Energy Conservation Program: Notice of Petition for Waiver of Store It Cold From the Department of Energy Walk-In Cooler Refrigeration System Test Procedure, and Notice of Grant of Interim Waiver, 11944-11965 [2019-06100]
Download as PDF
jbell on DSK30RV082PROD with NOTICES
11944
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
from the United States to Canada
pursuant to the Federal Power Act.
DATES: Comments, protests, or motions
to intervene must be submitted on or
before April 29, 2019.
ADDRESSES: Comments, protests,
motions to intervene, or requests for
more information should be addressed
to: Office of Electricity, Mail Code: OE–
20, U.S. Department of Energy, 1000
Independence Avenue SW, Washington,
DC 20585–0350. Because of delays in
handling conventional mail, it is
recommended that documents be
transmitted by overnight mail, by
electronic mail to Electricity.Exports@
hq.doe.gov, or by facsimile to 202–586–
8008.
SUPPLEMENTARY INFORMATION: The
Department of Energy (DOE) regulates
exports of electricity from the United
States to a foreign country, pursuant to
sections 301(b) and 402(f) of the
Department of Energy Organization Act
(42 U.S.C. 7151(b) and 7172(f)). Such
exports require authorization under
section 202(e) of the Federal Power Act
(16 U.S.C. 824a(e)).
On March 1, 2019, DOE received an
application from PSE for authorization
to transmit electric energy from the
United States to Canada as a power
marketer for a five-year term using
existing international transmission
facilities. DOE most recently granted
export authorization to PSE on May 6,
2014 for a five-year term, in Order No.
EA–98–M. That Order authorized
electricity exports by PSE and certain
other members of WSPP Inc., which the
Order described as ‘‘a non-profit
organization with approximately 300
electric utility members.’’ In its present
application, PSE requests authorization
effective by May 6, 2019, to prevent a
lapse in its current authorization under
Order No. EA–98–M, which expires on
that date.
In its application, PSE’s resale and
wholesale utility business includes the
generation, purchase, transmission,
distribution, and sale of electric energy.
The electric energy that PSE proposes to
export to Canada would be surplus
energy sold to a portfolio of resources,
including electric energy generated by
PSE’s system resources and electric
energy acquired from other sellers
within the United States and Canada.
The existing international transmission
facilities to be utilized by the Applicant
have previously been authorized by
Presidential permits issued pursuant to
Executive Order 10485, as amended,
and are appropriate for open access
transmission by third parties.
Procedural Matters: Any person
desiring to be heard in this proceeding
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
should file a comment or protest to the
application at the address provided
above. Protests should be filed in
accordance with Rule 211 of the Federal
Energy Regulatory Commission’s (FERC)
Rules of Practice and Procedure (18 CFR
385.211). Any person desiring to
become a party to this proceeding
should file a motion to intervene at the
above address in accordance with FERC
Rule 214 (18 CFR 385.214). Five (5)
copies of such comments, protests, or
motions to intervene should be sent to
the address provided above on or before
the date listed above.
Comments and other filings
concerning PSE’s application to export
electric energy to Canada should be
clearly marked with OE Docket No. EA–
469. An additional copy is to be
provided directly to both Robert E.
Neate, Puget Sound Energy, Inc., Puget
Sound Energy, EST–11N, P.O. Box
97034, Bellevue, Washington 98009–
9734 and Jason Kuzma, Perkins Coie
LLP, 10885 NE 4th Street, Suite 700,
Bellevue, Washington 98004.
A final decision will be made on this
application after the environmental
impacts have been evaluated pursuant
to DOE’s National Environmental Policy
Act Implementing Procedures (10 CFR
part 1021) and after DOE determines
that the proposed action will not have
an adverse impact on the sufficiency of
supply or reliability of the U.S. electric
power supply system.
Copies of this application will be
made available, upon request, for public
inspection and copying at the address
provided above, by accessing the
program website at https://energy.gov/
node/11845, or by emailing Angela Troy
at Angela.Troy@hq.doe.gov.
Signed in Washington, DC, on March 25,
2019.
Christopher Lawrence,
Management and Program Analyst,
Transmission Permitting and Technical
Assistance, Office of Electricity.
[FR Doc. 2019–06098 Filed 3–28–19; 8:45 am]
BILLING CODE 6450–01–P
DEPARTMENT OF ENERGY
[Case Number 2018–002; EERE–2018–BT–
WAV–0002]
Energy Conservation Program: Notice
of Petition for Waiver of Store It Cold
From the Department of Energy WalkIn Cooler Refrigeration System Test
Procedure, and Notice of Grant of
Interim Waiver
Office of Energy Efficiency and
Renewable Energy, Department of
Energy.
AGENCY:
PO 00000
Frm 00019
Fmt 4703
Sfmt 4703
Notice of petition for waiver,
notice of grant of an interim waiver, and
request for comments.
ACTION:
The U.S. Department of
Energy (‘‘DOE’’) announces receipt of
and publishes a petition for waiver from
Store It Cold, which seeks a waiver from
the test procedure used for determining
the efficiency of walk-in cooler
refrigeration system basic models. Store
It Cold seeks to use an alternate test
procedure to address issues involved in
testing certain basic models identified
in its petition. Store It Cold asserts in its
petition that for the specified °CoolBot®
Walk-In Cooler refrigeration system
basic models taking ‘‘refrigerant-side’’
measurements with refrigerant mass
flow meters yields results that are
unrepresentative of the basic models’
true energy consumption characteristics
and provides materially inaccurate
comparative data. Accordingly, Store It
Cold seeks to test and rate the basic
models identified in its petition using
its recommended alternate test
procedure, in which the refrigeration
capacity is measured using
psychrometric ‘‘air-side’’ measurements.
This document announces that DOE is
granting Store It Cold with an interim
waiver from DOE’s walk-in cooler
refrigeration system test procedure for
the specified basic models, subject to
use of the alternate test procedure as set
forth in the Interim Waiver Order. DOE
solicits comments, data, and
information concerning Store It Cold’s
petition and its suggested alternate test
procedure to inform its final decision on
Store It Cold’s waiver request.
DATES: DOE will accept comments, data,
and information with respect to the
Store It Cold petition until April 29,
2019.
SUMMARY:
Interested persons are
encouraged to submit comments using
the Federal eRulemaking Portal at
https://www.regulations.gov.
Alternatively, interested persons may
submit comments, identified by case
number ‘‘2018–002,’’ and Docket
number ‘‘EERE–2018–BT–WAV–0002,’’
by any of the following methods:
• Federal eRulemaking Portal: https://
www.regulations.gov. Follow the
instructions for submitting comments.
• E-mail: storeitcold2018wav0002@
ee.doe.gov. Include the case number
[Case No. 2018–002] in the subject line
of the message.
• Postal Mail: Appliance and
Equipment Standards Program, U.S.
Department of Energy, Office of Energy
Efficiency and Renewable Energy,
Building Technologies Office, Mailstop
EE–5B, Petition for Waiver Case No.
ADDRESSES:
E:\FR\FM\29MRN1.SGM
29MRN1
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
jbell on DSK30RV082PROD with NOTICES
2018–002, 1000 Independence Avenue
SW, Washington, DC 20585–0121. If
possible, please submit all items on a
compact disc (‘‘CD’’), in which case it is
not necessary to include printed copies.
• Hand Delivery/Courier: Appliance
and Equipment Standards Program, U.S.
Department of Energy, Building
Technologies Office, 950 L’Enfant Plaza
SW, Room 6055, Washington, DC,
20024. If possible, please submit all
items on a compact disc (‘‘CD’’), in
which case it is not necessary to include
printed copies.
No telefacsimilies (faxes) will be
accepted. For detailed instructions on
submitting comments and additional
information on this process, see section
V of this document.
Docket: The docket, which includes
Federal Register notices, comments,
and other supporting documents/
materials, is available for review at
https://www.regulations.gov. All
documents in the docket are listed in
the https://www.regulations.gov index.
However, some documents listed in the
index, such as those containing
information that is exempt from public
disclosure, may not be publicly
available.
The docket web page can be found at
https://www.regulations.gov/
docket?D=EERE-2018-BT-WAV-0002.
The docket web page contains simple
instruction on how to access all
documents, including public comments,
in the docket. See section V for
information on how to submit
comments through https://
www.regulations.gov.
FOR FURTHER INFORMATION CONTACT: Ms.
Lucy deButts, U.S. Department of
Energy, Building Technologies Office,
Mailstop EE–5B, 1000 Independence
Avenue SW, Washington, DC 20585–
0121. E-mail: AS_Waiver_Requests@
ee.doe.gov.
Mr. Michael Kido, U.S. Department of
Energy, Office of the General Counsel,
Mail Stop GC–33, Forrestal Building,
1000 Independence Avenue SW,
Washington, DC 20585–0103.
Telephone: (202) 586–8145. Email:
Michael.Kido@hq.doe.gov.
SUPPLEMENTARY INFORMATION:
I. Background and Authority
The Energy Policy and Conservation
Act of 1975, as amended, (‘‘EPCA’’) 1 (42
U.S.C. 6291–6317), among other things,
authorizes DOE to regulate the energy
efficiency of a number of consumer
products and industrial equipment.
1 All references to EPCA in this document refer
to the statute as amended through America’s Water
Infrastructure Act of 2018, Public Law 115–270
(October 23, 2018).
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
Title III, Part C 2 of EPCA established the
Energy Conservation Program for
Certain Industrial Equipment, which
sets forth a variety of provisions
designed to improve energy efficiency
for certain types of industrial
equipment. This equipment includes
walk-in cooler refrigeration systems, the
focus of this document. (42 U.S.C.
6311(1)(G)) A walk-in cooler and freezer
is defined under DOE’s regulations as
‘‘an enclosed storage space refrigerated
to temperatures, respectively, above,
and at or below 32 degrees Fahrenheit
that can be walked into, and has a total
chilled storage area of less than 3,000
square feet; however[,] the terms do not
include products designed and
marketed exclusively for medical,
scientific, or research purposes.’’ 10
CFR 431.302. See also 42 U.S.C.
6311(20) (statutory definition for ‘‘walkin cooler, walk-in freezer’’).
Under EPCA, DOE’s energy
conservation program consists
essentially of four parts: (1) Testing, (2)
labeling, (3) Federal energy conservation
standards, and (4) certification and
enforcement procedures. Relevant
provisions of EPCA include definitions
(42 U.S.C. 6311), energy conservation
standards (42 U.S.C. 6313), test
procedures (42 U.S.C. 6314), labeling
provisions (42 U.S.C. 6315), and the
authority to require information and
reports from manufacturers (42 U.S.C.
6316).
The Federal testing requirements
consist of test procedures that
manufacturers of covered equipment
must use as the basis for: (1) Certifying
to DOE that their equipment complies
with the applicable energy conservation
standards adopted pursuant to EPCA (42
U.S.C. 6316(a); 42 U.S.C. 6295(s)), and
(2) making representations about the
efficiency of that equipment (42 U.S.C.
6314(d)). Similarly, DOE must use these
test procedures to determine whether
the equipment complies with relevant
standards promulgated under EPCA. (42
U.S.C. 6316(a); 42 U.S.C. 6295(s))
Under 42 U.S.C. 6314, EPCA sets forth
the criteria and procedures DOE is
required to follow when prescribing or
amending test procedures for covered
products/equipment. EPCA requires that
any test procedures prescribed or
amended under this section must be
reasonably designed to produce test
results which reflect the energy
efficiency, energy use or estimated
annual operating cost of a covered
product/covered equipment during a
representative average use cycle and
requires that test procedures not be
2 For editorial reasons, upon codification in the
U.S. Code, Part C was re-designated as Part A–1.
PO 00000
Frm 00020
Fmt 4703
Sfmt 4703
11945
unduly burdensome to conduct. (42
U.S.C. 6314(a)(2)) The test procedure
used to determine the net capacity and
Annual Walk-in Energy Factor
(‘‘AWEF’’) of walk-in cooler
refrigeration systems is contained in the
Code of Federal Regulations (‘‘CFR’’) at
10 CFR part 431, subpart R, appendix C.
Under 10 CFR 431.401, any interested
person may submit a petition for waiver
from DOE’s test procedure
requirements. DOE will grant a waiver
from the test procedure requirements if
DOE determines either that the basic
model for which the waiver was
requested contains a design
characteristic that prevents testing of the
basic model according to the prescribed
test procedures, or that the prescribed
test procedures evaluate the basic model
in a manner so unrepresentative of its
true energy consumption characteristics
as to provide materially inaccurate
comparative data. 10 CFR 431.401(f)(2).
A petitioner must include in its petition
any alternate test procedures known to
the petitioner to evaluate the basic
model in a manner representative of its
energy consumption characteristics. 10
CFR 431.401(b)(1)(iii).
DOE may grant the waiver subject to
conditions, including adherence to
alternate test procedures. 10 CFR
431.401(f)(2). As soon as practicable
after the granting of any waiver, DOE
will publish in the Federal Register a
notice of proposed rulemaking to amend
its regulations so as to eliminate any
need for the continuation of such
waiver. 10 CFR 431.401(l). As soon
thereafter as practicable, DOE will
publish in the Federal Register a final
rule. Id.
The waiver process also provides that
DOE may grant an interim waiver if it
appears likely that the underlying
petition for waiver will be granted and/
or if DOE determines that it would be
desirable for public policy reasons to
grant immediate relief pending a
determination on the underlying
petition for waiver. 10 CFR
431.401(e)(2). Within one year of
issuance of an interim waiver, DOE will
either: (i) Publish in the Federal
Register a determination on the petition
for waiver; or (ii) publish in the Federal
Register a new or amended test
procedure that addresses the issues
presented in the waiver. 10 CFR
431.401(h)(1).
When DOE amends the test procedure
to address the issues presented in a
waiver, the waiver will automatically
terminate on the date on which use of
that test procedure is required to
demonstrate compliance. 10 CFR
431.401(h)(2).
E:\FR\FM\29MRN1.SGM
29MRN1
11946
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
jbell on DSK30RV082PROD with NOTICES
II. Store It Cold’s Petition for Waiver
and Application for Interim Waiver
On March 9, 2018, Store It Cold filed
a petition for waiver and a petition for
interim waiver from the test procedure
applicable to walk-in cooler
refrigeration systems set forth in 10 CFR
part 431, subpart R, appendix C, and in
response to DOE requests for technical
clarification, Store It Cold submitted a
revised petition for waiver and petition
for interim waiver on May 16, 2018.
(Store It Cold, No. 1 at pp. 1–7 3) AHRI
Standard 1250P (I–P)-2009 titled
‘‘Standard for Performance Rating of
Walk-in Coolers and Freezers’’ (‘‘AHRI
1250–2009’’) is incorporated by
reference in the test procedure for walkin cooler refrigeration systems with the
modifications enumerated in 10 CFR
part 431, subpart R, appendix C.
Referencing AHRI 1250–2009, 10 CFR
part 431, subpart R, appendix C
provides two possible methods for
measuring the refrigeration capacity of
single-package systems,4 the DX Dual
Instrumentation method and the DX
Calibrated Box method (see section C5.1
through C5.1.2 of AHRI 1250–2009). For
both methods, the refrigeration capacity
is determined by measuring the
enthalpy change and mass flow rate of
the refrigerant (‘‘Refrigerant Enthalpy
Method’’).
Store It Cold’s petition for waiver and
interim waiver lists walk-in cooler
refrigeration system basic models
CBLW08, CBLW10, CBLW12, CBLW15,
CBLW18, CBLW25), which it states are
single-package dedicated refrigeration
systems. These walk-in refrigeration
system basic models are comprised of a
controller (i.e., the °CoolBot® controller)
and a room air conditioner (‘‘RAC’’),
which as combined form a walk-in
refrigeration system. Store It Cold stated
in its petition that the resulting walk-in
refrigeration systems are designated for
both indoor and outdoor use. According
to Store It Cold’s petition, the CoolBot’s
technology controls a much smaller air
conditioner designed to be installed in
a window to maintain desired
3 A notation in this form provides a reference for
information that is in the docket for this test
procedure waiver (Docket No. EERE–2018–BT–
WAV–0002) (available at https://
www.regulations.gov/docket?D=EERE-2018-BTWAV-0002). This notation indicates that the
statement preceding the reference is document
number 1 in the docket and appears at pages 1–7
of that document.
4 ‘‘Single-packaged dedicated system’’ means a
refrigeration system (as defined in 10 CFR 431.302)
that is a single-package assembly that includes one
or more compressors, a condenser, a means for
forced circulation of refrigerated air, and elements
by which heat is transferred from air to refrigerant,
without any element external to the system
imposing resistance to flow of the refrigerated air.
10 CFR 431.302.
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
temperatures, as opposed to a
traditional walk-in cooler that would
utilize large compressors, large surface
area coils, multiple fans, and large
volumes of refrigerant to do the same.5
Store It Cold asserts in its petition
that, for the basic models listed in its
petition, the Refrigerant Enthalpy
Method (referred to as the ‘‘refrigerantside’’ gross capacity method by Store It
Cold) yields inconsistent refrigerant
mass flow rates and lower than expected
capacities. Store It Cold explains in its
petition that the installation of the
refrigerant mass flow meters used under
this method significantly increased the
refrigerant circuit’s internal volume,
requiring the system to be charged with
approximately twice the amount of
refrigerant as was present from the
factory. As a result, Store It Cold
contends that the capacities calculated
with this method are untrustworthy and
unrepresentative of the equipment’s true
performance capabilities.
In its suggested alternate test
procedure, Store It Cold proposes
instead to use an ‘‘air-side’’ method in
which the refrigeration capacity is
determined by measuring the enthalpy
change and mass flow rate of the air
passing through the evaporator side (i.e.,
Indoor Air Enthalpy Method) and
condenser side (i.e., Outdoor Air
Enthalpy Method). The condenser side
measurement is adjusted by subtracting
the system input power to determine
refrigeration capacity. In its petition,
Store It Cold presents ‘‘refrigerant-side’’
and ‘‘air-side’’ capacity test results,
asserting that the latter yields more
consistent measurements and accurate
capacities for the basic models assessed.
As outlined in the petition, in August of
2017, Intertek Testing Services, NA,
Inc., at the request of Store It Cold,
attempted to conduct baseline
performance evaluations on two of the
basic models listed in their petition
(CBLW10 and CBLW15) using the DX
Dual Instrumentation method,6 as
prescribed by AHRI 1250–2009 for
fixed-capacity single-package walk-in
cooler refrigeration systems with
5 Store It Cold notes in its product specification
sheets, that the °CoolBot® controller is also
distributed in commerce separately, i.e., not as part
of a walk-in cooler refrigeration system. This notice
of waiver and notice of grant of an interim waiver
apply only to the walk-in cooler refrigeration
system basic models identified by Store It Cold, i.e.,
the specific models listed in the Interim Waiver
order, which contain °CoolBot® controllers
integrated by Store It Cold with the specified RAC
models.
6 The DX Dual Instrumentation method is the
‘‘refrigerant-side’’ method discussed above (i.e.
Refrigerant Enthalpy Method) but with duplicate
sensors for all measurements. This approach
minimizes the risk of measurement error due to
equipment inaccuracy.
PO 00000
Frm 00021
Fmt 4703
Sfmt 4703
outdoor condensing units. In November
of 2017, Intertek then attempted to
conduct baseline performance
evaluations on two different basic
models listed in their petition (CBLW08
and CBLW25) in accordance with the
test procedure set forth in the AHRI
1250–2009, except that the units’
refrigeration capacities were determined
using the psychrometric ‘‘air-side’’
method proposed in its alternate test
procedure. Store It Cold presents the
test results in Table 1 and Figure 2 of
its petition, which show that the
‘‘refrigerant-side’’ method required
charging the unit to approximately
twice the factory refrigerant charge
because of the additional tubing needed
to accommodate the flow meters
required by the test procedure. Store It
Cold presented data for basic models
CBLW08 and CBLW25 at all three of the
required capacity test conditions
specified in AHRI 1250–2009 for walkin cooler refrigeration systems with
condensing units located outdoors. All
three conditions require the same
evaporator inlet air temperature but
specify progressively decreasing
condenser inlet dry-bulb air
temperatures: 95 °F for the A test
condition, 59 °F for the B test condition,
and 35 °F for the C test condition. For
the CBLW10 basic model, the net
capacity increases from 2,871 Btu/hr in
test condition A to 15,897 Btu/hr in
condition B and then decreases to 7,690
Btu/hr in condition C. Conversely, for
the CBLW15 basic model, the net
capacity decreases from 10,271 Btu/hr
in condition A to 8,846 Btu/hr in
condition B and then increases to 9,160
Btu/hr in condition C.
Store It Cold also presented data from
the ‘‘air-side’’ test performed on two
basic models, CBLW08 and CBLW25.
For the CBLW08 basic model, the net
capacity increases from 5,073 Btu/hr in
test condition A to 6,134 Btu/hr in
condition B and then increases to 6,976
Btu/hr in condition C. For the CBLW25
basic model, the net capacity increases
from 17,582 Btu/hr in condition A to
20,265 Btu/hr in condition B and then
increases to 21,678 Btu/hr in condition
C.
Store It Cold asserted that the
proposed ‘‘air-side’’ method yields more
accurate results for the basic models
listed in its petition and thus that the
alternate test procedure offered in its
petition alleviates the issues identified
with the current procedure.
Store It Cold also requests an interim
waiver from the existing DOE test
procedure. DOE will grant an interim
waiver if it appears likely that the
petition for waiver will be granted, and/
or if DOE determines that it would be
E:\FR\FM\29MRN1.SGM
29MRN1
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
desirable for public policy reasons to
grant immediate relief pending a
determination of the petition for waiver.
See 10 CFR 431.401(e)(2).
DOE understands that, absent an
interim waiver, the specified basic
models cannot be tested and rated for
energy consumption on a basis
representative of their true energy
characteristics. As presented in Store It
Cold’s petition, the subject basic models
of walk-in cooler refrigeration systems
are smaller than the typical walk-in
cooler refrigeration systems. Because of
the smaller size and configuration of the
specified °CoolBot® Walk-In Cooler
refrigeration systems, installation of the
refrigerant mass flow meters as specified
in the DOE test procedure significantly
impacts the internal refrigeration system
volumes and results in inconsistent
refrigerant mass flow rate measurements
and lower than expected capacities.
jbell on DSK30RV082PROD with NOTICES
III. Requested Alternate Test Procedure
EPCA requires that manufacturers use
DOE test procedures when making
representations about the energy
consumption and energy consumption
costs of products covered by the statute.
(42 U.S.C. 6314(d)) Consistent
representations are important for
manufacturers to use in making
representations about the energy
efficiency of their products or
equipment and to demonstrate
compliance with applicable DOE energy
conservation standards. Pursuant to its
regulations at 10 CFR 431.401 applying
to waivers and interim waivers from
applicable test procedures, and after
consideration of public comments on
the petition, DOE will consider setting
an alternate test procedure for the
equipment identified by Store It Cold in
a subsequent Decision and Order.
Store It Cold seeks to use an alternate
test procedure to test and rate specific
walk-in cooler refrigeration system basic
models. Store It Cold suggested that the
specified basic models be tested
according to the test procedure in 10
CFR part 431, subpart R, appendix C,
except that instead of using the
Refrigerant Enthalpy Method to
determine capacity, the specified basic
units be tested using the Indoor Air
Enthalpy and Outdoor Air Enthalpy test
methods to determine capacity.
IV. Summary of Grant of an Interim
Waiver
DOE has reviewed Store It Cold’s
application for an interim waiver, the
alternate test procedure requested by
Store It Cold, the company’s testing and
performance data, product
characteristics, and product
specification sheets published online by
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
Store It Cold. All materials reviewed by
DOE can be found in the docket.7 The
test photo provided by Store It Cold
shows that the refrigerant tubing exiting
the unit has multiple bends in it
without any extended straight sections
upstream and downstream of the
refrigerant mass flow meters, which
could have affected the accuracy of the
mass flow measurements during testing.
Additionally, Store It Cold stated that
the refrigerant tubing as configured
increased the refrigerant circuit’s
internal volume, requiring the system to
be charged with approximately twice
the amount of refrigerant as was present
from the factory.
For refrigeration systems in general, it
is expected that the capacity of the
system would monotonically increase as
the condenser air temperature decreases
(until further increases are limited by
refrigerant mass flow restriction of the
expansion device for the lower
condensing pressures that would occur
for lower condenser air temperatures).
This is because the cooler condenser air
temperature can further cool the
refrigerant such that it leaves the
condenser at lower temperature and
enthalpy,8 and similarly enters the
evaporator at lower enthalpy. This
increases the amount of heat the
refrigerant absorbs from the refrigerated
space as it flows through the evaporator
coil, increasing the capacity of the
evaporator. DOE notes that the
‘‘refrigerant-side’’ method test data in
Store It Cold’s petition do not follow
this trend. Instead, as discussed in
section II, the measured capacity
increases and decreases as condenser air
temperature decreases, with opposite
trends for the tests of basic model
CBLW10 as compared with CBLW15.
These inconsistent results suggest that
the capacity measurements are not
accurate. The mass flow measurements
may not be accurate due to the nonoptimal test setup of the refrigerant lines
conducting the refrigerant to and from
the mass flow meters. Conversely, the
data from testing using the ‘‘air side’’
method follows the expected trend,
showing increasing refrigeration
capacity as condenser air temperature
decreases for both tested units. This
gives much greater confidence that the
measurements are accurate. ‘‘Air side’’
capacity measurements are well
established for measurement of the
capacity of air conditioners (e.g. as
7 The docket is available at https://
www.regulations.gov/docket?D=EERE-2018-BTWAV-0002.
8 Enthalpy is a measure of refrigerant energy per
unit mass—the evaporator capacity (not accounting
for evaporator fan heat) is equal to refrigerant mass
flow multiplied by its enthalpy increase.
PO 00000
Frm 00022
Fmt 4703
Sfmt 4703
11947
described in American Society of
Heating and Air-Conditioning Engineers
(‘‘ASHRAE’’) Standard 37–2009,
‘‘Methods of Testing for Rating
Electrically Driven Unitary AirConditioning and Heat Pump
Equipment’’, which is incorporated by
reference into the requested alternate
test procedure), and the principles of
air-conditioner capacity measurement
apply equally to the capacity
measurement for refrigeration systems.
Therefore, DOE initially agrees that,
for the basic models listed in Store It
Cold’s petition, the current test
procedure produces results
unrepresentative of their true energy
consumption characteristics and
provides materially inaccurate
comparative data. Alternatively, DOE
notes that the ‘‘air-side’’ method
suggested in Store It Cold’s petition
does not require installation of a
refrigerant mass flow meter or any
alteration of the test unit’s refrigerant
charge. Further, DOE finds that the test
data for the proposed ‘‘air-side’’ method
is consistent with the performance
expected for refrigeration systems (i.e.
refrigeration capacity varies inversely
with condenser air temperature).
Based on this review, the alternate
test procedure appears to allow for the
accurate measurement of the of
efficiency of this equipment, while
alleviating the testing problems
associated with Store It Cold’s
implementation of walk-in cooler
refrigeration systems testing for the
basic models specified in its petition.
Consequently, it appears likely that
Store It Cold’s petition for waiver will
be granted. Furthermore, DOE has
determined that it is desirable for public
policy reasons to grant Store It Cold
immediate relief pending a
determination of the petition for waiver.
DOE recognizes that Store It Cold’s
refrigeration system, which is based
primarily on an off-the-shelf room air
conditioner coupled with its CoolBot
controller, is an unconventional one
compared to most other walk-in
refrigeration systems. The Agency
acknowledges, however, that Store It
Cold identifies this equipment in its
petition as a ‘‘single-package[d]
dedicated system’’ used to refrigerate
walk-in units and also offers this
equipment as part of a complete walkin kit. See https://www.storeitcold.com/
coolbot-walk-in-cooler/. DOE notes that
its decision to grant Store It Cold with
an interim waiver in this case is limited
to the specific facts presented in this
particular matter and does not
necessarily reflect how DOE would view
similar equipment—but involving
E:\FR\FM\29MRN1.SGM
29MRN1
11948
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
different facts—in other cases that may
come before the Department.
For the reasons stated, DOE has
issued an Order stating:
(1) Store It Cold must test and rate the
following walk-in cooler refrigeration
system basic models with the alternate
test procedure set forth in paragraph (2):
Basic Model
No.9
Brand
CoolBot
CoolBot
CoolBot
CoolBot
CoolBot
CoolBot
.................................
.................................
.................................
.................................
.................................
.................................
CBLW08
CBLW10
CBLW12
CBLW15
CBLW18
CBLW25
(2) The alternate test procedure for the
Store It Cold basic models listed in
paragraph (1) is the test procedure for
walk-in cooler refrigeration systems
prescribed by DOE at 10 CFR part 431,
subpart R, appendix C,10 except as
detailed below. All other requirements
of 10 CFR part 431, subpart R, appendix
C, and DOE’s regulations remain
applicable.
In 10 CFR part 431, subpart R,
appendix C, section 3.1. General
modifications: Test Conditions and
Tolerances revise sections 3.1.1. and
3.1.4., and add instructions in a new
section 3.1.6. regarding Tables 3 and 4
of AHRI 1250–2009, to read:
3.1.1. In Table 1, Instrumentation
Accuracy, refrigerant temperature
measurements shall have a tolerance of
±0.5 F for unit cooler in/out.
Temperature measurements used to
determine water vapor content of the air
shall be accurate to within ±0.4 F, ±1.0
F for all other temperature
measurements.
3.1.4. In Tables 2 through 14, the Test
Condition Outdoor Wet Bulb
Temperature requirement and its
associated tolerance apply only to units
with evaporative cooling and singlepackaged dedicated systems.
3.1.6. Tables 3 and 4 shall be
modified to read as follows:
TABLE 3—FIXED CAPACITY MATCHED REFRIGERATOR SYSTEM AND SINGLE-PACKAGED DEDICATED SYSTEM, CONDENSING
UNIT LOCATED INDOOR
Test description
Unit cooler air
entering
dry-bulb, °F
Unit cooler air
entering
relative
humidity,
(%)
Condenser air
entering
dry-bulb
(°F)
Condenser air
entering
wet-bulb
(°F)
35
<50
........................
........................
Compressor Off
35
<50
90
1 75, 2 65
Compressor On
Off-cycle Fan
Power.
Refrigeration Capacity.
Compressor
capacity
Test objective
Measure fan input wattage during
compressor off cycle.
Determine Net Refrigeration Capacity of Unit Cooler, input
power, and EER at Rating Condition.
Note:
1. Required only for evaporative Dedicated Condensing Units.
2. Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or
part of the equipment is located in the outdoor room.
TABLE 4—FIXED CAPACITY MATCHED REFRIGERATOR SYSTEM AND SINGLE-PACKAGED DEDICATED SYSTEM, CONDENSING
UNIT LOCATED OUTDOOR
Unit cooler air
entering
dry-bulb
(°F)
Unit cooler air
entering
relative
humidity
(%)
Condenser air
entering
dry-bulb,
(°F)
Condenser air
entering
wet-bulb,
(°F)
Off Cycle Fan
Power.
Refrigeration Capacity A.
35
<50
........................
........................
Compressor Off
35
<50
95
1 75, 2 68
Compressor On
Refrigeration Capacity B.
35
<50
59
1 54, 2 46
Compressor On
Refrigeration Capacity C.
35
<50
35
1 34, 2 29
Compressor On
Test description
Compressor
capacity
Test objective
Measure fan input wattage during
compressor off cycle.
Determine Net Refrigeration Capacity of Unit Cooler, input
power, and EER at Rating Condition.
Determine Net Refrigeration Capacity of Unit Cooler and system
input power at moderate condition.
Determine Net Refrigeration Capacity of Unit Cooler and system
input power at cold condition.
jbell on DSK30RV082PROD with NOTICES
Note:
1. Required only for evaporative Dedicated Condensing Units.
2. Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or
part of the equipment is located in the outdoor room.
9 The Interim Waiver Order applies only to the
walk-in cooler refrigeration system basic models
manufactured by Store It Cold specified in the
petition and Interim Waiver Order. The Interim
Waiver Order does not cover any other walk-in
refrigeration cooler system basic models
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
manufactured by Store It Cold, or any other
manufacturer, even if such basic models use a
°CoolBot® controller.
10 AHRI Standard 1250P (I–P)-2009 (‘‘AHRI 1250–
2009’’) titled ‘‘Standard for Performance Rating of
Walk-in Coolers and Freezers’’ is incorporated by
PO 00000
Frm 00023
Fmt 4703
Sfmt 4703
reference in the federal test procedure at 10 CFR
431.303(b)(2). The alternate test procedure provides
amendments 10 CFR part 431, subpart R, appendix
C that include required modifications to AHRI
1250–2009.
E:\FR\FM\29MRN1.SGM
29MRN1
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
jbell on DSK30RV082PROD with NOTICES
In 10 CFR part 431, subpart R,
appendix C, section 3.2. General
Modifications: Methods of Testing add
the following instructions regarding
additional modifications to appendix C
of AHRI 1250–2009:
3.2.6 In appendix C, section C1.
reads: Purpose. The purpose of this
appendix is to provide a method of
testing for Matched-pair, Singlepackaged Dedicated Systems, as well as
unit coolers and Dedicated Condensing
Units tested alone.
3.2.7 In appendix C, section C5. and
C5.1 read as follows:
3.2.7.1 C5 reads: C5. Methods of
Testing for walk-in cooler and freezer
systems that have matched unit coolers
and condensing units. The testing of the
walk-in cooler and freezer systems
include a steady state test, defrost test
and off-cycle fan power test. For singlepackaged dedicated systems, calculate
the refrigeration capacity and power
consumption using the Indoor Air
Enthalpy test method and the Outdoor
Air Enthalpy test method. The Indoor
Air Enthalpy test method shall be
considered the primary measurement
and used to report capacity. The
Outdoor Air Enthalpy test method shall
be considered the secondary
measurement and used to calculate the
Refrigeration Capacity Heat Balance. See
Section C10 of this appendix for
complete details on each test method.
3.2.7.2 C5.1 reads: The Gross Total
Refrigeration Capacity of Unit Coolers
for matched-pairs (not including singlepackaged dedicated systems) from
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
steady state test shall be determined by
either one of the following methods.
3.2.8 In appendix C, section C7.1
reads: Refer to the standard rating
conditions for a particular application
listed in Section 5 of this standard. Test
acceptance criteria listed in Table 2 in
section 4 of this standard apply to the
Dual Instrumentation and Calibrated
Box methods of test. Single-packaged
dedicated system test tolerances are
listed in each applicable Method of Test
outlined in section C10.
3.2.9 In appendix C, section C7.2
reads: Data that need to be recorded
during the test are listed in Table C2.
For single-packaged dedicated systems
tested in accordance with ASHRAE 37–
2009, data that need to be recorded
during the test are listed in ASHRAE
37–2009.
3.2.10 In appendix C, section C6.
Test Chambers Requirements, add C6.3
to read as follows:
C6.3 For all system constructions
(split systems, single-packaged, Unit
Cooler tested alone, and Dedicated
Condensing Unit tested alone), the Unit
Cooler under test may be used to aid in
achieving the required test chamber
ambient temperatures prior to beginning
any Steady-state test. However, the unit
under test must be free from frost before
initiating any Steady-state testing.
For single-packaged dedicated
systems, refer to the applicable methods
of test for single-packaged dedicated
systems listed in section C10 of this
appendix.
In 10 CFR part 431, subpart R,
appendix C, section 3.3. Matched
PO 00000
Frm 00024
Fmt 4703
Sfmt 4703
11949
systems, single-packaged dedicated
systems, and unit coolers tested alone,
revise the language to read:
3.3 Matched systems, singlepackaged dedicated systems, and unit
coolers tested alone: Use the test
method in AHRI 1250–2009
(incorporated by reference; see
§ 431.303), appendix C as the method of
test for matched refrigeration systems,
single-packaged dedicated systems, or
unit coolers tested alone, with the
modifications listed below in sections
3.3.1 through 3.3.7.2.:
In appendix C of AHRI 1250–2009,
renumber the following sections and
equations, and references to the
following sections and equations, as
follows:
Section C10 to Section C11;
Section C11 to C12;
Section C11.1 to C12.1;
Section C11.1.1 to C12.1.1;
Equation C11 to C12;
Equation C12 to C13;
Section C11.2 to C12.2;
Section C11.3 to C12.3;
Equation C13 to C14;
Equation C14 to C15;
Equation C15 to C16;
Equation C16 to C17;
Section C12 to C13; and
Section C13 to C14.
Insert the following as sections C10
through C10.2.3, and equation C11:
C10. Single-packaged Test Methods
and Allowable Refrigeration Capacity
Heat Balance.
C10.1 Single-packaged Test
Methods.
E:\FR\FM\29MRN1.SGM
29MRN1
Also see the following website for
Figure C3: https://www.regulations.gov/
document?D=EERE-2018-BT-WAV0002-0009.
C10.1.1 Indoor Air Enthalpy
Method. Determine Net Refrigeration
Capacity of Unit Cooler and input
power in accordance with ASHRAE 37–
2009, Figure C3, and the following
modifications.
C10.1.1.1 Space conditioning
capacity is determined by measuring
airflow rate and the dry-bub
temperature and water vapor content of
the air that enters and leaves the coil.
Air enthalpies shall be determined in
accordance with ANSI ASHRAE 41.6.
Entering air is to be sufficiently dry as
to not produce frost on the Unit Cooler
coil. Therefore, only sensible capacity
measured by dry bulb change shall be
used to calculate capacity.
C10.1.1.2 Test Setup for Non-Ducted
Unit Coolers. A single outlet plenum
box shall be constructed in a cubic
arrangement. The length of the longest
dimension of the Unit Cooler outlet
shall be used to determine the
dimension of the cube outlet plenum.
Four static pressure taps shall be
installed in the center of each face. A 6″
inlet plenum skirt shall be installed
with four static pressure taps at each
center face as well. Airflow shall be
adjusted by the exhaust fan on the
airflow plenum to achieve 0.00″WC (±
0.02″WC).
C10.1.2 Outdoor Air Enthalpy
Method. Determine Net Refrigeration
Capacity of Unit Cooler and input
power in accordance with ASHRAE 37–
2009, Figure C3, and the following
modifications.
C10.1.2.1 Outdoor Air Enthalpy is
only applicable on Dedicated
Condensing Units for which the leaving
air can be fully captured. Space
conditioning capacity is determined by
measuring airflow rate and the dry-bub
temperature and water vapor content of
the air that enters and leaves the coil.
Air enthalpies shall be determined in
accordance with ANSI ASHRAE 41.6.
Line loss adjustments in section 7.3.3.4
of ASHRAE 37–2009 are not applicable
to package units.
C10.2 Allowable Refrigeration
Capacity Heat Balance.
C10.2.1 Following the completion of
the Steady-state capacity test, for each
rating condition, the measured net
capacities of the primary and secondary
test methods must balance within 6%,
per Equation C11 11
C10.2.2 If measured net capacities
do not balance per Equation C11,
investigate all potential test facility
leaks and/or non-conformances. If no
leaks or non-conformances are detected,
proceed to Section C10.2.3. If any leaks
or non-conformances are detected,
remedy the concerns and rerun the
Steady-state test at all applicable rating
condition(s). If the measured net
capacities balance per Equation C11,
then the test is considered valid and
capacity and power measurements from
the primary method of the second test
will be used. If the measured net
11 The suggested alternate test procedure in Store
It Cold’s petition for waiver referenced equation
C24. DOE understands this to be an error and that
the appropriate equation to reference is C11.
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00025
Fmt 4703
Sfmt 4703
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.005
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
EN29MR19.004
jbell on DSK30RV082PROD with NOTICES
11950
jbell on DSK30RV082PROD with NOTICES
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
capacities still do not balance per
Equation C11, proceed to Section
C10.2.3
C10.2.3 To achieve a capacity heat
balance, the test lab may modify the
exterior of the unit under test to reduce
leakage and surface losses. Specifically,
the lab may add insulation to the
outside surface of the single-packaged
dedicated system and/or tape and seal
sheet metal edges to minimize outdoor
ambient air intrusion to the Unit Cooler.
After the unit is insulated, rerun the
Steady-state test at all applicable rating
condition(s). If the measured net
capacities balance per Equation C11,
then the lab facility and instrumentation
are verified as complying with the
applicable method of test. However,
capacity, power, and all downstream
calculations will be based on the results
of the primary method from the first
test, which occurred before the unit was
altered. If the measured net capacities
still do not balance per Equation C11,
then the lab facility and instrumentation
are considered non-compliant, must be
remedied, and all prior tests for the unit
under test are considered invalid.
In 10 CFR part 431, subpart R,
appendix C, sections 3.3 through 3.3.7.2
replace references to AHRI–1250–2009
sections C10, C11, C11.1, C11.1.1,
C11.2, and C11.3, with C11, C12, C12.1,
C12.1.1, C12.2, and C12.3, respectively;
and replace references to AHRI–1250–
2009 equations C13 and C14 with
equations C14 and C15, respectively.
(3) Representations. Store It Cold
must make representations about the
energy use, including the refrigeration
capacity (in Btu/h), of basic models
referenced in paragraph (1) for
compliance, marketing, or other
purposes only to the extent that the
basic models have been tested in
accordance with the provisions in the
alternate test procedure and such
representations fairly disclose the
results of such testing.
(4) This interim waiver shall remain
in effect according to the provisions of
10 CFR 431.401(h) and (k).
(5) This interim waiver is issued to
Store It Cold on the condition that the
walk-in cooler refrigeration system’s
performance characteristics, statements,
representations, and documentation
provided by Store It Cold are valid. DOE
may revoke or modify this waiver at any
time if it determines the factual basis
underlying the petition for waiver is
incorrect, or the results from the
alternate test procedure are
unrepresentative of the basic models’
true energy consumption characteristics.
10 CFR 431.401(k)(1). Likewise, Store It
Cold may request that DOE rescind or
modify the interim waiver if Store It
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
Cold discovers an error in the
information provided to DOE as part of
its petition, determines that the interim
waiver is no longer needed, or for other
appropriate reasons. 10 CFR
430.27(k)(2).
(6) Granting of this interim waiver
does not release Store It Cold from the
certification requirements set forth at 10
CFR part 429.
DOE makes decisions on waivers and
interim waivers for only those basic
models specifically set out in the
petition, not future basic models that
may be manufactured by the petitioner.
Store It Cold may submit a new or
amended petition for waiver and request
for grant of interim waiver, as
appropriate, for additional basic models
of walk-in cooler refrigeration systems.
Alternatively, if appropriate, Store It
Cold may request that DOE extend the
scope of a waiver or an interim waiver
to include additional basic models
employing the same technology as the
basic model(s) set forth in the original
petition consistent with 10 CFR
431.401(g).
V. Request for Comments
DOE is publishing Store It Cold’s
petition for waiver in its entirety,
pursuant to 10 CFR 431.401(b)(1)(iv).
The petition includes a suggested
alternate test procedure, as summarized
in section III of this document, to
determine the efficiency of Store It
Cold’s specified walk-in cooler
refrigeration systems. DOE may consider
including the alternate procedure
specified in the Interim Waiver Order,
and specified in section IV of this
document, in a subsequent Decision and
Order.
DOE invites all interested parties to
submit in writing by April 29, 2019,
comments and information on all
aspects of the petition, including the
alternate test procedure. Pursuant to 10
CFR 431.401(d), any person submitting
written comments to DOE must also
send a copy of such comments to the
petitioner. The contact information for
the petitioner is Brian R. Murphy,
brian@storeitcold.com, 3879 Tennyson
St., Denver, CO 80212.
Submitting comments via https://
www.regulations.gov. The https://
www.regulations.gov web page will
require you to provide your name and
contact information. Your contact
information will be viewable to DOE
Building Technologies staff only. Your
contact information will not be publicly
viewable except for your first and last
names, organization name (if any), and
submitter representative name (if any).
If your comment is not processed
properly because of technical
PO 00000
Frm 00026
Fmt 4703
Sfmt 4703
11951
difficulties, DOE will use this
information to contact you. If DOE
cannot read your comment due to
technical difficulties and cannot contact
you for clarification, DOE may not be
able to consider your comment.
However, your contact information
will be publicly viewable if you include
it in the comment or in any documents
attached to your comment. Any
information that you do not want to be
publicly viewable should not be
included in your comment, nor in any
document attached to your comment.
Persons viewing comments will see only
first and last names, organization
names, correspondence containing
comments, and any documents
submitted with the comments.
Do not submit to https://
www.regulations.gov information for
which disclosure is restricted by statute,
such as trade secrets and commercial or
financial information (hereinafter
referred to as Confidential Business
Information (‘‘CBI’’)). Comments
submitted through https://
www.regulations.gov cannot be claimed
as CBI. Comments received through the
website will waive any CBI claims for
the information submitted. For
information on submitting CBI, see the
Confidential Business Information
section.
DOE processes submissions made
through https://www.regulations.gov
before posting. Normally, comments
will be posted within a few days of
being submitted. However, if large
volumes of comments are being
processed simultaneously, your
comment may not be viewable for up to
several weeks. Please keep the comment
tracking number that https://
www.regulations.gov provides after you
have successfully uploaded your
comment.
Submitting comments via email, hand
delivery, or mail. Comments and
documents submitted via email, hand
delivery, or mail also will be posted to
https://www.regulations.gov. If you do
not want your personal contact
information to be publicly viewable, do
not include it in your comment or any
accompanying documents. Instead,
provide your contact information on a
cover letter. Include your first and last
names, email address, telephone
number, and optional mailing address.
The cover letter will not be publicly
viewable as long as it does not include
any comments.
Include contact information each time
you submit comments, data, documents,
and other information to DOE. If you
submit via mail or hand delivery, please
provide all items on a CD, if feasible. It
is not necessary to submit printed
E:\FR\FM\29MRN1.SGM
29MRN1
11952
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
jbell on DSK30RV082PROD with NOTICES
copies. No facsimiles (faxes) will be
accepted.
Comments, data, and other
information submitted to DOE
electronically should be provided in
PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file
format. Provide documents that are not
secured, written in English and free of
any defects or viruses. Documents
should not contain special characters or
any form of encryption and, if possible,
they should carry the electronic
signature of the author.
Campaign form letters. Please submit
campaign form letters by the originating
organization in batches of between 50 to
500 form letters per PDF or as one form
letter with a list of supporters’ names
compiled into one or more PDFs. This
reduces comment processing and
posting time.
Confidential Business Information.
According to 10 CFR 1004.11, any
person submitting information that he
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
or she believes to be confidential and
exempt by law from public disclosure
should submit via email, postal mail, or
hand delivery two well-marked copies:
one copy of the document marked
confidential including all the
information believed to be confidential,
and one copy of the document marked
‘‘non-confidential’’ with the information
believed to be confidential deleted.
Submit these documents via email or on
a CD, if feasible. DOE will make its own
determination about the confidential
status of the information and treat it
according to its determination.
Factors of interest to DOE when
evaluating requests to treat submitted
information as confidential include (1) a
description of the items, (2) whether
and why such items are customarily
treated as confidential within the
industry, (3) whether the information is
generally known by or available from
other sources, (4) whether the
information has previously been made
PO 00000
Frm 00027
Fmt 4703
Sfmt 4703
available to others without obligation
concerning its confidentiality, (5) an
explanation of the competitive injury to
the submitting person which would
result from public disclosure, (6) when
such information might lose its
confidential character due to the
passage of time, and (7) why disclosure
of the information would be contrary to
the public interest.
It is DOE’s policy that all comments
may be included in the public docket,
without change and as received,
including any personal information
provided in the comments (except
information deemed to be exempt from
public disclosure).
Signed in Washington, DC, on March 20,
2019.
Steven Chalk,
Acting Deputy Assistant Secretary for Energy
Efficiency, Energy Efficiency and Renewable
Energy.
BILLING CODE 6450–01–P
E:\FR\FM\29MRN1.SGM
29MRN1
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
11953
Store It Cold, LLC
3879 Tennyson St., Denver, CO 80212
Tel 720-456-1178
May 16,2018
VIA E-MAIL: AS_Waiver_Requests@ee.doe.gov
Lucy deButts
U.S. Department ofEnergy Building
Technologies Program Test Procedure
Waiver
1000 Independence Avenue, SW Mails top
EE-5B
Washington, DC 20585-0121
I.
RE: Petition for Waiver and Application for Interim Waiver of the requirement
to measure the refrigerant enthalpy change and refrigerant mass flow rate for certain
Store It Cold LLC °Coo1Bot® Walk-In Cooler refrigeration systems incorporating
Room Air Conditioning (RAC) window units
Dear Ms. deButts:
Pursuant to 10 C.F .R. § 431.401, Store It Cold LLC respectfully submits this petition for waiver, and
application for interim waiver, of the requirements in Appendix C of the test procedure set forth in AHRT
1250-2009 (incorporated by reference; see §431.303(2)) for Walk-In Coolers and Freezers (WICF) with
single-package dedicated refrigeration systems, found at Section 3.3 of Appendix C to Subpart R of 10 C.F.R.
Part 431, that specify measurement of the refrigerant enthalpy change and the refrigerant mass flow rate to
determine the Gross Total Refrigeration Capacity of the system. Specifically, Store It Cold LLC seeks to
waive the 'refrigerant-side' measurement requirements for its °Coo1Bot® Walk-In Cooler refrigeration
systems incorporating Room Air Conditioning (RAC) window units, because testing these systems with
refrigerant mass flow meters installed, produces results unrepresentative of their true energy consumption
characteristics, and would provide materially inaccurate comparative data. As explained below, Store It Cold
LLC requests that in lieu of 'refrigerant-side' measurements, it be permitted to use psychrometric 'air-side'
measurements to determine the Gross Total Refrigeration Capacity of these system.
I.
Store It Cold LLC
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00028
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.006
jbell on DSK30RV082PROD with NOTICES
Store It Cold LLC manufactures the oCoolBot® controller which when combined with a window air
conditioner becomes an energy efficient oCoolBot® Walk-In Cooler refrigeration system. ocoolBot® Walk-In
11954
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
Cooler refrigeration systems are intended as refrigeration systems for both indoor and outdoor walk-in cooler
applications. Where traditional walk-in coolers utilize large compressors, large surface area coils, multiple fans,
and large volumes of refrigerant, the CoolBot's patented technology intelligently controls a much smaller
window air conditioner to maintain desired temperatures.
II.
Background
Sections C5.1.1 and C5.1.2 in Appendix C of the test procedure set forth in AHRI 1250- 2009,
specify that the refrigeration capacity shall be determined by measuring the enthalpy change and mass flow
rate of the refrigerant. The result of this type of determination method is commonly termed 'refrigerant-side'
gross capacity, and is represented in AHRI 1250-2009 by the following equation:
'Refrigerant-Side' Gross Capacity Qrer= ffiref
(hout- hin)
where
Qrer= Refrigerant-side gross capacity, Btu/h firer=
Refrigerant mass flow rate, lb/h
hout =Refrigerant enthalpy leaving evaporator, Btu/lb hin =
Refrigerant enthalpy entering evaporator, Btu/lb
Similarly, refrigeration capacity can be determined by measuring the enthalpy change and mass flow
rate of the air being conditioned. The result of this type of determination method is commonly termed 'airside' gross capacity, and can be represented by the following equation:
'Air-Side' Gross Capacity Qair = ffiair
(hairout - hairin) where
Qair =Air-side gross capacity, Btu/h
ffiair =Mass flow rate of air circulated, lb/h
hairout =Enthalpy of air and water vapor mixture leaving evaporator, Btu/lb hairin =Enthalpy
of air and water vapor mixture entering evaporator, Btu/lb
III.
Basic Models for Which Waiver Is Requested
Store It Cold LLC requests a waiver from the 'refrigerant-side' measurement requirements for its
°Coo1Bot® Walk-In Cooler refrigeration systems incorporating RAC window units. Specifically, Store It
Cold LLC requests a waiver for all basic models listed in the table below by brand name and model
number:
~~o.~ts~~~~~~!~~~~-t~r\R~t~it{e~~~~:~i'~~~~aet,~~~~~ ~.::'·~·
· · · · •. · · ·· .·
··· · · . ·· ·· · \JI.nf1dow Unit Specifications
·
•·
·.•.,•..:.:·;,
.~~·.·
·
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00029
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.007
jbell on DSK30RV082PROD with NOTICES
d. M0· d 1 ;eru
.·c·EER • EER ;~nergy .Qehumid. R f . ·· Oey Air
El t . 1R t·
Brand :Moc.fel •8.
;
.i · ran •
e .Rating
Star :{Pts/Hr)
e ng. Flow (CFM)
ec nca a 109
CooiBot .CBlJNO!F LG LVV80**E~;8,o0o
12.0 12.1 (Yes
:2.2
R32 ··
2:20
115VAC,60Hz,62A;660Watts
caoiBot csLiiv1o LG · LVV10**ER 1o,ooo 12.o 12.1 ,Yes
2.7
·· ·· 11SVAC~6orii,7.7A;82bwatts ·
·cooiBot .csCvv1:2 LG ivvi2**ER•12,ooo
'3.8
•115vA.c,66Hz,9.3A;99bvvatts
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
.
CooiBot CBLW18, LG
1.9/
!Yes
19
'c 00 IB 0 t CBLW25' LG :LW25**E.Rl24,000/ 10·31 10·31 .y..
·
Q4 500 10.3 110.3 · es
'
•
·
l
I
;
11955
4.9
1?.?
'
°Coo1Bot® Walk-In Cooler Refrigeration System Model Matrix
Also see the following website for Table-Model Matrix:
IV.
Grounds for Test Procedure Waiver
DOE's regulations provide for granting of a test procedure waiver where testing of the basic model
according to the prescribed test procedures would "evaluate the basic model in a manner so unrepresentative
of its true energy ... consumption characteristics as to provide materially inaccurate comparative data." Store
It Cold LLC seeks a waiver from the 'refrigerant- side' measurement requirements for its °Coo1Bot® WalkIn Cooler refrigeration systems incorporating RAC window units, because the prescribed installation of
refrigerant mass flow meters, on these systems, so greatly affects the flow of refrigerant that the resulting
measurements and calculated capacities become untrustworthy and unrepresentative of their true
performance capabilities.
In August of 2017, Intertek Testing Services NA, Inc., a globally recognized and nationally accredited
energy efficiency testing resource, at the request of Store It Cold LLC, attempted to conduct baseline
performance evaluations on two °Coo1Bot® Walk-In Cooler refrigeration systems, in accordance with the
test procedure set forth in AHRI 1250-2009. All test equipment, used for these tests, was in calibration and is
traceable to National Institute of Standards and Technology (NIST) standards. As explained below, in both
cases, the introduction of refrigerant mass flow meters significantly impacted the internal refrigeration
system volumes and resulted in inconsistent refrigerant mass flow rate measurements and lower than
expected capacities.
Figure 1 - Refrigerant-Side Measuring Devices Installed for Attempted AHRI 1250-2009 Testing
See the following website for Figure 1: https://www.regulations.gov/document?D=EERE-2018-BT-WAV0002-0007.
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00030
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.008
jbell on DSK30RV082PROD with NOTICES
The steady state capacity tests, prescribed in AHRI 1250-2009, for fixed capacity matched
refrigerator systems, with outdoor condensing units, were attempted on a model CBLWlO 10,000 BTU unit
and a model CBLW15 15,000 BTU unit. Coriolis CMF025 flow meters were installed along with the other
required 'refrigerant-side' measuring devices and approximately 25ft of additional V4" copper tubing (see
Figure 1). When these refrigeration systems were evacuated and recharged, the corresponding increases in
internal refrigeration system volume, required approximately twice the amount of refrigerant as was present
from the factory. These attempted AHRI 1250-2009 tests resulted in the inconsistent refrigerant mass flow
rates and lower than expected capacities shown in Table I below:
11956
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
Fixed Capacity Matched Single-Package Refrigerator System
Store It Cold,LLC
11\ll!itqQ'IV,qnlt,,;
jyiQ~Ir,tum~r!
Wi~~?W·~nlt ..
~erlitt Numbe~::
CBLW10
CBLW15
LW1016ER
LW1516ER
702TAGHDY631
~ll~eit}i~~E!st~
6NPKG064611TAPEFC520
10.76
-0.32
25.65
2871.0
97.65
65.83
115.94
10271.5
~J)a!+~y-~t~~~:
$$• fi9f!;i4 (9 P}
124.03
15.39
173.5
15897.1
74.24
73.87
74.68
8846.1
C';!lpa~ifY~l"~~~§~S5J:~4{~Ft .
32.19
31.64
37.75
7690.3
70.35
58.32
72.2
9160.3
~ ~ 9517:'~\(":'FJ
Table 1 -Flow Rates & Capacities Resulting from 'Refrigerant-Side' Measurement Tests
Also see the following website for Table 1: https:l/www.regulations.gov/document?D=EERE-2018-BT-WAV0002-00JO.
In November of 2017, Intertek attempted to conduct baseline performance evaluations on two
additional °Coo1Bot® Walk-In Cooler refrigeration systems, in accordance with the test procedure set forth in
AHRI 1250-2009, using psychrometric 'air-side' measurements to determine the capacities. The steady state
capacity, prescribed in AHRI 1250-2009, for fixed capacity matched refrigerator systems, with outdoor
condensing units, were attempted on a model CBLW08 8,000 BTU unit and a model CBLW25 24,500 BTU
unit. These attempted AHRI
1250-2009 tests resulted in the much more consistent measurements and more accurate capacities shown in
Table 2 below:
i•> '• -~. ·. · · · •· . : )• :'. :-:.• ,. · . . . . t~Oif~s!ilrrp(fqtP
Um"'tToype:
~~~QQ-~!tr:r\E!;;
• . • .. • •• ·• ,, :• ~\ . . • ;; •
.•.. ,(,· i.. . \''
• • ·'":. •'·• " " , :· ... ·.·.·•· •\ <
Fixed Capacity Matched Single-Package Refrigerator System
.Y
.
Store It Cold,LLC
CBLW25
LW2516ER
~i'I'Jd~~hit_
$~~~~~ "Nillll.b!!i:(.
702TARUCW398
701TAULAD206
R32
I
31.7 oz
31.7 oz
•.. ·.·.·
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
297.3
PO 00000
Frm 00031
5073.0
Fmt 4703
681.3
Sfmt 4725
679.6
E:\FR\FM\29MRN1.SGM
682.9
29MRN1
17581.6
EN29MR19.009
jbell on DSK30RV082PROD with NOTICES
296.6
.•< .·•·•
11957
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
~ll~¢it\rBTe~:
13$:~$$/s.J.~~F} •.
~<'~~aC\tY~~e$t':
~~ ~~5/~•("F)•• •
298.2
297.9
298.6
6134.2
711.4
704.3
714.4
20265.0
297.7
297.2
298.0
6975.7
710.4
708.4
712.3
21678.1
Figure 2 - Flow Rates & Capacities Resulting from 'Air-Side' Measurement Tests
V-
Also see the following website for Table 2:
V.
Alternative Test Procedures
DOE's Appendix C to Subpart R of 10 C.F .R. Part 431, as currently promulgated but with the option
ofusing psychrometric 'air-side' measurements to determine the Gross Total Refrigeration Capacity of
systems incorporating RAC units, constitutes the appropriate alternate test procedure that will provide
materially accurate comparative data and allow evaluation of the performance of Store It Cold LLC's
°Coo1Bot® Walk-In Cooler refrigeration systems incorporating RAC window units in a manner
representative of their true energy characteristics. Therefore, Store It Cold LLC proposes to test the basic
models for which it seeks a waiver by applying the entirety of Appendix C to Subpart R of 10 C.P.R. Part
431, with the following additions/modifications to it and the test procedure set forth in AHRI 1250-2009:
Appendix C to Subpart R of 10 C.F.R. Part 431 Modifications
REVISE THE FOLLOWING SECTIONS
3 .1.1. In Table 1, Instrumentation Accuracy, refrigerant temperature measurements shall have a tolerance
of ±0.5 F for unit cooler in/out. Temperature measurements used to determine water vapor content of the
air shall be accurate to within ±0.4 F, ±1.0 F for all other temperature measurements.
3 .1.4. In Tables 2 through 14, the Test Condition Outdoor Wet Bulb Temperature requirement and its
associated tolerance apply only to units with evaporative cooling and Single-packaged Systems.
AHRI 1250-2009 Modifications
INCLUDE THE FOLLOWING ADDITIONAL DEFINITIONS
1. Dedicated Condensing Unit. A specific combination of Refrigeration System components for a given
refrigerant, consisting of an assembly that
(1) Includes one or more electric motor driven positive displacement compressors,
condensers, and accessories as provided by the manufacturer; and
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00032
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.010
jbell on DSK30RV082PROD with NOTICES
(2) Is designed to serve one refrigerated load.
11958
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
2. Refrigeration System. The mechanism (including all controls and other components integral to the
system's operation) used to create the refrigerated environment in the interior of a walk-in cooler or walk-in
freezer, consisting of:
A Dedicated Condensing Unit; or
A Unit Cooler.
2.1 Matched Refrigeration System (Matched-pair). A combination of a Dedicated Condensing Unit
and one or more Unit Coolers specified by the Dedicated Condensing Unit manufacturer which
are all distributed in commerce together. Single-Packaged Dedicated Systems are a subset of
Matched Refrigeration Systems.
2.2 Single-packaged Refrigeration System (Single-packaged). A Matched Refrigeration System that is a
Single-packaged assembly that includes one or more compressors, a condenser, a means for forced
circulation of refrigerated air, and elements by which heat is transferred from air to refrigerant,
without any element external to the system imposing resistance to flow of the refrigerated air.
REVISE THE FOLLOWING SECTIONS AND TABLES
C 1. Purpose. The purpose of this appendix is to provide a method of testing for Matched-pair, Singlepackaged walk-in Refrigeration Systems, as well as unit coolers and Dedicated Condensing Units tested
alone.
C5.1 The Gross Total Refrigeration Capacity of Unit Coolers for matched-pairs (not including Singlepackaged Systems) from steady state test shall be determined by either one of the following methods.
C7 .1 Refer to the standard rating conditions for a particular application listed in Section 5 of this standard.
Test acceptance criteria listed in Table 2 in section 4 of this standard apply to the Dual Instrumentation and
Calibrated Box methods of test. Single-package dedicated system test tolerances are listed in each
applicable Method of Test outlined in section C 10.
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00033
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.011
jbell on DSK30RV082PROD with NOTICES
C7.2 Data that need to be recorded during the test are listed in Table C2. For Single-package dedicated
systems tested in accordance with ASHRAE 37-2009, data that need to be recorded during the test are listed
in ASHRAE 37-2009.
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
11959
Table 3. Fixed Capacity Matched Refrigerator System, Condensing Unit Located Indoor
Also see the following website for Table 3: https:l/www.regulations.gov/document?D=EERE-2018-BT-WAV0002-00JJ.
Table 3. Fixed Capacity Matched Refrigerator System, Condensing Unit Located Indoor
Test Description
Unit
[Unit
Cooler
Cooler
lAir
lAir
Entering !Entering
Dry!Relative
bulb, 'F IHumidity,
Condenser
Air
Entering
Dry-bulb,
'F
Condenser
~ir
Entering
Compressor
Capacity
Test
Objective
Compressor
Off
Measure fan
input
~et-bulb,
'F
%
Off-cycle Fan Power
-
<50
35
-
~attage
Refrigeration Capacity
<50
35
90
75 1, 65 2
Compressor
On
during
compressor
off cycle
!Determine
~et
!Refrigeration
Capacity of
!Unit Cooler,
input power,
andEER at
!Rating
Condition
Note:
1.
Required only for evaporative Dedicated Condensing Units.
2. Maximum allowable value for Single-packaged Systems that do not usc evaporative Dedicated
Condensing Units, where all or part of the equipment is located in the outdoor room.
Table 4. Fixed Capacity Matched Refrigerator System, Condensing Unit Located Outdoor
Also see the following website for Table 4:
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00034
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.012
jbell on DSK30RV082PROD with NOTICES
()002-()(} 12.
11960
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
Table 4. Fixed Capacity Matched Refrigerator System, Condensing Unit Located Outdoor
Test Description
Unit
Cooler
Air
Entering
Drybulb, OF
[Unit
Cooler
~ir
!Entering
!Relative
IHumidity,
Condenser
~ir
!Entering
!Dry-bulb,
OF
Condenser
~ir
Entering
Compressor
Capacity
Test
Objective
Compressor
Off
!Measure fan
input
~et-bulb,
OF
%
35
Pff Cycle Fan Power
<50
~attage
!Refrigeration Capacity A
35
<50
95
75 1, 68 2
Compressor
On
!Refrigeration Capacity B
35
<50
59
54 1, 46 2
Compressor
On
!Refrigeration Capacity C
35
<50
35
34 1, 29 2
Compressor
On
during
compressor
off cycle
!Determine
~et
!Refrigeration
Capacity of
!Unit Cooler,
input power,
andEER at
!Rating
Condition
!Determine
~et
!Refrigeration
Capacity of
!Unit Cooler
and system
input power
at moderate
condition
!Determine
~et
!Refrigeration
Capacity of
!Unit Cooler
and system
input power
at cold
condition
~ote:
1.
Required only for evaporative Dedicated Condensing Units.
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00035
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.013
jbell on DSK30RV082PROD with NOTICES
2. Maximum allowable value for Single-packaged Systems that do not use evaporative Dedicated
Condensing Units, where all or part of the equipment is located in the outdoorroom.
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
11961
INSERT THE FOLLOWING ADDITIONAL SECTION BEFORE C5.2 AND RE-NUMBER REMAINING
SECTIONS
C5.2 For Single-packaged Systems, calculate the refrigeration capacity and power consumption using the
Indoor Air Enthalpy test method and the Outdoor Air Enthalpy test method. The Indoor Air Enthalpy test
method shall be considered the primary measurement and used to report capacity. The Outdoor Air Enthalpy
test method shall be considered the secondary measurement and used to calculate the Refrigeration Capacity
Heat Balance. See Section C 10 of this appendix for complete details on each test method.
INSERT THE FOLLOWING ADDITIONAL SECTION BEFORE C6.1 & RE-NUMBER REMAINING
SECTIONS
C6.1 For all system constructions (split systems, Single-packaged, Unit Cooler tested alone, and Dedicated
Condensing Unit tested alone), the Unit Cooler under test may be used to aid in achieving the required test
chamber ambient temperatures prior to beginning any Steady-state test. However, the unit under test must
free from frost before initiating any Steady-state testing.
INSERT THE FOLLOWING ADDITIONAL SECTION
C6.4 For Single-package Systems, refer to the applicable methods of test for Single-package systems
listed in section C 10 of this appendix.
ADD THE FOLLOWING ADDITIONAL FIGURE
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00036
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.014
jbell on DSK30RV082PROD with NOTICES
Figure C3 -Air Enthalpy Method
11962
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
Also see the following website for Figure C3: https://www.regulations.gov/document?D=EERE-2018-BTWAV-0002-0009.
INSERT THE FOLLOWING ADDITIONAL SECTIONS BEFORE C10 AND THE INCLUDEDEQUATION
BEFORE C11 & RE-NUMBER REMAINING SECTIONS AND EQUATIONS
C 10. Single-packaged Test Methods and Allowable Refrigeration Capacity Heat Balance.
C 10.1 Single-packaged Test Method<;.
C10.1.11ndoor Air Enthalpy Method. Determine Net Refrigeration Capacity of Unit Cooler and input
power in accordance with ASHRAE 37-2009, Figure C3, and the following modifications.
C 10.1.1.1 Space conditioning capacity is determined by measuring airflow rate and the dry-bub temperature
and water vapor content of the air that enters and leaves the coil. Air enthalpies shall be determined in
accordance with ANSI ASHRAE 41.6. Entering air is to be sufficiently dry as to not produce frost on the Unit
Cooler coil. Therefore, only sensible capacity measured by dry bulb change shall be used to calculate
capacity.
C10.1.1.2 Test Setup for Non-Ducted Unit Coolers. A single outlet plenum box shall be constructed in a
cubic arrangement. The length of the longest dimension of the Unit Cooler outlet shall be used to determine
the dimension of the cube outlet plenum. Four static pressure taps shall be installed in the center of each face.
A 6" inlet plenum skirt shall be installed with four static pressure taps at each center face as well. Airflow
shall be adjusted by the exhaust fan on the airflow plenum to achieve O.OO"WC (± 0.02"WC).
C 10.1.2 Outdoor Air Enthalpy Method. Determine Net Refrigeration Capacity of Unit Cooler and input power in
accordance with ASHRAE 37-2009, Figure C3, and the following modifications.
C 10.1.2.1 Outdoor Air Enthalpy is only applicable on Dedicated Condensing Units for which the leaving air
can be fully captured. Space conditioning capacity is determined by measuring airflow rate and the dry-bub
[sic] temperature and water vapor content of the air that enters and leaves the coil. Air enthalpies shall be
determined in accordance with ANSI ASHRAE 41.6. Line loss adjustments in section 7.3.3.4 of ASHRAE 372009 are not applicable to package units.
C10.2 Allowable Refrigeration Capacity Heat Balance.
C10.2.1 Following the completion of the Steady-state capacity test, for each rating condition, the measured
net capacities of the primary and secondary test methods must balance within 6%, per Equation C24
X
100% :::;: 6%
Cll
jbell on DSK30RV082PROD with NOTICES
Qnet,primary
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00037
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.015
_ 6 % :S: Qnet,pri~ary-Qnet,secondary
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
11963
C 10.2.2 If measured net capacities do not balance per Equation C 11, investigate all potential test facility leaks
and/or non-conformances. If no leaks or non-confonnances are detected, proceed to Section C 10.2.3. If any
leaks or non-conformances are detected, remedy the concerns and rerun the Steady-state test at all applicable
rating condition(s). If the measured net capacities balance per Equation C 11, then the test is considered valid
and capacity and power measurements from the primary method of the second test will be used. If the
measured net capacities still do not balance per Equation Cll, proceed to Section C 10.2.3
C 10.2.3 To achieve a capacity heat balance, the test lab may modify the exterior of the unit under test to
reduce leakage and surface losses. Specifically, the lab may add insulation to the outside surface of the Singlepackage system and/or tape and seal sheet metal edges to minimize outdoor ambient air intrusion to the Unit
Cooler. After the unit is insulated, rerun the Steady-state test at all applicable rating condition(s). If the
measured net capacities balance per Equation C11, then the
lab facility and instrumentation are verified as complying with the applicable method of test. However,
capacity, power, and all downstream calculations will be based on the results of the primary method from the
first test, which occurred before the unit was altered. If the measured net capacities still do not balance per
Equation C 11, then the lab facility and instrumentation are considered non-compliant, must be remedied, and
all prior tests for the unit under test are considered invalid.
Note: Certain content phrasing and figures provided courtesy of The Air-Conditioning, Heating, and
Refrigeration Institute (AHRI).
VI.
Similar Products
Store It Cold LLC is not aware of any other manufacturers offering Walk-In Cooler
refrigeration systems comprised ofRAC window units and proprietary controllers.
VII.
Petition for Interim Waiver
Pursuant to 10 CFR § 431.401, Store It Cold LLC also requests an interim waiver of the 'refrigerantside' measurement requirements for its °Coo1Bot® Walk-In Cooler refrigeration systems incorporating RAC
window units. DOE will grant an interim waiver if it appears likely that the petition for waiver will be granted
and/or if DOE determines that it would be desirable for public policy reasons to grant immediate relief
pending a determination on the petition for waiver (10 CFR § 431.401(e)(2)). Interim relief is important to
ensure that Store It Cold LLC can make materially accurate representations about the energy efficiency of its
°Coo1Bot® Walk-In Cooler refrigeration systems in its certifications to the DOE and marketing materials
while DOE is considering the merits of Store It Cold LLC' s petition for waiver.
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00038
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.016
jbell on DSK30RV082PROD with NOTICES
Basic Models for Which Interim Waiver Is Requested: Store It Cold LLC requests an interim waiver for all
basic models listed in the table below by brand name and model number:
11964
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
~~~~s~~,~~•~2014
17:48 Mar 28, 2019
Jkt 247001
PO 00000
Frm 00039
Fmt 4703
Sfmt 4725
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.017
jbell on DSK30RV082PROD with NOTICES
For all of these reasons, the Department should grant an interim waiver while it considers the petition
for waiver set out above.
[FR Doc. 2019–06100 Filed 3–28–19; 8:45 am]
BILLING CODE 6450–01–C
DEPARTMENT OF ENERGY
Federal Energy Regulatory
Commission
jbell on DSK30RV082PROD with NOTICES
Combined Notice of Filings #1
Take notice that the Commission
received the following electric corporate
filings:
Docket Numbers: EC19–69–000.
Applicants: Coolidge Power LLC.
Description: Application for
Authorization Under Section 203 of the
Federal Power Act, et al. of Coolidge
Power LLC.
Filed Date: 3/22/19.
Accession Number: 20190322–5214.
Comments Due: 5 p.m. ET 4/12/19.
Take notice that the Commission
received the following exempt
wholesale generator filings:
Docket Numbers: EG19–82–000.
Applicants: 225DD 8me LLC.
Description: Self-Certification of EWG
Status of 225DD 8me LLC.
Filed Date: 3/25/19.
Accession Number: 20190325–5113.
Comments Due: 5 p.m. ET 4/15/19.
Take notice that the Commission
received the following electric rate
filings:
Docket Numbers: ER10–1107–006.
Applicants: Pacific Gas and Electric
Company.
Description: Supplement to December
19, 2018 Updated Market Power
Analysis for the CAISO BAA Market of
Pacific Gas and Electric Company.
Filed Date: 3/22/19.
Accession Number: 20190322–5222.
VerDate Sep<11>2014
17:48 Mar 28, 2019
Jkt 247001
Comments Due: 5 p.m. ET 4/12/19.
Docket Numbers: ER19–1423–000.
Applicants: Virginia Electric and
Power Company, PJM Interconnection,
L.L.C.
Description: § 205(d) Rate Filing:
Dominion submits 4 WDSAs, Service
Agreement Nos. 5229, 5301, 5302, 5303
to be effective 12/1/2017.
Filed Date: 3/22/19.
Accession Number: 20190322–5167.
Comments Due: 5 p.m. ET 4/12/19.
Docket Numbers: ER19–1424–000.
Applicants: Langdon Wind, LLC.
Description: Tariff Cancellation:
Langdon Wind, LLC Notice of
Cancellation of Market-Based Rate Tariff
to be effective 3/23/2019.
Filed Date: 3/22/19.
Accession Number: 20190322–5179.
Comments Due: 5 p.m. ET 4/12/19.
Docket Numbers: ER19–1425–000.
Applicants: Midcontinent
Independent System Operator, Inc.
Description: § 205(d) Rate Filing:
2019–03–25_SA 3284 Hankinson
Wahpeton 230 kV Line MPFCA (J460
J488 J493 J526) to be effective 3/26/
2019.
Filed Date: 3/25/19.
Accession Number: 20190325–5066.
Comments Due: 5 p.m. ET 4/15/19.
Docket Numbers: ER19–1426–000.
Applicants: ITC Midwest LLC.
Description: Tariff Cancellation:
Cancellation of Corn Belt Joint Use
Agreements to be effective 3/11/2019.
Filed Date: 3/25/19.
Accession Number: 20190325–5069.
Comments Due: 5 p.m. ET 4/15/19.
Docket Numbers: ER19–1428–000.
Applicants: ISO New England Inc.
Description: § 205(d) Rate Filing: ISO–
NE; Inventoried Energy Program to be
effective 5/28/2019.
PO 00000
Frm 00040
Fmt 4703
Sfmt 4703
11965
Filed Date: 3/25/19.
Accession Number: 20190325–5091.
Comments Due: 5 p.m. ET 4/15/19.
Docket Numbers: ER19–1429–000.
Applicants: Midcontinent
Independent System Operator, Inc.
Description: § 205(d) Rate Filing:
2019–03–25_SA 3285 Big Stone
Terminal Upgrade MPFCA (J488 J493
J526) to be effective 3/26/2019.
Filed Date: 3/25/19.
Accession Number: 20190325–5093.
Comments Due: 5 p.m. ET 4/15/19.
Docket Numbers: ER19–1430–000.
Applicants: PJM Interconnection,
L.L.C.
Description: § 205(d) Rate Filing: First
Revised ISA, SA No. 2530; Queue No.
U4–014/AC1–087 to be effective 2/21/
2019.
Filed Date: 3/25/19.
Accession Number: 20190325–5150.
Comments Due: 5 p.m. ET 4/15/19.
Docket Numbers: ER19–1431–000.
Applicants: Columbia Energy LLC.
Description: § 205(d) Rate Filing:
Market-Based Rate Tariff Revisions to be
effective 3/26/2019.
Filed Date: 3/25/19.
Accession Number: 20190325–5158.
Comments Due: 5 p.m. ET 4/15/19.
Docket Numbers: ER19–1432–000.
Applicants: Midcontinent
Independent System Operator, Inc.
Description: § 205(d) Rate Filing:
2019–03–25_SA 3286 Blair Terminal
Equip and Disconnects MPFCA (J488
J493 J526) to be effective 3/26/2019.
Filed Date: 3/25/19.
Accession Number: 20190325–5159.
Comments Due: 5 p.m. ET 4/15/19.
Docket Numbers: ER19–1433–000.
Applicants: LifeEnergy, LLC.
Description: § 205(d) Rate Filing:
Market-Based Rate Tariff Revisions to be
effective 3/26/2019.
E:\FR\FM\29MRN1.SGM
29MRN1
EN29MR19.018
Federal Register / Vol. 84, No. 61 / Friday, March 29, 2019 / Notices
Agencies
[Federal Register Volume 84, Number 61 (Friday, March 29, 2019)]
[Notices]
[Pages 11944-11965]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2019-06100]
-----------------------------------------------------------------------
DEPARTMENT OF ENERGY
[Case Number 2018-002; EERE-2018-BT-WAV-0002]
Energy Conservation Program: Notice of Petition for Waiver of
Store It Cold From the Department of Energy Walk-In Cooler
Refrigeration System Test Procedure, and Notice of Grant of Interim
Waiver
AGENCY: Office of Energy Efficiency and Renewable Energy, Department of
Energy.
ACTION: Notice of petition for waiver, notice of grant of an interim
waiver, and request for comments.
-----------------------------------------------------------------------
SUMMARY: The U.S. Department of Energy (``DOE'') announces receipt of
and publishes a petition for waiver from Store It Cold, which seeks a
waiver from the test procedure used for determining the efficiency of
walk-in cooler refrigeration system basic models. Store It Cold seeks
to use an alternate test procedure to address issues involved in
testing certain basic models identified in its petition. Store It Cold
asserts in its petition that for the specified [deg]CoolBot[supreg]
Walk-In Cooler refrigeration system basic models taking ``refrigerant-
side'' measurements with refrigerant mass flow meters yields results
that are unrepresentative of the basic models' true energy consumption
characteristics and provides materially inaccurate comparative data.
Accordingly, Store It Cold seeks to test and rate the basic models
identified in its petition using its recommended alternate test
procedure, in which the refrigeration capacity is measured using
psychrometric ``air-side'' measurements. This document announces that
DOE is granting Store It Cold with an interim waiver from DOE's walk-in
cooler refrigeration system test procedure for the specified basic
models, subject to use of the alternate test procedure as set forth in
the Interim Waiver Order. DOE solicits comments, data, and information
concerning Store It Cold's petition and its suggested alternate test
procedure to inform its final decision on Store It Cold's waiver
request.
DATES: DOE will accept comments, data, and information with respect to
the Store It Cold petition until April 29, 2019.
ADDRESSES: Interested persons are encouraged to submit comments using
the Federal eRulemaking Portal at https://www.regulations.gov.
Alternatively, interested persons may submit comments, identified by
case number ``2018-002,'' and Docket number ``EERE-2018-BT-WAV-0002,''
by any of the following methods:
Federal eRulemaking Portal: https://www.regulations.gov.
Follow the instructions for submitting comments.
E-mail: [email protected]. Include the
case number [Case No. 2018-002] in the subject line of the message.
Postal Mail: Appliance and Equipment Standards Program,
U.S. Department of Energy, Office of Energy Efficiency and Renewable
Energy, Building Technologies Office, Mailstop EE-5B, Petition for
Waiver Case No.
[[Page 11945]]
2018-002, 1000 Independence Avenue SW, Washington, DC 20585-0121. If
possible, please submit all items on a compact disc (``CD''), in which
case it is not necessary to include printed copies.
Hand Delivery/Courier: Appliance and Equipment Standards
Program, U.S. Department of Energy, Building Technologies Office, 950
L'Enfant Plaza SW, Room 6055, Washington, DC, 20024. If possible,
please submit all items on a compact disc (``CD''), in which case it is
not necessary to include printed copies.
No telefacsimilies (faxes) will be accepted. For detailed
instructions on submitting comments and additional information on this
process, see section V of this document.
Docket: The docket, which includes Federal Register notices,
comments, and other supporting documents/materials, is available for
review at https://www.regulations.gov. All documents in the docket are
listed in the https://www.regulations.gov index. However, some documents
listed in the index, such as those containing information that is
exempt from public disclosure, may not be publicly available.
The docket web page can be found at https://www.regulations.gov/docket?D=EERE-2018-BT-WAV-0002. The docket web page contains simple
instruction on how to access all documents, including public comments,
in the docket. See section V for information on how to submit comments
through https://www.regulations.gov.
FOR FURTHER INFORMATION CONTACT: Ms. Lucy deButts, U.S. Department of
Energy, Building Technologies Office, Mailstop EE-5B, 1000 Independence
Avenue SW, Washington, DC 20585-0121. E-mail:
[email protected].
Mr. Michael Kido, U.S. Department of Energy, Office of the General
Counsel, Mail Stop GC-33, Forrestal Building, 1000 Independence Avenue
SW, Washington, DC 20585-0103. Telephone: (202) 586-8145. Email:
[email protected].
SUPPLEMENTARY INFORMATION:
I. Background and Authority
The Energy Policy and Conservation Act of 1975, as amended,
(``EPCA'') \1\ (42 U.S.C. 6291-6317), among other things, authorizes
DOE to regulate the energy efficiency of a number of consumer products
and industrial equipment. Title III, Part C \2\ of EPCA established the
Energy Conservation Program for Certain Industrial Equipment, which
sets forth a variety of provisions designed to improve energy
efficiency for certain types of industrial equipment. This equipment
includes walk-in cooler refrigeration systems, the focus of this
document. (42 U.S.C. 6311(1)(G)) A walk-in cooler and freezer is
defined under DOE's regulations as ``an enclosed storage space
refrigerated to temperatures, respectively, above, and at or below 32
degrees Fahrenheit that can be walked into, and has a total chilled
storage area of less than 3,000 square feet; however[,] the terms do
not include products designed and marketed exclusively for medical,
scientific, or research purposes.'' 10 CFR 431.302. See also 42 U.S.C.
6311(20) (statutory definition for ``walk-in cooler, walk-in
freezer'').
---------------------------------------------------------------------------
\1\ All references to EPCA in this document refer to the statute
as amended through America's Water Infrastructure Act of 2018,
Public Law 115-270 (October 23, 2018).
\2\ For editorial reasons, upon codification in the U.S. Code,
Part C was re-designated as Part A-1.
---------------------------------------------------------------------------
Under EPCA, DOE's energy conservation program consists essentially
of four parts: (1) Testing, (2) labeling, (3) Federal energy
conservation standards, and (4) certification and enforcement
procedures. Relevant provisions of EPCA include definitions (42 U.S.C.
6311), energy conservation standards (42 U.S.C. 6313), test procedures
(42 U.S.C. 6314), labeling provisions (42 U.S.C. 6315), and the
authority to require information and reports from manufacturers (42
U.S.C. 6316).
The Federal testing requirements consist of test procedures that
manufacturers of covered equipment must use as the basis for: (1)
Certifying to DOE that their equipment complies with the applicable
energy conservation standards adopted pursuant to EPCA (42 U.S.C.
6316(a); 42 U.S.C. 6295(s)), and (2) making representations about the
efficiency of that equipment (42 U.S.C. 6314(d)). Similarly, DOE must
use these test procedures to determine whether the equipment complies
with relevant standards promulgated under EPCA. (42 U.S.C. 6316(a); 42
U.S.C. 6295(s))
Under 42 U.S.C. 6314, EPCA sets forth the criteria and procedures
DOE is required to follow when prescribing or amending test procedures
for covered products/equipment. EPCA requires that any test procedures
prescribed or amended under this section must be reasonably designed to
produce test results which reflect the energy efficiency, energy use or
estimated annual operating cost of a covered product/covered equipment
during a representative average use cycle and requires that test
procedures not be unduly burdensome to conduct. (42 U.S.C. 6314(a)(2))
The test procedure used to determine the net capacity and Annual Walk-
in Energy Factor (``AWEF'') of walk-in cooler refrigeration systems is
contained in the Code of Federal Regulations (``CFR'') at 10 CFR part
431, subpart R, appendix C.
Under 10 CFR 431.401, any interested person may submit a petition
for waiver from DOE's test procedure requirements. DOE will grant a
waiver from the test procedure requirements if DOE determines either
that the basic model for which the waiver was requested contains a
design characteristic that prevents testing of the basic model
according to the prescribed test procedures, or that the prescribed
test procedures evaluate the basic model in a manner so
unrepresentative of its true energy consumption characteristics as to
provide materially inaccurate comparative data. 10 CFR 431.401(f)(2). A
petitioner must include in its petition any alternate test procedures
known to the petitioner to evaluate the basic model in a manner
representative of its energy consumption characteristics. 10 CFR
431.401(b)(1)(iii).
DOE may grant the waiver subject to conditions, including adherence
to alternate test procedures. 10 CFR 431.401(f)(2). As soon as
practicable after the granting of any waiver, DOE will publish in the
Federal Register a notice of proposed rulemaking to amend its
regulations so as to eliminate any need for the continuation of such
waiver. 10 CFR 431.401(l). As soon thereafter as practicable, DOE will
publish in the Federal Register a final rule. Id.
The waiver process also provides that DOE may grant an interim
waiver if it appears likely that the underlying petition for waiver
will be granted and/or if DOE determines that it would be desirable for
public policy reasons to grant immediate relief pending a determination
on the underlying petition for waiver. 10 CFR 431.401(e)(2). Within one
year of issuance of an interim waiver, DOE will either: (i) Publish in
the Federal Register a determination on the petition for waiver; or
(ii) publish in the Federal Register a new or amended test procedure
that addresses the issues presented in the waiver. 10 CFR
431.401(h)(1).
When DOE amends the test procedure to address the issues presented
in a waiver, the waiver will automatically terminate on the date on
which use of that test procedure is required to demonstrate compliance.
10 CFR 431.401(h)(2).
[[Page 11946]]
II. Store It Cold's Petition for Waiver and Application for Interim
Waiver
On March 9, 2018, Store It Cold filed a petition for waiver and a
petition for interim waiver from the test procedure applicable to walk-
in cooler refrigeration systems set forth in 10 CFR part 431, subpart
R, appendix C, and in response to DOE requests for technical
clarification, Store It Cold submitted a revised petition for waiver
and petition for interim waiver on May 16, 2018. (Store It Cold, No. 1
at pp. 1-7 \3\) AHRI Standard 1250P (I-P)-2009 titled ``Standard for
Performance Rating of Walk-in Coolers and Freezers'' (``AHRI 1250-
2009'') is incorporated by reference in the test procedure for walk-in
cooler refrigeration systems with the modifications enumerated in 10
CFR part 431, subpart R, appendix C. Referencing AHRI 1250-2009, 10 CFR
part 431, subpart R, appendix C provides two possible methods for
measuring the refrigeration capacity of single-package systems,\4\ the
DX Dual Instrumentation method and the DX Calibrated Box method (see
section C5.1 through C5.1.2 of AHRI 1250-2009). For both methods, the
refrigeration capacity is determined by measuring the enthalpy change
and mass flow rate of the refrigerant (``Refrigerant Enthalpy
Method'').
---------------------------------------------------------------------------
\3\ A notation in this form provides a reference for information
that is in the docket for this test procedure waiver (Docket No.
EERE-2018-BT-WAV-0002) (available at https://www.regulations.gov/docket?D=EERE-2018-BT-WAV-0002). This notation indicates that the
statement preceding the reference is document number 1 in the docket
and appears at pages 1-7 of that document.
\4\ ``Single-packaged dedicated system'' means a refrigeration
system (as defined in 10 CFR 431.302) that is a single-package
assembly that includes one or more compressors, a condenser, a means
for forced circulation of refrigerated air, and elements by which
heat is transferred from air to refrigerant, without any element
external to the system imposing resistance to flow of the
refrigerated air. 10 CFR 431.302.
---------------------------------------------------------------------------
Store It Cold's petition for waiver and interim waiver lists walk-
in cooler refrigeration system basic models CBLW08, CBLW10, CBLW12,
CBLW15, CBLW18, CBLW25), which it states are single-package dedicated
refrigeration systems. These walk-in refrigeration system basic models
are comprised of a controller (i.e., the [deg]CoolBot[supreg]
controller) and a room air conditioner (``RAC''), which as combined
form a walk-in refrigeration system. Store It Cold stated in its
petition that the resulting walk-in refrigeration systems are
designated for both indoor and outdoor use. According to Store It
Cold's petition, the CoolBot's technology controls a much smaller air
conditioner designed to be installed in a window to maintain desired
temperatures, as opposed to a traditional walk-in cooler that would
utilize large compressors, large surface area coils, multiple fans, and
large volumes of refrigerant to do the same.\5\
---------------------------------------------------------------------------
\5\ Store It Cold notes in its product specification sheets,
that the [deg]CoolBot[supreg] controller is also distributed in
commerce separately, i.e., not as part of a walk-in cooler
refrigeration system. This notice of waiver and notice of grant of
an interim waiver apply only to the walk-in cooler refrigeration
system basic models identified by Store It Cold, i.e., the specific
models listed in the Interim Waiver order, which contain
[deg]CoolBot[supreg] controllers integrated by Store It Cold with
the specified RAC models.
---------------------------------------------------------------------------
Store It Cold asserts in its petition that, for the basic models
listed in its petition, the Refrigerant Enthalpy Method (referred to as
the ``refrigerant-side'' gross capacity method by Store It Cold) yields
inconsistent refrigerant mass flow rates and lower than expected
capacities. Store It Cold explains in its petition that the
installation of the refrigerant mass flow meters used under this method
significantly increased the refrigerant circuit's internal volume,
requiring the system to be charged with approximately twice the amount
of refrigerant as was present from the factory. As a result, Store It
Cold contends that the capacities calculated with this method are
untrustworthy and unrepresentative of the equipment's true performance
capabilities.
In its suggested alternate test procedure, Store It Cold proposes
instead to use an ``air-side'' method in which the refrigeration
capacity is determined by measuring the enthalpy change and mass flow
rate of the air passing through the evaporator side (i.e., Indoor Air
Enthalpy Method) and condenser side (i.e., Outdoor Air Enthalpy
Method). The condenser side measurement is adjusted by subtracting the
system input power to determine refrigeration capacity. In its
petition, Store It Cold presents ``refrigerant-side'' and ``air-side''
capacity test results, asserting that the latter yields more consistent
measurements and accurate capacities for the basic models assessed. As
outlined in the petition, in August of 2017, Intertek Testing Services,
NA, Inc., at the request of Store It Cold, attempted to conduct
baseline performance evaluations on two of the basic models listed in
their petition (CBLW10 and CBLW15) using the DX Dual Instrumentation
method,\6\ as prescribed by AHRI 1250-2009 for fixed-capacity single-
package walk-in cooler refrigeration systems with outdoor condensing
units. In November of 2017, Intertek then attempted to conduct baseline
performance evaluations on two different basic models listed in their
petition (CBLW08 and CBLW25) in accordance with the test procedure set
forth in the AHRI 1250-2009, except that the units' refrigeration
capacities were determined using the psychrometric ``air-side'' method
proposed in its alternate test procedure. Store It Cold presents the
test results in Table 1 and Figure 2 of its petition, which show that
the ``refrigerant-side'' method required charging the unit to
approximately twice the factory refrigerant charge because of the
additional tubing needed to accommodate the flow meters required by the
test procedure. Store It Cold presented data for basic models CBLW08
and CBLW25 at all three of the required capacity test conditions
specified in AHRI 1250-2009 for walk-in cooler refrigeration systems
with condensing units located outdoors. All three conditions require
the same evaporator inlet air temperature but specify progressively
decreasing condenser inlet dry-bulb air temperatures: 95 [deg]F for the
A test condition, 59 [deg]F for the B test condition, and 35 [deg]F for
the C test condition. For the CBLW10 basic model, the net capacity
increases from 2,871 Btu/hr in test condition A to 15,897 Btu/hr in
condition B and then decreases to 7,690 Btu/hr in condition C.
Conversely, for the CBLW15 basic model, the net capacity decreases from
10,271 Btu/hr in condition A to 8,846 Btu/hr in condition B and then
increases to 9,160 Btu/hr in condition C.
---------------------------------------------------------------------------
\6\ The DX Dual Instrumentation method is the ``refrigerant-
side'' method discussed above (i.e. Refrigerant Enthalpy Method) but
with duplicate sensors for all measurements. This approach minimizes
the risk of measurement error due to equipment inaccuracy.
---------------------------------------------------------------------------
Store It Cold also presented data from the ``air-side'' test
performed on two basic models, CBLW08 and CBLW25. For the CBLW08 basic
model, the net capacity increases from 5,073 Btu/hr in test condition A
to 6,134 Btu/hr in condition B and then increases to 6,976 Btu/hr in
condition C. For the CBLW25 basic model, the net capacity increases
from 17,582 Btu/hr in condition A to 20,265 Btu/hr in condition B and
then increases to 21,678 Btu/hr in condition C.
Store It Cold asserted that the proposed ``air-side'' method yields
more accurate results for the basic models listed in its petition and
thus that the alternate test procedure offered in its petition
alleviates the issues identified with the current procedure.
Store It Cold also requests an interim waiver from the existing DOE
test procedure. DOE will grant an interim waiver if it appears likely
that the petition for waiver will be granted, and/or if DOE determines
that it would be
[[Page 11947]]
desirable for public policy reasons to grant immediate relief pending a
determination of the petition for waiver. See 10 CFR 431.401(e)(2).
DOE understands that, absent an interim waiver, the specified basic
models cannot be tested and rated for energy consumption on a basis
representative of their true energy characteristics. As presented in
Store It Cold's petition, the subject basic models of walk-in cooler
refrigeration systems are smaller than the typical walk-in cooler
refrigeration systems. Because of the smaller size and configuration of
the specified [deg]CoolBot[supreg] Walk-In Cooler refrigeration
systems, installation of the refrigerant mass flow meters as specified
in the DOE test procedure significantly impacts the internal
refrigeration system volumes and results in inconsistent refrigerant
mass flow rate measurements and lower than expected capacities.
III. Requested Alternate Test Procedure
EPCA requires that manufacturers use DOE test procedures when
making representations about the energy consumption and energy
consumption costs of products covered by the statute. (42 U.S.C.
6314(d)) Consistent representations are important for manufacturers to
use in making representations about the energy efficiency of their
products or equipment and to demonstrate compliance with applicable DOE
energy conservation standards. Pursuant to its regulations at 10 CFR
431.401 applying to waivers and interim waivers from applicable test
procedures, and after consideration of public comments on the petition,
DOE will consider setting an alternate test procedure for the equipment
identified by Store It Cold in a subsequent Decision and Order.
Store It Cold seeks to use an alternate test procedure to test and
rate specific walk-in cooler refrigeration system basic models. Store
It Cold suggested that the specified basic models be tested according
to the test procedure in 10 CFR part 431, subpart R, appendix C, except
that instead of using the Refrigerant Enthalpy Method to determine
capacity, the specified basic units be tested using the Indoor Air
Enthalpy and Outdoor Air Enthalpy test methods to determine capacity.
IV. Summary of Grant of an Interim Waiver
DOE has reviewed Store It Cold's application for an interim waiver,
the alternate test procedure requested by Store It Cold, the company's
testing and performance data, product characteristics, and product
specification sheets published online by Store It Cold. All materials
reviewed by DOE can be found in the docket.\7\ The test photo provided
by Store It Cold shows that the refrigerant tubing exiting the unit has
multiple bends in it without any extended straight sections upstream
and downstream of the refrigerant mass flow meters, which could have
affected the accuracy of the mass flow measurements during testing.
Additionally, Store It Cold stated that the refrigerant tubing as
configured increased the refrigerant circuit's internal volume,
requiring the system to be charged with approximately twice the amount
of refrigerant as was present from the factory.
---------------------------------------------------------------------------
\7\ The docket is available at https://www.regulations.gov/docket?D=EERE-2018-BT-WAV-0002.
---------------------------------------------------------------------------
For refrigeration systems in general, it is expected that the
capacity of the system would monotonically increase as the condenser
air temperature decreases (until further increases are limited by
refrigerant mass flow restriction of the expansion device for the lower
condensing pressures that would occur for lower condenser air
temperatures). This is because the cooler condenser air temperature can
further cool the refrigerant such that it leaves the condenser at lower
temperature and enthalpy,\8\ and similarly enters the evaporator at
lower enthalpy. This increases the amount of heat the refrigerant
absorbs from the refrigerated space as it flows through the evaporator
coil, increasing the capacity of the evaporator. DOE notes that the
``refrigerant-side'' method test data in Store It Cold's petition do
not follow this trend. Instead, as discussed in section II, the
measured capacity increases and decreases as condenser air temperature
decreases, with opposite trends for the tests of basic model CBLW10 as
compared with CBLW15. These inconsistent results suggest that the
capacity measurements are not accurate. The mass flow measurements may
not be accurate due to the non-optimal test setup of the refrigerant
lines conducting the refrigerant to and from the mass flow meters.
Conversely, the data from testing using the ``air side'' method follows
the expected trend, showing increasing refrigeration capacity as
condenser air temperature decreases for both tested units. This gives
much greater confidence that the measurements are accurate. ``Air
side'' capacity measurements are well established for measurement of
the capacity of air conditioners (e.g. as described in American Society
of Heating and Air-Conditioning Engineers (``ASHRAE'') Standard 37-
2009, ``Methods of Testing for Rating Electrically Driven Unitary Air-
Conditioning and Heat Pump Equipment'', which is incorporated by
reference into the requested alternate test procedure), and the
principles of air-conditioner capacity measurement apply equally to the
capacity measurement for refrigeration systems.
---------------------------------------------------------------------------
\8\ Enthalpy is a measure of refrigerant energy per unit mass--
the evaporator capacity (not accounting for evaporator fan heat) is
equal to refrigerant mass flow multiplied by its enthalpy increase.
---------------------------------------------------------------------------
Therefore, DOE initially agrees that, for the basic models listed
in Store It Cold's petition, the current test procedure produces
results unrepresentative of their true energy consumption
characteristics and provides materially inaccurate comparative data.
Alternatively, DOE notes that the ``air-side'' method suggested in
Store It Cold's petition does not require installation of a refrigerant
mass flow meter or any alteration of the test unit's refrigerant
charge. Further, DOE finds that the test data for the proposed ``air-
side'' method is consistent with the performance expected for
refrigeration systems (i.e. refrigeration capacity varies inversely
with condenser air temperature).
Based on this review, the alternate test procedure appears to allow
for the accurate measurement of the of efficiency of this equipment,
while alleviating the testing problems associated with Store It Cold's
implementation of walk-in cooler refrigeration systems testing for the
basic models specified in its petition. Consequently, it appears likely
that Store It Cold's petition for waiver will be granted. Furthermore,
DOE has determined that it is desirable for public policy reasons to
grant Store It Cold immediate relief pending a determination of the
petition for waiver.
DOE recognizes that Store It Cold's refrigeration system, which is
based primarily on an off-the-shelf room air conditioner coupled with
its CoolBot controller, is an unconventional one compared to most other
walk-in refrigeration systems. The Agency acknowledges, however, that
Store It Cold identifies this equipment in its petition as a ``single-
package[d] dedicated system'' used to refrigerate walk-in units and
also offers this equipment as part of a complete walk-in kit. See
https://www.storeitcold.com/coolbot-walk-in-cooler/. DOE notes that its
decision to grant Store It Cold with an interim waiver in this case is
limited to the specific facts presented in this particular matter and
does not necessarily reflect how DOE would view similar equipment--but
involving
[[Page 11948]]
different facts--in other cases that may come before the Department.
For the reasons stated, DOE has issued an Order stating:
(1) Store It Cold must test and rate the following walk-in cooler
refrigeration system basic models with the alternate test procedure set
forth in paragraph (2):
------------------------------------------------------------------------
Brand Basic Model No.\9\
------------------------------------------------------------------------
CoolBot................................. CBLW08
CoolBot................................. CBLW10
CoolBot................................. CBLW12
CoolBot................................. CBLW15
CoolBot................................. CBLW18
CoolBot................................. CBLW25
------------------------------------------------------------------------
(2) The alternate test procedure for the Store It Cold basic models
listed in paragraph (1) is the test procedure for walk-in cooler
refrigeration systems prescribed by DOE at 10 CFR part 431, subpart R,
appendix C,\10\ except as detailed below. All other requirements of 10
CFR part 431, subpart R, appendix C, and DOE's regulations remain
applicable.
---------------------------------------------------------------------------
\9\ The Interim Waiver Order applies only to the walk-in cooler
refrigeration system basic models manufactured by Store It Cold
specified in the petition and Interim Waiver Order. The Interim
Waiver Order does not cover any other walk-in refrigeration cooler
system basic models manufactured by Store It Cold, or any other
manufacturer, even if such basic models use a [deg]CoolBot[supreg]
controller.
\10\ AHRI Standard 1250P (I-P)-2009 (``AHRI 1250-2009'') titled
``Standard for Performance Rating of Walk-in Coolers and Freezers''
is incorporated by reference in the federal test procedure at 10 CFR
431.303(b)(2). The alternate test procedure provides amendments 10
CFR part 431, subpart R, appendix C that include required
modifications to AHRI 1250-2009.
---------------------------------------------------------------------------
In 10 CFR part 431, subpart R, appendix C, section 3.1. General
modifications: Test Conditions and Tolerances revise sections 3.1.1.
and 3.1.4., and add instructions in a new section 3.1.6. regarding
Tables 3 and 4 of AHRI 1250-2009, to read:
3.1.1. In Table 1, Instrumentation Accuracy, refrigerant
temperature measurements shall have a tolerance of 0.5 F
for unit cooler in/out. Temperature measurements used to determine
water vapor content of the air shall be accurate to within 0.4 F, 1.0 F for all other temperature measurements.
3.1.4. In Tables 2 through 14, the Test Condition Outdoor Wet Bulb
Temperature requirement and its associated tolerance apply only to
units with evaporative cooling and single-packaged dedicated systems.
3.1.6. Tables 3 and 4 shall be modified to read as follows:
Table 3--Fixed Capacity Matched Refrigerator System and Single-Packaged Dedicated System, Condensing Unit Located Indoor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit cooler Unit cooler
air entering air entering Condenser air Condenser air
Test description dry-bulb, relative entering dry- entering wet- Compressor capacity Test objective
[deg]F humidity, (%) bulb ([deg]F) bulb ([deg]F)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off-cycle Fan Power................ 35 <50 .............. .............. Compressor Off........ Measure fan input wattage
during compressor off
cycle.
Refrigeration Capacity............. 35 <50 90 \1\ 75, \2\ 65 Compressor On......... Determine Net Refrigeration
Capacity of Unit Cooler,
input power, and EER at
Rating Condition.
--------------------------------------------------------------------------------------------------------------------------------------------------------
Note:
1. Required only for evaporative Dedicated Condensing Units.
2. Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or part of the
equipment is located in the outdoor room.
Table 4--Fixed Capacity Matched Refrigerator System and Single-Packaged Dedicated System, Condensing Unit Located Outdoor
--------------------------------------------------------------------------------------------------------------------------------------------------------
Unit cooler Unit cooler
air entering air entering Condenser air Condenser air
Test description dry-bulb relative entering dry- entering wet- Compressor capacity Test objective
([deg]F) humidity (%) bulb, ([deg]F) bulb, ([deg]F)
--------------------------------------------------------------------------------------------------------------------------------------------------------
Off Cycle Fan Power................ 35 <50 .............. .............. Compressor Off........ Measure fan input wattage
during compressor off
cycle.
Refrigeration Capacity A........... 35 <50 95 \1\ 75, \2\ 68 Compressor On......... Determine Net Refrigeration
Capacity of Unit Cooler,
input power, and EER at
Rating Condition.
Refrigeration Capacity B........... 35 <50 59 \1\ 54, \2\ 46 Compressor On......... Determine Net Refrigeration
Capacity of Unit Cooler
and system input power at
moderate condition.
Refrigeration Capacity C........... 35 <50 35 \1\ 34, \2\ 29 Compressor On......... Determine Net Refrigeration
Capacity of Unit Cooler
and system input power at
cold condition.
--------------------------------------------------------------------------------------------------------------------------------------------------------
Note:
1. Required only for evaporative Dedicated Condensing Units.
2. Maximum allowable value for Single-Packaged Dedicated Systems that do not use evaporative Dedicated Condensing Units, where all or part of the
equipment is located in the outdoor room.
[[Page 11949]]
In 10 CFR part 431, subpart R, appendix C, section 3.2. General
Modifications: Methods of Testing add the following instructions
regarding additional modifications to appendix C of AHRI 1250-2009:
3.2.6 In appendix C, section C1. reads: Purpose. The purpose of
this appendix is to provide a method of testing for Matched-pair,
Single-packaged Dedicated Systems, as well as unit coolers and
Dedicated Condensing Units tested alone.
3.2.7 In appendix C, section C5. and C5.1 read as follows:
3.2.7.1 C5 reads: C5. Methods of Testing for walk-in cooler and
freezer systems that have matched unit coolers and condensing units.
The testing of the walk-in cooler and freezer systems include a steady
state test, defrost test and off-cycle fan power test. For single-
packaged dedicated systems, calculate the refrigeration capacity and
power consumption using the Indoor Air Enthalpy test method and the
Outdoor Air Enthalpy test method. The Indoor Air Enthalpy test method
shall be considered the primary measurement and used to report
capacity. The Outdoor Air Enthalpy test method shall be considered the
secondary measurement and used to calculate the Refrigeration Capacity
Heat Balance. See Section C10 of this appendix for complete details on
each test method.
3.2.7.2 C5.1 reads: The Gross Total Refrigeration Capacity of Unit
Coolers for matched-pairs (not including single-packaged dedicated
systems) from steady state test shall be determined by either one of
the following methods.
3.2.8 In appendix C, section C7.1 reads: Refer to the standard
rating conditions for a particular application listed in Section 5 of
this standard. Test acceptance criteria listed in Table 2 in section 4
of this standard apply to the Dual Instrumentation and Calibrated Box
methods of test. Single-packaged dedicated system test tolerances are
listed in each applicable Method of Test outlined in section C10.
3.2.9 In appendix C, section C7.2 reads: Data that need to be
recorded during the test are listed in Table C2. For single-packaged
dedicated systems tested in accordance with ASHRAE 37-2009, data that
need to be recorded during the test are listed in ASHRAE 37-2009.
3.2.10 In appendix C, section C6. Test Chambers Requirements, add
C6.3 to read as follows:
C6.3 For all system constructions (split systems, single-packaged,
Unit Cooler tested alone, and Dedicated Condensing Unit tested alone),
the Unit Cooler under test may be used to aid in achieving the required
test chamber ambient temperatures prior to beginning any Steady-state
test. However, the unit under test must be free from frost before
initiating any Steady-state testing.
For single-packaged dedicated systems, refer to the applicable
methods of test for single-packaged dedicated systems listed in section
C10 of this appendix.
In 10 CFR part 431, subpart R, appendix C, section 3.3. Matched
systems, single-packaged dedicated systems, and unit coolers tested
alone, revise the language to read:
3.3 Matched systems, single-packaged dedicated systems, and unit
coolers tested alone: Use the test method in AHRI 1250-2009
(incorporated by reference; see Sec. 431.303), appendix C as the
method of test for matched refrigeration systems, single-packaged
dedicated systems, or unit coolers tested alone, with the modifications
listed below in sections 3.3.1 through 3.3.7.2.:
In appendix C of AHRI 1250-2009, renumber the following sections
and equations, and references to the following sections and equations,
as follows:
Section C10 to Section C11;
Section C11 to C12;
Section C11.1 to C12.1;
Section C11.1.1 to C12.1.1;
Equation C11 to C12;
Equation C12 to C13;
Section C11.2 to C12.2;
Section C11.3 to C12.3;
Equation C13 to C14;
Equation C14 to C15;
Equation C15 to C16;
Equation C16 to C17;
Section C12 to C13; and
Section C13 to C14.
Insert the following as sections C10 through C10.2.3, and equation
C11:
C10. Single-packaged Test Methods and Allowable Refrigeration
Capacity Heat Balance.
C10.1 Single-packaged Test Methods.
[[Page 11950]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.004
Also see the following website for Figure C3: https://www.regulations.gov/document?D=EERE-2018-BT-WAV-0002-0009.
C10.1.1 Indoor Air Enthalpy Method. Determine Net Refrigeration
Capacity of Unit Cooler and input power in accordance with ASHRAE 37-
2009, Figure C3, and the following modifications.
C10.1.1.1 Space conditioning capacity is determined by measuring
airflow rate and the dry-bub temperature and water vapor content of the
air that enters and leaves the coil. Air enthalpies shall be determined
in accordance with ANSI ASHRAE 41.6. Entering air is to be sufficiently
dry as to not produce frost on the Unit Cooler coil. Therefore, only
sensible capacity measured by dry bulb change shall be used to
calculate capacity.
C10.1.1.2 Test Setup for Non-Ducted Unit Coolers. A single outlet
plenum box shall be constructed in a cubic arrangement. The length of
the longest dimension of the Unit Cooler outlet shall be used to
determine the dimension of the cube outlet plenum. Four static pressure
taps shall be installed in the center of each face. A 6'' inlet plenum
skirt shall be installed with four static pressure taps at each center
face as well. Airflow shall be adjusted by the exhaust fan on the
airflow plenum to achieve 0.00''WC ( 0.02''WC).
C10.1.2 Outdoor Air Enthalpy Method. Determine Net Refrigeration
Capacity of Unit Cooler and input power in accordance with ASHRAE 37-
2009, Figure C3, and the following modifications.
C10.1.2.1 Outdoor Air Enthalpy is only applicable on Dedicated
Condensing Units for which the leaving air can be fully captured. Space
conditioning capacity is determined by measuring airflow rate and the
dry-bub temperature and water vapor content of the air that enters and
leaves the coil. Air enthalpies shall be determined in accordance with
ANSI ASHRAE 41.6. Line loss adjustments in section 7.3.3.4 of ASHRAE
37-2009 are not applicable to package units.
C10.2 Allowable Refrigeration Capacity Heat Balance.
C10.2.1 Following the completion of the Steady-state capacity test,
for each rating condition, the measured net capacities of the primary
and secondary test methods must balance within 6%, per Equation C11
\11\
---------------------------------------------------------------------------
\11\ The suggested alternate test procedure in Store It Cold's
petition for waiver referenced equation C24. DOE understands this to
be an error and that the appropriate equation to reference is C11.
[GRAPHIC] [TIFF OMITTED] TN29MR19.005
C10.2.2 If measured net capacities do not balance per Equation C11,
investigate all potential test facility leaks and/or non-conformances.
If no leaks or non-conformances are detected, proceed to Section
C10.2.3. If any leaks or non-conformances are detected, remedy the
concerns and rerun the Steady-state test at all applicable rating
condition(s). If the measured net capacities balance per Equation C11,
then the test is considered valid and capacity and power measurements
from the primary method of the second test will be used. If the
measured net
[[Page 11951]]
capacities still do not balance per Equation C11, proceed to Section
C10.2.3
C10.2.3 To achieve a capacity heat balance, the test lab may modify
the exterior of the unit under test to reduce leakage and surface
losses. Specifically, the lab may add insulation to the outside surface
of the single-packaged dedicated system and/or tape and seal sheet
metal edges to minimize outdoor ambient air intrusion to the Unit
Cooler. After the unit is insulated, rerun the Steady-state test at all
applicable rating condition(s). If the measured net capacities balance
per Equation C11, then the lab facility and instrumentation are
verified as complying with the applicable method of test. However,
capacity, power, and all downstream calculations will be based on the
results of the primary method from the first test, which occurred
before the unit was altered. If the measured net capacities still do
not balance per Equation C11, then the lab facility and instrumentation
are considered non-compliant, must be remedied, and all prior tests for
the unit under test are considered invalid.
In 10 CFR part 431, subpart R, appendix C, sections 3.3 through
3.3.7.2 replace references to AHRI-1250-2009 sections C10, C11, C11.1,
C11.1.1, C11.2, and C11.3, with C11, C12, C12.1, C12.1.1, C12.2, and
C12.3, respectively; and replace references to AHRI-1250-2009 equations
C13 and C14 with equations C14 and C15, respectively.
(3) Representations. Store It Cold must make representations about
the energy use, including the refrigeration capacity (in Btu/h), of
basic models referenced in paragraph (1) for compliance, marketing, or
other purposes only to the extent that the basic models have been
tested in accordance with the provisions in the alternate test
procedure and such representations fairly disclose the results of such
testing.
(4) This interim waiver shall remain in effect according to the
provisions of 10 CFR 431.401(h) and (k).
(5) This interim waiver is issued to Store It Cold on the condition
that the walk-in cooler refrigeration system's performance
characteristics, statements, representations, and documentation
provided by Store It Cold are valid. DOE may revoke or modify this
waiver at any time if it determines the factual basis underlying the
petition for waiver is incorrect, or the results from the alternate
test procedure are unrepresentative of the basic models' true energy
consumption characteristics. 10 CFR 431.401(k)(1). Likewise, Store It
Cold may request that DOE rescind or modify the interim waiver if Store
It Cold discovers an error in the information provided to DOE as part
of its petition, determines that the interim waiver is no longer
needed, or for other appropriate reasons. 10 CFR 430.27(k)(2).
(6) Granting of this interim waiver does not release Store It Cold
from the certification requirements set forth at 10 CFR part 429.
DOE makes decisions on waivers and interim waivers for only those
basic models specifically set out in the petition, not future basic
models that may be manufactured by the petitioner. Store It Cold may
submit a new or amended petition for waiver and request for grant of
interim waiver, as appropriate, for additional basic models of walk-in
cooler refrigeration systems. Alternatively, if appropriate, Store It
Cold may request that DOE extend the scope of a waiver or an interim
waiver to include additional basic models employing the same technology
as the basic model(s) set forth in the original petition consistent
with 10 CFR 431.401(g).
V. Request for Comments
DOE is publishing Store It Cold's petition for waiver in its
entirety, pursuant to 10 CFR 431.401(b)(1)(iv). The petition includes a
suggested alternate test procedure, as summarized in section III of
this document, to determine the efficiency of Store It Cold's specified
walk-in cooler refrigeration systems. DOE may consider including the
alternate procedure specified in the Interim Waiver Order, and
specified in section IV of this document, in a subsequent Decision and
Order.
DOE invites all interested parties to submit in writing by April
29, 2019, comments and information on all aspects of the petition,
including the alternate test procedure. Pursuant to 10 CFR 431.401(d),
any person submitting written comments to DOE must also send a copy of
such comments to the petitioner. The contact information for the
petitioner is Brian R. Murphy, [email protected], 3879 Tennyson
St., Denver, CO 80212.
Submitting comments via https://www.regulations.gov. The https://www.regulations.gov web page will require you to provide your name and
contact information. Your contact information will be viewable to DOE
Building Technologies staff only. Your contact information will not be
publicly viewable except for your first and last names, organization
name (if any), and submitter representative name (if any). If your
comment is not processed properly because of technical difficulties,
DOE will use this information to contact you. If DOE cannot read your
comment due to technical difficulties and cannot contact you for
clarification, DOE may not be able to consider your comment.
However, your contact information will be publicly viewable if you
include it in the comment or in any documents attached to your comment.
Any information that you do not want to be publicly viewable should not
be included in your comment, nor in any document attached to your
comment. Persons viewing comments will see only first and last names,
organization names, correspondence containing comments, and any
documents submitted with the comments.
Do not submit to https://www.regulations.gov information for which
disclosure is restricted by statute, such as trade secrets and
commercial or financial information (hereinafter referred to as
Confidential Business Information (``CBI'')). Comments submitted
through https://www.regulations.gov cannot be claimed as CBI. Comments
received through the website will waive any CBI claims for the
information submitted. For information on submitting CBI, see the
Confidential Business Information section.
DOE processes submissions made through https://www.regulations.gov
before posting. Normally, comments will be posted within a few days of
being submitted. However, if large volumes of comments are being
processed simultaneously, your comment may not be viewable for up to
several weeks. Please keep the comment tracking number that https://www.regulations.gov provides after you have successfully uploaded your
comment.
Submitting comments via email, hand delivery, or mail. Comments and
documents submitted via email, hand delivery, or mail also will be
posted to https://www.regulations.gov. If you do not want your personal
contact information to be publicly viewable, do not include it in your
comment or any accompanying documents. Instead, provide your contact
information on a cover letter. Include your first and last names, email
address, telephone number, and optional mailing address. The cover
letter will not be publicly viewable as long as it does not include any
comments.
Include contact information each time you submit comments, data,
documents, and other information to DOE. If you submit via mail or hand
delivery, please provide all items on a CD, if feasible. It is not
necessary to submit printed
[[Page 11952]]
copies. No facsimiles (faxes) will be accepted.
Comments, data, and other information submitted to DOE
electronically should be provided in PDF (preferred), Microsoft Word or
Excel, WordPerfect, or text (ASCII) file format. Provide documents that
are not secured, written in English and free of any defects or viruses.
Documents should not contain special characters or any form of
encryption and, if possible, they should carry the electronic signature
of the author.
Campaign form letters. Please submit campaign form letters by the
originating organization in batches of between 50 to 500 form letters
per PDF or as one form letter with a list of supporters' names compiled
into one or more PDFs. This reduces comment processing and posting
time.
Confidential Business Information. According to 10 CFR 1004.11, any
person submitting information that he or she believes to be
confidential and exempt by law from public disclosure should submit via
email, postal mail, or hand delivery two well-marked copies: one copy
of the document marked confidential including all the information
believed to be confidential, and one copy of the document marked ``non-
confidential'' with the information believed to be confidential
deleted. Submit these documents via email or on a CD, if feasible. DOE
will make its own determination about the confidential status of the
information and treat it according to its determination.
Factors of interest to DOE when evaluating requests to treat
submitted information as confidential include (1) a description of the
items, (2) whether and why such items are customarily treated as
confidential within the industry, (3) whether the information is
generally known by or available from other sources, (4) whether the
information has previously been made available to others without
obligation concerning its confidentiality, (5) an explanation of the
competitive injury to the submitting person which would result from
public disclosure, (6) when such information might lose its
confidential character due to the passage of time, and (7) why
disclosure of the information would be contrary to the public interest.
It is DOE's policy that all comments may be included in the public
docket, without change and as received, including any personal
information provided in the comments (except information deemed to be
exempt from public disclosure).
Signed in Washington, DC, on March 20, 2019.
Steven Chalk,
Acting Deputy Assistant Secretary for Energy Efficiency, Energy
Efficiency and Renewable Energy.
BILLING CODE 6450-01-P
[[Page 11953]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.006
[[Page 11954]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.007
[[Page 11955]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.008
[[Page 11956]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.009
[[Page 11957]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.010
[[Page 11958]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.011
[[Page 11959]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.012
[[Page 11960]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.013
[[Page 11961]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.014
[[Page 11962]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.015
[[Page 11963]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.016
[[Page 11964]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.017
[[Page 11965]]
[GRAPHIC] [TIFF OMITTED] TN29MR19.018
[FR Doc. 2019-06100 Filed 3-28-19; 8:45 am]
BILLING CODE 6450-01-C