Energy Conservation Program: Notification of Petition for Waiver of GD Midea Air Conditioning Equipment Co. LTD From the Department of Energy Portable Air Conditioner Test Procedure and Notification of Grant of Interim Waiver, 17803-17821 [2021-07025]
Download as PDF
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
khammond on DSKJM1Z7X2PROD with NOTICES
For the reasons explained here and in
the Notification of Petition for Waiver,
absent a waiver the basic models
identified by Hercules in its petition
cannot be tested and rated for energy
consumption on a basis representative
of their true energy consumption
characteristics. DOE has reviewed the
recommended procedure suggested by
Hercules and concludes that it will
allow for the accurate measurement of
the energy use of the equipment, while
alleviating the testing issues associated
with Hercules’s implementation of
DOE’s applicable walk-in door test
procedure for the specified basic
models.
Thus, DOE is requiring that Hercules
test and rate specified walk-in door
basic models according to the alternate
test procedure specified in this Decision
and Order, which is identical to the
procedure provided in the interim
waiver.
This Decision and Order is applicable
only to the basic models listed and does
not extend to any other basic models.
DOE evaluates and grants waivers for
only those basic models specifically set
out in the petition, not future models
that may be manufactured by the
petitioner. Hercules may request that
DOE extend the scope of this waiver to
include additional basic models that
employ the same technology as those
listed in this waiver. 10 CFR 431.401(g).
Hercules may also submit another
petition for waiver from the test
procedure for additional basic models
that employ a different technology and
meet the criteria for test procedure
waivers. 10 CFR 431.401(a)(1).
DOE notes that it may modify or
rescind the waiver at any time upon
DOE’s determination that the factual
basis underlying the petition for waiver
is incorrect, or upon a determination
that the results from the alternate test
procedure are unrepresentative of the
basic models’ true energy consumption
characteristics. 10 CFR 431.401(k)(1).
Likewise, Hercules may request that
DOE rescind or modify the waiver if the
company discovers an error in the
information provided to DOE as part of
its petition, determines that the waiver
is no longer needed, or for other
appropriate reasons. 10 CFR
431.401(k)(2).
III. Order
After careful consideration of all the
material that was submitted by
Hercules, the various public-facing
materials (e.g., product literature,
installation manuals) for the units
identified in the petition, in this matter,
it is ordered that:
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
(1) Hercules must, as of the date of
publication of this Order in the Federal
Register, test and rate the basic models
listed in Appendix I of its October 14,
2020 petition as provided in Docket
Number EERE–2020–BT–WAV–0027–
0002 with the alternate test procedure as
set forth in paragraph (2):
(2) The alternate test procedure for the
Hercules basic models identified in
paragraph (1) of this Order is the test
procedure for walk-in doors prescribed
by DOE at 10 CFR part 431, subpart R,
appendix A, except that the PTO value
specified in section 4.5.2 ‘‘Direct Energy
Consumption of Electrical Components
of Non-Display Doors’’ shall be 92
percent for door motors. All other
requirements of 10 CFR part 431,
subpart R, appendix A and DOE’s
regulations remain applicable.
(3) Representations. Hercules may not
make representations about the energy
use of a basic model listed in paragraph
(1) of this Order for compliance or
marketing, unless the basic model has
been tested in accordance with the
provisions set forth above and such
representations fairly disclose the
results of such testing.
(4) This waiver shall remain in effect
according to the provisions of 10 CFR
431.401.
(5) DOE issues this waiver on the
condition that the statements,
representations, and information
provided by Hercules are valid. If
Hercules makes any modifications to the
controls or configurations of these basic
models, such modifications will render
the waiver invalid with respect to that
basic model, and Hercules will either be
required to use the current Federal test
method or submit a new application for
a test procedure waiver. DOE may
rescind or modify this waiver at any
time if it determines the factual basis
underlying the petition for waiver is
incorrect, or the results from the
alternate test procedure are
unrepresentative of a basic model’s true
energy consumption characteristics. 10
CFR 431.401(k)(1). Likewise, Hercules
may request that DOE rescind or modify
the waiver if Hercules discovers an error
in the information provided to DOE as
part of its petition, determines that the
waiver is no longer needed, or for other
appropriate reasons. 10 CFR
431.401(k)(2).
(6) Hercules remains obligated to
fulfill all applicable requirements set
forth at 10 CFR part 429.
Signing Authority
This document of the Department of
Energy was signed on March 31, 2021
by Kelly J. Speakes-Backman, Principal
Deputy Assistant Secretary and Acting
PO 00000
Frm 00037
Fmt 4703
Sfmt 4703
17803
Assistant Secretary for Energy Efficiency
and Renewable Energy, pursuant to
delegated authority from the Secretary
of Energy. That document with the
original signature and date is
maintained by DOE. For administrative
purposes only, and in compliance with
requirements of the Office of the Federal
Register, the undersigned DOE Federal
Register Liaison Officer has been
authorized to sign and submit the
document in electronic format for
publication, as an official document of
the Department of Energy. This
administrative process in no way alters
the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on March 31,
2021.
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
[FR Doc. 2021–06991 Filed 4–5–21; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
[Case Number 2020–006; EERE–2020–BT–
WAV–0023]
Energy Conservation Program:
Notification of Petition for Waiver of
GD Midea Air Conditioning Equipment
Co. LTD From the Department of
Energy Portable Air Conditioner Test
Procedure and Notification of Grant of
Interim Waiver
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
ACTION: Notification of petition for
waiver and grant of an interim waiver;
request for comments.
AGENCY:
This notification announces
receipt of and publishes a petition for
waiver and interim waiver from GD
Midea Air Conditioning Equipment Co.
LTD (‘‘Midea’’), which seeks a waiver
for specified portable air conditioner
basic models from the U.S. Department
of Energy (‘‘DOE’’) test procedure used
for determining the efficiency of
portable air conditioners. DOE also
gives notice of an Interim Waiver Order
that requires Midea to test and rate the
specified portable air conditioner basic
models in accordance with the alternate
test procedure set forth in the Interim
Waiver Order. DOE solicits comments,
data, and information concerning
Midea’s petition and its suggested
alternate test procedure to inform DOE’s
final decision on Midea’s waiver
request.
SUMMARY:
The Interim Waiver Order is
effective on April 6, 2021. Written
DATES:
E:\FR\FM\06APN1.SGM
06APN1
khammond on DSKJM1Z7X2PROD with NOTICES
17804
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
comments and information are
requested and will be accepted on or
before May 6, 2021.
ADDRESSES: Interested persons are
encouraged to submit comments using
the Federal eRulemaking Portal at
https://www.regulations.gov.
Alternatively, interested persons may
submit comments, identified by case
number ‘‘2020–006’’, and Docket
number ‘‘EERE–2020–BT–WAV–0023,’’
by any of the following methods:
• Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments.
• Email: AS_Waiver_Requests@
ee.doe.gov. Include Case No. 2020–006
in the subject line of the message.
No telefacsimilies (‘‘faxes’’) will be
accepted. For detailed instructions on
submitting comments and additional
information on this process, see the
SUPPLEMENTARY INFORMATION section of
this document.
Although DOE has routinely accepted
public comment submissions through a
variety of mechanism, including the
Federal eRulemaking Portal, email,
postal mail, or hand delivery/courier,
the Department has found it necessary
to make temporary modifications to the
comment submission process in light of
the ongoing Covid–19 pandemic. DOE is
currently suspending receipt of public
comments via postal mail and hand
delivery/courier. If a commenter finds
that this change poses an undue
hardship, please contact Appliance
Standards Program staff at (202) 586–
1445 to discuss the need for alternative
arrangements. Once the Covid–19
pandemic health emergency is resolved,
DOE anticipates resuming all of its
regular options for public comment
submission, including postal mail and
hand delivery/courier.
Docket: The docket, which includes
Federal Register notices, comments,
and other supporting documents/
materials, is available for review at
https://www.regulations.gov. All
documents in the docket are listed in
the https://www.regulations.gov index.
However, some documents listed in the
index, such as those containing
information that is exempt from public
disclosure, may not be publicly
available.
The docket web page can be found at
https://www.regulations.gov/
docket?D=EERE-2020-BT-WAV-0023.
The docket web page contains
instruction on how to access all
documents, including public comments,
in the docket. See the SUPPLEMENTARY
INFORMATION section for information on
how to submit comments through
https://www.regulations.gov.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
FOR FURTHER INFORMATION CONTACT:
Ms. Lucy deButts, U.S. Department of
Energy, Office of Energy Efficiency and
Renewable Energy, Building
Technologies Office, Mailstop EE–5B,
1000 Independence Avenue SW,
Washington, DC 20585–0121. Email:
AS_Waiver_Request@ee.doe.gov.
Ms. Sarah Butler, U.S. Department of
Energy, Office of the General Counsel,
Mail Stop GC–33, Forrestal Building,
1000 Independence Avenue SW,
Washington, DC 20585–0103.
Telephone: (202) 586–1777. Email:
Sarah.Butler@hq.doe.gov.
SUPPLEMENTARY INFORMATION: DOE is
publishing Midea’s petition for waiver
in its entirety, pursuant to 10 CFR
430.27(b)(1)(iv),1 absent any
confidential business information. DOE
invites all interested parties to submit in
writing by May 6, 2021, comments and
information on all aspects of the
petition, including the alternate test
procedure. Pursuant to 10 CFR
430.27(d), any person submitting
written comments to DOE must also
send a copy of such comments to the
petitioner. The contact information for
the petitioner is Daniel L. Atkins,
daniel.atkins@midea.com, Midea
America Research Center, 2700
Chestnut Station Court, Louisville, KY
40299.
Submitting comments via https://
www.regulations.gov. The https://
www.regulations.gov web page will
require you to provide your name and
contact information. Your contact
information will be viewable to DOE
Building Technologies staff only. Your
contact information will not be publicly
viewable except for your first and last
names, organization name (if any), and
submitter representative name (if any).
If your comment is not processed
properly because of technical
difficulties, DOE will use this
information to contact you. If DOE
cannot read your comment due to
technical difficulties and cannot contact
you for clarification, DOE may not be
able to consider your comment.
However, your contact information
will be publicly viewable if you include
it in the comment or in any documents
attached to your comment. Any
information that you do not want to be
publicly viewable should not be
1 On December 11, 2020, DOE published an
amendment to 10 CFR 430.27 regarding the
processing of petitions for an interim waiver, which
became effective beginning January 11, 2021. 85 FR
79802. Midea’s petition for waiver and petition for
interim waiver were received prior to the effective
date of that amendment. The interim waiver
therefore is being processed pursuant to the
regulation in effect at the time of receipt, i.e., 10
CFR 430.27 in the 10 CFR parts 200 to 499 edition
revised as of January 1, 2020.
PO 00000
Frm 00038
Fmt 4703
Sfmt 4703
included in your comment, nor in any
document attached to your comment. If
this instruction is followed, persons
viewing comments will see only first
and last names, organization names,
correspondence containing comments,
and any documents submitted with the
comments.
Do not submit to https://
www.regulations.gov information for
which disclosure is restricted by statute,
such as trade secrets and commercial or
financial information (hereinafter
referred to as Confidential Business
Information (‘‘CBI’’)). Comments
submitted through https://
www.regulations.gov cannot be claimed
as CBI. Comments received through the
website will waive any CBI claims for
the information submitted. For
information on submitting CBI, see the
Confidential Business Information
section.
DOE processes submissions made
through https://www.regulations.gov
before posting. Normally, comments
will be posted within a few days of
being submitted. However, if large
volumes of comments are being
processed simultaneously, your
comment may not be viewable for up to
several weeks. Please keep the comment
tracking number that https://
www.regulations.gov provides after you
have successfully uploaded your
comment.
Submitting comments via email.
Comments and documents submitted
via email also will be posted to https://
www.regulations.gov. If you do not want
your personal contact information to be
publicly viewable, do not include it in
your comment or any accompanying
documents. Instead, provide your
contact information on a cover letter.
Include your first and last names, email
address, telephone number, and
optional mailing address. The cover
letter will not be publicly viewable as
long as it does not include any
comments.
Include contact information each time
you submit comments, data, documents,
and other information to DOE.
Comments, data, and other
information submitted to DOE
electronically should be provided in
PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file
format. Provide documents that are not
secured, written in English and free of
any defects or viruses. Documents
should not contain special characters or
any form of encryption and, if possible,
they should carry the electronic
signature of the author.
Campaign form letters. Please submit
campaign form letters by the originating
organization in batches of between 50 to
E:\FR\FM\06APN1.SGM
06APN1
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
500 form letters per PDF or as one form
letter with a list of supporters’ names
compiled into one or more PDFs. This
reduces comment processing and
posting time.
Confidential Business Information.
According to 10 CFR 1004.11, any
person submitting information that he
or she believe s to be confidential and
exempt by law from public disclosure
should submit via email two wellmarked copies: One copy of the
document marked confidential
including all the information believed to
be confidential, and one copy of the
document marked ‘‘non-confidential’’
with the information believed to be
confidential deleted. DOE will make its
own determination about the
confidential status of the information
and treat it according to its
determination.
It is DOE’s policy that all comments
may be included in the public docket,
without change and as received,
including any personal information
provided in the comments (except
information deemed to be exempt from
public disclosure).
Case Number 2020–006
khammond on DSKJM1Z7X2PROD with NOTICES
Interim Waiver Order
I. Background and Authority
The Energy Policy and Conservation
Act, as amended (‘‘EPCA’’),1 authorizes
the U.S. Department of Energy (‘‘DOE’’)
to regulate the energy efficiency of a
number of consumer products and
certain industrial equipment. (42 U.S.C.
6291–6317) Title III, Part B 2 of EPCA
established the Energy Conservation
Program for Consumer Products Other
Than Automobiles, which sets forth a
variety of provisions designed to
improve energy efficiency for certain
types of consumer products. In addition
to specifying a list of covered products
and industrial equipment, EPCA
contains provisions that enable the
Secretary of Energy to classify
additional types of consumer products
as covered products. (42 U.S.C.
6292(a)(20)) In a final determination of
coverage published in the Federal
Register on April 18, 2016, DOE
classified portable air conditioners as
covered products under EPCA. 81 FR
22514.
The energy conservation program
under EPCA consists essentially of four
parts: (1) Testing, (2) labeling, (3)
Federal energy conservation standards,
and (4) certification and enforcement
1 All references to EPCA in this document refer
to the statute as amended through the Energy Act
of 2020, Public Law 116–260 (Dec. 27, 2020).
2 For editorial reasons, upon codification in the
U.S. Code, Part B was redesignated as Part A.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
procedures. Relevant provisions of
EPCA include definitions (42 U.S.C.
6291), test procedures (42 U.S.C. 6293),
labeling provisions (42 U.S.C. 6294),
energy conservation standards (42
U.S.C. 6295), and the authority to
require information and reports from
manufacturers (42 U.S.C. 6296).
The Federal testing requirements
consist of test procedures that
manufacturers of covered products must
use as the basis for: (1) Certifying to
DOE that their products comply with
the applicable energy conservation
standards adopted pursuant to EPCA (42
U.S.C. 6295(s)), and (2) making
representations about the efficiency of
that product (42 U.S.C. 6293(c)).
Similarly, DOE must use these test
procedures to determine whether the
product complies with relevant
standards promulgated under EPCA. (42
U.S.C. 6295(s))
Under 42 U.S.C. 6293, EPCA sets forth
the criteria and procedures DOE is
required to follow when prescribing or
amending test procedures for covered
products. EPCA requires that any test
procedures prescribed or amended
under this section must be reasonably
designed to produce test results which
reflect the energy efficiency, energy use
or estimated annual operating cost of a
covered product during a representative
average use cycle or period of use and
requires that test procedures not be
unduly burdensome to conduct. (42
U.S.C.6293(b)(3)) The test procedure for
portable air conditioners is contained in
the Code of Federal Regulations (‘‘CFR’’)
at 10 CFR part 430, subpart B, appendix
CC (‘‘Appendix CC’’).
Under 10 CFR 430.27, any interested
person may submit a petition for waiver
from DOE’s test procedure
requirements. DOE will grant a waiver
from the test procedure requirements if
DOE determines either that the basic
model for which the waiver was
requested contains a design
characteristic that prevents testing of the
basic model according to the prescribed
test procedures, or that the prescribed
test procedures evaluate the basic model
in a manner so unrepresentative of its
true energy consumption characteristics
as to provide materially inaccurate
comparative data. 10 CFR 430.27(f)(2). A
petitioner must include in its petition
any alternate test procedures known to
the petitioner to evaluate the
performance of the product type in a
manner representative of the energy
consumption characteristics of the basic
model. 10 CFR 430.27(b)(1)(iii). DOE
may grant the waiver subject to
conditions, including adherence to
alternate test procedures. 10 CFR
430.27(f)(2).
PO 00000
Frm 00039
Fmt 4703
Sfmt 4703
17805
As soon as practicable after the
granting of any waiver, DOE will
publish in the Federal Register a notice
of proposed rulemaking to amend its
regulations to eliminate any need for the
continuation of such waiver. 10 CFR
430.27(l). As soon thereafter as
practicable, DOE will publish in the
Federal Register a final rule to that
effect. Id.
The waiver process also provides that
DOE may grant an interim waiver if it
appears likely that the underlying
petition for waiver will be granted and/
or if DOE determines that it would be
desirable for public policy reasons to
grant immediate relief pending a
determination on the underlying
petition for waiver. 10 CFR 430.27(e)(2).
Within one year of issuance of an
interim waiver, DOE will either: (i)
Publish in the Federal Register a
determination on the petition for
waiver; or (ii) publish in the Federal
Register a new or amended test
procedure that addresses the issues
presented in the waiver. 10 CFR
430.27(h).
When DOE amends the test procedure
to address the issues presented in a
waiver, the waiver will automatically
terminate on the date on which use of
that test procedure is required to
demonstrate compliance. Id.
II. Midea’s Petition for Waiver and
Interim Waiver
On June 29, 2020, Midea filed a
petition for waiver and petition for
interim waiver from the test procedure
for portable air conditioners set forth at
Appendix CC. (Midea, No. 1 at pp. 2–
3 3) On July 10, 2020, Midea submitted
a revised petition for waiver and
application for interim waiver.4 On
September 11, 2020, Midea submitted a
request 5 to include five additional basic
models in their petition for waiver and
petition for interim waiver. On
November 17, 2020, Midea submitted a
request 6 to include three additional
3 A notation in this form provides a reference for
information that is in the docket for this test
procedure waiver (Docket No. EERE–2020–BT–
WAV–0023) (available at https://
www.regulations.gov/docket/EERE-2020-BT-WAV0023). This notation indicates that the statement
preceding the reference is document number 1 in
the docket and appears at pages 2–3 of that
document.
4 The revised petition for waiver and application
for interim waiver is available at https://
www.regulations.gov/document?D=EERE-2020-BTWAV-0023-0002.
5 The request to include additional basic models
is available at https://www.regulations.gov/
document?D=EERE-2020-BT-WAV-0023-0003.
6 The request to include additional basic models
is available at https://www.regulations.gov/
document?D=EERE-2020-BT-WAV-0023-0004.
E:\FR\FM\06APN1.SGM
06APN1
17806
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
khammond on DSKJM1Z7X2PROD with NOTICES
basic models in their petition for waiver
and petition for interim waiver.7 The
current DOE test procedure at Appendix
CC tests dual-duct portable air
conditioners at two operating
conditions, one measuring performance
at a high outdoor operating temperature
and one measuring performance at a
lower outdoor operating temperature.
Midea asserts that this testing does not
address the ability of variable-speed
compressors to adjust their operating
speed based on the demand load of the
conditioned space. Because of this,
Midea indicated that the test procedure
does not take into account the full range
of performance and efficiency benefits
of a variable-speed compressor
operating under part-load conditions.
Midea cited DOE’s test procedure for
central air conditioners, which includes
part-load test conditions that account
for the improved efficiency benefit from
variable-speed compressors at 10 CFR
430 subpart B, appendix M1, section
3.2.4. Midea also referenced several
waivers; first were two test procedure
waivers for room air conditioners that
contain variable-speed compressors:
Midea’s, granted on May 26, 2020, and
LG Electronics Inc. (‘‘LG’’)’s, granted on
May 8, 2019. 85 FR 31481; 84 FR 20111.
Second was the portable air conditioner
waiver DOE granted to LG on June 2,
2020. That waiver includes part-load
test conditions to account for the
improved efficiency benefit from
variable-speed compressors. 85 FR
33643. Midea asserted that the basic
models listed in the petition cannot be
tested according to the test procedure at
Appendix CC because their condenser
inlet and outlet air streams are
incorporated into the same structure
7 The brand and basic model numbers specified
by Midea in its petition (including the September
11, 2020 and November 17, 2020 submissions) are:
Midea, US–KC35Y1/BP3N8–PTB(CH3); Midea, US–
KC30Y1/BP3N8–PTB(CG8); Perfect aire,
1PORTV10000; Danby, DPA100B9IWDB–6; Heat
Controller LLC, PSV–101D; Whynter, ARC–
1030WN; Whynter, ARC–1030BN; Whynter, ARC–
1030GN; hOme, HME020373N; Vremi,
VRM050703N; Wappliance, BPI10MW; Perfect aire,
1PORTVP10000; Danby, DPA100HB9IWDB–6; Heat
Controller LLC, PSHV–101D; Whynter, ARC–
1030WNH; Whynter, ARC–1030GNH; Whynter,
ARC–1030BNH; hOme, HME020374N; Vremi,
VRM050704N; Wappliance, BPI10HMW; Perfect
aire, 1PORTV12000; Danby, DPA120B9IWDB–6;
Heat Controller LLC, PSV–121D; Whynter, ARC–
1230WN; Whynter, ARC–1230BN; Whynter, ARC–
1230GN; hOme, HME020375N; Vremi,
VRM050705N; Wappliance, BPI12MW; Perfectaire,
1PORTVP12000; Danby, DPA120HB9IWDB–6; Heat
Controller LLC, PSHV–121D; Whynter, ARC–
1230WNH; Whynter, ARC–1230GNH; Whynter,
ARC–1230BNH; hOme, HME020376N; Vremi,
VRM050706N; Wappliance, BPI12HMW; Toshiba,
RAC–PT1411HWRU; Toshiba, RAC–PT1411CWRU;
Toshiba, RAC–PT1211CWRU; Danby,
DPA100HB9IBDB–6; Danby, DPA120B9IBDB–6;
Midea, MPPTB–12HRN8–BCH4; Midea, MPPTB–
12CRN8–BCH4; Midea, MPPTB–10CRN8–BCG8.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
using ‘‘combined-duct technology.’’
Midea stated that the test procedure
does not provide for measuring airflow
in and out of a single condenser duct at
the same time, as would be required for
units with a combined duct.
Midea also requested an interim
waiver from the existing DOE test
procedure. DOE will grant an interim
waiver if it appears likely that the
petition for waiver will be granted, and/
or if DOE determines that it would be
desirable for public policy reasons to
grant immediate relief pending a
determination of the petition for waiver.
10 CFR 430.27(e)(2).
Based on the assertions in the
petition, absent an interim waiver,
Midea’s specified portable air
conditioner basic models contain design
characteristics which prevent testing of
the basic model according to the
prescribed test procedures and cause the
prescribed test procedures to be tested
in a manner that is unrepresentative of
their actual efficiency.
III. Requested Alternate Test Procedure
EPCA requires that manufacturers use
DOE test procedures when making
representations about the energy
consumption and energy consumption
costs of covered products. (42 U.S.C.
6293(c)) Consistency is important when
making representations about the energy
efficiency of covered products,
including when demonstrating
compliance with applicable DOE energy
conservation standards. Pursuant to 10
CFR 430.27, and after consideration of
public comments on the petition, DOE
may establish in a subsequent Decision
and Order an alternate test procedure
for the basic models addressed by the
Interim Waiver Order.
Midea seeks to use an alternate test
procedure to test and rate specific
portable air conditioner basic models.
The alternate test procedure is the test
procedure for portable air conditioners
prescribed by DOE in Appendix CC,
with the combined-duct variable-speed
portable air conditioners tested at both
the high- and low-temperature outdoor
operating conditions to measure a
weighted-average combined energy
efficiency ratio (‘‘CEER’’), except the
compressor speed is fixed at ‘‘full’’ and
‘‘low’’ in accordance with manufacturer
instructions at the two outdoor
conditions, respectively. Midea suggests
an additional set of calculations to
model the CEER of a theoretical
comparable dual-duct single-speed
portable air conditioner twice—once
with cycling losses and once without
cycling losses—based on the
performance of the combined-duct
variable-speed portable air conditioner
PO 00000
Frm 00040
Fmt 4703
Sfmt 4703
at full compressor speed at the lowoutdoor temperature condition. From
these results, a ‘‘performance
adjustment factor’’ is calculated,
representing the performance
improvement associated with avoiding
cycling losses. The performance
adjustment factor is then multiplied by
the measured CEER value for the
variable-speed portable air conditioner
according to Appendix CC to determine
the test unit’s final rated CEER value.
Midea states that this approach takes
into account performance and efficiency
improvements associated with
combined-duct variable-speed portable
air conditioners as compared to dualduct portable air conditioners with
single-speed compressors. In addition to
the provisions for variable-speed
compressors, Midea’s suggested
alternate test procedure also adds
provisions to the test procedure in
Appendix CC to test combined-duct
portable air conditioners using an
adapter to interface with the combined
duct and additional thermocouples to
measure temperature variations on the
surface of the combined duct.
IV. Interim Waiver Order
DOE has reviewed Midea’s
application for an interim waiver, the
alternate test procedure requested by
Midea, diagrams and renderings, and
confidential performance data Midea
provided to DOE. Based on this review,
the alternate test procedure, with
modifications discussed in the
following paragraphs, appears to allow
for the accurate measurement of the
efficiency of the specified basic models,
while alleviating the problems Midea
identified in testing these basic models.
DOE has made four modifications to
the alternate test procedure as presented
in the Media petition. First, at Midea’s
request, DOE removed an adjustment
factor that was originally requested in
the alternate test procedure to account
for different full compressor speeds for
single-speed and variable-speed
portable air conditioners at the lower
outdoor temperature operating
condition. Second, DOE doubled the
number of thermocouples on the
combined duct from eight to sixteen.
Third, DOE is altering the cycling loss
factor (‘‘CLF’’) to reflect the most recent
data and analysis. Last, DOE is requiring
the use of a unit setpoint of 75 °F at the
95 °F fixed chamber test condition to
improve test representativeness.
In its petition, Midea suggested an
adjustment factor for the purpose of
providing a more appropriate
comparison between the measured
capacity and power when testing the
variable-speed portable air conditioner
E:\FR\FM\06APN1.SGM
06APN1
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
with a full compressor speed at the
lower outdoor operating conditions and
that of a single-speed portable air
conditioner operating under those
conditions. In a communication
following the July 2020 revised petition,
Midea requested that the adjustment
factor be retracted stating that due to
subsequent modifications to the subject
basic models the adjustment factor is
now not necessary. DOE has therefore
removed this adjustment factor from the
alternate test procedure.
Additionally, DOE has initially
determined that the use of 16
thermocouples better assesses the
average temperature on the combined
duct given that it contains both the
condenser inlet and exhaust air streams.
Section 3.1.1.6 of Appendix CC requires
four thermocouples per duct. With the
basic models at issue, both of the air
streams are contained in the same
combined duct. The combined duct
potentially results in more significant
temperature gradients along its length
and perimeter, necessitating the use of
16 thermocouples.
Also, DOE considered data collected
in support of the ongoing room air
conditioner test procedure rulemaking,8
given the certain similarities of these
products to portable air conditioners, to
assess the portable air conditioner CLF
proposed in Midea’s petition. The data
for cooling degradation coefficient
(‘‘Cd’’), presented below in Table IV–1,
summarize the results from load-based
testing of two single-speed room air
conditioners at an outdoor temperature
of 82 °F and cooling loads between 49
and 55 percent of the full load (i.e., the
cooling capacity resulting from
maximum cooling at the 95 °F test
condition).
TABLE IV–1—TESTED AND EXTRAPOLATED COOLING DEGRADATION COEFFICIENT
Unit
Load %
Unit 1 ........................
Unit 2 ........................
52
54
* 55
49
54
* 55
Cd
0.42
0.39
* 0.38
0.39
0.30
* 0.28
khammond on DSKJM1Z7X2PROD with NOTICES
* Represent extrapolated values to estimate
the Cd at a 55% load.
8 The data were collected following publication of
the notice of proposed rulemaking, ‘‘Energy
Conservation Program: Test Procedure for Room Air
Conditioners’’ (85 FR 35700; Jun. 11, 2020), and
will be considered as part of that rulemaking.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
Extrapolating from the data collected,
the average Cd at 55 percent of the full
cooling load (i.e., the center of the
acceptable range specified in the low
compressor speed definition of this
waiver) would be 0.332, suggesting a
CLF of 0.8 would be more appropriate
at the 83 °F test condition as opposed to
the 0.875 CLF suggested in the Midea
petition. The analysis above represents
the best available information to date
regarding single-speed room air
conditioner cycling at reduced cooling
loads, which DOE believes is reflective
of the expected cycling that would be
observed for single-speed portable air
conditioners. Therefore, DOE is
adopting the use of 0.8 as the CLF for
the 83 °F test condition in this interim
waiver.
Furthermore, during the room air
conditioner test procedure rulemaking,
DOE observed that for units produced
by certain manufacturers, variable-speed
room air conditioners performed
differently depending on the method
used to produce maximum cooling
capacity. Testing of variable-speed room
air conditioners was conducted at
maximum cooling capacity for the ‘‘full
speed’’ 95 °F test condition, achieved
either with (1) the user settings (e.g., fan
speed, grille position) and thermostat
setpoint selected to produce maximum
cooling capacity in accordance with the
DOE room air conditioner test
procedure at 10 CFR part 430, subpart
B, appendix F (‘‘appendix F’’) (i.e., the
unit automatically selected the
compressor speed); or (2) using the user
settings, in accordance with appendix F,
but applying the manufacturer’s
confidential testing instructions to
achieve a fixed ‘‘full’’ compressor speed
(i.e., the control setting specified in the
room air condition waiver and
suggested by Midea in their petition).
One test unit was 10 percent more
efficient when using only the appendix
F user settings than when using fixed
compressor speed controls, while
another unit was 11 percent less
efficient.
Based on the observed differences in
room air conditioner performance when
using the fixed ‘‘full’’ compressor speed
(i.e., applying the confidential
manufacturer instructions) as compared
to using only the appendix F settings,
described above, DOE concludes that
similar differences may occur when
testing portable air conditioners and is
requiring a unit setpoint of 75 °F for the
portable air conditioner ‘‘full speed’’
PO 00000
Frm 00041
Fmt 4703
Sfmt 4703
17807
95 °F test condition, as it would be more
representative of typical consumer
settings than reliance on the
confidential manufacturer instructions
to achieve maximum cooling capacity.
In evaluating potential thermostat
setpoints, DOE reviewed data for 19
portable air conditioners that were field
metered in a 2014 study conducted by
Lawrence Berkeley National
Laboratory.9 Among these units, the
thermostat setpoints selected by
consumers ranged from 66 °F to 76 °F,
with a median value of 74.5 °F. DOE
expects, therefore, that 75 °F is a typical
consumer setpoint for portable air
conditioners that would achieve the
maximum cooling (given the differential
between the setpoint and the fixed
indoor test chamber dry-bulb
temperature of 80 °F), in accordance
with appendix CC. DOE is also
modifying the definition of ‘‘full
compressor speed’’ accordingly in this
interim waiver.
DOE notes that while variable-speed
waivers granted for other products
numerically estimate performance of a
theoretical single-speed product at
reduced outdoor temperature
conditions, given the complex heat
transfer dynamics related to the ducts,
infiltration air, and internal air mixing
within the chassis of the combined duct
used in the basic models specified by
Midea in its petition, DOE believes that
the approach proposed by Midea to
estimate performance of the theoretical
single-speed dual-duct portable air
conditioner using the performance of
the variable-speed combined-duct
portable air conditioner at the lowoutdoor temperature condition,
modified as discussed above, is
appropriate and reasonable.
Consequently, DOE has determined that
Midea’s petition for waiver likely will
be granted. Furthermore, DOE has
determined that it is desirable for public
policy reasons to grant Midea
immediate relief pending a
determination of the petition for waiver.
For the reasons stated, it is ordered
that:
(1) Midea must test and rate the
following portable air conditioner basic
models with the alternate test procedure
set forth in paragraph (2).
9 T. Burke et al., ‘‘Using Field-Metered Data to
Quantify Annual Energy Use of Portable Air
Conditioners,’’ Lawrence Berkeley National
Laboratory, LBNL–6868E, December 2014.
E:\FR\FM\06APN1.SGM
06APN1
17808
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
Brand
Model No.
khammond on DSKJM1Z7X2PROD with NOTICES
Midea .....................................................................................................................................................................
Midea .....................................................................................................................................................................
Perfect aire ............................................................................................................................................................
Danby .....................................................................................................................................................................
Heat Controller LLC ...............................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
hOme .....................................................................................................................................................................
Vremi ......................................................................................................................................................................
Wappliance ............................................................................................................................................................
Perfect aire ............................................................................................................................................................
Danby .....................................................................................................................................................................
Heat Controller LLC ...............................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
hOme .....................................................................................................................................................................
Vremi ......................................................................................................................................................................
Wappliance ............................................................................................................................................................
Perfect aire ............................................................................................................................................................
Danby .....................................................................................................................................................................
Heat Controller LLC ...............................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
hOme .....................................................................................................................................................................
Vremi ......................................................................................................................................................................
Wappliance ............................................................................................................................................................
Perfectaire ..............................................................................................................................................................
Danby .....................................................................................................................................................................
Heat Controller LLC ...............................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
Whynter ..................................................................................................................................................................
hOme .....................................................................................................................................................................
Vremi ......................................................................................................................................................................
Wappliance ............................................................................................................................................................
Toshiba ..................................................................................................................................................................
Toshiba ..................................................................................................................................................................
Toshiba ..................................................................................................................................................................
Danby .....................................................................................................................................................................
Danby .....................................................................................................................................................................
Midea .....................................................................................................................................................................
Midea .....................................................................................................................................................................
Midea .....................................................................................................................................................................
(2) The alternate test procedure for the
Midea basic models identified in
paragraph (1) of this Interim Waiver
Order is the test procedure for portable
air conditioners prescribed by DOE at
Appendix CC and 10 CFR 430.23(dd),
with three exceptions. First, install the
unit under test as detailed below.
Second, determine combined energy
efficiency ratio (CEER) as detailed
below. Third, calculate the estimated
annual operating cost in 10 CFR
430.23(dd)(2) as detailed below. In
addition, for each basic model listed in
paragraph (1), maintain the compressor
speed at each test condition, and set the
control settings used for the variable
components, according to the
instructions submitted to DOE by Midea
(https://www.regulations.gov/docket/
EERE-2020-BT-WAV-0023). Upon the
compliance date of any new energy
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
conservation standards for portable air
conditioners, Midea must report
product specific information pursuant
to 10 CFR 429.12(b)(13) and 10 CFR
429.62(b). All other requirements of
Appendix CC and DOE’s regulations
remain applicable.
In 10 CFR 430.2, add in alphabetical
order:
Combined-duct portable air
conditioner means a dual-duct portable
air conditioner with the condenser inlet
and outlet air streams flowing through
separate ducts housed in a single overall
duct structure.
In 10 CFR 430.23, in paragraph (dd)
revise paragraph (2) to read as follows:
(2) Determine the estimated annual
operating cost for a combined-duct
variable-speed portable air conditioner,
expressed in dollars per year, by
multiplying the following two factors:
PO 00000
Frm 00042
Fmt 4703
Sfmt 4703
US–KC35Y1/BP3N8–PTB(CH3)
US–KC30Y1/BP3N8–PTB(CG8)
1PORTV10000
DPA100B9IWDB–6
PSV–101D
ARC–1030WN
ARC–1030BN
ARC–1030GN
HME020373N
VRM050703N
BPI10MW
1PORTVP10000.
DPA100HB9IWDB–6
PSHV–101D
ARC–1030WNH
ARC–1030GNH
ARC–1030BNH
HME020374N
VRM050704N
BPI10HMW
1PORTV12000
DPA120B9IWDB–6
PSV–121D
ARC–1230WN
ARC–1230BN
ARC–1230GN
HME020375N
VRM050705N
BPI12MW
1PORTVP12000
DPA120HB9IWDB–6
PSHV–121D
ARC–1230WNH
ARC–1230GNH
ARC–1230BNH
HME020376N
VRM050706N
BPI12HMW
RAC–PT1411HWRU
RAC–PT1411CWRU
RAC–PT1211CWRU
DPA100HB9IBDB–6
DPA120B9IBDB–6
MPPTB–12HRN8–BCH4
MPPTB–12CRN8–BCH4
MPPTB–10CRN8–BCG8
(i) The sum of the following three
values: AEC95 multiplied by 0.2, AEC83_
Low multiplied by 0.8, and AECT, as
calculated in section 5.3 of appendix CC
of this subpart; and
(ii) A representative average unit cost
of electrical energy in dollars per
kilowatt-hour as provided by the
Secretary.
(iii) Round the resulting product to
the nearest dollar per year.
In Appendix CC:
Add in Section 2, Definitions:
2.11 Single-speed means a type of
portable air conditioner that cannot
adjust the compressor speed.
2.12 Variable-speed means a type of
portable air conditioner that can
automatically adjust the compressor
speed.
2.13 Full compressor speed (full)
means the compressor speed at which
the unit operates at full load test
E:\FR\FM\06APN1.SGM
06APN1
17809
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
conditions, when using user settings to
achieve maximum cooling capacity, and
with the thermostat setpoint set at 75 °F.
2.14 Low compressor speed (low)
means the compressor speed specified
by Midea (Docket No. EERE–2020–BT–
WAV–0023–0006), at which the unit
operates at low load test conditions,
such that Capacity_83_Low, the measured
cooling capacity at this speed at Test
Condition 3 in Table 1 of this appendix,
is no less than 50 percent and no greater
than 60 percent of Capacity95, the
measured cooling capacity with the full
compressor speed at Test Condition 1 in
Table 1 of this appendix.
2.15 Theoretical comparable singlespeed portable air conditioner means a
theoretical single-speed portable air
conditioner with the same cooling
capacity and electrical power input as
the variable-speed portable air
conditioner under test, with no cycling
losses considered, when operating with
the full compressor speed and at Test
Condition 1 in Table 1 of this appendix.
Replace section 3.1.1 Test conduct
with the following:
Test conduct. The test apparatus and
instructions for testing portable air
conditioners in cooling mode and offcycle mode must conform to the
requirements specified in Section 4,
‘‘Definitions’’ and Section 7, ‘‘Tests,’’ of
ANSI/AHAM PAC–1–2015
(incorporated by reference; see § 430.3),
except as otherwise specified in this
appendix. Measure duct heat transfer
and infiltration air heat transfer
according to section 4.1.1 and section
4.1.2 of this appendix, respectively.
Replace section 3.1.1.1 Duct Setup
with the following:
Use only ducting components
provided by the manufacturer,
including, where provided by the
manufacturer, ducts, connectors for
attaching the duct(s) to the test unit,
sealing, insulation, and window
mounting fixtures. Do not apply
additional sealing or insulation. To
measure the condenser inlet and outlet
airflows in the combined duct, use an
adapter provided by the manufacturer,
which allows for the individual
connection of the condenser inlet and
outlet airflows to the test lab’s airflow
measuring apparatuses.
Replace section 3.1.1.6 Duct
temperature measurements with the
following:
Duct temperature measurements.
Install any insulation and sealing
provided by the manufacturer. Then
adhere sixteen thermocouples to the
outer surface of the duct, spaced evenly
around the circumference (four
thermocouples, each 90 degrees apart,
radially) and down the length of the
duct (four sets of four thermocouples,
evenly placed along the length of the
duct), ensuring that the thermocouples
are distributed equally on the entire
surface of the combined duct. Ensure
that at least one thermocouple is placed
next to the condenser inlet aperture and
at least one thermocouple is placed on
the duct surface adjacent to or nearest
to the condenser outlet aperture.
Measure the surface temperature of the
combined duct at each thermocouple.
Temperature measurements must have
an error no greater than ±0.5 °F over the
range being measured.
Add to the end of Section 3.1.2,
Control settings:
Set the compressor speed during
cooling mode testing as described in
section 4.1 of this appendix, as
amended by this Order.
Replace Section 4.1, Cooling mode
with the following:
Cooling mode. Instead of the test
conditions in Table 3 of ANSI/AHAM
PAC–1–2015, establish the test
conditions presented in Table 1 of this
appendix. Test each sample unit three
times, once at each test condition in
Table 1. For each test condition,
measure the sample unit’s indoor room
cooling capacity and overall power
input in cooling mode in accordance
with Section 7.1.b and 7.1.c of ANSI/
AHAM PAC–1–2015 (incorporated by
reference; see § 430.3), respectively, and
determine the test duration in
accordance with Section 8.7 of ASHRAE
Standard 37–2009 (incorporated by
reference; § 430.3). Conduct the first test
in accordance with ambient conditions
for Test Condition 1 in Table 1 of this
appendix, achieving the full compressor
speed, as defined in section 2.13 of this
appendix, with user settings, for the
duration of cooling mode testing
(Capacity95, P95). Conduct the second
test in accordance with the ambient
conditions for Test Condition 2, in
Table 1 of this appendix, with the
compressor speed set to full, for the
duration of cooling mode testing
(Capacity83_Full, P83_Full). To confirm the
same full compressor speed is used, the
average compressor frequency for the
second test must equal that observed for
the first test, with a tolerance of +/¥
10% of the nominal average compressor
frequency of the first test. Conduct the
third test in accordance with the
ambient conditions for Test Condition 3,
with the compressor speed set to low for
the duration of cooling mode testing
(Capacity83_Low, P83_Low). Set the
compressor speed required for each test
condition in accordance with the
instructions Midea submitted to DOE
(Docket No. EERE–2020–BT–WAV–
0023–0006).
TABLE 1—EVAPORATOR AND CONDENSER INLET TEST CONDITIONS
Test condition
khammond on DSKJM1Z7X2PROD with NOTICES
Test Condition 1 ..................................................................
Test Condition 2 ..................................................................
Test Condition 3 ..................................................................
Replace Section 4.1.1, Duct Heat
Transfer, with the following:
Duct Heat Transfer. Measure the
circumference of the duct by wrapping
a flexible measuring tape, or equivalent,
around the outside of the combined
duct, making sure the tape is on the
outermost ridges. Calculate the surface
area of the combined duct as follows:
ACD = C × L
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
Evaporator inlet air °F (°C)
Condenser inlet air °F (°C)
Dry bulb
Dry bulb
Wet bulb
80 (26.7)
80 (26.7)
80 (26.7)
67 (19.4)
67 (19.4)
67 (19.4)
Where:
ACD = the outer area of the combined duct,
in square feet.
C = the circumference of the combined duct,
as measured in this section, in feet.
L = the extended length of the combined duct
while under test, in feet.
Calculate the average temperature at
each individual location. Then calculate
the average surface temperature of the
duct by averaging the sixteen average
PO 00000
Frm 00043
Fmt 4703
Sfmt 4703
95 (35.0)
83 (28.3)
83 (28.3)
Wet bulb
75 (23.9)
67.5 (19.7)
67.5 (19.7)
Compressor
speed
Full.
Full.
Low.
temperature measurements taken on the
duct. Calculate the total heat transferred
from the surface of the combined duct
to the indoor conditioned space while
operating in cooling mode at each test
condition in Table 1 of this appendix,
according to the following equations:
QCD_95 = 3 × ACD × (TCD_95¥Tei)
QCD_83_Full = 3 × ACD × (TCD_83_Full¥Tei)
QCD_83_Low = 3 × ACD × (TCD_83_
Low¥Tei)
E:\FR\FM\06APN1.SGM
06APN1
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
calculated in this section, in square feet.
TCD_95, TCD_83_Full, and TCD_83_Low = average
surface temperature for the combined
duct, in °F, as measured at Test
Condition 1, Test Condition 2, and Test
Condition 3 in Table 1 of this appendix,
respectively, as calculated in this
section.
Tei = average evaporator inlet air dry-bulb
temperature, as measured in section 4.1
of this appendix, in °F.
Where:
QCD_95, QCD_83_Full, and QCD_83_Low = the
total heat transferred from the combined
duct to the indoor conditioned space in
cooling mode, in Btu/h, when tested at
Test Condition 1, Test Condition 2, and
Test Condition 3 in Table 1 of this
appendix, respectively.
3 = convection coefficient in Btu/h per
square foot per °F.
ACD = surface area of the combined duct, as
.
= Vco-95 X Pco-95 -
m95
( 1 + Wco_95)
.
.
khammond on DSKJM1Z7X2PROD with NOTICES
-
=
Where:
˙ 95, m
˙ 83_Full and m
˙ 83_Low = dry air mass flow
m
rate of infiltration air for combined-duct
portable air conditioners, in lb/m, when
tested at Test Condition 1, Test
Condition 2, and Test Condition 3 in
Table 1 of this appendix, respectively.
Vco_95, Vco_83_Full and Vco_83_Low = average
volumetric flow rate of the condenser
outlet air, in cubic feet per minute (cfm),
as measured at Test Condition 1, Test
Condition 2, and Test Condition 3 in
Table 1 of this appendix, respectively, as
required in section 4.1 of this appendix.
Vci_95, Vci_83_Full and Vci_83_Low = average
volumetric flow rate of the condenser
inlet air, in cfm, as measured at Test
Condition 1, Test Condition 2, and Test
Condition 3 in Table 1 of this appendix,
respectively, as required in section 4.1 of
this appendix.
rco_95, rco_83_Full and rco_83_Low = average
density of the condenser outlet air, in
pounds mass per cubic foot (lbm/ft3), as
measured at Test Condition 1, Test
Condition 2, and Test Condition 3 in
Table 1 of this appendix, respectively, as
required in section 4.1 of this appendix.
rci_95, rci_83_Full and rci_83_Low = average
density of the condenser inlet air, in lbm/
ft3, as measured at Test Condition 1, Test
Condition 2, and Test Condition 3 in
Table 1 of this appendix, respectively, as
required in section 4.1 of this appendix.
wco_95, wco_83_Full and wco_83_Low = average
humidity ratio of condenser outlet air, in
pounds mass of water vapor per pounds
mass of dry air (lbw/lbda), as measured at
Test Condition 1, Test Condition 2, and
Test Condition 3 in Table 1 of this
appendix, respectively, as required in
section 4.1 of this appendix.
wci_95, wci_83_Full and wci_83_Low = average
humidity ratio of condenser inlet air, in
lbw/lbda, as measured at Test Condition 1,
Test Condition 2, and Test Condition 3
in Table 1 of this appendix, respectively,
17:34 Apr 05, 2021
-
(
-
1 + Wci_95)
vci_83_Full X Pci_83_Full
( 1 + Wco_83_Full)
m83 Low
VerDate Sep<11>2014
Vci 95 X Pei 95
= Vco-83-Full X Pco-83-Full
m83
Jkt 253001
Replace Section 4.1.2, Infiltration Air
Heat Transfer with the following:
Infiltration Air Heat Transfer.
Calculate the sample unit’s heat
contribution from infiltration air into
the conditioned space for each cooling
mode test. Calculate the dry air mass
flow rate of infiltration air according to
the following equations:
(
1 + Wci_83_Full)
Vco 83 Low X Pco 83 Low
vci_83_Low X Pci_83_Low
1 + Wco_83_Low
( 1 + Wci_83_Low)
(- -
- -)
as required in section 4.1 of this
appendix.
Calculate the sensible component of
infiltration air heat contribution
according to the following equations:
˙ 95 × 60 × [cp_da × (95 ¥ 80)
Qs_95 = m
+ (cp_wv × (0.0141 × 95 ¥ 0.0112 ×
80))]
˙ 83_Full × 60 × [(cp_da × (83
Qs_83_Full = m
¥ 80) + (cp_wv × (0.01086 × 83 ¥
0.0112 r × 80))]
˙ 83_Low × 60 × [(cp_da × (83
Qs_83_Low = m
¥ 80) + (cp_wv × (0.01086 × 83 ¥
0.0112 r × 80))]
Where:
Qs_95, Qs_83_Full and Qs_83_Low = sensible heat
added to the room by infiltration air, in
Btu/h, when tested at Test Condition 1,
Test Condition 2, and Test Condition 3
in Table 1 of this appendix, respectively.
˙ 95, m
˙ 83_Full and m
˙ 83_Low = dry air mass flow
m
rate of infiltration air for combined-duct
portable air conditioners, in lb/m, when
tested at Test Condition 1, Test
Condition 2, and Test Condition 3 in
Table 1 of this appendix, respectively, as
calculated in section 4.1.2 of this
appendix.
cp_da = specific heat of dry air, 0.24 Btu/(lbm
°F).
cp_wv = specific heat of water vapor, 0.444
Btu/(lbm °F).
80 = indoor chamber dry-bulb temperature,
in °F.
95 = infiltration air dry-bulb temperature for
Test Condition 1 in Table 1 of this
appendix, in °F.
83 = infiltration air dry-bulb temperature for
Test Conditions 2 and 3 in Table 1 of this
appendix, in °F.
0.0141 = humidity ratio of the dry-bulb
infiltration air for Test Condition 1 in
Table 1 of this appendix, in lbw/lbda.
0.01086 = humidity ratio of the dry-bulb
infiltration air for Test Conditions 2 and
PO 00000
Frm 00044
Fmt 4703
Sfmt 4703
3 in Table 1 of this appendix, in lbw/lbda.
0.0112 = humidity ratio of the indoor
chamber air, in lbw/lbda (windoor).
60 = conversion factor from minutes to hours.
Calculate the latent heat contribution
of the infiltration air according to the
following equations:
˙ 95 × 60 × 1061 ×
Ql_95 = m
(0.0141¥0.0112)
˙ 83_Full × 60 × 1061 ×
Ql_83_Full = m
(0.01086 ¥ 0.0112)
˙ 83_Low × 60 × 1061 ×
Ql_83_Low = m
(0.01086 ¥ 0.0112)
Where:
Ql_95, Ql_83_Full and Ql_83_Low = latent heat
added to the room by infiltration air,
when tested at Test Conditions 1, 2, and
3 in Table 1 of this appendix,
respectively, in Btu/h.
˙ 95, m
˙ 83_Full and m
˙ 83_Low = dry air mass flow
m
rate of infiltration air, in lb/m, when
tested at Test Condition 1, Test
Condition 2, and Test Condition 3 in
Table 1 of this appendix, respectively, as
calculated in section 4.1.2 of this
appendix.
1061 = latent heat of vaporization for water
vapor, in Btu/lbm (Hfg).
0.0141 = humidity ratio of the dry-bulb
infiltration air for Test Condition 1 in
Table 1 of this appendix, in lbw/lbda.
0.01086 = humidity ratio of the dry-bulb
infiltration air for Test Conditions 2 and
3 in Table 1 of this appendix, in lbw/lbda.
0.0112 = humidity ratio of the indoor
chamber air, in lbw/lbda.
60 = conversion factor from minutes to hours.
Calculate the total heat contribution
of the infiltration air at each test
condition by adding the sensible and
latent heat according to the following
equations:
Qinfiltration_95 = Qs_95 + Ql_95
Qinfiltration_83_Full = Qs_83_Full + Ql_83_Full
E:\FR\FM\06APN1.SGM
06APN1
EN06AP21.001
17810
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
Qinfiltration_83_Low = Qs_83_Low + Ql_83_Low
Where:
Qinfiltration_95, Qinfiltration_83_Full and Qinfiltration_
83_Low = total infiltration air heat in
cooling mode, when tested at Test
Conditions 1, 2, and 3 in Table 1 of this
appendix, respectively, in Btu/h
Qs_95, Qs_83_Full and Qs_83_Low = sensible heat
added to the room by infiltration air,
when tested at Test Conditions 1, 2, and
3 in Table 1 of this appendix,
respectively, in Btu/h, as calculated in
this section.
Ql_95, Ql_83_Full and Ql_83_Low = latent heat
added to the room by infiltration air,
when tested at Test Conditions 1, 2, and
3 in Table 1 of this appendix,
respectively, in Btu/h, as calculated in
this section.
Replace Section 5.1, Adjusted Cooling
Capacity with the following:
Adjusted Cooling Capacity. Calculate
the adjusted cooling capacity at each
outdoor temperature operating
condition, ACC95 and ACC83_Low,
expressed in Btu/h, according to the
following equations:
ACC95 = Capacity95¥QCD_95¥
Qinfiltration_95
ACC83_Low = Capacity83_Low¥QCD_
Low¥Qinfiltration_83_Low
Where:
Capacity95 and Capacity83_Low = cooling
capacity, as measured in section 4.1 of
this appendix, at Test Condition 1 and
Test Condition 3 in Table 1 of this
appendix, respectively, in Btu/h.
QCD_95 and QCD_83_Low = combined duct heat
transfer while operating in cooling mode
at Test Condition 1 and Test Condition
17:34 Apr 05, 2021
Cooling Mode, Test
Condition 1 1.
Cooling Mode, Test
Condition 2 1.
Cooling Mode, Test
Condition 3 1.
Off-Cycle .................
Inactive or Off .........
Jkt 253001
Annual
operating
hours
Subscript
95 ............
750
83_Full .....
750
83_Low ....
750
oc .............
ia or om ...
880
1,355
1 These operating mode hours are for the
purposes of calculating annual energy consumption under different ambient conditions
and are not a division of the total cooling
mode operating hours. The total cooling mode
operating hours are 750 hours.
AECm
= Pm X tm X 0.001
Where:
AECm = annual energy consumption in the
Where:
AECT = total annual energy consumption
attributed to off cycle mode and inactive
or off mode, in kWh/year;
AECm = total annual energy consumption in
the operating mode, in kWh/year.
m represents the following two operating
modes: Off cycle mode and inactive or
off mode.
Replace Section 5.4, Combined Energy
Efficiency Ratio with the following:
Unadjusted Combined Energy
Efficiency Ratio. Calculate the sample
unit’s unadjusted combined energy
efficiency ratio, CEERUA, expressed in
Btu/Wh, as follows:
I
I
year.
0.001 kWh/Wh = conversion factor for watthours to kilowatt-hours.
0.2 = weighting factor for the 95 °F dry-bulb
outdoor temperature operating
condition.
0.8 = weighting factor for the 83 °F dry-bulb
outdoor temperature operating
condition.
Add after Section 5.4, Combined
Energy Efficiency Ratio:
5.5 Adjustment of the Combined
Energy Efficiency Ratio. Adjust the
sample unit’s unadjusted combined
energy efficiency ratio as follows.
5.5.1 Theoretical Comparable
Single-Speed Portable Air Conditioner
Cooling Capacity and Power at the
Lower Outdoor Temperature Operating
Condition. Calculate the cooling
capacity and cooling capacity with
PO 00000
Frm 00045
Fmt 4703
Sfmt 4703
cycling losses, expressed in British
thermal units per hour (Btu/h), and
electrical power input, expressed in
watts, for a theoretical comparable
single-speed portable air conditioner at
an 83 °F outdoor dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix)
according to the following equations:
Capacity83_SS = Capacity83_Full
Capacity83_SS_CLF = Capacity83_SS × 0.8
P83_SS = P83_Full
Where:
Capacity83_SS = cooling capacity of a
theoretical comparable single-speed
portable air conditioner, calculated for
the 83 °F dry-bulb outdoor temperature
operating condition (Test Condition 2 in
Table 1 of this appendix), in Btu/h.
Capacity83_SS_CLF = cooling capacity of a
theoretical comparable single-speed
E:\FR\FM\06APN1.SGM
06APN1
EN06AP21.004
ACC9 s
]
ACCa3 Low
]
AEC95 + AECr x 0. 2 + (AECa3 Low + AECr) x O.B
( 750 X 0.001 )
750 X 0.001
Where:
CEERUA = unadjusted combined energy
efficiency ratio for the sample unit, in
Btu/Wh.
ACC95 and ACC83_Low = adjusted cooling
capacity, tested at Test Condition 1 and
Test Condition 3 in Table 1 of this
appendix, respectively, as calculated in
section 5.1 of this appendix, in Btu/h.
AEC95 and AEC83_Low = annual energy
consumption for cooling mode operation
at Test Condition 1 and Test Condition
3 in Table 1 in this appendix that
represent operation at 95 °F and 83 °F
dry-bulb outdoor temperature operating
conditions, respectively, as calculated in
section 5.3 of this appendix, in kWh/
year.
AECT = total annual energy consumption
attributed to off cycle mode and inactive
or off mode, in kWh/year, calculated in
section 5.3 of this appendix.
750 = number of cooling mode hours per
VerDate Sep<11>2014
Operating mode
Calculate the sample unit’s total
annual energy consumption in off cycle
mode and inactive or off mode as
follows:
EN06AP21.003
=
Replace Section 5.3, Annual Energy
Consumption with the following:
Annual Energy Consumption.
Calculate the sample unit’s annual
energy consumption in each operating
mode according to the equation below.
For each operating mode, use the
following annual hours of operation and
equation:
operating mode, in kWh/year.
m represents the operating mode (‘‘95’’ for
Test Condition 1, ‘‘83_Full’’ for Test
Condition 2, ‘‘83_Low’’ for Test
Condition 3, ‘‘oc’’ for off cycle, and ‘‘ia’’
for inactive or ‘‘om’’ for off mode).
Pm = average power in the operating mode,
in watts.
tm = number of annual operating time in each
operating mode, in hours.
0.001 kWh/Wh = conversion factor from
watt-hours to kilowatt-hours.
EN06AP21.002
khammond on DSKJM1Z7X2PROD with NOTICES
CEERuA
3 in Table 1 of this appendix,
respectively, in Btu/h, as calculated in
section 4.1.1 of this appendix.
Qinfiltration_95 and Qinfiltration_83_Low = total
infiltration air heat transfer in cooling
mode at Test Condition 1 and Test
Condition 3 in Table 1 of this appendix,
respectively, in Btu/h, as calculated in
section 4.1.2 of this appendix.
17811
17812
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
portable air conditioner with cycling
losses, in Btu/h, calculated for the 83 °F
dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of
this appendix).
Capacity83_Full = cooling capacity of the
sample unit, measured in section 4.1 of
this appendix at Test Condition 2 in
Table 1 of this appendix, in Btu/h.
P83_SS = power input of a theoretical
comparable single-speed portable air
conditioner calculated for the 83 °F drybulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of
this appendix), in watts.
P83_Full = electrical power input of the sample
unit, measured in section 4.1 of this
appendix at Test Condition 2 in Table 1
of this appendix, in watts.
0.8 = cycling loss factor for the 83 °F dry-bulb
outdoor temperature operating
condition.
5.5.2 Duct Heat Transfer for a
Theoretical Comparable Single-Speed
Portable Air Conditioner at the Lower
Outdoor Temperature Operating
Condition. Calculate the combined duct
heat transfer to the conditioned space
for a theoretical comparable singlespeed portable air conditioner at the
83 °F dry-bulb outdoor temperature
operating condition (Test Condition 2 in
Table 1 of this appendix), as follows:
QCD_83_SS = QCD_83_Full
khammond on DSKJM1Z7X2PROD with NOTICES
Where:
QCD_83_SS = total heat transferred from the
combined duct to the indoor conditioned
space in cooling mode, for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb outdoor
temperature operating condition), in Btu/
h.
QCD_83_Full = combined duct heat transfer for
the sample unit while operating in
cooling mode at Test Condition 2 in
Table 1 of this appendix (the 83 °F drybulb outdoor temperature operating
condition), in Btu/h, as calculated in
section 4.1.1 of this appendix.
5.5.3 Infiltration Air Heat Transfer
for a Theoretical Comparable SingleSpeed Portable Air Conditioner at the
Lower Outdoor Temperature Operating
Condition. Calculate the heat
contribution from infiltration air for a
theoretical comparable single-speed
portable air conditioner at the 83 °F drybulb outdoor temperature operating
condition (Test Condition 2 in Table 1
of this appendix), as detailed below.
Calculate the dry air mass flow rate of
infiltration air as follows:
˙ 83_SS = m
˙ 83_Full
m
Where:
˙ 83_SS = dry air mass flow rate of infiltration
m
air for a theoretical comparable singlespeed portable air conditioner at the
83 °F dry-bulb outdoor temperature
operating condition (Test Condition 2 in
Table 1 of this appendix), in lb/m.
˙ 83_Full = dry air mass flow rate of infiltration
m
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
air for the sample unit when tested at
Test Condition 2 in Table 1 of this
appendix (the 83 °F dry-bulb outdoor
temperature operating condition), as
calculated in section 4.1.2 of this
appendix, in lb/m.
Calculate the sensible component of
infiltration air heat contribution for a
theoretical comparable single-speed
portable air conditioner at the 83 °F drybulb outdoor temperature operating
condition (Test Condition 2 in Table 1
of this appendix) as follows:
Qs_83_SS = Qs_83_Full
Where:
Qs_83_SS = sensible heat added to the room
by infiltration air for a theoretical
comparable single-speed portable air
conditioner, at the 83 °F dry-bulb
outdoor temperature operating condition
(Test Condition 2 in Table 1 of this
appendix), in Btu/h.
Qs_83_Full = sensible heat added to the room
by infiltration air, when testing the
sample unit at Test Condition 2 in Table
1 of this appendix (the 83 °F dry-bulb
outdoor temperature operating
condition), as calculated in section 4.1.2
of this appendix, in Btu/h.
Calculate the latent component of
infiltration air heat contribution for a
theoretical comparable single-speed
portable air conditioner at the 83 °F drybulb outdoor temperature operating
condition (Test Condition 2 in Table 1
of this appendix) as follows:
Ql_83_SS = Ql_83_Full
Where:
Ql_83_SS = latent heat added to the room by
infiltration air for a theoretical
comparable single-speed portable air
conditioner, at the 83 °F dry-bulb
outdoor temperature operating condition
(Test Condition 2 in Table 1 of this
appendix), in Btu/h.
Ql_83_Full = latent heat added to the room by
infiltration air during testing of the
sample unit, when tested at Test
Condition 2 in Table 1 of this appendix
(the 83 °F dry-bulb outdoor temperature
operating condition), as calculated in
section 4.1.2 of this appendix, in Btu/h.
Calculate the total heat contribution
of the infiltration air for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb
outdoor temperature operating
condition (Test Condition 2 in Table 1
of this appendix) as follows:
Qinfiltration_83_SS = Qinfiltration_83_Full
Where:
Qinfiltration_83_SS = total infiltration air heat in
cooling mode for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix),
in Btu/h.
Qinfiltration_83_Full = total infiltration air heat
transfer of the sample unit in cooling
PO 00000
Frm 00046
Fmt 4703
Sfmt 4703
mode at Test Condition 2 in Table 1 of
this appendix (the 83 °F dry-bulb
outdoor temperature operating
condition), as calculated in section 4.1.2
of this appendix, in Btu/h.
5.5.4 Adjusted Cooling Capacity for
a Theoretical Comparable Single-Speed
Portable Air Conditioner at the Lower
Outdoor Temperature Operating
Condition. Calculate the adjusted
cooling capacity for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb
outdoor temperature operating
condition (Test Condition 2 in Table 1
of this appendix) both without cycling
losses, ACC83_SS, and with cycling
losses, ACC83_SS_CLF, in Btu/h,
according to the following equations:
ACC83_SS = Capacity83_SS ¥ QCD_83_SS
¥ Qinfiltration_83_SS
ACC83_SS_CLF = Capacity83_SS_CLF ¥
QCD_83_SS ¥ Qinfiltration_83_SS
Where:
ACC83_SS and ACC83_SS_CLF = adjusted
cooling capacity for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix)
without and with cycling losses,
respectively, in Btu/h.
Capacity83_SS and Capacity83_SS_CLF =
cooling capacity of a theoretical
comparable single-speed portable air
conditioner without and with cycling
losses, respectively, at Test Condition 2
in Table 1 of this appendix (the 83 °F
dry-bulb outdoor temperature operating
condition), calculated in section 5.5.1 of
this appendix, in Btu/h.
QCD_83_SS = total heat transferred from the
ducts to the indoor conditioned space in
cooling mode for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix),
in Btu/h, calculated in section 5.5.2 of
this appendix.
Qinfiltration_83_SS = total infiltration air heat in
cooling mode for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix),
calculated in section 5.5.3 of this
appendix, in Btu/h.
5.5.5 Annual Energy Consumption
in Cooling Mode for a Theoretical
Comparable Single-Speed Portable Air
Conditioner at the Lower Outdoor
Temperature Operating Condition.
Calculate the annual energy
consumption in cooling mode for a
theoretical comparable single-speed
portable air conditioner at the 83 °F drybulb outdoor temperature operating
condition (Test Condition 2 in Table 1
of this appendix), in kWh/year, as
follows:
E:\FR\FM\06APN1.SGM
06APN1
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
theoretical comparable single-speed
portable air conditioner at the 83 °F drybulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of
this appendix) as calculated in section
5.5.1 of this appendix, in watts.
750 = number of cooling mode hours per
year, as defined in section 5.3 of this
appendix.
0.001 kWh/Wh = conversion factor from
watt-hours to kilowatt-hours.
CEERss
750
CEERss_cLF
ACC 95
= [ (AEC95 + AECT)
khammond on DSKJM1Z7X2PROD with NOTICES
750
Where:
CEERSS and CEERSS_CLF = combined energy
efficiency ratio for a theoretical
comparable single-speed portable air
conditioner without and with cycling
losses considered, respectively, in Btu/
Wh.
ACC95 = adjusted cooling capacity for the
sample unit, as calculated in section 5.1
of this appendix, when tested at Test
Condition 1 in Table 1 of this appendix,
in Btu/h.
ACC83_SS and ACC83_SS_CLF = adjusted
cooling capacities for a theoretical
comparable single-speed portable air
conditioner at the 83 °F dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix)
without and with cycling losses,
respectively, as calculated in section
5.5.4 of this appendix, in Btu/h.
AEC95 = annual energy consumption for the
sample unit, as calculated in section 5.3
of this appendix, for cooling mode
operation at Test Condition 1 in Table 1
of this appendix, in kWh/year.
AEC83_SS = annual energy consumption for a
theoretical comparable single-speed
portable air conditioner in cooling mode
at the 83 °F dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix),
calculated in section 5.5.5 of this
appendix, in kWh/year.
AECT = total annual energy consumption
attributed to all operating modes except
cooling for the sample unit, calculated in
section 5.3 of this appendix, in kWh/
year.
750 and 0.001 as defined previously in this
section.
0.2 = weighting factor for the 95 °F dry-bulb
outdoor temperature operating
condition.
0.8 = weighting factor for the 83 °F dry-bulb
outdoor temperature operating
condition.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
l [
ACC 95
ACCa3_ss
]
x 0. 2 + (AEC 83 ss + AECT) x 0. 8
750 X 0.001
= [ (AEC 95 + AECT)
X
]
0.001
x 0.2
0.001
X
[
ACCa3_ss_cLF
750
X
P
( CEERss - CEERss CLF)
=~-_;;_;;_----=---~
CEERs~cLF
Where:
CEERSS and CEERSS_CLF = combined energy
efficiency ratios for a theoretical
comparable single-speed portable air
conditioner without and with cycling
losses, respectively, calculated in section
5.5.6 of this appendix, in Btu/Wh.
5.5.8 Dual-Duct Variable-Speed
Portable Air Conditioner Combined
Energy Efficiency Ratio. Calculate the
sample unit’s final combined energy
efficiency ratio, CEER, in Btu/Wh, as
follows:
CEER = CEERUA × (1 + Fp)
Where:
CEER = combined energy efficiency ratio for
the sample unit, in Btu/Wh.
CEERUA = unadjusted combined energy
efficiency ratio for the sample unit,
calculated in section 5.4 of this
appendix, in Btu/Wh.
Fp = sample unit’s performance adjustment
factor, calculated in section 5.5.7 of this
appendix.’’
(3) Representations. Midea may not
make representations about the
efficiency of a basic model listed in
paragraph (1) of this Interim Waiver
Order for compliance, marketing, or
other purposes unless that basic model
has been tested in accordance with the
provisions set forth in this alternate test
procedure and such representations
PO 00000
Frm 00047
Fmt 4703
Sfmt 4703
0.8
0.001
5.5.7 Combined-Duct VariableSpeed Portable Air Conditioner
Performance Adjustment Factor.
Calculate the sample unit’s performance
adjustment factor, Fp,, as follows:
F
]
+ (AECa3 ss + AECT) x
fairly disclose the results of such
testing.
(4) This Interim Waiver Order shall
remain in effect according to the
provisions of 10 CFR 430.27.
(5) This Interim Waiver Order is
issued on the condition that the
statements, representations, test data,
and documentary materials provided by
Midea are valid. If Midea makes any
modifications to the controls or
configurations of a basic model subject
to this Interim Waiver Order, the waiver
will be invalid with respect to that basic
model Midea either would be required
to use the current Federal test method
or submit a new application for a test
procedure waiver. DOE may rescind or
modify this waiver at any time if it
determines the factual basis underlying
the petition for the Interim Waiver
Order is incorrect, or the results from
the alternate test procedure are
unrepresentative of the basic model’s
true energy consumption characteristics.
10 CFR 430.27(k)(1). Likewise, Midea
may request that DOE rescind or modify
the Interim Waiver Order if Midea
discovers an error in the information
provided to DOE as part of its petition,
determines that the interim waiver is no
longer needed, or for other appropriate
reasons. 10 CFR 430.27(k)(2).
(6) Issuance of this Interim Waiver
Order does not release Midea from the
applicable requirements set forth at 10
CFR part 429.
DOE makes decisions on waivers and
interim waivers for only those basic
models specifically set out in the
petition, not future models that Midea
may manufacture. Midea may submit a
new or amended petition for waiver and
E:\FR\FM\06APN1.SGM
06APN1
EN06AP21.006
Where:
AEC83_SS = annual energy consumption for a
theoretical comparable single-speed
portable air conditioner in cooling mode
at the 83 °F dry-bulb outdoor
temperature operating condition (Test
Condition 2 in Table 1 of this appendix),
in kWh/year.
P83_SS = electrical power input for a
5.5.6 Combined Energy Efficiency
Ratio for a Theoretical Comparable
Single-Speed Portable Air Conditioner.
Calculate the combined energy
efficiency ratios for a theoretical
comparable single-speed portable air
conditioner both without cycling losses,
CEERSS, and with cycling losses,
CEERSS_CLF, in Btu/Wh, according to the
following equations:
EN06AP21.005
AEC83_SS = P83_SS × 750 × 0.001
17813
17814
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
request for grant of interim waiver, as
appropriate, for additional basic models
of portable air conditioners.
Alternatively, if appropriate, Midea may
request that DOE extend the scope of a
waiver or an interim waiver to include
additional basic models employing the
same technology as the basic model(s)
set forth in the original petition
consistent with 10 CFR 430.27(g).
Signing Authority
This document of the Department of
Energy was signed on March 31, 2021,
by Kelly J. Speakes-Backman, Principal
Deputy Assistant Secretary and Acting
Assistant Secretary for Energy Efficiency
and Renewable Energy, pursuant to
delegated authority from the Secretary
of Energy. That document with the
original signature and date is
maintained by DOE. For administrative
purposes only, and in compliance with
requirements of the Office of the Federal
Register, the undersigned DOE Federal
Register Liaison Officer has been
authorized to sign and submit the
document in electronic format for
publication, as an official document of
the Department of Energy. This
administrative process in no way alters
the legal effect of this document upon
publication in the Federal Register.
Signed in Washington, DC, on April 1,
2021.
Treena V. Garrett,
Federal Register Liaison Officer, U.S.
Department of Energy.
BEFORE THE
UNITED STATES DEPARTMENT OF
ENERGY
WASHINGTON, DC 20585
khammond on DSKJM1Z7X2PROD with NOTICES
In the Matter of: Energy Efficiency
Program: Test Procedure for Portable Air
Conditioners
Petition of Midea for Waiver, and
Application for Interim Waiver, of Test
Procedure for Portable Air Conditioners
Analysis
Introduction
The Midea Group, of which Midea is
a part, is the world’s largest producer of
major appliances, and the world’s No. 1
brand of air-treatment products, aircoolers, kettles, and rice cookers. It is
also a world-leading technologies group
in consumer appliances and HVAC
systems. It offers diversified products,
comprising consumer appliances
(kitchen appliances, refrigerators,
laundry appliances, and various small
home appliances) and HVAC
(residential air-conditioning,
commercial air-conditioning, heating &
ventilation). The Midea Group is
committed to improving lives by
adhering to the principle of ‘‘Creating
Value for Customers.’’ It focuses on
continuous technological innovation to
improve products and services to make
life more comfortable. The Midea
Group’s worldwide headquarters are
located at Midea Group headquarter
building, No. 6 Midea Avenue, Beijiao,
Shunde, Foshan, Guangdong, 528311
P.R. China; (tel. 011–86–757–2633–888);
URL: www.midea.com/global. GD Midea
Air Conditioning Equipment Co. LTD, is
located at No 6. Midea Avenue, Shunde
Foshan, Guangdong, 528311 P.R. China.
GD Midea Air Conditioning
Equipment Co. LTD. (Midea) hereby
submits this Petition for Waiver, and
Application for Interim Waiver, of the
Department of Energy (DOE) Test
Procedure for dual-duct portable air
conditioners (PACs) in 10 CFR part 430,
subpart B, Appendix CC, pursuant to 10
CFR 430.27. Midea requests expedited
treatment of the Petition and
Application.
Midea requests that DOE grant the
requested Waiver and Interim Waiver
because the current test procedure
cannot be used to test dual-duct PACs
with Midea’s duct-in-duct (combinedduct) technology, which combines the
condenser inlet and outlet ducts into a
single structure. Furthermore, the
current test procedure does not properly
measure the energy consumption of
combined-duct PACs with variablespeed compressors (VSCs).11 This
request is consistent with the approach
used for VSCs in the Waiver granted to
LG Electronics Inc. (LG) published June
2, 2020, 85 FR 33,643, for testing singleduct PACs with VSCs. It simply adds
procedures to accommodate Midea’s
combined-duct technology. Under DOE
rules, this Waiver request should be
granted. DOE also has authority to grant
an Interim Waiver because the requested
Waiver is likely be granted, because it
would avoid economic hardship and
competitive disadvantage to Midea, and
because it would reflect sound public
policy.
I. Midea Group
II. Basic Models Subject to the Waiver
Request
This Petition for Waiver, and
Application for Interim Waiver, are for
the following basic models of residential
PACs manufactured by Midea. All
models have Midea’s combined-duct
technology:
Brand
Model No.
Midea ..........................................
Midea ..........................................
Perfect aire .................................
Danby ..........................................
Heat Controller LLC ....................
Whynter .......................................
Whynter .......................................
Whynter .......................................
hOme ..........................................
Vremi ...........................................
Wappliance .................................
Perfect aire .................................
Danby ..........................................
Heat Controller LLC ....................
Whynter .......................................
Whynter .......................................
Whynter .......................................
hOme ..........................................
Vremi ...........................................
US–KC35Y1/BP3N8–PTB(CH3) .....................................................
US–KC30Y1/BP3N8–PTB(CG8) .....................................................
1PORTV10000 ................................................................................
DPA100B9IWDB–6 .........................................................................
PSV–101D .......................................................................................
ARC–1030WN .................................................................................
ARC–1030BN ..................................................................................
ARC–1030GN ..................................................................................
HME020373N ..................................................................................
VRM050703N ..................................................................................
BPI10MW ........................................................................................
1PORTVP10000 ..............................................................................
DPA100HB9IWDB–6 .......................................................................
PSHV–101D ....................................................................................
ARC–1030WNH ..............................................................................
ARC–1030GNH ...............................................................................
ARC–1030BNH ...............................................................................
HME020374N ..................................................................................
VRM050704N ..................................................................................
11 Midea intends to manufacture such units using
both standard compressors and VSCs. It expects to
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
Compressor type
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
add models that do not have VSCs to this waiver
request.
PO 00000
Frm 00048
Fmt 4703
Sfmt 4703
E:\FR\FM\06APN1.SGM
06APN1
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
Unit type
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
17815
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
Brand
Model No.
Wappliance .................................
Perfect aire .................................
Danby ..........................................
Heat Controller LLC ....................
Whynter .......................................
Whynter .......................................
Whynter .......................................
hOme ..........................................
Vremi ...........................................
Wappliance .................................
Perfectaire ...................................
Danby ..........................................
Heat Controller LLC ....................
Whynter .......................................
Whynter .......................................
Whynter .......................................
hOme ..........................................
Vremi ...........................................
Wappliance .................................
Midea ..........................................
Midea ..........................................
Midea ..........................................
BPI10HMW ......................................................................................
1PORTV12000 ................................................................................
DPA120B9IWDB–6 .........................................................................
PSV–121D .......................................................................................
ARC–1230WN .................................................................................
ARC–1230BN ..................................................................................
ARC–1230GN ..................................................................................
HME020375N ..................................................................................
VRM050705N ..................................................................................
BPI12MW ........................................................................................
1PORTVP12000 ..............................................................................
DPA120HB9IWDB–6 .......................................................................
PSHV–121D ....................................................................................
ARC–1230WNH ..............................................................................
ARC–1230GNH ...............................................................................
ARC–1230BNH ...............................................................................
HME020376N ..................................................................................
VRM050706N ..................................................................................
BPI12HMW ......................................................................................
MPPTB–12HRN8–BCH4 .................................................................
MPPTB–12CRN8–BCH4 .................................................................
MPPTB–10CRN8–BCG8 .................................................................
khammond on DSKJM1Z7X2PROD with NOTICES
III. Requested Waiver
Midea requests a waiver to test the
energy consumption of the above
residential PACs using the test
procedure detailed in the waiver for
PACs granted to LG,2 published on June
2, 2020, with modifications needed to
account for dual-duct units
incorporating Midea’s combined-duct
technology.
Strong demand for advanced energy
efficient PACs led Midea to design dualduct PACs with dramatic energy
savings, and the ability to maintain the
desired temperature without cycling the
compressor motor and fans on and off
by using inverter driven VSCs. The unit
responds automatically to surrounding
conditions by adjusting the compressor
rotational speed based upon demand.
This results in faster cooling and much
more efficient operation through
optimizing the speed of the compressor
to make minimal adjustments as the
room temperature rises and falls.
The current DOE test procedure tests
dual-duct PACs at two operating
conditions, one measuring performance
at a high outdoor operating temperature
and one measuring performance at a
lower outdoor operating temperature,
without addressing the ability of VSCs
to adjust their operating speed based on
the demand load of the conditioned
space. As such, the test procedure does
not take into account the full range of
performance and efficiency benefits of a
VSC operating under part-load
conditions. Other DOE test standards,
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
Compressor type
such as for central air conditioners—and
the test procedures approved through
waivers granted to Midea and LG for
room air conditioners and to LG for
PACs—include part-load test conditions
that account for the improved efficiency
benefit from VSCs that modulate their
operation to account for changing
conditions to the environment, rather
than cycling the compressor on and off.
Additionally, the current test
procedure prevents the testing of
Midea’s combined-duct technology
because the condenser inlet and outlet
air streams are incorporated into the
same structure. Since the airflow both in
and out of the condenser must be
measured at the same time,
modifications are needed to adapt
Midea’s combined-duct technology to
DOE’s test procedure and standard
airflow measurement lab apparatuses.
The DOE test procedure does not take
into account a specially designed
adapter that is needed for measuring the
airflows.
IV. Regulatory Framework
DOE’s regulations provide that the
Assistant Secretary ‘‘will’’ grant a
Petition to a manufacturer upon a
‘‘determination that the basic model for
which the waiver was requested
contains a design characteristic which
either prevents testing of the basic
model according to the prescribed test
procedures, or the prescribed test
procedures may evaluate the basic
model in a manner so unrepresentative
of its true energy consumption
PO 00000
Frm 00049
Fmt 4703
Sfmt 4703
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
Variable-Speed
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
...................
Unit type
Heat-Cool.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Cool-only.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Heat-Cool.
Cool-only.
Cool-only.
characteristics as to provide materially
inaccurate comparative data.’’ See 10
CFR 430.27 (emphasis supplied).
As noted, the current DOE test
procedure, 10 CFR part 430, subpart B,
Appendix CC, requires that dual-duct
PACs be tested at two operating
conditions, one measuring peak load
performance at a high outdoor operating
temperature, and one measuring a
reduced load performance at a lower
outdoor operating temperature, and
does not make any account for dualduct PACs offering variable speed
operation based upon different air test
conditions. As a result, Midea’s new
dual-duct VSC PACs cannot be tested in
a way that accurately reflects the energy
saving benefits of VSC technology. If
Midea were to test its dual-duct VSC
PACs to the current test procedure the
results would be wholly
unrepresentative of their true energy
consumption.
Moreover, the models in Section II of
this application cannot be tested using
the current test procedure because the
combined-duct design means that
airflows from the inlet and outlet of the
condenser must be measured together,
at the same time, as seen in Figure 1.
This requires a specially designed
adapter that, naturally, is not part of the
current test procedure. In addition, the
duct heat transfer for the combined duct
requires specific instructions on where
to place the thermocouples so the heat
transfer can be accounted for, which the
current test procedure does not provide.
E:\FR\FM\06APN1.SGM
06APN1
17816
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
Condenser Inlet
Airflow
Condenser
Outlet Airflow
khammond on DSKJM1Z7X2PROD with NOTICES
V. Other Manufacturers With Similar
Design Characteristics
To the best of Midea’s knowledge, (i)
Midea is the only manufacturer of dualduct PACs with combined-duct
technology, both with and without
VSCs, in the U.S. market; and (ii) Midea
and LG are the only manufacturers of
PACs with VSC technology in the U.S.
market.
VI. Proposed Modifications to the Test
Procedure
Midea proposes the following
alternative test method to evaluate the
performance of the basic models listed
in Section II. This alternative test
method is the same as the existing
procedure for PACs per Appendix CC,
except it accounts for the combinedduct technology by describing the
means to measure and calculate duct
heat transfer and by providing a
provision that requires a special adapter
be used during testing and evaluation to
measure the inlet and outlet condenser
airflows. Additionally, the modified test
procedure accounts for the increased
efficiency of using VSCs, similar to the
approach in the waver granted to LG
published June 2, 2020.12 Specifically:
Midea shall be required to test the
performance of the basic models listed
in the Section II hereto according to the
test procedure for portable air
conditioners in 10 CFR, Part 430,
Subpart B, Appendix CC, and the
waiver granted to LG published on June
2, 2020, except as follows:
12 Id.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
Add the following after ‘‘This
appendix covers the test requirements
used to measure the energy performance
of single-duct and dual-duct’’ in section
1 of Appendix CC: ‘‘, including
combined-duct,’’.
Include the following sections from
the LG waiver:
‘‘2.11 Single-speed means a type of
portable air conditioner that does not
automatically adjust either the
compressor or fan speed, or both, based
on the detected outdoor conditions.’’
‘‘2.12 Variable-speed means a type
of portable air conditioner that can
automatically adjust compressor and fan
speed, only compressor speed, or only
fan speed, based on the detected
outdoor conditions.’’
Replace the following sections from
the LG waiver, with:
‘‘2.13 Full compressor speed (full)
means the compressor speed specified
by the manufacturer at which the unit
operates at full load testing conditions.
Note—full compressor speed may be
different at different test conditions.’’
‘‘2.14 Low compressor speed (low)
means the compressor speed specified
by the manufacturer at which the unit
operates at low load test conditions,
such that Capacity83_Low, the measured
cooling capacity at test condition 3 in
Table 1 of this appendix, is no less than
50 percent and no greater than 60
percent of the measured cooling
capacity with the full compressor speed
at test condition 1 in Table 1 of this
appendix.’’
Modify section 2.15 of the LG waiver
by replacing the word ‘‘single’’ with the
PO 00000
Frm 00050
Fmt 4703
Sfmt 4703
word ‘‘dual’’. Add new section 2.16 to
Appendix CC as follows:
‘‘2.16 Combined-duct portable air
conditioner—a version of dual-duct
portable air conditioner where the ducts
for the condenser inlet and outlet air are
housed in the same structure.’’
Replace the sentence ‘‘Note that if a
product is able to operate as both a
single-duct and dual-duct portable AC
as distributed in commerce by the
manufacturer, it must be tested and
rated for all applicable duct
configurations.’’ in section 3.1.1 of
Appendix CC with:
‘‘Note that if a product is able to
operate in multiple duct configurations,
including single-duct, combined-duct,
and dual-duct portable AC as
distributed in commerce by the
manufacturer, it must be tested and
rated for all applicable duct
configurations.’’
Add the following after ‘‘Do not apply
additional sealing or insulation.’’ to
Appendix CC section 3.1.1.1:
‘‘For combined-duct portable air
conditioners a special adapter is needed
for testing to properly measure the
condenser inlet and outlet airflows. This
adapter must be provided by the
manufacturer and allow connection of
the condenser inlet and outlet airflows
to the test lab’s airflow measuring
apparatuses.’’
Replace the sentence in Appendix CC
section 3.1.1.6 with the following to
account for the combination duct
temperature measurements:
‘‘Duct temperature measurements.
Install any insulation and sealing
E:\FR\FM\06APN1.SGM
06APN1
EN06AP21.007
Figure J: PAC with combined-duct technology
17817
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
provided by the manufacturer. Then
adhere eight equally spaced
thermocouples to the outer surface of
the duct, ensuring that the
thermocouples are distributed equally
on both the inlet and outlet portion of
the combined-duct. Measure the surface
temperature of the combined duct.
Temperature measurements must have
an error no greater than ±0.5 °F over the
range being measured.’’
Include the modifications for section
3.1.2 of Appendix CC as defined in the
LG waiver:
‘‘3.1.2 Control settings. Set the
controls to the lowest available
temperature setpoint for cooling mode.
If the portable air conditioner has a
user-adjustable fan speed, select the
maximum fan speed setting. If the
portable air conditioner has an
automatic louver oscillation feature,
disable that feature throughout testing.
If the louver oscillation feature is
included but there is no option to
disable it, test with the louver
oscillation enabled. If the portable air
conditioner has adjustable louvers,
position the louvers parallel with the air
flow to maximize air flow and minimize
static pressure loss. Set the compressor
speed during cooling mode testing as
described in section 4.1, as amended by
this interim waiver.’’
Replace section 4.1 of Appendix CC
with the following to account for both
single-speed and variable-speed
compressor units as listed in Section II
of this petition:
‘‘4.1 Cooling mode. Instead of the
test conditions in Table 3 of ANSI/
AHAM PAC–1–2015, establish the test
conditions presented in Table 1 of this
appendix. Test each single-speed
sample unit twice, once at test condition
1 and once at test condition 2 in Table
1. Test each variable-speed sample unit
three times, once at each test condition
in Table 1. For each test condition,
measure the sample unit’s indoor room
cooling capacity and overall power
input in cooling mode in accordance
with Section 7.1.b and 7.1.c of ANSI/
AHAM PAC–1–2015 (incorporated by
reference; see § 430.3), respectively, and
determine the test duration in
accordance with Section 8.7 of ASHRAE
Standard 37–2009 (incorporated by
reference; § 430.3). Conduct the first
test, for both single and variable-speed
units, in accordance with ambient
conditions for test condition 1 in Table
1 of this appendix, with the compressor
speed set to full, for the duration of
cooling mode testing (Capacity95, P95),
which represents an outdoor
temperature operating condition of 95 °F
dry-bulb and 67 °F wet-bulb
temperatures. Conduct the second test
in accordance with the ambient
conditions for test condition 2 in Table
1 of this appendix, with the compressor
speed set to full, for the duration of
cooling mode testing (Capacity83, P83),
which represents an outdoor
temperature operating condition of 83 °F
dry-bulb and 67.5 °F wet-bulb
temperatures. For variable-speed units
only, conduct the third test in
accordance with the ambient conditions
for test condition 3 in Table 1 of this
appendix, with the compressor speed
set to low for the duration of the cooling
mode testing (Capacity83_Low, P83_Low),
which represents an outdoor
temperature operating condition of 83 °F
dry-bulb and 67.5 °F wet-bulb
temperatures. Set the compressor speed
required for each test condition in
accordance with the manufacturer’s
instructions.’’
Replace Table 1 of Appendix CC with
the following:
TABLE 1—EVAPORATOR (INDOOR) AND CONDENSER (OUTDOOR) INLET TEST CONDITIONS
Evaporator inlet air, °F (°C)
Test configuration
Dry bulb
Dual-Duct, Condition 1 ........................................................
Dual-Duct, Condition 2 ........................................................
Dual-Duct, Condition 3 ........................................................
Modify Appendix CC section 4.1.1
with the following after ‘‘Calculate the
surface area’’: , ACD, to the following
equation:
For combined-duct portable air
conditioners:
ACD = P × L
khammond on DSKJM1Z7X2PROD with NOTICES
Where:
ACD = the outer area of the combined-duct,
in square feet.
L = the extended length of the combined-duct
while under test, in feet.
P = the perimeter of the combined-duct, as
measured following the instructions
below, in ft.
Measure the perimeter of the
combined-duct air conditioners using a
flexible measuring tape, or equivalent,
by wrapping the measuring tape around
the outside of the combined-duct,
making sure the tape is on the outermost
ridges.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
Wet bulb
80 (26.7)
80 (26.7)
80 (26.7)
67 (19.4)
67 (19.4)
67 (19.4)
Calculate the total heat transferred
from the surface of the duct(s) to the
indoor conditioned space while
operating in cooling mode for the
outdoor test conditions in Table 1 of
this appendix, as follows.
For combined-duct portable air
conditioners:
QCD_95 = h × ACD × (TCD_95¥Tei)
QCD_83 = h × ACD × (TCD_83¥Tei)
QCD_83_Low = h × ACD × (TCD_83_
Low¥Tei)
Where:
QCD_95, QCD_83, and QCD_83_Low = for
combined-duct portable air conditioners,
the total heat transferred from the ducts
to the indoor conditioned space in
cooling mode, in Btu/h, when tested
according to test condition 1, 2, and 3 in
Table 1 of this appendix, respectively.
TCD_95, TCD_83, and TCD_83_Low = average
surface temperature for the duct, as
PO 00000
Frm 00051
Fmt 4703
Sfmt 4703
Condenser inlet air, °F (°C)
Dry bulb
95 (35.0)
83 (28.3)
83 (28.3)
Wet bulb
75 (23.9)
67.5 (19.7)
67.5 (19.7)
Condenser
speed
Full.
Full.
Low.
measured during testing according to the
three outdoor test conditions in Table 1
of this appendix, in °F.
ACD = the outer area of the combined-duct,
in square feet.
h = convection coefficient, 3 Btu/h per square
foot per °F.
Replace section 4.1.2 in Appendix CC
with the following:
‘‘4.1.2 Infiltration Air Heat Transfer.
Measure the heat contribution from
infiltration air for dual- duct portable air
conditioners that draw at least part of
the condenser air from the conditioned
space. Calculate the heat contribution
from infiltration air for dual-duct
portable air conditioners for all cooling
mode outdoor test conditions, as
described in this section. Calculate the
dry air mass flow rate of infiltration air
according to the following equations:
E:\FR\FM\06APN1.SGM
06APN1
17818
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
= [Vco_95 X Pco_95] _
rhgs
(1 + Wco_9s)
.
[Vci_95 X Pci_95]
(1 + Wci_9s)
_ [Vco_83 X Pco_83] _ [Vci_83 X Pci_83]
(1 + Wco_83)
(1 + Wci_83)
m93 Low -
.
_ [Vco 83 Low X Pco 83 Low] _
(1 + Wco_83_Low)
m93 low -
khammond on DSKJM1Z7X2PROD with NOTICES
-
Where:
˙ 95, m
˙ 83 and m
˙ 83_Low = dry air mass flow rate
m
of infiltration air for dual-duct portable
air conditioners, as calculated based on
testing according to the test conditions in
Table 1 of this appendix, in lb/m.
Vco_95, Vco_83 and Vco_83_Low = average
volumetric flow rate of the condenser
outlet air during cooling mode testing for
single-duct portable air conditioners; and
at the 95 °F and 83 °F dry-bulb outdoor
conditions for dual-duct portable air
conditioners, respectively, in cubic feet
per minute (cfm).
Vci_95, Vci_83 and Vci_83_Low = average
volumetric flow rate of the condenser
inlet air during cooling mode testing at
the 95 °F and 83 °F dry-bulb outdoor
conditions for dual-duct portable air
conditioners, respectively, in cfm.
rco_95, rco_83 and rco_83_Low = average density
of the condenser outlet air during
cooling mode testing for single-duct
portable air conditioners, and at the 95 °F
and 83 °F dry-bulb outdoor conditions
for dual-duct portable air conditioners,
respectively, in pounds mass per cubic
foot (lbm/ft3).
rci_95, rci_83 and rci_83_Low = average density
of the condenser inlet air during cooling
mode testing at the 95 °F and 83 °F drybulb outdoor conditions for dual-duct
portable air conditioners, respectively, in
lbm/ft3.
wco_95, wco_83 and wco_83_Low = average
humidity ratio of condenser outlet air
during cooling mode testing for singleduct portable air conditioners, and at the
95 °F and 83 °F dry-bulb outdoor
conditions for dual-duct portable air
conditioners, respectively, in pounds
mass of water vapor per pounds mass of
dry air (lbw/lbda).
wci_95, wci_83 and wci_83_Low = average
humidity ratio of condenser inlet air
during cooling mode testing at the 95 °F
and 83 °F dry-bulb outdoor conditions
for dual-duct portable air conditioners,
respectively, in lbw/lbda.
Calculate the sensible component of
infiltration air heat contribution
according to:
˙ × 60 × [cp_da × (Tia_95 ¥
Qs_95 = m
Tindoor) + (cp_wv × (wia_95 × Tia_95 ¥
windoor × Tindoor))]
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
[vci 83 Low X Pei 83 Low]
(1
+ Wci_83_Low)
˙ × 60 × [(cp_da × (Tia_83 ¥
Qs_83 = m
Tindoor) + (cp_wv × (wia_83 × Tia_83 ¥
windoor × Tindoor))]
˙ × 60 × [(cp_da × (Tia_83 ¥
Qs_83_Low = m
Tindoor) + (cp_wv × (wia_83 × Tia_83 ¥
windoor × Tindoor))
Where:
Qs_95, Qs_83 and Qs_83_Low = sensible heat
added to the room by infiltration air,
calculated at the 1, 2, and 3 test
conditions respectively in Table 1 of this
appendix, in Btu/h.
˙ = dry air mass flow rate of infiltration air,
m
˙ SD or m
˙ 95 when calculating Qs_95 and
m
˙ SD or m
˙ 83 when calculating Qs_83 and
m
˙ 83_Low when calculating Qs_83_Low, in
m
lb/m.
cp_da = specific heat of dry air, 0.24 Btu/lbm
¥ °F.
cp_wv = specific heat of water vapor, 0.444
Btu/lbm ¥ °F. Tindoor = indoor chamber
dry-bulb temperature, 80 °F.
Tia_95 and Tia_83 = infiltration air dry-bulb
temperatures for the three test conditions
in Table 1 of this appendix, 95 °F and
83 °F, respectively.
wia_95 and wia_83 = humidity ratios of the
95 °F and 83 °F dry-bulb infiltration air,
0.0141 and 0.01086 lbw/lbda,
respectively.
windoor = humidity ratio of the indoor chamber
air, 0.0112 lbw/lbda.
60 = conversion factor from minutes to hours.
Calculate the latent heat contribution
of the infiltration air according to:
˙ × 60 × Hfg × (wia_95 ¥ windoor)
Ql_95 = m
˙ × 60 × Hfg × (wia_83 ¥ windoor)
Ql_83 = m
˙ × 60 × Hfg × (wia_83 ¥
Ql_83_Low = m
windoor)
Where:
Ql_95, Ql_83 and Ql_83_LOW = latent heat
added to the room by infiltration air,
calculated at the 1, 2, and 3 test
conditions respectively in Table 1 of this
appendix, in Btu/h.
˙ = mass flow rate of infiltration air, m
˙ SD or
m
˙ 95 when calculating Ql_95 and m
˙ SD or
m
˙ 83 when calculating Ql_83 and m
˙ 83_Low
m
when calculating Qs_83_Low, in lb/m.
Hfg = latent heat of vaporization for water
vapor, 1061 Btu/lbm.
wia_95 and wia_83 = humidity ratios of the
95 °F and 83 °F dry-bulb infiltration air,
0.0141 and 0.01086 lbw/lbda,
respectively.
PO 00000
Frm 00052
Fmt 4703
Sfmt 4703
windoor = humidity ratio of the indoor chamber
air, 0.0112 lbw/lbda.
60 = conversion factor from minutes to hours.
The total heat contribution of the
infiltration air is the sum of the sensible
and latent heat:
Qinfiltration_95 = Qs_95 + Ql_95
Qinfiltration_83 = Qs_83 + Ql_83
Qinfiltration_83_Low = Qs_83_Low + Ql_83_Low
Where:
Qinfiltration_95, Qinfiltration_83 and Qinfiltration_83_Low
= total infiltration air heat in cooling
mode, calculated at the 1, 2, and 3 test
conditions respectively in Table 1 of this
appendix, in Btu/h.
Qs_95, Qs_83 and Qs_83_Low = sensible heat
added to the room by infiltration air,
calculated at the 1, 2, and 3 test
conditions respectively in Table 1 of this
appendix, in Btu/h.
Ql_95, Ql_83 and Ql_83_Low = latent heat added
to the room by infiltration air, calculated
at the 1, 2, and 3 test conditions
respectively in Table 1 of this appendix,
in Btu/h.
Modify section 5.1 of Appendix CC
after ‘‘Calculate the adjusted cooling
capacities for portable air conditioners,
ACC95, ACC83,’’ with the following:
‘‘and ACC83_Low expressed in Btu/h,
according to the following equations:
ACC95 = Capacity95—QCD_95 ¥
Qinfiltration_95
ACC83 = Capacity83 — QCD_83 ¥
Qinfiltration_83
ACC83_Low = Capacity83_Low ¥ QCD_83_
Low ¥ Qinfiltration_83_Low
Where:
Capacity95, Capacity83, and Capacity83_Low =
cooling capacity measured in section
4.1.1 of this appendix.
QCD_95, QCD_83, and QCD_83_Low = duct heat
transfer while operating in cooling mode,
calculated in section 4.1.1.1 of this
appendix.
Qinfiltration_95, Qinfiltration_83, and Qinfiltration_83_
Low = total infiltration air heat transfer in
cooling mode, calculated in section
4.1.1.2 of this appendix.’’
Replace the table of Annual Operating
Hours in Appendix CC section 5.3 with
the following:
E:\FR\FM\06APN1.SGM
06APN1
EN06AP21.008
-
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
Change the definition of variable ‘‘m’’
in Appendix CC section 5.3 to the
following:
‘‘m represents the operating mode
750 (‘‘95’’ for test condition 1, ‘‘83’’ for test
condition 2, ‘‘83_Low’’ for test
750 condition 3, ‘‘oc’’ off cycle, and ‘‘ia’’
inactive or ‘‘om’’ off mode).’’
750
Replace section 5.4 of Appendix CC
880
1,355 with the following:
Annual
operating
hours
CEERss
I
I
I
I
=
5
3
] x 0·8
]
AECAC~
x 0. 2 + AECAC~
95 + AECr
83 + AECr
( 750 X 0.001 )
( 750 X 0.001 )
For Variable Speed Units:
CEERuA
=
ACC95
]
ACCa3 Low
]
AEC95 + AECT) x 0. 2 + (AEC83 Low + AECT ) x 0. 8
(
750 X 0.001
750 X 0.001
khammond on DSKJM1Z7X2PROD with NOTICES
Where:
CEERSS = combined energy efficiency ratio
for the single-speed portable air
conditioner, in Btu/Wh.
ACC95, ACC83 and ACC83_Low = adjusted
cooling capacity, in Btu/h, calculated in
section 5.1 of this appendix.
CEERUA = combined energy efficiency ratio
for the variable-speed portable air
conditioner, in Btu/Wh.
AEC95, AEC83, and AEC83_Low = annual
energy consumption for the cooling
mode tests, in kWh/year, calculated in
section 5.3 of this appendix.
AECT = total annual energy consumption
attributed to all modes except cooling, in
kWh/year, calculated in section 5.3 of
this appendix.
750 = number of cooling mode hours per
year.
0.01 kWh/Wh = conversion factor for watthours to kilowatt-hours.
0.2 = weighting factor for the 95 °F dry-bulb
outdoor condition test.
0.8 = weighting factor for the 83 °F dry-bulb
outdoor condition test.’’
Modify section 5.5 of the LG waiver
by adding the following after ‘‘Adjust
the combined energy efficiency ratio’’
and before ‘‘as follows.’’: ‘‘for variable
speed units’’
Modify section 5.5.1 of the LG waiver
by replacing everything after ‘‘Calculate
the cooling capacity and cooling
capacity with cycling losses, expressed
in British thermal units per hour (Btu/
h), and electrical power input,
expressed in watts, for a theoretical
comparable single-speed portable air
conditioner’’ with the following:
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
‘‘at test condition 2 in Table 1 of this
appendix. A theoretical comparable
single-speed compressor has the same
cooling capacity and electrical input,
with cycling losses, as the tested per test
condition 2 in Table 4.1 of this
appendix and further adjusted to
account for the different compressor
speeds.
Capacity83_SS = Capacity83 × FCap
Capacity83_SS_CLF = Capacity83_SS ×
0.875
P83_SS = P83 × FCap
Where:
Capacity83_SS = theoretical comparable
single-speed portable air conditioner
cooling capacity, in Btu/h, calculated for
test condition 2 in Table 1.
Capacity83_SS_CLF = theoretical comparable
single-speed portable air conditioner
cooling capacity with cycling losses, in
Btu/h, calculated for test condition 2 in
Table 1.
Capacity83 = variable-speed portable air
conditioner cooling capacity, in Btu/h,
determined in section 4.1 of this
appendix for test condition 2 in Table 1.
P83_SS = theoretical comparable single-speed
portable air conditioner electrical power
input, in watts, calculated for test
condition 2 in Table 1.
P83 = variable-speed portable air conditioner
electrical power input, in watts,
determined in section 4.1 of this
appendix for test condition 2 in Table 1.
0.875 = cycling loss factor for the 83 °F drybulb outdoor temperature operating
condition.
FCap = adjustment factor to account for
different compressor speeds at test
condition 2 in Table 1 of this appendix
PO 00000
Frm 00053
Fmt 4703
Sfmt 4703
between single-speed and variable-speed
compressors, 0.92.’’
Delete section 5.5.2 from the LG
waiver. This section is not needed, and
instead the duct loss for a comparable
single speed unit is accounted for in
section 4.1.1.
Delete section 5.5.3 from the LG
waiver. This section is not needed, and
instead the infiltration for a comparable
single speed unit is accounted for in
section 4.1.2.
Replace section 5.5.4 in the LG waiver
with the following:
‘‘5.5.4 Adjusted Cooling Capacity for
a Theoretical Comparable Single-Speed
Portable Air Conditioner at the Lower
Outdoor Test Condition. Calculate the
adjusted cooling capacity for a
theoretical comparable single-speed
portable air conditioner operating at test
condition 2 in Table 1 of this appendix
with and without cycling losses,
ACC83_SS and ACC 83_SS_CLF,
respectively, expressed in Btu/h,
according to the following equation:
ACC83_SS = Capacity83_SS ¥ QCD_83 ¥
Qinfiltration_83
ACC83_SS_CLF = Capacity83_SS_CLF ¥
QCD_83 ¥ Qinfiltration_83
Where:
ACC83_SS and ACC83_SS_CLF = adjusted
cooling capacity for a theoretical
comparable single-speed portable air
conditioner at test condition 2 in Table
1 of this appendix without and with
cycling losses, respectively, in Btu/h.
Capacity83_SS and Capacity83_SS_CLF =
theoretical comparable single-speed
E:\FR\FM\06APN1.SGM
06APN1
EN06AP21.010
Cooling Mode, Dual-Duct test
condition 1 .................................
Cooling Mode, Dual-Duct test
condition 2 .................................
Cooling Mode, Dual-Duct, test
condition 3 .................................
Off-Cycle .......................................
Inactive or Off ...............................
‘‘5.4 Combined Energy Efficiency
Ratio. Using the annual operating hours,
as outlined in section.
5.3 of this appendix, calculate the
combined energy efficiency ratios,
CEERSS and CEERUA, expressed in Btu/
Wh, according to the following:
For Single-Speed Units:
EN06AP21.009
Operating mode
17819
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
portable air conditioner cooling capacity
without and with cycling losses,
respectively, in Btu/h, at test condition
2 in Table 1 of this appendix, calculated
in section 5.5.1 of this appendix.
QCD_83 = total heat transferred from the ducts
to the indoor conditioned space in
cooling mode for a theoretical
comparable single-speed portable air
conditioner at test condition 2 in Table
1 of this appendix, in Btu/h, calculated
in section 4.1.1 of this appendix.
Qinfiltration_83_SS = total infiltration air heat in
cooling mode for a theoretical
comparable single-speed portable air
conditioner at test condition 2 in Table
1 of this appendix, in Btu/h, calculated
in section 4.1.2 of this appendix.’’
Modify section 5.5.5 in the LG waiver
by replacing everything after ‘‘Calculate
the annual energy consumption in
cooling mode for a theoretical
comparable single-speed portable air
conditioner at’’ with the following:
‘‘test condition 2 in Table 1 of this
appendix, in kWh/year, according to the
following equations:
AEC83_SS = P83_SS × 750 × 0.001
Where:
AEC83_SS = annual energy consumption for a
theoretical comparable single-speed
portable air conditioner in cooling mode
at test condition 2 in Table 1 of this
appendix, in kWh/year.
P83_SS = electrical power input for a
theoretical comparable single-speed
portable air conditioner electrical power
input at condition 2 in Table 1 of this
appendix, in watts, calculated in section
xo.z+[
khammond on DSKJM1Z7X2PROD with NOTICES
CBBR=, =
Where:
CEERSS and CEERSS_CLF = combined energy
efficiency ratio for a theoretical
comparable single-speed portable air
conditioner without and with cycling
losses considered, respectively, in Btu/
Wh.
ACC95 = adjusted cooling capacity for the
sample unit, as calculated in section 5.1
of this appendix, when tested at test
condition 1 in Table 1 of this appendix
that is representative of operation at the
95 °F dry-bulb outdoor temperature
operating condition, in Btu/h.
ACC83 and ACC83_SS_CLF = adjusted cooling
capacity for a theoretical comparable
single-speed portable air conditioner at
test condition 2 in Table 1 of this
appendix without and with cycling
losses, respectively, as calculated in
section 5.5.4 of this appendix, in Btu/h.
AEC95 = annual energy consumption for the
sample unit, as calculated in section 5.3
of this appendix, for cooling mode
operation at test condition 1 in Table 1
of this appendix that represents
operation at a 95 °F dry-bulb outdoor
temperature operating condition, in
kWh/year.
AEC83_SS = annual energy consumption for a
theoretical comparable single-speed
portable air conditioner in cooling mode
at test condition 2 in Table 1 of this
appendix, calculated in section 5.5.5 of
this appendix, in kWh/year.
AECT = total annual energy consumption
attributed to all operating modes except
cooling for the sample unit, calculated in
section 5.3 of this appendix, in kWh/
year.
750 and 0.001 as defined previously in this
section.
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
l(•:~il.
02 +
5.5.1 of this appendix.
750 = number of cooling mode hours per
year, as defined in section 5.3 of this
appendix.
0.001 kWh/Wh = conversion factor from
watt-hours to kilowatt-hours.
Replace section 5.5.6 of the LG waiver
with the following:
‘‘5.5.6 Combined Energy Efficiency
Ratio for a Theoretical Comparable
Single-Speed Portable Air Conditioner.
Calculate the combined energy
efficiency ratio for a theoretical
comparable single-speed portable air
conditioner without and with cycling,
CEERSS, and with cycling losses,
CEERSS_CLF, in Btu/Wh, according to the
following equations:
ACCaus
I(
x:OJJ
0.2 = weighting factor for the 95 °F dry-bulb
outdoor temperature operating
condition.
0.8 = weighting factor for the 83 °F dry-bulb
outdoor temperature operating
condition.’’
and measure the duct heat transfer.
Midea has also demonstrated that its
approach is consistent with waivers
granted by DOE to other manufacturers
with VSC technology.
VII. Additional Justification for Interim
Waiver Application
b. Economic Hardship Would Be Caused
by Denial of an Interim Waiver
a. There Is a Strong Likelihood That the
Waiver Will Be Granted
In the absence of an Interim Waiver,
Midea will lack certainty as to whether
it can launch these combined-duct PACs
with VSCs. Midea believes there will be
strong consumer demand for these
PACs, and the inability to market due to
the denial of an Interim Waiver will
cause economic hardship and
competitive disadvantage to Midea. This
is because there are exceptionally long
lead times and significant expenses
associated with the design and
manufacturer of PACs. Compliance with
energy consumption standards is a
critical design factor for all of Midea’s
PACs. Any delay in obtaining clarity on
this issue will force Midea to postpone
key decisions regarding its investments
to build, launch and market these PACs.
In the event that this Interim Waiver is
not approved, Midea would not be able
to move forward with the launch of
these models, resulting in a multimillion-dollar impact to the company
and would require costly contingency
plans and put us at a competitive
disadvantage to competitors.
This Petition provides strong
evidence that the Waiver will be
granted. A Waiver is appropriate
because the current test procedure does
not accurately reflect the energy
efficiency of models with VSCs since it
tests only in the full load condition at
two test points. These compressors can
vary the rotational speed based upon the
difference in unit set-point and the
ambient temperature of the conditioned
space, and will optimize the energy
usage based on these conditions that can
result in a greater compressor speed at
less load. A PAC without a VSC cannot
operate in this fashion as the
compressor is either on at full capacity
or off. The test procedure in the waiver
granted to LG published on June 2,
2020, will account for energy being used
at different test conditions with some
modification for Midea’s units.
Additionally, the current test
procedure does not account for Midea’s
unique combined- duct technology that
requires special provisions to measure
the inlet and outlet condenser airflow
PO 00000
Frm 00054
Fmt 4703
Sfmt 4703
E:\FR\FM\06APN1.SGM
06APN1
EN06AP21.011
17820
Federal Register / Vol. 86, No. 64 / Tuesday, April 6, 2021 / Notices
Pedricktown Cogeneration Company LP,
Susquehanna Nuclear, LLC, Talen
Montana, LLC, York Generation
The grant of an Interim Waiver is also
Company LLC, TrailStone Energy
supported by sound public policy. The
Marketing, LLC.
models for which an interim waiver is
Description: Supplement to April 27,
sought utilize technological advances
2020 Notification of Change in Status of
that increase energy efficiency, reduce
the Indicated MBR Sellers.
energy consumption, lower costs for
Filed Date: 3/29/21.
consumers, and provide enhanced
Accession Number: 20210329–5273.
Dated:
March
31,
2021.
comfort.
Comments Due: 5 p.m. ET 4/19/21.
Kimberly D. Bose,
Conclusion
Docket Numbers: ER21–772–000.
Secretary.
Applicants: Resi Station, LLC.
Midea respectfully requests that DOE
[FR Doc. 2021–07076 Filed 4–5–21; 8:45 am]
Description: Response to February 24,
grant this Petition for Waiver and
BILLING CODE P
2021 Deficiency Letter of Resi Station,
Application for Interim Waiver. By
LLC.
granting this Waiver, DOE will ensure
Filed Date: 3/26/21.
that consumers will have access to new, DEPARTMENT OF ENERGY
Accession Number: 20210326–5228.
innovative and energy efficient
Comments Due: 5 p.m. ET 4/16/21.
Federal Energy Regulatory
combined-duct PACs with and without
Docket Numbers: ER21–787–001.
Commission
VSCs.
Applicants: ISO New England Inc.
Respectfully submitted,
Combined Notice of Filings #1
Description: Tariff Amendment: ISO
/s/ lllllllllllllllllll
New
England Inc.; Response to
Take notice that the Commission
Scott Blake Harris
Commission
Deficiency Notice; ER21–
received the following electric rate
John Hodges
787–000
to
be
effective 5/29/2021.
filings:
Harris, Wiltshire & Grannis LLP, 1919 M
Filed Date: 3/30/21.
Docket Numbers: ER15–705–008.
Street NW, Washington, DC 20036, Counsel
Accession Number: 20210330–5269.
Applicants: Pacific Gas and Electric
for GD Midea Air Conditioning Equipment
Comments Due: 5 p.m. ET 4/20/21.
Co. LTD.
Company.
Docket Numbers: ER21–1553–000.
Description: Compliance filing:
[FR Doc. 2021–07025 Filed 4–5–21; 8:45 am]
Applicants: Luna Storage, LLC.
Compliance filing CCSF IA and TFAs
BILLING CODE 6450–01–P
Description: § 205(d) Rate Filing: Luna
Following Order on Compliance (TO SA
Storage, LLC MISA Certificate of
284) to be effective 7/23/2015.
Concurrence to be effective 3/31/2021.
Filed Date: 3/30/21.
DEPARTMENT OF ENERGY
Filed Date: 3/30/21.
Accession Number: 20210330–5158
Accession Number: 20210330–5002.
Federal Energy Regulatory
Comments Due: 5 p.m. ET 4/20/21.
Comments Due: 5 p.m. ET 4/20/21.
Commission
Docket Numbers: ER15–705–009.
Docket Numbers: ER21–1554–000.
Applicants: Pacific Gas and Electric
Notice of Waiver Period for Water
Applicants: Luna Storage, LLC.
Company.
Quality Certification Application
Description: § 205(d) Rate Filing: Luna
Description: Compliance filing:
Storage, LLC LGIA Certificate of
Compliance
filing
CCSF
IA
and
TFAs
Project No.
Following Order on Compliance (TO SA Concurrence to be effective 3/31/2021.
Filed Date: 3/30/21.
Eagle Creek Hydro Power, LLC ......... 10482–122
284) to be effective 7/1/2015.
Eagle Creek Water Resources, LLC
Accession Number: 20210330–5003.
Filed Date: 3/30/21.
Eagle Creek Land Resources, LLC
Comments Due: 5 p.m. ET 4/20/21.
Accession
Number:
20210330–5159.
Eagle Creek Hydro Power, LLC ......... 10481–069
Docket Numbers: ER21–1555–000.
Eagle Creek Water Resources, LLC
Comments Due: 5 p.m. ET 4/20/21.
Eagle Creek Land Resources, LLC
Applicants: New Mexico Wind, LLC.
Docket Numbers: ER15–2013–010;
Eagle Creek Hydro Power, LLC ......... 9690–115
Description: Baseline eTariff Filing:
ER12–2510–009;
ER15–2014–005;
Eagle Creek Water Resources, LLC
Reactive
Power Compensation Filing to
Eagle Creek Land Resources, LLC
ER10–2435–016; ER10–2440–012;
be effective 3/31/2021.
ER10–2442–014; ER12–2512–009;
Filed Date: 3/30/21.
On March 30, 2021, Eagle Creek
ER19–481–002; ER15–2018–005; ER18–
Accession Number: 20210330–5004.
Hydro Power, LLC, Eagle Creek Water
2252–001; ER10–3286–013; ER15–2022–
Comments Due: 5 p.m. ET 4/20/21.
Resources, LLC, and Eagle Creek Land
005; ER10–3299–012; ER10–2444–016;
Docket Numbers: ER21–1556–000.
Resources, LLC (co-licensees) submitted ER10–2446–012; ER15–2026–005;
Applicants: TGE Pennsylvania 202,
to the Federal Energy Regulatory
ER15–2020–008; ER10–2449–014;
LLC, TGE Pennsylvania 203, LLC.
Commission a copy of their application
ER19–2250–002.
Description: Petition for Waiver, et al.
for a Clean Water Act section 401(a)(1)
Applicants: Talen Energy Marketing,
of TGE Pennsylvania 202, LLC, et al.
water quality certification filed with the LLC, Brandon Shores LLC, Brunner
Filed Date: 3/29/21.
New York State Department of
Island, LLC, Camden Plant Holding,
Accession Number: 20210329–5316.
Environmental Conservation (New York L.L.C., Dartmouth Power Associates
Comments Due: 5 p.m. ET 4/8/21.
DEC), in conjunction with the above
Limited Partnership, Elmwood Park
captioned projects. Pursuant to 40 CFR
Docket Numbers: ER21–1557–000.
Power, LLC, H.A. Wagner LLC, LMBE
121.6, we hereby notify the New York
Applicants: Leeward Renewable
Project Company LLC, Martins Creek,
DEC of the following:
Energy, LLC.
LLC, MC Project Company LLC,
Date of Receipt of the Certification
Description: Petition for Limited
Millennium Power Partners, LP,
Request: March 30, 2021.
Waiver, et al. of Leeward Renewable
Montour, LLC, New Athens Generating
Reasonable Period of Time to Act on
Energy, LLC.
Company, LLC, Newark Bay
the Certification Request: One year.
Filed Date: 3/29/21.
Cogeneration Partnership, L.P,
C. Sound Public Policy Supports Grant
of the Interim Waiver
khammond on DSKJM1Z7X2PROD with NOTICES
17821
VerDate Sep<11>2014
17:34 Apr 05, 2021
Jkt 253001
Date Waiver Occurs for Failure to Act:
March 30, 2022.
If the New York DEC fails or refuses
to act on the water quality certification
request by the above waiver date, then
the agency’s certifying authority is
deemed waived pursuant to section
401(a)(1) of the Clean Water Act, 33
U.S.C. 1341(a)(1).
PO 00000
Frm 00055
Fmt 4703
Sfmt 4703
E:\FR\FM\06APN1.SGM
06APN1
Agencies
[Federal Register Volume 86, Number 64 (Tuesday, April 6, 2021)]
[Notices]
[Pages 17803-17821]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2021-07025]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
[Case Number 2020-006; EERE-2020-BT-WAV-0023]
Energy Conservation Program: Notification of Petition for Waiver
of GD Midea Air Conditioning Equipment Co. LTD From the Department of
Energy Portable Air Conditioner Test Procedure and Notification of
Grant of Interim Waiver
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notification of petition for waiver and grant of an interim
waiver; request for comments.
-----------------------------------------------------------------------
SUMMARY: This notification announces receipt of and publishes a
petition for waiver and interim waiver from GD Midea Air Conditioning
Equipment Co. LTD (``Midea''), which seeks a waiver for specified
portable air conditioner basic models from the U.S. Department of
Energy (``DOE'') test procedure used for determining the efficiency of
portable air conditioners. DOE also gives notice of an Interim Waiver
Order that requires Midea to test and rate the specified portable air
conditioner basic models in accordance with the alternate test
procedure set forth in the Interim Waiver Order. DOE solicits comments,
data, and information concerning Midea's petition and its suggested
alternate test procedure to inform DOE's final decision on Midea's
waiver request.
DATES: The Interim Waiver Order is effective on April 6, 2021. Written
[[Page 17804]]
comments and information are requested and will be accepted on or
before May 6, 2021.
ADDRESSES: Interested persons are encouraged to submit comments using
the Federal eRulemaking Portal at https://www.regulations.gov.
Alternatively, interested persons may submit comments, identified by
case number ``2020-006'', and Docket number ``EERE-2020-BT-WAV-0023,''
by any of the following methods:
Federal eRulemaking Portal: https://www.regulations.gov.
Follow the instructions for submitting comments.
Email: [email protected]. Include Case No.
2020-006 in the subject line of the message.
No telefacsimilies (``faxes'') will be accepted. For detailed
instructions on submitting comments and additional information on this
process, see the SUPPLEMENTARY INFORMATION section of this document.
Although DOE has routinely accepted public comment submissions
through a variety of mechanism, including the Federal eRulemaking
Portal, email, postal mail, or hand delivery/courier, the Department
has found it necessary to make temporary modifications to the comment
submission process in light of the ongoing Covid-19 pandemic. DOE is
currently suspending receipt of public comments via postal mail and
hand delivery/courier. If a commenter finds that this change poses an
undue hardship, please contact Appliance Standards Program staff at
(202) 586-1445 to discuss the need for alternative arrangements. Once
the Covid-19 pandemic health emergency is resolved, DOE anticipates
resuming all of its regular options for public comment submission,
including postal mail and hand delivery/courier.
Docket: The docket, which includes Federal Register notices,
comments, and other supporting documents/materials, is available for
review at https://www.regulations.gov. All documents in the docket are
listed in the https://www.regulations.gov index. However, some documents
listed in the index, such as those containing information that is
exempt from public disclosure, may not be publicly available.
The docket web page can be found at https://www.regulations.gov/docket?D=EERE-2020-BT-WAV-0023. The docket web page contains
instruction on how to access all documents, including public comments,
in the docket. See the SUPPLEMENTARY INFORMATION section for
information on how to submit comments through https://www.regulations.gov.
FOR FURTHER INFORMATION CONTACT:
Ms. Lucy deButts, U.S. Department of Energy, Office of Energy
Efficiency and Renewable Energy, Building Technologies Office, Mailstop
EE-5B, 1000 Independence Avenue SW, Washington, DC 20585-0121. Email:
[email protected].
Ms. Sarah Butler, U.S. Department of Energy, Office of the General
Counsel, Mail Stop GC-33, Forrestal Building, 1000 Independence Avenue
SW, Washington, DC 20585-0103. Telephone: (202) 586-1777. Email:
[email protected].
SUPPLEMENTARY INFORMATION: DOE is publishing Midea's petition for
waiver in its entirety, pursuant to 10 CFR 430.27(b)(1)(iv),\1\ absent
any confidential business information. DOE invites all interested
parties to submit in writing by May 6, 2021, comments and information
on all aspects of the petition, including the alternate test procedure.
Pursuant to 10 CFR 430.27(d), any person submitting written comments to
DOE must also send a copy of such comments to the petitioner. The
contact information for the petitioner is Daniel L. Atkins,
[email protected], Midea America Research Center, 2700 Chestnut
Station Court, Louisville, KY 40299.
---------------------------------------------------------------------------
\1\ On December 11, 2020, DOE published an amendment to 10 CFR
430.27 regarding the processing of petitions for an interim waiver,
which became effective beginning January 11, 2021. 85 FR 79802.
Midea's petition for waiver and petition for interim waiver were
received prior to the effective date of that amendment. The interim
waiver therefore is being processed pursuant to the regulation in
effect at the time of receipt, i.e., 10 CFR 430.27 in the 10 CFR
parts 200 to 499 edition revised as of January 1, 2020.
---------------------------------------------------------------------------
Submitting comments via https://www.regulations.gov. The https://www.regulations.gov web page will require you to provide your name and
contact information. Your contact information will be viewable to DOE
Building Technologies staff only. Your contact information will not be
publicly viewable except for your first and last names, organization
name (if any), and submitter representative name (if any). If your
comment is not processed properly because of technical difficulties,
DOE will use this information to contact you. If DOE cannot read your
comment due to technical difficulties and cannot contact you for
clarification, DOE may not be able to consider your comment.
However, your contact information will be publicly viewable if you
include it in the comment or in any documents attached to your comment.
Any information that you do not want to be publicly viewable should not
be included in your comment, nor in any document attached to your
comment. If this instruction is followed, persons viewing comments will
see only first and last names, organization names, correspondence
containing comments, and any documents submitted with the comments.
Do not submit to https://www.regulations.gov information for which
disclosure is restricted by statute, such as trade secrets and
commercial or financial information (hereinafter referred to as
Confidential Business Information (``CBI'')). Comments submitted
through https://www.regulations.gov cannot be claimed as CBI. Comments
received through the website will waive any CBI claims for the
information submitted. For information on submitting CBI, see the
Confidential Business Information section.
DOE processes submissions made through https://www.regulations.gov
before posting. Normally, comments will be posted within a few days of
being submitted. However, if large volumes of comments are being
processed simultaneously, your comment may not be viewable for up to
several weeks. Please keep the comment tracking number that https://www.regulations.gov provides after you have successfully uploaded your
comment.
Submitting comments via email. Comments and documents submitted via
email also will be posted to https://www.regulations.gov. If you do not
want your personal contact information to be publicly viewable, do not
include it in your comment or any accompanying documents. Instead,
provide your contact information on a cover letter. Include your first
and last names, email address, telephone number, and optional mailing
address. The cover letter will not be publicly viewable as long as it
does not include any comments.
Include contact information each time you submit comments, data,
documents, and other information to DOE.
Comments, data, and other information submitted to DOE
electronically should be provided in PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file format. Provide documents that
are not secured, written in English and free of any defects or viruses.
Documents should not contain special characters or any form of
encryption and, if possible, they should carry the electronic signature
of the author.
Campaign form letters. Please submit campaign form letters by the
originating organization in batches of between 50 to
[[Page 17805]]
500 form letters per PDF or as one form letter with a list of
supporters' names compiled into one or more PDFs. This reduces comment
processing and posting time.
Confidential Business Information. According to 10 CFR 1004.11, any
person submitting information that he or she believe s to be
confidential and exempt by law from public disclosure should submit via
email two well-marked copies: One copy of the document marked
confidential including all the information believed to be confidential,
and one copy of the document marked ``non-confidential'' with the
information believed to be confidential deleted. DOE will make its own
determination about the confidential status of the information and
treat it according to its determination.
It is DOE's policy that all comments may be included in the public
docket, without change and as received, including any personal
information provided in the comments (except information deemed to be
exempt from public disclosure).
Case Number 2020-006
Interim Waiver Order
I. Background and Authority
The Energy Policy and Conservation Act, as amended (``EPCA''),\1\
authorizes the U.S. Department of Energy (``DOE'') to regulate the
energy efficiency of a number of consumer products and certain
industrial equipment. (42 U.S.C. 6291-6317) Title III, Part B \2\ of
EPCA established the Energy Conservation Program for Consumer Products
Other Than Automobiles, which sets forth a variety of provisions
designed to improve energy efficiency for certain types of consumer
products. In addition to specifying a list of covered products and
industrial equipment, EPCA contains provisions that enable the
Secretary of Energy to classify additional types of consumer products
as covered products. (42 U.S.C. 6292(a)(20)) In a final determination
of coverage published in the Federal Register on April 18, 2016, DOE
classified portable air conditioners as covered products under EPCA. 81
FR 22514.
---------------------------------------------------------------------------
\1\ All references to EPCA in this document refer to the statute
as amended through the Energy Act of 2020, Public Law 116-260 (Dec.
27, 2020).
\2\ For editorial reasons, upon codification in the U.S. Code,
Part B was redesignated as Part A.
---------------------------------------------------------------------------
The energy conservation program under EPCA consists essentially of
four parts: (1) Testing, (2) labeling, (3) Federal energy conservation
standards, and (4) certification and enforcement procedures. Relevant
provisions of EPCA include definitions (42 U.S.C. 6291), test
procedures (42 U.S.C. 6293), labeling provisions (42 U.S.C. 6294),
energy conservation standards (42 U.S.C. 6295), and the authority to
require information and reports from manufacturers (42 U.S.C. 6296).
The Federal testing requirements consist of test procedures that
manufacturers of covered products must use as the basis for: (1)
Certifying to DOE that their products comply with the applicable energy
conservation standards adopted pursuant to EPCA (42 U.S.C. 6295(s)),
and (2) making representations about the efficiency of that product (42
U.S.C. 6293(c)). Similarly, DOE must use these test procedures to
determine whether the product complies with relevant standards
promulgated under EPCA. (42 U.S.C. 6295(s))
Under 42 U.S.C. 6293, EPCA sets forth the criteria and procedures
DOE is required to follow when prescribing or amending test procedures
for covered products. EPCA requires that any test procedures prescribed
or amended under this section must be reasonably designed to produce
test results which reflect the energy efficiency, energy use or
estimated annual operating cost of a covered product during a
representative average use cycle or period of use and requires that
test procedures not be unduly burdensome to conduct. (42
U.S.C.6293(b)(3)) The test procedure for portable air conditioners is
contained in the Code of Federal Regulations (``CFR'') at 10 CFR part
430, subpart B, appendix CC (``Appendix CC'').
Under 10 CFR 430.27, any interested person may submit a petition
for waiver from DOE's test procedure requirements. DOE will grant a
waiver from the test procedure requirements if DOE determines either
that the basic model for which the waiver was requested contains a
design characteristic that prevents testing of the basic model
according to the prescribed test procedures, or that the prescribed
test procedures evaluate the basic model in a manner so
unrepresentative of its true energy consumption characteristics as to
provide materially inaccurate comparative data. 10 CFR 430.27(f)(2). A
petitioner must include in its petition any alternate test procedures
known to the petitioner to evaluate the performance of the product type
in a manner representative of the energy consumption characteristics of
the basic model. 10 CFR 430.27(b)(1)(iii). DOE may grant the waiver
subject to conditions, including adherence to alternate test
procedures. 10 CFR 430.27(f)(2).
As soon as practicable after the granting of any waiver, DOE will
publish in the Federal Register a notice of proposed rulemaking to
amend its regulations to eliminate any need for the continuation of
such waiver. 10 CFR 430.27(l). As soon thereafter as practicable, DOE
will publish in the Federal Register a final rule to that effect. Id.
The waiver process also provides that DOE may grant an interim
waiver if it appears likely that the underlying petition for waiver
will be granted and/or if DOE determines that it would be desirable for
public policy reasons to grant immediate relief pending a determination
on the underlying petition for waiver. 10 CFR 430.27(e)(2). Within one
year of issuance of an interim waiver, DOE will either: (i) Publish in
the Federal Register a determination on the petition for waiver; or
(ii) publish in the Federal Register a new or amended test procedure
that addresses the issues presented in the waiver. 10 CFR 430.27(h).
When DOE amends the test procedure to address the issues presented
in a waiver, the waiver will automatically terminate on the date on
which use of that test procedure is required to demonstrate compliance.
Id.
II. Midea's Petition for Waiver and Interim Waiver
On June 29, 2020, Midea filed a petition for waiver and petition
for interim waiver from the test procedure for portable air
conditioners set forth at Appendix CC. (Midea, No. 1 at pp. 2-3 \3\) On
July 10, 2020, Midea submitted a revised petition for waiver and
application for interim waiver.\4\ On September 11, 2020, Midea
submitted a request \5\ to include five additional basic models in
their petition for waiver and petition for interim waiver. On November
17, 2020, Midea submitted a request \6\ to include three additional
[[Page 17806]]
basic models in their petition for waiver and petition for interim
waiver.\7\ The current DOE test procedure at Appendix CC tests dual-
duct portable air conditioners at two operating conditions, one
measuring performance at a high outdoor operating temperature and one
measuring performance at a lower outdoor operating temperature. Midea
asserts that this testing does not address the ability of variable-
speed compressors to adjust their operating speed based on the demand
load of the conditioned space. Because of this, Midea indicated that
the test procedure does not take into account the full range of
performance and efficiency benefits of a variable-speed compressor
operating under part-load conditions. Midea cited DOE's test procedure
for central air conditioners, which includes part-load test conditions
that account for the improved efficiency benefit from variable-speed
compressors at 10 CFR 430 subpart B, appendix M1, section 3.2.4. Midea
also referenced several waivers; first were two test procedure waivers
for room air conditioners that contain variable-speed compressors:
Midea's, granted on May 26, 2020, and LG Electronics Inc. (``LG'')'s,
granted on May 8, 2019. 85 FR 31481; 84 FR 20111. Second was the
portable air conditioner waiver DOE granted to LG on June 2, 2020. That
waiver includes part-load test conditions to account for the improved
efficiency benefit from variable-speed compressors. 85 FR 33643. Midea
asserted that the basic models listed in the petition cannot be tested
according to the test procedure at Appendix CC because their condenser
inlet and outlet air streams are incorporated into the same structure
using ``combined-duct technology.'' Midea stated that the test
procedure does not provide for measuring airflow in and out of a single
condenser duct at the same time, as would be required for units with a
combined duct.
---------------------------------------------------------------------------
\3\ A notation in this form provides a reference for information
that is in the docket for this test procedure waiver (Docket No.
EERE-2020-BT-WAV-0023) (available at https://www.regulations.gov/docket/EERE-2020-BT-WAV-0023). This notation indicates that the
statement preceding the reference is document number 1 in the docket
and appears at pages 2-3 of that document.
\4\ The revised petition for waiver and application for interim
waiver is available at https://www.regulations.gov/document?D=EERE-2020-BT-WAV-0023-0002.
\5\ The request to include additional basic models is available
at https://www.regulations.gov/document?D=EERE-2020-BT-WAV-0023-0003.
\6\ The request to include additional basic models is available
at https://www.regulations.gov/document?D=EERE-2020-BT-WAV-0023-0004.
\7\ The brand and basic model numbers specified by Midea in its
petition (including the September 11, 2020 and November 17, 2020
submissions) are: Midea, US-KC35Y1/BP3N8-PTB(CH3); Midea, US-KC30Y1/
BP3N8-PTB(CG8); Perfect aire, 1PORTV10000; Danby, DPA100B9IWDB-6;
Heat Controller LLC, PSV-101D; Whynter, ARC-1030WN; Whynter, ARC-
1030BN; Whynter, ARC-1030GN; hOme, HME020373N; Vremi, VRM050703N;
Wappliance, BPI10MW; Perfect aire, 1PORTVP10000; Danby,
DPA100HB9IWDB-6; Heat Controller LLC, PSHV-101D; Whynter, ARC-
1030WNH; Whynter, ARC-1030GNH; Whynter, ARC-1030BNH; hOme,
HME020374N; Vremi, VRM050704N; Wappliance, BPI10HMW; Perfect aire,
1PORTV12000; Danby, DPA120B9IWDB-6; Heat Controller LLC, PSV-121D;
Whynter, ARC-1230WN; Whynter, ARC-1230BN; Whynter, ARC-1230GN; hOme,
HME020375N; Vremi, VRM050705N; Wappliance, BPI12MW; Perfectaire,
1PORTVP12000; Danby, DPA120HB9IWDB-6; Heat Controller LLC, PSHV-
121D; Whynter, ARC-1230WNH; Whynter, ARC-1230GNH; Whynter, ARC-
1230BNH; hOme, HME020376N; Vremi, VRM050706N; Wappliance, BPI12HMW;
Toshiba, RAC-PT1411HWRU; Toshiba, RAC-PT1411CWRU; Toshiba, RAC-
PT1211CWRU; Danby, DPA100HB9IBDB-6; Danby, DPA120B9IBDB-6; Midea,
MPPTB-12HRN8-BCH4; Midea, MPPTB-12CRN8-BCH4; Midea, MPPTB-10CRN8-
BCG8.
---------------------------------------------------------------------------
Midea also requested an interim waiver from the existing DOE test
procedure. DOE will grant an interim waiver if it appears likely that
the petition for waiver will be granted, and/or if DOE determines that
it would be desirable for public policy reasons to grant immediate
relief pending a determination of the petition for waiver. 10 CFR
430.27(e)(2).
Based on the assertions in the petition, absent an interim waiver,
Midea's specified portable air conditioner basic models contain design
characteristics which prevent testing of the basic model according to
the prescribed test procedures and cause the prescribed test procedures
to be tested in a manner that is unrepresentative of their actual
efficiency.
III. Requested Alternate Test Procedure
EPCA requires that manufacturers use DOE test procedures when
making representations about the energy consumption and energy
consumption costs of covered products. (42 U.S.C. 6293(c)) Consistency
is important when making representations about the energy efficiency of
covered products, including when demonstrating compliance with
applicable DOE energy conservation standards. Pursuant to 10 CFR
430.27, and after consideration of public comments on the petition, DOE
may establish in a subsequent Decision and Order an alternate test
procedure for the basic models addressed by the Interim Waiver Order.
Midea seeks to use an alternate test procedure to test and rate
specific portable air conditioner basic models. The alternate test
procedure is the test procedure for portable air conditioners
prescribed by DOE in Appendix CC, with the combined-duct variable-speed
portable air conditioners tested at both the high- and low-temperature
outdoor operating conditions to measure a weighted-average combined
energy efficiency ratio (``CEER''), except the compressor speed is
fixed at ``full'' and ``low'' in accordance with manufacturer
instructions at the two outdoor conditions, respectively. Midea
suggests an additional set of calculations to model the CEER of a
theoretical comparable dual-duct single-speed portable air conditioner
twice--once with cycling losses and once without cycling losses--based
on the performance of the combined-duct variable-speed portable air
conditioner at full compressor speed at the low-outdoor temperature
condition. From these results, a ``performance adjustment factor'' is
calculated, representing the performance improvement associated with
avoiding cycling losses. The performance adjustment factor is then
multiplied by the measured CEER value for the variable-speed portable
air conditioner according to Appendix CC to determine the test unit's
final rated CEER value. Midea states that this approach takes into
account performance and efficiency improvements associated with
combined-duct variable-speed portable air conditioners as compared to
dual-duct portable air conditioners with single-speed compressors. In
addition to the provisions for variable-speed compressors, Midea's
suggested alternate test procedure also adds provisions to the test
procedure in Appendix CC to test combined-duct portable air
conditioners using an adapter to interface with the combined duct and
additional thermocouples to measure temperature variations on the
surface of the combined duct.
IV. Interim Waiver Order
DOE has reviewed Midea's application for an interim waiver, the
alternate test procedure requested by Midea, diagrams and renderings,
and confidential performance data Midea provided to DOE. Based on this
review, the alternate test procedure, with modifications discussed in
the following paragraphs, appears to allow for the accurate measurement
of the efficiency of the specified basic models, while alleviating the
problems Midea identified in testing these basic models.
DOE has made four modifications to the alternate test procedure as
presented in the Media petition. First, at Midea's request, DOE removed
an adjustment factor that was originally requested in the alternate
test procedure to account for different full compressor speeds for
single-speed and variable-speed portable air conditioners at the lower
outdoor temperature operating condition. Second, DOE doubled the number
of thermocouples on the combined duct from eight to sixteen. Third, DOE
is altering the cycling loss factor (``CLF'') to reflect the most
recent data and analysis. Last, DOE is requiring the use of a unit
setpoint of 75 [deg]F at the 95 [deg]F fixed chamber test condition to
improve test representativeness.
In its petition, Midea suggested an adjustment factor for the
purpose of providing a more appropriate comparison between the measured
capacity and power when testing the variable-speed portable air
conditioner
[[Page 17807]]
with a full compressor speed at the lower outdoor operating conditions
and that of a single-speed portable air conditioner operating under
those conditions. In a communication following the July 2020 revised
petition, Midea requested that the adjustment factor be retracted
stating that due to subsequent modifications to the subject basic
models the adjustment factor is now not necessary. DOE has therefore
removed this adjustment factor from the alternate test procedure.
Additionally, DOE has initially determined that the use of 16
thermocouples better assesses the average temperature on the combined
duct given that it contains both the condenser inlet and exhaust air
streams. Section 3.1.1.6 of Appendix CC requires four thermocouples per
duct. With the basic models at issue, both of the air streams are
contained in the same combined duct. The combined duct potentially
results in more significant temperature gradients along its length and
perimeter, necessitating the use of 16 thermocouples.
Also, DOE considered data collected in support of the ongoing room
air conditioner test procedure rulemaking,\8\ given the certain
similarities of these products to portable air conditioners, to assess
the portable air conditioner CLF proposed in Midea's petition. The data
for cooling degradation coefficient (``Cd''), presented below in Table
IV-1, summarize the results from load-based testing of two single-speed
room air conditioners at an outdoor temperature of 82 [deg]F and
cooling loads between 49 and 55 percent of the full load (i.e., the
cooling capacity resulting from maximum cooling at the 95 [deg]F test
condition).
---------------------------------------------------------------------------
\8\ The data were collected following publication of the notice
of proposed rulemaking, ``Energy Conservation Program: Test
Procedure for Room Air Conditioners'' (85 FR 35700; Jun. 11, 2020),
and will be considered as part of that rulemaking.
Table IV-1--Tested and Extrapolated Cooling Degradation Coefficient
------------------------------------------------------------------------
Unit Load % Cd
------------------------------------------------------------------------
Unit 1............................................ 52 0.42
54 0.39
* 55 * 0.38
Unit 2............................................ 49 0.39
54 0.30
* 55 * 0.28
------------------------------------------------------------------------
* Represent extrapolated values to estimate the Cd at a 55% load.
Extrapolating from the data collected, the average Cd at 55 percent
of the full cooling load (i.e., the center of the acceptable range
specified in the low compressor speed definition of this waiver) would
be 0.332, suggesting a CLF of 0.8 would be more appropriate at the 83
[deg]F test condition as opposed to the 0.875 CLF suggested in the
Midea petition. The analysis above represents the best available
information to date regarding single-speed room air conditioner cycling
at reduced cooling loads, which DOE believes is reflective of the
expected cycling that would be observed for single-speed portable air
conditioners. Therefore, DOE is adopting the use of 0.8 as the CLF for
the 83 [deg]F test condition in this interim waiver.
Furthermore, during the room air conditioner test procedure
rulemaking, DOE observed that for units produced by certain
manufacturers, variable-speed room air conditioners performed
differently depending on the method used to produce maximum cooling
capacity. Testing of variable-speed room air conditioners was conducted
at maximum cooling capacity for the ``full speed'' 95 [deg]F test
condition, achieved either with (1) the user settings (e.g., fan speed,
grille position) and thermostat setpoint selected to produce maximum
cooling capacity in accordance with the DOE room air conditioner test
procedure at 10 CFR part 430, subpart B, appendix F (``appendix F'')
(i.e., the unit automatically selected the compressor speed); or (2)
using the user settings, in accordance with appendix F, but applying
the manufacturer's confidential testing instructions to achieve a fixed
``full'' compressor speed (i.e., the control setting specified in the
room air condition waiver and suggested by Midea in their petition).
One test unit was 10 percent more efficient when using only the
appendix F user settings than when using fixed compressor speed
controls, while another unit was 11 percent less efficient.
Based on the observed differences in room air conditioner
performance when using the fixed ``full'' compressor speed (i.e.,
applying the confidential manufacturer instructions) as compared to
using only the appendix F settings, described above, DOE concludes that
similar differences may occur when testing portable air conditioners
and is requiring a unit setpoint of 75 [deg]F for the portable air
conditioner ``full speed'' 95 [deg]F test condition, as it would be
more representative of typical consumer settings than reliance on the
confidential manufacturer instructions to achieve maximum cooling
capacity. In evaluating potential thermostat setpoints, DOE reviewed
data for 19 portable air conditioners that were field metered in a 2014
study conducted by Lawrence Berkeley National Laboratory.\9\ Among
these units, the thermostat setpoints selected by consumers ranged from
66 [deg]F to 76 [deg]F, with a median value of 74.5 [deg]F. DOE
expects, therefore, that 75 [deg]F is a typical consumer setpoint for
portable air conditioners that would achieve the maximum cooling (given
the differential between the setpoint and the fixed indoor test chamber
dry-bulb temperature of 80 [deg]F), in accordance with appendix CC. DOE
is also modifying the definition of ``full compressor speed''
accordingly in this interim waiver.
---------------------------------------------------------------------------
\9\ T. Burke et al., ``Using Field-Metered Data to Quantify
Annual Energy Use of Portable Air Conditioners,'' Lawrence Berkeley
National Laboratory, LBNL-6868E, December 2014.
---------------------------------------------------------------------------
DOE notes that while variable-speed waivers granted for other
products numerically estimate performance of a theoretical single-speed
product at reduced outdoor temperature conditions, given the complex
heat transfer dynamics related to the ducts, infiltration air, and
internal air mixing within the chassis of the combined duct used in the
basic models specified by Midea in its petition, DOE believes that the
approach proposed by Midea to estimate performance of the theoretical
single-speed dual-duct portable air conditioner using the performance
of the variable-speed combined-duct portable air conditioner at the
low-outdoor temperature condition, modified as discussed above, is
appropriate and reasonable. Consequently, DOE has determined that
Midea's petition for waiver likely will be granted. Furthermore, DOE
has determined that it is desirable for public policy reasons to grant
Midea immediate relief pending a determination of the petition for
waiver.
For the reasons stated, it is ordered that:
(1) Midea must test and rate the following portable air conditioner
basic models with the alternate test procedure set forth in paragraph
(2).
[[Page 17808]]
------------------------------------------------------------------------
Brand Model No.
------------------------------------------------------------------------
Midea......................... US-KC35Y1/BP3N8-PTB(CH3)
Midea......................... US-KC30Y1/BP3N8-PTB(CG8)
Perfect aire.................. 1PORTV10000
Danby......................... DPA100B9IWDB-6
Heat Controller LLC........... PSV-101D
Whynter....................... ARC-1030WN
Whynter....................... ARC-1030BN
Whynter....................... ARC-1030GN
hOme.......................... HME020373N
Vremi......................... VRM050703N
Wappliance.................... BPI10MW
Perfect aire.................. 1PORTVP10000.
Danby......................... DPA100HB9IWDB-6
Heat Controller LLC........... PSHV-101D
Whynter....................... ARC-1030WNH
Whynter....................... ARC-1030GNH
Whynter....................... ARC-1030BNH
hOme.......................... HME020374N
Vremi......................... VRM050704N
Wappliance.................... BPI10HMW
Perfect aire.................. 1PORTV12000
Danby......................... DPA120B9IWDB-6
Heat Controller LLC........... PSV-121D
Whynter....................... ARC-1230WN
Whynter....................... ARC-1230BN
Whynter....................... ARC-1230GN
hOme.......................... HME020375N
Vremi......................... VRM050705N
Wappliance.................... BPI12MW
Perfectaire................... 1PORTVP12000
Danby......................... DPA120HB9IWDB-6
Heat Controller LLC........... PSHV-121D
Whynter....................... ARC-1230WNH
Whynter....................... ARC-1230GNH
Whynter....................... ARC-1230BNH
hOme.......................... HME020376N
Vremi......................... VRM050706N
Wappliance.................... BPI12HMW
Toshiba....................... RAC-PT1411HWRU
Toshiba....................... RAC-PT1411CWRU
Toshiba....................... RAC-PT1211CWRU
Danby......................... DPA100HB9IBDB-6
Danby......................... DPA120B9IBDB-6
Midea......................... MPPTB-12HRN8-BCH4
Midea......................... MPPTB-12CRN8-BCH4
Midea......................... MPPTB-10CRN8-BCG8
------------------------------------------------------------------------
(2) The alternate test procedure for the Midea basic models
identified in paragraph (1) of this Interim Waiver Order is the test
procedure for portable air conditioners prescribed by DOE at Appendix
CC and 10 CFR 430.23(dd), with three exceptions. First, install the
unit under test as detailed below. Second, determine combined energy
efficiency ratio (CEER) as detailed below. Third, calculate the
estimated annual operating cost in 10 CFR 430.23(dd)(2) as detailed
below. In addition, for each basic model listed in paragraph (1),
maintain the compressor speed at each test condition, and set the
control settings used for the variable components, according to the
instructions submitted to DOE by Midea (https://www.regulations.gov/docket/EERE-2020-BT-WAV-0023). Upon the compliance date of any new
energy conservation standards for portable air conditioners, Midea must
report product specific information pursuant to 10 CFR 429.12(b)(13)
and 10 CFR 429.62(b). All other requirements of Appendix CC and DOE's
regulations remain applicable.
In 10 CFR 430.2, add in alphabetical order:
Combined-duct portable air conditioner means a dual-duct portable
air conditioner with the condenser inlet and outlet air streams flowing
through separate ducts housed in a single overall duct structure.
In 10 CFR 430.23, in paragraph (dd) revise paragraph (2) to read as
follows:
(2) Determine the estimated annual operating cost for a combined-
duct variable-speed portable air conditioner, expressed in dollars per
year, by multiplying the following two factors:
(i) The sum of the following three values: AEC95
multiplied by 0.2, AEC83_Low multiplied by 0.8, and
AECT, as calculated in section 5.3 of appendix CC of this
subpart; and
(ii) A representative average unit cost of electrical energy in
dollars per kilowatt-hour as provided by the Secretary.
(iii) Round the resulting product to the nearest dollar per year.
In Appendix CC:
Add in Section 2, Definitions:
2.11 Single-speed means a type of portable air conditioner that
cannot adjust the compressor speed.
2.12 Variable-speed means a type of portable air conditioner that
can automatically adjust the compressor speed.
2.13 Full compressor speed (full) means the compressor speed at
which the unit operates at full load test
[[Page 17809]]
conditions, when using user settings to achieve maximum cooling
capacity, and with the thermostat setpoint set at 75 [deg]F.
2.14 Low compressor speed (low) means the compressor speed
specified by Midea (Docket No. EERE-2020-BT-WAV-0023-0006), at which
the unit operates at low load test conditions, such that
Capacity_83_Low, the measured cooling capacity at this speed
at Test Condition 3 in Table 1 of this appendix, is no less than 50
percent and no greater than 60 percent of Capacity95, the
measured cooling capacity with the full compressor speed at Test
Condition 1 in Table 1 of this appendix.
2.15 Theoretical comparable single-speed portable air conditioner
means a theoretical single-speed portable air conditioner with the same
cooling capacity and electrical power input as the variable-speed
portable air conditioner under test, with no cycling losses considered,
when operating with the full compressor speed and at Test Condition 1
in Table 1 of this appendix.
Replace section 3.1.1 Test conduct with the following:
Test conduct. The test apparatus and instructions for testing
portable air conditioners in cooling mode and off-cycle mode must
conform to the requirements specified in Section 4, ``Definitions'' and
Section 7, ``Tests,'' of ANSI/AHAM PAC-1-2015 (incorporated by
reference; see Sec. 430.3), except as otherwise specified in this
appendix. Measure duct heat transfer and infiltration air heat transfer
according to section 4.1.1 and section 4.1.2 of this appendix,
respectively.
Replace section 3.1.1.1 Duct Setup with the following:
Use only ducting components provided by the manufacturer,
including, where provided by the manufacturer, ducts, connectors for
attaching the duct(s) to the test unit, sealing, insulation, and window
mounting fixtures. Do not apply additional sealing or insulation. To
measure the condenser inlet and outlet airflows in the combined duct,
use an adapter provided by the manufacturer, which allows for the
individual connection of the condenser inlet and outlet airflows to the
test lab's airflow measuring apparatuses.
Replace section 3.1.1.6 Duct temperature measurements with the
following:
Duct temperature measurements. Install any insulation and sealing
provided by the manufacturer. Then adhere sixteen thermocouples to the
outer surface of the duct, spaced evenly around the circumference (four
thermocouples, each 90 degrees apart, radially) and down the length of
the duct (four sets of four thermocouples, evenly placed along the
length of the duct), ensuring that the thermocouples are distributed
equally on the entire surface of the combined duct. Ensure that at
least one thermocouple is placed next to the condenser inlet aperture
and at least one thermocouple is placed on the duct surface adjacent to
or nearest to the condenser outlet aperture. Measure the surface
temperature of the combined duct at each thermocouple. Temperature
measurements must have an error no greater than 0.5 [deg]F
over the range being measured.
Add to the end of Section 3.1.2, Control settings:
Set the compressor speed during cooling mode testing as described
in section 4.1 of this appendix, as amended by this Order.
Replace Section 4.1, Cooling mode with the following:
Cooling mode. Instead of the test conditions in Table 3 of ANSI/
AHAM PAC-1-2015, establish the test conditions presented in Table 1 of
this appendix. Test each sample unit three times, once at each test
condition in Table 1. For each test condition, measure the sample
unit's indoor room cooling capacity and overall power input in cooling
mode in accordance with Section 7.1.b and 7.1.c of ANSI/AHAM PAC-1-2015
(incorporated by reference; see Sec. 430.3), respectively, and
determine the test duration in accordance with Section 8.7 of ASHRAE
Standard 37-2009 (incorporated by reference; Sec. 430.3). Conduct the
first test in accordance with ambient conditions for Test Condition 1
in Table 1 of this appendix, achieving the full compressor speed, as
defined in section 2.13 of this appendix, with user settings, for the
duration of cooling mode testing (Capacity95,
P95). Conduct the second test in accordance with the ambient
conditions for Test Condition 2, in Table 1 of this appendix, with the
compressor speed set to full, for the duration of cooling mode testing
(Capacity83_Full, P83_Full). To confirm the same
full compressor speed is used, the average compressor frequency for the
second test must equal that observed for the first test, with a
tolerance of +/- 10% of the nominal average compressor frequency of the
first test. Conduct the third test in accordance with the ambient
conditions for Test Condition 3, with the compressor speed set to low
for the duration of cooling mode testing (Capacity83_Low,
P83_Low). Set the compressor speed required for each test
condition in accordance with the instructions Midea submitted to DOE
(Docket No. EERE-2020-BT-WAV-0023-0006).
Table 1--Evaporator and Condenser Inlet Test Conditions
----------------------------------------------------------------------------------------------------------------
Evaporator inlet air [deg]F Condenser inlet air [deg]F
([deg]C) ([deg]C)
Test condition ---------------------------------------------------------------- Compressor speed
Dry bulb Wet bulb Dry bulb Wet bulb
----------------------------------------------------------------------------------------------------------------
Test Condition 1............ 80 (26.7) 67 (19.4) 95 (35.0) 75 (23.9) Full.
Test Condition 2............ 80 (26.7) 67 (19.4) 83 (28.3) 67.5 (19.7) Full.
Test Condition 3............ 80 (26.7) 67 (19.4) 83 (28.3) 67.5 (19.7) Low.
----------------------------------------------------------------------------------------------------------------
Replace Section 4.1.1, Duct Heat Transfer, with the following:
Duct Heat Transfer. Measure the circumference of the duct by
wrapping a flexible measuring tape, or equivalent, around the outside
of the combined duct, making sure the tape is on the outermost ridges.
Calculate the surface area of the combined duct as follows:
ACD = C x L
Where:
ACD = the outer area of the combined duct, in square
feet.
C = the circumference of the combined duct, as measured in this
section, in feet.
L = the extended length of the combined duct while under test, in
feet.
Calculate the average temperature at each individual location. Then
calculate the average surface temperature of the duct by averaging the
sixteen average temperature measurements taken on the duct. Calculate
the total heat transferred from the surface of the combined duct to the
indoor conditioned space while operating in cooling mode at each test
condition in Table 1 of this appendix, according to the following
equations:
QCD_95 = 3 x ACD x (TCD_95-
Tei)
QCD_83_Full = 3 x ACD x (TCD_83_Full-
Tei)
QCD_83_Low = 3 x ACD x (TCD_83_Low-
Tei)
[[Page 17810]]
Where:
QCD_95, QCD_83_Full, and QCD_83_Low
= the total heat transferred from the combined duct to the indoor
conditioned space in cooling mode, in Btu/h, when tested at Test
Condition 1, Test Condition 2, and Test Condition 3 in Table 1 of
this appendix, respectively.
3 = convection coefficient in Btu/h per square foot per [deg]F.
ACD = surface area of the combined duct, as calculated in
this section, in square feet.
TCD_95, TCD_83_Full, and TCD_83_Low
= average surface temperature for the combined duct, in [deg]F, as
measured at Test Condition 1, Test Condition 2, and Test Condition 3
in Table 1 of this appendix, respectively, as calculated in this
section.
Tei = average evaporator inlet air dry-bulb temperature,
as measured in section 4.1 of this appendix, in [deg]F.
Replace Section 4.1.2, Infiltration Air Heat Transfer with the
following:
Infiltration Air Heat Transfer. Calculate the sample unit's heat
contribution from infiltration air into the conditioned space for each
cooling mode test. Calculate the dry air mass flow rate of infiltration
air according to the following equations:
[GRAPHIC] [TIFF OMITTED] TN06AP21.001
Where:
m95, m83_Full and m83_Low = dry air
mass flow rate of infiltration air for combined-duct portable air
conditioners, in lb/m, when tested at Test Condition 1, Test
Condition 2, and Test Condition 3 in Table 1 of this appendix,
respectively.
Vco_95, Vco_83_Full and Vco_83_Low
= average volumetric flow rate of the condenser outlet air, in cubic
feet per minute (cfm), as measured at Test Condition 1, Test
Condition 2, and Test Condition 3 in Table 1 of this appendix,
respectively, as required in section 4.1 of this appendix.
Vci_95, Vci_83_Full and Vci_83_Low
= average volumetric flow rate of the condenser inlet air, in cfm,
as measured at Test Condition 1, Test Condition 2, and Test
Condition 3 in Table 1 of this appendix, respectively, as required
in section 4.1 of this appendix.
[rho]co_95, [rho]co_83_Full and
[rho]co_83_Low = average density of the condenser outlet
air, in pounds mass per cubic foot (lbm/ft3), as measured
at Test Condition 1, Test Condition 2, and Test Condition 3 in Table
1 of this appendix, respectively, as required in section 4.1 of this
appendix.
[rho]ci_95, [rho]ci_83_Full and
[rho]ci_83_Low = average density of the condenser inlet
air, in lbm/ft\3\, as measured at Test Condition 1, Test
Condition 2, and Test Condition 3 in Table 1 of this appendix,
respectively, as required in section 4.1 of this appendix.
[omega]co_95, [omega]co_83_Full and
[omega]co_83_Low = average humidity ratio of condenser
outlet air, in pounds mass of water vapor per pounds mass of dry air
(lbw/lbda), as measured at Test Condition 1,
Test Condition 2, and Test Condition 3 in Table 1 of this appendix,
respectively, as required in section 4.1 of this appendix.
[omega]ci_95, [omega]ci_83_Full and
[omega]ci_83_Low = average humidity ratio of condenser
inlet air, in lbw/lbda, as measured at Test
Condition 1, Test Condition 2, and Test Condition 3 in Table 1 of
this appendix, respectively, as required in section 4.1 of this
appendix.
Calculate the sensible component of infiltration air heat
contribution according to the following equations:
Qs_95 = m95 x 60 x [cp_da x (95 - 80)
+ (cp_wv x (0.0141 x 95 - 0.0112 x 80))]
Qs_83_Full = m83_Full x 60 x [(cp_da x
(83 - 80) + (cp_wv x (0.01086 x 83 - 0.0112 r x
80))]
Qs_83_Low = m83_Low x 60 x [(cp_da x
(83 - 80) + (cp_wv x (0.01086 x 83 - 0.0112 r x
80))]
Where:
Qs_95, Qs_83_Full and Qs_83_Low =
sensible heat added to the room by infiltration air, in Btu/h, when
tested at Test Condition 1, Test Condition 2, and Test Condition 3
in Table 1 of this appendix, respectively.
m95, m83_Full and m83_Low = dry air
mass flow rate of infiltration air for combined-duct portable air
conditioners, in lb/m, when tested at Test Condition 1, Test
Condition 2, and Test Condition 3 in Table 1 of this appendix,
respectively, as calculated in section 4.1.2 of this appendix.
cp_da = specific heat of dry air, 0.24 Btu/
(lbm [deg]F).
cp_wv = specific heat of water vapor, 0.444 Btu/
(lbm [deg]F).
80 = indoor chamber dry-bulb temperature, in [deg]F.
95 = infiltration air dry-bulb temperature for Test Condition 1 in
Table 1 of this appendix, in [deg]F.
83 = infiltration air dry-bulb temperature for Test Conditions 2 and
3 in Table 1 of this appendix, in [deg]F.
0.0141 = humidity ratio of the dry-bulb infiltration air for Test
Condition 1 in Table 1 of this appendix, in lbw/
lbda.
0.01086 = humidity ratio of the dry-bulb infiltration air for Test
Conditions 2 and 3 in Table 1 of this appendix, in lbw/
lbda.
0.0112 = humidity ratio of the indoor chamber air, in
lbw/lbda ([omega]indoor).
60 = conversion factor from minutes to hours.
Calculate the latent heat contribution of the infiltration air
according to the following equations:
Ql_95 = m95 x 60 x 1061 x (0.0141-0.0112)
Ql_83_Full = m83_Full x 60 x 1061 x (0.01086 -
0.0112)
Ql_83_Low = m83_Low x 60 x 1061 x (0.01086 -
0.0112)
Where:
Ql_95, Ql_83_Full and Ql_83_Low =
latent heat added to the room by infiltration air, when tested at
Test Conditions 1, 2, and 3 in Table 1 of this appendix,
respectively, in Btu/h.
m95, m83_Full and m83_Low = dry air
mass flow rate of infiltration air, in lb/m, when tested at Test
Condition 1, Test Condition 2, and Test Condition 3 in Table 1 of
this appendix, respectively, as calculated in section 4.1.2 of this
appendix.
1061 = latent heat of vaporization for water vapor, in Btu/
lbm (Hfg).
0.0141 = humidity ratio of the dry-bulb infiltration air for Test
Condition 1 in Table 1 of this appendix, in lbw/
lbda.
0.01086 = humidity ratio of the dry-bulb infiltration air for Test
Conditions 2 and 3 in Table 1 of this appendix, in lbw/
lbda.
0.0112 = humidity ratio of the indoor chamber air, in
lbw/lbda.
60 = conversion factor from minutes to hours.
Calculate the total heat contribution of the infiltration air at
each test condition by adding the sensible and latent heat according to
the following equations:
Qinfiltration_95 = Qs_95 + Ql_95
Qinfiltration_83_Full = Qs_83_Full +
Ql_83_Full
[[Page 17811]]
Qinfiltration_83_Low = Qs_83_Low +
Ql_83_Low
Where:
Qinfiltration_95, Qinfiltration_83_Full and
Qinfiltration_83_Low = total infiltration air heat in
cooling mode, when tested at Test Conditions 1, 2, and 3 in Table 1
of this appendix, respectively, in Btu/h
Qs_95, Qs_83_Full and Qs_83_Low =
sensible heat added to the room by infiltration air, when tested at
Test Conditions 1, 2, and 3 in Table 1 of this appendix,
respectively, in Btu/h, as calculated in this section.
Ql_95, Ql_83_Full and Ql_83_Low =
latent heat added to the room by infiltration air, when tested at
Test Conditions 1, 2, and 3 in Table 1 of this appendix,
respectively, in Btu/h, as calculated in this section.
Replace Section 5.1, Adjusted Cooling Capacity with the following:
Adjusted Cooling Capacity. Calculate the adjusted cooling capacity
at each outdoor temperature operating condition, ACC95 and
ACC83_Low, expressed in Btu/h, according to the following
equations:
ACC95 = Capacity95-QCD_95-
Qinfiltration_95
ACC83_Low = Capacity83_Low-
QCD_83_Low-
Qinfiltration_83_Low
Where:
Capacity95 and Capacity83_Low = cooling
capacity, as measured in section 4.1 of this appendix, at Test
Condition 1 and Test Condition 3 in Table 1 of this appendix,
respectively, in Btu/h.
QCD_95 and QCD_83_Low = combined duct heat
transfer while operating in cooling mode at Test Condition 1 and
Test Condition 3 in Table 1 of this appendix, respectively, in Btu/
h, as calculated in section 4.1.1 of this appendix.
Qinfiltration_95 and Qinfiltration_83_Low =
total infiltration air heat transfer in cooling mode at Test
Condition 1 and Test Condition 3 in Table 1 of this appendix,
respectively, in Btu/h, as calculated in section 4.1.2 of this
appendix.
Replace Section 5.3, Annual Energy Consumption with the following:
Annual Energy Consumption. Calculate the sample unit's annual
energy consumption in each operating mode according to the equation
below. For each operating mode, use the following annual hours of
operation and equation:
------------------------------------------------------------------------
Annual
Operating mode Subscript operating
hours
------------------------------------------------------------------------
Cooling Mode, Test Condition 1 1..... 95.................... 750
Cooling Mode, Test Condition 2 1..... 83_Full............... 750
Cooling Mode, Test Condition 3 1..... 83_Low................ 750
Off-Cycle............................ oc.................... 880
Inactive or Off...................... ia or om.............. 1,355
------------------------------------------------------------------------
\1\ These operating mode hours are for the purposes of calculating
annual energy consumption under different ambient conditions and are
not a division of the total cooling mode operating hours. The total
cooling mode operating hours are 750 hours.
[GRAPHIC] [TIFF OMITTED] TN06AP21.002
Where:
AECm = annual energy consumption in the operating mode,
in kWh/year.
m represents the operating mode (``95'' for Test Condition 1,
``83_Full'' for Test Condition 2, ``83_Low'' for Test Condition 3,
``oc'' for off cycle, and ``ia'' for inactive or ``om'' for off
mode).
Pm = average power in the operating mode, in watts.
tm = number of annual operating time in each operating
mode, in hours.
0.001 kWh/Wh = conversion factor from watt-hours to kilowatt-hours.
Calculate the sample unit's total annual energy consumption in off
cycle mode and inactive or off mode as follows:
[GRAPHIC] [TIFF OMITTED] TN06AP21.003
Where:
AECT = total annual energy consumption attributed to off
cycle mode and inactive or off mode, in kWh/year;
AECm = total annual energy consumption in the operating
mode, in kWh/year.
m represents the following two operating modes: Off cycle mode and
inactive or off mode.
Replace Section 5.4, Combined Energy Efficiency Ratio with the
following:
Unadjusted Combined Energy Efficiency Ratio. Calculate the sample
unit's unadjusted combined energy efficiency ratio, CEERUA,
expressed in Btu/Wh, as follows:
[GRAPHIC] [TIFF OMITTED] TN06AP21.004
Where:
CEERUA = unadjusted combined energy efficiency ratio for
the sample unit, in Btu/Wh.
ACC95 and ACC83_Low = adjusted cooling
capacity, tested at Test Condition 1 and Test Condition 3 in Table 1
of this appendix, respectively, as calculated in section 5.1 of this
appendix, in Btu/h.
AEC95 and AEC83_Low = annual energy
consumption for cooling mode operation at Test Condition 1 and Test
Condition 3 in Table 1 in this appendix that represent operation at
95 [deg]F and 83 [deg]F dry-bulb outdoor temperature operating
conditions, respectively, as calculated in section 5.3 of this
appendix, in kWh/year.
AECT = total annual energy consumption attributed to off
cycle mode and inactive or off mode, in kWh/year, calculated in
section 5.3 of this appendix.
750 = number of cooling mode hours per year.
0.001 kWh/Wh = conversion factor for watt-hours to kilowatt-hours.
0.2 = weighting factor for the 95 [deg]F dry-bulb outdoor
temperature operating condition.
0.8 = weighting factor for the 83 [deg]F dry-bulb outdoor
temperature operating condition.
Add after Section 5.4, Combined Energy Efficiency Ratio:
5.5 Adjustment of the Combined Energy Efficiency Ratio. Adjust the
sample unit's unadjusted combined energy efficiency ratio as follows.
5.5.1 Theoretical Comparable Single-Speed Portable Air Conditioner
Cooling Capacity and Power at the Lower Outdoor Temperature Operating
Condition. Calculate the cooling capacity and cooling capacity with
cycling losses, expressed in British thermal units per hour (Btu/h),
and electrical power input, expressed in watts, for a theoretical
comparable single-speed portable air conditioner at an 83 [deg]F
outdoor dry-bulb outdoor temperature operating condition (Test
Condition 2 in Table 1 of this appendix) according to the following
equations:
Capacity83_SS = Capacity83_Full
Capacity83_SS_CLF = Capacity83_SS x 0.8
P83_SS = P83_Full
Where:
Capacity83_SS = cooling capacity of a theoretical
comparable single-speed portable air conditioner, calculated for the
83 [deg]F dry-bulb outdoor temperature operating condition (Test
Condition 2 in Table 1 of this appendix), in Btu/h.
Capacity83_SS_CLF = cooling capacity of a theoretical
comparable single-speed
[[Page 17812]]
portable air conditioner with cycling losses, in Btu/h, calculated
for the 83 [deg]F dry-bulb outdoor temperature operating condition
(Test Condition 2 in Table 1 of this appendix).
Capacity83_Full = cooling capacity of the sample unit,
measured in section 4.1 of this appendix at Test Condition 2 in
Table 1 of this appendix, in Btu/h.
P83_SS = power input of a theoretical comparable single-
speed portable air conditioner calculated for the 83 [deg]F dry-bulb
outdoor temperature operating condition (Test Condition 2 in Table 1
of this appendix), in watts.
P83_Full = electrical power input of the sample unit,
measured in section 4.1 of this appendix at Test Condition 2 in
Table 1 of this appendix, in watts.
0.8 = cycling loss factor for the 83 [deg]F dry-bulb outdoor
temperature operating condition.
5.5.2 Duct Heat Transfer for a Theoretical Comparable Single-Speed
Portable Air Conditioner at the Lower Outdoor Temperature Operating
Condition. Calculate the combined duct heat transfer to the conditioned
space for a theoretical comparable single-speed portable air
conditioner at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix), as follows:
QCD_83_SS = QCD_83_Full
Where:
QCD_83_SS = total heat transferred from the combined duct
to the indoor conditioned space in cooling mode, for a theoretical
comparable single-speed portable air conditioner at the 83 [deg]F
dry-bulb outdoor temperature operating condition), in Btu/h.
QCD_83_Full = combined duct heat transfer for the sample
unit while operating in cooling mode at Test Condition 2 in Table 1
of this appendix (the 83 [deg]F dry-bulb outdoor temperature
operating condition), in Btu/h, as calculated in section 4.1.1 of
this appendix.
5.5.3 Infiltration Air Heat Transfer for a Theoretical Comparable
Single-Speed Portable Air Conditioner at the Lower Outdoor Temperature
Operating Condition. Calculate the heat contribution from infiltration
air for a theoretical comparable single-speed portable air conditioner
at the 83 [deg]F dry-bulb outdoor temperature operating condition (Test
Condition 2 in Table 1 of this appendix), as detailed below. Calculate
the dry air mass flow rate of infiltration air as follows:
m83_SS = m83_Full
Where:
m83_SS = dry air mass flow rate of infiltration air for a
theoretical comparable single-speed portable air conditioner at the
83 [deg]F dry-bulb outdoor temperature operating condition (Test
Condition 2 in Table 1 of this appendix), in lb/m.
m83_Full = dry air mass flow rate of infiltration air for
the sample unit when tested at Test Condition 2 in Table 1 of this
appendix (the 83 [deg]F dry-bulb outdoor temperature operating
condition), as calculated in section 4.1.2 of this appendix, in lb/
m.
Calculate the sensible component of infiltration air heat
contribution for a theoretical comparable single-speed portable air
conditioner at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix) as follows:
Qs_83_SS = Qs_83_Full
Where:
Qs_83_SS = sensible heat added to the room by
infiltration air for a theoretical comparable single-speed portable
air conditioner, at the 83 [deg]F dry-bulb outdoor temperature
operating condition (Test Condition 2 in Table 1 of this appendix),
in Btu/h.
Qs_83_Full = sensible heat added to the room by
infiltration air, when testing the sample unit at Test Condition 2
in Table 1 of this appendix (the 83 [deg]F dry-bulb outdoor
temperature operating condition), as calculated in section 4.1.2 of
this appendix, in Btu/h.
Calculate the latent component of infiltration air heat
contribution for a theoretical comparable single-speed portable air
conditioner at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix) as follows:
Ql_83_SS = Ql_83_Full
Where:
Ql_83_SS = latent heat added to the room by infiltration
air for a theoretical comparable single-speed portable air
conditioner, at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix), in Btu/h.
Ql_83_Full = latent heat added to the room by
infiltration air during testing of the sample unit, when tested at
Test Condition 2 in Table 1 of this appendix (the 83 [deg]F dry-bulb
outdoor temperature operating condition), as calculated in section
4.1.2 of this appendix, in Btu/h.
Calculate the total heat contribution of the infiltration air for a
theoretical comparable single-speed portable air conditioner at the 83
[deg]F dry-bulb outdoor temperature operating condition (Test Condition
2 in Table 1 of this appendix) as follows:
Qinfiltration_83_SS = Qinfiltration_83_Full
Where:
Qinfiltration_83_SS = total infiltration air heat in
cooling mode for a theoretical comparable single-speed portable air
conditioner at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix), in Btu/h.
Qinfiltration_83_Full = total infiltration air heat
transfer of the sample unit in cooling mode at Test Condition 2 in
Table 1 of this appendix (the 83 [deg]F dry-bulb outdoor temperature
operating condition), as calculated in section 4.1.2 of this
appendix, in Btu/h.
5.5.4 Adjusted Cooling Capacity for a Theoretical Comparable
Single-Speed Portable Air Conditioner at the Lower Outdoor Temperature
Operating Condition. Calculate the adjusted cooling capacity for a
theoretical comparable single-speed portable air conditioner at the 83
[deg]F dry-bulb outdoor temperature operating condition (Test Condition
2 in Table 1 of this appendix) both without cycling losses,
ACC83_SS, and with cycling losses, ACC83_SS_CLF,
in Btu/h, according to the following equations:
ACC83_SS = Capacity83_SS - QCD_83_SS -
Qinfiltration_83_SS
ACC83_SS_CLF = Capacity83_SS_CLF -
QCD_83_SS - Qinfiltration_83_SS
Where:
ACC83_SS and ACC83_SS_CLF = adjusted cooling
capacity for a theoretical comparable single-speed portable air
conditioner at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix) without and
with cycling losses, respectively, in Btu/h.
Capacity83_SS and Capacity83_SS_CLF = cooling
capacity of a theoretical comparable single-speed portable air
conditioner without and with cycling losses, respectively, at Test
Condition 2 in Table 1 of this appendix (the 83 [deg]F dry-bulb
outdoor temperature operating condition), calculated in section
5.5.1 of this appendix, in Btu/h.
QCD_83_SS = total heat transferred from the ducts to the
indoor conditioned space in cooling mode for a theoretical
comparable single-speed portable air conditioner at the 83 [deg]F
dry-bulb outdoor temperature operating condition (Test Condition 2
in Table 1 of this appendix), in Btu/h, calculated in section 5.5.2
of this appendix.
Qinfiltration_83_SS = total infiltration air heat in
cooling mode for a theoretical comparable single-speed portable air
conditioner at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix), calculated
in section 5.5.3 of this appendix, in Btu/h.
5.5.5 Annual Energy Consumption in Cooling Mode for a Theoretical
Comparable Single-Speed Portable Air Conditioner at the Lower Outdoor
Temperature Operating Condition. Calculate the annual energy
consumption in cooling mode for a theoretical comparable single-speed
portable air conditioner at the 83 [deg]F dry-bulb outdoor temperature
operating condition (Test Condition 2 in Table 1 of this appendix), in
kWh/year, as follows:
[[Page 17813]]
AEC83_SS = P83_SS x 750 x 0.001
Where:
AEC83_SS = annual energy consumption for a theoretical
comparable single-speed portable air conditioner in cooling mode at
the 83 [deg]F dry-bulb outdoor temperature operating condition (Test
Condition 2 in Table 1 of this appendix), in kWh/year.
P83_SS = electrical power input for a theoretical
comparable single-speed portable air conditioner at the 83 [deg]F
dry-bulb outdoor temperature operating condition (Test Condition 2
in Table 1 of this appendix) as calculated in section 5.5.1 of this
appendix, in watts.
750 = number of cooling mode hours per year, as defined in section
5.3 of this appendix.
0.001 kWh/Wh = conversion factor from watt-hours to kilowatt-hours.
5.5.6 Combined Energy Efficiency Ratio for a Theoretical Comparable
Single-Speed Portable Air Conditioner. Calculate the combined energy
efficiency ratios for a theoretical comparable single-speed portable
air conditioner both without cycling losses, CEERSS, and
with cycling losses, CEERSS_CLF, in Btu/Wh, according to the
following equations:
[GRAPHIC] [TIFF OMITTED] TN06AP21.005
Where:
CEERSS and CEERSS_CLF = combined energy
efficiency ratio for a theoretical comparable single-speed portable
air conditioner without and with cycling losses considered,
respectively, in Btu/Wh.
ACC95 = adjusted cooling capacity for the sample unit, as
calculated in section 5.1 of this appendix, when tested at Test
Condition 1 in Table 1 of this appendix, in Btu/h.
ACC83_SS and ACC83_SS_CLF = adjusted cooling
capacities for a theoretical comparable single-speed portable air
conditioner at the 83 [deg]F dry-bulb outdoor temperature operating
condition (Test Condition 2 in Table 1 of this appendix) without and
with cycling losses, respectively, as calculated in section 5.5.4 of
this appendix, in Btu/h.
AEC95 = annual energy consumption for the sample unit, as
calculated in section 5.3 of this appendix, for cooling mode
operation at Test Condition 1 in Table 1 of this appendix, in kWh/
year.
AEC83_SS = annual energy consumption for a theoretical
comparable single-speed portable air conditioner in cooling mode at
the 83 [deg]F dry-bulb outdoor temperature operating condition (Test
Condition 2 in Table 1 of this appendix), calculated in section
5.5.5 of this appendix, in kWh/year.
AECT = total annual energy consumption attributed to all
operating modes except cooling for the sample unit, calculated in
section 5.3 of this appendix, in kWh/year.
750 and 0.001 as defined previously in this section.
0.2 = weighting factor for the 95 [deg]F dry-bulb outdoor
temperature operating condition.
0.8 = weighting factor for the 83 [deg]F dry-bulb outdoor
temperature operating condition.
5.5.7 Combined-Duct Variable-Speed Portable Air Conditioner
Performance Adjustment Factor. Calculate the sample unit's performance
adjustment factor, Fp,, as follows:
[GRAPHIC] [TIFF OMITTED] TN06AP21.006
Where:
CEERSS and CEERSS_CLF = combined energy
efficiency ratios for a theoretical comparable single-speed portable
air conditioner without and with cycling losses, respectively,
calculated in section 5.5.6 of this appendix, in Btu/Wh.
5.5.8 Dual-Duct Variable-Speed Portable Air Conditioner Combined
Energy Efficiency Ratio. Calculate the sample unit's final combined
energy efficiency ratio, CEER, in Btu/Wh, as follows:
CEER = CEERUA x (1 + Fp)
Where:
CEER = combined energy efficiency ratio for the sample unit, in Btu/
Wh.
CEERUA = unadjusted combined energy efficiency ratio for
the sample unit, calculated in section 5.4 of this appendix, in Btu/
Wh.
Fp = sample unit's performance adjustment factor,
calculated in section 5.5.7 of this appendix.''
(3) Representations. Midea may not make representations about the
efficiency of a basic model listed in paragraph (1) of this Interim
Waiver Order for compliance, marketing, or other purposes unless that
basic model has been tested in accordance with the provisions set forth
in this alternate test procedure and such representations fairly
disclose the results of such testing.
(4) This Interim Waiver Order shall remain in effect according to
the provisions of 10 CFR 430.27.
(5) This Interim Waiver Order is issued on the condition that the
statements, representations, test data, and documentary materials
provided by Midea are valid. If Midea makes any modifications to the
controls or configurations of a basic model subject to this Interim
Waiver Order, the waiver will be invalid with respect to that basic
model Midea either would be required to use the current Federal test
method or submit a new application for a test procedure waiver. DOE may
rescind or modify this waiver at any time if it determines the factual
basis underlying the petition for the Interim Waiver Order is
incorrect, or the results from the alternate test procedure are
unrepresentative of the basic model's true energy consumption
characteristics. 10 CFR 430.27(k)(1). Likewise, Midea may request that
DOE rescind or modify the Interim Waiver Order if Midea discovers an
error in the information provided to DOE as part of its petition,
determines that the interim waiver is no longer needed, or for other
appropriate reasons. 10 CFR 430.27(k)(2).
(6) Issuance of this Interim Waiver Order does not release Midea
from the applicable requirements set forth at 10 CFR part 429.
DOE makes decisions on waivers and interim waivers for only those
basic models specifically set out in the petition, not future models
that Midea may manufacture. Midea may submit a new or amended petition
for waiver and
[[Page 17814]]
request for grant of interim waiver, as appropriate, for additional
basic models of portable air conditioners. Alternatively, if
appropriate, Midea may request that DOE extend the scope of a waiver or
an interim waiver to include additional basic models employing the same
technology as the basic model(s) set forth in the original petition
consistent with 10 CFR 430.27(g).
Signing Authority
This document of the Department of Energy was signed on March 31,
2021, by Kelly J. Speakes-Backman, Principal Deputy Assistant Secretary
and Acting Assistant Secretary for Energy Efficiency and Renewable
Energy, pursuant to delegated authority from the Secretary of Energy.
That document with the original signature and date is maintained by
DOE. For administrative purposes only, and in compliance with
requirements of the Office of the Federal Register, the undersigned DOE
Federal Register Liaison Officer has been authorized to sign and submit
the document in electronic format for publication, as an official
document of the Department of Energy. This administrative process in no
way alters the legal effect of this document upon publication in the
Federal Register.
Signed in Washington, DC, on April 1, 2021.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.
BEFORE THE UNITED STATES DEPARTMENT OF ENERGY WASHINGTON, DC 20585
In the Matter of: Energy Efficiency Program: Test Procedure for
Portable Air Conditioners
Petition of Midea for Waiver, and Application for Interim Waiver, of
Test Procedure for Portable Air Conditioners
Introduction
GD Midea Air Conditioning Equipment Co. LTD. (Midea) hereby submits
this Petition for Waiver, and Application for Interim Waiver, of the
Department of Energy (DOE) Test Procedure for dual-duct portable air
conditioners (PACs) in 10 CFR part 430, subpart B, Appendix CC,
pursuant to 10 CFR 430.27. Midea requests expedited treatment of the
Petition and Application.
Midea requests that DOE grant the requested Waiver and Interim
Waiver because the current test procedure cannot be used to test dual-
duct PACs with Midea's duct-in-duct (combined-duct) technology, which
combines the condenser inlet and outlet ducts into a single structure.
Furthermore, the current test procedure does not properly measure the
energy consumption of combined-duct PACs with variable-speed
compressors (VSCs).\11\ This request is consistent with the approach
used for VSCs in the Waiver granted to LG Electronics Inc. (LG)
published June 2, 2020, 85 FR 33,643, for testing single-duct PACs with
VSCs. It simply adds procedures to accommodate Midea's combined-duct
technology. Under DOE rules, this Waiver request should be granted. DOE
also has authority to grant an Interim Waiver because the requested
Waiver is likely be granted, because it would avoid economic hardship
and competitive disadvantage to Midea, and because it would reflect
sound public policy.
---------------------------------------------------------------------------
\11\ Midea intends to manufacture such units using both standard
compressors and VSCs. It expects to add models that do not have VSCs
to this waiver request.
---------------------------------------------------------------------------
Analysis
I. Midea Group
The Midea Group, of which Midea is a part, is the world's largest
producer of major appliances, and the world's No. 1 brand of air-
treatment products, air-coolers, kettles, and rice cookers. It is also
a world-leading technologies group in consumer appliances and HVAC
systems. It offers diversified products, comprising consumer appliances
(kitchen appliances, refrigerators, laundry appliances, and various
small home appliances) and HVAC (residential air-conditioning,
commercial air-conditioning, heating & ventilation). The Midea Group is
committed to improving lives by adhering to the principle of ``Creating
Value for Customers.'' It focuses on continuous technological
innovation to improve products and services to make life more
comfortable. The Midea Group's worldwide headquarters are located at
Midea Group headquarter building, No. 6 Midea Avenue, Beijiao, Shunde,
Foshan, Guangdong, 528311 P.R. China; (tel. 011-86-757-2633-888); URL:
www.midea.com/global. GD Midea Air Conditioning Equipment Co. LTD, is
located at No 6. Midea Avenue, Shunde Foshan, Guangdong, 528311 P.R.
China.
II. Basic Models Subject to the Waiver Request
This Petition for Waiver, and Application for Interim Waiver, are
for the following basic models of residential PACs manufactured by
Midea. All models have Midea's combined-duct technology:
----------------------------------------------------------------------------------------------------------------
Brand Model No. Compressor type Unit type
----------------------------------------------------------------------------------------------------------------
Midea.......................... US-KC35Y1/BP3N8- Variable-Speed...................... Cool-only.
PTB(CH3).
Midea.......................... US-KC30Y1/BP3N8- Variable-Speed...................... Cool-only.
PTB(CG8).
Perfect aire................... 1PORTV10000............ Variable-Speed...................... Cool-only.
Danby.......................... DPA100B9IWDB-6......... Variable-Speed...................... Cool-only.
Heat Controller LLC............ PSV-101D............... Variable-Speed...................... Cool-only.
Whynter........................ ARC-1030WN............. Variable-Speed...................... Cool-only.
Whynter........................ ARC-1030BN............. Variable-Speed...................... Cool-only.
Whynter........................ ARC-1030GN............. Variable-Speed...................... Cool-only.
hOme........................... HME020373N............. Variable-Speed...................... Cool-only.
Vremi.......................... VRM050703N............. Variable-Speed...................... Cool-only.
Wappliance..................... BPI10MW................ Variable-Speed...................... Cool-only.
Perfect aire................... 1PORTVP10000........... Variable-Speed...................... Heat-Cool.
Danby.......................... DPA100HB9IWDB-6........ Variable-Speed...................... Heat-Cool.
Heat Controller LLC............ PSHV-101D.............. Variable-Speed...................... Heat-Cool.
Whynter........................ ARC-1030WNH............ Variable-Speed...................... Heat-Cool.
Whynter........................ ARC-1030GNH............ Variable-Speed...................... Heat-Cool.
Whynter........................ ARC-1030BNH............ Variable-Speed...................... Heat-Cool.
hOme........................... HME020374N............. Variable-Speed...................... Heat-Cool.
Vremi.......................... VRM050704N............. Variable-Speed...................... Heat-Cool.
[[Page 17815]]
Wappliance..................... BPI10HMW............... Variable-Speed...................... Heat-Cool.
Perfect aire................... 1PORTV12000............ Variable-Speed...................... Cool-only.
Danby.......................... DPA120B9IWDB-6......... Variable-Speed...................... Cool-only.
Heat Controller LLC............ PSV-121D............... Variable-Speed...................... Cool-only.
Whynter........................ ARC-1230WN............. Variable-Speed...................... Cool-only.
Whynter........................ ARC-1230BN............. Variable-Speed...................... Cool-only.
Whynter........................ ARC-1230GN............. Variable-Speed...................... Cool-only.
hOme........................... HME020375N............. Variable-Speed...................... Cool-only.
Vremi.......................... VRM050705N............. Variable-Speed...................... Cool-only.
Wappliance..................... BPI12MW................ Variable-Speed...................... Cool-only.
Perfectaire.................... 1PORTVP12000........... Variable-Speed...................... Heat-Cool.
Danby.......................... DPA120HB9IWDB-6........ Variable-Speed...................... Heat-Cool.
Heat Controller LLC............ PSHV-121D.............. Variable-Speed...................... Heat-Cool.
Whynter........................ ARC-1230WNH............ Variable-Speed...................... Heat-Cool.
Whynter........................ ARC-1230GNH............ Variable-Speed...................... Heat-Cool.
Whynter........................ ARC-1230BNH............ Variable-Speed...................... Heat-Cool.
hOme........................... HME020376N............. Variable-Speed...................... Heat-Cool.
Vremi.......................... VRM050706N............. Variable-Speed...................... Heat-Cool.
Wappliance..................... BPI12HMW............... Variable-Speed...................... Heat-Cool.
Midea.......................... MPPTB-12HRN8-BCH4...... Variable-Speed...................... Heat-Cool.
Midea.......................... MPPTB-12CRN8-BCH4...... Variable-Speed...................... Cool-only.
Midea.......................... MPPTB-10CRN8-BCG8...... Variable-Speed...................... Cool-only.
----------------------------------------------------------------------------------------------------------------
III. Requested Waiver
Midea requests a waiver to test the energy consumption of the above
residential PACs using the test procedure detailed in the waiver for
PACs granted to LG,2 published on June 2, 2020, with modifications
needed to account for dual-duct units incorporating Midea's combined-
duct technology.
Strong demand for advanced energy efficient PACs led Midea to
design dual-duct PACs with dramatic energy savings, and the ability to
maintain the desired temperature without cycling the compressor motor
and fans on and off by using inverter driven VSCs. The unit responds
automatically to surrounding conditions by adjusting the compressor
rotational speed based upon demand. This results in faster cooling and
much more efficient operation through optimizing the speed of the
compressor to make minimal adjustments as the room temperature rises
and falls.
The current DOE test procedure tests dual-duct PACs at two
operating conditions, one measuring performance at a high outdoor
operating temperature and one measuring performance at a lower outdoor
operating temperature, without addressing the ability of VSCs to adjust
their operating speed based on the demand load of the conditioned
space. As such, the test procedure does not take into account the full
range of performance and efficiency benefits of a VSC operating under
part-load conditions. Other DOE test standards, such as for central air
conditioners--and the test procedures approved through waivers granted
to Midea and LG for room air conditioners and to LG for PACs--include
part-load test conditions that account for the improved efficiency
benefit from VSCs that modulate their operation to account for changing
conditions to the environment, rather than cycling the compressor on
and off.
Additionally, the current test procedure prevents the testing of
Midea's combined-duct technology because the condenser inlet and outlet
air streams are incorporated into the same structure. Since the airflow
both in and out of the condenser must be measured at the same time,
modifications are needed to adapt Midea's combined-duct technology to
DOE's test procedure and standard airflow measurement lab apparatuses.
The DOE test procedure does not take into account a specially designed
adapter that is needed for measuring the airflows.
IV. Regulatory Framework
DOE's regulations provide that the Assistant Secretary ``will''
grant a Petition to a manufacturer upon a ``determination that the
basic model for which the waiver was requested contains a design
characteristic which either prevents testing of the basic model
according to the prescribed test procedures, or the prescribed test
procedures may evaluate the basic model in a manner so unrepresentative
of its true energy consumption characteristics as to provide materially
inaccurate comparative data.'' See 10 CFR 430.27 (emphasis supplied).
As noted, the current DOE test procedure, 10 CFR part 430, subpart
B, Appendix CC, requires that dual-duct PACs be tested at two operating
conditions, one measuring peak load performance at a high outdoor
operating temperature, and one measuring a reduced load performance at
a lower outdoor operating temperature, and does not make any account
for dual-duct PACs offering variable speed operation based upon
different air test conditions. As a result, Midea's new dual-duct VSC
PACs cannot be tested in a way that accurately reflects the energy
saving benefits of VSC technology. If Midea were to test its dual-duct
VSC PACs to the current test procedure the results would be wholly
unrepresentative of their true energy consumption.
Moreover, the models in Section II of this application cannot be
tested using the current test procedure because the combined-duct
design means that airflows from the inlet and outlet of the condenser
must be measured together, at the same time, as seen in Figure 1. This
requires a specially designed adapter that, naturally, is not part of
the current test procedure. In addition, the duct heat transfer for the
combined duct requires specific instructions on where to place the
thermocouples so the heat transfer can be accounted for, which the
current test procedure does not provide.
[[Page 17816]]
[GRAPHIC] [TIFF OMITTED] TN06AP21.007
V. Other Manufacturers With Similar Design Characteristics
To the best of Midea's knowledge, (i) Midea is the only
manufacturer of dual-duct PACs with combined-duct technology, both with
and without VSCs, in the U.S. market; and (ii) Midea and LG are the
only manufacturers of PACs with VSC technology in the U.S. market.
VI. Proposed Modifications to the Test Procedure
Midea proposes the following alternative test method to evaluate
the performance of the basic models listed in Section II. This
alternative test method is the same as the existing procedure for PACs
per Appendix CC, except it accounts for the combined-duct technology by
describing the means to measure and calculate duct heat transfer and by
providing a provision that requires a special adapter be used during
testing and evaluation to measure the inlet and outlet condenser
airflows. Additionally, the modified test procedure accounts for the
increased efficiency of using VSCs, similar to the approach in the
waver granted to LG published June 2, 2020.\12\ Specifically:
---------------------------------------------------------------------------
\12\ Id.
---------------------------------------------------------------------------
Midea shall be required to test the performance of the basic models
listed in the Section II hereto according to the test procedure for
portable air conditioners in 10 CFR, Part 430, Subpart B, Appendix CC,
and the waiver granted to LG published on June 2, 2020, except as
follows:
Add the following after ``This appendix covers the test
requirements used to measure the energy performance of single-duct and
dual-duct'' in section 1 of Appendix CC: ``, including combined-
duct,''.
Include the following sections from the LG waiver:
``2.11 Single-speed means a type of portable air conditioner that
does not automatically adjust either the compressor or fan speed, or
both, based on the detected outdoor conditions.''
``2.12 Variable-speed means a type of portable air conditioner that
can automatically adjust compressor and fan speed, only compressor
speed, or only fan speed, based on the detected outdoor conditions.''
Replace the following sections from the LG waiver, with:
``2.13 Full compressor speed (full) means the compressor speed
specified by the manufacturer at which the unit operates at full load
testing conditions. Note--full compressor speed may be different at
different test conditions.''
``2.14 Low compressor speed (low) means the compressor speed
specified by the manufacturer at which the unit operates at low load
test conditions, such that Capacity83_Low, the measured
cooling capacity at test condition 3 in Table 1 of this appendix, is no
less than 50 percent and no greater than 60 percent of the measured
cooling capacity with the full compressor speed at test condition 1 in
Table 1 of this appendix.''
Modify section 2.15 of the LG waiver by replacing the word
``single'' with the word ``dual''. Add new section 2.16 to Appendix CC
as follows:
``2.16 Combined-duct portable air conditioner--a version of dual-
duct portable air conditioner where the ducts for the condenser inlet
and outlet air are housed in the same structure.''
Replace the sentence ``Note that if a product is able to operate as
both a single-duct and dual-duct portable AC as distributed in commerce
by the manufacturer, it must be tested and rated for all applicable
duct configurations.'' in section 3.1.1 of Appendix CC with:
``Note that if a product is able to operate in multiple duct
configurations, including single-duct, combined-duct, and dual-duct
portable AC as distributed in commerce by the manufacturer, it must be
tested and rated for all applicable duct configurations.''
Add the following after ``Do not apply additional sealing or
insulation.'' to Appendix CC section 3.1.1.1:
``For combined-duct portable air conditioners a special adapter is
needed for testing to properly measure the condenser inlet and outlet
airflows. This adapter must be provided by the manufacturer and allow
connection of the condenser inlet and outlet airflows to the test lab's
airflow measuring apparatuses.''
Replace the sentence in Appendix CC section 3.1.1.6 with the
following to account for the combination duct temperature measurements:
``Duct temperature measurements. Install any insulation and sealing
[[Page 17817]]
provided by the manufacturer. Then adhere eight equally spaced
thermocouples to the outer surface of the duct, ensuring that the
thermocouples are distributed equally on both the inlet and outlet
portion of the combined-duct. Measure the surface temperature of the
combined duct. Temperature measurements must have an error no greater
than 0.5 [deg]F over the range being measured.''
Include the modifications for section 3.1.2 of Appendix CC as
defined in the LG waiver:
``3.1.2 Control settings. Set the controls to the lowest available
temperature setpoint for cooling mode. If the portable air conditioner
has a user-adjustable fan speed, select the maximum fan speed setting.
If the portable air conditioner has an automatic louver oscillation
feature, disable that feature throughout testing. If the louver
oscillation feature is included but there is no option to disable it,
test with the louver oscillation enabled. If the portable air
conditioner has adjustable louvers, position the louvers parallel with
the air flow to maximize air flow and minimize static pressure loss.
Set the compressor speed during cooling mode testing as described in
section 4.1, as amended by this interim waiver.''
Replace section 4.1 of Appendix CC with the following to account
for both single-speed and variable-speed compressor units as listed in
Section II of this petition:
``4.1 Cooling mode. Instead of the test conditions in Table 3 of
ANSI/AHAM PAC-1-2015, establish the test conditions presented in Table
1 of this appendix. Test each single-speed sample unit twice, once at
test condition 1 and once at test condition 2 in Table 1. Test each
variable-speed sample unit three times, once at each test condition in
Table 1. For each test condition, measure the sample unit's indoor room
cooling capacity and overall power input in cooling mode in accordance
with Section 7.1.b and 7.1.c of ANSI/AHAM PAC-1-2015 (incorporated by
reference; see Sec. 430.3), respectively, and determine the test
duration in accordance with Section 8.7 of ASHRAE Standard 37-2009
(incorporated by reference; Sec. 430.3). Conduct the first test, for
both single and variable-speed units, in accordance with ambient
conditions for test condition 1 in Table 1 of this appendix, with the
compressor speed set to full, for the duration of cooling mode testing
(Capacity95, P95), which represents an outdoor
temperature operating condition of 95 [deg]F dry-bulb and 67 [deg]F
wet-bulb temperatures. Conduct the second test in accordance with the
ambient conditions for test condition 2 in Table 1 of this appendix,
with the compressor speed set to full, for the duration of cooling mode
testing (Capacity83, P83), which represents an
outdoor temperature operating condition of 83 [deg]F dry-bulb and 67.5
[deg]F wet-bulb temperatures. For variable-speed units only, conduct
the third test in accordance with the ambient conditions for test
condition 3 in Table 1 of this appendix, with the compressor speed set
to low for the duration of the cooling mode testing
(Capacity83_Low, P83_Low), which represents an
outdoor temperature operating condition of 83 [deg]F dry-bulb and 67.5
[deg]F wet-bulb temperatures. Set the compressor speed required for
each test condition in accordance with the manufacturer's
instructions.''
Replace Table 1 of Appendix CC with the following:
Table 1--Evaporator (Indoor) and Condenser (Outdoor) Inlet Test Conditions
----------------------------------------------------------------------------------------------------------------
Evaporator inlet air, [deg]F Condenser inlet air, [deg]F
([deg]C) ([deg]C)
Test configuration ---------------------------------------------------------------- Condenser speed
Dry bulb Wet bulb Dry bulb Wet bulb
----------------------------------------------------------------------------------------------------------------
Dual-Duct, Condition 1...... 80 (26.7) 67 (19.4) 95 (35.0) 75 (23.9) Full.
Dual-Duct, Condition 2...... 80 (26.7) 67 (19.4) 83 (28.3) 67.5 (19.7) Full.
Dual-Duct, Condition 3...... 80 (26.7) 67 (19.4) 83 (28.3) 67.5 (19.7) Low.
----------------------------------------------------------------------------------------------------------------
Modify Appendix CC section 4.1.1 with the following after
``Calculate the surface area'': , ACD, to the following
equation:
For combined-duct portable air conditioners:
ACD = P x L
Where:
ACD = the outer area of the combined-duct, in square
feet.
L = the extended length of the combined-duct while under test, in
feet.
P = the perimeter of the combined-duct, as measured following the
instructions below, in ft.
Measure the perimeter of the combined-duct air conditioners using a
flexible measuring tape, or equivalent, by wrapping the measuring tape
around the outside of the combined-duct, making sure the tape is on the
outermost ridges.
Calculate the total heat transferred from the surface of the
duct(s) to the indoor conditioned space while operating in cooling mode
for the outdoor test conditions in Table 1 of this appendix, as
follows.
For combined-duct portable air conditioners:
QCD_95 = h x ACD x (TCD_95-
Tei)
QCD_83 = h x ACD x (TCD_83-
Tei)
QCD_83_Low = h x ACD x (TCD_83_Low-
Tei)
Where:
QCD_95, QCD_83, and QCD_83_Low =
for combined-duct portable air conditioners, the total heat
transferred from the ducts to the indoor conditioned space in
cooling mode, in Btu/h, when tested according to test condition 1,
2, and 3 in Table 1 of this appendix, respectively.
TCD_95, TCD_83, and TCD_83_Low =
average surface temperature for the duct, as measured during testing
according to the three outdoor test conditions in Table 1 of this
appendix, in [deg]F.
ACD = the outer area of the combined-duct, in square
feet.
h = convection coefficient, 3 Btu/h per square foot per [deg]F.
Replace section 4.1.2 in Appendix CC with the following:
``4.1.2 Infiltration Air Heat Transfer. Measure the heat
contribution from infiltration air for dual- duct portable air
conditioners that draw at least part of the condenser air from the
conditioned space. Calculate the heat contribution from infiltration
air for dual-duct portable air conditioners for all cooling mode
outdoor test conditions, as described in this section. Calculate the
dry air mass flow rate of infiltration air according to the following
equations:
[[Page 17818]]
[GRAPHIC] [TIFF OMITTED] TN06AP21.008
Where:
m95, m83 and m83_Low = dry air mass
flow rate of infiltration air for dual-duct portable air
conditioners, as calculated based on testing according to the test
conditions in Table 1 of this appendix, in lb/m.
Vco_95, Vco_83 and Vco_83_Low =
average volumetric flow rate of the condenser outlet air during
cooling mode testing for single-duct portable air conditioners; and
at the 95 [deg]F and 83 [deg]F dry-bulb outdoor conditions for dual-
duct portable air conditioners, respectively, in cubic feet per
minute (cfm).
Vci_95, Vci_83 and Vci_83_Low =
average volumetric flow rate of the condenser inlet air during
cooling mode testing at the 95 [deg]F and 83 [deg]F dry-bulb outdoor
conditions for dual-duct portable air conditioners, respectively, in
cfm.
[rho]co_95, [rho]co_83 and
[rho]co_83_Low = average density of the condenser outlet
air during cooling mode testing for single-duct portable air
conditioners, and at the 95 [deg]F and 83 [deg]F dry-bulb outdoor
conditions for dual-duct portable air conditioners, respectively, in
pounds mass per cubic foot (lbm/ft\3\).
[rho]ci_95, [rho]ci_83 and
[rho]ci_83_Low = average density of the condenser inlet
air during cooling mode testing at the 95 [deg]F and 83 [deg]F dry-
bulb outdoor conditions for dual-duct portable air conditioners,
respectively, in lbm/ft\3\.
[omega]co_95, [omega]co_83 and
[omega]co_83_Low = average humidity ratio of condenser
outlet air during cooling mode testing for single-duct portable air
conditioners, and at the 95 [deg]F and 83 [deg]F dry-bulb outdoor
conditions for dual-duct portable air conditioners, respectively, in
pounds mass of water vapor per pounds mass of dry air
(lbw/lbda).
[omega]ci_95, [omega]ci_83 and
[omega]ci_83_Low = average humidity ratio of condenser
inlet air during cooling mode testing at the 95 [deg]F and 83 [deg]F
dry-bulb outdoor conditions for dual-duct portable air conditioners,
respectively, in lbw/lbda.
Calculate the sensible component of infiltration air heat
contribution according to:
Qs_95 = m x 60 x [cp_da x (Tia_95 -
Tindoor) + (cp_wv x ([omega]ia_95 x
Tia_95 - [omega]indoor x Tindoor))]
Qs_83 = m x 60 x [(cp_da x (Tia_83 -
Tindoor) + (cp_wv x ([omega]ia_83 x
Tia_83 - [omega]indoor x Tindoor))]
Qs_83_Low = m x 60 x [(cp_da x (Tia_83
- Tindoor) + (cp_wv x ([omega]ia_83 x
Tia_83 - [omega]indoor x Tindoor))
Where:
Qs_95, Qs_83 and Qs_83_Low =
sensible heat added to the room by infiltration air, calculated at
the 1, 2, and 3 test conditions respectively in Table 1 of this
appendix, in Btu/h.
m = dry air mass flow rate of infiltration air, mSD or
m95 when calculating Qs_95 and mSD
or m83 when calculating Qs_83 and
m83_Low when calculating Qs_83_Low, in lb/m.
cp_da = specific heat of dry air, 0.24 Btu/lbm
- [deg]F.
cp_wv = specific heat of water vapor, 0.444 Btu/
lbm - [deg]F. Tindoor = indoor chamber dry-
bulb temperature, 80 [deg]F.
Tia_95 and Tia_83 = infiltration air dry-bulb
temperatures for the three test conditions in Table 1 of this
appendix, 95 [deg]F and 83 [deg]F, respectively.
[omega]ia_95 and [omega]ia_83 = humidity
ratios of the 95 [deg]F and 83 [deg]F dry-bulb infiltration air,
0.0141 and 0.01086 lbw/lbda, respectively.
[omega]indoor = humidity ratio of the indoor chamber air,
0.0112 lbw/lbda.
60 = conversion factor from minutes to hours.
Calculate the latent heat contribution of the infiltration air
according to:
Ql_95 = m x 60 x Hfg x ([omega]ia_95 -
[omega]indoor)
Ql_83 = m x 60 x Hfg x ([omega]ia_83 -
[omega]indoor)
Ql_83_Low = m x 60 x Hfg x
([omega]ia_83 - [omega]indoor)
Where:
Ql_95, Ql_83 and Ql_83_LOW = latent
heat added to the room by infiltration air, calculated at the 1, 2,
and 3 test conditions respectively in Table 1 of this appendix, in
Btu/h.
m = mass flow rate of infiltration air, mSD or
m95 when calculating Ql_95 and mSD
or m83 when calculating Ql_83 and
m83_Low when calculating Qs_83_Low, in lb/m.
Hfg = latent heat of vaporization for water vapor, 1061
Btu/lbm.
[omega]ia_95 and [omega]ia_83 = humidity
ratios of the 95 [deg]F and 83 [deg]F dry-bulb infiltration air,
0.0141 and 0.01086 lbw/lbda, respectively.
[omega]indoor = humidity ratio of the indoor chamber air,
0.0112 lbw/lbda.
60 = conversion factor from minutes to hours.
The total heat contribution of the infiltration air is the sum of
the sensible and latent heat:
Qinfiltration_95 = Qs_95 + Ql_95
Qinfiltration_83 = Qs_83 + Ql_83
Qinfiltration_83_Low = Qs_83_Low +
Ql_83_Low
Where:
Qinfiltration_95, Qinfiltration_83 and
Qinfiltration_83_Low = total infiltration air heat in
cooling mode, calculated at the 1, 2, and 3 test conditions
respectively in Table 1 of this appendix, in Btu/h.
Qs_95, Qs_83 and Qs_83_Low =
sensible heat added to the room by infiltration air, calculated at
the 1, 2, and 3 test conditions respectively in Table 1 of this
appendix, in Btu/h.
Ql_95, Ql_83 and Ql_83_Low = latent
heat added to the room by infiltration air, calculated at the 1, 2,
and 3 test conditions respectively in Table 1 of this appendix, in
Btu/h.
Modify section 5.1 of Appendix CC after ``Calculate the adjusted
cooling capacities for portable air conditioners, ACC95,
ACC83,'' with the following:
``and ACC83_Low expressed in Btu/h, according to the
following equations:
ACC95 = Capacity95--QCD_95 -
Qinfiltration_95
ACC83 = Capacity83 -- QCD_83 -
Qinfiltration_83
ACC83_Low = Capacity83_Low -
QCD_83_Low - Qinfiltration_83_Low
Where:
Capacity95, Capacity83, and
Capacity83_Low = cooling capacity measured in section
4.1.1 of this appendix.
QCD_95, QCD_83, and QCD_83_Low =
duct heat transfer while operating in cooling mode, calculated in
section 4.1.1.1 of this appendix.
Qinfiltration_95, Qinfiltration_83, and
Qinfiltration_83_Low = total infiltration air heat
transfer in cooling mode, calculated in section 4.1.1.2 of this
appendix.''
Replace the table of Annual Operating Hours in Appendix CC section
5.3 with the following:
[[Page 17819]]
------------------------------------------------------------------------
Annual
Operating mode operating
hours
------------------------------------------------------------------------
Cooling Mode, Dual-Duct test condition 1..................... 750
Cooling Mode, Dual-Duct test condition 2..................... 750
Cooling Mode, Dual-Duct, test condition 3.................... 750
Off-Cycle.................................................... 880
Inactive or Off.............................................. 1,355
------------------------------------------------------------------------
Change the definition of variable ``m'' in Appendix CC section 5.3
to the following:
``m represents the operating mode (``95'' for test condition 1,
``83'' for test condition 2, ``83_Low'' for test condition 3, ``oc''
off cycle, and ``ia'' inactive or ``om'' off mode).''
Replace section 5.4 of Appendix CC with the following:
``5.4 Combined Energy Efficiency Ratio. Using the annual operating
hours, as outlined in section.
5.3 of this appendix, calculate the combined energy efficiency
ratios, CEERSS and CEERUA, expressed in Btu/Wh,
according to the following:
For Single-Speed Units:
[GRAPHIC] [TIFF OMITTED] TN06AP21.009
For Variable Speed Units:
[GRAPHIC] [TIFF OMITTED] TN06AP21.010
Where:
CEERSS = combined energy efficiency ratio for the single-
speed portable air conditioner, in Btu/Wh.
ACC95, ACC83 and ACC83_Low =
adjusted cooling capacity, in Btu/h, calculated in section 5.1 of
this appendix.
CEERUA = combined energy efficiency ratio for the
variable-speed portable air conditioner, in Btu/Wh.
AEC95, AEC83, and AEC83_Low =
annual energy consumption for the cooling mode tests, in kWh/year,
calculated in section 5.3 of this appendix.
AECT = total annual energy consumption attributed to all
modes except cooling, in kWh/year, calculated in section 5.3 of this
appendix.
750 = number of cooling mode hours per year.
0.01 kWh/Wh = conversion factor for watt-hours to kilowatt-hours.
0.2 = weighting factor for the 95 [deg]F dry-bulb outdoor condition
test.
0.8 = weighting factor for the 83 [deg]F dry-bulb outdoor condition
test.''
Modify section 5.5 of the LG waiver by adding the following after
``Adjust the combined energy efficiency ratio'' and before ``as
follows.'': ``for variable speed units''
Modify section 5.5.1 of the LG waiver by replacing everything after
``Calculate the cooling capacity and cooling capacity with cycling
losses, expressed in British thermal units per hour (Btu/h), and
electrical power input, expressed in watts, for a theoretical
comparable single-speed portable air conditioner'' with the following:
``at test condition 2 in Table 1 of this appendix. A theoretical
comparable single-speed compressor has the same cooling capacity and
electrical input, with cycling losses, as the tested per test condition
2 in Table 4.1 of this appendix and further adjusted to account for the
different compressor speeds.
Capacity83_SS = Capacity83 x FCap
Capacity83_SS_CLF = Capacity83_SS x 0.875
P83_SS = P83 x FCap
Where:
Capacity83_SS = theoretical comparable single-speed
portable air conditioner cooling capacity, in Btu/h, calculated for
test condition 2 in Table 1.
Capacity83_SS_CLF = theoretical comparable single-speed
portable air conditioner cooling capacity with cycling losses, in
Btu/h, calculated for test condition 2 in Table 1.
Capacity83 = variable-speed portable air conditioner
cooling capacity, in Btu/h, determined in section 4.1 of this
appendix for test condition 2 in Table 1.
P83_SS = theoretical comparable single-speed portable air
conditioner electrical power input, in watts, calculated for test
condition 2 in Table 1.
P83 = variable-speed portable air conditioner electrical
power input, in watts, determined in section 4.1 of this appendix
for test condition 2 in Table 1.
0.875 = cycling loss factor for the 83 [deg]F dry-bulb outdoor
temperature operating condition.
FCap = adjustment factor to account for different
compressor speeds at test condition 2 in Table 1 of this appendix
between single-speed and variable-speed compressors, 0.92.''
Delete section 5.5.2 from the LG waiver. This section is not
needed, and instead the duct loss for a comparable single speed unit is
accounted for in section 4.1.1.
Delete section 5.5.3 from the LG waiver. This section is not
needed, and instead the infiltration for a comparable single speed unit
is accounted for in section 4.1.2.
Replace section 5.5.4 in the LG waiver with the following:
``5.5.4 Adjusted Cooling Capacity for a Theoretical Comparable
Single-Speed Portable Air Conditioner at the Lower Outdoor Test
Condition. Calculate the adjusted cooling capacity for a theoretical
comparable single-speed portable air conditioner operating at test
condition 2 in Table 1 of this appendix with and without cycling
losses, ACC83_SS and ACC 83_SS_CLF, respectively,
expressed in Btu/h, according to the following equation:
ACC83_SS = Capacity83_SS - QCD_83 -
Qinfiltration_83
ACC83_SS_CLF = Capacity83_SS_CLF -
QCD_83 - Qinfiltration_83
Where:
ACC83_SS and ACC83_SS_CLF = adjusted cooling
capacity for a theoretical comparable single-speed portable air
conditioner at test condition 2 in Table 1 of this appendix without
and with cycling losses, respectively, in Btu/h.
Capacity83_SS and Capacity83_SS_CLF =
theoretical comparable single-speed
[[Page 17820]]
portable air conditioner cooling capacity without and with cycling
losses, respectively, in Btu/h, at test condition 2 in Table 1 of
this appendix, calculated in section 5.5.1 of this appendix.
QCD_83 = total heat transferred from the ducts to the
indoor conditioned space in cooling mode for a theoretical
comparable single-speed portable air conditioner at test condition 2
in Table 1 of this appendix, in Btu/h, calculated in section 4.1.1
of this appendix.
Qinfiltration_83_SS = total infiltration air heat in
cooling mode for a theoretical comparable single-speed portable air
conditioner at test condition 2 in Table 1 of this appendix, in Btu/
h, calculated in section 4.1.2 of this appendix.''
Modify section 5.5.5 in the LG waiver by replacing everything after
``Calculate the annual energy consumption in cooling mode for a
theoretical comparable single-speed portable air conditioner at'' with
the following:
``test condition 2 in Table 1 of this appendix, in kWh/year, according
to the following equations:
AEC83_SS = P83_SS x 750 x 0.001
Where:
AEC83_SS = annual energy consumption for a theoretical
comparable single-speed portable air conditioner in cooling mode at
test condition 2 in Table 1 of this appendix, in kWh/year.
P83_SS = electrical power input for a theoretical
comparable single-speed portable air conditioner electrical power
input at condition 2 in Table 1 of this appendix, in watts,
calculated in section 5.5.1 of this appendix.
750 = number of cooling mode hours per year, as defined in section
5.3 of this appendix.
0.001 kWh/Wh = conversion factor from watt-hours to kilowatt-hours.
Replace section 5.5.6 of the LG waiver with the following:
``5.5.6 Combined Energy Efficiency Ratio for a Theoretical
Comparable Single-Speed Portable Air Conditioner. Calculate the
combined energy efficiency ratio for a theoretical comparable single-
speed portable air conditioner without and with cycling,
CEERSS, and with cycling losses, CEERSS_CLF, in
Btu/Wh, according to the following equations:
[GRAPHIC] [TIFF OMITTED] TN06AP21.011
Where:
CEERSS and CEERSS_CLF = combined energy
efficiency ratio for a theoretical comparable single-speed portable
air conditioner without and with cycling losses considered,
respectively, in Btu/Wh.
ACC95 = adjusted cooling capacity for the sample unit, as
calculated in section 5.1 of this appendix, when tested at test
condition 1 in Table 1 of this appendix that is representative of
operation at the 95 [deg]F dry-bulb outdoor temperature operating
condition, in Btu/h.
ACC83 and ACC83_SS_CLF = adjusted cooling
capacity for a theoretical comparable single-speed portable air
conditioner at test condition 2 in Table 1 of this appendix without
and with cycling losses, respectively, as calculated in section
5.5.4 of this appendix, in Btu/h.
AEC95 = annual energy consumption for the sample unit, as
calculated in section 5.3 of this appendix, for cooling mode
operation at test condition 1 in Table 1 of this appendix that
represents operation at a 95 [deg]F dry-bulb outdoor temperature
operating condition, in kWh/year.
AEC83_SS = annual energy consumption for a theoretical
comparable single-speed portable air conditioner in cooling mode at
test condition 2 in Table 1 of this appendix, calculated in section
5.5.5 of this appendix, in kWh/year.
AECT = total annual energy consumption attributed to all
operating modes except cooling for the sample unit, calculated in
section 5.3 of this appendix, in kWh/year.
750 and 0.001 as defined previously in this section.
0.2 = weighting factor for the 95 [deg]F dry-bulb outdoor
temperature operating condition.
0.8 = weighting factor for the 83 [deg]F dry-bulb outdoor
temperature operating condition.''
VII. Additional Justification for Interim Waiver Application
a. There Is a Strong Likelihood That the Waiver Will Be Granted
This Petition provides strong evidence that the Waiver will be
granted. A Waiver is appropriate because the current test procedure
does not accurately reflect the energy efficiency of models with VSCs
since it tests only in the full load condition at two test points.
These compressors can vary the rotational speed based upon the
difference in unit set-point and the ambient temperature of the
conditioned space, and will optimize the energy usage based on these
conditions that can result in a greater compressor speed at less load.
A PAC without a VSC cannot operate in this fashion as the compressor is
either on at full capacity or off. The test procedure in the waiver
granted to LG published on June 2, 2020, will account for energy being
used at different test conditions with some modification for Midea's
units.
Additionally, the current test procedure does not account for
Midea's unique combined- duct technology that requires special
provisions to measure the inlet and outlet condenser airflow and
measure the duct heat transfer. Midea has also demonstrated that its
approach is consistent with waivers granted by DOE to other
manufacturers with VSC technology.
b. Economic Hardship Would Be Caused by Denial of an Interim Waiver
In the absence of an Interim Waiver, Midea will lack certainty as
to whether it can launch these combined-duct PACs with VSCs. Midea
believes there will be strong consumer demand for these PACs, and the
inability to market due to the denial of an Interim Waiver will cause
economic hardship and competitive disadvantage to Midea. This is
because there are exceptionally long lead times and significant
expenses associated with the design and manufacturer of PACs.
Compliance with energy consumption standards is a critical design
factor for all of Midea's PACs. Any delay in obtaining clarity on this
issue will force Midea to postpone key decisions regarding its
investments to build, launch and market these PACs. In the event that
this Interim Waiver is not approved, Midea would not be able to move
forward with the launch of these models, resulting in a multi-million-
dollar impact to the company and would require costly contingency plans
and put us at a competitive disadvantage to competitors.
[[Page 17821]]
C. Sound Public Policy Supports Grant of the Interim Waiver
The grant of an Interim Waiver is also supported by sound public
policy. The models for which an interim waiver is sought utilize
technological advances that increase energy efficiency, reduce energy
consumption, lower costs for consumers, and provide enhanced comfort.
Conclusion
Midea respectfully requests that DOE grant this Petition for Waiver
and Application for Interim Waiver. By granting this Waiver, DOE will
ensure that consumers will have access to new, innovative and energy
efficient combined-duct PACs with and without VSCs.
Respectfully submitted,
/s/--------------------------------------------------------------------
Scott Blake Harris
John Hodges
Harris, Wiltshire & Grannis LLP, 1919 M Street NW, Washington, DC
20036, Counsel for GD Midea Air Conditioning Equipment Co. LTD.
[FR Doc. 2021-07025 Filed 4-5-21; 8:45 am]
BILLING CODE 6450-01-P