.6 of ASHRAE 103-1993 may be omitted. In lieu of
conducting the cool-down and heat-up tests, the tester may use the
losses determined during the steady-state test described in section 9.1
of ASHRAE 103-1993 when calculating heating seasonal efficiency,
EffyHS.
8.10 Measurement of electrical standby and off mode power.
8.10.1 Standby power measurement. With all electrical auxiliaries
of the furnace not activated, measure the standby power
(PW,SB) in accordance with the procedures in IEC 62301,
except that section 8.5, Room Ambient Temperature, of ASHRAE 103-1993
and the voltage provision of section 8.2.1.4, Electrical Supply, of
ASHRAE 103-1993 shall apply in lieu of the corresponding provisions of
IEC 62301 at section 4.2, Test room, and the voltage specification of
section 4.3, Power supply. Frequency shall be 60Hz. Clarifying further,
IEC 62301 section 4.4, Power measurement instruments, and Section 5,
Measurements, apply in lieu of ASHRAE 103-1993 section 6.10, Energy
Flow Rate. Measure the wattage so that all possible standby mode
wattage for the entire appliance is recorded, not just the standby mode
wattage of a single auxiliary. Round the recorded standby power
(PW,SB) to the second decimal place, except for loads
greater than or equal to 10W, which must be recorded to at least three
significant figures.
8.10.2 Off mode power measurement. If the unit is equipped with an
off switch or there is an expected difference between off mode power
and standby mode power, measure off mode power
(PW,OFF) in accordance with the standby power
procedures in IEC 62301, except that section 8.5, Room Ambient
Temperature, of ASHRAE 103-1993 and the voltage provision of section
8.2.1.4, Electrical Supply, of ASHRAE 103-1993 shall apply in lieu of
the corresponding provisions of IEC 62301 at section 4.2, Test room,
and the voltage specification of section 4.3, Power supply. Frequency
shall be 60Hz. Clarifying further, IEC 62301 section 4.4, Power
measurement instruments, and section 5, Measurements, apply for this
measurement in lieu of ASHRAE 103-1993 section 6.10, Energy Flow Rate.
Measure the wattage so that all possible off mode wattage for the
entire appliance is recorded, not just the off mode wattage of a single
auxiliary. If there is no expected difference in off mode power and
standby mode power, let PW,OFF = PW,SB, in which
case no separate measurement of off mode power is necessary. Round the
recorded off mode power (PW,OFF) to the second decimal
place, except for loads greater than or equal to 10W, in which case
round the recorded value to at least three significant figures.
9. Nomenclature. Nomenclature includes the nomenclature specified
in section 10 of ASHRAE 103-1993 and the following additional
variables:
Effmotor = Efficiency of power burner motor
PEIG = Electrical power to the interrupted ignition device,
kW
RT,a = RT,F if flue gas is measured
= RT,S if stack gas is measured
RT,F = Ratio of combustion air mass flow rate to
stoichiometric air mass flow rate
RT,S = Ratio of the sum of combustion air and relief air
mass flow rate to stoichiometric air mass flow rate
tIG = Electrical interrupted ignition device on-time, min.
Ta,SS,X = TF,SS,X if flue gas temperature is
measured, [deg]F
= TS,SS,X if stack gas temperature is measured, [deg]F
yIG = Ratio of electrical interrupted ignition device on-
time to average burner on-time
yP = Ratio of power burner combustion blower on-time to
average burner on-time
ESO = Average annual electric standby mode and off mode
energy consumption, in kilowatt-hours
PW,OFF = Furnace off mode power, in watts
PW,SB = Furnace standby mode power, in watts
10. Calculation of derived results from test measurements. Perform
calculations as specified in section 11 of ASHRAE 103-1993 (except for
the excluded sub-sections as enumerated at Sec. 430.3(g)(15)); and as
specified in sections 10.1 through 10.11 and Figure 1 of this appendix.
10.1 Annual fuel utilization efficiency. The annual fuel
utilization efficiency (AFUE) is as defined in sections 11.2.12 (non-
condensing systems), 11.3.12 (condensing systems), 11.4.12 (non-
condensing modulating systems) and 11.5.12 (condensing modulating
systems) of ASHRAE 103-1993, except for the definition for the term
EffyHS in the defining equation for AFUE. EffyHS
is defined as:
EffyHS = heating seasonal efficiency as defined in sections
11.2.11 (non-condensing systems), 11.3.11 (condensing systems), 11.4.11
(non-condensing modulating systems) and 11.5.11 (condensing modulating
systems) of ASHRAE 103-1993, except that for condensing modulating
systems sections 11.5.11.1 and 11.5.11.2 are replaced by sections 10.2
and 10.3 of this appendix. EffyHS is based on the
assumptions that all weatherized warm air furnaces are located outdoors
and that non-weatherized warm air furnaces are installed as isolated
combustion systems.
10.2 Part-load efficiency at reduced fuel input rate. If the option
in section 8.9 of this appendix is not employed, calculate the part-
load efficiency at the reduced fuel input rate, EffyU,R, for
condensing furnaces equipped with either step-modulating or two-stage
controls, expressed as a percent and defined as:
[[Page 15543]]
[GRAPHIC] [TIFF OMITTED] TR13MR23.001
Where:
LL,A = value as defined in section 11.2.7 of ASHRAE 103-
1993,
LG = value as defined in section 11.3.11.1 of ASHRAE 103-
1993, at reduced input rate,
LC = value as defined in section 11.3.11.2 of ASHRAE 103-
1993 at reduced input rate,
LJ = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993 at maximum input rate,
tON = value as defined in section 11.4.9.11 of ASHRAE
103-1993,
QP = pilot fuel input rate determined in accordance with
section 9.2 of ASHRAE 103-1993 in Btu/h,
QIN = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993,
tOFF = value as defined in section 11.4.9.12 of ASHRAE
103-1993 at reduced input rate,
LS,ON = value as defined in section 11.4.10.5 of ASHRAE
103-1993 at reduced input rate,
LS,OFF = value as defined in section 11.4.10.6 of ASHRAE
103-1993 at reduced input rate,
LI,ON = value as defined in section 11.4.10.7 of ASHRAE
103-1993 at reduced input rate,
LI,OFF = value as defined in section 11.4.10.8 of ASHRAE
103-1993 at reduced input rate,
CJ = jacket loss factor and equal to:
= 0.0 for furnaces intended to be installed indoors
= 1.7 for furnaces intended to be installed as isolated combustion
systems
= 3.3 for furnaces intended to be installed outdoors
LS,SS = value as defined in section 11.4.6 of ASHRAE 103-
1993 at reduced input rate,
CS = value as defined in section 11.3.10.1 of ASHRAE 103-
1993 at reduced input rate.
10.3 Part-Load Efficiency at Maximum Fuel Input Rate. If the option
in section 8.9 of this appendix is not employed, calculate the part-
load efficiency at maximum fuel input rate, EffyU,H, for
condensing furnaces equipped with two-stage controls, expressed as a
percent and defined as:
[GRAPHIC] [TIFF OMITTED] TR13MR23.002
Where:
LL,A = value as defined in section 11.2.7 of ASHRAE 103-
1993,
LG = value as defined in section 11.3.11.1 of ASHRAE 103-
1993 at maximum input rate,
LC = value as defined in section 11.3.11.2 of ASHRAE 103-
1993 at maximum input rate,
LJ = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993 at maximum input rate,
tON = value as defined in section 11.4.9.11 of ASHRAE
103-1993,
QP = pilot fuel input rate determined in accordance with
section 9.2 of ASHRAE 103-1993 in Btu/h,
QIN = value as defined in section 11.4.8.1.1 of ASHRAE
103-1993,
tOFF = value as defined in section 11.4.9.12 of ASHRAE
103-1993 at maximum input rate,
LS,ON = value as defined in section 11.4.10.5 of ASHRAE
103-1993 at maximum input rate,
LS,OFF = value as defined in section 11.4.10.6 of ASHRAE
103-1993 at maximum input rate,
[[Page 15544]]
LI,ON = value as defined in section 11.4.10.7 of ASHRAE
103-1993 at maximum input rate,
LI,OFF = value as defined in section 11.4.10.8 of ASHRAE
103-1993 at maximum input rate,
CJ = value as defined in section 10.2 of this appendix,
LS,SS = value as defined in section 11.4.6 of ASHRAE 103-
1993 at maximum input rate,
CS = value as defined in section 11.4.10.1 of ASHRAE 103-
1993 at maximum input rate.
10.4 National average burner operating hours, average annual fuel
energy consumption, and average annual auxiliary electrical energy
consumption for gas or oil furnaces.
10.4.1 National average number of burner operating hours. For
furnaces equipped with single-stage controls, the national average
number of burner operating hours is defined as:
BOHSS = 2,080 (0.77) (A) DHR - 2,080 (B)
Where:
2,080 = national average heating load hours
0.77 = adjustment factor to adjust the calculated design heating
requirement and heating load hours to the actual heating load
experienced by the heating system
A = 100,000/[341,200 (yP PE + yIG
PEIG + y BE) + (QIN - QP)
EffyHS], for forced draft unit, indoors
= 100,000/[341,200 (yP PE Effmotor +
yIG PEIG + y BE) + (QIN -
QP) EffyHS], for forced draft unit, isolated
combustion system,
= 100,000/[341,200 (yP PE (1 - Effmotor) +
yIG PEIG + y BE) + (QIN -
QP) EffyHS], for induced draft unit, indoors,
and
= 100,000/[341,200 (yIG PEIG + y BE) +
(QIN - QP) EffyHS], for induced
draft unit, isolated combustion system.
DHR = typical design heating requirements as listed in Table 8 (in
kBtu/h) of ASHRAE 103-1993, using the proper value of
QOUT defined in section 11.2.8.1 of ASHRAE 103-1993.
B = 2 QP (EffyHS) (A)/100,000
Where:
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not provided
by the manufacturer.
100,000 = factor that accounts for percent and kBtu
yP = ratio of induced or forced draft blower on-time to
average burner on-time, as follows:
1 for units without post-purge;
1 + (tP/3.87) for single stage furnaces with post purge;
or
1 + (tP/10) for two-stage and step modulating furnaces
with post purge.
PE = all electrical power related to burner operation at full load
steady-state operation, including electrical ignition device if
energized, controls, gas valve or oil control valve, and draft
inducer, as determined in section 8.2 of this appendix.
yIG = ratio of burner interrupted ignition device on-time
to average burner on-time, as follows:
0 for burners not equipped with interrupted ignition device;
(tIG/3.87) for single-stage furnaces; or
(tIG/10) for two-stage and step modulating furnaces;
PEIG = electrical input rate to the interrupted ignition
device on burner (if employed), as defined in section 8.3 of this
appendix
y = ratio of blower on-time to average burner on-time, as follows:
1 for furnaces without fan delay;
1 + (t\+\-t-)/3.87 for single-stage furnaces with fan
delay; or
1 + (t\+\-t-)/10 for two-stage and step modulating
furnaces with fan delay.
BE = circulating air fan electrical energy input rate at full-load
steady-state operation as defined in section 8.2 of this appendix.
tP = post-purge time as defined in section 8.5 of this
appendix
= 0 if tP is equal to or less than 30 seconds
tIG = on-time of the burner interrupted ignition device,
as defined in section 8.3 of this appendix
QIN = as defined in section 11.2.8.1 of ASHRAE 103-1993
QP = as defined in section 11.2.11 of ASHRAE 103-1993
EffyHS = as defined in section 11.2.11 (non-condensing
systems) or section 11.3.11.3 (condensing systems) of ASHRAE 103-
1993, percent, and calculated on the basis of:
isolated combustion system installation, for non-weatherized warm
air furnaces; or outdoor installation, for furnaces that are
weatherized.
2 = ratio of the average length of the heating season in hours to
the average heating load hours
t\+\ = delay time between burner shutoff and the blower shutoff
measured as defined in section 9.5.1.2 of ASHRAE 103-1993
t- = as defined in section 9.6.1 of ASHRAE 103-1993
10.4.1.1 For furnaces equipped with two stage or step modulating
controls the average annual energy used during the heating season,
EM, is defined as:
EM = (QIN-QP) BOHSS +
(8,760-4,600) QP
Where:
QIN = as defined in section 11.4.8.1.1 of ASHRAE 103-1993
QP = as defined in section 11.4.12 of ASHRAE 103-1993
BOHSS = as defined in section 10.4.1 of this appendix, in
which the weighted EffyHS as defined in section 11.4.11.3
or 11.5.11.3 of ASHRAE 103-1993 is used for calculating the values
of A and B, the term DHR is based on the value of QOUT
defined in section 11.4.8.1.1 or 11.5.8.1.1 of ASHRAE 103-1993, and
the term (yPPE + yIGPEIG + yBE) in
the factor A is increased by the factor R, which is defined as:
R = 2.3 for two stage controls
= 2.3 for step modulating controls when the ratio of minimum-to-
maximum output is greater than or equal to 0.5
= 3.0 for step modulating controls when the ratio of minimum-to-
maximum output is less than 0.5
A = 100,000/[341,200 (yP PE + yIG
PEIG + y BE) R + (QIN-QP)
EffyHS], for forced draft unit, indoors
= 100,000/[341,200 (yP PE Effmotor +
yIG PEIG + y BE) R + (QIN-
QP) EffyHS], for forced draft unit, isolated
combustion system,
= 100,000/[341,200 (yP PE (1-Effmotor) +
yIG PEIG + y BE) R + (QIN-
QP) EffyHS], for induced draft unit, indoors,
and
= 100,000/[341,200 (yIG PEIG + y BE) R +
(QIN-QP) EffyHS], for induced draft
unit, isolated combustion system.
Where:
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not provided
by the manufacturer.
EffyHS = as defined in section 11.4.11.3 or 11.5.11.3 of
ASHRAE 103-1993, and calculated on the basis of:
isolated combustion system installation, for non-weatherized warm
air furnaces; or outdoor installation, for furnaces that are
weatherized.
8,760 = total number of hours per year
4,600 = as defined in section 11.4.12 of ASHRAE 103-1993
10.4.1.2 For furnaces equipped with two-stage or step-modulating
controls, the national average number of burner operating hours at the
reduced operating mode (BOHR) is defined as:
BOHR = XR EM/QIN,R
Where:
XR = as defined in section 11.4.8.7 of ASHRAE 103-1993
EM = as defined in section 10.4.1.1 of this appendix
QIN,R = as defined in section 11.4.8.1.2 of ASHRAE 103-
1993
10.4.1.3 For furnaces equipped with two-stage controls, the
national average number of burner operating hours at the maximum
operating mode (BOHH) is defined as:
BOHH = XH EM/QIN
Where:
XH = as defined in section 11.4.8.6 of ASHRAE 103-1993
EM = as defined in section 10.4.1.1 of this appendix
QIN = as defined in section 11.4.8.1.1 of ASHRAE 103-1993
10.4.1.4 For furnaces equipped with step-modulating controls, the
national average number of burner operating hours at the modulating
operating mode (BOHM) is defined as:
BOHM = XH EM/QIN,M
Where:
XH = as defined in section 11.4.8.6 of ASHRAE 103-1993
EM = as defined in section 10.4.1.1 of this appendix
QIN,M = QOUT,M/(EffySS,M/100)
[[Page 15545]]
QOUT,M = as defined in section 11.4.8.10 or 11.5.8.10 of
ASHRAE 103-1993, as appropriate
EffySS,M = as defined in section 11.4.8.8 or 11.5.8.8 of
ASHRAE 103-1993, as appropriate, in percent
100 = factor that accounts for percent
10.4.2 Average annual fuel energy consumption for gas or oil fueled
furnaces. For furnaces equipped with single-stage controls, the average
annual fuel energy consumption (EF) is expressed in Btu per
year and defined as:
EF = BOHSS (QIN-QP) + 8,760
QP
Where:
BOHSS = as defined in section 10.4.1 of this appendix
QIN = as defined in section 11.2.8.1 of ASHRAE 103-1993
QP = as defined in section 11.2.11 of ASHRAE 103-1993
8,760 = as defined in section 10.4.1.1 of this appendix
10.4.2.1 For furnaces equipped with either two-stage or step
modulating controls, EF is defined as:
EF = EM + 4,600 QP
Where:
EM = as defined in section 10.4.1.1 of this appendix
4,600 = as defined in section 11.4.12 of ASHRAE 103-1993
QP = as defined in section 11.2.11 of ASHRAE 103-1993
10.4.2.2 [Reserved]
10.4.3 Average annual auxiliary electrical energy consumption for
gas or oil-fueled furnaces. For furnaces equipped with single-stage
controls, the average annual auxiliary electrical consumption
(EAE) is expressed in kilowatt-hours and defined as:
EAE = BOHSS (yP PE + yIG
PEIG + yBE) + ESO
Where:
BOHSS = as defined in section 10.4.1 of this appendix
yP = as defined in section 10.4.1 of this appendix
PE = as defined in section 10.4.1 of this appendix
yIG = as defined in section 10.4.1 of this appendix
PEIG = as defined in section 10.4.1 of this appendix
y = as defined in section 10.4.1 of this appendix
BE = as defined in section 10.4.1 of this appendix
ESO = as defined in section 10.11 of this appendix
10.4.3.1 For furnaces equipped with two-stage controls,
EAE is defined as:
EAE = BOHR (yP PER +
yIG PEIG + yBER) + BOHH
(yP PEH + yIG PEIG + y
BEH) + ESO
Where:
BOHR = as defined in section 10.4.1.2 of this appendix
yP = as defined in section 10.4.1 of this appendix
PER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
yIG = as defined in section 10.4.1 of this appendix
PEIG = as defined in section 10.4.1 of this appendix
y = as defined in section 10.4.1 of this appendix
BER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
BOHH = as defined in section 10.4.1.3 of this appendix
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
ESO = as defined in section 10.11 of this appendix
10.4.3.2 For furnaces equipped with step-modulating controls,
EAE is defined as:
EAE = BOHR (yP PER +
yIG PEIG + y BER) + BOHM
(yP PEH + yIG PEIG + y
BEH) + ESO
Where:
BOHR = as defined in section 10.4.1.2 of this appendix
yP = as defined in section 10.4.1 of this appendix
PER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
yIG = as defined in section 10.4.1 of this appendix
PEIG = as defined in section 10.4.1 of this appendix
y = as defined in section 10.4.1 of this appendix
BER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
BOHM = as defined in 10.4.1.4 of this appendix
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
ESO = as defined in section 10.11 of this appendix
10.5 Average annual electric energy consumption for electric
furnaces. For electric furnaces, the average annual electrical energy
consumption (EE) is expressed in kilowatt-hours and defined
as:
EE = 100 (2,080) (0.77) DHR/(3.412 AFUE) + ESO
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this appendix
0.77 = as defined in section 10.4.1 of this appendix
DHR = as defined in section 10.4.1 of this appendix
3.412 = conversion factor from watt-hours to Btu
AFUE = as defined in section 11.1 of ASHRAE 103-1993, in percent,
and calculated on the basis of:
isolated combustion system installation, for non-weatherized warm
air furnaces; or
outdoor installation, for furnaces that are weatherized.
ESO = as defined in section 10.11 of this appendix.
10.6 Energy factor.
10.6.1 Energy factor for gas or oil furnaces. Calculate the energy
factor, EF, for gas or oil furnaces defined as, in percent:
EF = (EF-4,600 (QP))(EffyHS)/
(EF + 3,412 (EAE))
Where:
EF = average annual fuel consumption as defined in
section 10.4.2 of this appendix
4,600 = as defined in section 11.4.12 of ASHRAE 103-1993
QP = pilot fuel input rate determined in accordance with
section 9.2 of ASHRAE 103-1993 in Btu/h
EffyHS = annual fuel utilization efficiency as defined in
sections 11.2.11, 11.3.11, 11.4.11 or 11.5.11 of ASHRAE 103-1993, in
percent, and calculated on the basis of:
isolated combustion system installation, for non-weatherized warm
air furnaces; or
outdoor installation, for furnaces that are weatherized.
3,412 = conversion factor from kW to Btu/h
EAE = as defined in section 10.4.3 of this appendix
10.6.2 Energy factor for electric furnaces. The energy factor, EF,
for electric furnaces is defined as:
EF = AFUE
Where:
AFUE = annual fuel utilization efficiency as defined in section
10.4.3 of this appendix, in percent
10.7 Average annual energy consumption for furnaces located in a
different geographic region of the United States and in buildings with
different design heating requirements.
10.7.1 Average annual fuel energy consumption for gas or oil-fueled
furnaces located in a different geographic region of the United States
and in buildings with different design heating requirements. For gas or
oil-fueled furnaces, the average annual fuel energy consumption for a
specific geographic region and a specific typical design heating
requirement (EFR) is expressed in Btu per year and defined
as:
EFR = (EF-8,760 QP) (HLH/2,080) +
8,760 QP
Where:
[[Page 15546]]
EF = as defined in section 10.4.2 of this appendix
8,760 = as defined in section 10.4.1.1 of this appendix
QP = as defined in section 11.2.11 of ASHRAE 103-1993
HLH = heating load hours for a specific geographic region determined
from the heating load hour map in Figure 1 of this appendix
2,080 = as defined in section 10.4.1 of this appendix
10.7.2 Average annual auxiliary electrical energy consumption for
gas or oil-fueled furnaces located in a different geographic region of
the United States and in buildings with different design heating
requirements. For gas or oil-fueled furnaces, the average annual
auxiliary electrical energy consumption for a specific geographic
region and a specific typical design heating requirement
(EAER) is expressed in kilowatt-hours and defined as:
EAER = (EAE-ESO) (HLH/2080) +
ESOR
Where:
EAE = as defined in section 10.4.3 of this appendix
ESO = as defined in section 10.11 of this appendix
HLH = as defined in section 10.7.1 of this appendix
2,080 = as defined in section 10.4.1 of this appendix
ESOR = as defined in section 10.7.3 of this appendix.
10.7.3 Average annual electric energy consumption for electric
furnaces located in a different geographic region of the United States
and in buildings with different design heating requirements. For
electric furnaces, the average annual electric energy consumption for a
specific geographic region and a specific typical design heating
requirement (EER) is expressed in kilowatt-hours and defined
as:
EER = 100 (0.77) DHR HLH/(3.412 AFUE) + ESOR
Where:
100 = as defined in section 10.4.3 of this appendix
0.77 = as defined in section 10.4.1 of this appendix
DHR = as defined in section 10.4.1 of this appendix
HLH = as defined in section 10.7.1 of this appendix
3.412 = as defined in section 10.4.3 of this appendix
AFUE = as defined in section 10.4.3 of this appendix
ESOR = ESO as defined in section 10.11 of this
appendix, except that in the equation for ESO, the term
BOH is multiplied by the expression (HLH/2080) to get the
appropriate regional accounting of standby mode and off mode loss.
10.8 Annual energy consumption for mobile home furnaces
10.8.1 National average number of burner operating hours for mobile
home furnaces (BOHSS). BOHSS is the same as in
section 10.4.1 of this appendix, except that the value of
EffyHS in the calculation of the burner operating hours,
BOHSS, is calculated on the basis of a direct vent unit with
system number 9 or 10.
10.8.2 Average annual fuel energy for mobile home furnaces
(EF). EF is same as in section 10.4.2 of this
appendix except that the burner operating hours, BOHSS, is
calculated as specified in section 10.8.1 of this appendix.
10.8.3 Average annual auxiliary electrical energy consumption for
mobile home furnaces (EAE). EAE is the same as in
section 10.4.3 of this appendix, except that the burner operating
hours, BOHSS, is calculated as specified in section 10.8.1
of this appendix.
10.9 Calculation of sales weighted average annual energy
consumption for mobile home furnaces. To reflect the distribution of
mobile homes to geographical regions with average HLHMHF
values different from 2,080, adjust the annual fossil fuel and
auxiliary electrical energy consumption values for mobile home furnaces
using the following adjustment calculations.
10.9.1 For mobile home furnaces, the sales weighted average annual
fossil fuel energy consumption is expressed in Btu per year and defined
as:
EF,MHF = (EF-8,760 QP)
HLHMHF/2,080 + 8,760 QP
Where:
EF = as defined in section 10.8.2 of this appendix
8,760 = as defined in section 10.4.1.1 of this appendix
QP = as defined in section 10.2 of this appendix
HLHMHF = 1880, sales weighted average heating load hours
for mobile home furnaces
2,080 = as defined in section 10.4.1 of this appendix
10.9.2 For mobile home furnaces, the sales-weighted-average annual
auxiliary electrical energy consumption is expressed in kilowatt-hours
and defined as:
EAE,MHF = EAE HLHMHF/2,080
Where:
EAE = as defined in section 10.8.3 of this appendix
HLHMHF = as defined in section 10.9.1 of this appendix
2,080 = as defined in section 10.4.1 of this appendix
10.10 [Reserved]
10.11 Average annual electrical standby mode and off mode energy
consumption. Calculate the annual electrical standby mode and off mode
energy consumption (ESO) in kilowatt-hours, defined as:
ESO = (PW,SB (4160-BOH) + 4600 PW,OFF)
K
Where:
PW,SB = furnace standby mode power, in watts, as measured
in section 8.10.1 of this appendix
4,160 = average heating season hours per year
BOH = total burner operating hours as calculated in section 10.4 of
this appendix for gas or oil-fueled furnaces. Where for gas or oil-
fueled furnaces equipped with single-stage controls, BOH =
BOHSS; for gas or oil-fueled furnaces equipped with two-
stage controls, BOH = (BOHR + BOHH); and for
gas or oil-fueled furnaces equipped with step-modulating controls,
BOH = (BOHR + BOHM). For electric furnaces,
BOH = 100(2080)(0.77)DHR/(Ein 3.412(AFUE))
4,600 = as defined in section 11.4.12 of ASHRAE 103-1993
PW,OFF = furnace off mode power, in watts, as measured in
section 8.10.2 of this appendix
K = 0.001 kWh/Wh, conversion factor from watt-hours to kilowatt-
hours
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.4.1 of this appendix
0.77 = as defined in section 10.4.1 of this appendix
DHR = as defined in section 10.4.1 of this appendix
Ein = steady-state electric rated power, in kilowatts,
from section 9.3 of ASHRAE 103-1993
3.412 = as defined in section 10.4.3 of this appendix
AFUE = as defined in section 11.1 of ASHRAE 103-1993 in percent
[[Page 15547]]
[GRAPHIC] [TIFF OMITTED] TR13MR23.003
0
8. Appendix EE to subpart B of part 430 is added to read as follows:
Appendix EE to Subpart B of Part 430--Uniform Test Method For Measuring
the Energy Consumption of Consumer Boilers
0. Incorporation by reference
DOE incorporated by reference in Sec. 430.3, the entire standard
for ASHRAE 103-2017, ASHRAE 41.6-2014, ASTM D2156-09 (R2018), and IEC
62301. However, only enumerated provisions of ASHRAE 103-2017 are
applicable to this appendix, as follows. In cases where there is a
conflict, the language of the test procedure in this appendix takes
precedence over the incorporated standards.
0.1 ASHRAE 103-2017
(a) Section 2 ``Scope'' as referenced in section 1 of this
appendix;
(b) Section 3 ``Definitions'' as referenced in section 2 of this
appendix;
(c) Section 4 ``Classifications'' as referenced in section 3 of
this appendix;
(d) Section 5 ``Requirements'' as referenced in section 4 of this
appendix;
(e) Section 6 ``Instruments'' as referenced in sections 5 and 8 of
this appendix;
(f) Section 7 ``Apparatus'' (except for sections 7.1 and 7.8) as
referenced in sections 6, 7.7, and 8.6 of this appendix;
(g) Section 8 ``Methods of Testing'' (except for sections 8.3.1.3,
8.3.3.1, 8.4.1.1, 8.4.1.1.1, 8.4.1.2, 8.6.1.1, 8.7.2, and 8.8.3) as
referenced in sections 7 and 8 of this appendix;
(h) Section 9 ``Test Procedure'' (except for 9.1.2.2.1, 9.1.2.2.2,
9.5.2.1, 9.7.4, and 9.10) as referenced in sections 7.3, 8, and 10.4 of
this appendix;
(i) Section 10 ``Nomenclature'' as referenced in section 9 of this
appendix; and
(j) Section 11 ``Calculations'' as referenced in sections 8.8 and
10 of this appendix.
0.2 [Reserved]
1. Scope. The scope of this appendix is as specified in section 2
of ASHRAE 103-2017 as it pertains to low pressure steam or hot water
boiler and electric boilers.
2. Definitions. Definitions include those specified in section 3 of
ASHRAE 103-2017 and the following additional and modified definitions.
Active mode means the condition in which the boiler is connected to
the power source, and at least one of the burner, electric resistance
elements, or any electrical auxiliaries such as blowers or pumps, are
activated.
Boiler pump means a pump installed on a boiler that maintains
adequate water flow through the boiler heat exchanger and that is
separate from the circulating water pump.
Draft inducer means a fan incorporated in the boiler that either
draws or forces air into the combustion chamber.
Gas valve means an automatic or semi-automatic device consisting
essentially of a valve and operator that controls the gas supply to the
burner(s) during normal operation of an appliance. The operator may be
actuated by application of gas pressure on a flexible diaphragm, by
electrical means, by mechanical means or by other means.
Installation and operation (I&O) manual means instructions for
installing, commissioning, and operating the boiler, which are supplied
with the product when shipped by the manufacturer.
Off mode means a mode in which the boiler is connected to a mains
power source and is not providing any active mode or standby mode
function, and where the mode may persist for an indefinite time. The
existence of an off switch in off position (a disconnected
[[Page 15548]]
circuit) is included within the classification of off mode.
Off switch means the switch on the boiler that, when activated,
results in a measurable change in energy consumption between the
standby and off modes.
Oil control valve means an automatically or manually operated
device consisting of an oil valve for controlling the fuel supply to a
burner to regulate burner input.
Standard cubic foot of gas means the amount of gas that would
occupy 1 cubic foot when at a temperature of 60 [deg]F and under a
pressure equivalent to that of 30 inches Hg if saturated with water
vapor.
Standby mode means any mode in which the boiler is connected to a
mains power source and offers one or more of the following space
heating functions that may persist:
(a) To facilitate the activation of other modes (including
activation or deactivation of active mode) by remote switch (including
thermostat or remote control), internal or external sensors, or timer;
(b) Continuous functions, including information or status displays
or sensor-based functions.
Thermal stack damper means a type of stack damper that relies
exclusively upon the changes in temperature in the stack gases to open
or close the damper.
3. Classifications. Classifications are as specified in section 4
of ASHRAE 103-2017.
4. Requirements. Requirements are as specified in section 5 of
ASHRAE 103-2017.
5. Instruments. Instruments must be as specified in section 6 of
ASHRAE 103-2017. In addition to the requirements in Section 6.3 of
ASHRAE 103-2017, instruments for oil pressure shall be calibrated so
that the error is no greater than 0.5 psi.
6. Apparatus. The apparatus used in conjunction with the boiler
during the testing must be as specified in section 7 of ASHRAE 103-2017
except for sections 7.1 and 7.8; and as specified in sections 6.1 and
6.2 of this appendix. In section 7.2.3.1 of ASHRAE 103-2017, substitute
``in accordance with the I&O manual'' for ``in accordance with
manufacturer instructions'' with regard to installing the stack damper.
6.1 General.
(a) Install the boiler in the test room in accordance with the I&O
manual, as defined in section 2.5 of this appendix, except that if
provisions within this appendix are specified, then the provisions
herein drafted and prescribed by DOE govern. If the I&O manual and any
additional provisions of this appendix are not sufficient for testing a
boiler, the manufacturer must request a waiver from the test procedure
pursuant to Sec. 430.27.
(b) The apparatuses described in section 6 of this appendix are
used in conjunction with the boiler during testing. Each piece of
apparatus shall conform to material and construction specifications
listed in this appendix and in ASHRAE 103-2017, and the reference
standards cited in this appendix and in ASHRAE 103-2017.
(c) Test rooms containing equipment must have suitable facilities
for providing the utilities (including but not limited to environmental
controls, sufficient fluid source(s), applicable measurement equipment,
and any other technology or tools) necessary for performance of the
test and must be able to maintain conditions within the limits
specified in section 6 of this appendix.
6.2 Condensate collection. Attach condensate drain lines to the
unit as specified in the I&O manual. Maintain a continuous downward
slope of drain lines from the unit. Additional precautions (such as
eliminating any line configuration or position that would otherwise
restrict or block the flow of condensate or checking to ensure a proper
connection with condensate drain spout that allows for unobstructed
flow) must be taken to facilitate uninterrupted flow of condensate
during the test. Collection containers must be glass or polished
stainless steel to facilitate removal of interior deposits. The
collection container must have a vent opening to the atmosphere.
7. Testing conditions. The testing conditions must be as specified
in section 8 of ASHRAE 103-2017 (except for the excluded sub-sections
as enumerated in section 0.1(g) of this appendix); and as specified in
sections 7.1 to 7.8 of this appendix, respectively. For condensing
furnaces and boilers, the relative humidity of the room air shall be
measured in accordance with one of the methods described in ASHRAE
41.6-2014 (see section 8.5 of ASHRAE 103-2017).
7.1 Fuel supply, gas. In conducting the tests specified herein,
gases with characteristics as shown in Table 1 of ASHRAE 103-2017 shall
be used. Maintain the gas supply, ahead of all controls for a boiler,
at a test pressure between the normal and increased values shown in
Table 1 of ASHRAE 103-2017. Maintain the regulator outlet pressure at a
level approximating that recommended in the I&O manual, as defined in
section 2.5 of this appendix, or, in the absence of such
recommendation, to the regulator settings used when the product is
shipped by the manufacturer. Use a gas having a specific gravity of
approximately that shown in Table 1 of ASHRAE 103-2017 and with a
higher heating value within 5% of the higher heating value
shown in Table 1 of ASHRAE 103-2017. Determine the actual higher
heating value in Btu per standard cubic foot of gas (defined in section
2 of this appendix) to be used in the test within an error no greater
than 1%.
7.2 Installation of piping. Install piping equipment in accordance
with the I&O manual. In the absence of such specification, install
piping in accordance with section 8.3.1.1 of ASHRAE 103-2017.
7.3 Gas burner. Adjust the burners of gas-fired boilers to their
maximum Btu input ratings at the normal test pressure specified by
section 7.1 of this appendix. Correct the burner input rate to reflect
gas characteristics at a temperature of 60 [deg]F and atmospheric
pressure of 30 in of Hg and adjust to within 2 percent of
the hourly Btu nameplate input rating specified by the manufacturer as
measured at the maximum input rate during the steady-state performance
test in section 8 of this appendix. Set the primary air shutters in
accordance with the I&O manual to give a good flame at this condition.
If, however, the setting results in the deposit of carbon on the
burners during any test specified herein, the tester shall adjust the
shutters and burners until no more carbon is deposited and shall
perform the tests again with the new settings (see Figure 9 of ASHRAE
103-2017). After the steady-state performance test has been started, do
not make additional adjustments to the burners during the required
series of performance tests specified in section 9 of ASHRAE 103-2017.
If a vent-limiting means is provided on a gas pressure regulator, keep
it in place during all tests.
7.4 Modulating gas burner adjustment at reduced input rate. For
gas-fired boilers equipped with modulating-type controls, adjust the
controls to operate the unit at the nameplate minimum input rate. If
the modulating control is of a non-automatic type, adjust the control
to the setting recommended in the I&O manual. In the absence of such
recommendation, the midpoint setting of the non-automatic control shall
be used as the setting for determining the reduced fuel input rate.
Start the boiler by turning the safety control valve to the ``ON''
position. Use a supply water temperature that will allow for continuous
operation without shutoff by
[[Page 15549]]
the control. If necessary to achieve such continuous operation, supply
water may be increased above 120 [deg]F; in such cases, gradually
increase the supply water temperature to determine what minimum supply
water temperature, with a 20 [deg]F temperature rise across the boiler,
will be needed to adjust for the minimum input rate at the reduced
input rate control setting. Monitor regulated gas pressure out of the
modulating control valve (or entering the burner) to determine when no
further reduction of gas pressure results. The flow rate of water
through the boiler shall be adjusted to achieve a 20 [deg]F temperature
rise.
7.5 Oil burner. Adjust the burners of oil-fired boilers to give a
CO2 reading specified in the I&O manual and an hourly Btu
input within 2% of the hourly Btu nameplate input rating as
specified in the I&O manual and as measured at maximum input rate
during steady-state performance test as described in section 8 of this
appendix. Smoke in the flue may not exceed a No. 1 smoke during the
steady-state performance test as measured by the procedure in ASTM
D2156-09 (R2018). Maintain the average draft over the fire and in the
flue during the steady-state performance test at the value specified in
the I&O manual. Do not allow draft fluctuations exceeding 0.005 in.
water. Do not make additional adjustments to the burner during the
required series of performance tests. The instruments and measuring
apparatus for this test are described in section 6 of this appendix and
shown in Figure 8 of ASHRAE 103-2017.
7.6 Measurement of jacket surface temperature. Divide the jacket of
the boiler into 6-inch squares when practical, and otherwise into 36-
square-inch regions comprising 4 inch by 9 inch or 3 inch by 12 inch
sections, and determine the surface temperature at the center of each
square or section with a surface thermocouple. Record the surface
temperature of the 36-square-inch areas in groups where the temperature
differential of the 36-square-inch areas is less than 10 [deg]F for
temperature up to 100 [deg]F above room temperature, and less than 20
[deg]F for temperatures more than 100 [deg]F above room temperature.
7.7 Installation of vent system. Keep the vent or air intake system
supplied by the manufacturer in place during all tests. Test units
intended for installation with a variety of vent pipe lengths with the
minimum vent length as specified in the I&O manual, or a 5-ft. flue
pipe if there are no recommendations in the I&O manual. Do not connect
a boiler employing a direct vent system to a chimney or induced-draft
source. Vent combustion products solely by using the venting
incorporated in the boiler and the vent or air intake system supplied
by the manufacturer. For units that are not designed to significantly
preheat the incoming air, see section 7.5 of this appendix and Figure
4a or 4b in section 7 of ASHRAE 103-2017. For units that do
significantly preheat the incoming air, see Figure 4c or 4d in section
7 of ASHRAE 103-2017.
7.8 Additional optional method of testing for determining
DP and DF. On units whose design is such that
there is no measurable airflow through the combustion chamber and heat
exchanger when the burner(s) is (are) off as determined by the optional
test procedure in section 7.8.1 of this appendix, DF and
DP may be set equal to 0.05.
7.8.1 Optional test method for indicating the absence of flow
through the heat exchanger. Manufacturers may use the following test
protocol to determine whether air flows through the combustion chamber
and heat exchanger when the burner(s) is (are) off. The minimum default
draft factor may be used only for units determined pursuant to this
protocol to have no airflow through the combustion chamber and heat
exchanger.
7.8.1.1 Test apparatus. Use a smoke stick that produces smoke that
is easily visible and has a density less than or approximately equal to
air. Use a smoke stick that produces smoke that is non-toxic to the
test personnel and produces gas that is unreactive with the environment
in the test chamber.
7.8.1.2 Test conditions. Minimize all air currents and drafts in
the test chamber, including turning off ventilation if the test chamber
is mechanically ventilated. Wait at least two minutes following the
termination of the boiler on-cycle before beginning the optional test
method for indicating the absence of flow through the heat exchanger.
7.8.1.3 Location of the test apparatus. After all air currents and
drafts in the test chamber have been eliminated or minimized, position
the smoke stick based on the following equipment configuration:
(a) For horizontal combustion air intakes, approximately 4 inches
from the vertical plane at the termination of the intake vent and 4
inches below the bottom edge of the combustion air intake; or
(b) for vertical combustion air intakes, approximately 4 inches
horizontal from vent perimeter at the termination of the intake vent
and 4 inches down (parallel to the vertical axis of the vent). In the
instance where the boiler combustion air intake is closer than 4 inches
to the floor, place the smoke device directly on the floor without
impeding the flow of smoke.
7.8.1.4 Duration of test. Establish the presence of smoke from the
smoke stick and then monitor the direction of the smoke flow for no
less than 30 seconds.
7.8.1.5 Test results. During visual assessment, determine whether
there is any draw of smoke into the combustion air intake vent.
If absolutely no smoke is drawn into the combustion air intake, the
boiler meets the requirements to allow use of the minimum default draft
factor provided in section 7.8 of this appendix.
If there is any smoke drawn into the intake, proceed with the
methods of testing as prescribed in section 8.8 of ASHRAE 103-2017.
7.8.2 [Reserved]
8. Test procedure. Conduct testing and measurements as specified in
Section 9 of ASHRAE 103-2017 (except for the excluded sub-sections as
enumerated in section 0.1(h) of this appendix); and as specified in
sections 8.1 through 8.9 of this appendix. Section 8.4 of this appendix
may be used in lieu of section 9.2 of ASHRAE 103-2017.
8.1 Fuel input. For gas units, measure and record the steady-state
gas input rate in Btu/h, including pilot gas, corrected to standard
conditions of 60 [deg]F and 30 in. Hg. Use measured values of gas
temperature and pressure at the meter and barometric pressure to
correct the metered gas flow rate to the above standard conditions. For
oil units, measure and record the steady-state fuel input rate. For
maximum input rate, the measured burner input rate shall be within
2% of the hourly Btu nameplate input rating
(QIN) specified by the manufacturer. For modulating furnaces
and boilers operating at reduced input rate, the measured reduced heat
input rate (QIN,R) shall be recorded. At the discretion of
the one testing, the hourly Btu nameplate minimum input rating
specified by the manufacturer may be used in the calculations in place
of QIN,R if the measured rate is within 2% of
the nameplate rating.
8.2 Electrical input. During the steady-state test, perform a
single measurement of all of the electrical power involved in burner
operation (PE), including energizing the ignition system, controls, gas
valve or oil control valve, and draft inducer, if applicable. For
boilers, the measurement of PE must include the boiler pump if so
equipped. If the boiler pump does not operate during the measurement of
PE, add the boiler pump nameplate power to the
[[Page 15550]]
measurement of PE. If the boiler pump nameplate power is not available,
use 0.13 kW. For hot water boilers, use the circulating water pump
nameplate power for BE, or if the pump nameplate power is not
available, use 0.13 kW.
8.3 Input to interrupted ignition device. For burners equipped with
an interrupted ignition device, record the nameplate electric power
used by the ignition device, PEIG, or record that
PEIG = 0.4 kW if no nameplate power input is provided.
Record the nameplate ignition device on-time interval, tIG,
or, if the nameplate does not provide the ignition device on-time
interval, measure the on-time interval with a stopwatch at the
beginning of the test, starting when the burner is turned on. Set
tIG = 0 and PEIG = 0 if the device on-time
interval is less than or equal to 5 seconds after the burner is on.
8.4 Cycling Test Requirements. For the measurement of condensate
heat loss under cyclic conditions (for condensing boilers), section 9.8
of ASHRAE 103-2017 shall apply. Cycle times calculated from Table 7 of
ASHRAE 103-2017 shall be rounded to the nearest second.
8.5 Optional test procedures for condensing boilers, measurement of
condensate during the establishment of steady-state conditions. For
units with step-modulating or two-stage controls, conduct the test at
both the maximum and reduced inputs. In lieu of collecting the
condensate immediately after the steady state conditions have been
reached as required by section 9.2 of ASHRAE 103-2017, condensate may
be collected during the establishment of steady state conditions as
defined by section 9.1.2.1 of ASHRAE 103-2017. Perform condensate
collection for at least 30 minutes. Measure condensate mass immediately
at the end of the collection period to prevent evaporation loss from
the sample. Record fuel input for the 30-minute condensate collection
test period. Observe and record fuel higher heating value (HHV),
temperature, and pressures necessary for determining fuel energy input
(QC,SS). Measure the fuel quantity and HHV with errors no
greater than 1%. The humidity for the room air shall at no time exceed
80%. Determine the mass of condensate for the establishment of steady
state conditions (MC,SS) in pounds by subtracting the tare
container weight from the total container and condensate weight
measured at the end of the 30-minute condensate collection test period.
8.6 Cool-down test for gas- and oil-fueled boilers without stack
dampers. After steady-state testing has been completed, turn the main
burner(s) ``OFF'' and measure the flue gas temperature at 3.75 minutes
(temperature designated as TF,OFF(t3)) and 22.5
minutes (temperature designated as TF,OFF(t4))
after the burner shut-off using the thermocouple grid described in
section 7.6 of ASHRAE 103-2017.
a. During this off-period, for units that do not have pump delay
after shut-off, do not allow any water to circulate through the hot
water boilers.
b. For units that have pump delay on shut-off, except those having
pump controls sensing water temperature, the unit control must stop the
pump. Measure and record the time between burner shut-off and pump
shut-off (t\+\) to the nearest second.
c. For units having pump delay controls that sense water
temperature, operate the pump for 15 minutes and record t\+\ as 15
minutes. While the pump is operating, maintain the inlet water
temperature and flow rate at the same values as used during the steady-
state test, as specified in sections 9.1 and 8.4.2.3 of ASHRAE 103-
2017.
d. For boilers that employ post-purge, measure the length of the
post-purge period with a stopwatch. Record the time from burner ``OFF''
to combustion blower ``OFF'' (electrically de-energized) as
tP. Measure the flue gas temperature by means of the
thermocouple grid described in section 7.6 of ASHRAE 103-2017 at the
end of the post-purge period tP
(TF,OFF(tP)) and at (3.75 + tP)
minutes (TF,OFF(t3)) and (22.5 + tP)
minutes (TF,OFF(t4)) after the main burner shuts
off. If tP is prescribed by the I&O manual or measured to be
greater than 3 minutes, also measure the flue gas temperature at the
midpoint of the post-purge period tP/2
(TF,OFF(tP/2)). If the measured tP is
less than or equal to 30 seconds, record tP as 0 and conduct
the cool-down test as if there is no post-purge.
8.7 [Reserved]
8.8 Calculation options. The rate of the flue gas mass flow through
the boiler and the factors DP, DF, and
DS are calculated by the equations in sections 11.6.1,
11.6.2, 11.6.3, 11.6.4, 11.7.1, and 11.7.2 of ASHRAE 103-2017. On units
whose design is such that there is no measurable airflow through the
combustion chamber and heat exchanger when the burner(s) is (are) off
(as determined by the optional test procedure in section 7.8 of this
appendix), DF and DP may be set equal to 0.05.
8.9 Optional test procedures for condensing boilers that have no
off-period flue losses. For units that have applied the test method in
section 7.8 of this appendix to determine that no measurable airflow
exists through the combustion chamber and heat exchanger during the
burner off-period and having post-purge periods of less than 30
seconds, the cool-down and heat-up tests specified in sections 9.5 and
9.6 of ASHRAE 103-2017 may be omitted. In lieu of conducting the cool-
down and heat-up tests, the tester may use the losses determined during
the steady-state test described in section 9.1 of ASHRAE 103-2017 when
calculating heating seasonal efficiency, EffyHS.
8.10 Measurement of electrical standby and off mode power.
8.10.1 Standby power measurement. With all electrical auxiliaries
of the boiler not activated, measure the standby power
(PW,SB) in accordance with the procedures in IEC 62301,
except that section 8.5, Room Ambient Temperature, of ASHRAE 103-2017
and the voltage provision of section 8.2.1.4, Electrical Supply, of
ASHRAE 103-2017 shall apply in lieu of the corresponding provisions of
IEC 62301 at section 4.2, Test room, and the voltage specification of
section 4.3, Power supply. Frequency shall be 60Hz. Clarifying further,
IEC 62301 section 4.4, Power measurement instruments, and section 5,
Measurements, apply in lieu of ASHRAE 103-2017 section 6.10, Energy
Flow Rate. Measure the wattage so that all possible standby mode
wattage for the entire appliance is recorded, not just the standby mode
wattage of a single auxiliary. Round the recorded standby power
(PW,SB) to the second decimal place, except for loads
greater than or equal to 10W, which must be recorded to at least three
significant figures.
8.10.2 Off mode power measurement. If the unit is equipped with an
off switch or there is an expected difference between off mode power
and standby mode power, measure off mode power
(PW,OFF) in accordance with the standby power
procedures in IEC 62301, except that section 8.5, Room Ambient
Temperature, of ASHRAE 103-2017 and the voltage provision of section
8.2.1.4, Electrical Supply, of ASHRAE 103-2017 shall apply in lieu of
the corresponding provisions of IEC 62301 at section 4.2, Test room,
and the voltage specification of section 4.3, Power supply. Frequency
shall be 60Hz. Clarifying further, IEC 62301 section 4.4, Power
measurement instruments, and section 5, Measurements, apply for this
measurement in lieu of SHRAE 103-2017 section 6.10, Energy Flow Rate.
Measure the wattage so that all possible off mode wattage for the
entire appliance is recorded, not just the off mode wattage of a single
auxiliary. If there is no expected difference in off
[[Page 15551]]
mode power and standby mode power, let PW,OFF =
PW,SB, in which case no separate measurement of off mode
power is necessary. Round the recorded off mode power
(PW,OFF) to the second decimal place, except for loads
greater than or equal to 10W, in which case round the recorded value to
at least three significant figures.
9. Nomenclature. Nomenclature includes the nomenclature specified
in Section 10 of ASHRAE 103-2017 and the following additional
variables:
Effmotor = Efficiency of power burner motor
PEIG = Electrical power to the interrupted ignition device,
kW
RT,a = RT,F if flue gas is measured
= RT,S if stack gas is measured
RT,F = Ratio of combustion air mass flow rate to
stoichiometric air mass flow rate
RT,S = Ratio of the sum of combustion air and relief air
mass flow rate to stoichiometric air mass flow rate
tIG = Electrical interrupted ignition device on-time, min.
Ta,SS,X = TF,SS,X if flue gas temperature is
measured, [deg]F
= TS,SS,X if stack gas temperature is measured, [deg]F
yIG = Ratio of electrical interrupted ignition device on-
time to average burner on-time
yP = Ratio of power burner combustion blower on-time to
average burner on-time
ESO = Average annual electric standby mode and off mode
energy consumption, in kilowatt-hours
PW,OFF = Boiler off mode power, in watts
PW,SB = Boiler standby mode power, in watts
10. Calculation of derived results from test measurements. Perform
calculations as specified in section 11 of ASHRAE 103-2017, except for
appendices B and C; and as specified in sections 10.1 through 10.7 and
Figure 1 of this appendix.
10.1 Annual fuel utilization efficiency. The annual fuel
utilization efficiency (AFUE) is as defined in sections 11.2.12 (non-
condensing systems), 11.3.12 (condensing systems), 11.4.12 (non-
condensing modulating systems) and 11.5.12 (condensing modulating
systems) of ASHRAE 103-2017, except for the following:
10.1.1 Off-cycle Infiltration Heat Loss. The off-cycle infiltration
heat loss (LI,OFF1) is as defined in sections 11.2.10.8
(non-condensing systems), 11.3.10.8 (condensing systems), 11.4.10.8
(non-condensing modulating systems) and 11.5.10.8 (condensing
modulating systems) of ASHREAE 103-2017, with the following exception.
For systems numbered 2, 3, and 4, with a post-purge time of 3 minutes
or less, LI,OFF1 shall be determined as follows:
[GRAPHIC] [TIFF OMITTED] TR13MR23.004
10.1.2 Determination of EffyHS in the Defining Equation
for AFUE. EffyHS is defined as:
EffyHS = heating seasonal efficiency as defined in sections
11.2.11 (non-condensing systems), 11.3.11 (condensing systems), 11.4.11
(non-condensing modulating systems) and 11.5.11 (condensing modulating
systems) of ASHRAE 103-2017, and is based on the assumptions that
weatherized boilers are located outdoors and that non-weatherized
boilers are installed indoors.
10.1.3 Balance Point Temperature for Condensing Modulating Boilers.
Calculate the balance point temperature (TC) for condensing,
modulating boilers by using the following equation in place of that
referenced by section 11.5.8.4 of ASHRAE 103-2017: TC =
[GRAPHIC] [TIFF OMITTED] TR13MR23.005
Where:
TSH = typical average outdoor temperature at which a
boiler starts operating, 65 [deg]F
TOA,T = the typical outdoor design temperature, 5 [deg]F
[alpha] = oversize factor, as defined in 11.4.8.2
QIN = steady-state nameplate maximum fuel input rate
QIN,R = steady-state reduced input fuel input rate
LS,SSR = average sensible heat loss at steady state,
reduced input operation
LS,SS = average sensible heat loss at steady state,
maximum input operation
10.2 National average burner operating hours, average annual fuel
energy consumption, and average annual auxiliary electrical energy
consumption for gas or oil boilers.
10.2.1 National average number of burner operating hours.
10.2.1.1 For boilers equipped with single-stage controls, the
national average number of burner operating hours is defined as:
BOHSS = 2,080 (0.77) (A) [(QOUT/1000)/
(1+[alpha])]-2,080 (B)
Where:
2,080 = national average heating load hours
0.77 = adjustment factor to adjust the calculated design heating
requirement and heating load hours to the actual heating load
experienced by the heating system
A = 100,000/[341,200 (yP PE + yIG
PEIG + y BE) + (QIN-QP)
EffyHS], for forced draft unit, indoors
= 100,000/[341,200 (yP PE (1-Effmotor) +
yIG PEIG + y BE) + (QIN-
QP) EffyHS], for induced draft unit, indoors,
and
QOUT = value as defined in section 11.2.8.1 of ASHRAE
103-2017.
[alpha] = value as defined in section 11.2.8.2 of ASHRAE 103-2017.
[[Page 15552]]
B = 2 QP (EffyHS) (A)/100,000
Where:
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not provided
by the manufacturer.
100,000 = factor that accounts for percent and kBtu
yP = ratio of induced or forced draft blower on-time to
average burner on-time, as follows:
1 for units without post-purge;
1 + (tP/tON) for single stage boilers with
post purge; or
PE = all electrical power related to burner operation at full load
steady-state operation, including electrical ignition device if
energized, controls, gas valve or oil control valve, draft inducer,
and boiler pump, as determined in section 8.2 of this appendix.
yIG = ratio of burner interrupted ignition device on-time
to average burner on-time, as follows:
0 for burners not equipped with interrupted ignition device;
(tIG/tON) for single stage boilers
PEIG = electrical input rate to the interrupted ignition
device on burner (if employed), as defined in section 8.3 of this
appendix
y = ratio of pump on-time to average burner on-time, as follows:
1 for boilers without a pump delay;
1 + (t\+\/tON) for single-stage boilers with pump delay;
BE = circulating water pump electrical energy input rate at full-
load steady-state operation as defined in section 8.2 of this
appendix.
tP = post-purge time as defined in section 8.5 of this
appendix
= 0 if tP is equal to or less than 30 seconds
tIG = on-time of the burner interrupted ignition device,
as defined in section 8.3 of this appendix
QIN = as defined in section 11.2.8.1 of ASHRAE 103-2017
QP = as defined in section 11.2.11 of ASHRAE 103-2017
EffyHS = as defined in section 11.2.11 (non-condensing
systems) or section 11.3.11.3 (condensing systems) of ASHRAE 103-
2017, percent, and calculated on the basis of:
indoor installation, for non-weatherized boilers; or outdoor
installation, for boilers that are weatherized.
2 = ratio of the average length of the heating season in hours to
the average heating load hours
t\+\ = delay time between burner shutoff and the pump shutoff
measured as defined in section 8.5 of this appendix.
tON = value as defined in Table 7 of ASHRAE 103-2017.
10.2.1.2 For boilers equipped with two-stage or step-modulating
controls, the national average number of burner operating hours at the
reduced operating mode (BOHR) is defined as:
BOHR = XR (2080)(0.77)[(QOUT/1,000)/
(1+[alpha])](AR)-2080(BR)
Where:
XR = as defined in section 11.4.8.6 of SHRAE 103-2017
2080 = as defined in section 10.2.1.1 of this appendix
0.77 = as defined in section 10.2.1.1 of this appendix
QOUT = as defined in section 11.4.8.1.1 or 11.5.8.1.1 of
ASHRAE 103-2017
[alpha] = as defined in section 11.4.8.2 of ASHRAE 103-2017
AR = 100,000/[341,200(yP,RPER +
yIG,RPEIG + yRBER) +
(QIN,R-QP) EffyU,R] for forced
draft unit, indoors; and
= 100,000/[341,200(yP,RPER (1-
Effmotor) + yIG,RPEIG +
yRBER) + (QIN,R-QP)
EffyU,R] for induced draft unit, indoors
BR = 2QP (EffyU,R) (AR)/
100,000
100,000 = conversion factor accounting for percent and 1,000 Btu/
kBtu
341,200 = conversion factor accounting for percent and 3412 Btu/h/kW
yP,R = 1 + (tp/tON,R) for two-stage
and step modulating boilers with post purge
PER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
yIG,R = tIG/tON,R
PEIG = as defined in section 8.3 of this appendix
yR = 1 + (t\+\)/tON,R for two-stage and step
modulating boilers with fan delay
BER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
QIN,R = as defined in section 11.4.8.1.2 of ASHRAE 103-
2017
QP = as defined in section 11.4.12 of ASHRAE 103-2017
EffyU,R = as defined in section 11.4.11.1 or 11.5.11.1 of
ASHRAE 103-2017, and calculated on the basis of:
indoor installation, for non-weatherized boilers; or
outdoor installation, for boilers that are weatherized.
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not provided
by the manufacturer.
10.2.1.3 For boilers equipped with two-stage controls, the national
average number of burner operating hours at the maximum operating mode
(BOHH) is defined as:
BOHH = XH (2080)(0.77)[(QOUT/1,000)/
(1+[alpha])](AH)--2080(BH)
Where:
XH = as defined in section 11.4.8.5 of SHRAE 103-2017
2080 = as defined in section 10.2.1.1 of this appendix
0.77 = as defined in section 10.2.1.1 of this appendix
QOUT = as defined in section 11.4.8.1.1 or 11.5.8.1.1
ofASHRAE 103-2017
[alpha] = as defined in section 11.4.8.2 of ASHRAE 103-2017
AH = 100,000/[341,200(yP,HPEH +
yIG,HPEIG + yHBEH) +
(QIN,H--QP) EffyU,H] for forced
draft unit, indoors; and
= 100,000/[341,200(yP,HPEH (1--
Effmotor) + yIG,HPEIG +
yHBEH) + (QIN,H--QP)
EffyU,H] for induced draft unit, indoors
BH = 2QP (EffyU,H) (AH)/
100,000
100,000 = conversion factor accounting for percent and 1,000 Btu/
kBtu
341,200 = conversion factor accounting for percent and 3412 Btu/h/kW
yP,H = 1 + (tp/tON,H) for two-stage
and step modulating boilers with post purge
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
yIG,H = tIG/tON,H
PEIG = as defined in section 8.3 of this appendix
yH = 1 + (t\+\)/tON,H for two-stage and step
modulating boilers with fan delay
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
QIN,H = as defined in section 11.4.8.1.1 of ASHRAE 103-
2017
QP = as defined in section 11.4.12 of ASHRAE 103-2017
EffyU,H = as defined in section 11.4.11.2 or 11.5.11.2 of
ASHRAE 103-2017, and calculated on the basis of:
indoor installation, for non-weatherized boilers; or
outdoor installation, for boilers that are weatherized.
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not provided
by the manufacturer.
10.2.1.4 For boilers equipped with step-modulating controls, the
national average number of burner operating hours at the modulating
operating mode (BOHM) is defined as:
BOHM = XH (2080)(0.77)[(QOUT/1,000)/
(1+[alpha])](AM)--2080(BM)
Where:
XH = as defined in section 11.4.8.5 of ASHRAE 103-2017
2080 = as defined in section 10.2.1.1 of this appendix
0.77 = as defined in section 10.2.1.1 of this appendix
QOUT = as defined in section 11.4.8.1.1 or 11.5.8.1.1 of
ASHRAE 103-2017
[alpha] = as defined in section 11.4.8.2 of ASHRAE 103-2017
AM = 100,000/[341,200(yP,HPEH +
yIG,HPEIG + yHBEH) +
(QIN,M--QP) EffyU,M] for forced
draft unit, indoors; and
= 100,000/[341,200(yP,HPEH (1--
Effmotor) + yIG,HPEIG +
yHBEH) + (QIN,M--QP)
EffyU,M] for induced draft unit, indoors
BM = 2QP (EffyU,M) (AM)/
100,000
100,000 = conversion factor accounting for percent and 1,000 Btu/
kBtu
341,200 = conversion factor accounting for percent and 3412 Btu/h/kW
yP,H = 1 + (tp/tON,H) for two-stage
and step modulating boilers with post purge
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
yIG,H = tIG/tON,H
PEIG = as defined in section 8.3 of this appendix
yH = 1 + (t\+\)/tON,H for two-stage and step
modulating boilers with fan delay
[[Page 15553]]
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
QIN,M = (100)(QOUT,M/EffySS,M)
QOUT,M = as defined in section 11.4.8.9 or 11.5.8.9 of
ASHRAE 103-2017
EffySS,M = value as defined in section 11.4.8.7 or
11.5.8.7 of ASHRAE 103-2017
QP = as defined in section 11.4.12 of ASHRAE 103-2017
EffyU,M = as defined in section 11.4.9.2.3 or 11.5.9.2.3
of ASHRAE 103-2017, and calculated on the basis of:
indoor installation, for non-weatherized boilers; or
outdoor installation, for boilers that are weatherized.
Effmotor = nameplate power burner motor efficiency
provided by the manufacturer,
= 0.50, an assumed default power burner efficiency if not provided
by the manufacturer.
10.2.2 Average annual fuel energy consumption for gas or oil fueled
boilers.
10.2.2.1 For boilers equipped with single-stage controls, the
average annual fuel energy consumption (EF) is expressed in
Btu per year and defined as:
EF = BOHSS (QIN - QP) +
8,760 QP
Where:
BOHSS = as defined in section 10.2.1.1 of this appendix
QIN = as defined in section 11.2.8.1 of ASHRAE 103-2017
QP = as defined in section 11.2.11 of ASHRAE 103-2017
8,760 = total number of hours per year.
10.2.2.2 For boilers equipped with either two-stage or step
modulating controls, EF is defined as follows. For two-stage
control:
EF = (BOHH)(QIN) +
(BOHR)(QIN,R) + [8760 - (BOHH +
BOHR)]QP
For step-modulating control:
EF = (BOHM)(QIN,M) +
(BOHR)(QIN,R) + [8760 - (BOHH +
BOHR)]QP
Where:
BOHH = as defined in section 10.2.1.3 of this appendix
BOHR = as defined in section 10.2.1.2 of this appendix
BOHM = as defined in section 10.2.1.4 of this appendix
QIN = as defined in section 11.2.8.1 of ASHRAE 103-2017
QIN,R = as defined in section 11.4.8.1.2 of ASHRAE 103-
2017
QIN,M = as defined in section 10.2.1.4 of this appendix
8,760 = total number of hours per year
QP = as defined in section 11.2.11 of ASHRAE 103-2017.
10.2.3 Average annual auxiliary electrical energy consumption for
gas or oil-fueled boilers.
10.2.3.1 For boilers equipped with single-stage controls, the
average annual auxiliary electrical consumption (EAE) is
expressed in kilowatt-hours and defined as:
EAE = BOHSS (yP PE + yIG
PEIG + yBE) + ESO
Where:
BOHSS = as defined in section 10.2.1.1 of this appendix
yP = as defined in section 10.2.1.1 of this appendix
PE = as defined in section 10.2.1.1 of this appendix
yIG = as defined in section 10.2.1.1 of this appendix
PEIG = as defined in section 10.2.1.1 of this appendix
y = as defined in section 10.2.1.1 of this appendix
BE = as defined in section 10.2.1.1 of this appendix
ESO = as defined in section 10.7 of this appendix.
10.2.3.2 For boilers equipped with two-stage controls,
EAE is defined as:
EAE = BOHR (yP,R PER +
yIG,R PEIG + yRBER) +
BOHH (yP,H PEH + yIG,H
PEIG + yHBEH) + ESO
Where:
BOHR = as defined in section 10.2.1.2 of this appendix
yP,R = as defined in section 10.2.1.2 of this appendix
PER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
yIG,R = as defined in section 10.2.1.2 of this appendix
PEIG = as defined in section 10.2.1.1 of this appendix
yR = as defined in section 10.2.1.2 of this appendix
BER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
BOHH = as defined in section 10.2.1.3 of this appendix
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
yP,H = as defined in section 10.2.1.3 of this appendix
yIG,H = as defined in section 10.2.1.3 of this appendix
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
yH = as defined in section 10.2.1.3 of this appendix
ESO = as defined in section 10.7 of this appendix.
10.2.3.3 For boilers equipped with step-modulating controls,
EAE is defined as:
EAE = BOHR (yP,R PER +
yIG,R PEIG + yR BER) +
BOHM (yP,H PEH + yIG,H
PEIG + yHBEH) + ESO
Where:
BOHR = as defined in section 10.2.1.2 of this appendix
yP,R = as defined in section 10.2.1.2 of this appendix
PER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
yIG,R = as defined in section 10.2.1.2 of this appendix
PEIG = as defined in section 10.2.1 of this appendix
yR = as defined in section 10.2.1.2 of this appendix
BER = as defined in section 8.2 of this appendix and
measured at the reduced fuel input rate
BOHM = as defined in 10.2.1.4 of this appendix
yP,H = as defined in section 10.2.1.3 of this appendix
PEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
yIG,H = as defined in section 10.2.1.3 of this appendix
yH = as defined in section 10.2.1.3 of this appendix
BEH = as defined in section 8.2 of this appendix and
measured at the maximum fuel input rate
ESO = as defined in section 10.7 of this appendix.
10.3 Average annual electric energy consumption for electric
boilers. For electric boilers, the average annual electrical energy
consumption (EE) is expressed in kilowatt-hours and defined
as:
EE = 100 (2,080) (0.77) [QOUT/(1+[alpha])]/(3412
AFUE) + ESO
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.2.1.1 of this appendix
0.77 = as defined in section 10.2.1.1 of this appendix
QOUT = as defined in section 11.2.8 of ASHRAE 103-2017
[alpha] = as defined in section 11.2.8.2 of ASHRAE 103-2017
3412 = conversion factor from kilowatt-hours to Btu
AFUE = as defined in section 11.1 of ASHRAE 103-2017, in percent,
and calculated on the basis of:
indoor installation, for non-weatherized boilers; or
outdoor installation, for boilers that are weatherized.
ESO = as defined in section 10.7 of this appendix.
10.4 Energy factor.
10.4.1 Energy factor for gas or oil boilers. Calculate the energy
factor, EF, for gas or oil boilers defined as, in percent:
EF = (EF - 4,600 (QP))(EffyHS)/
(EF + 3,412 (EAE))
Where:
EF = average annual fuel consumption as defined in
section 10.2.2 of this appendix
4,600 = as defined in section 11.4.12 of ASHRAE 103-2017
QP = pilot fuel input rate determined in accordance with
section 9.2 of ASHRAE 103-2017 in Btu/h
[[Page 15554]]
EffyHS = annual fuel utilization efficiency as defined in
sections 11.2.11, 11.3.11, 11.4.11 or 11.5.11 of ASHRAE 103-2017, in
percent, and calculated on the basis of:
indoor installation, for non-weatherized boilers; or
outdoor installation, for boilers that are weatherized.
3,412 = conversion factor from kW to Btu/h
EAE = as defined in section 10.2.3 of this appendix.
10.4.2 Energy factor for electric boilers. The energy factor, EF, for
electric boilers is defined as:
EF = AFUE
Where:
AFUE = annual fuel utilization efficiency as defined in section 10.3
of this appendix, in percent.
10.5 Average annual energy consumption for boilers located in a
different geographic region of the United States and in buildings with
different design heating requirements.
10.5.1 Average annual fuel energy consumption for gas or oil-fueled
boilers located in a different geographic region of the United States
and in buildings with different design heating requirements. For gas or
oil-fueled boilers, the average annual fuel energy consumption for a
specific geographic region and a specific typical design heating
requirement (EFR) is expressed in Btu per year and defined
as:
EFR = (EF - 8,760 QP) (HLH/2,080) +
8,760 QP
Where:
EF = as defined in section 10.2.2 of this appendix
8,760 = as defined in section 10.2.2 of this appendix
QP = as defined in section 11.2.11 of ASHRAE 103-2017
HLH = heating load hours for a specific geographic region determined
from the heating load hour map in Figure 1 of this appendix
2,080 = as defined in section 10.2.1.1 of this appendix.
10.5.2 Average annual auxiliary electrical energy consumption for
gas or oil-fueled boilers located in a different geographic region of
the United States and in buildings with different design heating
requirements. For gas or oil-fueled boilers, the average annual
auxiliary electrical energy consumption for a specific geographic
region and a specific typical design heating requirement
(EAER) is expressed in kilowatt-hours and defined as:
EAER = (EAE-ESO) (HLH/2080) +
ESOR
Where:
EAE = as defined in section 10.2.3 of this appendix
ESO = as defined in section 10.7 of this appendix
HLH = as defined in section 10.5.1 of this appendix
2,080 = as defined in section 10.2.1.1 of this appendix
ESOR = as defined in section 10.5.3 of this appendix.
10.5.3 Average annual electric energy consumption for electric
boilers located in a different geographic region of the United States
and in buildings with different design heating requirements. For
electric boilers, the average annual electric energy consumption for a
specific geographic region and a specific typical design heating
requirement (EER) is expressed in kilowatt-hours and defined
as:
EER = 100 (0.77) [QOUT/(1+[alpha])] HLH/(3.412
AFUE) + ESOR
Where:
100 = as defined in section 10.2.3 of this appendix
0.77 = as defined in section 10.2.1.1 of this appendix
QOUT = as defined in section 11.2.8.1 of ASHRAE 103-2017
[alpha] = as defined in section 11.2.8.2 of ASHRAE 103-2017
HLH = as defined in section 10.5.1 of this appendix
3.412 = as defined in section 10.2.3 of this appendix
AFUE = as defined in section 10.2.3 of this appendix
ESOR = ESO as defined in section 10.7 of this
appendix, except that in the equation for ESO, the term
BOH is multiplied by the expression (HLH/2080) to get the
appropriate regional accounting of standby mode and off mode loss.
10.6 [Reserved]
10.7 Average annual electrical standby mode and off mode energy
consumption. Calculate the annual electrical standby mode and off mode
energy consumption (ESO) in kilowatt-hours, defined as:
ESO = (PW,SB (4160-BOH) + 4600 PW,OFF)
K
Where:
PW,SB = boiler standby mode power, in watts, as measured
in section 8.9.1 of this appendix
4,160 = average heating season hours per year
BOH = total burner operating hours as calculated in section 10.2 of
this appendix for gas or oil-fueled boilers. Where for gas or oil-
fueled boilers equipped with single-stage controls, BOH =
BOHSS; for gas or oil-fueled boilers equipped with two-
stage controls, BOH = (BOHR + BOHH); and for
gas or oil-fueled boilers equipped with step-modulating controls,
BOH = (BOHR + BOHM). For electric boilers, BOH
= 100(2080)(0.77)[QOUT/(1+[alpha])]/(Ein
3412(AFUE))
4,600 = as defined in section 11.4.12 of ASHRAE 103-2017
PW,OFF = boiler off mode power, in watts, as measured in
section 8.9.2 of this appendix
K = 0.001 kWh/Wh, conversion factor from watt-hours to kilowatt-
hours
Where:
100 = to express a percent as a decimal
2,080 = as defined in section 10.2.1.1 of this appendix
0.77 = as defined in section 10.2.1.1 of this appendix
QOUT = as defined in section 11.2.8 of ASHRAE 103-2017
[alpha] = as defined in section 11.2.8.2 of ASHRAE 103-2017
Ein = steady-state electric rated power, in kilowatts,
from section 9.3 of ASHRAE 103-2017
3412 = as defined in section 10.3 of this appendix
AFUE = as defined in section 11.1 of ASHRAE 103-2017 in percent.
BILLING CODE 6450-01-P
[[Page 15555]]
[GRAPHIC] [TIFF OMITTED] TR13MR23.006
[FR Doc. 2023-03982 Filed 3-10-23; 8:45 am]
BILLING CODE 6450-01-C