Notice of Final Approval for an Alternative Means of Emission Limitation, 38076-38078 [2021-15321]
Download as PDF
38076
Federal Register / Vol. 86, No. 135 / Monday, July 19, 2021 / Notices
name, mailing address, and an email
address or other contact information in
the body of your comment. This ensures
that you can be identified as the
submitter of the comment and allows
EPA to contact you in case EPA cannot
read your comment due to technical
difficulties or needs further information
on the substance of your comment. Any
identifying or contact information
provided in the body of a comment will
be included as part of the comment that
is placed in the official public docket
and made available in EPA’s electronic
public docket. If EPA cannot read your
comment due to technical difficulties
and cannot contact you for clarification,
EPA may not be able to consider your
comment.
Use of the https://
www.regulations.gov website to submit
comments to EPA electronically is
EPA’s preferred method for receiving
comments. The electronic public docket
system is an ‘‘anonymous access’’
system, which means EPA will not
know your identity, email address, or
other contact information unless you
provide it in the body of your comment.
Please ensure that your comments are
submitted within the specified comment
period. Comments received after the
close of the comment period will be
marked ‘‘late.’’ EPA is not required to
consider these late comments.
Gautam Srinivasan,
Associate General Counsel.
[FR Doc. 2021–15240 Filed 7–16–21; 8:45 am]
BILLING CODE 6560–50–P
ENVIRONMENTAL PROTECTION
AGENCY
[EPA–HQ–OAR–2020–0599; FRL–8194–02–
OAR]
Notice of Final Approval for an
Alternative Means of Emission
Limitation
Environmental Protection
Agency (EPA).
ACTION: Notice; final approval.
AGENCY:
This action announces the
Environmental Protection Agency (EPA)
approval of the request by Rohm and
Haas Chemicals LLC, a subsidiary of
The Rohm and Haas Chemical Company
(Rohm and Haas), under the Clean Air
Act (CAA) for an alternative means of
emission limitation (AMEL) for the
Standards of Performance for Volatile
Organic Liquid Storage Vessels. The
AMEL applies to a proposed new vinyl
acetate bulk storage tank to be used at
its chemical plant in Kankakee, Illinois.
The EPA received no adverse comments
lotter on DSK11XQN23PROD with NOTICES1
SUMMARY:
VerDate Sep<11>2014
18:23 Jul 16, 2021
Jkt 253001
on the request. This approval document
specifies the operating conditions and
monitoring, recordkeeping, and
reporting requirements that this facility
must follow to demonstrate compliance
with the approved AMEL.
DATES: The approval of the AMEL
request from Rohm and Haas to operate
its storage tank in Kankakee, Illinois, as
specified in this document, is effective
on July 19, 2021.
ADDRESSES: The EPA has established a
docket for this action under Docket ID
No. EPA–HQ–OAR–2020–0599. All
documents in the docket are listed on
the https://www.regulations.gov/
website. Although listed, some
information is not publicly available,
e.g., Confidential Business Information
or other information whose disclosure is
restricted by statute. Certain other
material, such as copyrighted material,
is not placed on the internet and will be
publicly available only in hard copy
form. Publicly available docket
materials are available either
electronically through https://
www.regulations.gov/.
Out of an abundance of caution for
members of the public and our staff, the
EPA Docket Center and Reading Room
are closed to the public, with limited
exceptions, to reduce the risk of
transmitting COVID–19. Our Docket
Center staff will continue to provide
remote customer service via email,
phone, and webform. For further
information and updates on EPA Docket
Center services, please visit us online at
https://www.epa.gov/dockets. The EPA
continues to carefully and continuously
monitor information from the Center for
Disease Control, local area health
departments, and our Federal partners
so that we can respond rapidly as
conditions change regarding COVID–19.
FOR FURTHER INFORMATION CONTACT: For
questions about this final action, contact
Ms. Angie Carey, Sector Policies and
Programs Division (E143–01), Office of
Air Quality Planning and Standards,
U.S. Environmental Protection Agency,
Research Triangle Park, North Carolina
27711; telephone number: (919) 541–
2187; fax number: (919) 541–0516; and
email address: carey.angela@epa.gov.
SUPPLEMENTARY INFORMATION: Preamble
acronyms and abbreviations. We use
multiple acronyms and terms in this
preamble. While this list may not be
exhaustive, to ease the reading of this
preamble and for reference purposes,
the EPA defines the following terms and
acronyms here:
AMEL alternative means of emission
limitation
CAA Clean Air Act
CFR Code of Federal Regulations
PO 00000
Frm 00090
Fmt 4703
Sfmt 4703
EPA Environmental Protection Agency
HAP hazardous air pollutant(s)
NESHAP national emission standards
for hazardous air pollutants
NSPS new source performance
standards
OAQPS Office of Air Quality Planning
and Standards
PRD pressure relief device
PRV pressure relief valve
VAM vinyl acetate monomer
VOC volatile organic compound(s)
Organization of this document. The
information in this document is
organized as follows:
I. Background
II. Summary of Public Comments on the
AMEL Request
III. AMEL for the Storage Tank
I. Background
On February 8, 2021, the EPA
provided public notice and solicited
comment on the request under section
111(h)(3) of the CAA by Rohm and Haas
for an alternative means of emission
limitation (AMEL) for the Standards of
Performance for Volatile Organic Liquid
Storage Vessels, 40 CFR part 60 subpart
Kb, 40 CFR 60.112b, that would apply
to a proposed new vinyl acetate bulk
storage tank to be used at its chemical
plant in Kankakee, Illinois (see 86 FR
8618). The volatile organic compound
(VOC) standards at 40 CFR 60.112b were
established as work practice standards
pursuant to CAA section 111(h)(1). For
standards established according to that
provision, CAA section 111(h)(3) allows
the EPA to permit the use of an AMEL
by a source if, after notice and
opportunity for public hearing, it is
established to the Administrator’s
satisfaction that such AMEL will
achieve emissions reductions at least
equivalent to the reductions required
under the applicable CAA section
111(h)(1) standards. NSPS subpart Kb
also includes specific regulatory
provisions (i.e., 40 CFR 114b) allowing
sources to request an AMEL for the VOC
standards at 40 CFR 60.112b.
In the initial notice, the EPA solicited
comment on all aspects of the AMEL
request, including the operating
conditions specified in that document
that are necessary to achieve a reduction
in emissions of volatile organic
compounds at least equivalent to the
reductions required by 40 CFR 60.112b.
Rohm and Haas intends to replace the
existing vinyl acetate monomer (VAM)
(CAS 108–05–4) tank (TK–72) with the
proposed bulk storage tank.
Rohm and Haas included in its AMEL
application information to demonstrate
that the proposed bulk storage tank,
through its vapor balancing system and
E:\FR\FM\19JYN1.SGM
19JYN1
Federal Register / Vol. 86, No. 135 / Monday, July 19, 2021 / Notices
pressure containment design, will
achieve a reduction in emissions at least
equivalent to the reduction in emissions
achieved by the VOC standards at 40
CFR 60.112b. Rohm and Haas’s AMEL
request was submitted on June 17, 2020.
For Rohm and Haas’s AMEL request,
including any supporting materials
Rohm and Haas submitted, see Docket
ID No. EPA–HQ–OAR–2020–0599.
This action finalizes our approval of
this AMEL request. Section II
summarizes the comments received on
the request and our responses thereto.
Section III sets forth the final operating
conditions EPA has established for the
proposed bulk storage tank as part of
this AMEL approval.
lotter on DSK11XQN23PROD with NOTICES1
II. Summary of Public Comments on the
AMEL Request
The Agency received comments from
only one commenter (Rohm and Haas)
on this action. The comments pertain to
the operating conditions for assuring
equivalency that were specified section
III of the initial notice. The comments
and our response thereto are
summarized below.
A. Comment on Paragraph (3)—EPA
Method 21 Monitoring Requirements
Paragraph 3 of the operating
conditions in the initial notice stated
that at the Rohm and Haas facility, each
of the PRDs and components of the
vapor collection system on the tank
must be monitored on a quarterly basis,
using EPA Method 21, and that an
instrument reading of 500 parts-permillion by volume or greater is an
excess emission event.
Rohm and Haas requests that EPA
classify an instrument reading of ≥500
ppmv as a leak instead of an excess
emission event, thereby following the
National Emission Standards for
Organic Hazardous Air Pollutants
(NESHAP) from the Synthetic Organic
Chemical Manufacturing Industry for
Process Vents, Storage Vessels, Transfer
Operations, and Wastewater, 40 CFR
part 63, subpart G. As mentioned in the
initial notice, in support of its AMEL
request, Rohm and Haas stated that the
proposed tank would comply with the
vapor balancing requirements in
NESHAP subpart G, 40 CFR 63.119(g) to
confirm proper vapor balancing. See 86
FR 8618 (February 8, 2021). 40 CFR
63.119(g)(5) identifies an instrument
reading of ≥500 ppmv as a leak, which
triggers a requirement to repair as soon
as practicable but no later than 5 days
after detection. Rohm and Haas states in
its comment that this change would be
consistent with 40 CFR 63.119(g).
The Agency declines to adopt this
suggested revision for the following
VerDate Sep<11>2014
18:23 Jul 16, 2021
Jkt 253001
reason. The EPA equivalency
determination is based on the closed
vent system being closed and not
leaking under any circumstances. To
ensure equivalency, the Agency is
requiring that no detectable emissions
occur from PRDs and components of the
vapor collection system on the tank;
accordingly, any leak would be an
excess emission. Therefore, the EPA has
not made the change requested by the
commenter.
B. Comment on Paragraph (4)—
Clarification on Welded Steel Piping
Rohm and Haas’s second comment
requests clarification on paragraph 4 of
the operating conditions in the initial
document, specifically the requirement
that ‘‘VAM must be transferred from
either railcars or truck trailers via
welded steel piping into the new bulk
storage tank. The tank must be equipped
with a welded steel vapor balance line
that returns displaced vinyl acetate
vapors from the headspace within the
tank to the railcar or tank truck during
tank filling operations.’’
Rohm and Haas states that they intend
for the piping to be welded steel piping
but notes that there will be a minimal
number of necessary flanged
connections, flanged valves, and flexible
coupling lines for the unloading line
and for the vapor balance line. The
Agency does not believe, and Rohm and
Hass do not claim, that the operating
conditions in paragraph 4 cannot be met
or otherwise need to be changed
because of the presence of these flanged
connections, flanged valves, and flexible
coupling lines. The EPA is therefore
finalizing the requirements in paragraph
4 as specified in the initial notice, and
we are adding a statement in the
paragraph acknowledging that ‘‘there
will be a number of necessary flanged
connections, flanged valves, and flexible
coupling lines as part of the vapor
balance line.’’
C. Comment on Paragraph (6)—
Recordkeeping Requirements
Rohm and Haas’s next comment is on
paragraph 6 of the operating conditions
in the initial notice, which states that,
‘‘The facility must keep a record of the
equipment to be used and the
procedures to be followed when
reloading the railcar, tank truck, or
barge and displacing vapors the storage
tank from which the liquid originates, as
well as a record of all components of the
PRDs, including PRVs and rupture
discs.’’
Rohm and Haas’s comment identifies
certain inaccuracies in paragraph 6 in
the initial notice. For example, the
statement incorrectly uses the term
PO 00000
Frm 00091
Fmt 4703
Sfmt 4703
38077
‘‘reloading’’ in describing the operation
of unloading vinyl acetate from a railcar
or tank truck. Rohm and Haas also
suggest removing the reference to a
barge because it is not possible to
unload a barge at this facility. In light
of the above, we accept Rohm and
Haas’s suggestion to revise the statement
to read as follows: ‘‘The facility must
keep a record of the equipment to be
used and the procedures to be followed
when unloading the railcar or tank truck
and displacing vapors from the storage
tank to the transport vessel from which
the liquid originates, as well as a record
of all components of the PRDs,
including PRVs and rupture discs.’’
C. Comments on Paragraph (7)—
Reporting Requirements
Rohm and Haas suggest, and the
Agency accepts, minor wording changes
to paragraph 7(a) of the operating
conditions in the initial notice.
Rohm and Haas also suggests several
edits to paragraph 7(b), which requires
the facility to report ‘‘The date and time
identifying each period during which
the continuous monitoring systems were
inoperative except for zero and span
checks and the nature of the system
repairs or adjustments.’’ Rohm and Haas
requests adding the terms ‘‘pressure’’
and ‘‘other required maintenance’’ such
that the requirement would read as
follows: ‘‘The date and time identifying
each period during which the
continuous pressure monitoring systems
were inoperative except for zero and
span checks or other required
maintenance and the nature of the
system repairs or adjustments.’’ The
Agency disagrees with adding the term
‘‘other required maintenance’’ because it
is important to include reporting of
downtime in monitoring to understand
system upsets, and adding the term
‘‘other required maintenance’’ would
limit reporting to only periods of
required maintenance, thus excluding
downtime. However, the Agency does
agree with the change to add the term
‘‘pressure’’ to specifically refer to the
‘‘continuous pressure monitoring
system.’’ This edit accurately reflects
paragraph 2 of the operating conditions
below and in the initial notice to only
require pressure to be monitored.
Lastly, Rohm and Haas suggests
adding ‘‘in this section’’ to Paragraph
7(d) so that it reads: ‘‘When the
continuous pressure monitoring systems
have not been inoperative, repaired, or
adjusted, such information shall be
stated in this section of the report.’’ The
Agency interprets the comment to
request that the information required in
paragraph 7(d) be reported in the storage
tank section of semiannual compliance
E:\FR\FM\19JYN1.SGM
19JYN1
38078
Federal Register / Vol. 86, No. 135 / Monday, July 19, 2021 / Notices
lotter on DSK11XQN23PROD with NOTICES1
reports for this facility. The Agency
does not object to making this addition.
III. AMEL for the Storage Tank
The EPA is approving the AMEL
request by Rohm and Haas. Based upon
our review of the AMEL request, the
Agency believes that, by complying
with the operating conditions specified
in the following paragraphs, the
proposed new tank at the Rohm and
Haas Chemicals LLC facility will
achieve emission reductions at least
equivalent to reduction in emissions
required by NSPS subpart Kb, 40 CFR
60.112b:
(1) No PRD on the storage tank, or on
the railcar or tank truck, shall open
during loading or as a result of diurnal
temperature changes (breathing losses).
(2) Both PRDs on the storage tank
must be set to release at no less than 9
psig at all times. Any release from a PRD
as indicated by pressure reading greater
than 9 psig is an excess emissions event.
To demonstrate that the PRD does not
open, the tank vapor space pressure and
the space between the rupture disk and
PRD will be continuously monitored for
pressure and recorded. If a release
occurs, the tank must follow 40 CFR
63.165(d)(2).
(3) Each of the PRDs and components
of the vapor collection system on the
tank must be monitored on a quarterly
basis, using EPA Method 21. An
instrument reading of 500 parts per
million by volume or greater is an
excess emissions event.
(4) VAM must be transferred from
either railcars or truck trailers via
welded steel piping into the new bulk
storage tank. The tank must be equipped
with a welded steel vapor balance line
that returns displaced vinyl acetate
vapors from the headspace within the
tank to the railcar or tank truck during
tank filling operations. The vapor
balance line must be hard piped from
the tank, crossing a pipe bridge, before
terminating at the off-loading station.
While there are a number of necessary
flanged connections, flanged valves, and
flexible coupling lines as part of the
vapor balance line, the tank vapor
balance line must not contain any PRDs
or release points. Displaced vapors must
be transferred to a vapor return fitting
on the offloading bulk vehicle through
a hose from the offloading station. Both
the transfer hoses and the vapor balance
return line must incorporate drydisconnect fittings to prevent vapor
discharge to the atmosphere when the
line is not connected. Tank trucks and
railcars must have a current certification
in accordance with the DOT pressure
test requirements of 49 CFR part 180 for
tank trucks and 49 CFR 173.31 for
VerDate Sep<11>2014
18:23 Jul 16, 2021
Jkt 253001
railcars. Railcars or tank trucks that
deliver VAM to a storage tank must be
reloaded or cleaned at a facility that
utilizes the control techniques specified
in paragraph (4)(a) or (b).
(a) The railcar or tank truck must be
connected to a closed-vent system with
a control device that reduces inlet
emissions of VAM by 95 percent by
weight or greater.
(b) A vapor balancing system
designed and operated to collect organic
VAM vapor displaced from the tank
truck or railcar during reloading must be
used to route the collected HAP vapor
to the storage tank from which the
liquid being transferred originated.
(5) Rohm and Haas must submit to the
Administrator a written certification
that the reloading or cleaning facility
meets the requirements of paragraph 4;
and the requirements for closed vent
system and control device specified at
40 CFR 63.119 through 63.123. The
notification and reporting requirements
at 40 CFR 63.122 do not apply to the
owner or operator of the offsite cleaning
or reloading facility.
(6) Recordkeeping requirements.
(a) The facility must keep a record of
the equipment to be used and the
procedures to be followed when
unloading the railcar or tank truck and
displacing vapors from the storage tank
to the transport vessel from which the
liquid originates, as well as a record of
all components of the PRDs, including
PRVs and rupture discs.
(b) Records must be kept as long as
the storage vessel is in operation.
(7) Reporting requirements. The
facility must submit excess emissions
and monitoring systems performance
reports to the Administrator
semiannually. All reports must be
postmarked by the 30th day following
the end of each 6-month period. Written
reports of excess emissions must
include the following information:
(a) The date and time of
commencement and completion of each
time period of excess emissions and the
process operating time during the
reporting period.
(b) The date and time identifying each
period during which the continuous
pressure monitoring system was
inoperative except for zero and span
checks and the nature of the system
repairs or adjustments.
(c) The report must include a list of
the affected sources or equipment, an
estimate of the volume of VAM emitted,
and a description of the method used to
estimate the emissions.
(d) When the continuous pressure
monitoring systems have not been
inoperative, repaired, or adjusted, such
PO 00000
Frm 00092
Fmt 4703
Sfmt 4703
information shall be stated in this
section of the report.
Dated: July 13, 2021.
Panagiotis Tsirigotis,
Director, Office of Air Quality Planning and
Standards.
[FR Doc. 2021–15321 Filed 7–16–21; 8:45 am]
BILLING CODE 6560–50–P
ENVIRONMENTAL PROTECTION
AGENCY
[FRL 8718–01–R5]
Public Water System Supervision
Program Approval for the State of
Wisconsin
Environmental Protection
Agency (EPA).
ACTION: Notice of tentative approval.
AGENCY:
Notice is hereby given that
the Environmental Protection Agency
(EPA) has tentatively approved the State
of Wisconsin’s revisions to the State’s
Public Water System Supervision
(PWSS) Program under the federal Safe
Drinking Water Act (SDWA) for
adoption of the federal Ground Water
Rule, as well as revisions to the federal
Surface Water Treatment Rule under the
Long Term 2 Enhanced Surface Water
Treatment Rule. The EPA has
determined that the State’s PWSS
program regulations and the revisions
thereto are no less stringent than the
corresponding federal regulations for
the Ground Water Rule and the Long
Term 2 Enhanced Surface Water
Treatment Rule. Therefore, the EPA
intends to approve this revision to the
State of Wisconsin’s Public Water
System Supervision Program, thereby
giving the Wisconsin Department of
Natural Resources primary enforcement
responsibility for the Ground Water
Rule and the Long Term 2 Enhanced
Surface Water Treatment Rule. This
approval action does not extend to
public water systems in Indian Country.
By approving this revision, the EPA
does not intend to affect the rights of
federally recognized Indian Tribes in
Wisconsin, nor does it intend to limit
existing rights of the State of Wisconsin.
DATES: Any interested party may request
a public hearing on this determination.
A request for a public hearing must be
submitted by August 18, 2021. The EPA
Region 5 Administrator may deny
frivolous or insubstantial requests for a
hearing. If a substantial request for a
public hearing is made by August 18,
2021, EPA Region 5 will hold a public
hearing, and a notice of such hearing
will be published in the Federal
Register and a newspaper of general
SUMMARY:
E:\FR\FM\19JYN1.SGM
19JYN1
Agencies
[Federal Register Volume 86, Number 135 (Monday, July 19, 2021)]
[Notices]
[Pages 38076-38078]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2021-15321]
-----------------------------------------------------------------------
ENVIRONMENTAL PROTECTION AGENCY
[EPA-HQ-OAR-2020-0599; FRL-8194-02-OAR]
Notice of Final Approval for an Alternative Means of Emission
Limitation
AGENCY: Environmental Protection Agency (EPA).
ACTION: Notice; final approval.
-----------------------------------------------------------------------
SUMMARY: This action announces the Environmental Protection Agency
(EPA) approval of the request by Rohm and Haas Chemicals LLC, a
subsidiary of The Rohm and Haas Chemical Company (Rohm and Haas), under
the Clean Air Act (CAA) for an alternative means of emission limitation
(AMEL) for the Standards of Performance for Volatile Organic Liquid
Storage Vessels. The AMEL applies to a proposed new vinyl acetate bulk
storage tank to be used at its chemical plant in Kankakee, Illinois.
The EPA received no adverse comments on the request. This approval
document specifies the operating conditions and monitoring,
recordkeeping, and reporting requirements that this facility must
follow to demonstrate compliance with the approved AMEL.
DATES: The approval of the AMEL request from Rohm and Haas to operate
its storage tank in Kankakee, Illinois, as specified in this document,
is effective on July 19, 2021.
ADDRESSES: The EPA has established a docket for this action under
Docket ID No. EPA-HQ-OAR-2020-0599. All documents in the docket are
listed on the https://www.regulations.gov/ website. Although listed,
some information is not publicly available, e.g., Confidential Business
Information or other information whose disclosure is restricted by
statute. Certain other material, such as copyrighted material, is not
placed on the internet and will be publicly available only in hard copy
form. Publicly available docket materials are available either
electronically through https://www.regulations.gov/.
Out of an abundance of caution for members of the public and our
staff, the EPA Docket Center and Reading Room are closed to the public,
with limited exceptions, to reduce the risk of transmitting COVID-19.
Our Docket Center staff will continue to provide remote customer
service via email, phone, and webform. For further information and
updates on EPA Docket Center services, please visit us online at
https://www.epa.gov/dockets. The EPA continues to carefully and
continuously monitor information from the Center for Disease Control,
local area health departments, and our Federal partners so that we can
respond rapidly as conditions change regarding COVID-19.
FOR FURTHER INFORMATION CONTACT: For questions about this final action,
contact Ms. Angie Carey, Sector Policies and Programs Division (E143-
01), Office of Air Quality Planning and Standards, U.S. Environmental
Protection Agency, Research Triangle Park, North Carolina 27711;
telephone number: (919) 541-2187; fax number: (919) 541-0516; and email
address: [email protected].
SUPPLEMENTARY INFORMATION: Preamble acronyms and abbreviations. We use
multiple acronyms and terms in this preamble. While this list may not
be exhaustive, to ease the reading of this preamble and for reference
purposes, the EPA defines the following terms and acronyms here:
AMEL alternative means of emission limitation
CAA Clean Air Act
CFR Code of Federal Regulations
EPA Environmental Protection Agency
HAP hazardous air pollutant(s)
NESHAP national emission standards for hazardous air pollutants
NSPS new source performance standards
OAQPS Office of Air Quality Planning and Standards
PRD pressure relief device
PRV pressure relief valve
VAM vinyl acetate monomer
VOC volatile organic compound(s)
Organization of this document. The information in this document is
organized as follows:
I. Background
II. Summary of Public Comments on the AMEL Request
III. AMEL for the Storage Tank
I. Background
On February 8, 2021, the EPA provided public notice and solicited
comment on the request under section 111(h)(3) of the CAA by Rohm and
Haas for an alternative means of emission limitation (AMEL) for the
Standards of Performance for Volatile Organic Liquid Storage Vessels,
40 CFR part 60 subpart Kb, 40 CFR 60.112b, that would apply to a
proposed new vinyl acetate bulk storage tank to be used at its chemical
plant in Kankakee, Illinois (see 86 FR 8618). The volatile organic
compound (VOC) standards at 40 CFR 60.112b were established as work
practice standards pursuant to CAA section 111(h)(1). For standards
established according to that provision, CAA section 111(h)(3) allows
the EPA to permit the use of an AMEL by a source if, after notice and
opportunity for public hearing, it is established to the
Administrator's satisfaction that such AMEL will achieve emissions
reductions at least equivalent to the reductions required under the
applicable CAA section 111(h)(1) standards. NSPS subpart Kb also
includes specific regulatory provisions (i.e., 40 CFR 114b) allowing
sources to request an AMEL for the VOC standards at 40 CFR 60.112b.
In the initial notice, the EPA solicited comment on all aspects of
the AMEL request, including the operating conditions specified in that
document that are necessary to achieve a reduction in emissions of
volatile organic compounds at least equivalent to the reductions
required by 40 CFR 60.112b. Rohm and Haas intends to replace the
existing vinyl acetate monomer (VAM) (CAS 108-05-4) tank (TK-72) with
the proposed bulk storage tank.
Rohm and Haas included in its AMEL application information to
demonstrate that the proposed bulk storage tank, through its vapor
balancing system and
[[Page 38077]]
pressure containment design, will achieve a reduction in emissions at
least equivalent to the reduction in emissions achieved by the VOC
standards at 40 CFR 60.112b. Rohm and Haas's AMEL request was submitted
on June 17, 2020. For Rohm and Haas's AMEL request, including any
supporting materials Rohm and Haas submitted, see Docket ID No. EPA-HQ-
OAR-2020-0599.
This action finalizes our approval of this AMEL request. Section II
summarizes the comments received on the request and our responses
thereto. Section III sets forth the final operating conditions EPA has
established for the proposed bulk storage tank as part of this AMEL
approval.
II. Summary of Public Comments on the AMEL Request
The Agency received comments from only one commenter (Rohm and
Haas) on this action. The comments pertain to the operating conditions
for assuring equivalency that were specified section III of the initial
notice. The comments and our response thereto are summarized below.
A. Comment on Paragraph (3)--EPA Method 21 Monitoring Requirements
Paragraph 3 of the operating conditions in the initial notice
stated that at the Rohm and Haas facility, each of the PRDs and
components of the vapor collection system on the tank must be monitored
on a quarterly basis, using EPA Method 21, and that an instrument
reading of 500 parts-per-million by volume or greater is an excess
emission event.
Rohm and Haas requests that EPA classify an instrument reading of
>=500 ppmv as a leak instead of an excess emission event, thereby
following the National Emission Standards for Organic Hazardous Air
Pollutants (NESHAP) from the Synthetic Organic Chemical Manufacturing
Industry for Process Vents, Storage Vessels, Transfer Operations, and
Wastewater, 40 CFR part 63, subpart G. As mentioned in the initial
notice, in support of its AMEL request, Rohm and Haas stated that the
proposed tank would comply with the vapor balancing requirements in
NESHAP subpart G, 40 CFR 63.119(g) to confirm proper vapor balancing.
See 86 FR 8618 (February 8, 2021). 40 CFR 63.119(g)(5) identifies an
instrument reading of >=500 ppmv as a leak, which triggers a
requirement to repair as soon as practicable but no later than 5 days
after detection. Rohm and Haas states in its comment that this change
would be consistent with 40 CFR 63.119(g).
The Agency declines to adopt this suggested revision for the
following reason. The EPA equivalency determination is based on the
closed vent system being closed and not leaking under any
circumstances. To ensure equivalency, the Agency is requiring that no
detectable emissions occur from PRDs and components of the vapor
collection system on the tank; accordingly, any leak would be an excess
emission. Therefore, the EPA has not made the change requested by the
commenter.
B. Comment on Paragraph (4)--Clarification on Welded Steel Piping
Rohm and Haas's second comment requests clarification on paragraph
4 of the operating conditions in the initial document, specifically the
requirement that ``VAM must be transferred from either railcars or
truck trailers via welded steel piping into the new bulk storage tank.
The tank must be equipped with a welded steel vapor balance line that
returns displaced vinyl acetate vapors from the headspace within the
tank to the railcar or tank truck during tank filling operations.''
Rohm and Haas states that they intend for the piping to be welded
steel piping but notes that there will be a minimal number of necessary
flanged connections, flanged valves, and flexible coupling lines for
the unloading line and for the vapor balance line. The Agency does not
believe, and Rohm and Hass do not claim, that the operating conditions
in paragraph 4 cannot be met or otherwise need to be changed because of
the presence of these flanged connections, flanged valves, and flexible
coupling lines. The EPA is therefore finalizing the requirements in
paragraph 4 as specified in the initial notice, and we are adding a
statement in the paragraph acknowledging that ``there will be a number
of necessary flanged connections, flanged valves, and flexible coupling
lines as part of the vapor balance line.''
C. Comment on Paragraph (6)--Recordkeeping Requirements
Rohm and Haas's next comment is on paragraph 6 of the operating
conditions in the initial notice, which states that, ``The facility
must keep a record of the equipment to be used and the procedures to be
followed when reloading the railcar, tank truck, or barge and
displacing vapors the storage tank from which the liquid originates, as
well as a record of all components of the PRDs, including PRVs and
rupture discs.''
Rohm and Haas's comment identifies certain inaccuracies in
paragraph 6 in the initial notice. For example, the statement
incorrectly uses the term ``reloading'' in describing the operation of
unloading vinyl acetate from a railcar or tank truck. Rohm and Haas
also suggest removing the reference to a barge because it is not
possible to unload a barge at this facility. In light of the above, we
accept Rohm and Haas's suggestion to revise the statement to read as
follows: ``The facility must keep a record of the equipment to be used
and the procedures to be followed when unloading the railcar or tank
truck and displacing vapors from the storage tank to the transport
vessel from which the liquid originates, as well as a record of all
components of the PRDs, including PRVs and rupture discs.''
C. Comments on Paragraph (7)--Reporting Requirements
Rohm and Haas suggest, and the Agency accepts, minor wording
changes to paragraph 7(a) of the operating conditions in the initial
notice.
Rohm and Haas also suggests several edits to paragraph 7(b), which
requires the facility to report ``The date and time identifying each
period during which the continuous monitoring systems were inoperative
except for zero and span checks and the nature of the system repairs or
adjustments.'' Rohm and Haas requests adding the terms ``pressure'' and
``other required maintenance'' such that the requirement would read as
follows: ``The date and time identifying each period during which the
continuous pressure monitoring systems were inoperative except for zero
and span checks or other required maintenance and the nature of the
system repairs or adjustments.'' The Agency disagrees with adding the
term ``other required maintenance'' because it is important to include
reporting of downtime in monitoring to understand system upsets, and
adding the term ``other required maintenance'' would limit reporting to
only periods of required maintenance, thus excluding downtime. However,
the Agency does agree with the change to add the term ``pressure'' to
specifically refer to the ``continuous pressure monitoring system.''
This edit accurately reflects paragraph 2 of the operating conditions
below and in the initial notice to only require pressure to be
monitored.
Lastly, Rohm and Haas suggests adding ``in this section'' to
Paragraph 7(d) so that it reads: ``When the continuous pressure
monitoring systems have not been inoperative, repaired, or adjusted,
such information shall be stated in this section of the report.'' The
Agency interprets the comment to request that the information required
in paragraph 7(d) be reported in the storage tank section of semiannual
compliance
[[Page 38078]]
reports for this facility. The Agency does not object to making this
addition.
III. AMEL for the Storage Tank
The EPA is approving the AMEL request by Rohm and Haas. Based upon
our review of the AMEL request, the Agency believes that, by complying
with the operating conditions specified in the following paragraphs,
the proposed new tank at the Rohm and Haas Chemicals LLC facility will
achieve emission reductions at least equivalent to reduction in
emissions required by NSPS subpart Kb, 40 CFR 60.112b:
(1) No PRD on the storage tank, or on the railcar or tank truck,
shall open during loading or as a result of diurnal temperature changes
(breathing losses).
(2) Both PRDs on the storage tank must be set to release at no less
than 9 psig at all times. Any release from a PRD as indicated by
pressure reading greater than 9 psig is an excess emissions event. To
demonstrate that the PRD does not open, the tank vapor space pressure
and the space between the rupture disk and PRD will be continuously
monitored for pressure and recorded. If a release occurs, the tank must
follow 40 CFR 63.165(d)(2).
(3) Each of the PRDs and components of the vapor collection system
on the tank must be monitored on a quarterly basis, using EPA Method
21. An instrument reading of 500 parts per million by volume or greater
is an excess emissions event.
(4) VAM must be transferred from either railcars or truck trailers
via welded steel piping into the new bulk storage tank. The tank must
be equipped with a welded steel vapor balance line that returns
displaced vinyl acetate vapors from the headspace within the tank to
the railcar or tank truck during tank filling operations. The vapor
balance line must be hard piped from the tank, crossing a pipe bridge,
before terminating at the off-loading station. While there are a number
of necessary flanged connections, flanged valves, and flexible coupling
lines as part of the vapor balance line, the tank vapor balance line
must not contain any PRDs or release points. Displaced vapors must be
transferred to a vapor return fitting on the offloading bulk vehicle
through a hose from the offloading station. Both the transfer hoses and
the vapor balance return line must incorporate dry-disconnect fittings
to prevent vapor discharge to the atmosphere when the line is not
connected. Tank trucks and railcars must have a current certification
in accordance with the DOT pressure test requirements of 49 CFR part
180 for tank trucks and 49 CFR 173.31 for railcars. Railcars or tank
trucks that deliver VAM to a storage tank must be reloaded or cleaned
at a facility that utilizes the control techniques specified in
paragraph (4)(a) or (b).
(a) The railcar or tank truck must be connected to a closed-vent
system with a control device that reduces inlet emissions of VAM by 95
percent by weight or greater.
(b) A vapor balancing system designed and operated to collect
organic VAM vapor displaced from the tank truck or railcar during
reloading must be used to route the collected HAP vapor to the storage
tank from which the liquid being transferred originated.
(5) Rohm and Haas must submit to the Administrator a written
certification that the reloading or cleaning facility meets the
requirements of paragraph 4; and the requirements for closed vent
system and control device specified at 40 CFR 63.119 through 63.123.
The notification and reporting requirements at 40 CFR 63.122 do not
apply to the owner or operator of the offsite cleaning or reloading
facility.
(6) Recordkeeping requirements.
(a) The facility must keep a record of the equipment to be used and
the procedures to be followed when unloading the railcar or tank truck
and displacing vapors from the storage tank to the transport vessel
from which the liquid originates, as well as a record of all components
of the PRDs, including PRVs and rupture discs.
(b) Records must be kept as long as the storage vessel is in
operation.
(7) Reporting requirements. The facility must submit excess
emissions and monitoring systems performance reports to the
Administrator semiannually. All reports must be postmarked by the 30th
day following the end of each 6-month period. Written reports of excess
emissions must include the following information:
(a) The date and time of commencement and completion of each time
period of excess emissions and the process operating time during the
reporting period.
(b) The date and time identifying each period during which the
continuous pressure monitoring system was inoperative except for zero
and span checks and the nature of the system repairs or adjustments.
(c) The report must include a list of the affected sources or
equipment, an estimate of the volume of VAM emitted, and a description
of the method used to estimate the emissions.
(d) When the continuous pressure monitoring systems have not been
inoperative, repaired, or adjusted, such information shall be stated in
this section of the report.
Dated: July 13, 2021.
Panagiotis Tsirigotis,
Director, Office of Air Quality Planning and Standards.