Download as PDF 29144 Federal Register / Vol. 83, No. 121 / Friday, June 22, 2018 / Notices Dated: June 18, 2018. Yoon Ferguson, Agency Clearance Officer, Office of Workers’ Compensation Programs, US Department of Labor. [FR Doc. 2018–13438 Filed 6–21–18; 8:45 am] BILLING CODE 4510–CR–P NUCLEAR REGULATORY COMMISSION [Docket No. 40–8943–MLA; ASLBP No. 07– 859–03–MLA–BD01] Crow Butte Resources, Inc. (North Trend Expansion Project); Notice of Atomic Safety and Licensing Board Reconstitution Pursuant to 10 CFR 2.313(c) and 2.321(b), the Atomic Safety and Licensing Board in the above-captioned North Trend Expansion Project license amendment proceeding is hereby reconstituted as follows: Administrative Judge Richard E. Wardwell is appointed to serve in place of Administrative Judge Frederick W. Oliver, who will retire at the end of this month; and Administrative Judge Nicholas G. Trikouros is appointed to serve in place of Administrative Judge Richard F. Cole, who passed away in December 2014.1 All correspondence, documents, and other materials shall continue to be filed in accordance with the NRC E-Filing rule. See 10 CFR 2.302 et seq. Rockville, Maryland, June 18, 2018. Edward R. Hawkens, Chief Administrative Judge, Atomic Safety and Licensing Board Panel. in ADAMS under Accession No. ML18103A252. Description of amendment request: The amendment request proposes to change Technical Specifications (TSs) Limiting Condition for Operation 3.5.5 to not require the Passive Residual Heat Removal Heat Exchanger to be operable in Mode 5 during vacuum fill operations. Additionally, the requested amendment proposes to change Surveillance Requirement (SR) 3.5.7.1 regarding operability requirements for the In-containment Refueling Water Storage Tank and associated flow paths and proposes to add an additional SR 3.5.7.2 to address operability requirements that are not required during vacuum fill operations. Finally, the requested amendment proposes conforming changes to the Updated Final Safety Analysis Report, Appendix 19E, Subsection 2.3.2.4.’’ [FR Doc. C1–2018–12506 Filed 6–21–18; 8:45 am] BILLING CODE 1301–00–D NUCLEAR REGULATORY COMMISSION [Docket Nos. 52–025 and 52–026; NRC– 2008–0252] Southern Nuclear Operating Company, Inc.; Vogtle Electric Generating Plant, Units 3 and 4; Improvements to Main Control Room Post-Accident Radiological Consequences Nuclear Regulatory Commission. ACTION: Exemption and combined license amendment; issuance. AGENCY: [FR Doc. 2018–13387 Filed 6–21–18; 8:45 am] BILLING CODE 7590–01–P The U.S. Nuclear Regulatory Commission (NRC) is granting an exemption to allow a departure from the certification information of Tier 1 of the generic AP1000 design control document (DCD) and is issuing License Amendment Nos. 123 and 122 to Combined Licenses (COL), NPF–91 and NPF–92, respectively. The COLs were issued to Southern Nuclear Operating Company, Inc., and Georgia Power Company, Oglethorpe Power Corporation, MEAG Power SPVM, LLC, MEAG Power SPVJ, LLC, MEAG Power SPVP, LLC, and the City of Dalton, Georgia (the licensee); for construction and operation of the Vogtle Electric Generating Plant (VEGP) Units 3 and 4, located in Burke County, Georgia. The granting of the exemption allows the changes to Tier 1 information that is requested in the amendment. Because the acceptability of the exemption was determined in part by the acceptability of the amendment, the exemption and SUMMARY: NUCLEAR REGULATORY COMMISSION [NRC–2018–0114] daltland on DSKBBV9HB2PROD with NOTICES Biweekly Notice; Applications and Amendments to Facility Operating Licenses and Combined Licenses Involving No Significant Hazards Considerations Correction In Notice document 2018–12506 beginning on page 28456 in the issue of Tuesday, June 19, 2018, make the following correction: On page 28464, in the second column, the seventh and eighth paragraphs should read as follows: ‘‘Date of amendment request: April 13, 2018. A publicly-available version is 1 Only two judges have been sitting on this Licensing Board since Judge Cole’s passing. This Notice restores the number of sitting judges to three. VerDate Sep<11>2014 17:16 Jun 21, 2018 Jkt 244001 PO 00000 Frm 00057 Fmt 4703 Sfmt 4703 amendment are being issued concurrently. DATES: The exemption and amendment were issued on April 20, 2018. ADDRESSES: Please refer to Docket ID NRC–2008–0252 when contacting the NRC about the availability of information regarding this document. You may access information related to this document, which the NRC possesses and is publicly available, using any of the following methods: • Federal Rulemaking website: Go to https://www.regulations.gov and search for Docket ID NRC–2008–0252. Address questions about NRC dockets to Jennifer Borges; 301–287–9127; email: Jennifer.Borges@nrc.gov. For technical questions, contact the individual listed in the FOR FURTHER INFORMATION CONTACT section of this document. • NRC’s Agencywide Documents Access and Management System (ADAMS): You may access publicly available documents online in the NRC Library at https://www.nrc.gov/readingrm/adams.html. To begin the search, select ‘‘ADAMS Public Documents’’ and then select ‘‘Begin Web-based ADAMS Search.’’ For problems with ADAMS, please contact the NRC’s Public Document Room (PDR) reference staff at 1–800–397–4209, 301–415–4737, or by email to pdr.resource@nrc.gov. The ADAMS accession number for each document referenced (if that document is available in ADAMS) is provided the first time that a document is referenced. The request for the amendment and exemption was submitted by letter dated August 31, 2017 (ADAMS Accession No. ML17243A352) and supplemented by letters dated February 9, 2018 and March 8, 2018 (ADAMS Accession Nos. ML18040A488 and ML18067A648). • NRC’s PDR: You may examine and purchase copies of public documents at the NRC’s PDR, Room O1–F21, One White Flint North, 11555 Rockville Pike, Rockville, Maryland 20852. FOR FURTHER INFORMATION CONTACT: Paul Kallan, Office of New Reactors, U.S. Nuclear Regulatory Commission, Washington, DC 20555–0001; telephone: 301–415–2809; email: Paul.Kallan@ nrc.gov. SUPPLEMENTARY INFORMATION: I. Background The NRC is granting exemptions from paragraph B of section III, ‘‘Scope and Contents,’’ of appendix D, ‘‘Design Certification Rule for the AP1000,’’ to part 52 of title 10 of the Code of Federal Regulations (10 CFR) and issuing License Amendment Nos. 123 and 122 to COLs, NPF–91 and NPF–92, E:\FR\FM\22JNN1.SGM 22JNN1 daltland on DSKBBV9HB2PROD with NOTICES Federal Register / Vol. 83, No. 121 / Friday, June 22, 2018 / Notices respectively, to the licensee. The exemptions are required by paragraph A.4 of section VIII, ‘‘Processes for Changes and Departures,’’ appendix D, to 10 CFR part 52 to allow the licensee to depart from Tier 1 information. With the requested amendment, the licensee proposes to departs from Tier 2 information in the Updated Final Safety Analysis Report (which includes the plant-specific Design Control Document (DCD) Tier 2 information) and involves related changes to plant-specific Tier 1 (and associated COL Appendix C) information, and COL Appendix A Technical Specifications. Specifically, the amendment changes the plantspecific nuclear island non-radioactive ventilation system, the main control room emergency habitability system, and post-accident operator dose analyses. These changes maintain compliance with General Design Criterion (19), which requires that main control room personnel dose does not exceed 5 roentgen equivalent man (rem) total effective dose equivalent for the duration of a design basis accident. Part of the justification for granting the exemptions was provided by the review of the amendments. Because the exemption is necessary in order to issue the requested license amendment, the NRC granted the exemptions and issued the amendments concurrently, rather than in sequence. This included issuing a combined safety evaluation containing the NRC staff’s review of both the exemption request and the license amendment. The exemptions met all applicable regulatory criteria set forth in 10 CFR 50.12, 10 CFR 52.7, and Section VIII.A.4 of appendix D to 10 CFR part 52. The license amendments were found to be acceptable as well. The combined safety evaluation is available in ADAMS under Accession No. ML18085A628. Identical exemption documents (except for referenced unit numbers and license numbers) were issued to the licensee for VEGP Units 3 and 4 (COLs NPF–91 and NPF–92). The exemption documents for VEGP Units 3 and 4 can be found in ADAMS under Accession Nos. ML18085A622 and ML18085A623, respectively. The exemption is reproduced (with the exception of abbreviated titles and additional citations) in Section II of this document. The amendment documents for COLs NPF–91 and NPF–92 are available in ADAMS under Accession Nos. ML18085A624 and ML18085A626, respectively. A summary of the amendment documents is provided in Section III of this document. VerDate Sep<11>2014 17:16 Jun 21, 2018 Jkt 244001 II. Exemption Reproduced below is the exemption document issued to VEGP, Units 3 and Unit 4. It makes reference to the combined safety evaluation that provides the reasoning for the findings made by the NRC (and listed under Item 1) in order to grant the exemption: 1. In a letter dated August 31, 2017, and supplemented by letters dated February 9, 2018, and March 8, 2018, the licensee requested from the Commission an exemption from the provisions of 10 CFR part 52, appendix D, section III.B, as part of license amendment request (LAR) 17–023, ‘‘Improvements to Main Control Room Post-Accident Radiological Consequences.’’ For the reasons set forth in Section 3.1, ‘‘Evaluation of Exemption,’’ of the NRC staff’s safety evaluation, which can be found in ADAMS under Accession No. ML18085A628, the Commission finds that: A. The exemption is authorized by law; B. The exemption presents no undue risk to public health and safety; C. The exemption is consistent with the common defense and security; D. Special circumstances are present in that the application of the rule in this circumstance is not necessary to serve the underlying purpose of the rule; E. The special circumstances outweigh any decrease in safety that may result from the reduction in standardization caused by the exemption; and F. The exemption will not result in a significant decrease in the level of safety otherwise provided by the design. 2. Accordingly, the licensee is granted an exemption from the certified DCD Tier 1 information, with corresponding changes to Appendix C of the Facility Combined Licenses as described in the licensee’s request dated August 31, 2017, as supplemented by letters dated February 9, 2018, and March 8, 2018. This exemption is related to, and necessary for, the granting of License Amendment Nos. 123 and 122, which is being issued concurrently with this exemption. 3. As explained in Section 5.0, ‘‘Environmental Consideration,’’ of the NRC staff’s safety evaluation (ADAMS Accession No. ML18085A628), this exemption meets the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Therefore, pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment needs to be prepared in connection with the issuance of the exemption. PO 00000 Frm 00058 Fmt 4703 Sfmt 9990 29145 4. These exemptions are effective as of the date of its issuance. III. License Amendment Request By letter dated August 31, 2017, and supplemented by letters dated February 9, 2018, and March 8, 2018, the licensee requested that the NRC amend the COLs for VEGP, Units 3 and 4, COLs NPF–91 and NPF–92. The proposed amendment is described in Section I of this Federal Register notice. The Commission has determined for these amendments that the application complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission’s rules and regulations. The Commission has made appropriate findings as required by the Act and the Commission’s rules and regulations in 10 CFR chapter I, which are set forth in the license amendment. A notice of consideration of issuance of amendment to facility operating license or combined license, as applicable, proposed no significant hazards consideration determination, and opportunity for a hearing in connection with these actions, was published in the Federal Register on October 24, 2017 (82 FR 49234). No comments were received during the 30day comment period. The Commission has determined that these amendments satisfy the criteria for categorical exclusion in accordance with 10 CFR 51.22. Therefore, pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared for these amendments. IV. Conclusion Using the reasons set forth in the combined safety evaluation, the staff granted the exemption and issued the amendment that the licensee requested on August 31, 2017, and supplemented on February 9, 2018 and March 8, 2018. The exemptions and amendments were issued on April 20, 2018, as part of a combined package to the licensee (ADAMS Accession No. ML18085A620). Dated at Rockville, Maryland, this 19th day of June 2018. For the Nuclear Regulatory Commission. Jennifer L. Dixon-Herrity, Chief, Licensing Branch 4, Division of Licensing, Siting, and Environmental Analysis, Office of New Reactors. [FR Doc. 2018–13404 Filed 6–21–18; 8:45 am] BILLING CODE 7590–01–P E:\FR\FM\22JNN1.SGM 22JNN1

Agencies

[Federal Register Volume 83, Number 121 (Friday, June 22, 2018)]
[Notices]
[Pages 29144-29145]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2018-13404]


-----------------------------------------------------------------------

NUCLEAR REGULATORY COMMISSION

[Docket Nos. 52-025 and 52-026; NRC-2008-0252]


Southern Nuclear Operating Company, Inc.; Vogtle Electric 
Generating Plant, Units 3 and 4; Improvements to Main Control Room 
Post-Accident Radiological Consequences

AGENCY: Nuclear Regulatory Commission.

ACTION: Exemption and combined license amendment; issuance.

-----------------------------------------------------------------------

SUMMARY: The U.S. Nuclear Regulatory Commission (NRC) is granting an 
exemption to allow a departure from the certification information of 
Tier 1 of the generic AP1000 design control document (DCD) and is 
issuing License Amendment Nos. 123 and 122 to Combined Licenses (COL), 
NPF-91 and NPF-92, respectively. The COLs were issued to Southern 
Nuclear Operating Company, Inc., and Georgia Power Company, Oglethorpe 
Power Corporation, MEAG Power SPVM, LLC, MEAG Power SPVJ, LLC, MEAG 
Power SPVP, LLC, and the City of Dalton, Georgia (the licensee); for 
construction and operation of the Vogtle Electric Generating Plant 
(VEGP) Units 3 and 4, located in Burke County, Georgia.
    The granting of the exemption allows the changes to Tier 1 
information that is requested in the amendment. Because the 
acceptability of the exemption was determined in part by the 
acceptability of the amendment, the exemption and amendment are being 
issued concurrently.

DATES: The exemption and amendment were issued on April 20, 2018.

ADDRESSES: Please refer to Docket ID NRC-2008-0252 when contacting the 
NRC about the availability of information regarding this document. You 
may access information related to this document, which the NRC 
possesses and is publicly available, using any of the following 
methods:
     Federal Rulemaking website: Go to https://www.regulations.gov and search for Docket ID NRC-2008-0252. Address 
questions about NRC dockets to Jennifer Borges; 301-287-9127; email: 
[email protected]. For technical questions, contact the 
individual listed in the FOR FURTHER INFORMATION CONTACT section of 
this document.
     NRC's Agencywide Documents Access and Management System 
(ADAMS): You may access publicly available documents online in the NRC 
Library at https://www.nrc.gov/reading-rm/adams.html. To begin the 
search, select ``ADAMS Public Documents'' and then select ``Begin Web-
based ADAMS Search.'' For problems with ADAMS, please contact the NRC's 
Public Document Room (PDR) reference staff at 1-800-397-4209, 301-415-
4737, or by email to [email protected]. The ADAMS accession number 
for each document referenced (if that document is available in ADAMS) 
is provided the first time that a document is referenced. The request 
for the amendment and exemption was submitted by letter dated August 
31, 2017 (ADAMS Accession No. ML17243A352) and supplemented by letters 
dated February 9, 2018 and March 8, 2018 (ADAMS Accession Nos. 
ML18040A488 and ML18067A648).
     NRC's PDR: You may examine and purchase copies of public 
documents at the NRC's PDR, Room O1-F21, One White Flint North, 11555 
Rockville Pike, Rockville, Maryland 20852.

FOR FURTHER INFORMATION CONTACT: Paul Kallan, Office of New Reactors, 
U.S. Nuclear Regulatory Commission, Washington, DC 20555-0001; 
telephone: 301-415-2809; email: [email protected].

SUPPLEMENTARY INFORMATION:

I. Background

    The NRC is granting exemptions from paragraph B of section III, 
``Scope and Contents,'' of appendix D, ``Design Certification Rule for 
the AP1000,'' to part 52 of title 10 of the Code of Federal Regulations 
(10 CFR) and issuing License Amendment Nos. 123 and 122 to COLs, NPF-91 
and NPF-92,

[[Page 29145]]

respectively, to the licensee. The exemptions are required by paragraph 
A.4 of section VIII, ``Processes for Changes and Departures,'' appendix 
D, to 10 CFR part 52 to allow the licensee to depart from Tier 1 
information. With the requested amendment, the licensee proposes to 
departs from Tier 2 information in the Updated Final Safety Analysis 
Report (which includes the plant-specific Design Control Document (DCD) 
Tier 2 information) and involves related changes to plant-specific Tier 
1 (and associated COL Appendix C) information, and COL Appendix A 
Technical Specifications. Specifically, the amendment changes the 
plant-specific nuclear island non-radioactive ventilation system, the 
main control room emergency habitability system, and post-accident 
operator dose analyses. These changes maintain compliance with General 
Design Criterion (19), which requires that main control room personnel 
dose does not exceed 5 roentgen equivalent man (rem) total effective 
dose equivalent for the duration of a design basis accident.
    Part of the justification for granting the exemptions was provided 
by the review of the amendments. Because the exemption is necessary in 
order to issue the requested license amendment, the NRC granted the 
exemptions and issued the amendments concurrently, rather than in 
sequence. This included issuing a combined safety evaluation containing 
the NRC staff's review of both the exemption request and the license 
amendment. The exemptions met all applicable regulatory criteria set 
forth in 10 CFR 50.12, 10 CFR 52.7, and Section VIII.A.4 of appendix D 
to 10 CFR part 52. The license amendments were found to be acceptable 
as well. The combined safety evaluation is available in ADAMS under 
Accession No. ML18085A628.
    Identical exemption documents (except for referenced unit numbers 
and license numbers) were issued to the licensee for VEGP Units 3 and 4 
(COLs NPF-91 and NPF-92). The exemption documents for VEGP Units 3 and 
4 can be found in ADAMS under Accession Nos. ML18085A622 and 
ML18085A623, respectively. The exemption is reproduced (with the 
exception of abbreviated titles and additional citations) in Section II 
of this document. The amendment documents for COLs NPF-91 and NPF-92 
are available in ADAMS under Accession Nos. ML18085A624 and 
ML18085A626, respectively. A summary of the amendment documents is 
provided in Section III of this document.

II. Exemption

    Reproduced below is the exemption document issued to VEGP, Units 3 
and Unit 4. It makes reference to the combined safety evaluation that 
provides the reasoning for the findings made by the NRC (and listed 
under Item 1) in order to grant the exemption:
    1. In a letter dated August 31, 2017, and supplemented by letters 
dated February 9, 2018, and March 8, 2018, the licensee requested from 
the Commission an exemption from the provisions of 10 CFR part 52, 
appendix D, section III.B, as part of license amendment request (LAR) 
17-023, ``Improvements to Main Control Room Post-Accident Radiological 
Consequences.''
    For the reasons set forth in Section 3.1, ``Evaluation of 
Exemption,'' of the NRC staff's safety evaluation, which can be found 
in ADAMS under Accession No. ML18085A628, the Commission finds that:
    A. The exemption is authorized by law;
    B. The exemption presents no undue risk to public health and 
safety;
    C. The exemption is consistent with the common defense and 
security;
    D. Special circumstances are present in that the application of the 
rule in this circumstance is not necessary to serve the underlying 
purpose of the rule;
    E. The special circumstances outweigh any decrease in safety that 
may result from the reduction in standardization caused by the 
exemption; and
    F. The exemption will not result in a significant decrease in the 
level of safety otherwise provided by the design.
    2. Accordingly, the licensee is granted an exemption from the 
certified DCD Tier 1 information, with corresponding changes to 
Appendix C of the Facility Combined Licenses as described in the 
licensee's request dated August 31, 2017, as supplemented by letters 
dated February 9, 2018, and March 8, 2018. This exemption is related 
to, and necessary for, the granting of License Amendment Nos. 123 and 
122, which is being issued concurrently with this exemption.
    3. As explained in Section 5.0, ``Environmental Consideration,'' of 
the NRC staff's safety evaluation (ADAMS Accession No. ML18085A628), 
this exemption meets the eligibility criteria for categorical exclusion 
set forth in 10 CFR 51.22(c)(9). Therefore, pursuant to 10 CFR 
51.22(b), no environmental impact statement or environmental assessment 
needs to be prepared in connection with the issuance of the exemption.
    4. These exemptions are effective as of the date of its issuance.

III. License Amendment Request

    By letter dated August 31, 2017, and supplemented by letters dated 
February 9, 2018, and March 8, 2018, the licensee requested that the 
NRC amend the COLs for VEGP, Units 3 and 4, COLs NPF-91 and NPF-92. The 
proposed amendment is described in Section I of this Federal Register 
notice.
    The Commission has determined for these amendments that the 
application complies with the standards and requirements of the Atomic 
Energy Act of 1954, as amended (the Act), and the Commission's rules 
and regulations. The Commission has made appropriate findings as 
required by the Act and the Commission's rules and regulations in 10 
CFR chapter I, which are set forth in the license amendment.
    A notice of consideration of issuance of amendment to facility 
operating license or combined license, as applicable, proposed no 
significant hazards consideration determination, and opportunity for a 
hearing in connection with these actions, was published in the Federal 
Register on October 24, 2017 (82 FR 49234). No comments were received 
during the 30-day comment period.
    The Commission has determined that these amendments satisfy the 
criteria for categorical exclusion in accordance with 10 CFR 51.22. 
Therefore, pursuant to 10 CFR 51.22(b), no environmental impact 
statement or environmental assessment need be prepared for these 
amendments.

IV. Conclusion

    Using the reasons set forth in the combined safety evaluation, the 
staff granted the exemption and issued the amendment that the licensee 
requested on August 31, 2017, and supplemented on February 9, 2018 and 
March 8, 2018.
    The exemptions and amendments were issued on April 20, 2018, as 
part of a combined package to the licensee (ADAMS Accession No. 
ML18085A620).

    Dated at Rockville, Maryland, this 19th day of June 2018.

    For the Nuclear Regulatory Commission.
Jennifer L. Dixon-Herrity,
Chief, Licensing Branch 4, Division of Licensing, Siting, and 
Environmental Analysis, Office of New Reactors.
[FR Doc. 2018-13404 Filed 6-21-18; 8:45 am]