Energy Conservation Program: Test Procedure for Air-Cooled, Three-Phase, Small Commercial Package Air Conditioning and Heating Equipment With a Cooling Capacity of Less Than 65,000 Btu/h and Air-Cooled, Three-Phase, Variable Refrigerant Flow Air Conditioners and Heat Pumps With a Cooling Capacity of Less Than 65,000 Btu/h, 70316-70347 [2021-24836]
Download as PDF
70316
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE–2017–BT–TP–0031]
RIN 1904–AE06
Energy Conservation Program: Test
Procedure for Air-Cooled, ThreePhase, Small Commercial Package Air
Conditioning and Heating Equipment
With a Cooling Capacity of Less Than
65,000 Btu/h and Air-Cooled, ThreePhase, Variable Refrigerant Flow Air
Conditioners and Heat Pumps With a
Cooling Capacity of Less Than 65,000
Btu/h
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking
and request for comment.
AGENCY:
The U.S. Department of
Energy (‘‘DOE’’ or ‘‘the Department’’)
proposes to amend its test procedure for
air-cooled, three-phase, small
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 British
thermal units (‘‘Btu/h’’) per hour and
air-cooled, three-phase, variable
refrigerant flow air conditioners and
heat pumps with a cooling capacity of
less than 65,000 Btu/h to incorporate by
reference the latest version of the
relevant industry test standard. DOE
also proposes to adopt the seasonal
energy efficiency ratio 2 (‘‘SEER2’’) and
heating seasonal performance factor 2
(‘‘HSPF2’’) metrics specified by that
industry test standard in the DOE test
procedures for the three-phase
equipment that is the subject of this
notice of proposed rulemaking
(‘‘NOPR’’). Additionally, DOE proposes
to amend certain provisions for
representations and enforcement to
harmonize with single-phase products.
DATES:
Meeting: DOE will hold a webinar on
Monday, January 10, 2022, from 1:00
p.m. to 4:00 p.m. See section V, ‘‘Public
Participation,’’ for webinar registration
information, participant instructions,
and information about the capabilities
available to webinar participants.
Comments: DOE will accept
comments, data, and information
regarding this proposal no later than
February 7, 2022. See section V, ‘‘Public
Participation,’’ for details.
ADDRESSES: Interested persons are
encouraged to submit comments using
the Federal eRulemaking Portal at
www.regulations.gov. Follow the
instructions for submitting comments.
Alternatively, interested persons may
khammond on DSKJM1Z7X2PROD with PROPOSALS2
SUMMARY:
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
submit comments, identified by docket
number EERE–2017–BT– TP–0031, by
any of the following methods:
(1) Federal eRulemaking Portal:
www.regulations.gov. Follow the
instructions for submitting comments.
(2) Email:
AirCooledACHP2017TP0031@
ee.doe.gov. Include the docket number
EERE–2017–BT–TP–0031 or regulatory
information number (RIN) 1904–AE06
in the subject line of the message.
No telefacsimilies (faxes) will be
accepted. For detailed instructions on
submitting comments and additional
information on the rulemaking process,
see section V of this document.
Although DOE has routinely accepted
public comment submissions through a
variety of mechanisms, including postal
mail and hand delivery/courier, the
Department has found it necessary to
make temporary modifications to the
comment submission process in light of
the ongoing COVID–19 pandemic. DOE
is currently suspending receipt of public
comments via postal mail and hand
delivery/courier, and instead, the
Department is only accepting electronic
submissions at this time. If a commenter
finds that this change poses an undue
hardship, please contact Appliance
Standards Program staff at (202) 586–
1445 to discuss the need for alternative
arrangements. Once the COVID–19
pandemic health emergency is resolved,
DOE anticipates resuming all of its
regular options for public comment
submission, including postal mail and
hand delivery/courier.
Docket: The docket, which includes
Federal Register notices, public meeting
attendee lists and transcripts (if a public
meeting is held), comments, and other
supporting documents/materials, is
available for review at
www.regulations.gov. All documents in
the docket are listed in the
www.regulations.gov index. However,
some documents listed in the index,
such as those containing information
that is exempt from public disclosure,
may not be publicly available.
The docket web page can be found at:
www.regulations.gov/docket?D=EERE2017-BT-TP-0031.
The docket web page contains
instructions on how to access all
documents, including public comments,
in the docket. See section V for
information on how to submit
comments through
www.regulations.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Catherine Rivest, U.S. Department
of Energy, Office of Energy Efficiency
and Renewable Energy, Building
Technologies Office, EE–2J, 1000
PO 00000
Frm 00002
Fmt 4701
Sfmt 4702
Independence Avenue SW, Washington,
DC 20585–0121. Telephone: (202) 586–
7335. Email:
ApplianceStandardsQuestions@
ee.doe.gov.
Ms. Kristin Koernig, U.S. Department
of Energy, Office of the General Counsel,
GC–33, 1000 Independence Avenue SW,
Washington, DC 20585–0121.
Telephone: (202) 586–8145.
Email:kristin.koernig@hq.doe.gov.
For further information on how to
submit a comment, review other public
comments, and the docket, contact the
Appliance and Equipment Standards
Program staff at (202) 287–1445 or by
email: ApplianceStandardsQuestions@
ee.doe.gov.
DOE
proposes to maintain and update
previously approved incorporations by
references for the following industry
standards in part 431:
Air-Conditioning, Heating, and
Refrigeration Institute (‘‘AHRI’’)
Standard 210/240–2008, (‘‘AHRI 210/
240–2008’’), ‘‘Performance Rating of
Unitary Air-Conditioning & Air-Source
Heat Pump Equipment,’’ approved 2011
and updated by addendum 1 in June
2011 and addendum 2 in March 2012.
American National Standards
Institute (‘‘ANSI’’)/AHRI Standard
1230–2010, ‘‘ANSI/AHRI 1230–
2010’’),’’2010 Standard for Performance
Rating of Variable Refrigerant Flow
(VRF) Multi-split Air-Conditioning and
Heat Pump Equipment,’’ approved 2010
and updated by addendum 1 in March
2011.
Copies of AHRI 210/240–2008 and
ANSI/AHRI 1230–2010 can be obtained
from the AHRI website by going to
https://www.ahrinet.org.
DOE proposes to incorporate by
reference the following industry
standard into parts 429 and 431:
AHRI Standard 210/240–2023,
(‘‘AHRI 210/240–2023’’), ‘‘Performance
Rating of Unitary Air-Conditioning &
Air-Source Heat Pump Equipment,’’
approved 2020.
Copies of AHRI 210/240–2023 can be
obtained from the AHRI website by
going to https://www.ahrinet.org.
DOE proposes to amend the
previously approved incorporation by
reference for the following industry
standard in part 431:
American National Standards
Institute (‘‘ANSI’’)/American Society of
Heating, Refrigerating, and AirConditioning Engineers (‘‘ASHRAE’’)
Standard 37–2009, ‘‘Methods of Testing
for Rating Electrically Driven Unitary
Air-Conditioning and Heat Pump
Equipment,’’ ASHRAE approved June
24, 2009.
SUPPLEMENTARY INFORMATION:
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
Copies of ANSI/ASHRAE Standard
37–2009 can be obtained from the
American National Standards Institute,
25 W. 43rd Street, 4th Floor, New York,
NY 10036, (212) 642–4900, or online at:
https://webstore.ansi.org/.
See section IV.M of this document for
further discussion of these standards.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Notice of Proposed
Rulemaking
III. Discussion
A. Scope of Applicability
B. Metrics
C. Proposed Organization of the Test
Procedure
D. Updates to the Federal Test Method for
Central Air Conditioners and Heat
Pumps
E. Updates to Industry Standards and
Proposed Test Procedures for ThreePhase Equipment With Cooling Capacity
of Less Than 65,000 Btu/h
1. Harmonization With Single-Phase
Products
2. AHRI 210/240
3. AHRI 1230
4. ASHRAE 37
F. Certification, Compliance, and
Enforcement Requirements
1. Representation Requirements
2. Basic Model Definition
3. Certification Reporting Requirements
4. Product-Specific Enforcement Provisions
G. Test Procedure Costs
H. Compliance Date
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility
Act
C. Review Under the Paperwork Reduction
Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates
Reform Act of 1995
H. Review Under the Treasury and General
Government Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General
Government Appropriations Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal
Energy Administration Act of 1974
M. Description of Materials Incorporated
by Reference
V. Public Participation
A. Participation in the Webinar
B. Procedure for Submitting Prepared
General Statements for Distribution
C. Conduct of the Webinar
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
VI. Approval of the Office of the Secretary
I. Authority and Background
Small, large, and very large
commercial package air conditioning
and heating equipment are included in
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
the list of ‘‘covered equipment’’ for
which DOE is authorized to establish
and amend energy conservation
standards and test procedures. (42
U.S.C. 6311(1)(B)–(D)) Air-cooled, threephase, small commercial air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h (‘‘3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h’’) 1 and air-cooled, three-phase,
variable refrigerant flow (‘‘VRF’’ or
‘‘VRF multi-split systems’’) air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h (‘‘3-phase VRF with cooling capacity
of less than 65,000 Btu/h’’) 2 are two
separate categories of small commercial
package air conditioning and heating
equipment. DOE’s test procedures and
energy conservation standards for
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and for 3-phase VRF with cooling
capacity of less than 65,000 Btu/h are
currently prescribed at title 10 of the
Code of Federal Regulations (‘‘CFR’’)
part 431. See 10 CFR 431.96 (test
procedures) and 10 CFR 431.97 (energy
conservation standards). The following
sections discuss DOE’s authority to
establish and amend the test procedure
for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and for 3-phase VRF with cooling
capacity of less than 65,000 Btu/h, and
relevant background information
regarding DOE’s consideration of test
procedures for this equipment.
A. Authority
The Energy Policy and Conservation
Act, as amended (‘‘EPCA’’),3 authorizes
DOE to regulate the energy efficiency of
a number of consumer products and
certain industrial equipment. (42 U.S.C.
6291–6317, as codified) Title III, Part C 2
of EPCA, added by Public Law 95–619,
Title IV, section 441(a), established the
Energy Conservation Program for
Certain Industrial Equipment, which
sets forth a variety of provisions
designed to improve energy efficiency
for certain industrial equipment,
including 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h, and 3-phase VRF
1 ACUACs and ACUHPS means air-cooled
commercial unitary air conditioners and heat
pumps and is terminology consistent with that used
for this equipment with a cooling capacity of greater
than or equal to 65,000 Btu/h.
2 As used in this rulemaking, the term ‘‘3-phase
VRF with cooling capacity of less than 65,000 Btu/
h’’ refers only to air-cooled equipment.
3 All references to EPCA in this document refer
to the statute as amended through the Energy Act
of 2020, Public Law 116–260 (Dec. 27, 2020).
2 For editorial reasons, upon codification in the
U.S. Code, Part C was redesignated Part A–1.
PO 00000
Frm 00003
Fmt 4701
Sfmt 4702
70317
with cooling capacity of less than
65,000 Btu/h, the subjects of this NOPR.
(42 U.S.C. 6311(1)(B))
The energy conservation program
under EPCA consists essentially of four
parts: (1) Testing, (2) labeling, (3) the
establishment of Federal energy
conservation standards, and (4)
certification and enforcement
procedures. Relevant provisions of
EPCA include definitions (42 U.S.C.
6311), test procedures (42 U.S.C. 6314),
labeling provisions (42 U.S.C. 6315),
energy efficiency standards (42 U.S.C.
6313), and the authority to require
information and reports from
manufacturers (42 U.S.C. 6316; 42
U.S.C. 6296).
The Federal testing requirements
consist of test procedures that
manufacturers of covered equipment
must use as the basis for: (1) Certifying
to DOE that their equipment complies
with the applicable energy conservation
standards adopted pursuant to EPCA (42
U.S.C. 6316(b); 42 U.S.C. 6296), and (2)
making representations about the
efficiency of that equipment (42 U.S.C.
6314(d)). Similarly, DOE uses these test
procedures to determine whether the
equipment complies with relevant
standards promulgated under EPCA.
Federal energy efficiency
requirements for covered equipment
established under EPCA generally
supersede State laws and regulations
concerning energy conservation testing,
labeling, and standards. (42 U.S.C.
6316(a)–(b); 42 U.S.C. 6297) However,
DOE may grant waivers of Federal
preemption for particular State laws or
regulations, in accordance with the
procedures and other provisions of
EPCA. (42 U.S.C. 6316(b)(2)(D))
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE must
follow when prescribing or amending
test procedures for covered equipment.
EPCA requires that any test procedures
prescribed or amended under this
section must be reasonably designed to
produce test results reflecting the energy
efficiency, energy use, and estimated
annual operating cost of a given type of
covered equipment during a
representative average use cycle and
requires that test procedures not be
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2))
As discussed, 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h are both categories of
small commercial package air
conditioning and heating equipment.
EPCA requires that the test procedures
for small commercial package air
conditioning and heating equipment
E:\FR\FM\09DEP2.SGM
09DEP2
70318
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
shall be those generally accepted
industry testing procedures or rating
procedures developed or recognized by
AHRI or by ASHRAE, as referenced in
ASHRAE Standard 90.1, ‘‘Energy
Standard for Buildings Except Low-Rise
Residential Buildings’’ (ASHRAE
Standard 90.1). (42 U.S.C. 6314(a)(4)(A))
Further, if that industry test procedure
is amended, DOE must amend its test
procedure to be consistent with the
amended industry test procedure,
unless DOE determines, by rule
published in the Federal Register and
supported by clear and convincing
evidence, that such amended test
procedure would not meet the
requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B)) In
addition, if DOE determines that a test
procedure amendment is warranted, it
must publish proposed test procedures
and offer the public an opportunity to
present oral and written comments on
them. (42 U.S.C. 6314(b))
EPCA also requires that, at least once
every 7 years, DOE shall evaluate test
procedures for each type of covered
equipment, including those addressed
in this NOPR, to determine whether
amended test procedures would more
accurately or fully comply with the
requirement that the test procedures not
be unduly burdensome to conduct and
be reasonably designed to produce test
results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 6314(a)(1)) In
addition, if DOE determines that a test
procedure amendment is warranted,
DOE must publish the proposed test
procedures in the Federal Register, and
afford interested persons an opportunity
of not less than 45 days to present oral
and written data, views, and arguments
on the proposed test procedures. (42
U.S.C. 6314(b)) If DOE determines that
test procedure revisions are not
appropriate, DOE must publish its
determination not to amend the test
procedures. (42 U.S.C. 6314(a)(1)(A)(ii))
DOE is publishing this NOPR
consistent with its obligations under
EPCA.
B. Background
DOE’s current test procedures for 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and for 3-phase VRF with cooling
capacity of less than 65,000 Btu/h are
codified at 10 CFR 431.96.
The Federal test procedure for
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h was last amended on May 16, 2012 to
incorporate by reference the ANSI/AHRI
Standard 210/240–2008, ‘‘Performance
Rating of Unitary Air-Conditioning &
Air-Source Heat Pump Equipment,’’
approved by ANSI on October 27, 2011
and updated by addendum 1 in June
2011 and addendum 2 in March 2012
(‘‘ANSI/AHRI 210/240–2008’’). 77 FR
28928 (‘‘May 2012 final rule’’). The May
2012 final rule also established
additional testing requirements at 10
CFR 431.96(c) and (e) that provide an
optional break-in period for testing and
specifications regarding the use of
manufacturer instructions in set-up,
respectively, applicable to measuring
seasonal energy efficiency ratio
(‘‘SEER’’) and heating seasonal
performance factor (‘‘HSPF’’) for this
equipment. 77 FR 28928, 28991 (May
16, 2012).
The Federal test procedure for
3-phase VRF with cooling capacity of
less than 65,000 Btu/h was also last
amended in the May 2012 final rule,
and incorporated by reference ANSI/
AHRI Standard 1230–2010, ‘‘2010
Standard for Performance Rating of
Variable Refrigerant Flow (VRF) MultiSplit Air-Conditioning and Heat Pump
Equipment,’’ approved August 2, 2010
and updated by addendum 1 in March
2011 (‘‘AHRI 1230–2010’’). The testing
requirements at 10 CFR 431.96(c) and
(e) also apply to VRF multi-split
systems. Additionally, the May 2012
final rule established additional testing
requirements at 10 CFR 431.96(d) and (f)
that provide for refrigerant line length
corrections for tests conducted using
AHRI 1230–2010, and for manufacturer
involvement in assessment or
enforcement testing for VRF multi-split
systems, respectively. 77 FR 28928,
28991 (May 16, 2012).
In 2017, AHRI published an updated
version of its standard, ‘‘Performance
Rating of Unitary Air-Conditioning &
Air-Source Heat Pump Equipment’’
(‘‘AHRI 210/240–2017’’). That updated
testing standard made a number of
changes that are relevant to DOE’s
current test procedure, and many of
these changes were based on DOE’s
current test procedure for single-phase
central air conditioners and central air
conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h (i.e.,
10 CFR part 430, subpart B, appendix
M, ‘‘Uniform Test Method for Measuring
the Energy Consumption of Central Air
Conditioners and Heat Pumps’’;
‘‘Appendix M’’).4
Following the publication of AHRI
210/240–2017, on October 2, 2018, DOE
published in the Federal Register a
request for information (‘‘RFI’’) seeking
comments on whether DOE should align
its test procedure (and certification and
enforcement requirements) for 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h with
that for air-cooled, single-phase, central
air conditioners and central air
conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h,
consistent with the update to AHRI 210/
240–2017. 83 FR 49501 (‘‘October 2018
RFI’’).
DOE received comments in response
to the October 2018 RFI from the
interested parties listed in Table I.I.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
TABLE I.I—INTERESTED PARTIES PROVIDING WRITTEN COMMENTS TO THE OCTOBER 2018 RFI
Organization(s)
Reference in
this NOPR
Air-Conditioning Heating and Refrigeration Institute ..........................................................
Pacific Gas and Electric Company (‘‘PG&E’’), San Diego Gas, and Electric (‘‘SDG&E’’),
and Southern California Edison (‘‘SCE’’).
Goodman Global, Inc .........................................................................................................
Ingersoll Rand ....................................................................................................................
Lennox International Inc .....................................................................................................
Natural Resources Defense Council (‘‘NRDC’’), and Appliance Standards Awareness
Project (‘‘ASAP’’).
United Technologies Corporation (submitted by Carrier Corporation) ..............................
AHRI ..........................
CA IOUs ....................
Trade Association.
Utilities.
Goodman ...................
Ingersoll Rand ...........
Lennox .......................
NRDC and ASAP ......
Manufacturer.
Manufacturer.
Manufacturer.
Energy Efficiency Advocates.
Carrier .......................
Manufacturer.
4 Three-phase equipment models generally are
identical physically to their single-phase,
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
residential counterparts, except for the electrical
PO 00000
Frm 00004
Fmt 4701
Sfmt 4702
Organization type
systems and components designed for three-phase
power input.
E:\FR\FM\09DEP2.SGM
09DEP2
70319
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
Throughout this document, a
parenthetical reference at the end of a
comment quotation or paraphrase
provides the location of the item in the
public record.5
In April 2019, AHRI published the
‘‘Performance Rating of Unitary AirConditioning & Air-Source Heat Pump
Equipment (with Addendum 1)’’
(‘‘AHRI 210/240–2017 with Addendum
1’’), which incorporated minor revisions
to definitions, testing requirements, and
efficiency calculations.
On October 23, 2019, ASHRAE
released ASHRAE Standard 90.1–2019,
which maintained the reference to AHRI
210/240 as the industry testing standard
for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h, but updated the editions referenced.
ASHRAE Standard 90.1–2019 references
AHRI 210/240–2017 for the period prior
to January 1, 2023. For the period
beginning January 1, 2023, ASHRAE
Standard 90.1–2019 references AHRI
210/240–2023 (to align with ASHRAE
Standard 90.1–2019 minimum
efficiency levels for this equipment in
terms of SEER2 and HSPF2 that take
effect on January 1, 2023). ASHRAE
Standard 90.1–2019 maintained the
reference to AHRI 1230 as the industry
testing standard for all VRF multi-split
systems, including air-cooled, threephase units with a cooling capacity of
less than 65,000 Btu/h, with an update
to AHRI 1230–2014 with Addendum 1.6
In May 2020, AHRI published AHRI
210/240–2023. The updates in AHRI
210/240–2017, AHRI 210/240–2017
with Addendum 1, and AHRI 210/240–
2023 are discussed in section III.E.2 of
this NOPR. DOE has reviewed the
comments from the October 2018 RFI in
the context of these updated industry
standards.
In May 2021, AHRI published AHRI
1230–2021, which excludes from its
scope air-cooled, VRF multi-split
systems with a cooling capacity of less
than 65,000 Btu/h. Both AHRI 210/240–
2017 with Addendum 1 and AHRI 210/
240–2023 exclude from their scope only
VRF multi-split systems that have
capacities greater than or equal to
65,000 Btu/h. Because AHRI 1230–2021
explicitly excludes VRF multi-split
systems with a cooling capacity of less
than 65,000 Btu/h from scope, and the
scope exclusion in AHRI 210/240–2023
applies only to VRF multi-split systems
with a cooling capacity of 65,000 Btu/
h or greater, VRF multi-split systems
with a cooling capacity of less than
65,000 Btu/h are included within the
scope of AHRI 210/240–2023.
As such, DOE has tentatively
determined that AHRI 210/240–2023 is
now the appropriate industry test
standard for 3-phase VRF with cooling
capacity of less than 65,000 Btu/h.
Three-phase VRF with cooling capacity
of less than 65,000 Btu/h do not
currently exist on the market, but DOE
expects that any such equipment
introduced to the market in the future
would likely be identical to air-cooled,
single-phase, VRF multi-split systems
(except for the components designed for
three-phase power input). Therefore,
DOE has tentatively determined that it
is appropriate to align its proposed test
procedure for 3-phase VRF with cooling
capacity of less than 65,000 Btu/h
(AHRI 210/240–2023) with the test
procedure for their single-phase
counterparts (i.e., 10 CFR part 430,
subpart B, appendix M1; (‘‘Appendix
M1’’)). For these reasons, DOE is
addressing the test procedures for this
equipment in this NOPR.
II. Synopsis of the Notice of Proposed
Rulemaking
This NOPR proposes to update the
references in the Federal test procedures
to the most recent version of the
relevant industry test procedures as they
relate to 3-phase ACUACs and ACUHPs
with cooling capacity of less than
65,000 Btu/h and 3-phase VRF with
cooling capacity of less than 65,000 Btu/
h. Specifically, DOE proposes to update
its regulations at 10 CFR 431.96,
‘‘Uniform test method for the
measurement of energy efficiency of
commercial air conditioners and heat
pumps,’’ as follows: (1) Incorporate by
reference AHRI 210/240–2023 and
ANSI/ASHRAE 37–2009 ‘‘Methods of
Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat
Pump Equipment’’ (‘‘ANSI/ASHRAE
37–2009’’); and (2) establish provisions
for determining SEER2 and HSPF2. The
current DOE test procedures for all
equipment addressed in this NOPR
would be relocated to a new appendix
B of subpart F to 10 CFR part 431
(‘‘Appendix B’’) without change, and
the new test procedure adopting AHRI
210/240–2023 would be established in a
new appendix B1 of subpart F to 10 CFR
part 431 (‘‘Appendix B1’’) for
determining SEER2 and HSPF2.
Compliance with appendix B1 would
not be required until such time as
compliance is required with amended
energy conservation standards that rely
on SEER2 and HSPF2, should DOE
adopt such standards. Compliance with
appendix B (which aligns with the
current Federal test procedure) would
be required beginning 360 days
following publication of the final rule.
Prior to the date 360 days following
publication of the final rule, testing
would be required to be conducted
either per appendix B or under 10 CFR
431.96 as it appeared in the 10 CFR
parts 200–499 edition revised as of
January 1, 2021.
In addition, DOE proposes to update
most of its compliance and enforcement
requirements for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and for 3-phase VRF
with cooling capacity of less than
65,000 Btu/h to be consistent with those
for the consumer product counterparts
(i.e., air-cooled, single-phase, central air
conditioners and central air
conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h
(which include single-phase VRF multisplit systems)).
DOE’s proposed actions are
summarized in Table II.2 and addressed
in detail in section III of this document.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
TABLE II.2—SUMMARY OF CHANGES IN PROPOSED TEST PROCEDURE RELATIVE TO CURRENT TEST PROCEDURE
Current DOE test procedures
Proposed amendment
Reason
Incorporates by reference ANSI/AHRI 210/240–2008 (for
equipment other than VRF multi-split systems) and
ANSI/AHRI 1230–2010 for VRF multi-split systems.
Incorporates by reference in a new appendix B1 AHRI
210/240–2023 and ANSI/ASHRAE 37–2009.
EPCA requirement to harmonize with industry test
procedure.
5 The parenthetical reference provides a reference
for information located in the docket of this
rulemaking. (Docket No. EERE–2017–BT–TP–0031,
which is maintained at www.regulations.gov). The
references are arranged as follows: (commenter
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
name, comment docket ID number, page of that
document).
6 Air-cooled, three-phase, VRF multi-split systems
with a cooling capacity of less than 65,000 Btu/h
PO 00000
Frm 00005
Fmt 4701
Sfmt 4702
are not excluded from the scope of either AHRI 210/
240 (2017 and 2023) or AHRI 1230–2014 with
Addendum 1.
E:\FR\FM\09DEP2.SGM
09DEP2
70320
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
TABLE II.2—SUMMARY OF CHANGES IN PROPOSED TEST PROCEDURE RELATIVE TO CURRENT TEST PROCEDURE—
Continued
Current DOE test procedures
Proposed amendment
Reason
Applicable representation requirements are those specified at 10 CFR 429.43 and 10 CFR 429.70 for commercial heating, ventilating, and air conditioning
(‘‘HVAC’’) equipment.
Amends representation requirements at new 10 CFR
429.64 and 10 CFR 429.70—including basic model
definition, tested combination, determination of represented value, and alternative energy determination
method (‘‘AEDM’’) requirements—largely consistent
with requirements for single-phase consumer product
counterparts.
Amended representation requirements allow the use of
an AEDM that is validated with testing of an otherwise identical single-phase central air conditioners
and heat pumps for rating three-phase, less than
65,000 Btu/h single package units and split systems.
Harmonization with singlephase consumer product
counterparts, and reduction of testing burden on
manufacturers.
DOE has tentatively determined that
the proposed amendments described in
section III of this NOPR regarding the
establishment of appendix B would not
alter the measured efficiency of
equipment addressed in this document
or require retesting solely as a result of
DOE’s adoption of this proposed
amendment to the test procedure. DOE
has tentatively determined, however,
that the proposed test procedure
amendments in appendix B1 would, if
adopted, alter the measured efficiency
of the affected equipment and that such
amendments are consistent with the
updated industry test procedure.
Further, compliance with the proposed
appendix B1 and the proposed
amendments to the representation
requirements in 10 CFR 429.43 and 10
CFR 429.70 would not be required until
the compliance date of amended
standards in terms of SEER2 and
HSPF2. Additionally, DOE has
tentatively determined that the
proposed amendments, if adopted,
would not increase the cost of testing
relative to the updated industry test
procedure. Discussion of DOE’s
proposed actions are addressed in detail
in section III of this NOPR.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
III. Discussion
The discussion that follows details
the specific changes that DOE is
proposing to make to the current test
procedure regulations affecting 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of
less than 65,000 Btu/h.
A. Scope of Applicability
Three-phase ACUACs and ACUHPs
with cooling capacity of less than
65,000 Btu/h and 3-phase VRF with
cooling capacity of less than 65,000 Btu/
h are both categories of small
commercial package air conditioning
and heating equipment. Commercial
package air-conditioning and heating
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
equipment may be air-cooled, watercooled, evaporatively-cooled, or water
source-based (not including ground
water source). These equipment are
electrically-operated and are designed
as unitary central air conditioners or
central air-conditioning heat pumps for
use in commercial applications. 10 CFR
431.92. As discussed in the following
sections, 3-phase ACUACs and ACUHPs
with cooling capacity of less than
65,000 Btu/h are typically nearly
identical (and therefore typically have
comparable efficiency) to single-phase
central air conditioners and central air
conditioning heat pumps with rated
cooling capacities of less than 65,000
Btu/h, the latter being consumer
products also subject to EPCA and for
which DOE has already established
energy conservation standards (10 CFR
430.32(c)) and test procedures
(appendix M and appendix M1). Based
on this ‘‘nearly identical’’ relationship,
while 3-phase VRF with cooling
capacity of less than 65,000 Btu/h do
not currently exist on the market, DOE
expects that any such equipment
introduced to the market in the future
would likely also be identical (except
for the components designed for threephase power input) to their single-phase
counterparts, which are a subset of
single-phase central air conditioners
and central air conditioning heat
pumps, and, as such, are also rated
using appendix M and appendix M1.
Three-phase ACUACs and ACUHPs
with cooling capacity of less than
65,000 Btu/h are further disaggregated
into four equipment classes: Singlepackage air conditioners, single-package
heat pumps, split-system air
conditioners, and split-system heat
pumps. 10 CFR 431.97(b).7 This NOPR
7 The term ‘‘single package unit’’ means ‘‘any
central air conditioner or central air-conditioning
heat pump in which all the major assemblies are
enclosed in one cabinet.’’ The term ‘‘split system’’
means ‘‘any central air conditioner or central air-
PO 00000
Frm 00006
Fmt 4701
Sfmt 4702
proposes to amend the test procedure
applicable to all four equipment classes
but without amending its current scope.
Three-phase VRF with cooling capacity
of less than 65,000 Btu/h are further
disaggregated into two equipment
classes: air conditioners and heat
pumps. 10 CFR 431.97(f). This NOPR
proposes to amend the test procedure
applicable to both equipment classes
but without amending its current scope.
B. Metrics
As noted, for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and for 3-phase VRF
with cooling capacity of less than
65,000 Btu/h, the cooling metric and
heating metric currently specified by
DOE are the SEER metric and the HSPF
metric, respectively. 10 CFR 431.96.
SEER is a seasonal efficiency metric that
accounts for electricity consumption in
active and standby cooling modes
during the cooling season, while HSPF
is a seasonal efficiency metric that
accounts for electricity consumption in
active and standby heating modes for
heat pumps during the heating season.
These are the same metrics that
currently apply to single-phase central
air conditioners and central air
conditioning heat pumps, including
single-phase, air-cooled VRF multi-split
systems with a cooling capacity of less
than 65,000 Btu/h (see appendix M).
C. Proposed Organization of the Test
Procedure
DOE is proposing to relocate and
centralize the current test procedures for
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h to a
new appendix B to subpart F of part
431. As proposed, appendix B would
conditioning heat pump in which one or more of
the major assemblies are separate from the others.’’
10 CFR 431.92.
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
khammond on DSKJM1Z7X2PROD with PROPOSALS2
not amend the current test procedures.
The test procedures as provided in the
proposed appendix B would continue to
reference ANSI/AHRI 210/240–2008
and ANSI/AHRI 1230–2010 and provide
instructions for determining SEER and
HSPF. DOE is proposing to also update
the existing incorporation by reference
of ANSI/AHRI 210/240–2008 and ANSI/
AHRI 1230–2010 at 10 CFR 431.95 to
apply it to appendix B. The proposed
appendix B would also centralize the
additional test provisions currently
applicable under 10 CFR 431.96, i.e., 10
CFR 431.96(c) through (f). As proposed,
the three-phase equipment addressed in
this document would be required to be
tested according to appendix B until
such time as compliance is required
with amended energy conservation
standards that rely on the SEER2 and
HSPF2 metrics, should DOE adopt such
standards.
DOE is also proposing to amend the
test procedures for 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h by adopting AHRI 210/
240–2023 in a new appendix B1 to
subpart F of part 431. As noted, EPCA
requires DOE to amend the test
procedure as necessary to be consistent
with the amended industry test
procedure unless it determines, by rule,
published in the Federal Register and
supported by clear and convincing
evidence, that to do so would not meet
the statutory requirements for test
procedures regarding representativeness
and no undue test burden. DOE
proposes to adopt the updated version
of AHRI 210/240, i.e., AHRI 210/240–
2023, including the SEER2 and HSPF2
metrics. As proposed, the three-phase
equipment addressed in this NOPR
would not be required to be tested using
the test procedure in proposed
Appendix B1 until such time as
compliance is required with amended
energy conservation standards that rely
on the SEER2 and HSPF2 metrics,
should DOE adopt such standards.
D. Updates to the Federal Test Method
for Central Air Conditioners and Heat
Pumps
On June 8, 2016, DOE published a test
procedure final rule amending appendix
M. 81 FR 36992 (‘‘June 2016 final
rule’’).8 DOE further amended appendix
M in a final rule, published on January
5, 2017, to improve test repeatability,
reduce testing burden, and improve the
accuracy of field representativeness of
the testing values without impacting the
8 A correction was issued on August 18, 2016, to
fix editorial errors. 81 FR 55111.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
measured energy consumption. 82 FR
1426 (‘‘January 2017 final rule’’).
The January 2017 final rule also
included other changes to improve test
repeatability, reduce testing burden, and
improve the accuracy of field
representativeness that would impact
the results of the test procedure. DOE
established a separate appendix M1
incorporating these changes and new
metrics to avoid confusion with the
metrics under appendix M. Appendix
M1 specifies new efficiency metrics
SEER2, energy efficiency ratio 2
(‘‘EER2’’), and HSPF2 that have the
same definitions as their counterpart
metrics in appendix M (i.e., SEER, EER,
and HSPF) but reflect the amendments
made to the test procedure in Appendix
M1, which change the measured
efficiency values compared to Appendix
M. (See 82 FR 1426, 1437 (Jan. 5, 2017)
explaining DOE’s decision to adopt the
new metrics SEER2, EER2, and HSPF2).
Beginning on January 1, 2023, efficiency
representations for single-phase central
air conditioners and central air
conditioning heat pumps with rated
cooling capacities of less than 65,000
Btu/h must be based on the test
procedure in appendix M1. 82 FR 1426.
Both appendices M and M1 reference
ANSI/AHRI 210/240–2008, sections
6.1.3.2, 6.1.3.4, 6.1.3.5 and figures D1,
D2, D4, along with sections of ANSI/
AHRI 1230–2010 (related to VRF multisplit systems), ANSI/ASHRAE 23.1–
2010, ANSI/ASHRAE 37–2009, ANSI/
ASHRAE 41.1–2013, ANSI/ASHRAE
41.2–1987 (RA 1992), ANSI/ASHRAE
41.6–2014, ANSI/ASHRAE 41.9–2011,
ANSI/ASHRAE 116–2010, and ANSI/
AMCA 210–2007.
Additionally, both the June 2016 final
rule and January 2017 final rule adopted
amendments related to the certification,
compliance, and enforcement of singlephase central air conditioners and
central air conditioning heat pumps
with rated cooling capacities of less
than 65,000 Btu/h, codified in 10 CFR
part 429. See generally, 81 FR 36992,
37049–37055 (June 8, 2016) and 82 FR
1426, 1468–1475 (Jan. 5, 2017). The
amendments included revisions to the
basic model definition, clarifications to
definitions, and a variety of revisions
related to the testing requirements for
determining represented values,
certification reporting requirements, and
product-specific enforcement
provisions. Id.
E. Updates to Industry Standards and
Proposed Test Procedures for ThreePhase Equipment With Cooling Capacity
of Less Than 65,000 Btu/h
As noted, the current DOE test
procedure at 10 CFR 431.96 for 3-phase
PO 00000
Frm 00007
Fmt 4701
Sfmt 4702
70321
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h
incorporates by reference ANSI/AHRI
Standard 210/240–2008 with Addenda 1
and 2 (‘‘ANSI/AHRI 210/240–2008,’’ but
omitting section 6.5). ANSI/AHRI 210/
240–2008 includes as appendix C
(which is designated as normative in the
industry test standard) 9 the entirety of
the text of appendix M as amended by
a final rule published on October 22,
2007 (72 FR 59906). Appendix M
provides the Federal test procedure for
determining the efficiency of singlephase central air conditioners and
central air conditioning heat pumps
with rated cooling capacities of less
than 65,000 Btu/h, which are consumer
products covered under 10 CFR part
430.
The current DOE test procedure at 10
CFR 431.96 for 3-phase VRF with
cooling capacity of less than 65,000 Btu/
h incorporates by reference ANSI/AHRI
Standard 1230–2010 with Addendum 1
(‘‘ANSI/AHRI 1230–2010’’, omitting
sections 5.1.2 and 6.6).
As noted previously in this document,
AHRI has recently published several
updated industry standards: AHRI 210/
240–2017 (published in December
2017), AHRI 210/240–2017 with
Addendum 1 (published in April 2019),
and AHRI 210/240–2023 (published in
May 2020). DOE has reviewed these
documents in the development of this
NOPR. In addition, AHRI has recently
published AHRI 1230–2021 (published
in May 2021).
As discussed in the following
sections, DOE is proposing to
incorporate by reference AHRI 210/240–
2023 as the test procedure for the threephase equipment addressed in this
document. As proposed, manufacturers
would not be required to rely on the
amended test procedure incorporating
AHRI 210/240–2023 until such time as
compliance is required with amended
standards in terms of the new metrics,
SEER2 and HSPF2, should DOE adopt
such energy conservation standards.
This proposed test procedure update
would align with the test procedure and
metrics for central air conditioners and
heat pumps specified at appendix M1.
DOE is also proposing to incorporate by
reference ANSI/ASHRAE 37–2009,
which is referenced by AHRI 210/240–
2023.
1. Harmonization With Single-Phase
Products
In the October 2018 RFI, DOE stated
that the three-phase equipment at issue
9 The inclusion of appendix M in a normative
appendix means that appendix M was required to
be followed when testing in accordance with ANSI/
AHRI 210/240–2008.
E:\FR\FM\09DEP2.SGM
09DEP2
khammond on DSKJM1Z7X2PROD with PROPOSALS2
70322
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
is often nearly identical to their singlephase counterparts. 83 FR 49501, 49504
(Oct. 2, 2018). Specifically, three-phase
models generally are manufactured on
the same production lines and are
physically identical to their
corresponding single-phase central air
conditioner and central air conditioning
heat pump models except the former
have three-phase electrical systems and
use components, primarily motors and
compressors, that are designed for threephase power input. Id. Other key
operational components, such as heat
exchangers and fans (excluding fan
motors), are typically identical for threephase and single-phase designs of a
given model family. Id. In addition,
most manufacturers’ model numbers for
single-phase products and three-phase
equipment are interchangeable, and
three-phase and single-phase versions of
the same model have the same energy
efficiency ratings. See, e.g., 80 FR
42614, 42622 (July 17, 2015), and 83 FR
49501, 49504 (Oct. 2, 2018).
The October 2018 RFI raised the
question of whether DOE should align
its test procedure for 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h with the test
procedure for single-phase central air
conditioners and central air
conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h. DOE
requested comments and information on
the merits of referencing the current
version of appendix M, or some portion
thereof, for the three-phase systems at
issue versus the merits of referencing
the updated AHRI 210/240–2017, which
reflects the updated appendix M. 83 FR
49501, 49504 (Oct. 2, 2018).
DOE notes that the October 2018 RFI
did not discuss 3-phase VRF with
cooling capacity of less than 65,000 Btu/
h, as AHRI had not updated the scope
of its industry standards for this
equipment at that time. As previously
noted in this document, this equipment
does not currently exist on the market;
however, DOE expects that any such
equipment introduced to the market in
the future would—for the same reasons
discussed earlier—presumably be nearly
identical to its single-phase
counterparts, which are a subset of
single-phase central air conditioners
and central air conditioning heat pumps
with a cooling capacity of less than
65,000 Btu/h.
In response to the October 2018 RFI,
all commenters supported harmonizing
the test procedures for both 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h, and
single-phase central air conditioners
and central air conditioning heat pumps
with a cooling capacity of less than
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
65,000 Btu/h.10 (CA IOUs, No. 2 at pp.
1–2; Ingersoll Rand, No. 3 at p. 2; AHRI,
No. 4 at pp. 1–2; NRDC and ASAP, No.
5 at pp. 1–2; Lennox, No. 6 at pp. 1–2;
Carrier, No. 7 at p. 1; Goodman, No. 8
at pp. 1–3) Specifically, AHRI, Lennox,
Carrier, and Goodman supported
harmonizing the two test procedures by
referencing the industry standard.
(AHRI, No. 4 at p. 2; Lennox, No. 6 at
pp. 1–2; Carrier, No. 7 at p. 1; Goodman,
No. 8 at p. 2) Lennox noted that EPCA
requires that the test procedure for this
equipment be those generally accepted
industry test procedures. (Lennox, No. 6
at p. 1) Others, however, suggested that
DOE harmonize the two test procedures
by adopting appendix M. (CA IOUs, No.
2 at p. 2; NRDC and ASAP, No. 5 at pp.
1–2) CA IOUs suggested that DOE
reference DOE’s own regulatory text,
and NRDC and ASAP preferred this
approach to ensure consistency and
transparency. (CA IOUs, No. 2 at p. 2;
NRDC and ASAP, No. 5 at p. 2) Ingersoll
Rand agreed that harmonization of the
test procedures is advantageous and
reduces burden, but did not specify
which test procedure DOE should
reference. (Ingersoll Rand, No. 3 at p. 2)
Beginning January 1, 2023, Appendix
M1 specifies that single-phase central
air conditioners and central air
conditioning heat pumps must be tested
according to appendix M1. The version
of AHRI 210/240 available at the time of
the October 2018 RFI publication, AHRI
210/240–2017, does not contain updates
to account for the more recent changes
contained in appendix M1. DOE noted
in the October 2018 RFI that AHRI
intended to address appendix M1, by
revising AHRI 210/240–2017. In the
October 2018 RFI, DOE requested
comment on the appropriateness of
testing 3-phase ACUACs and ACUHPs
with cooling capacity of less than
65,000 Btu/h according to appendix M1.
83 FR 49501, 49504–49505 (Oct. 2,
2018).
Carrier, Goodman, and AHRI urged
DOE to wait until AHRI finishes
updating AHRI 210/240 to reference the
version that would include both
appendix M1 and appendix M. (Carrier,
No. 7 at p. 2; Goodman, No. 8 at pp. 1–
2; AHRI, No. 4 at p. 2) The CA IOUs
supported several changes that were
made as part of appendix M1, including
changes to the coil-only test, new
external duct static pressure ratings, and
the heating load line increase for heat
pump HSPF tests. (CA IOUs, No. 2 at p.
2) The CA IOUs stated that by including
these changes that were made to
10 All comments are available at
www.regulations.gov, in Docket No. EERE–2017–
BT–TP–0031.
PO 00000
Frm 00008
Fmt 4701
Sfmt 4702
appendix M1, three-phase equipment
should be subject to the same
requirements as single-phase
equipment. (Id.) NRDC and ASAP
supported adopting appendix M1 for
three-phase equipment and noted that
applying appendix M1 in the future
along with revised standards will
maximize consistency and minimize
testing burden. (NRDC and ASAP, No. 5
at p. 2) Lennox agreed with DOE that if
DOE adopts the AHRI procedure, it
would not conflict with appendix M or
appendix M1 and would be highly
unlikely to impact measured efficiency
as compared to appendix M. (Lennox,
No. 6 at p. 2)
DOE is proposing to align the test
procedures for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and for 3-phase VRF
with cooling capacity of less than
65,000 Btu/h with the test procedure at
appendix M1 for central air
conditioners, by adopting AHRI 210/
240–2023. As discussed in section
III.E.2.b of this NOPR, AHRI 210/240–
2023 harmonizes with the updated
Federal test method for single-phase
central air conditioners and central air
conditioning heat pumps (i.e., appendix
M1).
DOE also considered whether to
harmonize the current test procedures
for the three-phase equipment
addressed in this document with
appendix M. However, the required 360day compliance lead-time period for test
procedure final rules for ASHRAE
equipment specified in EPCA (42 U.S.C.
6314(d)(1)) would result in little to no
time between the compliance date of the
final rule for this test procedure
rulemaking and January 1, 2023—when
appendix M1 is required for testing
central air conditioners and heat pumps
(and when appendix M will no longer
be used). Therefore, DOE has tentatively
concluded that there would be little
practical benefit to harmonizing the test
procedures for the three phaseequipment addressed in this document
with the current test procedures for
central air conditioners and heat pumps
at appendix M. Further, as described in
the following sub-sections, DOE has
identified errors in AHRI 210/240–2017
with Addendum 1 that DOE has
tentatively determined would need to be
corrected in regulatory text, if DOE
adopted AHRI 210/240–2017 with
Addendum 1.
In the October 2018 RFI, DOE
solicited comment on any other aspect
of its current test procedure for 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h. 83
FR 49501, 49505 (Oct. 2, 2018). The CA
IOUs and NRDC and ASAP
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
recommended that DOE begin
developing a dynamic load-based test
procedure for both three-phase and
single-phase equipment for the next
rulemaking cycle. (CA IOUs, No. 2 at p.
3; NRDC and ASAP, No. 5 at p. 2) These
commenters noted that work on a
Canadian Standards Association
Express Document (‘‘CSA EXP07’’) has
begun the development of a dynamic,
load-based test procedure, and that DOE
should start investigating a dynamic,
load-based test, similar to the test
procedure being developed by the CSA
Group (CSA EXP07 Public Review
Draft/September 2017). (CA IOUs, No. 2
at p. 3; NRDC and ASAP, No. 5 at p. 2).
DOE notes that it is reviewing
documents from the CSA EXP07
development process (e.g., the public
review draft and the more recently
published ‘‘Express Document’’ CSA
EXP07:19) and participating in
stakeholder efforts, such as the Next
Generation Test Method working group
(convened by the American Council for
an Energy-Efficient Economy), to
evaluate load-based, dynamic test
methods.11
2. AHRI 210/240
a. AHRI 210/240–2017 and AHRI 210/
240–2017 With Addendum 1
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Many of the revisions in AHRI 210/
240–2017 are intended to harmonize the
industry test procedure with the
updated Federal test method for singlephase central air conditioners and
central air conditioning heat pumps
with rated cooling capacities of less
than 65,000 Btu/h (i.e., appendix M).
AHRI 210/240–2017 does not contain
the text of appendix M in a normative
appendix (as is the case in Appendix C
of ANSI/AHRI 210/240–2008) and
instead integrates requirements
consistent with appendix M throughout
the standard.12 AHRI 210/240–2017 also
11 A dynamic load-based test method differs from
the steady-state test method currently used in DOE
test procedures for air conditioning and heat pump
equipment. In a steady-state test method, the indoor
room is maintained at a constant temperature
throughout the test. In this type of test, any
variable-speed or variable-position components of
air conditioners and heat pumps are set in a fixed
position, which is typically specified by the
manufacturer. In contrast, a dynamic load-based
test has the conditioning load applied to the indoor
room using a load profile that approximates how
the load varies for units installed in the field. In this
type of test, an air conditioning system or heat
pump is allowed to automatically determine and
vary its control settings in response to the imposed
conditioning loads, rather than relying on
manufacturer-specified settings.
12 For example, AHRI 210/240–2017 includes an
updated table of required tests (Table 7), as well as
provisions related to off-mode power.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
includes additional updates beyond
integrating the revised appendix M.13
AHRI 210/240–2017 with Addendum
1 includes further updates. These
include: Additional and revised
definitions (Section 3); new provisions
regarding multi-split systems, oil
recovery, and refrigerant line length
correction factors (Section 5); specified
tolerances and tests required for
different product types provided in
Table 7 and Table 8 (Section 6);
specified distinctions for total, net,
cooling, and heating capacity (Sections
7, 11, 12, and Appendix C) along with
multiple calculation updates (Section
11); revised testing requirements for
systems with a cooling expansion
device in the outdoor unit (Appendix
D); reduction in the nominal overall
resistance (i.e., R-value) of the thermal
insulation for indoor coil inlet and
outlet duct connections and inclusion of
provisions for sampling devices and
dew-point hygrometers (Appendix E);
and a new appendix that refers to
forthcoming changes to the industry
standard to address the test procedure
in appendix M1 (Appendix K).
While DOE understands that AHRI
210/240–2017 and AHRI 210/240–2017
with Addendum 1 were intended to
harmonize with the Federal test
procedure for central air conditioners
and heat pumps (appendix M), DOE has
identified errors and substantive
differences from appendix M in both
industry test standards. Specifically,
DOE has identified the following issues:
• In Section 11 (‘‘Calculations’’) of
AHRI 210/240–2017 with Addendum 1:
(1) Multiple formulas have
typographical errors; 14 (2) multiple
formulas are inapplicable; 15 and (3) the
section does not include any
specification for the calculation of
efficiency metrics for certain equipment
subtypes: Units with variable-airvolume fans; multiple-indoor blowers;
and Northern triple-capacity heat
pumps (this issue is also present in
AHRI 210/240–2017).
• In Section 5 (‘‘Test Requirements’’),
in Appendix D (‘‘Secondary Capacity
Check Requirements—Normative’’), and
13 For example, AHRI 210/240–2017 has stricter
requirements for heat balance and charge weight
tolerance than appendix M. AHRI 210/240–2017
also includes a detailed calculation section that is
based on ANSI/ASHRAE 37 and ANSI/ASHRAE
116.
14 For example, in Equation 11.64 in Section
11.2.1.2 of AHRI 210/240–2017 with Addendum 1,
the denominator of the second term (enclosed in
braces) should read ‘‘95–82’’ instead of ‘‘95–8’’.
15 For example, Equation 11.187 in Section
11.2.2.3 of AHRI 210/240–2017 with Addendum 1
is not applicable, given that linear interpolation is
used to determine COP at intermediate compressor
speed for units with a variable-speed compressor.
PO 00000
Frm 00009
Fmt 4701
Sfmt 4702
70323
in Appendix E (‘‘ANSI/ASHRAE
Standard 37 Clarifications/Exceptions’’)
of AHRI 210/240–2017 with Addendum
1, there are multiple inconsistencies
with appendix M (many of which are
also present in AHRI 210/240–2017),
such as the following: (1) Section 5
references the wrong table for testing
tolerances for cyclic testing (i.e.,
references ‘‘Table 11’’ in Section 5.2.4
Cycle Stability Requirements, rather
than Table 3b of ASHRAE Standard
116); and (2) Section D7.6.4 specifies
more burdensome condition tolerances
than appendix M for the ‘‘Closed Duct
test’’ of the outdoor air enthalpy
method.16
As noted, EPCA requires that the test
procedure for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h be the generally
accepted industry testing procedure
developed or recognized by AHRI or by
ASHRAE, as referenced in ASHRAE
Standard 90.1. (42 U.S.C. 6314(a)(4)(A))
Further, when the industry test
procedure is amended, DOE must
amend its test procedure to be
consistent with the amended industry
test procedure, unless DOE determines,
by rule published in the Federal
Register and supported by clear and
convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B))
DOE tentatively determines that
significant deviations in regulatory text
would be needed to correct errors in the
referenced industry test standard (e.g.,
correcting and adding certain formulas,
correcting test tolerances for cyclic
testing) if AHRI 210/240–2017 or AHRI
210/240–2017 with Addendum 1 were
to be adopted in the Federal test
procedure for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h. Additionally,
without further deviations in the
regulatory text, testing to AHRI 210/
240–2017 or AHRI 210/240–2017 with
Addendum 1 would still not align with
appendix M, because, as discussed,
there are discrepancies between the
industry test standards and appendix M.
Further, as discussed, there would be
minimal, if any, practical benefit from
16 Section D7.6.4 of AHRI 210/240–2017 with
Addendum 1 specifies condition tolerances for
indoor and outdoor entering air dry-bulb and wetbulb tolerances (the target temperature for each is
the average value measure during the free air test
(‘‘FA’’) test). For each of these temperatures, the
tolerance specified in Section D7.6.4 is half the
condition tolerance specified in Table 9 of
appendix M (e.g., for indoor entering dry-bulb
temperature, Table 9 of appendix M specifies a
condition tolerance of 0.5 °F, while Section 7.6.4.1
specifies a condition tolerance of 0.25 °F).
E:\FR\FM\09DEP2.SGM
09DEP2
70324
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
khammond on DSKJM1Z7X2PROD with PROPOSALS2
harmonizing the test procedure for 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h with the test procedure for singlephase products at appendix M, given
that the applicability of appendix M for
determining compliance of central air
conditioners will end January 1, 2023,
and it is unlikely that a compliance date
for a final rule for this rulemaking,
which would be 360 days after final rule
publication if a final rule is issued,
would precede January 1, 2023 by any
significant amount of time.
For these reasons, DOE has tentatively
concluded that adopting a revised test
procedure (i.e., referencing AHRI 210/
240–2017 or AHRI 210/240–2017 with
Addendum 1, along with the
substantive corrections and deviations
that would be required) for 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h
would be unduly burdensome to
manufacturers. DOE considers the
reasoning discussed in the paragraphs
above to constitute clear and convincing
evidence that adopting AHRI 210/240–
2017 or AHRI 210/240–2017 with
Addendum 1 would not meet the
requirements specified in 42 U.S.C.
6314(a)(2).
As such, DOE proposes to maintain
the current test procedure for 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h,
which incorporates by reference ANSI/
AHRI 210/240–2008, until such time as
compliance with the amended test
procedure referencing AHRI 210/240–
2023 would be required.
Issue 1: DOE seeks comment on its
proposal to maintain reference to ANSI/
AHRI 210/240–2008 with Addenda 1
and 2 as the Federal test procedure for
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h, until such time as compliance would
be required with the amended test
procedure referencing AHRI 210/240–
2023.
b. AHRI 210/240–2023
DOE notes that AHRI 210/240–2023
generally corrects the errors in AHRI
210/240–2017 with Addendum 1 and
harmonizes with the updated Federal
test method for single-phase central air
conditioners and central air
conditioning heat pumps with rated
cooling capacities of less than 65,000
Btu/h (i.e., appendix M1, effective
January 1, 2023), which includes singlephase, air-cooled, VRF multi-split
systems with a cooling capacity of less
than 65,000 Btu/h. The industry
standard updates the performance
metrics to EER2, SEER2 and HSPF2.
Significant changes related to the new
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
efficiency metrics include higher
minimum external static pressure
(‘‘ESP’’) requirements for conventional
systems (Table 10) and changes in the
building heating load line for HSPF2
(Section 11). Additional changes in
AHRI 210/240–2023 to align with
appendix M1 include the addition of:
(1) Minimum ESP requirements in Table
10 for varieties of ducted blower
systems specified in appendix M1 (i.e.,
ceiling- and wall-mount, mobile home,
and low/mid static); (2) a separate unit
configuration of single stage system
with a single variable-speed variable-airvolume blower or multiple indoor
blowers in Table 7; and (3) the optional
H4 test (i.e., the full-load heating test at
5 °F ambient temperature) in Table 7.
These changes apply for testing of both
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h.
In addition, AHRI 210/240–2023
reflects and is consistent with DOE’s
appendix M1, which will be the
required test procedure for single-phase
central air conditioners and central air
conditioning heat pumps with
capacities of less than 65,000 Btu/h
beginning January 1, 2023. No
commenters suggested that the test
procedure in appendix M1 would be
inappropriate for the testing of threephase equipment.
As discussed, the updates contained
in AHRI 210/240–2023 provide for
measuring energy efficiency using the
SEER2 and HSPF2 metrics, which are
the metrics adopted by ASHRAE
Standard 90.1–2019 for the 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h
standards beginning January 1, 2023.17
In response to this update to AHRI 210/
240, DOE proposes to incorporate AHRI
210/240–2023 as the test procedure with
which representations must be made
beginning with the compliance date of
any amended DOE standards for threephase equipment relying on SEER2 and
HSPF2 as the metrics.18
Harmonization of the test procedures
would provide for more comparable
17 ASHRAE 90.1–2019 did not update the metrics
for air-cooled, three-phase, variable refrigerant flow
air conditioners and heat pumps with a cooling
capacity of less than 65,000 Btu/h. Those metrics
remain SEER and HSPF in ASHRAE Standard 90.1.
18 The timing and implementation of any
amended standards may be different for air-cooled,
three-phase, small commercial package air
conditioning and heating equipment with a cooling
capacity of less than 65,000 Btu/h and for aircooled, three-phase variable refrigerant flow air
conditioners and heat pumps with a cooling
capacity of less than 65,000 Btu/h, depending on
DOE rulemaking related to energy conservation
standards for those separate categories of
equipment.
PO 00000
Frm 00010
Fmt 4701
Sfmt 4702
information between three-phase
equipment and single-phase products.
Commercial customers considering
either single-phase or three-phase
equipment would have ratings for both
sets of equipment that are based on
identical testing requirements when
evaluating product options. Because
AHRI 210/240–2023 aligns with
appendix M1, the proposed
incorporation of this industry testing
procedure for the three-phase
equipment at issue would produce
comparable ratings between singlephase and three-phase equipment (as
discussed in section III.E.1 of this
NOPR). Consequently, DOE has
tentatively concluded that this proposed
test procedure would not be unduly
burdensome to conduct.
Only certain sections of AHRI 210/
240–2023 apply to the DOE test
procedures for the three-phase
equipment that is the subject of this
NOPR. Therefore, DOE is proposing to
reference AHRI 210/240–2023 in the
proposed test procedure at appendix B1
except for the following sections:
• Section 6—Rating Requirements
(these provisions are not related to the
method of test and DOE separately
addresses these topics in 10 CFR part
429):
Æ Sections 6.1.8, 6.4.1, 6.4.2, 6.4.3,
6.4.4 (minimum testing and certification
requirements);
Æ Sections 6.2 and 6.4.6 (permit a
given product to have multiple ratings
of different values);
Æ Section 6.5 (uncertainty allowances
for testing, which are not relevant to the
Federal test procedure);
• Sections 7 through 10, Appendix C,
and Appendix I (these are relevant only
to AHRI’s certification program);
• Appendix F: Sections F15.2 and
F17 (these pertain to electrical
measurements and cyclic tolerances,
respectively; DOE proposes
modifications as discussed in the
following paragraphs);
• Appendix G (pertains to
configuration of the unit under test,
discussed in the following paragraphs);
• Appendix H (pertains to Off-Mode
testing, which is not required by DOE
for three-phase equipment).
Regarding energy measurement
provisions, section 2.8 of appendix M
requires that the watt-hour (i.e., ‘‘W·h’’,
also referred to as ‘‘integrated power’’ or
‘‘energy’’) measuring system give
readings that are accurate to within ±0.5
percent. In response to the October 2018
RFI, Carrier recommended that section
2.8.a of appendix M be revised to
include a lower limit (i.e., ‘‘greater of 0.5
percent of reading or 0.5 watts’’), stating
that, without a lower limit, compliance
E:\FR\FM\09DEP2.SGM
09DEP2
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
with this requirement at times of low
power (e.g., during an OFF cycle) can be
difficult for single-phase equipment and
possibly unrealistic for three-phase
equipment. (Carrier, No. 7 at p. 2)
Section F15.2 of AHRI 210/240–2023
addresses Carrier’s concern by adding a
lower limit, stating that the ‘‘watt-hour
measurement system shall be accurate
within ±0.5 percent or 0.5 W/h,
whichever is greater’’. However, Section
F15.2 of AHRI 210/240–2023 specifies
incorrect units of measurement and
should refer to watt hours (W·h)
(consistent with the first words of
Section F15.2) rather than to ‘‘W/h’’.
Therefore, DOE proposes not to
reference Section F15.2, and instead to
adopt similar provisions in section 3 of
appendix B1 that correct the units of
measurement to W·h.
Regarding cyclic test tolerances,
Section F17 of AHRI 210/240–2023
appears to incorrectly reference
ASHRAE 37 Table 2b for cyclic test
operating and condition tolerances.
ASHRAE 37 Table 2b does not specify
tolerances specific to cyclic testing.
Instead, as specified in footnote 1 to
Table 8 of AHRI 210/240–2023, the
tolerances in ASHRAE Standard 116
Table 3b (titled ‘‘Test Tolerances for
Cyclic Performance Tests’’) should be
used for cyclic testing. Therefore, DOE
proposes not to reference Section F17,
and instead to adopt similar provisions
in section 4 of appendix B1 that do not
reference ASHRAE 37 test tolerances.
Regarding Appendix G, currently
enforcement testing of 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h falls under DOE’s
Commercial HVAC Enforcement
Policy,19 which outlines how certain
features of this equipment will be
treated for compliance testing. In
Appendix G of AHRI 210/240–2023,
AHRI included a list of components that
must be present for testing (Section
G1.2) and a list of features that are
optional for testing (Section G2), which
provides additional instruction to
address certain of these features and
additional details that are beyond the
scope of the current Commercial HVAC
Enforcement Policy. Also, there are five
features 20 that are included in the
Commercial HVAC Enforcement Policy
for 3-phase ACUACs and ACUHPs with
19 The enforcement policy for commercial HVAC
equipment can be found at www.energy.gov/gc/
downloads/commercial-equipment-testingenforcement-policies.
20 These five features are high-static indoor
blower or oversized motor; desuperheaters; outdoor
fan with Variable Frequency Drive (‘‘VFD’’); indoor
fan with VFD; and compressor with VFD.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
cooling capacity of less than 65,000 Btu/
h that are not included in Section G2 of
AHRI 210/240–2023.
DOE has reviewed the market for 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h in connection with the specific
treatment of components and optional
features suggested in Appendix G of
AHRI 210/240–2023. DOE found that
certain optional features listed in
Section G2 (as well as certain features
that are included in DOE’s current
Commercial HVAC Enforcement Policy
but not included in Section G2 of AHRI
210/240–2023) are present in models of
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h. However, these same features are also
present in models of single-phase
central air conditioners and central air
conditioning heat pumps with cooling
capacity of less than 65,000 Btu/h. As
discussed in section III.E.1, in response
to the October 2018 RFI, all commenters
supported fully harmonizing the test
procedures for both 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and single-phase
central air conditioners and central air
conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h,
which aligns with the proposals in this
NOPR. DOE’s Commercial HVAC
Enforcement Policy does not apply to
single-phase products and appendix M
and M1 do not include any special
treatment for these optional features
within the test procedure. In addition,
DOE has not received any waivers
related to these features and DOE does
not have technical justification to
support differential treatment of such
features for three-phase equipment as
compared to single-phase products. As
such, DOE has tentatively determined
that any of these features present in 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h can also be tested in accordance with
the proposed test procedure and that to
maintain harmonization with singlephase products, it is not necessary or
appropriate to adopt Appendix G of
AHRI 210/240–2023 as part of DOE’s
test procedure. While there are currently
no models on the market of 3-phase VRF
with cooling capacity of less than
65,000 Btu/h, DOE expects that, if there
were, the same tentative determination
would apply for the same reasons. Were
DOE to adopt the proposals in this
NOPR, DOE would rescind the
Commercial HVAC Enforcement Policy
to the extent that it is applicable to 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and 3-phase VRF with cooling
PO 00000
Frm 00011
Fmt 4701
Sfmt 4702
70325
capacity of less than 65,000 Btu/h. DOE
notes that all models (with or without
any specific feature) may be tested by
DOE at any time under DOE’s current
authorities if such a model is distributed
in commerce in the U.S.
Issue 2: DOE seeks comment on its
proposal to incorporate by reference
AHRI 210/240–2023 in the DOE test
procedure for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h. DOE also seeks comment
on its proposal to require compliance
with this test procedure on the
compliance date of any amended energy
conservation standards that DOE may
decide to adopt later as part of a future
rulemaking.
3. AHRI 1230
In May 2021, AHRI published AHRI
1230–2021, which excludes from its
scope 3-phase VRF with cooling
capacity of less than 65,000 Btu/h. As
such, in this NOPR, DOE is considering
revisions based on updated versions of
AHRI 210/240 only, as AHRI 1230–2021
by its explicit terms is not applicable to
the equipment considered in this NOPR.
As discussed, DOE is proposing to
reference AHRI 210/240–2023 for
testing 3-phase VRF with cooling
capacity less than 65,000 Btu/h. As
proposed, the current Federal test
procedure for this equipment (which
references ANSI/AHRI 1230–2010),
would remain the required test
procedure until DOE decides to adopt
amended energy conservation standards
for this equipment.
4. ASHRAE 37
ANSI/ASHRAE Standard 37, which
provides a method of test for many
categories of air conditioning and
heating equipment, is referenced for
testing by all versions of AHRI
Standards 210/240 and 1230. Appendix
E of AHRI 210/240–2023 provides
additional instruction and exceptions
regarding the application of the test
methods specified in ANSI/ASHRAE
37–2009. ANSI/ASHRAE 37–2009 is
referenced in ANSI/AHRI 1230–2010,
which is currently the referenced
industry test standard in the DOE test
procedure for VRF multi-split systems.
ANSI/ASHRAE 37–2005 is referenced
by ANSI/AHRI 210/240–2008, which is
currently the referenced industry test
standard in the DOE test procedure for
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000
Btu/h.
Given the use of ANSI/ASHRAE 37–
2009 when testing according to AHRI
210/240–2023, DOE is proposing to
E:\FR\FM\09DEP2.SGM
09DEP2
70326
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
khammond on DSKJM1Z7X2PROD with PROPOSALS2
reference ANSI/ASHRAE 37–2009 in its
test procedure for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h. Specifically, in the
proposed appendix B1, DOE is
proposing to reference the applicable
sections of ANSI/ASHRAE 37–2009—
i.e., all sections except sections 1, 2 and
4.21
F. Certification, Compliance, and
Enforcement Requirements
In the October 2018 RFI, DOE also
requested comment on whether the
general structure and language related to
its certification, compliance, and
enforcement requirements for threephase equipment in 10 CFR part 429
should mirror the structure and
language of certification, compliance,
and enforcement requirements for
single-phase products already found in
10 CFR part 429. 83 FR 49501, 49505
(Oct. 2, 2018). DOE noted in the October
2018 RFI that AHRI 210/240–2017
included many updates to mirror these
requirements, which apply to both
single-phase products and three-phase
equipment. Id.
CA IOUs, Ingersoll Rand, and NRDC
and ASAP supported adopting the
certification, compliance, and
enforcement requirements for singlephase systems and applying them to
three-phase systems. (CA IOUs, No. 2 at
p. 2; Ingersoll Rand, No. 3 at p. 2; NRDC
and ASAP, No. 5 at p. 2) AHRI stated
that single-phase reporting requirements
are significantly more onerous than
what has historically been reported, and
that the reporting requirements for both
consumer and commercial products
should be simplified. (AHRI, No. 4 at p.
2) Carrier supported harmonizing threephase and single-phase requirements in
10 CFR part 429, stating that while the
single-phase reporting requirements are
significantly more onerous than what
has historically been reported, aligning
the reporting for the residential and
commercial products is the simplest
way to reduce manufacturer burden.
(Carrier, No. 7 at p. 2)
After reviewing the comments, and
given that AHRI has updated Standard
210/240 to include many of the
requirements found in 10 CFR 429.16,
DOE proposes to amend its
representation requirements for 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and
for 3-phase VRF with cooling capacity
21 DOE is proposing to exclude reference to
Section 1 (‘‘Purpose), Section 2 (‘‘Scope’’), and
Section 4 (‘‘Classifications’’) in ANSI/ASHRAE 37–
2009 to avoid any potentially contradictory
requirements with DOE regulations.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
of less than 65,000 Btu/h by applying
certain requirements currently
applicable to single-phase central air
conditioners and central air
conditioning heat pumps (currently
specified at 10 CFR 429.16 and 10 CFR
429.70(e)).22 DOE is not proposing to
amend its certification reporting
requirements for the three-phase
equipment that is the subject of this
NOPR.
DOE is proposing to amend the basic
model definition and product-specific
enforcement provisions for the threephase equipment specified at 10 CFR
431.92 and 10 CFR 429.134,
respectively, to align with the
provisions for single-phase products.
Harmonizing the representation
requirements for three-phase equipment
with the representation requirements for
single-phase products, as discussed,
would not increase manufacturer
burden as compared to industry practice
under the industry certification
program. Further, these proposals
would not apply until such time as DOE
amends the energy conservation
standards for this equipment to rely on
SEER2 and HSPF2. Therefore, these
proposals would not impose an undue
burden on manufacturers. DOE’s
proposals are discussed in detail in the
following sub-sections.
1. Representation Requirements
As discussed, DOE is proposing to
amend certain representation
requirements for the three-phase
equipment addressed by this NOPR, to
align with their single-phase
counterparts. As part of this proposal,
DOE is proposing to relocate its
representation and certification
requirements for three-phase
equipment. Specifically, DOE is
proposing that the representation and
certification requirements for this threephase equipment would be included in
a new section 10 CFR 429.64 and
excluded from the scope of 10 CFR
429.43. DOE is also proposing to
establish a new section 10 CFR 429.70(i)
for alternative energy determination
method (‘‘AEDM’’) requirements that
would apply to the three-phase
equipment addressed in this NOPR. As
proposed, manufacturers would not be
required to comply with the amended
representation requirements, if made
final, until such time that amended
standards are established that would
22 DOE notes that these single-phase requirements
are consistent with a consensus recommendation
made by the Central Air Conditioners and Heat
Pumps Working Group of the Appliance Standards
and Rulemaking Federal Advisory Committee. (See
CAC/HP Term Sheet, Docket No. EERE–2014–BT–
STD–0048, No. 0076, Recommendation #7.)
PO 00000
Frm 00012
Fmt 4701
Sfmt 4702
require compliance with amended
energy conservation standards that rely
on SEER2 and HSPF2 (as applicable).
In particular, 10 CFR 429.43, which is
applicable to commercial heating,
ventilating, and air conditioning
equipment, requires determination of
the represented value for each basic
model through either testing or by
applying an AEDM, and 10 CFR
429.70(c)(2)(iv) specifies that each
AEDM must be validated by testing at
least two basic models. Under 10 CFR
429.16, which is applicable to central
air conditioners and central air
conditioning heat pumps, determination
of represented values is based on each
individual model or combination (rather
than for each basic model), and
generally requires a minimum level of
testing for each basic model. For all
basic models except outdoor units with
no match and multi-split systems,
multi-circuit systems, and multi-head
mini-split systems, represented values
for individual models or combinations
other than those required to be tested
may be determined by using an AEDM
in accordance with 10 CFR 429.70(e),
with no additional testing required to
validate the AEDM beyond the
minimum testing required by 10 CFR
429.16. For outdoor units with no match
and multi-split systems, multi-circuit
systems, and multi-head mini-split
systems, 10 CFR 429.16 contains
additional requirements for determining
represented values.
Through its newly proposed
provisions in 10 CFR 429.64 and 10 CFR
420.70(i), DOE would mirror the
representation requirements in 10 CFR
429.16 and 10 CFR 429.70(e), except for
the minimum testing requirements and
certain AEDM validation requirements
for each basic model of single-package
unit and single-split systems. As
discussed, 10 CFR 429.16 for central air
conditioners and central air
conditioning heat pumps generally
requires testing for every basic model.
For 3-phase equipment, DOE proposes
in 10 CFR 429.64 to generally maintain
the current approach that not all basic
models of three-phase, less than 65,000
Btu/h single-package units and single
split-systems must be tested. The
following paragraphs describe in further
detail DOE’s proposal that would allow
a manufacturer to use an AEDM for
rating all basic models of three-phase,
less than 65,000 Btu/h single-package
units and single split-systems in the
case that the manufacturer rates all
models with AEDMs validated with
testing of otherwise identical singlephase models (i.e., no testing of 3-phase
equipment required), and would require
testing of only two basic models of 3-
E:\FR\FM\09DEP2.SGM
09DEP2
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
phase equipment in other cases (e.g.,
manufacturers that do not rate with an
AEDM validated with testing of an
otherwise identical single-phase model).
DOE has initially determined that an
AEDM validated pursuant to 10 CFR
429.70(e) would also be appropriate for
rating basic models of three-phase, less
than 65,000 Btu/h single-package units
and single split-systems that have
otherwise identical single-phase
counterparts. Specifically, DOE
understands that the vast majority of
three-phase equipment with a cooling
capacity of less than 65,000 Btu/h has
an otherwise identical single-phase
consumer product counterpart offered
by the same manufacturer, thus
providing comparable performance
between single-phase products and
three-phase equipment with a cooling
capacity of less than 65,000 Btu/h.
Further, DOE has tentatively concluded
that any slight differences in
performance between single-phase and
three-phase models (e.g., minor
differences in compressor performance
depending on the electrical phase of the
compressor motor) are well understood
and can be accounted for within an
AEDM (e.g., slightly different
compressor coefficients used to model
performance for single-phase vs threephase compressors), rather than
requiring testing of three-phase models.
Therefore, DOE has tentatively
determined that for three-phase, less
than 65,000 Btu/h single-package units
and single split-systems with otherwise
identical single-phase counterparts,
ratings developed using an AEDM
validated with the testing of otherwise
identical single-phase central air
conditioners and heat pumps would be
no less representative than ratings
developed using an AEDM validated
with the testing of three-phase, less than
65,000 Btu/h equipment.
As such, for three-phase, less than
65,000 Btu/h single-package units and
single split-systems, DOE proposes in 10
CFR 429.70(i)(2) to permit a
manufacturer to rely on an AEDM for
central air conditioners and heat pumps
that is validated in accordance with 10
CFR 429.70(e)(2) with testing of
otherwise identical single-phase
counterparts, without additional
validation testing.23 If a manufacturer
offers three-phase models that do not
have otherwise identical single-phase
counterparts, or the manufacturer has
not validated an AEDM in accordance
with 10 CFR 429.70(e)(2) with testing of
23 While the AEDM would not need additional
validation testing, it would need to reflect the slight
difference in performance between single-phase and
three-phase components.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
the otherwise identical single-phase
counterparts, the manufacturer would
be required to test a single unit sample
for each of two basic models to validate
an AEDM, consistent with the existing
requirements for all capacities of threephase equipment. DOE expects that this
case would arise only for a small
number of manufacturers who do not
produce otherwise identical singlephase and three-phase equipment, but
instead manufacture a line of
commercial three-phase equipment that
includes equipment below DOE’s 65,000
Btu/h capacity boundary.
In conjunction with this proposal,
DOE proposes to specify in the newly
proposed 10 CFR 429.70(i)(3) that
‘‘otherwise identical’’ means differing
only in the phase of the electrical
system and the phase of power input for
which the motors and compressors are
designed.
Issue 3: DOE seeks comment on its
proposal to align the representation
requirements for the three-phase
equipment addressed by this NOPR
with the requirements specified for
single-phase products at 10 CFR 429.16
and 10 CFR 429.70(e),—but with the
exception of testing requirements and
certain AEDM validation requirements
for single-package and single-split
system models. Specifically, DOE
requests comment on its proposal to
permit for three-phase, less than 65,000
Btu/h single-package and single-split
system basic models with otherwise
identical single-phase counterparts the
use of ratings based on an AEDM
validated using the test results from
otherwise identical central air
conditioners and heat pumps, rather
than requiring validation using the test
results of three-phase models. DOE also
requests comment on its proposed
specification of the term ‘‘otherwise
identical’’. Finally, DOE requests
comment on whether the proposed
AEDM requirements should include a
provision to validate the correlation
between single-phase and three-phase
performance as determined using an
AEDM.
As part of the harmonization with
single-phase requirements, the proposal
in 10 CFR 429.64 would require that all
representations for outdoor units with
no match and for multi-split systems,
multi-circuit systems, and multi-head
mini-split systems must be determined
through testing or other specified
means, rather than through an AEDM.
As currently specified, 10 CFR
429.16(c)(2)–(3) do not permit AEDMs
for single-phase products with these
configurations; as such, there would not
be any extensively validated AEDMs
available for products and equipment
PO 00000
Frm 00013
Fmt 4701
Sfmt 4702
70327
with these configurations. DOE is not
aware of any three-phase models on the
market with these configurations (i.e.,
outdoor unit with no match or multisplit, multi-circuit, and multi-head
mini-split systems); therefore, DOE
tentatively concludes that this proposal
would not result in increased testing
burden or costs for any manufacturer.
DOE may consider permitting the use of
an AEDM for these three-phase
equipment categories if interested
parties were to demonstrate a market for
this equipment and provide information
on what requirements for AEDM
validation should be specified.
Issue 4: DOE seeks comment on
whether there are three-phase, less than
65,000 Btu/h models of outdoor units
with no match or multi-split, multicircuit, and multi-head mini-split
systems on the market, and, if so,
whether AEDMs should be allowed for
their ratings and what requirements for
AEDM validation should be specified.
DOE notes that, as part of the
harmonization with single-phase
requirements, the proposal in 10 CFR
429.64 would require every individual
combination of single-split-system AC
equipped with a single-stage or twostage compressor distributed in
commerce to be rated as a coil-only
combination, with additional blowercoil representations allowed as
applicable. As discussed previously in
this section, the three-phase equipment
category may include models that are
part of a line of commercial three-phase
equipment that includes equipment
below DOE’s 65,000 Btu/h capacity
boundary (rather than models that are
otherwise identical to single-phase
central air conditioners). Based on
review of models certified in the DOE
Compliance Certification Database, DOE
expects almost all of these models to be
packaged units, which are not impacted
by this proposal.
Issue 5: DOE seeks comment on
whether there are models of three-phase
single-split-system air conditioners with
single-stage or two-stage compressors
that are not distributed in commerce as
a coil-only combination (i.e., distributed
in commerce only as blower-coil
combination(s)).
2. Basic Model Definition
DOE proposes to amend its basic
model definition for 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and for 3-phase
VRF with cooling capacity of less than
65,000 Btu/h to align with that for
single-phase central air conditioners
and central air conditioning heat
pumps, as this definition forms the basis
for the requirements in 10 CFR 429.16.
E:\FR\FM\09DEP2.SGM
09DEP2
70328
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
khammond on DSKJM1Z7X2PROD with PROPOSALS2
The current definition of basic model
for three-phase equipment in 10 CFR
431.92 refers to ‘‘all units manufactured
by one manufacturer within a single
equipment class, having the same or
comparably performing compressor(s),
heat exchangers, and air moving
system(s) that have a common
‘‘nominal’’ cooling capacity.’’ See 10
CFR 431.92(2).24 The definition of
‘‘basic model’’ for single-phase products
in 10 CFR 430.2 provides additional
specifications on this same concept. See
10 CFR 430.2 (defining the term ‘‘basic
model’’ and detailing the application of
this term to different configurations of
central air conditioners and central air
conditioner heat pumps). For example,
for split systems manufactured by
outdoor unit manufacturers, a basic
model includes all individual
combinations having the same model of
outdoor unit but with percentage
variation limits on compressor, outdoor
coil, and outdoor fan characteristics. See
id.
Issue 6: DOE requests comment on its
proposal to align the definition of basic
model for three-phase equipment at 10
CFR 431.96 with that for single-phase
products at 10 CFR 430.2.
3. Certification Reporting Requirements
DOE acknowledges that 10 CFR
429.16 currently requires more detail in
filed certification reports than that
required by 10 CFR 429.43. Therefore,
DOE proposes to retain the requirements
for certification reports (i.e., the
information that must be reported for
each individual model or combination)
currently found in 10 CFR 429.43 rather
than adopting wholesale the
certification report requirements for
single-phase products found in 10 CFR
429.16.
In response to the October 2018 RFI,
Carrier commented that the three-phase
requirements should mirror the
structure, language, and certification
requirements for single-phase systems to
minimize the manufacturer’s burden.
(Carrier, No. 7 at p. 2). In general, DOE
agrees with Carrier’s comments that
further aligning certification reporting
requirements across single-phase
products and three-phase equipment
could reduce overall manufacturer
burden despite the additional singlephase requirements. Therefore, should
interested parties provide detail as to
which information required as part of
the certification reports required under
10 CFR 429.16(e) would be particularly
burdensome to report and not impact
24 The definition applicable to variable refrigerant
flow systems is different in wording but similar in
content. See 10 CFR 431.92(5).
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
DOE’s ability to conduct enforcement
testing, DOE may consider changes to
the reporting requirements for both
single-phase products and three-phase
equipment in a separate rulemaking.
In addition, DOE may consider minor
revisions to the certification reporting
requirements in any energy
conservation standards rulemaking that
DOE may conduct for this equipment.
Issue 7: DOE seeks comment on its
proposal not to amend certification
reporting requirements for the threephase equipment subject to this notice
to align with single-phase products at
this time. DOE also requests details on
whether any particular certification
reporting requirements in 10 CFR
429.16(e) are particularly problematic
for manufacturers (for both single-phase
products and three-phase equipment)
and why.
4. Product-Specific Enforcement
Provisions
DOE is proposing to amend its
product-specific enforcement
requirements by adding provisions to a
new 10 CFR 429.134(s) for the threephase equipment addressed in this
NOPR that would align with those
already required at 10 CFR 429.134(k)
for single-phase products. These
provisions would pertain only to DOE
assessment and enforcement testing and
would not impact manufacturer testing.
Additionally, these requirements would
apply only to equipment subject to any
potential standards that DOE may set in
terms of SEER2 and HSPF2.
Regarding cooling capacity, DOE is
proposing that the cooling capacity of
each tested unit would be measured
pursuant to the test procedure and that
the mean of the measurement(s) would
be used to determine compliance with
the applicable standards.
Regarding cyclic degradation
coefficients, which are a measure of
efficiency loss that would occur as a
result of the compressor cycling to meet
a low load level in field applications,
DOE is proposing to measure the
cooling and/or heating cyclic
degradation coefficient, CDc/CDh,
respectively, by conducting the optional
cyclic tests if the manufacturer certifies
that they conducted the optional cyclic
tests. If the manufacturer certifies that it
did not conduct the optional cyclic
tests, the proposal would require that
the default CDc/CDh values would be
used as the basis for calculating SEER or
HSPF for each unit tested.
G. Test Procedure Costs
EPCA requires that the test
procedures for commercial package air
conditioning and heating equipment for
PO 00000
Frm 00014
Fmt 4701
Sfmt 4702
small commercial package air
conditioning and heating equipment,
which includes 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h, be generally accepted
industry testing procedures or rating
procedures developed or recognized by
either AHRI or ASHRAE, as referenced
in ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A)) Further, if such an
industry test procedure is amended,
DOE must amend its test procedure to
be consistent with the amended
industry test procedure, unless DOE
determines, by rule published in the
Federal Register and supported by clear
and convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C.
6314(a)(2)–(3) related to representative
use and test burden. (42 U.S.C.
6314(a)(4)(B))
In this NOPR, DOE proposes to amend
the existing test procedures for threephase, less than 65,000 Btu/h
equipment by incorporating by
reference, with some modification, the
updated version of the applicable
industry test method, AHRI 210/240–
2023, including the energy efficiency
metrics SEER2 and HSPF2. DOE also
proposes to amend certain
representation requirements to more
closely align with the representation
requirements for single-phase central air
conditioners and heat pumps.
Amendments to both the test procedures
and representation requirements in this
NOPR are consistent with comments
from interested parties who supported
aligning the Federal regulations for the
three-phase equipment addressed in this
document with the regulations of their
single-phase consumer product
counterparts.
DOE has tentatively determined that
these proposed test procedures would
be representative of an average use cycle
and would not be unduly burdensome
for manufacturers to conduct. The
proposed appendix B, measuring both
SEER and HSPF per ANSI/AHRI 210/
240–2008, does not contain any changes
from the current Federal test procedure,
and therefore would not require
retesting solely as a result of DOE’s
adoption of this proposed amendment.
The proposed test procedure in
appendix B1, measuring both SEER2
and HSPF2 per AHRI 210/240–2023,
would not lead to an increase in cost
from appendix B testing. Specifically,
DOE estimates that the cost for thirdparty lab testing according to the
proposed appendix B1 would be $5,500
for air conditioners and $8,500 for heat
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
khammond on DSKJM1Z7X2PROD with PROPOSALS2
pumps, consistent with the current test
procedures.
As discussed in section III.F.1 of this
NOPR, DOE is proposing to amend the
representation requirements for
certifying basic models of three-phase,
less than 65,000 Btu/h equipment to
harmonize with the requirements for
single-phase products. For models of
outdoor units with no match and multisplit, multi-circuit, and multi-head
mini-split systems, this proposal may
increase testing requirements for threephase equipment compared to the
existing requirements. However, DOE is
not aware of any such models on the
market in these categories—accordingly,
DOE does not believe the proposed
representation requirements will lead to
an increase in testing cost for any
manufacturer.
As discussed in section III.F.1 of this
NOPR, DOE is proposing to amend the
AEDM 25 requirements for certifying
basic models of three-phase, less than
65,000 Btu/h single-package units and
single-split systems. Because most
manufacturers’ models of three-phase,
less than 65,000 Btu/h equipment are
nearly identical to the corresponding
single-phase, consumer products, DOE
is proposing to allow the use of an
AEDM validated using testing of
otherwise identical single-phase
counterparts for certifying basic models
of three-phase, less than 65,000 Btu/h
single package units and split systems.
For manufacturers that produce both
single-phase consumer products and
three-phase, less than 65,000 Btu/h
equipment, this proposal would reduce
any burden that might result from the
proposed test procedures in appendix
B1 of this NOPR, because for such
manufacturers all certification of threephase, less than 65,000 Btu/h
equipment could be conducted using
AEDMs without resorting to the testing
of three-phase, less than 65,000 Btu/h
equipment.
As discussed previously throughout
this NOPR, the proposed test procedure
in appendix B1 would not be mandatory
until such time as DOE decides whether
to amend the energy conservation
standards based on SEER2 and HSPF2.
Given that most manufacturers of threephase equipment that are the subject of
25 Manufacturers
are not required to perform
laboratory testing on all basic models. In
accordance with 10 CFR 429.70, three-phase, less
than 65,000 Btu/h manufacturers may elect to use
AEDMs. An AEDM is a computer modeling or
mathematical tool that predicts the performance of
non-tested basic models. These computer modeling
and mathematical tools, when properly developed,
can provide a means to predict the energy usage or
efficiency characteristics of a basic model of a given
covered product or equipment and reduce the
burden and cost associated with testing.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
this NOPR are AHRI members, and DOE
is referencing the prevailing industry
test procedure that was established for
use in AHRI’s certification program
(which DOE presumes will be updated
to include SEER2 and HSPF2), DOE
expects that manufacturers will already
be testing using the test methods in
AHRI 210/240–2023 by January 1,
2023—the effective date for minimum
SEER2 and HSPF2 levels in ASHRAE
90.1–2019 for three-phase equipment,
and also the compliance date for testing
according to appendix M1 for singlephase central air conditioners. Based on
this expectation, DOE also has
tentatively determined that the
proposed test procedure amendments
would not be expected to increase the
testing burden on three-phase, less than
65,000 Btu/h equipment manufacturers.
Additionally, DOE has tentatively
determined that the test procedure
amendments, if finalized, would not
require manufacturers to redesign any of
the covered equipment, would not
require changes to how the equipment
is manufactured, and would not impact
the utility of the equipment.
Issue 8: DOE requests comment on its
understanding of the impact of the test
procedure proposals in this NOPR,
specifically DOE’s tentative
determination that the proposed DOE
test procedure amendments, if finalized,
would not increase testing burden on
manufacturers, compared to current
industry practice as indicated by AHRI
210/240–2023.
H. Compliance Date
EPCA prescribes that, for the
equipment at issue, all representations
of energy efficiency and energy use,
including those made on marketing
materials and product labels, must be
made in accordance with an amended
test procedure, beginning 360 days after
publication of such a test procedure
final rule in the Federal Register. (42
U.S.C. 6314(d)(1))
IV. Procedural Issues and Regulatory
Review
A. Review Under Executive Order 12866
The Office of Management and Budget
(‘‘OMB’’) has determined that this test
procedure proposed rulemaking does
not constitute a ‘‘significant regulatory
action’’ under section 3(f) of Executive
Order 12866, Regulatory Planning and
Review, 58 FR 51735 (October 4, 1993).
Accordingly, this action was not subject
to review under the Executive order by
the Office of Information and Regulatory
Affairs (‘‘OIRA’’) in OMB.
PO 00000
Frm 00015
Fmt 4701
Sfmt 4702
70329
B. Review Under the Regulatory
Flexibility Act
The Regulatory Flexibility Act (5
U.S.C. 601 et seq.) requires preparation
of an initial regulatory flexibility
analysis (‘‘IRFA’’) for any rule that by
law must be proposed for public
comment, unless the agency certifies
that the rule, if promulgated, will not
have a significant economic impact on
a substantial number of small entities.
As required by Executive Order 13272,
‘‘Proper Consideration of Small Entities
in Agency Rulemaking,’’ 67 FR 53461
(August 16, 2002), DOE published
procedures and policies on February 19,
2003, to ensure that the potential
impacts of its rules on small entities are
properly considered during the DOE
rulemaking process. 68 FR 7990. DOE
has made its procedures and policies
available on the Office of the General
Counsel’s website: www.energy.gov/gc/
office-general-counsel. DOE reviewed
this proposed rule under the provisions
of the Regulatory Flexibility Act and the
procedures and policies published on
February 19, 2003.
The following sections detail DOE’s
IRFA for this test procedure rulemaking.
1. Description of Reasons Why Action Is
Being Considered
DOE is proposing to amend the
existing DOE test procedures for 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of
less than 65,000 Btu/h. DOE must
update the Federal test procedures to be
consistent with the industry update
unless there is clear and convincing
evidence that the industry update
would not be representative of an
average use cycle or would be unduly
burdensome to conduct. (42 U.S.C.
6314(a)(4)(B))
2. Objective of, and Legal Basis for, Rule
EPCA requires that the test
procedures for commercial package
heating and cooling equipment, which
includes 3-phase ACUACs and ACUHPs
with cooling capacity of less than
65,000 Btu/h and 3-phase VRF with
cooling capacity of less than 65,000 Btu/
h, be generally accepted industry testing
procedures or rating procedures
developed or recognized by either AHRI
or ASHRAE, as referenced in ASHRAE
Standard 90.1. (42 U.S.C. 6314(a)(4)(A))
Further, if such an industry test
procedure is amended, DOE must
amend its test procedure to be
consistent with the amended industry
test procedure, unless DOE determines,
by rule published in the Federal
Register and supported by clear and
E:\FR\FM\09DEP2.SGM
09DEP2
70330
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
convincing evidence, that such
amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2)
and (3) related to representative use and
test burden. (42 U.S.C. 6314(a)(4)(B))
EPCA also requires that, at least once
every 7 years, DOE evaluate test
procedures for each type of covered
equipment, including 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h, to determine whether
amended test procedures would more
accurately or fully comply with the
requirements for the test procedures to
not be unduly burdensome to conduct
and be reasonably designed to produce
test results that reflect energy efficiency,
energy use, and estimated operating
costs during a representative average
use cycle. (42 U.S.C. 614(a)(1)(A))
khammond on DSKJM1Z7X2PROD with PROPOSALS2
3. Description and Estimate of Small
Entities Regulated
For manufacturers of 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of
less than 65,000 Btu/h, the Small
Business Administration (‘‘SBA’’) has
set a size threshold, which defines those
entities classified as ‘‘small businesses’’
for the purposes of the statute. DOE
used the SBA’s small business size
standards to determine whether any
small entities would be subject to the
requirements of the rule. See 13 CFR
part 121. The equipment covered by this
proposed rule is classified under North
American Industry Classification
System (‘‘NAICS’’) code 333415 ,26 ‘‘AirConditioning and Warm Air Heating
Equipment and Commercial and
Industrial Refrigeration Equipment
Manufacturing.’’ In 13 CFR 121.201, the
SBA sets a threshold of 1,250 employees
or fewer for an entity to be considered
as a small business for this category.
DOE reviewed the test procedures
proposed in this NOPR under the
provisions of the Regulatory Flexibility
Act and the procedures and policies
published on February 19, 2003. DOE
used publicly available information to
identify potential small businesses that
manufacture equipment covered this
this rulemaking. DOE identified thirtyseven manufacturers of equipment
covered by this rulemaking. Of the
thirty-seven, thirty manufacturers are
original equipment manufacturers
(‘‘OEM’’). DOE screened out companies
that do not meet the definition of a
26 The size standards are listed by NAICS code
and industry description and are available at:
www.sba.gov/document/support--table-sizestandards (Last accessed on July 16, 2021).
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
‘‘small business’’ or are foreign-owned
and operated. DOE identified eight
small, domestic OEMs for consideration.
DOE used subscription-based business
information tools to determine
headcount and revenue of the small
businesses.
Of those eight small OEMs, four of
them are AHRI members and four are
not AHRI members. Of the four nonAHRI-member small OEMs, two certify
their 3-phase, less than 65,000 Btu/h
equipment models in the AHRI
Directory of Certified Product
Performance (‘‘AHRI Directory’’).27
Therefore, DOE identified two small
OEMs who are not AHRI members and
do not certify their covered equipment
to the AHRI Directory.
4. Description and Estimate of
Compliance Requirements
DOE assumed each small business
would have different potential
regulatory costs depending whether
they are an OEM, they are a member of
AHRI, and/or they currently certify
equipment in the AHRI Directory. DOE
understands all AHRI members and all
manufacturers currently certifying in
the AHRI Directory (including small
businesses) will be testing their models
in accordance with AHRI 210/240–2023,
the industry test procedure DOE is
proposing to reference, and using
AHRI’s certification program, which
DOE presumes will be updated to
include the SEER2 and HSPF2 metrics.
The proposed test procedure
amendments would not add any
additional testing burden to
manufacturers that are or will be using
the AHRI 210/240–2023 test procedure
for their models of 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h.
DOE estimated the range of additional
potential testing costs for the two small
businesses that both are not AHRI
members and do not certify their
equipment that is the subject of this
NOPR to the AHRI Directory. These
small businesses would only incur
additional testing costs if these small
businesses would not have otherwise
been using the AHRI 210/240–2023 test
procedure to test their models of 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h. Of
these two small businesses, the first
manufacturer certifies one basic model
to the DOE Compliance Certification
27 The AHRI Directory of Certified Product
Performance is available at www.ahridirectory.org.
PO 00000
Frm 00016
Fmt 4701
Sfmt 4702
Database and the second manufacturer
certifies two basic models to the DOE
Compliance Certification Database.28
In this NOPR, DOE is proposing to
relocate the current DOE test procedures
to a new appendix B of subpart F of part
431 (‘‘appendix B’’) without change.
DOE is also proposing an amended test
procedure at appendix B1 to subpart F
of part 431 (‘‘appendix B1’’).
Specifically, DOE is proposing in
appendix B1 to incorporate by reference
the updated industry test standard AHRI
210/240–2023 for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h (for which the current
Federal test procedure references AHRI
210–240–2008) and for 3-phase VRF
with cooling capacity of less than
65,000 Btu/h (for which the current
Federal test procedure references AHRI
1230–2010). In addition, DOE is
proposing to adopt the efficiency
metrics, SEER2 and HSPF2, from AHRI
210/240–2023 in the test procedure at
appendix B1. Finally, DOE is proposing
to harmonize representation and
enforcement requirements with those
applicable to single-phase products.
Appendix B does not contain any
changes from the current Federal test
procedure, and therefore would have no
cost to industry and would not require
retesting solely as a result of DOE’s
adoption of this proposed amendment
to the test procedure, if made final. The
proposed appendix B1 adopts the most
recent industry test procedure, AHRI
210/240–2023. DOE estimated the cost
for third-party lab testing according to
the proposed appendix B1 test
procedure to be $8,500 for three-phase,
less than 65,000 Btu/h heating
equipment and $5,500 for three-phase,
less than 65,000 Btu/h air conditioning
equipment. If manufacturers conduct
physical testing to certify a basic model
of the equipment that is the subject of
this NOPR, two units are required to be
tested per basic model. However,
manufacturers are not required to
perform laboratory testing on all basic
models, as manufacturers may elect to
use AEDMs.29 An AEDM is a computer
modeling or mathematical tool that
predicts the performance of non-tested
basic models. These computer modeling
and mathematical tools, when properly
developed, can provide a means to
predict the energy usage or efficiency
characteristics of a basic model of a
given covered product or equipment
28 DOE’s Compliance Certification Database is
available at: www.regulations.doe.gov/ccms (last
accessed June 24, 2021).
29 In accordance with 10 CFR 429.70.
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
and reduce the burden and cost
associated with testing.
The first of the two analyzed small
businesses manufactures one basic
model of three-phase equipment with a
cooling capacity less than 65,000 Btu/
h—the model is an air conditioner. If
this manufacturer used a third-party lab
to test this basic model, DOE estimates
this small business would incur
additional testing costs of
approximately $11,000. The annual
revenue of the first small business is
approximately $82.5 million. DOE
estimates testing costs to be less than
0.01 percent of annual revenue for this
small business.
The second of two analyzed small
businesses manufactures two basic
model of three-phase equipment with a
cooling capacity of less than 65,000 Btu/
h—the models are air conditioners. If
this manufacturer used a third-party lab
to test these basic models, DOE
estimates this small business would
incur additional testing costs of
approximately $22,000. DOE estimates
that annual revenue of this small
business to be approximately $4
million. DOE estimates testing costs to
be less than 0.6 percent of annual
revenue for this small manufacturer.
However, DOE notes that this second
small business also manufactures singlephase central air conditioners and heat
pumps; therefore, this manufacturer
may use an AEDM for certifying their
central air conditioner and heat pump
(‘‘CAC/HP’’) models. Because the
proposed test procedure in appendix B1
aligns with the test procedure for CACs/
HPs at appendix M1 to subpart B of 10
CFR part 430, this manufacturer could
avoid testing costs and, as a lower-cost
alternative, use their CAC/HP AEDM to
certify performance for the equipment
that is the subject of this notice and
further reduce potential costs.30
Issue 9: DOE requests comment on the
number of small businesses DOE
identified. DOE also seeks comment on
the potential cost estimates for each
small business identified, compared to
current industry practice, as indicated
in AHRI 210/240–2023.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
5. Duplication, Overlap, and Conflict
With Other Rules and Regulations
DOE is not aware of any rules or
regulations that duplicate, overlap, or
conflict with the proposed rule being
considered today.
30 As discussed in section 111.G.1 of this NOPR,
DOE is proposing to allow the use of a AEDM that
is validated with single-phase CACs/HPs to be used
for certifying 3-phase ACUACs and ACUHPs with
cooling capacity less than 65,000 Btu/h.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
6. Significant Alternatives to the Rule
DOE proposes to reduce burden on
manufacturers, including small
businesses, by allowing AEDMs in lieu
of physically testing all basic models.
The use of an AEDM is less costly than
physical testing of models of 3-phase
ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of
less than 65,000 Btu/h.
Additionally, DOE considered
alternative test methods and
modifications to the AHRI 210/240–
2023 test procedure for three-phase,
small commercial package heating and
cooling equipment with a cooling
capacity of less than 65,000 Btu/h.
However, DOE has tentatively
determined that there are no better
alternatives than the existing industry
test procedures, in terms of both
meeting the agency’s objectives and
reducing burden on manufacturers.
Therefore, DOE is proposing to amend
the existing DOE test procedure for this
equipment through incorporation by
reference of AHRI 210/240–2023.
In addition, individual manufacturers
may petition for a waiver of the
applicable test procedure. (See 10 CFR
431.401) Also, Section 504 of the
Department of Energy Organization Act,
42 U.S.C. 7194, provides authority for
the Secretary to adjust a rule issued
under EPCA in order to prevent ‘‘special
hardship, inequity, or unfair
distribution of burdens’’ that may be
imposed on that manufacturer as a
result of such rule. Manufacturers
should refer to 10 CFR part 1003 for
additional details.
70331
for the certification and recordkeeping
is subject to review and approval by
OMB under the Paperwork Reduction
Act (‘‘PRA’’). This requirement has been
approved by OMB under OMB control
number 1910–1400. Public reporting
burden for the certification is estimated
to average 35 hours per response,
including the time for reviewing
instructions, searching existing data
sources, gathering and maintaining the
data needed, and completing and
reviewing the collection of information.
Notwithstanding any other provision
of the law, no person is required to
respond to, nor shall any person be
subject to a penalty for failure to comply
with, a collection of information subject
to the requirements of the PRA, unless
that collection of information displays a
currently valid OMB Control Number.
C. Review Under the Paperwork
Reduction Act of 1995
D. Review Under the National
Environmental Policy Act of 1969
DOE is analyzing this proposed
regulation in accordance with the
National Environmental Policy Act of
1969 (‘‘NEPA’’) and DOE’s NEPA
implementing regulations (10 CFR part
1021). DOE’s regulations include a
categorical exclusion for rulemakings
interpreting or amending an existing
rule or regulation that does not change
the environmental effect of the rule or
regulation being amended. 10 CFR part
1021, subpart D, appendix A5. DOE
anticipates that this rulemaking
qualifies for categorical exclusion A5
because it is an interpretive rulemaking
that does not change the environmental
effect of the rule and otherwise meets
the requirements for application of a
categorical exclusion. See 10 CFR
1021.410. DOE will complete its NEPA
review before issuing the final rule.
Manufacturers of 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h must certify to DOE that
their products comply with any
applicable energy conservation
standards. To certify compliance,
manufacturers must first obtain test data
for their products according to the DOE
test procedures, including any
amendments adopted for those test
procedures. DOE has established
regulations for the certification and
recordkeeping requirements for all
covered consumer products and
commercial equipment, including for 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h. (See
generally 10 CFR part 429.) The
collection-of-information requirement
E. Review Under Executive Order 13132
Executive Order 13132, ‘‘Federalism,’’
64 FR 43255 (August 10, 1999) imposes
certain requirements on agencies
formulating and implementing policies
or regulations that preempt State law or
that have federalism implications. The
Executive order requires agencies to
examine the constitutional and statutory
authority supporting any action that
would limit the policymaking discretion
of the States and to carefully assess the
necessity for such actions. The
Executive order also requires agencies to
have an accountable process to ensure
meaningful and timely input by State
and local officials in the development of
regulatory policies that have federalism
implications. On March 14, 2000, DOE
published a statement of policy
describing the intergovernmental
consultation process it will follow in the
development of such regulations. 65 FR
PO 00000
Frm 00017
Fmt 4701
Sfmt 4702
E:\FR\FM\09DEP2.SGM
09DEP2
70332
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
13735. DOE has examined this proposed
rule and has determined that it would
not have a substantial direct effect on
the States, on the relationship between
the national government and the States,
or on the distribution of power and
responsibilities among the various
levels of government. EPCA governs and
prescribes Federal preemption of State
regulations as to energy conservation for
the products that are the subject of this
proposed rule. States can petition DOE
for exemption from such preemption to
the extent, and based on criteria, set
forth in EPCA (42 U.S.C. 6297(d)). No
further action is required by Executive
Order 13132.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
F. Review Under Executive Order 12988
Regarding the review of existing
regulations and the promulgation of
new regulations, section 3(a) of
Executive Order 12988, ‘‘Civil Justice
Reform,’’ 61 FR 4729 (February 7, 1996),
imposes on Federal agencies the general
duty to adhere to the following
requirements: (1) Eliminate drafting
errors and ambiguity, (2) write
regulations to minimize litigation, (3)
provide a clear legal standard for
affected conduct rather than a general
standard, and (4) promote simplification
and burden reduction. Section 3(b) of
Executive Order 12988 specifically
requires that executive agencies make
every reasonable effort to ensure that the
regulation (1) clearly specifies the
preemptive effect, if any, (2) clearly
specifies any effect on existing Federal
law or regulation, (3) provides a clear
legal standard for affected conduct
while promoting simplification and
burden reduction, (4) specifies the
retroactive effect, if any, (5) adequately
defines key terms, and (6) addresses
other important issues affecting clarity
and general draftsmanship under any
guidelines issued by the Attorney
General. Section 3(c) of Executive Order
12988 requires Executive agencies to
review regulations in light of applicable
standards in sections 3(a) and 3(b) to
determine whether they are met, or it is
unreasonable to meet one or more of
them. DOE has completed the required
review and determined that, to the
extent permitted by law, the proposed
rule meets the relevant standards of
Executive Order 12988.
G. Review Under the Unfunded
Mandates Reform Act of 1995
Title II of the Unfunded Mandates
Reform Act of 1995 (‘‘UMRA’’) requires
each Federal agency to assess the effects
of Federal regulatory actions on State,
local, and Tribal governments, and the
private sector. Public Law 104–4, sec.
201 (codified at 2 U.S.C. 1531). For a
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
proposed regulatory action likely to
result in a rule that may cause the
expenditure by State, local, and Tribal
governments, in the aggregate, or by the
private sector of $100 million or more
in any one year (adjusted annually for
inflation), section 202 of UMRA requires
a Federal agency to publish a written
statement that estimates the resulting
costs, benefits, and other effects on the
national economy. (2 U.S.C. 1532(a), (b))
The UMRA also requires a Federal
agency to develop an effective process
to permit timely input by elected
officers of State, local, and Tribal
governments on a proposed ‘‘significant
intergovernmental mandate,’’ and
requires an agency plan for giving notice
and opportunity for timely input to
potentially affected small governments
before establishing any requirements
that might significantly or uniquely
affect small governments. On March 18,
1997, DOE published a statement of
policy on its process for
intergovernmental consultation under
UMRA. 62 FR 12820; also available at
www.energy.gov/gc/office-generalcounsel. DOE examined this proposed
rule according to UMRA and its
statement of policy and determined that
the rule contains neither an
intergovernmental mandate, nor a
mandate that may result in the
expenditure of $100 million or more in
any year, so these requirements do not
apply.
H. Review Under the Treasury and
General Government Appropriations
Act, 1999
Section 654 of the Treasury and
General Government Appropriations
Act, 1999 (Pub. L. 105–277) requires
Federal agencies to issue a Family
Policymaking Assessment for any rule
that may affect family well-being. This
proposed rule would not have any
impact on the autonomy or integrity of
the family as an institution.
Accordingly, DOE has concluded that it
is not necessary to prepare a Family
Policymaking Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive
Order 12630, ‘‘Governmental Actions
and Interference with Constitutionally
Protected Property Rights’’ 53 FR 8859
(March 18, 1988), that this proposed
regulation would not result in any
takings that might require compensation
under the Fifth Amendment to the U.S.
Constitution.
J. Review Under Treasury and General
Government Appropriations Act, 2001
Section 515 of the Treasury and
General Government Appropriations
PO 00000
Frm 00018
Fmt 4701
Sfmt 4702
Act, 2001 (44 U.S.C. 3516 note) provides
for agencies to review most
disseminations of information to the
public under guidelines established by
each agency pursuant to general
guidelines issued by OMB. OMB’s
guidelines were published at 67 FR
8452 (February 22, 2002), and DOE’s
guidelines were published at 67 FR
62446 (October 7, 2002). Pursuant to
OMB Memorandum M–19–15,
Improving Implementation of the
Information Quality Act (April 24,
2019), DOE published updated
guidelines which are available at
www.energy.gov/sites/prod/files/2019/
12/f70/DOE%20Final%20
Updated%20IQA%20
Guidelines%20Dec%202019.pdf. DOE
has reviewed this proposed rule under
the OMB and DOE guidelines and has
concluded that it is consistent with
applicable policies in those guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ‘‘Actions
Concerning Regulations That
Significantly Affect Energy Supply,
Distribution, or Use,’’ 66 FR 28355 (May
22, 2001), requires Federal agencies to
prepare and submit to OMB, a
Statement of Energy Effects for any
proposed significant energy action. A
‘‘significant energy action’’ is defined as
any action by an agency that
promulgated or is expected to lead to
promulgation of a final rule, and that (1)
is a significant regulatory action under
Executive Order 12866, or any successor
order; and (2) is likely to have a
significant adverse effect on the supply,
distribution, or use of energy; or (3) is
designated by the Administrator of
OIRA as a significant energy action. For
any proposed significant energy action,
the agency must give a detailed
statement of any adverse effects on
energy supply, distribution, or use
should the proposal be implemented,
and of reasonable alternatives to the
action and their expected benefits on
energy supply, distribution, and use.
The proposed regulatory action to
amend the test procedures for
measuring the energy efficiency of 3phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h is not
a significant regulatory action under
Executive Order 12866. Moreover, it
would not have a significant adverse
effect on the supply, distribution, or use
of energy, nor has it been designated as
a significant energy action by the
Administrator of OIRA. Therefore, it is
not a significant energy action, and,
accordingly, DOE has not prepared a
Statement of Energy Effects.
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
L. Review Under Section 32 of the
Federal Energy Administration Act of
1974
Under section 301 of the Department
of Energy Organization Act (Pub. L. 95–
91; 42 U.S.C. 7101), DOE must comply
with section 32 of the Federal Energy
Administration Act of 1974, as amended
by the Federal Energy Administration
Authorization Act of 1977. (15 U.S.C.
788; ‘‘FEAA’’) Section 32 essentially
provides in relevant part that, where a
proposed rule authorizes or requires use
of commercial standards, the notice of
proposed rulemaking must inform the
public of the use and background of
such standards. In addition, section
32(c) requires DOE to consult with the
Attorney General and the Chairman of
the Federal Trade Commission (‘‘FTC’’)
concerning the impact of the
commercial or industry standards on
competition.
The proposed modifications to the
test procedures for 3-phase ACUACs
and ACUHPs with cooling capacity of
less than 65,000 Btu/h and for 3-phase
VRF with cooling capacity of less than
65,000 Btu/h would reference testing
methods contained in certain sections of
the following commercial standards:
AHRI 210/240–2023 and ANSI/
ASHRAE 37–2009. DOE has evaluated
these standards and is unable to
conclude whether they fully comply
with the requirements of section 32(b) of
the FEAA (i.e., whether it was
developed in a manner that fully
provides for public participation,
comment, and review). DOE will
consult with both the Attorney General
and the Chairman of the FTC
concerning the impact of these test
procedures on competition, prior to
prescribing a final rule.
M. Description of Materials
Incorporated by Reference
khammond on DSKJM1Z7X2PROD with PROPOSALS2
In this NOPR, DOE proposes to
incorporate by reference the following
test standard:
(1) The test standard published by AHRI,
titled ‘‘2023 Standard for Performance Rating
of Unitary Air-Conditioning & Air-Source
Heat Pump Equipment,’’ AHRI Standard 210/
240–2023. AHRI Standard 210/240–2023 is
an industry-accepted test procedure for
measuring the performance of air
conditioning and heating equipment. AHRI
Standard 210/240–2023 is available on
AHRI’s website www.ahrinet.org/searchstandards.aspx.
In this NOPR, DOE proposes to amend
the incorporation by reference
previously approved for the following
test standard:
(2) The test standard published by
ASHRAE, titled ‘‘Methods of Testing for
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
Rating Electrically Driven Unitary AirConditioning and Heat Pump Equipment,’’
ANSI/ASHRAE Standard 37–2009. ANSI/
ASHRAE Standard 37–2009 is an industryaccepted test procedure that provides a
method of test for many categories of air
conditioning and heating equipment. ANSI/
ASHRAE Standard 37–2009 is available on
ANSI’s website at https://webstore.ansi.org/
RecordDetail.aspx?sku=ANSI%2FASHRAE+
Standard+37-2009.
(3) In this NOPR, DOE proposes to
maintain and update the incorporation by
reference previously approved for the
following test standards: The test standard
published by AHRI, titled 210/240–2008,
‘‘Performance Rating of Unitary AirConditioning & Air-Source Heat Pump
Equipment,’’ approved by ANSI on October
27, 2011 and updated by addendum 1 in June
2011 and addendum 2 in March 2012. ANSI/
AHRI Standard 210/240–2008 is an industryaccepted test procedure for measuring the
performance of air conditioning and heating
equipment. ANSI/AHRI Standard 210/240–
2008 is available on AHRI’s website at
www.ahrinet.org/search-standards.aspx.
(4) The test standards published by AHRI
titled, ANSI/AHRI Standard 1230–2010,
‘‘2010 Standard for Performance Rating of
Variable Refrigerant Flow (VRF) Multi-split
Air-Conditioning and Heat Pump
Equipment,’’ approved August 2, 2010 and
updated by addendum 1 in March 2011.
ANSI/AHRI Standard 1230–2010 is an
industry-accepted test procedure for
measuring the performance of air
conditioning and heating equipment. ANSI/
AHRI Standard 1230–2010 is available on
AHRI’s website www.ahrinet.org/searchstandards.aspx.
V. Public Participation
A. Participation in the Webinar
The time and date of the webinar are
listed in the DATES and ADDRESSES
sections at the beginning of this
document. If no participants register for
the webinar then it will be cancelled.
Webinar registration information,
participant instructions, and
information about the capabilities
available to webinar participants will be
published on DOE’s website: https://
www1.eere.energy.gov/buildings/
appliance_standards/standards.aspx?
productid=75&action=viewlive
Participants are responsible for ensuring
their systems are compatible with the
webinar software.
B. Procedure for Submitting Prepared
General Statements for Distribution
Any person who has an interest in the
topics addressed in this NOPR, or who
is representative of a group or class of
persons that has an interest in these
issues, may request an opportunity to
make an oral presentation at the
webinar. Such persons may submit to
ApplianceStandardsQuestions@
ee.doe.gov. Persons who wish to speak
PO 00000
Frm 00019
Fmt 4701
Sfmt 4702
70333
should include with their request a
computer file in WordPerfect, Microsoft
Word, PDF, or text (ASCII) file format
that briefly describes the nature of their
interest in this rulemaking and the
topics they wish to discuss. Such
persons should also provide a daytime
telephone number where they can be
reached.
Persons requesting to speak should
briefly describe the nature of their
interest in this rulemaking and provide
a telephone number for contact. DOE
requests persons selected to make an
oral presentation to submit an advance
copy of their statements at least two
weeks before the webinar. At its
discretion, DOE may permit persons
who cannot supply an advance copy of
their statement to participate, if those
persons have made advance alternative
arrangements with the Building
Technologies Office. As necessary,
requests to give an oral presentation
should ask for such alternative
arrangements.
C. Conduct of the Webinar
DOE will designate a DOE official to
preside at the webinar and may also use
a professional facilitator to aid
discussion. The meeting will not be a
judicial or evidentiary-type public
hearing, but DOE will conduct it in
accordance with section 336 of EPCA
(42 U.S.C. 6306). A court reporter will
be present to record the proceedings and
prepare a transcript. DOE reserves the
right to schedule the order of
presentations and to establish the
procedures governing the conduct of the
webinar/public meeting. There shall not
be discussion of proprietary
information, costs or prices, market
share, or other commercial matters
regulated by U.S. anti-trust laws. After
the webinar and until the end of the
comment period, interested parties may
submit further comments on the
proceedings and any aspect of the
rulemaking.
The webinar will be conducted in an
informal, conference style. DOE will
allow time for prepared general
statements by participants and
encourage all interested parties to share
their views on issues affecting this
rulemaking. Each participant will be
allowed to make a general statement
(within time limits determined by DOE),
before the discussion of specific topics.
DOE will permit, as time permits, other
participants to comment briefly on any
general statements.
At the end of all prepared statements
on a topic, DOE will permit participants
to clarify their statements briefly.
Participants should be prepared to
answer questions by DOE and by other
E:\FR\FM\09DEP2.SGM
09DEP2
70334
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
participants concerning these issues.
DOE representatives may also ask
questions of participants concerning
other matters relevant to this
rulemaking. The official conducting the
webinar/public meeting will accept
additional comments or questions from
those attending, as time permits. The
presiding official will announce any
further procedural rules or modification
of the above procedures that may be
needed for the proper conduct of the
webinar/public meeting.
A transcript of the webinar will be
included in the docket, which can be
viewed as described in the Docket
section at the beginning of this NOPR.
In addition, any person may buy a copy
of the transcript from the transcribing
reporter.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
D. Submission of Comments
DOE will accept comments, data, and
information regarding this proposed
rule no later than the date provided in
the DATES section at the beginning of
this proposed rule. Interested parties
may submit comments using any of the
methods described in the ADDRESSES
section at the beginning of this NOPR.31
Submitting comments via
www.regulations.gov. The
www.regulations.gov web page will
require you to provide your name and
contact information. Your contact
information will be viewable to DOE
Building Technologies staff only. Your
contact information will not be publicly
viewable except for your first and last
names, organization name (if any), and
submitter representative name (if any).
If your comment is not processed
properly because of technical
difficulties, DOE will use this
information to contact you. If DOE
cannot read your comment due to
technical difficulties and cannot contact
31 DOE has historically provided a 75-day
comment period for test procedure NOPRs pursuant
to the North American Free Trade Agreement, U.S.Canada-Mexico (‘‘NAFTA’’), Dec. 17, 1992, 32
I.L.M. 289 (1993); the North American Free Trade
Agreement Implementation Act, Public Law 103–
182, 107 Stat. 2057 (1993) (codified as amended at
10 U.S.C.A. 2576) (1993) (‘‘NAFTA Implementation
Act’’); and Executive Order 12889, ‘‘Implementation
of the North American Free Trade Agreement,’’ 58
FR 69681 (Dec. 30, 1993). However, on July 1, 2020,
the Agreement between the United States of
America, the United Mexican States, and the United
Canadian States (‘‘USMCA’’), Nov. 30, 2018, 134
Stat. 11 (i.e., the successor to NAFTA), went into
effect, and Congress’s action in replacing NAFTA
through the USMCA Implementation Act, 19 U.S.C.
4501 et seq. (2020), implies the repeal of E.O. 12889
and its 75-day comment period requirement for
technical regulations. Thus, the controlling laws are
EPCA and the USMCA Implementation Act.
Consistent with EPCA’s public comment period
requirements for consumer products, the USMCA
only requires a minimum comment period of 60
days. Consequently, DOE now provides a 60-day
public comment period for test procedure NOPRs.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
you for clarification, DOE may not be
able to consider your comment.
However, your contact information
will be publicly viewable if you include
it in the comment or in any documents
attached to your comment. Any
information that you do not want to be
publicly viewable should not be
included in your comment, nor in any
document attached to your comment.
Persons viewing comments will see only
first and last names, organization
names, correspondence containing
comments, and any documents
submitted with the comments.
Do not submit to www.regulations.gov
information for which disclosure is
restricted by statute, such as trade
secrets and commercial or financial
information (hereinafter referred to as
Confidential Business Information
(‘‘CBI’’)). Comments submitted through
www.regulations.gov cannot be claimed
as CBI. Comments received through the
website will waive any CBI claims for
the information submitted. For
information on submitting CBI, see the
Confidential Business Information
section.
DOE processes submissions made
through www.regulations.gov before
posting. Normally, comments will be
posted within a few days of being
submitted. However, if large volumes of
comments are being processed
simultaneously, your comment may not
be viewable for up to several weeks.
Please keep the comment tracking
number that www.regulations.gov
provides after you have successfully
uploaded your comment.
Submitting comments via email.
Comments and documents submitted
via email also will be posted to
www.regulations.gov. If you do not want
your personal contact information to be
publicly viewable, do not include it in
your comment or any accompanying
documents. Instead, provide your
contact information on a cover letter.
Include your first and last names, email
address, telephone number, and
optional mailing address. The cover
letter will not be publicly viewable as
long as it does not include any
comments.
Include contact information each time
you submit comments, data, documents,
and other information to DOE. If you
submit via postal mail or hand delivery/
courier, please provide all items on a
CD, if feasible. It is not necessary to
submit printed copies. No facsimiles
(faxes) will be accepted.
Comments, data, and other
information submitted to DOE
electronically should be provided in
PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file
PO 00000
Frm 00020
Fmt 4701
Sfmt 4702
format. Provide documents that are not
secured, written in English and free of
any defects or viruses. Documents
should not contain special characters or
any form of encryption and, if possible,
they should carry the electronic
signature of the author.
Campaign form letters. Please submit
campaign form letters by the originating
organization in batches of between 50 to
500 form letters per PDF or as one form
letter with a list of supporters’ names
compiled into one or more PDFs. This
reduces comment processing and
posting time.
Confidential Business Information.
According to 10 CFR 1004.11, any
person submitting information that he
or she believes to be confidential and
exempt by law from public disclosure
should submit via email two wellmarked copies: One copy of the
document marked confidential
including all the information believed to
be confidential, and one copy of the
document marked non-confidential with
the information believed to be
confidential deleted. DOE will make its
own determination about the
confidential status of the information
and treat it according to its
determination.
It is DOE’s policy that all comments
may be included in the public docket,
without change and as received,
including any personal information
provided in the comments (except
information deemed to be exempt from
public disclosure).
E. Issues on Which DOE Seeks Comment
Although DOE welcomes comments
on any aspect of this proposal, DOE is
particularly interested in receiving
comments and views of interested
parties concerning the following issues:
Issue 1: DOE seeks comment on its
proposal to maintain reference to ANSI/
AHRI 210/240–2008 with Addenda 1
and 2 as the Federal test procedure for
3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/
h, until such time as compliance would
be required with the amended test
procedure referencing AHRI 210/240–
2023.
Issue 2: DOE seeks comment on its
proposal to incorporate by reference
AHRI 210/240–2023 in the DOE test
procedure for 3-phase ACUACs and
ACUHPs with cooling capacity of less
than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than
65,000 Btu/h. DOE also seeks comment
on its proposal to require compliance
with this test procedure on the
compliance date of any amended energy
conservation standards that DOE may
E:\FR\FM\09DEP2.SGM
09DEP2
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
decide to adopt later as part of a future
rulemaking.
Issue 3: DOE seeks comment on its
proposal to align the representation
requirements for the three-phase
equipment addressed by this NOPR
with the requirements specified for
single-phase products at 10 CFR 429.16
and 10 CFR 429.70(e),—but with the
exception of testing requirements and
certain AEDM validation requirements
for single-package and single-split
system models. Specifically, DOE
requests comment on its proposal to
permit for three-phase, less than 65,000
Btu/h single-package and single-split
system basic models with otherwise
identical single-phase counterparts the
use of ratings based on an AEDM
validated using the test results from
otherwise identical central air
conditioners and heat pumps, rather
than requiring validation using the test
results of three-phase models. DOE also
requests comment on its proposed
specification of the term ‘‘otherwise
identical’’. Finally, DOE requests
comment on whether the proposed
AEDM requirements should include a
provision to validate the correlation
between single-phase and three-phase
performance as determined using an
AEDM.
Issue 4: DOE seeks comment on
whether there are three-phase, less than
65,000 Btu/h models of outdoor units
with no match or multi-split, multicircuit, and multi-head mini-split
systems on the market, and, if so,
whether AEDMs should be allowed for
their ratings and what requirements for
AEDM validation should be specified.
Issue 5: DOE seeks comment on
whether there are models of three-phase
single-split-system air conditioners with
single-stage or two-stage compressors
that are not distributed in commerce as
a coil-only combination (i.e., distributed
in commerce only as blower-coil
combination(s)).
Issue 6: DOE requests comment on its
proposal to align the definition of basic
model for three-phase equipment at 10
CFR 431.96 with that for single-phase
products at 10 CFR 430.2.
Issue 7: DOE seeks comment on its
proposal not to amend certification
reporting requirements for the threephase equipment subject to this notice
to align with single-phase products at
this time. DOE also requests details on
whether any particular certification
reporting requirements in 10 CFR
429.16(e) are particularly problematic
for manufacturers (for both single-phase
products and three-phase equipment)
and why.
Issue 8: DOE requests comment on its
understanding of the impact of the test
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
70335
procedure proposals in this NOPR,
specifically DOE’s tentative
determination that the proposed DOE
test procedure amendments, if finalized,
would not increase testing burden on
manufacturers, compared to current
industry practice as indicated by AHRI
210/240–2023.
Issue 9: DOE requests comment on the
number of small businesses DOE
identified. DOE also seeks comment on
the potential cost estimates for each
small business identified, compared to
current industry practice, as indicated
in AHRI 210/240–2023.
Signed in Washington, DC, on November 9,
2021 .
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
VI. Approval of the Office of the
Secretary
■
The Secretary of Energy has approved
publication of this notice of proposed
rulemaking and request for comment.
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
List of Subjects
Administrative practice and
procedure, Confidential business
information, Energy conservation,
Household appliances, Imports,
Incorporation by reference,
Intergovernmental relations, Reporting
and recordkeeping requirements, Small
businesses.
10 CFR Part 431
Administrative practice and
procedure, Confidential business
information, Energy conservation test
procedures, Incorporation by reference,
and Reporting and recordkeeping
requirements.
Signing Authority
This document of the Department of
Energy was signed on November 5,
2021, by Kelly Speakes-Backman,
Principal Deputy Assistant Secretary
and Acting Assistant Secretary for
Energy Efficiency and Renewable
Energy, pursuant to delegated authority
from the Secretary of Energy. That
document with the original signature
and date is maintained by DOE. For
administrative purposes only, and in
compliance with requirements of the
Office of the Federal Register, the
undersigned DOE Federal Register
Liaison Officer has been authorized to
sign and submit the document in
electronic format for publication, as an
official document of the Department of
Energy. This administrative process in
no way alters the legal effect of this
document upon publication in the
Federal Register.
Frm 00021
Fmt 4701
PART 429—CERTIFICATION,
COMPLIANCE, AND ENFORCEMENT
FOR CONSUMER PRODUCTS AND
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
1. The authority citation for part 429
continues to read as follows:
2. Amend § 429.4 by adding paragraph
(c)(3) to read as follows.
■
§ 429.4 Materials incorporated by
reference.
10 CFR Part 429
PO 00000
For the reasons stated in the
preamble, DOE is proposing to amend
parts 429 and 431 of Chapter II of Title
10, Code of Federal Regulations as set
forth below:
Sfmt 4702
*
*
*
*
*
(c) * * *
(3) AHRI Standard 210/240–2023,
(‘‘AHRI 210/240–2023’’), 2023 Standard
for Performance Rating of Unitary AirConditioning & Air-Source Heat Pump
Equipment, approved 2020, IBR
approved for §§ 429.64 and 429.134.
*
*
*
*
*
■ 3. Amend § 429.12 by revising
paragraph (b)(8) to read as follows:
§ 429.12 General requirements applicable
to certification reports.
*
*
*
*
*
(b) * * *
(8) The test sample size as follows:
(i) The number of units tested for the
basic model, or
(ii) In the case of single-split system
or single-package central air
conditioners and central air
conditioning heat pumps; air-cooled,
three-phase, small commercial package
air conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h; air-cooled, three-phase,
variable refrigerant flow multi-split air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h; or multi-split, multi-circuit, or multihead mini-split systems other than the
‘‘tested combination’’, the number of
units tested for each individual
combination or individual model, or
(iii) If an AEDM was used in lieu of
testing, enter ‘‘0’’ (and in the case of
central air conditioners and central air
conditioning heat pumps, this must be
indicated separately for each metric);
*
*
*
*
*
■ 4. Amend § 429.43 by:
■ a. Revising the section heading;
E:\FR\FM\09DEP2.SGM
09DEP2
70336
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
b. Removing paragraphs (b)(2)(iii),
(iv,) (ix) and (x);
■ c. Redesignating paragraphs (b)(2)(v)
through (viii), and (xi) through (xv) as
paragraphs (b)(2)(iii) through (vi), and
(vii) through (xi), respectively;
■ d. Removing paragraphs (b)(4)(iii)
through (vi); and
■ e. Redesignating paragraphs (b)(4)(vii)
through (xiv) as paragraphs (b)(4)(iii)
through (x).
The revisions read as follows:
■
§ 429.43 Commercial heating, ventilating,
air conditioning (HVAC) equipment
(excluding air-cooled, three-phase, small
commercial package air conditioning and
heating equipment with a cooling capacity
of less than 65,000 British thermal units per
hour and air-cooled, three-phase, variable
refrigerant flow multi-split air conditioners
and heat pumps with less than 65,000
British thermal units per hour cooling
capacity).
*
■
*
*
*
*
5. Add § 429.64 to read as follows:
Category
§ 429.64 Air-cooled, three-phase, small
commercial package air conditioning and
heating equipment with a cooling capacity
of less than 65,000 British thermal units per
hour and air-cooled, three-phase, variable
refrigerant flow multi-split air conditioners
and heat pumps with a cooling capacity of
less than 65,000 British thermal units per
hour.
(a) Applicability. (1) For air-cooled,
three-phase, small commercial package
air conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h and air-cooled, threephase, variable refrigerant flow multisplit air conditioners and heat pumps
with a cooling capacity of less than
65,000 Btu/h subject to standards in
terms of seasonal energy efficiency ratio
(SEER) and heating seasonal
performance factor (HSPF),
representations with respect to the
energy use or efficiency, including
compliance certifications, are subject to
the requirements in § 429.43 of this title
as it appeared in the 10 CFR parts 200–
499 edition revised as of January 1,
2021.
(2) For air-cooled, three-phase, small
commercial package air conditioning
Equipment subcategory
Single-Package unit ........................
Outdoor Unit and Indoor Unit (Distributed in Commerce by OUM
(Outdoor Unit Manufacturer)).
Single-Package AC (including
Space-Constrained).
Single-Package HP (including
Space-Constrained).
Single-Split-System AC with Single-Stage or Two-Stage Compressor (including Space-Constrained and Small-Duct, High
Velocity Systems (SDHV)).
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Single-Split-System AC with Other
Than Single-Stage or TwoStage Compressor (including
Space-Constrained and SDHV).
Single-Split-System HP (including
Space-Constrained and SDHV).
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
non-SDHV (including SpaceConstrained).
Indoor Unit Only Distributed in
Commerce by ICM (Independent
Coil Manufacturer).
VerDate Sep<11>2014
19:25 Dec 08, 2021
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
SDHV.
Single-Split-System Air Conditioner (including Space-Constrained and SDHV).
Jkt 256001
PO 00000
Frm 00022
Fmt 4701
and heating equipment with a cooling
capacity of less than 65,000
Btu/h and air-cooled, three-phase,
variable refrigerant flow multi-split air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h subject to standards in terms of
seasonal energy efficiency ratio 2
(‘‘SEER2’’) and heating seasonal
performance factor 2 (‘‘HSPF2’’) metrics,
representations with respect to the
energy use or efficiency, including
compliance certifications, are subject to
the requirements in this section. If
manufacturers choose to certify
compliance with any standards in terms
of SEER2 and HSPF2 prior to the
applicable compliance date for those
standards, the requirements of this
section must be followed.
(b) Determination of Represented
Value—(1) Required represented values.
Determine the represented values
(including SEER2, HSPF2, cooling
capacity, and heating capacity, as
applicable) for the individual models/
combinations (or ‘‘tested
combinations’’) specified in the table to
this paragraph (b)(1).
Required represented values
Every individual model distributed in commerce.
Every individual combination distributed in commerce must be rated
as a coil-only combination. For each model of outdoor unit, this
must include at least one coil-only value that is representative of
the least efficient combination distributed in commerce with that
particular model of outdoor unit. Additional blower-coil representations are allowed for any applicable individual combinations, if distributed in commerce.
Every individual combination distributed in commerce, including all
coil-only and blower coil combinations.
Every individual combination distributed in commerce.
For each model of outdoor unit, at a minimum, a non-ducted ‘‘tested
combination.’’ For any model of outdoor unit also sold with models
of ducted indoor units, a ducted ‘‘tested combination.’’ When determining represented values on or after the compliance date of any
amended energy conservation standards, the ducted ‘‘tested combination’’ must comprise the highest static variety of ducted indoor
unit distributed in commerce (i.e., conventional, mid-static, or lowstatic). Additional representations are allowed, as described in
paragraph (d)(3) of this section.
For each model of outdoor unit, an SDHV ‘‘tested combination.’’ Additional representations are allowed, as described in paragraph
(d)(3) of this section.
Every individual combination distributed in commerce.
Sfmt 4702
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
Equipment subcategory
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Outdoor Unit with no Match ........................................................................
(2) Refrigerants. (i) If a model of
outdoor unit (used in a single-split,
multi-split, multi-circuit, multi-head
mini-split, and/or outdoor unit with no
match system) is distributed in
commerce and approved for use with
multiple refrigerants, a manufacturer
must determine all represented values
for that model using each refrigerant
that can be used in an individual
combination of the basic model
(including outdoor units with no match
or ‘‘tested combinations’’). This
requirement may apply across the listed
categories in the table in paragraph
(b)(1) of this section. A refrigerant is
considered approved for use if it is
listed on the nameplate of the outdoor
unit. If any of the refrigerants approved
for use is HCFC–22 or has a 95 °F
midpoint saturation absolute pressure
that is ±18 percent of the 95 °F
saturation absolute pressure for HCFC–
22, or if there are no refrigerants
designated as approved for use, a
manufacturer must determine
represented values (including SEER2,
HSPF2, cooling capacity, and heating
capacity, as applicable) for, at a
minimum, an outdoor unit with no
match. If a model of outdoor unit is not
charged with a specified refrigerant
from the point of manufacture or if the
unit is shipped requiring the addition of
more than two pounds of refrigerant to
meet the charge required for testing per
section 5.1.8 of AHRI 210/240–2023
(incorporated by reference, see § 429.4)
(unless either (a) the factory charge is
equal to or greater than 70% of the
outdoor unit internal volume multiplied
by the liquid density of refrigerant at
95 °F or (b) an A2L refrigerant is
approved for use and listed in the
certification report), a manufacturer
must determine represented values
(including SEER2, HSPF2, cooling
capacity, and heating capacity, as
applicable) for, at a minimum, an
outdoor unit with no match.
(ii) If a model is approved for use with
multiple refrigerants, a manufacturer
may make multiple separate
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
For a model of indoor unit within each basic model, a SDHV ‘‘tested
combination.’’ Additional representations are allowed, as described
in section (d)(3)(ii) of this section.
Every model of outdoor unit distributed in commerce (tested with a
model of coil-only indoor unit as specified in paragraph (c)(2) of
this section).
representations for the performance of
that model (all within the same
individual combination or outdoor unit
with no match) using the multiple
approved refrigerants. In the alternative,
manufacturers may certify the model
(all within the same individual
combination or outdoor unit with no
match) with a single representation,
provided that the represented value is
no more efficient than its performance
using the least-efficient refrigerant. A
single representation made for multiple
refrigerants may not include equipment
in multiple categories or equipment
subcategories listed in the table in
paragraph (b)(1) of this section.
(3) Limitations for represented values
of individual combinations. The
following paragraph explains the
limitations for represented values of
individual combinations (or ‘‘tested
combinations’’).
(i) Multiple product classes. Models
of outdoor units that are rated and
distributed in individual combinations
that span multiple product classes must
be tested, rated, and certified pursuant
to paragraph (b) of this section as
compliant with the applicable standard
for each product class.
(ii) Reserved.
(4) Requirements. All represented
values under paragraph (b) of this
section must be based on testing in
accordance with the requirements in
paragraph (c) of this section or the
application of an AEDM or other
methodology as allowed in paragraph
(d) of this section.
(c) Units tested—(1) General. The
general requirements of § 429.11 apply
to air-cooled, three-phase, small
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 Btu/h, and
air-cooled, three-phase, variable
refrigerant flow multi-split air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h; and
(2) Sampling plans and represented
values. For individual models (for
single-package systems) or individual
PO 00000
Frm 00023
Fmt 4701
Sfmt 4702
combinations (for split-systems,
including ‘‘tested combinations’’ for
multi-split, multi-circuit, and multihead mini-split systems) with
represented values determined through
testing, each individual model/
combination (or ‘‘tested combination’’)
must have a sample of sufficient size
tested in accordance with the applicable
provisions of this subpart. For heat
pumps (other than heating-only heat
pumps), all units of the sample
population must be tested in both the
cooling and heating modes and the
results used for determining all
representations. The represented values
for any individual model/combination
must be assigned such that:
(i) Off-Mode. Any represented value
of power consumption or other measure
of energy consumption for which
consumers would favor lower values
must be greater than or equal to the
higher of:
(A) The mean of the sample, where:
and, x is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(B) The upper 90 percent confidence
limit (UCL) of the true mean divided by
1.05, where:
And x is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.90 is the t
statistic for a 90 percent one-tailed
confidence interval with n¥1 degrees of
freedom (from appendix A of this
subpart). Round represented values of
off-mode power consumption to the
nearest watt.
(ii) SEER2 and HSPF2. Any
represented value of the energy
efficiency or other measure of energy
consumption for which consumers
would favor higher values shall be less
than or equal to the lower of:
E:\FR\FM\09DEP2.SGM
09DEP2
EP09DE21.002
Single-Split-System Heat Pump
(including Space-Constrained
and SDHV).
Multi-Split, Multi-Circuit, or MultiHead Mini-Split Split System—
SDHV.
Required represented values
EP09DE21.001
Category
70337
And x¯ is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.90 is the t
statistic for a 90 percent one-tailed
confidence interval with n¥1 degrees of
freedom (from appendix A of this
subpart). Round represented values of
SEER2 and HSPF2 to the nearest 0.05.
(iii) Cooling Capacity and Heating
Capacity. The represented values of
cooling capacity and heating capacity
must each be a self-declared value that
is:
(A) Less than or equal to the lower of:
(1) The mean of the sample, where:
khammond on DSKJM1Z7X2PROD with PROPOSALS2
and, x¯ is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(2) The lower 90 percent confidence
limit (LCL) of the true mean divided by
0.95, where:
And x¯ is the sample mean; s is the
sample standard deviation; n is the
number of samples; and t0.90 is the t
statistic for a 90 percent one-tailed
confidence interval with n¥1 degrees of
freedom (from appendix D of this part).
(B) Rounded according to:
(1) The nearest 100 Btu/h if cooling
capacity or heating capacity is less than
20,000 Btu/h,
(2) The nearest 200 Btu/h if cooling
capacity or heating capacity is greater
than or equal to 20,000 Btu/h but less
than 38,000 Btu/h, and
(3) The nearest 500 Btu/h if cooling
capacity or heating capacity is greater
than or equal to 38,000 Btu/h and less
than 65,000 Btu/h.
(d) Determination of represented
values—(1) All basic models except
outdoor units with no match and multisplit systems, multi-circuit systems, and
multi-head mini-split systems.
(i) For every individual model/
combination within a basic model,
either—
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
PO 00000
Frm 00024
Fmt 4701
Sfmt 4702
combination’’ composed entirely of
SDHV indoor units. For each SDHV
basic model distributed in commerce by
an ICM, the ICM must test the model of
indoor unit with a ‘‘tested combination’’
composed entirely of SDHV indoor
units, where the outdoor unit is the least
efficient model of outdoor unit with
which the SDHV indoor unit will be
paired. The least efficient model of
outdoor unit is the model of outdoor
unit in the lowest SEER2 combination
as certified by the outdoor unit
manufacturer. If there are multiple
outdoor unit models with the same
lowest SEER2 represented value, the
indoor coil manufacturer may select one
for testing purposes.
(v) For basic models that include
SDHV and an indoor unit of another
variety (i.e., non-ducted, low-static,
mid-static, and conventional ducted),
the represented value for the mixed
SDHV/other combination is the mean of
the represented values for the SDHV
and other tested combination as
determined in accordance with
paragraphs (c)(1) through (2) and
paragraphs (d)(3)(i) through (ii) of this
section.
(vi) All other individual combinations
of models of indoor units for the same
model of outdoor unit for which the
manufacturer chooses to make
representations must be rated as
separate basic models, and the
provisions of paragraphs (c)(1) through
(2) and (d)(3)(i) through (v) of this
section apply.
(e) Alternative efficiency
determination methods. In lieu of
testing, represented values of efficiency
or consumption may be determined
through the application of an AEDM
pursuant to the requirements of
§ 429.70(i) and the provisions of this
section.
(1) Power or energy consumption. Any
represented value of the average off
mode power consumption or other
measure of energy consumption of an
individual model/combination for
which consumers would favor lower
values must be greater than or equal to
the output of the AEDM but no greater
than the standard.
(2) Energy efficiency. Any represented
value of the SEER2, HSPF2, or other
measure of energy efficiency of an
individual model/combination for
which consumers would favor higher
values must be less than or equal to the
output of the AEDM but no less than the
standard.
(3) Cooling capacity. The represented
value of cooling capacity of an
individual model/combination must be
no greater than the cooling capacity
output simulated by the AEDM.
E:\FR\FM\09DEP2.SGM
09DEP2
EP09DE21.005
and, x¯ is the sample mean; n is the
number of samples; and xi is the ith
sample; or,
(B) The lower 90 percent confidence
limit (LCL) of the true mean divided by
0.95, where:
(A) A sample of sufficient size,
comprised of production units or
representing production units, must be
tested as complete systems with the
resulting represented values for the
individual model/combination obtained
in accordance with paragraphs (c)(1)
and (2) of this section; or
(B) The represented values of the
measures of energy efficiency or energy
consumption through the application of
an AEDM in accordance with paragraph
(e) of this section and § 429.70.
(2) Outdoor units with no match. All
models of outdoor units with no match
within a basic model must be tested
with a model of coil-only indoor unit
meeting the requirements of section
5.1.6.2 of AHRI 210/240–2023. Models
of outdoor units with no match may not
be rated with an AEDM, other than to
determine the represented values for
models using approved refrigerants
other than the one used in testing.
(3) For multi-split systems, multicircuit systems, and multi-head minisplit systems. The following applies:
(i) For each non-SDHV basic model, at
a minimum, a manufacturer must test
the model of outdoor unit with a ‘‘tested
combination’’ composed entirely of nonducted indoor units. For any models of
outdoor units also sold with models of
ducted indoor units, a manufacturer
must test a second ‘‘tested combination’’
composed entirely of ducted indoor
units (in addition to the non-ducted
combination). The ducted ‘‘tested
combination’’ must comprise the
highest static variety of ducted indoor
unit distributed in commerce (i.e.,
conventional, mid-static, or low-static).
(ii) If a manufacturer chooses to make
representations of a variety of a basic
model (i.e., conventional, low static, or
mid-static) other than a variety for
which a representation is required
under paragraph (b)(1) of this section
the manufacturer must conduct testing
of a tested combination according to the
requirements in paragraphs (c)(1) and
(2) of this section.
(iii) For basic models that include
mixed combinations of indoor units
(i.e., combinations that are comprised of
any two of the following varieties—nonducted, low-static, mid-static, and
conventional ducted indoor units), the
represented value for the mixed
combination is the mean of the
represented values for the individual
component combinations as determined
in accordance with paragraphs (c)(1)
and (2) and paragraphs (d)(3)(i) and (ii)
of this section.
(iv) For each SDHV basic model
distributed in commerce by an OUM,
the OUM must, at a minimum, test the
model of outdoor unit with a ‘‘tested
EP09DE21.004
(A) The mean of the sample, where:
EP09DE21.006
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
EP09DE21.003
70338
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
(4) Heating capacity. The represented
value of heating capacity of an
individual model/combination must be
no greater than the heating capacity
output simulated by the AEDM.
(f) Certification reports. This
paragraph specifies the information that
must be included in a certification
report.
(1) The requirements of § 429.12; and
(2) Pursuant to § 429.12(b)(13), for
each individual model (for singlepackage systems) or individual
combination (for split-systems,
including outdoor units with no match
and ‘‘tested combinations’’ for multisplit, multi-circuit, and multi-head
mini-split systems), a certification
report must include the following
public equipment-specific information:
(i) Commercial package air
conditioning equipment that is aircooled with a cooling capacity of less
than 65,000 Btu/h (3-Phase): The
seasonal energy efficiency ratio (SEER
in British thermal units per Watt-hour
(Btu/Wh), and the rated cooling capacity
in British thermal units per hour (Btu/
h).
(ii) Commercial package heating
equipment that is air-cooled with a
cooling capacity of less than 65,000 Btu/
h (3-Phase): The seasonal energy
efficiency ratio (SEER in British thermal
units per Watt-hour (Btu/Wh)), the
heating seasonal performance factor
(HSPF in British thermal units per Watthour (Btu/Wh)), and the rated cooling
capacity in British thermal units per
hour (Btu/h).
(iii) Variable refrigerant flow multisplit air conditioners that are air-cooled
with rated cooling capacity of less than
65,000 Btu/h (3-Phase): The seasonal
energy efficiency ratio (SEER in British
thermal units per Watt-hour (Btu/Wh))
and rated cooling capacity in British
thermal units per hour (Btu/h).
(iv) Variable refrigerant flow multisplit heat pumps that are air-cooled
with rated cooling capacity of less than
65,000 Btu/h (3-Phase): The seasonal
energy efficiency ratio (SEER in British
thermal units per Watt-hour (Btu/Wh)),
the heating seasonal performance factor
(HSPF in British thermal units per Watthour (Btu/Wh)), and rated cooling
capacity in British thermal units per
hour (Btu/h).
(3) Pursuant to § 429.12(b)(13), for
each individual model/combination
(including outdoor units with no match
and ‘‘tested combinations’’), a
certification report must include
supplemental information submitted in
PDF format. The equipment-specific,
supplemental information must include
any additional testing and testing set up
instructions (e.g., charging instructions)
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
for the basic model; identification of all
special features that were included in
rating the basic model; and all other
information (e.g., operational codes or
component settings) necessary to
operate the basic model under the
required conditions specified by the
relevant test procedure. A manufacturer
may also include with a certification
report other supplementary items in
PDF format (e.g., manuals) for DOE
consideration in performing testing
under subpart C of this part. The
equipment-specific, supplemental
information must include at least the
following:
(i) Air cooled commercial package air
conditioning equipment with a cooling
capacity of less than 65,000 Btu/h (3phase): The nominal cooling capacity in
British thermal units per hour (Btu/h);
rated airflow in standard cubic feet per
minute (SCFM) for each fan coil; rated
static pressure in inches of water;
refrigeration charging instructions (e.g.,
refrigerant charge, superheat and/or
subcooling temperatures); frequency or
control set points for variable speed
components (e.g., compressors, VFDs);
required dip switch/control settings for
step or variable components; a
statement whether the model will
operate at test conditions without
manufacturer programming; any
additional testing instructions, if
applicable; if a variety of motors/drive
kits are offered for sale as options in the
basic model to account for varying
installation requirements, the model
number and specifications of the motor
(to include efficiency, horsepower,
open/closed, and number of poles) and
the drive kit, including settings,
associated with that specific motor that
were used to determine the certified
rating; and which, if any, special
features were included in rating the
basic model.
(ii) Commercial package heating
equipment that is air-cooled with a
cooling capacity of less than 65,000 Btu/
h (3-phase): The nominal cooling
capacity in British thermal units per
hour (Btu/h); rated heating capacity in
British thermal units per hour (Btu/h);
rated airflow in standard cubic feet per
minute (SCFM) for each fan coil; rated
static pressure in inches of water;
refrigeration charging instructions (e.g.,
refrigerant charge, superheat and/or
subcooling temperatures); frequency or
control set points for variable speed
components (e.g., compressors, VFDs);
required dip switch/control settings for
step or variable components; a
statement whether the model will
operate at test conditions without
manufacturer programming; any
additional testing instructions, if
PO 00000
Frm 00025
Fmt 4701
Sfmt 4702
70339
applicable; if a variety of motors/drive
kits are offered for sale as options in the
basic model to account for varying
installation requirements, the model
number and specifications of the motor
(to include efficiency, horsepower,
open/closed, and number of poles) and
the drive kit, including settings,
associated with that specific motor that
were used to determine the certified
rating; and which, if any, special
features were included in rating the
basic model.
(iii) Variable refrigerant flow multisplit air conditioners that are air-cooled
with a cooling capacity of less than
65,000 Btu/h (3-Phase): The nominal
cooling capacity in British thermal units
per hour (Btu/h); outdoor unit(s) and
indoor units identified in the tested
combination; components needed for
heat recovery, if applicable; rated
airflow in standard cubic feet per
minute (SCFM) for each indoor unit;
rated static pressure in inches of water;
compressor frequency set points;
required dip switch/control settings for
step or variable components; a
statement whether the model will
operate at test conditions without
manufacturer programming; any
additional testing instructions, if
applicable; if a variety of motors/drive
kits are offered for sale as options in the
basic model to account for varying
installation requirements, the model
number and specifications of the motor
(to include efficiency, horsepower,
open/closed, and number of poles) and
the drive kit, including settings,
associated with that specific motor that
were used to determine the certified
rating; and which, if any, special
features were included in rating the
basic model. Additionally, upon DOE
request, the manufacturer must provide
a layout of the system set-up for testing
including charging instructions
consistent with the installation manual.
(iv) Variable refrigerant flow multisplit heat pumps that are air-cooled
with rated cooling capacity of less than
65,000 Btu/h (3-Phase): The nominal
cooling capacity in British thermal units
per hour (Btu/h); rated heating capacity
in British thermal units per hour (Btu/
h); outdoor unit(s) and indoor units
identified in the tested combination;
components needed for heat recovery, if
applicable; rated airflow in standard
cubic feet per minute (SCFM) for each
indoor unit; rated static pressure in
inches of water; compressor frequency
set points; required dip switch/control
settings for step or variable components;
a statement whether the model will
operate at test conditions without
manufacturer programming; any
additional testing instructions, if
E:\FR\FM\09DEP2.SGM
09DEP2
70340
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
applicable; if a variety of motors/drive
kits are offered for sale as options in the
basic model to account for varying
installation requirements, the model
number and specifications of the motor
(to include efficiency, horsepower,
open/closed, and number of poles) and
the drive kit, including settings,
associated with that specific motor that
were used to determine the certified
rating; and which, if any, special
features were included in rating the
basic model. Additionally, upon DOE
request, the manufacturer must provide
a layout of the system set-up for testing
including charging instructions
consistent with the installation manual.
■ 6. Amend § 429.70 by:
■ a. Revising paragraph (c) introductory
text;
■ b. Revising the tables in paragraphs
(c)(2)(iv) and (c)(5)(vi)(B); and
■ c. Adding paragraph (i).
The revisions and addition read as
follows:
§ 429.70 Alternative methods for
determining energy efficiency and energy
use.
*
*
*
*
*
(c) Alternative efficiency
determination method (AEDM) for
commercial HVAC & WH products
(excluding air-cooled, three-phase,
small commercial package air
conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h and air-cooled, threephase, variable refrigerant flow multisplit air conditioners and heat pumps
with less than 65,000 Btu/h cooling
capacity), and commercial refrigerators,
freezers, and refrigerator-freezers—
*
*
*
*
*
(2) * * *
(iv) * * *
Minimum number of
distinct models that
must be tested per
AEDM
Validation class
(A) Commercial HVAC validation classes
Air-Cooled, Split and Packaged ACs and HPs Greater than or Equal to 65,000 Btu/h Cooling Capacity and Less than
760,000 Btu/h Cooling Capacity.
Water-Cooled, Split and Packaged ACs and HPs, All Cooling Capacities ................................................................................
Evaporatively-Cooled, Split and Packaged ACs and HPs, All Capacities .................................................................................
Water-Source HPs, All Capacities ..............................................................................................................................................
Single Package Vertical ACs and HPs .......................................................................................................................................
Packaged Terminal ACs and HPs ..............................................................................................................................................
Air-Cooled, Variable Refrigerant Flow ACs and HPs Greater than or Equal to 65,000 Btu/h Cooling Capacity ......................
Water-Cooled, Variable Refrigerant Flow ACs and HPs ............................................................................................................
Computer Room Air Conditioners, Air Cooled ............................................................................................................................
Computer Room Air Conditioners, Water-Cooled .......................................................................................................................
2 Basic Models.
2
2
2
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
2
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
Models.
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
(B) Commercial water heater validation classes
Gas-fired Water Heaters and Hot Water Supply Boilers Less than 10 Gallons ........................................................................
Gas-fired Water Heaters and Hot Water Supply Boilers Greater than or Equal to 10 Gallons .................................................
Oil-fired Water Heaters and Hot Water Supply Boilers Less than 10 Gallons ...........................................................................
Oil-fired Water Heaters and Hot Water Supply Boilers Greater than or Equal to 10 Gallons ...................................................
Electric Water Heaters ................................................................................................................................................................
Heat Pump Water Heaters ..........................................................................................................................................................
Unfired Hot Water Storage Tanks ...............................................................................................................................................
(C) Commercial packaged boilers validation classes
Gas-fired, Hot Water Only Commercial Packaged Boilers .........................................................................................................
Gas-fired, Steam Only Commercial Packaged Boilers ...............................................................................................................
Gas-fired Hot Water/Steam Commercial Packaged Boilers .......................................................................................................
Oil-fired, Hot Water Only Commercial Packaged Boilers ...........................................................................................................
Oil-fired, Steam Only Commercial Packaged Boilers .................................................................................................................
Oil-fired Hot Water/Steam Commercial Packaged Boilers .........................................................................................................
(D) Commercial furnace validation classes
Gas-fired Furnaces ......................................................................................................................................................................
Oil-fired Furnaces ........................................................................................................................................................................
2 Basic Models.
2 Basic Models.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
(E) Commercial refrigeration equipment validation classes
Self-Contained Open Refrigerators .............................................................................................................................................
Self-Contained Open Freezers ...................................................................................................................................................
Remote Condensing Open Refrigerators ....................................................................................................................................
Remote Condensing Open Freezers ..........................................................................................................................................
Self-Contained Closed Refrigerators ..........................................................................................................................................
Self-Contained Closed Freezers .................................................................................................................................................
Remote Condensing Closed Refrigerators .................................................................................................................................
Remote Condensing Closed Freezers ........................................................................................................................................
2
2
2
2
2
2
2
2
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Basic
Models.
Models.
Models.
Models.
Models.
Models.
Models.
Models.
1 The minimum number of tests indicated above must be comprised of a transparent model, a solid model, a vertical model, a semi-vertical
model, a horizontal model, and a service-over-the counter model, as applicable based on the equipment offering. However, manufacturers do not
need to include all types of these models if it will increase the minimum number of tests that need to be conducted.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
PO 00000
Frm 00026
Fmt 4701
Sfmt 4702
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
*
*
*
(5) * * *
(vi) * * *
*
*
(B) * * *
Equipment
Metric
Commercial Packaged Boilers .....................................................................................
Combustion Efficiency ..............................
Thermal Efficiency ....................................
Thermal Efficiency ....................................
Standby Loss ............................................
R-Value .....................................................
Energy Efficiency Ratio ............................
Coefficient of Performance .......................
Integrated Energy Efficiency Ratio ...........
Energy Efficiency Ratio ............................
Coefficient of Performance .......................
Integrated Energy Efficiency Ratio ...........
Energy Efficiency Ratio ............................
Coefficient of Performance .......................
Integrated Energy Efficiency Ratio ...........
Energy Efficiency Ratio ............................
Coefficient of Performance .......................
Integrated Energy Efficiency Ratio ...........
Energy Efficiency Ratio ............................
Coefficient of Performance .......................
Energy Efficiency Ratio ............................
Coefficient of Performance .......................
Energy Efficiency Ratio ............................
Coefficient of Performance .......................
Integrated Energy Efficiency Ratio ...........
Sensible Coefficient of Performance ........
Thermal Efficiency ....................................
Daily Energy Consumption .......................
Commercial Water Heaters or Hot Water Supply Boilers ...........................................
Unfired Storage Tanks .................................................................................................
Air-Cooled, Split and Packaged ACs and HPs Greater than or Equal to 65,000 Btu/
h Cooling Capacity and Less than 760,000 Btu/h Cooling Capacity.
Water-Cooled, Split and Packaged ACs and HPs, All Cooling Capacities .................
Evaporatively-Cooled, Split and Packaged ACs and HPs, All Capacities ..................
Water-Source HPs, All Capacities ...............................................................................
Single Package Vertical ACs and HPs ........................................................................
Packaged Terminal ACs and HPs ...............................................................................
Variable Refrigerant Flow ACs and HPs (Excluding Air-Cooled, Three-phase with
Less than 65,000 Btu/h Cooling Capacity).
Computer Room Air Conditioners ................................................................................
Commercial Warm-Air Furnaces ..................................................................................
Commercial Refrigeration Equipment ..........................................................................
khammond on DSKJM1Z7X2PROD with PROPOSALS2
*
*
*
*
*
(i) Alternate Efficiency Determination
Method (AEDM) for air-cooled, threephase, small commercial package air
conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h and air-cooled, threephase, variable refrigerant flow multisplit air conditioners and heat pumps
with less than 65,000 Btu/h cooling
capacity.
(1) Applicability. (i) For air-cooled,
three-phase, small commercial package
air conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h and air-cooled, threephase, variable refrigerant flow multisplit air conditioners and heat pumps
with a cooling capacity of less than
65,000 Btu/h subject to standards in
terms of seasonal energy efficiency ratio
(SEER) and heating seasonal
performance factor (HSPF),
representations with respect to the
energy use or efficiency, including
compliance certifications, are subject to
the requirements in § 429.70(c) of this
title as it appeared in the 10 CFR parts
200–499 edition revised as of January 1,
2021.
(ii) For air-cooled, three-phase, small
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 Btu/h and
VerDate Sep<11>2014
19:25 Dec 08, 2021
70341
Jkt 256001
air-cooled, three-phase, variable
refrigerant flow multi-split air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h subject to standards in terms of
seasonal energy efficiency ratio 2
(‘‘SEER2’’) and heating seasonal
performance factor 2 (‘‘HSPF2’’) metrics,
representations with respect to the
energy use or efficiency, including
compliance certifications, are subject to
the requirements in this section. If
manufacturers choose to certify
compliance with any standards in terms
of SEER2 and HSPF2 prior to the
applicable compliance date for those
standards, the requirements of this
section must be followed.
(2) Criteria an AEDM must satisfy. A
manufacturer may not apply an AEDM
to an individual model/combination to
determine its represented values (SEER2
and HSPF2, as applicable) pursuant to
this section unless authorized pursuant
to § 429.64(e) and:
(i) The AEDM is derived from a
mathematical model that estimates the
energy efficiency or energy
consumption characteristics of the
individual model or combination
(SEER2 and HSPF2, as applicable) as
measured by the applicable DOE test
procedure; and
PO 00000
Frm 00027
Fmt 4701
Sfmt 4702
Applicable
tolerance
(%)
5 (0.05)
5 (0.05)
5 (0.05)
10 (0.1)
10 (0.1)
5 (0.05)
5 (0.05)
10 (0.1)
5 (0.05)
5 (0.05)
10 (0.1)
5 (0.05)
5 (0.05)
10 (0.1)
5 (0.05)
5 (0.05)
10 (0.1)
5 (0.05)
5 (0.05)
5 (0.05)
5 (0.05)
5 (0.05)
5 (0.05)
10 (0.1)
5 (0.05)
5 (0.05)
5 (0.05)
(ii) The manufacturer has validated
the AEDM in accordance with
paragraph (i)(3) of this section.
(3) Validation of an AEDM. For
manufacturers whose models of aircooled, three-phase, small commercial
package air conditioning and heating
equipment with a cooling capacity of
less than 65,000 Btu/h or air-cooled,
three-phase, variable refrigerant flow
multi-split air conditioners and heat
pumps with a cooling capacity of less
than 65,000 Btu/h are otherwise
identical to their central air conditioner
and heat pump models (meaning
differing only in phase of the electrical
system and the phase of power input for
which the motors and compressors are
designed) and who have validated an
AEDM for the otherwise identical
central air conditioners and heat pumps
under § 429.70(e)(2), no additional
validation is required. For
manufacturers whose models of aircooled, three-phase, small commercial
package air conditioning and heating
equipment with a cooling capacity of
less than 65,000 Btu/h or air-cooled,
three-phase, variable refrigerant flow
multi-split air conditioners and heat
pumps with a cooling capacity of less
than 65,000 Btu/h who have not
validated an AEDM for otherwise
identical central air conditioners and
E:\FR\FM\09DEP2.SGM
09DEP2
khammond on DSKJM1Z7X2PROD with PROPOSALS2
70342
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
heat pumps under § 429.70(e)(2) must,
before using an AEDM, validate the
AEDM’s accuracy and reliability as
follows:
(i) Minimum testing. The
manufacturer must test a single unit
each of two basic models in accordance
with paragraph (i)(3)(iii) of this section.
Using the AEDM, calculate the energy
use or efficiency for each of the tested
individual models/combinations within
each basic model. Compare the
represented value based on testing and
the AEDM energy use or efficiency
output according to paragraph (i)(3)(ii)
of this section. The manufacturer is
responsible for ensuring the accuracy
and reliability of the AEDM and that
their representations are appropriate
and the models being distributed in
commerce meet the applicable
standards, regardless of the amount of
testing required in this paragraph.
(ii) Individual model/combination
tolerances. This paragraph (i)(3)(ii)
provides the tolerances applicable to
individual models/combinations rated
using an AEDM.
(A) The predicted represented values
for each individual model/combination
calculated by applying the AEDM may
not be more than four percent greater
(for measures of efficiency) or less (for
measures of consumption) than the
values determined from the
corresponding test of the individual
model/combination.
(B) The predicted energy efficiency or
consumption for each individual model/
combination calculated by applying the
AEDM must meet or exceed the
applicable federal energy conservation
standard.
(iii) Additional test unit requirements.
(A) Each AEDM must be supported by
test data obtained from physical tests of
current individual models/
combinations; and
(B) Test results used to validate the
AEDM must meet or exceed current,
applicable Federal standards as
specified in part 431 of this chapter; and
(C) Each test must have been
performed in accordance with the
applicable DOE test procedure with
which compliance is required at the
time the individual models/
combinations used for validation are
distributed in commerce.
(4) AEDM records retention
requirements. If a manufacturer has
used an AEDM to determine
representative values pursuant to this
section, the manufacturer must have
available upon request for inspection by
the Department records showing:
(i) The AEDM, including the
mathematical model, the engineering or
statistical analysis, and/or computer
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
simulation or modeling that is the basis
of the AEDM;
(ii) Product information, complete test
data, AEDM calculations, and the
statistical comparisons from the units
tested that were used to validate the
AEDM pursuant to paragraph (i)(3) of
this section; and
(iii) Product information and AEDM
calculations for each individual model/
combination to which the AEDM has
been applied.
(5) Additional AEDM requirements. If
requested by the Department, the
manufacturer must:
(i) Conduct simulations before
representatives of the Department to
predict the performance of particular
individual models/combinations;
(ii) Provide analyses of previous
simulations conducted by the
manufacturer; and/or
(iii) Conduct certification testing of
individual models or combinations
selected by the Department.
(6) AEDM verification testing. DOE
may use the test data for a given
individual model/combination
generated pursuant to § 429.104 to
verify the represented value determined
by an AEDM as long as the following
process is followed:
(i) Selection of units. DOE will obtain
one or more units for test from retail, if
available. If units cannot be obtained
from retail, DOE will request that a unit
be provided by the manufacturer;
(ii) Lab requirements. DOE will
conduct testing at an independent,
third-party testing facility of its
choosing. In cases where no third-party
laboratory is capable of testing the
equipment, testing may be conducted at
a manufacturer’s facility upon DOE’s
request.
(iii) Testing. At no time during
verification testing may the lab and the
manufacturer communicate without
DOE authorization. If, during test set-up
or testing, the lab indicates to DOE that
it needs additional information
regarding a given individual model or
combination in order to test in
accordance with the applicable DOE test
procedure, DOE may organize a meeting
between DOE, the manufacturer, and the
lab to provide such information.
(iv) Failure to meet certified value. If
an individual model/combination tests
worse than its certified value (i.e., lower
than the certified efficiency value or
higher than the certified consumption
value) by more than 5 percent, or the
test results in cooling capacity that is
lower than its certified cooling capacity,
DOE will notify the manufacturer. DOE
will provide the manufacturer with all
documentation related to the test set up,
test conditions, and test results for the
PO 00000
Frm 00028
Fmt 4701
Sfmt 4702
unit. Within the timeframe allotted by
DOE, the manufacturer may present any
and all claims regarding testing validity.
(v) Tolerances. This paragraph
specifies the tolerances DOE will permit
when conducting verification testing.
(A) For consumption metrics, the
result from a DOE verification test must
be less than or equal to 1.05 multiplied
by the certified represented value.
(B) For efficiency metrics, the result
from a DOE verification test must be
greater than or equal to 0.95 multiplied
by the certified represented value.
(vi) Invalid represented value. If,
following discussions with the
manufacturer and a retest where
applicable, DOE determines that the
verification testing was conducted
appropriately in accordance with the
DOE test procedure, DOE will issue a
determination that the represented
values for the basic model are invalid.
The manufacturer must conduct
additional testing and re-rate and recertify the individual models/
combinations within the basic model
that were rated using the AEDM based
on all test data collected, including
DOE’s test data.
(vii) AEDM use. This paragraph
(i)(6)(vii) specifies when a
manufacturer’s use of an AEDM may be
restricted due to prior invalid
represented values.
(A) If DOE has determined that a
manufacturer made invalid represented
values on individual models/
combinations within two or more basic
models rated using the manufacturer’s
AEDM within a 24-month period, the
manufacturer must test the least
efficient and most efficient individual
model/combination within each basic
model in addition to the individual
model/combination specified in
§ 429.16(b)(2). The 24-month period
begins with a DOE determination that a
represented value is invalid through the
process outlined in paragraphs (i)(6)(i)
through (vi) of this section.
(B) If DOE has determined that a
manufacturer made invalid represented
values on more than four basic models
rated using the manufacturer’s AEDM
within a 24-month period, the
manufacturer may no longer use an
AEDM.
(C) If a manufacturer has lost the
privilege of using an AEDM, the
manufacturer may regain the ability to
use an AEDM by:
(1) Investigating and identifying
cause(s) for failures;
(2) Taking corrective action to address
cause(s);
(3) Performing six new tests per basic
model, a minimum of two of which
must be performed by an independent,
E:\FR\FM\09DEP2.SGM
09DEP2
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
third-party laboratory from units
obtained from retail to validate the
AEDM; and
(4) Obtaining DOE authorization to
resume use of an AEDM.
■ 7. Section 429.134 is amended by
adding paragraph (s) to read as follows:
and/or Ch value pursuant to appendix
B1 to subpart F of part 431.
§ 429.134 Product-specific enforcement
provisions.
■
*
Authority: 42 U.S.C. 6291–6317; 28 U.S.C.
2461 note.
8. The authority citation for part 431
continues to read as follows:
*
*
*
*
(s) Air-cooled, three-phase, small
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 Btu/h and
air-cooled, three-phase, variable
refrigerant flow multi-split air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h. The following provisions apply for
assessment and enforcement testing of
models subject to standards in terms of
SEER2 and HSPF2 (as applicable).
(1) Verification of cooling capacity.
The cooling capacity of each tested unit
of the individual model (for singlepackage units) or individual
combination (for split systems) will be
measured pursuant to the test
requirements of appendix B1 to subpart
F of part 431. The mean of the cooling
capacity measurement(s) (either the
measured cooling capacity for a single
unit sample or the average of the
measured cooling capacities for a
multiple unit sample) will be used to
determine the applicable standards for
purposes of compliance.
(2) Verification of CD value. (i) For
models other than models of outdoor
units with no match, if manufacturers
certify that they did not conduct the
optional tests to determine the Cc and/
or Ch value for an individual model (for
single-package systems) or individual
combination (for split systems), as
applicable, the default Cc and/or Ch
value will be used as the basis for
calculation of SEER2 or HSPF2 for each
unit tested. If manufacturers certify that
they conducted the optional tests to
determine the Cc and/or Ch value for an
individual model (for single-package
systems) or individual combination (for
split systems), as applicable, the Cc and/
or Ch value will be measured pursuant
to the test requirements of appendix B1
to subpart F of part 431 for each unit
tested and the result for each unit tested
(either the tested value or the default
value, as selected according to the
criteria for the cyclic test in Sections
6.1.3.1 and 6.1.3.2 of AHRI 210/240–
2023 (incorporated by reference, see
§ 429.4)) used as the basis for
calculation of SEER2 or HSPF2 for that
unit.
(ii) For models of outdoor units with
no match, DOE will use the default Cc
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
PART 431—ENERGY EFFICIENCY
PROGRAM FOR CERTAIN
COMMERCIAL AND INDUSTRIAL
EQUIPMENT
9. Amend § 431.92 in the definition of
Basic model, by:
■ a. Revising paragraphs (2) and (5); and
■ b. Adding paragraph (7).
The revisions and addition read as
follows:
■
§ 431.92 Definitions concerning
commercial air conditioners and heat
pumps.
*
*
*
*
*
Basic model includes:
*
*
*
*
*
(2) Small, large, and very large aircooled or water-cooled commercial
package air conditioning and heating
equipment (excluding air-cooled, threephase, small commercial package air
conditioning and heating equipment
with a cooling capacity of less than
65,000 Btu/h cooling capacity) means
all units manufactured by one
manufacturer within a single equipment
class, having the same or comparably
performing compressor(s), heat
exchangers, and air moving system(s)
that have a common ‘‘nominal’’ cooling
capacity.
*
*
*
*
*
(5) Variable refrigerant flow systems
(excluding air-cooled, three-phase,
variable refrigerant flow air conditioners
and heat pumps with a cooling capacity
of less than 65,000 Btu/h) means all
units manufactured by one
manufacturer within a single equipment
class, having the same primary energy
source (e.g., electric or gas), and which
have the same or comparably
performing compressor(s) that have a
common ‘‘nominal’’ cooling capacity
and the same heat rejection medium
(e.g., air or water) (includes VRF water
source heat pumps).
*
*
*
*
*
(7) Air-cooled, three-phase, small
commercial package air conditioning
and heating equipment with a cooling
capacity of less than 65,000 Btu/h and
air-cooled, three-phase, variable
refrigerant flow multi-split air
conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/
h means all units manufactured by one
manufacturer; having the same primary
energy source; and, which have
PO 00000
Frm 00029
Fmt 4701
Sfmt 4702
70343
essentially identical electrical, physical,
and functional (or hydraulic)
characteristics that affect energy
consumption, energy efficiency, water
consumption, or water efficiency; where
essentially identical electrical, physical,
and functional (or hydraulic)
characteristics means:
(i) For split systems manufactured by
outdoor unit manufacturers (OUMs): All
individual combinations having the
same model of outdoor unit, which
means comparably performing
compressor(s) [a variation of no more
than five percent in displacement rate
(volume per time) as rated by the
compressor manufacturer, and no more
than five percent in capacity and power
input for the same operating conditions
as rated by the compressor
manufacturer], outdoor coil(s) [no more
than five percent variation in face area
and total fin surface area; same fin
material; same tube material], and
outdoor fan(s) [no more than ten percent
variation in airflow and no more than
twenty percent variation in power
input];
(ii) For split systems having indoor
units manufactured by independent coil
manufacturers (ICMs): All individual
combinations having comparably
performing indoor coil(s) [plus or minus
one square foot face area, plus or minus
one fin per inch fin density, and the
same fin material, tube material, number
of tube rows, tube pattern, and tube
size]; and
(iii) For single-package systems: All
individual models having comparably
performing compressor(s) [no more than
five percent variation in displacement
rate (volume per time) rated by the
compressor manufacturer, and no more
than five percent variations in capacity
and power input rated by the
compressor manufacturer corresponding
to the same compressor rating
conditions], outdoor coil(s) and indoor
coil(s) [no more than five percent
variation in face area and total fin
surface area; same fin material; same
tube material], outdoor fan(s) [no more
than ten percent variation in outdoor
airflow], and indoor blower(s) [no more
than ten percent variation in indoor
airflow, with no more than twenty
percent variation in fan motor power
input];
(iv) Except that,
(A) For single-package systems and
single-split systems, manufacturers may
instead choose to make each individual
model/combination its own basic model
provided the testing and represented
value requirements in 10 CFR 429.64 of
this chapter are met; and
(B) For multi-split, multi-circuit, and
multi-head mini-split combinations, a
E:\FR\FM\09DEP2.SGM
09DEP2
70344
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
basic model may not include both
individual small-duct, high velocity
(SDHV) combinations and non-SDHV
combinations even when they include
the same model of outdoor unit. The
manufacturer may choose to identify
specific individual combinations as
additional basic models.
*
*
*
*
*
■ 10. Amend § 431.95 by:
■ a. Removing paragraph (b)(1);
■ b. Redesignating paragraph (b)(2) as
(b)(1);
■ c. Revising newly redesignated
paragraph (b)(1);
■ d. Adding new paragraph (b)(2);
■ e. Revising paragraph (b)(6); and
■ f. Revising paragraph (c)(2).
The revisions and addition read as
follows:
§ 431.95 Materials incorporated by
reference.
*
*
*
*
*
(b) * * *
(1) ANSI/AHRI Standard 210/240–
2008, ‘‘2008 Standard for Performance
Rating of Unitary Air-Conditioning &
Air-Source Heat Pump Equipment’’,
approved by ANSI on October 27, 2011
and updated by addendum 1 in June
2011 and addendum 2 in March 2012
(AHRI 210/240–2008), IBR approved for
§ 431.96 and appendix B to this subpart.
(2) AHRI Standard 210/240–2023,
‘‘Performance Rating of Unitary AirConditioning & Air-Source Heat Pump
Equipment,’’ approved May 2020 (AHRI
210/240–2023), IBR approved for
appendix B1 to this subpart.
*
*
*
*
*
(6) ANSI/AHRI Standard 1230–2010,
‘‘2010 Standard for Performance Rating
of Variable Refrigerant Flow (VRF)
Multi-split Air-Conditioning and Heat
Pump Equipment,’’ approved August 2,
2010 and updated by addendum 1 in
March 2011 (AHRI 1230–2010), IBR
approved for § 431.96 and appendix B to
this subpart.
(c) * * *
(2) ANSI/ASHRAE Standard 37–2009,
(‘‘ANSI/ASHRAE 37–2009’’), ‘‘Methods
of Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat
Pump Equipment,’’ ASHRAE approved
June 24, 2009, IBR approved for § 431.96
and appendices A and B1 to this
subpart.
*
*
*
*
*
11. Amend § 431.96 by revising
paragraph (b)(1) and Table 1 to
paragraph (b)(2), to read as follows:
■
§ 431.96 Uniform test method for the
measurement of energy efficiency of
commercial air conditioners and heat
pumps.
*
*
*
*
*
(b) Testing and calculations. (1)
Determine the energy efficiency of each
type of covered equipment by
conducting the test procedure(s) listed
in table 1 to this section along with any
additional testing provisions set forth in
paragraphs (c) through (g) of this section
and appendices A, B, and B1 to this
subpart, that apply to the energy
efficiency descriptor for that equipment,
category, and cooling capacity. The
omitted sections of the test procedures
listed in table 1 to this section must not
be used. For equipment with multiple
appendices listed in table 1, consult the
notes at the beginning of those
appendices to determine the applicable
appendix to use for testing.
(2) * * *
TABLE 1 TO § 431.96—TEST PROCEDURES FOR COMMERCIAL AIR CONDITIONERS AND HEAT PUMPS
Equipment type
Category
Small Commercial Package Air-Conditioning and Heating Equipment.
Air-Cooled, 3Phase, AC and
HP.
Air-Cooled AC and
HP.
Water-Cooled and
EvaporativelyCooled AC.
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Large Commercial Package Air-Conditioning and Heating Equipment.
Very Large Commercial Package AirConditioning and Heating Equipment.
Packaged Terminal Air Conditioners
and Heat Pumps.
Computer Room Air Conditioners .......
VerDate Sep<11>2014
19:25 Dec 08, 2021
Cooling capacity
Energy efficiency
descriptor
SEER and HSPF
Appendix B to this
subpart 2.
None.
Appendix B1 to
this subpart 2.
Appendix A to this
subpart.
AHRI 210/240–
2008 (omit section 6.5).
AHRI 340/360–
2007 (omit section 6.3).
ISO Standard
13256–1 (1998).
Appendix A to this
subpart.
None.
≥65,000 Btu/h and
<135,000 Btu/h.
<65,000 Btu/h ......
SEER2 and
HSPF2.
EER, IEER, and
COP.
EER ......................
EER ......................
Water-Source HP
<135,000 Btu/h ....
EER and COP ......
Air-Cooled AC and
HP.
EER, IEER and
COP.
Water-Cooled and
EvaporativelyCooled AC.
AC and HP ...........
≥135,000 Btu/h
and <240,000
Btu/h.
≥135,000 Btu/h
and <240,000
Btu/h.
≥240,000 Btu/h
and <760,000
Btu/h.
≥240,000 Btu/h
and <760,000
Btu/h.
<760,000 Btu/h ....
AC ........................
<65,000 Btu/h ......
Jkt 256001
PO 00000
Additional test
procedure
provisions as
indicated in the
listed paragraphs
of this section
<65,000 Btu/h ......
≥65,000 Btu/h and
<135,000 Btu/h.
Water-Cooled and
EvaporativelyCooled AC.
Air-Cooled AC and
HP.
Use tests,
conditions, and
procedures in 1
Frm 00030
Fmt 4701
Sfmt 4702
EER ......................
EER, IEER and
COP.
EER ......................
EER and COP ......
SCOP ...................
E:\FR\FM\09DEP2.SGM
None.
Paragraphs (c)
and (e).
Paragraphs (c)
and (e).
Paragraph (e).
None.
AHRI 340/360–
2007 (omit section 6.3).
Appendix A to this
subpart.
Paragraphs (c)
and (e).
AHRI 340/360–
2007 (omit section 6.3).
Paragraph (g) of
this section.
ASHRAE 127–
2007 (omit section 5.11).
Paragraphs (c)
and (e).
09DEP2
None.
Paragraphs (c),
(e), and (g).
Paragraphs (c)
and (e).
70345
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
TABLE 1 TO § 431.96—TEST PROCEDURES FOR COMMERCIAL AIR CONDITIONERS AND HEAT PUMPS—Continued
Equipment type
Cooling capacity
Energy efficiency
descriptor
Use tests,
conditions, and
procedures in 1
≥65,000 Btu/h and
<760,000 Btu/h.
SCOP ...................
<65,000 Btu/h (3phase).
SEER ...................
ASHRAE 127–
2007 (omit section 5.11).
Appendix B to this
subpart 2.
Appendix B1 to
this subpart 2.
AHRI 1230–2010
(omit sections
5.1.2 and 6.6).
Appendix B to this
subpart 2.
Appendix B1 to
this subpart 2.
AHRI 1230–2010
(omit sections
5.1.2 and 6.6).
AHRI 1230–2010
(omit sections
5.1.2 and 6.6).
AHRI 390–2003
(omit section
6.4).
Category
Variable Refrigerant Flow Multi-split
Systems.
AC ........................
SEER2 .................
Variable Refrigerant Flow Multi-split
Systems, Air-cooled.
HP ........................
≥65,000 Btu/h and
<760,000 Btu/h.
EER ......................
<65,000 Btu/h (3phase).
SEER and HSPF
≥65,000 Btu/h and
<760,000 Btu/h.
SEER2 and
HSPF2.
EER and COP ......
Variable Refrigerant Flow Multi-split
Systems, Water-source.
HP ........................
<760,000 Btu/h ....
EER and COP ......
Single Package Vertical Air Conditioners and Single Package Vertical
Heat Pumps.
AC and HP ...........
<760,000 Btu/h ....
EER and COP ......
Additional test
procedure
provisions as
indicated in the
listed paragraphs
of this section
Paragraphs (c)
and (e).
None.
None.
Paragraphs (c),
(d), (e), and (f).
None.
None.
Paragraphs (c),
(d), (e), and (f).
Paragraphs (c),
(d), (e), and (f).
Paragraphs (c)
and (e).
1 Incorporated
by reference, as applicable; see § 431.95.
equipment with multiple appendices listed in Table 1, consult the notes at the beginning of those appendices to determine the applicable
appendix to use for testing.
2 For
*
*
*
*
*
12. Add appendix B to subpart F of
part 431 to read as follows:
■
khammond on DSKJM1Z7X2PROD with PROPOSALS2
Appendix B to Subpart F of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
Air-Cooled, Three-Phase, Small
Commercial Package Air Conditioning
and Heating Equipment With a Cooling
Capacity of Less Than 65,000 Btu/H and
Air-Cooled, Three-Phase, Variable
Refrigerant Flow Multi-Split Air
Conditioners and Heat Pumps With a
Cooling Capacity of Less Than 65,000
BTU/H
Note: Manufacturers must use the results of
testing under this appendix to determine
compliance with the relevant standard from
§ 431.97 as that standard appeared in the
January 1, 2021 edition of 10 CFR parts 200–
499. Specifically, before [Date 360 days
following publication of the final rule]
representations must be based upon results
generated either under this appendix or
under 10 CFR 431.96 as it appeared in the
10 CFR parts 200–499 edition revised as of
January 1, 2021.
Note: For any amended standards for aircooled, three-phase, small commercial
package air conditioning and heating
equipment with a cooling capacity of less
than 65,000 Btu/h and air-cooled, threephase, variable refrigerant flow multi-split air
conditioners and heat pumps with a cooling
capacity of less than 65,000 Btu/h that rely
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
on SEER2 and HSPF2 published after January
1, 2021, manufacturers must use the results
of testing under appendix B1 to determine
compliance.
Representations related to energy
consumption must be made in accordance
with the appropriate appendix that applies
(i.e., appendices B or B1) when determining
compliance with the relevant standard.
Manufacturers may also use appendix B1 to
certify compliance with any amended
standards prior to the applicable compliance
date for those standards.
1. Incorporation by Reference
DOE incorporated by reference in § 431.95,
the entire standard for ANSI/AHRI 210/240–
2008, ‘‘Performance Rating of Unitary AirConditioning & Air-Source Heat Pump
Equipment’’; and ANSI/AHRI 1230–2010,
‘‘Performance Rating of Variable Refrigerant
Flow (VRF) Multi-split Air-conditioning and
Heat Pump Equipment.’’ However, certain
enumerated provisions of those standards, as
set forth in paragraphs (a) and (b) of this
section, are inapplicable. To the extent there
is a conflict between the terms or provisions
of a referenced industry standard and the
CFR, the CFR provisions control.
(a) ANSI/AHRI 210/240–2008:
(i) Section 6.5 is inapplicable as specified
in section 2.1 of this appendix.
(ii) Reserved.
(b) ANSI/AHRI 1230–2010:
(i) Section 5.1.2—Manufacturer
involvement is inapplicable as specified in
section 2.2(1) of this appendix.
(ii) Section 6.6—Verification testing and
uncertainty is inapplicable as specified in
section 2.2(2) of this appendix.
PO 00000
Frm 00031
Fmt 4701
Sfmt 4702
2. General
2.1 Air-cooled, three-phase, small
commercial package air conditioning and
heating equipment with a cooling capacity of
less than 65,000 Btu/h. Determine the
seasonal energy efficiency ratio (SEER) and
heating seasonal performance factor (HSPF)
(as applicable) in accordance with ANSI/
AHRI 210/240–2008; however, Section 6.5,
Tolerances, of ANSI/AHRI 210/240–2008 is
not applicable. Sections 3 and 4 of this
appendix provide additional instructions for
determining SEER and HSPF. In cases where
there is a conflict, the language of this
appendix takes precedence over ANSI/AHRI
210/240–2008.
1.2. Air-cooled, three-phase, variable
refrigerant flow multi-split air conditioners
and heat pumps with a cooling capacity of
less than 65,000 Btu/h. Determine the SEER
and HSPF (as applicable) in accordance with
ANSI/AHRI 1230–2010; however, the
following enumerated provisions of that
document are not applicable.
(1) Section 5.1.2—Manufacturer
involvement,
(2) Section 6.6—Verification testing and
uncertainty
Sections 3 through 6 of this appendix
provide additional instructions for
determining SEER and HSPF. In cases where
there is a conflict, the language of this
appendix takes precedence over ANSI/AHRI
1230–2010.
3. Optional break-in period. Manufacturers
may optionally specify a ‘‘break-in’’ period,
not to exceed 20 hours, to operate the
equipment under test prior to conducting the
test method specified in this appendix. A
E:\FR\FM\09DEP2.SGM
09DEP2
70346
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
manufacturer who elects to use an optional
compressor break-in period in its
certification testing should record this
period’s duration as part of the information
in the supplemental testing instructions
under 10 CFR 429.43.
4. Additional provisions for equipment setup. The only additional specifications that
may be used in setting up the basic model
for test are those set forth in the installation
and operation manual shipped with the unit.
Each unit should be set up for test in
accordance with the manufacturer
installation and operation manuals. Sections
3.1 through 3.3 of this appendix provide
specifications for addressing key information
typically found in the installation and
operation manuals.
4.1. If a manufacturer specifies a range of
superheat, sub-cooling, and/or refrigerant
less than 65,000 Btu/h, the test set-up and the
fixed compressor speeds (i.e., the maximum,
minimum, and any intermediate speeds used
for testing) should be recorded and
maintained as part of the test data underlying
the certified ratings that is required to be
maintained under 10 CFR 429.71.
5. Refrigerant line length corrections for
air-cooled, three-phase, variable refrigerant
flow multi-split air conditioners and heat
pumps with a cooling capacity of less than
65,000 Btu/h. For test setups where it is
physically impossible for the laboratory to
use the required line length listed in Table
3 of the ANSI/AHRI 1230–2010, then the
actual refrigerant line length used by the
laboratory may exceed the required length
and the following cooling capacity correction
factors are applied:
Piping length beyond minimum, X
(ft)
Piping length beyond minimum, Y
(m)
0 > X ≤ 20 ................................................................................
20 > X ≤ 40 ..............................................................................
40 > X ≤ 60 ..............................................................................
60 > X ≤ 80 ..............................................................................
80 > X ≤ 100 ............................................................................
100 > X ≤ 120 ..........................................................................
0 > Y ≤ 6.1 ..............................................................................
6.1 > Y ≤ 12.2 .........................................................................
12.2 > Y ≤ 18.3 .......................................................................
18.3 > Y ≤ 24.4 .......................................................................
24.4 > Y ≤ 30.5 .......................................................................
30.5 > Y ≤ 36.6 .......................................................................
6. Manufacturer involvement in assessment
or enforcement testing for air-cooled, threephase, variable refrigerant flow multi-split air
conditioners and heat pumps with a cooling
capacity of less than 65,000 Btu/h. A
manufacturer’s representative will be
allowed to witness assessment and/or
enforcement testing. The manufacturer’s
representative will be allowed to inspect and
discuss set-up only with a DOE
representative and adjust only the
modulating components during testing in the
presence of a DOE representative that are
necessary to achieve steady-state operation.
Only previously documented specifications
for set-up as specified under sections 3 and
4 of this appendix will be used.
13. Add appendix B1 to subpart F of
part 431 to read as follows:
■
khammond on DSKJM1Z7X2PROD with PROPOSALS2
pressure in its installation and operation
manual for a given basic model, any value(s)
within that range may be used to determine
refrigerant charge or mass of refrigerant,
unless the manufacturer clearly specifies a
rating value in its installation and operation
manual, in which case the specified rating
value shall be used.
4.2. The airflow rate used for testing must
be that set forth in the installation and
operation manuals being shipped to the
commercial customer with the basic model
and clearly identified as that used to generate
the DOE performance ratings. If a rated
airflow value for testing is not clearly
identified, a value of 400 standard cubic feet
per minute (scfm) per ton shall be used.
4.3. For air-cooled, three-phase, variable
refrigerant flow multi-split air conditioners
and heat pumps with a cooling capacity of
Appendix B1 to Subpart F of Part 431—
Uniform Test Method for the
Measurement of Energy Consumption of
Air-Cooled, Three-Phase, Small
Commercial Package Air Conditioning
and Heating Equipment With a Cooling
Capacity of Less Than 65,000 BTU/H
and Air-Cooled, Three-Phase, Variable
Refrigerant Flow Multi-Split Air
Conditioners and Heat Pumps With a
Cooling Capacity of Less Than 65,000
BTU/H
Note: Manufacturers must use the results of
testing under this appendix to determine
compliance with any amended standards for
air-cooled, three-phase, small commercial
package air conditioning and heating
equipment with a cooling capacity of less
than 65,000 Btu/h and air-cooled, threephase, variable refrigerant flow multi-split air
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
conditioners and heat pumps with a cooling
capacity of less than 65,000 Btu/h provided
in § 431.97 that are published after January
1, 2021, and that rely on seasonal energy
efficiency ratio 2 (SEER2) and heating
seasonal performance factor 2 (HSPF2).
Representations related to energy
consumption must be made in accordance
with the appropriate appendix that applies
(i.e., appendices B or B1) when determining
compliance with the relevant standard.
Manufacturers may also use this appendix to
certify compliance with any amended
standards prior to the applicable compliance
date for those standards.
1. Incorporation by Reference
DOE incorporated by reference in § 431.95,
the entire standard for AHRI Standard 210/
240–2023, ‘‘Performance Rating of Unitary
Air-Conditioning & Air-Source Heat Pump
Equipment,’’ approved 2020 (AHRI 210/240–
2023); and ANSI/ASHRAE Standard 37–
2009, (‘‘ANSI/ASHRAE 37–2009’’), ‘‘Methods
of Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat Pump
Equipment,’’ ASHRAE approved June 24,
2009. However, certain enumerated
provisions of AHRI 210/240–2023 and ANSI/
ASHRAE 37–2009, as set forth in paragraphs
(a) and (b) of this section, are inapplicable.
To the extent there is a conflict between the
terms or provisions of a referenced industry
standard and the CFR, the CFR provisions
control.
(a) AHRI 210/240–2023:
(i) Section 6 Rating Requirements—6.1
Standard Ratings—6.1.8 Tested
Combinations or Tested Units is inapplicable
as specified in section 2.1(1) of this
appendix,
(ii) Section 6 Rating Requirements—6.2
Application Ratings is inapplicable as
specified in section 2.1(2) of this appendix,
PO 00000
Frm 00032
Fmt 4701
Sfmt 4702
Cooling capacity
correction
(%)
1
2
3
4
5
6
(iii) Section 6 Rating Requirements—6.4
Ratings is inapplicable as specified in section
2.1(3) of this appendix,
(iv) Section 6 Rating Requirements—6.5
Uncertainty and Variability is inapplicable as
specified in section 2.1(4) of this appendix,
(v) Section 7 Minimum Data Requirements
for Published Ratings is inapplicable as
specified in section 2.1(5) of this appendix,
(vi) Section 8 Operating Requirements is
inapplicable as specified in section 2.1(6) of
this appendix,
(vii) Section 9 Marking and Nameplate
Data is inapplicable as specified in section
2.1(7) of this appendix,
(viii) Section 10 Conformance Conditions
is inapplicable as specified in section 2.1(8)
of this appendix,
(ix) Appendix C Certification of Laboratory
Facilities Used to Determine Performance of
Unitary Air-Conditioning & Air-Source Heat
Pump Equipment—Informative is
inapplicable as specified in section 2.1(9) of
this appendix,
(x) Appendix F ANSI/ASHRAE Standard
116–2010 Clarifications/Exceptions—
Normative—F15.2 and F17 are inapplicable
as specified in section 2.1(10) of this
appendix,
(xi) Appendix G Unit Configuration for
Standard Efficiency Determination—
Normative is inapplicable as specified in
section 2.1(11) of this appendix,
(xi) Appendix H Off-Mode Testing—
Normative is inapplicable as specified in
section 2.1(12) of this appendix,
(xii) Appendix I Verification Testing—
Normative is inapplicable as specified in
section 2.1(13) of this appendix.
(b) ANSI/ASHRAE 37–2009:
(i) Section 1 Purpose is inapplicable as
specified in section 2.2(1) of this appendix,
E:\FR\FM\09DEP2.SGM
09DEP2
Federal Register / Vol. 86, No. 234 / Thursday, December 9, 2021 / Proposed Rules
khammond on DSKJM1Z7X2PROD with PROPOSALS2
(ii) Section 2 Scope is inapplicable as
specified in section 2.2(2) of this appendix,
and
(iii) Section 4 Classification is inapplicable
as specified in section 2.2(3) of this
appendix.
2. General. Determine the seasonal energy
efficiency ratio 2 (SEER2) and heating
seasonal performance factor 2 (HSPF2) (as
applicable) in accordance with AHRI 210/
240–2023, ‘‘Performance Rating of Unitary
Air-Conditioning & Air-Source Heat Pump
Equipment’’ and ANSI/ASHRAE 37–2009
‘‘Methods of Testing for Rating Electronically
Driven Unitary Air-Conditioning and Heat
Pump Equipment’’; however, the following
enumerated provisions of that document are
not applicable. Sections 3 and 4 of this
appendix provide additional instructions for
determining SEER2 and HSPF2. In cases
where there is a conflict, the language of this
appendix takes precedence over AHRI 210/
240–2023. Any subsequent amendment to a
referenced document by the standard-setting
organization will not affect the test procedure
in this appendix, unless and until the test
procedure is amended by DOE. Material is
incorporated as it exists on the date of the
approval, and a notice of any change in the
incorporation will be published in the
Federal Register.
VerDate Sep<11>2014
19:25 Dec 08, 2021
Jkt 256001
2.1. Excepted sections of AHRI 210/240–
2023
(1) Section 6 Rating Requirements—6.1
Standard Ratings—6.1.8 Tested
Combinations or Tested Units,
(2) Section 6 Rating Requirements—6.2
Application Ratings,
(3) Section 6 Rating Requirements—6.4
Ratings,
(4) Section 6 Rating Requirements—6.5
Uncertainty and Variability,
(5) Section 7 Minimum Data Requirements
for Published Ratings,
(6) Section 8 Operating Requirements,
(7) Section 9 Marking and Nameplate Data,
(8) Section 10 Conformance Conditions,
(9) Appendix C Certification of Laboratory
Facilities Used to Determine Performance of
Unitary Air-Conditioning & Air-Source Heat
Pump Equipment—Informative,
(10) Appendix F ANSI/ASHRAE Standard
116–2010 Clarifications/Exceptions—
Normative—F15.2 and F17,
(11) Appendix G Unit Configuration for
Standard Efficiency Determination—
Normative,
(12) Appendix H Off-Mode Testing—
Normative, and
(13) Appendix I Verification Testing—
Normative.
2.2. Excepted sections of ANSI/ASHRAE
37–2009
PO 00000
Frm 00033
Fmt 4701
Sfmt 9990
70347
(1) Section 1 Purpose,
(2) Section 2 Scope,
(3) Section 4 Classification.
3. Energy Measurement Accuracy. The
watt-hour (W·h) measurement system(s) shall
be accurate within ±0.5 percent or 0.5 W·h,
whichever is greater, for both ON and OFF
cycles. If two measurement systems are used,
then the meters shall be switched within 15
seconds of the start of the OFF cycle and
switched within 15 seconds prior to the start
of the ON cycle.
4. Cycle Stability Requirements. Conduct
three complete compressor OFF/ON cycles.
Calculate the degradation coefficient CD for
each complete cycle. If all three CD values are
within 0.02 of the average CD then stability
has been achieved, and the highest CD value
of these three shall be used. If stability has
not been achieved, conduct additional cycles,
up to a maximum of eight cycles total, until
stability has been achieved between three
consecutive cycles. Once stability has been
achieved, use the highest CD value of the
three consecutive cycles that establish
stability. If stability has not been achieved
after eight cycles, use the highest CD from
cycle one through cycle eight, or the default
CD, whichever is lower.
[FR Doc. 2021–24836 Filed 12–8–21; 8:45 am]
BILLING CODE 6450–01–P
E:\FR\FM\09DEP2.SGM
09DEP2
Agencies
[Federal Register Volume 86, Number 234 (Thursday, December 9, 2021)]
[Proposed Rules]
[Pages 70316-70347]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2021-24836]
[[Page 70315]]
Vol. 86
Thursday,
No. 234
December 9, 2021
Part IV
Department of Energy
-----------------------------------------------------------------------
10 CFR Parts 429 and 431
Energy Conservation Program: Test Procedure for Air-Cooled, Three-
Phase, Small Commercial Package Air Conditioning and Heating Equipment
With a Cooling Capacity of Less Than 65,000 Btu/h and Air-Cooled,
Three-Phase, Variable Refrigerant Flow Air Conditioners and Heat Pumps
With a Cooling Capacity of Less Than 65,000 Btu/h; Proposed Rule
Federal Register / Vol. 86 , No. 234 / Thursday, December 9, 2021 /
Proposed Rules
[[Page 70316]]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
10 CFR Parts 429 and 431
[EERE-2017-BT-TP-0031]
RIN 1904-AE06
Energy Conservation Program: Test Procedure for Air-Cooled,
Three-Phase, Small Commercial Package Air Conditioning and Heating
Equipment With a Cooling Capacity of Less Than 65,000 Btu/h and Air-
Cooled, Three-Phase, Variable Refrigerant Flow Air Conditioners and
Heat Pumps With a Cooling Capacity of Less Than 65,000 Btu/h
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notice of proposed rulemaking and request for comment.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (``DOE'' or ``the Department'')
proposes to amend its test procedure for air-cooled, three-phase, small
commercial package air conditioning and heating equipment with a
cooling capacity of less than 65,000 British thermal units (``Btu/h'')
per hour and air-cooled, three-phase, variable refrigerant flow air
conditioners and heat pumps with a cooling capacity of less than 65,000
Btu/h to incorporate by reference the latest version of the relevant
industry test standard. DOE also proposes to adopt the seasonal energy
efficiency ratio 2 (``SEER2'') and heating seasonal performance factor
2 (``HSPF2'') metrics specified by that industry test standard in the
DOE test procedures for the three-phase equipment that is the subject
of this notice of proposed rulemaking (``NOPR''). Additionally, DOE
proposes to amend certain provisions for representations and
enforcement to harmonize with single-phase products.
DATES:
Meeting: DOE will hold a webinar on Monday, January 10, 2022, from
1:00 p.m. to 4:00 p.m. See section V, ``Public Participation,'' for
webinar registration information, participant instructions, and
information about the capabilities available to webinar participants.
Comments: DOE will accept comments, data, and information regarding
this proposal no later than February 7, 2022. See section V, ``Public
Participation,'' for details.
ADDRESSES: Interested persons are encouraged to submit comments using
the Federal eRulemaking Portal at www.regulations.gov. Follow the
instructions for submitting comments. Alternatively, interested persons
may submit comments, identified by docket number EERE-2017-BT- TP-0031,
by any of the following methods:
(1) Federal eRulemaking Portal: www.regulations.gov. Follow the
instructions for submitting comments.
(2) Email: [email protected]. Include the docket
number EERE-2017-BT-TP-0031 or regulatory information number (RIN)
1904-AE06 in the subject line of the message.
No telefacsimilies (faxes) will be accepted. For detailed
instructions on submitting comments and additional information on the
rulemaking process, see section V of this document.
Although DOE has routinely accepted public comment submissions
through a variety of mechanisms, including postal mail and hand
delivery/courier, the Department has found it necessary to make
temporary modifications to the comment submission process in light of
the ongoing COVID-19 pandemic. DOE is currently suspending receipt of
public comments via postal mail and hand delivery/courier, and instead,
the Department is only accepting electronic submissions at this time.
If a commenter finds that this change poses an undue hardship, please
contact Appliance Standards Program staff at (202) 586-1445 to discuss
the need for alternative arrangements. Once the COVID-19 pandemic
health emergency is resolved, DOE anticipates resuming all of its
regular options for public comment submission, including postal mail
and hand delivery/courier.
Docket: The docket, which includes Federal Register notices, public
meeting attendee lists and transcripts (if a public meeting is held),
comments, and other supporting documents/materials, is available for
review at www.regulations.gov. All documents in the docket are listed
in the www.regulations.gov index. However, some documents listed in the
index, such as those containing information that is exempt from public
disclosure, may not be publicly available.
The docket web page can be found at: www.regulations.gov/docket?D=EERE-2017-BT-TP-0031.
The docket web page contains instructions on how to access all
documents, including public comments, in the docket. See section V for
information on how to submit comments through www.regulations.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Catherine Rivest, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, EE-2J,
1000 Independence Avenue SW, Washington, DC 20585-0121. Telephone:
(202) 586-7335. Email: [email protected].
Ms. Kristin Koernig, U.S. Department of Energy, Office of the
General Counsel, GC-33, 1000 Independence Avenue SW, Washington, DC
20585-0121. Telephone: (202) 586-8145.
Email:[email protected].
For further information on how to submit a comment, review other
public comments, and the docket, contact the Appliance and Equipment
Standards Program staff at (202) 287-1445 or by email:
[email protected].
SUPPLEMENTARY INFORMATION: DOE proposes to maintain and update
previously approved incorporations by references for the following
industry standards in part 431:
Air-Conditioning, Heating, and Refrigeration Institute (``AHRI'')
Standard 210/240-2008, (``AHRI 210/240-2008''), ``Performance Rating of
Unitary Air-Conditioning & Air-Source Heat Pump Equipment,'' approved
2011 and updated by addendum 1 in June 2011 and addendum 2 in March
2012.
American National Standards Institute (``ANSI'')/AHRI Standard
1230-2010, ``ANSI/AHRI 1230-2010''),''2010 Standard for Performance
Rating of Variable Refrigerant Flow (VRF) Multi-split Air-Conditioning
and Heat Pump Equipment,'' approved 2010 and updated by addendum 1 in
March 2011.
Copies of AHRI 210/240-2008 and ANSI/AHRI 1230-2010 can be obtained
from the AHRI website by going to https://www.ahrinet.org.
DOE proposes to incorporate by reference the following industry
standard into parts 429 and 431:
AHRI Standard 210/240-2023, (``AHRI 210/240-2023''), ``Performance
Rating of Unitary Air-Conditioning & Air-Source Heat Pump Equipment,''
approved 2020.
Copies of AHRI 210/240-2023 can be obtained from the AHRI website
by going to https://www.ahrinet.org.
DOE proposes to amend the previously approved incorporation by
reference for the following industry standard in part 431:
American National Standards Institute (``ANSI'')/American Society
of Heating, Refrigerating, and Air-Conditioning Engineers (``ASHRAE'')
Standard 37-2009, ``Methods of Testing for Rating Electrically Driven
Unitary Air-Conditioning and Heat Pump Equipment,'' ASHRAE approved
June 24, 2009.
[[Page 70317]]
Copies of ANSI/ASHRAE Standard 37-2009 can be obtained from the
American National Standards Institute, 25 W. 43rd Street, 4th Floor,
New York, NY 10036, (212) 642-4900, or online at: https://webstore.ansi.org/.
See section IV.M of this document for further discussion of these
standards.
Table of Contents
I. Authority and Background
A. Authority
B. Background
II. Synopsis of the Notice of Proposed Rulemaking
III. Discussion
A. Scope of Applicability
B. Metrics
C. Proposed Organization of the Test Procedure
D. Updates to the Federal Test Method for Central Air
Conditioners and Heat Pumps
E. Updates to Industry Standards and Proposed Test Procedures
for Three-Phase Equipment With Cooling Capacity of Less Than 65,000
Btu/h
1. Harmonization With Single-Phase Products
2. AHRI 210/240
3. AHRI 1230
4. ASHRAE 37
F. Certification, Compliance, and Enforcement Requirements
1. Representation Requirements
2. Basic Model Definition
3. Certification Reporting Requirements
4. Product-Specific Enforcement Provisions
G. Test Procedure Costs
H. Compliance Date
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
B. Review Under the Regulatory Flexibility Act
C. Review Under the Paperwork Reduction Act of 1995
D. Review Under the National Environmental Policy Act of 1969
E. Review Under Executive Order 13132
F. Review Under Executive Order 12988
G. Review Under the Unfunded Mandates Reform Act of 1995
H. Review Under the Treasury and General Government
Appropriations Act, 1999
I. Review Under Executive Order 12630
J. Review Under Treasury and General Government Appropriations
Act, 2001
K. Review Under Executive Order 13211
L. Review Under Section 32 of the Federal Energy Administration
Act of 1974
M. Description of Materials Incorporated by Reference
V. Public Participation
A. Participation in the Webinar
B. Procedure for Submitting Prepared General Statements for
Distribution
C. Conduct of the Webinar
D. Submission of Comments
E. Issues on Which DOE Seeks Comment
VI. Approval of the Office of the Secretary
I. Authority and Background
Small, large, and very large commercial package air conditioning
and heating equipment are included in the list of ``covered equipment''
for which DOE is authorized to establish and amend energy conservation
standards and test procedures. (42 U.S.C. 6311(1)(B)-(D)) Air-cooled,
three-phase, small commercial air conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/h (``3-phase ACUACs and ACUHPs
with cooling capacity of less than 65,000 Btu/h'') \1\ and air-cooled,
three-phase, variable refrigerant flow (``VRF'' or ``VRF multi-split
systems'') air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h (``3-phase VRF with cooling capacity of less
than 65,000 Btu/h'') \2\ are two separate categories of small
commercial package air conditioning and heating equipment. DOE's test
procedures and energy conservation standards for 3-phase ACUACs and
ACUHPs with cooling capacity of less than 65,000 Btu/h and for 3-phase
VRF with cooling capacity of less than 65,000 Btu/h are currently
prescribed at title 10 of the Code of Federal Regulations (``CFR'')
part 431. See 10 CFR 431.96 (test procedures) and 10 CFR 431.97 (energy
conservation standards). The following sections discuss DOE's authority
to establish and amend the test procedure for 3-phase ACUACs and ACUHPs
with cooling capacity of less than 65,000 Btu/h and for 3-phase VRF
with cooling capacity of less than 65,000 Btu/h, and relevant
background information regarding DOE's consideration of test procedures
for this equipment.
---------------------------------------------------------------------------
\1\ ACUACs and ACUHPS means air-cooled commercial unitary air
conditioners and heat pumps and is terminology consistent with that
used for this equipment with a cooling capacity of greater than or
equal to 65,000 Btu/h.
\2\ As used in this rulemaking, the term ``3-phase VRF with
cooling capacity of less than 65,000 Btu/h'' refers only to air-
cooled equipment.
---------------------------------------------------------------------------
A. Authority
The Energy Policy and Conservation Act, as amended (``EPCA''),\3\
authorizes DOE to regulate the energy efficiency of a number of
consumer products and certain industrial equipment. (42 U.S.C. 6291-
6317, as codified) Title III, Part C \2\ of EPCA, added by Public Law
95-619, Title IV, section 441(a), established the Energy Conservation
Program for Certain Industrial Equipment, which sets forth a variety of
provisions designed to improve energy efficiency for certain industrial
equipment, including 3-phase ACUACs and ACUHPs with cooling capacity of
less than 65,000 Btu/h, and 3-phase VRF with cooling capacity of less
than 65,000 Btu/h, the subjects of this NOPR. (42 U.S.C. 6311(1)(B))
---------------------------------------------------------------------------
\3\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020).
\2\ For editorial reasons, upon codification in the U.S. Code,
Part C was redesignated Part A-1.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) Testing, (2) labeling, (3) the establishment of Federal
energy conservation standards, and (4) certification and enforcement
procedures. Relevant provisions of EPCA include definitions (42 U.S.C.
6311), test procedures (42 U.S.C. 6314), labeling provisions (42 U.S.C.
6315), energy efficiency standards (42 U.S.C. 6313), and the authority
to require information and reports from manufacturers (42 U.S.C. 6316;
42 U.S.C. 6296).
The Federal testing requirements consist of test procedures that
manufacturers of covered equipment must use as the basis for: (1)
Certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted pursuant to EPCA (42 U.S.C.
6316(b); 42 U.S.C. 6296), and (2) making representations about the
efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE uses
these test procedures to determine whether the equipment complies with
relevant standards promulgated under EPCA.
Federal energy efficiency requirements for covered equipment
established under EPCA generally supersede State laws and regulations
concerning energy conservation testing, labeling, and standards. (42
U.S.C. 6316(a)-(b); 42 U.S.C. 6297) However, DOE may grant waivers of
Federal preemption for particular State laws or regulations, in
accordance with the procedures and other provisions of EPCA. (42 U.S.C.
6316(b)(2)(D))
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE must follow when prescribing or amending test procedures for
covered equipment. EPCA requires that any test procedures prescribed or
amended under this section must be reasonably designed to produce test
results reflecting the energy efficiency, energy use, and estimated
annual operating cost of a given type of covered equipment during a
representative average use cycle and requires that test procedures not
be unduly burdensome to conduct. (42 U.S.C. 6314(a)(2))
As discussed, 3-phase ACUACs and ACUHPs with cooling capacity of
less than 65,000 Btu/h and 3-phase VRF with cooling capacity of less
than 65,000 Btu/h are both categories of small commercial package air
conditioning and heating equipment. EPCA requires that the test
procedures for small commercial package air conditioning and heating
equipment
[[Page 70318]]
shall be those generally accepted industry testing procedures or rating
procedures developed or recognized by AHRI or by ASHRAE, as referenced
in ASHRAE Standard 90.1, ``Energy Standard for Buildings Except Low-
Rise Residential Buildings'' (ASHRAE Standard 90.1). (42 U.S.C.
6314(a)(4)(A)) Further, if that industry test procedure is amended, DOE
must amend its test procedure to be consistent with the amended
industry test procedure, unless DOE determines, by rule published in
the Federal Register and supported by clear and convincing evidence,
that such amended test procedure would not meet the requirements in 42
U.S.C. 6314(a)(2) and (3) related to representative use and test
burden. (42 U.S.C. 6314(a)(4)(B)) In addition, if DOE determines that a
test procedure amendment is warranted, it must publish proposed test
procedures and offer the public an opportunity to present oral and
written comments on them. (42 U.S.C. 6314(b))
EPCA also requires that, at least once every 7 years, DOE shall
evaluate test procedures for each type of covered equipment, including
those addressed in this NOPR, to determine whether amended test
procedures would more accurately or fully comply with the requirement
that the test procedures not be unduly burdensome to conduct and be
reasonably designed to produce test results that reflect energy
efficiency, energy use, and estimated operating costs during a
representative average use cycle. (42 U.S.C. 6314(a)(1)) In addition,
if DOE determines that a test procedure amendment is warranted, DOE
must publish the proposed test procedures in the Federal Register, and
afford interested persons an opportunity of not less than 45 days to
present oral and written data, views, and arguments on the proposed
test procedures. (42 U.S.C. 6314(b)) If DOE determines that test
procedure revisions are not appropriate, DOE must publish its
determination not to amend the test procedures. (42 U.S.C.
6314(a)(1)(A)(ii))
DOE is publishing this NOPR consistent with its obligations under
EPCA.
B. Background
DOE's current test procedures for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h and for 3-phase VRF with
cooling capacity of less than 65,000 Btu/h are codified at 10 CFR
431.96.
The Federal test procedure for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h was last amended on May 16,
2012 to incorporate by reference the ANSI/AHRI Standard 210/240-2008,
``Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump
Equipment,'' approved by ANSI on October 27, 2011 and updated by
addendum 1 in June 2011 and addendum 2 in March 2012 (``ANSI/AHRI 210/
240-2008''). 77 FR 28928 (``May 2012 final rule''). The May 2012 final
rule also established additional testing requirements at 10 CFR
431.96(c) and (e) that provide an optional break-in period for testing
and specifications regarding the use of manufacturer instructions in
set-up, respectively, applicable to measuring seasonal energy
efficiency ratio (``SEER'') and heating seasonal performance factor
(``HSPF'') for this equipment. 77 FR 28928, 28991 (May 16, 2012).
The Federal test procedure for 3-phase VRF with cooling capacity of
less than 65,000 Btu/h was also last amended in the May 2012 final
rule, and incorporated by reference ANSI/AHRI Standard 1230-2010,
``2010 Standard for Performance Rating of Variable Refrigerant Flow
(VRF) Multi-Split Air-Conditioning and Heat Pump Equipment,'' approved
August 2, 2010 and updated by addendum 1 in March 2011 (``AHRI 1230-
2010''). The testing requirements at 10 CFR 431.96(c) and (e) also
apply to VRF multi-split systems. Additionally, the May 2012 final rule
established additional testing requirements at 10 CFR 431.96(d) and (f)
that provide for refrigerant line length corrections for tests
conducted using AHRI 1230-2010, and for manufacturer involvement in
assessment or enforcement testing for VRF multi-split systems,
respectively. 77 FR 28928, 28991 (May 16, 2012).
In 2017, AHRI published an updated version of its standard,
``Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump
Equipment'' (``AHRI 210/240-2017''). That updated testing standard made
a number of changes that are relevant to DOE's current test procedure,
and many of these changes were based on DOE's current test procedure
for single-phase central air conditioners and central air conditioning
heat pumps with a cooling capacity of less than 65,000 Btu/h (i.e., 10
CFR part 430, subpart B, appendix M, ``Uniform Test Method for
Measuring the Energy Consumption of Central Air Conditioners and Heat
Pumps''; ``Appendix M'').\4\
---------------------------------------------------------------------------
\4\ Three-phase equipment models generally are identical
physically to their single-phase, residential counterparts, except
for the electrical systems and components designed for three-phase
power input.
---------------------------------------------------------------------------
Following the publication of AHRI 210/240-2017, on October 2, 2018,
DOE published in the Federal Register a request for information
(``RFI'') seeking comments on whether DOE should align its test
procedure (and certification and enforcement requirements) for 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h with
that for air-cooled, single-phase, central air conditioners and central
air conditioning heat pumps with a cooling capacity of less than 65,000
Btu/h, consistent with the update to AHRI 210/240-2017. 83 FR 49501
(``October 2018 RFI'').
DOE received comments in response to the October 2018 RFI from the
interested parties listed in Table I.I.
Table I.I--Interested Parties Providing Written Comments to the October 2018 RFI
----------------------------------------------------------------------------------------------------------------
Organization(s) Reference in this NOPR Organization type
----------------------------------------------------------------------------------------------------------------
Air-Conditioning Heating and AHRI............................ Trade Association.
Refrigeration Institute.
Pacific Gas and Electric Company CA IOUs......................... Utilities.
(``PG&E''), San Diego Gas, and
Electric (``SDG&E''), and
Southern California Edison
(``SCE'').
Goodman Global, Inc............... Goodman......................... Manufacturer.
Ingersoll Rand.................... Ingersoll Rand.................. Manufacturer.
Lennox International Inc.......... Lennox.......................... Manufacturer.
Natural Resources Defense Council NRDC and ASAP................... Energy Efficiency Advocates.
(``NRDC''), and Appliance
Standards Awareness Project
(``ASAP'').
United Technologies Corporation Carrier......................... Manufacturer.
(submitted by Carrier
Corporation).
----------------------------------------------------------------------------------------------------------------
[[Page 70319]]
Throughout this document, a parenthetical reference at the end of a
comment quotation or paraphrase provides the location of the item in
the public record.\5\
---------------------------------------------------------------------------
\5\ The parenthetical reference provides a reference for
information located in the docket of this rulemaking. (Docket No.
EERE-2017-BT-TP-0031, which is maintained at www.regulations.gov).
The references are arranged as follows: (commenter name, comment
docket ID number, page of that document).
---------------------------------------------------------------------------
In April 2019, AHRI published the ``Performance Rating of Unitary
Air-Conditioning & Air-Source Heat Pump Equipment (with Addendum 1)''
(``AHRI 210/240-2017 with Addendum 1''), which incorporated minor
revisions to definitions, testing requirements, and efficiency
calculations.
On October 23, 2019, ASHRAE released ASHRAE Standard 90.1-2019,
which maintained the reference to AHRI 210/240 as the industry testing
standard for 3-phase ACUACs and ACUHPs with cooling capacity of less
than 65,000 Btu/h, but updated the editions referenced. ASHRAE Standard
90.1-2019 references AHRI 210/240-2017 for the period prior to January
1, 2023. For the period beginning January 1, 2023, ASHRAE Standard
90.1-2019 references AHRI 210/240-2023 (to align with ASHRAE Standard
90.1-2019 minimum efficiency levels for this equipment in terms of
SEER2 and HSPF2 that take effect on January 1, 2023). ASHRAE Standard
90.1-2019 maintained the reference to AHRI 1230 as the industry testing
standard for all VRF multi-split systems, including air-cooled, three-
phase units with a cooling capacity of less than 65,000 Btu/h, with an
update to AHRI 1230-2014 with Addendum 1.\6\
---------------------------------------------------------------------------
\6\ Air-cooled, three-phase, VRF multi-split systems with a
cooling capacity of less than 65,000 Btu/h are not excluded from the
scope of either AHRI 210/240 (2017 and 2023) or AHRI 1230-2014 with
Addendum 1.
---------------------------------------------------------------------------
In May 2020, AHRI published AHRI 210/240-2023. The updates in AHRI
210/240-2017, AHRI 210/240-2017 with Addendum 1, and AHRI 210/240-2023
are discussed in section III.E.2 of this NOPR. DOE has reviewed the
comments from the October 2018 RFI in the context of these updated
industry standards.
In May 2021, AHRI published AHRI 1230-2021, which excludes from its
scope air-cooled, VRF multi-split systems with a cooling capacity of
less than 65,000 Btu/h. Both AHRI 210/240-2017 with Addendum 1 and AHRI
210/240-2023 exclude from their scope only VRF multi-split systems that
have capacities greater than or equal to 65,000 Btu/h. Because AHRI
1230-2021 explicitly excludes VRF multi-split systems with a cooling
capacity of less than 65,000 Btu/h from scope, and the scope exclusion
in AHRI 210/240-2023 applies only to VRF multi-split systems with a
cooling capacity of 65,000 Btu/h or greater, VRF multi-split systems
with a cooling capacity of less than 65,000 Btu/h are included within
the scope of AHRI 210/240-2023.
As such, DOE has tentatively determined that AHRI 210/240-2023 is
now the appropriate industry test standard for 3-phase VRF with cooling
capacity of less than 65,000 Btu/h. Three-phase VRF with cooling
capacity of less than 65,000 Btu/h do not currently exist on the
market, but DOE expects that any such equipment introduced to the
market in the future would likely be identical to air-cooled, single-
phase, VRF multi-split systems (except for the components designed for
three-phase power input). Therefore, DOE has tentatively determined
that it is appropriate to align its proposed test procedure for 3-phase
VRF with cooling capacity of less than 65,000 Btu/h (AHRI 210/240-2023)
with the test procedure for their single-phase counterparts (i.e., 10
CFR part 430, subpart B, appendix M1; (``Appendix M1'')). For these
reasons, DOE is addressing the test procedures for this equipment in
this NOPR.
II. Synopsis of the Notice of Proposed Rulemaking
This NOPR proposes to update the references in the Federal test
procedures to the most recent version of the relevant industry test
procedures as they relate to 3-phase ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h. Specifically, DOE proposes to
update its regulations at 10 CFR 431.96, ``Uniform test method for the
measurement of energy efficiency of commercial air conditioners and
heat pumps,'' as follows: (1) Incorporate by reference AHRI 210/240-
2023 and ANSI/ASHRAE 37-2009 ``Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment''
(``ANSI/ASHRAE 37-2009''); and (2) establish provisions for determining
SEER2 and HSPF2. The current DOE test procedures for all equipment
addressed in this NOPR would be relocated to a new appendix B of
subpart F to 10 CFR part 431 (``Appendix B'') without change, and the
new test procedure adopting AHRI 210/240-2023 would be established in a
new appendix B1 of subpart F to 10 CFR part 431 (``Appendix B1'') for
determining SEER2 and HSPF2. Compliance with appendix B1 would not be
required until such time as compliance is required with amended energy
conservation standards that rely on SEER2 and HSPF2, should DOE adopt
such standards. Compliance with appendix B (which aligns with the
current Federal test procedure) would be required beginning 360 days
following publication of the final rule. Prior to the date 360 days
following publication of the final rule, testing would be required to
be conducted either per appendix B or under 10 CFR 431.96 as it
appeared in the 10 CFR parts 200-499 edition revised as of January 1,
2021.
In addition, DOE proposes to update most of its compliance and
enforcement requirements for 3-phase ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and for 3-phase VRF with cooling
capacity of less than 65,000 Btu/h to be consistent with those for the
consumer product counterparts (i.e., air-cooled, single-phase, central
air conditioners and central air conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h (which include single-phase VRF
multi-split systems)).
DOE's proposed actions are summarized in Table II.2 and addressed
in detail in section III of this document.
Table II.2--Summary of Changes in Proposed Test Procedure Relative to
Current Test Procedure
------------------------------------------------------------------------
Current DOE test procedures Proposed amendment Reason
------------------------------------------------------------------------
Incorporates by reference ANSI/ Incorporates by EPCA requirement
AHRI 210/240-2008 (for reference in a new to harmonize
equipment other than VRF appendix B1 AHRI 210/ with industry
multi-split systems) and ANSI/ 240-2023 and ANSI/ test procedure.
AHRI 1230-2010 for VRF multi- ASHRAE 37-2009.
split systems.
[[Page 70320]]
Applicable representation Amends representation Harmonization
requirements are those requirements at new with single-
specified at 10 CFR 429.43 10 CFR 429.64 and 10 phase consumer
and 10 CFR 429.70 for CFR 429.70--including product
commercial heating, basic model counterparts,
ventilating, and air definition, tested and reduction
conditioning (``HVAC'') combination, of testing
equipment. determination of burden on
represented value, manufacturers.
and alternative
energy determination
method (``AEDM'')
requirements--largely
consistent with
requirements for
single-phase consumer
product counterparts.
Amended representation
requirements allow
the use of an AEDM
that is validated
with testing of an
otherwise identical
single-phase central
air conditioners and
heat pumps for rating
three-phase, less
than 65,000 Btu/h
single package units
and split systems.
------------------------------------------------------------------------
DOE has tentatively determined that the proposed amendments
described in section III of this NOPR regarding the establishment of
appendix B would not alter the measured efficiency of equipment
addressed in this document or require retesting solely as a result of
DOE's adoption of this proposed amendment to the test procedure. DOE
has tentatively determined, however, that the proposed test procedure
amendments in appendix B1 would, if adopted, alter the measured
efficiency of the affected equipment and that such amendments are
consistent with the updated industry test procedure. Further,
compliance with the proposed appendix B1 and the proposed amendments to
the representation requirements in 10 CFR 429.43 and 10 CFR 429.70
would not be required until the compliance date of amended standards in
terms of SEER2 and HSPF2. Additionally, DOE has tentatively determined
that the proposed amendments, if adopted, would not increase the cost
of testing relative to the updated industry test procedure. Discussion
of DOE's proposed actions are addressed in detail in section III of
this NOPR.
III. Discussion
The discussion that follows details the specific changes that DOE
is proposing to make to the current test procedure regulations
affecting 3-phase ACUACs and ACUHPs with cooling capacity of less than
65,000 Btu/h and 3-phase VRF with cooling capacity of less than 65,000
Btu/h.
A. Scope of Applicability
Three-phase ACUACs and ACUHPs with cooling capacity of less than
65,000 Btu/h and 3-phase VRF with cooling capacity of less than 65,000
Btu/h are both categories of small commercial package air conditioning
and heating equipment. Commercial package air-conditioning and heating
equipment may be air-cooled, water-cooled, evaporatively-cooled, or
water source-based (not including ground water source). These equipment
are electrically-operated and are designed as unitary central air
conditioners or central air-conditioning heat pumps for use in
commercial applications. 10 CFR 431.92. As discussed in the following
sections, 3-phase ACUACs and ACUHPs with cooling capacity of less than
65,000 Btu/h are typically nearly identical (and therefore typically
have comparable efficiency) to single-phase central air conditioners
and central air conditioning heat pumps with rated cooling capacities
of less than 65,000 Btu/h, the latter being consumer products also
subject to EPCA and for which DOE has already established energy
conservation standards (10 CFR 430.32(c)) and test procedures (appendix
M and appendix M1). Based on this ``nearly identical'' relationship,
while 3-phase VRF with cooling capacity of less than 65,000 Btu/h do
not currently exist on the market, DOE expects that any such equipment
introduced to the market in the future would likely also be identical
(except for the components designed for three-phase power input) to
their single-phase counterparts, which are a subset of single-phase
central air conditioners and central air conditioning heat pumps, and,
as such, are also rated using appendix M and appendix M1.
Three-phase ACUACs and ACUHPs with cooling capacity of less than
65,000 Btu/h are further disaggregated into four equipment classes:
Single-package air conditioners, single-package heat pumps, split-
system air conditioners, and split-system heat pumps. 10 CFR
431.97(b).\7\ This NOPR proposes to amend the test procedure applicable
to all four equipment classes but without amending its current scope.
Three-phase VRF with cooling capacity of less than 65,000 Btu/h are
further disaggregated into two equipment classes: air conditioners and
heat pumps. 10 CFR 431.97(f). This NOPR proposes to amend the test
procedure applicable to both equipment classes but without amending its
current scope.
---------------------------------------------------------------------------
\7\ The term ``single package unit'' means ``any central air
conditioner or central air-conditioning heat pump in which all the
major assemblies are enclosed in one cabinet.'' The term ``split
system'' means ``any central air conditioner or central air-
conditioning heat pump in which one or more of the major assemblies
are separate from the others.'' 10 CFR 431.92.
---------------------------------------------------------------------------
B. Metrics
As noted, for 3-phase ACUACs and ACUHPs with cooling capacity of
less than 65,000 Btu/h and for 3-phase VRF with cooling capacity of
less than 65,000 Btu/h, the cooling metric and heating metric currently
specified by DOE are the SEER metric and the HSPF metric, respectively.
10 CFR 431.96. SEER is a seasonal efficiency metric that accounts for
electricity consumption in active and standby cooling modes during the
cooling season, while HSPF is a seasonal efficiency metric that
accounts for electricity consumption in active and standby heating
modes for heat pumps during the heating season. These are the same
metrics that currently apply to single-phase central air conditioners
and central air conditioning heat pumps, including single-phase, air-
cooled VRF multi-split systems with a cooling capacity of less than
65,000 Btu/h (see appendix M).
C. Proposed Organization of the Test Procedure
DOE is proposing to relocate and centralize the current test
procedures for 3-phase ACUACs and ACUHPs with cooling capacity of less
than 65,000 Btu/h and 3-phase VRF with cooling capacity of less than
65,000 Btu/h to a new appendix B to subpart F of part 431. As proposed,
appendix B would
[[Page 70321]]
not amend the current test procedures. The test procedures as provided
in the proposed appendix B would continue to reference ANSI/AHRI 210/
240-2008 and ANSI/AHRI 1230-2010 and provide instructions for
determining SEER and HSPF. DOE is proposing to also update the existing
incorporation by reference of ANSI/AHRI 210/240-2008 and ANSI/AHRI
1230-2010 at 10 CFR 431.95 to apply it to appendix B. The proposed
appendix B would also centralize the additional test provisions
currently applicable under 10 CFR 431.96, i.e., 10 CFR 431.96(c)
through (f). As proposed, the three-phase equipment addressed in this
document would be required to be tested according to appendix B until
such time as compliance is required with amended energy conservation
standards that rely on the SEER2 and HSPF2 metrics, should DOE adopt
such standards.
DOE is also proposing to amend the test procedures for 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of less than 65,000 Btu/h by adopting
AHRI 210/240-2023 in a new appendix B1 to subpart F of part 431. As
noted, EPCA requires DOE to amend the test procedure as necessary to be
consistent with the amended industry test procedure unless it
determines, by rule, published in the Federal Register and supported by
clear and convincing evidence, that to do so would not meet the
statutory requirements for test procedures regarding representativeness
and no undue test burden. DOE proposes to adopt the updated version of
AHRI 210/240, i.e., AHRI 210/240-2023, including the SEER2 and HSPF2
metrics. As proposed, the three-phase equipment addressed in this NOPR
would not be required to be tested using the test procedure in proposed
Appendix B1 until such time as compliance is required with amended
energy conservation standards that rely on the SEER2 and HSPF2 metrics,
should DOE adopt such standards.
D. Updates to the Federal Test Method for Central Air Conditioners and
Heat Pumps
On June 8, 2016, DOE published a test procedure final rule amending
appendix M. 81 FR 36992 (``June 2016 final rule'').\8\ DOE further
amended appendix M in a final rule, published on January 5, 2017, to
improve test repeatability, reduce testing burden, and improve the
accuracy of field representativeness of the testing values without
impacting the measured energy consumption. 82 FR 1426 (``January 2017
final rule'').
---------------------------------------------------------------------------
\8\ A correction was issued on August 18, 2016, to fix editorial
errors. 81 FR 55111.
---------------------------------------------------------------------------
The January 2017 final rule also included other changes to improve
test repeatability, reduce testing burden, and improve the accuracy of
field representativeness that would impact the results of the test
procedure. DOE established a separate appendix M1 incorporating these
changes and new metrics to avoid confusion with the metrics under
appendix M. Appendix M1 specifies new efficiency metrics SEER2, energy
efficiency ratio 2 (``EER2''), and HSPF2 that have the same definitions
as their counterpart metrics in appendix M (i.e., SEER, EER, and HSPF)
but reflect the amendments made to the test procedure in Appendix M1,
which change the measured efficiency values compared to Appendix M.
(See 82 FR 1426, 1437 (Jan. 5, 2017) explaining DOE's decision to adopt
the new metrics SEER2, EER2, and HSPF2). Beginning on January 1, 2023,
efficiency representations for single-phase central air conditioners
and central air conditioning heat pumps with rated cooling capacities
of less than 65,000 Btu/h must be based on the test procedure in
appendix M1. 82 FR 1426.
Both appendices M and M1 reference ANSI/AHRI 210/240-2008, sections
6.1.3.2, 6.1.3.4, 6.1.3.5 and figures D1, D2, D4, along with sections
of ANSI/AHRI 1230-2010 (related to VRF multi-split systems), ANSI/
ASHRAE 23.1-2010, ANSI/ASHRAE 37-2009, ANSI/ASHRAE 41.1-2013, ANSI/
ASHRAE 41.2-1987 (RA 1992), ANSI/ASHRAE 41.6-2014, ANSI/ASHRAE 41.9-
2011, ANSI/ASHRAE 116-2010, and ANSI/AMCA 210-2007.
Additionally, both the June 2016 final rule and January 2017 final
rule adopted amendments related to the certification, compliance, and
enforcement of single-phase central air conditioners and central air
conditioning heat pumps with rated cooling capacities of less than
65,000 Btu/h, codified in 10 CFR part 429. See generally, 81 FR 36992,
37049-37055 (June 8, 2016) and 82 FR 1426, 1468-1475 (Jan. 5, 2017).
The amendments included revisions to the basic model definition,
clarifications to definitions, and a variety of revisions related to
the testing requirements for determining represented values,
certification reporting requirements, and product-specific enforcement
provisions. Id.
E. Updates to Industry Standards and Proposed Test Procedures for
Three-Phase Equipment With Cooling Capacity of Less Than 65,000 Btu/h
As noted, the current DOE test procedure at 10 CFR 431.96 for 3-
phase ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h
incorporates by reference ANSI/AHRI Standard 210/240-2008 with Addenda
1 and 2 (``ANSI/AHRI 210/240-2008,'' but omitting section 6.5). ANSI/
AHRI 210/240-2008 includes as appendix C (which is designated as
normative in the industry test standard) \9\ the entirety of the text
of appendix M as amended by a final rule published on October 22, 2007
(72 FR 59906). Appendix M provides the Federal test procedure for
determining the efficiency of single-phase central air conditioners and
central air conditioning heat pumps with rated cooling capacities of
less than 65,000 Btu/h, which are consumer products covered under 10
CFR part 430.
---------------------------------------------------------------------------
\9\ The inclusion of appendix M in a normative appendix means
that appendix M was required to be followed when testing in
accordance with ANSI/AHRI 210/240-2008.
---------------------------------------------------------------------------
The current DOE test procedure at 10 CFR 431.96 for 3-phase VRF
with cooling capacity of less than 65,000 Btu/h incorporates by
reference ANSI/AHRI Standard 1230-2010 with Addendum 1 (``ANSI/AHRI
1230-2010'', omitting sections 5.1.2 and 6.6).
As noted previously in this document, AHRI has recently published
several updated industry standards: AHRI 210/240-2017 (published in
December 2017), AHRI 210/240-2017 with Addendum 1 (published in April
2019), and AHRI 210/240-2023 (published in May 2020). DOE has reviewed
these documents in the development of this NOPR. In addition, AHRI has
recently published AHRI 1230-2021 (published in May 2021).
As discussed in the following sections, DOE is proposing to
incorporate by reference AHRI 210/240-2023 as the test procedure for
the three-phase equipment addressed in this document. As proposed,
manufacturers would not be required to rely on the amended test
procedure incorporating AHRI 210/240-2023 until such time as compliance
is required with amended standards in terms of the new metrics, SEER2
and HSPF2, should DOE adopt such energy conservation standards. This
proposed test procedure update would align with the test procedure and
metrics for central air conditioners and heat pumps specified at
appendix M1. DOE is also proposing to incorporate by reference ANSI/
ASHRAE 37-2009, which is referenced by AHRI 210/240-2023.
1. Harmonization With Single-Phase Products
In the October 2018 RFI, DOE stated that the three-phase equipment
at issue
[[Page 70322]]
is often nearly identical to their single-phase counterparts. 83 FR
49501, 49504 (Oct. 2, 2018). Specifically, three-phase models generally
are manufactured on the same production lines and are physically
identical to their corresponding single-phase central air conditioner
and central air conditioning heat pump models except the former have
three-phase electrical systems and use components, primarily motors and
compressors, that are designed for three-phase power input. Id. Other
key operational components, such as heat exchangers and fans (excluding
fan motors), are typically identical for three-phase and single-phase
designs of a given model family. Id. In addition, most manufacturers'
model numbers for single-phase products and three-phase equipment are
interchangeable, and three-phase and single-phase versions of the same
model have the same energy efficiency ratings. See, e.g., 80 FR 42614,
42622 (July 17, 2015), and 83 FR 49501, 49504 (Oct. 2, 2018).
The October 2018 RFI raised the question of whether DOE should
align its test procedure for 3-phase ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h with the test procedure for single-
phase central air conditioners and central air conditioning heat pumps
with a cooling capacity of less than 65,000 Btu/h. DOE requested
comments and information on the merits of referencing the current
version of appendix M, or some portion thereof, for the three-phase
systems at issue versus the merits of referencing the updated AHRI 210/
240-2017, which reflects the updated appendix M. 83 FR 49501, 49504
(Oct. 2, 2018).
DOE notes that the October 2018 RFI did not discuss 3-phase VRF
with cooling capacity of less than 65,000 Btu/h, as AHRI had not
updated the scope of its industry standards for this equipment at that
time. As previously noted in this document, this equipment does not
currently exist on the market; however, DOE expects that any such
equipment introduced to the market in the future would--for the same
reasons discussed earlier--presumably be nearly identical to its
single-phase counterparts, which are a subset of single-phase central
air conditioners and central air conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h.
In response to the October 2018 RFI, all commenters supported
harmonizing the test procedures for both 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h, and single-phase central
air conditioners and central air conditioning heat pumps with a cooling
capacity of less than 65,000 Btu/h.\10\ (CA IOUs, No. 2 at pp. 1-2;
Ingersoll Rand, No. 3 at p. 2; AHRI, No. 4 at pp. 1-2; NRDC and ASAP,
No. 5 at pp. 1-2; Lennox, No. 6 at pp. 1-2; Carrier, No. 7 at p. 1;
Goodman, No. 8 at pp. 1-3) Specifically, AHRI, Lennox, Carrier, and
Goodman supported harmonizing the two test procedures by referencing
the industry standard. (AHRI, No. 4 at p. 2; Lennox, No. 6 at pp. 1-2;
Carrier, No. 7 at p. 1; Goodman, No. 8 at p. 2) Lennox noted that EPCA
requires that the test procedure for this equipment be those generally
accepted industry test procedures. (Lennox, No. 6 at p. 1) Others,
however, suggested that DOE harmonize the two test procedures by
adopting appendix M. (CA IOUs, No. 2 at p. 2; NRDC and ASAP, No. 5 at
pp. 1-2) CA IOUs suggested that DOE reference DOE's own regulatory
text, and NRDC and ASAP preferred this approach to ensure consistency
and transparency. (CA IOUs, No. 2 at p. 2; NRDC and ASAP, No. 5 at p.
2) Ingersoll Rand agreed that harmonization of the test procedures is
advantageous and reduces burden, but did not specify which test
procedure DOE should reference. (Ingersoll Rand, No. 3 at p. 2)
---------------------------------------------------------------------------
\10\ All comments are available at www.regulations.gov, in
Docket No. EERE-2017-BT-TP-0031.
---------------------------------------------------------------------------
Beginning January 1, 2023, Appendix M1 specifies that single-phase
central air conditioners and central air conditioning heat pumps must
be tested according to appendix M1. The version of AHRI 210/240
available at the time of the October 2018 RFI publication, AHRI 210/
240-2017, does not contain updates to account for the more recent
changes contained in appendix M1. DOE noted in the October 2018 RFI
that AHRI intended to address appendix M1, by revising AHRI 210/240-
2017. In the October 2018 RFI, DOE requested comment on the
appropriateness of testing 3-phase ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h according to appendix M1. 83 FR
49501, 49504-49505 (Oct. 2, 2018).
Carrier, Goodman, and AHRI urged DOE to wait until AHRI finishes
updating AHRI 210/240 to reference the version that would include both
appendix M1 and appendix M. (Carrier, No. 7 at p. 2; Goodman, No. 8 at
pp. 1-2; AHRI, No. 4 at p. 2) The CA IOUs supported several changes
that were made as part of appendix M1, including changes to the coil-
only test, new external duct static pressure ratings, and the heating
load line increase for heat pump HSPF tests. (CA IOUs, No. 2 at p. 2)
The CA IOUs stated that by including these changes that were made to
appendix M1, three-phase equipment should be subject to the same
requirements as single-phase equipment. (Id.) NRDC and ASAP supported
adopting appendix M1 for three-phase equipment and noted that applying
appendix M1 in the future along with revised standards will maximize
consistency and minimize testing burden. (NRDC and ASAP, No. 5 at p. 2)
Lennox agreed with DOE that if DOE adopts the AHRI procedure, it would
not conflict with appendix M or appendix M1 and would be highly
unlikely to impact measured efficiency as compared to appendix M.
(Lennox, No. 6 at p. 2)
DOE is proposing to align the test procedures for 3-phase ACUACs
and ACUHPs with cooling capacity of less than 65,000 Btu/h and for 3-
phase VRF with cooling capacity of less than 65,000 Btu/h with the test
procedure at appendix M1 for central air conditioners, by adopting AHRI
210/240-2023. As discussed in section III.E.2.b of this NOPR, AHRI 210/
240-2023 harmonizes with the updated Federal test method for single-
phase central air conditioners and central air conditioning heat pumps
(i.e., appendix M1).
DOE also considered whether to harmonize the current test
procedures for the three-phase equipment addressed in this document
with appendix M. However, the required 360-day compliance lead-time
period for test procedure final rules for ASHRAE equipment specified in
EPCA (42 U.S.C. 6314(d)(1)) would result in little to no time between
the compliance date of the final rule for this test procedure
rulemaking and January 1, 2023--when appendix M1 is required for
testing central air conditioners and heat pumps (and when appendix M
will no longer be used). Therefore, DOE has tentatively concluded that
there would be little practical benefit to harmonizing the test
procedures for the three phase-equipment addressed in this document
with the current test procedures for central air conditioners and heat
pumps at appendix M. Further, as described in the following sub-
sections, DOE has identified errors in AHRI 210/240-2017 with Addendum
1 that DOE has tentatively determined would need to be corrected in
regulatory text, if DOE adopted AHRI 210/240-2017 with Addendum 1.
In the October 2018 RFI, DOE solicited comment on any other aspect
of its current test procedure for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h. 83 FR 49501, 49505 (Oct. 2,
2018). The CA IOUs and NRDC and ASAP
[[Page 70323]]
recommended that DOE begin developing a dynamic load-based test
procedure for both three-phase and single-phase equipment for the next
rulemaking cycle. (CA IOUs, No. 2 at p. 3; NRDC and ASAP, No. 5 at p.
2) These commenters noted that work on a Canadian Standards Association
Express Document (``CSA EXP07'') has begun the development of a
dynamic, load-based test procedure, and that DOE should start
investigating a dynamic, load-based test, similar to the test procedure
being developed by the CSA Group (CSA EXP07 Public Review Draft/
September 2017). (CA IOUs, No. 2 at p. 3; NRDC and ASAP, No. 5 at p.
2). DOE notes that it is reviewing documents from the CSA EXP07
development process (e.g., the public review draft and the more
recently published ``Express Document'' CSA EXP07:19) and participating
in stakeholder efforts, such as the Next Generation Test Method working
group (convened by the American Council for an Energy-Efficient
Economy), to evaluate load-based, dynamic test methods.\11\
---------------------------------------------------------------------------
\11\ A dynamic load-based test method differs from the steady-
state test method currently used in DOE test procedures for air
conditioning and heat pump equipment. In a steady-state test method,
the indoor room is maintained at a constant temperature throughout
the test. In this type of test, any variable-speed or variable-
position components of air conditioners and heat pumps are set in a
fixed position, which is typically specified by the manufacturer. In
contrast, a dynamic load-based test has the conditioning load
applied to the indoor room using a load profile that approximates
how the load varies for units installed in the field. In this type
of test, an air conditioning system or heat pump is allowed to
automatically determine and vary its control settings in response to
the imposed conditioning loads, rather than relying on manufacturer-
specified settings.
---------------------------------------------------------------------------
2. AHRI 210/240
a. AHRI 210/240-2017 and AHRI 210/240-2017 With Addendum 1
Many of the revisions in AHRI 210/240-2017 are intended to
harmonize the industry test procedure with the updated Federal test
method for single-phase central air conditioners and central air
conditioning heat pumps with rated cooling capacities of less than
65,000 Btu/h (i.e., appendix M). AHRI 210/240-2017 does not contain the
text of appendix M in a normative appendix (as is the case in Appendix
C of ANSI/AHRI 210/240-2008) and instead integrates requirements
consistent with appendix M throughout the standard.\12\ AHRI 210/240-
2017 also includes additional updates beyond integrating the revised
appendix M.\13\
---------------------------------------------------------------------------
\12\ For example, AHRI 210/240-2017 includes an updated table of
required tests (Table 7), as well as provisions related to off-mode
power.
\13\ For example, AHRI 210/240-2017 has stricter requirements
for heat balance and charge weight tolerance than appendix M. AHRI
210/240-2017 also includes a detailed calculation section that is
based on ANSI/ASHRAE 37 and ANSI/ASHRAE 116.
---------------------------------------------------------------------------
AHRI 210/240-2017 with Addendum 1 includes further updates. These
include: Additional and revised definitions (Section 3); new provisions
regarding multi-split systems, oil recovery, and refrigerant line
length correction factors (Section 5); specified tolerances and tests
required for different product types provided in Table 7 and Table 8
(Section 6); specified distinctions for total, net, cooling, and
heating capacity (Sections 7, 11, 12, and Appendix C) along with
multiple calculation updates (Section 11); revised testing requirements
for systems with a cooling expansion device in the outdoor unit
(Appendix D); reduction in the nominal overall resistance (i.e., R-
value) of the thermal insulation for indoor coil inlet and outlet duct
connections and inclusion of provisions for sampling devices and dew-
point hygrometers (Appendix E); and a new appendix that refers to
forthcoming changes to the industry standard to address the test
procedure in appendix M1 (Appendix K).
While DOE understands that AHRI 210/240-2017 and AHRI 210/240-2017
with Addendum 1 were intended to harmonize with the Federal test
procedure for central air conditioners and heat pumps (appendix M), DOE
has identified errors and substantive differences from appendix M in
both industry test standards. Specifically, DOE has identified the
following issues:
In Section 11 (``Calculations'') of AHRI 210/240-2017 with
Addendum 1: (1) Multiple formulas have typographical errors; \14\ (2)
multiple formulas are inapplicable; \15\ and (3) the section does not
include any specification for the calculation of efficiency metrics for
certain equipment subtypes: Units with variable-air-volume fans;
multiple-indoor blowers; and Northern triple-capacity heat pumps (this
issue is also present in AHRI 210/240-2017).
---------------------------------------------------------------------------
\14\ For example, in Equation 11.64 in Section 11.2.1.2 of AHRI
210/240-2017 with Addendum 1, the denominator of the second term
(enclosed in braces) should read ``95-82'' instead of ``95-8''.
\15\ For example, Equation 11.187 in Section 11.2.2.3 of AHRI
210/240-2017 with Addendum 1 is not applicable, given that linear
interpolation is used to determine COP at intermediate compressor
speed for units with a variable-speed compressor.
---------------------------------------------------------------------------
In Section 5 (``Test Requirements''), in Appendix D
(``Secondary Capacity Check Requirements--Normative''), and in Appendix
E (``ANSI/ASHRAE Standard 37 Clarifications/Exceptions'') of AHRI 210/
240-2017 with Addendum 1, there are multiple inconsistencies with
appendix M (many of which are also present in AHRI 210/240-2017), such
as the following: (1) Section 5 references the wrong table for testing
tolerances for cyclic testing (i.e., references ``Table 11'' in Section
5.2.4 Cycle Stability Requirements, rather than Table 3b of ASHRAE
Standard 116); and (2) Section D7.6.4 specifies more burdensome
condition tolerances than appendix M for the ``Closed Duct test'' of
the outdoor air enthalpy method.\16\
---------------------------------------------------------------------------
\16\ Section D7.6.4 of AHRI 210/240-2017 with Addendum 1
specifies condition tolerances for indoor and outdoor entering air
dry-bulb and wet-bulb tolerances (the target temperature for each is
the average value measure during the free air test (``FA'') test).
For each of these temperatures, the tolerance specified in Section
D7.6.4 is half the condition tolerance specified in Table 9 of
appendix M (e.g., for indoor entering dry-bulb temperature, Table 9
of appendix M specifies a condition tolerance of 0.5 [deg]F, while
Section 7.6.4.1 specifies a condition tolerance of 0.25 [deg]F).
---------------------------------------------------------------------------
As noted, EPCA requires that the test procedure for 3-phase ACUACs
and ACUHPs with cooling capacity of less than 65,000 Btu/h be the
generally accepted industry testing procedure developed or recognized
by AHRI or by ASHRAE, as referenced in ASHRAE Standard 90.1. (42 U.S.C.
6314(a)(4)(A)) Further, when the industry test procedure is amended,
DOE must amend its test procedure to be consistent with the amended
industry test procedure, unless DOE determines, by rule published in
the Federal Register and supported by clear and convincing evidence,
that such amended test procedure would not meet the requirements in 42
U.S.C. 6314(a)(2) and (3) related to representative use and test
burden. (42 U.S.C. 6314(a)(4)(B))
DOE tentatively determines that significant deviations in
regulatory text would be needed to correct errors in the referenced
industry test standard (e.g., correcting and adding certain formulas,
correcting test tolerances for cyclic testing) if AHRI 210/240-2017 or
AHRI 210/240-2017 with Addendum 1 were to be adopted in the Federal
test procedure for 3-phase ACUACs and ACUHPs with cooling capacity of
less than 65,000 Btu/h. Additionally, without further deviations in the
regulatory text, testing to AHRI 210/240-2017 or AHRI 210/240-2017 with
Addendum 1 would still not align with appendix M, because, as
discussed, there are discrepancies between the industry test standards
and appendix M.
Further, as discussed, there would be minimal, if any, practical
benefit from
[[Page 70324]]
harmonizing the test procedure for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h with the test procedure for
single-phase products at appendix M, given that the applicability of
appendix M for determining compliance of central air conditioners will
end January 1, 2023, and it is unlikely that a compliance date for a
final rule for this rulemaking, which would be 360 days after final
rule publication if a final rule is issued, would precede January 1,
2023 by any significant amount of time.
For these reasons, DOE has tentatively concluded that adopting a
revised test procedure (i.e., referencing AHRI 210/240-2017 or AHRI
210/240-2017 with Addendum 1, along with the substantive corrections
and deviations that would be required) for 3-phase ACUACs and ACUHPs
with cooling capacity of less than 65,000 Btu/h would be unduly
burdensome to manufacturers. DOE considers the reasoning discussed in
the paragraphs above to constitute clear and convincing evidence that
adopting AHRI 210/240-2017 or AHRI 210/240-2017 with Addendum 1 would
not meet the requirements specified in 42 U.S.C. 6314(a)(2).
As such, DOE proposes to maintain the current test procedure for 3-
phase ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/
h, which incorporates by reference ANSI/AHRI 210/240-2008, until such
time as compliance with the amended test procedure referencing AHRI
210/240-2023 would be required.
Issue 1: DOE seeks comment on its proposal to maintain reference to
ANSI/AHRI 210/240-2008 with Addenda 1 and 2 as the Federal test
procedure for 3-phase ACUACs and ACUHPs with cooling capacity of less
than 65,000 Btu/h, until such time as compliance would be required with
the amended test procedure referencing AHRI 210/240-2023.
b. AHRI 210/240-2023
DOE notes that AHRI 210/240-2023 generally corrects the errors in
AHRI 210/240-2017 with Addendum 1 and harmonizes with the updated
Federal test method for single-phase central air conditioners and
central air conditioning heat pumps with rated cooling capacities of
less than 65,000 Btu/h (i.e., appendix M1, effective January 1, 2023),
which includes single-phase, air-cooled, VRF multi-split systems with a
cooling capacity of less than 65,000 Btu/h. The industry standard
updates the performance metrics to EER2, SEER2 and HSPF2. Significant
changes related to the new efficiency metrics include higher minimum
external static pressure (``ESP'') requirements for conventional
systems (Table 10) and changes in the building heating load line for
HSPF2 (Section 11). Additional changes in AHRI 210/240-2023 to align
with appendix M1 include the addition of: (1) Minimum ESP requirements
in Table 10 for varieties of ducted blower systems specified in
appendix M1 (i.e., ceiling- and wall-mount, mobile home, and low/mid
static); (2) a separate unit configuration of single stage system with
a single variable-speed variable-air-volume blower or multiple indoor
blowers in Table 7; and (3) the optional H4 test (i.e., the full-load
heating test at 5 [deg]F ambient temperature) in Table 7. These changes
apply for testing of both 3-phase ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h.
In addition, AHRI 210/240-2023 reflects and is consistent with
DOE's appendix M1, which will be the required test procedure for
single-phase central air conditioners and central air conditioning heat
pumps with capacities of less than 65,000 Btu/h beginning January 1,
2023. No commenters suggested that the test procedure in appendix M1
would be inappropriate for the testing of three-phase equipment.
As discussed, the updates contained in AHRI 210/240-2023 provide
for measuring energy efficiency using the SEER2 and HSPF2 metrics,
which are the metrics adopted by ASHRAE Standard 90.1-2019 for the 3-
phase ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h
standards beginning January 1, 2023.\17\ In response to this update to
AHRI 210/240, DOE proposes to incorporate AHRI 210/240-2023 as the test
procedure with which representations must be made beginning with the
compliance date of any amended DOE standards for three-phase equipment
relying on SEER2 and HSPF2 as the metrics.\18\
---------------------------------------------------------------------------
\17\ ASHRAE 90.1-2019 did not update the metrics for air-cooled,
three-phase, variable refrigerant flow air conditioners and heat
pumps with a cooling capacity of less than 65,000 Btu/h. Those
metrics remain SEER and HSPF in ASHRAE Standard 90.1.
\18\ The timing and implementation of any amended standards may
be different for air-cooled, three-phase, small commercial package
air conditioning and heating equipment with a cooling capacity of
less than 65,000 Btu/h and for air-cooled, three-phase variable
refrigerant flow air conditioners and heat pumps with a cooling
capacity of less than 65,000 Btu/h, depending on DOE rulemaking
related to energy conservation standards for those separate
categories of equipment.
---------------------------------------------------------------------------
Harmonization of the test procedures would provide for more
comparable information between three-phase equipment and single-phase
products. Commercial customers considering either single-phase or
three-phase equipment would have ratings for both sets of equipment
that are based on identical testing requirements when evaluating
product options. Because AHRI 210/240-2023 aligns with appendix M1, the
proposed incorporation of this industry testing procedure for the
three-phase equipment at issue would produce comparable ratings between
single-phase and three-phase equipment (as discussed in section III.E.1
of this NOPR). Consequently, DOE has tentatively concluded that this
proposed test procedure would not be unduly burdensome to conduct.
Only certain sections of AHRI 210/240-2023 apply to the DOE test
procedures for the three-phase equipment that is the subject of this
NOPR. Therefore, DOE is proposing to reference AHRI 210/240-2023 in the
proposed test procedure at appendix B1 except for the following
sections:
Section 6--Rating Requirements (these provisions are not
related to the method of test and DOE separately addresses these topics
in 10 CFR part 429):
[cir] Sections 6.1.8, 6.4.1, 6.4.2, 6.4.3, 6.4.4 (minimum testing
and certification requirements);
[cir] Sections 6.2 and 6.4.6 (permit a given product to have
multiple ratings of different values);
[cir] Section 6.5 (uncertainty allowances for testing, which are
not relevant to the Federal test procedure);
Sections 7 through 10, Appendix C, and Appendix I (these
are relevant only to AHRI's certification program);
Appendix F: Sections F15.2 and F17 (these pertain to
electrical measurements and cyclic tolerances, respectively; DOE
proposes modifications as discussed in the following paragraphs);
Appendix G (pertains to configuration of the unit under
test, discussed in the following paragraphs);
Appendix H (pertains to Off-Mode testing, which is not
required by DOE for three-phase equipment).
Regarding energy measurement provisions, section 2.8 of appendix M
requires that the watt-hour (i.e., ``W[middot][hairsp]h'', also
referred to as ``integrated power'' or ``energy'') measuring system
give readings that are accurate to within 0.5 percent. In
response to the October 2018 RFI, Carrier recommended that section
2.8.a of appendix M be revised to include a lower limit (i.e.,
``greater of 0.5 percent of reading or 0.5 watts''), stating that,
without a lower limit, compliance
[[Page 70325]]
with this requirement at times of low power (e.g., during an OFF cycle)
can be difficult for single-phase equipment and possibly unrealistic
for three-phase equipment. (Carrier, No. 7 at p. 2) Section F15.2 of
AHRI 210/240-2023 addresses Carrier's concern by adding a lower limit,
stating that the ``watt-hour measurement system shall be accurate
within 0.5 percent or 0.5 W/h, whichever is greater''.
However, Section F15.2 of AHRI 210/240-2023 specifies incorrect units
of measurement and should refer to watt hours (W[middot][hairsp]h)
(consistent with the first words of Section F15.2) rather than to ``W/
h''. Therefore, DOE proposes not to reference Section F15.2, and
instead to adopt similar provisions in section 3 of appendix B1 that
correct the units of measurement to W[middot][hairsp]h.
Regarding cyclic test tolerances, Section F17 of AHRI 210/240-2023
appears to incorrectly reference ASHRAE 37 Table 2b for cyclic test
operating and condition tolerances. ASHRAE 37 Table 2b does not specify
tolerances specific to cyclic testing. Instead, as specified in
footnote 1 to Table 8 of AHRI 210/240-2023, the tolerances in ASHRAE
Standard 116 Table 3b (titled ``Test Tolerances for Cyclic Performance
Tests'') should be used for cyclic testing. Therefore, DOE proposes not
to reference Section F17, and instead to adopt similar provisions in
section 4 of appendix B1 that do not reference ASHRAE 37 test
tolerances.
Regarding Appendix G, currently enforcement testing of 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of less than 65,000 Btu/h falls under
DOE's Commercial HVAC Enforcement Policy,\19\ which outlines how
certain features of this equipment will be treated for compliance
testing. In Appendix G of AHRI 210/240-2023, AHRI included a list of
components that must be present for testing (Section G1.2) and a list
of features that are optional for testing (Section G2), which provides
additional instruction to address certain of these features and
additional details that are beyond the scope of the current Commercial
HVAC Enforcement Policy. Also, there are five features \20\ that are
included in the Commercial HVAC Enforcement Policy for 3-phase ACUACs
and ACUHPs with cooling capacity of less than 65,000 Btu/h that are not
included in Section G2 of AHRI 210/240-2023.
---------------------------------------------------------------------------
\19\ The enforcement policy for commercial HVAC equipment can be
found at www.energy.gov/gc/downloads/commercial-equipment-testing-enforcement-policies.
\20\ These five features are high-static indoor blower or
oversized motor; desuperheaters; outdoor fan with Variable Frequency
Drive (``VFD''); indoor fan with VFD; and compressor with VFD.
---------------------------------------------------------------------------
DOE has reviewed the market for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h in connection with the
specific treatment of components and optional features suggested in
Appendix G of AHRI 210/240-2023. DOE found that certain optional
features listed in Section G2 (as well as certain features that are
included in DOE's current Commercial HVAC Enforcement Policy but not
included in Section G2 of AHRI 210/240-2023) are present in models of
3-phase ACUACs and ACUHPs with cooling capacity of less than 65,000
Btu/h. However, these same features are also present in models of
single-phase central air conditioners and central air conditioning heat
pumps with cooling capacity of less than 65,000 Btu/h. As discussed in
section III.E.1, in response to the October 2018 RFI, all commenters
supported fully harmonizing the test procedures for both 3-phase ACUACs
and ACUHPs with cooling capacity of less than 65,000 Btu/h and single-
phase central air conditioners and central air conditioning heat pumps
with a cooling capacity of less than 65,000 Btu/h, which aligns with
the proposals in this NOPR. DOE's Commercial HVAC Enforcement Policy
does not apply to single-phase products and appendix M and M1 do not
include any special treatment for these optional features within the
test procedure. In addition, DOE has not received any waivers related
to these features and DOE does not have technical justification to
support differential treatment of such features for three-phase
equipment as compared to single-phase products. As such, DOE has
tentatively determined that any of these features present in 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h can
also be tested in accordance with the proposed test procedure and that
to maintain harmonization with single-phase products, it is not
necessary or appropriate to adopt Appendix G of AHRI 210/240-2023 as
part of DOE's test procedure. While there are currently no models on
the market of 3-phase VRF with cooling capacity of less than 65,000
Btu/h, DOE expects that, if there were, the same tentative
determination would apply for the same reasons. Were DOE to adopt the
proposals in this NOPR, DOE would rescind the Commercial HVAC
Enforcement Policy to the extent that it is applicable to 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of less than 65,000 Btu/h. DOE notes
that all models (with or without any specific feature) may be tested by
DOE at any time under DOE's current authorities if such a model is
distributed in commerce in the U.S.
Issue 2: DOE seeks comment on its proposal to incorporate by
reference AHRI 210/240-2023 in the DOE test procedure for 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of less than 65,000 Btu/h. DOE also
seeks comment on its proposal to require compliance with this test
procedure on the compliance date of any amended energy conservation
standards that DOE may decide to adopt later as part of a future
rulemaking.
3. AHRI 1230
In May 2021, AHRI published AHRI 1230-2021, which excludes from its
scope 3-phase VRF with cooling capacity of less than 65,000 Btu/h. As
such, in this NOPR, DOE is considering revisions based on updated
versions of AHRI 210/240 only, as AHRI 1230-2021 by its explicit terms
is not applicable to the equipment considered in this NOPR.
As discussed, DOE is proposing to reference AHRI 210/240-2023 for
testing 3-phase VRF with cooling capacity less than 65,000 Btu/h. As
proposed, the current Federal test procedure for this equipment (which
references ANSI/AHRI 1230-2010), would remain the required test
procedure until DOE decides to adopt amended energy conservation
standards for this equipment.
4. ASHRAE 37
ANSI/ASHRAE Standard 37, which provides a method of test for many
categories of air conditioning and heating equipment, is referenced for
testing by all versions of AHRI Standards 210/240 and 1230. Appendix E
of AHRI 210/240-2023 provides additional instruction and exceptions
regarding the application of the test methods specified in ANSI/ASHRAE
37-2009. ANSI/ASHRAE 37-2009 is referenced in ANSI/AHRI 1230-2010,
which is currently the referenced industry test standard in the DOE
test procedure for VRF multi-split systems. ANSI/ASHRAE 37-2005 is
referenced by ANSI/AHRI 210/240-2008, which is currently the referenced
industry test standard in the DOE test procedure for 3-phase ACUACs and
ACUHPs with cooling capacity of less than 65,000 Btu/h.
Given the use of ANSI/ASHRAE 37-2009 when testing according to AHRI
210/240-2023, DOE is proposing to
[[Page 70326]]
reference ANSI/ASHRAE 37-2009 in its test procedure for 3-phase ACUACs
and ACUHPs with cooling capacity of less than 65,000 Btu/h and 3-phase
VRF with cooling capacity of less than 65,000 Btu/h. Specifically, in
the proposed appendix B1, DOE is proposing to reference the applicable
sections of ANSI/ASHRAE 37-2009--i.e., all sections except sections 1,
2 and 4.\21\
---------------------------------------------------------------------------
\21\ DOE is proposing to exclude reference to Section 1
(``Purpose), Section 2 (``Scope''), and Section 4
(``Classifications'') in ANSI/ASHRAE 37-2009 to avoid any
potentially contradictory requirements with DOE regulations.
---------------------------------------------------------------------------
F. Certification, Compliance, and Enforcement Requirements
In the October 2018 RFI, DOE also requested comment on whether the
general structure and language related to its certification,
compliance, and enforcement requirements for three-phase equipment in
10 CFR part 429 should mirror the structure and language of
certification, compliance, and enforcement requirements for single-
phase products already found in 10 CFR part 429. 83 FR 49501, 49505
(Oct. 2, 2018). DOE noted in the October 2018 RFI that AHRI 210/240-
2017 included many updates to mirror these requirements, which apply to
both single-phase products and three-phase equipment. Id.
CA IOUs, Ingersoll Rand, and NRDC and ASAP supported adopting the
certification, compliance, and enforcement requirements for single-
phase systems and applying them to three-phase systems. (CA IOUs, No. 2
at p. 2; Ingersoll Rand, No. 3 at p. 2; NRDC and ASAP, No. 5 at p. 2)
AHRI stated that single-phase reporting requirements are significantly
more onerous than what has historically been reported, and that the
reporting requirements for both consumer and commercial products should
be simplified. (AHRI, No. 4 at p. 2) Carrier supported harmonizing
three-phase and single-phase requirements in 10 CFR part 429, stating
that while the single-phase reporting requirements are significantly
more onerous than what has historically been reported, aligning the
reporting for the residential and commercial products is the simplest
way to reduce manufacturer burden. (Carrier, No. 7 at p. 2)
After reviewing the comments, and given that AHRI has updated
Standard 210/240 to include many of the requirements found in 10 CFR
429.16, DOE proposes to amend its representation requirements for 3-
phase ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h
and for 3-phase VRF with cooling capacity of less than 65,000 Btu/h by
applying certain requirements currently applicable to single-phase
central air conditioners and central air conditioning heat pumps
(currently specified at 10 CFR 429.16 and 10 CFR 429.70(e)).\22\ DOE is
not proposing to amend its certification reporting requirements for the
three-phase equipment that is the subject of this NOPR.
---------------------------------------------------------------------------
\22\ DOE notes that these single-phase requirements are
consistent with a consensus recommendation made by the Central Air
Conditioners and Heat Pumps Working Group of the Appliance Standards
and Rulemaking Federal Advisory Committee. (See CAC/HP Term Sheet,
Docket No. EERE-2014-BT-STD-0048, No. 0076, Recommendation #7.)
---------------------------------------------------------------------------
DOE is proposing to amend the basic model definition and product-
specific enforcement provisions for the three-phase equipment specified
at 10 CFR 431.92 and 10 CFR 429.134, respectively, to align with the
provisions for single-phase products.
Harmonizing the representation requirements for three-phase
equipment with the representation requirements for single-phase
products, as discussed, would not increase manufacturer burden as
compared to industry practice under the industry certification program.
Further, these proposals would not apply until such time as DOE amends
the energy conservation standards for this equipment to rely on SEER2
and HSPF2. Therefore, these proposals would not impose an undue burden
on manufacturers. DOE's proposals are discussed in detail in the
following sub-sections.
1. Representation Requirements
As discussed, DOE is proposing to amend certain representation
requirements for the three-phase equipment addressed by this NOPR, to
align with their single-phase counterparts. As part of this proposal,
DOE is proposing to relocate its representation and certification
requirements for three-phase equipment. Specifically, DOE is proposing
that the representation and certification requirements for this three-
phase equipment would be included in a new section 10 CFR 429.64 and
excluded from the scope of 10 CFR 429.43. DOE is also proposing to
establish a new section 10 CFR 429.70(i) for alternative energy
determination method (``AEDM'') requirements that would apply to the
three-phase equipment addressed in this NOPR. As proposed,
manufacturers would not be required to comply with the amended
representation requirements, if made final, until such time that
amended standards are established that would require compliance with
amended energy conservation standards that rely on SEER2 and HSPF2 (as
applicable).
In particular, 10 CFR 429.43, which is applicable to commercial
heating, ventilating, and air conditioning equipment, requires
determination of the represented value for each basic model through
either testing or by applying an AEDM, and 10 CFR 429.70(c)(2)(iv)
specifies that each AEDM must be validated by testing at least two
basic models. Under 10 CFR 429.16, which is applicable to central air
conditioners and central air conditioning heat pumps, determination of
represented values is based on each individual model or combination
(rather than for each basic model), and generally requires a minimum
level of testing for each basic model. For all basic models except
outdoor units with no match and multi-split systems, multi-circuit
systems, and multi-head mini-split systems, represented values for
individual models or combinations other than those required to be
tested may be determined by using an AEDM in accordance with 10 CFR
429.70(e), with no additional testing required to validate the AEDM
beyond the minimum testing required by 10 CFR 429.16. For outdoor units
with no match and multi-split systems, multi-circuit systems, and
multi-head mini-split systems, 10 CFR 429.16 contains additional
requirements for determining represented values.
Through its newly proposed provisions in 10 CFR 429.64 and 10 CFR
420.70(i), DOE would mirror the representation requirements in 10 CFR
429.16 and 10 CFR 429.70(e), except for the minimum testing
requirements and certain AEDM validation requirements for each basic
model of single-package unit and single-split systems. As discussed, 10
CFR 429.16 for central air conditioners and central air conditioning
heat pumps generally requires testing for every basic model. For 3-
phase equipment, DOE proposes in 10 CFR 429.64 to generally maintain
the current approach that not all basic models of three-phase, less
than 65,000 Btu/h single-package units and single split-systems must be
tested. The following paragraphs describe in further detail DOE's
proposal that would allow a manufacturer to use an AEDM for rating all
basic models of three-phase, less than 65,000 Btu/h single-package
units and single split-systems in the case that the manufacturer rates
all models with AEDMs validated with testing of otherwise identical
single-phase models (i.e., no testing of 3-phase equipment required),
and would require testing of only two basic models of 3-
[[Page 70327]]
phase equipment in other cases (e.g., manufacturers that do not rate
with an AEDM validated with testing of an otherwise identical single-
phase model).
DOE has initially determined that an AEDM validated pursuant to 10
CFR 429.70(e) would also be appropriate for rating basic models of
three-phase, less than 65,000 Btu/h single-package units and single
split-systems that have otherwise identical single-phase counterparts.
Specifically, DOE understands that the vast majority of three-phase
equipment with a cooling capacity of less than 65,000 Btu/h has an
otherwise identical single-phase consumer product counterpart offered
by the same manufacturer, thus providing comparable performance between
single-phase products and three-phase equipment with a cooling capacity
of less than 65,000 Btu/h. Further, DOE has tentatively concluded that
any slight differences in performance between single-phase and three-
phase models (e.g., minor differences in compressor performance
depending on the electrical phase of the compressor motor) are well
understood and can be accounted for within an AEDM (e.g., slightly
different compressor coefficients used to model performance for single-
phase vs three-phase compressors), rather than requiring testing of
three-phase models. Therefore, DOE has tentatively determined that for
three-phase, less than 65,000 Btu/h single-package units and single
split-systems with otherwise identical single-phase counterparts,
ratings developed using an AEDM validated with the testing of otherwise
identical single-phase central air conditioners and heat pumps would be
no less representative than ratings developed using an AEDM validated
with the testing of three-phase, less than 65,000 Btu/h equipment.
As such, for three-phase, less than 65,000 Btu/h single-package
units and single split-systems, DOE proposes in 10 CFR 429.70(i)(2) to
permit a manufacturer to rely on an AEDM for central air conditioners
and heat pumps that is validated in accordance with 10 CFR 429.70(e)(2)
with testing of otherwise identical single-phase counterparts, without
additional validation testing.\23\ If a manufacturer offers three-phase
models that do not have otherwise identical single-phase counterparts,
or the manufacturer has not validated an AEDM in accordance with 10 CFR
429.70(e)(2) with testing of the otherwise identical single-phase
counterparts, the manufacturer would be required to test a single unit
sample for each of two basic models to validate an AEDM, consistent
with the existing requirements for all capacities of three-phase
equipment. DOE expects that this case would arise only for a small
number of manufacturers who do not produce otherwise identical single-
phase and three-phase equipment, but instead manufacture a line of
commercial three-phase equipment that includes equipment below DOE's
65,000 Btu/h capacity boundary.
---------------------------------------------------------------------------
\23\ While the AEDM would not need additional validation
testing, it would need to reflect the slight difference in
performance between single-phase and three-phase components.
---------------------------------------------------------------------------
In conjunction with this proposal, DOE proposes to specify in the
newly proposed 10 CFR 429.70(i)(3) that ``otherwise identical'' means
differing only in the phase of the electrical system and the phase of
power input for which the motors and compressors are designed.
Issue 3: DOE seeks comment on its proposal to align the
representation requirements for the three-phase equipment addressed by
this NOPR with the requirements specified for single-phase products at
10 CFR 429.16 and 10 CFR 429.70(e),--but with the exception of testing
requirements and certain AEDM validation requirements for single-
package and single-split system models. Specifically, DOE requests
comment on its proposal to permit for three-phase, less than 65,000
Btu/h single-package and single-split system basic models with
otherwise identical single-phase counterparts the use of ratings based
on an AEDM validated using the test results from otherwise identical
central air conditioners and heat pumps, rather than requiring
validation using the test results of three-phase models. DOE also
requests comment on its proposed specification of the term ``otherwise
identical''. Finally, DOE requests comment on whether the proposed AEDM
requirements should include a provision to validate the correlation
between single-phase and three-phase performance as determined using an
AEDM.
As part of the harmonization with single-phase requirements, the
proposal in 10 CFR 429.64 would require that all representations for
outdoor units with no match and for multi-split systems, multi-circuit
systems, and multi-head mini-split systems must be determined through
testing or other specified means, rather than through an AEDM. As
currently specified, 10 CFR 429.16(c)(2)-(3) do not permit AEDMs for
single-phase products with these configurations; as such, there would
not be any extensively validated AEDMs available for products and
equipment with these configurations. DOE is not aware of any three-
phase models on the market with these configurations (i.e., outdoor
unit with no match or multi-split, multi-circuit, and multi-head mini-
split systems); therefore, DOE tentatively concludes that this proposal
would not result in increased testing burden or costs for any
manufacturer. DOE may consider permitting the use of an AEDM for these
three-phase equipment categories if interested parties were to
demonstrate a market for this equipment and provide information on what
requirements for AEDM validation should be specified.
Issue 4: DOE seeks comment on whether there are three-phase, less
than 65,000 Btu/h models of outdoor units with no match or multi-split,
multi-circuit, and multi-head mini-split systems on the market, and, if
so, whether AEDMs should be allowed for their ratings and what
requirements for AEDM validation should be specified.
DOE notes that, as part of the harmonization with single-phase
requirements, the proposal in 10 CFR 429.64 would require every
individual combination of single-split-system AC equipped with a
single-stage or two-stage compressor distributed in commerce to be
rated as a coil-only combination, with additional blower-coil
representations allowed as applicable. As discussed previously in this
section, the three-phase equipment category may include models that are
part of a line of commercial three-phase equipment that includes
equipment below DOE's 65,000 Btu/h capacity boundary (rather than
models that are otherwise identical to single-phase central air
conditioners). Based on review of models certified in the DOE
Compliance Certification Database, DOE expects almost all of these
models to be packaged units, which are not impacted by this proposal.
Issue 5: DOE seeks comment on whether there are models of three-
phase single-split-system air conditioners with single-stage or two-
stage compressors that are not distributed in commerce as a coil-only
combination (i.e., distributed in commerce only as blower-coil
combination(s)).
2. Basic Model Definition
DOE proposes to amend its basic model definition for 3-phase ACUACs
and ACUHPs with cooling capacity of less than 65,000 Btu/h and for 3-
phase VRF with cooling capacity of less than 65,000 Btu/h to align with
that for single-phase central air conditioners and central air
conditioning heat pumps, as this definition forms the basis for the
requirements in 10 CFR 429.16.
[[Page 70328]]
The current definition of basic model for three-phase equipment in 10
CFR 431.92 refers to ``all units manufactured by one manufacturer
within a single equipment class, having the same or comparably
performing compressor(s), heat exchangers, and air moving system(s)
that have a common ``nominal'' cooling capacity.'' See 10 CFR
431.92(2).\24\ The definition of ``basic model'' for single-phase
products in 10 CFR 430.2 provides additional specifications on this
same concept. See 10 CFR 430.2 (defining the term ``basic model'' and
detailing the application of this term to different configurations of
central air conditioners and central air conditioner heat pumps). For
example, for split systems manufactured by outdoor unit manufacturers,
a basic model includes all individual combinations having the same
model of outdoor unit but with percentage variation limits on
compressor, outdoor coil, and outdoor fan characteristics. See id.
---------------------------------------------------------------------------
\24\ The definition applicable to variable refrigerant flow
systems is different in wording but similar in content. See 10 CFR
431.92(5).
---------------------------------------------------------------------------
Issue 6: DOE requests comment on its proposal to align the
definition of basic model for three-phase equipment at 10 CFR 431.96
with that for single-phase products at 10 CFR 430.2.
3. Certification Reporting Requirements
DOE acknowledges that 10 CFR 429.16 currently requires more detail
in filed certification reports than that required by 10 CFR 429.43.
Therefore, DOE proposes to retain the requirements for certification
reports (i.e., the information that must be reported for each
individual model or combination) currently found in 10 CFR 429.43
rather than adopting wholesale the certification report requirements
for single-phase products found in 10 CFR 429.16.
In response to the October 2018 RFI, Carrier commented that the
three-phase requirements should mirror the structure, language, and
certification requirements for single-phase systems to minimize the
manufacturer's burden. (Carrier, No. 7 at p. 2). In general, DOE agrees
with Carrier's comments that further aligning certification reporting
requirements across single-phase products and three-phase equipment
could reduce overall manufacturer burden despite the additional single-
phase requirements. Therefore, should interested parties provide detail
as to which information required as part of the certification reports
required under 10 CFR 429.16(e) would be particularly burdensome to
report and not impact DOE's ability to conduct enforcement testing, DOE
may consider changes to the reporting requirements for both single-
phase products and three-phase equipment in a separate rulemaking.
In addition, DOE may consider minor revisions to the certification
reporting requirements in any energy conservation standards rulemaking
that DOE may conduct for this equipment.
Issue 7: DOE seeks comment on its proposal not to amend
certification reporting requirements for the three-phase equipment
subject to this notice to align with single-phase products at this
time. DOE also requests details on whether any particular certification
reporting requirements in 10 CFR 429.16(e) are particularly problematic
for manufacturers (for both single-phase products and three-phase
equipment) and why.
4. Product-Specific Enforcement Provisions
DOE is proposing to amend its product-specific enforcement
requirements by adding provisions to a new 10 CFR 429.134(s) for the
three-phase equipment addressed in this NOPR that would align with
those already required at 10 CFR 429.134(k) for single-phase products.
These provisions would pertain only to DOE assessment and enforcement
testing and would not impact manufacturer testing. Additionally, these
requirements would apply only to equipment subject to any potential
standards that DOE may set in terms of SEER2 and HSPF2.
Regarding cooling capacity, DOE is proposing that the cooling
capacity of each tested unit would be measured pursuant to the test
procedure and that the mean of the measurement(s) would be used to
determine compliance with the applicable standards.
Regarding cyclic degradation coefficients, which are a measure of
efficiency loss that would occur as a result of the compressor cycling
to meet a low load level in field applications, DOE is proposing to
measure the cooling and/or heating cyclic degradation coefficient,
CDc/CDh, respectively, by
conducting the optional cyclic tests if the manufacturer certifies that
they conducted the optional cyclic tests. If the manufacturer certifies
that it did not conduct the optional cyclic tests, the proposal would
require that the default CDc/
CDh values would be used as the basis for
calculating SEER or HSPF for each unit tested.
G. Test Procedure Costs
EPCA requires that the test procedures for commercial package air
conditioning and heating equipment for small commercial package air
conditioning and heating equipment, which includes 3-phase ACUACs and
ACUHPs with cooling capacity of less than 65,000 Btu/h and 3-phase VRF
with cooling capacity of less than 65,000 Btu/h, be generally accepted
industry testing procedures or rating procedures developed or
recognized by either AHRI or ASHRAE, as referenced in ASHRAE Standard
90.1. (42 U.S.C. 6314(a)(4)(A)) Further, if such an industry test
procedure is amended, DOE must amend its test procedure to be
consistent with the amended industry test procedure, unless DOE
determines, by rule published in the Federal Register and supported by
clear and convincing evidence, that such amended test procedure would
not meet the requirements in 42 U.S.C. 6314(a)(2)-(3) related to
representative use and test burden. (42 U.S.C. 6314(a)(4)(B))
In this NOPR, DOE proposes to amend the existing test procedures
for three-phase, less than 65,000 Btu/h equipment by incorporating by
reference, with some modification, the updated version of the
applicable industry test method, AHRI 210/240-2023, including the
energy efficiency metrics SEER2 and HSPF2. DOE also proposes to amend
certain representation requirements to more closely align with the
representation requirements for single-phase central air conditioners
and heat pumps. Amendments to both the test procedures and
representation requirements in this NOPR are consistent with comments
from interested parties who supported aligning the Federal regulations
for the three-phase equipment addressed in this document with the
regulations of their single-phase consumer product counterparts.
DOE has tentatively determined that these proposed test procedures
would be representative of an average use cycle and would not be unduly
burdensome for manufacturers to conduct. The proposed appendix B,
measuring both SEER and HSPF per ANSI/AHRI 210/240-2008, does not
contain any changes from the current Federal test procedure, and
therefore would not require retesting solely as a result of DOE's
adoption of this proposed amendment. The proposed test procedure in
appendix B1, measuring both SEER2 and HSPF2 per AHRI 210/240-2023,
would not lead to an increase in cost from appendix B testing.
Specifically, DOE estimates that the cost for third-party lab testing
according to the proposed appendix B1 would be $5,500 for air
conditioners and $8,500 for heat
[[Page 70329]]
pumps, consistent with the current test procedures.
As discussed in section III.F.1 of this NOPR, DOE is proposing to
amend the representation requirements for certifying basic models of
three-phase, less than 65,000 Btu/h equipment to harmonize with the
requirements for single-phase products. For models of outdoor units
with no match and multi-split, multi-circuit, and multi-head mini-split
systems, this proposal may increase testing requirements for three-
phase equipment compared to the existing requirements. However, DOE is
not aware of any such models on the market in these categories--
accordingly, DOE does not believe the proposed representation
requirements will lead to an increase in testing cost for any
manufacturer.
As discussed in section III.F.1 of this NOPR, DOE is proposing to
amend the AEDM \25\ requirements for certifying basic models of three-
phase, less than 65,000 Btu/h single-package units and single-split
systems. Because most manufacturers' models of three-phase, less than
65,000 Btu/h equipment are nearly identical to the corresponding
single-phase, consumer products, DOE is proposing to allow the use of
an AEDM validated using testing of otherwise identical single-phase
counterparts for certifying basic models of three-phase, less than
65,000 Btu/h single package units and split systems. For manufacturers
that produce both single-phase consumer products and three-phase, less
than 65,000 Btu/h equipment, this proposal would reduce any burden that
might result from the proposed test procedures in appendix B1 of this
NOPR, because for such manufacturers all certification of three-phase,
less than 65,000 Btu/h equipment could be conducted using AEDMs without
resorting to the testing of three-phase, less than 65,000 Btu/h
equipment.
---------------------------------------------------------------------------
\25\ Manufacturers are not required to perform laboratory
testing on all basic models. In accordance with 10 CFR 429.70,
three-phase, less than 65,000 Btu/h manufacturers may elect to use
AEDMs. An AEDM is a computer modeling or mathematical tool that
predicts the performance of non-tested basic models. These computer
modeling and mathematical tools, when properly developed, can
provide a means to predict the energy usage or efficiency
characteristics of a basic model of a given covered product or
equipment and reduce the burden and cost associated with testing.
---------------------------------------------------------------------------
As discussed previously throughout this NOPR, the proposed test
procedure in appendix B1 would not be mandatory until such time as DOE
decides whether to amend the energy conservation standards based on
SEER2 and HSPF2. Given that most manufacturers of three-phase equipment
that are the subject of this NOPR are AHRI members, and DOE is
referencing the prevailing industry test procedure that was established
for use in AHRI's certification program (which DOE presumes will be
updated to include SEER2 and HSPF2), DOE expects that manufacturers
will already be testing using the test methods in AHRI 210/240-2023 by
January 1, 2023--the effective date for minimum SEER2 and HSPF2 levels
in ASHRAE 90.1-2019 for three-phase equipment, and also the compliance
date for testing according to appendix M1 for single-phase central air
conditioners. Based on this expectation, DOE also has tentatively
determined that the proposed test procedure amendments would not be
expected to increase the testing burden on three-phase, less than
65,000 Btu/h equipment manufacturers. Additionally, DOE has tentatively
determined that the test procedure amendments, if finalized, would not
require manufacturers to redesign any of the covered equipment, would
not require changes to how the equipment is manufactured, and would not
impact the utility of the equipment.
Issue 8: DOE requests comment on its understanding of the impact of
the test procedure proposals in this NOPR, specifically DOE's tentative
determination that the proposed DOE test procedure amendments, if
finalized, would not increase testing burden on manufacturers, compared
to current industry practice as indicated by AHRI 210/240-2023.
H. Compliance Date
EPCA prescribes that, for the equipment at issue, all
representations of energy efficiency and energy use, including those
made on marketing materials and product labels, must be made in
accordance with an amended test procedure, beginning 360 days after
publication of such a test procedure final rule in the Federal
Register. (42 U.S.C. 6314(d)(1))
IV. Procedural Issues and Regulatory Review
A. Review Under Executive Order 12866
The Office of Management and Budget (``OMB'') has determined that
this test procedure proposed rulemaking does not constitute a
``significant regulatory action'' under section 3(f) of Executive Order
12866, Regulatory Planning and Review, 58 FR 51735 (October 4, 1993).
Accordingly, this action was not subject to review under the Executive
order by the Office of Information and Regulatory Affairs (``OIRA'') in
OMB.
B. Review Under the Regulatory Flexibility Act
The Regulatory Flexibility Act (5 U.S.C. 601 et seq.) requires
preparation of an initial regulatory flexibility analysis (``IRFA'')
for any rule that by law must be proposed for public comment, unless
the agency certifies that the rule, if promulgated, will not have a
significant economic impact on a substantial number of small entities.
As required by Executive Order 13272, ``Proper Consideration of Small
Entities in Agency Rulemaking,'' 67 FR 53461 (August 16, 2002), DOE
published procedures and policies on February 19, 2003, to ensure that
the potential impacts of its rules on small entities are properly
considered during the DOE rulemaking process. 68 FR 7990. DOE has made
its procedures and policies available on the Office of the General
Counsel's website: www.energy.gov/gc/office-general-counsel. DOE
reviewed this proposed rule under the provisions of the Regulatory
Flexibility Act and the procedures and policies published on February
19, 2003.
The following sections detail DOE's IRFA for this test procedure
rulemaking.
1. Description of Reasons Why Action Is Being Considered
DOE is proposing to amend the existing DOE test procedures for 3-
phase ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h
and 3-phase VRF with cooling capacity of less than 65,000 Btu/h. DOE
must update the Federal test procedures to be consistent with the
industry update unless there is clear and convincing evidence that the
industry update would not be representative of an average use cycle or
would be unduly burdensome to conduct. (42 U.S.C. 6314(a)(4)(B))
2. Objective of, and Legal Basis for, Rule
EPCA requires that the test procedures for commercial package
heating and cooling equipment, which includes 3-phase ACUACs and ACUHPs
with cooling capacity of less than 65,000 Btu/h and 3-phase VRF with
cooling capacity of less than 65,000 Btu/h, be generally accepted
industry testing procedures or rating procedures developed or
recognized by either AHRI or ASHRAE, as referenced in ASHRAE Standard
90.1. (42 U.S.C. 6314(a)(4)(A)) Further, if such an industry test
procedure is amended, DOE must amend its test procedure to be
consistent with the amended industry test procedure, unless DOE
determines, by rule published in the Federal Register and supported by
clear and
[[Page 70330]]
convincing evidence, that such amended test procedure would not meet
the requirements in 42 U.S.C. 6314(a)(2) and (3) related to
representative use and test burden. (42 U.S.C. 6314(a)(4)(B))
EPCA also requires that, at least once every 7 years, DOE evaluate
test procedures for each type of covered equipment, including 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of less than 65,000 Btu/h, to
determine whether amended test procedures would more accurately or
fully comply with the requirements for the test procedures to not be
unduly burdensome to conduct and be reasonably designed to produce test
results that reflect energy efficiency, energy use, and estimated
operating costs during a representative average use cycle. (42 U.S.C.
614(a)(1)(A))
3. Description and Estimate of Small Entities Regulated
For manufacturers of 3-phase ACUACs and ACUHPs with cooling
capacity of less than 65,000 Btu/h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h, the Small Business Administration
(``SBA'') has set a size threshold, which defines those entities
classified as ``small businesses'' for the purposes of the statute. DOE
used the SBA's small business size standards to determine whether any
small entities would be subject to the requirements of the rule. See 13
CFR part 121. The equipment covered by this proposed rule is classified
under North American Industry Classification System (``NAICS'') code
333415 ,\26\ ``Air-Conditioning and Warm Air Heating Equipment and
Commercial and Industrial Refrigeration Equipment Manufacturing.'' In
13 CFR 121.201, the SBA sets a threshold of 1,250 employees or fewer
for an entity to be considered as a small business for this category.
---------------------------------------------------------------------------
\26\ The size standards are listed by NAICS code and industry
description and are available at: www.sba.gov/document/support--table-size-standards (Last accessed on July 16, 2021).
---------------------------------------------------------------------------
DOE reviewed the test procedures proposed in this NOPR under the
provisions of the Regulatory Flexibility Act and the procedures and
policies published on February 19, 2003. DOE used publicly available
information to identify potential small businesses that manufacture
equipment covered this this rulemaking. DOE identified thirty-seven
manufacturers of equipment covered by this rulemaking. Of the thirty-
seven, thirty manufacturers are original equipment manufacturers
(``OEM''). DOE screened out companies that do not meet the definition
of a ``small business'' or are foreign-owned and operated. DOE
identified eight small, domestic OEMs for consideration. DOE used
subscription-based business information tools to determine headcount
and revenue of the small businesses.
Of those eight small OEMs, four of them are AHRI members and four
are not AHRI members. Of the four non-AHRI-member small OEMs, two
certify their 3-phase, less than 65,000 Btu/h equipment models in the
AHRI Directory of Certified Product Performance (``AHRI
Directory'').\27\ Therefore, DOE identified two small OEMs who are not
AHRI members and do not certify their covered equipment to the AHRI
Directory.
---------------------------------------------------------------------------
\27\ The AHRI Directory of Certified Product Performance is
available at www.ahridirectory.org.
---------------------------------------------------------------------------
4. Description and Estimate of Compliance Requirements
DOE assumed each small business would have different potential
regulatory costs depending whether they are an OEM, they are a member
of AHRI, and/or they currently certify equipment in the AHRI Directory.
DOE understands all AHRI members and all manufacturers currently
certifying in the AHRI Directory (including small businesses) will be
testing their models in accordance with AHRI 210/240-2023, the industry
test procedure DOE is proposing to reference, and using AHRI's
certification program, which DOE presumes will be updated to include
the SEER2 and HSPF2 metrics. The proposed test procedure amendments
would not add any additional testing burden to manufacturers that are
or will be using the AHRI 210/240-2023 test procedure for their models
of 3-phase ACUACs and ACUHPs with cooling capacity of less than 65,000
Btu/h and 3-phase VRF with cooling capacity of less than 65,000 Btu/h.
DOE estimated the range of additional potential testing costs for
the two small businesses that both are not AHRI members and do not
certify their equipment that is the subject of this NOPR to the AHRI
Directory. These small businesses would only incur additional testing
costs if these small businesses would not have otherwise been using the
AHRI 210/240-2023 test procedure to test their models of 3-phase ACUACs
and ACUHPs with cooling capacity of less than 65,000 Btu/h and 3-phase
VRF with cooling capacity of less than 65,000 Btu/h. Of these two small
businesses, the first manufacturer certifies one basic model to the DOE
Compliance Certification Database and the second manufacturer certifies
two basic models to the DOE Compliance Certification Database.\28\
---------------------------------------------------------------------------
\28\ DOE's Compliance Certification Database is available at:
www.regulations.doe.gov/ccms (last accessed June 24, 2021).
---------------------------------------------------------------------------
In this NOPR, DOE is proposing to relocate the current DOE test
procedures to a new appendix B of subpart F of part 431 (``appendix
B'') without change. DOE is also proposing an amended test procedure at
appendix B1 to subpart F of part 431 (``appendix B1''). Specifically,
DOE is proposing in appendix B1 to incorporate by reference the updated
industry test standard AHRI 210/240-2023 for 3-phase ACUACs and ACUHPs
with cooling capacity of less than 65,000 Btu/h (for which the current
Federal test procedure references AHRI 210-240-2008) and for 3-phase
VRF with cooling capacity of less than 65,000 Btu/h (for which the
current Federal test procedure references AHRI 1230-2010). In addition,
DOE is proposing to adopt the efficiency metrics, SEER2 and HSPF2, from
AHRI 210/240-2023 in the test procedure at appendix B1. Finally, DOE is
proposing to harmonize representation and enforcement requirements with
those applicable to single-phase products.
Appendix B does not contain any changes from the current Federal
test procedure, and therefore would have no cost to industry and would
not require retesting solely as a result of DOE's adoption of this
proposed amendment to the test procedure, if made final. The proposed
appendix B1 adopts the most recent industry test procedure, AHRI 210/
240-2023. DOE estimated the cost for third-party lab testing according
to the proposed appendix B1 test procedure to be $8,500 for three-
phase, less than 65,000 Btu/h heating equipment and $5,500 for three-
phase, less than 65,000 Btu/h air conditioning equipment. If
manufacturers conduct physical testing to certify a basic model of the
equipment that is the subject of this NOPR, two units are required to
be tested per basic model. However, manufacturers are not required to
perform laboratory testing on all basic models, as manufacturers may
elect to use AEDMs.\29\ An AEDM is a computer modeling or mathematical
tool that predicts the performance of non-tested basic models. These
computer modeling and mathematical tools, when properly developed, can
provide a means to predict the energy usage or efficiency
characteristics of a basic model of a given covered product or
equipment
[[Page 70331]]
and reduce the burden and cost associated with testing.
---------------------------------------------------------------------------
\29\ In accordance with 10 CFR 429.70.
---------------------------------------------------------------------------
The first of the two analyzed small businesses manufactures one
basic model of three-phase equipment with a cooling capacity less than
65,000 Btu/h--the model is an air conditioner. If this manufacturer
used a third-party lab to test this basic model, DOE estimates this
small business would incur additional testing costs of approximately
$11,000. The annual revenue of the first small business is
approximately $82.5 million. DOE estimates testing costs to be less
than 0.01 percent of annual revenue for this small business.
The second of two analyzed small businesses manufactures two basic
model of three-phase equipment with a cooling capacity of less than
65,000 Btu/h--the models are air conditioners. If this manufacturer
used a third-party lab to test these basic models, DOE estimates this
small business would incur additional testing costs of approximately
$22,000. DOE estimates that annual revenue of this small business to be
approximately $4 million. DOE estimates testing costs to be less than
0.6 percent of annual revenue for this small manufacturer. However, DOE
notes that this second small business also manufactures single-phase
central air conditioners and heat pumps; therefore, this manufacturer
may use an AEDM for certifying their central air conditioner and heat
pump (``CAC/HP'') models. Because the proposed test procedure in
appendix B1 aligns with the test procedure for CACs/HPs at appendix M1
to subpart B of 10 CFR part 430, this manufacturer could avoid testing
costs and, as a lower-cost alternative, use their CAC/HP AEDM to
certify performance for the equipment that is the subject of this
notice and further reduce potential costs.\30\
---------------------------------------------------------------------------
\30\ As discussed in section 111.G.1 of this NOPR, DOE is
proposing to allow the use of a AEDM that is validated with single-
phase CACs/HPs to be used for certifying 3-phase ACUACs and ACUHPs
with cooling capacity less than 65,000 Btu/h.
---------------------------------------------------------------------------
Issue 9: DOE requests comment on the number of small businesses DOE
identified. DOE also seeks comment on the potential cost estimates for
each small business identified, compared to current industry practice,
as indicated in AHRI 210/240-2023.
5. Duplication, Overlap, and Conflict With Other Rules and Regulations
DOE is not aware of any rules or regulations that duplicate,
overlap, or conflict with the proposed rule being considered today.
6. Significant Alternatives to the Rule
DOE proposes to reduce burden on manufacturers, including small
businesses, by allowing AEDMs in lieu of physically testing all basic
models. The use of an AEDM is less costly than physical testing of
models of 3-phase ACUACs and ACUHPs with cooling capacity of less than
65,000 Btu/h and 3-phase VRF with cooling capacity of less than 65,000
Btu/h.
Additionally, DOE considered alternative test methods and
modifications to the AHRI 210/240-2023 test procedure for three-phase,
small commercial package heating and cooling equipment with a cooling
capacity of less than 65,000 Btu/h. However, DOE has tentatively
determined that there are no better alternatives than the existing
industry test procedures, in terms of both meeting the agency's
objectives and reducing burden on manufacturers. Therefore, DOE is
proposing to amend the existing DOE test procedure for this equipment
through incorporation by reference of AHRI 210/240-2023.
In addition, individual manufacturers may petition for a waiver of
the applicable test procedure. (See 10 CFR 431.401) Also, Section 504
of the Department of Energy Organization Act, 42 U.S.C. 7194, provides
authority for the Secretary to adjust a rule issued under EPCA in order
to prevent ``special hardship, inequity, or unfair distribution of
burdens'' that may be imposed on that manufacturer as a result of such
rule. Manufacturers should refer to 10 CFR part 1003 for additional
details.
C. Review Under the Paperwork Reduction Act of 1995
Manufacturers of 3-phase ACUACs and ACUHPs with cooling capacity of
less than 65,000 Btu/h and 3-phase VRF with cooling capacity of less
than 65,000 Btu/h must certify to DOE that their products comply with
any applicable energy conservation standards. To certify compliance,
manufacturers must first obtain test data for their products according
to the DOE test procedures, including any amendments adopted for those
test procedures. DOE has established regulations for the certification
and recordkeeping requirements for all covered consumer products and
commercial equipment, including for 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h. (See generally 10 CFR part 429.)
The collection-of-information requirement for the certification and
recordkeeping is subject to review and approval by OMB under the
Paperwork Reduction Act (``PRA''). This requirement has been approved
by OMB under OMB control number 1910-1400. Public reporting burden for
the certification is estimated to average 35 hours per response,
including the time for reviewing instructions, searching existing data
sources, gathering and maintaining the data needed, and completing and
reviewing the collection of information.
Notwithstanding any other provision of the law, no person is
required to respond to, nor shall any person be subject to a penalty
for failure to comply with, a collection of information subject to the
requirements of the PRA, unless that collection of information displays
a currently valid OMB Control Number.
D. Review Under the National Environmental Policy Act of 1969
DOE is analyzing this proposed regulation in accordance with the
National Environmental Policy Act of 1969 (``NEPA'') and DOE's NEPA
implementing regulations (10 CFR part 1021). DOE's regulations include
a categorical exclusion for rulemakings interpreting or amending an
existing rule or regulation that does not change the environmental
effect of the rule or regulation being amended. 10 CFR part 1021,
subpart D, appendix A5. DOE anticipates that this rulemaking qualifies
for categorical exclusion A5 because it is an interpretive rulemaking
that does not change the environmental effect of the rule and otherwise
meets the requirements for application of a categorical exclusion. See
10 CFR 1021.410. DOE will complete its NEPA review before issuing the
final rule.
E. Review Under Executive Order 13132
Executive Order 13132, ``Federalism,'' 64 FR 43255 (August 10,
1999) imposes certain requirements on agencies formulating and
implementing policies or regulations that preempt State law or that
have federalism implications. The Executive order requires agencies to
examine the constitutional and statutory authority supporting any
action that would limit the policymaking discretion of the States and
to carefully assess the necessity for such actions. The Executive order
also requires agencies to have an accountable process to ensure
meaningful and timely input by State and local officials in the
development of regulatory policies that have federalism implications.
On March 14, 2000, DOE published a statement of policy describing the
intergovernmental consultation process it will follow in the
development of such regulations. 65 FR
[[Page 70332]]
13735. DOE has examined this proposed rule and has determined that it
would not have a substantial direct effect on the States, on the
relationship between the national government and the States, or on the
distribution of power and responsibilities among the various levels of
government. EPCA governs and prescribes Federal preemption of State
regulations as to energy conservation for the products that are the
subject of this proposed rule. States can petition DOE for exemption
from such preemption to the extent, and based on criteria, set forth in
EPCA (42 U.S.C. 6297(d)). No further action is required by Executive
Order 13132.
F. Review Under Executive Order 12988
Regarding the review of existing regulations and the promulgation
of new regulations, section 3(a) of Executive Order 12988, ``Civil
Justice Reform,'' 61 FR 4729 (February 7, 1996), imposes on Federal
agencies the general duty to adhere to the following requirements: (1)
Eliminate drafting errors and ambiguity, (2) write regulations to
minimize litigation, (3) provide a clear legal standard for affected
conduct rather than a general standard, and (4) promote simplification
and burden reduction. Section 3(b) of Executive Order 12988
specifically requires that executive agencies make every reasonable
effort to ensure that the regulation (1) clearly specifies the
preemptive effect, if any, (2) clearly specifies any effect on existing
Federal law or regulation, (3) provides a clear legal standard for
affected conduct while promoting simplification and burden reduction,
(4) specifies the retroactive effect, if any, (5) adequately defines
key terms, and (6) addresses other important issues affecting clarity
and general draftsmanship under any guidelines issued by the Attorney
General. Section 3(c) of Executive Order 12988 requires Executive
agencies to review regulations in light of applicable standards in
sections 3(a) and 3(b) to determine whether they are met, or it is
unreasonable to meet one or more of them. DOE has completed the
required review and determined that, to the extent permitted by law,
the proposed rule meets the relevant standards of Executive Order
12988.
G. Review Under the Unfunded Mandates Reform Act of 1995
Title II of the Unfunded Mandates Reform Act of 1995 (``UMRA'')
requires each Federal agency to assess the effects of Federal
regulatory actions on State, local, and Tribal governments, and the
private sector. Public Law 104-4, sec. 201 (codified at 2 U.S.C. 1531).
For a proposed regulatory action likely to result in a rule that may
cause the expenditure by State, local, and Tribal governments, in the
aggregate, or by the private sector of $100 million or more in any one
year (adjusted annually for inflation), section 202 of UMRA requires a
Federal agency to publish a written statement that estimates the
resulting costs, benefits, and other effects on the national economy.
(2 U.S.C. 1532(a), (b)) The UMRA also requires a Federal agency to
develop an effective process to permit timely input by elected officers
of State, local, and Tribal governments on a proposed ``significant
intergovernmental mandate,'' and requires an agency plan for giving
notice and opportunity for timely input to potentially affected small
governments before establishing any requirements that might
significantly or uniquely affect small governments. On March 18, 1997,
DOE published a statement of policy on its process for
intergovernmental consultation under UMRA. 62 FR 12820; also available
at www.energy.gov/gc/office-general-counsel. DOE examined this proposed
rule according to UMRA and its statement of policy and determined that
the rule contains neither an intergovernmental mandate, nor a mandate
that may result in the expenditure of $100 million or more in any year,
so these requirements do not apply.
H. Review Under the Treasury and General Government Appropriations Act,
1999
Section 654 of the Treasury and General Government Appropriations
Act, 1999 (Pub. L. 105-277) requires Federal agencies to issue a Family
Policymaking Assessment for any rule that may affect family well-being.
This proposed rule would not have any impact on the autonomy or
integrity of the family as an institution. Accordingly, DOE has
concluded that it is not necessary to prepare a Family Policymaking
Assessment.
I. Review Under Executive Order 12630
DOE has determined, under Executive Order 12630, ``Governmental
Actions and Interference with Constitutionally Protected Property
Rights'' 53 FR 8859 (March 18, 1988), that this proposed regulation
would not result in any takings that might require compensation under
the Fifth Amendment to the U.S. Constitution.
J. Review Under Treasury and General Government Appropriations Act,
2001
Section 515 of the Treasury and General Government Appropriations
Act, 2001 (44 U.S.C. 3516 note) provides for agencies to review most
disseminations of information to the public under guidelines
established by each agency pursuant to general guidelines issued by
OMB. OMB's guidelines were published at 67 FR 8452 (February 22, 2002),
and DOE's guidelines were published at 67 FR 62446 (October 7, 2002).
Pursuant to OMB Memorandum M-19-15, Improving Implementation of the
Information Quality Act (April 24, 2019), DOE published updated
guidelines which are available at www.energy.gov/sites/prod/files/2019/12/f70/DOE%20Final%20Updated%20IQA%20Guidelines%20Dec%202019.pdf. DOE
has reviewed this proposed rule under the OMB and DOE guidelines and
has concluded that it is consistent with applicable policies in those
guidelines.
K. Review Under Executive Order 13211
Executive Order 13211, ``Actions Concerning Regulations That
Significantly Affect Energy Supply, Distribution, or Use,'' 66 FR 28355
(May 22, 2001), requires Federal agencies to prepare and submit to OMB,
a Statement of Energy Effects for any proposed significant energy
action. A ``significant energy action'' is defined as any action by an
agency that promulgated or is expected to lead to promulgation of a
final rule, and that (1) is a significant regulatory action under
Executive Order 12866, or any successor order; and (2) is likely to
have a significant adverse effect on the supply, distribution, or use
of energy; or (3) is designated by the Administrator of OIRA as a
significant energy action. For any proposed significant energy action,
the agency must give a detailed statement of any adverse effects on
energy supply, distribution, or use should the proposal be implemented,
and of reasonable alternatives to the action and their expected
benefits on energy supply, distribution, and use.
The proposed regulatory action to amend the test procedures for
measuring the energy efficiency of 3-phase ACUACs and ACUHPs with
cooling capacity of less than 65,000 Btu/h and 3-phase VRF with cooling
capacity of less than 65,000 Btu/h is not a significant regulatory
action under Executive Order 12866. Moreover, it would not have a
significant adverse effect on the supply, distribution, or use of
energy, nor has it been designated as a significant energy action by
the Administrator of OIRA. Therefore, it is not a significant energy
action, and, accordingly, DOE has not prepared a Statement of Energy
Effects.
[[Page 70333]]
L. Review Under Section 32 of the Federal Energy Administration Act of
1974
Under section 301 of the Department of Energy Organization Act
(Pub. L. 95-91; 42 U.S.C. 7101), DOE must comply with section 32 of the
Federal Energy Administration Act of 1974, as amended by the Federal
Energy Administration Authorization Act of 1977. (15 U.S.C. 788;
``FEAA'') Section 32 essentially provides in relevant part that, where
a proposed rule authorizes or requires use of commercial standards, the
notice of proposed rulemaking must inform the public of the use and
background of such standards. In addition, section 32(c) requires DOE
to consult with the Attorney General and the Chairman of the Federal
Trade Commission (``FTC'') concerning the impact of the commercial or
industry standards on competition.
The proposed modifications to the test procedures for 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h and
for 3-phase VRF with cooling capacity of less than 65,000 Btu/h would
reference testing methods contained in certain sections of the
following commercial standards: AHRI 210/240-2023 and ANSI/ASHRAE 37-
2009. DOE has evaluated these standards and is unable to conclude
whether they fully comply with the requirements of section 32(b) of the
FEAA (i.e., whether it was developed in a manner that fully provides
for public participation, comment, and review). DOE will consult with
both the Attorney General and the Chairman of the FTC concerning the
impact of these test procedures on competition, prior to prescribing a
final rule.
M. Description of Materials Incorporated by Reference
In this NOPR, DOE proposes to incorporate by reference the
following test standard:
(1) The test standard published by AHRI, titled ``2023 Standard
for Performance Rating of Unitary Air-Conditioning & Air-Source Heat
Pump Equipment,'' AHRI Standard 210/240-2023. AHRI Standard 210/240-
2023 is an industry-accepted test procedure for measuring the
performance of air conditioning and heating equipment. AHRI Standard
210/240-2023 is available on AHRI's website www.ahrinet.org/search-standards.aspx.
In this NOPR, DOE proposes to amend the incorporation by reference
previously approved for the following test standard:
(2) The test standard published by ASHRAE, titled ``Methods of
Testing for Rating Electrically Driven Unitary Air-Conditioning and
Heat Pump Equipment,'' ANSI/ASHRAE Standard 37-2009. ANSI/ASHRAE
Standard 37-2009 is an industry-accepted test procedure that
provides a method of test for many categories of air conditioning
and heating equipment. ANSI/ASHRAE Standard 37-2009 is available on
ANSI's website at https://webstore.ansi.org/RecordDetail.aspx?sku=ANSI%2FASHRAE+Standard+37-2009.
(3) In this NOPR, DOE proposes to maintain and update the
incorporation by reference previously approved for the following
test standards: The test standard published by AHRI, titled 210/240-
2008, ``Performance Rating of Unitary Air-Conditioning & Air-Source
Heat Pump Equipment,'' approved by ANSI on October 27, 2011 and
updated by addendum 1 in June 2011 and addendum 2 in March 2012.
ANSI/AHRI Standard 210/240-2008 is an industry-accepted test
procedure for measuring the performance of air conditioning and
heating equipment. ANSI/AHRI Standard 210/240-2008 is available on
AHRI's website at www.ahrinet.org/search-standards.aspx.
(4) The test standards published by AHRI titled, ANSI/AHRI
Standard 1230-2010, ``2010 Standard for Performance Rating of
Variable Refrigerant Flow (VRF) Multi-split Air-Conditioning and
Heat Pump Equipment,'' approved August 2, 2010 and updated by
addendum 1 in March 2011. ANSI/AHRI Standard 1230-2010 is an
industry-accepted test procedure for measuring the performance of
air conditioning and heating equipment. ANSI/AHRI Standard 1230-2010
is available on AHRI's website www.ahrinet.org/search-standards.aspx.
V. Public Participation
A. Participation in the Webinar
The time and date of the webinar are listed in the DATES and
ADDRESSES sections at the beginning of this document. If no
participants register for the webinar then it will be cancelled.
Webinar registration information, participant instructions, and
information about the capabilities available to webinar participants
will be published on DOE's website: https://www1.eere.energy.gov/buildings/appliance_standards/standards.aspx?productid=75&action=viewlive Participants are
responsible for ensuring their systems are compatible with the webinar
software.
B. Procedure for Submitting Prepared General Statements for
Distribution
Any person who has an interest in the topics addressed in this
NOPR, or who is representative of a group or class of persons that has
an interest in these issues, may request an opportunity to make an oral
presentation at the webinar. Such persons may submit to
[email protected]. Persons who wish to speak
should include with their request a computer file in WordPerfect,
Microsoft Word, PDF, or text (ASCII) file format that briefly describes
the nature of their interest in this rulemaking and the topics they
wish to discuss. Such persons should also provide a daytime telephone
number where they can be reached.
Persons requesting to speak should briefly describe the nature of
their interest in this rulemaking and provide a telephone number for
contact. DOE requests persons selected to make an oral presentation to
submit an advance copy of their statements at least two weeks before
the webinar. At its discretion, DOE may permit persons who cannot
supply an advance copy of their statement to participate, if those
persons have made advance alternative arrangements with the Building
Technologies Office. As necessary, requests to give an oral
presentation should ask for such alternative arrangements.
C. Conduct of the Webinar
DOE will designate a DOE official to preside at the webinar and may
also use a professional facilitator to aid discussion. The meeting will
not be a judicial or evidentiary-type public hearing, but DOE will
conduct it in accordance with section 336 of EPCA (42 U.S.C. 6306). A
court reporter will be present to record the proceedings and prepare a
transcript. DOE reserves the right to schedule the order of
presentations and to establish the procedures governing the conduct of
the webinar/public meeting. There shall not be discussion of
proprietary information, costs or prices, market share, or other
commercial matters regulated by U.S. anti-trust laws. After the webinar
and until the end of the comment period, interested parties may submit
further comments on the proceedings and any aspect of the rulemaking.
The webinar will be conducted in an informal, conference style. DOE
will allow time for prepared general statements by participants and
encourage all interested parties to share their views on issues
affecting this rulemaking. Each participant will be allowed to make a
general statement (within time limits determined by DOE), before the
discussion of specific topics. DOE will permit, as time permits, other
participants to comment briefly on any general statements.
At the end of all prepared statements on a topic, DOE will permit
participants to clarify their statements briefly. Participants should
be prepared to answer questions by DOE and by other
[[Page 70334]]
participants concerning these issues. DOE representatives may also ask
questions of participants concerning other matters relevant to this
rulemaking. The official conducting the webinar/public meeting will
accept additional comments or questions from those attending, as time
permits. The presiding official will announce any further procedural
rules or modification of the above procedures that may be needed for
the proper conduct of the webinar/public meeting.
A transcript of the webinar will be included in the docket, which
can be viewed as described in the Docket section at the beginning of
this NOPR. In addition, any person may buy a copy of the transcript
from the transcribing reporter.
D. Submission of Comments
DOE will accept comments, data, and information regarding this
proposed rule no later than the date provided in the DATES section at
the beginning of this proposed rule. Interested parties may submit
comments using any of the methods described in the ADDRESSES section at
the beginning of this NOPR.\31\ Submitting comments via
www.regulations.gov. The www.regulations.gov web page will require you
to provide your name and contact information. Your contact information
will be viewable to DOE Building Technologies staff only. Your contact
information will not be publicly viewable except for your first and
last names, organization name (if any), and submitter representative
name (if any). If your comment is not processed properly because of
technical difficulties, DOE will use this information to contact you.
If DOE cannot read your comment due to technical difficulties and
cannot contact you for clarification, DOE may not be able to consider
your comment.
---------------------------------------------------------------------------
\31\ DOE has historically provided a 75-day comment period for
test procedure NOPRs pursuant to the North American Free Trade
Agreement, U.S.-Canada-Mexico (``NAFTA''), Dec. 17, 1992, 32 I.L.M.
289 (1993); the North American Free Trade Agreement Implementation
Act, Public Law 103-182, 107 Stat. 2057 (1993) (codified as amended
at 10 U.S.C.A. 2576) (1993) (``NAFTA Implementation Act''); and
Executive Order 12889, ``Implementation of the North American Free
Trade Agreement,'' 58 FR 69681 (Dec. 30, 1993). However, on July 1,
2020, the Agreement between the United States of America, the United
Mexican States, and the United Canadian States (``USMCA''), Nov. 30,
2018, 134 Stat. 11 (i.e., the successor to NAFTA), went into effect,
and Congress's action in replacing NAFTA through the USMCA
Implementation Act, 19 U.S.C. 4501 et seq. (2020), implies the
repeal of E.O. 12889 and its 75-day comment period requirement for
technical regulations. Thus, the controlling laws are EPCA and the
USMCA Implementation Act. Consistent with EPCA's public comment
period requirements for consumer products, the USMCA only requires a
minimum comment period of 60 days. Consequently, DOE now provides a
60-day public comment period for test procedure NOPRs.
---------------------------------------------------------------------------
However, your contact information will be publicly viewable if you
include it in the comment or in any documents attached to your comment.
Any information that you do not want to be publicly viewable should not
be included in your comment, nor in any document attached to your
comment. Persons viewing comments will see only first and last names,
organization names, correspondence containing comments, and any
documents submitted with the comments.
Do not submit to www.regulations.gov information for which
disclosure is restricted by statute, such as trade secrets and
commercial or financial information (hereinafter referred to as
Confidential Business Information (``CBI'')). Comments submitted
through www.regulations.gov cannot be claimed as CBI. Comments received
through the website will waive any CBI claims for the information
submitted. For information on submitting CBI, see the Confidential
Business Information section.
DOE processes submissions made through www.regulations.gov before
posting. Normally, comments will be posted within a few days of being
submitted. However, if large volumes of comments are being processed
simultaneously, your comment may not be viewable for up to several
weeks. Please keep the comment tracking number that www.regulations.gov
provides after you have successfully uploaded your comment.
Submitting comments via email. Comments and documents submitted via
email also will be posted to www.regulations.gov. If you do not want
your personal contact information to be publicly viewable, do not
include it in your comment or any accompanying documents. Instead,
provide your contact information on a cover letter. Include your first
and last names, email address, telephone number, and optional mailing
address. The cover letter will not be publicly viewable as long as it
does not include any comments.
Include contact information each time you submit comments, data,
documents, and other information to DOE. If you submit via postal mail
or hand delivery/courier, please provide all items on a CD, if
feasible. It is not necessary to submit printed copies. No facsimiles
(faxes) will be accepted.
Comments, data, and other information submitted to DOE
electronically should be provided in PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file format. Provide documents that
are not secured, written in English and free of any defects or viruses.
Documents should not contain special characters or any form of
encryption and, if possible, they should carry the electronic signature
of the author.
Campaign form letters. Please submit campaign form letters by the
originating organization in batches of between 50 to 500 form letters
per PDF or as one form letter with a list of supporters' names compiled
into one or more PDFs. This reduces comment processing and posting
time.
Confidential Business Information. According to 10 CFR 1004.11, any
person submitting information that he or she believes to be
confidential and exempt by law from public disclosure should submit via
email two well-marked copies: One copy of the document marked
confidential including all the information believed to be confidential,
and one copy of the document marked non-confidential with the
information believed to be confidential deleted. DOE will make its own
determination about the confidential status of the information and
treat it according to its determination.
It is DOE's policy that all comments may be included in the public
docket, without change and as received, including any personal
information provided in the comments (except information deemed to be
exempt from public disclosure).
E. Issues on Which DOE Seeks Comment
Although DOE welcomes comments on any aspect of this proposal, DOE
is particularly interested in receiving comments and views of
interested parties concerning the following issues:
Issue 1: DOE seeks comment on its proposal to maintain reference to
ANSI/AHRI 210/240-2008 with Addenda 1 and 2 as the Federal test
procedure for 3-phase ACUACs and ACUHPs with cooling capacity of less
than 65,000 Btu/h, until such time as compliance would be required with
the amended test procedure referencing AHRI 210/240-2023.
Issue 2: DOE seeks comment on its proposal to incorporate by
reference AHRI 210/240-2023 in the DOE test procedure for 3-phase
ACUACs and ACUHPs with cooling capacity of less than 65,000 Btu/h and
3-phase VRF with cooling capacity of less than 65,000 Btu/h. DOE also
seeks comment on its proposal to require compliance with this test
procedure on the compliance date of any amended energy conservation
standards that DOE may
[[Page 70335]]
decide to adopt later as part of a future rulemaking.
Issue 3: DOE seeks comment on its proposal to align the
representation requirements for the three-phase equipment addressed by
this NOPR with the requirements specified for single-phase products at
10 CFR 429.16 and 10 CFR 429.70(e),--but with the exception of testing
requirements and certain AEDM validation requirements for single-
package and single-split system models. Specifically, DOE requests
comment on its proposal to permit for three-phase, less than 65,000
Btu/h single-package and single-split system basic models with
otherwise identical single-phase counterparts the use of ratings based
on an AEDM validated using the test results from otherwise identical
central air conditioners and heat pumps, rather than requiring
validation using the test results of three-phase models. DOE also
requests comment on its proposed specification of the term ``otherwise
identical''. Finally, DOE requests comment on whether the proposed AEDM
requirements should include a provision to validate the correlation
between single-phase and three-phase performance as determined using an
AEDM.
Issue 4: DOE seeks comment on whether there are three-phase, less
than 65,000 Btu/h models of outdoor units with no match or multi-split,
multi-circuit, and multi-head mini-split systems on the market, and, if
so, whether AEDMs should be allowed for their ratings and what
requirements for AEDM validation should be specified.
Issue 5: DOE seeks comment on whether there are models of three-
phase single-split-system air conditioners with single-stage or two-
stage compressors that are not distributed in commerce as a coil-only
combination (i.e., distributed in commerce only as blower-coil
combination(s)).
Issue 6: DOE requests comment on its proposal to align the
definition of basic model for three-phase equipment at 10 CFR 431.96
with that for single-phase products at 10 CFR 430.2.
Issue 7: DOE seeks comment on its proposal not to amend
certification reporting requirements for the three-phase equipment
subject to this notice to align with single-phase products at this
time. DOE also requests details on whether any particular certification
reporting requirements in 10 CFR 429.16(e) are particularly problematic
for manufacturers (for both single-phase products and three-phase
equipment) and why.
Issue 8: DOE requests comment on its understanding of the impact of
the test procedure proposals in this NOPR, specifically DOE's tentative
determination that the proposed DOE test procedure amendments, if
finalized, would not increase testing burden on manufacturers, compared
to current industry practice as indicated by AHRI 210/240-2023.
Issue 9: DOE requests comment on the number of small businesses DOE
identified. DOE also seeks comment on the potential cost estimates for
each small business identified, compared to current industry practice,
as indicated in AHRI 210/240-2023.
VI. Approval of the Office of the Secretary
The Secretary of Energy has approved publication of this notice of
proposed rulemaking and request for comment.
List of Subjects
10 CFR Part 429
Administrative practice and procedure, Confidential business
information, Energy conservation, Household appliances, Imports,
Incorporation by reference, Intergovernmental relations, Reporting and
recordkeeping requirements, Small businesses.
10 CFR Part 431
Administrative practice and procedure, Confidential business
information, Energy conservation test procedures, Incorporation by
reference, and Reporting and recordkeeping requirements.
Signing Authority
This document of the Department of Energy was signed on November 5,
2021, by Kelly Speakes-Backman, Principal Deputy Assistant Secretary
and Acting Assistant Secretary for Energy Efficiency and Renewable
Energy, pursuant to delegated authority from the Secretary of Energy.
That document with the original signature and date is maintained by
DOE. For administrative purposes only, and in compliance with
requirements of the Office of the Federal Register, the undersigned DOE
Federal Register Liaison Officer has been authorized to sign and submit
the document in electronic format for publication, as an official
document of the Department of Energy. This administrative process in no
way alters the legal effect of this document upon publication in the
Federal Register.
Signed in Washington, DC, on November 9, 2021 .
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
For the reasons stated in the preamble, DOE is proposing to amend
parts 429 and 431 of Chapter II of Title 10, Code of Federal
Regulations as set forth below:
PART 429--CERTIFICATION, COMPLIANCE, AND ENFORCEMENT FOR CONSUMER
PRODUCTS AND COMMERCIAL AND INDUSTRIAL EQUIPMENT
0
1. The authority citation for part 429 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
2. Amend Sec. 429.4 by adding paragraph (c)(3) to read as follows.
Sec. 429.4 Materials incorporated by reference.
* * * * *
(c) * * *
(3) AHRI Standard 210/240-2023, (``AHRI 210/240-2023''), 2023
Standard for Performance Rating of Unitary Air-Conditioning & Air-
Source Heat Pump Equipment, approved 2020, IBR approved for Sec. Sec.
429.64 and 429.134.
* * * * *
0
3. Amend Sec. 429.12 by revising paragraph (b)(8) to read as follows:
Sec. 429.12 General requirements applicable to certification
reports.
* * * * *
(b) * * *
(8) The test sample size as follows:
(i) The number of units tested for the basic model, or
(ii) In the case of single-split system or single-package central
air conditioners and central air conditioning heat pumps; air-cooled,
three-phase, small commercial package air conditioning and heating
equipment with a cooling capacity of less than 65,000 Btu/h; air-
cooled, three-phase, variable refrigerant flow multi-split air
conditioners and heat pumps with a cooling capacity of less than 65,000
Btu/h; or multi-split, multi-circuit, or multi-head mini-split systems
other than the ``tested combination'', the number of units tested for
each individual combination or individual model, or (iii) If an AEDM
was used in lieu of testing, enter ``0'' (and in the case of central
air conditioners and central air conditioning heat pumps, this must be
indicated separately for each metric);
* * * * *
0
4. Amend Sec. 429.43 by:
0
a. Revising the section heading;
[[Page 70336]]
0
b. Removing paragraphs (b)(2)(iii), (iv,) (ix) and (x);
0
c. Redesignating paragraphs (b)(2)(v) through (viii), and (xi) through
(xv) as paragraphs (b)(2)(iii) through (vi), and (vii) through (xi),
respectively;
0
d. Removing paragraphs (b)(4)(iii) through (vi); and
0
e. Redesignating paragraphs (b)(4)(vii) through (xiv) as paragraphs
(b)(4)(iii) through (x).
The revisions read as follows:
Sec. 429.43 Commercial heating, ventilating, air conditioning (HVAC)
equipment (excluding air-cooled, three-phase, small commercial package
air conditioning and heating equipment with a cooling capacity of less
than 65,000 British thermal units per hour and air-cooled, three-phase,
variable refrigerant flow multi-split air conditioners and heat pumps
with less than 65,000 British thermal units per hour cooling capacity).
* * * * *
0
5. Add Sec. 429.64 to read as follows:
Sec. 429.64 Air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less than
65,000 British thermal units per hour and air-cooled, three-phase,
variable refrigerant flow multi-split air conditioners and heat pumps
with a cooling capacity of less than 65,000 British thermal units per
hour.
(a) Applicability. (1) For air-cooled, three-phase, small
commercial package air conditioning and heating equipment with a
cooling capacity of less than 65,000 Btu/h and air-cooled, three-phase,
variable refrigerant flow multi-split air conditioners and heat pumps
with a cooling capacity of less than 65,000 Btu/h subject to standards
in terms of seasonal energy efficiency ratio (SEER) and heating
seasonal performance factor (HSPF), representations with respect to the
energy use or efficiency, including compliance certifications, are
subject to the requirements in Sec. 429.43 of this title as it
appeared in the 10 CFR parts 200-499 edition revised as of January 1,
2021.
(2) For air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less than
65,000 Btu/h and air-cooled, three-phase, variable refrigerant flow
multi-split air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h subject to standards in terms of seasonal energy
efficiency ratio 2 (``SEER2'') and heating seasonal performance factor
2 (``HSPF2'') metrics, representations with respect to the energy use
or efficiency, including compliance certifications, are subject to the
requirements in this section. If manufacturers choose to certify
compliance with any standards in terms of SEER2 and HSPF2 prior to the
applicable compliance date for those standards, the requirements of
this section must be followed.
(b) Determination of Represented Value--(1) Required represented
values. Determine the represented values (including SEER2, HSPF2,
cooling capacity, and heating capacity, as applicable) for the
individual models/combinations (or ``tested combinations'') specified
in the table to this paragraph (b)(1).
------------------------------------------------------------------------
Equipment Required represented
Category subcategory values
------------------------------------------------------------------------
Single-Package unit........... Single-Package AC Every individual
(including Space- model distributed in
Constrained). commerce.
Single-Package HP
(including Space-
Constrained).
Outdoor Unit and Indoor Unit Single-Split- Every individual
(Distributed in Commerce by System AC with combination
OUM (Outdoor Unit Single-Stage or distributed in
Manufacturer)). Two-Stage commerce must be
Compressor rated as a coil-only
(including Space- combination. For
Constrained and each model of
Small-Duct, High outdoor unit, this
Velocity Systems must include at
(SDHV)). least one coil-only
value that is
representative of
the least efficient
combination
distributed in
commerce with that
particular model of
outdoor unit.
Additional blower-
coil representations
are allowed for any
applicable
individual
combinations, if
distributed in
commerce.
Single-Split- Every individual
System AC with combination
Other Than distributed in
Single-Stage or commerce, including
Two-Stage all coil-only and
Compressor blower coil
(including Space- combinations.
Constrained and
SDHV).
Single-Split- Every individual
System HP combination
(including Space- distributed in
Constrained and commerce.
SDHV).
Multi-Split, For each model of
Multi-Circuit, outdoor unit, at a
or Multi-Head minimum, a non-
Mini-Split Split ducted ``tested
System--non-SDHV combination.'' For
(including Space- any model of outdoor
Constrained). unit also sold with
models of ducted
indoor units, a
ducted ``tested
combination.'' When
determining
represented values
on or after the
compliance date of
any amended energy
conservation
standards, the
ducted ``tested
combination'' must
comprise the highest
static variety of
ducted indoor unit
distributed in
commerce (i.e.,
conventional, mid-
static, or low-
static). Additional
representations are
allowed, as
described in
paragraph (d)(3) of
this section.
Multi-Split, For each model of
Multi-Circuit, outdoor unit, an
or Multi-Head SDHV ``tested
Mini-Split Split combination.''
System--SDHV. Additional
representations are
allowed, as
described in
paragraph (d)(3) of
this section.
Indoor Unit Only Distributed Single-Split- Every individual
in Commerce by ICM System Air combination
(Independent Coil Conditioner distributed in
Manufacturer). (including Space- commerce.
Constrained and
SDHV).
[[Page 70337]]
Single-Split- For a model of indoor
System Heat Pump unit within each
(including Space- basic model, a SDHV
Constrained and ``tested
SDHV). combination.''
Multi-Split, Additional
Multi-Circuit, representations are
or Multi-Head allowed, as
Mini-Split Split described in section
System--SDHV. (d)(3)(ii) of this
section.
------------------------------------------------------------------------
Outdoor Unit with no Match....................... Every model of
outdoor unit
distributed in
commerce (tested
with a model of coil-
only indoor unit as
specified in
paragraph (c)(2) of
this section).
------------------------------------------------------------------------
(2) Refrigerants. (i) If a model of outdoor unit (used in a single-
split, multi-split, multi-circuit, multi-head mini-split, and/or
outdoor unit with no match system) is distributed in commerce and
approved for use with multiple refrigerants, a manufacturer must
determine all represented values for that model using each refrigerant
that can be used in an individual combination of the basic model
(including outdoor units with no match or ``tested combinations'').
This requirement may apply across the listed categories in the table in
paragraph (b)(1) of this section. A refrigerant is considered approved
for use if it is listed on the nameplate of the outdoor unit. If any of
the refrigerants approved for use is HCFC-22 or has a 95 [deg]F
midpoint saturation absolute pressure that is 18 percent of
the 95 [deg]F saturation absolute pressure for HCFC-22, or if there are
no refrigerants designated as approved for use, a manufacturer must
determine represented values (including SEER2, HSPF2, cooling capacity,
and heating capacity, as applicable) for, at a minimum, an outdoor unit
with no match. If a model of outdoor unit is not charged with a
specified refrigerant from the point of manufacture or if the unit is
shipped requiring the addition of more than two pounds of refrigerant
to meet the charge required for testing per section 5.1.8 of AHRI 210/
240-2023 (incorporated by reference, see Sec. 429.4) (unless either
(a) the factory charge is equal to or greater than 70% of the outdoor
unit internal volume multiplied by the liquid density of refrigerant at
95 [deg]F or (b) an A2L refrigerant is approved for use and listed in
the certification report), a manufacturer must determine represented
values (including SEER2, HSPF2, cooling capacity, and heating capacity,
as applicable) for, at a minimum, an outdoor unit with no match.
(ii) If a model is approved for use with multiple refrigerants, a
manufacturer may make multiple separate representations for the
performance of that model (all within the same individual combination
or outdoor unit with no match) using the multiple approved
refrigerants. In the alternative, manufacturers may certify the model
(all within the same individual combination or outdoor unit with no
match) with a single representation, provided that the represented
value is no more efficient than its performance using the least-
efficient refrigerant. A single representation made for multiple
refrigerants may not include equipment in multiple categories or
equipment subcategories listed in the table in paragraph (b)(1) of this
section.
(3) Limitations for represented values of individual combinations.
The following paragraph explains the limitations for represented values
of individual combinations (or ``tested combinations'').
(i) Multiple product classes. Models of outdoor units that are
rated and distributed in individual combinations that span multiple
product classes must be tested, rated, and certified pursuant to
paragraph (b) of this section as compliant with the applicable standard
for each product class.
(ii) Reserved.
(4) Requirements. All represented values under paragraph (b) of
this section must be based on testing in accordance with the
requirements in paragraph (c) of this section or the application of an
AEDM or other methodology as allowed in paragraph (d) of this section.
(c) Units tested--(1) General. The general requirements of Sec.
429.11 apply to air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less than
65,000 Btu/h, and air-cooled, three-phase, variable refrigerant flow
multi-split air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h; and
(2) Sampling plans and represented values. For individual models
(for single-package systems) or individual combinations (for split-
systems, including ``tested combinations'' for multi-split, multi-
circuit, and multi-head mini-split systems) with represented values
determined through testing, each individual model/combination (or
``tested combination'') must have a sample of sufficient size tested in
accordance with the applicable provisions of this subpart. For heat
pumps (other than heating-only heat pumps), all units of the sample
population must be tested in both the cooling and heating modes and the
results used for determining all representations. The represented
values for any individual model/combination must be assigned such that:
(i) Off-Mode. Any represented value of power consumption or other
measure of energy consumption for which consumers would favor lower
values must be greater than or equal to the higher of:
(A) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TP09DE21.001
and, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(B) The upper 90 percent confidence limit (UCL) of the true mean
divided by 1.05, where:
[GRAPHIC] [TIFF OMITTED] TP09DE21.002
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.90 is the t statistic for a 90
percent one-tailed confidence interval with n-1 degrees of freedom
(from appendix A of this subpart). Round represented values of off-mode
power consumption to the nearest watt.
(ii) SEER2 and HSPF2. Any represented value of the energy
efficiency or other measure of energy consumption for which consumers
would favor higher values shall be less than or equal to the lower of:
[[Page 70338]]
(A) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TP09DE21.003
and, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(B) The lower 90 percent confidence limit (LCL) of the true mean
divided by 0.95, where:
[GRAPHIC] [TIFF OMITTED] TP09DE21.004
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.90 is the t statistic for a 90
percent one-tailed confidence interval with n-1 degrees of freedom
(from appendix A of this subpart). Round represented values of SEER2
and HSPF2 to the nearest 0.05.
(iii) Cooling Capacity and Heating Capacity. The represented values
of cooling capacity and heating capacity must each be a self-declared
value that is:
(A) Less than or equal to the lower of:
(1) The mean of the sample, where:
[GRAPHIC] [TIFF OMITTED] TP09DE21.005
and, x is the sample mean; n is the number of samples; and
xi is the ith sample; or,
(2) The lower 90 percent confidence limit (LCL) of the true mean
divided by 0.95, where:
[GRAPHIC] [TIFF OMITTED] TP09DE21.006
And x is the sample mean; s is the sample standard deviation; n is
the number of samples; and t0.90 is the t statistic for a 90
percent one-tailed confidence interval with n-1 degrees of freedom
(from appendix D of this part).
(B) Rounded according to:
(1) The nearest 100 Btu/h if cooling capacity or heating capacity
is less than 20,000 Btu/h,
(2) The nearest 200 Btu/h if cooling capacity or heating capacity
is greater than or equal to 20,000 Btu/h but less than 38,000 Btu/h,
and
(3) The nearest 500 Btu/h if cooling capacity or heating capacity
is greater than or equal to 38,000 Btu/h and less than 65,000 Btu/h.
(d) Determination of represented values--(1) All basic models
except outdoor units with no match and multi-split systems, multi-
circuit systems, and multi-head mini-split systems.
(i) For every individual model/combination within a basic model,
either--
(A) A sample of sufficient size, comprised of production units or
representing production units, must be tested as complete systems with
the resulting represented values for the individual model/combination
obtained in accordance with paragraphs (c)(1) and (2) of this section;
or
(B) The represented values of the measures of energy efficiency or
energy consumption through the application of an AEDM in accordance
with paragraph (e) of this section and Sec. 429.70.
(2) Outdoor units with no match. All models of outdoor units with
no match within a basic model must be tested with a model of coil-only
indoor unit meeting the requirements of section 5.1.6.2 of AHRI 210/
240-2023. Models of outdoor units with no match may not be rated with
an AEDM, other than to determine the represented values for models
using approved refrigerants other than the one used in testing.
(3) For multi-split systems, multi-circuit systems, and multi-head
mini-split systems. The following applies:
(i) For each non-SDHV basic model, at a minimum, a manufacturer
must test the model of outdoor unit with a ``tested combination''
composed entirely of non-ducted indoor units. For any models of outdoor
units also sold with models of ducted indoor units, a manufacturer must
test a second ``tested combination'' composed entirely of ducted indoor
units (in addition to the non-ducted combination). The ducted ``tested
combination'' must comprise the highest static variety of ducted indoor
unit distributed in commerce (i.e., conventional, mid-static, or low-
static).
(ii) If a manufacturer chooses to make representations of a variety
of a basic model (i.e., conventional, low static, or mid-static) other
than a variety for which a representation is required under paragraph
(b)(1) of this section the manufacturer must conduct testing of a
tested combination according to the requirements in paragraphs (c)(1)
and (2) of this section.
(iii) For basic models that include mixed combinations of indoor
units (i.e., combinations that are comprised of any two of the
following varieties--non-ducted, low-static, mid-static, and
conventional ducted indoor units), the represented value for the mixed
combination is the mean of the represented values for the individual
component combinations as determined in accordance with paragraphs
(c)(1) and (2) and paragraphs (d)(3)(i) and (ii) of this section.
(iv) For each SDHV basic model distributed in commerce by an OUM,
the OUM must, at a minimum, test the model of outdoor unit with a
``tested combination'' composed entirely of SDHV indoor units. For each
SDHV basic model distributed in commerce by an ICM, the ICM must test
the model of indoor unit with a ``tested combination'' composed
entirely of SDHV indoor units, where the outdoor unit is the least
efficient model of outdoor unit with which the SDHV indoor unit will be
paired. The least efficient model of outdoor unit is the model of
outdoor unit in the lowest SEER2 combination as certified by the
outdoor unit manufacturer. If there are multiple outdoor unit models
with the same lowest SEER2 represented value, the indoor coil
manufacturer may select one for testing purposes.
(v) For basic models that include SDHV and an indoor unit of
another variety (i.e., non-ducted, low-static, mid-static, and
conventional ducted), the represented value for the mixed SDHV/other
combination is the mean of the represented values for the SDHV and
other tested combination as determined in accordance with paragraphs
(c)(1) through (2) and paragraphs (d)(3)(i) through (ii) of this
section.
(vi) All other individual combinations of models of indoor units
for the same model of outdoor unit for which the manufacturer chooses
to make representations must be rated as separate basic models, and the
provisions of paragraphs (c)(1) through (2) and (d)(3)(i) through (v)
of this section apply.
(e) Alternative efficiency determination methods. In lieu of
testing, represented values of efficiency or consumption may be
determined through the application of an AEDM pursuant to the
requirements of Sec. 429.70(i) and the provisions of this section.
(1) Power or energy consumption. Any represented value of the
average off mode power consumption or other measure of energy
consumption of an individual model/combination for which consumers
would favor lower values must be greater than or equal to the output of
the AEDM but no greater than the standard.
(2) Energy efficiency. Any represented value of the SEER2, HSPF2,
or other measure of energy efficiency of an individual model/
combination for which consumers would favor higher values must be less
than or equal to the output of the AEDM but no less than the standard.
(3) Cooling capacity. The represented value of cooling capacity of
an individual model/combination must be no greater than the cooling
capacity output simulated by the AEDM.
[[Page 70339]]
(4) Heating capacity. The represented value of heating capacity of
an individual model/combination must be no greater than the heating
capacity output simulated by the AEDM.
(f) Certification reports. This paragraph specifies the information
that must be included in a certification report.
(1) The requirements of Sec. 429.12; and
(2) Pursuant to Sec. 429.12(b)(13), for each individual model (for
single-package systems) or individual combination (for split-systems,
including outdoor units with no match and ``tested combinations'' for
multi-split, multi-circuit, and multi-head mini-split systems), a
certification report must include the following public equipment-
specific information:
(i) Commercial package air conditioning equipment that is air-
cooled with a cooling capacity of less than 65,000 Btu/h (3-Phase): The
seasonal energy efficiency ratio (SEER in British thermal units per
Watt-hour (Btu/Wh), and the rated cooling capacity in British thermal
units per hour (Btu/h).
(ii) Commercial package heating equipment that is air-cooled with a
cooling capacity of less than 65,000 Btu/h (3-Phase): The seasonal
energy efficiency ratio (SEER in British thermal units per Watt-hour
(Btu/Wh)), the heating seasonal performance factor (HSPF in British
thermal units per Watt-hour (Btu/Wh)), and the rated cooling capacity
in British thermal units per hour (Btu/h).
(iii) Variable refrigerant flow multi-split air conditioners that
are air-cooled with rated cooling capacity of less than 65,000 Btu/h
(3-Phase): The seasonal energy efficiency ratio (SEER in British
thermal units per Watt-hour (Btu/Wh)) and rated cooling capacity in
British thermal units per hour (Btu/h).
(iv) Variable refrigerant flow multi-split heat pumps that are air-
cooled with rated cooling capacity of less than 65,000 Btu/h (3-Phase):
The seasonal energy efficiency ratio (SEER in British thermal units per
Watt-hour (Btu/Wh)), the heating seasonal performance factor (HSPF in
British thermal units per Watt-hour (Btu/Wh)), and rated cooling
capacity in British thermal units per hour (Btu/h).
(3) Pursuant to Sec. 429.12(b)(13), for each individual model/
combination (including outdoor units with no match and ``tested
combinations''), a certification report must include supplemental
information submitted in PDF format. The equipment-specific,
supplemental information must include any additional testing and
testing set up instructions (e.g., charging instructions) for the basic
model; identification of all special features that were included in
rating the basic model; and all other information (e.g., operational
codes or component settings) necessary to operate the basic model under
the required conditions specified by the relevant test procedure. A
manufacturer may also include with a certification report other
supplementary items in PDF format (e.g., manuals) for DOE consideration
in performing testing under subpart C of this part. The equipment-
specific, supplemental information must include at least the following:
(i) Air cooled commercial package air conditioning equipment with a
cooling capacity of less than 65,000 Btu/h (3-phase): The nominal
cooling capacity in British thermal units per hour (Btu/h); rated
airflow in standard cubic feet per minute (SCFM) for each fan coil;
rated static pressure in inches of water; refrigeration charging
instructions (e.g., refrigerant charge, superheat and/or subcooling
temperatures); frequency or control set points for variable speed
components (e.g., compressors, VFDs); required dip switch/control
settings for step or variable components; a statement whether the model
will operate at test conditions without manufacturer programming; any
additional testing instructions, if applicable; if a variety of motors/
drive kits are offered for sale as options in the basic model to
account for varying installation requirements, the model number and
specifications of the motor (to include efficiency, horsepower, open/
closed, and number of poles) and the drive kit, including settings,
associated with that specific motor that were used to determine the
certified rating; and which, if any, special features were included in
rating the basic model.
(ii) Commercial package heating equipment that is air-cooled with a
cooling capacity of less than 65,000 Btu/h (3-phase): The nominal
cooling capacity in British thermal units per hour (Btu/h); rated
heating capacity in British thermal units per hour (Btu/h); rated
airflow in standard cubic feet per minute (SCFM) for each fan coil;
rated static pressure in inches of water; refrigeration charging
instructions (e.g., refrigerant charge, superheat and/or subcooling
temperatures); frequency or control set points for variable speed
components (e.g., compressors, VFDs); required dip switch/control
settings for step or variable components; a statement whether the model
will operate at test conditions without manufacturer programming; any
additional testing instructions, if applicable; if a variety of motors/
drive kits are offered for sale as options in the basic model to
account for varying installation requirements, the model number and
specifications of the motor (to include efficiency, horsepower, open/
closed, and number of poles) and the drive kit, including settings,
associated with that specific motor that were used to determine the
certified rating; and which, if any, special features were included in
rating the basic model.
(iii) Variable refrigerant flow multi-split air conditioners that
are air-cooled with a cooling capacity of less than 65,000 Btu/h (3-
Phase): The nominal cooling capacity in British thermal units per hour
(Btu/h); outdoor unit(s) and indoor units identified in the tested
combination; components needed for heat recovery, if applicable; rated
airflow in standard cubic feet per minute (SCFM) for each indoor unit;
rated static pressure in inches of water; compressor frequency set
points; required dip switch/control settings for step or variable
components; a statement whether the model will operate at test
conditions without manufacturer programming; any additional testing
instructions, if applicable; if a variety of motors/drive kits are
offered for sale as options in the basic model to account for varying
installation requirements, the model number and specifications of the
motor (to include efficiency, horsepower, open/closed, and number of
poles) and the drive kit, including settings, associated with that
specific motor that were used to determine the certified rating; and
which, if any, special features were included in rating the basic
model. Additionally, upon DOE request, the manufacturer must provide a
layout of the system set-up for testing including charging instructions
consistent with the installation manual.
(iv) Variable refrigerant flow multi-split heat pumps that are air-
cooled with rated cooling capacity of less than 65,000 Btu/h (3-Phase):
The nominal cooling capacity in British thermal units per hour (Btu/h);
rated heating capacity in British thermal units per hour (Btu/h);
outdoor unit(s) and indoor units identified in the tested combination;
components needed for heat recovery, if applicable; rated airflow in
standard cubic feet per minute (SCFM) for each indoor unit; rated
static pressure in inches of water; compressor frequency set points;
required dip switch/control settings for step or variable components; a
statement whether the model will operate at test conditions without
manufacturer programming; any additional testing instructions, if
[[Page 70340]]
applicable; if a variety of motors/drive kits are offered for sale as
options in the basic model to account for varying installation
requirements, the model number and specifications of the motor (to
include efficiency, horsepower, open/closed, and number of poles) and
the drive kit, including settings, associated with that specific motor
that were used to determine the certified rating; and which, if any,
special features were included in rating the basic model. Additionally,
upon DOE request, the manufacturer must provide a layout of the system
set-up for testing including charging instructions consistent with the
installation manual.
0
6. Amend Sec. 429.70 by:
0
a. Revising paragraph (c) introductory text;
0
b. Revising the tables in paragraphs (c)(2)(iv) and (c)(5)(vi)(B); and
0
c. Adding paragraph (i).
The revisions and addition read as follows:
Sec. 429.70 Alternative methods for determining energy efficiency and
energy use.
* * * * *
(c) Alternative efficiency determination method (AEDM) for
commercial HVAC & WH products (excluding air-cooled, three-phase, small
commercial package air conditioning and heating equipment with a
cooling capacity of less than 65,000 Btu/h and air-cooled, three-phase,
variable refrigerant flow multi-split air conditioners and heat pumps
with less than 65,000 Btu/h cooling capacity), and commercial
refrigerators, freezers, and refrigerator-freezers--
* * * * *
(2) * * *
(iv) * * *
------------------------------------------------------------------------
Minimum number of distinct
Validation class models that must be tested
per AEDM
------------------------------------------------------------------------
(A) Commercial HVAC validation classes
------------------------------------------------------------------------
Air-Cooled, Split and Packaged ACs and HPs 2 Basic Models.
Greater than or Equal to 65,000 Btu/h
Cooling Capacity and Less than 760,000 Btu/
h Cooling Capacity.
Water-Cooled, Split and Packaged ACs and 2 Basic Models.
HPs, All Cooling Capacities.
Evaporatively-Cooled, Split and Packaged 2 Basic Models.
ACs and HPs, All Capacities.
Water-Source HPs, All Capacities........... 2 Basic Models.
Single Package Vertical ACs and HPs........ 2 Basic Models.
Packaged Terminal ACs and HPs.............. 2 Basic Models.
Air-Cooled, Variable Refrigerant Flow ACs 2 Basic Models.
and HPs Greater than or Equal to 65,000
Btu/h Cooling Capacity.
Water-Cooled, Variable Refrigerant Flow ACs 2 Basic Models.
and HPs.
Computer Room Air Conditioners, Air Cooled. 2 Basic Models.
Computer Room Air Conditioners, Water- 2 Basic Models.
Cooled.
------------------------------------------------------------------------
(B) Commercial water heater validation classes
------------------------------------------------------------------------
Gas-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Less than 10 Gallons.
Gas-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Greater than or Equal to 10
Gallons.
Oil-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Less than 10 Gallons.
Oil-fired Water Heaters and Hot Water 2 Basic Models.
Supply Boilers Greater than or Equal to 10
Gallons.
Electric Water Heaters..................... 2 Basic Models.
Heat Pump Water Heaters.................... 2 Basic Models.
Unfired Hot Water Storage Tanks............ 2 Basic Models.
------------------------------------------------------------------------
(C) Commercial packaged boilers validation classes
------------------------------------------------------------------------
Gas-fired, Hot Water Only Commercial 2 Basic Models.
Packaged Boilers.
Gas-fired, Steam Only Commercial Packaged 2 Basic Models.
Boilers.
Gas-fired Hot Water/Steam Commercial 2 Basic Models.
Packaged Boilers.
Oil-fired, Hot Water Only Commercial 2 Basic Models.
Packaged Boilers.
Oil-fired, Steam Only Commercial Packaged 2 Basic Models.
Boilers.
Oil-fired Hot Water/Steam Commercial 2 Basic Models.
Packaged Boilers.
------------------------------------------------------------------------
(D) Commercial furnace validation classes
------------------------------------------------------------------------
Gas-fired Furnaces......................... 2 Basic Models.
Oil-fired Furnaces......................... 2 Basic Models.
------------------------------------------------------------------------
(E) Commercial refrigeration equipment validation classes
------------------------------------------------------------------------
Self-Contained Open Refrigerators.......... 2 Basic Models.
Self-Contained Open Freezers............... 2 Basic Models.
Remote Condensing Open Refrigerators....... 2 Basic Models.
Remote Condensing Open Freezers............ 2 Basic Models.
Self-Contained Closed Refrigerators........ 2 Basic Models.
Self-Contained Closed Freezers............. 2 Basic Models.
Remote Condensing Closed Refrigerators..... 2 Basic Models.
Remote Condensing Closed Freezers.......... 2 Basic Models.
------------------------------------------------------------------------
\1\ The minimum number of tests indicated above must be comprised of a
transparent model, a solid model, a vertical model, a semi-vertical
model, a horizontal model, and a service-over-the counter model, as
applicable based on the equipment offering. However, manufacturers do
not need to include all types of these models if it will increase the
minimum number of tests that need to be conducted.
[[Page 70341]]
* * * * *
(5) * * *
(vi) * * *
(B) * * *
------------------------------------------------------------------------
Applicable
Equipment Metric tolerance (%)
------------------------------------------------------------------------
Commercial Packaged Boilers....... Combustion 5 (0.05)
Efficiency.
Thermal Efficiency.. 5 (0.05)
Commercial Water Heaters or Hot Thermal Efficiency.. 5 (0.05)
Water Supply Boilers.
Standby Loss........ 10 (0.1)
Unfired Storage Tanks............. R-Value............. 10 (0.1)
Air-Cooled, Split and Packaged ACs Energy Efficiency 5 (0.05)
and HPs Greater than or Equal to Ratio. 5 (0.05)
65,000 Btu/h Cooling Capacity and Coefficient of
Less than 760,000 Btu/h Cooling Performance.
Capacity.
Integrated Energy 10 (0.1)
Efficiency Ratio.
Water-Cooled, Split and Packaged Energy Efficiency 5 (0.05)
ACs and HPs, All Cooling Ratio.
Capacities.
Coefficient of 5 (0.05)
Performance.
Integrated Energy 10 (0.1)
Efficiency Ratio.
Evaporatively-Cooled, Split and Energy Efficiency 5 (0.05)
Packaged ACs and HPs, All Ratio.
Capacities.
Coefficient of 5 (0.05)
Performance.
Integrated Energy 10 (0.1)
Efficiency Ratio.
Water-Source HPs, All Capacities.. Energy Efficiency 5 (0.05)
Ratio.
Coefficient of 5 (0.05)
Performance.
Integrated Energy 10 (0.1)
Efficiency Ratio.
Single Package Vertical ACs and Energy Efficiency 5 (0.05)
HPs. Ratio.
Coefficient of 5 (0.05)
Performance.
Packaged Terminal ACs and HPs..... Energy Efficiency 5 (0.05)
Ratio.
Coefficient of 5 (0.05)
Performance.
Variable Refrigerant Flow ACs and Energy Efficiency 5 (0.05)
HPs (Excluding Air-Cooled, Three- Ratio. 5 (0.05)
phase with Less than 65,000 Btu/h Coefficient of
Cooling Capacity). Performance.
Integrated Energy 10 (0.1)
Efficiency Ratio.
Computer Room Air Conditioners.... Sensible Coefficient 5 (0.05)
of Performance.
Commercial Warm-Air Furnaces...... Thermal Efficiency.. 5 (0.05)
Commercial Refrigeration Equipment Daily Energy 5 (0.05)
Consumption.
------------------------------------------------------------------------
* * * * *
(i) Alternate Efficiency Determination Method (AEDM) for air-
cooled, three-phase, small commercial package air conditioning and
heating equipment with a cooling capacity of less than 65,000 Btu/h and
air-cooled, three-phase, variable refrigerant flow multi-split air
conditioners and heat pumps with less than 65,000 Btu/h cooling
capacity.
(1) Applicability. (i) For air-cooled, three-phase, small
commercial package air conditioning and heating equipment with a
cooling capacity of less than 65,000 Btu/h and air-cooled, three-phase,
variable refrigerant flow multi-split air conditioners and heat pumps
with a cooling capacity of less than 65,000 Btu/h subject to standards
in terms of seasonal energy efficiency ratio (SEER) and heating
seasonal performance factor (HSPF), representations with respect to the
energy use or efficiency, including compliance certifications, are
subject to the requirements in Sec. 429.70(c) of this title as it
appeared in the 10 CFR parts 200-499 edition revised as of January 1,
2021.
(ii) For air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less than
65,000 Btu/h and air-cooled, three-phase, variable refrigerant flow
multi-split air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h subject to standards in terms of seasonal energy
efficiency ratio 2 (``SEER2'') and heating seasonal performance factor
2 (``HSPF2'') metrics, representations with respect to the energy use
or efficiency, including compliance certifications, are subject to the
requirements in this section. If manufacturers choose to certify
compliance with any standards in terms of SEER2 and HSPF2 prior to the
applicable compliance date for those standards, the requirements of
this section must be followed.
(2) Criteria an AEDM must satisfy. A manufacturer may not apply an
AEDM to an individual model/combination to determine its represented
values (SEER2 and HSPF2, as applicable) pursuant to this section unless
authorized pursuant to Sec. 429.64(e) and:
(i) The AEDM is derived from a mathematical model that estimates
the energy efficiency or energy consumption characteristics of the
individual model or combination (SEER2 and HSPF2, as applicable) as
measured by the applicable DOE test procedure; and
(ii) The manufacturer has validated the AEDM in accordance with
paragraph (i)(3) of this section.
(3) Validation of an AEDM. For manufacturers whose models of air-
cooled, three-phase, small commercial package air conditioning and
heating equipment with a cooling capacity of less than 65,000 Btu/h or
air-cooled, three-phase, variable refrigerant flow multi-split air
conditioners and heat pumps with a cooling capacity of less than 65,000
Btu/h are otherwise identical to their central air conditioner and heat
pump models (meaning differing only in phase of the electrical system
and the phase of power input for which the motors and compressors are
designed) and who have validated an AEDM for the otherwise identical
central air conditioners and heat pumps under Sec. 429.70(e)(2), no
additional validation is required. For manufacturers whose models of
air-cooled, three-phase, small commercial package air conditioning and
heating equipment with a cooling capacity of less than 65,000 Btu/h or
air-cooled, three-phase, variable refrigerant flow multi-split air
conditioners and heat pumps with a cooling capacity of less than 65,000
Btu/h who have not validated an AEDM for otherwise identical central
air conditioners and
[[Page 70342]]
heat pumps under Sec. 429.70(e)(2) must, before using an AEDM,
validate the AEDM's accuracy and reliability as follows:
(i) Minimum testing. The manufacturer must test a single unit each
of two basic models in accordance with paragraph (i)(3)(iii) of this
section. Using the AEDM, calculate the energy use or efficiency for
each of the tested individual models/combinations within each basic
model. Compare the represented value based on testing and the AEDM
energy use or efficiency output according to paragraph (i)(3)(ii) of
this section. The manufacturer is responsible for ensuring the accuracy
and reliability of the AEDM and that their representations are
appropriate and the models being distributed in commerce meet the
applicable standards, regardless of the amount of testing required in
this paragraph.
(ii) Individual model/combination tolerances. This paragraph
(i)(3)(ii) provides the tolerances applicable to individual models/
combinations rated using an AEDM.
(A) The predicted represented values for each individual model/
combination calculated by applying the AEDM may not be more than four
percent greater (for measures of efficiency) or less (for measures of
consumption) than the values determined from the corresponding test of
the individual model/combination.
(B) The predicted energy efficiency or consumption for each
individual model/combination calculated by applying the AEDM must meet
or exceed the applicable federal energy conservation standard.
(iii) Additional test unit requirements. (A) Each AEDM must be
supported by test data obtained from physical tests of current
individual models/combinations; and
(B) Test results used to validate the AEDM must meet or exceed
current, applicable Federal standards as specified in part 431 of this
chapter; and
(C) Each test must have been performed in accordance with the
applicable DOE test procedure with which compliance is required at the
time the individual models/combinations used for validation are
distributed in commerce.
(4) AEDM records retention requirements. If a manufacturer has used
an AEDM to determine representative values pursuant to this section,
the manufacturer must have available upon request for inspection by the
Department records showing:
(i) The AEDM, including the mathematical model, the engineering or
statistical analysis, and/or computer simulation or modeling that is
the basis of the AEDM;
(ii) Product information, complete test data, AEDM calculations,
and the statistical comparisons from the units tested that were used to
validate the AEDM pursuant to paragraph (i)(3) of this section; and
(iii) Product information and AEDM calculations for each individual
model/combination to which the AEDM has been applied.
(5) Additional AEDM requirements. If requested by the Department,
the manufacturer must:
(i) Conduct simulations before representatives of the Department to
predict the performance of particular individual models/combinations;
(ii) Provide analyses of previous simulations conducted by the
manufacturer; and/or
(iii) Conduct certification testing of individual models or
combinations selected by the Department.
(6) AEDM verification testing. DOE may use the test data for a
given individual model/combination generated pursuant to Sec. 429.104
to verify the represented value determined by an AEDM as long as the
following process is followed:
(i) Selection of units. DOE will obtain one or more units for test
from retail, if available. If units cannot be obtained from retail, DOE
will request that a unit be provided by the manufacturer;
(ii) Lab requirements. DOE will conduct testing at an independent,
third-party testing facility of its choosing. In cases where no third-
party laboratory is capable of testing the equipment, testing may be
conducted at a manufacturer's facility upon DOE's request.
(iii) Testing. At no time during verification testing may the lab
and the manufacturer communicate without DOE authorization. If, during
test set-up or testing, the lab indicates to DOE that it needs
additional information regarding a given individual model or
combination in order to test in accordance with the applicable DOE test
procedure, DOE may organize a meeting between DOE, the manufacturer,
and the lab to provide such information.
(iv) Failure to meet certified value. If an individual model/
combination tests worse than its certified value (i.e., lower than the
certified efficiency value or higher than the certified consumption
value) by more than 5 percent, or the test results in cooling capacity
that is lower than its certified cooling capacity, DOE will notify the
manufacturer. DOE will provide the manufacturer with all documentation
related to the test set up, test conditions, and test results for the
unit. Within the timeframe allotted by DOE, the manufacturer may
present any and all claims regarding testing validity.
(v) Tolerances. This paragraph specifies the tolerances DOE will
permit when conducting verification testing.
(A) For consumption metrics, the result from a DOE verification
test must be less than or equal to 1.05 multiplied by the certified
represented value.
(B) For efficiency metrics, the result from a DOE verification test
must be greater than or equal to 0.95 multiplied by the certified
represented value.
(vi) Invalid represented value. If, following discussions with the
manufacturer and a retest where applicable, DOE determines that the
verification testing was conducted appropriately in accordance with the
DOE test procedure, DOE will issue a determination that the represented
values for the basic model are invalid. The manufacturer must conduct
additional testing and re-rate and re-certify the individual models/
combinations within the basic model that were rated using the AEDM
based on all test data collected, including DOE's test data.
(vii) AEDM use. This paragraph (i)(6)(vii) specifies when a
manufacturer's use of an AEDM may be restricted due to prior invalid
represented values.
(A) If DOE has determined that a manufacturer made invalid
represented values on individual models/combinations within two or more
basic models rated using the manufacturer's AEDM within a 24-month
period, the manufacturer must test the least efficient and most
efficient individual model/combination within each basic model in
addition to the individual model/combination specified in Sec.
429.16(b)(2). The 24-month period begins with a DOE determination that
a represented value is invalid through the process outlined in
paragraphs (i)(6)(i) through (vi) of this section.
(B) If DOE has determined that a manufacturer made invalid
represented values on more than four basic models rated using the
manufacturer's AEDM within a 24-month period, the manufacturer may no
longer use an AEDM.
(C) If a manufacturer has lost the privilege of using an AEDM, the
manufacturer may regain the ability to use an AEDM by:
(1) Investigating and identifying cause(s) for failures;
(2) Taking corrective action to address cause(s);
(3) Performing six new tests per basic model, a minimum of two of
which must be performed by an independent,
[[Page 70343]]
third-party laboratory from units obtained from retail to validate the
AEDM; and
(4) Obtaining DOE authorization to resume use of an AEDM.
0
7. Section 429.134 is amended by adding paragraph (s) to read as
follows:
Sec. 429.134 Product-specific enforcement provisions.
* * * * *
(s) Air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less than
65,000 Btu/h and air-cooled, three-phase, variable refrigerant flow
multi-split air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h. The following provisions apply for assessment
and enforcement testing of models subject to standards in terms of
SEER2 and HSPF2 (as applicable).
(1) Verification of cooling capacity. The cooling capacity of each
tested unit of the individual model (for single-package units) or
individual combination (for split systems) will be measured pursuant to
the test requirements of appendix B1 to subpart F of part 431. The mean
of the cooling capacity measurement(s) (either the measured cooling
capacity for a single unit sample or the average of the measured
cooling capacities for a multiple unit sample) will be used to
determine the applicable standards for purposes of compliance.
(2) Verification of CD value. (i) For models other than models of
outdoor units with no match, if manufacturers certify that they did not
conduct the optional tests to determine the Cc and/or
Ch value for an individual model (for single-package
systems) or individual combination (for split systems), as applicable,
the default Cc and/or Ch value will be used as
the basis for calculation of SEER2 or HSPF2 for each unit tested. If
manufacturers certify that they conducted the optional tests to
determine the Cc and/or Ch value for an
individual model (for single-package systems) or individual combination
(for split systems), as applicable, the Cc and/or
Ch value will be measured pursuant to the test requirements
of appendix B1 to subpart F of part 431 for each unit tested and the
result for each unit tested (either the tested value or the default
value, as selected according to the criteria for the cyclic test in
Sections 6.1.3.1 and 6.1.3.2 of AHRI 210/240-2023 (incorporated by
reference, see Sec. 429.4)) used as the basis for calculation of SEER2
or HSPF2 for that unit.
(ii) For models of outdoor units with no match, DOE will use the
default Cc and/or Ch value pursuant to appendix B1 to subpart F of part
431.
PART 431--ENERGY EFFICIENCY PROGRAM FOR CERTAIN COMMERCIAL AND
INDUSTRIAL EQUIPMENT
0
8. The authority citation for part 431 continues to read as follows:
Authority: 42 U.S.C. 6291-6317; 28 U.S.C. 2461 note.
0
9. Amend Sec. 431.92 in the definition of Basic model, by:
0
a. Revising paragraphs (2) and (5); and
0
b. Adding paragraph (7).
The revisions and addition read as follows:
Sec. 431.92 Definitions concerning commercial air conditioners and
heat pumps.
* * * * *
Basic model includes:
* * * * *
(2) Small, large, and very large air-cooled or water-cooled
commercial package air conditioning and heating equipment (excluding
air-cooled, three-phase, small commercial package air conditioning and
heating equipment with a cooling capacity of less than 65,000 Btu/h
cooling capacity) means all units manufactured by one manufacturer
within a single equipment class, having the same or comparably
performing compressor(s), heat exchangers, and air moving system(s)
that have a common ``nominal'' cooling capacity.
* * * * *
(5) Variable refrigerant flow systems (excluding air-cooled, three-
phase, variable refrigerant flow air conditioners and heat pumps with a
cooling capacity of less than 65,000 Btu/h) means all units
manufactured by one manufacturer within a single equipment class,
having the same primary energy source (e.g., electric or gas), and
which have the same or comparably performing compressor(s) that have a
common ``nominal'' cooling capacity and the same heat rejection medium
(e.g., air or water) (includes VRF water source heat pumps).
* * * * *
(7) Air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less than
65,000 Btu/h and air-cooled, three-phase, variable refrigerant flow
multi-split air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h means all units manufactured by one
manufacturer; having the same primary energy source; and, which have
essentially identical electrical, physical, and functional (or
hydraulic) characteristics that affect energy consumption, energy
efficiency, water consumption, or water efficiency; where essentially
identical electrical, physical, and functional (or hydraulic)
characteristics means:
(i) For split systems manufactured by outdoor unit manufacturers
(OUMs): All individual combinations having the same model of outdoor
unit, which means comparably performing compressor(s) [a variation of
no more than five percent in displacement rate (volume per time) as
rated by the compressor manufacturer, and no more than five percent in
capacity and power input for the same operating conditions as rated by
the compressor manufacturer], outdoor coil(s) [no more than five
percent variation in face area and total fin surface area; same fin
material; same tube material], and outdoor fan(s) [no more than ten
percent variation in airflow and no more than twenty percent variation
in power input];
(ii) For split systems having indoor units manufactured by
independent coil manufacturers (ICMs): All individual combinations
having comparably performing indoor coil(s) [plus or minus one square
foot face area, plus or minus one fin per inch fin density, and the
same fin material, tube material, number of tube rows, tube pattern,
and tube size]; and
(iii) For single-package systems: All individual models having
comparably performing compressor(s) [no more than five percent
variation in displacement rate (volume per time) rated by the
compressor manufacturer, and no more than five percent variations in
capacity and power input rated by the compressor manufacturer
corresponding to the same compressor rating conditions], outdoor
coil(s) and indoor coil(s) [no more than five percent variation in face
area and total fin surface area; same fin material; same tube
material], outdoor fan(s) [no more than ten percent variation in
outdoor airflow], and indoor blower(s) [no more than ten percent
variation in indoor airflow, with no more than twenty percent variation
in fan motor power input];
(iv) Except that,
(A) For single-package systems and single-split systems,
manufacturers may instead choose to make each individual model/
combination its own basic model provided the testing and represented
value requirements in 10 CFR 429.64 of this chapter are met; and
(B) For multi-split, multi-circuit, and multi-head mini-split
combinations, a
[[Page 70344]]
basic model may not include both individual small-duct, high velocity
(SDHV) combinations and non-SDHV combinations even when they include
the same model of outdoor unit. The manufacturer may choose to identify
specific individual combinations as additional basic models.
* * * * *
0
10. Amend Sec. 431.95 by:
0
a. Removing paragraph (b)(1);
0
b. Redesignating paragraph (b)(2) as (b)(1);
0
c. Revising newly redesignated paragraph (b)(1);
0
d. Adding new paragraph (b)(2);
0
e. Revising paragraph (b)(6); and
0
f. Revising paragraph (c)(2).
The revisions and addition read as follows:
Sec. 431.95 Materials incorporated by reference.
* * * * *
(b) * * *
(1) ANSI/AHRI Standard 210/240-2008, ``2008 Standard for
Performance Rating of Unitary Air-Conditioning & Air-Source Heat Pump
Equipment'', approved by ANSI on October 27, 2011 and updated by
addendum 1 in June 2011 and addendum 2 in March 2012 (AHRI 210/240-
2008), IBR approved for Sec. 431.96 and appendix B to this subpart.
(2) AHRI Standard 210/240-2023, ``Performance Rating of Unitary
Air-Conditioning & Air-Source Heat Pump Equipment,'' approved May 2020
(AHRI 210/240-2023), IBR approved for appendix B1 to this subpart.
* * * * *
(6) ANSI/AHRI Standard 1230-2010, ``2010 Standard for Performance
Rating of Variable Refrigerant Flow (VRF) Multi-split Air-Conditioning
and Heat Pump Equipment,'' approved August 2, 2010 and updated by
addendum 1 in March 2011 (AHRI 1230-2010), IBR approved for Sec.
431.96 and appendix B to this subpart.
(c) * * *
(2) ANSI/ASHRAE Standard 37-2009, (``ANSI/ASHRAE 37-2009''),
``Methods of Testing for Rating Electrically Driven Unitary Air-
Conditioning and Heat Pump Equipment,'' ASHRAE approved June 24, 2009,
IBR approved for Sec. 431.96 and appendices A and B1 to this subpart.
* * * * *
0
11. Amend Sec. 431.96 by revising paragraph (b)(1) and Table 1 to
paragraph (b)(2), to read as follows:
Sec. 431.96 Uniform test method for the measurement of energy
efficiency of commercial air conditioners and heat pumps.
* * * * *
(b) Testing and calculations. (1) Determine the energy efficiency
of each type of covered equipment by conducting the test procedure(s)
listed in table 1 to this section along with any additional testing
provisions set forth in paragraphs (c) through (g) of this section and
appendices A, B, and B1 to this subpart, that apply to the energy
efficiency descriptor for that equipment, category, and cooling
capacity. The omitted sections of the test procedures listed in table 1
to this section must not be used. For equipment with multiple
appendices listed in table 1, consult the notes at the beginning of
those appendices to determine the applicable appendix to use for
testing.
(2) * * *
Table 1 to Sec. 431.96--Test Procedures for Commercial Air Conditioners and Heat Pumps
--------------------------------------------------------------------------------------------------------------------------------------------------------
Additional test
Use tests, procedure provisions
Equipment type Category Cooling capacity Energy efficiency conditions, and as indicated in the
descriptor procedures in \1\ listed paragraphs of
this section
--------------------------------------------------------------------------------------------------------------------------------------------------------
Small Commercial Package Air- Air-Cooled, 3-Phase, <65,000 Btu/h......... SEER and HSPF........ Appendix B to this None.
Conditioning and Heating Equipment. AC and HP. subpart \2\.
SEER2 and HSPF2...... Appendix B1 to this None.
subpart \2\.
Air-Cooled AC and HP.. >=65,000 Btu/h and EER, IEER, and COP... Appendix A to this None.
<135,000 Btu/h. subpart.
Water-Cooled and <65,000 Btu/h......... EER.................. AHRI 210/240-2008 Paragraphs (c) and
Evaporatively-Cooled (omit section 6.5). (e).
AC.
>=65,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
<135,000 Btu/h. (omit section 6.3). (e).
Water-Source HP....... <135,000 Btu/h........ EER and COP.......... ISO Standard 13256-1 Paragraph (e).
(1998).
Large Commercial Package Air- Air-Cooled AC and HP.. >=135,000 Btu/h and EER, IEER and COP.... Appendix A to this None.
Conditioning and Heating Equipment. <240,000 Btu/h. subpart.
Water-Cooled and >=135,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
Evaporatively-Cooled <240,000 Btu/h. (omit section 6.3). (e).
AC.
Very Large Commercial Package Air- Air-Cooled AC and HP.. >=240,000 Btu/h and EER, IEER and COP.... Appendix A to this None.
Conditioning and Heating Equipment. <760,000 Btu/h. subpart.
Water-Cooled and >=240,000 Btu/h and EER.................. AHRI 340/360-2007 Paragraphs (c) and
Evaporatively-Cooled <760,000 Btu/h. (omit section 6.3). (e).
AC.
Packaged Terminal Air Conditioners AC and HP............. <760,000 Btu/h........ EER and COP.......... Paragraph (g) of this Paragraphs (c), (e),
and Heat Pumps. section. and (g).
Computer Room Air Conditioners..... AC.................... <65,000 Btu/h......... SCOP................. ASHRAE 127-2007 (omit Paragraphs (c) and
section 5.11). (e).
[[Page 70345]]
>=65,000 Btu/h and SCOP................. ASHRAE 127-2007 (omit Paragraphs (c) and
<760,000 Btu/h. section 5.11). (e).
Variable Refrigerant Flow Multi- AC.................... <65,000 Btu/h (3- SEER................. Appendix B to this None.
split Systems. phase). subpart \2\.
SEER2................ Appendix B1 to this None.
subpart \2\.
>=65,000 Btu/h and EER.................. AHRI 1230-2010 (omit Paragraphs (c), (d),
<760,000 Btu/h. sections 5.1.2 and (e), and (f).
6.6).
Variable Refrigerant Flow Multi- HP.................... <65,000 Btu/h (3- SEER and HSPF........ Appendix B to this None.
split Systems, Air-cooled. phase). subpart \2\.
SEER2 and HSPF2...... Appendix B1 to this None.
subpart \2\.
>=65,000 Btu/h and EER and COP.......... AHRI 1230-2010 (omit Paragraphs (c), (d),
<760,000 Btu/h. sections 5.1.2 and (e), and (f).
6.6).
Variable Refrigerant Flow Multi- HP.................... <760,000 Btu/h........ EER and COP.......... AHRI 1230-2010 (omit Paragraphs (c), (d),
split Systems, Water-source. sections 5.1.2 and (e), and (f).
6.6).
Single Package Vertical Air AC and HP............. <760,000 Btu/h........ EER and COP.......... AHRI 390-2003 (omit Paragraphs (c) and
Conditioners and Single Package section 6.4). (e).
Vertical Heat Pumps.
--------------------------------------------------------------------------------------------------------------------------------------------------------
\1\ Incorporated by reference, as applicable; see Sec. 431.95.
\2\ For equipment with multiple appendices listed in Table 1, consult the notes at the beginning of those appendices to determine the applicable
appendix to use for testing.
* * * * *
0
12. Add appendix B to subpart F of part 431 to read as follows:
Appendix B to Subpart F of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of Air-Cooled, Three-Phase, Small
Commercial Package Air Conditioning and Heating Equipment With a
Cooling Capacity of Less Than 65,000 Btu/H and Air-Cooled, Three-Phase,
Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps
With a Cooling Capacity of Less Than 65,000 BTU/H
Note: Manufacturers must use the results of testing under this
appendix to determine compliance with the relevant standard from
Sec. 431.97 as that standard appeared in the January 1, 2021
edition of 10 CFR parts 200-499. Specifically, before [Date 360 days
following publication of the final rule] representations must be
based upon results generated either under this appendix or under 10
CFR 431.96 as it appeared in the 10 CFR parts 200-499 edition
revised as of January 1, 2021.
Note: For any amended standards for air-cooled, three-phase,
small commercial package air conditioning and heating equipment with
a cooling capacity of less than 65,000 Btu/h and air-cooled, three-
phase, variable refrigerant flow multi-split air conditioners and
heat pumps with a cooling capacity of less than 65,000 Btu/h that
rely on SEER2 and HSPF2 published after January 1, 2021,
manufacturers must use the results of testing under appendix B1 to
determine compliance.
Representations related to energy consumption must be made in
accordance with the appropriate appendix that applies (i.e.,
appendices B or B1) when determining compliance with the relevant
standard. Manufacturers may also use appendix B1 to certify
compliance with any amended standards prior to the applicable
compliance date for those standards.
1. Incorporation by Reference
DOE incorporated by reference in Sec. 431.95, the entire
standard for ANSI/AHRI 210/240-2008, ``Performance Rating of Unitary
Air-Conditioning & Air-Source Heat Pump Equipment''; and ANSI/AHRI
1230-2010, ``Performance Rating of Variable Refrigerant Flow (VRF)
Multi-split Air-conditioning and Heat Pump Equipment.'' However,
certain enumerated provisions of those standards, as set forth in
paragraphs (a) and (b) of this section, are inapplicable. To the
extent there is a conflict between the terms or provisions of a
referenced industry standard and the CFR, the CFR provisions
control.
(a) ANSI/AHRI 210/240-2008:
(i) Section 6.5 is inapplicable as specified in section 2.1 of
this appendix.
(ii) Reserved.
(b) ANSI/AHRI 1230-2010:
(i) Section 5.1.2--Manufacturer involvement is inapplicable as
specified in section 2.2(1) of this appendix.
(ii) Section 6.6--Verification testing and uncertainty is
inapplicable as specified in section 2.2(2) of this appendix.
2. General
2.1 Air-cooled, three-phase, small commercial package air
conditioning and heating equipment with a cooling capacity of less
than 65,000 Btu/h. Determine the seasonal energy efficiency ratio
(SEER) and heating seasonal performance factor (HSPF) (as
applicable) in accordance with ANSI/AHRI 210/240-2008; however,
Section 6.5, Tolerances, of ANSI/AHRI 210/240-2008 is not
applicable. Sections 3 and 4 of this appendix provide additional
instructions for determining SEER and HSPF. In cases where there is
a conflict, the language of this appendix takes precedence over
ANSI/AHRI 210/240-2008.
1.2. Air-cooled, three-phase, variable refrigerant flow multi-
split air conditioners and heat pumps with a cooling capacity of
less than 65,000 Btu/h. Determine the SEER and HSPF (as applicable)
in accordance with ANSI/AHRI 1230-2010; however, the following
enumerated provisions of that document are not applicable.
(1) Section 5.1.2--Manufacturer involvement,
(2) Section 6.6--Verification testing and uncertainty
Sections 3 through 6 of this appendix provide additional
instructions for determining SEER and HSPF. In cases where there is
a conflict, the language of this appendix takes precedence over
ANSI/AHRI 1230-2010.
3. Optional break-in period. Manufacturers may optionally
specify a ``break-in'' period, not to exceed 20 hours, to operate
the equipment under test prior to conducting the test method
specified in this appendix. A
[[Page 70346]]
manufacturer who elects to use an optional compressor break-in
period in its certification testing should record this period's
duration as part of the information in the supplemental testing
instructions under 10 CFR 429.43.
4. Additional provisions for equipment set-up. The only
additional specifications that may be used in setting up the basic
model for test are those set forth in the installation and operation
manual shipped with the unit. Each unit should be set up for test in
accordance with the manufacturer installation and operation manuals.
Sections 3.1 through 3.3 of this appendix provide specifications for
addressing key information typically found in the installation and
operation manuals.
4.1. If a manufacturer specifies a range of superheat, sub-
cooling, and/or refrigerant pressure in its installation and
operation manual for a given basic model, any value(s) within that
range may be used to determine refrigerant charge or mass of
refrigerant, unless the manufacturer clearly specifies a rating
value in its installation and operation manual, in which case the
specified rating value shall be used.
4.2. The airflow rate used for testing must be that set forth in
the installation and operation manuals being shipped to the
commercial customer with the basic model and clearly identified as
that used to generate the DOE performance ratings. If a rated
airflow value for testing is not clearly identified, a value of 400
standard cubic feet per minute (scfm) per ton shall be used.
4.3. For air-cooled, three-phase, variable refrigerant flow
multi-split air conditioners and heat pumps with a cooling capacity
of less than 65,000 Btu/h, the test set-up and the fixed compressor
speeds (i.e., the maximum, minimum, and any intermediate speeds used
for testing) should be recorded and maintained as part of the test
data underlying the certified ratings that is required to be
maintained under 10 CFR 429.71.
5. Refrigerant line length corrections for air-cooled, three-
phase, variable refrigerant flow multi-split air conditioners and
heat pumps with a cooling capacity of less than 65,000 Btu/h. For
test setups where it is physically impossible for the laboratory to
use the required line length listed in Table 3 of the ANSI/AHRI
1230-2010, then the actual refrigerant line length used by the
laboratory may exceed the required length and the following cooling
capacity correction factors are applied:
------------------------------------------------------------------------
Piping length beyond minimum, Piping length beyond Cooling capacity
X (ft) minimum, Y (m) correction (%)
------------------------------------------------------------------------
0 > X <= 20................... 0 > Y <= 6.1......... 1
20 > X <= 40.................. 6.1 > Y <= 12.2...... 2
40 > X <= 60.................. 12.2 > Y <= 18.3..... 3
60 > X <= 80.................. 18.3 > Y <= 24.4..... 4
80 > X <= 100................. 24.4 > Y <= 30.5..... 5
100 > X <= 120................ 30.5 > Y <= 36.6..... 6
------------------------------------------------------------------------
6. Manufacturer involvement in assessment or enforcement testing
for air-cooled, three-phase, variable refrigerant flow multi-split
air conditioners and heat pumps with a cooling capacity of less than
65,000 Btu/h. A manufacturer's representative will be allowed to
witness assessment and/or enforcement testing. The manufacturer's
representative will be allowed to inspect and discuss set-up only
with a DOE representative and adjust only the modulating components
during testing in the presence of a DOE representative that are
necessary to achieve steady-state operation. Only previously
documented specifications for set-up as specified under sections 3
and 4 of this appendix will be used.
0
13. Add appendix B1 to subpart F of part 431 to read as follows:
Appendix B1 to Subpart F of Part 431--Uniform Test Method for the
Measurement of Energy Consumption of Air-Cooled, Three-Phase, Small
Commercial Package Air Conditioning and Heating Equipment With a
Cooling Capacity of Less Than 65,000 BTU/H and Air-Cooled, Three-Phase,
Variable Refrigerant Flow Multi-Split Air Conditioners and Heat Pumps
With a Cooling Capacity of Less Than 65,000 BTU/H
Note: Manufacturers must use the results of testing under this
appendix to determine compliance with any amended standards for air-
cooled, three-phase, small commercial package air conditioning and
heating equipment with a cooling capacity of less than 65,000 Btu/h
and air-cooled, three-phase, variable refrigerant flow multi-split
air conditioners and heat pumps with a cooling capacity of less than
65,000 Btu/h provided in Sec. 431.97 that are published after
January 1, 2021, and that rely on seasonal energy efficiency ratio 2
(SEER2) and heating seasonal performance factor 2 (HSPF2).
Representations related to energy consumption must be made in
accordance with the appropriate appendix that applies (i.e.,
appendices B or B1) when determining compliance with the relevant
standard. Manufacturers may also use this appendix to certify
compliance with any amended standards prior to the applicable
compliance date for those standards.
1. Incorporation by Reference
DOE incorporated by reference in Sec. 431.95, the entire
standard for AHRI Standard 210/240-2023, ``Performance Rating of
Unitary Air-Conditioning & Air-Source Heat Pump Equipment,''
approved 2020 (AHRI 210/240-2023); and ANSI/ASHRAE Standard 37-2009,
(``ANSI/ASHRAE 37-2009''), ``Methods of Testing for Rating
Electrically Driven Unitary Air-Conditioning and Heat Pump
Equipment,'' ASHRAE approved June 24, 2009. However, certain
enumerated provisions of AHRI 210/240-2023 and ANSI/ASHRAE 37-2009,
as set forth in paragraphs (a) and (b) of this section, are
inapplicable. To the extent there is a conflict between the terms or
provisions of a referenced industry standard and the CFR, the CFR
provisions control.
(a) AHRI 210/240-2023:
(i) Section 6 Rating Requirements--6.1 Standard Ratings--6.1.8
Tested Combinations or Tested Units is inapplicable as specified in
section 2.1(1) of this appendix,
(ii) Section 6 Rating Requirements--6.2 Application Ratings is
inapplicable as specified in section 2.1(2) of this appendix,
(iii) Section 6 Rating Requirements--6.4 Ratings is inapplicable
as specified in section 2.1(3) of this appendix,
(iv) Section 6 Rating Requirements--6.5 Uncertainty and
Variability is inapplicable as specified in section 2.1(4) of this
appendix,
(v) Section 7 Minimum Data Requirements for Published Ratings is
inapplicable as specified in section 2.1(5) of this appendix,
(vi) Section 8 Operating Requirements is inapplicable as
specified in section 2.1(6) of this appendix,
(vii) Section 9 Marking and Nameplate Data is inapplicable as
specified in section 2.1(7) of this appendix,
(viii) Section 10 Conformance Conditions is inapplicable as
specified in section 2.1(8) of this appendix,
(ix) Appendix C Certification of Laboratory Facilities Used to
Determine Performance of Unitary Air-Conditioning & Air-Source Heat
Pump Equipment--Informative is inapplicable as specified in section
2.1(9) of this appendix,
(x) Appendix F ANSI/ASHRAE Standard 116-2010 Clarifications/
Exceptions--Normative--F15.2 and F17 are inapplicable as specified
in section 2.1(10) of this appendix,
(xi) Appendix G Unit Configuration for Standard Efficiency
Determination--Normative is inapplicable as specified in section
2.1(11) of this appendix,
(xi) Appendix H Off-Mode Testing--Normative is inapplicable as
specified in section 2.1(12) of this appendix,
(xii) Appendix I Verification Testing--Normative is inapplicable
as specified in section 2.1(13) of this appendix.
(b) ANSI/ASHRAE 37-2009:
(i) Section 1 Purpose is inapplicable as specified in section
2.2(1) of this appendix,
[[Page 70347]]
(ii) Section 2 Scope is inapplicable as specified in section
2.2(2) of this appendix, and
(iii) Section 4 Classification is inapplicable as specified in
section 2.2(3) of this appendix.
2. General. Determine the seasonal energy efficiency ratio 2
(SEER2) and heating seasonal performance factor 2 (HSPF2) (as
applicable) in accordance with AHRI 210/240-2023, ``Performance
Rating of Unitary Air-Conditioning & Air-Source Heat Pump
Equipment'' and ANSI/ASHRAE 37-2009 ``Methods of Testing for Rating
Electronically Driven Unitary Air-Conditioning and Heat Pump
Equipment''; however, the following enumerated provisions of that
document are not applicable. Sections 3 and 4 of this appendix
provide additional instructions for determining SEER2 and HSPF2. In
cases where there is a conflict, the language of this appendix takes
precedence over AHRI 210/240-2023. Any subsequent amendment to a
referenced document by the standard-setting organization will not
affect the test procedure in this appendix, unless and until the
test procedure is amended by DOE. Material is incorporated as it
exists on the date of the approval, and a notice of any change in
the incorporation will be published in the Federal Register.
2.1. Excepted sections of AHRI 210/240-2023
(1) Section 6 Rating Requirements--6.1 Standard Ratings--6.1.8
Tested Combinations or Tested Units,
(2) Section 6 Rating Requirements--6.2 Application Ratings,
(3) Section 6 Rating Requirements--6.4 Ratings,
(4) Section 6 Rating Requirements--6.5 Uncertainty and
Variability,
(5) Section 7 Minimum Data Requirements for Published Ratings,
(6) Section 8 Operating Requirements,
(7) Section 9 Marking and Nameplate Data,
(8) Section 10 Conformance Conditions,
(9) Appendix C Certification of Laboratory Facilities Used to
Determine Performance of Unitary Air-Conditioning & Air-Source Heat
Pump Equipment--Informative,
(10) Appendix F ANSI/ASHRAE Standard 116-2010 Clarifications/
Exceptions--Normative--F15.2 and F17,
(11) Appendix G Unit Configuration for Standard Efficiency
Determination--Normative,
(12) Appendix H Off-Mode Testing--Normative, and
(13) Appendix I Verification Testing--Normative.
2.2. Excepted sections of ANSI/ASHRAE 37-2009
(1) Section 1 Purpose,
(2) Section 2 Scope,
(3) Section 4 Classification.
3. Energy Measurement Accuracy. The watt-hour (W[sdot]h)
measurement system(s) shall be accurate within 0.5
percent or 0.5 W[middot]h, whichever is greater, for both ON and OFF
cycles. If two measurement systems are used, then the meters shall
be switched within 15 seconds of the start of the OFF cycle and
switched within 15 seconds prior to the start of the ON cycle.
4. Cycle Stability Requirements. Conduct three complete
compressor OFF/ON cycles. Calculate the degradation coefficient
CD for each complete cycle. If all three CD
values are within 0.02 of the average CD then stability
has been achieved, and the highest CD value of these
three shall be used. If stability has not been achieved, conduct
additional cycles, up to a maximum of eight cycles total, until
stability has been achieved between three consecutive cycles. Once
stability has been achieved, use the highest CD value of
the three consecutive cycles that establish stability. If stability
has not been achieved after eight cycles, use the highest
CD from cycle one through cycle eight, or the default
CD, whichever is lower.
[FR Doc. 2021-24836 Filed 12-8-21; 8:45 am]
BILLING CODE 6450-01-P