Energy Conservation Program: Test Procedure for Single Package Vertical Air Conditioners and Single Package Vertical Heat Pumps, 2490-2522 [2021-28553]
Download as PDF
2490
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE–2017–BT–TP–0020]
RIN 1904–AD94
Energy Conservation Program: Test
Procedure for Single Package Vertical
Air Conditioners and Single Package
Vertical Heat Pumps
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking
and request for comment.
AGENCY:
The U.S. Department of
Energy (‘‘DOE’’) proposes to amend its
test procedures for single package
vertical air conditioners and single
package vertical heat pumps. DOE is
proposing to incorporate by reference
the most recent version of the relevant
industry test standard, AHRI 390–2021,
and to amend certain provisions for
representations for the subject
equipment. DOE is also proposing
definitions for ‘‘single-phase single
package vertical air conditioners with
cooling capacity less than 65,000 Btu/h’’
and for ‘‘single-phase single package
vertical heat pumps with cooling
capacity less than 65,000 Btu/h.’’ The
proposed definitions would explicitly
define this equipment as subsets of the
broader single package vertical air
conditioner and single package vertical
heat pump equipment categories, and
further distinguish such equipment
from certain residential central air
conditioners and heat pumps. DOE
seeks comment from interested parties
on this proposal.
DATES:
Comments: DOE will accept
comments, data, and information
regarding this proposal no later than
March 15, 2022. See section V, ‘‘Public
Participation,’’ for details.
Meeting: DOE will hold a webinar on
Wednesday, February 9th, 2022, from
1:00 p.m. to 3:00 p.m. See section V,
‘‘Public Participation,’’ for webinar
registration information, participant
instructions, and information about the
capabilities available to webinar
participants.
SUMMARY:
Interested persons are
encouraged to submit comments using
the Federal eRulemaking Portal at
www.regulations.gov. Follow the
instructions for submitting comments.
Alternatively, interested persons may
submit comments, identified by docket
number EERE–2017–BT–TP–0020, by
any of the following methods:
lotter on DSK11XQN23PROD with PROPOSALS2
ADDRESSES:
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
1. Federal eRulemaking Portal:
www.regulations.gov. Follow the
instructions for submitting comments.
2. Email: To
SPVACandHeatPumps2017TP0020@
ee.doe.gov. Include docket number
EERE–2017–BT–TP–0020 in the subject
line of the message.
No telefacsimiles (‘‘faxes’’) will be
accepted. For detailed instructions on
submitting comments and additional
information on this process, see section
V, ‘‘Public Participation,’’ of this
document.
Although DOE has routinely accepted
public comment submissions through a
variety of mechanisms, including postal
mail and hand delivery/courier, the
Department has found it necessary to
make temporary modifications to the
comment submission process in light of
the ongoing COVID–19 pandemic. DOE
is currently suspending receipt of public
comments via postal mail and hand
delivery/courier. If a commenter finds
that this change poses an undue
hardship, please contact Appliance
Standards Program staff at (202) 586–
1445 to discuss the need for alternative
arrangements. Once the COVID–19
pandemic health emergency is resolved,
DOE anticipates resuming all of its
regular options for public comment
submission, including postal mail and
hand delivery/courier.
Docket: The docket, which includes
Federal Register notices, public
meeting/webinar attendee lists and
transcripts, comments, and other
supporting documents/materials, is
available for review at
www.regulations.gov. All documents in
the docket are listed in the
www.regulations.gov index. However,
some documents listed in the index,
such as those containing information
that is exempt from public disclosure,
may not be publicly available.
The docket web page can be found at
www.regulations.gov/docket?D=EERE2017-BT-TP-0020. The docket web page
contains instructions on how to access
all documents, including public
comments, in the docket. See section V,
‘‘Public Participation,’’ for information
on how to submit comments through
www.regulations.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Catherine Rivest, U.S. Department
of Energy, Office of Energy Efficiency
and Renewable Energy, Building
Technologies Office, EE–5B, 1000
Independence Avenue SW, Washington,
DC 20585–0121. Telephone: (202) 586–
7335. Email:
ApplianceStandardsQuestions@
ee.doe.gov.
Mr. Eric Stas, U.S. Department of
Energy, Office of the General Counsel,
PO 00000
Frm 00002
Fmt 4701
Sfmt 4702
GC–33, 1000 Independence Avenue SW,
Washington, DC 20585–0121.
Telephone: (202) 586–5827. Email:
Eric.Stas@hq.doe.gov.
For further information on how to
submit a comment, review other public
comments and the docket, or participate
in a public meeting/webinar, contact the
Appliance and Equipment Standards
Program staff at (202) 287–1445 or by
email: ApplianceStandardsQuestions@
ee.doe.gov.
DOE
proposes to maintain a previously
approved incorporation by reference
and incorporate by reference the
following industry standards into parts
429 and 431:
AHRI Standard 390–2021
‘‘Performance Rating of Single Package
Vertical Air-Conditioners and Heat
Pumps,’’ dated 2021.
ANSI/ASHRAE Standard 37–2009,
‘‘Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment,’’ ASHRAE approved June
24, 2009.
ANSI/ASHRAE Standard 41.2–1987
(RA 92), ‘‘Standard Methods For
Laboratory Airflow Measurement,’’
ASHRAE approved October 1, 1987.
Copies of AHRI Standard 390–2021
can be obtained from the Airconditioning, Heating, and Refrigeration
Institute (AHRI), 2311 Wilson Blvd.,
Suite 400, Arlington, VA 22201, (703)
524–8800, or by going to
www.ahrinet.org/search-standards.aspx.
Copies of ANSI/ASHRAE Standard
37–2009 and ANSI/ASHRAE Standard
41.2–1987 (RA 92) can be obtained from
the American Society of Heating,
Refrigerating, and Air-Conditioning
Engineers (ASHRAE), 180 Technology
Parkway NW, Peachtree Corners, GA
30092, (404) 636–8400, or by going to
https://www.ashrae.org/.
See section IV.M for a further
discussion of these standards.
SUPPLEMENTARY INFORMATION:
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Notice of Proposed
Rulemaking
III. Discussion
A. Scope of Applicability
B. Updates to Industry Standards
1. Updates to AHRI 390
2. ASHRAE 37
C. Proposed Organization of the SPVU Test
Procedure
D. Energy Efficiency Descriptor
1. Efficiency Metrics
2. Test Conditions Used for Efficiency
Metrics
3. Fan Energy Use
E. Test Method
E:\FR\FM\14JAP2.SGM
14JAP2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
1. Unit Set-Up
2. Air Temperature Measurements
3. Defrost Energy Use
4. Outdoor Air Enthalpy Method
F. Configuration of Unit Under Test
1. Specific Components
G. Represented Values
1. Multiple Refrigerants
2. Cooling Capacity
H. Test Procedure Costs and Impact
I. Reserved Appendices for Test Procedures
for Commercial Air Conditioning and
Heating Equipment
J. Compliance Dates
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Description of Materials Incorporated
by Reference
V. Public Participation
A. Participation in the Webinar
B. Procedure for Submitting Prepared
General Statements for Distribution
C. Conduct of the Webinar
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
VI. Approval of the Office of the Secretary
lotter on DSK11XQN23PROD with PROPOSALS2
I. Authority and Background
Single package vertical air
conditioners (‘‘SPVACs’’) and single
package vertical heat pumps
(‘‘SPVHPs’’), collectively referred to as
single package vertical units (‘‘SPVUs’’),
are a category of small, large, and very
large commercial package air
conditioning and heating equipment.
Accordingly, SPVUs are included in the
list of ‘‘covered equipment’’ for which
DOE is authorized to establish and
amend energy conservation standards
and test procedures. (42 U.S.C.
6311(1)(B)–(D)) DOE’s energy
conservation standards and test
procedures for SPVUs are currently
prescribed at title 10 of the Code of
Federal Regulations (‘‘CFR’’) section 97
to subpart F of part 431 and section 96
to subpart F of part 431, respectively.
The following sections discuss DOE’s
authority to establish test procedures for
SPVUs and relevant background
information regarding DOE’s
consideration of test procedures for
SPVUs.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
A. Authority
The Energy Policy and Conservation
Act, as amended (‘‘EPCA’’),1 authorizes
DOE to regulate the energy efficiency of
a number of consumer products and
certain industrial equipment. (42 U.S.C.
6291–6317) Title III, Part C 2 of EPCA,
added by Public Law 95–619, Title IV,
section 441(a), established the Energy
Conservation Program for Certain
Industrial Equipment, which sets forth a
variety of provisions designed to
improve energy efficiency. This
equipment includes small, large, and
very large commercial package air
conditioning and heating equipment,
including SPVUs. (42 U.S.C. 6311(1)(B)–
(D))
The energy conservation program
under EPCA consists essentially of four
parts: (1) Testing, (2) labeling, (3)
Federal energy conservation standards,
and (4) certification and enforcement
procedures. Relevant provisions of
EPCA specifically include definitions
(42 U.S.C. 6291;42 U.S.C. 6311), test
procedures (42 U.S.C. 6293; 42 U.S.C.
6314), labeling provisions (42 U.S.C.
6294; 42 U.S.C. 6315), energy
conservation standards (42 U.S.C. 6295;
42 U.S.C. 6313), and the authority to
require information and reports from
manufacturers. (42 U.S.C. 6296; 42
U.S.C. 6316)
The Federal testing requirements
consist of test procedures that
manufacturers of covered equipment
must use as the basis for: (1) Certifying
to DOE that their equipment complies
with the applicable energy conservation
standards adopted pursuant to EPCA (42
U.S.C. 6316(b); 42 U.S.C. 6296), and (2)
making representations about the
efficiency of that equipment (42 U.S.C.
6314(d)). DOE also uses these test
procedures to determine whether the
equipment complies with relevant
standards promulgated under EPCA.
Federal energy efficiency
requirements for covered equipment
established under EPCA generally
supersede State laws and regulations
concerning energy conservation testing,
labeling, and standards. (42 U.S.C.
6316(a) and (b); 42 U.S.C. 6297) DOE
may, however, grant waivers of Federal
preemption for particular State laws or
regulations, in accordance with the
procedures and other provisions of
EPCA. (42 U.S.C. 6297(d); 42 U.S.C.
6316(b)(2)D))
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
1 All references to EPCA in this document refer
to the statute as amended through the Energy Act
of 2020, Public Law 116–260 (Dec. 27, 2020).
2 For editorial reasons, upon codification in the
U.S. Code, Part C was redesignated Part A–1.
PO 00000
Frm 00003
Fmt 4701
Sfmt 4702
2491
follow when prescribing or amending
test procedures for covered equipment.
EPCA requires that any test procedures
prescribed or amended under this
section be reasonably designed to
produce test results which measure
energy efficiency, energy use, or
estimated annual operating cost of a
covered product during a representative
average use cycle or period of use and
not be unduly burdensome to conduct.
(42 U.S.C. 6314 (a)(2))
As discussed earlier in this document,
SPVUs are a category of commercial
package air conditioning and heating
equipment. EPCA requires that the test
procedures for commercial package air
conditioning and heating equipment be
those generally accepted industry
testing procedures or rating procedures
developed or recognized by the AirConditioning, Heating, and Refrigeration
Institute (‘‘AHRI’’) or by the American
Society of Heating, Refrigerating and
Air-Conditioning Engineers
(‘‘ASHRAE’’), as referenced in ASHRAE
Standard 90.1, ‘‘Energy Standard for
Buildings Except Low-Rise Residential
Buildings’’ (‘‘ASHRAE Standard 90.1’’).
(42 U.S.C. 6314(a)(4)(A)) Further, if such
an industry test procedure is amended,
DOE must amend its test procedure to
be consistent with the amended
industry test procedure, unless DOE
determines, by rule published in the
Federal Register and supported by clear
and convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B))
EPCA also requires that, at least once
every 7 years, DOE must evaluate the
test procedures for each type of covered
equipment, including SPVUs, to
determine whether amended test
procedures would more accurately or
fully comply with the requirements for
the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 6314(a)(1)(A))
In addition, if the Secretary
determines that a test procedure
amendment is warranted, the Secretary
must publish proposed test procedures
in the Federal Register and afford
interested persons an opportunity (of
not less than 45 days duration) to
present oral and written data, views,
and arguments on the proposed test
procedures. (42 U.S.C. 6314(b)) If DOE
determines that test procedure revisions
are not appropriate, DOE must publish
its determination not to amend the test
procedures. (42 U.S.C. 6314(a)(1)(A)(ii))
E:\FR\FM\14JAP2.SGM
14JAP2
2492
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
DOE is publishing this NOPR in
satisfaction of its obligations under
EPCA. (42 U.S.C. 6314(a)(4)(B); 42
U.S.C. 6314(a)(1)(A))
B. Background
DOE’s existing test procedures for
SPVUs are set forth at 10 CFR 431.96.
The Federal test procedure currently
incorporates ANSI/AHRI Standard 390–
2003 (‘‘ANSI/AHRI 390–2003’’),
‘‘Performance Rating of Single Package
Vertical Air-Conditioners and Heat
Pumps,’’ (omitting section 6.4), and it
also includes additional provisions in
paragraphs (c) and (e) of 10 CFR 431.96
that provide for an optional break-in
period and additional provisions for
equipment set-up, respectively. DOE
established its test procedure for SPVUs
in a final rule for commercial heating,
air conditioning, and water heating
equipment published in the Federal
Register on May 16, 2012. 77 FR 28928,
28932. ANSI/AHRI 390–2003 was the
SPVU test standard referenced in the
edition of ASHRAE Standard 90.1
current at that time.
On July 20, 2018, DOE published a
request for information (‘‘RFI’’) in the
Federal Register to collect information
and data to consider amendments to
DOE’s test procedures for SPVUs. 83 FR
34499 (‘‘July 2018 RFI’’). As part of the
July 2018 RFI, DOE identified and
requested comment on several issues
associated with the currently applicable
Federal test procedures, in particular
concerning incorporation by reference
of the most recent version of the
relevant industry standard; efficiency
metrics and calculations; and
clarification of test methods. Id. at 83 FR
3449. DOE also sought comment on any
additional topics that may inform DOE’s
decisions in a future test procedure
rulemaking, including methods to
reduce regulatory burden while
ensuring the test procedures’ accuracy.
Id.
DOE received a number of comments
from interested parties in response to
the July 2018 RFI. Table I–1 lists each
commenter and the abbreviation for
each used in this document. DOE
considered these comments in the
preparation of this NOPR. Discussion of
the relevant comments, as well as DOE’s
responses, are provided in the
appropriate sections of this document.
TABLE I–1—INTERESTED PARTIES PROVIDING COMMENT ON THE JULY 2018 RFI
Commenter(s)
Abbreviation
Commenter type
Air-Conditioning, Heating, and Refrigeration Institute .....................................................................
Appliance Standards Awareness Project, Natural Resources Defense Council, American Council for an Energy-Efficient Economy.
GE Appliances, a Haier Company ..................................................................................................
Lennox International Inc ..................................................................................................................
Northwest Energy Efficiency Alliance, and Northwest Power and Conservation Council ..............
Pacific Gas and Electric Company (PG&E), San Diego Gas and Electric (SDG&E), and Southern California Edison (SCE); collectively the California Investor-Owned Utilities.
AHRI .................................
ASAP, NRDC, and
ACEEE.
GE .....................................
Lennox ..............................
NEEA and NWPCC ..........
CA IOUs ...........................
IR.
EA.
M.
M.
EA and Interstate Compact Agency.
U.
EA: Efficiency/Environmental Advocate; IR: Industry Representative; M: Manufacturer; U: Utility.
II. Synopsis of the Notice of Proposed
Rulemaking
In this NOPR, DOE is proposing to
amend the test procedures for SPVUs to
incorporate by reference AHRI 390–
2021. DOE proposes to add a new
appendix G, ‘‘Uniform test method for
measuring the energy consumption of
single package vertical air conditioners
and single package vertical heat
pumps,’’ (‘‘appendix G’’) that would
include the relevant test procedure
requirements for SPVUs for measuring
the existing efficiency metrics: (1) EER
for cooling mode and (2) COP for
heating mode. DOE is also proposing
add a new appendix G1 that would
include the relevant test procedure
requirements for SPVUs for measuring
with updated efficiency metrics: (1)
IEER for cooling mode and (2) COP for
heating mode. Appendix G1 would
provide the test procedure for
representations based on IEER and
would be mandatory only at such time
as compliance is required with amended
energy conservation standards based on
IEER, should DOE adopt standards
using such metrics.
Additionally, DOE is proposing to
define ‘‘single-phase single package
vertical air conditioner with cooling
capacity less than 65,000 Btu/h’’ and
‘‘single-phase single package vertical
heat pump with cooling capacity less
than 65,000 Btu/h’’ as subsets of the
broader SPVAC and SPVHP equipment
category, in order to clarify what kind
of single-phase equipment with cooling
capacity less than 65,000 Btu/h was
contemplated in the broader definitions
of SPVAC and SPVHP established by
Congress. Single-phase equipment
meeting these definitions would be
subject to the applicable commercial
equipment energy conservation
standards for SPVACs and SPVHPs,
while single-phase products not meeting
these definitions would properly be
classified as CAC and subject to the
applicable consumer products energy
conservation standards.
DOE is proposing to establish
appendices for the relevant test
procedures for SPVUs to better
differentiate the specific testing
requirements. Currently, the test
requirements for all types of commercial
air conditioners and heat pumps,
including SPVUs, are codified at 10 CFR
431.96. In conjunction, DOE proposes to
amend Table 1 to 10 CFR 431.96 to
identify the newly added Appendices G
and G1 as the applicable test procedures
for testing SPVUs.
DOE’s proposed actions are
summarized in Table II–1 and addressed
in detail in section III of this document.
3 The parenthetical reference provides a reference
for information located in the docket of DOE’s
rulemaking to amend the test procedures for SPVUs
(Docket No. EERE–2017–BT–TP–0020, which is
maintained at www.regulations.gov/
#!docketDetail;D=EERE-2017-BT-TP-0020). The
references are arranged as follows: (Commenter
name, comment docket ID number, page of that
document).
lotter on DSK11XQN23PROD with PROPOSALS2
A parenthetical reference at the end of
a comment quotation or paraphrase
provides the location of the item in the
public record.3
On June 24, 2021, AHRI published
updates to its test procedure for SPVUs
as AHRI Standard 390–2021,
‘‘Performance Rating of Single Package
Vertical Air-Conditioners and Heat
Pumps’’ (‘‘AHRI 390–2021’’). Among
other things, AHRI 390–2021 maintains
the existing efficiency metrics—energy
efficiency ratio (‘‘EER’’) for cooling
mode and coefficient of performance
(‘‘COP’’) for heating mode—but it also
added a seasonal metric that includes
part-load cooling performance—the
integrated energy efficiency ratio
(‘‘IEER’’) metric. AHRI 390–2021 also
includes additional specifications
regarding the test methods and
conditions.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
PO 00000
Frm 00004
Fmt 4701
Sfmt 4702
E:\FR\FM\14JAP2.SGM
14JAP2
2493
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
TABLE II–1—SUMMARY OF CHANGES IN PROPOSED TEST PROCEDURE RELATIVE TO CURRENT TEST PROCEDURE
Current DOE TP
Proposed TP
Incorporates by reference ANSI/
AHRI 390–2003 (excluding
section 6.4).
Incorporates by reference AHRI 390–2021, which includes the following changes ........................
—Includes a new energy efficiency descriptor, IEER, which incorporates part-load performance.
—Provides direction and accompanying definitions for determining whether a unit is tested
as a ducted or non-ducted unit.
—Directs that the outdoor air-side attachments used for testing must be specified by the
manufacturer in the supplemental testing instructions.
—Includes refrigerant charging instructions for cases where they are not provided by the
manufacturer.
—Specifies tolerances for achieving the rated airflow and/or minimum external static pressure (‘‘ESP’’) during testing and specifies how to set indoor airflow if airflow and ESP tolerances cannot be simultaneously met.
—Incorporates specifications for measuring outdoor air conditions.
—Requires data be recorded at equal intervals of 5 minutes or less over a 30-minute measurement period.
—Clarifies that test results for outdoor air enthalpy method are based on results without test
apparatus connected.
—Defines the term ‘‘manufacturer’s installation instructions’’ and includes hierarchy of precedence if multiple instructions are included.
Includes additional definitions: ‘‘single-phase single package vertical air conditioner with cooling
capacity less than 65,000 Btu/h’’ and ‘‘single-phase single package vertical heat pump with
cooling capacity less than 65,000 Btu/h’’.
Adopt industry test procedure.
Includes provisions for testing when certain components are present ............................................
Establish provisions for testing
with certain components.
Only includes definitions for the
equipment categories; ‘‘Single
Package Vertical Air Conditioner’’ and ‘‘Single Package
Vertical Heat Pump’’.
Does not include provisions for
certain components.
DOE has tentatively determined that
the proposed amendments would not be
unduly burdensome. Furthermore, DOE
has tentatively determined that the
proposed amendments described in
section III of this NOPR would not alter
the measured efficiency of SPVUs or
require retesting solely as a result of
DOE’s adoption of the proposed
amendments to the test procedure, if
made final. Use of the updated industry
test procedure provisions as proposed in
Appendix G1 and the related proposed
amendments to representation
requirements in 10 CFR 429.43 would
not be required until the compliance
date of any amended standards
denominated in terms of IEER.
Additionally, DOE has tentatively
determined that the proposed
amendments, if made final, would not
increase the cost of testing. Discussion
of DOE’s proposed actions are addressed
in detail in section III of this NOPR.
III. Discussion
lotter on DSK11XQN23PROD with PROPOSALS2
A. Scope of Applicability
EPCA, as amended by the Energy
Independence and Security Act of 2007
(‘‘EISA 2007’’), Public Law 110–140
(Dec. 19, 2007), defines ‘‘single package
vertical air conditioner’’ and ‘‘single
package vertical heat pump’’ at 42
U.S.C. 6311(22) and (23), respectively.
In particular, these units can be singleor three-phase; must have major
components arranged vertically; must be
an encased combination of components;
and must be intended for exterior
mounting on, adjacent interior to, or
through an outside wall. DOE codified
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
Attribution
the statutory definitions into its
regulations at 10 CFR 431.92.
Additionally, EPCA established initial
equipment classes for SPVUs with a
capacity less than 65,000 Btu/h based
on phase. (42 U.S.C. 6313(a)(10)(A)(i)–
(ii) and (v)–(vi))
DOE currently defines an SPVAC as
air-cooled commercial package air
conditioning and heating equipment
that: (1) Is factory-assembled as a single
package that: (i) Has major components
that are arranged vertically; (ii) is an
encased combination of cooling and
optional heating components; and (iii) is
intended for exterior mounting on,
adjacent interior to, or through an
outside wall; (2) is powered by a singleor 3-phase current; (3) may contain 1 or
more separate indoor grilles, outdoor
louvers, various ventilation options,
indoor free air discharges, ductwork,
well plenum, or sleeves; and (4) has
heating components that may include
electrical resistance, steam, hot water, or
gas, but may not include reverse cycle
refrigeration as a heating means. 10 CFR
431.92. Additionally, DOE defines an
SPVHP as a single package vertical air
conditioner that: (1) Uses reverse cycle
refrigeration as its primary heat source;
and (2) may include secondary
supplemental heating by means of
electrical resistance, steam, hot water, or
gas. Id. The Federal test procedures are
applicable to SPVUs with a cooling
capacity less than 760,000 Btu/h. (42
U.S.C. 6311(8)(D))
DOE is proposing to add specific
definitions for ‘‘single-phase single
package vertical air conditioner with
cooling capacity less than 65,000 Btu/h’’
PO 00000
Frm 00005
Fmt 4701
Sfmt 4702
Explicitly delineate SPVUs from
other covered products.
and ‘‘single-phase single package
vertical heat pump with cooling
capacity less than 65,000 Btu/h’’ to
explicitly delineate such equipment
from certain covered consumer
products, such as central air
conditioners, based on design
characteristics. On April 24, 2020, DOE
published in the Federal Register a
request for information (‘‘RFI’’) with
regards to SPVU energy conservation
standards (85 FR 22958). In response to
this RFI, Lennox commented that
misunderstanding the distinction
between CACs and SPVUs remains an
outstanding issue on which DOE should
take action. (Docket No. EERE–2019–
BT–STD–0033–0008 at pp. 1–2))
EPCA defines a ‘‘central air
conditioner’’ as a product, other than a
packaged terminal air conditioner,4
which is powered by single-phase
electric current, air-cooled, rated below
65,000 Btu per hour, is not contained
within the same cabinet as a furnace
with a rated capacity above 225,000 Btu
per hour, and is a heat pump or a
cooling only unit. (42 U.S.C. 6291(21))
DOE has incorporated this definition in
10 CFR 430.2.
Reading the two definitions of SPVUs
and CACs in isolation, certain singlephase air conditioners and heat pumps
with cooling capacity less than 65,000
4 ‘‘Packaged terminal air conditioner’’ is defined
in 10 CFR 430.92 as a wall sleeve and a separate
un-encased combination of heating and cooling
assemblies specified by the builder and intended
for mounting through the wall, and that is
industrial equipment. It includes a prime source of
refrigeration, separable outdoor louvers, forced
ventilation, and heating availability by builder’s
choice of hot water, steam, or electricity.
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
2494
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
Btu/h and with their components
arranged vertically could be understood
to be SPVUs, as opposed to CACs. DOE
has previously explained that the
definitions of SPVUs and CACs must be
read in the context of DOE’s authority
to regulate certain consumer products
(i.e., covered products) and certain
industrial equipment (i.e., covered
equipment). 79 FR 78614, 78625 (April
11, 2014). Industrial equipment under
EPCA generally excludes ‘‘covered
products.’’ (42 U.S.C. 6311(2)(A)(iii))
‘‘Covered products’’ are certain
consumer products explicitly set forth
in the statute, as well as consumer
products which have been classified as
a covered product under 42 U.S.C.
6292(b). EPCA defines ‘‘consumer
product,’’ in part, as an article which, to
any significant extent, is distributed in
commerce for personal use or
consumption by individuals. (42 U.S.C.
6291(1)(B)) CACs are covered products.
A product can only be classified as an
SPVU, and, therefore, industrial
equipment under EPCA, if it does not
meet the definition of any covered
product, including CACs. 79 FR 78614,
78625 (April 11, 2014).
To clarify the distinction between
SPVUs as industrial equipment and
CACs as covered consumer products,
DOE proposes to define in 10 CFR
431.92 ‘‘single-phase single package
vertical air conditioner with cooling
capacity less than 65,000 Btu/h’’ and
‘‘single-phase single package vertical
heat pump with cooling capacity less
than 65,000 Btu/h.’’ The current
definitions of SPVAC and SPVHP at 10
CFR 431.92 allow for both wallmounted and floor-mounted units, and
either may use single-phase or threephase power. DOE proposes to include
certain characteristics as part of these
definitions that will evidence that these
equipment would likely not be
distributed to any significant extent in
commerce for personal use or
consumption by individuals. These
characteristics would distinguish SPVU
equipment from CACs, which are
consumer products.
DOE has identified specific technical
features that differentiate floormounted, single-phase units intended
only for commercial applications (i.e.,
meaning they are SPVUs) from ones
intended for consumer applications,
such as multi-family type floormounted, single-phase units (i.e.,
meaning they are CACs). DOE has
preliminarily determined that, in order
to meet commercial building ventilation
requirements 5 (an indication that a unit
5 ASHRAE Standard 62.1–2019 details ventilation
standards for a variety of commercial building
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
is industrial equipment and not a
consumer product), floor-mounted,
single-phase units on the market have
the ability for outdoor air intake. This is
evidenced by the existence of outdoor
air intake dampers and associated
controls. These ventilation air
provisions make the unit capable of
drawing in and conditioning outdoor air
for delivery to the conditioned space
(with or without first mixing the
outdoor air with return air). Technical
specifications for these floor-mounted,
single-phase units detail both the
incremental and maximum outdoor air
flow rates available to meet the specific
indoor air quality needs of building
occupants. Of the maximum outdoor air
flow rates that DOE identified for each
unit on the market, the unit with the
lowest maximum outdoor air flow rate
identified was capable of providing a
maximum of 400 cubic feet per minute
(‘‘CFM’’) of outdoor air, with the same
drive kit and motor settings used to
determine the certified efficiency rating
of the equipment (as required for
submittal to DOE by 10 CFR
429.43(b)(4)(xi)).
Conversely, DOE preliminarily has
found that the multi-family type floormounted, single-phase units that are
consumer products because they are
distributed in commerce for personal
use or consumption by individuals (i.e.,
CACs) have little to no ability to provide
outdoor air to the conditioned space.
Based on DOE’s review of manufacturer
literature, for those consumer products
that do provide outdoor air, none could
provide more than 120 CFM of outdoor
air to the conditioned space. Building
ventilation codes may require specific
levels of outdoor air flow for multifamily type structures, but the outdoor
ventilation airflow requirements for
such living spaces are substantially
lower than those for the spaces
generally served by the market for floorspaces, including educational spaces, which are the
primary market for floor-mounted, single-phase
SPVUs. Specifically, for standard classrooms
occupied with persons between the ages of 5 and
8, 10 CFM of outdoor air flow per person is required
at a default occupancy of 25 individuals per 1,000
square feet. This translates to a requirement of 250
CFM per 1,000 square feet under default occupancy.
For standard classrooms occupied by persons 9
years and older, 10 CFM of outdoor air per person
is required at a default occupancy of 35 individuals
per 1,000 square feet. This translates to a
requirement of 350 CFM per 1,000 square feet under
default occupancy. For specialty classrooms
(lecture rooms, art, science, college laboratories,
wood/metal shops, computer labs, media centers,
music/theater/dance), specific outdoor air
requirements range from 250 CFM to 350 CFM per
1,000 square feet under default occupancy. (For
further details, see ANSI/ASHRAE Standard 62.1–
2019, Table 6–1.)
PO 00000
Frm 00006
Fmt 4701
Sfmt 4702
mounted, single-phase SPVUs.6 Thus,
DOE initially has determined that, at the
present time and in most cases, these
outdoor ventilation airflow
requirements are adequately met using
ventilation techniques other than the
outdoor air provisions incorporated in
single-package units.7 In addition, DOE
notes that in other applications in areas
where ventilation standards exist
specifically for residences, the required
outdoor air flow levels for these
structures are similar to those for multifamily type structures.8
Based on the discussion in the prior
paragraphs, DOE has preliminarily
determined that a key physical
characteristic demonstrating that floormounted, single-phase SPVUs are not
‘‘of a type’’ distributed in commerce for
personal use or consumption by
individuals is the ability to provide
outdoor air sufficient for commercial
applications. Equipment with the ability
to provide 400 CFM or greater of
outdoor air, which significantly exceeds
the outdoor air requirements for
residences and multi-family
applications, would likely not be
distributed to any significant extent in
commerce for personal use or
consumption by individuals and,
therefore, is not a consumer product.
(See 42 U.S.C. 6291(1))
DOE’s review of the market for wallmounted configurations did not find
that there was a threshold capability of
providing outdoor air to distinguish
between wall-mounted, single-phase
units for use in commercial applications
6 For the multi-family applications of hotels,
motels, resorts, and dormitories, ASHRAE Standard
62.1–2019 requires outdoor air flow rates of 5 CFM
per person at a default occupancy of 10 individuals
per 1,000 square feet. This translates to a
requirement of 50 CFM per 1,000 square feet under
default occupancy. (For further details, see ANSI/
ASHRAE Standard 62.1–2019, Table 6–1.)
7 Ventilation in high-rise multi-family apartment
buildings is typically achieved using a combination
of natural and mechanical ventilation. The
preferred mechanical ventilation method is a
central system, which uses ventilation ducts
oriented vertically through stacks of apartments,
with make-up air sourced from air conditioning/
heating units located on the roof and supplied via
vertical ducts. For more information see: A Guide
to Energy Efficient Ventilation in Apartment
Buildings. U.S. Department of Energy (DOE/EE–
0196). 1999 (Available at: eetd.lbl.gov/node/50537).
8 Table N1104.2 of the ‘‘Minnesota Rules, Chapter
1322 Residential Energy Code’’ specifies ventilation
rates for residences based on a range of square
footages and numbers of bedrooms. For residences
with a conditioned space between 1,000 and 1,500
square feet in area, ventilation rates are similar to
those listed in ASHRAE Standard 62.1–2013 per
1,000 square feet for the multi-family applications
of hotels, motels, resorts, and dormitories.
Specifically, for residences with a conditioned
space between 1,000 and 1,500 square feet in area,
total ventilation rates range from 60 CFM (for a
single-bedroom residence) to 135 CFM (for a sixbedroom residence).
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
(SPVUs) and multi-family-type floormounted, single-phase units (CACs).
However, based on DOE’s review, all
wall-mounted units marketed for
commercial applications identified by
DOE were weatherized (i.e., designed
for outdoor use) and denoted on their
nameplate that they are for ‘‘Outdoor
Use’’ or ‘‘Suitable for Outdoor Use.’’
Conversely, all units marketed for multifamily-type floor-mounted applications
identified by DOE were nonweatherized units. Based on this review,
DOE also proposes that whether a model
is weatherized or non-weatherized is a
criterion for distinguishing between
single-phase SPVUs and consumer
CACs.
Therefore, DOE proposes to define in
10 CFR 431.92 ‘‘single-phase single
package vertical air conditioner with
cooling capacity less than 65,000 Btu/h’’
and ‘‘single-phase single package
vertical heat pump with cooling
capacity less than 65,000 Btu/h’’ as
SPVACs and SPVHPs, respectively, that
are either (1) weatherized, or (2) nonweatherized and have the ability to
provide a minimum of 400 CFM of
outdoor air. Single-phase single package
products with cooling capacity less than
65,000 Btu/h not meeting these
definitions would be properly classified
as CACs, not SPVUs.
DOE recognizes that the confusion
with the appropriate classification of
CACs and SPVUs may have been
compounded by DOE’s definition of
‘‘space-constrained’’ CACs and
ASHRAE Standard 90.1’s definition of
‘‘nonweatherized space constrained
single-package vertical unit.’’
Nonetheless, because a spaceconstrained product is a central air
conditioner or heat pump, it is properly
classified as a consumer product. In 10
CFR 430.2, DOE defines ‘‘space
constrained product’’ as a central air
conditioner or heat pump with certain
characteristics including rated cooling
capacity no greater than 30,000 Btu/hr
and an outdoor or indoor unit with
dimensions or displacement
substantially smaller than those of other
units and that if increased would
increase installation cost or reduce
utility, and which was available for
purchase in the United States as of
December 1, 2000. As with CACs more
broadly, if a unit meets DOE’s definition
of ‘‘space constrained product,’’ it is not
an SPVU.
In contrast, ASHRAE Standard 90.1–
2013 created a new equipment class for
SPVACs and SPVHPs used in spaceconstrained applications, with a
definition for ‘‘nonweatherized space
constrained single-package vertical
unit’’ and specified efficiency standards
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
for the associated equipment class. In a
Notice of Data Availability addressing
energy conservation standards for
certain commercial heating, air
conditioning, and water heating
equipment, including SPVUs, published
in the Federal Register on April 11,
2014, DOE explicitly addressed
‘‘nonweatherized space constrained
single-package vertical units’’ and
tentatively concluded that there was no
need to establish a separate spaceconstrained class for SPVUs. 79 FR
20114, 20123. In that document, DOE
stated that certain models currently
listed by manufacturers as SPVUs, most
of which would have met the ASHRAE
space-constrained definition, were being
misclassified and should be classified as
central air conditioners (in most cases,
space-constrained central air
conditioners). Id. DOE reaffirmed this
position in a NOPR addressing energy
conservation standards for SPVUs,
published in the Federal Register on
December 30, 2014, emphasizing that a
product can only be considered
commercial/industrial equipment under
EPCA if it does not meet the definition
of a consumer product. 79 FR 78614,
78625. In the subsequent final rule
addressing energy conversation
standards for SPVUs, DOE did not adopt
definitions in response to this issue and
stated it would consider the matter in a
subsequent rulemaking. 80 FR 57438,
57448 (Sept. 23, 2015).
DOE has now tentatively determined
that the characteristics included in the
proposed definitions earlier in this
section of ‘‘single-phase single package
vertical air conditioner with cooling
capacity less than 65,000 Btu/h’’ and
‘‘single-phase single package vertical
heat pump with cooling capacity less
than 65,000 Btu/h’’ appropriately
distinguish such equipment from
consumer products and address any
potential confusion as to the application
of the DOE definition of ‘‘space
constrained products’’ to SPVUs.
In regard to determining if a unit is
capable of providing 400 CFM of
outdoor air, DOE is proposing to include
provisions in 10 CFR 429.134 that
specify the method of measurement of
the maximum outdoor ventilation
airflow rate. DOE is proposing to specify
that the outdoor ventilation airflow rate
should be set up and measured in
accordance with ASHRAE 41.2–1987,
‘‘Standard Methods for Laboratory
Airflow Measurement,’’ and Section 6.4
of ASHRAE 37–2009. DOE notes that
the proposed method for measuring
outdoor ventilation airflow is generally
consistent with the test methods
specified in AHRI 390–2021 (i.e., AHRI
390–2021 incorporates by reference
PO 00000
Frm 00007
Fmt 4701
Sfmt 4702
2495
ASHRAE 37–2009, including Section
6.4, which in turn incorporates by
reference ASHRAE 41.2–1987, which
specify the method of airflow
measurement.) DOE is proposing
additional specifications in this NOPR
to clarify how these provisions are
applied to measure the outdoor
ventilation airflow rate. First, DOE is
proposing to specify that all references
to the inlet in ASHRAE 41.2–1987 and
Section 6.4 of ASHRAE 37–2009 refer to
the outdoor air inlet. Second, DOE is
proposing to specify that the
measurement should take place at the
conditions specified for Full Load
Standard Rating Capacity Test, Cooling
in Table 3 of AHRI 390–2021, except for
the minimum external static pressure
(ESP). The minimum ESP for all
validations shall be 0.00 in. H2O
measured from inlet to outlet, with a
tolerance of ¥0.00/+0.05 in. H2O.
Finally, DOE is proposing that the
outdoor air inlet pressure shall be 0.00
in. H2O, with a tolerance of ¥0.00/
+0.05 in. H2O when measured against
the room ambient. These additional
provisions would improve the
representativeness, repeatability, and
reproducibility of the test methods for
validating the outdoor ventilation
airflow rate.
Issue 1: DOE requests comment on its
proposal to define ‘‘single-phase single
package vertical air conditioner with
cooling capacity less than 65,000 Btu/h’’
and ‘‘single-phase single package
vertical heat pump with cooling
capacity less than 65,000 Btu/h’’ as
subsets of the broader SPVAC and
SPVHP equipment category. DOE
requests feedback on the proposed
characteristics that would distinguish
this equipment as SPVUs (i.e.,
‘‘weatherized’’ or capable of utilizing a
maximum of 400 CFM of outdoor air).
Additionally, DOE requests comment on
the proposed method to validate that a
unit is capable of providing 400 CFM of
outdoor air.
B. Updates to Industry Standards
1. Updates to AHRI 390
As described in section I.A of this
NOPR, with respect to SPVUs, EPCA
directs DOE to use industry test
methods developed or recognized by
AHRI or ASHRAE, as referenced in
ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A)) If such an industry test
procedure is amended, EPCA requires
that DOE amend its test procedure as
necessary to be consistent with the
amended industry test method unless
DOE determines, by rule published in
the Federal Register and supported by
clear and convincing evidence, that the
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
2496
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
amended test procedure would be
unduly burdensome to conduct or
would not produce test results that
reflect the energy efficiency, energy use,
and estimated operating costs of that
equipment during a representative
average use cycle. (42 U.S.C.
6314(a)(4)(B))
As mentioned, the DOE test procedure
at 10 CFR 431.96 references ANSI/AHRI
390–2003 (excluding Section 6.4) for
testing SPVUs, and ASHRAE Standard
90.1 references this same industry test
standard. In response to the July 2018
RFI, GE commented that DOE should
continue to incorporate by reference the
ASHRAE, ANSI, and AHRI test
procedures for SPVUs, including new
editions when published by the
standards-setting bodies. (GE, No. 3 at p.
1) 9 AHRI and Lennox encouraged
DOE’s continued participation in the
process to revise AHRI 390. (AHRI, No.
5 at p. 2; Lennox, No. 6 at pp. 1–2) AHRI
and Lennox recommended that DOE
adopt the revised industry test standard
as the DOE test procedure. (AHRI, No.
5 at p. 2; Lennox, No. 6 at p. 1)
On June 24, 2021, AHRI published
AHRI 390–2021, which supersedes
ANSI/AHRI 390–2003. AHRI 390–2021,
which was developed as part of an
industry consensus process, includes
revisions that DOE has initially
determined improve the
representativeness, repeatability, and
reproducibility of the test methods.
These revisions include, among other
things, the following: (1) A new energy
efficiency descriptor, IEER, which
incorporates part-load cooling
performance; (2) additional
specification to the testing requirements
for ducted and non-ducted units; (3)
refrigerant charging instructions for
cases where they are not provided by
the manufacturer; (4) additional
specification for setting the airflow rates
and external static pressure for testing;
(5) additional specification for the
measurement of air conditions; (6)
additional specification for the
secondary capacity measurement using
the outdoor air enthalpy method; (7)
guidance on the filter to be used during
test; (8) specification of a maximum
compressor break-in period; (9) further
specificity for atmospheric pressure
measurement requirements; (10)
additional detail regarding the
installation of outdoor air-side
attachments; (11) additional direction
9 A notation in the form ‘‘GE, No. 3 at p. 1’’
identifies a written comment: (1) Made by GE; (2)
recorded in document number 3 that is filed in the
docket of the SPVU test procedure rulemaking
(Docket No. EERE–2017–BT–TP–0020) and
available for review at www.regulations.gov; and (3)
that appears on page 1 of document number 3.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
on the use of applicable manufacturer
instructions; and (12) a list of
components that must be present for
testing. DOE carefully reviewed the
changes in AHRI 390–2021 in
consideration of this NOPR. In this
NOPR, DOE proposes to incorporate by
reference the latest version of the
industry test procedure for SPVUs,
AHRI 390–2021, per 42 U.S.C.
6314(a)(4)(A) and (B).
2. ASHRAE 37
ANSI/ASHRAE 37–2009, a method of
test for many categories of air
conditioning and heating equipment, is
referenced by AHRI 390–2021 for testing
SPVUs. In particular, Appendix E of
AHRI 390–2021 specifies the method of
test for SPVUs, including the use of
specified provisions of ANSI/ASHRAE
37–2009. Consistent with AHRI 390–
2021, DOE is proposing to incorporate
by reference ANSI/ASHRAE 37–2009 in
its test procedure for SPVUs.
Specifically, in Section 1.2 of the
proposed test procedure for SPVUs in
the proposed Appendices G and G1 of
subpart F of 10 CFR part 431, DOE is
proposing to utilize the applicable
sections of ANSI/ASHRAE 37–2009—all
sections except sections 1, 2 and 4. DOE
also is proposing that in the event of any
conflicts between the DOE test
procedure, AHRI 390–2021 and
ASHRAE 37–2009, the DOE test
procedure takes highest precedence,
followed by AHRI 390–2021, followed
by ASHRAE 37–2009.
C. Proposed Organization of the SPVU
Test Procedure
DOE is proposing to relocate and
centralize the current test procedure for
SPVUs to a new Appendix G to subpart
F of part 431. Appendix G will
incorporate by reference AHRI 390–
2021, but DOE will exclude from use
those sections pertaining to the
calculation of IEER (section 6.2).
Correspondingly, DOE is proposing to
update the existing incorporation by
reference of ANSI/AHRI 390–2003 at 10
CFR 431.95 so that the incorporation by
reference applies to Appendix G rather
than 10 CFR 431.96. As proposed,
SPVUs would be tested according to
Appendix G unless and until DOE
adopts an amended energy conservation
standard that relies on the IEER metric.
DOE also is proposing to amend the
test procedure for SPVUs by adopting
the updated version of AHRI 390–2021,
including use of the sections pertaining
to IEER (section 6.2) in a new Appendix
G1 to subpart F of part 431, as discussed
in the following sections. As proposed,
SPVUs would not be required to test
according to the test procedure in
PO 00000
Frm 00008
Fmt 4701
Sfmt 4702
proposed Appendix G1 unless and until
DOE adopts an amended energy
conservation standard that relies on the
IEER metric.
D. Energy Efficiency Descriptor
For SPVUs, DOE currently prescribes
EER as the cooling mode metric and
COP as the heating mode metric. 10 CFR
431.96. These energy efficiency
descriptors are consistent with those
included in ASHRAE 90.1–2019 for
SPVUs. EER is the ratio of the produced
cooling effect of the SPVU to its net
work input, expressed in Btu/watt-hour
and measured at standard rating
conditions. COP is the ratio of the
produced heating effect of the SPVU to
its net work input, expressed in W/W,
and measured at standard rating
conditions.
1. Efficiency Metrics
EER measures efficiency at full-load
conditions. DOE’s current test
procedure for SPVUs does not include
a seasonal metric that measures partload performance. A seasonal metric is
a weighted average of the performance
of cooling or heating systems at different
rating points intended to represent
average efficiency over a full cooling or
heating season.
DOE noted in the July 2018 RFI that
several other categories of commercial
package air conditioning and heating
equipment are rated using a seasonal
metric, such as IEER for air-cooled
commercial unitary air conditioners
(‘‘CUACs’’), as presented in Section 6.2
of AHRI 340/360–2019, ‘‘Performance
Rating of Commercial and Industrial
Unitary Air-conditioning and Heat
Pump Equipment.’’ 83 FR 34499, 34503
(July 20, 2018). IEER is a weighted
average of efficiency at the four load
levels representing 100, 75, 50, and 25
percent of full-load capacity, each
measured at an outdoor air condition
representative of field operation at the
given load level.
DOE noted in the July 2018 RFI that
ANSI/AHRI 390–2003 includes a
seasonal part-load metric for SPVUs
(i.e., integrated part-load value
(‘‘IPLV’’)). 83 FR 34499, 34503 (July 20,
2018). IPLV integrates unit performance
at each capacity step provided by the
refrigeration system. The IPLV tests are
conducted at constant outdoor air
conditions of 80 °F dry-bulb temperature
and 67 °F wet-bulb temperature. Id. DOE
is aware that some manufacturers make
representations of part-load
performance of SPVUs in product
literature using IPLV. DOE has noted
that IPLV was formerly used for rating
CUACs but has since been removed
from AHRI 340/360 in favor of IEER. Id.
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
As part of the July 2018 RFI, DOE
requested comment on whether it
should consider adopting for SPVUs a
cooling-mode metric that integrates
part-load performance to better
represent full-season efficiency, and
whether a part-load metric such as IEER
or IPLV would be appropriate for
SPVUs. 83 FR 34499, 34503 (July 20,
2018).
AHRI and GE both commented that
DOE should not consider adopting a
part-load cooling metric at this time,
stating that doing so would increase test
burden for a specialized product sold in
a comparatively small market. (AHRI,
No. 5 at p. 6; GE, No. 3 at p. 2) GE noted
that for SPVUs with single-speed
compressors, the EER test method
requires only a single test with an
average of 8 hours to complete and
validate test data, whereas an IEER test
method would require four tests, which
entails additional testing time and cost.
(GE, No. 3 at p. 2) GE stated that for
dual-voltage units, the IEER test method
would increase test time to
approximately 64 hours per unit, and
that the time to test 3 units for a given
model would increase testing time from
48 hours to 192 hours under the IEER
test method. Id.
AHRI commented that a part-load
metric may be appropriate for some
equipment, such as two-stage or
variable-capacity SPVUs, but only for
certain applications. (AHRI, No. 5 at p.
6) AHRI and Lennox commented that as
part of the revisions to AHRI 390,
industry is assessing whether IEER or
IPLV would better represent part-load
performance for units other than singlestage products. (AHRI, No. 5 at p. 6;
Lennox. No. 6 at p. 5) Lennox
commented that while a part-load
metric may be a favorable option for
SPVUs in the long term, there was not
sufficient data at that time to evaluate
the impacts on performance and the
increase in test burden versus potential
consumer benefits of optimized partload performance. (Lennox. No. 6 at p.
5)
The CA IOUs commented that the
IEER metric was developed for CUACs
with greater than 65,000 Btu/h cooling
capacity using office, retail, and larger
permanent school space loads as the
basis for the part-load weighting factors.
(CA IOUs, No. 2 at p. 3) They noted that
SPVUs are generally used in smaller
settings, such as electronic sheds and
relatively small relocatable classrooms.
Id. The CA IOUs stated that, while there
may be some shortcomings with the
IEER metric, it results in ratings more
reflective of annual energy efficiency
than those produced by IPLV. Id. The
CA IOUs commented that IPLV, on the
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
other hand, has a strong potential to
misrepresent efficiency ratings because
it does not rate all units at identical
capacity points, leading to a difference
in the weighting factors used for various
equipment. Id. In addition, the CA IOUs
commented that all part-load ratings are
measured at an ambient outdoor
temperature of 80 °F. Id. The CA IOUs
asserted that these two factors often
cause tested units with fewer capacity
reduction stages to have higher
measured efficiencies than those with
more stages, whereas in reality, units
with more stages tend to be more
efficient. Id.
The CA IOUs stated that while the
IEER metric provides a valuable
measure of annual efficiency, the EER
metric is important for achieving
reductions in peak loads. (CA IOUs, No.
2 at p. 3) The CA IOUs stated that
because the IEER metric uses a low
weighting (i.e., 2 percent) of the fullload condition, a standard based only
on the IEER metric would incentive
manufacturers to optimize equipment at
the part-load conditions and could
potentially result in equipment that is
designed with lower full-load EERs than
the current standards for this
equipment. Id. The CA IOUs supported
using both the IEER metric that
measures part-load efficiencies in
conjunction with the currently regulated
full-load EER metric as a means to
prevent poor equipment performance at
full-load conditions. Id.
ASAP, NRDC, and ACEEE commented
that DOE should develop a new cooling
efficiency metric for SPVUs that reflects
annual energy consumption, including
part-load operation. (ASAP, NRDC, and
ACEEE, No. 4 at p. 1–2) They stated that
the current EER metric reflects only fullload, steady-state operation, but that
SPVUs rarely operate at full-load in the
field. Id. at 1. In addition, ASAP, NRDC,
and ACEEE stated that the current
metric is not able to demonstrate
potential improved efficiency of SPVUs
with variable-speed or thermostatic and
electronic expansion valve technologies.
Id.
ASAP, NRDC, and ACEEE also
commented that the IEER metric is not
representative of locations and usage
patterns for SPVUs and encouraged DOE
to investigate a part-load performance
metric that better reflects SPVU usage.
(ASAP, NRDC, and ACEEE, No. 4 at pp.
1–2) They commented that DOE should
consider its analysis from the most
recent SPVU standards rulemaking,
which included building simulation
models for modular classrooms,
modular offices, and telecommunication
shelters, to inform the development of
PO 00000
Frm 00009
Fmt 4701
Sfmt 4702
2497
load points and weightings for a partload metric. Id. at 2.
In response, DOE recognizes that
SPVUs often operate at part-load (i.e.,
less than designed full-load capacity) in
the field, depending on the application
and location. As discussed in section
III.B, AHRI 390–2021 includes a new
part-load cooling metric, IEER. To the
extent that AHRI expressed concerns
regarding the IEER test method in
response to the July 2018 TP RFI, DOE
presumes that AHRI’s original position
on this issue changed during the course
of developing AHRI 390–2021. The test
conditions and weighting factors for this
IEER metric in AHRI 390–2021 were
developed specifically for SPVUs based
on an annual building load analysis and
temperature data for buildings
representative of SPVU installations,
including modular classrooms, modular
offices, and telecommunication
shelters.10 The test conditions and
weighting factors for the four load levels
representing 100, 75, 50, and 25 percent
of full-load capacity are different than
those used in the IEER metric in AHRI
340/360–2019, which were developed
based on CUAC building types. As a
result, DOE considers the IEER metric
representative of the cooling efficiency
for SPVUs on an annual basis, and more
representative than the current EER
metric.
In this NOPR, DOE is proposing to
incorporate by reference AHRI 390–
2021, which maintains the existing fullload cooling mode metric, EER, and
adds the IEER metric for SPVUs. More
specifically, DOE is proposing to add a
new Appendix G that would include the
relevant test procedure requirements for
SPVUs for measuring efficiency using
the existing efficiency metrics (i.e., EER
for cooling mode and COP for heating
mode) and to add a new Appendix G1
that would incorporate the provisions
for measuring efficiency using IEER and
COP.
Issue 2: DOE requests comment on its
proposal to adopt the test methods
specified in AHRI 390–2021 for
calculating IEER for SPVUs.
As discussed, DOE’s current
standards for SPVUs at 10 CFR 431.97
specify minimum efficiency
requirements based on the full-load
cooling metric, EER, and the heating
metric, COP. The current DOE standards
levels are the same as those specified in
the current version of ASHRAE
Standard 90.1 (ASHRAE 90.1–2019).
10 Based on EnergyPlus analysis developed for the
previous energy conservation standards rulemaking
for SPVUs. 80 FR 57438, 57462 (Sept. 23, 2015).
EnergyPlus is a whole building energy simulation
program (Available at: https://apps1.eere.energy.gov/
buildings/energyplus/).
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
2498
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
Any future energy conservation
standards based on IEER would evaluate
differences in the measured energy
efficiency based on the IEER metric
relative to EER (i.e., by developing an
appropriate ‘‘crosswalk,’’ as necessary),
and would consider data and/or
analysis that compares the ratings of
SPVUs under the two metrics.
Issue 3: DOE requests comment and
data on ratings under the current EER
metric specified in 10 CFR 431.97 and
ASHRAE 90.1–2019 based on ANSI/
AHRI 390–2003, as compared to ratings
using the IEER metric under AHRI 390–
2021.
ASAP, NRDC, and ACEEE, as well as
NEEA and NWPCC, commented in
response to the July 2018 RFI that DOE
should consider a dynamic, load-based
test procedure to measure both cooling
and heating efficiency of SPVUs, similar
to the test procedure for residential
central air conditioners developed by
the Canadian Standards Association
(‘‘CSA’’) Group. (ASAP, NRDC, and
ACEEE, No. 4 at p. 2; NEEA and
NWPCC, No. 7 at p. 3) NEEA and
NWPCC commented that a load-based
test procedure, such as the CSA test
procedure, could measure energy use of
the equipment at 25, 50, 75 and 100percent load without overriding
equipment controls, as opposed to the
current IEER test specified in AHRI 340/
360 for CUACs that locks equipment
controls to 25, 50, 75 and 100 percent
of capacity. (NEEA and NWPCC, No. 7
at p. 3) They commented that a loadbased test would allow manufacturers to
design equipment controls and
thermostats that would reduce
unnecessary cycling and improve
humidity control. Id. According to
NEEA and NWPCC, the current IEER
test method specified in AHRI 340/360
uses an artificially low maximum
cycling loss that does not provide
incentive for manufacturers to reduce
cycling losses. Id. ASAP, NRDC, and
ACEEE, as well as NEEA and NWPCC,
commented that a load-based test would
better capture how SPVUs perform in
the field under varying loads, including
capturing the impact of cycling losses,
the potential benefits of variable-speed
operation, and the importance of control
strategies. (ASAP, NRDC, and ACEEE,
No. 4 at p. 2; NEEA and NWPCC, No.
7 at p. 3)
DOE is currently not aware of data
showing that any dynamic load-based
test procedure produces repeatable and
reproducible test results. Furthermore,
DOE is not aware of data showing that
the CSA test procedure recommended
by NEEA and NWPCC produces
repeatable and reproducible results for
central air conditioners (‘‘CACs’’) and
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
heat pumps, and that procedure has not
yet been evaluated for SPVUs.
Therefore, DOE is not proposing any
dynamic load-based test procedures at
this time.
2. Test Conditions Used for Efficiency
Metrics
Under 42 U.S.C. 6314(d)(1), EPCA
requires that representations with
respect to the energy consumption of
SPVUs must be based on the DOE test
procedure. DOE notes that the heating
mode test used to calculate COP and
determine compliance with standards
for SPVHPs is conducted at 47 °F
outdoor air dry-bulb temperature and
43 °F outdoor air wet-bulb temperature,
and is designated as the ‘‘Full Load
Standard Rating Capacity Test, Heating’’
in Table 3 of AHRI 390–2021. DOE is
proposing to also utilize Table 3 of
AHRI 390–2021, which includes an
optional ‘‘Low Temperature Operation’’
heating application rating test that
manufacturers may use to make
representations of energy consumption
for SPVUs. That test is based on an
outdoor air dry-bulb temperature of
17 °F and outdoor air wet-bulb
temperature of 15 °F.
To allow manufacturers to make
voluntary representations at the lower
temperature condition, DOE is
proposing to specify in Appendices G
and G1 that the low temperature
operation heating mode test conditions
specified in Table 3 of AHRI 390–2021
are optional. This would clarify that
additional representations for SPVHPs
at a lower temperature condition are
optional, but that if such representations
are made, they must be based on testing
conducted in accordance with the DOE
test procedure using the specified low
temperature operation heating mode test
conditions in addition to those made at
the full-load standard heating
conditions.
Issue 4: DOE requests comment on its
proposal to clarify that COP
representations using the ‘‘Low
Temperature Operation, Heating’’
conditions in Table 3 of AHRI 390–2021
are optional.
3. Fan Energy Use
As part of the July 2018 RFI, DOE
requested comment on whether changes
to the SPVU test procedure are needed
to properly characterize a representative
average use cycle, including changes to
more accurately represent fan energy
use in field applications. 83 FR 34499,
34503 (July 20, 2018). DOE also
requested information as to the extent
that accounting for the energy use of
fans in commercial equipment such as
SPVUs would be additive of other
PO 00000
Frm 00010
Fmt 4701
Sfmt 4702
existing accountings of fan energy use.
Id. The Appliance Standards and
Rulemaking Federal Advisory
Committee (‘‘ASRAC’’) Commercial and
Industrial Fans and Blowers Working
Group (‘‘Working Group’’) had earlier
provided recommendations regarding
the energy conservation standards, test
procedures, and efficiency metrics for
commercial and industrial fans and
blowers in a term sheet. (Docket No.
EERE–2013–BT–STD–0006–0179 at p. 1)
Specifically, recommendation #3
discussed the need for DOE’s test
procedures and related efficiency
metrics to account more fully for the
energy consumption of fan use in
regulated commercial air-conditioning
equipment. (Docket No. EERE–2013–
BT–STD–0006–0179 at pp. 3–4) The
Working Group recommended that DOE
consider revising efficiency metrics that
include energy use of supply and
condenser fans in order to include the
energy consumption during all relevant
operating modes, including ventilation
and part-load operation, in the next
round of test procedure rulemakings.
The Working Group included SPVUs in
its list of regulated equipment for which
fan energy use should be considered.
(Docket No. EERE–2013–BT–STD–
0006–0179 at pp. 3–4, 16)
In response to the 2018 RFI, ASAP,
NRDC, and ACEEE, as well as NEEA
and NWPCC, commented that DOE
should amend the test procedure to
account for fan energy use outside of
mechanical cooling and heating for fans
in regulated equipment to more fully
capture fan energy use. (ASAP, NRDC,
and ACEEE, No. 4 at p. 1; NEEA and
NWPCC, No. 7 at pp. 1–3) ASAP, NRDC,
and ACEEE asserted that by failing to
capture fan operation for economizing,
ventilation, and other functions outside
of cooling mode, the test procedure may
be significantly underestimating fan
energy consumption. (ASAP, NRDC,
and ACEEE, No. 4 at p. 1) NEEA and
NWPCC added that these amendments
would encourage the adoption of
features such as variable-speed fans,
which provide additional control and
flexibility for building owners and
operators in addition to reducing energy
waste. (NEEA and NWPCC, No. 7 at p. 2)
NEEA and NWPCC commented that
the commercial prototype building
models used in the analysis in support
of ASHRAE Standard 90.1 include
information on the operation of fans in
ventilation mode and economizer mode,
and these models could be used to
develop national average fan operating
hours outside of heating and cooling
modes. (NEEA and NWPCC, No. 7 at
p. 4) NEEA and NWPCC commented
that the vast majority of SPVUs are
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
installed in commercial buildings
requiring a building permit and that the
ASHRAE Standard 90.1 requirements
are reflective of building code
requirements. Id. NEEA and NWPCC
stated that, as a result, the energy
models used in support of ASHRAE
Standard 90.1 are representative of how
the equipment is installed and used
across the United States. Id.
NEEA and NWPCC commented that
one potential approach to represent fan
energy use in regulated equipment more
accurately would be to use IEER to
assess the efficiency of the refrigeration
cycle of SPVUs, and to use an
alternative metric to assess the
performance of embedded fans in
SPVUs. (NEEA and NWPCC, No. 7 at
pp. 3–4) NEEA and NWPCC suggested
that ANSI/AMCA 208–18, ‘‘Calculation
of the Fan Energy Index,’’ provides a
potential way to measure embedded fan
performance in SPVUs by using the fan
energy index (‘‘FEI’’). Id. NEEA and
NWPCC stated that DOE could,
therefore, develop a revised IEER-type
metric that weights together cooling
performance based on the traditional
IEER test and an FEI-based metric for
fan efficiency. Id. NEEA and NWPCC
stated that accounting for the energy use
of fan operation in SPVUs does not need
to alter measured efficiency, and that
DOE could align the FEI and IEER
metrics such that manufacturers would
have multiple viable design option
pathways to achieve the minimum IEER
efficiency standard without improving
the embedded fan efficiency above the
minimum FEI efficiency standard. Id.
AHRI and Lennox commented that
the current metrics for SPVUs (EER and
COP) account for fan power and that
there is no need to double count fan
contribution, asserting that standards
based on these metrics will likely
already require the need for improved
fan motor efficiency. (AHRI, No. 5 at pp.
6, 7; Lennox, No. 6 at p. 6) AHRI
commented that adding a requirement
to measure fan energy use during
economizing or electric heating would
increase testing burden. (AHRI, No. 5 at
p. 6)
AHRI and Lennox further commented
that while most SPVUs can provide
some level of ventilation, their primary
function is cooling and heating. (AHRI,
No. 5 at p. 7; Lennox, No. 6 at p. 6)
AHRI asserted that DOE is limited to
one metric per covered product, and,
therefore, the representative average use
cycle for SPVUs should concentrate on
the bulk of energy used during cooling
and heating, rather than the occasional
and ancillary fan-only ventilation
utility. (AHRI, No. 5 at p. 7) In addition,
AHRI asserted that a key goal in
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
prohibiting separate component
standards was to allow the manufacturer
to innovate to meet energy use
standards. Id.
AHRI commented that DOE has the
authority to include certain fans and
blowers, by rule, as ‘‘covered
equipment’’ if such products meet all
the requirements of 42 U.S.C. 6311(2),
but the commenter stated that it would
not be appropriate to apply such
standard to fans embedded in regulated
equipment. (AHRI, No. 5 at p. 8) AHRI
asserted that 42 U.S.C. 6312 limits
DOE’s authority to regulate as covered
industrial equipment certain articles
that are also components of consumer
products. Id. AHRI commented that
because the fans in SPVUs are built only
for the product and cannot be purchased
on the open market and applied as
‘‘stand alone fans,’’ the fans in SPVUs
are protected from double-regulation
under EPCA. Id. AHRI also commented
that DOE’s authority under 42 U.S.C.
6312(b) and (c) to regulate components
is based on necessity, and that adding
a fan metric to the current EER
requirement is not necessary because
SPVUs already have an overall energy
efficiency requirement. Id. AHRI and
Lennox commented that the fact that
Congress was compelled to grant a
specific provision of authority for a
consumer furnace ventilation metric
affirms that DOE lacks general authority
to create overlapping ventilation
requirements for other regulated
products. (AHRI, No. 5 at pp. 8–9;
Lennox, No. 6 at p. 6)
In response to these comments, DOE
does not have sufficient information at
this time regarding the operation of fans
outside of mechanical heating and
cooling during an average use cycle
(e.g., economizing, ventilation) specific
to SPVU installations as would allow it
to consider changing the existing
efficiency metric(s) to include this
aspect of energy use. DOE recognizes
that the current metrics for SPVUs do
not include fan energy use during all
relevant operation modes. Provisions to
measure fan energy use when there is no
heating or cooling being provided, and
when performing ancillary functions
(e.g., economizing, ventilation,
filtration, and auxiliary heat), are not
included in ANSI/AHRI 390–2003 and
have not been included in the updated
industry consensus standard, AHRI
390–2021. Further, DOE lacks sufficient
information on the number of units
capable of operating in these modes,
total energy use in these operating
modes, and information regarding the
frequency of operation of these modes
during field conditions, which the
Department would need to determine
PO 00000
Frm 00011
Fmt 4701
Sfmt 4702
2499
whether such testing would be
appropriate for SPVUs and/or to
develop a metric representing the
national average fan operating hours for
SPVUs. DOE notes further that the
commercial prototype building models
used in the analysis in support of
ASHRAE Standard 90.1 that NEEA and
NWPCC recommended do not include
information on building types typical to
SPVU installations (i.e., modular and
telecommunications). If additional
information becomes available as would
allow DOE to consider incorporation of
fan energy use during other relevant
SPVU operating modes for all relevant
building types into the test method and
metric for SPVUs, DOE may consider
such information in a subsequent
rulemaking proceeding. With regards to
comments concerning fan energy use
metrics and regulation of fan energy use
being double-counting, DOE will
consider its authority under EPCA when
and if developing such test procedures.
E. Test Method
This section discusses the various
issues that DOE identified in the test
methods for SPVUs, including those
raised in the July 2018 RFI and
considered as part of DOE’s review of
AHRI 390–2021. These issues include:
(1) Provisions for testing ducted and
non-ducted units; (2) outdoor air-side
airflow rate; (3) refrigerant charging
instructions; (4) voltage requirements;
(5) filter requirements; (6) airflow and
external static pressure requirements;
(7) air temperature measurements; (8)
defrost energy use; and (9) provisions
for the outdoor air enthalpy method.
In addition, in DOE’s existing
regulations, Table 1 to 10 CFR 431.96
specifies the applicable industry test
procedure for each category of
commercial package air conditioning
and heating equipment, and it identifies
additional testing requirements that also
apply. In this NOPR, DOE is proposing
to reorganize subpart F to 10 CFR part
431 so that the test procedure
requirements for SPVUs are included in
separate appendices (Appendix G and
G1). DOE proposes that Table 1 to 10
CFR 431.96 identify only the applicable
appendix to use for testing SPVUs
(Appendix G or G1) and that 10 CFR
431.96 would no longer include any
additional test requirements for SPVUs.
1. Unit Set-Up
a. Testing Ducted and Non-Ducted Units
DOE noted in the July 2018 RFI that
ANSI/AHRI 390–2003 specifies different
ESP requirements for ducted and nonducted units. 83 FR 34499, 34501 (July
20, 2018). Specifically, Section 5.2.2 of
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
2500
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
ANSI/AHRI 390–2003 requires that nonducted units be tested at zero ESP, and
it specifies ESP requirements in Table 4
of ANSI/AHRI 390–2003 for ducted
equipment. However, whether an SPVU
is ducted may depend on the
installation rather than the model. A
given SPVU model could be installed
either with or without a duct, thereby
resulting in its status as ducted or nonducted being determined in the field. In
the July 2018 RFI, DOE stated that it is
not aware of physical characteristics
that would readily distinguish SPVUs as
either ducted or non-ducted models and
that several models advertise the
capability for use in both ducted and
non-ducted installations. DOE noted
that ANSI/AHRI 390–2003 does not
specify how to determine whether an
SPVU model is to be tested using the
ducted or non-ducted provisions. As
part of the July 2018 RFI, DOE requested
comment on characteristics for
determining whether SPVU models
would be installed as ducted or nonducted and on how equipment sold for
both configurations are currently tested.
83 FR 34499, 34501 (July 20, 2018).
AHRI commented that many, if not
all, SPVUs on the market allow for
installation with or without a duct, and
that it is standard practice to test all
SPVUs in the ducted configuration.
(AHRI, No. 5 at pp. 2) AHRI stated that
the (then-draft) revised version of AHRI
390 sought to standardize industry
practice by defining a non-ducted unit
as an air conditioner or heat pump that
is not designed and marketed to deliver
conditioned air to the indoor space
through a duct(s), and that a factoryinstalled wall sleeve(s) would not be
considered as a duct. (AHRI, No. 5 at
pp. 2–3) AHRI also noted that the draft
version of AHRI 390 specified that if a
duct cannot be attached and the unit is
marketed as non-ducted only, then
testing would be performed in the nonducted configuration, and that all other
units would be tested as ducted. Id.
Lennox commented that any model
marketed for ducted applications should
be tested in a ducted configuration, and
that testing in a non-ducted
configuration would be appropriate if a
model does not provide provisions for
duct attachment and the unit is
marketed as non-ducted only. (Lennox,
No. 6 at p. 2)
DOE notes that the draft definition
and provisions referenced by AHRI are
included in AHRI 390–2021, along with
a definition for ducted units. DOE
preliminarily agrees that the definition
of a non-ducted unit and associated
provisions included in AHRI 390–2021
provide additional specification for
testing ducted and non-ducted SPVUs.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
DOE understands that these definitions
and provisions are consistent with how
units are currently classified by industry
and tested, as indicated by AHRI’s
comments and the inclusion in AHRI
390–2021. DOE is proposing to adopt
these definitions found in Sections 3.4
and 3.10 of AHRI 390–2021 and
associated provisions specified in
section 5.7 of AHRI 390–2021, as
enumerated in section 0 of the proposed
Appendix G and in section 0 of the
proposed Appendix G1.
b. Outdoor Air-Side Airflow Rate
The current DOE test procedure for
SPVUs requires that the unit be set up
for test in accordance with the
manufacturer installation and operation
manuals. 10 CFR 431.96(e). In addition,
Section 5.2.3 of ANSI/AHRI 390–2003
specifies that for SPVUs with an
outdoor air-side fan drive that is
adjustable, standard ratings are
determined at the outdoor-side airflow
rate specified by the manufacturer.
Section 5.2.3 of ANSI/AHRI 390–2003
also specifies that, where the outdoor
air-side fan drive is non-adjustable,
standard ratings are determined at the
outdoor airflow rate inherent to the
equipment when operated with all of
the resistance elements associated with
inlets, louvers, and any ductwork and
attachments considered by the
manufacturer as normal installation
practice.
However, Section 5.2.3 of ANSI/AHRI
390–2003 does not further specify what
attachments the manufacturer considers
‘‘normal installation practice.’’ For
externally-mounted SPVUs, provisions
for transferring outdoor air through an
external wall are not necessary, but it
may be possible that alternative
‘‘resistance elements’’ could be offered
as options (i.e., louvers instead of grills).
Furthermore, for internally-mounted
SPVUs, there may be multiple options
for the specific geometry for external
wall pass-through, as well as the option
for louvers instead of grills.
As part of the July 2018 RFI, DOE
requested comments on the variations in
outdoor air-side attachments (e.g., grills,
louvers, wall sleeve) that could affect
performance during testing and test
procedure provisions to standardize
outdoor air flow for both externally and
internally mounted SPVUs. 83 FR
34499, 34501 (July 20, 2018). On this
topic, ASAP, NRDC, and ACEEE
commented that DOE should
standardize which resistive elements
should be present for testing to ensure
that the test is representative of field
installations and to improve
repeatability and reproducibility of test
results. (ASAP, NRDC, and ACEEE, No.
PO 00000
Frm 00012
Fmt 4701
Sfmt 4702
4 at p. 3) AHRI stated that options for
different outdoor air-side attachments
do exist and could impact the
performance during testing. (AHRI, No.
5 at p. 3) AHRI and Lennox commented
that, to mitigate this issue, the
attachments to be used for testing
should be specified by the manufacturer
in the supplemental testing instructions
submitted to DOE. (AHRI, No. 5 at p. 3;
Lennox, No. 6 at p. 2) AHRI added that
information regarding the installation of
plenums, grills, or other outdoor air-side
attachments is provided by
manufacturers for testing conducted as
part of the AHRI certification program.
(AHRI, No. 5 at p. 3)
DOE notes that Section 5.8.4 of AHRI
390–2021 explicitly specifies use of the
outdoor air-side attachments specified
in the manufacturer’s supplemental
testing instructions. DOE expects this
practice would improve the
representativeness in that the unit is
tested in a configuration more similar to
that of the unit as installed in the
field.11 DOE also expects that the more
specific test set-up instruction would
improve the reproducibility of test
results by reducing potential variation
in the configuration of the unit when
tested. DOE understands that some
equipment may be offered for sale with
multiple outdoor air-side attachment
options, including an option to ship the
unit without any attachments. Based on
its review of manufacturer materials,
DOE has found that in such cases most
manufacturer’s instructions or
marketing materials indicate that use of
outdoor air-side attachments are
recommended or necessary for
installation. Based on the manufacturer
instructions, use of outdoor air-side
attachments is standard practice in field
use for units for which they are offered
for sale.
AHRI 390–2021 states that if a unit
includes multiple outdoor air-side
attachment options, including an option
for the unit to ship without any
attachments, an outdoor air-side
attachment must be specified in the
supplemental testing instructions. DOE
would expect that this instruction helps
ensure testing is representative of how
a unit would be installed and operated
in the field. DOE is proposing to adopt
these provisions regarding the outdoor
air-side attachments, as specified in
Section 5.8.4 of AHRI 390–2021,
11 Section 3.8.2 of AHRI 390–2021 specifies that
the supplemental testing instructions shall include
no instructions that deviate from the manufacturer’s
installation instructions unless necessary to comply
with steady-state requirements (in which case the
steady operation must match, to the extent possible,
the average performance obtained without deviating
from the manufacturer’s installation instructions).
E:\FR\FM\14JAP2.SGM
14JAP2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
lotter on DSK11XQN23PROD with PROPOSALS2
enumerated in section 0 of the proposed
Appendix G and section 0 of the
proposed Appendix G1.
c. Refrigerant Charging Instructions
The amount of refrigerant can have a
significant impact on the system
performance of air conditioners and
heat pumps. DOE’s current test
procedures for commercial package air
conditioners and heat pumps, including
the test procedures for SPVUs, require
that units be set up for test in
accordance with the manufacturer
installation and operation manuals. 10
CFR 431.96(e). In addition, the current
DOE test procedures state that if the
manufacturer specifies a range of
superheat, sub-cooling, and/or
refrigerant pressures in the installation
and operation manual, any value within
that range may be used to determine
refrigerant charge, unless the
manufacturer clearly specifies a rating
value in its installation or operation
manual, in which case the specified
value shall be used. 10 CFR 431.96(e)(1).
However, the current DOE test
procedures do not provide charging
instructions to be used if the
manufacturer does not provide
instructions in the manual that is
shipped with the unit or if the provided
instructions are unclear or incomplete.
DOE noted in the July 2018 RFI that
ANSI/AHRI 390–2003 does not provide
any specific guidance on setting and
verifying the refrigerant charge of a unit.
83 FR 34499, 34501 (July 20, 2018). DOE
also noted in the July 2018 RFI that the
test procedure final rule for central air
conditioners and heat pumps (‘‘CAC/
HPs’’) published in the Federal Register
on June 8, 2016 (81 FR 36992; ‘‘June
2016 CAC TP final rule’’) established a
comprehensive approach for refrigerant
charging to improve test reproducibility.
Id. The approach specifies which set of
installation instructions to use for
charging, explains what to do if there
are no instructions, specifies that target
values of parameters are the centers of
the ranges allowed by installation
instructions, and specifies tolerances for
the measured values. 10 CFR part 430,
subpart B, appendix M, section 2.2.5.
This approach also requires that
refrigerant line pressure gauges be
installed for single-package units, unless
otherwise specified in manufacturer
instructions. Id.
As part of the July 2018 RFI, DOE
sought comment on whether it would be
appropriate to adopt an approach for
charging requirements for SPVUs
similar to the approach adopted in the
June 2016 CAC TP final rule. 83 FR
34499, 34501 (July 20, 2018). DOE also
requested data demonstrating how
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
sensitive the performance of an SPVU is
to changes in the various charge
indicators used for different charging
methods, specifically the method based
on sub-cooling. Id.
ASAP, NRDC, and ACEEE commented
that while most manufacturers appear to
ship SPVUs with the refrigerant already
charged, DOE should still develop
consistent and comprehensive charging
instructions to ensure repeatable and
reproducible test results, and to account
for the possibility of products offering
different charging instructions in the
future. (ASAP, NRDC, and ACEEE, No.
4 at p. 3) NEEA and NWPCC
commented that DOE should review
how often SPVUs are charged with
refrigerant at the site when installed,
and that if refrigerant charge is often
modified at installation, they support
adopting charging requirements
consistent with the June 2016 CAC TP
final rule. (NEEA, NWPCC, No. 7 at p.
2)
AHRI commented that the charging
requirements adopted in the June 2016
CAC TP final rule are not appropriate
for SPVUs. (AHRI, No. 5 at p. 3) AHRI
stated that SPVUs are shipped charged
with refrigerant and no charging should
be required. Id. AHRI added that many
units do not have service ports, and
those that do are charged by weight to
the specification on the unit’s
nameplate. Id. Lennox stated that all of
its models are shipped with a full
refrigerant charge, and no further charge
adjustments are required. (Lennox, No.
6 at p. 3) Lennox also stated that if there
is any discrepancy regarding charge
quantity, the unit should be charged by
weight to the specification on the unit
nameplate. Id. Similarly, the CA IOUs
commented that because SPVUs are
factory-sealed, package units, many
charging requirements that were
adopted in the June 2016 CAC TP final
rule would not apply to SPVUs. (CA
IOUs, No. 2 at p. 1) The CA IOUs did
state that some language from the June
2016 CAC TP final rule would be
beneficial to adopt; in particular,
provisions related to pressure gauges for
single-package units and language
banning refrigerant charge adjustment
during testing. (Id. at pp. 1–2)
Based on a review of equipment
available on the market, DOE finds that
SPVUs are typically shipped from the
factory charged with refrigerant,
consistent with comments received.
DOE observed that while the majority of
units are charged by weight, at least one
manufacturer’s instructions specified
that if the refrigerant charge needs to be
adjusted (e.g., due to leaks), the charge
should be adjusted based on the
PO 00000
Frm 00013
Fmt 4701
Sfmt 4702
2501
manufacturer’s specified values for subcooling and superheat.
Section 5.6 of AHRI 390–2021
includes instructions for charging to be
used if sufficient information is not
provided in the manufacturer’s
installation instructions, similar to the
provisions for CACs adopted in the June
2016 CAC TP final rule. Specifically,
AHRI 390–2021 directs that charging be
performed at the conditions specified in
the manufacturer’s installation
instructions or, if not specified, at the
full-load cooling Standard Rating
Conditions. AHRI 390–2021 directs that
if the manufacturer’s installation
instructions specify a range for
superheat, sub-cooling, or refrigerant
pressure, the average of the range is
used to determine the refrigerant charge.
AHRI 390–2021 also specifies a
hierarchy of charging parameters to
follow (with charge weight being the
highest priority) if different
requirements provided in the
manufacturer’s installation instructions
cannot be simultaneously met. DOE
proposes to adopt section 5.6 in AHRI
390–2021 for refrigerant charging, as
enumerated in section 0 of the proposed
Appendix G and in section 0 of the
proposed Appendix G1.
The proposed refrigerant charging
instructions provide additional
specification to the Federal test method
that would produce more repeatable and
reproducible results. DOE notes that as
proposed, these refrigerant charging
provisions would only apply if the
manufacturer installation instructions
do not provide sufficient guidance
regarding refrigerant charging. As a
result, these provisions would not
restrict the flexibility that manufacturers
currently have in providing refrigerant
charging instructions, so long as the
provided instructions are sufficient.
d. Voltage Requirements
In the July 2018 RFI, DOE noted that
Section 5.2.1 of ANSI/AHRI 390–2003
requires that, for units rated with 208/
230 dual nameplate voltages, the test be
performed at 230 volts (V). 83 FR 34499,
34501 (July 20, 2018). For all other dual
nameplate voltage units, the test
standard requires that the test be
performed at both voltages, or at the
lower voltage if only a single rating is
to be published. Id. DOE also noted that
voltage can affect the measured
efficiency of air conditioners, and
requested data demonstrating the effect
of voltage on air conditioning
equipment. Id. DOE requested comment
on whether certain voltages within
common dual nameplate voltage ratings
(e.g., 208/230 V) are more representative
of a typical field installation. Id.
E:\FR\FM\14JAP2.SGM
14JAP2
2502
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
lotter on DSK11XQN23PROD with PROPOSALS2
Lennox commented that the voltage
requirements specified in ANSI/AHRI
390–2003 are consistent with other
similar industry test procedures and are
appropriate for this equipment.
(Lennox, No. 6 at p. 3) AHRI
acknowledged that voltage can affect the
measured efficiency of air conditioners,
but it stated that these variations tend to
be insignificant and do not correlate to
a specific voltage. (AHRI, No. 5 at pp.
2–3) AHRI also commented that the
majority of SPVUs are applied at 230 V,
and, therefore, the current test
procedure is appropriate. Id.
In response, DOE first points out that
Section 5.8.1 of AHRI 390–2021
maintains the same voltage
requirements for SPVUs as specified in
the current DOE test procedure and in
ANSI/AHRI 390–2003. DOE notes that
these voltage requirements are generally
consistent with industry test procedures
for other commercial air conditioning
and heat pump equipment. Accordingly,
DOE is proposing to adopt the voltage
requirements in Section 5.8.1 AHRI
390–2021, consistent with the existing
voltage requirements, as enumerated in
section 0 of the proposed Appendix G
and in section 0 of the proposed
Appendix G1.
e. Filter Requirements
DOE noted in the July 2018 RFI that
Section 5.2.2.a of ANSI/AHRI 390–2003
requires that non-filtered ducted
equipment be tested at the minimum
ESP specified in Table 4 of ANSI/AHRI
390–2003 plus an additional 0.08 inches
of water column (‘‘in H2O’’) of ESP. 83
FR 34499, 34501 (July 20, 2018). DOE
further noted that ANSI/AHRI 390–2003
does not define ‘‘non-filtered
equipment.’’ Id. As part of the July 2018
RFI, DOE requested comment on
whether any SPVUs are designed to be
installed without a filter. Id. at 83 FR
34499, 34502. DOE also requested
comment on the typical effectiveness
(i.e., minimum efficiency reporting
value (‘‘MERV’’) rating) of filters
provided with SPVUs. Id. DOE
requested comment on whether nonducted SPVUs intended for installation
with a filter are ever tested without a
filter installed and, if so, how such
testing has accounted for the filter
pressure drop to better represent actual
performance. Id.
AHRI and Lennox commented that all
SPVUs on the market are designed to be
installed with a filter, are shipped with
a filter, and should be tested with the
supplied filter. (AHRI, No. 5 at p. 4;
Lennox, No. 6 at p. 3) AHRI added that
the effectiveness of the filter can vary
based on application. (AHRI, No. 5 at p.
4) AHRI also stated that all SPVUs on
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
the market are tested with a filter. Id.
NEEA and NWPCC commented that
SPVUs are used primarily in
commercial buildings, and that
ASHRAE Standard 52.2, ‘‘Method of
Testing General Ventilation AirCleaning Devices for Removal Efficiency
by Particle Size,’’ recommends MERV 8
filters for commercial buildings.
Consequently, NEEA and NWPCC
recommended that SPVUs be tested
with a MERV 8 filter rating to be
representative of equipment use in the
field. (NEEA, NWPCC, No. 7 at p. 2) GE
commented that any test procedure
change requiring the addition of a filter
would increase test burden and product
development cost. (GE, No. 3 at p. 2) GE
stated that filter types, sometimes
specified by local or State requirements,
differ and that there is a risk of
unintended test variation depending
upon the filter specified. Id. GE stated
that such variation could result in
erroneous enforcement test results. Id.
GE also commented that it opposes any
test procedure change that potentially
could dictate product design
requirements, such as filter selection. Id.
Section 3.19 of AHRI 390–2021
includes a definition for the term
‘‘Standard Filter’’ and requires that an
SPVU must be tested with the filter
designated by the manufacturer in the
marketing materials for the model as the
‘‘default’’ or ‘‘standard’’ filter in Table 2,
and does not allow for testing without
a filter. Section 5.7.3.1 of AHRI 390–
2021 states that if the manufacturer does
not specify a ‘‘default’’ or ‘‘standard’’
filter option, then the Standard Filter is
the filter with the lowest level of
filtration, as specified in the marketing
materials for the model. If the marketing
materials do not specify a Standard
Filter, or do not specify which filter
option has the lowest filtration level,
then the Standard Filter is any filter
shipped by the manufacturer for that
model.
In light of the above, DOE
preliminarily concludes that a 0.08 in
H2O increase in the minimum ESP for
units tested without a filter is not
necessary in the SPVU test procedure
because, based on a review of
equipment on the market and supported
by the comments from AHRI and
Lennox, DOE finds that all SPVUs are
designed to be installed with a filter, are
shipped with a filter, and are tested
with a filter. In response to NEEA and
NWPCC, DOE identified many SPVUs
that offered filters with lower filtration
than MERV 8 filters, so requiring them
may not be representative of all field
applications. In addition, based on a
review of equipment on the market,
different manufacturers might specify
PO 00000
Frm 00014
Fmt 4701
Sfmt 4702
different filters as ‘‘standard’’ (i.e., there
is not a single filter type recognized as
‘‘standard’’ by the industry).
Manufacturers might also market an
SPVU with multiple filter options from
which the consumer can choose.
DOE has, therefore, initially
determined that the requirement to test
with a filter and the provisions on filter
selection would provide more
representative results by testing with a
filter that is more likely to be used by
a consumer in the field and is consistent
with how manufacturers are currently
testing. In this NOPR, DOE proposes to
adopt the provisions in Section 3.19 and
Table 2 in AHRI 390–2021 for testing
with the Standard Filter, as enumerated
in section 0 of the proposed Appendix
G and section 0 of the proposed
Appendix G1.
f. External Static Pressure and Airflow
Requirements
SPVUs include fans that circulate
indoor air over a heat exchanger and
provides heating or cooling either
through ductwork or directly to the
conditioned space. To deliver sufficient
conditioned air to the intended space,
the airflow provided by the unit must
overcome pressure losses throughout
duct work (if present), and to a smaller
degree, within the unit itself. Pressure
losses are the result of directional
changes in the ductwork, friction
between the moving air and surfaces of
the ductwork, and possible
appurtenances in the airflow path.
Further, different modes of operation
may require different amounts of
airflow. Therefore, indoor fan speed is
typically adjustable to assure that the
provided airflow rate is appropriate for
the field-installed ductwork system
serving the building in which the unit
is installed. The performance of an
SPVU can be significantly affected by
variation in ESP or operation with an
indoor airflow that is different from the
intended or designed airflow. To ensure
that a test procedure provides results
that are representative of an average-use
cycle, appropriate airflow settings for
testing and ESP requirements are
needed to reflect the typical pressure
losses. Such specifications would also
contribute to the repeatability of the test
procedure.
i. External Static Pressure
As part of the July 2018 RFI, DOE
noted that Table 4 of ANSI/AHRI 390–
2003 specifies the minimum ESP
required for testing ducted SPVUs based
on capacity range. DOE sought
comments on whether the minimum
ESP requirements in ANSI/AHRI 390–
2003 are representative of field
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
operation for ducted SPVUs, and if not,
comment and data on what
representative minimum ESP levels
would be. 83 FR 34499, 34502 (July 20,
2018).
The CA IOUs, as well as ASAP,
NRDC, and ACEEE, commented that the
minimum ESP requirements in the test
procedure may be significantly lower
than typical ESPs in the field, which
would significantly underestimate fan
power consumption. (CA IOUs, No. 2 at
pp. 2–3; ASAP, NRDC, and ACEEE, No.
4 at p. 3) ASAP, NRDC, and ACEEE
commented that DOE should ensure that
the minimum ESP requirements
specified in the SPVU test procedure
adequately reflect conditions in the
field. (ASAP, NRDC, and ACEEE, No. 4
at p. 3) NEEA and NWPCC added that
the ASRAC Working Group for
commercial package air conditioners
recommended that DOE develop
minimum ESP requirements for SPVUs
that adequately represent performance
in the field and that provide accurate
information to consumers to make
purchasing decisions. (NEEA and
NWPCC, No. 7 at pp. 1–2)
NEEA and NWPCC stated that for
CUACs, there is inconsistency between
the range of ESPs specified in the test
procedure (0.2 to 0.75 in H2O) compared
to the range of ESPs used for the
analysis for the standards rulemaking
(0.75 and 1.25 in H2O). (NEEA and
NWPCC, No. 7 at p. 2) NEEA and
NWPCC stated that if the ESP
requirements in the test procedure are
lower than those typically found in the
field, the ratings of SPVUs will provide
neither an adequate representation of
actual efficiency nor accurate
information to consumers. Id. NEEA and
NWPCC added that the ESP
requirements should have no impact on
test burden since there would be no
change to how the test is conducted. Id.
The CA IOUs referenced the
minimum ESP requirement of 0.5 in
H2O for residential central air
conditioners and heat pumps with
capacities less than 65,000 Btu/h, as
specified in 10 CFR part 430, subpart B,
appendix M1, ‘‘Uniform Test Method
for Measuring the Energy Consumption
of Central Air Conditioners and Heat
Pumps,’’ and commented that DOE
should align all other heating,
ventilating, and air conditioning
(‘‘HVAC’’) equipment, including SPVUs,
with the values specified in Appendix
M1, which increase in ESP based on
corresponding increases in cooling
capacity. (CA IOUs, No. 2 at pp. 2–3)
AHRI commented that based on
conversations with company
application engineers, the minimum
ESP requirements specified in ANSI/
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
AHRI 390–2003 are representative of
field operation for ducted SPVUs
installed with 10 feet of ductwork or
less. (AHRI, No. 5 at p. 4) Lennox also
stated that the current ESP requirements
are representative of field operation for
ducted SPVUs. (Lennox, No. 6 at p. 4)
No commenter provided data as to the
ESPs experienced in field operation.
In response, DOE notes the range of
comments received as to the appropriate
ESP for testing. AHRI 390–2021
maintained the same minimum ESP
requirements as specified in ANSI/AHRI
390–2003. DOE does not have data
indicating that these minimum ESP
requirements are unrepresentative of
field operation for ducted SPVUs. DOE
also recognizes that SPVUs are typically
installed in smaller modular buildings
with different duct configurations. As a
result, DOE notes that minimum ESP
requirements for other equipment (e.g.,
CACs, CUACs) may not be relevant for
SPVUs. DOE also notes that in the
previous standards rulemaking the ESP
values were aligned with the values
used in the test procedure. As a result,
DOE does not expect there to be
inconsistency between the test
procedure and the analysis conducted
for the standards rulemaking. Based on
this, DOE is tentatively not proposing to
revise the ESP requirements in the DOE
test procedure for SPVUs but to instead
remain consistent with AHRI 390–2021.
Issue 5: DOE welcomes data and
information on ESP conditions
experienced in field operation of ducted
SPVUs.
ii. Airflow Rate
Full-Load Cooling Test
DOE noted in the July 2018 RFI that
ANSI/AHRI 390–2003 does not specify
tolerances on achieving the rated
airflow or the minimum ESP during
testing. As discussed previously, the
performance of an air conditioner or
heat pump can be affected by variations
in airflow and ESP. In the July 2018 RFI,
DOE noted that the current DOE test
procedure for CUACs requires that the
indoor airflow for the full-load cooling
test be within ±3 percent of the rated
airflow and specifies a tolerance of
¥0.00/+0.05 in H2O for the ESP
requirements. 83 FR 34499, 34502 (July
20, 2018). DOE also noted that in DOE’s
test procedure for CAC/HPs, the method
for setting indoor air volume rate for
ducted units without variable-speed
constant-air-volume-rate indoor fans is a
multi-step process that addresses the
discrete-step fan speed control of these
units. Id. In this method, (a) the air
volume rate during testing may not be
higher than the certified air volume rate,
PO 00000
Frm 00015
Fmt 4701
Sfmt 4702
2503
but may be up to 10 percent less, and
(b) the ESP during testing may not be
lower than the minimum specified ESP,
but may be higher than the minimum if
this is required to avoid having the air
volume rate overshoot its certified
value. 10 CFR part 430, subpart B,
appendix M, section 3.1.4.2.a. As part of
the July 2018 RFI, DOE requested
information on the different types of
indoor air fan drive systems that are
used for SPVUs and information on
appropriate tolerances for setting
airflow and ESP. 83 FR 34499, 34502
(July 20, 2018).
On this topic, AHRI stated that SPVUs
use permanent split-capacitor motors
with discrete speed settings or
electronically-commutated motors with
variable speed settings; and that in
either case, the unit leaves the factory
with the fan and motor set at a specific
speed to provide the rated performance.
(AHRI, No. 5 at p. 4) Lennox
commented that its equipment uses
motors and controls with speed/airflow
settings developed for each specific
product and mode of operation, which
are factory pre-set to optimize
performance. (Lennox, No. 6 at p. 4)
Lennox stated that for its equipment, the
manufacturer-specified airflow setting
should allow the ability to set the
airflow to the specified value while
meeting the ESP requirements for
testing. Id. Lennox further commented
that the manufacturer settings should be
used for testing. Id. Lennox stated that
if the minimum ESP cannot be
maintained, the airflow should be set to
the maximum airflow while maintaining
the required ESP. Id.
AHRI commented that the then-draft
version of AHRI 390 directed use of the
manufacturer-specified fan control
settings for all tests for which they are
provided. (AHRI, No. 5 at p. 4) AHRI
also commented that the draft version of
AHRI 390 directed use of the full-load
cooling fan control settings specified by
the manufacturer for all tests for which
fan control settings are specified, and if
there are no specified fan control
settings for any tests, use the as-shipped
fan control settings for all tests. Id.
AHRI added that for testing, the priority
is setting the correct airflow speed, and
the ESP is adjusted to match the
required airflow. Id. AHRI noted that
the draft version of AHRI 390 provided
that the airflow-measuring apparatus
should be adjusted to maintain ESP
within ¥0/+0.05 in H2O of the required
minimum ESP and to maintain the
airflow within ±3 percent of the
manufacturer-specified full-load cooling
airflow. Id.
DOE notes that AHRI 390–2021
specifies an airflow tolerance of ±3
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
2504
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
percent of the full-load cooling airflow.
This would be consistent with the test
procedure for other commercial air
conditioning and heat pump equipment,
and it would ensure that the rated
airflow remains representative of field
use during testing. Therefore, DOE has
tentatively concluded that the ±3
percent airflow tolerance included in
AHRI 390–2021 is appropriate for
testing SPVUs. Accordingly, DOE
proposes to adopt the full-load cooling
airflow tolerance specified in Section
5.7 of AHRI 390–2021.
AHRI 390–2021 also includes
additional instructions for how to set
indoor airflow if the airflow and ESP
tolerances cannot be maintained
simultaneously. For non-ducted units,
ducting is not installed in the field;
therefore, increasing ESP (which
simulates the resistance to airflow from
longer duct length in the field) beyond
the specified tolerance of ¥0/+0.05 in
H2O during testing would not be
representative of field application.
Consequently, if both the ESP and
airflow cannot be maintained within
tolerance during the test, Section
5.7.3.3.4 of AHRI 390–2021 specifies
that the ESP be maintained within the
required tolerance and an airflow as
close to the certified value as possible
be used.
For ducted units, if ESP and/or
airflow are higher than the tolerance
range at the lowest fan control setting
(e.g., lowest fan speed), maintaining
airflow within tolerance should take
precedence over maintaining ESP
within tolerance. This is because
operating with an airflow higher than
the certified value would likely result in
an airflow (and thus measured
efficiency) that is unrepresentative of
field operation. Section 5.7.3.4.1.2 of
AHRI 390–2021 specifies that the
airflow-measuring apparatus be adjusted
to maintain airflow within tolerance and
to operate with the lowest possible ESP
that meets the minimum requirement. If
ESP or airflow are lower than the
tolerance range at the maximum fan
control setting (e.g., highest fan speed),
maintaining ESP at or above the
minimum value should take precedence
over maintaining airflow within
tolerance because operating with an ESP
lower than the minimum value does not
reflect typical duct lengths (or measured
efficiency) in field application. In such
a case, Section 5.7.3.4.1.3 of AHRI 390–
2021 specifies that the airflowmeasuring apparatus be adjusted to
maintain ESP within tolerance and to
operate with an airflow as close as
possible to the certified value.
DOE understands the provisions
regarding tolerances and priority for
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
adjustment of fan speed and ESP in
AHRI 390–2021 are consistent with the
methodology in the draft version of
AHRI 390, as evidenced by the excerpt
provided in AHRI’s comments (AHRI,
No. 5 at p. 5). DOE preliminarily finds
that these provisions would not conflict
with any provisions in the current DOE
test procedure, and would improve test
repeatability and provide test conditions
that are more representative of those
during operation in the field. Based on
this, DOE is proposing to adopt the
provisions specified in Section 5.7.3 of
AHRI 390–2021 for setting indoor
airflow if the airflow and ESP tolerances
cannot be maintained simultaneously,
as enumerated in section 0 of the
proposed Appendix G and section 0 of
the proposed Appendix G1.
Heating Test
DOE noted in the July 2018 RFI that
ANSI/AHRI 390–2003 does not
distinguish between cooling and heating
airflow rates required for testing. 83 FR
34499, 34502 (July 20, 2018). For
SPVHPs with multiple-speed or
variable-speed indoor fans, the indoor
airflow rate in heating operation could
be different from that in cooling
operation. Id. Different airflow rates
may be used for heating and cooling
operation because of different indoor
comfort needs in the heating season,
and there may be a minimum heating
airflow rate for electrical resistance
heating safety that exceeds the cooling
airflow rate. Id. DOE also noted in the
July 2018 RFI that, for CUAC heat
pumps, DOE’s current test procedure
requires that indoor airflow and ESP
first be established within required
tolerances for the full-load cooling test
condition by adjusting both the unit
under test and the test facility’s airflowmeasuring apparatus (see 10 CFR part
431, subpart F, appendix A, section
6(ii)). 83 FR 34499, 34502 (July 20,
2018)) The CUAC test procedure further
provides that, unless the unit is
designed to operate at different airflow
rates for cooling and heating modes, if
necessary, the airflow-measuring
apparatus (but not the unit under test)
may be adjusted to achieve an airflow in
heating mode equal to the cooling fullload airflow rate within the specified
tolerance, without regard to changes in
ESP (see 10 CFR part 431, subpart F,
appendix A, section 6(ii)). 83 FR 34499,
34502 (July 20, 2018).
As part of the July 2018 RFI, DOE
requested comment on whether
provisions similar to those required for
CUACs would be appropriate for
determining airflow rate and minimum
ESP for heating mode tests for SPVHPs.
83 FR 34499, 34502 (July 20, 2018).
PO 00000
Frm 00016
Fmt 4701
Sfmt 4702
NEEA and NWPCC commented that if
SPVHPs operate at different airflow
speeds for heating and cooling, then
SPVUs should be tested similar to
CUACs, for which the heating efficiency
is evaluated at the unique heating
airflow rate. (NEEA and NWPCC, No. 7
at p. 3) Lennox commented that SPVHP
airflow rates for heating and cooling are
generally the same, but that the test
procedure should not preclude using
different airflow rates that could
provide benefits in performance.
(Lennox, No. 6 at p. 4) AHRI added that
the draft version of AHRI 390 included
procedures that provide for a difference
in the manufacturer-specified heating
airflow and full-load cooling airflow.
(AHRI, No. 5 at pp. 4–5)
In response, DOE notes that AHRI
390–2021 includes provisions for setting
the heating airflow rate that are
consistent with the excerpt of the draft
version of AHRI 390 provided in AHRI’s
comments, (AHRI, No. 5 at p. 5), which
allows for testing with a manufacturerspecified heating airflow that is
different than the full-load cooling
airflow. These provisions reflect that
units may be designed to operate in the
field at a different heating airflow rate
as compared to the cooling airflow rate.
Therefore, DOE is proposing to adopt
Sections 5.7.2.3 and 5.7.3.4.2 of AHRI
390–2021 with regards to setting the
airflow and ESP for heating tests (as
applicable), as enumerated in section 0
of the proposed Appendix G and section
0 of proposed Appendix G1.
2. Air Temperature Measurements
Measurement of air conditions is a
critical aspect of performance testing for
air-conditioning and heat pump
equipment generally. The air conditions
affect performance (both capacity and
power input), and the primary methods
for determination of capacity rely on
measurements of air temperature and
humidity. ANSI/ASHRAE 390–2003
references ANSI/ASHRAE Standard 37–
1988, ‘‘Methods of Testing for Rating
Unitary Air-Conditioning and Heat
Pump Equipment’’ (‘‘ANSI/ASHRAE
37–1988’’) for methods of testing
SPVUs. As relevant here, ANSI/
ASHRAE 37–1988 provides
specifications for temperature sensors
(section 5.1), as well as for ensuring
measurement uniformity (section 8.5).
DOE noted in the July 2018 RFI that,
for air-cooled and evaporatively-cooled
CUACs, AHRI 340/360–2015 provides
more extensive direction for condenser
air temperature measurement in its
Appendix C, including specifications to
use air sampling trees and
psychrometers, temperature
measurement accuracy requirements,
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
and other specifications to ensure that
the measured conditions are
representative of average condenser air
inlet conditions. 83 FR 34499, 34503
(July 20, 2018). In the July 2018 RFI,
DOE requested comment on whether
requirements similar to AHRI 340/360–
2015 should be adopted for testing
SPVUs. Id.
DOE also noted in the July 2018 RFI
that while Appendix C of AHRI 340/
360–2015 provides detailed direction
for measurement of entering outdoor air
temperature, it provides no such
direction for measurement of entering
indoor air temperature, indoor leaving
air temperature, or outdoor leaving air
temperature. 83 FR 34499, 34503 (July
20, 2018). However, these parameters
have a significant impact on
performance of an SPVU as measured by
the indoor air enthalpy method and the
outdoor air enthalpy method. Id.
Therefore, in the July 2018 RFI, DOE
also requested comment on whether the
requirements contained in Appendix C
of AHRI 340/360–2015 would be
appropriate for measurement of these
parameters when testing SPVUs. Id.
The CA IOUs, NEEA and NWPCC
supported using provisions similar to
Appendix C of AHRI 340/360–2015 to
measure indoor air entering and leaving
temperatures, as well as outdoor air
entering and leaving temperatures. (CA
IOUs, No. 2 at p. 2; NEEA and NWPCC,
No. 7 at p. 3) NEEA and NWPCC added
that this would result in the most
accurate and repeatable test
measurement. (NEEA and NWPCC, No.
7 at p. 3) AHRI commented that adding
measurement requirements for indoor
air entering and leaving temperatures, as
well as outdoor air entering and leaving
temperatures for water slinger systems
(i.e., units that use condensate from the
evaporator to enhance condenser
cooling), similar to those in Appendix C
of AHRI Standard 340/360–2015 would
be appropriate. (AHRI, No. 5 at p. 6)
Lennox commented that further
evaluation of various SPVU
configurations is needed to determine
appropriateness of the provisions in
Appendix C of AHRI 340/360–2015.
(Lennox, No. 6 at p. 5)
In the interim, AHRI 390–2021 has
addressed this issue. Specifically,
Appendix D of AHRI 390–2021 includes
a comprehensive set of provisions to
measure air temperatures, including the
measurement of entering indoor
temperature, indoor leaving
temperature, entering outdoor
temperature, and outdoor leaving
temperature. DOE notes that these
additional requirements were also
included in the revised AHRI 340/360–
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
2019. Specifically, AHRI 390–2021
includes the following requirements:
• Measurements of indoor and
outdoor air entering dry-bulb
temperatures and water vapor
conditions. In addition, measurement of
the indoor air leaving dry-bulb
temperatures and water vapor
conditions if the indoor air enthalpy
method is used, and outdoor air leaving
dry-bulb temperatures and water vapor
conditions if the outdoor air enthalpy
method is used;
• Temperature measurement
accuracies and display resolutions for
dry-bulb and wet-bulb temperatures, as
well as thermopile temperatures;
• Methods of water vapor
measurement using either an aspirating
psychrometer or a dew point
hygrometer;
• Air sampling tree specifications,
including construction provisions, hole
density requirements, average air
velocity of the flow area, and thermopile
arrangement;
• Description of the test set-up for air
sampling trees, which includes defining
the arrangement of the face area, the
number of aspirating psychrometers per
unit side, the location of the air
sampling trees and their coverage of the
entrance to the unit, and the number of
sampling trees per aspirating
psychrometer;
• Dry-bulb temperature measurement
using psychrometer dry-bulb sensors;
• Wet-bulb or dew point temperature
measurements to determine air water
vapor content using psychrometers or
hygrometers;
• Measurements of temperature
change and pressure drop across the
conduit used to transfer air from air
samplers to psychrometers and, if
certain thresholds are exceeded,
provisions for determining dry-bulb
temperature and atmospheric pressure
(used to calculate humidity ratio);
• Specifications for dry-bulb and wetbulb temperature uniformity;
• Additional specifications for
measuring air conditions entering the
indoor coil, including provisions for
returning sampled air to the room,
conditions for temperature uniformity
specifications, and directions if air is
sampled within a duct; and
• Additional specifications for
measuring both indoor coil and outdoor
coil leaving air conditions, including
conditions for temperature uniformity
requirements, provisions for returning
sampled air to the duct leaving the coil,
provisions if the coil has a blow-through
fan, and additional requirements for the
air sampling tree.
DOE has tentatively determined that
the air measurement provisions of AHRI
PO 00000
Frm 00017
Fmt 4701
Sfmt 4702
2505
390–2021 in Appendix D address the
lack of specificity in the current DOE
test procedure for SPVUs, improve
temperature uniformity and ensure
accurate and repeatable temperature
measurements for SPVUs, and ensure
that representative conditions are
maintained during testing. Therefore,
DOE is proposing to adopt the
provisions for measurement of air
conditions in Appendix D of AHRI 390–
2021 both into section 1 of the proposed
Appendix G and into section 1 of the
proposed Appendix G1. Inclusion in
AHRI 390–2021 and AHRI’s comments
in support indicate that the proposed air
measurement specifications are
considered best practice by industry and
reflect current industry practice. As
such, DOE would expect that adoption
of the air measurement specifications in
AHRI 390–2021 would present minimal,
if any, increase in test burden for
manufacturers.
3. Defrost Energy Use
In the July 2018 RFI, DOE noted that
SPVHPs generally include a defrost
cycle to periodically defrost the outdoor
coil when operating in outdoor ambient
conditions in which frost collects on it
during heating operation. 83 FR 34499,
34504 (July 20, 2018). Based on
preliminary DOE review of product
literature, the time between defrost
cycles can be between 30 and 90
minutes, and typical defrost cycle
duration is approximately 10 minutes.
Id. During the defrost cycle, the SPVHP
is consuming energy but is not
providing heat to the conditioned space,
unless it also energizes auxiliary heat
during defrost. Id.
The current Federal test procedure for
SPVUs is based on testing in outdoor air
conditions for which defrost is not
necessary (i.e., 47 °F outdoor air drybulb temperature). This means that any
differences in defrost cycle performance
between different SPVHP models is not
reflected in the heating mode metric
(i.e., COP). DOE noted in the July 2018
RFI that the DOE test procedure for
CACs/HPs includes measurement of
average delivered heat and total energy
use (including for defrost cycles) during
operation in outdoor conditions for
which frost forms on the outdoor coil.
Id. In contrast, DOE’s test procedures for
commercial heat pumps do not include
consideration of defrost. Id. In the July
2018 RFI, DOE requested information
regarding the types of buildings most
commonly served by SPVHPs, as well as
the annual heating and cooling loads for
such buildings. Id. DOE also requested
information on the impact on heating
mode efficiency associated with the
defrost cycle for SPVHPs, including
E:\FR\FM\14JAP2.SGM
14JAP2
2506
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
lotter on DSK11XQN23PROD with PROPOSALS2
impacts associated with the potential
use of resistance heating during defrost.
Id.
On this topic, the CA IOUs stated that
relocatable classrooms commonly
utilize SPVUs. The CA IOUs suggested
that DOE should consider the CA Public
Utilities Commission building prototype
for relocatable classrooms.12 This
prototype provides typical dimensions,
plug loads, lighting, occupancy
schedule, envelope characteristics, and
thermostat set points of relocatable
classrooms which allows for the
modeling of annual cooling and heating
loads. (CA IOUs, No. 2 at p. 4) The CA
IOUs stated that this building prototype
was based on the Lawrence Berkeley
National Laboratory study titled ‘‘HighPerformance Commercial Buildings
Project’’ from 2003.13 Id.
ASAP, NRDC, and ACEEE commented
that DOE should incorporate defrost and
performance at lower ambient
temperatures in the heating efficiency
metric. (ASAP, NRDC, and ACEEE, No.
4 at p. 2) ASAP, NRDC, and ACEEE
stated that incorporating defrost would
allow the test procedure to better reflect
actual heating capacity and efficiency in
the field, thereby providing better
information to consumers and
encouraging manufacturers to develop
innovative defrost strategies. Id. ASAP,
NRDC, and ACEEE also encouraged
DOE to incorporate performance at
lower ambient temperatures into the
metric for heating efficiency. Id.
SPVHPs typically include back-up
electric resistance heating, which is
used when the heat pump cannot meet
the heating load. ASAP, NRDC, and
ACEEE stated that because the test
procedure only requires testing SPVHPs
at 47 °F outdoor air dry-bulb
temperature for heating mode, it does
not differentiate the ability of
equipment to maintain good heating
capacity using the heat pump cycle at
low ambient temperatures, as opposed
to shutting the heat pump cycle off and
switching to electric resistance heating.
Id. According to ASAP, NRDC, and
ACEEE, incorporating performance at
lower ambient temperatures in the
heating efficiency metric would
encourage equipment designs that
maintain efficiency performance at low
12 The CA Public Utilities Commission (CPUC)
building prototype for relocation classrooms is
available as part of the CPUC’s Database for Energy
Efficiency Resources, available at: https://
www.deeresources.com/.
13 Selkowitz, Stephen, High Performance
Commercial Building Systems. Prepared by the
Lawrence Berkeley National Laboratory for the
California Energy Commission. LBNL–53538
(October 2003) (Available at: https://www.osti.gov/
servlets/purl/821762).
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
ambient temperatures, which will
ultimately benefit consumers. Id.
NEEA and NWPCC commented that
the frequency of defrost cycles varies
between manufacturers and that the
defrost cycle typically stays on for
approximately 10 minutes. (NEEA and
NWPCC, No. 7 at p. 4) NEEA and
NWPCC recommended decreasing the
efficiency rating by a given increment
based on average annual defrost energy
use for the default defrost cycle
frequency setting. Id. NEEA and
NWPCC stated that this would likely
lead to manufacturers reducing the
frequency of their default defrost cycles,
which would result in energy savings
for building applications that do not
need frequent defrost cycles. Id.
AHRI and Lennox commented that
they respectively estimated that fewer
than 30 and 20 percent of SPVUs are
heat pumps, and they argued that DOE’s
proposal to include provisions to
measure the average delivered heat and
total energy use, including for defrost
cycles, during operation in outdoor
conditions for which frost forms on the
outdoor coil is not necessary for this
equipment. (AHRI, No. 5 at p. 9;
Lennox, No. 6 at p. 6) AHRI added that
the electric heat used during defrost is
small in comparison to electric heat use
when the heat pump cannot keep up to
meet the heating load. (AHRI, No. 5 at
p. 9)
DOE notes that AHRI 390–2021 does
not include provisions for measuring
defrost energy for SPVHPs. Consistent
with ANSI/AHRI 390–2003, AHRI 390–
2021, and DOE’s test procedures for
other commercial heat pumps, DOE is
not proposing to include provisions for
including the defrost energy of SPVHPs.
DOE notes that the study the CA IOUs
cited only monitored relocatable
classrooms within the State of California
and does not encompass the different
types of SPVU installations or operating
conditions. At this time, DOE lacks
sufficient information on the number of
SPVHP installations by building type
and geographical region, as well as
information regarding the frequency of
operation of defrost cycles or
representative low ambient conditions
during field use and the annual heating
and cooling loads in those installations,
which would be needed to determine
whether such testing conditions would
be appropriate for SPVUs and to
develop a metric representing the
national average for SPVUs.
Issue 6: DOE requests comment and
data on the number of SPVHP
installations by building type and
geographical region and the annual
heating and cooling loads for such
buildings. DOE also requests data on the
PO 00000
Frm 00018
Fmt 4701
Sfmt 4702
frequency of operation of defrost cycles
and representative low ambient
conditions for those buildings and
installations.
4. Outdoor Air Enthalpy Method
As discussed previously, the current
DOE test procedure, which incorporates
by reference ANSI/AHRI 390–2003, also
references ANSI/ASHRAE 37–1988 for
methods of testing SPVUs. Section 7.2
of ANSI/ASHRAE 37–1988 specifies
primary and secondary capacity
measurements for equipment with
cooling capacities less than 135,000
Btu/h. Specifically, the indoor air
enthalpy method must be used as the
primary method for capacity
measurement, and Table 3 of ANSI/
ASHRAE 37–1988 specifies the
applicable options for selecting a
secondary method. The two test
methods must agree within 6 percent
(see Section 10.1.2 of ANSI/ASHRAE
37–1988).
DOE noted in the July 2018 RFI that
the outdoor air enthalpy test method is
commonly used as the secondary test
method for determining capacity for
SPVUs. 83 FR 34499, 34502–34503 (July
20, 2018). The outdoor air enthalpy
method specified in ANSI/ASHRAE 37–
1988 specified the use of an air-side test
apparatus that is connected to the unit
under test. However, the airflow and
operating conditions achieved with the
outdoor air-side test apparatus
connected may differ from those
achieved without the apparatus
connected. Therefore, Section 8.5 of
ANSI/ASHRAE 37–1988 (which is
referenced by ANSI/AHRI 390–2003)
specifies testing both with and without
the air-side test apparatus connected. Id.
at 83 FR 34503. ANSI/ASHRAE 37–1988
specifies first conducting a one-hour
preliminary test without the outdoor airside test apparatus connected, followed
by a second one-hour test with the
outdoor air-side test apparatus
connected. Id. The second test (with the
outdoor air-side test apparatus
connected) serves as the official test. Id.
ANSI/ASHRAE 37–1988 further
provides that there must be agreement
of the evaporating and condensing
temperatures between the two tests for
a valid test. Id.
DOE further noted in the July 2018
RFI that in a test procedure final rule for
CACs/HPs (82 FR 1426 (Jan. 5, 2017)),
DOE amended its test procedure
requirements for use of the outdoor air
enthalpy method as the secondary test
method for capacity measurement for
CAC/HPs. 83 FR 34499, 34503 (July 20,
2018). DOE’s test procedure for CAC/
HPs had previously included provisions
similar to those in ANSI/ASHRAE 37–
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
1988: The preliminary test was
conducted without the outdoor air-side
test apparatus connected, and the
official test was conducted with the
outdoor air-side test apparatus
connected, with a requirement to
achieve agreement of the evaporating
and condensing temperatures between
the two tests. For CAC/HPs, DOE
determined that testing with the outdoor
air-side test apparatus connected
introduced more variability to the test
results when compared to testing
without the apparatus connected, and
that test variability could be reduced by
shifting to an approach in which the
official test is the one without the
apparatus connected. See 82 FR 1426,
1508–1509 (Jan. 5. 2017). As part of the
July 2018 RFI, DOE requested comment
on whether modifications to the
requirements for using the outdoor air
enthalpy method as the secondary
method for testing SPVUs (similar to
those made for CAC/HPs) would be
appropriate, including that the official
test be conducted without the outdoor
air-side test apparatus connected. 83 FR
34499, 34503 (July 20, 2018).
The CA IOUs commented that the
outdoor air enthalpy method should be
used as the secondary method for
testing SPVUs and agreed that the
official test should be conducted
without the outdoor air-side test
apparatus connected. (CA IOUs, No. 2 at
p. 2) AHRI commented that the AHRI
390 committee was reviewing the
secondary capacity measurement
methods. (AHRI, No. 5 at p. 6) AHRI
stated that after that evaluation is
complete, it would recommend
conducting the official test without the
outdoor air-side test apparatus
connected. Id. Lennox commented that
further evaluation of the secondary
capacity measurements is needed, but it
stated that secondary methods using
refrigerant flow require altering the
system to place the flowmeter into the
refrigerant system and, therefore, could
significantly alter performance.
(Lennox, No. 6 at p. 5)
Since the time of the July 2018 RFI,
AHRI 390–2021 was adopted, and that
test method includes provisions in
Section E5 consistent with those
adopted in the January 2017 CAC/HP TP
final rule. More specifically, AHRI 390–
2021 requires that the official test be the
one in which the outdoor air side test
apparatus is not connected. For the
same reasons DOE presented in the
January 2017 CAC/HP TP final rule and
discussed previously, DOE has
preliminarily determined that the
provisions in AHRI 390–2021 would
better represent field use of SPVUs and
improve test repeatability and
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
reproducibility. For these reasons, DOE
proposes to adopt the capacity
measurements specified in Section E5 of
AHRI 390–2021, into section 1 of the
proposed Appendix G and into section
1 of the proposed Appendix G1. DOE
has tentatively determined that this
proposal would impose only minimal
additional burden to manufacturers and
would not require retesting of units
because the existing test results contain
the data necessary for the capacity
measurements as specified in Section E5
of AHRI 390–2021.
F. Configuration of Unit Under Test
1. Specific Components
An ASRAC working group for certain
commercial heating, ventilating, and air
conditioning (‘‘HVAC’’) equipment
(‘‘Commercial HVAC Working
Group’’),14 which included SPVUs,
submitted a term sheet (‘‘Commercial
HVAC Term Sheet’’) providing the
Commercial HVAC Working Group’s
recommendations. (Docket No. EERE–
2013–BT–NOC–0023, No. 52) 15 The
Commercial HVAC Working Group
recommended that DOE issue guidance
under current regulations on how to test
certain equipment features when
included in a basic model, until such
time as the testing of such features can
be addressed through a test procedure
rulemaking. The Commercial HVAC
Term Sheet listed the subject features
under the heading ‘‘Equipment Features
Requiring Test Procedure Action.’’ (Id at
pp. 3–9) The Commercial HVAC
Working Group also recommended that
DOE issue an enforcement policy stating
that DOE would exclude certain
equipment with specified features from
Departmental testing, but only when the
manufacturer offers for sale at all times
a model that is identical in all other
features; otherwise, the model with that
feature would be eligible for
Departmental testing. These features
were listed under the heading
‘‘Equipment Features Subject to
Enforcement Policy.’’ (Id. at pp. 9–15)
On January 30, 2015, DOE issued a
Commercial HVAC Enforcement Policy
addressing the treatment of specific
features during Departmental testing of
commercial HVAC equipment. (See
www.energy.gov/gc/downloads/
commercial-equipment-testing14 In 2013, ASRAC formed the Commercial HVAC
Working Group to engage in a negotiated
rulemaking effort regarding the certification of
certain commercial HVAC equipment, including
SPVUs. The Commercial HVAC Working Group’s
recommendations are available at
www.regulations.gov under Docket No. EERE–2013–
BT–NOC–0023–0052.
15 Available at www.regulations.gov/document/
EERE-2013-BT-NOC-0023-0052.
PO 00000
Frm 00019
Fmt 4701
Sfmt 4702
2507
enforcement-policies.) The Commercial
HVAC Enforcement Policy stated that—
for the purposes of assessment testing
pursuant to 10 CFR 429.104, verification
testing pursuant to 10 CFR 429.70(c)(5),
and enforcement testing pursuant to 10
CFR 429.110—DOE would not test a
unit with one of the optional features
listed for a specified equipment type if
a manufacturer distributes in commerce
an otherwise identical unit that does not
include one of the optional features. (Id
at p. 1) The objective of the Commercial
HVAC Enforcement Policy is to ensure
that each basic model has a
commercially-available version eligible
for DOE testing, meaning that each basic
model includes either a model without
the optional feature(s) or a model with
the optional features that is eligible for
testing. Id. The features in the
Commercial HVAC Enforcement Policy
for SPVUs (Id. at pp. 3–4) align with the
Commercial HVAC Term Sheet’s list
designated ‘‘Equipment Features Subject
to Enforcement Policy.’’
AHRI 390–2021 includes Appendix F,
‘‘Unit Configuration for Standard
Efficiency Determination—Informative.’’
Section F1.3 of AHRI 390–2021 includes
a list of features that are optional for
testing. Section F1.3 of AHRI 390–2021
further specifies the following general
provisions regarding testing of units
with optional features:
• If an otherwise identical model
(within the basic model) without the
feature is not distributed in commerce,
conduct tests with the feature according
to the individual provisions specified in
Section F1.3 of AHRI 390–2021.
• For each optional feature, Section
F1.3 of AHRI 390–2021 includes
explicit instructions on how to conduct
testing for equipment with the optional
feature present.
The optional features provisions in
AHRI 390–2021 are generally consistent
with DOE’s Commercial HVAC
Enforcement Policy, but the optional
features in Section F1.3 of AHRI 390–
2021 do not entirely align with the list
of features included for SPVUs in the
Commercial HVAC Enforcement Policy.
The list of optional features in section
F1.3 includes five features that are not
present in the Commercial HVAC
Enforcement Policy for SPVUs: (1) Fresh
air dampers; (2) barometric relief
dampers; (3) power correction
capacitors; (4) hail guards, and (5) UV
lights. All five of these features in
Section F1.3 are included for SPVUs in
the ‘‘Equipment Features Requiring Test
Procedure Action’’ section of the
Commercial HVAC Term Sheet.
Therefore, DOE has tentatively
concluded that their inclusion as
E:\FR\FM\14JAP2.SGM
14JAP2
2508
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
lotter on DSK11XQN23PROD with PROPOSALS2
optional features for SPVUs is
appropriate.
DOE notes that the list of features and
provisions in Section F1.3 of Appendix
F of AHRI 390–2021 conflates features
that can be addressed by testing
provisions with features that warrant
enforcement relief (i.e., features that, if
present on a unit under test, could have
a substantive impact on test results and
that cannot be disabled or otherwise
mitigated). This differentiation was
central to the Commercial HVAC Term
Sheet, which as noted previously,
included separate lists for ‘‘Equipment
Features Requiring Test Procedure
Action’’ and ‘‘Equipment Features
Subject to Enforcement Policy,’’ and
remains central to providing clarity in
DOE’s regulations. Further, provisions
more explicit than included in Section
F1.3 of AHRI 390–2021 are warranted to
clarify the differences between how
specific components must be treated
when manufacturers are making
representations as opposed to when
DOE is conducting enforcement testing.
In order to provide clarity between
test procedure provisions (i.e., how to
test a specific unit) and certification and
enforcement provisions (e.g., which
model to test), DOE is not proposing to
adopt Appendix F of AHRI 390–2021
and instead is proposing related
provisions in 10 CFR 429.43, 10 CFR
429.134, and 10 CFR part 431, subpart
F, Appendix G1. Specifically, in
Appendix G1, DOE proposes test
provisions for specific components,
including all of the components listed
in Section F1.3 which there is a
neutralizing test procedure action (i.e.,
test procedure provisions specific to the
component that are not addressed by
general provisions in AHRI 390–2021
that negates the components impact on
performance).16 These provisions would
specify how to test a unit with such a
component—i.e., for a unit with hail
guards, remove hail guards for testing.
These proposed test provisions are
consistent with the provision in Section
F1.3 of AHRI 390–2021, but include
revisions for further clarity and
specificity (e.g., adding clarifying
provisions for how to test units with
modular economizers as opposed to
units shipped with economizers
installed).
16 For
the following components listed in Section
F1.3 of AHRI 390–2021, DOE has tentatively
concluded that there is not a neutralizing test
procedure action specified in Section F1.3 of AHRI
390–2021 for testing a unit with the component
present, and is, therefore, not proposing to include
test procedure actions specific to these components
in Appendix G1: Powered Exhaust/Powered Return
Air Fans and Hot Gas Bypass.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
Consistent with the Commercial
HVAC Term Sheet and the Commercial
HVAC Enforcement Policy, DOE is
proposing provisions that would allow
determination of represented values of a
model equipped with a particular
component to be based on an individual
model distributed in commerce without
the component in specific cases. The
provisions apply to certain components
for which the test provisions for testing
a unit with the component may result in
differences in ratings compared to
testing a unit without the component.17
For these such components, DOE
proposes in 10 CFR 429.43(a)(4) that:
• If a basic model includes only
individual models distributed in
commerce with a specific component, or
does not include any otherwise
identical individual models without the
specific component, the manufacturer
must determine represented values for
the basic model based on performance
of an individual model with the
component present (and consistent with
any relevant proposed test procedure
provisions in Appendix G1).
• If a basic model includes both
individual models distributed in
commerce with a specific component
and otherwise identical individual
models without the specific component,
the manufacturer may determine
represented values for the basic model
based on performance of an individual
model either with the component
present (and consistent with any
relevant proposed test procedure
provisions in Appendix G1) or without
the component present.
DOE notes that in some cases,
individual models may include more
than one of the specified components
(i.e., both an economizer and
dehumidification components) or there
may be individual models within a
basic model that include various
dehumidification components that
result in more or less energy use. In
these cases, the represented values of
performance must be representative of
the lowest efficiency found within the
basic model.
Also consistent with the Commercial
HVAC Term Sheet and the Commercial
HVAC Enforcement Policy, DOE is
proposing provisions in 10 CFR
429.134(s)(1) regarding how DOE would
assess compliance for basic models that
17 DOE has tentatively concluded that for the
following features included in Section F1.3 of AHRI
390–2021, testing a unit with these components in
accordance with the proposed test provisions
would not result in differences in ratings compared
to testing a unit without these components;
therefore, DOE is not proposing to include these
features in 10 CFR 429.43(a)(4): UV lights, Power
Correction Capacitors, Hail Guards, Barometric
Relief Dampers, and Fresh Air Dampers.
PO 00000
Frm 00020
Fmt 4701
Sfmt 4702
include individual models distributed
in commerce with air economizers or
dehumidification components.
Specifically:
• If a basic model includes only
individual models distributed in
commerce with a specific component, or
does not include any otherwise
identical individual models without the
specific component, DOE may assess
compliance for the basic model based
on testing an individual model with the
component present (and consistent with
any relevant proposed test procedure
provisions in Appendix G1).
• If a basic model includes both
individual models distributed in
commerce with a specific component
and otherwise identical individual
models without the specific component,
DOE will assess compliance for the
basic model based on testing of an
otherwise identical model within the
basic model that does not include the
component; except if DOE is not able to
obtain such a model for testing. In such
a case, DOE will assess compliance for
the basic model based on testing of an
individual model with the specific
component present (and consistent with
any relevant proposed test procedure
provisions in Appendix G1).
Were DOE to adopt the provisions in
10 CFR 429.43, 10 CFR 429.134, and 10
CFR part 431, subpart F, appendix G1 as
proposed, DOE would rescind the
Commercial HVAC Enforcement Policy
to the extent it is applicable to SPVUs.
In a separate certification rulemaking,
DOE may consider certification
reporting requirements such that
manufacturers would be required to
certify which otherwise identical
models are used for making
representations of basic models that
include individual models with specific
components.
Issue 7: DOE requests comment on its
proposal regarding specific components
in 10 CFR 429.43, 10 CFR 429.134, and
10 CFR part 431, subpart F, Appendices
G and G1.
G. Represented Values
1. Multiple Refrigerants
DOE recognizes that some commercial
package air conditioning and heating
equipment may be sold with more than
one refrigerant option (e.g., R–410A or
R–407C). Typically, manufacturers
specify a single refrigerant in their
literature for each unique model, but in
its review, DOE has identified at least
one commercial package air
conditioning and heating equipment
manufacturer that provides two
refrigerant options under the same
model number. The refrigerant chosen
E:\FR\FM\14JAP2.SGM
14JAP2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
lotter on DSK11XQN23PROD with PROPOSALS2
by the customer in the field installation
may impact the energy efficiency of a
unit. For this reason, DOE is proposing
representation requirements specific for
models approved for use with multiple
refrigerants. So that the proposals in this
NOPR would only require
manufacturers to update representations
once, DOE proposes to align the
compliance date for these representation
requirements with the proposed metric
change (i.e., these proposals would only
be required when certifying to amended
standards denominated in terms of
IEER, if adopted).
Use of a refrigerant (such as R–407C
as compared to R–410A) that requires
different hardware (i.e., compressors,
heat exchangers, or air moving systems
that are not the same or comparably
performing) would represent a different
basic model, and according to the
current CFR, separate representations of
energy efficiency are required for each
basic model. 10 CFR 429.43(a). On the
other hand, some refrigerants (such as
R–422D and R–427A) would not require
different hardware, and a manufacturer
may consider them to be the same basic
model, per DOE’s current definition for
‘‘basic model at 10 CFR 431.92. In the
latter case of an SPVU with multiple
refrigerant options that do not require
different hardware, DOE proposes that a
manufacturer determine the represented
values (for example, IEER, COP, and
cooling capacity) based on the
refrigerant(s)—among all refrigerants
listed on the unit’s nameplate—that
results in the lowest cooling efficiency.
These represented values would apply
to the basic model with the use of all
refrigerants specified by the
manufacturer.
Issue 8: DOE requests comment on its
proposal regarding representations for
SPVU models approved for use with
multiple refrigerants.
2. Cooling Capacity
For SPVUs, cooling capacity
determines equipment class, which in
turn determines the applicable energy
conservation standard. 10 CFR 431.97.
While cooling capacity is a required
represented value for SPVUs, DOE does
not currently specify provisions for
SPVUs regarding how close the
represented value of cooling capacity
must be to the tested or alternative
energy-efficiency determination method
(‘‘AEDM’’) simulated cooling capacity,
or whether DOE will use measured or
certified cooling capacity to determine
equipment class for enforcement testing.
In contrast, at paragraphs (a)(1)(iv) and
(a)(2)(ii) of 10 CFR 429.43 and
paragraph (g) of 10 CFR 429.134, DOE
specifies such provisions regarding the
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
cooling capacity for air-cooled CUACs.
Again, because energy conservation
standards for SPVUs are dependent on
cooling capacity, inconsistent
approaches to the application of cooling
capacity between basic models could
result in inconsistent determinations of
equipment class and, in turn,
inconsistent applications of the energy
conservation standards.
For these reasons, DOE is proposing
to add to its regulations the following
provisions regarding cooling capacity
for SPVUs: (1) A requirement that the
represented cooling capacity be between
95 percent and 100 percent of the tested
or AEDM-simulated cooling capacity;
and (2) an enforcement provision stating
that DOE would use the mean of
measured cooling capacity values from
testing, rather than the certified cooling
capacity, to determine the applicable
standards.
First, DOE proposes to require in 10
CFR 429.43(a)(3)(v)(B) that the
represented value of cooling capacity
must be between 95 percent and 100
percent of the mean of the cooling
capacity values measured for the units
in the sample (if determined through
testing), or between 95 percent and 100
percent of the cooling capacity output
simulated by an AEDM. This tolerance
would help to ensure that equipment is
capable of performing at the cooling
capacity for which it is represented to
commercial consumers, while also
enabling manufacturers to
conservatively rate the cooling capacity
to allow for minor variations in the
capacity measurements from different
units tested at different laboratories.
Second, DOE is proposing in its
product-specific enforcement provisions
at 10 CFR 429.134(s)(1) that the cooling
capacity of each tested unit of the basic
model will be measured pursuant to the
test requirements of part 431 and that
the mean of the measurement(s) will be
used to determine the applicable
standard with which the model must
comply.
As discussed in this section,
applicable energy conservation
standards for SPVUs are dependent on
the rated cooling capacity. DOE has
tentatively concluded that these
proposals would result in more accurate
ratings of cooling capacity, and ensure
appropriate application of the energy
conservation standards, while still
providing flexibility for manufacturers
to conservatively rate cooling capacity
so that they can be confident the
equipment is capable of delivering the
cooling capacity represented to
commercial consumers.
Issue 9: DOE requests comment on its
proposals related to represented values
PO 00000
Frm 00021
Fmt 4701
Sfmt 4702
2509
and verification testing of cooling
capacity for SPVUs.
H. Test Procedure Costs and Impact
As stated, EPCA requires that the test
procedures for commercial package air
conditioning and heating equipment,
which includes SPVUs, be those
generally accepted industry testing
procedures or rating procedures
developed or recognized by AHRI or by
ASHRAE, as referenced in ASHRAE
Standard 90.1. (42 U.S.C. 6314(a)(4)(A))
Further, if such an industry test
procedure is amended, DOE must
amend its test procedure to be
consistent with the amended industry
test procedure, unless DOE determines,
by rule published in the Federal
Register and supported by clear and
convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B))
In this NOPR, DOE proposes to amend
the existing test procedure for SPVUs
by: (1) Incorporating by reference the
updated version of the applicable
industry test method, AHRI 390–2021,
including the energy efficiency
descriptors; (2) adding definitions for
‘‘single-phase single package vertical air
conditioner with cooling capacity less
than 65,000 Btu/h’’ and ‘‘single-phase
single package vertical heat pump with
cooling capacity less than 65,000 Btu/h’’
to clarify which single-phase equipment
with cooling capacity less than 65,000
Btu/h are properly classified as SPVU
rather than CAC; (3) specifying
provisions for specific components; and
(4) further specifying the requirements
for determination of represented values
for cooling capacity and for models
approved for use with multiple
refrigerants.
DOE has tentatively determined that
these proposed amended test
procedures would be representative of
an average use cycle and would not be
unduly burdensome for manufacturers
to conduct. Based on review of AHRI
390–2021, DOE expects that the
proposed test procedure in Appendix G
for measuring EER and COP would not
increase testing costs per unit compared
to the current DOE test procedure,
which DOE estimates to be $3,100 for
SPVACs and $3,700 for SPVHPs per
unit for third-party lab testing. DOE
estimates that the cost for third-party lab
testing according to the proposed
Appendix G1 for measuring IEER and
COP to be $4,900 for SPVACs and
$5,500 for SPVHPs per unit.
DOE further notes that manufacturers
are not required to perform laboratory
testing on all basic models. In
E:\FR\FM\14JAP2.SGM
14JAP2
2510
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
accordance with 10 CFR 429.70 of
DOE’s regulations, SPVU manufacturers
may elect to use AEDMs. An AEDM is
a computer modeling or mathematical
tool that predicts the performance of
non-tested basic models. These
computer modeling and mathematical
tools, when properly developed, can
provide a means to predict the energy
usage or efficiency characteristics of a
basic model of a given covered product
or equipment and reduce the burden
and cost associated with testing. DOE
estimates the per-manufacturer cost to
develop and validate an AEDM for
SPVU equipment to be $15,800. DOE
estimates an additional cost of
approximately $50 per basic model 18
for determining energy efficiency using
the validated AEDM.
As discussed in section II of this
NOPR, the proposed test procedure
provisions regarding IEER would not be
mandatory unless and until DOE adopts
energy conservation standards that
specify IEER as the regulatory metric
and compliance with such standards is
required. Given that most SPVU
manufacturers are AHRI members and
that DOE is referencing the prevailing
industry test procedure that was
established for use in AHRI’s
certification program (which DOE
presumes will be updated to include
IEER), DOE expects that manufacturers
will already be testing using the IEER
test method. Based on this, DOE has
tentatively determined that the
proposed test procedure amendments
would not be expected to increase the
testing burden on most SPVU
manufacturers. Additionally, DOE has
tentatively determined that the test
procedure amendments, if finalized,
would not require manufacturers to
redesign any of the covered equipment,
would not require changes to how the
equipment is manufactured, and would
not impact the utility of the equipment.
Issue 10: DOE requests comment on
its understanding of the impact of the
test procedure proposals in this NOPR,
specifically DOE’s initial conclusion
that the proposed DOE test procedure
amendments, if finalized, would not
increase testing burden on SPVU
manufacturers, as compared to current
lotter on DSK11XQN23PROD with PROPOSALS2
18 DOE
estimated initial costs to validate an
AEDM assuming 80 hours of general time to
develop an AEDM based on existing simulation
tools and 16 hours to validate two basic models
within that AEDM at the cost of an engineering
technician wage of $50 per hour plus the cost of
third-party physical testing of two units per
validation class (as required in 10 CFR
429.70(c)(2)(iv)). DOE estimated the additional per
basic model cost to determine efficiency using an
AEDM assuming 1 hour per basic model at the cost
of an engineering technician wage of $50 per hour.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
industry practice indicated by AHRI
390–2021.
I. Reserved Appendices for Test
Procedures for Commercial Air
Conditioning and Heating Equipment
DOE proposes to amend its test
procedures for SPVUs and to relocate
those test procedures to new Appendix
G and Appendix G1 to 10 CFR part 431,
subpart F. This proposed reorganization
of the SPVU test procedures would be
consistent with the organization of the
test procedures for other covered
equipment and covered products. DOE
has tentatively concluded that providing
the test procedures for specific
equipment in a designated appendix
would improve the readability of the
test procedure. Further, DOE proposes
to make the provisions currently in 10
CFR 431.96(c) and (e) specific to SPVUs
in 10 CFR part 431, subpart F,
Appendices G and G1, thereby
eliminating the references to test
procedures for other equipment. To
provide for future consideration of a
similar reorganization for other
commercial package air conditioning
and heating equipment test procedures,
DOE is proposing to reserve Appendices
B through F under 10 CFR part 431,
subpart F. The reserved appendices are
presented to facilitate any future
reorganization of the regulations and are
not an indication of any substantive
changes to the respective test
procedures at this time. Any such
reorganization of test procedures for the
equipment identified in the proposed
reserved appendices would be
addressed in separate rulemakings.
J. Compliance Dates
EPCA prescribes that, if DOE amends
its test procedure for covered
commercial package air-conditioning
and heating equipment (including
SPVUs), all representations of energy
efficiency and energy use, including
those made on marketing materials and
product labels, must be made in
accordance with that amended test
procedure, beginning 360 days after
publication of such a test procedure
final rule in the Federal Register. (42
U.S.C. 6314(d)(1))
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
(‘‘OMB’’) has determined that this test
procedure rulemaking does not
constitute ‘‘significant regulatory
actions’’ under section 3(f) of Executive
Order (‘‘E.O.’’) 12866, Regulatory
Planning and Review, 58 FR 51735 (Oct.
PO 00000
Frm 00022
Fmt 4701
Sfmt 4702
4, 1993). Accordingly, this action was
not subject to review under the
Executive order by the Office of
Information and Regulatory Affairs
(‘‘OIRA’’) in OMB.
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis (‘‘IRFA’’) for any rule that by
law must be proposed for public
comment, unless the agency certifies
that the rule, if promulgated, will not
have a significant economic impact on
a substantial number of small entities.
As required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s website: www.energy.gov/gc/
office-general-counsel. DOE reviewed
this proposed rule to amend the test
procedures for SPVUs under the
provisions of the Regulatory Flexibility
Act and the policies and procedures
published on February 19, 2003.
The following sections detail DOE’s
IRFA for this test procedure rulemaking.
1. Description of Reasons Why Action Is
Being Considered
DOE is proposing to amend the
existing DOE test procedures for SPVUs.
DOE must update the Federal test
procedures to be consistent with the
updated industry consensus test
procedure, unless DOE determines by
rule published in the Federal Register
and supported by clear and convincing
evidence, that the industry update
would not be representative of an
average use cycle or would be unduly
burdensome to conduct. (42 U.S.C.
6314(a)(4)(B))
2. Objective of, and Legal Basis for, Rule
EPCA, as amended, requires that the
test procedures for commercial package
air conditioning and heating equipment,
which includes SPVUs, be those
generally accepted industry testing
procedures or rating procedures
developed or recognized by AHRI or by
ASHRAE, as referenced in ASHRAE
Standard 90.1. (42 U.S.C. 6314(a)(4)(A))
Further, if such an industry test
procedure is amended, DOE must
amend its test procedure to be
consistent with the amended industry
test procedure, unless DOE determines,
E:\FR\FM\14JAP2.SGM
14JAP2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
by rule published in the Federal
Register and supported by clear and
convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B))
EPCA also requires that, at least once
every 7 years, DOE must evaluate test
procedures for each type of covered
equipment including SPVUs, to
determine whether amended test
procedures would more accurately or
fully comply with the requirements for
the test procedures to not be unduly
burdensome to conduct and be
reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 614(a)(1)(A))
Once completed, the current
rulemaking will satisfy both of these
legal requirements of EPCA.
lotter on DSK11XQN23PROD with PROPOSALS2
3. Description and Estimate of Small
Entities Regulated
DOE uses the Small Business
Administration (‘‘SBA’’) small business
size standards to determine whether
manufacturers qualify as ‘‘small
businesses,’’ which are listed by the
North American Industry Classification
System (‘‘NAICS’’).19 The SBA
considers a business entity to be small
business if, together with its affiliates, it
employs less than a threshold number of
workers specified in 13 CFR part 121.
SPVU manufacturers, who produce
the equipment covered by this rule, are
classified under NAICS code 333415,
‘‘Air-Conditioning and Warm Air
Heating Equipment and Commercial
and Industrial Refrigeration Equipment
Manufacturing.’’ In 13 CFR 121.201, the
SBA sets a threshold of 1,250 employees
or fewer for an entity to be considered
as a small business for this category.
This employee threshold includes all
employees in a business’s parent
company and any other subsidiaries.
DOE reviewed the test procedures
proposed in this NOPR under the
provisions of the Regulatory Flexibility
Act and the procedures and policies
published on February 19, 2003. The
Department conducted a focused
inquiry into small business
manufacturers of the equipment covered
by this rulemaking. DOE used publicly
available information to identify
potential small businesses that
manufacture SPVUs domestically. DOE
identified manufacturers using DOE’s
Compliance Certification Database
19 Available at: www.sba.gov/document/supporttable-size-standards.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
(‘‘CCD’’),20 the California Energy
Commission’s Modernized Appliance
Efficiency Database System
(‘‘MAEDbS’’),21 and prior rulemakings.
Additionally, DOE used publiclyavailable information and subscriptionbased market research tools (e.g., reports
from Dun & Bradstreet 22). As a result of
this inquiry, DOE identified a total of
eight companies that are manufacturers
or private labelers of SPVUs in the
United States. DOE screened out
companies that do not meet the
definition of a ‘‘small business’’ or are
foreign-owned and operated. Of these
eight SPVU manufacturers or private
labelers, DOE identified three potential
small businesses.
Two of the three small businesses are
original equipment manufacturers
(‘‘OEM’’) of the SPVUs each small
business sells. The third small business
is not an OEM of the SPVUs they sell.
Instead, it rebrands its SPVU models
which are supplied by a different OEM
(i.e., making the small business a private
labeler). Of the two OEM small
businesses, one is a member of AHRI
and the other is not a member of AHRI.
The private labeler small business is not
a member of AHRI.
4. Description and Estimate of
Compliance Requirements
DOE assumed each small business
would have different potential
regulatory costs depending on if they
are an OEM and if they are a member
of AHRI. DOE assumed all AHRI
members, including small businesses,
will be testing their SPVU models in
accordance with AHRI 390–2021, the
industry test procedure DOE is
proposing to reference, and using
AHRI’s certification program, which
DOE presumes will be updated to
include the IEER metric. Therefore, the
proposed test procedure amendments
would not add testing burden to SPVU
manufacturers that are or will be using
the AHRI 390–2021 test procedure for
their SPVU models, including one of the
identified small businesses.
DOE assumed the small business that
is not an OEM of the SPVU models they
sell (i.e., the private labeler) does not
pay for the testing costs for the
rebranded SPVU models they sell
because the test performance of the
20 DOE’s Compliance Certification Database is
available at: www.regulations.doe.gov/ccms (last
accessed September 1, 2021).
21 California Energy Commission’s MAEDbS is
available at cacertappliances.energy.ca.gov/Pages/
ApplianceSearch.aspx (last accessed September 1,
2021).
22 Dun & Bradstreet reports are available at:
app.dnbhoovers.comI (last access September 1,
2021).
PO 00000
Frm 00023
Fmt 4701
Sfmt 4702
2511
rebranded SPVU models is identical to
the SPVU models the OEM sells.
Therefore, DOE does not anticipate that
any non-OEMs, including this small
business, incur any testing burden to
sell rebranded SPVU models.
Lastly, while DOE assumed that all
SPVU manufacturers will be using the
industry test procedure, AHRI 390–
2021, DOE estimated the potential
testing costs for the small business that
is an OEM but is not an AHRI member.
This small business would only incur
additional testing costs if that small
business will not be using the AHRI
390–2021 to test their SPVU models.
This one small business manufactures
six SPVU basic models.
As previously stated in section III.H of
this NOPR, DOE estimated that the cost
for third-party lab testing according to
the proposed appendix G1 for
measuring IEER and COP to be $4,900
for SPVACs and $5,500 for SPVHPs per
unit. If SPVU manufacturers conduct
physical testing to certify a SPVU basic
model, two units are required to be
tested per basic model. However,
manufacturers are not required to
perform laboratory testing on all basic
models, as SPVU manufacturers may
elect to use AEDMs.23 An AEDM is a
computer modeling or mathematical
tool that predicts the performance of
non-tested basic models. These
computer modeling and mathematical
tools, when properly developed, can
provide a means to predict the energy
usage or efficiency characteristics of a
basic model of a given covered product
or equipment and reduce the burden
and cost associated with testing.
When developing cost estimates, DOE
considered the cost to develop an
AEDM, the costs to validate the AEDM
through physical testing, and the cost
per model to determine ratings using the
AEDM. DOE estimated the cost to
develop and validate an AEDM for
SPVUs to be approximately $15,800,
which includes physical testing of two
models per validation class.24
Additionally, DOE estimated a cost of
approximately $50 per basic model for
determining energy efficiency using the
validated AEDM. In the case of the
single small, non-AHRI member, the
estimated cost to rate the remaining four
basic models with the AEDM would be
23 In
accordance with 10 CFR 429.70.
(AEDM development and validation
costs) + $5,500 (per-unit physical testing costs) ×
(units required for physical testing per validation
class) = $15,800. AEDM development ad validation
costs are based on 96 hours of development and
testing using an engineering technician wage of $50
per hour. This estimate utilizes the more costly
SPVHP testing cost of $5,500 per unit.
24 $4,800
E:\FR\FM\14JAP2.SGM
14JAP2
2512
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
$200.25 Based on these estimates, the
small SPVU manufacturer that is an
OEM and not a member of AHRI would
incur $16,000 to test and rate all six of
its SPVU models.
Market research tools report that
company’s annual revenue to be
approximately $1.3 million. The cost to
re-rate all model would be
approximately 1.2 percent of annual
revenue for that small manufacturer.26
Issue 11: DOE requests comment on
the number of small businesses DOE
identified. DOE also requests comment
on the potential cost estimates for each
small business identified, compared to
current industry practice, as indicated
by AHRI 390–2021.
5. Duplication, Overlap, and Conflict
With Other Rules and Regulations
DOE is not aware of any rules or
regulations that duplicate, overlap, or
conflict with the rule being considered.
lotter on DSK11XQN23PROD with PROPOSALS2
6. Significant Alternatives to the Rule
DOE proposes to reduce burden on
manufacturers, including small
businesses, by allowing AEDMs in lieu
of physically testing all basic models.
The use of AEDMs is less costly than
physical testing for SPVUs. Without
AEDMs, the cost for the small, nonAHRI-member to rate all basic models
would increase to $66,000.27
Additionally, DOE considered
alternative test methods and
modifications to the AHRI 390–2021 test
procedure for SPVUs. However, DOE
has tentatively determined that there are
no better alternatives than the existing
industry test procedures, in terms of
both meeting the agency’s objectives
and reducing burden on manufacturers.
Therefore, DOE is proposing to amend
the existing DOE test procedure for
SPVUs through incorporation by
reference of AHRI 390–2021.
Additional compliance flexibilities
may be available through other means.
Manufacturers subject to DOE’s energy
efficiency standards may apply to DOE’s
Office of Hearings and Appeals for
exception relief under certain
circumstances. Manufacturers should
refer to 10 CFR part 1003 for additional
details.
C. Review Under the Paperwork
Reduction Act of 1995
Manufacturers of SPVUs must certify
to DOE that their products comply with
25 $50 (per-unit rating cost) × 4 (remaining units)
= $200.
26 $16,000 (costs) ÷ $1,300,000 (annual revenue)
= 1.2% of annual revenue.
27 $5,500 (per-unit test cost) × 2 (units tested per
model) × 6 (number of SPVU models) = $66,000.
This estimate utilizes the more costly SPVHP
testing cost of $5,500 per unit.
VerDate Sep<11>2014
19:15 Jan 13, 2022
Jkt 256001
any applicable energy conservation
standards. To certify compliance,
manufacturers must first obtain test data
for their products according to the DOE
test procedures, including any
amendments adopted for those test
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including
SPVUs. (See generally 10 CFR part 429.)
The collection-of-information
requirement for the certification and
recordkeeping is subject to review and
approval by OMB under the Paperwork
Reduction Act (‘‘PRA’’). This
requirement has been approved by OMB
under OMB control number 1910–1400.
Public reporting burden for the
certification is estimated to average 35
hours per response, including the time
for reviewing instructions, searching
existing data sources, gathering and
maintaining the data needed, and
completing and reviewing the collection
of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
D. Review Under the National
Environmental Policy Act of 1969
DOE is analyzing this proposed
regulation in accordance with the
National Environmental Policy Act of
1969 (‘‘NEPA’’) and DOE’s NEPA
implementing regulations (10 CFR part
1021). DOE’s regulations include a
categorical exclusion for rulemakings
interpreting or amending an existing
rule or regulation that does not change
the environmental effect of the rule or
regulation being amended. 10 CFR part
1021, subpart D, appendix A5. DOE
anticipates that this rulemaking
qualifies for categorical exclusion A5
because it is an interpretive rulemaking
that does not change the environmental
effects of the rule and otherwise meets
the requirements for application of a
categorical exclusion. See 10 CFR
1021.410. DOE will complete its NEPA
review before issuing the final rule.
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 10, 1999), imposes
certain requirements for agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive order requires agencies to
examine the constitutional and statutory
PO 00000
Frm 00024
Fmt 4701
Sfmt 4702
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive order also requires agencies to
have an accountable process to ensure
meaningful and timely input by State
and local officials in the development of
regulatory policies that have federalism
implications. On March 14, 2000, DOE
published a statement of policy
describing the intergovernmental
consultation process it will follow in the
development of such regulations. 65 FR
13735. DOE has examined this proposed
rule and has determined that it would
not have a substantial direct effect on
the States, on the relationship between
the national government and the States,
or on the distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
proposed rule. States can petition DOE
for exemption from such preemption to
the extent, and based on criteria, set
forth in EPCA. (42 U.S.C. 6297(d)) No
further action is required by Executive
Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (Feb. 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity; (2) write
regulations to minimize litigation; (3)
provide a clear legal standard for
affected conduct rather than a general
standard, and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that Executive agencies make
every reasonable effort to ensure that the
regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly
specifies any effect on existing Federal
law or regulation; (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction; (4) specifies the
retroactive effect, if any; (5) adequately
defines key terms, and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met or it is
unreasonable to meet one or more of
them. DOE has completed the required
E:\FR\FM\14JAP2.SGM
14JAP2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
review and determined that, to the
extent permitted by law, the proposed
rule meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (‘‘UMRA’’) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
proposed regulatory action likely to
result in a rule that may cause the
expenditure by State, local, and Tribal
governments, in the aggregate, or by the
private sector of $100 million or more
in any one year (adjusted annually for
inflation), section 202 of UMRA requires
a Federal agency to publish a written
statement that estimates the resulting
costs, benefits, and other effects on the
national economy. (2 U.S.C. 1532(a), (b))
The UMRA also requires a Federal
agency to develop an effective process
to permit timely input by elected
officers of State, local, and Tribal
governments on a proposed ‘‘significant
intergovernmental mandate,’’ and
requires an agency plan for giving notice
and opportunity for timely input to
potentially affected small governments
before establishing any requirements
that might significantly or uniquely
affect small governments. On March 18,
1997, DOE published a statement of
policy on its process for
intergovernmental consultation under
UMRA. 62 FR 12820; also available at
www.energy.gov/gc/office-generalcounsel. DOE examined this proposed
rule according to UMRA and its
statement of policy and determined that
the rule contains neither an
intergovernmental mandate, nor a
mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
lotter on DSK11XQN23PROD with PROPOSALS2
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
proposed rule would not have any
impact on the autonomy or integrity of
the family as an institution.
Accordingly, DOE has concluded that it
is not necessary to prepare a Family
Policymaking Assessment.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights,’’ 53 FR 8859
(March 18, 1988), that this proposed
regulation would not result in any
takings that might require compensation
under the Fifth Amendment to the U.S.
Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (Feb. 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (Oct. 7, 2002). Pursuant to OMB
Memorandum M–19–15, Improving
Implementation of the Information
Quality Act (April 24, 2019), DOE
published updated guidelines which are
available at www.energy.gov/sites/prod/
files/2019/12/f70/DOE%20Final
%20Updated%20IQA%
20Guidelines%20Dec%202019.pdf.
DOE has reviewed this proposed rule
under the OMB and DOE guidelines and
has concluded that it is consistent with
applicable policies in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
proposed significant energy action. A
‘‘significant energy action’’ is defined as
any action by an agency that
promulgated or is expected to lead to
promulgation of a final rule, and that:
(1) Is a significant regulatory action
under Executive Order 12866, or any
successor order; and (2) is likely to have
a significant adverse effect on the
supply, distribution, or use of energy; or
(3) is designated by the Administrator of
OIRA as a significant energy action. For
any proposed significant energy action,
the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use
should the proposal be implemented,
and of reasonable alternatives to the
action and their expected benefits on
energy supply, distribution, and use.
The proposed regulatory action to
amend the test procedure for measuring
PO 00000
Frm 00025
Fmt 4701
Sfmt 4702
2513
the energy efficiency of SPVUs is not a
significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; ‘‘FEAA’’) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (‘‘FTC’’)
concerning the impact of the
commercial or industry standards on
competition.
The proposed amendments to the
Federal test procedure for SPVUs are
primarily in response to modifications
to the applicable industry consensus
test standards (i.e., AHRI 390–2021 and
ANSI/ASHRAE 37–2009). DOE has
evaluated these standards and is unable
to conclude whether they fully comply
with the requirements of section 32(b) of
the FEAA (i.e., whether it was
developed in a manner that fully
provides for public participation,
comment, and review).DOE will consult
with both the Attorney General and the
Chairman of the FTC concerning the
impact of these test procedures on
competition, prior to prescribing a final
rule.
M. Description of Materials
Incorporated by Reference
In this NOPR, DOE proposes to
incorporate by reference the test
standard published by AHRI, titled
‘‘Performance Rating of Single Package
Vertical Air-Conditioners and Heat
Pumps,’’ AHRI Standard 390–2021.
Specifically, the Federal test procedure
proposed in this NOPR would adopt
sections 3 (except 3.1, 3.2, 3.5, 3.12, and
3.15), 5 (except section 5.8.5), 6 (except
6.1.1, 6.2, 6.3, 6.4, and 6.5), Appendices
A, D, and E of the industry test method.
AHRI 390–2021 is an industry-accepted
E:\FR\FM\14JAP2.SGM
14JAP2
2514
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
test procedure for measuring the
performance of SPVUs. AHRI Standard
390–2021 is available online at
www.ahrinet.org/search-standards.aspx.
In this NOPR, DOE also proposes to
incorporate by reference the test
standard published by ASHRAE, titled
‘‘Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment,’’ ANSI/ASHRAE Standard
37–2009. ANSI/ASHRAE Standard 37–
2009 is an industry-accepted test
procedure for measuring the
performance of electrically driven
unitary air-conditioning and heat pump
equipment. ANSI/ASHRAE Standard
37–2009 is available on ANSI’s website
at https://webstore.ansi.org/
RecordDetail.aspx?sku=ANSI%
2FASHRAE+Standard+37-2009.
In this NOPR, DOE also proposes to
incorporate by reference the test
standard published by ASHRAE, titled
‘‘Standard Methods For Laboratory
Airflow Measurement,’’ ANSI/ASHRAE
Standard 41.2–1987 (RA 92). ANSI/
ASHRAE Standard 41.2–1987 (RA 92) is
an industry-accepted test procedure for
consistent measurement procedures for
use in the preparation of other ASHRAE
standards. Procedures described are
used in testing air-moving, air-handling,
and air-distribution equipment and
components. ANSI/ASHRAE Standard
41.2–1987 (RA 92) is available on
ANSI’s website at https://webstore.
ansi.org/Standards/ASHRAE/
ANSIASHRAE411987RA92.
The following standards, which
appear in the regulatory text, were
previously approved for IBR and no
changes are proposed: AHRI 210/240–
2008, AHRI 340/360–2007, AHRI 1230–
2010, ASHRAE 127–2007, and ISO
Standard 13256–1 (1998).
V. Public Participation
lotter on DSK11XQN23PROD with PROPOSALS2
A. Participation in the Webinar
The time and date of the webinar are
listed in the DATES section at the
beginning of this document. Webinar
registration information, participant
instructions, and information about the
capabilities available to webinar
participants will be published on DOE’s
website: www.energy.gov/eere/
buildings/public-meetings-andcomment-deadlines. Participants are
responsible for ensuring their systems
are compatible with the webinar
software.
B. Procedure for Submitting Prepared
General Statements for Distribution
Any person who has an interest in the
topics addressed in this notice, or who
is representative of a group or class of
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
persons that has an interest in these
issues, may request an opportunity to
make an oral presentation at the
webinar/public meeting. Such persons
may submit requests to speak via email
to the Appliance and Equipment
Standards Program at:
ApplianceStandardsQuestions@
ee.doe.gov. Persons who wish to speak
should include with their request a
computer file in WordPerfect, Microsoft
Word, PDF, or text (ASCII) file format
that briefly describes the nature of their
interest in this rulemaking and the
topics they wish to discuss. Such
persons should also provide a daytime
telephone number where they can be
reached.
DOE requests persons selected to
make an oral presentation to submit an
advance copy of their statements at least
two weeks before the webinar/public
meeting. At its discretion, DOE may
permit persons who cannot supply an
advance copy of their statement to
participate, if those persons have made
advance alternative arrangements with
the Building Technologies Office. As
necessary, requests to give an oral
presentation should ask for such
alternative arrangements.
C. Conduct of the Webinar
DOE will designate a DOE official to
preside at the webinar/public meeting
and may also use a professional
facilitator to aid discussion. The
meeting will not be a judicial or
evidentiary-type public hearing, but
DOE will conduct it in accordance with
section 336 of EPCA (42 U.S.C. 6306). A
court reporter will be present to record
the proceedings and prepare a
transcript. DOE reserves the right to
schedule the order of presentations and
to establish the procedures governing
the conduct of the webinar/public
meeting. There shall not be discussion
of proprietary information, costs or
prices, market share, or other
commercial matters regulated by U.S.
anti-trust laws. After the webinar/public
meeting and until the end of the
comment period, interested parties may
submit further comments on the
proceedings and any aspect of the
rulemaking.
The webinar will be conducted in an
informal, conference style. DOE will
present summaries of comments
received before the webinar/public
meeting, allow time for prepared general
statements by participants, and
encourage all interested parties to share
their views on issues affecting this
rulemaking. Each participant will be
allowed to make a general statement
(within time limits determined by DOE),
before the discussion of specific topics.
PO 00000
Frm 00026
Fmt 4701
Sfmt 4702
DOE will permit, as time permits, other
participants to comment briefly on any
general statements.
At the end of all prepared statements
on a topic, DOE will permit participants
to clarify their statements briefly and
comment on statements made by others.
Participants should be prepared to
answer questions posed by DOE and by
other participants concerning these
issues. DOE representatives may also
ask questions of participants concerning
other matters relevant to this
rulemaking. The official conducting the
webinar/public meeting will accept
additional comments or questions from
those attending, as time permits. The
presiding official will announce any
further procedural rules or modification
of the above procedures that may be
needed for the proper conduct of the
webinar/public meeting.
A transcript of the webinar/public
meeting will be included in the docket,
which can be viewed as described in the
Docket section at the beginning of this
document. In addition, any person may
buy a copy of the transcript from the
transcribing reporter.
D. Submission of Comments
DOE will accept comments, data, and
information regarding this proposed
rule no later than the date provided in
the DATES section at the beginning of
this proposed rule. Interested parties
may submit comments using any of the
methods described in the ADDRESSES
section at the beginning of this
document.
DOE has historically provided a 75day comment period for test procedure
NOPRs pursuant to the North American
Free Trade Agreement, U.S.-CanadaMexico (‘‘NAFTA’’), Dec. 17, 1992, 32
I.L.M. 289 (1993); the North American
Free Trade Agreement Implementation
Act, Public Law 103–182, 107 Stat. 2057
(1993) (codified as amended at 10
U.S.C.A. 2576) (1993) (‘‘NAFTA
Implementation Act’’); and Executive
Order 12889, ‘‘Implementation of the
North American Free Trade
Agreement,’’ 58 FR 69681 (Dec. 30,
1993). However, on July 1, 2020, the
Agreement between the United States of
America, the United Mexican States,
and the United Canadian States
(‘‘USMCA’’), Nov. 30, 2018, 134 Stat. 11
(i.e., the successor to NAFTA), went into
effect, and Congress’s action in
replacing NAFTA through the USMCA
Implementation Act, 19 U.S.C. 4501 et
seq. (2020), implies the repeal of E.O.
12889 and its 75-day comment period
requirement for technical regulations.
Thus, the controlling laws are EPCA and
the USMCA Implementation Act.
Consistent with EPCA’s public comment
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
period requirements for consumer
products, the USMCA only requires a
minimum comment period of 60 days.
Consequently, DOE now provides a 60day public comment period for test
procedure NOPRs.
Submitting comments via
www.regulations.gov. The
www.regulations.gov web page will
require you to provide your name and
contact information. Your contact
information will be viewable to DOE
Building Technologies staff only. Your
contact information will not be publicly
viewable except for your first and last
names, organization name (if any), and
submitter representative name (if any).
If your comment is not processed
properly because of technical
difficulties, DOE will use this
information to contact you. If DOE
cannot read your comment due to
technical difficulties and cannot contact
you for clarification, DOE may not be
able to consider your comment.
However, your contact information
will be publicly viewable if you include
it in the comment or in any documents
attached to your comment. Any
information that you do not want to be
publicly viewable should not be
included in your comment, nor in any
document attached to your comment.
Persons viewing comments will see only
first and last names, organization
names, correspondence containing
comments, and any documents
submitted with the comments.
Do not submit to www.regulations.gov
information for which disclosure is
restricted by statute, such as trade
secrets and commercial or financial
information (hereinafter referred to as
Confidential Business Information
(‘‘CBI’’)). Comments submitted through
www.regulations.gov cannot be claimed
as CBI. Comments received through the
website will waive any CBI claims for
the information submitted. For
information on submitting CBI, see the
Confidential Business Information
section.
DOE processes submissions made
through www.regulations.gov before
posting. Normally, comments will be
posted within a few days of being
submitted. However, if large volumes of
comments are being processed
simultaneously, your comment may not
be viewable for up to several weeks.
Please keep the comment tracking
number that www.regulations.gov
provides after you have successfully
uploaded your comment.
Submitting comments via email.
Comments and documents submitted
via email also will be posted to
www.regulations.gov. If you do not want
your personal contact information to be
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
publicly viewable, do not include it in
your comment or any accompanying
documents. Instead, provide your
contact information in a cover letter.
Include your first and last names, email
address, telephone number, and
optional mailing address. The cover
letter will not be publicly viewable as
long as it does not include any
comments.
Include contact information each time
you submit comments, data, documents,
and other information to DOE. No
telefacsimiles (faxes) will be accepted.
Comments, data, and other
information submitted to DOE
electronically should be provided in
PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file
format. Provide documents that are not
secured, written in English, and free of
any defects or viruses. Documents
should not contain special characters or
any form of encryption, and, if possible,
they should carry the electronic
signature of the author.
Campaign form letters. Please submit
campaign form letters by the originating
organization in batches of between 50 to
500 form letters per PDF or as one form
letter with a list of supporters’ names
compiled into one or more PDFs. This
reduces comment processing and
posting time.
Confidential Business Information.
Pursuant to 10 CFR 1004.11, any person
submitting information that he or she
believes to be confidential and exempt
by law from public disclosure should
submit via email two well-marked
copies: One copy of the document
marked ‘‘confidential’’ including all the
information believed to be confidential,
and one copy of the document marked
‘‘non-confidential’’ with the information
believed to be confidential deleted. DOE
will make its own determination about
the confidential status of the
information and treat it according to its
determination.
It is DOE’s policy that all comments
may be included in the public docket,
without change and as received,
including any personal information
provided in the comments (except
information deemed to be exempt from
public disclosure).
E. Issues on Which DOE Seeks Comment
Although DOE welcomes comments
on any aspect of this proposal, DOE is
particularly interested in receiving
comments and views of interested
parties concerning the following issues:
Issue 1: DOE requests comment on its
proposal to define ‘‘single-phase single
package vertical air conditioner with
cooling capacity less than 65,000 Btu/h’’
and ‘‘single-phase single package
PO 00000
Frm 00027
Fmt 4701
Sfmt 4702
2515
vertical heat pump with cooling
capacity less than 65,000 Btu/h’’ as
subsets of the broader SPVAC and
SPVHP equipment category. DOE
requests feedback on the proposed
characteristics that would distinguish
this equipment as SPVUs (i.e.,
‘‘weatherized’’ or capable of utilizing a
maximum of 400 CFM of outdoor air).
Additionally, DOE requests comment on
the proposed method to validate that a
unit is capable of providing 400 CFM of
outdoor air.
Issue 2: DOE requests comment on its
proposal to adopt the test methods
specified in AHRI 390–2021 for
calculating IEER for SPVUs.
Issue 3: DOE requests comment and
data on ratings under the current EER
metric specified in 10 CFR 431.97 and
ASHRAE 90.1–2019 based on ANSI/
AHRI 390–2003 as compared to ratings
using the IEER metric under AHRI 390–
2021.
Issue 4: DOE requests comment on its
proposal to clarify that COP
representations using the ‘‘Low
Temperature Operation, Heating’’
conditions in Table 3 of AHRI 390–2021
are optional.
Issue 5: DOE welcomes data and
information on ESP conditions
experienced in field operation of ducted
SPVUs.
Issue 6: DOE requests comment and
data on the number of SPVHP
installations by building type and
geographical region and the annual
heating and cooling loads for such
buildings. DOE also requests data on the
frequency of operation of defrost cycles
and representative low ambient
conditions for those buildings and
installations.
Issue 7: DOE requests comment on its
proposal regarding specific components
in 10 CFR 429.43, 10 CFR 429.134, and
10 CFR part 431, subpart F, appendices
G and G1.
Issue 8: DOE requests comment on its
proposal regarding representations for
SPVU models approved for use with
multiple refrigerants.
Issue 9: DOE requests comment on its
proposals related to represented values
and verification testing of cooling
capacity for SPVUs.
Issue 10: DOE requests comment on
its understanding of the impact of the
test procedure proposals in this NOPR,
specifically DOE’s initial conclusion
that the proposed DOE test procedure
amendments, if finalized, would not
increase testing burden on SPVU
manufacturers, as compared to current
industry practice indicated by AHRI
390–2021.
Issue 11: DOE requests comment on
the number of small businesses DOE
E:\FR\FM\14JAP2.SGM
14JAP2
2516
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
identified. DOE also requests comment
on the potential cost estimates for each
small business identified, compared to
current industry practice, as indicated
by AHRI 390–2021.
DOE also seeks comment on any other
matter concerning the proposed test
procedures for SPVUs not already
addressed by the specific areas
identified in this document. DOE
particularly seeks information that
would ensure that the test procedure
measures energy efficiency during a
representative average use cycle, as well
as information that would help DOE
create a procedure that is not unduly
burdensome to conduct.
For the reasons stated in the
preamble, DOE is proposing to amend
parts 429 and 431 of Chapter II of Title
10, Code of Federal Regulations as set
forth below:
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
■
VI. Approval of the Office of the
Secretary
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
The Secretary of Energy has approved
publication of this proposed rule.
■
■
■
List of Subjects
10 CFR Part 429
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Reporting
and recordkeeping requirements, Small
businesses.
10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Incorporation by reference, Reporting
and recordkeeping requirements.
Signing Authority
lotter on DSK11XQN23PROD with PROPOSALS2
Signed in Washington, DC, on December
30, 2021.
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
This document of the Department of
Energy was signed on December 28,
2021, by Kelly J. Speakes-Backman,
Principal Deputy Assistant Secretary for
Energy Efficiency and Renewable
Energy, pursuant to delegated authority
from the Secretary of Energy. That
document with the original signature
and date is maintained by DOE. For
administrative purposes only, and in
compliance with requirements of the
Office of the Federal Register, the
undersigned DOE Federal Register
Liaison Officer has been authorized to
sign and submit the document in
electronic format for publication, as an
official document of the Department of
Energy. This administrative process in
no way alters the legal effect of this
document upon publication in the
Federal Register.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
2. Amend § 429.4 by:
a. Revising paragraph (a);
b. Redesignating paragraph (c)(2) as
paragraph (c)(3);
■ c. Adding new paragraph (c)(2);
■ d. Redesignating paragraphs (d), (e),
and (f) as paragraphs (e), (f), and (g); and
■ e. Adding new paragraph (d).
The revisions and additions read as
follows.
§ 429.4 Materials incorporated by
reference.
(a) Certain material is incorporated by
reference into this part with the
approval of the Director of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. To enforce
any edition other than that specified in
this section, DOE must publish a
document in the Federal Register and
the material must be available to the
public. All approved material is
available for inspection at the U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Program, Sixth
Floor, 950 L’Enfant Plaza SW,
Washington, DC 20024, (202) 586–9127,
Buildings@ee.doe.gov, https://
www.energy.gov/eere/buildings/
building-technologies-office, and may be
obtained from the other sources in this
section. It is also available for
inspection at the National Archives and
Records Administration (NARA). For
information on the availability of this
material at NARA, email: fr.inspection@
nara.gov, or go to: www.archives.gov/
federal-register/cfr/ibr-locations.html.
*
*
*
*
*
(c) * * *
(2) AHRI Standard 390–2021, (‘‘AHRI
390–2021’’), 2021 Standard for
Performance Rating of Single Package
Vertical Air-conditioners and Heat
Pumps, IBR approved for § 429.134.
*
*
*
*
*
PO 00000
Frm 00028
Fmt 4701
Sfmt 4702
(d) ASHRAE. The American Society of
Heating, Refrigerating and AirConditioning Engineers. 180
Technology Parkway NW, Peachtree
Corners, GA 30092, (404) 636–8400,
https://www.ashrae.org.
(1) ANSI/ASHRAE 37–2009,
‘‘Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment’’, ASHRAE approved June
24, 2009. IBR approved for § 429.134.
(2) ANSI/ASHRAE 41.2–1987 (RA 92),
‘‘Standard Methods For Laboratory
Airflow Measurement’’, ASHRAE
approved October 1, 1987. IBR approved
for § 429.134.
*
*
*
*
*
■ 3. Amend § 429.43 by adding
paragraphs (a)(3) and (4) to read as
follows:
§ 429.43 Commercial heating, ventilating,
air conditioning (HVAC) equipment.
(a) * * *
(3) Product-specific provisions for
determination of represented values.
(i)–(vi) [Reserved]
(vii) Single Package Vertical Units.
When certifying to standards in terms of
IEER, the following provisions apply.
(A) If a basic model is distributed in
commerce and approved for use with
multiple refrigerants, a manufacturer
must determine all represented values
for that basic model (for example, IEER,
COP and cooling capacity) based on the
refrigerant that results in the lowest
cooling efficiency. A refrigerant is
considered approved for use if it is
listed on the nameplate of the outdoor
unit. Per the definition of basic model
in 10 CFR 431.92 of this chapter, use of
a refrigerant that requires different
hardware (i.e., compressors, heat
exchangers, or air moving systems that
are not the same or comparably
performing), would represent a different
basic model, and separate
representations would be required for
each basic model.
(B) The represented value of cooling
capacity must be between 95 percent
and 100 percent of the mean of the
capacities measured for the units in the
sample selected as described in
paragraph (a)(1)(ii) of this section, or
between 95 percent and 100 percent of
the net sensible cooling capacity output
simulated by the AEDM as described in
paragraph (a)(2) of this section.
(C) Represented values must be based
on performance (either through testing
or by applying an AEDM) of individual
models with components and features
that are selected in accordance with
section 3 of appendix G1 to subpart F
of part 431 of this chapter.
E:\FR\FM\14JAP2.SGM
14JAP2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
(4) Determination of represented
values for individual models with
specific components for SPVUs.
(i) If a manufacturer distributes in
commerce individual models with one
of the components listed in the
following table, determination of
represented values is dependent on the
selected grouping of individual models
into a basic model, as indicated in
paragraphs (a)(4)(ii) through (a)(4)(v) of
2517
this section. For the purposes of this
paragraph, ‘‘otherwise identical’’ means
differing only in the presence of specific
components listed in table 1 to this
paragraph (a)(4)(i).
TABLE 1—TO PARAGRAPH (a)(4)(i)
Component
Description
Desiccant Dehumidification Components ...........
An assembly that reduces the moisture content of the supply air through moisture transfer with
solid or liquid desiccants.
An automatic system that enables a cooling system to supply outdoor air to reduce or eliminate the need for mechanical cooling during mid or cold weather.
An assembly that preconditions outdoor air entering the equipment through direct or indirect
thermal and/or moisture exchange with the exhaust air, which is defined as the building air
being exhausted to the outside from the equipment.
Coils used to provide supplemental heating.
A heat exchanger located downstream of the indoor coil that heats the Supply Air during cooling operation using high pressure refrigerant in order to increase the ratio of moisture removal to Cooling Capacity provided by the equipment.
A damper assembly including means to open and close the damper mounted at the supply or
return duct opening of the equipment.
A powered exhaust fan is a fan that transfers directly to the outside a portion of the building
air that is returning to the unit, rather than allowing it to recirculate to the indoor coil and
back to the building. A powered return fan is a fan that draws building air into the equipment.
An assembly of structures through which the supply air passes before leaving the equipment
or through which the return air from the building passes immediately after entering the
equipment for which the sound insertion loss is at least 6 dB for the 125 Hz octave band
frequency range.
A method to adjust the cooling delivered by the equipment in which some portion of the hot
high-pressure refrigerant from the discharge of the compressor(s) is diverted from its normal
flow to the outdoor coil and is instead allowed to enter the indoor coil to modulate the capacity of a refrigeration circuit or to prevent evaporator coil freezing.
Air Economizers ..................................................
Ventilation Energy Recovery System (VERS) ....
Steam/Hydronic Heat Coils ................................
Hot Gas Reheat ..................................................
Fire/Smoke/Isolation Dampers ...........................
Powered Exhaust/Powered Return Air Fans ......
Sound Traps/Sound Attenuators ........................
lotter on DSK11XQN23PROD with PROPOSALS2
Hot Gas Bypass ..................................................
(ii) If a basic model includes only
individual models distributed in
commerce without a specific component
listed in paragraph (a)(4)(i) of this
section, the manufacturer must
determine represented values for the
basic model based on performance of an
individual model distributed in
commerce without the component.
(iii) If a basic model includes only
individual models distributed in
commerce with a specific component
listed in paragraph (a)(4)(i) of this
section, the manufacturer must
determine represented values for the
basic model based on performance of an
individual model with the component
present (and consistent with any
component-specific test provisions
specified in section 3 of appendix G1 to
subpart F of part 431 of this chapter).
(iv) If a basic model includes both
individual models distributed in
commerce with a specific component
listed in paragraph (4)(i) of this section
and individual models distributed in
commerce without that specific
component, and none of the individual
models distributed in commerce
without the specific component are
otherwise identical to any individual
model distributed in commerce with the
specific component, the manufacturer
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
must consider the performance of
individual models with the component
present when determining represented
values for the basic model (and
consistent with any component-specific
test provisions specified in section 3 of
appendix G1 to subpart F of part 431 of
this chapter).
(v) If a basic model includes both
individual models distributed in
commerce with a specific component
listed in paragraph (a)(4)(i) of this
section and individual models
distributed in commerce without that
specific component, and at least one of
the individual models distributed in
commerce without the specific
component is otherwise identical to any
given individual model distributed in
commerce with the specific component,
the manufacturer may determine
represented values for the basic model
either:
(A) Based on performance of an
individual model distributed in
commerce without the specific
component, or
(B) Based on performance of an
individual model with the specific
component present (and consistent with
any component-specific test provisions
specified in section 3 of appendix G1 to
subpart F of part 431 of this chapter).
PO 00000
Frm 00029
Fmt 4701
Sfmt 4702
(vi) In any of the cases specified in
paragraphs (a)(4)(ii) through (a)(4)(v) of
this section, the represented values for
a basic model must be determined
through either testing (paragraph (a)(1)
of this section) or an AEDM
(paragraph(a)(2) of this section).
*
*
*
*
*
■ 4. Amend § 429.134 by adding
paragraph (s) to read as follows:
§ 429.134 Product-specific enforcement
provisions.
*
*
*
*
*
(s) Single package vertical air
conditioners and heat pumps. The
following provisions apply for
assessment and enforcement testing of
models subject to standards in terms of
IEER.
(1) Verification of cooling capacity.
The cooling capacity of each tested unit
of the basic model will be measured
pursuant to the test requirements of
appendix G1 to subpart F of part 431 of
this chapter. The mean of the
measurement(s) will be used to
determine the applicable standards for
purposes of compliance.
(2) Specific Components. For basic
models that include individual models
distributed in commerce with any of the
specific components listed at
E:\FR\FM\14JAP2.SGM
14JAP2
lotter on DSK11XQN23PROD with PROPOSALS2
2518
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
§ 429.43(a)(4)(i), the following
provisions apply. For the purposes of
this paragraph, ‘‘otherwise identical’’
means differing only in the presence of
specific components listed at
§ 429.43(a)(4)(i).
(i) If the basic model includes only
individual models distributed in
commerce with a specific component, or
does not include any otherwise
identical individual models without the
specific component, DOE may assess
compliance for the basic model based
on testing of an individual model with
the component present (and consistent
with any component-specific test
provisions specified in section 3 of
appendix G1 to subpart F of part 431 of
this chapter).
(ii) If the basic model includes both
individual models distributed in
commerce with a specific component
and otherwise identical individual
models without the specific component,
DOE will assess compliance for the
basic model based on testing an
otherwise identical model within the
basic model that does not include the
component, unless DOE is not able to
obtain an individual model for testing
that does not include the component. In
such a situation, DOE will assess
compliance for the basic model based
on testing of an individual model with
the specific component present (and
consistent with any component-specific
test provisions specified in section 3 of
appendix G1 to subpart F of part 431 of
this chapter).
(3) Validation of outdoor ventilation
airflow rate. The outdoor ventilation
airflow rate in cubic feet per minute
(‘‘CFM’’) of the basic model will be
measured in accordance with ASHRAE
41.2–1987 (incorporated by reference,
see § 429.4) and Section 6.4 of ASHRAE
37–2009. All references to the inlet shall
be determined to mean the outdoor air
inlet.
(i) The outdoor ventilation airflow
rate validation shall be conducted at the
conditions specified in Table 3 of AHRI
390–2021 (incorporated by reference,
see § 429.4), Full Load Standard Rating
Capacity Test, Cooling, except for the
following:
(A) The outdoor ventilation airflow
rate shall be determined at 0 in. H2O
external static pressure with a tolerance
of ¥0.00/+0.05 in. H2O.
(B) Reserved.
(ii) When validating the outdoor
ventilation airflow rate, the outdoor air
inlet pressure shall be 0.00 in. H2O,
with a tolerance of ¥0.00/+0.05 in. H2O
when measured against the room
ambient pressure.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
5. The authority citation for part 431
continues to read as follows:
■
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
6. Amend § 431.92 by:
a. Revising the definitions of ‘‘Single
package vertical air conditioner’’ and
‘‘Single package vertical heat pump.’’
■ b. Adding the definitions of ‘‘Singlephase single package vertical air
conditioner with cooling capacity less
than 65,000 Btu/h’’ and ‘‘Single-phase
single package vertical heat pump with
cooling capacity less than 65,000 Btu/h’’
in alphabetical order; and
The additions and revisions read as
follows:
■
■
§ 431.92 Definitions concerning
commercial air conditioners and heat
pumps.
*
*
*
*
*
Single package vertical air
conditioner means:
(1) Air-cooled commercial package air
conditioning and heating equipment
that—
(i) Is factory-assembled as a single
package that—
(A) Has major components that are
arranged vertically;
(B) Is an encased combination of
cooling and optional heating
components; and
(C) Is intended for exterior mounting
on, adjacent interior to, or through an
outside wall;
(ii) Is powered by a single-or 3-phase
current;
(iii) May contain 1 or more separate
indoor grilles, outdoor louvers, various
ventilation options, indoor free air
discharges, ductwork, well plenum, or
sleeves; and
(iv) Has heating components that may
include electrical resistance, steam, hot
water, or gas, but may not include
reverse-cycle refrigeration as a heating
means; and
(2) Includes single-phase single
package vertical air conditioner with
cooling capacity less than 65,000 Btu/h,
as defined in this section.
Single package vertical heat pump
means:
(1) A single package vertical air
conditioner that—
(i) Uses reverse-cycle refrigeration as
its primary heat source; and—
(ii) May include secondary
supplemental heating by means of
electrical resistance, steam, hot water, or
gas;
(2) Includes single-phase single
package vertical heat pump with cooling
PO 00000
Frm 00030
Fmt 4701
Sfmt 4702
capacity less than 65,000 Btu/h, as
defined in this section.
Single-phase single package vertical
air conditioner with cooling capacity
less than 65,000 Btu/h means air-cooled
commercial package air conditioning
and heating equipment that meets the
criteria in paragraphs (1)(i) through (iv)
of the definition of a single package
vertical air conditioner; that is singlephase; has a cooling capacity less than
65,000 Btu/h, and that:
(1) Is weatherized, determined by a
model being denoted for ‘‘Outdoor Use’’
or marked as ‘‘Suitable for Outdoor
Use’’ on the equipment nameplate; or
(2) Is non-weatherized and is a model
that has optional ventilation air
provisions available. When such
ventilation air provisions are present on
the unit, the unit must be capable of
drawing in and conditioning outdoor air
for delivery to the conditioned space at
a rate of at least 400 cubic feet per
minute, as determined in accordance
with § 429.134(s)(3), while the
equipment is operating with the same
drive kit and motor settings used to
determine the certified efficiency rating
of the equipment (as required for
submittal to DOE by § 429.43(b)(4)(xi)).
Single-phase single package vertical
heat pump with cooling capacity less
than 65,000 Btu/h means air-cooled
commercial package air conditioning
and heating equipment that meets the
criteria in paragraphs (1)(i) through (ii)
of the definition of a single package
vertical heat pump; that is single-phase;
has a cooling capacity less than 65,000
Btu/h, and that:
(1) Is weatherized, determined by a
model being denoted for ‘‘Outdoor Use’’
or marked as ‘‘Suitable for Outdoor
Use’’ on the equipment nameplate; or
(2) Is non-weatherized and is a model
that has optional ventilation air
provisions available. When such
ventilation air provisions are present on
the unit, the unit must be capable of
drawing in and conditioning outdoor air
for delivery to the conditioned space at
a rate of at least 400 cubic feet per
minute, as determined in accordance
with § 429.134(s)(3), while the
equipment is operating with the same
drive kit and motor settings used to
determine the certified efficiency rating
of the equipment (as required for
submittal to DOE by § 429.43(b)(4)(xii)).
*
*
*
*
*
■ 7. Amend § 431.95 by revising
paragraphs (a), (b)(5) and (c)(2) to read
as follows:
§ 431.95 Materials incorporated by
reference.
(a) Certain material is incorporated by
reference into this part with the
E:\FR\FM\14JAP2.SGM
14JAP2
2519
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
approval of the Director of the Federal
Register in accordance with 5 U.S.C.
552(a) and 1 CFR part 51. To enforce
any edition other than that specified in
this section, DOE must publish a
document in the Federal Register and
the material must be available to the
public. All approved material is
available for inspection at the U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Program, Sixth
Floor, 950 L’Enfant Plaza SW,
Washington, DC 20024, (202) 586–9127,
Buildings@ee.doe.gov, https://
www.energy.gov/eere/buildings/
building-technologies-office, and may be
obtained from the other sources in this
section. It is also available for
inspection at the National Archives and
Records Administration (NARA). For
information on the availability of this
material at NARA, email: fr.inspection@
nara.gov, or go to: www.archives.gov/
federal-register/cfr/ibr-locations.html.
(b) * * *
(5) AHRI Standard 390–2021, ‘‘2021
Standard for Performance Rating of
Single Package Vertical AirConditioners and Heat Pumps,’’ dated
2021, (AHRI 390–2021), IBR approved
for appendices G and G1 to this subpart.
*
*
*
*
*
(c) * * *
(2) ANSI/ASHRAE Standard 37–2009,
(‘‘ANSI/ASHRAE 37–2009’’), ‘‘Methods
of Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat
Pump Equipment,’’ ASHRAE approved
June 24, 2009, IBR approved for § 431.96
and appendices A, G, and G1 to this
subpart.
*
*
*
*
*
■ 8. Amend § 431.96 by revising
paragraph (b)(1), table 1 to § 431.96, and
paragraph (c) to read as follows:
§ 431.96 Uniform test method for the
measurement of energy efficiency of
commercial air conditioners and heat
pumps.
*
*
*
*
*
(b) Testing and calculations. (1)
Determine the energy efficiency and
capacity of each category of covered
equipment by conducting the test
procedure(s) listed in Table 1 of this
paragraph (b) along with any additional
testing provisions set forth in
paragraphs (c) through (g) of this section
and appendices A through G1 to this
subpart, that apply to the energy
efficiency descriptor for that equipment,
category, and cooling capacity. The
omitted sections of the test procedures
listed in Table 1 must not be used. For
equipment with multiple appendices
listed in Table 1, consult the notes at the
beginning of those appendices to
determine the applicable appendix to
use for testing.
(2) * * *
TABLE 1 TO PARAGRAPH (b)(2)—TEST PROCEDURES FOR COMMERCIAL AIR CONDITIONERS AND HEAT PUMPS
Category
Cooling capacity
Energy efficiency
descriptor
Small Commercial Package Air-Conditioning
and Heating Equipment.
Air-Cooled, 3-Phase, AC
and HP.
<65,000 Btu/h .................
SEER and HSPF ............
AHRI 210/240–2008
(omit section 6.5).
Paragraphs (c) and (e).
Air-Cooled AC and HP ...
≥65,000 Btu/h and
<135,000 Btu/h.
<65,000 Btu/h .................
EER, IEER, and COP ....
Appendix A to this subpart.
AHRI 210/240–2008
(omit section 6.5).
AHRI 340/360–2007
(omit section 6.3).
ISO Standard 13256–1
(1998).
Appendix A to this subpart.
AHRI 340/360–2007
(omit section 6.3).
Appendix A to this subpart.
AHRI 340/360–2007
(omit section 6.3).
Paragraph (g) of this section.
None.
Water-Cooled and Evaporatively-Cooled AC.
Water-Source HP ...........
Large Commercial Package Air-Conditioning
and Heating Equipment.
Very Large Commercial
Package Air-Conditioning and Heating
Equipment.
Packaged Terminal Air
Conditioners and Heat
Pumps.
Computer Room Air Conditioners.
Variable Refrigerant Flow
Multi-split Systems.
lotter on DSK11XQN23PROD with PROPOSALS2
Variable Refrigerant Flow
Multi-split Systems, Aircooled.
Variable Refrigerant Flow
Multi-split Systems,
Water-source.
Single Package Vertical
Air Conditioners and
Single Package Vertical
Heat Pumps.
≥65,000 Btu/h and
<135,000 Btu/h.
<135,000 Btu/h ...............
EER ................................
EER ................................
EER and COP ................
Water-Cooled and Evaporatively-Cooled AC.
AC and HP .....................
≥135,000 Btu/h and
<240,000 Btu/h.
≥135,000 Btu/h and
<240,000 Btu/h.
≥240,000 Btu/h and
<760,000 Btu/h.
≥240,000 Btu/h and
<760,000 Btu/h.
<760,000 Btu/h ...............
EER and COP ................
AC ...................................
<65,000 Btu/h .................
SCOP .............................
SCOP .............................
AC ...................................
≥65,000 Btu/h and
<760,000 Btu/h.
<65,000 Btu/h (3-phase)
HP ...................................
≥65,000 Btu/h and
<760,000 Btu/h.
<65,000 Btu/h (3-phase)
HP ...................................
≥65,000 Btu/h and
<760,000 Btu/h.
<760,000 Btu/h ...............
EER and COP ................
AC and HP .....................
<760,000 Btu/h ...............
EER and COP ................
Air-Cooled AC and HP ...
Water-Cooled and Evaporatively-Cooled AC.
Air-Cooled AC and HP ...
EER, IEER and COP .....
EER ................................
EER, IEER and COP .....
EER ................................
SEER ..............................
EER ................................
SEER and HSPF ............
EER and COP ................
EER, IEER, and COP ....
Use tests, conditions,
and procedures 1 in
Additional test procedure
provisions as indicated in
the listed paragraphs of
this section
Equipment type
ASHRAE 127–2007 (omit
section 5.11).
ASHRAE 127–2007 (omit
section 5.11).
AHRI 1230–2010 (omit
sections 5.1.2 and 6.6).
AHRI 1230–2010 (omit
sections 5.1.2 and 6.6).
AHRI 1230–2010 (omit
sections 5.1.2 and 6.6).
Paragraphs (c) and (e).
Paragraphs (c) and (e).
Paragraph (e).
None.
Paragraphs (c) and (e).
None.
Paragraphs (c) and (e).
Paragraphs (c), (e), and
(g).
Paragraphs (c) and (e).
Paragraphs (c) and (e).
Paragraphs (c), (d), (e),
and (f).
Paragraphs (c), (d), (e),
and (f).
Paragraphs (c), (d), (e),
and (f).
AHRI 1230–2010 (omit
Paragraphs (c), (d), (e),
sections 5.1.2 and 6.6).
and (f).
AHRI 1230–2010 (omit
Paragraphs (c), (d), (e),
sections 5.1.2 and 6.6).
and (f).
Appendix G to this subpart 2.
Appendix G1 to this subpart 2.
1 Incorporated
None.
None.
by reference; see § 431.95.
2 For equipment with multiple appendices listed in Table 1, consult the notes at the beginning of those appendices to determine the applicable appendix to use for
testing.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
PO 00000
Frm 00031
Fmt 4701
Sfmt 4702
E:\FR\FM\14JAP2.SGM
14JAP2
2520
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
(c) Optional break-in period for tests
conducted using AHRI 210/240–2008,
AHRI 1230–2010, and ASHRAE 127–
2007. Manufacturers may optionally
specify a ‘‘break-in’’ period, not to
exceed 20 hours, to operate the
equipment under test prior to
conducting the test method specified by
AHRI 210/240–2008, AHRI 1230–2010,
or ASHRAE 127–2007 (incorporated by
reference; see § 431.95). A manufacturer
who elects to use an optional
compressor break-in period in its
certification testing should record this
information (including the duration) in
the test data underlying the certified
ratings that is required to be maintained
under 10 CFR 429.71.
*
*
*
*
*
Appendix B to Subpart F of Part 431
[Reserved]
9. Add and reserve appendix B to
subpart F of part 431.
■
Appendix C to Subpart F of Part 431
[Reserved]
10. Add and reserve appendix C to
subpart F of part 431.
■
Appendix D to Subpart F of Part 431
[Reserved]
11. Add and reserve appendix D to
subpart F of part 431.
■
Appendix E to Subpart F of Part 431
[Reserved]
12. Add and reserve appendix E to
subpart F of part 431.
■
Appendix F to Subpart F of Part 431
[Reserved]
13. Add and reserve appendix F to
subpart F of part 431.
■ 14. Add appendix G to subpart F of
part 431 to read as follows:
■
lotter on DSK11XQN23PROD with PROPOSALS2
Appendix G to Subpart F of Part 431—
Uniform Test Method for Measuring the
Energy Consumption of Single Package
Vertical Air Conditioners and Single
Package Vertical Heat Pumps
Note: Prior to [DATE 360 DAYS AFTER
DATE OF PUBLICATION OF THE FINAL
RULE IN THE FEDERAL REGISTER]
manufacturers must use the results of testing
under either this appendix or § 431.96 as it
appeared in the 10 CFR parts 200–499
edition revised as of January 1, 2021, to
determine compliance with the relevant
standard from § 431.97 as that standard
appeared in the January 1, 2021 edition of 10
CFR parts 200–499. On or after [date 360
days after date of publication of the final rule
in the Federal Register] manufacturers must
use the results of testing generated under this
appendix to demonstrate compliance with
the relevant standard from § 431.97 as that
standard appeared in the January 1, 2021
edition of 10 CFR parts 200–499.
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
Beginning [DATE 360 DAYS AFTER DATE
OF PUBLICATION OF THE FINAL RULE IN
THE FEDERAL REGISTER], if manufacturers
make voluntary representations with respect
to the integrated energy efficiency ratio
(IEER) of single packaged vertical air
conditioners and single package vertical heat
pumps, such representations must be based
on testing conducted in accordance with
appendix G1 of this subpart.
For any amended standards for single
packaged vertical air conditioners and single
package vertical heat pumps based on IEER
published after January 1, 2021,
manufacturers must use the results of testing
under appendix G1 to determine compliance.
Representations related to energy
consumption must be made in accordance
with the appropriate appendix that applies
(i.e., this appendix or appendix G1) when
determining compliance with the relevant
standard. Manufacturers may also use
appendix G1 to certify compliance with any
amended standards prior to the applicable
compliance date for those standards.
0. DOE incorporated by reference the entire
standard for AHRI 390–2021 and ASHRAE
37–2009 in § 431.95. However, only
enumerated provisions of AHRI 390–2021
and ASHRAE 37–2009 apply to this
appendix, as follows:
0.1 AHRI 390–2021:
(a) Section 3—Definitions (omitting sections
3.1, 3.2, 3.5, 3.12, and 3.15)
(b) Section 5—Test Requirements (omitting
section 5.8.5)
(c) Section 6—Rating Requirements (omitting
sections 6.1.1 and 6.2 through 6.5)
(d) Appendix A. ‘‘References—Normative’’
(e) Appendix D. ‘‘Indoor and Outdoor Air
Condition Measurement—Normative’’
(f) Appendix E. ‘‘Method of Testing Single
Package Vertical Units—Normative’’
0.2 All provisions of ANSI/ASHRAE 37–
2009 apply except for the following
provisions:
(a) Section 1—Purpose
(b) Section 2—Scope
(c) Section 4—Classifications
1. General.
Determine cooling capacity (Btu/h) and
energy efficiency ratio (EER) for all single
package vertical air conditioners and heat
pumps and coefficient of performance (COP)
for all single package vertical heat pumps, in
accordance with the specified sections of
AHRI 390–2021 ‘‘Performance Rating of
Single Package Vertical Air-conditioners And
Heat Pumps’’ and the specified sections of
ANSI/ASHRAE 37–2009 ‘‘Methods of Testing
for Rating Electronically Driven Unitary AirConditioning and Heat-Pump Equipment’’.
Only enumerated provisions of AHRI 390–
2021 and ANSI/ASHRAE 37–2009 are
applicable, as set forth in section 0 of this
appendix.
In addition, the instructions in section 2 of
this appendix apply to determining EER and
COP. In cases where there is a conflict, the
language of this appendix takes highest
precedence, followed by AHRI 390–2021,
followed by ANSI/ASHRAE 37–2009. Any
subsequent amendment to a referenced
document by a standard-setting organization
will not affect the test procedure in this
PO 00000
Frm 00032
Fmt 4701
Sfmt 4702
appendix, unless and until the test procedure
is amended by DOE. Material is incorporated
as it exists on the date of the approval, and
a notice of any change in the incorporation
will be published in the Federal Register.
2. Test Conditions. The ‘‘Standard Rating
Full Load Capacity Test, Cooling’’ conditions
for cooling mode tests and ‘‘Standard Rating
Full Load Capacity Test, Heating’’ conditions
for heat pump heating mode tests specified
in Table 3 of AHRI 390–2021 shall be used.
2.1 Optional Representations.
Representations of COP for single package
vertical heat pumps made using the ‘‘Low
Temperature Operation, Heating’’ condition
specified in Table 3 of AHRI 390–2021 are
optional and are determined according to the
applicable provisions in section 1 of this
appendix.
15. Add appendix G1 to subpart F of
part 431 to read as follows:
■
Appendix G1 to Subpart F of Part 431—
Uniform Test Method for Measuring the
Energy Consumption of Single Package
Vertical Air Conditioners and Single
Package Vertical Heat Pumps
Note: Beginning [DATE 360 DAYS AFTER
DATE OF PUBLICATION OF THE FINAL
RULE IN THE FEDERAL REGISTER], if
manufacturers make voluntary
representations with respect to the integrated
energy efficiency ratio (IEER) of single
packaged vertical air conditioners and single
package vertical heat pumps, such
representations must be based on testing
conducted in accordance with this appendix.
Manufacturers must use the results of
testing under this appendix to determine
compliance with any amended standards for
single packaged vertical air conditioners and
single package vertical heat pumps based on
IEER provided in § 431.97 that are published
after January 1, 2021. Representations related
to energy consumption must be made in
accordance with the appropriate appendix
that applies (i.e., appendix G or this
appendix) when determining compliance
with the relevant standard. Manufacturers
may also use this appendix to certify
compliance with any amended standards
prior to the applicable compliance date for
those standards.
0. DOE incorporated by reference the entire
standard for AHRI 390–2021 and ASHRAE
37–2009 in § 431.95. However, only
enumerated provisions of AHRI 390–2021
and ASHRAE 37–2009 apply to this
appendix, as follows:
0.1 AHRI 390–2021:
(a) Section 3—Definitions (omitting sections
3.1, 3.2, 3.5, 3.12, and 3.15)
(b) Section 5—Test Requirements (omitting
section 5.8.5)
(c) Section 6—Rating Requirements (omitting
sections 6.1.1 and 6.3 through 6.5)
(d) Appendix A. ‘‘References—Normative’’
(e) Appendix D. ‘‘Indoor and Outdoor Air
Condition Measurement—Normative’’
(f) Appendix E. ‘‘Method of Testing Single
Package Vertical Units—Normative’’
0.2 All provisions of ANSI/ASHRAE 37–
2009 apply except for the following
provisions:
E:\FR\FM\14JAP2.SGM
14JAP2
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
(a) Section 1—Purpose
(b) Section 2—Scope
(c) Section 4—Classifications
1. General.
Determine cooling capacity (Btu/h) and
integrated energy efficiency ratio (IEER) for
all single package vertical air conditioners
and heat pumps and coefficient of
performance (COP) for all single package
vertical heat pumps, in accordance with the
specified sections of AHRI 390–2021
‘‘Performance Rating of Single Package
Vertical Air-conditioners And Heat Pumps’’
and the specified sections of ANSI/ASHRAE
37–2009 ‘‘Methods of Testing for Rating
Electronically Driven Unitary AirConditioning and Heat-Pump Equipment’’.
Only enumerated provisions of AHRI 390–
2021 and ANSI/ASHRAE 37–2009 are
applicable, as set forth in section 0 of this
appendix.
In addition, the instructions in section 2 of
this appendix apply to determining IEER and
COP. In cases where there is a conflict, the
language of this appendix takes highest
precedence, followed by AHRI 390–2021,
followed by ANSI/ASHRAE 37–2009. Any
subsequent amendment to a referenced
document by a standard-setting organization
will not affect the test procedure in this
appendix, unless and until the test procedure
is amended by DOE. Material is incorporated
as it exists on the date of the approval, and
a notice of any change in the incorporation
will be published in the Federal Register.
2. Test Conditions. The ‘‘Part-Load
Standard Rating Conditions’’ conditions for
2521
cooling mode tests and ‘‘Standard Rating Full
Load Capacity Test, Heating’’ conditions for
heat pump heating mode tests specified in
Table 3 of AHRI 390–2021 shall be used.
2.1 Optional Representations.
Representations of COP for single package
vertical heat pumps made using the ‘‘Low
Temperature Operation, Heating’’ condition
specified in Table 3 of AHRI 390–2021 are
optional and are determined according to the
applicable provisions in section 1 of this
appendix.
3. Set-Up and Test Provisions for Specific
Components. When testing an SPVU that
includes any of the features listed in Table
3.1 of this appendix, test in accordance with
the set-up and test provisions specified in
Table 3.1.
TABLE 3.1—TEST PROVISIONS FOR SPECIFIC COMPONENTS
Component
Desiccant Dehumidification
Components.
Air Economizers ...................
Test provisions
An assembly that reduces the moisture content of the
supply air through moisture transfer with solid or liquid desiccants.
An automatic system that enables a cooling system to
supply outdoor air to reduce or eliminate the need for
mechanical cooling during mid or cold weather.
Disable desiccant dehumidification components for testing.
Fresh Air Dampers ...............
An assembly with dampers and means to set the
damper position in a closed and one open position to
allow air to be drawn into the equipment when the indoor fan is operating.
Hail Guards ..........................
A grille or similar structure mounted to the outside of
the unit covering the outdoor coil to protect the coil
from hail, flying debris and damage from large objects.
A capacitor that increases the power factor measured
at the line connection to the equipment.
An assembly that preconditions outdoor air entering the
equipment through direct or indirect thermal and/or
moisture exchange with the exhaust air, which is defined as the building air being exhausted to the outside from the equipment.
Power Correction Capacitors
Ventilation Energy Recovery
System (VERS).
Barometric Relief Dampers ..
UV Lights .............................
Steam/Hydronic Heat Coils ..
Hot Gas Reheat ...................
lotter on DSK11XQN23PROD with PROPOSALS2
Description
Sound Traps/Sound Attenuators.
VerDate Sep<11>2014
18:24 Jan 13, 2022
An assembly with dampers and means to automatically
set the damper position in a closed position and one
or more open positions to allow venting directly to the
outside a portion of the building air that is returning
to the unit, rather than allowing it to recirculate to the
indoor coil and back to the building.
A lighting fixture and lamp mounted so that it shines
light on the indoor coil, that emits ultraviolet light to
inhibit growth of organisms on the indoor coil surfaces, the condensate drip pan, and/other locations
within the equipment.
Coils used to provide supplemental heating ...................
A heat exchanger located downstream of the indoor
coil that heats the Supply Air during cooling operation
using high pressure refrigerant in order to increase
the ratio of moisture removal to Cooling Capacity
provided by the equipment.
An assembly of structures through which the Supply Air
passes before leaving the equipment or through
which the return air from the building passes immediately after entering the equipment for which the
sound insertion loss is at least 6 dB for the 125 Hz
octave band frequency range.
Jkt 256001
PO 00000
Frm 00033
Fmt 4701
Sfmt 4702
For any air economizer that is factory-installed, place
the economizer in the 100% return position and close
and seal the outside air dampers for testing. For any
modular air economizer shipped with the unit but not
factory-installed, do not install the economizer for
testing.
For any fresh air dampers that are factory-installed,
close and seal the dampers for testing. For any modular fresh air dampers shipped with the unit but not
factory-installed, do not install the dampers for testing.
Remove hail guards for testing.
Remove power correction capacitors for testing.
For any VERS that is factory-installed, place the VERS
in the 100% return position and close and seal the
outside air dampers and exhaust air dampers for
testing, and do not energize any VERS subcomponents (e.g., energy recovery wheel motors). For any
VERS module shipped with the unit but not factoryinstalled, do not install the VERS for testing.
For any barometric relief dampers that are factory-installed, close and seal the dampers for testing. For
any modular barometric relief dampers shipped with
the unit but not factory-installed, do not install the
dampers for testing.
Turn off UV lights for testing.
Test with steam/hydronic heat coils in place but providing no heat.
De-activate refrigerant reheat coils for testing so as to
provide the minimum (none if possible) reheat
achievable by the system controls.
Removable sound traps/sound attenuators shall be removed for testing. Otherwise, test with sound traps/
attenuators in place.
E:\FR\FM\14JAP2.SGM
14JAP2
2522
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 / Proposed Rules
TABLE 3.1—TEST PROVISIONS FOR SPECIFIC COMPONENTS—Continued
Component
Fire/Smoke/Isolation
Dampers.
Description
Test provisions
A damper assembly including means to open and close
the damper mounted at the supply or return duct
opening of the equipment.
For any fire/smoke/isolation dampers that are factoryinstalled, set the dampers in the fully open position
for testing. For any modular fire/smoke/isolation
dampers shipped with the unit but not factory-installed, do not install the dampers for testing.
[FR Doc. 2021–28553 Filed 1–13–22; 8:45 am]
lotter on DSK11XQN23PROD with PROPOSALS2
BILLING CODE 6450–01–P
VerDate Sep<11>2014
18:24 Jan 13, 2022
Jkt 256001
PO 00000
Frm 00034
Fmt 4701
Sfmt 9990
E:\FR\FM\14JAP2.SGM
14JAP2
Agencies
[Federal Register Volume 87, Number 10 (Friday, January 14, 2022)]
[Proposed Rules]
[Pages 2490-2522]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2021-28553]
[[Page 2489]]
Vol. 87
Friday,
No. 10
January 14, 2022
Part II
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Single Package Vertical
Air Conditioners and Single Package Vertical Heat Pumps; Proposed Rule
Federal Register / Vol. 87, No. 10 / Friday, January 14, 2022 /
Proposed Rules
[[Page 2490]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE-2017-BT-TP-0020]
RIN 1904-AD94
Energy Conservation Program: Test Procedure for Single Package
Vertical Air Conditioners and Single Package Vertical Heat Pumps
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking and request for comment.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (``DOE'') proposes to amend its
test procedures for single package vertical air conditioners and single
package vertical heat pumps. DOE is proposing to incorporate by
reference the most recent version of the relevant industry test
standard, AHRI 390-2021, and to amend certain provisions for
representations for the subject equipment. DOE is also proposing
definitions for ``single-phase single package vertical air conditioners
with cooling capacity less than 65,000 Btu/h'' and for ``single-phase
single package vertical heat pumps with cooling capacity less than
65,000 Btu/h.'' The proposed definitions would explicitly define this
equipment as subsets of the broader single package vertical air
conditioner and single package vertical heat pump equipment categories,
and further distinguish such equipment from certain residential central
air conditioners and heat pumps. DOE seeks comment from interested
parties on this proposal.
DATES:
Comments: DOE will accept comments, data, and information regarding
this proposal no later than March 15, 2022. See section V, ``Public
Participation,'' for details.
Meeting: DOE will hold a webinar on Wednesday, February 9th, 2022,
from 1:00 p.m. to 3:00 p.m. See section V, ``Public Participation,''
for webinar registration information, participant instructions, and
information about the capabilities available to webinar participants.
ADDRESSES: Interested persons are encouraged to submit comments using
the Federal eRulemaking Portal at www.regulations.gov. Follow the
instructions for submitting comments. Alternatively, interested persons
may submit comments, identified by docket number EERE-2017-BT-TP-0020,
by any of the following methods:
1. Federal eRulemaking Portal: www.regulations.gov. Follow the
instructions for submitting comments.
2. Email: To [email protected]. Include docket
number EERE-2017-BT-TP-0020 in the subject line of the message.
No telefacsimiles (``faxes'') will be accepted. For detailed
instructions on submitting comments and additional information on this
process, see section V, ``Public Participation,'' of this document.
Although DOE has routinely accepted public comment submissions
through a variety of mechanisms, including postal mail and hand
delivery/courier, the Department has found it necessary to make
temporary modifications to the comment submission process in light of
the ongoing COVID-19 pandemic. DOE is currently suspending receipt of
public comments via postal mail and hand delivery/courier. If a
commenter finds that this change poses an undue hardship, please
contact Appliance Standards Program staff at (202) 586-1445 to discuss
the need for alternative arrangements. Once the COVID-19 pandemic
health emergency is resolved, DOE anticipates resuming all of its
regular options for public comment submission, including postal mail
and hand delivery/courier.
Docket: The docket, which includes Federal Register notices, public
meeting/webinar attendee lists and transcripts, comments, and other
supporting documents/materials, is available for review at
www.regulations.gov. All documents in the docket are listed in the
www.regulations.gov index. However, some documents listed in the index,
such as those containing information that is exempt from public
disclosure, may not be publicly available.
The docket web page can be found at www.regulations.gov/docket?D=EERE-2017-BT-TP-0020. The docket web page contains
instructions on how to access all documents, including public comments,
in the docket. See section V, ``Public Participation,'' for information
on how to submit comments through www.regulations.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Catherine Rivest, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, EE-5B,
1000 Independence Avenue SW, Washington, DC 20585-0121. Telephone:
(202) 586-7335. Email: [email protected].
Mr. Eric Stas, U.S. Department of Energy, Office of the General
Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC 20585-0121.
Telephone: (202) 586-5827. Email: [email protected].
For further information on how to submit a comment, review other
public comments and the docket, or participate in a public meeting/
webinar, contact the Appliance and Equipment Standards Program staff at
(202) 287-1445 or by email: [email protected].
SUPPLEMENTARY INFORMATION: DOE proposes to maintain a previously
approved incorporation by reference and incorporate by reference the
following industry standards into parts 429 and 431:
AHRI Standard 390-2021 ``Performance Rating of Single Package
Vertical Air-Conditioners and Heat Pumps,'' dated 2021.
ANSI/ASHRAE Standard 37-2009, ``Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment,''
ASHRAE approved June 24, 2009.
ANSI/ASHRAE Standard 41.2-1987 (RA 92), ``Standard Methods For
Laboratory Airflow Measurement,'' ASHRAE approved October 1, 1987.
Copies of AHRI Standard 390-2021 can be obtained from the Air-
conditioning, Heating, and Refrigeration Institute (AHRI), 2311 Wilson
Blvd., Suite 400, Arlington, VA 22201, (703) 524-8800, or by going to
www.ahrinet.org/search-standards.aspx.
Copies of ANSI/ASHRAE Standard 37-2009 and ANSI/ASHRAE Standard
41.2-1987 (RA 92) can be obtained from the American Society of Heating,
Refrigerating, and Air-Conditioning Engineers (ASHRAE), 180 Technology
Parkway NW, Peachtree Corners, GA 30092, (404) 636-8400, or by going to
https://www.ashrae.org/.
See section IV.M for a further discussion of these standards.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Notice of Proposed Rulemaking
III. Discussion
A. Scope of Applicability
B. Updates to Industry Standards
1. Updates to AHRI 390
2. ASHRAE 37
C. Proposed Organization of the SPVU Test Procedure
D. Energy Efficiency Descriptor
1. Efficiency Metrics
2. Test Conditions Used for Efficiency Metrics
3. Fan Energy Use
E. Test Method
[[Page 2491]]
1. Unit Set-Up
2. Air Temperature Measurements
3. Defrost Energy Use
4. Outdoor Air Enthalpy Method
F. Configuration of Unit Under Test
1. Specific Components
G. Represented Values
1. Multiple Refrigerants
2. Cooling Capacity
H. Test Procedure Costs and Impact
I. Reserved Appendices for Test Procedures for Commercial Air
Conditioning and Heating Equipment
J. Compliance Dates
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Description of Materials Incorporated by Reference
V. Public Participation
A. Participation in the Webinar
B. Procedure for Submitting Prepared General Statements for
Distribution
C. Conduct of the Webinar
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
VI. Approval of the Office of the Secretary
I. Authority and Background
Single package vertical air conditioners (``SPVACs'') and single
package vertical heat pumps (``SPVHPs''), collectively referred to as
single package vertical units (``SPVUs''), are a category of small,
large, and very large commercial package air conditioning and heating
equipment. Accordingly, SPVUs are included in the list of ``covered
equipment'' for which DOE is authorized to establish and amend energy
conservation standards and test procedures. (42 U.S.C. 6311(1)(B)-(D))
DOE's energy conservation standards and test procedures for SPVUs are
currently prescribed at title 10 of the Code of Federal Regulations
(``CFR'') section 97 to subpart F of part 431 and section 96 to subpart
F of part 431, respectively. The following sections discuss DOE's
authority to establish test procedures for SPVUs and relevant
background information regarding DOE's consideration of test procedures
for SPVUs.
A. Authority
The Energy Policy and Conservation Act, as amended (``EPCA''),\1\
authorizes DOE to regulate the energy efficiency of a number of
consumer products and certain industrial equipment. (42 U.S.C. 6291-
6317) Title III, Part C \2\ of EPCA, added by Public Law 95-619, Title
IV, section 441(a), established the Energy Conservation Program for
Certain Industrial Equipment, which sets forth a variety of provisions
designed to improve energy efficiency. This equipment includes small,
large, and very large commercial package air conditioning and heating
equipment, including SPVUs. (42 U.S.C. 6311(1)(B)-(D))
---------------------------------------------------------------------------
\1\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020).
\2\ For editorial reasons, upon codification in the U.S. Code,
Part C was redesignated Part A-1.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) Testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. Relevant
provisions of EPCA specifically include definitions (42 U.S.C. 6291;42
U.S.C. 6311), test procedures (42 U.S.C. 6293; 42 U.S.C. 6314),
labeling provisions (42 U.S.C. 6294; 42 U.S.C. 6315), energy
conservation standards (42 U.S.C. 6295; 42 U.S.C. 6313), and the
authority to require information and reports from manufacturers. (42
U.S.C. 6296; 42 U.S.C. 6316)
The Federal testing requirements consist of test procedures that
manufacturers of covered equipment must use as the basis for: (1)
Certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted pursuant to EPCA (42 U.S.C.
6316(b); 42 U.S.C. 6296), and (2) making representations about the
efficiency of that equipment (42 U.S.C. 6314(d)). DOE also uses these
test procedures to determine whether the equipment complies with
relevant standards promulgated under EPCA.
Federal energy efficiency requirements for covered equipment
established under EPCA generally supersede State laws and regulations
concerning energy conservation testing, labeling, and standards. (42
U.S.C. 6316(a) and (b); 42 U.S.C. 6297) DOE may, however, grant waivers
of Federal preemption for particular State laws or regulations, in
accordance with the procedures and other provisions of EPCA. (42 U.S.C.
6297(d); 42 U.S.C. 6316(b)(2)D))
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered equipment. EPCA requires that any test procedures prescribed or
amended under this section be reasonably designed to produce test
results which measure energy efficiency, energy use, or estimated
annual operating cost of a covered product during a representative
average use cycle or period of use and not be unduly burdensome to
conduct. (42 U.S.C. 6314 (a)(2))
As discussed earlier in this document, SPVUs are a category of
commercial package air conditioning and heating equipment. EPCA
requires that the test procedures for commercial package air
conditioning and heating equipment be those generally accepted industry
testing procedures or rating procedures developed or recognized by the
Air-Conditioning, Heating, and Refrigeration Institute (``AHRI'') or by
the American Society of Heating, Refrigerating and Air-Conditioning
Engineers (``ASHRAE''), as referenced in ASHRAE Standard 90.1, ``Energy
Standard for Buildings Except Low-Rise Residential Buildings''
(``ASHRAE Standard 90.1''). (42 U.S.C. 6314(a)(4)(A)) Further, if such
an industry test procedure is amended, DOE must amend its test
procedure to be consistent with the amended industry test procedure,
unless DOE determines, by rule published in the Federal Register and
supported by clear and convincing evidence, that such amended test
procedure would not meet the requirements in 42 U.S.C. 6314(a)(2) and
(3) related to representative use and test burden. (42 U.S.C.
6314(a)(4)(B))
EPCA also requires that, at least once every 7 years, DOE must
evaluate the test procedures for each type of covered equipment,
including SPVUs, to determine whether amended test procedures would
more accurately or fully comply with the requirements for the test
procedures to not be unduly burdensome to conduct and be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs during a representative average use
cycle. (42 U.S.C. 6314(a)(1)(A))
In addition, if the Secretary determines that a test procedure
amendment is warranted, the Secretary must publish proposed test
procedures in the Federal Register and afford interested persons an
opportunity (of not less than 45 days duration) to present oral and
written data, views, and arguments on the proposed test procedures. (42
U.S.C. 6314(b)) If DOE determines that test procedure revisions are not
appropriate, DOE must publish its determination not to amend the test
procedures. (42 U.S.C. 6314(a)(1)(A)(ii))
[[Page 2492]]
DOE is publishing this NOPR in satisfaction of its obligations
under EPCA. (42 U.S.C. 6314(a)(4)(B); 42 U.S.C. 6314(a)(1)(A))
B. Background
DOE's existing test procedures for SPVUs are set forth at 10 CFR
431.96. The Federal test procedure currently incorporates ANSI/AHRI
Standard 390-2003 (``ANSI/AHRI 390-2003''), ``Performance Rating of
Single Package Vertical Air-Conditioners and Heat Pumps,'' (omitting
section 6.4), and it also includes additional provisions in paragraphs
(c) and (e) of 10 CFR 431.96 that provide for an optional break-in
period and additional provisions for equipment set-up, respectively.
DOE established its test procedure for SPVUs in a final rule for
commercial heating, air conditioning, and water heating equipment
published in the Federal Register on May 16, 2012. 77 FR 28928, 28932.
ANSI/AHRI 390-2003 was the SPVU test standard referenced in the edition
of ASHRAE Standard 90.1 current at that time.
On July 20, 2018, DOE published a request for information (``RFI'')
in the Federal Register to collect information and data to consider
amendments to DOE's test procedures for SPVUs. 83 FR 34499 (``July 2018
RFI''). As part of the July 2018 RFI, DOE identified and requested
comment on several issues associated with the currently applicable
Federal test procedures, in particular concerning incorporation by
reference of the most recent version of the relevant industry standard;
efficiency metrics and calculations; and clarification of test methods.
Id. at 83 FR 3449. DOE also sought comment on any additional topics
that may inform DOE's decisions in a future test procedure rulemaking,
including methods to reduce regulatory burden while ensuring the test
procedures' accuracy. Id.
DOE received a number of comments from interested parties in
response to the July 2018 RFI. Table I-1 lists each commenter and the
abbreviation for each used in this document. DOE considered these
comments in the preparation of this NOPR. Discussion of the relevant
comments, as well as DOE's responses, are provided in the appropriate
sections of this document.
Table I-1--Interested Parties Providing Comment on the July 2018 RFI
----------------------------------------------------------------------------------------------------------------
Commenter(s) Abbreviation Commenter type
----------------------------------------------------------------------------------------------------------------
Air-Conditioning, Heating, and AHRI........................ IR.
Refrigeration Institute.
Appliance Standards Awareness Project, ASAP, NRDC, and ACEEE....... EA.
Natural Resources Defense Council,
American Council for an Energy-
Efficient Economy.
GE Appliances, a Haier Company.......... GE.......................... M.
Lennox International Inc................ Lennox...................... M.
Northwest Energy Efficiency Alliance, NEEA and NWPCC.............. EA and Interstate Compact Agency.
and Northwest Power and Conservation
Council.
Pacific Gas and Electric Company (PG&E), CA IOUs..................... U.
San Diego Gas and Electric (SDG&E), and
Southern California Edison (SCE);
collectively the California Investor-
Owned Utilities.
----------------------------------------------------------------------------------------------------------------
EA: Efficiency/Environmental Advocate; IR: Industry Representative; M: Manufacturer; U: Utility.
A parenthetical reference at the end of a comment quotation or
paraphrase provides the location of the item in the public record.\3\
---------------------------------------------------------------------------
\3\ The parenthetical reference provides a reference for
information located in the docket of DOE's rulemaking to amend the
test procedures for SPVUs (Docket No. EERE-2017-BT-TP-0020, which is
maintained at www.regulations.gov/#!docketDetail;D=EERE-2017-BT-TP-
0020). The references are arranged as follows: (Commenter name,
comment docket ID number, page of that document).
---------------------------------------------------------------------------
On June 24, 2021, AHRI published updates to its test procedure for
SPVUs as AHRI Standard 390-2021, ``Performance Rating of Single Package
Vertical Air-Conditioners and Heat Pumps'' (``AHRI 390-2021''). Among
other things, AHRI 390-2021 maintains the existing efficiency metrics--
energy efficiency ratio (``EER'') for cooling mode and coefficient of
performance (``COP'') for heating mode--but it also added a seasonal
metric that includes part-load cooling performance--the integrated
energy efficiency ratio (``IEER'') metric. AHRI 390-2021 also includes
additional specifications regarding the test methods and conditions.
II. Synopsis of the Notice of Proposed Rulemaking
In this NOPR, DOE is proposing to amend the test procedures for
SPVUs to incorporate by reference AHRI 390-2021. DOE proposes to add a
new appendix G, ``Uniform test method for measuring the energy
consumption of single package vertical air conditioners and single
package vertical heat pumps,'' (``appendix G'') that would include the
relevant test procedure requirements for SPVUs for measuring the
existing efficiency metrics: (1) EER for cooling mode and (2) COP for
heating mode. DOE is also proposing add a new appendix G1 that would
include the relevant test procedure requirements for SPVUs for
measuring with updated efficiency metrics: (1) IEER for cooling mode
and (2) COP for heating mode. Appendix G1 would provide the test
procedure for representations based on IEER and would be mandatory only
at such time as compliance is required with amended energy conservation
standards based on IEER, should DOE adopt standards using such metrics.
Additionally, DOE is proposing to define ``single-phase single
package vertical air conditioner with cooling capacity less than 65,000
Btu/h'' and ``single-phase single package vertical heat pump with
cooling capacity less than 65,000 Btu/h'' as subsets of the broader
SPVAC and SPVHP equipment category, in order to clarify what kind of
single-phase equipment with cooling capacity less than 65,000 Btu/h was
contemplated in the broader definitions of SPVAC and SPVHP established
by Congress. Single-phase equipment meeting these definitions would be
subject to the applicable commercial equipment energy conservation
standards for SPVACs and SPVHPs, while single-phase products not
meeting these definitions would properly be classified as CAC and
subject to the applicable consumer products energy conservation
standards.
DOE is proposing to establish appendices for the relevant test
procedures for SPVUs to better differentiate the specific testing
requirements. Currently, the test requirements for all types of
commercial air conditioners and heat pumps, including SPVUs, are
codified at 10 CFR 431.96. In conjunction, DOE proposes to amend Table
1 to 10 CFR 431.96 to identify the newly added Appendices G and G1 as
the applicable test procedures for testing SPVUs.
DOE's proposed actions are summarized in Table II-1 and addressed
in detail in section III of this document.
[[Page 2493]]
Table II-1--Summary of Changes in Proposed Test Procedure Relative to Current Test Procedure
----------------------------------------------------------------------------------------------------------------
Current DOE TP Proposed TP Attribution
----------------------------------------------------------------------------------------------------------------
Incorporates by reference ANSI/AHRI 390- Incorporates by reference AHRI 390-2021, Adopt industry test
2003 (excluding section 6.4). which includes the following changes. procedure.
--Includes a new energy efficiency
descriptor, IEER, which incorporates part-
load performance.
--Provides direction and accompanying
definitions for determining whether a
unit is tested as a ducted or non-
ducted unit.
--Directs that the outdoor air-side
attachments used for testing must be
specified by the manufacturer in the
supplemental testing instructions.
--Includes refrigerant charging
instructions for cases where they are
not provided by the manufacturer.
--Specifies tolerances for achieving
the rated airflow and/or minimum
external static pressure (``ESP'')
during testing and specifies how to
set indoor airflow if airflow and ESP
tolerances cannot be simultaneously
met.
--Incorporates specifications for
measuring outdoor air conditions.
--Requires data be recorded at equal
intervals of 5 minutes or less over a
30-minute measurement period.
--Clarifies that test results for
outdoor air enthalpy method are based
on results without test apparatus
connected.
--Defines the term ``manufacturer's
installation instructions'' and
includes hierarchy of precedence if
multiple instructions are included.
Only includes definitions for the Includes additional definitions: ``single- Explicitly delineate SPVUs
equipment categories; ``Single Package phase single package vertical air from other covered
Vertical Air Conditioner'' and ``Single conditioner with cooling capacity less products.
Package Vertical Heat Pump''. than 65,000 Btu/h'' and ``single-phase
single package vertical heat pump with
cooling capacity less than 65,000 Btu/h''.
Does not include provisions for certain Includes provisions for testing when Establish provisions for
components. certain components are present. testing with certain
components.
----------------------------------------------------------------------------------------------------------------
DOE has tentatively determined that the proposed amendments would
not be unduly burdensome. Furthermore, DOE has tentatively determined
that the proposed amendments described in section III of this NOPR
would not alter the measured efficiency of SPVUs or require retesting
solely as a result of DOE's adoption of the proposed amendments to the
test procedure, if made final. Use of the updated industry test
procedure provisions as proposed in Appendix G1 and the related
proposed amendments to representation requirements in 10 CFR 429.43
would not be required until the compliance date of any amended
standards denominated in terms of IEER. Additionally, DOE has
tentatively determined that the proposed amendments, if made final,
would not increase the cost of testing. Discussion of DOE's proposed
actions are addressed in detail in section III of this NOPR.
III. Discussion
A. Scope of Applicability
EPCA, as amended by the Energy Independence and Security Act of
2007 (``EISA 2007''), Public Law 110-140 (Dec. 19, 2007), defines
``single package vertical air conditioner'' and ``single package
vertical heat pump'' at 42 U.S.C. 6311(22) and (23), respectively. In
particular, these units can be single- or three-phase; must have major
components arranged vertically; must be an encased combination of
components; and must be intended for exterior mounting on, adjacent
interior to, or through an outside wall. DOE codified the statutory
definitions into its regulations at 10 CFR 431.92. Additionally, EPCA
established initial equipment classes for SPVUs with a capacity less
than 65,000 Btu/h based on phase. (42 U.S.C. 6313(a)(10)(A)(i)-(ii) and
(v)-(vi))
DOE currently defines an SPVAC as air-cooled commercial package air
conditioning and heating equipment that: (1) Is factory-assembled as a
single package that: (i) Has major components that are arranged
vertically; (ii) is an encased combination of cooling and optional
heating components; and (iii) is intended for exterior mounting on,
adjacent interior to, or through an outside wall; (2) is powered by a
single-or 3-phase current; (3) may contain 1 or more separate indoor
grilles, outdoor louvers, various ventilation options, indoor free air
discharges, ductwork, well plenum, or sleeves; and (4) has heating
components that may include electrical resistance, steam, hot water, or
gas, but may not include reverse cycle refrigeration as a heating
means. 10 CFR 431.92. Additionally, DOE defines an SPVHP as a single
package vertical air conditioner that: (1) Uses reverse cycle
refrigeration as its primary heat source; and (2) may include secondary
supplemental heating by means of electrical resistance, steam, hot
water, or gas. Id. The Federal test procedures are applicable to SPVUs
with a cooling capacity less than 760,000 Btu/h. (42 U.S.C. 6311(8)(D))
DOE is proposing to add specific definitions for ``single-phase
single package vertical air conditioner with cooling capacity less than
65,000 Btu/h'' and ``single-phase single package vertical heat pump
with cooling capacity less than 65,000 Btu/h'' to explicitly delineate
such equipment from certain covered consumer products, such as central
air conditioners, based on design characteristics. On April 24, 2020,
DOE published in the Federal Register a request for information
(``RFI'') with regards to SPVU energy conservation standards (85 FR
22958). In response to this RFI, Lennox commented that misunderstanding
the distinction between CACs and SPVUs remains an outstanding issue on
which DOE should take action. (Docket No. EERE-2019-BT-STD-0033-0008 at
pp. 1-2))
EPCA defines a ``central air conditioner'' as a product, other than
a packaged terminal air conditioner,\4\ which is powered by single-
phase electric current, air-cooled, rated below 65,000 Btu per hour, is
not contained within the same cabinet as a furnace with a rated
capacity above 225,000 Btu per hour, and is a heat pump or a cooling
only unit. (42 U.S.C. 6291(21)) DOE has incorporated this definition in
10 CFR 430.2.
---------------------------------------------------------------------------
\4\ ``Packaged terminal air conditioner'' is defined in 10 CFR
430.92 as a wall sleeve and a separate un-encased combination of
heating and cooling assemblies specified by the builder and intended
for mounting through the wall, and that is industrial equipment. It
includes a prime source of refrigeration, separable outdoor louvers,
forced ventilation, and heating availability by builder's choice of
hot water, steam, or electricity.
---------------------------------------------------------------------------
Reading the two definitions of SPVUs and CACs in isolation, certain
single-phase air conditioners and heat pumps with cooling capacity less
than 65,000
[[Page 2494]]
Btu/h and with their components arranged vertically could be understood
to be SPVUs, as opposed to CACs. DOE has previously explained that the
definitions of SPVUs and CACs must be read in the context of DOE's
authority to regulate certain consumer products (i.e., covered
products) and certain industrial equipment (i.e., covered equipment).
79 FR 78614, 78625 (April 11, 2014). Industrial equipment under EPCA
generally excludes ``covered products.'' (42 U.S.C. 6311(2)(A)(iii))
``Covered products'' are certain consumer products explicitly set forth
in the statute, as well as consumer products which have been classified
as a covered product under 42 U.S.C. 6292(b). EPCA defines ``consumer
product,'' in part, as an article which, to any significant extent, is
distributed in commerce for personal use or consumption by individuals.
(42 U.S.C. 6291(1)(B)) CACs are covered products. A product can only be
classified as an SPVU, and, therefore, industrial equipment under EPCA,
if it does not meet the definition of any covered product, including
CACs. 79 FR 78614, 78625 (April 11, 2014).
To clarify the distinction between SPVUs as industrial equipment
and CACs as covered consumer products, DOE proposes to define in 10 CFR
431.92 ``single-phase single package vertical air conditioner with
cooling capacity less than 65,000 Btu/h'' and ``single-phase single
package vertical heat pump with cooling capacity less than 65,000 Btu/
h.'' The current definitions of SPVAC and SPVHP at 10 CFR 431.92 allow
for both wall-mounted and floor-mounted units, and either may use
single-phase or three-phase power. DOE proposes to include certain
characteristics as part of these definitions that will evidence that
these equipment would likely not be distributed to any significant
extent in commerce for personal use or consumption by individuals.
These characteristics would distinguish SPVU equipment from CACs, which
are consumer products.
DOE has identified specific technical features that differentiate
floor-mounted, single-phase units intended only for commercial
applications (i.e., meaning they are SPVUs) from ones intended for
consumer applications, such as multi-family type floor-mounted, single-
phase units (i.e., meaning they are CACs). DOE has preliminarily
determined that, in order to meet commercial building ventilation
requirements \5\ (an indication that a unit is industrial equipment and
not a consumer product), floor-mounted, single-phase units on the
market have the ability for outdoor air intake. This is evidenced by
the existence of outdoor air intake dampers and associated controls.
These ventilation air provisions make the unit capable of drawing in
and conditioning outdoor air for delivery to the conditioned space
(with or without first mixing the outdoor air with return air).
Technical specifications for these floor-mounted, single-phase units
detail both the incremental and maximum outdoor air flow rates
available to meet the specific indoor air quality needs of building
occupants. Of the maximum outdoor air flow rates that DOE identified
for each unit on the market, the unit with the lowest maximum outdoor
air flow rate identified was capable of providing a maximum of 400
cubic feet per minute (``CFM'') of outdoor air, with the same drive kit
and motor settings used to determine the certified efficiency rating of
the equipment (as required for submittal to DOE by 10 CFR
429.43(b)(4)(xi)).
---------------------------------------------------------------------------
\5\ ASHRAE Standard 62.1-2019 details ventilation standards for
a variety of commercial building spaces, including educational
spaces, which are the primary market for floor-mounted, single-phase
SPVUs. Specifically, for standard classrooms occupied with persons
between the ages of 5 and 8, 10 CFM of outdoor air flow per person
is required at a default occupancy of 25 individuals per 1,000
square feet. This translates to a requirement of 250 CFM per 1,000
square feet under default occupancy. For standard classrooms
occupied by persons 9 years and older, 10 CFM of outdoor air per
person is required at a default occupancy of 35 individuals per
1,000 square feet. This translates to a requirement of 350 CFM per
1,000 square feet under default occupancy. For specialty classrooms
(lecture rooms, art, science, college laboratories, wood/metal
shops, computer labs, media centers, music/theater/dance), specific
outdoor air requirements range from 250 CFM to 350 CFM per 1,000
square feet under default occupancy. (For further details, see ANSI/
ASHRAE Standard 62.1-2019, Table 6-1.)
---------------------------------------------------------------------------
Conversely, DOE preliminarily has found that the multi-family type
floor-mounted, single-phase units that are consumer products because
they are distributed in commerce for personal use or consumption by
individuals (i.e., CACs) have little to no ability to provide outdoor
air to the conditioned space. Based on DOE's review of manufacturer
literature, for those consumer products that do provide outdoor air,
none could provide more than 120 CFM of outdoor air to the conditioned
space. Building ventilation codes may require specific levels of
outdoor air flow for multi-family type structures, but the outdoor
ventilation airflow requirements for such living spaces are
substantially lower than those for the spaces generally served by the
market for floor-mounted, single-phase SPVUs.\6\ Thus, DOE initially
has determined that, at the present time and in most cases, these
outdoor ventilation airflow requirements are adequately met using
ventilation techniques other than the outdoor air provisions
incorporated in single-package units.\7\ In addition, DOE notes that in
other applications in areas where ventilation standards exist
specifically for residences, the required outdoor air flow levels for
these structures are similar to those for multi-family type
structures.\8\
---------------------------------------------------------------------------
\6\ For the multi-family applications of hotels, motels,
resorts, and dormitories, ASHRAE Standard 62.1-2019 requires outdoor
air flow rates of 5 CFM per person at a default occupancy of 10
individuals per 1,000 square feet. This translates to a requirement
of 50 CFM per 1,000 square feet under default occupancy. (For
further details, see ANSI/ASHRAE Standard 62.1-2019, Table 6-1.)
\7\ Ventilation in high-rise multi-family apartment buildings is
typically achieved using a combination of natural and mechanical
ventilation. The preferred mechanical ventilation method is a
central system, which uses ventilation ducts oriented vertically
through stacks of apartments, with make-up air sourced from air
conditioning/heating units located on the roof and supplied via
vertical ducts. For more information see: A Guide to Energy
Efficient Ventilation in Apartment Buildings. U.S. Department of
Energy (DOE/EE-0196). 1999 (Available at: eetd.lbl.gov/node/50537).
\8\ Table N1104.2 of the ``Minnesota Rules, Chapter 1322
Residential Energy Code'' specifies ventilation rates for residences
based on a range of square footages and numbers of bedrooms. For
residences with a conditioned space between 1,000 and 1,500 square
feet in area, ventilation rates are similar to those listed in
ASHRAE Standard 62.1-2013 per 1,000 square feet for the multi-family
applications of hotels, motels, resorts, and dormitories.
Specifically, for residences with a conditioned space between 1,000
and 1,500 square feet in area, total ventilation rates range from 60
CFM (for a single-bedroom residence) to 135 CFM (for a six-bedroom
residence).
---------------------------------------------------------------------------
Based on the discussion in the prior paragraphs, DOE has
preliminarily determined that a key physical characteristic
demonstrating that floor-mounted, single-phase SPVUs are not ``of a
type'' distributed in commerce for personal use or consumption by
individuals is the ability to provide outdoor air sufficient for
commercial applications. Equipment with the ability to provide 400 CFM
or greater of outdoor air, which significantly exceeds the outdoor air
requirements for residences and multi-family applications, would likely
not be distributed to any significant extent in commerce for personal
use or consumption by individuals and, therefore, is not a consumer
product. (See 42 U.S.C. 6291(1))
DOE's review of the market for wall-mounted configurations did not
find that there was a threshold capability of providing outdoor air to
distinguish between wall-mounted, single-phase units for use in
commercial applications
[[Page 2495]]
(SPVUs) and multi-family-type floor-mounted, single-phase units (CACs).
However, based on DOE's review, all wall-mounted units marketed for
commercial applications identified by DOE were weatherized (i.e.,
designed for outdoor use) and denoted on their nameplate that they are
for ``Outdoor Use'' or ``Suitable for Outdoor Use.'' Conversely, all
units marketed for multi-family-type floor-mounted applications
identified by DOE were non-weatherized units. Based on this review, DOE
also proposes that whether a model is weatherized or non-weatherized is
a criterion for distinguishing between single-phase SPVUs and consumer
CACs.
Therefore, DOE proposes to define in 10 CFR 431.92 ``single-phase
single package vertical air conditioner with cooling capacity less than
65,000 Btu/h'' and ``single-phase single package vertical heat pump
with cooling capacity less than 65,000 Btu/h'' as SPVACs and SPVHPs,
respectively, that are either (1) weatherized, or (2) non-weatherized
and have the ability to provide a minimum of 400 CFM of outdoor air.
Single-phase single package products with cooling capacity less than
65,000 Btu/h not meeting these definitions would be properly classified
as CACs, not SPVUs.
DOE recognizes that the confusion with the appropriate
classification of CACs and SPVUs may have been compounded by DOE's
definition of ``space-constrained'' CACs and ASHRAE Standard 90.1's
definition of ``nonweatherized space constrained single-package
vertical unit.'' Nonetheless, because a space-constrained product is a
central air conditioner or heat pump, it is properly classified as a
consumer product. In 10 CFR 430.2, DOE defines ``space constrained
product'' as a central air conditioner or heat pump with certain
characteristics including rated cooling capacity no greater than 30,000
Btu/hr and an outdoor or indoor unit with dimensions or displacement
substantially smaller than those of other units and that if increased
would increase installation cost or reduce utility, and which was
available for purchase in the United States as of December 1, 2000. As
with CACs more broadly, if a unit meets DOE's definition of ``space
constrained product,'' it is not an SPVU.
In contrast, ASHRAE Standard 90.1-2013 created a new equipment
class for SPVACs and SPVHPs used in space-constrained applications,
with a definition for ``nonweatherized space constrained single-package
vertical unit'' and specified efficiency standards for the associated
equipment class. In a Notice of Data Availability addressing energy
conservation standards for certain commercial heating, air
conditioning, and water heating equipment, including SPVUs, published
in the Federal Register on April 11, 2014, DOE explicitly addressed
``nonweatherized space constrained single-package vertical units'' and
tentatively concluded that there was no need to establish a separate
space-constrained class for SPVUs. 79 FR 20114, 20123. In that
document, DOE stated that certain models currently listed by
manufacturers as SPVUs, most of which would have met the ASHRAE space-
constrained definition, were being misclassified and should be
classified as central air conditioners (in most cases, space-
constrained central air conditioners). Id. DOE reaffirmed this position
in a NOPR addressing energy conservation standards for SPVUs, published
in the Federal Register on December 30, 2014, emphasizing that a
product can only be considered commercial/industrial equipment under
EPCA if it does not meet the definition of a consumer product. 79 FR
78614, 78625. In the subsequent final rule addressing energy
conversation standards for SPVUs, DOE did not adopt definitions in
response to this issue and stated it would consider the matter in a
subsequent rulemaking. 80 FR 57438, 57448 (Sept. 23, 2015).
DOE has now tentatively determined that the characteristics
included in the proposed definitions earlier in this section of
``single-phase single package vertical air conditioner with cooling
capacity less than 65,000 Btu/h'' and ``single-phase single package
vertical heat pump with cooling capacity less than 65,000 Btu/h''
appropriately distinguish such equipment from consumer products and
address any potential confusion as to the application of the DOE
definition of ``space constrained products'' to SPVUs.
In regard to determining if a unit is capable of providing 400 CFM
of outdoor air, DOE is proposing to include provisions in 10 CFR
429.134 that specify the method of measurement of the maximum outdoor
ventilation airflow rate. DOE is proposing to specify that the outdoor
ventilation airflow rate should be set up and measured in accordance
with ASHRAE 41.2-1987, ``Standard Methods for Laboratory Airflow
Measurement,'' and Section 6.4 of ASHRAE 37-2009. DOE notes that the
proposed method for measuring outdoor ventilation airflow is generally
consistent with the test methods specified in AHRI 390-2021 (i.e., AHRI
390-2021 incorporates by reference ASHRAE 37-2009, including Section
6.4, which in turn incorporates by reference ASHRAE 41.2-1987, which
specify the method of airflow measurement.) DOE is proposing additional
specifications in this NOPR to clarify how these provisions are applied
to measure the outdoor ventilation airflow rate. First, DOE is
proposing to specify that all references to the inlet in ASHRAE 41.2-
1987 and Section 6.4 of ASHRAE 37-2009 refer to the outdoor air inlet.
Second, DOE is proposing to specify that the measurement should take
place at the conditions specified for Full Load Standard Rating
Capacity Test, Cooling in Table 3 of AHRI 390-2021, except for the
minimum external static pressure (ESP). The minimum ESP for all
validations shall be 0.00 in. H2O measured from inlet to
outlet, with a tolerance of -0.00/+0.05 in. H2O. Finally,
DOE is proposing that the outdoor air inlet pressure shall be 0.00 in.
H2O, with a tolerance of -0.00/+0.05 in. H2O when
measured against the room ambient. These additional provisions would
improve the representativeness, repeatability, and reproducibility of
the test methods for validating the outdoor ventilation airflow rate.
Issue 1: DOE requests comment on its proposal to define ``single-
phase single package vertical air conditioner with cooling capacity
less than 65,000 Btu/h'' and ``single-phase single package vertical
heat pump with cooling capacity less than 65,000 Btu/h'' as subsets of
the broader SPVAC and SPVHP equipment category. DOE requests feedback
on the proposed characteristics that would distinguish this equipment
as SPVUs (i.e., ``weatherized'' or capable of utilizing a maximum of
400 CFM of outdoor air). Additionally, DOE requests comment on the
proposed method to validate that a unit is capable of providing 400 CFM
of outdoor air.
B. Updates to Industry Standards
1. Updates to AHRI 390
As described in section I.A of this NOPR, with respect to SPVUs,
EPCA directs DOE to use industry test methods developed or recognized
by AHRI or ASHRAE, as referenced in ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A)) If such an industry test procedure is amended, EPCA
requires that DOE amend its test procedure as necessary to be
consistent with the amended industry test method unless DOE determines,
by rule published in the Federal Register and supported by clear and
convincing evidence, that the
[[Page 2496]]
amended test procedure would be unduly burdensome to conduct or would
not produce test results that reflect the energy efficiency, energy
use, and estimated operating costs of that equipment during a
representative average use cycle. (42 U.S.C. 6314(a)(4)(B))
As mentioned, the DOE test procedure at 10 CFR 431.96 references
ANSI/AHRI 390-2003 (excluding Section 6.4) for testing SPVUs, and
ASHRAE Standard 90.1 references this same industry test standard. In
response to the July 2018 RFI, GE commented that DOE should continue to
incorporate by reference the ASHRAE, ANSI, and AHRI test procedures for
SPVUs, including new editions when published by the standards-setting
bodies. (GE, No. 3 at p. 1) \9\ AHRI and Lennox encouraged DOE's
continued participation in the process to revise AHRI 390. (AHRI, No. 5
at p. 2; Lennox, No. 6 at pp. 1-2) AHRI and Lennox recommended that DOE
adopt the revised industry test standard as the DOE test procedure.
(AHRI, No. 5 at p. 2; Lennox, No. 6 at p. 1)
---------------------------------------------------------------------------
\9\ A notation in the form ``GE, No. 3 at p. 1'' identifies a
written comment: (1) Made by GE; (2) recorded in document number 3
that is filed in the docket of the SPVU test procedure rulemaking
(Docket No. EERE-2017-BT-TP-0020) and available for review at
www.regulations.gov; and (3) that appears on page 1 of document
number 3.
---------------------------------------------------------------------------
On June 24, 2021, AHRI published AHRI 390-2021, which supersedes
ANSI/AHRI 390-2003. AHRI 390-2021, which was developed as part of an
industry consensus process, includes revisions that DOE has initially
determined improve the representativeness, repeatability, and
reproducibility of the test methods. These revisions include, among
other things, the following: (1) A new energy efficiency descriptor,
IEER, which incorporates part-load cooling performance; (2) additional
specification to the testing requirements for ducted and non-ducted
units; (3) refrigerant charging instructions for cases where they are
not provided by the manufacturer; (4) additional specification for
setting the airflow rates and external static pressure for testing; (5)
additional specification for the measurement of air conditions; (6)
additional specification for the secondary capacity measurement using
the outdoor air enthalpy method; (7) guidance on the filter to be used
during test; (8) specification of a maximum compressor break-in period;
(9) further specificity for atmospheric pressure measurement
requirements; (10) additional detail regarding the installation of
outdoor air-side attachments; (11) additional direction on the use of
applicable manufacturer instructions; and (12) a list of components
that must be present for testing. DOE carefully reviewed the changes in
AHRI 390-2021 in consideration of this NOPR. In this NOPR, DOE proposes
to incorporate by reference the latest version of the industry test
procedure for SPVUs, AHRI 390-2021, per 42 U.S.C. 6314(a)(4)(A) and
(B).
2. ASHRAE 37
ANSI/ASHRAE 37-2009, a method of test for many categories of air
conditioning and heating equipment, is referenced by AHRI 390-2021 for
testing SPVUs. In particular, Appendix E of AHRI 390-2021 specifies the
method of test for SPVUs, including the use of specified provisions of
ANSI/ASHRAE 37-2009. Consistent with AHRI 390-2021, DOE is proposing to
incorporate by reference ANSI/ASHRAE 37-2009 in its test procedure for
SPVUs. Specifically, in Section 1.2 of the proposed test procedure for
SPVUs in the proposed Appendices G and G1 of subpart F of 10 CFR part
431, DOE is proposing to utilize the applicable sections of ANSI/ASHRAE
37-2009--all sections except sections 1, 2 and 4. DOE also is proposing
that in the event of any conflicts between the DOE test procedure, AHRI
390-2021 and ASHRAE 37-2009, the DOE test procedure takes highest
precedence, followed by AHRI 390-2021, followed by ASHRAE 37-2009.
C. Proposed Organization of the SPVU Test Procedure
DOE is proposing to relocate and centralize the current test
procedure for SPVUs to a new Appendix G to subpart F of part 431.
Appendix G will incorporate by reference AHRI 390-2021, but DOE will
exclude from use those sections pertaining to the calculation of IEER
(section 6.2). Correspondingly, DOE is proposing to update the existing
incorporation by reference of ANSI/AHRI 390-2003 at 10 CFR 431.95 so
that the incorporation by reference applies to Appendix G rather than
10 CFR 431.96. As proposed, SPVUs would be tested according to Appendix
G unless and until DOE adopts an amended energy conservation standard
that relies on the IEER metric.
DOE also is proposing to amend the test procedure for SPVUs by
adopting the updated version of AHRI 390-2021, including use of the
sections pertaining to IEER (section 6.2) in a new Appendix G1 to
subpart F of part 431, as discussed in the following sections. As
proposed, SPVUs would not be required to test according to the test
procedure in proposed Appendix G1 unless and until DOE adopts an
amended energy conservation standard that relies on the IEER metric.
D. Energy Efficiency Descriptor
For SPVUs, DOE currently prescribes EER as the cooling mode metric
and COP as the heating mode metric. 10 CFR 431.96. These energy
efficiency descriptors are consistent with those included in ASHRAE
90.1-2019 for SPVUs. EER is the ratio of the produced cooling effect of
the SPVU to its net work input, expressed in Btu/watt-hour and measured
at standard rating conditions. COP is the ratio of the produced heating
effect of the SPVU to its net work input, expressed in W/W, and
measured at standard rating conditions.
1. Efficiency Metrics
EER measures efficiency at full-load conditions. DOE's current test
procedure for SPVUs does not include a seasonal metric that measures
part-load performance. A seasonal metric is a weighted average of the
performance of cooling or heating systems at different rating points
intended to represent average efficiency over a full cooling or heating
season.
DOE noted in the July 2018 RFI that several other categories of
commercial package air conditioning and heating equipment are rated
using a seasonal metric, such as IEER for air-cooled commercial unitary
air conditioners (``CUACs''), as presented in Section 6.2 of AHRI 340/
360-2019, ``Performance Rating of Commercial and Industrial Unitary
Air-conditioning and Heat Pump Equipment.'' 83 FR 34499, 34503 (July
20, 2018). IEER is a weighted average of efficiency at the four load
levels representing 100, 75, 50, and 25 percent of full-load capacity,
each measured at an outdoor air condition representative of field
operation at the given load level.
DOE noted in the July 2018 RFI that ANSI/AHRI 390-2003 includes a
seasonal part-load metric for SPVUs (i.e., integrated part-load value
(``IPLV'')). 83 FR 34499, 34503 (July 20, 2018). IPLV integrates unit
performance at each capacity step provided by the refrigeration system.
The IPLV tests are conducted at constant outdoor air conditions of 80
[deg]F dry-bulb temperature and 67 [deg]F wet-bulb temperature. Id. DOE
is aware that some manufacturers make representations of part-load
performance of SPVUs in product literature using IPLV. DOE has noted
that IPLV was formerly used for rating CUACs but has since been removed
from AHRI 340/360 in favor of IEER. Id.
[[Page 2497]]
As part of the July 2018 RFI, DOE requested comment on whether it
should consider adopting for SPVUs a cooling-mode metric that
integrates part-load performance to better represent full-season
efficiency, and whether a part-load metric such as IEER or IPLV would
be appropriate for SPVUs. 83 FR 34499, 34503 (July 20, 2018).
AHRI and GE both commented that DOE should not consider adopting a
part-load cooling metric at this time, stating that doing so would
increase test burden for a specialized product sold in a comparatively
small market. (AHRI, No. 5 at p. 6; GE, No. 3 at p. 2) GE noted that
for SPVUs with single-speed compressors, the EER test method requires
only a single test with an average of 8 hours to complete and validate
test data, whereas an IEER test method would require four tests, which
entails additional testing time and cost. (GE, No. 3 at p. 2) GE stated
that for dual-voltage units, the IEER test method would increase test
time to approximately 64 hours per unit, and that the time to test 3
units for a given model would increase testing time from 48 hours to
192 hours under the IEER test method. Id.
AHRI commented that a part-load metric may be appropriate for some
equipment, such as two-stage or variable-capacity SPVUs, but only for
certain applications. (AHRI, No. 5 at p. 6) AHRI and Lennox commented
that as part of the revisions to AHRI 390, industry is assessing
whether IEER or IPLV would better represent part-load performance for
units other than single-stage products. (AHRI, No. 5 at p. 6; Lennox.
No. 6 at p. 5) Lennox commented that while a part-load metric may be a
favorable option for SPVUs in the long term, there was not sufficient
data at that time to evaluate the impacts on performance and the
increase in test burden versus potential consumer benefits of optimized
part-load performance. (Lennox. No. 6 at p. 5)
The CA IOUs commented that the IEER metric was developed for CUACs
with greater than 65,000 Btu/h cooling capacity using office, retail,
and larger permanent school space loads as the basis for the part-load
weighting factors. (CA IOUs, No. 2 at p. 3) They noted that SPVUs are
generally used in smaller settings, such as electronic sheds and
relatively small relocatable classrooms. Id. The CA IOUs stated that,
while there may be some shortcomings with the IEER metric, it results
in ratings more reflective of annual energy efficiency than those
produced by IPLV. Id. The CA IOUs commented that IPLV, on the other
hand, has a strong potential to misrepresent efficiency ratings because
it does not rate all units at identical capacity points, leading to a
difference in the weighting factors used for various equipment. Id. In
addition, the CA IOUs commented that all part-load ratings are measured
at an ambient outdoor temperature of 80 [deg]F. Id. The CA IOUs
asserted that these two factors often cause tested units with fewer
capacity reduction stages to have higher measured efficiencies than
those with more stages, whereas in reality, units with more stages tend
to be more efficient. Id.
The CA IOUs stated that while the IEER metric provides a valuable
measure of annual efficiency, the EER metric is important for achieving
reductions in peak loads. (CA IOUs, No. 2 at p. 3) The CA IOUs stated
that because the IEER metric uses a low weighting (i.e., 2 percent) of
the full-load condition, a standard based only on the IEER metric would
incentive manufacturers to optimize equipment at the part-load
conditions and could potentially result in equipment that is designed
with lower full-load EERs than the current standards for this
equipment. Id. The CA IOUs supported using both the IEER metric that
measures part-load efficiencies in conjunction with the currently
regulated full-load EER metric as a means to prevent poor equipment
performance at full-load conditions. Id.
ASAP, NRDC, and ACEEE commented that DOE should develop a new
cooling efficiency metric for SPVUs that reflects annual energy
consumption, including part-load operation. (ASAP, NRDC, and ACEEE, No.
4 at p. 1-2) They stated that the current EER metric reflects only
full-load, steady-state operation, but that SPVUs rarely operate at
full-load in the field. Id. at 1. In addition, ASAP, NRDC, and ACEEE
stated that the current metric is not able to demonstrate potential
improved efficiency of SPVUs with variable-speed or thermostatic and
electronic expansion valve technologies. Id.
ASAP, NRDC, and ACEEE also commented that the IEER metric is not
representative of locations and usage patterns for SPVUs and encouraged
DOE to investigate a part-load performance metric that better reflects
SPVU usage. (ASAP, NRDC, and ACEEE, No. 4 at pp. 1-2) They commented
that DOE should consider its analysis from the most recent SPVU
standards rulemaking, which included building simulation models for
modular classrooms, modular offices, and telecommunication shelters, to
inform the development of load points and weightings for a part-load
metric. Id. at 2.
In response, DOE recognizes that SPVUs often operate at part-load
(i.e., less than designed full-load capacity) in the field, depending
on the application and location. As discussed in section III.B, AHRI
390-2021 includes a new part-load cooling metric, IEER. To the extent
that AHRI expressed concerns regarding the IEER test method in response
to the July 2018 TP RFI, DOE presumes that AHRI's original position on
this issue changed during the course of developing AHRI 390-2021. The
test conditions and weighting factors for this IEER metric in AHRI 390-
2021 were developed specifically for SPVUs based on an annual building
load analysis and temperature data for buildings representative of SPVU
installations, including modular classrooms, modular offices, and
telecommunication shelters.\10\ The test conditions and weighting
factors for the four load levels representing 100, 75, 50, and 25
percent of full-load capacity are different than those used in the IEER
metric in AHRI 340/360-2019, which were developed based on CUAC
building types. As a result, DOE considers the IEER metric
representative of the cooling efficiency for SPVUs on an annual basis,
and more representative than the current EER metric.
---------------------------------------------------------------------------
\10\ Based on EnergyPlus analysis developed for the previous
energy conservation standards rulemaking for SPVUs. 80 FR 57438,
57462 (Sept. 23, 2015). EnergyPlus is a whole building energy
simulation program (Available at: https://apps1.eere.energy.gov/buildings/energyplus/).
---------------------------------------------------------------------------
In this NOPR, DOE is proposing to incorporate by reference AHRI
390-2021, which maintains the existing full-load cooling mode metric,
EER, and adds the IEER metric for SPVUs. More specifically, DOE is
proposing to add a new Appendix G that would include the relevant test
procedure requirements for SPVUs for measuring efficiency using the
existing efficiency metrics (i.e., EER for cooling mode and COP for
heating mode) and to add a new Appendix G1 that would incorporate the
provisions for measuring efficiency using IEER and COP.
Issue 2: DOE requests comment on its proposal to adopt the test
methods specified in AHRI 390-2021 for calculating IEER for SPVUs.
As discussed, DOE's current standards for SPVUs at 10 CFR 431.97
specify minimum efficiency requirements based on the full-load cooling
metric, EER, and the heating metric, COP. The current DOE standards
levels are the same as those specified in the current version of ASHRAE
Standard 90.1 (ASHRAE 90.1-2019).
[[Page 2498]]
Any future energy conservation standards based on IEER would evaluate
differences in the measured energy efficiency based on the IEER metric
relative to EER (i.e., by developing an appropriate ``crosswalk,'' as
necessary), and would consider data and/or analysis that compares the
ratings of SPVUs under the two metrics.
Issue 3: DOE requests comment and data on ratings under the current
EER metric specified in 10 CFR 431.97 and ASHRAE 90.1-2019 based on
ANSI/AHRI 390-2003, as compared to ratings using the IEER metric under
AHRI 390-2021.
ASAP, NRDC, and ACEEE, as well as NEEA and NWPCC, commented in
response to the July 2018 RFI that DOE should consider a dynamic, load-
based test procedure to measure both cooling and heating efficiency of
SPVUs, similar to the test procedure for residential central air
conditioners developed by the Canadian Standards Association (``CSA'')
Group. (ASAP, NRDC, and ACEEE, No. 4 at p. 2; NEEA and NWPCC, No. 7 at
p. 3) NEEA and NWPCC commented that a load-based test procedure, such
as the CSA test procedure, could measure energy use of the equipment at
25, 50, 75 and 100-percent load without overriding equipment controls,
as opposed to the current IEER test specified in AHRI 340/360 for CUACs
that locks equipment controls to 25, 50, 75 and 100 percent of
capacity. (NEEA and NWPCC, No. 7 at p. 3) They commented that a load-
based test would allow manufacturers to design equipment controls and
thermostats that would reduce unnecessary cycling and improve humidity
control. Id. According to NEEA and NWPCC, the current IEER test method
specified in AHRI 340/360 uses an artificially low maximum cycling loss
that does not provide incentive for manufacturers to reduce cycling
losses. Id. ASAP, NRDC, and ACEEE, as well as NEEA and NWPCC, commented
that a load-based test would better capture how SPVUs perform in the
field under varying loads, including capturing the impact of cycling
losses, the potential benefits of variable-speed operation, and the
importance of control strategies. (ASAP, NRDC, and ACEEE, No. 4 at p.
2; NEEA and NWPCC, No. 7 at p. 3)
DOE is currently not aware of data showing that any dynamic load-
based test procedure produces repeatable and reproducible test results.
Furthermore, DOE is not aware of data showing that the CSA test
procedure recommended by NEEA and NWPCC produces repeatable and
reproducible results for central air conditioners (``CACs'') and heat
pumps, and that procedure has not yet been evaluated for SPVUs.
Therefore, DOE is not proposing any dynamic load-based test procedures
at this time.
2. Test Conditions Used for Efficiency Metrics
Under 42 U.S.C. 6314(d)(1), EPCA requires that representations with
respect to the energy consumption of SPVUs must be based on the DOE
test procedure. DOE notes that the heating mode test used to calculate
COP and determine compliance with standards for SPVHPs is conducted at
47 [deg]F outdoor air dry-bulb temperature and 43 [deg]F outdoor air
wet-bulb temperature, and is designated as the ``Full Load Standard
Rating Capacity Test, Heating'' in Table 3 of AHRI 390-2021. DOE is
proposing to also utilize Table 3 of AHRI 390-2021, which includes an
optional ``Low Temperature Operation'' heating application rating test
that manufacturers may use to make representations of energy
consumption for SPVUs. That test is based on an outdoor air dry-bulb
temperature of 17 [deg]F and outdoor air wet-bulb temperature of 15
[deg]F.
To allow manufacturers to make voluntary representations at the
lower temperature condition, DOE is proposing to specify in Appendices
G and G1 that the low temperature operation heating mode test
conditions specified in Table 3 of AHRI 390-2021 are optional. This
would clarify that additional representations for SPVHPs at a lower
temperature condition are optional, but that if such representations
are made, they must be based on testing conducted in accordance with
the DOE test procedure using the specified low temperature operation
heating mode test conditions in addition to those made at the full-load
standard heating conditions.
Issue 4: DOE requests comment on its proposal to clarify that COP
representations using the ``Low Temperature Operation, Heating''
conditions in Table 3 of AHRI 390-2021 are optional.
3. Fan Energy Use
As part of the July 2018 RFI, DOE requested comment on whether
changes to the SPVU test procedure are needed to properly characterize
a representative average use cycle, including changes to more
accurately represent fan energy use in field applications. 83 FR 34499,
34503 (July 20, 2018). DOE also requested information as to the extent
that accounting for the energy use of fans in commercial equipment such
as SPVUs would be additive of other existing accountings of fan energy
use. Id. The Appliance Standards and Rulemaking Federal Advisory
Committee (``ASRAC'') Commercial and Industrial Fans and Blowers
Working Group (``Working Group'') had earlier provided recommendations
regarding the energy conservation standards, test procedures, and
efficiency metrics for commercial and industrial fans and blowers in a
term sheet. (Docket No. EERE-2013-BT-STD-0006-0179 at p. 1)
Specifically, recommendation #3 discussed the need for DOE's test
procedures and related efficiency metrics to account more fully for the
energy consumption of fan use in regulated commercial air-conditioning
equipment. (Docket No. EERE-2013-BT-STD-0006-0179 at pp. 3-4) The
Working Group recommended that DOE consider revising efficiency metrics
that include energy use of supply and condenser fans in order to
include the energy consumption during all relevant operating modes,
including ventilation and part-load operation, in the next round of
test procedure rulemakings. The Working Group included SPVUs in its
list of regulated equipment for which fan energy use should be
considered. (Docket No. EERE-2013-BT-STD-0006-0179 at pp. 3-4, 16)
In response to the 2018 RFI, ASAP, NRDC, and ACEEE, as well as NEEA
and NWPCC, commented that DOE should amend the test procedure to
account for fan energy use outside of mechanical cooling and heating
for fans in regulated equipment to more fully capture fan energy use.
(ASAP, NRDC, and ACEEE, No. 4 at p. 1; NEEA and NWPCC, No. 7 at pp. 1-
3) ASAP, NRDC, and ACEEE asserted that by failing to capture fan
operation for economizing, ventilation, and other functions outside of
cooling mode, the test procedure may be significantly underestimating
fan energy consumption. (ASAP, NRDC, and ACEEE, No. 4 at p. 1) NEEA and
NWPCC added that these amendments would encourage the adoption of
features such as variable-speed fans, which provide additional control
and flexibility for building owners and operators in addition to
reducing energy waste. (NEEA and NWPCC, No. 7 at p. 2)
NEEA and NWPCC commented that the commercial prototype building
models used in the analysis in support of ASHRAE Standard 90.1 include
information on the operation of fans in ventilation mode and economizer
mode, and these models could be used to develop national average fan
operating hours outside of heating and cooling modes. (NEEA and NWPCC,
No. 7 at p. 4) NEEA and NWPCC commented that the vast majority of SPVUs
are
[[Page 2499]]
installed in commercial buildings requiring a building permit and that
the ASHRAE Standard 90.1 requirements are reflective of building code
requirements. Id. NEEA and NWPCC stated that, as a result, the energy
models used in support of ASHRAE Standard 90.1 are representative of
how the equipment is installed and used across the United States. Id.
NEEA and NWPCC commented that one potential approach to represent
fan energy use in regulated equipment more accurately would be to use
IEER to assess the efficiency of the refrigeration cycle of SPVUs, and
to use an alternative metric to assess the performance of embedded fans
in SPVUs. (NEEA and NWPCC, No. 7 at pp. 3-4) NEEA and NWPCC suggested
that ANSI/AMCA 208-18, ``Calculation of the Fan Energy Index,''
provides a potential way to measure embedded fan performance in SPVUs
by using the fan energy index (``FEI''). Id. NEEA and NWPCC stated that
DOE could, therefore, develop a revised IEER-type metric that weights
together cooling performance based on the traditional IEER test and an
FEI-based metric for fan efficiency. Id. NEEA and NWPCC stated that
accounting for the energy use of fan operation in SPVUs does not need
to alter measured efficiency, and that DOE could align the FEI and IEER
metrics such that manufacturers would have multiple viable design
option pathways to achieve the minimum IEER efficiency standard without
improving the embedded fan efficiency above the minimum FEI efficiency
standard. Id.
AHRI and Lennox commented that the current metrics for SPVUs (EER
and COP) account for fan power and that there is no need to double
count fan contribution, asserting that standards based on these metrics
will likely already require the need for improved fan motor efficiency.
(AHRI, No. 5 at pp. 6, 7; Lennox, No. 6 at p. 6) AHRI commented that
adding a requirement to measure fan energy use during economizing or
electric heating would increase testing burden. (AHRI, No. 5 at p. 6)
AHRI and Lennox further commented that while most SPVUs can provide
some level of ventilation, their primary function is cooling and
heating. (AHRI, No. 5 at p. 7; Lennox, No. 6 at p. 6) AHRI asserted
that DOE is limited to one metric per covered product, and, therefore,
the representative average use cycle for SPVUs should concentrate on
the bulk of energy used during cooling and heating, rather than the
occasional and ancillary fan-only ventilation utility. (AHRI, No. 5 at
p. 7) In addition, AHRI asserted that a key goal in prohibiting
separate component standards was to allow the manufacturer to innovate
to meet energy use standards. Id.
AHRI commented that DOE has the authority to include certain fans
and blowers, by rule, as ``covered equipment'' if such products meet
all the requirements of 42 U.S.C. 6311(2), but the commenter stated
that it would not be appropriate to apply such standard to fans
embedded in regulated equipment. (AHRI, No. 5 at p. 8) AHRI asserted
that 42 U.S.C. 6312 limits DOE's authority to regulate as covered
industrial equipment certain articles that are also components of
consumer products. Id. AHRI commented that because the fans in SPVUs
are built only for the product and cannot be purchased on the open
market and applied as ``stand alone fans,'' the fans in SPVUs are
protected from double-regulation under EPCA. Id. AHRI also commented
that DOE's authority under 42 U.S.C. 6312(b) and (c) to regulate
components is based on necessity, and that adding a fan metric to the
current EER requirement is not necessary because SPVUs already have an
overall energy efficiency requirement. Id. AHRI and Lennox commented
that the fact that Congress was compelled to grant a specific provision
of authority for a consumer furnace ventilation metric affirms that DOE
lacks general authority to create overlapping ventilation requirements
for other regulated products. (AHRI, No. 5 at pp. 8-9; Lennox, No. 6 at
p. 6)
In response to these comments, DOE does not have sufficient
information at this time regarding the operation of fans outside of
mechanical heating and cooling during an average use cycle (e.g.,
economizing, ventilation) specific to SPVU installations as would allow
it to consider changing the existing efficiency metric(s) to include
this aspect of energy use. DOE recognizes that the current metrics for
SPVUs do not include fan energy use during all relevant operation
modes. Provisions to measure fan energy use when there is no heating or
cooling being provided, and when performing ancillary functions (e.g.,
economizing, ventilation, filtration, and auxiliary heat), are not
included in ANSI/AHRI 390-2003 and have not been included in the
updated industry consensus standard, AHRI 390-2021. Further, DOE lacks
sufficient information on the number of units capable of operating in
these modes, total energy use in these operating modes, and information
regarding the frequency of operation of these modes during field
conditions, which the Department would need to determine whether such
testing would be appropriate for SPVUs and/or to develop a metric
representing the national average fan operating hours for SPVUs. DOE
notes further that the commercial prototype building models used in the
analysis in support of ASHRAE Standard 90.1 that NEEA and NWPCC
recommended do not include information on building types typical to
SPVU installations (i.e., modular and telecommunications). If
additional information becomes available as would allow DOE to consider
incorporation of fan energy use during other relevant SPVU operating
modes for all relevant building types into the test method and metric
for SPVUs, DOE may consider such information in a subsequent rulemaking
proceeding. With regards to comments concerning fan energy use metrics
and regulation of fan energy use being double-counting, DOE will
consider its authority under EPCA when and if developing such test
procedures.
E. Test Method
This section discusses the various issues that DOE identified in
the test methods for SPVUs, including those raised in the July 2018 RFI
and considered as part of DOE's review of AHRI 390-2021. These issues
include: (1) Provisions for testing ducted and non-ducted units; (2)
outdoor air-side airflow rate; (3) refrigerant charging instructions;
(4) voltage requirements; (5) filter requirements; (6) airflow and
external static pressure requirements; (7) air temperature
measurements; (8) defrost energy use; and (9) provisions for the
outdoor air enthalpy method.
In addition, in DOE's existing regulations, Table 1 to 10 CFR
431.96 specifies the applicable industry test procedure for each
category of commercial package air conditioning and heating equipment,
and it identifies additional testing requirements that also apply. In
this NOPR, DOE is proposing to reorganize subpart F to 10 CFR part 431
so that the test procedure requirements for SPVUs are included in
separate appendices (Appendix G and G1). DOE proposes that Table 1 to
10 CFR 431.96 identify only the applicable appendix to use for testing
SPVUs (Appendix G or G1) and that 10 CFR 431.96 would no longer include
any additional test requirements for SPVUs.
1. Unit Set-Up
a. Testing Ducted and Non-Ducted Units
DOE noted in the July 2018 RFI that ANSI/AHRI 390-2003 specifies
different ESP requirements for ducted and non-ducted units. 83 FR
34499, 34501 (July 20, 2018). Specifically, Section 5.2.2 of
[[Page 2500]]
ANSI/AHRI 390-2003 requires that non-ducted units be tested at zero
ESP, and it specifies ESP requirements in Table 4 of ANSI/AHRI 390-2003
for ducted equipment. However, whether an SPVU is ducted may depend on
the installation rather than the model. A given SPVU model could be
installed either with or without a duct, thereby resulting in its
status as ducted or non-ducted being determined in the field. In the
July 2018 RFI, DOE stated that it is not aware of physical
characteristics that would readily distinguish SPVUs as either ducted
or non-ducted models and that several models advertise the capability
for use in both ducted and non-ducted installations. DOE noted that
ANSI/AHRI 390-2003 does not specify how to determine whether an SPVU
model is to be tested using the ducted or non-ducted provisions. As
part of the July 2018 RFI, DOE requested comment on characteristics for
determining whether SPVU models would be installed as ducted or non-
ducted and on how equipment sold for both configurations are currently
tested. 83 FR 34499, 34501 (July 20, 2018).
AHRI commented that many, if not all, SPVUs on the market allow for
installation with or without a duct, and that it is standard practice
to test all SPVUs in the ducted configuration. (AHRI, No. 5 at pp. 2)
AHRI stated that the (then-draft) revised version of AHRI 390 sought to
standardize industry practice by defining a non-ducted unit as an air
conditioner or heat pump that is not designed and marketed to deliver
conditioned air to the indoor space through a duct(s), and that a
factory-installed wall sleeve(s) would not be considered as a duct.
(AHRI, No. 5 at pp. 2-3) AHRI also noted that the draft version of AHRI
390 specified that if a duct cannot be attached and the unit is
marketed as non-ducted only, then testing would be performed in the
non-ducted configuration, and that all other units would be tested as
ducted. Id. Lennox commented that any model marketed for ducted
applications should be tested in a ducted configuration, and that
testing in a non-ducted configuration would be appropriate if a model
does not provide provisions for duct attachment and the unit is
marketed as non-ducted only. (Lennox, No. 6 at p. 2)
DOE notes that the draft definition and provisions referenced by
AHRI are included in AHRI 390-2021, along with a definition for ducted
units. DOE preliminarily agrees that the definition of a non-ducted
unit and associated provisions included in AHRI 390-2021 provide
additional specification for testing ducted and non-ducted SPVUs. DOE
understands that these definitions and provisions are consistent with
how units are currently classified by industry and tested, as indicated
by AHRI's comments and the inclusion in AHRI 390-2021. DOE is proposing
to adopt these definitions found in Sections 3.4 and 3.10 of AHRI 390-
2021 and associated provisions specified in section 5.7 of AHRI 390-
2021, as enumerated in section 0 of the proposed Appendix G and in
section 0 of the proposed Appendix G1.
b. Outdoor Air-Side Airflow Rate
The current DOE test procedure for SPVUs requires that the unit be
set up for test in accordance with the manufacturer installation and
operation manuals. 10 CFR 431.96(e). In addition, Section 5.2.3 of
ANSI/AHRI 390-2003 specifies that for SPVUs with an outdoor air-side
fan drive that is adjustable, standard ratings are determined at the
outdoor-side airflow rate specified by the manufacturer. Section 5.2.3
of ANSI/AHRI 390-2003 also specifies that, where the outdoor air-side
fan drive is non-adjustable, standard ratings are determined at the
outdoor airflow rate inherent to the equipment when operated with all
of the resistance elements associated with inlets, louvers, and any
ductwork and attachments considered by the manufacturer as normal
installation practice.
However, Section 5.2.3 of ANSI/AHRI 390-2003 does not further
specify what attachments the manufacturer considers ``normal
installation practice.'' For externally-mounted SPVUs, provisions for
transferring outdoor air through an external wall are not necessary,
but it may be possible that alternative ``resistance elements'' could
be offered as options (i.e., louvers instead of grills). Furthermore,
for internally-mounted SPVUs, there may be multiple options for the
specific geometry for external wall pass-through, as well as the option
for louvers instead of grills.
As part of the July 2018 RFI, DOE requested comments on the
variations in outdoor air-side attachments (e.g., grills, louvers, wall
sleeve) that could affect performance during testing and test procedure
provisions to standardize outdoor air flow for both externally and
internally mounted SPVUs. 83 FR 34499, 34501 (July 20, 2018). On this
topic, ASAP, NRDC, and ACEEE commented that DOE should standardize
which resistive elements should be present for testing to ensure that
the test is representative of field installations and to improve
repeatability and reproducibility of test results. (ASAP, NRDC, and
ACEEE, No. 4 at p. 3) AHRI stated that options for different outdoor
air-side attachments do exist and could impact the performance during
testing. (AHRI, No. 5 at p. 3) AHRI and Lennox commented that, to
mitigate this issue, the attachments to be used for testing should be
specified by the manufacturer in the supplemental testing instructions
submitted to DOE. (AHRI, No. 5 at p. 3; Lennox, No. 6 at p. 2) AHRI
added that information regarding the installation of plenums, grills,
or other outdoor air-side attachments is provided by manufacturers for
testing conducted as part of the AHRI certification program. (AHRI, No.
5 at p. 3)
DOE notes that Section 5.8.4 of AHRI 390-2021 explicitly specifies
use of the outdoor air-side attachments specified in the manufacturer's
supplemental testing instructions. DOE expects this practice would
improve the representativeness in that the unit is tested in a
configuration more similar to that of the unit as installed in the
field.\11\ DOE also expects that the more specific test set-up
instruction would improve the reproducibility of test results by
reducing potential variation in the configuration of the unit when
tested. DOE understands that some equipment may be offered for sale
with multiple outdoor air-side attachment options, including an option
to ship the unit without any attachments. Based on its review of
manufacturer materials, DOE has found that in such cases most
manufacturer's instructions or marketing materials indicate that use of
outdoor air-side attachments are recommended or necessary for
installation. Based on the manufacturer instructions, use of outdoor
air-side attachments is standard practice in field use for units for
which they are offered for sale.
---------------------------------------------------------------------------
\11\ Section 3.8.2 of AHRI 390-2021 specifies that the
supplemental testing instructions shall include no instructions that
deviate from the manufacturer's installation instructions unless
necessary to comply with steady-state requirements (in which case
the steady operation must match, to the extent possible, the average
performance obtained without deviating from the manufacturer's
installation instructions).
---------------------------------------------------------------------------
AHRI 390-2021 states that if a unit includes multiple outdoor air-
side attachment options, including an option for the unit to ship
without any attachments, an outdoor air-side attachment must be
specified in the supplemental testing instructions. DOE would expect
that this instruction helps ensure testing is representative of how a
unit would be installed and operated in the field. DOE is proposing to
adopt these provisions regarding the outdoor air-side attachments, as
specified in Section 5.8.4 of AHRI 390-2021,
[[Page 2501]]
enumerated in section 0 of the proposed Appendix G and section 0 of the
proposed Appendix G1.
c. Refrigerant Charging Instructions
The amount of refrigerant can have a significant impact on the
system performance of air conditioners and heat pumps. DOE's current
test procedures for commercial package air conditioners and heat pumps,
including the test procedures for SPVUs, require that units be set up
for test in accordance with the manufacturer installation and operation
manuals. 10 CFR 431.96(e). In addition, the current DOE test procedures
state that if the manufacturer specifies a range of superheat, sub-
cooling, and/or refrigerant pressures in the installation and operation
manual, any value within that range may be used to determine
refrigerant charge, unless the manufacturer clearly specifies a rating
value in its installation or operation manual, in which case the
specified value shall be used. 10 CFR 431.96(e)(1). However, the
current DOE test procedures do not provide charging instructions to be
used if the manufacturer does not provide instructions in the manual
that is shipped with the unit or if the provided instructions are
unclear or incomplete.
DOE noted in the July 2018 RFI that ANSI/AHRI 390-2003 does not
provide any specific guidance on setting and verifying the refrigerant
charge of a unit. 83 FR 34499, 34501 (July 20, 2018). DOE also noted in
the July 2018 RFI that the test procedure final rule for central air
conditioners and heat pumps (``CAC/HPs'') published in the Federal
Register on June 8, 2016 (81 FR 36992; ``June 2016 CAC TP final rule'')
established a comprehensive approach for refrigerant charging to
improve test reproducibility. Id. The approach specifies which set of
installation instructions to use for charging, explains what to do if
there are no instructions, specifies that target values of parameters
are the centers of the ranges allowed by installation instructions, and
specifies tolerances for the measured values. 10 CFR part 430, subpart
B, appendix M, section 2.2.5. This approach also requires that
refrigerant line pressure gauges be installed for single-package units,
unless otherwise specified in manufacturer instructions. Id.
As part of the July 2018 RFI, DOE sought comment on whether it
would be appropriate to adopt an approach for charging requirements for
SPVUs similar to the approach adopted in the June 2016 CAC TP final
rule. 83 FR 34499, 34501 (July 20, 2018). DOE also requested data
demonstrating how sensitive the performance of an SPVU is to changes in
the various charge indicators used for different charging methods,
specifically the method based on sub-cooling. Id.
ASAP, NRDC, and ACEEE commented that while most manufacturers
appear to ship SPVUs with the refrigerant already charged, DOE should
still develop consistent and comprehensive charging instructions to
ensure repeatable and reproducible test results, and to account for the
possibility of products offering different charging instructions in the
future. (ASAP, NRDC, and ACEEE, No. 4 at p. 3) NEEA and NWPCC commented
that DOE should review how often SPVUs are charged with refrigerant at
the site when installed, and that if refrigerant charge is often
modified at installation, they support adopting charging requirements
consistent with the June 2016 CAC TP final rule. (NEEA, NWPCC, No. 7 at
p. 2)
AHRI commented that the charging requirements adopted in the June
2016 CAC TP final rule are not appropriate for SPVUs. (AHRI, No. 5 at
p. 3) AHRI stated that SPVUs are shipped charged with refrigerant and
no charging should be required. Id. AHRI added that many units do not
have service ports, and those that do are charged by weight to the
specification on the unit's nameplate. Id. Lennox stated that all of
its models are shipped with a full refrigerant charge, and no further
charge adjustments are required. (Lennox, No. 6 at p. 3) Lennox also
stated that if there is any discrepancy regarding charge quantity, the
unit should be charged by weight to the specification on the unit
nameplate. Id. Similarly, the CA IOUs commented that because SPVUs are
factory-sealed, package units, many charging requirements that were
adopted in the June 2016 CAC TP final rule would not apply to SPVUs.
(CA IOUs, No. 2 at p. 1) The CA IOUs did state that some language from
the June 2016 CAC TP final rule would be beneficial to adopt; in
particular, provisions related to pressure gauges for single-package
units and language banning refrigerant charge adjustment during
testing. (Id. at pp. 1-2)
Based on a review of equipment available on the market, DOE finds
that SPVUs are typically shipped from the factory charged with
refrigerant, consistent with comments received. DOE observed that while
the majority of units are charged by weight, at least one
manufacturer's instructions specified that if the refrigerant charge
needs to be adjusted (e.g., due to leaks), the charge should be
adjusted based on the manufacturer's specified values for sub-cooling
and superheat.
Section 5.6 of AHRI 390-2021 includes instructions for charging to
be used if sufficient information is not provided in the manufacturer's
installation instructions, similar to the provisions for CACs adopted
in the June 2016 CAC TP final rule. Specifically, AHRI 390-2021 directs
that charging be performed at the conditions specified in the
manufacturer's installation instructions or, if not specified, at the
full-load cooling Standard Rating Conditions. AHRI 390-2021 directs
that if the manufacturer's installation instructions specify a range
for superheat, sub-cooling, or refrigerant pressure, the average of the
range is used to determine the refrigerant charge. AHRI 390-2021 also
specifies a hierarchy of charging parameters to follow (with charge
weight being the highest priority) if different requirements provided
in the manufacturer's installation instructions cannot be
simultaneously met. DOE proposes to adopt section 5.6 in AHRI 390-2021
for refrigerant charging, as enumerated in section 0 of the proposed
Appendix G and in section 0 of the proposed Appendix G1.
The proposed refrigerant charging instructions provide additional
specification to the Federal test method that would produce more
repeatable and reproducible results. DOE notes that as proposed, these
refrigerant charging provisions would only apply if the manufacturer
installation instructions do not provide sufficient guidance regarding
refrigerant charging. As a result, these provisions would not restrict
the flexibility that manufacturers currently have in providing
refrigerant charging instructions, so long as the provided instructions
are sufficient.
d. Voltage Requirements
In the July 2018 RFI, DOE noted that Section 5.2.1 of ANSI/AHRI
390-2003 requires that, for units rated with 208/230 dual nameplate
voltages, the test be performed at 230 volts (V). 83 FR 34499, 34501
(July 20, 2018). For all other dual nameplate voltage units, the test
standard requires that the test be performed at both voltages, or at
the lower voltage if only a single rating is to be published. Id. DOE
also noted that voltage can affect the measured efficiency of air
conditioners, and requested data demonstrating the effect of voltage on
air conditioning equipment. Id. DOE requested comment on whether
certain voltages within common dual nameplate voltage ratings (e.g.,
208/230 V) are more representative of a typical field installation. Id.
[[Page 2502]]
Lennox commented that the voltage requirements specified in ANSI/
AHRI 390-2003 are consistent with other similar industry test
procedures and are appropriate for this equipment. (Lennox, No. 6 at p.
3) AHRI acknowledged that voltage can affect the measured efficiency of
air conditioners, but it stated that these variations tend to be
insignificant and do not correlate to a specific voltage. (AHRI, No. 5
at pp. 2-3) AHRI also commented that the majority of SPVUs are applied
at 230 V, and, therefore, the current test procedure is appropriate.
Id.
In response, DOE first points out that Section 5.8.1 of AHRI 390-
2021 maintains the same voltage requirements for SPVUs as specified in
the current DOE test procedure and in ANSI/AHRI 390-2003. DOE notes
that these voltage requirements are generally consistent with industry
test procedures for other commercial air conditioning and heat pump
equipment. Accordingly, DOE is proposing to adopt the voltage
requirements in Section 5.8.1 AHRI 390-2021, consistent with the
existing voltage requirements, as enumerated in section 0 of the
proposed Appendix G and in section 0 of the proposed Appendix G1.
e. Filter Requirements
DOE noted in the July 2018 RFI that Section 5.2.2.a of ANSI/AHRI
390-2003 requires that non-filtered ducted equipment be tested at the
minimum ESP specified in Table 4 of ANSI/AHRI 390-2003 plus an
additional 0.08 inches of water column (``in H2O'') of ESP.
83 FR 34499, 34501 (July 20, 2018). DOE further noted that ANSI/AHRI
390-2003 does not define ``non-filtered equipment.'' Id. As part of the
July 2018 RFI, DOE requested comment on whether any SPVUs are designed
to be installed without a filter. Id. at 83 FR 34499, 34502. DOE also
requested comment on the typical effectiveness (i.e., minimum
efficiency reporting value (``MERV'') rating) of filters provided with
SPVUs. Id. DOE requested comment on whether non-ducted SPVUs intended
for installation with a filter are ever tested without a filter
installed and, if so, how such testing has accounted for the filter
pressure drop to better represent actual performance. Id.
AHRI and Lennox commented that all SPVUs on the market are designed
to be installed with a filter, are shipped with a filter, and should be
tested with the supplied filter. (AHRI, No. 5 at p. 4; Lennox, No. 6 at
p. 3) AHRI added that the effectiveness of the filter can vary based on
application. (AHRI, No. 5 at p. 4) AHRI also stated that all SPVUs on
the market are tested with a filter. Id. NEEA and NWPCC commented that
SPVUs are used primarily in commercial buildings, and that ASHRAE
Standard 52.2, ``Method of Testing General Ventilation Air-Cleaning
Devices for Removal Efficiency by Particle Size,'' recommends MERV 8
filters for commercial buildings. Consequently, NEEA and NWPCC
recommended that SPVUs be tested with a MERV 8 filter rating to be
representative of equipment use in the field. (NEEA, NWPCC, No. 7 at p.
2) GE commented that any test procedure change requiring the addition
of a filter would increase test burden and product development cost.
(GE, No. 3 at p. 2) GE stated that filter types, sometimes specified by
local or State requirements, differ and that there is a risk of
unintended test variation depending upon the filter specified. Id. GE
stated that such variation could result in erroneous enforcement test
results. Id. GE also commented that it opposes any test procedure
change that potentially could dictate product design requirements, such
as filter selection. Id.
Section 3.19 of AHRI 390-2021 includes a definition for the term
``Standard Filter'' and requires that an SPVU must be tested with the
filter designated by the manufacturer in the marketing materials for
the model as the ``default'' or ``standard'' filter in Table 2, and
does not allow for testing without a filter. Section 5.7.3.1 of AHRI
390-2021 states that if the manufacturer does not specify a ``default''
or ``standard'' filter option, then the Standard Filter is the filter
with the lowest level of filtration, as specified in the marketing
materials for the model. If the marketing materials do not specify a
Standard Filter, or do not specify which filter option has the lowest
filtration level, then the Standard Filter is any filter shipped by the
manufacturer for that model.
In light of the above, DOE preliminarily concludes that a 0.08 in
H2O increase in the minimum ESP for units tested without a
filter is not necessary in the SPVU test procedure because, based on a
review of equipment on the market and supported by the comments from
AHRI and Lennox, DOE finds that all SPVUs are designed to be installed
with a filter, are shipped with a filter, and are tested with a filter.
In response to NEEA and NWPCC, DOE identified many SPVUs that offered
filters with lower filtration than MERV 8 filters, so requiring them
may not be representative of all field applications. In addition, based
on a review of equipment on the market, different manufacturers might
specify different filters as ``standard'' (i.e., there is not a single
filter type recognized as ``standard'' by the industry). Manufacturers
might also market an SPVU with multiple filter options from which the
consumer can choose.
DOE has, therefore, initially determined that the requirement to
test with a filter and the provisions on filter selection would provide
more representative results by testing with a filter that is more
likely to be used by a consumer in the field and is consistent with how
manufacturers are currently testing. In this NOPR, DOE proposes to
adopt the provisions in Section 3.19 and Table 2 in AHRI 390-2021 for
testing with the Standard Filter, as enumerated in section 0 of the
proposed Appendix G and section 0 of the proposed Appendix G1.
f. External Static Pressure and Airflow Requirements
SPVUs include fans that circulate indoor air over a heat exchanger
and provides heating or cooling either through ductwork or directly to
the conditioned space. To deliver sufficient conditioned air to the
intended space, the airflow provided by the unit must overcome pressure
losses throughout duct work (if present), and to a smaller degree,
within the unit itself. Pressure losses are the result of directional
changes in the ductwork, friction between the moving air and surfaces
of the ductwork, and possible appurtenances in the airflow path.
Further, different modes of operation may require different amounts of
airflow. Therefore, indoor fan speed is typically adjustable to assure
that the provided airflow rate is appropriate for the field-installed
ductwork system serving the building in which the unit is installed.
The performance of an SPVU can be significantly affected by variation
in ESP or operation with an indoor airflow that is different from the
intended or designed airflow. To ensure that a test procedure provides
results that are representative of an average-use cycle, appropriate
airflow settings for testing and ESP requirements are needed to reflect
the typical pressure losses. Such specifications would also contribute
to the repeatability of the test procedure.
i. External Static Pressure
As part of the July 2018 RFI, DOE noted that Table 4 of ANSI/AHRI
390-2003 specifies the minimum ESP required for testing ducted SPVUs
based on capacity range. DOE sought comments on whether the minimum ESP
requirements in ANSI/AHRI 390-2003 are representative of field
[[Page 2503]]
operation for ducted SPVUs, and if not, comment and data on what
representative minimum ESP levels would be. 83 FR 34499, 34502 (July
20, 2018).
The CA IOUs, as well as ASAP, NRDC, and ACEEE, commented that the
minimum ESP requirements in the test procedure may be significantly
lower than typical ESPs in the field, which would significantly
underestimate fan power consumption. (CA IOUs, No. 2 at pp. 2-3; ASAP,
NRDC, and ACEEE, No. 4 at p. 3) ASAP, NRDC, and ACEEE commented that
DOE should ensure that the minimum ESP requirements specified in the
SPVU test procedure adequately reflect conditions in the field. (ASAP,
NRDC, and ACEEE, No. 4 at p. 3) NEEA and NWPCC added that the ASRAC
Working Group for commercial package air conditioners recommended that
DOE develop minimum ESP requirements for SPVUs that adequately
represent performance in the field and that provide accurate
information to consumers to make purchasing decisions. (NEEA and NWPCC,
No. 7 at pp. 1-2)
NEEA and NWPCC stated that for CUACs, there is inconsistency
between the range of ESPs specified in the test procedure (0.2 to 0.75
in H2O) compared to the range of ESPs used for the analysis
for the standards rulemaking (0.75 and 1.25 in H2O). (NEEA
and NWPCC, No. 7 at p. 2) NEEA and NWPCC stated that if the ESP
requirements in the test procedure are lower than those typically found
in the field, the ratings of SPVUs will provide neither an adequate
representation of actual efficiency nor accurate information to
consumers. Id. NEEA and NWPCC added that the ESP requirements should
have no impact on test burden since there would be no change to how the
test is conducted. Id.
The CA IOUs referenced the minimum ESP requirement of 0.5 in
H2O for residential central air conditioners and heat pumps
with capacities less than 65,000 Btu/h, as specified in 10 CFR part
430, subpart B, appendix M1, ``Uniform Test Method for Measuring the
Energy Consumption of Central Air Conditioners and Heat Pumps,'' and
commented that DOE should align all other heating, ventilating, and air
conditioning (``HVAC'') equipment, including SPVUs, with the values
specified in Appendix M1, which increase in ESP based on corresponding
increases in cooling capacity. (CA IOUs, No. 2 at pp. 2-3)
AHRI commented that based on conversations with company application
engineers, the minimum ESP requirements specified in ANSI/AHRI 390-2003
are representative of field operation for ducted SPVUs installed with
10 feet of ductwork or less. (AHRI, No. 5 at p. 4) Lennox also stated
that the current ESP requirements are representative of field operation
for ducted SPVUs. (Lennox, No. 6 at p. 4) No commenter provided data as
to the ESPs experienced in field operation.
In response, DOE notes the range of comments received as to the
appropriate ESP for testing. AHRI 390-2021 maintained the same minimum
ESP requirements as specified in ANSI/AHRI 390-2003. DOE does not have
data indicating that these minimum ESP requirements are
unrepresentative of field operation for ducted SPVUs. DOE also
recognizes that SPVUs are typically installed in smaller modular
buildings with different duct configurations. As a result, DOE notes
that minimum ESP requirements for other equipment (e.g., CACs, CUACs)
may not be relevant for SPVUs. DOE also notes that in the previous
standards rulemaking the ESP values were aligned with the values used
in the test procedure. As a result, DOE does not expect there to be
inconsistency between the test procedure and the analysis conducted for
the standards rulemaking. Based on this, DOE is tentatively not
proposing to revise the ESP requirements in the DOE test procedure for
SPVUs but to instead remain consistent with AHRI 390-2021.
Issue 5: DOE welcomes data and information on ESP conditions
experienced in field operation of ducted SPVUs.
ii. Airflow Rate
Full-Load Cooling Test
DOE noted in the July 2018 RFI that ANSI/AHRI 390-2003 does not
specify tolerances on achieving the rated airflow or the minimum ESP
during testing. As discussed previously, the performance of an air
conditioner or heat pump can be affected by variations in airflow and
ESP. In the July 2018 RFI, DOE noted that the current DOE test
procedure for CUACs requires that the indoor airflow for the full-load
cooling test be within 3 percent of the rated airflow and
specifies a tolerance of -0.00/+0.05 in H2O for the ESP
requirements. 83 FR 34499, 34502 (July 20, 2018). DOE also noted that
in DOE's test procedure for CAC/HPs, the method for setting indoor air
volume rate for ducted units without variable-speed constant-air-
volume-rate indoor fans is a multi-step process that addresses the
discrete-step fan speed control of these units. Id. In this method, (a)
the air volume rate during testing may not be higher than the certified
air volume rate, but may be up to 10 percent less, and (b) the ESP
during testing may not be lower than the minimum specified ESP, but may
be higher than the minimum if this is required to avoid having the air
volume rate overshoot its certified value. 10 CFR part 430, subpart B,
appendix M, section 3.1.4.2.a. As part of the July 2018 RFI, DOE
requested information on the different types of indoor air fan drive
systems that are used for SPVUs and information on appropriate
tolerances for setting airflow and ESP. 83 FR 34499, 34502 (July 20,
2018).
On this topic, AHRI stated that SPVUs use permanent split-capacitor
motors with discrete speed settings or electronically-commutated motors
with variable speed settings; and that in either case, the unit leaves
the factory with the fan and motor set at a specific speed to provide
the rated performance. (AHRI, No. 5 at p. 4) Lennox commented that its
equipment uses motors and controls with speed/airflow settings
developed for each specific product and mode of operation, which are
factory pre-set to optimize performance. (Lennox, No. 6 at p. 4) Lennox
stated that for its equipment, the manufacturer-specified airflow
setting should allow the ability to set the airflow to the specified
value while meeting the ESP requirements for testing. Id. Lennox
further commented that the manufacturer settings should be used for
testing. Id. Lennox stated that if the minimum ESP cannot be
maintained, the airflow should be set to the maximum airflow while
maintaining the required ESP. Id.
AHRI commented that the then-draft version of AHRI 390 directed use
of the manufacturer-specified fan control settings for all tests for
which they are provided. (AHRI, No. 5 at p. 4) AHRI also commented that
the draft version of AHRI 390 directed use of the full-load cooling fan
control settings specified by the manufacturer for all tests for which
fan control settings are specified, and if there are no specified fan
control settings for any tests, use the as-shipped fan control settings
for all tests. Id. AHRI added that for testing, the priority is setting
the correct airflow speed, and the ESP is adjusted to match the
required airflow. Id. AHRI noted that the draft version of AHRI 390
provided that the airflow-measuring apparatus should be adjusted to
maintain ESP within -0/+0.05 in H2O of the required minimum
ESP and to maintain the airflow within 3 percent of the
manufacturer-specified full-load cooling airflow. Id.
DOE notes that AHRI 390-2021 specifies an airflow tolerance of
3
[[Page 2504]]
percent of the full-load cooling airflow. This would be consistent with
the test procedure for other commercial air conditioning and heat pump
equipment, and it would ensure that the rated airflow remains
representative of field use during testing. Therefore, DOE has
tentatively concluded that the 3 percent airflow tolerance
included in AHRI 390-2021 is appropriate for testing SPVUs.
Accordingly, DOE proposes to adopt the full-load cooling airflow
tolerance specified in Section 5.7 of AHRI 390-2021.
AHRI 390-2021 also includes additional instructions for how to set
indoor airflow if the airflow and ESP tolerances cannot be maintained
simultaneously. For non-ducted units, ducting is not installed in the
field; therefore, increasing ESP (which simulates the resistance to
airflow from longer duct length in the field) beyond the specified
tolerance of -0/+0.05 in H2O during testing would not be
representative of field application. Consequently, if both the ESP and
airflow cannot be maintained within tolerance during the test, Section
5.7.3.3.4 of AHRI 390-2021 specifies that the ESP be maintained within
the required tolerance and an airflow as close to the certified value
as possible be used.
For ducted units, if ESP and/or airflow are higher than the
tolerance range at the lowest fan control setting (e.g., lowest fan
speed), maintaining airflow within tolerance should take precedence
over maintaining ESP within tolerance. This is because operating with
an airflow higher than the certified value would likely result in an
airflow (and thus measured efficiency) that is unrepresentative of
field operation. Section 5.7.3.4.1.2 of AHRI 390-2021 specifies that
the airflow-measuring apparatus be adjusted to maintain airflow within
tolerance and to operate with the lowest possible ESP that meets the
minimum requirement. If ESP or airflow are lower than the tolerance
range at the maximum fan control setting (e.g., highest fan speed),
maintaining ESP at or above the minimum value should take precedence
over maintaining airflow within tolerance because operating with an ESP
lower than the minimum value does not reflect typical duct lengths (or
measured efficiency) in field application. In such a case, Section
5.7.3.4.1.3 of AHRI 390-2021 specifies that the airflow-measuring
apparatus be adjusted to maintain ESP within tolerance and to operate
with an airflow as close as possible to the certified value.
DOE understands the provisions regarding tolerances and priority
for adjustment of fan speed and ESP in AHRI 390-2021 are consistent
with the methodology in the draft version of AHRI 390, as evidenced by
the excerpt provided in AHRI's comments (AHRI, No. 5 at p. 5). DOE
preliminarily finds that these provisions would not conflict with any
provisions in the current DOE test procedure, and would improve test
repeatability and provide test conditions that are more representative
of those during operation in the field. Based on this, DOE is proposing
to adopt the provisions specified in Section 5.7.3 of AHRI 390-2021 for
setting indoor airflow if the airflow and ESP tolerances cannot be
maintained simultaneously, as enumerated in section 0 of the proposed
Appendix G and section 0 of the proposed Appendix G1.
Heating Test
DOE noted in the July 2018 RFI that ANSI/AHRI 390-2003 does not
distinguish between cooling and heating airflow rates required for
testing. 83 FR 34499, 34502 (July 20, 2018). For SPVHPs with multiple-
speed or variable-speed indoor fans, the indoor airflow rate in heating
operation could be different from that in cooling operation. Id.
Different airflow rates may be used for heating and cooling operation
because of different indoor comfort needs in the heating season, and
there may be a minimum heating airflow rate for electrical resistance
heating safety that exceeds the cooling airflow rate. Id. DOE also
noted in the July 2018 RFI that, for CUAC heat pumps, DOE's current
test procedure requires that indoor airflow and ESP first be
established within required tolerances for the full-load cooling test
condition by adjusting both the unit under test and the test facility's
airflow-measuring apparatus (see 10 CFR part 431, subpart F, appendix
A, section 6(ii)). 83 FR 34499, 34502 (July 20, 2018)) The CUAC test
procedure further provides that, unless the unit is designed to operate
at different airflow rates for cooling and heating modes, if necessary,
the airflow-measuring apparatus (but not the unit under test) may be
adjusted to achieve an airflow in heating mode equal to the cooling
full-load airflow rate within the specified tolerance, without regard
to changes in ESP (see 10 CFR part 431, subpart F, appendix A, section
6(ii)). 83 FR 34499, 34502 (July 20, 2018).
As part of the July 2018 RFI, DOE requested comment on whether
provisions similar to those required for CUACs would be appropriate for
determining airflow rate and minimum ESP for heating mode tests for
SPVHPs. 83 FR 34499, 34502 (July 20, 2018). NEEA and NWPCC commented
that if SPVHPs operate at different airflow speeds for heating and
cooling, then SPVUs should be tested similar to CUACs, for which the
heating efficiency is evaluated at the unique heating airflow rate.
(NEEA and NWPCC, No. 7 at p. 3) Lennox commented that SPVHP airflow
rates for heating and cooling are generally the same, but that the test
procedure should not preclude using different airflow rates that could
provide benefits in performance. (Lennox, No. 6 at p. 4) AHRI added
that the draft version of AHRI 390 included procedures that provide for
a difference in the manufacturer-specified heating airflow and full-
load cooling airflow. (AHRI, No. 5 at pp. 4-5)
In response, DOE notes that AHRI 390-2021 includes provisions for
setting the heating airflow rate that are consistent with the excerpt
of the draft version of AHRI 390 provided in AHRI's comments, (AHRI,
No. 5 at p. 5), which allows for testing with a manufacturer-specified
heating airflow that is different than the full-load cooling airflow.
These provisions reflect that units may be designed to operate in the
field at a different heating airflow rate as compared to the cooling
airflow rate. Therefore, DOE is proposing to adopt Sections 5.7.2.3 and
5.7.3.4.2 of AHRI 390-2021 with regards to setting the airflow and ESP
for heating tests (as applicable), as enumerated in section 0 of the
proposed Appendix G and section 0 of proposed Appendix G1.
2. Air Temperature Measurements
Measurement of air conditions is a critical aspect of performance
testing for air-conditioning and heat pump equipment generally. The air
conditions affect performance (both capacity and power input), and the
primary methods for determination of capacity rely on measurements of
air temperature and humidity. ANSI/ASHRAE 390-2003 references ANSI/
ASHRAE Standard 37-1988, ``Methods of Testing for Rating Unitary Air-
Conditioning and Heat Pump Equipment'' (``ANSI/ASHRAE 37-1988'') for
methods of testing SPVUs. As relevant here, ANSI/ASHRAE 37-1988
provides specifications for temperature sensors (section 5.1), as well
as for ensuring measurement uniformity (section 8.5).
DOE noted in the July 2018 RFI that, for air-cooled and
evaporatively-cooled CUACs, AHRI 340/360-2015 provides more extensive
direction for condenser air temperature measurement in its Appendix C,
including specifications to use air sampling trees and psychrometers,
temperature measurement accuracy requirements,
[[Page 2505]]
and other specifications to ensure that the measured conditions are
representative of average condenser air inlet conditions. 83 FR 34499,
34503 (July 20, 2018). In the July 2018 RFI, DOE requested comment on
whether requirements similar to AHRI 340/360-2015 should be adopted for
testing SPVUs. Id.
DOE also noted in the July 2018 RFI that while Appendix C of AHRI
340/360-2015 provides detailed direction for measurement of entering
outdoor air temperature, it provides no such direction for measurement
of entering indoor air temperature, indoor leaving air temperature, or
outdoor leaving air temperature. 83 FR 34499, 34503 (July 20, 2018).
However, these parameters have a significant impact on performance of
an SPVU as measured by the indoor air enthalpy method and the outdoor
air enthalpy method. Id. Therefore, in the July 2018 RFI, DOE also
requested comment on whether the requirements contained in Appendix C
of AHRI 340/360-2015 would be appropriate for measurement of these
parameters when testing SPVUs. Id.
The CA IOUs, NEEA and NWPCC supported using provisions similar to
Appendix C of AHRI 340/360-2015 to measure indoor air entering and
leaving temperatures, as well as outdoor air entering and leaving
temperatures. (CA IOUs, No. 2 at p. 2; NEEA and NWPCC, No. 7 at p. 3)
NEEA and NWPCC added that this would result in the most accurate and
repeatable test measurement. (NEEA and NWPCC, No. 7 at p. 3) AHRI
commented that adding measurement requirements for indoor air entering
and leaving temperatures, as well as outdoor air entering and leaving
temperatures for water slinger systems (i.e., units that use condensate
from the evaporator to enhance condenser cooling), similar to those in
Appendix C of AHRI Standard 340/360-2015 would be appropriate. (AHRI,
No. 5 at p. 6) Lennox commented that further evaluation of various SPVU
configurations is needed to determine appropriateness of the provisions
in Appendix C of AHRI 340/360-2015. (Lennox, No. 6 at p. 5)
In the interim, AHRI 390-2021 has addressed this issue.
Specifically, Appendix D of AHRI 390-2021 includes a comprehensive set
of provisions to measure air temperatures, including the measurement of
entering indoor temperature, indoor leaving temperature, entering
outdoor temperature, and outdoor leaving temperature. DOE notes that
these additional requirements were also included in the revised AHRI
340/360-2019. Specifically, AHRI 390-2021 includes the following
requirements:
Measurements of indoor and outdoor air entering dry-bulb
temperatures and water vapor conditions. In addition, measurement of
the indoor air leaving dry-bulb temperatures and water vapor conditions
if the indoor air enthalpy method is used, and outdoor air leaving dry-
bulb temperatures and water vapor conditions if the outdoor air
enthalpy method is used;
Temperature measurement accuracies and display resolutions
for dry-bulb and wet-bulb temperatures, as well as thermopile
temperatures;
Methods of water vapor measurement using either an
aspirating psychrometer or a dew point hygrometer;
Air sampling tree specifications, including construction
provisions, hole density requirements, average air velocity of the flow
area, and thermopile arrangement;
Description of the test set-up for air sampling trees,
which includes defining the arrangement of the face area, the number of
aspirating psychrometers per unit side, the location of the air
sampling trees and their coverage of the entrance to the unit, and the
number of sampling trees per aspirating psychrometer;
Dry-bulb temperature measurement using psychrometer dry-
bulb sensors;
Wet-bulb or dew point temperature measurements to
determine air water vapor content using psychrometers or hygrometers;
Measurements of temperature change and pressure drop
across the conduit used to transfer air from air samplers to
psychrometers and, if certain thresholds are exceeded, provisions for
determining dry-bulb temperature and atmospheric pressure (used to
calculate humidity ratio);
Specifications for dry-bulb and wet-bulb temperature
uniformity;
Additional specifications for measuring air conditions
entering the indoor coil, including provisions for returning sampled
air to the room, conditions for temperature uniformity specifications,
and directions if air is sampled within a duct; and
Additional specifications for measuring both indoor coil
and outdoor coil leaving air conditions, including conditions for
temperature uniformity requirements, provisions for returning sampled
air to the duct leaving the coil, provisions if the coil has a blow-
through fan, and additional requirements for the air sampling tree.
DOE has tentatively determined that the air measurement provisions
of AHRI 390-2021 in Appendix D address the lack of specificity in the
current DOE test procedure for SPVUs, improve temperature uniformity
and ensure accurate and repeatable temperature measurements for SPVUs,
and ensure that representative conditions are maintained during
testing. Therefore, DOE is proposing to adopt the provisions for
measurement of air conditions in Appendix D of AHRI 390-2021 both into
section 1 of the proposed Appendix G and into section 1 of the proposed
Appendix G1. Inclusion in AHRI 390-2021 and AHRI's comments in support
indicate that the proposed air measurement specifications are
considered best practice by industry and reflect current industry
practice. As such, DOE would expect that adoption of the air
measurement specifications in AHRI 390-2021 would present minimal, if
any, increase in test burden for manufacturers.
3. Defrost Energy Use
In the July 2018 RFI, DOE noted that SPVHPs generally include a
defrost cycle to periodically defrost the outdoor coil when operating
in outdoor ambient conditions in which frost collects on it during
heating operation. 83 FR 34499, 34504 (July 20, 2018). Based on
preliminary DOE review of product literature, the time between defrost
cycles can be between 30 and 90 minutes, and typical defrost cycle
duration is approximately 10 minutes. Id. During the defrost cycle, the
SPVHP is consuming energy but is not providing heat to the conditioned
space, unless it also energizes auxiliary heat during defrost. Id.
The current Federal test procedure for SPVUs is based on testing in
outdoor air conditions for which defrost is not necessary (i.e., 47
[deg]F outdoor air dry-bulb temperature). This means that any
differences in defrost cycle performance between different SPVHP models
is not reflected in the heating mode metric (i.e., COP). DOE noted in
the July 2018 RFI that the DOE test procedure for CACs/HPs includes
measurement of average delivered heat and total energy use (including
for defrost cycles) during operation in outdoor conditions for which
frost forms on the outdoor coil. Id. In contrast, DOE's test procedures
for commercial heat pumps do not include consideration of defrost. Id.
In the July 2018 RFI, DOE requested information regarding the types of
buildings most commonly served by SPVHPs, as well as the annual heating
and cooling loads for such buildings. Id. DOE also requested
information on the impact on heating mode efficiency associated with
the defrost cycle for SPVHPs, including
[[Page 2506]]
impacts associated with the potential use of resistance heating during
defrost. Id.
On this topic, the CA IOUs stated that relocatable classrooms
commonly utilize SPVUs. The CA IOUs suggested that DOE should consider
the CA Public Utilities Commission building prototype for relocatable
classrooms.\12\ This prototype provides typical dimensions, plug loads,
lighting, occupancy schedule, envelope characteristics, and thermostat
set points of relocatable classrooms which allows for the modeling of
annual cooling and heating loads. (CA IOUs, No. 2 at p. 4) The CA IOUs
stated that this building prototype was based on the Lawrence Berkeley
National Laboratory study titled ``High-Performance Commercial
Buildings Project'' from 2003.\13\ Id.
---------------------------------------------------------------------------
\12\ The CA Public Utilities Commission (CPUC) building
prototype for relocation classrooms is available as part of the
CPUC's Database for Energy Efficiency Resources, available at:
https://www.deeresources.com/.
\13\ Selkowitz, Stephen, High Performance Commercial Building
Systems. Prepared by the Lawrence Berkeley National Laboratory for
the California Energy Commission. LBNL-53538 (October 2003)
(Available at: https://www.osti.gov/servlets/purl/821762).
---------------------------------------------------------------------------
ASAP, NRDC, and ACEEE commented that DOE should incorporate defrost
and performance at lower ambient temperatures in the heating efficiency
metric. (ASAP, NRDC, and ACEEE, No. 4 at p. 2) ASAP, NRDC, and ACEEE
stated that incorporating defrost would allow the test procedure to
better reflect actual heating capacity and efficiency in the field,
thereby providing better information to consumers and encouraging
manufacturers to develop innovative defrost strategies. Id. ASAP, NRDC,
and ACEEE also encouraged DOE to incorporate performance at lower
ambient temperatures into the metric for heating efficiency. Id. SPVHPs
typically include back-up electric resistance heating, which is used
when the heat pump cannot meet the heating load. ASAP, NRDC, and ACEEE
stated that because the test procedure only requires testing SPVHPs at
47 [deg]F outdoor air dry-bulb temperature for heating mode, it does
not differentiate the ability of equipment to maintain good heating
capacity using the heat pump cycle at low ambient temperatures, as
opposed to shutting the heat pump cycle off and switching to electric
resistance heating. Id. According to ASAP, NRDC, and ACEEE,
incorporating performance at lower ambient temperatures in the heating
efficiency metric would encourage equipment designs that maintain
efficiency performance at low ambient temperatures, which will
ultimately benefit consumers. Id.
NEEA and NWPCC commented that the frequency of defrost cycles
varies between manufacturers and that the defrost cycle typically stays
on for approximately 10 minutes. (NEEA and NWPCC, No. 7 at p. 4) NEEA
and NWPCC recommended decreasing the efficiency rating by a given
increment based on average annual defrost energy use for the default
defrost cycle frequency setting. Id. NEEA and NWPCC stated that this
would likely lead to manufacturers reducing the frequency of their
default defrost cycles, which would result in energy savings for
building applications that do not need frequent defrost cycles. Id.
AHRI and Lennox commented that they respectively estimated that
fewer than 30 and 20 percent of SPVUs are heat pumps, and they argued
that DOE's proposal to include provisions to measure the average
delivered heat and total energy use, including for defrost cycles,
during operation in outdoor conditions for which frost forms on the
outdoor coil is not necessary for this equipment. (AHRI, No. 5 at p. 9;
Lennox, No. 6 at p. 6) AHRI added that the electric heat used during
defrost is small in comparison to electric heat use when the heat pump
cannot keep up to meet the heating load. (AHRI, No. 5 at p. 9)
DOE notes that AHRI 390-2021 does not include provisions for
measuring defrost energy for SPVHPs. Consistent with ANSI/AHRI 390-
2003, AHRI 390-2021, and DOE's test procedures for other commercial
heat pumps, DOE is not proposing to include provisions for including
the defrost energy of SPVHPs. DOE notes that the study the CA IOUs
cited only monitored relocatable classrooms within the State of
California and does not encompass the different types of SPVU
installations or operating conditions. At this time, DOE lacks
sufficient information on the number of SPVHP installations by building
type and geographical region, as well as information regarding the
frequency of operation of defrost cycles or representative low ambient
conditions during field use and the annual heating and cooling loads in
those installations, which would be needed to determine whether such
testing conditions would be appropriate for SPVUs and to develop a
metric representing the national average for SPVUs.
Issue 6: DOE requests comment and data on the number of SPVHP
installations by building type and geographical region and the annual
heating and cooling loads for such buildings. DOE also requests data on
the frequency of operation of defrost cycles and representative low
ambient conditions for those buildings and installations.
4. Outdoor Air Enthalpy Method
As discussed previously, the current DOE test procedure, which
incorporates by reference ANSI/AHRI 390-2003, also references ANSI/
ASHRAE 37-1988 for methods of testing SPVUs. Section 7.2 of ANSI/ASHRAE
37-1988 specifies primary and secondary capacity measurements for
equipment with cooling capacities less than 135,000 Btu/h.
Specifically, the indoor air enthalpy method must be used as the
primary method for capacity measurement, and Table 3 of ANSI/ASHRAE 37-
1988 specifies the applicable options for selecting a secondary method.
The two test methods must agree within 6 percent (see Section 10.1.2 of
ANSI/ASHRAE 37-1988).
DOE noted in the July 2018 RFI that the outdoor air enthalpy test
method is commonly used as the secondary test method for determining
capacity for SPVUs. 83 FR 34499, 34502-34503 (July 20, 2018). The
outdoor air enthalpy method specified in ANSI/ASHRAE 37-1988 specified
the use of an air-side test apparatus that is connected to the unit
under test. However, the airflow and operating conditions achieved with
the outdoor air-side test apparatus connected may differ from those
achieved without the apparatus connected. Therefore, Section 8.5 of
ANSI/ASHRAE 37-1988 (which is referenced by ANSI/AHRI 390-2003)
specifies testing both with and without the air-side test apparatus
connected. Id. at 83 FR 34503. ANSI/ASHRAE 37-1988 specifies first
conducting a one-hour preliminary test without the outdoor air-side
test apparatus connected, followed by a second one-hour test with the
outdoor air-side test apparatus connected. Id. The second test (with
the outdoor air-side test apparatus connected) serves as the official
test. Id. ANSI/ASHRAE 37-1988 further provides that there must be
agreement of the evaporating and condensing temperatures between the
two tests for a valid test. Id.
DOE further noted in the July 2018 RFI that in a test procedure
final rule for CACs/HPs (82 FR 1426 (Jan. 5, 2017)), DOE amended its
test procedure requirements for use of the outdoor air enthalpy method
as the secondary test method for capacity measurement for CAC/HPs. 83
FR 34499, 34503 (July 20, 2018). DOE's test procedure for CAC/HPs had
previously included provisions similar to those in ANSI/ASHRAE 37-
[[Page 2507]]
1988: The preliminary test was conducted without the outdoor air-side
test apparatus connected, and the official test was conducted with the
outdoor air-side test apparatus connected, with a requirement to
achieve agreement of the evaporating and condensing temperatures
between the two tests. For CAC/HPs, DOE determined that testing with
the outdoor air-side test apparatus connected introduced more
variability to the test results when compared to testing without the
apparatus connected, and that test variability could be reduced by
shifting to an approach in which the official test is the one without
the apparatus connected. See 82 FR 1426, 1508-1509 (Jan. 5. 2017). As
part of the July 2018 RFI, DOE requested comment on whether
modifications to the requirements for using the outdoor air enthalpy
method as the secondary method for testing SPVUs (similar to those made
for CAC/HPs) would be appropriate, including that the official test be
conducted without the outdoor air-side test apparatus connected. 83 FR
34499, 34503 (July 20, 2018).
The CA IOUs commented that the outdoor air enthalpy method should
be used as the secondary method for testing SPVUs and agreed that the
official test should be conducted without the outdoor air-side test
apparatus connected. (CA IOUs, No. 2 at p. 2) AHRI commented that the
AHRI 390 committee was reviewing the secondary capacity measurement
methods. (AHRI, No. 5 at p. 6) AHRI stated that after that evaluation
is complete, it would recommend conducting the official test without
the outdoor air-side test apparatus connected. Id. Lennox commented
that further evaluation of the secondary capacity measurements is
needed, but it stated that secondary methods using refrigerant flow
require altering the system to place the flowmeter into the refrigerant
system and, therefore, could significantly alter performance. (Lennox,
No. 6 at p. 5)
Since the time of the July 2018 RFI, AHRI 390-2021 was adopted, and
that test method includes provisions in Section E5 consistent with
those adopted in the January 2017 CAC/HP TP final rule. More
specifically, AHRI 390-2021 requires that the official test be the one
in which the outdoor air side test apparatus is not connected. For the
same reasons DOE presented in the January 2017 CAC/HP TP final rule and
discussed previously, DOE has preliminarily determined that the
provisions in AHRI 390-2021 would better represent field use of SPVUs
and improve test repeatability and reproducibility. For these reasons,
DOE proposes to adopt the capacity measurements specified in Section E5
of AHRI 390-2021, into section 1 of the proposed Appendix G and into
section 1 of the proposed Appendix G1. DOE has tentatively determined
that this proposal would impose only minimal additional burden to
manufacturers and would not require retesting of units because the
existing test results contain the data necessary for the capacity
measurements as specified in Section E5 of AHRI 390-2021.
F. Configuration of Unit Under Test
1. Specific Components
An ASRAC working group for certain commercial heating, ventilating,
and air conditioning (``HVAC'') equipment (``Commercial HVAC Working
Group''),\14\ which included SPVUs, submitted a term sheet
(``Commercial HVAC Term Sheet'') providing the Commercial HVAC Working
Group's recommendations. (Docket No. EERE-2013-BT-NOC-0023, No. 52)
\15\ The Commercial HVAC Working Group recommended that DOE issue
guidance under current regulations on how to test certain equipment
features when included in a basic model, until such time as the testing
of such features can be addressed through a test procedure rulemaking.
The Commercial HVAC Term Sheet listed the subject features under the
heading ``Equipment Features Requiring Test Procedure Action.'' (Id at
pp. 3-9) The Commercial HVAC Working Group also recommended that DOE
issue an enforcement policy stating that DOE would exclude certain
equipment with specified features from Departmental testing, but only
when the manufacturer offers for sale at all times a model that is
identical in all other features; otherwise, the model with that feature
would be eligible for Departmental testing. These features were listed
under the heading ``Equipment Features Subject to Enforcement Policy.''
(Id. at pp. 9-15)
---------------------------------------------------------------------------
\14\ In 2013, ASRAC formed the Commercial HVAC Working Group to
engage in a negotiated rulemaking effort regarding the certification
of certain commercial HVAC equipment, including SPVUs. The
Commercial HVAC Working Group's recommendations are available at
www.regulations.gov under Docket No. EERE-2013-BT-NOC-0023-0052.
\15\ Available at www.regulations.gov/document/EERE-2013-BT-NOC-0023-0052.
---------------------------------------------------------------------------
On January 30, 2015, DOE issued a Commercial HVAC Enforcement
Policy addressing the treatment of specific features during
Departmental testing of commercial HVAC equipment. (See www.energy.gov/gc/downloads/commercial-equipment-testing-enforcement-policies.) The
Commercial HVAC Enforcement Policy stated that--for the purposes of
assessment testing pursuant to 10 CFR 429.104, verification testing
pursuant to 10 CFR 429.70(c)(5), and enforcement testing pursuant to 10
CFR 429.110--DOE would not test a unit with one of the optional
features listed for a specified equipment type if a manufacturer
distributes in commerce an otherwise identical unit that does not
include one of the optional features. (Id at p. 1) The objective of the
Commercial HVAC Enforcement Policy is to ensure that each basic model
has a commercially-available version eligible for DOE testing, meaning
that each basic model includes either a model without the optional
feature(s) or a model with the optional features that is eligible for
testing. Id. The features in the Commercial HVAC Enforcement Policy for
SPVUs (Id. at pp. 3-4) align with the Commercial HVAC Term Sheet's list
designated ``Equipment Features Subject to Enforcement Policy.''
AHRI 390-2021 includes Appendix F, ``Unit Configuration for
Standard Efficiency Determination--Informative.'' Section F1.3 of AHRI
390-2021 includes a list of features that are optional for testing.
Section F1.3 of AHRI 390-2021 further specifies the following general
provisions regarding testing of units with optional features:
If an otherwise identical model (within the basic model)
without the feature is not distributed in commerce, conduct tests with
the feature according to the individual provisions specified in Section
F1.3 of AHRI 390-2021.
For each optional feature, Section F1.3 of AHRI 390-2021
includes explicit instructions on how to conduct testing for equipment
with the optional feature present.
The optional features provisions in AHRI 390-2021 are generally
consistent with DOE's Commercial HVAC Enforcement Policy, but the
optional features in Section F1.3 of AHRI 390-2021 do not entirely
align with the list of features included for SPVUs in the Commercial
HVAC Enforcement Policy. The list of optional features in section F1.3
includes five features that are not present in the Commercial HVAC
Enforcement Policy for SPVUs: (1) Fresh air dampers; (2) barometric
relief dampers; (3) power correction capacitors; (4) hail guards, and
(5) UV lights. All five of these features in Section F1.3 are included
for SPVUs in the ``Equipment Features Requiring Test Procedure Action''
section of the Commercial HVAC Term Sheet. Therefore, DOE has
tentatively concluded that their inclusion as
[[Page 2508]]
optional features for SPVUs is appropriate.
DOE notes that the list of features and provisions in Section F1.3
of Appendix F of AHRI 390-2021 conflates features that can be addressed
by testing provisions with features that warrant enforcement relief
(i.e., features that, if present on a unit under test, could have a
substantive impact on test results and that cannot be disabled or
otherwise mitigated). This differentiation was central to the
Commercial HVAC Term Sheet, which as noted previously, included
separate lists for ``Equipment Features Requiring Test Procedure
Action'' and ``Equipment Features Subject to Enforcement Policy,'' and
remains central to providing clarity in DOE's regulations. Further,
provisions more explicit than included in Section F1.3 of AHRI 390-2021
are warranted to clarify the differences between how specific
components must be treated when manufacturers are making
representations as opposed to when DOE is conducting enforcement
testing.
In order to provide clarity between test procedure provisions
(i.e., how to test a specific unit) and certification and enforcement
provisions (e.g., which model to test), DOE is not proposing to adopt
Appendix F of AHRI 390-2021 and instead is proposing related provisions
in 10 CFR 429.43, 10 CFR 429.134, and 10 CFR part 431, subpart F,
Appendix G1. Specifically, in Appendix G1, DOE proposes test provisions
for specific components, including all of the components listed in
Section F1.3 which there is a neutralizing test procedure action (i.e.,
test procedure provisions specific to the component that are not
addressed by general provisions in AHRI 390-2021 that negates the
components impact on performance).\16\ These provisions would specify
how to test a unit with such a component--i.e., for a unit with hail
guards, remove hail guards for testing. These proposed test provisions
are consistent with the provision in Section F1.3 of AHRI 390-2021, but
include revisions for further clarity and specificity (e.g., adding
clarifying provisions for how to test units with modular economizers as
opposed to units shipped with economizers installed).
---------------------------------------------------------------------------
\16\ For the following components listed in Section F1.3 of AHRI
390-2021, DOE has tentatively concluded that there is not a
neutralizing test procedure action specified in Section F1.3 of AHRI
390-2021 for testing a unit with the component present, and is,
therefore, not proposing to include test procedure actions specific
to these components in Appendix G1: Powered Exhaust/Powered Return
Air Fans and Hot Gas Bypass.
---------------------------------------------------------------------------
Consistent with the Commercial HVAC Term Sheet and the Commercial
HVAC Enforcement Policy, DOE is proposing provisions that would allow
determination of represented values of a model equipped with a
particular component to be based on an individual model distributed in
commerce without the component in specific cases. The provisions apply
to certain components for which the test provisions for testing a unit
with the component may result in differences in ratings compared to
testing a unit without the component.\17\ For these such components,
DOE proposes in 10 CFR 429.43(a)(4) that:
---------------------------------------------------------------------------
\17\ DOE has tentatively concluded that for the following
features included in Section F1.3 of AHRI 390-2021, testing a unit
with these components in accordance with the proposed test
provisions would not result in differences in ratings compared to
testing a unit without these components; therefore, DOE is not
proposing to include these features in 10 CFR 429.43(a)(4): UV
lights, Power Correction Capacitors, Hail Guards, Barometric Relief
Dampers, and Fresh Air Dampers.
---------------------------------------------------------------------------
If a basic model includes only individual models
distributed in commerce with a specific component, or does not include
any otherwise identical individual models without the specific
component, the manufacturer must determine represented values for the
basic model based on performance of an individual model with the
component present (and consistent with any relevant proposed test
procedure provisions in Appendix G1).
If a basic model includes both individual models
distributed in commerce with a specific component and otherwise
identical individual models without the specific component, the
manufacturer may determine represented values for the basic model based
on performance of an individual model either with the component present
(and consistent with any relevant proposed test procedure provisions in
Appendix G1) or without the component present.
DOE notes that in some cases, individual models may include more
than one of the specified components (i.e., both an economizer and
dehumidification components) or there may be individual models within a
basic model that include various dehumidification components that
result in more or less energy use. In these cases, the represented
values of performance must be representative of the lowest efficiency
found within the basic model.
Also consistent with the Commercial HVAC Term Sheet and the
Commercial HVAC Enforcement Policy, DOE is proposing provisions in 10
CFR 429.134(s)(1) regarding how DOE would assess compliance for basic
models that include individual models distributed in commerce with air
economizers or dehumidification components. Specifically:
If a basic model includes only individual models
distributed in commerce with a specific component, or does not include
any otherwise identical individual models without the specific
component, DOE may assess compliance for the basic model based on
testing an individual model with the component present (and consistent
with any relevant proposed test procedure provisions in Appendix G1).
If a basic model includes both individual models
distributed in commerce with a specific component and otherwise
identical individual models without the specific component, DOE will
assess compliance for the basic model based on testing of an otherwise
identical model within the basic model that does not include the
component; except if DOE is not able to obtain such a model for
testing. In such a case, DOE will assess compliance for the basic model
based on testing of an individual model with the specific component
present (and consistent with any relevant proposed test procedure
provisions in Appendix G1).
Were DOE to adopt the provisions in 10 CFR 429.43, 10 CFR 429.134,
and 10 CFR part 431, subpart F, appendix G1 as proposed, DOE would
rescind the Commercial HVAC Enforcement Policy to the extent it is
applicable to SPVUs. In a separate certification rulemaking, DOE may
consider certification reporting requirements such that manufacturers
would be required to certify which otherwise identical models are used
for making representations of basic models that include individual
models with specific components.
Issue 7: DOE requests comment on its proposal regarding specific
components in 10 CFR 429.43, 10 CFR 429.134, and 10 CFR part 431,
subpart F, Appendices G and G1.
G. Represented Values
1. Multiple Refrigerants
DOE recognizes that some commercial package air conditioning and
heating equipment may be sold with more than one refrigerant option
(e.g., R-410A or R-407C). Typically, manufacturers specify a single
refrigerant in their literature for each unique model, but in its
review, DOE has identified at least one commercial package air
conditioning and heating equipment manufacturer that provides two
refrigerant options under the same model number. The refrigerant chosen
[[Page 2509]]
by the customer in the field installation may impact the energy
efficiency of a unit. For this reason, DOE is proposing representation
requirements specific for models approved for use with multiple
refrigerants. So that the proposals in this NOPR would only require
manufacturers to update representations once, DOE proposes to align the
compliance date for these representation requirements with the proposed
metric change (i.e., these proposals would only be required when
certifying to amended standards denominated in terms of IEER, if
adopted).
Use of a refrigerant (such as R-407C as compared to R-410A) that
requires different hardware (i.e., compressors, heat exchangers, or air
moving systems that are not the same or comparably performing) would
represent a different basic model, and according to the current CFR,
separate representations of energy efficiency are required for each
basic model. 10 CFR 429.43(a). On the other hand, some refrigerants
(such as R-422D and R-427A) would not require different hardware, and a
manufacturer may consider them to be the same basic model, per DOE's
current definition for ``basic model at 10 CFR 431.92. In the latter
case of an SPVU with multiple refrigerant options that do not require
different hardware, DOE proposes that a manufacturer determine the
represented values (for example, IEER, COP, and cooling capacity) based
on the refrigerant(s)--among all refrigerants listed on the unit's
nameplate--that results in the lowest cooling efficiency. These
represented values would apply to the basic model with the use of all
refrigerants specified by the manufacturer.
Issue 8: DOE requests comment on its proposal regarding
representations for SPVU models approved for use with multiple
refrigerants.
2. Cooling Capacity
For SPVUs, cooling capacity determines equipment class, which in
turn determines the applicable energy conservation standard. 10 CFR
431.97. While cooling capacity is a required represented value for
SPVUs, DOE does not currently specify provisions for SPVUs regarding
how close the represented value of cooling capacity must be to the
tested or alternative energy-efficiency determination method (``AEDM'')
simulated cooling capacity, or whether DOE will use measured or
certified cooling capacity to determine equipment class for enforcement
testing. In contrast, at paragraphs (a)(1)(iv) and (a)(2)(ii) of 10 CFR
429.43 and paragraph (g) of 10 CFR 429.134, DOE specifies such
provisions regarding the cooling capacity for air-cooled CUACs. Again,
because energy conservation standards for SPVUs are dependent on
cooling capacity, inconsistent approaches to the application of cooling
capacity between basic models could result in inconsistent
determinations of equipment class and, in turn, inconsistent
applications of the energy conservation standards.
For these reasons, DOE is proposing to add to its regulations the
following provisions regarding cooling capacity for SPVUs: (1) A
requirement that the represented cooling capacity be between 95 percent
and 100 percent of the tested or AEDM-simulated cooling capacity; and
(2) an enforcement provision stating that DOE would use the mean of
measured cooling capacity values from testing, rather than the
certified cooling capacity, to determine the applicable standards.
First, DOE proposes to require in 10 CFR 429.43(a)(3)(v)(B) that
the represented value of cooling capacity must be between 95 percent
and 100 percent of the mean of the cooling capacity values measured for
the units in the sample (if determined through testing), or between 95
percent and 100 percent of the cooling capacity output simulated by an
AEDM. This tolerance would help to ensure that equipment is capable of
performing at the cooling capacity for which it is represented to
commercial consumers, while also enabling manufacturers to
conservatively rate the cooling capacity to allow for minor variations
in the capacity measurements from different units tested at different
laboratories.
Second, DOE is proposing in its product-specific enforcement
provisions at 10 CFR 429.134(s)(1) that the cooling capacity of each
tested unit of the basic model will be measured pursuant to the test
requirements of part 431 and that the mean of the measurement(s) will
be used to determine the applicable standard with which the model must
comply.
As discussed in this section, applicable energy conservation
standards for SPVUs are dependent on the rated cooling capacity. DOE
has tentatively concluded that these proposals would result in more
accurate ratings of cooling capacity, and ensure appropriate
application of the energy conservation standards, while still providing
flexibility for manufacturers to conservatively rate cooling capacity
so that they can be confident the equipment is capable of delivering
the cooling capacity represented to commercial consumers.
Issue 9: DOE requests comment on its proposals related to
represented values and verification testing of cooling capacity for
SPVUs.
H. Test Procedure Costs and Impact
As stated, EPCA requires that the test procedures for commercial
package air conditioning and heating equipment, which includes SPVUs,
be those generally accepted industry testing procedures or rating
procedures developed or recognized by AHRI or by ASHRAE, as referenced
in ASHRAE Standard 90.1. (42 U.S.C. 6314(a)(4)(A)) Further, if such an
industry test procedure is amended, DOE must amend its test procedure
to be consistent with the amended industry test procedure, unless DOE
determines, by rule published in the Federal Register and supported by
clear and convincing evidence, that such amended test procedure would
not meet the requirements in 42 U.S.C. 6314(a)(2) and (3) related to
representative use and test burden. (42 U.S.C. 6314(a)(4)(B))
In this NOPR, DOE proposes to amend the existing test procedure for
SPVUs by: (1) Incorporating by reference the updated version of the
applicable industry test method, AHRI 390-2021, including the energy
efficiency descriptors; (2) adding definitions for ``single-phase
single package vertical air conditioner with cooling capacity less than
65,000 Btu/h'' and ``single-phase single package vertical heat pump
with cooling capacity less than 65,000 Btu/h'' to clarify which single-
phase equipment with cooling capacity less than 65,000 Btu/h are
properly classified as SPVU rather than CAC; (3) specifying provisions
for specific components; and (4) further specifying the requirements
for determination of represented values for cooling capacity and for
models approved for use with multiple refrigerants.
DOE has tentatively determined that these proposed amended test
procedures would be representative of an average use cycle and would
not be unduly burdensome for manufacturers to conduct. Based on review
of AHRI 390-2021, DOE expects that the proposed test procedure in
Appendix G for measuring EER and COP would not increase testing costs
per unit compared to the current DOE test procedure, which DOE
estimates to be $3,100 for SPVACs and $3,700 for SPVHPs per unit for
third-party lab testing. DOE estimates that the cost for third-party
lab testing according to the proposed Appendix G1 for measuring IEER
and COP to be $4,900 for SPVACs and $5,500 for SPVHPs per unit.
DOE further notes that manufacturers are not required to perform
laboratory testing on all basic models. In
[[Page 2510]]
accordance with 10 CFR 429.70 of DOE's regulations, SPVU manufacturers
may elect to use AEDMs. An AEDM is a computer modeling or mathematical
tool that predicts the performance of non-tested basic models. These
computer modeling and mathematical tools, when properly developed, can
provide a means to predict the energy usage or efficiency
characteristics of a basic model of a given covered product or
equipment and reduce the burden and cost associated with testing. DOE
estimates the per-manufacturer cost to develop and validate an AEDM for
SPVU equipment to be $15,800. DOE estimates an additional cost of
approximately $50 per basic model \18\ for determining energy
efficiency using the validated AEDM.
---------------------------------------------------------------------------
\18\ DOE estimated initial costs to validate an AEDM assuming 80
hours of general time to develop an AEDM based on existing
simulation tools and 16 hours to validate two basic models within
that AEDM at the cost of an engineering technician wage of $50 per
hour plus the cost of third-party physical testing of two units per
validation class (as required in 10 CFR 429.70(c)(2)(iv)). DOE
estimated the additional per basic model cost to determine
efficiency using an AEDM assuming 1 hour per basic model at the cost
of an engineering technician wage of $50 per hour.
---------------------------------------------------------------------------
As discussed in section II of this NOPR, the proposed test
procedure provisions regarding IEER would not be mandatory unless and
until DOE adopts energy conservation standards that specify IEER as the
regulatory metric and compliance with such standards is required. Given
that most SPVU manufacturers are AHRI members and that DOE is
referencing the prevailing industry test procedure that was established
for use in AHRI's certification program (which DOE presumes will be
updated to include IEER), DOE expects that manufacturers will already
be testing using the IEER test method. Based on this, DOE has
tentatively determined that the proposed test procedure amendments
would not be expected to increase the testing burden on most SPVU
manufacturers. Additionally, DOE has tentatively determined that the
test procedure amendments, if finalized, would not require
manufacturers to redesign any of the covered equipment, would not
require changes to how the equipment is manufactured, and would not
impact the utility of the equipment.
Issue 10: DOE requests comment on its understanding of the impact
of the test procedure proposals in this NOPR, specifically DOE's
initial conclusion that the proposed DOE test procedure amendments, if
finalized, would not increase testing burden on SPVU manufacturers, as
compared to current industry practice indicated by AHRI 390-2021.
I. Reserved Appendices for Test Procedures for Commercial Air
Conditioning and Heating Equipment
DOE proposes to amend its test procedures for SPVUs and to relocate
those test procedures to new Appendix G and Appendix G1 to 10 CFR part
431, subpart F. This proposed reorganization of the SPVU test
procedures would be consistent with the organization of the test
procedures for other covered equipment and covered products. DOE has
tentatively concluded that providing the test procedures for specific
equipment in a designated appendix would improve the readability of the
test procedure. Further, DOE proposes to make the provisions currently
in 10 CFR 431.96(c) and (e) specific to SPVUs in 10 CFR part 431,
subpart F, Appendices G and G1, thereby eliminating the references to
test procedures for other equipment. To provide for future
consideration of a similar reorganization for other commercial package
air conditioning and heating equipment test procedures, DOE is
proposing to reserve Appendices B through F under 10 CFR part 431,
subpart F. The reserved appendices are presented to facilitate any
future reorganization of the regulations and are not an indication of
any substantive changes to the respective test procedures at this time.
Any such reorganization of test procedures for the equipment identified
in the proposed reserved appendices would be addressed in separate
rulemakings.
J. Compliance Dates
EPCA prescribes that, if DOE amends its test procedure for covered
commercial package air-conditioning and heating equipment (including
SPVUs), all representations of energy efficiency and energy use,
including those made on marketing materials and product labels, must be
made in accordance with that amended test procedure, beginning 360 days
after publication of such a test procedure final rule in the Federal
Register. (42 U.S.C. 6314(d)(1))
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget (``OMB'') has determined that
this test procedure rulemaking does not constitute ``significant
regulatory actions'' under section 3(f) of Executive Order (``E.O.'')
12866, Regulatory Planning and Review, 58 FR 51735 (Oct. 4, 1993).
Accordingly, this action was not subject to review under the Executive
order by the Office of Information and Regulatory Affairs (``OIRA'') in
OMB.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of an initial regulatory flexibility analysis (``IRFA'')
for any rule that by law must be proposed for public comment, unless
the agency certifies that the rule, if promulgated, will not have a
significant economic impact on a substantial number of small entities.
As required by Executive Order 13272, ``Proper Consideration of Small
Entities in Agency Rulemaking,'' 67 FR 53461 (August 16, 2002), DOE
published procedures and policies on February 19, 2003, to ensure that
the potential impacts of its rules on small entities are properly
considered during the DOE rulemaking process. 68 FR 7990. DOE has made
its procedures and policies available on the Office of the General
Counsel's website: www.energy.gov/gc/office-general-counsel. DOE
reviewed this proposed rule to amend the test procedures for SPVUs
under the provisions of the Regulatory Flexibility Act and the policies
and procedures published on February 19, 2003.
The following sections detail DOE's IRFA for this test procedure
rulemaking.
1. Description of Reasons Why Action Is Being Considered
DOE is proposing to amend the existing DOE test procedures for
SPVUs. DOE must update the Federal test procedures to be consistent
with the updated industry consensus test procedure, unless DOE
determines by rule published in the Federal Register and supported by
clear and convincing evidence, that the industry update would not be
representative of an average use cycle or would be unduly burdensome to
conduct. (42 U.S.C. 6314(a)(4)(B))
2. Objective of, and Legal Basis for, Rule
EPCA, as amended, requires that the test procedures for commercial
package air conditioning and heating equipment, which includes SPVUs,
be those generally accepted industry testing procedures or rating
procedures developed or recognized by AHRI or by ASHRAE, as referenced
in ASHRAE Standard 90.1. (42 U.S.C. 6314(a)(4)(A)) Further, if such an
industry test procedure is amended, DOE must amend its test procedure
to be consistent with the amended industry test procedure, unless DOE
determines,
[[Page 2511]]
by rule published in the Federal Register and supported by clear and
convincing evidence, that such amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2) and (3) related to
representative use and test burden. (42 U.S.C. 6314(a)(4)(B))
EPCA also requires that, at least once every 7 years, DOE must
evaluate test procedures for each type of covered equipment including
SPVUs, to determine whether amended test procedures would more
accurately or fully comply with the requirements for the test
procedures to not be unduly burdensome to conduct and be reasonably
designed to produce test results that reflect energy efficiency, energy
use, and estimated operating costs during a representative average use
cycle. (42 U.S.C. 614(a)(1)(A))
Once completed, the current rulemaking will satisfy both of these
legal requirements of EPCA.
3. Description and Estimate of Small Entities Regulated
DOE uses the Small Business Administration (``SBA'') small business
size standards to determine whether manufacturers qualify as ``small
businesses,'' which are listed by the North American Industry
Classification System (``NAICS'').\19\ The SBA considers a business
entity to be small business if, together with its affiliates, it
employs less than a threshold number of workers specified in 13 CFR
part 121.
---------------------------------------------------------------------------
\19\ Available at: www.sba.gov/document/support-table-size-standards.
---------------------------------------------------------------------------
SPVU manufacturers, who produce the equipment covered by this rule,
are classified under NAICS code 333415, ``Air-Conditioning and Warm Air
Heating Equipment and Commercial and Industrial Refrigeration Equipment
Manufacturing.'' In 13 CFR 121.201, the SBA sets a threshold of 1,250
employees or fewer for an entity to be considered as a small business
for this category. This employee threshold includes all employees in a
business's parent company and any other subsidiaries.
DOE reviewed the test procedures proposed in this NOPR under the
provisions of the Regulatory Flexibility Act and the procedures and
policies published on February 19, 2003. The Department conducted a
focused inquiry into small business manufacturers of the equipment
covered by this rulemaking. DOE used publicly available information to
identify potential small businesses that manufacture SPVUs
domestically. DOE identified manufacturers using DOE's Compliance
Certification Database (``CCD''),\20\ the California Energy
Commission's Modernized Appliance Efficiency Database System
(``MAEDbS''),\21\ and prior rulemakings. Additionally, DOE used
publicly-available information and subscription-based market research
tools (e.g., reports from Dun & Bradstreet \22\). As a result of this
inquiry, DOE identified a total of eight companies that are
manufacturers or private labelers of SPVUs in the United States. DOE
screened out companies that do not meet the definition of a ``small
business'' or are foreign-owned and operated. Of these eight SPVU
manufacturers or private labelers, DOE identified three potential small
businesses.
---------------------------------------------------------------------------
\20\ DOE's Compliance Certification Database is available at:
www.regulations.doe.gov/ccms (last accessed September 1, 2021).
\21\ California Energy Commission's MAEDbS is available at
cacertappliances.energy.ca.gov/Pages/ApplianceSearch.aspx (last
accessed September 1, 2021).
\22\ Dun & Bradstreet reports are available at:
app.dnbhoovers.comI (last access September 1, 2021).
---------------------------------------------------------------------------
Two of the three small businesses are original equipment
manufacturers (``OEM'') of the SPVUs each small business sells. The
third small business is not an OEM of the SPVUs they sell. Instead, it
rebrands its SPVU models which are supplied by a different OEM (i.e.,
making the small business a private labeler). Of the two OEM small
businesses, one is a member of AHRI and the other is not a member of
AHRI. The private labeler small business is not a member of AHRI.
4. Description and Estimate of Compliance Requirements
DOE assumed each small business would have different potential
regulatory costs depending on if they are an OEM and if they are a
member of AHRI. DOE assumed all AHRI members, including small
businesses, will be testing their SPVU models in accordance with AHRI
390-2021, the industry test procedure DOE is proposing to reference,
and using AHRI's certification program, which DOE presumes will be
updated to include the IEER metric. Therefore, the proposed test
procedure amendments would not add testing burden to SPVU manufacturers
that are or will be using the AHRI 390-2021 test procedure for their
SPVU models, including one of the identified small businesses.
DOE assumed the small business that is not an OEM of the SPVU
models they sell (i.e., the private labeler) does not pay for the
testing costs for the rebranded SPVU models they sell because the test
performance of the rebranded SPVU models is identical to the SPVU
models the OEM sells. Therefore, DOE does not anticipate that any non-
OEMs, including this small business, incur any testing burden to sell
rebranded SPVU models.
Lastly, while DOE assumed that all SPVU manufacturers will be using
the industry test procedure, AHRI 390-2021, DOE estimated the potential
testing costs for the small business that is an OEM but is not an AHRI
member. This small business would only incur additional testing costs
if that small business will not be using the AHRI 390-2021 to test
their SPVU models. This one small business manufactures six SPVU basic
models.
As previously stated in section III.H of this NOPR, DOE estimated
that the cost for third-party lab testing according to the proposed
appendix G1 for measuring IEER and COP to be $4,900 for SPVACs and
$5,500 for SPVHPs per unit. If SPVU manufacturers conduct physical
testing to certify a SPVU basic model, two units are required to be
tested per basic model. However, manufacturers are not required to
perform laboratory testing on all basic models, as SPVU manufacturers
may elect to use AEDMs.\23\ An AEDM is a computer modeling or
mathematical tool that predicts the performance of non-tested basic
models. These computer modeling and mathematical tools, when properly
developed, can provide a means to predict the energy usage or
efficiency characteristics of a basic model of a given covered product
or equipment and reduce the burden and cost associated with testing.
---------------------------------------------------------------------------
\23\ In accordance with 10 CFR 429.70.
---------------------------------------------------------------------------
When developing cost estimates, DOE considered the cost to develop
an AEDM, the costs to validate the AEDM through physical testing, and
the cost per model to determine ratings using the AEDM. DOE estimated
the cost to develop and validate an AEDM for SPVUs to be approximately
$15,800, which includes physical testing of two models per validation
class.\24\ Additionally, DOE estimated a cost of approximately $50 per
basic model for determining energy efficiency using the validated AEDM.
In the case of the single small, non-AHRI member, the estimated cost to
rate the remaining four basic models with the AEDM would be
[[Page 2512]]
$200.\25\ Based on these estimates, the small SPVU manufacturer that is
an OEM and not a member of AHRI would incur $16,000 to test and rate
all six of its SPVU models.
---------------------------------------------------------------------------
\24\ $4,800 (AEDM development and validation costs) + $5,500
(per-unit physical testing costs) x (units required for physical
testing per validation class) = $15,800. AEDM development ad
validation costs are based on 96 hours of development and testing
using an engineering technician wage of $50 per hour. This estimate
utilizes the more costly SPVHP testing cost of $5,500 per unit.
\25\ $50 (per-unit rating cost) x 4 (remaining units) = $200.
---------------------------------------------------------------------------
Market research tools report that company's annual revenue to be
approximately $1.3 million. The cost to re-rate all model would be
approximately 1.2 percent of annual revenue for that small
manufacturer.\26\
---------------------------------------------------------------------------
\26\ $16,000 (costs) / $1,300,000 (annual revenue) = 1.2% of
annual revenue.
---------------------------------------------------------------------------
Issue 11: DOE requests comment on the number of small businesses
DOE identified. DOE also requests comment on the potential cost
estimates for each small business identified, compared to current
industry practice, as indicated by AHRI 390-2021.
5. Duplication, Overlap, and Conflict With Other Rules and Regulations
DOE is not aware of any rules or regulations that duplicate,
overlap, or conflict with the rule being considered.
6. Significant Alternatives to the Rule
DOE proposes to reduce burden on manufacturers, including small
businesses, by allowing AEDMs in lieu of physically testing all basic
models. The use of AEDMs is less costly than physical testing for
SPVUs. Without AEDMs, the cost for the small, non-AHRI-member to rate
all basic models would increase to $66,000.\27\
---------------------------------------------------------------------------
\27\ $5,500 (per-unit test cost) x 2 (units tested per model) x
6 (number of SPVU models) = $66,000. This estimate utilizes the more
costly SPVHP testing cost of $5,500 per unit.
---------------------------------------------------------------------------
Additionally, DOE considered alternative test methods and
modifications to the AHRI 390-2021 test procedure for SPVUs. However,
DOE has tentatively determined that there are no better alternatives
than the existing industry test procedures, in terms of both meeting
the agency's objectives and reducing burden on manufacturers.
Therefore, DOE is proposing to amend the existing DOE test procedure
for SPVUs through incorporation by reference of AHRI 390-2021.
Additional compliance flexibilities may be available through other
means. Manufacturers subject to DOE's energy efficiency standards may
apply to DOE's Office of Hearings and Appeals for exception relief
under certain circumstances. Manufacturers should refer to 10 CFR part
1003 for additional details.
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of SPVUs must certify to DOE that their products
comply with any applicable energy conservation standards. To certify
compliance, manufacturers must first obtain test data for their
products according to the DOE test procedures, including any amendments
adopted for those test procedures. DOE has established regulations for
the certification and recordkeeping requirements for all covered
consumer products and commercial equipment, including SPVUs. (See
generally 10 CFR part 429.) The collection-of-information requirement
for the certification and recordkeeping is subject to review and
approval by OMB under the Paperwork Reduction Act (``PRA''). This
requirement has been approved by OMB under OMB control number 1910-
1400. Public reporting burden for the certification is estimated to
average 35 hours per response, including the time for reviewing
instructions, searching existing data sources, gathering and
maintaining the data needed, and completing and reviewing the
collection of information.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
DOE is analyzing this proposed regulation in accordance with the
National Environmental Policy Act of 1969 (``NEPA'') and DOE's NEPA
implementing regulations (10 CFR part 1021). DOE's regulations include
a categorical exclusion for rulemakings interpreting or amending an
existing rule or regulation that does not change the environmental
effect of the rule or regulation being amended. 10 CFR part 1021,
subpart D, appendix A5. DOE anticipates that this rulemaking qualifies
for categorical exclusion A5 because it is an interpretive rulemaking
that does not change the environmental effects of the rule and
otherwise meets the requirements for application of a categorical
exclusion. See 10 CFR 1021.410. DOE will complete its NEPA review
before issuing the final rule.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 10,
1999), imposes certain requirements for agencies formulating and
implementing policies or regulations that preempt State law or that
have federalism implications. The Executive order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR 13735. DOE has examined this
proposed rule and has determined that it would not have a substantial
direct effect on the States, on the relationship between the national
government and the States, or on the distribution of power and
responsibilities among the various levels of government. EPCA governs
and prescribes Federal preemption of State regulations as to energy
conservation for the products that are the subject of this proposed
rule. States can petition DOE for exemption from such preemption to the
extent, and based on criteria, set forth in EPCA. (42 U.S.C. 6297(d))
No further action is required by Executive Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (Feb. 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity; (2) write regulations to
minimize litigation; (3) provide a clear legal standard for affected
conduct rather than a general standard, and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that Executive agencies make every reasonable
effort to ensure that the regulation: (1) Clearly specifies the
preemptive effect, if any; (2) clearly specifies any effect on existing
Federal law or regulation; (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction;
(4) specifies the retroactive effect, if any; (5) adequately defines
key terms, and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to review regulations in light of applicable standards in
sections 3(a) and 3(b) to determine whether they are met or it is
unreasonable to meet one or more of them. DOE has completed the
required
[[Page 2513]]
review and determined that, to the extent permitted by law, the
proposed rule meets the relevant standards of Executive Order 12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (``UMRA'')
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a proposed regulatory action likely to result in a rule that may
cause the expenditure by State, local, and Tribal governments, in the
aggregate, or by the private sector of $100 million or more in any one
year (adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820; also available
at www.energy.gov/gc/office-general-counsel. DOE examined this proposed
rule according to UMRA and its statement of policy and determined that
the rule contains neither an intergovernmental mandate, nor a mandate
that may result in the expenditure of $100 million or more in any year,
so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This proposed rule would not have any impact on the autonomy or
integrity of the family as an institution. Accordingly, DOE has
concluded that it is not necessary to prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights,'' 53 FR 8859 (March 18, 1988), that this proposed regulation
would not result in any takings that might require compensation under
the Fifth Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (Feb. 22, 2002), and
DOE's guidelines were published at 67 FR 62446 (Oct. 7, 2002). Pursuant
to OMB Memorandum M-19-15, Improving Implementation of the Information
Quality Act (April 24, 2019), DOE published updated guidelines which
are available at www.energy.gov/sites/prod/files/2019/12/f70/DOE%20Final%20Updated%20IQA%20Guidelines%20Dec%202019.pdf. DOE has
reviewed this proposed rule under the OMB and DOE guidelines and has
concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any proposed significant energy
action. A ``significant energy action'' is defined as any action by an
agency that promulgated or is expected to lead to promulgation of a
final rule, and that: (1) Is a significant regulatory action under
Executive Order 12866, or any successor order; and (2) is likely to
have a significant adverse effect on the supply, distribution, or use
of energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any proposed significant energy action,
the agency must give a detailed statement of any adverse effects on
energy supply, distribution, or use should the proposal be implemented,
and of reasonable alternatives to the action and their expected
benefits on energy supply, distribution, and use.
The proposed regulatory action to amend the test procedure for
measuring the energy efficiency of SPVUs is not a significant
regulatory action under Executive Order 12866. Moreover, it would not
have a significant adverse effect on the supply, distribution, or use
of energy, nor has it been designated as a significant energy action by
the Administrator of OIRA. Therefore, it is not a significant energy
action, and, accordingly, DOE has not prepared a Statement of Energy
Effects.
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788;
``FEAA'') Section 32 essentially provides in relevant part that, where
a proposed rule authorizes or requires use of commercial standards, the
notice of proposed rulemaking must inform the public of the use and
background of such standards. In addition, section 32(c) requires DOE
to consult with the Attorney General and the Chairman of the Federal
Trade Commission (``FTC'') concerning the impact of the commercial or
industry standards on competition.
The proposed amendments to the Federal test procedure for SPVUs are
primarily in response to modifications to the applicable industry
consensus test standards (i.e., AHRI 390-2021 and ANSI/ASHRAE 37-2009).
DOE has evaluated these standards and is unable to conclude whether
they fully comply with the requirements of section 32(b) of the FEAA
(i.e., whether it was developed in a manner that fully provides for
public participation, comment, and review).DOE will consult with both
the Attorney General and the Chairman of the FTC concerning the impact
of these test procedures on competition, prior to prescribing a final
rule.
M. Description of Materials Incorporated by Reference
In this NOPR, DOE proposes to incorporate by reference the test
standard published by AHRI, titled ``Performance Rating of Single
Package Vertical Air-Conditioners and Heat Pumps,'' AHRI Standard 390-
2021. Specifically, the Federal test procedure proposed in this NOPR
would adopt sections 3 (except 3.1, 3.2, 3.5, 3.12, and 3.15), 5
(except section 5.8.5), 6 (except 6.1.1, 6.2, 6.3, 6.4, and 6.5),
Appendices A, D, and E of the industry test method. AHRI 390-2021 is an
industry-accepted
[[Page 2514]]
test procedure for measuring the performance of SPVUs. AHRI Standard
390-2021 is available online at www.ahrinet.org/search-standards.aspx.
In this NOPR, DOE also proposes to incorporate by reference the
test standard published by ASHRAE, titled ``Methods of Testing for
Rating Electrically Driven Unitary Air-Conditioning and Heat Pump
Equipment,'' ANSI/ASHRAE Standard 37-2009. ANSI/ASHRAE Standard 37-2009
is an industry-accepted test procedure for measuring the performance of
electrically driven unitary air-conditioning and heat pump equipment.
ANSI/ASHRAE Standard 37-2009 is available on ANSI's website at https://webstore.ansi.org/RecordDetail.aspx?sku=ANSI%2FASHRAE+Standard+37-2009.
In this NOPR, DOE also proposes to incorporate by reference the
test standard published by ASHRAE, titled ``Standard Methods For
Laboratory Airflow Measurement,'' ANSI/ASHRAE Standard 41.2-1987 (RA
92). ANSI/ASHRAE Standard 41.2-1987 (RA 92) is an industry-accepted
test procedure for consistent measurement procedures for use in the
preparation of other ASHRAE standards. Procedures described are used in
testing air-moving, air-handling, and air-distribution equipment and
components. ANSI/ASHRAE Standard 41.2-1987 (RA 92) is available on
ANSI's website at https://webstore.ansi.org/Standards/ASHRAE/ANSIASHRAE411987RA92.
The following standards, which appear in the regulatory text, were
previously approved for IBR and no changes are proposed: AHRI 210/240-
2008, AHRI 340/360-2007, AHRI 1230-2010, ASHRAE 127-2007, and ISO
Standard 13256-1 (1998).
V. Public Participation
A. Participation in the Webinar
The time and date of the webinar are listed in the DATES section at
the beginning of this document. Webinar registration information,
participant instructions, and information about the capabilities
available to webinar participants will be published on DOE's website:
www.energy.gov/eere/buildings/public-meetings-and-comment-deadlines.
Participants are responsible for ensuring their systems are compatible
with the webinar software.
B. Procedure for Submitting Prepared General Statements for
Distribution
Any person who has an interest in the topics addressed in this
notice, or who is representative of a group or class of persons that
has an interest in these issues, may request an opportunity to make an
oral presentation at the webinar/public meeting. Such persons may
submit requests to speak via email to the Appliance and Equipment
Standards Program at: [email protected]. Persons
who wish to speak should include with their request a computer file in
WordPerfect, Microsoft Word, PDF, or text (ASCII) file format that
briefly describes the nature of their interest in this rulemaking and
the topics they wish to discuss. Such persons should also provide a
daytime telephone number where they can be reached.
DOE requests persons selected to make an oral presentation to
submit an advance copy of their statements at least two weeks before
the webinar/public meeting. At its discretion, DOE may permit persons
who cannot supply an advance copy of their statement to participate, if
those persons have made advance alternative arrangements with the
Building Technologies Office. As necessary, requests to give an oral
presentation should ask for such alternative arrangements.
C. Conduct of the Webinar
DOE will designate a DOE official to preside at the webinar/public
meeting and may also use a professional facilitator to aid discussion.
The meeting will not be a judicial or evidentiary-type public hearing,
but DOE will conduct it in accordance with section 336 of EPCA (42
U.S.C. 6306). A court reporter will be present to record the
proceedings and prepare a transcript. DOE reserves the right to
schedule the order of presentations and to establish the procedures
governing the conduct of the webinar/public meeting. There shall not be
discussion of proprietary information, costs or prices, market share,
or other commercial matters regulated by U.S. anti-trust laws. After
the webinar/public meeting and until the end of the comment period,
interested parties may submit further comments on the proceedings and
any aspect of the rulemaking.
The webinar will be conducted in an informal, conference style. DOE
will present summaries of comments received before the webinar/public
meeting, allow time for prepared general statements by participants,
and encourage all interested parties to share their views on issues
affecting this rulemaking. Each participant will be allowed to make a
general statement (within time limits determined by DOE), before the
discussion of specific topics. DOE will permit, as time permits, other
participants to comment briefly on any general statements.
At the end of all prepared statements on a topic, DOE will permit
participants to clarify their statements briefly and comment on
statements made by others. Participants should be prepared to answer
questions posed by DOE and by other participants concerning these
issues. DOE representatives may also ask questions of participants
concerning other matters relevant to this rulemaking. The official
conducting the webinar/public meeting will accept additional comments
or questions from those attending, as time permits. The presiding
official will announce any further procedural rules or modification of
the above procedures that may be needed for the proper conduct of the
webinar/public meeting.
A transcript of the webinar/public meeting will be included in the
docket, which can be viewed as described in the Docket section at the
beginning of this document. In addition, any person may buy a copy of
the transcript from the transcribing reporter.
D. Submission of Comments
DOE will accept comments, data, and information regarding this
proposed rule no later than the date provided in the DATES section at
the beginning of this proposed rule. Interested parties may submit
comments using any of the methods described in the ADDRESSES section at
the beginning of this document.
DOE has historically provided a 75-day comment period for test
procedure NOPRs pursuant to the North American Free Trade Agreement,
U.S.-Canada-Mexico (``NAFTA''), Dec. 17, 1992, 32 I.L.M. 289 (1993);
the North American Free Trade Agreement Implementation Act, Public Law
103-182, 107 Stat. 2057 (1993) (codified as amended at 10 U.S.C.A.
2576) (1993) (``NAFTA Implementation Act''); and Executive Order 12889,
``Implementation of the North American Free Trade Agreement,'' 58 FR
69681 (Dec. 30, 1993). However, on July 1, 2020, the Agreement between
the United States of America, the United Mexican States, and the United
Canadian States (``USMCA''), Nov. 30, 2018, 134 Stat. 11 (i.e., the
successor to NAFTA), went into effect, and Congress's action in
replacing NAFTA through the USMCA Implementation Act, 19 U.S.C. 4501 et
seq. (2020), implies the repeal of E.O. 12889 and its 75-day comment
period requirement for technical regulations. Thus, the controlling
laws are EPCA and the USMCA Implementation Act. Consistent with EPCA's
public comment
[[Page 2515]]
period requirements for consumer products, the USMCA only requires a
minimum comment period of 60 days. Consequently, DOE now provides a 60-
day public comment period for test procedure NOPRs.
Submitting comments via www.regulations.gov. The
www.regulations.gov web page will require you to provide your name and
contact information. Your contact information will be viewable to DOE
Building Technologies staff only. Your contact information will not be
publicly viewable except for your first and last names, organization
name (if any), and submitter representative name (if any). If your
comment is not processed properly because of technical difficulties,
DOE will use this information to contact you. If DOE cannot read your
comment due to technical difficulties and cannot contact you for
clarification, DOE may not be able to consider your comment.
However, your contact information will be publicly viewable if you
include it in the comment or in any documents attached to your comment.
Any information that you do not want to be publicly viewable should not
be included in your comment, nor in any document attached to your
comment. Persons viewing comments will see only first and last names,
organization names, correspondence containing comments, and any
documents submitted with the comments.
Do not submit to www.regulations.gov information for which
disclosure is restricted by statute, such as trade secrets and
commercial or financial information (hereinafter referred to as
Confidential Business Information (``CBI'')). Comments submitted
through www.regulations.gov cannot be claimed as CBI. Comments received
through the website will waive any CBI claims for the information
submitted. For information on submitting CBI, see the Confidential
Business Information section.
DOE processes submissions made through www.regulations.gov before
posting. Normally, comments will be posted within a few days of being
submitted. However, if large volumes of comments are being processed
simultaneously, your comment may not be viewable for up to several
weeks. Please keep the comment tracking number that www.regulations.gov
provides after you have successfully uploaded your comment.
Submitting comments via email. Comments and documents submitted via
email also will be posted to www.regulations.gov. If you do not want
your personal contact information to be publicly viewable, do not
include it in your comment or any accompanying documents. Instead,
provide your contact information in a cover letter. Include your first
and last names, email address, telephone number, and optional mailing
address. The cover letter will not be publicly viewable as long as it
does not include any comments.
Include contact information each time you submit comments, data,
documents, and other information to DOE. No telefacsimiles (faxes) will
be accepted.
Comments, data, and other information submitted to DOE
electronically should be provided in PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file format. Provide documents that
are not secured, written in English, and free of any defects or
viruses. Documents should not contain special characters or any form of
encryption, and, if possible, they should carry the electronic
signature of the author.
Campaign form letters. Please submit campaign form letters by the
originating organization in batches of between 50 to 500 form letters
per PDF or as one form letter with a list of supporters' names compiled
into one or more PDFs. This reduces comment processing and posting
time.
Confidential Business Information. Pursuant to 10 CFR 1004.11, any
person submitting information that he or she believes to be
confidential and exempt by law from public disclosure should submit via
email two well-marked copies: One copy of the document marked
``confidential'' including all the information believed to be
confidential, and one copy of the document marked ``non-confidential''
with the information believed to be confidential deleted. DOE will make
its own determination about the confidential status of the information
and treat it according to its determination.
It is DOE's policy that all comments may be included in the public
docket, without change and as received, including any personal
information provided in the comments (except information deemed to be
exempt from public disclosure).
E. Issues on Which DOE Seeks Comment
Although DOE welcomes comments on any aspect of this proposal, DOE
is particularly interested in receiving comments and views of
interested parties concerning the following issues:
Issue 1: DOE requests comment on its proposal to define ``single-
phase single package vertical air conditioner with cooling capacity
less than 65,000 Btu/h'' and ``single-phase single package vertical
heat pump with cooling capacity less than 65,000 Btu/h'' as subsets of
the broader SPVAC and SPVHP equipment category. DOE requests feedback
on the proposed characteristics that would distinguish this equipment
as SPVUs (i.e., ``weatherized'' or capable of utilizing a maximum of
400 CFM of outdoor air). Additionally, DOE requests comment on the
proposed method to validate that a unit is capable of providing 400 CFM
of outdoor air.
Issue 2: DOE requests comment on its proposal to adopt the test
methods specified in AHRI 390-2021 for calculating IEER for SPVUs.
Issue 3: DOE requests comment and data on ratings under the current
EER metric specified in 10 CFR 431.97 and ASHRAE 90.1-2019 based on
ANSI/AHRI 390-2003 as compared to ratings using the IEER metric under
AHRI 390-2021.
Issue 4: DOE requests comment on its proposal to clarify that COP
representations using the ``Low Temperature Operation, Heating''
conditions in Table 3 of AHRI 390-2021 are optional.
Issue 5: DOE welcomes data and information on ESP conditions
experienced in field operation of ducted SPVUs.
Issue 6: DOE requests comment and data on the number of SPVHP
installations by building type and geographical region and the annual
heating and cooling loads for such buildings. DOE also requests data on
the frequency of operation of defrost cycles and representative low
ambient conditions for those buildings and installations.
Issue 7: DOE requests comment on its proposal regarding specific
components in 10 CFR 429.43, 10 CFR 429.134, and 10 CFR part 431,
subpart F, appendices G and G1.
Issue 8: DOE requests comment on its proposal regarding
representations for SPVU models approved for use with multiple
refrigerants.
Issue 9: DOE requests comment on its proposals related to
represented values and verification testing of cooling capacity for
SPVUs.
Issue 10: DOE requests comment on its understanding of the impact
of the test procedure proposals in this NOPR, specifically DOE's
initial conclusion that the proposed DOE test procedure amendments, if
finalized, would not increase testing burden on SPVU manufacturers, as
compared to current industry practice indicated by AHRI 390-2021.
Issue 11: DOE requests comment on the number of small businesses
DOE
[[Page 2516]]
identified. DOE also requests comment on the potential cost estimates
for each small business identified, compared to current industry
practice, as indicated by AHRI 390-2021.
DOE also seeks comment on any other matter concerning the proposed
test procedures for SPVUs not already addressed by the specific areas
identified in this document. DOE particularly seeks information that
would ensure that the test procedure measures energy efficiency during
a representative average use cycle, as well as information that would
help DOE create a procedure that is not unduly burdensome to conduct.
VI. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this proposed
rule.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Reporting and
recordkeeping requirements, Small businesses.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation, Incorporation by reference, Reporting
and recordkeeping requirements.
Signing Authority
This document of the Department of Energy was signed on December
28, 2021, by Kelly J. Speakes-Backman, Principal Deputy Assistant
Secretary for Energy Efficiency and Renewable Energy, pursuant to
delegated authority from the Secretary of Energy. That document with
the original signature and date is maintained by DOE. For
administrative purposes only, and in compliance with requirements of
the Office of the Federal Register, the undersigned DOE Federal
Register Liaison Officer has been authorized to sign and submit the
document in electronic format for publication, as an official document
of the Department of Energy. This administrative process in no way
alters the legal effect of this document upon publication in the
Federal Register.
Signed in Washington, DC, on December 30, 2021.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
For the reasons stated in the preamble, DOE is proposing to amend
parts 429 and 431 of Chapter II of Title 10, Code of Federal
Regulations as set forth below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
2. Amend Sec. 429.4 by:
0
a. Revising paragraph (a);
0
b. Redesignating paragraph (c)(2) as paragraph (c)(3);
0
c. Adding new paragraph (c)(2);
0
d. Redesignating paragraphs (d), (e), and (f) as paragraphs (e), (f),
and (g); and
0
e. Adding new paragraph (d).
The revisions and additions read as follows.
Sec. 429.4 Materials incorporated by reference.
(a) Certain material is incorporated by reference into this part
with the approval of the Director of the Federal Register in accordance
with 5 U.S.C. 552(a) and 1 CFR part 51. To enforce any edition other
than that specified in this section, DOE must publish a document in the
Federal Register and the material must be available to the public. All
approved material is available for inspection at the U.S. Department of
Energy, Office of Energy Efficiency and Renewable Energy, Building
Technologies Program, Sixth Floor, 950 L'Enfant Plaza SW, Washington,
DC 20024, (202) 586-9127, [email protected], https://www.energy.gov/eere/buildings/building-technologies-office, and may be obtained from
the other sources in this section. It is also available for inspection
at the National Archives and Records Administration (NARA). For
information on the availability of this material at NARA, email:
[email protected], or go to: www.archives.gov/federal-register/cfr/ibr-locations.html.
* * * * *
(c) * * *
(2) AHRI Standard 390-2021, (``AHRI 390-2021''), 2021 Standard for
Performance Rating of Single Package Vertical Air-conditioners and Heat
Pumps, IBR approved for Sec. 429.134.
* * * * *
(d) ASHRAE. The American Society of Heating, Refrigerating and Air-
Conditioning Engineers. 180 Technology Parkway NW, Peachtree Corners,
GA 30092, (404) 636-8400, https://www.ashrae.org.
(1) ANSI/ASHRAE 37-2009, ``Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment'',
ASHRAE approved June 24, 2009. IBR approved for Sec. 429.134.
(2) ANSI/ASHRAE 41.2-1987 (RA 92), ``Standard Methods For
Laboratory Airflow Measurement'', ASHRAE approved October 1, 1987. IBR
approved for Sec. 429.134.
* * * * *
0
3. Amend Sec. 429.43 by adding paragraphs (a)(3) and (4) to read as
follows:
Sec. 429.43 Commercial heating, ventilating, air conditioning (HVAC)
equipment.
(a) * * *
(3) Product-specific provisions for determination of represented
values.
(i)-(vi) [Reserved]
(vii) Single Package Vertical Units. When certifying to standards
in terms of IEER, the following provisions apply.
(A) If a basic model is distributed in commerce and approved for
use with multiple refrigerants, a manufacturer must determine all
represented values for that basic model (for example, IEER, COP and
cooling capacity) based on the refrigerant that results in the lowest
cooling efficiency. A refrigerant is considered approved for use if it
is listed on the nameplate of the outdoor unit. Per the definition of
basic model in 10 CFR 431.92 of this chapter, use of a refrigerant that
requires different hardware (i.e., compressors, heat exchangers, or air
moving systems that are not the same or comparably performing), would
represent a different basic model, and separate representations would
be required for each basic model.
(B) The represented value of cooling capacity must be between 95
percent and 100 percent of the mean of the capacities measured for the
units in the sample selected as described in paragraph (a)(1)(ii) of
this section, or between 95 percent and 100 percent of the net sensible
cooling capacity output simulated by the AEDM as described in paragraph
(a)(2) of this section.
(C) Represented values must be based on performance (either through
testing or by applying an AEDM) of individual models with components
and features that are selected in accordance with section 3 of appendix
G1 to subpart F of part 431 of this chapter.
[[Page 2517]]
(4) Determination of represented values for individual models with
specific components for SPVUs.
(i) If a manufacturer distributes in commerce individual models
with one of the components listed in the following table, determination
of represented values is dependent on the selected grouping of
individual models into a basic model, as indicated in paragraphs
(a)(4)(ii) through (a)(4)(v) of this section. For the purposes of this
paragraph, ``otherwise identical'' means differing only in the presence
of specific components listed in table 1 to this paragraph (a)(4)(i).
Table 1--to Paragraph (a)(4)(i)
------------------------------------------------------------------------
Component Description
------------------------------------------------------------------------
Desiccant Dehumidification An assembly that reduces the moisture
Components. content of the supply air through
moisture transfer with solid or liquid
desiccants.
Air Economizers.............. An automatic system that enables a
cooling system to supply outdoor air to
reduce or eliminate the need for
mechanical cooling during mid or cold
weather.
Ventilation Energy Recovery An assembly that preconditions outdoor
System (VERS). air entering the equipment through
direct or indirect thermal and/or
moisture exchange with the exhaust air,
which is defined as the building air
being exhausted to the outside from the
equipment.
Steam/Hydronic Heat Coils.... Coils used to provide supplemental
heating.
Hot Gas Reheat............... A heat exchanger located downstream of
the indoor coil that heats the Supply
Air during cooling operation using high
pressure refrigerant in order to
increase the ratio of moisture removal
to Cooling Capacity provided by the
equipment.
Fire/Smoke/Isolation Dampers. A damper assembly including means to open
and close the damper mounted at the
supply or return duct opening of the
equipment.
Powered Exhaust/Powered A powered exhaust fan is a fan that
Return Air Fans. transfers directly to the outside a
portion of the building air that is
returning to the unit, rather than
allowing it to recirculate to the indoor
coil and back to the building. A powered
return fan is a fan that draws building
air into the equipment.
Sound Traps/Sound Attenuators An assembly of structures through which
the supply air passes before leaving the
equipment or through which the return
air from the building passes immediately
after entering the equipment for which
the sound insertion loss is at least 6
dB for the 125 Hz octave band frequency
range.
Hot Gas Bypass............... A method to adjust the cooling delivered
by the equipment in which some portion
of the hot high-pressure refrigerant
from the discharge of the compressor(s)
is diverted from its normal flow to the
outdoor coil and is instead allowed to
enter the indoor coil to modulate the
capacity of a refrigeration circuit or
to prevent evaporator coil freezing.
------------------------------------------------------------------------
(ii) If a basic model includes only individual models distributed
in commerce without a specific component listed in paragraph (a)(4)(i)
of this section, the manufacturer must determine represented values for
the basic model based on performance of an individual model distributed
in commerce without the component.
(iii) If a basic model includes only individual models distributed
in commerce with a specific component listed in paragraph (a)(4)(i) of
this section, the manufacturer must determine represented values for
the basic model based on performance of an individual model with the
component present (and consistent with any component-specific test
provisions specified in section 3 of appendix G1 to subpart F of part
431 of this chapter).
(iv) If a basic model includes both individual models distributed
in commerce with a specific component listed in paragraph (4)(i) of
this section and individual models distributed in commerce without that
specific component, and none of the individual models distributed in
commerce without the specific component are otherwise identical to any
individual model distributed in commerce with the specific component,
the manufacturer must consider the performance of individual models
with the component present when determining represented values for the
basic model (and consistent with any component-specific test provisions
specified in section 3 of appendix G1 to subpart F of part 431 of this
chapter).
(v) If a basic model includes both individual models distributed in
commerce with a specific component listed in paragraph (a)(4)(i) of
this section and individual models distributed in commerce without that
specific component, and at least one of the individual models
distributed in commerce without the specific component is otherwise
identical to any given individual model distributed in commerce with
the specific component, the manufacturer may determine represented
values for the basic model either:
(A) Based on performance of an individual model distributed in
commerce without the specific component, or
(B) Based on performance of an individual model with the specific
component present (and consistent with any component-specific test
provisions specified in section 3 of appendix G1 to subpart F of part
431 of this chapter).
(vi) In any of the cases specified in paragraphs (a)(4)(ii) through
(a)(4)(v) of this section, the represented values for a basic model
must be determined through either testing (paragraph (a)(1) of this
section) or an AEDM (paragraph(a)(2) of this section).
* * * * *
0
4. Amend Sec. 429.134 by adding paragraph (s) to read as follows:
Sec. 429.134 Product-specific enforcement provisions.
* * * * *
(s) Single package vertical air conditioners and heat pumps. The
following provisions apply for assessment and enforcement testing of
models subject to standards in terms of IEER.
(1) Verification of cooling capacity. The cooling capacity of each
tested unit of the basic model will be measured pursuant to the test
requirements of appendix G1 to subpart F of part 431 of this chapter.
The mean of the measurement(s) will be used to determine the applicable
standards for purposes of compliance.
(2) Specific Components. For basic models that include individual
models distributed in commerce with any of the specific components
listed at
[[Page 2518]]
Sec. 429.43(a)(4)(i), the following provisions apply. For the purposes
of this paragraph, ``otherwise identical'' means differing only in the
presence of specific components listed at Sec. 429.43(a)(4)(i).
(i) If the basic model includes only individual models distributed
in commerce with a specific component, or does not include any
otherwise identical individual models without the specific component,
DOE may assess compliance for the basic model based on testing of an
individual model with the component present (and consistent with any
component-specific test provisions specified in section 3 of appendix
G1 to subpart F of part 431 of this chapter).
(ii) If the basic model includes both individual models distributed
in commerce with a specific component and otherwise identical
individual models without the specific component, DOE will assess
compliance for the basic model based on testing an otherwise identical
model within the basic model that does not include the component,
unless DOE is not able to obtain an individual model for testing that
does not include the component. In such a situation, DOE will assess
compliance for the basic model based on testing of an individual model
with the specific component present (and consistent with any component-
specific test provisions specified in section 3 of appendix G1 to
subpart F of part 431 of this chapter).
(3) Validation of outdoor ventilation airflow rate. The outdoor
ventilation airflow rate in cubic feet per minute (``CFM'') of the
basic model will be measured in accordance with ASHRAE 41.2-1987
(incorporated by reference, see Sec. 429.4) and Section 6.4 of ASHRAE
37-2009. All references to the inlet shall be determined to mean the
outdoor air inlet.
(i) The outdoor ventilation airflow rate validation shall be
conducted at the conditions specified in Table 3 of AHRI 390-2021
(incorporated by reference, see Sec. 429.4), Full Load Standard Rating
Capacity Test, Cooling, except for the following:
(A) The outdoor ventilation airflow rate shall be determined at 0
in. H2O external static pressure with a tolerance of -0.00/
+0.05 in. H2O.
(B) Reserved.
(ii) When validating the outdoor ventilation airflow rate, the
outdoor air inlet pressure shall be 0.00 in. H2O, with a
tolerance of -0.00/+0.05 in. H2O when measured against the
room ambient pressure.
PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
5. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
6. Amend Sec. 431.92 by:
0
a. Revising the definitions of ``Single package vertical air
conditioner'' and ``Single package vertical heat pump.''
0
b. Adding the definitions of ``Single-phase single package vertical air
conditioner with cooling capacity less than 65,000 Btu/h'' and
``Single-phase single package vertical heat pump with cooling capacity
less than 65,000 Btu/h'' in alphabetical order; and
The additions and revisions read as follows:
Sec. 431.92 Definitions concerning commercial air conditioners and
heat pumps.
* * * * *
Single package vertical air conditioner means:
(1) Air-cooled commercial package air conditioning and heating
equipment that--
(i) Is factory-assembled as a single package that--
(A) Has major components that are arranged vertically;
(B) Is an encased combination of cooling and optional heating
components; and
(C) Is intended for exterior mounting on, adjacent interior to, or
through an outside wall;
(ii) Is powered by a single-or 3-phase current;
(iii) May contain 1 or more separate indoor grilles, outdoor
louvers, various ventilation options, indoor free air discharges,
ductwork, well plenum, or sleeves; and
(iv) Has heating components that may include electrical resistance,
steam, hot water, or gas, but may not include reverse-cycle
refrigeration as a heating means; and
(2) Includes single-phase single package vertical air conditioner
with cooling capacity less than 65,000 Btu/h, as defined in this
section.
Single package vertical heat pump means:
(1) A single package vertical air conditioner that--
(i) Uses reverse-cycle refrigeration as its primary heat source;
and--
(ii) May include secondary supplemental heating by means of
electrical resistance, steam, hot water, or gas;
(2) Includes single-phase single package vertical heat pump with
cooling capacity less than 65,000 Btu/h, as defined in this section.
Single-phase single package vertical air conditioner with cooling
capacity less than 65,000 Btu/h means air-cooled commercial package air
conditioning and heating equipment that meets the criteria in
paragraphs (1)(i) through (iv) of the definition of a single package
vertical air conditioner; that is single-phase; has a cooling capacity
less than 65,000 Btu/h, and that:
(1) Is weatherized, determined by a model being denoted for
``Outdoor Use'' or marked as ``Suitable for Outdoor Use'' on the
equipment nameplate; or
(2) Is non-weatherized and is a model that has optional ventilation
air provisions available. When such ventilation air provisions are
present on the unit, the unit must be capable of drawing in and
conditioning outdoor air for delivery to the conditioned space at a
rate of at least 400 cubic feet per minute, as determined in accordance
with Sec. 429.134(s)(3), while the equipment is operating with the
same drive kit and motor settings used to determine the certified
efficiency rating of the equipment (as required for submittal to DOE by
Sec. 429.43(b)(4)(xi)).
Single-phase single package vertical heat pump with cooling
capacity less than 65,000 Btu/h means air-cooled commercial package air
conditioning and heating equipment that meets the criteria in
paragraphs (1)(i) through (ii) of the definition of a single package
vertical heat pump; that is single-phase; has a cooling capacity less
than 65,000 Btu/h, and that:
(1) Is weatherized, determined by a model being denoted for
``Outdoor Use'' or marked as ``Suitable for Outdoor Use'' on the
equipment nameplate; or
(2) Is non-weatherized and is a model that has optional ventilation
air provisions available. When such ventilation air provisions are
present on the unit, the unit must be capable of drawing in and
conditioning outdoor air for delivery to the conditioned space at a
rate of at least 400 cubic feet per minute, as determined in accordance
with Sec. 429.134(s)(3), while the equipment is operating with the
same drive kit and motor settings used to determine the certified
efficiency rating of the equipment (as required for submittal to DOE by
Sec. 429.43(b)(4)(xii)).
* * * * *
0
7. Amend Sec. 431.95 by revising paragraphs (a), (b)(5) and (c)(2) to
read as follows:
Sec. 431.95 Materials incorporated by reference.
(a) Certain material is incorporated by reference into this part
with the
[[Page 2519]]
approval of the Director of the Federal Register in accordance with 5
U.S.C. 552(a) and 1 CFR part 51. To enforce any edition other than that
specified in this section, DOE must publish a document in the Federal
Register and the material must be available to the public. All approved
material is available for inspection at the U.S. Department of Energy,
Office of Energy Efficiency and Renewable Energy, Building Technologies
Program, Sixth Floor, 950 L'Enfant Plaza SW, Washington, DC 20024,
(202) 586-9127, [email protected], https://www.energy.gov/eere/buildings/building-technologies-office, and may be obtained from the
other sources in this section. It is also available for inspection at
the National Archives and Records Administration (NARA). For
information on the availability of this material at NARA, email:
[email protected], or go to: www.archives.gov/federal-register/cfr/ibr-locations.html.
(b) * * *
(5) AHRI Standard 390-2021, ``2021 Standard for Performance Rating
of Single Package Vertical Air- Conditioners and Heat Pumps,'' dated
2021, (AHRI 390-2021), IBR approved for appendices G and G1 to this
subpart.
* * * * *
(c) * * *
(2) ANSI/ASHRAE Standard 37-2009, (``ANSI/ASHRAE 37-2009''),
``Methods of Testing for Rating Electrically Driven Unitary Air-
Conditioning and Heat Pump Equipment,'' ASHRAE approved June 24, 2009,
IBR approved for Sec. 431.96 and appendices A, G, and G1 to this
subpart.
* * * * *
0
8. Amend Sec. 431.96 by revising paragraph (b)(1), table 1 to Sec.
431.96, and paragraph (c) to read as follows:
Sec. 431.96 Uniform test method for the measurement of energy
efficiency of commercial air conditioners and heat pumps.
* * * * *
(b) Testing and calculations. (1) Determine the energy efficiency
and capacity of each category of covered equipment by conducting the
test procedure(s) listed in Table 1 of this paragraph (b) along with
any additional testing provisions set forth in paragraphs (c) through
(g) of this section and appendices A through G1 to this subpart, that
apply to the energy efficiency descriptor for that equipment, category,
and cooling capacity. The omitted sections of the test procedures
listed in Table 1 must not be used. For equipment with multiple
appendices listed in Table 1, consult the notes at the beginning of
those appendices to determine the applicable appendix to use for
testing.
(2) * * *
Table 1 to Paragraph (b)(2)--Test Procedures for Commercial Air Conditioners and Heat Pumps
--------------------------------------------------------------------------------------------------------------------------------------------------------
Additional test
Use tests, procedure provisions
Equipment type Category Cooling capacity Energy efficiency conditions, and as indicated in the
descriptor procedures \1\ in listed paragraphs of
this section
--------------------------------------------------------------------------------------------------------------------------------------------------------
Small Commercial Package Air- Air-Cooled, 3-Phase, <65,000 Btu/h......... SEER and HSPF........ AHRI 210/240-2008 Paragraphs (c) and
Conditioning and Heating Equipment. AC and HP. (omit section 6.5). (e).
Air-Cooled AC and HP.. >=65,000 Btu/h and EER, IEER, and COP... Appendix A to this None.
<135,000 Btu/h. subpart.
Water-Cooled and <65,000 Btu/h......... EER.................. AHRI 210/240-2008 Paragraphs (c) and
Evaporatively-Cooled (omit section 6.5). (e).
AC.
>=65,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
<135,000 Btu/h. (omit section 6.3). (e).
Water-Source HP....... <135,000 Btu/h........ EER and COP.......... ISO Standard 13256-1 Paragraph (e).
(1998).
Large Commercial Package Air- Air-Cooled AC and HP.. >=135,000 Btu/h and EER, IEER and COP.... Appendix A to this None.
Conditioning and Heating Equipment. ...................... <240,000 Btu/h. ..................... subpart. .....................
Water-Cooled and >=135,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
Evaporatively-Cooled <240,000 Btu/h. (omit section 6.3). (e).
AC.
Very Large Commercial Package Air- Air-Cooled AC and HP.. >=240,000 Btu/h and EER, IEER and COP.... Appendix A to this None.
Conditioning and Heating Equipment. ...................... <760,000 Btu/h. ..................... subpart. .....................
Water-Cooled and >=240,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
Evaporatively-Cooled <760,000 Btu/h. (omit section 6.3). (e).
AC.
Packaged Terminal Air Conditioners AC and HP............. <760,000 Btu/h........ EER and COP.......... Paragraph (g) of this Paragraphs (c), (e),
and Heat Pumps. section. and (g).
Computer Room Air Conditioners..... AC.................... <65,000 Btu/h......... SCOP................. ASHRAE 127-2007 (omit Paragraphs (c) and
section 5.11). (e).
>=65,000 Btu/h and SCOP................. ASHRAE 127-2007 (omit Paragraphs (c) and
<760,000 Btu/h. section 5.11). (e).
Variable Refrigerant Flow Multi- AC.................... <65,000 Btu/h (3- SEER................. AHRI 1230-2010 (omit Paragraphs (c), (d),
split Systems. phase). sections 5.1.2 and (e), and (f).
6.6).
>=65,000 Btu/h and EER.................. AHRI 1230-2010 (omit Paragraphs (c), (d),
<760,000 Btu/h. sections 5.1.2 and (e), and (f).
6.6).
Variable Refrigerant Flow Multi- HP.................... <65,000 Btu/h (3- SEER and HSPF........ AHRI 1230-2010 (omit Paragraphs (c), (d),
split Systems, Air-cooled. phase). sections 5.1.2 and (e), and (f).
6.6).
>=65,000 Btu/h and EER and COP.......... AHRI 1230-2010 (omit Paragraphs (c), (d),
<760,000 Btu/h. sections 5.1.2 and (e), and (f).
6.6).
Variable Refrigerant Flow Multi- HP.................... <760,000 Btu/h........ EER and COP.......... AHRI 1230-2010 (omit Paragraphs (c), (d),
split Systems, Water-source. sections 5.1.2 and (e), and (f).
6.6).
Single Package Vertical Air AC and HP............. <760,000 Btu/h........ EER and COP.......... Appendix G to this None.
Conditioners and Single Package ..................... subpart \2\. .....................
Vertical Heat Pumps. EER, IEER, and COP... Appendix G1 to this None.
subpart \2\.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Incorporated by reference; see Sec. 431.95.
\2\ For equipment with multiple appendices listed in Table 1, consult the notes at the beginning of those appendices to determine the applicable
appendix to use for testing.
[[Page 2520]]
(c) Optional break-in period for tests conducted using AHRI 210/
240-2008, AHRI 1230-2010, and ASHRAE 127-2007. Manufacturers may
optionally specify a ``break-in'' period, not to exceed 20 hours, to
operate the equipment under test prior to conducting the test method
specified by AHRI 210/240-2008, AHRI 1230-2010, or ASHRAE 127-2007
(incorporated by reference; see Sec. 431.95). A manufacturer who
elects to use an optional compressor break-in period in its
certification testing should record this information (including the
duration) in the test data underlying the certified ratings that is
required to be maintained under 10 CFR 429.71.
* * * * *
Appendix B to Subpart F of Part 431 [Reserved]
0
9. Add and reserve appendix B to subpart F of part 431.
Appendix C to Subpart F of Part 431 [Reserved]
0
10. Add and reserve appendix C to subpart F of part 431.
Appendix D to Subpart F of Part 431 [Reserved]
0
11. Add and reserve appendix D to subpart F of part 431.
Appendix E to Subpart F of Part 431 [Reserved]
0
12. Add and reserve appendix E to subpart F of part 431.
Appendix F to Subpart F of Part 431 [Reserved]
0
13. Add and reserve appendix F to subpart F of part 431.
0
14. Add appendix G to subpart F of part 431 to read as follows:
Appendix G to Subpart F of Part 431--Uniform Test Method for Measuring
the Energy Consumption of Single Package Vertical Air Conditioners and
Single Package Vertical Heat Pumps
Note: Prior to [DATE 360 DAYS AFTER DATE OF PUBLICATION OF THE
FINAL RULE IN THE FEDERAL REGISTER] manufacturers must use the
results of testing under either this appendix or Sec. 431.96 as it
appeared in the 10 CFR parts 200-499 edition revised as of January
1, 2021, to determine compliance with the relevant standard from
Sec. 431.97 as that standard appeared in the January 1, 2021
edition of 10 CFR parts 200-499. On or after [date 360 days after
date of publication of the final rule in the Federal Register]
manufacturers must use the results of testing generated under this
appendix to demonstrate compliance with the relevant standard from
Sec. 431.97 as that standard appeared in the January 1, 2021
edition of 10 CFR parts 200-499.
Beginning [DATE 360 DAYS AFTER DATE OF PUBLICATION OF THE FINAL
RULE IN THE FEDERAL REGISTER], if manufacturers make voluntary
representations with respect to the integrated energy efficiency
ratio (IEER) of single packaged vertical air conditioners and single
package vertical heat pumps, such representations must be based on
testing conducted in accordance with appendix G1 of this subpart.
For any amended standards for single packaged vertical air
conditioners and single package vertical heat pumps based on IEER
published after January 1, 2021, manufacturers must use the results
of testing under appendix G1 to determine compliance.
Representations related to energy consumption must be made in
accordance with the appropriate appendix that applies (i.e., this
appendix or appendix G1) when determining compliance with the
relevant standard. Manufacturers may also use appendix G1 to certify
compliance with any amended standards prior to the applicable
compliance date for those standards.
0. DOE incorporated by reference the entire standard for AHRI
390-2021 and ASHRAE 37-2009 in Sec. 431.95. However, only
enumerated provisions of AHRI 390-2021 and ASHRAE 37-2009 apply to
this appendix, as follows:
0.1 AHRI 390-2021:
(a) Section 3--Definitions (omitting sections 3.1, 3.2, 3.5, 3.12,
and 3.15)
(b) Section 5--Test Requirements (omitting section 5.8.5)
(c) Section 6--Rating Requirements (omitting sections 6.1.1 and 6.2
through 6.5)
(d) Appendix A. ``References--Normative''
(e) Appendix D. ``Indoor and Outdoor Air Condition Measurement--
Normative''
(f) Appendix E. ``Method of Testing Single Package Vertical Units--
Normative''
0.2 All provisions of ANSI/ASHRAE 37-2009 apply except for the
following provisions:
(a) Section 1--Purpose
(b) Section 2--Scope
(c) Section 4--Classifications
1. General.
Determine cooling capacity (Btu/h) and energy efficiency ratio
(EER) for all single package vertical air conditioners and heat
pumps and coefficient of performance (COP) for all single package
vertical heat pumps, in accordance with the specified sections of
AHRI 390-2021 ``Performance Rating of Single Package Vertical Air-
conditioners And Heat Pumps'' and the specified sections of ANSI/
ASHRAE 37-2009 ``Methods of Testing for Rating Electronically Driven
Unitary Air-Conditioning and Heat-Pump Equipment''. Only enumerated
provisions of AHRI 390-2021 and ANSI/ASHRAE 37-2009 are applicable,
as set forth in section 0 of this appendix.
In addition, the instructions in section 2 of this appendix
apply to determining EER and COP. In cases where there is a
conflict, the language of this appendix takes highest precedence,
followed by AHRI 390-2021, followed by ANSI/ASHRAE 37-2009. Any
subsequent amendment to a referenced document by a standard-setting
organization will not affect the test procedure in this appendix,
unless and until the test procedure is amended by DOE. Material is
incorporated as it exists on the date of the approval, and a notice
of any change in the incorporation will be published in the Federal
Register.
2. Test Conditions. The ``Standard Rating Full Load Capacity
Test, Cooling'' conditions for cooling mode tests and ``Standard
Rating Full Load Capacity Test, Heating'' conditions for heat pump
heating mode tests specified in Table 3 of AHRI 390-2021 shall be
used.
2.1 Optional Representations. Representations of COP for single
package vertical heat pumps made using the ``Low Temperature
Operation, Heating'' condition specified in Table 3 of AHRI 390-2021
are optional and are determined according to the applicable
provisions in section 1 of this appendix.
0
15. Add appendix G1 to subpart F of part 431 to read as follows:
Appendix G1 to Subpart F of Part 431--Uniform Test Method for Measuring
the Energy Consumption of Single Package Vertical Air Conditioners and
Single Package Vertical Heat Pumps
Note: Beginning [DATE 360 DAYS AFTER DATE OF PUBLICATION OF THE
FINAL RULE IN THE FEDERAL REGISTER], if manufacturers make voluntary
representations with respect to the integrated energy efficiency
ratio (IEER) of single packaged vertical air conditioners and single
package vertical heat pumps, such representations must be based on
testing conducted in accordance with this appendix.
Manufacturers must use the results of testing under this
appendix to determine compliance with any amended standards for
single packaged vertical air conditioners and single package
vertical heat pumps based on IEER provided in Sec. 431.97 that are
published after January 1, 2021. Representations related to energy
consumption must be made in accordance with the appropriate appendix
that applies (i.e., appendix G or this appendix) when determining
compliance with the relevant standard. Manufacturers may also use
this appendix to certify compliance with any amended standards prior
to the applicable compliance date for those standards.
0. DOE incorporated by reference the entire standard for AHRI
390-2021 and ASHRAE 37-2009 in Sec. 431.95. However, only
enumerated provisions of AHRI 390-2021 and ASHRAE 37-2009 apply to
this appendix, as follows:
0.1 AHRI 390-2021:
(a) Section 3--Definitions (omitting sections 3.1, 3.2, 3.5, 3.12,
and 3.15)
(b) Section 5--Test Requirements (omitting section 5.8.5)
(c) Section 6--Rating Requirements (omitting sections 6.1.1 and 6.3
through 6.5)
(d) Appendix A. ``References--Normative''
(e) Appendix D. ``Indoor and Outdoor Air Condition Measurement--
Normative''
(f) Appendix E. ``Method of Testing Single Package Vertical Units--
Normative''
0.2 All provisions of ANSI/ASHRAE 37-2009 apply except for the
following provisions:
[[Page 2521]]
(a) Section 1--Purpose
(b) Section 2--Scope
(c) Section 4--Classifications
1. General.
Determine cooling capacity (Btu/h) and integrated energy
efficiency ratio (IEER) for all single package vertical air
conditioners and heat pumps and coefficient of performance (COP) for
all single package vertical heat pumps, in accordance with the
specified sections of AHRI 390-2021 ``Performance Rating of Single
Package Vertical Air-conditioners And Heat Pumps'' and the specified
sections of ANSI/ASHRAE 37-2009 ``Methods of Testing for Rating
Electronically Driven Unitary Air-Conditioning and Heat-Pump
Equipment''. Only enumerated provisions of AHRI 390-2021 and ANSI/
ASHRAE 37-2009 are applicable, as set forth in section 0 of this
appendix.
In addition, the instructions in section 2 of this appendix
apply to determining IEER and COP. In cases where there is a
conflict, the language of this appendix takes highest precedence,
followed by AHRI 390-2021, followed by ANSI/ASHRAE 37-2009. Any
subsequent amendment to a referenced document by a standard-setting
organization will not affect the test procedure in this appendix,
unless and until the test procedure is amended by DOE. Material is
incorporated as it exists on the date of the approval, and a notice
of any change in the incorporation will be published in the Federal
Register.
2. Test Conditions. The ``Part-Load Standard Rating Conditions''
conditions for cooling mode tests and ``Standard Rating Full Load
Capacity Test, Heating'' conditions for heat pump heating mode tests
specified in Table 3 of AHRI 390-2021 shall be used.
2.1 Optional Representations. Representations of COP for single
package vertical heat pumps made using the ``Low Temperature
Operation, Heating'' condition specified in Table 3 of AHRI 390-2021
are optional and are determined according to the applicable
provisions in section 1 of this appendix.
3. Set-Up and Test Provisions for Specific Components. When
testing an SPVU that includes any of the features listed in Table
3.1 of this appendix, test in accordance with the set-up and test
provisions specified in Table 3.1.
Table 3.1--Test Provisions for Specific Components
------------------------------------------------------------------------
Component Description Test provisions
------------------------------------------------------------------------
Desiccant Dehumidification An assembly that Disable desiccant
Components. reduces the dehumidification
moisture content of components for
the supply air testing.
through moisture
transfer with solid
or liquid
desiccants.
Air Economizers............. An automatic system For any air
that enables a economizer that is
cooling system to factory-installed,
supply outdoor air place the
to reduce or economizer in the
eliminate the need 100% return
for mechanical position and close
cooling during mid and seal the
or cold weather. outside air dampers
for testing. For
any modular air
economizer shipped
with the unit but
not factory-
installed, do not
install the
economizer for
testing.
Fresh Air Dampers........... An assembly with For any fresh air
dampers and means dampers that are
to set the damper factory-installed,
position in a close and seal the
closed and one open dampers for
position to allow testing. For any
air to be drawn modular fresh air
into the equipment dampers shipped
when the indoor fan with the unit but
is operating. not factory-
installed, do not
install the dampers
for testing.
Hail Guards................. A grille or similar Remove hail guards
structure mounted for testing.
to the outside of
the unit covering
the outdoor coil to
protect the coil
from hail, flying
debris and damage
from large objects.
Power Correction Capacitors. A capacitor that Remove power
increases the power correction
factor measured at capacitors for
the line connection testing.
to the equipment.
Ventilation Energy Recovery An assembly that For any VERS that is
System (VERS). preconditions factory-installed,
outdoor air place the VERS in
entering the the 100% return
equipment through position and close
direct or indirect and seal the
thermal and/or outside air dampers
moisture exchange and exhaust air
with the exhaust dampers for
air, which is testing, and do not
defined as the energize any VERS
building air being subcomponents
exhausted to the (e.g., energy
outside from the recovery wheel
equipment. motors). For any
VERS module shipped
with the unit but
not factory-
installed, do not
install the VERS
for testing.
Barometric Relief Dampers... An assembly with For any barometric
dampers and means relief dampers that
to automatically are factory-
set the damper installed, close
position in a and seal the
closed position and dampers for
one or more open testing. For any
positions to allow modular barometric
venting directly to relief dampers
the outside a shipped with the
portion of the unit but not
building air that factory-installed,
is returning to the do not install the
unit, rather than dampers for
allowing it to testing.
recirculate to the
indoor coil and
back to the
building.
UV Lights................... A lighting fixture Turn off UV lights
and lamp mounted so for testing.
that it shines
light on the indoor
coil, that emits
ultraviolet light
to inhibit growth
of organisms on the
indoor coil
surfaces, the
condensate drip
pan, and/other
locations within
the equipment.
Steam/Hydronic Heat Coils... Coils used to Test with steam/
provide hydronic heat coils
supplemental in place but
heating. providing no heat.
Hot Gas Reheat.............. A heat exchanger De-activate
located downstream refrigerant reheat
of the indoor coil coils for testing
that heats the so as to provide
Supply Air during the minimum (none
cooling operation if possible) reheat
using high pressure achievable by the
refrigerant in system controls.
order to increase
the ratio of
moisture removal to
Cooling Capacity
provided by the
equipment.
Sound Traps/Sound An assembly of Removable sound
Attenuators. structures through traps/sound
which the Supply attenuators shall
Air passes before be removed for
leaving the testing. Otherwise,
equipment or test with sound
through which the traps/attenuators
return air from the in place.
building passes
immediately after
entering the
equipment for which
the sound insertion
loss is at least 6
dB for the 125 Hz
octave band
frequency range.
[[Page 2522]]
Fire/Smoke/Isolation Dampers A damper assembly For any fire/smoke/
including means to isolation dampers
open and close the that are factory-
damper mounted at installed, set the
the supply or dampers in the
return duct opening fully open position
of the equipment. for testing. For
any modular fire/
smoke/isolation
dampers shipped
with the unit but
not factory-
installed, do not
install the dampers
for testing.
------------------------------------------------------------------------
[FR Doc. 2021-28553 Filed 1-13-22; 8:45 am]
BILLING CODE 6450-01-P