Energy Conservation Program: Test Procedure for Automatic Commercial Ice Makers, 65856-65902 [2022-22927]
Download as PDF
65856
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE–2017–BT–TP–0006]
RIN 1904–AD81
Energy Conservation Program: Test
Procedure for Automatic Commercial
Ice Makers
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Final rule.
AGENCY:
In this final rule, the U.S.
Department of Energy (‘‘DOE’’) amends
the test procedure for automatic
commercial ice makers to update
incorporated references to the latest
version of the industry standards;
establish a relative humidity test
condition; provide additional detail
regarding certain test conditions,
settings, setup requirements, and
calculations; include a voluntary
measurement of potable water use;
clarify certification and reporting
requirements; and add enforcement
provisions. This final rule also provides
additional detail to the DOE test
procedure to improve the
representativeness and repeatability of
the current test procedure.
DATES: The effective date of this rule is
December 1, 2022. The final rule
changes will be mandatory for
equipment testing starting October 27,
2023. The incorporation by reference of
certain publications listed in the rule is
approved by the Director of the Federal
Register on December 1, 2022.
ADDRESSES: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts,
comments, and other supporting
documents/materials, is available for
review at www.regulations.gov. All
documents in the docket are listed in
the www.regulations.gov index.
However, not all documents listed in
the index may be publicly available,
such as those containing information
that is exempt from public disclosure.
A link to the docket web page can be
found at www.regulations.gov/docket/
EERE-2017-BT-TP-0006. The docket
web page contains instructions on how
to access all documents, including
public comments, in the docket.
For further information on how to
review the docket contact the Appliance
and Equipment Standards Program staff
at (202) 287–1445 or by email:
ApplianceStandardsQuestions@
ee.doe.gov.
lotter on DSK11XQN23PROD with RULES2
SUMMARY:
FOR FURTHER INFORMATION CONTACT:
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
Ms. Julia Hegarty, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, EE–2J, 1000
Independence Avenue SW, Washington,
DC 20585–0121. Telephone: (202) 586–
0729. Email:
ApplianceStandardsQuestions@
ee.doe.gov.
Ms. Sarah Butler, U.S. Department of
Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue SW,
Washington, DC 20585–0121.
Telephone: (202) 586–1777. Email:
Sarah.Butler@hq.doe.gov.
SUPPLEMENTARY INFORMATION: DOE
incorporates by reference the following
industry standards into part 431:
AHRI Standard 810 (I–P)–2016 with
Addendum 1, ‘‘Performance Rating of
Automatic Commercial Ice-Makers,’’
January 2018; and
ANSI/ASHRAE Standard 29–2015,
‘‘Method of Testing Automatic Ice
Makers,’’ approved April 30, 2015.
AHRI standards can be obtained from
the Air-Conditioning, Heating, and
Refrigeration Institute (AHRI), 2111
Wilson Blvd., Suite 500, Arlington, VA
22201, 703–524–8800, ahri@ahrinet.org,
or www.ahrinet.org.
ASHRAE standards can be purchased
from the American Society of Heating,
Refrigerating and Air-Conditioning
Engineers, Inc. (ASHRAE), 1791 Tullie
Circle NE, Atlanta, GA 30329, (404)
636–8400, ashrae@ashrae.org, or
www.ashrae.org. (Co-published with
American National Standards Institute
(ANSI).)
For a further discussion of these
standards, see section IV.N of this
document.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Scope
B. Definitions
1. Refrigerated Storage ACIM
2. Portable ACIM
3. Industry Standard Definitions
C. Industry Test Standards Incorporated by
Reference
D. Additional Amendments
1. Low-Capacity ACIMs
2. Stability Criteria
3. Test Conditions
4. Test Setup and Equipment
Configurations
5. Modulating Capacity Ice Makers
6. Standby Energy Use and Energy Use
Associated With Ice Storage
7. Calculations and Rounding
Requirements
8. Potable Water Use
E. Representations of Energy Use and
Energy Efficiency
PO 00000
Frm 00002
Fmt 4701
Sfmt 4700
1. Sampling Plan and Determination of
Represented Values
2. Test Sample Value Rounding
Requirements
3. Enforcement Provisions
F. Test Procedure Costs and Harmonization
1. Test Procedure Costs and Impact
2. Harmonization With Industry Standards
G. Effective and Compliance Dates
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866
and 13563
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by
Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Automatic commercial ice makers
(‘‘ACIMs’’ or ‘‘ice makers’’) are included
in the list of ‘‘covered equipment’’ for
which the U.S. Department of Energy
(‘‘DOE’’) is authorized to establish and
amend energy conservation standards
and test procedures. (42 U.S.C.
6311(1)(F)) DOE’s energy conservation
standards and test procedures for
ACIMs are currently prescribed at 10
CFR 431.136 and 431.134, respectively.
The following sections discuss DOE’s
authority to establish test procedures for
ACIMs and relevant background
information regarding DOE’s
consideration of test procedures for this
equipment.
A. Authority
The Energy Policy and Conservation
Act, as amended (‘‘EPCA’’),1 authorizes
DOE to regulate the energy efficiency of
a number of consumer products and
certain industrial equipment. (42 U.S.C.
6291–6317) Title III, Part C 2 of EPCA
established the Energy Conservation
Program for Certain Industrial
Equipment, which sets forth a variety of
provisions designed to improve energy
1 All references to EPCA in this document refer
to the statute as amended through the Energy Act
of 2020, Public Law 116–260 (Dec. 27, 2020), which
reflect the last statutory amendments that impact
Parts A and A–1 of EPCA.
2 For editorial reasons, upon codification in the
U.S. Code, Part C was redesignated Part A–1.
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
efficiency. This equipment includes
ACIMs, the subject of this document.
(42 U.S.C. 6311(1)(F))
The energy conservation program
under EPCA consists essentially of four
parts: (1) testing, (2) labeling, (3) Federal
energy conservation standards, and (4)
certification and enforcement
procedures. Relevant provisions of
EPCA specifically include definitions
(42 U.S.C. 6311), test procedures (42
U.S.C. 6314), labeling provisions (42
U.S.C. 6315), energy conservation
standards (42 U.S.C. 6313), and the
authority to require information and
reports from manufacturers (42 U.S.C.
6316; 42 U.S.C. 6296).
The Federal testing requirements
consist of test procedures that
manufacturers of covered equipment
must use as the basis for: (1) certifying
to DOE that their equipment complies
with the applicable energy conservation
standards adopted pursuant to EPCA (42
U.S.C. 6316(a); 42 U.S.C. 6295(s)), and
(2) making other representations about
the efficiency of that equipment (42
U.S.C. 6314(d)). Similarly, DOE must
use these test procedures to determine
whether the equipment complies with
relevant standards promulgated under
EPCA. (42 U.S.C. 6316(a); 42 U.S.C.
6295(s))
Federal energy efficiency
requirements for covered equipment
established under EPCA generally
supersede State laws and regulations
concerning energy conservation testing,
labeling, and standards. (42 U.S.C.
6316(a) and 42 U.S.C. 6316(b); 42 U.S.C.
6297) DOE may, however, grant waivers
of Federal preemption for particular
State laws or regulations, in accordance
with the procedures and other
provisions of EPCA. (42 U.S.C.
6316(b)(2)(D))
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered equipment.
EPCA requires that any test procedures
prescribed or amended under this
section must be reasonably designed to
produce test results which reflect energy
efficiency, energy use, or estimated
annual operating cost of a given type of
covered equipment during a
representative average use cycle (as
determined by the Secretary) and
requires that test procedures not be
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
EPCA prescribed the first Federal test
procedure for ACIMs, directing that the
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
ACIM test procedure shall be the AHRI
Standard 810–2003, ‘‘Performance
Rating of Automatic Commercial IceMakers’’ (‘‘AHRI Standard 810–2003’’).
(42 U.S.C. 6314(a)(7)(A)) EPCA requires
if AHRI Standard 810–2003 is amended,
that DOE must amend the Federal test
procedures as necessary to be consistent
with the amended AHRI standard,
unless DOE determines, by rule,
published in the Federal Register and
supported by clear and convincing
evidence, that to do so would not meet
the requirements for test procedures to
be representative of actual energy
efficiency and to not be unduly
burdensome to conduct. (42 U.S.C.
6314(a)(7)(B)(i))
EPCA also requires that, at least once
every 7 years, DOE evaluate test
procedures for each type of covered
equipment, including ACIMs, to
determine whether amended test
procedures would more accurately or
fully comply with the requirements for
the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 6314(a)(1))
If the Secretary determines, on her
own behalf or in response to a petition
by any interested person, that a test
procedure should be prescribed or
amended, the Secretary shall promptly
publish in the Federal Register
proposed test procedures and afford
interested persons an opportunity to
present oral and written data, views,
and arguments with respect to such
procedures. The comment period on a
proposed rule to amend a test procedure
shall be at least 60 days and may not
exceed 270 days. In prescribing or
amending a test procedure, the
Secretary shall take into account such
information as the Secretary determines
relevant to such procedure, including
technological developments relating to
energy use or energy efficiency of the
type (or class) of covered products
involved. (42 U.S.C. 6293(b)(2)) If DOE
determines that test procedure revisions
are not appropriate, DOE must publish
its determination not to amend the test
procedures.
DOE is publishing this final rule in
satisfaction of the 7-year review
requirement specified in EPCA. (42
U.S.C. 6314(b)(1))
PO 00000
Frm 00003
Fmt 4701
Sfmt 4700
65857
B. Background
DOE’s existing test procedures for
ACIMs appear at title 10 of the Code of
Federal Regulations (‘‘CFR’’), part 431,
§ 431.134.
On March 19, 2019, DOE published a
request for information (‘‘RFI’’) to solicit
comment and information to inform
DOE’s determination of whether to
propose amendments to the current
ACIM test procedure. 84 FR 9979
(‘‘March 2019 RFI’’). Following the RFI
and in consideration of the comments
received, DOE published a notice of
proposed rulemaking (‘‘NOPR’’) on
December 21, 2021, to seek feedback on
initial proposals. 86 FR 72322
(‘‘December 2021 NOPR’’). In the
December 2021 NOPR, DOE proposed
the following amendments to the test
procedure:
(1) Updating the referenced methods
of test to AHRI Standard 810 (I–P)–2016
with Addendum 1 and ASHRAE
Standard 29–2015, except for the
provisions as discussed;
(2) Including definitions and test
requirements for low-capacity ACIMs;
(3) Incorporating changes to improve
test procedure representativeness,
accuracy, and precision, which include:
clarifying calorimeter constant test
instructions; specifying ambient
temperature measurement requirements;
establishing a relative humidity test
condition; establishing an allowable
range of water hardness; clarifying the
stability requirements that were updated
in ASHRAE Standard 29–2015;
clarifying water pressure requirements;
and increasing the tolerance on capacity
collection time;
(4) Specifying certain test settings,
conditions, and installations, including:
clarifying ice hardness test conditions;
clarifying baffle use for testing;
amending clearance requirements;
clarifying automatic purge control
settings; and providing instructions for
testing ACIMs with automatic
dispensers;
(5) Including voluntary provisions for
measuring potable water use;
(6) Including clarifying language for
calculations, rounding requirements,
sampling plan calculations, and
certification instructions; and
(7) Adding language to the
equipment-specific enforcement
provisions.
DOE received comments in response
to the December 2021 NOPR from the
interested parties listed in Table I.1.
E:\FR\FM\01NOR2.SGM
01NOR2
65858
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
TABLE I.1—LIST OF COMMENTERS WITH WRITTEN SUBMISSIONS IN RESPONSE TO THE DECEMBER 2021 NOPR
Comment No.
in the docket
Commenter(s)
Reference in this final rule
Air-Conditioning, Heating, and Refrigeration Institute
Appliance Standards Awareness Project; American
Council for an Energy-Efficient Economy; Natural
Resources Defense Council.
Hoshizaki America, Inc ...............................................
Mile High Equipment Co. DBA Ice-O-Matic ...............
Pacific Gas and Electric Company; San Diego Gas
and Electric; and Southern California Edison; collectively, the California Investor-Owned Utilities.
Association of Home Appliance Manufacturers .........
AHRI ...............................................
ASAP, ACEEE, NRDC (Joint Commenters).
13
15
Trade Association.
Efficiency Advocacy Organizations.
Hoshizaki ........................................
Ice-O-Matic (IOM) ..........................
CA IOUs .........................................
14
11
16
Manufacturer.
Manufacturer.
Utilities.
AHAM .............................................
318
A parenthetical reference at the end of
a comment quotation or paraphrase
provides the location of the item in the
public record.4
II. Synopsis of the Final Rule
In this final rule, DOE amends the
representation provisions, productspecific enforcement provisions, and
test procedure for ACIMs as follows:
(1) Updating the referenced methods
of test to AHRI Standard 810 (I–P)–2016
with Addendum 1 and ASHRAE
Standard 29–2015, except for the
provisions as discussed;
(2) Including definitions and test
requirements for low-capacity ACIMs;
(3) Incorporating changes to improve
test procedure representativeness,
accuracy, and precision, which include:
clarifying calorimeter constant test
instructions; specifying ambient
temperature measurement requirements;
establishing a relative humidity test
condition; clarifying the stability
requirements that were updated in
ASHRAE Standard 29–2015; and
clarifying water pressure requirements;
(4) Specifying certain test settings,
conditions, and installations, including:
clarifying ice hardness test conditions;
clarifying baffle use for testing;
amending clearance requirements;
clarifying automatic purge control
Commenter type
Trade Association.
settings; and providing instructions for
testing ACIMs with automatic
dispensers;
(5) Including voluntary provisions for
measuring potable water use;
(6) Including clarifying language for
calculations, rounding requirements,
sampling plan calculations, and
certification instructions; and
(7) Adding language to the
equipment-specific enforcement
provisions.
The adopted amendments are
summarized in Table II.1 compared to
the test procedure provisions prior to
the amendment, as well as the reason
for the adopted change.
TABLE II.1—SUMMARY OF CHANGES ESTABLISHED IN THIS FINAL RULE
Current DOE approach
Amended approach
References industry standard AHRI Standard 810–
2007 with Addendum 1 ‘‘2007 Standard for Performance Rating of Automatic Commercial Ice
Makers’’ (‘‘AHRI Standard 810–2007’’), which refers to ANSI/ASHRAE Standard 29–2009 ‘‘Method
of Testing Automatic Ice Makers,’’ (including Errata
Sheets issued April 8, 2010 and April 21, 2010),
approved January 28, 2009 (‘‘ASHRAE Standard
29–2009’’).
Scope includes ACIMs with capacities between 50
and 4,000 lb/24 h.
Updates reference to industry standard AHRI Standard 810 (I–P)–2016 with Addendum 1, which refers to ASHRAE Standard 29–2015.
Adopts latest industry standards.
Includes definitions for low-capacity ACIMs and expands test procedure scope to include low-capacity ACIMs with capacity less than or equal to 50
lb/24 h; includes additional instructions to allow
for testing low-capacity ACIMs.
Specifies that the harvested ice used to determine
the ice hardness factor must be produced at the
Standard Rating Conditions presented in section
5.1.2 of AHRI Standard 810 (I–P)–2016 with Addendum 1.
Specifies that the temperature measurement location must be at approximately the geometric center of the block of ice and that any liquid water on
the block of ice must be wiped off the surface
prior to placement in the calorimeter.
Ensures representative, repeatable, and reproducible measures of performance for ACIMs
currently not in scope.
Does not specify the ambient & water temperature
and water pressure when harvesting ice to be
used in determining the ice hardness factor.
lotter on DSK11XQN23PROD with RULES2
Does not specify where to measure the temperature
of the ice block used to determine the calorimeter
constant.
3 DOE received AHAM’s late comment on
September 1, 2022, which was past the comment
deadline of February 22, 2022. Although this
comment was received 191 days after the close of
the comment period, DOE has included the
comment and responses in this final rule. AHAM
indicated it did not file timely comments on the
proposed test procedure because AHAM was not
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
aware that the proposed test procedure included
AHAM products in its scope. DOE has determined
that AHAM’s comments may provide a unique
stakeholder perspective not included in other
comments received during this rulemaking, and
therefore DOE has considered them in this final rule
despite the late submission.
PO 00000
Frm 00004
Fmt 4701
Sfmt 4700
Attribution
Harmonizes with industry standard; improves representativeness, repeatability, and reproducibility.
Improves representativeness, repeatability, and reproducibility.
4 The parenthetical reference provides a reference
for information located in the docket of DOE’s
rulemaking to develop test procedures for ACIMs.
(Docket No. EERE–2017–BT–TP–0006, which is
maintained at www.regulations.gov) The references
are arranged as follows: (commenter name,
comment docket ID number, page of that
document).
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
65859
TABLE II.1—SUMMARY OF CHANGES ESTABLISHED IN THIS FINAL RULE—Continued
Current DOE approach
Amended approach
Attribution
Capacity measurements begin after the unit has
been stabilized.
All cycles or samples used for the capacity test
must meet the stability criteria.
Continuous ACIMs shall be considered stabilized
when the weights of three consecutive 14.4-minute
samples taken within a 1.5-hour period do not vary
by more than ±2 percent.
Continuous ACIMs shall be considered stabilized
when the weights of two consecutive 15.0 min ±
2.5 s samples having no more than 5 minutes between the end of a sample and the start of the
next sample do not vary more than ±2 percent or
0.055 pounds, whichever is greater.
Adds an average minimum relative humidity test
condition of 30.0 percent.
Incorporates existing guidance into the test procedure; allows for an alternate ambient measurement location instead of shielding the thermocouple and for rear clearances which are less
than the required inlet measurement distance.
ACIMs shall be tested according to the manufacturer’s specified minimum rear clearances requirements, or 3 feet from the rear of the ACIMs,
whichever is less; all other sides of the ACIMs
and all sides of the remote condensers, if applicable, shall be tested with a minimum clearance of
3 feet or the minimum clearance specified by the
manufacturer, whichever is greater.
Specifies that unweighted sensors shall be used for
all ambient temperature measurements.
Specifies that the water pressure shall be measured
within 8 inches of the ACIM and within the allowable range within 5 seconds of water flowing into
the ACIM.
Provides instruction to test certain ACIMs with an
automatic dispenser with an empty internal bin at
the start of the test and to allow for the continuous production and dispensing of ice, with samples collected from the dispenser through a conduit connected to an external bin one-half full of
ice.
Includes voluntary reference to potable water use in
10 CFR 431.134 based on AHRI Standard 810
(I–P)–2016 with Addendum 1.
Clarifies industry test procedure
(‘‘TP’’) to reduce test burden
while maintaining representative
results; harmonize with industry
standard.
Harmonizes with industry TP update.
Does not specify relative humidity test condition .......
Use of baffles and purge setting addressed in guidance..
ACIMs shall be tested with a clearance of 18 inches
on all four sides.
Does not specify use of weighted/unweighted sensors to measure ambient temperature.
Does not specify how to measure water inlet pressure requirements.
Does not specify how to collect capacity samples for
ACIMs with dispensers.
Does not specifically reference potable water usage
Rounds energy use in multiples of 0.1 kWh/100 lb
and harvest rate to the nearest 1 lb/24 h.
Rounds energy use in multiples of 0.01 kWh/100 lb;
rounds harvest rate to the nearest 0.1 lb/24 h for
ACIMs with harvest rates of 50 lb/24 h or less.
Does not specify if intermediate values used in calculations should be rounded.
Clarifies that the calculations of intermediate values
be performed with raw measured data and only
the final results be rounded; clarifies that the energy use, condenser water use, and potable
water use (if voluntarily measured) be calculated
by averaging the calculated values for the three
measured samples for each respective metric.
Specifies that the percent difference between two
measurements be calculated by taking the absolute difference between two measurements and
divide by the average of the two measurements.
Removes ‘‘maximum’’ from the referenced terms;
adds reference to condenser water use in sampling plan.
Modifies the term and definition of ‘‘maximum condenser water use’’ to instead refer to the term
‘‘condenser water use’’.
Removes ‘‘cube type ice’’ from 10 CFR 431.132; removes reference to cube type ice in the definition
of ‘‘batch type ice maker’’.
The represented value of harvest rate for the basic
model is determined as the mean of the harvest
rate for each tested unit.
Does not specify how to calculate the percent difference between two measurements.
lotter on DSK11XQN23PROD with RULES2
References ‘‘maximum energy use’’ and ‘‘maximum
condenser water use’’ at 10 CFR 429.45, no reference to water use in sampling plan.
Defines ‘‘maximum condenser water use’’ at 10 CFR
431.132.
Defines ‘‘cube type ice’’ at 10 CFR 431.132 ..............
Does not specify how the represented value of harvest rate for each basic model should be determined based on the test sample.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
PO 00000
Frm 00005
Fmt 4701
Sfmt 4700
E:\FR\FM\01NOR2.SGM
Improves representativeness, repeatability, and reproducibility.
Improves representativeness, repeatability, and reproducibility.
Improves representativeness, repeatability, and reproducibility
and updates certain requirements to harmonize with industry standard.
Improves representativeness, repeatability, and reproducibility.
Improves representativeness, repeatability, and reproducibility.
In response to waiver.
Harmonizes with industry standard; improves representativeness, repeatability, and reproducibility.
Harmonizes with latest industry
standard; improves representativeness, repeatability, and reproducibility.
Improves representativeness, repeatability, and reproducibility.
Improves representativeness, repeatability, and reproducibility.
Improves clarity.
Improves clarity.
Improves clarity.
Improves representativeness, repeatability, and reproducibility.
01NOR2
65860
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
TABLE II.1—SUMMARY OF CHANGES ESTABLISHED IN THIS FINAL RULE—Continued
Current DOE approach
Amended approach
Attribution
Does not specify rounding requirements for represented values in 10 CFR 429.45.
Specifies that represented values determined in 10
CFR 429.45 must be rounded consistent with the
test procedure rounding instructions, upon the
compliance date of any amended standards.
The certified harvest rate will be considered for determination of the energy consumption and condenser water use levels only if the average measured harvest rate is within five percent of the certified harvest rate, otherwise the measured harvest rate will be used to determine the applicable
standards.
Improves representativeness, repeatability, and reproducibility.
No equipment-specific enforcement provisions ..........
DOE has determined that while the
amendments will introduce additional
test requirements compared to the
current approach, any impact to the
measured efficiency of certified ACIMs
is expected to be de minimis. For lowcapacity ACIMs newly added within
scope of the test procedure, testing
according to the amended test
procedure for purposes of certifications
of compliance will not be required until
the compliance date of any energy
conservation standards for that
equipment. However, if a manufacturer
chooses to make representations of the
energy efficiency or energy use of a lowcapacity ACIM, beginning 360 days after
publication of the final rule in the
Federal Register, the manufacturer will
be required to base such representations
on the DOE test procedure. (42 U.S.C.
6314(d)(1)) While DOE does not expect
that manufacturers will incur additional
cost as a result of the amended test
procedure, DOE provides a discussion
of testing costs in section III.F.1 of this
final rule. DOE has also determined that
the amended test procedure will not be
unduly burdensome to conduct.
Discussion of DOE’s amendments are
addressed in detail in section III of this
final rule.
The effective date for the amended
test procedures adopted in this final
rule is 30 days after publication of this
document in the Federal Register.
Representations of energy use or energy
efficiency must be based by testing in
accordance with the amended test
procedures beginning 360 days after the
publication of this final rule.
III. Discussion
In the following sections, DOE
describes the amendments to the test
procedures for ACIMs. This reflects
DOE’s review of the updates to the
referenced industry test procedures, the
comments received in response to the
March 2019 RFI and the December 2021
NOPR, and other relevant information.
A. Scope
DOE defines automatic commercial
ice maker as a factory-made assembly
(not necessarily shipped in 1 package)
that: (1) consists of a condensing unit
and ice-making section operating as an
integrated unit, with means for making
and harvesting ice and (2) may include
means for storing ice, dispensing ice, or
Improves clarity.
storing and dispensing ice. 10 CFR
431.132 (see also, 42 U.S.C. 6311(19))
The current DOE test procedure for
ACIMs applies to both batch type and
continuous type ice makers 5 with
harvest rates between 50 and 4,000 lb/
24 h. DOE further subdivides the batch
type and continuous type equipment
ACIM categories into several distinct
equipment classes based on the
equipment configuration, condenser
cooling method, and harvest rate in
pounds per 24 hours (lb/24 h), as shown
in Table III.1. See also, 10 CFR
431.136(c) and (d). ACIM configurations
include ice-making heads, remote
condensing equipment (both with and
without a remote compressor), and selfcontained equipment. Ice-making heads
and self-contained equipment can be
either air- or water-cooled; however,
DOE prescribes standards only for
remote condensing equipment that are
air-cooled. Self-contained ACIMs
include a means for storing ice, while
ice-making heads and remote
condensing equipment are typically
paired with separate ice storage bins. At
10 CFR 431.132, DOE defines these
configurations, as well as several
metrics related to ACIMs.
TABLE III.1—SUMMARY OF ACIM EQUIPMENT CLASSES
Harvest rate
(lb/24 h)
Equipment configuration
Condenser cooling fluid
Ice-making mechanism
Ice-Making Head ............................
Water ............................................
Batch .............................................
Continuous ....................................
lotter on DSK11XQN23PROD with RULES2
Air .................................................
Batch .............................................
Continuous ....................................
5 A batch type ice maker is defined as an ice
maker that has alternate freezing and harvesting
periods, including ACIMs that produce cube type
ice and other batch technologies. 10 CFR 431.132.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
Batch type ice makers also produce tube type ice
and fragmented ice. A continuous type ice maker
is defined as an ice maker that continually freezes
and harvests ice at the same time. Id. Continuous
PO 00000
Frm 00006
Fmt 4701
Sfmt 4700
<300.
≥300 and <850.
≥850 and <1,500.
≥1,500 and <2,500.
≥2,500 and <4,000.
<801.
≥801 and >2,500.
≥2,500 and >4,000.
<300.
≥300 and >800.
≥800 and <1,500.
≥1,500 and <4,000.
<310.
type ice makers primarily produce flake and nugget
ice.
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
65861
TABLE III.1—SUMMARY OF ACIM EQUIPMENT CLASSES—Continued
Equipment configuration
Condenser cooling fluid
Remote-Condensing (but not remote compressor).
Air .................................................
Harvest rate
(lb/24 h)
Ice-making mechanism
Batch .............................................
Continuous ....................................
Remote-Condensing and Remote
Compressor.
Air .................................................
Batch .............................................
Continuous ....................................
Self-Contained ...............................
Water ............................................
Batch .............................................
Continuous ....................................
Air .................................................
Batch .............................................
lotter on DSK11XQN23PROD with RULES2
Continuous ....................................
The regulatory and statutory
definitions of ACIM are not limited by
harvest rate (i.e., capacity). (See 10 CFR
431.132 and 42 U.S.C. 6311(19),
respectively) However, the scope of
DOE’s test procedure is limited
explicitly to ACIMs with capacities
between 50 and 4,000 lb/24 h. 10 CFR
431.134(a). DOE is aware of ACIMs
available in the market with harvest
rates less than or equal to 50 lb/24 h
(hereafter referred to as ‘‘low-capacity
ACIMs’’).
DOE had previously considered test
procedures for low-capacity ACIMs in a
December 16, 2014, NOPR for test
procedures for miscellaneous
refrigeration products (‘‘MREFs’’). 79 FR
74894 (‘‘December 2014 MREF Test
Procedure NOPR’’).6 In a supplemental
notice of proposed determination
regarding miscellaneous refrigeration
products coverage, DOE noted that a
working group established to consider
test procedures and standards for
miscellaneous refrigeration products
made two observations: (1) ice makers
are fundamentally different from the
other product categories considered as
miscellaneous refrigeration products;
and (2) ice makers are covered as
commercial equipment and there is no
clear differentiation between consumer
and commercial ice makers. 81 FR
11454, 11456 (Mar. 4, 2016). In a 2016
final rule, DOE determined that ice
makers were significantly different from
the other product categories considered,
and ice makers were not included in the
6 Available at www.regulations.gov/
document?D=EERE-2013-BT-TP-0029-0011.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
scope of coverage or test procedure for
miscellaneous refrigeration products. 81
FR 46773 (July 18, 2016).
As discussed, EPCA defines ‘‘covered
equipment’’ to include certain types of
‘‘industrial equipment,’’ including
automatic commercial ice makers. 42
U.S.C. 6311(1). EPCA defines
‘‘industrial equipment’’ to mean
equipment, including automatic
commercial ice makers, (1) which in
operation consumes, or is designed to
consume, energy, (2) which, to any
significant extent, is distributed in
commerce for industrial or commercial
use; and (3) which is not a ‘‘covered
product’’ as defined in 42 U.S.C.
6291(a)(2), other than a component of a
covered product with respect to which
there is in effect a determination under
42 U.S.C. 6312(c); without regard to
whether such article is in fact
distributed in commerce for industrial
or commercial use. 42 U.S.C. 6311(2).
As discussed, the regulatory and
statutory definitions of ACIM are not
limited by harvest rate (see 10 CFR
431.132 and 42 U.S.C. 6311(19),
respectively) and low-capacity ACIMs
are not a covered product as defined in
42 U.S.C. 6291–6292. DOE has
determined that low-capacity ACIMs
are, to a significant extent, distributed in
commerce for commercial use. DOE
reviewed the low-capacity ACIM market
and found that manufacturers
specifically market certain low-capacity
ACIMs for commercial use and/or using
commercial air and water ambient rating
conditions (i.e., 90 °F air temperature
and 70 °F water temperature which are
the same air and water ambient rating
PO 00000
Frm 00007
Fmt 4701
Sfmt 4700
≥310 and >820.
≥820 and <4,000.
<988.
≥988 and <4,000.
<800.
≥800 and <4,000.
<930.
≥930 and <4,000.
<800.
≥800 and <4,000.
<200.
≥200 and <2,500.
≥2,500 and <4,000.
<900.
≥900 and <2,500.
≥2,500 and <4,000.
<110.
≥110 and <200.
≥200 and <4,000.
<200.
≥200 and <700.
≥700 and <4,000.
conditions used in DOE’s test
procedures for ACIMs currently
prescribed at 10 CFR 431.134) 7 and
distributors sell low-capacity ACIMs for
commercial use.8 As such,
notwithstanding that low-capacity
ACIMs may also be distributed in
commerce for personal use or
consumption by individuals, lowcapacity ACIMs meet the definition of
‘‘industrial equipment’’ and therefore
are covered under the EPCA definition
of ‘‘covered equipment.’’
In the December 2014 MREF Test
Procedure NOPR, DOE stated it is aware
that manufacturers are using the DOE
ACIM test procedure to represent the
energy use of consumer ice makers (i.e.,
7 See www.scotsman-ice.com/service/
Specs%20Sheets/2017/SIS-SS-CU0415_
0117%20LR.pdf, https://www.hoshizaki.com/docs/
color-specs/AM-50BAJ-(AD)DS.pdf, https://
www.hoshizaki.com/docs/color-specs/IM-50BAAQ.pdf, https://www.hoshizaki.com/docs/color-specs/
C-80BAJ-(AD)DS.pdf, https://
www.manitowocice.com/asset/?id=qsoqru&
regions=us&prefLang=en, https://www.scotsmanice.com/service/Specs%20Sheets/2018/SIS-SS-CUCU50_0118%20LR.pdf, https://iomstage.azurewebsites.net/getattachment/b06fdb7caaaa-4e5b-b5a6-b091e657a0d3/UCG060A-SpecSheet, and https://www.summitappliance.com/
catalog/model/BIM44GCSS.
8 See www.katom.com/cat/countertop-icemakers.html?brand=Danby, https://
www.katom.com/cat/undercounter-icemakers.html?suggested_
use=Commercial&production_range_
lb%2Fday=1%20-%2099%20lbs, https://
www.ckitchen.com/313767/ice-machine-withbin.html?filter=type-of-cooling:air-cooled;4-hrproduction:10-50lbs, https://
www.webstaurantstore.com/13283/undercounterice-machines.html?filter=24-hour-ice-yield:38∼102pounds, and www.staples.com/ice+maker/
directory_ice%2520maker.
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65862
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
low-capacity ACIMs). 79 FR 74894,
74916. DOE also stated that it is
unaware of any test procedure that has
been specifically developed for
consumer ice makers (i.e., low-capacity
ACIMs). Id.
In the December 2021 NOPR, DOE
proposed a test procedure for lowcapacity ACIMs and requested comment
on the proposal to include test
procedure provisions for low-capacity
ACIMs within the scope of the ACIM
test procedure. 86 FR 72322,72328.
In response to the December 2021
NOPR, the Joint Commenters responded
that there are many low-capacity models
on the market, and these units currently
are not subject to DOE efficiency
standards or test procedures. (Joint
Commenters, No. 15, p. 1)
The CA IOUs and the Joint
Commenters expressed support for
DOE’s proposal to include ACIMs with
daily harvest rates below 50 lb/day into
the scope of the test procedure, with the
Joint Commenters adding that this will
ensure any manufacturer claims about
capacity and efficiency will be based on
standardized test procedures to help
purchasers make informed choices. (CA
IOUs, No. 16, p. 1; Joint Commenters,
No. 15, p. 1)
The CA IOUs stated that they believe
extending the scope of the test
procedure to low-capacity ice makers is
a reasonable first step to a future
rulemaking to set minimum energy
efficiency standards for these lowcapacity ACIM units. (CA IOUs, No. 16,
p. 1)
Hoshizaki and AHRI stated that they
do not agree with adding provisions for
low-capacity ACIMs. (Hoshizaki, No. 14,
p. 1; AHRI, No. 13, p. 2) AHAM stated
that they do not agree with adding
provisions for low-capacity ACIMs to
the extent that they include consumer or
residential ice makers. (AHAM, No. 18,
p. 2) IOM stated that it supports the goal
of developing an industry standard to
allow for the consistent testing of lowcapacity ACIMs.. (IOM, No. 11, p. 1)
However, IOM, AHRI, and Hoshizaki
stated that such a standard should be
developed by an industry organization
(ASHRAE 29 or AHRI 810) to determine
proper methodology for consistent
testing. (IOM, No. 11, p. 1; AHRI, No.
13, p. 2; Hoshizaki, No. 14, p. 1)
AHAM stated that DOE first examined
establishing coverage for consumer
stand-alone ice makers as part of the
rulemaking to establish coverage for
miscellaneous refrigeration products.
(AHAM, No. 18, p. 2) AHAM noted that,
per the recommendation of an
Appliance Standards Rulemaking
Advisory Committee (ASRAC) working
group and its agreed-upon term sheet,
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
DOE declined to cover consumer standalone ice makers as part of that
rulemaking with the stated reasoning
that those products were too different
from the other products over which
DOE was proposing to establish
coverage under the miscellaneous
refrigeration product category. Id.
AHAM noted that the ASRAC
stakeholders never suggested or
determined that the difference between
stand-alone small capacity ice makers
and other miscellaneous refrigeration
products was that ice makers were
commercial equipment. (AHAM, No. 18,
p. 3)
AHAM stated that consumer standalone ice makers are not automatic
commercial ice makers. Id. AHAM
stated that Congress intended to include
only commercial products under the
scope of ‘‘automatic commercial ice
makers’’ as demonstrated by the word
‘‘commercial’’ and did not intend to
cover residential/consumer products. Id.
AHAM stated that, in EPCA, automatic
commercial ice makers are included in
42 U.S.C. Part A–1 for ‘‘Certain
Industrial Equipment’’, not Part A,
which is for ‘‘Consumer Products other
than Automobiles’’. Id. AHAM stated
that automatic commercial ice makers
fall under the EPCA definition of
‘‘covered equipment’’ which means that,
as a threshold matter, it is a type of
‘‘industrial equipment’’. Id. AHAM
commented that DOE’s guidance states
that ‘‘consumer products and industrial
equipment are mutually exclusive
categories. An appliance model can only
be considered commercial under the Act
if it does not fit the definition of
‘consumer product’ ’’.9 (AHAM, No. 18,
p. 4) AHAM states that stand-alone ice
makers that are capable of making 50
pounds per day or less more squarely fit
under DOE’s definition of a consumer
product and that residential ice makers
that fit under the counter or on the
countertop are regularly distributed in
commerce for personal use or
consumption by individuals. (AHAM,
No. 18, p. 3)
AHAM commented that there are
several distinguishing design features or
characteristics of stand-alone or undercounter ice makers with low capacities
including: space constraints, ice quality
(i.e., clear, cubed ice or nugget type ice),
countertop designs (portable ice makers
only), lack of connection to the water
supply (portable ice makers only),
infrequent and low ice usage, different
durability requirements, different
sanitary considerations, lack of
requirement for National Sanitation
9 See https://www1.eere.energy.gov/buildings/
appliance_standards/pdfs/cce_faq.pdf.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4700
Foundation (‘‘NSF’’) certifications/
listings, different manufacturer
warranties, and different safety
standards (i.e., Underwriters’
Laboratories (‘‘UL’’) 60335–2–89,
Particular Requirements for Commercial
Refrigerating Appliances and Ice makers
with an Incorporated or Remote
Refrigerant Unit or Motor-Compressor
and UL 60335–2–24, Particular
Requirements for Refrigerating
Appliances, Ice-Cream Appliances, and
Ice Makers). (AHAM, No. 18, p. 4–6)
Hoshizaki commented that
repeatability is key with low-production
models where one cube or chunk could
cause the test to be out of tolerance.
(Hoshizaki, No. 14, p. 1) Hoshizaki
stated that a very low-production
machine could have 31% stability
swings and could prove impossible to
meet the stability threshold in the
ASHRAE 29 test. Id.
In the December 2021 NOPR, DOE
also requested comment on whether
there are any industry test procedures
for testing and rating low-capacity
ACIMs, specifically asking about
features specific to low-capacity ACIMs
that might need addressed to produce
results representative of an average use
cycle. 86 FR 72322,72328.
Hoshizaki, AHRI, and AHAM
commented they are not aware of any
test procedures for low-capacity ice
makers. (Hoshizaki, No. 14, p. 1; AHRI,
No. 13, p. 2; AHAM, No. 18, p. 8) AHRI
and Hoshizaki added that a study would
be needed to determine a repeatable
process to accurately represent ice
capacity and energy use. Id. AHRI
recommended DOE bring this to the
ASHRAE Standard Project Committee
(‘‘SPC’’) 29 for consideration. (AHRI,
No. 13, p. 2)
As stated in the December 2021
NOPR, the energy performance of lowcapacity ACIMs are typically either not
specified or based on the existing ACIM
industry test procedures. 86 FR
72322,72328. However, the lack of a
DOE test procedure could allow for
manufacturers to make performance
claims using other unknown test
procedures, which could result in
inconsistent ratings from model to
model. Id.
DOE is still unaware of an industry
test procedure for testing and rating
low-capacity ACIMs. Manufacturers
continue to use the DOE ACIM test
procedure to represent the energy use of
low-capacity ACIMs or do not specify
the energy use. DOE acknowledges the
comments regarding including lowcapacity ACIMs within scope of
industry test standards and will
consider any updated industry test
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
standards, if available, during future
ACIM test procedure rulemakings.
DOE discusses stability requirements
for low-capacity ACIMs in section
III.D.1 of this final rule.
In response to AHAM’s comments
regarding low-capacity ACIMs, as
previously stated, EPCA defines
‘‘industrial equipment’’ to mean
equipment (1) which in operation
consumes, or is designed to consume,
energy, (2) which, to any significant
extent, is distributed in commerce for
industrial or commercial use; and (3)
which is not a ‘‘covered product’’ as
defined in 42 U.S.C. 6291(a)(2), other
than a component of a covered product
with respect to which there is in effect
a determination under 42 U.S.C.
6312(c); without regard to whether such
article is in fact distributed in commerce
for industrial or commercial use. 42
U.S.C. 6311(2). DOE has determined
that low-capacity ACIMs (1) consume
energy; (2) are, to a significant extent,
distributed in commerce for commercial
use; and (3) are not covered products.
As such, notwithstanding that lowcapacity ACIMs may also be distributed
in commerce for personal use or
consumption by individuals, lowcapacity ACIMs meet the definition of
‘‘industrial equipment’’ and therefore
are covered under the EPCA definition
of ‘‘covered equipment.’’ DOE has
determined that establishing a test
procedure for low-capacity ACIMs will
allow purchasers to make more
informed decisions regarding the
performance of low-capacity ACIMs.
DOE is amending the scope of the ACIM
test procedure to include all automatic
commercial ice makers with capacities
up to 4,000 lb/24 h (i.e., to include
within the scope of the test procedure,
low-capacity ACIMs with a harvest rate
less than 50 lb/24 h). Under the
amended test procedure, were a
manufacturer to choose to make
representations of the energy efficiency
or energy use of a low-capacity ACIM,
beginning 360 days after publication of
the final rule in the Federal Register,
manufacturers would be required to
base such representations on the DOE
test procedure. (42 U.S.C. 6314(d)(1))
B. Definitions
As noted, 10 CFR 431.132 provides
definitions concerning ACIMs. DOE
adds new definitions to support test
procedure amendments elsewhere in
this document, as discussed in the
following paragraphs.
1. Refrigerated Storage ACIM
Typical self-contained ACIMs have an
ice storage bin that is insulated but
provides no active refrigeration. As a
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
result, the ice melts at a certain rate and
the ice maker must periodically
replenish the melted ice. Conversely,
some self-contained low-capacity
ACIMs feature a refrigerated storage bin
that prevents melting of the stored ice.
Because of the additional refrigeration
system components, ACIMs with a
refrigerated storage bin (i.e., refrigerated
storage ACIMs) have different energy
use characteristics than ACIMs without
refrigerated storage.
In the December 2021 NOPR, DOE
proposed to define ‘‘refrigerated storage
automatic commercial ice maker’’ as an
automatic commercial ice maker that
has a refrigeration system that actively
refrigerates the self-contained storage
bin in 10 CFR 431.132 for refrigerated
storage ACIMs. 86 FR 72322, 72328.
In the December 2021 NOPR, DOE
requested comment on the proposed
definitions for refrigerated storage
automatic commercial ice maker. 86 FR
72322, 72328.
In response to the December 2021
NOPR, Hoshizaki commented that it is
not aware of any standard, selfcontained refrigerated storage
commercial ice makers. (Hoshizaki, No.
14, p. 1)
AHRI commented it was unable to
categorize this equipment class with the
information provided and would
appreciate clarification on this
equipment class and the desired intent
behind its potential inclusion. (AHRI,
No. 13, p. 2) Hoshizaki additionally
requested examples of this product, and
requested that this be addressed in
AHRI 810 and ASHRAE 29 for
definition. (Hoshizaki, No. 14, p. 1)
As stated in the December 2021
NOPR, DOE included a definition of
refrigerated storage ACIMs to effectively
differentiate refrigerated storage ACIMs
from ACIMs with unrefrigerated storage
bins, and to support the proposed test
provisions for refrigerated storage
ACIMs. 86 FR 72322, 72328. An
example of a refrigerated storage ACIM
is the Whynter UIM–155.10 To clarify
and provide more information on the
scope of the refrigerated storage ACIM
definition, DOE has added ‘‘ice’’ to the
definition to differentiate refrigerated
storage ACIMs from other refrigeration
equipment that is not intended only for
ice storage, so the phrase at the end of
the definition reads ‘‘self-contained ice
storage bin’’.
DOE will consider any updated
industry standards, if available, during
future ACIM test procedure
rulemakings.
10 See
PO 00000
www.whynter.com/product/uim-155/.
Frm 00009
Fmt 4701
Sfmt 4700
65863
DOE is modifying the definition of
refrigerated storage automatic
commercial ice maker in this final rule.
2. Portable ACIM
Some low-capacity ACIMs are
‘‘portable’’ and do not require
connection to water supply plumbing to
operate. Instead, these units contain a
reservoir that the user manually fills
with water prior to operation and must
refill when it becomes empty. In the
December 2014 MREF Test Procedure
NOPR, DOE proposed to define
‘‘portable ice maker’’ as an ice maker
that does not require connection to a
water supply and instead has one or
more reservoirs that would be manually
supplied with water. 79 FR 74894,
74916. DOE noted that the lack of a
fixed water connection and the small
size of these units contribute to their
portability. Id. DOE did not receive
comments on the proposed definition
for portable ice makers in response to
the December 2014 MREF Test
Procedure NOPR.
In the December 2021 NOPR, DOE
proposed a definition for a portable ice
maker as proposed in the December
2014 MREF Test Procedure NOPR, but
with additional specification that
ACIMs with an optional connection to
a water supply line would not be
considered portable ACIMs (i.e., a unit
would be considered portable if the
water supplied to the unit is only via
one or more reservoirs). 86 FR 72322,
72328. DOE proposed to define
‘‘portable automatic commercial ice
maker’’ as an automatic commercial ice
maker that does not have a means to
connect to a water supply line and has
one or more reservoirs that are manually
supplied with water in 10 CFR 431.132.
Id.
In the December 2021 NOPR, DOE
requested comment on the proposed
definition for portable automatic
commercial ice maker. Id.
In response to the December 2021
NOPR, AHRI commented that the
proposed definitions seemed
reasonable. (AHRI, No. 13, p. 2–3)
However, Hoshizaki and AHRI
requested that DOE work with AHRI
and ASHRAE to add this definition in
both AHRI 810 and ASHRAE 29.
(Hoshizaki, No. 14, p. 1–2; AHRI, No.
13, p. 2–3)
AHAM stated that portable ice makers
are designed to fit on the countertop and
rely on a reservoir instead of being
plumbed into the water supply. (AHAM,
No. 18, p.4)
The CA IOUs commented on two
types of portable ACIMs: portable
drawer ice machines and portable bin
ice machines. (CA IOUs, No. 16, p. 3)
E:\FR\FM\01NOR2.SGM
01NOR2
65864
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
The CA IOUs commented that portable
drawer ice machines are designed
without a door, and the ice drops
directly from the evaporator into a
drawer. Id. The CA IOUs stated that in
this design, the user does not have to
open a door to access the drawer. Id.
The CA IOUs commented that portable
bin ice machines are similar to
traditional self-contained machines
where the evaporator is in the bin itself;
however, the evaporator uses a pipe
trickle design to create semi-hollow or
gourmet ice. Id. The CA IOUs noted that
water can be filled directly into the
evaporator in the portable bin ice
machines, but both portable drawer and
portable bin low-capacity ice machine
designs can reuse ice-melt water to feed
the evaporator. Id.
DOE notes that the proposed
definition of portable automatic
commercial ice maker does not
distinguish between portable ACIMs
with and without doors. DOE has also
not identified any need to differentiate
between these portable ACIM
configurations for the purposes of
testing. Therefore, all portable ACIMs
would be included under this definition
and any further categorization of
portable ACIM equipment classes could
be investigated in any energy
conservation standards rulemaking for
portable ACIMs.
DOE is maintaining the definition of
portable automatic commercial ice
maker in this final rule, consistent with
the December 2021 NOPR.
3. Industry Standard Definitions
In addition to the definitions
specified at 10 CFR 431.132, the current
DOE test procedure at 10 CFR 431.134
references section 3, ‘‘Definitions’’ of
AHRI Standard 810–2007, which
includes many of the same terms DOE
defines at 10 CFR 431.132 and 31.134.
In the December 2021 NOPR, to avoid
potential confusion regarding multiple
definitions of similar terms, DOE
proposed to clarify in 10 CFR 431.134
that where definitions in AHRI Standard
810 conflict with those in DOE’s
regulations, the DOE definitions take
precedence. 86 FR 72322, 72328–72329.
AHRI Standard 810 (I–P)–2016 with
Addendum 1 updated its definition of
‘‘Energy Consumption Rate’’ to require
expressing the rate in multiples of 0.01
kWh/100 lb of ice. To maintain
consistency with the industry standard,
DOE proposed to incorporate this same
rounding requirement in its definition
of ‘‘Energy use’’ at 10 CFR 431.132
instead of the current requirement of
multiples of 0.1 kWh/100 lb of ice. 86
FR 72322, 72328.
AHRI Standard 810 (I–P)–2016 with
Addendum 1 also deleted its definition
of ‘‘Cubes Type Ice Maker’’ and replaced
it with a definition of ‘‘Batch Type IceMaker.’’ 86 FR 72322, 72328. To be
consistent with this industry update,
DOE proposed to remove the reference
to cubes type ice maker in the definition
of ‘‘batch type ice maker’’ in 10 CFR
431.132. Id. DOE also proposed to
remove ‘‘cube type ice’’ from the list of
DOE definitions at 10 CFR 431.132,
consistent with the industry standard
update. 86 FR 72322, 72329.
In the December 2021 NOPR, DOE
requested comment on its proposal to
amend 10 CFR 431.132 to revise the
previously described definitions,
consistent with updates to AHRI
Standard 810 (I–P)–2016 with
Addendum 1, additionally requesting
feedback on the proposed clarification
that the DOE definitions take
precedence over any conflicting
industry standard definitions. 86 FR
72322, 72329.
Hoshizaki agreed with this proposal,
but requested that AHRI 810, ASHRAE
29, and 10 CFR 431.132 definitions be
consistent. (Hoshizaki, No. 14, p. 2)
AHRI commented that the proposed
definitions seemed reasonable, but
stated that this should go to ASHRAE
SPC 29 and AHRI standard 810 for
consideration and inclusion. (AHRI, No.
13, p. 2–3)
DOE is amending 10 CFR 431.132 to
revise the previously described
definitions in this final rule. These
updates are consistent with updates in
the current industry standard AHRI
Standard 810 (I–P)–2016 with
Addendum 1. DOE is also maintaining
in this final rule the clarification that
the DOE definitions take precedence
over any conflicting industry standard
definitions, consistent with the
December 2021 NOPR.
The following section discusses
additional updates included in the latest
versions of the industry standards.
C. Industry Test Standards Incorporated
by Reference
The existing DOE ACIM test
procedure incorporates by reference
AHRI Standard 810–2007 and ASHRAE
Standard 29–2009. 10 CFR 431.134(b).
Since publication of the January 11,
2012 test procedure final rule (‘‘January
2012 final rule’’), both AHRI and
ASHRAE have published new versions
of the referenced standards. 77 FR 1591.
The most recent versions are AHRI
Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015 (reaffirmed in 2018). DOE has
reviewed the most recent versions of
both AHRI Standard 810 and ASHRAE
Standard 29 and has compared the
updated versions of these industry
standards to those currently
incorporated by reference in the ACIM
test procedure.
The updates in ASHRAE Standard
29–2015 provide additional specificity
to several aspects of the test method. In
general, these updates increase the
precision and improve the repeatability
of the test method, but do not
fundamentally change the testing
process, conditions, or results. In
addition, ASHRAE made several
grammatical, editorial, and formatting
changes to improve the clarity of the test
method. DOE summarizes these changes
in Table III.2.
lotter on DSK11XQN23PROD with RULES2
TABLE III.2—SUMMARY OF CHANGES BETWEEN ASHRAE STANDARD 29–2009 AND ASRHAE STANDARD 29–2015
Requirement
ASHRAE standard 29–2009
ASHRAE standard 29–2015
Test Room Operations ....................
None ..............................................
Temperature
ments.
Instru-
Accuracy of ±1.0 °F and resolution
of ≤2.0 °F.
Harvest Water Collection ................
None ..............................................
Ice Collection Container Specifications.
‘‘Perforated pan, bucket, or wire
basket’’ and ‘‘non-perforated
pan or bucket.’’
None ..............................................
None ..............................................
No changes to the test room shall be made during operation of the
ice maker under test that would impact the vertical ambient temperature gradient or the ambient air movement.
Accuracy and resolution of ±1.0 °F; where accuracy greater than ±1.0
°F, the resolution shall be at least equal to the accuracy requirement.
Harvest water shall be captured by a non-perforated pan located
below the perforated pan.
Requirements regarding water retention weight and perforation size
for perforated pans and ‘‘solid surface’’ for non-perforated pans.
Measuring
Pressure Measuring Instruments ....
Sampling Rate .................................
VerDate Sep<11>2014
18:34 Oct 31, 2022
Jkt 259001
PO 00000
Frm 00010
Fmt 4701
Accuracy of and resolution of ±2.0 percent of the quantity measured.
Maximum interval between data samples of 5 sec.
Sfmt 4700
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
65865
TABLE III.2—SUMMARY OF CHANGES BETWEEN ASHRAE STANDARD 29–2009 AND ASRHAE STANDARD 29–2015—
Continued
Requirement
Supply Water
Pressure.
Temperature
ASHRAE standard 29–2009
and
Inlet Air Temperature Measurement
Clearances ......................................
Stabilization Criteria ........................
Capacity Test Ice Collection ...........
Calorimetry Testing .........................
lotter on DSK11XQN23PROD with RULES2
Recorded Data ................................
±1 °F (water supply temperature).
±1 °F (water supply temperature) and ‘‘within 8 in. of the ice maker
. . . within the specified range’’ (water pressure) during water fill
interval.
Measure a minimum of 2 places, Measure at a location geometrically center to the inlet area at a discentered 1 ft from the air inlet(s).
tance 1 ft from each inlet.
18 inches on all sides .................... 3 ft or the minimum clearance allowed by the manufacturer, whichever is greater.
Three consecutive 14.4 min sam- Two consecutive 15.0 min ± 2.5 sec samples taken within 5 mins of
ples (continuous) taken within a
each other within 2 percent or 0.055 lbs (continuous) or calculated
1.5 hr period or two consecutive
24-hour ice production rate from two consecutive batches within ±2
batches (batch) do not vary by
percent or 2.2 lb (batch).
more than ±2 percent.
Three consecutive 14.4 min sam- Specifies that batch ice must be weighed 30 ± 2.5 sec after collection
ples (continuous) or batches
and continuous ice samples must be within 5 mins of each other.
(batch).
(1) Room temperature is not spec- (1) Room temperature shall be within 65–75°F during the entire proified.
cedure.
(2) To determine the calorimeter (2) To determine the calorimeter constant, add a quantity of water 5
constant, 30 lbs of water must
times the mass of ice (see #4 below).
be added.
(3) Rate of stirring is to be 1 ± 0.5 revolutions/second.
(3) Rate of stirring is described as (4) To determine the calorimeter constant, add a mass of ice be‘‘vigorously’’.
tween 50–200% of the rated ice production for a period of 15 min(4) To determine the calorimeter
utes of the ice maker to be tested, or 6 lbs, whichever is less.
constant, 6 lbs of ice must be (5) The block of pure ice must reach an equilibrium temperature
added.
measured by a thermocouple embedded in the interior of the block
(5) The block of ice is seasoned at
and free of trapped water.
room temperature. A tempera- (6) To determine the calorimeter constant, continue stirring for 15
ture measurement location is
minutes after ice has disappeared.
not specified for the block of ice. (7) The calorimeter constant shall be determined, at a minimum,
(6) To determine the calorimeter
each time the temperature measuring and weighting instruments
constant, it is not explicitly statare calibrated or if there is a change to the container or stirring aped to continue stirring for 15
paratus.
minutes after the ice has melt- (8) The calorimeter constant must be within 1.0–1.02.
ed.
(9) To determine the net cooling effect, stir the water for 15 minutes
(7) The calorimeter constant shall
prior to the addition of the harvested ice.
be determined twice, at the be- (10) Section 7.2.4 specifies that the ice sample used for calorimetry
ginning and at the end of the
testing shall be intercepted using a non-perforated container,
daily tests.
precooled to ice temperature, and collected from a stabilized ice
(8) The calorimeter constant shall
maker over a time period of 15 min or until 6 lbs has been capbe no greater than 1.02.
tured.
(9) To determine the net cooling
effect, the water must stand in
the calorimeter for 1 min before
adding harvested ice.
(10) Section 7.2.3 specifies that
the ice sample used for
calorimetry testing shall be intercepted in a manner similar to
that prescribed in section 7.2.2
(7.2.2 reads: Record the required data (see section 8).), except that the sample size shall
be suitable for the test.
Specifies 7 discrete elements be Specifies that ambient temperature gradient (at rest), maximum airrecorded.
circulation velocity (at rest), and water pressure must also be recorded.
DOE also reviewed the updates to
AHRI Standard 810 (I–P)–2016 with
Addendum 1 and identified the
following revisions: new definitions for,
among others, ice hardness factor and
potable water use rate; and an updated
rounding requirement for energy
consumption rate (from 0.1 kilowatt
hours per 100 pounds (‘‘kWh/100 lb’’) to
0.01 kWh/100 lb). The changes to AHRI
VerDate Sep<11>2014
18:03 Oct 31, 2022
ASHRAE standard 29–2015
Jkt 259001
Standard 810 (I–P)–2016 with
Addendum 1 are primarily clerical in
nature and provide greater consistency
in the use of terms and specific
definitions for those terms.
DOE also compared the latest version
of ASHRAE Standard 29–2015 to the
requirements in the current DOE test
procedure in 10 CFR 431.134. These test
methods specify different conditions for
PO 00000
Frm 00011
Fmt 4701
Sfmt 4700
calorimetry testing of continuous ice
makers. Specifically, the current DOE
test procedure requires an ambient air
temperature of 70 ± 1 °F, with an initial
water temperature of 90 ± 1 °F. 10 CFR
431.134(b)(2)(ii). ASHRAE Standard 29–
2015 states in appendix A3 that room
temperature shall be kept between 65 °F
and 75 °F, and that the water
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65866
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
temperature is 20 °F ± 1 °F above room
temperature.
In the December 2021 NOPR, DOE
tentatively determined that the current
ambient and water condition
requirements for calorimetry testing in
the DOE test procedure are appropriate
because they provide more precise and
repeatable measurements than the
tolerances described in ASHRAE
Standard 29–2015. 86 FR 72322, 72331.
Additionally, manufacturers have been
meeting the requirements to maintain
70 °F ± 1 °F ambient air temperature and
90 °F ± 1 °F initial water temperature for
calorimetry testing as part of the current
DOE test procedure in 10 CFR 431.134.
The current DOE test approach also is
consistent with the industry test
standard requirements, i.e., a test
performed at the DOE-required
temperature conditions meets the
temperature conditions specified in
ASHRAE Standard 29–2015. Therefore,
in the December 2021 NOPR, DOE did
not propose to amend the 70 °F ± 1 °F
ambient air temperature and 90 °F ± 1 °F
initial water temperature requirements
for calorimetry testing. 86 FR 72322,
72331. DOE proposed to explicitly
provide that the harvested ice used to
determine the ice hardness factor be
produced at the Standard Rating
Conditions specified in section 5.2.1 of
AHRI Standard 810 (I–P)–2016 with
Addendum 1. Id. These conditions are
provided in the industry standard,
indicating that they are currently used
by manufacturers and therefore this
clarification would not change how
manufacturers test.
Additionally, added specificity may
be needed to accurately determine the
calorimeter constant. DOE has found
that the lack of specificity as to the
location of the temperature
measurement of the block of pure ice
may lead to variation in the resulting
calorimeter constant. Therefore, in the
December 2021 NOPR, DOE proposed to
specify that the block of pure ice, as
specified in section A2.e of ASHRAE
Standard 29–2015, is measured by a
thermocouple embedded at
approximately the geometric center of
the interior of the block. 86 FR 72322,
72331. Furthermore, DOE proposed to
specify that any liquid water present on
the block of ice must be wiped off the
surface of the block before placing the
block into the calorimeter. Id.
In the December 2021 NOPR, DOE
proposed to adopt by reference AHRI
Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015 (note that AHRI Standard 810
(I–P)–2016 with Addendum 1 refers to
ASHRAE Standard 29–2015 and not the
2018 re-affirmed version) as the basis for
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
DOE’s ACIM test procedure, with
additional proposed provisions as
specified in the December 2021 NOPR.
86 FR 72322, 72331.
In the December 2021 NOPR, DOE
requested comment on its proposal to
maintain the current specifications for
ambient air temperature and initial
water temperature for calorimetry
testing. 86 FR 72322, 72331. DOE
additionally requested comment on its
proposal to clarify that the harvested ice
used to determine the ice hardness
factor be collected from the ACIM under
test at the Standard Rating Conditions
specified in section 5.2.1 of AHRI
Standard 810 (I–P)–2016 with
Addendum 1. Id.
In response to the December 2021
NOPR, Hoshizaki commented that it
does not agree with this change, and
requested that any changes to the test
procedure be brought to the ASHRAE 29
standard committee for clarification and
acceptance. (Hoshizaki, No. 14, p. 2)
Similarly, AHRI commented that
members are not opposed to this change
but note that such a change must follow
the proper channels and first be
incorporated into the ASHRAE 29
method of test before being adopted into
federal regulation. (AHRI, No. 13, p. 3)
AHAM commented that requiring the
ice sample to be used for calorimetry
testing be intercepted using a nonperforated container, precooled to ice
temperature is not necessary because
the measurement of ice sample weight
is very quick (about five seconds) and
will not reduce the accuracy due to the
ice sample melting or evaporating.
(AHAM, No. 18, p. 13) AHAM stated
that this requirement does not add a
large burden, but it is an unnecessary
burden. Id.
The test approach proposed in the
December 2021 NOPR is consistent with
the industry test standard requirements
and manufacturers have been meeting
the requirements to maintain 70 °F ±
1 °F ambient air temperature and 90 °F
± 1 °F initial water temperature for
calorimetry testing as part of the current
DOE test procedure in 10 CFR 431.134.
DOE is maintaining in this final rule
the current specifications for ambient
air temperature and initial water
temperature for calorimetry testing and
clarifying that the harvested ice used to
determine the ice hardness factor be
collected from the ACIM under test at
the Standard Rating Conditions
specified in section 5.2.1 of AHRI
Standard 810 (I–P)–2016 with
Addendum 1.
Additionally, DOE requested
comment on its proposal to clarify that
the temperature of the block of pure ice,
as specified in section A2.e. of ASHRAE
PO 00000
Frm 00012
Fmt 4701
Sfmt 4700
Standard 29–2015, is measured by a
thermocouple embedded at
approximately the geometric center of
the interior of the block. 86 FR 72322,
72331. DOE also requested comment on
its proposal to clarify that any water that
remains on the block of ice must be
wiped off the surface of the block before
placing the ice into the calorimeter. Id.
In response to the December 2021
NOPR, Hoshizaki requested that any
clarification of wording in ASHRAE 29
be brought to the ASHRAE 29 standard
committee for discussion and
acceptance. (Hoshizaki, No. 14, p. 2)
AHRI encouraged DOE to bring any
requests for clarification or
interpretation to the proper industry
working groups for consideration, since
consistency and repeatability are of
utmost importance to ensure that all
original equipment manufacturers
(‘‘OEMs’’) and testing bodies address
these provisions in a constant manner.
(AHRI, No. 13, p. 3)
The test approach proposed in the
December 2021 NOPR is consistent with
the industry test standard requirements
and would limit variation in
determining the calorimeter constant.
Therefore, DOE is maintaining these
clarifications in this final rule,
consistent with the December 2021
NOPR.
Additionally, DOE requested
comment on its proposal to adopt by
reference AHRI Standard 810 (I–P)–2016
with Addendum 1 and ASHRAE
Standard 29–2015, except for the
provisions for calorimetry testing as
discussed previously, for all ACIMs. 86
FR 72322, 72331.
Hoshizaki and AHRI agreed to the
adoption of AHRI Standard 810 (I–P)–
2016 with Addendum 1 and ASHRAE
29–2015. (Hoshizaki, No. 14, p. 2; AHRI,
No. 13, p. 3) However, Hoshizaki
supports adoption of the standards in
their entirety with no exceptions,
otherwise there is a risk that changes
not reflected in the standards will not be
realized by testers. (Hoshizaki, No. 14,
p. 2) Hoshizaki and AHRI requested that
any proposed changes be brought before
the relevant standard committees for
discussion and acceptance. (Hoshizaki,
No. 14, p. 2)
DOE is adopting by reference AHRI
Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015, except for the additional
amendments as specified in this final
rule. DOE has determined that the
additional amendments are consistent
with the test requirements in the
industry standards but provide added
specificity to limit variation in testing.
These modifications are consistent with
section 8(c) of 10 CFR part 430, subpart
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
C, appendix A (the ‘‘Process Rule’’),
applicable to ACIMs under 10 CFR
431.4, which states that DOE may adopt
industry test procedure standards with
modifications, or craft its own
procedures as necessary to ensure
compatibility with the relevant statutory
requirements, as well as DOE’s
compliance, certification, and
enforcement requirements. Additional
modifications to the industry standard
test methods are discussed in the
following sections.
lotter on DSK11XQN23PROD with RULES2
D. Additional Amendments
As part of this rulemaking, DOE
conducted testing to identify whether
ASHRAE Standard 29–2015 and AHRI
Standard 810 (I–P)–2016 with
Addendum 1 could potentially benefit
from additional detail and to investigate
topics discussed in the March 2019 RFI
and December 2021 NOPR. The testing
and initial findings are discussed along
with any corresponding amendments in
the following sections.
1. Low-Capacity ACIMs
DOE examined the comments
received in response to the December
2014 MREF Test Procedure NOPR to
consider what test method would be
appropriate for low-capacity ACIMs.
During the December 2014 MREF Test
Procedure NOPR public meeting, True
Manufacturing commented that there
are very few differences between ice
makers with harvest rates less than 50
lb/24 h and those with harvest rates
greater than 50 lb/24 h. (Public Meeting
Transcript, No. EERE–2013–BT–TP–
0029–0014 at p. 31) Hoshizaki
commented in response to the December
2014 MREF Test Procedure NOPR that
the ASHRAE 29 test needs to be
evaluated for accuracy for units that
make less than 50 lb/24 h, as they are
outside the listed scope of the standard.
(Hoshizaki, No. EERE–2013–BT–TP–
0029–0011 at p. 1)
In the December 2021 NOPR, DOE
evaluated the provisions in its existing
ACIM test procedure to determine if any
modifications are necessary to ensure
the proposed test method would
provide representative and repeatable
measures of performance for lowcapacity ACIMs and would not be
unduly burdensome to conduct. 86 FR
72322, 72331. DOE also evaluated the
provisions in AHRI Standard 810 (I–P)–
2016 with Addendum 1 and ASHRAE
Standard 29–2015 to determine their
applicability to low-capacity ACIMs. Id.
During investigative testing of batch
type low-capacity ACIMs, DOE observed
that the ice collection container
requirements in section 5.5.2(a) of
ASHRAE Standard 29–2015 may not be
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
appropriate for this equipment. Section
5.5.2(a) requires that the collection
container have a water retention weight
that is no more than 1.0 percent of that
of the smallest batch of ice for which the
container is used. For low-capacity
batch type ACIMs, the weight of ice in
each batch is significantly lower than
for other higher capacity ACIMs.
Accordingly, 1.0 percent of an
individual batch represents a very small
weight for low-capacity ACIMs. For
example, one such low-capacity ACIM
has a typical batch weight of 0.087
pounds; 1.0 percent of that would be
0.00087 pounds, the equivalent of 0.080
teaspoons of water. The water retention
weight of a typical very small collection
container is approximately 0.0030
pounds. DOE was not able to identify
collection containers that would meet
this threshold for the low-capacity
ACIMs with the lowest batch weights.
From its test sample, DOE determined
that a water retention weight of no more
than 4.0 percent would allow for testing
low-capacity ACIMs with the lowest
batch weights with a typical collection
container. Accordingly, in the December
2021 NOPR, DOE proposed that the
water retention requirement in section
5.5.2(a) not apply to batch type lowcapacity ACIMs, and instead to require
a water retention weight of no more
than 4.0 percent of the smallest batch of
ice for which the container is used. 86
FR 72322, 72332.
During the January 24, 2022, webinar
to discuss the December 2021 NOPR,
AHRI commented that the water
retention weight requirement for lowcapacity ACIMs and DOE’s test data
should be considered by the method of
test committee (e.g., ASHRAE 29).
(AHRI, January 24, 2022, webinar to
discuss the December 2021 NOPR 11)
DOE will consider any updated
industry standards, if available, during
future ACIM test procedure
rulemakings.
DOE is maintaining that the water
retention requirement in section 5.5.2(a)
of ASHRAE Standard 29–2015 not apply
to batch type low-capacity ACIMs, and
instead to require a water retention
weight of no more than 4.0 percent of
the smallest batch of ice for which the
container is used, consistent with the
December 2021 NOPR.
a. Portable ACIMs
For portable ACIMs, DOE has
determined that some provisions for
measuring and maintaining inlet water
conditions in ASHRAE Standard 29–
2015 are not appropriate: i.e., sections
11 See pages 19–20; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
PO 00000
Frm 00013
Fmt 4701
Sfmt 4700
65867
5.4, 5.6, 6.2, and 6.3. These sections
include instrument specifications, test
conditions, and measurement
instructions regarding inlet water flow,
pressure, and temperature. These
sections are not applicable to portable
ACIMs because such equipment does
not have a fixed water connection, and
therefore the conditions in these
sections would not provide
representative conditions for portable
ACIMs. Portable ACIMs instead require
that the fill reservoir be manually filled
with a maximum volume of water that
is recommended by the manufacturer.
To determine typical operation and
the corresponding need for additional
test procedure instructions regarding the
water supply for portable ACIMs, DOE
conducted tests on portable ACIMs
according to the requirements of AHRI
Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015, except for sections 5.4, 5.6,
6.2, and 6.3 of ASHRAE Standard 29–
2015. From this testing, DOE has
determined that additional instructions
are needed regarding supply water
characteristics and filling the water
reservoirs in portable ACIMs.
Section 5.2.1 of AHRI Standard 810
(I–P)–2016 with Addendum 1 specifies
an inlet water temperature of 70.0 °F for
ACIM testing. Because portable ACIMs
do not have a continuous water supply,
the water filled in the water reservoir is
not maintained at a constant
temperature; the temperature may
change after the initial fill based on heat
transfer with the ambient air and the
other components of the ACIM.
Accordingly, DOE has determined that
specifying only the initial fill
temperature of the water supplied to the
reservoir is most representative of
typical use. In the December 2021
NOPR, DOE proposed to establish the
initial water temperature in a separate
external container before transferring
the water to the water reservoir. 86 FR
72322, 72332. In DOE’s experience,
using an external container to establish
and verify the initial water temperature
is significantly less burdensome than
measuring and adjusting the water
temperature within the water reservoir
itself. Therefore, in the December 2021
NOPR, DOE proposed that the initial
water temperature condition be
established in an external container and
verified by inserting a temperature
sensor into approximately the geometric
center of the water in the external
container. 86 FR 72322, 72332. The
initial water temperature would be
defined as 70 °F ± 1.0 °F, consistent with
the condition as specified in section
5.2.1 of AHRI Standard 810 (I–P)–2016
with Addendum 1 and the tolerance as
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65868
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
specified in section 6.2 of ASHRAE
Standard 29–2015. Id.
Portable ACIM users may have an
option of filling the reservoirs to varying
levels. To determine the appropriate fill
level for testing, DOE reviewed
operating instructions for portable
ACIMs available from a range of
manufacturers. DOE observed that the
operating instructions typically instruct
the user to fill to the maximum
specified level, or to any level up to the
maximum. To ensure repeatable and
reproducible test results, DOE
determined that filling the water
reservoir to the maximum volume of
water as specified by the manufacturer
is representative of typical use. In
addition, specifying a consistent fill
level for testing at the maximum fill
level would limit variability associated
with reservoir water temperature and
would ensure the portable ACIM has
sufficient water to conduct the test.
In summary, in the December 2021
NOPR, DOE proposed that portable
ACIMs be subject to the test procedure
as proposed in the NOPR, except that
sections 5.4, 5.6, 6.2, and 6.3 of
ASHRAE Standard 29–2015 would not
apply. 86 FR 72322, 72332. DOE
proposed to provide the following
additional test instructions necessary for
testing portable ACIMs: ensure that the
ice storage bin is empty; fill an external
container with water; establish a water
temperature in the external container
that is consistent with the requirements
of section 5.2.1 of AHRI Standard 810
(I–P)–2016 with Addendum 1 and the
tolerance specified in section 6.2 of
ASHRAE Standard 29–2015 (i.e., 70 °F ±
1.0 °F); verify the water temperature in
the external container by inserting a
temperature sensor into approximately
the geometric center of the water; after
establishing water temperature,
immediately transfer the water to the
portable ACIM reservoir and fill the
reservoir to the maximum level as
specified by the manufacturer. Id.
DOE also determined that additional
instructions are needed for portable
ACIMs to meet the requirements of
section 6.6 of ASHRAE Standard 29–
2015, which requires that ‘‘bins shall be
used when testing and shall be filled
one-half full with ice.’’ Because section
6.6 of ASHRAE Standard 29–2015 does
not specify how the bin would be filled
with ice, a laboratory may fill the ice
storage bin one-half full of externally
produced ice (i.e., ice that was made by
a separate ACIM), for example to avoid
waiting for the unit under test to
produce enough ice to fill the bin onehalf full prior to initiating the start of
the test. Using externally produced ice
does not directly affect the performance
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
of a non-portable ACIM because the
conditions within the ice storage bin do
not have a direct impact on the
incoming potable water temperature.
In contrast, the conditions within the
ice storage bin of a portable ACIM do
directly impact performance because
portable ACIMs typically recycle the
melt water (at 32 degrees) from the
internal ice storage bin and combine it
with water from the reservoir (initially
at 70 degrees) to make additional ice.
Accordingly, any externally produced
ice introduced to a portable ACIM to fill
the bin one-half full prior to testing
could affect the performance of the
system during the test when compared
to the tested performance using ice
produced by the portable ACIM under
test.
To limit test variability that could
occur due to the introduction of
externally produced ice, in the
December 2021 NOPR DOE proposed
that for portable ACIMs, the ice storage
bin must be empty prior to the initial
water fill, and the unit under test must
be operated to produce ice into the ice
storage bin until the bin is one-half full
(i.e., precluding the use of externally
produced ice to fill the bin one-half full
prior to testing). 86 FR 72322, 72333.
DOE proposed to define one-half full as
half of the vertical dimension of the
storage bin, based on the maximum
possible fill level. Id. Once the ice
storage bin is one-half full of ice, testing
would proceed according to section 7 of
ASHRAE Standard 29–2015, consistent
with non-portable ACIM testing. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal
regarding reservoir water and ice storage
bin instructions for portable ACIMs. 86
FR 72322, 72332–72333.
Hoshizaki agreed with the proposal if
the portable units have a way to collect
the ice in a way not to confuse the ice
made in each cycle from the 1⁄2 full bin.
(Hoshizaki, No. 14, p. 2–3) Hoshizaki
and AHRI requested that this be brought
to the ASHRAE 29 standard committee
for consideration. (Hoshizaki, No. 14, p.
2–3; AHRI, No. 13, p. 3)
AHRI commented that consistency
and repeatability are of utmost
importance to ensure that all
manufacturers and testing bodies
address these provisions in a constant
manner. (AHRI, No. 14, p. 3)
AHAM commented that the 70 °F ±
1.0 °F tolerance requirement for the
initial water temperature is
unnecessarily tight for low-capacity
ACIMs, including portable ACIMs,
which adds unnecessary test burden.
(AHAM, No. 18, p. 10–11) AHAM
commented that the test procedure
should specify that the water should be
PO 00000
Frm 00014
Fmt 4701
Sfmt 4700
stirred to eliminate gradients that would
naturally occur because some models
recirculate melt water to the reservoir
and that, for all low-capacity ACIMs, the
temperature of the inlet water will vary
throughout the entire test with little
effect on the ultimate result. Id.
AHAM commented that the DOE’s
proposed test procedure for portable
ACIMs does not specify that the bin
should be emptied and dried out before
the first 15-minute run, which AHAM
suggests may be implicit in the
proposed test procedure but should be
stated clearly. (AHAM, No. 18, p. 12)
DOE notes that, in the December 2021
NOPR, DOE proposed that the ice
storage bin is empty prior to the initial
potable water reservoir fill and that the
initial water temperature of 70 °F ±
1.0 °F for testing portable ACIMs is only
required to be verified in an external
container immediately before filling the
portable ACIM water reservoir. 86 FR
72322, 72332–72333.
DOE testing has shown that portable
ACIMs are able to have ice collected in
a similar manner to non-portable ACIMs
which distinguish the ice made in each
cycle from the ice already present in the
ice storage bin. DOE has additionally
determined that the additional
provisions regarding reservoir water fill
are necessary to allow for testing of
portable ACIMs.
DOE is maintaining the test
requirements as proposed in the
December 2021 NOPR for portable
ACIMs in this final rule.
b. Refrigerated Storage ACIMs
DOE has determined that refrigerated
storage ACIMs can be tested according
to the current DOE ACIM test procedure
as well as AHRI Standard 810 (I–P)–
2016 with Addendum 1 and ASHRAE
Standard 29–2015. DOE investigated
whether additional specification was
necessary to ensure that these test
methods would provide representative
and repeatable results for refrigerated
storage ACIMs and would not be unduly
burdensome to conduct.
DOE identified two aspects of
refrigerated storage ACIM testing that
may need further specification to limit
variability: door openings for
refrigerated storage ACIMs and
refrigeration set point controls.
Door opening durations may affect the
measured performance of refrigerated
storage ACIMs more than nonrefrigerated storage ACIMs because the
refrigeration system provides cooling for
the entire self-contained storage bin
rather than only for the ice making
evaporator. Thus, when opening the
storage container door to collect ice
from refrigerated storage ACIMs, some
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
portion of cold air from the storage
container will likely be replaced by
higher temperature ambient air. Both
the duration and the extent of the door
opening can contribute to this air
exchange within the storage container.
Therefore, specifying the duration and
the extent of the door opening would
limit variability from test to test, thus
promoting repeatable and reproducible
test results.
From investigative testing, DOE has
determined that the process of opening
the bin door, carefully removing or
replacing the ice collection container,
and closing the door can be readily
performed in under 10 seconds.
Therefore, in the December 2021 NOPR,
DOE proposed that for refrigerated
storage ACIMs, any storage bin door
openings shall be conducted with the
door in the fully open position for 10 ±
1 seconds. 86 FR 72322, 72333. DOE
proposed to specify that ‘‘fully open’’
means opened to an angle of not less
than 75 degrees (or to the maximum
angle possible, if that is less than 75
degrees), which is consistent with the
definition for fully open in ANSI/
ASHRAE Standard 72–2018, ‘‘Method of
Testing Open and Closed Commercial
Refrigerators and Freezers.’’ Id. To
ensure a consistent number of door
openings, DOE also proposed to specify
that door openings would occur only
when collecting the ice sample and
when returning the empty collection
container to the ice storage
compartment (i.e., two separate door
openings per sample collection). Id.
Refrigeration set point controls may
also affect the measured performance of
refrigerated storage ACIMs, if the
controls can be adjusted by the user to
maintain different storage compartment
temperatures. DOE investigated whether
refrigerated storage ACIMs allow the
user to adjust the refrigeration set point
of the ACIM and if so, how. DOE
reviewed user manuals for several
refrigerated storage ACIMs and found
that the models either do not allow the
user to adjust the refrigeration set point,
or have a factory preset temperature
control that can be adjusted by the user,
but not in an easily accessible manner
(e.g., temperature control screws
adjustable only with a screwdriver or
accessible behind grilles). The ability to
adjust the refrigeration set point on
some refrigerated storage ACIMs does
not appear to be a setting that users
would typically adjust and is likely
used only for troubleshooting. Based on
this information, DOE proposed in the
December 2021 NOPR that the
refrigeration set point for testing a
refrigerated storage ACIM be consistent
with section 4.1.4 of AHRI Standard 810
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
(I–P)–2016 with Addendum 1 (i.e., per
the manufacturer’s written instructions
with no adjustment prior to or during
the test). 86 FR 72322, 72333.
In the December 2021 NOPR, DOE
requested comment on its proposal to
test refrigerated storage ACIMs
consistent with AHRI Standard 810 (I–
P)–2016 with Addendum 1, with the
specified proposed door opening
duration and frequency. 86 FR 72322,
72333. DOE requested comment on
whether a specific refrigeration set point
or internal air temperature should be
specified instead of the manufacturer’s
factory preset. Id.
In response to the December 2021
NOPR, Hoshizaki and AHRI both
requested DOE clarify refrigerated
storage ACIMs and share examples
before feedback can be given.
(Hoshizaki, No. 14, p. 3; AHRI, No. 13,
p. 4)
AHRI commented that ASHRAE 29
does not cover products installed in
residential refrigerators or freezers, and
if these are the type of systems being
referred to as self-contained refrigerated
storage ACIMs, the scope of both
ASHRAE 29 and the DOE rulemaking
would need to be expanded to cover
such equipment. (AHRI, No. 13, p. 4)
AHRI suggested that DOE clarify the
equipment type and bring this issue to
ASHRAE SPC 29 for consideration. Id.
AHAM commented that DOE’s proposed
test procedure draws heavily from AHRI
Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015 that were not developed with
residential products in mind. (AHAM,
No. 18, p. 9)
DOE is not referring to products
installed in residential refrigerators or
freezers in this Final rule. Refrigerated
storage ACIMs are explicitly excluded
from the freezer definition at 10 CFR
430.2 and differ from the refrigeratorfreezer definition at 10 CFR 430.2
because refrigerated storage ACIMs only
produce and store ice in a single
compartment. Section III.B.1 provides
further clarity and an example of
refrigerated storage ACIMs.
Because DOE did not receive any
comments regarding the refrigerated
storage ACIM proposals, DOE is
maintaining the test requirements as
proposed in the December 2021 NOPR
for refrigerated storage ACIMs in this
final rule.
2. Stability Criteria
The current DOE test procedure,
through reference to section 7.1.1 of
ASHRAE Standard 29–2009, defines
ACIM stability based on the harvest rate.
Specifically, continuous type ice makers
shall be considered stabilized when the
PO 00000
Frm 00015
Fmt 4701
Sfmt 4700
65869
weights of three consecutive 14.4minute samples taken within a 1.5-hour
period do not vary by more than ±2
percent. Batch type ice makers are
considered stable when the weights
from the samples from two consecutive
cycles do not vary by more than ±2
percent.
a. Capacity Test Cycles or Samples
Section 7.1.1 of ASHRAE Standard
29–2015 revised the stabilization
criteria to consider continuous type ice
makers stable when the weights of two
consecutive 15.0 minute ± 2.5 seconds
samples do not vary by more than the
greater of ±2 percent, or 0.055 pounds.
Section 7.1.1. of ASHRAE Standard 29–
2015 specifies that batch type ice
makers are considered stable when the
24-hour calculated ice production rate
from samples taken from two
consecutive cycles do not vary by the
greater of ±2 percent or 2.2 pounds.
Compared to the 2009 version, ASHRAE
Standard 29–2015 added absolute
stability criteria of 0.055 lb/15 minutes
for continuous equipment and 2.2 lb/24
h for batch equipment.
In addition, ASHRAE Standard 29–
2009 states that the unit must be stable
before the capacity tests are started. This
provision was changed in ASHRAE
Standard 29–2015, which instead states
that the ice maker must be stable for
capacity test data to be valid. In
application, the stability provision in
ASHRAE Standard 29–2009 means that
any cycle or sample after the stability
criteria is met is valid to be used for the
capacity test. DOE notes that the
applicability of the stability criteria in
ASHRAE Standard 29–2015 could be
understood in one of two ways: (1)
Unchanged from ASHRAE Standard 29–
2009, meaning that any cycle or sample
after the stability criteria are met is valid
to be used for the capacity test; or (2) the
ice production rate for each cycle used
for the capacity test relative to any other
cycle or sample used for the capacity
test must be within the greater of ±2
percent and 2.2 lb/24 h for batch type
ice makers, and each sample used for
the capacity test must be within the
greater of ±2 percent and 0.055 lb/15
mins for continuous ice makers. The
second interpretation limits potential
variability compared to the first
interpretation because it puts specific
limits on the variability between cycles
and samples to be used for the capacity
tests. The difference in the potential
interpretations of the stability
provisions in ASHRAE Standard 29–
2015 could result in variation in
capacity ratings. Additionally, the
second interpretation limits test burden
by not requiring separate cycles for
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65870
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
meeting the stability criteria and for
testing performance. Under the second
interpretation, the same cycles are used
to determine stability and performance.
In the December 2021 NOPR, DOE
proposed to expressly provide that the
second interpretation be used for
determining stability, such that all
cycles or samples used for the capacity
test are stable. 86 FR 72322, 72334. DOE
does not expect that this proposal
would impact ACIM performance as
measured under the existing test
procedure as it would not substantively
change the cycles required for
evaluating performance. Id.
In the December 2021 NOPR, DOE
requested comment on its interpretation
of section 7.1.1 of ASHRAE Standard
29–2015 and proposal to require that all
cycles or samples used for the capacity
test meet the stability criteria. 86 FR
72322, 72334.
Hoshizaki agreed that all cycles
should meet the stability criteria.
(Hoshizaki, No. 14, p. 3) AHRI
commented that the stability criteria
should match the requirements of
ASHRAE 29. (AHRI, No. 13, p. 4)
AHRI commented that some units
vary in performance each cycle due to
water dump frequency by design, and
DOE should ask the ASHRAE committee
for an interpretation if DOE is
concerned about ambiguity in ASHRAE
29. (AHRI, No. 13, p. 4)
IOM commented that this proposal
would take the stabilization criteria
further than ASHRAE Standard 29–2009
and ASHRAE Standard 29–2015,
requiring that all cycles not differ by
more than 2%. (Ice-O-Matic, No. 11, p.
1) IOM added that a dataset with small
linear growth (100, 102, and 104 lb/24
hr) would not be considered stabilized
under this DOE rule, while it would be
considered stabilized under ASHRAE
Standard 29–2015. Id. IOM commented
that in practice it is not uncommon for
units which achieved stabilization
under ASHRAE Standard 29–2009 to
produce capacity test samples which
vary in excess of ±2 percent. Id. IOM
stated that because allowable variance
during capacity tests is already being
reduced by changing from ASHRAE 29–
2009 to ASHRAE 29–2015, IOM finds
DOE’s proposal to further reduce
potential variance excessive, and
believes it has the potential to increase
test burden on manufacturers. Id. IOM
generally supported using test cycles to
also confirm stability following the
requirements for stability as defined in
ASHRAE Standard 29–2015. (IOM, No.
11, p. 3)
DOE has determined that clarifying
the stability criteria specified in
ASHRAE 29–2015 will produce test
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
results that are more representative,
repeatable, and reproducible. As
indicated in the IOM comment, the
current ASHRAE 29–2009 approach
may introduce potential variability in
test results. Additionally, reducing the
number of cycles or samples required
for the capacity test will reduce test
burden by reducing total test time. DOE
discusses test burden in section III.F.1
of this final rule.
Therefore, DOE is maintaining in this
final rule its interpretation of section
7.1.1 of ASHRAE Standard 29–2015 and
requirement that all cycles or samples
used for the capacity test meet the
stability criteria, consistent with the
December 2021 NOPR.
b. Test Sample Duration
Section 7.1.1 of ASHRAE Standard
29–2015 added a requirement that the
duration of each sample for continuous
type ice makers be 15.0 minutes ±2.5
seconds. DOE testing indicated that
removing the plastic pan or bucket
within the tolerance of ±2.5 seconds can
be difficult depending on the specific
test setup (e.g., removing the container
from the ice maker or bin without
spilling ice). An increased tolerance
would reduce burden on manufacturers
to test continuous ice makers, while still
sufficiently limiting the variability
between samples used for the capacity
test to the criteria proposed.
In the December 2021 NOPR, DOE
proposed to increase the tolerance to
collect samples for continuous ice
makers from 15.0 minutes ± 2.5 seconds
to 15.0 minutes ± 9.0 seconds. 86 FR
72322, 72334. Increasing the tolerance
to 9.0 seconds could affect the weight of
each sample; however, variability would
not increase because the samples used
for the capacity test would still need to
meet the proposed stability criteria. Id.
With the 9-second tolerance, the
maximum and minimum allowable
collection times would vary by
approximately 2 percent, which is
consistent with the allowable variation
in capacity to determine stability. Id.
DOE expected that this proposal would
reduce the test burden compared to the
ASHRAE Standard 29–2015 approach
and would ensure that valid samples
can be obtained. Id. Additionally, in the
December 2021 NOPR, DOE did not
expect that this proposal would affect
measured performance as compared to
the existing test procedure because the
sample collection period as proposed is
not substantively different from the
existing test procedure approach. Id.
In the December 2021 NOPR, DOE
requested comment on the proposal to
increase the tolerance for continuous ice
makers to collect samples to 15.0
PO 00000
Frm 00016
Fmt 4701
Sfmt 4700
minutes ± 9.0 seconds. 86 FR 72322,
72334.
In response to the December 2021
NOPR, IOM commented in support of
the proposal to increase the tolerance on
sample collection for continuous ice
makers. (Ice-O-Matic, No. 11, p. 1)
Hoshizaki and AHRI commented that
they do not agree with the proposed
change. (Hoshizaki, No. 14, p. 3; AHRI,
No. 13, p. 4) Hoshizaki commented such
time could impact high-capacity
continuous models and have a
significant impact on capacity and
energy totals, and AHRI added that the
proposed changes could impact the
output depending on the capacity of the
unit. Id. AHRI stated that this proposal
could change the integrity of the test
and would need further evaluation prior
to being considered. Id.
AHRI added that the increase to ±9.0
seconds would allow high-capacity
units to potentially collect a greater
sample and while the test was not
designed to be applied to low-capacity
machines, the impact of this proposed
change could be substantially less. Id.
Hoshizaki requests that further
discussion be put through the ASHRAE
29 committee. (Hoshizaki, No. 14, p. 3)
DOE has re-evaluated its proposal and
determined that although a greater
tolerance would reduce test burden on
manufacturers to test continuous
ACIMs, the collection duration
tolerance in ASHRAE 29–2015 provides
a repeatable and reproducible method of
test. DOE has determined that the
specified tolerance included in
ASHRAE 29–2015 demonstrates that
manufacturers can meet the specified
tolerance without the need for an
increased tolerance. Therefore, DOE is
declining to allow for a greater
collection duration tolerance than the
tolerance specified for continuous
ACIMs in ASHRAE 29–2015 (i.e., ±2.5
seconds).
c. Low-Capacity ACIM Stability
Criterion
Section 7.1.1 of ASHRAE 29–2015
includes stabilization requirements,
which specify: (1) For continuous
ACIMs, collected weights must not vary
by more than ±2 percent or 25 g (0.055
lb), whichever is greater; or (2) for batch
ACIMs, the calculated 24-hour ice
production rates must not vary by more
than ±2 percent or 1 kg (2.2 lb),
whichever is greater.
Based on investigative testing
conducted as part of this rulemaking,
DOE observed that the absolute stability
criteria of 2.2 lb/24 h for batch type ice
makers would not necessarily represent
stable operation for low-capacity batch
ACIMs. DOE conducted a market
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
assessment and observed batch lowcapacity ACIMs with harvest rates as
low as 7 lb/24 h. Based on this harvest
rate of 7 lb/24 h, a 2.2 lb/24 h stability
criteria could result in a harvest rate
variation of up to 31 percent (i.e., 2.2 lb/
24 h divided by 7 lb/24 h). Because of
the potential high variability in the
stability criteria for low-capacity
ACIMs, DOE proposed in the December
2021 NOPR to not apply the absolute
stability criteria specified in ASHRAE
29–2015 to the proposed test procedure
for low-capacity ACIMs. 86 FR 72322,
72334.
DOE also considered whether
applying only the ±2 percent stability
criterion would be appropriate for lowcapacity ACIMs. Due to the lower
overall ice harvest rates, a ±2 percent
stability requirement represents much
smaller weight variations for lowcapacity ACIMs. For example, a 2
percent stability requirement for the 7
lb/24 h model represents a variation of
0.14 lb/24 h, which may be difficult to
achieve for low-capacity ACIMs.
The ±2 percent stability requirement
is also not currently applicable to the
lowest capacity ACIMs currently in
scope for the DOE test procedure (i.e.,
the requirement is 2 percent or 2.2 lb/
24 h, whichever is greater). Accordingly,
the effective stability requirement for
the lowest capacity ACIMs currently in
scope is approximately 4 percent (i.e.,
2.2 lb/24 h divided by 50 lb/24 h). In the
December 2021 NOPR, DOE determined
that applying this same percentage (i.e.,
4 percent) as the low-capacity ACIM
stability requirement would be more
appropriate than applying either the 2
percent or 2.2 lb/24 h stability
requirements currently defined in
section 7.1.1 of ASHRAE 29–2015. 86
FR 72322, 72334. DOE observed through
testing that low-capacity ACIMs are able
to achieve stability based on a 4 percent
requirement. Id.
Therefore, for consistency (on a
percentage basis) with the ASHRAE 29–
2015 test requirements for the lowest
capacity ACIMs currently in scope and
to limit test burden, in the December
2021 NOPR, DOE proposed to require a
±4 percent stability criterion (without an
absolute stability criterion) for testing
low-capacity ACIMs. 86 FR 72322,
72334.
In the December 2021 NOPR, DOE
requested comment on the proposal to
require that all cycles or samples of lowcapacity ACIMs used for the capacity
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
test meet a ±4 percent stability criterion
and not be subject to an absolute
stability criterion. 86 FR 72322, 72334.
In response to the December 2021
NOPR, Hoshizaki and AHRI requested
that this proposal be brought to the
ASHRAE 29 standard committee with
supporting testing to show that this
stability is necessary and adequate for
these products since currently they are
outside of the scope, and that ASHRAE
29 was not developed for low-capacity
ACIMs. (Hoshizaki, No. 14, p. 3; AHRI,
No. 13, p. 4–5) AHRI added that the
units should not be allowed to bypass
stability requirements currently in the
standard simply because the method of
test has not been designed to
incorporate such units. (AHRI, No. 13,
p. 4–5) AHRI commented that members
do not currently have testing data to
show that 4 percent would be accurate
or comparable for this equipment type.
Id.
AHAM commented in support of the
±4 percent stability criterion for lowcapacity ice makers. (AHAM, No. 18, p.
11) AHAM stated that DOE’s ACIM
energy conservation standards or test
procedure need a method to account for
this planned variation such that the
variation does not penalize
manufacturers when the test procedure
is used for enforcement purposes. Id.
DOE observed from testing of lowcapacity ACIMs to support the
December 2021 NOPR that a ±4 percent
stability criterion is appropriate and
ensures representative, repeatable, and
reproducible measures of performance
for low-capacity ACIMs. A ±4 percent
stability criterion is consistent with the
absolute stability requirements from
ASHRAE 29–2015 for the lowest
capacity ACIMs currently in scope (i.e.,
2.2 lb/24 h divided by 50 lb/24 h). A ±4
percent stability criterion does not
bypass any requirement because lowcapacity ACIMs are not currently
subject to the DOE test procedure and
are not within the scope of ASHRAE
29–2009 or ASHRAE 29–2015. DOE will
consider any updated industry
standards, if available, during future
ACIM test procedure rulemakings. DOE
discusses enforcement provisions for
ACIMs in section III.E.3 of this final
rule.
DOE is maintaining in this final rule
the requirement that all cycles or
samples of low-capacity ACIMs used for
the capacity test meet a ±4 percent
stability criterion and not be subject to
PO 00000
Frm 00017
Fmt 4701
Sfmt 4700
65871
an absolute stability criterion, consistent
with the December 2021 NOPR.
3. Test Conditions
The DOE test procedure specifies
standard test conditions to ensure that
test results reflect energy use during a
representative average use cycle and are
not unduly burdensome for
manufacturers to perform.
DOE discusses test conditions,
including tolerances and
instrumentation accuracies, in the
following sections.
a. Relative Humidity
Variation in the moisture content of
ambient air may affect the energy
consumption of automatic commercial
ice makers. However, neither the
current DOE test procedure, nor AHRI
Standard 810 (I–P)–2016 with
Addendum 1 or ASHRAE Standard 29–
2015 include requirements to control for
moisture content for testing. In contrast,
industry test standards for other
refrigeration equipment, such as
commercial refrigerators, freezers and
refrigerator-freezers (‘‘CRE’’) and
refrigerated bottled or canned beverage
vending machines (‘‘BVMs’’), have
requirements for the moisture content.
In the December 2021 NOPR, DOE
presented data from three ACIMs tested
at relative humidity levels of 35, 55, and
75 percent at the standard rating
conditions to investigate the effect of
relative humidity on energy use, as
replicated in Table III.3. 86 FR 72322,
72335. The results showed a wide range
of impacts on energy use among the
three tested units when relative
humidity is varied. Id. Test Unit 1
showed less than 1 percent variation in
energy use among the three relative
humidity test conditions. Id. Whereas,
Test Unit 2 showed a 35 percent
difference in energy use between the 35
percent and 75 percent relative
humidity test conditions. Id. Test Unit
3 showed a 4 percent difference in
energy use between the 35 percent and
75 percent relative humidity conditions.
Id. DOE stated in the December 2021
NOPR that it was unable to determine
why Test Unit 2 showed significantly
greater variation in performance
compared to the other test units. Id. In
summary, these results indicated that
for certain ACIM models, relative
humidity has a significant impact on
measured energy use.
E:\FR\FM\01NOR2.SGM
01NOR2
65872
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
TABLE III.3—COMPARISON OF ENERGY USE RATES AT DIFFERENT RELATIVE HUMIDITY TEST CONDITIONS AS PRESENTED
IN THE DECEMBER 2021 NOPR
Test unit
1
2
3
35% relative
humidity
(kWh/100 lb)
Type
Batch ...................................................
Batch ...................................................
Continuous ..........................................
In the December 2021 NOPR, DOE
considered relative humidity test
conditions for ACIMs by comparing the
test conditions required for testing other
types of commercial food service
equipment, including CRE, BVMs, and
8.27
8.47
4.27
55% relative
humidity
(kWh/100 lb)
75% relative
humidity
(kWh/100 lb)
8.28 ......................
10.49 ....................
Not Tested ............
refrigerated buffet and preparation
tables. 86 FR 72322, 72335. In
particular, DOE compared the moisture
content level corresponding to the
combination of ambient temperature
and relative humidity specified for these
8.28
11.47
4.43
Difference
from 35%
relative
humidity to
55% relative
humidity
(%)
+0.2
+24
N/A
Difference
from 35%
relative
humidity to
75% relative
humidity
(%)
+0.2
+35
+4
other equipment types. Id. DOE
summarized these test condition
requirements along with the proposed
relative humidity test condition of 35
percent for ACIMs, as replicated in
Table III.4. Id.
TABLE III.4—COMPARISON OF RELATIVE HUMIDITY TEST CONDITIONS AS PRESENTED IN THE DECEMBER 2021 NOPR
Ambient
temperature
(°F)
Wet Bulb temperature
(°F)
Corresponding
moisture
content
(lbs water
vapor/lbs dry
air)
Relative
humidity
(percent)
Equipment type
Test standard
Commercial Refrigeration
Equipment.
Refrigerated Beverage Vending Machines.
Refrigerated Buffet and Preparation Tables.
Automatic Commercial Ice
Makers.
ASHRAE 72–2005† ..............
75.2
64.4 .......................................
* 55
0.010
ASHRAE 32.1–2010† ...........
75
No requirement .....................
45
0.008
ASTM Standard F2143–2016
86
No requirement .....................
35
0.009
Proposed ..............................
90
No requirement .....................
** 35
0.011
lotter on DSK11XQN23PROD with RULES2
* The relative humidity for commercial refrigeration equipment is calculated from the dry bulb temperature and the wet bulb temperature using
a pressure of 760 mm of mercury.
** Proposed test condition.
† The test conditions currently incorporated by refence in the DOE test procedures are unchanged in the most recent versions of the industry
standards, ASHRAE 72–2018 and ASHRAE 32.1–2017.
Based on these considerations, DOE
proposed to require a relative humidity
test condition of 35 percent for ACIM
testing. 86 FR 72322, 72335. As
indicated in Table III.4, the proposed
relative humidity condition of 35
percent, in combination with the
ambient air condition of 90 °F, would
correspond to a moisture content of
0.011 lbs water vapor/lbs dry air. This
would closely match the moisture
contents associated with the test
procedures for the other types of
commercial food service equipment.
In the December 2021 NOPR, DOE
also investigated appropriate tolerances
to specify for the relative humidity test
condition. 86 FR 72322, 72336. DOE
considered a test condition tolerance
and test operating tolerance on relative
humidity. Id. A test condition tolerance
is a tolerance that is calculated based on
the average of all relative humidity
measurements during each freeze cycle.
Id. In contrast, a test operating tolerance
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
would apply to all individual
measurements during each cycle. Id.
The industry standards referenced in
Table III.4, ASHRAE 72–2018, ASHRAE
32.1–2017, and ASTM Standard F2143–
2016, all require a test condition
tolerance. Id. ASHRAE 72–2018 is the
only standard mentioned in Table III.4
that also requires a test operating
tolerance. Id.
DOE also investigated typical
accuracies of relative humidity sensors,
finding that accuracies of ±2.0 percent
are typical for relative humidity sensors.
Id. Additionally, DOE noted that its test
procedure for BVMs requires a relative
humidity instrument accuracy of ±2.0
percent for a test condition tolerance of
±5.0 percent. See section 1.1 of
appendix B to subpart Q of 10 CFR part
431. Id. Similarly, section 6.3 of ASTM
Standard F2143–2016 also requires a
relative humidity instrument accuracy
of ±2.0 percent for a test condition
tolerance of ±5.0 percent. Id.
PO 00000
Frm 00018
Fmt 4701
Sfmt 4700
Based on this analysis, DOE proposed
a relative humidity test condition
tolerance of ±5.0 percent. Id. DOE also
proposed to require a relative humidity
instrument accuracy of ±2.0 percent. Id.
In summary, DOE proposed to require
a relative humidity test condition of 35
percent. 86 FR 72322, 72335. DOE
proposed that the relative humidity be
maintained and measured at the same
location used to confirm ambient dry
bulb temperature, or as close as the test
setup permits. 86 FR 72322, 72336. DOE
proposed to add a test condition
tolerance on the proposed relative
humidity test condition of ±5.0 percent.
Id. DOE proposed to require a relative
humidity instrument accuracy of ±2.0
percent. Id. DOE stated in the December
2021 NOPR that it did not expect the
proposal to affect measured
performance of existing ACIM models.
Id.
DOE requested comment on the
proposal to control relative humidity at
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
35 ± 5.0 percent. 86 FR 72322, 72336.
Specifically, DOE requested comment
on the representativeness of 35 percent
relative humidity in field use
conditions, whether manufacturers
currently control and measure relative
humidity for ACIM testing (and if so,
the conditions used for testing), and the
burden associated with controlling
relative humidity within a tolerance of
±5.0 percent. Id.
In response to the December 2021
NOPR, Hoshizaki and AHRI commented
that due to inherent humidity caused by
ice makers in the production of ice, the
control of relative humidity has been
left out of the test protocols currently
used (e.g., ASHRAE 29). (Hoshizaki, No.
14, p. 3; AHRI, No. 13, p. 5) AHRI, Joint
Commenters, Hoshizaki, IOM, The
Legacy Companies, and Manitowoc Ice
commented that ACIMs respond
differently to the humidity of ambient
air than other refrigerated equipment
because the evaporator is in a wetted
setting, so units are not greatly affected
by humidity changes during testing.
(AHRI, No. 13, p. 5; Joint Commenters,
No. 15, p. 1; Hoshizaki, No. 14, p. 3;
IOM, No. 11, p. 2; The Legacy
Companies, January 24, 2022 webinar to
discuss the December 2021 NOPR; 12
Manitowoc Ice, January 24, 2022
webinar to discuss the December 2021
NOPR) 13 AHRI and added that units are
designed to handle these conditions and
that humidity control is not necessary
(AHRI, No. 13, p. 5; AHAM, No. 18, p.
12).
IOM and The Legacy Companies
commented that they do not support the
proposal to control humidity. (IOM, No.
11, p. 2; The Legacy Companies, January
24, 2022 webinar to discuss the
December 2021 NOPR) 14 Joint
Commenters commented that ACIM test
chambers typically do not control the
relative humidity of ambient air. (Joint
Commenters, No. 15, p. 1) IOM
commented that they do not control for
or measure humidity levels in its
environmental chambers. (IOM, No. 11,
p. 2) Welbilt commented that they do
not have humidity control in their test
chambers and that ACIM test chambers
are often very specialized because of the
range of ambient conditions that are
needed to test ACIMs whereas CRE test
chambers are typically used for testing
at one or two ambient conditions.
12 See pages 30–31; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
13 See pages 32–33; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
14 See pages 30–31; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
VerDate Sep<11>2014
19:48 Oct 31, 2022
Jkt 259001
(Welbilt, January 24, 2022 webinar to
discuss the December 2021 NOPR) 15
AHRI, Hoshizaki, IOM, Joint
Commenters, and Manitowoc Ice
commented that test data should be
reviewed and validated to confirm the
need for relative humidity control.
(AHRI, Public Meeting Transcript, No.
EERE–2017–BT–TP–0006–0012 at p. 29;
Hoshizaki, No. 14, p. 3; IOM, No. 11, p.
2; Joint Commenters, No. 15, p. 1–2;
Manitowoc Ice, January 24, 2022
webinar to discuss the December 2021
NOPR) 16 AHAM commented that DOE’s
testing is not sufficient to justify its
proposed requirement. AHAM, No. 18,
p. 13. Joint Commenters added that DOE
should conduct additional relative
humidity testing and if a large
performance difference for some units is
confirmed, then a relative humidity
requirement is needed to ensure the
reproducibility of the test procedure.
(Joint Commenters, No. 15, p. 1–2)
AHRI, Hoshizaki, IOM, Welbilt, and
Joint Commenters commented that a
relative humidity of 35 percent may be
unrepresentative of the variety of
environments housing ACIMs. (AHRI,
No. 13, p. 5; Hoshizaki, No. 14, p. 3;
IOM, No. 11, p. 2; Welbilt, January 24,
2022 webinar to discuss the December
2021 NOPR; 17 Joint Commenters, No.
15, p. 2) IOM added that commercial
kitchens may have humidity much
higher than 35 percent, front-of-house
locations may be lower than 35 percent,
and ACIMs utilizing a remote condenser
may see humidity anywhere between 15
and100 percent. (IOM, No. 11, p. 2)
AHRI commented that the ambient
temperatures would also vary greatly by
application and such a humidity would
be difficult to control while entering the
test chamber for sample collection.
(AHRI, No. 13, p. 5) IOM believes that
a ±5 percent tolerance is too narrow and
would be difficult to control during
tests. (IOM, No. 11, p. 2) IOM suggested
a ±10 percent tolerance if humidity is
controlled. Id.
AHRI, IOM, and Welbilt asserted that
the addition of humidity control
requirements would impose undue
burden to OEMs and testing facilities
without benefiting the efficiency or
testing of ACIMs. (AHRI, No. 13, p. 5;
IOM, No. 11, p. 2; Welbilt, January 24,
2022 webinar to discuss the December
2021 NOPR 18) AHRI, IOM, and Welbilt
commented that it would also be
15 See pages 29–30; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
16 See pages 32–33; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
17 See pages 29–30; www.regulations.gov/
document/EERE-2017-BT-TP-0006–0012.
18 See pages 29–30; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
PO 00000
Frm 00019
Fmt 4701
Sfmt 4700
65873
extremely costly to add humidity
control upgrades to testing laboratories
for little wielded benefit. Id. Hoshizaki
commented that full costs should be
considered in adding this to the test
criteria along with the cost to retest all
products that currently do not have
humidity control in their test.
(Hoshizaki, No. 14, p. 3)
Hoshizaki requested that this be
addressed in the ASHRAE 29 standard
committee for consensus. (Hoshizaki,
No. 14, p. 3)
DOE has reviewed and confirmed the
validity of the test data from the three
units presented in the December 2021
NOPR.
DOE has also conducted further
analysis of the test data from Test Unit
2 to further investigate that unit’s
significant variation in energy use
among the different relative humidity
test conditions. DOE notes that during
the January 24, 2022 webinar to discuss
the December 2021 NOPR, True
Manufacturing commented in response
to a request for comment about the
relative humidity test condition that
some ACIMs that have poor insulation
may inadvertently make ice on the back
side of the evaporator plate or other
unwanted areas, which could possibly
decrease the harvest rate.19 Indeed, DOE
observed for Test Unit 2 that the 75
percent relative humidity test had
additional drain water collected during
the freeze cycles compared to the 35
percent relative humidity test. DOE
investigated whether this additional
drain water could have resulted from
additional condensation of moisture at
the higher relative humidity, and
whether the higher energy use for Test
Unit 2 at the 75 percent relative
humidity test condition may correspond
to such additional condensate being
produced at that test condition. If so,
this would indicate that the higher
energy use was directly related to the
relative humidity test condition.
Based on the technical characteristics
of Test Unit 2, DOE calculated the
theoretical amount of additional energy
use that would be required by Test Unit
2 to condense the amount of additional
drain water measured.20 DOE compared
19 See pages 34–35; www.regulations.gov/
document/EERE-2017-BT-TP-0006-0012.
20 DOE calculated the additional amount of heat
removal required from the evaporator of Test Unit
2 to condense the same amount of moisture from
the surrounding air that was observed in the
additional drain water from the 75% relative
humidity test. Subsequently, DOE calculated the
additional amount of compressor, sump pump, and
condenser fan motor energy and additional freeze
cycle duration that would be necessary to remove
this additional heat based on the Test Unit 2’s
compressor specification data at an assumed
E:\FR\FM\01NOR2.SGM
Continued
01NOR2
65874
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
the resulting theoretical amount of
additional energy use to the measured
amount of additional energy use. Table
III.5 shows the average measured drain
water (in lbs) and the average measured
energy use (in kWh) of the freeze cycles
for Test Unit 2. Table III.6 shows the
comparison of these measured values to
the theoretical amount of additional
energy use that would be required by
Test Unit 2 to condense this amount of
additional drain water, as calculated by
DOE.
TABLE III.5—SUMMARY OF DRAIN WATER AND ENERGY USE MEASUREMENTS FOR TEST UNIT 2
35% relative
humidity
Cycle description
Freeze cycle drain water (lbs) .....................................................................................................
Freeze cycle energy use (kWh) ..................................................................................................
75% relative
humidity
0.59
0.21
Difference
between 35%
and 75%
relative
humidity
1.01
0.32
0.43
0.11
TABLE III.6—COMPARISON OF THEORETICAL ADDITIONAL ENERGY USE TO MEASURED ADDITIONAL ENERGY USE FOR
TEST UNIT 2
Cycle description
Measured
difference
between 35%
and 75%
relative
humidity
Theoretical
energy use
required to
produce
0.43 lbs of
condensate
Freeze cycle energy use (kWh) ..............................................................................................................................
0.11
0.12
As indicated in Table III.6, DOE’s
calculated approach to determine the
additional energy use required to
condense the amount of additional
drain water measured closely matched
the measured approach. This indicates
that the additional energy use at the 75
percent relative humidity test condition
was likely due to the difference in
condensed moisture accumulated at the
75 percent test condition, thus
supporting that the relative humidity
level during the test may have a direct
impact on measured energy
performance.
DOE also evaluated additional test
data from previous investigative ACIM
testing to further confirm the effects of
relative humidity on measured energy
use. DOE previously tested four batch
style ACIMs at 55 and 75 percent
relative humidity using the standard
rating conditions specified in AHRI 810.
Although this testing was not conducted
at 35 percent relative humidity, the test
data is instructive on whether a
difference in relative humidity affects
ACIM performance. Table III.7
summarizes the results of this previous
testing.
TABLE III.7—COMPARISON OF ENERGY USE RATES AT DIFFERENT RELATIVE HUMIDITY TEST CONDITIONS
Test unit
lotter on DSK11XQN23PROD with RULES2
4
5
6
7
55% relative
humidity
(kWh/100 lb)
Type
Batch
Batch
Batch
Batch
..................................................................................................................
..................................................................................................................
..................................................................................................................
..................................................................................................................
These results show that for some
ACIM models, a difference in relative
humidity makes very little impact on
ACIM performance, but for other
models, a difference in relative
humidity makes a significant impact on
ACIM performance. Considering the
three tested units presented in the
December 2021 NOPR in addition to
these four units, out of a total test
sample of 7 ACIMs, relative humidity
had a significant impact on ACIM
performance for at least two ACIMs.
This suggests that a difference in
relative humidity may affect a
substantial portion of the ACIM market.
As summarized previously in this
section, comments received in response
to the December 2021 NOPR indicate
that certain manufacturers do not
measure relative humidity of the
ambient air during testing, and that
evaporator temperature of 15 °F and condenser
temperature of 115 °F, and sump pump and
condenser fan motor specification data with an
assumed power factor of 80%.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
PO 00000
Frm 00020
Fmt 4701
Sfmt 4700
9.45
17.47
30.33
40.46
75% relative
humidity
(kWh/100 lb)
9.30
21.58
30.56
40.49
Difference
from 55%
relative
humidity to
75%
relative
humidity
(%)
¥1.6
+23.5
+0.8
+0.1
ACIM test chambers typically do not
control the relative humidity of the
ambient air. Commenters also generally
suggested defining a broader tolerance
as compared to the proposed tolerance
of ±5 percent, asserting that controlling
relative humidity to within ±5 percent
during testing would be difficult.
Based on the additional analysis
discussed in this final rule, including
consideration of comments received in
E:\FR\FM\01NOR2.SGM
01NOR2
65875
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
response to the December 2021 NOPR,
DOE is modifying the relative humidity
test conditions adopted in this final
rule, as compared to the provisions as
proposed in the December 2021 NOPR,
to instead specify a minimum threshold
rather than a defined range. Specifically,
this final rule adopts a requirement to
maintain an average minimum ambient
relative humidity of 30.0 percent
throughout testing. This revised
specification represents the minimum of
the relative humidity tolerance, 35.0 ±
5.0 percent, as proposed in the
December 2021 NOPR and will allow for
a broader range of relative humidity
values that will be easier to control
during testing. Furthermore, DOE notes
that its test data indicated that higher
humidity levels are associated with
higher measured energy use for certain
ACIM models—suggesting that
manufacturers of such models will be
incentivized to test with relative
humidity levels as close to the
minimum defined threshold as possible.
See section III.F.1 of this final rule for
a discussion of DOE’s analysis of any
expected costs or impacts on measured
performance as a result of this
amendment.
b. Water Hardness
ASHRAE Standard 29–2015 and AHRI
Standard 810 (I–P)–2016 with
Addendum 1 do not specify the water
hardness of the water supply used for
testing. The United States Geological
Survey (‘‘USGS’’) defines water
hardness as the concentration of
calcium carbonate in milligrams per
liter (‘‘mg/L’’) of water and lists general
guidelines for the classification of water
hardness as 0 to 60 mg/L of calcium
carbonate for soft water; 61 to 120 mg/
L of calcium carbonate for moderately
hard water; 121 to 180 mg/L of calcium
carbonate for hard water; and more than
180 mg/L of calcium carbonate for very
hard water.21 In the January 2012 final
rule, DOE stated that harder water
depresses the freezing temperature of
water and results in increased energy
use to produce the same quantity of ice.
77 FR 1591, 1605. DOE also stated that
hard water (i.e., water with a higher
concentration of calcium carbonate) can
affect energy consumption in the field
due to increased scale build up on the
heat exchanger surfaces over time, and
the use of higher water purge quantities
to help flush out dissolved solids to
limit scale build up. Id. However, DOE
declined to set requirements for water
hardness for testing because of
insufficient information to allow proper
consideration of such a requirement. 77
FR 1591, 1605–1606. Specifically, DOE
did not have information regarding the
impact of variation in water hardness on
as-tested performance of ACIMs, and
therefore could not justify the additional
burden associated with establishing a
standardized water hardness
requirement at that time. Id.
As part of this rulemaking, DOE
conducted testing to investigate whether
changing the water hardness could
affect the energy consumption and
harvest rate of ACIMs. Testing was
conducted on new models (i.e., with
clean evaporators prior to accumulation
of any significant scale). DOE conducted
water hardness tests on three batch type
ice makers and one continuous type ice
maker.
According to the USGS, the vast
majority of water hardness in the United
States ranges from 0 mg/L to 250 mg/L
of calcium carbonate.22 Given the range
of water hardness in the United States,
DOE used a water hardness of 42 mg/
L of calcium carbonate for a ‘‘soft water’’
test (which also represented water
readily available at the test facility) and
a water hardness of 342 mg/L of calcium
carbonate for a ‘‘very hard water’’ test
(i.e., a 300 mg/L increase relative to the
soft water test to represent an extreme
comparison case). The ‘‘soft water’’ test
at 42 mg/L of calcium carbonate was
based on the water hardness of the
potable water at the testing facility
where the tests were conducted and
therefore no additional preparation of
the potable water was required to meet
the 42 mg/L of calcium carbonate water
hardness level. The ‘‘very hard water’’
test at 342 mg/L of calcium carbonate
was prepared by adding calcium
chloride and magnesium chloride
hexahydrate with a mass ratio of
304:139 to the potable water at the
testing facility to reach the water
hardness level of 342 mg/L of calcium
carbonate and the resulting mixture was
recirculated for sixteen hours to ensure
even mixing. DOE tested four ACIMs in
a test chamber with soft and very hard
water hardness at the standard rating
conditions to investigate the effect of
water hardness on harvest rate and
energy use. The results of these tests are
summarized in Table III.8.
TABLE III.8—ACIM PERFORMANCE DIFFERENCES OF SOFT WATER COMPARED TO VERY HARD WATER
Unit
lotter on DSK11XQN23PROD with RULES2
1
2
3
4
Harvest
rate with
soft water *
Type
Batch ..............................
Batch ..............................
Batch ..............................
Continuous .....................
Harvest rate
with very
hard water *
95
126
351
562
Difference
(%)
105
131
359
582
Energy
use with
soft water *
11
4
2.3
3.4
10.49
8.28
5.73
4.40
Energy use
with very
hard water *
9.43
7.96
5.64
4.18
Difference
(%)
¥10.1
¥3.9
¥1.6
¥5.0
These test results show that water
hardness can impact measured harvest
rates and energy consumption rates, and
that very hard water generally resulted
in more favorable performance than soft
water. DOE acknowledges that the
observed test results show the opposite
impact on performance than expected
and discussed in the January 2012 final
rule (i.e., that harder water would be
expected to increase energy
consumption).
In the December 2021 NOPR, DOE
proposed to require that water used for
testing have a maximum hardness of
180 mg/L of calcium carbonate. 86 FR
72322, 72337. DOE stated that
establishing a maximum water hardness
of 180 mg/L would ensure that ACIMs
are tested with water that is not
considered ‘‘very hard’’ according to the
USGS and that the tested water
hardness is within a range
representative of water hardness that
ACIMs are likely to experience in actual
use. Id.
In the December 2021 NOPR, DOE
proposed that water hardness must be
measured using a water hardness meter
with an accuracy of ±10 mg/L or taken
from the most recent version of the
water quality report that is sent by water
suppliers, which is updated at least
annually and is accessible at:
ofmpub.epa.gov/apex/safewater/
f?p=136:102. 86 FR 72322, 72337. DOE
21 See www.usgs.gov/special-topic/water-scienceschool/science/hardness-water?qt-science_center_
objects=0#qt-science_center_objectswater.usgs.gov/
owq/hardness-alkalinity.html.
22 See www.usgs.gov/media/images/map-waterhardness-united-states.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
PO 00000
Frm 00021
Fmt 4701
Sfmt 4700
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65876
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
expected that any test facilities in
locations with water supply hardness
greater than 180 mg/L would likely
already incorporate water softening
controls, and therefore this proposal is
not expected to require updates to
existing test facilities. Id. For this same
reason, DOE did not expect that this
proposal would impact rated
performance for any ACIMs tested
under the current DOE test procedure.
Id.
In the December 2021 NOPR, DOE
also noted that this proposal would not
conflict with any provisions of the
industry test and rating standards and
would provide additional specifications
to ensure the representativeness of the
results and improve the repeatability
and reproducibility of the test results.
86 FR 72322, 72337.
In the December 2021 NOPR, DOE
requested comment on its proposal that
water used for ACIM testing have a
maximum water hardness of 180 mg/L
of calcium carbonate and on whether
any test facilities would not have water
hardness supplied within the proposed
allowable range. 86 FR 72322, 72337.
DOE requested comment on whether the
supply water is softened when testing
ACIMs and, if the water is not softened,
the burden associated with
implementing controls for water
hardness. 86 FR 72322, 72337–72338.
Additionally, DOE requested
information on whether this
requirement should only be applicable
to potable water used to make ice (and
not any condenser cooling water). 86 FR
72322, 72338.
In response to the December 2021
NOPR, Hoshizaki agreed that water
hardness would be good to investigate
for the test standard. (Hoshizaki, No. 14,
p. 4) However, Hoshizaki and AHRI
requested that water hardness be
brought to the ASHRAE 29 committee
for consideration. (Hoshizaki, No. 14, p.
4; AHRI, No. 14, p. 5)
Joint Commenters supported DOE’s
proposal to introduce a water hardness
requirement to improve the
reproducibility of the test procedure.
(Joint Commenters, No. 15, p. 2) The
Joint Commenters added that since the
hardness of tap water varies throughout
the U.S., DOE’s proposal to establish a
water hardness condition will likely
increase the reproducibility of the test
procedure, and therefore stated support
for DOE’s proposal to establish a
maximum water hardness for testing of
180 mg/L, which will exclude very hard
water. Id.
AHRI commented that different
regions experience hard water that can
consistently exceed 180 mg/L, so this
issue would need to be evaluated across
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
regions to ensure that undue burden is
not being unfairly inflicted on specific
areas of the country. (AHRI, No. 14, p.
5) During the January 24, 2022 ACIM
test procedure public meeting, True
Manufacturing commented that their
test facilities have potable water that is
approximately 300 mg/L all year long.23
IOM commented that although DOE’s
test data showed that harvest rate
increases and energy use decreases
when increasing calcium carbonate
concentration, DOE does not provide
any details on the characteristics of their
test water besides calcium carbonate
concentration. (IOM, No. 11, p. 2) If the
‘‘very soft’’ water was created by
softening the ‘‘very hard’’ sample water
using a salt-based ion-exchange water
softener, the total dissolved solids (TDS)
of the test water would remain the same,
as ion-exchange systems simply replace
calcium and magnesium with sodium
chloride. Id. The act of softening ‘‘very
hard’’ water creates a high salinity
solution which might affect the freezing
point of water, causing the diminished
performance seen with ‘‘very soft’’
water. Id.
IOM commented the only way to
reliably supply consistent test water to
IOM’s laboratory with specifications
around calcium carbonate concentration
would be to implement reverse osmosis
systems, which are costly to install and
maintain, and consume a significant
amount of energy during use. (IOM, No.
11, p. 2)
IOM requested that if DOE were to
implement this rule, it should only be
applicable to the potable water used to
make ice, unless DOE is able to
demonstrate that hardness has an effect
on energy consumption in water-cooled
ACIMs. (IOM, No. 11, p. 2)
Comments from interested parties
indicated that some ACIM test facilities
have potable water with water hardness
above of 180 mg/L of calcium carbonate
and that softening or controlling the
water hardness would impose a burden
on certain manufacturers. DOE
acknowledges that DOE’s expectation in
the December 2021 NOPR that any test
facilities in locations with water supply
hardness greater than 180 mg/L would
likely already incorporate water
softening controls was incorrect and
therefore, updates to certain existing test
facilities would be needed to control for
water hardness. Although the USGS
designates water hardness above of 180
mg/L of calcium carbonate as very hard
water, DOE has determined that further
investigation is necessary before
establishing a water hardness test
23 See page 40; www.regulations.gov/document/
EERE-2017-BT-TP-0006-0012.
PO 00000
Frm 00022
Fmt 4701
Sfmt 4700
condition and is declining to specify a
water hardness range for ACIM testing
in this final rule. DOE notes that
because a specific water hardness range
is not specified, all water hardness
levels will be considered valid for ACIM
testing.
c. Ambient Temperature Gradient
The current ACIM test procedure
incorporates by reference section 5.1.1
of ASHRAE Standard 29–2009, which
stipulates that, with the ice maker at
rest, the vertical ambient temperature
gradient in any foot of vertical distance
from 2 inches above the floor or
supporting platform to a height of 7 feet
above the floor, or to a height of 1 foot
above the top of the ice maker cabinet,
whichever is greater, shall not exceed
0.5 °F/foot. This language, which is
consistent with the requirement in
section 5.1.1 of ASHRAE Standard 29–
2015, is consistent with the test room
requirements for residential
refrigerators, as specified in section 7.2
of ANSI–AHAM Standard HRF–1–1979,
‘‘Household Refrigerators, Combination
Refrigerator-Freezers, and Household
Freezers’’ (ANSI/AHAM HRF–1–1979),
the version of the AHAM standard that
was incorporated by reference in the
DOE test procedure for residential
refrigerators in a final rule published
August 10, 1982. 47 FR 34517. DOE
modified the requirements associated
with temperature gradient for
residential refrigerators, in a final rule
published April 21, 2014, to remove the
reference to a 7 feet height requirement
and require only that the gradient be
maintained to a height 1 foot higher
than the top of the unit. 79 FR 22320,
22335.
In the December 2021 NOPR, DOE did
not propose any changes to the ambient
temperature gradient requirements,
except through an updated reference to
ASHRAE Standard 29–2015, and
requested comment on this approach
and on whether any modifications
would improve test accuracy or
decrease test burden. 86 FR 72322,
72338.
In response to the December 2021
NOPR, Hoshizaki commented that if
ASHRAE 29–2015 is adopted, it
supports use of the ambient temperature
gradient requirements in that edition.
(Hoshizaki, No. 14, p. 4) AHRI agreed
with the adoption of ASHRAE Standard
29–2015 and its gradient requirements.
(AHRI, No. 13, p. 5)
DOE is maintaining in this final rule
the existing ambient temperature
gradient requirements, through an
updated reference to ASHRAE Standard
29–2015.
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
d. Ambient Temperature and Water
Temperature
The current DOE ACIM test procedure
incorporates by reference AHRI 810–
2007, which specifies an ambient
temperature of 90 °F and a supply water
temperature of 70 °F. AHRI Standard
810 (I–P)–2016 with Addendum 1
provides the same specifications.
However, many ice makers may be
installed in conditioned environments
such as offices, schools, hospitals,
hotels, and convenience stores (see 80
FR 4646, 4700 (Jan. 28, 2015)), which
may have ambient air temperatures and
supply water temperatures higher or
lower than those specified in AHRI
Standard 810.
In the December 2021 NOPR, DOE
proposed to maintain the single set of
rating conditions currently required in
the DOE test procedure. 86 FR
72322,72338. Specifically, DOE
proposed to maintain the reference to
AHRI Standard 810, through AHRI
Standard 810 (I–P)–2016 with
Addendum 1, for rating conditions
because those were selected as
representative, repeatable rating
conditions of this equipment. Id. As
noted, EPCA requires that if AHRI
Standard 810 is amended, DOE must
amend the test procedures for ACIM as
necessary to be consistent with the
amended AHRI test standard, unless
DOE determines, by rule, published in
the Federal Register and supported by
clear and convincing evidence, that to
do so would not meet the requirements
for test procedures regarding
representativeness and test burden. (42
U.S.C. 6314(7)(B)) DOE does not have
any contrary data or information
regarding the representativeness of the
conditions specified in AHRI Standard
810 (I–P)–2016 with Addendum 1.
In addition, the response of ACIM
refrigeration systems to varying ambient
conditions is different than the response
of refrigeration systems in other
refrigeration and heating, ventilation,
and air-conditioning (‘‘HVAC’’)
equipment. Other refrigeration or HVAC
equipment are typically designed to
maintain conditions within a space.
Accordingly, as ambient conditions
change, the refrigeration systems
typically cycle (or in the case of
variable-speed compressors, adjust
speed) to match the varying heat loads.
In the case of ACIMs, the refrigeration
system continuously operates while
actively making ice, as heat is
constantly removed from the water
throughout the freezing process. As a
result, introducing a second lowertemperature test condition would not
result in part-load operation for ACIMs
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
and would not additionally differentiate
between units based on a part-load
response, as is the case for other
refrigeration or HVAC equipment. Thus,
in the December 2021 NOPR, DOE
tentatively determined that the existing
test conditions provide representative,
repeatable rating conditions for this
equipment, and DOE expected that the
burden of introducing a second test
condition (which would approximately
double test duration) would not be
justified. 86 FR 72322,72339.
In the December 2021 NOPR, DOE
requested comment on its proposal to
maintain the existing ambient
temperature and water supply
temperature requirements. If
modifications should be considered to
improve test representativeness or
decrease test burden, DOE requested
supporting data and information. 86 FR
72322,72339.
In response to the December 2021
NOPR, AHRI commented that the
current 90 °F ambient temperature
(which includes 90 °F for both the
indoor ambient temperature and the
condenser air inlet temperature for
ACIMs with remote condensing units)
and 70 °F water inlet temperature test
conditions are representative for much
of the installed base. (AHRI, No. 13, p.
6) AHRI stated that changing the test
point would disrupt historical data and
understanding of the performance of the
equipment, for both manufacturers and
consumers. (Id.) Hoshizaki stated that
the existing ambient temperature and
water supply temperature requirements
provide representative, repeatable rating
conditions for this equipment.
(Hoshizaki, No. 14, p. 4)
AHAM commented that the 90 °F
ambient temperature is applicable to
commercial settings but not residential
settings and that any measured energy
use at a 90 °F ambient temperature is not
representative of real-world use because
most residential ice makers are installed
in air-conditioned spaces with ambient
temperature closer to 70 °F. (AHAM, No.
18, p. 10) AHAM clarified that they are
not suggesting that DOE lower the
proposed ambient temperature because
most of the test chambers used for
residential ice maker manufacturers are
set to 90 °F because that is the test
condition required for other
refrigeration products. Id. AHAM stated
that a second ambient condition would
create undue burden through additional
resource, personnel, and time
requirements for testing. Id.
DOE is maintaining in this final rule
the existing ambient temperature and
water supply temperature requirements.
PO 00000
Frm 00023
Fmt 4701
Sfmt 4700
65877
e. Water Pressure
As discussed in section III.C and
shown in Table III.2, ASHRAE Standard
29–2015 now includes water pressure
measurement requirements, whereas
ASHRAE Standard 29–2009 did not
address water pressure. Section 6.3 of
ASHRAE Standard 29–2015 directs that
the pressure of the supply water be
measured within 8 inches of the ACIM
and that the pressure remains within the
specified range (AHRI Standard 810–
2007 and 2016 both specify 30 ± 3 psig
water supply) during the period of time
that water is flowing into the ACIM
inlet(s).
Certain ACIMs do not continuously
draw water into the unit during the
entire test. The portions of the test when
the water inlet valve begins to open may
result in a short, transient state when
the water pressure falls outside of the
allowable tolerance. Eliminating such
transient periods would likely require
certain laboratories to re-configure their
water supply setups. Because of this
burden and the relatively low impact of
these transient periods on water
consumed (i.e., the transient periods are
typically very short relative to the
overall duration of water flow), in the
December 2021 NOPR, DOE proposed to
allow for water pressure to be outside of
the specified tolerance for a short period
of time when water begins flowing into
the unit. 86 FR 72322, 72339.
Section 2.4 of the DOE test procedure
for consumer dishwashers addresses
this same issue by requiring that the
specified water pressure be achieved
within 2 seconds of opening the water
supply valve. 10 CFR part 430, subpart
B, appendix C1. The sampling rate in
section 5.7 of ASHRAE Standard 29–
2015 requires a maximum interval
between data samples for water pressure
of no more than 5 seconds. Therefore, in
the December 2021 NOPR, DOE
proposed to clarify that water pressure,
when water is flowing into the ice
maker, must be within the allowable
range within 5 seconds of opening the
water supply valve. 86 FR 72322, 72339.
DOE did not expect that this proposal
would impact tested performance under
the current DOE test procedure as it
provides additional specificity regarding
the existing water pressure
requirements. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
require that water pressure when water
is flowing into the ice maker be within
the allowable range within 5 seconds of
opening the water supply valve. 86 FR
72322, 72339.
In response to the December 2021
NOPR, IOM supported DOE’s proposal
E:\FR\FM\01NOR2.SGM
01NOR2
65878
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
to allow 5 seconds after opening the
water supply valve for water pressure to
be in the allowable range. (IOM, No. 11,
p. 3) Hoshizaki and AHRI commented
they see the benefit to having an
allowable range for water supply
pressure but requests this be addressed
by the ASHRAE 29 standard committee
to ensure a consensus of the committee
to change such requirements.
(Hoshizaki, No. 14, p. 4; AHRI, No. 13,
p. 6)
AHAM commented that the maximum
five second sampling rate for water
pressure is unnecessary, impractical,
burdensome, and adds difficulty and
complexity to the test procedure.
(AHAM, No. 18, p. 12) AHAM
commented that energy measurement
only needs a timestamp and Watt-hour
reading at the beginning and end of the
test and that the intermediate scans
check for ambient and gradient
temperatures which can have a
sampling rate of 30 seconds to one
minute which is similar to the test
procedure for refrigeration products.24
Id. The sampling rate proposed in the
December 2021 NOPR is consistent with
the industry test standard requirements.
DOE has determined that the industry
standard approach is appropriate
because ACIMs typically have a shorter
overall test duration as compared to
other refrigeration products, and for
batch type ACIMs, the water fills may
represent only a portion of the test
period. Therefore, the more frequent
sampling interval is appropriate to
ensure the required water pressure is
maintained throughout the water fill
period, except for within the initial 5
seconds after opening the water supply
valve.
DOE is maintaining in this final rule
the requirement that water pressure,
when water is flowing into the ice
maker, be within the allowable range
within 5 seconds of opening the water
supply valve, consistent with the
December 2021 NOPR.
4. Test Setup and Equipment
Configurations
Since publication of the January 2012
final rule, DOE has issued two final
guidance documents addressing certain
aspects of the ACIM test procedure:
prohibiting the use of temporary baffles
and requiring use of a fixed purge water
setting. As discussed in the following
paragraphs, DOE has reviewed the
guidance documents to determine
whether they should be maintained and
expressly included in the test
procedure. In addition, in reviewing the
24 See 10 CFR part 430, subpart B, appendices A
and B.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
existing DOE ACIM test procedure, DOE
has determined that the
representativeness and repeatability of
the test procedure could be further
improved through certain test setup and
equipment configuration amendments
as discussed in the following
paragraphs.
a. Temporary Baffles
After publication of the January 2012
final rule, DOE issued a guidance
document on September 24, 2013,
regarding the use of temporary baffles
during testing.25 As described in the
guidance, a baffle is a partition, usually
made of a flat material such as
cardboard, plastic, or sheet metal, that
reduces or prevents recirculation of
warm air from an ice maker’s air outlet
to its air inlet, or, for remote condensers,
from the condenser’s air outlet to its
inlet. Temporary baffles refer to those
installed only temporarily during testing
and are not part of the ACIM model as
distributed in commerce or installed in
the field. During testing, the use of
temporary baffles can block
recirculation of warm condenser
discharge air to the air inlet. This would
reduce the average temperature of the
air entering the inlet, which would
result in lower energy use that would
not be representative of the energy use
of the unit as operated by the end user.
In the guidance document, DOE
expressly stated that installing such
temporary baffles is inconsistent with
the ACIM test procedure, which states
that the unit must be ‘‘set up for testing
according to the manufacturer’s written
instruction provided with the unit’’ and
that ‘‘no adjustments of any kind shall
be made to the test unit prior to or
during the test that would affect the ice
capacity, energy usage, or water usage of
the test sample.’’ 26 Therefore, DOE’s
final guidance stated that the use of
baffles to prevent recirculation of air
between the air outlet and inlet of the
ice maker during testing is not
consistent with the DOE test procedure
for automatic commercial ice makers,
unless the baffle is (a) a part of the ice
maker or (b) shipped with the ice maker
to be installed according to the
manufacturer’s installation instructions.
Based on the final guidance
document, DOE proposed in the
December 2021 NOPR to define the term
‘‘baffle’’ consistent with the description
in the guidance document and to
expressly prohibit the use of baffles
25 See www1.eere.energy.gov/buildings/
appliance_standards/pdfs/acim_baffles_faq_20139-24final.pdf.
26 Section 4.1.4, ‘‘Test Set Up,’’ of AHRI Standard
810–2007 and AHRI Standard 810 (I–P)–2016 with
Addendum 1.
PO 00000
Frm 00024
Fmt 4701
Sfmt 4700
when testing of ACIMs unless the baffle
is (a) a part of the ice maker or (b)
shipped with the ice maker to be
installed according to the
manufacturer’s installation instructions.
86 FR 72322, 72340. In the December
2021 NOPR, DOE stated the proposed
approach based on manufacturer
installation instruction is likely how an
ice maker would be installed during use
and is most representative of the energy
use of ACIMs operated in the field. Id.
DOE added that this proposal would not
add any burden or impact measured
performance compared to the existing
test procedure, as it is consistent with
how the test procedure currently must
be performed. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
expressly provide that a baffle must not
be used when testing ACIMs unless the
baffle is (a) a part of the ice maker or
(b) shipped with the ice maker to be
installed according to the
manufacturer’s installation instructions.
86 FR 72322, 72340.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed that
the unit should be installed in
accordance with the manufacturer’s
installation instructions, and that baffles
should only be used if instructed to do
so in installation instructions.
(Hoshizaki, No. 14, p. 4; AHRI, No. 13,
p. 6)
AHAM commented that DOE’s
proposal to expressly provide that a
baffle must not be used when testing
ACIMs unless the baffle is (a) a part of
the ice maker or (b) shipped with the ice
maker to be installed according to the
manufacturer’s installation instructions
fails to account for the differences
between built-in and freestanding ice
makers (i.e., built-in products must be
counter depth to be incorporated into
kitchen designs and be flush with
cabinetry). (AHAM, No. 18, p. 12)
AHAM commented that applying the
test as written may penalize
manufacturers of built-in products, as it
is not representative of their real-world
use. Id.
The proposal to expressly provide
that a baffle must not be used when
testing ACIMs unless the baffle is (a) a
part of the ice maker or (b) shipped with
the ice maker to be installed according
to the manufacturer’s installation
instructions is representative because a
baffle is permitted to be used in testing
if it is integral to the ice maker or
shipped with the ice maker and
instructed to be installed in the
manufacturer’s installation instructions.
Regarding other installation
requirements, DOE provides a
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
discussion of clearances in section
III.D.4.c of this final rule.
DOE is maintaining in this final rule
the requirement that a baffle must not be
used when testing ACIMs unless the
baffle is (a) a part of the ice maker or
(b) shipped with the ice maker to be
installed according to the
manufacturer’s installation instructions,
consistent with the December 2021
NOPR.
The guidance document issued by
DOE on September 24, 2013, also
acknowledged that warm air discharged
from an ice maker’s outlet can affect the
ambient air temperature measurement
such that it fluctuates outside the
maximum allowed ±1 °F or ±2 °F range,
and that baffles can prevent such
fluctuation. Because temporary baffles
are not permitted for use during testing,
DOE stated in the guidance document
that if the ambient air temperature
fluctuations cannot be maintained
within the required tolerances,
temperature measuring devices may be
shielded so that the indicated
temperature will not be affected by the
intermittent passing of warm discharge
air at the measurement location. DOE
also stated that the shields must not
block recirculation of the warm
discharge air into the condenser or ice
maker inlet.
Based on the final guidance
document, in the December 2021 NOPR,
DOE proposed to specify in the test
procedure that if the ambient air
temperature fluctuations (and relative
humidity as discussed in section
III.D.3.a) cannot be maintained within
the required tolerances, temperature
measuring devices (and relative
humidity measuring devices) may be
shielded to limit the impact of
intermittent passing of warm discharge
air at the measurement locations. 86 FR
72322, 72340. DOE further proposed
that if shields are used, they must not
block recirculation of the warm
discharge air into the condenser or ice
maker inlet. Id. DOE did not expect this
proposal to impact measured ACIM
performance compared to the existing
test procedure, as it is consistent with
the existing test approach. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
specify that temperature measuring
devices may be shielded to limit the
impact of intermittent warm discharge
air at the measurement locations and
that if shields are used, they must not
block recirculation of the warm
discharge air into the condenser or ice
maker air inlet. 86 FR 72322, 72340.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed with
DOE’s proposal to specify that
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
temperature measuring devices may be
shielded to limit the impact of
intermittent warm discharge air at the
measurement locations. (Hoshizaki, No.
14, p. 4; AHRI, No. 13, p. 6) However,
Hoshizaki requested that this be
addressed in the ASHRAE 29 standard
committee. (Hoshizaki, No. 14, p. 4)
DOE is maintaining in this final rule
the requirement that temperature and
relative humidity measuring devices
may be shielded to limit the impact of
intermittent warm discharge air at the
measurement locations and that if
shields are used, they must not block
recirculation of the warm discharge air
into the condenser or ice maker air inlet,
consistent with the December 2021
NOPR.
In the December 2021 NOPR, DOE
also requested comment on whether any
ACIM models discharge air such that
the temperature and relative humidity
measuring devices would be unable to
maintain the required ambient air
temperature or relative humidity
tolerances even with the measuring
devices shielded. 86 FR 72322, 72340. If
so, DOE requested comment on whether
alternate ambient air temperature and
relative humidity measurement
locations would be necessary (e.g., the
ambient temperature measurement
locations for water-cooled ice makers, if
those locations are not affected by
condenser discharge air) and if the
ambient air temperature and relative
humidity measured at the alternate
locations should be within the same
tolerances as would otherwise be
required. Id.
In response to the December 2021
NOPR, Hoshizaki and AHRI commented
that they are not aware of a need for
alternate ambient temperature locations.
(Hoshizaki, No. 14, p. 4; AHRI, No. 13,
p. 6)
Based on comments from interested
parties that alternate ambient air
temperature and relative humidity
measurement locations are not
necessary, DOE is maintaining the
current ambient measurement locations
for ACIM testing in this final rule,
except as discussed in section III.D.4.d.
b. Purge Settings
Purge water refers to water that is
introduced into the ice maker during an
ice-making cycle to flush dissolved
solids out of the ice maker and prevent
scale buildup on the ice maker’s wetted
surfaces. Ice makers generally allow for
setting the purge water controls to
provide different amounts of purge
water or different frequencies of purge
cycles. Different amounts of purge water
may be appropriate for different levels
of water hardness or contaminants in
PO 00000
Frm 00025
Fmt 4701
Sfmt 4700
65879
the ACIM water supply. Most ice
makers have manually set purge settings
that provide a fixed amount of purge
water, but some ice makers include an
automatic purge water control setting
that automatically adjusts the purge
water quantity based on the supply
water hardness.
Because purge water is cooled by the
ice maker, allowing a different purge
water quantity will result in a different
measured energy use. To ensure
representative and consistent test results
for ice makers with automatic purge
water controls, on September 25, 2013,
DOE issued final guidance stating that
ice makers with automatic purge water
control should be tested using a fixed
purge water setting that is described in
the written instructions shipped with
the unit as being appropriate for water
of normal, typical, or average
hardness.27 DOE further stated that the
automatic purge setting should not be
used for testing.
Consistent with DOE’s existing
guidance, in the December 2021 NOPR,
DOE proposed that ice makers with
automatic purge water control must be
tested using a fixed purge water setting
that is described in the manufacturer’s
written instructions shipped with the
unit as being appropriate for water of
normal, typical, or average hardness. 86
FR 72322, 72341. Such a control setting
is likely to reflect the most typical ACIM
installation and operation. Any other
automatic purge controls (i.e., those
without any user-controllable settings)
would operate as they would during
normal use. Additionally, while ACIMs
may be installed and set up by service
technicians based on the installation
location, such setup is not appropriate
for testing because it may introduce
variability in test settings based on the
test facility location. Consistent with
DOE’s existing guidance, DOE also
proposed that purge water settings
described in the instructions as suitable
for use only with water that has higher
or lower than normal hardness (such as
distilled water or reverse osmosis water)
must not be used for testing. Id.
DOE stated that this proposal would
not conflict with any of the setup or
installation requirements in AHRI
Standard 810 (I–P)–2016 with
Addendum 1. 86 FR 72322, 72341.
Additionally, this proposal would not
add burden to manufacturers or impact
ACIM performance as measured under
the existing test procedure, as it would
codify the final guidance document
issued on September 25, 2013,
27 See www1.eere.energy.gov/buildings/
appliance_standards/pdfs/acim_purge_faq_2013-925final.pdf.
E:\FR\FM\01NOR2.SGM
01NOR2
65880
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
specifying use of a fixed purge setting.
Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
require ACIMs with automatic purge
water control to be tested using a fixed
purge water setting that is described in
the manufacturer’s written instructions
shipped with the unit as being
appropriate for water of normal, typical,
or average hardness. 86 FR 72322,
72342.
In response to the December 2021
NOPR, Hoshizaki and AHRI requested
that units be tested per normal operating
instructions in accordance with
manufacturer installation instructions.
(Hoshizaki, No. 14, p. 5; AHRI, No. 13,
p. 7)
DOE is maintaining in this final rule
the requirement that ACIMs with
automatic purge water control be tested
using a fixed purge water setting that is
described in the manufacturer’s written
instructions shipped with the unit as
being appropriate for water of normal,
typical, or average hardness, consistent
with the December 2021 NOPR.
In support of the December 2021
NOPR, DOE conducted testing to
investigate the energy and water
consumption associated with flush or
purge cycles. 86 FR 72322, 72341. DOE
testing of a batch ACIM showed that the
purge occurred once every 5 hours
under the default setting and coincided
with the start of a harvest, resulting in
no separate purge cycle. Id. Table III.9
summarizes how a purge cycle
contributes to the energy and water
consumption of a continuous ACIM. Id.
Table III.10 presents DOE’s estimates of
the test durations under the existing test
approach and under an approach that
would account for purge operation. Id.
TABLE III.9—SUMMARY OF ENERGY & WATER CONSUMPTION OF A CONTINUOUS ACIM WITH PURGE CYCLE
Average
power draw
(W)
Mode
Ice Production ..............................................................................................................................
Purge (every 12 hours by default) ...............................................................................................
Recovery after Purge ...................................................................................................................
Energy
consumption
(kWh)
936
35
1,062
Average
water usage
(lbs)
11.23
0.01
0.08
* 275
2.0
N/A
* This number represents the harvest weight during the associated operating period. The total amount of water used may be higher.
N/A: The water used during the recovery after purge does not differ from normal ice production.
TABLE III.10—SUMMARY OF ESTIMATED TEST DURATIONS WITH AND WITHOUT INCLUDING PURGE CYCLES
Duration (hours)
Test unit
Existing ice
production test
(without purge)
Existing
test total
(without purge)
Ice
production test
(with purge)
2
2
8
8
12.5
5.5
lotter on DSK11XQN23PROD with RULES2
Continuous .......................................................................................................
Batch ................................................................................................................
DOE observed that purge cycles for
both batch and continuous ACIMs did
not significantly contribute to the
energy consumption over a period of
normal operation.
Accounting for purge cycle operation
would require extending the test period
to capture both stable ice production
and normal purge operation.
The energy and water consumption
during the flush or purge cycles are very
small relative to the energy and water
consumed during normal ice
production, and the additional test
burden associated with measuring purge
events would be a significant increase in
test burden. Therefore, in the December
2021 NOPR, DOE did not propose to
address flush or purge cycles in its test
procedure. 86 FR 72322, 72342.
In the December 2021 NOPR, DOE
requested comment on its initial
determination to not directly account
for energy or water used during
intermittent flush or purge cycles. 86 FR
72322, 72342. DOE also requested data
regarding the energy and water use
impacts of purge cycles. Id.
In response to the December 2021
NOPR, Hoshizaki agreed with DOE that
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
the test should not be changed to
account for intermittent flush or purge
cycles. (Hoshizaki, No. 14, p. 5)
Hoshizaki added that accounting for
purge cycles would require a significant
increase in total test time, resulting in
significant increase in test burden with
only a small amount of energy and
water contribution. (Hoshizaki, No. 14,
p. 5) During the January 24, 2022 ACIM
test procedure public meeting,
Hoshizaki stated that for continuous
ACIMs, a normal purge cycle contains
less than five ounces of water and
occurs once every 12 hours.28
Joint Commenters stated that DOE
may have underestimated the frequency
of purge cycles, citing the DOE’s test of
a batch type ACIM with a default purge
setting of a purge every 5 hours
(coinciding with the start of a harvest,
resulting in no separate purge cycle).
(Joint Commenters, No. 15, p. 2)
However, Joint Commenters added that
for batch type ACIMs, the purge water
setting used in the field may differ from
that in the manufacturer’s instructions
28 See page 47; www.regulations.gov/document/
EERE-2017-BT-TP-0006-0012.
PO 00000
Frm 00026
Fmt 4701
Sfmt 4700
Test total
(with purge)
18.5
11.5
or default settings and may be set such
that a separate purge cycle occurs as
frequently as every batch cycle. Id. Joint
Commenters encouraged DOE to
investigate how the purge cycle settings
in field installations may differ from the
manufacturer default settings for ACIMs
and to consider capturing the purge
cycle energy in the test procedures. Id.
DOE is not aware of and did not
receive any data to indicate how purge
water settings used in the field may
differ from that in the manufacturer’s
instructions or default settings.
However, if a default purge setting was
as frequent as every batch cycle, purges
would be accounted for in the amended
ACIM test procedure because the
batches would likely be consistent even
with the purge occurring every cycle
and therefore the batches would meet
the stability criteria as amended in this
final rule.
DOE is maintaining in this final rule
its determination to not directly account
for energy or water used during
intermittent flush or purge cycles,
consistent with the December 2021
NOPR.
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
c. Clearances
As discussed in section III.C and
shown in Table III.2, the clearance
requirements around a unit under test
changed between ASHRAE Standard
29–2009 and ASHRAE Standard 29–
2015. The current DOE test procedure,
through reference to section 6.4 of
ASHRAE Standard 29–2009, requires a
clearance of 18 inches on all four sides
of the test unit, while section 6.5 of
ASHRAE Standard 29–2015 requires a
minimum clearance of 3 feet to adjacent
test chamber walls, or the minimum
clearance specified by the manufacturer,
whichever is greater.
In response to the March 2019 RFI,
Howe Corporation (‘‘Howe’’)
commented that it is reasonable for
customers to expect units to perform at
their ratings when using the minimum
clearances as described in the
manufacturer literature. Howe
recommended that DOE require a
clearance of 3 feet, or the minimum
clearance allowed by the manufacturer,
whichever is less, to better represent an
average use cycle. Howe also
commented that this clearance should
include all machine clearances, not just
walls within the test chamber, and that
a minimum clearance enclosure be built
for testing ACIMs based on the harshest
manufacturer-recommended operating
installation, without blocking an intake
air path to the ice maker. Howe also
commented that this setup would not be
a large test burden as many
manufacturers test units of similar size,
and the enclosures could be used over
multiple tests. (Howe, No. 6 at p. 4)
65881
In support of the December 2021
NOPR, DOE conducted testing to assess
how different clearance requirements
could affect the measured energy
consumption and harvest rate of ACIMs.
86 FR 72322, 72342. DOE investigated
the performance of ACIMs under four
clearance setups: (1) the clearance
required by ASHRAE Standard 29–2015,
(2) the clearance required by the current
DOE test procedure (through reference
to ASHRAE Standard 29–2009), (3) all
minimum clearances as recommend by
the manufacturer, and (4) the rear
minimum clearance as recommend by
the manufacturer with all other
clearances per ASHRAE Standard 29–
2015. Id. Table III.11 summarizes how
four test units performed under the four
clearance setups. Id.
TABLE III.11—SUMMARY OF CLEARANCE IMPACT ON ACIM PERFORMANCE
Test unit
1
2
3
lotter on DSK11XQN23PROD with RULES2
4
ASHRAE Standard 29–2015 .................................................
Current DOE Test Procedure ................................................
Minimum Clearances .............................................................
Minimum Rear Clearance ......................................................
ASHRAE Standard 29–2015 .................................................
Current DOE Test Procedure ................................................
Minimum Clearances .............................................................
Minimum Rear Clearance ......................................................
ASHRAE Standard 29–2015 .................................................
Current DOE Test Procedure ................................................
Minimum Clearances .............................................................
Minimum Rear Clearance ......................................................
ASHRAE Standard 29–2015 .................................................
Current DOE Test Procedure ................................................
Minimum Clearances .............................................................
Minimum Rear Clearance ......................................................
The tests indicate that the different
clearance requirements, except for the
installation with all minimum
clearances, have little to no impact on
the measured performance of ACIMs. Id.
The impact observed from the minimum
clearance test is likely due to the
exhaust air being directed through the
test enclosure (i.e., the minimum
clearances on the sides, back, and top of
the ACIM resulted in an enclosure
guiding condenser exhaust air) back to
the front air inlet on the ACIM, which
results in the ACIM drawing in warmer
air than under the three other setup
configurations. Id. As described in
section III.D.4.a, testing with a
temporary baffle to prevent such air
flow is not appropriate, so the
condenser exhaust re-circulated during
this investigative testing. Id.
VerDate Sep<11>2014
Harvest rate
(lbs of
ice/24hrs)
Clearance setup
18:03 Oct 31, 2022
Jkt 259001
573
575
548
576
814
815
794
820
1,164
1,164
1,043
1,149
1,197
1,195
1,105
1,197
Based on these test results, an
installation configuration that provides
only the minimum manufacturer test
clearances for all sides represents a
worst-case installation for ACIM
performance. Id. While manufacturers
might provide minimum clearances for
all sides of a unit, the expectation may
be that units are installed such that one
or more of the sides has clearance
exceeding the manufacturer minimum.
Id.
Similarly, a minimum clearance of 3
feet to adjacent test chamber walls or a
clearance of 18 inches on all four sides
(as required by ASHRAE Standard 29–
2015 and the current DOE test
procedure, respectively) may also not be
a typical ACIM installation. Id. Because
ACIMs are typically installed in
commercial food service applications
PO 00000
Frm 00027
Fmt 4701
Sfmt 4700
Change in
harvest rate
(from
ASHRAE
standard
29–2015)
N/A
0%
¥4%
1%
N/A
0%
¥2%
1%
N/A
0%
¥10%
¥1%
N/A
0%
¥8%
0%
Energy
consumption
(kWh/100 lbs
of ice)
4.93
4.97
5.25
4.94
4.46
4.48
4.59
¥4.41
4.41
4.46
5.14
4.44
5.40
5.43
6.04
5.39
Change
in energy
consumption
(from
ASHRAE
standard
29–2015)
N/A
1%
6%
0%
N/A
0%
3%
1%
N/A
1%
17%
1%
N/A
1%
12%
0%
with space constraints, such as
commercial kitchens, end users likely
install their ACIMs against at least a rear
wall using the manufacturer minimum
clearance to maximize available
working space. Id. Based on the test data
in Table III.10, testing according to the
manufacturer-specified minimum rear
clearance has little to no measured
impact on ACIM performance for the
four test units. Id. However, because
ACIMs may exhaust condenser air from
the rear of the unit, an inappropriate
manufacturer minimum rear clearance
(or lack of manufacturer instructions
regarding rear clearance) could
adversely affect ACIM performance
while being representative of typical
use, and should be captured in the
tested performance. Id.
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65882
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
Therefore, in the December 2021
NOPR, DOE proposed that ACIMs be
tested according to the manufacturer’s
specified minimum rear clearance
requirements, or 3 feet from the rear of
the ACIM, whichever is less. 86 FR
72322, 72343. DOE proposed testing be
conducted with a minimum clearance of
3 feet or the minimum clearance
specified by the manufacturer,
whichever is greater, on all other sides
of the ACIM and all sides of the remote
condenser, if applicable. Id. As
discussed, and shown in the DOE test
data, the impact of this proposed change
on measured energy use for currently
certified ACIMs would likely be de
minimis. Id. DOE expected
manufacturer installation instructions
would typically provide for clearances
that would ensure sufficient air flow to
avoid any adverse impacts on ACIM
performance under the proposed test
setup. Id.
In the December 2021 NOPR, DOE did
not propose specific requirements for
the wall used to maintain the rear
clearance when conducting the test. 86
FR 72322, 72343. Test laboratories
would be able to satisfy the clearance
requirements in any way they choose, as
long as the test installation meets the
proposed requirements. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
require that ACIMs be tested according
to the manufacturer’s specified
minimum rear clearance requirements,
or 3 feet from the rear of the ACIM,
whichever is less, and that all other
sides of the ACIM and all sides of the
remote condenser, if applicable, shall be
tested with a minimum clearance of 3
feet or the minimum clearance specified
by the manufacturer, whichever is
greater. 86 FR 72322, 72343. DOE also
requested comment on whether this
proposal would affect measured energy
use and harvest rate compared to the
existing DOE test procedure. Id.
In response to the December 2021
NOPR, Hoshizaki requested that this be
explored in the ASHRAE 29 standard
committee to clarify any changes to the
current test specifications. (Hoshizaki,
No. 14, p. 5) IOM did not support this
proposal to change clearance
requirements. (IOM, No. 11, p. 3)
AHRI commented that depending on
the condenser location and air
discharge, changes to the clearance
requirements could impact performance
of the unit. (AHRI, No. 13, p. 7) IOM
commented that reducing the rear
minimum clearance will very likely
increase measured energy use and
decrease measured harvest rate. (IOM,
No. 11, p. 3) IOM added that minimum
clearances are established to provide
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
guidelines for installation from a
product safety standpoint, not a
performance standpoint, and it is well
understood in the industry that
increasing clearance around the unit
will result in improved performance
and efficiency. Id.
IOM commented that measuring
performance and efficiency of a product
in its worst possible installation
configuration is unfair to manufacturers.
(IOM, No. 11, p. 3) AHRI added that the
requirements in ASHRAE Standard 29
are clear and effective regarding the
clearance allowed and changes to these
requirements could result in undue
burden to test facilities that have
already setup for ASHRAE 29
requirements. (AHRI, No. 13, p. 7)
DOE notes that, in response to the
March 2019 RFI, Howe commented that
it is reasonable for customers to expect
ACIMs to perform at their certified
ratings when using the minimum
clearances as described in the
manufacturer literature. (Howe, No. 6 at
p. 4) While manufacturers might
provide minimum clearances for all
sides of an ACIM, the expectation may
be that ACIMs are installed such that
one or more of the sides have clearances
exceeding the manufacturer minimum.
ACIMs may have different condenser
locations and air discharge but because
ACIMs are typically installed in
commercial food service applications
with space constraints, end users likely
install their ACIMs against at least a rear
wall using the manufacturer minimum
clearance to maximize available
working space and, therefore, the
manufacturer’s minimum rear clearance
should be accounted for in the tested
performance. Based on the test data in
Table III.10, testing according to the
manufacturer-specified minimum rear
clearance has little to no measured
impact on ACIM performance for the
four test units. However, because ACIMs
may exhaust condenser air from the rear
of the unit, an inappropriate
manufacturer minimum rear clearance
(or lack of manufacturer instructions
regarding rear clearance) could
adversely affect ACIM performance
while being representative of typical use
and should be captured in the tested
performance.
DOE notes that, in the December 2021
NOPR, DOE did not propose specific
requirements for the wall used to
maintain the rear clearance, which is
the only change from the ASHRAE 29–
2015 clearance requirements, when
conducting the test and that test
facilities would be able to setup the
clearance requirements in any way they
choose, as long as the test installation
PO 00000
Frm 00028
Fmt 4701
Sfmt 4700
meets the proposed requirements, in
order to limit any potential test burden.
DOE will consider any updated
industry standards, if available, during
future ACIM test procedure
rulemakings.
DOE is maintaining in this final rule
that ACIMs be tested according to the
manufacturer’s specified minimum rear
clearance requirements, or 3 feet from
the rear of the ACIM, whichever is less,
consistent with the December 2021
NOPR. On all other sides of the ACIM
and all sides of the remote condenser,
if applicable, testing shall be conducted
with a minimum clearance of 3 feet or
the minimum clearance specified by the
manufacturer, whichever is greater. Test
laboratories may satisfy the clearance
requirements in any way they choose, as
long as the test installation meets the
amended requirements.
d. Ambient Temperature Measurement
Air temperature fluctuations from the
test chamber or the ACIM’s condenser
exhaust air can potentially affect an
ACIM’s measured energy consumption
and harvest rate.
i. Ambient Temperature Sensors
The current ACIM test procedure,
which is based on AHRI Standard 810–
2007 and ASHRAE Standard 29–2009,
does not specify whether a weighted or
unweighted sensor is to be used to
measure ambient temperature. A
weighted sensor measures the
temperature of a high conductivity
(isothermal) mass to which it is
connected. The mass slows
equilibration of the measured
temperature with the surrounding air,
thus damping out air temperature
fluctuations. This may result in a
weighted sensor indicating that the
fluctuations are within the required
temperature test condition tolerances,
whereas an unweighted sensor could
indicate temperature extremes
exceeding the required temperature test
condition tolerances. This difference in
function of the sensors impacts the
application of the required temperature
test condition tolerances, i.e.,
temperature fluctuations that fall
outside the required tolerances may not
be detected when using a weighted
sensor, but would be detected when
using an unweighted sensor.
In support of the December 2021
NOPR, DOE conducted testing to
evaluate the ability to meet the specified
tolerances of ASHRAE Standard 29–
2015 using both weighted and
unweighted temperature sensors. 86 FR
72322, 72344. The temperature
fluctuations recorded by weighted
temperature sensors may be less than
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
those recorded with unweighted
measurement due to damping of the
fluctuations by the weighted thermal
mass. Id. As such, weighted sensors may
give the false impression that ambient
temperature test condition tolerances of
±2 °F during the first 5 minutes of each
freeze cycle, and not more than ±1 °F
thereafter, are met during testing. Id.
The measurement of ambient
temperature using unweighted sensors
provides more representative measures
of actual instantaneous ambient
temperature conditions than the
measurement of weighted sensors. Id.
DOE observed in its testing in support
of the December 2021 NOPR that the
ambient temperature was within the test
condition tolerances specified in
ASHRAE Standard 29–2015 for all
freeze cycles when using either
weighted or unweighted sensors. Id.
Therefore, in the December 2021
NOPR, DOE proposed to specify that
unweighted sensors be used to make all
ambient temperature measurements. 86
FR 72322, 72344. Based on comments
received in the March 2019 RFI, this
proposal reflects current industry
practice and would not add any burden.
Id. This proposal is consistent with
AHRI Standard 810 (I–P)–2016 with
Addendum 1 because it specifies the
instrumentation for measuring ambient
temperature, but does not otherwise
change the existing requirements. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
specify that ambient temperature
measurements be made using
unweighted sensors. 86 FR 72322,
72344.
In response to the December 2021
NOPR, Hoshizaki agreed with the
proposal, but noted that if a clarification
is needed that this be addressed by the
ASHRAE 29 standard committee.
(Hoshizaki, No. 14, p. 5) AHRI
commented that the testing location is
currently allowed to designate the
sensor type used, and this has not
negatively impacted ratings or product
performance and therefore should not
be changed without further clarification
of issues that it may resolve and
discussion at the method of test level.
(AHRI, No. 13, p. 7) AHRI added that
the change to requiring unweighted
sensors could incur associated costs
without providing benefits to the test
results, but if such a change is to be
considered, it should go through the
ASHRAE 29 standards committee. Id.
AHRI noted that this issue has been
debated within other refrigeration
ASHRAE committees continuously
without conclusions being reached that
unweighted sensors should be required.
Id.
AHAM commented that in DOE’s
proposed test procedure the mean of the
ambient temperatures is more important
than a momentary fluctuation of
temperature. (AHAM, No. 18, p. 13)
AHAM commented in support of
weighted sensors because they would
dampen the influence of other units
being simultaneously tested on the
ambient and gradient measurements and
disagreed with the use of unweighted
sensors because they are more easily
influenced by changes in temperature,
including those resulting from opening
and closing the test room door. Id.
AHAM stated that, similar to DOE’s test
procedure for refrigeration products,
weighted sensors are appropriate for
testing residential ice makers in order to
compensate for the fluctuations
occurring during testing. Id.
Based on DOE’s analysis indicating
that the specified test conditions can be
met with an unweighted sensor, which
was presented in the December 2021
NOPR, DOE is maintaining in this final
rule that ambient temperature
measurements be made using
unweighted sensors, consistent with the
December 2021 NOPR.
ii. Alternative Ambient Measurement
Locations
The current DOE guidance and
proposal in the December 2021 NOPR
65883
regarding the use of temporary baffles,
as discussed in section III.D.4.a,
illustrates that temporary baffles can
reduce or prevent recirculation of warm
air from an ACIM’s condenser exhaust
air to its air inlet. This recirculation of
warm air can potentially affect an
ACIM’s measured energy consumption
and harvest rate and using a temporary
baffle for testing is unrepresentative of
actual ACIM use. The recirculation of
warm air may also affect the ability to
maintain ambient temperature within
the range specified in AHRI Standard
810 (I–P)–2016 with Addendum 1 and
relative humidity within the range
proposed in the December 2021 NOPR.
For example, if the condenser exhaust is
warm enough and directed towards the
air inlet location (and corresponding
ambient temperature measurement), the
measured ambient temperature may be
warmer than the representative ambient
temperature around the unit under test,
even with shielding around the
temperature sensor.
To evaluate the extent of this
potential impact on temperature, DOE
tested, in support of the December 2021
NOPR, an ACIM which exhausted its
warm condenser air on the side of the
ACIM adjacent to the side with the air
intake. 86 FR 72322, 72344. Three
ambient thermocouples were placed 1
foot from the geometric center of each
side around the ACIM in addition to the
unshielded ambient thermocouple that
was placed 1 foot from the air inlet. Id.
The unshielded ambient thermocouple
that was located 1 foot from the air inlet
was used to control the test chamber
conditions in accordance with AHRI
Standard 810 (I–P)–2016 with
Addendum 1 (i.e., the overall chamber
temperature was reduced as necessary
to maintain the temperature one foot in
front of the air inlet as close to 90 °F as
possible). Id. Table III.12 summarizes
the results of this testing.
TABLE III.12—AVERAGE AMBIENT TEMPERATURES MEASURED ON EACH SIDE AROUND AND ACIM
Inlet
(°F)
Exhaust
(°F)
lotter on DSK11XQN23PROD with RULES2
89.9 ..............................................................................................................................................
As shown in Table III.12, the air
within the chamber had to be reduced
below 89 °F (outside the 90 ± 1 °F
allowable ambient temperature range
specified in ASHRAE Standard 29–
2015) to maintain the temperature at the
air inlet near the specified 90 °F
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
condition. Id. This data suggests that
ACIM models that allow the warm
condenser exhaust air to recirculate to
the air intake may require lower overall
ambient test chamber temperatures to
maintain the specified condition at the
air inlet. Id.
PO 00000
Frm 00029
Fmt 4701
Sfmt 4700
90.2
Opposite side
of exhaust
(°F)
Opposite side
of inlet
(°F)
88.5
88.2
The ambient temperature
measurement is meant to represent the
temperature of the air around the unit
under test that is not impacted by unit
operation. Id. Because test facilities may
have difficulty effectively shielding the
air inlet thermocouple from warm
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65884
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
discharge air without blocking the
recirculation of that air to the ACIM air
inlet, as discussed in section III.D.4.a.,
in the December 2021 NOPR, DOE
proposed that the ambient temperature
may be recorded at an alternative
location. Id. DOE proposed that for
ACIMs in which warm air discharge
impacts the ambient temperature as
measured in front of the air inlet (i.e.,
the warm condenser exhaust airflow is
directed to the ambient temperature
location in front of the air inlet), the
ambient temperature may instead be
measured at locations 1 foot from the
cabinet, centered with respect to the
sides of the cabinet, for each side of the
ACIM cabinet with no air discharge or
inlet. Id. DOE expected that this
proposal would not impact measured
ACIM performance compared to the
existing test approach. 86 FR 72322,
72344–72345. DOE also proposed that
the relative humidity measurement, as
proposed in the December 2021 NOPR,
would also be made at the same
alternative locations. 86 FR 72322,
72345.
Test installation according to the
manufacturer’s minimum rear clearance
requirements, as discussed in section
III.D.4.c, may affect the ability to
measure the ambient temperature and
relative humidity one foot from the air
inlet if the air intake is through the rear
side of the ACIM and the minimum rear
clearance is less than 1 foot from the air
inlet. Id. Additionally, the alternate
measurement location, as proposed in
the December 2021 NOPR, would not be
feasible for the rear side of a model with
no air discharge or inlet on that side and
with a minimum rear clearance of less
than 1 foot. Id.
In the December 2021 NOPR, DOE
proposed that if a measurement location
1 foot from the rear of an ACIM is not
feasible for testing that would otherwise
require a measurement at that location,
the ambient temperature and relative
humidity shall instead be measured 1
foot from the cabinet, centered with
respect to the surface(s) of the ACIM, for
any surfaces around the perimeter of the
ACIM that do not include an air
discharge or air inlet. 86 FR 72322,
72345. DOE similarly did not expect
this proposal to impact current ACIM
measurements as it provides an
alternative measurement location for the
existing ambient temperature and
relative humidity requirements. 86 FR
72322, 72345.
In the December 2021 NOPR, DOE
requested comment on its proposal to
allow for an alternate ambient
temperature (and relative humidity)
measurement location to avoid
complications associated with shielding
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
the measurement in front of the air inlet,
as currently required. 86 FR 72322,
72345. DOE also requested comment on
the proposal for measuring ambient
temperature and relative humidity for
ACIMs for which the proposed rear
clearance would preclude temperature
measurements at the rear of the unit
under test. Id.
In response to the December 2021
NOPR, Hoshizaki and AHRI commented
that if manufacturers need an alternate
location for ambient temperatures, this
can either be addressed by waiver or
addressed through the ASHRAE 29
standard committee to change the
requirements. (Hoshizaki, No. 14, p. 5;
AHRI, No. 13, p. 7) AHRI added it does
not feel that a dictated alternative
measurement location will address any
concerns that may arise with a
particular model. (AHRI, No. 13, p. 7)
As discussed in section III.D.4.c, DOE
is maintaining that ACIMs be tested
according to the manufacturer’s
specified minimum rear clearance
requirements, or 3 feet from the rear of
the ACIM, whichever is less. The
alternate measurement location is
necessary to allow for testing certain
equipment configurations—for example,
if the air intake is through the rear side
of the ACIM and the minimum rear
clearance is less than 1 foot from the air
inlet. Therefore, DOE is maintaining in
this final rule to allow for an alternate
ambient temperature (and relative
humidity) measurement location,
consistent with the December 2021
NOPR.
e. Ice Cube Settings
DOE is aware that some ice makers
have the capability to make various
sizes of cubes. The size of the cube can
typically be selected on the control
panel of the ice maker, for example.
Section 5.2 of AHRI Standard 810 (I–P)–
2016 with Addendum 1 states that for
machines with adjustable ice cube
settings, standard ratings are determined
for the largest and the smallest cube
settings, and that ratings for
intermediate cube settings may be
published as application ratings. This is
consistent with the current DOE
requirement as incorporated by
reference in AHRI Standard 810–2007.
In the December 2021 NOPR, DOE did
not propose any change to the existing
industry requirement to determine
ratings under the largest and smallest
cube settings for ACIMs with adjustable
ice cube settings. 86 FR 72322, 72345.
EPCA requires the DOE test procedure
to be reasonably designed to produce
test results which reflect energy use
during a representative average use
cycle. The current requirement to test
PO 00000
Frm 00030
Fmt 4701
Sfmt 4700
using the largest and smallest cube
setting is based on the industry
standard, which was developed based
on industry’s experience with this
equipment. There is no information to
support that testing at the ‘‘worst
possible configuration’’ would be
representative of an average use cycle.
As such, DOE did not propose to change
the current requirement to test at both
the smallest and largest cube setting,
which is the same as the requirement in
AHRI Standard 810 (I–P)–2016 with
Addendum 1. Id.
In the December 2021 NOPR, DOE
requested comment on maintaining the
current requirement to test at the largest
and smallest ice cube size settings,
consistent with AHRI Standard 810 (I–
P)–2016 with Addendum 1. 86 FR
72322, 72345. DOE also requested
information on the ice cube size setting
typically used by customers with ACIMs
with multiple size settings (largest,
smallest, default, etc.). 86 FR 72322,
72345.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed with
maintaining the requirements set by
AHRI Standard 810 (I–P)–2016 with
Addendum 1 for cube size settings.
(Hoshizaki, No. 14, p. 5; AHRI, No. 13,
p. 8)
DOE is maintaining in this final rule
the current requirement to test at the
largest and smallest ice cube size
settings, consistent with AHRI Standard
810 (I–P)–2016 with Addendum 1.
f. Ice Makers With Dispensers
DOE is aware of certain self-contained
ACIMs that dispense ice to a user
through an automatic dispenser when
prompted by the user. Testing according
to the current DOE test procedure or the
updated industry standards as proposed
in the December 2021 NOPR may be
difficult or impossible for certain ACIM
configurations with automatic
dispensers. 86 FR 72322, 72345.
Section 6.6 in ASHRAE Standard 29–
2015 specifies that an ACIM must have
its bin one-half full of ice when
collecting capacity measurements. DOE
is aware of self-contained ACIMs with
dispensers that contain internal storage
bins that are not accessible during
normal operation (i.e., users access the
ice only through use of the dispenser).
Because the internal bins are not
accessible during normal operation, it
can be difficult or impossible to
establish a storage bin one-half full of
ice for testing. Additionally, isolating
the ice produced during testing from the
ice initially placed in a one-half full
storage bin may be difficult or
impossible, depending on the dispenser
and internal storage bin configuration.
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
Section 6.10 of ASHRAE Standard
29–2015 requires that the ACIM be
completely assembled with all panels,
doors, and lids in their normally closed
positions during the test. Additionally,
section 4.1.4 of AHRI Standard 810 (I–
P)–2016 with Addendum 1 requires that
the test unit shall be configured for
testing per the manufacturer’s written
instructions provided with the unit. It
also requires that no adjustments of any
kind shall be made to the test unit prior
to or during the test that would affect
the ice capacity, energy usage, or water
usage of the test sample. Many selfcontained ACIMs with dispensers
would require removing case panels or
the top lid to access the internal ice bin
for ice collection or establishing initial
test setup. In typical operation, users
would access the ice only through the
dispenser mechanism.
Through a letter dated January 28,
2020, Hoshizaki petitioned for a waiver
and interim waiver from the DOE ACIM
test procedure at 10 CFR 431.134 for
ice/water dispenser ACIM basic models
to address the test issues previously
described in this section (case number
2020–001).29 On July 23, 2020, DOE
granted Hoshizaki an interim waiver to
test the identified ACIM basic models
with a modified test procedure. 85 FR
44529. After providing opportunity for
public comment on the interim waiver
and reviewing the one comment
received, DOE granted Hoshizaki a
waiver through a final decision and
order published on October 28, 2020. 85
FR 68315.
The decision and order requires, prior
to the start of the test, removing the
front panel of the unit under test and
inserting a bracket to hold the shutter
(which allows for the dispensing of ice
during the test) completely open for the
duration of the test. After inserting the
bracket, return the front panel to its
original position on the unit under test.
Conduct the test procedure as specified
in 10 CFR 431.134 except that the
internal ice bin for the unit under test
shall be empty at the start of the test and
intercepted ice samples shall be
obtained from a container in an external
ice bin that is filled one-half full with
ice and is connected to the outlet of the
ice dispenser through the minimum
length of conduit that can be used. Id.
This waiver granted to Hoshizaki
includes instructions for testing the
specific basic models addressed in that
waiver process. However, other ACIM
models with dispensers would likely
require similar testing instructions.
29 The petition and related documents are
available at www.regulations.gov in docket EERE–
2020–BT–WAV–0005.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
Moreover, after the granting of any
waiver, DOE must publish in the
Federal Register a notice of proposed
rulemaking to amend its regulations to
eliminate any need for the continuation
of such waiver. 10 CFR 431.401(l).
Therefore, in the December 2021 NOPR,
DOE proposed to add general test
instructions to the proposed DOE test
procedure at 10 CFR 431.134(b)(6) to
allow for testing such models. 86 FR
72322, 72346. DOE proposed that
ACIMs with a dispenser be tested with
continuous production and dispensing
of ice throughout the stabilization and
test periods. Id. As noted in the
December 2021 NOPR, if an ACIM with
a dispenser is not able to allow for the
continuous production and dispensing
of ice because of certain mechanisms
within the ACIM that prohibit this
function, those mechanisms must be
overridden to the minimum extent that
allows for the continuous production
and dispensing of ice. Id. For example,
this would allow for the temporary
removal of panels or overriding of
certain controls, if necessary. Id. The
capacity samples would be collected in
an external bin one-half full with ice
and connected to the outlet of the ice
dispenser through the minimal length of
conduit that can be used for the
required time period as defined in
ASHRAE Standard 29–2015. Id. Because
of the continuous production and
dispensing of ice, these ACIMs would
be required to have an empty internal
storage bin at the beginning of testing.
Id. This would ensure that the
collection periods capture only the
quantity of ice produced during that
period (i.e., this would avoid any ice
being collected that was produced prior
to the collection period). Id. This
proposed approach would address
issues with testing ACIM models with
automatic dispensers, while allowing a
representative measure of how ACIMs
with dispensers are typically used. Id.
This approach would also minimize test
burden by avoiding the need to
significantly alter the configurations of
these ACIM models for testing (e.g.,
allowing for access to any internal
storage bins during performance
testing). Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
collect capacity samples for ACIMs with
dispensers through the continuous
production and dispensing of ice
throughout testing, using an empty
internal storage bin at the beginning of
the test period and collecting the ice
sample through the dispenser in an
external bin one-half full of ice. 86 FR
72322, 72346. DOE also requested
PO 00000
Frm 00031
Fmt 4701
Sfmt 4700
65885
comment on its proposal to allow for
certain mechanisms within the ACIM
that would prohibit the continuous
production and dispensing of ice
throughout testing to be overridden to
the minimum extent that allows for the
continuous production and dispensing
of ice. Id. DOE sought information on
how manufacturers of these ACIMs
currently test and rate this equipment
under the existing DOE test procedure,
whether the proposal would impact the
energy use as currently measured, and
on the burden associated with the
proposed approach or any alternative
test approaches. Id.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed with
adopting the approach stated, and AHRI
noted that this process is also being
proposed to the ASHRAE 29 committee
for consideration. (Hoshizaki, No. 14, p.
6; AHRI, No. 13, p. 8)
AHAM commented that DOE’s
proposed test procedure does not
account for integrated dispensing, such
as for a dispenser ice maker with ice
internal to the unit (a feature offered in
certain residential products). (AHAM,
No. 18, p. 11) AHAM states that, for
these products, there is no way to
determine if the bin is half full during
the run-in portion of the test, and that
DOE proposes to override the
dispensing function so that it
continually dispenses, which is not
possible on all units that have this
feature. Id.
The CA IOUs commented that a selfcontained ice maker category type that
DOE recognized needs specialized test
methodology is the ice dispenser ice
maker. (CA IOUs, No. 16, p. 4) The CA
IOUs noted that the ice is made inside
the ice bin and an automated ice
dispenser is located underneath the bin
to dispense ice into a cup. Id. The CA
IOUs described that usually these
machines have automated water
dispensers integrated into them, the
bins range between 10 and 100 lb, and
the production capacity ranges between
200 and 500 lb per day. Id. The CA IOUs
stated that there are 18 different models
on the market, which are purchased by
foodservice establishments and offices.
Id. The CA IOUs recommended
separating these ice machines into
different classes to allow the test
methodology to be refined for each
category, resulting in testing consistency
within each category. Id.
In the December 2021 NOPR, DOE
proposed that mechanisms must be
overridden to the minimum extent
which allows for the continuous
production and dispensing of ice (e.g.,
insert a bracket to hold the shutter
(which allows for the dispensing of ice
E:\FR\FM\01NOR2.SGM
01NOR2
65886
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
during the test) completely open for the
duration of the test). 86 FR 72322,
72345–72346. DOE also proposed that
the internal storage bin be empty at the
beginning of the test period and that the
intercepted ice samples be obtained
from a container in an external ice bin
that is filled one-half full of ice. Id. This
would ensure that the collection periods
capture only the quantity of ice
produced during that period (i.e., this
would avoid any ice being collected that
was produced prior to the collection
period).
DOE notes that the test method
proposed in the December 2021 NOPR
would apply to all ACIMs with
dispensers, not just the basic model for
which there is a test procedure waiver.
DOE has not identified the need for
additional test instructions for any other
ACIMs with dispensers and DOE has
not received any additional petitions for
waiver for other ACIMs with dispensers.
Therefore, DOE is maintaining in this
final rule the test method proposed in
the December 2021 NOPR for ACIMs
with dispensers. Further categorization
of equipment may be discussed in any
amended energy conservation standards
for ACIMs with dispensers.
g. Remote ACIMs
DOE did not propose amendments to
the existing test procedures for testing
remote condensing ACIMs in the
December 2021 NOPR. 86 FR 72322,
72346. Based on a review of
manufacturer installation instructions
for ACIMs with dedicated remote
condensing units, manufacturers
typically recommend line sets and/or
limitations to installation locations.
DOE preliminarily determined that
testing according to the manufacturer
recommendations, as is currently
required, rather than one specified
remote setup, would represent typical
use in the field and would produce
consistent test results. 86 FR 72322,
72347. DOE also did not propose any
amendments to its test procedure to
address ACIMs installed with a
compressor rack because it lacked
information on typical installation
locations, operation, and market
availability, and because any ACIMs
designed only for connection to remote
compressor racks are out of the scope of
DOE’s regulations. 86 FR 72322, 72344.
In the December 2021 NOPR, DOE
requested comment on its initial
determination that additional test setup
and installation instructions are not
required for testing remote condensing
ACIMs. 86 FR 72322, 72347.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed that
no additional test setup or installation
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
instructions are required for units with
dedicated remote condensing units.
(Hoshizaki, No. 14, p. 6; AHRI, No. 13,
p. 8) Hoshizaki added that if a
manufacturer has further requests that
are different from its instructions, it
could file that with DOE so it is in the
record of special instructions or taken
through the waiver process for
clarification. (Hoshizaki, No. 14, p. 6)
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed with
DOE in not establishing test procedures
for ACIMs for rack units. (Hoshizaki,
No. 14, p. 6; AHRI, No. 13, p. 8)
Hoshizaki added that the sector is very
small, and a new test criterion would
need to be addressed in the ASHRAE 29
standard. (Hoshizaki, No. 14, p. 6)
DOE is maintaining in this final rule
that additional test setup and
installation instructions are not required
for testing ACIMs with dedicated remote
condensing units, consistent with the
December 2021 NOPR. DOE is also not
establishing separate test procedures for
ACIMs intended for installation with a
compressor rack.
5. Modulating Capacity Ice Makers
An ice maker could be designed to be
capable of operating at multiple
capacity levels, i.e., a ‘‘modulating
capacity ice maker.’’ This modulation
could be accomplished by using a single
compressor with multiple or variable
capacities, using multiple compressors,
or in some other manner. In the January
2012 final rule, DOE did not establish a
test method for measuring the energy
use or water consumption of automatic
commercial ice makers that are capable
of operating at multiple capacities. 77
FR 1591, 1601–1602. The decision to
exclude modulating capacity ice makers
was based on the lack of existing ACIMs
with modulating capacity, as well as
limited information regarding how such
equipment would function. Id.
DOE conducted market research and
examined publicly available sources to
determine the prevalence of modulating
capacity ice makers. DOE did not find
any modulating capacity ice makers that
are currently available in the market.
Therefore, in the December 2021 NOPR,
DOE did not propose test procedures for
modulating capacity ice makers. 86 FR
72322, 72347.
In the December 2021 NOPR, DOE
requested comment on its initial
determination regarding the lack of
availability of modulating capacity ice
makers on the market. 86 FR 72322,
72347.
In response to the December 2021
NOPR, AHRI agreed with DOE’s
determination. (AHRI, No. 13, p. 8)
Hoshizaki commented it is not aware of
PO 00000
Frm 00032
Fmt 4701
Sfmt 4700
any modulating capacity ice makers on
the market. (Hoshizaki, No. 14, p. 6)
Hoshizaki requested that DOE share
examples of modulating capacity
ACIMs, and if examples exist, Hoshizaki
will review and then offer comment. Id.
DOE continues to not be aware of any
modulating capacity ice makers
available on the market. Therefore, DOE
is not establishing test instructions for
modulating capacity ice makers in this
final rule.
6. Standby Energy Use and Energy Use
Associated With Ice Storage
The current ACIM test procedure
considers only active mode energy use
when an ice maker is actively producing
ice and represents that consumption
using a metric of energy use per 100
pounds of ice. The existing ACIM test
procedure does not address standby
energy use associated with continuously
powered sensors and controls or ice
storage outside of active mode
operation. When not actively making
ice, an ice maker continues to consume
energy to power sensors and controls. In
addition, ice that is stored in an integral
or paired ice storage bin will melt over
time and the ice maker will use
additional energy to replace the ice that
has melted to keep the bin full. In these
ways, standby energy use from control
devices and energy use associated with
ice storage can impact the daily energy
consumption of ACIM equipment.
DOE researched available test
methods for determining energy use
associated with ice storage. The AHRI
certification program currently includes
rating ice storage bins using AHRI 820–
2017, ‘‘Performance Rating of Ice
Storage Bins.’’ Similar methods are
currently referenced in the Australian
and Canadian test methods and
standards applicable to self-contained
ice makers and storage bins.30 31 AHRI
820–2017 describes a standardized
method for measuring the ‘‘efficiency’’
of ice storage bins using a metric called
‘‘Theoretical Storage Effectiveness,’’
which describes the percent of ice that
would remain in a bin 24 hours after it
is produced. In contrast, the December
2014 MREF Test Procedure NOPR
considered energy use associated with
ice storage based on testing the ice
maker and storing the ice in a bin over
30 The Australian minimum energy performance
standards (‘‘MEPS’’) apply to both stand-alone
storage bins and ice storage bins contained in standalone equipment (AS/NZS 4865.2 & 3). The NRCan
standard appears to apply only to storage bins
contained in self-contained ice makers with integral
storage bins.
31 The newest version of the CSA test method,
C742–15, refers directly to the 2012 version of AHRI
820 (and AHRI 821, which is the SI version of the
standard).
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
a period of up to 48 hours with no ice
retrieval to determine the energy use
associated with replenishing the bin. 79
FR 74894, 74921–74922.
Many ice makers (including ice
making heads (‘‘IMHs’’) and remote
condensing unit (‘‘RCU’’) ice makers)
can be paired with any number of
storage bins, including those produced
by other manufacturers. These ice
makers are typically paired in the field
with a bin chosen by the end user,
rather than the manufacturer. However,
DOE understands that many IMH and
RCU equipment are advertised as
compatible with a list of specific bins
and, therefore, may be able to be rated
based on recommended bin
combinations.
In the December 2021 NOPR, DOE
initially determined that the energy use
of ACIMs in standby mode is likely very
low compared to active mode ice
making energy use. 86 FR 72322, 72348.
Additionally, the contribution of any
standby mode energy use to overall
energy use can vary significantly
depending on the specific installation
and end use of the ACIM. Id.
At the time of the December 2021
NOPR, DOE did not have sufficient data
and information to establish test
procedures for standby energy use or
energy use associated with ice storage.
86 FR 72322, 72348. In addition,
incorporating standby energy use and
energy use associated with ice storage
would require significant test procedure
changes requiring an increase in test
time. Therefore, because of the lack of
data and undue burden on
manufacturers, DOE did not propose to
amend its test procedures to account for
standby or ice storage energy use in the
December 2021 NOPR. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
not amend its test procedures to account
for standby or ice storage energy use. 86
FR 72322, 72348. DOE also requested
data on the typical durations and
associated energy use for all ACIM
operating modes and on the potential
burden associated with testing energy
use in those modes. Id.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed that
DOE should not amend the test
procedure to account for standby energy
use. (Hoshizaki, No. 14, p. 6; AHRI, No.
13, p. 8)
Hoshizaki commented the normal bin
control switch in low-voltage test data
shows very little power used to
communicate with the control board.
(Hoshizaki, No. 14, p. 6) Hoshizaki
added that accounting for standby
energy would require a significant
increase in total test time, which would
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
be a significant increase in test burden
to measure a very small amount of
energy. Id.
Joint Commenters commented that the
standby power associated with powered
controls outside of active icemaking can
be around 25–50 kWh per year. (Joint
Commenters, No. 15, p. 2) Joint
Commenters noted that in the 2015
Final Rule Technical Support Document
(‘‘TSD’’) for ACIM standards, DOE
assumed a utilization factor (i.e., the
percent of time the ice maker is actively
producing ice) of 42 percent, and
assumed the unit was in standby mode
58 percent of the time, adding that DOE
stated that the utilization factor was
based on data provided by
manufacturers and a field study. Id.
Joint Commenters stated that despite the
information cited in the 2015 Final Rule
TSD, DOE cites insufficient information
as a reason not to amend the test
procedures to capture standby power,
therefore, the Joint Commenters
encouraged DOE to capture standby
energy use in the test procedure to
improve representativeness by more
fully capturing the total energy
consumption of ACIMs. Id.
The CA IOUs recommended that for
self-contained machines the ice-melt
rate procedure from AHRI 820 should be
integrated into the method of test, and
the ice-melt rate should be reported or
integrated into the daily energy and
harvest rate. (CA IOUs, No. 16, p. 7) The
CA IOUs added that self-contained ice
machines have an ice bin that is integral
to the unit, and ice-melt rate should be
reported for these units or have the icemelt rate accounted for in the reported
energy consumption. Id.
Joint Commenters urged DOE to
capture the energy use associated with
ice storage due to replacement cycles in
the test procedures for self-contained
units (SCU), which include an
integrated storage bin, as well as for icemaking heads (IMH) and remotecondensing units (RCU). (Joint
Commenters, No. 15, p. 3) Joint
Commenters noted that in a NOPR
published on December 16, 2014,
regarding the miscellaneous
refrigeration products (‘‘MREFs’’) test
procedure (‘‘December 2014 MREF Test
Procedure NOPR’’; 79 FR 74894), DOE
proposed a test procedure that included
a measurement of both the energy
consumed during active ice production
and the energy use associated with
replenishing the ice supply to replace
melted ice during ice storage. Id. For
SCUs, Joint Commenters encouraged
DOE to investigate the appropriateness
of a procedure similar to the one it
proposed for ice makers in the
PO 00000
Frm 00033
Fmt 4701
Sfmt 4700
65887
December 2014 MREF Test Procedure
NOPR. Id.
Joint Commenters commented that the
operation of ice makers includes
replacement cycles (i.e., when
additional ice is produced to replenish
the storage bin due to ice melt), and the
effectiveness of the storage bin at
keeping the stored ice cold (i.e., slowing
the melt) drives the frequency of the
replacement cycles, and thus impacts
the energy consumed over a period of
time, such as a day or a year. (Joint
Commenters, No. 15, p. 2–3) Joint
Commenters noted that DOE previously
found that the energy use associated
with replacement of melted ice from ice
storage bins ranged from 30 to 75% of
total ice maker energy consumption. Id.
For IMHs and RCUs, Joint
Commenters encouraged DOE to
consider an approach that could involve
establishing default values that
represent the energy use associated with
ice replacement. (Joint Commenters, No.
15, p. 3) Joint Commenters added the
melt rates associated with the leastefficient storage bins on the market
could be used to determine the extent of
replacement cycle operation during a
fixed period, such as 24 hours, noting
that the default value of replacement
cycle energy would take the form of an
adder to measured energy consumption
in the normal icemaking cycle. Id. Joint
Commenters stated that a manufacturer
could then choose to either use the
default value or, if they wanted to
demonstrate improved storage bin
effectiveness, they could conduct a
similar test to that used for SCUs. Id.
Specifically, Joint Commenters
addressed DOE’s statements in the
NOPR that many IMH and RCU models
are advertised as compatible with a list
of specific bins, stating they believe that
it could make sense in these cases for
the manufacturer to test with the leastefficient storage bin of those advertised
in their literature. Id. If no bin is
specified, the manufacturer would
instead use the default values. Id.
In the December 2021 NOPR, DOE
initially determined that the
contribution of any standby mode
energy use to overall energy use can
vary significantly depending on the
specific installation and end use of the
ACIM. 86 FR 72322, 72348. Because
ACIMs may be installed and operated in
a range of end uses (e.g., commercial
kitchens, offices, schools, hospitals,
hotels, and convenience stores),
determining the performance based on
the metric of energy use per 100 pounds
of ice during an ACIM’s active mode
best reflects energy efficiency, energy
use, or estimated annual operating cost
of a given type of covered equipment
E:\FR\FM\01NOR2.SGM
01NOR2
65888
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
during a representative average use
cycle while not being unduly
burdensome to conduct, consistent with
42 U.S.C. 6314(a)(2).
DOE also initially determined that
IMHs and RCU ice makers are typically
paired in the field with a storage bin
chosen by the end user, rather than the
manufacturer, which can result in IMHs
and RCU ice makers paired with storage
bins from a different manufacturer. 86
FR 72322, 72348. DOE acknowledges
that self-contained ice makers contain a
storage bin that is integral to the ACIM.
However, the energy use associated with
ice storage of all ACIMs, including selfcontained ice makers, can vary
significantly depending on the specific
installation and end use of the ACIM.
DOE acknowledges the comments
regarding DOE’s utilization factor from
the 2015 Final Rule TSD for ACIM
standards.32 The utilization factor
estimates the percent of time ice makers
actively produce ice. The assumed
utilization factor in the 2015 Final Rule
TSD for ACIM standards was 42 percent
across all equipment classes and
efficiency levels and was based on data
provided by manufacturers and data
obtained from a field study.33 The
assumed utilization factor was used to
estimate the annual energy consumption
of each equipment class and efficiency
level considered in the 2015 Final Rule
TSD for ACIM standards and does not
represent the utilization factor for an
individual test unit. As noted by the
field study, ice maker usage can vary
dramatically from one installation to
another as illustrated by the results of
the field study in which the duty cycles
of tested units averaged between 34.5
percent and 86.6 percent.
DOE has determined that the
measurement of active mode energy use,
when an ice maker is actively producing
ice, and the metric of energy use per 100
pounds of ice represent a repeatable and
reproducible test method that is
reasonably designed to produce test
results which reflect energy use during
a representative average use cycle.
Therefore, DOE is maintaining in this
final rule to not amend its test
procedures to account for standby or ice
storage energy use.
7. Calculations and Rounding
Requirements
As compared to ASHRAE Standard
29–2009, section 9.1.1 of ASHRAE
Standard 29–2015 specifies averaging
instructions for calculating the gross
weight of product produced. ASHRAE
Standard 29–2015 specifies to ‘‘average
the quantity for the three samples to
determine the ice produced.’’ However,
this averaging instruction is not
specified for the water or energy
consumption calculations.
In the December 2021 NOPR, DOE
proposed to provide explicitly that the
energy use, condenser water use, and
potable water use (as described in
section III.D.8) be calculated by
averaging the measured values for each
of the three samples for each respective
metric. 86 FR 72322, 72348. DOE added
that this clarification would not affect
the measured performance of ACIMs but
would more explicitly present the
calculation approach. Id.
In the December 2021 NOPR, DOE
requested comment on the proposal to
clarify that the energy use, condenser
water use, and potable water use (as
described in section III.D.8) be
calculated by averaging the calculated
values for the three measured samples
for each respective metric. 86 FR 72322,
72348.
In response to the December 2021
NOPR, AHRI agreed with DOE that
these could be valid proposed changes.
(AHRI, No. 13, p. 9) However, AHRI and
Hoshizaki requested that any
clarifications to the ASHRAE 29 be
addressed by the ASHRAE 29 standard
committee. (AHRI, No. 13, p. 9;
Hoshizaki, No. 14, p. 6).
DOE has determined to amend the test
procedure in this final rule to clarify
that the energy use, condenser water
use, and potable water use (as described
in section III.D.8) be calculated by
averaging the calculated values for the
three measured samples for each
respective metric.
The regulations in 10 CFR 431.132
specify rounding requirements for the
ACIM metrics ‘‘energy use’’ and
‘‘maximum condenser water use.’’
Specifically, DOE requires energy use to
be in multiples of 0.1 kWh/100 lb and
condenser water use to be in multiples
of 1 gallon per 100 pounds of ice (‘‘gal/
100 lb’’). 10 CFR 431.132.
AHRI Standard 810–2007, which is
currently incorporated by reference in
the DOE test procedure, and AHRI
Standard 810 (I–P)–2016 with
Addendum 1, which was proposed for
use in the December 2021 NOPR,
specify rounding requirements for the
following quantities:
32 See https://www.regulations.gov/document/
EERE-2010-BT-STD-0037-0136.
33 See https://p2infohouse.org/ref/50/49015.pdf.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
PO 00000
Frm 00034
Fmt 4701
Sfmt 4700
TABLE III.13—SUMMARY OF ROUNDING
REQUIREMENTS
Quantity
Ice Harvest Rate .......
Condenser Water
Use Rate.
Potable Water Use
Rate.
Energy Consumption
Rate.
Ice Hardness Factor
AHRI standard 810
(both 2007 and 2016,
except as noted)
1 lb/24 h.
1 gal/100 lb.
0.1 gal/100 lb.
0.1 kWh/100 lb
(2007).
0.01 kWh/100 lb
(2016).
Not Specified (percent).
In the December 2021 NOPR, DOE
proposed to incorporate by reference
AHRI Standard 810 (I–P)–2016 with
Addendum 1, which would include the
rounding requirements shown in Table
III.12, with the exception of the
provision for harvest rate. 86 FR 72322,
72349. For harvest rate, the specified
rounding to the nearest 1 lb/24 h could
represent a significant percentage of
harvest rates for low-capacity ACIMs.
As discussed in section III.D.2, DOE
observed low-capacity ACIMs available
on the market with harvest rates as low
as 7 lb/24 h. For this harvest rate,
rounding to the nearest pound would
allow a range of measured performance
of approximately ±7 percent to have the
same harvest rate result. Section 5.5.1 of
ASHRAE Standard 29–2015 provides
that ice-weighing instruments have
accuracy and readability of ±1.0% of the
quantity measured. Therefore, to avoid
rounding harvest rate to a level that
could impact test procedure accuracy,
DOE proposed that harvest rate be
rounded to the nearest 0.1 lb/24 h for
ACIMs with harvest rates less than or
equal to 50 lb/24 h. 86 FR 72322, 72349.
DOE further discusses rounding
requirements in section III.E.2.
DOE has determined to amend the test
procedure in this final rule to require
the rounding requirements specified in
AHRI Standard 810 (I–P)–2016 with
Addendum 1 except that for ACIMs
with harvest rates less than or equal to
50 lb/24 h, the harvest rate shall be
rounded to the nearest 0.1 lb/24 h.
DOE also proposed in the December
2021 NOPR to specifically state that all
calculations must be performed with
raw measured values and that only the
resultant energy use, condenser water
use, and harvest rate metrics be
rounded. 86 FR 72322, 72349.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed with
this assessment, but requested that any
clarification be addressed by the
ASHRAE 29 standard committee.
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
In addition, ASHRAE Standard 29–
2015 specifies stabilization
requirements in terms of either percent
or absolute weight without specifically
referencing a calculation for percent
variation. In the December 2021 NOPR,
DOE proposed to apply the following
Percent Difference
The proposed equation for calculating
percent difference may affect when a
unit meets the stability criteria, but DOE
determined it would not affect the
stabilization determination for any of
the over 50 ice maker tests conducted
prior to this rulemaking. 86 FR 72322,
72344.
In the December 2021 NOPR, DOE
requested comment on its proposal to
clarify that percent difference shall be
calculated based on the average of the
two measured values. 86 FR 72322,
72349.
In response to the December 2021
NOPR, Hoshizaki agreed that this
proposal can help in understanding of
how percent difference is calculated and
should be spelled out in the Code of
Federal Regulation’s language but
requested that this be addressed by the
ASHRAE 29 standard committee.
(Hoshizaki, No. 14, p. 7) AHRI agreed
with DOE that these could be valid
proposed changes. (AHRI, No. 13, p. 9)
To ensure consistency in stability
determinations, DOE is amending the
test procedure in this final rule to
require that percent difference be
calculated based on the average of the
two measured values.
lotter on DSK11XQN23PROD with RULES2
8. Potable Water Use
The water use of an ACIM includes
water used in making the harvested ice;
any dump or purge water used as part
of the ice making process; and for watercooled ACIMs, the water used to
transfer heat from the condenser. In
establishing initial standards for ACIMs,
Congress addressed the latter type of
water use. For ACIMs that produce cube
type ice with capacities between 50 and
2,500 pounds per 24-hour period, EPCA
specified maximum condenser water
use rates (in gallons per 100 pounds of
ice). (42 U.S.C. 6313(d)(1)) In a note to
the table establishing initial maximum
condenser water use rates, the statute
provides that ‘‘Water use is for the
condenser only and does not include
potable water used to make ice.’’ (Id.)
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
=
IA-Bl
A+ B x100percent
-2-
In the January 2012 final rule, DOE
noted that 42 U.S.C. 6313(d) does not
require DOE to develop a water
conservation test procedure or standard
for potable water use in cube type ice
makers or other ACIMs; rather, it sets
forth energy and condenser water use
standards for cube type ice makers at 42
U.S.C. 6313(d)(1), and allows, but does
not require, the Secretary to issue
analogous standards for other types of
ACIMs under 42 U.S.C. 6313(d)(2). 77
FR 1591, 1605.
DOE further stated that ambiguous
statutory language may lead to multiple
interpretations in the development of
regulations. Id. DOE stated that the
statutory language is unclear whether
the footnote on potable water use that
appears in 42 U.S.C. 6313(d)(1) has a
controlling effect on 42 U.S.C.
6313(d)(2) and 42 U.S.C. 6313(d)(3)—
the statutory direction to review and
consider amended standards. Id. Potable
water use is not referenced anywhere
else in 42 U.S.C. 6313(d), and thus it is
difficult to determine whether this
footnote is a clarification or a mandate
in regard to cube type ice makers, and
furthermore, whether it would apply to
the regulation of other types of ACIMS.
Id.
DOE also stated that while there is
generally a positive correlation between
energy use and potable water use, DOE
understands that at a certain point the
relationship between potable water use
and energy consumption reverses due to
scaling. Id. Based on this fact, and given
the added complexity inherent to the
regulation of potable water use and the
concomitant burden on ACIM
manufacturers, DOE did not establish
regulations or require testing and
reporting of the potable water use of
ACIMs. Id. Without a clear mandate
from Congress on potable water use
generally, and given that Congress chose
not to regulate potable water use for
cube type ice makers by statute, DOE
exercised its discretion in choosing not
to include potable water use rate in its
test procedure for ACIMs. Id.
PO 00000
Frm 00035
Fmt 4701
equation to calculate the percent
difference between any two
measurements. 86 FR 72322, 72349.
This includes any calculation to
determine if the ice production rate has
stabilized between cycles or samples, as
described in section III.D.2.
Sfmt 4700
ASHRAE Standard 29–2015 and AHRI
Standard 810 (I–P)–2016 with
Addendum 1 include measurements
and rating requirements for potable
water use. The measurement of ‘‘noncondenser’’ potable water use (i.e.,
water used in making the harvested ice
and any dump or purge water) is
currently not specified by the DOE test
procedure, but is required by other
programs, such as ENERGY STAR 34 and
the AHRI certification program.35
As stated in the March 2019 RFI, DOE
reviewed the relationship between
potable water use with harvest rate and
daily energy consumption by analyzing
reported ACIM data from the AHRI
directory and the ENERGY STAR
product database.36 37 84 FR 9979, 9986.
DOE observed that all continuous ice
makers had reported values for potable
water use per 100 pounds of ice
between 11.9 and 12.0 gallons because
all the water is converted to produced
ice. Id. In contrast, potable water use
varies for batch type ice makers because
a portion of the potable water is drained
from the sump at the end of each ice
making cycle—this portion is different
for different ice maker models. Id. The
relationship between potable water use
and daily energy consumption of the
AHRI and ENERGY STAR data is not
identifiable when considering the entire
dataset. Id.
Because energy use can be affected by
many factors other than potable water
use, the lack of a clear trend between
energy use and potable water use does
not provide a definitive indication of
the extent of the relationship between
energy use and potable water use. 86 FR
72322, 72350. Although the exact
34 The ENERGY STAR specification for automatic
commercial ice makers is available at
www.energystar.gov/sites/default/files/
Final%20V3.0%20ACIM%20Specification%205-1717_1.pdf.
35 www.ahrinet.org/Certification.aspx.
36 Available at www.ahridirectory.org/
NewSearch?programId=31&searchTypeId=3.
37 Available at www.energystar.gov/
productfinder/product/certified-commercial-icemachines/results.
E:\FR\FM\01NOR2.SGM
01NOR2
ER01NO22.000
(Hoshizaki, No. 14, p. 6; AHRI, No. 13,
p. 9)
DOE has determined to amend the test
procedure in this final rule to require
that all calculations must be performed
with raw measured values and that only
the resultant energy use, water use, and
harvest rate metrics be rounded.
65889
lotter on DSK11XQN23PROD with RULES2
65890
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
relationship between potable water use
and energy use is not understood,
potable water use does impact energy
use. Id. An ACIM must chill the
entering potable water to some extent.
Id. The extent to which potable water is
not directly converted to ice, it still is
likely cooled to 32 °F. Id. Cooled potable
water that is not directly converted to
ice and is drained from the unit
represents lost refrigeration capacity. Id.
As such, reducing potable water use
may provide the potential for reduced
energy consumption. Id.
In the December 2021 NOPR, DOE
initially determined that ACIMs
currently available on the market have
a wide range of potable water use, and
the relationship between potable water
use and energy use and harvest rate is
not clear. 86 FR 72322, 72350. Based on
its inclusion in the AHRI certification
program and ENERGY STAR
qualification criteria, potable water use
may be a useful measurement as part of
characterizing the energy use associated
with ACIM performance. Id. To align
with the AHRI certification program and
ENERGY STAR, while allowing for a
measurement of potable water use that
is consistent with the test requirements
proposed in the December 2021 NOPR
for energy use, harvest rate, and
condenser water use, DOE proposed in
the December 2021 NOPR to include
measurement of potable water use in the
DOE ACIM test procedure at 10 CFR
431.134. Id. Because DOE does not
regulate ACIM potable water use, testing
for the potable water measurements
under the proposed approach would be
voluntary. Id. Specifically, DOE did not
propose to require manufacturers to
conduct the potable water provisions of
the test procedure, and manufacturers
would not report the results of the
potable water test to DOE, if conducted.
Id. In addition, DOE stated that
manufacturers would not be required to
use the voluntary test procedure as the
basis of any representations of potable
water use. Id.
DOE proposed that the measurement
of potable water use would generally
follow the test methods in AHRI
Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015, but with the additional test
procedure amendments as proposed in
the December 2021 NOPR. 86 FR 72322,
72350. This proposed approach is
generally consistent with the methods
currently used for the AHRI and
ENERGY STAR programs; additionally,
DOE does not expect that the additional
test provisions as proposed in the
December 2021 NOPR would impact
performance as measured under the
existing approaches used by AHRI
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
(AHRI Standard 810 (I–P)–2016 with
Addendum 1) or ENERGY STAR (AHRI
Standard 810–2007). Id.
DOE also proposed to add a definition
of ‘‘potable water use’’ in 10 CFR
431.132. 86 FR 72322, 72350. DOE
proposed to define ‘‘potable water use’’
as the amount of potable water used in
making ice, which is equal to the sum
of the ice harvested, dump or purge
water, and the harvest water, expressed
in gal/100 lb, in multiples of 0.1, and
excludes any condenser water use. Id.
This definition is generally consistent
with the term ‘‘potable water use rate’’
in AHRI Standard 810 (I–P)–2016 with
Addendum 1, with the clarification that
condenser water use is not considered
potable water use. Id.
In the December 2021 NOPR, DOE
noted that AHRI Standard 810 (I–P)–
2016 with Addendum 1 specifies under
the ‘‘Certified Ratings’’ section that
potable water use rate is applicable to
batch type ice makers only, but that
AHRI’s Directory of Certified Product
Performance includes the potable water
use rate for both batch type and
continuous type ACIMs.38 86 FR 72322,
72350. Thus, the industry standard
appears to currently be used for
measuring potable water use for both
batch and continuous ice makers. Id.
In the December 2021 NOPR, DOE
requested comment on the proposal to
include a voluntary method for
measuring potable water use, including
the value or drawbacks of such an
approach, in 10 CFR 431.134 according
to the industry standards and additional
test procedure proposals as discussed in
the NOPR. 86 FR 72322, 72350.
In response to the December 2021
NOPR, Hoshizaki and AHRI commented
that potable water requirements are not
covered by the regulation today and
added that potable water restrictions
should be reviewed against sanitation
requirements to ensure no issues or
impact on performance. (Hoshizaki, No.
13, p. 9; AHRI, No. 13, p. 9) Hoshizaki
added that ASHRAE 29 and AHRI 810
account for the collected water use.
(Hoshizaki, No. 14, p. 7)
The Joint Commenters and CA IOUs
encouraged DOE to require that potable
water use be measured and reported,
which would ensure that information
about the potable water use of all ice
maker models is available to purchasers
so that they can make informed
decisions. (Joint Commenters, No. 15, p.
3; CA IOUs, No. 16, p. 4) The CA IOUs
added that due to the ambiguous
relationship between potable water use
and efficiency, more reporting from
38 www.ahridirectory.org/NewSearch?programId=
31&searchTypeId=3.
PO 00000
Frm 00036
Fmt 4701
Sfmt 4700
manufacturers will elucidate these
impacts. (CA IOUs, No. 16, p. 7) The CA
IOUs supported DOE’s potable water
usage measurement. (CA IOUs, No. 16,
p. 4)
The Joint Commenters stated that
manufacturers are already measuring
potable water use as part of the ENERGY
STAR and AHRI certification and
programs. (Joint Commenters, No. 15, p.
3) The CA IOUs commented that
ASHRAE 29 covers water consumption
methodology; however, manufacturers
only report water consumption data to
ENERGY STAR, which covers
approximately 30 percent of the market.
(CA IOUs, No. 16, p. 4) The Joint
Commenters added that while most
ACIM models in the AHRI directory
meet the ENERGY STAR potable water
use requirements, the three highest
water-consuming models consume
120%, 97%, and 72% more potable
water than the ENERGY STAR
requirements. Id. The CA IOUs
commented that two major
manufacturers represent most models in
the ENERGY STAR database, with
harvest rates ranging from
approximately 200 lb/day to 1800 lb/
day. (CA IOUs, No. 16, p. 5–6) The CA
IOUs further added that one of the
manufacturer’s machines consistently
use more water, and this water use does
not appear to correlate with energy use.
Id. The CA IOUs stated that there is only
a strong relationship between water and
energy use for smaller self-contained ice
machine categories and did not show a
relationship for ice making heads and
remote condensed units. Id.
The CA IOUs commented that DOE’s
NOPR cites ‘‘Prohibited
Representations,’’ to avoid imposing a
mandate for representations with regard
to potable water use (86 FR 72322,
72350); however, CA IOUs stated that
nowhere in this provision does Congress
bar DOE from imposing a representation
requirement for water use. Id.
CA IOUs commented that currently,
the ASHRAE 29 test method does not
adequately capture water consumption
from purge cycles, which may occur
every one to twelve harvest cycles and
can be adjusted by a technician in the
field, and recommended that purge
cycle water consumption should be
measured for batch machines and
integrated into the reported total water
consumption of the machine. (CA IOUs,
No. 16, p. 4) The CA IOUs added that
the results for energy use may differ;
energy use may increase as pre-cooled
water near the freezing point is lost as
purge water, or it may decrease if
additional dump and purge water leads
to lessened scaling in the ice maker. Id.
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
Because DOE does not regulate ACIM
potable water use and because the DOE
test procedures are used to determine
compliance with energy and condenser
water use (as applicable) standards, the
harvest rate, energy use, and condenser
water use (as applicable) are the
relevant required metrics. DOE
acknowledges that potable water use
may be a useful measurement as part of
characterizing the performance of an
ACIM and is providing a repeatable and
reproducible test method that allows
potable water use to be tested
consistently with the other performance
metrics. DOE is maintaining in this final
rule a voluntary method for measuring
potable water use in 10 CFR 431.134
that generally follows the test methods
in AHRI Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015 with some modifications,
consistent with the December 2021
NOPR.
In the December 2021 NOPR, DOE did
not propose to adjust potable water use
based on ice hardness factor, as is
currently required for energy use and
condenser water use. 86 FR 72322,
72351. Both energy use and condenser
water use correspond to the amount of
heat removed from the potable water in
producing ice. Id. Ice that is more
completely frozen will require more
energy use and more heat rejection (via
condenser water use, if applicable). Id.
However, potable water use does not
similarly vary depending on the ice
hardness. Id. The same amount of
potable water is used to make partially
frozen ice as completely frozen ice. Id.
This is supported by nearly all
continuous ice makers showing the
same 11.9 to 12 gallons of potable water
use per 100 lbs of ice production. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal that
potable water use is not adjusted based
on ice hardness factor. 86 FR 72322,
72351.
In response to the December 2021
NOPR, Hoshizaki and AHRI agreed that
potable water should not be adjusted
based on ice hardness. (Hoshizaki, No.
14, p. 7; AHRI, No. 13, p. 9)
DOE has determined in this final rule
to not adjust the potable water use based
on ice hardness.
Potable water use for portable ACIMs
is different than for ACIMs with a fixed
water connection. As discussed,
portable ACIMs require that the fill
reservoir be filled manually with the
maximum volume of water that is
recommended by the manufacturer. In a
portable ACIM, the unused ice collected
in the ice storage bin slowly melts. This
melt water is recycled back into the
potable water reservoir to be reused.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
Unlike batch type non-portable ACIMs,
there is no dump or purge water to be
measured. For portable ACIMs, water
introduced to the reservoir is typically
only removed from the unit as ice (and
any corresponding melt water).
Therefore, in the December 2021 NOPR,
DOE proposed that the potable water
use rate for portable ACIMs be defined
as equal to the weight of ice and any
corresponding melt water collected for
the capacity test as specified in section
7.2 of ASHRAE Standard 29–2015. 86
FR 72322, 72351.
In the December 2021 NOPR, DOE
requested comment on the proposal that
the potable water use rate of portable
ACIMs be defined as equal to the weight
of ice and water captured for the
capacity test, as specified in section 7.2
of ASHRAE Standard 29–2015. 86 FR
72322, 72351.
In response to the December 2021
NOPR, Hoshizaki agreed to the
calculation method if the ASHRAE 29–
2015 standard is adopted at this time.
(Hoshizaki, No. 14, p. 7)
DOE is maintaining in this final rule
that the potable water use rate of
portable ACIMs be defined as equal to
the weight of ice and water captured for
the capacity test, as specified in section
7.2 of ASHRAE Standard 29–2015,
consistent with the December 2021
NOPR.
E. Representations of Energy Use and
Energy Efficiency
In addition to updates to the ACIM
test procedure, DOE proposed in the
December 2021 NOPR revisions to the
provisions related to the sampling plan
and the determination of represented
values currently specified at 10 CFR
429.45. 86 FR 72322, 72351. DOE also
proposed to add equipment-specific
enforcement provisions for ACIMs to 10
CFR 429.134. Id.
1. Sampling Plan and Determination of
Represented Values
In subpart B to 10 CFR part 429, DOE
provides uniform methods for
manufacturers to determine
representative values of energy- and
non-energy-related metrics for each
basic model of covered equipment. The
purpose of a statistical sampling plan is
to provide a method to ensure that the
test sample size (i.e., number of units
tested) is sufficiently large that
represented values of energy- and nonenergy-related metrics are representative
of aggregate performance of the units in
the basic model, while accounting for
variability inherent to the
manufacturing and testing processes.
DOE currently specifies the ACIMspecific sampling plans and
PO 00000
Frm 00037
Fmt 4701
Sfmt 4700
65891
requirements for the determination of
represented values at 10 CFR 429.45.
The sampling plan and method for
determining represented values applies
to represented values of maximum
energy use, or other measures of energy
consumption for which consumers
would favor lower values.
The reference to ‘‘maximum energy
use’’ and ‘‘maximum condenser water
use’’ in 10 CFR 429.45 could be
misinterpreted to refer to the energy and
water conservation standard levels for
that basic model (i.e., the maximum
allowable energy and maximum
allowable condenser water use), as
opposed to the tested performance.
Therefore, in the December 2021 NOPR,
for consistency and clarity, DOE
proposed to replace the term ‘‘maximum
energy use’’ with the term ‘‘energy use’’
and the term ‘‘maximum condenser
water use’’ with the term ‘‘condenser
water use.’’ 86 FR 72322, 72351. In
addition, values of both energy and
condenser water consumption are
relevant for ACIMs. As such, DOE
proposed to modify the language at 10
CFR 429.45 to specify expressly that the
sampling plan at 10 CFR 429.45(a)(2)(i)
applies both to measures of energy and
condenser water use for which
consumers would favor lower values. Id.
Similarly, 10 CFR 431.132 includes a
definition for the term ‘‘maximum
condenser water use.’’ This language
may also be misinterpreted to refer to
the condenser water conservation
standard level for a basic model as
opposed to the tested condenser water
use. Therefore, in the December 2021
NOPR, DOE proposed to modify the
term and definition of ‘‘maximum
condenser water use’’ to instead refer to
the term ‘‘condenser water use.’’ 86 FR
72322, 72351. This modification is
consistent with the existing definition of
‘‘energy use’’ in 10 CFR 431.132.
In 10 CFR 429.45(a)(2)(ii), DOE also
specifies calculation procedures for
energy efficiency metrics, or measures
of energy consumption where
consumers would favor higher values.
As DOE’s test procedure does not
require determining any values of
energy efficiency or other measure of
performance for which consumers
would favor higher values, DOE
proposed to remove this provision in
the December 2021 NOPR. 86 FR 72322,
72351.
In addition to energy related metrics,
10 CFR 429.45 mandates the reporting
of harvest rate, a key non-energy metric
associated with determining energy and
condenser water standards for ACIM
equipment, as applicable. However, 10
CFR 429.45 does not specify how the
represented value of harvest rate for
E:\FR\FM\01NOR2.SGM
01NOR2
lotter on DSK11XQN23PROD with RULES2
65892
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
each basic model should be determined
based on the test results from the
sample of individual models tested.
Similar to the requirements for other
covered products and commercial
equipment, DOE proposed in the
December 2021 NOPR that the
represented value of harvest rate for the
basic model be determined as the mean
of the measured harvest rates for each
unit in the test sample, based on the
same tests used to determine the
reported energy use and condenser
water use, if applicable. 86 FR 72322,
72351. Although not specified in 10
CFR 429.45, DOE expected
manufacturers are currently certifying
ACIM performance based on the tested
harvest rates. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
amend the sampling plan and reporting
requirements for ACIMs in 10 CFR
429.45. 86 FR 72322, 72351. DOE sought
information on how manufacturers are
currently interpreting ‘‘maximum
energy use’’ and ‘‘maximum condenser
water use’’ in the context of the
sampling and certification report
requirements, how manufacturers are
currently determining harvest rates, and
whether the proposed amendments
would impose any burden on
manufacturers. Id. DOE also requested
comment on its proposal to modify the
term and definition of ‘‘maximum
condenser water use’’ to instead refer to
‘‘condenser water use’’. Id.
In response to the December 2021
NOPR, Hoshizaki and AHRI commented
that further clarification is needed for
this proposal. (Hoshizaki, No. 14, p. 7;
AHRI, No. 13, p. 9) Hoshizaki requested
that this be brought to the ASHRAE 29
standard committee for clarification and
comment. (Hoshizaki, No. 14, p. 7)
AHRI commented that the definitions
used by the method of test and rating
standards are accurate today and should
be adopted by DOE without
modification. (AHRI, No. 13, p. 9–10)
AHRI added that there are differences
between reporting for some certification
programs and DOE reporting although
all values are determined per the
current method of test and rating
standard. (AHRI, No. 13, p. 9–10)
The sampling plan and determination
of represented values amendments
proposed in the December 2021 NOPR
would clarify the terminology and
requirements and would not impose any
additional burden on manufacturers
because DOE believes the clarifications
are consistent with how manufacturers
are currently testing.
DOE is maintaining in this final rule
the amends to the sampling plan and
reporting requirements for ACIMs in 10
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
CFR 429.45, replacing the term
‘‘maximum energy use’’ and ‘‘maximum
condenser water use’’ in 10 CFR 429.45
with the term ‘‘energy use’’ and
‘‘condenser water use’’, respectively,
and modifying the term and definition
of ‘‘maximum condenser water use’’ at
10 CFR 431.132 to instead refer to
‘‘condenser water use’’, consistent with
the December 2021 NOPR.
2. Test Sample Value Rounding
Requirements
DOE currently requires test results for
ACIMs to be rounded, as discussed in
section III.D.7; however, the
requirements in 10 CFR 429.45 do not
specify how values calculated in
accordance with 10 CFR 429.45(a)
would be rounded. To ensure
consistency, DOE proposed, in the
December 2021 NOPR, that any
calculations according to 10 CFR 429.45
be rounded consistent with the
rounding requirements for individual
test results. 86 FR 72322, 72351–72352.
Specifically, DOE proposed to require
that values calculated from a test sample
be rounded as follows: energy use to the
nearest 0.01 kWh/100 lb, condenser
water use to the nearest gal/100 lb, and
harvest rate to the nearest 1 lb/24 h (for
ACIMs with harvest rates greater than
50 lb/24 h) or to the nearest 0.1 lb/24
h (for ACIMs with harvest rates less
than or equal to 50 lb/24 h). 86 FR
72322, 72352.
In the December 2021 NOPR, DOE
requested comment on its proposal to
require that values calculated from a test
sample be rounded as follows: energy
use to the nearest 0.01 kWh/100 lb,
condenser water use to the nearest gal/
100 lb, and harvest rate to the nearest 1
lb/24 h (for ACIMs with harvest rates
greater than 50 lb/24 h) or to the nearest
0.1 lb/24 h (for ACIMs with harvest
rates less than or equal to 50 lb/24 h).
86 FR 72322, 72352.
In response to the December 2021
NOPR, Hoshizaki and AHRI requested
that any changes to the calculation of
values be addressed by the AHRI 810
standard committee. (Hoshizaki, No. 14,
p. 7; AHRI, No. 13, p. 10) AHRI added
that changes made during this
rulemaking should be consistent with
the current version of AHRI Standard
810, and DOE is welcome to participate
in any AHRI standard working groups to
provide suggestions for consideration.
(AHRI, No. 13, p. 10)
As discussed in section III.D.7, DOE is
amending the rounding requirements in
this final rule to be consistent with
AHRI Standard 810 (I–P)–2016 with
Addendum 1, except that for ACIMs
with harvest rates less than or equal to
PO 00000
Frm 00038
Fmt 4701
Sfmt 4700
50 lb/24 h, the harvest rate shall be
rounded to the nearest 0.1 lb/24 h.
DOE is maintaining in this final rule
that values calculated from a test sample
are required to be rounded as follows:
energy use to the nearest 0.01 kWh/100
lb, condenser water use to the nearest
gal/100 lb, and harvest rate to the
nearest 1 lb/24 h (for ACIMs with
harvest rates greater than 50 lb/24 h) or
to the nearest 0.1 lb/24 h (for ACIMs
with harvest rates less than or equal to
50 lb/24 h), consistent with the
December 2021 NOPR.
3. Enforcement Provisions
Subpart C of 10 CFR part 429
establishes enforcement provisions
applicable to covered products and
covered equipment, including ACIMs.
Product-specific enforcement provisions
are provided in 10 CFR 429.134, but that
section currently does not specify
product-specific enforcement provisions
for ACIMs. The DOE requirements in 10
CFR 429.134 provide which ratings or
measurements will be used to determine
the applicable energy or condenser
water conservation standard. Normally,
DOE provides that the certified metric
would be used for enforcement
purposes (e.g., calculation of the
applicable energy conservation
standard) if the average value measured
during enforcement testing is within a
specified percent of the rated value (the
specific allowable range varies based on
product and equipment type).
Otherwise, the average measured value
would be used.
Section 7.1 of ASHRAE Standard 29–
2009, incorporated by reference into the
DOE ACIM test procedure, allows for a
two percent weight variation between
collected ice samples when establishing
stability of an ACIM. Additionally,
section 5.5.1 of ASHRAE Standard 29–
2009 specifies that the ice-weighing
instruments are required to be accurate
to within 1.0 percent of the quantity
measured. Due to the allowable
variability in test measurements, a five
percent tolerance around the rated
capacity value likely is appropriate for
ACIMs. This tolerance is consistent with
the tolerance for ice harvest rate ratings
as specified in section 5.4 of AHRI
Standard 810 (I–P)–2016 with
Addendum 1. In the December 2021
NOPR, DOE proposed that the certified
capacity metric for ACIMs (i.e,, the
harvest rate) will be used for
determination of the maximum
allowable energy consumption and
maximum allowable condenser water
use levels only if the average measured
harvest rate during DOE testing is
within five percent of the certified
harvest rate. 86 FR 72322, 72352. If the
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
average measured harvest rate is found
to be outside of this range when
compared to the certified harvest rate,
the average measured harvest rate of the
units in the tested sample will be used
as the basis for determining the
maximum allowable energy
consumption and maximum allowable
condenser water use levels, as
applicable. Id.
In the December 2021 NOPR, DOE
requested comment on its proposal to
include a new paragraph in 10 CFR
429.134 to specify how to determine
whether the certified or measured
harvest rate is used to calculate the
maximum energy consumption and
maximum condenser water use levels.
86 FR 72322, 72352. DOE also requested
comment on whether a five percent
tolerance for the average measured
harvest rate compared to the certified
harvest rate is an appropriate tolerance
for such purposes, and if not, what
tolerance is appropriate. Id.
In response to the December 2021
NOPR, Hoshizaki commented that
further clarification is needed to
determine a response. (Hoshizaki, No.
14, p. 7) Hoshizaki requested that this
be brought to the ASHRAE 29 standard
committee for clarification and
comment. (Hoshizaki, No. 14, p. 7)
Subpart C of 10 CFR 429.134
establishes product-specific
enforcement provisions applicable to
covered products and covered
equipment. The DOE requirements in 10
CFR 429.134 provide which ratings or
measurements will be used to determine
the applicable energy or water
conservation standard. DOE’s
enforcement provisions are outside the
scope of industry standards and,
therefore, ASHRAE 29 does not apply to
DOE’s enforcement provisions.
DOE is maintaining in this final rule
the inclusion of a new paragraph in 10
CFR 429.134 to specify how to
determine whether the certified or
measured harvest rate is used to
calculate the maximum energy
consumption and maximum condenser
water use levels and to establish a five
percent tolerance for the average
measured harvest rate compared to the
certified harvest rate, consistent with
the December 2021 NOPR.
lotter on DSK11XQN23PROD with RULES2
F. Test Procedure Costs and
Harmonization
1. Test Procedure Costs and Impact
In this final rule, DOE amends the
ACIM test procedure to include lowcapacity ACIMs in the scope of the test
procedure; references the most recent
versions of the test procedures
incorporated by reference; clarifies the
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
stability criteria; revises clearances for
test installations; includes additional
updates to clarify appropriate test
measurements, conditions, settings, and
setup requirements; establishes
provisions for the voluntary
measurement of potable water use; and
updates calculation instructions. The
following paragraphs discuss DOE’s
determination of any impacts on testing
costs or measured performance resulting
from these amendments.
a. Testing Cost Impacts
i. Per-Test Cost
In the January 2012 final rule, DOE
estimated a per-test cost of $5,000 to
$7,500 for the current ACIM test
procedure. 77 FR 1591, 1610. In the
December 2021 NOPR, DOE initially
determined that the low end of that
range, or $5,000, is representative of
current ACIM per test cost. 86 FR 72322,
72352.
As discussed in section III.D.2, the
current test procedure requires multiple
cycles to determine stability, after
which additional cycles are performed
to measure performance. In this final
rule, DOE references the updated
version of ASHRAE Standard 29–2015,
which includes updated stabilization
requirements, and expressly requires
that the cycles or samples used for the
capacity test are stable, thus eliminating
the need to perform separate cycles for
meeting the stability criteria and for
testing performance (i.e., reducing the
total number of cycles required for
testing). For batch ice makers, this
amendment will eliminate the need for
testing two cycles prior to the test. For
continuous ice makers, this amendment
will eliminate the need for measuring
three consecutive 14.4 min samples
taken within a 1.5-hour period prior to
the test.
In the December 2021 NOPR, DOE
estimated that total ice maker test
duration, including set up, pull-down,
and test operation currently requires 8
hours. 86 FR 72322, 72352. Under the
amended approach, consistent with the
December 2021 NOPR, DOE estimates
that the total test time will decrease by
approximately 1 hour, representing a
12.5-percent reduction in test duration.
Taking overhead costs into account,
consistent with the December 2021
NOPR, DOE estimates that the proposed
stabilization requirement will decrease
the test cost by approximately 6 percent,
or $300 per test based on the initial
$5,000 per-test estimate. Because DOE
requires manufacturers to test at least
two units per model to certify
performance, testing will cost
manufacturers approximately $600 less
PO 00000
Frm 00039
Fmt 4701
Sfmt 4700
65893
per basic model for all future basic
models tested in accordance with this
amended test procedure, resulting in a
total test cost of $9,400 per basic
model.39
In response to the December 2021
NOPR, Hoshizaki commented that the
use of test cycles to confirm stability is
already done, so no additional cost is
associated. (Hoshizaki, No. 14, p. 7)
AHRI commented that stability
should be determined in accordance
with ASHRAE Standard 29 Provisions
to avoid any incurred cost to testing.
(AHRI, No. 13, p. 10)
IOM commented that DOE’s proposal
to further restrict the definition of
‘‘stability’’ has the potential to increase
burden and cost, as all test cycles must
have ice harvest rates within 2% rather
than consecutive test cycles. (IOM, No.
11, p. 3)
AHAM commented that DOE deviated
from ASHRAE and AHRI standards in
some ways in order to create a test
procedure that could be applicable to
residential products but that the
proposed test and its deviations are
unworkable, unrealistic, and
burdensome given the way residential
appliance manufacturers carry out
testing and the test facilities residential
ice maker manufacturers have. (AHAM,
No. 18, p. 9) AHAM also stated that
since the proposed test requires
complete attention to the test once it
starts, the technician must be dedicated
to this test due to the time requirements
of 15 minutes for the fill, plus-or-minus
nine seconds to empty the bin, and the
five minute requirement to start the next
test. (AHAM, No. 18, p. 13–14) AHAM
states that this is a burdensome
requirement because it will require
active monitoring by the test technician
as opposed to a test that can be largely
automated, which may require
manufacturers to hire additional
technicians. Id.
DOE acknowledges the comment
regarding the potential for the amended
stability requirements to increase
burden and cost. Although it is possible
a test unit will require additional cycles
to meet the amended stability
requirements, based on investigative
testing using the amended stability
requirements, DOE observed that the
average number of cycles or samples
required to reach stability was 3.0 based
on a sample of 39 batch ACIM tests and
6 continuous ACIM tests which
indicates that unstable operation would
represent a minority of tests conducted.
DOE estimates that the total test time
will decrease by approximately 1 hour,
representing a 12.5-percent reduction in
39 Based
E:\FR\FM\01NOR2.SGM
on a new per-test cost of $4,700.
01NOR2
65894
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
test duration, for the majority of tests
conducted. The amended stability
requirements address unstable operation
to ensure repeatable and reproducible
test results.
DOE reaffirms its determination that
testing will cost manufacturers
approximately $600 less per basic
model for all future basic models tested
in accordance with this amended test
procedure, as compared to the existing
test procedure. DOE recognizes that
testing does require facilities and
technician labor, and maintains the cost
estimate of $4,700 per individual test or
$9,400 when testing to certify
performance of a basic model (requiring
at least two test units).
lotter on DSK11XQN23PROD with RULES2
ii. One-Time Cost
As discussed in section III.D.3.a, this
final rule implements a relative
humidity test condition.
In the December 2021 NOPR, DOE
estimated the one-time cost for
purchasing relative humidity controls to
range from $1,000 to $5,000, depending
on the method that is chosen. 86 FR
72322, 72353. DOE estimated that the
purchase and installation of a
humidifier boiler with modulating
valves that releases steam on the wall to
control relative humidity costs $5,000,
although less expensive options could
be used, such as a dedicated coil with
reheat, steam generators, humidifiers,
and dehumidifiers. Id. In addition, DOE
also estimated that instrumentation to
measure relative humidity at an
accuracy of ±2 percent costs around
$500.40 Id.
Hoshizaki and AHRI stated that
upgrading facilities for water hardness
and relative humidity could incur
significant facility upgrade costs.
(Hoshizaki, No. 14, p. 8; AHRI, No. 13,
p. 10–11) AHAM stated that the relative
humidity requirement is unduly
burdensome for manufacturers. (AHAM,
No. 18, p. 12–13) AHAM commented
that unless the test chamber was
initially designed with
dehumidification capabilities and
appropriately sealed, there is a
significant investment to achieve the
35.0 ± 5.0 percent levels required in the
proposed test procedure. Id. Residential
ice maker manufacturers have not built
test chambers with these capabilities in
mind and, thus, this provision would
likely require all manufacturers to
overhaul their test facilities. Id.
Hoshizaki stated that extending tests
for purge water and/or standby energy
would require additional test time that
40 For example, see Campbell Scientific model
EE181–L at www.campbellsci.com/ee181-l.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
would hamper design cycles.
(Hoshizaki, No. 14, p. 8)
This final rule does not implement
water hardness requirements as
proposed in the December 2021 NOPR.
Similarly, this final rule does not
directly account for energy or water
used during intermittent flush or purge
cycles nor accounts for standby or ice
storage energy use. Regarding humidity
controls, DOE has reviewed and
maintains its estimates from the
December 2021 NOPR regarding the
costs associated with purchasing
relative humidity controls and
instrumentation, as described in this
section.
As discussed in section III.A, this
final rule expands the scope of the test
procedure to include low-capacity
ACIMs. This final rule incorporates
additional test procedure requirements
to ensure appropriate testing of lowcapacity ACIMs, as discussed in section
III.D.1. In the December 2021 NOPR,
DOE requested comment on any
expected costs associated with the
proposed amendment to expand test
procedure scope to include low-capacity
ACIMs. 86 FR 72322, 72353.
Specifically, DOE requested comment
on whether any manufacturers are
currently making representations of
low-capacity ACIM energy consumption
based on test methods that would
produce measures of performance that
would be inconsistent with the existing
DOE test procedure or the test
procedure for low-capacity ACIMs as
proposed in the December 2021 NOPR.
86 FR 72322, 72353–72354.
DOE stated in the December 2021
NOPR that based on a review of lowcapacity ACIMs available on the market,
DOE preliminarily determined that
manufacturers either make no claims
regarding the energy consumption of
their low-capacity ACIM models, or
currently specify energy consumption in
accordance with the existing DOE test
procedure (and referenced industry
standards). DOE stated that it expects
that the manufacturers currently
electing to make no claims regarding
low-capacity ACIM energy consumption
will continue to do so even after a test
procedure is established.
In response to the December 2021
NOPR, Hoshizaki commented there are
representations of low-capacity ACIM
energy consumption. (Hoshizaki, No.
14, p. 8) However, Hoshizaki and AHRI
commented that low-capacity ACIMs
were not included in the scope for
DOE’s 2010 or 2018 ACIM energy
conservation standards. (Hoshizaki, No.
14, p. 8; AHRI, No. 13, p. 11) AHRI
urged DOE to exclude low-capacity
units until they are included into the
PO 00000
Frm 00040
Fmt 4701
Sfmt 4700
appropriate method of test because
including these units would require
significant testing to factor the energy
use and any changes to meet the current
standards designed for units above 50
pounds. (AHRI, No. 13, p. 11)
Hoshizaki requested that this be
brought up in the ASHRAE 29 standard
committee to discuss test method
options for low-capacity ACIMs.
(Hoshizaki, No. 14, p. 8)
As discussed, DOE estimates that the
amended test procedure has a per-test
cost of $4,700, and that testing two basic
models for certification purposes would
have a total cost of $9,400. To the extent
that manufacturers are currently
voluntarily making representations of
low-capacity ACIM energy consumption
based on test methods inconsistent with
the DOE test procedure as amended by
this final rule, such manufacturers
would incur a one-time cost of $9,400
per basic model to make voluntary
representations consistent with the DOE
test procedure as amended by this final
rule.
Low-capacity ACIMs are not currently
subject to DOE testing or energy
conservation standards. Manufacturers
will not be required to test low-capacity
ACIMs until such time as the
compliance date for any newly
established energy conservation
standards for such equipment. Under
the amended test procedure, were a
manufacturer to choose to make
representations of the energy efficiency
or energy use of a low-capacity ACIM,
beginning 360 days after publication of
the final rule in the Federal Register,
manufacturers would be required to
base such representations on the DOE
test procedure. (42 U.S.C. 6314(d)(1))
b. Impact on Measured Performance
DOE expects that any impact from the
other amendments to the measured
efficiency of certified ACIMs is de
minimis as compared to the current test
procedure, as discussed in detail for
each proposal in section III in this final
rule. The amendments will generally
improve representativeness,
repeatability, and reproducibility of
DOE’s test procedure. Additionally,
certain amendments will also
incorporate test requirements consistent
with DOE guidance or test procedure
waivers already in effect for testing
ACIMs.
Specifically, DOE incorporated the
following amendments: (1) updating
references to the latest versions of the
relevant industry standards (see section
III.C); (2) clarifying stabilization criteria;
(3) incorporating a test condition for
relative humidity and a clarification
regarding water pressure (see section
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
III.D.3); (4) establishing and clarifying
test setup and setting requirements (see
section III.D.4); (5) specifying a
voluntary measurement of potable water
use (see section III.D.8); and (6)
including revisions to test sample
calculations and enforcement provisions
(see section III.E).
In response to the December 2021
NOPR, Hoshizaki and AHRI commented
that addressing all the proposed
amendments would necessitate retesting
most ACIM units, placing undue burden
on manufacturers. (Hoshizaki, No. 14, p.
8; AHRI, No. 13, p. 10–11) Hoshizaki
added that the proposals would require
testing of 190 models with multiple
samples of each. (Hoshizaki, No. 14, p.
8)
DOE does not agree with Hoshizaki
and AHRI’s assertions that the amended
test procedure would necessitate
retesting most ACIM units. As this final
rule discusses within each relevant
section, DOE expects that any impact on
measured performance from these
amendments is expected to be de
minimis as compared to the current test
procedure. Equipment with no
measurable change to energy use under
the amended test procedure would not
need to be retested. To the extent that
a manufacturer determines that a
particular test procedure amendment
would impact the existing measured
energy use for a specific basic model,
DOE estimates a re-testing cost of $9,400
per basic model.
2. Harmonization With Industry
Standards
DOE’s established practice is to adopt
relevant industry standards as DOE test
procedures unless such methodology
would be unduly burdensome to
conduct or would not produce test
results that reflect the energy efficiency,
energy use, water use (as specified in
EPCA) or estimated operating costs of
that product during a representative
average use cycle. 10 CFR 431.4; section
8(c) of appendix A to subpart C of part
430. In cases where the industry
standard does not meet EPCA statutory
criteria for test procedures, DOE will
make modifications through the
rulemaking process to these standards
and incorporate the modified standard
as the DOE test procedure.
The test procedure for ACIMs at 10
CFR 431.134 incorporates by reference
certain provisions of AHRI Standard
810–2007 and ASHRAE Standard 29–
2009. DOE references 810–2007 for
definitions and test procedure
requirements. DOE references ASHRAE
Standard 29–2009 for test procedure
requirements and ice hardness factor
calculations. In January 2018, AHRI
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
released an updated version of the 810
Standard which DOE evaluated as part
of this rulemaking. In January 2015,
ASHRAE released an updated version of
the 29 Standard which DOE evaluated
as part of this rulemaking. The industry
standards DOE is incorporating by
reference via amendments described in
this final rule are discussed in further
detail in section IV.N.
G. Effective and Compliance Dates
The effective date for the adopted test
procedure amendment will be 30 days
after publication of this final rule in the
Federal Register. EPCA prescribes that
all representations of energy efficiency
and energy use, including those made
on marketing materials and product
labels, must be made in accordance with
an amended test procedure, beginning
360 days after publication of the final
rule in the Federal Register. (42 U.S.C.
6314(d)(1)) EPCA provides an allowance
for individual manufacturers to petition
DOE for an extension of the 360-day
period if the manufacturer may
experience undue hardship in meeting
the deadline. (42 U.S.C. 6314(d)(2)) To
receive such an extension, petitions
must be filed with DOE no later than 60
days before the end of the 360-day
period and must detail how the
manufacturer will experience undue
hardship. (Id.) To the extent the
modified test procedure adopted in this
final rule is required only for the
evaluation and issuance of updated
efficiency standards, compliance with
the amended test procedure does not
require use of such modified test
procedure provisions until the
compliance date of updated standards.
Upon the compliance date of test
procedure provisions in this final rule
any waivers that had been previously
issued and are in effect that pertain to
issues addressed by such provisions are
terminated. 10 CFR 431.404(h)(3).
Recipients of any such waivers are
required to test the products subject to
the waiver according to the amended
test procedure as of the compliance date
of the amended test procedure. The
amendments adopted in this document
pertain to issues addressed by a waiver
granted to Hoshizaki in Case No. 2020–
001. 85 FR 68315.
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Orders
12866 and 13563
Executive Order (‘‘E.O.’’) 12866,
‘‘Regulatory Planning and Review,’’ as
supplemented and reaffirmed by E.O.
13563, ‘‘Improving Regulation and
Regulatory Review,’’ 76 FR 3821 (Jan.
PO 00000
Frm 00041
Fmt 4701
Sfmt 4700
65895
21, 2011), requires agencies, to the
extent permitted by law, to (1) propose
or adopt a regulation only upon a
reasoned determination that its benefits
justify its costs (recognizing that some
benefits and costs are difficult to
quantify); (2) tailor regulations to
impose the least burden on society,
consistent with obtaining regulatory
objectives, taking into account, among
other things, and to the extent
practicable, the costs of cumulative
regulations; (3) select, in choosing
among alternative regulatory
approaches, those approaches that
maximize net benefits (including
potential economic, environmental,
public health and safety, and other
advantages; distributive impacts; and
equity); (4) to the extent feasible, specify
performance objectives, rather than
specifying the behavior or manner of
compliance that regulated entities must
adopt; and (5) identify and assess
available alternatives to direct
regulation, including providing
economic incentives to encourage the
desired behavior, such as user fees or
marketable permits, or providing
information upon which choices can be
made by the public. DOE emphasizes as
well that E.O. 13563 requires agencies to
use the best available techniques to
quantify anticipated present and future
benefits and costs as accurately as
possible. In its guidance, the Office of
Information and Regulatory Affairs
(‘‘OIRA’’) in the Office of Management
and Budget (‘‘OMB’’) has emphasized
that such techniques may include
identifying changing future compliance
costs that might result from
technological innovation or anticipated
behavioral changes. For the reasons
stated in the preamble, this final
regulatory action is consistent with
these principles.
Section 6(a) of E.O. 12866 also
requires agencies to submit ‘‘significant
regulatory actions’’ to OIRA for review.
OIRA has determined that this final
regulatory action does not constitute a
‘‘significant regulatory action’’ under
section 3(f) of E.O. 12866. Accordingly,
this action was not submitted to OIRA
for review under E.O. 12866.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of a final regulatory flexibility analysis
(FRFA) for any final rule where the
agency was first required by law to
publish a proposed rule for public
comment, unless the agency certifies
that the rule, if promulgated, will not
have a significant economic impact on
a substantial number of small entities.
E:\FR\FM\01NOR2.SGM
01NOR2
65896
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
As required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s website: www.energy.gov/gc/
office-general-counsel.
DOE reviewed this final rule under
the provisions of the Regulatory
Flexibility Act and the procedures and
policies published on February 19,
2003. DOE has concluded that this rule
would not have a significant impact on
a substantial number of small entities.
The factual basis for this certification is
as follows: The Small Business
Administration (‘‘SBA’’) considers a
business entity to be a small business,
if, together with its affiliates, it employs
less than a threshold number of workers
specified in 13 CFR part 121. The size
standards and codes are established by
the 2017 North American Industry
Classification System (‘‘NAICS’’).
ACIM manufacturers are classified
under NAICS code 333415, ‘‘Airconditioning and Warm Air Heating
Equipment and Commercial and
Industrial Refrigeration Equipment
Manufacturing,’’ which includes icemaking machinery manufacturing.41
The SBA sets a threshold of 1,250
employees or fewer for an entity to be
considered as a small business. This
employee threshold includes all
employees in a business’s parent
company and any other subsidiaries.
DOE conducted a focused inquiry into
small business manufacturers of the
equipment covered by this rulemaking.
To identify companies that import or
otherwise manufacture ACIMs with
harvest rates greater than 50 lb/24h,
DOE expanded on the analysis
conducted for the December 2021
NOPR. This updated analysis included
a review of DOE’s Compliance
Certification Database (‘‘CCD’’),42
California Energy Commission’s
Modernized Appliance Efficiency
Database System (‘‘MAEDbS’’),43 the
41 The SBA Size Standards are available at:
www.sba.gov/document/support-table-sizestandards (last accessed June 2, 2022).
42 U.S. Department of Energy Compliance
Certification Database, available at:
www.regulations.doe.gov/certification-data/
products.html#q=Product_Group_s%3A* (last
accessed November 11, 2021).
43 California Energy Commission. Modernized
Appliance Efficiency Database System. Available at:
cacertappliances.energy.ca.gov/Pages/
ApplianceSearch.aspx (accessed November 17,
2021).
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
Air-Conditioning, Heating, and
Refrigeration Institute’s (‘‘AHRI’s’’)
Directory of Certified Product
Performance,44 and retailer websites.
DOE relied on retailer websites and
other public sources to identify
companies that import or otherwise
manufacture low-capacity ACIMs,
consistent with the December 2021
NOPR. Since the December 2021 NOPR,
and consistent with the approach
detailed in the Preliminary Analysis
Technical Support Document published
on March 24, 2022,45 DOE conducted
additional research to determine which
companies selling ACIMs in the United
States are original equipment
manufacturers (‘‘OEMs’’) of the
equipment covered by this rulemaking.
Using publicly available information
from manufacturer websites, import and
export data (e.g., bills of lading from
Panjiva) 46 and basic model numbers,
DOE identified 22 ACIM OEMs.
DOE then consulted publicly
available data, such as individual
company websites and subscriptionbased market research tools (e.g., Dun &
Bradstreet) 47 to determine company
location, headcount, and annual
revenue. DOE screened out companies
that do not offer equipment covered by
this rulemaking, do not meet the SBA’s
definition of a ‘‘small business,’’ or are
foreign-owned and operated. Of the 22
OEMs identified, DOE determined that
two domestic OEMs qualify as ‘‘small
businesses.’’ DOE estimates that one
small OEM has an annual revenue of
approximately $11.2 million and the
other has an annual revenue of
approximately $186.5 million.
Consistent with its preliminary
determination in the December 2021
NOPR, DOE does not expect small
domestic ACIM OEMs to incur costs as
a result of the amended test procedure.
However, in the event that any test
facilities require upgrade to meet the
amended test conditions for relative
humidity, DOE has estimated the costs
of this potential upgrade to be $5,500,
as discussed in section III.F.1.a of this
44 The Air Conditioning, Heating, and
Refrigeration Institute. Directory of Certified
Product Performance. Available at:
www.ahridirectory.org/ (accessed November 17,
2021).
45 ‘‘2022–03 Technical Support Document:
Energy Efficiency Program For Consumer Products
And Commercial And Industrial Equipment:
Automatic Commercial Ice Makers.’’ See chapter 12,
section 12.3.3 (published on March 24, 2022).
Available at: www.regulations.gov/document/EERE2017-BT-STD-0022-0009.
46 Panjiva. S&P Global Supply Chain Intelligence.
Available at: panjiva.com/import-export/UnitedStates (last accessed June 5, 2022).
47 The Dun & Bradstreet Hoovers subscription
login is accessible at: /app.dnbhoovers.com/ (last
accessed June 2, 2022).
PO 00000
Frm 00042
Fmt 4701
Sfmt 4700
final rule.48 DOE estimates that this
potential cost would represent less than
0.1 percent of annual revenues for both
identified small businesses.
In response to the December 2021
NOPR, Hoshizaki commented that the
proposed changes would necessitate retesting of ACIM models by many
manufacturers. Hoshizaki suggested that
small entities may not have the means
to test their models in house and would
have to send units to test at third party
labs. (Hoshizaki, No. 14, p. 8) AHRI
noted that the changes outlined in the
December 2021 NOPR would necessitate
retesting of existing models and would
therefore ‘‘most definitely place undue
burden and additional cost on OEMs.’’
Specifically, they stated that the
humidity control requirement would
require retesting of every model and
would also necessitate facility upgrade
costs. AHRI also asserted that this
requirement may limit the ability to find
external test labs with appropriate test
chambers and thereby disadvantage
small entities who do not have the
means to test in house and would be
subject to scheduling at third party
testing facilities. AHRI noted that the
costs associated with the proposal
‘‘would not be miniscule’’ and such
testing would not be advantageous with
all the third-party testing needed to
verify safety for ACIM’s that are
changing to flammable refrigerants.
AHRI also noted that the proposed 3foot side clearance requirement could
also impact the ability of small entities
participating in this market. (AHRI, No.
13, p. 11)
As detailed in section III.F.1 of this
final rule, DOE expects that the impact
from these amendments to the measured
efficiency of certified ACIMs is expected
to be de minimis as compared to the
current test procedure. DOE expects that
it is unlikely that a substantial portion
of ACIM units would need to be retested
or recertified as a result of this final
rule, and therefore that manufacturers
will be able to rely on data generated
under the existing test procedure. If a
manufacturer re-tests models according
to the amended test procedure, DOE
estimates a testing cost of $9,400 per rerated basic model.49 DOE notes that the
small OEM with an annual revenue of
approximately $11.2 million offers four
basic models. The other small OEM
48 DOE estimates the cost for purchasing relative
humidity controls to range from $1,000 to $5,000,
depending on the method that is chosen, and an
additional cost of $500 for a relative humidity
sensor.
49 Based on the $5,000 per unit test cost estimate
and the $300 savings due to the stability criteria,
as detailed in this final rule. Each basic model is
tested twice: ($5,000¥$300) × 2 = $9,400.
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
with an annual revenue of
approximately $186.5 million offers two
basic models.50 Therefore, DOE expects
that any re-testing would account for
less than 0.1 percent of each company’s
annual revenue.51
Therefore, DOE concludes that the
cost effects accruing from the final rule
would not have a ‘‘significant economic
impact on a substantial number of small
entities,’’ and that the preparation of a
FRFA is not warranted. DOE has
submitted a certification and supporting
statement of factual basis to the Chief
Counsel for Advocacy of the Small
Business Administration for review
under 5 U.S.C. 605(b).
C. Review Under the Paperwork
Reduction Act of 1995
lotter on DSK11XQN23PROD with RULES2
Manufacturers of ACIMs must certify
to DOE that their products comply with
any applicable energy conservation
standards. To certify compliance,
manufacturers must first obtain test data
for their products according to the DOE
test procedures, including any
amendments adopted for those test
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including
ACIMs. (See generally 10 CFR part 429.)
The collection-of-information
requirement for the certification and
recordkeeping is subject to review and
approval by OMB under the Paperwork
Reduction Act (PRA). This requirement
has been approved by OMB under OMB
control number 1910–1400. Public
reporting burden for the certification is
estimated to average 35 hours per
response, including the time for
reviewing instructions, searching
existing data sources, gathering and
maintaining the data needed, and
completing and reviewing the collection
of information.
DOE is not amending the certification
or reporting requirements for ACIMs in
this final rule. Instead, DOE may
consider proposals to amend the
certification requirements and reporting
for ACIMs under a separate rulemaking
regarding appliance and equipment
certification. DOE will address changes
50 DOE used the estimated annual revenue figures
from the Dun & Bradstreet Hoovers subscriptionbased market research tool. The Dun & Bradstreet
login is accessible at: /app.dnbhoovers.com/ (last
accessed June 2, 2022).
51 One small OEM may incur testing costs of
$37,600, if they choose to re-test their 4 models
according to the amended test procedure. (4 ×
$9,400 = $37,600) The other small OEM may incur
testing costs of $18,800, if they choose to re-test
their 2 models according to the amended test
procedure. (2 × $9,400 = $18,800)
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
to OMB Control Number 1910–1400 at
that time, as necessary.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
In this final rule, DOE establishes test
procedure amendments that it expects
will be used to develop and implement
future energy conservation standards for
ACIMs. DOE has determined that this
rule falls into a class of actions that are
categorically excluded from review
under the National Environmental
Policy Act of 1969 (42 U.S.C. 4321 et
seq.) and DOE’s implementing
regulations at 10 CFR part 1021.
Specifically, DOE has determined that
adopting test procedures for measuring
energy efficiency of consumer products
and industrial equipment is consistent
with activities identified in 10 CFR part
1021, appendix A to subpart D, A5 and
A6. Accordingly, neither an
environmental assessment nor an
environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 4, 1999), imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive order also requires agencies to
have an accountable process to ensure
meaningful and timely input by State
and local officials in the development of
regulatory policies that have federalism
implications. On March 14, 2000, DOE
published a statement of policy
describing the intergovernmental
consultation process it will follow in the
development of such regulations. 65 FR
13735. DOE examined this final rule
and determined that it will not have a
substantial direct effect on the States, on
the relationship between the National
Government and the States, or on the
distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
PO 00000
Frm 00043
Fmt 4701
Sfmt 4700
65897
final rule. States can petition DOE for
exemption from such preemption to the
extent, and based on criteria, set forth in
EPCA. (42 U.S.C. 6297(d)) No further
action is required by Executive Order
13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard; and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that executive agencies make
every reasonable effort to ensure that the
regulation (1) clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms; and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, this final rule
meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (‘‘UMRA’’) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. (Pub. L. 104–4, sec. 201
(codified at 2 U.S.C. 1531)). For a
regulatory action resulting in a rule that
may cause the expenditure by State,
local, and Tribal governments, in the
aggregate, or by the private sector of
$100 million or more in any one year
(adjusted annually for inflation), section
202 of UMRA requires a Federal agency
to publish a written statement that
estimates the resulting costs, benefits,
and other effects on the national
economy. (2 U.S.C. 1532(a), (b)) The
E:\FR\FM\01NOR2.SGM
01NOR2
65898
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
UMRA also requires a Federal agency to
develop an effective process to permit
timely input by elected officers of State,
local, and Tribal governments on a
proposed ‘‘significant intergovernmental
mandate,’’ and requires an agency plan
for giving notice and opportunity for
timely input to potentially affected
small governments before establishing
any requirements that might
significantly or uniquely affect small
governments. On March 18, 1997, DOE
published a statement of policy on its
process for intergovernmental
consultation under UMRA. 62 FR
12820; also available at
www.energy.gov/gc/office-generalcounsel. DOE examined this final rule
according to UMRA and its statement of
policy and determined that the rule
contains neither an intergovernmental
mandate, nor a mandate that may result
in the expenditure of $100 million or
more in any year, so these requirements
do not apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
final rule will not have any impact on
the autonomy or integrity of the family
as an institution. Accordingly, DOE has
concluded that it is not necessary to
prepare a Family Policymaking
Assessment.
lotter on DSK11XQN23PROD with RULES2
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this regulation
will not result in any takings that might
require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). Pursuant to OMB
Memorandum M–19–15, Improving
Implementation of the Information
Quality Act (April 24, 2019), DOE
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
published updated guidelines which are
available at www.energy.gov/sites/prod/
files/2019/12/f70/DOE%20Final
%20Updated%20IQA%20
Guidelines%20Dec%202019.pdf. DOE
has reviewed this final rule under the
OMB and DOE guidelines and has
concluded that it is consistent with
applicable policies in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
significant energy action. A ‘‘significant
energy action’’ is defined as any action
by an agency that promulgated or is
expected to lead to promulgation of a
final rule, and that (1) is a significant
regulatory action under Executive Order
12866, or any successor order; and (2)
is likely to have a significant adverse
effect on the supply, distribution, or use
of energy; or (3) is designated by the
Administrator of OIRA as a significant
energy action. For any significant energy
action, the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use if the
regulation is implemented, and of
reasonable alternatives to the action and
their expected benefits on energy
supply, distribution, and use.
This regulatory action is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; ‘‘FEAA’’) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (‘‘FTC’’)
PO 00000
Frm 00044
Fmt 4701
Sfmt 4700
concerning the impact of the
commercial or industry standards on
competition.
The modifications to the test
procedure for ACIMs adopted in this
final rule incorporates testing methods
contained in certain sections of the
following commercial standards: AHRI
Standard 810 (I–P)–2016 with
Addendum 1 and ASHRAE Standard
29–2015. DOE has evaluated these
standards and is unable to conclude
whether it fully complies with the
requirements of section 32(b) of the
FEAA (i.e., whether it was developed in
a manner that fully provides for public
participation, comment, and review.)
DOE has consulted with both the
Attorney General and the Chairman of
the FTC about the impact on
competition of using the methods
contained in these standards and has
received no comments objecting to their
use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will
report to Congress on the promulgation
of this rule before its effective date. The
report will state that it has been
determined that the rule is not a ‘‘major
rule’’ as defined by 5 U.S.C. 804(2).
N. Description of Materials Incorporated
by Reference
DOE incorporates by reference the
following standards:
AHRI Standard 810 (I–P)–2016 with
Addendum 1. Specifically, the test
procedure codified by this final rule
references section 3, ‘‘Definitions,’’
section 4, ‘‘Test Requirements,’’ and
section 5.2, ‘‘Standard Ratings’’. AHRI
Standard 810 (I–P)–2016 with
Addendum 1 is an industry-accepted
standard that provides a method to rate
the performance of automatic
commercial ice makers.
AHRI standards are reasonably
available from the Air-Conditioning,
Heating, and Refrigeration Institute,
2111 Wilson Blvd., Suite 500, Arlington,
VA 22201, 703–524–8800, ahri@
ahrinet.org, or www.ahrinet.org.
ASHRAE Standard 29–2015. ASHRAE
Standard 29–2015 is an industryaccepted standard that provides a
method of test to measure the
performance of automatic commercial
ice makers.
Copies of ASHRAE standards are
reasonably available from the American
Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc., 1791
Tullie Circle NE, Atlanta, GA 30329,
(404) 636–8400, ashrae@ashrae.org, or
www.ashrae.org.
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
§ 429.45 Automatic commercial ice
makers.
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Intergovernmental relations, Reporting
and recordkeeping requirements, Small
businesses.
(a) * * *
(2) For each basic model of automatic
commercial ice maker selected for
testing, a sample of sufficient size shall
be randomly selected and tested to
ensure that any represented value of
energy use, condenser water use, or
other measure of consumption of a basic
model for which consumers would favor
lower values shall be greater than or
equal to the higher of:
(i) The mean of the sample, where:
10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation test
procedures, Incorporation by reference,
Reporting and recordkeeping
requirements.
Signing Authority
This document of the Department of
Energy was signed on October 6, 2022,
by Francisco Alejandro Moreno, Acting
Assistant Secretary for Energy Efficiency
and Renewable Energy, pursuant to
delegated authority from the Secretary
of Energy. That document with the
original signature and date is
maintained by DOE. For administrative
purposes only, and in compliance with
requirements of the Office of the Federal
Register, the undersigned DOE Federal
Register Liaison Officer has been
authorized to sign and submit the
document in electronic format for
publication, as an official document of
the Department of Energy. This
administrative process in no way alters
the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on October 18,
2022.
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
For the reasons stated in the
preamble, DOE amends parts 429 and
431 of chapter II of title 10, Code of
Federal Regulations as set forth below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
lotter on DSK11XQN23PROD with RULES2
■
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
2. Amend § 429.45 by revising
paragraph (a)(2) and adding paragraph
(a)(3) to read as follows:
■
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
4. The authority citation for part 431
continues to read as follows:
■
And, x¯ is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(ii) The upper 95 percent confidence
limit (UCL) of the true mean divided by
1.10, where:
UCL
= x-
to.9s
(.ln)
And x¯ is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.95 is the t
statistic for a 95 percent two-tailed
confidence interval with n-1 degrees of
freedom (from appendix A to this
subpart).
(3) The harvest rate of a basic model
is the mean of the measured harvest
rates for each tested unit of the basic
model, based on the same tests to
determine energy use and condenser
water use, if applicable. Round the
mean harvest rate to the nearest pound
of ice per 24 hours (lb/24 h) for harvest
rates above 50 lb/24 h; round the mean
harvest rate to the nearest 0.1 lb/24 h for
harvest rates less than or equal to 50 lb/
24 h.
*
*
*
*
*
■ 3. Amend § 429.134 by adding
paragraph (w) to read as follows:
§ 429.134 Product-specific enforcement
provisions.
*
*
*
*
*
(w) Automatic commercial ice
makers—verification of harvest rate.
The harvest rate will be measured
pursuant to the test requirements of 10
CFR part 431 for each unit tested. The
results of the measurement(s) will be
averaged and compared to the value of
harvest rate certified by the
manufacturer of the basic model. The
certified harvest rate will be considered
valid only if the average measured
harvest rate is within five percent of the
certified harvest rate.
(1) If the certified harvest rate is found
to be valid, the certified harvest rate will
PO 00000
Frm 00045
Fmt 4701
Sfmt 4700
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
5. Amend § 431.132 by:
a. Adding a definition in alphabetical
order for ‘‘Baffle’’;
■ b. Revising the definition of ‘‘Batch
type ice maker’’;
■ c. Adding a definition in alphabetical
order for ‘‘Condenser water use’’;
■ d. Removing the definition of ‘‘Cube
type ice’’;
■ e. Revising the definition of ‘‘Energy
use’’;
■ f. Removing the definition of
‘‘Maximum condenser water use’’; and
■ g. Adding definitions in alphabetical
order for ‘‘Portable automatic
commercial ice maker’’, ‘‘Potable water
use’’, and ‘‘Refrigerated storage
automatic commercial ice maker’’.
The additions and revisions read as
follows:
■
■
§ 431.132 Definitions concerning
automatic commercial ice makers.
*
*
*
*
*
Baffle means a partition (usually
made of flat material like cardboard,
plastic, or sheet metal) that reduces or
prevents recirculation of warm air from
an ice maker’s air outlet to its air inlet—
or, for remote condensers, from the
condenser’s air outlet to its inlet.
*
*
*
*
*
Batch type ice maker means an ice
maker having alternate freezing and
harvesting periods.
Condenser water use means the total
amount of water used by the condensing
unit (if water-cooled), stated in gallons
per 100 pounds (gal/100 lb) of ice, in
multiples of 1.
*
*
*
*
*
Energy use means the total energy
consumed, stated in kilowatt hours per
one-hundred pounds (kWh/100 lb) of
ice, in multiples of 0.01. For remote
condensing (but not remote compressor)
automatic commercial ice makers and
remote condensing and remote
E:\FR\FM\01NOR2.SGM
01NOR2
ER01NO22.002
The Secretary of Energy has approved
publication of this final rule.
be used as the basis for determining the
maximum energy use and maximum
condenser water use, if applicable,
allowed for the basic model.
(2) If the certified harvest rate is found
to be invalid, the average measured
harvest rate of the units in the sample
will be used as the basis for determining
the maximum energy use and maximum
condenser water use, if applicable,
allowed for the basic model.
ER01NO22.001
V. Approval of the Office of the
Secretary
65899
65900
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
compressor automatic commercial ice
makers, total energy consumed shall
include the energy use of the ice-making
mechanism, the compressor, and the
remote condenser or condensing unit.
*
*
*
*
*
Portable automatic commercial ice
maker means an automatic commercial
ice maker that does not have a means to
connect to a water supply line and has
one or more reservoirs that are manually
supplied with water.
Potable water use means the amount
of potable water used in making ice,
which is equal to the sum of the ice
harvested, dump or purge water, and the
harvest water, expressed in gal/100 lb,
in multiples of 0.1, and excludes any
condenser water use.
Refrigerated storage automatic
commercial ice maker means an
automatic commercial ice maker that
has a refrigeration system that actively
refrigerates the self-contained ice
storage bin.
*
*
*
*
*
■ 6. Revise § 431.133 to read as follows:
lotter on DSK11XQN23PROD with RULES2
§ 431.133 Materials incorporated by
reference.
Certain material is incorporated by
reference into this subpart with the
approval of the Director of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. To enforce
any edition other than that specified in
this section, the U.S. Department of
Energy (DOE) must publish a document
in the Federal Register and the material
must be available to the public. All
approved incorporation by reference
(IBR) material is available for inspection
at DOE and at the National Archives and
Records Administration (NARA).
Contact DOE at: the U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Program, Sixth Floor, 950
L’Enfant Plaza SW, Washington, DC
20024, (202)-586–9127, Buildings@
ee.doe.gov, www.energy.gov/eere/
buildings/building-technologies-office.
For information on the availability of
this material at NARA, email:
fr.inspection@nara.gov, or go to:
www.archives.gov/federal-register/cfr/
ibr-locations.html. The material may be
obtained from the following sources:
(a) AHRI. Air-Conditioning, Heating,
and Refrigeration Institute, 2111 Wilson
Blvd., Suite 500, Arlington, VA 22201;
(703) 524–8800; ahri@ahrinet.org;
www.ahrinet.org.
(1) AHRI Standard 810 (I–P)–2016
with Addendum 1, Performance Rating
of Automatic Commercial Ice-Makers,
January 2018; IBR approved for
§ 431.134.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
(2) [Reserved]
(b) ASHRAE. American Society of
Heating, Refrigerating and AirConditioning Engineers, Inc., 1791
Tullie Circle NE, Atlanta, GA 30329;
(404) 636–8400; ashrae@ashrae.org;
www.ashrae.org.
(1) ANSI/ASHRAE Standard 29–2015,
Method of Testing Automatic Ice
Makers, approved April 30, 2015; IBR
approved for § 431.134.
(2) [Reserved]
■ 7. Revise § 431.134 to read as follows:
§ 431.134 Uniform test methods for the
measurement of harvest rate, energy
consumption, and water consumption of
automatic commercial ice makers.
Note 1 to § 431.134. On or after October 27,
2023, any representations, including
certifications of compliance for automatic
commercial ice makers, made with respect to
the energy use or efficiency of automatic
commercial ice makers must be made in
accordance with the results of testing
pursuant to this section. Prior to October 27,
2023, any representations with respect to
energy use or efficiency of automatic
commercial ice makers must be made either
in accordance with the results of testing
pursuant to this section or with the results
of testing pursuant to this section as it
appeared in 10 CFR 431.134 in the 10 CFR
parts 200–499 edition revised as of January
1, 2022.
(a) Scope. This section provides the
test procedures for measuring the
harvest rate in pounds of ice per 24
hours (lb/24 h), energy use in kilowatt
hours per 100 pounds of ice (kWh/100
lb), and the condenser water use in
gallons per 100 pounds of ice (gal/100
lb) of automatic commercial ice makers
with capacities up to 4,000 lb/24 h. This
section also provides voluntary test
procedures for measuring the potable
water use in gallons per 100 pounds of
ice (gal/100 lb).
(b) Testing and calculations. Measure
the harvest rate, the energy use, the
condenser water use, and, to the extent
elected, the potable water use of each
covered automatic commercial ice
maker by conducting the test procedures
set forth in AHRI Standard 810 (I–P)–
2016 with Addendum 1, section 3,
‘‘Definitions,’’ section 4, ‘‘Test
Requirements,’’ and section 5.2,
‘‘Standard Ratings’’ (incorporated by
reference, see § 431.133), and according
to the provisions of this section. Use
ANSI/ASHRAE Standard 29–2015
(incorporated by reference, see
§ 431.133) referenced by AHRI Standard
810 (I–P)–2016 with Addendum 1 for all
automatic commercial ice makers,
except as noted in paragraphs (c)
through (k) of this section. If any
provision of the referenced test
procedures conflicts with the
PO 00000
Frm 00046
Fmt 4701
Sfmt 4700
requirements in this section or the
definitions in § 431.132, the
requirements in this section and the
definitions in § 431.132 control.
(c) Test setup and equipment
configurations — (1) Baffles. Conduct
testing without baffles unless the baffle
either is a part of the automatic
commercial ice maker or shipped with
the automatic commercial ice maker to
be installed according to the
manufacturer’s installation instructions.
(2) Clearances. Install all automatic
commercial ice makers for testing
according to the manufacturer’s
specified minimum rear clearance
requirements, or with 3 feet of clearance
from the rear of the automatic
commercial ice maker, whichever is
less, from the chamber wall. All other
sides of the automatic commercial ice
maker and all sides of the remote
condenser, if applicable, shall have
clearances according to section 6.5 of
ANSI/ASHRAE Standard 29–2015.
(3) Purge settings. Test automatic
commercial ice makers equipped with
automatic purge water control using a
fixed purge water setting that is
described in the manufacturer’s written
instructions shipped with the unit as
being appropriate for water of normal,
typical, or average hardness. Purge
water settings described in the
instructions as suitable for use only
with water that has higher or lower than
normal hardness (such as distilled water
or reverse osmosis water) must not be
used for testing.
(4) Ambient conditions
measurement—(i) Ambient temperature
sensors. Measure all ambient
temperatures according to section 6.4 of
ANSI/ASHRAE Standard 29–2015,
except as provided in paragraph
(c)(4)(iv) of this section, with
unweighted temperature sensors.
(ii) Ambient relative humidity
measurement. Except as provided in
paragraph (c)(4)(iv) of this section,
ambient relative humidity shall be
measured at the same location(s) used to
confirm ambient dry bulb temperature,
or as close as the test setup permits.
Ambient relative humidity shall be
measured with an instrument accuracy
of ±2.0 percent.
(iii) Ambient conditions sensors
shielding. Ambient temperature and
relative humidity sensors may be
shielded if the ambient test conditions
cannot be maintained within the
specified tolerances because of warm
discharge air from the condenser
exhaust affecting the ambient
measurements. If shields are used, the
shields must not inhibit recirculation of
the warm discharge air into the
E:\FR\FM\01NOR2.SGM
01NOR2
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
sides of the cabinet, for any side of the
automatic commercial ice maker cabinet
with no warm air discharge or air inlet.
(5) Collection container for batch type
automatic commercial ice makers with
harvest rates less than or equal to 50 lb/
24 h. Use an ice collection container as
specified in section 5.5.2(a) of ANSI/
ASHRAE Standard 29–2015, except that
the water retention weight of the
container is no more than 4.0 percent of
that of the smallest batch of ice for
which the container is used.
(d) Test conditions—(1) Relative
humidity. Maintain an average
minimum ambient relative humidity of
30.0 percent throughout testing.
lotter on DSK11XQN23PROD with RULES2
Perent Difference
(2) Automatic commercial ice makers
with harvest rates greater than 50lb/24
h. The three or more consecutive cycles
or samples used to calculate harvest
rate, energy use, condenser water use,
and potable water use, must meet the
stability criteria in section 7.1.1 of
ANSI/ASHRAE Standard 29–2015.
(3) Automatic commercial ice makers
with harvest rates less than or equal to
50 lb/24 h. The three or more
consecutive cycles or samples used to
calculate harvest rate, energy use,
condenser water use, and potable water
use, must meet the stability criteria in
section 7.1.1 of ANSI/ASHRAE
Standard 29–2015, except that the
weights of the samples (for continuous
type automatic commercial ice makers
(ACIMs)) or 24-hour calculated ice
production (for batch type ACIMs) must
not vary by more than ±4 percent, and
the 25 g (for continuous type ACIMs)
and 1 kg (for batch type ACIMs) criteria
do not apply.
(f) Calculations. The harvest rate,
energy use, condenser water use, and
potable water use must be calculated by
averaging the values for the three
calculated samples for each respective
reported metric as specified in section 9
of ANSI/ASHRAE Standard 29–2015.
All intermediate calculations prior to
the reported value, as applicable, must
be performed with unrounded values.
(g) Rounding. Round the reported
values as follows: Harvest rate to the
nearest 1 lb/24 h for harvest rates above
50 lb/24 h; harvest rate to the nearest 0.1
lb/24 h for harvest rates less than or
equal to 50 lb/24 h; condenser water use
to the nearest 1 gal/100 lb; and energy
use to the nearest 0.01 kWh/100 lb.
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
=
IA-Bl
A+ B x100percent
-z-
Round final potable water use value to
the nearest 0.1 gal/100 lb.
(h) Continuous type automatic
commercial ice makers—(1) Ice
hardness adjustment—(i) Calorimeter
constant. Determine the calorimeter
constant according to the requirements
in section A1 and A2 of Normative
Annex A Method of Calorimetry in
ANSI/ASHRAE Standard 29–2015,
except that the trials shall be conducted
at an ambient air temperature (room
temperature) of 70 °F ± 1 °F, with an
initial water temperature of 90 °F ± 1 °F.
To verify the temperature of the block
of pure ice as provided in section A2.e
in ANSI/ASHRAE Standard 29–2015, a
thermocouple shall be embedded at
approximately the geometric center of
the interior of the block. Any water that
remains on the block of ice shall be
wiped off the surface of the block before
being placed into the calorimeter.
(ii) Ice hardness factor. Determine the
ice hardness factor according to the
requirements in section A1 and A3 of
Normative Annex A Method of
Calorimetry in ANSI/ASHRAE Standard
29–2015, except that the trials shall be
conducted at an ambient air temperature
(room temperature) of 70 °F ± 1 °F, with
an initial water temperature of 90 °F ±
1 °F. The harvested ice used to
determine the ice hardness factor shall
be produced according to the test
methods specified at § 431.134. The ice
hardness factor shall be calculated using
the equation for ice hardness factor in
section 5.2.2 of AHRI Standard 810 (I–
P)–2016 with Addendum 1.
(iii) Ice hardness adjustment
calculation. Determine the reported
energy use and reported condenser
water use by multiplying the measured
PO 00000
Frm 00047
Fmt 4701
(2) Inlet water pressure. Except for
portable automatic commercial ice
makers, the inlet water pressure when
water is flowing into the automatic
commercial ice maker shall be within
the allowable range within 5 seconds of
opening the water supply valve.
(e) Stabilization—(1) Percent
difference calculation. Calculate the
percent difference in the ice production
rate between two cycles or samples
using the following equation, where A
and B are the harvest rates, in lb/24 h
(for batch type ice makers) or lb/15 mins
(for continuous type ice makers), of any
cycles or samples used to determine
stability:
Sfmt 4700
energy use or measured condenser water
use by the ice hardness adjustment
factor, determined using the ice
hardness adjustment factor equation in
section 5.2.2 of AHRI Standard 810 (I–
P)–2016 with Addendum 1.
(2) [Reserved]
(i) Automatic commercial ice makers
with automatic dispensers. Allow for
the continuous production and
dispensing of ice throughout testing. If
an automatic commercial ice maker
with an automatic dispenser is not able
to continuously produce and dispense
ice because of certain mechanisms
within the automatic commercial ice
maker that prohibit the continuous
production and dispensing of ice
throughout testing, those mechanisms
must be overridden to the minimum
extent which allows for the continuous
production and dispensing of ice. The
automatic commercial ice maker shall
have an empty internal storage bin at
the beginning of the test period. Collect
capacity samples according to the
requirements of ANSI/ASHRAE
Standard 29–2015, except that the
samples shall be collected through
continuous use of the dispenser rather
than in the internal storage bin. The
intercepted ice samples shall be
obtained from a container in an external
ice bin that is filled one-half full of ice
and is connected to the outlet of the ice
dispenser through the minimal length of
conduit that can be used.
(j) Portable automatic commercial ice
makers. Sections 5.4, 5.6, 6.2, and 6.3 of
ANSI/ASHRAE Standard 29–2015 do
not apply. Ensure that the ice storage
bin is empty prior to the initial potable
water reservoir fill. Fill an external
container with water to be supplied to
E:\FR\FM\01NOR2.SGM
01NOR2
ER01NO22.003
condenser or automatic commercial ice
maker inlet.
(iv) Alternate ambient conditions
measurement location. For automatic
commercial ice makers in which warm
air discharge from the condenser
exhaust affects the ambient conditions
as measured 1 foot in front of the air
inlet, or automatic commercial ice
makers in which the air inlet is located
in the rear of the automatic commercial
ice maker and the manufacturer’s
specified minimum rear clearance is
less than or equal to 1 foot, the ambient
temperature and relative humidity may
instead be measured 1 foot from the
cabinet, centered with respect to the
65901
65902
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 / Rules and Regulations
lotter on DSK11XQN23PROD with RULES2
the portable automatic commercial ice
maker water reservoir. Establish an
initial water temperature of 70 °F ±
1.0 °F. Verify the initial water
temperature by inserting a temperature
sensor into approximately the geometric
center of the water in the external
container. Immediately after
establishing the initial water
temperature, fill the ice maker water
reservoir to the maximum level of
potable water as specified by the
manufacturer. After the potable water
reservoir is filled, operate the portable
automatic commercial ice maker to
produce ice into the ice storage bin until
the bin is one-half full. One-half full for
VerDate Sep<11>2014
18:03 Oct 31, 2022
Jkt 259001
the purposes of testing portable
automatic commercial ice makers means
that half of the vertical dimension of the
ice storage bin, based on the maximum
ice fill level within the ice storage bin,
is filled with ice. Once the ice storage
bin is one-half full, conduct testing
according to section 7 of ANSI/ASHRAE
Standard 29–2015. The potable water
use is equal to the sum of the weight of
ice and any corresponding melt water
collected for the capacity test as
specified in section 7.2 of ANSI/
ASHRAE Standard 29–2015.
(k) Self-contained refrigerated storage
automatic commercial ice makers. For
door openings, the door shall be in the
PO 00000
Frm 00048
Fmt 4701
Sfmt 9990
fully open position, which means
opening the ice storage compartment
door to an angle of not less than 75
degrees from the closed position (or the
maximum extent possible, if that is less
than 75 degrees), for 10.0 ± 1.0 seconds
to collect the sample. Conduct door
openings only for ice sample collection
and returning the empty ice collection
container to the ice storage
compartment (i.e., conduct two separate
door openings, one for removing the
collection container to collect the ice
and one for replacing the collection
container after collecting the ice).
[FR Doc. 2022–22927 Filed 10–31–22; 8:45 am]
BILLING CODE 6450–01–P
E:\FR\FM\01NOR2.SGM
01NOR2
Agencies
[Federal Register Volume 87, Number 210 (Tuesday, November 1, 2022)]
[Rules and Regulations]
[Pages 65856-65902]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2022-22927]
[[Page 65855]]
Vol. 87
Tuesday,
No. 210
November 1, 2022
Part II
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Automatic Commercial
Ice Makers; Final Rule
Federal Register / Vol. 87, No. 210 / Tuesday, November 1, 2022 /
Rules and Regulations
[[Page 65856]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE-2017-BT-TP-0006]
RIN 1904-AD81
Energy Conservation Program: Test Procedure for Automatic
Commercial Ice Makers
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Final rule.
-----------------------------------------------------------------------
SUMMARY: In this final rule, the U.S. Department of Energy (``DOE'')
amends the test procedure for automatic commercial ice makers to update
incorporated references to the latest version of the industry
standards; establish a relative humidity test condition; provide
additional detail regarding certain test conditions, settings, setup
requirements, and calculations; include a voluntary measurement of
potable water use; clarify certification and reporting requirements;
and add enforcement provisions. This final rule also provides
additional detail to the DOE test procedure to improve the
representativeness and repeatability of the current test procedure.
DATES: The effective date of this rule is December 1, 2022. The final
rule changes will be mandatory for equipment testing starting October
27, 2023. The incorporation by reference of certain publications listed
in the rule is approved by the Director of the Federal Register on
December 1, 2022.
ADDRESSES: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts, comments, and other supporting
documents/materials, is available for review at www.regulations.gov.
All documents in the docket are listed in the www.regulations.gov
index. However, not all documents listed in the index may be publicly
available, such as those containing information that is exempt from
public disclosure.
A link to the docket web page can be found at www.regulations.gov/docket/EERE-2017-BT-TP-0006. The docket web page contains instructions
on how to access all documents, including public comments, in the
docket.
For further information on how to review the docket contact the
Appliance and Equipment Standards Program staff at (202) 287-1445 or by
email: [email protected].
FOR FURTHER INFORMATION CONTACT:
Ms. Julia Hegarty, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, EE-2J,
1000 Independence Avenue SW, Washington, DC 20585-0121. Telephone:
(202) 586-0729. Email: [email protected].
Ms. Sarah Butler, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC 20585-0121.
Telephone: (202) 586-1777. Email: [email protected].
SUPPLEMENTARY INFORMATION: DOE incorporates by reference the following
industry standards into part 431:
AHRI Standard 810 (I-P)-2016 with Addendum 1, ``Performance Rating
of Automatic Commercial Ice-Makers,'' January 2018; and
ANSI/ASHRAE Standard 29-2015, ``Method of Testing Automatic Ice
Makers,'' approved April 30, 2015.
AHRI standards can be obtained from the Air-Conditioning, Heating,
and Refrigeration Institute (AHRI), 2111 Wilson Blvd., Suite 500,
Arlington, VA 22201, 703-524-8800, [email protected], or
www.ahrinet.org.
ASHRAE standards can be purchased from the American Society of
Heating, Refrigerating and Air-Conditioning Engineers, Inc. (ASHRAE),
1791 Tullie Circle NE, Atlanta, GA 30329, (404) 636-8400,
[email protected], or www.ashrae.org. (Co-published with American
National Standards Institute (ANSI).)
For a further discussion of these standards, see section IV.N of
this document.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Final Rule
III. Discussion
A. Scope
B. Definitions
1. Refrigerated Storage ACIM
2. Portable ACIM
3. Industry Standard Definitions
C. Industry Test Standards Incorporated by Reference
D. Additional Amendments
1. Low-Capacity ACIMs
2. Stability Criteria
3. Test Conditions
4. Test Setup and Equipment Configurations
5. Modulating Capacity Ice Makers
6. Standby Energy Use and Energy Use Associated With Ice Storage
7. Calculations and Rounding Requirements
8. Potable Water Use
E. Representations of Energy Use and Energy Efficiency
1. Sampling Plan and Determination of Represented Values
2. Test Sample Value Rounding Requirements
3. Enforcement Provisions
F. Test Procedure Costs and Harmonization
1. Test Procedure Costs and Impact
2. Harmonization With Industry Standards
G. Effective and Compliance Dates
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866 and 13563
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Congressional Notification
N. Description of Materials Incorporated by Reference
V. Approval of the Office of the Secretary
I. Authority and Background
Automatic commercial ice makers (``ACIMs'' or ``ice makers'') are
included in the list of ``covered equipment'' for which the U.S.
Department of Energy (``DOE'') is authorized to establish and amend
energy conservation standards and test procedures. (42 U.S.C.
6311(1)(F)) DOE's energy conservation standards and test procedures for
ACIMs are currently prescribed at 10 CFR 431.136 and 431.134,
respectively. The following sections discuss DOE's authority to
establish test procedures for ACIMs and relevant background information
regarding DOE's consideration of test procedures for this equipment.
A. Authority
The Energy Policy and Conservation Act, as amended (``EPCA''),\1\
authorizes DOE to regulate the energy efficiency of a number of
consumer products and certain industrial equipment. (42 U.S.C. 6291-
6317) Title III, Part C \2\ of EPCA established the Energy Conservation
Program for Certain Industrial Equipment, which sets forth a variety of
provisions designed to improve energy
[[Page 65857]]
efficiency. This equipment includes ACIMs, the subject of this
document. (42 U.S.C. 6311(1)(F))
---------------------------------------------------------------------------
\1\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020), which reflect the last statutory amendments that impact
Parts A and A-1 of EPCA.
\2\ For editorial reasons, upon codification in the U.S. Code,
Part C was redesignated Part A-1.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. Relevant
provisions of EPCA specifically include definitions (42 U.S.C. 6311),
test procedures (42 U.S.C. 6314), labeling provisions (42 U.S.C. 6315),
energy conservation standards (42 U.S.C. 6313), and the authority to
require information and reports from manufacturers (42 U.S.C. 6316; 42
U.S.C. 6296).
The Federal testing requirements consist of test procedures that
manufacturers of covered equipment must use as the basis for: (1)
certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted pursuant to EPCA (42 U.S.C.
6316(a); 42 U.S.C. 6295(s)), and (2) making other representations about
the efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE
must use these test procedures to determine whether the equipment
complies with relevant standards promulgated under EPCA. (42 U.S.C.
6316(a); 42 U.S.C. 6295(s))
Federal energy efficiency requirements for covered equipment
established under EPCA generally supersede State laws and regulations
concerning energy conservation testing, labeling, and standards. (42
U.S.C. 6316(a) and 42 U.S.C. 6316(b); 42 U.S.C. 6297) DOE may, however,
grant waivers of Federal preemption for particular State laws or
regulations, in accordance with the procedures and other provisions of
EPCA. (42 U.S.C. 6316(b)(2)(D))
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered equipment. EPCA requires that any test procedures prescribed or
amended under this section must be reasonably designed to produce test
results which reflect energy efficiency, energy use, or estimated
annual operating cost of a given type of covered equipment during a
representative average use cycle (as determined by the Secretary) and
requires that test procedures not be unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
EPCA prescribed the first Federal test procedure for ACIMs,
directing that the ACIM test procedure shall be the AHRI Standard 810-
2003, ``Performance Rating of Automatic Commercial Ice-Makers'' (``AHRI
Standard 810-2003''). (42 U.S.C. 6314(a)(7)(A)) EPCA requires if AHRI
Standard 810-2003 is amended, that DOE must amend the Federal test
procedures as necessary to be consistent with the amended AHRI
standard, unless DOE determines, by rule, published in the Federal
Register and supported by clear and convincing evidence, that to do so
would not meet the requirements for test procedures to be
representative of actual energy efficiency and to not be unduly
burdensome to conduct. (42 U.S.C. 6314(a)(7)(B)(i))
EPCA also requires that, at least once every 7 years, DOE evaluate
test procedures for each type of covered equipment, including ACIMs, to
determine whether amended test procedures would more accurately or
fully comply with the requirements for the test procedures to not be
unduly burdensome to conduct and be reasonably designed to produce test
results that reflect energy efficiency, energy use, and estimated
operating costs during a representative average use cycle. (42 U.S.C.
6314(a)(1))
If the Secretary determines, on her own behalf or in response to a
petition by any interested person, that a test procedure should be
prescribed or amended, the Secretary shall promptly publish in the
Federal Register proposed test procedures and afford interested persons
an opportunity to present oral and written data, views, and arguments
with respect to such procedures. The comment period on a proposed rule
to amend a test procedure shall be at least 60 days and may not exceed
270 days. In prescribing or amending a test procedure, the Secretary
shall take into account such information as the Secretary determines
relevant to such procedure, including technological developments
relating to energy use or energy efficiency of the type (or class) of
covered products involved. (42 U.S.C. 6293(b)(2)) If DOE determines
that test procedure revisions are not appropriate, DOE must publish its
determination not to amend the test procedures.
DOE is publishing this final rule in satisfaction of the 7-year
review requirement specified in EPCA. (42 U.S.C. 6314(b)(1))
B. Background
DOE's existing test procedures for ACIMs appear at title 10 of the
Code of Federal Regulations (``CFR''), part 431, Sec. 431.134.
On March 19, 2019, DOE published a request for information
(``RFI'') to solicit comment and information to inform DOE's
determination of whether to propose amendments to the current ACIM test
procedure. 84 FR 9979 (``March 2019 RFI''). Following the RFI and in
consideration of the comments received, DOE published a notice of
proposed rulemaking (``NOPR'') on December 21, 2021, to seek feedback
on initial proposals. 86 FR 72322 (``December 2021 NOPR''). In the
December 2021 NOPR, DOE proposed the following amendments to the test
procedure:
(1) Updating the referenced methods of test to AHRI Standard 810
(I-P)-2016 with Addendum 1 and ASHRAE Standard 29-2015, except for the
provisions as discussed;
(2) Including definitions and test requirements for low-capacity
ACIMs;
(3) Incorporating changes to improve test procedure
representativeness, accuracy, and precision, which include: clarifying
calorimeter constant test instructions; specifying ambient temperature
measurement requirements; establishing a relative humidity test
condition; establishing an allowable range of water hardness;
clarifying the stability requirements that were updated in ASHRAE
Standard 29-2015; clarifying water pressure requirements; and
increasing the tolerance on capacity collection time;
(4) Specifying certain test settings, conditions, and
installations, including: clarifying ice hardness test conditions;
clarifying baffle use for testing; amending clearance requirements;
clarifying automatic purge control settings; and providing instructions
for testing ACIMs with automatic dispensers;
(5) Including voluntary provisions for measuring potable water use;
(6) Including clarifying language for calculations, rounding
requirements, sampling plan calculations, and certification
instructions; and
(7) Adding language to the equipment-specific enforcement
provisions.
DOE received comments in response to the December 2021 NOPR from
the interested parties listed in Table I.1.
[[Page 65858]]
Table I.1--List of Commenters With Written Submissions in Response to the December 2021 NOPR
----------------------------------------------------------------------------------------------------------------
Reference in this final Comment No. in
Commenter(s) rule the docket Commenter type
----------------------------------------------------------------------------------------------------------------
Air-Conditioning, Heating, and AHRI...................... 13 Trade Association.
Refrigeration Institute.
Appliance Standards Awareness Project; ASAP, ACEEE, NRDC (Joint 15 Efficiency Advocacy
American Council for an Energy- Commenters). Organizations.
Efficient Economy; Natural Resources
Defense Council.
Hoshizaki America, Inc.................. Hoshizaki................. 14 Manufacturer.
Mile High Equipment Co. DBA Ice-O-Matic. Ice-O-Matic (IOM)......... 11 Manufacturer.
Pacific Gas and Electric Company; San CA IOUs................... 16 Utilities.
Diego Gas and Electric; and Southern
California Edison; collectively, the
California Investor-Owned Utilities.
Association of Home Appliance AHAM...................... \3\18 Trade Association.
Manufacturers.
----------------------------------------------------------------------------------------------------------------
A parenthetical reference at the end of a comment quotation or
paraphrase provides the location of the item in the public record.\4\
---------------------------------------------------------------------------
\3\ DOE received AHAM's late comment on September 1, 2022, which
was past the comment deadline of February 22, 2022. Although this
comment was received 191 days after the close of the comment period,
DOE has included the comment and responses in this final rule. AHAM
indicated it did not file timely comments on the proposed test
procedure because AHAM was not aware that the proposed test
procedure included AHAM products in its scope. DOE has determined
that AHAM's comments may provide a unique stakeholder perspective
not included in other comments received during this rulemaking, and
therefore DOE has considered them in this final rule despite the
late submission.
\4\ The parenthetical reference provides a reference for
information located in the docket of DOE's rulemaking to develop
test procedures for ACIMs. (Docket No. EERE-2017-BT-TP-0006, which
is maintained at www.regulations.gov) The references are arranged as
follows: (commenter name, comment docket ID number, page of that
document).
---------------------------------------------------------------------------
II. Synopsis of the Final Rule
In this final rule, DOE amends the representation provisions,
product-specific enforcement provisions, and test procedure for ACIMs
as follows:
(1) Updating the referenced methods of test to AHRI Standard 810
(I-P)-2016 with Addendum 1 and ASHRAE Standard 29-2015, except for the
provisions as discussed;
(2) Including definitions and test requirements for low-capacity
ACIMs;
(3) Incorporating changes to improve test procedure
representativeness, accuracy, and precision, which include: clarifying
calorimeter constant test instructions; specifying ambient temperature
measurement requirements; establishing a relative humidity test
condition; clarifying the stability requirements that were updated in
ASHRAE Standard 29-2015; and clarifying water pressure requirements;
(4) Specifying certain test settings, conditions, and
installations, including: clarifying ice hardness test conditions;
clarifying baffle use for testing; amending clearance requirements;
clarifying automatic purge control settings; and providing instructions
for testing ACIMs with automatic dispensers;
(5) Including voluntary provisions for measuring potable water use;
(6) Including clarifying language for calculations, rounding
requirements, sampling plan calculations, and certification
instructions; and
(7) Adding language to the equipment-specific enforcement
provisions.
The adopted amendments are summarized in Table II.1 compared to the
test procedure provisions prior to the amendment, as well as the reason
for the adopted change.
Table II.1--Summary of Changes Established in This Final Rule
------------------------------------------------------------------------
Current DOE approach Amended approach Attribution
------------------------------------------------------------------------
References industry standard Updates reference Adopts latest
AHRI Standard 810-2007 with to industry industry
Addendum 1 ``2007 Standard for standard AHRI standards.
Performance Rating of Automatic Standard 810 (I-
Commercial Ice Makers'' (``AHRI P)-2016 with
Standard 810-2007''), which Addendum 1, which
refers to ANSI/ASHRAE Standard refers to ASHRAE
29-2009 ``Method of Testing Standard 29-2015.
Automatic Ice Makers,''
(including Errata Sheets issued
April 8, 2010 and April 21,
2010), approved January 28,
2009 (``ASHRAE Standard 29-
2009'').
Scope includes ACIMs with Includes Ensures
capacities between 50 and 4,000 definitions for representative,
lb/24 h. low-capacity repeatable, and
ACIMs and expands reproducible
test procedure measures of
scope to include performance for
low-capacity ACIMs currently
ACIMs with not in scope.
capacity less
than or equal to
50 lb/24 h;
includes
additional
instructions to
allow for testing
low-capacity
ACIMs.
Does not specify the ambient & Specifies that the Harmonizes with
water temperature and water harvested ice industry
pressure when harvesting ice to used to determine standard;
be used in determining the ice the ice hardness improves
hardness factor. factor must be representativenes
produced at the s, repeatability,
Standard Rating and
Conditions reproducibility.
presented in
section 5.1.2 of
AHRI Standard 810
(I-P)-2016 with
Addendum 1.
Does not specify where to Specifies that the Improves
measure the temperature of the temperature representativenes
ice block used to determine the measurement s, repeatability,
calorimeter constant. location must be and
at approximately reproducibility.
the geometric
center of the
block of ice and
that any liquid
water on the
block of ice must
be wiped off the
surface prior to
placement in the
calorimeter.
[[Page 65859]]
Capacity measurements begin All cycles or Clarifies industry
after the unit has been samples used for test procedure
stabilized. the capacity test (``TP'') to
must meet the reduce test
stability burden while
criteria. maintaining
representative
results;
harmonize with
industry
standard.
Continuous ACIMs shall be Continuous ACIMs Harmonizes with
considered stabilized when the shall be industry TP
weights of three consecutive considered update.
14.4-minute samples taken stabilized when
within a 1.5-hour period do not the weights of
vary by more than 2 two consecutive
percent. 15.0 min 2.5 s
samples having no
more than 5
minutes between
the end of a
sample and the
start of the next
sample do not
vary more than
2
percent or 0.055
pounds, whichever
is greater.
Does not specify relative Adds an average Improves
humidity test condition. minimum relative representativenes
humidity test s, repeatability,
condition of 30.0 and
percent. reproducibility.
Use of baffles and purge setting Incorporates Improves
addressed in guidance.. existing guidance representativenes
into the test s, repeatability,
procedure; allows and
for an alternate reproducibility.
ambient
measurement
location instead
of shielding the
thermocouple and
for rear
clearances which
are less than the
required inlet
measurement
distance.
ACIMs shall be tested with a ACIMs shall be Improves
clearance of 18 inches on all tested according representativenes
four sides. to the s, repeatability,
manufacturer's and
specified minimum reproducibility
rear clearances and updates
requirements, or certain
3 feet from the requirements to
rear of the harmonize with
ACIMs, whichever industry
is less; all standard.
other sides of
the ACIMs and all
sides of the
remote
condensers, if
applicable, shall
be tested with a
minimum clearance
of 3 feet or the
minimum clearance
specified by the
manufacturer,
whichever is
greater.
Does not specify use of weighted/ Specifies that Improves
unweighted sensors to measure unweighted representativenes
ambient temperature. sensors shall be s, repeatability,
used for all and
ambient reproducibility.
temperature
measurements.
Does not specify how to measure Specifies that the Improves
water inlet pressure water pressure representativenes
requirements. shall be measured s, repeatability,
within 8 inches and
of the ACIM and reproducibility.
within the
allowable range
within 5 seconds
of water flowing
into the ACIM.
Does not specify how to collect Provides In response to
capacity samples for ACIMs with instruction to waiver.
dispensers. test certain
ACIMs with an
automatic
dispenser with an
empty internal
bin at the start
of the test and
to allow for the
continuous
production and
dispensing of
ice, with samples
collected from
the dispenser
through a conduit
connected to an
external bin one-
half full of ice.
Does not specifically reference Includes voluntary Harmonizes with
potable water usage. reference to industry
potable water use standard;
in 10 CFR 431.134 improves
based on AHRI representativenes
Standard 810 (I- s, repeatability,
P)-2016 with and
Addendum 1. reproducibility.
Rounds energy use in multiples Rounds energy use Harmonizes with
of 0.1 kWh/100 lb and harvest in multiples of latest industry
rate to the nearest 1 lb/24 h. 0.01 kWh/100 lb; standard;
rounds harvest improves
rate to the representativenes
nearest 0.1 lb/24 s, repeatability,
h for ACIMs with and
harvest rates of reproducibility.
50 lb/24 h or
less.
Does not specify if intermediate Clarifies that the Improves
values used in calculations calculations of representativenes
should be rounded. intermediate s, repeatability,
values be and
performed with reproducibility.
raw measured data
and only the
final results be
rounded;
clarifies that
the energy use,
condenser water
use, and potable
water use (if
voluntarily
measured) be
calculated by
averaging the
calculated values
for the three
measured samples
for each
respective metric.
Does not specify how to Specifies that the Improves
calculate the percent percent representativenes
difference between two difference s, repeatability,
measurements. between two and
measurements be reproducibility.
calculated by
taking the
absolute
difference
between two
measurements and
divide by the
average of the
two measurements.
References ``maximum energy Removes Improves clarity.
use'' and ``maximum condenser ``maximum'' from
water use'' at 10 CFR 429.45, the referenced
no reference to water use in terms; adds
sampling plan. reference to
condenser water
use in sampling
plan.
Defines ``maximum condenser Modifies the term Improves clarity.
water use'' at 10 CFR 431.132. and definition of
``maximum
condenser water
use'' to instead
refer to the term
``condenser water
use''.
Defines ``cube type ice'' at 10 Removes ``cube Improves clarity.
CFR 431.132. type ice'' from
10 CFR 431.132;
removes reference
to cube type ice
in the definition
of ``batch type
ice maker''.
Does not specify how the The represented Improves
represented value of harvest value of harvest representativenes
rate for each basic model rate for the s, repeatability,
should be determined based on basic model is and
the test sample. determined as the reproducibility.
mean of the
harvest rate for
each tested unit.
[[Page 65860]]
Does not specify rounding Specifies that Improves
requirements for represented represented representativenes
values in 10 CFR 429.45. values determined s, repeatability,
in 10 CFR 429.45 and
must be rounded reproducibility.
consistent with
the test
procedure
rounding
instructions,
upon the
compliance date
of any amended
standards.
No equipment-specific The certified Improves clarity.
enforcement provisions. harvest rate will
be considered for
determination of
the energy
consumption and
condenser water
use levels only
if the average
measured harvest
rate is within
five percent of
the certified
harvest rate,
otherwise the
measured harvest
rate will be used
to determine the
applicable
standards.
------------------------------------------------------------------------
DOE has determined that while the amendments will introduce
additional test requirements compared to the current approach, any
impact to the measured efficiency of certified ACIMs is expected to be
de minimis. For low-capacity ACIMs newly added within scope of the test
procedure, testing according to the amended test procedure for purposes
of certifications of compliance will not be required until the
compliance date of any energy conservation standards for that
equipment. However, if a manufacturer chooses to make representations
of the energy efficiency or energy use of a low-capacity ACIM,
beginning 360 days after publication of the final rule in the Federal
Register, the manufacturer will be required to base such
representations on the DOE test procedure. (42 U.S.C. 6314(d)(1)) While
DOE does not expect that manufacturers will incur additional cost as a
result of the amended test procedure, DOE provides a discussion of
testing costs in section III.F.1 of this final rule. DOE has also
determined that the amended test procedure will not be unduly
burdensome to conduct. Discussion of DOE's amendments are addressed in
detail in section III of this final rule.
The effective date for the amended test procedures adopted in this
final rule is 30 days after publication of this document in the Federal
Register. Representations of energy use or energy efficiency must be
based by testing in accordance with the amended test procedures
beginning 360 days after the publication of this final rule.
III. Discussion
In the following sections, DOE describes the amendments to the test
procedures for ACIMs. This reflects DOE's review of the updates to the
referenced industry test procedures, the comments received in response
to the March 2019 RFI and the December 2021 NOPR, and other relevant
information.
A. Scope
DOE defines automatic commercial ice maker as a factory-made
assembly (not necessarily shipped in 1 package) that: (1) consists of a
condensing unit and ice-making section operating as an integrated unit,
with means for making and harvesting ice and (2) may include means for
storing ice, dispensing ice, or storing and dispensing ice. 10 CFR
431.132 (see also, 42 U.S.C. 6311(19)) The current DOE test procedure
for ACIMs applies to both batch type and continuous type ice makers \5\
with harvest rates between 50 and 4,000 lb/24 h. DOE further subdivides
the batch type and continuous type equipment ACIM categories into
several distinct equipment classes based on the equipment
configuration, condenser cooling method, and harvest rate in pounds per
24 hours (lb/24 h), as shown in Table III.1. See also, 10 CFR
431.136(c) and (d). ACIM configurations include ice-making heads,
remote condensing equipment (both with and without a remote
compressor), and self-contained equipment. Ice-making heads and self-
contained equipment can be either air- or water-cooled; however, DOE
prescribes standards only for remote condensing equipment that are air-
cooled. Self-contained ACIMs include a means for storing ice, while
ice-making heads and remote condensing equipment are typically paired
with separate ice storage bins. At 10 CFR 431.132, DOE defines these
configurations, as well as several metrics related to ACIMs.
---------------------------------------------------------------------------
\5\ A batch type ice maker is defined as an ice maker that has
alternate freezing and harvesting periods, including ACIMs that
produce cube type ice and other batch technologies. 10 CFR 431.132.
Batch type ice makers also produce tube type ice and fragmented ice.
A continuous type ice maker is defined as an ice maker that
continually freezes and harvests ice at the same time. Id.
Continuous type ice makers primarily produce flake and nugget ice.
Table III.1--Summary of ACIM Equipment Classes
----------------------------------------------------------------------------------------------------------------
Equipment configuration Condenser cooling fluid Ice-making mechanism Harvest rate (lb/24 h)
----------------------------------------------------------------------------------------------------------------
Ice-Making Head...................... Water.................. Batch.................. <300.
>=300 and <850.
>=850 and <1,500.
>=1,500 and <2,500.
>=2,500 and <4,000.
Continuous............. <801.
>=801 and >2,500.
>=2,500 and >4,000.
Air.................... Batch.................. <300.
>=300 and >800.
>=800 and <1,500.
>=1,500 and <4,000.
Continuous............. <310.
[[Page 65861]]
>=310 and >820.
>=820 and <4,000.
Remote-Condensing (but not remote Air.................... Batch.................. <988.
compressor). >=988 and <4,000.
Continuous............. <800.
>=800 and <4,000.
Remote-Condensing and Remote Air.................... Batch.................. <930.
Compressor. >=930 and <4,000.
Continuous............. <800.
>=800 and <4,000.
Self-Contained....................... Water.................. Batch.................. <200.
>=200 and <2,500.
>=2,500 and <4,000.
Continuous............. <900.
>=900 and <2,500.
>=2,500 and <4,000.
Air.................... Batch.................. <110.
>=110 and <200.
>=200 and <4,000.
Continuous............. <200.
>=200 and <700.
>=700 and <4,000.
----------------------------------------------------------------------------------------------------------------
The regulatory and statutory definitions of ACIM are not limited by
harvest rate (i.e., capacity). (See 10 CFR 431.132 and 42 U.S.C.
6311(19), respectively) However, the scope of DOE's test procedure is
limited explicitly to ACIMs with capacities between 50 and 4,000 lb/24
h. 10 CFR 431.134(a). DOE is aware of ACIMs available in the market
with harvest rates less than or equal to 50 lb/24 h (hereafter referred
to as ``low-capacity ACIMs'').
DOE had previously considered test procedures for low-capacity
ACIMs in a December 16, 2014, NOPR for test procedures for
miscellaneous refrigeration products (``MREFs''). 79 FR 74894
(``December 2014 MREF Test Procedure NOPR'').\6\ In a supplemental
notice of proposed determination regarding miscellaneous refrigeration
products coverage, DOE noted that a working group established to
consider test procedures and standards for miscellaneous refrigeration
products made two observations: (1) ice makers are fundamentally
different from the other product categories considered as miscellaneous
refrigeration products; and (2) ice makers are covered as commercial
equipment and there is no clear differentiation between consumer and
commercial ice makers. 81 FR 11454, 11456 (Mar. 4, 2016). In a 2016
final rule, DOE determined that ice makers were significantly different
from the other product categories considered, and ice makers were not
included in the scope of coverage or test procedure for miscellaneous
refrigeration products. 81 FR 46773 (July 18, 2016).
---------------------------------------------------------------------------
\6\ Available at www.regulations.gov/document?D=EERE-2013-BT-TP-0029-0011.
---------------------------------------------------------------------------
As discussed, EPCA defines ``covered equipment'' to include certain
types of ``industrial equipment,'' including automatic commercial ice
makers. 42 U.S.C. 6311(1). EPCA defines ``industrial equipment'' to
mean equipment, including automatic commercial ice makers, (1) which in
operation consumes, or is designed to consume, energy, (2) which, to
any significant extent, is distributed in commerce for industrial or
commercial use; and (3) which is not a ``covered product'' as defined
in 42 U.S.C. 6291(a)(2), other than a component of a covered product
with respect to which there is in effect a determination under 42
U.S.C. 6312(c); without regard to whether such article is in fact
distributed in commerce for industrial or commercial use. 42 U.S.C.
6311(2).
As discussed, the regulatory and statutory definitions of ACIM are
not limited by harvest rate (see 10 CFR 431.132 and 42 U.S.C. 6311(19),
respectively) and low-capacity ACIMs are not a covered product as
defined in 42 U.S.C. 6291-6292. DOE has determined that low-capacity
ACIMs are, to a significant extent, distributed in commerce for
commercial use. DOE reviewed the low-capacity ACIM market and found
that manufacturers specifically market certain low-capacity ACIMs for
commercial use and/or using commercial air and water ambient rating
conditions (i.e., 90 [deg]F air temperature and 70 [deg]F water
temperature which are the same air and water ambient rating conditions
used in DOE's test procedures for ACIMs currently prescribed at 10 CFR
431.134) \7\ and distributors sell low-capacity ACIMs for commercial
use.\8\ As such, notwithstanding that low-capacity ACIMs may also be
distributed in commerce for personal use or consumption by individuals,
low-capacity ACIMs meet the definition of ``industrial equipment'' and
therefore are covered under the EPCA definition of ``covered
equipment.''
---------------------------------------------------------------------------
\7\ See www.scotsman-ice.com/service/Specs%20Sheets/2017/SIS-SS-CU0415_0117%20LR.pdf, https://www.hoshizaki.com/docs/color-specs/AM-50BAJ-(AD)DS.pdf, https://www.hoshizaki.com/docs/color-specs/IM-50BAA-Q.pdf, https://www.hoshizaki.com/docs/color-specs/C-80BAJ-
(AD)DS.pdf, https://www.manitowocice.com/asset/?id=qsoqru®ions=us&prefLang=en, https://www.scotsman-ice.com/service/Specs%20Sheets/2018/SIS-SS-CU-CU50_0118%20LR.pdf, https://iom-stage.azurewebsites.net/getattachment/b06fdb7c-aaaa-4e5b-b5a6-b091e657a0d3/UCG060A-Spec-Sheet, and https://www.summitappliance.com/catalog/model/BIM44GCSS.
\8\ See www.katom.com/cat/countertop-ice-makers.html?brand=Danby, https://www.katom.com/cat/undercounter-ice-makers.html?suggested_use=Commercial&production_range_lb%2Fday=1%20-%2099%20lbs, https://www.ckitchen.com/313767/ice-machine-with-bin.html?filter=type-of-cooling:air-cooled;4-hr-production:10-50lbs,
https://www.webstaurantstore.com/13283/undercounter-ice-
machines.html?filter=24-hour-ice-yield:38~102-pounds, and
www.staples.com/ice+maker/directory_ice%2520maker.
---------------------------------------------------------------------------
In the December 2014 MREF Test Procedure NOPR, DOE stated it is
aware that manufacturers are using the DOE ACIM test procedure to
represent the energy use of consumer ice makers (i.e.,
[[Page 65862]]
low-capacity ACIMs). 79 FR 74894, 74916. DOE also stated that it is
unaware of any test procedure that has been specifically developed for
consumer ice makers (i.e., low-capacity ACIMs). Id.
In the December 2021 NOPR, DOE proposed a test procedure for low-
capacity ACIMs and requested comment on the proposal to include test
procedure provisions for low-capacity ACIMs within the scope of the
ACIM test procedure. 86 FR 72322,72328.
In response to the December 2021 NOPR, the Joint Commenters
responded that there are many low-capacity models on the market, and
these units currently are not subject to DOE efficiency standards or
test procedures. (Joint Commenters, No. 15, p. 1)
The CA IOUs and the Joint Commenters expressed support for DOE's
proposal to include ACIMs with daily harvest rates below 50 lb/day into
the scope of the test procedure, with the Joint Commenters adding that
this will ensure any manufacturer claims about capacity and efficiency
will be based on standardized test procedures to help purchasers make
informed choices. (CA IOUs, No. 16, p. 1; Joint Commenters, No. 15, p.
1)
The CA IOUs stated that they believe extending the scope of the
test procedure to low-capacity ice makers is a reasonable first step to
a future rulemaking to set minimum energy efficiency standards for
these low-capacity ACIM units. (CA IOUs, No. 16, p. 1)
Hoshizaki and AHRI stated that they do not agree with adding
provisions for low-capacity ACIMs. (Hoshizaki, No. 14, p. 1; AHRI, No.
13, p. 2) AHAM stated that they do not agree with adding provisions for
low-capacity ACIMs to the extent that they include consumer or
residential ice makers. (AHAM, No. 18, p. 2) IOM stated that it
supports the goal of developing an industry standard to allow for the
consistent testing of low-capacity ACIMs.. (IOM, No. 11, p. 1) However,
IOM, AHRI, and Hoshizaki stated that such a standard should be
developed by an industry organization (ASHRAE 29 or AHRI 810) to
determine proper methodology for consistent testing. (IOM, No. 11, p.
1; AHRI, No. 13, p. 2; Hoshizaki, No. 14, p. 1)
AHAM stated that DOE first examined establishing coverage for
consumer stand-alone ice makers as part of the rulemaking to establish
coverage for miscellaneous refrigeration products. (AHAM, No. 18, p. 2)
AHAM noted that, per the recommendation of an Appliance Standards
Rulemaking Advisory Committee (ASRAC) working group and its agreed-upon
term sheet, DOE declined to cover consumer stand-alone ice makers as
part of that rulemaking with the stated reasoning that those products
were too different from the other products over which DOE was proposing
to establish coverage under the miscellaneous refrigeration product
category. Id. AHAM noted that the ASRAC stakeholders never suggested or
determined that the difference between stand-alone small capacity ice
makers and other miscellaneous refrigeration products was that ice
makers were commercial equipment. (AHAM, No. 18, p. 3)
AHAM stated that consumer stand-alone ice makers are not automatic
commercial ice makers. Id. AHAM stated that Congress intended to
include only commercial products under the scope of ``automatic
commercial ice makers'' as demonstrated by the word ``commercial'' and
did not intend to cover residential/consumer products. Id. AHAM stated
that, in EPCA, automatic commercial ice makers are included in 42
U.S.C. Part A-1 for ``Certain Industrial Equipment'', not Part A, which
is for ``Consumer Products other than Automobiles''. Id. AHAM stated
that automatic commercial ice makers fall under the EPCA definition of
``covered equipment'' which means that, as a threshold matter, it is a
type of ``industrial equipment''. Id. AHAM commented that DOE's
guidance states that ``consumer products and industrial equipment are
mutually exclusive categories. An appliance model can only be
considered commercial under the Act if it does not fit the definition
of `consumer product' ''.\9\ (AHAM, No. 18, p. 4) AHAM states that
stand-alone ice makers that are capable of making 50 pounds per day or
less more squarely fit under DOE's definition of a consumer product and
that residential ice makers that fit under the counter or on the
countertop are regularly distributed in commerce for personal use or
consumption by individuals. (AHAM, No. 18, p. 3)
---------------------------------------------------------------------------
\9\ See https://www1.eere.energy.gov/buildings/appliance_standards/pdfs/cce_faq.pdf.
---------------------------------------------------------------------------
AHAM commented that there are several distinguishing design
features or characteristics of stand-alone or under-counter ice makers
with low capacities including: space constraints, ice quality (i.e.,
clear, cubed ice or nugget type ice), countertop designs (portable ice
makers only), lack of connection to the water supply (portable ice
makers only), infrequent and low ice usage, different durability
requirements, different sanitary considerations, lack of requirement
for National Sanitation Foundation (``NSF'') certifications/listings,
different manufacturer warranties, and different safety standards
(i.e., Underwriters' Laboratories (``UL'') 60335-2-89, Particular
Requirements for Commercial Refrigerating Appliances and Ice makers
with an Incorporated or Remote Refrigerant Unit or Motor-Compressor and
UL 60335-2-24, Particular Requirements for Refrigerating Appliances,
Ice-Cream Appliances, and Ice Makers). (AHAM, No. 18, p. 4-6)
Hoshizaki commented that repeatability is key with low-production
models where one cube or chunk could cause the test to be out of
tolerance. (Hoshizaki, No. 14, p. 1) Hoshizaki stated that a very low-
production machine could have 31% stability swings and could prove
impossible to meet the stability threshold in the ASHRAE 29 test. Id.
In the December 2021 NOPR, DOE also requested comment on whether
there are any industry test procedures for testing and rating low-
capacity ACIMs, specifically asking about features specific to low-
capacity ACIMs that might need addressed to produce results
representative of an average use cycle. 86 FR 72322,72328.
Hoshizaki, AHRI, and AHAM commented they are not aware of any test
procedures for low-capacity ice makers. (Hoshizaki, No. 14, p. 1; AHRI,
No. 13, p. 2; AHAM, No. 18, p. 8) AHRI and Hoshizaki added that a study
would be needed to determine a repeatable process to accurately
represent ice capacity and energy use. Id. AHRI recommended DOE bring
this to the ASHRAE Standard Project Committee (``SPC'') 29 for
consideration. (AHRI, No. 13, p. 2)
As stated in the December 2021 NOPR, the energy performance of low-
capacity ACIMs are typically either not specified or based on the
existing ACIM industry test procedures. 86 FR 72322,72328. However, the
lack of a DOE test procedure could allow for manufacturers to make
performance claims using other unknown test procedures, which could
result in inconsistent ratings from model to model. Id.
DOE is still unaware of an industry test procedure for testing and
rating low-capacity ACIMs. Manufacturers continue to use the DOE ACIM
test procedure to represent the energy use of low-capacity ACIMs or do
not specify the energy use. DOE acknowledges the comments regarding
including low-capacity ACIMs within scope of industry test standards
and will consider any updated industry test
[[Page 65863]]
standards, if available, during future ACIM test procedure rulemakings.
DOE discusses stability requirements for low-capacity ACIMs in
section III.D.1 of this final rule.
In response to AHAM's comments regarding low-capacity ACIMs, as
previously stated, EPCA defines ``industrial equipment'' to mean
equipment (1) which in operation consumes, or is designed to consume,
energy, (2) which, to any significant extent, is distributed in
commerce for industrial or commercial use; and (3) which is not a
``covered product'' as defined in 42 U.S.C. 6291(a)(2), other than a
component of a covered product with respect to which there is in effect
a determination under 42 U.S.C. 6312(c); without regard to whether such
article is in fact distributed in commerce for industrial or commercial
use. 42 U.S.C. 6311(2). DOE has determined that low-capacity ACIMs (1)
consume energy; (2) are, to a significant extent, distributed in
commerce for commercial use; and (3) are not covered products. As such,
notwithstanding that low-capacity ACIMs may also be distributed in
commerce for personal use or consumption by individuals, low-capacity
ACIMs meet the definition of ``industrial equipment'' and therefore are
covered under the EPCA definition of ``covered equipment.'' DOE has
determined that establishing a test procedure for low-capacity ACIMs
will allow purchasers to make more informed decisions regarding the
performance of low-capacity ACIMs. DOE is amending the scope of the
ACIM test procedure to include all automatic commercial ice makers with
capacities up to 4,000 lb/24 h (i.e., to include within the scope of
the test procedure, low-capacity ACIMs with a harvest rate less than 50
lb/24 h). Under the amended test procedure, were a manufacturer to
choose to make representations of the energy efficiency or energy use
of a low-capacity ACIM, beginning 360 days after publication of the
final rule in the Federal Register, manufacturers would be required to
base such representations on the DOE test procedure. (42 U.S.C.
6314(d)(1))
B. Definitions
As noted, 10 CFR 431.132 provides definitions concerning ACIMs. DOE
adds new definitions to support test procedure amendments elsewhere in
this document, as discussed in the following paragraphs.
1. Refrigerated Storage ACIM
Typical self-contained ACIMs have an ice storage bin that is
insulated but provides no active refrigeration. As a result, the ice
melts at a certain rate and the ice maker must periodically replenish
the melted ice. Conversely, some self-contained low-capacity ACIMs
feature a refrigerated storage bin that prevents melting of the stored
ice. Because of the additional refrigeration system components, ACIMs
with a refrigerated storage bin (i.e., refrigerated storage ACIMs) have
different energy use characteristics than ACIMs without refrigerated
storage.
In the December 2021 NOPR, DOE proposed to define ``refrigerated
storage automatic commercial ice maker'' as an automatic commercial ice
maker that has a refrigeration system that actively refrigerates the
self-contained storage bin in 10 CFR 431.132 for refrigerated storage
ACIMs. 86 FR 72322, 72328.
In the December 2021 NOPR, DOE requested comment on the proposed
definitions for refrigerated storage automatic commercial ice maker. 86
FR 72322, 72328.
In response to the December 2021 NOPR, Hoshizaki commented that it
is not aware of any standard, self-contained refrigerated storage
commercial ice makers. (Hoshizaki, No. 14, p. 1)
AHRI commented it was unable to categorize this equipment class
with the information provided and would appreciate clarification on
this equipment class and the desired intent behind its potential
inclusion. (AHRI, No. 13, p. 2) Hoshizaki additionally requested
examples of this product, and requested that this be addressed in AHRI
810 and ASHRAE 29 for definition. (Hoshizaki, No. 14, p. 1)
As stated in the December 2021 NOPR, DOE included a definition of
refrigerated storage ACIMs to effectively differentiate refrigerated
storage ACIMs from ACIMs with unrefrigerated storage bins, and to
support the proposed test provisions for refrigerated storage ACIMs. 86
FR 72322, 72328. An example of a refrigerated storage ACIM is the
Whynter UIM-155.\10\ To clarify and provide more information on the
scope of the refrigerated storage ACIM definition, DOE has added
``ice'' to the definition to differentiate refrigerated storage ACIMs
from other refrigeration equipment that is not intended only for ice
storage, so the phrase at the end of the definition reads ``self-
contained ice storage bin''.
---------------------------------------------------------------------------
\10\ See www.whynter.com/product/uim-155/.
---------------------------------------------------------------------------
DOE will consider any updated industry standards, if available,
during future ACIM test procedure rulemakings.
DOE is modifying the definition of refrigerated storage automatic
commercial ice maker in this final rule.
2. Portable ACIM
Some low-capacity ACIMs are ``portable'' and do not require
connection to water supply plumbing to operate. Instead, these units
contain a reservoir that the user manually fills with water prior to
operation and must refill when it becomes empty. In the December 2014
MREF Test Procedure NOPR, DOE proposed to define ``portable ice maker''
as an ice maker that does not require connection to a water supply and
instead has one or more reservoirs that would be manually supplied with
water. 79 FR 74894, 74916. DOE noted that the lack of a fixed water
connection and the small size of these units contribute to their
portability. Id. DOE did not receive comments on the proposed
definition for portable ice makers in response to the December 2014
MREF Test Procedure NOPR.
In the December 2021 NOPR, DOE proposed a definition for a portable
ice maker as proposed in the December 2014 MREF Test Procedure NOPR,
but with additional specification that ACIMs with an optional
connection to a water supply line would not be considered portable
ACIMs (i.e., a unit would be considered portable if the water supplied
to the unit is only via one or more reservoirs). 86 FR 72322, 72328.
DOE proposed to define ``portable automatic commercial ice maker'' as
an automatic commercial ice maker that does not have a means to connect
to a water supply line and has one or more reservoirs that are manually
supplied with water in 10 CFR 431.132. Id.
In the December 2021 NOPR, DOE requested comment on the proposed
definition for portable automatic commercial ice maker. Id.
In response to the December 2021 NOPR, AHRI commented that the
proposed definitions seemed reasonable. (AHRI, No. 13, p. 2-3) However,
Hoshizaki and AHRI requested that DOE work with AHRI and ASHRAE to add
this definition in both AHRI 810 and ASHRAE 29. (Hoshizaki, No. 14, p.
1-2; AHRI, No. 13, p. 2-3)
AHAM stated that portable ice makers are designed to fit on the
countertop and rely on a reservoir instead of being plumbed into the
water supply. (AHAM, No. 18, p.4)
The CA IOUs commented on two types of portable ACIMs: portable
drawer ice machines and portable bin ice machines. (CA IOUs, No. 16, p.
3)
[[Page 65864]]
The CA IOUs commented that portable drawer ice machines are designed
without a door, and the ice drops directly from the evaporator into a
drawer. Id. The CA IOUs stated that in this design, the user does not
have to open a door to access the drawer. Id. The CA IOUs commented
that portable bin ice machines are similar to traditional self-
contained machines where the evaporator is in the bin itself; however,
the evaporator uses a pipe trickle design to create semi-hollow or
gourmet ice. Id. The CA IOUs noted that water can be filled directly
into the evaporator in the portable bin ice machines, but both portable
drawer and portable bin low-capacity ice machine designs can reuse ice-
melt water to feed the evaporator. Id.
DOE notes that the proposed definition of portable automatic
commercial ice maker does not distinguish between portable ACIMs with
and without doors. DOE has also not identified any need to
differentiate between these portable ACIM configurations for the
purposes of testing. Therefore, all portable ACIMs would be included
under this definition and any further categorization of portable ACIM
equipment classes could be investigated in any energy conservation
standards rulemaking for portable ACIMs.
DOE is maintaining the definition of portable automatic commercial
ice maker in this final rule, consistent with the December 2021 NOPR.
3. Industry Standard Definitions
In addition to the definitions specified at 10 CFR 431.132, the
current DOE test procedure at 10 CFR 431.134 references section 3,
``Definitions'' of AHRI Standard 810-2007, which includes many of the
same terms DOE defines at 10 CFR 431.132 and 31.134. In the December
2021 NOPR, to avoid potential confusion regarding multiple definitions
of similar terms, DOE proposed to clarify in 10 CFR 431.134 that where
definitions in AHRI Standard 810 conflict with those in DOE's
regulations, the DOE definitions take precedence. 86 FR 72322, 72328-
72329.
AHRI Standard 810 (I-P)-2016 with Addendum 1 updated its definition
of ``Energy Consumption Rate'' to require expressing the rate in
multiples of 0.01 kWh/100 lb of ice. To maintain consistency with the
industry standard, DOE proposed to incorporate this same rounding
requirement in its definition of ``Energy use'' at 10 CFR 431.132
instead of the current requirement of multiples of 0.1 kWh/100 lb of
ice. 86 FR 72322, 72328.
AHRI Standard 810 (I-P)-2016 with Addendum 1 also deleted its
definition of ``Cubes Type Ice Maker'' and replaced it with a
definition of ``Batch Type Ice-Maker.'' 86 FR 72322, 72328. To be
consistent with this industry update, DOE proposed to remove the
reference to cubes type ice maker in the definition of ``batch type ice
maker'' in 10 CFR 431.132. Id. DOE also proposed to remove ``cube type
ice'' from the list of DOE definitions at 10 CFR 431.132, consistent
with the industry standard update. 86 FR 72322, 72329.
In the December 2021 NOPR, DOE requested comment on its proposal to
amend 10 CFR 431.132 to revise the previously described definitions,
consistent with updates to AHRI Standard 810 (I-P)-2016 with Addendum
1, additionally requesting feedback on the proposed clarification that
the DOE definitions take precedence over any conflicting industry
standard definitions. 86 FR 72322, 72329.
Hoshizaki agreed with this proposal, but requested that AHRI 810,
ASHRAE 29, and 10 CFR 431.132 definitions be consistent. (Hoshizaki,
No. 14, p. 2)
AHRI commented that the proposed definitions seemed reasonable, but
stated that this should go to ASHRAE SPC 29 and AHRI standard 810 for
consideration and inclusion. (AHRI, No. 13, p. 2-3)
DOE is amending 10 CFR 431.132 to revise the previously described
definitions in this final rule. These updates are consistent with
updates in the current industry standard AHRI Standard 810 (I-P)-2016
with Addendum 1. DOE is also maintaining in this final rule the
clarification that the DOE definitions take precedence over any
conflicting industry standard definitions, consistent with the December
2021 NOPR.
The following section discusses additional updates included in the
latest versions of the industry standards.
C. Industry Test Standards Incorporated by Reference
The existing DOE ACIM test procedure incorporates by reference AHRI
Standard 810-2007 and ASHRAE Standard 29-2009. 10 CFR 431.134(b). Since
publication of the January 11, 2012 test procedure final rule
(``January 2012 final rule''), both AHRI and ASHRAE have published new
versions of the referenced standards. 77 FR 1591. The most recent
versions are AHRI Standard 810 (I-P)-2016 with Addendum 1 and ASHRAE
Standard 29-2015 (reaffirmed in 2018). DOE has reviewed the most recent
versions of both AHRI Standard 810 and ASHRAE Standard 29 and has
compared the updated versions of these industry standards to those
currently incorporated by reference in the ACIM test procedure.
The updates in ASHRAE Standard 29-2015 provide additional
specificity to several aspects of the test method. In general, these
updates increase the precision and improve the repeatability of the
test method, but do not fundamentally change the testing process,
conditions, or results. In addition, ASHRAE made several grammatical,
editorial, and formatting changes to improve the clarity of the test
method. DOE summarizes these changes in Table III.2.
Table III.2--Summary of Changes Between ASHRAE Standard 29-2009 and
ASRHAE Standard 29-2015
------------------------------------------------------------------------
ASHRAE standard ASHRAE standard 29-
Requirement 29-2009 2015
------------------------------------------------------------------------
Test Room Operations.......... None............. No changes to the
test room shall be
made during
operation of the ice
maker under test
that would impact
the vertical ambient
temperature gradient
or the ambient air
movement.
Temperature Measuring Accuracy of 1.0 [deg]F resolution of 1.0 [deg]F;
of <=2.0 [deg]F. where accuracy
greater than 1.0 [deg]F,
the resolution shall
be at least equal to
the accuracy
requirement.
Harvest Water Collection...... None............. Harvest water shall
be captured by a non-
perforated pan
located below the
perforated pan.
Ice Collection Container ``Perforated pan, Requirements
Specifications. bucket, or wire regarding water
basket'' and retention weight and
``non-perforated perforation size for
pan or bucket.'' perforated pans and
``solid surface''
for non-perforated
pans.
Pressure Measuring Instruments None............. Accuracy of and
resolution of 2.0 percent of
the quantity
measured.
Sampling Rate................. None............. Maximum interval
between data samples
of 5 sec.
[[Page 65865]]
Supply Water Temperature and 1 1 [deg]F
Pressure. [deg]F (water (water supply
supply temperature) and
temperature). ``within 8 in. of
the ice maker . . .
within the specified
range'' (water
pressure) during
water fill interval.
Inlet Air Temperature Measure a minimum Measure at a location
Measurement. of 2 places, geometrically center
centered 1 ft to the inlet area at
from the air a distance 1 ft from
inlet(s). each inlet.
Clearances.................... 18 inches on all 3 ft or the minimum
sides. clearance allowed by
the manufacturer,
whichever is
greater.
Stabilization Criteria........ Three consecutive Two consecutive 15.0
14.4 min samples min 2.5
(continuous) sec samples taken
taken within a within 5 mins of
1.5 hr period or each other within 2
two consecutive percent or 0.055 lbs
batches (batch) (continuous) or
do not vary by calculated 24-hour
more than 2 percent. from two consecutive
batches within 2 percent or
2.2 lb (batch).
Capacity Test Ice Collection.. Three consecutive Specifies that batch
14.4 min samples ice must be weighed
(continuous) or 30 2.5
batches (batch). sec after collection
and continuous ice
samples must be
within 5 mins of
each other.
Calorimetry Testing........... (1) Room (1) Room temperature
temperature is shall be within 65-
not specified. 75[deg]F during the
(2) To determine entire procedure.
the calorimeter (2) To determine the
constant, 30 lbs calorimeter
of water must be constant, add a
added.. quantity of water 5
(3) Rate of times the mass of
stirring is ice (see #4 below).
described as (3) Rate of stirring
``vigorously''.. is to be 1 0.5
the calorimeter revolutions/second.
constant, 6 lbs (4) To determine the
of ice must be calorimeter
added.. constant, add a mass
(5) The block of of ice between 50-
ice is seasoned 200% of the rated
at room ice production for a
temperature. A period of 15 minutes
temperature of the ice maker to
measurement be tested, or 6 lbs,
location is not whichever is less.
specified for (5) The block of pure
the block of ice must reach an
ice.. equilibrium
(6) To determine temperature measured
the calorimeter by a thermocouple
constant, it is embedded in the
not explicitly interior of the
stated to block and free of
continue trapped water.
stirring for 15 (6) To determine the
minutes after calorimeter
the ice has constant, continue
melted.. stirring for 15
(7) The minutes after ice
calorimeter has disappeared.
constant shall (7) The calorimeter
be determined constant shall be
twice, at the determined, at a
beginning and at minimum, each time
the end of the the temperature
daily tests.. measuring and
(8) The weighting
calorimeter instruments are
constant shall calibrated or if
be no greater there is a change to
than 1.02.. the container or
stirring apparatus.
(8) The calorimeter
constant must be
within 1.0-1.02.
(9) To determine the
net cooling effect,
stir the water for
15 minutes prior to
the addition of the
harvested ice.
(10) Section 7.2.4
specifies that the
ice sample used for
calorimetry testing
shall be intercepted
using a non-
perforated
container, precooled
to ice temperature,
and collected from a
stabilized ice maker
over a time period
of 15 min or until 6
lbs has been
captured.
(9) To determine
the net cooling
effect, the
water must stand
in the
calorimeter for
1 min before
adding harvested
ice.
(10) Section
7.2.3 specifies
that the ice
sample used for
calorimetry
testing shall be
intercepted in a
manner similar
to that
prescribed in
section 7.2.2
(7.2.2 reads:
Record the
required data
(see section
8).), except
that the sample
size shall be
suitable for the
test..
Recorded Data................. Specifies 7 Specifies that
discrete ambient temperature
elements be gradient (at rest),
recorded. maximum air-
circulation velocity
(at rest), and water
pressure must also
be recorded.
------------------------------------------------------------------------
DOE also reviewed the updates to AHRI Standard 810 (I-P)-2016 with
Addendum 1 and identified the following revisions: new definitions for,
among others, ice hardness factor and potable water use rate; and an
updated rounding requirement for energy consumption rate (from 0.1
kilowatt hours per 100 pounds (``kWh/100 lb'') to 0.01 kWh/100 lb). The
changes to AHRI Standard 810 (I-P)-2016 with Addendum 1 are primarily
clerical in nature and provide greater consistency in the use of terms
and specific definitions for those terms.
DOE also compared the latest version of ASHRAE Standard 29-2015 to
the requirements in the current DOE test procedure in 10 CFR 431.134.
These test methods specify different conditions for calorimetry testing
of continuous ice makers. Specifically, the current DOE test procedure
requires an ambient air temperature of 70 1 [deg]F, with
an initial water temperature of 90 1 [deg]F. 10 CFR
431.134(b)(2)(ii). ASHRAE Standard 29-2015 states in appendix A3 that
room temperature shall be kept between 65 [deg]F and 75 [deg]F, and
that the water
[[Page 65866]]
temperature is 20 [deg]F 1 [deg]F above room temperature.
In the December 2021 NOPR, DOE tentatively determined that the
current ambient and water condition requirements for calorimetry
testing in the DOE test procedure are appropriate because they provide
more precise and repeatable measurements than the tolerances described
in ASHRAE Standard 29-2015. 86 FR 72322, 72331. Additionally,
manufacturers have been meeting the requirements to maintain 70 [deg]F
1 [deg]F ambient air temperature and 90 [deg]F 1 [deg]F initial water temperature for calorimetry testing as
part of the current DOE test procedure in 10 CFR 431.134. The current
DOE test approach also is consistent with the industry test standard
requirements, i.e., a test performed at the DOE-required temperature
conditions meets the temperature conditions specified in ASHRAE
Standard 29-2015. Therefore, in the December 2021 NOPR, DOE did not
propose to amend the 70 [deg]F 1 [deg]F ambient air
temperature and 90 [deg]F 1 [deg]F initial water
temperature requirements for calorimetry testing. 86 FR 72322, 72331.
DOE proposed to explicitly provide that the harvested ice used to
determine the ice hardness factor be produced at the Standard Rating
Conditions specified in section 5.2.1 of AHRI Standard 810 (I-P)-2016
with Addendum 1. Id. These conditions are provided in the industry
standard, indicating that they are currently used by manufacturers and
therefore this clarification would not change how manufacturers test.
Additionally, added specificity may be needed to accurately
determine the calorimeter constant. DOE has found that the lack of
specificity as to the location of the temperature measurement of the
block of pure ice may lead to variation in the resulting calorimeter
constant. Therefore, in the December 2021 NOPR, DOE proposed to specify
that the block of pure ice, as specified in section A2.e of ASHRAE
Standard 29-2015, is measured by a thermocouple embedded at
approximately the geometric center of the interior of the block. 86 FR
72322, 72331. Furthermore, DOE proposed to specify that any liquid
water present on the block of ice must be wiped off the surface of the
block before placing the block into the calorimeter. Id.
In the December 2021 NOPR, DOE proposed to adopt by reference AHRI
Standard 810 (I-P)-2016 with Addendum 1 and ASHRAE Standard 29-2015
(note that AHRI Standard 810 (I-P)-2016 with Addendum 1 refers to
ASHRAE Standard 29-2015 and not the 2018 re-affirmed version) as the
basis for DOE's ACIM test procedure, with additional proposed
provisions as specified in the December 2021 NOPR. 86 FR 72322, 72331.
In the December 2021 NOPR, DOE requested comment on its proposal to
maintain the current specifications for ambient air temperature and
initial water temperature for calorimetry testing. 86 FR 72322, 72331.
DOE additionally requested comment on its proposal to clarify that the
harvested ice used to determine the ice hardness factor be collected
from the ACIM under test at the Standard Rating Conditions specified in
section 5.2.1 of AHRI Standard 810 (I-P)-2016 with Addendum 1. Id.
In response to the December 2021 NOPR, Hoshizaki commented that it
does not agree with this change, and requested that any changes to the
test procedure be brought to the ASHRAE 29 standard committee for
clarification and acceptance. (Hoshizaki, No. 14, p. 2)
Similarly, AHRI commented that members are not opposed to this
change but note that such a change must follow the proper channels and
first be incorporated into the ASHRAE 29 method of test before being
adopted into federal regulation. (AHRI, No. 13, p. 3)
AHAM commented that requiring the ice sample to be used for
calorimetry testing be intercepted using a non-perforated container,
precooled to ice temperature is not necessary because the measurement
of ice sample weight is very quick (about five seconds) and will not
reduce the accuracy due to the ice sample melting or evaporating.
(AHAM, No. 18, p. 13) AHAM stated that this requirement does not add a
large burden, but it is an unnecessary burden. Id.
The test approach proposed in the December 2021 NOPR is consistent
with the industry test standard requirements and manufacturers have
been meeting the requirements to maintain 70 [deg]F 1
[deg]F ambient air temperature and 90 [deg]F 1 [deg]F
initial water temperature for calorimetry testing as part of the
current DOE test procedure in 10 CFR 431.134.
DOE is maintaining in this final rule the current specifications
for ambient air temperature and initial water temperature for
calorimetry testing and clarifying that the harvested ice used to
determine the ice hardness factor be collected from the ACIM under test
at the Standard Rating Conditions specified in section 5.2.1 of AHRI
Standard 810 (I-P)-2016 with Addendum 1.
Additionally, DOE requested comment on its proposal to clarify that
the temperature of the block of pure ice, as specified in section A2.e.
of ASHRAE Standard 29-2015, is measured by a thermocouple embedded at
approximately the geometric center of the interior of the block. 86 FR
72322, 72331. DOE also requested comment on its proposal to clarify
that any water that remains on the block of ice must be wiped off the
surface of the block before placing the ice into the calorimeter. Id.
In response to the December 2021 NOPR, Hoshizaki requested that any
clarification of wording in ASHRAE 29 be brought to the ASHRAE 29
standard committee for discussion and acceptance. (Hoshizaki, No. 14,
p. 2)
AHRI encouraged DOE to bring any requests for clarification or
interpretation to the proper industry working groups for consideration,
since consistency and repeatability are of utmost importance to ensure
that all original equipment manufacturers (``OEMs'') and testing bodies
address these provisions in a constant manner. (AHRI, No. 13, p. 3)
The test approach proposed in the December 2021 NOPR is consistent
with the industry test standard requirements and would limit variation
in determining the calorimeter constant. Therefore, DOE is maintaining
these clarifications in this final rule, consistent with the December
2021 NOPR.
Additionally, DOE requested comment on its proposal to adopt by
reference AHRI Standard 810 (I-P)-2016 with Addendum 1 and ASHRAE
Standard 29-2015, except for the provisions for calorimetry testing as
discussed previously, for all ACIMs. 86 FR 72322, 72331.
Hoshizaki and AHRI agreed to the adoption of AHRI Standard 810 (I-
P)-2016 with Addendum 1 and ASHRAE 29-2015. (Hoshizaki, No. 14, p. 2;
AHRI, No. 13, p. 3) However, Hoshizaki supports adoption of the
standards in their entirety with no exceptions, otherwise there is a
risk that changes not reflected in the standards will not be realized
by testers. (Hoshizaki, No. 14, p. 2) Hoshizaki and AHRI requested that
any proposed changes be brought before the relevant standard committees
for discussion and acceptance. (Hoshizaki, No. 14, p. 2)
DOE is adopting by reference AHRI Standard 810 (I-P)-2016 with
Addendum 1 and ASHRAE Standard 29-2015, except for the additional
amendments as specified in this final rule. DOE has determined that the
additional amendments are consistent with the test requirements in the
industry standards but provide added specificity to limit variation in
testing. These modifications are consistent with section 8(c) of 10 CFR
part 430, subpart
[[Page 65867]]
C, appendix A (the ``Process Rule''), applicable to ACIMs under 10 CFR
431.4, which states that DOE may adopt industry test procedure
standards with modifications, or craft its own procedures as necessary
to ensure compatibility with the relevant statutory requirements, as
well as DOE's compliance, certification, and enforcement requirements.
Additional modifications to the industry standard test methods are
discussed in the following sections.
D. Additional Amendments
As part of this rulemaking, DOE conducted testing to identify
whether ASHRAE Standard 29-2015 and AHRI Standard 810 (I-P)-2016 with
Addendum 1 could potentially benefit from additional detail and to
investigate topics discussed in the March 2019 RFI and December 2021
NOPR. The testing and initial findings are discussed along with any
corresponding amendments in the following sections.
1. Low-Capacity ACIMs
DOE examined the comments received in response to the December 2014
MREF Test Procedure NOPR to consider what test method would be
appropriate for low-capacity ACIMs. During the December 2014 MREF Test
Procedure NOPR public meeting, True Manufacturing commented that there
are very few differences between ice makers with harvest rates less
than 50 lb/24 h and those with harvest rates greater than 50 lb/24 h.
(Public Meeting Transcript, No. EERE-2013-BT-TP-0029-0014 at p. 31)
Hoshizaki commented in response to the December 2014 MREF Test
Procedure NOPR that the ASHRAE 29 test needs to be evaluated for
accuracy for units that make less than 50 lb/24 h, as they are outside
the listed scope of the standard. (Hoshizaki, No. EERE-2013-BT-TP-0029-
0011 at p. 1)
In the December 2021 NOPR, DOE evaluated the provisions in its
existing ACIM test procedure to determine if any modifications are
necessary to ensure the proposed test method would provide
representative and repeatable measures of performance for low-capacity
ACIMs and would not be unduly burdensome to conduct. 86 FR 72322,
72331. DOE also evaluated the provisions in AHRI Standard 810 (I-P)-
2016 with Addendum 1 and ASHRAE Standard 29-2015 to determine their
applicability to low-capacity ACIMs. Id. During investigative testing
of batch type low-capacity ACIMs, DOE observed that the ice collection
container requirements in section 5.5.2(a) of ASHRAE Standard 29-2015
may not be appropriate for this equipment. Section 5.5.2(a) requires
that the collection container have a water retention weight that is no
more than 1.0 percent of that of the smallest batch of ice for which
the container is used. For low-capacity batch type ACIMs, the weight of
ice in each batch is significantly lower than for other higher capacity
ACIMs. Accordingly, 1.0 percent of an individual batch represents a
very small weight for low-capacity ACIMs. For example, one such low-
capacity ACIM has a typical batch weight of 0.087 pounds; 1.0 percent
of that would be 0.00087 pounds, the equivalent of 0.080 teaspoons of
water. The water retention weight of a typical very small collection
container is approximately 0.0030 pounds. DOE was not able to identify
collection containers that would meet this threshold for the low-
capacity ACIMs with the lowest batch weights.
From its test sample, DOE determined that a water retention weight
of no more than 4.0 percent would allow for testing low-capacity ACIMs
with the lowest batch weights with a typical collection container.
Accordingly, in the December 2021 NOPR, DOE proposed that the water
retention requirement in section 5.5.2(a) not apply to batch type low-
capacity ACIMs, and instead to require a water retention weight of no
more than 4.0 percent of the smallest batch of ice for which the
container is used. 86 FR 72322, 72332.
During the January 24, 2022, webinar to discuss the December 2021
NOPR, AHRI commented that the water retention weight requirement for
low-capacity ACIMs and DOE's test data should be considered by the
method of test committee (e.g., ASHRAE 29). (AHRI, January 24, 2022,
webinar to discuss the December 2021 NOPR \11\)
---------------------------------------------------------------------------
\11\ See pages 19-20; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
DOE will consider any updated industry standards, if available,
during future ACIM test procedure rulemakings.
DOE is maintaining that the water retention requirement in section
5.5.2(a) of ASHRAE Standard 29-2015 not apply to batch type low-
capacity ACIMs, and instead to require a water retention weight of no
more than 4.0 percent of the smallest batch of ice for which the
container is used, consistent with the December 2021 NOPR.
a. Portable ACIMs
For portable ACIMs, DOE has determined that some provisions for
measuring and maintaining inlet water conditions in ASHRAE Standard 29-
2015 are not appropriate: i.e., sections 5.4, 5.6, 6.2, and 6.3. These
sections include instrument specifications, test conditions, and
measurement instructions regarding inlet water flow, pressure, and
temperature. These sections are not applicable to portable ACIMs
because such equipment does not have a fixed water connection, and
therefore the conditions in these sections would not provide
representative conditions for portable ACIMs. Portable ACIMs instead
require that the fill reservoir be manually filled with a maximum
volume of water that is recommended by the manufacturer.
To determine typical operation and the corresponding need for
additional test procedure instructions regarding the water supply for
portable ACIMs, DOE conducted tests on portable ACIMs according to the
requirements of AHRI Standard 810 (I-P)-2016 with Addendum 1 and ASHRAE
Standard 29-2015, except for sections 5.4, 5.6, 6.2, and 6.3 of ASHRAE
Standard 29-2015. From this testing, DOE has determined that additional
instructions are needed regarding supply water characteristics and
filling the water reservoirs in portable ACIMs.
Section 5.2.1 of AHRI Standard 810 (I-P)-2016 with Addendum 1
specifies an inlet water temperature of 70.0 [deg]F for ACIM testing.
Because portable ACIMs do not have a continuous water supply, the water
filled in the water reservoir is not maintained at a constant
temperature; the temperature may change after the initial fill based on
heat transfer with the ambient air and the other components of the
ACIM. Accordingly, DOE has determined that specifying only the initial
fill temperature of the water supplied to the reservoir is most
representative of typical use. In the December 2021 NOPR, DOE proposed
to establish the initial water temperature in a separate external
container before transferring the water to the water reservoir. 86 FR
72322, 72332. In DOE's experience, using an external container to
establish and verify the initial water temperature is significantly
less burdensome than measuring and adjusting the water temperature
within the water reservoir itself. Therefore, in the December 2021
NOPR, DOE proposed that the initial water temperature condition be
established in an external container and verified by inserting a
temperature sensor into approximately the geometric center of the water
in the external container. 86 FR 72322, 72332. The initial water
temperature would be defined as 70 [deg]F 1.0 [deg]F,
consistent with the condition as specified in section 5.2.1 of AHRI
Standard 810 (I-P)-2016 with Addendum 1 and the tolerance as
[[Page 65868]]
specified in section 6.2 of ASHRAE Standard 29-2015. Id.
Portable ACIM users may have an option of filling the reservoirs to
varying levels. To determine the appropriate fill level for testing,
DOE reviewed operating instructions for portable ACIMs available from a
range of manufacturers. DOE observed that the operating instructions
typically instruct the user to fill to the maximum specified level, or
to any level up to the maximum. To ensure repeatable and reproducible
test results, DOE determined that filling the water reservoir to the
maximum volume of water as specified by the manufacturer is
representative of typical use. In addition, specifying a consistent
fill level for testing at the maximum fill level would limit
variability associated with reservoir water temperature and would
ensure the portable ACIM has sufficient water to conduct the test.
In summary, in the December 2021 NOPR, DOE proposed that portable
ACIMs be subject to the test procedure as proposed in the NOPR, except
that sections 5.4, 5.6, 6.2, and 6.3 of ASHRAE Standard 29-2015 would
not apply. 86 FR 72322, 72332. DOE proposed to provide the following
additional test instructions necessary for testing portable ACIMs:
ensure that the ice storage bin is empty; fill an external container
with water; establish a water temperature in the external container
that is consistent with the requirements of section 5.2.1 of AHRI
Standard 810 (I-P)-2016 with Addendum 1 and the tolerance specified in
section 6.2 of ASHRAE Standard 29-2015 (i.e., 70 [deg]F
1.0 [deg]F); verify the water temperature in the external container by
inserting a temperature sensor into approximately the geometric center
of the water; after establishing water temperature, immediately
transfer the water to the portable ACIM reservoir and fill the
reservoir to the maximum level as specified by the manufacturer. Id.
DOE also determined that additional instructions are needed for
portable ACIMs to meet the requirements of section 6.6 of ASHRAE
Standard 29-2015, which requires that ``bins shall be used when testing
and shall be filled one-half full with ice.'' Because section 6.6 of
ASHRAE Standard 29-2015 does not specify how the bin would be filled
with ice, a laboratory may fill the ice storage bin one-half full of
externally produced ice (i.e., ice that was made by a separate ACIM),
for example to avoid waiting for the unit under test to produce enough
ice to fill the bin one-half full prior to initiating the start of the
test. Using externally produced ice does not directly affect the
performance of a non-portable ACIM because the conditions within the
ice storage bin do not have a direct impact on the incoming potable
water temperature.
In contrast, the conditions within the ice storage bin of a
portable ACIM do directly impact performance because portable ACIMs
typically recycle the melt water (at 32 degrees) from the internal ice
storage bin and combine it with water from the reservoir (initially at
70 degrees) to make additional ice. Accordingly, any externally
produced ice introduced to a portable ACIM to fill the bin one-half
full prior to testing could affect the performance of the system during
the test when compared to the tested performance using ice produced by
the portable ACIM under test.
To limit test variability that could occur due to the introduction
of externally produced ice, in the December 2021 NOPR DOE proposed that
for portable ACIMs, the ice storage bin must be empty prior to the
initial water fill, and the unit under test must be operated to produce
ice into the ice storage bin until the bin is one-half full (i.e.,
precluding the use of externally produced ice to fill the bin one-half
full prior to testing). 86 FR 72322, 72333. DOE proposed to define one-
half full as half of the vertical dimension of the storage bin, based
on the maximum possible fill level. Id. Once the ice storage bin is
one-half full of ice, testing would proceed according to section 7 of
ASHRAE Standard 29-2015, consistent with non-portable ACIM testing. Id.
In the December 2021 NOPR, DOE requested comment on its proposal
regarding reservoir water and ice storage bin instructions for portable
ACIMs. 86 FR 72322, 72332-72333.
Hoshizaki agreed with the proposal if the portable units have a way
to collect the ice in a way not to confuse the ice made in each cycle
from the \1/2\ full bin. (Hoshizaki, No. 14, p. 2-3) Hoshizaki and AHRI
requested that this be brought to the ASHRAE 29 standard committee for
consideration. (Hoshizaki, No. 14, p. 2-3; AHRI, No. 13, p. 3)
AHRI commented that consistency and repeatability are of utmost
importance to ensure that all manufacturers and testing bodies address
these provisions in a constant manner. (AHRI, No. 14, p. 3)
AHAM commented that the 70 [deg]F 1.0 [deg]F tolerance
requirement for the initial water temperature is unnecessarily tight
for low-capacity ACIMs, including portable ACIMs, which adds
unnecessary test burden. (AHAM, No. 18, p. 10-11) AHAM commented that
the test procedure should specify that the water should be stirred to
eliminate gradients that would naturally occur because some models
recirculate melt water to the reservoir and that, for all low-capacity
ACIMs, the temperature of the inlet water will vary throughout the
entire test with little effect on the ultimate result. Id.
AHAM commented that the DOE's proposed test procedure for portable
ACIMs does not specify that the bin should be emptied and dried out
before the first 15-minute run, which AHAM suggests may be implicit in
the proposed test procedure but should be stated clearly. (AHAM, No.
18, p. 12)
DOE notes that, in the December 2021 NOPR, DOE proposed that the
ice storage bin is empty prior to the initial potable water reservoir
fill and that the initial water temperature of 70 [deg]F
1.0 [deg]F for testing portable ACIMs is only required to be verified
in an external container immediately before filling the portable ACIM
water reservoir. 86 FR 72322, 72332-72333.
DOE testing has shown that portable ACIMs are able to have ice
collected in a similar manner to non-portable ACIMs which distinguish
the ice made in each cycle from the ice already present in the ice
storage bin. DOE has additionally determined that the additional
provisions regarding reservoir water fill are necessary to allow for
testing of portable ACIMs.
DOE is maintaining the test requirements as proposed in the
December 2021 NOPR for portable ACIMs in this final rule.
b. Refrigerated Storage ACIMs
DOE has determined that refrigerated storage ACIMs can be tested
according to the current DOE ACIM test procedure as well as AHRI
Standard 810 (I-P)-2016 with Addendum 1 and ASHRAE Standard 29-2015.
DOE investigated whether additional specification was necessary to
ensure that these test methods would provide representative and
repeatable results for refrigerated storage ACIMs and would not be
unduly burdensome to conduct.
DOE identified two aspects of refrigerated storage ACIM testing
that may need further specification to limit variability: door openings
for refrigerated storage ACIMs and refrigeration set point controls.
Door opening durations may affect the measured performance of
refrigerated storage ACIMs more than non-refrigerated storage ACIMs
because the refrigeration system provides cooling for the entire self-
contained storage bin rather than only for the ice making evaporator.
Thus, when opening the storage container door to collect ice from
refrigerated storage ACIMs, some
[[Page 65869]]
portion of cold air from the storage container will likely be replaced
by higher temperature ambient air. Both the duration and the extent of
the door opening can contribute to this air exchange within the storage
container. Therefore, specifying the duration and the extent of the
door opening would limit variability from test to test, thus promoting
repeatable and reproducible test results.
From investigative testing, DOE has determined that the process of
opening the bin door, carefully removing or replacing the ice
collection container, and closing the door can be readily performed in
under 10 seconds. Therefore, in the December 2021 NOPR, DOE proposed
that for refrigerated storage ACIMs, any storage bin door openings
shall be conducted with the door in the fully open position for 10
1 seconds. 86 FR 72322, 72333. DOE proposed to specify
that ``fully open'' means opened to an angle of not less than 75
degrees (or to the maximum angle possible, if that is less than 75
degrees), which is consistent with the definition for fully open in
ANSI/ASHRAE Standard 72-2018, ``Method of Testing Open and Closed
Commercial Refrigerators and Freezers.'' Id. To ensure a consistent
number of door openings, DOE also proposed to specify that door
openings would occur only when collecting the ice sample and when
returning the empty collection container to the ice storage compartment
(i.e., two separate door openings per sample collection). Id.
Refrigeration set point controls may also affect the measured
performance of refrigerated storage ACIMs, if the controls can be
adjusted by the user to maintain different storage compartment
temperatures. DOE investigated whether refrigerated storage ACIMs allow
the user to adjust the refrigeration set point of the ACIM and if so,
how. DOE reviewed user manuals for several refrigerated storage ACIMs
and found that the models either do not allow the user to adjust the
refrigeration set point, or have a factory preset temperature control
that can be adjusted by the user, but not in an easily accessible
manner (e.g., temperature control screws adjustable only with a
screwdriver or accessible behind grilles). The ability to adjust the
refrigeration set point on some refrigerated storage ACIMs does not
appear to be a setting that users would typically adjust and is likely
used only for troubleshooting. Based on this information, DOE proposed
in the December 2021 NOPR that the refrigeration set point for testing
a refrigerated storage ACIM be consistent with section 4.1.4 of AHRI
Standard 810 (I-P)-2016 with Addendum 1 (i.e., per the manufacturer's
written instructions with no adjustment prior to or during the test).
86 FR 72322, 72333.
In the December 2021 NOPR, DOE requested comment on its proposal to
test refrigerated storage ACIMs consistent with AHRI Standard 810 (I-
P)-2016 with Addendum 1, with the specified proposed door opening
duration and frequency. 86 FR 72322, 72333. DOE requested comment on
whether a specific refrigeration set point or internal air temperature
should be specified instead of the manufacturer's factory preset. Id.
In response to the December 2021 NOPR, Hoshizaki and AHRI both
requested DOE clarify refrigerated storage ACIMs and share examples
before feedback can be given. (Hoshizaki, No. 14, p. 3; AHRI, No. 13,
p. 4)
AHRI commented that ASHRAE 29 does not cover products installed in
residential refrigerators or freezers, and if these are the type of
systems being referred to as self-contained refrigerated storage ACIMs,
the scope of both ASHRAE 29 and the DOE rulemaking would need to be
expanded to cover such equipment. (AHRI, No. 13, p. 4) AHRI suggested
that DOE clarify the equipment type and bring this issue to ASHRAE SPC
29 for consideration. Id. AHAM commented that DOE's proposed test
procedure draws heavily from AHRI Standard 810 (I-P)-2016 with Addendum
1 and ASHRAE Standard 29-2015 that were not developed with residential
products in mind. (AHAM, No. 18, p. 9)
DOE is not referring to products installed in residential
refrigerators or freezers in this Final rule. Refrigerated storage
ACIMs are explicitly excluded from the freezer definition at 10 CFR
430.2 and differ from the refrigerator-freezer definition at 10 CFR
430.2 because refrigerated storage ACIMs only produce and store ice in
a single compartment. Section III.B.1 provides further clarity and an
example of refrigerated storage ACIMs.
Because DOE did not receive any comments regarding the refrigerated
storage ACIM proposals, DOE is maintaining the test requirements as
proposed in the December 2021 NOPR for refrigerated storage ACIMs in
this final rule.
2. Stability Criteria
The current DOE test procedure, through reference to section 7.1.1
of ASHRAE Standard 29-2009, defines ACIM stability based on the harvest
rate. Specifically, continuous type ice makers shall be considered
stabilized when the weights of three consecutive 14.4-minute samples
taken within a 1.5-hour period do not vary by more than 2
percent. Batch type ice makers are considered stable when the weights
from the samples from two consecutive cycles do not vary by more than
2 percent.
a. Capacity Test Cycles or Samples
Section 7.1.1 of ASHRAE Standard 29-2015 revised the stabilization
criteria to consider continuous type ice makers stable when the weights
of two consecutive 15.0 minute 2.5 seconds samples do not
vary by more than the greater of 2 percent, or 0.055
pounds. Section 7.1.1. of ASHRAE Standard 29-2015 specifies that batch
type ice makers are considered stable when the 24-hour calculated ice
production rate from samples taken from two consecutive cycles do not
vary by the greater of 2 percent or 2.2 pounds. Compared to
the 2009 version, ASHRAE Standard 29-2015 added absolute stability
criteria of 0.055 lb/15 minutes for continuous equipment and 2.2 lb/24
h for batch equipment.
In addition, ASHRAE Standard 29-2009 states that the unit must be
stable before the capacity tests are started. This provision was
changed in ASHRAE Standard 29-2015, which instead states that the ice
maker must be stable for capacity test data to be valid. In
application, the stability provision in ASHRAE Standard 29-2009 means
that any cycle or sample after the stability criteria is met is valid
to be used for the capacity test. DOE notes that the applicability of
the stability criteria in ASHRAE Standard 29-2015 could be understood
in one of two ways: (1) Unchanged from ASHRAE Standard 29-2009, meaning
that any cycle or sample after the stability criteria are met is valid
to be used for the capacity test; or (2) the ice production rate for
each cycle used for the capacity test relative to any other cycle or
sample used for the capacity test must be within the greater of 2 percent and 2.2 lb/24 h for batch type ice makers, and each
sample used for the capacity test must be within the greater of 2 percent and 0.055 lb/15 mins for continuous ice makers. The
second interpretation limits potential variability compared to the
first interpretation because it puts specific limits on the variability
between cycles and samples to be used for the capacity tests. The
difference in the potential interpretations of the stability provisions
in ASHRAE Standard 29-2015 could result in variation in capacity
ratings. Additionally, the second interpretation limits test burden by
not requiring separate cycles for
[[Page 65870]]
meeting the stability criteria and for testing performance. Under the
second interpretation, the same cycles are used to determine stability
and performance. In the December 2021 NOPR, DOE proposed to expressly
provide that the second interpretation be used for determining
stability, such that all cycles or samples used for the capacity test
are stable. 86 FR 72322, 72334. DOE does not expect that this proposal
would impact ACIM performance as measured under the existing test
procedure as it would not substantively change the cycles required for
evaluating performance. Id.
In the December 2021 NOPR, DOE requested comment on its
interpretation of section 7.1.1 of ASHRAE Standard 29-2015 and proposal
to require that all cycles or samples used for the capacity test meet
the stability criteria. 86 FR 72322, 72334.
Hoshizaki agreed that all cycles should meet the stability
criteria. (Hoshizaki, No. 14, p. 3) AHRI commented that the stability
criteria should match the requirements of ASHRAE 29. (AHRI, No. 13, p.
4)
AHRI commented that some units vary in performance each cycle due
to water dump frequency by design, and DOE should ask the ASHRAE
committee for an interpretation if DOE is concerned about ambiguity in
ASHRAE 29. (AHRI, No. 13, p. 4)
IOM commented that this proposal would take the stabilization
criteria further than ASHRAE Standard 29-2009 and ASHRAE Standard 29-
2015, requiring that all cycles not differ by more than 2%. (Ice-O-
Matic, No. 11, p. 1) IOM added that a dataset with small linear growth
(100, 102, and 104 lb/24 hr) would not be considered stabilized under
this DOE rule, while it would be considered stabilized under ASHRAE
Standard 29-2015. Id. IOM commented that in practice it is not uncommon
for units which achieved stabilization under ASHRAE Standard 29-2009 to
produce capacity test samples which vary in excess of 2
percent. Id. IOM stated that because allowable variance during capacity
tests is already being reduced by changing from ASHRAE 29-2009 to
ASHRAE 29-2015, IOM finds DOE's proposal to further reduce potential
variance excessive, and believes it has the potential to increase test
burden on manufacturers. Id. IOM generally supported using test cycles
to also confirm stability following the requirements for stability as
defined in ASHRAE Standard 29-2015. (IOM, No. 11, p. 3)
DOE has determined that clarifying the stability criteria specified
in ASHRAE 29-2015 will produce test results that are more
representative, repeatable, and reproducible. As indicated in the IOM
comment, the current ASHRAE 29-2009 approach may introduce potential
variability in test results. Additionally, reducing the number of
cycles or samples required for the capacity test will reduce test
burden by reducing total test time. DOE discusses test burden in
section III.F.1 of this final rule.
Therefore, DOE is maintaining in this final rule its interpretation
of section 7.1.1 of ASHRAE Standard 29-2015 and requirement that all
cycles or samples used for the capacity test meet the stability
criteria, consistent with the December 2021 NOPR.
b. Test Sample Duration
Section 7.1.1 of ASHRAE Standard 29-2015 added a requirement that
the duration of each sample for continuous type ice makers be 15.0
minutes 2.5 seconds. DOE testing indicated that removing
the plastic pan or bucket within the tolerance of 2.5
seconds can be difficult depending on the specific test setup (e.g.,
removing the container from the ice maker or bin without spilling ice).
An increased tolerance would reduce burden on manufacturers to test
continuous ice makers, while still sufficiently limiting the
variability between samples used for the capacity test to the criteria
proposed.
In the December 2021 NOPR, DOE proposed to increase the tolerance
to collect samples for continuous ice makers from 15.0 minutes 2.5 seconds to 15.0 minutes 9.0 seconds. 86 FR
72322, 72334. Increasing the tolerance to 9.0 seconds could affect the
weight of each sample; however, variability would not increase because
the samples used for the capacity test would still need to meet the
proposed stability criteria. Id. With the 9-second tolerance, the
maximum and minimum allowable collection times would vary by
approximately 2 percent, which is consistent with the allowable
variation in capacity to determine stability. Id. DOE expected that
this proposal would reduce the test burden compared to the ASHRAE
Standard 29-2015 approach and would ensure that valid samples can be
obtained. Id. Additionally, in the December 2021 NOPR, DOE did not
expect that this proposal would affect measured performance as compared
to the existing test procedure because the sample collection period as
proposed is not substantively different from the existing test
procedure approach. Id.
In the December 2021 NOPR, DOE requested comment on the proposal to
increase the tolerance for continuous ice makers to collect samples to
15.0 minutes 9.0 seconds. 86 FR 72322, 72334.
In response to the December 2021 NOPR, IOM commented in support of
the proposal to increase the tolerance on sample collection for
continuous ice makers. (Ice-O-Matic, No. 11, p. 1)
Hoshizaki and AHRI commented that they do not agree with the
proposed change. (Hoshizaki, No. 14, p. 3; AHRI, No. 13, p. 4)
Hoshizaki commented such time could impact high-capacity continuous
models and have a significant impact on capacity and energy totals, and
AHRI added that the proposed changes could impact the output depending
on the capacity of the unit. Id. AHRI stated that this proposal could
change the integrity of the test and would need further evaluation
prior to being considered. Id.
AHRI added that the increase to 9.0 seconds would allow
high-capacity units to potentially collect a greater sample and while
the test was not designed to be applied to low-capacity machines, the
impact of this proposed change could be substantially less. Id.
Hoshizaki requests that further discussion be put through the
ASHRAE 29 committee. (Hoshizaki, No. 14, p. 3)
DOE has re-evaluated its proposal and determined that although a
greater tolerance would reduce test burden on manufacturers to test
continuous ACIMs, the collection duration tolerance in ASHRAE 29-2015
provides a repeatable and reproducible method of test. DOE has
determined that the specified tolerance included in ASHRAE 29-2015
demonstrates that manufacturers can meet the specified tolerance
without the need for an increased tolerance. Therefore, DOE is
declining to allow for a greater collection duration tolerance than the
tolerance specified for continuous ACIMs in ASHRAE 29-2015 (i.e.,
2.5 seconds).
c. Low-Capacity ACIM Stability Criterion
Section 7.1.1 of ASHRAE 29-2015 includes stabilization
requirements, which specify: (1) For continuous ACIMs, collected
weights must not vary by more than 2 percent or 25 g (0.055
lb), whichever is greater; or (2) for batch ACIMs, the calculated 24-
hour ice production rates must not vary by more than 2
percent or 1 kg (2.2 lb), whichever is greater.
Based on investigative testing conducted as part of this
rulemaking, DOE observed that the absolute stability criteria of 2.2
lb/24 h for batch type ice makers would not necessarily represent
stable operation for low-capacity batch ACIMs. DOE conducted a market
[[Page 65871]]
assessment and observed batch low-capacity ACIMs with harvest rates as
low as 7 lb/24 h. Based on this harvest rate of 7 lb/24 h, a 2.2 lb/24
h stability criteria could result in a harvest rate variation of up to
31 percent (i.e., 2.2 lb/24 h divided by 7 lb/24 h). Because of the
potential high variability in the stability criteria for low-capacity
ACIMs, DOE proposed in the December 2021 NOPR to not apply the absolute
stability criteria specified in ASHRAE 29-2015 to the proposed test
procedure for low-capacity ACIMs. 86 FR 72322, 72334.
DOE also considered whether applying only the 2 percent
stability criterion would be appropriate for low-capacity ACIMs. Due to
the lower overall ice harvest rates, a 2 percent stability
requirement represents much smaller weight variations for low-capacity
ACIMs. For example, a 2 percent stability requirement for the 7 lb/24 h
model represents a variation of 0.14 lb/24 h, which may be difficult to
achieve for low-capacity ACIMs.
The 2 percent stability requirement is also not
currently applicable to the lowest capacity ACIMs currently in scope
for the DOE test procedure (i.e., the requirement is 2 percent or 2.2
lb/24 h, whichever is greater). Accordingly, the effective stability
requirement for the lowest capacity ACIMs currently in scope is
approximately 4 percent (i.e., 2.2 lb/24 h divided by 50 lb/24 h). In
the December 2021 NOPR, DOE determined that applying this same
percentage (i.e., 4 percent) as the low-capacity ACIM stability
requirement would be more appropriate than applying either the 2
percent or 2.2 lb/24 h stability requirements currently defined in
section 7.1.1 of ASHRAE 29-2015. 86 FR 72322, 72334. DOE observed
through testing that low-capacity ACIMs are able to achieve stability
based on a 4 percent requirement. Id.
Therefore, for consistency (on a percentage basis) with the ASHRAE
29-2015 test requirements for the lowest capacity ACIMs currently in
scope and to limit test burden, in the December 2021 NOPR, DOE proposed
to require a 4 percent stability criterion (without an
absolute stability criterion) for testing low-capacity ACIMs. 86 FR
72322, 72334.
In the December 2021 NOPR, DOE requested comment on the proposal to
require that all cycles or samples of low-capacity ACIMs used for the
capacity test meet a 4 percent stability criterion and not
be subject to an absolute stability criterion. 86 FR 72322, 72334.
In response to the December 2021 NOPR, Hoshizaki and AHRI requested
that this proposal be brought to the ASHRAE 29 standard committee with
supporting testing to show that this stability is necessary and
adequate for these products since currently they are outside of the
scope, and that ASHRAE 29 was not developed for low-capacity ACIMs.
(Hoshizaki, No. 14, p. 3; AHRI, No. 13, p. 4-5) AHRI added that the
units should not be allowed to bypass stability requirements currently
in the standard simply because the method of test has not been designed
to incorporate such units. (AHRI, No. 13, p. 4-5) AHRI commented that
members do not currently have testing data to show that 4 percent would
be accurate or comparable for this equipment type. Id.
AHAM commented in support of the 4 percent stability
criterion for low-capacity ice makers. (AHAM, No. 18, p. 11) AHAM
stated that DOE's ACIM energy conservation standards or test procedure
need a method to account for this planned variation such that the
variation does not penalize manufacturers when the test procedure is
used for enforcement purposes. Id.
DOE observed from testing of low-capacity ACIMs to support the
December 2021 NOPR that a 4 percent stability criterion is
appropriate and ensures representative, repeatable, and reproducible
measures of performance for low-capacity ACIMs. A 4 percent
stability criterion is consistent with the absolute stability
requirements from ASHRAE 29-2015 for the lowest capacity ACIMs
currently in scope (i.e., 2.2 lb/24 h divided by 50 lb/24 h). A 4 percent stability criterion does not bypass any requirement
because low-capacity ACIMs are not currently subject to the DOE test
procedure and are not within the scope of ASHRAE 29-2009 or ASHRAE 29-
2015. DOE will consider any updated industry standards, if available,
during future ACIM test procedure rulemakings. DOE discusses
enforcement provisions for ACIMs in section III.E.3 of this final rule.
DOE is maintaining in this final rule the requirement that all
cycles or samples of low-capacity ACIMs used for the capacity test meet
a 4 percent stability criterion and not be subject to an
absolute stability criterion, consistent with the December 2021 NOPR.
3. Test Conditions
The DOE test procedure specifies standard test conditions to ensure
that test results reflect energy use during a representative average
use cycle and are not unduly burdensome for manufacturers to perform.
DOE discusses test conditions, including tolerances and
instrumentation accuracies, in the following sections.
a. Relative Humidity
Variation in the moisture content of ambient air may affect the
energy consumption of automatic commercial ice makers. However, neither
the current DOE test procedure, nor AHRI Standard 810 (I-P)-2016 with
Addendum 1 or ASHRAE Standard 29-2015 include requirements to control
for moisture content for testing. In contrast, industry test standards
for other refrigeration equipment, such as commercial refrigerators,
freezers and refrigerator-freezers (``CRE'') and refrigerated bottled
or canned beverage vending machines (``BVMs''), have requirements for
the moisture content.
In the December 2021 NOPR, DOE presented data from three ACIMs
tested at relative humidity levels of 35, 55, and 75 percent at the
standard rating conditions to investigate the effect of relative
humidity on energy use, as replicated in Table III.3. 86 FR 72322,
72335. The results showed a wide range of impacts on energy use among
the three tested units when relative humidity is varied. Id. Test Unit
1 showed less than 1 percent variation in energy use among the three
relative humidity test conditions. Id. Whereas, Test Unit 2 showed a 35
percent difference in energy use between the 35 percent and 75 percent
relative humidity test conditions. Id. Test Unit 3 showed a 4 percent
difference in energy use between the 35 percent and 75 percent relative
humidity conditions. Id. DOE stated in the December 2021 NOPR that it
was unable to determine why Test Unit 2 showed significantly greater
variation in performance compared to the other test units. Id. In
summary, these results indicated that for certain ACIM models, relative
humidity has a significant impact on measured energy use.
[[Page 65872]]
Table III.3--Comparison of Energy Use Rates at Different Relative Humidity Test Conditions as Presented in the December 2021 NOPR
--------------------------------------------------------------------------------------------------------------------------------------------------------
Difference Difference
from 35% from 35%
35% relative 55% relative humidity (kWh/ 75% relative relative relative
Test unit Type humidity (kWh/ 100 lb) humidity (kWh/ humidity to humidity to
100 lb) 100 lb) 55% relative 75% relative
humidity (%) humidity (%)
--------------------------------------------------------------------------------------------------------------------------------------------------------
1 Batch....................... 8.27 8.28....................... 8.28 +0.2 +0.2
2 Batch....................... 8.47 10.49...................... 11.47 +24 +35
3 Continuous.................. 4.27 Not Tested................. 4.43 N/A +4
--------------------------------------------------------------------------------------------------------------------------------------------------------
In the December 2021 NOPR, DOE considered relative humidity test
conditions for ACIMs by comparing the test conditions required for
testing other types of commercial food service equipment, including
CRE, BVMs, and refrigerated buffet and preparation tables. 86 FR 72322,
72335. In particular, DOE compared the moisture content level
corresponding to the combination of ambient temperature and relative
humidity specified for these other equipment types. Id. DOE summarized
these test condition requirements along with the proposed relative
humidity test condition of 35 percent for ACIMs, as replicated in Table
III.4. Id.
Table III.4--Comparison of Relative Humidity Test Conditions as Presented in the December 2021 NOPR
----------------------------------------------------------------------------------------------------------------
Corresponding
Ambient Wet Bulb Relative moisture
Equipment type Test standard temperature temperature humidity content (lbs
([deg]F) ([deg]F) (percent) water vapor/
lbs dry air)
----------------------------------------------------------------------------------------------------------------
Commercial Refrigeration ASHRAE 72- 75.2 64.4........... * 55 0.010
Equipment. 2005[dagger].
Refrigerated Beverage Vending ASHRAE 32.1- 75 No requirement. 45 0.008
Machines. 2010[dagger].
Refrigerated Buffet and ASTM Standard 86 No requirement. 35 0.009
Preparation Tables. F2143-2016.
Automatic Commercial Ice Proposed........ 90 No requirement. ** 35 0.011
Makers.
----------------------------------------------------------------------------------------------------------------
* The relative humidity for commercial refrigeration equipment is calculated from the dry bulb temperature and
the wet bulb temperature using a pressure of 760 mm of mercury.
** Proposed test condition.
[dagger] The test conditions currently incorporated by refence in the DOE test procedures are unchanged in the
most recent versions of the industry standards, ASHRAE 72-2018 and ASHRAE 32.1-2017.
Based on these considerations, DOE proposed to require a relative
humidity test condition of 35 percent for ACIM testing. 86 FR 72322,
72335. As indicated in Table III.4, the proposed relative humidity
condition of 35 percent, in combination with the ambient air condition
of 90 [deg]F, would correspond to a moisture content of 0.011 lbs water
vapor/lbs dry air. This would closely match the moisture contents
associated with the test procedures for the other types of commercial
food service equipment.
In the December 2021 NOPR, DOE also investigated appropriate
tolerances to specify for the relative humidity test condition. 86 FR
72322, 72336. DOE considered a test condition tolerance and test
operating tolerance on relative humidity. Id. A test condition
tolerance is a tolerance that is calculated based on the average of all
relative humidity measurements during each freeze cycle. Id. In
contrast, a test operating tolerance would apply to all individual
measurements during each cycle. Id. The industry standards referenced
in Table III.4, ASHRAE 72-2018, ASHRAE 32.1-2017, and ASTM Standard
F2143-2016, all require a test condition tolerance. Id. ASHRAE 72-2018
is the only standard mentioned in Table III.4 that also requires a test
operating tolerance. Id.
DOE also investigated typical accuracies of relative humidity
sensors, finding that accuracies of 2.0 percent are typical
for relative humidity sensors. Id. Additionally, DOE noted that its
test procedure for BVMs requires a relative humidity instrument
accuracy of 2.0 percent for a test condition tolerance of
5.0 percent. See section 1.1 of appendix B to subpart Q of
10 CFR part 431. Id. Similarly, section 6.3 of ASTM Standard F2143-2016
also requires a relative humidity instrument accuracy of 2.0 percent for a test condition tolerance of 5.0
percent. Id.
Based on this analysis, DOE proposed a relative humidity test
condition tolerance of 5.0 percent. Id. DOE also proposed
to require a relative humidity instrument accuracy of 2.0
percent. Id.
In summary, DOE proposed to require a relative humidity test
condition of 35 percent. 86 FR 72322, 72335. DOE proposed that the
relative humidity be maintained and measured at the same location used
to confirm ambient dry bulb temperature, or as close as the test setup
permits. 86 FR 72322, 72336. DOE proposed to add a test condition
tolerance on the proposed relative humidity test condition of 5.0 percent. Id. DOE proposed to require a relative humidity
instrument accuracy of 2.0 percent. Id. DOE stated in the
December 2021 NOPR that it did not expect the proposal to affect
measured performance of existing ACIM models. Id.
DOE requested comment on the proposal to control relative humidity
at
[[Page 65873]]
35 5.0 percent. 86 FR 72322, 72336. Specifically, DOE
requested comment on the representativeness of 35 percent relative
humidity in field use conditions, whether manufacturers currently
control and measure relative humidity for ACIM testing (and if so, the
conditions used for testing), and the burden associated with
controlling relative humidity within a tolerance of 5.0
percent. Id.
In response to the December 2021 NOPR, Hoshizaki and AHRI commented
that due to inherent humidity caused by ice makers in the production of
ice, the control of relative humidity has been left out of the test
protocols currently used (e.g., ASHRAE 29). (Hoshizaki, No. 14, p. 3;
AHRI, No. 13, p. 5) AHRI, Joint Commenters, Hoshizaki, IOM, The Legacy
Companies, and Manitowoc Ice commented that ACIMs respond differently
to the humidity of ambient air than other refrigerated equipment
because the evaporator is in a wetted setting, so units are not greatly
affected by humidity changes during testing. (AHRI, No. 13, p. 5; Joint
Commenters, No. 15, p. 1; Hoshizaki, No. 14, p. 3; IOM, No. 11, p. 2;
The Legacy Companies, January 24, 2022 webinar to discuss the December
2021 NOPR; \12\ Manitowoc Ice, January 24, 2022 webinar to discuss the
December 2021 NOPR) \13\ AHRI and added that units are designed to
handle these conditions and that humidity control is not necessary
(AHRI, No. 13, p. 5; AHAM, No. 18, p. 12).
---------------------------------------------------------------------------
\12\ See pages 30-31; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
\13\ See pages 32-33; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
IOM and The Legacy Companies commented that they do not support the
proposal to control humidity. (IOM, No. 11, p. 2; The Legacy Companies,
January 24, 2022 webinar to discuss the December 2021 NOPR) \14\ Joint
Commenters commented that ACIM test chambers typically do not control
the relative humidity of ambient air. (Joint Commenters, No. 15, p. 1)
IOM commented that they do not control for or measure humidity levels
in its environmental chambers. (IOM, No. 11, p. 2) Welbilt commented
that they do not have humidity control in their test chambers and that
ACIM test chambers are often very specialized because of the range of
ambient conditions that are needed to test ACIMs whereas CRE test
chambers are typically used for testing at one or two ambient
conditions. (Welbilt, January 24, 2022 webinar to discuss the December
2021 NOPR) \15\
---------------------------------------------------------------------------
\14\ See pages 30-31; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
\15\ See pages 29-30; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
AHRI, Hoshizaki, IOM, Joint Commenters, and Manitowoc Ice commented
that test data should be reviewed and validated to confirm the need for
relative humidity control. (AHRI, Public Meeting Transcript, No. EERE-
2017-BT-TP-0006-0012 at p. 29; Hoshizaki, No. 14, p. 3; IOM, No. 11, p.
2; Joint Commenters, No. 15, p. 1-2; Manitowoc Ice, January 24, 2022
webinar to discuss the December 2021 NOPR) \16\ AHAM commented that
DOE's testing is not sufficient to justify its proposed requirement.
AHAM, No. 18, p. 13. Joint Commenters added that DOE should conduct
additional relative humidity testing and if a large performance
difference for some units is confirmed, then a relative humidity
requirement is needed to ensure the reproducibility of the test
procedure. (Joint Commenters, No. 15, p. 1-2)
---------------------------------------------------------------------------
\16\ See pages 32-33; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
AHRI, Hoshizaki, IOM, Welbilt, and Joint Commenters commented that
a relative humidity of 35 percent may be unrepresentative of the
variety of environments housing ACIMs. (AHRI, No. 13, p. 5; Hoshizaki,
No. 14, p. 3; IOM, No. 11, p. 2; Welbilt, January 24, 2022 webinar to
discuss the December 2021 NOPR; \17\ Joint Commenters, No. 15, p. 2)
IOM added that commercial kitchens may have humidity much higher than
35 percent, front-of-house locations may be lower than 35 percent, and
ACIMs utilizing a remote condenser may see humidity anywhere between 15
and100 percent. (IOM, No. 11, p. 2)
---------------------------------------------------------------------------
\17\ See pages 29-30; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
AHRI commented that the ambient temperatures would also vary
greatly by application and such a humidity would be difficult to
control while entering the test chamber for sample collection. (AHRI,
No. 13, p. 5) IOM believes that a 5 percent tolerance is
too narrow and would be difficult to control during tests. (IOM, No.
11, p. 2) IOM suggested a 10 percent tolerance if humidity
is controlled. Id.
AHRI, IOM, and Welbilt asserted that the addition of humidity
control requirements would impose undue burden to OEMs and testing
facilities without benefiting the efficiency or testing of ACIMs.
(AHRI, No. 13, p. 5; IOM, No. 11, p. 2; Welbilt, January 24, 2022
webinar to discuss the December 2021 NOPR \18\) AHRI, IOM, and Welbilt
commented that it would also be extremely costly to add humidity
control upgrades to testing laboratories for little wielded benefit.
Id. Hoshizaki commented that full costs should be considered in adding
this to the test criteria along with the cost to retest all products
that currently do not have humidity control in their test. (Hoshizaki,
No. 14, p. 3)
---------------------------------------------------------------------------
\18\ See pages 29-30; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
Hoshizaki requested that this be addressed in the ASHRAE 29
standard committee for consensus. (Hoshizaki, No. 14, p. 3)
DOE has reviewed and confirmed the validity of the test data from
the three units presented in the December 2021 NOPR.
DOE has also conducted further analysis of the test data from Test
Unit 2 to further investigate that unit's significant variation in
energy use among the different relative humidity test conditions. DOE
notes that during the January 24, 2022 webinar to discuss the December
2021 NOPR, True Manufacturing commented in response to a request for
comment about the relative humidity test condition that some ACIMs that
have poor insulation may inadvertently make ice on the back side of the
evaporator plate or other unwanted areas, which could possibly decrease
the harvest rate.\19\ Indeed, DOE observed for Test Unit 2 that the 75
percent relative humidity test had additional drain water collected
during the freeze cycles compared to the 35 percent relative humidity
test. DOE investigated whether this additional drain water could have
resulted from additional condensation of moisture at the higher
relative humidity, and whether the higher energy use for Test Unit 2 at
the 75 percent relative humidity test condition may correspond to such
additional condensate being produced at that test condition. If so,
this would indicate that the higher energy use was directly related to
the relative humidity test condition.
---------------------------------------------------------------------------
\19\ See pages 34-35; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
Based on the technical characteristics of Test Unit 2, DOE
calculated the theoretical amount of additional energy use that would
be required by Test Unit 2 to condense the amount of additional drain
water measured.\20\ DOE compared
[[Page 65874]]
the resulting theoretical amount of additional energy use to the
measured amount of additional energy use. Table III.5 shows the average
measured drain water (in lbs) and the average measured energy use (in
kWh) of the freeze cycles for Test Unit 2. Table III.6 shows the
comparison of these measured values to the theoretical amount of
additional energy use that would be required by Test Unit 2 to condense
this amount of additional drain water, as calculated by DOE.
---------------------------------------------------------------------------
\20\ DOE calculated the additional amount of heat removal
required from the evaporator of Test Unit 2 to condense the same
amount of moisture from the surrounding air that was observed in the
additional drain water from the 75% relative humidity test.
Subsequently, DOE calculated the additional amount of compressor,
sump pump, and condenser fan motor energy and additional freeze
cycle duration that would be necessary to remove this additional
heat based on the Test Unit 2's compressor specification data at an
assumed evaporator temperature of 15 [deg]F and condenser
temperature of 115 [deg]F, and sump pump and condenser fan motor
specification data with an assumed power factor of 80%.
Table III.5--Summary of Drain Water and Energy Use Measurements for Test Unit 2
----------------------------------------------------------------------------------------------------------------
Difference
between 35%
Cycle description 35% relative 75% relative and 75%
humidity humidity relative
humidity
----------------------------------------------------------------------------------------------------------------
Freeze cycle drain water (lbs).................................. 0.59 1.01 0.43
Freeze cycle energy use (kWh)................................... 0.21 0.32 0.11
----------------------------------------------------------------------------------------------------------------
Table III.6--Comparison of Theoretical Additional Energy Use to Measured
Additional Energy Use for Test Unit 2
------------------------------------------------------------------------
Theoretical
Measured energy use
difference required to
Cycle description between 35% and produce 0.43
75% relative lbs of
humidity condensate
------------------------------------------------------------------------
Freeze cycle energy use (kWh)......... 0.11 0.12
------------------------------------------------------------------------
As indicated in Table III.6, DOE's calculated approach to determine
the additional energy use required to condense the amount of additional
drain water measured closely matched the measured approach. This
indicates that the additional energy use at the 75 percent relative
humidity test condition was likely due to the difference in condensed
moisture accumulated at the 75 percent test condition, thus supporting
that the relative humidity level during the test may have a direct
impact on measured energy performance.
DOE also evaluated additional test data from previous investigative
ACIM testing to further confirm the effects of relative humidity on
measured energy use. DOE previously tested four batch style ACIMs at 55
and 75 percent relative humidity using the standard rating conditions
specified in AHRI 810. Although this testing was not conducted at 35
percent relative humidity, the test data is instructive on whether a
difference in relative humidity affects ACIM performance. Table III.7
summarizes the results of this previous testing.
Table III.7--Comparison of Energy Use Rates at Different Relative Humidity Test Conditions
----------------------------------------------------------------------------------------------------------------
Difference
from 55%
55% relative 75% relative relative
Test unit Type humidity (kWh/ humidity (kWh/ humidity to
100 lb) 100 lb) 75% relative
humidity (%)
----------------------------------------------------------------------------------------------------------------
4 Batch......................... 9.45 9.30 -1.6
5 Batch......................... 17.47 21.58 +23.5
6 Batch......................... 30.33 30.56 +0.8
7 Batch......................... 40.46 40.49 +0.1
----------------------------------------------------------------------------------------------------------------
These results show that for some ACIM models, a difference in
relative humidity makes very little impact on ACIM performance, but for
other models, a difference in relative humidity makes a significant
impact on ACIM performance. Considering the three tested units
presented in the December 2021 NOPR in addition to these four units,
out of a total test sample of 7 ACIMs, relative humidity had a
significant impact on ACIM performance for at least two ACIMs. This
suggests that a difference in relative humidity may affect a
substantial portion of the ACIM market.
As summarized previously in this section, comments received in
response to the December 2021 NOPR indicate that certain manufacturers
do not measure relative humidity of the ambient air during testing, and
that ACIM test chambers typically do not control the relative humidity
of the ambient air. Commenters also generally suggested defining a
broader tolerance as compared to the proposed tolerance of 5 percent, asserting that controlling relative humidity to within
5 percent during testing would be difficult.
Based on the additional analysis discussed in this final rule,
including consideration of comments received in
[[Page 65875]]
response to the December 2021 NOPR, DOE is modifying the relative
humidity test conditions adopted in this final rule, as compared to the
provisions as proposed in the December 2021 NOPR, to instead specify a
minimum threshold rather than a defined range. Specifically, this final
rule adopts a requirement to maintain an average minimum ambient
relative humidity of 30.0 percent throughout testing. This revised
specification represents the minimum of the relative humidity
tolerance, 35.0 5.0 percent, as proposed in the December
2021 NOPR and will allow for a broader range of relative humidity
values that will be easier to control during testing. Furthermore, DOE
notes that its test data indicated that higher humidity levels are
associated with higher measured energy use for certain ACIM models--
suggesting that manufacturers of such models will be incentivized to
test with relative humidity levels as close to the minimum defined
threshold as possible.
See section III.F.1 of this final rule for a discussion of DOE's
analysis of any expected costs or impacts on measured performance as a
result of this amendment.
b. Water Hardness
ASHRAE Standard 29-2015 and AHRI Standard 810 (I-P)-2016 with
Addendum 1 do not specify the water hardness of the water supply used
for testing. The United States Geological Survey (``USGS'') defines
water hardness as the concentration of calcium carbonate in milligrams
per liter (``mg/L'') of water and lists general guidelines for the
classification of water hardness as 0 to 60 mg/L of calcium carbonate
for soft water; 61 to 120 mg/L of calcium carbonate for moderately hard
water; 121 to 180 mg/L of calcium carbonate for hard water; and more
than 180 mg/L of calcium carbonate for very hard water.\21\ In the
January 2012 final rule, DOE stated that harder water depresses the
freezing temperature of water and results in increased energy use to
produce the same quantity of ice. 77 FR 1591, 1605. DOE also stated
that hard water (i.e., water with a higher concentration of calcium
carbonate) can affect energy consumption in the field due to increased
scale build up on the heat exchanger surfaces over time, and the use of
higher water purge quantities to help flush out dissolved solids to
limit scale build up. Id. However, DOE declined to set requirements for
water hardness for testing because of insufficient information to allow
proper consideration of such a requirement. 77 FR 1591, 1605-1606.
Specifically, DOE did not have information regarding the impact of
variation in water hardness on as-tested performance of ACIMs, and
therefore could not justify the additional burden associated with
establishing a standardized water hardness requirement at that time.
Id.
---------------------------------------------------------------------------
\21\ See www.usgs.gov/special-topic/water-science-school/science/hardness-water?qt-science_center_objects=0#qt-science_center_objectswater.usgs.gov/owq/hardness-alkalinity.html.
---------------------------------------------------------------------------
As part of this rulemaking, DOE conducted testing to investigate
whether changing the water hardness could affect the energy consumption
and harvest rate of ACIMs. Testing was conducted on new models (i.e.,
with clean evaporators prior to accumulation of any significant scale).
DOE conducted water hardness tests on three batch type ice makers and
one continuous type ice maker.
According to the USGS, the vast majority of water hardness in the
United States ranges from 0 mg/L to 250 mg/L of calcium carbonate.\22\
Given the range of water hardness in the United States, DOE used a
water hardness of 42 mg/L of calcium carbonate for a ``soft water''
test (which also represented water readily available at the test
facility) and a water hardness of 342 mg/L of calcium carbonate for a
``very hard water'' test (i.e., a 300 mg/L increase relative to the
soft water test to represent an extreme comparison case). The ``soft
water'' test at 42 mg/L of calcium carbonate was based on the water
hardness of the potable water at the testing facility where the tests
were conducted and therefore no additional preparation of the potable
water was required to meet the 42 mg/L of calcium carbonate water
hardness level. The ``very hard water'' test at 342 mg/L of calcium
carbonate was prepared by adding calcium chloride and magnesium
chloride hexahydrate with a mass ratio of 304:139 to the potable water
at the testing facility to reach the water hardness level of 342 mg/L
of calcium carbonate and the resulting mixture was recirculated for
sixteen hours to ensure even mixing. DOE tested four ACIMs in a test
chamber with soft and very hard water hardness at the standard rating
conditions to investigate the effect of water hardness on harvest rate
and energy use. The results of these tests are summarized in Table
III.8.
---------------------------------------------------------------------------
\22\ See www.usgs.gov/media/images/map-water-hardness-united-states.
Table III.8--ACIM Performance Differences of Soft Water Compared to Very Hard Water
--------------------------------------------------------------------------------------------------------------------------------------------------------
Harvest rate Harvest rate Energy use Energy use
Unit Type with soft with very hard Difference (%) with soft with very hard Difference (%)
water * water * water * water *
--------------------------------------------------------------------------------------------------------------------------------------------------------
1 Batch..................... 95 105 11 10.49 9.43 -10.1
2 Batch..................... 126 131 4 8.28 7.96 -3.9
3 Batch..................... 351 359 2.3 5.73 5.64 -1.6
4 Continuous................ 562 582 3.4 4.40 4.18 -5.0
--------------------------------------------------------------------------------------------------------------------------------------------------------
These test results show that water hardness can impact measured
harvest rates and energy consumption rates, and that very hard water
generally resulted in more favorable performance than soft water. DOE
acknowledges that the observed test results show the opposite impact on
performance than expected and discussed in the January 2012 final rule
(i.e., that harder water would be expected to increase energy
consumption).
In the December 2021 NOPR, DOE proposed to require that water used
for testing have a maximum hardness of 180 mg/L of calcium carbonate.
86 FR 72322, 72337. DOE stated that establishing a maximum water
hardness of 180 mg/L would ensure that ACIMs are tested with water that
is not considered ``very hard'' according to the USGS and that the
tested water hardness is within a range representative of water
hardness that ACIMs are likely to experience in actual use. Id.
In the December 2021 NOPR, DOE proposed that water hardness must be
measured using a water hardness meter with an accuracy of 10 mg/L or taken from the most recent version of the water
quality report that is sent by water suppliers, which is updated at
least annually and is accessible at: ofmpub.epa.gov/apex/safewater/f?p=136:102. 86 FR 72322, 72337. DOE
[[Page 65876]]
expected that any test facilities in locations with water supply
hardness greater than 180 mg/L would likely already incorporate water
softening controls, and therefore this proposal is not expected to
require updates to existing test facilities. Id. For this same reason,
DOE did not expect that this proposal would impact rated performance
for any ACIMs tested under the current DOE test procedure. Id.
In the December 2021 NOPR, DOE also noted that this proposal would
not conflict with any provisions of the industry test and rating
standards and would provide additional specifications to ensure the
representativeness of the results and improve the repeatability and
reproducibility of the test results. 86 FR 72322, 72337.
In the December 2021 NOPR, DOE requested comment on its proposal
that water used for ACIM testing have a maximum water hardness of 180
mg/L of calcium carbonate and on whether any test facilities would not
have water hardness supplied within the proposed allowable range. 86 FR
72322, 72337. DOE requested comment on whether the supply water is
softened when testing ACIMs and, if the water is not softened, the
burden associated with implementing controls for water hardness. 86 FR
72322, 72337-72338. Additionally, DOE requested information on whether
this requirement should only be applicable to potable water used to
make ice (and not any condenser cooling water). 86 FR 72322, 72338.
In response to the December 2021 NOPR, Hoshizaki agreed that water
hardness would be good to investigate for the test standard.
(Hoshizaki, No. 14, p. 4) However, Hoshizaki and AHRI requested that
water hardness be brought to the ASHRAE 29 committee for consideration.
(Hoshizaki, No. 14, p. 4; AHRI, No. 14, p. 5)
Joint Commenters supported DOE's proposal to introduce a water
hardness requirement to improve the reproducibility of the test
procedure. (Joint Commenters, No. 15, p. 2) The Joint Commenters added
that since the hardness of tap water varies throughout the U.S., DOE's
proposal to establish a water hardness condition will likely increase
the reproducibility of the test procedure, and therefore stated support
for DOE's proposal to establish a maximum water hardness for testing of
180 mg/L, which will exclude very hard water. Id.
AHRI commented that different regions experience hard water that
can consistently exceed 180 mg/L, so this issue would need to be
evaluated across regions to ensure that undue burden is not being
unfairly inflicted on specific areas of the country. (AHRI, No. 14, p.
5) During the January 24, 2022 ACIM test procedure public meeting, True
Manufacturing commented that their test facilities have potable water
that is approximately 300 mg/L all year long.\23\
---------------------------------------------------------------------------
\23\ See page 40; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
IOM commented that although DOE's test data showed that harvest
rate increases and energy use decreases when increasing calcium
carbonate concentration, DOE does not provide any details on the
characteristics of their test water besides calcium carbonate
concentration. (IOM, No. 11, p. 2) If the ``very soft'' water was
created by softening the ``very hard'' sample water using a salt-based
ion-exchange water softener, the total dissolved solids (TDS) of the
test water would remain the same, as ion-exchange systems simply
replace calcium and magnesium with sodium chloride. Id. The act of
softening ``very hard'' water creates a high salinity solution which
might affect the freezing point of water, causing the diminished
performance seen with ``very soft'' water. Id.
IOM commented the only way to reliably supply consistent test water
to IOM's laboratory with specifications around calcium carbonate
concentration would be to implement reverse osmosis systems, which are
costly to install and maintain, and consume a significant amount of
energy during use. (IOM, No. 11, p. 2)
IOM requested that if DOE were to implement this rule, it should
only be applicable to the potable water used to make ice, unless DOE is
able to demonstrate that hardness has an effect on energy consumption
in water-cooled ACIMs. (IOM, No. 11, p. 2)
Comments from interested parties indicated that some ACIM test
facilities have potable water with water hardness above of 180 mg/L of
calcium carbonate and that softening or controlling the water hardness
would impose a burden on certain manufacturers. DOE acknowledges that
DOE's expectation in the December 2021 NOPR that any test facilities in
locations with water supply hardness greater than 180 mg/L would likely
already incorporate water softening controls was incorrect and
therefore, updates to certain existing test facilities would be needed
to control for water hardness. Although the USGS designates water
hardness above of 180 mg/L of calcium carbonate as very hard water, DOE
has determined that further investigation is necessary before
establishing a water hardness test condition and is declining to
specify a water hardness range for ACIM testing in this final rule. DOE
notes that because a specific water hardness range is not specified,
all water hardness levels will be considered valid for ACIM testing.
c. Ambient Temperature Gradient
The current ACIM test procedure incorporates by reference section
5.1.1 of ASHRAE Standard 29-2009, which stipulates that, with the ice
maker at rest, the vertical ambient temperature gradient in any foot of
vertical distance from 2 inches above the floor or supporting platform
to a height of 7 feet above the floor, or to a height of 1 foot above
the top of the ice maker cabinet, whichever is greater, shall not
exceed 0.5 [deg]F/foot. This language, which is consistent with the
requirement in section 5.1.1 of ASHRAE Standard 29-2015, is consistent
with the test room requirements for residential refrigerators, as
specified in section 7.2 of ANSI-AHAM Standard HRF-1-1979, ``Household
Refrigerators, Combination Refrigerator-Freezers, and Household
Freezers'' (ANSI/AHAM HRF-1-1979), the version of the AHAM standard
that was incorporated by reference in the DOE test procedure for
residential refrigerators in a final rule published August 10, 1982. 47
FR 34517. DOE modified the requirements associated with temperature
gradient for residential refrigerators, in a final rule published April
21, 2014, to remove the reference to a 7 feet height requirement and
require only that the gradient be maintained to a height 1 foot higher
than the top of the unit. 79 FR 22320, 22335.
In the December 2021 NOPR, DOE did not propose any changes to the
ambient temperature gradient requirements, except through an updated
reference to ASHRAE Standard 29-2015, and requested comment on this
approach and on whether any modifications would improve test accuracy
or decrease test burden. 86 FR 72322, 72338.
In response to the December 2021 NOPR, Hoshizaki commented that if
ASHRAE 29-2015 is adopted, it supports use of the ambient temperature
gradient requirements in that edition. (Hoshizaki, No. 14, p. 4) AHRI
agreed with the adoption of ASHRAE Standard 29-2015 and its gradient
requirements. (AHRI, No. 13, p. 5)
DOE is maintaining in this final rule the existing ambient
temperature gradient requirements, through an updated reference to
ASHRAE Standard 29-2015.
[[Page 65877]]
d. Ambient Temperature and Water Temperature
The current DOE ACIM test procedure incorporates by reference AHRI
810-2007, which specifies an ambient temperature of 90 [deg]F and a
supply water temperature of 70 [deg]F. AHRI Standard 810 (I-P)-2016
with Addendum 1 provides the same specifications. However, many ice
makers may be installed in conditioned environments such as offices,
schools, hospitals, hotels, and convenience stores (see 80 FR 4646,
4700 (Jan. 28, 2015)), which may have ambient air temperatures and
supply water temperatures higher or lower than those specified in AHRI
Standard 810.
In the December 2021 NOPR, DOE proposed to maintain the single set
of rating conditions currently required in the DOE test procedure. 86
FR 72322,72338. Specifically, DOE proposed to maintain the reference to
AHRI Standard 810, through AHRI Standard 810 (I-P)-2016 with Addendum
1, for rating conditions because those were selected as representative,
repeatable rating conditions of this equipment. Id. As noted, EPCA
requires that if AHRI Standard 810 is amended, DOE must amend the test
procedures for ACIM as necessary to be consistent with the amended AHRI
test standard, unless DOE determines, by rule, published in the Federal
Register and supported by clear and convincing evidence, that to do so
would not meet the requirements for test procedures regarding
representativeness and test burden. (42 U.S.C. 6314(7)(B)) DOE does not
have any contrary data or information regarding the representativeness
of the conditions specified in AHRI Standard 810 (I-P)-2016 with
Addendum 1.
In addition, the response of ACIM refrigeration systems to varying
ambient conditions is different than the response of refrigeration
systems in other refrigeration and heating, ventilation, and air-
conditioning (``HVAC'') equipment. Other refrigeration or HVAC
equipment are typically designed to maintain conditions within a space.
Accordingly, as ambient conditions change, the refrigeration systems
typically cycle (or in the case of variable-speed compressors, adjust
speed) to match the varying heat loads. In the case of ACIMs, the
refrigeration system continuously operates while actively making ice,
as heat is constantly removed from the water throughout the freezing
process. As a result, introducing a second lower-temperature test
condition would not result in part-load operation for ACIMs and would
not additionally differentiate between units based on a part-load
response, as is the case for other refrigeration or HVAC equipment.
Thus, in the December 2021 NOPR, DOE tentatively determined that the
existing test conditions provide representative, repeatable rating
conditions for this equipment, and DOE expected that the burden of
introducing a second test condition (which would approximately double
test duration) would not be justified. 86 FR 72322,72339.
In the December 2021 NOPR, DOE requested comment on its proposal to
maintain the existing ambient temperature and water supply temperature
requirements. If modifications should be considered to improve test
representativeness or decrease test burden, DOE requested supporting
data and information. 86 FR 72322,72339.
In response to the December 2021 NOPR, AHRI commented that the
current 90 [deg]F ambient temperature (which includes 90 [deg]F for
both the indoor ambient temperature and the condenser air inlet
temperature for ACIMs with remote condensing units) and 70 [deg]F water
inlet temperature test conditions are representative for much of the
installed base. (AHRI, No. 13, p. 6) AHRI stated that changing the test
point would disrupt historical data and understanding of the
performance of the equipment, for both manufacturers and consumers.
(Id.) Hoshizaki stated that the existing ambient temperature and water
supply temperature requirements provide representative, repeatable
rating conditions for this equipment. (Hoshizaki, No. 14, p. 4)
AHAM commented that the 90 [deg]F ambient temperature is applicable
to commercial settings but not residential settings and that any
measured energy use at a 90 [deg]F ambient temperature is not
representative of real-world use because most residential ice makers
are installed in air-conditioned spaces with ambient temperature closer
to 70 [deg]F. (AHAM, No. 18, p. 10) AHAM clarified that they are not
suggesting that DOE lower the proposed ambient temperature because most
of the test chambers used for residential ice maker manufacturers are
set to 90 [deg]F because that is the test condition required for other
refrigeration products. Id. AHAM stated that a second ambient condition
would create undue burden through additional resource, personnel, and
time requirements for testing. Id.
DOE is maintaining in this final rule the existing ambient
temperature and water supply temperature requirements.
e. Water Pressure
As discussed in section III.C and shown in Table III.2, ASHRAE
Standard 29-2015 now includes water pressure measurement requirements,
whereas ASHRAE Standard 29-2009 did not address water pressure. Section
6.3 of ASHRAE Standard 29-2015 directs that the pressure of the supply
water be measured within 8 inches of the ACIM and that the pressure
remains within the specified range (AHRI Standard 810-2007 and 2016
both specify 30 3 psig water supply) during the period of
time that water is flowing into the ACIM inlet(s).
Certain ACIMs do not continuously draw water into the unit during
the entire test. The portions of the test when the water inlet valve
begins to open may result in a short, transient state when the water
pressure falls outside of the allowable tolerance. Eliminating such
transient periods would likely require certain laboratories to re-
configure their water supply setups. Because of this burden and the
relatively low impact of these transient periods on water consumed
(i.e., the transient periods are typically very short relative to the
overall duration of water flow), in the December 2021 NOPR, DOE
proposed to allow for water pressure to be outside of the specified
tolerance for a short period of time when water begins flowing into the
unit. 86 FR 72322, 72339.
Section 2.4 of the DOE test procedure for consumer dishwashers
addresses this same issue by requiring that the specified water
pressure be achieved within 2 seconds of opening the water supply
valve. 10 CFR part 430, subpart B, appendix C1. The sampling rate in
section 5.7 of ASHRAE Standard 29-2015 requires a maximum interval
between data samples for water pressure of no more than 5 seconds.
Therefore, in the December 2021 NOPR, DOE proposed to clarify that
water pressure, when water is flowing into the ice maker, must be
within the allowable range within 5 seconds of opening the water supply
valve. 86 FR 72322, 72339. DOE did not expect that this proposal would
impact tested performance under the current DOE test procedure as it
provides additional specificity regarding the existing water pressure
requirements. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
require that water pressure when water is flowing into the ice maker be
within the allowable range within 5 seconds of opening the water supply
valve. 86 FR 72322, 72339.
In response to the December 2021 NOPR, IOM supported DOE's proposal
[[Page 65878]]
to allow 5 seconds after opening the water supply valve for water
pressure to be in the allowable range. (IOM, No. 11, p. 3) Hoshizaki
and AHRI commented they see the benefit to having an allowable range
for water supply pressure but requests this be addressed by the ASHRAE
29 standard committee to ensure a consensus of the committee to change
such requirements. (Hoshizaki, No. 14, p. 4; AHRI, No. 13, p. 6)
AHAM commented that the maximum five second sampling rate for water
pressure is unnecessary, impractical, burdensome, and adds difficulty
and complexity to the test procedure. (AHAM, No. 18, p. 12) AHAM
commented that energy measurement only needs a timestamp and Watt-hour
reading at the beginning and end of the test and that the intermediate
scans check for ambient and gradient temperatures which can have a
sampling rate of 30 seconds to one minute which is similar to the test
procedure for refrigeration products.\24\ Id. The sampling rate
proposed in the December 2021 NOPR is consistent with the industry test
standard requirements. DOE has determined that the industry standard
approach is appropriate because ACIMs typically have a shorter overall
test duration as compared to other refrigeration products, and for
batch type ACIMs, the water fills may represent only a portion of the
test period. Therefore, the more frequent sampling interval is
appropriate to ensure the required water pressure is maintained
throughout the water fill period, except for within the initial 5
seconds after opening the water supply valve.
---------------------------------------------------------------------------
\24\ See 10 CFR part 430, subpart B, appendices A and B.
---------------------------------------------------------------------------
DOE is maintaining in this final rule the requirement that water
pressure, when water is flowing into the ice maker, be within the
allowable range within 5 seconds of opening the water supply valve,
consistent with the December 2021 NOPR.
4. Test Setup and Equipment Configurations
Since publication of the January 2012 final rule, DOE has issued
two final guidance documents addressing certain aspects of the ACIM
test procedure: prohibiting the use of temporary baffles and requiring
use of a fixed purge water setting. As discussed in the following
paragraphs, DOE has reviewed the guidance documents to determine
whether they should be maintained and expressly included in the test
procedure. In addition, in reviewing the existing DOE ACIM test
procedure, DOE has determined that the representativeness and
repeatability of the test procedure could be further improved through
certain test setup and equipment configuration amendments as discussed
in the following paragraphs.
a. Temporary Baffles
After publication of the January 2012 final rule, DOE issued a
guidance document on September 24, 2013, regarding the use of temporary
baffles during testing.\25\ As described in the guidance, a baffle is a
partition, usually made of a flat material such as cardboard, plastic,
or sheet metal, that reduces or prevents recirculation of warm air from
an ice maker's air outlet to its air inlet, or, for remote condensers,
from the condenser's air outlet to its inlet. Temporary baffles refer
to those installed only temporarily during testing and are not part of
the ACIM model as distributed in commerce or installed in the field.
During testing, the use of temporary baffles can block recirculation of
warm condenser discharge air to the air inlet. This would reduce the
average temperature of the air entering the inlet, which would result
in lower energy use that would not be representative of the energy use
of the unit as operated by the end user.
---------------------------------------------------------------------------
\25\ See www1.eere.energy.gov/buildings/appliance_standards/pdfs/acim_baffles_faq_2013-9-24final.pdf.
---------------------------------------------------------------------------
In the guidance document, DOE expressly stated that installing such
temporary baffles is inconsistent with the ACIM test procedure, which
states that the unit must be ``set up for testing according to the
manufacturer's written instruction provided with the unit'' and that
``no adjustments of any kind shall be made to the test unit prior to or
during the test that would affect the ice capacity, energy usage, or
water usage of the test sample.'' \26\ Therefore, DOE's final guidance
stated that the use of baffles to prevent recirculation of air between
the air outlet and inlet of the ice maker during testing is not
consistent with the DOE test procedure for automatic commercial ice
makers, unless the baffle is (a) a part of the ice maker or (b) shipped
with the ice maker to be installed according to the manufacturer's
installation instructions.
---------------------------------------------------------------------------
\26\ Section 4.1.4, ``Test Set Up,'' of AHRI Standard 810-2007
and AHRI Standard 810 (I-P)-2016 with Addendum 1.
---------------------------------------------------------------------------
Based on the final guidance document, DOE proposed in the December
2021 NOPR to define the term ``baffle'' consistent with the description
in the guidance document and to expressly prohibit the use of baffles
when testing of ACIMs unless the baffle is (a) a part of the ice maker
or (b) shipped with the ice maker to be installed according to the
manufacturer's installation instructions. 86 FR 72322, 72340. In the
December 2021 NOPR, DOE stated the proposed approach based on
manufacturer installation instruction is likely how an ice maker would
be installed during use and is most representative of the energy use of
ACIMs operated in the field. Id. DOE added that this proposal would not
add any burden or impact measured performance compared to the existing
test procedure, as it is consistent with how the test procedure
currently must be performed. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
expressly provide that a baffle must not be used when testing ACIMs
unless the baffle is (a) a part of the ice maker or (b) shipped with
the ice maker to be installed according to the manufacturer's
installation instructions. 86 FR 72322, 72340.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
that the unit should be installed in accordance with the manufacturer's
installation instructions, and that baffles should only be used if
instructed to do so in installation instructions. (Hoshizaki, No. 14,
p. 4; AHRI, No. 13, p. 6)
AHAM commented that DOE's proposal to expressly provide that a
baffle must not be used when testing ACIMs unless the baffle is (a) a
part of the ice maker or (b) shipped with the ice maker to be installed
according to the manufacturer's installation instructions fails to
account for the differences between built-in and freestanding ice
makers (i.e., built-in products must be counter depth to be
incorporated into kitchen designs and be flush with cabinetry). (AHAM,
No. 18, p. 12) AHAM commented that applying the test as written may
penalize manufacturers of built-in products, as it is not
representative of their real-world use. Id.
The proposal to expressly provide that a baffle must not be used
when testing ACIMs unless the baffle is (a) a part of the ice maker or
(b) shipped with the ice maker to be installed according to the
manufacturer's installation instructions is representative because a
baffle is permitted to be used in testing if it is integral to the ice
maker or shipped with the ice maker and instructed to be installed in
the manufacturer's installation instructions. Regarding other
installation requirements, DOE provides a
[[Page 65879]]
discussion of clearances in section III.D.4.c of this final rule.
DOE is maintaining in this final rule the requirement that a baffle
must not be used when testing ACIMs unless the baffle is (a) a part of
the ice maker or (b) shipped with the ice maker to be installed
according to the manufacturer's installation instructions, consistent
with the December 2021 NOPR.
The guidance document issued by DOE on September 24, 2013, also
acknowledged that warm air discharged from an ice maker's outlet can
affect the ambient air temperature measurement such that it fluctuates
outside the maximum allowed 1 [deg]F or 2
[deg]F range, and that baffles can prevent such fluctuation. Because
temporary baffles are not permitted for use during testing, DOE stated
in the guidance document that if the ambient air temperature
fluctuations cannot be maintained within the required tolerances,
temperature measuring devices may be shielded so that the indicated
temperature will not be affected by the intermittent passing of warm
discharge air at the measurement location. DOE also stated that the
shields must not block recirculation of the warm discharge air into the
condenser or ice maker inlet.
Based on the final guidance document, in the December 2021 NOPR,
DOE proposed to specify in the test procedure that if the ambient air
temperature fluctuations (and relative humidity as discussed in section
III.D.3.a) cannot be maintained within the required tolerances,
temperature measuring devices (and relative humidity measuring devices)
may be shielded to limit the impact of intermittent passing of warm
discharge air at the measurement locations. 86 FR 72322, 72340. DOE
further proposed that if shields are used, they must not block
recirculation of the warm discharge air into the condenser or ice maker
inlet. Id. DOE did not expect this proposal to impact measured ACIM
performance compared to the existing test procedure, as it is
consistent with the existing test approach. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
specify that temperature measuring devices may be shielded to limit the
impact of intermittent warm discharge air at the measurement locations
and that if shields are used, they must not block recirculation of the
warm discharge air into the condenser or ice maker air inlet. 86 FR
72322, 72340.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
with DOE's proposal to specify that temperature measuring devices may
be shielded to limit the impact of intermittent warm discharge air at
the measurement locations. (Hoshizaki, No. 14, p. 4; AHRI, No. 13, p.
6) However, Hoshizaki requested that this be addressed in the ASHRAE 29
standard committee. (Hoshizaki, No. 14, p. 4)
DOE is maintaining in this final rule the requirement that
temperature and relative humidity measuring devices may be shielded to
limit the impact of intermittent warm discharge air at the measurement
locations and that if shields are used, they must not block
recirculation of the warm discharge air into the condenser or ice maker
air inlet, consistent with the December 2021 NOPR.
In the December 2021 NOPR, DOE also requested comment on whether
any ACIM models discharge air such that the temperature and relative
humidity measuring devices would be unable to maintain the required
ambient air temperature or relative humidity tolerances even with the
measuring devices shielded. 86 FR 72322, 72340. If so, DOE requested
comment on whether alternate ambient air temperature and relative
humidity measurement locations would be necessary (e.g., the ambient
temperature measurement locations for water-cooled ice makers, if those
locations are not affected by condenser discharge air) and if the
ambient air temperature and relative humidity measured at the alternate
locations should be within the same tolerances as would otherwise be
required. Id.
In response to the December 2021 NOPR, Hoshizaki and AHRI commented
that they are not aware of a need for alternate ambient temperature
locations. (Hoshizaki, No. 14, p. 4; AHRI, No. 13, p. 6)
Based on comments from interested parties that alternate ambient
air temperature and relative humidity measurement locations are not
necessary, DOE is maintaining the current ambient measurement locations
for ACIM testing in this final rule, except as discussed in section
III.D.4.d.
b. Purge Settings
Purge water refers to water that is introduced into the ice maker
during an ice-making cycle to flush dissolved solids out of the ice
maker and prevent scale buildup on the ice maker's wetted surfaces. Ice
makers generally allow for setting the purge water controls to provide
different amounts of purge water or different frequencies of purge
cycles. Different amounts of purge water may be appropriate for
different levels of water hardness or contaminants in the ACIM water
supply. Most ice makers have manually set purge settings that provide a
fixed amount of purge water, but some ice makers include an automatic
purge water control setting that automatically adjusts the purge water
quantity based on the supply water hardness.
Because purge water is cooled by the ice maker, allowing a
different purge water quantity will result in a different measured
energy use. To ensure representative and consistent test results for
ice makers with automatic purge water controls, on September 25, 2013,
DOE issued final guidance stating that ice makers with automatic purge
water control should be tested using a fixed purge water setting that
is described in the written instructions shipped with the unit as being
appropriate for water of normal, typical, or average hardness.\27\ DOE
further stated that the automatic purge setting should not be used for
testing.
---------------------------------------------------------------------------
\27\ See www1.eere.energy.gov/buildings/appliance_standards/pdfs/acim_purge_faq_2013-9-25final.pdf.
---------------------------------------------------------------------------
Consistent with DOE's existing guidance, in the December 2021 NOPR,
DOE proposed that ice makers with automatic purge water control must be
tested using a fixed purge water setting that is described in the
manufacturer's written instructions shipped with the unit as being
appropriate for water of normal, typical, or average hardness. 86 FR
72322, 72341. Such a control setting is likely to reflect the most
typical ACIM installation and operation. Any other automatic purge
controls (i.e., those without any user-controllable settings) would
operate as they would during normal use. Additionally, while ACIMs may
be installed and set up by service technicians based on the
installation location, such setup is not appropriate for testing
because it may introduce variability in test settings based on the test
facility location. Consistent with DOE's existing guidance, DOE also
proposed that purge water settings described in the instructions as
suitable for use only with water that has higher or lower than normal
hardness (such as distilled water or reverse osmosis water) must not be
used for testing. Id.
DOE stated that this proposal would not conflict with any of the
setup or installation requirements in AHRI Standard 810 (I-P)-2016 with
Addendum 1. 86 FR 72322, 72341. Additionally, this proposal would not
add burden to manufacturers or impact ACIM performance as measured
under the existing test procedure, as it would codify the final
guidance document issued on September 25, 2013,
[[Page 65880]]
specifying use of a fixed purge setting. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
require ACIMs with automatic purge water control to be tested using a
fixed purge water setting that is described in the manufacturer's
written instructions shipped with the unit as being appropriate for
water of normal, typical, or average hardness. 86 FR 72322, 72342.
In response to the December 2021 NOPR, Hoshizaki and AHRI requested
that units be tested per normal operating instructions in accordance
with manufacturer installation instructions. (Hoshizaki, No. 14, p. 5;
AHRI, No. 13, p. 7)
DOE is maintaining in this final rule the requirement that ACIMs
with automatic purge water control be tested using a fixed purge water
setting that is described in the manufacturer's written instructions
shipped with the unit as being appropriate for water of normal,
typical, or average hardness, consistent with the December 2021 NOPR.
In support of the December 2021 NOPR, DOE conducted testing to
investigate the energy and water consumption associated with flush or
purge cycles. 86 FR 72322, 72341. DOE testing of a batch ACIM showed
that the purge occurred once every 5 hours under the default setting
and coincided with the start of a harvest, resulting in no separate
purge cycle. Id. Table III.9 summarizes how a purge cycle contributes
to the energy and water consumption of a continuous ACIM. Id. Table
III.10 presents DOE's estimates of the test durations under the
existing test approach and under an approach that would account for
purge operation. Id.
Table III.9--Summary of Energy & Water Consumption of a Continuous ACIM With Purge Cycle
----------------------------------------------------------------------------------------------------------------
Energy
Mode Average power consumption Average water
draw (W) (kWh) usage (lbs)
----------------------------------------------------------------------------------------------------------------
Ice Production.................................................. 936 11.23 * 275
Purge (every 12 hours by default)............................... 35 0.01 2.0
Recovery after Purge............................................ 1,062 0.08 N/A
----------------------------------------------------------------------------------------------------------------
* This number represents the harvest weight during the associated operating period. The total amount of water
used may be higher.
N/A: The water used during the recovery after purge does not differ from normal ice production.
Table III.10--Summary of Estimated Test Durations With and Without Including Purge Cycles
----------------------------------------------------------------------------------------------------------------
Duration (hours)
---------------------------------------------------------------
Existing ice Existing test Ice
Test unit production total production Test total
test (without (without test (with (with purge)
purge) purge) purge)
----------------------------------------------------------------------------------------------------------------
Continuous...................................... 2 8 12.5 18.5
Batch........................................... 2 8 5.5 11.5
----------------------------------------------------------------------------------------------------------------
DOE observed that purge cycles for both batch and continuous ACIMs
did not significantly contribute to the energy consumption over a
period of normal operation.
Accounting for purge cycle operation would require extending the
test period to capture both stable ice production and normal purge
operation.
The energy and water consumption during the flush or purge cycles
are very small relative to the energy and water consumed during normal
ice production, and the additional test burden associated with
measuring purge events would be a significant increase in test burden.
Therefore, in the December 2021 NOPR, DOE did not propose to address
flush or purge cycles in its test procedure. 86 FR 72322, 72342.
In the December 2021 NOPR, DOE requested comment on its initial
determination to not directly account for energy or water used during
intermittent flush or purge cycles. 86 FR 72322, 72342. DOE also
requested data regarding the energy and water use impacts of purge
cycles. Id.
In response to the December 2021 NOPR, Hoshizaki agreed with DOE
that the test should not be changed to account for intermittent flush
or purge cycles. (Hoshizaki, No. 14, p. 5) Hoshizaki added that
accounting for purge cycles would require a significant increase in
total test time, resulting in significant increase in test burden with
only a small amount of energy and water contribution. (Hoshizaki, No.
14, p. 5) During the January 24, 2022 ACIM test procedure public
meeting, Hoshizaki stated that for continuous ACIMs, a normal purge
cycle contains less than five ounces of water and occurs once every 12
hours.\28\
---------------------------------------------------------------------------
\28\ See page 47; www.regulations.gov/document/EERE-2017-BT-TP-0006-0012.
---------------------------------------------------------------------------
Joint Commenters stated that DOE may have underestimated the
frequency of purge cycles, citing the DOE's test of a batch type ACIM
with a default purge setting of a purge every 5 hours (coinciding with
the start of a harvest, resulting in no separate purge cycle). (Joint
Commenters, No. 15, p. 2) However, Joint Commenters added that for
batch type ACIMs, the purge water setting used in the field may differ
from that in the manufacturer's instructions or default settings and
may be set such that a separate purge cycle occurs as frequently as
every batch cycle. Id. Joint Commenters encouraged DOE to investigate
how the purge cycle settings in field installations may differ from the
manufacturer default settings for ACIMs and to consider capturing the
purge cycle energy in the test procedures. Id.
DOE is not aware of and did not receive any data to indicate how
purge water settings used in the field may differ from that in the
manufacturer's instructions or default settings. However, if a default
purge setting was as frequent as every batch cycle, purges would be
accounted for in the amended ACIM test procedure because the batches
would likely be consistent even with the purge occurring every cycle
and therefore the batches would meet the stability criteria as amended
in this final rule.
DOE is maintaining in this final rule its determination to not
directly account for energy or water used during intermittent flush or
purge cycles, consistent with the December 2021 NOPR.
[[Page 65881]]
c. Clearances
As discussed in section III.C and shown in Table III.2, the
clearance requirements around a unit under test changed between ASHRAE
Standard 29-2009 and ASHRAE Standard 29-2015. The current DOE test
procedure, through reference to section 6.4 of ASHRAE Standard 29-2009,
requires a clearance of 18 inches on all four sides of the test unit,
while section 6.5 of ASHRAE Standard 29-2015 requires a minimum
clearance of 3 feet to adjacent test chamber walls, or the minimum
clearance specified by the manufacturer, whichever is greater.
In response to the March 2019 RFI, Howe Corporation (``Howe'')
commented that it is reasonable for customers to expect units to
perform at their ratings when using the minimum clearances as described
in the manufacturer literature. Howe recommended that DOE require a
clearance of 3 feet, or the minimum clearance allowed by the
manufacturer, whichever is less, to better represent an average use
cycle. Howe also commented that this clearance should include all
machine clearances, not just walls within the test chamber, and that a
minimum clearance enclosure be built for testing ACIMs based on the
harshest manufacturer-recommended operating installation, without
blocking an intake air path to the ice maker. Howe also commented that
this setup would not be a large test burden as many manufacturers test
units of similar size, and the enclosures could be used over multiple
tests. (Howe, No. 6 at p. 4)
In support of the December 2021 NOPR, DOE conducted testing to
assess how different clearance requirements could affect the measured
energy consumption and harvest rate of ACIMs. 86 FR 72322, 72342. DOE
investigated the performance of ACIMs under four clearance setups: (1)
the clearance required by ASHRAE Standard 29-2015, (2) the clearance
required by the current DOE test procedure (through reference to ASHRAE
Standard 29-2009), (3) all minimum clearances as recommend by the
manufacturer, and (4) the rear minimum clearance as recommend by the
manufacturer with all other clearances per ASHRAE Standard 29-2015. Id.
Table III.11 summarizes how four test units performed under the four
clearance setups. Id.
Table III.11--Summary of Clearance Impact on ACIM Performance
----------------------------------------------------------------------------------------------------------------
Change in
Change in Energy energy
Harvest rate harvest rate consumption consumption
Test unit Clearance setup (lbs of ice/ (from ASHRAE (kWh/100 lbs (from ASHRAE
24hrs) standard 29- of ice) standard 29-
2015) 2015)
----------------------------------------------------------------------------------------------------------------
1 ASHRAE Standard 29- 573 N/A 4.93 N/A
2015.
Current DOE Test 575 0% 4.97 1%
Procedure.
Minimum Clearances.... 548 -4% 5.25 6%
Minimum Rear Clearance 576 1% 4.94 0%
2 ASHRAE Standard 29- 814 N/A 4.46 N/A
2015.
Current DOE Test 815 0% 4.48 0%
Procedure.
Minimum Clearances.... 794 -2% 4.59 3%
Minimum Rear Clearance 820 1% -4.41 1%
3 ASHRAE Standard 29- 1,164 N/A 4.41 N/A
2015.
Current DOE Test 1,164 0% 4.46 1%
Procedure.
Minimum Clearances.... 1,043 -10% 5.14 17%
Minimum Rear Clearance 1,149 -1% 4.44 1%
4 ASHRAE Standard 29- 1,197 N/A 5.40 N/A
2015.
Current DOE Test 1,195 0% 5.43 1%
Procedure.
Minimum Clearances.... 1,105 -8% 6.04 12%
Minimum Rear Clearance 1,197 0% 5.39 0%
----------------------------------------------------------------------------------------------------------------
The tests indicate that the different clearance requirements,
except for the installation with all minimum clearances, have little to
no impact on the measured performance of ACIMs. Id. The impact observed
from the minimum clearance test is likely due to the exhaust air being
directed through the test enclosure (i.e., the minimum clearances on
the sides, back, and top of the ACIM resulted in an enclosure guiding
condenser exhaust air) back to the front air inlet on the ACIM, which
results in the ACIM drawing in warmer air than under the three other
setup configurations. Id. As described in section III.D.4.a, testing
with a temporary baffle to prevent such air flow is not appropriate, so
the condenser exhaust re-circulated during this investigative testing.
Id.
Based on these test results, an installation configuration that
provides only the minimum manufacturer test clearances for all sides
represents a worst-case installation for ACIM performance. Id. While
manufacturers might provide minimum clearances for all sides of a unit,
the expectation may be that units are installed such that one or more
of the sides has clearance exceeding the manufacturer minimum. Id.
Similarly, a minimum clearance of 3 feet to adjacent test chamber
walls or a clearance of 18 inches on all four sides (as required by
ASHRAE Standard 29-2015 and the current DOE test procedure,
respectively) may also not be a typical ACIM installation. Id. Because
ACIMs are typically installed in commercial food service applications
with space constraints, such as commercial kitchens, end users likely
install their ACIMs against at least a rear wall using the manufacturer
minimum clearance to maximize available working space. Id. Based on the
test data in Table III.10, testing according to the manufacturer-
specified minimum rear clearance has little to no measured impact on
ACIM performance for the four test units. Id. However, because ACIMs
may exhaust condenser air from the rear of the unit, an inappropriate
manufacturer minimum rear clearance (or lack of manufacturer
instructions regarding rear clearance) could adversely affect ACIM
performance while being representative of typical use, and should be
captured in the tested performance. Id.
[[Page 65882]]
Therefore, in the December 2021 NOPR, DOE proposed that ACIMs be
tested according to the manufacturer's specified minimum rear clearance
requirements, or 3 feet from the rear of the ACIM, whichever is less.
86 FR 72322, 72343. DOE proposed testing be conducted with a minimum
clearance of 3 feet or the minimum clearance specified by the
manufacturer, whichever is greater, on all other sides of the ACIM and
all sides of the remote condenser, if applicable. Id. As discussed, and
shown in the DOE test data, the impact of this proposed change on
measured energy use for currently certified ACIMs would likely be de
minimis. Id. DOE expected manufacturer installation instructions would
typically provide for clearances that would ensure sufficient air flow
to avoid any adverse impacts on ACIM performance under the proposed
test setup. Id.
In the December 2021 NOPR, DOE did not propose specific
requirements for the wall used to maintain the rear clearance when
conducting the test. 86 FR 72322, 72343. Test laboratories would be
able to satisfy the clearance requirements in any way they choose, as
long as the test installation meets the proposed requirements. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
require that ACIMs be tested according to the manufacturer's specified
minimum rear clearance requirements, or 3 feet from the rear of the
ACIM, whichever is less, and that all other sides of the ACIM and all
sides of the remote condenser, if applicable, shall be tested with a
minimum clearance of 3 feet or the minimum clearance specified by the
manufacturer, whichever is greater. 86 FR 72322, 72343. DOE also
requested comment on whether this proposal would affect measured energy
use and harvest rate compared to the existing DOE test procedure. Id.
In response to the December 2021 NOPR, Hoshizaki requested that
this be explored in the ASHRAE 29 standard committee to clarify any
changes to the current test specifications. (Hoshizaki, No. 14, p. 5)
IOM did not support this proposal to change clearance requirements.
(IOM, No. 11, p. 3)
AHRI commented that depending on the condenser location and air
discharge, changes to the clearance requirements could impact
performance of the unit. (AHRI, No. 13, p. 7) IOM commented that
reducing the rear minimum clearance will very likely increase measured
energy use and decrease measured harvest rate. (IOM, No. 11, p. 3) IOM
added that minimum clearances are established to provide guidelines for
installation from a product safety standpoint, not a performance
standpoint, and it is well understood in the industry that increasing
clearance around the unit will result in improved performance and
efficiency. Id.
IOM commented that measuring performance and efficiency of a
product in its worst possible installation configuration is unfair to
manufacturers. (IOM, No. 11, p. 3) AHRI added that the requirements in
ASHRAE Standard 29 are clear and effective regarding the clearance
allowed and changes to these requirements could result in undue burden
to test facilities that have already setup for ASHRAE 29 requirements.
(AHRI, No. 13, p. 7)
DOE notes that, in response to the March 2019 RFI, Howe commented
that it is reasonable for customers to expect ACIMs to perform at their
certified ratings when using the minimum clearances as described in the
manufacturer literature. (Howe, No. 6 at p. 4) While manufacturers
might provide minimum clearances for all sides of an ACIM, the
expectation may be that ACIMs are installed such that one or more of
the sides have clearances exceeding the manufacturer minimum.
ACIMs may have different condenser locations and air discharge but
because ACIMs are typically installed in commercial food service
applications with space constraints, end users likely install their
ACIMs against at least a rear wall using the manufacturer minimum
clearance to maximize available working space and, therefore, the
manufacturer's minimum rear clearance should be accounted for in the
tested performance. Based on the test data in Table III.10, testing
according to the manufacturer-specified minimum rear clearance has
little to no measured impact on ACIM performance for the four test
units. However, because ACIMs may exhaust condenser air from the rear
of the unit, an inappropriate manufacturer minimum rear clearance (or
lack of manufacturer instructions regarding rear clearance) could
adversely affect ACIM performance while being representative of typical
use and should be captured in the tested performance.
DOE notes that, in the December 2021 NOPR, DOE did not propose
specific requirements for the wall used to maintain the rear clearance,
which is the only change from the ASHRAE 29-2015 clearance
requirements, when conducting the test and that test facilities would
be able to setup the clearance requirements in any way they choose, as
long as the test installation meets the proposed requirements, in order
to limit any potential test burden.
DOE will consider any updated industry standards, if available,
during future ACIM test procedure rulemakings.
DOE is maintaining in this final rule that ACIMs be tested
according to the manufacturer's specified minimum rear clearance
requirements, or 3 feet from the rear of the ACIM, whichever is less,
consistent with the December 2021 NOPR. On all other sides of the ACIM
and all sides of the remote condenser, if applicable, testing shall be
conducted with a minimum clearance of 3 feet or the minimum clearance
specified by the manufacturer, whichever is greater. Test laboratories
may satisfy the clearance requirements in any way they choose, as long
as the test installation meets the amended requirements.
d. Ambient Temperature Measurement
Air temperature fluctuations from the test chamber or the ACIM's
condenser exhaust air can potentially affect an ACIM's measured energy
consumption and harvest rate.
i. Ambient Temperature Sensors
The current ACIM test procedure, which is based on AHRI Standard
810-2007 and ASHRAE Standard 29-2009, does not specify whether a
weighted or unweighted sensor is to be used to measure ambient
temperature. A weighted sensor measures the temperature of a high
conductivity (isothermal) mass to which it is connected. The mass slows
equilibration of the measured temperature with the surrounding air,
thus damping out air temperature fluctuations. This may result in a
weighted sensor indicating that the fluctuations are within the
required temperature test condition tolerances, whereas an unweighted
sensor could indicate temperature extremes exceeding the required
temperature test condition tolerances. This difference in function of
the sensors impacts the application of the required temperature test
condition tolerances, i.e., temperature fluctuations that fall outside
the required tolerances may not be detected when using a weighted
sensor, but would be detected when using an unweighted sensor.
In support of the December 2021 NOPR, DOE conducted testing to
evaluate the ability to meet the specified tolerances of ASHRAE
Standard 29-2015 using both weighted and unweighted temperature
sensors. 86 FR 72322, 72344. The temperature fluctuations recorded by
weighted temperature sensors may be less than
[[Page 65883]]
those recorded with unweighted measurement due to damping of the
fluctuations by the weighted thermal mass. Id. As such, weighted
sensors may give the false impression that ambient temperature test
condition tolerances of 2 [deg]F during the first 5 minutes
of each freeze cycle, and not more than 1 [deg]F
thereafter, are met during testing. Id. The measurement of ambient
temperature using unweighted sensors provides more representative
measures of actual instantaneous ambient temperature conditions than
the measurement of weighted sensors. Id. DOE observed in its testing in
support of the December 2021 NOPR that the ambient temperature was
within the test condition tolerances specified in ASHRAE Standard 29-
2015 for all freeze cycles when using either weighted or unweighted
sensors. Id.
Therefore, in the December 2021 NOPR, DOE proposed to specify that
unweighted sensors be used to make all ambient temperature
measurements. 86 FR 72322, 72344. Based on comments received in the
March 2019 RFI, this proposal reflects current industry practice and
would not add any burden. Id. This proposal is consistent with AHRI
Standard 810 (I-P)-2016 with Addendum 1 because it specifies the
instrumentation for measuring ambient temperature, but does not
otherwise change the existing requirements. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
specify that ambient temperature measurements be made using unweighted
sensors. 86 FR 72322, 72344.
In response to the December 2021 NOPR, Hoshizaki agreed with the
proposal, but noted that if a clarification is needed that this be
addressed by the ASHRAE 29 standard committee. (Hoshizaki, No. 14, p.
5) AHRI commented that the testing location is currently allowed to
designate the sensor type used, and this has not negatively impacted
ratings or product performance and therefore should not be changed
without further clarification of issues that it may resolve and
discussion at the method of test level. (AHRI, No. 13, p. 7) AHRI added
that the change to requiring unweighted sensors could incur associated
costs without providing benefits to the test results, but if such a
change is to be considered, it should go through the ASHRAE 29
standards committee. Id. AHRI noted that this issue has been debated
within other refrigeration ASHRAE committees continuously without
conclusions being reached that unweighted sensors should be required.
Id.
AHAM commented that in DOE's proposed test procedure the mean of
the ambient temperatures is more important than a momentary fluctuation
of temperature. (AHAM, No. 18, p. 13) AHAM commented in support of
weighted sensors because they would dampen the influence of other units
being simultaneously tested on the ambient and gradient measurements
and disagreed with the use of unweighted sensors because they are more
easily influenced by changes in temperature, including those resulting
from opening and closing the test room door. Id. AHAM stated that,
similar to DOE's test procedure for refrigeration products, weighted
sensors are appropriate for testing residential ice makers in order to
compensate for the fluctuations occurring during testing. Id.
Based on DOE's analysis indicating that the specified test
conditions can be met with an unweighted sensor, which was presented in
the December 2021 NOPR, DOE is maintaining in this final rule that
ambient temperature measurements be made using unweighted sensors,
consistent with the December 2021 NOPR.
ii. Alternative Ambient Measurement Locations
The current DOE guidance and proposal in the December 2021 NOPR
regarding the use of temporary baffles, as discussed in section
III.D.4.a, illustrates that temporary baffles can reduce or prevent
recirculation of warm air from an ACIM's condenser exhaust air to its
air inlet. This recirculation of warm air can potentially affect an
ACIM's measured energy consumption and harvest rate and using a
temporary baffle for testing is unrepresentative of actual ACIM use.
The recirculation of warm air may also affect the ability to maintain
ambient temperature within the range specified in AHRI Standard 810 (I-
P)-2016 with Addendum 1 and relative humidity within the range proposed
in the December 2021 NOPR. For example, if the condenser exhaust is
warm enough and directed towards the air inlet location (and
corresponding ambient temperature measurement), the measured ambient
temperature may be warmer than the representative ambient temperature
around the unit under test, even with shielding around the temperature
sensor.
To evaluate the extent of this potential impact on temperature, DOE
tested, in support of the December 2021 NOPR, an ACIM which exhausted
its warm condenser air on the side of the ACIM adjacent to the side
with the air intake. 86 FR 72322, 72344. Three ambient thermocouples
were placed 1 foot from the geometric center of each side around the
ACIM in addition to the unshielded ambient thermocouple that was placed
1 foot from the air inlet. Id. The unshielded ambient thermocouple that
was located 1 foot from the air inlet was used to control the test
chamber conditions in accordance with AHRI Standard 810 (I-P)-2016 with
Addendum 1 (i.e., the overall chamber temperature was reduced as
necessary to maintain the temperature one foot in front of the air
inlet as close to 90 [deg]F as possible). Id. Table III.12 summarizes
the results of this testing.
Table III.12--Average Ambient Temperatures Measured on Each Side Around and ACIM
----------------------------------------------------------------------------------------------------------------
Opposite side Opposite side
Inlet ([deg]F) Exhaust of exhaust of inlet
([deg]F) ([deg]F) ([deg]F)
----------------------------------------------------------------------------------------------------------------
89.9............................................................ 90.2 88.5 88.2
----------------------------------------------------------------------------------------------------------------
As shown in Table III.12, the air within the chamber had to be
reduced below 89 [deg]F (outside the 90 1 [deg]F allowable
ambient temperature range specified in ASHRAE Standard 29-2015) to
maintain the temperature at the air inlet near the specified 90 [deg]F
condition. Id. This data suggests that ACIM models that allow the warm
condenser exhaust air to recirculate to the air intake may require
lower overall ambient test chamber temperatures to maintain the
specified condition at the air inlet. Id.
The ambient temperature measurement is meant to represent the
temperature of the air around the unit under test that is not impacted
by unit operation. Id. Because test facilities may have difficulty
effectively shielding the air inlet thermocouple from warm
[[Page 65884]]
discharge air without blocking the recirculation of that air to the
ACIM air inlet, as discussed in section III.D.4.a., in the December
2021 NOPR, DOE proposed that the ambient temperature may be recorded at
an alternative location. Id. DOE proposed that for ACIMs in which warm
air discharge impacts the ambient temperature as measured in front of
the air inlet (i.e., the warm condenser exhaust airflow is directed to
the ambient temperature location in front of the air inlet), the
ambient temperature may instead be measured at locations 1 foot from
the cabinet, centered with respect to the sides of the cabinet, for
each side of the ACIM cabinet with no air discharge or inlet. Id. DOE
expected that this proposal would not impact measured ACIM performance
compared to the existing test approach. 86 FR 72322, 72344-72345. DOE
also proposed that the relative humidity measurement, as proposed in
the December 2021 NOPR, would also be made at the same alternative
locations. 86 FR 72322, 72345.
Test installation according to the manufacturer's minimum rear
clearance requirements, as discussed in section III.D.4.c, may affect
the ability to measure the ambient temperature and relative humidity
one foot from the air inlet if the air intake is through the rear side
of the ACIM and the minimum rear clearance is less than 1 foot from the
air inlet. Id. Additionally, the alternate measurement location, as
proposed in the December 2021 NOPR, would not be feasible for the rear
side of a model with no air discharge or inlet on that side and with a
minimum rear clearance of less than 1 foot. Id.
In the December 2021 NOPR, DOE proposed that if a measurement
location 1 foot from the rear of an ACIM is not feasible for testing
that would otherwise require a measurement at that location, the
ambient temperature and relative humidity shall instead be measured 1
foot from the cabinet, centered with respect to the surface(s) of the
ACIM, for any surfaces around the perimeter of the ACIM that do not
include an air discharge or air inlet. 86 FR 72322, 72345. DOE
similarly did not expect this proposal to impact current ACIM
measurements as it provides an alternative measurement location for the
existing ambient temperature and relative humidity requirements. 86 FR
72322, 72345.
In the December 2021 NOPR, DOE requested comment on its proposal to
allow for an alternate ambient temperature (and relative humidity)
measurement location to avoid complications associated with shielding
the measurement in front of the air inlet, as currently required. 86 FR
72322, 72345. DOE also requested comment on the proposal for measuring
ambient temperature and relative humidity for ACIMs for which the
proposed rear clearance would preclude temperature measurements at the
rear of the unit under test. Id.
In response to the December 2021 NOPR, Hoshizaki and AHRI commented
that if manufacturers need an alternate location for ambient
temperatures, this can either be addressed by waiver or addressed
through the ASHRAE 29 standard committee to change the requirements.
(Hoshizaki, No. 14, p. 5; AHRI, No. 13, p. 7) AHRI added it does not
feel that a dictated alternative measurement location will address any
concerns that may arise with a particular model. (AHRI, No. 13, p. 7)
As discussed in section III.D.4.c, DOE is maintaining that ACIMs be
tested according to the manufacturer's specified minimum rear clearance
requirements, or 3 feet from the rear of the ACIM, whichever is less.
The alternate measurement location is necessary to allow for testing
certain equipment configurations--for example, if the air intake is
through the rear side of the ACIM and the minimum rear clearance is
less than 1 foot from the air inlet. Therefore, DOE is maintaining in
this final rule to allow for an alternate ambient temperature (and
relative humidity) measurement location, consistent with the December
2021 NOPR.
e. Ice Cube Settings
DOE is aware that some ice makers have the capability to make
various sizes of cubes. The size of the cube can typically be selected
on the control panel of the ice maker, for example. Section 5.2 of AHRI
Standard 810 (I-P)-2016 with Addendum 1 states that for machines with
adjustable ice cube settings, standard ratings are determined for the
largest and the smallest cube settings, and that ratings for
intermediate cube settings may be published as application ratings.
This is consistent with the current DOE requirement as incorporated by
reference in AHRI Standard 810-2007.
In the December 2021 NOPR, DOE did not propose any change to the
existing industry requirement to determine ratings under the largest
and smallest cube settings for ACIMs with adjustable ice cube settings.
86 FR 72322, 72345. EPCA requires the DOE test procedure to be
reasonably designed to produce test results which reflect energy use
during a representative average use cycle. The current requirement to
test using the largest and smallest cube setting is based on the
industry standard, which was developed based on industry's experience
with this equipment. There is no information to support that testing at
the ``worst possible configuration'' would be representative of an
average use cycle. As such, DOE did not propose to change the current
requirement to test at both the smallest and largest cube setting,
which is the same as the requirement in AHRI Standard 810 (I-P)-2016
with Addendum 1. Id.
In the December 2021 NOPR, DOE requested comment on maintaining the
current requirement to test at the largest and smallest ice cube size
settings, consistent with AHRI Standard 810 (I-P)-2016 with Addendum 1.
86 FR 72322, 72345. DOE also requested information on the ice cube size
setting typically used by customers with ACIMs with multiple size
settings (largest, smallest, default, etc.). 86 FR 72322, 72345.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
with maintaining the requirements set by AHRI Standard 810 (I-P)-2016
with Addendum 1 for cube size settings. (Hoshizaki, No. 14, p. 5; AHRI,
No. 13, p. 8)
DOE is maintaining in this final rule the current requirement to
test at the largest and smallest ice cube size settings, consistent
with AHRI Standard 810 (I-P)-2016 with Addendum 1.
f. Ice Makers With Dispensers
DOE is aware of certain self-contained ACIMs that dispense ice to a
user through an automatic dispenser when prompted by the user. Testing
according to the current DOE test procedure or the updated industry
standards as proposed in the December 2021 NOPR may be difficult or
impossible for certain ACIM configurations with automatic dispensers.
86 FR 72322, 72345.
Section 6.6 in ASHRAE Standard 29-2015 specifies that an ACIM must
have its bin one-half full of ice when collecting capacity
measurements. DOE is aware of self-contained ACIMs with dispensers that
contain internal storage bins that are not accessible during normal
operation (i.e., users access the ice only through use of the
dispenser). Because the internal bins are not accessible during normal
operation, it can be difficult or impossible to establish a storage bin
one-half full of ice for testing. Additionally, isolating the ice
produced during testing from the ice initially placed in a one-half
full storage bin may be difficult or impossible, depending on the
dispenser and internal storage bin configuration.
[[Page 65885]]
Section 6.10 of ASHRAE Standard 29-2015 requires that the ACIM be
completely assembled with all panels, doors, and lids in their normally
closed positions during the test. Additionally, section 4.1.4 of AHRI
Standard 810 (I-P)-2016 with Addendum 1 requires that the test unit
shall be configured for testing per the manufacturer's written
instructions provided with the unit. It also requires that no
adjustments of any kind shall be made to the test unit prior to or
during the test that would affect the ice capacity, energy usage, or
water usage of the test sample. Many self-contained ACIMs with
dispensers would require removing case panels or the top lid to access
the internal ice bin for ice collection or establishing initial test
setup. In typical operation, users would access the ice only through
the dispenser mechanism.
Through a letter dated January 28, 2020, Hoshizaki petitioned for a
waiver and interim waiver from the DOE ACIM test procedure at 10 CFR
431.134 for ice/water dispenser ACIM basic models to address the test
issues previously described in this section (case number 2020-001).\29\
On July 23, 2020, DOE granted Hoshizaki an interim waiver to test the
identified ACIM basic models with a modified test procedure. 85 FR
44529. After providing opportunity for public comment on the interim
waiver and reviewing the one comment received, DOE granted Hoshizaki a
waiver through a final decision and order published on October 28,
2020. 85 FR 68315.
---------------------------------------------------------------------------
\29\ The petition and related documents are available at
www.regulations.gov in docket EERE-2020-BT-WAV-0005.
---------------------------------------------------------------------------
The decision and order requires, prior to the start of the test,
removing the front panel of the unit under test and inserting a bracket
to hold the shutter (which allows for the dispensing of ice during the
test) completely open for the duration of the test. After inserting the
bracket, return the front panel to its original position on the unit
under test. Conduct the test procedure as specified in 10 CFR 431.134
except that the internal ice bin for the unit under test shall be empty
at the start of the test and intercepted ice samples shall be obtained
from a container in an external ice bin that is filled one-half full
with ice and is connected to the outlet of the ice dispenser through
the minimum length of conduit that can be used. Id.
This waiver granted to Hoshizaki includes instructions for testing
the specific basic models addressed in that waiver process. However,
other ACIM models with dispensers would likely require similar testing
instructions. Moreover, after the granting of any waiver, DOE must
publish in the Federal Register a notice of proposed rulemaking to
amend its regulations to eliminate any need for the continuation of
such waiver. 10 CFR 431.401(l). Therefore, in the December 2021 NOPR,
DOE proposed to add general test instructions to the proposed DOE test
procedure at 10 CFR 431.134(b)(6) to allow for testing such models. 86
FR 72322, 72346. DOE proposed that ACIMs with a dispenser be tested
with continuous production and dispensing of ice throughout the
stabilization and test periods. Id. As noted in the December 2021 NOPR,
if an ACIM with a dispenser is not able to allow for the continuous
production and dispensing of ice because of certain mechanisms within
the ACIM that prohibit this function, those mechanisms must be
overridden to the minimum extent that allows for the continuous
production and dispensing of ice. Id. For example, this would allow for
the temporary removal of panels or overriding of certain controls, if
necessary. Id. The capacity samples would be collected in an external
bin one-half full with ice and connected to the outlet of the ice
dispenser through the minimal length of conduit that can be used for
the required time period as defined in ASHRAE Standard 29-2015. Id.
Because of the continuous production and dispensing of ice, these ACIMs
would be required to have an empty internal storage bin at the
beginning of testing. Id. This would ensure that the collection periods
capture only the quantity of ice produced during that period (i.e.,
this would avoid any ice being collected that was produced prior to the
collection period). Id. This proposed approach would address issues
with testing ACIM models with automatic dispensers, while allowing a
representative measure of how ACIMs with dispensers are typically used.
Id. This approach would also minimize test burden by avoiding the need
to significantly alter the configurations of these ACIM models for
testing (e.g., allowing for access to any internal storage bins during
performance testing). Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
collect capacity samples for ACIMs with dispensers through the
continuous production and dispensing of ice throughout testing, using
an empty internal storage bin at the beginning of the test period and
collecting the ice sample through the dispenser in an external bin one-
half full of ice. 86 FR 72322, 72346. DOE also requested comment on its
proposal to allow for certain mechanisms within the ACIM that would
prohibit the continuous production and dispensing of ice throughout
testing to be overridden to the minimum extent that allows for the
continuous production and dispensing of ice. Id. DOE sought information
on how manufacturers of these ACIMs currently test and rate this
equipment under the existing DOE test procedure, whether the proposal
would impact the energy use as currently measured, and on the burden
associated with the proposed approach or any alternative test
approaches. Id.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
with adopting the approach stated, and AHRI noted that this process is
also being proposed to the ASHRAE 29 committee for consideration.
(Hoshizaki, No. 14, p. 6; AHRI, No. 13, p. 8)
AHAM commented that DOE's proposed test procedure does not account
for integrated dispensing, such as for a dispenser ice maker with ice
internal to the unit (a feature offered in certain residential
products). (AHAM, No. 18, p. 11) AHAM states that, for these products,
there is no way to determine if the bin is half full during the run-in
portion of the test, and that DOE proposes to override the dispensing
function so that it continually dispenses, which is not possible on all
units that have this feature. Id.
The CA IOUs commented that a self-contained ice maker category type
that DOE recognized needs specialized test methodology is the ice
dispenser ice maker. (CA IOUs, No. 16, p. 4) The CA IOUs noted that the
ice is made inside the ice bin and an automated ice dispenser is
located underneath the bin to dispense ice into a cup. Id. The CA IOUs
described that usually these machines have automated water dispensers
integrated into them, the bins range between 10 and 100 lb, and the
production capacity ranges between 200 and 500 lb per day. Id. The CA
IOUs stated that there are 18 different models on the market, which are
purchased by foodservice establishments and offices. Id. The CA IOUs
recommended separating these ice machines into different classes to
allow the test methodology to be refined for each category, resulting
in testing consistency within each category. Id.
In the December 2021 NOPR, DOE proposed that mechanisms must be
overridden to the minimum extent which allows for the continuous
production and dispensing of ice (e.g., insert a bracket to hold the
shutter (which allows for the dispensing of ice
[[Page 65886]]
during the test) completely open for the duration of the test). 86 FR
72322, 72345-72346. DOE also proposed that the internal storage bin be
empty at the beginning of the test period and that the intercepted ice
samples be obtained from a container in an external ice bin that is
filled one-half full of ice. Id. This would ensure that the collection
periods capture only the quantity of ice produced during that period
(i.e., this would avoid any ice being collected that was produced prior
to the collection period).
DOE notes that the test method proposed in the December 2021 NOPR
would apply to all ACIMs with dispensers, not just the basic model for
which there is a test procedure waiver. DOE has not identified the need
for additional test instructions for any other ACIMs with dispensers
and DOE has not received any additional petitions for waiver for other
ACIMs with dispensers. Therefore, DOE is maintaining in this final rule
the test method proposed in the December 2021 NOPR for ACIMs with
dispensers. Further categorization of equipment may be discussed in any
amended energy conservation standards for ACIMs with dispensers.
g. Remote ACIMs
DOE did not propose amendments to the existing test procedures for
testing remote condensing ACIMs in the December 2021 NOPR. 86 FR 72322,
72346. Based on a review of manufacturer installation instructions for
ACIMs with dedicated remote condensing units, manufacturers typically
recommend line sets and/or limitations to installation locations. DOE
preliminarily determined that testing according to the manufacturer
recommendations, as is currently required, rather than one specified
remote setup, would represent typical use in the field and would
produce consistent test results. 86 FR 72322, 72347. DOE also did not
propose any amendments to its test procedure to address ACIMs installed
with a compressor rack because it lacked information on typical
installation locations, operation, and market availability, and because
any ACIMs designed only for connection to remote compressor racks are
out of the scope of DOE's regulations. 86 FR 72322, 72344.
In the December 2021 NOPR, DOE requested comment on its initial
determination that additional test setup and installation instructions
are not required for testing remote condensing ACIMs. 86 FR 72322,
72347.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
that no additional test setup or installation instructions are required
for units with dedicated remote condensing units. (Hoshizaki, No. 14,
p. 6; AHRI, No. 13, p. 8) Hoshizaki added that if a manufacturer has
further requests that are different from its instructions, it could
file that with DOE so it is in the record of special instructions or
taken through the waiver process for clarification. (Hoshizaki, No. 14,
p. 6)
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
with DOE in not establishing test procedures for ACIMs for rack units.
(Hoshizaki, No. 14, p. 6; AHRI, No. 13, p. 8) Hoshizaki added that the
sector is very small, and a new test criterion would need to be
addressed in the ASHRAE 29 standard. (Hoshizaki, No. 14, p. 6)
DOE is maintaining in this final rule that additional test setup
and installation instructions are not required for testing ACIMs with
dedicated remote condensing units, consistent with the December 2021
NOPR. DOE is also not establishing separate test procedures for ACIMs
intended for installation with a compressor rack.
5. Modulating Capacity Ice Makers
An ice maker could be designed to be capable of operating at
multiple capacity levels, i.e., a ``modulating capacity ice maker.''
This modulation could be accomplished by using a single compressor with
multiple or variable capacities, using multiple compressors, or in some
other manner. In the January 2012 final rule, DOE did not establish a
test method for measuring the energy use or water consumption of
automatic commercial ice makers that are capable of operating at
multiple capacities. 77 FR 1591, 1601-1602. The decision to exclude
modulating capacity ice makers was based on the lack of existing ACIMs
with modulating capacity, as well as limited information regarding how
such equipment would function. Id.
DOE conducted market research and examined publicly available
sources to determine the prevalence of modulating capacity ice makers.
DOE did not find any modulating capacity ice makers that are currently
available in the market. Therefore, in the December 2021 NOPR, DOE did
not propose test procedures for modulating capacity ice makers. 86 FR
72322, 72347.
In the December 2021 NOPR, DOE requested comment on its initial
determination regarding the lack of availability of modulating capacity
ice makers on the market. 86 FR 72322, 72347.
In response to the December 2021 NOPR, AHRI agreed with DOE's
determination. (AHRI, No. 13, p. 8) Hoshizaki commented it is not aware
of any modulating capacity ice makers on the market. (Hoshizaki, No.
14, p. 6) Hoshizaki requested that DOE share examples of modulating
capacity ACIMs, and if examples exist, Hoshizaki will review and then
offer comment. Id.
DOE continues to not be aware of any modulating capacity ice makers
available on the market. Therefore, DOE is not establishing test
instructions for modulating capacity ice makers in this final rule.
6. Standby Energy Use and Energy Use Associated With Ice Storage
The current ACIM test procedure considers only active mode energy
use when an ice maker is actively producing ice and represents that
consumption using a metric of energy use per 100 pounds of ice. The
existing ACIM test procedure does not address standby energy use
associated with continuously powered sensors and controls or ice
storage outside of active mode operation. When not actively making ice,
an ice maker continues to consume energy to power sensors and controls.
In addition, ice that is stored in an integral or paired ice storage
bin will melt over time and the ice maker will use additional energy to
replace the ice that has melted to keep the bin full. In these ways,
standby energy use from control devices and energy use associated with
ice storage can impact the daily energy consumption of ACIM equipment.
DOE researched available test methods for determining energy use
associated with ice storage. The AHRI certification program currently
includes rating ice storage bins using AHRI 820-2017, ``Performance
Rating of Ice Storage Bins.'' Similar methods are currently referenced
in the Australian and Canadian test methods and standards applicable to
self-contained ice makers and storage bins.30 31 AHRI 820-
2017 describes a standardized method for measuring the ``efficiency''
of ice storage bins using a metric called ``Theoretical Storage
Effectiveness,'' which describes the percent of ice that would remain
in a bin 24 hours after it is produced. In contrast, the December 2014
MREF Test Procedure NOPR considered energy use associated with ice
storage based on testing the ice maker and storing the ice in a bin
over
[[Page 65887]]
a period of up to 48 hours with no ice retrieval to determine the
energy use associated with replenishing the bin. 79 FR 74894, 74921-
74922.
---------------------------------------------------------------------------
\30\ The Australian minimum energy performance standards
(``MEPS'') apply to both stand-alone storage bins and ice storage
bins contained in stand-alone equipment (AS/NZS 4865.2 & 3). The
NRCan standard appears to apply only to storage bins contained in
self-contained ice makers with integral storage bins.
\31\ The newest version of the CSA test method, C742-15, refers
directly to the 2012 version of AHRI 820 (and AHRI 821, which is the
SI version of the standard).
---------------------------------------------------------------------------
Many ice makers (including ice making heads (``IMHs'') and remote
condensing unit (``RCU'') ice makers) can be paired with any number of
storage bins, including those produced by other manufacturers. These
ice makers are typically paired in the field with a bin chosen by the
end user, rather than the manufacturer. However, DOE understands that
many IMH and RCU equipment are advertised as compatible with a list of
specific bins and, therefore, may be able to be rated based on
recommended bin combinations.
In the December 2021 NOPR, DOE initially determined that the energy
use of ACIMs in standby mode is likely very low compared to active mode
ice making energy use. 86 FR 72322, 72348. Additionally, the
contribution of any standby mode energy use to overall energy use can
vary significantly depending on the specific installation and end use
of the ACIM. Id.
At the time of the December 2021 NOPR, DOE did not have sufficient
data and information to establish test procedures for standby energy
use or energy use associated with ice storage. 86 FR 72322, 72348. In
addition, incorporating standby energy use and energy use associated
with ice storage would require significant test procedure changes
requiring an increase in test time. Therefore, because of the lack of
data and undue burden on manufacturers, DOE did not propose to amend
its test procedures to account for standby or ice storage energy use in
the December 2021 NOPR. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
not amend its test procedures to account for standby or ice storage
energy use. 86 FR 72322, 72348. DOE also requested data on the typical
durations and associated energy use for all ACIM operating modes and on
the potential burden associated with testing energy use in those modes.
Id.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
that DOE should not amend the test procedure to account for standby
energy use. (Hoshizaki, No. 14, p. 6; AHRI, No. 13, p. 8)
Hoshizaki commented the normal bin control switch in low-voltage
test data shows very little power used to communicate with the control
board. (Hoshizaki, No. 14, p. 6) Hoshizaki added that accounting for
standby energy would require a significant increase in total test time,
which would be a significant increase in test burden to measure a very
small amount of energy. Id.
Joint Commenters commented that the standby power associated with
powered controls outside of active icemaking can be around 25-50 kWh
per year. (Joint Commenters, No. 15, p. 2) Joint Commenters noted that
in the 2015 Final Rule Technical Support Document (``TSD'') for ACIM
standards, DOE assumed a utilization factor (i.e., the percent of time
the ice maker is actively producing ice) of 42 percent, and assumed the
unit was in standby mode 58 percent of the time, adding that DOE stated
that the utilization factor was based on data provided by manufacturers
and a field study. Id. Joint Commenters stated that despite the
information cited in the 2015 Final Rule TSD, DOE cites insufficient
information as a reason not to amend the test procedures to capture
standby power, therefore, the Joint Commenters encouraged DOE to
capture standby energy use in the test procedure to improve
representativeness by more fully capturing the total energy consumption
of ACIMs. Id.
The CA IOUs recommended that for self-contained machines the ice-
melt rate procedure from AHRI 820 should be integrated into the method
of test, and the ice-melt rate should be reported or integrated into
the daily energy and harvest rate. (CA IOUs, No. 16, p. 7) The CA IOUs
added that self-contained ice machines have an ice bin that is integral
to the unit, and ice-melt rate should be reported for these units or
have the ice-melt rate accounted for in the reported energy
consumption. Id.
Joint Commenters urged DOE to capture the energy use associated
with ice storage due to replacement cycles in the test procedures for
self-contained units (SCU), which include an integrated storage bin, as
well as for ice-making heads (IMH) and remote-condensing units (RCU).
(Joint Commenters, No. 15, p. 3) Joint Commenters noted that in a NOPR
published on December 16, 2014, regarding the miscellaneous
refrigeration products (``MREFs'') test procedure (``December 2014 MREF
Test Procedure NOPR''; 79 FR 74894), DOE proposed a test procedure that
included a measurement of both the energy consumed during active ice
production and the energy use associated with replenishing the ice
supply to replace melted ice during ice storage. Id. For SCUs, Joint
Commenters encouraged DOE to investigate the appropriateness of a
procedure similar to the one it proposed for ice makers in the December
2014 MREF Test Procedure NOPR. Id.
Joint Commenters commented that the operation of ice makers
includes replacement cycles (i.e., when additional ice is produced to
replenish the storage bin due to ice melt), and the effectiveness of
the storage bin at keeping the stored ice cold (i.e., slowing the melt)
drives the frequency of the replacement cycles, and thus impacts the
energy consumed over a period of time, such as a day or a year. (Joint
Commenters, No. 15, p. 2-3) Joint Commenters noted that DOE previously
found that the energy use associated with replacement of melted ice
from ice storage bins ranged from 30 to 75% of total ice maker energy
consumption. Id.
For IMHs and RCUs, Joint Commenters encouraged DOE to consider an
approach that could involve establishing default values that represent
the energy use associated with ice replacement. (Joint Commenters, No.
15, p. 3) Joint Commenters added the melt rates associated with the
least-efficient storage bins on the market could be used to determine
the extent of replacement cycle operation during a fixed period, such
as 24 hours, noting that the default value of replacement cycle energy
would take the form of an adder to measured energy consumption in the
normal icemaking cycle. Id. Joint Commenters stated that a manufacturer
could then choose to either use the default value or, if they wanted to
demonstrate improved storage bin effectiveness, they could conduct a
similar test to that used for SCUs. Id. Specifically, Joint Commenters
addressed DOE's statements in the NOPR that many IMH and RCU models are
advertised as compatible with a list of specific bins, stating they
believe that it could make sense in these cases for the manufacturer to
test with the least-efficient storage bin of those advertised in their
literature. Id. If no bin is specified, the manufacturer would instead
use the default values. Id.
In the December 2021 NOPR, DOE initially determined that the
contribution of any standby mode energy use to overall energy use can
vary significantly depending on the specific installation and end use
of the ACIM. 86 FR 72322, 72348. Because ACIMs may be installed and
operated in a range of end uses (e.g., commercial kitchens, offices,
schools, hospitals, hotels, and convenience stores), determining the
performance based on the metric of energy use per 100 pounds of ice
during an ACIM's active mode best reflects energy efficiency, energy
use, or estimated annual operating cost of a given type of covered
equipment
[[Page 65888]]
during a representative average use cycle while not being unduly
burdensome to conduct, consistent with 42 U.S.C. 6314(a)(2).
DOE also initially determined that IMHs and RCU ice makers are
typically paired in the field with a storage bin chosen by the end
user, rather than the manufacturer, which can result in IMHs and RCU
ice makers paired with storage bins from a different manufacturer. 86
FR 72322, 72348. DOE acknowledges that self-contained ice makers
contain a storage bin that is integral to the ACIM. However, the energy
use associated with ice storage of all ACIMs, including self-contained
ice makers, can vary significantly depending on the specific
installation and end use of the ACIM.
DOE acknowledges the comments regarding DOE's utilization factor
from the 2015 Final Rule TSD for ACIM standards.\32\ The utilization
factor estimates the percent of time ice makers actively produce ice.
The assumed utilization factor in the 2015 Final Rule TSD for ACIM
standards was 42 percent across all equipment classes and efficiency
levels and was based on data provided by manufacturers and data
obtained from a field study.\33\ The assumed utilization factor was
used to estimate the annual energy consumption of each equipment class
and efficiency level considered in the 2015 Final Rule TSD for ACIM
standards and does not represent the utilization factor for an
individual test unit. As noted by the field study, ice maker usage can
vary dramatically from one installation to another as illustrated by
the results of the field study in which the duty cycles of tested units
averaged between 34.5 percent and 86.6 percent.
---------------------------------------------------------------------------
\32\ See https://www.regulations.gov/document/EERE-2010-BT-STD-0037-0136.
\33\ See https://p2infohouse.org/ref/50/49015.pdf.
---------------------------------------------------------------------------
DOE has determined that the measurement of active mode energy use,
when an ice maker is actively producing ice, and the metric of energy
use per 100 pounds of ice represent a repeatable and reproducible test
method that is reasonably designed to produce test results which
reflect energy use during a representative average use cycle.
Therefore, DOE is maintaining in this final rule to not amend its test
procedures to account for standby or ice storage energy use.
7. Calculations and Rounding Requirements
As compared to ASHRAE Standard 29-2009, section 9.1.1 of ASHRAE
Standard 29-2015 specifies averaging instructions for calculating the
gross weight of product produced. ASHRAE Standard 29-2015 specifies to
``average the quantity for the three samples to determine the ice
produced.'' However, this averaging instruction is not specified for
the water or energy consumption calculations.
In the December 2021 NOPR, DOE proposed to provide explicitly that
the energy use, condenser water use, and potable water use (as
described in section III.D.8) be calculated by averaging the measured
values for each of the three samples for each respective metric. 86 FR
72322, 72348. DOE added that this clarification would not affect the
measured performance of ACIMs but would more explicitly present the
calculation approach. Id.
In the December 2021 NOPR, DOE requested comment on the proposal to
clarify that the energy use, condenser water use, and potable water use
(as described in section III.D.8) be calculated by averaging the
calculated values for the three measured samples for each respective
metric. 86 FR 72322, 72348.
In response to the December 2021 NOPR, AHRI agreed with DOE that
these could be valid proposed changes. (AHRI, No. 13, p. 9) However,
AHRI and Hoshizaki requested that any clarifications to the ASHRAE 29
be addressed by the ASHRAE 29 standard committee. (AHRI, No. 13, p. 9;
Hoshizaki, No. 14, p. 6).
DOE has determined to amend the test procedure in this final rule
to clarify that the energy use, condenser water use, and potable water
use (as described in section III.D.8) be calculated by averaging the
calculated values for the three measured samples for each respective
metric.
The regulations in 10 CFR 431.132 specify rounding requirements for
the ACIM metrics ``energy use'' and ``maximum condenser water use.''
Specifically, DOE requires energy use to be in multiples of 0.1 kWh/100
lb and condenser water use to be in multiples of 1 gallon per 100
pounds of ice (``gal/100 lb''). 10 CFR 431.132.
AHRI Standard 810-2007, which is currently incorporated by
reference in the DOE test procedure, and AHRI Standard 810 (I-P)-2016
with Addendum 1, which was proposed for use in the December 2021 NOPR,
specify rounding requirements for the following quantities:
Table III.13--Summary of Rounding Requirements
------------------------------------------------------------------------
AHRI standard 810 (both
Quantity 2007 and 2016, except as
noted)
------------------------------------------------------------------------
Ice Harvest Rate.......................... 1 lb/24 h.
Condenser Water Use Rate.................. 1 gal/100 lb.
Potable Water Use Rate.................... 0.1 gal/100 lb.
Energy Consumption Rate................... 0.1 kWh/100 lb (2007).
0.01 kWh/100 lb (2016).
Ice Hardness Factor....................... Not Specified (percent).
------------------------------------------------------------------------
In the December 2021 NOPR, DOE proposed to incorporate by reference
AHRI Standard 810 (I-P)-2016 with Addendum 1, which would include the
rounding requirements shown in Table III.12, with the exception of the
provision for harvest rate. 86 FR 72322, 72349. For harvest rate, the
specified rounding to the nearest 1 lb/24 h could represent a
significant percentage of harvest rates for low-capacity ACIMs. As
discussed in section III.D.2, DOE observed low-capacity ACIMs available
on the market with harvest rates as low as 7 lb/24 h. For this harvest
rate, rounding to the nearest pound would allow a range of measured
performance of approximately 7 percent to have the same
harvest rate result. Section 5.5.1 of ASHRAE Standard 29-2015 provides
that ice-weighing instruments have accuracy and readability of 1.0% of the quantity measured. Therefore, to avoid rounding
harvest rate to a level that could impact test procedure accuracy, DOE
proposed that harvest rate be rounded to the nearest 0.1 lb/24 h for
ACIMs with harvest rates less than or equal to 50 lb/24 h. 86 FR 72322,
72349. DOE further discusses rounding requirements in section III.E.2.
DOE has determined to amend the test procedure in this final rule
to require the rounding requirements specified in AHRI Standard 810 (I-
P)-2016 with Addendum 1 except that for ACIMs with harvest rates less
than or equal to 50 lb/24 h, the harvest rate shall be rounded to the
nearest 0.1 lb/24 h.
DOE also proposed in the December 2021 NOPR to specifically state
that all calculations must be performed with raw measured values and
that only the resultant energy use, condenser water use, and harvest
rate metrics be rounded. 86 FR 72322, 72349.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
with this assessment, but requested that any clarification be addressed
by the ASHRAE 29 standard committee.
[[Page 65889]]
(Hoshizaki, No. 14, p. 6; AHRI, No. 13, p. 9)
DOE has determined to amend the test procedure in this final rule
to require that all calculations must be performed with raw measured
values and that only the resultant energy use, water use, and harvest
rate metrics be rounded.
In addition, ASHRAE Standard 29-2015 specifies stabilization
requirements in terms of either percent or absolute weight without
specifically referencing a calculation for percent variation. In the
December 2021 NOPR, DOE proposed to apply the following equation to
calculate the percent difference between any two measurements. 86 FR
72322, 72349. This includes any calculation to determine if the ice
production rate has stabilized between cycles or samples, as described
in section III.D.2.
[GRAPHIC] [TIFF OMITTED] TR01NO22.000
The proposed equation for calculating percent difference may affect
when a unit meets the stability criteria, but DOE determined it would
not affect the stabilization determination for any of the over 50 ice
maker tests conducted prior to this rulemaking. 86 FR 72322, 72344.
In the December 2021 NOPR, DOE requested comment on its proposal to
clarify that percent difference shall be calculated based on the
average of the two measured values. 86 FR 72322, 72349.
In response to the December 2021 NOPR, Hoshizaki agreed that this
proposal can help in understanding of how percent difference is
calculated and should be spelled out in the Code of Federal
Regulation's language but requested that this be addressed by the
ASHRAE 29 standard committee. (Hoshizaki, No. 14, p. 7) AHRI agreed
with DOE that these could be valid proposed changes. (AHRI, No. 13, p.
9)
To ensure consistency in stability determinations, DOE is amending
the test procedure in this final rule to require that percent
difference be calculated based on the average of the two measured
values.
8. Potable Water Use
The water use of an ACIM includes water used in making the
harvested ice; any dump or purge water used as part of the ice making
process; and for water-cooled ACIMs, the water used to transfer heat
from the condenser. In establishing initial standards for ACIMs,
Congress addressed the latter type of water use. For ACIMs that produce
cube type ice with capacities between 50 and 2,500 pounds per 24-hour
period, EPCA specified maximum condenser water use rates (in gallons
per 100 pounds of ice). (42 U.S.C. 6313(d)(1)) In a note to the table
establishing initial maximum condenser water use rates, the statute
provides that ``Water use is for the condenser only and does not
include potable water used to make ice.'' (Id.)
In the January 2012 final rule, DOE noted that 42 U.S.C. 6313(d)
does not require DOE to develop a water conservation test procedure or
standard for potable water use in cube type ice makers or other ACIMs;
rather, it sets forth energy and condenser water use standards for cube
type ice makers at 42 U.S.C. 6313(d)(1), and allows, but does not
require, the Secretary to issue analogous standards for other types of
ACIMs under 42 U.S.C. 6313(d)(2). 77 FR 1591, 1605.
DOE further stated that ambiguous statutory language may lead to
multiple interpretations in the development of regulations. Id. DOE
stated that the statutory language is unclear whether the footnote on
potable water use that appears in 42 U.S.C. 6313(d)(1) has a
controlling effect on 42 U.S.C. 6313(d)(2) and 42 U.S.C. 6313(d)(3)--
the statutory direction to review and consider amended standards. Id.
Potable water use is not referenced anywhere else in 42 U.S.C. 6313(d),
and thus it is difficult to determine whether this footnote is a
clarification or a mandate in regard to cube type ice makers, and
furthermore, whether it would apply to the regulation of other types of
ACIMS. Id.
DOE also stated that while there is generally a positive
correlation between energy use and potable water use, DOE understands
that at a certain point the relationship between potable water use and
energy consumption reverses due to scaling. Id. Based on this fact, and
given the added complexity inherent to the regulation of potable water
use and the concomitant burden on ACIM manufacturers, DOE did not
establish regulations or require testing and reporting of the potable
water use of ACIMs. Id. Without a clear mandate from Congress on
potable water use generally, and given that Congress chose not to
regulate potable water use for cube type ice makers by statute, DOE
exercised its discretion in choosing not to include potable water use
rate in its test procedure for ACIMs. Id.
ASHRAE Standard 29-2015 and AHRI Standard 810 (I-P)-2016 with
Addendum 1 include measurements and rating requirements for potable
water use. The measurement of ``non-condenser'' potable water use
(i.e., water used in making the harvested ice and any dump or purge
water) is currently not specified by the DOE test procedure, but is
required by other programs, such as ENERGY STAR \34\ and the AHRI
certification program.\35\
---------------------------------------------------------------------------
\34\ The ENERGY STAR specification for automatic commercial ice
makers is available at www.energystar.gov/sites/default/files/Final%20V3.0%20ACIM%20Specification%205-17-17_1.pdf.
\35\ www.ahrinet.org/Certification.aspx.
---------------------------------------------------------------------------
As stated in the March 2019 RFI, DOE reviewed the relationship
between potable water use with harvest rate and daily energy
consumption by analyzing reported ACIM data from the AHRI directory and
the ENERGY STAR product database.36 37 84 FR 9979, 9986. DOE
observed that all continuous ice makers had reported values for potable
water use per 100 pounds of ice between 11.9 and 12.0 gallons because
all the water is converted to produced ice. Id. In contrast, potable
water use varies for batch type ice makers because a portion of the
potable water is drained from the sump at the end of each ice making
cycle--this portion is different for different ice maker models. Id.
The relationship between potable water use and daily energy consumption
of the AHRI and ENERGY STAR data is not identifiable when considering
the entire dataset. Id.
---------------------------------------------------------------------------
\36\ Available at www.ahridirectory.org/NewSearch?programId=31&searchTypeId=3.
\37\ Available at www.energystar.gov/productfinder/product/certified-commercial-ice-machines/results.
---------------------------------------------------------------------------
Because energy use can be affected by many factors other than
potable water use, the lack of a clear trend between energy use and
potable water use does not provide a definitive indication of the
extent of the relationship between energy use and potable water use. 86
FR 72322, 72350. Although the exact
[[Page 65890]]
relationship between potable water use and energy use is not
understood, potable water use does impact energy use. Id. An ACIM must
chill the entering potable water to some extent. Id. The extent to
which potable water is not directly converted to ice, it still is
likely cooled to 32 [deg]F. Id. Cooled potable water that is not
directly converted to ice and is drained from the unit represents lost
refrigeration capacity. Id. As such, reducing potable water use may
provide the potential for reduced energy consumption. Id.
In the December 2021 NOPR, DOE initially determined that ACIMs
currently available on the market have a wide range of potable water
use, and the relationship between potable water use and energy use and
harvest rate is not clear. 86 FR 72322, 72350. Based on its inclusion
in the AHRI certification program and ENERGY STAR qualification
criteria, potable water use may be a useful measurement as part of
characterizing the energy use associated with ACIM performance. Id. To
align with the AHRI certification program and ENERGY STAR, while
allowing for a measurement of potable water use that is consistent with
the test requirements proposed in the December 2021 NOPR for energy
use, harvest rate, and condenser water use, DOE proposed in the
December 2021 NOPR to include measurement of potable water use in the
DOE ACIM test procedure at 10 CFR 431.134. Id. Because DOE does not
regulate ACIM potable water use, testing for the potable water
measurements under the proposed approach would be voluntary. Id.
Specifically, DOE did not propose to require manufacturers to conduct
the potable water provisions of the test procedure, and manufacturers
would not report the results of the potable water test to DOE, if
conducted. Id. In addition, DOE stated that manufacturers would not be
required to use the voluntary test procedure as the basis of any
representations of potable water use. Id.
DOE proposed that the measurement of potable water use would
generally follow the test methods in AHRI Standard 810 (I-P)-2016 with
Addendum 1 and ASHRAE Standard 29-2015, but with the additional test
procedure amendments as proposed in the December 2021 NOPR. 86 FR
72322, 72350. This proposed approach is generally consistent with the
methods currently used for the AHRI and ENERGY STAR programs;
additionally, DOE does not expect that the additional test provisions
as proposed in the December 2021 NOPR would impact performance as
measured under the existing approaches used by AHRI (AHRI Standard 810
(I-P)-2016 with Addendum 1) or ENERGY STAR (AHRI Standard 810-2007).
Id.
DOE also proposed to add a definition of ``potable water use'' in
10 CFR 431.132. 86 FR 72322, 72350. DOE proposed to define ``potable
water use'' as the amount of potable water used in making ice, which is
equal to the sum of the ice harvested, dump or purge water, and the
harvest water, expressed in gal/100 lb, in multiples of 0.1, and
excludes any condenser water use. Id. This definition is generally
consistent with the term ``potable water use rate'' in AHRI Standard
810 (I-P)-2016 with Addendum 1, with the clarification that condenser
water use is not considered potable water use. Id.
In the December 2021 NOPR, DOE noted that AHRI Standard 810 (I-P)-
2016 with Addendum 1 specifies under the ``Certified Ratings'' section
that potable water use rate is applicable to batch type ice makers
only, but that AHRI's Directory of Certified Product Performance
includes the potable water use rate for both batch type and continuous
type ACIMs.\38\ 86 FR 72322, 72350. Thus, the industry standard appears
to currently be used for measuring potable water use for both batch and
continuous ice makers. Id.
---------------------------------------------------------------------------
\38\ www.ahridirectory.org/NewSearch?programId=31&searchTypeId=3.
---------------------------------------------------------------------------
In the December 2021 NOPR, DOE requested comment on the proposal to
include a voluntary method for measuring potable water use, including
the value or drawbacks of such an approach, in 10 CFR 431.134 according
to the industry standards and additional test procedure proposals as
discussed in the NOPR. 86 FR 72322, 72350.
In response to the December 2021 NOPR, Hoshizaki and AHRI commented
that potable water requirements are not covered by the regulation today
and added that potable water restrictions should be reviewed against
sanitation requirements to ensure no issues or impact on performance.
(Hoshizaki, No. 13, p. 9; AHRI, No. 13, p. 9) Hoshizaki added that
ASHRAE 29 and AHRI 810 account for the collected water use. (Hoshizaki,
No. 14, p. 7)
The Joint Commenters and CA IOUs encouraged DOE to require that
potable water use be measured and reported, which would ensure that
information about the potable water use of all ice maker models is
available to purchasers so that they can make informed decisions.
(Joint Commenters, No. 15, p. 3; CA IOUs, No. 16, p. 4) The CA IOUs
added that due to the ambiguous relationship between potable water use
and efficiency, more reporting from manufacturers will elucidate these
impacts. (CA IOUs, No. 16, p. 7) The CA IOUs supported DOE's potable
water usage measurement. (CA IOUs, No. 16, p. 4)
The Joint Commenters stated that manufacturers are already
measuring potable water use as part of the ENERGY STAR and AHRI
certification and programs. (Joint Commenters, No. 15, p. 3) The CA
IOUs commented that ASHRAE 29 covers water consumption methodology;
however, manufacturers only report water consumption data to ENERGY
STAR, which covers approximately 30 percent of the market. (CA IOUs,
No. 16, p. 4) The Joint Commenters added that while most ACIM models in
the AHRI directory meet the ENERGY STAR potable water use requirements,
the three highest water-consuming models consume 120%, 97%, and 72%
more potable water than the ENERGY STAR requirements. Id. The CA IOUs
commented that two major manufacturers represent most models in the
ENERGY STAR database, with harvest rates ranging from approximately 200
lb/day to 1800 lb/day. (CA IOUs, No. 16, p. 5-6) The CA IOUs further
added that one of the manufacturer's machines consistently use more
water, and this water use does not appear to correlate with energy use.
Id. The CA IOUs stated that there is only a strong relationship between
water and energy use for smaller self-contained ice machine categories
and did not show a relationship for ice making heads and remote
condensed units. Id.
The CA IOUs commented that DOE's NOPR cites ``Prohibited
Representations,'' to avoid imposing a mandate for representations with
regard to potable water use (86 FR 72322, 72350); however, CA IOUs
stated that nowhere in this provision does Congress bar DOE from
imposing a representation requirement for water use. Id.
CA IOUs commented that currently, the ASHRAE 29 test method does
not adequately capture water consumption from purge cycles, which may
occur every one to twelve harvest cycles and can be adjusted by a
technician in the field, and recommended that purge cycle water
consumption should be measured for batch machines and integrated into
the reported total water consumption of the machine. (CA IOUs, No. 16,
p. 4) The CA IOUs added that the results for energy use may differ;
energy use may increase as pre-cooled water near the freezing point is
lost as purge water, or it may decrease if additional dump and purge
water leads to lessened scaling in the ice maker. Id.
[[Page 65891]]
Because DOE does not regulate ACIM potable water use and because
the DOE test procedures are used to determine compliance with energy
and condenser water use (as applicable) standards, the harvest rate,
energy use, and condenser water use (as applicable) are the relevant
required metrics. DOE acknowledges that potable water use may be a
useful measurement as part of characterizing the performance of an ACIM
and is providing a repeatable and reproducible test method that allows
potable water use to be tested consistently with the other performance
metrics. DOE is maintaining in this final rule a voluntary method for
measuring potable water use in 10 CFR 431.134 that generally follows
the test methods in AHRI Standard 810 (I-P)-2016 with Addendum 1 and
ASHRAE Standard 29-2015 with some modifications, consistent with the
December 2021 NOPR.
In the December 2021 NOPR, DOE did not propose to adjust potable
water use based on ice hardness factor, as is currently required for
energy use and condenser water use. 86 FR 72322, 72351. Both energy use
and condenser water use correspond to the amount of heat removed from
the potable water in producing ice. Id. Ice that is more completely
frozen will require more energy use and more heat rejection (via
condenser water use, if applicable). Id. However, potable water use
does not similarly vary depending on the ice hardness. Id. The same
amount of potable water is used to make partially frozen ice as
completely frozen ice. Id. This is supported by nearly all continuous
ice makers showing the same 11.9 to 12 gallons of potable water use per
100 lbs of ice production. Id.
In the December 2021 NOPR, DOE requested comment on its proposal
that potable water use is not adjusted based on ice hardness factor. 86
FR 72322, 72351.
In response to the December 2021 NOPR, Hoshizaki and AHRI agreed
that potable water should not be adjusted based on ice hardness.
(Hoshizaki, No. 14, p. 7; AHRI, No. 13, p. 9)
DOE has determined in this final rule to not adjust the potable
water use based on ice hardness.
Potable water use for portable ACIMs is different than for ACIMs
with a fixed water connection. As discussed, portable ACIMs require
that the fill reservoir be filled manually with the maximum volume of
water that is recommended by the manufacturer. In a portable ACIM, the
unused ice collected in the ice storage bin slowly melts. This melt
water is recycled back into the potable water reservoir to be reused.
Unlike batch type non-portable ACIMs, there is no dump or purge water
to be measured. For portable ACIMs, water introduced to the reservoir
is typically only removed from the unit as ice (and any corresponding
melt water). Therefore, in the December 2021 NOPR, DOE proposed that
the potable water use rate for portable ACIMs be defined as equal to
the weight of ice and any corresponding melt water collected for the
capacity test as specified in section 7.2 of ASHRAE Standard 29-2015.
86 FR 72322, 72351.
In the December 2021 NOPR, DOE requested comment on the proposal
that the potable water use rate of portable ACIMs be defined as equal
to the weight of ice and water captured for the capacity test, as
specified in section 7.2 of ASHRAE Standard 29-2015. 86 FR 72322,
72351.
In response to the December 2021 NOPR, Hoshizaki agreed to the
calculation method if the ASHRAE 29-2015 standard is adopted at this
time. (Hoshizaki, No. 14, p. 7)
DOE is maintaining in this final rule that the potable water use
rate of portable ACIMs be defined as equal to the weight of ice and
water captured for the capacity test, as specified in section 7.2 of
ASHRAE Standard 29-2015, consistent with the December 2021 NOPR.
E. Representations of Energy Use and Energy Efficiency
In addition to updates to the ACIM test procedure, DOE proposed in
the December 2021 NOPR revisions to the provisions related to the
sampling plan and the determination of represented values currently
specified at 10 CFR 429.45. 86 FR 72322, 72351. DOE also proposed to
add equipment-specific enforcement provisions for ACIMs to 10 CFR
429.134. Id.
1. Sampling Plan and Determination of Represented Values
In subpart B to 10 CFR part 429, DOE provides uniform methods for
manufacturers to determine representative values of energy- and non-
energy-related metrics for each basic model of covered equipment. The
purpose of a statistical sampling plan is to provide a method to ensure
that the test sample size (i.e., number of units tested) is
sufficiently large that represented values of energy- and non-energy-
related metrics are representative of aggregate performance of the
units in the basic model, while accounting for variability inherent to
the manufacturing and testing processes.
DOE currently specifies the ACIM-specific sampling plans and
requirements for the determination of represented values at 10 CFR
429.45. The sampling plan and method for determining represented values
applies to represented values of maximum energy use, or other measures
of energy consumption for which consumers would favor lower values.
The reference to ``maximum energy use'' and ``maximum condenser
water use'' in 10 CFR 429.45 could be misinterpreted to refer to the
energy and water conservation standard levels for that basic model
(i.e., the maximum allowable energy and maximum allowable condenser
water use), as opposed to the tested performance. Therefore, in the
December 2021 NOPR, for consistency and clarity, DOE proposed to
replace the term ``maximum energy use'' with the term ``energy use''
and the term ``maximum condenser water use'' with the term ``condenser
water use.'' 86 FR 72322, 72351. In addition, values of both energy and
condenser water consumption are relevant for ACIMs. As such, DOE
proposed to modify the language at 10 CFR 429.45 to specify expressly
that the sampling plan at 10 CFR 429.45(a)(2)(i) applies both to
measures of energy and condenser water use for which consumers would
favor lower values. Id.
Similarly, 10 CFR 431.132 includes a definition for the term
``maximum condenser water use.'' This language may also be
misinterpreted to refer to the condenser water conservation standard
level for a basic model as opposed to the tested condenser water use.
Therefore, in the December 2021 NOPR, DOE proposed to modify the term
and definition of ``maximum condenser water use'' to instead refer to
the term ``condenser water use.'' 86 FR 72322, 72351. This modification
is consistent with the existing definition of ``energy use'' in 10 CFR
431.132.
In 10 CFR 429.45(a)(2)(ii), DOE also specifies calculation
procedures for energy efficiency metrics, or measures of energy
consumption where consumers would favor higher values. As DOE's test
procedure does not require determining any values of energy efficiency
or other measure of performance for which consumers would favor higher
values, DOE proposed to remove this provision in the December 2021
NOPR. 86 FR 72322, 72351.
In addition to energy related metrics, 10 CFR 429.45 mandates the
reporting of harvest rate, a key non-energy metric associated with
determining energy and condenser water standards for ACIM equipment, as
applicable. However, 10 CFR 429.45 does not specify how the represented
value of harvest rate for
[[Page 65892]]
each basic model should be determined based on the test results from
the sample of individual models tested. Similar to the requirements for
other covered products and commercial equipment, DOE proposed in the
December 2021 NOPR that the represented value of harvest rate for the
basic model be determined as the mean of the measured harvest rates for
each unit in the test sample, based on the same tests used to determine
the reported energy use and condenser water use, if applicable. 86 FR
72322, 72351. Although not specified in 10 CFR 429.45, DOE expected
manufacturers are currently certifying ACIM performance based on the
tested harvest rates. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
amend the sampling plan and reporting requirements for ACIMs in 10 CFR
429.45. 86 FR 72322, 72351. DOE sought information on how manufacturers
are currently interpreting ``maximum energy use'' and ``maximum
condenser water use'' in the context of the sampling and certification
report requirements, how manufacturers are currently determining
harvest rates, and whether the proposed amendments would impose any
burden on manufacturers. Id. DOE also requested comment on its proposal
to modify the term and definition of ``maximum condenser water use'' to
instead refer to ``condenser water use''. Id.
In response to the December 2021 NOPR, Hoshizaki and AHRI commented
that further clarification is needed for this proposal. (Hoshizaki, No.
14, p. 7; AHRI, No. 13, p. 9) Hoshizaki requested that this be brought
to the ASHRAE 29 standard committee for clarification and comment.
(Hoshizaki, No. 14, p. 7)
AHRI commented that the definitions used by the method of test and
rating standards are accurate today and should be adopted by DOE
without modification. (AHRI, No. 13, p. 9-10) AHRI added that there are
differences between reporting for some certification programs and DOE
reporting although all values are determined per the current method of
test and rating standard. (AHRI, No. 13, p. 9-10)
The sampling plan and determination of represented values
amendments proposed in the December 2021 NOPR would clarify the
terminology and requirements and would not impose any additional burden
on manufacturers because DOE believes the clarifications are consistent
with how manufacturers are currently testing.
DOE is maintaining in this final rule the amends to the sampling
plan and reporting requirements for ACIMs in 10 CFR 429.45, replacing
the term ``maximum energy use'' and ``maximum condenser water use'' in
10 CFR 429.45 with the term ``energy use'' and ``condenser water use'',
respectively, and modifying the term and definition of ``maximum
condenser water use'' at 10 CFR 431.132 to instead refer to ``condenser
water use'', consistent with the December 2021 NOPR.
2. Test Sample Value Rounding Requirements
DOE currently requires test results for ACIMs to be rounded, as
discussed in section III.D.7; however, the requirements in 10 CFR
429.45 do not specify how values calculated in accordance with 10 CFR
429.45(a) would be rounded. To ensure consistency, DOE proposed, in the
December 2021 NOPR, that any calculations according to 10 CFR 429.45 be
rounded consistent with the rounding requirements for individual test
results. 86 FR 72322, 72351-72352. Specifically, DOE proposed to
require that values calculated from a test sample be rounded as
follows: energy use to the nearest 0.01 kWh/100 lb, condenser water use
to the nearest gal/100 lb, and harvest rate to the nearest 1 lb/24 h
(for ACIMs with harvest rates greater than 50 lb/24 h) or to the
nearest 0.1 lb/24 h (for ACIMs with harvest rates less than or equal to
50 lb/24 h). 86 FR 72322, 72352.
In the December 2021 NOPR, DOE requested comment on its proposal to
require that values calculated from a test sample be rounded as
follows: energy use to the nearest 0.01 kWh/100 lb, condenser water use
to the nearest gal/100 lb, and harvest rate to the nearest 1 lb/24 h
(for ACIMs with harvest rates greater than 50 lb/24 h) or to the
nearest 0.1 lb/24 h (for ACIMs with harvest rates less than or equal to
50 lb/24 h). 86 FR 72322, 72352.
In response to the December 2021 NOPR, Hoshizaki and AHRI requested
that any changes to the calculation of values be addressed by the AHRI
810 standard committee. (Hoshizaki, No. 14, p. 7; AHRI, No. 13, p. 10)
AHRI added that changes made during this rulemaking should be
consistent with the current version of AHRI Standard 810, and DOE is
welcome to participate in any AHRI standard working groups to provide
suggestions for consideration. (AHRI, No. 13, p. 10)
As discussed in section III.D.7, DOE is amending the rounding
requirements in this final rule to be consistent with AHRI Standard 810
(I-P)-2016 with Addendum 1, except that for ACIMs with harvest rates
less than or equal to 50 lb/24 h, the harvest rate shall be rounded to
the nearest 0.1 lb/24 h.
DOE is maintaining in this final rule that values calculated from a
test sample are required to be rounded as follows: energy use to the
nearest 0.01 kWh/100 lb, condenser water use to the nearest gal/100 lb,
and harvest rate to the nearest 1 lb/24 h (for ACIMs with harvest rates
greater than 50 lb/24 h) or to the nearest 0.1 lb/24 h (for ACIMs with
harvest rates less than or equal to 50 lb/24 h), consistent with the
December 2021 NOPR.
3. Enforcement Provisions
Subpart C of 10 CFR part 429 establishes enforcement provisions
applicable to covered products and covered equipment, including ACIMs.
Product-specific enforcement provisions are provided in 10 CFR 429.134,
but that section currently does not specify product-specific
enforcement provisions for ACIMs. The DOE requirements in 10 CFR
429.134 provide which ratings or measurements will be used to determine
the applicable energy or condenser water conservation standard.
Normally, DOE provides that the certified metric would be used for
enforcement purposes (e.g., calculation of the applicable energy
conservation standard) if the average value measured during enforcement
testing is within a specified percent of the rated value (the specific
allowable range varies based on product and equipment type). Otherwise,
the average measured value would be used.
Section 7.1 of ASHRAE Standard 29-2009, incorporated by reference
into the DOE ACIM test procedure, allows for a two percent weight
variation between collected ice samples when establishing stability of
an ACIM. Additionally, section 5.5.1 of ASHRAE Standard 29-2009
specifies that the ice-weighing instruments are required to be accurate
to within 1.0 percent of the quantity measured. Due to the allowable
variability in test measurements, a five percent tolerance around the
rated capacity value likely is appropriate for ACIMs. This tolerance is
consistent with the tolerance for ice harvest rate ratings as specified
in section 5.4 of AHRI Standard 810 (I-P)-2016 with Addendum 1. In the
December 2021 NOPR, DOE proposed that the certified capacity metric for
ACIMs (i.e,, the harvest rate) will be used for determination of the
maximum allowable energy consumption and maximum allowable condenser
water use levels only if the average measured harvest rate during DOE
testing is within five percent of the certified harvest rate. 86 FR
72322, 72352. If the
[[Page 65893]]
average measured harvest rate is found to be outside of this range when
compared to the certified harvest rate, the average measured harvest
rate of the units in the tested sample will be used as the basis for
determining the maximum allowable energy consumption and maximum
allowable condenser water use levels, as applicable. Id.
In the December 2021 NOPR, DOE requested comment on its proposal to
include a new paragraph in 10 CFR 429.134 to specify how to determine
whether the certified or measured harvest rate is used to calculate the
maximum energy consumption and maximum condenser water use levels. 86
FR 72322, 72352. DOE also requested comment on whether a five percent
tolerance for the average measured harvest rate compared to the
certified harvest rate is an appropriate tolerance for such purposes,
and if not, what tolerance is appropriate. Id.
In response to the December 2021 NOPR, Hoshizaki commented that
further clarification is needed to determine a response. (Hoshizaki,
No. 14, p. 7) Hoshizaki requested that this be brought to the ASHRAE 29
standard committee for clarification and comment. (Hoshizaki, No. 14,
p. 7)
Subpart C of 10 CFR 429.134 establishes product-specific
enforcement provisions applicable to covered products and covered
equipment. The DOE requirements in 10 CFR 429.134 provide which ratings
or measurements will be used to determine the applicable energy or
water conservation standard. DOE's enforcement provisions are outside
the scope of industry standards and, therefore, ASHRAE 29 does not
apply to DOE's enforcement provisions.
DOE is maintaining in this final rule the inclusion of a new
paragraph in 10 CFR 429.134 to specify how to determine whether the
certified or measured harvest rate is used to calculate the maximum
energy consumption and maximum condenser water use levels and to
establish a five percent tolerance for the average measured harvest
rate compared to the certified harvest rate, consistent with the
December 2021 NOPR.
F. Test Procedure Costs and Harmonization
1. Test Procedure Costs and Impact
In this final rule, DOE amends the ACIM test procedure to include
low-capacity ACIMs in the scope of the test procedure; references the
most recent versions of the test procedures incorporated by reference;
clarifies the stability criteria; revises clearances for test
installations; includes additional updates to clarify appropriate test
measurements, conditions, settings, and setup requirements; establishes
provisions for the voluntary measurement of potable water use; and
updates calculation instructions. The following paragraphs discuss
DOE's determination of any impacts on testing costs or measured
performance resulting from these amendments.
a. Testing Cost Impacts
i. Per-Test Cost
In the January 2012 final rule, DOE estimated a per-test cost of
$5,000 to $7,500 for the current ACIM test procedure. 77 FR 1591, 1610.
In the December 2021 NOPR, DOE initially determined that the low end of
that range, or $5,000, is representative of current ACIM per test cost.
86 FR 72322, 72352.
As discussed in section III.D.2, the current test procedure
requires multiple cycles to determine stability, after which additional
cycles are performed to measure performance. In this final rule, DOE
references the updated version of ASHRAE Standard 29-2015, which
includes updated stabilization requirements, and expressly requires
that the cycles or samples used for the capacity test are stable, thus
eliminating the need to perform separate cycles for meeting the
stability criteria and for testing performance (i.e., reducing the
total number of cycles required for testing). For batch ice makers,
this amendment will eliminate the need for testing two cycles prior to
the test. For continuous ice makers, this amendment will eliminate the
need for measuring three consecutive 14.4 min samples taken within a
1.5-hour period prior to the test.
In the December 2021 NOPR, DOE estimated that total ice maker test
duration, including set up, pull-down, and test operation currently
requires 8 hours. 86 FR 72322, 72352. Under the amended approach,
consistent with the December 2021 NOPR, DOE estimates that the total
test time will decrease by approximately 1 hour, representing a 12.5-
percent reduction in test duration. Taking overhead costs into account,
consistent with the December 2021 NOPR, DOE estimates that the proposed
stabilization requirement will decrease the test cost by approximately
6 percent, or $300 per test based on the initial $5,000 per-test
estimate. Because DOE requires manufacturers to test at least two units
per model to certify performance, testing will cost manufacturers
approximately $600 less per basic model for all future basic models
tested in accordance with this amended test procedure, resulting in a
total test cost of $9,400 per basic model.\39\
---------------------------------------------------------------------------
\39\ Based on a new per-test cost of $4,700.
---------------------------------------------------------------------------
In response to the December 2021 NOPR, Hoshizaki commented that the
use of test cycles to confirm stability is already done, so no
additional cost is associated. (Hoshizaki, No. 14, p. 7)
AHRI commented that stability should be determined in accordance
with ASHRAE Standard 29 Provisions to avoid any incurred cost to
testing. (AHRI, No. 13, p. 10)
IOM commented that DOE's proposal to further restrict the
definition of ``stability'' has the potential to increase burden and
cost, as all test cycles must have ice harvest rates within 2% rather
than consecutive test cycles. (IOM, No. 11, p. 3)
AHAM commented that DOE deviated from ASHRAE and AHRI standards in
some ways in order to create a test procedure that could be applicable
to residential products but that the proposed test and its deviations
are unworkable, unrealistic, and burdensome given the way residential
appliance manufacturers carry out testing and the test facilities
residential ice maker manufacturers have. (AHAM, No. 18, p. 9) AHAM
also stated that since the proposed test requires complete attention to
the test once it starts, the technician must be dedicated to this test
due to the time requirements of 15 minutes for the fill, plus-or-minus
nine seconds to empty the bin, and the five minute requirement to start
the next test. (AHAM, No. 18, p. 13-14) AHAM states that this is a
burdensome requirement because it will require active monitoring by the
test technician as opposed to a test that can be largely automated,
which may require manufacturers to hire additional technicians. Id.
DOE acknowledges the comment regarding the potential for the
amended stability requirements to increase burden and cost. Although it
is possible a test unit will require additional cycles to meet the
amended stability requirements, based on investigative testing using
the amended stability requirements, DOE observed that the average
number of cycles or samples required to reach stability was 3.0 based
on a sample of 39 batch ACIM tests and 6 continuous ACIM tests which
indicates that unstable operation would represent a minority of tests
conducted. DOE estimates that the total test time will decrease by
approximately 1 hour, representing a 12.5-percent reduction in
[[Page 65894]]
test duration, for the majority of tests conducted. The amended
stability requirements address unstable operation to ensure repeatable
and reproducible test results.
DOE reaffirms its determination that testing will cost
manufacturers approximately $600 less per basic model for all future
basic models tested in accordance with this amended test procedure, as
compared to the existing test procedure. DOE recognizes that testing
does require facilities and technician labor, and maintains the cost
estimate of $4,700 per individual test or $9,400 when testing to
certify performance of a basic model (requiring at least two test
units).
ii. One-Time Cost
As discussed in section III.D.3.a, this final rule implements a
relative humidity test condition.
In the December 2021 NOPR, DOE estimated the one-time cost for
purchasing relative humidity controls to range from $1,000 to $5,000,
depending on the method that is chosen. 86 FR 72322, 72353. DOE
estimated that the purchase and installation of a humidifier boiler
with modulating valves that releases steam on the wall to control
relative humidity costs $5,000, although less expensive options could
be used, such as a dedicated coil with reheat, steam generators,
humidifiers, and dehumidifiers. Id. In addition, DOE also estimated
that instrumentation to measure relative humidity at an accuracy of
2 percent costs around $500.\40\ Id.
---------------------------------------------------------------------------
\40\ For example, see Campbell Scientific model EE181-L at
www.campbellsci.com/ee181-l.
---------------------------------------------------------------------------
Hoshizaki and AHRI stated that upgrading facilities for water
hardness and relative humidity could incur significant facility upgrade
costs. (Hoshizaki, No. 14, p. 8; AHRI, No. 13, p. 10-11) AHAM stated
that the relative humidity requirement is unduly burdensome for
manufacturers. (AHAM, No. 18, p. 12-13) AHAM commented that unless the
test chamber was initially designed with dehumidification capabilities
and appropriately sealed, there is a significant investment to achieve
the 35.0 5.0 percent levels required in the proposed test
procedure. Id. Residential ice maker manufacturers have not built test
chambers with these capabilities in mind and, thus, this provision
would likely require all manufacturers to overhaul their test
facilities. Id.
Hoshizaki stated that extending tests for purge water and/or
standby energy would require additional test time that would hamper
design cycles. (Hoshizaki, No. 14, p. 8)
This final rule does not implement water hardness requirements as
proposed in the December 2021 NOPR. Similarly, this final rule does not
directly account for energy or water used during intermittent flush or
purge cycles nor accounts for standby or ice storage energy use.
Regarding humidity controls, DOE has reviewed and maintains its
estimates from the December 2021 NOPR regarding the costs associated
with purchasing relative humidity controls and instrumentation, as
described in this section.
As discussed in section III.A, this final rule expands the scope of
the test procedure to include low-capacity ACIMs. This final rule
incorporates additional test procedure requirements to ensure
appropriate testing of low-capacity ACIMs, as discussed in section
III.D.1. In the December 2021 NOPR, DOE requested comment on any
expected costs associated with the proposed amendment to expand test
procedure scope to include low-capacity ACIMs. 86 FR 72322, 72353.
Specifically, DOE requested comment on whether any manufacturers are
currently making representations of low-capacity ACIM energy
consumption based on test methods that would produce measures of
performance that would be inconsistent with the existing DOE test
procedure or the test procedure for low-capacity ACIMs as proposed in
the December 2021 NOPR. 86 FR 72322, 72353-72354.
DOE stated in the December 2021 NOPR that based on a review of low-
capacity ACIMs available on the market, DOE preliminarily determined
that manufacturers either make no claims regarding the energy
consumption of their low-capacity ACIM models, or currently specify
energy consumption in accordance with the existing DOE test procedure
(and referenced industry standards). DOE stated that it expects that
the manufacturers currently electing to make no claims regarding low-
capacity ACIM energy consumption will continue to do so even after a
test procedure is established.
In response to the December 2021 NOPR, Hoshizaki commented there
are representations of low-capacity ACIM energy consumption.
(Hoshizaki, No. 14, p. 8) However, Hoshizaki and AHRI commented that
low-capacity ACIMs were not included in the scope for DOE's 2010 or
2018 ACIM energy conservation standards. (Hoshizaki, No. 14, p. 8;
AHRI, No. 13, p. 11) AHRI urged DOE to exclude low-capacity units until
they are included into the appropriate method of test because including
these units would require significant testing to factor the energy use
and any changes to meet the current standards designed for units above
50 pounds. (AHRI, No. 13, p. 11)
Hoshizaki requested that this be brought up in the ASHRAE 29
standard committee to discuss test method options for low-capacity
ACIMs. (Hoshizaki, No. 14, p. 8)
As discussed, DOE estimates that the amended test procedure has a
per-test cost of $4,700, and that testing two basic models for
certification purposes would have a total cost of $9,400. To the extent
that manufacturers are currently voluntarily making representations of
low-capacity ACIM energy consumption based on test methods inconsistent
with the DOE test procedure as amended by this final rule, such
manufacturers would incur a one-time cost of $9,400 per basic model to
make voluntary representations consistent with the DOE test procedure
as amended by this final rule.
Low-capacity ACIMs are not currently subject to DOE testing or
energy conservation standards. Manufacturers will not be required to
test low-capacity ACIMs until such time as the compliance date for any
newly established energy conservation standards for such equipment.
Under the amended test procedure, were a manufacturer to choose to make
representations of the energy efficiency or energy use of a low-
capacity ACIM, beginning 360 days after publication of the final rule
in the Federal Register, manufacturers would be required to base such
representations on the DOE test procedure. (42 U.S.C. 6314(d)(1))
b. Impact on Measured Performance
DOE expects that any impact from the other amendments to the
measured efficiency of certified ACIMs is de minimis as compared to the
current test procedure, as discussed in detail for each proposal in
section III in this final rule. The amendments will generally improve
representativeness, repeatability, and reproducibility of DOE's test
procedure. Additionally, certain amendments will also incorporate test
requirements consistent with DOE guidance or test procedure waivers
already in effect for testing ACIMs.
Specifically, DOE incorporated the following amendments: (1)
updating references to the latest versions of the relevant industry
standards (see section III.C); (2) clarifying stabilization criteria;
(3) incorporating a test condition for relative humidity and a
clarification regarding water pressure (see section
[[Page 65895]]
III.D.3); (4) establishing and clarifying test setup and setting
requirements (see section III.D.4); (5) specifying a voluntary
measurement of potable water use (see section III.D.8); and (6)
including revisions to test sample calculations and enforcement
provisions (see section III.E).
In response to the December 2021 NOPR, Hoshizaki and AHRI commented
that addressing all the proposed amendments would necessitate retesting
most ACIM units, placing undue burden on manufacturers. (Hoshizaki, No.
14, p. 8; AHRI, No. 13, p. 10-11) Hoshizaki added that the proposals
would require testing of 190 models with multiple samples of each.
(Hoshizaki, No. 14, p. 8)
DOE does not agree with Hoshizaki and AHRI's assertions that the
amended test procedure would necessitate retesting most ACIM units. As
this final rule discusses within each relevant section, DOE expects
that any impact on measured performance from these amendments is
expected to be de minimis as compared to the current test procedure.
Equipment with no measurable change to energy use under the amended
test procedure would not need to be retested. To the extent that a
manufacturer determines that a particular test procedure amendment
would impact the existing measured energy use for a specific basic
model, DOE estimates a re-testing cost of $9,400 per basic model.
2. Harmonization With Industry Standards
DOE's established practice is to adopt relevant industry standards
as DOE test procedures unless such methodology would be unduly
burdensome to conduct or would not produce test results that reflect
the energy efficiency, energy use, water use (as specified in EPCA) or
estimated operating costs of that product during a representative
average use cycle. 10 CFR 431.4; section 8(c) of appendix A to subpart
C of part 430. In cases where the industry standard does not meet EPCA
statutory criteria for test procedures, DOE will make modifications
through the rulemaking process to these standards and incorporate the
modified standard as the DOE test procedure.
The test procedure for ACIMs at 10 CFR 431.134 incorporates by
reference certain provisions of AHRI Standard 810-2007 and ASHRAE
Standard 29-2009. DOE references 810-2007 for definitions and test
procedure requirements. DOE references ASHRAE Standard 29-2009 for test
procedure requirements and ice hardness factor calculations. In January
2018, AHRI released an updated version of the 810 Standard which DOE
evaluated as part of this rulemaking. In January 2015, ASHRAE released
an updated version of the 29 Standard which DOE evaluated as part of
this rulemaking. The industry standards DOE is incorporating by
reference via amendments described in this final rule are discussed in
further detail in section IV.N.
G. Effective and Compliance Dates
The effective date for the adopted test procedure amendment will be
30 days after publication of this final rule in the Federal Register.
EPCA prescribes that all representations of energy efficiency and
energy use, including those made on marketing materials and product
labels, must be made in accordance with an amended test procedure,
beginning 360 days after publication of the final rule in the Federal
Register. (42 U.S.C. 6314(d)(1)) EPCA provides an allowance for
individual manufacturers to petition DOE for an extension of the 360-
day period if the manufacturer may experience undue hardship in meeting
the deadline. (42 U.S.C. 6314(d)(2)) To receive such an extension,
petitions must be filed with DOE no later than 60 days before the end
of the 360-day period and must detail how the manufacturer will
experience undue hardship. (Id.) To the extent the modified test
procedure adopted in this final rule is required only for the
evaluation and issuance of updated efficiency standards, compliance
with the amended test procedure does not require use of such modified
test procedure provisions until the compliance date of updated
standards.
Upon the compliance date of test procedure provisions in this final
rule any waivers that had been previously issued and are in effect that
pertain to issues addressed by such provisions are terminated. 10 CFR
431.404(h)(3). Recipients of any such waivers are required to test the
products subject to the waiver according to the amended test procedure
as of the compliance date of the amended test procedure. The amendments
adopted in this document pertain to issues addressed by a waiver
granted to Hoshizaki in Case No. 2020-001. 85 FR 68315.
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Orders 12866 and 13563
Executive Order (``E.O.'') 12866, ``Regulatory Planning and
Review,'' as supplemented and reaffirmed by E.O. 13563, ``Improving
Regulation and Regulatory Review,'' 76 FR 3821 (Jan. 21, 2011),
requires agencies, to the extent permitted by law, to (1) propose or
adopt a regulation only upon a reasoned determination that its benefits
justify its costs (recognizing that some benefits and costs are
difficult to quantify); (2) tailor regulations to impose the least
burden on society, consistent with obtaining regulatory objectives,
taking into account, among other things, and to the extent practicable,
the costs of cumulative regulations; (3) select, in choosing among
alternative regulatory approaches, those approaches that maximize net
benefits (including potential economic, environmental, public health
and safety, and other advantages; distributive impacts; and equity);
(4) to the extent feasible, specify performance objectives, rather than
specifying the behavior or manner of compliance that regulated entities
must adopt; and (5) identify and assess available alternatives to
direct regulation, including providing economic incentives to encourage
the desired behavior, such as user fees or marketable permits, or
providing information upon which choices can be made by the public. DOE
emphasizes as well that E.O. 13563 requires agencies to use the best
available techniques to quantify anticipated present and future
benefits and costs as accurately as possible. In its guidance, the
Office of Information and Regulatory Affairs (``OIRA'') in the Office
of Management and Budget (``OMB'') has emphasized that such techniques
may include identifying changing future compliance costs that might
result from technological innovation or anticipated behavioral changes.
For the reasons stated in the preamble, this final regulatory action is
consistent with these principles.
Section 6(a) of E.O. 12866 also requires agencies to submit
``significant regulatory actions'' to OIRA for review. OIRA has
determined that this final regulatory action does not constitute a
``significant regulatory action'' under section 3(f) of E.O. 12866.
Accordingly, this action was not submitted to OIRA for review under
E.O. 12866.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of a final regulatory flexibility analysis (FRFA) for any
final rule where the agency was first required by law to publish a
proposed rule for public comment, unless the agency certifies that the
rule, if promulgated, will not have a significant economic impact on a
substantial number of small entities.
[[Page 65896]]
As required by Executive Order 13272, ``Proper Consideration of Small
Entities in Agency Rulemaking,'' 67 FR 53461 (August 16, 2002), DOE
published procedures and policies on February 19, 2003, to ensure that
the potential impacts of its rules on small entities are properly
considered during the DOE rulemaking process. 68 FR 7990. DOE has made
its procedures and policies available on the Office of the General
Counsel's website: www.energy.gov/gc/office-general-counsel.
DOE reviewed this final rule under the provisions of the Regulatory
Flexibility Act and the procedures and policies published on February
19, 2003. DOE has concluded that this rule would not have a significant
impact on a substantial number of small entities. The factual basis for
this certification is as follows: The Small Business Administration
(``SBA'') considers a business entity to be a small business, if,
together with its affiliates, it employs less than a threshold number
of workers specified in 13 CFR part 121. The size standards and codes
are established by the 2017 North American Industry Classification
System (``NAICS'').
ACIM manufacturers are classified under NAICS code 333415, ``Air-
conditioning and Warm Air Heating Equipment and Commercial and
Industrial Refrigeration Equipment Manufacturing,'' which includes ice-
making machinery manufacturing.\41\ The SBA sets a threshold of 1,250
employees or fewer for an entity to be considered as a small business.
This employee threshold includes all employees in a business's parent
company and any other subsidiaries.
---------------------------------------------------------------------------
\41\ The SBA Size Standards are available at: www.sba.gov/document/support-table-size-standards (last accessed June 2, 2022).
---------------------------------------------------------------------------
DOE conducted a focused inquiry into small business manufacturers
of the equipment covered by this rulemaking. To identify companies that
import or otherwise manufacture ACIMs with harvest rates greater than
50 lb/24h, DOE expanded on the analysis conducted for the December 2021
NOPR. This updated analysis included a review of DOE's Compliance
Certification Database (``CCD''),\42\ California Energy Commission's
Modernized Appliance Efficiency Database System (``MAEDbS''),\43\ the
Air-Conditioning, Heating, and Refrigeration Institute's (``AHRI's'')
Directory of Certified Product Performance,\44\ and retailer websites.
DOE relied on retailer websites and other public sources to identify
companies that import or otherwise manufacture low-capacity ACIMs,
consistent with the December 2021 NOPR. Since the December 2021 NOPR,
and consistent with the approach detailed in the Preliminary Analysis
Technical Support Document published on March 24, 2022,\45\ DOE
conducted additional research to determine which companies selling
ACIMs in the United States are original equipment manufacturers
(``OEMs'') of the equipment covered by this rulemaking. Using publicly
available information from manufacturer websites, import and export
data (e.g., bills of lading from Panjiva) \46\ and basic model numbers,
DOE identified 22 ACIM OEMs.
---------------------------------------------------------------------------
\42\ U.S. Department of Energy Compliance Certification
Database, available at: www.regulations.doe.gov/certification-data/products.html#q=Product_Group_s%3A* (last accessed November 11,
2021).
\43\ California Energy Commission. Modernized Appliance
Efficiency Database System. Available at:
cacertappliances.energy.ca.gov/Pages/ApplianceSearch.aspx (accessed
November 17, 2021).
\44\ The Air Conditioning, Heating, and Refrigeration Institute.
Directory of Certified Product Performance. Available at:
www.ahridirectory.org/ (accessed November 17, 2021).
\45\ ``2022-03 Technical Support Document: Energy Efficiency
Program For Consumer Products And Commercial And Industrial
Equipment: Automatic Commercial Ice Makers.'' See chapter 12,
section 12.3.3 (published on March 24, 2022). Available at:
www.regulations.gov/document/EERE-2017-BT-STD-0022-0009.
\46\ Panjiva. S&P Global Supply Chain Intelligence. Available
at: panjiva.com/import-export/United-States (last accessed June 5,
2022).
---------------------------------------------------------------------------
DOE then consulted publicly available data, such as individual
company websites and subscription-based market research tools (e.g.,
Dun & Bradstreet) \47\ to determine company location, headcount, and
annual revenue. DOE screened out companies that do not offer equipment
covered by this rulemaking, do not meet the SBA's definition of a
``small business,'' or are foreign-owned and operated. Of the 22 OEMs
identified, DOE determined that two domestic OEMs qualify as ``small
businesses.'' DOE estimates that one small OEM has an annual revenue of
approximately $11.2 million and the other has an annual revenue of
approximately $186.5 million.
---------------------------------------------------------------------------
\47\ The Dun & Bradstreet Hoovers subscription login is
accessible at: /app.dnbhoovers.com/ (last accessed June 2, 2022).
---------------------------------------------------------------------------
Consistent with its preliminary determination in the December 2021
NOPR, DOE does not expect small domestic ACIM OEMs to incur costs as a
result of the amended test procedure. However, in the event that any
test facilities require upgrade to meet the amended test conditions for
relative humidity, DOE has estimated the costs of this potential
upgrade to be $5,500, as discussed in section III.F.1.a of this final
rule.\48\ DOE estimates that this potential cost would represent less
than 0.1 percent of annual revenues for both identified small
businesses.
---------------------------------------------------------------------------
\48\ DOE estimates the cost for purchasing relative humidity
controls to range from $1,000 to $5,000, depending on the method
that is chosen, and an additional cost of $500 for a relative
humidity sensor.
---------------------------------------------------------------------------
In response to the December 2021 NOPR, Hoshizaki commented that the
proposed changes would necessitate re-testing of ACIM models by many
manufacturers. Hoshizaki suggested that small entities may not have the
means to test their models in house and would have to send units to
test at third party labs. (Hoshizaki, No. 14, p. 8) AHRI noted that the
changes outlined in the December 2021 NOPR would necessitate retesting
of existing models and would therefore ``most definitely place undue
burden and additional cost on OEMs.'' Specifically, they stated that
the humidity control requirement would require retesting of every model
and would also necessitate facility upgrade costs. AHRI also asserted
that this requirement may limit the ability to find external test labs
with appropriate test chambers and thereby disadvantage small entities
who do not have the means to test in house and would be subject to
scheduling at third party testing facilities. AHRI noted that the costs
associated with the proposal ``would not be miniscule'' and such
testing would not be advantageous with all the third-party testing
needed to verify safety for ACIM's that are changing to flammable
refrigerants. AHRI also noted that the proposed 3-foot side clearance
requirement could also impact the ability of small entities
participating in this market. (AHRI, No. 13, p. 11)
As detailed in section III.F.1 of this final rule, DOE expects that
the impact from these amendments to the measured efficiency of
certified ACIMs is expected to be de minimis as compared to the current
test procedure. DOE expects that it is unlikely that a substantial
portion of ACIM units would need to be retested or recertified as a
result of this final rule, and therefore that manufacturers will be
able to rely on data generated under the existing test procedure. If a
manufacturer re-tests models according to the amended test procedure,
DOE estimates a testing cost of $9,400 per re-rated basic model.\49\
DOE notes that the small OEM with an annual revenue of approximately
$11.2 million offers four basic models. The other small OEM
[[Page 65897]]
with an annual revenue of approximately $186.5 million offers two basic
models.\50\ Therefore, DOE expects that any re-testing would account
for less than 0.1 percent of each company's annual revenue.\51\
---------------------------------------------------------------------------
\49\ Based on the $5,000 per unit test cost estimate and the
$300 savings due to the stability criteria, as detailed in this
final rule. Each basic model is tested twice: ($5,000-$300) x 2 =
$9,400.
\50\ DOE used the estimated annual revenue figures from the Dun
& Bradstreet Hoovers subscription-based market research tool. The
Dun & Bradstreet login is accessible at: /app.dnbhoovers.com/ (last
accessed June 2, 2022).
\51\ One small OEM may incur testing costs of $37,600, if they
choose to re-test their 4 models according to the amended test
procedure. (4 x $9,400 = $37,600) The other small OEM may incur
testing costs of $18,800, if they choose to re-test their 2 models
according to the amended test procedure. (2 x $9,400 = $18,800)
---------------------------------------------------------------------------
Therefore, DOE concludes that the cost effects accruing from the
final rule would not have a ``significant economic impact on a
substantial number of small entities,'' and that the preparation of a
FRFA is not warranted. DOE has submitted a certification and supporting
statement of factual basis to the Chief Counsel for Advocacy of the
Small Business Administration for review under 5 U.S.C. 605(b).
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of ACIMs must certify to DOE that their products
comply with any applicable energy conservation standards. To certify
compliance, manufacturers must first obtain test data for their
products according to the DOE test procedures, including any amendments
adopted for those test procedures. DOE has established regulations for
the certification and recordkeeping requirements for all covered
consumer products and commercial equipment, including ACIMs. (See
generally 10 CFR part 429.) The collection-of-information requirement
for the certification and recordkeeping is subject to review and
approval by OMB under the Paperwork Reduction Act (PRA). This
requirement has been approved by OMB under OMB control number 1910-
1400. Public reporting burden for the certification is estimated to
average 35 hours per response, including the time for reviewing
instructions, searching existing data sources, gathering and
maintaining the data needed, and completing and reviewing the
collection of information.
DOE is not amending the certification or reporting requirements for
ACIMs in this final rule. Instead, DOE may consider proposals to amend
the certification requirements and reporting for ACIMs under a separate
rulemaking regarding appliance and equipment certification. DOE will
address changes to OMB Control Number 1910-1400 at that time, as
necessary.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
In this final rule, DOE establishes test procedure amendments that
it expects will be used to develop and implement future energy
conservation standards for ACIMs. DOE has determined that this rule
falls into a class of actions that are categorically excluded from
review under the National Environmental Policy Act of 1969 (42 U.S.C.
4321 et seq.) and DOE's implementing regulations at 10 CFR part 1021.
Specifically, DOE has determined that adopting test procedures for
measuring energy efficiency of consumer products and industrial
equipment is consistent with activities identified in 10 CFR part 1021,
appendix A to subpart D, A5 and A6. Accordingly, neither an
environmental assessment nor an environmental impact statement is
required.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 4,
1999), imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have federalism implications. The Executive order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE examined this final
rule and determined that it will not have a substantial direct effect
on the States, on the relationship between the National Government and
the States, or on the distribution of power and responsibilities among
the various levels of government. EPCA governs and prescribes Federal
preemption of State regulations as to energy conservation for the
products that are the subject of this final rule. States can petition
DOE for exemption from such preemption to the extent, and based on
criteria, set forth in EPCA. (42 U.S.C. 6297(d)) No further action is
required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard; and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that executive agencies make every reasonable
effort to ensure that the regulation (1) clearly specifies the
preemptive effect, if any; (2) clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the retroactive effect, if any; (5) adequately defines
key terms; and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to review regulations in light of applicable standards in
sections 3(a) and 3(b) to determine whether they are met or it is
unreasonable to meet one or more of them. DOE has completed the
required review and determined that, to the extent permitted by law,
this final rule meets the relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (``UMRA'')
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. (Pub. L. 104-4, sec. 201 (codified at 2 U.S.C. 1531)).
For a regulatory action resulting in a rule that may cause the
expenditure by State, local, and Tribal governments, in the aggregate,
or by the private sector of $100 million or more in any one year
(adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The
[[Page 65898]]
UMRA also requires a Federal agency to develop an effective process to
permit timely input by elected officers of State, local, and Tribal
governments on a proposed ``significant intergovernmental mandate,''
and requires an agency plan for giving notice and opportunity for
timely input to potentially affected small governments before
establishing any requirements that might significantly or uniquely
affect small governments. On March 18, 1997, DOE published a statement
of policy on its process for intergovernmental consultation under UMRA.
62 FR 12820; also available at www.energy.gov/gc/office-general-counsel. DOE examined this final rule according to UMRA and its
statement of policy and determined that the rule contains neither an
intergovernmental mandate, nor a mandate that may result in the
expenditure of $100 million or more in any year, so these requirements
do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This final rule will not have any impact on the autonomy or integrity
of the family as an institution. Accordingly, DOE has concluded that it
is not necessary to prepare a Family Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights,'' 53 FR 8859 (March 18, 1988), that this regulation will not
result in any takings that might require compensation under the Fifth
Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). Pursuant
to OMB Memorandum M-19-15, Improving Implementation of the Information
Quality Act (April 24, 2019), DOE published updated guidelines which
are available at www.energy.gov/sites/prod/files/2019/12/f70/DOE%20Final%20Updated%20IQA%20Guidelines%20Dec%202019.pdf. DOE has
reviewed this final rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any significant energy action. A
``significant energy action'' is defined as any action by an agency
that promulgated or is expected to lead to promulgation of a final
rule, and that (1) is a significant regulatory action under Executive
Order 12866, or any successor order; and (2) is likely to have a
significant adverse effect on the supply, distribution, or use of
energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any significant energy action, the
agency must give a detailed statement of any adverse effects on energy
supply, distribution, or use if the regulation is implemented, and of
reasonable alternatives to the action and their expected benefits on
energy supply, distribution, and use.
This regulatory action is not a significant regulatory action under
Executive Order 12866. Moreover, it would not have a significant
adverse effect on the supply, distribution, or use of energy, nor has
it been designated as a significant energy action by the Administrator
of OIRA. Therefore, it is not a significant energy action, and,
accordingly, DOE has not prepared a Statement of Energy Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788;
``FEAA'') Section 32 essentially provides in relevant part that, where
a proposed rule authorizes or requires use of commercial standards, the
notice of proposed rulemaking must inform the public of the use and
background of such standards. In addition, section 32(c) requires DOE
to consult with the Attorney General and the Chairman of the Federal
Trade Commission (``FTC'') concerning the impact of the commercial or
industry standards on competition.
The modifications to the test procedure for ACIMs adopted in this
final rule incorporates testing methods contained in certain sections
of the following commercial standards: AHRI Standard 810 (I-P)-2016
with Addendum 1 and ASHRAE Standard 29-2015. DOE has evaluated these
standards and is unable to conclude whether it fully complies with the
requirements of section 32(b) of the FEAA (i.e., whether it was
developed in a manner that fully provides for public participation,
comment, and review.) DOE has consulted with both the Attorney General
and the Chairman of the FTC about the impact on competition of using
the methods contained in these standards and has received no comments
objecting to their use.
M. Congressional Notification
As required by 5 U.S.C. 801, DOE will report to Congress on the
promulgation of this rule before its effective date. The report will
state that it has been determined that the rule is not a ``major rule''
as defined by 5 U.S.C. 804(2).
N. Description of Materials Incorporated by Reference
DOE incorporates by reference the following standards:
AHRI Standard 810 (I-P)-2016 with Addendum 1. Specifically, the
test procedure codified by this final rule references section 3,
``Definitions,'' section 4, ``Test Requirements,'' and section 5.2,
``Standard Ratings''. AHRI Standard 810 (I-P)-2016 with Addendum 1 is
an industry-accepted standard that provides a method to rate the
performance of automatic commercial ice makers.
AHRI standards are reasonably available from the Air-Conditioning,
Heating, and Refrigeration Institute, 2111 Wilson Blvd., Suite 500,
Arlington, VA 22201, 703-524-8800, [email protected], or
www.ahrinet.org.
ASHRAE Standard 29-2015. ASHRAE Standard 29-2015 is an industry-
accepted standard that provides a method of test to measure the
performance of automatic commercial ice makers.
Copies of ASHRAE standards are reasonably available from the
American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Inc., 1791 Tullie Circle NE, Atlanta, GA 30329, (404) 636-
8400, [email protected], or www.ashrae.org.
[[Page 65899]]
V. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this final
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Intergovernmental relations, Reporting and recordkeeping requirements,
Small businesses.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation test procedures, Incorporation by
reference, Reporting and recordkeeping requirements.
Signing Authority
This document of the Department of Energy was signed on October 6,
2022, by Francisco Alejandro Moreno, Acting Assistant Secretary for
Energy Efficiency and Renewable Energy, pursuant to delegated authority
from the Secretary of Energy. That document with the original signature
and date is maintained by DOE. For administrative purposes only, and in
compliance with requirements of the Office of the Federal Register, the
undersigned DOE Federal Register Liaison Officer has been authorized to
sign and submit the document in electronic format for publication, as
an official document of the Department of Energy. This administrative
process in no way alters the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on October 18, 2022.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
For the reasons stated in the preamble, DOE amends parts 429 and
431 of chapter II of title 10, Code of Federal Regulations as set forth
below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
2. Amend Sec. 429.45 by revising paragraph (a)(2) and adding paragraph
(a)(3) to read as follows:
Sec. 429.45 Automatic commercial ice makers.
(a) * * *
(2) For each basic model of automatic commercial ice maker selected
for testing, a sample of sufficient size shall be randomly selected and
tested to ensure that any represented value of energy use, condenser
water use, or other measure of consumption of a basic model for which
consumers would favor lower values shall be greater than or equal to
the higher of:
(i) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TR01NO22.001
And, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(ii) The upper 95 percent confidence limit (UCL) of the true mean
divided by 1.10, where:
[GRAPHIC] [TIFF OMITTED] TR01NO22.002
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.95 is the t statistic for a 95
percent two-tailed confidence interval with n-1 degrees of freedom
(from appendix A to this subpart).
(3) The harvest rate of a basic model is the mean of the measured
harvest rates for each tested unit of the basic model, based on the
same tests to determine energy use and condenser water use, if
applicable. Round the mean harvest rate to the nearest pound of ice per
24 hours (lb/24 h) for harvest rates above 50 lb/24 h; round the mean
harvest rate to the nearest 0.1 lb/24 h for harvest rates less than or
equal to 50 lb/24 h.
* * * * *
0
3. Amend Sec. 429.134 by adding paragraph (w) to read as follows:
Sec. 429.134 Product-specific enforcement provisions.
* * * * *
(w) Automatic commercial ice makers--verification of harvest rate.
The harvest rate will be measured pursuant to the test requirements of
10 CFR part 431 for each unit tested. The results of the measurement(s)
will be averaged and compared to the value of harvest rate certified by
the manufacturer of the basic model. The certified harvest rate will be
considered valid only if the average measured harvest rate is within
five percent of the certified harvest rate.
(1) If the certified harvest rate is found to be valid, the
certified harvest rate will be used as the basis for determining the
maximum energy use and maximum condenser water use, if applicable,
allowed for the basic model.
(2) If the certified harvest rate is found to be invalid, the
average measured harvest rate of the units in the sample will be used
as the basis for determining the maximum energy use and maximum
condenser water use, if applicable, allowed for the basic model.
PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
4. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
5. Amend Sec. 431.132 by:
0
a. Adding a definition in alphabetical order for ``Baffle'';
0
b. Revising the definition of ``Batch type ice maker'';
0
c. Adding a definition in alphabetical order for ``Condenser water
use'';
0
d. Removing the definition of ``Cube type ice'';
0
e. Revising the definition of ``Energy use'';
0
f. Removing the definition of ``Maximum condenser water use''; and
0
g. Adding definitions in alphabetical order for ``Portable automatic
commercial ice maker'', ``Potable water use'', and ``Refrigerated
storage automatic commercial ice maker''.
The additions and revisions read as follows:
Sec. 431.132 Definitions concerning automatic commercial ice makers.
* * * * *
Baffle means a partition (usually made of flat material like
cardboard, plastic, or sheet metal) that reduces or prevents
recirculation of warm air from an ice maker's air outlet to its air
inlet--or, for remote condensers, from the condenser's air outlet to
its inlet.
* * * * *
Batch type ice maker means an ice maker having alternate freezing
and harvesting periods.
Condenser water use means the total amount of water used by the
condensing unit (if water-cooled), stated in gallons per 100 pounds
(gal/100 lb) of ice, in multiples of 1.
* * * * *
Energy use means the total energy consumed, stated in kilowatt
hours per one-hundred pounds (kWh/100 lb) of ice, in multiples of 0.01.
For remote condensing (but not remote compressor) automatic commercial
ice makers and remote condensing and remote
[[Page 65900]]
compressor automatic commercial ice makers, total energy consumed shall
include the energy use of the ice-making mechanism, the compressor, and
the remote condenser or condensing unit.
* * * * *
Portable automatic commercial ice maker means an automatic
commercial ice maker that does not have a means to connect to a water
supply line and has one or more reservoirs that are manually supplied
with water.
Potable water use means the amount of potable water used in making
ice, which is equal to the sum of the ice harvested, dump or purge
water, and the harvest water, expressed in gal/100 lb, in multiples of
0.1, and excludes any condenser water use.
Refrigerated storage automatic commercial ice maker means an
automatic commercial ice maker that has a refrigeration system that
actively refrigerates the self-contained ice storage bin.
* * * * *
0
6. Revise Sec. 431.133 to read as follows:
Sec. 431.133 Materials incorporated by reference.
Certain material is incorporated by reference into this subpart
with the approval of the Director of the Federal Register in accordance
with 5 U.S.C. 552(a) and 1 CFR part 51. To enforce any edition other
than that specified in this section, the U.S. Department of Energy
(DOE) must publish a document in the Federal Register and the material
must be available to the public. All approved incorporation by
reference (IBR) material is available for inspection at DOE and at the
National Archives and Records Administration (NARA). Contact DOE at:
the U.S. Department of Energy, Office of Energy Efficiency and
Renewable Energy, Building Technologies Program, Sixth Floor, 950
L'Enfant Plaza SW, Washington, DC 20024, (202)-586-9127,
[email protected], www.energy.gov/eere/buildings/building-technologies-office. For information on the availability of this
material at NARA, email: [email protected], or go to:
www.archives.gov/federal-register/cfr/ibr-locations.html. The material
may be obtained from the following sources:
(a) AHRI. Air-Conditioning, Heating, and Refrigeration Institute,
2111 Wilson Blvd., Suite 500, Arlington, VA 22201; (703) 524-8800;
[email protected]; www.ahrinet.org.
(1) AHRI Standard 810 (I-P)-2016 with Addendum 1, Performance
Rating of Automatic Commercial Ice-Makers, January 2018; IBR approved
for Sec. 431.134.
(2) [Reserved]
(b) ASHRAE. American Society of Heating, Refrigerating and Air-
Conditioning Engineers, Inc., 1791 Tullie Circle NE, Atlanta, GA 30329;
(404) 636-8400; [email protected]; www.ashrae.org.
(1) ANSI/ASHRAE Standard 29-2015, Method of Testing Automatic Ice
Makers, approved April 30, 2015; IBR approved for Sec. 431.134.
(2) [Reserved]
0
7. Revise Sec. 431.134 to read as follows:
Sec. 431.134 Uniform test methods for the measurement of harvest
rate, energy consumption, and water consumption of automatic commercial
ice makers.
Note 1 to Sec. 431.134. On or after October 27, 2023, any
representations, including certifications of compliance for
automatic commercial ice makers, made with respect to the energy use
or efficiency of automatic commercial ice makers must be made in
accordance with the results of testing pursuant to this section.
Prior to October 27, 2023, any representations with respect to
energy use or efficiency of automatic commercial ice makers must be
made either in accordance with the results of testing pursuant to
this section or with the results of testing pursuant to this section
as it appeared in 10 CFR 431.134 in the 10 CFR parts 200-499 edition
revised as of January 1, 2022.
(a) Scope. This section provides the test procedures for measuring
the harvest rate in pounds of ice per 24 hours (lb/24 h), energy use in
kilowatt hours per 100 pounds of ice (kWh/100 lb), and the condenser
water use in gallons per 100 pounds of ice (gal/100 lb) of automatic
commercial ice makers with capacities up to 4,000 lb/24 h. This section
also provides voluntary test procedures for measuring the potable water
use in gallons per 100 pounds of ice (gal/100 lb).
(b) Testing and calculations. Measure the harvest rate, the energy
use, the condenser water use, and, to the extent elected, the potable
water use of each covered automatic commercial ice maker by conducting
the test procedures set forth in AHRI Standard 810 (I-P)-2016 with
Addendum 1, section 3, ``Definitions,'' section 4, ``Test
Requirements,'' and section 5.2, ``Standard Ratings'' (incorporated by
reference, see Sec. 431.133), and according to the provisions of this
section. Use ANSI/ASHRAE Standard 29-2015 (incorporated by reference,
see Sec. 431.133) referenced by AHRI Standard 810 (I-P)-2016 with
Addendum 1 for all automatic commercial ice makers, except as noted in
paragraphs (c) through (k) of this section. If any provision of the
referenced test procedures conflicts with the requirements in this
section or the definitions in Sec. 431.132, the requirements in this
section and the definitions in Sec. 431.132 control.
(c) Test setup and equipment configurations -- (1) Baffles. Conduct
testing without baffles unless the baffle either is a part of the
automatic commercial ice maker or shipped with the automatic commercial
ice maker to be installed according to the manufacturer's installation
instructions.
(2) Clearances. Install all automatic commercial ice makers for
testing according to the manufacturer's specified minimum rear
clearance requirements, or with 3 feet of clearance from the rear of
the automatic commercial ice maker, whichever is less, from the chamber
wall. All other sides of the automatic commercial ice maker and all
sides of the remote condenser, if applicable, shall have clearances
according to section 6.5 of ANSI/ASHRAE Standard 29-2015.
(3) Purge settings. Test automatic commercial ice makers equipped
with automatic purge water control using a fixed purge water setting
that is described in the manufacturer's written instructions shipped
with the unit as being appropriate for water of normal, typical, or
average hardness. Purge water settings described in the instructions as
suitable for use only with water that has higher or lower than normal
hardness (such as distilled water or reverse osmosis water) must not be
used for testing.
(4) Ambient conditions measurement--(i) Ambient temperature
sensors. Measure all ambient temperatures according to section 6.4 of
ANSI/ASHRAE Standard 29-2015, except as provided in paragraph
(c)(4)(iv) of this section, with unweighted temperature sensors.
(ii) Ambient relative humidity measurement. Except as provided in
paragraph (c)(4)(iv) of this section, ambient relative humidity shall
be measured at the same location(s) used to confirm ambient dry bulb
temperature, or as close as the test setup permits. Ambient relative
humidity shall be measured with an instrument accuracy of 2.0 percent.
(iii) Ambient conditions sensors shielding. Ambient temperature and
relative humidity sensors may be shielded if the ambient test
conditions cannot be maintained within the specified tolerances because
of warm discharge air from the condenser exhaust affecting the ambient
measurements. If shields are used, the shields must not inhibit
recirculation of the warm discharge air into the
[[Page 65901]]
condenser or automatic commercial ice maker inlet.
(iv) Alternate ambient conditions measurement location. For
automatic commercial ice makers in which warm air discharge from the
condenser exhaust affects the ambient conditions as measured 1 foot in
front of the air inlet, or automatic commercial ice makers in which the
air inlet is located in the rear of the automatic commercial ice maker
and the manufacturer's specified minimum rear clearance is less than or
equal to 1 foot, the ambient temperature and relative humidity may
instead be measured 1 foot from the cabinet, centered with respect to
the sides of the cabinet, for any side of the automatic commercial ice
maker cabinet with no warm air discharge or air inlet.
(5) Collection container for batch type automatic commercial ice
makers with harvest rates less than or equal to 50 lb/24 h. Use an ice
collection container as specified in section 5.5.2(a) of ANSI/ASHRAE
Standard 29-2015, except that the water retention weight of the
container is no more than 4.0 percent of that of the smallest batch of
ice for which the container is used.
(d) Test conditions--(1) Relative humidity. Maintain an average
minimum ambient relative humidity of 30.0 percent throughout testing.
(2) Inlet water pressure. Except for portable automatic commercial
ice makers, the inlet water pressure when water is flowing into the
automatic commercial ice maker shall be within the allowable range
within 5 seconds of opening the water supply valve.
(e) Stabilization--(1) Percent difference calculation. Calculate
the percent difference in the ice production rate between two cycles or
samples using the following equation, where A and B are the harvest
rates, in lb/24 h (for batch type ice makers) or lb/15 mins (for
continuous type ice makers), of any cycles or samples used to determine
stability:
[GRAPHIC] [TIFF OMITTED] TR01NO22.003
(2) Automatic commercial ice makers with harvest rates greater than
50lb/24 h. The three or more consecutive cycles or samples used to
calculate harvest rate, energy use, condenser water use, and potable
water use, must meet the stability criteria in section 7.1.1 of ANSI/
ASHRAE Standard 29-2015.
(3) Automatic commercial ice makers with harvest rates less than or
equal to 50 lb/24 h. The three or more consecutive cycles or samples
used to calculate harvest rate, energy use, condenser water use, and
potable water use, must meet the stability criteria in section 7.1.1 of
ANSI/ASHRAE Standard 29-2015, except that the weights of the samples
(for continuous type automatic commercial ice makers (ACIMs)) or 24-
hour calculated ice production (for batch type ACIMs) must not vary by
more than 4 percent, and the 25 g (for continuous type
ACIMs) and 1 kg (for batch type ACIMs) criteria do not apply.
(f) Calculations. The harvest rate, energy use, condenser water
use, and potable water use must be calculated by averaging the values
for the three calculated samples for each respective reported metric as
specified in section 9 of ANSI/ASHRAE Standard 29-2015. All
intermediate calculations prior to the reported value, as applicable,
must be performed with unrounded values.
(g) Rounding. Round the reported values as follows: Harvest rate to
the nearest 1 lb/24 h for harvest rates above 50 lb/24 h; harvest rate
to the nearest 0.1 lb/24 h for harvest rates less than or equal to 50
lb/24 h; condenser water use to the nearest 1 gal/100 lb; and energy
use to the nearest 0.01 kWh/100 lb. Round final potable water use value
to the nearest 0.1 gal/100 lb.
(h) Continuous type automatic commercial ice makers--(1) Ice
hardness adjustment--(i) Calorimeter constant. Determine the
calorimeter constant according to the requirements in section A1 and A2
of Normative Annex A Method of Calorimetry in ANSI/ASHRAE Standard 29-
2015, except that the trials shall be conducted at an ambient air
temperature (room temperature) of 70 [deg]F 1 [deg]F, with
an initial water temperature of 90 [deg]F 1 [deg]F. To
verify the temperature of the block of pure ice as provided in section
A2.e in ANSI/ASHRAE Standard 29-2015, a thermocouple shall be embedded
at approximately the geometric center of the interior of the block. Any
water that remains on the block of ice shall be wiped off the surface
of the block before being placed into the calorimeter.
(ii) Ice hardness factor. Determine the ice hardness factor
according to the requirements in section A1 and A3 of Normative Annex A
Method of Calorimetry in ANSI/ASHRAE Standard 29-2015, except that the
trials shall be conducted at an ambient air temperature (room
temperature) of 70 [deg]F 1 [deg]F, with an initial water
temperature of 90 [deg]F 1 [deg]F. The harvested ice used
to determine the ice hardness factor shall be produced according to the
test methods specified at Sec. 431.134. The ice hardness factor shall
be calculated using the equation for ice hardness factor in section
5.2.2 of AHRI Standard 810 (I-P)-2016 with Addendum 1.
(iii) Ice hardness adjustment calculation. Determine the reported
energy use and reported condenser water use by multiplying the measured
energy use or measured condenser water use by the ice hardness
adjustment factor, determined using the ice hardness adjustment factor
equation in section 5.2.2 of AHRI Standard 810 (I-P)-2016 with Addendum
1.
(2) [Reserved]
(i) Automatic commercial ice makers with automatic dispensers.
Allow for the continuous production and dispensing of ice throughout
testing. If an automatic commercial ice maker with an automatic
dispenser is not able to continuously produce and dispense ice because
of certain mechanisms within the automatic commercial ice maker that
prohibit the continuous production and dispensing of ice throughout
testing, those mechanisms must be overridden to the minimum extent
which allows for the continuous production and dispensing of ice. The
automatic commercial ice maker shall have an empty internal storage bin
at the beginning of the test period. Collect capacity samples according
to the requirements of ANSI/ASHRAE Standard 29-2015, except that the
samples shall be collected through continuous use of the dispenser
rather than in the internal storage bin. The intercepted ice samples
shall be obtained from a container in an external ice bin that is
filled one-half full of ice and is connected to the outlet of the ice
dispenser through the minimal length of conduit that can be used.
(j) Portable automatic commercial ice makers. Sections 5.4, 5.6,
6.2, and 6.3 of ANSI/ASHRAE Standard 29-2015 do not apply. Ensure that
the ice storage bin is empty prior to the initial potable water
reservoir fill. Fill an external container with water to be supplied to
[[Page 65902]]
the portable automatic commercial ice maker water reservoir. Establish
an initial water temperature of 70 [deg]F 1.0 [deg]F.
Verify the initial water temperature by inserting a temperature sensor
into approximately the geometric center of the water in the external
container. Immediately after establishing the initial water
temperature, fill the ice maker water reservoir to the maximum level of
potable water as specified by the manufacturer. After the potable water
reservoir is filled, operate the portable automatic commercial ice
maker to produce ice into the ice storage bin until the bin is one-half
full. One-half full for the purposes of testing portable automatic
commercial ice makers means that half of the vertical dimension of the
ice storage bin, based on the maximum ice fill level within the ice
storage bin, is filled with ice. Once the ice storage bin is one-half
full, conduct testing according to section 7 of ANSI/ASHRAE Standard
29-2015. The potable water use is equal to the sum of the weight of ice
and any corresponding melt water collected for the capacity test as
specified in section 7.2 of ANSI/ASHRAE Standard 29-2015.
(k) Self-contained refrigerated storage automatic commercial ice
makers. For door openings, the door shall be in the fully open
position, which means opening the ice storage compartment door to an
angle of not less than 75 degrees from the closed position (or the
maximum extent possible, if that is less than 75 degrees), for 10.0
1.0 seconds to collect the sample. Conduct door openings
only for ice sample collection and returning the empty ice collection
container to the ice storage compartment (i.e., conduct two separate
door openings, one for removing the collection container to collect the
ice and one for replacing the collection container after collecting the
ice).
[FR Doc. 2022-22927 Filed 10-31-22; 8:45 am]
BILLING CODE 6450-01-P